10 s03-1-5-07 wiring diagram switch pack control data notes: cable

NOTES:
ACTIVES TO LANTERNS
TO LANTERNS
ACTIVES
NEUTRALS
NEUTRALS
TO LANTERNS
10A
10A
10A
EARTHS
TO
LANTERNS
1
DIAGRAM SHOWS ARRANGEMENT FOR 18M COLUMNS.
2.
FOR SINGLE LAMP APPLICATIONS FIT ONE CIRCUIT BREAKER AT POSITION 1.
3.
FOR DOUBLE LAMP APPLICATINS FIT TWO CIRCUIT BREAKERS AT POSITIONS 1 & 2.
4.
FOR ADDITIONAL MAINS TEE OFF, CONNECT 25sqmm CABLES (ACTIVE AND NEUTRAL)
TO TOP SIDE OF TERMINAL LINK BLOCK.
5.
25sqmm MAINS SHALL BE TERMINATED TO 16SQMM WITHIN THE COLUMN USING
COPPER CONNECTIONS ANDS THICK WALLED HEAT SHRINK.
6.
ALL CRIMP CONNECTIONS SHALL BE DONE AS PER S02-2-2-10.
7.
25sqmm NEUTRAL CABLES SHALL BE T-CONNECTED INTO POLE USING 3 WAY
TERMINAL BLOCK (CABAC TB503) WITH 16sqmm CABLE. TIGHTENING TORQUE 10-14NM.
8.
ALL CABLES SHALL HAVE DESTINATION TAG WITH CRITCHLEY K-TYPE TAG SECURED
TO THE CABLE WITH NYLON CABLE TIES.
9.
WHERE CABLE PITS ARE USED A EARTH JOINT USING 35 / 35 'C' CRIMP IS ALLOWED
EARTHS
9
2
1.
CABLE SIZES
POLE
EARTH STUD
3
INCOMING & OUTGOING MAINS 25sqmm (35sqmm EARTH)
LANTERN CABLE - FROM
TERMINAL LINKS THROUGH TO
LANTERN, REFER S02-1-1-14
10
POLE
EARTH STUD
4
MAIN 16sqmm
NOTE 5
4sqmm TWIN/ECC
RED - ACTIVE
BLACK - NEUTRAL
YELLOW/GREEN - EARTH
MAIN EARTH
TEE-OFF
7
EARTH TEE-OFF
(35sqmm)
16sqm
MAIN EARTH TEE OFF 6sqmm GREEN/YELLOW
E
8
6
4
2
E
ITEM 11 REFER NOTE 7
5
2
NOTE 9
TO BE READ IN CONJUNCTION WITH CONSTRUCTION DRG No. S03-1-5-12
ACTIVE
A
NEUTRAL
1
2
406821
35sqmm 'C' CLAMP
S01-1-5-08
2
AR
9449
25sqmm CU CABLE - RED
S02-1-1-20
3
AR
9456
25sqmm CU CABLE - BLACK
S02-1-1-20
N
EARTH
E
7
8
11
11
NOTE 7
6
NOTE 5
3
3
1
WIRING DIAGRAM
4
AR
1644
16sqmm CU CABLE - RED
S02-1-1-23
5
AR
1636
16sqmm CU CABLE - BLACK
S02-1-1-23
6
AR
9829
35sqmm CU BARE EARTH WIRE
S01-1-5-05
7
2
5272
16 - 25sqmm COMPRESSION LINK
8
AR
3129
HEATSHRINK TO SUIT CU LINK
S02-1-2-15
9
AR
2733
4sqmm TWIN/ECC CABLE
S02-1-1-14
10
AR
2774
6sqmm CU Y/GR INSULATED CABLE
S02-1-1-23
11
1
502906
NOTE 7
1
SCHEMATIC WIRING DIAGRAM
ITEM
10
9
EXTRA EARTH CRIMP ADDED, NOTE 9 ADDED
C.C. AUG'17 I.B.
B.C.
NOTE 7, ITEM 5 UPDATED
A.T. MAY'16 I.B.
B.C.
8
ITEM 11 ADDED, NOTE 7 AMENDED, MATERIAL TABLE UPDATED
A.S
FEB'15 I.B.
B.C.
7
NOTE 6 ADDED
A.T. MAY'12 B.C.
S.C.
6
CABLE SIZES/NOTES 5 ADDED
5
TEE OFF AMENDED
NO
DESCRIPTION
AMENDMENTS
A3 297 X 420
RAJ
AUG'06
RAJ
RAJ
AUG'06
RAJ
S.C.
DRN
DATE
CKD
APPD
S.C.
NORTHERN TERRITORY
QTY. STOCK CODE
DES
G.S.
DRN
HT
CKD
N.F.S.
APPD
B.T.Kent
SCALE
NTS
ISSUED
..
ALL DIM. IN mm
-
3 WAY TERMINAL BLOCK (SEE NOTE 7)
DESCRIPTION
DRAWING No.
POWER STANDARD DRAWING
CONTROL DATA
SWITCH PACK
WIRING DIAGRAM
A3
DRAFTING STANDARD TO A.S.1100
DRAWING
NUMBER
CAD PRODUCT
S03-1-5-07
DO NOT AMEND MANUALLY
10
AMDT