JOB #4-15-005 Revised Plans received 11/06/2015

JOB #4-15-005 Revised Plans received 11/06/2015
TITLE/SITE
T1.0
TITLE SHEET
LEGAL JURISDICTION: STATE OF LOUISIANA STATE FIRE MARSHAL & CITY OF MINDEN BUILDING DEPARTMENT
BUILDING CODE:
IBC 2012, 2013 LSPC, IMC 2012, NEC 2011, 2009 NFPA 1010, 2012 IFGC, 2013 LSSC, 2010 ADA-ABA
DEMOLITION
N
O
I
T
C
Y
U
L
R
N
T
O
S
S
N
E
O
S
C
O
D
P
R
R
A
U
N
P
I
U
D
I
O
B
H
C OR
F
ACCESSIBILITY GUIDELINESTENANT
AREA:
D1.0
2,419 S.F. (INCLUDING 144 S.F. WALK-IN COOLER/FREEZER)
SEATING:
TYPE CONSTRUCTION: EXISTING SHELL
II-B, SPRINKLERED
EXISTING BUILDING IS TYPE M-MERCANTILE, ENTIRE BUILDING SQUARE FOOTAGE: APPROX. 28,000 SQ. FT.
TABLE 503: TYPE III-B ALLOWABLE HEIGHT/AREA: 4 STORIES, 19,000 SQ. FT.
TABLE 508.3.3 REQUIRED SEPARATION OF OCCUPANCIES:
PROPOSED: EXISTING 1 HOUR SEPARATION PROVIDED, SPRINKLERS PROVIDED.
SECTION 903.2.6 GROUP M: AN AUTOMATIC SPRINKLER SYSTEM SHALL BE PROVIDED THROUGH BUILDING
CONTAINING A GROUP M OCCUPANCY WHERE ONE OF THE FOLLOWING CONDITIONS EXISTS:
1. WHERE A GROUP B FIRE AREA EXCEEDS 12,000 SQUARE FEET.
2. WHERE A GROUP B FIRE AREA IS LOCATED MORE THAN THREE STORIES ABOVE GRADE PLANE; OR
3. WHERE THE COMBINED AREA OF ALL GROUP M FIRE AREAS ON ALL FLOORS, INCLUDING ANY MEZZANINES,
EXCEEDS 24,0000 SQUARE FEET.
AN AUTOMATIC SPRINKLER SYSTEM IS REQUIRED PER CODE AND IS EXISTING. SPRINKLER HEADS WITHIN PIZZA HUT
TENANT SPACE SHALL BE MODIFIED TO ADHERE TO THE NEW BUILDING LAYOUT.
TABLE 1004.1.1 MAXIMUM FLOOR AREA ALLOWANCE PER OCCUPANT
KITCHEN: 200 GROSS.
FLOOR AREA = 1,178 SQ. FT.
OCCUPANT LOAD: 1,178/ 200 = 6 OCCUPANTS
FLOOR AREA = 918 SQ. FT.
OCCUPANT LOAD: 918/ 15 = 62 OCCUPANTS
TOTAL OCCUPANT LOAD: 68 OCCUPANTS
UTILITIES:
25 PAIR CABLE IN 2" CONDUIT
ELECTRIC SERVICE:
ROOF FRAMING PLAN
SLAB AND FRAMING DETAILS
ARCHITECTURAL
A1.0
FLOOR PLAN
A1.1
DOOR AND WDW ELEVATION SCHEDULES
A2.0
EQUIPMENT PLAN
A2.1
EQUIPMENT SCHEDULE
A3.0
ROOF PLAN
A4.0
EXTERIOR ELEVATIONS
A5.0
WALL SECTIONS
A7.0
EXTERIOR CONSTRUCTION DETAILS
A8.0
FLOOR FINISH PLAN
A8.1
FINISH SCHEDULE
A9.0
REFLECTED CEILING PLAN
A10.0 INTERIOR ELEVATIONS - DINING
A10.1 INTERIOR ELEVATIONS - SERVICE
A10.2 INTERIOR ELEVATIONS - RESTROOMS
A10.3 METRO SHELVING ASSEMBLY AIDES
A11.0 INTERIOR CONSTRUCTION DETAILS
A11.1 MILLWORK DETAILS
A11.2 MILLWORK DETAILS
A11.3 INTERIOR DETAILS
ADA1.0 ACCESSIBILITY REQUIREMENTS
ADA1.1 ACCESSIBILITY REQUIREMENTS
M1.0
HVAC NOTES AND SCHEDULES
M2.0
M3.0
DUCT AND DIFFUSER PLAN
HOOD DWGS.
M3.1
M3.2
M4.0
M5.0
M5.1
HOOD DWGS.
HOOD DWGS.
MECHANICAL DETAILS
HVAC SPECIFICATIONS
HVAC SPECIFICATIONS
PLUMBING
400 AMPS / 3 PHASE / 120-208 VOLT
1,329.9 MBH
WATER PRESSURE:
S1.0
S2.0
MECHANICAL
SEATING: 15 SF PER OCCUPANT
# PHONE LINES:
520 South Main Street, Suite 2531
Akron, OH 44311
330.572.2100 Fax: 330.572.2102
STRUCTURAL
55
SECTION 302: OCCUPANCY CLASSIFICATION: PREVIOUS: M-MERCANTILE, PROPOSED: A-2 RESTAURANT
GAS:
DEMOLITION PLAN
45 - 60 PSI @ BLDG. POINT OF ENTRY
P1.0
PLUMBING SCHEDULE
P2.0
P3.0
P4.0
P5.0
P6.0
P7.0
WASTE & VENT PLAN
WATER & GAS PLAN
UNDERGROUND PLMB. ROUGH-IN
RISER DIAGRAMS
PLUMBING DETAILS
PEPSI PLATFORM
ELECTRICAL
PROJECT SUMMARY
A. ALL WORK SHALL CONFORM TO THE 2012 EDITION OF THE INTERNATIONAL BUILDING CODE, AND ALL OTHER
APPLICABLE CODES, STANDARDS, AND REGULATIONS OF THE CITY OF MINDEN, LA AND PARISH OF WEBSTER.
NAME
ROOM NAME
1
B. IT IS INTENDED THAT A COMPLETE OCCUPIABLE BUILDING PROJECT IS PROVIDED.
C. THE GENERAL CONDITIONS OF THE CONTRACT FOR CONSTRUCTION (A.I.A. LATEST EDITION) ARE A PART OF
THESE CONTRACT DOCUMENTS. A COPY IS ON FILE AT THE ARCHITECT'S OFFICE.
D. DO NOT SCALE THESE DRAWINGS. VERIFY ALL DIMENSIONS AND CONDITIONS IN THE FIELD. ANY
DISCREPANCIES IN THESE DRAWINGS SHALL BE BROUGHT TO THE ATTENTION OF THE ARCHITECT PRIOR TO
STARTING WORK.
G. G.C. SHALL PROVIDE EACH SUBCONTRACTOR WITH A COMPLETE AGENCY-PERMITTED DRAWING SET AT TIME
OF CONSTRUCTION.
H. IT IS THE G.C.'S RESPONSIBILITY TO CONFIRM THE AVAILABLE "RESIDUAL" WATER PRESSURE, PRIOR TO THE
START OF ANY WORK, AND NOTIFY THE OWNER IF THE AVAILABLE PRESSURE IS NOT ADEQUATE TO SERVICE
THE ANSUL SYSTEM OR OTHER PRESSURE SENSITIVE EQUIPMENT.
I.
G.C. SHALL CONFIRM MINIMUM RESIDUAL PRESSURE AVAILABLE AT HOOD ANSUL SYSTEM IS 33 PSI.
J. ALL ABBREVIATIONS INCLUDED FOLLOW INDUSTRY STANDARDS. CONTACT ARCHITECT IF ANY ABBREVIATIONS
ARE NOT CLEAR.
ELEV. LETTER
ELEV. SHEET
SHEET NUMBER
4
AX.X
X
WINDOW NUMBER / DECOR ITEM NUMBER
3
8'-4"
X
EXTERIOR WALL FINISH NUMBER
X
KEY NOTE
CEILING HEIGHT
BLDG. SECTION LETTER
X
AX.X
BLDG. SECTION SHEET
X-000
EQUIPMENT NUMBER
XX
ROOM FINISH NUMBER
X
INTERIOR ELEVATION DESIGNATION
DETAIL NUMBER
X
AX.X
DIRECTION OF DETAIL
DETAIL SHEET
X
0'-0"
ELEV
OWNER
CIVIL ENGINEER
Pizza Hut
7100 Corporate Drive
Plano, TX 75024
GPD GROUP
520 S. MAIN STREET, SUITE 2531
AKRON, OH 44311
CONTACT: ANTHONY BARCHANOWICZ
PHONE: 216.518.5544
DOOR NUMBER
2
ELEVATION NUMBER
E. ALL PROPOSED SUBSTITUTIONS SHALL BE APPROVED BY THE OWNER, IN WRITING, PRIOR TO INSTALLATION.
F. G.C. IS RESPONSIBLE FOR SUBMITTAL, PAYING FEES AND OBTAINING ALL PERMITS ASSOCIATED WITH THE
PROJECT EXCEPT GENERAL BUILDING PERMIT. THIS INCLUDES, BUT IS NOT LIMITED TO ELECTRICAL,
MECHANICAL, PLUMBING, FIRE SPRINKLER, HOOD ANSUL, OR OTHER RELATED FIRE PERMITS, ENCROACHMENT
PERMIT, ETC. OWNER WILL PAY FOR "CONNECTION FEES" ASSOCIATED WITH UTILITY PERMITS. G.C. REQUIRED
TO PAY FOR TEMPORARY FACILITIES FEES AS REQUIRED TO COMPLETE THE WORK IN A TIMELY MANNER.
X
AX.X
REVISION NUMBER
BLDG. HEIGHT
REFERENCE POINT
X
XXX 000
CONSTRUCTION MANAGER
MECH. / ELEC. ENGINEER
Pizza Hut
7100 Corporate Drive
Plano, TX 75024
Contact: John McCarthy
Phone: (407) 864-8260
GPD GROUP
520 S. MAIN STREET, SUITE 2531
AKRON, OH 44311
CONTACT: ANTHONY BARCHANOWICZ
PHONE: 216.518.5544
ARCHITECT
STRUCTURAL ENGINEER
GPD GROUP
520 S. MAIN STREET, SUITE 2531
AKRON, OH 44311
CONTACT: ANTHONY BARCHANOWICZ
PHONE: 216.518.5544
GPD GROUP
520 S. MAIN STREET, SUITE 2531
AKRON, OH 44311
CONTACT: ANTHONY BARCHANOWICZ
PHONE: 216.518.5544
E2.0
E3.0
E4.0
E4.1
E5.0
E6.0
POWER /ROOF PLAN
LIGHTING PLAN & SCHEDULE
TELECOM PLAN
POWER ROUGH-IN PLAN
PANEL SCHEDULE AND RISER DIAGRAM
ELECTRICAL DETAILS
SHEET INDEX
CONTRACT DATE:
SHEAR WALL TYPE (STRUCTURAL)
EQUIPMENT / FIXTURE NUMBER (M.E.P.)
L. ALL CONTRACTORS SHALL VISIT THE SITE TO BECOME FAMILIAR WITH CONDITIONS AFFECTING THE SCOPE OF
WORK. NO CONTRACT ADJUSTMENTS WILL BE PERMITTED DUE TO THE LACK OF KNOWLEDGE OF SITE
CONDITIONS.
JOB #4-15-005
Revised Plans received
11/06/2015
DBR 37
PLAN VERSION:
009.00.00
311465 / 434385
STORE NUMBER:
GENERAL DRAWING SYMBOLS
K. GRAPHIC AND WRITTEN INFORMATION ON DRAWINGS SHALL BE COORDINATED
WITH ALL TRADES PRIOR TO INSTALLATION.
BUILDING TYPE:
SITE NUMBER:
REFER TO STRUCTURAL, MECHANICAL, PLUMBING AND ELECTRICAL SHEETS FOR SPECIFIC SYMBOLS
09.21.15
PROJECT DIRECTORY
GAS
BUILDING DEPARTMENT
CENTERPOINT
318.382.0315
CITY OF MINDEN
520 BROADWAY
MINDEN, LA 71058
BRENT COOLEY
318.371.4215
ELECTRIC
HEALTH DEPARTMENT
520 BROADWAY
MINDEN, LA 71055
CITY OF MINDEN
GARY MORLEN
318-453-7726
WEBSTER PARISH HEALTH UNIT
1200 HOMER ROAD,
MINDEN, LA 71055
FLOYDE SMITH
318.371.3030
2015388.14
PIZZA HUT
123 Minden Shopping Dr.
Minden, LA 71055
DBR 37
TITLE SHEET
T1.0
NOTE: HATCHED AREA INDICATES PROPOSED PIZZA HUT TENANT SPACE.
PROJECT GENERAL NOTES
VICINITY MAP
UTILITY CONTACTS
KEY PLAN
PLOT DATE:
N
O
I
T
C
Y
U
L
R
N
T
O
S
S
N
E
O
S
C
O
D
P
R
R
A
U
N
P
I
U
D
I
O
B
H
C OR
F
520 South Main Street, Suite 2531
Akron, OH 44311
330.572.2100 Fax: 330.572.2102
EXIST. DEMISED WALL V.I.F.
EXIST. 8" CMU
WALL V.I.F.
EXIST. 4x4
COL V.I.F.
EXHAUST FANSEE MECH
RESTROOM
EXHAUST FANSEE MECH
(BELOW)
(BELOW)
(2) 2X4
(BELOW)
JOIST REINF. REQ'DSEE 8/S2.0
RTU-2
1300 lbs
9
S2.0
(2) 2X4
(BELOW)
(2) 2X4
(BELOW)
HSS4X2X41 LSH
(BELOW)
(2) 2X4
HSS4X2X41 LSH
(2) 2X4
HSS4X2X41 LSH
HSS4X2X41 LSH
HSS4X2X41 LSH
(2) 2X4
(BELOW)
(2) 2X4
V.I.F. ANY DISCREPANCIES WITH ASSUMPTIONS MADE
RESTROOM
EXHAUST FANSEE MECH
(BELOW)
(2) 2X4
EXIST. 20" DEEP OPEN WEB JOISTS @ 5'-0" o.c. (20k5 ASSUMED)
EXIST. W18 V.I.F. (W18X46 ASSUMED)
EXHAUST FANSEE MECH
(2) 2X4
EXIST. W18 V.I.F. (W18X46 ASSUMED)
8
S2.0
V.I.F. ANY DISCREPANCIES WITH ASSUMPTIONS MADE
RTU-1
2500 lbs
TYP
SEE 5/S2.0 FOR
DECK SUPPORT @
NEW OPENING
EXIST. 24" DEEP OPEN WEB JOISTS @ 5'-0" o.c. (24k7 ASSUMED)
JOIST REINF. REQ'DSEE 8/S2.0
V.I.F. ANY DISCREPANCIES WITH ASSUMPTIONS MADE
29'-11" V.I.F.
EXIST. 12" DEEP OPEN WEB JOISTS @ 5'-0" o.c.
EXHAUST FANSEE MECH
HSS4X2X41 LSH
EXIST. 4x4
COL V.I.F.
(BELOW)
(2) 2X4
(BELOW)
EXIST. 8" CMU
WALL V.I.F.
EXIST. 4x4 COL VERIFY
5
THICKNESS 16
" MIN.
5
(HSS4X4X16 ASSUMED)
10
8"
EXIST. 8" CMU
WALL V.I.F.
EXIST. 4x4
COL V.I.F.
S2.0
W16X50+3/8" PL
W16X31+3/8" PL
B/STL EL.+10'-2"
B/STL EL.+10'-2"
10
3
S2.0
8"
24'-0" V.I.F.
S2.0
25'-421" V.I.F.
OPP. HAND
18'-621" V.I.F.
EXIST. 8" CMU
WALL V.I.F.
3
S2.0
12'-3" V.I.F.
CONTRACT DATE:
WALL FRAMING PLAN
A.
B.
GENERAL PROVISIONS:
PROVIDE TEMPORARY SHORING AS REQUIRED DURING REINFORCING
OF EXISTING JOISTS.
THIS STRUCTURE HAS BEEN MODIFIED IN ACCORDANCE WITH THE 2012
INTERNATIONAL BUILDING CODE. MATERIALS AND SERVICES PROVIDED
BY THE CONTRACTOR SHALL CONFORM TO THE ABOVE MENTIONED
CODES AND THE CONTRACT SPECIFICATIONS.
REMOVE LIVE LOAD FROM ROOF PRIOR TO AND DURING
REINFORCEMENT OF EXISTING JOISTS.
C.
IF SECTION OF EXISTING BRIDGING REMOVED: ADD CROSS BRIDGING
ON EITHER SIDE OF REMOVED SECTION.
D.
SEE "B" THIS SHEET FOR GENERAL STRUCTURAL NOTES.
STRUCTURAL STEEL:
WIDE FLANGE:
ASTM A992 UNO
PLATE, ANGLES, CHANNELS: ASTM A36 UNO
TUBES:
ASTM A500 GRADE B (Fy=46 ksi)
DETAILING, FABRICATION, AND ERECTION SHALL CONFORM
EXISTING ROOF CONSTRUCTION SHOWN ON THE DRAWINGS IS BASED ON WITH THE AISC "STEEL CONSTRUCTION MANUAL", 13TH
A SITE SURVEY AND PHOTOS PERFORMED BY GPD GROUP. CONTRACTOR EDITION AND THE "CODE OF STANDARD PRACTICE FOR STEEL
BUILDINGS AND BRIDGES" EXCEPT SECTION 4.2 OF THE CODE
SHALL FIELD VERIFY ALL THE DIMENSIONS AND ALL EXISTING
WHICH SHALL NOT BE APPLICABLE TO THIS PROJECT.
CONSTRUCTION CONDITIONS PRIOR TO STEEL FABRICATION OR
ORDERING MATERIALS AND COORDINATE ANY DISCREPANCIES WITH THE
HOT-DIP GALVANIZING SHALL CONFORM WITH ASTM A123
ENGINEER.
THE EXISTING ROOF CONSTRUCTION CONSISTS OF A MEMBRANE ROOF
OVER RIGID INSULATION OVER 134" NARROW RIBBED METAL DECK OVER
OPEN WEB METAL JOISTS (SEE PLAN FOR SPACING). FIELD VERIFY JOIST
SIZE, OVERALL SPAN, AND DECK TYPE AND COORDINATE DISCREPANCIES
WITH ENGINEER PRIOR TO ORDERING MATERIALS.
GENERAL CONTRACTOR SHALL VERIFY ALL MECHANICAL
EQUIPMENT LOCATIONS, OPENING DIMENSIONS AND
WEIGHTS PRIOR TO STRUCTURAL STEEL FABRICATION.
NOTIFY ENGINEER IF DIFFERENT FROM THAT SHOWN ON
DRAWINGS.
TOP OF EXISTING FLOOR SLAB = 0'-0". ALL OTHER ELEVATIONS ARE
REFERENCED FROM THIS ELEVATION.
ALL WELDING SHALL BE DONE USING E-70XX ELECTRODES IN
ACCORDANCE WITH THE LATEST AWS SPECIFICATIONS.
SEE ARCH. DRAWINGS FOR DIMENSIONS NOT SHOWN.
FIELD VERIFY ALL CONDITIONS AT AND CONNECTIONS TO THE
EXISTING CONSTRUCTION BEFORE FABRICATION.
WHERE EXISTING CONDITIONS ARE CUT OR DISTURBED TO PERMIT
INSTALLATION OF NEW WORK, MATCH AND PATCH EXISTING DISTURBED
CONSTRUCTION TO ORIGINAL CONDITION.
PRIME ALL STEEL NOT IN CONTACT WITH CONCRETE.
CONCRETE
WOOD:
CONCRETE SHALL BE HARD ROCK CONC. (5 SACK CEMENT PER CU.YD. MIN.) AND MEET THE
FOLLOWING MIN. ULTIMATE COMPRESSIVE STRENGTHS AT 28 DAYS:
MATERIALS
a. FRAMING LUMBER 2X6 AND LARGER SHALL BE SOUTHERN PINE NO. 1 USED
AT A MAXIMUM MOISTURE CONTENT OF 19% WITH THE FOLLOWING MINIMUM
ALLOWABLE STRESSES:
Fb=1,650 PSI
Fv= 90 PSI
Fc=1,750 PSI
E=1,700,000 PSI
LOCATION
MIN. STRENGTH
28 DAYS PSI
AGGREGATE
SIZE - INCHESS
SLUMP
INCHES
TOLERANCE
CONCRETE MIX DESIGN AND TESTING SHALL MEET WITH THESE SPECS. CEMENT SHALL BE IN
ACCORDANCE WITH ASTM C 150 TYPE II. VERIFY MIN. CONC. STRENGTH AND CEMENT TYPE.
REINFORCING STEEL SHALL CONFORM TO ASTM A-615, GRADE 60. STEEL SHALL BE KEPT
CLEAN AND FREE OF RUST.
DETAIL, FABRICATE AND ERECT STRUCTURAL WOOD IN ACCORDANCE WITH THE
LATEST EDITON WITH THE NANTIONAL DESIGN SPECIFICATION FOR WOOD
CONSTUCTION.
WELDED WIRE REINFORCEMENT SHALL CONFORM TO ASTM A-185.
ALL WOOD IN CONTACT WITH CONCRETE OR STEEL SHALL BE PERSERVATIVE
TREATED.
CONCRETE CURING SHALL BE IN ACCORDANCE WITH REQUIREMENTS OF ACI-318-08 SECTION
5.11 AND STANDARD PRACTICE FOR CURING CONCRETE REPORTED BY COMMITTEE 308.
ALL BEAMS AND JOISTS SHALL BE CUT FOR FULL UNIFORM BEARING AT
SUPPORTS.
1/4"=1'-0"
A
DESIGN LOADS:
09.21.15
BUILDING TYPE:
DBR 37
PLAN VERSION:
009.00.00
SITE NUMBER:
311465 / 434385
STORE NUMBER:
A. ROOF LIVE LOAD
20 PSF
B. ROOF SNOW LOADS
GROUND SNOW LOAD (Pg)
5 PSF
EXPOSURE FACTOR (Ce)
0.9
IMPORTANCE FACTOR (I)
1.0
FLAT ROOF SNOW LOAD (Pf)
5 PSF MIN.
THERMAL FACTOR (Ct)
1.0
C. WIND LOADS
3 SECOND GUST
90 MPH
IMPORTANCE FACTOR
1.0
EXPOSURE CATEGORY
C
E. SEISMIC LOADS
ANALYSIS NOT REQUIRED PER INTERNATIONAL BUILDING CODE 3404.4
2015388.14
PIZZA HUT
123 Minden Shopping Dr.
Minden, LA 71055
DBR 37
ALL WOOD CONSTRUCTION CONNECTORS SHALL BE MANUFACTURED BY
SIMPSON STRONG-TIE COMPANY AND SHALL BE FASTENED PER THE
MANUFACTURER'S RECOMMENDATIONS.
ROOF FRAMING
PLAN
S1.0
GENERAL SHEET NOTES
C
GENERAL STRUCTURAL NOTES
B
PLOT DATE:
3x3x1/4" ANGLE, TYP. PROVIDE ANGLES
AS REQUIRED TO FRAME OPENING.
PROVIDE JOIST STRUT AS REQUIRED. SEE
TYPICAL JOIST LOAD STRUT DETAIL.
1
2"
EXPANSION JOINT
MATERIAL
#4 DOWEL 1'-0"x1'-0" LG
@16" O.C.
#4 DOWEL 1'-0" LG
@16" O.C. WITH HILTI
HIT-HY200ADHESIVE
6" MIN EMBED.
#4 DOWEL 1'-0" LG
@16" O.C. WITH HILTI
HIT-HY70 ADHESIVE 6"
MIN EMBED.
N
O
I
T
C
Y
U
L
R
N
T
O
S
S
N
E
O
S
C
O
D
P
R
R
A
U
N
P
I
U
D
I
O
B
H
C OR
F
3/16
"E"
"E"
T/FND WALL
EL. -0'-8"
JOIST
JOIST
PLAN VIEW
11
2
EX. FOOTING
WHERE DIMENSION "E" IS LESS THAN 6" ANGLE MAY BE OMITTED.
EXIST. ROOF DECK
3/16
REMOVE TOP
COURSE OF WALL
EX. CMU (ASSUMED)
FOUNDATION
WALL GROUT SOLID IF
NOT GROUTED
NOTE:
TYPICAL ROOF OPENING DETAIL SHOWN APPLIES TO ALL ROOF
OPENINGS WHERE LEAST DIMENSION IS 12" OR LARGER.
REINFORCE ROOF OPENINGS LESS THAN 12" BY WELDING 16 GA.
SHEET METAL 1'-0" WIDER THAN OPENING TO METAL ROOF DECK.
NOT USED
520 South Main Street, Suite 2531
Akron, OH 44311
330.572.2100 Fax: 330.572.2102
T/SLAB
EL. 0'-0"
6"
TYP.
EX. SLAB
BEAMSEE PLAN
EXIST. JOIST
V.I.F. TYP
BEAMSEE PLAN
2
3/16
TYP. ROOF OPENING DETAIL
3/16
3/4" = 1'-0"
5
SLAB REPAIR AT NEW STOREFRONT
3/4" = 1'-0"
1
2
MECH. UNIT
STEEL SHIMS @ 2'-0" O.C. (NOT
REQ'D IF TAPERED CURBS ARE
PROVIDED)
MECH. UNIT CURB
SEE MECH'L DWGS
CONT. MC6x15.3
HSS @ 6'-0" o.c.SEE PLAN FOR SIZE
SIMPSON H6
SIMPSON H6
1/4
C6x8.2
1/4
#4x1'-0" @ 16" O.C. EA. SIDE,
DOWEL INTO EXISTING SLAB
w/HILTI HIT-HY200
(6" MIN. EMBED.)
EA. BEAM
2
2x4 TYP
U.N.O.
EXISTING SLAB
(3)-10d
COMMON NAILS
TYP.
NOT USED
12
L REINFORCEMENT REQ'D WHEN
GREATER THAN 6"
1/8
4" MIN. THICK CONCRETE
INFILL ON VAPOR
RETARDER AND 4"
GRANULAR FILL W/ 6x6
2.9xW2.9 WWF CENTERED
COMPACTED GRANULAR
SUB-BASE
UTILITY
TRENCH
5
L121x121x16
EA SIDE
TYP. RTU CURB SUPPORT DETAIL
3/4" = 1'-0"
6
TRENCH REPAIR DETAIL
4
S2.0
3/4" = 1'-0"
2
ADJUSTABLE MASONRY
ANCHOR TIES @ 32" O.C.
w/(1)-8" MAX FROM EA. END
ANG. REINFORCEMENT REQ'D.
WHEN GREATER THAN 6"
9'-6"
PROVIDE OVERSIZED
WASHERS
6" MAX.
1/2"
FLAT SCREEN TVCOORD. w/ ARCH
7'-0"
RODS W/ HILTI
HIT-HY70 ADHESIVE (9"
MIN EMBED)
PL 1/2"x7"x0'-8"LG.
5
L121x121x16
EA. SIDE
JOIST REINF.
EQUIPMENT HANGER
SUPPORT BY OTHERS
1/2" S.S. THREADED
ROD TYP. U.N.O.
S.S. WASHER & (2)-NUTS.
PROVIDE GASKET IF HANGER IS
OF DIFFERING MATERIAL
GROUT MASONRY SOLID
16" DEEPx16" WIDE
BELOW LINTEL BRG.
CONTRACT DATE:
MASONRY OPENING
TYPICAL STEEL LINTEL BEARING DETAIL
(LINTEL PARALLEL TO WALL)
BUILDING TYPE:
DBR 37
PLAN VERSION:
009.00.00
SITE NUMBER:
311465 / 434385
STORE NUMBER:
NOT USED
13
SECTION
3/4" = 1'-0"
9
TYP. HANGER WEB REINF. DETAIL
3/4" = 1'-0"
7
TYP. LINTEL BEARING DETAIL
3/4" = 1'-0"
09.21.15
2015388.14
3
PIZZA HUT
EXTENTS OF JOIST REINFORCING
NEEDLE BEAM AS REQ'D
123 Minden Shopping Dr.
Minden, LA 71055
MECH. UNIT.
EXIST. COL
PL21"x3"x8"
SEE SECT. 6 THIS SHEET
1/4
8"
SHORE EX. AS REQ'D
1/4
8"
1/4
8"
SHORE EX. AS REQ'D
EXISTING WALL
TYP.
3/16
BEAMSEE PLAN
EXIST. BEAM V.I.F.
NOTES:
3
L121x121x16
JOIST WEB
REINFORCEMENT (NEAR SIDE &
FAR SIDE. ALTERNATE SIDES.)
3
L121x121x16
JOIST CHORD REINF.
SEE DETAIL 6 THIS SHT.
PROVIDE NEW MASONRY
TO MATCH EXISTING
14
SECTION
3/4" = 1'-0"
10
4-12
1/4"
TYP. U.N.O.
EX. JOIST V.I.F.
JOIST PROFILE SHOWN IS FOR CONCEPTUAL USE ONLY.
ACTUAL NUMBER OF WEB MEMBERS THAT REQUIRE
REINFORCEMENT SHALL BE FIELD VERIFIED.
NOT USED
DBR 37
NON-SHRINK GROUT FOR
UNIFORM BEARING
TYP.
LINTEL BEAM. SEE PLAN
S2.0
CONT BOT. PL 7x3/8
SECTION
3/4" = 1'-0"
8
SLAB &
FRAMING
DETAILS
SECTION
3/4" = 1'-0"
4
PLOT DATE:
N
O
I
T
C
Y
U
L
R
N
T
O
S
S
N
E
O
S
C
O
D
P
R
R
A
U
N
P
I
U
D
I
O
B
H
C OR
F
520 South Main Street, Suite 2531
Akron, OH 44311
330.572.2100 Fax: 330.572.2102
SS
7
1
2
9
12
13
CW
3
18
10
4
5
6
9
11
12
14
8
15
17
12
16
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
14.
15.
16.
THESE DRAWINGS WERE PREPARED BASED ON INFORMATION ATTAINED FROM A
SITE SURVEY AND AS-BUILT DRAWINGS. CONTRACTOR TO VERIFY ALL EXISTING
CONDITIONS IN FIELD PRIOR TO DEMOLITION AND NOTIFY THIS OFFICE IN CASE OF
DISCREPANCIES ASAP. DEMOLITION IS TO BE EXECUTED SO AS NOT TO DISTURB
EXISTING STRUCTURAL AND ROOFING SYSTEMS, AND OTHER AREAS THAT ARE
INTENDED TO REMAIN INTACT. VERIFY ALL CONSTRUCTION TO BE REMOVED THAT
IS NOT INTEGRAL TO STRUCTURAL SYSTEM PRIOR TO DEMOLITION.
ALL DIMENSIONS SHOWN AS EXISTING SHOULD BE FIELD VERIFIED BY
CONTRACTOR PRIOR TO DEMOLITION. VERIFY ALL DEMOLITION WORK WITH NEW
CONSTRUCTION AND INSTALLATION DRAWINGS PRIOR TO BEGINNING
CONSTRUCTION.
DEMOLITION CONTRACTOR TO COORDINATE AND REVIEW ALL CONSTRUCTION
DOCUMENTS AND DETERMINE THE EXTENT OF DEMOLITION WORK AND BECOME
FAMILIAR WITH THEM THOROUGHLY BEFORE PERFORMING ANY DEMOLITION
WORK. BY THE ACT OF STARTING DEMOLITION, THE CONTRACTOR WILL BE
DEEMED TO HAVE COMPLIED WITH THE FOREGOING, TO HAVE ACCEPTED SUCH
CONDITIONS, AND TO HAVE MADE THE NECESSARY ALLOWANCES IN PREPARING
HIS BID.
VERIFY DISPOSITION OF ALL FURNISHINGS, MILLWORK, LIGHTING FIXTURES,
EQUIPMENT, ETC. TO BE REMOVED WITH OWNER AND/OR LANDLORD. ALL ITEMS
TO BE DISPOSED SHALL BE DISPOSED OF OFF-SITE AND IN AN EXPEDITIOUS
MANNER.
WHEN UTILITIES ARE REMOVED, CAP AND SEAL A MINIMUM OF 6" ABOVE FINISH
CEILING.
SAWCUT AND REMOVE EXISTING SLABS AS REQUIRED FOR UNDERGROUND
ELECTRICAL AND PLUMBING LINES. ALL CONCRETE FLOOR WORK TO BE FINISHED
FLUSH WITH EXISTING FLOOR. REPLACE OR REPAIR ANY VAPOR BARRIERS
DISTURBED DURING EXCAVATIONS. VERIFY EXTENT OF WORK WITH KITCHEN
EQUIPMENT MANUFACTURER.
CONTRACTOR SHALL PROVIDE ALL TEMPORARY BRACING AS REQUIRED TO
MAINTAIN STRUCTURAL STABILITY OF THE EXISTING STRUCTURE DURING ALL
PHASES OF CONSTRUCTION.
PROTECT FROM DAMAGE DURING CONSTRUCTION ALL EXISTING WALLS, FLOORS,
CEILINGS, ETC. THAT ARE TO REMAIN. CONTRACTOR TO PATCH AND REPAIR ANY
DAMAGED PORTIONS OF THE EXISTING BUILDING AS REQUIRED TO MATCH THE
EXISTING ADJACENT CONSTRUCTION AND FINISHES.
THIS PLAN INDICATES A GENERAL SCOPE OF WORK TO BE PERFORMED AND DOES
NOT RELIEVE THE CONTRACTOR TO COMPLETE THE BUILDING MODIFICATIONS AS
SHOWN AND REQUIRED BY THE CONTRACT DOCUMENTS, INCLUDING BUT NOT
LIMITED TO PLUMBING, ELECTRICAL AND HVAC WORK.
IF CONTRACTOR ENCOUNTERS ANY HAZARDOUS MATERIALS DURING DEMOLITION
OR CONSTRUCTION, HE SHALL IMMEDIATELY SUSPEND WORK AND NOTIFY THE
PIZZA HUT CONSTRUCTION MANAGER BEFORE PROCEEDING.
ALL DEMOLITION SHALL BE CARRIED OUT IN A SAFE MANNER AND IN STRICT
ACCORDANCE WITH LOCAL REGULATIONS.
THE SUB-CONTRACTOR SHALL FIELD VERIFY THE EXTENT OF DEMOLITION. THE
WORK INCLUDES, BUT IS NOT LIMITED TO THE DEMOLITION AND REMOVAL OF ANY
WALLS, COUNTERS, FURNITURE, BULKHEADS, DOORS, PLUMBING, MECHANICAL
AND ELECTRICAL ITEMS INCLUDING CONDUITS AND DUCTWORK AS SHOWN ON
THE DRAWINGS OR AS REQUIRED TO COMPLETE THE INSTALLATION OF THE NEW
WORK FOR A COMPLETE JOB.
REMOVE ANY SINKS, WATER CLOSETS, URINALS, LAVATORIES, FLOOR DRAINS,
NOTED ON DRAWINGS AS WELL AS ALL ASSOCIATED PLUMBING ACCESSORIES.
CAP, PLUG ALL ABANDONED SUPPLY AND WASTE LINES. PATCH AND SEAL ALL
FLOOR PENETRATIONS.
ALL DEVICES REMOVED DURING DEMOLITION SHALL HAVE ALL ASSOCIATED
CONDUIT, WIRING, AND CONTROLS REMOVED BACK TO SOURCE OR NEXT DEVICE
THAT REMAINS.
RE-FEED ANY ELECTRICAL DEVICE OR ITEM THAT IS EXISTING TO REMAIN WHOSE
WIRING IS INTERRUPTED DUE TO RENOVATION IN ADJACENT AREA.
ANY ELECTRICAL DEVICE THAT IS TO REMAIN THAT IS LOCATED ON OR IN A WALL
OR CEILING BEING REMOVED SHALL BE RELOCATED AS DIRECTED BY G.C. IN FIELD
AND RECONNECTED AS REQUIRED.
GENERAL DEMOLITION NOTES
DEMO FLOOR PLAN
1
REMOVE PLUMBING FIXTURES IN THEIR ENTIRETY. CAP UNUSED PLUMBING LINES BELOW
FLOOR/BEHIND WALLS.
2
REMOVE EXISTING WATER HEATER IN ITS ENTIRETY. TERMINATE ALL PLUMBING AS REQUIRED
FOR NEW CONSTRUCTION.
3
DOOR AND FRAME TO REMAIN.
4
REMOVE ALL INTERIOR PARTITIONS TERMINATE ALL WIRING BACK TO SOURCE. CAP EXISTING
PLUMBING AS REQUIRED FOR NEW CONSTRUCTION.
5
1/4"=1'-0"
A
CONTRACT DATE:
REMOVE CEILING FINISHES, LIGHT FIXTURES AND ASSOCIATED WIRING (BACK TO SOURCE),
DIFFUSERS, AND SOFFITS.
BUILDING TYPE:
DBR 37
PLAN VERSION:
009.00.00
SITE NUMBER:
REMOVE EXISTING FLOOR FINISHES. PREPARE EXISTING CONCRETE FLOOR WITHIN THE ENTIRE
SPACE AND PATCH EXISTING FLOOR TO RECEIVE NEW FINISHES.
7
EXISTING SANITARY LINE LOCATION. DEPTH AT 32" BELOW FINISHED FLOOR.
8
REMOVE EXISTING ELECTRIC PANEL AND ALL ASSOCIATED BRANCH WIRING.
9
REMOVE EXISTING WATER SUPPLY LINES BACK TO INCOMING WATER LINE.
A.
B.
10
REMOVE EXISTING RTU AND ALL ASSOCIATED SUPPLY AND RETURN AIR DUCTWORK IN ITS
ENTIRETY.
C.
11
REMOVE EXISTING DOOR AND FRAME.
12
SAWCUT EXISTING CONCRETE SLAB AS SHOWN HATCHED FOR THE INSTALLATION OF NEW
PLUMBING LINES AS INDICATED ON DRAWING P2.0.
13
EXISTING 1" WATER LINE SERVICING TENANT SPACE.
14
WHERE NEW MECHANICAL EQUIPMENT OCCURS, CREATE NEW ROOF OPENINGS, PATCH/FLASH
ROOF AT CURBS AS REQUIRED.
15
REMOVE EXISTING ROOFTOP UNIT, ROOF CURB. REPAIR ROOF DECK, RIGID INSULATION AND
ROOFING TO MATCH EXISTING.
16
REMOVE EXISTING CMU WALL AS REQUIRED FOR NEW STOREFRONT. SEE SHEET A1.0.
17
MODIFY EXISTING STOREFRONT. SEE SHEET A1.0 & A1.1.
18
EXISTING STOREFRONT TO BE REMOVED. SAVE FOR RELOCATION.
D.
123 Minden Shopping Dr.
Minden, LA 71055
DO NOT SCALE DRAWINGS
DIMENSIONS ARE FROM FACE OF FINISHED WALL TO FACE OF
FINISHED WALL UNLESS NOTED OTHERWISE (U.N.O.)
WHERE EXISTING CONDITIONS ARE CUT OR DISTURBED TO PERMIT
INSTALLATION OF NEW WORK, MATCH & PATCH EXISTING DISTURBED
CONSTRUCTION TO ORIGINAL CONDITION.
BUILDING ELEMENTS SHOWN WITHOUT ANY KEYNOTE, ARE EXISTING
TO REMAIN, U.O.N.
DEMOLITION PLAN NOTES
E
DBR 37
DEMO
PLAN
EXISTING WALL TO REMAIN
KEY NOTES
2015388.14
PIZZA HUT
EXISTING TO BE REMOVED
D
311465 / 434385
STORE NUMBER:
6
09.21.15
C
D1.0
WALL TYPES
N.T.S.
B
PLOT DATE:
N
O
I
T
C
Y
U
L
R
N
T
O
S
S
N
E
O
S
C
O
D
P
R
R
A
U
N
P
I
U
D
I
O
B
H
C OR
F
520 South Main Street, Suite 2531
Akron, OH 44311
330.572.2100 Fax: 330.572.2102
10'-141"
9'-10"
15
7'-1141"
9'-541"
16'-341"
13'-141"
2
GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR VERIFICATION OF ALL
BUILDING DIMENSIONS PRIOR TO BEGINNING CONSTRUCTION AND SHALL
IMMEDIATELY NOTIFY OWNER'S REPRESENTATIVE OF ANY VARIANCE OR
DISCREPANCY AFFECTING NEW CONSTRUCTION PRIOR TO PROCEEDING WITH
WORK.
2'-941"
15
13
17
15
18
6
9
A11.3
2x6
A10.1
2
A11.3
1
A11.1
22
3
6
5
321"
COOLER
9'-11"
3"
12'-94
3
A10.0
2
4
A10.0
8
A11.3
A10.1
1
18
A10.0
22
4
1
9
A11.3
7'-741"
7'-121"
5'-6"
DINING
2x6
FREEZER
A10.1
1
A5.0
10
321"
14. ALL MEANS OF EGRESS AND FIRE PROTECTION SHALL BE MAINTAINED AT ALL
TIMES AND ANY SHUT DOWN OF LIFE SAFETY OR BUILDING SYSTEMS SHALL BE
APPROVED AND COORDINATED IN ADVANCE WITH THE OWNER AND LOCAL
BUILDING DEPARTMENT.
2
5
6
13. UPON COMPLETION OF PROJECT, GENERAL CONTRACTOR TO OBTAIN ALL
FINAL INSPECTIONS AS REQUIRED BY LOCAL JURISDICTIONS AND FURNISH
OWNER WITH EVIDENCE OF ALL SUCH INSPECTIONS AND CERTIFICATES OF
OCCUPANCY.
A10.1
4
2x4
11. ALL PENETRATIONS SHALL RECEIVE CAULKING TO SEAL ANY TYPE OF ENERGY
LOSS.
12. THE DRAWINGS ARE NOT TO BE SCALED. FOR INFORMATION CONCERNING
EXISTING PARTITIONS, ETC., VERIFICATION MUST BE DONE IN THE FIELD.
2
A11.1
19
1
10. GENERAL CONTRACTOR SHALL PROVIDE ALL NECESSARY BLOCKING IN WALLS
FOR SUPPORT OF ALL EQUIPMENT, SHELVING, ACCESSORIES SEE FLOOR PLAN
FOR LOCATION OF BLOCKING.
3
A11.1
14
18
8
GENERAL CONTRACTOR SHALL COORDINATE EXISTING STRUCTURE WITH NEW
CONSTRUCTION INCLUDING MECHANICAL, PLUMBING, FIRE PROTECTION AND
ELECTRICAL WORK.
10'-11"
2'-8"
9
3'-041"
3'-1"
SERVICE
15
17
21
5
3'-341"
7'-0"
3'-6"
7
A10.1
18
7
2
12
A10.2
7
11'-1121"
9.
12
4'-421"
8.
GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR VERIFICATION OF THE
BUILDING'S STRUCTURAL SYSTEM. STRUCTURAL MEMBERS, INCLUDING
BEARING AND SHEAR WALLS, SHALL NOT BE REMOVED, CUT OR OTHERWISE
MODIFIED WITHOUT WRITTEN AUTHORIZATION FROM THE OWNER'S
REPRESENTATIVE.
DRY STORAGE
11
321"
12
5'-1041"
7.
12
PRIOR TO COMMENCEMENT OF ANY CONSTRUCTION, GENERAL CONTRACTOR
SHALL VERIFY EXISTENCE AND LOCATION OF ALL EXISTING ABOVE AND BELOW
GRADE UTILITIES,INCLUDING SANITARY SEWER, STORM SEWER, WATER, GAS,
ELECTRICAL, TELEPHONE, ETC. ANY DISCREPANCIES IN UTILITY LOCATIONS
SHALL BE BROUGHT TO THE IMMEDIATE ATTENTION OF THE OWNER'S
REPRESENTATIVE.
16'-021"
6
2x6
6.
6
10'-53
4"
16
13'-2"
3'-6"
ALL REMODELED BUILDING ELEMENTS INCLUDED AS PART OF THIS PROJECT
SHALL COMPLY WITH THE MOST CURRENT EDITION OF BUILDING CODES, AND
LOCAL CODES.
11'-121"
5.
3'-0"
16
1
2'-8"
ALL WORK SHALL BE IN COMPLIANCE WITH APPLICABLE FEDERAL, STATE AND
LOCAL BUILDING CODES, REGULATIONS, ORDINANCES AND STANDARDS.
2'-8"
4.
20
10'-10"
CUT, REMOVE AND REPLACE EXISTING CONCRETE SLAB AS REQUIRED FOR
INSTALLATION OF NEW UNDER SLAB PIPING AND CONDUIT.
5'-921"
3.
3"
1'-104
PREPARE EXISTING CONCRETE SLAB TO RECEIVE NEW FLOOR FINISHES AS
SCHEDULED.
7'-941"
2.
5'-5"
REPLACE OR REPAIR DAMAGED, DETERIORATED OR UNSUITABLE SUBSTRATES
AS REQUIRED TO RECEIVE NEW WALL FINISHES AS SCHEDULED.
2x6
1.
3
3
4
A11.1
3
3"
43'-104
4
15. DEMISING WALLS SHALL EXTEND FULL HEIGHT TO STRUCTURE ABOVE. G.C.
SHALL SEAL ALL PENETRATIONS AS REQUIRED TO MAINTAIN INTEGRITY OF
DEMISING WALLS AND PREVENT INSECT OR RODENT EGRESS INTO STORE
SPACE.
12'-23
4"
CONTRACT DATE:
16. GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR VERIFICATION OF
EXISTING INSULATION VALUES IN EXTERIOR WALL AND ROOF/CEILING
ASSEMBLY. CONTRACTOR SHALL PROVIDE ADDITIONAL INSULATION TO
ACHIEVE A MINIMUM R-19 IN EXTERIOR WALLS AND R-30 IN ROOF/CEILING
ASSEMBLY.
09.21.15
BUILDING TYPE:
DBR 37
PLAN VERSION:
009.00.00
SITE NUMBER:
311465 / 434385
STORE NUMBER:
2015388.14
PIZZA HUT
17. ALL DIMENSIONS TO FINISHED WALL UNLESS OTHERWISE NOTED.
PROJECT GENERAL NOTES
F
TYPICAL EXTERIOR WALL:
EXISTING CMU WALL W/ 2X4 WOOD STUDS @ 16" O.C. TO
DECK IN OPEN CEILING AREAS, 2X4 WOOD STUDS @ 16"
O.C. TO 6" ABOVE CEILING @ RESTROOMS AND B.O.H.
INSULATE STUD CAVITIES WITH R-13 FIBERGLASS BATT
INSULATION.
TYPICAL INTERIOR WALL:
2x4 WD STUDS AT 16" O.C. (2x6 WHERE NOTED) TO DECK
IN OPEN CEILING AREAS, 2X4 WD STUDS @ 16" O.C. TO 6"
ABOVE CEILING @ RESTROOMS AND B.O.H. W/ 1/2" TYPE
"X" GYP. BD. SUBSTRATE U.O.N. USE MOISTURE
RESISTANT GYP. BD. BEHIND ALL CERAMIC WALL TILE.
U.O.N. PROVIDE 3 1/2" SOUND BATT INSULATION AT ALL
RESTROOM WALLS.
FLOOR PLAN
DASHED LINE INDICATES SUBSTRATE LOCATION. ALL
WALLS SHALL BE AS INDICATED EXCEPT FROM TOP OF
SLAB TO 12" ABOVE SLAB SHALL BE 1/2" CEMENT BOARD,
U.O.N. THIS NOTE DOES NOT APPLY TO EXTERIOR FACE
OF EXTERIOR WALLS.
TYPICAL INTERIOR LOW WALL:
2X4 STUDS AT 16" O.C. (2X6 OR 2X8 WHERE NOTED) W/
1/2" GYP. BD. SUBSTRATE U.O.N. T.O. WALL AT 4'-0" A.F.F.
U.N.O.
DIMENSIONS:
A. ALL DIMENSIONS ARE TO FACE OF STUD U.O.N. REFER TO FOUNDATION PLAN FOR
FACE OF CONC. DIMENSIONS.
B. DIMENSIONS NOTED AS CLEAR ARE MIN. REQ'D. NET CLEARANCE FROM FACE OF
WALL / WAINSCOT FINISH. REFER TO DWG A2.0 FOR CRITICAL "HOLD" EQUIPMENT
CLEARANCES. VERIFY FINAL EQUIPMENT SIZES W/ VENDOR PRIOR TO INT. WALL
FRAMING.
WINDOWS / DOORS:
A. SEE SHT. A1.1 FOR WINDOW TYPES AND DOOR SCHEDULE.
B. ALL DOOR AND WINDOW OPENING DIMENSIONS ARE TO ROUGH OPENING.
FINISH SUBSTRATES:
A. PROVIDE 1/2" THICK CEMENTITIOUS BD. FROM FLOOR SLAB TO 12" A.F.F. MIN. IN LIEU
OF GYP. BD. U.O.N.
B. ALL JOINTS, GAPS OR SPACES LEADING TO ALL HOLLOW OR INACCESSIBLE SPACES
SHALL BE SEALED WITH "NSF INTERNATIONAL" APPROVED SEALANTS.
C. SEE SHTS. A8.0 AND A10.0 THRU A10.2 FOR ROOM FINISHES.
D. ALL BACK OF HOUSE WALLS SHALL HAVE 1/2" EXPOSURE 1 PLYWD U.O.N.
DECOR:
A. SEE A2.0 FOR SEATING PLAN AND DETAILS.
B. SEE A8.0 FOR FLOOR FINISHES.
C. SEE A10.0 - A10.2 FOR WALL FINISHES.
D. SEE A9.0 FOR CEILING FINISHES.
WALL LEGEND
D
FLOOR PLAN NOTES
1
STARTING POINT. ALL SUB-TRADES SHALL USE THIS POINT AS A BEGINNING LAY-OUT
(OUTSIDE FACE OF EXT. WALL STUDS).
2
INSTALL BACKER ROD AND SEALANT BETWEEN COOLER/FREEZER AND ADJACENT
WALL SURFACES. DISCONTINUE WALL COVERING BEHIND COOLER / FREEZER.
1/4"=1'-0"
A
13
BUNDLED SYRUP LINES IN 8" PVC CHASE BELOW SLAB FOR DRINK SYSTEM.
14
SAFE PEDESTAL, SEE DETAIL 19/A11.0
15
S.S. CORNER GUARD / WALL CAP, TYP. ALL CORNERS IN BACK-OF-HOUSE FROM REAR
WALL TO THE KITCHEN SIDE OF THE SERVICE COUNTER. SEE DETAIL 15/A11.0.
16
HOOD AT THIS WALL REFERENCE MECHANICAL. OWNER SUPPLIED AND CONTRACTOR
INSTALLED S.S. PANELS. APPLY WITH CONSTRUCTION ADHESIVE NO EXPOSED
SCREWS/ATTACHMENTS.
3
EXISTING BUILDING COLUMN.
4
DEMO CMU WALL AS REQUIRED FOR INSTALLATION OF NEW STOREFRONT. SEE
STRUCTURAL DRAWINGS.
5
CONTINUE B.O.H FINISHES INTO WALK IN COOLER AND UNDER FREEZER.
17
6
3/4" PLYWOOD BACKING BEHIND WALL MOUNTED HAND SINKS
18
HATCHED AREAS INDICATE MILLWORK. SEE SCOPE OF WORK.
7
ALUMINUM THRESHOLD. REF. SHEET DOOR HARDWARE SCHEDULE SHEET A1.1
19
LOW WALL. SEE DETAIL - 10/A11.3.
8
FIRE EXTINGUISHERS (PER LOCAL CODE) TO BE FURNISHED AND INSTALLED BY G.C.
CONFIRM LOCATIONS WITH FIRE MARSHAL.
20
EXISTING TENANT SEPARATION WALL TO REMAIN..
MOP SINK LOCATION.
21
9
INSTANTANEOUS WATER HEATERS MOUNTED ABOVE CEILING . SEE PLUMBING
SHEETS.
10
FREEZER FLOOR AND BASE FURNISHED BY MANUFACTURER.
11
ELECTRICAL PANELS AND CLEAR FLOOR SPACE.
12
SPLASH GUARD. SEE DETAIL 11/A11.0.
DBR 37
FLOOR PLAN
22
A1.0
SUPPORT.
C
123 Minden Shopping Dr.
Minden, LA 71055
KEY NOTES
B
PLOT DATE:
BUTTS
LOCKS
CLOSERS
KICKPLATE
DOOR
STOP
THRESHOLD
2
3
4
1
2
3
520 South Main Street, Suite 2531
Akron, OH 44311
330.572.2100 Fax: 330.572.2102
X
X
X
X
X
X
-
-
-
8, 9, 11, 12
3
EX. 3'-0" x 7'-0" x 1-3/4"
-
HM HM
-
-
-
7, 10, 11, 16
4
3'-0" x 6'-8" x 1-3/4"
B WD HM
X
X
X
X
X
X
X
14/A11.0 14/A11.0
-
6, 11, 12, 13, 15, 17
5
3'-0" x 6'-8" x 1-3/4"
B WD HM
X
X
X
X
X
X
X
14/A11.0 14/A11.0
-
6, 11, 12, 13, 15, 17
X
VISTA # TH43
I.D.C. 652-P
X
DOOR SIGN
AL AL
COAT HOOK - IVES 571-A92
A
UNDERCUT 3/4"
3'-0" x 7'-0" x 1-3/4"
2
SWEEP (VISTA 231 STD) NGP 101VA
8, 9, 11, 12
QUALITY W302-26D
-
FLOOR STOP - QUALITY 433ES
-
STAINLESS STEEL 18" x 34"
-
STAINLESS STEEL 10" x 22"
X
STAINLESS STEEL 10" x 34"
X
X
DOORMAN D-1550
X
3'-0" x 7'-0" x 1-3/4"
FALCON #D271A
X
1
CONT. HINGE MCKINNEY 300 SERIES
X
1 1/2 PR VISTA STADARD BH-1
SILL
1
JAMB
4
HEAD
3
SURFACE BOLTS TOP & BOTTOM IVES SB1600
2
PROVIDE A SIGN STATING "THIS
DOOR TO REMAIN UNLOCKED
DURING BUSINESS HOURS"
1
SWEEP & WEATHERSTRIP INCL. IN PACKAGE
3
PULL
2
PULL PLATE #1610A 4" x 16" - QUALITY S.S.
1
PUSH
6
PUSH PLATE #40 8"x16" - QUALITY S.S.
5
HINGE STOP - STANLEY 76 6327 (US26)
4
NORTON 1604 OVERHEAD
3
PEMKO COMMERCIAL THRESHOLD - ALUM.
2
PANIC HARDWARE INCLUDED IN PACKAGE
1 1/2 PR McKINNEY #TA2731, 4-1/2" x 4-1/2"
FRAME
DOOR
TYPE
1
X
KICKPLATE
PUSH SIDE
ONLY
DOOR TYPES
1/4" = 1' - 0"
3
GLASS SCHEDULE
1.
SEE SCHEDULE FOR GLASS TYPES.
2.
REFER TO FLOOR PLAN, ELEVATIONS AND WALL SECTIONS FOR ROUGH OPENING
DIMENSIONS.
A
1" INSULATED GLASS
B
REFERENCE NOTES:
1. STAIN/PAINT ALL DOORS AND FRAMES EXCEPT ALUMINUM ENTRY
DOORS, 1 & 2.
1" INSULATED TEMPERED GLASS
ALL STOREFRONT MATERIAL AND GLAZING SHALL BE SUPPLIED AND INSTALLED BY G.C.
U.O.N.
4.
ALL ALUMINUM DOOR AND WINDOW FRAMES SHALL BE DARK BRONZE ANODIZED.
5.
REFER SPECIFICATIONS FOR GLASS & ALUM. STOREFRONT.
2.
ALL HARDWARE SHALL BE US32D U.O.N.
3.
ALL HM FRAMES SHALL BE 16 GA STEEL U.O.N.
4.
ALL LOCKS SHALL BE FALCON 6 PIN INTERCHANGEABLE CORE
SUPPLIED AND INSTALLED BY THE G.C. ALL EXTERIOR LOCKS
SHALL BE PROVIDED WITH CONSTRUCTION CORES. ALL
PERMANENT CORES SHALL BE KEYED ALIKE.
5.
PERMANENT CORES SHALL BE SHIPPED TO THE RESTAURANT
GENERAL MANAGER.
6.
MOUNT DOOR CLOSURES ON TOILET ROOM OR KITCHEN SIDE
ONLY.
NOTE:
SHADING COEFFICIENT SPECIFICATION PER LOCAL CODE REQUIREMENTS.
DAYTIME VISIBILITY INTO DINING ROOM SHALL BE MAINTAINED.
9.
DOOR SCHEDULE
2
DOOR SCHEDULE NOTES
1
IF REQUIRED BY LOCAL CODE, STOREFRONT DOOR PANIC HARDWARE
SHALL BE :
DOR-O-MATIC 2092 RIM PANIC HARDWARE AND EXTERIOR PULLS WITH
QUALITY #520 DOOR PULL.
10. EXISTING H.M. DOOR AND FRAME TO REMAIN. PROVIDE NEW
HARDWARE.
11. MAXIMUM DOOR OPERATING PRESSURE : 5 LBS INTERIOR : 8.5 LBS
EXTERIOR MEASURED AT 90 DEGREES TO THE DOOR AT THE STRIKE
EDGE.
12. ADA COMPLIANT ACCESSIBILITY SIGNAGE WHERE REQUIRED - (1) MEN;
(1) WOMEN; (2) EXIT.
13. RESTROOM SIGN IF REQUIRED. VERIFY LOCAL REQUIREMENTS.
7.
KEYLESS ENTRY SYSTEM REQUIRED. INCLUDES PANIC
HARDWARE, AND KEYLESS ENTRY, ORDERED THRU LOCKNET
SECURITY DOORS, (1-800-887-4307).
8.
PROVIDE PUSH/PULL BARS.
(ROCKWOOD GEOMETEK #RM7902 16" MOUNT VERT. "PULL")
(#RM7902 36" MOUNT HORIZ. "PUSH")
14. NOT USED.
15. DOORS AND FRAMES SHALL BE PAINTED, SEE FINISH SCHEDULE SHT
A8.1
16. PROVIDE WIDE ANGLE PEEP HOLE AT 48" A.F.F.
GENERAL NOTES
17. DOORS SHALL BE PAINT GRADE.
4
N.T.S.
REMOVE GLAZING AND
SWAP POSITIONS
B
B
2
A7.0
8
A11.0
A
A
A
B
3'-1"
2
A7.0
A
A
2
A7.0
CONTRACT DATE:
8'-1"
6'-11"
B
A
B
B
DBR 37
PLAN VERSION:
009.00.00
SITE NUMBER:
A
3'-2"
7'-0"
B
B
311465 / 434385
1'-4"
3'-0"
3'-4"
4'-8"
B
6'-4"
B
6'-621"
B
B
5'-821"
6'-4"
B
B
1'-421"
6'-4"
B
3'-0"
1'-421"
3"
43'-114
5
A7.0
1
A7.0
2
DARK BRONZE
ANODIZED ALUMINUM
(MATCH EXISTING)
1
A7.0
2015388.14
B
B
B
09.21.15
BUILDING TYPE:
STORE NUMBER:
2'-0"
3.
4
FALCON C952 OR C986 AS REQUIRED
5'-4"
3'-0"
1'-0"
DARK BRONZE ANODIZED
ALUM. DOOR
3
DOOR NOTES
X
B
DOOR
PULL
2
DETAIL LOCATIONS
AL AL
SIGN WHERE
NOTED
DOOR
PULL &
PUSH
PLATE
1
MISCELLANEOUS
A
SEE DOOR TYPE ELEVATIONS
4"
4"
4"
DOOR SIZE
PAIR
N
O
I
T
C
Y
U
L
R
N
T
O
S
S
N
E
O
S
C
O
D
P
R
R
A
U
N
P
I
U
D
I
O
B
H
C OR
F
DOOR
NO.
5
A7.0
1
A7.0
EX.
EX.
EX.
EX.
EXISTING
STOREFRONT
SYSTEM TO REMAIN
B
3'-0"
EX.
EX.
EX.
EX.
PIZZA HUT
EX.
EX.
EX.
EX.
123 Minden Shopping Dr.
Minden, LA 71055
EXISTING STOREFRONT SYSTEM TO REMAIN
1
DARK BRONZE
ANODIZED ALUMINUM
(MATCH EXISTING)
DBR 37
WINDOW NOTES
ALL WINDOW ARE TO BE GLAZED W/ TYPE
OTHERWISE.
A
GLASS UNLESS NOTED
ROLLER SHADES TO BE FURNISHED AND INSTALLED BY G.C. ON ALL
WINDOWS WITH SOUTHERN EXPOSURE.
INDICATES LOCATION
OF ROLLER SHADES
NOTE:
MOUNT ROLLER SHADES INSIDE FRAMES.
DOOR & WDW
ELEVATIONS/
SCHEDULE
ROLLER SHADES:
SUPPLIER: BLIND EXPRESS
HUNTER DOUGLAS - ROLLERSHADE SHEAR WEAVE
4100, COLOR: V10 EBONY, 10% OPENNESS MOUNTED
TO INSIDE OF WINDOW FRAME
PHONE: 770.644.1688
A1.1
ROLLER SHADES TO BE FURNISHED AND INSTALLED
BY G.C.
WINDOW TYPES
1/4" = 1'-0"
5
PLOT DATE:
N
O
I
T
C
Y
U
L
R
N
T
O
S
S
N
E
O
S
C
O
D
P
R
R
A
U
N
P
I
U
D
I
O
B
H
C OR
F
520 South Main Street, Suite 2531
Akron, OH 44311
330.572.2100 Fax: 330.572.2102
E
D
K-959
K-XX1
DELIVERY
B-915
F-930 U-909 F-270
F-911 K-879 F-907
F-023 F-095
F-085 F-070
K-925
S-600
S-590
K-959
R-905
K-870
N-062
B-242
B-252
B-295
N-923
B-405
K-968
DRY STORAGE
K-893
P-803
K-926
B-915
K-968
F-043
F-031
K-870
B-295
N-062
N-923
B-242
B-405
B-252
K-870
N-062
B-242
B-252
B-295
N-923
B-405
K-012
K-013
R-400
K-968
F-178
U-901
S-457
F-922
S-663
L-947
BELOW
U-910
U-904
E-939
E-938
C-951
U-904 P-097 U-904
K-886
B-405
K-968
SHELVING ALONG BACK
SIDE OF BULKHEAD (GC
TO PROVIDE BLOCKING)
N-062
B-295
B-252
B-242
SERVICE
DIGITAL MB DIGITAL MB DIGITAL MB
R-011
F-178
S-457
S-663 (3)
F-922
U-901
L-909
L-910
DISHWASH
S-580
S-927
K-926
B-406
B-242
B-265
B-295
N-134
W-XX1
K-XX3
12
10
10
10
10
10
11
B
MEN
3
5
5
8
5
3
15
L-907
DINING
L-905
L-907
B-300
11
L-906
3
B-406
S
S
S
B-242
B-265
B-295
N-134
WOMEN
K-XX3
FREEZER
S
B-275
B-305
B-300
COOLER
K-XX2
C
B-405
R-100
14
SHELVING ALONG BACK
SIDE OF BULKHEAD (GC
TO PROVIDE BLOCKING)
F-265
1
2
CONTRACT DATE:
12
10
11
9
8
6
7
5
3
4
2
EQUIPMENT/SEATING PLAN
X
QTY.
ITEM
REMARKS
1
4
48" SINGLE DBR BOOTH
--
2
6
48" DOUBLE DBR BOOTH
--
3
3
30" x 48" LAMINATE TABLE TOP
ACCESSIBLE BASE
4
7
30" x 48" LAMINATE TABLE TOP
5
3
6
DRY STORAGE SHELVING CALCULATIONS
REMARKS
EQUIPMENT #
1/4"=1'-0"
A
TOTAL
EQUIPMENT #
QUANTITY X FACTOR X LENGTH =
1.0
X
.40
X
4.0
=
1.6
K-926
5.0
X
.75
X
N/A
=
3.0
K-658
1.0
X
1.0
X
6.0
=
6.0
K-920
1.0
X
1.25
X
3.0
=
3.75
K-659
1.0
X
1.0
X
3.0
=
3.0
K-922
2.0
X
1.25
X
6.0
=
15.0
--
K-870
2.0
X
.33
X
2.0
=
1.32
K-983
3.0
X
1.25
X
5.0
=
18.75
36" X 36" WOOD TABLE TOP
BAR HEIGHT BASE
K-919
1.0
X
1.0
X
5.0
=
5.0
5
30" x 48" WOOD TABLE TOP
ACCESSIBLE BASE
K-944
4.0
X
1.0
X
4.0
=
16.0
7
3
30" X 24" DWODO TABLE TOP
--
K-970
1.0
X
.66
X
2.0
=
1.32
8
1
30" x 96" WOOD TOP COMMUNITY TABLE
ACCESSIBLE BASE
K-982
1.0
X
1.25
X
5.0
=
6.25
9
8
DBR SOFT SEATING
BAR HEIGHT
K-983
3.0
X
1.25
X
5.0
=
18.75
10
22
DBR WOOD SEATING
BAR HEIGHT
11
6
DBR WOOD SEATING
--
12
1
18" X 90" BENCH
--
14
5
48" FLAT SCREEN TV
WALL MOUNT
15
1
60" FLAT SCREEN TV
WALL MOUNT
K-999
2.0
X
1.25
6.0
=
15.0
TOTAL
HC
NOT USED
E
KEY NOTES
311465 / 434385
STORE NUMBER:
2015388.14
123 Minden Shopping Dr.
Minden, LA 71055
DBR 37
QUANTITY X FACTOR X LENGTH =
TOTAL
K-659
1.0
X
1.0
X
3.0
=
6.0
K-922
2.0
X
1.25
X
5.0
=
12.5
18.5
ACCESSIBLE SEATING
EQUIPMENT
PLAN
A2.0
**DO NOT INCLUDE SPEED RACK
F
009.00.00
40.5
FREEZER SHELVING CALCULATIONS
TOTAL
DECOR
1. REFER TO SCOPE OF WORK FOR RESPONSIBILITIES.
SEATING PACKAGE - BY SEATING VENDOR U.O.N.
X
PLAN VERSION:
TOTAL
K-323
EQUIPMENT #
DBR 37
PIZZA HUT
COOLER SHELVING CALCULATIONS
QUANTITY X FACTOR X LENGTH =
BUILDING TYPE:
SITE NUMBER:
1
09.21.15
D
TOTAL
74.24
STORAGE CAPACITY MATRIX
B
PLOT DATE:
EQUIPMENT SCHEDULE
NO. QTY
B-242
B-252
B-265
B-275
B-295
B-300
B-305
B-310
B-400
B-405
B-406
B-410
B-643
4
2
2
2
5
2
2
2
1
5
2
1
1
B-915
2
BY G.C.
SUPPLY INST.
X
X
X
X
X
X
X
X
X
X
X
X
X
ITEM DESCRIPTION
B CONTRACTOR BUILDING ELEMENTS
SOAP DISPENSER (WALL MOUNT)
SANITIZER DISPENSER
MIRROR, 18" x 36"
TOILET PAPER DISPENSER
PAPER TOWEL DISPENSER
GRAB BAR 1-1/2"DIA X 36" S.S. FIN.
GRAB BAR 1-1/2"DIA X 42" S.S. FIN.
VERTICAL GRAB BAR 1-1/2"DIA X 18" S.S. FIN.
WASTE BASKET - 32 GALLON
WASTE BASKET
WASTE BASKET
SANITARY NAPKIN DISPOSAL
KAY CHEMICALS DISPENSING SYSTEM
MFR. & MODEL NUMBER
EQUIPMENT SCHEDULE
PLUMB ELECT
REMARKS
GAS
BY G.C.
SUPPLY INST.
NO.
NO. QTY
B-242
B-252
B-265
B-275
B-295
B-300
B-305
B-310
B-400
B-405
B-406
B-410
B-643
N-062
N-071
N-075
N-130
N-134
N-171
N-207
N-903
N-909
N-912
N-922
N-923
N-926
2
1
1
1
2
2
1
1
1
1
1
4
1
X
X
X
X
X
X
X
X
X
X
X
X
X
B-915
P-094
P-097
P-533
1
1
1
X
X
X
P-803
P-XXX
1
1
X
X
R-011
R-067
R-100
R-400
R-905
1
1
1
1
1
ITEM DESCRIPTION
MFR & MODEL NUMBER
PLUMB ELECT
REMARKS
GAS
NO.
N SINKS/DISHWASHERS
KAY CHEMICAL #92021176
KAY CHEMICAL #92021175
BOBRICK #B-165-1836
BOBRICK B2890
BOBRICK #B-2620
BOBRICK #B6806X36
BOBRICK #B6806X42
BOBRICK #B6806X18
RUBBERMAID #2632 (GREY)
RUBBERMAID SLIM JIM #3541 (GREY)
RUBBERMAID #2956 (BLACK)
RUBBERMAID #6140
KAY CHEMICALS SYSTEM KIT 0187
SURFACE MTD
HAND SINK
MOP SINK FAUCET
PRE-RINSE UNIT
PREP SINK EQUIPMENT
HAND SINK EQUIPMENT
LEVER
MOP SINK BASIN
DUMP SINK
PREP SINK
3-COMP LEFT HAND SINK & FAUCET W/ HANDLES
LEASED DISHWASHER: ECOLAB
HAND SINK SPLASH GUARDS
DISH TABLE EXTENSION
P FOOD PREPARATION
SALAD ROLL IN MAKE TABLE
8' PIZZA MAKE TABLE
GREASE SHUTTLE
AERO #HSK-SKV
T&S #B2465
T&S #B-0133-B
T&S BRASS & BRONZE #B2463
T&S BRASS #B2460
AERO #S-20
MUSTEE #M63
AERO #2F1YUM152012
AERO #3F1-2116-18R
AERO #3F3-DC-YUM-LH48
INFERNO - w/ VAPPR VENT
AERO #HAND SINK SPLASH
AERO #3CDL30
TRAULSEN #RPP132L-FHS-LH
MCCALL
X
X
X
X
X
1-COMP PROOFER
3-COMP RETARDER
R REFRIGERATION
UNDER COUNTER KEG COOLER W/ TAPS
ICE TROUGH
UNDER COUNTER MUG CHILLER
UNDER COUNTER REFRIGERATOR
1-DOOR FULL HEIGHT WINGSTREET FREEZER (LH)
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
N-062
N-071
N-075
N-130
N-134
N-171
N-207
N-903
N-909
N-912
N-922
N-923
N-926
N
O
I
T
C
Y
U
L
R
N
T
O
S
S
N
E
O
S
C
O
D
P
R
R
A
U
N
P
I
U
D
I
O
B
H
C OR
F
C-906
C-951
C-XX1
1
1
1
X
X
X
X
X
SWITCHGEAR PACKAGE
C COOKING EQUIPMENT
MICROWAVE
FRYER
PIZZA HUT OVEN, TRIPLE
SURFACE MTD.
SURFACE MTD
SURFACE MTD
SURFACE MTD
SURFACE MTD VERTICALLY
SURFACE MTD
SEE S.O.W. FOR COMPANY VS FRANCHISE
X
SES #RMS10T
PITCO #PHSSH552FDFSNG
MIDDLEBY MARSHALL #PS870-3
X
X
X
INCLUDES BRANCH PANELS
X
X
INCLUDES GAS HOSE
W/ START UP; (CAST IRON FINISH)
C-906
C-951
C-XX1
D BUFFET - NOT USED
E EXHAUST HOODS/FIRE SUPP.
E-938
E-939
E-XX1
F-023
F-031
F-043
F-070
F-085
F-095
F-178
F-179
F-265
F-270
F-907
F-908
F-911
F-915
F-922
F-930
1
1
1
1
1
1
1
1
1
1
3
4
1
1
2
1
2
1
1
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
FRYER HOOD 36"
STAINLESS STEEL WALL PANEL
OVEN HOOD
F OFFICE/EMPLOYEE/MUSIC/MISC.
MANAGER'S STOOL
COAT HOOKS
PH OFFICE COMPUTER
PH MONITOR-OFFICE
OFFICE PRINTER/ COPIER/ FAX/ SCANNER
PH UPS
SAFE
DRIVER DROP BOX
HIGH CHAIR
FIRST AID KIT
WALL TELEPHONE
DESK TELEPHONE
FILE CABINET (2 DRAWER HIGH)
FLOOR MAT-CHARCOAL, 3'x5'
BLACK 24x30 LICENSE FRAME
WAVE TELEPHONE SYSTEM
K-003
1
X
K WORKSTATIONS/SHELVING/CARTS
CUT TABLE
K-012
K-013
K-017
K-195
K-216
1
1
1
1
1
X
X
X
X
X
WINGSTREET 48" SAUCING STATION
WINGSTREET PREP STATION - 24" x 30" x 74"
EXPO STATION
WALL GRID SYSTEM
WALL MOUNTED SHELF SYSTEM
CAPTIVE AIRE #3044BD2
CAPTIVE-AIRE #BSFH96X72
MIDDLEBY MARSHALL
X
X
X
SEE HOOD MFR. DRAWINGS
SEE HOOD MFR. DRAWINGS
SEE HOOD MFR. DRAWINGS; CAST IRON FINISH
B&B SYSTEMS #4060550
BOBRICK # B-212
AMERICAN SECURITY#9336131
JR DROPBOX #DD-330
X
X
X
X
X
POS PROVIDED
POS PROVIDED
POS PROVIDED
#PRST2617
HON # HON312CPL
WSM #800503
ACCUSERV #FFST
E-938
E-939
E-XX1
F-023
F-031
F-043
F-070
F-085
F-095
F-178
F-179
F-265
F-270
F-907
F-908
F-911
F-915
F-922
F-930
TBD
K-003
METRO #PHWF4C
METRO #PHWPF
TBD
METRO # PHSG24
METRO #PHSS36
K-012
K-013
K-017
K-195
K-216
MOUNT TOP RAIL AT 81" SEE CUTSHEET
K-830
K-870
K-879
K-886
K-893
1
3
1
1
1
X
X
X
X
X
LID BIN - BLACK CART
14"x24" WIRE WALL SHELF UNIT
48" ORDER ENTRY STATION / MANAGERS DESK
MAKETABLE OVERSHELF 18" x 96" W/ HOOKS & PRINTER
24" x 30" x 74" - 6 SHELF UNIT
WSM #6039040
METRO # WS1424A
METRO #PHMW48D
METRO #PHMTS33
METRO #PH117A
K-830
K-870
K-879
K-886
K-893
K-903
K-901
1
1
X
X
UNDERSINK SHELVING UNIT
24" x 48" x 74" 5-SHELF UNIT W/ S.S.
METRO #PHUS1824
METRO # PHMW48B
K-903
K-901
K-925
K-926
K-959
K-968
K-970
K-982
K-XX1
K-XX2
K-XX3
1
5
5
2
1
4
1
1
2
X
X
X
X
X
X
X
X
X
27"x 19"x 60" BAG IN BOX RACK
DOUGH CART 21" x 30"
24" x 54" x 74" 5 SHELF UNIT
PREP. TABLE
14"x24" DOUBLE WIRE WALL SHELF UNIT
30" x 60" x 74" - 5 SHELF
30" x 54" x 74" - 5 SHELF
24" x 30" x 74" - 5 SHELF
30" x 48" x 74" - 5 SHELF
METRO #PHDC2130A
METRO #PH112F
METRO #PHPREP3060C
METRO # PH108A
METRO #PH114G
METRO #PH
METRO #PH
METRO #PH
SEE SCOPE OF WORK
S-457
S-570
S-580
S-590
S-600
S-663
S-826
S-903
S-907
1
1
1
1
1
3
1
1
1
X
X
X
X
X
X
X
X
X
S SERVING/PICK-UP
BAG HOLDER
CARBONATOR
CO2 (BULK) TANK
WATER FILTER SYSTEM
BUNDLED SYRUP LINES
18" x 36" x 27" - UNDERCOUNTER SHELF
WING HOT HOLD
7 QT. SAUCE WARMER W/ SAUCE PUMP
COFFEE BREWER
S-928
1
X
ICE TEA BREWER
S-XX2
S-XX3
S-XX4
1
1
1
X
X
X
DRINK DISPENSER
UNDER COUNTER ICE MACHINE
UNDER COUNTER ICE BIN
U-007
U-901
U-902
U-904
U-909
U-910
1
3
2
5
1
2
X
X
X
X
W-XX1
1
X
BEVAIR #SPE4818MPH
RANDELL #PH96E3MSS
AERO #SSA925
X
X
PERLICK #DDS60
FRANKE #E4038PQ02
PERLICK #FR36SS2
BEVAIR #UCR20Y141
TRAULSEN #G12010
X
X
FRANKIE #27012968
CORNELIUS/REMCOR
MVE #11805373
SELECTO #MF5/600
100' 12 BUNDLE
METRO #PHEXPO3
PRINCE CASTLE #DHB2PT33WS2 (FUTURE ITEM)
VOLLRATH #72018 SERVER PUMP #83019
BUNN # 04275.0031
X
X
DISHWASHER ON LEFT END
CONTACT ECOLAB: SEE SCOPE OF WORK
P-094
P-097
P-533
(RELOCATED FROM EXIST. STORE)
(RELOCATED FROM EXIST. STORE)
X
REQUIRES FLOOR DRAIN
X
X
X
X
X
X
X
X
P-803
P-XXX
R-011
R-067
R-100
R-400
R-905
SEE SCOPE OF WORK
SEE SCOPE OF WORK (PEPSI PROVIDED)
WITHOUT IMPURITY RING
SEE SCOPE OF WORK (PEPSI PROVIDED)
SEE SCOPE OF WORK (PEPSI PROVIDED)
S-457
S-570
S-580
S-590
S-600
S-663
S-826
S-903
S-907
X
X
X
X
CORNELIUS LBIT MODEL 3D
X
X
SEE SCOPE OF WORK (LIPTON PROVIDED)
S-928
TBD
TBD
TBD
X
X
X
X
X
SEE SCOPE OF WORK (PEPSI PROVIDED)
SEE SCOPE OF WORK (PEPSI PROVIDED)
SEE SCOPE OF WORK (PEPSI PROVIDED)
S-XX2
S-XX3
S-XX4
X
X
X
X
X
X
SEE SCOPE OF WORK
SEE SCOPE OF WORK
SEE SCOPE OF WORK
SEE SCOPE OF WORK
SEE SCOPE OF WORK
U-007
U-901
U-902
U-904
U-909
U-910
X
(1) COOLER, (1) FREEZER
W-XX1
U SECURITY/COMM./FIRE PROT./POS
PRESENCE ALERT SYSTEM
HME #C10810D
FCO - FRONT CASH OUT TERMINAL, CASH DRAWER, CREDIT CARD SWIPE
BOE - BACK ORDER ENTRY TERMINAL
KITCHEN MONITOR
ALARM SYSTEM PANEL
TYCO - E53200146
SUS TICKET PRINTER
W WALK-IN COOLERS/FREEZERS
WALK IN COOLER / FREEZER
X
520 South Main Street, Suite 2531
Akron, OH 44311
330.572.2100 Fax: 330.572.2102
K-925
K-926
K-968
K-968
K-970
K-982
K-XX1
K-XX2
K-XX3
CONTRACT DATE:
09.21.15
BUILDING TYPE:
DBR 37
PLAN VERSION:
009.00.00
SITE NUMBER:
311465 / 434385
STORE NUMBER:
2015388.14
PIZZA HUT
123 Minden Shopping Dr.
Minden, LA 71055
L-067
L-902
1
1
X
X
L LIGHTING/SIGNAGE/MENUBOARDS
DISCO BALL
NO SMOKING SIGN
ADJ #STARBURST
GRAPHICS SYSTEMS, INC.
L-905
L-906
L-907
L-909
L-910
L-912
1
1
2
1
1
1
X
X
X
X
X
X
MEN'S SIGN
WOMEN'S SIGN
HAND WASH SIGN
DELIVERY DRIVERS ONLY SIGN
NO DELIVERIES AFTER 11:00 AM SIGN
HOURS SIGN
GRAPHICS SYSTEMS, INC.
GRAPHICS SYSTEMS, INC.
GRAPHICS SYSTEMS, INC.
GRAPHICS SYSTEMS, INC.
GRAPHICS SYSTEMS, INC.
GRAPHICS SYSTEMS, INC.
X
#PIZNOSMOKESUBDEL
L-067
L-902
L-905
L-906
L-907
L-909
L-910
L-912
DBR 37
NOTE:
L-XX2
L-XX3
L-XX4
4
4
2
X
X
X
COUNTER MENU
LUNCH MENU / PEN HOLDER
EXIT SIGN
VGS
VGS
GRAPHICS SYSTEMS, INC.
L-XX2
L-XX3
L-XX1
B
C
E
F
K
L
P/U CLEARANCE BAR, SECURITY DOOR, WATER HEATER, P/U WINDOW, RESTROOM ACCESSORIES, AIR
DOOR/CURTAIN, MOP SINK, HAND SINK ACC., CORNER GUARDS, MATS
FRYERS, OVENS, GRILLS, RETHERMALIZERS, TOASTERS, MICROWAVES
KITCHEN EXHAUST HOODS, FIRE SUPPRESSION EQUIPMENT
SAFE, OFFICE EQUIPMENT
SHELVING, WORKSTATIONS, CARTS, RACKS, DOLLIES
SITE LIGHTING, SIGNAGE
N
P
R
S
U
W
KITCHEN HAND SINKS, PREP. SINKS, DISHWASHERS
HOT WATER, WORK TABLES, FOOD PREP
REFRIGERATORS AND FREEZERS (NOT WALK-IN)
DRINK SYSTEMS & EQUIP., HEAT CABINETS, WARMERS, SERVING EQUIP., P/U EQUIP.
SECURITY SYSTEM, LOCKS, CCTV, D/T COMMUNICATIONS/POS SYSTEM, POS EQUIP.
WALK-IN COOLERS/FREEZERS
EQUIPMENT
SCHEDULE
A2.1
PLOT DATE:
N
O
I
T
C
Y
U
L
R
N
T
O
S
S
N
E
O
S
C
O
D
P
R
R
A
U
N
P
I
U
D
I
O
B
H
C OR
F
520 South Main Street, Suite 2531
Akron, OH 44311
330.572.2100 Fax: 330.572.2102
8
6
12
11
18
2
2
15
15
1
16
15
5
17
13
3
15
15
21'-9"
15
7
14
13
12
11
19
8
6
9
10
1
15
9'-11"
9
10
18
16
14
CONTRACT DATE:
4
BUILDING TYPE:
DBR 37
PLAN VERSION:
009.00.00
SITE NUMBER:
311465 / 434385
STORE NUMBER:
ROOF PLAN
WATERPROOFING:
A. TOP NAILING AT PARAPET CAP FLASHING WILL NOT BE ACCEPTED.
B. PENETRATIONS IN ROOFING MEMBRANE AND FLASHING SHALL ONLY BE MADE AS
INDICATED ON THE DRAWINGS OR SPECS.
SEE SPECIFICATIONS FOR SEALANT SPECS.
C. ALL SHEET MTL FLASHING SHALL BE 22 GA MIN.
A
1
ROOFTOP UNIT. INSTALL PLUMB AND LEVEL.
16
EXISTING PARAPET CAP TO REMAIN.
2
KITCHEN HOOD EXHAUST FAN. SEE: MECHANICAL SHEETS & 13 & 14/A7.0.
17
WATER HEATER INTAKE & EXHAUST, SEE 2/P6.0. GC TO COORDINATE LOCATION
WITH PARAPET.
3
RESTROOM EXHAUST FAN. SEE: MECHANICAL SHEETS & 13 & 14/A7.0.
18
WASTE VENT THROUGH ROOF. SEE 10/A7.0 FOR FLASHING ASSEMBLY.
4
METAL CANOPY. SEE SCOPE OF WORK
19
ICE MACHINE CONDENSER ON PRESSURE TREATED BLOCKING. SEE SCOPE OF WORK.
5
REMOVE EXISTING ROOFTOP UNIT, ROOF CURB. REPAIR ROOF DECK, RIGID INSULATION
AND ROOFING TO MATCH EXISTING.
6
POWER / GAS / CONDENSATE ENTRY UNDER HVAC UNIT (PER HVAC MFR. SPECS.)
REFER TO MECH. AND PLUMB DWGS. UTILITY ACCESS FROM WITHIN CURB - NO ROOF
PENETRATIONS. DO NOT RUN ON ROOF SURFACE.
7
WALK-IN COOLER / FREEZER CONDENSERS ON PRESSURE TREATED BLOCKING. SEE
SCOPE OF WORK SHEET.
MISCELLANEOUS:
A. ROOF PENETRATIONS CLOSER THAN 12" FROM ANOTHER WILL NOT BE ALLOWED.
B. EXHAUST FANS MIN. 10'-0" AWAY FROM ALL AIR INTAKE / SUPPLY.
1/4"=1'-0"
09.21.15
2015388.14
PIZZA HUT
123 Minden Shopping Dr.
Minden, LA 71055
ROOF INSULATION:
A. RIGID BOARD, INSULATION TYPE 3. REFER TO SPECIFICATION SECTION 07210.
B. BOARD THICKNESS TO BE DETERMINED BY SITE-SPECIFIC REGIONAL REQUIREMENTS;
1/4" MINIMUM (PER ROOFING SYSTEM STANDARD).
DBR 37
8
OUTSIDE AIR INTAKE FOR ROOFTOP UNIT. MAINTAIN MIN 10'-0" SEPARATION FROM
PLUMBING VENTS, FLUES AND BUILDING EXHAUST.
ROOFING SYSTEM:
9
A. DURO-LAST SINGLE-PLY SYSTEM. REFER TO SPECIFICATIONS SECTION 07523.
B. G.C. SHALL COORDINATE ALL INSTALLATION REQUIREMENTS.
10
PIPE HOOD FOR CONDENSER LINES. SEE DETAIL 9/A7.0.
ROOF PLAN
DOWNSPOUT AND GUTTER.
11
ROOF CRICKETS:
MAINTAIN MFR'S ROOFTOP UNIT MAINT CLEARANCE.
A. CRICKETS @ ROOFTOP EQUIPMENT SHALL BE FORMED WITH TAPERED INSULATION TO
SUCH AN EXTENT AS TO PROVIDE A POSITIVE MIN. 1/2" SLOPE TO THE VALLEY.
12
HVAC ROOF CURB. SEE DETAIL 16/A7.0.
13
A3.0
EXISTING ROOFING TO REMAIN.
14
SEE SCOPE OF WORK FOR WALL SIGNAGE, TYP.
15
ROOF CRICKET.
NOT USED
C
ROOF PLAN NOTES
C
KEY NOTES
B
PLOT DATE:
13
12
N
O
I
T
C
Y
U
L
R
N
T
O
S
S
N
E
O
S
C
O
D
P
R
R
A
U
N
P
I
U
D
I
O
B
H
C OR
F
3
520 South Main Street, Suite 2531
Akron, OH 44311
330.572.2100 Fax: 330.572.2102
11
2
1
5
4
6
16
15
14
5
4
17
6
2
11
10
14
14
11
9
18
10
LEFT SIDE ELEVATION
1/4"=1'-0"
A
12
11
3
4
5
13
4
5
15
1
11
15
5
6
2
17
2
6
2
8
4
4
7
1
11
FRONT ELEVATION
1/4"=1'-0"
C
FRONT ELEVATION
QTY.
NOTE
SIGNAGE VENDOR TO PROVIDE
TRANSFORMERS TO GC PRIOR
TO INTERIOR DRYWALLING. GC
TO INSTALL TRANSFORMERS
12" MINIMUM ABOVE TRUSS
BEARING LINE AND STUB OUT
ELECTRICAL PER LOCATIONS
SHOWN. ROUTE ALL CONDUIT
IN THE EXTERIOR WALL.
ITEM
1/4"=1'-0"
B
ELEC
1
2
DBR 40" PIZZA HUT SIGN
X
2
2
DBR 72" DIAM. SWIRL SIGN
X
5
1
DBR 18" CANOPY
X
6
MISC
DBR METAL BEAM
X
7
MISC
DBR CORNER LED
X
CONTRACT DATE:
NO CONDUIT IS TO PENETRATE
THE ROOF.
09.21.15
BUILDING TYPE:
DBR 37
PLAN VERSION:
009.00.00
SITE NUMBER:
311465 / 434385
STORE NUMBER:
2015388.14
PIZZA HUT
123 Minden Shopping Dr.
Minden, LA 71055
SIGNAGE DETAIL
SYMBOL
PRODUCT
NTS
MANUFACTURER
J
NOT USED
COLOR
ALTERNATE MFR.
PAINT
SHERWIN WILLIAMS
MACADAMIA #SW6142
-
-
2
PAINT
SHERWIN WILLIAMS
TRICON BLACK #SW6528
-
-
STANDING SEAM
5
METAL
H
REMARKS
1
4
NTS
NOT USED
NTS
E
MISCELLANEOUS
A. SEE SHT A1.1 "WINDOW TYPES" FOR WINDOW ELEVATIONS.
B. SEE SCOPE OF WORK FOR RESPONSIBILITIES.
AEP SPAN
COOL RED 16" STRAITED
-
-
SEALERS (REFER TO SPECS):
A. SEALANT AT ALL WALL AND ROOF PENETRATIONS.
B. SEALANT AT ALL WINDOW AND DOOR FRAMES AT HEAD AND JAMB. DO NOT SEAL SILL @
WINDOWS.
SHERWIN WILLIAMS
TRICON BLACK #SW6528
-
-
LEGEND:
A. VENDOR SCOPE INCLUDES SUPPLY AND INSTALLATION OF AWNINGS,
CANOPIES, AND SIGNAGE.
EXTERIOR FINISH SCHEDULE
G
GENERAL NOTES
F
SIGNAGE & AWNING SCHEDULE
D
NOT USED
NTS
1
NOT USED.
14
L.E.D. LIGHTING. SEE ELECTRICAL
2
EXISTING E.I.F.S. TO REMAIN. PATCH AND REPAIR AS REQUIRED. SKIMCOAT
WHERE SIGNS ARE REMOVED.
15
METAL AWNING, SEE SCOPE OF WORK
16
3
EXISTING METAL ROOF TO REMAIN.
PRE-FINISHED METAL WALL PANELS - REF. SPECS.
17
4
EXISTING GUTTER AND DOWNSPOUT TO REMAIN.
EMERGENCY LIGHTING, RE: ELECTRICAL
5
EXISTING BUILDING LIGHTING TO REMAIN.
6
NOT USED.
7
EXISTING HM DOOR AND FRAME. PAINT.
8
REWORK EXISTING ALUMINUM STOREFRONT SEE SHEET A1.1.
9
EXISTING HOSE BIBB TO REMAIN.
10
NEW ALUMINUM STOREFRONT DOOR AND WINDOW
11
EXISTING SPLIT FACED CMU TO REMAIN.
12
INDICATES ROOF OR PARAPET BEYOND
13
SIGNAGE, RE: DETAIL J/A4.0 AND SCOPE OF WORK
D
DBR 37
EXTERIOR
ELEVATIONS
A4.0
KEY NOTES
C
PLOT DATE:
N
O
I
T
C
Y
U
L
R
N
T
O
S
S
N
E
O
S
C
O
D
P
R
R
A
U
N
P
I
U
D
I
O
B
H
C OR
F
N
O
I
T
C
Y
U
L
R
N
T
O
S
S
N
E
O
S
C
O
D
P
R
R
A
U
N
P
I
U
D
I
O
B
H
C OR
F
520 South Main Street, Suite 2531
Akron, OH 44311
330.572.2100 Fax: 330.572.2102
NOT USED
NTS
18
NOT USED
STANDARD CURB BASE,
FASTEN PER MFR'S
RECOMMENDATIONS
PREFABRICATED CUSTOM
CURB FLASHING
14
SCHEDULE ROOF
DECK and ROOF
OPENING SUPPORT
2x SOLID BLOCKING
STACKED W/ DRILLED
HOLE FOR PIPE
PENETRATION
8" MIN.
HINGED BASE FOR SERVICING/
CLEANING.
SEAL WITH APPROVED MATERIAL
40" MIN.
KNOCK-DOWN FLAT METAL CURB SEE SCOPE OF WORK
5/8" PLYWOOD SECURED TO CURB
-
4
2X4 WOOD STUDS
AT 16" O.C.
GROUT CORES
SOLID
SEALANT @
PENETRATION
SEALED PIPE FLASHING
KITCHEN HOOD EXHAUST FAN
1" HEAD NAILS AT 6" O.C.
8" MIN.
T.O. CURB TO T.O. ROOF
FILL AREA AROUND PIPING
W/ FOAM INSULATION TO
SEAL SPACES
1 1/2"=1'-0"
10
NOT USED
N.T.S.
6
STANDING SEAM
METAL SIDING
NEW BEAM SEE
STRUCTURAL
DRAWINGS
MULTI PIPE GROUPING PIPE SLOPING DOWN
AWAY FROM SHROUD
MIN. 24 GA. G.I. PIPE
ENCLOSURE COVER
PRE-FABRICATED VENTILATED CURB
EXTENSION
NEMA 3R FUSED DISCONNECT,
MOUNT TO HINGED BASE, SEE ELEC.
1" HEAD NAIL @ 6" O.C.
SHEET METAL COUNTER FLASHINGWRAPS TOP & OUTSIDE OF CURB,
EXTENDING OVER BASE FLASHING
SCREW THRU NEOPRENE
WASHER , 3 PER SIDE
PREFABRICATED GALV. STEEL CURB
W/ INSULATION
(2) 2x12 WD CURB OVER 2x
SECURED TO DECK
CURB FLASHING
TAPERED SLEEPER TO LEVEL CURB
ROOFING MATERIAL OVER RIGID
INSULATION
NOTE:
EXHAUST FAN SHALL BE
LEVEL WITHIN 1/8" OVER
WIDTH OF CURB
NOTE:
RTU SHALL BE LEVEL
WITHIN 1/8" OVER LENGTH
OF EQUIPMENT
SCHEDULE ROOF
DECK and ROOF
OPENING
SUPPORT
SCHEDULE ROOF DECK and
ROOF OPENING SUPPORT
HVAC CURB
3"=1'-0"
16
BASE FLASHING
DUCT WRAP - SEE MECHANICAL
N.T.S.
ANODIZED ALUMINUM WINDOW
FRAME - SEE WINDOW SCHEDULE.
ALIGN FRAME WITH FACE OF
PLYWOOD SHEATHING.
SCHEDULE ROOF DECK and
ROOF OPENING SUPPORT
MIN. 16 GA. WELDED DUCT
EXHAUST FAN CURB
WRAP LEDGER BOARDS IN
BREAK METAL BY AWNING
CONTR.
2X HEADER WITH
1/2" PLYWOOD - SEE
STRUCTURAL
CONTRACT DATE:
WRAP GYP. BD. TO FRAME
SEALANT AND BACKER ROD
13
MULTIPLE PIPE FLASHING
1-1/2" = 1'-0"
9
NOT USED
3"=1'-0"
6
ENTRY AWNING / TRANSOM HEAD
DBR 37
PLAN VERSION:
009.00.00
SITE NUMBER:
3"=1'-0"
2
09.21.15
BUILDING TYPE:
311465 / 434385
STORE NUMBER:
2015388.14
PIZZA HUT
123 Minden Shopping Dr.
Minden, LA 71055
ALUM STOREFRONT ENTRY
SYSTEM
ALUMINUM STOREFRONT
SYSETM
DOOR SILL. REF: DOOR
SCHEDULE
EXPANSION JOINT
DBR 37
METAL FLASHING WITH
WEEP HOLES
1/2"
MAX
1'-2"
NOTE:
EXHAUST FAN SHALL
BE LEVEL WITHIN 1/8"
OVER WIDTH OF
CURB
1-1/2" = 1'-0"
NOT USED
NEW SPLIT FACED
CMU TO MATCH
EXISTING
ROOFING MATERIAL
EXHAUST FAN CURB
UNIT COUNTERFLASHING W/
NEOPRENE PERIMETER GASKET
7
DURO-LAST ROOFING
MATERIAL OVER RIGID
INSULATION
(2) TAPERED 2x12 WD
CURB OVER 2x
SECURED TO DECK
SCHEDULE ROOF DECK and
ROOF OPENING SUPPORT
HVAC UNIT
6" = 1'-0"
DURO-LAST
PRE-FABRICATED VENT
STACK FLASHING
8" MIN.
SCREW THRU NEOPRENE
WASHER , 3 PER SIDE
17
NOT USED
S.S. BAND POSITIONED
1/4" FROM TOP OF
STACK FLASHING
GALVANIZED NAILS @
6" O.C.
3" = 1'-0"
11
TYPICAL VENT PIPE
ELECTRICAL CONDUIT
NOT USED
1-1/2"=1'-0"
EXTERIOR
CONSTRUCTION
DETAILS
CONC SIDEWALK
CONC SIDEWALK
EXPANSION JOINT
NOT USED
1-1/2"=1'-0"
15
NOT USED
N.T.S.
11
NOT USED
3" = 1'-0"
8
DOOR SILL
3"=1'-0"
5
A7.0
STOREFRONT SILL DETAIL
3"=1'-0"
1
PLOT DATE:
N
O
I
T
C
Y
U
L
R
N
T
O
S
S
N
E
O
S
C
O
D
P
R
R
A
U
N
P
I
U
D
I
O
B
H
C OR
F
520 South Main Street, Suite 2531
Akron, OH 44311
330.572.2100 Fax: 330.572.2102
B-1
B-1
B-1
T-1
T-1
T-1
TYP. @ ALL KITCHEN AREAS
TYP. @ ALL KITCHEN AREAS
TYP. @ ALL KITCHEN AREAS
10
11
10
10
9
5
10
3
6
11
5
2
F-1
T-1
B-2
6
F-1
F-1
7
B-3
B-3
F-1
B-3
1
F-1
6
F-1
B-2
B-2
7
7
CONTRACT DATE:
BUILDING TYPE:
DBR 37
PLAN VERSION:
009.00.00
SITE NUMBER:
311465 / 434385
STORE NUMBER:
FLOOR FINISH PLAN
1/4"=1'-0"
A. SEE SPECS FOR PAINTING, GYPSUM BOARD AND TILE.
1
FACTORY FLOOR FINISH (GALV STL) W/ INTEGRAL COVE BASE AND BUILT-IN INT. RAMP.
B.
2
CONTRACTOR SHALL PROVIDE FLOOR TILE INSIDE WALK-IN COOLER, BASE TILE
PROVIDED WITH COOLER. FLOAT FLOOR TILE IN COOLERS TO DRAIN TO KITCHEN.
COORD. WITH COOLER WALL CONFIGURATION
3
5/8" CEMENT BOARD PLATFORM AT SAFE LOCATION. SEE DETAIL 13/A11.0.
4
NOT USED.
5
FLOOR SINK - REF. P2.0
6
FLOOR DRAIN - REF. P2.0
7
SANITARY TILE BASE IN RESTROOMS. SEE DETAIL 6/A11.0 FOR INSTALLATION.
8
NOT USED.
9
MOP SINK LOCATION
F-#
DENOTES FINISH MATERIAL. REFER TO SHT A8.1 FOR FINISHES.
B-#
C. TILE JOINTS (U.O.N.):
1. FLOOR TILE
2. FLOOR FINISH TILE
3. BASE, TRIM AND ACCESSORIES: MATCH ADJOINING TILE UNITS
D. FLOOR TILE JOINTS SHALL MATCH UP WITH SLAB JOINTS.
E.
ALL BASE TILE SHALL BE SANITARY COVE STYLE WITH 3/8" MIN RADIUS.
F.
SEE SCOPE OF WORK SHEETS FOR RESPONSIBILITIES.
G. PROVIDE CLEAR SILICONE CAULK WHERE FRP STOPS AT TOP OF COVE BASE.
H. PROVIDE CLEAR SILICONE CAULK WHERE ALL FIXED AND BUILT-IN COUNTERS /
EQUIPMENT ABUTS WALL SURFACE.
I.
ALL INTERIOR FINISHES SHALL HAVE CLASS 1 FIRE RATING.
10
LINE OF FLOOR FINISH TRANSITION
11
8" DIA. PVC STUB DOWN BELOW SLAB.
A
09.21.15
2015388.14
PIZZA HUT
123 Minden Shopping Dr.
Minden, LA 71055
DBR 37
FLOOR
FINISH PLAN
A8.0
NOT USED
D
FINISH NOTES
C
KEY NOTES
B
PLOT DATE:
FLOORS
SYM
WALLS
DESCRIPTION
ALTERNATE/NOTES
SYM
LAMINATES / MISC
DESCRIPTION
ALTERNATE/NOTES
SYM
DESCRIPTION
CEILINGS
ALTERNATE/NOTES
DESCRIPTION
SYM
NOTES
N
O
I
T
C
Y
U
L
R
N
T
O
S
S
N
E
O
S
C
O
D
P
R
R
A
U
N
P
I
U
D
I
O
B
H
C OR
F
F-1
MFR:
TYPE:
NAME:
COLOR #:
SIZE:
GROUT:
SEALER:
T-1
T-2
MFR.:
TYPE:
COLOR:
SIZE:
GROUT:
SEALER:
MFG:
TYPE:
NAME:
COLOR #:
FIANDRE USA
PORCELAIN TILE
SHELLSTONE
SHELLSTONE
12" x 24" OR 18" x 36"
POLYBLEND GROUT #185
NEW TAUPE
AQUA MIX SEALER'S CHOICE (SEAL
GROUT ONLY). ALTERNATE
SEALER: MIRACLE SEALANTS 511
IMPREGNATOR.
ITEM:
MFG.:
COLOR:
COLOR #:
POLISHED CONCRETE, MEDIUM GRADE (MG-2)
FRP-1 ITEM:
FRP
L & M CONSTRUCTION CHEMICALS
MFG.:
MAR-LITE
VIVID DYE
PRODUCT #: P-100
COCOA BROWN 100%
NAME:
FRP
POLYBLEND #52 TOBACCO BROWN GROUT
@ SAW CUTS
SEALER:
AQUA MIX SEALER'S CHOICE (SEAL GROUT
W-1
MFR:
GLEN GARY
ONLY). ALTERNATE SEALER: MIRACLE SEALANTS
TYPE:
THIN BRICK 1/2"
COLOR:
MILWAUKEE, RUNNING BOND PATTERN
511 IMPREGNATOR.
SIZE:
1/2" x 2 1/4" x 7 5/8"
MORTAR:
NATURAL GREY PIPED, ROUGH RAKED
LOCATION: DINING ROOM & RESTROOMS
CROSSVILLE
PORCELAIN TILE
GREY MINGLE
CROSS TREAD 8" x 8"
POLYBLEND GROUT #335 WINTER GREY
AQUA MIX SEALER'S CHOICE (SEAL GROUT
ONLY). ALTERNATE SEALER: MIRACLE
SEALANTS 511 IMPREGNATOR.
LOCATION: B.O.H. & SERVICE LINE FLOORING
RESILIENT FLOORING - VCT
ARMSTRONG
EXCELON IMPERIAL TEXTURE
CLASSIC BLACK #51910
LOCATION: BOOTH RAISED PLATFORM
FLOORING
WALL BASE
SYM
B-1
B-2
B-3
DESCRIPTION
MFR.:
TYPE:
COLOR:
SIZE:
GROUT:
SEALER:
LOCATION: B.O.H. & SERVICE LINE
MFG:
ITEM:
NAME:
COLOR:
SIZE:
GROUT:
COVE TRIM:
DALTILE
PORCELAIN TILE
ALTA VISTA
SUNSET GOLD #AV51
6" X 12"
POLYBLEND GROUT #380 HAYSTACK
SCHLUTER #DILEX-AHKA (BRUSHED STEEL)
LOCATION: RESTROOMS
MFR.:
TYPE:
COLOR:
SIZE:
ARMSTONG
VINYL COVE BASE
JET BLACK
4"
LOCATION: BASE AT WOOD WAINSCOT & RAISED
BOOTH PLATFORM
M-1
USE THIN TECH - CLASSIC SERIES
M-2
LOCATION: F.O.H. WALLS
W-2
MFR:
NAME:
SIZE:
GROUT:
USE BRUSHED STEEL VERTICAL TRANSITION AT
IRIS CERAMICS US
MAIOLICA ROSSO
OUTER CORNERS: SCHLUTER - QUADEC-EB
4" x 12", HORIZONTALLY LAID RUNNING BOND
POLYBLEND GROUT #60 CHARCOAL
LOCATION: FEATURE COOK LINE VERTICAL WALL
W-3
MFR:
TYPE:
NAME:
COLOR:
SIZE:
GROUT:
DALTILE
PORCELAIN TILE
ALTA VISTA
SUNSET GOLD AV51
12" x 12"
POLYBLEND GROUT #380 HAYSTACK
LOCATION: RESTROOM WALLS
ST-1
MFR:
TYPE:
SPECIES:
STAIN:
ITEM:
MFG:
COLOR:
REMARKS:
MINWAX
OIL BASED WOOD STAIN
BIRCH PLYWOOD
GOLDEN OAK #210B
CLEAR COAT LACQUER
OIL BASED WOOD STAIN
#T77F62
MEDIUM RUBBED EFFECT
LOCATION: RESTROOM HALLWAY WAINSCOT
P-1
ITEM:
MFG.:
TYPE:
COLOR:
TEXTURE:
PAINT
SHERWIN WILLIAMS
SEMI-GLOSS ENAMEL
MACADAMIA #SW6142
LIGHT ORANGE PEEL
LOCATION: LOWER BULKHEAD FACE (TV WALL),
RESTROOM HALL & UPPER RESTROOM WALLS
P-2
ITEM:
MFG.:
TYPE:
COLOR:
TEXTURE:
PAINT
SHERWIN WILLIAMS
SEMI-GLOSS ENAMEL
FOOTHILLS #SW7514
LIGHT ORANGE PEEL
LOCATION: UPPER BULKHEAD FACE
P-3
ITEM:
MFG.:
TYPE:
COLOR:
TEXTURE:
PAINT
SHERWIN WILLIAMS
SEMI-GLOSS ENAMEL
SUNDEW #SW7688
LIGHT ORANGE PEEL
LOCATION: BULKHEAD SOFFIT
P-4
ITEM:
MFG.:
TYPE:
COLOR:
TEXTURE:
PAINT
SHERWIN WILLIAMS
FLAT ENAMEL
TRICORN BLACK #SW6258
LIGHT ORANGE PEEL
LOCATION: DINING ROOM BLADE ELEMENT
P-5
ITEM:
MFG.:
TYPE:
COLOR:
TEXTURE:
PAINT
SHERWIN WILLIAMS
FLAT ENAMEL
BLACK FOX #SW7020
LIGHT ORANGE PEEL
LOCATION: MISC CEILING FIXTURES AT AND ABOVE
BOTTOM OF TRUSSES IN DINING SPACE
ALTERNATE/NOTES
CROSSVILLE
PORCELAIN STONE
GREY MINGLE
6"x8" COVE BASE
POLYBLEND GROUT #335 WINTER GREY
AQUA MIX SEALER'S CHOICE (SEAL GROUT
ONLY). ALTERNATE SEALER: MIRACLE
SEALANTS 511 IMPREGNATOR.
LOCATION: B.O.H. WALLS
MFR:
ITEM:
COLOR:
WILSONART
PLASTIC LAMINATE
MOUNTAIN PASSAGE #1843K-45
LOCATION: MILLWORK INSETS
MFR:
ITEM:
COLOR:
THICKNESS:
WILSONART
SOLID SURFACE
NIGHT STARS #9105CS(5)
1/2" MIN THICKNESS
LOCATION: ALL COUNTERTOPS
CL-1
CL-2
CL-3
ITEM:
MFG.:
COLOR:
LOCATION:
PAINTED STRUCTURE
SHERWIN WILLIAMS
BLACK FOX #SW7020
DINING ROOM
EXPOSED ROOF TRUSS AND 1" TECTUM SOUND
ABSORPTION BOARD APPLIED TO THE BOTTOM OF
ROOF DECK, BETWEEN TRUSSES, PAINT TO MATCH
TRUSSES. INCLUDING DUCT, CONDUIT, HANGERS,
AND SIMILAR EXPOSED ITEMS.
ITEM:
MFG.:
TYPE:
COLOR:
PAINTED GYPSUM BOARD CEILING
SHERWIN WILLIAMS
SEMI-GLOSS ENAMEL
TOWNHALL TAN #SW7690
SMOOTH - NO TEXTURE
ITEM:
MFG.:
TYPE:
SIZE
CEILING TILE & GRID
GYPSUM LAY IN PANEL
WHITE VINYL WITH STIPPLE PATTERN
1/2" x 24" x 24"
LOCATION: RESTROOM HALLWAY
ACOUSTICAL CEILING GRID SHALL BE EQUAL TO
ARMSTRONG PRELUDE 15/16" OR US GYPSUM
ENVIRONMENTAL ZXA GRID SYSTEM. WIDE FACED,
ALUMINUM CAPPED, DOUBLE WEB, HOT DIP
GALVANIZED STEEL, INTERMEDIATE DUTY, HIGH
HUMIDITY FINISH, PAINTED WHITE.
ALTERNATE:
MFR: ARMSTRONG
TYPE: #793 GEORGIAN HIGH WASHABILITY
COLOR: WHITE
SIZE: 1/2" x 24" x 24"
LOCATION: KITCHEN AND RESTROOM
CEILING
CONTRACT DATE:
DOORS/TRIM
SYM
ST-1
1.
INSTALL FRP PANELS ON WALLS FROM TOP OF TILE BASE TO BOTTOM OF CEILING
GRID EXCEPT WHERE CERAMIC TILE IS INDICATED. INSTALL FRP ON KITCHEN SIDE
OF SERVING COUNTER WALL.
2.
GALV STEEL WALL AND CEILING FINISHES BY WIC / WIF BOX MFR.
3.
REFER TO INTERIOR ELEVATIONS FOR LOCATIONS OF TILE AND FRP.
4.
FOR FINISH LOCATIONS REFER TO:
SHEETS A4.0 & A4.1 - EXTERIOR ELEVATIONS
SHEET A8.0 - FLOOR FINISH PLAN
SHEET A9.0 - REFLECTED CEILING PLAN
SHEETS A10.0 TO A10.4 - INTERIOR ELEVATIONS
5.
MARLITE
CUSTOMER SERVICE
800-377-1221
www.marlite.com
ARMSTRONG
STEVE PATTERSON
214-755-9186
BLIND EXPRESS, INC.
LEE ASKENAS
30 Mansell Court, Suite 108
Roswell, GA 30076
P: 770-664-1688
F: 770-664-1191
[email protected]
ALL INTERIOR FINISHES SHALL HAVE CLASS 1 FIRE RATING.
WILSONART INTERNATIONAL, INC.
TERESA HUMPHRY
214-634-2310
[email protected]
ECO-LAB
NATE DAMRO
3309 MATRIX DRIVE
phone: 651-293-4205
ALTERNATE/NOTES
ALL TRIM IS 1X4 UNLESS NOTED OTHERWISE
- 1X2 TRIM BETWEEN PLYWOOD JOINTS
MFR:
TYPE:
SPECIES:
STAIN:
ITEM:
MFG:
COLOR:
REMARKS:
MINWAX
OIL BASED WOOD STAIN
RED OAK
GOLDEN OAK #210B
CLEAR COAT LACQUER
OIL BASED WOOD STAIN
#T77F62
MEDIUM RUBBED EFFECT
P-6
ITEM:
MFG.:
TYPE:
COLOR:
PAINT
SHERWIN WILLIAMS
SEMI-GLOSS ENAMEL
BLACK FOX #SW7020
LOCATION: DINING & RESTROOM DOORS &
FRAMES
P-7
ITEM:
MFG.:
TYPE:
COLOR:
PAINT
SHERWIN WILLIAMS
SEMI-GLOSS ENAMEL
GREY CLOUDS #SW7658
LOCATION: B.O.H. EXIT DOORS & FRAMES
IRIS CERAMICS US
NOREEN SCHERTLER
312-342-4689
GLEN GERY BRICK
MIKE SCHMEDDING
816-589-3956
DESCRIPTION
LOCATION: WAINSCOT / CHAIR RAIL & MISC TRIM IN
DINING / RESTROOM HALL
ROOM FINISH NOTES
D
09.21.15
BUILDING TYPE:
DBR 37
PLAN VERSION:
009.00.00
SITE NUMBER:
311465 / 434385
STORE NUMBER:
2015388.14
PIZZA HUT
123 Minden Shopping Dr.
Minden, LA 71055
DBR 37
CROSSVILLE
TONI HALE
931-456-3997
DALTILE
SHANNON HOPKINS
214-392-3000
[email protected]
520 South Main Street, Suite 2531
Akron, OH 44311
330.572.2100 Fax: 330.572.2102
FINISH
SCHEDULES
NOTE:
CONTRACTOR SHALL REQUEST
"PIZZA HUT NATIONAL PRICING"
WHEN ORDERING MATERIALS
NATIONAL ACCOUNT PRICING-CONTACTS
A8.1
C
ROOM FINISH SCHEDULE LEGEND
A
PLOT DATE:
N
O
I
T
C
Y
U
L
R
N
T
O
S
S
N
E
O
S
C
O
D
P
R
R
A
U
N
P
I
U
D
I
O
B
H
C OR
F
520 South Main Street, Suite 2531
Akron, OH 44311
330.572.2100 Fax: 330.572.2102
1'-2"
1'-821"
1
DRY STORAGE
CL-3 10'-2"
15
DELIVERY
SERVICE
7
CL-3 10'-2"
4
7
CL-3 10'-2"
18
TYP.
7
7'-0"
CL-3
10'-2"
4'-6" TYP.
4
4'-6" TYP.
CL-2
9'-6"
EQ.
DISHWASH
EQ.
13
2
TYP.
2
TYP.
EQ.
18
TYP.
13
4
10
8'-6"
CL-3
COOLER
11
18
TYP.
4
6'-421"
6'-0"
17
10'-0"
6'-0"
17'-2"
17
MEN
11
19
19
19
19
FREEZER
10
DINING
4
CL-1
8'-6"
CL-3
8'-6"
CL-3
WOMEN
11
11
8
TYP.
VESTIBULE
6'-4"
6'-4"
6'-4"
6'-4"
11
4
3"
14'-74
11
2'-021"
4
6'-4"
6'-321"
4
7'-7"
6
18
TYP.
3
CONTRACT DATE:
5
BUILDING TYPE:
DBR 37
PLAN VERSION:
009.00.00
SITE NUMBER:
311465 / 434385
STORE NUMBER:
REFLECTED CEILING PLAN
1
CEILING GRID STARTING POINT.
16
NOT USED.
2
CENTER DOWNLIGHT IN CEILING TILE THROUGHOUT SERVING/BAR. (U.N.O.)
17
MECHANICAL DUCTWORK. PAINT TO MATCH CEILING.
3
RECESSED LED IN SOFFIT BY AWNING CONTRACTOR. SEE SCOPE OF WORK.
18
RECESSED DOWN LIGHT.(TYP.)
SUSPENDED CEILING:
A. ACOUSTICAL PANEL INSTALLATION: INSTALL ACOUSTICAL PANELS WITH EDGES IN
CLOSE CONTACT WITH METAL SUPPORTS AND IN TRUE ALIGNMENT.
B. ALLOWABLE VARIATIONS FROM FLAT AND LEVEL SURFACE: 1/8" IN 10'-0" MAX.
C. ALLOWABLE VARIATIONS FROM PLUMB OF GRID MEMBERS: AS CAUSED BY ECCENTRIC
4
EXTEND WALL TO BOTTOM ROOF DECK.
19
TRACK MOUNTED ON BOTTOM OF JOIST @ 11'-1 1/2" A.F.F.
4'-0" AND 8'-0" LENGTHS AS NOTED.
5
METAL CANOPY WITH LED LIGHTING. SEE SCOPE OF WORK.
6
DISCO BALL STARBURST LIGHT BY AMERICAN DJ SUPPLY.
D. INSTALL SYSTEM AFTER MAJOR ABOVE CLG. WORK IS COMPLETE. COORD LOCATIONS
OF HANGERS WITH RELATED WORK.
E. SEE SPECS FOR ADDITIONAL INFORMATION.
7
PROVIDE BLOCKING ALONG ENTIRE LENGTH OF BULKHEAD BEHIND SUBSTRATE FOR
SHELVING TO BE MOUNTED ALONG BACKSIDE OF BULKHEAD.
8
PENDANT LTG - CENTER OVER TABLE TOP (TYP) SEE DWG A2.0 FOR TABLE LOCATIONS.
9
NOT USED.
10
WALK-IN LIGHTING SUPPLIED BY WALK-IN MFR.
11
EMERGENCY DUAL HEAD FIXTURE. BATTERY UNIT INSIDE ABOVE CLG. SEE ELECT.
DWGS.
12
NOT USED.
13
GYPSUM BOARD BULKHEAD.
14
NOT USED
15
REFER TO SHEETS M3.0, M3.1 AND M3.2 FOR EXHAUST HOOD INFORMATION.
DIMENSIONS:
A. ALL DIMENSIONS ARE TO FACE OF FINISH U.O.N.
1" TECTUM SOUND BOARD
@ ALL EXPOSED CEILINGS
(CL-1)
2'-0" x 4'-0"
FLUORESCENT LIGHT
FIXTURE
S
S
2'-0" x 2'-0"
FLUORESCENT LIGHT
FIXTURE
EXTERIOR WALL FIXTURE
WIRE GUARD FIXTURE
HORIZONTAL MTD.
OUTSIDE SPEAKER
SMALL PENDANT
SPEAKER
P.O.S. MONITOR
C.C.T.V. CAMERA
DOWNLIGHT @ WALK-IN
(BY WALK-IN MFR.)
PENDANT FIXTURE
CEILING FINISHES:
A. REFER TO ROOM FINISH SCHEDULE (SHT A8.1) FOR CLG. FINISHES.
EXTERIOR
EMERGENCY LIGHTS
INTERIOR HIGH OUTPUT
L.E.D. (RED)
C.C.T.V. MONITOR
12" EXHAUST FAN
GYPSUM BOARD CEILING:
A. SUBSTRATE SHALL BE 5/8" THICK TYPE "X" GYP BD.
B. ACOUSTICAL SEALANT: APPLY TO GYP. BD. PANELS AS INDICATED IN SPECS.
GYP. BD. FINISHING AND DECORATING: REFER TO DWGS FOR TEXTURE AND FINISHES.
C. PAINT GRILLES & DIFFUSERS TO MATCH CEILING COLOR.
HVAC RETURN GRILLE
ELECTRICAL:
A. SEE ELECT. DWGS. FOR FIXTURE SCHED.
DOWNLIGHT
EMERGENCY LIGHTS
EXIT LIGHT
(WALL MOUNTED)
GENERAL NOTES
F
EXIT LIGHT
(CEILING MOUNTED)
HVAC SUPPLY DIFFUSER
FIXTURE, TRACK MOUNTED
PENDANT OR DIRECTIONAL
STROBE LIGHT
BACK DOOR SECURITY
CEILING SYMBOL LEGEND
E
REFLECTED CEILING PLAN NOTES
D
1/4"=1'-0"
A
09.21.15
2015388.14
PIZZA HUT
123 Minden Shopping Dr.
Minden, LA 71055
DBR 37
REFLECTED
CEILING PLAN
A9.0
KEY NOTES
B
PLOT DATE:
N
O
I
T
C
Y
U
L
R
N
T
O
S
S
N
E
O
S
C
O
D
P
R
R
A
U
N
P
I
U
D
I
O
B
H
C OR
F
520 South Main Street, Suite 2531
Akron, OH 44311
330.572.2100 Fax: 330.572.2102
P-5
1'-021"
P-5
W-1
15
TV
P-1
1
A11.0
7'-0"
ST-1
10'-1"
P-1
OPEN TO
VESTIBULE
BEYOND
M-1
2
A11.0
M-1
2'-10"
4'-0"
M-2
B-3
B-3
B-3
DINING ROOM
3/8"=1'-0"
ST-1
3
DINING ROOM
P-5
3/8"=1'-0"
2
DINING ROOM
P-1
P-3
UNDER SIDE
OF SOFFIT
P-2
27
27
27
27
27
27
TV
TV
TV
TV
TV
TV
1'-021"
P-2
AND CLIPS WITH 3/8" TEMPERED GLASS
SNEEZE GUARD (TYP.)
U-901
U-901
M-2
3'-6"
2'-10"
3'-6"
6'-0"
2'-10"
4'-10"
OPENING FOR
GLASS
REACH-IN
COOLER
U-901
P-3
UNDER SIDE
OF SOFFIT
7'-0"
P-5
2'-10"
2'-6"
1'-721"
P-1
CARRYOUT
MONITOR
P-2
1
P-5
P-5
P-3
UNDER SIDE
OF SOFFIT
3/8"=1'-0"
CONTRACT DATE:
BUILDING TYPE:
DBR 37
PLAN VERSION:
009.00.00
SITE NUMBER:
M-1
09.21.15
311465 / 434385
STORE NUMBER:
B-3
M-1
M-2
B-3
M-1
M-2
M-1
B-3
M-2
M-2
M-1
B-3
PIZZA HUT
B-3
M-1
DINING ROOM
3/8"=1'-0"
2015388.14
4
123 Minden Shopping Dr.
Minden, LA 71055
1. PROVIDE PROPER 2x BLOCKING AT WALL RECESSED MOUNTED ACCESSORIES.
2. GRAB BARS, FASTENERS AND MOUNTING DEVICES SHALL BE INSTALLED PER ADA
REQUIREMENTS. REFER TO SHEET ADA1.0.
3. REFER TO FLOOR PLAN NOTES FOR BLOCKING AND SUBSTRATE NOTES.
4. LOCATE FLUSH HANDLE ON WIDE SIDE OF STALL.
5. PROVIDE WALL TILE BEHIND ENTIRE MIRROR AREA TO ALIGN MOUNTING SURFACES.
DBR 37
INTERIOR
ELEVATIONS
DINING
6. REFER TO SHEET ADA1.0 FOR MOUNTING HEIGHTS AND CLEARANCES OF
ACCESSORIES AND FIXTURES.
7. ALL DIMENSIONS THIS DRAWING ARE TO FINISH SURFACE.
A10.0
GENERAL NOTES
A
PLOT DATE:
N
O
I
T
C
Y
U
L
R
N
T
O
S
S
N
E
O
S
C
O
D
P
R
R
A
U
N
P
I
U
D
I
O
B
H
C OR
F
520 South Main Street, Suite 2531
Akron, OH 44311
330.572.2100 Fax: 330.572.2102
ST-1
ST-1
ST-1
ST-1
B-3
B-3
4'-0"
M-1
B-3
B-3
SEE SHEET A8.1 FOR FINISH SCHEDULE.
3/8"=1'-0"
4
DINING
3/8"=1'-0"
3
DINING
3/8"=1'-0"
2
DINING
3/8"=1'-0"
1
P-3
UNDER SIDE
OF SOFFIT
U-901
U-901
OPEN TO
DINING
BEYOND
U-901
OPEN TO
DINING
BEYOND
B-292
B-252
B-242
N-062
K-970
N-903
M-2
M2
F-173
B-1
FRP-1
3'-6"
DINING
2'-10"
A
2'-10"
GENERAL NOTES
10'-2"
X-X
M-1
2'-10"
M-1
4'-0"
2'-10"
M-1
4'-0"
M-2
4'-0"
M-2
FRP-1
R-011
R-XX3
B-405
B-1
SERVICE
3/8"=1'-0"
5
CONTRACT DATE:
09.21.15
BUILDING TYPE:
DBR 37
PLAN VERSION:
009.00.00
SITE NUMBER:
311465 / 434385
STORE NUMBER:
2015388.14
PIZZA HUT
123 Minden Shopping Dr.
Minden, LA 71055
DBR 37
INTERIOR
ELEVATIONS
SERVICE
A10.1
PLOT DATE:
N
O
I
T
C
Y
U
L
R
N
T
O
S
S
N
E
O
S
C
O
D
P
R
R
A
U
N
P
I
U
D
I
O
B
H
C OR
F
LIGHT
RE: ELEC.
520 South Main Street, Suite 2531
Akron, OH 44311
330.572.2100 Fax: 330.572.2102
LIGHT
RE: ELEC.
P-1
P-1
7'-6"
P-1
P-6
P-6
7'-6"
P-6
6'-6"
P-1
9"
P-6
P-6
9"
8'-6"
8'-6"
8'-6"
OPEN TO
DINING ROOM
B-2
WOMEN
B-3
5
3/8"=1'-0"
WOMEN
3/8"=1'-0"
4
ST-1
3'-1021"
5'-0"
3'-1021"
ST-1
3'-1021"
ST-1
5'-0"
ST-1
P-6
ST-1
ST-1
B-3
VESTIBULE
3/8"=1'-0"
B-3
3
VESTIBULE
3/8"=1'-0"
2
VESTIBULE
6'-6"
3/8"=1'-0"
1
LIGHT
RE: ELEC.
LIGHT
RE: ELEC.
P-1
B-3
P-6
7'-6"
6'-6"
6'-6"
P-1
7'-6"
6'-6"
6'-6"
MEN
3/8"=1'-0"
11
MEN
2'-10"
2'-10"
8'-6"
W-3
3/8"=1'-0"
10
MEN
3/8"=1'-0"
9
MEN
3/8"=1'-0"
8
WOMEN
3/8"=1'-0"
7
WOMEN
3/8"=1'-0"
6
12'-821"
CONTRACT DATE:
1'-5"
HOLD
6'-3"
9
PLAN VERSION:
009.00.00
5
WOMEN
SEE SHEET
A2.0 FOR
EQUIPMENT
KEYNOTES
7'-521"
2
A10.2
1
2'-0"
CLEAR
3
4
4'-8"
CLEAR
123 Minden Shopping Dr.
Minden, LA 71055
1. PROVIDE PROPER 2x BLOCKING AT WALL RECESSED MOUNTED ACCESSORIES.
5'-0" CLEAR
1'-6"
CLEAR
6
A10.2
2015388.14
5'-0" CLEAR
1'-6"
CLEAR
7
311465 / 434385
PIZZA HUT
2'-0"
CLEAR
2'-6"
CLEAR
1'-3"
MIN.
4'-0"
CLEAR
MEN
SEE SHEET
A2.0 FOR
EQUIPMENT
KEYNOTES
4'-0" CLEAR
A10.2
2'-6"
CLEAR
4'-8" 8
CLEAR
5'-0" CLEAR
DBR 37
STORE NUMBER:
4'-0"
CLEAR
5'-041"
5'-0" MIN
11
7'-6"
BUILDING TYPE:
SITE NUMBER:
10
09.21.15
2. GRAB BARS, FASTENERS AND MOUNTING DEVICES SHALL BE INSTALLED PER ADA
REQUIREMENTS. REFER TO SHEET ADA1.0.
DBR 37
3. REFER TO FLOOR PLAN NOTES FOR BLOCKING AND SUBSTRATE NOTES.
4. LOCATE FLUSH HANDLE ON WIDE SIDE OF STALL.
5. PROVIDE WALL TILE BEHIND ENTIRE MIRROR AREA TO ALIGN MOUNTING SURFACES.
4'-0"
CLEAR
6. REFER TO SHEET ADA1.0 FOR MOUNTING HEIGHTS AND CLEARANCES OF
ACCESSORIES AND FIXTURES.
7. ALL DIMENSIONS THIS DRAWING ARE TO FINISH SURFACE.
4'-1041"
ENLARGED RESTROOM FLOOR PLAN
X-X
3/8"=1'-0"
12
INTERIOR
ELEVATIONS
RESTROOMS
A10.2
SEE SHEET A8.1 FOR FINISH SCHEDULE.
GENERAL NOTES
A
PLOT DATE:
N
O
I
T
C
Y
U
L
R
N
T
O
S
S
N
E
O
S
C
O
D
P
R
R
A
U
N
P
I
U
D
I
O
B
H
C OR
F
520 South Main Street, Suite 2531
Akron, OH 44311
330.572.2100 Fax: 330.572.2102
CONTRACT DATE:
09.21.15
BUILDING TYPE:
DBR 37
PLAN VERSION:
009.00.00
SITE NUMBER:
311465 / 434385
STORE NUMBER:
2015388.14
PIZZA HUT
123 Minden Shopping Dr.
Minden, LA 71055
DBR 37
METRO
SHELVING
ASSEMBLY AIDS
A10.3
PLOT DATE:
ALUM. BRAKE METAL
FINISH TO MATCH ALUM.
STOREFRONT
1/2" PLYWD. ON 1x WOOD BLKG.
2"
2"
(4) #12 S.S. WOOD SCREWS
3/4" LG. W/ S.S. WASHERS.
20 GA. S.S. CORNER GUARD - TOP
OF BASE TO BOTTOM OF CLG. ATTACH W/ CONST. ADHESIVE
GRID
LINE
3"
2x4 WOOD STUD
4x4 STEEL COLUMN
REF. STRUCT.
3"
AIR AND MOISTURE
BARRIER - REF. SPECS.
1/2" GYPSUM BOARD
N
O
I
T
C
Y
U
L
R
N
T
O
S
S
N
E
O
S
C
O
D
P
R
R
A
U
N
P
I
U
D
I
O
B
H
C OR
F
16 GA. BRUSHED STAINLESS STEEL.
1/2" HEM ON TOP AND FRONT EDGES.
20 GA. S.S. END WALL GUARD - TOP
OF BASE TO BOTTOM OF CLG. ATTACH W/ CONST. ADHESIVE
2" FLANGE
BENT 90
DEG.
SAFE PEDESTAL
1-1/2"=1'-0"
YAW020
YAF006
ANCHOR BOLTS - SEE SCOPE OF
WORK - BOLT HOLES = 3/4" DIA. x 3"
DEEP
2"
19
CORNER GUARD
3"=1'-0"
WINDOW SILL BELOW
BOTTOM EDGE OF SPLASH GUARD
SHALL BE EVEN W/ THE EDGE OF
THE HIGHEST ADJ. SINK.
NOTE: CAULK ALL SEAMS AT WALL
SURFACE.
15
GRID
LINE
SPLASH GUARD
N.T.S.
W-6
20 GA. SS CHANNEL ATTACH
W/ CONST. ADHESIVE
EL. +7'-6"
SEALANT + BACKER
ROD
1/2" GYP. BD. ON 1x WOOD BLKG.
PAW040
CONCRETE FLOOR SURFACE
W-4
3"
EXTEND FRONT OF PANEL TO FRONT
EDGE OF ADJ. SINK. APPROX. 24"
(SEE PLAN)
GROUT TO MATCH ADJ. FLOOR.
520 South Main Street, Suite 2531
Akron, OH 44311
330.572.2100 Fax: 330.572.2102
2x6 BOX BEAM HEADER
1/2" RAD. EASED CORNER (TYP.)
WALL FINISH O/ SUBSTRATE PER
PLAN
5/8" CEMENT BD. SIZE 1/2"
SMALLER THAN SAFE FOOTPRINT.
ALUM. STOREFRONT
REF. SPECS.
WINDOW SILL BELOW
221"
SAFE - SEE SCOPE OF WORK FOR
SCOPE DEFINITIONS
SEALANT + BACKER ROD
ALUM. BRAKE METAL
FINISH TO MATCH ALUM.
STOREFRONT
11
WINDOW/COLUMN DETAIL
8
3" = 1'-0"
BULKHEAD @ PICK-UP
3" = 1'-0"
4
NOT USED
3"=1'-0"
3
WALL (WHERE OCCURS)
CEILING TILE & GRID
DOUBLE STUDS AT JAMB
AND HEAD WITH ANCHOR
STRAP.
1/2" GYP. BD.
PAINT
P-4
J MOLD BELOW SUSPENDED
CEILING - FILL J-MOLD W/ SILICONE
PRIOR TO INSTALLING FRP, WIPE
OFF EXCESS
P-1
ST-1
1x1 WOOD TRIM
HM FRAME
FINISH PER ELEVATIONS
ST-1
SUBSTRATE PER PLAN OVER WOOD
STUDS @ 16" O.C.
W-1
THIN BRICK
VENEER
OVER 1/2" GYP BD.
DOOR
TRIM DETAIL
3" = 1'-0"
18
INTERIOR DOOR HEAD / JAMB
3" = 1'-0"
YAW039
SUBSTRATE AS NOTED ON
SHEET A1.0
YAW022
SEALANT
14
NOT USED
3" = 1'-0"
10
FRP @ CEILING
7
3"=1'-0"
WAINSCOT PER ELEVATIONS
SUBSTRATE PER PLAN - PROVIDE 1/4"
GAP BETWEEN SUBSTRATE & CEMENT
BD. BELOW
9'-6" A.F.F.
P-3
2x4 WOOD
BLOCKING FOR
TV'S
1/2" GYP BOARD
CEMENT BD. TO 12" ABOVE
FLOOR- ALL WALLS (EXCEPT @
FRONT & REAR WALLS).
2x4 WOOD BRACING
@ 32" O.C.
COVE BASE TILE
CONTRACT DATE:
CLG. 8'-6"
NOT USED
N.T.S.
17
NOT USED
3"=1'-0"
13
YAF014
P-1
PAW035
STAINED CONCRETE FLOOR
BASE @ RESTROOM
6
3"=1'-0"
JAMB @ RESTROOM VESTIBULE
3"=1'-0"
2
1/2" GYP BOARD
1/2" GYP BOARD
P-1
09.21.15
BUILDING TYPE:
DBR 37
PLAN VERSION:
009.00.00
SITE NUMBER:
311465 / 434385
STORE NUMBER:
2015388.14
PIZZA HUT
123 Minden Shopping Dr.
Minden, LA 71055
FRP
STUD WALL
SUBSTRATE PER PLAN - PROVIDE
1/4" GAP BETWEEN SUBSTRATE &
CEMENT BD. BELOW
DRINK COUNTER
DOOR AS SCHEDULED
CUT FLUSH WITH WALL AND
FILL GAPS WITH FOAM.
6"
6" PVC CHASE FROM BELOW
CEMENT BD. TO 12" ABOVE FLOORALL WALLS (EXCEPT @ FRONT &
REAR WALLS)
DOOR SILL. REF: DOOR
SCHEDULE
2x4 WOOD
BLOCKING FOR
TV'S
EXPANSION JOINT
2x4 WOOD STUD
OR 3 5 8" MTL
STUD FRAMING
DBR 37
WOOD STUDS @ 16" O.C.
J MOLD SET IN SILICONE SEALANT FILL J-MOLD W/ SILICONE PRIOR TO
INSTALLING FRP, WIPE OFF EXCESS
INTERIOR
CONSTRUCTION
DETAILS
CONC SIDEWALK
FIN. FLOOR
PAW034
WALL SECTION
SYRUP CHASE IN WALL
TV - PROVIDED
BY PIZZA HUT
N.T.S.
16
EXTERIOR DOOR SILL
3"=1'-0"
12
EL. +6'-8"
BOTTOM OF 1X TRIM
COVE BASE TILE
P-3
FURR DOWN DETAIL
3" = 1'-0"
9
A11.0
YAW023
CLG. 7'-0"
BOTTOM OF
SOFFIT
FRP @ KITCHEN BASE
3" = 1'-0"
5
BULKHEAD @ RESTROOM VESTIBULE
3"=1'-0"
1
PLOT DATE:
1
A11.3
3
A11.2
2
A11.2
3"
19'-48
N
O
I
T
C
Y
U
L
R
N
T
O
S
S
N
E
O
S
C
O
D
P
R
R
A
U
N
P
I
U
D
I
O
B
H
C OR
F
4'-621"
641"
3"
44
11'-25
8"
3'-1"
520 South Main Street, Suite 2531
Akron, OH 44311
330.572.2100 Fax: 330.572.2102
3'-2"
6"
2'-8"
3'-6"
8"
1'-021"
2'-0"
93
4"
2'-2"
2'-8"
8"
M-2
5'-021"
5"
5'-1016
9
A11.3
3'-05
8"
4'-221"
1
A11.3
3'-621"
5"
2'-416
M-2
1121"
6'-741"
18'-23
8"
8"
6"
AND CLIPS WITH 3/8" TEMPERED GLASS
SNEEZE GUARD (TYP.)
6'-0"
3'-0"
3'-341"
7'-0"
SERVICE/BAR COUNTER
3
A11.3
1
A11.2
M-2
3/4" = 1'-0"
1
9
A11.3
2'-8"
1'-10"
M-2
1'-8"
6"
1"
2'-516
8
A11.3
1'-6"
5'-141"
AND CLIPS WITH 3/8" TEMPERED GLASS
SNEEZE GUARD (TYP.)
5'-2"
2'-0"
3'-9"
CONTRACT DATE:
10'-11"
BUILDING TYPE:
DBR 37
PLAN VERSION:
009.00.00
SITE NUMBER:
311465 / 434385
STORE NUMBER:
ORDER COUNTER
3/4" = 1'-0"
ORDER ENTRY COUNTER
3
3/4"=1'-0"
2
09.21.15
2015388.14
PIZZA HUT
123 Minden Shopping Dr.
Minden, LA 71055
7
A11.3
8
SIM. A11.3
11'-1"
1'-6"
DBR 37
MILLWORK
DETAILS
A11.1
NOT USED
1" = 1'-0"
5
NOT USED
3/4"=1'-0"
4
ENTRY ORDER COUNTER
3/4"=1'-0"
4
PLOT DATE:
N
O
I
T
C
Y
U
L
R
N
T
O
S
S
N
E
O
S
C
O
D
P
R
R
A
U
N
P
I
U
D
I
O
B
H
C OR
F
WOOD TRUSSES - REF.
STRUCTURAL
WOOD TRUSSES - REF.
STRUCTURAL
11'-1 1/2"
WOOD TRUSSES - REF.
STRUCTURAL
11'-1 1/2"
1/2" GYP. BD. ON 2x4
WOOD FRAMING @
16" O.C. - PAINT
11'-1 1/2"
1/2" GYP. BD. ON 2x4
WOOD FRAMING @
16" O.C. - PAINT
1/2" GYP. BD. ON 2x4
WOOD FRAMING @
16" O.C. - PAINT
3'-8"
3'-8"
2x4 WOOD BRACING
@ 32" O.C.
3'-8"
2x4 WOOD BRACING
@ 32" O.C.
9'-6"
2x4 WOOD BRACING
@ 32" O.C.
9'-6"
9'-6"
1/2" GYP. BD. ON 2x4
WOOD FRAMING @
16" O.C. - PAINT
1/2" GYP. BD. ON 2x4
WOOD FRAMING @
16" O.C. - PAINT
1/2" GYP. BD. ON 2x4
WOOD FRAMING @
16" O.C. - PAINT
LIGHT FIXTURE REF. ELEC.
LIGHT FIXTURE REF. ELEC.
LIGHT FIXTURE REF. ELEC.
T.V. - REF.
EQUIPMENT PLAN PROVIDE WOOD
BLOCKING
T.V. - REF.
EQUIPMENT PLAN PROVIDE WOOD
BLOCKING
T.V. - REF.
EQUIPMENT PLAN PROVIDE WOOD
BLOCKING
1/2" GYP. BD. ON 2x4
WOOD FRAMING @
16" O.C. - PAINT
1/2" GYP. BD. ON 2x4
WOOD FRAMING @
16" O.C. - PAINT
1/2" GYP. BD. ON 2x4
WOOD FRAMING @
16" O.C. - PAINT
7'-0"
7'-0"
CL-3 A.C.T. - REF.
REFLECTED CLG. PLAN
6
A11.3
7'-0"
CL-3 A.C.T. - REF.
REFLECTED CLG. PLAN
M-2 1/2" SOLID SURFACE
ON 3/4" PLYWOOD
921"
2'-0"
520 South Main Street, Suite 2531
Akron, OH 44311
330.572.2100 Fax: 330.572.2102
6
A11.3
M-2 1/2" SOLID SURFACE
BEYOND
3'-6"
CL-3 A.C.T. - REF.
REFLECTED CLG. PLAN
921"
3"
1'-016
2'-8"
97
8"
CONTRACT DATE:
M-2 1/2" SOLID SURFACE
ON 3/4" PLYWOOD
M-2 1/2" SOLID SURFACE
ON 3/4" PLYWOOD
6
A11.3
1x4 WOOD TRIM STAINED ST-1
6
A11.3
6
A11.3
2'-10"
DBR 37
PLAN VERSION:
009.00.00
311465 / 434385
STORE NUMBER:
6
A11.3
2"
2015388.14
PIZZA HUT
3'-6"
123 Minden Shopping Dr.
Minden, LA 71055
R-XX3
AMBER LED
LIGHT STRIP
1x4 WOOD TRIM STAINED ST-1
BUILDING TYPE:
SITE NUMBER:
2'-8"
09.21.15
1x4 WOOD TRIM STAINED ST-1
8" MIN.
M-1 PLASTIC
LAMINATE OVER 3/4"
PLYWOOD ON 2x4
WOOD FRAMING @
16" O.C.
M-1 PLASTIC
LAMINATE OVER 3/4"
PLYWOOD ON 2x4
WOOD FRAMING @
16" O.C.
FRP-1 FRP
M-1 PLASTIC
LAMINATE OVER 3/4"
PLYWOOD ON 2x4
WOOD FRAMING @
16" O.C.
FRP-1 FRP
1/2" HILTI HIT HY150
1/2" HILTI HIT HY150
ADHESIVE ANCHOR @
16" O.C. STAGGERED.
ADHESIVE ANCHOR @
16" O.C. STAGGERED.
11" MIN.
1x4 WOOD TRIM STAINED ST-1
1x4 WOOD TRIM STAINED ST-1
B-1 TILE BASE
SECTION AT SALAD STATION
1 1/2" =1'-0"
B-3 RUBBER BASE
3
MILLWORK
DETAILS
ADHESIVE ANCHOR @
16" O.C. STAGGERED.
1/2" HILTI HIT HY150
1x4 WOOD TRIM STAINED ST-1
B-3 RUBBER BASE
DBR 37
FRP-1 FRP
6" MIN.
B-1 TILE BASE
SECTION AT FRONT BAR
B-3 RUBBER BASE
1 1/2" = 1'-0"
2
A11.2
B-1 TILE BASE
SECTION AT ENTRY POS
1 1/2" = 1'-0"
1
PLOT DATE:
N
O
I
T
C
Y
U
L
R
N
T
O
S
S
N
E
O
S
C
O
D
P
R
R
A
U
N
P
I
U
D
I
O
B
H
C OR
F
520 South Main Street, Suite 2531
Akron, OH 44311
330.572.2100 Fax: 330.572.2102
COATED POLES AND CLIPS
WITH 3/8" TEMPERED
GLASS SNEEZE GUARD
1'-6"
NOT USED
1 1/2" = 1'-0"
5
1x4 WOOD TRIM ST-1
M-2
1x4 APRON (STAINED)
1"
STL PIPE TO PENATRATE
TOP PLATE
3'-07
8"
S-XX2
3/4" PLYWOOD
6
A11.3
M-2
6
A11.3
ST-1
EA. SIDE
M-2 1/2" SOLID SURFACE
ON 3/4" PLYWOOD
PT-5
1/2" GYP.BD.
3'-6"
1/2" GYP. BD.
1'-6"
COATED POLES AND CLIPS
WITH 3/8" TEMPERED GLASS
SNEEZE GUARD
M-2
3'-6"
2x6 WOOD FRAMING
@ 16" O.C.
2x4 WOOD FRAMING @
16" O.C.
FRP-1
2'-10"
TREATED SILL PLATE,
ANCHOR TO SLAB
BASE B-3
2x4 WOOD FRAMING
@ 16" O.C.
1/2" HILTI HIT HY150
B-3
CONC. FLOOR F-1
1x4 WOOD TRIM STAINED ST-1
321"
B-1
ADHESIVE ANCHOR @
16" O.C. STAGGERED.
GROUTED IN PLACE. SEE A1
FOR LOCATIONS
3'-6"
2x4 WOOD FRAMING @
16" O.C.
B-3 RUBBER BASE
LOW WALL AT BOOTH
1 1/2" =1'-0"
10
STEEL POST LOW WALL DETAIL
1 1/2" =1'-0"
8
NOT USED
N.T.S.
4
DRINK STATION CABINET SECTION
1 1/2"=1'-0"
2
M-2
1x4 APRON (STAINED)
M-1 PLASTIC
LAMINATE OVER 3/4"
PLYWOOD ON 2x4
WOOD FRAMING @
16" O.C.
3"
ST-1
1x4 WOOD TRIM STAINED ST-1
1'-6"
FRP-1
1x4 WOOD TRIM STAINED ST-1
1/2" SOLID SURFACE
ON 3/4" PLYWOOD
SIM. 3A
MITRE & GRIND SHARP
EDGES / POINTS
M-1 PLASTIC
LAMINATE OVER 3/4"
PLYWOOD ON 2x4
WOOD FRAMING @
16" O.C.
1'-6"
COATED POLES AND CLIPS
WITH 3/8" TEMPERED
GLASS SNEEZE GUARD
(SEE PLAN FOR
LOCATIONS)
M-2
M-2 1/2" SOLID SURFACE
ON 3/4" PLYWOOD
3"
2" 64
2'-6"
COUNTER DETAIL
7
1 1/2" = 1'-0"
M-2 1/2" SOLID SURFACE
ON 3/4" PLYWOOD
6
11.3
3'-6"
1x4 APRON (STAINED)
1'-321"
921"
6
A11.3
2x4 WOOD FRAMING @
16" O.C.
1/2" HILTI HIT HY150
1/2" HILTI HIT HY150
ADHESIVE ANCHOR @
16" O.C. STAGGERED.
ADHESIVE ANCHOR @
16" O.C. STAGGERED.
ORDER COUNTER SECTION
1 1/2" =1'-0"
1/2" HILTI HIT HY150
PAW067
B-1 TILE BASE
DBR 37
FRP-1 FRP
MILLWORK
DETAILS
9
COUNTER EDGE DETAIL
3" = 1'-0"
6
1x4 WOOD TRIM STAINED ST-1
ADHESIVE ANCHOR @
16" O.C. STAGGERED.
B-3
2015388.14
123 Minden Shopping Dr.
Minden, LA 71055
P-XX1
1x4 TRIM (STAINED)
B-3 RUBBER BASE
311465 / 434385
STORE NUMBER:
3'-6"
M-1 PLASTIC
LAMINATE OVER 3/4"
PLYWOOD ON 2x4
WOOD FRAMING @
16" O.C.
3/4" PLYWD.
1x4 WOOD TRIM STAINED ST-1
009.00.00
3/4" PLYWOOD
3'-6"
1 1/2"
FRP-1
2'-10"
M-1 PLASTIC
LAMINATE OVER 3/4"
PLYWOOD ON 2x4
WOOD FRAMING @
16" O.C.
SOLID SURFACE.
COUNTERTOP & EDGE.
PLAN VERSION:
ST-1
3/4" PLYWOOD
A
DBR 37
PIZZA HUT
ST-1
A
09.21.15
BUILDING TYPE:
SITE NUMBER:
1x4 WOOD TRIM STAINED ST-1
1x4 WOOD TRIM STAINED ST-1
CONTRACT DATE:
1'-6"
121"
6
A11.3
COATED POLES AND CLIPS
WITH 3/8" TEMPERED GLASS
SNEEZE GUARD
2 x 2 x 41" ANGLE FRAME - MAX.
SPACING 16" O.C.
1x4 LEDGER W/ P. LAM TO MATCH COUNTERTOP.
PLAN SECTION A-A
3'-6"
3/4" PLYWOOD
C
L BOLT, STUD & ANGLE
1'-6"
341"
121"
6"
B-3 RUBBER BASE
B-3
LOW WALL SECTION
1 1/2" = 1'-0"
3
A11.3
B-1 TILE BASE
COUNTER SECTION @ SALAD
1 1/2" = 1'-0"
1
PLOT DATE:
20" MAX
MIRROR MTD @ 40" A.F.F.
MAX TO BOTTOM OF
REFLECTING SURFACE
LAV.
INSULATE HOT WATER & DRAIN
PIPES
VERTICAL S.S. GRAB
BAR (IF RQ'D)
>20-25" MAX
DRYER
PAPER TOWEL DISPENSER
N
O
I
T
C
Y
U
L
R
N
T
O
S
S
N
E
O
S
C
O
D
P
R
R
A
U
N
P
I
U
D
I
O
B
H
C OR
F
ACCESSIBLE SEATS
121 - 140
7
7" 9"
8"
6"
17"-19"
NUMBER OF ACCESSIBLE SEATS
10" MAX.
30"
30"
19" TO 48" A.F.F. FOR OPERABLE
OPENING W/O OBSTRUCTION
FROM GRAB BAR
24" MAX.
6" MAX. DEPTH x 30" MIN. WIDTH TOE
CLEARANCE
ALTENATE
DOOR LOCATION
FREESTANDING OBJECT
MOUNTED ON POSTS OR
PYLON MAY OVERHANG 12"
MAX FROM 27" TO 80"
ABOVE FINISH FLOOR
15" MIN.
27"MIN.
12"
4"
15" MIN.
36" MIN. CLR.
ACCESSIBLE ROUTE
46" MAX.
OBJECT PROJECTION
FROM WALL LESS THAN
27" ABOVE FINISH FLOOR
MAY PROTRUDE ANY
AMOUNT
SEATING AND TABLES
N.T.S.
18
REACH RANGES
9"
9"
N.T.S.
14
REQ'D IN
CA ONLY
INT. ACCESS. ROUTE CLEARANCES
1/2" = 1'-0"
10
ACCESSIBLE URINAL
3/4" =1'-0"
6
SIGN POST OBSTRUCTION
121"
MIN.
CLR.
12" MAX
17" MIN. TO
18" MAX
TOILET PAPER
4" MAX.
VERTICAL GRAB
BAR. SEE DTL 1
STANDARD TOILET STALL
CLEAR
FLOOR
SPACE
N.T.S.
2
17" MIN.
2- 1/4"x3' EXPANSION ANCHORS AT
MASONRY OR CONC. WALL 2- #10x2"
SCREWS AT WOOD OR STEEL STUD
WALL-TYP.
27" MIN
60"
60"
TACTILE CHARACTERS
48" MIN TO BOTTOM OF BRAILLE
60" MAX TO BASELINE OF
THE HIGHEST LINE OF TEXT
GRAB BAR SHALL BE 1-1/4" TO 2" MAX.,
OUTSIDE DIA.- TYPICAL
1
6" MAX. (150)
** IF TOILET STALL IS
CONSTRUCTED OF SOLID WALLS
WITHOUT 9" OF TOE CLEARANCE
UNDER PARTITION, PROVIDE
ADDITIONAL 6" WIDTH AND DEPTH
FLOOR SHALL BE
SLIP-RESISTANT SURFACE
AND LEVEL WITH MAX 1/4"
CHANGE IN LEVEL
CONDIMENTS
N.T.S.
2'-8" MIN.
(815)
48" MIN.
13 1/2"
MAX
27"
48" MAX.
30" MIN
REQ'D IN
CA ONLY
CLEAR
FLOOR
SPACE
80" MIN.
OBJECT PROJECTION FROM
WALL BETWEEN 27" TO 80"
ABOVE FINISH FLOOR SHALL
PROTRUDE NO MORE THAN
4"
>10-24" MAX
ELEVATION
FIRE ALARM
PROTRUDING OBJECT
EXAMPLE: DRINK MACHINE, ETC.
10" MAX
THERMOSTAT
MOUNTING HTS. & CLEARANCES FOR ACCESSIBILITY BY THE DISABLED
46" MAX.
34" MAX
15" MIN.
48" MAX.
CONTROLS MOUNTED ON
WIDE SIDE OF TOILET AREA
28"-34" A.F.F.
SWITCHES
8" MIN. DEPTH x 30" MIN.
WIDTH KNEE SPACE
4'-8" MIN. (1420) W. WALL
MOUNTED W.C.
4'-11" MIN. (150) W.
FLR. MOUNTED W.C.
6
33" (EXCEPT @
TANK TOILETS,
WHICH SHALL BE
36")
APPROACH
3'-6"MIN. LATCH
APPROACH ONLY,
101 - 120
2'-0"
36" S.S. GRAB BAR
4'-6" MIN. (1320)
5
6" TO 12" MAX
OTHER APPROACHES
81 - 100
520 South Main Street, Suite 2531
Akron, OH 44311
330.572.2100 Fax: 330.572.2102
30" MIN.
4
39" to 41"
PULL STATION
14" MIN. / 17" MAX.
PROJECTION FROM
WALL URINAL
12" MAX.
(305)
61 - 80
T.S. COVER DISPENSER SHALL
BE MOUNTED 1 1/2" (MIN.)
BELOW GRAB RAIL
4" MAX.
2'-8" MIN. (815)
(100)
3
2.
TOP OF GRIPPING SURFACE
33" TO 36" MAX TO THE TOP OF
THE BAR. SEE NOTES BELOW
12" MINIMUM CLEAR
ABOVE GRAB BAR
18" MIN. FOR CALIFORNIA
15" MIN.
41 - 60
44" MAX.
2
48" MAX.
21 - 40
48" MAX.
1
15" MIN
1.
1 - 20
48" S.S. GRAB BAR
NOTES:
30" MIN.
TOTAL SEATS
48" MIN.
CONTRACT DATE:
1/8"x2" BENT PLATE WELDED TO RAIL
AND1/8"x3" DIAMETER MOUNTING
PLATE @ 4'-0"
ACCESSIBLE ROUTE WALK
2"x6" BLOCKING AT WOOD STUD WALLS
(OMIT BLOCKING AT MASONRY OR
CONC. WALL) - TYPICAL
15
PROTRUDING HAZARDS
1/2" = 1'-0"
MOUNT COAT HOOK ON
INSIDE OF TOILET STALL
DOOR
11
CHRISTYHARDWARE.COM
877-544-5400
NOTE: SEE DOOR SCHEDULE. AND DOOR SCHEDULE NOTES
COAT HOOK
20
30"
CLEAR
1/4" - 1/2"
48" A.F.F MAX.
PARTITION DOOR LATCH @ PULL
ACCESSIBLE LAVATORY
1.
009.00.00
3/4"=1'-0"
3
INDICATED DIMENSIONS, HEIGHTS, DEPTHS, AREAS AND OTHER GRAPHIC
INFORMATION ARE PROVIDED AS MINIMUMS THAT MUST BE MAINTAINED. THESE
MINIMUMS ARE BASED UPON YUM STANDARDS AND MAY EXCEED ADA
REQUIREMENTS.
2.
60" TURNING SPACE
- PERMITTED OVERLAP LIMITED TO 1 ARM OF T-SHAPED SPACE
- CAN OVERLAP FIXTURE & DOOR CLEARANCE
- DOOR CAN SWING INTO TURNING SPACE A MAXIMUM OF 12"
3.
RESTROOM, IN GENERAL, DOOR SWING MUST BE OUTSIDE OF THE FXTR CLEAR
FLOOR SPACE HOWEVER A DOOR CAN SWING INTO FIXTURE CLEAR FLOOR
SPACE IF WHEELCHAIR SPACE 30"X48" IS PROVIDED BEYOND THE DOOR SWING.
4.
TOILET ROOM MUST ALLOW FOR SIDE TRANSFER - 42" BETWEEN FIXTURES
CHANGES IN LEVEL
N.T.S.
12 DINING ROOM SEATING CLEARANCES
N.T.S.
8
GENERAL NOTES
2015388.14
PIZZA HUT
123 Minden Shopping Dr.
Minden, LA 71055
DBR 37
NOTE:
1. MAINTAIN 36" MIN. CLEAR AISLE EGRESS PATHS TO EXIT DOORS.
2. INTERNATIONAL SYMBOL OF ACCESSIBILITY REQUIRED ON TOP EDGE OR FRONT OF ALL
ACCESSIBLE TABLES.
16
311465 / 434385
THE DETAILS SHOWN ARE CONCEPTUAL ONLY AND INTENDED TO SHOW
ABSOLUTE MINIMUMS AND SHALL BE COORDINATED WITH THE OTHER
CONSTRUCTION DOCUMENTS ASSOCIATED WITH THIS PROJECT.
2
NOTE: SEE DOOR SCHEDULE. AND DOOR SCHEDULE NOTES
N.T.S.
7
ACCESSIBLE ROUTE
48"
CLEAR
19"
30"
CLEAR
1
PLAN VERSION:
30"
CLEAR
NOTE: DOOR HOOKS
SHALL BE PLACED IN
ACCESSIBLE STALLS
BETWEEN 40" MIN TO
48" MAX ABOVE FINISH
FLOOR
34" A.F.F MIN.
48" A.F.F MAX.
BOBRICK OR CHRISTY
COMMERCIAL
HARDWARE & SUPPLY
WAREHOUSE
#039-6529 OR SIMILAR
ADA COMPLIANT HOOK.
3" - 1'-0"
30"
CLEAR
REINFORCED S.S.
LATCH WITH THROUGH
BOLTED KEEPER. ADA
COMPLIANT
S.S. PULL (BOTH SIDES)
ON ALL ACCESSIBLE
TOILET STALLS. MOUNT
PULLS BELOW LATCH
AND KEEPER.
DBR 37
STORE NUMBER:
GRAB BAR
19"
1/4" MAX
N.T.S.
BUILDING TYPE:
SITE NUMBER:
ACCESSIBLE ROUTE
ACCESSIBLE RESTROOM DOORS
09.21.15
4
PLOT DATE:
CLEAR FLOOR SPACE AT DOOR
STRIKE SIDE
DOOR CLOSER IF
PROVIDED, SHALL
HAVE AT LEAST A
5-SECOND
CLOSING TIME
PERIOD FROM 90
OPEN POSITION
THRESHOLD - SEE
DETAILS 12, 14 / A6.1
32" MIN.
CLR. OPENING
N
O
I
T
C
Y
U
L
R
N
T
O
S
S
N
E
O
S
C
O
D
P
R
R
A
U
N
P
I
U
D
I
O
B
H
C OR
F
520 South Main Street, Suite 2531
Akron, OH 44311
330.572.2100 Fax: 330.572.2102
DOOR AND HARDWARE
PER SHEET A1.1
PROVIDE ISA DECAL
@ ALL PUBLIC
ACCESSIBLE
ENTRANCES
SLIP RESISTANT SURFACE (MEDIUM
BROOM FINISH)
34" TO 44"
60"
10"
MIN.
CROSS SLOPE 1:50 OR 2% MAX.
IN ALL DIRECTIONS.
NOTE:
1. EXTERIOR DOOR PRESSURE CANNOT EXCEED 8.5 LBS (GC TO DOOR PRESSURE TO
MINIMUM ALLOWABLE BY AHJ).
2. INTERIOR DOOR PRESSURE CANNOT EXCEED 5 LBS.
3. 60% OF PUBLIC ENTRANCES MUST BE ACCESSIBLE. (100% IN CA)
3'-0" DOOR WIDTH
TYP. ENTRANCE / EXIT DOOR
N.T.S.
17
EXTERIOR DOOR REQUIREMENTS
1/2" = 1'-0"
13
MIN. 60 DEGREE SLOPE
10" MIN.
BOTTOM RAIL OF DOOR
SEE DETAIL
12 / ADA1.0
1/2" MAX.
DOOR HANDLE,
SEE HARDWARE
NOTES
CLEAR SPACE FINISH ELEVATION TO
MATCH FINISH FLOOR ELEVATION AT
DOOR
18"
24" REQ. IN
CA. FOR
EXTERIOR
DOORS
60"
LATCH
ALUMINUM THRESHOLD
#10 S.M. IN PLASTIC
EXPANSION ANCHOR
NOT USED
N.T.S.
18
BOTTOM RAIL (EXTERIOR DOOR)
3" = 1'-0"
14
NOT USED
N.T.S.
2
CONTRACT DATE:
BUILDING TYPE:
DBR 37
PLAN VERSION:
009.00.00
SITE NUMBER:
311465 / 434385
STORE NUMBER:
NOT USED
N.T.S.
11
NOT USED
N.T.S.
3
09.21.15
2015388.14
PIZZA HUT
123 Minden Shopping Dr.
Minden, LA 71055
DBR 37
ACCESSIBILITY
REQUIREMENTS
NOT USED
N.T.S.
16
NOT USED
N.T.S.
12
NOT USED
N.T.S.
4
PLOT DATE:
GENERAL:
1.
2.
FAN DATA
LOCATE, CUT AND FRAME ROOF OPENINGS AS SHOWN FOR ALL HVAC EQUIPMENT AND EXHAUST FANS.
XX-XXX
AREA SERVED SUPPLY MIN O.A.
CFM
CFM
ESP
COOLING CAPACITY
HP
NOM
TONS
RPM
MIN CAP
(MBH)
NET TOTAL
HEATING CAPACITY
MIN
EER
UNIT ELECT DATA
INPUT
OUTPUT PHASE
STAGE
AFUE
(MBH) (STAGES)
(MBH)
VOLTS/
PH
FLA
MCA
MOCP
MAX
UNIT
WEIGHT
(LBS)
IT IS VERY IMPORTANT THAT ACCURATE MEASUREMENTS ARE USED WHEN LOCATING EXHAUST FAN ROOF OPENINGS TO ENSURE THAT NO OFF-SETS ARE REQUIRED IN THE EXHAUST DUCTWORK. COORDINATE ROOF OPENINGS
WITH THE KITCHEN EQUIPMENT.
MARK
PROVIDE ANY FRAMING REQUIRED FOR DIFFUSER INSTALLATION IN HARD CEILING.
RTU-1
KITCHEN
5000
1475
1.0"
3.0
1740
12.5
144
12.1
250
203
2
81%
208/3
-
65
90
2500
RTU-2
DINING
4000
1225
1.0"
3.75
1483
10.0
113
11.3
200
160
2
80%
208/3
-
49.6
60
1300
MANUFACTURER
AND
MODEL NUMBER
REMARKS
N
O
I
T
C
Y
U
L
R
N
T
O
S
S
N
E
O
S
C
O
D
P
R
R
A
U
N
P
I
U
D
I
O
B
H
C OR
F
3.
HVAC:
1.
INSTALLATION SHALL CONFORM TO THE ENERGY CONSERVATION DESIGN MANUAL STANDARDS FOR NEW NONRESIDENTIAL BUILDINGS, IF REQUIRED.
2.
ALL WORK AND MATERIALS SHALL COMPLY WITH GOVERNING CODES, SAFETY ORDERS AND REGULATIONS.
3.
OBTAIN AND PAY FOR ALL NECESSARY PERMITS, FEES AND INSPECTIONS REQUIRED BY GOVERNING AUTHORITIES. UNLESS NOTED OTHERWISE.
4.
PROVIDE CONDUIT FOR LINE AND LOW VOLTAGE WIRING, LINE VOLTAGE WIRING SWITCHES, AND FINAL CONNECTIONS.
5.
ANY EQUIPMENT THAT IS SUBSTITUTED SHALL FIT IN THE SPACE PROVIDED WITH ADEQUATE ROOM FOR SERVICING, INCLUDING SUBSTITUTE EQUIPMENT NAMED IN THE SPECIFICATIONS. CONTRACTOR SHALL SUBMIT A 1/4" SCALE
DRAWING OF ALL EQUIPMENT SUBSTITUTED FOR APPROVAL PRIOR TO INSTALLATION, INCLUDING, BUT NOT LIMITED TO, STRUCTURAL AND ARCHITECTURAL IMPACT, CLEARANCE REQUIREMENTS AND UTILITY REQUIREMENTS.
6.
INSTALL RECHARGEABLE REFRIGERANT LINES FROM ICE MACHINE TO CONDENSER ON ROOF.
7.
HVAC UNITS SHALL BE MOUNTED LEVEL ON ROOF CURBS.
8.
ALL EXPOSED DUCTWORK TO BE INTERNALLY LINED AND PAINTED AS SHOWN ON ARCHITECTURAL DRAWINGS. ALL OTHER DUCTWORK SHALL BE INSULATED PER THE SPECIFICATIONS.
9.
ALL ROUND SUPPLY / RETURN DUCTS SHALL BE RIGID, WITH THE EXCEPTION OF THE LAST 5'-0", WHICH MAY BE FLEX. (ACCESSIBLE CEILINGS ONLY)
TRANE
YHD150F3
TRANE
YSC120E3EM
1,2,3,4,5,6&7
520 South Main Street, Suite 2531
Akron, OH 44311
330.572.2100 Fax: 330.572.2102
1,2,3,4,5,&6
NOTES:
1. LISTED CAPACITY IS NET COOLING CAPACITY AT 97DB/77 WB EAT AND 105F AMBIENT (ARI CONDITIONS).
2.
SPECIFIED RTU'S ARE DOWN DISCHARGE PACKAGED GAS / ELECTRIC ROOFTOP UNITS . INCLUDES THROUGH THE ROOF CURB POWER, GAS & CONDENSATE DRAIN. GAS PIPING SHALL BE FACTORY
PIPED WITH SHUT-OFF OUTSIDE OF UNIT.
3.
GUARD, SMOKE DETECTOR IN RETURN, AND FACTORY FABRICATED KNOCK-DOWN ROOF CURB.
4.
SPECIFIED UNIT INCLUDES A UN-POWERED CONVENIENCE OUTLET.
5.
SPECIFIED UNIT INCLUDES SUPPLY AIR TEMPERING CONTROL WITH REMOTE MOUNTED TEMPERATURE SENSOR AT 60"AFF, WHERE INDICATED ON PLANS
6.
INTERLOCK OPERATION WITH PIZZA OVEN HOOD. SUPPLY FAN ON AND OUTDOOR AIR DAMPER OPEN WHEN HOOD EXHAUST IS ENERGIZED.
7.
INTERLOCK OPERATION WITH FRYER HOOD. SUPPLY FAN ON AND OUTDOOR AIR DAMPER OPEN WHEN HOOD EXHAUST IS ENERGIZED.
10. SMOKE DETECTOR SHALL BE INSTALLED IN THE RETURN AIR DUCTS AND SHALL DEACTIVATE ROOFTOP UNIT UPON SENSING SMOKE. REFER ELECTRICAL DRAWINGS.
HVAC UNIT SCHEDULE
11. ALL KITCHEN HOOD EXHAUST DUCTS SHALL BE RIGID 16 GA MINIMUM, WELDED DUCT. GRIND ALL WELDS SMOOTH.
12. ALL BRANCH DUCTS FEEDING INDIVIDUAL DIFFUSERS SHALL HAVE DAMPERS AT TAKEOFFS FOR AIR BALANCING. DIFFUSERS SHALL HAVE OPPOSED BLADE DAMPER INSTALLED AT AIRFLOW DEVICE AT AREAS WHERE THE CEILING IS
INACCESSIBLE.
13. ALL UTILITY PIPING FOR RTU'S SHALL RUN UP THROUGH ROOF INSIDE EACH UNIT'S ROOF CURB.
14. ALL OUTSIDE AIR INTAKES SHALL BE A MINIMUM OF 10'-0" FROM EXHAUST FANS AND / OR VENTS.
MARK
15. NOT USED.
EF-1
1800
1.0"
1623
1/2
115/1
EF-2
510
1.0"
1487
1/3
115/1
EF-3
200
0.50"
1504
0.129
115/1
16. FINAL HVAC SYSTEM TESTING AND BALANCING SHALL BE PERFORMED BY THE OWNERS INDEPENDENT AGENT. A RE-TEST IS MANDATORY FOR A FALSE START (I.E. NO POWER UPON AGENT'S ARRIVAL, EQUIPMENT NOT WIRED, ETC.)
AND SHALL BE A COST INCURRED BY THE G.C. IN THE EVENT A SYSTEM / STORE RECEIVES A GRADE OF 5 OR BELOW AS A RESULT OF THE HVAC SYSTEM PERFORMANCE OR OPERATIONAL DEFICIENCIES, OWNER WILL REQUEST A
RE-TEST AND THE COST FOR SAME SHALL BE ALSO INCURRED BY THE GENERAL CONTRACTOR.
X
X
-
X
X
-
X
X
MANUFACTURER
AND
MODEL NUMBER
D-DR
ELECT
V-BELT
POWER
HP/
AMPS
BIRD
SCREEN
RPM
BDD
SP
DISC
CFM
XX-XXX
STARTER
ACCESSORIES
ACME
PDU135RG
X
X
SEE NOTES 1,2,3,5,9,10,11,12
CAPTIVEAIRE
DU33HFA
COOK 70 ACE-B
GREENHECK GB-071
17. TRANE PROGRAMMABLE THERMOSTAT MODEL #BAYSENS019B, PROVIDED WITH TRANE PACKAGE. (QUANTITY PER PLANS)
REMARKS
SEE NOTES 1,2,3,5,9,10,11,12
SEE NOTES 1,3,5 & 8
1
REMARKS:
1. WEATHERPROOF DISCONNECT SWITCH
2. UNVENTED ROOF CURB EXTENSION
3. ROOF CURB, SHIM LEVEL
4. PROVIDE SUPPLY WASHABLE AIR FILTER
5. PROVIDE L-200 BEARINGS AND FAN HUBS KEYED TO SHAFT
6. SINGLE SIDE OUTSIDE AIR INTAKE
7. PROVIDE SOLID STATE SPEED CONTROLLER
8. ALUMINUM BACKDRAFT DAMPER
9. UL 762 LISTED (GREASE)
10. GREASE DRAIN AND TROUGH
11. HINGED SUB-BASE
12. PROVIDED BY OWNER INSTALLED BY CONTRACTOR
18. TRANE THERMOSTAT SENSOR (REMOTE) MODEL #4190-7015, PROVIDED WITH TRANE PACKAGE. (QUANTITY PER PLANS)
19. THESE DRAWINGS ARE ACCOMPANIED BY SPECIFICATIONS. SEE SPECIFICATIONS FOR FURTHER INFORMATION.
CIRCUIT BREAKER
CD/SR
CEILING DIFFUSER/SUPPLY REGISTER
(ARROWHEAD REPRESENTS NUMBER OF THROW)
RETURN REGISTER/GRILLE
MVD
FD
(L)
EXHAUST REGISTER/GRILLE
FLEXIBLE CONNECTION
MANUAL VOLUME DAMPER
FIRE DAMPER
DUCT LINING (1" THICK UNLESS OTHERWISE NOTED)
DUCT TRANSITION (RECTANGULAR TO ROUND)
FLEXIBLE DUCT (5'-0 MAXIMUM)
T
T-STAT
PROGRAMMABLE THERMOSTAT (PROVIDED WITH TRANE PACKAGE)
TS
T-STAT
THERMOSTAT SENSOR (REMOTE)
H
CONDENSATE DRAIN
DIA.
DIAMETER
DL
DL
DOOR LOUVER
UC
UC
DOOR UNDERCUT (3/4" MINIMUM)
M
FURNISHED AND INSTALLED BY MECHANICAL
CONTRACTOR.
E
FURNISHED AND INSTALLED BY ELECTRICAL
CONTRACTOR.
ME
X-X 0000
CONNECT/CONNECTION
CONTINUATION
CONT'R
CONTRACTOR
CFM
CUBIC FEET PER MINUTE
DET.
DETAIL
DISC.
DISCONNECT
DTR
DOWN THRU ROOF
EF
EXHAUST FAN
EXISTING
GA.
GAGE/GAUGE
GC
GENERAL CONTRACTOR
HVAC
MFR.
0
VAR
24x24
X
S-2
0
VAR
24x24
X
S-3
8
VAR
24x24
X
S-4
0
VAR
15x15
X
S-5
2
VAR
11x11
X
S-6
0
12x12
14x14
X
(0)
S-7
10
18x10
20x12
X
(10)
R-1
3
22x22
24x24
X
(3)
E-1
2
VAR
10x10
X
(2)
450-725
(0)4W, (0)3W
250-350
(5)4W, (3)3W
500-700
(0)4W,(0)3W
300-350
(2)4W
50-150
300-500
350-600
1050-1200
200
X
X
X
METAL-AIRE / TITUS
5000-1 / TDC-AA-1
MOUNT TO EXPOSED DUCTWORK.
X
X
X
METAL-AIRE / TITUS
5000-1 / TDC-AA-1
AT SHEETROCK CLG. INSTALL DAMPER IN DIFFUSER FACE.
X
X
X
X
METAL-AIRE / TITUS
5000-1 / TDC-AA-1
FRN SQR TO RND ADAPTER
X
X
X
X
METAL-AIRE / TITUS
5000-1 / TDC-AA-1
FRN SQR TO RND ADAPTER
X
X
X
METAL-AIRE / TITUS
5000-1 / TDC-AA-1
FRN SQR TO RND ADAPTER
X
X
X
X
X
X
X
X
MODEL NUMBER
REMARKS
X
X
TITUS
(OR EQUAL)
300RL-HD
SIDE WALL SUPPLY
X
X
TITUS
(OR EQUAL)
US301FL
SIDE WALL SUPPLY
METAL-AIRE / TITUS
CC5-FB-TB / 50FF
METAL-AIRE / TITUS
CC5D / 50F
X
X
MANUFACTURER
X
X
FULLY REMOVABLE FACE, DO NOT INSTALL FILTER
HEATING, VENTILATING, AND AIR CONDITIONING
MANUFACTURER
NOTES:
MECHANICAL
DIFFUSERS IN SURFACE MOUNTED CEILINGS SHALL BE PROVIDED WITH OPPOSED BLADE DAMPERS. SEE ARCHITECTURAL DRAWINGS FOR CEILING TYPES.
CONTRACT DATE:
NEW
IT IS THE CONTRACTOR'S RESPONSIBILITY TO VERIFY FINAL COUNTS BASED ON LOCATIONS SHOWN ON DRAWINGS.
BUILDING TYPE:
DBR 37
OUTSIDE AIR
PLAN VERSION:
009.00.00
OBD
OPPOSED BLADE DAMPER
SITE NUMBER:
S/S
STAINLESS STEEL
STORE NUMBER:
TYP.
TYPICAL
UON
UNLESS OTHERWISE NOTED
UTR
UP THRU ROOF
MECH.
HUMIDISTAT, PROVIDED WITH TRANE PACKAGE.
D
CONN.
(E)
SINGLE LINE DUCT BRANCH TAKEOFF
FLEX
CEILING
CONT.
RECTANGULAR DUCT ELBOW WITH TURNING VANES
FC
CLG.
(0)4W
S-1
OBD
CB
STEEL
EXHAUST AIR DUCT (RISE/DROP)
ALUMINUM
EA/EXH
TRANSFER
BACK DRAFT DAMPER
EXHAUST
BDD
RETURN
RETURN AIR DUCT (RISE/DROP)
CFM
RANGE
MATERIAL
SUPPLY
RA/RET
MARK
DUTY
2
SURFACE
SUPPLY AIR (RISE/DROP)
ER/EG
D
AIR CONDITIONING
SA/SUP
RR/RG
XX-XXX
MOUNTING
LAY-IN
A/C , AC
DESCRIPTION
GRILLE
SYMBOL & ABBREV.
(NO.) & AIR
PATTERN
TYPE
REGISTER
DESCRIPTION
DIFFUSER FACE
NECK
OR
SIZE
CEILING GRID
SIZE
DIFFUSER
SYMBOL & ABBREV.
10
QUANTITY
GENERAL NOTES
EXHAUST FAN SCHEDULE
(N)
OA/OSA
09.21.15
311465 / 434385
2015388.14
PIZZA HUT
AIR DEVICE SCHEDULE
FURNISHED BY MECHANICAL CONTRACTOR AND
INSTALLED BY ELECTRICAL CONTRACTOR.
FOR COMPLETE INFORMATION AND PRICING ON THE TRANE HVAC PACKAGE CONTACT
MARTY CUSICK, THE YUM! BRANDS ACCOUNT EXECUTIVE AT TRANE NATIONAL
ACCOUNTS.
TOLL-FREE PHONE: (866) YUM-HVAC or (866) 986-4822
FAX: (502) 499-7870
EMAIL: [email protected]
MECHANICAL EQUIPMENT DESIGNATION
TRANE HAS AGREED TO SUPPLY AN HVAC PACKAGE CONSISTING OF THE ROOF-TOP
UNITS, CURBS, AND THERMOSTATS. RTU'S AS SPECIFIED INCLUDE AN UNPOWERED
CONVENIENCE OUTLET (SEE ELECTRICAL) AND AN HACR CIRCUIT BREAKER WHICH
PROVIDES UNIT DISCONNECT. TRANE ALSO HAVE AVAILABLE OPTION PACKAGES
WHICH INCLUDE SMOKE DETECTORS AND ENUNCIATORS, ECONOMIZERS, AND RTU
VARIATIONS SUCH AS HIGH-EFFICIENCY MODELS.
ITEM
OA
RA
SA
EA
PRESSURE
EF-1
--
--
--
1800
-1800
EF-2
--
--
--
510
-510
EF-3
--
--
--
200
-200
RTU-1
1475
3525
5000
--
+1475
RTU-2
1225
2775
4000
--
+1225
TOTAL
2700
6300
9000
2510
+190
3
DBR 37
BE PREPARED AT TIME OF ORDER OR QUOTE REQUEST TO PROVIDE ALL PROJECT
DETAILS REGARDING SPECIFICATIONS AND QUANTITIES AS SITE SPECIFIC DESIGN MAY
NOT MATCH NATIONAL DESIGN.
SEE THE SCOPE OF WORK SHEETS FOR ADDITIONAL INFORMATION.
123 Minden Shopping Dr.
Minden, LA 71055
HVAC NOTES
& SCHEDULES
M1.0
MECHANICAL SYMBOLS
12
TRANE PACKAGE
N.T.S.
8
AIR BALANCE SCHEDULE
4
PLOT DATE:
N
O
I
T
C
Y
U
L
R
N
T
O
S
S
N
E
O
S
C
O
D
P
R
R
A
U
N
P
I
U
D
I
O
B
H
C OR
F
520 South Main Street, Suite 2531
Akron, OH 44311
330.572.2100 Fax: 330.572.2102
R-1 1175
15
TYP OF 3
1
RTU
1
8
26/26
6
5
6
RTU-1 T T RTU-2
14
EF
2
EF
4
S-3 625
S-3 625
2
S-3 625
S-3 625
1
3
14x14
S
S-3 625
S-3 625
12 TYP
13
S-3 625
24/20
9
WH
24/14
18/14
14/14
1
S-3 625
1
RTU
2
3
EF
14
24/24 TIGHT TO
STRUCTURE
13
S-7 390
S-7 390
S-7 390
S-7 390
10
16
S-7 390
S
18
E-1 100
S-5
S-7 390
50
S-7 390
11
TYP
S-7 390
S-7 390
11
S
S-7 390
7
17
E-1 100
17
S-5
50
18
CONTRACT DATE:
09.21.15
BUILDING TYPE:
DBR 37
PLAN VERSION:
009.00.00
SITE NUMBER:
311465 / 434385
STORE NUMBER:
2015388.14
PIZZA HUT
A.
DINING ROOM LIGHT FIXTURE LOCATIONS ARE CRITICAL. COORDINATE
DUCTWORK LOCATIONS SO AS NOT TO CONFLICT WITH LIGHT FIXTURE
LOCATIONS.
1
RTU UNIT, VERIFY UNIT LOCATION AND SUPPORT WITH BUILDING STRUCTURE.
G.C. REFER TO STRUCTURAL. SET OUTSIDE AIR ON RTU AS SCHEDULED ON
SHEET M1.0. MAINTAIN WORKING CLEARANCES PER MANUFACTURER'S
INSTALLATION INSTRUCTIONS.
7
B.
THERMOSTATS SHALL BE PROGRAMMABLE THERMOSTAT WITH SUBBASE.
REMOTE TEMPERATURE SENSOR. (PROVIDED WITH TRANE PACKAGE).
2
10'-6"x 4'-0" TYPE I PIZZA OVEN EXHAUST HOOD AND FANS PROVIDED BY
OWNER AND INSTALLED BY GC. REFER TO DETAIL 1/M3.0 FOR MORE INFO.
C.
DIFFUSERS INSTALLED IN THE EXPOSED STRUCTURE AREAS SHALL BE MOUNTED
FLUSH TO THE BOTTOM CORD OF THE TRUSSES.
3
FIELD INSTALL 14"x14" EXHAUST CONNECTION TO HOOD, ROUTE 16"x16", 16
GA. EXTERNAL CONTINUOUSLY WELDED LIQUID TIGHT EXHAUST DUCT FROM
OVEN HOOD UP THRU ROOF TO EF-1. MINIMUM 1 HOUR, U.L. LISTED, FIRE
RATED BLANKET WRAP UP TO EF-1 ON ROOF. OFFSET DUCT ABOVE AS
REQUIRED AND SLOPE DUCT BACK TO HOOD. TRANSITION TO HOOD AND
FAN CONNECTIONS AS REQUIRED. PROVIDE AND INSTALL ACCESS DOOR IN
DUCT AT EACH CHANGE OF DIRECTION PER CODE.
D.
DIFFUSERS LOCATED AROUND PERIMETER OF KITCHEN HOODS SHALL BE
DIRECTED AWAY FROM THE HOOD. REFER TO PLAN FOR BLOW PATTERN
INDICATIONS.
4
5
6
3'-0" X 2'-6" TYPE I FRYER HOOD PROVIDED BY OWNER AND INSTALLED BY GC.
REFER TO SHEET M3.0 FOR MORE INFO.
8"x8", 16 GA. WELDED STEEL EXHAUST DUCT WITH MINIMUM 1 HOUR, U.L.
LISTED, FIRE RATED BLANKET WRAP UP TO EF-2 ON ROOF. REFER TO
SPECIFICATIONS. OFFSET DUCT ABOVE AS REQUIRED AND SLOPE DUCT
BACK TO HOOD. TRANSITION TO HOOD AND FAN CONNECTIONS AS
REQUIRED. PROVIDE AND INSTALL ACCESS DOOR IN DUCT AT EACH CHANGE
OF DIRECTION PER CODE.
LOCATE THERMOSTAT CONTROLS ON WALL NEAR MANAGERS DESK AT 48"
A.F.F. COORDINATE WITH EQUIPMENT INSTALLED.
INSTALL REMOTE TEMPERATURE IN RETURN AIR DUCT FOR RTU-2. SEE
SPECIFICATIONS.
15
8
RTU-1 SHALL HAVE A THERMOSTAT WITH NO REMOTE SENSOR.
16
9
FURNISH AND INSTALL 3" DIAMETER FLUE VENT AND 3" DIAMETER INTAKE
FROM WATER HEATER THROUGH ROOF AND TERMINATE PER
MANUFACTURER'S REQUIREMENTS. COORDINATE WORK WITH ALL TRADES.
SEE DETAIL 1/P6.0. INSTALL PER MANUFACTURER'S INSTALLATION
INSTRUCTIONS.
PROVIDE 22"x48" OPENING IN TOP OF RETURN AIR DUCT. COVER RETURN AIR DUCT
OPENING WITH 1"x 16 GA EXPANDED METAL (78% FREE AREA) IN 1-1/4"x1-1/4"x1/8"STL
ANGLE FRAME.
17
UNDERCUT RESTROOM DOORS A MINIMUM 3/4" FOR MAKE-UP AIR.
18
CONDENSING UNITS FOR COOLER/FREEZER AND ICE MACHINE MOUNTED ON FIELD
FABRICATED PLATFORM ON THE ROOF. ROOF PENETRATIONS AND LEVEL SUPPORT
BY THE G.C. SEE ARCHITECTURAL ROOF PLAN.
10
SUPPLY OR RETURN DUCTWORK RUN BETWEEN ROOF TRUSSES ABOVE
BOTTOM CORD OF TRUSSES.
11
EXPOSED DUCTWORK IN DINING SHALL BE SUITABLE TO RECEIVE FIELD PAINT
AS SCHEDULED. SEE ARCH SHEETS FOR FINISH.
12
ROUTE DUCTWORK BELOW BOTTOM CORD OF THE TRUSSES ABOVE THE
CEILING. COORDINATE ROUTING OF DUCTWORK WITH LIGHTS.
13
ROUTE SUPPLY AIR DUCT AND RETURN AIR DUCT UP BETWEEN TRUSSES.
TRANSITION IN ROOF CURB TO ROOF TOP UNIT AND INSTALL FLEXIBLE
CONNECTION AT CONNECTION TO UNIT.
14
SMOKE DETECTORS ARE FACTORY INSTALLED IN THE RETURN AIR SECTIONS
OF THE RTU. REFER TO ELECTRICAL DRAWINGS FOR ADDITIONAL
INFORMATION.
ABOVE.
123 Minden Shopping Dr.
Minden, LA 71055
DBR 37
DUCT AND
DIFFUSER
PLAN
M2.0
PLOT DATE:
REVISIONS
N
O
I
T
C
Y
U
L
R
N
T
O
S
S
N
E
O
S
C
O
D
P
R
R
A
U
N
P
I
U
D
I
O
B
H
C OR
F
TAG
1
E56370035+E56370069
MODEL
EXHAUST PLENUM
MAX.
RISER(S)
COOKING TOTAL EXH.
WIDTH LENG.
DIA.
CFM
TEMP.
CFM
LENGTH
3347
3' 0.00"
450 Deg.
8"
510
BD-2
510
HOOD CONFIG.
HOOD
CONSTRUCTION
S.P.
-0.205"
430 SS
Where Exposed
END TO
END
ROW
ALONE
ALONE
3"
8"
520 South Main Street, Suite 2531
Akron, OH 44311
330.572.2100 Fax: 330.572.2102
BUILT
IN
ACCORDANCE
WITH
NFPA
No. 96
HOOD
NO.
33"
1
E56370035+E56370069
HOOD
NO.
QTY. HEIGHT
TYPE
LENGTH
16"
2
SS Baffle with Handles
QTY.
TYPE
30%
1
L55 Series E26
FIRE SYSTEM
TYPE
UTILITY CABINET(S)
ELECTRICAL
SIZE
MODEL #
SWITCHES
QUANTITY
FIRE
HOOD
SYSTEM HANGING
PIPING
WGHT
NO
YES
18"
18"
Front, Left, Right
BACKSPLASH 96.00" High X 72.00" Long
E56370035+E56370069
U.L. Listed L55 Series E26 Canopy Light Fixture High Temp Assembly
148 LBS
OPTION
FIELD WRAPPER 15.00" High
1
EFFICIENCY @ 9 MICRONS
16"
TAG
WIRE
LOCATION
GUARD
R
LIGHT(S)
430 SS Vertical
RIGHT QUARTER END PANEL 23" Top Width, 0" Bottom Width, 23" High 430 SS
3' 0.00"Nom./3' 0.00"OD
LEFT QUARTER END PANEL 23" Top Width, 0" Bottom Width, 23" High 430 SS
L55 SERIES E26 CANOPY LIGHT FIXTURE HIGH TEMP ASSEMBLY, INCLUDES CLEAR THERMAL
AND SHOCK RESISTANT GLOBE (L55 FIXTURE)
33"
FIELD WRAPPER 15.00" HIGH
(SEE HOOD OPTIONS TABLE)
DALLAS OFFICE
EXHAUST RISER
4"
16" SS BAFFLE WITH
HANDLES AND HOOK
14" NOM.
3" INTERNAL STANDOFF
IT IS THE RESPONSIBILITY
OF THE ARCHITECT/OWNER TO
ENSURE THAT THE HOOD CLEARANCE
FROM LIMITED-COMBUSTIBLE
AND COMBUSTIBLE MATERIALS
IS IN COMPLIANCE WITH
LOCAL CODE REQUIREMENTS.
47"
47.0" MAX
100"
BACKSPLASH 96.00" HIGH
X 72.00" LONG
GREASE DRAIN
WITH REMOVABLE CUP
71" AFF REFERENCE
FIELD INSTALLED
QUARTER END PANELS
TAG
1
E56370039
FAN UNIT MODEL #
CFM
ESP.
RPM
H.P.
B.H.P.
VOLT
FLA
WEIGHT (LBS.)
19 1/2"
SONES
19 1/2"
DU33HFA
510
1.000
1487
0.333
0.2200
1
115
5.6
62
11.5
FAN #1 DU33HFA - EXHAUST FAN (E56370039)
VENTED
CURB
FEATURES:
FAN
UNIT
NO.
TAG
1
E56370039
OPTION (Qty. - Descr.)
- ROOF MOUNTED FANS
25 1/2
- RESTAURANT MODEL
1 - Grease Box
- UL705 AND UL762
1 - Hinge Kit - Ships Loose for Curb Supplied by Others
- VARIABLE SPEED CONTROL
22"
20 GAUGE
STEEL
CONSTRUCTION
- INTERNAL WIRING
- WEATHERPROOF DISCONNECT
- THERMAL OVERLOAD PROTECTION (SINGLE PHASE)
EXHAUST
FAN
UNIT
NO.
SUPPLY
- GREASE CLASSIFICATION TESTING
TAG
GREASE
CUP
1
E56370039
GRAVITY
DAMPER
WALL
MOUNT
SIDE
DISCHARGE
GRAVITY
DAMPER
MOTORIZED
DAMPER
WALL
MOUNT
NORMAL TEMPERATURE TEST
EXHAUST FAN MUST OPERATE CONTINUOUSLY
25 1/4
YES
18 1/2
NO.
ON
FAN
WEIGHT
ITEM
1
#1
30 LBS
Curb
3" FLANGE
SIZE
UNTIL ALL FAN PARTS HAVE REACHED
THERMAL EQUILIBRIUM, AND WITHOUT ANY
DETERIORATING EFFECTS TO THE FAN WHICH
WOULD CAUSE UNSAFE OPERATION.
GREASE DRAIN
ABNORMAL FLARE-UP TEST
EXHAUST FAN MUST OPERATE CONTINUOUSLY
WHILE EXHAUSTING BURNING GREASE VAPORS
19.500"W x 19.500"L x 22.000"H Vented
2
12 1/8
15 MINUTES WITHOUT THE FAN BECOMING
DAMAGED TO ANY EXTENT THAT COULD CAUSE
AN UNSAFE CONDITION.
OPTIONS
17 1/2
17 1/2
17 1/2
ROOF OPENING
DIMENSIONS
CARROLLTON, TX, 75007
FAN
UNIT
NO.
Pizza Hut MUA 11 DBR 37A
EQUIPMENT
BY OTHERS
1901 Royal Lane Suite 101, DALLAS, TX, 75229 PHONE: (214) 220-3999 FAX: (214) 220-0099 EMAIL: [email protected]
TAG
www.captiveaire.com
FILTER(S)
HOOD
NO.
CONTRACT DATE:
09.21.15
BUILDING TYPE:
DBR 37
PLAN VERSION:
009.00.00
SITE NUMBER:
311465 / 434385
STORE NUMBER:
2015388.14
PIZZA HUT
123 Minden Shopping Dr.
Minden, LA 71055
DATE:
DWG.#:
2322728
DRAWN DJL-45
BY:
SCALE:
MASTER DRAWING
DBR 37
SHEET NO.
HOOD DWGS.
GREASE BOX
HINGE KIT - SHIPS LOOSE FOR CURB SUPPLIED BY OTHERS
21
DUCTWORK BETWEEN
EXHAUST RISER ON HOOD
AND FAN (BY OTHERS)
M3.0
PLOT DATE:
REVISIONS
N
O
I
T
C
Y
U
L
R
N
T
O
S
S
N
E
O
S
C
O
D
P
R
R
A
U
N
P
I
U
D
I
O
B
H
C OR
F
LOCATION ON HOOD
1
E56370036
Ansul R102
3.0
8
Wall Mount Left
N/A
QTY. BY
DIST.
0 - 0 - METALCAP-CB BLOWOFF CAP - Metal
4
0
1 - 1 - AT - 3.0 TANK(#1B) - 3.0 Gallon SS Tank (for use with Automan Release, Actuator,
or SS Enclosure (UL/ULC))
0
1
2 - 2 - AP - AR AUTOMAN RELEASE - Ansul Automan Mechanical Release (UL)429853 Tank
sold separately
0
1
5 - 5 - LIQ-3.0 AGENT - Ansulex Low PH Wet Chemical Agent, 3 Gallon (UL) 79372
0
1
- APPLIANCE DIMENSIONS LISTED REPRESENT THE COOKING SURFACE
SIZE, NOT THE OVERALL APPLIANCE SIZE.
7 - 7 - 101-20 CARTRIDGE - Carbon Dioxide 101-20, 3 Gallon Cartridge (R-102)
0
1
10 - 10 - TLINK LINK - Test Link (1 test link)
0
1
11 - 11 - MICRO-SDA MICROSWITCH - Single Dual Electric Switch, One Standard Switch,
One Alarm Duty Switch 437155
0
1
14 - 14 - 419336 NOZZLE - 1W Nozzle, Duct/Appliance (Replaces ANSUL Part# 419347,
CAS Part# 419336) A0001266
1
0
16 - 16 - 419335 NOZZLE - 1N Nozzle, Plenum/Appliance (Replaces ANSUL Part# 419346,
CAS Part# 419335) A0001265
1
0
19 - 19 - 419338 NOZZLE - 3N Nozzle, Appliance (Replaces ANSUL Part# 419349, CAS
Part# 419338) A0001268
2
0
26 - 26 - QSA-3/8 QUIK SEAL - 3/8" (UL)
4
0
27 - 27 - QPSA-1/2 PULLEY SEAL - 1/2" Hood Seal (UL)
1
0
28 - 28 - S-DET DETECTOR - Series (Scissor Linkage) NEW#435547/435548 (OLD#417369/434480)
1
0
30 - 30 - ANS-500FL FUSIBLE LINK - 500deg F, R-102 and PIRANHA
1
0
34 - 34 - RPS-A REMOTE PULL STATION - Red composite (without wire rope) 434618 (Old
Macola #06-4835)
0
1
35 - 35 - PE-LT PULLEY ELBOW - Low Temp. Pulley Elbow, Set Screw Type ANSUL Part
#415670
0
10
36 - 36 - PE-HT PULLEY ELBOW - High Temp Pulley Elbow, Compression Type
1
0
Plenum
Duct
24"
- THIS FIRE SYSTEM COMPLIES WITH U.L. 300 REQUIREMENTS
24"
Hood # 1 (E56370035+E56370069)
Job #: 2322728
Job Name: Pizza Hut MUA 11 DBR 37A
Drawn By:
System Size: ANSUL-3.0 Total FP required: 8
Hood # 1 3' 0.00" Long x 33" Wide x 47" High
Riser # 1 Size: 8" Dia.
Hood # 1 Metal Blow-Off Caps included.
1W
34
1B
2
30
5
7
28
10 11
21.5" 16"
1N10"
10"
3N
3N
Fryer-M w/Drip Board
High Proximity
16.00" L x16.00" D
E56370036
KEY NUMBER - PART DESCRIPTION
Fryer-M w/Drip Board
High Proximity
16.00" L x16.00" D
1
QTY. BY
FACTORY
TAG
520 South Main Street, Suite 2531
Akron, OH 44311
330.572.2100 Fax: 330.572.2102
PLENUM PROTECTION
NOZZLE
DUCT PROTECTION
NOZZLE
DETECTORS
AGENT LINE
Job #: 2322728
Job Name: Pizza Hut MUA 11 DBR 37A
Drawn By:
System Size: ANSUL-3.0 Total FP required: 8
Hood # 1 3' 0.00" Long x 33" Wide x 47" High
Riser # 1 Size: 0" x 0"
SYSTEM CONTROL AUTOMAN
WITH AGENT TANK ENCLOSED
REMOTE
MANUAL
PULL STATION
NOTES
- FIELD PIPE DROPS AS SHOWN
SLEEVING, ELBOWS, TEES, AND NOZZLES SUPPLIED BY CAS
- RELOCATE NOZZLES IF FLOW PATTERN IS BLOCKED BY SHELVING,
SALAMANDERS, ETC.
- MAXIMUM 9 ELBOWS IN SUPPLY LINE.
- MINIMUM 72 INCHES OF AGENT LINE FROM TANK TO FIRST NOZZLE.
- IF APPLICABLE, PRE-PIPED CHARBROILER DROPS ARE SHIPPED LOOSE.
- FACTORY PIPING EXTENDS A MAXIMUM OF 6" ABOVE THE TOP OF THE HOOD.
- APPLIANCE DIMENSIONS LISTED REPRESENT THE COOKING SURFACE
SIZE, NOT THE OVERALL APPLIANCE SIZE.
- THIS FIRE SYSTEM COMPLIES WITH U.L. 300 REQUIREMENTS
SPECIFICATIONS
THE RESTAURANT FIRE SUPPRESSION SYSTEM SHALL BE THE PRE-ENGINEERED
TYPE WITH A FIXED NOZZLE AGENT DISTRIBUTION NETWORK. IT SHALL BE LISTED
WITH UNDERWRITERS LABORATORIES, INC. (UL)
THE SYSTEM SHALL BE CAPABLE OF AUTOMATIC DETECTION AND ACTUATION
WITH LOCAL OR REMOTE MANUAL ACTUATION. ACCESSORIES SHALL BE AVAILABLE
FOR MECHANICAL OR ELECTRICAL GAS LINE SHUT-OFF APPLICATIONS.
THE EXTINGUISHING AGENT SHALL BE A POTASSIUM CARBONATE, POTASSIUM
ACETATE-BASED FORMULATION DESIGNED FOR FLAME KNOCKDOWN AND SECUREMENT
OF GREASE RELATED FIRES. IT SHALL BE AVAILABLE IN PLASTIC CONTAINERS
WITH INSTRUCTIONS FOR LIQUID AGENT HANDLING AND USAGE.
THE REGULATED RELEASE MECHANISM SHALL BE COMPATIBLE WITH A FUSIBLE
LINK DETECTION SYSTEM. THE FUSIBLE LINK SHALL BE SELECTED AND
INSTALLED ACCORDING TO THE OPERATING TEMPERATURE IN THE VENTILATING
SYSTEM. THE FUSIBLE LINK SHALL BE SUPPORTED BY A DETECTOR BRACKET/
LINKAGE ASSEMBLY.
1A 1.5 GALLON TANK
1B 3.0 GALLON TANK
2
AUTOMAN RELEASE
3 3 GALLON TANK ENCLOSURE
3A 6 GALLON TANK ENCLOSURE
4 REGULATED ACTUATOR
5 ANSULEX LIQUID AGENT (3 GAL.)
6 ANSULEX LIQUID AGENT (1.5 GAL.)
7 CARTRIDGE (101-20)
8 CARTRIDGE (101-10)
9 CARTRIDGE (101-30)
9A CARTRIDGE (LT-A-101-30)
9B DOUBLE TANK CARTRIDGE
10
TEST LINK
11
DOUBLE MICROSWITCH
2W
DUCT NOZZLE (419337)
1W
NOZZLE ASSEMBLY (419336)
1F NOZZLE ASSEMBLY (419333)
1N NOZZLE ASSEMBLY (419335)
1/2N NOZZLE ASSEMBLY (419334)
3N
NOZZLE ASSEMBLY (419338)
245
NOZZLE ASSEMBLY (419340)
230 NOZZLE ASSEMBLY (419339)
2120
NOZZLE ASSEMBLY (419343)
290 NOZZLE ASSEMBLY (419342)
260 NOZZLE ASSEMBLY (419341)
28
DETECTOR BRACKET
29
LOW TEMP FUSIBLE LINK
30 HIGH TEMP FUSIBLE LINK
MGV
MECHANICAL GAS VALVE
EGV
ELECTRICAL GAS VALVE
34
REMOTE MANUAL PULL STATION
S
SWIVEL ADAPTOR
CARROLLTON, TX, 75007
APPLIANCE PROTECTION
NOZZLE
Pizza Hut MUA 11 DBR 37A
DETECTION LINE
1901 Royal Lane Suite 101, DALLAS, TX, 75229 PHONE: (214) 220-3999 FAX: (214) 220-0099 EMAIL: [email protected]
SYSTEM
BUILT
IN
ACCORDANCE
WITH
NFPA
No. 96
FLOW
POINTS
R
SIZE
www.captiveaire.com
TYPE
DALLAS OFFICE
Tag
FIRE
SYSTEM
NO.
NOTES
- FIELD PIPE DROPS AS SHOWN
SLEEVING, ELBOWS, TEES, AND NOZZLES SUPPLIED BY CAS
- RELOCATE NOZZLES IF FLOW PATTERN IS BLOCKED BY SHELVING,
SALAMANDERS, ETC.
- MAXIMUM 9 ELBOWS IN SUPPLY LINE.
- MINIMUM 72 INCHES OF AGENT LINE FROM TANK TO FIRST NOZZLE.
- IF APPLICABLE, PRE-PIPED CHARBROILER DROPS ARE SHIPPED LOOSE.
- FACTORY PIPING EXTENDS A MAXIMUM OF 6" ABOVE THE TOP OF THE HOOD.
INSTALLATION
FIRE
SYSTEM
NO.
CONTRACT DATE:
09.21.15
BUILDING TYPE:
DBR 37
PLAN VERSION:
009.00.00
SITE NUMBER:
311465 / 434385
STORE NUMBER:
2015388.14
PIZZA HUT
123 Minden Shopping Dr.
Minden, LA 71055
DATE:
DWG.#:
2322728
DRAWN DJL-45
BY:
SCALE:
MASTER DRAWING
SHEET NO.
DBR 37
HOOD DWGS.
M3.1
PLOT DATE:
N
O
I
T
C
Y
U
L
R
N
T
O
S
S
N
E
O
S
C
O
D
P
R
R
A
U
N
P
I
U
D
I
O
B
H
C OR
F
520 South Main Street, Suite 2531
Akron, OH 44311
330.572.2100 Fax: 330.572.2102
CONTRACT DATE:
09.21.15
BUILDING TYPE:
DBR 37
PLAN VERSION:
009.00.00
SITE NUMBER:
311465 / 434385
STORE NUMBER:
2015388.14
PIZZA HUT
123 Minden Shopping Dr.
Minden, LA 71055
DBR 37
HOOD DWGS.
M3.2
PLOT DATE:
KITCHEN HOOD EXHAUST FAN
40" MIN.
DISCHARGE HEIGHT
N
O
I
T
C
Y
U
L
R
N
T
O
S
S
N
E
O
S
C
O
D
P
R
R
A
U
N
P
I
U
D
I
O
B
H
C OR
F
NEMA 3R DISCONNECT FACTORY
WIRED FROM MOTOR TO
DISCONNECT THROUGH THE
BREATHER TUBE
520 South Main Street, Suite 2531
Akron, OH 44311
330.572.2100 Fax: 330.572.2102
NOTE:
LOCATE EXHAUST FANS MIN. 10'-0"
FROM ANY OUTSIDE AIR INTAKE
FIRE-PROOF INSULATION
LIQUID TIGHT FLEXIBLE CONDUIT
VENTED CURB EXTENSION
MIN. 16" GA. WELDED EXHAUST
DUCT - EXTEND MIN. OF 18"
ABOVE ROOF DECK PER NFPA
ROOF
PREFABRICATED GALV. STEEL
CURB WITH INSULATION.
GREASE TRAP
NOT USED
N.T.S.
5
EXHAUST FAN
N.T.S.
1
STANDARD CURB CAP,
FASTEN PER MFR'S
RECOMMENDATIONS
FACTORY INSTALLED
DISCONNECT & CONDUIT
CHASE, PROVIDE POWER TO
DISCONNECT WITHIN CURB
OPPOSED BLADE DAMPERS
METAL EXHAUST DUCT
RESTROOM FAN
KITCHEN GREASE EXHAUST HOOD FIRE SUPPRESSION SYSTEM:
N.T.S.
2
ALL-THREADS ROD
THE EXHAUST HOOD MANUFACTURER SHALL FURNISH AND INSTALL A KITCHEN EXHAUST
HOOD FIRE SUPPRESSION INSTALLED TO MEET ALL NFPA AND LOCAL CODE REQUIREMENTS.
SUPPLY
WASHER & NUT
THE SYSTEM SHALL INCLUDE:
1. CYLINDER CONTROL HEAD
GASKET
2. PIPING
HOOD MOUNTING
CHANNEL ON HOOD
L
3. CYLINDERS - CONTAINING FIRE SUPPRESSION CHEMICAL AGENT TO MEET ALL LOCAL
CODE REQUIREMENTS
4. FIRE SUPPRESSION NOZZLE AS REQUIRED BY THE KITCHEN EXHAUST HOOD AND
KITCHEN EQUIPMENT
HOOD
TRANSITION TO ROUND SEE PLANS
FOR SIZE (WHERE OCCURS)
5. REMOTE MANUAL PULL STATION
6. FUSIBLE LINKS
NOTE:
L = 4" MIN. OR 1/4 OF "W"
BRANCH DUCT - RECTANGULAR OR
ROUND
W
CONTRACT DATE:
7. AUTOMATIC GAS SHUT-OFF VALVE & SHUNT TRIP FOR ELECTRICAL DEVICES UNDER HOOD
8. CORNER PULLEYS
YMC001
BUTTERFLY DAMPER WITH ARM &
LOCKING QUADRANT (TYPICAL)
THE FIRE SUPPRESSION SYSTEM SHALL BE INTERLOCKED WITH THE HVAC, GAS,
ELECTRICAL AND BUILDING FIRE ALARM SYSTEMS AS REQUIRED BY CODE.
BOLT CONNECTION TO HOOD
THE FIRE SUPPRESSION SHALL BE PROVIDED WITH A POWER BACK-UP SYSTEM TO ALLOW
THE SYSTEM TO OPERATE WHEN ELECTRICAL POWER TO THE SPACE IS DISCONNECTED.
N.T.S.
3
LOW VELOCITY DUCT
BUILDING TYPE:
DBR 37
PLAN VERSION:
009.00.00
SITE NUMBER:
311465 / 434385
STORE NUMBER:
2015388.14
PIZZA HUT
INSULATED FLEX DUCT - PROVIDE
SHORT RADIUS RIGID METAL ELBOW
WHERE 18" R. FLEX ELBOW CANNOT
BE MAINTAINED
THE CONTRACTOR SHALL SCHEDULE AND CONDUCT ALL TESTS AND INSPECTIONS
REQUIRED FOR THE APPROVAL OF THE FIRE SUPPRESSION SYSTEM.
09.21.15
123 Minden Shopping Dr.
Minden, LA 71055
TRUNK DUCT
DIRECTION OF AIR FLOW
STRAP HANGER
DUCTWORK:
KITCHEN HOOD GREASE EXHAUST DUCTWORK:
NYLON STRAP FASTENER (TYP)
BLACK STEEL WELDED CONSTRUCTION (16 GA) TO BE FABRICATED AND INSTALLED PER
SMACNA STANDARDS AND SPECIFICATIONS AND ALL LOCAL CODE REQUIREMENTS.
1 1/2" DUCT WRAP INSULATION
EXHAUST
RETURN
SUPPLY
DBR 37
L
.
IN
.M
"R
18
THE KITCHEN HOOD EXHAUST DUCTWORK SHALL BE COVERED WITH A 1-HR CODE
APPROVED FIRE RATED INSULATION.
THE CONTRACTOR SHALL INCLUDE IN HIS PRICE:
W
- ALL NECESSARY TRANSITION AND CONNECTION FITTINGS TO THE HOOD AND EXHAUST
FANS.
NOTE:
MAXIMUM ALLOWABLE LENGTH OF FLEX DUCT
RUNOUTS TO SUPPLY DIFFUSERS = 5'-0". FLEX
DUCT IS NOT ALLOWED ON EXHAUST, RETURN
OR EXPOSED DUCTWORK.
- ALL CLEAN-OUT ACCESS PANELS AS REQUIRED BY CODE.
- ALL ELBOW AND TRANSITION FITTINGS.
L = 4" MINIMUM
OR 1/4 OF "W"
MECHANICAL
DETAILS
BRANCH DUCT RECTANGULAR OR
ROUND
TOP CONNECTION
PMF002
- ALL HANGERS AND SUPPORTS.
SIDE CONNECTION
- SHOP DRAWINGS SHOWING PROPOSED FABRICATION AND INSTALLATION COORDINATED
WITH EXISTING FIELD CONDITIONS AND OTHER TRADES.
HOOD EXHAUST NOTES
NO SCALE
7
CEILING DIFFUSER CONNECTIONS
N.T.S.
6
DUCT CONNECTION DETAIL
N.T.S.
4
M4.0
PLOT DATE:
N
O
I
T
C
Y
U
L
R
N
T
O
S
S
N
E
O
S
C
O
D
P
R
R
A
U
N
P
I
U
D
I
O
B
H
C OR
F
520 South Main Street, Suite 2531
Akron, OH 44311
330.572.2100 Fax: 330.572.2102
CONTRACT DATE:
09.21.15
BUILDING TYPE:
DBR 37
PLAN VERSION:
009.00.00
SITE NUMBER:
311465 / 434385
STORE NUMBER:
2015388.14
PIZZA HUT
123 Minden Shopping Dr.
Minden, LA 71055
DBR 37
HVAC
SPECIFICATIONS
M5.0
PLOT DATE:
N
O
I
T
C
Y
U
L
R
N
T
O
S
S
N
E
O
S
C
O
D
P
R
R
A
U
N
P
I
U
D
I
O
B
H
C OR
F
520 South Main Street, Suite 2531
Akron, OH 44311
330.572.2100 Fax: 330.572.2102
CONTRACT DATE:
09.21.15
BUILDING TYPE:
DBR 37
PLAN VERSION:
009.00.00
SITE NUMBER:
311465 / 434385
STORE NUMBER:
2015388.14
PIZZA HUT
123 Minden Shopping Dr.
Minden, LA 71055
DBR 37
HVAC
SPECIFICATIONS
M5.1
PLOT DATE:
N
O
I
T
C
Y
U
L
R
N
T
O
S
S
N
E
O
S
C
O
D
P
R
R
A
U
N
P
I
U
D
I
O
B
H
C OR
F
HWR
HWR
HOT WATER RETURN
N
O
I
T
C
Y
U
L
R
N
T
O
S
S
N
E
O
S
C
O
D
P
R
R
A
U
N
P
I
U
D
I
O
B
H
C OR
F
520 South Main Street, Suite 2531
Akron, OH 44311
330.572.2100 Fax: 330.572.2102
F
E
10
2-WAY CO
ECO
S
1
S
FS
1
5
1
S
1
V
V
FCO
CO
2-WAY CO
8
1
ECO
SEWER
1
V
FCO
12
17
B.I.B.
1
S
2
DM
9
1
11
FS
S
1
3
10
CD
1
FD
CD
1
FS
CO
13
1
FS
13
4
3
HD
C
5
2
2"V
3"V UP IN WALL COORDINATE
WITH STRUCTURAL SHEAR
WALL CONSTRUCTIONS.
1
12
CD
1
S
2"V
1
FD
1
4"
1
15
1
S
GW
ECO
GI
D
1
FD
GW
16
2-WAY CO
14
1
1
FD
1
GW
4"
2-WAY CO
1
SEWER
4"
V
1
5
CD
TO SANITARY MAIN
18
RTU
V
ECO
6
3"VTR
RTU
1
1
2
V
1
WC
1
L
FD
7
1
V
1
L
1
FD
4
B
1
1
S
S
S
S
6
3"VTR
WC
CO
1
WCO 1
A
CONTRACT DATE:
BUILDING TYPE:
DBR 37
PLAN VERSION:
009.00.00
SITE NUMBER:
12
10
11
9
8
7
6
5
4
3
2
A. REFER TO RISER DIAGRAM ON SHEET P5.0 FOR ALL WASTE AND VENT SIZES.
F
E
GENERAL NOTES
D
A
ROUTE WASTE LINE FROM DISHWASHER TO FLOOR SINK WITH INDIRECT
WASTE CONNECTION. PROVIDE AIR GAP PER LOCAL CODE.
1
PROVIDE WITH TRAP PRIMER AND CONNECT TO NEAREST CW PIPING.
2
PROVIDE CONDENSATE LINE AND DRAIN LINE FROM ICE MACHINE TO FLOOR
SINK, PROVIDE AIR GAP PER LOCAL CODE.
12
GREASE WASTE PIPING SHALL BE COMBINATION WASTE AND VENT.
3
PROVIDE WASTE LINES FROM BEVERAGE UNIT/ICE BIN TO HUB DRAIN, PROVIDE
AIR GAP PER LOCAL CODE.
13
ROUTE DRAIN LINE FROM BEER DISPENSER/HAND SINK TO FLOOR SINK,
PROVIDE AIR GAP PER LOCAL CODE.
4
PROVIDE 3/4" COPPER CONDENSATE FROM DRAIN PROVIDED BY VENDOR TO
OUTFALL AT MOP SINK (HEAT TAPE IS SUPPLIED WITH FREEZER
CONDENSATE).
14
SAMPLE WELL BASIN. SEE SITE UTILITY DRAWING FOR EXACT
LOCATION . SEE DRAWING SHEET P7.0 FOR DETAILS.
5
CONDENSATE DRAIN FROM HVAC UNITS ON ROOF, RUN ABOVE CEILING TO
AND DROP DOWN TO DISCHARGE TO MOP SINK.
15
6
VENT UP THROUGH ROOF. SEE DRAWING SHEET P5.0 FOR ALL VENT AND PIPE
SIZING.
OFFSET 2" VENT AT A MINIMUM OF 45 DEGREES FOR AT LEAST 6" PRIOR TO
HORIZONTAL TRANSITION. EXTEND VENT TO/UP EXTERIOR WALL TO ROOF
AS INDICATED. THIS VENT MAY NOT TIE INTO ANY OTHER VENT UNTIL IT
REACHES A HEIGHT OF A MINIMUM OF 6" ABOVE FLOOD RIM LEVEL OF
HIGHEST FIXTURE SERVED.
7
PROVIDE 3/4" COPPER CONDENSATE FROM EVAPORATOR COILS IN COOLER.
ROUTE TO MOP SINK AND MAINTAIN A 2" AIR GAP ABOVE FLOOD RIM.
LOCATION OF CONDENSATE SHALL BE LOCATED AS HIGH AS POSSIBLE IN
COOLER TO ALLOW SHELVING INSTALLATION.
8
DO NOT ROUTE PIPING OVER ELECTRICAL PANEL.
9
PROVIDE CONDENSATE LINE AND DRAIN LINE FROM DISHWASHER TO
FLOOR SINK, PROVIDE AIR GAP PER LOCAL CODE.
10
ROUTE WASTE LINE FROM SINK TO FLOOR SINK WITH INDIRECT WASTE
CONNECTION. PROVIDE AIR GAP PER LOCAL CODE.
11
1/4"=1'-0"
16
1000 GALLON GREASE INTERCEPTOR. SEE SITE UTILITY DRAWING FOR
EXACT LOCATION . SEE DRAWING SHEET P7.0 FOR DETAILS.
17
6" PVC CHASE FROM BAG-IN-BOX LOCATION TO DRINK DISPENSERS
ROUTED BELOW SLAB.
18
EXTEND AND CONNECT NEW WASTE TO EXISTING SANITARY SEWER.
VERIFY EXACT LOCATION AND CONNECTION REQUIREMENTS. THE
CONTRACTOR SHALL VERIFY ALL EXISTING CONDITIONS FOR
ROUTING AND CONNECTION OF WASTE LINES.
KEY NOTES
311465 / 434385
STORE NUMBER:
1
WASTE AND VENT PLAN
09.21.15
2015388.14
PIZZA HUT
123 Minden Shopping Dr.
Minden, LA 71055
DBR 37
WASTE
AND VENT
PLAN
P2.0
B
PLOT DATE:
N
O
I
T
C
Y
U
L
R
N
T
O
S
S
N
E
O
S
C
O
D
P
R
R
A
U
N
P
I
U
D
I
O
B
H
C OR
F
520 South Main Street, Suite 2531
Akron, OH 44311
330.572.2100 Fax: 330.572.2102
F
E
3
9
S
MV
1
1
S
3
9
5
S
MV
1
1
20
7
RTU
1
3
9
S
MV
1
1
MV
11
15
7
9
1
1
D
CW
21
HW
WH
2
HWR
19
B.I.B.
1
4
HW
HWR
5
8
3
S
6
NEW GAS METER AT METER BANK
APPROXIMATELY 75' AWAY. COORDINATE
INSTALLATION OF NEW GAS METER AND
REGUALTOR WITH LOCAL UTILITY COMPANY.
CW
2
S
22
CW
4
1
17
11
1
DM
14
S
S
3
RTU
18
16
2
C
13
WC 1
L
MV
1
1
12
9
10
L
MV
1
1
12
9
B
S
S
S
S
10
13
WC 1
A
CONTRACT DATE:
BUILDING TYPE:
DBR 37
PLAN VERSION:
009.00.00
SITE NUMBER:
12
10
11
9
8
7
6
5
4
3
2
A. NO ROOF PENETRATIONS PERMITTED WITHIN THE ROOF "WATER VALLEYS", REFER
TO ROOF PLAN FOR LOCATIONS.
1
2" GAS DOWN TO OVENS. SEE OVEN GAS PIPING DETAIL ON SHEET P6.0.
13
1/2" CW DOWN TO WATER CLOSET. PROVIDE 3/8" STOP.
2
1 1/4" GAS DOWN TO WATER HEATER WITH GAS COCK, DIRT LEG, AND UNION.
14
SLEEVE GAS LINE THRU WALL AND SEAL WATER TIGHT.
B.
3
1/2" TEMPERED WATER DOWN IN WALL TO HAND SINK.
15
DO NOT ROUTE WATER LINES OVER ELECTRICAL PANELS.
4
1" HOT AND COLD WATER DOWN TO WATER HEATER. REFER TO DETAIL ON
SHEET P6.0.
16
RISE REFRIGERANT LINES UP THRU ROOF TO REMOTE CONDENSING UNITS VIA MULTIPLE
PIPE FLASHING. REFER TO ROOF PLAN ON SHEET A3.0.
5
3/4" CW RISE AND VALVE WATER LINES LINE DOWN TO WATER FILTER SERVING
BEVERAGE DISPENSER AND TEA BREWER. COORDINATE WITH BEVERAGE
COMPANY FOR CONNECTIONS TO TAKE PLACE INSIDE THE CABINET. PROVIDE
IN-LINE ASSE 1022 BACKFLOW PREVENTER AND SHUT OFF VALVE AT EACH
UNIT. TEA BREWER WATER SUPPLY MUST BE METAL BRAIDED HOSE.
17
RISE AND VALVE WATER LINES ABOVE FLOOR, BELOW BAR, TO SERVE BAR SINK.
18
PROVIDE 3/4"HOT WATER TO DISHWASHER. CONTRACTOR SHALL PROVIDE AND INSTALL
WATER HAMMER ARRESTOR (PDI SIZE A, ASSE 1010) AND 25 PSI PRESSURE REGULATING
VALVE WITH INTERNAL THERMAL EXPANSION BY-PASS ON SUPPLY LINE. CONTRACTOR SHALL
INSTALL VACUUM BREAKER AND ALL ACCESSORIES PROVIDED WITH THE DISHWASHER PER
MANUFACTURER'S RECOMMENDATIONS.
WATER DISTRIBUTION PIPING IS SHOWN ABOVE FINISHED CEILING. UNDERSLAB
DISTRIBUTION ALLOWED AT CONTRACTOR OPTION. COORDINATE ALL DETAILS.
NO JOINTS ALLOWED IN WATER PIPING LOCATED BELOW SLAB.
C. REFER TO SHEET P5.0 FOR WATER AND GAS ISOMETRIC DRAWINGS. REFER TO
ISOMETRIC DRAWINGS FOR PIPE SIZES.
F
GENERAL NOTES
E
6
3/4" HOT AND COLD WATER DOWN IN WALL TO 3-COMPARTMENT SINK.
INSTALL WATTS NO.9N BACKFLOW PREVENTER FOR EACH WATER LINE
CONNECTION TO FAUCET.
7
SOLENOID EMERGENCY SHUT-OFF VALVE ABOVE ACCESSIBLE CEILING FOR
EXHAUST HOOD FIRE SUPPRESSION SYSTEM.
8
EXTEND 1/2" HOT AND COLD WATER DOWN IN THE WALL TO THE MOP SINK.
9
THERMOSTATIC MIXING VALVE ABOVE CEILING.
10
ROUTE REFRIGERANT LINES TO REMOTE CONDENSERS AS REQUIRED.
INSTALL PER MANUFACTURER'S RECOMMENDATIONS.
11
12
19
BUNDLED DRINK SYSTEM THRU WALL. VERIFY EXACT ROUTING. ROUTE LINES THRU WALL TO
SERVE DRINK SYSTEM.
20
ROUTE 1 1/4" GAS LINE DOWN IN WALL, STUB THRU WALL, AND VALVE AT 12" A.F.F.
FOR GAS FRYER.
21
EXTEND AND CONNECT NEW 1" DOMESITC WATER LINE INTO EXISTING 1" DOMESTIC
COLD WATER (METER IN VAULT). INSTALL NEW BACKFLOW PREVENTER IN VAULT AS
REQUIRED BY LOCAL WATER CO.
1 1/4" GAS UP TO RTU THRU CURB BASE. INSTALL DIRT LEG, GAS COCK, AND
UNION AT UNIT CONNECTION.
22
ROUTE NEW 1" DOMESTIC COLD WATER BELOW SLAB AND RISE UP AS SHOWN.
1/2" TEMPERED AND COLD WATER LINES DOWN IN WALL TO LAVATORY.
23
PROVIDE INLINE HOT WATER RECIRCULATION PUMP AND CHECK VALVE. REFER TO SHEET P3.0
FOR DETAILED PIPING SCHEMATIC.
1/4"=1'-0"
311465 / 434385
STORE NUMBER:
1
WATER AND GAS PLAN
09.21.15
A
2015388.14
PIZZA HUT
123 Minden Shopping Dr.
Minden, LA 71055
DBR 37
WATER
AND GAS
PLAN
P3.0
KEY NOTES
B
PLOT DATE:
1
1
INSIDE WALL
1
FD
1
FS
15'-8"
26'-10"
19'-1121"
FS
FD
39'-221"
36'-6"
1
1
1
HD
1
1
FS
S
28'-221"
1
S
20'-221"
21'-221"
1
L
16'-2"
15'-3"
FD
1
FD
1
13'-8"
1
FS
FD
13'-121"
1
11'-5"
9'-8"
S
WC
2
1
FS
4'-4"
7'-1121"
S
INSIDE WALL
1
L
WC
1
N
O
I
T
C
Y
U
L
R
N
T
O
S
S
N
E
O
S
C
O
D
P
R
R
A
U
N
P
I
U
D
I
O
B
H
C OR
F
520 South Main Street, Suite 2531
Akron, OH 44311
330.572.2100 Fax: 330.572.2102
INSIDE WALL
INSIDE WALL
G
FS
1
FD
1
S
1
G
1'-1"
5'-0"
5'-0"
1
S
2
FS
FS
1
1
L
1
WC
1
FD
1
L
1
FD
1
WC
1
1
FD
1
6'-9"
9'-721"
HD
FD
FS
1
FS
1
11'-621"
13'-821"
14'-5"
15'-8"
17'-421"
18'-521"
22'-721"
24'-1121"
27'-521"
CONTRACT DATE:
09.21.15
BUILDING TYPE:
DBR 37
PLAN VERSION:
009.00.00
SITE NUMBER:
311465 / 434385
STORE NUMBER:
PLUMBING ROUGH-IN PLAN
EQUIP #
EQUIPMENT ITEM
TYPE
ELEVATION
REMARKS
EQUIP #
EQUIPMENT ITEM
TYPE
ELEVATION
FS
1
FLOOR SINK
--
S
4
SERVICE SINK
CW/HW
+9" A.F.F.
--
FS
2
FLOOR SINK
--
S
4
SERVICE SINK
W
+19" A.F.F.
--
FD
1
FLOOR DRAIN
--
S
5
BAR SINK
CW/HW
+3" A.F.F.
--
HD
1
HUB DRAIN
--
WH
1
WATER HEATER
CW
WH
1
WATER HEATER
G
WC
1
WATER CLOSET FLUSH TANK
WC
2
WC
COLD WATER
GAS
B. IT IS THE RESPONSIBILITY OF THE CONTRACTOR TO COORDINATE THIS DATA ON THE
LOCATION OF ALL PLUMBING ROUGH-INS WITH INFORMATION PROVIDED ON THE
ARCHITECTURAL AND THE STRUCTURAL DRAWINGS AND THE EQUIPMENT ACTUALLY
SUPPLIED AND TO CONFIRM THE CORRECTNESS OF ANY DIMENSIONS INDICATED
HEREIN.
FLOOR DRAIN
1
TEMPERED WATER
G
--
C-919
TRIPLE FRYER
G
+12" A.F.F.
+15" A.F.F.
--
C-924
PIZZA OVEN (TRIPLE DECK)
G
+10" A.F.F.
CW
+10" A.F.F
--
N-100
GLASS WASHER
HW
+8" A.F.F.
INSTALL PER MANUF. INSTRUCTIONS
WATER CLOSET FLUSH TANK
CW
+10" A.F.F
--
N-100
GLASS WASHER
W
+16" A.F.F.
INSTALL PER MANUF. INSTRUCTIONS
3
WATER CLOSET FLUSH TANK
CW
+8" A.F.F
--
S-570
CARBONATOR
FW
+36" A.F.F.
VALVE BELOW COUNTER
UR
1
URINAL FLUSH VALVE
CW
+40" A.F.F.
WALL MOUNTED
S-590
WATER FILTER SYSTEM
CW
+94" A.F.F.
INLET TO & OUTLET FROM FILTER
UR
1
URINAL WASTE STUB
W
+9-1/2" A.F.F.
WALL MOUNTED
S-906
DRINK DISPENSER
FW
-
VIA SYRUP BUNDLE
L
1
LAVATORY
TW
+20" A.F.F.
--
S-907
COFFEE BREWER
FW
+12" A.F.F.
AND ICE TEA BREWER S-928
L
1
LAVATORY WASTE LINE
W
+16-1/2" A.F.F.
--
S-928
ICE TEA BREWER
FW
+36" A.F.F.
VALVE BELOW COUNTER
S
1
HAND SINK
TW
+18" A.F.F
RIM OF LAV @ +2'-8" A.F.F.
S-936
HOT HOLDING CABINET
FW
+78" A.F.F.
S
2
MOP SINK FAUCET
CW/HW +36" A.F.F
--
S-937
HOT HOLDING CABINET
FW
+78" A.F.F.
S
3
3-COMPARTMENT SINK FAUCET
CW/HW +38" A.F.F
--
S-957
BAR GUN DRINK DISPENSER SYSTEM
FW
-
A
A. ALL DIMENSIONS TO FLOOR SINKS, FLOOR DRAINS, AND HUB DRAINS ARE TO CENTER
OF FIXTURE.
HOT WATER
REMARKS
1/4"=1'-0"
2015388.14
PIZZA HUT
123 Minden Shopping Dr.
Minden, LA 71055
VERIFY ROUGH-IN IN HEIGHTS WITH FIXTURE PROVIDED. RIM SHALL BE NO HIGHER
THAN 17" AFF AND FLUSH VALVE HANDLE SHALL BE 44" AFF MAX. DIMENSION.
FLOOR SINK
DBR 37
HUB DRAIN
WASTE OUTLET
UNDERGROUND
PLMB. ROUGH-IN
FLOOR CLEANOUT
WALL CLEANOUT
FILTERED WATER
VIA SYRUP BUNDLE
P4.0
VENT UP FROM UNDER SLAB
WATER LINE THRU FLOOR.
PLUMBING ROUGH-IN SCHEDULE
D
SYMBOL LEGEND
C
PLUMBING ROUGH-IN NOTES
B
PLOT DATE:
ECO 1
2-WAY CO
N
O
I
T
C
Y
U
L
R
N
T
O
S
S
N
E
O
S
C
O
D
P
R
R
A
U
N
P
I
U
D
I
O
B
H
C OR
F
MV
S
MV
1
4" SANITARY SEWER TO
SITE SANITARY MAIN
1
1
520 South Main Street, Suite 2531
Akron, OH 44311
330.572.2100 Fax: 330.572.2102
4" WASTE TO 1000 GALLON
EXTERIOR GREASE INTERCEPTOR
S
MV
RP
1 1/2"
1
1
ECO 1
2-WAY CO
MV
1
2"
HS
1
SS
4"
HW
WH
WH
R
1
1
S
1 1/2"
5
MV
4
S
S
MV
HW
R
FS
4"
3" VENT TO 1000 GALLON
EXTERIOR GREASE INTERCEPTOR
1
1
1
2"
2"
GW
4"
4"
3"
HS
4"
2"
3"VTR
1 1/2"
SS
3"VTR
R
HW
MV
1
ROUTE BELOW
SLAB TO SODA
CABINET
1
LAV
2"
SODA
WC
1 1/2"
2"
ROUTE BELOW
SLAB TO BAR
CW
TW
DM
1
WC
4"
FS
2"
4"
2"
2"
2"
4"
FD
FCO
LAV
4"
3"
FS
4"
WCO
3"
WC
S
S
MV
1
1
3
S
S
HS
4"
SS
1
1
SS
3"
FD
2"
4"
GW
2"
4"
WC
L
2"
FD
4"
2"
1 1/2"
CW
MV
2"
3"
FD
3"
1
4"
HD
4
1
FS
4"
FS
WATER ISOMETRIC
N.T.S.
4
FD
GW
3"
4"
4"
FCO
WASTE AND VENT ISOMETRIC
N.T.S.
1
GAS DEMAND SCHEDULE
RTU-1
250 MBH
RTU-2
200 MBH
WH-1 (2 @ 199 MBH EA)
398 MBH
PIZZA OVEN (3 @ 150 MBH EA)
450 MBH
FRYER (2 @ 80 MBH EA.)
160 MBH
TOTAL
DEMAND
1458 MBH =1,458,000 BTUH
PLUMBING CONTRACTOR SHALL VERIFY THE GAS PRESSURE AT
EACH APPLIANCE BEFORE TURNOVER. PIPE SIZED BASED ON 7"
W.C. DELIVERY PRESSURE AND 0.5" W.C. PRESSURE DROP PER
INTERNATIONAL FUEL GAS CODE TABLE 402.1(1). NEW GAS
METER LOCATED APPROXIMATELY 150' AWAY ON LONGEST RUN.
CONTRACT DATE:
RTU
DBR 37
PLAN VERSION:
009.00.00
311465 / 434385
STORE NUMBER:
NOT USED
N.T.S.
2
2015388.14
PIZZA HUT
123 Minden Shopping Dr.
Minden, LA 71055
2-1/2"G ABOVE CEILING
FRYERS
BUILDING TYPE:
SITE NUMBER:
EMERGENCY
GAS SHUT-OFF
1
09.21.15
EMERGENCY
GAS SHUT-OFF
RISE UP IN WALL
TO GAS METER,
BY LOCAL
UTILITY.
DIRT LEG
(TYPICAL)
WH
WH
1
1
PIZZA
OVEN
DBR 37
1-1/4"
(TYP)
RISER
DIAGRAMS
RTU
2
P5.0
GAS ISOMETRIC
N.T.S.
5
NOT USED
3
PLOT DATE:
1/2" CW
EDGE OF WALL
TRAP PRIMER VALVE
2" GAS IN WALL
CONNECTION TO DRAIN PAN
FULL SIZE VENT TO ATMOSPHERE
1/2" CW TO FIXTURE
2" FULL PORT
GAS BALL VALVE W/
LEVER HANDLE (EQUAL
TO NIBCO FP-600)
2" GAS
DOWN IN WALL
N
O
I
T
C
Y
U
L
R
N
T
O
S
S
N
E
O
S
C
O
D
P
R
R
A
U
N
P
I
U
D
I
O
B
H
C OR
F
RTU
EQUIPMENT CURB
2"x1-1/4"
BELL REDUCER
1-1/4" FLEX
HOSE TO OVENS
REVISIONS
DATE
APPRVD.
Unit 1
Unit 2
RETURN CONDENSATE DRAIN LINE
THROUGH CURB, CONNECT TO
MAIN ABOVE CEILING AND
TERMINATE 2" ABOVE RIM OF MOP
SINK. INSULATE ALL PIPING BEYOND
THIS PENETRATION
Notes:
1. Size the pump to provide at least 2 GPM through the system at
10 ft of head plus piping losses.
System
Controller (*4)
2. Pump Control Signal is Noritz's preferred method to control the
recirculation pump. For pumps larger than 85W, relay connection
should be used. If Noritz pump control is not used, an aquastat
may be be used to control pump.
N
UP
PRIORTY
BURNER
Power
gal.
ON/OFF
DOWN
-Please read instructions carefully before using this appliance.
WARNING
-Check actual and controller water temperature before entering
shower or bath.
FLOW METER
ALARM SET
burns instantly or death from scalding.
RC-7646M-1
FLOOR
FLOOR
SIDE ELEVATION
FRONT ELEVATION
CONTRACTOR SHALL MAKE CONNECTION TO OVENS
PER MANUFACTURER'S RECOMMENDATIONS
DEEP SEAL P-TRAP W/ TRAP
PRIMER CONNECTION
SEE WASTE PLAN FOR
CONDENSATE LINE BELOW ROOF
5. When connecting 2 devices, use only a single remote
controller.
520 South Main Street, Suite 2531
Akron, OH 44311
330.572.2100 Fax: 330.572.2102
DIRT LEG
1/2" CW
REMOVABLE THREADED CAP FOR
CLEAN-OUT & WINTER DRAINING
4. System Controller can be used to connect a 2 or more unit
multisystem application. When System Controller is in use, pump
control and tub alarm features are disabled. Refer to SC-201-6M
manual for detailed instructions in setting up system controller.
NORITZ
2" GAS THRU WALL
W/ ESCUTCHEON
WALL
DIRT LEG
FLOOR DRAIN
NOTE: PROVIDE TRAP PRIMERS FOR
DRAINS AS REQUIRED BY LOCAL
AUTHORITIES OR CODE.
3. If system controller isn't controlling pump, an aquastat may be
used. Wire aquastat to pump according to "Circulation Pump to
Aquastat Wire Diagram (PAWD.pdf)."
Remote
Controller (*5)
12"X12" S/S ACCESS PANEL IN WALL
OR CEILING IF REQUIRED
18"
DESCRIPTION
CLOSE NIPPLE
CONNECTOR
(TYP)
HANDLE IN
CLOSED
POSITION
YMS003
REV.
6. Size the piping to allow for the maximum flow rates of the units.
Isolator
Kit (*7)
RTU CONDENSATE
7. Noritz recommends the use of Isolator Kit (IK-WV-6) with
installation. Connections are available in Threaded, Sweat, or
Push-On. These kits include an integrated shut-off and service
valve with unions and a pressure relief valve.
Expansion Tank
(Install according
to local code)
13
TRAP PRIMER (AS REQ. BY CODE)
N.T.S.
9
OVEN GAS CONNECTION
Hot Water Return
Aquastat (*3)
Pump (*1)
Pump Control Signal (*2)
FILTER LINE F1 SUPPLIES
_______________________
SHUT-OFF VALVE (TYP)
1. CARBONATORS
2. DRINK DISPENSERS
THERMOMETER
8-10 Gallon
Storage Tank
(To alleviate cold
water sandwich)
MV
MF5/600
Noritz Accessories
11160 Grace Avenue
Fountain Valley, California 92708
866-7NORITZ (866-766-7489)
www.noritz.com
DRAWING NUMBER:
(2a2)N132M
DRAWING DATE:
December 19, 2007
Power
gal.
ON/OFF
DOWN
RC-CORD10 (10' Remote
Controller Cord, optional in 26')
VC-132M (Outdoor Vent Cap,
place on top of unit)
SC-201-6M (System Controller,
for 2 or more unit Multi-System)
Shut-off Ball Valve
Aquastat (Honeywell Model
#L6006A or L6006C)
Check Valve
Pump
F1
1
1/2" LINE
Union
Mixing Valve
Pressure Relief Valve (Watts 174A,
Zurn P3000BR, Cash Acme F-82)
Thermal Expansion Tank
DOMESTIC CW
YMF002
NORITZ
BURNER
2
DOMESTIC HW
WATER HEATERS
N.T.S.
1
8
KEY NOTES:
1
3/4" COLD WATER INLET TO 1/2" COPPER LINE AND FITTINGS AT FILTER.
2
3/4" F2 OUTLET W/ INTEGRAL BACKFLOW PREVENTER, EQUAL TO WATTS
REGULATOR CO. SERIES 007 AND SERVICE BALL VALVE.
TEMPERING VALVE
3" PVC EXHAUST
DUCT
MANUFACTURER
WALL
WATER HEATER
1/2" SWEAT/ 3/8" COMPRESSION
1/2" VINYL OR PVC CONDENSATE
DRAIN. MUST INCLUDE LOOP AIR
TRAP. 1/4"/ FT MIN. SLOPE
3"
5.
6.
7.
6
FACE OF SINK
NOTE:
1/2" PIPING SHALL BE HARD COPPER
LINE, OR BRAIDED STAINLESS HOSE.
SOFT COPPER IS NOT ACCEPTABLE.
1.
2.
3.
4.
N.T.S.
GENERAL NOTES:
1/2" COPPER LINE FROM
MIXING VALVE ABOVE
OVERALL DIMENSIONS 21-0" WIDE x 8" DEEP x 18" HIGH
SEE SCOPE OF WORK FOR ADDITIONAL INFORMATION.
SEE SHT. A2.0 FOR LOCATION.
INSTALLATION MUST COMPLY WITH STATE OR LOCAL PLUMBING
CODES.
THE UNIT MUST BE PROTECTED AGAINST FREEZING.
USE ONLY TEFLON (HIGH-LOW TEMPERATURE) TAPE TO SEAL
THREADED PARTS; NO PIPE DOPE.
DO NOT INSTALL WHERE LINE PRESSURE EXCEEDS 125 PSI OR
WHERE TEMPERATURE EXCEEDS 100 F.
1/2" SWEAT W/ 1/2" MALE ADAPTER
WATER HEATER PLATFORM
1/2" ANGLE STOP VALVE
TOP OF LOOP MUST BE BELOW
BOTTOM OF EXHAUST ELBOW.
1/2" HARD COPPER LINE TO SINK
1/2" WALL STRAP
HUB DRAIN/FLOOR SINK
NOT TO EXCEED 1" A.F.F.
1/2" SWEAT ELBOW
CONTRACT DATE:
SINGLE FOOT PEDAL
1/4" X 3" TAPCON HEX HEAD SCREW
1/2" SWEAT W/ 1/2" MALE ADAPTER
YMF001
UP
PRIORTY
Note: This diagram is for reference only. Installation must comply with State and Local Code,
all gas and water pipe must be sized correctly to specific length, according to accepted
RC-7646M-2 (Remote Controller) engineering methods or the UPC Code for Noritz Water Heaters to operate correctly.
KMW001
NORITZ
CARBON
N
PARTICULATE
N-132M
Domestic Hot Water
2 Unit Multi-System
Recirculation
1
CHECK VALVE (TYP)
Fixtures
APPLICATION:
5
HIGH FLOW WATER FILTRATION SYSTEM
Hot Water (*6)
MODEL:
N.T.S.
1/2" TEMPERED WATER TO
LAVATORIES
Cold Water Supply
Gas Supply
Relay for Pump
(If over 85 Watts)
N.T.S.
09.21.15
BUILDING TYPE:
DBR 37
PLAN VERSION:
009.00.00
SITE NUMBER:
311465 / 434385
STORE NUMBER:
19
15
WATER FILTER SYSTEM
N.T.S.
11
FOOT PEDAL
N.T.S.
7
WATER HEATER CONDENSATE DETAIL
N.T.S.
3
2015388.14
PIZZA HUT
123 Minden Shopping Dr.
Minden, LA 71055
PRESS. RELIEF VALVE
(PIPE TO F.S.)
2X4 WALL
BOOSTER HEATER
SHOCKSTOP
LAVATORY
UNION (TYP)
HW TO
DISHWASHER
DBR 37
FLOOR MOUNT UPRIGHT SUPPORT
PRESSURE/TEMPERATURE
GAUGE (TYP OF 2)
4x4 WELDED BASE PLATE W/ (4) 1/2"
HILTI KWIK BOLT II OR EQUAL
BLENDED PHOSPHATE WATER
TREATMENT SYSTEM (INSTALL
IN ACCESSIBLE LOCATION)
PRESSURE
REDUCING VALVE
FINISH FLOOR
P6.0
BALL VALVE
3/4"HW
20
16
12
LAVATORY SUPPORT
PLUMBING
DETAILS
N.T.S.
8
BOOSTER HEATER PIPING DETAIL
N.T.S.
4
PLOT DATE:
GREASE TRAP MODEL No. GT-1000
N
O
I
T
C
Y
U
L
R
N
T
O
S
S
N
E
O
S
C
O
D
P
R
R
A
U
N
P
I
U
D
I
O
B
H
C OR
F
30"
24"
GRADE
CAST IRON
FRAME AND COVER
520 South Main Street, Suite 2531
Akron, OH 44311
330.572.2100 Fax: 330.572.2102
6" PVC DOUBLE
TEE MANIFOLD
SPECIFICATIONS
CONCRETE :
4500 PSI AT 28 DAYS. UNIT IS OF MONOLITHIC
SEWER
SEWER
W
30"
VARIES
INLET
OUTLET
SECTIONAL RISER
RCP PIPE
JOINT SEALED w/
NONSHRINK GROUT
REINFORCEMENT:
INLET AND OUTLET
PIPING PROVIDED
BY OTHERS.
C.I. CASTINGS:
24"
DIAMETER AND BE TRAFFIC DUTY.
NOTES
2.
INLET
3.
USE 24" T&G R.C.P. FOR INSTALLATION GREATER THAN 6'-0" DEEP. (STD RING
AND M.H. COVER REQUIRED)
4.
SAMPLING WELL MUST BE SET IN A CIRCULAR OR SQUARE CONCRETE PAD ( 1'-0"
GREATER THAN OUTSIDE DIAMETER OF PIPE.)
18"
OUTLET
FRONT VIEW
TO BE INSTALLED ON PRIVATE PROPERTY, IN AN ACCESSIBLE LOCATION TO CITY
PERSONNEL.
USE 15" T&G R.C.P. FOR INSTALLATION FOR INSTALLATION 6'-0" DEEP AND LESS.
5.
INSIDE INSTALLATION NOT PERMITTED, WHERE OUTSIDE INSTALLATION IS POSSIBLE.
6.
INSTALLATION INSIDE BLDG MUST BE POURED IN PLACE (15"MIN) NO CONCRETE PIPE
IS PERMITTED, (AIR-TIGHT COVER REQUIRED.)
7.
LAWN INSTALLATION MUST BE 4" ABOVE FINISHED GRADE.
8.
DRIVE & SIDEWALK INSTALLATION MUST BE BROUGHT TO FINISHED GRADE
GRADE
GRADE
VENT
1.
6" VENT SLEEVE
LIQUID SURFACE
MONOLITHIC BAFFLE
H
GRADE
SPECIFICATIONS
CONCRETE :
CLASS 1 CONCRETE WITH OF DESIGN STRENGTH OF
4500 PSI AT 28 DAYS. UNIT IS OF MONOLITHIC
CONSTRUCTION AT FLOOR AND FIRST STAGE OF WALL
WITH SECTIONAL RISER TO REQUIRED DEPTH.
C.I. CASTINGS:
CAST IRON FRAMES AND GRATES ARE MANUFACTURED
OF GREY CAST IRON CONFORMING TO ASTM A48-76
CLASS 30, HEAVY-DUTY AASHTO H-20
REVERSIBLE CONFIGURATION
6" PVC DOUBLE
TEE MANIFOLD
FL2
NOTE:
GALVANIZED RISER
SUPPORT (TYPICAL)
SAMPLING WELL SHALL BE EQUIVALENT TO: PARKS
EQUIPMENT SERVICES SAMPLE WELL SWB-1; HANSON
PRE-CAST PRODUCTS TEST WELL; PW EAGLE SAMPLE
WALL. SAMPLE WELLS WILL HAVE A 15" DIAMETER
ACCESS COVER AND FLOW FROM INLET TO OUTLET
PIPING THROUGH SAMPLING WELL.
PRECAST CONCRETE
INTERCEPTOR
FL1
L
1000 GALLON GREASE INTERCEPTOR DETAILS
GENERAL NOTES:
SYRUP LINES, WATER LINES FOR THE CARBONATOR PUMPS, ICO2
LINE FOR PNEUMATIC GATE AND PLAIN WATER FOR THE
DISPENSERS ARE RUN INSIDE THE TUBING BUNDLE.
1/4" CO2 LINE TO PNEUMATIC GATE REGULATOR
(LOCATED BEHIND DISPENSER FRONT PANEL).
PRESSURE PRESET TO 30-35 MAX PSI.
3/8 LINES TO
DISPENSERS
3/8 LINES TO
ICEMAKER
1.
OVERALL FILTER DIMENSIONS:
25-1/2" WIDE x 9" DEEP x 32" HIGH
2.
SEE 2/ V2.0 AND THE SCOPE OF WORK FOR
SCOPE DEFINITIONS.
3.
ROUGH-INS SHALL BE PROVIDED BY THE
CONTRACTOR.
4.
INSTALLATION MUST COMPLY WITH ANY
STATE OR LOCAL PLUMBING CODES.
5.
THE FILTER MUST BE PROTECTED AGAINST
FREEZING.
6.
USE ONLY TEFLON (HIGH-LOW
TEMPERATURE) TAPE TO SEAL THREADED
PARTS; NO PIPE DOPE.
7.
DO NOT INSTALL WHERE LINE PRESSURE
EXCEEDS 125 PSI OR WHERE
TEMPERATURE EXCEEDS 100 F.
1/2 I.D.
LINE
WATER REGULATOR
- 60PSI
UNFILTERED
BOOSTER TANK
PRESSURE SWITCH/
RELIEF VALVE
DOUBLE CHECK VALVE
REGULATOR
WATER PRSSURE GAGE
60PSIG PRESSURE
SETTING
PUMP 100GPH
DRINK COUNTER
1/2" LINE
WATER FILTER
FILTERED
SURGE
TANK
DRINK COUNTER
SHUT-OFF
VALVE 3/8 BARB
FITTINGS ON
INLET AND
OUTLET
1/2 LINE
CO2
SECONDARY
REGULATOR
MT DEW
CODE RED
55-60 PSI
SIERRA MIST
PRE-SET
CO2
REGULATOR
PRE-SET
CO2
REGULATOR
REGULATOR
PEPSI
PEPSI
MOUNTAIN DEW
DISPENSER
DRAIN
DISPENSER
DRAIN
OPEN
OPTIONAL
DR. PEPPER
8.
CONTRACT DATE:
SEE THE EQUIPMENT PLAN FOR LOCATION.
SEE 8/ V2.0 FOR BUNDLE DETAILS
9.
"Y" FOR ICE MACHINES SUPPLY LINES
10. SHALL BE INSTALLED @ FILTER OUTLET.
CO2 SECONDARY
REGULATOR 90-100 PSI
BULK CO2 TANK
3 RECEPT.
115/60/1 20
AMPS EA.
3
11. BACKFLOW PREVENTERS FOR FILTER
ASSEMBLY ARE PROVIDED.
BACK ROOM
WAIT STATION
WITHIN 4" CHASE.
WITHIN 4" CHASE.
009.00.00
311465 / 434385
2015388.14
12. COORDINATE AND VERIFY ALL WORK WITH
VENDOR FOR DRINK SYSTEMS
123 Minden Shopping Dr.
Minden, LA 71055
STRAPPED OR SECURED
TO THE WALL
DIET PEPSI
LIPTON BRISK
DBR 37
SWITCH-OVER VALVE
TYPICAL SYRUP LINE (ONLY 1
SHOWN FOR CLARITY)
FLOOR SINK
PLAN VERSION:
PIZZA HUT
NOTE INSTALL ELECTRICAL, WATER, AND DRAIN IN
ACCORDANCE WITH ALL LOCAL, STATE & FEDERAL
CODES.
EQUIPMENT RATING:
ED300 DISPENSER - 115V, 5.2 AMPS
ED250 DISPENSER - 115V, 3.5 AMPS
CARBONATOR - 115V, 60 Hz, 7.0 AMPS
BOOSTER ASSEMBLY - 115V. 60 Hz, 6.5 AMPS
PEPSI
PLATFORM
LEGEND
Nxxx
FLOW ARROW
KITCHEN EQPT NO. (SHT
A2.1)
PPS005
BAR
DISPENSER DRAIN
DBR 37
STORE NUMBER:
FINISHED FLOOR
FLOOR SINK
BUILDING TYPE:
SITE NUMBER:
CARBONATOR
DISPENSER DRAIN
09.21.15
POINT OF CONNECTION (PEPSI)
SYSTEM
POINT OF CONNECTION (GC)
DRINK SYSTEM SCHEMATIC
N.T.S.
2
WATER FILTRATION SCHEMATIC
N.T.S.
4
P7.0
PLOT DATE:
N
O
I
T
C
Y
U
L
R
N
T
O
S
S
N
E
O
S
C
O
D
P
R
R
A
U
N
P
I
U
D
I
O
B
H
C OR
F
520 South Main Street, Suite 2531
Akron, OH 44311
330.572.2100 Fax: 330.572.2102
R8
D
EF
2
B-21
WP
GFI
B-37
P12 WH
R2
1
B-21
A-27
WP
GFI
SD CO
V
F
P17
P18
SYMBOL LIST
P11
POWER PLAN
NOT USED.
P11
J-BOX FOR SIGNAGE. COORDINATE LOCATION WITH SIGNAGE VENDOR. SEE SCOPE OF WORK.
P2
NOT USED.
P12
PROVIDE A 20-AMP, 1-POLE DISCONNECT SWITCH AND 120V ,1P/20 AMP CIRCUIT TO INSTANTANEOUS WATER HEATER
CONTROLS. VERIFY POINT OF CONNECTION.
P3
PROVIDE 20A., 120V., DUPLEX ISOLATED GROUND RECEPTACLE FOR DEMARK TELEPHONE TERMINAL BOARD.
P13
INSTALL CONTROL CABLE FROM FREEZER/COOLER FAN COIL TO ROOF MOUNTED CONDENSER.
P4
NOT USED.
P14
P5
DISHWASHER - 60A., 3P., 240V., MANUAL MOTOR STARTER SWITCH WITH STAINLESS STEEL LOCKOUT AND
TAGOUT COVER PLATE.
PROOFER - 20A., 2P., 240V., CEILING MOUNTED L6-20R TWIST LOCK RECEPTACLE AND STAINLESS STEEL
COVER PLATE.
OVENS - 20A., 1P., 120V., MANUAL MOTOR STARTING SWITCH WITHOUT OVERLOADS WITH STAINLESS STEEL
LOCKOUT AND TAG OUT COVER PLATE. PROVIDE FLEX CONNECTION FROM MANUAL MOTOR STARTERS TO
OVEN DECKS (TYP.). REFER TO ARCHITECTURAL DETAIL IF OVENS ARE PROVIDED WITH FACTORY CORD AND
PLUG SETS, PROVIDE PLUG WITH MATCHING CONFIGURATION.
P18
P7
J
G
P1
P6
J
P8
NOT USED.
P9
DEDICATED CIRCUIT FOR SECURITY SYSTEM POWER. PROVIDE LOCK-ON CLIP AT CIRCUIT BREAKER.
P10
ALL EXTERIOR LIGHTING AND SIGNAGE SHALL BE CIRCUITED THROUGH EXTERIOR LIGHTING
CONTACTOR/PHOTOCELL CONTROL PANEL. SEE DETAIL 8 ON SHEET E6.0 FOR ADDITIONAL INFORMATION.
A
SPECIFIED TRANE RTU IS SUPPLIED WITH THRU THE BASE ELECTRICAL CONNECTIONS
AND FACTORY INSTALLED HACR CIRCUIT BREAKER WITH WEATHER TIGHT
ENCLOSURES AND ACCESS THRU SWINGING DOOR.
CONTRACT DATE:
R2
POWER AND CONTROL ENTRY FROM BOTTOM OF UNIT.
BUILDING TYPE:
DBR 37
NOT USED.
R3
CONNECT TO CONTACTOR LC. SEE LIGHTING CONTROL RELAY REAR. SHEET E6.0.
PLAN VERSION:
009.00.00
P15
NOT USED.
R4
1/2" C, WITH REQ'D CONDUCTORS TO J-BOX IN CEILING ABOVE ICE MACHINE. MAKE
CONNECTION TO ICE MACHINE AND CONDENSING UNIT ON ROOF.
SITE NUMBER:
P16
NOT USED.
R5
COOLER / FREEZER CONDENSING UNIT ON ROOF. SEE ARCH.
P17
POWER SUPPLY BOX FOR CANOPY LIGHTING. VERIFY WITH CANOPY MANUFACTURER
FOR EXACT REQUIREMENTS. SEE SCOPE OF WORK.
J-BOX FOR CANOPY LIGHTING. MOUNT INSIDE OF CANOPY. VERIFY EXACT
LOCATION IN FIELD.
P19
R6
R7
NOT USED
C
R9
A. NO CONDUIT SHALL BE FASTENED DIRECTLY TO OR THROUGH
ROOFING MEMBRANE.
B. ALL CUTS IN ROOFING MEMBRANE SHALL BE MINIMAL AND IN
ACCORDANCE WITH ROOFING MFR'S AND INSTALLER'S REQ'S.
E
K. PER SECTION 210.8(B)(3) NEC 2011, ALL 15 AND 20A, 120V RECEPTACLES IN COMMERCIAL KITCHENS
REQUIRED TO BE GFCI PROTECTED AND READILY ACCESSIBLE, IF DEVICE IS NOT READILY ACCESSIBLE A
GFCI PROTECTED BREAKER OR DEADFRONT DEVICE SHALL BE PROVIDED.
L. ALL CONNECTIONS AND ELECTRICAL EQUIPMENT LISTED IN SCHEDULE SHALL BE PROVIDED AND INSTALLED
BY THE ELECTRICAL CONTRACTOR. FIELD VERIFY CONNECTION REQUIREMENTS AND EQUIPMENT PROVIDED
BY OTHERS PRIOR TO ROUGH-IN.
M. REFER TO MECHANICAL DRAWINGS AND SPECIFICATIONS FOR THE REQUIREMENTS ASSOCIATED WITH
WIRING AND CONNECTIONS OF INTERLOCKING, THERMOSTAT LOCATIONS, EXHAUST FAN CONTROL
SWITCHES, AND OTHER CONTROLS OF MECHANICAL EQUIPMENT.
N. PROVIDE DUCT MOUNTED SMOKE DETECTORS IN THE SUPPLY DUCT. VERIFY THE REQUIRED QUANTITY OF
DUCT SMOKE DETECTORS FOR EACH UNIT WITH DUCTWORK LAYOUT TO MEET NFPA REQUIREMENTS.
R8
MOUNT PHOTOCELL ON NORTH SIDE OF RTU-1. CONNECT TO EXTERIOR LIGHTING
311465 / 434385
2015388.14
PIZZA HUT
RTU'S SHALL BE PROVIDED WITH BUILT-IN FUSED DISCONNECT, SINGLE POINT WIRING AND
CONVENIENCE OUTLET. OUTLET TO BE WIRED SEPARATE FROM RTU. CIRCUIT AS SHOWN.
EXHAUST FANS SHALL BE PROVIDED WITH A WEATHERPROOF DISCONNECT SWITCH,
SINGLE POINT WIRING.
123 Minden Shopping Dr.
Minden, LA 71055
PROVIDE CONNECTION FROM RETURN AIR DUCT SMOKE DETECTORS TO MECHANICAL
CONTROL CIRCUIT PER DETAIL 2/E6.0, AND FIRE ALARM SYSTEM (IF PRESENT).
PROVIDE A RELAY TO SHUT DOWN HVAC EQUIPMENT UPON ACTIVATION OF DUCT
DETECTOR OR FIRE ALARM SYSTEM (IF PRESENT).
C. REFER TO MECH DWGS FOR MECHANICAL EQUIPMENT ELECTRICAL
REQ'S.
DBR 37
D. ALL EXPOSED ELECTRICAL CONDUITS SHALL PENETRATE ROOF
E. MEMBRANE AT PIPE HOODS U.O.N.
F. REFER TO ELECT EQUIP SCHEDULE AND ELECT ROUGH-IN PLAN.
G. ALL CONDUITS FROM EXHAUST FANS SHALL BE ROUTED INSIDE OF
CURB.
POWER/
ROOF PLAN
H. ALL CONDUITS TO AND FROM RTU SHALL BE ROUTED INSIDE OF RTU
CURB. COORDINATE WITH RTU MFR RECOMMENDATIONS.
I. REFER TO GENERAL NOTES SHEET E1.0 FOR IMPORTANT
INFORMATION.
E2.0
J. ALL WIRING AND CONDUITS SHALL BE CONCEALED. NO CONDUITS
PERMITTED TO RUN EXPOSED ACROSS ROOF DECK. ROUTE ALL CONDUITS
THROUGH EQUIPMENT ROOF CURBS OR SRHCITECT SPECIFIED ROOF
PENETRATIONS.
POWER PLAN GENERAL NOTES
09.21.15
STORE NUMBER:
CONTROL PANEL.
LIGHTING CONTROL PANEL SHALL BE PROVIDED BY OWNER, AND INSTALLED BY ELECTRICAL CONTRACTOR. CONTROL
PANEL SHALL BE RECESSED DIRECTLY BELOW ELECTRICAL PANEL "C". COORDINATE WITH OWNER PRIOR TO ANY
ROUGH-IN WORK. SEE DETAIL 8 ON SHEET E6.0 FOR ADDITIONAL CONTROL PANEL INFORMATION.
POWER KEY NOTES
A. ALL RECEPTACLES SHALL BE INSTALLED 18" AFF UNLESS NOTED OTHERWISE.
B. ALL CONDUIT DROPS ARE INSIDE WALLS U.O.N. SEE ARCH DWGS FOR WALL DIMS.
C. ALL J-BOX CIRCUITS, CONDUITS, FIXTURES, ETC SHALL BE AS INDICATED ON THE ELECT DWGS AND SPECS.
D. CONTRACTOR TO VERIFY UNDERGROUND CONDUIT LOCATIONS PRIOR TO POURING SLAB.
E. IT IS THE RESPONSIBILITY OF THE CONTRACTOR TO COORDINATE THIS DATA ON THE LOCATION OF ELECT
ROUGH-INS WITH INFO PROVIDED ON THE ARCH AND STRUCT DWGS AND THE EQUIPMENT ACTUALLY
SUPPLIED, AND TO CONFIRM THE CORRECTNESS OF ANY DIMENSIONS HEREIN.
F. LOCATIONS OF ALL OUTLETS MAY BE RELOCATED TO NEAREST STUD. DO NOT CUT INTO STUDS.
G. FOR EXACT LOCATIONS OF KITCHEN & MECHANICAL EQUIPMENT AND POINTS OF CONNECTION, REFER TO
KITCHEN & MECHANICAL EQUIPMENT DRAWINGS AND MANUFACTURER'S SHOP DRAWINGS.
H. ALL CIRCUIT FEEDERS AND DISCONNECTS SHALL BE SIZED BY NEC.
I. CONTRACTOR SHALL VERIFY CIRCUIT BREAKER, DISCONNECT SWITCH, STARTER AND FUSE SIZES WITH
SELECTED EQUIPMENT MANUFACTURER'S SHOP DRAWINGS PRIOR TO PLACING ORDER AND PROVIDE
EVERYTHING AS REQUIRED.
J. ELECTRICAL EQUIPMENT ENCLOSURES SHALL BE NEMA-1 FOR INTERIOR AND NEMA 3R FOR EXTERIOR. IN
COASTAL REGIONS THE STANDARD FOR OUTSIDE SHALL BE NEMA-4X.
R1
1/4"=1'-0"
F
POWER ROOF PLAN NOTES
D
POWER ROOF PLAN KEY NOTES
B
PLOT DATE:
N
O
I
T
C
Y
U
L
R
N
T
O
S
S
N
E
O
S
C
O
D
P
R
R
A
U
N
P
I
U
D
I
O
B
H
C OR
F
520 South Main Street, Suite 2531
Akron, OH 44311
330.572.2100 Fax: 330.572.2102
2
G
B-22
PANEL "A"
G
B-22
G
B-22
GE
B-22
8
G
B-22
G
B-22
G
B-22
G
B-22
G
B-22
PANEL "B"
G
B-22
RH
K
7
B-25
B-17
8
G
B-22
10
B-20
8
GE
B-22
#1
#2
A-14
5
G
B-22
A-14
4
E
B-33
E
B-33
E
B-33
E
B-33
E
B-33
E
B-33
E
B-33
E
B-33
E
B-33
E
B-33
12
B-27
11
E
B-20
6
E
B-33
E
B-20
E
B-20
EM
LB
LB
LB
LB
3
LB
LB
LB
LB
LB
LB
LB
LB
B-9
E
B-20
EM
B-25
E
B-33
9
3
6
1
E
B-20
K
12
B-27
8
LB
E
B-33
EM
11
A
B-29
K
A
B-29
A
B-29
A
B-29
A
B-29
A
B-29
RH
LB
B-25
LB
B-25
RH
B-39
9
B-9
9
LIGHTING PLAN
NO.
A
QUANTITY
7
E
26
EM
5
K
2
LB
33
LOCATION
MANUFACTURER / CATALOG NUMBER
DINING
ACCUSERV/ BES00298-105
DINING
ACCUSERV/ 0039-017/ CT6FB/ RC6-GU24
DINING
KITCHEN
KITCHEN
DINING
DINING
LITHONIA / ELM4
DESCRIPTION
CORD HUNG PENDANT
ELECTRONIC
RECESSED COMPACT
FLUORESCENT DOWNLIGHT
EMERGENCY LIGHT
LITHONIA/ LQM SW3 R 120/277 ELN
LED EXIT
LIGHTOLIER/ LT-J-08-RWF-827-BK
MINI CYLINDER
TRACK HEAD
LAMP
#
1
1
2
-
1
TYPE
MOUNTING
GU24 LED
PENDANT
-
RECESSED
N1212 HEADS
W/ FIXT.
SUPPLIED
W/ FIXTURE
LED
WALL
CEILING
TRACK MT.
VOLT WATT
120
10
120
120
25
120
3
120
9
2
DINING
JUNO/ T4BL
4' BLACK TRACK SECTION
REFER TO LIGHT FIXTURE SCHEDULE NOTE #3.
LB8
7
DINING
JUNO/ T8BL
8' BLACK TRACK SECTION
REFER TO LIGHT FIXTURE SCHEDULE NOTE #3.
EXTERIOR
ACCUSERV #B9354NB
DECORATIVE
WALL SCONCE
WALL SCONCE
1-LIGHT DOWN
REMOTE HEAD
W1
2
W2
5
RH
3
EXTERIOR
ACCUSERV #7037-42
EXTERIOR
LITHONIA # ELA-T-NX-NO806
1
1
1
WALL
8W INC.
WALL
WALL
120
1.
RED SHADE
NOTE #13
LB4
L1372
HALOGEN
42 WATT CF
REMARKS
18
120
46
120
16
EMERGENCY FIXTURE WITH
EMERGENCY BATTERY
EXIT FIXTURE W/ BATTERY
SEE NOTE #2
PROVIDE TRACK AS LISTED
BELOW
LIGHT FIXTURES SHALL BE PROVIDED WITH ELECTRONIC BALLASTS. COMPACT
FLUORESCENT ELECTRONIC BALLASTS SHALL HAVE END-OF-LIFE PROTECTION CIRCUIT TO
PREVENT WELDING OF LAMPS IN SOCKETS OR LAMP BREAKAGE. SEE SPECIFICATIONS.
2.
PROVIDE ARROWS AND FACES AS INDICATED ON THE DRAWINGS.
3.
PROVIDE TRACK, END FEEDS, AND COUPLING DEVICES IN QUANTITIES AS REQUIRED TO
FORM THE TRACK LENGTHS SHOWN. REFER TO THE PLANS FOR LOCATIONS OF TRACK.
REFER TO ARCHITECTURAL REFLECTED CEILING PLANS AND ELEVATIONS FOR EXACT
LOCATIONS FOR LIGHTING FIXTURES.
4.
ELECTRICAL CONTRACTOR SHALL VERIFY ALL FIXTURE LOCATIONS WITH ARCHITECTURAL
ELEVATIONS.
5.
ELECTRICAL CONTRACTOR SHALL INSTALL ALL CEILING MOUNTED LIGHTING FIXTURES IN
LOCATIONS AS INDICATED ON THE ARCHITECTURAL REFLECTED CEILING PLAN.
6.
ALL PENDANT FIXTURES ARE PROVIDED WITH FACTORY INSTALLED 12' CORD AND STRAIN
RELIEF FITTINGS. CONNECTION AND CUTTING OF CORD FOR PENDANT FIXTURE MOUNTING
SHALL BE ONLY AT UPPER CANOPY.
7.
LIGHTING FIXTURE CONTACT: ACCUSERV EQUIPMENT & SUPPLY
3865 PRODUCE RD., SUITE #208, LOUISVILLE, KY 40218,
PHONE: 877-707-7378, FAX: 502-961-0357.
SURFACE MOUNT FIXTURE
SURFACE MOUNT FIXTURE
8.
FIELD PAINT PENDANT TRACK ADAPTER BLACK. MOUNT FIXTURES AT 58" A.F.F. TO BOTTOM.
9.
CONFIRM LIGHTING FIXTURE QUANTITIES WITH SUPPLIER.
10. ALL CONDUITS ENTERING OR LEAVING COOLER SHALL BE PROVIDED WITH EYS SEAL-OFF
FITTING WITH COMPOUND PER NEC 300-(7a).
11. CONTRACTOR TO FIELD VERIFY CEILING TYPE AND PROVIDE PROPER MOUNTING
HARDWARD.
1/4"=1'-0"
A
1
JUNCTION BOX AND ASSOCIATED 120V ,1P/20 AMP CIRCUIT MOUNTED BELOW ROOF DECK FOR CONNECTION
TO EF-3 ON ROOF. REFER TO SHEET E2.0.
2
EXHAUST HOOD LIGHTS PROVIDED WITH HOOD AND INSTALLED BY E.C.
3
PROVIDE 120V ,1P/20 AMP WALL SWITCH FOR LOCAL LIGHT CONTROL. MOUNT AT 48" AFF.
4
PROVIDE 120V ,1P/20 AMP WALL SWITCH AT 48" AFF FOR CONTROL OF FRONT OF HOUSE LIGHTING.
CONTRACTOR SHALL PROVIDE ENGRAVED LABEL AT EACH SWITCH IDENTIFYING USE. SEE DETAIL 18 ON SHEET
E6.0 FOR ADDITIONAL INFORMATION.
BUILDING TYPE:
DBR 37
PLAN VERSION:
009.00.00
5
PROVIDE 120V ,1P/20 AMP WALL SWITCH AT 48" AFF FOR REAR LIGHTING CONTACTOR CONTROL PANEL. SEE
DETAIL 14 ON SHEET E6.0 FOR ADDITIONAL INFORMATION.
SITE NUMBER:
6
LIGHTING FIXTURES AND SWITCHES FOR COOLER/FREEZER ARE PROVIDED WITH COOLER/FREEZER. FIXTURES
AND SWITCHES ARE TO BE INSTALLED BY ELECTRICAL CONTRACTOR PER MANUFACTURER'S REQUIREMENTS
AND N.E.C. ARTICLE 300-7. CONTRACTOR TO PROVIDE LAMPS FOR COOLER AND FREEZER FIXTURES.
CONTRACT DATE:
7
PROVIDE JUNCTION BOX AND ASSOCIATED 120V ,1P/20 AMP CIRCUIT MOUNTED ABOVE CEILING FOR
CONNECTION TO LIGHTING FIXTURES IN WALK IN COOLER AND FREEZER. ROUTE CIRCUIT TO PANEL
INDICATED VIA LIGHTING CONTACTOR, SEE DETAIL 14/E6.
8
EMERGENCY (BATTERY PACK), EXIT LIGHTING FIXTURES AND NIGHT LIGHT FIXTURES (SHOWN HATCHED) TO
BE CIRCUITED ON UNSWITCHED LEG OF CIRCUIT INDICATED. PROVIDE WITH LOCK-ON BREAKER.
9
ALL EXTERIOR LIGHTING AND SIGNAGE SHALL BE CIRCUITED THROUGH EXTERIOR LIGHTING
CONTACTOR/PHOTOCELL CONTROL PANEL. SEE DETAIL 8 ON SHEET E6.0 FOR ADDITIONAL INFORMATION.
10
PROVIDE JUNCTION BOX AND ASSOCIATED 120V ,1P/20 AMP CIRCUIT MOUNTED ABOVE CEILING FOR
CONNECTION TO WALK IN COOLER , FREEZER HEAT-TRACE AND DEFROST. PROVIDE SEALED FITTINGS INSIDE
COOLER/FREEZER.
11
RESTROOM (DUAL-SENSOR) OCCUPANCY SENSOR AND POWER SUPPLY. E.C. TO PROVIDE JUNCTION BOX
ABOVE CEILING FOR POWER SUPPLY (MOUNT IN AN ACCESIBLE LOCATION). PROVIDE "DOME" STYLE SENSOR
SURFACE MOUNTED ON THE CEILING FOR THE BEST POSSIBLE COVERAGE AREA. CIRCUIT SHOWN, AHEAD OF
LOCAL SWITCHING.
12
PROVIDE 1 AMP CURRENT LIMITER PER MANUFACTURER SPECIFICATION.
09.21.15
311465 / 434385
STORE NUMBER:
2015388.14
PIZZA HUT
123 Minden Shopping Dr.
Minden, LA 71055
DBR 37
12. ALL INTERIOR LIGHITNG CIRCUITS TO BE WIRED THRU THE LIGHTING CONTROL RELAYS. SEE
DETAILS 14 & 18/E6.0.
LIGHTING PLAN
& SCHEDULE
13. SEE ARCHITECTURAL REFLECTED CEILING PLAN FOR FINISH OF TRIM RING.
E3.0
LIGHTING FIXTURE SCHEDULE
D
LIGHTING GENERAL NOTES
C
LIGHTING KEY NOTES
B
PLOT DATE:
N
O
I
T
C
Y
U
L
R
N
T
O
S
S
N
E
O
S
C
O
D
P
R
R
A
U
N
P
I
U
D
I
O
B
H
C OR
F
520 South Main Street, Suite 2531
Akron, OH 44311
330.572.2100 Fax: 330.572.2102
1
6
7
2
3
5
52"
11
96"
84"
48"
5
60"
60"
48"
60"
5
S6
AS
PANEL "A"
4
PANEL "B"
5
S6
S3
90"
90"
90"
88"
96"
96"
96"
FS KP
S5
90"
S
S
S
S
S3
S3
CONTRACT DATE:
09.21.15
BUILDING TYPE:
DBR 37
PLAN VERSION:
009.00.00
SITE NUMBER:
311465 / 434385
STORE NUMBER:
TELCOM PLAN
A.
HOLD-UP BUTTON (MOUNT 2-1/2"
BEHIND COUNTER EDGE)
DOOR CONTACTOR (LINKED TO
AUDIO / VISUAL ALARM)
S
MUSIC SYSTEM SPEAKERS
"SOUND ALERT" DEVICE (CLG.)
S
OUTSIDE SPEAKER
SECURITY STROBE
J
KP
KEYPAD (MTD AT 48" A.F.F.)
AS
ALARM SIREN ABOVE CLG
SUPPLY AND INSTALL OUTLETS AND CONDUIT FOR OWNER SUPPLIED AND INSTALLED
CABLE AND LOW VOLTAGE WIRING (U.O.N.) TELEPHONE AND MUSIC SYSTEM WIRING
SHALL BE SUPPLIED AND INSTALLED BY G.C. SEE SCOPE OF WORK SHEETS.
B.
SEE SHEET E2.0 FOR ELECT INFO ON POS, SECURITY SYSTEM, CCTV SYSTEM, (OFFICE)
COMPUTER, DRIVE-THRU TIMER AND DRIVE-THRU COMMUNICATION SYSTEM.
C.
THIS PLAN INCLUDES CONDUITS AND J-BOXES FOR POS, SECURITY SYSTEM, CCTV
SYSTEM, (OFFICE) COMPUTER, TELEPHONE SYSTEM, MUSIC SYSTEM, DRIVE-THRU TIMER
AND DRIVE-THRU COMMUNICATION SYSTEM.
CCTV OUTLET AT CLG U.O.N.
J-BOX
2" x 4" J-BOX W/ 2 DATA PORTS
B
BUMP PAD (MOUNT AT FRONT
COUNTER)
FS
HOOD FIRE SUPPRESSION SYSTEM
PULL STATION
MOTION DETECTOR (MTD AT 72" A.F.F.)
DOOR CONTACTOR
2x4 J-BOX FLUSH MOUNTED @ 76" A.F.F CENTERED OVER DOOR IN WALK-IN
WALL BY COOLER MANUFACTURER WITH 1/2" CONDUIT TO OUTSIDE OF
COOLER NEAR KITCHEN CEILING. SECURITY SYSTEM INSTALLER TO INSTALL
HOLD-UP BUTTON FACING DOWN AND RUN WIRING.
A
PIZZA HUT
PROVIDE (1) 2" CONDUIT WITH PULL STRING FROM TELEPHONE TERMINAL BOARD
123 Minden Shopping Dr.
Minden, LA 71055
TURNS. VERIFY SITE AND TELEPHONE COMPANY REQUIREMENTS PRIOR TO BIDDING
PROVIDE (1) 2" CONDUIT WITH PULL STRING STUBBED UP ABOVE TO ACCESSIBLE
CEILING FROM J-BOX AT COMPUTER WALL CABINET FOR DATA CABLES. PROVIDE
HOLD UP BUTTON LOCATION (MOUNT 2 1/2" BEHIND COUNTER EDGE). VERIFY
EXACT LOCATION AND REQUIREMENTS WITH SECURITY PROVIDER.
DOOR CONTACT MOUNTED AT TOP OF JAMB. VERIFY EXACT LOCATION AND
REQUIREMENTS WITH SECURITY PROVIDER.
PROVIDE (1) 3/4" CONDUIT WITH PULL STRING STUBBED UP ABOVE
ACCESSIBLE CEILING FROM J-BOX WITH VOICE/DATA OUTLET.
HOLD UP BUTTON BY MANAGER DESK. VERIFY EXACT LOCATION AND
REQUIREMENTS WITH SECURITY PROVIDER.
D. PROVIDE (1) ONE (25) TWENTY-FIVE PAIR TELEPHONE CABLE, ONLY (3) THREE LINES
SHALL BE ACTIVATED :
LINE ONE FOR VOICE / FAX
LINE TWO FOR SECURITY
LINE THREE FOR COMPUTER
1/4"=1'-0"
2015388.14
4" X 4" J-BOX MTD. AT 48" AFF FOR SECURITY SYSTEM KEYPAD. PROVIDE (1) 3/4" C. &
(1) 1/2" C. TO 4" X 4" J-B0X MTD. ABOVE CEILING. VERIFY EXACT LOCATION AND
REQUIREMENTS WITH SECURITY PROVIDER.
TELEPHONE SERVICE PER LOCAL TELEPHONE COMPANY. PROVIDE 2" C.
WITH PULL WIRE TO POINT OF TELEPHONE COMPANY CONNECTION. VERIFY
ALL REQUIREMENTS WITH LOCAL TELEPHONE COMPANY.
ALARM SIREN ABOVE CEILING. CONNECT TO SECURITY SYSTEM. VERIFY EXACT LOCATION
AND REQUIREMENTS WITH SECURITY PROVIDER.
PROVIDE (1) 3/4" CONDUIT WITH PULL STRING STUBBED UP ABOVE
ACCESSIBLE CEILING FROM J-BOX WITH DATA OUTLET.
WALL MTD. MOTION DETECTOR AT 90" AFF. TO COVER CASH REGISTER AND SAFE. VERIFY
EXACT LOCATION AND REQUIREMENTS WITH SECURITY PROVIDER.
TELEPHONE TERMINAL BOARD.
SECURITY CAMERA MOUNTED AS DIRECTED BY SECURITY PROVIDER. MOUNT SO
THAT CAMERA COVERS CASH REGISTER AREA. VERIFY EXACT LOCATION AND
REQUIREMENTS WITH SECURITY CAMERA PROVIDER.
E.C. TO PROVIDE 1" CONDUIT (RIGID) THRU - ROOF FOR SATELLITE SYSTEM.
PENETRATION SHALL BE SEALED WATER TIGHT. COORDINATE WITH SATELLITE
INSTALLER.
DBR 37
TELCOM PLAN
E4.0
COMMUNICATIONS LEGEND
D
COMMUNICATIONS NOTES
D
SECURITY SYSTEM NOTES
C
KEY NOTES
B
PLOT DATE:
*CONTRACTOR SHALL VERIFY ALL EQUIPMENT
LOADS, VOLTAGE, AMPS, DISCONNECT, AND/OR
PLUG REQUIREMENTS WITH OWNERS EQUIPMENT
BEFORE START OF WORK.
N
O
I
T
C
Y
U
L
R
N
T
O
S
S
N
E
O
S
C
O
D
P
R
R
A
U
N
P
I
U
D
I
O
B
H
C OR
F
520 South Main Street, Suite 2531
Akron, OH 44311
330.572.2100 Fax: 330.572.2102
KITCHEN EQUIPMENT PANEL
A
GENERAL NOTE:
*CONTRACTOR SHALL VERIFY ALL EQUIPMENT
LOADS, VOLTAGE, AMPS, DISCONNECT, AND/OR
PLUG REQUIREMENTS WITH OWNERS EQUIPMENT
BEFORE START OF WORK.
LIGHTING CIRCUITS INSIDE THE BUILDING SHALL BE WIRED THRU
LIGHTING CONTACTORS. REFER TO DETAILS ON SHEET E6.0.
PANELBOARD NOTES:
1
PROVIDE LOCK-ON BREAKER.
2
CIRCUITS TO BE WIRED THRU EXTERIOR LIGHTING CONTROL RELAY. SEE
DETAIL 8/E6.0.
3
CIRCUITS TO BE WIRED THRU THE LIGHTING CONTROL RELAY-FRONT.
SEE DETAIL 18/E6.0.
4
CIRCUITS TO BE WIRED THRU THE LIGHTING CONTROL RELAY-REAR. SEE
DETAIL 14/E6.0.
5
6
LOAD KEY LEGEND
LOAD
DESCRIPTION
CIRCUIT BREAKER INDICATED SHALL BE A SHUNT TRIP CIRCUIT BREAKER
CONTROLLED BY HOOD'S FIRE EXTINGUISHER SYSTEM.
WESTERN REGION PANELS WILL HAVE A STANDARD 42KAIC RATING.
WHEN GE PANELS ARE USED IN THE WESTERN REGION PANELS WILL HAVE
A 65 KAIC RATING. EASTERN REGION PANELS WILL HAVE A 22KAIC
RATING.
APPLICABLE
FACTOR
L
LIGHTING
125%
K
KITCHEN EQUIPMENT
65%
H
HVAC
100%
M
MISC. EQUIPMENT
100%
LOAD SUMMARY & LEGEND
CONDUCTORS
DESIG.
SETS
NO.
SIZE
GROUND ISOLATED CONDUIT
SIZE
GROUND
SIZE
PER SET
SIZE
PER SET
1
1
4
#500 KCM 16
#3
#6
3-1/2"
2
1
4
#3/0
#6
#6
2"
C
E.C. SHALL COORDINATE WITH POWER COMPANY
TO REMOVE EXISTING 120/208V 200A METER. E.C.
SHALL REMOVE EXISTING 200A DISC. ALONG WITH
ASSOCIATED FEEDER & CONDUIT BACK TO TENANT
SPACE.
E.C. SHALL REMOVE
EXISTING PANEL (S) AND
REPLACE WITH NEW
PANELS.
KITCHEN EQUIPMENT PANEL
NOTES:
1. PROVIDE OTHER GROUND CONNECTIONS AS
SPECIFIED IN N.E.C. ARTICLE 250-50. (1999)
2. LIGHTING CONTROL PANEL SHALL BE RECESSED
DIRECTLY BELOW ELECTRICAL PANEL "B".
3. COORDINATE W/ POWER CO., PROVIDE C.T.
CABINET IF REQUIRED .
4. PROVIDE NEW SERVICE GROUNDS IF NO
EXISTING SERVICE GROUND. VERIFY IN FIELD.
B
CONTRACT DATE:
09.21.15
BUILDING TYPE:
DBR 37
PLAN VERSION:
009.00.00
SITE NUMBER:
311465 / 434385
STORE NUMBER:
2015388.14
PIZZA HUT
NEW UTILITY CO. METERING
SEE NOTE #3 BELOW
123 Minden Shopping Dr.
Minden, LA 71055
EXISTING WIREWAY
A
EXISTING
1200A.,
120/208V., 3PH.,
4 WIRE,
SERVICE
DISCONNECT
SWITCH
NEW 400A., 120/208V.,
3PH., 4 WIRE, FUSED,
DISCONNECT SWITCH,
SERVICE ENTRANCE
RATED, NEMA 3R
EXISTING
1200A.,
FEEDERS FROM
UTILITY
TRANSFORMER
1-#1/0 - 1" CONDUIT TO WATER SERVICE WHERE
SERVICE ENTERS BUILDING. (NOTE 2)
EXISTING TENANT'S METERS
AND DISCONNECTS
(TYPICAL)
B
DBR 37
LTG
CNTL
RELAY
(NOTE 2)
PANEL
SCHEDULE &
RISER DIAGRAM
EXISTING SERVICE GROUND,
SEE NOTE 4.
1-#1/0 -3 4" CONDUIT TO 3 4" DIAMETER X 10'-0" LONG
COPPERCLAD GROUND ROD W/ 'CADWELD'
CONNECTION. (NOTE 2)
E5.0
SINGLE LINE DIAGRAM
D
PLOT DATE:
RTU TERMINAL STRIP
(RTRM)
SEQUENCE OF OPERATION:
AFTER COMPLETION AND TESTING OF THE INTERLOCK
SYSTEM SHOWN BELOW, BUT BEFORE PUTTING IT INTO
OPERATION, PROGRAM THERMOSTATS FOR RTU1 AND
RRU2 TO INITIATE "OCCUPIED" TEMPERATURE SETTINGS
AT TIME OF ARRIVAL OF FIRST EMPLOYEE OR MANAGER.
(APPROXIMATELY 8:00 A.M.)
THIS INTERLOCK SYSTEM IS INTENDED TO:
1. MAKE AVAILABLE A FULL VOLUME OF OUTSIDE AIR TO THE
BUILDING WHEN ALL EXHAUST FANS ARE ACTIVATED BY THE
"OCCUPIED" RELAY
JUMPER
SMOKE DETECTORS
LOCATED IN SUPPLY AIR
DUCTS. INCLUDE IN
RETURN DUCTS ONLY
WHERE REQUIRED BY
LOCAL CODE. WIRE TO
SHUTDOWN AC UNITS
UPON DETECTION OF
SMOKE.
N
O
I
T
C
Y
U
L
R
N
T
O
S
S
N
E
O
S
C
O
D
P
R
R
A
U
N
P
I
U
D
I
O
B
H
C OR
F
2. STOP THE FLOW OF OUTSIDE AIR FROM THE RTUs BY
DE-ENERGIZING UNITS WHEN ANY HOOD FIRE SUPPRESSION
SYSTEM IS ACTIVATED.
CONTACT LC-7 SHALL ENABLE THE EXHAUST FAN CONTROL RELAY
"R3" TO SENSE THE "OCCUPIED" (OR "UNOCCUPIED" CONDITION.
(REFER TO DET. 2, SHT E6_0 FOR SEQUENCE OF OPER.)
NOTES:
1. REFER TO THE ELECTRICAL ROOF PLAN, E2.0 FOR
UNIT LOCATIONS
2. REFER TO THE MECHANICAL SCHEDULES ON SHEET
M1 FOR ELECTRICAL REQUIREMENTS
SEQUENCE OF OPERATION:
CONTACT LC-8 SHALL ENABLE THE LIGHTING CONTROL RELAY-EXT TO
BEGIN THE "OCCUPIED" SEQUENCES PROGRAMMED INTO IT (REFER
TO DET 8, SHT E6_0).
OCCUPIED:
UNOCCUPIED:
KITCHEN EXHAUST FANS SHALL CEASE
OPERATE OPERATION WHEN RELAY "R3" IS DE-ENERGIZED
CORRESPONDING TO TURNING OFF THE LIGHT SWITCH IN
THE KITCHEN. SPACE THERMOSTATS SHALL CYCLE
ROOFTOPS' FANS AND HEATING OR COOLING TO MAINTAIN
"UNOCCUPIED" SPACE TEMPERATURES.
A-15
B-20
B-22
UNDER SLAB CONDUIT
N.T.S.
17
"LC"
C
LC- 1
2
3
4
5
6
7
EQUIPMENT
CONTROL
8
R4
120V
PANEL "A"
CKT. 14
CIRCUIT BREAKER
B-42
B-41
B-33
B-29
B-27
FROM ELECTRICAL PANELS
C
R4- 1
(SEE 16/E6.0)
RECESSED DOWNLIGHTS
TELEVISIONS
6
7
8
FREEZER/COOLER LIGHTS
DINING PEND/DOWN LTS
5
SPARE
4
SPARE
3
SPARE
2
TELEVISIONS
FC- 1
DINING TRACK LTS
C
WOMEN RESTROOM
MEN RESTROOM
KITCHEN LIGHTS
"FC"
HOOD EXHAUST FAN
CONTROL
C
N.T.S.
18
SPST SWITCH #2.
SEE E4.0 FOR
LOC'N. KEYNOTE
TO
TO
RTU-1 RTU-2
SPARE SPARE T-STAT T-STAT
ELECTRICALLY HELD, 4-POLE
120 VOLT AC 20 AMP
CONTINUOUS DUTY LIGHTING
CONTACTOR.
SPARE
SHUNT-TRIP
ELECTRICALLY HELD, 120 VOLT
AC 20 AMP CONTINUOUS DUTY
LIGHTING CONTACTOR.
7
FRYER
HOOD
LIGHTS
8
SPARE SPARE
BC- 4
3
2
REFER TO
NOTES
ABOVE
N.T.S.
1
NEUT
C
NEUT (A-15)
14
HOOD SHUT-DOWN DETAIL
SEQUENCE OF OPERATIONS:
* SET TIME CLOCK FOR THE HOURS THE STORE
WILL BE OCCUPIED- COORDINATE WITH OWNER'S
REPRESENTATIVE.
* ADJUST PHOTOCELL TO ACTIVATE WHEN
AMBIENT LIGHT APPROXIMATES DUSK COORDINATE WITH OWNER'S REPRESENTATIVE
* SET BOTH SWITCHES TO THE "AUTOMATIC"
POSTITION. SIGNS AND LIGHTS WILL NOW BE
ENERGIZED WHEN THE TIME CLOCK INDICATES THE
STORE IS OCCUPIED AND THE PHOTOCELL
INDICATES LOW LIGHT LEVELS.
* WHEN THE STORE CLOSES BUT IS STILL
OCCUPIED, THE SIGNS/ BUILDING LIGHTS SWITCH
SHOULD BE TURNED TO "OFF" TO EXTINGUISH
THESE LIGHTS.
* WHEN THE CREW LEAVES THE TIMECLOCK WILL
TURN OFF ALL EXTERIOR LIGHTS - THE 30 MINUTE
DELAY TIMER IS USED TO PROVIDE POWER TO THE
SITE LIGHTS FOR ENOUGH TIME TO ALLOW THE
CREW TO LEAVE SAFELY.
OVEN HOOD HEAT
SENSOR
N.T.S.
2
PHOTOCELL
TORK #2101, MOUNT
FACING NORTH.
CALIBRATE TO OPERATE
WHEN AMBIENT LIGHT
APPROXIMATES DUSK.
COORDINATE WITH
OWNER'S
REPRESENTATIVE
ON CIRCUIT A-14
N
L
TIMECLOCK
TORK #1101
MOUNT ON WALL ABOVE
ENCLOSURE
A
120V COIL
O
* SEE LIGHTING PLANS FOR CIRCUIT NUMBERS.
CONTRACT DATE:
H
C
20A HAND-OFFAUTOMATIC (HOA)
SWITCH. MOUNT IN
ENCLOSURE
PILOT-LIGHT SWTICH
MOUNTED ON HOOD
FACE FOR FRYER
HOOD FAN
SHUT-DOWN.
0
SIGN/ BLDG. LTS.
E-MAX THERMOSTAT
T
NOT USED
120V COIL
O
B-19
H
NEUT (B-19)
3
EQUIPMENT SHUT-DOWN DETAIL
N.T.S.
16
THERMOSTAT
(TRANE)
30 MINUTE TWIST TIMER
FOR PARKING LOT LIGHT
DELAY
MOUNT IN ENCLOSURE
COOL
OFF
HEAT
HEAT 1 W1
G
RC
311465 / 434385
2015388.14
PIZZA HUT
FAN
ON
COOL
AUTO
OFF
W1
W2
G
DBR 37
HEAT
NORMALLY OPEN
ELECTRICALLY HELD
RELAY WITH 120V COIL
AND 30 AMP CONT. DUTY
CONTACTS
FOR SITE LIGHTS
MOUNT IN ENCLOSURE
N.T.S.
009.00.00
ROOF TOP UNIT
(TERMINAL BOARD 3J7 CTI)
HEAT 2 W2
20A HAND-OFFAUTOMATIC (HOA)
SWITCH. MOUNT IN
ENCLOSURE
EXTERIOR LIGHTING CONTROL SCHEMATIC
PLAN VERSION:
123 Minden Shopping Dr.
Minden, LA 71055
COOL
OFF
Y1
ELECTRICAL
DETAILS
Y1
COOL 1
HEAT
Y2
COOL 2
COMMON
Y2
COMMON
E6.0
YER055
SITE LTS.
N.T.S.
2-10 TON PRECEDENT
UNIT
RH
OVEN HOOD EXHAUST FAN
WING HOOD EXHAUST FAN
THERMOSTAT CONTACT
PIZZA HOOD LIGHTS
30
DBR 37
STORE NUMBER:
NORMALLY OPEN
ELECTRICALLY HELD
RELAY WITH 120V COIL
AND 30 AMP CONT. DUTY
CONTACTS
FOR BUILDING LIGHTS
AND SIGNAGE
MOUNT IN ENCLOSURE
09.21.15
BUILDING TYPE:
SITE NUMBER:
C
A
NEUT
AUX
PIZZA
HOOD
LIGHTS
C
FAN CONTROL
RELAY
OVEN HOOD EXHAUST FAN
S
FAN MOTOR
STARTER SEE
PLANS FOR
CIRCUIT
NUMBER IN
PANEL "B"
O.L.
C
10
SHUNT-TRIP
SPST SWITCH
IN KITCHEN
4
LIGHTING & CONTROL RELAY - REAR
FRYER EXHAUST FAN
FAN MOTOR
STARTER SEE
PLANS FOR
CIRCUIT
NUMBER IN
PANEL "B"
LOW VOLTAGE
TERMINAL BOARD
(LTB)
O.L.
"LC"
RTU BLOWER
CONTROL
RELAY
20A,1P, 120V
NON FUSED,
NEMA 3R
DISCONNECT
SWITCH ON
ROOF (TYP)
FRYER
HOOD
(SEE 2/E6.0)
R3- 1
20A, 1P, 120V
NON FUSED,
NEMA 3R
DISCONNECT
SWITCH ON
ROOF
HARDWARE SPECIFICATIONS: HOFFMAN A-HE SERIES WITH
HINGED COVER AND CYLINDER KEY LOCK SET. RELAYS:
SQUARE-D CLASS 8501, RS43, V20 WITH SOCKET BASE.
R3
"BC"
LIGHTING CONTROL RELAY - FRONT
EMERGENCY OPERATION: UPON ACTIVATION OF ANY HOOD
FIRE SUPPRESSION RELAY, A RELAY IN THAT FIRE
SUPPRESSION SYSTEM SHALL CAUSE THE SHUNT TRIP
CONTROLLED DEVICES TO OPERATE, THUS
REMOVING POWER FROM ALL OTHER DEVICES
CONNECTED TO THAT PANEL. EXHAUST FANS SHALL NOT BE
AFFECTED BY THIS ACTION AND SHALL CONTINUE TO BE
CONTROLLED BY THE "OCCUPIED" OR "NON-OCCUPIED"
CONDITIONS LISTED ABOVE.
5
M EF-3
120V
PANEL "A"
CKT. 14
ALARM
CONTACTS
SPACE THERMOSTATS SHALL CYCLE ROOF TOP UNITS TO
MAINTAIN "OCCUPIED" SPACE TEMPERATURES. BLOWER
MOTORS SHALL OPERATE AS NOTED IN DETAIL 14, SHT E6_0.
CIRCUIT
BREAKERS
(TYP)
520 South Main Street, Suite 2531
Akron, OH 44311
330.572.2100 Fax: 330.572.2102
REMOVE
JUMPER
2-10 TON PRECEDENT UNIT
SMOKE DETECTOR
ACTIVATION OF RELAY "BC" (BLOWER CONTROL) SHALL CAUSE THE
THERMOSTATS ON ALL ROOF TOP UNITS TO START THE BLOWERS ON
RTU-1 AND RTU-2. EACH RTU BLOWER MOTOR SHALL RUN
CONTINUOUSLY UNTIL EITHER BC-1 IS DEACTIVATED BY TURNING OFF
THE KITCHEN LIGHTS OR WHEN A SMOKE DETECTOR ON AN
INDIVIDUAL SHALL SHUT THAT UNIT DOWN INDIVIDUALLY AS
REQUIRED BY NFPA.
REFER TO PANEL BOARD
SCHEDULES
24 VAC
8
THERMOSTAT DETAIL
N.T.S.
4