comfort system - Jackson Systems

TM
COMFORT SYSTEM
Commercial VAV & Zone Control System
Modulating
The Alternative to Trane® VaritracTM and Carrier® VVTTM
Zone Control Systems
www.jacksonsystems.com
1.888.652.9663
Z-1600 MODULATING ZONE CONTROL SYSTEM
System Features
• Fully modulating zone dampers or diffusers
• Up to 16 zones
• Auto changeover
• Works with single stage, multi-stage, or heat pump systems
• No programming required
• Auxiliary heat control option for each zone
• Night setback option
• All low voltage wiring
• LEDs indicates status of equipment and zones
• Fused inputs and outputs
System Benefits
• Low Cost
• Simple to wire
• Easy to set up (No Laptop Required)
• Reliable design
• Toll-free phone number for technical support
Zone Control Made Simple™
5418 Elmwood Avenue, Indianapolis, IN 46203-6025
Toll Free: 888.652.9663 Fax: 317.227.1034
www.jacksonsystems.com
08-1009-122206
Z-1600 MODULATING ZONE CONTROL SYSTEM
OVERVIEW
The Z-1600 Comfort System™ is a commercial zone control system that allows a single
HVAC unit to have up to 16 individual zones. Each zone is controlled by its own space thermostat
and a modulating damper. When a majority of zones are calling for cooling, the system operates in
the cooling mode. The Z-1600 controls up to two stages of cooling to maintain a cooling discharge air
setpoint. If a majority of zones are calling for heating, the system changes from the cooling mode to
the heating mode. The Z-1600 then controls up to two stages of heating to maintain a heating
discharge air setpoint. When the number of heating and cooling requests are equal, the system
satisfies the cooling request first.
Comfort System™ zone dampers are available in round and rectangular, as well as VAV
diffusers. All three types are controlled by a P+I modulating thermostat that controls the mode of
operation based on duct temperature. The thermostat controls the zone damper to maintain room
temperature in both cooling and heating modes. When the zone temperature falls below the heating
setpoint, the zone damper sends a signal to the Z-1600 control panel requesting heat. When the
zone temperature rises above the cooling setpoint, the zone damper sends a signal to the Z-1600
control panel requesting cooling. These signals are used to determine the mode (heating or cooling)
of the HVAC unit as described above. The zone thermostat heating output can also be used to
control auxiliary baseboard, duct, or ceiling radiation heat.
A bypass damper is installed between the supply and return air duct to maintain the proper
system static pressure. Bypass dampers are available in both electronic and barometric type.
Electronic bypass dampers are recommended for systems with static pressure of 0.75” w.c. and
over. Barometric bypass dampers are recommended for systems under 0.75” w.c. of static pressure.
Zone Control Made Simple™
5418 Elmwood Avenue, Indianapolis, IN 46203-6025
Toll Free: 888.652.9663 Fax: 317.227.1034
www.jacksonsystems.com
08-1010-122206
Z-1600-T MODULATING ZONE THERMOSTAT
WITH AUTO CHANGEOVER
DISCHARGE AIR SENSOR
A discharge air sensor is supplied with each
thermostat. The purpose of the discharge air
sensor is to select the mode of operation of the
damper. If the discharge air temperature is
above 72° F, the damper will open on a call for
heating. If the discharge air temperature is
below 72° F, the damper will open on a call for
cooling.
TESTING DISCHARGE SENSOR
DISASSEMBLING THERMOSTAT
To separate the thermostat from the
backplate, hold the front of the thermostat
with right hand. Use the thumbnail of left
hand to hook the extremely small rounded
tab located on the top edge of the
thermostat backplate and pull apart.
PUSH BUTTON FUNCTIONS
Press the ON button to activate the
thermostat.
Press the OFF button to deactivate the
thermostat. This will also drive the zone
damper closed.
The C/F button switches the display
between Fahrenheit and Celsius.
THERMOSTAT DISPLAY
The thermostat continuously displays room
temperature.
If the thermostat calls for heating, “HEAT”
will flash on the display. If the thermostat
calls for cooling, “COOL” will flash on the
display.
Setpoint limits are factory preset from
68° F to 76° F. It is recommended that
these setpoint limits not be exceeded.
Zone Control Made Simple™
Disconnecting the discharge air sensor will put
the thermostat in the cool mode. Shorting out
the sensor will put the thermostat in the heat
mode.
TERMINAL DESIGNATIONS
TERMINAL
NUMBER
TERMINAL
DESCRIPTION
1
OPEN DAMPER (24 VOLTS OUT)
2
CLOSE DAMPER (24 VOLTS OUT)
3
HEAT OUTPUT (24 VOLTS OUT)
4
HOT (24 VOLTS IN)
5
COMMON (24 VOLTS IN)
6
DUCT SENSOR
7
DUCT SENSOR
8
COOL OUTPUT (24 VOLTS OUT)
SETTING THERMOSTAT LIMITS
1. Set the setpoint as low as it will go.
2. Press and hold the C/F button until the stat
. beeps and the word “COOL” flashes.
3, Use the (+) or (-) button to adjust the cooling
limit.
4. Press the C/F button again until the stat
beeps and the word “HEAT” flashes.
5. Use the (+) or (-) button to adjust the heating
limit.
6. Press the C/F button again until the stat
beeps and the word “AUX” flashes.
7. This is to adjust the thermostat calibration.
8. Press the C/F button again to exit program.
5418 Elmwood Avenue, Indianapolis, IN 46203-6025
Toll Free: 888.652.9663 Fax: 317.227.1034
www.jacksonsystems.com
06-1009-122206
Z-1600 COMFORT SYSTEM™ PANEL
24 VOLT
TRANSFORMER
HVAC UNIT
24 VOLT TIME CLOCK
(CONTACTS SHOWN IN
OCCUPIED MODE)
M
OVERRIDE TIMER
24 VOLT
POWER
R G Y1 Y2 W1 W2 O
DISCHARGE SENSOR
SETPOINTS
DISC.
SENSOR
(USE N.O. CONTACTS)
NIGHT
STAT
HEAT SETPOINT 140°
COOL SETPOINT 54°
R
WIRE TO ZONE
DAMPER
TERMINALS.
RYW
TO
ZONE
DAMPER
TYPICAL
OF ALL
ZONES
SPEED-UP
JUMPER
(FOR TEST
ONLY)
R ZONE 1
COOL
Y
W
HEAT
ZONE
2
R
Y
COOL
W
HEAT
R ZONE 3
Y
COOL
W
HEAT
ZONE
4
R
Y
COOL
W
HEAT
ZONE
5
R
COOL
Y
W
HEAT
R ZONE 6
COOL
Y
W
HEAT
R ZONE 7
COOL
Y
W
HEAT
24 VAC
# CALLS
DISC
TIME
INPUT
REQUIRED
TEMP
CLOCK
RESISTOR CONTACTS SENSOR POWER
TO BYPASS DISCHARGE AIR SENSOR FOR
TESTING USE 10 K RESISTOR TO BRING ON
COOLING.
DISCHARGE SENSOR IS 12 K @ 70°
ZONE CONTROL
PANEL
DISCHARGE AIR TEMPERAT URE CAN BE
MEASURED BY USING A DC VOLT METER
ACROSS GND AND 8 ON THE LOWER RIGHT
HAND TERMINALS OF THE
MICROPROCESSOR BOARD. (NOT SHOWN)
.1 VDC = 10° F
2
COOL 1
HEAT 2
INPUT
3 AMP FUSE
TS-8 TO MICROPROCESSOR
TS6
ZONE 9 R
COOL Y
HEAT W
ZONE 10 R
COOL Y
HEAT W
ZONE 11 R
COOL Y
HEAT W
ZONE 12 R
COOL Y
HEAT W
ZONE 16 R
COOL Y
HEAT W
HEAT 1
3
4
5
6
HVAC UNIT
TERMINALS
OUTPUT
3 AMP
FUSE
COOL MODE ZONE 13 R
COOL Y
HEAT W
ZONE 14 R
COOL Y
HEAT W
ZONE 15 R
COOL 2
COOL Y
HEAT W
FAN
R ZONE 8
COOL
Y
W
HEAT
24
24
C
1
G Y1 Y2 W1 W2 O
PATENTED
GND
G
Y1
Y2
W2
C
1
2
3
4
5
6
TS-7 FROM MICROPROCESSOR
TO FACTORY WIRED AND MOUNTED
MICRO PROCESSOR BOARD (NO FIELD
SETUP OR ADJUSTMENTS REQUIRED)
Zone Control Made Simple™
5418 Elmwood Avenue, Indianapolis, IN 46203-6025
Toll Free: 888.652.9663 Fax: 317.227.1034
www.jacksonsystems.com
07-1006-122206
TO
ZONE
DAMPER
TYPICAL
OF ALL
ZONES
Z-1600-T MODULATING ZONE THERMOSTAT
AND DAMPER WIRING DIAGRAM
RED LED INDICATES THE ZONE
STAT IS CALLING FOR HEATING.
GREEN LED INDICATES THE
ZONE STAT IS CALLING
FOR COOLING.
Z-1600-T
AUTO CHANGEOVER
SPACE THERMOSTAT
72
1
2
3
4
5
6
7
8
DAMPER OPEN
(24VAC)
DAMPER CLOSED
(24VAC)
CALL FOR HEAT
24 VAC POWER
(24VAC)
(HOT)
24 VAC POWER
(COM.)
DUCT SENSOR
DUCT SENSOR
CALL FOR COOL
(24VAC)
ALLOW 3 MINUTES FOR
THERMOSTAT TO
SYNCHRONIZE ITSELF
JUMPER TERMINALS 1 AND 4
AT THE THERMOSTAT TO
DRIVE DAMPER OPEN
ACTUATOR
BOARD
1
2
3
4
5
6
7
8
T
T
R
Y
W
HEAT
OPEN
CLOSED
COM.
DS
DS
1
2
3
4
5
PURPLE
ORANGE
RED
90 SECOND TIMING
90° STROKE
44 lb.-in.
3VA
COOL
R TO W CONTACTS CLOSE
ON A CALL FOR HEAT.
R TO Y CONTACTS CLOSE
ON A CALL FOR COOL
24 VAC
POWER
DAMPER OR
DIFFUSER
ACTUATOR
WIRE TO
Z-1600
CONTROL
PANEL
DISCHARGE
AIR SENSOR
(59.6 K OHMS @ 70°)
OPERATION SEQUENCE:
TO
OPTIONAL
SLAVE
DAMPER
When the room temperature is 1.5 degrees below setpoint the thermostat will close the R to W contacts on the
actuator board and signal the Z-1600 panel that there is a heating call.
When the room temperature is 1.5 degrees above the setpoint the thermostat will close the R to Y contacts on
the actuator board and signal the Z-1600 panel that there is a cooling call.
DAMPER NOTES:
To balance the HVAC system, remove each zone thermostat from its subbase and jumper terminals 1 and 4 to
drive dampers open.
The actuator board is located on the side of the damper actuator and is wired at the factory.
Each zone damper requires 3VA.
The space thermostat will control up to 6 damper actuators wired in parallel.
If the discharge air temperature at the damper is warmer than 72 degrees, the zone damper operates as a
heating d a m p e r .
If the discharge air temperature at the damper is below 72 degrees, the zone damper operates as a cooling
d a m p e r.
The Z-1600-T zone thermostats have temperature limits set at 68 degrees and 76 degrees and should not be
changed.
Z-1600- PANEL NOTES:
Use standard 18 gauge thermostat wire.
Run three wire cable from the panel terminals (R,Y,W) to each individual zone damper
actuator board.
Panel requires a 24 VAC 40VA transformer.
Locate discharge air sensor 3 feet down stream in trunk line.
“Speed up jumper” shortens all the time delays on the control panel (use for testing only).
“Number of calls required resistor” determines the number of zones that must be calling
in order for he system to bring on the heating or cooling equipment.
Time clock contacts are closed during occupied cycle.
Zone Control Made Simple™
5418 Elmwood Avenue, Indianapolis, IN 46203-6025
Toll Free: 888.652.9663 Fax: 317.227.1034
www.jacksonsystems.com
07-1007-122206
Z-1600 MODULATING ZONE CONTROL SYSTEM
SYSTEM WIRING AND LAYOUT GUIDE
UP TO 2 HEAT / 2 COOL
SIDE VIEW
ZONE DAMPER
MOTORS
BLOWER
TO ADDITIONAL
ZONES
OUTSIDE
AIR
DISCHARGE
AIR SENSOR
HVAC UNIT
PANEL
-2
2-
TO 24 VOLT
POWER
RETURN
AIR
3-
INDICATES NUMBER OF WIRES
2
LOCATE NIGHT STAT
AND OVERRIDE TIMER
IN AN AREA THAT HAS
SOME OUTSIDE WALL
EXPOSURE.
TO 24 VOLT
POWER
TO 24 VOLT
POWER
-8
3-
3ZONE # 1
STAT
A 75 VA TRANSFORMERWILL
POWER UP TO 18 DAMPER
MOTORS.
24 VOLT POWER TO DAMPER
CAN BE EITHER HOMERUNNED OR DAISY-CHAINED.
-2
-8
-8
-7
NIGHT STAT AND
OVERRIDE TIMER
(OPTIONAL)
-2
ZONE # 2
STAT
ZONE # 3
STAT
CONTROL PANEL
TRANSFORMER
24 VOLT, 40VA
2
4
Z-1600
ZONE
PANEL
TO 120 VOLT POWER
2
2
7-DAY TIME CLOCK
(OPTIONAL)
WIRE TIME CLOCK,
NIGHT STAT AND
OVERRIDE TIMER IN
PARALLEL AND
CONNECT TO TIME
CLOCK TERMINALS ON
Z-1600 PANEL.
BYPASS DAMPER SYSTEM
HVAC UNIT
TOP VIEW
STATIC
PRESSURE
PROBE AND
¼” POLY
TUBING
TO 24 VOLT POWER
2
BYPASS DAMPER MOTOR
Zone Control Made Simple™
STATIC PRESSURE CONTROL
5418 Elmwood Avenue, Indianapolis, IN 46203-6025
Toll Free: 888.652.9663 Fax: 317.227.1034
www.jacksonsystems.com
07-1008-122206
Z-1600 PANEL OPERATION
This system generally does not require any adjustments.
A red light indicates the zone is calling for heating. A green light indicates the zone is callinbg
for cooling.
The number printed on the “Call Required Resistor” indicates the number of like calls that must
take place before the heating or cooling equipment will start.
MAJORITY WINS
If more zones call for heating than cooling, the system will be in the heating mode. If more
zones call for cooling than heating, the system will be in the cooling mode.
If the number of heating and cooling calls are equal, the system will be in the cooling mode.
This is referred to as Cooling Priority.
The heating discharge air setpoint is approximately 140° F.
The cooling discharge air setpoint is approximately 54° F.
TIME DELAYS
SPEED-UP JUMPER
NOT INSTALLED
MINIMUM TIME IN HEAT OR COOL MODE
JUMPER
INSTALLED
15 MIN.
3 MIN.
MINIMUM OFF TIME REQUIRED BEFORE THE
EQUIPMENT CAN SWITCH FROM HEAT
TO COOL MODE (Same as purge cycle)
5 MIN.
1 MIN.
TIME BETWEEN STAGES (Up-staging)
15 MIN.
3 MIN.
5 MIN.
1 MIN.
(Once the system is in the heat or cool mode, it
will remain there for a minimum of 15 minutes.
The equipment may or may not be on during
this period.
EQUIPMENT MINIMUM OFF TIME
(Same as short cycle protection)
USE SPEED-UP JUMPER FOR TESTING ONLY!
Zone Control Made Simple™
5418 Elmwood Avenue, Indianapolis, IN 46203-6025
Toll Free: 888.652.9663 Fax: 317.227.1034
www.jacksonsystems.com
06-1010-122806
Z-1600 COMFORT SYSTEM™
DESIGN AND INSTALLATION NOTES
•
Extra consideration should be given when applying any zone control system to a building that
requires large amounts of cooling in the core zones during cold weather. Consider adding
auxiliary heat to external zones or using one system for the core zones and one system for the
external zones.
•
It is recommended that the system installation be limited to 50 tons of capacity. Rooftop units
with economizers and relief dampers are strongly recommended for buildings with core
cooling loads.
•
Oversizing of the HVAC equipment is not recommended. In most cases, it is better to slightly
undersize the equipment.
•
It is recommended that the HVAC equipment have two stages of heating and two stages of
cooling.
•
The pressure drop through the zone dampers is negligible and should not be a factor when
sizing branch duct runs.
•
Zone dampers are rated up to 2” w.c. of static pressure and up to 2,000 fpm.
•
Zone dampers should be installed as far back from discharge air grille as possible. Flex duct
should be used for the last 5 feet of each branch run.
•
Bypass dampers should be sized for 90% of the total system air flow at 2,500 fpm.
•
The Z-1600 Comfort System™ panel should be located near the center of the building to keep
wire runs as short as possible.
•
DO NOT mount the Z-1600 Comfort System™ panel on or inside the rooftop unit.
•
Use a separate 24 VAC, 40 VA transformer for the Z-1600 Comfort System™ panel.
Zone Control Made Simple™
5418 Elmwood Avenue, Indianapolis, IN 46203-6025
Toll Free: 888.652.9663 Fax: 317.227.1034
www.jacksonsystems.com
08-1000-122206
Z-1600 COMFORT SYSTEM™
WIRING DETAILS
GENERAL NOTES
Install the Z-1600 Comfort System™ control panel on a flat surface near the HVAC equipment. The panel should be
installed in a dry, clean location approximately 60 inches from the floor. Do not install the control panel on or inside a
rooftop unit.
24 VOLT POWER
The control panel requires a 24 Volt, 40VA transformer. Do not power the control panel from the transformer in the HVAC
equipment. Connect 24 Volts to the terminals labeled 24 VAC INPUT POWER on the interface board. 18-2 thermostat wire
is recommended.
DISCHARGE AIR TEMPERATURE SENSOR
The control panel requires a discharge air temperature sensor. Mount the sensor 26 inches from the HVAC equipment in
the supply duct. Connect the sensor to the terminals labeled DISC TEMP SENSOR on the interface board. 18-2
thermostat wire is recommended.
HVAC UNIT
The control panel is wired to the HVAC equipment in the same way as a standard 2-stage heat / 2-stage cool thermostat.
Connect the HVAC equipment to the terminals labeled HVAC UNIT TERMINALS on the interface board. 18-8 thermostat
wire is recommended.
R, Y, AND W ZONE DAMPER TERMINALS
The control panel requires a heating and cooling contact closure from each zone damper. Connect terminals R, Y, and W
from each zone damper to the terminals labeled R, Y, and W on the interface board. 18-3 thermostat wire is
recommended.
TIME CLOCK, NIGHT STAT AND OVERRIDE TIMER (OPTIONAL)
The control panel has an optional input for a time clock, night stat, and override timer. To install a time clock, remove the
factory installed jumper between the two terminals labeled TIME CLOCK CONTACTS. Wire the time clock using the
contacts that are closed during the occupied mode. A normally open night stat and override timer can be wired in parallel
with the time clock for unoccupied temperature control. 18-2 thermostat wire is recommended.
PROGRAMMING RESISTOR
The control panel is equipped with a “2 calls required” resistor factory installed on the interface board. This resistor
determines the number of zones that must be calling for heating or cooling before the system will change modes. Resistor
for 1 through 4 “calls required” are also shipped with the control panel. Install the appropriate resistor in the terminals
labeled # CALLS REQUIRED RESISTOR.
SPEED-UP JUMPER
The control panel is equipped with “speed-up jumper” terminals. Installing a jumper between the two terminals labeled
SPEED-UP JUMPER will reduce the time delays between stages and between modes of operation. The standard time
delay between stages and between modes is 15 minutes. With the jumper installed, the time delays are reduced to 3
minutes.The speed-up-jumper is for commissioning only. Do not leave the jumper installed after the unit is commissioned.
MICROPROCESSOR BOARD
The microprocessor board requires no wiring, adjustment, or maintenance.
Zone Control Made Simple™
5418 Elmwood Avenue, Indianapolis, IN 46203-6025
Toll Free: 888.652.9663 Fax: 317.227.1034
www.jacksonsystems.com
08-1001-122206
Z-1600 COMFORT SYSTEM™
CONTROL PANEL SPECIFICATIONS
APPLICATION:
The model Z-1600 Comfort System™ is a commercial zone control system that allows a single heating and cooling unit to
have up to 16 individual zones. Each zone is controlled by its own space thermostat and motorized damper. If a majority of
zones are calling for heat, the system will operate in the heating mode. The two stages of heat will be cycled to maintain
the heating discharge air setpoint. If a majority of zones are calling for cooling, the system will operate in the cooling mode
and the two stages of cooling will be cycled to maintain the cooling discharge air setpoint. If the number of zones calling for
heating and cooling are equal, the system will operate in the cooling mode first. This is known as Cooling Priority. Each
zone damper or diffuser will modulate, based on zone and discharge air temperature, to maintain the individual zone
temperature setpoint. A barometric or electronic bypass damper will modulate to maintain the duct static pressure.
DIMENSIONS:
Height:
Width:
Depth:
16.0”
13.0”
2.75”
PANEL CONSTRUCTION:
Rating:
Material
Door:
Finish:
NEMA 1
#18 aluminum with 6 knock-outs on top (open bottom)
Fully removable, self-centering
Anodized
POWER REQUIREMENTS:
Voltage:
VA:
24 VAC
Panel - 20 VA
Dampers / Diffusers - 3 VA Each
OPERATING AMBIENT:
Temperature:
32°F to 120°F
SHIPPING WEIGHT:
Panel Weight:
10.0 lbs.
WARRANTY:
Panel:
5 Years
Zone Control Made Simple™
5418 Elmwood Avenue, Indianapolis, IN 46203-6025
Toll Free: 888.652.9663 Fax: 317.227.1034
www.jacksonsystems.com
08-1002-122206
Z-1600 COMFORT SYSTEM™
ZD SERIES ZONE CONTROL DAMPER SPECIFICATIONS
APPLICATION:
The model ZD is a round commercial zone control damper assembly that includes a damper, modulating actuator, duct
temperature sensor, and actuator control board. The ZD zone damper can be used as part of the Z-1600 Comfort
System™, or as a stand-alone control damper.
AVAILABLE SIZES:
Diameters:
Length:
6”, 8”, 10”, 12”, 14”, 16”, 18”, 20”
6” - 10” diameter =
10”
12” diameter =
13”
14” - 20” =
14”
CONSTRUCTION:
Shell Material:
Damper Material:
Shaft:
18 gauge spiral steel
18 gauge
½”aluminum
AIR FLOW & PRESSURE:
Max static pressure:
Max velocity:
CFM:
2 inches w.c.
2,000 fpm
0 - 4,000 cfm
WARRANTY:
Damper:
5 Years
Zone Control Made Simple™
5418 Elmwood Avenue, Indianapolis, IN 46203-6025
Toll Free: 888.652.9663 Fax: 317.227.1034
www.jacksonsystems.com
08-1003-122206
Z-1600 COMFORT SYSTEM™
VAV DIFFUSER SPECIFICATIONS
APPLICATION:
The Model VAV Comfort System™ Diffuser is used to vary the supply air volume from a wall-mounted thermostat. The
diffuser is designed to maintain the coanda effect (draft free) of discharge air along the ceiling, providing a sustained
discharge velocity throughout the volume range. The Comfort System™ VAV Diffuser can be used as part of the Z-1600
Comfort System™ or with the Z-1600-T wall-mounted thermostat that enables the user to choose their own desired
comfort level.
AVAILABLE SIZES:
Face Size:
Neck Size:
12” X 12”
24” X 24”
6”, 8” for 12” x 12” face size
6”, 8”, 10”, 12”, 14” for 24” x 24” face size
CONSTRUCTION:
Face Plate:
Back Cone:
Removable 18 gauge steel with baked white enamel finish
Unitary stamped 18 gauge steel
OPERATION:
Diffuser:
Integral modulating disk that continually regulates supply air volume
in response to thermostat control
Air Volume Range:
118 to 710 CFM
DIFFUSER ACTUATOR OPTIONS:
24 VAC, 3VA , 3-wire floating point actuator (standard)
Pneumatic actuator
Lon Works compatible
Custom mounting for BAS controls
Manually adjustable volume controller
AIR HANDLER CONTROL OPTIONS:
Master thermostat
Standard VAV controller (55º F discharge air)
Changeover VAV controller (heating & cooling VAV)
Zone Control Made Simple™
5418 Elmwood Avenue, Indianapolis, IN 46203-6025
Toll Free: 888.652.9663 Fax: 317.227.1034
www.jacksonsystems.com
08-1006-122206
Z-1600 COMFORT SYSTEM™
SPECIFICATION SUGGESTIONS
1.01
ZONE CONTROL SYSTEMS
A.
1.02
General. Provide a Z-1600 Comfort System™ zone control system manufactured by
Jackson Systems to meet the performance as specified in this section. Each zone
control system shall meet the following requirements.
1.
The zone control system shall be composed of one logic panel, up to 16 zone
dampers with actuators, zone thermostats, and bypass damper(s).
2.
The zone control system shall be capable of controlling up to 16 zones and
must use proprietary fully modulating thermostats.
3,
The system shall have auto changeover and be capable of controlling two
stages of heat and two stages of cooling. The system shall also be
compatible with heat pump systems.
4.
The zone control system shall not require any field programming. A
laptop computer or service tool shall not be required for setup and
troubleshooting.
B.
Environment. The zone control panel shall be suitable for the indoor ambient
conditions and shall be rated for operation between 32°F and 120° F.
C.
Serviceability. Provide diagnostic LEDs for heating stages, cooling stages, fan,
and the heating or cooling request of each zone.
D.
No battery back-up. The zone control system shall not require a battery back-up.
E.
Power and Immunity to noise. The zone control system shall be able to operate
between 90% and 110% of nominal voltage rating and shall not be affected by
radio frequency interference (RFI).
ZONE DAMPERS
A.
Zone dampers shall be round, rectangular or VAV diffuser type. Round dampers
shall have a diameter of 6 inch to 36 inch. Rectangular dampers shall have a
minimum size of 8 inch by 8 inch. VAV diffusers shall have an inlet size of
6 inch to 14 inch.
1. Frames. 18 gauge (minimum) galvanized steel.
2. Blades. 18 gauge (minimum) galvanized steel.
3. Bearings. Oil impregnated sintered iron bushings.
Zone Control Made Simple™
5418 Elmwood Avenue, Indianapolis, IN 46203-6025
Toll Free: 888.652.9663 Fax: 317.227.1034
www.jacksonsystems.com
08-1004-122206
Z-1600 COMFORT SYSTEM™
SPECIFICATION SUGGESTIONS
1.03
Seals for Round Dampers. EDPM seal installed on inside of round damper
shell. Leakage shall be less than 2% at 3 inches of static pressure.
5.
Dampers shall be Jackson Systems ZD-XX, ZD-XXXX or approved equal.
6.
VAV Diffusers shall be Jackson Systems VD-XX or approved equal.
7.
All zone dampers to have minimum position adjustments.
ELECTRIC DAMPER ACTUATORS AND ACTUATOR CONTROL BOARDS
A.
B.
1.04
4.
Modulating and two position damper actuators. All zone damper actuators shall
have sufficient reserve power to provide smooth action as specified.
1.
Damper actuators shall be capable of turning clockwise or counterclockwise
and be powered by a reversible motor which is connected to the output shaft.
2.
All actuators shall be factory wired to the damper control board.
3.
All damper actuators shall be mounted outside of the air stream.
The damper actuator control board shall provide wiring terminals for all field and
factory wiring. The damper actuator board will also provide an output for
auxiliary zone heat.
1.
Factory Wiring. Damper actuator and duct sensor.
2.
Field Wiring. Zone thermostat, 24 VAC power, wiring to system panel, and
optional auxiliary heat.
BYPASS DAMPERS
A.
Bypass damper(s) shall be provided to maintain the proper duct static pressure.
1.
The bypass damper(s) shall be round or rectangular.
2.
Systems under 0.75” w.c. of static pressure shall use a barometric
bypass damper.
3.
Systems 0.75” w.c. and over of static pressure shall use an electronic
bypass damper with static pressure controller.
4.
The bypass damper(s) shall be sized for 90% of the total air flow at
2500 FPM.
Zone Control Made Simple™
5418 Elmwood Avenue, Indianapolis, IN 46203-6025
Toll Free: 888.652.9663 Fax: 317.227.1034
www.jacksonsystems.com
08-1007-122206
Z-1600 COMFORT SYSTEM™
SPECIFICATION SUGGESTIONS
1.05
WIRING
A.
1.06
Control Wiring.
1.
All control wiring shall be 24 Volts or less.
2.
All control wiring shall be standard or plenum-rated thermostat wire.
18 gauge minimum. No shielded cable shall be required.
3.
Control wire and cable shall be installed in accordance with NEC.
SERVICE AND GUARANTEE
A.
General. The entire zone control system shall be warranted for a period of five (5)
years from date of installation. This includes the components only and does not
include labor of any kind.
Zone Control Made Simple™
5418 Elmwood Avenue, Indianapolis, IN 46203-6025
Toll Free: 888.652.9663 Fax: 317.227.1034
www.jacksonsystems.com