black ht
Thermal power (A7:W45) 35 ÷ 238 kW
Cooling power (A35;W7) 32 ÷ 201 kW
High efficiency and high temperature air/water heat pump
with axial fans and semihermetic reciprocating compressors
134a
H2O
80°
MINIBOSS
CONTROL
black HT
High efficiency and high temperature air/water heat pump with
axial fans and semihermetic reciprocating compressors
Technical book
black ht
134a
CLASS A
MULTI-PURPOSE
R134a
LOW NOISE
MINIBOSS
H2O
80°
CONTROL
3
TWO CIRCUITS
WATER
UP TO 80°
HORIZONTAL AIR
DISCHARGE
New series of dedicated heat pumps with semihermetic
reciprocating compressors.
Standard version in 12 sizes
Thermal power (A7:W45) 35 ÷ 238 kW
Cooling power (A35;W7) 32 ÷ 201 kW
BLACK HT is a series of heat pumps in R134a, with the possibility of having water at 80°.
SUPERVISION
VIA WEB
MANAGEMENT
OF UP TO 4-6
UNITS WITH
MINIBOSS
STRONG POINTS
>> H
igh temperature of the produced water: up to 80°C
>> Extended limits of operation in heat: air up to -20°
>> Automatic management of DHW
>> DWS always available (multi-purpose)
>> Intelligent management of defrosts
>> Subcooler and increased fin pitch
>> /LN Silent version
>> Supervision via web
>> Management of up to 4-6 units with proprietary
control
>> Dual refrigerant circuit starting from size 70
The technical documentation can be improved all the times. Enerblue can update, time by time, all technical data in order to improve all necessary information for the customer.
CONTENTS
1Technical features__________________ p.6
2 Technical data____________________ p.19
3 Electrical data_____________________ p.21
Technical book
black ht
4Operating limits___________________ p.22
5 Pumps and exchanger data__________ p.23
6Cooling and heating capacity________ p.24
7Dimensional drawing_______________ p.31
5
STANDARD
UNIT
STRUCTURE
In galvanised sheet metal and painted at 180°C with
RAL7035 polyester powder, that gives high resistance
against atmospheric agents.
The panels can be easily removed for complete access to
the internal components. All structures are equipped with
two condensation collection trays with relative drain (one
for each coil).
COMPRESSOR
Technical book
Black ht
1
TECHNICAL
FEATURES
Semi-hermetic reciprocating compressor, complete with
thermal protection included in the windings of the electric motor, crankcase heater and rubber vibration damper
supports. The compressors used in this series are specifically designed to work in heat pump at very high temperatures. The optimisation of the high value compression ratio allows higher efficiencies if compared with traditional
scroll compressors. The compressor is cooled by a system
inside the unit. This cooling system allows an outlet water
temperature of 80°C.
INTERNAL EXCHANGER (SYSTEM SIDE)
Brazed plates made of
​​ AISI 316 stainless steel, insulated
with closed cell foam cladding that reduces heat loss and
prevents the formation of condensation. The exchanger is
equipped with a temperature probe for ice protection, a
probe for detecting the inlet and outlet water temperature
and a pallet flow switch supplied as standard.
EXTERNAL EXCHANGER (SOURCE SIDE)
6
Consists of two coils with copper pipes and high exchange surface aluminium finning with fin pitch dimensioned to maximise heat exchange and reduce noise. The
fin clearance of the exchanger was increased to allow the
unit to work at very low outdoor temperatures and at high
concentrations of humidity. At the base of the exchanger
is the subcooler, a further refrigerant circuit that prevents
the formation of ice in the lower part of the coil and facilitates the flow of condensation during defrosts. The effects
of the subcooler are: the reduction of number of defrosts
and the certainty of having a clean exchanger at the end
of defrost.
FANS
Helicoidal fan directly coupled with electric motor, made
of plastic with the blade profile with WINGLET, a special
mould in the end part of the blades that allows noise
reduction and an increase in ventilation performances.
The control manages the fan speed through a phase-cut
speed regulator, in order to optimise the operating conditions, efficiency, and allow the unit to work in heat pump,
even with high outdoor temperatures.
This adjustment also reduces the level of noise of the
unit, in fact, the typical conditions in which the control
will modulate the fan speed are the night-time and spring
and autumn. This ensures that, whenever there is the opportunity, the machine decreases the fan speed to minimum and, therefore, noise.
The fans are helicoidal type, directly coupled with 6-pole
electric motor, with IP 54 protection degree, with shaped
nozzles and accident prevention grille according to UNI
EN 294.
REFRIGERANT CIRCUIT
Includes:
>> inlet valve in the liquid and suction line
>> liquid and humidity warning light
>> solenoid valve
>> 4-way reverse valve
>> check valve
>> drier filter
>> electronic expansion valve
>> high pressure transducer
>> low pressure transducer
>> high and low pressure switches
>> safety valve
>> liquid receiver
>> suction separator
>> subcooler
The technical documentation can be improved all the times. Enerblue can update, time by time, all technical data in order to improve all necessary information for the customer.
ELECTRIC PANEL
The electric panel consists of:
>> main cut-out switch
>> Main circuit breaker and fuses to protect the auxiliary
and power circuits
>> compressor contactor
>> fan revolution regulator for condensation and evaporation control
>> contactor and pump overload cut-out (version 1P, 2P
and 1R)
>> general alarm dry contacts
>> microprocessor controller
The standard power supply is 400V/3~/50Hz for all sizes.
CONTROL
Microprocessor control for managing the following
functions:
>> Water temperature adjustment with inlet control
>> Ice protection
>> Compressor timing
>> High pressure pre-alarm management
>> Compressor high flow temperature alarm management
>> Alarm signal
>> Alarm reset
>> Digital input for external ON-OFF
>> Digital input for summer/winter selection
The control allows display of the following information:
>> Outlet water temperature
>> Inlet water temperature
>> Condensation pressure
>> Evaporation pressure
>> Outdoor air temperature
>> Set differential and temperature set
>> Description of alarms
>> Pump and compressor operation counter
>> Alarm history
Some functions are only available with the unit properly
configured. Some functions must be enabled from the
control.
CONTROLS AND SAFETY DEVICES
>> Utility water temperature control probe (located at exchanger inlet)
>> Antifreeze probe that activates the antifreeze alarm
(manual reset)
>> High pressure switch (automatic reset with limited
interventions)
>> Low pressure switch (automatic reset with limited
interventions)
>> Standard supplied mechanical pallet flow switch (manual reset)
>> Condensation pressure control via speed regulator for
operation with low outdoor temperatures
>> Evaporation pressure control via speed regulator for operation with high outdoor temperatures in DHW production or recovery
>> High pressure safety valve
>> Compressor over-temperature protection
Technical book
black ht
TESTING
The units are tested in both summer and winter operation at the factory and are despatched filled with oil and
coolant.
STANDARD EQUIPMENT
>> Sliding defrost management
>> Compressor stop for outdoor air temperature below
the operating limits
>> Main disconnecting device
>> Power and auxiliary circuit protection
>> Microprocessor control
>> Counter for compressors and pumps
>> Alarm History
>> Condensation and evaporation control with fan revolution regulator
>> Flow switch (supplied)
>> Directive 97/23/EEC (PED) Certification
>> Remote On/Off from standard digital input
>> Summer/Winter from standard digital input
The technical documentation can be improved all the times. Enerblue can update, time by time, all technical data in order to improve all necessary information for the customer.
1
TECHNICAL
FEATURES
7
OPTIONS
CONSTRUCTIVE CONFIGURATIONS
/LN Version
silenced unit
The unit, in addition to the basic version components,
includes the compressor compartment acoustically
insulated with sound-absorbing and soundproof material.
The choice of coupling of the materials has allowed the
removal of the frequencies generated by compressors
and pumps.
/OD Version
unit with horizontal discharge
(available up to size 75)
Technical book
Black ht
1
TECHNICAL
FEATURES
The unit in this version has horizontal air discharge. This
version allows reduction of the unit height or installation
where vertical discharge is not admitted for logistical
reasons or noise. If equipped with EC fan high pressure,
it is possible to convey the air flow for discharge through
ducts.
/DWS Version
multi-purpose heat pump
In this set-up, the unit is equipped with two utility
exchangers: one on the system side for air conditioning
and heating, and one exclusively for the production of
DHW.
A
C
S
C
H
O
O
L
T
D
On the system side exchanger, the unit is able to produce
hot or cold water to meet, depending on the seasons, the
heating and cooling requirements of the building. In the
sanitary exchanger, the unit produces high temperature
water to be sent to the storage tank outside the machine,
selected and dimensioned according to the system
requirements. Depending on the season, the unit works
with different modes: the passage through various modes
of operation (within the season) is automatic through the
reading of the temperature probes and of the set-points
set. Switching logics and times are designed to ensure
maximum system efficiency and reliability.
It is compulsory to associate this configuration to a suitably
sized boiler in which to store high temperature water; we
recommend a volume of at least 20÷25 l per thermal kW
of the unit. The boiler must be provided with sump for the
insertion of the DHW operating probe, located in the top
part, through which the unit controller monitors the need
to produce DHW.
8
The technical documentation can be improved all the times. Enerblue can update, time by time, all technical data in order to improve all necessary information for the customer.
SUMMER OPERATION
There are three summer modes of operation:
>> Chiller mode: the unit only produces chilled water for
the system.
>> Chiller mode with simultaneous production of
DHW: the unit produces chilled water for the system
and DHW, simultaneously. The recovered power for the
production of DHW is total.
>> Heat pump mode for the production of DHW:
without cold load and on call of the DHW operating
probe, the unit heats the water inside the DHW storage
tank, using the finned tube bundle coil as evaporator.
The use of the external hot air as a source of heat
ensures extremely high COP.
Switching from one mode to another is entirely automatic
based on a logic of priority in the production of DHW
and, when there is contemporaneity of loads, recovering
condensation energy for the production of DHW.
WINTER OPERATION
There are two winter modes of operation:
>> Heat pump mode for heating: the unit produces hot
water to system side exchanger for heating
>> Heat pump mode for the production of DHW:
produces high temperature hot water to the connected
exchanger of the DHW storage.
Switching from one mode to another is entirely automatic
based on a logic of priority in the production of DHW.
In addition to the basic version components, the /DWS
version includes:
>> dedicated exchanger for the production of DHW
>> recovery exchanger inlet and outlet probes
>> temperature probe to be placed on the DHW storage
tank.
HYDRAULIC MODULE OPTIONS
/1P
unit with pump
The unit includes a circulation pump on the unit. The
pump is centrifugal type, with body and impeller in AISI
304 steel. The mechanical seal is designed to work with
up to 40% concentration of ethylene glycol. The electric
motor is three-phase with IP 55 degree of protection. The
pump is complete with thermoformed insulating shell.
The different models available differ for useful head to
system.
/2P
unit with two pumps, one in reserve to the other
The unit includes two circulation pumps on the unit, one
in reserve to the other, managed in rotation on an hourly
basis and with automatic switching in case of failure. The
pump is of centrifugal type, with body and impeller in AISI
304 steel. The mechanical seal is designed to work with
up to 40% concentration of ethylene glycol. The electric
motor is three-phase with IP 55 degree of protection. The
pump is complete with thermoformed insulating shell.
The different models available differ for useful head to
system.
/1R
unit with DHW side pump
The unit is equipped with a DHW side pump installed
inside the unit.
The pump is centrifugal type, with body and impeller
in AISI 304 steel. The mechanical seal is designed to
work with up to 40% concentration of ethylene glycol.
The electric motor is three-phase with IP 55 degree of
protection. The pump is complete with thermoformed
insulating shell.
This module can be combined only with the /DWS version
units and can be combined with modules /1P or /2P. The
/DWS version units without the /1R module are equipped
with a consent for the management of an external pump.
The different models available differ for useful head to
system.
/S
unit with inertial tank
The unit is equipped with a inertial tank (only avaible
for utility and not for recovery side), installed inside the
unit. The tank is sized to improve the unit’s efficiency
and positioned on the system’s input. It is complete with
closed cell heat insulation to decrease heat losses. It is
compulsory to combine it with version /1P or /2P. The
different models available differ in capacity.
The technical documentation can be improved all the times. Enerblue can update, time by time, all technical data in order to improve all necessary information for the customer.
Technical book
black ht
1
TECHNICAL
FEATURES
9
ACCESSORIES
All units can be configured with various accessories to
better meet the requirements of the specific application
in which they will be inserted. To verify availability
and compatibility of the accessories with size and
configuration, refer to the price list or selection software.
HYDRAULIC CIRCUIT ACCESSORIES
>> Filling unit with pressure gauge supplied
>> Antifreeze heater
-- basic version: electric heater on utility exchanger
-- /1P, /2P and /1R version: electric heater on utility
exchanger and heating cable on piping
>> 3-way valve for DHW management (supplied)
>> System pump with Pulse function
>> Water filter for system
>> Water filter for DWS version
ELECTRIC ACCESSORIES
Technical book
Black ht
1
TECHNICAL
FEATURES
>> Maximum and minimum voltage relay
>> Double set-point from digital input
>> RS485 Serial interface
>> Remote user terminal
>> Electronic soft starter
>> EC Electronic fans
>> EC Electronic fans high pressure (up to size 75)
>> Compensation of set-point based on the outdoor air
temperature
>> DHW Automatic management
>> DHW operating probe (standard on /DWS unit)
>> Anti-legionella function
>> Auxiliary heat source management
>> DHW production with timer
>> Single operation dry contacts
>> Management relay for external pump
>> Miniboss S
>> Miniboss M
>> Supervision via WEB
VARIOUS ACCESSORIES
10
>> Rubber vibration dampers
>> Packaging in wooden crate
MAIN DESCRIPTION
FUNCTIONALITY/ACCESSORIES
Remote ON/OFF from digital input (standard)
Remote ON/OFF from digital input (standard). This function
is standard on all units and consists of a remote contact for
the switching on and off of the machine via a signal that
can be brought inside the building or controlled by a BMS
(Building Management System) system.
Summer/winter selection from digital input
(standard)
This function is standard on all heat pumps. When turning
on the unit, it is always necessary to set a mode of
operation that can either be heat pump or chiller. Through
this remote contact it is possible to change this mode of
operation also from inside the building and without the
need to directly access the microprocessor control.
Sliding defrosting (standard)
The control manages the defrost according to a variable
intervention threshold, based on the pressures inside
the unit and the outdoor air temperature. By crossreferencing this information, the control is able to identify
the presence of ice on the coil, activating the defrosting
sequence only when necessary, so as to maximise the
energy efficiency of the unit. The dynamic management
of the defrost threshold ensures that for outdoor air
temperatures below -5°C, when the absolute humidity of
the air is very low, defrosting is only carried out when the
ice on the coil degrades its performance.
Auxiliary heat source management
(accessory)
The controller is able to manage an external heat source
which, depending on the type of hydraulic connection,
can be integration or back-up. The auxiliary heat source
is activated when the outdoor air temperature falls below
a threshold settable from control and when only the
heat pump proves to be insufficient to meet the load.
Activation is through the closure of a dry contact.
It is also possible to set the unit so that the controller turns
off the compressors when the unit works in heat pump
mode and the outdoor air temperature falls below an
established minimum temperature: the controller stops
the compressors before the unit goes into low pressure
alarm, thus avoiding having to manually reactivate the
machine.
This function is particularly useful when the heat pump
is installed in an area where the outdoor air temperature
definitely falls below the minimum temperature admitted
by the operating limits (in agreement with the set-point
set). When the outdoor air temperature returns above the
set threshold temperature, the unit automatically starts
working again without the need for any intervention.
For units equipped with integrated pump, this will always
be kept running in order to avoid the formation of ice
and guarantee, at any moment, the correct reading of
the antifreeze safety and temperature probes. The stop
temperature must be set according to the highest setpoint temperature and in agreement with that admitted
by the operating limits of the machine. A stop temperature
The technical documentation can be improved all the times. Enerblue can update, time by time, all technical data in order to improve all necessary information for the customer.
can be set different to the default one, as long as it is
compatible with the unit’s operating limits. The standard
programming provides the set-point in heating set at
40/45° with a stop temperature of -20°C
Should the unit be used also for the production of DHW,
the stop temperature must consider the highest water
set, and the operating limits allowed.
DHW Automatic management (accessory)
The accessory is not compatible with accessory tank
(1PS e 2PS).
This feature allows the unit, through a DHW operation
probe (accessory), to control the temperature inside the
DHW storage tank and manage a 3-way valve (accessory)
outside the unit. The priority is always for the production
of DHW.
Activation of the function must be requested when
ordering, but it can also be configured subsequently (by
qualified and authorised technical personnel), as long as
the unit is connected to an appropriate hydraulic circuit.
The request when ordering accessories for managing
the DHW automatically involves enabling the “DHW
automatic management” function.
The heat pump normally operates on the system to meet
the building’s comfort needs, but when the temperature
of the water inside the tank drops below an established
threshold, the control manages the DHW production: if
the unit is operating as heat pump for heating, the 3-way
valve will be switched and the set-point modified; whereas,
if the unit is producing chilled water for air conditioning, the
control switches the unit to heat pump mode, assigns it the
set-point for DHW (normally higher than the system setpoint) and turns the 3-way valve to the appropriate position.
Once the temperature inside the DHW tank has reached the
set value, the unit automatically goes back to producing
water for the heating and air conditioning system.
Description of winter operation
The following situations occur during the winter season:
>> Heating request: the temperature of the inlet water
to the unit, coming from the system, is lower than
expected, so the control turns on the compressor and
the unit will operate until the set-point temperature is
reached.
Once the wanted temperature is reached, the compressor
stops and only the circulation pump remains in operation,
continuing to circulate water in the system. The unit waits
in this condition until the inlet water temperature drops
again.
DHW request: suppose that the unit is working for the
production of hot water for the heating system (45°C) and
it receives a call from the DHW operating probe located
inside the storage tank to produce high temperature
water, since the DHW temperature has dropped As the
set limit (e.g. 55°C). Being the DHW is managed with the
logic of priority, the control will change the set-point to
55°C and will switch the 3-way valve.
A
C
S
C
H
O
O
L
T
D
As soon as the water inside the tank reaches the requested
55°C, the control will again switch the 3-way valve to
operate on the system and will bring the set-point back
to 45°C.
Should it be necessary to defrost, in any mode the unit is
operating, it will force the 3-way valve to be switched to
system which, given the greater inertia, is less sensitive to
the lowering of the temperature.
Description of summer operation
The following situations occur during the summer season:
>> Cooling only: the temperature of the inlet water to the
unit, coming from the system, is higher than expected,
the control turns on the compressor and the unit will
operate until the set-point temperature is reached.
Technical book
black ht
1
TECHNICAL
FEATURES
A
C
S
11
C
H
O
O
L
T
D
A
C
S
C
H
O
O
L
T
D
The technical documentation can be improved all the times. Enerblue can update, time by time, all technical data in order to improve all necessary information for the customer.
At that point, the compressor stops and only the circulation
pump remains in operation, continuing to circulate water
in the system. The unit waits in this condition until the
inlet water temperature rises again.
>> DHW request: suppose that the unit is working for the
production of chilled water for the air conditioning
system (7°C) and it receives a call from the DHW
operating probe located inside the storage tank to
produce high temperature water, since the DHW
temperature has dropped below the set limit (e.g.
55°C). As the DHW is managed with the logic of priority,
the control will change the unit mode from chiller to
heat pump, set the set-point at 55°C and switch the
3-way valve.
A
C
S
C
H
O
O
L
T
D
Technical book
Black ht
As soon as the water inside the tank reaches the requested
55°C, the control will again switch the unit to chiller mode,
will turn the 3-way valve to operate on the system and will
bring the set-point back to 7°C.
TECHNICAL
FEATURES
Depending on the type of tank chosen for the production
of DHW, the management of anti-legionella cycles may
be necessary. The controller is able to manage them by
activating, according to scheduled timing with a weekly
timer, an auxiliary heat source that will perform the
thermal shock on the DHW tank.
The anti-legionella function is realised exclusively through
an external source (e.g. electric heater).
System pump with Pulse function (accessory)
As standard, the unit is set to maintain the system
side circulation pump always on, even when the set
temperature is reached. Whereas, when the unit is
equipped with this accessory, when the set-point is
reached, the controller turns off the pump, reactivating it
periodically, long enough to detect the water temperature.
If the controller verifies that the water temperature is still
in set-point conditions, it will turn off the pump again.
Otherwise, the controller re-activates the compressors
to meet the system requirements. This accessory allows
to drastically reduce the electric absorptions due to
pumping, especially during spring and autumn, when the
load is extremely low.
The application of this accessory requires the compulsory
presence of the “Antifreeze heaters” accessory.
DHW production with timer (accessory)
DHW operating probe (accessory)
1
Anti-legionella function (accessory)
For the production of DHW, the controller requires this
accessory: it is a temperature probe with 6 m cable located
in an appropriate sump of the tank for the production of
DHW. For proper positioning, read the “Advice for installing
a heat pump” section. Standard on units in DWS version.
With this accessory present, it will be possible to associate
two different temperatures for the DHW to different times
of the day: Normal and Saving. This allows you to decide
at what time of the day the heat pump must concentrate
the production of DHW, always keeping the minimum
level of Saving temperature, and always managed with
the logic of priority.
For example, by concentrating the production of water
at Normal temperature during night-time, the best
electricity rates will be exploited and production of DHW
will be ensured before the time of greater consumption.
12
With this system, the unit never stops controlling the
temperature inside the DHW tank and if hot water is
occasionally used outside the regular times, the unit will
give the production of DHW priority until it brings the
water in the tank to a temperature equal to the Saving
set-point.
The technical documentation can be improved all the times. Enerblue can update, time by time, all technical data in order to improve all necessary information for the customer.
Electronic thermostatic valve (standard)
MINIBOSS S (accessory)
Using this accessory is particularly suitable on units
having to operate in very variable heat load conditions,
with strong differences of outdoor air temperature or
with frequent change of operating mode, like in joint
management of air conditioning, heating and production
of high temperature water.
The use of the electronic thermostatic valve allows:
>> maximisation of the heat exchange to the utility
exchanger
>> minimisation of the response times of the refrigerant
circuit to the variations of the operating conditions and
load
>> optimisation of the superheat adjustment
>> maximisation of energy efficiency
The Miniboss S allows connection of up to 6 units in
parallel: management allows activation and deactivation
of them at power steps and makes them rotate, thus
allowing an identical use of all units.
The connected units must all be the same. The Miniboss
S cannot control units with the DHW management active.
Directly from the Miniboss S panel it is possible to manage:
>> the system set-point
>> the summer/winter selection of all machines
>> the ON/OFF of the single units or of the entire system
This accessory is supplied in an electrical panel with
the unit (to be installed in a technical compartment);
it must be provided on only one machine connected
in parallel and all connected units must have the same
configuration. When ordering, it is compulsory to
specify the number of units that must be managed
to allow for proper programming of the supervisor.
Furthermore, the hydraulic circuit connecting the units
must compulsorily respect one of the following diagrams.
For more information on the use, refer to the specific
documentation.
MINIBOSS M (accessory)
The Miniboss M allows management of up to 4 units in
parallel. The main functions are:
>> Manage units with DWS configurations
>> Manage systems with a hot/cold tank for heating/air
conditioning and a hot tank for the production of DHW
EC Fans (accessory)
The units can be requested with EC fans, with electronic
switching brushless motor. These motors with permanent
magnet rotor ensure very high levels of efficiency for
each working condition and allow a 15% saving on the
power absorbed by each fan.
Furthermore, the microprocessor, through a 0-10V
analogue signal sent to each fan, controls the
condensation/evaporation
through
continuous
adjustment of the air flow rate upon variation of the
outdoor air temperature, with a further decrease of
electric absorptions and a reduction of sound emissions.
In addition to that also carried out by the Miniboss S:
>> the system set-point
>> the DHW set-point
>> use a compensation climate of the system set-point
>> the summer/winter selection of all machines
>> the ON/OFF of the single units or of the entire system
>> the switching of three-way valves
>> manage the operation of pumps outside the units
This accessory is supplied in an electrical panel with the
unit (to be installed in a technical compartment), it must
be provided on only one machine connected in parallel
and all connected units must have the same configuration.
When ordering, it is compulsory to specify the number
of units that must be managed to allow for proper
programming of the supervisor. For more information on
the use, refer to the specific documentation.
Filling unit with pressure gauge (accessory)
This accessory allows automatic loading of the hydraulic
system, adjustment of the correct working pressure,
always verifiable through the pressure gauge, and
continuously maintains this pressure by reintegrating the
missing water.
The technical documentation can be improved all the times. Enerblue can update, time by time, all technical data in order to improve all necessary information for the customer.
Technical book
black ht
1
TECHNICAL
FEATURES
13
Antifreeze heater (accessory)
Remote user terminal (accessory)
This accessory consists in heaters inserted on the utility
exchanger, on the pump and in the tank (based on
the machine configuration) to prevent damaging the
hydraulic components following the formation of ice
during machine downtime. The power of the antifreeze
heaters is only of a few tens of watts, depending on the
unit model, meaning sufficient enough to avoid failure of
the components. The control monitors (even when the
unit is in stand-by) the outlet pump from the exchanger
and when this detects a water temperature below or
equal to 5°C (or 2°C below set-point temperature, with
differential of 1°C), it turns on the pump (if present) and
makes the antifreeze heaters intervene.
If the outlet water temperature reaches 4°C (or 3°C below
set-point), the antifreeze alarm will also trigger, stopping
the compressor, keeping the heaters active. The antifreeze
heaters are present in the evaporator and on any recovery
exchangers.
This accessory consists in a copy of the remote control
panel, from where it is possible to fully configure the unit
and display all its parameters. Access to the masks is via
passwords that enable the different levels of modification.
Double set-point from digital input
(accessory)
Technical book
Black ht
The double set-point allows two different working
temperatures to be set: one for heating operation and
one for cooling operation. Should a double set-point
be required for both modes, it will be compulsory to
provide the electronic thermostatic valve. The set-point
temperatures must be specified when ordering. The setpoint can be changed from keyboard or from digital input.
RS485 Serial interface (accessory)
1
TECHNICAL
FEATURES
The growing diffusion of home automation systems and
BMS (Building Management System) has led to the need to
integrate all plant components under a single supervision.
To meet this requirement, the unit can be equipped with
a RS485 serial board with MODBUS protocol.
DHW 3-way valve (accessory)
The accessory is not compatible with accessory tank
(1PS e 2PS).
It is an on/off type three-way valve that, combined with
the automatic management of DHW function, allows the
machine to manage two separate circuits for comfort
and DHW production, automatically switching from one
to the other based on the system need. The DHW 3-way
valve must be installed in a technical compartment.
Compensation of set-point depending on the
outdoor temperature (accessory)
The controller allows modification of the unit set-point
both in chiller operation and in heat pump, depending on
the outdoor temperature. Compensation can be positive
or negative: with positive compensation, upon outdoor air
temperature increase, the summer temperature set-point
will also increase, while with the negative compensation,
upon air temperature increase, the temperature set-point
decreases. Should the unit be used also for the production
of DHW, the adjustment climate will not affect the DHW
temperature set-point.
Maximum and minimum voltage relay
(accessory)
This device continuously controls the unit’s power
supply voltage, ensuring it is always within an admissible
range. Should the voltage value be above or below that
range, the device stops the unit to avoid damaging the
electric motors. The same device also controls the phase
sequence.
14
The technical documentation can be improved all the times. Enerblue can update, time by time, all technical data in order to improve all necessary information for the customer.
Condensation/evaporation control with
revolution regulator (standard)
The microprocessor control of the unit controls all
operating parameters of the unit and continuously adjusts
the speed of the fans through a revolution regulator,
in order to optimise the operating conditions and the
efficiency of the unit.
This adjustment also reduces the level of noise of the
unit, in fact, the typical conditions in which the control
will modulate the fan speed are the night-time and spring
and autumn. This ensures that, whenever there is the
opportunity, the machine decreases the fan speed to
minimum and, therefore, noise.
Water filter (accessory)
The water filter, located at the unit’s water inlet, aims at
preventing sludge, processing residues or other, from
clogging the unit exchangers. It is compulsory that at the
inlet of each circuit: source, utility and recovery, there is a
filter with a 0.4 or 0.5 mm mesh. The absence of the filter
automatically voids the warranty.
Condensing drain pan (standard)
This accessory is compulsory when installed in a
passageway. This is a drain pan used during winter mode
(heat pump functions) to contain the water coming from
the coil (also during defrost operating). This is standard on
all products.
Web supervision (accessory)
The units can be remotely managed in 2 different ways:
>> via web through LAN
>> via web through modem and telephone board
(integrated in supervision)
The unit can be controlled totally through the connection.
The display possibilities are:
>> Inlet water temperature
>> Outlet water temperature
>> Air temperature
>> Condensation pressure
>> Evaporation pressure
>> Status of the unit
>> Presence of alarms
>> Compressor operation
>> Pump operation
>> Fan operation percentage
The modification possibilities are:
>> Power on and off of the unit
>> Switching of status: summer/winter or vice-versa
>> Reset of alarms. All unit alarms can be reset without
physically reaching the installation
>> Modification of all set-points
>> Modification of climates
It is also possible to view a history of the operation of all
variables (temperatures and pressures) detected by the
control. This allows a view of the effective behaviour of
the unit and of the system.
This function is essential to correctly set the system.
Relay for outdoor pump management
If the unit is purchased without pumps, the customer
is entrusted with the start and stop of the pump in
accordance with the instructions in the installation,
operation and maintenance manual. This accessory
is necessary if the unit needs to control one or more
external pumps. It allows control of an external pump
with the same logic as a pump integrated in the unit.
The accessory consists in the supply of a dry contact only
usable for controlling the start and stop. The customer is
responsible for the protection and power.
The technical documentation can be improved all the times. Enerblue can update, time by time, all technical data in order to improve all necessary information for the customer.
Technical book
black ht
1
TECHNICAL
FEATURES
15
RECOMMENDATIONS FOR INSTALLATION
The following instructions are intended to improve use
of the heat pumps in systems and to prevent installation
problems.
1.Heat Pumps are often combined with radiant heating
systems. If the radiant system is in areas with control
of the individual manifold head, it is compulsory to
provide at least 20 litres of water per kW of heat yield
of the unit, in condition of minimum water content,
or with all heads closed. This is necessary because it is
possible that a situation arises where almost all heads
are closed and the heat pump works with an extremely
reduced water volume. In this case, during defrosting,
it is possible that the safety devices intervene due to
excessive cooling of the water.
2.In the DWS version or with use of the “DHW automatic
management” function, it is compulsory to work the
recovery exchanger on technical water and not on
pipe coil. In fact, the coupling of heat pumps with pipe
coils has repeatedly proven to be a problem due to an
incorrect dimensioning of the pipe coil surface.
Technical book
Black ht
1
TECHNICAL
FEATURES
16
3.In the DWS version or with use of the “DHW automatic
management” function, installation of the temperature
probe supplied is essential. The DHW storage tank must
have a sump in its top part, long enough to reach almost
the centre of the tank. The probe supplied with the unit
must be inserted in the sump with conductive paste
in order to allow the probe to accurately read the tank
temperature. The incorrect reading of the temperature,
caused by an unsuitable positioning, may lead to the
intervention of the safety devices or blocking of the
unit.
4.
When using the “DHW automatic management”
logic, it is necessary to use a three-way valve which,
during switching, allows the water to flow and never
presents the situation of blocked or reduced flow.
The Installation, Operation and Maintenance Manual
contains guidelines for selecting the valve.
5.The possible integration of water from the aqueduct
must never be inserted in the inlet piping of the heat
pump. The cold water made to abruptly enter the “hot”
exchanger may cause the safety devices to intervene. If
using a tank, the inlet of the water integration from the
aqueduct must not directly flow in the inlet piping of
the heat pump.
6.For the following reasons, it is not advisable to position
the unit set-points on the operating limits:
a.Modification of the room temperature. The room
temperature varies and may lead the unit to work
outside the limits.
b.Presence of the water filter. The water filter must
always be present at the unit’s water inlet, under
penalty of voiding the warranty. The filter will
certainly get dirty over time. A dirty filter will increase
load losses and consequently the flow rate. The DT
increases and can go from 4/5° to 9°, 10°, causing the
safety devices to intervene.
c.If the hydraulic circuit provides more areas, it may
happen that when a circuit closes the pump has
to operate on the remaining hydraulic circuit. This
increases the load losses, decreases the flow rate and
increases the DT with possible intervention of the
safety devices.
d.In summer, the unit will be subject to solar radiation.
Assuming air at 35°, the coil (in copper and
aluminium, so very good conductor) will be at a very
high temperature. When turning on the unit, even
with fans at stand-still, the evaporation will be very
high thus certainly producing the intervention of the
high pressure switch.
e.Recirculation of air can create a micro-environment
with a lower temperature of even 4/5°, leading the
unit to operate outside the limits.
f.Clearances are very important, the upstream or
downstream obstruction of the fan causes load
losses that reduce the air flow rate. This reduction
may cause the operating temperatures to drop. This
drop may cause the unit to be outside the operating
limits.
g.Air in the circuit. The air in the system, even if wellvented, creates a heat exchange coefficient loss
with possible consequential intervention of the high
pressure safety devices.
The technical documentation can be improved all the times. Enerblue can update, time by time, all technical data in order to improve all necessary information for the customer.
7.Use of unit to dry the screed. When building a house
large amounts of water are used for the mortar, plaster,
screed, which then evaporate from the building very
slowly. Also, rain may significantly increase the humidity
content of the construction. Due to the high humidity
content in the whole building, during the first two
heating periods, the heat requirement of the building
is much higher. The masonry work must be dried using
special equipment. If the heat power of the heat pump
was calculated to be sufficient for the home and drying
takes place in the autumn or winter, we recommend
installing an additional electric heater to compensate
the higher heat requirement.
8.Starting the system with low outdoor temperatures.
The safety devices may intervene when starting the
system during winter, with the temperature of the
system water particularly cold and outside the unit’s
operating limits. To bring the system up to speed, just
reduce the heat load by isolating part of the system.
When the temperature of the partial system water is
within the operating limits, it will be possible to also
connect the previously isolated part of the system.
9.During defrosting, the unit cools the system water in
order to eliminate the ice in the coil. To eliminate any
problem, it is appropriate to insert a storage of at least
20÷25 litres of water per thermal kW of the unit.
ACOUSTIC ASPECTS FOR THE INSTALLATION
For proper unit installation, keep the following in mind:
>> Installation of the unit near walls or other creates reverberation phenomena that increase the input of noise in
the environment, even by 16 dBA
>> Bear in mind the possible sensitive receptors when installing the unit; avoid installing units near bedrooms
>> Check the noise regulation of the municipality where
the unit will be installed to verify its absolute and differential limit
>> Bear in mind that, regardless of the acoustic class of the
territory (Italian Prime Ministerial Decree 14 November
1997), there is a differential day and night-time criterion
>> In the event of critical installations, contact a Competent
Technician in Acoustics for a preliminary evaluation
Italian Prime Ministerial Decree 14 November 1997
The Italian Prime Ministerial Decree 14/11/97, which entered into force on 1st January 1998, determines the limit
values of the sound sources, in particular it sets:
>> Emission limit values maximum noise that can be
emitted by a source;
>> Input limit values maximum noise that can be input by one or more sound sources in the house or in
the external environment, divided into absolute and
differential;
>> Attention values of noise that signal the presence of a
potential risk to health or for the environment;
>> Quality values of noise to achieve as a target in the
short-, medium- and long-term.
The Italian Prime Ministerial Decree 14/11/97, like the
Italian Prime Ministerial Decree 1/3/91, sets the absolute
input limits for the outdoor environment for all types of
sources. The decree also defines the limit values of emissions to be understood as “emission levels for a specific
source evaluated at the receiver”. These values, with the
exception of the transport infrastructures, must be complied with by all sound sources. The limit values are set by
acoustically dividing the territory in six classes. In particular, it is very important to know the “differential criterion”
present and described in the decree. It is this criterion
that most technicians do not know and which is the most
restrictive.
DIFFERENTIAL CRITERION
The differential noise level is the difference between the
ambient noise level (i.e. that present when the noise
source causing the disturbance is in operation) and the
residual noise level (i.e. background noise). The differential
noise level must not exceed the following input differential limit values (art. 4, comma 1 of Italian Prime Ministerial
Decree 14/11/97):
>> 5 dB(A) for the daytime period (from 6.00-to 22.00)
>> 3 dB(A) for the night-time period (from 22.00-to 6.00)
The technical documentation can be improved all the times. Enerblue can update, time by time, all technical data in order to improve all necessary information for the customer.
Technical book
black ht
1
TECHNICAL
FEATURES
17
ETHYLENE GLYCOL CORRECTIVE COEFFICIENTS
Correction factors for the presence of Ethylene Glycol
5%
10%
15%
20%
25%
30%
35%
40%
Freezing temperature
ETHYLENE GLYCOL % IN WEIGHT
°C
-2,0
-3,9
-6,5
-8,9
-11,8
-15,6
-19
-23,4
Safety temperature
°C
3,0
1,0
-1,0
-4,0
-6,0
-10,0
-14,0
-19,0
Cooling Power Coefficient
-
0,995
0,990
0,985
0,981
0,977
0,974
0,971
0,968
Absorbed Power Coefficient
-
0,997
0,993
0,990
0,988
0,986
0,984
0,982
0,981
Mass flow rate coefficient
-
1,003
1,010
1,020
1,033
1,050
1,072
1,095
1,124
Load losses coefficient
-
1,029
1,060
1,090
1,118
1,149
1,182
1,211
1,243
The maximum admitted percentage of glycol per standard unit is 40%. For higher values, contact the sales department.
PERFORMANCE ACCORDING TO EN14511 STANDARD
Data is provided according to the requirements of EN14511.
This set of rules redefines the method for calculating the performances of the heat pump chillers.
According to EN14511-2011, on the unit performance calculation, also add the power required to overcome the hydronic
load losses of the circuit.
Method of calculation of the performance as follows.
P cooling= P cooling - P abs.Δp
Technical book
EN14511
Black ht
P heating= P heating + P abs.Δp
EN14511
1
TECHNICAL
FEATURES
P abs = P abs + P abs.Δp
EN14511
P cooling
EN14511
EER EN14511 = —————
P abs
EN14511
P heating
EN14511
18
COP EN14511 = —————
P abs
EN14511
ESEER EN14511 = 0.003 x EER 100% + 0.33 x EER 75% + 0.41 x EER 50% + 0.23 x EER 25%
EN14511
EN14511
EN14511
EN14511
With:
Pcooling : cooling power
Pheating : heating power
Pcooling , Pheating , EEREN14511, COPEN14511, ESEEREN14511 : data provided in compliance with EN14511
EN14511
EN14511
Pabs : electric power absorbed (compressors and fan section) [ kW ]
Pabs.Δp : electric power absorbed by the pump to overcome load losses of water in the heat exchanger
The technical documentation can be improved all the times. Enerblue can update, time by time, all technical data in order to improve all necessary information for the customer.
TECHNICAL DATA
UNIT SIZE
Heating (EN 14511 values)
Nominal heating capacity
Total Power input in heating mode
COP
Efficiency class
SCOP
Seasonal Efficiency class
Heating (EN 14511 values)
Nominal heating capacity
Total Power input in heating mode
COP
Cooling (EN 14511 values)
Nominal cooling capacity
Total Power input in cooling mode
EER
ESEER
Efficiency class
Compressor
Type
Quantity/Refrigerant circuits
Capacity steps
Total oil charge
Total refrigerant charge
Fans
Type - axial
Quantity
Air flow
Utility side exchanger
Type
Water content
Water flow rate (A35/W7)
Pressure drop (A35/W7)
Water flow rate (A7/W75)
Pressure drop (A7/W75)
Water flow rate (A7/W45)
Pressure drop (A7/W45)
Hydraulic module
Available pump pressure
Nominal Power input of pump
Available pump pressure (A35/W7)
Available pump pressure (A7/W45)
Storage tank capacity
Expansion vessel
Hydraulic connection
Connection
Sound level STD version
Sound power value
Sound pressure value
Sound level LN version
Sound power value
Sound pressure value
Basic unit size and weights
(1), (7)
kW
(1), (2), (7)
kW
(1), (7)
(9)
(9)
(8)
kW
(2), (8)
kW
(8)
(3), (7)
kW
(3), (2), (7)
kW
(3), (7)
n° / n°
n°
kg
kg
40
45
55
65
75
90
33,6
10,7
3,22
A
3,42
A+
40,3
12,6
3,30
A
3,45
A+
51,0
15,3
3,41
A
3,58
A+
59,2
16,3
3,44
A
4,02
A++
71,7
22,0
3,08
B
3,62
A+
84,9
25,3
3,13
B
3,75
A+
25,3
12,5
2,03
30,5
14,3
2,13
36,4
16,7
2,18
45,8
19,8
2,32
54,6
25,9
2,11
63,1
29,4
2,15
32,0
10,7
2,98
3,52
B
36,8
13,5
2,72
3,14
C
46,8
17,0
2,76
3,11
C
56,3
18,8
3,00
3,37
B
62,5
22,6
2,76
3,26
C
74,3
27,1
2,74
3,26
C
1/1
2
4,0
11,3
1/1
2
4,5
13,5
Reciprocating
1/1
1/1
2
2
4,8
4,8
17,1
19,8
1/1
2
4,8
24,1
1/1
2
4,8
28,5
1
21.000
1
21.000
1
20.000
1
20.000
2
40.000
2
40.000
2,3
5.524
17
4.239
9
5.840
19
2,7
6.353
18
5.245
10
6.954
21
Plate exchanger
3,4
4,0
8.083
9.715
18
21
5.721
6.932
8
10
8.803
10.212
21
24
4,8
10.794
23
8.409
11
12.456
31
5,7
12.822
16
9.527
7
14.682
21
P1
1,1
184
181
-
P1
1,1
181
176
-
P1
1,1
177
171
-
P1
1,1
168
164
-
P2
2,5
192
182
200
18
P2
2,5
196
186
200
18
1" 1/2
1" 1/2
1" 1/2
1" 1/2
2"
2"
83
55
83
55
84
56
85
57
86
58
86
58
Axial
n°
m3/h
l
(3)
l/h
(3)
kPa
(8)
l/h
(8)
kPa
(1)
l/h
(1)
kPa
kW
(3)
kPa
(1)
kPa
l
l
(4), (6)
dB(A)
(5), (6)
dB(A)
(4), (6)
dB(A)
(5), (6)
dB(A)
81
53
81
53
82
54
83
55
84
56
84
56
Width
mm
1.408
1.408
1.408
1.408
3.508
3.508
Depth
mm
1.208
1.208
1.208
1.208
1.208
1.208
Height
mm
2.390
2.390
2.390
2.390
1.912
1.912
Delivery weight
kg
585
592
630
648
1.017
1.142
Operating weight
kg
590
597
637
656
1.027
1.152
(1) External air temperature 7°C BS, 6°C BU, Inlet-outlet water 40-45 °C
(2) Total power input is sum of compressors and funs power input and pump, according with EN 14511
(3) External air temperature 35°C, Inlet-outlet water 12-7°C .
(4) Sound power level calculate in compliance with ISO 3744
(5) Sound pressure level calculate in compliance with ISO 3744
(6) External air temperature 35°C, Inlet-outlet water 12-7°C .
(7) Values calculate in compliance with EN 14511
(8) External air temperature 7°C BS, 6°C BU, Inlet-outlet water 70-75 °C
(9) according to European Regulation n° 813/2013
This datasheet gives the characteristic data of the basic and standard versions of the series; for details refer to the specific documentation
The technical documentation can be improved all the times. Enerblue can update, time by time, all technical data in order to improve all necessary information for the customer.
Technical book
black ht
2
TECHNICAL DATA
19
TECHNICAL DATA
UNIT SIZE
Technical book
Black ht
2
TECHNICAL DATA
20
Heating (EN 14511 values)
Nominal heating capacity
Total Power input in heating mode
COP
Efficiency class
SCOP
Seasonal Efficiency class
Heating (EN 14511 values)
Nominal heating capacity
Total Power input in heating mode
COP
Cooling (EN 14511 values)
Nominal cooling capacity
Total Power input in cooling mode
EER
ESEER
Efficiency class
Compressor
Type
Quantity/Refrigerant circuits
Capacity steps
Total oil charge
Total refrigerant charge
Fans
Type - axial
Quantity
Air flow
Utility side exchanger
Type
Water content
Water flow rate (A35/W7)
Pressure drop (A35/W7)
Water flow rate (A7/W75)
Pressure drop (A7/W75)
Water flow rate (A7/W45)
Pressure drop (A7/W45)
Hydraulic module
Available pump pressure
Nominal Power input of pump
Available pump pressure (A35/W7)
Available pump pressure (A7/W45)
Storage tank capacity
Expansion vessel
Hydraulic connection
Connection
Sound level
Sound power value
Sound pressure value
Sound level
Sound power value
Sound pressure value
Basic unit size and weights
(1), (7)
kW
(1), (2), (7)
kW
(1), (7)
(9)
(9)
(8)
kW
(2), (8)
kW
(8)
(3), (7)
kW
(3), (2), (7)
kW
(3), (7)
n° / n°
n°
kg
kg
n°
m3/h
l
(3)
l/h
(3)
kPa
(8)
l/h
(8)
kPa
(1)
l/h
(1)
kPa
kW
(3)
kPa
(1)
kPa
l
l
70
85
105
125
145
180
200
235
68,8
21,0
3,33
A
3,50
A+
81,5
25,7
3,24
A
3,40
A+
103,8
32,0
3,29
A
3,48
A+
120,1
32,9
3,31
A
4,00
A++
143,0
42,3
3,14
B
3,74
A+
171,2
50,6
3,24
A
3,78
A+
202,3
61,9
3,29
A
3,63
A+
234,4
71,4
3,31
A
3,63
A+
51,8
24,4
2,12
61,0
29,1
2,09
74,2
35,1
2,11
93,0
40,1
2,32
110,1
50,7
2,17
128,2
59,5
2,15
150,6
70,8
2,13
182,6
86,7
2,11
61,4
21,4
2,87
3,22
C
71,3
25,9
2,75
3,12
C
90,6
32,3
2,80
3,17
C
100,7
34,6
2,91
3,29
B
120,9
44,6
2,71
3,17
C
145,2
52,3
2,78
3,17
C
173,8
65,2
2,66
3,06
D
201,1
78,0
2,58
3,00
D
2/2
4
8,0
23,1
2/2
4
9,0
27,5
2/2
4
9,5
34,8
Reciprocating
2/2
2/2
4
4
9,5
9,5
40,4
48,3
2/2
4
9,5
56,9
2/2
4
14,8
67,2
2/2
4
10,0
77,9
2
40.000
2
40.000
2
40.000
Axial
2
3
40.000
60.000
3
60.000
4
80.000
4
80.000
4,6
10.581
13
8.478
7
11.914
16
5,5
12.291
16
10.490
9
14.187
22
7,0
15.630
15
11.443
6
17.958
20
Plate exchanger
8,1
9,7
17.352
20.843
14
15
13.864
16.819
6
7
20.832
24.912
20
22
11,4
25.039
19
21.685
10
29.363
26
13,4
29.957
20
24.583
10
34.686
26
15,6
34.669
20
29.848
11
40.189
28
P2
2,5
202
197
200
18
P2
2,5
197
187
200
18
P2
2,5
189
176
200
18
P2
2,5
184
164
200
18
P3
3,0
190
179
400
18
P3
3,0
182
169
400
18
P3
3,0
174
159
400
18
P3
3,0
165
145
400
18
2" 1/2
2" 1/2
2" 1/2
2" 1/2
2" 1/2
2" 1/2
3"
3"
87
59
87
59
88
60
88
60
89
61
89
61
93
65
93
65
(4), (6)
dB(A)
(5), (6)
dB(A)
(4), (6)
dB(A)
(5), (6)
dB(A)
85
57
85
57
86
58
86
58
87
59
87
59
91
63
91
63
Width
mm
3.508
3.508
3.508
3.508
4.608
4.608
5.330
5.330
Depth
mm
1.208
1.208
1.208
1.208
1.208
1.208
1.208
1.208
Height
mm
1.912
1.912
1.912
1.912
1.912
1.912
1.912
1.912
Delivery weight
kg
1.323
1.505
1.539
1.541
1.744
1.759
2.099
2.268
Operating weight
kg
1.334
1.516
1.550
1.552
1.758
1.773
2.114
2.284
(1) External air temperature 7°C BS, 6°C BU, Inlet-outlet water 40-45 °C
(2) Total power input is sum of compressors and funs power input and pump, according with EN 14511
(3) External air temperature 35°C, Inlet-outlet water 12-7°C .
(4) Sound power level calculate in compliance with ISO 3744
(5) Sound pressure level calculate in compliance with ISO 3744
(6) External air temperature 35°C, Inlet-outlet water 12-7°C .
(7) Values calculate in compliance with EN 14511
(8) External air temperature 7°C BS, 6°C BU, Inlet-outlet water 70-75 °C
(9) according to European Regulation n° 813/2013
This datasheet gives the characteristic data of the basic and standard versions of the series; for details refer to the specific documentation
The technical documentation can be improved all the times. Enerblue can update, time by time, all technical data in order to improve all necessary information for the customer.
ELECTRICAL DATA
UNIT SIZE
40
45
55
65
75
90
Maximum absorbed
power
22,6
26,6
31,6
37,6
45,2
54,2
(23,7)
(27,7)
(32,7)
(38,7)
(47,7)
(56,7)
41,1
47,9
57,1
68,3
81,7
104,0
(43,8)
(50,6)
(59,8)
(71,0)
(86,2)
(108,5)
Maximum starting
current
Full load current
(1),(3)
kW
(2),(3)
A
(4)
A
104,8
132,8
172,8
172,8
234,6
241,6
(62,9)
(79,7)
(103,7)
(103,7)
(140,8)
(145,0)
Fan motor nominal
power
n° x kW
1 x 1,6
1 x 1,6
1 x 1,6
1 x 1,6
2 x 1,6
2 x 1,6
Fan motor nominal
absorbed current
n° x A
1 x 3,9
1 x 3,9
1 x 3,9
1 x 3,9
2 x 3,9
2 x 3,9
Pump motor
nominal power
kW
1,10
1,10
1,10
1,10
2,45
2,45
Pump motor
nominal current
A
2,70
2,70
2,70
2,70
4,53
4,53
Power supply
V/ph/Hz
400/3N~/50 ±5%
Power supply
V/ph/Hz
230/1~/50 ±5%
UNIT SIZE
70
85
105
125
145
180
200
235
Maximum absorbed
power
45,2
53,2
63,2
75,2
88,8
106,8
198,4
162,4
(47,7)
(55,7)
(65,7)
(77,7)
(91,8)
(109,8)
(201,4)
(165,4)
82,2
95,8
114,2
136,6
159,5
204,1
358,0
293,6
(86,7)
(100,3)
(118,7)
(141,1)
(165,9)
(210,5)
(364,4)
(300,0)
142,0
176,8
226,0
237,2
304,6
333,9
481,0
555,6
Maximum starting
current
Full load current
(1),(3)
kW
(2),(3)
A
(4)
A
(85,2)
(106,1)
(135,6)
(142,3)
(182,8)
(200,3)
(288,6)
(333,4)
n° x kW
2 x 1,6
2 x 1,6
2 x 1,6
2 x 1,6
3 x 1,6
3 x 1,6
4 x 1,6
4 x 1,6
n° x A
2 x 3,9
2 x 3,9
2 x 3,9
2 x 3,9
3 x 3,9
3 x 3,9
4 x 3,9
4 x 3,9
Pump motor
nominal power
kW
2,45
2,45
2,45
2,45
3,00
3,00
3,00
3,00
Pump motor
nominal current
A
4,53
4,53
4,53
4,53
6,35
6,35
6,35
6,35
Fan motor nominal
power
Fan motor nominal
absorbed current
Power supply
V/ph/Hz
400/3N~/50 ±5%
Power supply
V/ph/Hz
230/1~/50 ±5%
Technical book
black ht
3
ELECTRICAL
DATA
21
Notes
>> Voltage unbalance: max 2%
>> “The standard power supply voltage (see specific wiring diagram) must not vary by more than ±5%”
>> Electric data refers to standard unit. Data may change based on the installed accessories
(1) Mains power supply to allow unit operation
(2) Maximum current before safety cut-outs stop the unit. This value is never exceeded and must be used to size the electrical supply cables and relevant safety devices (refer to electrical
wiring diagram supplied with the unit).
(3) alues in brackets refer to ST version units (units with storage tank and pumps or units with exclusively pumps)
(4) Maximum starting current calculated considering the bigger size compressor starting current plus the maximum absorbed power of the other electrical devices (pumps, fans)
The technical documentation can be improved all the times. Enerblue can update, time by time, all technical data in order to improve all necessary information for the customer.
OPERATION LIMITS
OPERATION IN COOLING
Utility water outlet temperature [°C]
Raffreddamento
25
20
15
10
5
➀
0
-5
-10
-15
-10
-5
0
5
10
15
20
25
30
35
40
45
50
External air temperature [°C]
Notes
>> The thermal head to the utility side exchange must be between 3°C and 6°C
>> ➀ : in this area the unit can only work with evaporator side glycoled water
>> Operating outside the operating limits may cause the safety devices to intervene or serious malfunctions
>> Within the operating limits, the fan section may be subject to modulation
Utility water outlet temperature [°C]
HEATING AND RECOVERY OPERATION
HT VERSION
Riscaldamento
e Recupero
Technical book
Black ht
4
OPERATION
LIMITS
Notes
85
75
65
55
45
35
25
-25
-20
-15
-10
-5
0
5
10
15
20
25
30
35
40
45
50
External air temperature [°C]
>> The thermal head to the utility side exchange must be between 3°C and 6°C
>> Operating outside the operating limits may cause the safety devices to intervene or serious malfunctions
>> The temperature of inlet water to utility side exchanger cannot be less than 25°C
>> ■ The unit can work within this field but NOT CONTINUOUSLY
>> Within the operating limits, the fan section may be subject to modulation
>> Within the operating limits, to limit the flow temperature, the unit may be subject to choking
22
The technical documentation can be improved all the times. Enerblue can update, time by time, all technical data in order to improve all necessary information for the customer.
PRESSURE DROP DIAGRAM
80
40
45
Pressure drop Diagram
55 65
70 85
75
105
90
Plate exchanger Pressure Drop [kPa]
70
125
145
60
180
50
200
40
235
30
20
10
0
3000
6000
9000 12000 15000 18000 21000 24000 27000 30000 33000 36000 39000 42000 45000
Flow rate [l/h]
Technical book
black ht
5
AVAILABLE PRESSURE DIAGRAM
220
85
210
40
200
EXCHANGER
DATA
90
190
Available Pressure [kPa]
180
45
170
160
105
70
150
140
200
125
235
130
145
55
120
110
180
75
100
90
65
80
70
60
50
3000
6000
9000
12000 15000 18000 21000 24000 27000 30000 33000 36000 39000 42000 45000
Flow rate [l/h]
The technical documentation can be improved all the times. Enerblue can update, time by time, all technical data in order to improve all necessary information for the customer.
23
COOLING CAPACITY
Ta [°C]
40
25
30
35
40
45
To
[°C]
KWF
kWe
EER
KWF
kWe
EER
KWF
kWe
EER
KWF
kWe
EER
KWF
kWe
EER
10/5
33,2
9,3
3,6
32,6
10,1
3,2
30,6
10,4
2,9
28,7
10,9
2,6
27,0
11,3
2,4
11/6
35,6
9,8
3,6
33,2
10,2
3,3
31,6
10,7
3,0
29,6
11,1
2,7
27,8
11,5
2,4
12/7
35,6
9,7
3,7
35,3
10,5
3,4
32,0
10,7
3,0
31,6
11,5
2,7
28,9
11,8
2,5
13/8
36,6
9,8
3,7
35,3
10,5
3,4
33,9
11,0
3,1
31,9
11,6
2,8
28,9
11,8
2,4
14/9
38,2
10,1
3,8
36,5
10,7
3,4
34,6
11,2
3,1
32,5
11,8
2,8
30,7
12,3
2,5
15/10
38,6
10,3
3,8
37,5
10,8
3,5
36,3
11,6
3,1
33,7
12,0
2,8
31,9
12,5
2,5
17/12
41,8
10,6
3,9
39,8
11,3
3,5
38,4
12,0
3,2
35,9
12,5
2,9
33,1
12,8
2,6
19/14
44,4
11,0
4,0
42,9
11,8
3,6
40,4
12,4
3,3
38,4
12,9
3,0
34,8
13,3
2,6
21/16
45,9
11,2
4,1
45,9
12,2
3,8
43,4
12,8
3,4
40,6
13,5
3,0
37,7
13,9
2,7
23/18
49,7
11,6
4,3
47,8
12,4
3,9
47,3
13,4
3,5
44,0
14,1
3,1
-
-
-
10/5
39,9
12,1
3,3
37,0
12,5
3,0
34,6
13,0
2,7
32,8
13,6
2,4
30,5
13,9
2,2
11/6
40,2
12,3
3,3
37,5
12,8
2,9
35,9
13,4
2,7
33,9
13,7
2,5
31,1
14,0
2,2
12/7
41,3
12,4
3,3
40,8
13,3
3,1
36,8
13,5
2,7
34,4
14,0
2,5
32,4
14,5
2,2
13/8
43,6
12,8
3,4
40,6
13,3
3,1
38,2
13,8
2,8
36,5
14,4
2,5
33,2
14,5
2,3
14/9
44,5
12,9
3,4
42,7
13,6
3,1
41,2
14,4
2,9
37,2
14,6
2,6
34,3
14,9
2,3
15/10
46,1
13,2
3,5
43,8
13,8
3,2
41,6
14,6
2,8
38,3
14,8
2,6
36,1
15,4
2,3
17/12
49,9
13,9
3,6
45,8
14,1
3,2
43,9
14,9
3,0
40,4
15,4
2,6
37,5
15,8
2,4
19/14
51,4
14,3
3,6
48,8
14,8
3,3
46,8
15,4
3,0
43,4
15,9
2,7
39,6
16,4
2,4
Technical book
21/16
54,7
14,7
3,7
52,6
15,3
3,4
49,2
16,0
3,1
45,4
16,5
2,8
42,4
17,1
2,5
Black ht
23/18
58,0
15,2
3,8
54,9
15,8
3,5
52,2
16,5
3,2
48,6
17,3
2,8
-
-
-
10/5
49,0
15,4
3,2
45,4
15,8
2,9
44,1
16,6
2,7
40,6
16,8
2,4
37,1
17,0
2,2
11/6
50,4
15,6
3,2
48,1
16,1
3,0
45,7
16,9
2,7
41,6
17,0
2,4
38,3
17,4
2,2
12/7
52,1
16,0
3,3
50,1
16,5
3,0
46,8
17,0
2,8
44,1
17,5
2,5
40,1
17,9
2,2
13/8
54,0
16,3
3,3
50,8
16,7
3,0
48,5
17,4
2,8
45,4
17,9
2,5
41,1
18,1
2,3
14/9
55,5
16,6
3,4
52,6
17,0
3,1
50,2
17,8
2,8
45,8
18,0
2,5
42,0
18,3
2,3
15/10
57,7
16,9
3,4
56,1
17,8
3,2
51,1
17,8
2,9
47,6
18,4
2,6
44,1
19,0
2,3
17/12
62,6
17,6
3,6
58,2
18,0
3,2
54,2
18,4
2,9
50,6
19,1
2,6
46,9
19,6
2,4
19/14
64,8
18,0
3,6
60,5
18,4
3,3
58,1
19,3
3,0
53,9
19,9
2,7
49,5
20,3
2,4
21/16
70,0
18,7
3,7
66,2
19,4
3,4
61,1
19,9
3,1
57,2
20,6
2,8
52,6
21,1
2,5
23/18
73,4
19,3
3,8
69,1
19,8
3,5
65,1
20,7
3,1
60,0
21,2
2,8
-
-
-
10/5
56,1
16,2
3,5
54,2
17,0
3,2
50,7
17,7
2,9
49,4
18,5
2,7
45,2
19,2
2,4
11/6
58,5
16,7
3,5
54,9
17,4
3,2
52,8
18,1
2,9
48,5
18,5
2,6
45,7
19,2
2,4
12/7
61,1
17,2
3,5
58,1
17,8
3,3
56,3
18,8
3,0
51,1
19,1
2,7
46,8
19,6
2,4
13/8
62,3
17,4
3,6
59,5
18,0
3,3
56,0
18,8
3,0
53,3
20,0
2,7
50,0
20,5
2,4
14/9
65,7
18,0
3,6
61,1
18,5
3,3
57,7
19,1
3,0
53,4
19,8
2,7
50,8
20,7
2,5
15/10
65,5
18,0
3,6
62,7
18,8
3,3
59,8
19,7
3,0
56,0
20,6
2,7
51,5
21,1
2,4
17/12
69,7
18,7
3,7
67,9
20,1
3,4
62,7
20,4
3,1
58,8
21,3
2,8
54,1
21,9
2,5
19/14
75,6
19,8
3,8
71,8
20,6
3,5
66,6
21,5
3,1
62,2
22,3
2,8
58,1
23,2
2,5
21/16
78,1
20,2
3,9
76,0
21,7
3,5
71,1
22,6
3,1
65,5
23,3
2,8
60,9
24,1
2,5
23/18
82,9
21,4
3,9
77,9
21,9
3,6
73,4
23,1
3,2
68,7
24,6
2,8
-
-
-
45
6
55
COOLING
AND
HEATING
CAPACITY
24
65
To: evaporator in/out water temperature [°C]
Ta: External air temperature (Dry Bulb) [°C]
kWF : cooling capacity [kW] (in conformity of EN14511)
kWe: electrical power input in kW (in conformity of EN14511)
The technical documentation can be improved all the times. Enerblue can update, time by time, all technical data in order to improve all necessary information for the customer.
Ta [°C]
75
90
70
85
105
25
30
35
40
45
To
[°C]
KWF
kWe
EER
KWF
kWe
EER
KWF
kWe
EER
KWF
kWe
EER
KWF
kWe
EER
10/5
63,6
19,4
3,3
63,4
20,9
3,0
59,4
21,9
2,7
54,8
22,5
2,4
51,1
23,3
2,2
11/6
65,7
19,7
3,3
63,1
20,9
3,0
59,8
22,0
2,7
57,9
23,4
2,5
53,2
24,0
2,2
12/7
67,5
20,1
3,4
66,9
21,5
3,1
62,6
22,6
2,8
58,5
23,4
2,5
53,4
24,1
2,2
13/8
70,0
20,5
3,4
67,0
21,7
3,1
64,5
23,1
2,8
59,6
23,9
2,5
56,2
24,6
2,3
14/9
71,8
20,8
3,5
69,5
22,1
3,1
66,1
23,4
2,8
61,4
24,2
2,5
58,4
25,3
2,3
15/10
74,8
21,2
3,5
74,5
23,0
3,2
68,4
23,7
2,9
63,1
24,8
2,5
59,4
25,7
2,3
17/12
79,8
22,0
3,6
75,5
23,5
3,2
75,3
25,2
3,0
68,5
25,7
2,7
62,6
26,7
2,3
19/14
84,0
22,6
3,7
80,1
23,9
3,4
76,3
25,4
3,0
71,8
26,8
2,7
67,1
27,9
2,4
21/16
88,7
23,3
3,8
85,1
24,9
3,4
80,2
26,1
3,1
76,2
27,7
2,7
71,8
29,0
2,5
23/18
92,6
23,8
3,9
89,8
25,6
3,5
85,3
27,2
3,1
80,6
28,7
2,8
-
-
-
10/5
77,6
23,5
3,3
75,1
24,7
3,0
70,5
25,9
2,7
65,8
26,9
2,4
60,3
27,5
2,2
11/6
80,8
24,0
3,4
76,7
25,2
3,0
74,0
26,7
2,8
68,4
27,5
2,5
61,9
27,8
2,2
12/7
83,0
24,5
3,4
79,3
25,7
3,1
74,3
27,1
2,7
69,3
27,8
2,5
64,3
28,6
2,2
13/8
86,9
25,1
3,5
82,4
26,2
3,1
77,3
27,2
2,8
72,3
28,8
2,5
66,3
29,3
2,3
14/9
88,6
25,3
3,5
84,7
26,7
3,2
79,7
28,1
2,8
73,3
29,1
2,5
68,6
29,9
2,3
15/10
95,0
26,4
3,6
86,3
27,0
3,2
82,8
28,7
2,9
75,9
29,5
2,6
72,5
31,3
2,3
17/12
95,8
26,5
3,6
94,0
28,4
3,3
87,1
29,6
2,9
81,2
30,7
2,6
75,2
31,8
2,4
19/14
104,0
27,9
3,7
98,5
29,3
3,4
93,4
30,8
3,0
87,0
32,0
2,7
79,4
33,0
2,4
21/16
110,2
29,0
3,8
102,8
30,1
3,4
97,1
31,6
3,1
90,4
33,0
2,7
86,2
34,9
2,5
23/18
114,6
29,7
3,9
110,3
31,3
3,5
104,3
32,9
3,2
95,7
34,1
2,8
-
-
-
10/5
61,9
18,8
3,3
58,5
19,5
3,0
57,7
20,8
2,8
53,6
21,7
2,5
49,5
21,9
2,3
11/6
62,6
18,6
3,4
61,3
19,7
3,1
58,8
21,2
2,8
56,3
22,3
2,5
51,9
22,8
2,3
12/7
65,0
19,2
3,4
63,6
20,5
3,1
61,3
21,4
2,9
56,1
22,3
2,5
54,8
23,4
2,3
13/8
67,3
19,5
3,4
65,2
20,7
3,1
62,7
21,7
2,9
59,3
23,0
2,6
56,1
23,6
2,4
14/9
69,4
19,9
3,5
67,6
21,2
3,2
63,6
22,1
2,9
61,0
23,5
2,6
55,6
23,8
2,3
15/10
71,2
20,2
3,5
69,0
21,5
3,2
66,1
22,6
2,9
62,1
23,7
2,6
58,9
24,7
2,4
17/12
75,7
20,9
3,6
73,3
21,9
3,3
68,5
23,1
3,0
67,4
24,5
2,7
62,3
25,5
2,4
19/14
81,1
21,7
3,7
77,4
22,8
3,4
73,6
23,9
3,1
69,5
25,4
2,7
65,8
26,4
2,5
21/16
85,5
22,3
3,8
81,7
23,7
3,4
78,8
25,0
3,2
71,9
25,9
2,8
68,8
27,2
2,5
23/18
89,2
23,1
3,9
84,9
24,1
3,5
82,7
25,7
3,2
77,8
27,1
2,9
-
-
-
10/5
74,9
22,9
3,3
71,0
23,9
3,0
67,4
24,8
2,7
63,3
25,6
2,5
59,3
26,5
2,2
11/6
76,7
23,3
3,3
74,5
24,7
3,0
69,8
25,3
2,8
64,8
26,2
2,5
60,3
26,9
2,2
12/7
79,1
23,7
3,3
75,3
24,5
3,1
71,3
25,9
2,8
68,3
26,8
2,6
63,1
27,4
2,3
13/8
83,2
24,3
3,4
79,1
25,4
3,1
74,0
26,4
2,8
70,2
27,4
2,6
64,7
28,0
2,3
14/9
84,6
24,9
3,4
82,2
25,8
3,2
77,6
26,9
2,9
70,2
27,6
2,5
66,1
28,0
2,4
15/10
87,6
25,0
3,5
83,3
26,1
3,2
79,0
27,1
2,9
74,3
28,3
2,6
70,5
29,7
2,4
17/12
91,8
25,8
3,6
87,0
27,0
3,2
82,8
28,0
3,0
78,9
29,4
2,7
72,1
30,1
2,4
19/14
98,9
26,8
3,7
92,9
27,9
3,3
88,8
29,2
3,0
83,0
30,5
2,7
77,2
31,5
2,5
21/16
102,6
27,5
3,7
100,0
29,0
3,5
94,5
30,3
3,1
87,6
31,4
2,8
81,9
32,7
2,5
23/18
107,9
28,3
3,8
102,5
29,5
3,5
98,9
31,3
3,2
91,3
32,4
2,8
-
-
-
10/5
93,9
28,9
3,3
88,4
29,8
3,0
83,4
30,5
2,7
80,9
32,3
2,5
71,8
32,2
2,2
11/6
97,0
29,5
3,3
92,5
30,3
3,0
86,5
31,4
2,8
84,8
33,0
2,6
75,2
32,8
2,3
12/7
99,7
29,8
3,3
94,4
31,0
3,1
90,6
32,3
2,8
84,2
33,0
2,6
76,4
33,6
2,3
13/8
103,3
30,3
3,4
97,8
31,6
3,1
95,5
32,9
2,9
89,5
34,3
2,6
81,1
35,2
2,3
14/9
106,2
31,0
3,4
101,0
32,1
3,1
96,1
33,5
2,9
88,9
34,3
2,6
81,5
34,9
2,3
15/10
110,4
31,6
3,5
104,3
32,6
3,2
101,4
34,3
3,0
92,7
35,0
2,6
85,8
36,0
2,4
17/12
117,5
32,7
3,6
112,6
34,0
3,3
105,7
35,3
3,0
95,2
35,9
2,7
91,1
37,2
2,4
19/14
124,1
33,6
3,7
117,6
34,9
3,4
114,5
36,6
3,1
107,5
37,9
2,8
96,4
38,6
2,5
21/16
131,0
34,8
3,8
129,1
36,6
3,5
118,2
37,7
3,1
110,3
38,9
2,8
100,3
39,6
2,5
23/18
137,6
35,9
3,8
132,9
37,4
3,6
124,4
38,6
3,2
115,8
40,0
2,9
-
-
-
To: evaporator in/out water temperature [°C]
Ta: External air temperature (Dry Bulb) [°C]
kWF : cooling capacity [kW] (in conformity of EN14511)
kWe: electrical power input in kW (in conformity of EN14511)
The technical documentation can be improved all the times. Enerblue can update, time by time, all technical data in order to improve all necessary information for the customer.
Technical book
black ht
6
COOLING
AND
HEATING
CAPACITY
25
Ta [°C]
125
145
Technical book
Black ht
6
180
COOLING
AND
HEATING
CAPACITY
200
26
235
25
30
35
40
45
To
[°C]
KWF
kWe
EER
KWF
kWe
EER
KWF
kWe
EER
KWF
kWe
EER
KWF
kWe
EER
10/5
104,3
30,5
3,4
99,7
31,8
3,1
94,8
32,8
2,9
89,2
34,3
2,6
81,7
35,1
2,3
11/6
107,8
31,1
3,5
103,5
32,5
3,2
97,7
33,8
2,9
91,8
35,0
2,6
84,6
36,0
2,3
12/7
111,1
31,8
3,5
106,8
33,3
3,2
100,7
34,6
2,9
93,4
35,6
2,6
87,3
36,7
2,4
13/8
113,0
32,3
3,5
108,1
33,6
3,2
104,7
35,4
3,0
97,0
36,5
2,7
90,9
38,2
2,4
14/9
117,9
33,2
3,6
113,7
34,7
3,3
107,8
36,2
3,0
100,0
37,5
2,7
94,0
38,9
2,4
15/10
126,0
34,7
3,6
116,8
35,3
3,3
111,2
36,9
3,0
103,7
38,4
2,7
95,7
39,5
2,4
17/12
132,7
36,0
3,7
124,2
36,7
3,4
117,2
38,4
3,0
109,6
40,0
2,7
102,4
41,6
2,5
19/14
140,0
37,5
3,7
130,5
38,2
3,4
124,0
40,2
3,1
116,0
41,8
2,8
107,0
43,2
2,5
21/16
142,6
37,9
3,8
137,6
39,6
3,5
131,9
42,2
3,1
122,3
43,6
2,8
117,9
46,8
2,5
23/18
155,9
40,4
3,9
148,7
42,1
3,5
136,3
43,3
3,1
127,6
45,4
2,8
-
-
-
10/5
124,3
39,2
3,2
118,9
40,7
2,9
113,3
43,1
2,6
104,9
44,4
2,4
98,6
45,3
2,2
11/6
129,9
39,9
3,3
121,5
41,8
2,9
116,3
43,4
2,7
109,6
45,5
2,4
103,6
47,4
2,2
12/7
133,0
40,7
3,3
126,7
42,9
3,0
120,2
44,9
2,7
113,5
46,3
2,5
106,0
47,9
2,2
13/8
138,3
41,6
3,3
130,9
43,3
3,0
125,1
45,4
2,8
115,9
47,4
2,4
108,8
49,3
2,2
14/9
142,3
42,4
3,4
135,4
44,4
3,0
128,3
46,6
2,8
122,5
48,5
2,5
112,3
50,1
2,2
15/10
146,0
43,0
3,4
139,2
45,0
3,1
133,4
47,9
2,8
123,7
49,0
2,5
115,5
51,2
2,3
17/12
154,5
44,5
3,5
148,3
47,0
3,2
140,2
49,3
2,8
131,6
51,4
2,6
121,7
53,1
2,3
19/14
164,5
46,1
3,6
157,8
48,8
3,2
149,4
51,0
2,9
138,7
53,2
2,6
129,2
55,4
2,3
21/16
175,6
48,3
3,6
164,6
50,3
3,3
155,4
52,8
2,9
145,7
55,1
2,6
136,3
57,5
2,4
23/18
181,7
49,3
3,7
172,6
51,9
3,3
164,1
54,6
3,0
154,2
57,6
2,7
-
-
-
10/5
145,5
45,7
3,2
143,2
48,8
2,9
133,7
50,4
2,7
125,5
52,2
2,4
117,6
54,1
2,2
11/6
152,0
47,2
3,2
144,2
48,9
2,9
137,9
50,9
2,7
129,2
53,4
2,4
122,7
55,7
2,2
12/7
157,4
48,1
3,3
150,1
50,1
3,0
145,2
52,3
2,8
134,3
54,6
2,5
126,5
56,9
2,2
13/8
161,5
48,7
3,3
154,3
51,5
3,0
146,6
53,1
2,8
136,2
55,3
2,5
128,2
57,5
2,2
14/9
167,5
50,0
3,4
160,3
52,2
3,1
153,8
54,5
2,8
142,5
56,3
2,5
134,0
59,2
2,3
15/10
170,3
50,9
3,3
164,8
53,1
3,1
156,5
55,5
2,8
147,6
58,2
2,5
134,0
59,5
2,3
17/12
179,6
52,3
3,4
174,3
54,7
3,2
165,8
57,6
2,9
153,8
59,9
2,6
142,4
61,9
2,3
19/14
193,2
54,6
3,5
182,2
56,6
3,2
173,9
59,3
2,9
164,8
62,6
2,6
150,8
64,5
2,3
21/16
197,2
55,7
3,5
192,5
58,6
3,3
181,1
61,3
3,0
173,0
64,6
2,7
160,3
67,1
2,4
23/18
216,0
58,7
3,7
200,3
60,3
3,3
195,7
64,6
3,0
177,4
66,1
2,7
-
-
-
10/5
180,5
57,5
3,1
169,6
59,7
2,8
160,8
62,3
2,6
149,7
64,2
2,3
137,5
65,5
2,1
11/6
183,7
58,1
3,2
177,1
61,0
2,9
165,7
63,4
2,6
153,7
65,4
2,4
143,4
67,1
2,1
12/7
190,2
59,4
3,2
182,4
62,2
2,9
173,8
65,2
2,7
163,5
67,8
2,4
148,6
68,4
2,2
13/8
196,8
60,9
3,2
186,8
63,2
3,0
178,9
66,4
2,7
163,5
68,0
2,4
153,4
70,0
2,2
14/9
204,2
62,2
3,3
194,5
64,8
3,0
182,7
67,1
2,7
171,1
69,6
2,5
157,0
71,3
2,2
15/10
211,6
64,2
3,3
198,8
65,7
3,0
189,1
68,5
2,8
174,0
70,7
2,5
164,6
73,3
2,2
17/12
223,8
65,9
3,4
209,5
67,7
3,1
199,3
71,2
2,8
185,7
73,6
2,5
170,6
75,3
2,3
19/14
235,2
67,6
3,5
223,3
70,8
3,2
207,6
72,7
2,9
193,5
75,4
2,6
180,0
77,8
2,3
21/16
250,2
70,1
3,6
236,3
74,3
3,2
219,1
75,7
2,9
206,3
78,5
2,6
192,5
81,3
2,4
23/18
257,6
72,2
3,6
251,1
76,4
3,3
233,2
78,9
3,0
217,0
81,7
2,7
-
-
-
10/5
214,2
70,2
3,0
201,1
72,1
2,8
190,7
75,2
2,5
174,5
77,4
2,3
161,3
79,4
2,0
11/6
218,5
71,0
3,1
207,6
73,6
2,8
192,7
76,0
2,5
179,0
78,7
2,3
165,8
81,2
2,0
12/7
228,8
73,1
3,1
213,1
74,7
2,9
201,1
78,0
2,6
185,5
80,3
2,3
171,5
82,9
2,1
13/8
236,5
75,4
3,1
220,3
76,7
2,9
207,6
80,1
2,6
192,1
82,3
2,3
178,7
85,2
2,1
14/9
234,1
74,9
3,1
227,6
78,2
2,9
213,0
80,9
2,6
198,0
83,8
2,4
184,6
87,1
2,1
15/10
250,2
77,1
3,2
233,2
79,4
2,9
218,6
82,9
2,6
205,1
86,0
2,4
188,8
88,2
2,1
17/12
260,4
79,5
3,3
250,4
83,4
3,0
230,5
85,8
2,7
215,9
89,1
2,4
199,9
92,0
2,2
19/14
274,0
82,2
3,3
260,5
86,1
3,0
245,7
90,5
2,7
226,8
92,8
2,4
209,9
95,7
2,2
21/16
289,9
85,9
3,4
278,5
90,4
3,1
254,2
93,3
2,7
237,6
97,9
2,4
223,5
100,8
2,2
23/18
305,4
88,4
3,5
285,0
92,2
3,1
270,9
97,7
2,8
251,0
101,3
2,5
-
-
-
To: evaporator in/out water temperature [°C]
Ta: External air temperature (Dry Bulb) [°C]
kWF : cooling capacity [kW] (in conformity of EN14511)
kWe: electrical power input in kW (in conformity of EN14511)
The technical documentation can be improved all the times. Enerblue can update, time by time, all technical data in order to improve all necessary information for the customer.
HEATING CAPACITY
Ta [°C] / RH
MOD. To [°C]
-15 / 90
-10 / 90
-5 / 80
0 / 80
5 / 80
7 / 80
KWT kWe COP KWT kWe COP KWT kWe COP KWT kWe COP KWT kWe COP KWT kWe COP
40
45
55
65
75
90
70
30/35
35/40
40/45
45/50
50/55
55/60
60/65
65/70
70/75
30/35
35/40
40/45
45/50
50/55
55/60
60/65
65/70
70/75
30/35
35/40
40/45
45/50
50/55
55/60
60/65
65/70
70/75
30/35
35/40
40/45
45/50
50/55
55/60
60/65
65/70
70/75
30/35
35/40
40/45
45/50
50/55
55/60
60/65
65/70
70/75
30/35
35/40
40/45
45/50
50/55
55/60
60/65
65/70
70/75
30/35
35/40
40/45
45/50
50/55
55/60
60/65
65/70
70/75
16,6
15,8
15,0
14,2
13,2
12,4
19,9
18,8
17,8
16,6
15,7
14,7
23,4
22,0
20,6
19,0
17,6
16,1
29,1
27,9
26,5
25,3
24,0
22,6
34,7
33,1
31,3
29,6
27,5
25,9
40,2
38,7
37,2
35,2
33,3
31,5
33,0
31,4
29,9
28,0
26,4
24,6
-
6,667
6,8
6,9
7,0
7,1
7,1
8,012
8,0
8,0
8,0
8,0
7,9
9,342
9,4
9,4
9,4
9,3
9,2
9,421
9,7
9,9
10,1
10,3
10,5
13,08
13,4
13,5
13,7
13,8
13,9
15,08
15,4
15,7
15,9
16,0
16,1
12,88
13,1
13,4
13,5
13,7
13,8
-
To: Condenser in/out water temperature [°C]
Ta: External air temperature (Dry Bulb) [°C]
RH: relative humidity [%]
2,5
2,3
2,2
2,0
1,9
1,7
2,5
2,3
2,2
2,1
2,0
1,9
2,5
2,3
2,2
2,0
1,9
1,8
3,1
2,9
2,7
2,5
2,3
2,2
2,7
2,5
2,3
2,2
2,0
1,9
2,7
2,5
2,4
2,2
2,1
2,0
2,6
2,4
2,2
2,1
1,9
1,8
-
20,1
19,2
20,5
17,6
16,8
15,9
16,4
24,0
23,0
24,3
20,7
19,6
18,5
19,4
29,3
27,8
29,7
24,6
23,0
21,4
22,3
35,0
33,8
34,0
30,9
29,6
28,1
27,0
42,2
40,8
40,7
37,5
35,4
33,2
32,5
50,0
48,0
46,4
43,8
41,6
39,7
34,9
40,6
38,9
37,2
35,7
33,6
31,9
29,6
-
7,344
7,5
8,2
7,9
8,0
8,1
8,7
8,795
8,9
9,6
9,0
9,0
9,0
9,7
10,47
10,6
11,5
10,8
10,8
10,7
11,4
10,51
10,9
12,0
11,4
11,7
11,9
12,7
14,61
15,0
16,1
15,7
15,9
16,1
16,3
16,92
17,4
18,4
18,1
18,4
18,6
18,2
14,32
14,7
15,0
15,3
15,6
15,8
15,9
-
2,7
2,6
2,5
2,2
2,1
2,0
1,9
2,7
2,6
2,5
2,3
2,2
2,0
2,0
2,8
2,6
2,6
2,3
2,1
2,0
2,0
3,3
3,1
2,8
2,7
2,5
2,4
2,1
2,9
2,7
2,5
2,4
2,2
2,1
2,0
3,0
2,8
2,5
2,4
2,3
2,1
1,9
2,8
2,6
2,5
2,3
2,2
2,0
1,9
-
24,2
23,5
22,3
21,5
20,5
19,3
18,2
17,2
16,1
29,2
28,0
26,2
25,5
24,3
23,0
21,4
20,6
19,5
36,2
34,1
32,5
30,8
28,9
27,2
25,4
23,6
21,7
42,1
40,8
39,2
37,8
36,2
34,7
32,0
31,2
29,5
51,3
49,4
46,6
45,6
43,7
41,6
38,1
37,1
34,5
60,4
57,9
54,1
53,6
51,0
48,6
42,3
43,5
40,7
49,0
47,4
45,6
43,9
41,9
39,6
37,2
35,2
32,8
8,118
8,4
8,6
8,8
9,0
9,1
9,3
9,4
9,5
9,7
9,9
10,0
10,2
10,3
10,4
10,4
10,5
10,6
11,67
11,8
12,1
12,2
12,3
12,3
12,4
12,3
12,1
11,75
12,2
13,0
13,0
13,3
13,6
14,1
14,2
14,5
16,31
16,8
17,4
17,7
18,1
18,5
18,2
19,0
19,1
18,7
19,3
19,9
20,4
20,8
21,2
20,5
21,7
21,8
15,82
16,3
16,8
17,2
17,6
17,9
18,1
18,4
18,7
3,0
2,8
2,6
2,4
2,3
2,1
2,0
1,8
1,7
3,0
2,8
2,6
2,5
2,4
2,2
2,1
2,0
1,8
3,1
2,9
2,7
2,5
2,4
2,2
2,0
1,9
1,8
3,6
3,3
3,0
2,9
2,7
2,5
2,3
2,2
2,0
3,1
2,9
2,7
2,6
2,4
2,3
2,1
2,0
1,8
3,2
3,0
2,7
2,6
2,5
2,3
2,1
2,0
1,9
3,1
2,9
2,7
2,5
2,4
2,2
2,1
1,9
1,8
28,9
27,9
27,0
25,9
24,6
23,5
22,3
21,1
19,9
34,8
33,5
32,2
30,8
29,4
28,0
26,5
25,1
23,9
43,5
41,7
39,9
37,6
35,7
33,8
31,9
29,6
27,5
50,3
48,8
47,1
45,6
43,9
42,0
39,9
38,0
36,1
61,4
59,2
57,4
54,7
52,5
50,0
47,9
45,1
42,4
72,4
70,2
67,1
64,3
61,4
58,8
55,5
52,6
49,7
58,8
57,0
54,8
52,4
50,0
47,7
45,5
42,8
40,4
8,831
9,1
9,5
9,7
9,9
10,2
10,4
10,6
10,8
10,55
10,8
11,1
11,3
11,5
11,7
11,8
12,0
12,1
12,74
13,1
13,4
13,6
13,8
14,0
14,1
14,1
14,1
13,02
13,6
14,1
14,6
15,1
15,5
15,8
16,3
16,6
17,93
18,6
19,3
19,8
20,4
20,8
21,3
21,6
21,9
20,56
21,4
22,1
22,8
23,4
24,0
24,4
24,7
25,1
17,31
18,0
18,5
19,0
19,5
20,0
20,4
20,8
21,1
3,3
3,1
2,9
2,7
2,5
2,3
2,1
2,0
1,8
3,3
3,1
2,9
2,7
2,6
2,4
2,2
2,1
2,0
3,4
3,2
3,0
2,8
2,6
2,4
2,3
2,1
2,0
3,9
3,6
3,3
3,1
2,9
2,7
2,5
2,3
2,2
3,4
3,2
3,0
2,8
2,6
2,4
2,2
2,1
1,9
3,5
3,3
3,0
2,8
2,6
2,5
2,3
2,1
2,0
3,4
3,2
3,0
2,8
2,6
2,4
2,2
2,1
1,9
33,9
32,9
31,6
30,5
29,1
27,9
26,5
25,1
23,8
40,9
39,3
37,8
36,3
34,8
33,2
31,6
30,1
28,5
51,5
49,7
47,6
45,3
43,1
40,7
38,6
36,2
33,8
58,9
57,3
55,6
53,7
51,5
49,6
47,3
45,3
43,0
72,0
69,7
67,3
64,9
62,5
59,8
57,0
54,0
51,0
85,6
82,9
79,7
76,3
72,9
69,7
66,5
62,9
59,5
69,3
67,3
64,8
62,2
59,8
56,9
54,3
51,4
48,5
9,57
10,0
10,3
10,7
11,0
11,3
11,6
11,9
12,1
11,44
11,8
12,2
12,5
12,8
13,1
13,3
13,5
13,8
13,84
14,4
14,8
15,1
15,5
15,7
15,9
16,0
16,1
14,25
15,0
15,6
16,3
16,8
17,4
17,9
18,5
19,0
19,49
20,4
21,3
22,1
22,8
23,4
24,0
24,5
24,9
22,38
23,5
24,4
25,3
26,1
26,8
27,5
28,0
28,5
18,78
19,7
20,4
21,1
21,7
22,3
22,9
23,3
23,7
3,5
3,3
3,1
2,8
2,6
2,5
2,3
2,1
2,0
3,6
3,3
3,1
2,9
2,7
2,5
2,4
2,2
2,1
3,7
3,5
3,2
3,0
2,8
2,6
2,4
2,3
2,1
4,1
3,8
3,6
3,3
3,1
2,8
2,6
2,5
2,3
3,7
3,4
3,2
2,9
2,7
2,6
2,4
2,2
2,0
3,8
3,5
3,3
3,0
2,8
2,6
2,4
2,2
2,1
3,7
3,4
3,2
3,0
2,8
2,6
2,4
2,2
2,0
36,1
35,0
33,6
32,4
31,1
29,6
28,2
26,8
25,3
43,4
42,0
40,3
38,7
37,1
35,4
33,7
32,1
30,5
55,0
53,1
51,0
48,5
46,2
43,6
41,2
38,8
36,4
62,4
60,7
59,2
57,2
55,0
52,8
50,4
47,9
45,8
76,4
74,4
71,7
69,1
66,5
63,8
60,5
57,7
54,6
91,5
88,6
84,9
81,6
77,9
74,6
70,8
67,1
63,1
73,8
71,6
68,8
66,2
63,7
60,6
57,9
54,8
51,8
9,88
10,3
10,7
11,1
11,4
11,7
12,0
12,2
12,5
11,76
12,2
12,6
13,0
13,3
13,6
13,9
14,1
14,3
14,29
14,9
15,3
15,7
16,1
16,3
16,5
16,6
16,7
14,73
15,5
16,3
17,0
17,6
18,2
18,7
19,2
19,8
20,09
21,1
22,0
22,8
23,5
24,2
24,7
25,4
25,9
23,16
24,4
25,3
26,3
27,1
27,8
28,5
29,0
29,4
19,35
20,3
21,0
21,7
22,3
22,9
23,4
23,9
24,4
kWF : cooling capacity [kW] (in conformity of EN14511)
kWe: electrical power input in kW (in conformity of EN14511)
The technical documentation can be improved all the times. Enerblue can update, time by time, all technical data in order to improve all necessary information for the customer.
3,7
3,4
3,1
2,9
2,7
2,5
2,4
2,2
2,0
3,7
3,4
3,2
3,0
2,8
2,6
2,4
2,3
2,1
3,8
3,6
3,3
3,1
2,9
2,7
2,5
2,3
2,2
4,2
3,9
3,6
3,4
3,1
2,9
2,7
2,5
2,3
3,8
3,5
3,3
3,0
2,8
2,6
2,4
2,3
2,1
4,0
3,6
3,4
3,1
2,9
2,7
2,5
2,3
2,1
3,8
3,5
3,3
3,1
2,9
2,6
2,5
2,3
2,1
Technical book
black ht
6
COOLING
AND
HEATING
CAPACITY
27
Ta [°C] / RH
MOD. To [°C]
-15 / 90
-10 / 90
-5 / 80
0 / 80
5 / 80
7 / 80
KWT kWe COP KWT kWe COP KWT kWe COP KWT kWe COP KWT kWe COP KWT kWe COP
85
105
125
Technical book
Black ht
6
COOLING
AND
HEATING
CAPACITY
145
180
28
200
235
30/35 38,7 16,09
35/40 36,7 16,1
40/45 34,7 16,2
45/50 32,6 16,1
50/55 30,6 16,0
55/60 28,6 15,9
60/65
65/70
70/75
30/35 47,4 19,55
35/40 44,2 19,6
40/45 41,9 19,8
45/50 38,7 19,7
50/55 35,5 19,5
55/60 32,5 19,2
60/65
65/70
70/75
30/35 58,7 18,94
35/40 56,4 19,5
40/45 53,9 20,0
45/50 51,3 20,4
50/55 48,2 20,7
55/60 45,5 21,1
60/65
65/70
70/75
30/35 69,7 24,77
35/40 66,6 25,3
40/45 63,1 25,8
45/50 59,8 26,2
50/55 56,2 26,5
55/60 52,5 26,7
60/65
65/70
70/75
30/35 86,4 30,6
35/40 83,5 31,5
40/45 79,5 32,0
45/50 75,6 32,4
50/55 71,5 32,7
55/60 67,1 32,8
60/65
65/70
70/75
30/35 99,4 37,25
35/40 93,9 37,9
40/45 88,8 38,4
45/50 84,1 38,8
50/55 79,3 39,1
55/60 73,5 38,9
60/65
65/70
70/75
30/35 110,2 42,87
35/40 105,9 43,7
40/45 101,1 44,4
45/50 97,0 45,1
50/55 92,5 45,6
55/60 88,1 46,0
60/65
65/70
70/75
-
2,4
2,3
2,1
2,0
1,9
1,8
2,4
2,3
2,1
2,0
1,8
1,7
3,1
2,9
2,7
2,5
2,3
2,2
2,8
2,6
2,4
2,3
2,1
2,0
2,8
2,7
2,5
2,3
2,2
2,0
2,7
2,5
2,3
2,2
2,0
1,9
2,6
2,4
2,3
2,2
2,0
1,9
-
47,8
45,7
43,4
41,4
39,0
36,7
34,6
59,5
56,2
53,0
50,4
46,8
43,3
39,8
71,3
69,0
66,1
63,5
60,6
57,7
54,6
84,5
81,1
77,7
74,2
70,4
67,2
63,5
103,8
99,7
95,7
91,1
87,0
82,3
77,8
119,9
116,2
111,3
105,1
99,7
93,6
87,3
135,4
131,2
125,5
119,6
114,7
109,2
105,0
-
17,83
18,1
18,2
18,4
18,4
18,4
18,4
21,87
22,2
22,4
22,6
22,6
22,5
22,2
21,29
22,0
22,6
23,2
23,7
24,2
24,6
27,72
28,5
29,2
29,8
30,3
30,8
31,3
33,86
34,9
35,8
36,4
37,0
37,4
37,7
41,34
42,7
43,7
44,3
44,9
45,1
45,1
47,67
49,2
50,1
50,9
51,9
52,6
53,6
-
2,7
2,5
2,4
2,3
2,1
2,0
1,9
2,7
2,5
2,4
2,2
2,1
1,9
1,8
3,3
3,1
2,9
2,7
2,6
2,4
2,2
3,0
2,8
2,7
2,5
2,3
2,2
2,0
3,1
2,9
2,7
2,5
2,3
2,2
2,1
2,9
2,7
2,5
2,4
2,2
2,1
1,9
2,8
2,7
2,5
2,4
2,2
2,1
2,0
-
58,1
55,6
53,0
50,8
48,5
45,9
43,4
41,1
38,7
72,9
69,7
66,1
63,0
59,2
55,6
51,7
48,2
44,3
85,6
82,9
79,8
76,8
73,8
70,5
67,3
63,4
59,9
102,2
98,8
94,8
91,3
87,3
82,7
78,4
74,1
69,5
124,7
119,8
115,0
110,7
105,6
100,5
95,0
89,6
84,1
144,1
139,8
134,7
128,5
122,2
115,8
109,2
102,4
94,6
163,6
158,3
152,7
147,0
140,3
134,3
128,2
123,1
117,0
19,64
20,0
20,3
20,7
20,9
21,1
21,3
21,4
21,5
24,21
24,8
25,2
25,6
25,8
26,0
25,9
25,8
25,6
23,76
24,7
25,5
26,2
26,9
27,6
28,2
28,7
29,3
30,98
32,1
33,0
34,0
34,7
35,3
35,9
36,5
36,9
37,48
38,8
40,0
41,1
42,0
42,7
43,3
43,8
44,0
45,76
47,5
48,9
50,0
51,0
51,6
52,1
52,3
52,0
52,57
54,3
56,0
57,5
58,8
60,0
61,1
62,4
63,2
3,0
2,8
2,6
2,5
2,3
2,2
2,0
1,9
1,8
3,0
2,8
2,6
2,5
2,3
2,1
2,0
1,9
1,7
3,6
3,4
3,1
2,9
2,7
2,6
2,4
2,2
2,0
3,3
3,1
2,9
2,7
2,5
2,3
2,2
2,0
1,9
3,3
3,1
2,9
2,7
2,5
2,4
2,2
2,0
1,9
3,1
2,9
2,8
2,6
2,4
2,2
2,1
2,0
1,8
3,1
2,9
2,7
2,6
2,4
2,2
2,1
2,0
1,9
70,0
67,3
64,4
61,6
58,5
56,0
53,3
50,3
47,8
88,7
84,9
80,4
77,3
72,9
69,1
64,8
60,4
56,1
101,5
98,8
95,7
92,1
89,0
85,2
81,0
77,2
73,1
121,8
117,9
113,9
109,7
105,3
100,7
95,8
91,0
85,7
147,4
142,1
137,6
131,5
126,1
120,3
113,9
108,0
101,7
173,0
167,5
161,3
154,8
148,2
141,2
133,5
125,2
116,5
196,6
190,6
184,3
177,5
169,7
162,9
156,6
150,0
142,4
21,45
22,1
22,6
23,1
23,4
23,9
24,2
24,5
24,8
26,62
27,4
28,0
28,7
29,0
29,4
29,6
29,6
29,6
26,28
27,5
28,5
29,4
30,4
31,3
32,1
33,0
33,7
34,18
35,6
36,9
38,1
39,3
40,2
41,1
41,9
42,7
41,02
42,8
44,4
45,8
47,1
48,3
49,1
49,9
50,5
50,36
52,5
54,4
56,0
57,3
58,4
59,3
59,8
59,9
57,79
60,1
62,3
64,4
66,2
67,9
69,8
71,4
72,7
3,3
3,1
2,9
2,7
2,5
2,3
2,2
2,1
1,9
3,3
3,1
2,9
2,7
2,5
2,3
2,2
2,0
1,9
3,9
3,6
3,4
3,1
2,9
2,7
2,5
2,3
2,2
3,6
3,3
3,1
2,9
2,7
2,5
2,3
2,2
2,0
3,6
3,3
3,1
2,9
2,7
2,5
2,3
2,2
2,0
3,4
3,2
3,0
2,8
2,6
2,4
2,3
2,1
1,9
3,4
3,2
3,0
2,8
2,6
2,4
2,2
2,1
2,0
82,8
79,7
76,4
72,8
69,9
66,8
63,6
60,5
57,2
104,7
101,2
97,0
92,5
87,8
83,7
78,9
73,9
68,5
119,0
115,9
112,0
109,1
104,8
100,0
96,2
91,7
87,5
143,6
139,0
134,8
129,7
125,1
119,6
114,0
108,5
103,0
172,1
166,3
161,0
155,0
147,9
141,4
135,1
128,2
120,8
203,2
196,4
189,8
183,4
176,2
167,4
159,7
150,6
140,9
234,0
226,6
218,9
211,2
203,6
194,7
186,6
178,4
170,4
23,21
24,1
24,8
25,4
26,1
26,7
27,3
27,7
28,1
28,79
29,9
30,9
31,7
32,4
33,0
33,4
33,7
33,7
28,77
30,3
31,5
32,9
34,1
35,1
36,4
37,3
38,5
37,2
39,1
40,9
42,4
44,0
45,3
46,4
47,6
48,8
44,58
46,8
48,8
50,7
52,3
53,8
55,3
56,5
57,4
54,76
57,3
59,7
61,9
63,7
65,2
66,8
67,6
68,1
62,96
66,0
68,8
71,5
74,1
76,3
78,5
80,8
82,6
3,6
3,3
3,1
2,9
2,7
2,5
2,3
2,2
2,0
3,6
3,4
3,1
2,9
2,7
2,5
2,4
2,2
2,0
4,1
3,8
3,6
3,3
3,1
2,8
2,6
2,5
2,3
3,9
3,6
3,3
3,1
2,8
2,6
2,5
2,3
2,1
3,9
3,6
3,3
3,1
2,8
2,6
2,4
2,3
2,1
3,7
3,4
3,2
3,0
2,8
2,6
2,4
2,2
2,1
3,7
3,4
3,2
3,0
2,7
2,6
2,4
2,2
2,1
88,2
85,0
81,5
78,0
74,5
71,2
67,8
64,3
61,0
112,2
108,0
103,8
98,9
94,1
89,2
84,2
79,4
74,2
126,8
123,8
120,1
115,8
112,0
107,2
102,5
97,5
93,0
151,9
148,1
143,0
138,6
133,1
127,6
121,5
115,8
110,1
183,9
176,9
171,2
164,9
158,1
150,8
143,3
135,6
128,2
216,3
209,5
202,3
196,0
187,6
178,5
169,9
161,7
150,6
251,2
243,6
234,4
227,4
219,2
209,6
200,1
191,5
182,6
23,93
24,9
25,7
26,4
27,0
27,6
28,2
28,7
29,1
29,75
30,9
32,0
32,9
33,6
34,2
34,6
34,9
35,1
29,8
31,5
32,9
34,3
35,7
36,8
38,0
39,0
40,1
38,36
40,5
42,3
44,2
45,7
47,1
48,4
49,5
50,7
46,11
48,4
50,6
52,7
54,6
56,2
57,5
58,5
59,5
56,53
59,4
61,9
64,4
66,3
67,9
69,3
70,5
70,8
65,1
68,5
71,4
74,7
77,5
80,0
82,3
84,6
86,7
To: Condenser in/out water temperature [°C]
Ta: External air temperature (Dry Bulb) [°C]
RH: relative humidity [%]
kWF : cooling capacity [kW] (in conformity of EN14511)
kWe: electrical power input in kW (in conformity of EN14511)
The technical documentation can be improved all the times. Enerblue can update, time by time, all technical data in order to improve all necessary information for the customer.
3,7
3,4
3,2
3,0
2,8
2,6
2,4
2,2
2,1
3,8
3,5
3,2
3,0
2,8
2,6
2,4
2,3
2,1
4,3
3,9
3,6
3,4
3,1
2,9
2,7
2,5
2,3
4,0
3,7
3,4
3,1
2,9
2,7
2,5
2,3
2,2
4,0
3,7
3,4
3,1
2,9
2,7
2,5
2,3
2,2
3,8
3,5
3,3
3,0
2,8
2,6
2,5
2,3
2,1
3,9
3,6
3,3
3,0
2,8
2,6
2,4
2,3
2,1
Ta [°C] / RH
MOD. To [°C]
10 / 70
15 / 70
20 / 60
25 / 60
30 / 50
35 / 50
KWT kWe COP KWT kWe COP KWT kWe COP KWT kWe COP KWT kWe COP KWT kWe COP
40
45
55
65
75
90
70
30/35
35/40
40/45
45/50
50/55
55/60
60/65
65/70
70/75
30/35
35/40
40/45
45/50
50/55
55/60
60/65
65/70
70/75
30/35
35/40
40/45
45/50
50/55
55/60
60/65
65/70
70/75
30/35
35/40
40/45
45/50
50/55
55/60
60/65
65/70
70/75
30/35
35/40
40/45
45/50
50/55
55/60
60/65
65/70
70/75
30/35
35/40
40/45
45/50
50/55
55/60
60/65
65/70
70/75
30/35
35/40
40/45
45/50
50/55
55/60
60/65
65/70
70/75
38,4
37,1
35,9
34,5
33,1
31,6
30,2
28,8
27,2
46,7
44,9
43,1
41,2
39,6
37,9
36,0
34,5
32,8
58,7
56,8
54,4
51,8
49,1
46,7
44,2
41,7
39,0
66,4
64,4
62,4
60,8
58,3
56,0
53,7
51,2
48,6
81,4
78,8
76,6
73,5
70,6
67,8
64,8
61,8
58,7
96,6
93,8
91,0
87,0
83,3
79,2
75,4
71,3
67,8
78,1
75,8
73,2
70,5
67,6
64,7
61,4
58,7
55,5
10,07
10,5
10,9
11,3
11,7
12,0
12,3
12,6
12,9
12,15
12,6
13,0
13,3
13,7
14,0
14,3
14,6
14,9
14,69
15,3
15,8
16,2
16,5
16,8
17,1
17,3
17,4
15,22
16,0
16,8
17,6
18,2
18,8
19,4
20,0
20,6
20,44
21,5
22,5
23,3
24,1
24,9
25,6
26,3
27,0
23,66
24,9
26,1
27,0
27,9
28,7
29,4
30,0
30,6
19,55
20,5
21,3
22,1
22,8
23,4
24,0
24,6
25,2
3,8
3,5
3,3
3,0
2,8
2,6
2,5
2,3
2,1
3,8
3,6
3,3
3,1
2,9
2,7
2,5
2,4
2,2
4,0
3,7
3,5
3,2
3,0
2,8
2,6
2,4
2,2
4,4
4,0
3,7
3,5
3,2
3,0
2,8
2,6
2,4
4,0
3,7
3,4
3,1
2,9
2,7
2,5
2,4
2,2
4,1
3,8
3,5
3,2
3,0
2,8
2,6
2,4
2,2
4,0
3,7
3,4
3,2
3,0
2,8
2,6
2,4
2,2
43,1
41,8
40,6
39,1
37,4
35,8
34,2
32,8
31,2
52,2
50,4
48,4
46,7
44,9
42,8
40,9
39,0
37,3
66,4
63,7
61,3
58,5
56,0
53,3
50,6
47,9
45,0
74,5
72,4
70,2
67,9
65,1
62,7
60,3
57,6
54,9
91,2
88,6
85,9
82,9
79,8
76,7
73,3
69,9
66,5
109,1
105,3
102,1
98,5
94,2
89,9
85,5
81,2
76,7
87,3
84,9
82,0
79,1
76,0
72,7
69,6
66,1
62,6
10,3
10,8
11,4
11,8
12,2
12,7
13,1
13,5
13,8
12,52
13,1
13,6
14,0
14,5
14,9
15,3
15,7
16,0
15,24
15,9
16,5
17,0
17,5
17,9
18,3
18,6
18,8
15,86
16,8
17,7
18,6
19,3
20,1
20,9
21,6
22,3
20,95
22,2
23,4
24,4
25,5
26,4
27,3
28,1
28,9
24,47
25,9
27,2
28,5
29,5
30,5
31,5
32,2
32,9
19,82
20,9
21,9
22,8
23,7
24,5
25,2
25,9
26,6
4,2
3,9
3,6
3,3
3,1
2,8
2,6
2,4
2,3
4,2
3,9
3,6
3,3
3,1
2,9
2,7
2,5
2,3
4,4
4,0
3,7
3,4
3,2
3,0
2,8
2,6
2,4
4,7
4,3
4,0
3,7
3,4
3,1
2,9
2,7
2,5
4,4
4,0
3,7
3,4
3,1
2,9
2,7
2,5
2,3
4,5
4,1
3,8
3,5
3,2
2,9
2,7
2,5
2,3
4,4
4,1
3,7
3,5
3,2
3,0
2,8
2,5
2,4
47,4
45,9
44,3
42,6
41,0
39,3
37,5
35,8
33,9
56,8
55,3
53,3
51,2
49,1
47,1
45,1
43,1
40,9
71,6
69,1
66,4
63,7
61,0
57,9
55,1
52,2
49,3
80,6
78,1
75,6
73,5
70,7
68,0
65,1
62,2
59,6
99,2
96,3
92,9
89,5
87,0
83,1
79,6
76,0
72,3
118,4
114,5
110,9
106,1
102,0
97,5
92,9
88,3
83,7
94,5
91,5
88,4
85,2
81,7
78,1
74,6
71,1
67,3
10,48
11,1
11,7
12,2
12,7
13,2
13,6
14,1
14,5
12,81
13,5
14,1
14,6
15,1
15,6
16,1
16,5
16,9
15,6
16,4
17,0
17,7
18,2
18,7
19,1
19,5
19,8
16,28
17,3
18,3
19,3
20,2
21,0
21,8
22,7
23,5
21,27
22,7
24,0
25,2
26,4
27,4
28,5
29,5
30,4
24,98
26,6
28,1
29,4
30,7
31,8
32,8
33,8
34,6
19,97
21,2
22,3
23,3
24,2
25,1
26,0
26,8
27,5
4,5
4,1
3,8
3,5
3,2
3,0
2,8
2,5
2,3
4,4
4,1
3,8
3,5
3,2
3,0
2,8
2,6
2,4
4,6
4,2
3,9
3,6
3,3
3,1
2,9
2,7
2,5
5,0
4,5
4,1
3,8
3,5
3,2
3,0
2,7
2,5
4,7
4,3
3,9
3,6
3,3
3,0
2,8
2,6
2,4
4,7
4,3
4,0
3,6
3,3
3,1
2,8
2,6
2,4
4,7
4,3
4,0
3,7
3,4
3,1
2,9
2,7
2,4
51,2
49,5
47,7
46,0
44,3
42,4
40,4
38,5
36,5
62,3
60,1
57,8
55,4
53,0
50,9
48,6
46,3
44,2
77,6
75,1
71,9
69,0
65,8
62,8
59,7
56,5
53,3
87,0
84,3
81,8
79,1
76,1
73,3
70,2
67,3
64,1
107,0
103,7
100,7
97,2
93,5
89,7
85,6
81,7
77,9
128,1
123,9
119,3
114,6
110,2
105,2
100,2
95,4
90,0
100,8
97,5
94,0
90,5
86,6
82,7
78,5
73,8
69,4
10,6
11,3
11,9
12,5
13,1
13,6
14,1
14,6
15,1
13,12
13,8
14,5
15,1
15,7
16,2
16,8
17,2
17,7
15,96
16,8
17,6
18,3
18,9
19,4
19,9
20,3
20,7
16,66
17,9
18,9
20,0
21,0
22,0
22,9
23,8
24,7
21,55
23,1
24,6
26,0
27,2
28,5
29,6
30,7
31,7
25,46
27,3
28,9
30,4
31,8
33,0
34,2
35,3
36,2
20,09
21,4
22,6
23,7
24,7
25,7
26,6
27,3
28,0
4,8
4,4
4,0
3,7
3,4
3,1
2,9
2,6
2,4
4,7
4,3
4,0
3,7
3,4
3,1
2,9
2,7
2,5
4,9
4,5
4,1
3,8
3,5
3,2
3,0
2,8
2,6
5,2
4,7
4,3
4,0
3,6
3,3
3,1
2,8
2,6
5,0
4,5
4,1
3,7
3,4
3,2
2,9
2,7
2,5
5,0
4,5
4,1
3,8
3,5
3,2
2,9
2,7
2,5
5,0
4,6
4,2
3,8
3,5
3,2
3,0
2,7
2,5
53,3
51,5
49,7
47,8
45,7
44,0
42,0
39,6
37,2
64,7
62,5
60,1
57,7
55,2
52,8
50,4
48,1
45,6
80,8
77,6
74,8
71,7
68,4
65,2
61,8
58,5
55,3
90,8
87,7
85,0
81,9
79,4
76,1
73,1
69,7
66,4
111,5
107,9
104,2
100,6
96,8
92,6
88,2
82,5
78,6
133,4
128,9
124,4
119,4
114,1
108,8
103,8
98,4
92,0
103,7
100,1
96,3
91,9
87,4
83,0
78,5
74,0
69,4
10,66
11,4
12,1
12,7
13,3
13,9
14,4
14,8
15,2
13,26
14,0
14,7
15,4
16,0
16,6
17,1
17,6
18,1
16,14
17,0
17,8
18,6
19,2
19,8
20,3
20,8
21,1
16,9
18,1
19,3
20,4
21,5
22,5
23,5
24,4
25,3
21,68
23,3
24,8
26,3
27,7
28,9
30,0
30,7
31,7
25,73
27,6
29,3
30,9
32,3
33,6
34,8
35,9
36,6
20,13
21,5
22,7
23,8
24,8
25,7
26,5
27,3
28,0
5,0
4,5
4,1
3,8
3,4
3,2
2,9
2,7
2,4
4,9
4,5
4,1
3,8
3,5
3,2
2,9
2,7
2,5
5,0
4,6
4,2
3,9
3,6
3,3
3,0
2,8
2,6
5,4
4,8
4,4
4,0
3,7
3,4
3,1
2,9
2,6
5,1
4,6
4,2
3,8
3,5
3,2
2,9
2,7
2,5
5,2
4,7
4,2
3,9
3,5
3,2
3,0
2,7
2,5
5,2
4,7
4,2
3,9
3,5
3,2
3,0
2,7
2,5
55,8
53,5
51,3
49,0
46,2
44,6
42,8
40,2
37,9
68,2
65,9
63,1
60,2
57,1
54,2
51,4
49,3
46,8
85,0
81,6
78,3
75,2
71,7
67,5
62,2
59,5
55,8
95,6
92,6
89,6
86,3
83,0
79,8
76,3
72,2
68,1
115,0
111,5
107,0
102,4
97,7
93,0
88,2
83,4
78,6
139,7
135,0
129,7
123,6
117,3
110,9
103,8
98,6
92,0
104,5
100,4
96,2
91,9
87,1
83,0
78,5
9,6
69,4
10,73
11,5
12,1
12,7
13,8
14,2
14,9
15,0
15,6
13,43
14,2
15,0
15,7
16,2
16,7
17,5
17,9
18,6
16,34
17,3
18,2
18,9
19,6
20,1
20,5
20,8
21,8
17,14
18,4
19,7
20,9
22,0
23,1
24,1
24,9
25,7
21,58
23,4
24,9
26,3
27,6
28,7
29,7
30,7
31,5
26,03
28,0
29,8
31,3
32,6
33,8
34,5
36,0
36,3
20,13
21,5
22,7
23,8
24,6
25,7
26,4
3,3
28,0
To: Condenser in/out water temperature [°C]
Ta: External air temperature (Dry Bulb) [°C]
RH: relative humidity [%]
kWF : cooling capacity [kW] (in conformity of EN14511)
kWe: electrical power input in kW (in conformity of EN14511)
The technical documentation can be improved all the times. Enerblue can update, time by time, all technical data in order to improve all necessary information for the customer.
5,2
4,7
4,2
3,8
3,3
3,1
2,9
2,7
2,4
5,1
4,6
4,2
3,8
3,5
3,2
2,9
2,8
2,5
5,2
4,7
4,3
4,0
3,7
3,4
3,0
2,9
2,6
5,6
5,0
4,5
4,1
3,8
3,5
3,2
2,9
2,7
5,3
4,8
4,3
3,9
3,5
3,2
3,0
2,7
2,5
5,4
4,8
4,4
4,0
3,6
3,3
3,0
2,7
2,5
5,2
4,7
4,2
3,9
3,5
3,2
3,0
3,0
2,5
Technical book
black ht
6
COOLING
AND
HEATING
CAPACITY
29
Ta [°C] / RH
MOD. To [°C]
10 / 70
15 / 70
20 / 60
25 / 60
30 / 50
35 / 50
KWT kWe COP KWT kWe COP KWT kWe COP KWT kWe COP KWT kWe COP KWT kWe COP
85
105
125
Technical book
Black ht
6
COOLING
AND
HEATING
CAPACITY
145
180
30
200
235
30/35
35/40
40/45
45/50
50/55
55/60
60/65
65/70
70/75
30/35
35/40
40/45
45/50
50/55
55/60
60/65
65/70
70/75
30/35
35/40
40/45
45/50
50/55
55/60
60/65
65/70
70/75
30/35
35/40
40/45
45/50
50/55
55/60
60/65
65/70
70/75
30/35
35/40
40/45
45/50
50/55
55/60
60/65
60/70
70/75
30/35
35/40
40/45
45/50
50/55
55/60
60/65
65/70
70/75
30/35
35/40
40/45
45/50
50/55
55/60
60/65
65/70
70/75
93,8
90,2
87,5
83,3
79,7
75,8
72,5
69,1
65,9
119,1
115,5
110,2
106,3
100,6
95,9
90,7
85,2
80,0
135,0
131,5
126,9
123,0
118,8
114,0
109,1
103,4
99,0
161,4
156,5
152,1
147,1
141,7
136,1
129,6
123,7
117,4
196,1
188,7
181,1
174,5
167,2
159,9
151,7
143,9
136,6
230,1
224,4
215,6
207,7
199,9
190,9
181,0
170,9
162,0
266,4
258,9
251,5
241,7
232,6
223,8
213,9
204,4
194,9
24,4
25,4
26,3
27,1
27,8
28,5
29,1
29,7
30,4
30,5
31,8
32,8
33,8
34,6
35,3
35,8
36,2
36,5
30,83
32,5
34,0
35,4
36,9
38,1
39,4
40,4
41,7
39,36
41,5
43,5
45,4
47,1
48,7
50,1
51,5
52,8
47,65
50,1
52,2
54,3
56,2
57,9
59,3
60,7
61,9
58,25
61,4
63,9
66,3
68,3
70,1
71,5
72,7
73,7
67,1
70,8
74,3
77,3
80,3
83,0
85,4
87,8
90,1
3,8
3,6
3,3
3,1
2,9
2,7
2,5
2,3
2,2
3,9
3,6
3,4
3,1
2,9
2,7
2,5
2,4
2,2
4,4
4,0
3,7
3,5
3,2
3,0
2,8
2,6
2,4
4,1
3,8
3,5
3,2
3,0
2,8
2,6
2,4
2,2
4,1
3,8
3,5
3,2
3,0
2,8
2,6
2,4
2,2
4,0
3,7
3,4
3,1
2,9
2,7
2,5
2,4
2,2
4,0
3,7
3,4
3,1
2,9
2,7
2,5
2,3
2,2
105,4
101,8
98,1
94,1
90,3
86,3
82,9
78,9
74,6
135,0
129,7
124,2
120,1
114,5
108,9
103,2
97,7
92,0
151,3
147,0
142,7
137,4
133,3
127,8
122,6
117,1
111,4
181,0
175,8
170,3
165,0
159,8
153,1
146,6
139,7
133,1
218,2
211,2
203,7
195,4
187,0
179,4
171,2
162,6
153,5
259,5
251,7
245,6
235,1
226,4
216,0
206,0
195,4
184,1
302,0
294,4
283,5
272,6
263,6
252,9
242,6
232,4
221,6
25,13
26,3
27,4
28,4
29,4
30,3
31,2
32,0
32,5
31,55
33,0
34,3
35,6
36,6
37,5
38,3
38,9
39,4
32,07
34,0
35,9
37,5
39,2
40,7
42,2
43,7
45,1
40,52
43,1
45,4
47,6
49,8
51,7
53,6
55,3
57,0
49,42
52,3
55,0
57,4
59,6
61,6
63,5
65,2
66,7
60,44
63,8
67,1
69,7
72,2
74,4
76,3
78,0
79,3
70,32
74,5
78,2
81,7
85,3
88,7
91,7
94,7
97,4
4,2
3,9
3,6
3,3
3,1
2,9
2,7
2,5
2,3
4,3
3,9
3,6
3,4
3,1
2,9
2,7
2,5
2,3
4,7
4,3
4,0
3,7
3,4
3,1
2,9
2,7
2,5
4,5
4,1
3,8
3,5
3,2
3,0
2,7
2,5
2,3
4,4
4,0
3,7
3,4
3,1
2,9
2,7
2,5
2,3
4,3
3,9
3,7
3,4
3,1
2,9
2,7
2,5
2,3
4,3
4,0
3,6
3,3
3,1
2,9
2,6
2,5
2,3
114,7
110,8
106,6
102,1
98,1
93,9
90,0
85,7
81,7
145,6
141,0
135,7
130,2
124,3
117,9
112,5
106,6
101,2
163,7
158,4
153,3
148,8
143,6
137,8
132,1
126,2
120,7
196,0
191,7
185,1
178,6
172,3
165,4
158,9
151,5
144,7
236,5
228,0
219,8
211,2
203,3
194,5
185,1
175,9
169,0
281,2
272,6
263,4
255,2
245,2
234,9
223,8
214,3
201,9
329,4
318,3
306,5
296,7
285,8
275,4
264,2
253,4
241,5
25,61
26,9
28,2
29,3
30,5
31,5
32,5
33,4
34,3
32,21
33,9
35,4
36,7
38,0
39,0
39,9
40,8
41,5
32,97
35,0
37,1
39,0
40,8
42,5
44,2
45,9
47,5
41,3
44,2
46,8
49,3
51,6
53,9
56,1
57,9
60,0
50,78
53,9
56,8
59,6
62,1
64,5
66,5
68,5
70,7
61,85
65,5
68,9
72,0
74,9
77,4
79,7
81,8
83,3
72,34
76,7
80,8
85,0
89,0
92,7
96,2
99,8
102,9
4,5
4,1
3,8
3,5
3,2
3,0
2,8
2,6
2,4
4,5
4,2
3,8
3,5
3,3
3,0
2,8
2,6
2,4
5,0
4,5
4,1
3,8
3,5
3,2
3,0
2,7
2,5
4,7
4,3
4,0
3,6
3,3
3,1
2,8
2,6
2,4
4,7
4,2
3,9
3,5
3,3
3,0
2,8
2,6
2,4
4,5
4,2
3,8
3,5
3,3
3,0
2,8
2,6
2,4
4,6
4,1
3,8
3,5
3,2
3,0
2,7
2,5
2,3
124,2
119,9
115,1
110,7
106,1
101,5
97,3
92,3
87,9
158,5
152,8
146,9
141,2
134,9
128,6
122,2
115,7
109,1
175,9
170,7
166,2
161,2
154,0
148,5
142,3
136,6
130,4
212,7
206,5
200,2
193,3
186,8
179,2
172,1
164,0
156,8
260,1
251,3
242,1
232,7
222,7
212,4
202,6
193,1
182,3
305,0
297,5
286,0
275,9
265,7
253,6
240,7
231,4
218,6
361,4
347,3
335,3
322,4
311,4
299,3
286,8
274,8
262,3
26,06
27,6
29,0
30,3
31,5
32,7
33,9
34,9
35,9
32,9
34,7
36,4
38,0
39,4
40,5
41,6
42,6
43,3
33,75
36,1
38,4
40,6
42,5
44,5
46,4
48,3
50,0
42
45,2
48,1
50,9
53,7
56,1
58,6
60,7
63,1
52,3
55,9
59,2
62,3
65,1
67,7
70,1
72,3
74,2
63,29
67,4
70,9
74,4
77,6
80,4
82,8
85,4
87,1
74,47
79,3
84,1
88,6
92,9
97,0
100,9
104,9
108,2
4,8
4,3
4,0
3,7
3,4
3,1
2,9
2,6
2,4
4,8
4,4
4,0
3,7
3,4
3,2
2,9
2,7
2,5
5,2
4,7
4,3
4,0
3,6
3,3
3,1
2,8
2,6
5,1
4,6
4,2
3,8
3,5
3,2
2,9
2,7
2,5
5,0
4,5
4,1
3,7
3,4
3,1
2,9
2,7
2,5
4,8
4,4
4,0
3,7
3,4
3,2
2,9
2,7
2,5
4,9
4,4
4,0
3,6
3,4
3,1
2,8
2,6
2,4
129,2
124,5
119,7
114,8
109,8
104,9
100,4
95,2
89,6
164,8
158,5
153,1
146,4
139,9
133,3
126,8
119,7
113,1
183,9
178,0
172,6
167,0
160,7
154,5
147,9
141,1
134,4
221,2
215,0
208,3
201,1
194,1
185,9
177,7
169,5
162,0
269,9
260,4
250,7
241,5
231,3
221,2
209,8
199,1
188,2
318,7
308,5
297,6
287,7
276,3
264,3
251,8
238,5
226,4
377,8
363,9
351,5
338,5
325,0
313,1
300,0
286,2
273,3
26,28
27,9
29,4
30,8
32,1
33,3
34,4
35,4
36,2
33,21
35,1
36,9
38,5
40,0
41,3
42,5
43,4
44,2
34,21
36,7
39,0
41,3
43,5
45,5
47,5
49,3
51,2
42,33
45,7
48,8
51,7
54,6
57,2
59,7
62,1
64,3
52,97
56,7
60,2
63,4
66,4
69,2
71,5
73,8
75,9
64,07
68,2
72,1
75,6
78,9
81,9
84,6
86,9
88,8
75,44
80,6
85,7
90,5
95,2
99,4
103,6
107,4
111,1
4,9
4,5
4,1
3,7
3,4
3,2
2,9
2,7
2,5
5,0
4,5
4,1
3,8
3,5
3,2
3,0
2,8
2,6
5,4
4,9
4,4
4,0
3,7
3,4
3,1
2,9
2,6
5,2
4,7
4,3
3,9
3,6
3,3
3,0
2,7
2,5
5,1
4,6
4,2
3,8
3,5
3,2
2,9
2,7
2,5
5,0
4,5
4,1
3,8
3,5
3,2
3,0
2,7
2,5
5,0
4,5
4,1
3,7
3,4
3,1
2,9
2,7
2,5
135,9
130,3
124,6
118,4
112,5
106,5
100,9
95,3
89,7
174,5
167,3
161,5
153,9
147,1
138,2
130,2
122,0
113,6
194,5
188,4
182,0
175,3
169,0
162,1
154,1
144,9
137,6
234,2
226,7
219,9
211,7
201,9
192,2
182,4
172,5
162,6
285,7
275,4
264,4
254,5
243,1
230,7
217,3
204,4
190,7
337,7
326,5
314,4
303,3
290,5
275,2
259,4
243,9
228,3
402,1
388,5
374,3
360,1
344,9
331,4
316,4
299,0
282,2
26,55
28,2
29,7
31,1
32,4
33,3
34,5
35,4
36,2
33,65
35,7
37,6
39,3
40,9
42,0
42,9
43,8
44,3
34,84
37,4
40,0
42,4
44,6
46,8
48,7
50,3
51,9
42,73
46,3
49,7
52,8
55,6
58,1
60,3
62,6
64,5
53,92
57,9
61,5
65,0
68,1
70,8
73,0
74,9
76,5
65,03
69,4
73,5
77,2
80,7
83,5
85,5
87,4
89,2
76,87
82,6
88,0
93,3
98,1
102,6
106,9
110,3
113,1
To: Condenser in/out water temperature [°C]
Ta: External air temperature (Dry Bulb) [°C]
RH: relative humidity [%]
kWF : cooling capacity [kW] (in conformity of EN14511)
kWe: electrical power input in kW (in conformity of EN14511)
The technical documentation can be improved all the times. Enerblue can update, time by time, all technical data in order to improve all necessary information for the customer.
5,1
4,6
4,2
3,8
3,5
3,2
2,9
2,7
2,5
5,2
4,7
4,3
3,9
3,6
3,3
3,0
2,8
2,6
5,6
5,0
4,5
4,1
3,8
3,5
3,2
2,9
2,6
5,5
4,9
4,4
4,0
3,6
3,3
3,0
2,8
2,5
5,3
4,8
4,3
3,9
3,6
3,3
3,0
2,7
2,5
5,2
4,7
4,3
3,9
3,6
3,3
3,0
2,8
2,6
5,2
4,7
4,3
3,9
3,5
3,2
3,0
2,7
2,5
Black HT 40 - 45 - 55 - 65
30
1408
1208
30
Pm
Pm
2390
Rp
Cdh
Cdh
Es
Uout
Rp
258
Rp
179
Rp
470
Rp
Ep
Lh
Lh
333
333
Rout
Uin
A
Uin
B
Rin
A *
Rin
252
C *
362
300
Technical book
black ht
1500
1500
7
300
DIMENSIONAL
DRAWING
SPAZI DI INSTALLAZIONE \ CLEARANCES
*
SOLO PER VERIONE DWS
ONLY DWS VERSION
Ep
QUADRO ELETTRICO
ELECTRICAL PANEL
Cdh
SCARICO CONDENSA
CONDENSATE DRAIN
Es
INGRESSO ALIMENTAZIONE ELETTRICA
ELECTRICAL SUPPLY INLET
Uin
INGRESSO ACQUA UTILIZZO
USER WATER INLET
Lh
FORI DI SOLLEVAMENTO
LIFTING HOLES
Uout
USCITA ACQUA UTILIZZO
USER WATER OUTLET
Pm
GRIGLIE DI PROTEZIONE
PROTECTIVE METAL MESH
Rin
USCITA ACQUA RECUPERO
RECOVERY WATER OUTLET
Rp
PANNELLO ASPORTABILE
REMOVABLE PANEL
Rout
USCITA ACQUA RECUPERO
RECOVERY WATER OUTLET
\
\
\
Rev. Data-Date
Dis.-Draftsman
Denominazione-Denomination
\
Visto-Checked by
ø35
1"1/2 BSPM (A)
2" BSPM (B)
1"1/2 BSPM
1"1/2 BSPM (A)
2" BSPM (C)
1"1/2 BSPM
Data-Date
05\09\2014
Sost. il dis.-Replace draw.
/
Materiale-Material
/
Spessore-Thickness
/
A
B
C
ACQUA UTILIZZO\RECUPERO SENZA MODULO IDRAULICO
USER\RECOVERY WATER WITHOUT HYDRAULIC MODULE
ACQUA UTILIZZO CON MODULO IDRAULICO 1P-2P
USER WATER WITH HYDRAULIC MODULE 1P-2P
ACQUA RECUPERO CON MODULO IDRAULICO 1P
RECOVERY WATER WITH HYDRAULIC MODULE 1P
DIMENSIONI / DIMENSIONS
LUNGHEZZA
WIDTH
PROFONDITA'
DEPTH
ALTEZZA
HEIGHT
1408
1208
2390
\
Descrizione revisione-Revision description
Codice-Code
SCHEMA DIMENSIONALE / DIMENSIONAL DRAWING
BLACK 35-45-50-55-60-65
Scala-Scale
1/30
CONNESSIONI IDRAULICHE / HYDRAULIC CONNECTION
Dis.-Draftsman
F. Sanavia
Visto-Checked by
N. Bettio
Sost. dal dis.-Replaced by draw.
/
Trattamento-Treatment
/
/
\
Disegno-Drawing
SD00275
Rev.
A
Foglio
di 1
N. 1
Sheet
of
Peso-Weight [kg]
Colore vernice-Painted colour
/
- Proprietà riservata, riproduzione vietata a termini di
legge.Copyright.
- Reserved property, reproduction prohibited accordin to
existent laws.Copyright.
The technical documentation can be improved all the times. Enerblue can update, time by time, all technical data in order to improve all necessary information for the customer.
31
Black HT /OD 40 - 45 - 55 - 65
280
30
1408
1208
1688
30
Pm
2108
Pm
Cdh
Es
Ep
Uout
Rp
258
Rp
179
Rp
470
Rp
Lh
Cdh
333
333
300
Lh
Technical book
Rout
Uin
A
Uin
B
Rin
A *
Rin
252
C *
362
Black ht
1500
1500
7
2000
DIMENSIONAL
DRAWING
SPAZI DI INSTALLAZIONE \ CLEARANCES
*
32
SOLO PER VERIONE DWS
ONLY DWS VERSION
Ep
QUADRO ELETTRICO
ELECTRICAL PANEL
Cdh
SCARICO CONDENSA
CONDENSATE DRAIN
Es
INGRESSO ALIMENTAZIONE ELETTRICA
ELECTRICAL SUPPLY INLET
Uin
INGRESSO ACQUA UTILIZZO
USER WATER INLET
Lh
FORI DI SOLLEVAMENTO
LIFTING HOLES
Uout
USCITA ACQUA UTILIZZO
USER WATER OUTLET
Pm
GRIGLIE DI PROTEZIONE
PROTECTIVE METAL MESH
Rin
USCITA ACQUA RECUPERO
RECOVERY WATER OUTLET
Rp
PANNELLO ASPORTABILE
REMOVABLE PANEL
Rout
USCITA ACQUA RECUPERO
RECOVERY WATER OUTLET
\
\
\
Rev. Data-Date
Dis.-Draftsman
Denominazione-Denomination
\
Visto-Checked by
ø35
1"1/2 BSPM (A)
Data-Date
05\09\2014
Sost. il dis.-Replace draw.
/
Materiale-Material
/
Spessore-Thickness
/
A
2" BSPM (B)
B
1"1/2 BSPM
C
ACQUA UTILIZZO\RECUPERO SENZA MODULO IDRAULICO
USER\RECOVERY WATER WITHOUT HYDRAULIC MODULE
ACQUA UTILIZZO CON MODULO IDRAULICO 1P-2P
USER WATER WITH HYDRAULIC MODULE 1P-2P
ACQUA RECUPERO CON MODULO IDRAULICO 1P
RECOVERY WATER WITH HYDRAULIC MODULE 1P
1"1/2 BSPM (A)
2" BSPM (C)
1"1/2 BSPM
DIMENSIONI / DIMENSIONS
LUNGHEZZA
WIDTH
PROFONDITA'
DEPTH
ALTEZZA
HEIGHT
1688
1208
2108
\
Descrizione revisione-Revision description
Codice-Code
SCHEMA DIMENSIONALE / DIMENSIONAL DRAWING
BLACK OD 35-45-50-55-60-65
Scala-Scale
1/30
CONNESSIONI IDRAULICHE / HYDRAULIC CONNECTION
Dis.-Draftsman
F. Sanavia
Visto-Checked by
N. Bettio
Sost. dal dis.-Replaced by draw.
/
Trattamento-Treatment
/
/
\
Disegno-Drawing
SD00276
Rev.
A
Foglio
di 1
N. 1
Sheet
of
Peso-Weight [kg]
Colore vernice-Painted colour
/
- Proprietà riservata, riproduzione vietata a termini di
legge.Copyright.
- Reserved property, reproduction prohibited accordin to
existent laws.Copyright.
The technical documentation can be improved all the times. Enerblue can update, time by time, all technical data in order to improve all necessary information for the customer.
Black HT 75 - 90 - 70 - 85 - 105 - 125
26
1210
26
3510
Rp
Ep
Rp
Es
Rp
390
Rp
187 337
423
602
Rp
Cdh
Lh
Lh
Cdh
*
Lh
Rout
Rin
Uout
Uin
*
1500
Rp
1000
1000
Technical book
1500
black ht
SPAZI D' INSTALLAZIONE \ CLEARANCES
7
DIMENSIONAL
DRAWING
DIMENSIONI - DIMENSIONS
LUNGHEZZA
WIDTH
PROFONDITA'
DEPTH
ALTEZZA
HEIGHT
3510
1262
1912
Ep
QUADRO ELETTRICO
ELECTRICAL PANEL
Cdh
SCARICO CONDENSA
CONDENSATE DRAIN
ø 30
Es
INGRESSO ALIMENTAZIONE ELETTRICA
ELECTRICAL SUPPLY INLET
Uin
INGRESSO ACQUA UTILIZZO
USER WATER INLET
2" 1/2
BSPF
Uout
USCITA ACQUA UTILIZZO
USER WATER OUTLET
2" 1/2
BSPF
PANNELLO ASPORTABILE
REMOVABLE PANEL
Rin
INGRESSO ACQUA RECUPERO
RECOVERY WATER INLET
2" 1/2
BSPF
FLUSSO ARIA
AIR FLOW
Rout
USCITA ACQUA RECUPERO
RECOVERY WATER OUTLET
2" 1/2
BSPF
Lh
Rp
FORI SOLLEVAMENTO
LIFTING HOLES
Ø40
33
SOLO PER VERSIONE DWS
* ONLY DWS VERSION
The technical documentation can be improved all the times. Enerblue can update, time by time, all technical data in order to improve all necessary information for the customer.
Black HT 145 - 180
1210
4610
Rp
Rp
Es
Rp
390
Rp
1916
A
Cdh
Cdh
Lh
Lh
Cdh
Lh
*
Rout
Rin
Uout
*
Uin
1500
Lh
187
337
423
604
1000
Ep
1000
Technical book
1500
Black ht
SPAZI D' INSTALLAZIONE \ CLEARANCES
7
Rp
Rp
VIEW A
DIMENSIONAL
DRAWING
34
Ep
QUADRO ELETTRICO
ELECTRICAL PANEL
Cdh
SCARICO CONDENSA
CONDENSATE DRAIN
ø 30
Es
INGRESSO ALIMENTAZIONE ELETTRICA
ELECTRICAL SUPPLY INLET
Uin
INGRESSO ACQUA UTILIZZO
USER WATER INLET
2" 1/2
BSPF
Uout
USCITA ACQUA UTILIZZO
USER WATER OUTLET
2" 1/2
BSPF
Lh
Rp
FORI SOLLEVAMENTO
LIFTING HOLES
PANNELLO ASPORTABILE
REMOVABLE PANEL
Ø40
FLUSSO ARIA
AIR FLOW
DIMENSIONI - DIMENSIONS
LUNGHEZZA
WIDTH
4610
PROFONDITA'
DEPTH
1210
ALTEZZA
HEIGHT
1916
The technical documentation can be improved all the times. Enerblue can update, time by time, all technical data in order to improve all necessary information for the customer.
Black HT 200 - 235
5332
4888
1214
444
Ep
Rp
Lh
Lh
Lh
Lh
Rin
Lh
523
Rp
192
Rp
Uout
Uin
188
850
168
194
Rout
390
2388
A
1500
Es
1000
2000
Rp
Rp
Technical book
1500
black ht
SPAZI D 'INSTALLAZIONE \ CLEARANCES
VIEW A
235
Ui n
Uout
Ri n
Rout
3" BSPF
3" BSPF
3" BSPM
3" BSPM
7
DIMENSIONAL
DRAWING
CONNESSIONI IDRAULICHE \ HYDRAULIC CONNECTION
DIMENSIONI / DIMENSIONS
LUNGHEZZA
WIDTH
PROFONDITA'
DEPTH
ALTEZZA
HEIGHT
5329
1211
2388
Ep
QUADRO ELETTRICO
ELECTRICAL PANEL
Uin
INGRESSO ACQUA UTENZA
USER WATER INLET
Es
ALIEMNTAZIONE ELETTRICA
ELECTRICAL SUPPLY
Uout
USCITA ACQUA UTENZA
USER WATER OUTLET
Lh
FORI DI SOLLEVAMENTO
LIFTING HOLES
Rin
INGRESSO ACQUA RECUPERO
RECOVERY WATER INLET
Rp
PANNELLO REMOVIBILE
REMOVABLE PANEL
Rout
USCITA ACQUA RECUPERO
RECOVERY WATER OUTLET
FLUSSO ARIA
AIR FLOW
The technical documentation can be improved all the times. Enerblue can update, time by time, all technical data in order to improve all necessary information for the customer.
35
032016_002
ENERBLUE S.r.l.
Sede legale
Via dell’Industria, 24
35028 PIOVE di SACCO - (Padova) Italy
Sede operativa
Via G. Puccini, 9
30010 CANTARANA di CONA - (Venezia) Italy
Tel. +39.0426.302051
Fax +39.0426.840000
info@enerblue.it
www.enerblue.it