Combi Boilers - Poor Hot Water Delivery
Combi Boilers have no hot water storage and so heat the water as it flows through the appliance. The appliances are
catagorised by their maximum power measured in kW and the maximum hot water flow rate:
Morco Model
FEB20E
FEB24 range
EB24CPM
GB24
GB30
Max.
Power
24kW
24kW
24kW
24kW
30kW
Maximum Hot water
Flow Rate
9.6 litres/minute
10 litres/minute
10.6 litres/minute
9.9 litres/minute
12.4 litres/minute
Temperature Lift
35 °C*
34 °C*
35 °C*
35 °C*
35 °C*
*Refer to section 3
All of the above combis have a water temperature control knob – this should be set to maximum unless the water
being produced at a tap or shower is too hot in which case it should be turned down. If water is too cool then one or
more of the following is occurring:
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
The gas supply to the burner is too little
The water flow through the combi is too great
The mains supply water temperature is very low (this will only occur in winter)
Damaged mixer taps or shower mixer valve (usually caused by frost or high mains water pressure)
Low mains cold water operating/working pressure
One of the two combi heat sensors (thermistors) is faulty or is correctly indicating a problem
Damaged diaphragm (more prevalent in areas with chalky water)
A water saving shower head is fitted
Crossed pipework
More than one hot water outlet is being operated at once
The list looks a little long and our advice is to carry out as many of the checks supplied in the following notes
yourself. It may lead you to the correct diagnosis without the cost of calling an engineer. In any event it will make
you more confident when discussing the problem and solution with the engineer. Morco will connect any Gas Safe
Registered engineer with our technical team should they ring in during normal business hours. We will advise
engineers how to diagnose the problem.
1. Gas Supply
Insufficient gas reaching the combi will result in poor hot water delivery. Do not be fooled into thinking all is well just
because the hob and/or the gas fire work – they use very little gas compared to the boiler and they can continue to
operate even though some of the problems below are present:
•
•
Gas regulator is damaged or of the wrong size – a minimum of 3.5kg per hour is recommended. This should
be stamped onto the regulator situated on top of the bottle
Gas type – Propane is recommended as it will continue to work even at the low temperatures we experience
in the UK. The boiler will work on Butane, ONLY when the weather is warm. LPG bottles in the UK are red
and Butane bottles are generally blue.
•
•
The GB24 and GB30 combis will not run on Butane
Bottle size –a 47kg propane bottle is required to reliably operate a combi in all conditions
The combis feature a gas valve that controls the amount of gas that is burned. If this is faulty or the gas pressure has
been incorrectly adjusted then a Gas Safe Registered Engineer will need to be contacted.
2. Water Flow Through the Combi is Too Great
All combi boilers (except the FEB20E) have water flow regulators fitted inside their cold water inlets. These ensure
that the flow rate cannot exceed a certain level and hence the power of the boiler is sufficient to heat the quantity of
water passing through it. If this regulator is damaged or missing then the quantity of water passing through the
combi will be too great for it to provide hot water of an acceptable temperature.
MCB2240 - Flow Regulator – this is fitted
inside the combi on the cold water inlet. It
cannot usually be seen unless the cold
water inlet system is removed from the
inside of the combi. This is usually a job for
an experienced engineer. It is about the
diameter of a penny and is easy to lose or
forget when re-assembling a boiler and
this may explain why they can be missing.
Solution
To test that the flow rate is correct you should open the hot tap in the kitchen fully and measure the amount of
water that flows through it in 1 minute - if this exceeds the amount quoted for the model of boiler in the table
above then either:
•
•
The flow regulator is likely to be damaged or missing
There is a source of cold water that is diluting the hot water supply - see section 4 below
3. Supply Water Temperature Low
The Temperature Lift quoted in the table on the first page is the amount of heat that the combi boiler gives to the
water passing through it. If the water coming into the home from the mains water supply is 15°C and the
temperature lift is 35°C then the temperature of water leaving the boiler will be the temperature lift of 15 +35 =
50°C. This is more than warm enough for a shower and in fact the shower mixer will dilute this with cold to achieve a
comfortable temperature. If the water entering the home is 3°C then the temperature of water leaving the boiler
will be 3 + 35 = 38°C which is just hot enough for a shower but probably too cool for washing dishes. This issue
applies to all makes and types of instantaneous water heaters such as combi boilers.
Solution
If the temperature provided by the combi is insufficient (maybe you prefer the washing up water to be hotter) then
the only way of increasing the temperature is by slowing the flow through the combi by closing the hot water tap
until the desired temperature is achieved. During winter months, when the water temperature entering the home is
cold, use of this method may be vital to ensure acceptable hot water delivery.
4. Damaged Mixer Taps or Shower Mixer Valve
Many Caravan Holiday Homes have mono-block basin taps and TMV2 shower mixer valves. These are very
susceptible to frost damage even when the home has been drained down. This is due to the fitting of non-return
valves in the shower mixer (see our factsheet on winterising your home). The damage caused by frost to these items
is internal and so no leak shows. However it causes cold water from the mains supply to enter the hot water supply
once a hot outlet is open and this dilutes the hot water delivery. The boiler is functioning correctly but it cannot
overcome damaged mixer taps or shower mixers.
Mixer taps and TMV2 shower mixers are generally specified to run at an incoming mains water pressure of 6 bar
maximum. Operating them above this pressure either damages them or causes them to work incorrectly. Mains
water pressure on parks varies throughout the year so it is possible for a TMV2 or mixer to work fine at certain times
and then cause problems at others. Morco’s combination boilers and water heaters can tolerate a mains water
pressure of 10 bar and so it will be the mixer/TMV2 that will cause problems first. Some manufacturers install
pressure regulation valves on the incoming mains water and set them to 3 bar. Some parks with high or variable
pressure also install the pressure regulators when siting a home.
This is a typical pressure
reducing valve and it will be
found close to the point at
which the mains water supply
enters the holiday home
Diagnosis
If you are getting cool water at any one of the hot water outlets you can diagnose the above problem by measuring
the hot water flow rate at the hot tap in the kitchen (if the tap is a mixer, ONLY switch on the hot side). Turn the hot
tap on fully and run the water into a washing up bowl or similar for exactly 1 minute. Then measure the water in the
bowl using a measuring jug or even an empty 1 litre milk bottle. If the volume of water exceeds the maximum flow
rate shown in the table above then it is very likely the shower mixer or the taps are frost damaged. Alternatively it
may be the flow regulator inside the boiler that is missing or damaged – see section 2 for more details. A small
number of taps have flow regulators fitted to the outlet as a water saving device. These will restrict the flow and
hence not allow you to diagnose the problem. These flow regulators are easy to remove using either your fingers or
a pair of plumber’s pliers.
If the problem is high pressure then a pressure gauge with a range of 0-10 bar can be attached on the mains inlet to
establish what the pressure is. Remember that the pressure will be significantly lower in summer when there is high
demand for water.
Solution
You will need to establish whether the tap, shower mixer or flow regulator is damaged and replace them. This is
usually best done by calling an experienced engineer.
Advanced Diagnosis
A more involved but failsafe way of checking the boiler is working correctly is as follows:
•
Switch off the main water supply to the van at the stop cock.
•
•
•
•
•
•
•
•
•
•
Gain access to the van under the boiler and locate the hot feed pipe from the boiler. It is the left hand 15mm
copper pipe as you look at the front of the boiler.
The copper pipe will either have a 15mm push fit tee or 15mm elbow connected. (see below)
Turn the wheel on the fitting that is closest to the copper pipe anti-clockwise until it stops
Press the collet that is between the wheel and the copper pipe into the fitting as you pull on the fitting
This should disconnect the fitting from the pipe
Now place a bucket under the pipe and switch the cold water supply onto the van
Hot water should now leave the copper pipe at a flow rate and temperature lift that matches the table on page
1.
If the flow rate is too high, the flow regulator in the boiler is likely to be missing (section2). If the flow rate is
correct and the temperature lift is too low then you have established that the problem lies with the boiler, the
gas supply or the water supply pressure.
The benefit of this procedure is that it operates the combi in hot water mode independent of the rest of the hot
water pipework and outlets and so rules certain problems in or out.
Replacing the fitting is the reverse of removal.
5. Low Mains Cold Water Operating/Working Pressure
All combi boilers have a minimum operating/working pressure (usually measure in bar) below which they will not
function correctly. If the mains supply pressure is too low this minimum operating pressure will not be achieved and
will cause one or more of the following:
•
•
•
•
•
The boiler not to fire when hot water is demanded
With mixer taps and shower mixers hot water delivery will be poor
One outlet will consistently provide hot water and yet another one will not
Hot water delivery will come and go. For example a shower temperature will rise and fall during the shower
Water will run cold from a tap when a toilet is flushed or a cold tap is switched on and will return to hot when
the toilet cistern is filled or the cold outlet is switched off
Solution
You will need to prove to the park that they are not providing you with sufficient water pressure. This can only be
done by asking an engineer to place a pressure gauge in a tee on the cold water supply pipe below the boiler. See
photo below.
This is a photo of the underneath of a typical
combi boiler before the gauge is fitted with the
filling loop in place. The 15mm copper pipe 2nd
from the right is the cold water inlet.
This shows a pressure gauge fitted to the cold
water inlet pipe connected via the filling loop
tee. Open the black plastic tap and the gauge will
read the “standing pressure”. To read the
“operating pressure”, open each hot outlet in
turn and take a reading from the gauge while the
hot water is running. This will provide you with
the “operating pressure” for each hot outlet. The
connection on the filling loop tee is 1/2inch BSP.
If the operating/working pressure is less than 0.8 bar for the GB24/30 models or 0.3 bar for all other models, then
the water operating/working pressure is too low to operate the appliance. DO NOT make the mistake of placing a
pressure gauge on the end of the incoming water supply as this will provide you with “standing pressure” and this is
not relevant in this instance. A high “standing pressure” DOES NOT ensure an acceptable “operating pressure”. Both
standing and operating pressure can vary during the day depending on demand. It is not unusual for a boiler to work
correctly at midday when hot water demand is low and not work at 7pm when demand for hot water on the park is
high.
6. Boiler Heat Sensor (Thermistor)
This sensor tells the boiler controls at what temperature the hot water is being produced. The information supplied
by the sensor is used to control the temperature of the hot water. If the thermistor is faulty it will either tell the
controls nothing (the boiler will lock out and show a fault code on the indicator- see fact sheet on fault codes) or it
gives the boiler controls an incorrect temperature reading. The latter causes the boiler to reduce the temperature of
hot water it produces (it may not even allow the boiler to fire up).
Solution
A Gas Safe engineer will be able to test the output of a thermistor using an electrical multi-meter and hence
diagnose any problems. Replacing the sensor in some boilers is straightforward (clip on type) and does not involve
opening the gas or the water circuits. Other boilers have a wet pocket type and this involves partially draining the
primary circuit. Thermistors ARE NOT on or off switches and hence cannot be assessed using a continuity test or
“shorted out” to get the boiler working. They produce a resistivity that is proportional to the temperature being
tested and only a multi-meter capable of measuring resistivity can be used to diagnose their correct operation.
Boiler Type
FEB20E
FEB24E
FEB24ED
FEB24ED3*
MCB2245
Hot Water Thermistor Code
FCB1175
FCB1080
FCB1080
MCB2245
Clip on Thermistor
Clip on
Type
Yes
No
no
yes
Wet Pocket
Type
No
yes
yes
no
FCB1080
Wet Pocket Thermistor
The FEB24ED3* boiler uses 2 x MCB2245 to calculate the hot water temperature. Both of these need to be working
normally for the correct operation of the combi. The GB range of condensing boilers also use 2 thermistors with part
codes ICB309001 and ICB128001. Both these are wet pocket types and will require partial draining of the primary
circuit to replace.
7. Damaged Diaphragm (more prevalent in areas with chalky water)
This problem only occurs with boilers in the FEB24 range. The FEB20E and GB range of boilers do not have a
diaphragm.
The diaphragm is an EPDM rubber disc that is positioned in the heart of the boiler. It is subject to heat and a number
of damaging chemicals found in mains water, such as chlorine and dissolved salts and as such is viewed as a
consumable item. If the diaphragm splits the boiler will not switch from central heating mode to hot water. Once the
hot tap is open the boiler may ignite but only warm water reaches the taps or shower. Another way to tell if this is
the problem is to feel the temperature of the central heating flow pipe under the boiler while the hot tap is open. If
it feels hot you have probably got a diaphragm problem. The flow pipe for the FEB24 and GB24 range of boilers is on
the far left as you look at the front of the boiler.
Solution
You will need to contact a Gas Safe registered engineer to either replace the diaphragm (MCB2255) or the hydraulic
valve kit (MCB2257, this houses the diaphragm). A good engineer can achieve this in approx. 1 hour.
MCB2255 – Diaphragm for the following
boilers:
•
•
•
FEB24
FEB24ED
FEB24ED3*
MCB2257 Hydraulic Valve Kit
(containing the diaphragm) for the
following boilers:
•
•
•
FEB24
FEB24ED
FEB24ED3*
8. A water saving shower head is fitted
All combination boilers are designed to work with a certain working or operating pressure (see section 5) and a
certain minimum flow rate of water passing through the boiler. Both of these parameters are influenced by the
pipework and outlets on the hot water system. Certain shower heads, especially those advertised for water saving,
can cause the boiler to either not fire or to fire with a low gas burn rate reducing the temperature of the water
supplied. These shower heads only usually create the problem when the mains water pressure is relatively low. You
may find that the hot water tap in the kitchen works fine but the shower does not. As water pressure on caravan
sites can vary throughout the day, the problem may be intermittent.
Solution
To assess the situation, simply remove the shower head from the flexible hose and turn on the shower. If the water
coming out of the pipe becomes hot then:
1. The shower head needs replacing for a “full flow” type and/or
2. The water pressure on the site needs increasing
Obviously the first solution is the easiest to carry out!
9. Crossed Pipes
It is not unheard of for a caravan to be supplied with hot and cold pipes connected the wrong way around to a pair
of taps or a shower mixer valve. This mistake can also be caused when repair work is carried out on the van,
especially as a common repair is to replace the shower mixer tap due to frost damage. The effect is the same as a
damaged mixer tap/shower mixer and the diagnosis and solution are highlighted in section 4 of the factsheet. We
have also come across homes where the manufacturer has crossed the hot and cold supply pipes under the boiler.
The GB range of boilers will run in reverse but hot water delivery is affected and damage can occur. They also may
make a weird noise!
10. More Than One Hot Water Outlet is Being Operated at Once
Combination boilers in both the domestic and leisure market work in an identical manner and produce a set flow of
hot water with a set temperature lift. In the case of Morco’s 24kW combis they supply approximately 10 litres per
minute of hot water with a temperature lift of 35 °C. This is fine for a shower when it is used by itself but when a hot
tap or a second shower is opened at the same time the hot water delivery will reduce for both outlets.
If two outlets are opened at once you would think the 10 litres per minute of hot water would divide equally
providing 5 litres per minute to each outlet. This is not the case as the pipe runs to each outlet will be of different
lengths and provide different resistance to water flow.