PT713-EI
FOR FLOOR HEATING
DIGITAL
THERMOSTAT
•maintaining minimum floor temperature
•monitoring maximum floor temperature
•PI regulation and predictive system
•backup in case of voltage failure > 100 hours
•direct installation on junction box
•well-arranged backlit display
•VENUS switch design
•including external sensor
MADE IN CZECH REPUBLIC
DESCRIPTION
PT713-EI is a digital thermostat with a room and floor sensor, specially designed for electric floor heating
control. The internal-external sensor combination provides for the regulation (for setting, see page 8)
of:
1) room temperature (internal sensor) - when comfortable room temperature is required;
(external sensor) - when comfortable room temperature is required; locate the external
sensor in a suitable place where the measured values will not be
distorted;
2) floor temperature (external sensor) - suitable, for instance, for bathrooms where a warm floor is
desirable, irrespective of the room temperature;
3) combined (both sensors)
- the internal sensor scans the room temperature, and the external
one monitors the maximum floor temperature; comfortable room
temperature is required, however, with simultaneous monitoring of
the floor temperature (suitable for wooden and laminated floors).
Another advantage is the simple installation in KU/KP68 junction boxes by means of the PLUG-IN system; the possibility of setting 9 weekly programs with 6 temperature changes per day; regulation type
selection (page 6); as well as other functions for efficient regulation of the floor heating.
INSTALLATION AND LOCATION
Install the thermostat in a suitable place (minimum height of 1.2-1.5 m above the floor) where its
operation will not be affected by direct hot/cold air flows, sunshine or other disturbing influences.
Do not mount the thermostat on an exterior wall either. In rooms with increased humidity (bathroom,
kitchen), observe valid standards and install the thermostat as far from the bathtub, shower, basin
or sink as possible.
The external floor sensor (type CT04-10k P, CYXY 2 x 0.5 mm, 10 kΩ, length 3 m, PVC plastic case)
must be located in a flexible plastic tube embedded in the floor, as near to the surface as possible.
The tube must be sealed and protected against in-leak of building materials so that the floor sensor
can be replaced easily if need be. It must not run parallel with power conductors! It can be extended
to a maximum length of 30 metres.
The installation must only be executed by a properly qualified person!
Switch off power supply before installation!
1) Switch off the main circuit breaker.
2) Check that the junction box is placed parallel with the wall.
3) Separate the power part of the thermostat from its microprocessor (main) part; see Fig. 1.
4) Pull the connecting terminals out of the thermostat rear part, see Fig. 2.
5) Connect conductors to the terminals acc. to the wiring diagram below, see page 3 and Fig. 3.
6) Insert the terminals into the thermostat terminals and fasten the power part to the junction
box, see Fig. 4 and 5.
7) Insert the main part connector into the power part and push it; the metal springs must
fit in the given holes, see Fig. 6 and 7.
8) Switch on the main circuit breaker; the thermostat is ready for operation.
Note: We recommend you test correct connection after installation, see the TEST function (page 10).
2
Wiring diagram:
N L
power part
main part
COM NO
2760 W
COM NO
2760 W
N L
Fig. 1
When using the low tariff
NTC 10k
PULL
PULL
NTC 10k
connecting
terminals
L'
L‘ = disconnected phase
Fig. 2
Fig. 3
Fig. 4
PUSH the connecting
terminals in.
9
NO COM
L N
PULL out the connecting terminals.
Connect according to the wiring diagram.
Fig. 6
Fig. 5
Screw the power part to
the junction box.
Fig. 7
Connector and holes
for metal springs.
PUSH the
main part
onto the
power part.
BACKUP BATTERY (rechargeable NiMH):
The thermostat is equipped with a backup battery. The battery charging time is about 12
hours. In case of voltage failure, the device automatically operates on the backup battery (the
relay is in the off state). Actual time is kept for more than 100 hours; the preset programs are
kept permanently in the E-EPROM memory. When the voltage is restored, the thermostat returns to the last selected mode.
After the first connection of the thermostat, the backup battery is charged for about 12 hours!
PLUG-IN SYSTEM = quick and easy installation. The thermostat is divided into the power
part and the main microprocessor part, which can be joined by simple insertion of the interconnecting terminals. The input conductors (or external sensor) are connected to the power
part terminals and fastened to the junction box; then you can simply finish the installation by
inserting the main part onto the power part.
3
LCD DESCRIPTION
1, Current date (in the PROG mode, selection
of number of days for programming)
2, Operating modes
OFF/PROG/AUTO/MANU/HOLIDAY
3, Current room temperature
4, Indication of room temperature measurement
by the external sensor
5, Heating on indication
6, Button lock indication
7, CLOC mode indication
(current date and time setting)
8, Required temperature and current time
display / listing of operating modes (this line
is explained in detail with every mode)
9, Battery supply indication (in case of
230V/50Hz voltage failure, it is functional
only after 1 day of operation, when
the backup battery is charged!)
10, Indication of setting the external sensor
as the floor one
11, Anti-freeze temperature of 3°C
12, Comfortable temperature in the MANU mode
13, Economical temperature in the MANU mode
DESCRIPTION OF CONTROL BUTTONS
MENU
button:
short press = opens the main menu and
confirmation (ENTER)
long press (approx. 3 sec) = return from
the main menu
MENU
simultaneous press of the MENU and
simultaneous press of the MENU and
simultaneous press of the MENU and
mode
/
button:
basic mode = opens info (see page 9)
main menu =browse and set current values
buttons (in basic mode) = key lock
buttons (in basic mode) = key unlock
/
buttons (in main menu) = return to basic
Note: The LCD backlight is activated by pressing any button!
4
OPERATING MODES
By pressing any button, you activate the display backlight. Next, pressing the MENU button
briefly, you enter the main menu, in which you can choose the operating modes.
AUTO
The thermostat works according to the preset weekly program.
Press the MENU button and choose the AUTO mode with
/
buttons. Press MENU to confirm.
the
AUTO OFF
The thermostat is switched off until the next change given by the
program.
Press the MENU button and choose the AUTO OFF mode with the
/
buttons. Press MENU to confirm.
(default setting of 21°C)
MANU
The thermostat works according to the preset temperature
which remains constant until the next manual change.
Press the MENU button and choose the MANU
/
buttons. Press MENU to confirm.
MANU
,
mode with the
(default setting of 19°C)
The thermostat works according to the preset temperature
which remains constant until the next manual change.
Press the MENU button and choose the MANU
/
buttons. Press MENU to confirm.
,
mode with the
MANU OFF
The thermostat is switched off until the next manual change.
Press the MENU button and choose the MAN OFF mode with the
/
buttons. Press MENU to confirm.
HOLIDAY IN THE AUTO MODE
The thermostat maintains the preset temperature until the given
date and time. When the preset period expires, it returns to the
AUTO mode automatically.
Press the MENU button and choose the AUTO mode with the
/
buttons. Press MENU to confirm.
The temperature value flashes on the LCD. Set the desired temperature with the
/
buttons and press MENU to confirm it;
next, set the hour, minute, day, month and year when your holiday
ends; confirm each setting by pressing MENU .
After setting, the device automatically switches to the HOLIDAY mode
within 1 minute! The holiday end date appears on the display!
Note: You can end the holiday mode at any time by choosing another mode (e.g., AUTO).
5
HOLIDAY IN THE MANU
MODE
The thermostat maintains the preset temperature until the given
date and time. When the preset period expires, it returns to the
MANU
mode automatically.
Press the MENU button and choose the
MANU
mode with the
/
buttons. Press MENU to confirm. The temperature value flashes on the LCD. Set the desired tem/
buttons and press MENU to confirm it; next, set the hour, minute, day, month and
perature with the
year when your holiday ends; confirm each setting by pressing MENU . After setting, the device automatically
switches to the HOLIDAY mode within 1 minute! The holiday end date appears on the LCD.
HOLIDAY IN THE MANU
MODE
The thermostat maintains the preset temperature until the given
date and time. When the preset period expires, it returns to the
MANU mode automatically .
Press the MENU button and choose the MANU mode with the
/
buttons. Press MENU to confirm.
Further setting is the same as for the MANU mode .
Note: You can end the holiday mode at any time by choosing another mode (e.g., AUTO).
CLOC
Setting the current date and time.
Press the MENU button and choose the CLOC mode with the
/
buttons. Press MENU to confirm.
The current hour value flashes on the LCD. Set the current hour and
confirm it by pressing MENU then, set the minutes and seconds; next,
the current date appears; again, set the current day, month and year
with the
/
buttons. Confirm each setting by pressing MENU .
PROG
Setting of weekly programs (9 weekly programs are available,
each with 6 changes per day).
Press the MENU and choose the PROG mode with the
/
buttons. Press MENU to confirm.
P1 (the first weekly program) flashes on the LCD; press MENU to confirm
it. The programmed day number flashes on the LCD, choose one of the
options with the
/
buttons (you can program “day after day”, or
Mon-Fri, Sat-Sun or Mon-Sun). Press MENU to confirm your choice.
The display shows U1 for setting the first temperature change; set the temperature with the
/
buttons and confirm with the MENU button.
Set the switching time with the
/
buttons and confirm with the
MENU button again.
The display shows U2 for setting the second temperature change. Follow
the procedure for the first temperature change. In this way, you can set
up to 6 temperature changes per day. To return to the basic mode, press
the MENU and
/
buttons simultaneously.
EVEN / ODD WEEK SELECTION
The last 2 programs (PU = even, PL = odd) are intended for setting programs for even and odd weeks.
This is suitable for shift operation in which you require a different temperature mode for every week. If you
enable this function (see page 10), the PU and PL programs automatically alternate every week.
6
CONST
Setting of the regulation parameters.
Press the MENU button and choose the CONST mode with the
/
buttons. Press MENU to confirm it. The first parameter appears on the LCD.
1 MINIMUM REGULATED TEMPERATURE
Limitation of the minimum temperature adjustable.
It can be set within the range 3°C to 10°C.
Set the pertinent value with the
/
buttons and press
to confirm.
MENU
2 MAXIMUM REGULATED TEMPERATURE
Limitation of the maximum temperature adjustable.
It can be set within the range 15°C to 99,5°C.
Set the pertinent value with the
/
buttons and press
to confirm.
MENU
3 SELECTION OF PI REGULATION OR HYSTERESIS
Choose the regulation type with the
/
buttons and
press MENU to confirm.
If PI regulation is selected, constant 4 is automatically skipped, and constants 5, 6 and 7 appear, which apply to the PI
regulation setting.
If hysteresis is selected, you can set values from 0.1 to 5 °C.
If, for example, the hysteresis is 1 °C and the required temperature is 20 °C, the thermostat switches off at 20 °C and
switches on again at 19 °C.
4 MINIMUM SWITCH-ON TIME IN HYSTERESIS
Here, you can set the minimum switch-on time of the heating device in
hysteresis in minutes. It can be set within the range 1 to 5 minutes.
/
buttons and press MENU
Set the pertinent value with the
to confirm.
5 TIME INTERVAL OF PI REGULATION
This can be set within the range 5 to 20 minutes. The interval
value is given by the room thermal inertia.
For floor heating, the optimum setting is 10-15 minutes.
Set the pertinent value with the
to confirm.
/
buttons and press
MENU
6 MINIMUM SWITCH-ON TIME OF HEATING DEVICE IN PI REGULATION
This can be set within the range 1 to 5 minutes. The setting is
given by the type of heating system and depends on the selected time interval of PI regulation. For floor heating, the optimum
setting is 4 minutes.
Set the pertinent value with the
to confirm.
7
/
buttons and press
MENU
7 PROPORTIONAL BAND IN PI REGULATION
This item determines the value from which the PI regulation starts operating. Example: The required temperature is 22.0 °C and the proportional band is 1.5 °C. Then, the source will fully heat up to 20.5 °C;
once this temperature is reached, PI regulation starts operating. The
proportional band can be set within the range 1 to 3 °C.
Set the pertinent value with the
/
buttons and press MENU to confirm.
8 EXTERNAL SENSOR SELECTION
Select the external sensor according to the regulation type:
1, Regulation by room temperature - the sensor is located in the room (selection - - -)
2, Regulation by floor temperature - the sensor is located in the floor (selection - - -)
3, Monitoring of floor maximum temperature - the sensor is located in the floor (selection 15 to 99.5°C)
Choose according to the type of use with the
/
buttons and press
MENU
to confirm.
EXTERNAL SENSOR USED AS ROOM ONE:
---
The external sensor, if connected, measures the
temperature at the point of location (suitable, for
instance, for bathrooms, where you wish to
have a warm floor irrespective of the room
temperature);
This use of the sensor is indicated by the
sign on the LCD.
EXTERNAL SENSOR USED AS FLOOR ONE (MAXIMUM FLOOR TEMPERATURE IS SET):
15…99,5°C The external sensor, if connected, monitors the floor
temperature; the maximum permissible temperature is
set for the floor heating ((you regulate with the room
temperature, monitoring the floor temperature at
the same time).
The floor (monitoring) sensor is indicated by the
sign on the LCD.
If the preset limit temperature is exceeded, the thermostat is switched off irrespective of the room temperature, and the STOP message appears on the LCD. Once the external sensor temperature drops by 0.5 °C,
the heating device is switched on again. If the sensor is not connected or it is defective, the C2.Err error
message appears on the LCD.
After connecting the external sensor, it is NECESSARY to RESET (see parameter 11)!
9 MINIMUM TEMPERATURE OF FLOOR HEATING
This setting can be used only if the external sensor is connected and the “External sensor used as
floor one” function is selected. It determines the time interval during which the minimum floor temperature should be maintained. Thus, it is possible to maintain a comfortable floor temperature during
the preset time. If the temperature drops below the given limit, the floor is automatically heated up to
the minimum temperature.
Set the beginning of the time interval for maintaining the minimum
/
buttons and press MENU to confloor temperature with the
firm.
Set the end of the time interval for maintaining the minimum floor
/
buttons and press MENU to confirm.
temperature with the
Set the minimum floor temperature value with the
tons and press MENU to confirm.
8
/
but-
Note: The example shows a setting where the floor temperature
must not drop below 10 °C all day long.
10 CURRENT TEMPERATURE CORRECTION (internal sensor)
This is used for correcting the thermostat-measured temperature. The
setting can be done only after 12 operating hours, when the internal
sensor temperature has settled. Measure the room temperature with
a thermometer; if it is different from that measured by the thermostat,
set the correction within the range from -5 °C to +5 °C.
Set the pertinent value with the
/
buttons and press MENU
to confirm.
11 FIRMWARE VERSION / DEFAULT SETTING RECOVERY
Information on the firmware version. If you keep pressing the
button (approx. 3 sec), the RESET message briefly appears on the LCD, and the thermostat recovers the default setting!
You can exit the CONST mode at any time by simultaneously pressing the MENU and
buttons (return to the basic mode).
/
OTHER FUNCTIONS
INFO
By pressing the
/
buttons in the basic mode, you can view the following information:
REQUIRED TEMPERATURE
In the basic mode, press the
/
buttons. The LCD shows
the required temperature value for the current operating mode
(it can be changed with the
/
buttons; in the AUTO
mode, the change is short-term – until the next change in the
program; in the MANU mode, the change is permanent).
With another press of the MENU button, you can switch to:
SELECTED PROGRAM NUMBER - in the AUTO mode only
This is used for quick change of the program selected in the
AUTO mode. If both P1 and P2 programs are preset, they can be
changed, after a week for example, with the
/
buttons.
With another press of the
MENU
button, you can switch to:
SUMMER MODE
Heating cannot be switched on in this mode. It can be used particularly in the summer period, where heating is not necessary.
Enable the function with the
/
buttons and choose A (the
“SUMMER” message appears on the LCD);
Press the
MENU
MENU button to confirm and switch to:
EARLY START OF HEATING – predictive system
This function guarantees you the required temperature at the required
time. Within two operating days, the thermostat ascertains the temperature constants of the room, and then switches the heating in advance. The early start time is limited to 2 hours. You can enable it with the
/
buttons and the A selection;
Press the
9
MENU
button to confirm and switch to:
EVEN / ODD WEEK SELECTION
This function is effective provided you have set the PU (even week)
and PL (odd week) programs, see page 5. Once you have chosen this
function, the preset program will automatically alternate every week.
This can be used particularly for shift operation, when you need a different temperature mode every week. You can enable it with the
/
buttons and the A selection;
Press the
MENU
button to confirm and switch to:
„ OPEN WINDOW “ FUNCTION - automatic inhibition
If the room temperature abruptly falls by 1.2 °C within 10 minutes
(owing to, for example, an open window), the heating is switched off.
The INHIBITION message appears on the LCD. The mode is terminated if the temperature increases within 30 minutes, or if you open the
main menu.
You can enable it with the
/
buttons and the A selection;
Press the
MENU
button to confirm and switch to:
OPERATING HOURS
The LCD shows the operating hour value of the heating device.
You can clear the counter by pressing the
3 sec;
With another press of the
MENU
button for
button, you can switch to:
TEST
The LCD shows the TEST message, which can be switched to the
LCD test on/off with the
/
buttons (the output relay will be
switched on/off several times).
We recommend using this function for the first use of the thermostat to check its correct connection!
With another press of the MENU button, you can view prior information if the external sensor is connected as the floor (monitoring) one:
CURRENT TEMPERATURE OF THE FLOOR SENSOR
This is enabled if the external sensor is connected as a floor
one. The LCD shows the current temperature value of the floor
sensor.
To return to the basic mode, keep pressing the MENU button (for approx. 3 sec)!
10
LOCK
In the basic mode, simultaneously press the MENU and
buttons, the buttons will lock (the key
sign on the LCD). Unlocking can be done by simultaneously pressing the MENU and
buttons.
ANTI-FREEZE MODE
If the room temperature drops below 3 °C, the heating is switched on automatically (the
symbol appears on the LCD). As soon as the temperature increases, the device returns to
the preset mode.
PROGRAM SETTING EXAMPLE
P1
Program number
U1
Temp.
period
T [°C]
U2
t [h]
T [°C]
U3
t [h]
T [°C]
U4
t [h]
T [°C]
U5
t [h]
Mon-Fri
23
6:00
19
9:00
21
13:00
23
16:00
Sat-Sun
23
8:00
20
11:00
23
15:00
19
21:00
T [°C]
25
U6
t [h]
18:00
T [°C]
19
t [h]
22:00
TABLE OF YOUR PROGRAMS
P1
Program number
U1
Temp.
period
T [°C]
U2
t [h]
T [°C]
U3
t [h]
T [°C]
U4
t [h]
T [°C]
U5
t [h]
T [°C]
t [h]
T [°C]
U6
t [h]
T [°C]
t [h]
T [°C]
t [h]
Mon-Fri
Sat-Sun
P2
Program number
U1
Temp.
period
T [°C]
U2
t [h]
T [°C]
U3
t [h]
T [°C]
U4
t [h]
T [°C]
U5
U6
Mon-Fri
Sat-Sun
Dimensions:
WARRANTY CERTIFICATE
(a 2-year warranty is granted for the product)
Date of sale:
81
Product number:
Shop stamp:
Checked by:
81
11
47
t [h]
DIGITAL THERMOSTAT
PT713-EI
Used for the control of electric floor heating (heating cables, mats, foils). It enables regulation according to the room temperature with possible floor temperature monitoring. The
thermostat evaluates the thermal gradient of the room and is able to determine the time
necessary to reach the required temperature (the “Early start of heating” function). The PI
regulation system guarantees temperature increase and its subsequent maintenance at
optimum power consumption.
Properties:
4 9 weekly programs with 6 temperature
changes per day
4 backlit display
4 regulation type selection
PI regulation or HYSTERESIS
4 heating source min. switch-on time setting
4 predictive system (guarantees the specified
temperature at the required time)
4 operating modes:
AUTO/MANU/OFF/HOLIDAY
4 maximum floor temperature limit value
setting
4 minimum floor temperature limit value
setting with possible specification of
time interval for which the temperature
should be maintained
4 summer mode
PI regulation – hysteresis comparison:
temperature
External sensor:
4 even / odd week selection
4 “open window” function (automatic
inhibition upon abrupt temperature fall)
4 quick change of the required temperature
4 operating hours information
4 TEST function for checking the correct
connection
4 child lock – locking of keys
4 backup in case of voltage failure for
more than 100 hours
4 simple installation (PLUG-IN system)
4 elegant design of the VENUS switch series
4 possibility to purchase an inner frame in
a different colour (see the sample card
at www.elbock.cz)
included in the package
type CT04-10k,
CYXY 2 x 0.5 mm,
10 kΩ, length 3 m,
PVC plastic case
required temperature
thermostat with PI regul.
thermostat with hysteresis
time
Technical parameters
Another advantage:
The thermostat can be located in the multiple frame of the
VENUS design.
Pb
LEAD FREE
v souladu s RoHS
Power supply
Number of adjustable temp.
Hysteresis
Minimum program time
Adjustable temp. range
Temperature setting
Minimum indication step
Measurement accuracy
Backup battery
Degree of protection
Output
Working temperature
230 V/ 50 Hz
6 different temp. per every day
0.1 to 5°C
10 minutes
+3°C to 99.5°C
by 0.5°C
0.1°C
± 0,5°C
more than 100 hours
IP20
max.12A (potential-free contacts)
0°C to +40°C