Design Guidelines and Technical Standards

DESIGN GUIDELINES
AND
TECHNICAL STANDARDS
Date of Issuance: January 1, 2014
NORTHWESTERN UNIVERSITY
Design Guidelines and Technical Standards
TABLE OF CONTENTS
Introduction
PART 1 – DESIGN GUIDELINES
Site, Civil, Grounds
Utility Systems
Building – General
Sustainability
Sustainability Guidelines
Key Sustainable Guidelines for all Projects
PART 2 – TECHNICAL STANDARDS
DIVISION 01 – GENERAL REQUIREMENTS
Section 01 100
General Requirements
DIVISION 2 – EXISTING CONDITIONS
Section 24 119
Selective Demolition
DIVISION 3 – CONCRETE
Section 03 3000
Section 03 4000
Cast-in-Place Concrete
Precast Concrete
DIVISION 4 – MASONRY
Section 04 2000
Section 04 4600
Unit Masonry
Limestone
DIVISION 5 – METALS
Section 05 1200
Section 05 3100
Section 05 5000
Section 05 5100
Section 05 7230
Structural Steel Framing
Steel Decking
Metal Fabrications
Metal Stairs and Railings
Stair Treads and Nosings
DIVISION 6 – WOOD, PLASTICS, AND COMPOSITES
Section 06 1000
Section 06 4000
Rough Carpentry
Architectural Woodwork
Date of Issuance: January 1, 2014
TOC - 1
NORTHWESTERN UNIVERSITY
Design Guidelines and Technical Standards
DIVISION 7 – THERMAL AND MOISTURE PROTECTION
Section 07 2100
Section 07 2700
Section 07 3126
Section 07 5200
Section 07 5323
Section 07 5419
Section 07 6200
Section 07 7200
Section 07 9200
Thermal Insulation
Barriers (Firestopping)
Slate Shingles
Modified Bituminous Membrane Roofing
EPDM Roofing
PVC Roofing
Sheet Metal Flashing and Trim
Roof Accessories
Joint Sealants
DIVISION 8 – OPENINGS
Section 08 1113
Section 08 1416
Section 08 3113
Section 08 4113
Section 08 5000
Section 08 7100
Section 08 8000
Section 08 9200
Hollow Metal Doors and Frames
Wood Doors
Access Doors and Frames
Aluminum-Framed Entrances and Storefronts
Windows
Door Hardware
Glazing
Glazed Aluminum Curtain Wall System
DIVISION 9 – FINISHES
Section 09 2900
Section 09 3000
Section 09 6500
Section 09 6600
Section 09 6800
Section 09 9000
Gypsum Board
Tile
Resilient Flooring
Terrazzo Flooring
Carpet
Painting
DIVISION 10 – SPECIALTIES
Section 10 1100
Section 10 2113
Section 10 2226
Section 10 2800
Visual Display Surfaces
Toilet Compartments
Operable Partitions
Toilet, Bath and Laundry Accessories
DIVISION 11 – EQUIPMENT
Section 11 5213
Projection Screens
DIVISION 12 – FURNISHINGS
Section 12 2000
Section 12 4816
Window Treatments
Entrance Floor Grilles
DIVISION 14 – CONVEYING EQUIPMENT
Section 14 2100
Section 14 2400
Electric Traction Elevators
Hydraulic Elevators
Date of Issuance: January 1, 2014
TOC - 2
NORTHWESTERN UNIVERSITY
Design Guidelines and Technical Standards
DIVISION 21 – FIRE SUPPRESSION
Section 21 0000
Section 21 1314
Section 21 2400
Section 21 2500
General Fire Suppression Requirements
Automatic Sprinkler Systems
Chemical Suppression Systems
Smoke Control Systems
DIVISION 22 – PLUMBING
Section 22 1118
Section 22 2114
Section 22 2116
Section 22 4000
Section 22 4500
Domestic Water Distribution System
Plumbing Specialties
Pipe and Fittings
Plumbing Fixtures
Plumbing Equipment
DIVISION 23 – HVAC
Section 23 0000
Section 23 0513
Section 23 0514
Section 23 0529
Section 23 0550
Section 23 0553
Section 23 0594
Section 23 0700
Section 23 2113
Section 23 2116
Section 23 2123
Section 23 2213
Section 23 2216
Section 23 3114
Section 23 3314
Section 23 3400
Section 23 3600
Section 23 4114
Section 23 5214
Section 23 7313
Section 23 7323
Section 23 8216
Section 23 8413
General HVAC Design Criteria
Motors
Variable Frequency Drives (VFD)
Mechanical Supporting Devices
Vibration Isolation
Mechanical Systems Identification
Testing, Adjusting, and Balancing (TAB)
Mechanical System Insulation
Hydronic Piping
Hydronic Piping Specialties
Pumps
Steam Piping
Steam Piping Specialties
Ductwork
Ductwork Specialties
Fans
Air Terminal Devices
Filters
Primary Heating Equipment
Packaged Air Handling Units.
Factory Fabricated Custom Air Handling Units
Coils
Humidification Equipment
DIVISION 25 – INTERGRATED AUTOMATION
Section 25 0000
Integrated Automation Design Criteria
DIVISION 26 – ELECTRICAL
Section 26 0000
Section 26 0519
Section 26 0533
Section 26 0553
Electrical Design Criteria
Medium and Low Voltage Conductors
Raceway and Boxes
Identification for Electrical Systems
Date of Issuance: January 1, 2014
TOC - 3
NORTHWESTERN UNIVERSITY
Design Guidelines and Technical Standards
Section 26 2200
Section 26 2300
Section 26 2413
Section 26 2416
Section 26 2419
Section 26 2713
Section 26 2726
Section 26 2816
Section 26 3213
Section 26 3353
Section 26 5100
Low Voltage Transformers
Low Voltage Switchgear
Switchboards
Panelboards
Motor Control Centers
Electricity Metering
Wiring Devices
Switches and Disconnects
Engine Generators and Transfer Switches
Uninterruptible Power Supplies (UPS)
Lighting
DIVISION 27 – COMMUNICATIONS
Section 27 0000
Communications Design Criteria
DIVISION 28 – ELECTRONIC SAFETY AND SECURITY
Section 28 0000
Section 28 1000
Section 28 3113
Security Design Criteria
Access Control
Fire Detection and Alarm Systems
DIVISIONS 31 – EXTERIOR IMPROVEMENTS
Section 31 1000
Section 31 2000
Site Clearing
Earth Moving
DIVISIONS 32 – EXTERIOR IMPROVEMENTS
Section 32 1216
Section 32 1313
Section 32 1400
Section 32 8400
Section 32 9200
Section 32 9300
Asphalt Paving
Concrete Paving
Unit Paving
Planting Irrigation
Turf and Natives / Adaptive Plantings
Plants
DIVISIONS 33 – EXTERIOR IMPROVEMENTS
Section 33 1313
Section 33 4100
Facility Sanitary Sewers
Storm Utility Drainage Piping
APPENDIX
END OF TABLE OF CONTENTS
Date of Issuance: January 1, 2014
TOC - 4
NORTHWESTERN UNIVERSITY
Design Guidelines and Technical Standards
01.01.14
INTRODUCTION
General
The Design Guidelines and Technical Criteria included in this manual identify the standards and
preferences of Northwestern University (NU) Facilities Management Department. The Design
Guidelines are organized by subject matter while the Technical Criteria generally follow the
numbering system suggested by the Construction Specification Institute (CSI).
It is intended that these General Guidelines and Technical Criteria serve as a reference for
consultants providing architectural and engineering services for NU design and construction
projects. The Guidelines do not include “standard” or “master” specifications for any
construction material or system.
The translation of these General Guidelines and Technical Criteria into contract documents is
left to the individual consultant. In no instance shall a direct referral to these Design Guidelines
and Technical Criteria be included in contract documents prepared by design consultants, nor
shall any portion of the Technical Criteria be reproduced in project specifications without being
specifically tailored to the individual project.
Since requirements of applicable ordinances, codes, statutes, and regulations are subject to
change, it is the responsibility of the design professional to determine independently that the
project fully complies with all applicable ordinances, codes, statutes, and regulations at the time
of design. If, in the opinion of a design professional working on a specific matter, a requirement
of these guidelines is inconsistent with a requirement of an applicable ordinance, code, statute,
or regulation that compliance with this manual would violate the applicable provision, the design
professional should comply with the applicable ordinance, code, statute, or regulation and
should also advise the NU Project Representative in writing of the apparent inconsistency and
the reasons that the guideline may not be followed.
Modification and Waiver
Users of this guideline, including Facilities Management staff who have suggestions for
modifying or expanding the subject matter covered in these guidelines are encouraged to
submit their suggestions in writing to the Facilities Management representative coordinating
these standards. A form for providing such input is provided in the Appendix to the manual,
although any form of written communication or email is welcome.
Application for waivers to any section of these guidelines shall be made, in writing, by the
Architect/Engineer of Record to the Director of Design and Construction, copying the NU Project
Manager.
The origination date of these standards is January 1, 2014. This guideline is to be reviewed
annually for modification or expansion as determined during the course of the year by Facilities
Management. The period of review of this guideline will be the last quarter of the calendar year.
All modification requests received by October 1 will be reviewed by the Guidelines Review
Committee within 30 to 90 days, with recommendations to be incorporated into this guideline by
the annual date following the origination date.
INTRODUCTION
Page - 1
NORTHWESTERN UNIVERSITY
Design Guidelines and Technical Standards
01.01.14
Related Northwestern University Standards
The following University Standards are listed below by reference:
1. Building Infrastructure Requirements for Communications Facilities, January 2010.
2. Required Architect/Engineer Services and Deliverables.
3. Facilities Management – Planning – AutoCAD Standard Layers, 2006.
4. DDC Standards.
Single Source and Preferred Items
1. Products, materials, and equipment described herein establish a guideline for the
required function, dimension, appearance, and quality. When a single item or source is
described, the design professional shall specify only that item.
2. Substitutions are not permitted without written permission from the University.
3. When more than one item is specified or the item is described as “preferred,”
substitutions may be considered by the University, if equal to the specified standards.
4. The University may obtain a written agreement of “lowest commercial price” from single
source vendors, suppliers, or manufacturer’s named in these Design Guidelines and
Technical Standards.
INTRODUCTION
Page - 2
NORTHWESTERN UNIVERSITY
Design Guidelines
Issuance Date: 01.01.2014
PART 1 – DESIGN GUIDELINES
Site, Civil, and Grounds
1. Sites:
a. Buildings shall integrate with the existing campus, surrounding buildings, longterm stewardship goals, and the campus master plan.
b. Review historic districts and specific requirements with the NU Project Manager
at the beginning of the project.
2. Streets and Drives:
a. Review specific site parking requirements, exterior directories, and refuse
collection points if located outside of loading dock areas.
b. Study vehicular requirements for buildings affected by the work/project to
determine design requirements.
c. Provide truck turn studies are required for all uses.
d. Designers shall include design of temporary roads and walks necessary to
complete the work.
3. Sidewalks and Bike Paths:
a. Building entrances shall be strongly influence by Universal design, without steps
if possible. Ramps shall strive for 1:20 slopes as 1:12 slopes are very difficult for
most people with physical differences.
b. Design walks with landscape between curbs and walks such that wheel stops are
not required and to allow for favorable ADA access.
4. Site Lighting and Emergency Telephones:
a. Minimum Illumination: Provide light levels as recommended by code and
authorities having jurisdiction. Review specific requirements with NU Project
Manager during the design phase of the project.
b. NU Standard Light Fixture: Phillips Lumec. See Appendix for additional
information. Do not use bollards for site lighting without review with NU Project
Manager.
c. NU Standard Emergency Telephone: Provide products by Ramtel Corp. See
Appendix for additional information.
d. Design Review: NU Project Manager and NU Police Department to review
locations of exterior light fixtures and emergency telephones.
DESIGN GUIDELINES
Page - 1
NORTHWESTERN UNIVERSITY
Design Guidelines
Issuance Date: 01.01.2014
5. Building Exterior Lighting:
a. Generally do not illuminate the building with up lighting.
b. Review requirements for security lighting with NU Project Manager.
c. Comply with LEED requirements with respect to light pollution.
6. Site Accessories:
a. Bollards and Removable Bollards: Provide removable bollards as required to
maintain Fire Department access. Review types and locations with local Fire
Department.
b. Exterior Benches: NU Standard benches are described in Appendix. See
Appendix for additional information.
c. Exterior Garbage and Recycling Cans: NU Standard receptacles are described
in Appendix. See Appendix for additional information.
d. Bike Racks: NU Standard bike racks are described in Appendix. See Appendix
for additional information.
7. Storm Drainage:
a. The storm sewer system on the Evanston Campus is a combination of draining to
the City of Evanston’s combined sewer system (storm and sanitary), draining
directly to the soil, and to existing outfalls to Lake Michigan.
b. Each project should evaluate the existing systems in place and maximize site
retention back into the soil. Use of the existing City of Evanston system should
be minimized to the extent possible.
8. Site Clearing and Erosion Control:
a. Existing structures should not allow sedimentation from storm runoff to infiltrate
the campus storm system, sanitary system, or open waters.
9. Sanitary Sewers:
a. The Evanston Campus sanitary sewer system slopes from north campus and
south campus to central campus where it is pumped west via lift stations. The
existing system on the north and central campus is approaching the limits of
good design practice.
b. A new north campus sanitary sewer discharge to the west and associated lift
station should be considered when planning new buildings north of the
Technological Institute Building.
c. Properties adjacent to public ways typically have numerous connections directly
to the Evanston sewer system.
DESIGN GUIDELINES
Page - 2
NORTHWESTERN UNIVERSITY
Design Guidelines
Issuance Date: 01.01.2014
Utility Systems
1. Vaults:
a. General:
i. Vaults are to have stainless steel sump pumps that are alarmed back to
DDC.
ii. Discharge water to pumped to city drain or French drain below frost line.
Areas below lake level need to be pumped to a campus lift station.
iii. Weatherproof lighting to be installed in vaults and areas where applicable.
iv. Ladders are to be installed on the wall in vaults.
2. Steam:
a. General:
i. Requirements for stand-alone building heating plants, including boilers
and boiler accessories shall be reviewed with the NU Project Manager
prior to the start of the project.
b. Evanston Campus: A framework master plan has been developed for steam
utilities on campus and should be referenced with the NU Project Manager prior
to the start of the design phase of the project.
i. Steam produced in the Central Utility Plant (CUP) is available all year,
except for the scheduled annual maintenance shutdown, which typically
occurs over the Labor Day Holiday.
ii. For the Evanston campus central steam is distributed at 230 PSIG and a
second line distributed at 150 PSIG from the Central Utility Plant (CUP).
Steam shall be metered and reduced in pressure after entrance of each
building.
iii. Systems are to be designed for operation at 150 psi if NU chooses to
drop working pressure, but system has to be able to handle 250 psi
systems. Specific requirements should be confirmed with the NU Project
Manager prior to the start of the design phase of the project.
iv. Each building typically has a low pressure pumped condensate return.
Condensate is to be metered returned to the central plant 50 to 75 PSIG.
Condensate metering preferred to steam metering, refer to NU Metering
Standards.
v. Each building and sometimes each department is metered for billing and
management purposes. This should be confirmed prior to the start of the
design phase of the project. See NU Metering Standards for additional
information.
DESIGN GUIDELINES
Page - 3
NORTHWESTERN UNIVERSITY
Design Guidelines
Issuance Date: 01.01.2014
c. Chicago Campus:
i. Steam produced in the heating plant is available all year, except for the
scheduled annual maintenance shutdown, which typically occurs over the
Labor Day Holiday.
ii. For the Chicago campus central steam is distributed from the central
plant 150 to 175 PSIG. Steam shall be metered and reduced in pressure
after entrance of each building.
iii. Each building typically has a low pressure pumped condensate return.
Condensate is to be metered and returned to the central plant 50 to 75
PSIG. Condensate metering is preferred to steam metering, refer to NU
Metering Standards.
iv. Each building and sometimes each department is metered for billing and
management purposes. This should be confirmed prior to the start of the
design phase of the project. See NU Metering Standards for additional
information.
3. Chilled Water:
a. General:
i. Each campus has a campus framework plan which shall be referenced
for each project. Review specific requirements with the NU Project
Manager.
ii. Each of the buildings on both the Evanston and Chicago campuses are
that are connected to the Central Utility Plant (CUP) are to be metered.
iii. Chilled water and heating hot water piping is to have a side stream filter
and pot feeder. A chemical pot feeder shall be installed across the hot
water pump.
iv. Requirements for stand-alone building chiller plants, including cooling
towers and chillers shall be reviewed with the NU Project Manager prior
to the start of the project.
b. Evanston Campus: Chilled water is produced in the Central Utility Plant.
i. The piping should be designed for a working pressure of 150 psi.
ii. Chilled water is currently distributed at 80 psi to 100 psi leaving the
Central Utility Plant with a 6 to 8 psi differential pressure at the
extremities.
iii. The chilled water temperatures are as low as 42 degrees F on peak
cooling days and reset upwards to 50 degrees F under winter economizer
cooling operation. Cooling coils should be selected for a minimum 16
degrees F temperature differential.
DESIGN GUIDELINES
Page - 4
NORTHWESTERN UNIVERSITY
Design Guidelines
Issuance Date: 01.01.2014
iv. Return chilled water temperature needs to be designed for 54 degrees F.
v. Pumping on campus is typically accomplished through the Central Utility
Plant’s secondary distribution of pumps. The use of tertiary pumps shall
be reviewed with the NU Project Manager and the NU FM Operations
Staff Engineer.
c. Chicago Campus:
i. Chilled water is produced in a distributed satellite CHW plant
configuration.
ii. The chilled water temperatures are as low as 42 degrees F on peak
cooling days and reset upwards to 50 degrees F under winter economizer
cooling operation. Cooling coils should be selected for a minimum 16
degrees F temperature differential.
iii. Project integration into this system shall be reviewed at start of design
process with NU Project Manager and NU FMO Staff Engineer.
4. Geothermal:
a. The use of geothermal is to be reviewed with the NU Project Manager on a
project specific basis.
b. The costs associated with the installation and energy savings payback as well as
the ability to have steam and chilled water delivered to the site should be
reviewed.
5.
Domestic Water:
a. Evanston Campus:
i. Domestic water is metered at a few locations entering campus and is
mostly a private distribution system within campus.
ii. Domestic Water service to buildings must retain and/or create new water
loops to eliminate dead end runs.
iii. Each building and sometimes each department is metered for billing and
management purposes. This should be confirmed prior to the start of the
design phase of the project.
b. Chicago Campus: Review specific requirements with NU Project Manager.
DESIGN GUIDELINES
Page - 5
NORTHWESTERN UNIVERSITY
Design Guidelines
Issuance Date: 01.01.2014
6. Natural Gas:
a. Evanston Campus:
i. Natural gas is metered at a few locations entering campus and is mostly a
private, low pressure (5-inch), distribution system within campus. Some
limited high pressure (30-pound) natural gas lines are available.
ii. Each new load needs to study the existing systems and potentially plan
for extensions or new distribution and service as necessary.
b. Chicago Campus: Review specific requirements with NU Project Manager.
7. Laboratory Services:
a. Review requirements for specialty systems including the following:
i. Process Chilled Water:
1. Used for laboratory equipment that requires continuous cooling.
2. Labs are to use stainless steel braided hose when connected to
process chilled water rated for 175 psi. Connections are to be
threaded.
ii. Tempered Water.
1. Used for emergency showers and eyewash. Design to correct
temperature and flow rate per applicable codes.
iii. Compressed Air.
1. House systems to be filtered and oil free.
iv. Specialty Gases including nitrogen and helium capture.
1. House systems to be filtered and oil free.
8. Fire Protection:
a. Evanston Campus:
i. Several separate fire protection loops are distributed throughout campus
for service to many buildings and may be part of the solution for any new
building.
ii. Some existing buildings will require evaluation of existing systems and
requirements for extension and/or new fire pumps.
b. Chicago Campus: Review specific requirements with NU Project Manager.
DESIGN GUIDELINES
Page - 6
NORTHWESTERN UNIVERSITY
Design Guidelines
Issuance Date: 01.01.2014
9. Electrical Service:
a. ComEd: A/E shall work with NU and local utility providers to determine scope of
the project.
b. ComEd will typically provide and install primary wire and equipment and
contractor will typically provide secondary wire and equipment.
c. A/E shall provide bid documents for conduit ductbanks, manholes, and
transformer pads in locations that comply with ComEd design standards for
Contractor to install.
d. Include ample time for ComEd design, review, and approval.
10. Emergency Generators:
a. Each of the major buildings on campus utilizes an emergency generator.
b. For new buildings or replacements, diesel fueled emergency generators are
preferred. An alternate to use natural gas emergency generators should be
considered where diesel fueled emergency generators are less desirable.
c. Review existing generator loads and capacity for remodeling projects and/or
additions to existing buildings, including the following:
i. Life safety;
ii. Essential loads including pumps and exhaust fans; and
iii. Research loads.
Building – General
1. Exterior Campus Palette: Both the Chicago campus and Evanston campus share a
similar palette of exterior materials.
a. Indiana Limestone, standard buff color.
b. Lanon Stone, module and pattern to be reviewed.
2. Interior Finishes: Both the Chicago campus and Evanston campus share similar
expectations for interior materials and finishes.
a. Materials: Materials and products are selected based on durability; maintenance
requirements, and timeless qualities.
b. Polished Concrete: The use of polished concrete as a finish material shall be
reviewed with the NU Project Manager.
c. Matrix of Finishes: A matrix of proposed finishes is included for information and
reference. Materials and finishes shall be reviewed with the NU Project Manager
DESIGN GUIDELINES
Page - 7
NORTHWESTERN UNIVERSITY
Design Guidelines
Issuance Date: 01.01.2014
as part of the design phase of the project. Additional reviews with the user
group(s) should be anticipated. See the Appendix for additional information.
3. Room Planning Criteria: Both the Chicago campus and Evanston campus share similar
expectations for space planning.
a. General:
i. Exit corridors shall remain clear of any obstructions. Do not plan for items
such as microwave ovens, copiers, or other similar office equipment in
exit corridors.
ii. Rated walls shall extend to the underside of structure as required to
maintain fire ratings. Penetrations shall be sealed with appropriate
firestopping.
iii. Unrated walls shall typically extend to the underside of structure as
required to maintain acoustic performance. Penetrations shall be sealed
with appropriate sealant or acoustic sealant.
b. Office and Classroom Spaces:
i. Hinge side of doors to be placed a minimum of 12-inches from the wall to
allow for shelving behind the door.
ii. Structural columns should not be placed in the mid span of interior
demising walls. Maintain an uninterrupted rectangular room shape as
much as possible.
iii. The latch side of doors shall be the typical location for light switches,
occupancy sensors, fire alarm devices or strobes, and thermostats.
c. Restrooms:
i. Wall hung fixtures including water closets, urinals, and lavatories are
preferred.
ii. A shelf or counter shall be provided at each mirror for personal items.
iii. Coat hooks shall be provided on a wall near the door.
iv. Toilet partitions shall typically be floor to ceiling and hooks shall be
provided in the interior of each stall door.
v. Provide a required number of unisex and/or family assistance restrooms
in new construction. Consider including a required number of unisex
and/or family assistance restrooms in major renovations.
vi. Trash receptacles shall be free standing and typically provided by NU.
Design bathrooms such that free standing trash cans are located at the
back wall adjacent to the latch side of the door so that paper towels can
DESIGN GUIDELINES
Page - 8
NORTHWESTERN UNIVERSITY
Design Guidelines
Issuance Date: 01.01.2014
be used to open the door and dropped into the trash receptacle at the
door location without blocking the exit path.
vii. Tile walls shall typically be full height.
viii. Shower stalls shall be either full height tile or other durable materials.
d. Mechanical Rooms:
i. Mechanical rooms located above occupied floor levels shall be curbed,
room floors waterproof sealed, and all floor penetrations sleeved to 2"
above the floor to prevent liquid spills and leaks from traveling out of the
space.
ii. Mechanical Rooms shall be well lit, maintaining a minimum of 25 footcandles. Lighting shall be switched at each exit. Power at least 25% of
mechanical room lighting from standby generator power source where it
is available. Provide 120VAC convenience outlets in mechanical rooms to
provide for ready servicing of equipment.
iii. Provide adequate number of floor drains in mechanical rooms; drains are
to be connected to the sanitary sewer system, not to storm sewer. Locate
drains to avoid running of condensate drains and other similar equipment
across mechanical room floors. Provide trap primers as required per
Code.
iv. Locate all floor-mounted major mechanical equipment on concrete
housekeeping pads.
v. Mechanical rooms typically do not need to be painted. Review specific
requirements with the NU Project Manager.
vi. Where mechanical interstitial space is required, provide adequate head
room for maintenance staff to walk upright.
vii. Mechanical rooms shall have adequate heating, cooling to maintain
reasonable space temperatures.
viii. Consider insulation on walls and ceiling of mechanical rooms to minimize
heat transfer to adjoining spaces.
ix. Provide telephone in mechanical rooms.
x. Provide minimum of 3 spare data jacks per mechanical room.
xi. NU has a preference for mounting of air handler temperature control
valves and piping system isolation and control valves for serviceability
from the floor without the use of ladders; maximum height 6 feet above
finished floor. Where service valves are mounted 8 feet or higher above
the floor, provide service platform, catwalk, or valve chain wheels and
DESIGN GUIDELINES
Page - 9
NORTHWESTERN UNIVERSITY
Design Guidelines
Issuance Date: 01.01.2014
safety-trimmed chains. Do not block equipment access when locating
valves.
e. Data Network Centers:
i. All data center units are to have N + 1 redundancy for cooling. Units that
are critical need to have domestic water piped for emergency backup.
4. Signage: Signage is typically provided by NU. Review specific requirements with the
NU Project Manager prior to the start of the design phase of the project.
5. Vertical Transportation / Elevators:
a. NU typically hires a third party, independent elevator consultant for assistance
with the reviews related to elevators and conveying equipment.
b. Review the specific requirements for elevators and vertical transportation with the
NU Project Manager prior to the start of the design phase of the project.
c. Provide at least one C2 class elevator in each building. Consider tall doors for all
elevators.
d. Passenger elevator locations shall have more than one passenger elevator for
ADA redundancy while one car is out of service or being maintained.’
e. Consider energy capture technology.
6. Mechanical Systems:
a. The Architect/Engineer shall develop the Basis-of-Design (BOD) as part of the
Schematic Design submittal. The BOD shall be refined and further developed as
part of the Design Development and Construction Document submittals.
b. NU welcomes innovation in design. Systems or components not addressed in
these Design Guidelines and Technical Standards should be reviewed with the
NU Project Manager as early in the process as possible.
c. Systems shall be durable and low maintenance with particular focus to be placed
on the operability and maintainability of the installed systems.
d. A Life Cycle Cost Analysis is typically required for major mechanical systems.
Review specific requirements with the NU Project Manager prior to the start of
the design phase of the project.
7. Electrical Systems:
a. General:
i. Review minimum size requirements for electrical and telecommunication
rooms and closets with the NU Project Manager prior to the start of the
project.
DESIGN GUIDELINES
Page - 10
NORTHWESTERN UNIVERSITY
Design Guidelines
Issuance Date: 01.01.2014
ii. Electrical and telecommunication rooms and closets shall typically be
painted. Review requirements for plywood equipment panels with NU
Project Manager prior to the start of the project.
b. Coordinate with ComEd early in the design process for both temporary
construction service, conflict relocation, and new permanent service.
c. Renovation projects require a load study and arc flash study.
d. Review the following basic information with the NU Project Manager and Chief
Electrician prior to the start of the project:
i. General Requirements:
1. Codes Applied: NEC, NESC, ANSI C2, 70E, NU Standards.
2. System Voltages.
3. Variations in Supply Voltage.
4. System Power Factors.
5. Supply Capacity.
6. Short Circuit Ratings.
7. Electrical Protection and Control.
8. System Grounding.
9. Electrical Supply Facility for Safe Guards.
ii. Normal Equipment Requirements:
1. Switchgear.
2. Transformers.
3. Motor Control Center (MCC).
4. Electrical Motors.
iii. Cables and Wire Requirements:
1. Ampacity will be in accordance with NEC.
2. Special requirements such as voltage drop, fault current, and
environment shall be taken into consideration.
3. Flame retardant cables.
4. MV cables.
DESIGN GUIDELINES
Page - 11
NORTHWESTERN UNIVERSITY
Design Guidelines
Issuance Date: 01.01.2014
5. Grounding.
6. Raceways and Equipment.
7. Duct Banks, Man Holes, and Hand Holes.
iv. Lighting Requirements:
1. Classroom and Laboratory Lighting.
2. Office and Meeting Room Lighting.
3. Corridor Lighting.
4. Parking Lot Lighting.
5. Street Lighting.
6. Sidewalk Lighting.
7. Exterior Lighting at entrances, stairs, ramps, signage, and
landscaping areas.
8. Bicycle Rack Lighting.
9. Emergency Lighting.
a. Provide emergency lighting as required by the applicable
codes. In addition, provide a minimum of one emergency
light fixture in each public restroom.
10. Lighting Controls.
v. Power Requirements:
1. Convenience Outlets.
2. Metering Equipment.
3. Grounding.
4. Substations.
vi. Motor Requirements:
1. Review the following recommendations:
a. 1/3 HP to less than 1/2 HP = 120v
b. 1/2 HP to 249 HP = 480v
c. 250 HP and larger = 4160v
DESIGN GUIDELINES
Page - 12
NORTHWESTERN UNIVERSITY
Design Guidelines
Issuance Date: 01.01.2014
vii. Emergency Requirements:
1. Generators.
2. Battery Systems (invertors) / Battery Lighting.
3. Life Safety Emergency Systems.
4. Essential Systems.
5. Critical Operations Power (COP) Systems.
6. Uninterruptable Power Supplies (UPS) (Flywheel).
7. Fire Pumps.
8. Fire Alarms.
viii. Grounding and Lightning Protection System Requirements:
1. Testing Requirements.
2. Document and Drawing Requirements.
Sustainability
1. Introduction:
a. This portion of the Design Guidelines and Technical Standards includes the
sustainability guidelines to be followed by the Project Managers, Consultants,
Architects, and/or Engineers in the course of a project at Northwestern
University.
b. Northwestern University recognizes that the environmental impact of our facilities
and infrastructure is significant and that it has implications for the local
community and the world beyond our borders. We are committed to reducing
this impact by reducing materials and waste during construction, designing
buildings that conserve energy and water use, planning and designing
infrastructure that encourages walking and alternative forms of commuting like
cycling and public transit, and creating built environments that provide
opportunities to enhance the performance of the occupants.
c. These guidelines are designed to support Northwestern University’s commitment
to sustainability as stated in the Strategic Plan and to fulfill the President’s
commitment to position Northwestern University as a national leader in
sustainability. These guidelines will help Northwestern University to place clear
parameters and identify measureable results around what it means to be truly
sustainable. The goal is to incorporate sustainable principles, materials, and
actions into building design, construction, and maintenance.
DESIGN GUIDELINES
Page - 13
NORTHWESTERN UNIVERSITY
Design Guidelines
Issuance Date: 01.01.2014
d. These guidelines should be considered at every decision point and economic
and environmental assessments done when necessary to make the right
decisions for the stewardship of Northwestern University campuses.
e. For questions, please contact the Office of Sustainability at
sustainability@northwestern.edu.
2. Sustainability and Integrated Design:
a. The optimal way to ensure that sustainability occurs is by focusing on the
environmental, economic, and social impacts of planning, design, construction,
operations and maintenance to improve resource conservation and create
healthy work and living spaces in a way that is meaningful for the people who
study, teach, work, or live in our buildings.
b. Application of whole-systems design approach is crucial for sustainability. The
sustainability categories and strategies are interdependent; none stand in
isolation. Decisions made in one area may affect the performance in another. A
single design improvement might simultaneously improve several building
systems’ performance.
c. It is essential that all members of the project team work together and consider all
sustainability categories in order to be aware of the influence of their decisions
on the overall sustainability performance of the building in each category. In
addition, not all strategies suggested here are relevant for every project and
certainly not all strategies will be implemented in every project.
d. These decisions are not made in isolation but rather they should recognize the
interactions and tradeoffs of a particular project. Northwestern University’s
sustainability guidelines outline an integrated design approach. The process
steps are identified to establish performance goals and to ensure that decisions
are made in a collaborative and informed manner. The maximum benefits to the
programmatic mission can be achieved when sustainability is incorporated at
every point along the project delivery process.
3. Planning and Project Initiation:
a. Translate academic or departmental initiatives into potential facility needs to
determine if a capital construction project is necessary. As part of that effort,
sustainable features should be discussed in a preliminary sustainability working
session and document by the Northwestern University Project Manager and
stakeholders so that they can be incorporated as the project is developed.
b. Incorporate the sustainability initiatives discussed into the Request for Proposal
(RFP) and Owner’s Project Requirements (OPR) outlined in the Design
Guidelines and Technical Standards. Understand any costs or savings that may
be incurred in order to create an more sustainable building.
4. Programming:
DESIGN GUIDELINES
Page - 14
NORTHWESTERN UNIVERSITY
Design Guidelines
Issuance Date: 01.01.2014
a. During the programming phase, the programming requirements should be further
developed to incorporate sustainability goals as they pertain to the user needs
and design parameters.
b. As the project team develops or verifies the project program, summary schedule,
and preliminary budget, the FM Project Manager should arrange a Sustainability
Working Session (SWS) to review the options and the underlying principles of
sustainability as they relate to the building design, construction, and operation.
c. Programming Consultant is to begin development of the Basis of Design (BOD)
and LEED Checklist in response to the Owner’s Project Requirements (OPR)
and results of the sustainability working session.
5. Schematic Design:
a. The largest resources impacts of the project should be identified, prioritized, and
discussed at design meetings and should include energy, water, materials, and
people. The consultant should be prepared to discuss major mechanical
systems and alternatives like geothermal.
b. Modeling tools such as DOE-2, eQUEST, or ENERGY-10 should be used to
evaluate energy efficient design alternatives and refine the project’s sustainability
goals for energy usage. The results are to be incorporated into the BOD
document and LEED Checklist.
6. Design Development:
a. During the Design Development (DD) phase, the approved schematic design
begins to include a level of detail necessary to work out a clear, coordinated
description of all aspects of the project. Because the DD Phase is one of the last
opportunities for the User Group to become fully involved in the design, it is
crucial that sustainability principles from each of the LEED categories be fully
discussed and implications be understood and integrated as appropriate.
b. Design and construction costs associated with the sustainable attributes of the
project should be clarified. Sustainable component cost metrics (capital and life
cycle) should be developed and cost and/or savings decisions evaluated against
performance and life cycle cost considerations. The results are to be refined
within the BOD document and LEED Checklist.
c. The project team should ensure that the project schedule allows adequate time
for implementing the activities that may lead to a more sustainable project, such
as commissioning, demolition waste diversion, and training.
7. Construction Documents:
a. During the Construction Documents (CD) phase, a comprehensive, fully
coordinated set of construction documents and technical specifications are
issued to obtain the necessary permits and construct the project. A review of
sustainability elements should be included in the preliminary CD review (such as
DESIGN GUIDELINES
Page - 15
NORTHWESTERN UNIVERSITY
Design Guidelines
Issuance Date: 01.01.2014
50% CD review) along with any update of the BOD document and LEED
Checklist. This review should specifically address materials selection.
8. Construction:
a. At the start of the construction phase, a representative from the Construction
Manager (CM) and/or General Contractor (GC), each subcontractor, and
Sustainability Team (FM, FMO, FM OoS), and the Architect/Engineer should
attend the pre-construction meeting. The sustainability goals and design
features of the project should be discussed at this meeting and a review of the
project LEED requirements should occur if applicable.
b. Contractor ideas and opinions should be encouraged during these discussions to
allow for innovations and efficiencies during construction.
Sustainability Guidelines
1. These guidelines are for use by NU Project Managers and consultants on projects of all
scales. Although Northwestern sets LEED Gold as a target for larger projects, each
project should follow these guidelines when applicable.
2. These guidelines are organized into the following categories:
a. Sustainable Sites.
b. Energy.
c. Water.
d. Materials and Resources.
e. Indoor Environmental Quality.
f.
Human Centric.
3. In view of the environmental concerns associated with buildings, sustainable design
embodies certain goals within each category. The discussion of each sustainable
category begins with a set of goals, followed by a list of suggested strategies to be used
in achieving those goals.
4. The sustainability strategies included here are not comprehensive; these guidelines are
intended to provide ideas and not exclude any from consideration. The project team is
encouraged to develop additional strategies and refer to current documents published by
the United States Green Building Council (USGBC) at www.usgbc.org.
DESIGN GUIDELINES
Page - 16
NORTHWESTERN UNIVERSITY
Design Guidelines
Issuance Date: 01.01.2014
Key Sustainable Guidelines for all Projects
1. Sustainable Sites:
a. Promote development that relates well to both natural systems and existing
infrastructure.
b. Promote walking, cycling, and the use of alternative transportation.
c. Maintain and enhance the biodiversity of natural systems and/or the existing
character of the site.
2. Energy:
a. Maximize energy performance of building systems to reduce total building energy
consumption and peak electrical demand.
i. Design Team to propose Energy Usage Intensity (EUI) in Kbtu/SF/year
for each type of building. Design Team shall provide code compliant
baseline EUI and subsequent proposed building EUI’s for evaluation
during the design phases of the project.
ii. Review project specific goals with the NU Project Manager prior to the
start of the project.
b. Reduce greenhouse gas emissions and contributions to climate change.
c. Achieve energy cost and related savings through infrastructure upgrades and
system design and operation (e.g. labs).
d. Calculate life cycle costs of alternative systems for payback of investment.
3. Water:
a. Increase the harvesting and recycling of all available water resources in both
buildings and landscape projects.
b. Reduce the consumption of potable water.
c. Maintain the aesthetics of the campus landscape and botanic garden.
d. Minimize impacts to natural resources from the discharge of storm water.
4. Materials and Resources:
a. Reduce consumption and depletion of material resources, especially
nonrenewable resources.
b. Minimize waste generated from construction, renovation, and demolition of
buildings.
c. Minimize waste generated during building occupancy.
DESIGN GUIDELINES
Page - 17
NORTHWESTERN UNIVERSITY
Design Guidelines
Issuance Date: 01.01.2014
d. Encourage better management of waste (e.g. strategic planning of recycling
containers).
5. Indoor Air Quality:
a. Provide and maintain acceptable indoor air quality.
b. Monitor and avoid indoor air quality problems during renovation, demolition, and
construction activities.
c. Provide occupants with operational control of lighting and HVAC systems where
practical.
6. Human Centric:
a. Incorporate attributes of ergonomic, human factors, biophilia.
b. Incorporate attributes of universal design.
c. Incorporate attributes that support and enhance learning and creativity.
d. Incorporate attributes to enhance security and crime prevention through
environmental design (CPTED).
END OF SECTION
DESIGN GUIDELINES
Page - 18
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
DIVISION 1 – GENERAL REQUIREMENTS
SECTION 01 1000 – GENERAL REQUIREMENTS
1. General: This section outlines the general requirements and coordination required by
the Architect / Engineer and the NU Project Manager during the design and construction
phases of the project.
2. Front End Documents: Northwestern University Facilities Management – Design and
Construction (FMDC) has standard front end documents to be used by the Architect /
Engineer including the following:
a. Bid Form: This form should be reviewed the NU Project Manager and modified
by the Architect / Engineer for the specific project.
3. Standard Warranties: The minimum allowable warranty for materials and equipment
shall be one year from the Date of Substantial Completion. The warranty period shall
not begin prior to the Date of Substantial Completion, regardless of the date of
installation.
4. Special Warranties: Certain systems and/or components may require additional special
warranties. These systems and components shall be reviewed with the NU Project
Manager and modified by the Architect / Engineer for the specific project. Refer to
specific sections for additional information.
5. Close-Out Documents / Training:
a. The receipt of close-out documents, including, but not limited to, as-built
drawings and specifications, O&M manuals, and warranty letters and the
completion of required training for Owner personnel, shall be a condition of the
release of retainage.
b. Close out documents shall include a list of finishes for all building elements with a
finish.
c. Closeout documents shall include copies of all reviewed submittals in pdf format.
6. Special Inspections: Independent Special Inspections, contracted directly with the
Owner, shall typically be required for the following work:
a. Geotechnical / Environmental: Include soil characterization study for
contaminants during design phase.
b. Earthwork: Include soils compaction testing.
c. Concrete: Include slump tests and test cylinders.
d. Steel Erection: Include review of bolted and/or welded connections. When
required, provide for full-time inspection of full-penetration welds.
GENERAL REQUIREMENTS
01 1000 - 1
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
7. Temporary Utilities:
a. Review specific requirements with NU Project Manager during design phases.
b. Contractor shall not utilize temporary power, especially science buildings, for
construction welding. General Contractor to provide separate power for welder
generator remote from any fresh air intake.
END OF SECTION
GENERAL REQUIREMENTS
01 1000 - 2
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
DIVISION 2 – EXISTING CONDITIONS
SECTION 02 4119 – SELECTIVE DEMOLITION
1. General:
a. This section outlines requirements for selective demolition. Architect/Engineer
shall indicate requirements in the technical specifications.
b. Project specific requirements shall be coordinated by the Architect / Engineer
with the NU Project Manager.
c. See Division 33 for Site Requirements previously included as part of Division 2.
2. Submittals – Photographs:
a. Review requirements for Photographic Documentation with NU Project Manager.
Typically Include requirements that Contractor shall, before starting work, file with
the University, photographs or video documenting existing conditions that later
could be mistaken for damage caused by demolition operations.
b. Record with photographs or videotape unusual structural, electrical, or
mechanical conditions.
3. Protection of Existing Conditions: When existing buildings are directly adjacent, provide
survey and monitoring as needed to document movement during construction.
4. Hazardous Materials:
a. Typically, asbestos containing materials (ACMs), polychlorinated biphenyls
(PCBs), and/or other hazardous materials will be removed by Northwestern prior
to demolition or renovation operations.
b. If hazardous materials are encountered during construction, the Contractor shall
immediately notify the NU Project Manager.
5. Existing Utilities:
a. During construction, Contractor shall verify with Northwestern that existing
utilities have been disconnected and capped.
b. Insofar as is practical, Contractor shall arrange operations to reveal unknown or
concealed structural conditions for examination and verification before removal or
demolition.
6. Salvaged Materials: Architect/Engineer shall identify items to be salvaged with the NU
Project Manager and communicate these to the Contractor in the Construction
Documents.
SELECTIVE DEMOLITION
02 4119 - 1
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
7. Walks and Public Ways:
a. Contractor shall not obstruct walks or public ways without the written permission
of Northwestern and/or authorities having jurisdiction.
b. Where routes are permitted to be closed, Contractor shall provide alternate
routes if required.
c. Provide adequate signage for new routes to avoid confusion for pedestrians,
bikes, vehicles, and emergency vehicles.
8. Tree Protection:
a. Architect/Engineer shall indicate existing trees to remain and be protected or
trees to be removed as part of the project.
b. Trees should be protected at drip-line. When this is not possible, Contractor shall
provide a plainly visible fence at least 5 feet from trunks of individual trees or
around outer perimeter of clumps of trees that are to be protected.
c. Protect drip-line tree roots from excessive compaction, leave free from materials
to allow for air circulation and give the tree ability to benefit from natural rainfall.
d. For long term construction projects where existing plant material is under
extreme duress, auxiliary watering may be necessary during drought/extreme
conditions.
e. Tree surfaces should be periodically cleared of dust and debris and mulched to
help protect roots and maintain available water for the plant.
9. Maintaining Utility Services:
a. Contractor shall provide bypass connections as necessary to maintain service to
occupied areas during construction.
b. Contractor shall notify Northwestern at least 2 weeks in advance of changeover.
10. Underground Work: Contractor shall contact utility locating service prior to proceeding
with underground work.
11. Explosives: Contractor shall not use explosives.
12. Disposal of Demolished Materials:
a. Contractor shall promptly dispose of materials resulting from demolition
operations to a legal, offsite location.
b. Contractor shall not allow materials to accumulate on site. Use of Universityowned containers or equipment is not permitted.
END OF SECTION
SELECTIVE DEMOLITION
02 4119 - 2
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
DIVISION 3 – CONCRETE
SECTION 03 3000 – CAST-IN-PLACE CONCRETE
1. General: This section outlines requirements for cast-in-place concrete construction.
2. Concrete Design Criteria:
a. Except for lean concrete, which is typically used for backfill, minimum 28-day
concrete strength shall be 3,000 psi, for below grade construction, and 3,500 psi
for slabs-on-grade and above-grade construction.
b. Concrete exposed to freeze / thaw shall have a minimum air content of 4.5%.
3. Design Considerations:
a. No conduit shall be placed in concrete slabs without approval by the University.
b. Consideration must be given to the precast connection to the superstructure,
prior to commencement of construction.
c. Precast camber – minimum thickness of topping shall be measured at the high
point of camber.
d. Do not use gypsum-based products for anchorage into exterior exposed
concrete.
e. Epoxy coat all reinforcing in exterior permanently-exposed face of concrete.
f.
Coordinate brick ledges and exterior grades so that soils are not placed against
exterior façade materials (e.g. stone, precast concrete, or masonry).
g. Form tie depressions shall be patched on all vertically formed concrete surfaces
that are either exposed to view or are to receive damp-proofing or waterproofing.
h. Perimeter foundation walls shall receive, at minimum, fluid-applied dampproofing. Foundation walls that form the perimeter of a basement or crawl space,
and elevator pit walls, shall be waterproofed. Provide a footing / wall water stop
at waterproofed locations.
i.
Pipe, conduit, and other penetrations through perimeter basement walls shall be
provided with an appropriate seal as manufactured by Link-Seal or approved
equal.
j.
The minimum reinforcing for slab-on-grade and slab-on-deck concrete shall be
WWF 6x6 – W1.4 x W1.4, with the WWF supplied in sheets, not rolls.
k. The minimum allowable vapor barrier under interior slabs-on-grade shall be a 12
mil reinforced polyethylene product (“Moistop” or approved equal.) The joints in
the vapor barrier shall be sealed with the manufacturer’s recommended tape.
CAST-IN-PLACE CONCRETE
03 3000 - 1
NORTHWESTERN UNIVERSITY
Technical Standards
l.
Issuance Date: 01.01.2014
Concrete placement during cold weather conditions shall be performed in strict
accordance with the ACI Standard Specification for Cold Weather Concreting.
m. Concrete slabs (exclusive of mud slabs) shall receive a minimum of a float finish;
if indicated to be broomed, the slab shall be floated and then broomed.
n. Apply an acrylic curing compound similar to Sonneborn “Kure-N-Seal” to cast-inplace slab concrete. If there is a specified surface finish product or adhesive that
is not compatible with the curing compound, it shall be the finish installer’s
responsibility to remove the compound (sand, etch, bead blast, etc. as needed)
prior to their installation.
4. Tolerances: The University requires proper forming, placement and finishing to meet the
following:
a. Sizes of sleeves, floor openings, and wall openings: Center line of sleeves, floor
and wall openings, +/-1/2”.
b. The following are recommended tolerances for finished slab surfaces:
i. Scratch Finish: For surfaces to receive concrete floor topping or mortar
setting beds for tile and other bonded applied cementitious finish flooring
material: Depressions between high spots shall not exceed 1/4” under a
10-foot straightedge.
ii. Float Finish: For surfaces to be covered with membrane or elastic
waterproofing, membrane or elastic roofing: Depressions between high
spots shall not exceed 5/16” under a 10-foot straightedge.
iii. Trowel Finish: For surfaces to be exposed to view and slab surfaces to
be covered with resilient flooring, carpet, ceramic or quarry tile, paint, or
other thin film finish coating system: Achieve level surface plane so that
depressions between high spots do not exceed 1/8” under a 10-foot
straightedge.
c. Floor Leveling: Contractor, at his own expense, shall provide floor leveling, to
the satisfaction of the University, in areas where the above tolerances are not
achieved.
5. Quality Assurance:
a. Installer Qualifications: An experienced installer who has completed Concrete
Work similar in material, design, and extent to that indicated for the intended
Project and whose work has resulted in construction with a record of successful
in-service performance.
b. Professional Engineer Qualifications: An Illinois licensed structural engineer who
is experienced in providing engineering services of the kind indicated. Delete
this requirement if Contractor is not required to engage the services of a
professional engineer.
CAST-IN-PLACE CONCRETE
03 3000 - 2
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
c. Manufacturer Qualifications: A firm experienced in manufacturing ready-mixed
concrete products complying with ASTM C 94 requirements for production
facilities and equipment.
i. Manufacturer must be certified according to the National Ready Mixed
Concrete Association's Certification of Ready Mixed Concrete Production
Facilities.
d. Source Limitations: Obtain each type or class of cementitious material of the
same brand from the same manufacturer's plant, each aggregate from one
source, and each admixture from the same manufacturer.
e. Welding: Qualify procedures and personnel according to AWS D1.4, "Structural
Welding Code--Reinforcing Steel."
6. Pre-Installation Conference: Architect/Engineer shall review requirements for preinstallation conference with NU Project Manager.
7. Mockups: Architect/Engineer shall review requirements for mock-ups with NU Project
Manager.
a. Cast concrete slabs-on-grade mockup to demonstrate typical joints, surface
finish, texture, tolerances, and standard of workmanship.
b. Obtain Architect/Engineer's approval of mockups before starting construction.
c. If Architect/Engineer determines that mockups do not meet requirements,
demolish and remove them from the site and cast another until the mockup is
approved.
d. Maintain mockups during construction in an undisturbed condition as a standard
for judging the completed Work.
e. Demolish and remove mockups when directed.
f.
Approved mockups may become part of the completed Work if undisturbed at
time of Substantial Completion.
8. Delivery, Storage, and Handling:
a. Deliver, store, and handle steel reinforcement to prevent bending and damage.
b. Avoid damaging coatings on steel reinforcement. Repair damaged epoxy
coatings on steel reinforcement.
9. Accessories:
a. Vapor Retarder: not less than 15 mils thick.
b. Fine-Graded Granular Material: Clean mixture of crushed stone, crushed gravel,
and manufactured or natural sand.
CAST-IN-PLACE CONCRETE
03 3000 - 3
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
c. Granular Fill: Clean mixture of crushed stone or crushed or uncrushed gravel.
10. Concrete Mixes:
a. Prepare design mixes for each type and strength of concrete determined by
either laboratory trial mix or field test data bases.
b. Use a qualified independent testing agency for preparing and reporting proposed
mix designs for the laboratory trial mix basis.
11. Concrete Mixing:
a. Ready-Mixed Concrete: Measure, batch, mix, and deliver concrete according to
ASTM C 94, and furnish batch ticket information.
12. Embedded Items: Place and secure anchorage devices and other embedded items
required for adjoining work that is attached to or supported by cast-in-place concrete.
13. Vapor Retarders:
a. Vapor Retarder: Place, protect, and repair vapor-retarder sheets.
b. Fine-Graded Granular Material: Cover vapor retarder with fine-graded granular
material, moisten, and compact with mechanical equipment to elevation
tolerances of plus 0 inch (0 mm) or minus 3/4 inch (19 mm).
c. Granular Fill: Cover vapor retarder with granular fill, moisten, and compact with
mechanical equipment to elevation tolerances of plus 0 inch (0 mm) or minus 3/4
inch (19 mm).
14. Steel Reinforcement:
a. General: Comply with CRSI's "Manual of Standard Practice" for placing
reinforcement.
i. Do not cut or puncture vapor retarder. Repair damage and reseal vapor
retarder before placing concrete.
b. Clean reinforcement of loose rust and mill scale, earth, ice, and other foreign
materials.
c. Accurately position, support, and secure reinforcement against displacement.
Locate and support reinforcement with bar supports to maintain minimum
concrete cover. Do not tack weld crossing reinforcing bars.
d. Set wire ties with ends directed into concrete, not toward exposed concrete
surfaces.
e. Install welded wire fabric in longest practicable lengths on bar supports spaced to
minimize sagging. Lap edges and ends of adjoining sheets at least one mesh
CAST-IN-PLACE CONCRETE
03 3000 - 4
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
spacing. Offset laps of adjoining sheet widths to prevent continuous laps in
either direction. Lace overlaps with wire.
f.
Epoxy-Coated Reinforcement: Use epoxy-coated steel wire ties to fasten epoxycoated reinforcement. Repair cut and damaged epoxy coatings with epoxy repair
coating.
15. Joints: Typically joints are to constructed true to line with faces perpendicular to surface
plane of concrete. Special requirements shall be indicated on the drawings.
16. Concrete Placement: Before placing concrete, contractor shall be required to verify that
installation of formwork, reinforcement, and embedded items is complete and that
required inspections have been performed.
17. Concrete Surface Repairs:
a. Filling In: Contractor shall be required to fill in holes and openings left in
concrete structures, unless otherwise indicated, after work of other trades is in
place.
b. Defective Concrete: Contractor shall be required to repair and patch defective
areas when approved by Architect/Engineer. Remove and replace concrete that
cannot be repaired and patched to Architect/Engineer's approval.
c. Patching Mortar: It is recommended to mix dry-pack patching mortar, consisting
of one part portland cement to two and one-half parts fine aggregate passing a
No. 16 (1.2-mm) sieve, using only enough water for handling and placing.
d. Repairing Formed Surfaces: Surface defects include color and texture
irregularities, cracks, spalls, air bubbles, honeycombs, rock pockets, fins and
other projections on the surface, and stains and other discolorations that cannot
be removed by cleaning.
i. Immediately after form removal, Contractor shall be required to cut out
honeycombs, rock pockets, and voids more than 1/2 inch (13 mm) in any
dimension in solid concrete but not less than 1 inch (25 mm) in depth.
Make edges of cuts perpendicular to concrete surface. Clean, dampen
with water, and brush-coat holes and voids with bonding agent. Fill and
compact with patching mortar before bonding agent has dried. Fill formtie voids with patching mortar or cone plugs secured in place with bonding
agent.
ii. Contractor shall be required to repair defects on surfaces exposed to view
by blending white portland cement and standard portland cement so that,
when dry, patching mortar will match surrounding color. Patch a test area
at inconspicuous locations to verify mixture and color match before
proceeding with patching. Compact mortar in place and strike off slightly
higher than surrounding surface.
CAST-IN-PLACE CONCRETE
03 3000 - 5
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
iii. Contractor shall be required to repair defects on concealed formed
surfaces that affect concrete's durability and structural performance as
determined by Architect/Engineer.
e. Repairing Unformed Surfaces: Contractor shall be required to test unformed
surfaces, such as floors and slabs, for finish and verify surface tolerances
specified for each surface. Correct low and high areas. Test surfaces sloped to
drain for trueness of slope and smoothness; use a sloped template.
i. Repair finished surfaces containing defects. Surface defects include
spalls, popouts, honeycombs, rock pockets, crazing and cracks in excess
of 0.01 inch (0.25 mm) wide or that penetrate to reinforcement or
completely through unreinforced sections regardless of width, and other
objectionable conditions.
ii. After concrete has cured at least 14 days, correct high areas by grinding.
iii. Correct localized low areas during or immediately after completing
surface finishing operations by cutting out low areas and replacing with
patching mortar. Finish repaired areas to blend into adjacent concrete.
iv. Correct other low areas scheduled to receive floor coverings with a repair
underlayment.
v. Correct other low areas scheduled to remain exposed with a repair
topping.
vi. Repair defective areas, except random cracks and single holes 1 inch (25
mm) or less in diameter, by cutting out and replacing with fresh concrete.
vii. Repair random cracks and single holes 1 inch (25 mm) or less in diameter
with patching mortar.
18. Polished Concrete Floor Finishing:
a. The desired results of a ground, polished floor should be specified in three
categories:
i. Flatness and levelness of the concrete: Manufacturers typically
recommend F(f)40 and F(l)25.
ii. Aggregate Exposure: Please note that each finish below will have some
percentage of all four finishes. The finish choices are described as:
1. Cream: No exposed aggregates.
2. Salt and Pepper: Exposed sand and small aggregate.
3. Medium: 1/8-inch to 1/4-inch exposed aggregate.
4. Heavy: 1/4-inch to 1/2-inch exposed aggregate.
CAST-IN-PLACE CONCRETE
03 3000 - 6
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
iii. Sheen:
1. Level A: Hard-shell, satin finish (400 grit).
2. Level B: Hard-shell, medium sheen finish (800 grit).
3. Level C: Light reflective, mirror finish (1800 grit).
b. The depth of the grind to achieve the desired results is dependent on the
techniques used for finishing, the concrete mix, and the amount of time between
concrete pouring and grinding. To avoid disputes later, however, it is necessary
to specify a minimum required depth of the grind of at least 1/4-inch. That gives
the contractor a starting point to achieve the desired finish results.
c. Utilize a mock-up to determine the final technique.
d. Do not grind and polish lightweight concrete. Shale aggregates will be pulled
from the surface resulting in pits.
19. Field Quality Control – Testing Agency: Typically, Northwestern will engage a qualified
independent testing and inspecting agency to sample materials, perform tests, and
submit test reports during concrete placement. Architect/Engineer shall review project
specific requirements with the NU Project Manager during the Design Phase of the
project.
a. Testing Agency Qualifications: Personnel conducting field tests shall be qualified
as ACI Concrete Field Testing Technician, Grade 1, according to ACI CP-1 or an
equivalent certification program.
b. Testing Services: The following are recommended minimums for field quality
control and testing. Testing of composite samples of fresh concrete obtained
according to ASTM C 172 shall be performed according to the following
requirements:
i. Testing Frequency:
1. Obtain one composite sample for each day's pour of each
concrete mix exceeding 5 cu. yd. (4 cu. m), but less than 25 cu.
yd. (19 cu. m), plus one set for each additional 50 cu. yd. (38 cu.
m) or fraction thereof.
2. Obtain at least one composite sample for each 100 cu. yd. (76 cu.
m) or fraction thereof of each concrete mix placed each day.
3. When frequency of testing will provide fewer than five
compressive-strength tests for each concrete mix, testing shall be
conducted from at least five randomly selected batches or from
each batch if fewer than five are used.
ii. Slump: ASTM C 143; one test at point of placement for each composite
sample, but not less than one test for each day's pour of each concrete
CAST-IN-PLACE CONCRETE
03 3000 - 7
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
mix. Perform additional tests when concrete consistency appears to
change.
iii. Air Content: ASTM C 231, pressure method, for normal-weight concrete;
ASTM C 173, volumetric method, for structural lightweight concrete; one
test for each composite sample, but not less than one test for each day's
pour of each concrete mix.
iv. Concrete Temperature: ASTM C 1064; one test hourly when air
temperature is 40 deg F (4.4 deg C) and below and when 80 deg F (27
deg C) and above, and one test for each composite sample.
v. Unit Weight: ASTM C 567, fresh unit weight of structural lightweight
concrete; one test for each composite sample, but not less than one test
for each day's pour of each concrete mix.
vi. Compression Test Specimens: ASTM C 31/C 31M; cast and laboratory
cure one set of four standard cylinder specimens for each composite
sample.
1. Cast and field cure one set of four standard cylinder specimens for
each composite sample.
vii. Compressive-Strength Tests: ASTM C 39; test two laboratory-cured
specimens at 7 days and two at 28 days.
1. Test two field-cured specimens at 7 days and two at 28 days.
2. A compressive-strength test shall be the average compressive
strength from two specimens obtained from same composite
sample and tested at age indicated.
3. When strength of field-cured cylinders is less than 85 percent of
companion laboratory-cured cylinders, Contractor shall evaluate
operations and provide corrective procedures for protecting and
curing in-place concrete.
4. Strength of each concrete mix will be satisfactory if every average
of any three consecutive compressive-strength tests equals or
exceeds specified compressive strength and no compressivestrength test value falls below specified compressive strength by
more than 500 psi (3.4 MPa).
viii. Test results shall be reported in writing to Architect, concrete
manufacturer, and Contractor within 48 hours of testing. Reports of
compressive-strength tests shall contain Project identification name and
number, date of concrete placement, name of concrete testing and
inspecting agency, location of concrete batch in Work, design
compressive strength at 28 days, concrete mix proportions and materials,
compressive breaking strength, and type of break for both 7-and 28-day
tests.
CAST-IN-PLACE CONCRETE
03 3000 - 8
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
c. Nondestructive Testing: Impact hammer, sonoscope, or other nondestructive
device may be permitted by Architect/Engineer but will not be used as sole basis
for approval or rejection of concrete.
d. Additional Tests: Testing and inspecting agency shall make additional tests of
concrete when test results indicate that slump, air entrainment, compressive
strengths, or other requirements have not been met, as directed by
Architect/Engineer. Testing and inspecting agency may conduct tests to
determine adequacy of concrete by cored cylinders complying with ASTM C 42
or by other methods as directed by Architect/Engineer.
END OF SECTION
CAST-IN-PLACE CONCRETE
03 3000 - 9
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
This page intentionally left blank
CAST-IN-PLACE CONCRETE
03 3000 - 10
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
DIVISION 3 – CONCRETE
SECTION 03 400 – PRECAST CONCRETE
1. General: This section outlines the requirements for precast concrete. Specific
requirements shall be reviewed with the NU Project Manager during the design phases
of the project
2. Submittal Requirements:
a. Submittal requirements shall include fully-engineered shop drawings and design
calculations stamped by an engineer registered in the State of Illinois.
b. Fully-dimensioned shop drawings shall be required that include “closing”
dimensions to the Architect/Engineer’s dimensional reference (grid lines, face of
foundation, etc.) and that dimension rough opening sizes for windows, etc.
bounded by precast components.
c. Shop drawings shall specifically identify the locations and magnitudes of loads
that will be imposed on the structure by precast connections.
3. Quality Assurance:
a. Precast pieces that are damaged during shipping, handling, etc. shall be
reviewed by the Architect/Engineer and Owner prior to installation.
b. The Architect/Engineer and Owner shall have the discretion to require that
damaged pieces be repaired to their satisfaction prior to installation.
END OF SECTION
PRECAST CONCRETE
03 4000 - 1
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
This page intentionally left blank
PRECAST CONCRETE
03 4000 - 2
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
DIVISION 4 – MASONRY
SECTION 04 2000 – UNIT MASONRY
1. General: This section outlines the general requirements for unit masonry.
2. Masonry Design Criteria:
a. Deflection shall be limited to the lesser of l/600 or 0.3-inches for structures or
components thereof, which support masonry.
3. Quality Assurance:
a. Cold Weather Guidelines: Architect/Engineer shall require Contractor to submit
cold-weather procedures before starting work and to keep a copy of guidelines
on site.
4. Face Brick:
a. Exterior face brick shall be Grade SW, Type FBX.
b. Wherever brick is shown to "match existing," provide facing brick of color,
texture, and size which duplicate the corresponding properties of existing
masonry at the site. Samples shall be reviewed for approval by the Architect and
NU Project Manager at the project site.
5. Ground Face Concrete Masonry Units: Provide in public areas. Ground surfaces filled
with cementitious grout. Apply heat treated acrylic finish in compliance with ASTM C744
after polishing.
a. Acceptable Manufacturers:
i. Trendstone by Trenwyth Industries
ii. Jandis & Sons, Inc.
iii. Anchor Concrete Products, Inc.
iv. RichStone by United Glazed Products
v. Premier Line by Dillon & Co.
6. Mortar and Grout Materials: Portland cement Type I or Type II. Provide Portland
cement of color required to produce approved mortar sample.
a. Colored Mortar Aggregates (permitted only under special conditions): Ground
stone, in colors required to match Architect's sample.
7. Mortar and Grout Mixes: Limit cementitious materials to lime and Portland cement. Do
not use calcium chloride additives.
UNIT MASONRY
04 2000 - 1
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
a. Mortar Colored with Pigments: Use organic pigments only. Do not exceed ratio
of pigment-to-cement recommended by pigment manufacturer.
8. Joint Reinforcement and Anchorage Materials:
a. Use stainless steel.
b. The use of galvanized steel in lieu of stainless steel shall be reviewed with the
NU Project Manager.
9. Cavity Wall Construction:
a. Horizontal Joint Reinforcement: Install continuously in bed joints at 16 inches on
center vertically to bond wythes of cavity walls, lapping individual sections at
least 6 inches. Use prefabricated L-shaped and T-shaped sections at corners
and intersections. Do not span movement joints with reinforcement.
i. Maximum CMU horizontal joint reinforcing spacing shall be 16” on center.
ii. Minimum CMU vertical reinforcing shall be a #4 bar at 48” on center, in
fully grouted cores.
b. Cavity Wall Insulation:
i. Extruded polystyrene is preferred over polyisocyanurate.
ii. The use of polyisocyanurate insulation in lieu of polystyrene shall be
reviewed with the NU Project Manager.
c. Provide a permanent weep system for masonry assemblies. Utilize a weep / air
space protective product to prevent obstructions from mortar droppings, etc.
i. Venting of Cavity Walls: Provide weatherproof method of venting at top
and bottom of internal cavities.
ii. Weeps: Provide permanent system of weeps that will remain free
draining and will not be clogged by mortar.
d. Architect is encouraged to utilize an air / vapor barrier (preferably a spray-applied
product) on the exterior face of the back-up component in a masonry assembly.
END OF SECTION
UNIT MASONRY
04 2000 - 2
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
DIVISION 4 – MASONRY
SECTION 04 4600 – LIMESTONE
1. General: This section outlines the general requirements for limestone masonry.
2. Design Considerations: To match existing stone bearing wall construction with modern
cavity wall veneer stone technique, the following notes should be incorporated into the
specifications:
a. Corner pieces shall be “L” shaped units with heights and lengths of pieces given
based on the project specific requirements.
b. Arrange corners with larger stones at the bottom, decreasing in size higher up
the building.
c. Edges of all units shall be hand chipped to remove shelves at mortar joints.
d. Vertical edges of the units shall be chipped or sawn to be vertical leaving a
uniform mortar joint.
e. The horizontal mortar joints shall be emphasized, uniform in thickness, and be as
long as practical.
f.
Grey hued stone will buff over time. It is best to start a bit grey when trying to
match existing older stone.
g. Most of the stone walls on the Evanston campus are a mixture of stone quarried
from horizontal locations (tan in color) and vertical edge pieces (grey in color).
h. Where appropriate, specify an abrasive blast to match existing “weathered” stone
finish.
i.
Utilize tern-coated through wall flashings to avoid any shiny stainless steel
edges.
j.
Two 5-foot by 7-foot mock-up wall samples shall be made for mortar color, stone
color, and to set the limit on stone unit “rectangleness”.
k. Once in place, the mock-up shall be made to confirm stone layout patterns and
limits on mortar joint uniformity. Once approve, the mock-up can remain in place.
3. Quality Assurance: Single Source Responsibility: Design, fabrication, and installation
shall be the responsibility of a single entity. Contractor shall require an engineer to
perform structural design, determine the testing program, and evaluate the test results.
The engineer shall be licensed in Illinois and have experience in engineering stonework
that has resulted in successful installation of stonework similar to that required for this
project.
LIMESTONE
04 4600 - 1
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
a. Safety factors: Use safety factor of 8. Design with redundant load paths, so that
failure of one element (fastener, anchor, etc.) does not result in failure of any
other element.
b. Normal Thermal Movement: Movement resulting from an air temperature range
of 120 degrees F, solar heat gain, and nighttime re-radiation.
c. Horizontal Building Movement: Allow for horizontal building movement from floor
to floor (interstory drift) not more than the floor-to-floor height divided by 400.
d. Individual Fasteners and Attachments: Design to withstand the stresses
produced by the following loads applied separately, applied through the center of
gravity of the element supported, each added to the stresses produced by
thermal movement: Vertical: 4 times the weight of the supported elements.
Horizontal: 2 times the weight of the supported elements.
e. Stone Testing: Test each variety of stone to show compliance with physical
characteristics specified. Test limestone in accordance with ASTM C 568. For
stone veneer thinner than 2-1/4 inches, perform modulus of rupture tests on
specimens of the smallest thickness and with the finish to be used on the project.
4. Stone pieces that are damaged during shipping, handling, etc. shall be reviewed by the
Architect / Owner prior to installation. The Architect / Owner shall have the discretion to
require that damaged pieces be repaired to their satisfaction prior to installation.
5. Submittals: Architect shall require the following minimum submittals:
f.
Contractor shall provide fully-dimensioned shop drawings that include “closing”
dimensions to the Architect’s dimensional reference (grid lines, face of
foundation, etc.) and that dimension rough opening sizes for windows, etc.
bounded by stone components.
g. Structural Design Data: Engineer's evaluation of test reports.
h. Testing program for full-scale mock-up testing.
i.
Test reports for tests indicated.
6. Limestone:
j.
Color: Buff.
k. Variety: Indiana Limestone.
l.
ILI Grade: Select preferred, other grades may be used under special conditions.
m. Selection from three 12-inch by 12-inch samples.
n. Classification II, medium density.
LIMESTONE
04 4600 - 2
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
o. Finishes: If shot sawn, also provide sandblasting at fabrication plant. Plucked
finishes are not permitted.
7. Accessory Materials:
p. Stone Anchors in Direct Contact with Stone: Stainless steel, Type 304 or 316
unless specifically indicated otherwise.
a. Provide internal gutter system for draining water from stone cladding in
accordance with the Indiana Limestone Institute Design Handbook.
END OF SECTION
LIMESTONE
04 4600 - 3
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
This page intentionally left blank
LIMESTONE
04 4600 - 4
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
DIVISION 5 – METALS
SECTION 05 1200 – STRUCTURAL STEEL FRAMING
1. General: This section outlines the general requirements for structural steel framing.
2. Structural Steel Design Considerations:
a. No bar joists shall be used for floor construction.
b. Consideration must be made for effects of hanger loads from M/E/P systems,
hung stairs, etc., on building structure.
c. Exterior lintels shall be galvanized.
d. Stainless steel should be considered for areas that are permanently exposed to
the elements.
e. For multi-story structures, design to a strict deflection limit. The fit & finish of
architectural components, the long term durability and construction delays
associated with elevated slab concrete that would need to be leveled (filled,
patched, bushed, topped, etc.), the additional loading on the structure associated
with increased concrete thickness needed to meet flatness / levelness standards,
etc. should all be considered when determining acceptable deflections.
f.
Architecturally exposed welded connections shall be ground smooth; for
materials indicated to be painted, the erector shall prime all exposed steel
following grinding.
3. Performance Requirements:
a. Connections: Provide details of connections required by the Construction
Documents to be selected or completed by structural-steel fabricator to withstand
ASD-service or LRFD loads indicated and comply with other information and
restrictions indicated.
b. Engineering Responsibility: Fabricator's responsibilities include using an Illinois
licensed structural engineer to prepare structural analysis data for structural-steel
connections.
4. Quality Assurance:
a. Installer Qualifications: A qualified installer who participates in the AISC Quality
Certification Program and is designated an AISC-Certified Erector.
b. Fabricator Qualifications: A qualified fabricator who participates in the AISC
Quality Certification Program and is designated an AISC-Certified Plant.
STRUCTURAL STEEL FRAMING
05 1200 – 1
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
c. Shop-Painting Applicators: Qualified according to AISC's Sophisticated Paint
Endorsement [P1] [P2] [P3] or SSPC-QP 3, "Standard Procedure for Evaluating
Qualifications of Shop Painting Applicators."
d. Welding: Qualify procedures and personnel according to AWS D1.1, "Structural
Welding Code--Steel."
e. Mockups: Build mockups of architecturally exposed structural steel to set quality
standards for fabrication and installation.
i. Approved mockups may become part of the completed Work if
undisturbed at time of Substantial Completion.
f.
Pre-Installation Conference Architect / Engineer shall coordinate requirements for
pre-installation conference with NU Project Manager.
5. Delivery, Storage, and Handling:
a. Contractor shall store materials to permit easy access for inspection and
identification. Keep steel members off ground and spaced by using pallets,
dunnage, or other supports and spacers. Protect steel members and packaged
materials from erosion and deterioration.
b. Contractor shall store fasteners in a protected place. Clean and relubricate bolts
and nuts that become dry or rusty before use.
c. Contractor shall not store materials on structure in a manner that might cause
distortion, damage, or overload to members or supporting structures. Repair or
replace damaged materials or structures as directed.
6. Coordination: Contractor shall furnish anchorage items to be embedded in or attached
to other construction without delaying the Work. Provide setting diagrams, sheet metal
templates, instructions, and directions for installation.
7. Products:
a. Structural Steel: Fabricate and assemble in shop to greatest extent possible.
Fabricate according to AISC's "Code of Standard Practice for Steel Buildings and
Bridges" and AISC's "Specification for Structural Steel Buildings--Allowable
Stress Design and Plastic Design or Load and Resistance Factor Design
Specification for Structural Steel Buildings."
i. Camber structural-steel members where indicated.
ii. Identify high-strength structural steel according to ASTM A 6/ A 6M and
maintain markings until structural steel has been erected.
iii. Mark and match-mark materials for field assembly.
iv. Complete structural-steel assemblies, including welding of units, before
starting shop-priming operations.
STRUCTURAL STEEL FRAMING
05 1200 – 2
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
b. Architecturally Exposed Structural Steel: Comply with fabrication requirements,
including tolerance limits, of AISC's "Code of Standard Practice for Steel
Buildings and Bridges" for structural steel identified as architecturally exposed
structural steel.
i. Fabricate with exposed surfaces smooth, square, and free of surface
blemishes including pitting, rust, scale, seam marks, roller marks, rolled
trade names, and roughness.
ii. Remove blemishes by filling or grinding or by welding and grinding,
before cleaning, treating, and shop priming.
c. Thermal Cutting: Perform thermal cutting by machine to greatest extent possible.
d. Bolt Holes: Cut, drill, mechanically thermal cut or punch standard bolt holes
perpendicular to metal surfaces.
e. Finishing: Accurately finish ends of columns and other members transmitting
bearing loads.
f.
Cleaning: Clean and prepare steel surfaces that are to remain unpainted.
g. Shear Connectors: Prepare steel surfaces as recommended by manufacturer of
shear connectors. Use automatic end welding of headed-stud shear connectors
according to AWS D1.1 and manufacturer's written instructions.
h. Steel Wall-Opening Framing: Select true and straight members for fabricating
steel wall-opening framing to be attached to structural steel. Straighten as
required to provide uniform, square, and true members in completed wall
framing.
i.
Holes: Provide holes required for securing other work to structural steel and for
passage of other work through steel framing members.
i. Cut, drill, or punch holes perpendicular to steel surfaces. Do not thermally
cut bolt holes or enlarge holes by burning.
ii. Base-Plate Holes: Cut, drill, mechanically thermal cut, or punch holes
perpendicular to steel surfaces.
iii. Weld threaded nuts to framing and other specialty items indicated to
receive other work.
8. Shop Connections:
a. High-Strength Bolts: Shop install high-strength bolts according to RCSC's
"Specification for Structural Joints Using ASTM A 325 or A 490 Bolts" for type of
bolt and type of joint specified.
STRUCTURAL STEEL FRAMING
05 1200 – 3
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
b. Weld Connections: Comply with AWS D1.1 for welding procedure specifications,
tolerances, appearance, and quality of welds and for methods used in correcting
welding work.
i. Remove backing bars or runoff tabs, back gouge, and grind steel smooth.
ii. Assemble and weld built-up sections by methods that will maintain true
alignment of axes without exceeding tolerances of AISC's "Code of
Standard Practice for Steel Buildings and Bridges" for mill material.
iii. Verify that weld sizes, fabrication sequence, and equipment used for
architecturally exposed structural steel will limit distortions to allowable
tolerances. Prevent weld show-through on exposed steel surfaces.
1. Grind butt welds flush.
2. Grind or fill exposed fillet welds to smooth profile. Dress exposed
welds.
9. Shop Priming:
a. Shop prime steel surfaces except the following:
i. Surfaces embedded in concrete or mortar. Extend priming of partially
embedded members to a depth of 2 inches (50 mm).
ii. Surfaces to be field welded
iii. Surfaces to be high-strength bolted with slip-critical connections
iv. Surfaces to receive sprayed fire-resistive materials
v. Galvanized surfaces
b. Surface Preparation: Clean surfaces to be painted. Remove loose rust and mill
scale and spatter, slag, or flux deposits.
c. Priming: Immediately after surface preparation, apply primer according to
manufacturer's written instructions and at rate recommended by SSPC to provide
a dry film thickness of not less than 1.5 mils (0.038 mm). Use priming methods
that result in full coverage of joints, corners, edges, and exposed surfaces.
i. Stripe paint corners, crevices, bolts, welds, and sharp edges.
ii. Apply two coats of shop paint to inaccessible surfaces after assembly or
erection. Change color of second coat to distinguish it from first.
d. Painting: Apply a 1-coat, nonasphaltic primer complying with SSPCPS Guide 7.00, "Painting System Guide 7.00: Guide for Selecting One-Coat
Shop Painting Systems," to provide a dry film thickness of not less than 1.5 mils
(0.038 mm).
STRUCTURAL STEEL FRAMING
05 1200 – 4
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
10. Galvanizing:
a. Hot-Dip Galvanized Finish: Apply zinc coating by the hot-dip process to
structural steel according to ASTM A 123/ A 123M.
i. Fill vent holes and grind smooth after galvanizing.
ii. Galvanize lintels and shelf angles attached to structural-steel frame and
located in exterior walls.
11. Source Quality Control:
a. Owner will engage an independent testing and inspecting agency to perform
shop tests and inspections and prepare test reports.
i. Provide testing agency with access to places where structural-steel work
is being fabricated or produced to perform tests and inspections.
b. Correct deficiencies in Work that test reports and inspections indicate does not
comply with the Contract Documents.
c. Bolted Connections: Shop-bolted connections will be tested and inspected
according to RCSC's "Specification for Structural Joints Using ASTM A 325 or
A 490 Bolts."
d. Welded Connections: In addition to visual inspection, shop-welded connections
will be tested and inspected according to AWS D1.1 and the following inspection
procedures, at testing agency's option:
i. Liquid Penetrant Inspection: ASTM E 165.
ii. Magnetic Particle Inspection: ASTM E 709; performed on root pass and
on finished weld. Cracks or zones of incomplete fusion or penetration will
not be accepted.
iii. Ultrasonic Inspection: ASTM E 164.
iv. Radiographic Inspection: ASTM E 94.
e. In addition to visual inspection, shop-welded shear connectors will be tested and
inspected according to requirements in AWS D1.1 for stud welding and as
follows:
i. Bend tests will be performed if visual inspections reveal either a lessthan- continuous 360-degree flash or welding repairs to any shear
connector.
ii. Tests will be conducted on additional shear connectors if weld fracture
occurs on shear connectors already tested, according to requirements in
AWS D1.1.
STRUCTURAL STEEL FRAMING
05 1200 – 5
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
12. Examination:
a. Verify elevations of concrete- and masonry-bearing surfaces and locations of
anchor rods, bearing plates, and other embedments, with steel erector present,
for compliance with requirements.
b. Proceed with installation only after unsatisfactory conditions have been
corrected.
13. Preparation:
a. Provide temporary shores, guys, braces, and other supports during erection to
keep structural steel secure, plumb, and in alignment against temporary
construction loads and loads equal in intensity to design loads. Remove
temporary supports when permanent structural steel, connections, and bracing
are in place, unless otherwise indicated.
i. Do not remove temporary shoring supporting composite deck
construction until cast-in-place concrete has attained its design
compressive strength.
14. Erection:
a. Set structural steel accurately in locations and to elevations indicated and
according to AISC's "Code of Standard Practice for Steel Buildings and Bridges"
and "Specification for Structural Steel Buildings--Allowable Stress Design and
Plastic Design or Load and Resistance Factor Design Specification for Structural
Steel Buildings."
b. Base and Bearing Plates: Clean concrete and masonry-bearing surfaces of
bond-reducing materials, and roughen surfaces prior to setting base and bearing
plates. Clean bottom surface of base and bearing plates.
c. Align and adjust various members forming part of complete frame or structure
before permanently fastening. Before assembly, clean bearing surfaces and
other surfaces that will be in permanent contact with members. Perform
necessary adjustments to compensate for discrepancies in elevations and
alignment.
d. Splice members only where indicated.
e. Remove erection bolts on welded, architecturally exposed structural steel; fill
holes with plug welds; and grind smooth at exposed surfaces.
f.
Do not use thermal cutting during erection.
g. Do not enlarge unfair holes in members by burning or using drift pins. Ream
holes that must be enlarged to admit bolts.
15. Field Connections:
STRUCTURAL STEEL FRAMING
05 1200 – 6
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
a. High-Strength Bolts: Shop install high-strength bolts according to RCSC's
"Specification for Structural Joints Using ASTM A 325 or A 490 Bolts" for type of
bolt and type of joint specified.
b. Weld Connections: Comply with AWS D1.1 for welding procedure specifications,
tolerances, appearance, and quality of welds and for methods used in correcting
welding work.
16. Field Quality Control:
a. Testing Agency: Owner will engage a qualified independent testing and
inspecting agency to inspect field welds and high-strength bolted connections.
b. Bolted Connections: Shop-bolted connections will be tested and inspected.
c. Welded Connections: Field welds will be tested and visually inspected.
d. Correct deficiencies in Work that test reports and inspections indicate does not
comply with the Contract Documents.
17. Repairs And Protection:
a. Repair damaged galvanized coatings.
b. Provide touchup painting as required.
END OF SECTION
STRUCTURAL STEEL FRAMING
05 1200 – 7
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
This page intentionally left blank
STRUCTURAL STEEL FRAMING
05 1200 – 8
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
DIVISION 5 – METALS
SECTION 05 3100 –STEEL DECKINIG
1. General: This section outlines the general requirements for steel decking.
2. Design Criteria:
a. Composite metal deck shall be a minimum thickness of 20 gauge.
b. Metal decking shall be provided with deck and flute closures, metal edge forms,
etc. as required to contain the wet concrete during slab-on-deck placement.
3. Design Considerations:
a. Edge of steel decking should be shown on structural drawings and coordinated
with architectural drawings.
END OF SECTION
STEEL DECKING
05 3100 – 1
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
This page intentionally left blank
STEEL DECKING
05 3100 – 2
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
DIVISION 5 – METALS
SECTION 05 5000 –METAL FABRICATIONS
1. General: This section outlines the general requirements for metal fabrications.
2. Design Criteria:
a. Except where it conflicts with fireproofing or welding, steel and miscellaneous
metal materials shall be shop primed.
b. Exterior lintels shall be galvanized.
c. Exterior railings shall be stainless steel.
d. Architecturally exposed welded connections shall be ground smooth.
i. For materials indicated to be painted, the erector shall prime all exposed
steel following grinding.
3. Bollards:
a. Bollards shall be placed sufficiently far apart for bicycle traffic and close enough
to prohibit automobile traffic.
b. Provide removable bollards with handles on each side located in the direction of
traffic.
c. Place removable bollards in a removable concrete band with troweled joints to
avoid expansion cracks. Tooled joints should be provided between bollards and
not from the recessed sleeves. Concrete band is to be flush with its
surroundings. A sealed expansion joint is to be provided between the concrete
band and asphalt pavement or adjacent roadway.
d. Provide a bank of additional receivers for the removable bollards, equal to the
number of bollards. Locate out of the way of traffic. These may be located in
lawn or mulched areas.
e. Provide two 2-inch wide reflective strips located 2-inches down from the top of
the bollard the second row 2-inches below the first strip.
f.
Northwestern shall provide a standard padlock for removable bollards.
g. Acceptable Manufacturer:
i. Cal-Pipe; Model SSP06000 removable, 6-inch, stainless steel bollard with
Model ESR060 embedment sleeve.
END OF SECTION
METAL FABRICATIONS
05 5000 – 1
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
This page intentionally left blank
METAL FABRICATIONS
05 5000 – 2
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
DIVISION 5 – METALS
SECTION 05 5100 – METAL STAIRS AND RAILINGS
1. General: This section outlines the general requirements for metal fabrications.
2. Design Criteria:
a. Exterior Railings:
i. Exterior railings shall be stainless steel. Painted handrails are not
permitted. Stainless steel, grade 316L is preferred.
ii. The preferred base detail for exterior railings is to use base plates and
fasteners.
iii.
If the condition requires a embedment of the bottom of the railing post,
then an epoxy-based setting compound should be utilized. Por-Rok is not
recommended.
iv. Side attachment using Hilti anchorage systems is also recommended in
lieu of embedding rail ends.
v. When mild steel balusters are used, provide stainless steel ends welded
to the mild steel for the embedded portion.
END OF SECTION
METAL STAIRS AND RAILINGS
05 5100 – 1
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
This page intentionally left blank
METAL STAIRS AND RAILINGS
05 5100 – 2
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
DIVISION 5 – METALS
SECTION 05 7230 – STAIR TREADS AND NOSINGS
1. General: This section outlines the general requirements for stair treads and nosings.
2. Design Criteria:
a. Stair Nosings: For interior and exterior public stairs, provide full length, non-slip
nosings and treads.
END OF SECTION
STAIR TREADS AND NOSINGS
05 7230 – 1
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
This page intentionally left blank
STAIR TREADS AND NOSINGS
05 7230 – 2
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
DIVISION 6 –WOOD, PLASTICS & COMPOSITES
SECTION 06 1000 – ROUGH CARPENTRY
1. General: This section outlines general requirements for rough carpentry.
2. Design Considerations:
a. Rough Carpentry:
i. Lumber products shall meet a minimum grade standard of “No. 2 or
better.”
ii. Load bearing lumber shall meet the following minimum working stresses:
f = 1,000 psi, H = 135 psi and E = 1,300,000 psi.
iii. Wood products used in wet locations (windows, roofs, etc.) shall be
moisture-treated. Moisture-treated lumber shall be kiln-dried following
treatment.
iv. Interior wood blocking shall be fire-treated lumber.
v. Electrical rooms and communication closets shall have at least two 4 ft. x
8 ft. plywood backboards; refer to NUIT Standards for requirements at
main telecommunication rooms.
vi. Backboard plywood shall be a minimum of 3/4”, BC, fire-treated and
painted.
b. Wood Trusses:
i. Truss supplier shall be responsible for submitting engineered calculations
stamped by an engineer registered in the State of Illinois.
ii. Truss calculations shall account for mechanical and electrical utilities
supported from the bottom chord of the trusses.
iii. The minimum bottom chord member size shall be nominal 2x6.
END OF SECTION
ROUGH CARPENTRY
06 1000 – 1
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
This page intentionally left blank
ROUGH CARPENTRY
06 1000 – 2
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
DIVISION 6 –WOOD, PLASTICS & COMPOSITES
SECTION 06 4000 – ARCHITECTURAL WOODWORK
1. General: This section outlines general requirements for architectural woodwork.
2. Quality Assurance:
a. Single Source Manufacturing and Installation Responsibility: Require a qualified
Manufacturer to assume sole responsibility for woodwork, including fabrication,
finishing, and installation.
b. FSC Certified Wood: Review project specific requirements with NU Project
Manager.
3. Woodwork:
a. Woodwork: AWI “Custom” grade typical; “Premium” grade for door frames and
sidelights and for laboratory casework.
b. Include the following for laboratory casework:
i. Five knuckle exposed hinges;
ii. Solid wood drawer sides;
iii. Plywood drawer bottoms with chemical/moisture resistant finish;
iv. 150 lb. drawer glides with return;
v. Solid, epoxy resin tops;
vi. Chemical resistant plastic laminate shelving;
vii. Under cabinet lighting.
4. Wood Materials:
a. General: Comply with applicable requirements of AWI Section 100.
b. Formaldehyde Emission Levels: Comply with formaldehyde emission
requirements of each voluntary AWI standards.
END OF SECTION
ARCHITECTURAL WOODWORK
06 4000 – 1
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
This page intentionally left blank
ARCHITECTURAL WOODWORK
06 4000 – 2
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
DIVISION 7 – THERMAL AND MOISTURE PROTECTION
SECTION 07 2100 – THERMAL INSULATION
1. General: This section outlines general requirements for building insulation.
2. Design Considerations:
a. Architect shall perform a dew point analysis of the exterior wall enclosure.
b. Thermal Insulation: Provide the following minimum R values:
i. Walls: R20
ii. Roofs: R30
c. Vapor Barriers: Provide a continuous vapor barrier system at the warm side of
building insulation.
END OF SECTION
THERMAL INSULATION
07 2100 – 1
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
This page intentionally left blank
THERMAL INSULATION
07 2100 – 2
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
DIVISION 7 – THERMAL AND MOISTURE PROTECTION
SECTION 07 2700 – BARRIERS (FIRE STOPPING AND SMOKE STOPPING)
1. General: This section outlines general requirements for firestopping and smoke
stopping systems.
2. Design Considerations
a. General: Products for fire stopping and smoke stopping shall be by a single
manufacturer throughout the project.
b. Fire Stopping:
i. Provide penetration seal assemblies whose fire-resistance ratings have
been tested in configurations required and have appropriate fireresistance ratings for the fire-rated assembly in which they are to be
installed.
ii. Comply with applicable codes; provide assemblies listed by Underwriters
Laboratories Inc. (UL).
iii. Provide products which emit no hazardous, combustible, or irritating byproducts during installation or curing period and do not require special
tools for installation.
c. Smoke Stopping:
i. Use Hilti Foam or other approved joint sealant suitable for the application;
use only fully curing types where accessible in the finished work.
ii. Provide products which:
1. Allow normal expansion and contraction movement of the
penetrating item without failure of the penetration seal;
2. Emit no hazardous, combustible, or irritating by-products during
installation or curing period; and
3. Do not require special tools for installation.
b. Provide a “use matrix” indicating manufacturer and UL label system for each
condition on the drawings or in the technical specifications.
END OF SECTION
BARRIERS
07 2700 – 1
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
This page intentionally left blank
BARRIERS
07 2700 – 2
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
DIVISION 7 – THERMAL AND MOISTURE PROTECTION
SECTION 07 3126 – SLATE SHINGLES
1. General: This section outlines general requirements for slate shingles.
2. Materials:
a. Slate Shingles: ASTM C 406 Grade S2 slate shingles, machine punched for two
nails located for proper head lap and complying with the following requirements:
i. Type: Standard shingles.
ii. Texture: Rough texture.
iii. Colors: To be reviewed with the NU Project Manager during the design
phases of the project.
b. Snow Guards: Prefabricated copper units designed for use with slate shingle
roofing and complete with hook for installation onto slate.
i. Basis of Design:
1. Snow Guards as manufactured by Zaleski Snow Guards, Inc.
END OF SECTION
SLATE SHINGLES
07 3126 – 1
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
This page intentionally left blank
SLATE SHINGLES
07 3126 – 2
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
DIVISION 7 – THERMAL AND MOISTURE PROTECTION
SECTION 07 5200 – MODIFIED BITUMINOUS MEMBRANE ROOFING
1. General: This section outlines general requirements for modified bituminous membrane
roofing systems.
2. Design Considerations:
a. Do not use single ply roofing in high traffic areas.
3. Performance Requirements: Meet standards of both of the following:
a. Factory Mutual System Classification: Provide roofing materials and a roofing
system assembly, which have been listed in the Factory Mutual System
"Approval Guide" as being acceptable for Class I roof assembly construction.
Provide roof system, including insulation and fasteners, rated by FM for Class I90 wind uplift.
b. UL 790: Class A rating for flammability for external fire exposure.
4. Roof System:
a. Provide a two-ply system, with a heavy base sheet as the bottom ply. Finish with
Type II flood coat at 70 lbs / square and gravel at 400 lbs / square.
b. Provide APP of SPS base flashings cover with fibrated coating after installation.
c. Insulation System Requirements:
i. Flame spread: 75 or less when tested in accordance with ASTM E 84.
ii. Minimum average "R-value" in accordance with ASTM C 518 after
conditioning: R30 at 75 degrees F.
iii. Polyisocyanurate Foam: ASTM C 591.
iv. Top: 1/2 inch thick, perlite board is preferred.
d. Accessories:
i. Roof Drain Flashing: 2-1/2-pound to 4-pound lead sheet.
ii. Walkways: Roofing membrane manufacturer's granule-surfaced modified
bituminous sheet intended for use as a protection course for foot traffic.
1. Width: 36 inches.
5. Warranty Requirements: Review project specific requirements with NU Project
Manager.
MODIFIED BITUMINOUS MEMBRANE ROOFING
07 5200 – 1
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
6. Quality Assurance:
a. Manufacturer's Qualifications:
i. A company that has produced roofing materials and accessories of the
type included in this section for at least 5 years.
ii. Certification: Furnish to the University, before roofing contract award,
written documentation that installer is manufacturer-certified to install
roofing systems of the type included in this section.
b. Installer Qualifications:
i. Installation Requirements: The installer shall execute the entire project
with a single crew and superintendent.
ii. Installer supervision: Have installer identify a supervisor with at least 5
years experience in the application of the type of modified bituminous
sheet roofing system included in this section, to provide full-time review of
built-up roofing installation work.
c. Initial Roofing Meeting: Before start of roof deck construction, a meeting shall be
held with General Contractor, roofing installer; installers of roof deck, roofmounted equipment, and other work adjacent to or integral with the roof system;
the architect; the owner and other parties concerned with roofing system
performance.
d. Pre-Roofing Meeting: Contractor shall organize and conduct a meeting at the
construction site 2 weeks before scheduled start of roof system installation with
roofing installer; installer of each component of related work, including deck or
substrate construction, roof equipment, penetrations of roof deck, and other work
integral with or adjacent to roofing; the architect; the owner; the roofing
manufacturer's representative; and other parties involved with roofing system
performance, including owner's insurance representative, independent testing
agencies, and governing authorities.
END OF SECTION
MODIFIED BITUMINOUS MEMBRANE ROOFING
07 5200 – 2
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
DIVISION 7 – THERMAL AND MOISTURE PROTECTION
SECTION 07 5323 – ETHYLENE-PROPYLENE-DIENE-MONOMER (EPDM) ROOFING
1. General: This section outlines general requirements for EPDM roofing systems.
2. Design Considerations:
a. Do not use single ply roofing in high traffic areas.
3. Performance Requirements: Meet standards of both of the following:
a. Factory Mutual System Classification: Provide roofing materials and a roofing
system assembly, which have been listed in the Factory Mutual System
"Approval Guide" as being acceptable for Class I roof assembly construction.
Provide roof system, including insulation and fasteners, rated by FM for Class I90 wind uplift.
b. UL 790: Class A rating for flammability for external fire exposure.
4. Roof System:
a. Single Ply Roofing Membrane:
i. Membrane Material: EPDM sheet, 0.060 inch (60 mils) thick.
ii. Minimum properties: ASTM D 4637, Type I, Grade 1 or 2, Class SR,
scrim or fabric internal reinforced.
iii. Manufacturers: Provide products by one of the following manufacturers:
1. Carlisle SynTec Systems Division / Carlisle Corporation.
2. Firestone Building Products Company.
3. Other manufacturers may be considered upon reviewed with NU.
iv. Color: Manufacturer's standard black or dark gray.
b. Flashing: Cured EPDM, Nominal 0.060 inch thick except uncured EPDM,
Nominal 0.060 inch thick, for conditions where flashing is formed around corners,
projections, or changes in direction. Match color of membrane material.
c. Insulation System Requirements: Provide type and style of insulation that meets
contract requirements and is approved by the membrane manufacturer for the
indicated installation.
i. Flame spread: 75 or less when tested in accordance with ASTM E 84.
EPDM ROOFING
07 5323– 1
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
ii. Minimum average "R-value" in accordance with ASTM C 518 after
conditioning: R30 at 75 degrees F.
iii. Polyisocyanurate Foam: ASTM C 591.
iv. Top: 1/2 inch thick, perlite board is preferred.
d. Walkways: Provide 2 foot square precast concrete pavers at 26-inches on
center leading from roof access point to all equipment areas.
i. Concrete shall provide a minimum of 4000 psi compressive strength and
95/115 pcf density.
ii. Provide manufacturer recommended slip sheet under pavers.
5. Warranty Requirements: Review project specific requirements with NU Project
Manager.
6. Quality Assurance:
a. Manufacturer's Qualifications:
i. A company that has produced roofing materials and accessories of the
type included in this section for at least 5 years.
ii. Certification: Furnish to the University, before roofing contract award,
written documentation that installer is manufacturer-certified to install
roofing systems of the type included in this section.
b. Installer Qualifications:
i. Installation Requirements: The installer shall execute the entire project
with a single crew and superintendent.
ii. Installer supervision: Have installer identify a supervisor with at least 5
years of experience in the application of the type of modified bituminous
sheet roofing system included in this section, to provide full-time review of
built-up roofing installation work.
c. Initial Roofing Meeting: Before start of roof deck construction, a meeting shall be
held with General Contractor, roofing installer; installers of roof deck, roofmounted equipment, and other work adjacent to or integral with the roof system;
the architect; the owner and other parties concerned with roofing system
performance.
d. Pre-Roofing Meeting: Contractor shall organize and conduct a meeting at the
construction site 2 weeks before scheduled start of roof system installation with
roofing installer; installer of each component of related work, including deck or
substrate construction, roof equipment, penetrations of roof deck, and other work
integral with or adjacent to roofing; the architect; the owner; the roofing
manufacturer's representative; and other parties involved with roofing system
EPDM ROOFING
07 5323– 2
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
performance, including owner's insurance representative, independent testing
agencies, and governing authorities.
END OF SECTION
EPDM ROOFING
07 5323– 3
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
This page intentionally left blank
EPDM ROOFING
07 5323– 4
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
DIVISION 7 – THERMAL AND MOISTURE PROTECTION
SECTION 07 5419 – POLYVINYL CHLORIDE (PVC) ROOFING
1. General: This section outlines general requirements for PVC roofing systems.
2. Design Considerations:
a. Do not use single ply roofing in high traffic areas.
3. Performance Requirements: Meet standards of both of the following:
a. Factory Mutual System Classification: Provide roofing materials and a roofing
system assembly, which have been listed in the Factory Mutual System
"Approval Guide" as being acceptable for Class I roof assembly construction.
Provide roof system, including insulation and fasteners, rated by FM for Class I90 wind uplift.
b. UL 790: Class A rating for flammability for external fire exposure.
4. Roof System:
a. Single Ply Roofing Membrane:
i. Membrane Material: PVC sheet, minimum 0.060 inch (60 mils) thick.
Review the option of 0.080 inch (80 mils) thick membrane with NU Project
Manager.
ii. Minimum properties: ASTM D 4434, Type II, Grade I, glass fiber
reinforced, felt backed.
iii. Manufacturer - Roof System: Provide products of the following
manufacturer:
1. Sarnafil Inc.; Sarnafil G410.
iv. Color: Manufacturer's standard white.
b. Flashing: PVC 0.060 inch thick.
c. Insulation System Requirements:
i. Flame spread: 75 or less when tested in accordance with ASTM E 84.
ii. Minimum average "R-value" in accordance with ASTM C 518 after
conditioning: 30 at 75 degrees F.
iii. Polyisocyanurate Foam: ASTM C 591.
PVC ROOFING
07 5419– 1
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
iv. Cover Board: ASTM C 1177/C 1177M, glass-mat, water-resistant
gypsum substrate, 1/2 inch (13 mm) factory primed.
1. Products: USG; Securock.
2. Roof /cover board should be installed in accordance with local
buildings codes, roof system manufacturer’s written instructions,
and FMG and UL installation requirements.
d. Accessories:
i. Roof Drain Flashing: Zinc-Tin Alloy-Coated Stainless Steel
ii. Walkways: PVC walkway protective membrane as coordinated with the
PVC roofing membrane manufacturer.
5. Warranty Requirements: Review project specific requirements with NU Project
Manager.
6. Quality Assurance:
a. General: Roofing system, insulation, and cover board shall be installed in
accordance with local building codes, roof system manufacturer’s written
instructions, and FMG and UL installation requirements.
b. Manufacturer's Qualifications:
i. A company that has produced roofing materials and accessories of the
type included in this section for at least 5 years.
ii. Certification: Furnish to the University, before roofing contract award,
written documentation that installer is manufacturer-certified to install
roofing systems of the type included in this section.
c. Installer Qualifications:
i. Installation Requirements: The installer shall execute the entire project
with a single crew and superintendent.
ii. Installer supervision: Have installer identify a supervisor with at least 5
years of experience in the application of the type of modified bituminous
sheet roofing system included in this section, to provide full-time review of
built-up roofing installation work.
d. Initial Roofing Meeting: Before start of roof deck construction, a meeting shall be
held with General Contractor, roofing installer; installers of roof deck, roofmounted equipment, and other work adjacent to or integral with the roof system;
the architect; the owner and other parties concerned with roofing system
performance.
PVC ROOFING
07 5419– 2
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
e. Pre-Roofing Meeting: Contractor shall organize and conduct a meeting at the
construction site 2 weeks before scheduled start of roof system installation with
roofing installer; installer of each component of related work, including deck or
substrate construction, roof equipment, penetrations of roof deck, and other work
integral with or adjacent to roofing; the architect; the owner; the roofing
manufacturer's representative; and other parties involved with roofing system
performance, including owner's insurance representative, independent testing
agencies, and governing authorities.
END OF SECTION
PVC ROOFING
07 5419– 3
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
This page intentionally left blank
PVC ROOFING
07 5419– 4
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
DIVISION 7 – THERMAL AND MOISTURE PROTECTION
SECTION 076 200 – SHEET METAL FLASHING AND TRIM
1. General: This section outlines general requirements for sheet metal flashing and trim.
2. Materials: Do not use galvanized metal in exterior applications. Use one of the
following:
a. Stainless Steel Sheet: ASTM A 167, Type 316L, non-corroding. Finish: 2D (dull
annealed).
b. Copper Sheet: ASTM B 370, of temper appropriate for use.
c. Terne Coated Stainless Steel Sheet: ASTM A 167, Type 304 sheet, coated both
sides with terne alloy (80 percent lead; 20 percent tin); FS QQ-T-201F, Type II.
Minimum coating weight: 40 lb., nominal (1.45 ounces per square foot total
coating weight).
d. Fasteners: Fasteners shall be stainless steel screw-type fasteners. Nail-in or
driven type fasteners shall not be allowed.
3. Preformed Reglet Flashing Systems:
a. Furnish manufactured product wherever possible. Provide secure interlocking of
separate reglet and counterflashing pieces.
b. Basis of Design Manufacturers: Subject to compliance with requirements,
provide products by the following manufacturers:
i. Fry Reglet Corporation.
ii. Keystone Flashing Company.
4. Gutters And Downspouts:
a. Fabricate from same material and finish used for adjacent exposed flashings.
b. Provide removable debris screens for gutters, fabricated from 1/4-inch mesh wire
cloth of same material used for gutters or approved compatible material.
c. Provide formed sheet metal frame on 4 sides of each screen unit. Length of
screen units shall not exceed 10 feet.
d. Provide wire basket type strainers at downspouts, fabricated from wire and sheet
metal of same material used downspouts or approved compatible material.
Provide sheet metal baffles 6 inches high with legs 18 inches long at gutter
corners below roof valleys.
SHEET METAL FLASHING AND TRIM
07 6200– 1
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
e. Provide formed metal splash pans fabricated from same type of sheet metal used
for downspouts. Locate where downspout discharges onto lower roof.
END OF SECTION
SHEET METAL FLASHING AND TRIM
07 6200– 2
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
DIVISION 7 – THERMAL AND MOISTURE PROTECTION
SECTION 07 7200 – ROOF ACCESSORIES (HEAT AND SMOKE VENTS)
1. General: This section outlines general requirements for roof accessories including heat
and smoke vents.
2. Design Considerations:
a. Heat and Smoke Vents:
i. Labels: Provide units listed and labeled by Underwriters Laboratories Inc.
(UL) or Factory Mutual System (FM) for emergency automatic heat and
smoke relief venting.
1. Operation to be by fusible link, with temperature rating of 50
degrees F above highest ambient temperature.
ii. Construction: Cover in galvanized sheet steel, mill phosphatized to
receive paint finish; 14 gage outside face, rigid insulation 1 inch thick, 22
gage inner liner; fully welded and reinforced for rigidity.
iii. Curb: Fully welded units, manufacturer's standard height but not less
than 12 inches from base flange to top of frame. Fabricate from same
material and thickness used for cover top.
iv. Insulation: Wood fiberboard, minimum 1 inch thick, protected by metal
liner of same material and thickness used for inner liner of cover.
v. Hinges: Spring lift mechanism, sized to open doors with 10 pounds per
square foot uniform live load applied to exterior.
1. Shock absorbers or similar damping mechanism to prevent
uncontrolled rapid opening of doors.
2. Hold-open arm, set to hold cover at 90 degrees, with detent
release.
END OF SECTION
ROOF ACCESSORIES
07 7200– 1
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
This page intentionally left blank
ROOF ACCESSORIES
07 7200– 2
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
DIVISION 7 – THERMAL AND MOISTURE PROTECTION
SECTION 07 9200 – JOINT SEALANTS
1. General: This section outlines general requirements for joint sealants.
2. Quality Assurance:
a. Field Installation Tests: Before installation, test the adhesion of each sealant to
actual substrates.
3. Mock-ups: Before beginning installation, install sealants in joints in required mock-ups to
show color, materials, and installation.
4. Warranty: Review project specific requirements with the NU Project Manager.
5. Materials:
a. Elastomeric Sealants:
i. Elastomeric Sealants – General: Chemically curing elastomeric sealants
of types indicated, complying with ASTM C 920, including specific Type,
Grade, Class, and Uses indicated, as well as all other requirements
specified.
b. Paving Joint Sealants:
i. Two-part Urethane Paving Sealant: Pourable, chemically curing (coldapplied) complying with FS SS-S-200.
ii. Composition: Urethane, with minimum movement capability of plus or
minus 12-1/2 percent.
c. High Movement Silicone Sealant:
i. One- or two-part, non-acid-curing, ASTM C 920, Grade NS (Non-Sag),
Class 25, Use NT, plus movement capability of at least 50 percent in both
extension and compression.
d. Low-Modulus Urethane Sealant:
i. Non-Sag, two-part, ASTM C 920, Type M, Grade NS, Class 25, Use NT,
plus movement capability of 50 percent in both extension and
compression.
e. Urethane Exterior Wall Sealant:
i. Nonsag, two-part, ASTM C 920 for Use T: Type S or M, Grade NS, Class
25, Use T.
JOINT SEALANTS
07 9200– 1
NORTHWESTERN UNIVERSITY
Technical Standards
f.
Issuance Date: 01.01.2014
Solvent-Release-Curing Sealants:
i. Acrylic Sealant: Nonsag, one-part, solvent-release-curing; complying with
ASTM C 920, Type S, Grade NS, Use NT, with the following exceptions:
ii. Weight loss: 15 percent maximum.
iii. Movement capability: 7-1/2 percent in both extension and compression,
minimum.
g. Butyl Sealant:
i. Nonsag, one part, solvent-release-curing; complying with FS A-A-272,
Type III; nonstaining; paintable.
h. Latex Sealants:
i. Acrylic-Latex Emulsion Sealant: One-part, nonsag, mildew-resistant,
paintable; complying with ASTM C 834.
i.
Noncuring Sealers:
i. Butyl Polyisobutylene Sealant: Noncuring, nondrying, solvent-release;
complying with 809.2, as described in AAMA 800.
j.
Sealant Backers:
i. General: Non-staining.
ii. Recommended or approved by sealant manufacturer for specific use.
6. Schedule of Recommended Joint Sealers:
a. Exterior Joints for Which No Other Sealer Is Indicated:
i. Use one of the following sealants: High movement silicone sealant or
two-part nonsag low-modulus urethane sealant.
ii. Backer: Backer rod.
iii. Joint shape: Concave joint configuration.
b. Interior Joints for Which No Other Sealer Is Indicated:
i. Use the following sealant: Acrylic-emulsion latex sealant.
ii. Backer: Backer rod.
iii. Joint shape: Concave joint configuration.
JOINT SEALANTS
07 9200– 2
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
c. Below-Grade Joints:
i. Use the following sealant: Urethane sealant for water immersion.
ii. Backer: Backer rod.
iii. Joint shape: Concave joint configuration.
d. Exterior Joints Well Protected from Weather and Not Subject to Movement:
i. Use one of the following sealants: Acrylic sealant; Butyl sealant.
ii. Backer: Backer rod.
e. Vehicular Paving Joints, Not Over 1-1/2 Percent Slope:
i. Use the following sealant: Two-part cold-applied urethane paving sealant.
Use bond-breaker tape.
ii. Backer: Joint filler as required.
f.
Interior Floor Joints and Pedestrian Paving Joints, Less than 1-1/2 Percent
Slope:
i. Use one of the following sealants: Silicone sealant for Use T; Two-part
nonsag urethane sealant for Use T.
ii. Backer: Backer rod.
iii. Joint shape: Flush joint configuration.
g. Joints around Pipes, Ducts, and Conduit Penetrating Exterior Walls and Roofs:
Same as used for adjacent substrates.
h. Joints in Interior Wet Areas:
i. Mildew-resistant silicone sealant.
ii. Backer: Backer rod.
iii. Joint shape: Concave joint configuration.
i.
Concealed Joints in Acoustical Assemblies:
i. Butyl polyisobutylene sealant.
END OF SECTION
JOINT SEALANTS
07 9200– 3
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
This page intentionally left blank
JOINT SEALANTS
07 9200– 4
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
DIVISION 8 – OPENINGS
SECTION 08 1113 – HOLLOW METAL DOORS AND FRAMES
1. General: This section outlines general requirements for interior and exterior hollow
metal doors and frames.
2. Design Considerations:
a. Paired doors are discouraged. When paired doors are absolutely necessary
provide removable mullions.
i. Exception: No mullions are required at laboratory access and low use
paired doors.
b. Exterior doors shall be galvanized.
c. Solid grout frames, both interior and exterior, at concrete, concrete masonry,
brick masonry, or limestone walls.
d. Provide batt insulation full perimeter of hollow metal frames in interior walls at
drywall partitions.
3. Quality Assurance:
a. Fire Rated Door Assemblies: Comply with SDI 100, Fire-Rated Door Assemblies
and in compliance with NFPA 80 and labeled per ASTM E 152 by UL, FM or
Warnock-Hersey.
b. Temperature Rise Rating: For fire-rated doors in stairwell enclosures, provide
door construction tested and certified to limit temperature rise in thirty minutes to
450 degrees, F.
4. Manufacturers: Products of the following manufacturer, provided they comply with
requirements of the contract documents:
a. Basis-of-Design: 747 N Series by The Curries Company or approved equal.
5. Steel Doors: Fabricate steel doors in accordance with requirements of SDI 100.
a. Doors: Grade III - Extra Heavy-Duty, Model 1 - Full Flush, 16 ga. min. face skin
for exterior use and 18 ga. min. for interior use. Stiffened with 20 ga. ribs spaced
not more than 6” apart, 14ga. lock rail, 12 ga. continuous channel hinge rail, 16
ga. top and bottom rails, seamless edges. Provide 12 ga. reinforcing for closer at
head.
b. Exterior Doors: Fabricate from hot-dip galvanized steel.
HOLLOW METAL DOORS AND FRAMES
08 1113– 1
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
c. Insulated Assemblies: At exterior locations, provide insulating door and frame
assemblies which have been tested in accordance with ASTM C 236 for thermal
resistance.
i. Minimum U-value: 0.24 BTU per hour per square foot per degree F
d. Acoustical Assemblies: Provide assemblies tested by ASTM E 90 procedures
and classified in compliance with ASTM E 413.
e. Hardware Preparation: Comply with DHI A115 series specifications.
f.
Glazed or Louvered Doors: Provide minimum 12-inch high bottom rail.
6. Steel Frames: Fabricate steel frames with concealed fasteners.
a. Construction: Mitered and welded corners. Reinforce head with 12 ga. can.
b. 14 ga. for exterior locations, 16ga. for interior locations.
c. Exterior Frames: Fabricate from hot-dip galvanized steel.
END OF SECTION
HOLLOW METAL DOORS AND FRAMES
08 1113– 2
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
DIVISION 8 – OPENINGS
SECTION 08 1416 – WOOD DOORS
1. General: This section outlines general requirements for wood doors.
2. Design Considerations:
a. Wood doors are for interior use only and not for exterior applications, with the
following exception:
i. Use of custom wood doors for exterior applications may be required for
historic buildings. Review specific project requirements with NU Project
Manager.
b. Natural finishes are preferred. Opaque finishes shall be permitted under special
conditions.
c. Solid, staved wood core doors with matching hardwood stiles and rails shall be
specified, with the exception that mineral cores shall be used for fire rated doors
where required by code.
2. Warranties:
a. Solid core, wood-faced, interior doors: 5 years.
b. Solid core, plastic laminate-faced, interior doors: 5 years.
3. Wood Doors:
a. Solid Core Wood-Faced Doors: Face veneers for transparent finish, Premium
Grade, Premium, 5 ply construction.
b. Solid Core Plastic Laminate-Faced Doors: High-pressure decorative laminate
faces meeting the requirements of NEMA LD 3, Custom Grade, 5 ply
construction.
c. Stile and Rail Wood Doors: Permitted under special conditions. NWWDA
Premium/Select grade.
4. Wood Door Frames:
a. Steel frames are preferred. Wood frames are permitted only in special situations.
Architect shall review requirements and options with NU Project Manager.
a. Fabricate frames in accordance with AWI Section 900 and casings in accordance
with AWI Section 200. Same grade as door.
END OF SECTION
WOOD DOORS
08 1416– 1
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
This page intentionally left blank
WOOD DOORS
08 1416– 2
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
DIVISION 8 – OPENINGS
SECTION 08 3113 – ACCESS DOORS AND FRAMES
1. General: This section outlines general requirements for access doors and frames.
2. Design Considerations:
a. Architect to review locations for access doors and access panels with NU Project
Manager during the design phase.
b. If possible, access door and access panel locations shall be shown on the
drawings.
c. All access doors shall be by the same manufacturer. If necessary, the
Construction Manager and/or General Contractor shall coordinate with each
subcontractor.
3. Manufactured Units: The following are the minimum requirements for manufactured
access doors and frames. Architect shall review specific requirements with the NU
Project Manager.
a. Type: Flush door panel with exposed frame.
b. Frame: 14 gage steel.
c. Door: 14 gage steel flush panel; when fire-rated, provide standard insulated
flush panel/doors with continuous piano hinge.
d. Hinge: Double-acting concealed spring hinges allowing door to open a minimum
of 165 degrees.
e. Locking device: Keyed cylinder lock. Supply 2 keys with each lock. Key all
cylinder locks to keying system established for other finish hardware.
f.
Finish: Baked-on rust-inhibitive prime coat.
4. Fabrication: Fabricate access door and door components of continuous welded
construction, with welds ground smooth.
5. Exposed Frames: Fabricate frame with nominal 1-inch-wide exposed flange at door
panel perimeter.
6. Doors: Flush panel doors: Fabricate door panel from material and material gage
indicated, with a smooth face, and with door edges installed square with door frame.
7. Shop/Factory Finishing: Prime paint finish: Where indicated, finish door assembly with
manufacturer's standard factory-applied rust-inhibitive primer.
END OF SECTION
ACCESS DOORS AND FRAMES
08 3113– 1
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
This page intentionally left blank
ACCESS DOORS AND FRAMES
08 3113– 2
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
DIVISION 8 – OPENINGS
SECTION 08 4113 – ALUMINUM FRAMED ENTRANCES AND STOREFRONTS
1. General: This section outlines general requirements for aluminum framed entrances and
storefronts.
2. Design Considerations:
a. Kawneer TUFFLINE system is preferred, with 8-1/4” mid rail, 10-1/4” bottom rail,
and 1” insulating glass.
b. Provide all welded construction with back-sealed joints to prevent light leaks.
c. Provide ROTON Series 780LL continuous hinges. Refer to Door Hardware
section for additional information.
d. Paired doors are discouraged. When paired doors are necessary, provide fixed
or removable mullions.
3. Performance Requirements – Exterior Assemblies: Design to comply with the
performance criteria listed below:
a. Thermal Movement: Design to accommodate expansion and contraction
resulting from air temperature range of 120 degrees F, solar heat gain, and
nighttime re-radiation.
b. Structural Performance: Design to withstand all live and dead loads without
deformation and without deflection greater than 1/175 of span.
c. Deflection in Plane of Wall: Not greater than that which would reduce glass edge
clearance to 25 percent of design dimension or 1/8 inch, whichever is greater, or
that which would reduce glass bite to 75 percent of design dimension.
d. Wind Loads:
i. Determine in accordance with ASCE 7.
ii. Design system to withstand 150 percent of design wind load with no
failure or permanent deformation greater than 0.2 percent of span.
e. Air Infiltration:
i. Fixed Framing: Not more than 0.06 cfm per square foot of fixed area
ii. Measure at 6.24 psf
iii. Single Doors: Not more than 0.5 cfm per linear foot of crack
ALUMINUM FRAMED ENTRANCES AND STOREFRONTS
08 4113– 1
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
iv. Pairs of Doors (Not recommended): Not more than 1.0 cfm per linear foot
of crack
v. Doors: Measure at 1.57 psf
f.
Water Penetration:
i. Fixed framing (excluding operable door edges): No penetration at 6.24
psf.
g. Condensation Resistance:
i. Fixed framing: Not less than 45.
ii. Door frames: Not less than 48.
h. Thermal Transmittance (U-Value):
i. Fixed framing: Not more than 0.65.
ii. Door frames: Not more than 0.93.
4. Warranty: Review project specific requirements with NU Project Manager.
5. Materials:
a. Aluminum Members: ASTM B 221 for extrusions, ASTM B 209 for sheet/plate;
alloy and temper recommended by the manufacturer for the strength required, for
corrosion resistance, and for the finish required.
b. Fluoropolymer Finish: Multiple coats of thermally cured primer and topcoats,
resin minimum 70 percent "Kynar 500" or "Hylar 5000"; comply with AAMA 605.2
and AA-C12C42R1X (inhibited chemical-cleaned; acid chromate-fluoridephosphate chemical coating; organic coating). Clean with inhibited chemicals and
conversion-coat with acid chromate-fluoride- phosphate treatment, in accordance
with coating manufacturer's instructions. Products: Provide one of the following
products:
i. "Fluropon"; The Valspar Corporation.
ii. "Nubelar" or "Nubelar S"; The Glidden Company.
iii. "Duranar"; PPG Industries, Inc.
6. Framing Systems:
a. Aluminum Framing System: Extruded aluminum.
b. Style: Flush glazed (without projecting stops), with glazing centered in frame
members; see drawings for profiles, dimensions, and arrangement of members.
ALUMINUM FRAMED ENTRANCES AND STOREFRONTS
08 4113– 2
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
c. Framing members: Thermally improved or thermally broken design with
concealed, low thermal conductance material completely separating exterior
metal members from interior metal members. Use only standard construction
methods which have been in use for at least five (5) years.
d. Glazing method: Resilient gasket glazed, with provision for replacement of
glazing without disassembly of framing.
e. Finish: Review options with NU Project Manager during the design phase.
f.
Aluminum Door Frames: Extruded tube or channel frames with welded joints.
7. Swinging Doors:
a. Stile and Rail Doors: Glazed doors with tubular extruded aluminum frame
members.
b. Frame joints: Welded.
c. Thickness: 1-3/4 inches.
d. Stile width: 5 inches (Narrow stile doors are not recommended).
e. Full glazed, with one mullion minimum.
f.
Glazing stops: Snap-on extruded aluminum, designed to allow replacement of
glazing without disassembly of frame. Provide non-removable exterior stops.
g. Finish: Typically to match framing system. Review options with NU Project
Manager during the design phase.
h. Weather-stripping:
i. At fixed stops: Replaceable, compression type molded gaskets of
neoprene or EPDM rubber complying with C 864 or of polyvinyl chloride
complying with ASTM D 2287.
ii. At other edges: Replaceable woven polypropylene, wool, or nylon pile,
with aluminum or nylon fabric backing, complying with AAMA 701.
iii. Provide weather-stripping on all exterior doors.
END OF SECTION
ALUMINUM FRAMED ENTRANCES AND STOREFRONTS
08 4113– 3
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
This page intentionally left blank
ALUMINUM FRAMED ENTRANCES AND STOREFRONTS
08 4113– 4
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
DIVISION 8 – OPENINGS
SECTION 08 5000 – WINDOWS
1. General: This section outlines general requirements for exterior windows.
2. Design Considerations:
a. Fixed windows are preferred. Operable windows will be permitted in residence
halls and under special conditions.
b. Maintain clearance from adjacent surfaces to permit re-glazing.
c. Wood windows are not permitted.
d. Window Design: Where glazing stops are indicated, design for re-glazing without
removal or dismantling of ventilator/sash or frames.
i. Operable ventilator/sash: Design so ventilator/sash can be removed from
inside. In residence halls at first floors and other areas accessible from
grade, provide ventilating locks at 4” open position.
ii. Provide weather-stripping on all operable ventilator/sash in exterior wall.
iii. Thermally improved or thermally broken construction: Provide frame and
ventilator/sash members with concealed, structural, load-bearing, low
thermal conductance material separating exterior metal members from
interior metal members.
Use only a standard construction which has
been in use at least five (5) years. Do not bridge thermal gap with any
fasteners or hardware.
iv. Glazing Stops: Aluminum to match windows, screwed or snapped on.
3. Performance Requirements: As specified in AAMA 101, for window type, grade, and
class indicated.
4. Basis of Design Manufacturers:
a. Double-hung windows: Traco TR-9000 or Milco/Wasau #3750 are preferred.
b. Projected windows: Traco TR-3500 preferred.
c. Casement windows: Traco TR-3100 or EFCO Series 590 are preferred.
d. Acceptable field values: Not more than 1.5 times laboratory allowed value.
e. Acceptable field result: No water leakage.
f.
Thermal Performance Required: Thermally improved or thermally broken
construction.
WINDOWS
08 5000– 1
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
5. Quality Assurance:
a. Test Units: Fabricated in accordance with requirements of contract documents,
fully assembled, and glazed as specified in AAMA 101.
i. Air, Water, and Structural Test Methods: As specified in AAMA 101.
ii. Component Structural Test Methods: As specified in AAMA 101.
b. Field Tests:
i. Air infiltration test method: ASTM E 783.
ii. Water infiltration test method: AAMA 501.3.
6. Warranty: Review project specific requirements with NU Project Manager.
7. Fixed Windows: (Preferred for all windows)
a. Glazing method: Compression gasket/sealant tape; glazing stops; pre-glazed.
b. Grade: F, Heavy Commercial.
8. Hung Windows (for Residence Halls): Vertically sliding sash, with counterbalances.
Provide tilting sash to allow cleaning of both sides of sash from inside of same unit.
a. Glazing method: Compression gasket/sealant tape; glazing stops; pre-glazed
b. Grade: DH-HC40
c. Counterbalances: One on each side of each operable sash
d. Hardware: Locks: Manufacturer's standard
e. Lift handle: Continuous bar on bottom rail
f.
Pull-down handle: Continuous pull on bottom rail
9. Materials:
a. Fluoropolymer coating: Multiple coats of thermally cured fluoropolymer primer
and top coats, resin minimum 70 percent "Kynar 500" or "Hylar 5000"; comply
with AAMA 605.2 and AA-C12C42R1X (inhibited chemical-cleaned; acid
chromate-fluoride-phosphate chemical conversion coating; organic coating).
Provide the number and type of coats as recommended by coating manufacturer
for color and sheen required.
b. Fasteners: Do not use exposed fasteners, except for hardware.
i. Hardware fasteners: Match finish of members to which they are fastened.
Anchor fasteners: Same as anchors.
WINDOWS
08 5000– 2
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
ii. Other fasteners: Noncorrosive and corrosion-resistant material that is
compatible with materials being fastened.
c. Concealed Anchors: Specify one or more of the following:
i. Aluminum.
ii. Steel, zinc electroplated after fabrication in accordance with ASTM B 633.
iii. Stainless steel.
d. Pile Weather Stripping: Woven polypropylene, wool, or nylon pile; complying
with AAMA 701.
e. Sealants:
i. Use only non-hardening, non-shrinking, and non-migrating materials.
ii. For nonworking, metal-to-metal joints within window units: Small joint
sealant conforming to 803.3, as described in AAMA 800.
iii. For joints between other window components: Suitable for application.
iv. For joints between window units and other building components: Provide
products specified in Division 7.
v. For glazing: Provide products specified elsewhere.
10. Accessories:
a. Window Cleaner's Anchors: Stainless steel; designed, located, and anchored to
comply with ASME A39.1 or with requirements of governing authorities if more
stringent. Reinforce window frames and anchor frames to structure as required.
Verify location of anchors with the owner. Install window cleaner's anchors at
each exterior window above the ground floor.
b. Insect Screens: Formed or extruded aluminum frames with screen fabric. Design
to fit tightly, but be removable, using as few exposed fasteners or latches as
possible.
i. Do not use wickets for access to window-operating hardware, unless
absolutely necessary; make wickets hinged or sliding, with the same type
of frames as screens, and tight-fitting. Frame construction: Minimum wall
thickness of 0.040-inch, with joints mitered or coped and fastened with
concealed fasteners. Anchor screen fabric with removable plastic or
rubber splines
ii. Finish: To match window.
iii. Screen Fabric: Aluminum wire fabric complying with FS RR-W-365, Type
VII.
WINDOWS
08 5000– 3
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
iv. Mesh size: Window manufacturer's standard.
v. Provide screens for all operable ventilators/sash
11. Field Quality Control: Test for air and water infiltration after installation. Review specific
requirements with NU Project Manager during the design phase.
END OF SECTION
WINDOWS
08 5000– 4
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
DIVISION 8 – OPENINGS
SECTION 08 7100 – Door Hardware
1. General:
a. This section outlines the requirements for door hardware.
b. Door hardware specifications shall be reviewed with the NU Project Manager and
the NU Lock Shop during the design phases of the project.
2. SUMMARY
a. This Section includes commercial door hardware for the following:
i. Swinging doors.
ii. Sliding Doors.
iii. Other doors to the extent indicated.
b. Door hardware includes, but is not necessarily limited to, the following:
i. Mechanical door hardware.
ii. Electromechanical door hardware, power supplies, back-ups and surge
protection.
iii. Automatic operators.
iv. Cylinders specified for doors in other sections.
c. Related Sections:
i. Section 06 10 00 – Rough Carpentry.
ii. Section 06 20 00 – Finish Carpentry.
iii. Section 08 01 00 – Operations and Maintenance.
iv. Section 08 06 10 – Door Schedule.
v. Section 08 06 71 – Door Hardware Schedule.
vi. Section 08 11 13 – Hollow Metal Doors and Frames.
vii. Section 08 14 16 – Flush Wood Doors.
viii. Section 08 14 23 – Clad Wood Doors.
ix. Section 08 14 33 – Stile and Rail Wood Doors.
DOOR HARDWARE
08 7100– 1
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
x. Section 08 17 00 – Integrated Door Opening Assemblies.
xi. Section 08 41 13 – Aluminum-Framed Entrances and Storefronts.
xii. Section 08 42 26 – All-Glass Entrances.
xiii. Section 08 42 29 – Automatic Entrances.
xiv. Section 08 71 13 – Automatic Door Operators.
xv. Section 08 81 00 – Glass and Glazing.
xvi. Section 09 90 00 – Painting and Coating.
xvii. Section 28 13 00 – Access Control.
d. Codes and References: Comply with the version year adopted by the Authority
Having Jurisdiction.
i. ANSI A117.1 - Accessible and Usable Buildings and Facilities.
ii. ANSI/SDI A250.13 - Testing and Rating of Severe Windstorm Resistant
Components for Swing Door Assemblies.
iii. ASTM E1886 - Test Method for Performance of Exterior Windows, Curtin
Walls, Doors and Shutters Impacted by Missiles and Exposed to Cyclic
Pressure Differentials.
iv. ASTM E330 - Standard Test Method for Structural Performance of
Exterior Windows, Curtain Walls, and Doors by Uniform Static Air
Pressure difference.
v. ASTM E1996 - Standard specification for performance of exterior
windows, curtain walls, doors and storm shutters impacted by Windborne
Debris in Hurricanes.
vi. FEMA 361 2008 - Design and Construction Guidance for Community Safe
Rooms.
vii. ICC 500 - ICC/NSSA Standard for the Design and Construction of Storm
Shelters.
viii. ICC/IBC - International Building Code.
ix. NFPA 70 - National Electrical Code.
x. NFPA 80 - Fire Doors and Windows.
xi. NFPA 101 - Life Safety Code.
xii. NFPA 105 - Installation of Smoke Door Assemblies.
DOOR HARDWARE
08 7100– 2
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
xiii. TAS-201-94 - Impact Test Procedures.
xiv. TAS-202-94 - Criteria for Testing Impact and Non-Impact Resistant
Building Envelope Components using Uniform Static Air Pressure.
xv. TAS-203-94 - Criteria for Testing Products Subject to Cyclic Wind
Pressure Loading.
e. Standards: Hardware specified herein shall comply with the following industry
standards:
i. ANSI/BHMA Certified Product Standards - A156 Series
ii. UL10C – Positive Pressure Fire Tests of Door Assemblies
3. SUBMITTALS
a. Product Data: Manufacturer's product data sheets including installation details,
material descriptions, dimensions of individual components and profiles,
operational descriptions and finishes.
b. Door Hardware Schedule: Prepared by or under the supervision of supplier,
detailing fabrication and assembly of door hardware, as well as procedures and
diagrams. Coordinate the final Door Hardware Schedule with doors, frames, and
related work to ensure proper size, thickness, hand, function, and finish of door
hardware.
i. Format: Comply with scheduling sequence and vertical format in DHI's
"Sequence and Format for the Hardware Schedule."
ii. Organization: Organize the Door Hardware Schedule into door hardware
sets indicating complete designations of every item required for each
door or opening. Organize door hardware sets in same order as in the
Door Hardware Sets at the end of Part 3. Submittals that do not follow the
same format and order as the Door Hardware Sets will be rejected and
subject to resubmission.
iii. Content: Include the following information:
1. Type, style, function, size, label, hand, and finish of each door
hardware item.
2. Manufacturer of each item.
3. Fastenings and other pertinent information.
4. Location of door hardware set, cross-referenced to Drawings,
both on floor plans and in door and frame schedule.
5. Explanation of abbreviations, symbols, and codes contained in
schedule.
DOOR HARDWARE
08 7100– 3
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
6. Mounting locations for door hardware.
7. Door and frame sizes and materials.
iv. Submittal Sequence: Submit the final Door Hardware Schedule at
earliest possible date, particularly where approval of the Door Hardware
Schedule must precede fabrication of other work that is critical in the
Project construction schedule. Include Product Data, Samples, Shop
Drawings of other work affected by door hardware, and other information
essential to the coordinated review of the Door Hardware Schedule.
c. Proof of Certification: Provide copy of manufacturer(s) official certification or
accreditation document indicating proof of status as a qualified and authorized
provider of the primary Integrated Wiegand Access Control Products.
d. Keying Schedule: Prepared by the Owner, Contractor to order manufacturer
pinned cylinders.
e. Operating and Maintenance Manuals: Provide manufacturers operating and
maintenance manuals for each item comprising the complete door hardware
installation in quantity as required in Division 01, Closeout Submittals. The
manual to include the name, address, and contact information of the
manufacturers providing the hardware and their nearest service representatives.
The final copies delivered after completion of the installation test to include "as
built" modifications made during installation, checkout, and acceptance.
f.
Warranties and Maintenance: Special warranties and maintenance agreements
specified in this Section.
4. QUALITY ASSURANCE
a. Manufacturers Qualifications: Engage qualified manufacturers with a minimum 5
years of documented experience in producing hardware and equipment similar to
that indicated for this Project and that have a proven record of successful inservice performance.
b. Installer Qualifications: Installers, trained by the primary product manufacturers,
with a minimum 3 years documented experience installing both standard and
electrified builders hardware similar in material, design, and extent to that
indicated for this Project and whose work has resulted in construction with a
record of successful in-service performance.
c. Door Hardware Supplier Qualifications: Experienced commercial door
hardware distributors with a minimum 5 years documented experience supplying
both mechanical and electromechanical hardware installations comparable in
material, design, and extent to that indicated for this Project. Supplier recognized
as a factory direct distributor in good standing by the manufacturers of the
primary materials with a warehousing facility in Project's vicinity.
DOOR HARDWARE
08 7100– 4
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
d. Supplier to have a certified Architectural Hardware Consultant (AHC) available
during the course of the Work to consult with Contractor, Architect, and Owner
concerning both standard and electromechanical door hardware and keying.
i. Scheduling Responsibility: Preparation of door hardware schedules.
e. Automatic Operator Supplier Qualifications: Suppliers are to be factory trained,
certified, and a direct purchaser of the specified power operators and be
responsible for the installation and maintenance of the units and accessories
indicated for the Project.
f.
Source Limitations: Obtain each type and variety of Door Hardware specified
in this Section from a single source, qualified supplier unless otherwise indicated.
i. Electrified modifications or enhancements made to a source
manufacturer's product line by a secondary or third party source will not
be accepted.
ii. Provide electromechanical door hardware from the same manufacturer
as mechanical door hardware, unless otherwise indicated.
g. Regulatory Requirements: Comply with NFPA 70, NFPA 80, NFPA 101 and
ANSI A117.1 requirements and guidelines as directed in the model building code
including, but not limited to, the following:
i. NFPA 70 "National Electrical Code", including electrical components,
devices, and accessories listed and labeled as defined in Article 100 by a
testing agency acceptable to authorities having jurisdiction, and marked
for intended use.
ii. Where indicated to comply with accessibility requirements, comply with
Americans with Disabilities Act (ADA), "Accessibility Guidelines for
Buildings and Facilities (ADAAG)," ANSI A117.1 as follows:
1. Handles, Pulls, Latches, Locks, and other Operating Devices:
Shape that is easy to grasp with one hand and does not require
tight grasping, tight pinching, or twisting of the wrist.
2. Door Closers: Comply with the following maximum openingforce requirements indicated:
a. Interior Hinged Doors: 5 lbf applied perpendicular to door.
b. Fire Doors: Minimum opening force allowable by
authorities having jurisdiction.
3. Thresholds: Not more than 1/2 inch high. Bevel raised thresholds
with a slope of not more than 1:2.
iii. NFPA 101: Comply with the following for means of egress doors:
DOOR HARDWARE
08 7100– 5
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
1. Latches, Locks, and Exit Devices: Not more than 15 lbf to release
the latch. Locks shall not require the use of a key, tool, or special
knowledge for operation.
2. Thresholds: Not more than 1/2 inch high.
h. Fire-Rated Door Assemblies: Provide door hardware for assemblies complying
with NFPA 80 that are listed and labeled by a testing and inspecting agency
acceptable to authorities having jurisdiction, for fire ratings indicated, based on
testing according to NFPA 252 (neutral pressure at 40" above sill) or UL-10C.
i. Test Pressure: Positive pressure labeling.
i.
Pre-Submittal Conference: Conduct coordination conference in compliance with
requirements in Division 01 Section "Project Meetings" with attendance by
representatives of Supplier(s), Installer(s), and Contractor(s) to review proper
methods and the procedures for receiving, handling, and installing door
hardware.
i. Prior to installation of door hardware, arrange for manufacturers'
representatives to hold a project specific training meeting to instruct the
installing contractors' personnel on the proper installation and adjustment
of their respective products. Product training to be attended by installers
of door hardware (including electromechanical hardware) for aluminum,
hollow metal and wood doors. Training will include the use of installation
manuals, hardware schedules, templates and physical product samples
as required.
ii. Inspect and discuss electrical roughing-in, power supply connections, and
other preparatory work performed by other trades.
iii. Review sequence of operation narratives for each unique access
controlled opening.
iv. Review and finalize construction schedule and verify availability of
materials.
v. Review the required inspecting, testing, commissioning, and
demonstration procedures.
5. DELIVERY, STORAGE, AND HANDLING
a. Inventory door hardware on receipt and provide secure lock-up and shelving for
door hardware delivered to Project site. Do not store electronic access control
hardware, software or accessories at Project site without prior authorization.
b. Tag each item or package separately with identification related to the final
Door Hardware Schedule, and include basic installation instructions with each
item or package.
DOOR HARDWARE
08 7100– 6
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
c. Deliver, as applicable all manufacture supplied, permanent keys, access
control credentials, software and related accessories directly to Owner via
registered mail or overnight package service. Instructions for delivery to the
Owner shall be established at the "Keying Conference".
6. COORDINATION
a. Templates: Obtain and distribute to the parties involved templates for doors,
frames, and other work specified to be factory prepared for installing standard
and electrified hardware. Check Shop Drawings of other work to confirm that
adequate provisions are made for locating and installing hardware to comply
with indicated requirements.
b. Door Hardware and Electrical Connections: Coordinate the layout and
installation of scheduled electrified door hardware and related access control
equipment with required connections to source power junction boxes, low voltage
power supplies, detection and monitoring hardware, and fire and detection alarm
systems.
c. Door and Frame Preparation: Related Division 08 Sections (Steel, Aluminum
and Wood) doors and corresponding frames are to be prepared, reinforced and
pre-wired (if applicable) to receive the installation of the specified electrified,
monitoring, signaling and access control system hardware without additional infield modifications.
7. WARRANTY
a. General Warranty: Reference Division 01, General Requirements. Special
warranties specified in this Article shall not deprive Owner of other rights Owner
may have under other provisions of the Contract Documents and shall be in
addition to, and run concurrent with, other warranties made by Contractor under
requirements of the Contract Documents.
b. Warranty Period: Written warranty, executed by manufacturer(s), agreeing to
repair or replace components of standard and electrified door hardware that
fails in materials or workmanship within specified warranty period after final
acceptance by the Owner. Failures include, but are not limited to, the following:
i. Structural failures including excessive deflection, cracking, or breakage.
ii. Faulty operation of the hardware.
iii. Deterioration of metals, metal finishes, and other materials beyond normal
weathering.
iv. Electrical component defects and failures within the systems operation.
c. Standard Warranty Period: One year from date of Substantial Completion,
unless otherwise indicated.
d. Special Warranty Periods:
DOOR HARDWARE
08 7100– 7
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
i. Ten (10) years for mortise locks and latches.
ii. Five (5) years for exit hardware.
iii. Ten (10) years for manual door closers.
iv. Two (2) years for electromechanical door hardware.
8. MAINTENANCE SERVICE
a. Maintenance Tools and Instructions: Furnish a complete set of specialized tools
and maintenance instructions as needed for Owner's continued adjustment,
maintenance, and removal and replacement of door hardware.
b. Continuing Service: Beginning at Substantial Completion, and running
concurrent with the specified warranty period, provide continuous (6) months full
maintenance including repair and replacement of worn or defective components,
lubrication, cleaning, and adjusting as required for proper door opening
operation. Provide parts and supplies as used in the manufacture and installation
of original products.
9. SCHEDULED DOOR HARDWARE
a. General: Provide door hardware for each door to comply with requirements in
Door Hardware Sets and each referenced section that products are to be
supplied under.
i. Designations: Requirements for quantity, item, size, finish or color,
grade, function, and other distinctive qualities of each type of door
hardware are indicated in the Door Hardware Sets at the end of Part 3.
Products are identified by using door hardware designations, as
follows:
1. Named Manufacturer's Products: Product designation and
manufacturer are listed for each door hardware type required for
the purpose of establishing requirements. Manufacturers' names
are abbreviated in the Door Hardware Schedule.
2. Products furnished, but not installed, under this Section include
the following. Coordinating, purchasing, delivering, and scheduling
remain requirements of this Section.
a. Permanent cores to be installed by contractor.
b. Keys to be issued by Owner.
b. Finishes – All finishes for hardware [(626/630/689), (613/690), or (612/691)]
are available as university standards. (606/688) available with special approval.
No other finishes will be allowed without approval from owner and 20% additional
product for attic stock to the owner.
DOOR HARDWARE
08 7100– 8
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
c. Substitutions: No substitutions will be allowed without prior approval from the
owner in writing. Any substitution approved will also need to supply 20%
additional of each hardware item approved not in the university standard for attic
stock
10. HANGING DEVICES
a. Hinges: ANSI/BHMA A156.1 certified butt hinges with number of hinge knuckles
as specified in the Door Hardware Sets.
i. Quantity: Provide the following hinge quantity, unless otherwise indicated:
1. Two Hinges: For doors with heights up to 60 inches.
2. Three Hinges: For doors with heights 61 to 90 inches.
3. Four Hinges: For doors with heights 91 to 120 inches.
4. For doors with heights more than 120 inches, provide 4 hinges,
plus 1 hinge for every 30 inches of door height greater than 120
inches.
ii. Hinge Size: Provide the following, unless otherwise indicated, with
hinge widths sized for door thickness and clearances required:
1. Widths up to 3’0”: 4-1/2” standard or heavy weight as specified.
2. Sizes from 3’1” to 4’0”: 5” standard or heavy weight as specified.
iii. Hinge Weight and Base Material: Unless otherwise indicated, provide the
following:
1. Exterior Doors: Heavy weight, non-ferrous, ball bearing hinges
unless Hardware Sets indicate standard weight.
2. Interior Doors: Standard weight, steel, ball bearing hinges
unless Hardware Sets indicate heavy weight.
3. Tornado Resistant Assemblies: At a minimum, provide heavy
weight hinges with stainless steel screws used in accordance
with and specified as part of a Severe Storm Shelter Opening
meeting ICC 500 and FEMA 361.
iv. Hinge Options: Comply with the following where indicated in the
Hardware Sets or on Drawings:
1. Non-removable Pins: Provide set screw in hinge barrel that, when
tightened into a groove in hinge pin, prevents removal of pin while
door is closed; for the following applications:
a. Out-swinging exterior doors.
DOOR HARDWARE
08 7100– 9
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
b. Out-swinging access controlled doors.
v. Acceptable Manufacturers:
1. Hager Companies (HA).
2. McKinney Products (MK).
b. Continuous Geared Hinges: ANSI/BHMA A156.26 certified continuous geared
hinge with minimum 0.120-inch thick extruded 6060 T6 aluminum alloy hinge
leaves and a minimum overall width of 4 inches. Hinges are non-handed,
reversible and fabricated to template screw locations. Provide concealed flush
mount (with or without inset), full surface, or half surface, in standard and heavy
duty models, as specified in the Hardware Sets. Concealed continuous
hinges to be U.L. listed for use on up to and including 90 minute rated door
installations and U.L. listed for windstorm components where applicable. Factory
cut hinges for door size and provide with removable service power transfer panel
where indicated at electrified openings.
i. Acceptable Manufacturers:
1. Pemko Manufacturing (PE).
2. McKinney Products (MK).
c. Pin and Barrel Continuous Hinges: ANSI/BHMA A156.26 certified pin and
barrel continuous hinges with minimum 12 gauge (.105) Type 304 stainless steel
hinge leaves, concealed teflon- coated stainless pin, and twin self-lubricated
nylon bearings at each knuckle separation. Fabricate hinges non-handed and
U.L. listed for use on up to and including 3 hour rated doors and U.L. listed for
windstorm components where applicable. Provide hinges with power transfer
cutouts where indicated at electrified openings.
i. Acceptable Manufacturers:
1. Markar Products (MA).
2. McKinney Products (MK).
3. Pemko Manufacturing (PE).
d. Floor Closers: ANSI/BHMA A156.4 certified floor closers provided either center
hung or 3/4" offset hung type complete with top and intermediate pivots (offset
closers only) in quantity according to manufacturer's recommendation. Floor
closers available with options for labeled, lead lined and regular doors. Provide
independent and adjustable valves for closing speed, latch speed, and
backcheck with built-in dead stop and hold open features as specified. Provide
finish cover plates or thresholds as indicated in door Hardware Sets.
i. Acceptable Manufacturers:
DOOR HARDWARE
08 7100– 10
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
1. Rixson Door Controls (RF).
e. Pivots: ANSI/BHMA A156.4, Grade 1, certified pivots provided either center
hung or 3/4" offset type complete with top, bottom, and intermediate pivots
(offset pivots only) in quantity according to manufacturer's recommendations.
Space intermediate pivots equally not less than 25 inches on center apart or not
more than 35 inches on center for doors over 121 inches high. Pivot hinges to
have oil impregnated bronze bearing in the top pivot and a radial roller and
thrust bearing in the bottom pivot with the bottom pivot designed to carry the full
weight of the door. Pivots to be UL listed for windstorm where applicable.
i. Acceptable Manufacturers:
1. Rixson Door Controls (RF).
f.
Sliding Door Hardware: Sliding door hardware is to be of type and design as
specified and should comply with ANSI/BHMA A156.14.
i. Sliding Bi-Passing Pocket Door Hardware: Provide complete sets
consisting of track, hangers, stops, bumpers, floor channel, guides, and
accessories indicated.
ii. Bi-folding Door Hardware: Rated for door panels weighing up to 125 lb.
iii. Pocket Sliding Door Hardware: Rated for doors weighing up to 200 lb.
iv. Acceptable Manufacturers:
1. Hafele Manufacturing (HF).
2. Pemko Manufacturing (PE).
11. POWER TRANSFER DEVICES
a. Electrified Quick Connect Transfer Hinges: Provide electrified transfer hinges
with Molex™ standardized plug connectors and sufficient number of concealed
wires (up to 12) to accommodate the electrified functions specified in the Door
Hardware Sets. Connectors plug directly to through-door wiring harnesses for
connection to electric locking devices and power supplies. Wire nut connections
are not acceptable.
i. Acceptable Manufacturers:
1. Hager Companies (HA) - ETW-QC (# wires) Option.
2. McKinney Products (MK) - QC (# wires) Option.
b. Electrified Quick Connect Continuous Geared Transfer Hinges: Provide
electrified transfer continuous geared hinges with a 12" removable service panel
cutout accessible without de- mounting door from the frame. Furnish with
Molex™ standardized plug connectors with sufficient number of concealed wires
DOOR HARDWARE
08 7100– 11
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
(up to 12) to accommodate the electrified functions specified in the Door
Hardware Sets. Connectors plug directly to through-door wiring harnesses for
connection to electric locking devices and power supplies. Wire nut connections
are not acceptable.
i. Acceptable Manufacturers:
1. Bommer Industries (BO) - SER-QC (# of wires) Option.
2. McKinney Products (MK) - SER-QC (# wires) Option.
3. Pemko Manufacturing (PE) - SER-QC (# wires) Option.
c. Electrified Quick Connect Stainless Steel Continuous Transfer Hinges: Provide
electrified transfer stainless steel continuous hinges with electrical transfer
access prep accessible without de-mounting door from the frame. Furnish with
Molex™ standardized plug connectors with sufficient number of concealed wires
(up to 12) to accommodate the electrified functions specified in the Door
Hardware Sets. Connectors plug directly to through-door wiring harnesses for
connection to electric locking devices and power supplies. Wire nut connections
are not acceptable.
i. Acceptable Manufacturers:
1. Markar Products (MA) - MP-ETAP-EL (# wires) Option.
2. McKinney Products (MK) - MCK-ETAP-EL (# wires) Option.
d. Electrified Quick Connect Intermediate Transfer Pivots: Provide electrified offset
intermediate transfer pivot hinges with Molex™ standardized plug connectors
and sufficient number of concealed wires (up to 12) to accommodate the
electrified functions specified in the Door Hardware Sets. Connectors plug
directly to through-door wiring harnesses for connection to electric locking
devices and power supplies. Wire nut connections are not acceptable.
i. Acceptable Manufacturers:
1. Rixson Door Controls (RF) - E-M19-QC (# wires).
e. Electric Door Hardware Cords: Provide electric transfer wiring harnesses with
standardized plug connectors to accommodate up to twelve (12) wires.
Connectors plug directly to through- door wiring harnesses for connection to
electric locking devices and power supplies. Provide sufficient number of
concealed wires to accommodate electric function of specified hardware. Provide
a connector for through-door electronic locking devices and from hinge to
junction box above the opening. Wire nut connections are not acceptable.
Determine the length required for each electrified hardware component for the
door type, size and construction, minimum of two per electrified opening.
i. Acceptable Manufacturers:
DOOR HARDWARE
08 7100– 12
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
1. McKinney Products (MK) - Inner Door Cord 3 inches: QC-C003P.
2. McKinney Products (MK) - Inner Door Cord 3 foot door: QCC206P.
3. McKinney Products (MK) - Inner Door Cord 4 foot door: QCC306P.
4. McKinney Products (MK) - Inner Door Cord 15 feet: QC-C1500P.
5. McKinney Products (MK) - Hinge to Junction Panel 15 feet: QCC1500P.
6. Or Northwestern University approved equal.
f.
Provide one each of the following tools as part of the base bid contract to the
contractor:
i. McKinney Products (MK) - Electrical Connecting Kit: 52-3000.
ii. McKinney Products (MK) - Connector Hand Tool: 52-0439.
iii. Or Northwestern University approved equal..
12. DOOR OPERATING TRIM
a. Flush Bolts and Surface Bolts: ANSI/BHMA A156.3 and A156.16, Grade 1,
certified automatic, self-latching, and manual flush bolts and surface bolts.
Manual flush bolts to be furnished with top rod of sufficient length to allow bolt
location approximately six feet from the floor. Furnish dust proof strikes for
bottom bolts. Surface bolts to be minimum 8” in length and U.L. listed for labeled
fire doors and U.L. listed for windstorm components where applicable. Provide
related accessories (mounting brackets, strikes, coordinators, etc.) as required
for appropriate installation and operation.
i. Acceptable Manufacturers:
1. McKinney Architectural Hardware (MK).
2. Rockwood Manufacturing (RO).
b. Coordinators: ANSI/BHMA A156.3 certified door coordinators consisting of
active-leaf, hold- open lever and inactive-leaf release trigger. Coordinators
fabricated from steel with nylon- coated strike plates and built-in adjustable
safety release.
i. Acceptable Manufacturers:
1. McKinney Architectural Hardware (MK).
2. Rockwood Manufacturing (RO).
DOOR HARDWARE
08 7100– 13
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
c. Door Push Plates and Pulls: ANSI/BHMA A156.6 certified door pushes and
pulls of type and design specified below or in the Hardware Sets. Coordinate
and provide proper width and height as required where conflicting hardware
dictates.
i. Push/Pull Plates: Minimum .050 inch thick, 4-inches wide by 16-inches
high, with square corners and beveled edges, secured with exposed
screws unless otherwise indicated.
ii. Straight Pull Design: Minimum 1-inch round diameter stainless steel
bar or tube stock pulls with 2 1/2-inch projection from face of door unless
otherwise indicated.
iii. Offset Pull Design: Minimum 1-inch round diameter stainless steel bar or
tube stock pulls with 2 1/2-inch projection and offset of 90 degrees unless
otherwise indicated.
iv. Push Bars: Minimum 1-inch round diameter horizontal push bars with
minimum clearance of 2 1/2-inch projection from face of door unless
otherwise indicated.
v. Fasteners: Provide machine screws for all metal doors (drill and tap not
self-tapping) and provide manufacture standard for all wood doors.
vi. Acceptable Manufacturers:
1. Rockwood Manufacturing (RO).
2. McKinney (MK)
3. Trimco (TR)
d. Locking Pull System: Post-mount style door pulls with integrated deadbolt
locking system in type and design as specified in the Hardware Sets. Pulls
available in multiple head, floor, or combination locking options, with outside
keyed rim cylinder operation and inside turn piece activation. Mounting
applications for aluminum, glass, steel and wood doors, with customized sizing
and configuration options. Pull finishes include brass, bronze, and stainless steel.
Provide pulls standard with dustproof strike and auxiliary door stop as specified.
i. Acceptable Manufacturers:
1. Rockwood Manufacturing (RO) – LP Series.
2. Blumcraft (BL)
13. CYLINDERS AND KEYING
a. General: Permanent cores to be supplied by Owner.
DOOR HARDWARE
08 7100– 14
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
b. Permanent Cores: Manufacturer's standard; finish face to match lockset;
complying with the following:
i. Acceptable Manufacturers:
1. Medeco M3 fixed core (MC) – No Substitution permanent
cylinders provided by contractor.
14. MECHANICAL LOCKS AND LATCHING DEVICES
a. Mortise Locksets, Grade 1 (Heavy Duty): ANSI/BHMA A156.13, Series 1000,
Operational Grade 1 certified mortise locksets furnished in the functions as
specified in the Hardware Sets. Locksets to be manufactured with a corrosion
resistant, stamped 12 gauge minimum formed steel case and be fieldreversible for handing without disassembly of the lock body. Lockset trim
(including knobs, levers, escutcheons, roses) to be the product of a single
manufacturer. Furnish with standard 2 3/4" backset, 3/4" throw anti-friction
stainless steel latchbolt, and a full 1" throw stainless steel bolt for deadbolt
functions.
i. Acceptable Manufacturers:
1. Sargent Manufacturing (SA) – LC 8200 Series. Provide #97
cylinder rosette for all keyed locks.
b. Multi-Point Locksets: Vertical rod locking devices designed for openings
requiring multiple latching points within one locking mechanism. Rods are
retracted by dual mounted outside lever trim controls available in a variety of
ANSI/BHMA operational functions. Option for single top latching only eliminates
the need for bottom strikes. Electromechanical options include solenoid activated
trim and inside and outside lever monitoring.
i. Acceptable Manufacturers:
1. Sargent Manufacturing (SA) - 7000 Series.
c. Cylindrical Locksets, Grade 1 (Extra-Heavy Duty): ANSI 156.2 Series 4000,
Grade 1 certified cylindrical (bored) locksets able to withstand 3000 inch pounds
of torque applied to the locked lever without gaining access. Locksets to fit a
standard 2 1/8” bore without the use of through- bolts. Lever handles to be made
of solid material with no plastic fillers and latchbolt head to be one-piece
stainless steel construction encased within the lock body. Furnish with
standard 2 3/4” backset, 1/2" throw latchbolt (3/4" at rated paired openings), and
universal non-handed.
i. Acceptable Manufacturers:
1. Sargent Manufacturing (SA) – 11 Line.
2. Only when replacing existing Cylindrical locks and not replacing
door.
DOOR HARDWARE
08 7100– 15
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
d. Lock Trim Design: LNL, LNJ [LNG or TEG by approval only, if approved no
attic stock required], [WTL by approval only, if approved no attic stock required] .
all other trim must be approved by the owner and provide 20% additional product
in attic stock.
e. Knurling: Where specified provide knurling or abrasive coating to all levers on
doors leading to hazardous areas such as mechanical rooms, boiler and furnace
rooms, janitor closets, and as otherwise required by the Illinois Accessibility
Code.
15. ELECTROMECHANICAL LOCKING DEVICES
a. Electromechanical Mortise Locksets, Grade 1 (Heavy Duty): Subject to same
compliance standards and requirements as mechanical mortise locksets,
electrified locksets to be of type and design as specified below.
i. Electrified Lock Options: Where indicated in the Hardware Sets,
provide electrified options including: outside door lock/unlock trim control,
latchbolt and lock/unlock status monitoring, and request-to-exit signaling.
Unless otherwise indicated, provide electrified locksets standard as fail
secure.
ii. Acceptable Manufacturers:
1. Sargent Manufacturing (SA) - 8200 Series.
16. INTEGRATED WIEGAND OUTPUT ACCESS CONTROL LOCKING DEVICES
a. Integrated Wiegand Output Mortise Locks: Wiegand output ANSI A156.13, Grade
1, mortise lockset with integrated iClass® elite card reader, request-to-exit
signaling, door position status switch, and latchbolt monitoring in one complete
unit. Hard wired, solenoid driven locking/unlocking control of the lever handle
trim, 3/4" deadlocking anti-friction latch, and 1" case-hardened steel deadbolt.
Lock is U.L listed and labeled for use on up to 3 hour fire rated openings. Keyed
high security cylinder override.
i. Open architecture, hard wired platform supports centralized control of
locking units with new or existing Wiegand compatible access control
systems. Latchbolt monitoring and door position switch act in conjunction
to report door-in-frame (DPS) and door latched (door closed and latched)
conditions.
ii. Reader supports 13.56 MHz (2K-32K) iClass® elite credentials.
iii. 24VDC operation with iClass® elite reader. Fail safe or fail secure
options.
iv. Installation requires only one cable run from the lock to the access
control panel without requirements for additional proprietary lock panel
interface boards or modules.
DOOR HARDWARE
08 7100– 16
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
v. Installation to include manufacturer's access control panel interface
board or module where required for Wiegand output protocol.
vi. Acceptable Manufacturers:
1. Sargent Manufacturing (SA) - Harmony - H2 8200 Series.or
university approved equal
17. AUXILIARY LOCKS
a. Mortise Deadlocks, Small Case: ANSI/BHMA A156.5, Grade 1, certified small
case mortise type deadlocks constructed of heavy gauge wrought corrosion
resistant steel. Steel or stainless steel bolts with a 1" throw and hardened steel
roller pins. Deadlocks to be products of the same source manufacturer and
keyway as other specified locksets.
i. Acceptable Manufacturers:
1. Sargent Manufacturing (SA) - 4870 Series.
b. Push-Pull Latches, Ligature Resistant, Mortise: ANSI/BHMA A156.13,
Series 1000, Operational and Security Grade 1 mortise type push-pull locks and
latches with ligature- resistant paddle trim capable of being mounted in vertical
(up or down) and horizontal (sideways) positions. Locksets to be manufactured
with a corrosion resistant, formed steel case and be non-handed, field-reversible
for re-handing without disassembly of the lock body. Paddles and covers are
manufactured from cast stainless steel or brass material. Provide optional leadlining (lock body) and Torx® fasteners as specified in Hardware Sets.
i. Acceptable Manufacturers:
1. Sargent Manufacturing (SA) - 8200 ALP Series.
18. LOCK AND LATCH STRIKES
a. Strikes: Provide manufacturer's standard strike with strike box for each latch or
lock bolt, with curved lip extended to protect frame, finished to match door
hardware set, unless otherwise indicated, and as follows:
i. Flat-Lip Strikes: For locks with three-piece antifriction latchbolts, as
recommended by manufacturer.
ii. Extra-Long-Lip Strikes: For locks used on frames with applied wood
casing trim.
iii. Aluminum-Frame Strike Box: Provide manufacturer's special strike box
fabricated for aluminum framing.
b. Standards: Comply with the following:
i. Strikes for Mortise Locks and Latches: BHMA A156.13.
DOOR HARDWARE
08 7100– 17
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
ii. Strikes for Bored Locks and Latches: BHMA A156.2.
iii. Strikes for Auxiliary Deadlocks: BHMA A156.5.
iv. Dustproof Strikes: BHMA A156.16.
19. ELECTROMAGNETIC LOCKING DEVICES
a. Surface Electromagnetic Locks (Heavy Duty): Electromagnetic locks to be
surface mounted type conforming to ANSI A156.23, Grade 1 with minimum
holding force strength of 1,200 pounds. Locks to be capable of either 12 or 24
voltage and be UL listed for use on fire rated door assemblies. Electronics are
to be fully sealed against tampering and allow exterior weatherproof applications.
As indicated in Hardware Sets, provide specified mounting brackets and
housings. Power supply to be by the same manufacturer as the lock with
combined products having a lifetime replacement warranty.
i. Acceptable Manufacturers:
ii. Security Door Controls (SD) – EMLock 1500 Series.
iii. Securitron Door Controls (SU) – M62 Series.
20. ELECTRIC STRIKES
a. Standard Electric Strikes: Heavy duty, cylindrical and mortise lock electric
strikes conforming to ANSI/BHMA A156.31, Grade 1, UL listed for both Burglary
Resistance and for use on fire rated door assemblies. Stainless steel
construction with dual interlocking plunger design tested to exceed 3000 lbs. of
static strength and 350 ft-lbs. of dynamic strength. Strikes tested for a minimum 1
million operating cycles. Provide strikes with 12 or 24 VDC capability and
supplied standard as fail-secure unless otherwise specified. Option available for
latchbolt and latchbolt strike monitoring indicating both the position of the
latchbolt and locked condition of the strike.
i. Acceptable Manufacturers:
1. Folger Adam EDC (FO) - 700 Series
2. HES (HE) - 1006 Series.
b. Surface Mounted Rim Electric Strikes: Surface mounted rim exit device electric
strikes conforming to ANSI/BHMA A156.31, Grade 1, and UL Listed for both
Burglary Resistance and for use on fire rated door assemblies. Construction
includes internally mounted solenoid with two heavy-duty, stainless steel locking
mechanisms operating independently to provide tamper resistance. Strikes
tested for a minimum of 500,000 operating cycles. Provide strikes with 12 or
24 VDC capability supplied standard as fail-secure unless otherwise
specified. Option available for latchbolt and latchbolt strike monitoring indicating
both the position of the latchbolt and locked condition of the strike. Strike
requires no cutting to the jamb prior to installation.
DOOR HARDWARE
08 7100– 18
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
i. Acceptable Manufacturers:
1. HES (HE) - 9500/9600 Series.
2. Folger Adam (FO)
c. Provide electric strikes with in-line power controller and surge suppressor by the
same manufacturer as the strike with combined products having unlimited lifetime
warranty.
21. CONVENTIONAL EXIT DEVICES
a. General Requirements: All exit devices specified herein shall meet or exceed
the following criteria:
i. At doors not requiring a fire rating, provide devices complying with NFPA
101 and listed and labeled for "Panic Hardware" according to UL305.
Provide proper fasteners as required by manufacturer including sex nuts
and bolts at openings specified in the Hardware Sets.
ii. Where exit devices are required on fire rated doors, provide devices
complying with NFPA 80 and with UL labeling indicating "Fire Exit
Hardware". Provide devices with the proper fasteners for installation as
tested and listed by UL. Consult manufacturer’s catalog and template
book for specific requirements.
1. Fire Exit Removable Mullions: Provide keyed removable mullions
for use with fire exit devices complying with NFPA 80 that are
listed and labeled by a testing and inspecting agency acceptable
to authorities having jurisdiction, for fire and panic protection,
based on testing according to UL 305 and NFPA 252. Mullions
to be used only with exit devices for which they have been tested.
iii. Except on fire rated doors, provide exit devices with hex key dogging
device to hold the pushbar and latch in a retracted position. Provide
optional keyed cylinder dogging on devices where specified in Hardware
Sets.
iv. Flush End Caps: Provide heavy weight impact resistant flush end caps
made of architectural metal in the same finish as the devices as in the
Hardware Sets. Plastic end caps will not be acceptable. Prefix on all exit
devices should be 43-.
v. Lever Operating Trim: Where exit devices require lever trim, furnish
manufacturer's heavy duty trim with cold forged escutcheons, beveled
edges, and four threaded studs for thru-bolts.
1. Lock Trim Design: As indicated in Hardware Sets, provide
finishes and designs to match that of the specified locksets.
Provided free-wheeling type trim where indicated.
DOOR HARDWARE
08 7100– 19
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
2. Where function of exit device requires a cylinder, provide an
interchangeable core type keyed cylinder (Rim or Mortise) as
specified in Hardware Sets.
vi. Vertical Rod Exit Devices: Provide and install interior surface and
concealed vertical rod exit devices as Less Bottom Rod (LBR) unless
otherwise indicated.
vii. Narrow Stile Applications: At doors constructed with narrow stiles, or
as specified in Hardware Sets, provide devices designed for maximum 2”
wide stiles.
viii. Dummy Push Bar: Nonfunctioning push bar matching functional push bar.
ix. Rail Sizing: Provide exit device rails factory sized for proper door width
application.
x. Through Bolt Installation: For exit devices and trim as indicated in Door
Hardware Sets.
b. Conventional Push Rail Exit Devices (Heavy Duty): ANSI/BHMA A156.3,
Grade 1 certified panic and fire exit hardware devices furnished in the functions
specified in the Hardware Sets. Mounting rails to be formed from smooth
stainless steel, brass or bronze architectural materials no less than 0.072" thick,
with push rails a minimum of 0.062" thickness. Painted or aluminum metal rails
are not acceptable. Exit device latch to be investment cast stainless steel,
pullman type, with deadlock feature.
i. Acceptable Manufacturers:
1. Sargent Manufacturing (SA) - 80 Series.
c. Extruded Aluminum Removable Mullions: ANSI/BHMA A156.3 anodized,
removable mullions with malleable-iron top and bottom retainers. Mullions to be
provided standard with stabilizers and imbedded weatherstrip.
i. Acceptable Manufacturers:
1. Sargent Manufacturing (SA) - 650A Series, or Northwestern
University approved equal..
d. Tube Steel Removable Mullions: ANSI/BHMA A156.3 removable steel mullions
with malleable-iron top and bottom retainers and a primed paint finish. Provide
keyed removable feature, stabilizers, and mounting brackets as specified in the
Hardware Sets. At openings designed for severe wind load conditions due to
hurricanes or tornadoes, provide manufacturers approved mullion and
accessories to meet applicable state and local windstorm codes.
i. Acceptable Manufacturers:
DOOR HARDWARE
08 7100– 20
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
1. Sargent Manufacturing (SA) - 980S Series, or Northwestern
University approved equal..
22. ELECTROMECHANICAL CONVENTIONAL EXIT DEVICES
a. Electrified Conventional Push Rail Devices (Heavy Duty): Subject to same
compliance standards and requirements as mechanical exit devices, electrified
devices to be of type and design as specified below.
i. Acceptable Manufacturers:
1. Sargent Manufacturing (SA) - 80 Series.
b. Electrified Options: As indicated in hardware sets, provide electrified exit device
options including: electric latch retraction, electric dogging, outside door trim
control, exit alarm, delayed egress, latchbolt monitoring, lock/unlock status
monitoring, touchbar monitoring and request-to-exit signaling. Unless otherwise
indicated, provide electrified exit devices standard as fail secure.
c. Electrified Tube Steel Removable Mullions: ANSI/BHMA A156.3 removable
steel mullions with malleable-iron top and bottom retainers and a primed paint
finish. Provide keyed removable feature, electrical quick connect wiring,
stabilizers, and mounting brackets as specified in the Hardware Sets.
i. Acceptable Manufacturers:
1. Sargent Manufacturing (SA) - EL980S Series.
d. Hurricane and Tornado Resistance Compliance: Electromechanical
conventional exit devices and electrified tube steel removable mullions to be
U.L. listed for windstorm components where applicable. Provide the appropriate
hurricane or tornado resistant products that have been independent third party
tested, certified, and labeled to meet state and local windstorm building codes
applicable to project.
23. INTEGRATED WIEGAND OUTPUT ACCESS CONTROL EXIT DEVICES
a. Wiegand Output Integrated Card Reader Exit Hardware: Wiegand output ANSI
156.3 Grade 1 rim, mortise, and vertical rod exit device hardware with integrated
proximity card reader, latchbolt and touchbar monitoring, and request-to-exit
signaling, in one complete unit. Hard wired, solenoid driven locking/unlocking
control of the lever handle exit trim with 3/4" throw latch bolt. U.L listed and
labeled for either panic or "fire exit hardware" for use on up to 3 hour fire rated
openings. Available with or without keyed high security cylinder override.
i. Open architecture, hard wired platform supports centralized control of
locking units with new or existing Wiegand compatible access control
systems. Inside push bar (request-to- exit) signaling and door position
(open/closed status) monitoring (via separately connected DPS).
ii. Reader supports 13.56 MHz (2K-32K) iClass® elite credentials.
DOOR HARDWARE
08 7100– 21
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
iii. 24VDC operation available with iClass® elite reader. 24VDC required for
solenoid operated exit trim. Fail safe or fail secure options.
iv. Installation requires only one cable run from the exit hardware to the
access control panel without requirements for additional proprietary lock
panel interface boards or modules.
v. <Competitor Alternates Allowed Option>Installation to include
manufacturer's access control panel interface board or module where
required for Wiegand output protocol.
vi. Acceptable Manufacturers:
1. Sargent Manufacturing (SA) - Harmony - H2 80 Series, or
Northwestern University approved equal.
24. DOOR CLOSERS
a. Door closers specified herein shall meet or exceed the following criteria:
i. General: Door closers to be from one manufacturer, matching in design
and style, with the same type door preparations and templates
regardless of application or spring size. Closers to be non-handed with
full sized covers including installation and adjusting information on inside
of cover.
ii. Standards: Closers to comply with UL-10C and UBC 7-2 for Positive
Pressure Fire Test and be U.L. listed for use of fire rated doors.
iii. Size of Units: Comply with manufacturer's written recommendations for
sizing of door closers depending on size of door, exposure to weather,
and anticipated frequency of use. Where closers are indicated for doors
required to be accessible to the physically handicapped, provide units
complying with ANSI ICC/A117.1 provisions for door opening force and
delayed action closing.
iv. Closer Arms: Provide heavy duty, forged steel closer arms unless
otherwise indicated in Hardware Sets.
1. Where closers are indicated to have mechanical dead-stop,
provide heavy duty arms and brackets with an integral positive
stop.
2. Where closers are indicated to have mechanical hold open,
provide heavy duty units with an additional built-in mechanical
holder assembly designed to hold open against normal wind and
traffic conditions. Holder to be manually selectable to on-off
position.
DOOR HARDWARE
08 7100– 22
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
3. Where closers are indicated to have a cushion-type stop, provide
heavy duty arms and brackets with spring stop mechanism to
cushion door when opened tomaximum degree.
v. Closer Accessories: Provide door closer accessories including custom
templates, special mounting brackets, spacers and drop plates, and
through-bolt or security type fasteners as specified in the door Hardware
Sets.
vi. Hurricane and Tornado Resistance Compliance: Door closers to be U.L.
listed for windstorm components where applicable. Provide the
appropriate hurricane or tornadoresistant products that have been
independent third party tested, certified, and labeled to meet state and
local windstorm building codes applicable to project.
b. Door Closers, Surface Mounted (Large Body Cast Iron): ANSI/BHMA A156.4,
Grade 1 surface mounted, heavy duty door closers with complete spring power
adjustment, sizes 1 thru 6; and fully operational adjustable according to door
size, frequency of use, and opening force. Closers to be rack and pinion type,
one piece cast iron body construction, with adjustable backcheck and separate
non-critical valves for closing sweep and latch speed control. Provide high
impact, non-corrosive plastic covers standard.
i. Acceptable Manufacturers:
1. LCN Closers (LC) - 4041XP Series x TBWMS screw pack for all
closers.
c. Door Closers, Surface mounted (Standard Duty): ANSI/BHMA 156.4 certified
Grade 1 standard duty door closers with closers with complete spring power
adjustment, sizes 1 thru 6. Closers to have fully concealed body in the frame
head and track assembly in the door, rack and pinion type construction, either
offset or center hung applications, with separate and independent valves for
closing speed, latch speed, and backcheck adjustments. Overhead concealed
closers require a minimum 4-inch frame head for mounting.
i. Acceptable Manufacturers:
1. LCN Closers (LC) - 1461 Series x TBWMS screw pack for all
closers.
d. Door Closers, Overhead Concealed (Heavy Duty): ANSI/BHMA 156.4 certified
Grade 1 heavy duty door closers with closers with complete spring power
adjustment, sizes 1 thru 6. Closers to have fully concealed body in the frame
head and track assembly in the door, rack and pinion type construction, either
offset or center hung applications, with separate and independent valves for
closing speed, latch speed, and backcheck adjustments. Overhead concealed
closers require a minimum 4-inch frame head for mounting.
i. Acceptable Manufacturers:
DOOR HARDWARE
08 7100– 23
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
1. LCN Closers (LC) - 2010 Series.
25. AUTOMATIC DOOR OPERATORS
a. General: Provide operators of size recommended by manufacturer for door
size, weight, and movement; for condition of exposure; and for compliance
with UL 325. Coordinate operator mechanisms with door operation, hinges, and
activation devices.
i. Fire-Rated Doors: Provide door operators for fire-rated door assemblies
that comply with NFPA 80 for fire-rated door components and are listed
and labeled by a qualified testing agency.
b. Electromechanical Door Operators: Self-contained units powered by
permanent magnet DC motor, with closing speed controlled mechanically by
gear train, connections for power, activation and safety device wiring, and
manual operation including spring closing when power is off.
c. Electrohydraulic Door Operators: Self-contained low-pressure units with
separate cylinders for power and checking, connections for power, activation,
and safety device wiring and manual operation including spring closing when
power is off.
d. Brackets and Reinforcements: Manufacturer's standard, fabricated from
aluminum with nonferrous shims for aligning system components.
e. Standard: Certified ANSI/BHMA A156.19.
i. Performance Requirements:
1. Opening Force if Power Fails: Not more than 15 lbf required to
release a latch if provided, not more than 30 lbf required to
manually set door in motion, and not more than 15 lbf required to
fully open door.
2. Entrapment Protection: Not more than 15 lbf required to
prevent stopped door from closing or opening.
f.
Configuration: Surface mounted. Door operators to control single swinging and
pair of swinging doors.
g. Operation: Power opening and spring closing operation capable of meeting
ANSI A117.1 accessibility guideline. Provide time delay for door to remain
open before initiating closing cycle as required by ANSI/BHMA A156.19.
When not in automatic mode, door operator to function as manual door closer
with fully adjustable opening and closing forces, with or without electrical power.
i. On-off switch to control power to be key switch operated.
h. Features: Operator units to have full feature adjustments for door opening and
closing force and speed, backcheck, motor assist acceleration from 0 to 30
DOOR HARDWARE
08 7100– 24
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
seconds, time delay, vestibule interface delay, obstruction recycle, and hold open
time from 0 up to 30 seconds.
i.
Provide outputs and relays on board the operator to allow for coordination of
exit device latch retraction, electric strikes, magnetic locks, card readers, safety
and motion sensors and specified auxiliary contacts.
j.
Activation Devices: Provide activation devices in accordance with ANSI/BHMA
A156.19 standard, for condition of exposure indicated and for long term,
maintenance free operation under normal traffic load operation. Coordinate
activation control with electrified hardware and access control interfaces.
Activation switches are standard SPST, with optional DPDT availability.
k. Signage: As required by cited ANSI/BHMA A156.19 standard for the type of
operator.
l.
Acceptable Manufacturers:
i. LCN Closers (LC) - 4640 Series x TBWMS screw pack for all closers
26. SURFACE MOUNTED CLOSER HOLDERS
a. Single Point Closer Holders: Single point closer holder designed to hold open
fire or smoke rated doors until interruption of signal from fire alarm, smoke
detector or remote release switch. Pull side, push side, or double egress
mounting applications available with non-handed track and closer body and
dual voltage input (24V/120V). Voltage to be 24VDC unless otherwise specified.
Pull side mounted closers to have minimum adjustable hold-open range of 85 to
110 degrees. Auxiliary door stops are required at hold open point.
i. Acceptable Manufacturers:
1. LCN Door Closers (LC) - 4040SE Series x TBWMS screw pack for
all closers.
b. Electromagnetic Door Holders: Certified ANSI A156.15 electromagnetic door
holder/releases with a minimum 20 to 40 pounds holding power and single coil
construction able to accommodate.12VDC, 24VAC, 24VDC and 120VAC. Coils
to be independently wound, employing an integral fuse and armatures to include
a positive release button.
i. Acceptable Manufacturers:
1. Rixson (RF) - 980/990 Series.
2. Sargent Manufacturing (SA) - 1560 Series.
c. Electrified Holders: Electrified door holders are designed to provide single point
hold open for fire and smoke labeled doors and must be used in conjunction
with a opposite side mounted U.L. listed door closer. Single track arm is nonhanded with detector or non-detector option.
DOOR HARDWARE
08 7100– 25
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
i. Acceptable Manufacturers:
1. Rixson (RF) - Checkmate 99 Series.
27. ARCHITECTURAL TRIM
a. Door Protective Trim
i. General: Door protective trim units to be of type and design as specified
below or in the Hardware Sets.
ii. Size: Fabricate protection plates (kick, armor, or mop) not more than 2"
less than door width (LDW) on stop side and not more than 1" less than
door width on pull side. Coordinate and provide proper width and height
as required where conflicting hardware dictates. Height to be as specified
in the Hardware Sets.
iii. Metal Protection Plates: ANSI/BHMA A156.6 certified metal protection
plates (kick, armor, or mop), beveled on four edges (B4E), fabricated
from the following.
1. Stainless Steel: 050-inch thick, with countersunk screw holes
(CSK).
2. Brass or Bronze: 050-inch thick, with countersunk screw holes
(CSK).
3. Laminate Plastic or Acrylic: 1/8-inch thick, with countersunk screw
holes (CSK).
iv. Fasteners: Provide manufacturer's designated fastener type as specified
in the Hardware Sets.
v. Metal Door Edging: Door protection edging fabricated from a minimum
.050-inch thick metal sheet, formed into an angle or "U" cap shapes,
surface or mortised mounted onto edge of door. Provide appropriate leg
overlap to account for protection plates as required. Height to be as
specified in the Hardware Sets.
vi. Acceptable Manufacturers:
1. McKinney Architectural Hardware (MK).
2. Rockwood Manufacturing (RO).
28. DOOR STOPS AND HOLDERS
a. General: Door stops and holders to be of type and design as specified below or
in the Hardware Sets.
DOOR HARDWARE
08 7100– 26
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
b. Door Stops and Bumpers: ANSI/BHMA A156.16, Grade 1 certified door stops
and wall bumpers. Provide wall bumpers, either convex or concave types with
anchorage as indicated, unless floor or other types of door stops are specified
in Hardware Sets. Do not mount floor stops where they will impede traffic.
Where floor or wall bumpers are not appropriate, provide overhead type stops
and holders.
i. Acceptable Manufacturers:
1. McKinney Architectural Hardware (MK).
2. Rockwood Manufacturing (RO).
3. Trimco (TC).
c. Overhead Door Stops and Holders: ANSI/BHMA A156.6, Grade 1 certified
overhead stops and holders to be surface or concealed types as indicated in
Hardware Sets. Track, slide, arm and jamb bracket to be constructed of extruded
bronze and shock absorber spring of heavy tempered steel. Provide non-handed
design with mounting brackets as required for proper operation and function.
i. Acceptable Manufacturers:
ii. Rixson Door Controls (RF).
iii. Sargent Manufacturing (SA).
29. ARCHITECTURAL SEALS
a. General: Thresholds, weatherstripping, and gasket seals to be of type and
design as specified below or in the Hardware Sets. Provide continuous
weatherstrip gasketing on exterior doors and provide smoke, light, or sound
gasketing on interior doors where indicated. At exterior applications provide noncorrosive fasteners and elsewhere where indicated.
b. Smoke Labeled Gasketing: Assemblies complying with NFPA 105 that are listed
and labeled by a testing and inspecting agency acceptable to authorities having
jurisdiction, for smoke control ratings indicated, based on testing according to UL
1784.
i. Provide smoke labeled perimeter gasketing at all smoke labeled
openings.
c. Fire Labeled Gasketing: :Assemblies complying with NFPA 80 that are listed
and labeled by a testing and inspecting agency acceptable to authorities having
jurisdiction, for fire ratings indicated, based on testing according to UL-10C.
i. Provide intumescent seals as indicated to meet UL10C Standard for
Positive Pressure Fire Tests of Door Assemblies, and UBC 7-2, Fire
Tests of Door Assemblies.
DOOR HARDWARE
08 7100– 27
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
d. Sound-Rated Gasketing: Assemblies that are listed and labeled by a testing
and inspecting agency, for sound ratings indicated, based on testing according to
ASTM E 1408.
e. Replaceable Seal Strips: Provide only those units where resilient or flexible seal
strips are easily replaceable and readily available from stocks maintained by
manufacturer.
i. Acceptable Manufacturers:
1. McKinney Weatherstripping Products (MW).
2. Pemko Manufacturing (PE).
3. Zero International (ZE).
30. ELECTRONIC ACCESSORIES
a. Key Switches: Key switches furnished standard with stainless steel single gang
face plate with a 12/24VDC bi-color LED indicator. Integral backing bracket
permits integration with any 1 1/4" or 1 1/2" mortise type cylinder. Key switches
available as momentary or maintained action and in narrow face plate options.
i. Acceptable Manufacturers:
1. Security Door Controls (SD) - 800 Series.
2. Securitron Door Controls (SU) - MK Series.
b. Push-Button Switches: Industrial grade momentary or alternate contact, backlighted push buttons with stainless-steel switch enclosures. 12/24 VDC bicolor illumination suitable for either flush or surface mounting.
i. Acceptable Manufacturers:
1. Security Door Controls (SD) - 400 Series.
2. Securitron Door Controls (SU) - PB Series.
c. Request-to-Exit Motion Sensor: Request-to-Exit Sensors motion detectors
specifically designed for detecting exiting through a door from the secure area to
a non-secure area. Include built-in timers (up to 60 second adjustable timing),
door monitor with sounder alert, internal vertical pointability coverage, 12VDC
or 24VDC power and selectable relay trigger with fail safe/fail secure modes.
i. Acceptable Manufacturers:
1. Security Door Controls (SD) - MD-31D Series.
2. Securitron Door Controls (SU) - XMS Series.
DOOR HARDWARE
08 7100– 28
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
d. Door Position Switches: Door position magnetic reed contact switches
specifically designed for use in commercial door applications. On recessed
models the contact and magnetic housing snap-lock into a 1" diameter hole.
Surface mounted models include wide gap distance design complete with
armored flex cabling. Provide SPDT, N/O switches with optional Rare Earth
Magnet installation on steel doors with flush top channels.
i. Acceptable Manufacturers:
1. Security Door Controls (SD) - DPS Series.
2. Securitron Door Controls (SU) - DPS Series.
e. Wiegand Test Unit: Test unit verifies proper Wiegand output integrated card
reader lock installation in the field by testing for proper wiring, card reader data
integrity, and lock functionality including lock/unlock, door position, and requestto-exit status. 12 or 24VDC voltage adjustable operating as Fail Safe or Fail
Secure.
i. Acceptable Manufacturers:
ii. Sargent Manufacturing (SA) - WT1 Wiegand Test Unit.
f.
Power Supplies: Provide Nationally Recognized Testing Laboratory Listed
12VDC or 24VDC (field selectable) filtered and regulated power supplies. Include
battery backup option with integral battery charging capability in addition to
operating the DC load in event of line voltage failure. Provide the least number of
units, at the appropriate amperage level, sufficient to exceed the required total
draw for the specified electrified hardware and access control equipment.
i. Acceptable Manufacturers:
1. Security Door Controls (SD) - 630 Series.
2. Securitron Door Controls (SU) - BPS 12/24 Series.
31. FABRICATION
a. Fasteners: Provide door hardware manufactured to comply with published
templates generally prepared for machine, wood, and sheet metal screws.
Provide screws according to manufacturers recognized installation standards
for application intended.
32. FINISHES
a. Standard: Designations used in the Hardware Sets and elsewhere indicate
hardware finishes complying with ANSI/BHMA A156.18, including coordination
with traditional U.S. finishes indicated by certain manufacturers for their products.
b. Provide quality of finish, including thickness of plating or coating (if any),
composition, hardness, and other qualities complying with manufacturer's
DOOR HARDWARE
08 7100– 29
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
standards, but in no case less than specified by referenced standards for the
applicable units of hardware.
c. Protect mechanical finishes on exposed surfaces from damage by applying a
strippable, temporary protective covering before shipping.
d. Antimicrobial Finishes: Where specified, finishes on locksets, latchsets, exit
devices and push/pull trim to incorporate an FDA recognized. Silver Ion,
antimicrobial coating (MicroShield™) listed for use on equipment as a
suppressant to the growth and spread of a broad range of bacteria, algae,
fungus, mold and mildew.
33. EXAMINATION
a. Examine scheduled openings, with Installer present, for compliance with
requirements for installation tolerances, labeled fire door assembly construction,
wall and floor construction, and other conditions affecting performance.
b. Notify architect of any discrepancies or conflicts between the door schedule, door
types, drawings and scheduled hardware. Proceed only after such discrepancies
or conflicts have been resolved in writing.
34. PREPARATION
a. Hollow Metal Doors and Frames: Comply with ANSI/DHI A115 series. B. Wood
Doors: Comply with ANSI/DHI A115-W series.
35. INSTALLATION
a. Install each item of mechanical and electromechanical hardware and access
control equipment to comply with manufacturer's written instructions and
according to specifications.
i. Installers are to be trained and certified by the manufacturer on the proper
installation and adjustment of fire, life safety, and security products
including: hanging devices; locking devices; closing devices; and seals.
b. Mounting Heights: Mount door hardware units at heights indicated in
following applicable publications, unless specifically indicated or required to
comply with governing regulations:
i. Standard Steel Doors and Frames: DHI's "Recommended Locations
for Architectural Hardware for Standard Steel Doors and Frames."
ii. Wood Doors: DHI WDHS.3, "Recommended Locations for Architectural
Hardware for Wood Flush Doors."
iii. Where indicated to comply with accessibility requirements, comply with
ANSI A117.1 "Accessibility Guidelines for Buildings and Facilities."
DOOR HARDWARE
08 7100– 30
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
iv. Provide blocking in drywall partitions where wall stops or other wall
mounted hardware is located.
c. Retrofitting: Install door hardware to comply with manufacturer's published
templates and written instructions. Where cutting and fitting are required to install
door hardware onto or into surfaces that are later to be painted or finished in
another way, coordinate removal, storage, and reinstallation of surface protective
trim units with finishing work specified in Division 9 Sections. Do not install
surface-mounted items until finishes have been completed on substrates
involved.
d. Thresholds: Set thresholds for exterior and acoustical doors in full bed of
sealant complying with requirements specified in Division 7 Section "Joint
Sealants."
e. Storage: Provide a secure lock up for hardware delivered to the project but
not yet installed. Control the handling and installation of hardware items so that
the completion of the work will not be delayed by hardware losses before and
after installation.
36. FIELD QUALITY CONTROL
a. Field Inspection: Supplier will perform a final inspection of installed door
hardware and state in report whether work complies with or deviates from
requirements, including whether door hardware is properly installed, operating
and adjusted.
37. ADJUSTING
a. Initial Adjustment: Adjust and check each operating item of door hardware and
each door to ensure proper operation or function of every unit. Replace units
that cannot be adjusted to operate as intended. Adjust door control devices to
compensate for final operation of heating and ventilating equipment and to
comply with referenced accessibility requirements.
38. CLEANING AND PROTECTION
a. Protect all hardware stored on construction site in a covered and dry place.
Protect exposed hardware installed on doors during the construction phase.
Install any and all hardware at the latest possible time frame.
b. Clean adjacent surfaces soiled by door hardware installation.
c. Clean operating items as necessary to restore proper finish. and provide final
protection and maintain conditions that ensure door hardware is without damage
or deterioration at time of owner occupancy.
39. DEMONSTRATION
a. Instruct Owner's maintenance personnel to adjust, operate, and maintain
mechanical and electromechanical door hardware.
DOOR HARDWARE
08 7100– 31
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
40. DOOR HARDWARE SCHEDULE
a. The hardware sets represent the design intent and direction of the owner and
architect. They are a guideline only and should not be considered a detailed
hardware schedule. Discrepancies, conflicting hardware and missing items
should be brought to the attention of the architect with corrections made prior to
the bidding process. Omitted items not included in a hardware set should be
scheduled with the appropriate additional hardware required for proper
application and functionality.
Hardware Set 1 – Typical Out Swing Classroom Door
Qty.
Item
Description / Model No.
Finish
Man.
3
Hinges
TA2714 4 ½ X 4 ½ NRP
652
MC
1
Lockset
LC 8216 LNL
630
SA
1
Mortise Cylinder
As Required
626
ME
3
Door Silencers
S1M
1
Door Stop
480
626
RO
1
Kick Plate
KP50 10" x 2" LDW x B4E x CSK
630
MC
MC
Hardware Set 2 – Typical Out Swing Classroom Door – Fire Rated
Qty.
Item
Description / Model No.
Finish
Man.
3
Hinges
TA2714 4 ½ X 4 ½ NRP
652
MC
1
Lockset
LC 8216 LNL
630
SA
1
Mortise Cylinder
As Required
626
ME
1
Closer
4041 TBWM REG/PA
689
LC
3
Door Silencers
S1M
1
Door Stop
480
626
RO
1
Kick Plate
KP50 10" x 2" LDW x B4E x CSK
630
MC
MC
DOOR HARDWARE
08 7100– 32
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
Hardware Set 3 – Typical In-Swing Classroom Door
Qty.
Item
Description / Model No.
Finish
Man.
3
Hinges
TA2714 4 1/2 X 4 1/2
652
MC
1
Lockset
LC 8216 LNL
630
SA
1
Mortise Cylinder
As Required
626
ME
3
Door Silencers
S1M
1
Door Stop
480
626
RO
1
Kick Plate
KP50 10" x 2" LDW x B4E x CSK
630
MC
MC
Hardware Set 4 – Typical In-Swing Classroom Door – Fire Rated
Qty.
Item
Description / Model No.
Finish
Man.
3
Hinges
TA2714 4 1/2 X 4 1/2
652
MC
1
Lockset
LC 8216 LNL
630
SA
1
Mortise Cylinder
As Required
626
ME
1
Closer
4041 TBWM REG/PA
689
LC
3
Door Silencers
S1M
1
Door Stop
480
626
RO
1
Kick Plate
KP50 10" x 2" LDW x B4E x CSK
630
MC
MC
Hardware Set 5 – Typical Office In-swing Office – Fire Rated.
Qty.
Item
Description / Model No.
Finish
Man.
3
Hinges
TA2714 4 ½ X 4 ½
652
MC
1
Lockset
LC 8255 LNL
630
SA
1
Mortise Cylinder
As Required
626
ME
1
Closer
4041 TBWM REG/PA
689
LC
1
Door Stop
480
626
RO
1
Gasketing
S88 C
PE
3
Door Silencers
S1M
MC
DOOR HARDWARE
08 7100– 33
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
Hardware Set 6 – Typical Office Out Swing – Fire Rated.
Qty.
Item
Description / Model No.
Finish
Man.
3
Hinges
TA2714 4 ½ X 4 ½ NRP
652
MC
1
Lockset
LC 8255 LNL
630
SA
1
Mortise Cylinder
As Required
626
ME
1
Closer
4041 TBWM REG/PA
689
LC
1
Door Stop
480
626
RO
1
Gasketing
S88 C
PE
3
Door Silencers
S1M
MC
Hardware Set 7 – Typical Office Out Swing – Non Rated.
Qty.
Item
Description / Model No.
Finish
Man.
3
Hinges
TA2714 4 ½ X 4 ½ NRP
652
MC
1
Lockset
LC 8255 LNL
630
SA
1
Mortise Cylinder
As Required
626
ME
3
Door Silencers
S1M
1
Door Stop
480
MC
626
RO
Hardware Set 8 – Typical Office Suite Entry Out Swing - Rated
Qty.
Item
Description / Model No.
Finish
Man.
3
Hinges
TA2714 4 ½ X 4 ½ NRP
652
MC
1
Lockset
LC 8216 LNL
630
SA
2
Mortise Cylinder
As Required
626
ME
1
Closer
4041 TBWM REG/PA
689
LC
1
Door Stop
480
626
RO
3
Door Silencers
S1M
MC
Hardware Set 9 – Typical Office Suite Entry – Non Rated
Qty.
Item
Description / Model No.
Finish
Man.
3
Hinges
TA2714 4 ½ X 4 ½ NRP
652
MC
1
Lockset
LC 8216 LNL
630
SA
2
Mortise Cylinder
As Required
626
ME
3
Door Silencers
S1M
1
Door Stop
480
MC
626
RO
DOOR HARDWARE
08 7100– 34
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
Hardware Set 10 – Typical Privacy In Swing– Rated.
Qty.
Item
Description / Model No.
Finish
Man.
3
Hinges
TA2714 4 1/2 X 4 1/2
652
MC
1
Privacy Set
49 8265 LNL
626
SA
1
Closer
4041 TBWM REG/PA
689
LC
1
Wall Stop
WS03
626
MC
1
Gasketing
S88 C
PE
3
Door Silencers
S1M
MC
Hardware Set 11 – Typical Privacy – Non Rated.
Qty.
Item
Description / Model No.
Finish
Man.
3
Hinges
TA2714 4 1/2 X 4 1/2
652
MC
1
Privacy Set
49 8265 LNL
626
SA
3
Door Silencers
S1M
1
Wall Stop
WS03
MC
626
MC
Hardware Set 12 – Typical Multi-User Toilet Room- Out Swing
Qty.
Item
Description / Model No.
Finish
Man.
3
Hinges
TA2714 4 1/2 X 4 1/2
652
MC
1
Push Plate
P055 CTC
630
MC
1
Door Pull
DP08
630
MC
1
Deadbolt
4878
630
SA
1
Mortise Cylinder
As Required
626
ME
1
Closer
4041 E TBWM REG/PA
689
LC
1
Door Stop
480
626
RO
1
Kick Plate
KP50 10" x 2" LDW x B4E x CSK
630
MC
1
Mop Plate
KP50 4” x 1” LDW x B4E x CSK
630
MC
3
Door Silencers
S1M
MC
DOOR HARDWARE
08 7100– 35
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
Hardware Set 13 – Typical Multi-User Toilet Room- In Swing.
Qty.
Item
Description / Model No.
Finish
Man.
3
Hinges
TA2714 4 1/2 X 4 1/2
652
MC
1
Push Plate
P055 CTC
630
MC
1
Door Pull
DP08
630
MC
1
Deadbolt
4878
630
SA
1
Mortise Cylinder
As Required
626
ME
1
Closer
4041 TBWM REG/PA
689
LC
1
Door Stop
480
626
RO
1
Kick Plate
KP50 10" x 2" LDW x B4E x CSK
630
MC
1
Mop Plate
KP50 4” x 1” LDW x B4E x CSK
630
MC
3
Door Silencers
S1M
MC
Hardware Set 14 – Typical Janitor Closet – Out Swing
Qty.
Item
Description / Model No.
Finish
Man.
3
Hinges
TA2714 4 1/2 X 4 1/2 NRP
652
MC
1
Lockset
LC 8204 LNL
630
SA
1
Mortise Cylinder
As Required
626
ME
1
Closer
4041 SC TBWM
689
LC
1
Kick Plate
KP50 10" x 2" LDW x B4E x CSK
630
MC
3
Door Silencers
S1M
MC
Hardware Set 15 – Typical Storage Room Hazardous Area– Out Swing
Qty.
Item
Description / Model No.
Finish
Man.
3
Hinges
TA2714 4 1/2 X 4 1/2 NRP
652
MC
1
Lockset
76 LC 8204 LNL
630
SA
1
Mortise Cylinder
As Required
626
ME
1
Closer
4041 SC TBWM
689
LC
1
Kick Plate
KP50 10" x 2" LDW x B4E x CSK
630
MC
3
Door Silencers
S1M
MC
DOOR HARDWARE
08 7100– 36
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
Hardware Set 16 – Typical Stair Door
Qty.
Item
Description / Model No.
Finish
Man.
3
Hinges
TA2714 4 1/2 X 4 1/2 NRP
26D
MC
1
Exit Device
16 43 LC 8813 F ETL
32D
SA
1
Mortise Cylinder
As Required
626
ME
1
Rim Cylinder
As Required
626
ME
1
Closer
4041 TBWM REG/PA
AL
LC
1
Wall Stop
WS03
US26D
MC
1
Protection Plate
K1050 10" x 2" LDW x B4E x CSK
US32D
RO
3
Door Silencers
S1M
MC
Hardware Set 17 – Typical Cross Corridor Pair – Held Open
Qty.
Item
Description / Model No.
Finish
Man.
6
Hinges
TA2714 4 1/2 X 4 1/2 NRP
652
MC
1
Exit Device
12 43 LC 8713 F ETL
630
SA
1
Exit Device
12 43 LC 8710 F ETL-DT
630
SA
1
Rim Cylinder
As Required
626
ME
2
Mortise Cylinder
As Required
626
ME
2
Closer
4041 TBWM REG/PA
689
LC
2
Magnetic Holder
990 Series
689
RX
1
Kick Plate
KP50 10" x 1" LDW x B4E x CSK
630
MC
2
Meeting Stile Set
18041 CNB
PE
2
Gasket Set
S88 C
PE
Hardware Set 18 – Typical Passage – Non Rated
Qty.
Item
Description / Model No.
Finish
Man.
3
Hinges
TA2714 4 1/2 X 4 1/2
652
MC
1
Passage Set
8215 LNL
626
SA
3
Door Silencers
S1M
1
Wall Stop
WS03
MC
626
MC
DOOR HARDWARE
08 7100– 37
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
Hardware Set 19 – Typical Passage In Swing– Rated
Qty.
Item
Description / Model No.
Finish
Man.
3
Hinges
TA2714 4 1/2 X 4 1/2
652
MC
1
Privacy Set
8215 LNL
626
SA
1
Closer
4041 TBWM REG/PA
689
LC
1
Wall Stop
WS03
626
MC
3
Door Silencers
S1M
MC
Hardware Set 20 – Typical Mechanical Room – Out Swing
Qty.
Item
Description / Model No.
Finish
Man.
3
Hinges
TA2714 4 1/2 X 4 1/2 NRP
652
MC
1
Lockset
86 LC 8204 LNL
630
SA
1
Mortise Cylinder
As Required
626
ME
1
Closer
4041 SC TBWM
689
LC
1
Kick Plate
KP50 10" x 2" LDW x B4E x CSK
630
MC
3
Door Silencers
S1M
MC
Hardware Set 21 – Typical Out Swing Laboratory Door
Qty.
Item
Description / Model No.
Finish
Man.
3
Hinges
TA2714 4 ½ X 4 ½ NRP
652
MC
1
Lockset
LC 8216 LNL
630
SA
1
Mortise Cylinder
As Required
626
ME
3
Door Silencers
S1M
1
Door Stop
480
626
RO
1
Kick Plate
KP50 10" x 2" LDW x B4E x CSK
630
MC
MC
DOOR HARDWARE
08 7100– 38
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
Hardware Set 22 – Typical Out Swing Laboratory Door – Fire Rated
Qty.
Item
Description / Model No.
Finish
Man.
3
Hinges
TA2714 4 ½ X 4 ½ NRP
652
MC
1
Lockset
LC 8216 LNL
630
SA
1
Mortise Cylinder
As Required
626
ME
1
Closer
4041 TBWM REG/PA
689
LC
3
Door Silencers
S1M
1
Door Stop
480
626
RO
1
Kick Plate
KP50 10" x 2" LDW x B4E x CSK
630
MC
MC
Hardware Set 23 – Typical In-Swing Laboratory Door
Qty.
Item
Description / Model No.
Finish
Man.
3
Hinges
TA2714 4 1/2 X 4 1/2
652
MC
1
Lockset
LC 8216 LNL
630
SA
1
Mortise Cylinder
As Required
626
ME
3
Door Silencers
S1M
1
Door Stop
480
626
RO
1
Kick Plate
KP50 10" x 2" LDW x B4E x CSK
630
MC
MC
Hardware Set 24 – Typical In-Swing Laboratory Door – Fire Rated
Qty.
Item
Description / Model No.
Finish
Man.
3
Hinges
TA2714 4 1/2 X 4 1/2
652
MC
1
Lockset
LC 8216 LNL
630
SA
1
Mortise Cylinder
As Required
626
ME
1
Closer
4041 TBWM REG/PA
689
LC
3
Door Silencers
S1M
1
Door Stop
480
626
RO
1
Kick Plate
KP50 10" x 2" LDW x B4E x CSK
630
MC
MC
DOOR HARDWARE
08 7100– 39
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
Hardware Set 25 – Typical Out Swing Electronic Access Door
Qty.
Item
Description / Model No.
Finish
Man.
2
Hinges
TA2714 4 ½ X 4 ½ NRP
652
MC
1
Hinges
TA2714 4 ½ X 4 ½ QC6
652
MC
1
Lockset
LC 8270/71 LNL
630
SA
1
Mortise Cylinder
As Required
626
ME
3
Door Silencers
S1M
1
Door Stop
480
626
RO
1
Kick Plate
KP50 10" x 2" LDW x B4E x CSK
630
MC
MC
Hardware Set 26 – Typical Out Swing Electronic Access Door – Fire Rated
Qty.
Item
Description / Model No.
Finish
Man.
2
Hinges
TA2714 4 ½ X 4 ½ NRP
652
MC
1
Hinges
TA2714 4 ½ X 4 ½ QC6
652
MC
1
Lockset
LC 8270/71 LNL
630
SA
1
Mortise Cylinder
As Required
626
ME
1
Closer
4041 TBWM REG/PA
689
LC
3
Door Silencers
S1M
1
Door Stop
480
626
RO
1
Kick Plate
KP50 10" x 2" LDW x B4E x CSK
630
MC
MC
Hardware Set 27 – Typical In-Swing Electronic Access Door
Qty.
Item
Description / Model No.
Finish
Man.
2
Hinges
TA2714 4 1/2 X 4 1/2
652
MC
1
Hinges
TA2714 4 1/2 X 4 1/2 QC6
652
MC
1
Lockset
LC 8270/71 LNL
630
SA
1
Mortise Cylinder
As Required
626
ME
3
Door Silencers
S1M
1
Door Stop
480
626
RO
1
Kick Plate
KP50 10" x 2" LDW x B4E x CSK
630
MC
MC
DOOR HARDWARE
08 7100– 40
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
Hardware Set 28 – Typical In-Swing Electronic Access Door – Fire Rated
Qty.
Item
Description / Model No.
Finish
Man.
2
Hinges
TA2714 4 1/2 X 4 1/2
652
MC
1
Hinges
TA2714 4 1/2 X 4 1/2 QC6
652
MC
1
Lockset
LC 8270/71 LNL
630
SA
1
Mortise Cylinder
As Required
626
ME
1
Closer
4041 TBWM REG/PA
689
LC
3
Door Silencers
S1M
1
Door Stop
480
626
RO
1
Kick Plate
KP50 10" x 2" LDW x B4E x CSK
630
MC
MC
END OF SECTION
DOOR HARDWARE
08 7100– 41
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
This page intentionally left blank
DOOR HARDWARE
08 7100– 42
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
DIVISION 8 – OPENINGS
SECTION 08 8000 - GLAZING
1. General: This section outlines the requirements for interior and exterior glazing.
2. Design Criteria:
a. Design to withstand wind loading as specified by applicable code for
parts/portions of buildings.
b. Statistical probability of breakage: 8 per 1000, maximum, at 60-second wind
load.
c. Low-E glass is preferred at exterior locations.
d. Provide requirements for certification by Contractor, installer, glass fabricator,
and/or manufacturer that glass thickness and heat treatment have been selected
to provide the strength required to meet specified structural performance
requirements.
3. Warranty: Review project specific requirements with NU Project Manager during the
design phase.
4. Insulated Glass Units (IGU):
a. Sealed insulating units.
b. Total Thickness: 1 inch, nominal.
c. Review options for low-e coatings, frit patterns, and insulating glass unit
construction with the NU Project Manager during the design phase.
5. Closeout Documents – Glazing Schedule: Architect/Engineer shall require that the
Contractor provide, at completion of the project, a schedule listing size, type, location,
and installation method of all installed glass.
END OF SECTION
GLAZING
08 8000– 1
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
This page intentionally left blank
GLAZING
08 8000– 2
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
DIVISION 8 – OPENINGS
SECTION 08 9200 – GLAZED ALUMINUM CURTAIN WALL SYSTEM
1. General: This section outlines the requirements for glazed aluminum curtain wall
systems for exterior applications:
2. Quality Assurance: Architect shall review the following Contractor Required Quality
Assurance and Field Quality Control Testing requirements with the NU Project Manager
during the design phase of the project.
a. Engineering Design: Structural engineering shall be performed by a professional
engineer licensed in the State of Illinois and employed by the system
manufacturer.
b. Mock-up Testing: The following testing is mandatory unless manufacturer can
submit acceptable reports of previously performed tests on products equivalent to
those to be provided. For standard, stock products, tests performed on the same
product for other projects will be accepted.
c. Perform the following tests on a full-size mock-up in the order indicated:
i. Verify air infiltration resistance by testing in accordance with ASTM E 283;
report result as cubic feet per minute per unit of measurement indicated, at
pressure differential indicated.
ii. Verify water penetration resistance by testing in accordance with ASTM E
331 and AAMA 501.1; report result at pressure differential indicated.
iii. Perform the following tests on mock-up of the size specified by the test
method:
1. Verify thermal transmittance by testing in accordance with AAMA
1503.1; report result as U-value (Btu per hour per square foot per
degree F).
2. Verify condensation resistance by testing in accordance with AAMA
1503.1; report result as CRF.
iv. Test mock-up(s) in laboratory of testing agency or in manufacturer's plant
under supervision of testing agency.
v. Fabricate mock-up(s) from materials matching those proposed for use,
using personnel who will perform field installation.
vi. Furnish shop drawing of mock-up to testing agency.
vii. Provide reports certified by the testing agency.
viii. Do not use materials from test mock-up on project.
GLAZED ALUMINUM CURTAIN WALL SYSTEM
08 9200– 1
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
d. Testing Laboratory Qualifications:
i. Independent testing agency
ii. Firm having experience in the testing specified and having the capability to
do the testing specified within the time frame required by the contractor, as
shown by information supplied as required by ASTM E 699
iii. Firm approved by the University
e. Mock-up: Provide field-constructed mock-ups to serve as the standard of quality
for appearance and workmanship to be expected in the completed work.
i. Construct mock-ups of each system, at least 2 stories high by 2 bays wide.
ii. Locate mock-ups where indicated on drawings.
iii. Maintain mock-ups in good condition during construction.
iv. Demolish mock-ups when directed, and remove from site.
3. Field Quality Control:
a. Perform field testing of installed wall for water penetration resistance.
i. Perform testing before covering up of inside face of wall assembly.
ii. Perform AAMA 501.3 ("static") test on the first area of wall to be completed;
at least 2 bays wide by 2 stories high.
b. Repair deficiencies discovered by testing and modify installation procedures before
installing remainder of wall, to prevent these deficiencies.
c. Perform AAMA 501.2 ("hose") test on at least 2 additional areas of a similar size at
higher levels.
i. Repair deficiencies discovered by testing, including similar conditions in
areas not tested.
4. Continue to test an additional area and make repairs on entire installation until an area not
previously tested tests without deficiencies.
END OF SECTION
GLAZED ALUMINUM CURTAIN WALL SYSTEM
08 9200– 2
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
DIVISION 9 – FINISHES
SECTION 09 2900 – GYPSUM BOARD
1. General: This section outlines the requirements for gypsum board systems.
2. Design Considerations:
a. Acoustically Rated Walls: Partitions or assemblies with an STC of 45 or higher.
b. Inspection of Acoustic Insulation and Sealants:
i. Prior to installing drywall on the second side of acoustically rated
partitions, Architect/Engineer and/or Northwestern University shall be
given the opportunity to confirm proper installation of acoustic products.
3. Cementitious Backer Board: Provide one of the following
a. Durock Cement Board by USG.
b. Wonderboard.
4. Field Constructed Mock-Ups:
a. Review requirements for mock-ups with the NU Project Manager.
b. Prior to installation of drywall systems, erect sample walls to indicate the
construction of the following partitions types to confirm details for vapor barrier
and acoustically rated partitions.
END OF SECTION
GYPSUM BOARD
09 2900 – 1
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
This page intentionally left blank
GYPSUM BOARD
09 2900 – 2
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
DIVISION 9 – FINISHES
SECTION 09 3000 – TILE
1. General: This section outlines the requirements for tile:
2. Design Considerations:
a. Tile Finishes: Review materials, colors, and finishes with NU Project Manager
during the design phase.
b. Tile Grouts: Avoid light colored grouts on floors and other horizontal surfaces.
END OF SECTION
TILE
09 3000 – 1
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
This page intentionally left blank
TILE
09 3000 – 2
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
DIVISION 9 – FINISHES
SECTION 09 6500 – RESILIENT FLOORING
1. General: This section outlines the requirements for resilient flooring.
2. Design Considerations:
a. Finishes: Review materials, colors, and finishes with NU Project Manager during
the design phase.
b. Accessories:
i. Wall Base: Minimum 6-inch height is recommended.
c. Architect shall review the following Contractor requirements with the NU Project
Manager and include in the Construction Documents:
i. Initial Cleaning and Sealing: Dry-mop, removing all dust and debris.
Clean surface with a neutral cleaner using green pad and floor machine.
Clean with a fine abrasive where necessary to remove any stains or
cement smears. Clean edges, baseboards, door jambs, and corners
using a Doodle Bug pad and holder with a green pad. Pick up all
solutions using a wet/dry vacuum. Thoroughly rinse twice with clear
water.
ii. Sealing: Where required, apply two coats of water-based sealer and 3
coats of water-based finish using a fine strand rayon mop. Allow a
minimum of 45 minutes between coats. All prior coats shall be dry to the
touch before any subsequent coats are applied. Apply first coat of sealer
and first coat of finish wall to wall. Stop subsequent coats of sealer and
finish 1” from baseboards, door jambs, and other vertical edges.
iii. Protection: Cover floor surface, and protect from soiling, staining,
marring, scratching, and other damage. Construction traffic, including foot
traffic, is strictly prohibited on completed surface. Maintain protection until
final completion unless floor is put into service at time of substantial
completion.
1. Exceptions: Do not seal static dissipative flooring. Provide visible
integral “DO NOT WAX” label in static dissipative flooring tiles.
END OF SECTION
RESILIENT FLOORING
09 6500 – 1
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
This page intentionally left blank
RESILIENT FLOORING
09 6500 – 2
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
DIVISION 9 – FINISHES
SECTION 09 6600 – TERRAZZO FLOORING
1. General: This section outlines the requirements for terrazzo flooring:
2. Design Considerations:
a. Materials and Finishes: Review materials, colors, and finishes with NU Project
Manager during the design phase.
b. Architect shall review the following contractor requirements with the NU Project
Manager and include in the Construction Documents:
i. Initial Cleaning and Sealing: Dry-mop, removing all dust and debris.
Clean surface with a neutral cleaner using green pad and floor machine.
Clean with a fine abrasive where necessary to remove any stains or
cement smears. Clean edges, baseboards, door jambs, and corners
using a Doodle Bug pad and holder with a green pad. Pick up all
solutions using a wet/dry vacuum. Thoroughly rinse twice with clear
water.
ii. Sealing: Apply two coats of water-based sealer and 3 coats of waterbased finish using a fine strand rayon mop. Allow a minimum of 45
minutes between coats. All prior coats shall be dry to the touch before
any subsequent coats are applied. Apply first coat of sealer and first coat
of finish wall to wall. Stop subsequent coats of sealer and finish 1” from
baseboards, door jambs, and other vertical edges.
iii. Protection: Cover terrazzo surface, and protect from soiling, staining,
marring, scratching, and other damage. Construction traffic, including
foot traffic, is strictly prohibited on completed surface. Maintain protection
until final completion unless terrazzo is put into service at time of
substantial completion.
END OF SECTION
TERRAZZO
09 6600 – 1
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
This page intentionally left blank
TERRAZZO
09 6600 – 2
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
DIVISION 9 – FINISHES
SECTION 09 6800 – CARPET
1. General: This section outlines the requirements for carpet.
2. Design Considerations:
a. Finishes: Review materials, colors, and patterns with NU Project Manager during
the design phase.
3. Materials:
a. Glue-Down Installation:
i. Construction: Woven, Unitary, Enhancer/Cushion back.
ii. Yarn: Dupont Antron Nylon or equivalent.
iii. Yarn Weight: 28 oz. minimum.
iv. Yarn color: Yarn dyed.
v. Stitching: 8.0 per inch minimum.
vi. Primary backing: Polypropylene or equivalent.
vii. Secondary backing: Interlocked with face yarn or unitary.
viii. Flammability: Class 1 Radiant Panel Test ASTM E-648.
ix. Smoke Density: 450 or less in a flaming mode ASTM E-622.
x. Static Propensity: Less than 3.5 KVA ATCC -134
xi. Warranty minimum: 10 yr. wear and edge ravel, 15 yr. tuft bind
b. Tackless Installation:
i. Construction: Woven, Tufted with double back unitary, (i.e. sur_lock,
duralock, unibond)
ii. Yarn: Dupont Antron Nylon or equivalent.
iii. Yarn Weight: 28 oz. minimum.
iv. Yarn color: Yarn dyed.
v. Stitching: 8.0 per inch minimum.
vi. Primary backing: Polypropylene or equivalent.
CARPET
09 6800 – 1
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
vii. Secondary backing: : Polypropylene or equivalent.
viii. Flammability: Class 1 Radiant Panel Test ASTM E-648.
ix. Smoke Density: 450 or less in a flaming mode ASTM E-622.
x. Static Propensity: Less than 3.5 KVA ATCC -134
xi. Warranty minimum: 10 yr. wear and edge ravel/no zipper, 15 yr. tuft bind
c. Provide 38 oz. minimum yarn weight at steps and classroom risers with rubber
nosings.
d. Elevators: Review special fire retardant code requirements for elevators.
e. Require manufacturer to certify, in writing, that product is appropriate for the
intended use.
2. Installation:
a. Perform installation in accordance with manufacturer's instructions, except where
more stringent requirements are shown or specified, and except where project
conditions require extra precautions or provisions to ensure satisfactory
performance of the work.
b. Seams: Using carpet manufacturer's recommended procedures, form secure
seams capable of sustaining expected stresses without failure for the life of the
installation.
a. Provide samples and seaming diagrams for all areas before proceeding with
carpet installation.
END OF SECTION
CARPET
09 6800 – 2
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
DIVISION 9 – FINISHES
SECTION 099 000 – PAINTING
1. General: This section outlines the requirements for interior and exterior painting.
2. Design Considerations:
a. Colors: Northwestern has standardized the following Benjamin Moore white
paint colors on campus. The intent is to provide a range of standard white colors
that architects can specify.
i. Decorators White
ii. Bone White
iii. White Dove
iv. China White
v. Linen White
vi. Super White for ceilings and soffits.
3. Submittals: Provide for each coating system, color, and texture; apply to representative
substrate samples. Prepare samples to show bare, prepared surface and each
successive coat. Label each sample with coating name manufacturer type and color,
name and/or number.
4. Manufacturer: Top line products of Benjamin Moore & Company. Pratt & Lambert may
be used for wood finishing products.
a. Colors: For multi-coat systems, apply each coat using a successively darker tint
or shade, unless approved otherwise.
b. Top coat colors: As indicated in color schedule.
5. Prime Coats:
a. Thinned top coats are not permitted as primers.
b. Field apply bottom coats scheduled except where the contract documents require
shop coating of ferrous metals. Ferrous metals that have not been shop primed
shall be field primed promptly after arrival at the site or shall be stored away from
the effects of weather. Repair and retouch damaged prime coats using
approved, compatible primer.
c. Primers for Wood and Wood Products: Apply first coat to wood upon receipt at
the site and before wood is exposed to sun or rain.
PAINING
09 9000 – 1
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
6. Schedule of Coatings for Interior Non-Traffic Surfaces:
a. Gypsum Wallboard & Plaster: Latex, eggshell on walls, flat on ceilings.
b. Concrete Masonry Units - Filled Finish: As scheduled, Latex, satin or Tile-like
epoxy, low gloss.
c. Concrete and Masonry: As scheduled, Latex, satin or Tile-like epoxy, low gloss.
d. Wood: As scheduled, Latex, satin. Varnish, satin (stained wood).
e. Ferrous Metal: Latex, satin, low gloss.
f.
Galvanized Metal: Latex, gloss.
g. In extraordinary cases, such as very high use doors or windows, or in
laboratories, oil base or epoxy may be necessary. Request University approval
prior to specifying.
7. Schedule of Coatings for Interior Traffic Surfaces:
a. Concrete: Epoxy floor enamel.
b. Wood: As scheduled, Alkyd/urethane floor enamel, gloss. Varnish, gloss (stained
wood).
8. Schedule of Coatings for Exterior Surfaces:
a. Concrete Masonry Units - Filled Finish: Latex.
b. Ferrous Metal: Latex, gloss.
c. Galvanized Metal: Latex, gloss.
9. Project Closeout:
a. Schedule of Installed Coatings: At the completion of the project, Architect shall
require that Contractor provide a complete listing of all coatings. Include
manufacturer, product name, primer and top coats, number of coats, application
methods and a detailed diagram of colors by location.
END OF SECTION
PAINING
09 9000 – 2
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
DIVISION 10 – SPECIALTIES
SECTION 10 1100 – VISUAL DISPLAY SURFACES
1. General: This section outlines the requirements for visual display surfaces.
2. Design Considerations: Review project specific requirements including size, location,
and types of visual display surfaces with the NU Project Manager during the design
phases of the project.
3. Basis of Design Manufacturers:
a. Marker Boards: Provide Claridge Co. LCS writing surface.
END OF SECTION
VISUAL DISPLAY SURFACES
10 1100 – 1
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
This page intentionally left blank
VISUAL DISPLAY SURFACES
10 1100 – 2
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
DIVISION 10 – SPECIALTIES
SECTION 10 2113 – TOILET COMPARTMENTS
1. General:
a. This section outlines the requirements for toilet compartments.
b. NU preference is solid plastic, recycled, high-density polyethylene (HDPE) floor
mounted, overhead braced (floor to ceiling) units. Ceiling hung units are not
preferred.
i. Basis of Design Manufacturer: Santana Solid Plastic Products.
c. Other products are acceptable pending review with NU Project Manager.
2. Materials:
a. General: Materials shall be scratch and graffiti resistant.
b. Steel Sheets for Baked Enamel Finish: ASTM A 591, Class C, galvanized
bonderized, of following minimum thickness.
i. Pilasters (overhead braced): 20 gauge.
ii. Pilasters (unbraced): 16 gauge.
iii. Panels and Screens: 20 gauge.
iv. Doors: 22 gauge.
c. Core Material for Metal Partitions: Manufacturer's standard sound deadening
honey comb of impregnated Kraft paper, in thickness to provide finished
dimension of 1" minimum for doors, panels, and screens, 1 1/4" minimum for
pilasters.
d. Pilaster Shoes: ASTM A 167, Type 302/304 stainless steel, not less than 3"
high, 20 gauge, finished to match hardware.
e. Hardware:
i. Hinges: Provide continuous self-closing hinges.
ii. Material: Stainless steel.
3. Fabrication:
a. General: Provide floor mounted, overhead braced units. Furnish standard
doors, panels, screens, and pilasters fabricated for partition system, unless
otherwise indicated. Furnish units with cutouts, drilled holes, and internal
TOILET COMPARTMENTS
10 2113 – 1
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
reinforcement to receive partition mounted hardware, accessories, and grab
bars, as indicated. Furnish continuous, full-height bracket at rear walls.
b. Door Dimensions: Unless otherwise indicated, furnish 24" wide in-swinging
doors for ordinary toilet stalls and 32" wide (clear opening) out-swinging doors at
stalls equipped for use by handicapped.
c. Metal Toilet Partitions: Pressure laminate seamless face sheets to core material
and seal edges with continuous interlocking strip or with lapped and formed
edges. Weld edges and corners, with exposed welds ground smooth.
a. Finishes: Baked Enamel Finish: Clean galvanized steel surfaces after fabrication
and before application of enamel coating system, to remove processing
compounds, oils, and other contaminants. Prime metal with baked on rust
inhibitive primer. Apply two coats of thermosetting enamel finish, applied by
electrostatic process, and baked in accordance with paint manufacturer's
instructions.
END OF SECTION
TOILET COMPARTMENTS
10 2113 – 2
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
DIVISION 10 – SPECIALTIES
SECTION 10 2226 - OPERABLE PARTITIONS
1. General: This section outlines the requirements for toilet compartments.
2. Design Considerations:
a. When operable partitions are required, provide STC 52 or higher.
b. Review project specific requirements with the NU Project Manager during the
design phase of the project.
END OF SECTION
OPERABLE PARTITIONS
10 2226 – 1
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
This page intentionally left blank
OPERABLE PARTITIONS
10 2226 – 2
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
DIVISION 10 – SPECIALTIES
SECTION 10 2800 – TOILET AND BATH ACCESSORIES
1. General: This section outlines the requirements for toilet compartments.
2. Design Considerations: Architect shall review project requirements for toilet and bath
accessories with the NU Project Manager during the design phases.
3. Products:
a. Typically, the standard paper towel dispensers, soap dispensers, toilet paper
dispensers, and feminine napkin dispensers are provided by Northwestern for
installation by the Contractor.
b. Typically, the grab bars, mirrors, feminine napkin disposals, and other
accessories shall be furnished and installed by the Contractor.
c. Review project requirements and coordinate electrical requirements for any
electrical accessories.
END OF SECTION
TOILET AND BATH ACCESSORIES
10 2800 – 1
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
This page intentionally left blank
TOILET AND BATH ACCESSORIES
10 2800 – 2
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
DIVISION 11 – EQUIPMENT
SECTION 11 5213 – PROJECTION SCREENS
1. General: This section outlines the requirements for projection screens that are provided
as part of the project.
2. Design Considerations:
a. Projection screens, both manual and motorized, shall typically be provided as
part of the base bid scope of work and not part of the furnishings, fixtures and
equipment (FF&E).
b. Architect/Engineer shall review options with the NU Project Manager during the
design phase of the project and coordinate power and/or data requirements.
3. Quality Assurance: Obtain each type of projection screen required from a single
manufacturer as a complete unit, including necessary mounting hardware and
accessories.
4. Projection Screen Surfaces, General: Obtain screens manufactured from mildew and
flame resistant fabric of type indicated for each type of screen specified and complying
with the following requirements:
a. Normally provide matte white viewing surface with minimum gain characteristics
complying with FS GG S 00172D (1) for Type A screen surface.
b. For larger rooms provide glass beaded viewing surface with minimum gain
characteristics complying with FS GG S 00172D (1) for Type C screen surface.
5. Electrically Operated Front Projection Screens: Single Station Control: Three position,
UL listed control switch for each screen with metal device box and cover plate for flush
wall mounting and for connection to 120 V a/c. power supply.
a. Motor Operated Screens with Automatic Closure: Units designed and fabricated
for recessed installation in ceiling with bottom of case composed of two panels
fully enclosing screen and wiring compartments, one panel hinged and activated
by operation of screen to open and close automatically when screen is lowered
and fully raised and the other panel removable or operable for access to interior
of case.
b. Offset mount bottom panels to case in position where their bottom surfaces will
align flush with finished surface of adjoining ceiling and the bottom edges of case
surrounding panels will be recessed by the depth of, and concealed behind,
overlapping ceiling finish.
6. Manually Operated Front Projection Screens: Provide case, screen, mounting
accessories and other components as required for a complete installation and complying
with descriptive requirements indicated below.
PROJECTION SCREENS
11 5213 – 1
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
a. Spring Roller Operated Projection Screens: Units designed and fabricated for
wall or ceiling installation and complying with the following requirements:
b. Screen Case: Fabricated in one piece from not less than 22 gage steel with flat
back design, vinyl covered or baked enamel finish, and end caps with integral
roller brackets and furnished with universal mounting brackets in finish matching
end caps to enable attachment to wall or ceiling.
END OF SECTION
PROJECTION SCREENS
11 5213 – 2
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
DIVISION 12 – FURNISHINGS
SECTION 12 2000 – WINDOW TREATMENTS
1. General: This section outlines the requirements for window screens that are provided as
part of the project.
2. Design Considerations:
a. Window treatments shall typically be provided as part of the base bid scope of
work and not part of the furnishings, fixtures and equipment (FF&E).
b. Architect/Engineer shall review options with NU Project Manager during the
design phase of the project and coordinate power requirements for motorized
shades.
3. Horizontal Blinds:
a. General: Head rail and blinds shall conform to shape of window. Bottom rail,
tubular steel, designed to withstand twisting or sagging. Contour top surface to
match slat curvature, with flat or slightly curved bottom. Close ends with metal or
plastic end caps of same color as rail. Finish rail in same color as slats.
b. Slats: Spring tempered aluminum (louver blades), rounded corners with forming
burrs removed.
c. Tilting Mechanism: Assembly including disengaging worm and gear mechanism
to eliminate overdrive, low friction gear tilter, drum and cradle at each ladder, tilt
rod, tape clips, and grommet guides to prevent wear on ladder and cords;
designed to hold slats at any angle and prevent movement of slats due to
vibration, operated as follows:
d. Wand Operator: Detachable clear plastic wand, of proper length to suit blind
installation, detachable without tools by raising locking sleeve.
e. Lifting Mechanism: Crash-proof cord locks with cord separators and braided
polyester or nylon lift cords with tassels at ends. Size cord to suit blind type.
Include self-aligning cord equalizers designed to maintain horizontal blind
position.
f.
Installation Brackets: Designed to facilitate removal of head channels. Design
brackets to support safely the weight of blind assemblies plus forces applied to
operate blinds.
END OF SECTION
WINDOW TREATMENTS
12 2000– 1
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
This page intentionally left blank
WINDOW TREATMENTS
12 2000– 2
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
DIVISION 12 – FURNISHINGS
SECTION 12 4816 – ENTRANCE FLOOR GRILLES
1. General: This section outlines the requirements for entrance floor grilles.
2. Design Criteria:
a. Foot grilles and frames shall be designed to support a uniform distributed load of
at least 200 pounds per square foot.
3. Quality Assurance: Single Source Responsibility: Obtain foot grilles and frames from
one source from a single manufacturer.
4. Aluminum Foot Grilles: Provide manufacturer's standard extruded aluminum foot grille
with top surfaced tread rails. Framing members and tread rail material, aluminum finish,
tread top surface, and tread rail spacing as indicated.
a. Provide frames for foot grilles of same material as other framing members with
finish to match tread rails.
b. Aluminum: Extruded aluminum, ASTM B 221, alloy 6061 T6 for tread rails and
keylock, where used; alloy 6063 T5 or T6 for framing and connecting members.
c. Tread Rail Spacing: 1-1/2 inches on center with 1/8-inch to 3/16-inch wide
openings between treads.
d. Aluminum Finish: Natural mill finish.
e. Top Surface: Fusion bonded level cut pile nylon carpet insert; DuPont "Antron
III" filament, 1/4 inch high, 28 oz. per sq. yd.
5. Support System: Provide cushion support system.
6. Drainage Pit Applications: Provide special deep pit frame and support extrusion system
with intermediate support beams, sized and spaced as recommended by manufacturer
for indicated spans and equipped with vinyl support cushions.
a. Provide 16 gage stainless steel or 0.060 inch thick aluminum pit liner for each
entrance mat unit, with 2 inch IPS floor drain. Coat bottom of aluminum pan with
zinc chromate paint. Provide joint sealant between the concrete slab and metal
pan.
END OF SECTION
ENTRANCE FLOOR GRILLES
12 4816– 1
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
This page intentionally left blank
ENTRANCE FLOOR GRILLES
12 4816– 2
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
DIVISION 14 – CONVEYING EQUIPMENT
SECTION 14 2100 – ELECTRIC TRACTION ELEVATORS
1. General:
a. Northwestern requires a third party, independent elevator consultant for
assistance with the design and reviews related to elevators and conveying
equipment.
b. Elevators must be specified by a licensed engineer in compliance with all
applicable codes.
c. Elevator consultant to include Construction Administration during the construction
phase. Services shall include a minimum of three (3) site meetings with report or
ideally, bi-monthly site meetings throughout elevator construction.
1. Submittals:
a. Maintenance Manuals: Three (3) Bound manuals with operating and
maintenance instructions, parts listing, recommended parts inventory listing,
purchase source listing for major and critical components, emergency
instructions, and similar information.
b. Provide complete wiring diagrams to be left on-site, secured in elevator machine
room.
c. Certificates and Permits: Provide University with copies of all
inspection/acceptance certificates and operating permits as required by
governing authorities to allow normal, unrestricted use of elevator.
2. Keys:
a. Contractor to provide Northwestern with a minimum of three (3) sets of all keys at
the time of acceptance.
3. Quality Assurance:
a. Installer Qualifications: Elevator contractor must be member of Local 2 elevator
union in good standing, and has completed several successful elevator
installations similar in material, design, and extent as what is being specified for
the Project.
4. Maintenance Service:
a. Architect/Engineer shall review maintenance service agreements for existing
and/or new elevators.
b. Initial Maintenance Service: Elevator specification shall require the Contractor to
Provide full maintenance service by skilled, competent employees of the Elevator
ELECTRIC TRACTION ELEVATORS
14 2100 – 1
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
Installer for period of twelve (12) months following Date of Substantial
Completion.
i. Include monthly preventive maintenance performed during normal
working hours.
ii. Include repair or replacement of worn or defective parts or components
and lubricating, cleaning, and adjusting as required for proper elevator
operation in conformance with specified requirements.
iii. Include 24 hours per day, 7 days per week emergency callback service.
iv. Exclude only repair or replacement due to misuse, abuse, accidents, or
neglect caused by persons other than Installer's personnel.
5. Elevator Characteristics Summary:
a. Capacity Exclusive of Car: Minimum 3500 lbs.
b. Rated Speed: Per elevator consultant specification, varies with size/use..
c. Cab Inside Size: Minimum 6'-8" wide x 5'-5" deep.
d. Cab Height: Minimum 7’- 2”; preferred 8'-0", inside clear..
e. Door Operation: Minimum Single slide, left hand opening, 3'-6" wide x 7'-0" high.
f.
Power Supply: 208 volts, 3 phase, 3 wires, 60 hz, 40 H.P., AC, verify with
sources available.
g. Lighting Supply: 120 volts, 15 amps, single phase 60 hz, AC.
h. Lighting: LED.
i.
Microprocessor electronics.
j.
Controllers: Controllers shall be Galaxy (GAL), MCE, Otis and/or other nonproprietary manufacturer per review and approval by NU Project Manager.
k. Cabling: Provide additional twisted pair and coax for future security or control
use as per Project Manager. Millennium requires 5 sets twisted pair; cameras 1
coax each.
l.
Hoistway: Provide a sump pump and sump pump basin if required by applicable
codes and/or engineer/architect/project manager review.
6. Signal Equipment:
a. Telephone / Intercom: Provide rough in for “hands free” intercom in car,
contained in flush mounted cabinet. Elevator contractor to set up phone to accept
direct ring down to Northwestern University Police (NUPD). Northwestern will
ELECTRIC TRACTION ELEVATORS
14 2100 – 2
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
provide correctly activated phone jack & patch cord. If required by applicable
code, provide a fireman's telephone cabinet or fireman's telephone jack in main
elevator lobby.
b. Alarm System: Provide security system as required per all applicable codes.
c. Vandal Resistant Signal Equipment: Adams Survivor Plus:
i.
Car control stations.
ii.
Car position indicators.
iii.
Hall push button stations.
iv.
Hall lanterns.
d. Hall Lanterns must be easily visible throughout the elevator lobby, as per code.
7. Personal Protective Devices:
a. General: Provide personal protective devices as per all applicable codes and
elevator consultant.
b. Handrails: Coordinate installation of handrails with interior panels.
c. Door Edge Protective Device: Provide retractable edge shoe on leading edges
of elevator entrance doors that causes doors to stop and reopen upon contacting
an obstruction in entrance, per all applicable codes.
d. Photo Eye Detection Device: Provide electronic photo eye device with timed
cutout, projecting dual light beams across car entrance at 5 inch and 29 inch
heights, that when interrupted will cause closing doors to stop and reopen.
Provide keyed switch in car operating panel or toggle switch in service cabinet for
disconnecting photo eye protective device, per all applicable codes.
8. Passenger Hoistway Entrances:
a. Enameled Frames: Formed steel with manufacturer's standard primed-for-paint
finish.
b. Stainless Steel Frames: Formed steel with brushed finish.
c. Aluminum Sills: Extruded aluminum, with grooved surface, 1/4 inch thickness,
mill finish.
9. Passenger Cab Details:
a. General: Elevator cab to be specified to full compliance with all applicable
codes.
ELECTRIC TRACTION ELEVATORS
14 2100 – 3
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
b. Rubber flooring or terrazzo is preferred over carpet by Northwestern. Review
options for carpet and associated replacement carpet or attic stock with NU
Project Manager.
c. Ceilings must be completely accessible from the car top as per applicable codes.
d. Handrails to be removable (but tamper proof) from inside the cab.
e. Provide scratch and graffiti-proof wall panels. Review options that include
stainless steel or plastic laminate with the NU Project Manager.
f.
Provide passenger cab protection blankets for each side of elevator cab.
g. Provide blanket hooks at perimeter.
h. Provide convenience electrical outlet.
10. Field Quality Control:
a. Acceptance Testing: Elevator may not be turned over before passing
acceptance tests as required and recommended by Code and by the authority
having jurisdiction (AHJ).
b. Operating Tests: As required by the AHJ and all applicable codes.
11. Demonstration and Training:
a. Contractor shall instruct Northwestern personnel in proper use, operations, and
daily maintenance of elevators. Review emergency provisions, including
emergency access and procedures to be followed at time of failure in operation
and other building emergencies. Train University's personnel in normal
procedures to be followed in checking for sources of operational failures or
malfunctions. Confer with Northwestern on requirements for a complete elevator
maintenance program.
b. Contractor shall make a final check of each elevator operation with University's
personnel present and just prior to date of Substantial Completion. Determine
that control systems and operating devices are functioning properly. Contractor
must provide Northwestern a copy of all inspection reports and complete
paperwork to provide Northwestern the State Elevator tag before closing the
project.
c. Contractor to check that software is updated at end of 12 month warranty period
and also run diagnostics to check that no boards are failing. If needed, replace
faulty boards under warranty.
END OF SECTION
ELECTRIC TRACTION ELEVATORS
14 2100 – 4
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
DIVISION 14 – CONVEYING EQUIPMENT
SECTION 14 2400 – HYDRAULIC ELEVATORS
1. General:
a. Northwestern requires a third party, independent elevator consultant for
assistance with the design and reviews related to elevators and conveying
equipment.
b. Elevators must be specified by a licensed engineer in compliance with all
applicable codes.
c. Elevator consultant to include Construction Administration during the construction
phase. Services shall include a minimum of three (3) site meetings with report or
ideally, bi-monthly site meetings throughout elevator construction.
1. Submittals:
a. Maintenance Manuals: Three (3) Bound manuals with operating and
maintenance instructions, parts listing, recommended parts inventory listing,
purchase source listing for major and critical components, emergency
instructions, and similar information.
b. Provide complete wiring diagrams to be left on-site, secured in elevator machine
room.
c. Certificates and Permits: Provide University with copies of all
inspection/acceptance certificates and operating permits as required by
governing authorities to allow normal, unrestricted use of elevator.
2. Keys:
a. Contractor to provide Northwestern with a minimum of three (3) sets of all keys at
the time of acceptance.
3. Quality Assurance:
a. Installer Qualifications: Elevator contractor must be member of Local 2 elevator
union in good standing, and has completed several successful elevator
installations similar in material, design, and extent as what is being specified for
the Project.
4. Maintenance Service:
a. Architect/Engineer shall review maintenance service agreements for existing
and/or new elevators.
b. Initial Maintenance Service: Elevator specification shall require the Contractor to
Provide full maintenance service by skilled, competent employees of the Elevator
HYDRAULIC ELEVATORS
14 2400– 1
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
Installer for period of twelve (12) months following Date of Substantial
Completion.
i. Include monthly preventive maintenance performed during normal
working hours.
ii. Include repair or replacement of worn or defective parts or components
and lubricating, cleaning, and adjusting as required for proper elevator
operation in conformance with specified requirements.
iii. Include 24 hours per day, 7 days per week emergency callback service.
iv. Exclude only repair or replacement due to misuse, abuse, accidents, or
neglect caused by persons other than Installer's personnel.
5. Elevator Characteristics Summary:
a. Capacity Exclusive of Car: Minimum 3500 lbs.
b. Rated Speed: 125 fpm or as per elevator specification.
c. Cab Inside Size: Minimum 6'-8" wide x 5'-5" deep.
d. Cab Height: Minimum 7’-2”; preferred 8'-0", inside clear.
e. Door Operation: Single slide, left hand opening, 3'-6" wide x 7'-0" high.
f.
Power Supply: 208 volts, 3 phase, 3 wires, 60 hz, 40 H.P., AC, verify with
sources available.
g. Lighting Supply: 120 volts, 15 amps, single phase 60 hz, AC
h. Machine Location: Non- basement location preferred.
i.
Microprocessor electronics.
j.
Controllers: Controllers shall be Galaxy (GAL), MCE, Otis and/or other nonproprietary manufacturer per review and approval by NU Project Manager.
k. Cabling: Provide additional twisted pair and coax for future security or control
use as per Project Manager. Millennium requires 5 sets twisted pair; cameras 1
coax each.
l.
Hoistway: Provide a sump pump and sump pump basin if required by applicable
codes and/or engineer/architect/project manager review.
6. Signal Equipment:
a. Telephone / Intercom: Provide rough in for “hands free” intercom in car,
contained in flush mounted cabinet. Elevator contractor to set up phone to accept
direct ring down to Northwestern University Police (NUPD). Northwestern will
HYDRAULIC ELEVATORS
14 2400– 2
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
provide correctly activated phone jack & patch cord. If required by applicable
code, provide a fireman's telephone cabinet or fireman's telephone jack in main
elevator lobby.
b. Alarm System: Provide security system as required per all applicable codes.
c. Vandal Resistant Signal Equipment: Adams Survivor Plus:
i.
Car control stations.
ii.
Car position indicators.
iii.
Hall push button stations.
iv.
Hall lanterns.
d. Hall Lanterns must be easily visible throughout the elevator lobby.
7. Personal Protective Devices:
a. Handrails: Coordinate installation of handrails with interior panels.
b. Door Edge Protective Device: Provide as required per all applicable codes.
c. Photo Eye Detection Device: Provide as required per all applicable codes.
8. Passenger Hoistway Entrances:
a. Enameled Frames: Formed steel with manufacturer's standard primed-for-paint
finish.
b. Stainless Steel Frames: Formed steel with brushed finish.
c. Aluminum Sills: Extruded aluminum, with grooved surface, 1/4 inch thickness,
mill finish.
9. Passenger Cab Details:
a. General: Elevator cab to be specified to full compliance with all applicable
codes.
b. Rubber flooring or terrazzo is preferred over carpet by Northwestern. Review
options for carpet and associated replacement carpet or attic stock with NU
Project Manager.
c. Ceilings must be completely accessible from the car top as per applicable codes.
d. Handrails to be removable (but tamper proof) from inside the cab.
e. Provide scratch and graffiti-proof wall panels. Review options that include
stainless steel or plastic laminate with the NU Project Manager.
HYDRAULIC ELEVATORS
14 2400– 3
NORTHWESTERN UNIVERSITY
Technical Standards
f.
Issuance Date: 01.01.2014
Provide passenger cab protection blankets for each side of elevator cab for each
elevator. Provide blanket hooks at perimeter of each elevator.
g. Provide convenience electrical outlet in each elevator.
10. Installation of Elevator System:
a. General: Provide “holeless” hydraulic system where possible. When not
possible, provide as follows:
b. Excavation for Jack: Drill excavation in each elevator pit to accommodate
installation of plunger cylinder unit; comply with applicable requirements of
Division 2 "Excavation" section.
c. Install casings with waterproof seals at pit floor and with waterproof, high
pressure seal at bottom of casings.
d. Provide a second (inner) casing with welded waterproof, high pressure seal at
bottom and set inside outer (initial) casing.
e. Corrosion Protection: The inside of the cylinder shall be treated with rust
preventative and the outside with a suitable heavy duty service bitumastic or tape
wrap.
11. Field Quality Control:
a. Acceptance Testing: Elevator may not be turned over before passing
acceptance tests as required and recommended by Code and by the authority
having jurisdiction (AHJ).
b. Operating Tests: As required by the AHJ and all applicable codes.
12. Demonstration and Training:
a. Contractor shall instruct University personnel in proper use, operations, and daily
maintenance of elevators. Review emergency provisions, including emergency
access and procedures to be followed at time of failure in operation and other
building emergencies. Train University's personnel in normal procedures to be
followed in checking for sources of operational failures or malfunctions. Confer
with University on requirements for a complete elevator maintenance program.
b. Contractor shall make a final check of each elevator operation with University's
personnel present and just prior to date of Substantial Completion. Determine
that control systems and operating devices are functioning properly. Contractor
must provide Northwestern a copy of all inspection reports and complete
paperwork to provide Northwestern the State Elevator tag before closing the
project.
c. Contractor to check that software is updated at end of 12 month warranty period
and also run diagnostics to check that no boards are failing. If needed, replace
faulty boards under warranty.
HYDRAULIC ELEVATORS
14 2400– 4
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
d. Hydraulic Elevators are included in the University's Spill Response Plan. All new
elevators must be catalogued with the FMO Staff Engineer.
END OF SECTION
HYDRAULIC ELEVATORS
14 2400– 5
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
This page intentionally left blank
HYDRAULIC ELEVATORS
14 2400– 6
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
DIVISION 21 – FIRE SUPPRESSION
SECTION 21 0000 – GENERAL FIRE SUPPRESSION REQUIREMENTS
1. General:
a. This section outlines general requirements for fire suppression systems.
b. Section 28 3113 also contains design requirements for automatic sprinkler
systems.
2. Design Criteria:
a. NFPA Standards 13 and 14 provide the basic design guidance for automatic
sprinkler systems. Modifications and clarifications that follow must be
incorporated into the design and specifications.
i. As a minimum, each floor of a building shall be a separate automatic
sprinkler zone coordinated with the fire alarm system.
ii. Automatic sprinkler zones shall be coordinated with the smoke control
systems. In no case shall parts of one automatic sprinkler zone be
contained in more than one smoke control zone.
iii. When sprinklers are specified, provide a combined automatic sprinkler
and standpipe system.
1. On the Evanston campus pressure for hose steam requirements
in "low rise" buildings is provided by the responding fire
department. Fire pumps are to be provided where insufficient
pressure is available for automatic sprinkler demands and "high
rise" buildings. For buildings equipped with fire pumps, the pump
shall provide both hose stream and automatic sprinkler demands.
iv. The automatic sprinkler design criterion applies to wet pipe systems.
Increase the area of application in accordance with NFPA Standard 13 for
dry systems.
v. Occupancy classification definitions shall follow NFPA Standard 13. The
Room Design Method in NFPA Standard 13 shall not be used to reduce
the area of application for each classification below. However, the use of
the Special Design Methods is permitted and should be used where
applicable.
vi. On the Chicago campus, the Chicago Building Code shall be consulted
for deviations from NFPA standards.
b. The following occupancies shall be reviewed with the NU Project Manager and
the University’s Office of Risk Management to determine the sprinkler system
design basis for the following areas and vaults:
GENERAL FIRE SUPPRESSION REQUIREMENTS
21 0000 - 1
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
i. Multiple purpose areas that may be used for exhibits.
ii. Storage areas over 12 feet high.
iii. Storage for tires, rolled paper, Group A plastics, or unusual materials of
any height.
iv. Vaults for liquids, gases, or wastes.
END OF SECTION
GENERAL FIRE SUPPRESSION REQUIREMENTS
21 0000 - 2
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
DIVISION 21 – FIRE SUPPRESSION
SECTION 21 1314 – AUTOMATIC FIRE SPRINKLER SYSTEMS
1. General: This section outlines general requirements for automatic fire sprinkler systems.
2. Design Considerations:
a. Siamese connections shall be arranged to supply both the automatic sprinkler
and standpipe systems.
b. Fire pumps shall include a valved bypass city loop and a valved connection to an
outside test header. Valve arrangements shall be such that the fire pumps can
be isolated during testing with the city loop remaining in service.
c. Dry pipe systems to be utilized:
i. Areas exposed to outdoor temperatures, eg pedestrian bridges between
buildings, loading docks, etc.
ii. Areas sensitive to water, eg document storage, museums/art galleries,
etc.
d. Dry pipe valves should be provided with a dedicated tank-type air compressor.
In no case shall dry pipe valves be connected to an HVAC control air
compressor. Dedicated air compressors must be connected to the emergency
power system.
e. Drains from automatic sprinkler system equipment (dry pipe valves, flow test
valves, RPZ backflow preventers) shall be piped to a floor drain capable of
handling the expected maximum discharge for at least two minutes.
f.
Quick response automatic sprinklers are required in offices, classrooms,
hallways, assembly areas, atriums, sleeping rooms, dining rooms, and most
laboratory areas. Ordinary response heads shall be used in storage areas,
mechanical rooms, janitor closets, and areas where special coated sprinkler
heads are required. Temperature ratings shall be the maximum expected ceiling
temperature.
g. A water flow alarm shall be installed in each automatic sprinkler zone at the main
water supply entrance, and at the supply connection to each vertical combined
automatic sprinkler and standpipe riser.
h. Valve supervisory switches shall be provided for each point where the water
supply to the system or parts of the system can be shutoff. Valves grouped at a
common location can be combined into the same zone to a maximum of five. In
no case shall control valves be concealed. External tamper switches or external
wired tamper switches are required. Butterfly sectional and floor control valves
are preferred.
AUTOMATIC FIRE SPRINKLER SYSTEMS
21 1314 - 1
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
i.
Architect/Engineer of record will be required to meet with the Authority Having
Jurisdiction (AHJ) for either Chicago or Evanston Campus.
j.
Siamese connections shall be of the flush type having a polished chrome plated
finish. Lettering shall indicate dual service.
i. On the Evanston campus, provide a weatherproof visual fire alarm signal
device above the Siamese connection along with a weatherproof box for
a future audible device.
k. Sprinkler heads located in ceiling tiles should be centered in the tile unless the
head can otherwise be aesthetically located.
END OF SECTION
AUTOMATIC FIRE SPRINKLER SYSTEMS
21 1314 - 2
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
DIVISION 21 – FIRE SUPPRESSION
SECTION 21 2400 –CHEMICAL SUPPRESSION SYSTEMS
1. General: This section outlines general requirements for chemical suppression systems.
2. Design Considerations:
a. Dry chemical suppression systems are preferred except in kitchens where wet
chemical systems have typically replaced dry chemical systems. Review specific
requirements with the NU Project Manager.
b. Clean agent fire extinguishing systems shall be Halon substitutes.
c. Fire extinguishing agents shall be a clean Halon substitute or carbon dioxide.
d. Trouble and alarm signals from fire extinguishing systems shall be connected to
the building's fire alarm control panel. Where not possible, alarm and trouble
signals shall be transmitted to Northwestern’s central monitoring station.
3. Quality Assurance: The following quality assurance requirements should be reviewed
with the NU Project Manager during the design phases of the project.
a. The system and agent supplier shall have provided equipment and agent for at
least 50 systems of similar size.
b. The installation contractor shall have installed at least 12 of the supplier’s
systems and have sufficient agent on hand to recharge a system within 24 hours.
END OF SECTION
DRY CHEMICAL SUPPRESSION SYSTEM
21 2400 - 1
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
This page intentionally left blank
DRY CHEMICAL SUPPRESSION SYSTEM
21 2400 - 2
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
DIVISION 21 – FIRE SUPPRESSION
SECTION 21 2500 – SMOKE CONTROLSYSTEMS
1. General: This section outlines general requirements for smoke control systems.
2. Design Considerations:
a. Engineer of record will be required to meet with the Authority Having Jurisdiction
(AHJ) for either Chicago or Evanston Campus for Specific requirements for
smoke control requirements.
3. Definitions:
a. A dynamic smoke control system is a system that remains operational in the
event of a fire (fans ON).
b. A static system is a system that automatically shuts down (fans OFF) when
smoke is detected in the supply or return air of the HVAC system.
4. Design Guidelines:
a. To meet the Chicago and the City of Evanston codes a static system is required
as a minimum.
b. To meet the Chicago and the City of Evanston Hi Rise codes a dynamic system
is required as a minimum.
c. If a smoke control system is provided to meet code the guidelines herein must be
followed.
d. For the Chicago campus high rise buildings, a stairwell pressurization system
should be considered to enhance life safety.
e. To consider the use of a dynamic smoke control system the smoke control zone
must be sprinkled and the sprinkler and smoke zones must be the same physical
floor area.
5. System Descriptions:
a. General: All smoke control safety devices shall be hardwired into the fan safety
circuit, with auxiliary relay contacts used for notification to BAS platform.
Building Automation System (BAS) software control logic shall not be used for
fire alarm shutdown.
b. Static Systems (Fans OFF). All smoke detectors and Fire Alarm Relay Panels
(FARP) shall be furnished and installed by the fire alarm contractor. The fire
alarm relay panel shall be within 10 ft of each Building Automation System (BAS)
panel.
SMOKE CONTROLSYSTEMS
21 2500 - 1
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
i. The BMS contractor shall provide minimum 1/2 inch EMT conduit
between the BAS control panel and the Fire Alarm Relay Panel (FARP).
Confirm size of conduit with electrical requirements.
ii. Wiring from the smoke detectors to the Fire Alarm Control Panel (FACP)
and from the FACP to the fire alarm relay panels shall typically be by the
fire alarm contractor. Wiring between the BAS panels and fire alarm relay
panels shall typically be by the BAS contractor. Confirm who is
responsible for terminations in each panel and verify project specific
requirements with NU Project Manager and indicate requirements in
Construction Documents.
c. Dynamic Systems (Fans ON). Smoke detectors and Fire Alarm Relay Panels
(FARP) shall be furnished and installed by the fire alarm contractor. Fire Alarm
Relay Panels shall be located within 10 feet of the BAS panels and one for each
smoke zone. The location of the smoke zone FARPs shall be coordinated by the
BAS and fire alarm contractors. Wiring from the smoke detectors to the FACP
(Fire Alarm Control Panel) and from the FACP to the fire alarm relay panels shall
be by the fire alarm contractor.
d. The BAS contractor shall provide (1) the power source and controls for the
smoke dampers or the combination fire/smoke dampers, and (2) 1/2 in. EMT
conduit between the BAS control panels and the nearby FARP. Confirm size of
conduit with electrical requirements. Wiring between the BAS panels and fire
alarm relay panels shall be by the BAS contractor.
END OF SECTION
SMOKE CONTROLSYSTEMS
21 2500 - 2
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
DIVISION 22 – PLUMBING
SECTION 22 1118 – DOMESTIC WATER DISTRIBUTION SYSTEM
1. General: This section outlines general requirements for domestic water distribution
systems.
2. Design Considerations:
a. Potable water pipe shall be routed so that the circuit terminates at high use
areas, such as washrooms. The purpose is to avoid stagnation leading to a high
bacteria count.
b. Piping shall be routed orthogonally (no diagonal shortcuts).
c. Domestic cold water, domestic hot water supply and recirculation, laboratory cold
water, laboratory hot water and recirculation, and fill/makeup water lines shall be
copper.
d. Faucets and fixtures, such as emergency showers, eye wash, dishwashers, and
autoclaves shall have local shutoff valves within five feet of the faucet/fixture.
Valves must be accessible.
e. No piping with a fluid shall be routed over electrical busway housings. For
electrical busway housings provide a minimum 24 inches on top, both sides and
the bottom.
f.
An excellent table giving the chemical resistance of four commonly used
thermoplastic piping materials can be found in the Technical Manual published
by the Charlotte Pipe and Foundry Company, Industrial Division (800-438-6091).
g. In lab buildings, consider a redundant distribution system such as a pair of risers
cross connected at the floors.
3. Materials:
a. Steel and copper pipe shall be built and stamped to meet ASTM standards.
b. Copper Tubing:
i. Copper tubing shall be type L hard drawn.
ii. Copper tubing shall be 95-5 soldered. Solder shall be lead free.
iii. Grooved copper tubing is not permitted.
c. Galvanized pipe is not permitted.
DOMESTIC WATER DISTRIBUTION SYSTEM
22 1118 - 1
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
d. Laboratory Drain and Vent Piping:
i. General:
1. Joints shall be mechanical. Beading, fusing caulking, or welding
of joints is not acceptable.
2. Review requirements for neutralizing basins.
ii. Material: PP (polypropylene).
iii. Acceptable Manufactures for Polypropylene:
1. Enfield Industrial Corp.
END OF SECTION
DOMESTIC WATER DISTRIBUTION SYSTEM
22 1118 - 2
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
DIVISION 22 – PLUMBING
SECTION 22 2114 – PLUMBING SPECIALTIES
1. General: this section outlines general requirements for plumbing specialties.
2. Materials:
a. Ball Valves:
i. Ball valves shall be bronze, 600 psig WOG, full port, with a 316 stainless
steel ball and stem.
ii. Insulated valves shall have a 2-1/4 in. stem extension.
iii. Acceptable Manufacturers:
1. Conbraco Industries, Inc. (APOLLO)
2. Neles-Jamesbury, Inc.
3. Watts Regulator Co.
b. Gate Valves:
i. Gate valves are not permitted.
c. Backflow Preventers:
i. Backflow preventers shall be by the Watts Regulator Company, Series
909.
1. Exception: Fire Protection Systems.
d. P-Traps:
i. Trim P-traps and accessories shall be 17 gauge minimum.
END OF SECTION
PLUMBING SPECIALTIES
22 2114 - 1
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
This page intentionally left blank
PLUMBING SPECIALTIES
22 2114 - 2
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
DIVISION 22 – PLUMBING
SECTION 22 4000 – PLUMBING FIXTURES
1. General: This section outlines general requirements for plumbing fixtures.
2. Design Considerations:
a. When possible sinks, urinals and closets should match existing fixtures for
renovation projects.
b. Review project specific requirements with NU Project Manager.
3. Materials:
a. Sinks, Urinals, and Closets:
i. Acceptable Manufacturers:
1. American Standard, Inc.
2. Crane Company.
3. Eljer Plumbingware.
4. Kohler Company.
b. Faucets, Except Laboratories:
i. Electronic eye faucets are preferred in public washrooms. The
transformer shall be hard wired. Spring loaded non-electric faucets are
not acceptable.
ii. Coordinate power requirements and indicate on electrical power
drawings.
iii. Acceptable Manufacturers:
1. The Chicago Faucet Company.
2. Kohler.
3. Sloan Valve Company.
c. Laboratory Faucets and Hardware:
i. Laboratory, eyewash and shower faucets, vacuum breakers, and
appurtenances shall be furnished by The Chicago Faucet Company.
PLUMBING FIXTURES
22 4000 - 1
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
d. Urinal Flush Valves:
i. Acceptable Manufacturer:
1. Sloan Valve Company, Model 8186-1 (1.0 gpf).
e. Water Closet Flush Valves:
i. Toilet flush valves shall have a transformer and shall be hard wired with a
courtesy flush override button. Coordinate power requirements and
indicate on electrical power drawings.
1. Exception: Tank-type toilets.
ii. Acceptable Products:
1. Chicago and Evanston campus: 111ES-S (1.6 gpf)
iii. Acceptable Manufacturers:
1. Sloan Valve Company.
f.
Drinking Fountains:
i. Design Considerations:
1. Provide dual-height drinking fountains with bottle fillers.
2. Coordinate power requirements and indicate on electrical power
drawings.
ii. Acceptable Manufacturers:
1. Halsey Taylor.
a. Basis-of-Design Product: HAC Hydro-Boost, barrier-free,
Model HTHB-HAC8BL-WF.
2. Elkay Mfg. Co.
g. Hand Dryers:
i. Northwestern prefers paper towels over electric hand dryers. Review
specific requirements with NU Project Manager.
ii. If provided, hand dryers shall be surface mounted equipped with an infrared sensor and an automatic 60 second cut-off switch, 120 Vac.
Coordinate power requirements and indicate on electrical power
drawings.
PLUMBING FIXTURES
22 4000 - 2
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
iii. Acceptable Manufacturer:
1. Sloan Valve Company, Model EHD-401.
END OF SECTION
PLUMBING FIXTURES
22 4000 - 3
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
This page intentionally left blank
PLUMBING FIXTURES
22 4000 - 4
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
DIVISION 22 – PLUMBING
SECTION 22 4500 – PLUMBING EQUIPMENT
1. General: This section outlines general requirements for plumbing equipment.
2. Materials:
a. Domestic Water Booster System:
i. No encased (can type) pumps are permitted.
ii. Above 10 hp domestic water booster pumps shall be variable speed.
iii. Acceptable Manufacturers:
1. Metropolitan Industries, Inc.
b. Sump and Ejector Pumps:
i. Acceptable Manufacturers:
1. Metropolitan Industries, Inc.
2. Hydro·O·Matic Pumps, A Division of Wylain, Inc.
3. No submersible sump pumps are permitted, except in elevator
shafts.
END OF SECTION
PLUMBING EQUIPMENT
22 4500 - 1
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
This page intentionally left blank
PLUMBING EQUIPMENT
22 4500 - 2
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
DIVISION 23 – HVAC
SECTION 23 0000 – HVAC DESIGN CRITERIA
General Criteria
1. General: The Heating, Ventilation, and Air Conditioning (HVAC) systems within
Northwestern’s facilities need to be designed and maintained to provide occupant
comfort and to meet the goals of safety, reliability, serviceability, and efficient operation
as described below:
a. Safety for building occupants during equipment operation and for maintenance
personnel equipment service.
b. Reliability of the systems in regard to the quality of components and materials
and in the required equipment redundancy.
c. Well-maintained HVAC systems result in lower operating costs and extended
service life. Therefore, the serviceability of the systems should promote easy
access to equipment and valves.
d. Systems efficiency should consider all operating costs, including energy and
maintenance.
2. Redundancy: The design must identify and address points of failure for systems serving
critical spaces, which are to be identified with the owner. Redundancy and/or back-up
systems should be identified. (For example, for an area with critical temperature stability
requirements, a secondary source of cooling may be required as back-up to the central
plant systems).
3. Sustainability: HVAC system design should employ sustainable design concepts to
meet the goals of NU and the community it serves.
Sustainability Overview
1. General: Refer to Design Guidelines for Energy Usage Intensity (EUI) requirements.
2. Energy Analysis and Modeling:
a. Energy analysis shall be completed in the Schematic Design Phase and updated
during the Design Development Phase utilizing a DOE-2 energy analysis
computer program.
b. The energy analysis shall be used to evaluate energy efficiency measures and
inform design decisions. A final model shall be prepared upon completion of the
construction documents.
GENERAL HVAC DESIGN GUIDELINES
23 0000 - 1
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
3. Refrigerants:
a. Use of zero CFC-based refrigerants shall be the minimum requirement.
b. Refrigerants that have low impact on both ozone depletion and global warming
shall be chosen.
4. HVAC Systems:
a. Consideration should be given to provide increased ventilation beyond the coderequired minimum when doing so would have minimal impact on energy
consumption.
b. Consideration for natural ventilation systems during appropriate seasonal
conditions to maximize energy savings.
c. Consideration should be given to providing individual thermal comfort control to
the maximum number of occupants. Where possible, greater than 50% of all
permanent occupants shall be provided with localized means to control their
thermal comfort. Thermal comfort control shall be provided for all multi-occupant
spaces, such as classrooms and conference rooms.
d. Review project specific requirements and current standards with NU Project
Manager during the design phase of the project.
5. Controls:
a. Building Automation System (BAS) – For projects with energy-using systems, a
BAS shall be included or the systems shall be controlled by an existing BAS.
b. Lighting – Lighting systems shall have local controls and shall include switches,
occupancy sensors, photocells, pre-set controllers and/or other controls as
appropriate. Where daylight dimming is used, the lighting controls may be
integrated into the BAS to maximize energy conservation.
c. Measurement, metering, monitoring system shall be fully integrated into campuswide system. Refer to the NU Metering Standards.
d. Minimum items to be metered:
i. System level outside air.
ii. Building level cooling.
iii. Building level heating.
iv. Building level electrical subdivided by lighting and power.
v. System level heat recovery.
vi. Building level water.
GENERAL HVAC DESIGN GUIDELINES
23 0000 - 2
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
e. Integration with campus-wide system:
i. New construction projects and renovation projects will include the
installation of Direct Digital Control (DDC) systems integrated into the
central BAS platform.
ii. Refer to DDC standards for additional information.
6. Commissioning:
a. HVAC systems and controls shall be commissioned by an independent
commissioning authority.
b. Specific systems to be commissioned and responsibilities for commissioning
shall be discussed with the NU Project Manager.
c. A/E shall include commissioning specifications in their construction documents.
HVAC Criteria
1. General:
a. Investigate the application of condensate reclamation off AHU cooling coils, for
irrigation, cooling tower make-up, etc.
b. Chemical shot feeders only apply to building closed loops. Chemical treatment
on Central Utility Plant (CUP) systems are accomplished at the CUP with no
additional chemical treatment or makeup in the buildings.
2. Steam Distribution: Refer to Design Guidelines.
3. Hydronic Distribution:
a. Hot water heating systems shall utilize the campus central steam system when
available. If central system steam is not nearby, a life cycle cost analysis will
need to be completed comparing extending campus steam into the building
versus other types of heating systems. Refer to NU Steam Framework Plan.
b. Hot water heating systems shall have standby pumps and heat exchangers sized
for 100% of the load.
4. Comfort Cooling: Refer to Design Guidelines.
5. Process Cooling:
a. Process chilled water (CHW) shall be through plate and frame heat exchanger to
CUP CHW. In no case shall CUP CHW be used directly for process cooling.
Design the heat exchanger for a maximum CUP CHW supply temperature of 52
degrees F.
GENERAL HVAC DESIGN GUIDELINES
23 0000 - 3
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
b. Process cooling loads are to be presented to the NU Project Manager for review
during the design phases of the project.
c. Where process cooling loads are identified in the design, provide hard pipe
connections to the loop. Braided tubing, barbed fittings, etc. are not permitted.
6. Air Distribution:
a. Ductwork and diffuser velocities must achieve the sound criteria developed for
each project. Review project specific requirements with the NU Project Manager.
b. Return air is to be ducted. Ceiling plenum returns are not permitted.
7. HVAC Controls: Refer to NU DDC Standards.
8. Health and Safety Criteria:
a. HVAC System designs shall comply with:
i. The local codes having jurisdiction.
ii. Occupational Safety and Health Administration (OSHA).
iii. Northwestern University Insurance requirements.
9. Vibration Monitoring:
a. NU has an existing vibration monitoring system installed on critical equipment
bearings, motors, fans, and pumps.
b. Determine with NU Project Manager prior to completion of Design Development
Phase whether vibration monitoring will be required for the project.
10. Operation and Maintenance Criteria:
a. Design documents shall require operation and maintenance manuals to be
delivered to the owner.
b. The design and layout of HVAC equipment shall show flow arrows for each
hydronic system.
c. Floor plans with the design and layout of HVAC equipment shall show the
required service clearance space for each piece of equipment, including, but not
limited to, tube pull space, coil removal, and unit-mounted starter electrical panel
code required clearances.
d. Floor plans with the design and layout of HVAC equipment shall show the
required path for equipment removal and replacement to the exterior of the
building. This equipment is defined as equipment too large to fit through a
standard 30” x 84” door such as AHU sections, pumps, chillers, boilers, large
fans, heat exchangers and electric switch gear, etc.
GENERAL HVAC DESIGN GUIDELINES
23 0000 - 4
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
11. Comfort Criteria:
a. General: Room comfort to be designed to provide space temperature of 72
degrees F year round, with seasonal set points of 68 degrees F and 74 degrees
F.
b. Labs shall be provided with humidification. Specific requirements to be reviewed
with NU Project Manager during the design phases of the project.
c. See Comfort Criteria Matrix at the end of this section for additional information.
12. Project Requirements:
a. Submittal /Shop Drawing requirements: Review project specific requirements
with NU Project Manager.
b. Coordination Drawing requirements: Review project specific requirements with
NU Project Manager.
c. Coordination with other trades: Review project specific requirements with NU
Project Manager.
d. Operation and Maintenance Manual requirements: Review project specific
requirements with NU Project Manager.
e. Record Drawings requirements: Review project specific requirements with NU
Project Manager. Coordinate Steam, Chilled water, Domestic water and
Sprinkler outages with Campus Facilities Management Operations.
GENERAL HVAC DESIGN GUIDELINES
23 0000 - 5
NORTHWESTERN UNIVERSITY
Technical Standards
X
X
X
Displacement air from floor, column
or low side wall discharge
X
X
X
X
X
X
Chilled beam with code minimum
outside air
X
X
X
X
Telecomm Rooms
X
Electrical Rooms
Student Centers
X
Mechanical Rooms
Dining Halls
X
Administrative
Offices
Residence Halls
All air variable air volume with code
minimums with reheat
Comfort Criteria Matrix
Teaching and
Research Labs
Library
General Classroom
Issuance Date: 01.01.2014
X
X
HVAC SYSTEM TYPES
X
100% Outside air Constant or
Variable air volume with makeup air
and code minimums with reheat
X
Heat Recovery unit for laboratory
exhaust system
X
X
Heat Recovery unit for
kitchen/dishwasher exhaust to
exchange with 100% minimum
outside air AHU
X
Heat Recovery unit for
bathroom/toilet exhaust to exchange
with 100% minimum outside air
AHU
X
Gang hood and general lab exhaust
where acceptable
X
4 pipe fan coil units with code
minimum outside air
X
Provide mechanical ventilation
supply and exhaust as required by
code or for cooling or combustion
air
X
HEATING
Design Temperature 70°F ± 2°F
X
X
X
X
X
X
X
Temperature Set Point 68°F
X
X
X
X
X
X
X
Reheat for interior rooms & exterior
room perimeter walls with no glass
X
X
X
X
X
X
X
Perimeter fin tube or radiant ceiling
Panel for perimeter with glass
heights less than 12ft
X
X
X
X
X
X
X
X
GENERAL HVAC DESIGN GUIDELINES
23 0000 - 6
NORTHWESTERN UNIVERSITY
Technical Standards
X
Telecomm Rooms
Student Centers
X
Electrical Rooms
Dining Halls
X
Mechanical Rooms
Residence Halls
X
Administrative
Offices
Library
Teaching and
Research Labs
General Classroom
Comfort Criteria Matrix
Issuance Date: 01.01.2014
HEATING Cont'd
Perimeter fin tube at multiple levels
or forced hot air from top & bottom
or a combination of the two for
perimeter with glass height 12 feet
or more
X
For rooms over 25 feet deep from
window, consider a separate
perimeter zone.
X
X
X
X
X
X
X
Provide Unit Heaters
X
Provide electric only Unit Heaters
X
COMFORT COOLING
Provide mechanical/electrical
cooling for mechanical rooms that
have electronic controls with
maximum temperature requirements
X
Provide computer room air
conditioning units for mechanical
cooling, heating, dehumidifying and
humidifying the space
X
X
AIR DISTRIBUTION
Provide even distribution of air with
multiple supply and returns
X
Avoid supply air directed at or near
face of laminar flow of fume hood
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
HUMIDITY CONTROL EQUIPMENT
No winter humidification is required
X
Summer maintain 50% maximum ±
5%
X
X
X
Winter maintain 30% minimum ± 5%
X
X
Clean steam humidification with RO
water make up and all stainless
steel piping is required
X
X
X
GENERAL HVAC DESIGN GUIDELINES
23 0000 - 7
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
ABBREVIATIONS, GENERAL
AI
AO
BAS
BI (DI)
BO (DO)
CUP
EMS
FACP
PRS
SD
Analog Input
Analog Output
Building Automation System
Binary (Digital) Input
Binary (Digital) Output
Central Utility Plant
Energy Management System
Fire Alarm Control Panel
Pressure Reducing Station
Smoke Detector
ABBREVIATIONS, DRAWINGS
AFMS
CHWP
CHWR
CHWS
CU
D
DP
DPT
EMS
FCV
FOT
FT
F&T
HPS
HWR
HWS
IB
LCHWR
LCHWS
LPC
LPS
NC (FC)
NO (FO)
PRV
P
PI
PP
PS
RPZ
SS
TI
TT (RTD)
Airflow Measuring Station
Chilled Water Pump
Chilled Water Return
Chilled Water Supply
Copper
Diameter
Differential Pressure
Differential Pressure Transmitter
Energy Management System
Flow Control Valve
Flat On Top
Flow Transmitter
Float and Thermostatic (Trap)
High Pressure Steam
Hot Water Return
Hot Water Supply
Inverted Bucket (Trap)
Laboratory Chilled Water Return
Laboratory Chilled Water Supply
Low Pressure Condensate
Low Pressure Steam
Normally Closed (Failed Closed)
Normally Open (Fail Open)
Pressure Reducing Valve
Pump
Pressure Indicator (Gauge)
Primary Pump (Chilled Water)
Proof (Status) Switch
Reduced Pressure Zone
Stainless Steel
Temperature Indicator (Thermometer)
Temperature Transmitter (Resistance Temperature Device)
END OF SECTION
GENERAL HVAC DESIGN GUIDELINES
23 0000 - 8
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
DIVISION 23 – HVAC
SECTION 23 0513 – MOTORS
1. General: This section outlines general requirements for motors.
2. Design Considerations:
a. Motors driven by a VFD shall not operate into their service factor.
b. Motors within an air handling unit (air stream) shall be Totally Enclosed Fan
Cooled (TEFC).
c. HVAC motors outdoors not in an air stream shall be Totally Enclosed Fan Cooled
(TEFC).
d. HVAC motors indoors not in an air stream shall be open drip proof (ODP).
e. The service factor of HVAC motors shall be 1.15.
f.
Motors, except those controlled driven by a variable frequency drive, shall have
class B insulation.
g. Motors controlled by a variable frequency drive shall have class F or H insulation
and a winding thermostat to detect motor overheat conditions.
h. Motors driven by a VFD shall be provided with shaft grounding brush similar to
AEGIS SGR to prevent bearing from shaft current.
END OF SECTION
MOTORS
23 0513 - 1
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
This page intentionally left blank
MOTORS
23 0513 - 2
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
DIVISION 23 – HVAC
SECTION 23 0514 – VARIABLE FREQUENCY DRIVES (VFD’s)
1. General: This section outlines general requirements for variable frequency drives.
2. Design Considerations:
a. VFD’s to be purchased by local contractor through a local representative
authorized for startup and service.
b. The VFD manufacturer shall perform a harmonic analysis at no cost to the
University. The minimum Allowable shall be 5% distortion for current and voltage
per IEEE-519
c. The VFD shall include the following features:
i. Main input circuit breaker.
ii. Input: 4 - 20 mA (AO).
iii. Output for a 4-20 mA feedback to Energy Management System (EMS)
(AI) via communications link.
iv. System enable terminals from EMS (BO).
v. System status contact for EMS (BI).
vi. Malfunction alarm contact for EMS.
vii. Digital current meter mounted on the door.
viii. 3 Contactor bypass.
1. NOTE: Bypass on VFD’s is not permitted. However if desired by
Engineer of Record, they will be reviewed on a case by case
basis.
2. Consider dual-inverter option where redundancy is critical.
ix. Overload relay.
x. RFI protection.
xi. DC link reactor.
xii. IGBT (Insulated Gate Bipolar Transistors) technology.
xiii. Carrier frequency: 8 kHz.
xiv. Isolation transformer, if required.
VARIABLE FREQUENCY DRIVES
23 0514 - 1
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
d. The VFD shall have 110% continuous current capability, 120% overload capacity
for 60 seconds.
e. The VFD shall have minimum NEMA 1 enclosure. Enclosure shall be
determined by the environment where VFD is being installed.
f.
High motor winding temperatures shall shut down the driven device and alarm.
3. Application
a. No bypass is to be provided when:
i. Fan Array: 3 or more fans are used.
ii. Redundant Fans: 2 fans are used, each at 100% capacity.
iii. Redundant Pumps: 2 pumps are used, each at 100% or 3 pumps are
used, each at 50%.
4. Acceptable Manufacturers:
a. Danfoss Graham Company.
b. Emerson (Saftronics Inc.).
c. ABB.
END OF SECTION
VARIABLE FREQUENCY DRIVES
23 0514 - 2
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
DIVISION 23 – HVAC
SECTION 23 0529 – MECHANICAL SUPPORTING DEVICES
1. General: This section outlines general requirements for mechanical supporting devices.
2. Design Considerations:
a. Hangers and supports for both interior and exterior use to be steel hot dipped
galvanized coated.
b. Hangers are required to be specific to pipe and ductwork independently and not
shared.
c. Where insulation in not required use similar metal hangers such as copper
hanger for copper pipe and stainless steel hanger for stainless steel pipe.
d. Rods shall have electroplated zinc or hot dip galvanized finish.
e. Rigid inserts are required for insulated pipe and ductwork.
f.
Ductwork: Metal and flexible duct hangers and supports shall be in accordance
with SMACNA “HVAC Duct Construction Standards – Metal and Flexible,” latest
edition.
END OF SECTION
MECHANICAL SUPPORTING DEVICES
23 0529 - 1
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
This page intentionally left blank
MECHANICAL SUPPORTING DEVICES
23 0529 - 2
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
DIVISION 23 – HVAC
SECTION 23 0550 – VIBRATION ISOLATION
1. General: This section outlines general requirements for vibration isolation.
2. Design Considerations:
a. All rotating equipment shall have vibration isolation from building structure.
b. Free standing spring isolators are not permitted.
c. Floor-mounted spring vibration isolators shall be housed type springs.
3. Fans and Ductwork:
a. Fan vibration isolation shall be completed by the Architect / Engineer in
compliance with Table 23 0550-1.
Table 23 0550-1
Fan Schedule
Fan No.
Location
Wheel
Diameter
in.
Vibration Isolation
Arrange
ment
Fan
Motor
Type
RPM
HP
Isolator
Static
Deflection
in.
a. Ducts within 50 feet of the fan discharge shall be isolated by spring hangers with
neoprene cups.
4. Pumps and Piping:
a. Pump vibration isolation shall be in compliance with Table 23 0550-2.
Table 23 0550-2
Pump Schedule
Pump No.
Location
Vibration Isolation
Type
Motor
Type
Static
HP
Isolator
Deflection, in.
a. The first three hangers and floor supports from equipment (, pumps) shall be
isolated by spring hangers with neoprene cup for pipe and spring isolated
concrete inertia base mounts respectively.
VIBRATION ISOLATION
23 0550 - 1
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
b. Piping passing through equipment room walls, floors, or ceilings shall be all
directional acoustical pipe seals.
c. Risers shall be suspended from or supported by all directional acoustical pipe
anchors and telescoping type guides
d. Concrete bases after the system is in operation shall have a minimum 2 in.
clearance between the floating base and the floor.
5. Acceptable Manufacturers:
a. Amber/Booth Company.
b. Mason Industries.
c. Vibration Mountings & Controls, Inc.
d. Vibro-Acoustics.
END OF SECTION
VIBRATION ISOLATION
23 0550 - 2
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
DIVISION 23 – HVAC
SECTION 23 0553 – MECHANICAL SYSTEMS IDENTIFICATION
1. General: This section outlines general requirements for mechanical systems
identification.
2. Design Considerations:
a. Provide labels on pipe and ductwork every 20 feet and at every change in
direction.
b. Stenciling of labels is not permitted.
c. Piping shall be marked in accordance with ANSI Standard A13.1, most current
version.
d. Provide a flow arrow at each pipe label for direction of flow.
e. Provide labels for each type of air duct including a flow arrow for direction of flow.
f.
Fire damper access panels shall be permanently identified on the exterior by
labels not less than 2 inches in height reading: FIRE DAMPER.
g. Smoke damper access panels shall be permanently identified on the exterior by
labels not less than 2 inches in height reading: SMOKE DAMPER.
h. Combination fire/smoke dampers can be reset manually. Mark the access panel
from which the damper can be reset by a label not less than 2 inch in height
reading: RESETTABLE FIRE/SMOKE DAMPER. Mark the other access panel
by a label not less than 2 inches in height reading: FIRE/SMOKE DAMPER.
i.
Static pressure sensors in ductwork shall be permanently identified on the
exterior by labels not less than 2 inches in height reading: STATIC PRESSURE
SENSOR.
j.
Humidity sensors in ductwork shall be permanently identified on the exterior by
labels not less than 2 inches in height reading: HUMIDITY SENSOR.
k. Provide equipment labels for air-handling units, fan pumps, chillers, boilers, etc.
Labels shall spell out the system or equipment. Do not use abbreviations.
MECHANICAL SYSTEMS IDENTIFICATION
23 0553 - 1
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
3. Acceptable Manufacturers:
a. Brady USA Inc., Signmark Div.
b. Kolbi Industries Inc.
c. Panduit Corp.
END OF SECTION
MECHANICAL SYSTEMS IDENTIFICATION
23 0553 - 2
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
DIVISION 23 – HVAC
SECTION 23 0594 – TESTING, ADJUSTING, AND BALANCING (TAB)
1. General: This section outlines the general requirements for testing and balancing during
the design and/or construction phases of the project.
2. Design Considerations:
a. The TAB contractor shall be typically procured directly by Northwestern
University. Review specific requirements with the NU Project Manager prior to
the start of the project and/or during the design phases.
3. Certification:
a. Each TAB technician shall be certified by AABC (Associated Air Balance Council)
or NEBB (National Environmental Balancing Bureau).
b. Certification is required for air systems, hydronic systems, sound, and vibration.
Test procedures shall be in accordance with the latest edition of AABC or NEBB
Standards, ASHRAE - 2011 HVAC Applications Chapter 38.
4. Acceptance Criteria:
a. For most spaces, the total supply air quantity to each space of a system shall be
within -5% to +10% of design. Review project specific requirements with NU
Project Manager.
b. The percent tolerance of each outlet within a space shall be per Table 23 0594-1.
Table 23 0594-1
System
Single Zone, Multizone,
VAV
Heating and Ventilating
Number of Outlets in Space
1
2
3 or More
-5%
±10%
±15%
±15%
±15%
+10%
-5%
+10%
c. Air quantity of each return air grille and diffuser shall be within ±10% of design.
The design room pressurization must be maintained regardless of the tolerance
at each individual diffuser.
d. Vivariums: In general, these laboratories shall be under negative pressure. The
design should meet the current NIH Design Requirements Manual for Biomedical
TESTING, ADJUSTING, AND BALANCING
23 0594 - 1
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
Laboratories and Animal Research Facilities. Any reduction in airflow shall be
presented by the project Engineer of Record and reviewed by the NU Project
Manager and Project Engineer.
e. Culture Rooms: These rooms shall be under positive pressure.
f.
Hydronic Systems: Heating and cooling hydronic systems shall be balanced so
that the flow is from 0 to +5% of design at each coil.
g. Combination fire/smoke dampers in dynamic smoke control systems shall be
tested for closure under airflow conditions (International Mechanical Code-2009,
Section 607), and to assure positive pressure of certain zones, and negative
pressure for other zones. Smoke dampers in dynamic smoke control systems
must close under airflow conditions.
5. Reports:
a. The contractor prior to TAB work shall submit the following data for review.
b. TAB personnel qualification and certification reports.
c. Test procedures.
d. TAB report forms.
e. As tests are completed the contractor shall submit test reports with includes an
executive summary. The executive summary shall state extent of system
compliance, system deficiencies, and recommended changes.
6. Approved Contractors:
a. Independent Test and Balance.
b. CEPRO.
c. Project Architect / Engineer to confirm with NU Project Manager that testing and
balancing contractors are currently in good standing with NU.
END OF SECTION
TESTING, ADJUSTING, AND BALANCING
23 0594 - 2
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
DIVISION 23 – HVAC
SECTION 23 0700 – MECHANICAL SYSTEM INSULATION
1. General: This section outlines the general requirements for mechanical system
insulation.
2. Design Considerations:
a. Piping insulation thickness shall be in compliance with ASHRAE/IES Standard
90.1-2010, “Energy Efficient Design of New Buildings Except New Low-Rise
Residential Building,” Table 6.8.3A and 6.8.3B.
b. Insulation shall butt to preformed insulation covers furnished with circuit setters.
c. Insulated pipe and fittings outdoors shall be covered by Zeston 300 series fitting
covers and pipe jacketing. Seams and joints shall be waterproof.
d. Insulated pipe fittings indoors shall be covered by Zeston 2000 PVC covers.
e. Pipe insulation subject to maintenance personnel traffic or within 18 inches of the
floor shall be rigid and water resistant.
i. Density of the insulation shall not be less than 12 lb/ft3; the thermal
conductivity of the material shall not exceed 0.45 BTU·in./(hr·ft2·ºF) at
100ºF.
ii. Insulation thickness shall be determined from ASHRAE/IES Standard
90.1-2010 and increased to the values in Table 23 0700-1.
Table 23 0700-1
Thickness from
ASHRAE/IES
Standard 90.1-2010
Rigid Insulation
Thickness, in.
0.5
1.0
1.0
2.0
1.5
2.5
2.0
3.5
2.5
4.5
3.5
6.0
iii. Insulation shall have a jacket; either metal or Zeston series 300 PVC.
MECHANICAL SYSTEM INSULATION
23 0700 - 1
NORTHWESTERN UNIVERSITY
Technical Standards
f.
Issuance Date: 01.01.2014
Glass vent piping shall be insulated and metal jacketed.
i. Acceptable Manufacturers:
1. Certain Teed Corp.
2. Knauf Fiber Glass GmbH.
3. Owens-Corning Fiberglas Corp.
4. Schuller International, Inc.
g. Removable Insulation Covers:
i. Steam valves, steam expansion joints, and awkward surfaces not
covered by insulation shall be covered by a removable ceramic fiber
blanket.
ii. Acceptable Manufacturers:
1. Advance Thermal Corp.
2. Thermal Energy Products, Inc.
3. Temptec.
4. Remco Technology, Inc.
h. Chilled and Low temperature Condenser Water Pumps: Each water pumps shall
be covered by 1 inch thick AP Armaflex applied with a waterproof adhesive.
Removable components shall use Velcro applied to both the Armaflex and the
pump surface with a waterproof adhesive such that the pieces can be removed
for servicing without damage.
i.
Chillers: Each chiller shall be covered by 1 in. thick AP Armaflex applied with a
waterproof adhesive. All removable components shall use Velcro applied to both
the Armaflex and the shell surface with a waterproof adhesive such that the
pieces can be removed for servicing without damage.
j.
Converters:
i. Shell and tube heating shall be covered by 2-1/2 in thick rigid glass fiber
insulation in accordance with ASTM C612, Type IA and IB, suitable for
temperatures to 450°F,
ii. Plate and frame shall be covered by 1 in. thick AP Armaflex applied with a
waterproof adhesive:
k. Condensate Pump / Receivers: Provide a cover of 2 inch thick rigid glass fiber
insulation in accordance with ASTM C612, Type IA and IB, suitable for
temperatures to 450°F,
MECHANICAL SYSTEM INSULATION
23 0700 - 2
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
i. Supply, return, and exhaust ducts and plenums shall be insulated in
accordance with ASHRAE/IES Standard 90.1-2010, “Energy Efficient
Design of New Buildings Except New Low-Rise Residential Building,”
Table 6.8.2A and 6.8.2B.
1. Exception: Exhaust ducts not used for heat recovery in
unconditioned spaces need not be insulated.
l.
Ductwork in mechanical equipment rooms and exposed in other areas shall be
covered with rigid insulation with a flame retardant vapor barrier.
m. Flexible fibrous blanket insulation with a factory-applied vapor-barrier shall be
applied to all concealed ductwork requiring insulation.
n. Exhaust ductwork in unconditioned spaces which exits through an exterior wall
shall be insulated 20 ft minimum from the exterior wall.
o. Insulation shall be installed in compliance with the “Commercial & Industrial
Insulation Standards” by MICA (Midwest Insulation Contractors Association).
END OF SECTION
MECHANICAL SYSTEM INSULATION
23 0700 - 3
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
This page intentionally left blank
MECHANICAL SYSTEM INSULATION
23 0700 - 4
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
DIVISION 23 – HVAC
SECTION 23 2113 – HYDRONIC PIPING
1. General:
a. This section outlines the general requirements for hydronic pipe and pipe fittings,
including valves, unions, and flanges.
b. Specific requirements shall be reviewed with the NU Project Manager during the
design phases of the project.
c. Materials: Piping shall conform to ASTM standards.
2. Design Considerations:
a. General: Piping shall be routed orthogonally (no diagonal shortcuts).
i. Exception: Common pipe of the chilled water bridge.
b. Provide vents at the high point of piping systems, in accessible locations, to allow
for system venting. Vents shall have isolation valves, pressure gauge, and boiler
drain.
c. Expansion tanks shall be diaphragm type; the pre-charge pressure shall be
specified to suit the system.
d. Air separators shall be installed in each heating system distribution loop at the
point of lowest air solubility and vented to atmosphere.
e. Hot and Chilled Water Piping:
i. Each new closed hydronic system shall have full bore strainers and a
particulate side-stream filter rated at 100 microns, unless specified
otherwise.
1. Show on the drawings for each new hydronic system full bore
strainers and a 15% side stream filter. Specify the micron filtration
size for the side-stream filter.
ii. No piping with a fluid shall be routed over electrical busway housings.
For electrical busway housings provide a minimum 24 inches on both
sides and the bottom.
f.
Tracer Wire:
i. Non-electrical pipe installed below grade shall have a 12 AWG
copperhead Reinforced Tracer Wire, or equal. Tracer wire to be
accessible at each end in manholes.
HYDRONIC PIPING
23 2113 - 1
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
ii. Tracer Wire shall be installed on the pipe as shown on the contract
drawings.
iii. Tracer wires shall terminate in each tunnel and manhole where new
utilities penetrate. Tracer wires shall be provided with labels noting what
pipe the wire is affixed to (ie. Chilled Water Supply, Pumped Condensate
Return, etc).
3. Pipe Support Guides:
a. Piping shall be spaced and supported at a maximum of 10 foot intervals in
conduit by insulating support-guides and to permit pipe to expand and contract
freely without stress or wear on pipe or insulation as well as provide for drainage
and free air circulation.
4. Expansion Loops, Moment Guided, Ells and Tees:
a. Prefabricated ells, loops and tees to be provided where shown on plan drawings
and to consist of pipe, insulation, and conduit conforming to the same pipe and
welding specifications as specified before herein for straight runs. Tees, anchors,
elbows and other fittings shall be factory connected and prefabricated to straight
sections whenever shipping requirements permit.
b. Expansion loops to be of proper design in accordance with stress limits indicated
by ASME Code for pressure piping, District Heating Section. Install loop piping in
conduit suitably oversized to handle the calculated pipe expansion without
damaging the insulation.
c. The piping system is designed with both expansion loops and expansion joints.
The piping system shall be designed to accommodate this requirement by
including moment guides as required for the piping system to function properly in
conjunction with expansion joints.
d. Cold springing or pre-stressing piping as a means for control of expansion in any
portion of the steam system is not allowed.
5. Anchors:
a. Prefabricated plate anchors to be provided where shown and to consist of a steel
plate welded to pipe and conduit. Steel plate shall be 1/2” thick for 1” to 22”
conduit and 3/4” thick for conduit over 22” for anchors with expansion loops.
b. Concrete block to be cast over plate and conduit and to be large enough for firm
anchorage into undisturbed trench sidewalls and/or bottom. Concrete block to be
at least 36” in length and extend minimum of 12” beyond entire anchor plate. The
piping vendor shall provide detailed instructions to Contractor for oversized
anchors due to expansion joints. The Contractor shall provide oversized anchors
as detailed by the piping vendor.
HYDRONIC PIPING
23 2113 - 2
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
6. End Seals and Gland Seals:
a. Terminal ends of conduits inside manholes, to be equipped with end seals
consisting of steel bulk head plate welded to pipe and conduit. Where there is no
anchor within 5’-0” of terminal end, conduits to be equipped with gland seals
consisting of packed stuffing box and gland follower mounted on steel plate
welded to end of conduit. End seals or gland seals to be equipped with drain and
vent openings located diametrically opposite on vertical centerline of mounting
plate and to be shipped to job site with plugs in place. Terminate conduits 4”
beyond inside face of manhole or building walls to protect any exposed piping
insulation from damp wall condensation. Refer to drawing details for further
construction and dimensional requirements
b. All end and gland seals shall be reinforced with 12” long galvanized steel sleeve
at the sealing surface to prevent compression of the outer jacket and insulation
from modular wall sealing devices. The protection sleeve shall be minimum 6
gauge thickness and shall be outside of the HDPE jacket. Where the galvanized
steel sleeve stops on the outside of the manhole, the sleeve shall be shrink
wrapped to the HDPE jacket and sealed water tight.
7. Field Joints:
a. Field joints shall conform to the pipe manufacturer’s specifications.
b. Field joints shall consist of field installed mineral wool insulation banded with
stainless steel bans on the carrier pipe, field applied 10 gauge connector sleeve
on the inner conduit, field applied foam insulation, polyethylene heat shrink wrap
and split HDPE jacket at a minimum. Field joint materials and methods shall be
provided by and approved by the piping manufacturer.
8. Chilled Water in Central Utility Plant (CUP):
a. 2-1/2 inches and Smaller:
i. Pipe: ASTM A53, Type F, standard weight, carbon steel.
ii. Fittings: ASME B16.4, Class 125, cast iron, threaded or ASME B16.3,
Class 150, malleable iron, threaded.
iii. Unions: ASME B16.29, malleable iron, Class 250. Refer to Unions and
Flanges in this Section.
b. 3 inches through 24 inches:
i. Pipe: ASTM A53, Grade B, Type E or S, standard weight, carbon steel.
ii. Fittings: ASTM A234 Grade WPB/ASME B16.9, standard weight,
seamless, carbon steel weld.
iii. Flanges: Class 150. Refer to Unions and Flanges in this Section.
HYDRONIC PIPING
23 2113 - 3
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
c. 30 inches through 42 inches:
i. Pipe: API-5L, Grade B, Type DSAW, 0.375" wall thickness, carbon steel.
ii. Fittings: ASTM A234, Grade WPB/ASME B16.9, 0.375" wall thickness,
seamless, carbon steel weld.
iii. Flanges: Class 150. Refer to Unions and Flanges in this Section.
9. Chilled Water (Underground):
a. Piping and Fittings 8 inches through 36 inches:
i. Ductile iron pipe, 300 psi minimum working pressure, ANSI/AWWA
C151/A21.51, with external asphaltic coating. Nominal piping wall
thicknesses shall be as follows:
4”
0.25”
6”
0.25”
8”
0.25”
10”
0.26”
12”
0.28”
14"
0.30"
16"
0.32"
18"
0.34"
20"
0.36"
24"
0.40"
30”
0.45”
ii. Fittings shall be ductile iron mechanical joint type manufactured in
accordance with ANSI/AWWA C110/A21-10, rated for 250 psi working
pressure.
iii. Straight pipe joints and fittings to be restrained joint-type. Joints and
fittings shall be flexible and shall be designed to provide positive restraint
against end-wise separation due to thrust.
iv. All pipe taps shall be drilled and tapped using corporation stop. Saddle
taps will not be allowed.
HYDRONIC PIPING
23 2113 - 4
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
b. Restrained Type Joint - All Sizes:
i. Pipe Joints:
1. US Pipe “TRFlex” or American Cast Iron Pipe “Flex Ring” or
approved equal. American Cast Iron Pipe “Fastite” or US Pipe
“Tyton” joint with EBBA Iron Series 1100 or Series 1700 harness
type restraints may also be used. All joints shall be restrained
type. Pressure rating of 250 psi minimum.
2. All bolts shall be low alloy, high strength steel bolts having
minimum yield strength of 45,000 PSI and which are cathodic to
the pipe, meeting the requirements of AWWA C111.
3. Gasket material shall be SBR.
4. Pipe Fittings, Valves and Connections to Existing Systems: Equal
to EBBA Iron Series 1100 or Series 1700 Megalug restraint
systems for push-type or mechanical joint piping, fittings and
valves.
5. Series 1100 solid ring restraints shall have a rated working
pressure of 350 psi up to 16” pipe and 250 psi for 18” to 36” pipe.
6. Series 1700 restraints shall have a rated working pressure of 350
psi up to 16” pipe and 250 psi for 18” to 36” pipe.
7. Gasket material shall be SBR.
10. Waste Water:
a. Pressurized Waste Water:
i. Type K copper water tube, (drawn) temper, ASTM B88; with copper
drainage fittings (DWV), ANSI B16.23; wrought copper drainage fittings
(DWV), ANSI B16.29; lead free (<.2%) solder ASTM B32; flux, ASTM
B813.
11. Unions and Flanges:
a. Unions:
i. 2 1/2 inches and Smaller:
1. Forged steel, ASTM A105 Grade 2, ASME B16.11, socket weld,
3000lb. WOG with steel to steel seats.
HYDRONIC PIPING
23 2113 - 5
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
b. Flanges:
i. 3 inches and Larger:
1. ASTM A105, ANSI B16.5, hot forged steel flanges, welding neck
pattern. Slipon pattern flanges are not allowed. Bore dimension of
welding neck flange shall match inside diameter of connected
pipe. Use raised face flanges for mating with other raised face
flanges with self-centering flat ring gaskets. Use flat face flanges
for mating with other flat face flanges with full face gaskets.
ii. Flange pressure class indicated in respective piping service is minimum
required. Mating flange pressure class shall match pressure class of
device connected to such as valves and piping specialties. Flanged
connection will on be permitted at specialty connections such as at a
vessel or specialty valve.
c. Flange Gaskets:
i. Gasket material to be asbestos free and suitable for pressure
temperatures and fluid of piping system. Non-metallic gaskets shall be in
accordance with ANSI/ASME B16.21 and ASTM F104.
ii. Gaskets shall be equal to Flexitallic Style CG, graphite filler, 304 SS
winding, carbon steel centering ring, 0.175" thickness.
d. Bolting:
i. For all connections to valves, use bolts studs.
ii. Bolts, bolt studs, nuts and washers used on piping systems in Central
Utility Plant (CUP), tunnel and manholes shall have zinc plated finish.
iii. Thread shall be in accordance with ANSI/ASME B1.1, Class 2A tolerance
for external threads and Class 2B tolerance for internal threads. Threads
shall be coarse-thread series except that alloy steel bolting 1-1/8" and
larger in diameter shall be 8 pitch thread series.
iv. Threaded rods are not allowed as fastening elements on steam systems.
v. For Class 150 and Class 300 flanges at 400°F or lower temperature, use
carbon steel bolts or stud bolts conforming to ASTM A307, Grade B with
nuts conforming to ASTM A307.
vi. For Class 300 flanges at 500°F or lower temperature, use alloy steel bolts
or stud bolts conforming to ASTM A193, Grade B7 or B16, with nuts
conforming to ASTM A194, Grade 2H.
HYDRONIC PIPING
23 2113 - 6
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
12. Valves – General:
a. General: Install valves as shown on plans, details and according to the valve
manufacturer's installation recommendations.
b. Provide chain operators for manually operated valves 4" and larger, located more
than 6'-0" above normal working surface.
13. Chilled Water (In Tunnel):
a. Butterfly Valves:
i. Valves to conform to latest revision of AWWA C-504. Valves to be tight
closing, rubber seated. Valves to be zero-leakage at 200 psig, and shall
be suitable for throttling service and operation after long periods of
inactivity. Valves shall be rated for 250-psi non-shock working pressure
minimum. Valves to be designed for direct buried application.
ii. Cast iron body ASTM A-126B, Class B, restrained flanged (ANSI B16.1)
ends. Valve shall be furnished complete with joint accessories (bolts,
nuts, and gaskets). Flanging shall be lugged type permitting removal of
downstream piping while using valve for system shutoff.
iii. Resilient seat shall be ethylene propylene diene Monomer (M-class)
rubber (EPDM). EPDM seats shall be peroxide cured.
iv. Valves 20" and smaller shall have the seat bonded directly to the body.
Valve 24" and larger shall have seats that are mechanically retained in
the valve body. Either seat shall be capable of mechanical adjustment in
the field and field replacement.
v. Valve discs shall be constructed of cast iron ASTM A-126, Class B or
ductile iron ASTM-A-536. Disc shall have stainless steel seating edge to
mate with valve seat.
vi. Valve shaft to be 18-8, Type 304 stainless steel with "V" / "cup" PTF style
self-adjusting packing.
vii. Valve assembly shall be furnished with a non-adjustable factory set thrust
bearing designed to center the valve disc at all times.
viii. Shaft bearings shall be contained in the integral hubs of the valve body
and shall be self-lubricated sleeve type and shall be sealed in place with
"V" / "cup" PTF style self-adjusting packing.
ix. Prior to shipment, valves to be hydrostatically and leak tested at the
factory in accordance with AWWA C-504. Factory hydrostatic test shall be
performed at 200 psig for all valves.
1. NU and Architect / Engineer shall have option to be present to
witness factory testing for the first valves that are 20" and smaller
HYDRONIC PIPING
23 2113 - 7
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
and the first valves that are 24" and larger. Valve manufacturer
shall be responsible for providing transportation and
accommodations for two (2) NU representatives and one (1)
representative of the Architect / Engineer.
x. Provide worm gear operators. Provide rotary hand wheels with adjustable
position stop and position indicators. Size hand wheel operators with no
higher than 40 lb rim pull at full valve pressure rating.
14. Chilled Water (Underground):
a. Butterfly Valves:
i. Valves to conform to latest revision of AWWA C-504. Valves to be tight
closing, rubber seated. Valves to be zero-leakage at 200 psig, and shall
be suitable for throttling service and operation after long periods of
inactivity. Valves shall be rated for 250-psi non-shock working pressure
minimum. Valves to be designed for direct buried application.
ii. Cast iron body ASTM A-126B, Class B, restrained mechanical joint
(AWWA C-151/ANSI 21.11) or flanged (ANSI B16.1) ends. Valve shall be
furnished complete with joint accessories (bolts, nuts, gaskets and
glands).
iii. Resilient seat shall be ethylene propylene diene Monomer (M-class)
rubber (EPDM). EPDM seats shall be peroxide cured.
iv. Valves 20" and smaller shall have the seat bonded directly to the body.
Valve 24" and larger shall have seats that are mechanically retained in
the valve body. Either seat shall be capable of mechanical adjustment in
the field and field replacement.
v. Valve discs shall be constructed of cast iron ASTM A-126, Class B or
ductile iron ASTM-A-536. Disc shall have stainless steel seating edge to
mate with valve seat.
vi. Valve shaft to be 18-8, Type 304 stainless steel with "V" / "cup" PTF style
self-adjusting packing.
vii. Valve assembly shall be furnished with a non-adjustable factory set thrust
bearing designed to center the valve disc at all times.
viii. Shaft bearings shall be contained in the integral hubs of the valve body
and shall be self-lubricated sleeve type and shall be sealed in place with
"V" / "cup" PTF style self-adjusting packing.
ix. Prior to shipment, valves to be hydrostatically and leak tested at the
factory in accordance with AWWA C-504. Factory hydrostatic test shall be
performed at 200 psig for all valves.
HYDRONIC PIPING
23 2113 - 8
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
1. NU and Architect / Engineer shall have option to be present to
witness factory testing for the first valves that are 20" and smaller
and the first valves that are 24" and larger. Valve manufacturer
shall be responsible for providing transportation and
accommodations for two (2) NU representatives and one (1)
representative of the Architect / Engineer.
x. Valves to be complete with grease packed buried service gear operator,
shaft extensions with centering disk located on shaft, to within one foot of
finished grade and soil pipe.
xi. Refer to drawings for length of shaft extensions and soil pipes.
xii. Valves shall be Pratt Groundhog or approved equal.
15. Underground Valve Specialties:
a. Valve Boxes:
i. Valve boxes shall be 2 - piece cast iron, screw type, 5 1/4" shaft with
stay-put heavy duty traffic weight lid marked “CHILLED WATER” to match
piping system. Boxes shall be equal to Figure UTL 273, as manufactured
by Dewey Brothers, Tyler or Charlotte Pipe and Foundry Co.
ii. Valve boxes to be coated with coal tar for buried service application.
b. Valve Wrenches:
i. Provide T-handle extension wrench with flexible socket for each different
shaft size. Socket shall be sized for gate valve operating nut.
16. Ball Valves:
a. 2" and Smaller: bronze body, threaded, stainless steel ball and stem, full port,
teflon seat rings, blowout-proof stem, three piece construction, 600 psi WOG,
150 psi SWP.
17. Drain and Vent Valves:
a. In Tunnel: Ball valves as specified above with hose thread adapter and cap.
Provide 2" minimum drain valves provided with short threaded nipple and cap. All
vent valves shall be minimum 3/4" in size.
18. Swing Check Valves:
a. Provide check valves at condensate lines at outlet of traps. Install check valve
between trap and gate valve.
HYDRONIC PIPING
23 2113 - 9
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
19. Drain Valves:
a. Provide drain valves at all low points of piping systems for complete drainage of
systems.
20. Chilled Water - Drain and Vent Valves:
a. Provide drain valves at all low points of piping systems for complete drainage of
systems. Provide vent valves at high points for venting of air. Locate drains and
vents as indicated on the contract drawings and as required due to actual
installed conditions.
21. Pressure Equalizing Valves:
a. Provide pressure equalizing valves on valves in the following locations:
i. High pressure steam (230 psig) shut-off valves 3" and larger for
supervised warm-up.
END OF SECTION
HYDRONIC PIPING
23 2113 - 10
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
DIVISION 23 – HVAC
SECTION 23 2116 – HYDRONIC PIPING SPECIALTIES
1. General: This section outlines the general requirements for hydronic piping specialties.
2. Design Considerations:
a. Provide chain-wheel operators for valves 6 inches and larger mounted over 8
feet above floor.
b. Furnish gear operators for valves 8 inches and larger.
i. Acceptable Manufacturers:
1. Flowseal.
2. Bray.
3. Neles-Jamesbury.
4. DeZurik.
5. Posi-Seal.
6. Zwick (Tri-Con series).
7. Milwaukee.
3. Primary/Secondary Bridge Valves, Hot and Chilled Water: Typically not permitted.
Project specific requirements to be reviewed on a case-by-case basis.
a. For each project the A/E shall submit bridge piping details to NU Project Manager
and NU Project Campus Energy Management System (EMS) Department for
review.
b. A minimum 60 psig instrument-quality air shall be piped to the bridge valve.
c. For piping details see the NU Direct Digital Control Standards.
4. Hot and Chilled Water Coil Control Valves:
a. For piping details see the NU Direct Digital Control Standards.
b. Valves shall be standard as manufactured by controls vendor, electric actuated
unless special case calls for pneumatic, to be flagged by engineer for NU review.
c. Engineer to calculate valve CV and select appropriate valve as part of design.
HYDRONIC PIPING SPECIALTIES
23 2116 - 1
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
5. Butterfly Valves (Regular Isolation Valve):
a. Resilient Seat:
i. Isolation valves 2-1/2 inch and 3 inch may be ball or butterfly. Pipe sizes
4 inch and larger shall be butterfly.
ii. Butterfly valves shall ANSI Class 150, lugged design.
iii. Butterfly valves shall be with a handle or actuator as follows:
1. 6 inch: handle.
2. 8 inches and greater: Manual-gear actuator.
iv. Acceptable Manufacturer:
1. Neles-Jamesbury, Inc.; Model No. 815L-11-2236TT.
b. Butterfly for Control Valve Duty: High Performance with Rubber Seat.
i. Carbon steel or stainless steel body
ii. ANSI Class 150 design rated for 275 psi at 100°F
1. Bubble-tight shut off with pressures in either direction to 275 psi.
2. Threaded lug type, upper and lower body bearings with thrust
bearings,
3. One piece single or double offset shaft of 316 stainless steel and
center less ground and polished to minimize bearing and packing
wear, PTFE seats.
c. Butterfly for Critical Shutoff Duty:
i. High Performance with Metal seat for steam and condensate only. No
triple offset high performance butterfly valves permitted elsewhere in
system.
d. Butterfly for Direct Buried Service:
i. Pratt Groundhog/AWWA Valves.
6. Ball Valves:
a. Isolation valves 2-1/2 inch and 3 inch may be a ball or butterfly. Pipe sizes 2
inches and smaller shall be ball.
b. Ball valves shall be bronze, 600 psig WOG, full port, with a 316 stainless steel
ball and stem.
HYDRONIC PIPING SPECIALTIES
23 2116 - 2
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
c. Insulated valves shall have a 2-1/4 in. stem extension.
d. Acceptable Manufacturers:
i. Conbraco Industries, Inc. (APOLLO®)
ii. Neles-Jamesbury, Inc.
iii. Watts Regulator Co.
7. Gate Valves: Gate valves are not permitted.
8. Circuit Setters:
a. Circuit setters shall be furnished with preformed insulation covers by the circuit
setter manufacturer.
b. Acceptable Manufacturers:
i. Bell & Gossett, ITT Fluid Handling Division.
ii. Nexus.
9. Triple Duty Valves:
a. Acceptable Manufacturers:
i. Bell & Gossett, ITT Fluid Handling Division.
ii. TACO, Inc.
10. Check Valves:
a. Check valves shall be ANSI class 150, minimum depending on the service.
Valve shall be carbon steel body and plate, metal seal, serrated raised face end
connections, and a solid body lug design with threaded holes bolted from each
end.
b. Horizontal:
i. Acceptable Manufacturers:
1. Nibco.
2. Mueller.
c. Vertical:
i. Acceptable Manufacturers:
1. Crane.
HYDRONIC PIPING SPECIALTIES
23 2116 - 3
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
2. Nibco.
3. Mueller.
d. Non Slam Type:
i. Acceptable Manufacturers:
1. Stockham, Style G.
2. Crane Duo Chek.
11. Thermometers:
a. Thermometers shall be red appearing mercury, 9-inch scale, aluminum case,
adjustable angle, and aluminum stem.
b. Wells shall be brass with a 2.5 inch extension neck. The insertion length shall be
in compliance with Table 23 2116-1.
Table 23 2116-1 Immersion Length for Thermometer Wells
Pipe Diameter,
Well Immersion Length, in.
in.
Perpendicular
Mount
Elbow Mount
3
N/A*
8½
4
N/A*
8½
6
4½-5½
8½
8
4½-5½
8½
10
4½-5½
8½
12 and larger
8½
8½
* Perpendicular mount shall not be used on 3 and 4-in. pipe. Stem cooling
effects may occur.
c. Scale Range:
i. Chilled Water: 0 to 100°F or 0 to 120°F.
ii. Hot Water: 30 to 240°F or 30 to 300°F.
d. Thermometers shall be packed in a thermal conductive compound by the Piping
Contractor. Preferred products are:
HYDRONIC PIPING SPECIALTIES
23 2116 - 4
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
i. Honeywell: Part No. 107408.
ii. Johnson Controls: F-1000-182.
iii. York: 013-00898-000.
e. Acceptable Manufacturers:
i. H. O. Trerice Co.
ii. Weksler Instruments Corporation.
12. Pressure Gauges:
a. Pressure gauges shall have a minimum 4-1/2" diameter die cast aluminum case,
glass or acrylic plastic window, phosphor bronze bourdon tube with bronze
bushed movement, recalibration from front of gauge dial and 1/4" NPT forged
brass socket
b. Gauge accuracy shall meet ANSI B40.100 Grade 1A (±1% full scale).
c. Select gauge range so that normal operating pressure is at midpoint of gauge.
d. Acceptable Manufacturers:
i. Trerice 600 Series.
ii. Weksler.
iii. Weiss.
13. Flexible Metal Hose:
a. Flexible hose shall be stainless steel, double braided.
b. Length shall be adequate to control vibration and noise. The live (flexible portion
of the assembly) and assembly lengths shall be determined by the Piping
Contractor.
c. Acceptable Manufacturers:
i. Flexicraft Industries, Chicago.
ii. Metraflex.
iii. Hyspan.
iv. Expansion Joint Systems.
v. Flexonics
HYDRONIC PIPING SPECIALTIES
23 2116 - 5
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
14. Chilled Water Flow Meters:
a. Flow meters in conjunction with RTDs to measure temperature difference are
used on the both campuses to totalize ton-hours of chilled water usage of each
building on the central chilled water system.
b. For Chilled water flow meter detail and specifications see the NU Direct Digital
Control Standards.
c. See NU Meter Requirements for both steam/condensate systems and chilled
water systems.
15. Solenoid Valves:
a. Solenoid valves are to be slow acting.
b. Acceptable Manufacturer:
i. Automatic Switch Company (ASCO).
16. Chemical Feed Pumps:
a. Acceptable Manufacturer:
i. LMI (Liquid Metronics Division) Milton Roy, Acton, MA 01720.
17. Expansion Tanks:
a. Expansion tanks shall be compression or pressurized as shown on the drawings.
b. Expansion compression tanks shall be constructed in accordance with Section
VIII, Division 1 of the ASME Boiler and Pressure code and stamped 125 psig
working pressure or greater.
c. Expansion pressurized tanks shall be pre-charged, steel with a replaceable butyl
rubber bladder. The tank shall be constructed in accordance with Section VIII of
the ASME Boiler and Pressure Code and stamped 125 psig working pressure or
greater. The tank shall include a charging valve (standard tire valve) to facilitate
on-site charging of the tank to meet system requirements.
d. Expansion tanks shall be located and piped in compliance with the drawing
details.
e. Acceptable Manufacturers:
i. AMTROL.
ii. Bell and Gossett.
iii. Armstrong.
HYDRONIC PIPING SPECIALTIES
23 2116 - 6
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
18. Acoustical Penetration Seals:
a. Provide acoustical pipe penetrations at all mechanical room penetrations in
compliance with the drawing details.
b. Option 1. The vibration isolation manufacturer may provide a molded synthetic
rubber seals between the penetration sleeve and the pipe on both sides of the
penetration. The seals shall be attached by stainless steel clamps. The
clearance between the pipe and the sleeve shall be filled with fiberglass.
c. Option 2. The vibration isolation manufacturer may provide a split seal consisting
of two bolted halves with 3/4 in. or thicker neoprene sponge bolted to the inner
faces. The seal shall be tightened around the pipe to eliminate clearance
between the inner sponge face and the piping. Concrete may be packed around
the seal to make it integral with the wall or ceiling if the seal is not in place prior
to the construction of the building member. Seals shall project a minimum 1 in.
past either face of the penetration.
d. Acceptable Manufacturers:
i. Amber/Booth Company.
ii. Mason Industries.
iii. Vibration Mountings & Controls, Inc.
19. Backflow Preventers:
a. Acceptable Manufacturers:
i. Watts Regulator Company, Series 909.
20. Baseboard Radiation Heaters:
a. Baseboard heaters shall be hot water, minimum 1-1/4 inch copper tubing.
b. A/E shall consider the design for baseboard radiation heaters with a supply water
temperature of 120 degrees F.
21. Air Separators:
a. Install on building closed loops only, not on Central Utility Plant (CUP) distributed
utilities.
b. Air separators shall be constructed in accordance with Section VIII, Division 1 of
the ASME Boiler and Pressure code and stamped 125 psig working pressure or
greater.
c. Expansion tanks shall be located and piped in compliance with the drawing
details.
HYDRONIC PIPING SPECIALTIES
23 2116 - 7
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
d. Acceptable Manufacturers:
i. AMTROL.
ii. Bell and Gossett.
iii. Armstrong.
END OF SECTION
HYDRONIC PIPING SPECIALTIES
23 2116 - 8
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
DIVISION 23 – HVAC
SECTION 23 2123 – PUMPS
1. General: This section outlines the general requirements for mechanical pumps.
2. Design Considerations:
a. It is preferred that pump speeds not exceed 1800 rpm.
b. Standby pumps should be 100% capacity.
c. For pump piping details see drawings. Strainers shall be full bore.
d. Nameplates shall include impeller diameter, rated capacity (gpm), rated head (ft)
rpm, motor horsepower, and rpm.
e. Pump suction diffusers shall be provided when the pump suction pipe is 90
degrees.
f.
Status Switch: The piping contractor shall install the differential pressure switch
status (proof) switches provided by the BAS (Building Automation System)
contractor.
g. Gauges:
i. Provide differential pressure gages at all pumps:
ii. Gauges shall be glycerine-filled.
iii. Gauges on a common hydronic system shall have consistent scale
ranges.
iv. Provide isolation “pete” plug valves on all gage connections.
v. Provide temperature indicators on the supply and return side of all heat
exchangers, chillers and boilers. All gauges shall have consistent
temperature ranges.
vi. Provide pressure gauges on the supply and discharge sides of all pumps
and heat exchangers.
3. Acceptable Manufacturers:
a. Motors up to 25 hp:
i. Bell & Gossett, ITT Fluid Handling Division.
ii. Fairbanks-Morse®, Aurora Pump Co.
iii. Armstrong.
PUMPS
23 2123 - 1
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
iv. Peerless.
v. Gould.
b. Motors 30 hp and greater:
i. Fairbanks-Morse, Aurora Pump Co.
ii. ITT A-C Pump.
iii. Armstrong.
iv. Peerless.
v. Gould.
END OF SECTION
PUMPS
23 2123 - 2
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
DIVISION 23 – HVAC
SECTION 23 2113 – STEAM PIPING
1. General:
a. This section outlines the general requirements for steam pipe and pipe fittings,
including valves, unions, and flanges.
b. Specific requirements shall be reviewed with the NU Project Manager during the
design phases of the project.
c. Materials: Piping shall be meet ASTM requirements.
2. Design Considerations:
a. General: Piping shall be routed orthogonally (no diagonal shortcuts).
b. Tracer Wire:
i. All non-electrical pipe installed below grade shall have a 12 AWG
copperhead Reinforced Tracer Wire, or equal. Tracer wire to be
accessible at each end in manholes.
ii. Tracer Wire shall be installed on the pipe as shown on the contract
drawings.
iii. Tracer wires shall terminate in each tunnel and manhole where new
utilities penetrate. Tracer wires shall be provided with labels noting what
pipe the wire is affixed to (ie. Chilled Water Supply, Pumped Condensate
Return, etc).
3. High Pressure Steam in CUP and Manholes (100 and 230 PSIG):
a. 2-1/2 inches and Smaller:
i. Pipe: ASTM A106, Grade B, extra strong, carbon steel.
ii. Fittings: ASTM A105 Grade II/ASME B16.11, 3000 lb. forged steel, socket
weld.
iii. Unions: Forged steel, 3000 lb., socket weld. Refer to Unions and Flanges
in this Section.
b. 3 inches and Larger:
i. Pipe: ASTM A106, Grade B, extra strong, carbon steel.
ii. Fittings: ASTM A234 Grade WPB/ASME B16.9, extra strong, seamless,
carbon steel weld.
HYDRONIC PIPING
23 2113 - 1
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
iii. Flanges: Class 300. Refer to Unions and Flanges in this Section.
4. Pumped Condensate and Steam Trap Condensate in CUP (100 And 230 PSIG):
a. 2-1/2 inches and Smaller:
i. Pipe: ASTM A106, Grade B, extra strong, carbon steel.
ii. Fittings: ASTM A105 Grade II/ASME B16.11, 3000 lb. forged steel, socket
weld.
iii. Unions: Forged steel, 3000 lb., socket weld. Refer to Unions and Flanges
in this Section.
b. 3 inches and Larger:
i. Pipe: ASTM A106, Grade B, extra strong, carbon steel.
ii. Fittings: ASTM A234 Grade WPB/ASME B16.9, extra strong, seamless,
carbon steel weld.
iii. Flanges: Class 300. Refer to Unions and Flanges in this Section.
5. Pumped Condensate and Steam Trap Condensate in Manholes:
a. 2-1/2 inches and Smaller:
i. Pipe: ASTM A312, 304L, Schedule 40S, seamless stainless steel.
ii. Fittings: ASTM 182, Gr. F304, ASME B16.11, 3000 lb socket-weld.
iii. Unions: 3000 lb socket-weld, stainless steel ground joint.
b. 3 inches and Larger:
i. Pipe: ASTM A312, 304L, Schedule 40S, seamless stainless steel.
ii. Fittings: ASTM A403, Gr. WP, Class S or Class W, ASME 16.9.
iii. Flanges: ASTM A182, Gr. F304, ASME B16.5, 150 lb std. with 1/16"
raised face, serrated face finish and welding neck.
iv. Bolts: Stud bolts, ASTM A193, Gr. B7.
v. Nuts: ASTM A194, Gr. 2H.
6. High Pressure Steam and Condensate (Underground) – General:
a. All underground steam and condensate shall be engineered drainable, dryable
type. Contractor fabricated piping and fittings are not allowed. No metal
components shall be exposed to earth.
HYDRONIC PIPING
23 2113 - 2
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
b. The high pressure piping design shall be based on 230 psig steam at 410
degrees F. The condensate piping design shall be based on 230psig at 410
degrees F.
c. All straight sections, fittings, anchors and other accessories shall be factory
prefabricated to job dimensions, and designed to minimize the number of field
welds. The design shall be computer analyzed by the piping system
manufacturer to determine stresses and movements of the service pipe and to
ensure that the system design is in strict conformance with ANSI B31.1 latest
edition, and stamped by a registered professional engineer licensed in the state
of Illinois. The analysis shall include piping and structures inside the manholes.
d. The piping manufacturer shall provide minimum of 25 days of on-site technical
assistance during installation of the piping. The factory representative shall be a
factory trained technician to witness requirements outlined in the installation
portion of this specification.
e. Contractor shall perform a computerized pipe stress analysis for the piping
systems in the underground steam system. Submit stress analysis report
including input data, system graphics, output data including: system forces and
moments, system deflections, system stresses, hanger, support and anchor
loading summary and other pertinent data. Analysis shall consider actual
materials of construction and a system pressure and temperature of 250 PSIG
and 450°F, base temperature is 50°F. Analysis output data shall be utilized to
select proper supports, guides and anchors to resist actual loads calculated. Pipe
stress analysis calculations to be submitted to the Engineer for review along with
the re-engineered piping system shop drawings.
7. Pipe Support Guides: Piping shall be spaced and supported at a maximum of 10 foot
intervals in conduit by insulating support-guides and to permit pipe to expand and
contract freely without stress or wear on pipe or insulation as well as provide for
drainage and free air circulation.
8. Expansion Loops, Moment Guided, Ells and Tees:
a. Prefabricated ells, loops and tees to be provided where shown on plan drawings
and to consist of pipe, insulation, and conduit conforming to the same pipe and
welding specifications as specified before herein for straight runs. Tees, anchors,
elbows and other fittings shall be factory connected and prefabricated to straight
sections whenever shipping requirements permit.
b. Expansion loops to be of proper design in accordance with stress limits indicated
by ASME Code for pressure piping, District Heating Section. Install loop piping in
conduit suitably oversized to handle the calculated pipe expansion without
damaging the insulation.
c. The piping system is designed with both expansion loops and expansion joints.
The piping system shall be designed to accommodate this requirement by
including moment guides as required for the piping system to function properly in
conjunction with expansion joints.
HYDRONIC PIPING
23 2113 - 3
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
d. Cold springing or pre-stressing piping as a means for control of expansion in any
portion of the steam system is not allowed.
9. Anchors:
a. Prefabricated plate anchors to be provided where shown and to consist of a steel
plate welded to pipe and conduit. Steel plate shall be 1/2” thick for 1” to 22”
conduit and 3/4” thick for conduit over 22” for anchors with expansion loops.
b. Concrete block to be cast over plate and conduit and to be large enough for firm
anchorage into undisturbed trench sidewalls and/or bottom. Concrete block to be
at least 36” in length and extend minimum of 12” beyond entire anchor plate. The
piping vendor shall provide detailed instructions to Contractor for oversized
anchors due to expansion joints. The Contractor shall provide oversized anchors
as detailed by the piping vendor.
10. End Seals and Gland Seals:
a. Terminal ends of conduits inside manholes, to be equipped with end seals
consisting of steel bulk head plate welded to pipe and conduit. Where there is no
anchor within 5’-0” of terminal end, conduits to be equipped with gland seals
consisting of packed stuffing box and gland follower mounted on steel plate
welded to end of conduit. End seals or gland seals to be equipped with drain and
vent openings located diametrically opposite on vertical centerline of mounting
plate and to be shipped to job site with plugs in place. Terminate conduits 4”
beyond inside face of manhole or building walls to protect any exposed piping
insulation from dampwall condensation. Refer to drawing details for further
construction and dimensional requirements
b. All end and gland seals shall be reinforced with 12” long galvanized steel sleeve
at the sealing surface to prevent compression of the outer jacket and insulation
from modular wall sealing devices. The protection sleeve shall be minimum 6
gauge thickness and shall be outside of the HDPE jacket. Where the galvanized
steel sleeve stops on the outside of the manhole, the sleeve shall be shrink
wrapped to the HDPE jacket and sealed water tight.
11. Field Joints
a. Field joints shall conform to the pipe manufacturer’s specifications.
b. Field joints shall consist of field installed mineral wool insulation banded with
stainless steel bans on the carrier pipe, field applied 10 gauge connector sleeve
on the inner conduit, field applied foam insulation, polyethylene heat shrink wrap
and split HDPE jacket at a minimum. Field joint materials and methods shall be
provided by and approved by the piping manufacturer.
12. Service Pipe (Steam and Condensate Carrier Pipe):
a. Steam:
i. 2-1/2 inches and Smaller:
HYDRONIC PIPING
23 2113 - 4
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
1. Pipe: ASTM A106, Grade B, extra strong, carbon steel.
2. Fittings: ASTM A105 Grade II/ASME B16.11, 3000 lb. forged
steel, socket weld.
3. Unions: Forged steel, 3000 lb., socket weld. Refer to Unions and
Flanges in this Section.
ii. 3 inches and Larger:
1. Pipe: ASTM A106, Grade B, extra strong, carbon steel.
2. Fittings: ASTM A234 Grade WPB/ASME B16.9, extra strong,
seamless, carbon steel weld.
3. Flanges: Class 300. Refer to Unions and Flanges in this Section.
b. Pumped Condensate
i. 2 inches and Smaller:
1. Pipe: ASTM A312, 304L, Schedule 40S, seamless stainless steel
2. Fittings: ASTM 182, Gr. F304, ASME B16.11, 3000 lb socket-weld
3. Unions: 3000 lb socket-weld, stainless steel ground joint
ii. 2-1/2 inches and Larger:
1. Pipe: ASTM A312, 304L, Schedule 40S, seamless stainless steel
2. Fittings: ASTM A403, Gr. WP, Class S or Class W, ASME 16.9
3. Flanges: ASTM A182, Gr. F304, ASME B16.5, 150 lb std. with
1/16" raised face, serrated face finish and welding neck
4. Bolts: Stud bolts, ASTM A193, Gr. B7.
5. Nuts: ASTM A194, Gr. 2H.
iii. Straight sections shall be supplied in 40-foot or random length with 6” of
piping exposed at each end for field joint fabrication where possible.
Fittings shall be ASTM A234 Grade WPC/ANSI B16.9, Schedule 40,
seamless, carbon steel butt weld fittings.
c. Service Pipe Insulation:
i. Insulation shall be mineral wool insulation fabricated in half or V-Groove
insulation sections.
HYDRONIC PIPING
23 2113 - 5
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
ii. The insulation shall be secured to the pipe by stainless steel bands.
Insulation thickness shall be as specified herein with a thermal
conductivity of not more than 0.33 at 200°F mean temperature. The
insulation shall be installed such that joints are staggered preventing a
continuous joint between the carrier pipe and the inner conduit.
d. Inner Conduit:
i. 10 gauge for conduits 26” and smaller. 6 gauge for conduits above 26”.
All conduit shall be either electric resistance welded pipe conforming to
ASTM A-135 or electric fusion welded pipe conforming to ASTM A-139.
Conduit shall be finished in prime coat finish. Where field welds and
connections are made, Contractor shall field install prime coat finish.
e. Inner Conduit Insulation and Outer Jacket:
i. Conduit insulation shall be factory-applied polyurethane foam, having
density of 2.0 to 3.0 pounds per cubic foot for all straight lengths and
fittings. The insulation thickness shall be 1” minimum. The urethane foam
shall meet ASTM C591 with the following minimum characteristic K factor
equal to 0.14, density of 2 pcf and a closed cell content of 90 to 95%.
ii. The outer jacket shall be High Density Polyethylene (HPDE) with a
minimum wall thickness of 150 mils.
f.
System Description:
i. The underground conduit system shall consist of the following minimum:
Carrier Pipe
Insulation (Mineral Wool)
Nominal Outer Conduit
16" HPS
4.0"
28"
14” HPS
4.0”
26”
12” HPS
4.0”
24”
8” HPS
4.0”
22”
6” HPS
4.0”
19”
8” CPD
2.0”
18”
6” CPD
2.0”
15”
4” CPD
1.0”
13”
3” CPD
1.0”
11”
ii. All piping inner conduit shall be insulated with 1.0” polyurethane foam
insulation with HDPE outer jacket as specified above.
HYDRONIC PIPING
23 2113 - 6
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
iii. Manufacturers:
1. Ravanco model Insul-800, Thermacor model Duo-Therm 505 or
Perma Pipe model Multi-Therm 500.
13. Unions and Flanges:
a. Unions:
i. 2 1/2 inches and Smaller:
1. Forged steel, ASTM A105 Grade 2, ASME B16.11, socket weld,
3000lb. WOG with steel to steel seats.
b. Flanges:
i. 3 inches and Larger:
1. ASTM A105, ANSI B16.5, hot forged steel flanges, welding neck
pattern. Slipon pattern flanges are not allowed. Bore dimension of
welding neck flange shall match inside diameter of connected
pipe. Use raised face flanges for mating with other raised face
flanges with self-centering flat ring gaskets. Use flat face flanges
for mating with other flat face flanges with full face gaskets.
ii. Flange pressure class indicated in respective piping service is minimum
required. Mating flange pressure class shall match pressure class of
device connected to such as valves and piping specialties. Flanged
connection will on be permitted at specialty connections such as at a
vessel or specialty valve.
c. Flange Gaskets:
i. Gasket material to be asbestos free and suitable for pressure
temperatures and fluid of piping system. Non-metallic gaskets shall be in
accordance with ANSI/ASME B16.21 and ASTM F104.
ii. Gaskets shall be equal to Flexitallic Style CG, graphite filler, 304 SS
winding, carbon steel centering ring, 0.175" thickness.
d. Bolting:
i. For all connections to valves, use bolts studs.
ii. Bolts, bolt studs, nuts and washers used on piping systems in CUP,
tunnel and manholes shall have zinc plated finish.
iii. Thread shall be in accordance with ANSI/ASME B1.1, Class 2A tolerance
for external threads and Class 2B tolerance for internal threads. Threads
shall be coarse-thread series except that alloy steel bolting 1-1/8" and
larger in diameter shall be 8 pitch thread series.
HYDRONIC PIPING
23 2113 - 7
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
iv. Threaded rods are not allowed as fastening elements on steam systems.
v. For Class 150 and Class 300 flanges at 400°F or lower temperature, use
carbon steel bolts or stud bolts conforming to ASTM A307, Grade B with
nuts conforming to ASTM A307.
vi. For Class 300 flanges at 500°F or lower temperature, use alloy steel bolts
or stud bolts conforming to ASTM A193, Grade B7 or B16, with nuts
conforming to ASTM A194, Grade 2H.
14. Valves – General:
a. General: Install valves as shown on plans, details and according to the valve
manufacturer's installation recommendations.
b. Provide chain operators for manually operated valves 4" and larger, located more
than 6'-0" above normal working surface.
15. High Pressure Steam Pumped Condensate and Steam Trap Condensate System Valves
(100 TO 230 PSIG/450°F):
a. Isolation Valves:
i. High pressure steam and condensate isolation valves shall be ANSI
Class 300.
1. Up thru 2-1/2 inches:
a. Description: Ball, full port, carbon steel body, 316 SS ball
& stem, “Xtreme” seats & PTFE seals or reinforced PTFE
seats & seals, rated for 300 psi at 600°F, threaded end
connections, 4” stem extension Jamesbury: ASTM A193
Grade B7bolts with ASTM A194 Grade 2H nuts.
b. Manufacturer and Model No.:
i. Apollo 83-540-64-04.
ii. Jamesbury 4BX-22236XT-1.
2. 3 inches and Larger:
a. Description: Butterfly ANSI Class 300, rated for 300 psi at
600°F, lugged, carbon steel body as follows:
i. Disc: nickel plated carbon steel or carbon steel.
ii. Seat: laminated Type 321 SS & graphic disc seat,
or carbon steel body with a SS welded overlay for
the body seat.
HYDRONIC PIPING
23 2113 - 8
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
iii. Shaft: A276 Type 431 stainless steel shaft.
iv. Bi-directional dead end.
v. Valve shall be triple offset.
vi. Valve shutoff shall be ANSI Class IV.
vii. All valves shall have a manual-gear actuator.
viii. All valves located more than 8 ft above the
equipment floor shall have a chain wheel.
b. Manufacturer and Model No.:
i. Jamesbury/Metso/Neles LI/SD.
ii. Zwick A1-YZA11AG.
iii. Adams MAK.
ii. Prior to shipment, valves to be hydrostatically and leak tested at the
factory. Factory hydrostatic test shall be performed at 300 psig for all
valves.
1. NU and Architect / Engineer shall have option to be present to
witness factory testing for the first valves that are 2-1/2" and
smaller and the first valves that are 3" and larger. Valve
manufacturer shall be responsible for providing transportation and
accommodations for two (2) NU representatives and one (1)
representative of the Architect / Engineer.
b. Swing Check Valves:
i. 2” and Smaller: ASTM B62, cast steel body, threaded ends, regrinding, Ypattern swing type, renewable TFE seat disc, Class 300 (300 psi WOG),
conforming to MSS SP-80.
c. Globe Valves:
i. 2" and Smaller: ANSI Class 600, steel body, stainless steel disc & seat
ring, threaded ends.
ii. 2-1/2" and Larger: ANSI Class 300, steel body, stainless steel disc & seat
ring, butt weld ends, constructed in accordance with ASME B16.34
d. Pressure Equalizing Valves
i. Use 1-1/2" globe valve for use on valves 6" to 10".
ii. Use 2" globe valve for use on valves larger than 12".
HYDRONIC PIPING
23 2113 - 9
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
e. Drain Valves:
i. Gate valves as specified above with hose thread adapter and cap.
Provide 1" minimum drain valve except strainer blowdown valves to be
blowdown connection size. Drain valves shall be provided with short
threaded nipple and cap.
16. Pressure Equalizing Valves:
a. Provide pressure equalizing valves on valves in the following locations:
i. High pressure steam (230 psig) shut-off valves 3" and larger for
supervised warm-up.
END OF SECTION
HYDRONIC PIPING
23 2113 - 10
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
DIVISION 23 – HVAC
SECTION 23 2116 – STEAM PIPING SPECIALTIES
1. General: This section outlines the general requirements for steam piping specialties.
2. Design Considerations:
a. Provide chain-wheel operators for valves 6 inches and larger mounted over 8
feet above floor.
b. Furnish gear operators for valves 8 inches and larger.
c. Isolation valves 2-1/2 inch and 3 inch may be a ball or butterfly. Pipe sizes 2
inches and smaller shall be ball valves.
3. Butterfly Valves:
a. Butterfly for Critical Shutoff Duty: High Performance with metal seat for steam
and condensate only. No triple offset high performance butterfly valves permitted
elsewhere in system.
4. Gate Valves: Gate valves are not permitted.
5. Pressure Gauges:
a. Pressure gauges shall have a minimum 4-1/2" diameter die cast aluminum case,
glass or acrylic plastic window, phosphor bronze bourdon tube with bronze
bushed movement, recalibration from front of gauge dial and 1/4" NPT forged
brass socket
b. Gauge accuracy shall meet ANSI B40.100 Grade 1A (±1% full scale).
c. Select gauge range so that normal operating pressure is at midpoint of gauge.
d. Acceptable Manufacturers:
i. Trerice, others equal to Trerice 600 Series.
ii. Weksler.
iii. Weiss.
6. Steam Pressure Reducing Valves:
a. The maximum sound pressure level of a valve shall not exceed 92 dBA.
b. The Federal (OSHA) standard for permissible noise exposure is as follows:
HYDRONIC PIPING SPECIALTIES
23 2116 - 1
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
Duration,
Hours per Day
Sound Level, dBA
8
90
6
92
4
95
7. Pressure Reducing Stations (PRS):
a. General: The justification for a single stage PRS is space and cost.
b. Preferred. Each PRS shall be two stage with the main and bypass valves in
each stage as follows, and piped in compliance with the drawing details.
i. Main Valve: Fisher type 667-E-4160K globe valve with cast iron body,
SST trim, PTFE packing, fail closed diaphragm actuator, and a pneumatic
controller with proportional plus reset control. Low bleed assembly
(MIZER) shall be included with the controller.
ii. Bypass Valve: Fisher type 92B pilot-operated regulator with a cast iron
body, and SST trim.
c. Alternate. Each PRS shall have one main valve in parallel with one bypass valve
piped in accordance to the drawing details.
i. Two inch and smaller valves shall be screwed; 3-inch and larger valves
shall be class 250 flanged.
d. Approved Manufacturers:
i. Fisher Controls International, Inc.
ii. Spence Engineering Co.
8. Ball Valves:
a. Ball valves shall be bronze, 600 psig WOG, full port, with a 316 stainless steel
ball and stem and 250 psi steam trim.
b. Insulated valves shall have a 2-1/4 inch stem extension.
c. Acceptable Manufacturers
i. Conbraco Industries, Inc. (APOLLO®)
ii. Neles-Jamesbury, Inc.
iii. Watts Regulator Co.
HYDRONIC PIPING SPECIALTIES
23 2116 - 2
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
9. Condensate Receiver Sets:
a. Condensate receiver sets shall have two 100% capacity pumps.
b. Pump motors shall be TEFC, 1800 rpm maximum (3600 rpm not acceptable).
c. Condensate pumps shall have 2 NPSH pumps.
d. Acceptable Manufacturers:
i. Peerless.
ii. Domestic.
iii. Skidmore.
iv. Weinman.
v. Sterling.
vi. Hoffman.
vii. Mepco.
viii. Shipco.
10. Steam Traps:
a. A/E shall size each steam trap required for projects.
b. Traps shall be inverted bucket or float and thermostatic (F&T).
c. Orifice traps are not permitted.
d. Acceptable Manufacturers:
i. Armstrong International, Inc.
ii. Spirax Sarco, Inc.
11. Steam / Condensate Flow Meters:
a. For condensate meter detail and specifications see the NU Direct Digital Control
(DDC) Standards.
b. See NU Meter Requirements for steam/condensate systems.
END OF SECTION
HYDRONIC PIPING SPECIALTIES
23 2116 - 3
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
This page intentionally left blank
HYDRONIC PIPING SPECIALTIES
23 2116 - 4
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
DIVISION 23 – HVAC
SECTION 23 3114 – DUCTWORK
1. General: This section outlines the general requirements for ductwork. Specific
requirements shall be coordinated with the NU Project Manager during the design
phases of the project.
2. Design Considerations:
a. Fibrous glass ductwork is not permitted.
b. Lined ductwork is not permitted.
c. When space permits, round spiral ductwork is preferred over rectangular
ductwork.
d. Laboratory exhaust ductwork shall be 316 stainless steel and not 304 stainless
steel. Engineer of Record shall evaluate other ductwork material options based
on use and dilution of system.
e. Duct systems must be designed, not just sized by use of the Trane Ductulator or
the friction chart. Procedures to follow are the 2013 ASHRAE Handbook of
Fundamentals, Chapter 21 (Duct Design), page 21.21 (HVAC Duct Design
Procedures).
3. Ductwork Construction:
a. Round, flat oval and rectangular ductwork shall be fabricated in accordance with
SMACNA “HVAC Duct Construction Standards - Metal and Flexible,” Third
Edition, 2005, except as follows:
i. General:
1. Galvanized outdoor ductwork shall have a G90 galvanized
coating per ASTM Standard A525. G60 coating is not permitted.
2. Laboratory exhaust ductwork shall be 316 stainless steel.
3. Laboratory exhaust ductwork must be welded construction.
4. Show all Volume dampers on the contract drawings.
ii. Round:
1. Round ducts shall be spiral or longitudinal with fully welded
seams. Longitudinal seams are not permitted where ductwork is
exposed. Snap-lock seams are not permitted.
DUCTWORK
23 3114- 1
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
2. Acoustical lined round ductwork shall have an inner perforated
liner.
a. Acceptable Product: Acoustic-K27, United McGill Corp.
3. Crimp joints are not permitted.
4. Pleated elbows are not permitted.
5. Adjustable elbows are not permitted.
6. Use radius elbows with minimum centerline radius to width or
diameter ratio of 1.5.
a.
Where 1.5 radius elbows do not fit use 1.0 radius elbows.
b. Where 1.0 radius elbows do not fit use square throat
elbows with full splitter vanes.
iii. Rectangular:
1. Acoustical lined rectangular ductwork is not permitted.
2. Ductwork thickness shall be 22 gauge minimum, except where
any welding other than longitudinal seams is performed, the
thickness shall be 18 gauge minimum.
3. Button punch snaplock seams are not permitted.
4. Transverse (girth) joints T-4, 9, 17, 18, 19, 20, and 23 not
permitted.
5. Mitered elbows with turning vanes are not permitted. Use radius
elbows.
iv. Flat Oval:
1. SMACNA Type 1 reinforcement (Figure 3-6 of SMACNA’s duct
construction standards) is not permitted.
2. Flat oval ductwork is not permitted for exhaust systems.
4. Ductwork Installation:
a. Hangers and supports shall be in accordance with SMACNA “HVAC Duct
Construction Standards - Metal and Flexible,” third edition, 2005, except as
follows:
i. Wire hangers are not permitted.
DUCTWORK
23 3114- 2
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
ii. Flexible duct shall be installed and supported in accordance to the
SMACNA “HVAC Duct Construction Standards - Metal and Flexible,”
second edition, 1995.
b. SMACNA HVAC Duct Construction Standards, 1995, Figure 2-15: Flexible duct
elbows at the diffuser as shown is not permitted. Elbows must be sheet metal
(see drawing details).
c. Provide acoustical duct silencers at fan room duct penetrations.
d. Branch connections shall be in compliance with the drawing details. Extractors
and splitter dampers are not permitted.
5. Sealing:
a. Ductwork shall be sealed at the factory and remain sealed at all times until
installed. Ductwork must be sealed at all times even if being worked on. Seals
can be removed only during immediate installation and must be restored
immediately upon non-work activity. Ductwork being worked on shall be sealed
at the end of each work day.
b. Ductwork shall be sealed in compliance with Table 23-3114-1. Pressuresensitive tape shall not be used as the primary sealant on metal ducts.
Table 23-3114-1 – Minimum Duct Seal Levelsa
Duct Location
Supply
Exhaust
Return
< 2 in.
wg
> 2 in. wg
Outdoors
A
A
A
A
Unconditioned
Spaces
B
A
B
B
Conditioned
Spaces
C
B
B
B
A
A
B
B
(concealed
ductwork)
Conditioned
Spaces
(exposed
ductwork)
DUCTWORK
23 3114- 3
NORTHWESTERN UNIVERSITY
Technical Standards
6.
Issuance Date: 01.01.2014
a
See Table 23-3114-2 for definition of seal level.
Table 23-3114-2 – Duct Seal Levelsa
Seal
Level
A
Sealing Requirements
All transverse joints, longitudinal seams,
and ductwork penetrations.
B
All transverse joints and longitudinal seams.
C
Transverse joints only
a
Transverse joints are two ducts orientated perpendicular to flow.
Longitudinal seams are joints orientated in the direction of airflow.
Duct wall penetrations are openings made by screws, fasteners,
Round and flat oval spiral lock seams need not be sealed prior
assembly, but may be coated after assembly to reduce leakage. All
other connections are considered transverse joints, including but
not limited to spin-ins, taps, and other branch connections, access
door frames, and duct connections to equipment.
a. Gasketed flanges (SMACNA Joints T-24, T-25, and proprietary slip-on flanges)
shall be sealed with a mastic.
b. Acceptable Products: United Duct Sealer (United McGill Corp.) Hardcast, McGill
AirSeal, Ductmate, Mon-Eco Industries or H.B. Fuller/Foster
7. Leakage Tests:
a. Leakage tests shall be conducted in accordance with the SMACNA HVAC Air
Duct Leakage Test Manual, 1st edition, 1985. Section 3 (General Procedures),
Section 5 (Test Apparatus, and Section 6 (Test Reports). Positive and negative
pressure ductwork shall be tested in the positive mode.
b. Tests shall be completed before insulation is applied and ducts are concealed by
building enclosures. Tests may be conducted in sections.
c. Leakage tests shall be witnessed by the University.
d. Leakage shall not exceed the values in Table 23-3114-3
DUCTWORK
23 3114- 4
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
Table 23-3114-3 – Allowable Leakage Rates, cfm/100 ft2 Surface Area
Location
Test
Pressure,
in. wg
Low Pressure
Ductwork
Ductwork
Round
Ductwork
Flat Oval
Ductwork
2
9.4
4.7
4.7
4
14.8
7.4
7.4
a
All Other
Ductwork
Rectangular
b
a
Supply Ductwork: Ductwork downstream of VAV/CAV Terminals
Return Ductwork: Ductwork upstream of VAV/CAV Terminals.
b
Supply, Return, and Exhaust Ductwork.
END OF SECTION
DUCTWORK
23 3114- 5
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
This page intentionally left blank
DUCTWORK
23 3114- 6
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
DIVISION 23 – HVAC
SECTION 23 3314 – DUCTWORK SPECIALTIES
1. General: This section outlines the general requirements for ductwork specialties and
accessories.
2. Flexible Duct:
a. Flexible duct shall be Class 1 “Air Duct” manufactured in compliance with UL
181. Each piece of “Air Duct” shall be UL labeled.
b. Acceptable Manufacturers:
i. Thermaflex, Model M-KE.
ii. Casco.
iii. Flexmaster, Type 6.
c. “Air Connectors” manufactured in accordance to US 181 are not permitted
because “Air Connectors” are less durable than “Air Ducts.”
3. Combination Fire/Smoke Dampers:
a. Combination fire/smoke dampers shall be installed at combination fire and
smoke zone boundaries.
b. Fire/smoke dampers shall be multi-blade, UL555 and UL 555S labeled. Curtaintype dampers are not permitted.
c. Combination fire/smoke dampers shall have a 3-hour rating.
d. Dampers shall have a Leakage Class III label. Seals shall be metal-to-metal.
e. Dampers shall be rated for 4000 fpm minimum.
f.
Fire dampers shall incorporate a reusable electric McCabe™ link with an
external manual reset lever (see drawing details). The releasing device shall be
24 Vdc in compliance with UL 873. The resettable link shall be 280ºF, UL 33
listed.
g. Combination fire/smoke dampers shall be installed in accordance with the
manufacturer’s installation instructions.
h. Combination smoke/fire dampers shall have access panels on each side of the
damper in compliance with the drawing details. Access panels shall have a
single pane Plexiglas viewport.
i.
Acceptable Fire/Smoke Damper Manufacturers
DUCTWORK SPECIALTIES
23 3314 - 1
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
i. Prefco Products, Inc., Model 5010 with a manual actuator.
ii. Air Balance.
iii. Greenheck.
iv. Nailor.
v. Cesco.
vi. Ruskin.
j.
The maximum sizes for UL listed 1 1/2 hour rated fire/smoke dampers is
tabulated below. For 3 hour rated dampers the maximum vertical damper is 30”
x 30”. No multiple sizes or horizontal dampers are UL listed as of the date of this
standard.
UL Listed Prefco Model 5010 Fire/Smoke Dampers
Orientation
Single
Section
Multiple Section
Single Section
Vertical
36” W x 45” H
36” W x 45” H
72” W x 45’ H (2 sections)
30” W x 30” H
120” W x 30” H (4
sections)
36” W x 42” H
Horizontal
31” W x 33” H
Multiple Section
26” W x 42” H
72” W x 84” H (4
sections)
52” W x 42” H (2
sections)
4. Fire Dampers:
a. Fire dampers shall be installed at all duct penetrations through fire rated walls
and floors.
b. Fire dampers shall be multi-blade, UL 555 labeled. Curtain dampers are not
permitted.
c. Fire dampers shall have a either a 1-1/2 or 3-hour rating depending on the rating
of the wall.
d. Fusible links shall be 212ºF, UL listed.
e. Fire dampers shall be installed in accordance with the manufacturer’s installation
instructions.
DUCTWORK SPECIALTIES
23 3314 - 2
NORTHWESTERN UNIVERSITY
Technical Standards
f.
Issuance Date: 01.01.2014
Fire dampers shall have access panels on each side of the damper in
compliance with the drawing details. Access panels shall have a single pane
Plexiglas viewport.
5. Smoke Dampers:
a. Smoke dampers shall be installed at all duct penetrations through smoke zone
boundaries not having a fire resistance rating.
b. Smoke dampers shall be multi-blade, UL555 and UL555S labeled. Curtain-type
dampers are not permitted.
c. Dampers shall have a Leakage Class III label. All seals shall be metal-to-metal.
d. Dampers shall be rated for 4,000 fpm minimum.
e. Damper actuators shall be electric.
f.
Smoke dampers shall be installed in accordance with the manufacturer’s
installation instructions.
g. Combination smoke/fire dampers shall have access panels on each side of the
damper in compliance with the drawing details. Access panels shall have a
single pane Plexiglas viewport.
6. Flexible Connections:
a. Flexible connections shall be 0.024 in. thick, 30 oz/yd2 glass fabric doublecoated with polychloroprene.
b. Acceptable Product:
i. Ventfabrics, Inc., Ventglas.
7. Access Panels:
a. Access panels shall be as shown on the project drawings and as follows:
i. upstream of modulating dampers;
ii. upstream and downstream of airflow measuring stations;
iii.
upstream and downstream of duct mounted coils;
iv. upstream of humidifiers; and
v. between the VAV terminal units and the reheat coil, and downstream of
the VAV terminal unit reheat coils.
DUCTWORK SPECIALTIES
23 3314 - 3
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
b. Access panels shall be located upstream and downstream of fire dampers,
smoke dampers, and combination fire/smoke dampers to permit inspection and
maintenance of the damper and its operating parts.
c. Access panels shall be 16 in. by 16 in minimum, or 16 in. by the duct
height/width.
8. Louvers:
a. Minimum Louver depth: 6 inches.
b. The minimum free area of a 48 in. square louver shall be 45%.
c. The water penetration of outdoor air intake louvers shall be less than 0.2
oz/SF/0.25 hour based on laboratory tests in compliance with AMCA Standard
500.
d. The face velocity of individual louvers or each louver in a bank of louvers should
not exceed the following values (Source: ASHRAE Handbook of Fundamentals,
2013, Table 6, Page 21.17. Review project specific requirements with NU
Project Manager and take into consideration snow infiltration.
i. Outdoor Air Intake:
1. 7000 cfm and greater: 400 fpm maximum (Peak velocity not
average velocity).
2. Less than 700 fpm: see Table 23-3314-1.
ii. Exhaust:
1. 5000 cfm and greater: 500 fpm maximum.
2. Less than 500 fpm: See Table 23-3314-1.
Table 23-3314-1
Outdoor Air Intake Louver
Exhaust Louver
CFM
per
Louver
Maximum
Face Velocity,
fpm
Minimum Face
Area, SF
Maximum
Face Velocity,
fpm
Minimum Face
Area, SF
1000
170
6
190
5.5
2000
250
8
310
6.5
3000
300
10
400
8
4000
330
12
450
9
DUCTWORK SPECIALTIES
23 3314 - 4
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
Table 23-3314-1
Outdoor Air Intake Louver
Exhaust Louver
CFM
per
Louver
Maximum
Face Velocity,
fpm
Minimum Face
Area, SF
Maximum
Face Velocity,
fpm
Minimum Face
Area, SF
5000
380
13.5
500
10
6000
390
15.5
500
12
7000
400
17.5
500
14
9. Sound Attenuators:
a. A noise calculation is required for both the supply and return ductwork of all air
handling units, and the supply and return ductwork of all return/exhaust fans.
b. For each system the minimum attenuator DIL (Dynamic Insertion Loss) in each
octave band shall be in compliance with Table 23 3314-2. The self-noise of the
attenuator must be at least 5 dB less than the silenced sound power level in
each octave band. A schedule should be issued with the drawings specifying
the noise attenuation required in each of the following octave band frequencies
(Hz): 125, 250, 500, 1000, 2000, 4000, and 8000, similar to the following:
Table 23 3314-2 – Minimum Required Attenuator DIL (dB, re 10-12 watts)
System
Octave Band Center Frequency
125
250
500
1000
2000
4000
8000
c. Provide acoustical duct silencers at conference rooms and classrooms, 3 foot
length minimum. Consider acoustical duct silencers at offices. Review and
verify specific requirements with NU Project Manager.
d. Acoustical lined round ductwork is permitted, but the duct must have an inner
perforated liner.
e. Acoustical lined rectangular ductwork is typically not permitted. Review and
verify specific requirements with NU Project Manager.
f.
Acceptable Flexible Duct Manufacturers:
i. Industrial Acoustics Company.
ii. Semco, Aerosonics.
DUCTWORK SPECIALTIES
23 3314 - 5
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
iii. United McGill.
iv. Aeroacoustic.
v. Commercial Acoustics.
vi. Vibro-Acoustics, VAW Systems.
vii. Ruskin Sound.
viii. Dynasonics.
g. Sound Attenuators shall be tested in accordance with ASTM E-477-99 silencer
test standard in aero-acoustic test facility which is NVLAP accredited for ASTM
E-477-99 Standard.
END OF SECTION
DUCTWORK SPECIALTIES
23 3314 - 6
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
DIVISION 23 – HVAC
SECTION 23 3400 – FANS
1. General:
a. This section outlines the general requirements for mechanical fans.
b. Specific requirements shall be coordinated with the NU Manager during the
design phases of the project.
2. Design Considerations:
a. Stainless steel and fiberglass reinforced plastic (FRP) are available.
b. For fan coatings, consult with fan manufacturers.
3. Packaged Air Handling Units:
a. Review fan assembly on a case-by-case basis with NU Project Manager.
4. Centrifugal Fans:
a. Fans with wheel diameters 36 inches and smaller shall be Class II minimum.
Fans greater than 36 inches shall be Class III minimum.
b. Bearings shall be mounted in split-pillow blocks with grease fittings. Bearings
shall be designed for a minimum L10 (rating) life of 100,000 hours as defined by
ANSI/AFBMA Standard 9.
c. Vibration isolation base shall have seismic restraints.
d. Fan ratings shall be tested and certified in accordance with AMCA Standards
211 and 311 and fans shall bear AMCA Seal
e. Provide OSHA Compliant belt and shaft guards for belt driven fans.
f.
Acceptable Manufacturers:
i. Barry Blower.
ii. Buffalo Forge Div., The Howden Fan Co.
iii. Chicago Blower Corp.
iv. Greenheck.
v. Industrial Air.
vi. Twin City.
FANS
23 3400- 1
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
5. Plenum Fans:
a. Plenum Fans may be used for static pressure 6 inches SP and below.
b. Fans shall be airfoil centrifugal type designed for industrial duty and suitable for
continuous operation. Fans shall be single width, single inlet, arrangement 3.
c. Air handling quality, heavy-duty, grease lubricated, pillow block, self-aligning ball
or roller type. Bearings shall be selected for minimum life (ABMA L10) of not
less than 100,000 h operation at maximum cataloged operating speed.
d. Acceptable Manufacturers:
i. Barry Blower.
ii. Chicago Blower Corp.
iii. Greenheck.
iv. Twin City.
6. Fan Array:
a. Fan array system shall consist of multiple, direct driven, arrangement 4 plenum
fans constructed per AMCA requirements for duty specified. Fans shall be
selected to deliver scheduled airflow quantity at scheduled operating total static
pressure and scheduled fan/motor speed. Fan array shall be selected to operate
at system total static pressure that does not exceed 90% of scheduled fan’s peak
static pressure producing capability at scheduled fan/motor speed.
b. Fan intake wall, inlet funnel, and motor support structure shall be powder coated
for superior corrosion resistance. Motors shall be standard pedestal mounted
type, T-frame motors selected at specified operating voltage, rpm, and efficiency
as needed to meet performance requirements. Motors shall include isolated
bearings or shaft grounding. Each fan/motor cartridge shall be dynamically
balanced to meet AMCA standard 204-96, category BV-5, to meet or exceed
Grade 2.5 residual unbalance.
i. Fan array shall provide uniform air flow and velocity profile across entire
air way tunnel cross section. Airflow and velocity shall not exceed
scheduled cooling coil and/or filter bank face velocity when measured at
a point 12 inches from intake side of fan wall array intake plenum wall,
and distance of 48 inches from discharge side of fan wall intake plenum
wall.
ii. Provide partition between fans to minimize system effect.
iii. Provide structural frame to support upper fans with solid floor panel
partition between fans as shown on drawings to minimize system effect.
FANS
23 3400- 2
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
iv. Each fan in array shall be provided with back flow prevention means that
produces less than 0.10 inches wc of static pressure drop and/or system
effect when that fan is enabled. Any such system effects and/or pressure
drops shall be submitted and included as component in determining fan
system total static pressure as submitted. Manufacturer's pressure drop
ratings of any such equipment, developed from straight run test
conditions will not be accepted.
v. Provide 2 separate variable frequency drives for fan array. Each VFD
shall control half of fans in array. Provide one backup VFD for air
handling unit.
vi. Fan array shall be sized such that upon single fan failure, remaining fans
could ramp up and provide same 100% design capacity.
vii. Technology with multiple fans having individual VFDs may be
considered.
viii. Provide local electrical disconnect for each fan.
ix. Contractor shall provide all wiring to air handling unit components that
require power.
c. Acceptable Manufacturers:
i. AcoustiFLO.
ii. Greenheck.
iii. Hunt Air.
iv. Twin City.
7. Laboratory Exhaust Fans – Centrifugal:
a. Lab Fume hood fans shall be with coating recommended for application, drive
arrangement 10 or 1, AMCA Class C spark resistant construction
b. Air handling quality, heavy-duty, grease lubricated, pillow block, self-aligning ball
or roller type. Bearings shall be selected for minimum life (ABMA L10) of not
less than 100,000 h operation at maximum cataloged operating speed.
FANS
23 3400- 3
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
c. Acceptable Manufacturers:
i. Barry Blower.
ii. Chicago Blower Corp.
iii. Greenheck.
iv. Twin City.
END OF SECTION
FANS
23 3400- 4
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
DIVISION 23 – HVAC
SECTION 23 3600 – AIR TERMINAL DEVICES
1. General: This section outlines the general requirements for air terminal devices.
2. Design Considerations:
a. Fan powered terminals are not generally permitted. Fan powered terminal for
final diffuser filtering applications may be considered with NU Project Manager
approval.
b. VAV terminals shall have a reheat coil with access panels upstream and
downstream.
3. VAV Terminals:
a. Terminal units shall be variable volume, single duct, pressure independent,
direct digital control (DDC).
b. Terminal unit shall be furnished with a hot water reheat coil. The reheat coil
control valve shall be DDC controlled by the terminal box controller. For reheat
coil piping details see drawings.
c. The box casing shall be 22 gauge minimum; the damper assembly shall be 16
gauge minimum.
d. Box manufacturer shall provide an access door between the terminal unit and
the reheat coil.
e. The box manufacturer shall furnish the multi-point, center averaging sensor.
f.
The control contractor shall furnish the control components to the terminal box
manufacturer for factory mounting. The box manufacturer shall include the cost
to mount the control components.
g. Acceptable Manufacturers
i. Price.
ii. Nailor.
iii. Titus Products.
iv. Tuttle & Bailey.
v. Phoenix electric actuated in laboratory buildings.
AIR TERMINAL DEVICES
23 3600- 1
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
4. Exhaust Air Terminals:
a. Basis-of-Design: Titus Products, Model ECV.
b. Acceptable Manufacturers:
i. Price.
ii. Nailor.
iii. Tuttle & Bailey.
iv. Phoenix electric actuated in laboratory buildings.
5. Diffusers:
a. The diffuser style and color shall be reviewed by the NU Project Manager.
b. Grilles, not diffusers, shall be specified, and duct dampers used for balancing.
Show all balancing dampers on the drawings.
c. VAV ceiling diffusers shall be in accordance with Table 23 3600 – 1.
Table 23 3600-1 VAV Ceiling Diffusers
Metalaire
Titus
Tuttle & Bailey
5000-IV
--
RC
5800A
--
DA
--
TMRA
P3
5800
--
DM
Note: Model numbers on the same line are comparable diffusers.
d. Diffusers shall be tested in accordance with ANSI/ASHRAE Standard 70, current
edition.
e. Acceptable Manufacturers:
i. Metalaire Industries, Inc.
ii. Titus Products.
iii. Tuttle & Bailey.
iv. Price.
AIR TERMINAL DEVICES
23 3600- 2
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
v. Krueger.
vi. Enviro-Tec (ETI).
vii. Nailor.
END OF SECTION
AIR TERMINAL DEVICES
23 3600- 3
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
AIR TERMINAL DEVICES
23 3600- 4
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
DIVISION 23 – HVAC
SECTION 23 4114 – FILTERS
1. General:
a. This section outlines the general requirements for filters.
b. Specific requirements shall be coordinated with the NU Project Manager during
the design phases of the project.
2. Design Considerations:
a. General:
i. It is preferred that air handling units have the following filter sections,
where efficiency is the ASHRAE atmospheric dust-spot efficiency
determined by ASHRAE Standard 52.2-2007.
1. Prefilter: 25-30% efficiency minimum MERV 7
2. Final: 80-90% efficiency minimum MERV 13
ii. Heat recovery coils must have prefilters.
3. Prefilters: Prefilters shall be extended surface pleated panel 4 inches in depth.
Efficiency shall be 25-30% minimum, MERV 7 where efficiency is the atmospheric dust
spot efficiency determined by ASHRAE Standard 52.2-2007.
4. Final Filters: Final filters shall be extended surface, non-supportive pocket type.
Efficiency shall be 80-90% minimum, MERV 13 where efficiency is the atmospheric dust
spot efficiency determined by ASHRAE Standard 52.2-2007.
5. Filters shall have UL, Class I or Class II Listing
6. Filters on 100% OA units for before and after the preheat coil depending on winter and
summer (Snow loading)
7. Use Slide out filter racks when total CFM is 5000 CFM or under, Use Lift out filter
frames for units above 5000 CFM.
8. For slide out filter racks, each housing shall have door on both sides to facilitate
changing filters. Doors shall have perimeter gaskets to minimize air leakage, shall be
hinged, and shall have cam-lock or lever handle latches to secure the door
9. For lift out filter frames, the frames shall be minimum 16 gauge galvanized construction
with provisions for assembly in a bank. Frames shall be suitable for filters scheduled
and incorporate gaskets and spring clips to prevent air bypass.
FILTERS
23 4114- 1
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
10. Three (3) sets of pre-filters shall be provided, one (1) set for use during construction,
one (1) set for building turnover to owner, and one (1) spare set. Two (2) sets of after
and final filters shall be provided: one (1) set for building turnover to owner and one (1)
spare set.
11. Bag-In / Bag-Out filter housings shall be provided with isolation dampers/valves on each
side.
12. Filter pressure drop gauges shall be across each bank of filters.
END OF SECTION
FILTERS
23 4114- 2
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
DIVISION 23 – HVAC
SECTION 23 5214 – PRIMARY HEATING EQUIPMENT
1. General: This section outlines the general requirements for primary heating equipment.
2. Design Considerations:
a. Fired boilers are used in the Central Utility Plant (CUP) for both the Chicago and
Evanston campuses. The primary heating equipment is for convertors from
steam to heating hot water.
b. Convertor (shell and tube heat exchanger)
i. Shell and tube type with removable copper U-tube bundle, steel shell,
tube sheets, and heads.
ii. Heat exchangers shall be constructed and stamped in accordance with
the latest ASME Code for Unfired Pressure Vessels. Each unit shall be
registered with National Board of Boiler and Pressure Vessel Inspector.
iii. Heat exchangers shall have tube side working pressure of125 psi and
test pressure of 250 psi with shell side working pressure of 150 psi and
test pressure of 195 psi.
c. Acceptable Manufacturers:
i. Bell and Gossett.
ii.
Armstrong.
iii.
Adamson.
iv.
Taco.
END OF SECTION
PRIMARY HEATING EQUIPMENT
23 5214 - 1
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
This page intentionally left blank
PRIMARY HEATING EQUIPMENT
23 5214 - 2
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
DIVISION 23 – HVAC
SECTION 23 7313 – PACKAGED AIR HANDLING UNITS
1. General: This section outlines the general requirements for packaged air-handling units
(AHU).
2. Design Considerations – Systems 3500 CFM and Smaller:
a. Units shall be factory packaged.
b. Systems shall be constant air volume (CAV). Engineer of Record shall evaluate
the use of Variable Air Volume (VAV) with Life cycle analysis.
c. Air handling units are to be designed with 20 percent additional capacity for
future expansion.
d. Unit shall be 16 gauge, galvanized steel, bolted standing seam construction.
Galvanized steel shall have a G-90 coating. A G-60 coating is not permitted.
e. The base shall be welded 2-1/2 in. minimum structural channel construction with
full walk-on G-90 galvanized steel floors in all sections. No paint is permitted.
f.
Unit shall have a double wall casing with 2 in. insulation minimum and in
compliance with ASHRAE/IES Standard 90.1-2010, “Energy Efficient Design of
New Buildings Except New Low-Rise Residential Building,” Table 9-2. The fan
section shall have a perforated liner. All other sections shall have a solid inner
liner.
g. The condensate drain pan shall be 16 gauge, 304 stainless steel. Drain pans are
to be insulated double bottom construction.
h. Fans: Refer to Section 23 3400.
i.
Filters: Filters shall be in compliance with Section 23 4114 and removable
through access doors without removing the doors.
j.
Economizer Dampers: An economizer damper section shall not be furnished
with the air handling unit. Economizer dampers shall be furnished by the
temperature control contractor and installed in the ductwork by the sheet metal
contractor.
k. Coils: Refer to Section 23 8216.
l.
Humidifier: Refer to Humidification Equipment Section 23 8413.
i. The humidifier control valves , strainers and valves shall be outside of the
AHU (outside of the airstream)
PACKAGED AIR HANDLING UNITS
23 7313- 1
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
m. Access Sections:
i. Access sections shall be 24 in. minimum and shall have access doors on
both sides.
ii. Access doors shall have a single pane Plexiglas viewport. Access panels
are not permitted.
iii. Actual height of view port window to consider concrete pad height and be
5’-0” above finished floor to bottom of view port window. View port
window to be 12 inch x 10 inch minimum size.
n. The housekeeping pad shall be adequate to install the cooling coil drain pan trap
in compliance with the drawing details.
o. Acceptable Manufacturers:
i. AAON.
ii. Buffalo Air Handling Co.
iii. ETL.
iv. Hunt Air.
v. Ventrol.
END OF SECTION
PACKAGED AIR HANDLING UNITS
23 7313- 2
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
DIVISION 23 – HVAC
SECTION 23 7323 – FACTORY-FABRICATED CUSTOM AIR HANDLING UNITS
1. General:
a. This section outlines the general requirements for factory-fabricated custom air
handling units (AHU’s).
b. Specific requirements shall be coordinated with the NU Project Manager during
the design phases of the project.
2. Design Considerations:
a. Air handling units greater than 3500 cfm shall be factory built-up air handling
units.
b. Air handling units shall be double wall, 4-in. thick, acoustically lined, with a 22gage minimum galvanized steel inner liner. The fan section shall be perforated;
the other sections shall be solid. Perforated fan section with stand-offs for
insulation liner with Tedlar film thickness of 1.0.
c. Cooling coils shall have a 16 gauge, 304 stainless steel drain pan. Drain pans
are to be insulated double bottom construction.
d. The cooling coil drain pan shall have a trap in compliance with the drawing
details. When the housekeeping pad is not adequate for the trap, the cooling
coil(s) shall be mounted on a 304 stainless steel stand to permit installation of
the trap.
e. Coils shall have slide out racks and not face bolted.
f.
Seal coat mechanical room concrete floors and equipment pad underneath AHU.
3. Fans: Fan shall be in compliance with Section 23 3400.
4. Filters: Filters shall be in compliance with Section 23 4114.
5. Humidifier. Refer to Humidification Equipment Section 23 8413.
a. The humidifier control valves , strainers and valves shall be outside of the AHU
(outside of the airstream)
b. Do not locate the humidifier upstream of the fan section. The preferred location
for the humidifier section is downstream from the fan section.
c. When the humidifier is located in the air handling unit it should be located 18
inches downstream of the heating coil and a minimum 3 ft upstream of the
cooling coil.
FACTORY FABRICATED CUSTOM AIR HANDLING UNITS
23 7323- 1
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
6. Plenums:
a. Each plenum between components shall have an access door with a view port
on both sides of the unit. Doors shall open against pressure and the view port
shall be 12 inch x 12 inch minimum size, double wire thermal pane. Actual height
of view port window to consider concrete pad height and be 5’-0” above finished
floor to bottom of view port window.
i. Acceptable access door manufacturers are:
1. Cesco Products.
2. Semco Inc.
b. Plenums shall have a fluorescent fixture with a moisture-proof cover. All
penetrating conduit shall be sealed internally. Low temperature electronic ballast
required for fluorescent lights. Provide a light switch for each plenum.
c. Plenums shall have outside each door a 120 VAC outlet with waterproof cover.
7. Dampers:
a. Leakage. Damper leakage shall not exceed 4 cfm/ft2 at 1 in. wg pressure
differential (Leakage Class I). Leakage shall be determined by tests conducted
in compliance with AMCA 500.
b. Basis of Design – Outside Air Dampers: Outside air dampers shall be equal to
Tamco Series 9000 thermally insulated dampers
c. Acceptable Manufacturers:
i. Tamco.
ii. Ruskin.
d. Frame:
i. Type. The frame shall be channel shape.
ii. Material. The frame shall be 13 gage (0.0934 in.) galvanized sheet steel
or 0.125 (actual web thickness) 6063-T5 extruded aluminum.
e. Blade:
i. The blade shape shall be airfoil symmetrical to the axle pivot point.
ii. Material. The blade shall be a 0.063 in. aluminum extrusion.
f.
Blade Seals: Blade seals shall be Santoprene (Advanced Elastomer Systems,
L.P.) thermoplastic rubber.
FACTORY FABRICATED CUSTOM AIR HANDLING UNITS
23 7323- 2
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
g. Jamb Seals: Stainless steel.
h. Axle: Axles shall be plated steel and both ends 3/8 in. square minimum for
positive linkage attachment.
i.
Linkage:
i. Plated steel.
ii. Linkage shall be dual and concealed in the jamb (out of the air stream).
iii. Jack shafting is not permitted.
j.
Bearings: Axle bearings shall be bronze oilite. Blade seals shall be accessible
for removal and replacement at the blade edges.
k. Acceptable Manufacturers – Factory Built-up Air Handling Units:
i. Air Enterprise.
ii. Buffalo.
iii. Trane Custom.
iv. TMI.
v. Ventrol.
8. Leakage Testing:
a. Built-up units must be leak tested at 12 in. wg. Tests shall be conducted in
compliance with SMACNA’s HVAC Air Duct Leakage Test Manual, 1st edition,
1985.
b. Draw-thru units shall be tested under negative pressure. Blow-thru units shall be
tested under positive pressure.
c. Inlets and outlets shall be sealed. The leakage rate of the unit shall not exceed
0.5% of the total Scheduled AHU CFM.
END OF SECTION
FACTORY FABRICATED CUSTOM AIR HANDLING UNITS
23 7323- 3
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
This page intentionally left blank
FACTORY FABRICATED CUSTOM AIR HANDLING UNITS
23 7323- 4
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
DIVISION 23 – HVAC
SECTION 23 8216 – COILS
1. General: This section outlines the general requirements for coils.
2. Design Considerations:
a. For both the Evanston and Chicago campuses the supply chilled water
temperature is 42 degrees F. The coil should be selected for a minimum 16
degrees F temperature differential.
b. For the Evanston campus central chilled water system primary and secondary
(distribution) piping, consult the NU Facilities Management Office (FMO).
c. For the Chicago campus central chilled water system piping, consult the NU
Facilities Management Office (FMO).
d. Drawings of the buildings on the system are on file at the NU Facilities
Management Office (FMO).
e. Packaged Air Handling Units:
i. Coils shall be slide out style and not face bolted so that they can be
removed without affecting the structural integrity of the unit.
ii. Coil connections to be schedule 40 red brass.
iii. Vent and drain connections shall be stainless steel pipe and extend to
the exterior of the unit.
iv. Piping details to be provided on the drawings.
f.
Coil Types for the following:
i. Heat Recovery:
1. Coils shall be constructed of 0.024” tube wall, 5/8” OD seamless
copper tubes with aluminum fins
2. Casings shall be minimum 16 gauge, 304 stainless steel having
stainless steel end supports and top and bottom .
3. Maximum allowable fin spacing shall be 10 fins per inch. Coil
depth shall not exceed 8 rows
4. Acceptable manufacturers:
a. Buffalo.
COILS
23 8216- 1
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
b. Marlo.
c. Heatcraft.
d. Aerofin.
e. Temtrol.
ii. Hot Water Preheat and Reheat:
1. Coils shall be constructed of 0.024 inch tube wall, 5/8-inch OD
seamless copper tubes with aluminum fins
2. Casings shall be minimum 16 gauge, galvanized steel having
galvanized end supports and top and bottom.
3. Maximum allowable fin spacing shall be 10 fins per inch. Coil
depth shall not exceed 8 rows
4. Acceptable manufacturers:
a. Buffalo.
b. Marlo.
c. Heatcraft.
d. Aerofin.
e. Temtrol.
iii. Chilled Water:
1. Coils shall be constructed of 0.035” tube wall, 5/8” OD seamless
copper tubes with continuous plate type aluminum fins
2. Casings shall be minimum 16 gauge, 304 stainless steel having
stainless steel end supports and top and bottom .
3. Maximum allowable fin spacing shall be 10 fins per inch. Coil
depth shall not exceed 8 rows
4. Acceptable manufacturers:
a. Buffalo.
b. Marlo.
c. Heatcraft.
d. Aerofin.
COILS
23 8216- 2
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
e. Temtrol.
END OF SECTION
COILS
23 8216- 3
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
This page intentionally left blank
COILS
23 8216- 4
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
DIVISION 23 – HVAC
SECTION 23 8413 – HUMIDIFICATION EQUIPMENT
1. General: This section outlines the general requirements for humidification equipment.
2. Design Considerations:
a. Central Utility Plant (CUP) steam must not be used for humidification.
b. Steam for building humidification may be generated by an evaporative heat
exchanger that uses CUP steam on the primary side of the heat exchanger.
3. Do not locate steam humidifiers immediately upstream of a fan. The preferred location
is downstream of the supply fan. Observe manufacturer’s free distance downstream of
steam injectors.
4. Maintain minimum recommended manufacturer’s air velocity for vapor absorption.
5. Provide Humidifiers for:
a.
In AHU:
i. .Factory-assembled steam dispersion unit shall include the following
components:
1. Steam supply header/separator
2. Condensate collection header
ii. Each dispersion tube shall be fitted with steam discharge tubelets
inserted into tube wall. Each tubelet shall be made of thermal-resin
material designed for high steam temperatures. Two rows of tubelets in
each dispersion tube shall discharge steam in diametrically opposite
directions, perpendicular to airflow
iii. Acceptable manufacturers:
1. Armstrong.
2. Dri-Steem.
3. Carel.
4.
Pure Humidifier Co.
b. In Ductwork (Booster).
i. Factory-assembled steam dispersion unit shall include the following
components:
HUMIDIFICATION EQUIPMENT
23 8413- 1
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
1. Steam supply header/separator.
2. Condensate collection header.
3. Steam dispersion tubes spanning distance between 2 headers.
ii. Each dispersion tube shall be fitted with steam discharge tubelets
inserted into tube wall. Each tubelet shall be made of thermal-resin
material designed for high steam temperatures. Two rows of tubelets in
each dispersion tube shall discharge steam in diametrically opposite
directions, perpendicular to airflow
iii. Acceptable manufacturers:
1. Armstrong.
2. Dri-Steem.
3. Carel.
4. Pure Humidifier Co.
6. For CUP steam to Clean steam generators the acceptable manufacturers:
a. For small units use Dri-Steem model STS (all Stainless steel).
b. For larger units use Cemline unfired boilers (all Stainless steel).
7. Clean steam piping and makeup water to be 304 stainless steel.
8. Make up water to the clean steam generators to use RO water and DI water.
9. Provide after coolers for condensate to drain applications.
a. After coolers shall be constructed of 304 stainless steel and furnished with inlet,
vent and drain connections and stainless steel striking plate
b. Acceptable Manufacturers: (Units shall be similar to DriSteem Drane Kooler)
i.
DriSteem.
ii. Penn Separator.
c. Consider air cooled condensate coolers for humidifiers in custom air handling
units to save water versus domestic water cooled condensate coolers.
END OF SECTION
HUMIDIFICATION EQUIPMENT
23 8413- 2
NORTHWESTERN UNIVERSITY
Technical Criteria
Issuance Date: 01.01.2014
DIVISION 25 – INTEGRATED AUTOMATION
SECTION 25 0000 – INTEGRATED AUTOMATION DESIGN CRITERIA
1. General: Reference NU Direct Digital Control (DDC) Standards for reference to
Northwestern University Standards for Building Automation (BAS) , Building
Management Systems (BMS), Automatic Temperature Control (ATC) standards
including control diagrams, sequences and equipment.
END OF SECTION
INTEGRATED AUTOMATION
25 0000 - 1
NORTHWESTERN UNIVERSITY
Technical Criteria
Issuance Date: 01.01.2014
This page intentionally left blank
INTEGRATED AUTOMATION
25 0000 - 2
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
DIVISION 26 – ELECTRICAL
SECTION 26 0000 – ELECTRICAL DESIGN CRITERIA
General Design Criteria
1. General: The Electrical systems within Northwestern’s facilities need to be designed
and maintained to meet the goals of safe, reliable and efficient operation.
2. Safety: Electrical safety is paramount in any facility and that begins with a design that is
safe to operate and maintain. Electrical equipment should be specified and located with
emphasis placed on reduced maintenance exposure, manageable short circuit and
ground fault current, and arc-flash safety.
3. Reliability: Reliability in the electrical system is also critical to meeting the goals of the
University to provide world class technical and health research capabilities. Electrical
systems that are reliable also require less maintenance, have lower operating costs, and
produce less waste.
4. Redundancy: The design must identify and address points of failure for systems serving
critical spaces, which are to be identified with the owner. Redundancy and/or back-up
systems should be identified.
5. Sustainability: Electrical system design should address sustainable design concepts,
energy use reduction, and occupant comfort to meet the goals of NU and the community
it serves.
Sustainability Overview
1. Sustainability is not just about energy efficiency and energy savings. From the
Advanced Lighting Guidelines: “Lighting is primarily provided for people, not for the
buildings or roadways or objects illuminated. Peoples’ needs should determine what
kind of lighting is provided. Meeting those needs is important because a good visual
environment is critical to health, productivity, comfort, aesthetics, safety, communication
and mood. Lighting designers have an opportunity and responsibility to support and
improve the quality of life for everyone. Recently, lighting has become a subject of much
greater interest than for many years. This is for three reasons:
a. The ageing of the population in many developed countries. As the human visual
system ages, its capabilities deteriorate. Lighting can be used to help older
people to see well and hence to live active lives for longer.
b. The need to reduce carbon emissions to minimize climate change. Lighting is a
major user of electricity and the generation of electricity is a major source of
carbon emissions. This means that lighting is under pressure to do more with
less.
c. The recognition that exposure to light can have significant non-visual effects on
human health. The potential for exposure to light to cause tissue damage has
been known for many years, but now its influence on the human circadian
ELECTRICAL DESIGN CRITERIA
26 0000 - 1
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
system, which operates at a very basic level of human physiology, is also
appreciated.
d. Taken together, these developments mean that the number of factors that should
be considered when determining if a lighting installation is fit for purpose has
increased. However, one factor that will almost always need to be considered is
how well the lighting enables people to see.”
2. Lighting energy efficiency shall be a significant consideration for all lighting designs. The
following shall be taken into consideration:
a. Efficiency based on ASHRAE 90.1 guidelines – strive to improve efficiency
relative to the guidelines while maintaining lighting quality
b. IESNA guidelines based on the latest IESNA Lighting Handbook
3. Site lighting shall be designed to reduce night sky light pollution.
4. Motor efficiency – motors shall be premium efficiency.
Utility Service Entrance
1. Service entrance types vary depending on campus location, building size and type of
use.
a. Transformer Vaults:
i. Underground or indoor transformer vaults are preferred over above
ground, outdoor vaults or pad-mounted transformers for aesthetics,
reliability and maintenance. Undergound vaults are to be adjacent to the
building they serve.
ii. Utility (ComEd)-owned transformer vaults are to be built to ComEd
standards for size and construction. Transformer vaults are required to
be ventilated to ComEd standards based on the transformer and
equipment ratings within the vault.
iii. University-owned transformer vaults are to be located to allow
maintenance and removal of failed transformers or other vault equipment.
Indoor vaults are to be constructed with a three-hour fire rating.
iv. Natural ventilation of the vault is preferred over forced ventilation. A
minimum of two square inches of open space per transformer rated kVA
is required for natural ventilation. Two CFM of forced ventilation per
transformer rated kVA is required for forced ventilation. Forced ventilated
vaults require high temperature and fan failure alarms connected to the
Building Automation System (BAS).
v. Vault equipment must be clearly marked, so that each component and
raceway can be identified from the entrance to the vault.
ELECTRICAL DESIGN CRITERIA
26 0000 - 2
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
vi. Vaults are to be lighted with low maintenance, all-weather lighting fixtures
connected to the building essential power system and switched at the
entrance. Adequate lighting is to be provided to allow identification of all
component and raceway markings from the entrance to the vault.
vii. Vault man doors are to open in the direction of egress with panic
hardware.
viii. Vault equipment doors are to be sized to allow the largest single piece of
equipment to be removed for replacement.
ix. A 6-inch concrete dike is to be cast onto the floor to prevent leaking
transformer oil from escaping vault. An integral transformer leak basin
can be used in lieu of a dike. The basin is to be sized large enough to
contain the liquid contents of the transformer.
x. A sump pit with cover is to be placed in one corner of vaults located
below or at grade.
xi. Where allowed by the AHJ, water fire suppression is not to be used in
transformer vaults.
xii. For transformer vaults and/or main distribution rooms located below
grade, provide high water alarms connected to the Building Automation
System (BAS).
xiii. Electrical vaults and gear rooms shall be painted with white walls and
battleship gray epoxy floors.
b. Transformers:
i. Oil-filled transformers are preferred to air-insulated type. Insulating oil is
to be FM listed as “less flammable” or “non-flammable.”
ii. If air-insulated transformers are used for service entrance applications,
only VPE silicone encapsulated or cast-coil type units are to be specified.
VPI polyester resin impregnated type units are not allowed.
iii. Air-insulated transformers are to have forced air cooling with a core
temperature indicating display.
iv. Transformer MV terminations are to be loop-feed type.
c. Duct Banks:
i. Service Entrance (MV and LV) duct banks are to be concrete encased.
Duct banks are to terminate in a service entrance switchboard or
switchgear within 5’ of entering the building or are to remain in concrete
and painted red until terminated in a service entrance rated disconnect.
d. Service Disconnect:
ELECTRICAL DESIGN CRITERIA
26 0000 - 3
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
i. MV service disconnecting means will be in metal enclosed, fused
switchgear.
ii. LV service disconnecting means rated over 1200 amperes will be in either
a service entrance rated switchboard or switchgear. Laboratory and
research facility services will utilize switchgear equipment with power
style circuit breakers.
iii. Service disconnects will be in dedicated service rooms. No foreign
systems are allowed in service rooms. Service rooms are to be
constructed with a three-hour fire-rated enclosure with doors that open in
the direction of egress with panic hardware.
iv. All components in a service room are to be clearly labeled to allow
identification from the entrance to the room.
Distribution
1. Equipment:
a. Electrical distribution equipment is to be designed and specified for a minimum
life span of 25 years.
b. Equipment is to be selected to allow for growth of the facility within reason and
meeting the goals of the University. See specific equipment sections for space
requirements.
c. The distribution system design should allow for safe maintenance of
components. Short circuit and ground fault levels are to be minimized to allow
safe maintenance and operation of systems.
d. Special attention is to be given to allow for inspection of equipment bus and
junction points without the use of arc-flash PPE wherever possible. This can
include IR viewing windows, remote IR inspection and detection equipment, and
maintenance settings on circuit breakers.
e. Equipment that has a lower maintenance alternative is to be utilized wherever
possible. Maintenance intensive components such as bus duct, battery systems,
fan-cooled equipment, etc. are to be avoided.
f.
Energy conserving and Energy Star listed equipment should be used as the
design basis for all facilities.
2. Electrical Rooms:
a. Rooms are to be designed to allow growth within the electrical system and safe
maintenance of components within the room. Space allowed for growth will
depend on the facility type and type of equipment in the room. Space for future
panels and transformers is to be discussed with NU during the design. At a
minimum, provide 30% of clear wall space in all electrical rooms for future panels
and equipment.
ELECTRICAL DESIGN CRITERIA
26 0000 - 4
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
b. Components are to be clearly labeled to allow identification from the room
entrance.
c. Electrical rooms are to be free of foreign systems such as ductwork, piping and
other equipment.
d. The room is to be fire rated based on the equipment that is located in the room.
e. Electrical rooms should be stacked from floor to floor and located with attention
given to the noise, heat, and magnetic interference caused by the room.
f.
The room air is to be exhausted to keep the space below 104F in conditioned
buildings.
Lighting
1. Lighting methods and requirements vary depending on the facility type. An emphasis on
energy conservation and controllability are to be included in each design. The latest
lighting methods and technologies are to be researched and their applications explained
during the design review process.
2. The goals of energy reduction, energy code compliance, and LEED certification are a
priority to the University and efficient lighting designs and controls are a key part in
meeting those goals.
3. The University maintains a stock of lamp types, and new lighting designs should utilize
stocked lamps whenever possible. When designs include lamps that are not NUstocked items, advise Facilities Management of this condition early in the process.
Power and Lighting Calculations
1. The goal of the required engineering calculations for each project is to provide a safe,
reliable design that can be easily revised or added to in the future with complete
knowledge of the existing system’s capacities and limitations.
2. Engineering calculations and studies that are required for every system design for both
new facilities and renovations/additions shall include the following:
a. Short Circuit
b. Time-Current Coordination
c. Arc-Flash
d. Voltage Drop
e. Lighting Power Density
f.
Lighting Photometrics
3. Power calculations are to be performed using SKM Power Tools software.
ELECTRICAL DESIGN CRITERIA
26 0000 - 5
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
4. Preliminary short circuit calculations are to be provided for review during the design
phase.
5. Time-current coordination for all new overcurrent protective devices and existing devices
where connections are made as part of the project is to be performed after the Design
Engineer has been given the circuit breaker and fuse submittals for the project. The
Design Engineer is responsible for correcting devices that do not coordinate with the
manufacturer. The installing electrical contractor is responsible for providing feeder
length and routing deviations from the design to the Design Engineer as these affect the
calculations. Adjustable device setting will be provided to the installing electrical
contractor who will make the device adjustments.
6. An arc-flash study is required to be submitted to NU and the installing electrical
contractor before the completion of the project. The installing electrical contractor is
responsible for producing and applying NFPA 70E compliant labels that contain the
appropriate information obtained from the Design Engineer’s study. All new switchgear,
switchboards, panelboards, motor control centers, starters, VFDs and disconnect
switches for each project are to be included in the study and properly labeled. Existing
equipment where connections are made as part of the project will also be included in the
study and properly labeled.
7. Lighting power density calculations for each area to show compliance with the energy
code are to be shown on the lighting plan drawings.
8. Lighting photometric drawings for laboratories, office areas, classrooms, auditoriums,
entrance lobbies and other high profile spaces as required by the University are to be
submitted during the design review process.
9. Four (4) copies of a binder with final versions of the power calculations listed above for
the project are to be submitted by the Design Engineer to NU with the record drawings at
the end of the project.
General Electrical Requirements
1. The Contractor, after inspecting the premises and the drawings, shall call to the attention
of the Architect/Engineer and NU Supervising Electrician any lack of space or clearance
required by the various equipment before the contract is signed.
2. Electrical projects are not considered complete until as-built drawings with home runs
identified are received by the NU Project Manager and the NU Supervising Electrician.
3. An over-current protection device coordination study using SKM Power Tools and
following ANSI standards for over-current device settings, transformer and cable
damage curves will be included in the engineering documents for all new electrical
power systems. For renovation projects, the study is to include coordination with all
devices in the existing source panel where the new work is added. Device trip settings
will be adjusted by the installing electrician and verified before the system is energized.
4. An arc-flash study of all new electrical power systems using SKM Power Tools will be
conducted by the engineer of record in accordance with NFPA 70E requirements. For
renovation projects, the study is to include the source equipment where the new work is
ELECTRICAL DESIGN CRITERIA
26 0000 - 6
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
added. The results of the study will be provided to the installing electrician who will
furnish and install arc-flash safety labels on all new system components where
applicable.
5. Provide a minimum of a 2-year warranty on labor and materials unless stated otherwise
in the Project General Requirements. The warranty period begins on the date the
project is completed.
6. Provide complete functional testing, start-up services, and owner training for each
system component installed.
7. Prior to project completion, all electrical system areas and components are to be
cleaned, painted, and returned to like-new condition.
8. Coordinate electrical system outages with campus Chief Electrician, Building Manager
and General Contractor. Provide a minimum of 2-week notice before outage is to occur.
9. Installing Electrician is responsible for electrical connections and testing for electrical
equipment provided by other trades or the University such as motors, motor control
devices. Coordinate with other trades and the University for requirements and
responsibilities for equipment provided by others.
Basic Electrical Materials And Methods
1. The Contractor and/or supplier shall alert the University of any specified items that
require long lead times for parts replacement (excess of 48 hours).
2. Electrical materials shall be UL approved for the type of use being applied.
3. Provide a 4-inch high concrete housekeeping pad for floor mounted equipment above
grade. Use a 6-inch high concrete housekeeping pad for locations below grade.
4. Steel anchors or toggle bolts shall be used for supporting equipment, pipe, and lights
from the ceiling. The use of plastic anchors is prohibited.
5. See list of materials not allowed in Northwestern facilities. Materials are to be RoHS
compliant were applicable. Non-RoHS compliant materials are to be reviewed on an
individual basis.
6. Electrical system components are to be Energy Star approved where applicable.
7. Material manufacturer’s and types are to match current Northwestern warehouse stock
where applicable.
8. Other system components (i.e. ductwork, piping, etc.) are not allowed to be located
within electrical rooms, electrical closets, or over electrical equipment.
ELECTRICAL DESIGN CRITERIA
26 0000 - 7
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
Technology Systems
1. Refer to Northwestern University Information Technology (NUIT) for Reference
Standards.
http://www.it.northwestern.edu/
END OF SECTION
ELECTRICAL DESIGN CRITERIA
26 0000 - 8
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
DIVISION 26 – ELECTRICAL
SECTION 26 0519 – MEDIUM AND LOW VOLTAGE CONDUCTORS
1. General: This section outlines the general requirements for medium and low voltage
conductors. Specific requirements are to be reviewed with the NU Project Manager
during the design phases of the project
2. Design Considerations:
a. Conductor ampacities shall be based on 90 degree C ratings in all cases and
adhere to the following:
b. Cable in excess of 2400 volts must be shielded and copper.
c. Cable for primary and/or secondary distribution for voltage applications in excess
of 2400 volts shall adhere to the following criteria.
i. Cable shall be suitable for use in wet and dry locations in underground
encased duct systems.
ii. Cable shall be rated for 105 degree centigrade for normal operation, 130
degree centigrade for emergency overload and 250 degree centigrade for
short circuit conditions. Use of 90 degree centigrade rated cable is to be
approved by the Supervising Electrician.
iii. Cable shall have 133% insulation.
iv. Power cable shall have a performance record of 15 years minimum of
operating experience in utility and industrial cable application. This
includes shielded cable.
d. Wire and cable for secondary power and light distribution shall be new 600 volt
insulated copper conductor.
e. Aluminum conductors are not acceptable.
f.
Wire and cable in dry locations shall be THHN (copper) or THWN (in areas of
high moisture); in damp locations, such as crawl spaces or below grade, shall be
XHHW, THWN or XLP-USE type (copper).
MEDIUM AND LOW VOLTAGE CONDUCTORS
26 0519 - 1
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
g. Wiring shall be color coded as follows:
120/208
480/277
A Phase
Black
Brown
B Phase
Red
Orange
C Phase
Blue
Yellow
Neutral
White
Gray
Ground
Green
Green w/ Yellow Stripe
h. Voltage drop calculations shall assume nominal system voltage at building
service entrance. Minimum voltage with full connected load energized shall be
as follows:
i. 98% of voltage at panelboards.
ii. 95% at equipment connections.
i.
Branch circuits supplying personal computers and other equipment generating
harmonics shall each be run with individual neutral (minimum #10 AWG). Where
the load on a specific feeder is at least 25% of such equipment the neutral on
that feeder will be sized at 173% of the over-current protective device.
j.
Minimum size conductors for power and lighting loads shall be #12 AWG.
Minimum size for control wiring will be #14 AWG. All power and control
conductors are to be stranded copper.
k. Wiring shall be installed in conduit with no exceptions.
l.
Signal and communication wiring can be installed in a cable tray system for non
plenum areas, when allowed by code.
m. Twist-on connectors are allowed for #10 AWG and smaller conductors. Only
mechanical compression type connectors shall be used on conductors larger
than #10 AWG.
n. Conductor splices are not allowed unless the circuit run exceeds 500 feet.
Splices are to be made with mechanical compression connectors only. Insulation
of the splice is to be the same as the conductor being spliced. Splices are to be
located in dry locations only and inside pull or junction boxes with “SPLICE”
identified on the cover.
o. Bus duct is not permitted.
END OF SECTION
MEDIUM AND LOW VOLTAGE CONDUCTORS
26 0519 - 2
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
DIVISION 26 – ELECTRICAL
SECTION 26 0533 – RACEWAYS AND BOXES
1. General: This section outlines the general requirements for raceways and boxes.
Specific requirements are to be reviewed with the NU Project Manager during the design
phases of the project
2. Design Considerations:
a. Provide dedicated raceway systems for the following:
i. Essential circuits.
ii. Stand-by feeders and circuits.
iii. Fire alarm systems.
iv. Security and Intrusion detection systems.
v. Access control systems.
vi. Telecommunication wiring.
vii. Public address system.
viii. Audio/visual systems.
ix. Environmental control systems.
x. Spare conduit in underground trenches. Spare shall be evaluated by
Chief Electrician.
xi. Class I circuits; remote control and signaling circuits, less than 600V.
xii. Class II circuits; remote control and signaling circuits fed from a Class II
limited power supply, 150V and less.
xiii. Where legally required.
b. Types of Conduit:
i. Electric metallic tubing “EMT” shall be utilized for concealed interior work,
except as described herein.
ii. Intermediate grade conduit “IMC” shall be utilized for interior feeders in
wet areas, damp areas, exterior, exposed in mechanical rooms and
vertical drops to equipment. Review potential wet or damp areas with
Chief Electrician.
RACEWAYS AND BOXES
26 0533 - 1
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
iii. Galvanized Rigid Steel Conduit “GRSC” shall be utilized in areas subject
to physical damage in wet areas, exterior, within masonry walls, hollow
tile walls, and all hazardous areas.
iv. PVC schedule 40 conduit shall be used in concrete slab and encased in
3" of concrete. In no case shall conduit be direct buried below slab.
Provide PVC coated GRSC for all underground elbows. Use long sweep
elbows for feeders above 600V.
1. 4 inch elbow: 36 inch minimum radius.
2. 5 inch elbow: 50 inch minimum radius.
3. 6 inch elbow: 61 inch minimum radius.
v. Flex conduit shall be used only for chasing existing walls, suspended
lights in drop-in in suspended ceilings and connections to equipment
subject to vibration, etc. Flexible conduit shall have green ground wire.
Flexible conduit shall not exceed 6 feet in length.
c. Conduit Colors:
i. Yellow:
1. Feeders 600V – 12.4kV in vaults, gear rooms, electrical rooms, or
electrical closets.
2. Gas monitoring outside vaults, gear rooms, electrical rooms, or
electrical closets only. Conduit shall be tagged with a red strip at
each connection point.
ii. Orange: Feeders 277V – 600V in vaults, gear rooms, electrical rooms, or
electrical closets.
iii. White: Feeders 120V – 240V in vaults, gear rooms, electrical rooms, or
electrical closets.
iv. Red: Fire alarm systems.
v. Blue: Building Automation System (BAS) and Security systems.
vi. Green: Dedicated ground and Hogan systems.
vii. Where conduit is exposed in public or finished areas, the conduits shall
typically be painted to match the adjacent wall or ceiling color. The
associated junction box covers shall be painted to match the
Northwestern standard conduit color code above.
viii. Refer to Electrical Identification for labeling requirements.
RACEWAYS AND BOXES
26 0533 - 2
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
d. Conduit Size:
i. 3/8-inch flexible metallic conduit is allowed for final connection to lighting
fixtures. Review specific requirements with NU Project Manager.
ii. 1/2-inch above grade allowed for controls, and some low voltage
systems. Review specific requirements with NU Project Manager.
iii. 3/4-inch minimum for all line voltage above grade.
iv. 3/4-inch minimum for all security system conduits, including CCTV and
access control systems.
v. 1-inch minimum below grade or in concrete for light loads.
vi. 4-inch minimum for main feeders, primary services and
telecommunication lines.
e. Conduit Installation:
i. Raceways shall be installed with 30% or less conductor fill.
ii. Underground conduit and ducts shall be encased in a minimum 3"
concrete envelope; trench and backfill will be done under this division of
work; a tracer wire will be installed on the conduit and in the concrete
encasement for future duct location requirements. Review specific
requirements for tracer wire with NU Project Manager and Chief
Electrician.
iii. Where conduits follow the same run, trapeze hangers (unistrut) may be
utilized with provisions made for proper spacing and the use approved
conduit straps. Suspending conduit from the bottom of a unistrut support
is not permitted.
iv. Trapeze hangers shall utilize two 3/8” minimum threaded rods per cross
member strut. Rod size is to be increased to match trapeze load with a
30% design safety factor.
v. Conduits are not to be embedded in the floor slab.
vi. PVC and PVC coated GRSC will be used in concrete. All PVC must have
ground wire installed, minimum #12.
vii. Provide conduit sealing bushings for conduits 1-1/2 inches or greater and
at all points where conduits enter the building from the outside or from
below grade. Sealing fitting are to be used at all points where conduits
enter air handlers and cold rooms.
1. All below grade conduit entries are to be specifically reviewed and
approved with the NU Project Manager and NU Chief Electrician.
RACEWAYS AND BOXES
26 0533 - 3
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
viii. Before any cutting or coring of walls and floors, the Engineering and
Electrical Department must be notified at least 2 weeks in advance.
ix. When coring through fire-rated walls and floor, fire - stop fittings and
sealers must be installed.
x. In areas where the headroom is below 12 feet, a maximum headroom
must be maintained when installing conduit.
xi. Conduits shall be located to insure access to all mechanical systems
requiring maintenance.
xii. In existing multi-story buildings new conduit shall be routed tight to
underside of slab (above grade floors only).
xiii. Raceways terminating to cable tray are to be bonded to the tray using
approved fittings and bonding conductor.
xiv. See Electrical Systems Identification Section of this Standard for raceway
identification requirements.
f.
Conduit Fittings:
i. Intermediate and Rigid: Threaded.
ii. EMT or Thin wall: Compression type, steel with insulated throats in
connectors.
iii. Fittings shall be watertight. Conduits installed underground shall be
sloped for drainage away from the building and equipment entrances.
g. Surface Metal Raceways:
i. Surface raceways shall be used in finished areas where conduit cannot
be concealed in construction, 4000 raceway with barrier for laboratories
and other application requiring a high degree of flexibility.
ii. Provide #12 isolated ground wires in all surface raceways.
iii. Wiremold #500 series or smaller shall not be used on either campus.
iv. Provide wiremold entrance fittings only. Do not drill surface raceway.
h. Manholes:
i. Precast concrete manholes are preferred to cast-in place.
ii. Manholes shall be manufactured by Utility Concrete Products, Cretex or
Elmhurst Chicago Stone Company and include the following:
RACEWAYS AND BOXES
26 0533 - 4
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
1. Windows on all sides with knock-out openings for duct entrances
to include spare knock-outs for future raceways.
2. Provisions for connecting duct bank reinforcement bars to
manhole body.
3. Cast steel solid cover with lifting shackle and cover support
complying with ASTM A 48/A 48M. The word “ELECTRIC” is to
be cast into the lid face.
4. Minimum of four external lifting rings and four internal pulling rings
cast into manhole body.
5. Internal cable support racks made of non-conductive fiber
reinforced polymer.
6. Fixed ladder attached to wall, made from non-conductive fiber
reinforced resin.
i.
Hand Holes: Comply with the following:
i. Made from polymer concrete and Manufactured by Hubbell-Quazite,
High-Line, or approved alternate.
ii. Provide Tier 22 or A-16 rated cover, minimum. Cover is to have non-skid
surface with system identification cast into lid face. Lid is to have
structural integrity matching that of the body.
iii. Designed for flush burial with tapered sides that prevent heaving.
END OF SECTION
RACEWAYS AND BOXES
26 0533 - 5
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
This page intentionally left blank
RACEWAYS AND BOXES
26 0533 - 6
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
DIVISION 26 – ELECTRICAL
SECTION 26 0553 – IDENTIFICATION FOR ELECTRICAL SYSTEMS
1. General: This section outlines the general requirements for identification for electrical
systems. Specific requirements are to be reviewed with the NU Project Manager and
NU Chief Electrician during the design phases of the project.
2. Design Considerations:
a. General:
a. All electrical equipment, switches, outlets, MCC, disconnects, drives,
disconnecting means and switches shall be labeled. Junction boxes shall
be labeled for use, circuit, voltage, etc.
b. Labeling for medium voltage shall be Charlie number, voltage, fuse size,
etc. Junction boxes shall match this requirement.
c. In finished areas, labels can be clear with black lettering. Each label shall
include panel and circuit number.
d. In areas where conduits are exposed in public areas, the conduits should
be painted to match the ceiling color. The associated junction box covers
shall be painted and labeled to match the NU standard conduit color
code.
b. Switchboard and separately mounted circuit breakers, motor starters, disconnect
switches, relays, panels to include locations of breakers feeding panel, or
distribution panel by room and breaker number, and all apparatus used for the
operation or control of power circuits, appliances or equipment shall be properly
and permanently identified by means of permanent label.
c. Colors:
i. Normal Power, 600V and up: Black letters on yellow background.
ii. Normal Power, 277V – 600V: Black letters on orange background.
iii. Normal Power, 120V – 240V: Black letters on white background.
iv. Emergency (EM) & Essential (ES) 480/277V – Red letters w/black outline
on Orange background. Differentiate EM from ES (Chicago) and EM, LR,
OS, and CS (Evanston).
v. Emergency (EM) & Essential (ES) 208/120V – Red letters on white
background. Differentiate EM from ES (Chicago) and EM, LR, OS, and
CS (Evanston).
IDENTIFICATION FOR ELECTRICAL SYSTEMS
26 0553 - 1
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
d. Motors and other pieces of electrically operated apparatus shall be identified with
suitable painted or stenciled lettering.
e. Panel directories shall be type written under a plastic or glass protective cover on
panel door. Hand printed directory and stick on type labels are not acceptable.
When panelboard directories are installed or updated, the date shall be identified
on the directory. The name of the installing or updating contractor shall be
indicated on the directory.
f.
Three spare type panel directories will be provide along with As-Built drawing to
the University. Provide one spare directory located at each panel.
g. Prior to typing directories, room numbers and area designation must be reviewed
by the university architect and university supervising electrician in case of conflict
with construction drawing designations.
h. Laboratory raceway receptacles shall display source panel and circuit numbers.
i.
Raceways in electrical rooms and vaults are to be identified every 10 feet to
indicate voltage, amperage, source switch number, and destination.
j.
Junction box covers are to be marked with the source panel and circuit numbers
for conductors found within the junction box. Use the same color coding as with
raceway identification.
k. Receptacles, switches and disconnects are to be labeled with the voltage, phase
and amperage in addition to the source panel and circuit number/s.
END OF SECTION
IDENTIFICATION FOR ELECTRICAL SYSTEMS
26 0553 - 2
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
DIVISION 26 – ELECTRICAL
SECTION 26 2200 – LOW VOLTAGE TRANSFORMERS
1. General: This section outlines the general requirements for low voltage transformers.
Specific requirements are to be reviewed with the NU Project Manager and NU Chief
Electrician during the design phases of the project.
2. Design Considerations:
a. Transformers are to have the following maximum rated rise temperatures over a
40°C ambient:
i. 150kVA and above; 80°C.
ii. 45kVA – 112.5kVA; 115°C.
iii. 30kVA and below; 150°C.
b. Appropriate K factor transformers shall be installed in laboratories and area of
multiple computer use to offset effects of harmonics.
c. Transformers are to have 220°C class insulation.
d. Transformers are to have copper windings.
e. Transformers are to be rated NEMA TP-1 efficiency or higher.
f.
Transformers are to be mounted on vibration isolation pads.
g. Transformers are limited to the following maximum sound levels:
i. 25kVA and below; 45dB.
ii. 30kVA – 150kVA; 50dB.
iii. 225kVA – 300kVA; 55dB.
iv. Above 300kVA; 60dB.
END OF SECTION
LOW VOLTAGE TRANSFORMERS
26 2200 - 1
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
This page intentionally left blank
LOW VOLTAGE TRANSFORMERS
26 2200 - 2
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
DIVISION 26 – ELECTRICAL
SECTION 26 2300 – LOW VOLTAGE SWITCHGEAR
1. General: This section outlines the general requirements for low voltage switchgear.
Specific requirements are to be reviewed with the NU Project Manager and NU Chief
Electrician during the design phases of the project.
2. Design Considerations:
a. Locations:
i. Main switchgear is not to be located in areas of elevated temperatures or
high humidity.
ii. A separate switchgear room in close proximity to the transformer vault is
recommended.
iii. Mechanical ducts, water pipes, drain pipes, etc. will not be permitted in
electrical switchgear room.
iv. Switchgear is to be self-supporting and placed on a housekeeping pad.
b. Bussing of the switchgear should be of sufficient capacity to accommodate the
next size larger transformer bank. Main breaker should be similarly sized. Buss
bracing shall be for the expected fault current for the next size transformer, a
minimum of 65,000 amperes for 30 cycles on any switchgear. Overcurrent
devices are to have an interrupt rating the same as the switchgear fault current
rating. Prepared spaces shall be provided and shall not be less than 25% of the
switchgear spaces in each frame size at completion of the project.
c. Main switchgear is to be UL1558 listed and to comply with ANSI C37.20.1.
d. Switchgear bus is to be insulated, silver plated copper, 98% conductivity, size
based on 1000 amperes per square inch current density. An interior ground bus
and terminals are to be provided along with a jumper to the system neutral where
required for service entrance. Switchgear bus is to have bolted connections.
Provide 100% neutral where indicated.
e. Vertical bus compartment is to be separated from the horizontal bus with an
insulated metal barrier.
f.
All switchgear compartments are to be segregated into cubicles with a divider
between the device cubicle and the bus. Each breaker cubicle is to have
shutters that allow draw-out circuit breakers to be installed with its finger contacts
passing through the shutters to make contact with the vertical bus. The shutter is
to spring shut when the breaker contacts have been pulled free from the bus.
LOW VOLTAGE SWITCHGEAR
26 2300 - 1
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
g. Rear cable compartments are to be separated vertically with glass polyester
dividers. Cable compartments are to be separated from vertical and horizontal
buses with an insulted metal barrier.
h. Feeder to switchgear may be wire in conduit or feeder bus. Wire in conduit
where multiple conductors per phase are required must be precut such that all
conductors per phase are the same identical length after connection. Current
capacity of “bus ways” and size of conduit for conductors shall be sized to
accommodate the next size transformer bank for future expansion.
i.
Each switchgear vertical section is to be labeled with the vertical bus voltage,
amperage, phase, and fault current bracing rating. Each switchgear circuit
breaker is to be labeled with the load identification, breaker amperage, voltage
and phase.
j.
Provide provisions and housekeeping pad for an additional vertical section to be
added to switchgear line-up. Double-ended switchgear is to have provisions and
housekeeping pad for two additional vertical sections. Room layout is to
accommodate code required clearances for both current and future sections.
k. All switchgear circuit breakers are to be power style UL1066 listed, ANSI C37.13
air frame or insulated-case type with electronic trip in draw-out cubicles, 800A
frame size minimum. Electronic trip modules are to have adjustments for long
time pickup and delay, short time pickup and delay, instantaneous pickup and
delay. All circuit breakers are to be 100% rated. Main circuit breakers are to
have an arc flash maintenance switch that minimizes the instantaneous delay to
allow for lower required PPE level during maintenance.
l.
Where ground fault protection is required by code or for coordination, ground
fault modules are to have adjustable pickup current and delay with I2T “in” and
“out” functions. Ground fault trip modules are to indicate ground current and
have programmable alarm contacts to indicate an elevated ground current
condition.
m. If ground fault protection is required on the main circuit breaker/s, two levels of
ground fault protection is required to allow coordination of ground fault devices
and avoid complete system outages due to ground faults.
n. Switchgear with zone protective interlocking is allowed as an alternate to having
circuit breakers with individual trip settings. Zone protective interlocking
switchgear will utilize a centralized CPU to monitor all circuit breaker trip
functions for each feeder. The CPU will open selected breakers upon detection
of a condition that is out of range for the setting of that breaker.
o. Install 200kA surge protection devices on all service entrance switchgear.
p. Surge protection devices are to be mounted externally to switchgear with no
more than 36” conductor length.
q. Customer metering is to be provided in addition to utility metering. Provide pulse
meter with ComEd meters required, tied to NUELEC SCADA equipment.
LOW VOLTAGE SWITCHGEAR
26 2300 - 2
NORTHWESTERN UNIVERSITY
Technical Standards
r.
Issuance Date: 01.01.2014
Rear covers shall be hinged door with Corbin #4T3142 key lock. Lock type shall
be same for both campuses.
s. Front covers shall be formed and mounted with thumb screws. All front covers
over draw out devices or with meters mounted on them shall be hung with loose
pin hinges.
t.
An overhead breaker trolley with hoist is to be provided for each switchgear lineup. Trolley rails are to be installed to allow pull boxes to be installed above
switchgear without interfering with the trolley.
u. Switchgear is to be divided into shipping splits sized to allow delivery and
installation into existing facilities. Electrical contractor is responsible for
reassembly and testing of installed switchgear to factory tolerances.
v. A mimic bus made from laminated plastic is to be attached to the front of the
switchgear with screws. The mimic bus is to indicate the bus pattern as it passes
through the switchgear. The mimic bus is to show both the horizontal and
vertical buses and all overcurrent devices.
w. Arc-flash labels are to be applied to all switchgear compartments.
x. Switchgear in new facilities shall be manufactured by Cutler Hammer, G.E., Gus
Berthold. Switchgear in existing facilities shall match the manufacturer of
equipment already being used.
END OF SECTION
LOW VOLTAGE SWITCHGEAR
26 2300 - 3
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
This page intentionally left blank
LOW VOLTAGE SWITCHGEAR
26 2300 - 4
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
DIVISION 26 – ELECTRICAL
SECTION 26 2413 – SWITCHBOARDS
1. General: This section outlines the general requirements for switchboards. Specific
requirements are to be reviewed with the NU Project Manager and NU Chief Electrician
during the design phases of the project.
2. Design Considerations:
a. Location:
i. Main switchboards are not to be located in areas of elevated
temperatures or high humidity.
ii. Provide a separate switchboard room in close proximity to the transformer
vault.
iii. Mechanical ducts, water pipes, drain pipes, etc. will not be permitted in
electrical switchboard room.
b. Bussing of the switchboard should be of sufficient capacity to accommodate the
next size larger transformer bank. Main breaker should be similarly sized. Buss
bracing shall be for the expected fault current of the next size transformer, a
minimum of 65,000 amperes on any switchboard. Overcurrent devices are to
have an interrupt rating the same as the switchboard fault current rating. Blank
spaces shall be provided and shall not be less than 25% of the switchboard
spaces in each frame size.
c. All bus joints shall be bolted and be visible with switchboard energized for
inspection and readily accessible with the board de-energized for maintenance.
Windows shall be provided for infrared capability at joint locations.
d. Main switchboards are to be UL listed dead front (UL891) with silver plated
copper bus, size based on 1000 amperes per square inch current density. An
interior ground bus and terminals are to be provided along with a jumper to the
system neutral. All ground terminations must be cadwelded.
e. Feeder to switchboard may be wire in conduit. Wire in conduit where multiple
conductors per phase are required must be precut such that all conductors per
phase are the same identical length after connection. Current capacity of “bus
ways” and size of conduit for conductors shall be sized to accommodate the next
size transformer bank for future expansion.
f.
Circuit breakers are to be used for protective devices including main disconnect.
Fuses are to be avoided. Where fault currents warrant, current limiting devices
are to be specified. All breakers are to be identified and a complete index
provided. All circuit breakers to have threaded bolts on bus connections. Circuit
breakers employing plug-in, finger type bus connections are not acceptable.
SWITCHBOARDS
26 2413 - 1
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
Blank spaces shall be provided and shall not be less than 25% of the
switchboard spaces in each frame size.
g. Each switchboard vertical section is to be labeled with the vertical bus voltage,
amperage, phase, and fault current bracing rating. Each switchboard circuit
breaker is to be labeled with the load identification, breaker amperage, voltage
and phase.
h. Main and Tie Breakers are to be insulated-case type with electronic trip in drawout cubicles. Branch breakers 600A trip and above are to be individually
mounted insulated-case type with electronic trip. 800A frame size minimum.
Electronic trip modules are to have adjustments for long time pickup and delay,
short time pickup and delay, instantaneous pickup and delay. All insulated-case
breakers are 100% rated. Other options: Arc flash maintenance switch, arch
flash detection and control relay.
i.
Where ground fault protection is required by code or for coordination, ground
fault modules are to have adjustable pickup current and delay with I2T “in” and
“out” functions.
j.
If ground fault protection is required on the main breaker, ground fault is to be
provided on branch breakers where ground faults commonly occur (feeds to
lighting panels, motor control equipment, etc.) to allow coordination of ground
fault devices.
k. Branch breakers rated below 600 amps to 400 amps are to be molded-case,
current-limiting type with electronic trip including adjustable trip settings. No
circuit breakers with trip ratings below 400 amps are to be installed in service
entrance switchboards except to feed surge protection devices.
l.
Install 200kA surge protection devices on all service entrance switchboards.
m. Surge protection devices are to be mounted externally to switchboard with no
more than 36” conductor length.
n. Customer metering is to be provided in addition to utility metering. Metering
should be added by distribution, such as Mechanical meter, Kitchen Meter,
RP/LP metering etc. Metering shall be fused and have CT shorting blocks.
(Provide Diagram)
o. Rear covers shall be hinged door with Corbin #4T3142 key lock. Lock type shall
be same for both campuses.
p. Front cover shall be formed and mounted with thumb screws. All front covers
over draw out devices or with meters mounted on them shall be hung with loose
pin switchboard type hinges.
q. Arc-flash labels are to be applied to switchboard compartments. Labels shall say
all class information and proper PPE.
SWITCHBOARDS
26 2413 - 2
NORTHWESTERN UNIVERSITY
Technical Standards
r.
Issuance Date: 01.01.2014
Switchboards in new facilities shall be manufactured by Cutler Hammer, Gus
Berthold, or Siemens. Switchboards in existing facilities shall match the
manufacturer of equipment already being used.
s. Switchboard bays shall be individual, free standing units with steel angles and
fully welded construction.
i. Front covers shall be 12 gauge formed 1” deep hinged covers to be hung
with switchboards type loose pin type and held closed with knurled thumb
screws.
ii. Interiors brackets and supports to be #10 gauge steel arc welded frame.
Brackets by means of bolting will not be accepted.
iii. Top and sides plates shall be 12 gauge or better steel, buss bar shall be
copper, 98% conductivity, size based on 1000A per sq inch current
density.
iv. All bus joints to be silver plated all bolts shall be grade 5 bolts. All
equipment shall bear the UL INC dead front switchboard label.
END OF SECTION
SWITCHBOARDS
26 2413 - 3
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
This page intentionally left blank
SWITCHBOARDS
26 2413 - 4
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
DIVISION 26 – ELECTRICAL
SECTION 26 2416 – PANELBOARDS
1. General: This section outlines the general requirements for panelboards. Specific
requirements are to be reviewed with the NU Project Manager and NU Chief Electrician
during the design phases of the project.
2. Design Considerations:
a. Panelboards shall be surface mounted in electric closets. Panel mounting
method for different bus ratings as follows:
i. 225A and below;
ii. 400A – 600A;
iii. 800A – 1200A;
iv. Above 1200A; Floor mounted.
b. Panelboards recessed in walls shall have a minimum of four 3/4-inch spare
conduits stubbed into ceiling space for future load requirements.
c. Nameplate ampacity of panel shall be 200% of connected load.
d. Neutral bus ampacity shall be rated 200% for panels feeding harmonic type
loads.
e. 100 ampere panelboards shall contain space for a maximum of 30 circuits, 125
ampere panelboards shall contain space for a maximum of 36 circuits; 225
ampere panelboards shall contain space for a maximum of 42 circuits.
f.
Include in each panel one spare 20 ampere, 1 pole circuit breaker a minimum of
25% of the total number of circuit breakers in panel.
g. Use combination AFCI breakers in living areas.
h. Arc-flash labels are to be applied to all panelboards.
i.
Panelboard assembly will adhere to the following:
i. Busses shall be copper and must be located in the rear of the panelboard
cabinet.
ii. Minimum AIC ratings:
1. 35kA for 480/277V.
2. 10kA for 208/120V.
PANELBOARDS
26 2416 - 1
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
iii. Circuit breakers will be mounted on suitable supporting members at the
front of the cabinet and connected via suitable straps of lugs to the
bussing at the rear of the cabinet. All circuit breakers to have threaded
bolts on bus connections. Circuit breakers employing plug-in, finger type
connections are not acceptable.
iv. Breakers shall be bolt-on type and shall be removable without disturbing
the bussing and/or other branch protective devices. No plug-in breakers
allowed.
v. Panelboards shall be keyed alike with Corbin #4T3142 key lock in each
building and attention must be given additions and revisions to existing
buildings; all keying must be cleared with university lock shop.
vi. Panelboard covers to be hinged with piano style hinges with door-in-door
construction.
vii. Panelboard tubs are to have fully welded construction and not to have
concentric knock-outs.
viii. Exterior panelboards shall have heaters.
ix. Panelboards shall be dead front, totally enclosed, convertible type.
x. For the Chicago Campus, all fluorescent lighting circuits are to be on a 15
ampere breaker with #12 wire and comply with Article 14-24-250 (87410.26).
xi. There are numerous Northwestern buildings with electrical feeders and
risers exceeding 80% capacity. Existing loads must be confirmed prior to
adding any additional load. New lighting or power panels installed on
existing risers must be approved by Northwestern Supervising Electrician.
j.
Panelboards in new facilities shall be manufactured by Gus Berthold.
Panelboards in existing facilities shall match the manufacturer of equipment
already being used. Other manufacturers are to be approved by the Supervising
Electrician.
END OF SECTION
PANELBOARDS
26 2416 - 2
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
DIVISION 26 – ELECTRICAL
SECTION 26 2419 – MOTOR CONTROL CENTERS
1. General: This section outlines the general requirements for motor control centers.
Specific requirements are to be reviewed with the NU Project Manager and NU Chief
Electrician during the design phases of the project.
2. Design Considerations:
a. Motor starters and overload protective devices shall be provided for all motors ½
HP or larger. Receptacles may be used for disconnects only on motors less than
1/2 HP and only as allowed by the Chicago Electrical Code and the N.E.C. and is
recommended for all hot water circulating pumps.
b. Motors shall be 480V, 3 phase except for motors less than 1/2 HP.
c. Starters shall be grouped into motor control centers. Individual starters except in
isolated cases are to be avoided. Each starter shall have a hand/off/automatic
selector switch pilot light (run), two normally open and two normally closed
auxiliary contacts.
d. Control power for starter must originate from MCC cubicle to maintain voltage
continuity with disconnection of power to starter or MCC.
e. Heater overloads will be sized at no more than 130% of running load of motor.
f.
Lockable, heavy duty safety non-fused disconnect switches are to be located
near motor which are not within sight of MCC.
g. Pushbuttons for starters will have positive lockout on “OFF” position.
h. Motors over 30 HP shall have reduced voltage or solid-state starting and power
factor correction.
i.
Minimum NEMA size for starters shall be number 1.
j.
Motor control centers shall have copper bussing.
k. Motor starters are to use fuses for overcurrent protection.
l.
Provide minimum 500va control power transformer in each starter cubicle. Size
larger transformers as needed with 100% spare capacity.
m. Motor starters are to have phase loss/under voltage detection relays and shall
open contactor upon a loss of any one or two phases or voltage that is 30%
below rated system voltage with a 5 second adjustable delay.
n. Arc-flash labels are to be applied to all motor control devices including VFDs.
MOTOR CONTROL CENTERS
26 2419 - 1
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
o. Provide “Open / Close” and “Run / Stop” light in MCC
p. Motor control centers shall have fully welded construction, welded frames, and
infrared windows.
q. Motor control centers shall be Allen Bradley, Cutler-Hammer, Gus Berthold, or
Siemens.
END OF SECTION
MOTOR CONTROL CENTERS
26 2419 - 2
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
DIVISION 26 – ELECTRICAL
SECTION 26 2713 – ELECTRICITY METERING
1. General: This section outlines the general requirements for metering of electrical
systems. Specific requirements are to be reviewed with the NU Project Manager and
NU Chief Electrician during the design phases of the project.
2. Power Meters:
a. The meter shall be UL listed and CE marked.
b. Power meter shall be designed for Multifunction Electrical Measurement on 3
phase power systems.
i. Meter shall support 3- Element Wye, 2.5 Element Wye, 2 Element delta, 4
wire Delta systems.
ii. Surge shall conform to IEEE C37.90.1 and ANSI C62.41 (6 kV)
iii. The meter shall be user programmable for voltage range to any CT or PT
ratio.
iv. Meter shall have a burden of not more than 0.36VA per phase, Max at
660V, 0.01VA and 120 Volts.
v. Meter shall have a burden of not more than 0.005VA per phase, Max at
11 Amps.
vi. The meter shall accept a voltage input range from 20 up to 576 Volts Line
to Neural, and a range from 0 up to 721 Volts from Line to Line.
vii. Meter shall accept a current reading of up to 10 Amps continuous. Start
up current for a 5 Amp input shall be no greater than 0.005 Amps.
c. Power meter shall use a dual input method for current inputs. Method one shall
allow the CT to pass directly through the meter without any physical termination
on the meter, ensuring the meter cannot be a point of failure on the CT circuit.
The second method shall provide additional termination pass-through bars,
allowing the CT leads to be terminated on the meter. The meter must support
both termination methods.
i. Fault Current Withstand shall be 100 Amps for 10 seconds, 300 Amps for
3 seconds and 500 Amps for 1 second.
ii. Pass through wire gauge dimension of 0.177"/4.5 mm shall be available.
iii. All inputs and outputs shall be galvanically isolated to 2500 Volts AC.
ELECTRICITY METERING
26 2713 - 1
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
iv. The meter shall accept current inputs of class 10: ( 0 to 10) a, 5 Amp
Nominal and class 2 (0 to 2) A, 1 A Nominal Secondary.
d. The meter shall have an accuracy of +/- 0.1% or better for volts and amps, and
0.2% for power and energy functions. The meters shall meet the accuracy
requirements of IEC687 (Class 0.2%) and ANSI C12.20 (Class 0.2%)
i. The meter shall provide true RMS measurement of voltage, - phase to
neutral and phase-to-phase; and current, per phase and neutral.
ii. The meter shall calculate RMS readings, sampling at over 400 samples
per cycle on all channels measured readings.
iii. The meter shall utilize 24 bit Analog to Digital conversion.
iv. The meter shall provide %THD ( % of total Harmonic Distortion).
Harmonic magnitude recording to the 40th order shall be available for
voltage and current harmonics.
e. The meter shall provide a simultaneous voltage and current waveform recorder.
i. The meter shall be capable of recording 512 samples per cycle for a
voltage sag or swell or a current fault event.
ii. The meter shall provide pre- and post-even recording capability.
iii. The meter shall have a programmable sampling rate for the waveform
recorder.
iv. The meter shall have an advanced DSP design that allows power quality
triggers to be based on a 1 cycle updated RMS.
v. The meter shall allow up to 170 events to be recorded.
vi. The meter shall store waveform data in a first-in, first-out circular buffer to
insure that data is always being recorded.
f.
The meter shall include a three-line, bright red, .56" LED display.
i. The meter shall fit in both DIN 92 mm and ANSI C39.1 round cut- outs.
ii. The meter must display a % of Load Bar on the front panel to provide an
analog feel. The % Load bar shall not have less than 10 segments.
g. The meter shall be available in transducer only version, which shall not include a
display.
i. The meter shall mount directly to a DIN rail and provide RS485 Modbus
or DNP 3.0 output.
ELECTRICITY METERING
26 2713 - 2
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
h. Power meter shall include virtual measurement upgrade packs, which shall allow
user to upgrade in field without removing installed meter.
i. The six upgrade packs shall be:
1. Volts, Amps, kW, kVAR, PF, kVA, Freq, kWh, kVAh, kVARh, and
I/O expansion- V1.
2. Above with 2 Megabytes of memory for Data- logging- V2.
3. Above with Power Quality Harmonics- V3.
4. Above with Limit and Control Functions- V4.
5. Above with 64 samples per cycle Waveform Recorder and 3
Megabytes of memory for Data- logging- V5.
6. Above with 512 samples per cycle Waveform Recorder and 4
Megabytes of memory for Data-logging- V6.
ii. The virtual upgrade packs must be able to be implemented without
physically removing the installed meter.
iii. Meter shall be a traceable revenue meter, and shall contain a utility grade
test pulse allowing power providers to verify and confirm that the meter is
performing to its rated accuracy.
i.
The meter shall include 2 independent communications ports on the back and
face plate with advanced features.
i. One port shall provide RS485 communications speaking Modbus ASCII,
Modbus RTU or DNP 3.0 protocol through back plate.
ii. Baud rates shall be from 9600 baud to 57600 baud.
iii. The meter shall provide an optical IrDA port (through faceplate), as the
second communication port, which shall allow the unit to be set up and
programmed using a PDA or remote laptop without the need for a
communication cable.
iv. The meter shall have Pocket PC based software available for remote
programming and integration.
j.
The meter shall provide user configured fixed window or rolling window demand.
This shall allow the user to set up the particular utility demand profile.
i. Readings for kW, kVAR, kVA and PF shall be calculated using utility
demand features.
ii. All other parameters shall offer max and min capability over the user
selectable averaging period.
ELECTRICITY METERING
26 2713 - 3
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
iii. Voltage shall provide an instantaneous max and min reading displaying
the highest surge and lowest sag seen by the meter.
iv. The Meter shall provide upgrade rate of 6 cycles for Watts, Var and VA.
All other parameters shall be 60 cycles.
k. The meter shall support power supply of 90 to 265 Volts AC and 100 to 370 Volts
DC. Universal AC/DC Supply shall be available and shall have burden of less
than 11VA.
l.
The meter shall provide Limits Alarms and Control Capability as follows:
i. Limits can be set for any measured parameter.
ii. Up to 16 limits per parameter can be set.
iii. Limits shall be based on % of Full Scale settings.
iv. Manual Relay Control shall be available through software.
v. Relay set delays and reset delays shall be available.
m. The meter shall have data-logging capability with the 2, 3, and 4 Megabyte
memory upgrade (Upgrade packs 2-6). The meter shall have a real-time clock
allow for time stamping of all the data in the meter when log events are created.
The meter with Upgrade packs 2-4 shall have six logs; the meter with Upgrade
packs 5 and 6 shall also have the Waveform Log:
i. The meter shall have three historical logs for trending profiles. Each log
shall be capable of being programmed with up to 64 parameters. The
user shall have the ability to allocate memory between the three
historical logs in order to increase or decrease the memory allotted to
each of the logs.
ii. The meter shall have a log for Limits Alarms. The Limits log shall provide
magnitude and duration of an event, time-stamp and log value. The log
must be capable of recording 2048 events.
iii. The meter shall have a log for System Events. The System Events log
shall record the following occurrences with a time-stamp: Demand
Resets, Password Requests, System Startup, Energy Resets, Log
Resets, Log Reads, Programmable Settings Changes.
iv. The meter shall have a log for I/O changes. The I/O Change log shall
provide a time-stamped record of any Relay Outputs and any Input Status
changes. The log must be capable of recording up to 2048 events.
v. The meter with Upgrade packs 5 and 6 shall have a log which is capable
of recording a waveform both when a user-programmed value goes out of
limit and when the value returns to within a limit.
ELECTRICITY METERING
26 2713 - 4
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
n. The meter shall have I/O expandability through two Option card slots on the
back.
i. The cards shall be capable of being installed in the field, without removing
the meter from installation.
ii. The meter shall auto-detect the presence of any I/O Option cards.
iii. The Option card slots shall accept I/O cards in all of the following formats:
100BaseT Ethernet Communication Card; Four Channel Bi-directional 01mA Output Card; Four Channel 4-20mA Output Card; Two Relay
Outputs/2 Status Inputs Card; Four Pulse Output/4 Status Inputs Card;
Fiber Optic Card.
iv. The meter shall be capable of accepting any combination of up to two
cards.
v. The Ethernet Option Card shall provide the meter with the 100BaseT
Ethernet functionality. The Ethernet Option card shall:
1. Allow the meter to speak with 12 simultaneous sockets of Modbus
TCP, so that multiple requests for data can be received
simultaneously.
2. Allow auto transmit/receive detection for straight or null RJ45
cables.
vi. The 1mAO Option Card shall provide the following features:
1. Four channel, bi-directional from 0-1mA Outputs.
2. Assignable to any measured parameter.
3. 0.1% of Full Scale accuracy throughout range and load.
4. iv. Maximum load impedance to 10k Ohms, with no accuracy
losses.
vii. The 20mAO Option Card shall provide the following features:
1. 4 channel, 4-20mA outputs
2. Assignable to any measured parameter.
3. 0.1% of Full Scale accuracy throughout range and load.
4. Maximum load impedance to 850 Ohms, with no accuracy losses.
5. Loop powered using up to 24 Volts DC.
ELECTRICITY METERING
26 2713 - 5
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
viii. The Relay Output/Status Input Option Card shall provide the following
features:
1. 2 relay outputs, 2 Status inputs.
2. Status inputs- Wet/Dry Auto Detect up to 150 VDC.
3. Trigger on User Set Limits/Alarms (with upgrade pack 4)
4. Set delays and Reset delays.
ix. The Pulse Output/Digital Input Option Card shall provide the following
features:
1.
4 KYZ pulse/4 Status inputs.
2. Programmable to any energy parameter and pulse value.
3. Programmable to End of Interval Pulse.
4. Can function for manual relay control and limit based control (with
upgrade pack 4).
5. 120mA continuous load current.
x. The Fiber Optic Option Card shall provide the following features:
1. Built in logic to mimic RS485 half- duplex bus, allowing the user to
daisy chain meters for low installation cost.
2. ST Terminated Option.
3. Versatile Link Terminated Option.
4. Modbus and DNP 3.0 protocols available.
o. (o) The meter shall have transformer loss, line loss, and total substation loss
compensation.
i. Substation losses shall be programmable for Watts and VARs, and for
Ferris and copper losses.
p. The meter shall have a standard 4-year warranty.
q. Power meter shall be able to be stored in (-20 to +70) degrees C.
i. Operating temperature shall be (-20 to +70) degrees C.
ii. NEMA 12 faceplate shall be available for the power meter.
r.
The following options shall be available for ordering:
ELECTRICITY METERING
26 2713 - 6
NORTHWESTERN UNIVERSITY
Technical Standards
Model
Frequency
Issuance Date: 01.01.2014
Current
Input
V-Switch
Pack
Power
Supply
Shark 200
-50: 50 Hz
-10: 10A
-V1:
-D2: 90-
Meter/Transducer
System
Secondary
Multifunction
265 Volts
Meter only
AC/DC
-V2: Above &
2 Megabytes
Data- logging
-D: 18-60
Volts DC
Shark 200T
-60: 60 Hz
-2: 2A
Transducer
System
Secondary
memory
I/O Slot 1
I/O Slot 2
-X: None
-X: None
-INP100S
-INP100S;
100BaseT
100BaseT
Ethernet
Ethernet
-V3: Above
and Power
quality
Harmonics
-RO1S: 2
Relays/2
Status
-ROIS:2
-V4: Above
and Limit and
control
functions
-PO1S: 4
Pulses/4
Status
-PO1S: 4
Pulses/4
Status
-V5: Above
and 3
Megabytes
Data-logging
memory; 64
samples per
cycle
Waveform
recorder
-1mAOS: 4
Channel
Analog
Output 0-1
bidirectional
-1mAOS: 4
Channel
Analog
Output 0-1
bidirectional
-V6: Above &
4 Megabytes
Data- logging
memory;512
samples per
cycle
Waveform
recorder
-20mAOS:
4 Channel
Analog
Output, 420 mA
-20mAOS:
4 Channel
Analog
Output, 420 mA
-FOSTS:
Fiber Optic
Output ST
Terminated
-FOSTS:
Fiber Optic
Output ST
Terminated
-FOVPS:
Fiber Optic
Output
Versatile
Link
Terminated
-FOVPS:
Fiber Optic
Output
Versatile
Link
Terminated
Relays/2
Status
ELECTRICITY METERING
26 2713 - 7
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
s. Acceptable product is Electro Industries/GaugeTech, Model Shark 200 Meter.
i. Add the following suffixes for added option:
1.
9PINC: RS232 Cable
2. CAB6490: USB to IrDA Adapter
3. Unicom 2500: RS485 to RS232 Converter
4. Unicom 2500-F:RS485 to RS232 to Fiber Optic Converter
5. Modem Manager, Model# MM1: RS485 to RS232 Converter for
Modem Communication.
6. Certificate of Calibration, Part #, Ccal: This provides Certificate of
Calibration with NIST traceable test data.
7. COMEXT3: Communicator EXT 3.0 for Windows.
END OF SECTION
ELECTRICITY METERING
26 2713 - 8
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
DIVISION 26 – ELECTRICAL
SECTION 26 2726 – WIRING DEVICES
1. General: This section outlines the general requirements for wiring devices. Specific
requirements are to be reviewed with the NU Project Manager and NU Chief Electrician
during the design phases of the project.
2. Design Considerations:
a. Use only standard NEMA “Specification Grade” for receptacles, except:
i. Where subject to physical abuse - use nylon type devices and plates.
Use in all dorms and housing facilities. Use stainless steel cover plates
elsewhere in laboratory spaces.
ii. Where subject to tampering, specify tamper-resistant devices.
iii. Where subject to water spray, high humidity, acid fumes, etc., specify
corrosion resistant devices with in-use weatherproof cover plates.
b. Provide cleaning outlets in corridors and stairs at least every 40'. Provide
receptacles in corridors so that no point along the corridor is greater than 40 feet
from a receptacle. Corridor receptacles shall be on an independent circuit from
other rooms or equipment. Maximum of six receptacles per circuit. Light
switches and convenience receptacles shall be rated for 20 amperes.
c. Receptacles within six feet of sink, tub, shower, etc. shall be GFI type.
d. A 120 volt receptacle on essential power (red in color) shall be provided in each
mechanical and switchboard room. Provide emergency lighting in each
mechanical and switchboard room.
e. Typically, color coding for receptacles is to be as follows:
i. Essential Power: RED
ii. Dedicated: GRAY
iii. Isolated Ground: IVORY WITH ORANGE TRIANGLE
iv. Normal: IVORY
v. Switched Outlets for projects pursuing LEED certification: GREEN
vi. Consult with project architect to match device color with facility finish
requirements.
END OF SECTION
26 2726 – WIRING DEVICES
26 2726 - 1
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
This page intentionally left blank
26 2726 – WIRING DEVICES
26 2726 - 2
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
DIVISION 26 – ELECTRICAL
SECTION 26 2816 – SWITCHES AND DISCONNECTS
1. General: This section outlines the general requirements for switches and disconnects.
Specific requirements are to be reviewed with the NU Project Manager and NU Chief
Electrician during the design phases of the project.
2. Design Considerations:
a. Switches shall be provided for disconnects and switching. Circuit breakers shall
not be used for switching.
b. Switches shall be rated for 20 amperes, minimum, at 120/277 volts.
c. Disconnect switches shall be rated “heavy duty”.
d. Switches and disconnects used where the available fault current is higher than
10kA shall have fuses.
e. Motor disconnects located downstream from starters or VFDs will use auxiliary
contacts to open starter or e-stop VFD prior to the knife blades opening the
circuit when the handle is placed into the off position.
f.
Arc-flash labels are to be applied to each disconnect enclosure.
END OF SECTION
SWITCHES AND DISCONNECTS
26 2816 - 1
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
This page intentionally left blank
SWITCHES AND DISCONNECTS
26 2816 - 2
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
DIVISION 26 – ELECTRICAL
SECTION 26 3213 – ENGINE GENERATORS AND TRANSFER SWITCHES
1. General: This section outlines the general requirements for engine generators and
transfer switches. Specific requirements are to be reviewed with the NU Project
Manager and NU Chief Electrician during the design phases of the project.
2. Design Considerations:
a. Stand-by (diesel or gas) generator power and automatic transfer switch
interlocked with dual service systems to provide power for designated critical and
emergency loads. Life safety, critical, and standby loads are to be fed from
different transfer switches. Essential – ES and Emergency - EM loads include
the following (review with NU):
i. Exit signs.
ii. Selected corridor and stairwell lights.
iii. Lights in mechanical and electric room.
iv. Lights in main electric room.
v. Selected sump and ejector pumps.
vi. One passenger elevator per bank.
vii. Critical laboratory experiments which cannot withstand a minimum 2 hour
power loss.
viii. Fire pumps.
ix. Fire alarm and door security systems.
x. Critical HVAC controls.
xi. Critical smoke control systems.
xii. Telecom systems.
b. Where generators are installed, generator exhaust fumes shall be prevented
from re-entering the building. Connect to existing carbon monoxide monitoring
stations.
c. Set-mounted diesel fuel tanks are to be listed UL2085.
d. Diesel generator fuel supplies are to be designed to allow for 24 hours of
operation at full load before refueling. All generators are to be designed to
operate at their listed standby rating for a period of 168 continuous hours.
ENGINE GENERATORS AND TRANSFER SWITCHES
26 3213 - 1
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
e. Enclosures and silencers for outdoor generators are to be critical grade, sound
attenuating type.
f.
Generator annunciator panel is to be located next to building fire alarm control
panel. Additional annunciator communications are required for campus
monitoring.
g. Generator shall be as manufactured by: Caterpillar, Cummins Power
Generation, or Kohler.
h. Transfer switches are to be open transition ordelayed transition type.
i.
Transfer switches are to be electrically operated and mechanically held.
j.
Transfer switches are not to use circuit breakers as switching devices.
k. Transfer switches are to be connected to the SCADA system for monitoring.
l.
Automatic transfer switches shall be as manufactured by ASCO, Cummins
Power Generation, or Russelectric.
END OF SECTION
ENGINE GENERATORS AND TRANSFER SWITCHES
26 3213 - 2
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
DIVISION 26 – ELECTRICAL
SECTION 26 3353 – UNINTERRUPTABLE POWER SUPPLIES (UPS)
1. General: This section outlines the general requirements for Uninterruptable Power
Supplies (UPS). Specific requirements are to be reviewed with the NU Project Manager
and NU Chief Electrician during the design phases of the project.
2. Design Considerations:
a. UPS systems are to be double-conversion type.
b. UPS systems are to use batteries for the DC source. Flywheels can be provided
as an alternate for systems supported by a generator.
c. Batteries will adhere to the following:
i. Valve regulated, lead acid type.
ii. Contained in metal enclosure racks or on metal racks in a dedicated
room.
iii. Space is to be ventilated to prevent hydrogen gas build-up.
iv. Space is to be maintained between 68°F and 77°F. Provide room
temperature and hydrogen gas alarms tied to building management
system.
d. UPS input is to create less than 5% THD from no load to full load.
e. UPS shall be manufactured by Eaton, Liebert, or Mitsubishi.
f.
UPS systems shall have the ability of connectivity to the device it is backing up or
IP to the software. Provide SCADA connections for monitoring.
END OF SECTION
UNINTERRUPTABLE POWER SUPPLIES (UPS)
26 3353 - 1
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
This page intentionally left blank
UNINTERRUPTABLE POWER SUPPLIES (UPS)
26 3353 - 2
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
DIVISION 26 – ELECTRICAL
SECTION 26 5100 – LIGHTING
1. General: This section outlines the general requirements for interior and exterior lighting.
Specific requirements are to be reviewed with the NU Project Manager and NU Chief
Electrician during the design phases of the project.
2. Design Considerations:
a. Light sources in interior areas shall be fluorescent with electronic ballasts (less
than 10% distortion in use), with T-8 lamps or compact fluorescent lamps.
Remote ballasts must be reviewed with the NU Project Manager and Chief
Electrician before installation.
i. LED lighting fixtures are acceptable for use based on review of the
application by the University. Lamps over 50,000 hours shall be LED.
b. High ceiling areas (spaces over 12 feet) in finished areas not subject to frequent
switching shall be metal halide (MH). High ceiling spaces in unfinished areas
shall be pulse start metal halide (PSMH) or fluorescent type.
c. Inductive lighting is an acceptable alternative in areas subject to frequent
switching and where controllability is not important.
d. Lighting controls may be integrated with motorized window shades. Control
systems shall be by the same manufacturer for integrated control.
e. Reflectors:
i. Ballast access shall be “tool free”.
ii. Reflectors must be installed without use of screws or mechanical
fasteners.
f.
Electronic Ballasts:
i. Operate both F32T8 and F25T8 rapid start lamps.
ii. Output frequency shall be greater than 20KHZ with no detectable flicker.
iii. Provide constant light output over and above 10% operating voltage
range.
iv. Maintain total harmonic distortion of no more than 10%.
v. Power factor greater than 0.95.
vi. Class P thermal protector.
LIGHTING
26 5100 - 1
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
vii. Use program-rapid start for fixtures controlled by occupancy sensors, light
controller systems, or dimming controls.
g. Fluorescent Lamps:
i. Three foot and four foot lamps shall T8 diameter with a 75 CRI, medium
bi-pin base and 4100°K color temperature.
1. 3 foot lamp shall be F25T8.
2. 4 foot lamp shall be F32T8.
ii. Lamps shall be Phillips 700 series or Sylvania or G.E. equivalent.
iii. Reduced mercury (green tip).
h. Exterior Lighting:
i. Light sources in exterior areas shall be metal halide or LED.
ii. Luminaries over emergency telephone stations shall be metal halide
M110 50W or LED approved by NUIT.
iii. Provide convenience outlet in exterior light poles. See appendix for
standard outdoor fixture specifications.
i.
Occupancy sensors are to be used in areas required by the Illinois Energy
Conservation Code or the Chicago Energy Conservation Code for facilities
located in Chicago. Areas exempt from occupancy sensor use are:
i. Electrical Rooms.
ii. Mechanical Rooms.
iii. Elevator Equipment Rooms.
iv. Areas where moving or electrified equipment would make a lighting
disruption hazardous.
v. Areas where open pits or fall hazards exist.
vi. Other areas identified by the owner as being hazardous when dark.
j.
Occupancy sensors shall adhere to:
i. Dual technology type sensors are to be used were applicable.
ii. Wall mounted sensors are not allowed.
iii. Ceiling mounted in corridors, large conference rooms, and classrooms.
LIGHTING
26 5100 - 2
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
k. Time clocks or Lutron Quantum lighting control panels are to be used in open
areas or classrooms where after-hours sweep is required by the energy
conservation code or LEED. Local area override is to be provided for after-hours
operation.
l.
Where electronic time clocks are specified, they shall be manufactured by Tork,
Paragon, Intermatic, or BRK or included in the lighting control.
m. Exterior lighting systems and lighting control shall be controlled by single photo
cell actuated contactors for large areas or across the line photo cell control for
individual luminaries. The lighting control system shall be dimmable or switched
all electrical lighting and day light weather through manual or automatic control of
light and shades. Systems shall easily integrate with SCADA. Provide
emergency lighting at points of discharge as required by authorities having
jurisdiction.
n. Exterior light levels shall be designed to achieve a minimum level of illumination
0.5 foot-candles at ground level for all walkways and driveways and 1 foot-candle
at exits. Exterior fixtures are to be cut-off type to comply with LEED light
pollution requirements.
o. Interior lighting systems shall be designed with energy conservation in mind as
well as color scheme of walls, ceilings and floors to achieve the following light
levels while complying with the energy code and LEED requirements. Levels are
measured in foot-candles on a working service 30" above finished floor. The
following are generally recommended light levels. Specific requirements shall be
coordinated with current energy codes, other applicable codes, the NU Project
Manager, and the authority having jurisdiction.
SPACE TYPE
LEVEL (fc)
Auditoriums, lecture halls:
30
Bedrooms
15
Classrooms:
50
Corridors:
15
Dining Halls:
20
Gymnasiums:
30
Gymnasiums (Varsity)
50
Laboratories (General and
Task)
75
Libraries (Reading Areas):
50
Library (Stacks):
30
Locker rooms:
20
Lounges:
20
Mechanical rooms:
20
LIGHTING
26 5100 - 3
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
SPACE TYPE
LEVEL (fc)
Music rooms:
50
Storage Areas:
15
Toilets:
15
Workshops:
75
p. Lighting Fixtures:
i. Fixtures should be easy to maintain and replacement lenses available
from open stock.
ii. Where strip lighting is used, it is recommended that rows be arranged
parallel with any exposed ceiling beams.
iii. Flush and recessed fixtures installed in furred ceilings shall be provided
with junction boxes located at least 1 foot from fixture.
iv. Small dimension “egg crate” lenses are not permitted.
v. A minimum of 3/8” threaded rod shall support pendant light fixtures.
vi. Metal trim plates shall be provided.
q. Corridor Lighting:
i. Corridor lights shall be circuited so that a small number of lights will be
left on for night service and the remainder will be controlled by occupancy
sensor or Quantum system with local override.
ii. Emergency egress lighting is to be provided to meet the code.
r.
Emergency Lighting:
i. Emergency lighting systems shall be installed in generator rooms, electric
rooms, mechanical rooms, over fire alarm panels and wherever required
for reasons of personal safety and in compliance with the code. Unit
battery fixtures are to be provided in these spaces in addition to
emergency fixtures supported by a generator.
ii. Exit and directional lighting shall be on the emergency system. Exit signs
for the Evanston Campus shall be equipped with LED type lamps for
longer life. Exit signs for the Chicago Campus shall be Chicago approved
type.
1. Exit signs shall have illuminated red letters and arrows.
2. If the Area of Rescue Assistance (ARA) sign is electrically
illuminated, provide illuminated blue letters. Otherwise,
emergency lighting can fulfill the need for sign illuminaton.
LIGHTING
26 5100 - 4
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
iii. Emergency distribution panels shall be located in mechanical and
switchboard rooms, accessible only to qualified personnel.
iv. Minimum of 20 foot-candles of lighting is to be provided in mechanical
and switchboard rooms. Provide override relay and switch if the
mechanical room has more than 10 fixtures on the emergency circuit.
v. Emergency lights are not to be locally switched except in equipment
rooms, tunnels and vaults. Emergency lights controlled by the Quantum
lighting control system can be switched by that system.
vi. Emergency unit battery lights shall be as manufactured by Surelites.
vii. In buildings where generators and/or life safety equipment exists, the
design and construction shall connect to the existing systems.
viii. Emergency unit battery lights shall be designed to be tested as a system
per floor.
s. Unfinished Areas:
i. Unfinished areas to have a minimum of 2 foot candles.
ii. Panels and associated feeders for shell spaces will be sized to provide
adequate power for maximum future lighting requirements.
END OF SECTION
LIGHTING
26 5100 - 5
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
This page intentionally left blank
LIGHTING
26 5100 - 6
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
DIVISION 27 – COMMUNICATIONS
SECTION 27 0000 – COMMUNICATIONS DESIGN CRITERIA
1. General: Reference NUIT Standards for reference to Northwestern University Standards
for standard telecommunications systems and equipment.
END OF SECTION
COMMUNICATIONS DESIGN CRITERIA
27 0000 - 1
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
This page intentionally left blank
COMMUNICATIONS DESIGN CRITERIA
27 0000 - 2
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
DIVISION 28 – SECURITY
SECTION 28 0000 – SECURITY DESIGN CRITERIA
1. General: This section outlines general requirements for security systems.
2. Design Considerations:
a. Raceways:
i. Security conductors are to be routed in blue metal raceways.
ii. Minimum raceway size is 3/4-inch.
iii. Follow other raceway requirements as shown is Section 26 0533
Raceways and Boxes for Electrical Systems.
b. Bonding and Grounding:
i. Security system components are to be bonded to the building grounding
system by:
1. Equipment grounding conductor used in Class I systems.
2. Raceway bonding bushings properly bonded to wire ways, cable
trays, and pull boxes.
3. See Class III power supply installation instructions for proper
power supply grounding.
c. Lightning Protection:
i. Every underground and overhead security conductor which enter each
facility from the outdoors requires lighting arrestors or optical isolation to
protect the system from stray voltages and surges caused by the build up
or contact with static discharge.
d. Utility Power Outage Protection:
i. Security device power supplies, monitoring equipment, recording
equipment, and other components critical to the physical security and
safety of each facility shall be supported by an uninterruptable power
supply.
ii. Uninterruptable power supplies are to utilize batteries and are to be
powered from the building’s essential power system where available.
iii. Battery support duration will be determined by the NU Physical Security
Dept.
SECURITY DESIGN CRITERIA
28 0000 - 1
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
iv. Door security device power supplies are to have internal back-up
batteries. Refer to Section 28 1000 Access Control for power supply
requirements.
END OF SECTION
SECURITY DESIGN CRITERIA
28 0000 - 2
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
DIVISION 28 – SECURITY
SECTION 28 1000 – ACCESS CONTROL
1. General: This section outlines general requirements for security systems. Specific
requirements are to be reviewed with the Northwestern Project Manager during the
design phases of the project
2. Design Considerations:
a. Access control entry hardware, monitoring and control shall be selected by the
NU Physical Security Department.
b. The access control system will:
i. Unlock electrified door locks upon authentication of submitted credential
to local card readers.
ii. Monitor door alarms and remotely unlock.
iii. Lock doors on an automated schedule from central system.
iv. Unlock doors as required by code via fire alarm relays.
v. Annunciate intrusion alarms from remote sensors.
vi. Unlock individual doors manually via operator interface.
vii. Manual unlocking shall be logged in system audit trail.
c. Electrified mortise locks are the preferred locking mechanisms. Door hardware is
to be coordinated with Project Architect and NU Physical Security Director.
3. Equipment
a. System Controller:
i. RS2 Technologies model CP-2500 or University approved equal.
b. Serial Multiplexer:
i. RS2 Technologies model MUX-8 or University approved equal.
c. Door Controller:
i. RS2 Technologies model MR-52 or University approved equal.
ii. Controller shall accommodate a minimum of two card readers and
associated inputs/outputs.
ACCESS CONTROL
28 1000 - 1
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
d. Proximity Card Readers:
i. Evanston Campus:
1. HID RP40 model 6125BKN0410 (black) or 6125BGN0410 (grey)
for wall mount applications, 42”AFF.
2. HID RP15 model 6145AKN0410 (black) or 6145AGN0410 (grey)
for mullion mount applications, 42” AFF.
ii. Chicago Campus:
1. HID RP40 model 6125BKD0410 (black) or 6125BGD0410 (grey)
for wall mount applications, 42”AFF.
2. HID RP15 model 6145AKD0410 (black) or 6145AGD0410 (grey)
for mullion mount applications, 42” AFF.
iii. Frequency: 13.56MHz
iv. Green and red LED indicator to signal acceptance or rejection of card.
v. Outdoor readers shall be of weatherproof construction.
e. Door Contacts:
i. Door contact switches shall be concealed in the door or frame.
ii. Gap: 3/8”.
iii. Configuration: Normally Closed.
iv. Manufacturers: GE, Honeywell or University approved equal.
f.
Request to Exit Motion Sensors:
i. Detection Technology: Infrared.
ii. Detection Pattern: 35 degree narrow cone.
iii. Power requirements: 12-24VDC.
iv. Mounting: Ceiling.
g. Power Supplies:
i. General:
1. Provide Battery backup for all power supplies. Coordinate runtime with University requirements for the facility.
ACCESS CONTROL
28 1000 - 2
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
2. Provide alarm terminals for:
a. Loss of power.
b. Tamper.
3. Input voltage: 120-240VAC with input fusing.
4. Output voltage: see below. Provide output fusing for each
individual circuit.
5. New facilities are to be 24VDC.
6. Power supply shall be mounted in a locking metal cabinet.
ii. 13.8VDC Applications:
1. Manufacturer: Millennium Group.
2. Model: PS-1.
3. Output Amperes: 5A.
4. Battery Backup: (2) 8AH, 6VDC.
iii. 12VDC and 24VDC Applications:
1. Manufacturer: Alarm-SAF.
2. Model: 10036.
3. Output Amperes: 10A.
4. Battery Backup: (2) 17AH, 12VDC.
h. Conductors:
i. All conductors shall be shielded.
ii. Minimum conductor size for field assembled cables is 20 AWG.
iii. Serial cables are to be RS-485 compliant.
iv. All conductors shall be routed in metallic raceways when installed indoors.
v. Verify outdoor requirements with NU Physical Security Dept.
i.
Rough-In Diagrams: The following diagrams are for information and reference
only. Specific requirements shall be reviewed with the Northwestern Project
Manager.
ACCESS CONTROL
28 1000 - 3
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
Typical Access Control Rough-In Diagram
12VDC and 13VDC Systems Diagram
ACCESS CONTROL
28 1000 - 4
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
24VDC System Diagram
END OF SECTION
ACCESS CONTROL
28 1000 - 5
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
This page intentionally left blank
ACCESS CONTROL
28 1000 - 6
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
DIVISION 28 – SECURITY
SECTION 28 3113 – FIRE DETECTION AND ALARM SYSTEMS
1. General:
a. This section outlines general requirements for fire detection and alarm systems.
b. Specific requirements are to be reviewed with the Northwestern Project Manager
during the design phases of the project.
c. Review the Life safety Systems Checklist in the Appendix. Copies are available
from the Northwestern Project Manager.
2. Design Considerations:
a. General:
i. Fire alarm systems shall provide full and complete coverage per NFPA
and include mass notification with a connection to the NUPD system.
ii. Total (complete) coverage shall be provided per NFPA 72 for R2
occupancies with more than eleven units or more than 3 stories. Provide
infrastructure for connecting the mass notification system to the NUPD
system.
b. City of Chicago Guidance:
i. Most fire alarm requirements are contained within two separate sections
of Group 9, Chapter 15-16 of the City of Chicago Building Code. In
addition, careful research in other chapters pertaining to occupancy is
required to identify special fire alarm needs.
1. For example, dormitory smoke detectors are covered in Group 3,
Chapter 13-64.
ii. On a general basis, two distinct types of fire alarm system requirements
exist: Class I and Class II and equipment must be City of Chicago
approved for use in the alarm system class being installed. Review and
approval of fire alarm plans usually includes both the Fire Prevention
Bureau and Electrical Inspection Bureau.
iii. In the Building Code, references to NFPA fire alarm and detection
standards covers a range of years from 1984 to 1993 requiring careful
coordination in the specifications. (Note: the example specification needs
considerable revision for use on a City of Chicago project.)
iv. A number of common wiring and device connection means permitted by
NFPA standards are not allowed in Chicago.
FIRE DETECTION AND ALARM SYSTEMS
28 3113 - 1
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
1. For example, "T-tapping" of intelligent (addressable) fire alarm
initiating circuits is not permitted.
v. And there are special fire resistance requirements for initiating and
signaling circuit risers.
vi. There are other unique requirements that may not be specifically
contained in the Building Code but are encountered in the review
process.
vii. A preliminary meeting is strongly recommended with the Fire Prevention
Bureau on projects.
c. Sections 26 0000, 26 1000, 26 0519, 26 0533 and 26 0553 of these standards
also contain related design requirements which shall be incorporated or
referenced in the design and specifications for the fire detection and alarm
system.
3. Contractor Requirements: The following requirements shall be reviewed with the
Northwestern Project Manager during the design phases of the project and incorporated
into the Construction Documents.
a. The fire detection and alarm system (including the conduit) shall be a separate
bid item and not part of the general electrical contract for typical FMO projects.
b. The contractor responsible for installing the conduit, wiring and devices shall
have completed at least five similar fire alarm projects.
c. Training for University technicians must consist of more than a description of the
equipment and its operation. Tuition for two attendees at manufacturer
sponsored and taught service schools shall be included in the contract.
d. Installer system warranty is to include complete maintenance and testing for 2
year after completion of project.
e. Provide a system recertification if there is an emergency system repair during the
2 year warranty.
f.
Provide free software upgrade if it is available within 6 months of the acceptance
test.
4. Spare Capacity:
a. The fire alarm control panel, and its back box enclosure, shall accommodate a
minimum of 25 percent additional zones for hardwire and 25 percent additional
initiating points for addressable systems.
b. Initiating circuits and signaling circuits to be designed with 25 percent spare
capacity. Any signaling circuits using speakers and/or voice alert shall be
designed with 25 percent spare capacity.
FIRE DETECTION AND ALARM SYSTEMS
28 3113 - 2
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
c. For voice alert/speaker systems, speakers shall be designed with a tap setting
not to exceed 2 watts at any single speaker. In calculating spare circuit capacity,
all speakers shall be assumed being at their highest available power setting
except that 4 watts shall be the maximum required at any speaker in this
calculation.
5. Equipment:
a. Northwestern University has standardized on Siemens (Pyrotronics), Notifier, and
Symplex equipment throughout the campuses. Moderate sized and larger
projects shall use intelligent technology. Small projects may use System 3
technology with review and approval by the NU Project Manager. Systems shall
be addressable with voice notification.
b. Devices shall be provided with alarm reconfirmation features. Devices shall be
combination heat and smoke detectors. Devices with voice notification shall say
“alert”.
c. Fire alarm control panels shall be located in a secure location having a minimum
1 hour fire resistance rated enclosure for any building. A 2 hour fire resistance
rated enclosure is required for major facilities having command centers or voice
alert. Rooms shall have clean conditioned air with a temperature range of 50 to
80 degrees F and without wide fluctuations in humidity. Floor space and wall
space shall provide room to install and maintain all systems and equipment
located within. At least three feet of clear space shall be provided in front of all
cabinets.
d. Fire alarm raceway riser shall be routed in a 2 hour rated shaft.
e. Fire alarm control panels and remote control modules shall not exceed 6 feet
above finished floor to the top of the cabinet. Annunciators shall not exceed 5.5
feet above finished floor to the top of the cabinet. This is to assure that
messages and controls can be readily accessed.
f.
Voice alerting systems shall have a digitally synthesized recording (no tape
drives) and messages shall use female voices. The system shall use the
University's standard message and it must be reviewed and approved by the
University before recording. Finished voice messages shall be installed and
tested prior to building occupancy and final acceptance testing of the system.
g. System printers shall be full 80 column impact printers provided with a stand and
paper catch tray. After final acceptance testing of the system, the printer shall be
provided with a new ribbon and at least 1,000 sheets of continuous feed paper.
h. Duct type smoke detector should be limited to the return air side of fans and on
supply fans downstream of all filtering and conditioning equipment. These
detectors shall not cause a building wide fire alarm signal but will cause a trouble
supervisory signal on the fire alarm system. Means shall be provided for
bypassing these signals when the fan system is being operated in the smoke
control mode.
FIRE DETECTION AND ALARM SYSTEMS
28 3113 - 3
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
i.
Provide a covered weatherproof box above the fire department Siamese
connection for future audible device next to strobe. The strobe shall be red and
continue to flash until the system is reset.
j.
The fire alarm control panel will be connected by the University to the campus
wide central supervisory system. Requirements for this connection can be
obtained from Facilities Management Operations (FMO).
k. Door frame mounted combination smoke detectors and door holders are not
permitted in University buildings. Door frame mounted holders require special
University approval prior to their use.
l.
Provide a minimum of two sets of keys to equipment locks and two sets of
special tools to access flow switches and tamper switches. These shall be
turned over to the Supervising Electrician during final acceptance testing.
m. Status lights shall be provided on fire alarm control panels to identify the smoke
control zone operation and the elevator recall. Other special functions shall also
have status lights.
n. Where voice alerting is used, provide a minimum of one back-up amplifier that
can be switched to take the place of any three primary amplifiers without
rewiring. Additional back-up amplifiers shall be provided on the ratio of one for
each three primary amplifiers.
o. Provide fault separation modules in large and complex systems to limit the
number of devices affected.
6. Design Considerations:
a. General: Review requirements with the latest version of the NU Design Checklist
for Life Safety Systems.
b. Fire Command Center:
i. Evanston Campus: An Evanston area phone shall be provided in each
fire command center.
ii. Chicago Campus: Specific requirements are to be reviewed with the NU
Manager during the design phases of the project.
c. Zone smoke door closure by smoke control zones and/or by floor. Stairway door
closure and unlocking shall take place throughout the entire building upon fire
alarm signal.
d. Each laboratory suite/room over 500 square feet shall be provided with at least
one audio/visual alerting device and manual pull station. A visual alerting device
shall be installed in all public washrooms.
e. Electric powered magnetic door holders shall be 24 volt dc supplied from the fire
alarm system.
FIRE DETECTION AND ALARM SYSTEMS
28 3113 - 4
NORTHWESTERN UNIVERSITY
Technical Standards
f.
Issuance Date: 01.01.2014
Wire nuts are not acceptable for joining wires. Either crimp connections or wire
terminal strips shall be used to join wires. Wire terminal strips shall be
permanently mounted inside junction boxes with wires neatly bundled and
arranged. Junction box cover is to be labeled “splice”.
g. Fire Alarm Devices:
i. Ceiling mounted speakers and strobes are preferred.
ii. Smoke detectors shall be installed at the top of each stairway and
elevator shaft.
iii. Smoke detector(s) shall be installed in the room housing the main and
auxiliary fire alarm control panels, elevator machine room, telephone
rooms, main electrical switch gear room and computer rooms over 500
square feet in area.
iv. Smoke detectors installed for elevator recall and control will also activate
the building and/or zone alarm signals.
v. Fixed temperature heat detectors will be installed in sheltered outside
electrical vaults and emergency generator rooms. Major electrical closets
will be provided with rate-of-rise heat detectors.
vi. Only double action type manual pull stations shall be specified.
vii. Residential Buildings
1. Provide hard-wired single station smoke detectors in the rooms.
2. System connected photoelectric type smoke detectors are
preferred in the corridors.
3. Carbon monoxide (CO) detectors are required within 15 feet of
each sleeping room or as required by the authority having
jurisdiction.
viii. Each laboratory suite/room over 500 square feet shall be provided with a
manual pull station inside the suite/room at the entrance/exit door. This is
to assist in notification of emergencies.
ix. In non-sprinkled buildings, combination fixed temperature/rate-of-rise heat
detectors shall be provided in Janitor's closets.
h. Color Coding:
i. Wiring shall be color coded as to function. Color codes shall be
continuous from the fire alarm control panel to and through the last
device. Initiating loops on addressable systems are an exception to the
following requirements.
FIRE DETECTION AND ALARM SYSTEMS
28 3113 - 5
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
Initiating Loop
Positive
Negative
Smoke detectors and duct
detectors
Yellow
Brown
Pull Stations
Yellow
Brown
Heat Detectors
Yellow
Brown
Flow Switches
Yellow w/white
stripe
Brown w/white
stripe
Tamper Switches and
Pressure Indicators
Slate
Violet
Signaling Loops
Positive
Negative
24 volt dc Power
Red
Black
A/V Horns/Strobes
Yellow
Blue
Door Holders
Orange
Brown
NOTES:

Minimum 16 AWG size; digital communication loops use minimum
18 AWG twisted and shielded low capacitance cable.

The lighter color shall always be used to indicate the positive wire.
Earth ground wires shall always be identified by a green wire with a
yellow stripe. These grounds are to be supplied and wire per
manufacturer's specifications. (Applies to both tables)
ii. Tags on wiring shall be of a permanent means and shall be subject to
University approval. Stick-on wire tags are not acceptable as a means of
permanent marking.
iii. The address of each initiating device shall be recorded in the fixed, nonremovable base as a minimum.
iv. The audio amplifiers shall be labeled as to each speaker zone and
channel being supplied.
v. Wiring:
24 DC Auxiliary Power
Annunciator
#14 Stranded
#18 TSP FPLR
FIRE DETECTION AND ALARM SYSTEMS
28 3113 - 6
NORTHWESTERN UNIVERSITY
Technical Standards
City Circuit
Door Control
Network RS232
Communication RUI
Fire Phone
Audio Riser
Audible
Phone Riser
Remote Test
Remote LED
Addressable Alarm SLC
Relay
Speaker
Visual
Initiating (Non-Addressable)
Issuance Date: 01.01.2014
#14 Stranded
#12 Stranded
#18 TSP FPLR
#18 TSP
#18 TSP FPLR
#18 TSP FPLR
#12 THHN Stranded
#18 TSP FPLR
#14 THHN Stranded
#14 Stranded
#18 TSP FPLR
#14 Stranded
#18 TSP FPLR
#12 THHN Stranded
#14 THHN Stranded
FIRE DETECTION AND ALARM SYSTEMS
28 3113 - 7
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
7. Spare Parts:
a. The following spare parts list and quantities shall be used in the specification.
Part Description
Required Number
Printer Ribbons
4
Spot Type Smoke Detectors (for each type
used)
3% of total units, minimum of 5
Audio and Visual Devices (for each type
used)
3% of total units, minimum of 5
Spot Type Heat Detectors (for each type and
temperature used)
3% of total units, minimum of 5
Address Modules
3% of total units, minimum of 3
Magnetic Door Holders
40% of total units, maximum of 5
b. The spare parts shall be turned over to Northwestern Supervising Electrician and
receipt acknowledging this shall be required before final payment to contractor.
8. Acceptance Testing and Documentation:
a. NFPA Standard No. 72 provides guidance for conducting acceptance testing and
documentation of the results. It is critical that each device be fully tested on a
functional basis including the annunciation and operational interface with other
building functions. Where the project is phased or partial occupancy and
acceptance is made, full testing of the system must still be conducted prior to
final acceptance. In this case, a written work plan shall be developed by the
installing contractor and the design engineer and accepted by the University to
assure complete acceptance testing.
b. Acceptance test records shall include all of the information requested by NFPA
Standard No. 72, Figure 7-5.2.2. The contractor shall submit test record forms
prior to acceptance testing for review and comment by the University. Deficient
or lacking information shall be attached to the contractor's forms. Preliminary
test record submission shall be made for systems installed or tested in phases.
Final records shall be provided at the completion of testing.
c. As-built drawings shall be provided before acceptance of the work and final
payment. A reproducible set and four (4) copies are required. Submit a CD
ROM copy of all CAD files in addition to the drawings. File format shall be
suitable for use with AutoCad. Confirm the revision requirements with the
Northwestern University Project Manager.
FIRE DETECTION AND ALARM SYSTEMS
28 3113 - 8
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
d. Addition of devices or changes in layout need to be updated on SCADA in EV
and FACP software Chicago. An internal review shall be complete by NU before
submitting to the City of Evanston.
e. A parts cabinet with a minimum of 10 percent attic stock is required to be kept
on-site in the FACP room.
f.
The FACP room shall have the following document containers provided by the
fire alarm system vendor:
i. Fire alarm as-built prints and pertinent information.
ii. Generator as-built prints and pertinent information.
iii. Normal power as-built prints and pertinent information.
iv. Inspection certificates, service work tickets, etc. This box shall have a
recordable device for updates and program changes.
END OF SECTION
FIRE DETECTION AND ALARM SYSTEMS
28 3113 - 9
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
This page intentionally left blank
FIRE DETECTION AND ALARM SYSTEMS
28 3113 - 10
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
DIVISION 31 – EARTHWORK
SECTION 311000 – SITE CLEARING
1. General: This section includes general requirements for site clearing and removal of
existing above- and below-grade improvements as indicated and as necessary to
facilitate new construction, including the following:
a. Protecting existing trees shrubs plants and grass to remain.
b. Removing existing trees shrubs plants and grass.
c. Clearing and grubbing.
d. Stripping and stockpiling topsoil.
e. Removing above- and below-grade site improvements.
f.
Disconnecting and capping or sealing site utilities.
g. Temporary erosion and sedimentation control measures.
2. Sustainability: Identify requirements for contractor to separate recyclable materials
produced during site clearing from other non-recyclable materials. Contractor shall store
or stockpile without intermixing with other materials and transport them to recycling
facilities.
3. Material Ownership: Except for stripped topsoil or other materials indicated to remain
NU’s property, cleared materials shall become Contractor's property and shall be legally
removed from the project site and legally disposed of.
4. Project Conditions: The following project requirements shall be coordinated with NU
during the design phase and indicated in the Contract Documents:
a. Traffic: The City of Chicago and the City of Evanston have specific requirements
for traffic control and load limits. Minimize interference with adjoining roads,
streets, walks, and other adjacent occupied or used facilities during site-clearing
operations.
i. Do not close or obstruct streets, walks, or other adjacent occupied or
used facilities without permission from NU and authorities having
jurisdiction.
ii. Provide alternate routes around closed or obstructed traffic ways if
required by authorities having jurisdiction.
b. Salvable Improvements: Coordinate items to be salvaged with NU and identify
locations to be stored either on-site or off-site on NU’s premises.
SITE CLEARING
31 1000 - 1
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
c. Utility Locator Service: Identify requirements for Contractor to notify utility locator
service for area where Project is located before site clearing.
d. Erosion and Sedimentation Control:
Identify temporary erosion and
sedimentation control measures to prevent soil erosion and discharge of soilbearing water runoff or airborne dust to adjacent properties and walkways,
according to requirements of authorities having jurisdiction. Contractor shall not
commence site clearing operations until temporary erosion and sedimentation
control measures are in place.
e. Tree Protection: Locate and identify trees and vegetation to remain or to be
relocated. Identify temporary fencing around tree protection zones. Contractor
shall not excavate within tree protection zones, unless otherwise indicated.
Contractor shall repair or replace trees and vegetation indicated to remain that
are damaged by construction operations, in a manner approved by Architect.
f.
Utilities: Identify utilities to be removed. Coordinate requirements with NU and
utility companies to shut off indicated utilities.
i. Existing Utilities: Contractor shall not interrupt utilities serving facilities
occupied by NU or others unless permitted under the following conditions
and then only after arranging to provide temporary utility services
according to requirements indicated:
1. Notify NU not less than fourteen (14) days in advance of proposed
utility interruptions.
2. Do not proceed with utility interruptions without NU’s written
permission.
5. Products:
a. Soil Materials: Obtain approved borrow soil materials off-site when satisfactory
soil materials are not available on-site.
6. Field Quality Control:
a. Clearing and Grubbing:
i. Fill depressions caused by clearing and grubbing operations with
satisfactory soil material unless further excavation or earthwork is
indicated.
ii. Place fill material in horizontal layers not exceeding a loose depth of 8
inches, and compact each layer to a density required for the proposed
condition.
SITE CLEARING
31 1000 - 2
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
b. Topsoil Stripping:
i. Remove sod and grass before stripping topsoil. Strip topsoil to whatever
depths are encountered in a manner to prevent intermingling with
underlying subsoil or other waste materials.
ii. Stockpile topsoil materials away from edge of excavations without
intermixing with subsoil. Grade and shape stockpiles to drain surface
water. Cover to prevent windblown dust.
iii. Limit height of topsoil stockpiles to 72 inches
iv. Dispose of excess topsoil as specified for waste material disposal
v. Do not stockpile topsoil within drip line of trees to remain.
END OF SECTION
SITE CLEARING
31 1000 - 3
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
This page intentionally left blank
SITE CLEARING
31 1000 - 4
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
DIVISION 31 – EARTHWORK
SECTION 31 2000 – EARTH MOVING
1. General: This section includes minimum project requirements for earth moving, including
the following:
a. Preparing subgrades for walks, pavements, lawns and grasses and exterior
plants.
b. Drainage course for slabs-on-grade excluding building slabs.
c. Base course for concrete walks and pavements.
d. Base course for asphalt paving.
e. Excavating and backfilling for utility trenches.
f.
Excavating and backfilling trenches for buried mechanical, plumbing and
electrical utilities and pits for buried utility structures.
2. Definitions:
a. Backfill: Soil material or controlled low-strength material used to fill an
excavation.
b. Initial Backfill: Backfill placed beside and over pipe in a trench, including
haunches to support sides of pipe.
c. Final Backfill: Backfill placed over initial backfill to fill a trench.
d. Base Course: Course placed between the subbase course and hot-mix asphalt
paving.
e. Bedding Course: Course placed over the excavated subgrade in a trench before
laying pipe.
f.
Borrow Soil: Satisfactory soil imported from off-site for use as fill or backfill.
g. Drainage Fill:
h. Course placed over the excavated subgrade before laying subdrainage pipe and
placed around and over the subdrainage pipe.
i.
Course supporting the slab-on-grade excluding building that also minimizes
upward capillary flow of pore water.
j.
Excavation: Removal of material encountered above subgrade elevations and to
lines and dimensions indicated.
EARTH MOVING
31 2000 - 1
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
k. Authorized Additional Excavation: Excavation below subgrade elevations or
beyond indicated lines and dimensions as directed by Architect. Authorized
additional excavation and replacement material will be paid for according to
Contract provisions for changes in the Work.
l.
Unauthorized Excavation: Excavation below subgrade elevations or beyond
indicated lines and dimensions without direction by Architect. Unauthorized
excavation, as well as remedial work directed by Architect, shall be without
additional compensation.
m. Fill: Soil materials used to raise existing grades.
n. Structures: Modular Block Retaining walls, slabs on-grade (excluding building),
tanks, curbs, sewerage, mechanical and electrical appurtenances, or other manmade stationary features constructed above or below the ground surface
excluding building.
o. Subbase Course: Course placed between the subgrade and base course for
hot-mix asphalt pavement, or course placed between the subgrade and base
course for a cement concrete pavement or a cement concrete or hot-mix asphalt
walk.
p. Subgrade: Surface or elevation remaining after completing excavation, or top
surface of a fill or backfill immediately below base, subbase, drainage fill, or
topsoil materials.
q. Utilities: On-site underground pipes, conduits, ducts, and cables.
3. Quality Assurance:
a. Contractor shall be responsible for contacting the Owner’s Geotechnical Testing
Agency at those times required by the specifications for the appropriate materials
and soils testing.
b. Contractor shall coordinate with the Owner’s Geotechnical Testing Agency as to
the Testing Agency’s requirements for advance notification, but allow for a
minimum 24-hr notification.
4. Project Conditions:
a. Existing Utilities: Contractor shall not interrupt utilities serving facilities occupied
by Owner or others unless permitted in writing by NU and then only after
arranging to provide temporary utility services according to requirements
indicated.
i. Notify NU not less than fourteen (14) days in advance of proposed utility
interruptions.
ii. Do not proceed with utility interruptions without NU’s written permission.
EARTH MOVING
31 2000 - 2
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
iii. Contractor shall contact utility-locator service (J.U.L.I.E.) for area where
Project is located before excavating. A private utility locating service may
be required for non-public utilities.
iv. Contractor shall demolish and completely remove from site existing
underground utilities indicated to be removed. Coordinate with utility
companies to shut off services if lines are active.
b. Dewatering: Review requirements for dewatering with NU during the design
phase. Discharge from dewatering operations must meet with local and State
National Pollutant Discharge Elimination System (NPDES) requirements.
c. Explosives: Do not use explosives.
5. Products:
a. Soil Materials:
i. General: Provide borrow soil materials when sufficient satisfactory soil
materials are not available from excavations.
ii. Satisfactory Soils: ASTM D 2487 Soil Classification Groups GW, GP,
GM, GC, SC, SW, SP, ML, CL and SM, or a combination of these groups;
free of rock or gravel larger than 3 inches in any dimension, debris,
waste, frozen materials, vegetation, and other deleterious matter.
iii. Unsatisfactory Soils: Soil Classification Groups MH, CH, OL, OH, and PT
according to ASTM D 2487, or a combination of these groups.
Unsatisfactory soils also include satisfactory soils not maintained within 2
percent of optimum moisture content at time of compaction.
b. Topsoil: ASTM D 5268, pH range of 5.5 to 7, a minimum of 4 percent organic
material content; less than 3 percent stones 3/4-inch or larger in any dimension
and roots, plants, sod, clay lumps, and other extraneous materials harmful to
plant growth.
i. Where possible try to match NU sandy loam soil conditions with topsoil
re-use or importing similar soil structure.
ii. Topsoil shall be free of all deleterious material that may adversely affect
the use of the planted surface including any metal, wood, plastic, glass or
other manmade materials not intended specifically as a soil supplement.
iii. Topsoil shall be free of obnoxious weeds and invasive plants or other
undesirable organisms and disease-causing plant pathogens. Topsoil
shall be free of chemicals and pesticides, farm crop seeds, with
documentation on topsoil origin and soil testing.
iv. Topsoil particle sizes shall fall in the following ranges as percentages by
mass both separately and in combination:
EARTH MOVING
31 2000 - 3
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
1. Clay: 35 percent to 60 percent
2. Silt: 35 percent to 60 percent
3. Sand: less than 60 percent
4. Silt and Clay in combination: less than 65 percent
v. Topsoil Source: Reuse surface soil stockpiled on-site. Verify suitability of
stockpiled surface soil to produce topsoil. Clean surface soil of roots,
plants, sod, stones, clay lumps, and other extraneous materials harmful to
plant growth. Supplement with imported topsoil from off-site sources
when quantities are insufficient. Obtain topsoil displaced from naturally
well-drained construction or mining sites where topsoil occurs at least 6
inches deep; do not obtain from bogs or marshes.
vi. Topsoil Testing: Include specification to cover testing of topsoil (both
from NU and from off site) and remediation of topsoil.
c. Subbase Material: Naturally or artificially graded mixture of natural or crushed
gravel, crushed stone; ASTM D 2940; conforming to State of Illinois, Dept of
Transportation Gradation CA-6 or CA-10.
d. Base Course: Naturally or artificially graded mixture of natural or crushed gravel,
crushed stone ASTM D 2940; conforming to State of Illinois, Dept of
Transportation Gradation CA-6.
e. Engineered Fill: Naturally or artificially graded mixture of natural or crushed
gravel, crushed stone; ASTM D 2940; conforming to State of Illinois, Dept of
Transportation Gradation CA-6 or CA-7.
f.
Bedding Course: Naturally or artificially graded mixture of natural or crushed
gravel, crushed stone, and natural or crushed sand; ASTM D 2940; conforming
to State of Illinois, Dept of Transportation Gradation CA-11.
g. Drainage Fill: Narrowly graded mixture of washed crushed stone, or washed
crushed or uncrushed gravel; ASTM D 448; coarse-aggregate conforming to
State of Illinois, Dept of Transportation Gradation CA-14
h. Impervious Fill: Clayey gravel and sand mixture capable of compacting to a
dense state.
i.
Geotextiles:
i. General: Limit use of geo-textiles. Past experience and over-use has
prevented adequate water/rainfall for plant absorption, created surface
water collection and "ponding", and prevented optimal sub-surface
drainage.
ii. Subsurface Drainage Geotextile: Nonwoven needle-punched geotextile,
manufactured for subsurface drainage applications, made from
EARTH MOVING
31 2000 - 4
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
polyolefins or polyesters; with elongation greater than 50 percent;
complying with AASHTO M 288 and the following, measured per test
methods referenced:
1. Survivability: Class 2; AASHTO M 288.
2. Grab Tensile Strength: 248 lbf; ASTM D 4632.
3. Sewn Seam Strength: 223 lbf ; ASTM D 4632.
4. Tear Strength: 90 lbf; ASTM D 4533.
5. Puncture Strength: 90 lbf ;ASTM D 4833.
6. Apparent Opening Size: No. 60 sieve, maximum; ASTM D 4751.
7. Water Flow Rate: 110 gpm minimum; ASTM D 4491
8. Permittivity: 0.02 per second, minimum; ASTM D 4491.
9. UV Stability: 50 percent after 500 hours' exposure; ASTM D 4355.
iii. Separation Geotextile: Nonwoven needle punched geotextile fabric,
manufactured for separation applications, made from polyolefins or
polyesters; with elongation less than 50 percent; complying with
AASHTO M 288 and the following, measured per test methods
referenced:
1. Survivability: Class 1; AASHTO M 288.
2. Grab Tensile Strength: 315 lbf; ASTM D 4632.
3. Sewn Seam Strength: 284 lbf ; ASTM D 4632.
4. Tear Strength: 113 lbf; ASTM D 4533.
5. Puncture Strength: 113 lbf ;ASTM D 4833.
6. Apparent Opening Size: No. 70 sieve, maximum; ASTM D 4751.
7. Water Flow Rate: 110 gpm minimum; ASTM D 4491
8. Permittivity: 0.02 per second, minimum; ASTM D 4491.
9. UV Stability: 50 percent after 500 hours' exposure; ASTM D 4355.
j.
Controlled Low-Strength Material:
i. Controlled Low-Strength Material: Low-density, self-compacting, flowable
concrete material as follows:
1. Portland Cement: ASTM C 150, Type I.
EARTH MOVING
31 2000 - 5
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
2. Fly Ash: ASTM C 618, Class C or F.
3. Fine Aggregate: Sand IDOT Gradation FA-1 or FA-2
4. Foaming Agent: ASTM C 869.
5. Water: ASTM C 94/C 94M.
6. Air-Entraining Admixture: ASTM C 260.
7. Compressive Strength: Minimum 30 psi at 28 days and 150 psi at
180 days when tested according to ASTM C 495.
k. Detectable Warning Tape: Acid- and alkali-resistant polyethylene film warning
tape manufactured for marking and identifying underground utilities, a minimum
of 4 inches wide and 4 mils thick, continuously inscribed with a description of the
utility, with metallic core encased in a protective jacket for corrosion protection,
detectable by metal detector when tape is buried up to 30 inches deep; colored
as follows:
i. Red: Electric.
ii. Yellow: Gas, oil, steam, and dangerous materials.
iii. Orange: Telephone and other communications.
iv. Blue: Water systems.
v. Green: Sewer systems.
6. Field Quality Control:
a. Geotechnical Testing Agency: NU will typically engage a qualified independent
geotechnical engineering testing agency to perform field quality-control testing.
i. Testing agency will test compaction of soils in place according to
ASTM D 1557, ASTM D 2167, ASTM D 2922, and ASTM D 2937, as
applicable. Tests will be performed at the following locations and
frequencies:
ii. Paved and Building Slab Areas: At subgrade and at each compacted fill
and backfill layer, at least 1 test for every 3500 sq. ft. or less of paved
area or building slab, but in no case fewer than 2 tests.
iii. Trench Backfill: At each compacted initial and final backfill layer, at least
1 test for each 250 feet or less of trench length, but no fewer than 1 tests.
iv. When testing agency reports that subgrades, fills, or backfills have not
achieved degree of compaction specified, contractor shall scarify and
moisten or aerate, or remove and replace soil to depth required;
recompact and retest until specified compaction is obtained.
EARTH MOVING
31 2000 - 6
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
b. Subgrade Inspection: Contractor shall notify NU’s Geotechnical Testing Agency
when excavations have reached required subgrade. If NU’s Geotechnical
Testing Agency determines that unsatisfactory soil is present, continue
excavation and replace with compacted backfill or fill material as directed.
c. Proof-Rolling: Contractor shall proof-roll subgrade below the building slabs and
pavements with heavy pneumatic-tired equipment to identify soft pockets and
areas of excess yielding. Review requirements and additional compensation for
authorized additional excavation and replacement material with NU during the
design phase.
d. Unauthorized Excavation: Fill unauthorized excavations under other construction
or utility pipe as directed by NU’s Geotechnical Testing Agency.
e. Storage of Soil Materials: Contractor shall stockpile borrow soil materials and
excavated satisfactory soil materials without intermixing. Contractor shall place,
grade, and shape stockpiles to drain surface water and cover to prevent
windblown dust. Contractor shall stockpile soil materials away from edge of
excavations. Do not store within drip line of remaining trees.
f.
Protection:
i. Protecting Graded Areas: Contractor shall protect newly graded areas
from traffic, freezing, and erosion. Keep free of trash and debris.
ii. Contractor shall repair and reestablish grades to specified tolerances
where completed or partially completed surfaces become eroded, rutted,
settled, or where they lose compaction due to subsequent construction
operations or weather conditions.
i. Where settling occurs before Project correction period elapses, contractor
shall remove finished surfacing, backfill with additional soil material,
compact, and reconstruct surfacing.
END OF SECTION
EARTH MOVING
31 2000 - 7
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
This page intentionally left blank
EARTH MOVING
31 2000 - 8
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
DIVISION 32 – EXTERIOR IMPROVEMENTS
SECTION 32 1216 – ASPHALT PAVING
1. General: This section includes general requirements for hot asphalt paving, including the
following:
a. Cold milling of existing hot-mix asphalt pavement.
b. Hot-mix asphalt patching.
c. Hot-mix asphalt paving.
d. Hot-mix asphalt paving overlay.
e. Asphalt surface treatments.
f.
Pavement-marking paint.
g. Traffic-calming devices.
2. Project Conditions:
a. Regulatory Requirements: Comply with materials, workmanship, and other
applicable requirements of IDOT for asphalt paving work.
b. Environmental Limitations: Do not apply asphalt materials if subgrade is wet or
excessively damp, if rain is imminent or expected before time required for
adequate cure, or if the following conditions are not met:
i. HMA Temperature: Delivered between 250 deg F and 350 deg F
ii. Prime Coat: Minimum surface temperature of 60 deg F
iii. Slurry Coat: Comply with weather limitations in ASTM D 3910.
iv. Asphalt Base Course: Minimum surface temperature of 40 deg F in the
shade and rising at time of placement.
v. Asphalt Surface Course: Minimum surface temperature of 45 deg F in
the shade at time of placement and rising at time of placement.
c. Pavement-Marking Paint: Proceed with pavement marking only on clean, dry
surfaces and at a minimum ambient or surface temperature of 55 deg F for
water-based materials, and not exceeding 95 deg F. When more restrictive,
manufacturer limits shall be adhered to.
d. Imprinted Asphalt Paving: Proceed with coating imprinted pavement only when
air temperature is at least 50 deg F and rising and will not drop below 50 deg F
within 8 hours of coating application. Proceed only if no precipitation is expected
within two hours after applying the final layer of coating.
ASPHALT PAVING
32 1216 - 1
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
3. Products:
a. Aggregates:
i. General: Use materials and gradations that have performed satisfactorily
in previous installations.
ii. Coarse Aggregate: ASTM D 692, sound; angular crushed stone, crushed
gravel.
iii. Fine Aggregate: ASTM D 1073, sharp-edged natural sand or sand
prepared from stone, gravel, or combinations thereof.
iv. For hot-mix asphalt, limit natural sand to a maximum of 20 percent by
weight of the total aggregate mass.
v. Mineral Filler: ASTM D 242, rock or slag dust, hydraulic cement, or other
inert material.
b. Asphalt Materials:
i. Asphalt Binder: AASHTO M 320 and AASHTO MP 1a, PG 58-28, PG5822, PG64-22
ii. Prime Coat: ASTM D 2027, medium-curing cutback asphalt matching
IDOT MC-30 per Section 1032 of the Standard Specifications for Road
and Bridge construction.
iii. Tack Coat: IDOT SS-1, SS-1hP, CSS-1, CSS-1hP, emulsified asphalt or
cationic emulsified asphalt, slow curing, diluted in water, per Section 1032
of the Standard Specifications for Road and Bridge Construction and of
suitable grade and consistency for application.
iv. Tack Coat: Where Paving Geotextile as an interlayer is used;
Performance Grade asphalt binder of the same grade as the overlaying
pavement.
v. Fog Seal: AASHTO M 140, emulsified asphalt, or AASHTO M 208
cationic emulsified asphalt, slow curing, factory diluted in water, of
suitable grade and consistency for application.
vi. Water: Potable.
c. Herbicide: Commercial chemical for weed control, registered by the EPA.
Provide in granular, liquid, or wettable powder form.
d. Sand: AASHTO M 29 Grade Nos. 2 or 3.
e. Paving Geotextile (Reflective Crack Control): AASHTO M 288-06, nonwoven
polypropylene; resistant to chemical attack, rot, and mildew; and specifically
designed for paving applications.
ASPHALT PAVING
32 1216 - 2
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
i. Weight: ASTM D1910, minimum 4.1 oz/sq. yd.
ii. Grab Tensile Strength: ASTM D4632, minimum 101 lbs
iii. Asphalt Retention: ASTM 6140, minimum 0.20 gal/sq. yd.
f.
Joint Sealant: ASTM D 6690 or AASHTO M 324 Type II or III Type II Type IV,
hot-applied, single-component, polymer-modified bituminous sealant.
g. Pavement-Marking Paint Type 1: Alkyd-resin type, lead and chromate free,
ready mixed, complying with AASHTO M 248, Type N Type F Type S; colors
complying with FS TT-P-1952.
i. Colors: Yellow and/or White. Accessible spaces shall typically be yellow
with blue and white signage.
h. Pavement-Marking Paint Type 2: Latex, waterborne emulsion, lead and
chromate free, ready mixed, complying with FS TT-P-1952, Type II, with drying
time of no more than 15 minutes
i. Colors: Yellow and/or White. Accessible spaces shall typically be yellow
with blue and white signage.
ii. Glass Beads: AASHTO M 247, Type 1.
i.
Wheel Stops:
i. Locate sidewalks away from curbs to avoid the need for wheel stops.
ii. If necessary, wheel stops shall be precast, air-entrained concrete, 3500psi minimum compressive strength. Provide chamfered corners, drainage
slots on underside, and holes for anchoring to substrate.
j.
Dowels: Reinforcing Bars: ASTM A 615, Grade 60; deformed
k. Imprinted Asphalt Materials:
i. Templates: Imprinted-asphalt manufacturer's standard flexible templates
for imprinting pattern into hot asphalt paving.
ii. Pattern: Specify or indicate on Drawings.
l.
Coating System: Imprinted-asphalt manufacturer's standard system formulated
for exterior application on asphalt paving surfaces.
i. Base Coating: Portland cement and epoxy-modified acrylic polymer
blended with sand and aggregate, formulated for exterior application on
asphalt paving surfaces.
ii. Top Coating: Epoxy-modified acrylic polymer blended with sand and
aggregate, formulated for exterior application on asphalt paving surfaces.
ASPHALT PAVING
32 1216 - 3
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
iii. Colorant: UV-stable pigment blend, added to each coating layer.
iv. Color: Specify or indicate on Drawings.
m. Mixes:
i. Hot-Mix Asphalt: Dense, hot-laid, hot-mix asphalt plant mixes designed
according to the Illinois Modified Strategic Highway Research Program
criteria and the IDOT Special Provision “Superpave Bituminous Concrete
Mixtures”.
ii. Binder Course Mixture N50, IL-19.0, Surface Course Mixture N50, IL9.5,Mix “C” designed in accordance with Sections 1030 and Sections 406
and 407 of the Standard Specifications for Road and Bridge Construction
and the special provision, “Quality Control/Quality Assurance of
Bituminous Concrete Mixtures.”
iii. Provide mixes with a history of satisfactory performance in geographical
area where Project is located.
iv. Emulsified-Asphalt Slurry: ASTM D 3910, Type 1, consisting of
emulsified asphalt, fine aggregate, and mineral fillers.
4. Field Quality Control”
a. Testing Agency: NU will typically engage a qualified testing agency to perform
tests and inspections.
5. Disposal: Except for material indicated to be recycled, remove excavated materials from
Project site and legally dispose of them in an EPA-approved landfill. Contractor shall not
allow milled materials to accumulate on-site.
END OF SECTION
ASPHALT PAVING
32 1216 - 4
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
DIVISION 32 – EXTERIOR IMPROVEMENTS
SECTION 32 1313 – CONCRETE PAVING
1. General: This section includes general requirements for concrete paving, including the
following:
a. Driveways and roadways.
b. Parking lots.
c. Curbs and gutters.
d. Walkways.
e. Unit paver base.
2. Definitions:
a. Cementitious Materials: Portland cement alone or in combination with one or
more of blended hydraulic cement, fly ash and other pozzolans, and ground
granulated blast-furnace slag.
3. Project Conditions:
a. ACI Publications: Comply with ACI 301, "Specification for Structural Concrete,"
unless modified by requirements in the Contract Documents.
b. Steel Reinforcement: Comply with CRSI's "Manual of Standard Practice" for
fabricating, placing, and supporting reinforcement.
4. Products:
a. Forms:
i. Form Materials: Plywood, metal, metal-framed plywood, or other
approved panel-type materials to provide full-depth, continuous, straight,
smooth exposed surfaces. Use flexible or curved forms for curves with a
radius 100 feet or less.
ii. Form-Release Agent: Commercially formulated form-release agent that
will not bond with, stain, or adversely affect concrete surfaces and will not
impair subsequent treatments of concrete surfaces.
b. Steel Reinforcement:
i. Plain-Steel Welded Wire Reinforcement: ASTM A 185, fabricated from
as-drawn steel wire into flat sheets.
ii. Epoxy-Coated Welded Wire Fabric: ASTM A 884, Class A, plain steel.
CONCRETE PAVING
32 1313 - 1
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
iii. Reinforcing Bars: ASTM A 615, Grade 60; deformed.
iv. Epoxy-Coated Reinforcing Bars: ASTM A 775 or ASTM A 934; with
ASTM A 615, Grade 60 deformed bars.
v. Joint Dowel Bars: Plain steel bars, ASTM A 615, Grade 60. Cut bars
true to length with ends square and free of burrs.
vi. Epoxy-Coated Joint Dowel Bars: ASTM A 775; with ASTM A 615,
Grade 60 , plain steel bars.
vii. Tie Bars: ASTM A 615/A 615M, Grade 60, deformed.
viii. Hook Bolts: ASTM A 307, Grade A, internally and externally threaded.
Design hook-bolt joint assembly to hold coupling against pavement form
and in position during concreting operations, and to permit removal
without damage to concrete or hook bolt.
ix. Bar Supports: Bolsters, chairs, spacers, and other devices for spacing,
supporting, and fastening reinforcing bars, welded wire reinforcement,
and dowels in place. Manufacture bar supports according to CRSI's
"Manual of Standard Practice" from steel wire, plastic, or precast concrete
of greater compressive strength than concrete, and as follows:
1. Equip wire bar supports with sand plates or horizontal runners
where base material will not support chair legs.
2. For epoxy-coated reinforcement, use epoxy-coated or other
dielectric-polymer-coated wire bar supports.
c. Concrete Materials:
i. Cementitious Material: Use the following cementitious materials, of the
same type, brand, and source throughout the Project:
1. Portland Cement: ASTM C 150, Type I II I/II III, gray, Supplement
with the following:
a. Fly Ash: ASTM C 618, Class F.
2. Blended Hydraulic Cement: ASTM C 595, Type IP, portlandpozzolan, or I PM, pozzolan-modified portland cement.
ii. Normal-Weight Aggregates: ASTM C 33, coarse aggregate, uniformly
graded. Provide aggregates from a single source.
1. Maximum Coarse-Aggregate Size: 1-1/2” nominal.
2. Fine Aggregate: Free of materials with deleterious reactivity to
alkali in cement.
CONCRETE PAVING
32 1313 - 2
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
iii. Exposed Aggregate: Selected, hard, and durable; washed; free of
materials with deleterious reactivity to cement or that cause staining; from
a single source, with gap-graded coarse aggregate as follows:
1. Aggregate Sizes: 1/2 to 3/4 inch 3/8 to 5/8 inch nominal.
2. Aggregate Source, Shape, and Color:
iv. Water: ASTM C 94/C 94M.
v. Air-Entraining Admixture: ASTM C 260.
vi. Chemical Admixtures: Provide admixtures certified by manufacturer to be
compatible with other admixtures and to contain not more than 0.1
percent water-soluble chloride ions by mass of cementitious material.
1. Water-Reducing Admixture: ASTM C 494/C 494M, Type A.
2. Retarding Admixture: ASTM C 494/C 494M, Type B.
3. Water-Reducing and Retarding Admixture: ASTM C 494/C 494M,
Type D.
d. Curing Materials:
i. Absorptive Cover: AASHTO M 182, Class 2, burlap cloth made from jute
or kenaf, weighing approximately 9 oz./sq. yd. dry.
ii. Moisture-Retaining Cover: ASTM C 171, polyethylene film or white
burlap-polyethylene sheet.
iii. Water: Potable.
iv. Evaporation Retarder: Waterborne, monomolecular film forming;
manufactured for application to fresh concrete.
v. Clear Waterborne Membrane-Forming Curing Compound: ASTM C 309,
Type 1, Class B.
vi. Concrete Sealer: Water based USEPA VOC compliant penetrating sealer
for concrete. Cured concrete to conform to ASTM C309.
1. Dries to low or medium luster, UV resistant, no color change.
2. Reduction of Water absorption (NCHRP Series II): 75% minimum
3. Reduction of Chloride Ion absorption (NCHRP Series II): 85%
minimum.
e. Joint Filler: Two types of joint filler are listed below. Confirm use of sealant with
NU.
CONCRETE PAVING
32 1313 - 3
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
i. Expansion- and Isolation-Joint-Filler Strips: ASTM D 1751, asphaltsaturated cellulosic fiber.
ii. Expansion- and Isolation-Joint-Filler Strips: ASTM D 1752, Polyethylene
closed cell joint filler
f.
Color Pigment: ASTM C 979, synthetic mineral-oxide pigments or colored waterreducing admixtures; color stable, free of carbon black, nonfading, and resistant
to lime and other alkalis.
g. Slip-Resistive Aggregate Finish: Factory-graded, packaged, rustproof,
nonglazing, abrasive aggregate of fused aluminum-oxide granules or crushed
emery with emery aggregate containing not less than 50 percent aluminum oxide
and not less than 20 percent ferric oxide; unaffected by freezing, moisture, and
cleaning materials.
h. Bonding Agent: ASTM C 1059, Type II, non-redispersible, acrylic emulsion or
styrene butadiene.
i. Types I and II, non-load bearing IV and V, load bearing, for bonding
hardened or freshly mixed concrete to hardened concrete.
i.
Chemical Surface Retarder: Water-soluble, liquid-set retarder with color dye, for
horizontal concrete surface application, capable of temporarily delaying final
hardening of concrete to a depth of 1/8 to 1/4 inch.
j.
Pigmented Mineral Dry-Shake Hardener: Factory-packaged dry combination of
portland cement, graded quartz aggregate, color pigments, and plasticizing
admixture. Use color pigments that are finely ground, nonfading mineral oxides
interground with cement.
k. Pavement Markings:
i. Pavement-Marking Paint: Alkyd-resin type, lead and chromate free,
ready mixed, complying with AASHTO M 248, Type N Type F.
ii. Color: Accessible Spaces Yellow
iii. Glass Beads: AASHTO M 247, Type 1.
l.
Wheel Stops: Two types of wheel stops are described below. Review
requirements with NU.
i. Wheel Stops – Type 1: Precast, air-entrained concrete, 3500-psi.
Provide chamfered corners and drainage slots on underside and holes for
anchoring to substrate.
ii. Wheel Stops – Type 2: Solid, integrally colored, 96 percent recycled
HDPE or commingled postconsumer and postindustrial recycled plastic;
UV stabilized. Provide chamfered corners and drainage slots on
underside and holes for anchoring to substrate.
CONCRETE PAVING
32 1313 - 4
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
iii. Dowels: Galvanized steel.
5. Concrete Mixtures:
a. Prepare design mixtures, proportioned according to ACI 301, for each type and
strength of normal-weight concrete determined by either laboratory trial mixes or
field experience.
b. Proportion mixtures to provide normal-weight concrete with the following
properties:
i. Minimum Compressive Strength (28 Days): 4,000 psi.
ii. Maximum Water-Cementitious Materials Ratio at Point of Placement:
0.32-0.42.
iii. Slump Limit: 4 inches , plus or minus 1/2 inch.
c. Add air-entraining admixture at manufacturer's prescribed rate to result in
normal-weight concrete at point of placement having an air content as follows:
i. Air Content: 5 to 8 percent for 1-inch to 1-1/2-inch nominal maximum
aggregate size.
d. Limit water-soluble, chloride-ion content in hardened concrete to 0.15 percent by
weight of cement.
e. Chemical Admixtures: Use admixtures according to manufacturer's written
instructions.
i. Use water-reducing and retarding admixture when required by high
temperatures, low humidity, or other adverse placement conditions.
f.
Cementitious Materials: Limit percentage, by weight, of cementitious materials
other than portland cement according to ACI 301 requirements for concrete
exposed to deicing chemicals.
g. Color Pigment: Add color pigment to concrete mixture according to
manufacturer's written instructions and to result in hardened concrete color
consistent with approved mockup.
6. Concrete Mixing:
a. Ready-Mixed Concrete: Measure, batch, and mix concrete materials and
concrete according to ASTM C 94/C and ASTM C 1116. Furnish batch
certificates for each batch discharged and used in the Work.
i. When air temperature is between 85 deg F and 90 deg F, reduce mixing
and delivery time from 1-1/2 hours to 75 minutes; when air temperature is
above 90 deg F, reduce mixing and delivery time to 45 minutes.
CONCRETE PAVING
32 1313 - 5
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
b. Project-Site Mixing: Measure, batch, and mix concrete materials and concrete
according to ASTM C 94/C 94M. Mix concrete materials in appropriate drumtype batch machine mixer.
7. Field Quality Control:
a. Testing Agency: NU will typically engage a qualified independent testing and
inspecting agency to perform field tests and inspections and prepare test reports.
END OF SECTION
CONCRETE PAVING
32 1313 - 6
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
DIVISION 32 – EXTERIOR IMPROVEMENTS
SECTION 32 1400 – UNIT PAVING
1. General: This section includes general requirements for unit pavers set in aggregate
setting beds.
2. Sustainability / Regional Materials:
a. Precast concrete pavers and curbs shall be manufactured within 500 miles of
Project site from aggregates and cement extracted and manufactured within 500
miles of Project site.
b. Granite and natural stone curbs shall be manufactured within 500 miles of
Project site from materials extracted and manufactured within 500 miles of
Project site.
c. Aggregate and soil extracted, harvested, or recovered, as well as manufactured,
within 500 miles of Project site.
3. Warranty Requirements: Warranty shall include filling of paver joints 1 year after
installation at no additional cost.
4. Materials:
a. Review use of materials including precast concrete, clay pavers, and natural
stone with NU Project Manager.
5. Products:
a. Edge Restraints: Stainless Steel or Aluminum.
b. Curbs: Precast concrete or Granite.
END OF SECTION
UNIT PAVING
32 1400 - 1
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
This page intentionally left blank
UNIT PAVING
32 1400 - 2
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
DIVISION 32 – EXTERIOR IMPROVEMENTS
SECTION 32 8400 – PLANTING IRRIGATION
1. General:
a. This irrigation system guideline is for design-build system as well as designed
systems, and is considered minimum standards for Northwestern University.
b. A sample technical specification Section 32 8400 – Planting Irrigation prepared
by Northwestern University is available for information and reference. Review
specific project requirements with the NU Project Manager during the design
phase.
c. Work specified or called for on the drawings, shall be executed in accordance
with governing ordinances, laws, and regulations and shall meet local codes and
conditions. Changes or additions in the work necessary to meet ordinances,
regulations, and/or conditions shall have the prior written approval of
Northwestern University.
2. Design Considerations:
a. The design of the system shall be according to standard practices of the
Irrigation Association, local codes, Northwestern Standards and manufacturer's
recommendations.
b. Irrigation should contain rain-sensors, soil moisture sensors, solar clocks where
applicable and/or other sustainable friendly measures. When possible irrigation
water source should be derived from site water collection and re-use such as a
cistern.
c. Maximum velocity of water through piping and equipment = 5ft per second all
piping shall not exceed 75% of it rated GPM or psi capacity. Metallic pipe for any
exposed piping, PVC pipe Sch40 1-1/2-inch and smaller SDR21 for 2-inch and
larger 1-inch to 1-1/2-inch polyethylene may be used for lateral piping.
d. Rotary heads are only allowed on areas exceeding 16’ spacing the rotor must be
equipped with the stainless steel riser models for areas with head spacing up to
50’ Hunter I-20stainless for areas with head spacing exceeding 50’ or heavy
use areas such as sports fields or open activity areas use Toro 640 series.
e. Pop-up spray heads only. Use 4-inch pop-ups for turf areas and 12-inch pop-ups
for plantings.
f.
The angel of trajectory of the sprinkler head should be calculated so that the
spray will be above the expected mature plant elevation use Rainbird 1800
series.
g. Planting beds and turf areas must be located on separate zones.
PLANTING IRRIGATION
32 8400 - 1
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
h. All sprinklers heads within a zone to operate at no more than a maximum loss of
3 psi from solenoid valve to farthest sprinkler head. The zone to have 25%
available capacity for higher GPM nozzles or additional sprinklers.
i.
The spray of the sprinklers shall not intentionally reach or spray over walk or
pavement. Sprinkler heads spacing, only triangular or square sprinkler head
spacing is to be used (signal row spacing is not allowed) 8' maximum spacing for
landscape planting areas. Detail all pipe sizes from the point of connection and
all irrigation pipe sizes. Include a minimum of one quick coupler valve per 70'
hose can reach all areas.
j.
Irrigation Controller to be housed in a stainless enclosure and UL listed.
Controller to be internet based with all equipment including added lightening
protection and flow meters to monitor all zones and to include starting at
acceptance 1 year of Internet control programming communication of service
Model Irritrols Rain Master Eagle Plus.
k. Show all details of tap, meter, meter pit, RPZ valve, RPZ enclosure, blowout
connection and all other related details. Give a detailed description of
winterization procedures and spring start-up, the description shall be detailed so
Northwestern University can perform these procedures.
l.
Pipe Depth – Minimum Finished Grade to Top of Pipe:
i. Lateral 16-inches to 24-inches.
ii. Mainline 24-inches to 36-inches.
m. Sleeves: Pipes under walks or pavement to be sleeved with the sleeve shall be
2 times larger than the pipe size all wire shall be in a separate conduit or sleeve.
i. Minimum sleeve depth for walks: 24-inches.
ii. For pavement with vehicle traffic: 36-inches.
2. Project Considerations:
a. Submittals: Shop drawings and submittals are required shall be submitted and
approved prior to starting work. Design drawings and submittals are to be
prepared by an Illinois registered Professional Engineer or State of Illinois
licensed Plumbing Contractor detailing the entire layout of the planed irrigation
system.
i. Minimum requirements include characteristics of the system including
pipe type, pipe size, manufactures, part names, part numbers, model
numbers, equipment type and layout, and fabrication.
ii. The design shall include calculations indicating gallons per minute,
pressure all water calculations are to be indicated at point of connection
solenoid valves, sprinkler heads and any other pertinent equipment.
PLANTING IRRIGATION
32 8400 - 2
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
iii. An Illinois registered professional engineer or State of Illinois licensed
Plumbing contractor shall stamp and put his or signature with identifying
license number on each design drawing and submittal.
b. Record Documents: As-built drawings of the installed system must be submitted
at time of system acceptance and indicate all items as described for shop
drawing.
END OF SECTION
PLANTING IRRIGATION
32 8400 - 3
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
This page intentionally left blank
PLANTING IRRIGATION
32 8400 - 4
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
DIVISION 32 – EXTERIOR IMPROVEMENTS
SECTION 32 9200 – TURF AND NATIVE / ADAPTIVE PLANTINGS
1. General:
a. A sample technical specification Section 32 9200 – Turf and Native / Adaptive
Plantings prepared by Northwestern University is available in the Appendix for
information and reference. Review specific project requirements with NU during
the design phase.
2. Project Conditions:
a. Contractor shall obtain and submit copies to Northwestern University all
necessary related city and environmental permits (e.g. irrigation - water
department permits; use of city hydrants - city hydrant permit, etc.).
END OF SECTION
TURF AND NATIVE / ADAPTIVE PLANTINGS
32 9200 - 1
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
This page intentionally left blank
TURF AND NATIVE / ADAPTIVE PLANTINGS
32 9200 - 2
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
DIVISION 32 – EXTERIOR IMPROVEMENTS
SECTION 32 9300 – PLANTS
1. General:
a. A sample technical specification Section 32 9300 – Plants prepared by NU is
available in the Appendix for information and reference.
b. Review specific project requirements with Northwestern University during the
design phase.
2. Project Conditions:
a. Contractor shall obtain and submit copies to Northwestern University all
necessary related city and environmental permits (e.g. irrigation - water
department permits; use of city hydrants - city hydrant permit, etc.).
END OF SECTION
PLANTS
32 9300 - 1
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
This page intentionally left blank
PLANTS
32 9300 - 2
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
DIVISION 33 – UTILITIES
SECTION 33 1313 - FACILITY SANITARY SEWERS
1. General: This section includes performance requirements and minimum requirements
for the following products and materials:
a. Pipe and fittings.
b. Non-pressure and pressure couplings.
c. Expansion joints and deflection fittings.
d. Backwater valves.
e. Cleanouts.
f.
Encasement for piping.
g. Manholes.
2. Definitions:
a. DIP: Ductile Iron Pipe
b. PVC: Polyvinyl chloride plastic pipe
3. Regulatory Requirements: Comply with the Metropolitan Water Reclamation District
(MWRD) requirements, including inspections prior to and during work.
4. Performance Requirements:
a. Pressure pipe pressure ratings: At least equal to system operating pressure, but
not less than 150 psig.
5. Project Conditions:
a. Site Information: Architect-Engineer shall coordinate site survey, research public
utility records, and verify existing utility locations with NU representatives. Locate
existing structures and piping to be closed and abandoned.
b. Coordinate the Interruption of Existing Sanitary Sewerage Service with NU.
Contract Documents should indicate that interruption of service to facilities
occupied by NU or others is only permitted under the following conditions and
then only after arranging to provide temporary service according to requirements
indicated:
i. Notify NU no fewer than fourteen (14) days in advance of proposed
interruption of service.
FACILITY SANITARY SEWERS
33 1313 - 1
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
ii. Do not proceed with interruption of service without NU's written
permission.
6. Products: The following products and materials indicate NU preferences.
specific project requirements with NU during the design phase of the project.
Review
a. Hub-and-Spigot, Cast-Iron Soil Pipe and Fittings:
i. Pipe and Fittings: ASTM A 74, service class.
ii. Gaskets: ASTM C 564, rubber.
iii. Calking Materials: ASTM B 29, pure lead and oakum or hemp fiber.
b. Ductile-Iron Pipe and Fittings:
i. Push-on-Joint Piping:
1. Pipe: AWWA C151 ANSI A21.51, cement lined with bituminous
coating per AWWA C104 ANSI 21.4 thickness class 50 52 55 56
per AWWA C150 ANSI A 21.50.
2. Standard Fittings: AWWA C110, ductile or gray iron.
3. Gaskets: AWWA C111 ANSI 21.11, rubber, of shape matching
pipe and fittings.
ii. Mechanical-Joint Piping:
1. Pipe: AWWA C151 ANSI A21.51, with bolt holes in bell.
2. Standard Fittings:
holes in bell.
AWWA C110, ductile or gray iron, with bolt
3. Compact Fittings: AWWA C153, with bolt holes in bells.
4. Glands: Cast or ductile iron; with bolt holes and high-strength,
cast-iron or high-strength, low-alloy steel bolts and nuts.
5. Gaskets: AWWA C111, ANSI A21.11 rubber, of shape matching
pipe, fittings, and glands.
c. PVC Pipe and Fittings:
i. PVC Type PSM Sewer Piping, 15-inch and smaller:
1. Pipe: ASTM D 3034, SDR 26 PVC Type PSM sewer pipe with
bell-and-spigot ends for gasketed joints.
2. Fittings: ASTM D 3034, PVC with bell ends.
3. Gaskets: ASTM F 477, elastomeric seals.
FACILITY SANITARY SEWERS
33 1313 - 2
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
ii. PVC Type PSM Sewer Piping,18-inch and larger:
1. Pipe: ASTM F 679, T-1 wall thickness, bell and spigot for
gasketed joints.
2. Fittings: ASTM F679
3. Gaskets: ASTM F 477, elastomeric seals.
iii. PVC Pressure Piping:
1. Pipe: AWWA C900, Class 150 Class 200 PVC pipe with bell-andspigot ends for gasketed joints.
2. Fittings: AWWA C900, Class 150 Class 200 PVC pipe with bell
ends.
3. Gaskets: ASTM F 477, elastomeric seals.
4. Ductile-Iron, Compact Fittings: AWWA C153, for push-on joints.
5. Gaskets for Ductile-Iron Fittings: AWWA C111, rubber.
d. Non-Pressure-Type Transition Couplings:
i. Comply with ASTMC 1173, elastomeric, sleeve-type, reducing or
transition coupling, for joining underground non-pressure piping. Include
ends of same sizes as piping to be joined and corrosion-resistant-metal
tension band and tightening mechanism on each end.
ii. Sleeve Materials:
1. For Cast-Iron Soil Pipes: ASTM C 564, rubber.
2. For Plastic Pipes: ASTM F 477, elastomeric seal or ASTM D 926,
PVC.
3. For Dissimilar Pipes: ASTM D 5926, PVC or other material
compatible with pipe materials being joined.
e. Unshielded, Flexible Couplings:
Elastomeric sleeve with stainless steel
corrosion-resistant-metal tension band and tightening mechanism on each end.
f.
Shielded, Flexible Couplings: ASTM C 1460, elastomeric or rubber sleeve with
full-length, corrosion-resistant stainless steel outer shield and corrosion-resistant
stainless steel tension band and tightening mechanism on each end.
g. Pressure-Type Pipe Couplings:
i. Metal, bolted, mechanical joint sleeve, reducing or transition coupling, for
joining underground pressure piping. Include 200-psig minimum pressure
rating and ends of same sizes as piping to be joined.
FACILITY SANITARY SEWERS
33 1313 - 3
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
1. Gasket Material: Natural or synthetic rubber.
2. Metal Component Finish: Corrosion-resistant coating or material.
h. Ductile-Iron Deflection Fittings: Compound coupling fitting with ball joint, flexing
section, gaskets, and restrained-joint ends complying with AWWA C110 or
AWWA C153. Include rating for 250-psig minimum working pressure and for up
to 15 degrees of deflection.
i.
Backwater Valves:
i. Cast-Iron Backwater Valves:
bolted cover, with bronze seat.
ASME A112.14.1, gray-iron body and
ii. PVC Backwater Valves: Horizontal type; with PVC body, PVC removable
cover, and PVC swing check valve.
j.
Cleanouts:
i. Cast-Iron Cleanouts: ASME A112.36.2M, round, gray-iron housing with
clamping device and round, secured, scoriated, gray-iron cover. Include
gray-iron ferrule with inside calk or spigot connection and countersunk,
tapered-thread, brass closure plug.
1. Top-Loading Classifications: Heavy Duty.
2. Sewer Pipe Fitting and Riser to Cleanout: ASTM A 74, Service
class, cast-iron soil pipe and fittings.
ii. PVC Cleanouts: PVC body with PVC threaded plug. Include PVC sewer
pipe fitting and riser to cleanout of same material as sewer piping.
k. Encasement for Piping:
i. Standard: ASTM A 674 or AWWA C105.
ii. Material: polyethylene film of 0.008-inch (0.20-mm) minimum thickness.
iii. Form: Sheet or tube.
iv. Color: Black or natural.
l.
Standard Precast Concrete Manholes: ASTM C 478, precast, reinforced
concrete, of depth indicated, with provision for sealant joints.
i. Ballast: Increase thickness of precast concrete sections or add concrete
to base section, as required to prevent flotation.
ii. Riser Sections: Of length to provide depth indicated.
iii. Top Section: Eccentric-cone type unless flat-slab-top type is required;
with top of cone of size that matches grade rings.
FACILITY SANITARY SEWERS
33 1313 - 4
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
iv. Section Joint Sealant: ASTM C 443 rubber gasket.
v. Resilient Pipe Connectors: ASTM C 923 rubber boot, cast or fitted into
manhole walls, for each pipe connection. Boot shall result in a water tight
connection conforming to the performance requirements of ASTM C 443.
vi. Steps: Cast Iron steps conforming to the performance standards of
ASTM C 478. Omit steps if total depth from floor of manhole to finished
grade is less than 48. Cast or anchor steps into sidewalls at 16-inch
intervals inches.
vii. Grade (Adjusting) Rings: Reinforced-concrete rings, with diameter
matching manhole frame and cover, and with height as required to adjust
manhole frame and cover to indicated elevation and slope. Maximum per
Drawings.
m. Manhole Frames and Covers: Include indented top design with lettering cast into
cover, using wording equivalent to "SANITARY SEWER."
i. Material: ASTM A 48, Class 35 gray ASTM A 536, Grade 60-40-18
ductile iron unless otherwise indicated.
n. Manhole-Cover Inserts: Manufactured, plastic form, of size to fit between
manhole frame and cover and designed to prevent stormwater inflow. Include
handle for removal and gasket for gastight sealing.
i. Type: Solid.
o. External Chimney Seal: Rubber sleeves shall be extruded from a high grade
rubber compound meeting the applicable requirements of ASTM C923. Sleeves
shall be double or triple pleated with a minimum unexpanded vertical height of 8
inches, a minimum thickness of 3/16 inch, capable of expanding not less than 2
inches vertically when installed.
i. Screws, bolts and nuts: Stainless steel, ASTM F-593 and 594 Type 304.
ii. Expansion Bands shall be16 gauge thickness, 1-3/4 inches wide and
made of stainless steel meeting the requirements of ASTM A240, Type
304.
p. Protective Coatings:
One- or two-coat, coal-tar epoxy; 15-mil minimum
thickness, unless otherwise indicated; factory or field applied to the exterior and
interior surfaces.
q. Manhole Channels and Benches: Factory or field formed from concrete.
Portland cement design mix, 4000 psi minimum. Include channels and benches
in manholes.
i. Channels: Concrete invert, formed to same width as connected piping,
with height of vertical sides to three-fourths of pipe diameter. Form
curved channels with smooth, uniform radius and slope.
FACILITY SANITARY SEWERS
33 1313 - 5
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
ii. Invert Slope: 1 percent through manhole.
iii. Benches: Concrete, sloped to drain into channel.
iv. Slope: 8 percent.
7. Field Quality Control:
a. Inspections: Require inspection and report by Contractor of interior of piping to
determine whether line displacement or other damage has occurred. Inspections
should occur after approximately 24 inches of backfill is in place, and again at
completion of Project.
i. Contractor shall submit separate report for each system inspection.
ii. Defects requiring correction include the following:
1. Alignment: Less than full diameter of inside of pipe is visible
between structures.
2. Deflection: Flexible piping with deflection that prevents passage
of ball or cylinder of size not less than 92.5 percent of piping
diameter.
3. Damage:
piping.
Crushed, broken, cracked, or otherwise damaged
4. Infiltration: Water leakage into piping.
5. Exfiltration: Water leakage from or around piping.
iii. Contractor shall replace defective piping using new materials, and repeat
inspections until defects are within allowances specified.
iv. Contractor shall reinspect and repeat procedure until results are
satisfactory.
b. Testing: Contractor shall test new piping systems, and parts of existing systems
that have been altered, extended, or repaired, for leaks and defects.
i. Contractor shall not enclose, cover, or put into service before inspection
and approval.
ii. Contractor shall test completed piping systems according to requirements
of authorities having jurisdiction.
iii. Contractor shall schedule tests and inspections by authorities having
jurisdiction with at least 24 hours' advance notice.
iv. Contractor shall submit separate report for each test.
FACILITY SANITARY SEWERS
33 1313 - 6
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
v. Hydrostatic Tests: Contractor shall test sanitary sewerage according to
requirements of authorities having jurisdiction and per Exfiltration and
Infiltration Method Procedures per the Standard Specifications for Water
and Sewer Construction in Illinois latest edition where no separate written
standards exist.
vi. Air Tests:
Test sanitary sewerage according to requirements of
authorities having jurisdiction, UNI-B-6, and the following:
1. Option: Test plastic gravity sewer piping according to ASTM F
1417
2. Option: Test clay gravity sewer piping according to ASTM C 828.
vii. Force Main: Perform hydrostatic test after thrust blocks, supports, and
anchors have hardened. Test at pressure not less than 1-1/2 times the
maximum system operating pressure, but not less than 150 psig.
viii. Ductile-Iron Piping: Test according to AWWA C600, "Hydraulic Testing"
Section.
ix. PVC Piping: Test according to AWWA M23, "Testing and Maintenance"
Chapter.
x. Manholes: Perform hydraulic test according to ASTM C 969.
xi. Leaks and loss in test pressure constitute defects that must be repaired.
c. Replace leaking piping using new materials, and repeat testing until leakage is
within allowances specified.
END OF SECTION
FACILITY SANITARY SEWERS
33 1313 - 7
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
This page intentionally left blank
FACILITY SANITARY SEWERS
33 1313 - 8
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
DIVISION 33 – UTILITIES
SECTION 33 4100 – STORM UTILITY DRAINAGE PIPING
1. General: This section includes performance requirements and minimum requirements
for gravity-flow, non-pressure storm drainage outside the building.
2. Definitions:
a. PVC: Polyvinyl chloride plastic
b. HDPE: High Density Polyethylene.
c. RCP: Reinforce Concrete Sewer Pipe
d. CSP: Non-reinforced Concrete Sewer Pipe
3. Performance Requirements – Gravity-Flow, Nonpressure, Drainage-Piping Pressure
Ratings:
a. At least equal to system test pressure.
4. Project Conditions:
a. Site Information: Architect-Engineer shall coordinate site survey, research public
utility records, and verify existing utility locations with NU representatives. Locate
existing structures and piping to be closed and abandoned.
b. Locate existing structures and piping to be closed and abandoned.
a. Existing Storm Drainage Service: Contract Documents should indicate that
interruption of service to facilities occupied by NU or others is only permitted
under the following conditions and then only after arranging to provide temporary
service according to requirements indicated:
i. Notify NU no fewer than two days in advance of proposed interruption of
service.
i. Do not proceed with interruption of service without NU's written
permission.
5. Products:
a. Pipes and Fittings:
i. Hub-and-Spigot, Cast-Iron Soil Pipe and Fittings: ASTM A 74, gray iron,
for gasketed joints.
1. Gaskets: ASTM C 564, rubber, compression type, thickness to
match class of pipe.
STORM UTILITY DRAINAGE PIPING
33 4100 - 1
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
ii. Ductile Iron Pipe and Fittings: AWWA C151, for push-on joints.
1. Standard-Pattern, Ductile-Iron Fittings: AWWA C110, ductile or
gray iron, for push-on joints.
2. Gaskets: AWWA C111, rubber.
iii. Corrugated-Steel Pipe: Not permitted.
iv. Corrugated HDPE Drainage Tubing and Fittings: AASHTO M 252,
Type S, with smooth waterway for coupling joints.
1. Soiltight Couplings: AASHTO M 252, corrugated, matching tube
and fittings to form soiltight joints.
v. Corrugated HDPE Pipe and Fittings: AASHTO M 294, Type S, with
smooth waterway for coupling
1. Soiltight Couplings: AASHTO M 294, corrugated, matching pipe
and fittings to form soiltight joints.
2. Silttight Couplings: PE sleeve with ASTM D 1056, Type 2,
Class A, Grade 2 gasket material that mates with pipe and fittings
to form silttight joints.
vi. PVC Pressure Pipe: AWWA C900/C905, Class 150, for gasketed joints.
1. PVC Pressure Fittings: AWWA C907, for gasketed joints.
2. Gaskets for PVC Piping: ASTM F 477, elastomeric seals.
vii. PVC Sewer Pipe and Fittings:
1. PVC Sewer Pipe and Fittings, 15” and Smaller: ASTM D 3034,
SDR 26, gasketed joints.
2. Gaskets: ASTM F 477, elastomeric seals.
viii. PVC Sewer Pipe and Fittings, 18”and Larger: ASTM F 679, T-1 wall
thickness, bell and spigot for gasketed joints.
1. Gaskets: ASTM F 477, elastomeric seals.
ix. Nonreinforced-Concrete Sewer (CSP) Pipe and Fittings: Not permitted.
x. Reinforced-Concrete (RCP) Sewer Pipe and Fittings: ASTM C 76,
Class III, with gasketed joints.
1. Gaskets: ASTM C 443, rubber.
STORM UTILITY DRAINAGE PIPING
33 4100 - 2
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
xi. Reinforced-Concrete Arch Pipe: ASTM C 506, Class IV, for banded
joints.
1. Sealing Bands: ASTM C 877, Type I.
xii. Reinforced-Concrete Elliptical Pipe: ASTM C 507, Class III, for banded
joints.
1. Pattern: Type HE, horizontal.
2. Pattern: Type VE, vertical.
3. Sealing Bands: ASTM C 877, Type I.
b. Special Pipe Couplings and Fittings:
i. Comply with ASTM C 1173, elastomeric, sleeve-type, reducing or
transition coupling, for joining underground nonpressure piping. Include
ends of same sizes as piping to be joined, and corrosion-resistant-metal
tension band and tightening mechanism on each end.
ii. Sleeve Materials: ASTM C 1173, rubber or elastomeric sleeve and band
assembly fabricated to mate with OD of pipes to be joined, for
nonpressure joints.
1. Sleeve Material for Concrete Pipe: ASTM C 443, rubber.
2. Sleeve Material for Cast-Iron Soil Pipe: ASTM C 564, rubber.
3. Sleeve Material for Plastic Pipe: ASTM F 477, elastomeric seal.
4. Sleeve Material for Dissimilar Pipe: Compatible with pipe
materials being joined.
5. Bands: Stainless steel, at least one at each pipe insert.
iii. Shielded Couplings: ASTM C 1277 assembly of metal shield or housing,
corrosion-resistant fasteners, and rubber sleeve with integral, center pipe
stop.
1. Heavy-Duty, Shielded, Stainless-Steel Couplings, 10-inch and
Smaller: With ASTM A 666, Type 301 or Type 304, stainless-steel
shield; 2 or more stainless-steel bands and tightening devices;
and ASTM C 564, rubber sleeve.
2. Heavy-Duty, Shielded, Stainless-Steel Couplings, 12-inch and 15inch: With ASTM A 666, Type 301 or Type 304, stainless-steel
shield; stainless-steel bands and tightening devices; and
ASTM C 564, rubber sleeve.
STORM UTILITY DRAINAGE PIPING
33 4100 - 3
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
iv. Unshielded Flexible Couplings: Elastomeric sleeve with stainless steel
tension band and tightening mechanism on each end.
c. Normal-Traffic Precast Concrete Manholes: ASTM C 478, precast, reinforced
concrete, of depth indicated, with provision for rubber gasketed joints.
i. Ballast: Increase thickness of precast concrete sections or add concrete
to base section, as required to prevent flotation.
ii. Steps: Steel Reinforced Plastic or Cast Iron, individual steps. Wide
enough to allow worker to place both feet on one step and is designed to
prevent lateral slippage off step. Cast or anchor steps into sidewalls at
12- to 16-inch intervals. Omit steps if total depth from floor of manhole to
finished grade is less than 60 inches
iii. Manhole Frames and Covers: ASTM A 536, Grade 60-40-18, ductile-iron
castings designed for heavy-duty service. Include indented top design
with lettering "STORM SEWER" cast into cover.
iv. Resilient Pipe Connectors: ASTM C 923, cast or fitted into manhole
walls, for each pipe connection.
v. Adjusting Rings: Interlocking rings with level or sloped edge in thickness
and diameter matching manhole frame and cover. Include sealant
recommended by ring manufacturer.
vi. Protective Coating: Plant-applied, Bitumastic Coal Tar SSPC-Paint 16,
10-mil minimum thickness applied to exterior surface.
d. Normal-Traffic, Precast Concrete Catch Basins: ASTM C 478, precast,
reinforced concrete, of depth indicated, with provision for rubber gasketed joints.
i. Gaskets: ASTM C 443, rubber.
ii. Steps: Provide one of the following:
1. Fiberglass, individual steps or ladder of a width that allows worker
to place both feet on one step and is designed to prevent lateral
slippage off step.
2. Steel Reinforced Plastic or Cast Iron individual steps. Wide
enough to allow worker to place both feet on one step and is
designed to prevent lateral slippage off step. Cast or anchor steps
into sidewalls at 12- to 16-inch intervals. Omit steps if total depth
from invert to finished grade is less than 60 inches.
iii. Frames and Covers: ASTM A 536, Grade 60-40-18, ductile-iron castings
designed for heavy-duty service.
iv. Pipe Connectors: ASTM C 923, resilient, of size required, for each pipe
connecting to base section.
STORM UTILITY DRAINAGE PIPING
33 4100 - 4
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
v. Adjusting Rings: Interlocking rings with level or sloped edge in thickness
and diameter matching manhole frame and cover. Include sealant
recommended by ring manufacturer.
vi. Protective Coating: Plant-applied, Bitumastic Coal Tar SSPC-Paint 16
10-mil minimum thickness applied to exterior surface.
e. Stormwater Inlets:
i. Curb Inlets: Made with vertical curb opening, of materials and
dimensions according to utility standards.
ii. Gutter Inlets: Made with horizontal gutter opening, of materials and
dimensions according to utility standards. Include heavy-duty frames and
grates.
iii. Combination Inlets: Made with vertical curb and horizontal gutter
openings, of materials and dimensions according to utility standards.
Include heavy-duty frames and grates.
f.
Cleanouts:
i. Gray-Iron Cleanouts: ASME A112.36.2M, round, gray-iron housing with
clamping device and round, secured, scoriated, gray-iron cover. Include
gray-iron ferrule with inside calk or spigot connection and countersunk,
tapered-thread, brass closure plug. Use units with top-loading
classifications according to the following applications:
1. Light Duty: In earth or grass foot-traffic areas.
2. Medium Duty: In paved foot-traffic areas.
3. Heavy Duty: In vehicle-traffic service areas.
4. Extra-Heavy Duty: In roads.
5. Sewer Pipe Fitting and Riser to Cleanout: ASTM A 74, Service
class, cast-iron soil pipe and fittings.
ii. PVC Cleanouts: PVC body with PVC threaded plug. Include PVC sewer
pipe fitting and riser to cleanout of same material as sewer piping.
1. Light Duty: In earth or grass foot-traffic areas.
2. Medium Duty: In paved foot-traffic areas.
3. Heavy Duty: In vehicle-traffic service areas.
4. Extra-Heavy Duty: In roads.
STORM UTILITY DRAINAGE PIPING
33 4100 - 5
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
iii. Gray-Iron Area Drains: ASME A112.21.1M, round, gray-iron body with
anchor flange and round, secured, gray-iron grate. Include bottom outlet
with inside calk or spigot connection, of sizes indicated. Use units with
top-loading classifications according to the following applications:
1. Medium Duty: In paved foot-traffic areas.
2. Heavy Duty: In vehicle-traffic, structural loading; of depth, shape,
dimensions, and appurtenances indicated.
3. Ballast: Increase thickness of concrete, as required to prevent
flotation.
g. Polymer-Concrete, Channel Drainage Systems: Modular system of precast,
polymer-concrete channel sections, grates, and appurtenances; designed so
grates fit into channel recesses without rocking or rattling. Include number of
units required to form total lengths indicated.
i. Sloped-Invert, Polymer-Concrete Systems: Include the following
components:
1. Channel Sections: Interlocking-joint, precast, modular units with
end caps, rounded bottom, with built-in invert slope of 0.6 percent
minimum and with outlets in number, sizes, and locations
indicated. Include extension sections necessary for required
depth.
a. Frame: Include gray-iron or steel frame for grate.
2. Grates with manufacturer's designation "Heavy Duty," with slots or
perforations that fit recesses in channels.
a. Material: Provide fiberglass, galvanized steel, or stainless
steel.
3. Locking Mechanism: Manufacturer's standard device for securing
grates to channel sections.
h. Plastic, Channel Drainage Systems: Modular system of plastic channel sections,
grates, and appurtenances; designed so grates fit into frames without rocking or
rattling. Include number of units required to form total lengths indicated.
i. Fiberglass Systems: Include the following components:
1. Channel Sections: Interlocking-joint, fiberglass modular units, with
built-in invert slope of approximately 1 percent and with end caps.
Include rounded or inclined inside bottom surface, with outlets in
number, sizes, and locations indicated.
2. Factory- or field-attached frames that fit channel sections and
grates.
STORM UTILITY DRAINAGE PIPING
33 4100 - 6
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
a. Material: Galvanized steel Stainless steel Bronze
3. Grates with slots or perforations that fit frames.
a. Material: Fiberglass Galvanized steel Gray iron Stainless
steel Bronze.
4. Drainage Specialties: Include the following plastic components:
a. Large Catch Basins: 24-inch- square plastic body, with
outlets in number and sizes indicated. Include gray-iron
frame and slotted grate.
b. Small Catch Basins: 12-by-24-inch plastic body, with
outlets in number and sizes indicated. Include gray-iron
frame and slotted grate.
6. Identification:
a. Requirements include installing green warning tapes directly over piping and at
outside edges of underground structures.
i. Use warning tape or detectable warning tape over ferrous piping.
ii. Use detectable warning tape over nonferrous piping and over edges of
underground structures.
7. Field Quality Control:
a. Contractor shall clear interior of piping and structures of dirt and superfluous
material as work progresses. Maintain swab or drag in piping, and pull past each
joint as it is completed.
i. In large, accessible piping, brushes and brooms may be used for
cleaning.
ii. Place plug in end of incomplete piping at end of day and when work
stops.
iii. Flush piping between manholes and other structures to remove collected
debris, if required by authorities having jurisdiction.
b. Inspections: Contractor shall inspect interior of piping to determine whether line
displacement or other damage has occurred. Inspect after approximately 24
inches of backfill is in place, and again at completion of Project.
i. Submit separate reports for each system inspection.
ii. Defects requiring correction include the following:
STORM UTILITY DRAINAGE PIPING
33 4100 - 7
NORTHWESTERN UNIVERSITY
Technical Standards
Issuance Date: 01.01.2014
1. Alignment: Less than full diameter of inside of pipe is visible
between structures.
2. Deflection: Flexible piping with deflection that prevents passage
of ball or cylinder of size not less than 92.5 percent of piping
diameter.
3. Crushed, broken, cracked, or otherwise damaged piping.
4. Infiltration: Water leakage into piping.
5. Exfiltration: Water leakage from or around piping.
iii. Contractor shall replace defective piping using new materials, and repeat
inspections until defects are within allowances specified.
iv. Contractor shall reinspect and repeat procedure until results are
satisfactory.
c. Testing: Contractor shall test new piping systems, and parts of existing systems
that have been altered, extended, or repaired, for leaks and defects.
i. Contractor shall not enclose, cover, or put into service before inspection
and approval.
ii. Contractor shall test completed piping systems according to authorities
having jurisdiction.
iii. Contractor shall schedule tests and inspections by authorities having
jurisdiction with at least 24 hours' advance notice.
iv. Contractor shall submit separate reports for each test.
v. Contractor shall replace leaking piping using new materials, and repeat
testing until leakage is within allowances specified.
END OF SECTION
STORM UTILITY DRAINAGE PIPING
33 4100 - 8
NORTHWESTERN UNIVERSITY
APPENDIX
A. Division 01 – General:
1. NU AutoCAD Standard Layers, dated 5/26/2004
2. NU Design Guidelines for Interior Finishes, dated 1/1/2014
3. NU Design Checklist and Guidance to Life Safety Systems, dated 2/10/2014
B. Division 25 – Integrated Automation:
1. NU Direct Digital Control Standards dated 12/18/2013
2. NU DDC SI Spec dated 2/12/2014
C. Division 26 – Electrical:
1. NU Standard Exterior Light Fixture – Lumec
2. NU Standard Metering Enclosure and Wiring Diagram
3. NU Standard CCTV Equipment – Pelco
4. NU Standard Emergency Telephone – Ramtel
5. NU Standard AED Cabinet – HeartStation
D. Division 27 – Communications:
1. NUIT Standards included by reference only. Contact NU Project Manager
for additional information.
E. Division 32 – Exterior Improvements:
1. NU Standard Site Furnishings – Gretchen Bench – Landscape Forms
2. NU Standard Site Furnishings – Bike Rack – Wabash Valley
3. NU Standard Site Furnishings – Trash / Recycling – Victor Stanley
Date of Issuance: January 1, 2014
Appendix - 1
Northwestern University
Facilities Management - Planning
AutoCAD Standard Layers (using plotstyle "NU plotstyle 1.ctb)
Revised: 26 May 2004
File: Northwestern University CAD Layer Standards Rev.xls
Layer Name
ARCHITECTURAL LAYERS
A-ANNO
A-ANNO-AREA
A-ANNO-ASGN
A-ANNO-DIMS
A-ANNO-TITL
A-ANNO-USE
A-POLYLINE
A-AREA-IDEN
A-AREA-PATT
A-CLNG
A-CLNG-GRID
A-COLS
A-DOOR
A-EQIP
A-FLOR-CASE
A-FLOR-CHSE
A-FLOR-EVTR
A-FLOR-IDEN
A-FLOR-PATT
A-FLOR-PFIX
A-FLOR-SLAB
A-FLOR-STRS
A-FLOR-TPTN
A-FURN
A-GLAZ
A-GLAZ-SILL
A-LAB-CASE
A-LAB-SINK
A-LAB-TEXT
A-LITE
A-PORCH
A-ROOF
A-WALL-CAGE
A-WALL-EXTR
A-WALL-INTR
CIVIL LAYERS
C-BLDG
C-COMM
C-ELEC
C-FIRE
C-IT
C-NGAS
C-PKNG
C-PROP
C-ROAD
C-SDWK
C-STEAM
C-SSWR
C-TOPO
C-WATR
C-TUNL
Description
General annotation that does not fit into any other category
Area Calculation
Assignee
Dimensions
Building Name and Floor Number
Use
Area Calculation Boundary line
Room Numbers, Tennant ID, Area Calcs
FM Space hatch patterns
Ceiling Information
Ceiling Grid
Columns
Doors
Equipment
Casework
Chases and other Vertical Penetrations
Elevator Cars and Equipment
Room Numbers, Names, Targets
Floor Tiles and other Surface Patterns
Plumbing Fixtures
Floor Edges that do not meet walls, Slab Perforations, Stages
Stair Treads, Escalators, Ladders
Toilet Partitions
Furniture
Windows, Window Walls, Curtain Walls, Glazed Partitions
Windowsills
Fixed Lab Casework/Benches
Sinks in Laboratory only
Lab Fixture Text
Light Fixtures
Porches, porch walls
Roof
Interior Fences or Caged Areas
Exterior walls
Interior walls
Built elements
Site Communication/Telephone Poles, Boxes, Towers
Underground Electric
Fire Protection-Underground Lines
IT Communication Lines-Underground
Natural Gas-Pipes, Manholes, Meters, Storage Tanks
Parking Lots
Property Lines, Survey Benchmarks
Roads
Sidewalks & Alleys
Steam & Condensate
Sanitary Sewers-Manholes, Pumping Stations
Contour Lines and Elevations
Domestic Water-Underground Lines
Underground Tunnel
Page 1 of 2
Display
Color #
Linetype
Print Color
3
7
7
140 *
2
7
1
7***
7
3
4
170*
90 *
5
5
210*
30 *
3
30
5
5
10 *
151***
5
130 *
5
190
135
140
3
3
5
190
1
3
Cont
Cont
Cont
Cont
Cont
Cont
Cont
Cont
Cont
Cont
Cont
Cont
Cont
Cont
Cont
Cont
Cont
Cont
Cont
Cont
Cont
Cont
Cont
Hidden2
Cont
Cont
Mix
Cont
Cont
Cont
Cont
Cont
Hidden
Cont
Cont
Black
Black
Black
Lt. Blue
Black
Black
Black
Black
FM Space**
Black
Black
Dk. Blue
Green
Black
Black
Magenta
Orange
Black
Orange
Black
Black
Red
Black
Black
Cyan
Black
190
135
140
Black
Black
Black
190
Black
Black
2
2
2
3
4
3
3
1
3
3
3
3
5
3
3
Cont
Cont
Hidden2
Dashdot2
Cont
Cont
Cont
Phantom2
Cont
Cont
Cont
Cont
Cont
Hidden2
Cont
Black
Black
Black
Black
Black
Black
Black
Black
Black
Black
Black
Black
Black
Black
Black
ELECTRICAL LAYERS
E-COMM
E-CTRL
E-FIRE
E-LITE
E-LTNG
E-POWR
E-SERT
E-SITE-UNDR
Telephone, Communication Outlets
Electric Control Systems
Fire Alarm, Fire Extinguishers
Lighting
Lightning Protection System
Power
Security
Underground Electrical lines
FIRE PROTECTION
F-PROT
Fire System
LANDSCAPE LAYERS
L-IRRG
L-PLNT
L-PLNT-BEDS
L-PLNT-TURF
L-SITE
L-SITE-FURN
L-SITE-LITE
L-SITE-REC
L-SITE-SIGN
L-WALK
Irrigation Systems
Plant & Landscape Materials
Rock, bark and Other Landscaping Beds
Lawn Areas
Site elements
Site Furnishings
Exterior Site Lighting
Athletic and Recreational Fields
Signage and Donor Info
Walks and Steps
MECHANICAL LAYERS
M-CONT
M-DUST
M-ELHT-EQPM
M-HVAC
M-MDGS
Controls & Instrumentations
Dust & Fume Collection Sys (and Riser Diagram)
Electric Heat Equipment (and Riser Diagram)
HVAC System
Medical Gas Systems
PLUMBING LAYERS
P-FIXT
Plumbing Fixtures
STRUCTURAL LAYERS
S-GRID
Column Grid
3
3
3
3
3
3
3
3
Cont
Cont
Cont
Hidden2
Cont
Hidden2
Cont
Hidden2
Black
Black
Black
Black
Black
Black
Black
Black
3
Cont
Black
2
151***
3
3
2
2
3
4
3
3
Hidden2
Cont
Cont
Cont
Cont
Cont
Cont
Cont
Cont
Cont
Black
Black
Black
Black
Black
Black
Black
Black
Black
Black
3
3
3
3
3
Cont
Cont
Cont
Cont
Hidden2
Black
Black
Black
Black
Black
5
Cont
Black
4
Hidden
Black
* denotes that layer prints in color, otherwise, all layers print as black (see gradient note below)
** denotes that the plotted color is defined by the FM Space program
***L-PLNT-Color 4 revised to 151 because it read too dark. (revised July 20 by Dana)
*** A-AREA-IDEN - Color #40 is set by FM Space. Change color in AutoCAD to color #7 (white) (revised 29 April 2004)
***A-FLOR-TPTN-Color #4 changed to 151, read too dark for bathrooms, (revised July 21 by Dana)
Gradient Note:
Color numbers 1-5 denote a gradient from darkest (1) to lightest (5) when plotstyle "NU plotstyle 1.ctb" is
used. See document R:\CAD Layer Documentation\NU Using Color.dwg for notes about plotted colors and
lineweights.
Page 2 of 2
NORTHWESTERN UNIVERSITY
Appendix A2 – Interior Finishes
Issuance Date: 01.01.2014
The following is a summary of recommended interior finishes for the most common space types. Review project specific requirements with the NU
Project Manager. Review requirements for specialty spaces including auditoriums, research labs, residential spaces, and food service with the NU
Manager.
Space Type
Design Considerations
Flooring
Wall Base
Walls
Ceiling
Entrances / Vestibules
High Volume Traffic
Review options with NU
Project Manager
Review options with NU
Project Manager
Acrylic latex paint
Gypsum ceiling board;
Low VOC
Review alternatives with
NU Project Manager
Slip Resistance
Walk-off mats
Satin Finish
Acoustic Considerations
Review alternatives with
NU Project Manager
STC 45-50 Separation
Lobbies
High Volume Traffic
Review options with NU
Project Manager
Review options with NU
Project Manager
Review options with NU
Project Manager
Review options with NU
Project Manager
High Volume Traffic
Resilient tile or sheet;
4-inch high rubber
Acrylic latex paint
Slip Resistance
Patterned carpet
Suspended acoustic ceiling
system
Slip Resistance
Acoustic Considerations
STC 45-50 Separation
Corridors
Low VOC
Acoustic Considerations
Satin Finish
STC 50 Separation
9/16-inch suspended
ceiling grid
Acoustic ceiling panels
0.65 NRC / 0.85 LRV
Stairways
High Volume Traffic
Slip Resistance
Acoustic Considerations
STC 45-50 Separation
Concrete or terrazzo stair
treads
Review options with NU
Project Manager
Review alternatives with
NU Project Manager
Epoxy paint
Low VOC
Eggshell Finish
Wall protection
Suspended acoustic ceiling
system
9/16-inch suspended
ceiling grid
Acoustic ceiling panels
0.65 NRC / 0.85 LRV
Page - 1
NORTHWESTERN UNIVERSITY
Appendix A2 – Interior Finishes
Issuance Date: 01.01.2014
Space Type
Design Considerations
Flooring
Wall Base
Walls
Ceiling
Classrooms
Medium Volume Traffic
Resilient tile or sheet
4-inch high rubber
Acrylic latex paint
Suspended acoustic ceiling
system
Acoustic Considerations
Low VOC
STC 50 Separation
Satin Finish
Dimmable / Controllable
Lighting
9/16-inch suspended
ceiling grid
Acoustic ceiling panels
0.65 NRC / 0.85 LRV
Computer Labs
Medium Volume Traffic
Resilient tile or sheet;
Acoustic Considerations
Patterned carpet
4-inch high rubber
Acrylic latex paint
Low VOC
STC 50 Separation
Satin Finish
Dimmable / Controllable
Lighting
Labs – Dry
9/16-inch suspended
ceiling grid
Acoustic ceiling panels
0.65 NRC / 0.85 LRV
Medium Volume Traffic
Resilient sheet;
4-inch high rubber;
Acrylic latex paint
Acoustic Considerations
Epoxy
Integral epoxy wall base
Low VOC
STC 45-50 Separation
Satin Finish
Dimmable / Controllable
Lighting
Labs – Wet
Suspended acoustic ceiling
system
Suspended acoustic ceiling
system
9/16-inch suspended
ceiling grid
Acoustic ceiling panels
0.65 NRC / 0.85 LRV
Medium Volume Traffic
Resilient sheet;
4-inch high rubber;
Acrylic latex paint
Acoustic Considerations
Epoxy
Integral epoxy wall base
Low VOC
STC 45-50 Separation
Satin Finish
Dimmable / Controllable
Lighting
Suspended acoustic ceiling
system
9/16-inch suspended
ceiling grid
Acoustic ceiling panels
0.65 NRC / 0.85 LRV
Slip Resistance / Spills /
Chemical Staining
Page - 2
NORTHWESTERN UNIVERSITY
Appendix A2 – Interior Finishes
Issuance Date: 01.01.2014
Space Type
Design Considerations
Flooring
Wall Base
Walls
Ceiling
Offices
Low Volume Traffic
Patterned carpet
4-inch high rubber
Acrylic latex paint
Suspended acoustic ceiling
system
STC 45-50 Separation
Low VOC
Dimmable / Controllable
Lighting
Satin Finish
9/16-inch suspended
ceiling grid
Acoustic ceiling panels
0.65 NRC / 0.85 LRV
Conference Room
Low Volume Traffic
Patterned carpet
4-inch high rubber
Acrylic latex paint
Acoustic Considerations
Low VOC
STC 50-55 Separation
Satin Finish
Dimmable / Controllable
Lighting
0.65 NRC / 0.85 LRV
Medium Volume Traffic
Resilient tile or sheet;
Acoustic Considerations
Patterned carpet
4-inch high rubber
Acrylic latex paint
Low VOC
STC 45-50 Separation
Satin Finish
Dimmable / Controllable
Lighting
Suspended acoustic ceiling
system
9/16-inch suspended
ceiling grid
Acoustic ceiling panels
0.65 NRC / 0.85 LRV
Chemical Staining
Storage Room
9/16-inch suspended
ceiling grid
Acoustic ceiling panels
Audio/Visual Systems
Copy Room
Suspended acoustic ceiling
system
Low Volume Traffic
Resilient tile or sheet;
STC 50 Separation
Patterned carpet
4-inch high rubber
Acrylic latex paint
Low VOC
Built-in shelving vs.
furniture
Satin Finish
Suspended acoustic ceiling
system
9/16-inch suspended
ceiling grid
Acoustic ceiling panels
0.65 NRC / 0.85 LRV
Page - 3
NORTHWESTERN UNIVERSITY
Appendix A2 – Interior Finishes
Issuance Date: 01.01.2014
Space Type
Design Considerations
Flooring
Wall Base
Walls
Ceiling
Public Restroom
High Volume Traffic
Ceramic Tile;
Ceramic Tile;
Ceramic Tile;
Gypsum ceiling board;
STC 50 Separation
Porcelain Tile;
Porcelain Tile;
Porcelain Tile;
Slip Resistance / Spills
Terrazzo;
Terrazzo;
Suspended acoustic ceiling
system
9/16-inch suspended
ceiling grid
Acoustic / moisture
resistant ceiling panels
0.65 NRC / 0.85 LRV
Janitors Closet
Low Volume Traffic
Sealed concrete;
STC 50 Separation
Resilient tile or sheet
4-inch high rubber
Epoxy paint
Low VOC
Slip Resistance / Spills /
Chemical Staining
Eggshell Finish
Wall protection
Suspended acoustic ceiling
system
9/16-inch suspended
ceiling grid
Acoustic ceiling panels
0.65 NRC / 0.85 LRV
Mechanical / Electrical
Rooms
Low Volume Traffic
Sealed concrete
4-inch high rubber
Epoxy paint
STC 50 Separation
Low VOC
Review specific
requirements in Technical
Standards
Eggshell Finish
Page - 4
Exposed construction,
painted
NORTHWESTERN UNIVERSITY
Design checklist and guidance to Life Safety Systems
(10-Feb 2014)
Building Information provided by Facilities Management Planning
(The questions will be turned into statements for the drawing notes)
1. Building Name:__________________________________
2. Building Address:_____________________
3. Building:
NEW
EXISTING
4. Building Stories (total):_________________
5. Total Building Area in square feet :___________________
6. Building height:____________________
7. IBC Building Use (occupancy):_______________
8. The building is used for:______________________________________
9. IBC Building Construction Type:______________
10. Does the building have a full sprinkler system? YES
NO
PARTIAL
11. Does the building have a generator?
YES
NO
12. Does the building have a fire pump?
YES
NO
13. Is the building on a fire pump loop?
YES
NO
Project Information provided by the Project Manager
(The questions will be turned into statements for the drawing notes)
1. Circle one:
A.
B.
C.
D.
E.
New construction
Demolition
Remodel (cosmetic)
Modest renovation
Renovation (major room/system modifications
1
2. What rooms of the existing building are involved? (list or provide plan)
______________________________________________________________
3. How many square feet of renovation or construction are involved? _________
4. Are existing exit paths being altered?
5. Are exterior doors being added?
YES
NO
YES (contact UP)
N/A
NO
6. Age of existing sprinkler heads (20 year life):__________________________
7. Is a non-water fire suppression system involved in the project?
YES
NO
8. Is a pre-action fire suppression system involved in the project?
YES
NO
10. Are there any smoke evacuation systems (atriums) in the project? YES
NO
11. Is any existing gas detection system getting modified?
NO
N/A
12. Are any areas of refuge getting modified?
YES
NO
13. Are any existing emergency phones getting modified?
YES
NO
14. Are any fossil fuels being used in the project area?
YES
NO
9. Is the existing FS system supported every 12’ to structure properly?
YES NO
N/A
YES
15. Will streets/fire department vehicle access lanes be changed or blocked?
YES NO
N/A
16. Will fire department connections or fire hydrants be changed for this project?
YES NO
N/A
17. Are there adjacent occupied buildings within 30 feet of the new building?
YES NO
N/A
18. Are the areas adjacent to the renovation occupied?
NO
N/A
19. What is the rating of the construction zone boundary walls? 1hr
2hr
NONE
20. Will the HVAC system be turned off in the construction zone?
YES
NO
YES
21. Are the adjacent and vertically adjacent FA zone strobes visible and do they
need to be synched to the renovation area?
YES NO
2
22. Will gas or diesel equipment be used adjacent to occupied buildings?
(Provide equipment scrubbers and carbon filters in AHU’s if YES) YES
NO
Building information provided by Electrical shop
(The questions will be turned into statements for the drawing notes)
1. Existing building FA manufacturer:____________________
2. Age of existing FA system:__________________
3. Is the building sub zoned for evacuation?
YES
NO
4. Does the FA system have voice evacuation capabilities?
YES
NO
5. Does the FA system have central station voice alert capabilities?
YES
NO
6. The FA system has a class A or B communication loop.
7. Where is the fire command center or panel located? ____________________
8. Where are FA annunciators located? ________________________________
9. The existing EM lighting is powered by GENERATOR or BATTERY?
10. Do stairway doors lock to prevent reentry?
Yes
NO
11. New FA circuits will be wired to panel or sub-panel _____________________
12. Where is the sub-panel located? ____________________________________
13. The existing FA circuits for the construction area run through a junction box
located in room ____________________.
14. For non-battery powered systems, is there enough EM power for the EM lighting
in the renovated space?
YES NO
15. Provide last FA system maintenance report.
FM Senior Staff review and decision regarding existing FA system
(Questions four, seven and eight will be turned into statements for the drawing notes)
1. What is the percentage of new or renovated space to the total square feet in the
building? ___________
2. Age of existing FA system:__________________
3
3. How much longer will the existing FA system model be supported by the
manufacturer? _________________
4. Fire alarm systems should be replaced every 15 years by IEEE standards.
5. The existing FA system will be REPLACED
RECONFIGURED NO WORK
6. Age of existing sprinkler heads (20 year life):________________
7. Sprinkler systems should be replaced every 30 years by IEEE standards.
8. The sprinkler Heads will be
KEPT
9. The existing FS system will be REPLACED
REPLACED
RECONFIGURED NO WORK
FA Bidding Guidance:
(The option taken below will be stated in the drawing notes)
1. New building FA system specifications will be limited to approved University
manufacturers.
2. Major renovations in existing building require the FA system to be evaluated for
adequacy and expected life span. If the existing fire alarm system is near to the
end of service life, a new FA system shall be bid to the approved University
manufacturers.
3. Where new FA systems are provided, a predesign walk through will be
scheduled between the Electrical Shop and the design Electrical Engineer.
4. Minor renovations or renovations in buildings with adequate FA systems shall be
designed directly by the existing FA system manufacturer as a consultant to the
Architect. This design or shop drawing will be included in the design package to
the Electrical or General Contractor for bidding. The existing FA system
manufacturer will provide pricing, components and programming as a part of the
Electrical subcontractor’s or General Contractor’s bid.
5. Where existing systems are used or modified, a predesign walk through will be
scheduled between the existing FA manufacturer, Risk Management and the
Electrical Shop.
City of Evanston Requirements (Synopsis)
(include in design drawings as notes)
1. A building permit is required when a project area changes use, changes the exit
path or affects a life Safety system.
4
2. The new or renovated area must be designed in accordance with IBC 2012, the
Illinois Accessibility Code, 2010 NFPA 72 and 2010 NFPA 13.
3. An alarm or sprinkler permit is required for any modification to the life safety
system. The NU Electrical Shop and Risk Management must review the drawings
prior to submission to the City.
4. FA or FS shut-downs cannot be for more than 6 hours a day in occupied
structures.
5. FA or FS shut-downs cannot be for more than 20 hours a week in occupied
structures.
6. Only one safety system (FA or FS) can be shut-down at a time in occupied
structures unless a fire watch plan is pre-approved by the Fire Marshall.
7. Modifying or adding less than 20 sprinkler heads does not require a hydro test
(visual test is required to clear permit).
8. All final room, area of rescue assistance, stair level of exit, and standard exiting
signage including Braille where required must be installed prior to the TCO
inspection.
9. Provide inspection tags for all fire extinguishers.
10. Provide tent signage for extinguishers and hose stations.
11. Fire hose stations must have pressure reducing valves with 2.5”x 1.5” NST
reducers.
12. All student residence halls shall have NFPA 72 and NFPA 13 full and complete
coverage.
13. Provide dual power CO detectors within 15 of every sleeping room.
14. Provide elevator key boxes at all elevator locations.
15. Each building will have a Knox box with all building keys at the front entrance and
other locations requested by EFD.
16. New structures and major renovation projects larger than 5,000 square feet shall
have a sprinkler system installed. The sprinkler requirement for minor renovation
projects of this size shall be reviewed individually by EFD.
5
17. An outside line accessible phone shall be provided in each fire command center.
Fire command centers required by code shall be 200 square feet and have a
minimum dimension of 10 feet.
18. Provide a lighted concrete pad and outside strobe over the STORZ type building
Fire Department Connection.
19. All building exits shall have a paved illuminated path to a public way.
20. Audible devices shall provide a minimum sound pressure level of 15 decibels
above ambient noise in all areas of any building (70 dba minimum or 15 dba
above ambient at the pillow in residential occupancies with the door shut). The
maximum sound pressure level is 110 decibels.
21. It should be noted that upon completion of Fire Alarm hardware modifications
and/or programming modifications, a FA test of at least 10% of the existing
unmodified system will have to be performed in addition to the complete project
area as required by the code.
22. Temporary winter heating propane tanks must be kept 25 feet away from any
building. Gas supply hoses must be kept off of the floor or ground. (requires site
approval from EFD)
23. ABC rated fire extinguishers greater than or equal to Classification 10A: 60B:C
shall be placed at a maximum travel distance of 75 feet in occupied spaces and
50 feet in construction areas.
24. All doors on hold opens will be released and closed and any stairway door shall
be unlocked throughout the entire building upon fire alarm signal.
25. Smoke detectors shall be installed at the top of each stairway and elevator shaft.
26. Install a horn/speaker at the top most level in an exit stair.
27. Smoke detectors installed for elevator recall and control will also activate the
building and/or zone alarm signals.
28. During a full fire alarm, silencing the alarm panel shall not turn off the visual
alarm devices (strobes) in the building or at the exterior strobe for the Fire
Department connection.
29. All visible visual devices shall be synchronized. This may require older strobes
on multiple floors to be replaced.
6
Northwestern University General Requirements (Synopsis)
(include in design drawings as notes)
1. Hot work permits are managed through the NU Facilities Management Shops.
2. Risk Management shall inspect the open ceiling prior to the City inspection.
3. Existing rated walls adjacent to the construction zone shall be fire caulked.
4. Existing non rated walls adjacent to the construction zone shall be caulked to
prevent smoke migration.
5. Provide a fire extinguisher in all pantries and kitchens.
6. Microwaves shall not be placed in any exit paths.
7. Combination safety shower/eye washes shall comply with ANSI code Z358.1
8. When required at the level of discharge on an exit stair, stair barriers (gate) shall
be 42” high
9. Stairs and elevator cabs shall be numbered and labeled both inside and out.
10. Security cameras shall be placed at all exits and large occupancy areas.
Northwestern University Life Safety System Requirements (synopsis)
(include in design drawings as notes)
1. Sprinkler flow switches shall be set between a 30 and 45 second delay.
2. Contact the Electrical Shop for the approved list of fire alarm shop drawing
symbols.
3. Offices shall be assumed to have two occupants and require a visual device.
4. New construction shall be designed with voice capable devices for mass
notification direct from University Police. This requires a fiber optic cable
connection between the FA panel and data closet and include the programming
to interface with the NUPD system.
5. All audio visual devices shall be marked with “ALERT”.
6. Ceiling mounted strobes are preferred by the University.
7. Maximum speaker/horn output should not be above 80 decibels in office type
areas and 105 decibels in mechanical areas.
7
8. "T-tapping" of intelligent (addressable) fire alarm initiating circuits is not
permitted.
9. Any new fire alarm control panel, and its back box enclosure, shall accommodate
a minimum of 25 percent additional zones for hardwire and 25 percent additional
initiating points for addressable systems.
10. For non-code required Fire Command Centers, fire alarm control panels shall be
located in a secure location having a minimum one hour fire resistance rated
enclosure for any building. A two hour fire resistance rated enclosure is required
for major facilities having command centers or voice alert. Rooms shall have
clean conditioned air with a temperature range of 50 to 80 degrees F and without
wide fluctuations in humidity. Floor space and wall space shall provide room to
install and maintain all systems and equipment located within. At least three feet
of clear space shall be provided in front of all cabinets.
11. Any new fire alarm control panels will be connected by the University to the
campus wide central ADT supervisory system. New ADT installations require
both analog telephone and standard data connections directly adjacent to the
ADT panel.
12. Smoke detectors, manual pull stations and heat detectors may be combined on
the same addressable zone. Flow switches, valve tamper switches, and duct
smoke detectors shall each be on separate zones.
13. Each laboratory suite/room over 500 square feet shall be provided with at least
one audio/visual alerting device and one manual pull station at the exit.
14. A visual alerting device shall be installed in all public washrooms.
15. Electric powered magnetic door holders shall be supplied with24 volt dc from the
fire alarm system.
16. Wire nuts are not acceptable for joining wires. Either crimp connections or wire
terminal strips shall be used to join wires. Wire terminal strips shall be
permanently mounted inside junction boxes with wires neatly bundled and
arranged.
17. .Smoke detector(s) shall be installed in the room housing the main and auxiliary
fire alarm control panels, elevator machine room, telephone rooms, main
electrical switch gear room and computer rooms over 500 square feet in area.
18. .Fixed temperature 195 degree heat detectors will be installed in sheltered
outside electrical vaults and emergency generator rooms.
8
19. .Residential buildings will have hard wired single station smoke detectors in the
rooms with system connected photoelectric type smoke detectors in the
corridors.
20. . Rate-of-rise heat detectors shall be provided in Janitor's closets with sinks.
21. Conduit for the alarm system will be a minimum of ¾” and be pre-painted red for
concealed conditions. In exposed areas, the conduit shall be site painted to
match the back ground color with only the junction box covers being painted red.
22. Conduits shall use only compression type connectors and be sized for a
maximum 30% fill in new or renovation projects.
23. All wiring shall be color coded as to function as stated in the separate
Northwestern University Design Standards book. Color codes shall be
continuous from the fire alarm control panel to and through the last device.
Initiating loops on addressable systems are an exception to the requirements.
24. Provide a Minimum 14 AWG stranded wire for all addressable circuits.
25. Provide a Minimum 12 AWG stranded wire for all AV circuits.
26. The lighter color shall always be used to indicate the positive wire. Earth ground
wires shall always be identified by a green wire with a yellow stripe. These
grounds are to be supplied and wire per manufacturer's specifications.
27. .Tags on wiring shall be of a permanent means and shall be subject to University
approval. Stick-on wire tags are not acceptable as a means of permanent
marking.
28. .The address of each initiating device shall be recorded on the fixed, nonremovable base.
29. .The audio amplifiers shall be labeled as to each speaker zone and channel
being supplied.
30. All electrical equipment rooms shall have combination heat/smoke detector
devices installed in them.
31. Provide rate of rise heat detectors at any microwave locations.
32. When making general announcements, strobes shall flash throughout the
structure.
9
33. Flow switches shall be replaced and re-timed of all as a part of all fire alarm
replacement projects and whenever an individual FS zone is more than 50%
reconfigured.
34. Smoke detectors inside the construction zone boundary and any other adjacent
areas shall be changed temporarily to heat detectors for the duration of the
construction period.
35. Fire alarm shut down and testing procedures are to be included in the section 015000 and 01-1000 sections of the specifications.
36. In addition to regular exit signs, low level exit signs shall be considered for all
residential buildings.
Design and Shop Drawing Review Process
1. All projects will be reviewed with the Building Department and the Fire Prevention
Bureau at the schematic design stage.
2. Large projects will be reviewed by the University insurance carrier at the
Schematic, Design Development and Construction Document levels.
3. Temporary FA system layout for renovations during the construction period will
be designed or sketched by the existing FA manufacturer or general contractor. It
is best if this sketch can be included in the renovation design drawings for permit.
If it is not in the bid package, the sketch will be reviewed and approved by both
the NU Electrical Shop and Risk Management. Upon approval, the sketch will be
forwarded to EFD for approval. The temporary system will be tested by the
Electrical Shop and witnessed by Risk Management. Once the temporary system
layout which may include fire extinguishers, mast mounted pull stations,
audio/visual devices and heat detectors (may be similar to the air wired “safety
station” below) is tested the existing FA and FS systems can be taken out of
service. The temporary system must be active until the final FA and FS systems
have been tested and approved. The Electrical Shop will confirm the removal of
the temporary system with a copy to EFD.
4. FA and FS shop drawings will be reviewed by NU Electrical Shop and Risk
management prior to submission to EFD.
5. Submit FA and FS drawings to EFD. Allow 2 weeks for review.
6. Submit FA and FS drawings to the University insurance carrier for information.
10
Testing Requirements
(Review sections 01-1000 and 01-5000 of the specification)
Fire Alarm installation testing is comprised of three steps. The installing contractor
shall test all equipment and the entire operation of the system. The contractor
then shall certify to the Office of Risk Management and the Facilities
Management Chief Electrician that the system performs as designed and that it is
in full compliance with the permitted work and relevant codes. The Contractor
shall then make an appointment with the Office of Risk Management to test the
entire system with University electricians and Office of Risk Management
personnel. After completion, Risk Management will then advise the Fire Marshal
that the system is approved for Fire Department testing. The contractor shall then
make an appointment with the Fire Prevention Bureau (through the Evanston
“311 request system” or by calling 847-448-4311 outside of Evanston) for
acceptance testing. When the appointment is made the contractor shall notify
the electric shop and Risk Management of the date and time. The contractor
shall provide a minimum of 2 alarm personnel with radio communications and all
necessary equipment to provide complete testing of each alarm system device at
each test. In addition, the contractor shall provide 3 copies of a list of initiating
devices, with device nomenclature for each test.
Special noise limiting testing precautions must be taken in and around residential
spaces, CCM areas, classroom schedules and clinic schedules.
Fire Sprinkler
EVANSTON LIST OF POSSIBLE TESTS AND INSPECTIONS
Pressure -hydro tests
Loop tie -Ins
Roof shot
Sprinkler Coverage I head locations
Flows and tampers
Pre-action system
o Air I pressure
o Devices
o Trip
Dry Systems
o Air I pressure
o Devices
o Tri p (Less than 1 minute)
•
•
•
•
•
•
•
Fire and Smoke Dampers

Operational test
11
Fire Alarm
• Fire Alarm devices - manual pulls, strobes, horns, smokes, heats, etc.
o Strobes have to be synchronized
o Doors on magnetic hold opens work properly
o Devices report correctly to the FA panel and are labeled with correct room ID's
o Main panel talks to the ADT panel
o ADT panel talks to University police
Electrical
• Power drop
o Transfer switches
o Emergency lighting
o Exit lights
Communications
 Area of rescue
 EFD radio coverage
Oxygen Depletion Alarm

Test connection to ADT
Atriums
 Smoke Evacuation HVAC system
o Full functional test to see If the system does what Is designed to do
 Fire Alarm activation
 Devices - beam detectors, smoke detectors, dampers
 Pre-action system
 Hot smoke test
General
 Fire Shutter operation
 Fire extinguishers tags
 Final Room Signage
 Rated Doors latch and close
12
Safety Station
This is an example of a temporary fire alarm “Safety Station”. These stations will be
placed at a rate of not less than one for every 2,500 square feet of renovation area.
13
NU DDC Standards
Table of Contents
Point Naming Conventions .................................................................................................. 3
General Abbreviations ..................................................................................................... 4
Building Abbreviations ..................................................................................................... 7
Standard Units, Significant Digits, and Change of Value ........................................................14
Alarm Standards ...............................................................................................................15
Alarm Levels..................................................................................................................15
Alarm Class ...................................................................................................................16
Trending Standards ...........................................................................................................17
Graphic Standards .............................................................................................................19
Universal Graphic Standards ...........................................................................................21
NU Home Screen Graphic ...............................................................................................23
Individual Building Home Screen Graphic .........................................................................24
Floor Plan Graphic .........................................................................................................25
Plant Graphics ...............................................................................................................27
Converter Graphics ........................................................................................................27
AHU Graphics ................................................................................................................28
VAV Graphics ................................................................................................................30
NU DDC Standards
Page 2
Point Naming Conventions
Point names shall be the combination of several identifying elements that are represented by a
list of standard abbreviations. Within a point name, the following attributes shall be identified:




Chicago campus,Evanton campus, or off-campus building (denoted by “C”, “E”, “O”) ,
“F” for Fraternity, “S” for Sorority, “H” for Housing
Building (four letter abbreviation)
Equipment tag (if applicable)
Point identifier (setpoint, command, alarm, etc)
Attributes shall be separated by “_” and will go from the building name (four letter
abbreviation) down to point type (ending in _STP, _CMD, etc where applicable). Equipment tags
shall not contain “-“or “/”, and shall be double-digits (i.e. AHU-1 is AHU01 in point name).
The naming convention shall be slightly modified depending on if the point is for a piece of
equipment, virtual point, meter, etc
Examples:
CAMPUS_BUILDING_EQUIPMENTTAG_POINTIDENTIFIER_POINTTYPE
E_COOK_AHU01_DA_TMP_STPT
E_COOK_AHU01_VAV020100:XXX
VAV Box point names shall include AHU tag serving the VAV box (or EF tag for exhaust VAV
boxes)
FOR VAV’S THE FIRST TWO DIGITS AFTER “VAV” WILL REPRESENT THE FLR NUMBER,
FOLLOWED BY A FOUR DIGIT ROOM NUMBER. WHERE MORE THAN ONE VAV BOX SERVE A
SINGLE ROOM THE VAV TAG SHALL END IN “A”, “B”, “C”, ETC FOR EACH BOX. WHERE A VAV
BOX SERVES MULTIPLE ROOMS, THE ROOM NUMBER SHALL BE THE LOCATION OF THE
THERMOSTAT.
Will all equipment tags other than VAVs be two digit number (i.e. AHU01, CHLR02, etc)?
NU DDC Standards
Page 3
General Abbreviations
The below abbreviations shall be used for all naming, including:







Point names
Graphics
Wiring diagrams
Equipment labeling
Device labeling
Wire labeling
Design documents
DESCRIPTION
ABBREVIATION
AIRFLOW MEASURING STATION
AIR-HANDLING UNIT
ALARM (Virtual)
BOILER
BREAK TANK
BROWN WATER
CABINET UNIT HEATER (HOT WATER)
CHILLED WATER
CHILLED WATER RETURN
CHILLED WATER SUPPLY
CHILLER
CHW COOLING COIL
COLD DECK
COMMAND (Analog Output)
COMPRESSOR
COMPUTER ROOM AIR CONDITIONER
CONDENSATE PUMP
CONDENSER WATER
CONDENSER WATER PUMP
CONDENSER WATER RETURN
CONDENSER WATER SUPPLY
CONDENSING UNIT
CONTROL VALVE
COOLING
COOLING TOWER
CROSS CONNECT DAMPER
CROSS CONNECT VALVE
DEHUMIDIFICATION UNIT
DE-IONIZED WATER
DEW POINT
DIFFERENTIAL (e.g., PRESSURE)
AFMS
AHU
ALM
BLR
BRK_TANK
BRNW
CUH
CHW
CHWR
CHWS
CHLR
CC
CD
CMD
COMP
CRAC
CS_PMP
CW
CW_PMP
CWR
CWS
CU
VLV
CLG
CT
XC_DMPR
XC_VLV
DHU
DI
DEWP
DIFF
NU DDC Standards
Page 4
DISABLE (Binary Output)
DISCHARGE AIR (out of AHU to terminal
device)
DISCHARGE STATIC PRESSURE
DOMESTIC COLD WATER
DOMESTIC HOT WATER HEATER
DOMESTIC HOT WATER PUMP
DOMESTIC HOT WATER RETURN
DOMESTIC HOT WATER SUPPLY
DOMESTIC WATER BOOSTER PUMP
DUCT STATIC PRESSURE
DX COOLING COIL
ECONOMIZER MODE
ELECTRIC DUCT HEATER
ENABLE (Binary Output)
ENERGY-RECOVERY UNIT
ENTHALPY
EXHAUST AIR
EXHAUST AIR DAMPER
EXHAUST FAN (GENERAL)
FAN COIL UNIT
FAN POWERED BOX
FILTER
FINAL FILTER
FLOW (AIR)
FLOW (HYDRONIC)
FREQUENCY
FUME HOOD
FUME HOOD CONTROLLER
GEOTHERMAL
GRAY WATER
HAND-OFF-AUTO
HEAT EXCHANGER
HEAT PUMP
HEATING
HEATING COIL
HEAT-RECOVERY CHILLER
HEAT-RECOVERY EXHAUST FAN
HEPA FILTER
HIGH STATIC SWITCH
HOT DECK
HOT WATER
HOT WATER PUMP
HOT WATER RETURN
HOT WATER SUPPLY
HUMIDIFIER
ISOLATION EXHAUST FAN
NU DDC Standards
DIS
DA
DA_PRS
DCW
DHW_HX or DHW_HTR
DHW_PMP
DHWR
DHWS
DCW_PMP
DUCT_PRS
DX
ECON
EL_DH
ENA
ERU
ENTH
EA
EA_DMP
EF
FCU
FPB
FLTR
FNL_FLTR
CFM
GPM
FREQ
FH
FHC
GEO
GRYW
HOA
HX
HT_PMP
HTG
HC
HRC
HR_EF
HEPA_FLTR
HI_STAT_ALM
HD
HW
HW_PMP
HWR
HWS
HUM
ISO_EF
Page 5
ISOLATION
KITCHEN EXHAUST FAN
LAB EXHAUST FAN
LEVEL
LOW LIMIT / FREEZESTAT
LOW STATIC SWITCH
MAKE-UP AIR UNIT
METER
MINIMUM OA DAMPER
MIXED AIR
MIXED AIR PRESSURE
OCCUPIED
OUTSIDE AIR
OUTSIDE AIR DAMPER
OVERRIDE
PACKAGED TERMINAL AIR CONDITIONER
PERIMETER HOT WATER
POSITION
PRE-FILTER
PREHEAT COIL
PRESSURE
PRESSURE REDUCING VALVE
PRIMARY CHILLED WATER PUMP
PROCESS CHILLED WATER
PUMP
REHEAT COIL
REHEAT RETURN WATER
REHEAT SUPPLY WATER
RELATIVE HUMIDITY
RELIEF AIR DAMPER
RELIEF FAN
RETURN AIR
RETURN AIR DAMPER
RETURN AIR PRESSURE
RETURN FAN
REVERSE OSMOSIS WATER
ROOF-TOP UNIT
SECONDARY CHILLED WATER
SECONDARY CHILLED WATER PUMP
SECONDARY HOT WATER
SECONDARY HOT WATER PUMP
SETPOINT (Virtual point)
SMOKE DETECTOR
SNOW MELT
NU DDC Standards
ISO
KIT_EF
LAB_EF
LVL
FRZ
LOW_STAT_ALM
MAU
MTR
MIN_OA_DMP
MA
MA_PRS
OCC
OA
OA_DMP
OVRD
PTAC
PERIM_HW
POS
PRE_FLTR
PHC
PRS
PRV
CHW_PMP
PCHW
PMP
RHC
RHTWR
RHTWS
RH
RLF_DMP
RLF
RA
RA_DMP
RA_PRS
RF
RO
RTU
SCHW
SCHW_PMP
SHW
SHW_PMP
STPT – if more than one setpoint due to reset
schedule abbreviate with _low, _mid, _high,
i.e. DA_TMP_STPT_LOW,
DA_TMP_STPT_HIGH
SMK
SNOW_MELT
Page 6
STAGE
STATUS (Binary Input)
STEAM
SUPPLY AIR (out of terminal device to space)
SUPPLY FAN
SYSTEM STATIC PRESSURE
TANK
TEMPERATURE (DRY BULB)
THERMAL STORAGE
TOILET EXHAUST FAN
TOTAL DISSOLVED SOLIDS
TOTAL HARDNESS
ULTRA VIOLET FILTER
UNIT HEATER (HOT WATER)
UNIT VENTILATOR
UNOCCUPIED
VARIABLE AIR VOLUME BOX
VARIABLE FREQUENCY DRIVE
VIBRATION SENSOR
WATER SOURCE HEAT PUMP
WET BULB
WIND SPEED
ZONE DAMPER
ZONE PRESSURE
ZONE TEMPERATURE
STG
STS
STM
SA
SF
SYS_PRS
TNK (NUMBER IF APPLICABLE)
TMP
TS
TLT_EF
TDS
TH
UVLT_FLTR
UH
UV
UNOCC
VAV
VFD
VIB
WSHP
WB
WIND_SPD
ZN_DMPR (NOTE: FOR MULTI-ZONE ZN1DMPR, ZN2_DMPR, ETC)
ZN_PRS
ZN_TMP
Building Abbreviations
Building #
Building Description
Address
8830
Majorie Ward Marshall Dance
Center
Josephine Louis Theater
Ethel M. Barber Theater
Mary & Leigh Block Museum of
Art
Pick-Staiger Concert Hall
Regenstein Hall of Music
Boat House
Kresge Underground
Evanston Garage
Locy Hall
Crowe Hall
McCormick Tribune Center
10 Arts Circle Drive
Four Character
Abbreviation
DNCE
20 Arts Circle Drive
30 Arts Circle Drive
40 Arts Circle Drive
JLTH
BARB
BLOK
50 Arts Circle Drive
60 Arts Circle Drive
1823 Campus Drive
1840 Campus Drive
1847 Campus Drive
1850 Campus Drive
1860 Campus Drive
1870 Campus Drive
PICK
REGS
BOAT
UNDG
EVSG
LOCY
CROW
TRIB
8785
8732
8831
3105
8728
1806
8737
8784
8716
8714
8837
NU DDC Standards
Page 7
Building #
Building Description
Address
8785
8714
8731
8732
8739
8723
8782
8789
5784
8835
John J. Louis Hall
Kresge Centennial Hall
Annie May Swift Hall
Theatre and Interpretation Center
University Library
Norris University Center
Central Utility Plant
Walter Annenberg Hall
James L. Allen Center
Center for Nanofabrication and
Molecular Self-Assembly, Ryan
Hall
Arthur & Gladys Pancoe –
Evanston Northwestern
Healthcare Life Sciences Pavilion
William A. & Gayle Cook Hall
Frances Searle Building
Henry Crown Sports Pavilion,
Dellora A. & Lester J. Norris
Aquatics Center, Combe Tennis
Center
Ayers College of Commerce &
Industry
Slivka Hall
Kemper Hall
Chi Phi
562 Lincoln
Pi Kappa Alpha
Theta Chi
Zeta Beta Tau
584 Lincoln
Fisk Hall
East Fairchild
West Fairchild
Harris Hall
University Hall
Charles Deering Library
Arthur Andersen/Donald Jacobs
Center: Leverone Hall
Cresap Hall Laboratory
Swift Hall
Shanley Pavilion
Lunt Hall
Garrett – Evangelical Theological
Seminary
1877
1880
1920
1949
1970
1999
2026
2120
2169
2190
8836
8786
8707
1816
8607
8655
8650
2244
8597
2255
2261
2265
2254
8711
8578
8579
8712
8738
8709
8719
8708
8734
8730
8717
8715
NU DDC Standards
Campus
Campus
Campus
Campus
Campus
Campus
Campus
Campus
Campus
Campus
Drive
Drive
Drive
Drive
Drive
Drive
Drive
Drive
Drive
Drive
Four Character
Abbreviation
LUIS
KRSG
AMSW
THTR
ULIB
NORR
ECUP
ANNB
ALLN
RYNH
2200 Campus Drive
PANC
2220 Campus Drive
2240 Campus Drive
2311 Campus Drive
COOK
FSRL
SPAC
2324 Campus Drive
AYER
2332 Campus Drive
2420 Campus Drive
550 Lincoln
562 Lincoln
566 Lincoln
572 Lincoln
576 Lincoln
584 Lincoln
1845 Sheridan
1855 Sheridan
1861 Sheridan
1881 Sheridan
1897 Sheridan
1937 Sheridan
2001 Sheridan
SLVK
KMPR
2244 (BLDG
8597 (BLDG
2255 (BLDG
2261 (BLDG
2265 (BLDG
2254 (BLDG
FISK
EFCH
WFCH
HARR
UHAL
DEER
JACB
2021
2029
2031
2033
2121
CRES
SWFT
SHLY
LUNT
GART
Sheridan
Sheridan
Sheridan
Sheridan
Sheridan
#)
#)
#)
#)
#)
#)
Page 8
Building #
Building Description
Address
8847
Ford Motor Company Engineering
Design Center
Technological Institute – A Wing
Technological Institute – B Wing
Technological Institute – C Wing
Technological Institute – D Wing
Technological Institute – E Wing
Technological Institute – F Wing
Technological Institute – G Wing
Technological Institute – H Wing
Technological Institute – K Wing
Technological Institute – L Wing
Technological Institute – M Wing
Technological Institute – N Wing
Technological Institute – BC Wing
Technological Institute – AB Wing
Technological Institute – FG Wing
Sargent Hall
Phi Kappa Psi
Sigma Chi
Kappa Sigma
Foster House
2303 Sheridan
Bobb Hall
Delta Upsilon
Lindgren House
Chi Psi
McCulloch Hall
Delta Tau Delta
Goodrich
2325 Sheridan
Phi Gamma Delta
Sigma Nu
Lamda Chi Alpha
Sigma Phi Epsilon
Phi Delta Theta
Beta Theta Pi
Patten Gymnasium
Dearborn Observatory
Center for Catalysis & Surface
Science
O.T. Hogan Biological Sciences
Building
Seeley G. Mudd Library
Anderson Hall
2133 Sheridan
Four Character
Abbreviation
FORD
2145
2145
2145
2145
2145
2145
2145
2145
2145
2145
2145
2145
2145
2145
2145
2245
2247
2249
2251
2253
2303
2305
2307
2309
2313
2315
2317
2321
2325
2331
2335
2339
2341
2347
2349
2407
2131
2137
TIAW
TIBW
TICW
TIDW
TIEW
TIFW
TIGW
TIHW
TIKW
TILW
TIMW
TINW
TIBC
TIAB
TIFG
SARG
2253 (BLDG
2258 (BLDG
2249 (BLDG
8573 (BLDG
8593 (BLDG
BOBB
2247 (BLDG
LNGR
2245 (BLDG
MCLH
2246 (BLDG
GOOD
2241 (BLDG
2252 (BLDG
2259 (BLDG
2250 (BLDG
2239 (BLDG
8608 (BLDG
2243 (BLDG
PATT
DBRN
CATL
8735
8735
8735
8735
8735
8735
8735
8735
8735
8735
8735
8735
8735
8735
8735
8585
2253
2258
2249
8573
8593
8569
2247
8580
2245
8581
2246
8575
2241
2252
2259
2250
2239
8608
2243
1812
8724
8845
8713
8720
1808
NU DDC Standards
Sheridan
Sheridan
Sheridan
Sheridan
Sheridan
Sheridan
Sheridan
Sheridan
Sheridan
Sheridan
Sheridan
Sheridan
Sheridan
Sheridan
Sheridan
Sheridan
Sheridan
Sheridan
Sheridan
Sheridan
Sheridan
Sheridan
Sheridan
Sheridan
Sheridan
Sheridan
Sheridan
Sheridan
Sheridan
Sheridan
Sheridan
Sheridan
Sheridan
Sheridan
Sheridan
Sheridan
Tech Drive
Tech Drive
2205 Tech Drive
HOGN
2233 Tech Drive
2701 Ashland
MUDD
ANDS
#)
#)
#)
#)
#)
#)
#)
#)
#)
#)
#)
#)
#)
#)
#)
Page 9
Building #
Building Description
Address
1811
1817
1809
McGaw Memorial Hall
Tennis Bubble
Byron S. Coon Sports
Center/Nicolet Football
639 Central
1808 Chicago
1809 Chicago
1810/1812 Chicago
1815 Chicago
Allison Hall
1838 Chicago
Traffic Institute
1007 Church
515 Clark
555 Clark
619 Clark
624 Clark
Rebecca Crown Center
618 Colfax
Delta Chi
624 Colfax
625 Colfax
628 Colfax
629 Colfax
617 Dartmouth
627 Dartmouth
630 Dartmouth
Music Administration Building
Cahn Auditorium
Delta Gamma
619 Emerson
626 Emerson
Hobart House
Health Service
Pi Beta Phi
Gamma Phi Beta
North Mid-Quads
710 Emerson
720 Emerson
Chambers Hall
Blomquist Recreation Center
605-615 Garrett
621-623 Garrett
618 Garrett
2705 Ashland
2707 Ashland
2707 Ashland
Four Character
Abbreviation
MGAW
TRIE
COON
639 Central
1808 Chicago
1809 Chicago
1810/1812 Chicago
1815 Chicago
1820 Chicago
1838 Chicago
405 Church
1007 Church
515 Clark
555 Clark
619 Clark
624 Clark
633 Clark
618 Colfax
619 Colfax
624 Colfax
625 Colfax
628 Colfax
629 Colfax
617 Dartmouth
627 Dartmouth
630 Dartmouth
711 Elgin Road
600 Emerson
618 Emerson
619 Emerson
626 Emerson
630 Emerson
633 Emerson
636 Emerson
640 Emerson
650 Emerson
710 Emerson
720 Emerson
600 Foster
617 Foster
605-615 Garrett
621-623 Garrett
618 Garrett
8743 (BLDG #)
8744 (BLDG #)
8745 (BLDG #)
8746 (BLDG #)
8747 (BLDG #)
ALLI
8588 (BLDG #)
8427 (BLDG #)
R123 (BLDG #)
8748 (BLDG #)
8832 (BLDG #)
8704 (BLDG #)
8803 (BLDG #)
CRWN
8804 (BLDG #)
2283 (BLDG #)
8805 (BLDG #)
8749 (BLDG #)
8802 (BLDG #)
8750 (BLDG #)
8806 (BLDG #)
8751 (BLDG #)
8752 (BLDG #)
MADM
CAHN
2273 (BLDG #)
8753 (BLDG #)
8568 (BLDG #)
HBRT
HLTH
2279 (BLDG #)
2275 (BLDG #)
NMQD
8595 (BLDG #)
8594 (BLDG #)
CHAM
BLOM
8872 (BLDG #)
8873 (BLDG #)
8788 (BLDG #)
8743
8744
8745
8746
8747
8567
8588
8427
R123
8748
8832
8704
8803
8727
8804
2283
8805
8749
8802
8750
8806
8751
8752
8721
8729A
2273
8753
8568
8577
8733
2279
2275
8583
8595
8594
8825
1807
8872
8873
8788
NU DDC Standards
Page 10
Building #
Building Description
Address
8826
8560
8754
8755
8838
8756
8757
8839
8758
8840
8589
8814
8760
8821
8808
8761
8762
8590
8599
2256
8566
8920
8502
8598
8809
8763
8810
8764
8765
R124
8601
8610
2270
2278
8819
8574
8815
8823
8844
8817
8767
8592
8706
Charles Dawes House
600 Haven
617 Haven
625 Haven
1801 Hinman
1810 Hinman
1812 Hinman
1813 Hinman
1818 Hinman
1819 Hinman
1835 Hinman
1620 Judson
617 Library
Family Institute
619 Library
620 Library
626 Library
600 Lincoln
610 Lincoln
Career Services
630 Lincoln
1801 Maple
1890 Maple
Engelhart Hall
616 Noyes
617 Noyes
624 Noyes
625 Noyes
629 Noyes
1603 Orrington
McManus Living-Learning Center
1856 Orrington
Chi Omega
Kappa Kappa Gamma
1900 Orrington
Foster-Walker Complex
1941 Orrington
1948 Ridge
2020 Ridge
1616 Sheridan
John Evans Alumni Center
1820 Sheridan
Alice S. Millar Chapel and
Religions Center
225 Greenwood
600 Haven
617 Haven
625 Haven
1801 Hinman
1810 Hinman
1812 Hinman
1813 Hinman
1818 Hinman
1819 Hinman
1835 Hinman
1620 Judson
617 Library
618 Library
619 Library
620 Library
626 Library
600 Lincoln
610 Lincoln
620 Lincoln
630 Lincoln
1801 Maple
1890 Maple
1915 Maple
616 Noyes
617 Noyes
624 Noyes
625 Noyes
629 Noyes
1603 Orrington
1725 Orrington
1856 Orrington
1870 Orrington
1871 Orrington
1900 Orrington
1927 Orrington
1941 Orrington
1948 Ridge
2020 Ridge
1616 Sheridan
1800 Sheridan
1820 Sheridan
1870 Sheridan
NU DDC Standards
Four Character
Abbreviation
CDAW
8560 (BLDG #)
8754 (BLDG #)
8755 (BLDG #)
8838 (BLDG #)
8756 (BLDG #)
8757 (BLDG #)
8839 (BLDG #)
8758 (BLDG #)
8840 (BLDG #)
8589 (BLDG #)
8814 (BLDG #)
8760 (BLDG #)
FMLY
8808 (BLDG #)
8761 (BLDG #)
8762 (BLDG #)
8590 (BLDG #)
8599 (BLDG #)
2256 (BLDG #)
8566 (BLDG #)
1801
8502 (BLDG #)
ENGH
8809 (BLDG #)
8763 (BLDG #)
8810 (BLDG #)
8764 (BLDG #)
8765 (BLDG #)
R124 (BLDG #)
MCMN
8610 (BLDG #)
2270 (BLDG #)
2278 (BLDG #)
8819 (BLDG #)
FSWK
8815 (BLDG #)
8823 (BLDG #)
2020
8817 (BLDG #)
8767 (BLDG #)
8592 (BLDG #)
MLLR
Page 11
Building #
Building Description
Address
8768
8822
8769
8770
8771
8772
8773
8774
8775
8776
8777
8778
8779
8865
1902
1908
1914
1918
1922
1936
1940
2000
2006
2010
2016
2040
2046
2122
8572
8766
8722
8587
8854
8729
1902 Sheridan
1908 Sheridan
1914 Sheridan
1918 Sheridan
1922 Sheridan
1936 Sheridan
1940 Sheridan
2000 Sheridan
2006 Sheridan
2010 Sheridan
2016 Sheridan
2040 Sheridan
2046 Sheridan
Seabury-Western Theological
Seminary
Elder Hall
2870 Sheridan Place
Music Practice Building
Willard Hall
1800 Sherman
Scott Hall
2276
Kappa Alpha Theta
2272
Delta Delta Delta
8586
Shepard Residential College
2266
Alpha Chi Omega
8584
Rogers House
8582
South Mid-Quads
8718
Lutkin Hall
2269
Alpha Phi
2277
Kappa Delta
2274
Delta Zeta
8725
Human Resources
2248
Evans Scholars
NU DDC Standards
Sheridan
Sheridan
Sheridan
Sheridan
Sheridan
Sheridan
Sheridan
Sheridan
Sheridan
Sheridan
Sheridan
Sheridan
Sheridan
Sheridan
2400 Sheridan
2870 Sheridan
1823 Sherman
1865 Sherman
1800 Sherman
601 University
Place
619 University
Place
625 University
Place
626 University
Place
637 University
Place
647 University
Place
655 University
Place
700 University
Place
701 University
Place
711 University
Place
717 University
Place
720 University
Place
721 University
Four Character
Abbreviation
8768 (BLDG #)
8822 (BLDG #)
8769 (BLDG #)
8770 (BLDG #)
8771 (BLDG #)
8772 (BLDG #)
8773 (BLDG #)
8774 (BLDG #)
8775 (BLDG #)
8776 (BLDG #)
8777 (BLDG #)
8778 (BLDG #)
8779 (BLDG #)
SEAB
ELDR
8766 (BLDG #)
MUPR
WILL
1800
SCOT
2276 (BLDG #)
2272 (BLDG #)
SHEP
2266 (BLDG #)
ROGR
SMQD
LTKN
2269 (BLDG #)
2277 (BLDG #)
2274 (BLDG #)
HRCS
EVAN
Page 12
Building #
Building Description
8570
Chapin Hall
8780
906 University Place
8780
910 University Place
8780
920 University Place
Visitors Center
Kellogg Building
Bienen School of Music
P102
P100
P101
8816
8798
8796
8797
8795
8794
8793
8792
8791
8602
0511
8846
8799
Address
Place
726 University
Place
906 University
Place
910 University
Place
920 University
Place
TBD
TBD
TBD
Chicago Campus
Chestnut Parking Garage, E-Lot
275 E Chestnut
Huron Parking Lot, C-Lot
222 E Huron
Erie Parking Lot, D-Lot
321 E Erie
Rubloff
375 E Chicago
Gary Law Library
357 E Chicago
Levy Mayer
357 E Chicago
McCormick Hall
350 E Superior
Wieboldt
340 E Superior
Searle
320 E Superior
Morton
310 E Superior
Ward
303 E Chicago
Tarry
300 E Superior
Abbott
710 N Lake Shore
Heating Plant
410 E Huron
Lurie
303 E Superior
Olson
240 E Huron
NU DDC Standards
Four Character
Abbreviation
CHAP
8780 (BLDG #)
8780 (BLDG #)
8780 (BLDG #)
VCTR
KELG
BIEN
ELOT
CLOT
DLOT
RUBL
GARY
LVMY
MCMK
WBLT
SRLE
MORT
WARD
TARY
ABBT
CCUP
LURE
OLSN
Page 13
Standard Units, Significant Digits, and Change of Value
The below units, significant digits, and change of value standards shall be used for displaying
values in graphics. For example, a static pressure reading displayed on the graphic shall change
whenever the sensor reading changes by a value of 0.1, but it shall display two decimal
significant digits (i.e. 0.01 significant digits). If a sensor is reading 1.642” w.c., the display shall
show 1.64” w.c., and the value on the screen shall not change until the reading changes by
0.1”w.c. (i.e. when the sensor reading changes to a value that can be rounded to 1.54” w.c. or
1.74” w.c.).
Description
Air Flow
Air Static Pressure or
Differential Pressure
Air Velocity
Building Pressure
CO2 Level
Damper Command and
Position
Damper Command and
Position (F/B damper)
Differential Pressure (water
systems)
Electric Consumption
Electric Current
Electric Demand
Electric Potential
Energy
Filter Status
Frequency
Gas Consumption
Percent Output
Relative Humidity
Runtime
Speed (motor)
Speed (fan or pump)
Status (pump, fan, etc)
Temperature – Critical Spaces
Temperature – Non-Critical
Spaces
Valve (modulating) Command
& Position
Valve (2-pos) Command &
Position
Water Flow
Water Quality
NU DDC Standards
Units
CFM
in/w.c.
Significant Digits
1
0.01
Change of Value
1% of Max
0.01
FPM
in/w.c.
PPM
% Open
1
0.001
5
1
1% of Max
0.005
10
1
% Face
1
1
Psig
0.1
0.1
kWh
Amps
kW
V
BTU
Clean/Dirty
Hz
Therms
% Full
%RH
Hours
RPM
%
On/Off
°F
°F
1
0.1
1
1
1
0.1
1
0.1
1
1
1
1
0.1
0.1
1%
1%
1%
1%
1%
1
1%
1
1
1
1
1
0.1
0.5
% Open
1
1
Open/Closed
-
-
GPM
pH
1
0.01
1% of Max
0.1
of
of
of
of
of
Max
Max
Max
Max
Max
of Max
Page 14
Alarm Standards
Alarm Levels
Type
Freezestat
Fan Status does
not match
command
Hi Static Pressure
Smoke Detector
Discharge
temperature (5°F
deviation from
setpoint)
Duct static
pressure (0.5” wc
deviation from
setpoint)
Supply HW temp
(10°F deviation
from setpoint)
Delay (into
alarm)
Alarm Class
Air-Handling Units
None (immediate) None (immediate)
5 min.
None (immediate)
Emergency
Critical
None (immediate)
None (immediate)
5 min.
None (immediate)
None (immediate)
2 min.
Critical
Emergency
Non-critical
5 min.
2 min.
Non-critical
5 min
Pump Status does
not match
command
Diff. water
pressure (5 psig
deviation from
setpoint)
Chiller status does
not match
command
Chiller Alarm
Refrigerant alarm
CHWS Temp (5°F
deviation from
setpoint when
chiller enabled)
5 min.
Boiler status does
not match
command
Boiler Alarm
5 min.
NU DDC Standards
Delay (out of alarm)
Converters
5 min.
Chiller System
None (immediate)
Non-critical
Non-critical
5 min.
5 min.
Non-critical
5 min.
None (immediate)
Non-critical
None (immediate)
None (immediate)
30 min.
None (immediate)
None (immediate)
15 min.
Critical
Emergency
Non-critical
Boiler System
None (immediate)
Non-critical
None (immediate)
None (immediate)
Critical
Page 15
Type
Secondary HW
loop temp (10°F
deviation from
setpoint when
boilers enabled)
Low Steam
Pressure Alarm (5
psig below
setpoint)
Space pressure
Exhaust fan status
does not match
command
Space
Temperature (4°F
deviation from
setpoint)
Critical Space
Temperature (1°F
deviation from
setpoint)
VFD in hand mode
or bypass
Delay (into
alarm)
30 min.
Delay (out of alarm)
Alarm Class
15 min.
Non-critical
1 min.
1 min.
Emergency
1 min.
5 min.
Labs
1 min.
None (immediate)
Critical
Critical
Space Temperature
30 min. (tied to
10 min.
occupied mode,
not optimal start)
30 min. (tied to
occupied mode,
not optimal start)
None (immediate)
Alert
5 min.
Critical
VFDs
None (immediate)
Critical
Alarm message shall include timestamp, type of alarm, full point name, and value of point
(including units) causing alarm.
Alarm Class
Link users to alarm type acknowledgement
Alarm Class (in order of least to
most critical)
Alert
Non-critical
Critical*
Emergency*
Nuclear*
Notified User Group
Alarm Routing
DDC Technician
Logfile on server
DDC Technician
Console
DDC Technician, DDC Foreman E-mail, Pager, and Console
DDC Technician, DDC Foreman E-mail, Pager, and Console
DDC Technician, DDC Foreman, E-mail, Pager, and Console
Facilities Director
*Critical, Emergency, and Nuclear alarms shall pop-up on any screen the user is logged into
COORDINATE ALARM ROUTING W/OWNER TO DETERMINE PERSONNEL ASSIGNMENTS TO
DIFFERENT USER GROUPS. ROUTE PER CAMPUS, ENGINEERING GROUP, AND MANAGEMENT.
NU DDC Standards
Page 16
Trending Standards
All trends shall be instantaneous trends, not averaging
Description
Discharge Air Temperature
Mixed Air Temperature
Return Air Temperature
Exhaust Air Temperature
Return Air Humidity
Discharge Air Humidity
Damper Commands
Duct Static
Fan Speed
Valve Position Command
Valve Position Feedback (if available)
Coil Entering/Leaving Water Temperature
Occupied/Unoccupied Mode
Fan Status
Heating Coil Pump Status
Description
Zone Temperature
Airflow
Airflow Setpoint
Damper Position
Perimeter Valve Position
Reheat Valve Position
Leaving Air Temperature
Occupied/Unoccupied Mode
AHU Trends
Trend Interval
10 min., Boolean points shall be COV
COV
VAV Trends
Trend Interval
30 min., Boolean points shall be COV
COV
Steam/Hot Water Converter Trends
Description
Trend Interval
Hot Water Entering Temperature
Hot Water Leaving Temperature
Hot Water Temperature Setpoint
Water Differential Pressure
10 min., Boolean points shall be COV
Steam Valve Command
Steam Valve Position (feedback, if available)
Pump Speed
Pump Enable/Unable Command
COV
Pump Status
NU DDC Standards
Page 17
Description
Chiller CHWS Temperature
Chiller CHWR Temperature
CHWS Setpoint
Chiller CWS Temperature
Chiller CWR Temperature
CW Setpoint
System CHWS Temperature
System CHWR Temperature
Secondary CHWS Temperature
Secondary CHWR Temperature
Chiller CHW Flow (GPM)
Chiller CW Flow (GPM)
System CHW Flow (GPM)
System CW Flow (GPM)
Tower Fan Speed
3-way Bypass Valve Position
Indoor Sump Temperature
Chiller %RLA
Tower Fan Status
Chiller Status
System Differential Pressure
CHW Pump Status
CW Pump Status
Description
Boiler HWS Temperature
Boiler HWR Temperature
System HWS Temperature
System HWR Temperature
HWS Temperature Setpoint
Boiler % Fire or High/Low Fire (where
applicable)
System HWS Flow (GPM)
3-way Mixing Valve Position
HW Pump Speed
System Differential Pressure
NU DDC Standards
Chiller Trends
Trend Interval
10 min., Boolean points shall be COV
COV
Boiler Trends
Trend Interval
10 min., Boolean points shall be COV
COV
Page 18
Graphic Standards
The graphic hierarchy will be as follows:
 NU Home Screen (Opening screen with picture of NU Campus and links to Evanston,
Chicago, and Off-Campus)
o Evanston Campus (points beginning with “E”, “F”, “S”, and “H”)
 List of buildings by type (Science, Academic, Athletic, Housing, Fraternity,
Sorority, Utilities)
 Individual Building Home Screen (Dashboard for: instantaneous
meter data, alarm statuses, outside air temp/humidity/enthalpy)
o Floor Plan Graphic
 Detailed Floor Plan Graphic
 Dynamic space temperature
 Occupancy Status (where applicable)
 Link to VAV graphic
o Equipment Graphics (boilers, chillers, converters, AHUs,
etc.)
o Detailed Meter Graphic
o AHU status table (valve positions, discharge temps,
damper positions, fan speeds, etc.)
o VAV status table(s) (valve position, damper position,
airflow, discharge air temp)
o “Other” Graphics
 Misc. equipment
 Utilities
o Evanston CUP Home Screen (status only)
o System Meters Screen
o One-line diagrams (CHW, Steam, Condensate, etc)
o Chicago Campus (points beginning with “C”)
 List of buildings by type (FSM, Law, Academic, Utilities)
 Individual Building Home Screen (Dashboard for: instantaneous
meter data, alarm statuses, outside air temp/humidity/enthalpy)
o Floor Plan Graphic
 Detailed Floor Plan Graphic
 Dynamic space temperature
 Occupancy Status (where applicable)
 Link to VAV graphic
o Equipment Graphics (boilers, chillers, converters, AHUs,
etc.)
o Detailed Meter Graphic
o AHU status table (valve positions, discharge temps,
damper positions, fan speeds, etc.)
o VAV status table(s) (valve position, damper position,
airflow, discharge air temp)
o “Other” Graphics
 Misc. equipment
NU DDC Standards
Page 19

o
Utilities
o Chicago CUP Home Screen (status only)
o System Meters Screen
o One-line diagrams (CHW, Steam, Condensate, etc)
Off-Campus (points beginning with “O”)
 List of buildings
 Individual Building Home Screen (Dashboard for: instantaneous
meter data, alarm statuses, outside air temp/humidity/enthalpy)
o Floor Plan Graphic
 Detailed Floor Plan Graphic
 Dynamic space temperature
 Occupancy Status (where applicable)
 Link to VAV graphic
o Equipment Graphics (boilers, chillers, converters, AHUs,
etc.)
o Detailed Meter Graphic
o AHU status table (valve positions, discharge temps,
damper positions, fan speeds, etc.)
o VAV status table(s) (valve position, damper position,
airflow, discharge air temp)
o “Other” Graphics
 Misc. equipment
NU DDC Standards
Page 20
Universal Graphic Standards
Formatting








The default font for words in graphics shall be Tahoma. The minimum font size shall be
12 pt.
Graphic background color shall not be white/shall be lighter color to contrast graphics
(coordinate with Owner)
Commandable points shall have a background color (rather than transparent); noncommandable points shall be transparent
Any points in override mode shall appear in different color on the graphic (coordinate
with Owner)
At campus-level screens, display status of campus-wide emergency fan shut-down,
chiller plant load shedding program, power loss (via “pop-up” alarm status)
Piping shall be color-coded
o HWS: bright red
o HWR: darker red
o CHWS: bright blue
o CHWR: darker blue
o Steam: white
o Condensate: orange
o CWS: bright green
o CWR: darker green
Graphics shall be designed for screen resolution of 1280x800 (most commonly issued
laptop in FM). Useable graphic area will be smaller due to the space needed for the
graphic header, upper window bar, and left navigation tree. See below for
recommended maximum pixels for graphic header, upper window bar, tabs, and left
navigation tree:
Future graphics: graphic for tablets shall be designed using HTML, not Java
NU DDC Standards
Page 21
Appearance/Layout













Setpoint the operator can change should appear as a button (defined by user access)
Main header – top of screen (banner)
o NU logo
o OA conditions (temp, %RH, enthalpy)
o Building Name/Equipment tag/Plant description/Service/Location (where
applicable) – located center of banner
o Standard Drop-down menu to links
 Link to NU BAS home screen
 Link to NU Campus home screens
 Link to NU Building abbreviations
 Link to NU Std. Point Names
o Secondary Drop-down menu (personalized to user)
All setpoints shall be located in upper right corner
All alarm points shall be shown on graphic next to associated device (freeze, hi-static,
smoke detector)
Units shall be shown next to all values suing the Standard Units outlined earlier in this
document
All points being trended (per Trend Standards) shall have small graphical image of a line
chart next to point value that is a button linking the user to 24-hr trends for that point.
Descriptions for points will be typed into background, similar to JCI graphic
All equipment graphics (including terminal equipment) shall include a link to:
o Sequence of Operation in .pdf format
o Equipment O&M manuals in .pdf format
o Wiring diagram and parts list in .pdf format
Piping graphics shall be 2D, not isometric
NO VENDOR LOGOS
User shall have ability to leave text notes on graphic
Graphic shall display correct type of equipment (centrifugal chiller vs screw chiller,
counter-flow vs. cross-flow cooling tower, inline vs. base-mounted pump, etc)
Equipment with VFDs shall have VFD button on graphic that links user to VFD table
showing information available from VFD via BACNET. The VFD table shall include the
following parameters:
o
o
o
o
o
o
o
o
o
o
o
o
Speed Input (%)
Output Speed (RPM)
Output Frequency (Hz)
DC Bus Voltage (V)
Output Voltage (V)
Current (A)
Fault Status
Drive Ready Status
Run Enable Status
Drive Run Status
Drive Mode
Runtime (hr)
NU DDC Standards
Page 22
NU Home Screen Graphic
Figure 1: Example Home Screen Graphic
The NU home screen graphic will be similar to the existing Siemen’s NU home screen graphic
shown above. The NU home screen graphic will include links to Evanston, Chicago, and Offcampus graphics that each have a list of the buildings associated with that campus.
1. The Evanston home screen graphic shall have alphabetical lists of buildings by the
following building types: Science, Academic, Athletic, Housing, Fraternity, Sorority,
Utilities
2. The Chicago home screen graphic shall have alphabetical lists of buildings by the
following building types: FSM, Law School, Academic, Utilities
3. The Off-campus building home screen shall have a single alphabetical list of all offcampus buildings
NU DDC Standards
Page 23
Individual Building Home Screen Graphic
Figure 2: Example Individual Building Home Screen Graphic
Individual building’s home screen graphics will be similar to Norris’s existing home screen graphic. Per
the graphic hierarchy, there shall be links to:






Each Floor Plan Graphic (not shown on Norris example above)
Equipment Graphics
AHU Status Table Graphic (not shown on Norris example above)
VAV Status Table Grpahic (not shown on Norris example above)
Detailed Meter Graphics
“Other” Graphics (where applicable)
The building home screen graphic shall include a dashboard showing current utility meter
readings for that building, along with current outside air temperature/humidity conditions. The
graphic shall include a picture of the building, and display the address of the building.
NU DDC Standards
Page 24
Floor Plan Graphic





Overall floor plan shall be color-coded/hatched by AHU zones (see Figure 3 below).
There shall be a legend with a list of the AHU tags and associated color.
If user clicks on the AHU tag (in the legend), it shall route them to that AHU graphic. If
user clicks on AHU region in floor plan it shall take them to detailed floor plan (see
Figure 4 on pg. 26) of that AHU service area.
If area served by an AHU is large and must be split up into several detailed floor plan
graphics, then all zones served shall remain one color, but there shall be a boundary
(showing the detailed floor plan graphic boundary) that highlights when the user places
their mouse in the zones that link to a given detailed floor plan graphic.
Link to as-built floor plan of ductwork/piping
Figure 3: Floor Plan Graphic Example
The above floor plan graphic example shows AHU service zones color-coded by AHU (existing
Tech Building graphic). Per this standard, the above graphic will also have a legend showing
AHU tag and associated color. If the user clicks on the AHU tag in the legend it shall route them
to the AHU graphic. If the user clicks on the AHU service zone in the hatching it shall take them
to a detailed floor plan graphic displaying VAV service zones, room temp/humidity.
NU DDC Standards
Page 25
Figure 4: Detailed Floor Plan Graphic Example
The above detailed floor plan graphic example shows VAV service zones color-coded by VAV box. The
detailed floor plan graphic shall display:




Space temperature
Relative humidity (where applicable)
Occupancy status
Space Pressure sensor probe location (where applicable)
If space temp, relative humidity (where applicable), or space pressure (where applicable), is out of
range, the background color of the point value box shall turn red.
If the user clicks on the VAV service zone it shall route them to the VAV graphic.
NU DDC Standards
Page 26
Plant Graphics




Animation on cooling tower fans, pumps, (based on status, not output)
One graphic showing combination of all chillers (per existing Chicago)
Design for large screen (per existing Chicago)
Condenser water and chilled water-side shown on separate graphics with link on graphic
to navigate between the two
Converter Graphics




Flow arrows shall be included on piping
Isolation valves shall not be shown; control valves only
Graphic shall display correct type of converter (i.e. shell & tube)
Graphic shall display correct type of pump (in-line, base-mounted)
NU DDC Standards
Page 27
AHU Graphics











Setpoints in upper right corner (main virtual points, occupied mode, reset schedules).
Clicking on occupied mode or reset schedules shall take user to additional graphic
showing AHU occupancy schedule or reset schedule.
Graphic shall include override buttons for related to terminal equipment served by the
AHU that allows user to:
o Override all terminal equipment heating valves fully open
o Override all VAV dampers fully open
o Override all VAV dampers to max scheduled airflow
o Override all VAV dampers to min scheduled airflow
o Override all VAV dampers closed
Animation on fans (based on status, not output), not on dampers
For systems that are interconnected (energy recovery, EFs, DOAS, etc), but do not all fit
on one graphic, include link on graphic to interconnected system’s graphic
Supply and return airflow shall always be shown from right-edge of graphic (include
label)
Exhaust and outside airflow shall always be shown from left-edge of graphic (include
label)
Transfer button shown for terminal device graphics
Transfer button for related plant equipment (local chiller, boiler, pumps, converters, etc)
Graphic shall display both command and feedback points
Use standard units and point names described in sections above
Each facility shall have a link to an AHU status table. The table shall contain (at
minimum) the following columns (given in order from left to right):
o
o
o
o
o
o
o
o
o
AHU tag (clicking on this shall link to AHU graphic)
Area Served (i.e. Bio Labs, Chem Classrooms, etc)
Supply/Return/Relief Fan Status – all systems
Supply/Return/Relief Fan Speed – variable volume systems only
Mixed Air Temperature
Damper Position (applicable all dampers at AHU)
Valve position (applicable all HW/CHW/Steam valves)
Discharge Air Temp
Duct Static Pressure
If AHU has multiple supply fans (i.e. fan row) then the AHU row shall be taller and the
cell for the supply fan status shall be split into several rows so that all fan status and
speeds can be displayed clearly.
NU DDC Standards
Page 28

VAV AHU graphics shall have a link to a VAV status table. This table shall display all VAV
boxes served from the AHU with the following columns (in order from left to right)
o VAV tag (clicking on this shall link to VAV box graphic)
o Room(s) served
o Zone temperature setpoint
o Zone temperature
o Discharge air temperature
o Reheat valve position
o Damper position
o Airflow setpoint
o Airflow
Final row of VAV status table shall show minimum and maximum discharge air
temperature, minimum and maximum reheat valve position, minimum and maximum
damper position, and total airflow. If a system is large enough to require multiple VAV
status tables, this final row shall be shown at the bottom of each table
NU DDC Standards
Page 29
VAV Graphics




Setpoints in upper right corner (main virtual points). Shall include min. heat, min. cool,
max heat, max cool CFM, space temperature setpoint (where applicable)
Room name and number shall be included in the VAV object name. Coordinate final
room numbers with owner. Where VAV box serves more than one room, the room
number shall be the room where the thermostat is located.
Where more than one VAV serves a single room there shall be a typical VAV graphic at
the top of the screen with a table below showing values for airflow, damper position,
discharge air temp, etc. Table shall include room airflow totals at bottom row of the
table. Any exhaust dampers associated with a VAV box shall also be shown on the
graphic, included in the tables
Include link to AHU graphic serving VAV box
NU DDC Standards
Page 30
Northwestern University
Scope of BAS Contractor
The purpose of this document is to describe the Enterprise Level Server at Northwestern
University, and the separation of roles between the System Integrator and the Building
Automation System Contractor.
The Enterprise Server consists of the Honeywell Tridium WebsAX running on three Marathon
redundant servers. Two servers are located on the Evanston Campus, and one server is located
on the Chicago Campus. Both the JCI and Siemens head end servers currently reside on this
Marathon redundant server. The long term plan is these two software packages are used for
high level programming only, and will not be used for day to day operations of the JCI or
Siemens BAS.
All new DDC system controllers, terminal device controllers, VFDs, and any other intelligent
control device shall be BTL Certified and shall communicate using BACNET MS/TP. All network
controllers shall communicate to lower level controllers using BACNET MS/TP. Network
controllers shall communicate to each other, and BAS Servers, using BACNET/IP.
The control contractor shall provide a complete DDC system, which interfaces with both the
control vendors "head end" server, and the Northwestern University Tridium Enterprise Server.
The Owners' normal day to day interface will be with the Tridium Enterprise Server. The
configuration of graphics for the Tridium Enterprise Server will be done by the Owner's System
Integrator. The BAS contractor is responsible for coordinating with the System Integrator to
verify all points are properly transmitted to the Enterprise Server including alarm values and
links to trend files. Provide sufficient manpower to work with the System Integrator to do a
point to point test of alarms, trending, setpoint overrides, etc.
Figure 1 shows a simple schematic of the Enterprise Network.
Page 1 of 5
1/15/2014
Northwestern University
Scope of BAS Contractor
Figure 1: Simplified Riser Diagram
Page 2 of 5
1/15/2014
Northwestern University
Scope of BAS Contractor
Role of the Building Automation System Contractor (BASC)
1.
Provide the field devices and wiring including DDC controllers, relays, sensors,
transducers, control devices, control panels, controller programming, controller
programming software, controller input/output and power wiring and controller
network wiring to provide a complete working system of the mechanical equipment.
2.
Submittals: Provide an electronic copy of the specification sheets for the equipment
and DDC controls being provided for the specific project. The drawings shall be
drawn in Visio or AutoCAD, and shall include separate sections for the following:
index page, a riser diagram, flow diagrams, panel detail, wiring schematics,
termination of controllers, full points list including any global or virtual points, any
valve schedules and damper schedules.
3.
Use the Northwestern University DDC Standard document for point naming
structure.
4.
Provide as-built drawings and O&M Manuals in electronic form (Visio or MS Word or
Adobe pdf format).
5.
Provide Network Controllers as required for a project. Coordinate quantity and
locations of new network controller with Owner and System Integrator. Acceptable
network controllers are manufactured by Siemens, Tridium, Johnson Controls, Delta
Controls, and Automated Logic Corporation.
6.
Network Controllers:
a. Johnson Controls:
i. Provide most current Metasys controller compatible with the existing
Johnson Controls campus infrastructure.
ii. Communication to field control devices shall be through BACNET MS/TP,
not JCI N2 unless approved by NU for specific applications.
b. Siemens Controls:
i. Provide most current Apogee controller compatible with the existing
Siemens campus infrastructure. PXC Modular is preferred to PXC
Compact.
ii. Communications to field control devices shall be through BACNET MS/TP,
not Siemens FLN unless approved by NU for specific applications.
c. Honeywell Tridium:
i. Northwestern University has standardized on the Honeywell WEB-600-OUS NiagaraAX™ Controller, to follow a consistent standard of design and
operation supporting overall system conformance standards. Other
branded NiagaraAX™ network controllers are unacceptable.
ii. All network controller hardware products shall be “Made in the USA” or
come through the Tridium Richmond, Virginia shipping facility.
Page 3 of 5
1/15/2014
Northwestern University
Scope of BAS Contractor
iii. All network controllers shall include a lifetime license for free software
upgrades.
iv. The network controllers shall be provided with no connectivity restrictions
on which brand stations or tools can interact with the system. The
station and tool “NiCS” would be as follows:
Property
Value
STATION COMPATIBILITY IN
ALL
STATION COMPATIBILITY OUT
ALL
TOOL COMPATIBILITY IN
ALL
TOOL COMPATIBILITY OUT
ALL
d. Delta Controls:
i. Northwestern University does not have a standard developed for Delta
Controls at the time of publication.
e. Automated Logic
i. Provide most current controller compatible with existing ALC campus
infrastructure.
ii. Communications to field control devices shall be through BACNET MS/TP.
7.
Point to point checkout.
8.
Verify all physical alarms.
9.
Setup alarms in the network controller in accordance with the Northwestern
University DDC Standards document. Coordinate with Owner on alarm distribution.
Work with the SI to make sure the Enterprise Server is receiving the alarms.
10.
Setup trends in the BASC’s associated server in accordance with the Northwestern
University DDC Standards document. Work with the SI to make sure the Enterprise
Server is receiving the trends.
11.
Accessing controllers via PCAnywhere, Telnet or similar software is not allowed.
Remote access shall be through Northwestern’s SSLVPN.
12.
Any software required for controller configuration shall be included as a leave-behind
tool with enough license capability to support the installation. Provide the
appropriate quantity of legal copies of all software tools, configuration tools,
management tools, and utilities used during system commissioning and installation.
All tools shall be generally available in the market. No closed and/or unavailable
tools will be permitted. Contractor shall convey all software tools and their legal
licenses at project close out.
Page 4 of 5
1/15/2014
Northwestern University
Scope of BAS Contractor
Role of the System Integrator (Separate Contract):
1.
The System Integrator (SI), Engineer, Owner and selected Building Automation
System Contractor (BASC) meet to review the project so that all programming,
design standards and job specific requirements are consistent with the NU DDC
Standards.
2.
Coordinate with the BASC to ensure point discovery and integration is scheduled at
appropriate times during construction.
3.
The SI shall be responsible to build/create the graphic layout/background slides in
conformance with the Northwestern University DDC Standards document. The
graphics shall be resident on the Enterprise Server.
4.
Maintain point naming structure. Verify BASC is adhering to the naming convention.
5.
Coordinate with the BASC to verify proper alarm input to the Enterprise server, and
display on the graphics.
6.
Coordinate with the BASC to verify proper link to the trend files on the Enterprise
server graphics.
7.
Setup event log.
8.
Merge project O&M documents, including the control drawings, into a common
system O&M manual.
9.
Work with the Owners IT Department to establish I/P network addresses with
BACnet instance IDs and ensure the appropriate I/P addresses with BACnet instance
IDs are used throughout the BAS Enterprise.
10.
Maintain the Energy Analytics software on the Marathon redundant server, including
all software upgrades.
Page 5 of 5
1/15/2014
Our Purpose Is To Enrich Outdoor Spaces
We believe in the power of design and its ability to
elevate experience and help create a sense of place
in public environments. Our high quality products and
outstanding customer service have e a r n e d u s a
reputation as one of the world’s premier designers
and manufacturers of outdoor commercial furnishings.
Woodbench Specifications
Gretchen Bench
Finishes
Available backed or backless. Backed version available with two armrest
Interior woods are finished with Landscape Forms’
styles — loop or ornamental. Offered in 72" or 96" lengths. Freestanding,
exclusive LF-80 wood finish, a clear, catalyzed acrylic
surface mounted, or wall mounted styles offered. Available in a variety of
catalyzed acrylic lacquer.
woods or PolySite ™ recycled timbers (PolySite not offered in 96" length).
Exterior woods are unfinished and will weather to a soft
Gretchen Picnic Table
pewter gray, requiring no future maintenance.
Wheelchair accessible from either end. Available in a variety of woods or
Metal is finished with Landscape Forms’ proprietary
PolySite™ recycled timbers. Freestanding or surface mounted. Umbrella hole
Pangard II ® polyester powercoat, a hard yet flexible
available. ADA compliant style available. Contact Landscape Forms for details.
finish that resists rusting, chipping, peering and fading.
Gretchen Litter Receptacle and Ash Urn
Large 30-gallon capacity receptacle with liner. Choose from side or top
opening receptacle styles. Sand pan available for side opening receptacle.
Available in a variety of woods or PolySite ™ recycled timbers. Coordinating
ash urn available.
Call for standard color chart. A wide array of optional
colors may be specified for an upcharge.
Consult Landscape Forms price list for complete
specifying information. Visit landscapeforms.com; click
Design Tools, Materials/Colors link for standard offerings, including FSC wood options.
Balustrade
Constructed of 2" x 3" wood rails individually fastened to steel bands. Available
backed or backless. Backed bench offered in 72" and 96" lengths, backless
in 72" only. End loop arm available on backed bench. Freestanding, embedded, surface mounted or wall mounted styles offered. Available in a variety
of woods or PolySite ™ recycled timbers (PolySite ™ not offered in 96" length).
Palisade and Shadowline
Backless benches are constructed of solid wood, fastened together with
internal steel rods. Available in 72" and 96" lengths. Palisade is freestanding,
and offered in a variety of woods. Anchor clips available. Shadowline offered
in a variety of woods. May be surface mounted, embedded, freestanding or
wall mounted.
Cover Photo: Shadowline Bench
Specifications are subject to change without notice.
Woodbench collection is manufactured in U.S.A.
Location Photography : Kalamazoo Institute of Arts
Landscape Forms supports the LAF at the Second Century level.
©2011 Landscape Forms, Inc. Printed in U.S.A.
Metal is the world’s most recycled material and is fully recyclable. Powdercoat finish
on metal parts contains no heavy metals, is HAPS-free and has extremely low VOCs.
Consult our website for recycled content for this product.
Landscape Forms is proud to specify FSC and Green-e certified paper. This paper meets
the Forest Stewardship Council’s standards for responsible forest management and is
made using certified renewable energy.
800.521.2546   269.381.3455 fax 