Methods for maintaining the continuity of power
supply in hospitals
To cite this article: V V Mihut et al 2018 IOP Conf. Ser.: Mater. Sci. Eng. 294 012008
- Modification and simulation of the power
supply of a metal vapor laser
D N Ogorodnikov, M V Trigub, S N
Torgaev et al.
- ON THE CONTINUITY OF METRIC
PROJECTION IN BANACH SPACE
E V Ošman
- Some structure properties of conjugate
View the article online for updates and enhancements.
functions in
V A Okulov
This content was downloaded from IP address 88.99.70.242 on 22/03/2018 at 00:45
International Conference on Applied Sciences (ICAS2017)
IOP Publishing
IOP Conf. Series: Materials Science and Engineering
294 (2017) 012008 doi:10.1088/1757-899X/294/1/012008
1234567890
Methods for maintaining the continuity of power supply in
hospitals
V V Mihut, M Panoiu, C Panoiu and I Baciu
Politehnica University of Timisoara, Department of Electrical Engineering and
Industrial Informatics, 5 Revolution Street, Hunedoara, 331128, Romania
E-mail: mihut_voicu@yahoo.com
Abstract. This paper presents alternative solutions to ensure power supply of critical
consumer, such hospitals. In a hospital it is extremely important to have a power supply
without any interruption. This is the reason of the using various solutions that ensure continuity
of power supply. In this paper it is presented a solution used in a hospital in Romania. Here is
used a generator controlled by microprocessor capable of taking over power supply in case
there are problems with power supply from the national power grid.
1. Introduction
Knowing the current need for stability and continuity in the power supply of critiques equipment, it
tends increasingly to use more alternative sources of electricity as a back-up method in power supply
[1], [2]. Alternative solutions to traditional methods of producing electricity offer stability in operation
of the equipment [3]. Knowing that such equipment can feed including surgery rooms, medical
emergency reception centres, intensive care and resuscitation centres, etc., we can say that the
implementation of these automated systems save lives [4].
Alternative methods of producing electricity must meet the following technical and economic
considerations:
- reach the current and nominal power in very short time (between 0.1 to 120 seconds),
depending on the type of alternative source.
- can be operated and / or put back into operation quickly by qualified staff
- provide as much as possible operational autonomy as well
- provide stability in operation from technical standpoint and electricity supplied
- have a relatively low cost of implementation and operation
From a technical standpoint we recommend the use of two types of elective alternative sources,
namely:
a) Electrical sources UPS - inverter which provides a very fast coupling in load, between 0.1 - 0.5
seconds. The installed power is between 250 VA ÷ 90 kVA. The high power can provide a
greater autonomy of unloading operation in both linear voltage 230V and 400V as well. This
type of sources use batteries gel (mainly with nominal voltage of 12V DC) which has the
following characteristics: require no maintenance operations provides maximum safety against
leaks, can support up to 800 cycles of operation, and ensure longevity and reliability in
operation. The advantage of this type of alternative electrical source consists in fast task
switching and disadvantage group consists in using of batteries that can be discharged without
possibility of supplementary charge.
Content from this work may be used under the terms of the Creative Commons Attribution 3.0 licence. Any further distribution
of this work must maintain attribution to the author(s) and the title of the work, journal citation and DOI.
Published under licence by IOP Publishing Ltd
1
International Conference on Applied Sciences (ICAS2017)
IOP Publishing
IOP Conf. Series: Materials Science and Engineering
294 (2017) 012008 doi:10.1088/1757-899X/294/1/012008
1234567890
b) Electric generator which provides a coupling in the load between 60-300 seconds. Coupling
time depends on the type of fuel, temperature of the ambient temperature of the engine block
during standby engine output heat electric power generator - mostly installed power ranges
from 650 VA ÷ 300 KVA. The advantage of this type of alternative source is that we can
increase the operating time as long as there is fuel in the tank. Even recommend switching to
more fuel tanks, tanks that can be fed in functioning
In the electrical systems of major importance it is recommend using both types of electrical energy
sources. Of course you can use other types of sources that keep mandatory features described namely:
quick-coupler pregnancy, high power cut, high autonomy of operation.
Also the operation mode and the input / output to / from the load are very important. Knowing that
it is difficult to balance two alternative power sources in parallel does not recommend starting
simultaneously these types of equipment.
Always the first source that feed the electrical equipment must be source-in the task. Depending on
the necessity it is possible to command the second source to enter in compensation with the first, but it
all depends on the installed power of the first sources and power requirements of the consumer.
Always has to be a balance between power generated by the power source and absorbed by the
consumer.
Depending on the consumer it can be made a calculus of power of alternative sources, such as their
technical characteristics and functioning and especially the installed power.
It is not recommended to use alternative power sources without knowing the entire assembly, not to
endanger the optimal functioning of the equipment.
Also always recommended calibration and optimal setting of these sources (given that some have a
wide range of settings), according to the type of consumer, environmental and binding according to
the main system power supply.
In the following an optimal implementation in operation for generating electrical systems major is
presents.
2. The electric generator group
The electric generator groups a fixed or mobile autonomous electricity production, which
ensure independent power supply, emergency, if the main electrical supply interrupted [5-10].
The group is made up of a diesel engine which drives a synchronous generator capable of
providing an output of at least 1.5 times the normal amount of power consumed routinely and
automatically transfer the load equipment that monitors network parameters main engine and
the generator ensuring command sequences automatic START - STOP.
2.1. Automatic load transfer equipment
It is the "brain" of the generator and is equipped with a microprocessor and it has multiple
inputs and multiple outputs that enable it to perform the following functions:
a) Measure and display the voltage primary source. If any phase voltage main power is
out of the (± 10%) Unom is starting command for the generator start cycle.
b) Measure and display engine for the following parameters: battery voltage (V), engine
coolant temperature (oC), lubricating oil temperature (°C), lubricating oil pressure
(kPa), engine rotation speed (revolutions/minute), cumulative total number of operating
hours, the number of starting attempts, fuel level in the buffer tank, the fuel level in the
tank outside.
c) Measure and display synchronous generator following parameters: line and phase
voltages (V), the phase currents (A), active powers (KW), total apparent power (KVA),
total reactive power (KVAR), total active energy (KWh), total reactive energy
2
International Conference on Applied Sciences (ICAS2017)
IOP Publishing
IOP Conf. Series: Materials Science and Engineering
294 (2017) 012008 doi:10.1088/1757-899X/294/1/012008
1234567890
(kVARh), total power factor, the percentage of rated output (%), the level of
excitation of the generator, frequency (Hz).
d) The following cases are ordered protection for stopping the engine while the onset of
light signals: oil under reduced pressure, overheats coolant, packaging or excessive
speed, start attempt failed, too low or to high values of frequency, too low or to high
values of output voltage, generator overload, generator short circuit
e) The motor-warning for the following parameters: coolant temperature dangerously
high, dangerously low coolant temperature, engine oil level too low, dangerously low
engine oil pressure, dangerously low fuel level in the tank buffer, unsafe voltage
batteries
f) Operating mode selection. There are three modes of operation: local manual control,
local automatic control, and automatic remote control.
g) Diagnosing failures
PLC must display the diagnosis and to identify the nature of functional errors. Errors must
be preserved in memory, supporting in obtaining a history of behavior of the generator,
following the last or the last reset.
The main parameters or components that are aimed at the diagnosis failures: failure
lubrication oil pressure, coolant temperature detection, voltage batteries, motor rotation speed
detection, microprocessor or memory automatically, DC power transducers, unexplained
unscheduled stoppages, failure speed regulator, failure voltage regulator, failure synchronous
generator, incorrect starting sequence, failure starter, failure generator, fuel electric valve
control relay, guillotine intake air control relay.
h) Generate startup sequence
i) Generate stop sequence
To explain the generation sequences mentioned, considered the case supplying a hospital.
According to the figure1, KN represents mains contactor, KG emergency contactor and Kins
auxiliary source realized islanding consumer class 15 for others. Islanding is necessary to use
a low cost generator, with a power that permit the supply only consumers in class 15 using a
backup solution from another transformer station that does not belong to the hospital with a
switch manually controlled or remotely by a human operator, overload protection and short
circuit.
The starting sequence is as follows:
- The main source fall after 5-10 seconds commands the starter.
- If the engine does not start, longer command the starter twice more with break
between starts about 10 seconds.
- If the engine speed reaches 15% of rated speed, ordering off the starter. If this
condition is not achieved, destroying the starter.
Interruptions of mains voltage distribution can last from less than a second to several
minutes or longer. If interruptions between two seconds and two minutes are common, caused
by minor incidents distribution system, the extended more than two minutes, are due to events
such as storms, lightning, earthquakes, fault lines of high voltage switchgear (110, 230 KV)
underground cable disruption due to construction etc.
2.2. Diesel Engine
Are used, four-stroke engine with direct injection and turbocharging, in particular to be able
to take 100% of nominal load in a single operation, diesel fuel must have an average octane
number higher than 35.
3
International Conference on Applied Sciences (ICAS2017)
IOP Publishing
IOP Conf. Series: Materials Science and Engineering
294 (2017) 012008 doi:10.1088/1757-899X/294/1/012008
1234567890
.
Figure 1. Power supply system for a hospital
Figure 2. Schematic Diesel group - synchronous generator
4
International Conference on Applied Sciences (ICAS2017)
IOP Publishing
IOP Conf. Series: Materials Science and Engineering
294 (2017) 012008 doi:10.1088/1757-899X/294/1/012008
1234567890
The power supply circuit comprises:
- A buffer tank with a maximum capacity of 200 l,
- A tank outside, of higher capacity necessary to assure autonomy according to the group,
- An automatic pump, coupled with a manual pump, for filling the buffer tank from outside
the tank.
The buffer tank is placed at a height above the engine, based on the required circuit
pressure of the injection
Lubrication circuit comprises a container and a mini-pump to ensure sufficient pressure.
The cooling circuit comprises a radiator, a fan and a pump attached to the cooling water
circulation. The heating standby circuit contains a heater (corded) which ensures the
maintenance of internal motor temperature around 40oC. The electric starting system is
composed of the group of batteries, electric starter and an independent electronic charger.
Battery capacity should allow three repeated attempts to start a current of 1000 A
minimum at 0o C.
Electronic charger powered from the mains with a charging current of 10A minimum, must
provide 80% of the rated load in 4 hours and 100% within 12 hours.
Speed controller includes:
- An electronic PID control to adjust motor speed by injection,
- A tachometer generator mounted on the motor shaft which produces a voltage
proportional to motor speed, as input to the controller,
- A mechanical device security (guillotine for air inlet) to stop the engine immediately in
case of needed.
System for noise limitation is made of specific devices for sound insulation in areas of the air
supply and the special acoustic panels and panels for engine room. Allowable noise level for these
areas is approximately 75 dB.
2.3. Synchronous generator
For synchronous generator driven by the diesel engine, the permissible voltage variation to variation
in the slow load power provided is up 1% of nominal voltage Unom. The most critical regime is
characterized by varying the instantaneous voltage generator when suddenly loading or unloading the
generator occurs. Loading suddenly the generator with a high current, lead to a rapid decrease of the
terminal voltage.
If this drop exceeds 25% - 35% Unom may occur two cases: the generator get out of synchronism, or
is command stopping the group. For this regime the maximum allowable voltage variation is 5% Unom.
It is considered that a maximum of 1.8 Inom_generator is acceptable if the number of starts is higher than
10 starts / day.
3. Conclusions
Electricity is produced and transported away from the place where we use so often, its supply
interruption occurs. Continuity of power supply is important and sometimes critical for some users.
An electric generator group provides important sources of power supply, in particular when large
consumers or productive units where interruptions can cause high problems. Whether banks, hospitals,
hotels, guesthouses, restaurants, residential buildings, corporate headquarters, production facility or
private residence, by lack of electricity can be absolutely no access to a resource required daily. Diesel
generators maintenance costs are lower, are reliable, robust and resilient over time.
The electric generator groups represent modern solutions to ensure continuity of power supply
regardless of the consumer who require uninterrupted electrical energy supply.
5
International Conference on Applied Sciences (ICAS2017)
IOP Publishing
IOP Conf. Series: Materials Science and Engineering
294 (2017) 012008 doi:10.1088/1757-899X/294/1/012008
1234567890
References
[1] Tutelea L N, Deaconu S I and Popa G N 2014 Reduced cost low speed wind or hydro energy
conversion system with twin stator windings induction generator, 16th International Power
Electronics and Motion Control Conference and Exposition, 21-24 sept, Antalya, Turkey, pp
317 – 324
[2] Baciu I, Cuntan C D and Gabor B 2014 The study of the electric parameters of an autonomous
supply system with photovoltaic panel, International Conference and Exposition on Electrical
and Power Engineering (EPE), 16-18 Oct, Iasi, Romania, pp 1138 – 1143
[3] Cunțan C D, Baciu I and Ghiorghioni L 2011
DC Stabilizer With Digital Control, 10th
Aniversary International Conference on Accomplishments In Electrical and Mechanical
Engineering and Information Technology, Banjaluka, Rep Srpska, pp 807-812
[4] Sărăcin C G, Sărăcin M and Zdrenţu D 2015 Integration of residential alarm systems into
electric power supplies of vital consumers, 9th International Symposium on Advanced
Topics in Electrical Engineering (ATEE), Bukarest, Romania, 7 – 9 May
[5] Chobanov V 2016 Continuity of power supply in smart grid with PV penetration, IEEE
International Conference on Power Electronics and Motion Control Conference (PEMC),
Varna, Bulgaria, 25-28 September
[6] Barsali S, Ceraolo M, Pelacchi P and Poli D 2002, Control techniques of Dispersed Generators
to improve the continuity of electricity supply, IEEE Power Engineering Society Winter
Meeting, New York, USA Conference Proceedings Vol. 2 pp 789 - 794
[7] Abdin E S, Osheiba A M and Khater M M 1999 Modeling and optimal controllers design for a
stand-alone photovoltaic-diesel generating unit, IEEE Transactions on Energy Conversion
14(3) 560-565
[8] Anderson P M and Mirheydar M 1995 Analysis of a diesel-engine driven generating unit and
the possibility for voltage flicker, IEEE Transactions on Energy Conversion 10(1) 37-47
[9] Lidozzi A, Solero L and Crescimbini F 2012 Adaptive Direct-Tuning Control for VariableSpeed Diesel-Electric Generating Units, IEEE Transactions on Industrial Electronics 59(5)
2126-2134
[10] Shetty P K, Lewlyn L and Rodrigues R 2010 Total Productive Maintenance of a Diesel power
generating unit of a institution campus, 2010 International Conference on Mechanical and
Electrical Technology, 10 – 12 September, Singapore, Singapore, pp 68 - 71