AlarmGard & FireGard
Closing Systems
™
™
Cornell answers the call for safe, reliable and simplified fire door closing options with its full line of FireGard™ and
Advanced AlarmGard™ fire door closing systems. Unlike conventional, old style fire door operators, all FireGard systems
close fire rated doors without releasing spring tension. Cornell’s systems eliminate potentially dangerous closing
speeds and allow for simplified testing and resetting without mechanically resetting the door. Besides saving time and
money, these unique features help ensure your fire doors are fully functional and ready to protect the safety of building
occupants and property during an emergency.
E M E R G E N C Y R E S P O N S E
O P E R A T O R S
AlarmGard™ Advanced Closing Systems
Recommended Applications for
AlarmGard Closing Systems:
Any application where
mechanical testing and
resetting is impractical or
not desired.
Activation by fire alarm
system or smoke detector is
desired or required.
Where fire doors are installed
within pedestrian
thoroughfares.
Fire-rated units in recessed
applications.
Units in areas susceptible to
frequent power outages.
▪
▪
▪
▪
▪
AlarmGard Operating System Benefits:
▪ Automatic resetting of the automatic, fail-safe closing system yields dramatic savings for building owners in
testing and resetting costs as well as minimized opening downtime.
▪ AlarmGard systems can be activated by fire alarm systems, local detectors or power failure without the need for
▪
a separate alarm interface release device.
Eliminates mechanical spring release and complicated testing and resetting, especially critical for recessed and
larger doors.
● System automatically resets to normal operation upon clearing of alarm signal and/or restoration of power.
● Routine testing of the automatic closing system occurs in minutes from floor level by facility personnel.
● Required annual inspection by a trained fire door systems technician is simplified.
▪ A safe and controlled, automatic closing speed.
▪ Can be applied consistently on fire door, insulated fire door, counter fire door and SmokeShield products.
▪ UL approval allows Cornell to retrofit AlarmGard motor, chain and crank operators to most manufacturers’ fire
®
doors while maintaining the door’s UL ratings.
AlarmGard Motor Operated Systems
These systems close the fire door in response to an alarm signal and are fail-safe by design, safely closing the
door during a prolonged power failure. When the alarm is cleared and/or power is restored, resetting is done
automatically without requiring human interaction. Unlike conventional fire door operators, AlarmGard Motor
Operators do not require an additional mechanical release device to respond to central alarm signals or local
smoke detectors. For doors up to 51’ wide, 36’ high or a maximum 1200 sq. ft.
Benefits:
Safe and controlled, uniform closing speed.
0 or 10 second selectable time delay.
Recommended Applications: All motor operated fire doors.
Options: Battery Backup, Horn Strobe, Voice Warning Module, Sensing Devices and more.
▪
▪
AlarmGard Tube Motor Operated Systems
For Counter Fire Doors
AlarmGard Tube Motor operators are concealed in the Counter Fire Door’s shaft assembly making them ideal for
openings with tight clearances around the coil area or to neatly conceal the operator and drive components. 115
VAC power required for motor, 24 VDC, 115 VAC or 24 VAC required for control panel. Available for Counter Fire
Doors up to 6’ wide, 10’ high or up to 60 square feet.
Benefits:
▪
▪
Protected by US Patent #6,155,324
Convenience of ergonomic motor operation in an aesthetic, low profile design.
Full height openings from floor to 10’ high.
Recommended Applications:
Fire shutters that require the convenience of a motor operator in limited headroom conditions.
Aesthetic motor operation that eliminates the need for a bulky motor cover.
Options: Control Stations, Key Test Station, Sensing Devices, Battery Backup, fusible link switch and more.
▪
▪
Manual AlarmGard Chain and Crank Operated Systems
AlarmGard Chain
These compact designs include a built-in automatic reset release device for connection to a central alarm
system or local detectors - no external release device is required. Units will close automatically upon alarm
or power failure in excess of 10 seconds. Resetting spring tension or re-engaging the operator is not required.
AlarmGard Chain and Crank Operators are available for use on all Counter Fire Doors and Fire Doors up to 34’
wide or 28’ high standard construction. Crank units available to 12’ high.
Benefits:
Integral governing device provides safe closing speed.
Accepts 24V DC, 115V AC or 24V AC power supply.
UL 864 Listing.
10 second alarm and power failure time delay.
24V DC output for close warning device.
Recommended Applications:
Use for fire products that do not require the daily operating convenience of a motor operator.
Clearance and access to the hand chain or crank eye is required.
Options: Electric Key Switch, Battery Backup, Horn Strobe and more.
▪
▪
▪
▪
▪
AlarmGard Crank
1Protected by US Patent #6,155,324
▪
▪
E M E R G E N C Y R E S P O N S E
Fire Door Closing System Alternatives
O P E R A T O R S
AlarmGard
FireGard
Motor
Tube
Chain & Crank
Activation by fire alarm systems, local detectors or power
failure without separate interface / device.
●
●
●
Fail-safe operation: fire doors will close during power failure.
●
●
●
System automatically resets on clearing of alarm or restoration of power.
●
●
●
No mechanical spring release, avoiding tension reset at coil.
●
●
●
Routine testing of closing system occurs in minutes from floor level by
facility personnel.
●
●
●
Required annual inspection by trained fire systems technician is simplified.
●
●
●
Motor
Chain & Crank
●
●
●
●
●
Power is unavailable at opening.
UL approval for retrofit while maintaining door’s listing.
●
●
Push-up
fusible link
●
●
Fusible link closing. Testing releases spring tension, causing extended
opening down time and requiring mechanical reset at coil by trained technician. Not fail-safe. Consistent with conventional systems.
●
Available as an option
Recommended Applications for
FireGard Closing Systems:
Opening is not a pedestrian thoroughfare.
Connection to Central Alarm System or
▪
▪
▪
Local Smoke Detectors is not required by
local building officials.
Applications where the installation of
fusible links, turnbuckles, chains and
eyebolts to the face of both sides of the
wall above the opening will not detract
from the intended aesthetics.
FireGard™ Operating System Benefits
▪ Activate fire rated doors without releasing spring tension, avoid dangerous resetting process
▪ Fusible link activated
▪ Simple floor level testing and resetting
▪ Annual inspection by a trained fire door system technician is simplified
▪ Systems will not automatically close upon power failure
▪ Safe, controlled rate of descent
Options: Floor level test switch - allows system testing at floor level rather than above coil at fusible link location.
FireGard Motor Operated Systems
UL listed, industrial duty gear head operator recommended for units that normally cycle up to 20 times per day.
HP Available: 1/3, 1/2 and 3/4. Available for fire doors up to 225 square feet, insulated fire doors up to 165
square feet.
Features and Benefits
▪ Spring tension is not released upon activation
▪ Convenience of motor operation
▪ Auxiliary Chain for emergency operation - just pull to operate
▪ Safe and controlled closing speed
Options: Floor Level Test Switch, Sensing Devices, Release Devices, Battery Backup
FireGard Chain, FireGard Crank Operated Systems
Available for use on all Counter Fire Doors and Fire Doors up to 34’ wide or 28’ high standard
construction. Crank units available to 12’ high.
Features and Benefits
Spring tension is not released upon fusible link closing
▪
▪ Safe and controlled closing speed
▪ Power not required
▪ Economical
Options: Floor Level Reset Device, Battery Backup, Fail-Safe Release Device
Retrofit Operators
Specialty UL approval allows Cornell to retrofit AlarmGard and FireGard operators to most
manufacturers’ fire doors while maintaining the door’s listing agency ratings.
Push Up Operation, Specialty Operators
Specialty Operators and Push-Up Operation are available. These conventional systems release
spring tension and require mechanical resetting by a trained door system technician.
2
E M E R G E N C Y R E S P O N S E
O P E R A T O R S
Fire Door Closing System Accessories
Battery Backup Devices
Prevents unplanned door closure due to power failures for up to 8 hours. Also functions as a backup DC power
source for local warning devices and detectors during power failures.
UL 325 Compliant Entrapment Protection Devices
Per UL 325-2010, doors without a connected and properly functioning primary entrapment device will only
function by constant pressure close operation. The primary entrapment protection devices below enable
momentary contact to close operation. Tube motors are not currently approved to accept these devices.
Electric Sensing Edge with 2 Wire Wireless Edge Kit: Eliminates the need for a physical travelling electric cord
connection between the bottom bar sensing edge device and the motor operator.
ELR Electric Sensing Edge: 2 wire monitored electric sensing/smoke seal edge. Contact with the edge before
the door fully closes causes the door to immediately stop downward travel and reverse direction to the fully
open position. Provide a retracting safety cord and reel or a self-coiling cable connection to control the circuit.
Photo Eyes: Interruption of the beam before the door fully closes causes the door to immediately stop
downward travel and reverse direction to the fully open position.
Optional Secondary Entrapment Protection Devices: May be used in conjunction with primary entrapment
devices or with constant pressure to close operation.
▪
▪
▪
FireGard Floor Level Test Device
Enables the convenience and safety of testing of the fire door at floor level rather than at the fusible link above the
coil. Designed for surface mounting.
Fail-Safe Release Devices
If conditions require that Fire-Master Motor Operators respond to alarm signals from detection devices such as smoke
detectors, heat sensors and central alarm systems, a fail-safe release device may be incorporated to receive the signal
and activate the door. Onboard or wall mounted, depending on the system configuration, these devices permit doors to
close long before high temperatures melt fusible links.
FireGard AR-D
Note: Cornell’s advanced AlarmGard Fire Door Closing Systems do not require an additional mechanical release device
to respond to alarm signals from detection devices.
Fire Door Annunciators
Optional safety devices that provide a visual and/or audible advanced warning when the door is about to close. Can
be activated upon alarm signal or loss of power when supported by a battery backup device.
Horn Strobe: ADA compliant, 24 VDC warning devices that are powered by a release device power source to provide an advanced fire door closing warning. Activation upon alarm signal and power failure and/or alarm signal
only depending on release device.
Voice Warning Module: An ADA compliant warning device. Provides up to four different voice warning messages
upon activation. Messages are in English and are field selectable.
▪
▪