PGFM Series (GFCI)
GFCI Ground Fault Protection Sensing Module
INTRODUCTION
The LineGard™ PGFM GFCI Sensing Module is a ground fault or equipment leakage sensing device
designed and manufactured by North Shore Safety, a leader in innovated safety products. The PGFM
operates in tandem with an approved Airpax LEL Series, UL 489 listed circuit breaker, with shunt trip
and auxiliary switch.
The combined assembly is recognized as a Class A UL 943 rated device. The sensing module is
available in models to operate at supply voltages of 120 VAC or 240VAC and can monitor single and
split phase circuits.
These devices meet the requirements of OSHA 29 CFR1926.404 (b)(1)(ii) and OSHA 29 CFR 1926.405 (a)
(2)(ii)(G) and are backed by a 2 year manufacturer’s warranty.
Airpax ™ LEL series
FEATURES
• Power and fault status indicators
• Provides identification of a ground fault vs. short circuit trip
• Chemical and UV resistant enclosure
• Trip level of sensing device 5mA ± 1mA Class A UL 943
• Sensing module operates at 120VAC or 240VAC, single phase
• Unit operating temperature is -35°C to +66°C
• Accommodates up to 2 wires, 10 AWG, twisting of the wires
is required
Specifications
Type
Operating Voltage
Interrupting Voltage
Sensing Coil Voltage Limit
Phase Interrupt
Interrupting Current
Trip Time of Combined Assembly
E-11 GFP - UL 943 Category FTTJ2 when used in tandem with Airpax LEL series UL 489
listed circuit breaker with shunt trip
120 VAC or 120/240 VAC
Rating of UL 489 listed circuit breaker
600 VAC maximum
Single (120 VAC 3 wire) and Split (120/240 VAC 4 wire)
Rating of UL 489 listed circuit breaker
100mS or less (60mS nominal)
Trip Level
5mA +/- 1mA
Frequency
50/60 Hz
Operating Temperature
Reset Type
-35°C to +66°C
Automatic on power up
Note: 1. Manual configuration should be specified if automatic start-up after power restoration of circuit power creates an unsafe condition.
2. As per UL 943 requirements, portable devices may require breaking of neutral during ground fault detection. Please contact the factory.
3. Please contact Airpax for optional ELCI, UL 1053 compliant devices.
209
PGFM Series - Introduction
http://airpax.sensata.com/
Ground Fault / Equipment Leakage
Sensing Module Dimensions:
Circuit Schematic (examples):
Single Phase 120VAC (Hot, Neutral, GRND)
3.41
[86.6]
Circuit
Breaker
Part #
Auto PGFM-111B
Man. PGFM-110B
LOAD
120VAC GFCI
Sensing Module
Split Phase 120/240VAC (L1, L2, Neutral, GRND)
Part #
Auto PGFM-111B
Man. PGFM-110B
LINE
White
LINE
White
Black
Yellow (Shunt)
GRND
1.30
[33.0]
2.18
[55.4]
NO
C
L1
L2
N
N
2.62
[66.5]
3.67
[93.2]
LOAD
120VAC GFCI
Sensing Module
NO
C
H
2.52
[64.0]
Orange
shunt
jumper
Circuit
Breaker
Orange
shunt
jumper
System Neutral (N)
Part #
Auto PGFM-211B
Man. PGFM-210B
Notice: Current carrying wires must be
twisted together as they pass through
the sensing module
Orange
shunt
jumper
LOAD
System Neutral (N)
GRND
Single Phase 240VAC (L1, L2, GRND)
Circuit
Breaker
Black
Yellow (Shunt)
NO
C
240VAC GFCI
Sensing Module
LINE
L1
M3 inserts
Recommended torque 4 - 5
inch pounds
L2
Red
3.28
[83.3]
1 Product Type
Black
Yellow (Shunt)
GRND
PGFM - 1 1 0 - B - A1
6
Installation Kit*
A1
One or two pole circuit breaker
A2
Three pole circuit breaker
2 Operating Voltage
3 Configuration
4 Reset Type**
5 Assembly Options
1
120VAC
1
0
Manual
B
2
240VAC
1
Automatic
Shunt w/ Aux. Switch
Matching circuit breaker
(see below)
*Note: Installation kits are for mounting the module and connecting to the tandem circuit breaker.
A1 - Kit # 057-000-0001 = panel seal gasket, module mounting screws, instructions and jumper w/ two 90° quick connectors
A2 - Kit # 057-000-0002 = panel seal gasket, module mounting screws, instructions, jumper w/ one 90° quick connector, one straight quick connector
**Note: Manual configuration should be specified if automatic power-up, after power restoration of circuit power, could create an unsafe condition.
To determine a matching circuit breaker for use in tandem with
the LineGard™ Sensing Module, please contact us directly
or your local Sensata Representative for assistance with the
appropriate identifying part number.
http://airpax.sensata.com/
PGFM Series - Single Pole
210
PGFM Series (ELCI, Marine)
ELCI Marine Ground Fault Protection Sensing Module
INTRODUCTION
The LineGard™ PGFM product family provides ELCI (equipment leakage) ground fault sensing and is
designed and manufactured by North Shore Safety, a leader in innovative safety products. The PGFM
series operates in tandem with a Airpax ™ LEL series, UL 489 listed circuit breaker, with shunt trip and
auxiliary switch manufactured by Sensata Technologies.
The combined assembly of the PGFM and LEL series meets the requirements of ABYC E-11 for ground
fault protection and main shore power circuit protection.
The PGFM constantly monitors the current balance of the conductors (wires / cables) supplying power to
the load. When a ground fault of 27mA nominal (30 mA max) occurs, the PGFM uses the LEL’s shunt trip
coil to signal the breaker to trip.
Airpax ™ LEL series
FEATURES
• Power and fault status indicators
• Provides identification of a ground fault vs. short circuit trip
• Chemical and UV resistant enclosure
• Trip level of sensing device < 30mA (27mA nominal)
at trip time of < 100mS (60mS nominal) per E-11
• Module incorporates high frequency noise filtering
• Protection range and operating voltage:
0 - 50 Amps, 120 VAC, 120/240 VAC
• Unit operating temperature is -35°C to +66°C
• Accommodates up to 3 wires, 6 AWG, with no twisting
of the wires required
Specifications
Type
Operating Voltage
Interrupting Voltage
Sensing Coil Voltage Limit
Phase Interrupt
Interrupting Current
Trip Time of Combined Assembly
120 VAC or 120/240 VAC
Rating of UL 489 listed circuit breaker
600 VAC maximum
Single (120 VAC 3 wire), Split (120/240 VAC 4 wire) , 240VAC 3-wire (L1, L2, N)
120VAC, 50A, 5kAIC
120/240VAC, 50A, 5kAIC
100mS or less (60mS nominal)
Trip Level
27mA +/- 2mA
Frequency
50/60 Hz
Operating Temperature
Reset Type
211
E-11 GFP - UL 943 Category FTTJ2 when used in tandem with Airpax LEL series UL 489
listed circuit breaker with shunt trip
PGFM Series - Introduction
-35°C to +66°C
Automatic on power up
http://airpax.sensata.com/
Ground Fault / Equipment Leakage
AIRPAX™ LEL SERIES CIRCUIT BREAKER RATINGS (PER UL489)
Voltage
Current
Frequency
Short Circuit
Poles
125VAC
0.05 to 50 amps
50/60 Hz
5,000 amps
1 to 3
120/240VAC
.05 to 50 amps
50/60 Hz
5,000 amps
2 to 3
AIRPAX™ LEL SERIES CIRCUIT BREAKER Specifications
Moisture Resistance
MIL-STD-202, Method 106
Salt Spray (Corrosion)
MIL-STD-202, Method 101
Shock
MIL-STD-202, Method 213, Test Condition I with 100% rated current applied
Vibration
MIL-STD-202, Method 204, Test Condition A with 100% rated current applied
Approvals
UL489 Listed, CSA Certified, VDE Approved, CCC Approved, CE Compliant
LINEGARD™ PGFM SERIES ELCI Specifications
Salt Fog (Corrosion)
Shock
Vibration
Ignition Protection
ASTM B117
33CFR183.534 - modified to supply 5,000 shocks @ 25G,
instead of test standard of 1,000 shocks
MIL-STD-810 (random vibe 4G RMS), IEC 6945 (sine sweep 5 to 100 Hz for low frequency)
SAE J1171
ABYC E-11 ACCEPTABILITY
The LineGard™ PGFM ELCI module used in tandem with the Airpax™ LEL type circuit breaker meets the requirements of the ABYC
(American Boat and Yacht Council) E-11 standard covering AC and DC systems on boats. This standard states the following:
11.11.1
An Equipment Leakage Circuit Interrupter (ELCI) shall be installed with or in addtition to the main shore power disconnect
circuit breaker(s) or at the additional overcurrent protection as required by E-11.10.2.8.3, whichever is closer to the shore
power connection.
11.11.1.1 This device shall meet the requirements of UL 1053 Standard for Safety for Ground-Fault Sensing and Relaying Equipment
and the requirements of UL 943 Ground Fault Circuit Interrupters with the exception of trip level and trip time. Trip level shall
be set at a maximum of 30mA. The trip time shall be set at a maximum of 100ms.
http://airpax.sensata.com/
PGFM Series - Single Pole
212
WIRING DIAGRAM (120VAC APPLICATION)
NEUTRAL (white) to breaker line side NEUTRAL
HOT (black) to breaker line side HOT
NEUTRAL
(white)toto
tobreaker
breakerauxiliary
line side
sideswitch
NEUTRAL
SHUNT
(yellow)
(NO terminal)
NEUTRAL
(white)
breaker
line
NEUTRAL
HOT
HOT (black)
(black) to
to breaker
breaker line
line side
side HOT
HOT
SHUNT (yellow)
(yellow) to
to breaker
breaker auxiliary
auxiliary switch
switch (NO
(NO terminal)
terminal)
SHUNT
NEUTRAL (white) from power supply (source)
NEUTRAL (white) to breaker line input
NEUTRAL
HOT (white)
(black) from
NEUTRAL
(white)
from power
power supply
supply (source)
(source)
NEUTRAL
(white)
to
line
HOT
(black)
to breaker
line input
NEUTRAL
(white)
to breaker
breaker
line input
input
HOT (black)
(black) from
from power
power supply
supply (source)
(source)
HOT
HOT (black)
(black) to
to breaker
breaker line
line input
input
HOT
WIRING DIAGRAM (240 VAC APPLICATION)
L1 (black) to breaker line side L1
L2 (red) to breaker line side L2
L1 (black)
(black)
to breaker
breaker
line side
side
L1
SHUNT
(yellow)
to breaker
auxiliary
switch (NO terminal)
L1
to
line
L1
L2
L2 (red)
(red) to
to breaker
breaker line
line side
side L2
L2
SHUNT (yellow)
(yellow) to
to breaker
breaker auxiliary
auxiliary switch
switch (NO
(NO terminal)
terminal)
SHUNT
L1 (black) from power supply (source)
L1 (black) to circuit breaker line input
L1L2
(black)
from power
power supply
(red) from
supply (source)
(source)
L1
(black)
L1 (black)
(black)
to
circuit
breaker
line
input
L2
(red)
toto
circuit
breaker
line
input
L1
circuit
breaker
line
input
L2
L2 (red)
(red) from
from power
power supply
supply (source)
(source)
WIRING DIAGRAM (120/240 VAC APPLICATION)
L2
L2 (red)
(red) to
to circuit
circuit breaker
breaker line
line input
input
L1 (black) to breaker line side L1
NEUTRAL (white) to breaker line side NEUTRAL
L1
to
line
L1
SHUNT
(yellow)
to breaker
auxiliary
switch (NO terminal)
L1 (black)
(black)
to breaker
breaker
line side
side
L1
NEUTRAL
NEUTRAL (white)
(white) to
to breaker
breaker line
line side
side NEUTRAL
NEUTRAL
SHUNT (yellow)
(yellow) to
to breaker
breaker auxiliary
auxiliary switch
switch (NO terminal)
terminal)
SHUNT
L1 (black) to circuit breaker(NO
line input
L1 (black) from power supply (source)
L1
(black)
circuit
breaker
line
input
L2
toto
circuit
breaker
line
input
L1 (red)
(black)
to
circuit
breaker
line
input
L1
(black)
(red) from
L1L2
(black)
from power
power supply
supply (source)
(source)
(red) from
from power
power supply
supply (source)
(source)
NEUTRALL2
(white)
L2
(red)
NEUTRAL
NEUTRAL (white)
(white) from
from power
power supply
supply (source)
(source)
213
PGFM Series - Wiring Diagrams
NEUTRAL
- may orline
mayinput
not require a circuit
L2 (red)
(red) to
to(white)
circuit breaker
breaker
L2
circuit
line input
breaker contact, consult factory for determination
NEUTRAL (white)
(white) -- may
may or
or may
may not
not require
require aa circuit
circuit
NEUTRAL
breaker
breaker contact,
contact, consult
consult factory
factory for
for determination
determination
http://airpax.sensata.com/
Ground Fault / Equipment Leakage
WIRING DIAGRAM (ORANGE JUMPER WIRE FOR CIRCUIT BREAKER)
LINE
C
NO
LOAD
INSTALLATION INSTRUCTIONS
TESTING AND TROUBLESHOOTING
1.Read and follow all instructions
2.Identify all the features and wires (see drawings)
3.Identify line wires and load wires
4.Verify that the ratings on the device including the circuit
breaker match your field line ratings
5.Strip wires to 5/8”, or as recommended for your connections
(module may include field terminations)
6.Choose the right wiring application (120VAC or 120/240VAC
split phase) and connect wires according to diagrams
7.Place supplied test instruction label in close proximity to the
ground fault sensing module mounting location.
In the normal operating state, the PGFM green LED is “ON” and
circuit breaker is in the “ON” position.
NOTE: The ground wire should be connected externally. The
Ground wire does not enter or exit the ground fault sensing
module. Although the PGFM does not require ground to operate,
ground connection is recommended and should be made at
junction box.
!
1.Press “TEST” button: Green LED should go “OFF” and red LED
should come “ON” and circuit breaker should trigger to “OFF”
position
2.If sensing device LED or breaker does not trip or change state,
DO NOT USE and consult an electrician for assistance
3.Press “RESET” button: Red LED should turn “OFF” and green
LED should turn “ON”
4.Manually reset (switch) the circuit breaker to the “ON”
position to restore circuit power
WARNING: If the test fails, do not use this GFCI. Consult a
qualified electrician for repair or replacement.
DANGER!
Hazard of electrical shock, burn or explosion. Disconnect power at main power feed before
you start installation. Failure to do so may cause severe shock, personal injury, or death.
http://airpax.sensata.com/
PGFM Series - Installation, Testing, Troubleshooting
214
DIMENSIONAL DRAWINGS (PGFM MARINE)
.710 [18.03] DIAMETER LARGE
ENOUGH FOR (3) 6GA. WIRES
16 GA. WIRE 105 DEGREES C
UL STYLE 1015 / 1230 600V
CSA TEW 10 IN LONG +/- 1 IN
COLOR: WHITE 120V RED 240V
0.007 [0.18]
16 GA. WIRE 105 DEGREES C
UL STYLE 1015 / 1230 600V
CSA TEW 10 IN LONG +/- 1 IN
COLOR: BLACK 120V BLACK 240V
16 GA. WIRE 105 DEGREES C
UL STYLE 1015 / 1230 600V
CSA TEW 10 IN LONG +/- 1 IN
COLOR: YELLOW 120V YELLOW 240V
WITH QUICK DISCONNECT MOLEX PN
19006-0015 OR EQUIVALENT
M3.0 x .5 THREADED BRASS
INSERTS FOR MOUNTING
(2) PLACES
1.850 [46.99]
2.353 [59.77]
1.320 [33.53]
0.657 [16.68]
2.655 [67.44] DIAMETER
2.788 [70.82] DIAMETER
DIMENSIONAL DRAWINGS (EXAMPLE OF LEL, TYPICAL 2-POLE CONFIGURATION)
.250
[6.35]
C & NO
.030
[0.76]
1.147
[29.13]
.281
[7.14]
2.438 MAX.
[61.93]
.648
1.055 [16.46]
[26.80]
2.560
[65.02]
32°
C NO NC
32°
2.490
[63.25]
.220
[5.59]
1.438
[36.53]
2.060
[52.32]
OFF
4X M5 SCREW
.142
[3.61]
215
.140
[3.56]
ON
1.940
[49.28]
Panel Mounting Detail
Tolerance ±.005 [.13] unless noted.
4X M3 ISO THD.
.140 [3.56] DEEP
.402
[10.21]
20
1REC5
.356
[9.03]
.250
[6.35]
.721
[18.31]
.187
[4.75]
PGFM Series - Dimensional Drawings
.955
[24.25]
1.859
[47.22]
1.515 MAX.
[38.48]
.750
[19.05]
.690
[17.53]
http://airpax.sensata.com/
Ground Fault / Equipment Leakage
DECISION TABLES (PGFM Series)
1 Product Type
PGFM - 1 1 1 - B - A1 - 188
7
Physical Shape
-188
2 Operating Voltage
3 Configuration
4 Reset Type
5 Assembly Options
1
120VAC
1
1
B
2
240VAC
Shunt w/ Aux. Switch
Automatic
Round Configuration
6
Installation Kit
A1
Jumper Wire
Matching circuit breaker
(see below)
COMPATIBLE AIRPAX™ CIRCUIT BREAKER PART NUMBERS
AMPS
2 Pole Break
120/240 VAC
2 Pole Break
120/240 VAC
3 Pole Break
120/240 VAC
Trip Coil
30
LEL12-1REC5-37583-30-G1-V
—
LEL121-1REC5-37275-30-G1-V
120V
30
—
LEL12-1REC5-37583-30-G2-V
—
240V
50
LELK12-1REC5-37583-50-G1-V
—
LELK121-1REC5-37275-50-G1-V
120V
50
—
LELK12-1REC5-37583-50-G2-V
—
240V
* All breakers with the exclusion of the 50 amp breakers come standard with #10-32 screw terminals.
* 50 amp breakers come standard with #10-32 stud terminals.
Contact factory for additional constructions and part numbers
http://airpax.sensata.com/
PGFM Series - Decision Tables
216
PGFP Series
15 Amp Plug Series GFCI / ELCI
INTRODUCTION
The LineGard™ 15 Amp Plug Series is a ground fault circuit interrupter designed and manufactured by North Shore Safety, Ltd., a
leader in innovated safety products. The PGFP product is rated for 15 amps at 120 VAC and available in either manual (safe start) or
automatic reset configuration.
Standard offerings include products geared for maintenance repair organizations (MRO), original equipment manufacturers (OEM)
or general portable power applications. MRO products are supplied with heavy-duty 12/3 conductor high flex (indoor/outdoor) safety
yellow cable (SJTW type) capable of withstanding heavy trade or industrial use. OEM products are configured with robust 14/3
conductor (indoor/outdoor) black cable (SJTW type) for integration into trade related equipment. All products are industrial/trade
grade tough and are backed by a 2 year manufacturer’s warranty. Note that any cord or equipment updated with this device becomes
OSHA compliant for power usage in a confined space and NEC compliant to NEC 590.6 (a) and (b).
FEATURES
•
•
•
•
•
•
•
•
•
Bright LED power indicator
Recessed interface buttons reduce damage and
nuisance tripping from rough service
High strength polycarbonate housing
Class A cULus 943 listed with load side connector
assemblies
Assemblies without load side connectors are UL
recognized for use under UL 943
NEMA 3R rated (indoor / outdoor use)
Assembly is rated for 15 amps / 120 VAC
Available in automatic or manual reset configurations*
Available with single or tri-tap plug assembly
Specifications
Listing Type
Rated Supply Voltage
Rated Current
Trip Level, Class A
Operating Frequency
1
Reset Type
Ground Trip Current
Overload Current
Insulation Voltage
Endurance Operations
cULus Listed Class A
UL 943
120VAC
Up to 15 Amps or rating of wiring device
and/or cable
5mA +/– 1mA (UL 943)
60 Hz
Automatic or Manual
4 mA to 6 mA
90 Amps @ 125VAC
1,500 VRMS for 1 minute
3000 operations
1. Manual configuration should be specified if automatic start-up after power
restoration of circuit power creates an unsafe condition.
2. Integrated or replacement cable must be indoor/outdoor 3-conductor cable of type
ST, SJT, SE, SJE, SO or SJO
217
PGFI Series - 15 Amp Plug Series
http://airpax.sensata.com/
Confined Space
Construction Sites
Application Opportunities:
Electrical wet locations
Power generators
Agricultural equipment
Outdoor electrical equipment
Cement cutting equipment
Portable electric heaters
Submersible pumps
Pipeline heaters
Automotive garages
Industrial part washers
Outdoor signage
Vending equipment
OSHA 29 CFR 1926.404 (b)(1)(ii),
OSHA 29 CFR 1926.405 (a)(2)(ii)(G)
(NEC 590.6)
Commercial Garages
(NEC 511.12)
Outdoor Signs
(NEC 600.10)
Fountains & Water
Displays
(NEC 680.58)
Spa & Hot Tubs
(NEC 680.40)
Marinas & Boat Yards
Ground Fault / Equipment Leakage
RELATED CODES
(NEC 555.3)
DECISION TABLES
PGFP - M11 0 K Y - ST2
1 Product Type
6 Cable Configuration
No designation
No cable required
(field wireable)
2 Reset Type
(1)
M11
Manual
A11
Automatic
Note:
3 Cable Gauge
4 Cable Type
No designation
No cable required
(field wireable)
5 Connector
No designation
No cable required
(field wireable)
No designation
No cable required
(field wireable)
0
12 gauge, 3 conductor
K
SJTW (yellow)
Y
cULus 943 Listed
1
14 gauge (15 amp)
J
SJ00W (black)
N No connector
2
16 gauge (13 amp)
3
18 gauge (10A)
ST2
Single-tap, 2’ yellow cable
TT2
Tri-tap, 2’ yellow cable
ST25
Single-tap, 25’ yellow cable
TT25
Tri-tap, 25‘ yellow cable
ST50
Single tap, 50’ yellow cable
FL __
Flying leads, specify cable
length in feet
1. Manual configuration should be specified if automatic power-up, after power restoration of circuit power, could create an unsafe condition.
2. Integrated or replacement cable must be indoor/outdoor 3-conductor cable of type ST, SJT, SE, SJE, SO or SJO
3. Custom cord sets are available. Please consult Airpax for other options
Tri-tap
http://airpax.sensata.com/
OEM Cordset (SJOOW)
Field wireable
PGFI Series - 15 Amp Plug Series
218
PGFI Series
15 Amp Portable Series GFCI / ELCI
INTRODUCTION
The LineGard™ 15 Amp In-Line Series is a ground fault circuit interrupter designed and manufactured by North Shore Safety, Ltd.,
a leader in innovative safety products. The 15 amp PGFI product is rated at 120 VAC and available in either manual (safe start) or
automatic reset configuration.
Standard offerings include products geared for maintenance repair organizations (MRO), original equipment manufacturers (OEM)
or general portable power applications. MRO products are supplied with heavy-duty 12/3 conductor high flex (indoor/outdoor) safety
yellow cable (SJTW type) capable of withstanding heavy trade or industrial use. OEM products are configured with robust 14/3
conductor (indoor/outdoor) black cable (SJTW type) for integration into trade related equipment. All products are industrial/trade
grade tough and are backed by a 2 year manufacturer’s warranty. These devices meet the requirements of OSHA 29 CFR 1926.404(b)(1)
(ii) & OSHA 29 CFR 1926.405(a)(2)(ii)(G) and additionally meet the requirements of NEC 590.6(a) and (b).
FEATURES
• Bright LED power indicator
• Recessed interface buttons reduce damage and
nuisance tripping from rough service
• High strength polycarbonate housing
• Class A cULus 943 listed with load side connector
assemblies
• NEMA 3R rated (indoor / outdoor use)
• Assembly is rated for 15 amps / 120 VAC
• Available in automatic or manual reset configurations*
• Available with single or tri-tap plug assembly
• 2-year manufacturer’s warranty
Specifications
Listing Type
Rated Supply Voltage
Rated Current
Trip Level, Class A
Operating Frequency
1
Reset Type
Ground Trip Current
Overload Current
Insulation Voltage
Endurance Operations
cULus Listed Class A
UL 943
CSA 22.2 No. 144
120VAC
Up to 15 Amps or rating of wiring device
and/or cable
5mA +/– 1mA (UL 943)
60 Hz
Automatic or Manual
4 mA to 6 mA
90 Amps @ 125VAC
1,500 VRMS for 1 minute
3000 operations
1. Manual configuration should be specified if automatic start-up after power
restoration of circuit power creates an unsafe condition.
2. Integrated or replacement cable must be indoor/outdoor 3-conductor cable of type
ST, SJT, SE, SJE, SO or SJO
219
PGFI Series - 15 Amp In-Line Series
http://airpax.sensata.com/
Confined Space
Construction Sites
Application Opportunities:
(NEC 590.6)
Commercial Garages
(NEC 511.12)
Outdoor Signs
(NEC 600.10)
Fountains & Water
Displays
(NEC 680.58)
Spa & Hot Tubs
(NEC 680.40)
Marinas & Boat Yards
Electrical wet locations
Power generators
Agricultural equipment
Outdoor electrical equipment
Cement cutting equipment
Portable electric heaters
Submersible pumps
Pipeline heaters
Automotive garages
Industrial part washers
Outdoor signage
Vending equipment
OSHA 29 CFR 1926.404 (b)(1)(ii),
OSHA 29 CFR 1926.405 (a)(2)(ii)(G)
(NEC 555.3)
Ground Fault / Equipment Leakage
RELATED CODES
DECISION TABLES
PGFI - M04 0 K Y - ST2
1 Product Type
6 Cable Configuration
No designation
No cable required
(field wireable)
2 Reset Type
(1)
M04
Manual
A04
Automatic
*Note:
3 Cable Gauge
4 Cable Type
No designation
No cable required
(field wireable)
0
12 gauge, 3 conductor
1
14 gauge (15 amp)
2
16 gauge (13 amp)
3
18 gauge (10A)
5 Connector
No designation
No cable required
(field wireable)
No designation
No cable required
(field wireable)
K
J
SJTW (yellow)
Y
SJ00W (black)
N No connector
cULus 943 Listed
ST2
Single-tap, 2’ yellow cable
TT2
Tri-tap, 2’ yellow cable
ST25
Single-tap, 25’ yellow cable
TT25
Tri-tap, 25’ yellow cable
ST50
Single tap, 50’ yellow cable
FL __
Flying leads, specify cable
length in feet
1. Manual configuration should be specified if automatic power-up, after power restoration of circuit power, could create an unsafe condition.
2. Integrated or replacement cable must be indoor/outdoor 3-conductor cable of type ST, SJT, SE, SJE, SO or SJO
3. Custom cord sets are available. Please consult Airpax for other options
Single Tap (SJTW)
http://airpax.sensata.com/
Tri-Tap (SJTW)
PGFI Series - 15 Amp In-Line Series
220
PGFI Series
20 Amp Portable Series (Cord) GFCI / ELCI
INTRODUCTION
The LineGard™ 20 Amp Portable Series is an industrial grade ground fault circuit interrupter designed and manufactured by North
Shore Safety, Ltd., a leader in innovated safety products. This product is the “Go Anywhere” protection device. Rated for 20 amps and
available at 120 VAC, 240 VAC, 208 VAC, or 277 VAC (UL 1053 compliant), the device is also available with either manual (safe start) or
automatic reset configuration. Standard offerings include products with plug and connector or flying leads for field configuring which
can be constructed into stand-alone cord sets or equipment integrated power supply cords. The product series is well suited for wet
location use with an achieved NEMA 4X rating.
Note that any power cord integrated with this device becomes OSHA compliant for portable power usage in confined space: OSHA 29
CFR 1926.404(b)(1)(ii) and 29 CFR 1926.405(a)(2)(ii)(G). Additionally, this product meets the requirements of NEC 590.6(a) & (b).
FEATURES
• Power and fault status indicators
•
•
•
Electro-mechanically latched contacts will not
de-latch under rough service usage
Chemical and UV resistant enclosure
Class A cULus 943 listed
• NEMA 4X rated (indoor / outdoor use)
• Double insulated user interface for added safety
• Available in automatic or manual reset configurations*
• Available with wiring devices or flying leads
• 2-year manufacturer’s warranty
Specifications
Listing Type
Rated Supply Voltage
Rated Current
Trip Level, Class A
Operating Frequency
1
Reset Type
Ground Trip Current
Overload Current
Insulation Voltage
Endurance Operations
cULus Listed Class A
UL 943
CSA 22.2 No. 144
120 VAC, 240 VAC, 208 VAC,
277 VAC (UL 1053 compliant)
Up to 20 Amps or rating of wiring device
and/or cable
5mA +/– 1mA (UL 943)
60 Hz
Automatic or Manual
4 mA to 6 mA
90 Amps @ 125VAC
1,500 VRMS for 1 minute
3000 operations
1. Manual configuration should be specified if automatic start-up after power
restoration of circuit power creates an unsafe condition.
2. Integrated or replacement cable must be indoor/outdoor 3-conductor cable of type
ST, SJT, SE, SJE, SO or SJO
221
PGFI Series - 20 Amp Portable (Cord) Series
http://airpax.sensata.com/
Confined Space
Construction Sites
Application Opportunities:
(NEC 590.6)
Commercial Garages
(NEC 511.12)
Outdoor Signs
(NEC 600.10)
Fountains & Water
Displays
(NEC 680.58)
Spa & Hot Tubs
(NEC 680.40)
Marinas & Boat Yards
Electrical wet locations
Power generators
Agricultural equipment
Outdoor electrical equipment
Cement cutting equipment
Portable electric heaters
Submersible pumps
Pipeline heaters
Automotive garages
Industrial part washers
Outdoor signage
De-icing equipment (roof heaters)
OSHA 29 CFR 1926.404 (b)(1)(ii),
OSHA 29 CFR 1926.405 (a)(2)(ii)(G)
(NEC 555.3)
Ground Fault / Equipment Leakage
RELATED CODES
DECISION TABLES
PGFI - 2 2 0 1 N
1 Product Type
1
6 Connector
N
None
1
Locking (see notes)
2 Voltage
3 Ampacity
4 Reset Type
1
120 VAC
2
0
Manual
1
2’ yellow, 12/3, SJEOOW cable
2
240 VAC
1
Automatic
2
25’ yellow, 12/3, SJEOOW cable
9
208 VAC
3
50’ yellow, 12/3, SJEOOW cable
D 277 VAC
5
6’ yellow, 12/3, SJEOOW cable
Note:
20 amps
5 Cable Configuration
1. Manual configuration should be specified if automatic power-up, after power restoration of circuit power, could create an unsafe condition.
2. Units are configured with SJTW cable and molded locking non-watertight connectors configured to 20 Amps.
NEMA configurations for the 120 VAC and 208/240 VAC are L5-20 and L6-20 respectively. 277 VAC configurations are L7-20
3. Integrated or replacement cable must be indoor/outdoor 3-conductor cable of type ST, SJT, SE, SJE, SO or SJO
4. Custom cord sets and watertight connectors are available. Please consult Airpax
NEMA and IEC 309 Connectors available
http://airpax.sensata.com/
Flying Leads (SJOOW)
PGFI Series - 20 Amp Portable (Cord) Series
222
PGFI Series
30 Amp Portable Series (Cord) GFCI / ELCI
INTRODUCTION
The LineGard™ 30 Amp Portable Series is an industrial grade ground fault interrupter device designed and manufactured by North
Shore Safety, Ltd., a leader in innovated safety products.
Available with an operating voltage of 120 VAC, 208 VAC, 240 VAC or 277 VAC (UL 1053 compliant), this product can be integrated
during after-market equipment upgrades or used as a stand-alone portable cordset. All units are MADE IN THE USA and are listed
per UL 943 and CSA 22.2 No.144. Note that any power cord integrated with this GFCI becomes OSHA compliant for portable power
usage in confinded space: OSHA 29 CFR 1926.404 (b)(1)(ii) and OSHA 29 CFR 1926.405 (a)(2)(ii)(G). Additionally, these devices meet NEC
requirement 590.6 (a) and (b).
FEATURES
Specifications
Listing Type
• Power and fault status indicators
•
•
•
•
•
Double insulated user interface
Industrial design for rough service
Chemical and UV resistant enclosure
cULus Listed as a Class A GFCI per UL 943 and
CSA 22.2 No. 144
30 amp, 3-wire configurations in 120VAC, 208 VAC,
240 VAC or 277 VAC (UL 1053)
• NEMA 4X and 6P wet location rated (indoor / outdoor)
• Available in automatic or manual reset configurations*
Rated Supply Voltage
Rated Current
Trip Level, Class A
Operating Frequency
1
Reset Type
Response Time
Operating Temperature
Operating Voltage Range
Let-Go Voltage
Open Neutral Protection2
Grounded Neutral Protection2
cULus Listed Class A
UL 943
CSA 22.2 No. 144
120 VAC, 240 VAC, 208 VAC,
277 VAC (UL 1053 compliant)
Up to 30 Amps or rating of wiring
device and/or cable
5mA +/– 1mA (UL 943)
60 Hz
Automatic or Manual
25mS max
–35°C to 66°C
85% to 110% of rated VAC
60% of supply voltage
Trips upon loss of neutral
Trips if ground and neutral touch
at load side
1. Manual configuration should be specified if automatic start-up after power
restoration of circuit power creates an unsafe condition.
2. Applicable models only
223
PGFI Series - 30 Amp Portable (Cord) Series
http://airpax.sensata.com/
Confined Space
Construction Sites
Application Opportunities:
(NEC 590.6)
Commercial Garages
(NEC 511.12)
Outdoor Signs
(NEC 600.10)
Fountains & Water
Displays
(NEC 680.58)
Spa & Hot Tubs
(NEC 680.40)
Marinas & Boat Yards
Electrical wet locations
Power generators
Agricultural equipment
Outdoor electrical equipment
Cement cutting equipment
Portable electric heaters
Submersible pumps
Pipeline heaters
Automotive garages
Industrial part washers
Outdoor signage
De-icing equipment (roof heaters)
OSHA 29 CFR 1926.404 (b)(1)(ii),
OSHA 29 CFR 1926.405 (a)(2)(ii)(G)
(NEC 555.3)
Ground Fault / Equipment Leakage
RELATED CODES
DECISION TABLES
PGFI - 2 3 0 1 N
1 Product Type
1
6 Connector
N
None
1
Locking
2 Voltage
3 Ampacity
4 Reset Type
1
120 VAC
3
0
Manual
1
2’ yellow, 10/3, SJEOOW cable
2
240 VAC
1
Automatic
2
25’ yellow, 10/3, SJEOOW cable
9
208 VAC
3
50’ yellow, 10/3, SJEOOW cable
D 277 VAC
5
6’ yellow, 10/3, SJEOOW cable
Note:
30 amps
(see notes)
5 Cable Configuration
1. Manual configuration should be specified if automatic power-up, after power restoration of circuit power, could create an unsafe condition.
2. Units are configured with SJTW cable and molded locking non-watertight connectors configured to 30 Amps.
3. Custom cord sets are available. Please consult Airpax for other options
NEMA and IEC 309 Connectors available
http://airpax.sensata.com/
PGFI Series - 30 Amp Portable (Cord) Series
224
PGFI Series
30 Amp Multi-Phase Portable Series (Cord) GFCI / ELCI
INTRODUCTION
The LineGard™ 30 Amp Portable Series is an industrial grade ground fault interrupter device designed and manufactured by North
Shore Safety, Ltd., a leader in innovated safety products.
Available with an operating voltage of 120/240 VAC, 3Ø 120/208 VAC, 3Ø 240 VAC (certified to CSA 22.2 only) or 3Ø 208 VAC, 3Ø 277
VAC (UL 1053 compliant). This product can be integrated during after-market equipment upgrades or used as a stand-alone portable
cordset. All units are MADE IN THE USA and are listed per UL 943 and CSA 22.2 No.144. Note that any power cord integrated with
this GFCI becomes OSHA compliant for portable power usage in confinded space: OSHA 29 CFR 1926.404 (b)(1)(ii) and OSHA 29 CFR
1926.405 (a)(2)(ii)(G). Additionally, these devices meet NEC requirement 590.6 (a) and (b).
FEATURES
Specifications
Listing Type
• Power and fault status indicators
•
•
•
•
•
Double insulated user interface
Industrial design for rough service
Chemical and UV resistant enclosure
cULus Listed as a Class A GFCI per UL 943 and
CSA 22.2 No. 144
30 amp configurations in 120/240 VAC 4-wire,
3Ø 120/208 VAC 5-wire, 3Ø 240 VAC 4-wire,
3Ø 208 VAC 4-wire, 3Ø 277 VAC 4-wire (UL 1053)
Rated Supply Voltage
120/240 VAC, 3Ø 120/208 VAC,
3Ø 240 VAC (CSA only),
3Ø 208 VAC, 3Ø 277 VAC (UL 1053)
Rated Current
Up to 30 Amps or rating of wiring
device and/or cable
Horse Power
1HP @ 120 VAC, 3HP @ 240 VAC
Trip Level, Class A
• NEMA 4X and 6P wet location rated (indoor / outdoor)
• Available in automatic or manual reset configurations*
cULus Listed Class A
UL 943, UL 1053
CSA 22.2 No. 144
Phase
Operating Frequency
Reset Type1
Response Time
Operating Temperature
Operating Voltage Range
Let-Go Voltage
Open Neutral Protection
Grounded Neutral Protection
5mA +/– 1mA
Dual voltage and 3 phase
60 Hz
Automatic or Manual
25mS max
–35°C to 66°C
85% to 110% of rated VAC
60% of supply voltage
Trips upon loss of neutral
Trips if ground and neutral touch
at load side
1. Manual configuration should be specified if automatic start-up after power
restoration of circuit power creates an unsafe condition.
225
PGFI Series - 30 Amp Multi-Phase Portable (Cord) Series
http://airpax.sensata.com/
Confined Space
Construction Sites
Application Opportunities:
(NEC 590.6)
Commercial Garages
(NEC 511.12)
Outdoor Signs
(NEC 600.10)
Fountains & Water
Displays
(NEC 680.58)
Spa & Hot Tubs
(NEC 680.40)
Marinas & Boat Yards
Electrical wet locations
Power generators
Agricultural equipment
Outdoor electrical equipment
Cement cutting equipment
Portable electric heaters
Submersible pumps
Pipeline heaters
Automotive garages
Industrial part washers
Outdoor signage
De-icing equipment (roof heaters)
OSHA 29 CFR 1926.404 (b)(1)(ii),
OSHA 29 CFR 1926.405 (a)(2)(ii)(G)
(NEC 555.3)
Ground Fault / Equipment Leakage
RELATED CODES
DECISION TABLES
PGFI - 4 3 0 9 N
1 Product Type
6 Connector
N
1
2
2 Voltage
3 Ampacity
4 Reset Type
C 120/240 VAC split Ø
3
0
Manual
A
2’ black, 10/4 SEOOW cable
1
Automatic
9
25’ black, 10/4 SEOOW cable
C
50’ black, 10/4 SEOOW cable
30 amps
4 120/208 VAC 3Ø
7 240 VAC 3Ø
5 Cable Configuration
None
8 208 VAC 3Ø
B 277 VAC 3Ø
*Note:
1. Manual configuration should be specified if automatic power-up,
after power restoration of circuit power, could create an unsafe condition.
2. 120/208 VAC 3Ø configurations use 10/5 SEOOW cable
Flying Leads (SEOOW)
http://airpax.sensata.com/
PGFI Series - 30 Amp Multi-Phase Portable (Cord) Series
226
PGFI Series
40, 50 & 60 Amp Portable Series (Cord) ELCI
INTRODUCTION
The LineGard™ 40, 50 and 60 Amp Portable Series is an industrial grade ground fault interrupter device designed and manufactured by
North Shore Safety, Ltd., a leader in innovated safety products. These devices are designed for industrial and trade applications such
as welders, pumps, motors and generators and come standard with selectable key switching for fault level threshold, power on and
reset type (automatic vs. manual) settings.
As configured the device has three fault threshold settings of 6mA, 10mA and 30mA, with all engineered trip times of 25mS or less.
These units come standard with a 6’ primary cord and a 6’ secondary cord length with flying leads for field configuring. Integrated
NEMA or IEC 309 wiring devices are also available as factory customs. The enclosure is configured with floor mount feet but is
additionally supplied with wall or surface mounted feet for more permanent installations. All units are MADE IN THE USA and are UL
1053 Compliant.
FEATURES
Specifications
Rated Supply Voltage
• Power and fault status indicators
•
•
•
•
•
•
•
Rated Current
Double insulated user interface
UL1053 compliant
Chemical and UV resistant enclosure
40, 50 and 60 amp configurations in 1Ø 120 VAC,
1Ø 240 VAC, 1Ø 208 VAC, 1Ø 277 VAC, 120/240 VAC,
3Ø 240 VAC, 3Ø 208 VAC, 3Ø 277 (Available with or
without neutral), 3Ø 480 VAC, 3Ø 600 VAC
Fault level key switch - max. trip threshold
6mA, 10mA, and 30mA
Surge protection optional
NEMA 4X wet location rated (indoor / outdoor)
Field selectable threshold @
6mA, 10mA and 30mA
Phase
Single, dual and three phase
1
Reset Type
Response Time
Operating Temperature
Operating Voltage Range
• Automatic or manual reset key switch
40 thru 60 Amps or rating of
wiring device and/or cable
Trip Level
Operating Frequency
1
120 VAC 1Ø to 600 VAC 3Ø
Let-Go Voltage
Open Neutral Protection
Grounded Neutral Protection
60 Hz
Automatic or Manual
25mS max
–35°C to 66°C
85% to 110% of rated VAC
60% of supply voltage
Trips upon loss of neutral
Trips if ground and neutral touch
at load side
1. Manual configuration should be specified if automatic start-up after power
restoration of circuit power creates an unsafe condition.
227
PGFI Series - 40, 50, 60 Amp Portable (Cord) Series
http://airpax.sensata.com/
Confined Space
Construction Sites
Application Opportunities:
(NEC 590.6)
Commercial Garages
(NEC 511.12)
Outdoor Signs
(NEC 600.10)
Fountains & Water
Displays
(NEC 680.58)
Spa & Hot Tubs
(NEC 680.40)
Marinas & Boat Yards
Electrical wet locations
Power generators
Agricultural equipment
Outdoor electrical equipment
Cement cutting equipment
Portable electric heaters
Submersible pumps
Pipeline heaters
Automotive garages
Industrial part washers
Outdoor signage
De-icing equipment (roof heaters)
OSHA 29 CFR 1926.404 (b)(1)(ii),
OSHA 29 CFR 1926.405 (a)(2)(ii)(G)
(NEC 555.3)
Ground Fault / Equipment Leakage
RELATED CODES
DECISION TABLES
PGFI - 1 5 4 5 N
1 Product Type
2 Voltage
6 Connectors
N
Flying leads
3 Ampacity
4 Power-up
5 Secondary cord
4
5 6’ Black, SEOOW
1 120 VAC 1Ø
2 240 VAC 1Ø
4
40 amps
5 480 VAC 3Ø
6 600 VAC 3Ø
5
50 amps
7 240 VAC 3Ø
8 208 VAC 3Ø
6
60 amps
9 208 VAC 1Ø
B 277 VAC 3Ø
C 120/240 VAC
D 277 VAC 1Ø
Key Switch
Auto / Manual
Contact Sensata for custom integrated connectors
http://airpax.sensata.com/
PGFI Series - 40, 50, 60 Amp Portable (Cord) Series
228
PGFS Series
30 Amp Permanent Series (Splice-In) GFCI/ELCI
INTRODUCTION
The LineGard™ 30 Amp Permanent Series is an industrial grade ground fault interrupter device designed and manufactured by North
Shore Safety, Ltd., a leader in innovated safety products. The unique design offers the flexibility of splicing in protection of a GFCI
anywhere within the length of the circuit run, making it ideal for both new and existing applications. Unlike breaker style GFCI’s which
have limitations of circuit length from the service panel, the PFGS series can be integrated directly into a circuit or paired in tandem
with an approved receptacle and enclosure.
Available with an operating voltage of 120 VAC, 240 VAC, 208 VAC, 277 VAC or 120/240 VAC, all units have 18” splicing leads and a 3/4”
NPT fitting to allow connection to 3/4” PVC, EMT, burial and flexible conduits. All units are MADE IN THE USA and are listed per UL 943
and CSA 22.2 No.144
FEATURES
Specifications
Listing Type
• Power and fault status indicators
•
•
•
•
•
•
Industrial design for rough service
Chemical and UV resistant enclosure
cULus Listed as a Class A GFCI per UL 943 and
CSA 22.2 No. 144
30 amp configurations in 120 VAC 3-wire,
240 VAC 3-wire, 208 VAC 3-wire, 277 VAC 3-wire, or
120/240 VAC 4-wire
NEMA 4X and 6P wet location rated (indoor / outdoor)
Available in automatic or manual reset configurations1
Rated Supply Voltage
Rated Current
Trip Level
Operating Frequency
Reset Type1
Response Time
Operating Temperature
Operating Voltage Range
Let-Go Voltage
Open Neutral Protection
Grounded Neutral Protection
cULus Listed Class A
UL 943
CSA 22.2 No. 144
120 VAC, 240 VAC, 208 VAC,
277 VAC, 120/240 VAC
Up to 30 Amps or rating of wiring
device and/or cable
5mA +/–1mA
60 Hz
Automatic or Manual
25mS max
–35°C to 66°C
85% to 110% of rated VAC
60% of supply voltage
Trips upon loss of neutral
Trips if ground and neutral touch
at load side
1. Manual configuration should be specified if automatic start-up after power
restoration of circuit power creates an unsafe condition.
229
PGFS Series - 30 Amp Permanent (Splice-In) Series
http://airpax.sensata.com/
Confined Space
Construction Sites
Application Opportunities:
Electrical wet locations
Power generators
Agricultural equipment
Outdoor electrical equipment
Cement cutting equipment
Portable electric heaters
Submersible pumps
Pipeline heaters
Automotive garages
Industrial part washers
Outdoor signage
De-icing equipment (roof heaters)
OSHA 29 CFR 1926.404 (b)(1)(ii),
OSHA 29 CFR 1926.405 (a)(2)(ii)(G)
(NEC 590.6)
Commercial Garages
(NEC 511.12)
Outdoor Signs
(NEC 600.10)
Fountains & Water
Displays
(NEC 680.58)
Spa & Hot Tubs
(NEC 680.40)
Marinas & Boat Yards
Ground Fault / Equipment Leakage
RELATED CODES
(NEC 555.3)
DECISION TABLES
1 Product Type
PGFS - 2 3 0 1 5
2 Voltage
3
Ampacity
4
Reset Type
1 120 VAC
3
30 amps
0
1
2 240 VAC
*Note:
1
6 Mounting Type
5
Panel mount
5
Fault Output Options
Manual
0
None
Automatic
1
Internal annunciation
3 120/240 VAC
2
120 VAC or 240 VAC
9 208 VAC
3
24 VDC
D 277 VAC
4
12 VDC
2
1. Manual configuration should be specified if automatic power-up, after power restoration of circuit power, could create an unsafe condition.
2. VAC fault outputs are at line voltage and are not GFCI protected (4-wire 120/240 VAC configuration is a 240 VAC output)
3. 3-mode surge protection is available. Please consult Airpax for other options
Flying Leads (Splice-in)
http://airpax.sensata.com/
PGFS Series - 30 Amp Permanent (Splice-In) Series
230
PGFS Series
30 Amp Multi-Phase Permanent Series (Splice-In) GFCI
INTRODUCTION
The LineGard™ 30 Amp Permanent Series is an industrial grade ground fault interrupter device designed and manufactured by North
Shore Safety, Ltd., a leader in innovated safety products. The unique design offers the flexibility of splicing in protection of a GFCI
anywhere within the length of the circuit run, making it ideal for both new and existing applications. Unlike breaker style GFCI’s which
have limitations of circuit length from the service panel, the PFGS series can be integrated directly into a circuit or paired in tandem
with an approved receptacle and enclosure.
Available with an operating voltage of 120/240 VAC dual voltage, 3Ø 120/208 VAC, 3Ø 240 VAC (certified to CSA 22.2 only), 3Ø 208 VAC or
3Ø 277 VAC (UL 1053 compliant), all units have 18” splicing leads and a 3/4” NPT fitting to allow connection to 3/4” PVC, EMT, burial and
flexible conduits. All units are MADE IN THE USA and are listed per UL 943 and CSA 22.2 No.144
FEATURES
• Power and fault status indicators
• Double insulated user interface
•
•
•
•
•
•
Industrial design for rough service
Chemical and UV resistant enclosure
cULus Listed as a Class A GFCI per UL 943 and
CSA 22.2 No. 144
30 amp configurations in 120/240 VAC 4-wire,
3Ø 120/208 VAC 5-wire, 3Ø 240 VAC 4-wire,
3Ø 208 VAC 4-wire, 3Ø 277 VAC 4-wire (UL 1053)
NEMA 4X and 6P wet location rated (indoor / outdoor)
Available in automatic or manual reset configurations1
Specifications
Listing Type
Rated Supply Voltage
cULus Listed Class A
UL 943
CSA 22.2 No. 144
120/240 VAC Dual Voltage, 120/208 VAC 3Ø, 240 VAC 3Ø
(CSA only), 208 VAC 3Ø,
277 VAC 3Ø (UL 1053)
Rated Current
Up to 30 Amps or rating of wiring
device and/or cable
Horse Power
1HP@120 VAC, 3HP@240 VAC
Trip Level
Operating Frequency
Reset Type1
Phase
Response Time
Operating Temperature
Operating Voltage Range
Let-Go Voltage
Open Neutral Protection
Grounded Neutral Protection
5mA +/–1mA
60 Hz
Automatic or Manual
Dual voltage and 3 phase
25mS max
–35°C to 66°C
85% to 110% of rated VAC
60% of supply voltage
Trips upon loss of neutral
Trips if ground and neutral touch
at load side
1. Manual configuration should be specified if automatic start-up after power
restoration of circuit power creates an unsafe condition.
2. Applicable models only
231
PGFS Series - 30 Amp Multi-Phase Permanent (Splice-In) Series
http://airpax.sensata.com/
Confined Space
Construction Sites
Application Opportunities:
(NEC 590.6)
Commercial Garages
(NEC 511.12)
Outdoor Signs
(NEC 600.10)
Fountains & Water
Displays
(NEC 680.58)
Spa & Hot Tubs
(NEC 680.40)
Marinas & Boat Yards
Electrical wet locations
Power generators
Agricultural equipment
Outdoor electrical equipment
Cement cutting equipment
Portable electric heaters
Submersible pumps
Pipeline heaters
Automotive garages
Industrial part washers
Outdoor signage
De-icing equipment (roof heaters)
OSHA 29 CFR 1926.404 (b)(1)(ii),
OSHA 29 CFR 1926.405 (a)(2)(ii)(G)
(NEC 555.3)
Ground Fault / Equipment Leakage
RELATED CODES
DECISION TABLES
1 Product Type
PGFS - 4 3 0 0 5
6 Mounting Type
5
2 Voltage
3 Ampacity
4 Reset Type
C 120/240 VAC split Ø
3
0
Manual
1
Automatic
30 amps
4 120/208 VAC 3Ø
1
Panel mount
5
Fault Output Options
0
None
7 240 VAC 3Ø
8 208 VAC 3Ø
B 277 VAC 3Ø
*Note:
1. Manual configuration should be specified if automatic power-up, after power restoration of circuit power, could create an unsafe condition.
Flying Leads (Splice-in)
http://airpax.sensata.com/
PGFS Series - 30 Amp Multi-Phase Permanent (Splice-In) Series
232
PGFS Series
40, 50, 60 Amp Permanent Series (Splice-In) GFCI / ELCI
INTRODUCTION
The LineGard™ 40, 50 and 60 Amp Permanent Series is an industrial grade ground fault interrupter device designed and manufactured
by North Shore Safety, Ltd., a leader in innovated safety products. These units are ideal for both new and existing circuit installations
and have a unique design that offers the flexibility of splicing this device anywhere within the length of a circuit run.(Note: ELCI only
protects downstream or “load side”) This convenience allows the installer to place this ELCI at an accessible location for the end user.
As configured the device has three fault threshold settings of 6mA, 10mA and 30mA, with all engineered trip times of 25mS or less.
These units come standard with 24” lead wires for electrical splicing and two 1” flexible conduit fittings for integration to 1” flexible or
burial conduit. All units are MADE IN THE USA and are UL 1053 Compliant.
FEATURES
• Power and fault status indicators
• Double insulated user interface
•
•
•
•
•
•
•
Chemical and UV resistant enclosure
UL 1053 Compliant
40, 50 and 60 amp configurations in 1Ø 120 VAC,
1Ø 240 VAC, 120/240 VAC, 3Ø 240 VAC, 3Ø 208 VAC,
3Ø 277 VAC (Available with or without neutral),
3Ø 277/480, 3Ø 480 VAC, 3Ø 600 VAC
Fault level key switch - max. trip threshold
6mA, 10mA, and 30mA
Surge protection optional
NEMA 4X wet location rated (indoor / outdoor)
Automatic or manual reset key switch1
• Xenon strobe indication on ground fault
Specifications
Listing Type
Rated Supply Voltage
Rated Current
Trip Level
Operating Frequency
1
Reset Type
Phase
Response Time
Operating Temperature
Operating Voltage Range
Let-Go Voltage
Open Neutral Protection
Grounded Neutral Protection
UL 1053 Compliant
120 VAC 1Ø to 600 VAC 3Ø
40 thru 60 Amps or rating of
wiring device and/or cable
Field selectable threshold @
6mA, 10mA and 30mA
60 Hz
Field selectable automatic or
manual1
Single, dual and 3 phase
25mS max
–35°C to 66°C
85% to 110% of rated VAC
60% of supply voltage
Trips upon loss of neutral
Trips if ground and neutral touch
at load side
1. Manual configuration should be specified if automatic start-up after power
restoration of circuit power creates an unsafe condition.
233
PGFS Series - 40, 50, 60 Amp Permanent (Splice-In) Series
http://airpax.sensata.com/
Confined Space
Construction Sites
Application Opportunities:
(NEC 590.6)
Commercial Garages
(NEC 511.12)
Outdoor Signs
(NEC 600.10)
Fountains & Water
Displays
(NEC 680.58)
Spa & Hot Tubs
(NEC 680.40)
Marinas & Boat Yards
Electrical wet locations
Power generators
Agricultural equipment
Outdoor electrical equipment
Cement cutting equipment
Portable electric heaters
Submersible pumps
Pipeline heaters
Automotive garages
Industrial part washers
Outdoor signage
De-icing equipment (roof heaters)
OSHA 29 CFR 1926.404 (b)(1)(ii),
OSHA 29 CFR 1926.405 (a)(2)(ii)(G)
(NEC 555.3)
Ground Fault / Equipment Leakage
RELATED CODES
DECISION TABLES
1 Product Type
PGFS - 4 5 4 5 6
6
Mounting
6
Surface Mount
3 Ampacity
4 Power-up
5 Fault Output Options
1 120 VAC 1Ø
2 240 VAC 1Ø
4
40 amps
4
5
4 120/208 VAC
5 480 VAC 3Ø
5
50 amps
6 600 VAC 3Ø
7 240 VAC 3Ø
6
60 amps
8 208 VAC 3Ø
9 208 VAC 1Ø
0 277/480 VAC
A 347/600 VAC
B 277 VAC 3Ø
C 120/240 VAC
2 Voltage
Key Switch
Auto / Manual
Alarm Strobe & SEL fault
D 277 VAC 1Ø
http://airpax.sensata.com/
PGFS Series - 40, 50, 60 Amp Permanent (Splice-In) Series
234
PGFR Series
15 / 20 Amp Linegard™ Series GFCI Duplex Receptacle
INTRODUCTION
The LineGard™ 15 / 20 Amp GFCI Duplex Receptacle is a ground fault circuit interrupter receptacle designed and manufactured by
North Shore Safety, Ltd., a leader in innovated safety products. The PGFR series product come standard with power indicator light and
series wire-through connections. Available in standard white and black, and come with decorative, impact-resistant nylon face plates.
2-year manufacturer’s warranty.
Specifications
Listing Type
Rated Supply Voltage
Rated Current
Trip Level
Operating Frequency
Response Time
Operating Temperature
Operating Voltage Range
UL Recognized,
Class A UL 943,
CSA 22.2 No. 144
120 VAC
Up to 20 Amps or rating of wiring device and/or cable
5mA +/– 1mA (UL 943)
60 Hz
25mS max
–35°C to 66°C
85% to 110% of rated VAC
DECISION TABLES
235
Order Number
Voltage Enclosure
PGFR-120
120 VAC
15 / 20 White
PGFR-120
120 VAC
15 / 20 Black
PGFR Series - 15 / 20 Amp GFCI Receptacle
http://airpax.sensata.com/
This document is generated from the AIRPAX™ full-line catalog #2455005000 printed in USA, January 2011
BUSINESS CENTERS
Sensata Technologies
807 Woods Road
Cambridge, MD 21613, USA
Phone: +1 410-228-1500
Brands: Airpax™
Sensata Technologies Holland B.V.
Kolthofsingel 8
7602 EM Almelo, The Netherslands
Phone: +31 546 87 95 55
Brands: Klixon™, Sensata Technologies™
Sensata Technologies Inc.
529 Pleasant Street
Attleboro, MA 02703, USA
Phone: +1 508-236-3287
Brands: Klixon™, Sensata Technologies™
Sensata Technologies China Co., Ltd.
Novel Plaza, 8th Floor
128 Nanjing Road West
Shaghai, 20003
People’s Republic of China
Phone: +86 21 23061500
Brands: Klixon™, Sensata Technologies™
Sensata Technologies
4467 White Bear Lake Parkway
St. Paul, MN 55110, USA
Phone: +1 800-553-6418
Brands: Dimensions™
Sensata Technologies Japan Ltd.
305, Tanagashira
Oyama-cho, Sunto-gun, Shizuoka-ken
Japan, 410-1396
Phone: +81 550 78 1211
Brands: Klixon™, Sensata Technologies™
Sensata Technologies Nihon-Airpax
6-3, Chi Yoda 5 Chome
Saitama-Ken
Japan, 350-0214
Phone: +81 492 83 7575
Brands: Airpax™
Sensata Technologies Korea Ltd.
29F, Trade Tower
159-1 SamSung-Dong, KangNam-Ku, Seoul
135-729, Korea
Phone: +81-2-551-2918
Brands: Klixon™, Sensata Technologies™
Important Notice: Sensata Technologies (Sensata) reserves the right to make changes to or discontinue any
product or service identified in this publication without notice. Sensata advises its customers to obtain the
latest version of the relevant information to verify, before placing any orders, that the information being
relied upon is current. Sensata assumes no responsibility for infringement of patents or rights of others
based on Sensata applications assistance or product specifications since Sensata does not possess full
access concerning the use or application of customers’ products. Sensata also assumes no responsibility for
customers’ product designs.
http://airpax.sensata.com/