QUICK INSTALLATION
QUICK INSTALLATION Art Top 450
Presentation
This manual describes in detail how to make the connections and settings in relation to the functions you want to enable.
Key to abbreviations
TA
room thermostat
TC
water temperature read by the probe in the boiler
T_pompa
temperature setting pump
T_caldaia
boiler temperature setting
T_ev
solenoid temperature setting
T AG
frost thermostat
T IS
safety thermostat
T EM
thermostat emergency
OUT_POMPA
pump output
OUT_ fan
output fan
OUT_ cochlea
Release auger
X
indifferent, whatever the state does not affect the final result
Legend alarms
ASA
Water sensor alarm
you receive the written notice ASA + sound;
ASR
Return water sensor alarm
you receive the written ASR + beep (if enabled);
Temperature Alarm Security
TSI reached, activates the pump even if the TA is open;
TEM reached you view the All written alternating the water temperature + beep;
ACT
Alarm à activities (accidental shutdown)
you receive the written Act and everything stops, turn off and on to restart the
unit
TAG
Antifreeze
activates the circulator at a temperature below 4 ° C
S_P
Sensor pellet
Programs
There are 3 main programs of operation to be selected in Parameter 6 BP6 Tour
a.
b.
BP6 PRG 0 program provides the mode of operation à Wood and Pellet.
BP6 PRG 1 Program 1 includes the operating mode à Wood and Pellet and Automatic without using spark
ignition or hair dryer.
c.
BP6 PRG 2
Program 2 provides for the mode of operation à Wood and Pellet and Automatic with spark
ignition or hair dryer.
PRG BP6 0 Program
You select the mode of operation using the MODE button, it displays the LEG written for Pel and wood pellet fuel, or any other
trite.
Mode Wood
the controller behaves as a simple control unit for activating only the circulator fireplace at the set temperature
You can turn the fan enabling it hanging in the FLE in BP1 .
With the fan enabled the circulator is controlled only by the temperature of the water, also by the room thermostat. The fan
remains on until the boiler temperature is reached provided that the TA is closed.
In mode 0 fle wood with BP1 you can have it spit out, see the section on for more details.
Pag. 1
QUICK INSTALLATION
TABLE 1
Row N.
condition
TA
Out_pompa
Condition 2
Out_ventola
1
BP1 fle 0
TC> = T_pompa
x
1
0
2
BP1 fle 0
TC <T_pompa
x
0
0
3
BP1 fle 1
TC> = T_pompa
1
1
TC> = T_caldaia
0
4
BP1 fle 1
TC <T_pompa
1
0
TC <T_caldaia
1
5
BP1 fle 1
TC> = T_pompa
0
0
TC> = T_caldaia
0
6
BP1 fle 1
TC <T_pompa
0
0
TC <T_caldaia
0
Mode Pellets
In pellet mode activates the outputs of the fan and auger. They are subject to the temperature of water by the thermostat
T_caldaia and ambient temperature by contact TA
TABLE 2
n.riga
condition
TA
Out_pompa
Condition 2
Out_ventola
Out_coclea
1
TC> = T_pompa
1
1
TC> = T_caldaia
0
0
2
TC <T_pompa
1
0
TC <T_caldaia
1
1
3
TC> = T_pompa
0
0
TC> = T_caldaia
0
0
4
TC <T_pompa
0
0
TC <T_caldaia
0
0
Ventilation
The regulation of ventilation occurs through the ventilation knob, the fan is connected to terminal FAN and parameters is defined
ventola1. The adjustment range is from 0, the fan stops at 50, the fan at 100%, to tighten the adjustment range should be adjusted
to limit the maxi and min accessing hangings BP3 F1h and BP3 F1L.
Enabling ventola2
You can use the output OUT5 to control a second fan, to enable this feature you must set the parameter
BP1 OU5 to 10. The adjustment range can be determined by acting on the parameters BP3 F2H and BP3 F2L.
To change the ventilation to ventola2 ventilation must turn the knob until you get the beep beep of the unit and within one second
press the MODE button, at this point appears for a moment before the written VE2 and then the adjustment value. If during the
adjustment you repeatedly press the mode button you have the continuous passage from VE2 to Ve1 and vice versa.
Power supply (auger)
The controller allows you to control the flow of fuel through direct implementation with single-phase motor with an inverter for
220 volts or 220 volts three-phase motor driver. In the first case the engine is operated in a cyclic manner by altering the timing of
work and rest, then we talk about the drive pulse / pause. In the second case the motor runs continuously but at variable
speed. The description of the hanging BP1 OU3 auger drive down the rules:
TABLE 3
BP1 OU3 0
Release auger control inverter output terminal OUT3 used as the source for the inverter
BP1 OU3 1
output relay screw on the knob adjusts the break working time is determined by the parameter
BP1 OU3 2
output relay screw on the knob adjusts the work the pause time is set by the parameter
BP4 TCO
BP4 TCO
Pag. 2
QUICK INSTALLATION
NB. For a better understanding please refer also to the section connections.
In pellet operation are also active integrated functions for dynamic cleaning of the brazier, coals regeneration, and control
activities for the detection of failure or accidental shutdown. Refer to the sections dedicated for more details.
Pellet Sensor
If the sensor input pellet is open, meaning that the fuel is exhausted, you do not have the option of switching from wood and the
other shows the message S_P. If you are working to end the fuel pellets and appears the word no alternating pel and everything
stops until it is done refueling.
Rotisserie function
In order to have output "Rotisserie" you must set the output OUT4 or OUT5 to a value of BP1 OU4 8 or BP1 OU5 8 . Moreover,
there should be excluded the operation of the fan during the burning mode BP1 FLE 0.Turning on or off with the pressing the
MODE button for 1 second;
Clean Dynamics
when the boiler is in operation for some time, some ash deposits can affect the combustion by reducing the yield, and then
periodically gets activate the fan for a few seconds at high power to remove or at least reduce these deposits in the brazier. Some
parameters related to dynamic cleaning are described below:
TABLE 4
BP1 OU4 1
Activation of output OUT 4 during dynamic cleaning
BP1 OU5 1
BP4 ipd
Activation OUT 5 during dynamic cleaning
BP4 dpd
cleaning cycles duration in seconds
BP5 F1P
1 power fan during cleaning dynamics
Interval between cleaning cycles in minutes
2 Power fan during cleaning dynamics
BP5 F2P
Regeneration embers
is enabled when the boiler stops because it has reached the set temperature by the boiler thermostat or why not stop by open
surgery TA (thermostat). Remain idle for many minutes I can turn off the coals, so to prevent this from happening you leave at
regular intervals for a set time, the cochlea, and possibly the fan, adding new fuel in the grate. Some parameters related to the
regeneration coals are described below:
TABLE 5
BP4 irb
Range regeneration embers, each unit is set to 30 minutes
BP4 trb
Cyclical life or regeneration embers in seconds
BP5 F1R
1 fan power during regeneration embers
BP5 F2R
2 fan power during regeneration embers
Inverter regulation during regeneration embers
BP5 inr
BP6 program PRG 1
You select the mode of operation using the MODE button, it displays the LEG written for wood, pellet Pel or any other
fuel aut chopped and combined modality for wood / pellet.
We omit the descriptions for the methods and wood pellets as previously described.
Are presented in this section concerning the management capabilities combined wood / pellet defined as the Auto mode.
AUT mode "no spark"
Following the selection of the control mode, Auto mode performs the wood until detects the presence of fire,
then when the wood runs out there is a change to automatic mode pellet in a definitive manner, so that a subsequent
wood loading, you must manually reset the AUT mode.
How is the recognition of the presence of fire in the logic of the unit there is a timer that resets always active whenever the
temperature rises one degree, until there is fire temperature increases and decreases depending on the status of the pump and
amount of wood present, when the fuel runs out, the timer is not reset and move forward until you reach the
parameter BP6 PAP, this condition starts automatically switch to pellets.
Pag. 3
QUICK INSTALLATION
BP6 program PRG 2
You select the mode of operation using the MODE button, it displays the LEG written for wood, pellet Pel or any other
fuel aut chopped and combined modality for wood / pellet.
We omit the descriptions for the methods and wood pellets as previously described.
Are presented in this section concerning the management capabilities combined wood / pellet defined as the Auto mode with
automatic ignition and burning of the pellets.
AUT mode "with electric igniter"
The description of this method is described schematically for ease of understanding:
a.
Check water temperature to determine the presence fire in the boiler (continuous assessment of the time BP6
PAP, for more details see the section: How is the recognition of the presence of fire in the description of the program 1)
a1) fire is not detected is running b);
a2) fire detected is running c);
b.
Turn on ignition of the pellet through the glow plug to serve as a trigger to 'ignition of wood,
detected the ignition performs c);
c.
d.
e.
Performs mode until it is burning à detects the presence of fire, then when the wood runs out to switches)
Switching to operating mode à pellet with activating the glow plug handled automatically;
The operating status of the final pellet is why a subsequent loading of wood must be reset to AUT;
How is the 'spark ignition of the pellet by: power-management come into play several parameters to adjust the timing of the
various stages leading power of the chopped material (pellets);
1.
the mode selection à AUT activates the 'dedicated output function plug (BP1 OU4 6 or BP1 OU5 6) for the time
set by parameter BP 6 tpr preheating time expressed in seconds, the stage door the display of the written PRE;
2.
after the preheating time you start the phase of the ignition where the electrode is maintained, and the
cochlea mantien times or speed dial à established by the Food, ventilation is established by BP vestments 6 fa1 1 for the
fan and BP 6 Fa2 for the fan 2. Duration of the ignition phase is determined by the parameter BP 6 TAC expressed in
minutes.
During this phase, the display reads ACC.
3.
spent the time you start the ignition phase of the stabilization where the glow plug is switched off, the auger
keeps timing or speed dial à established by the Food, ventilation is established by BP vestments 6 fa1 1 for the fan andBP
6 Fa2 for the fan 2. Duration of the ignition phase is determined by the parameter BP 6 TST in minutes.
During this phase is kept displaying the written ACC.
4.
after the stabilization time of the glow plug is switched off and the burning continues as normal mode à pellets.
Ancillary Functions
Output alarm signal
You can have external signaling of the alarm status of the control unit enabling the output out4 or out5 for this purpose by setting
the parameters BP1 OU4 0 or BP1 OU5 0.
Output loader
The output loader allows to start a secondary auger for filling the hopper whenever the sensor detects exhaustion of the fuel
pellet. After the exit loader is active, it remains in this state for the time set by hanging BP4 TL0, each unit corresponds to a set
time of 10 seconds. You can enable output out4 or out5 to do this by setting the parameters BP1 OU4 6 or BP1 OU5 6.
Input / output water level sensor
Some systems require automatic boiler filling by level sensor that activates a solenoid valve accordingly to 220 volts, you can enable
this function outputs out4 or out5, enabling parameters BP1 OU4 9 orBP1 OU5 9.
Enabling this function involves the use of a water level sensor (sensor specifications to be agreed, no product in the catalog) to be
connected to the input terminals COM and S3.
Pag. 4
QUICK INSTALLATION
Functions related to the thermostat
The input terminal of the thermostat TA has the main task of controlling the pump function of the temperature of the air in homes
and water temperature in the boiler. This function may be associated with other related to the management of the state of activity
of the boiler, the following table describes these functions and their vestments control:
TABLE 6
No additional feature enabled the TA
With TA open the boiler works in relation to the temperature set by the
hanging Bp2 He
With TA open the boiler door stop
2 fan power during regeneration embers
Ta opened the boiler goes to sleep when the water temperature reaches the value
+ Is only available if T_pompa Bp2 cta = 1
Bp2 cta 0
Bp2 cta 1
Bp2 cta 2
He bp2
NOTE: Setting this parameter to 1 cta you have the possibility to maintain the boiler to a temperature which allows an immediate
start of the circulator in the moment of closure of the TA with a considerable saving of fuel due to the lower heat losses produced
in maintaining the water in the boiler at a lower temperature.
Parameter Programming
To facilitate access to the desired parameter map data has been divided into 6 groups, each group
define the parameters BP1 bench. . 6 in each bank are interested in selecting the parameter by means of written identification,
eg.: VTE is for setting Thermostat T And V lettro good tube.
CAUTION: The procedure to follow to access the programming is intended for technical personnel.
1.
2.
3.
4.
5.
6.
Power cycle the unit;
in the first 5 seconds, press the mode button 5 times;
followed by 3 beeps, the written PAR for 1 second and then BP1;
At this point the pump by turning the knob you can choose ò BP1 to BP6;
s tabilito the counter parameters to which you want to access, press the mode button;
at this point, always with the rotary pump you select the parameter itself and with the knob boiler setting
value;
7.
8.
to change a parameter in a different bank must return to step 4) by pressing the power button;
to store the data as soon as the impostat it takes about ten seconds, and the momentary appearance of the
writing end.
Map parameters
TABLE 1 PARAMETERS
CONFIGURATIONS
parameter
Minimum
Maximum
code
limit
limit
ID_
0
1
option
default
0
0
1
PRE
0
1
0
unit
function
Details
0 = master
core identity
1 = slave
0
1
0 = TA and TIMER_PROG UNIT
ENABLE REMOTE CONNECTION
1 = TA and TIMER_PROG PANEL
out PWM control enables and activates the
ou3
0
2
0
1
Release auger control inverter
mini relay, the relay out3 fixed for inverter
Power Management
1
2
output relay screw on the knob adjusts
the break
output relay screw on the knob adjusts
the time on
direct output relay screw
direct output relay screw
Pag. 5
QUICK INSTALLATION
OU4
0
9
0
2
function in alarm
1
function in dynamic cleaning
function with state thermostat
2
circulator on
function and output enable
3
recirculation
with thermostat valve function was on
4
"tev"
5
0
ou5
10
function with fan on
6
output spark
7
function loader
8
outlet grill
9
water level sensor input on S3
0
10
function in dynamic cleaning
function with state thermostat
2
circulator on
function and output enable
3
recirculation
with thermostat valve function was on
4
"tev"
5
0
0
function in alarm
1
Fle
only wood-burning mode without spark prg =
function with fan on
6
output spark
7
function loader
8
outlet grill
9
water level sensor input on S3
10
output fan 2
1
0
Fan operating a wood 0 = no 1 = yes
only wood with fle 0
If Fle = 1 WOOD and opens the TA, it also
stops the pump
TEMPERATURES
TABLE 2 PARAMETERS
parameter
Minimum
Maximum
code
limit
limit
and v
30
tsi
70
tall
70
dev
dci
option
default
unit
function
80
50
°C
temperature thermostat valve surgery
100
85
°C
active outputs for safety
Delta intervention to 2 degrees
100
95
°C
active alarm state
Delta intervention to 2 degrees
1
40
2
°C
Delta IV thermostat
1
40
2
°C
delta thermostat circulator
dca
1
40
2
°C
CTA
0
2
1
no control, boiler operates only in
relation to the boiler thermostat
TA open the boiler works in relation to
1
the following parameter STA
2
1
10
delta boiler thermostat
boiler control to open TA
0
is
Details
TA to open the boiler is always in stop
2
°C
stop boiler thermostat open temp =
STA + pump
only available if CTA = 1
Pag. 6
QUICK INSTALLATION
dri
1
10
2
°C
differential recirculation
tri
30
60
35
°C
temperature recirculation intervention
default
unit
function
TABLE 3 PARAMETERS
SETTING LIMITS
parameter
Minimum
Maximum
code
limit
limit
cih
30
90
70
°C
limit circulator high
option
cil
30
90
40
°C
low limit circulator
cah
30
90
80
°C
boiler high limit
°C
cal
30
90
50
F1H
0
50
50
boiler low limit
upper limit ventola1
F1L
0
50
0
lower limit ventola1
F2H
0
50
50
upper limit ventola2
F2L
0
50
0
lower limit ventola2
coh
0
200
60
sec
high limit screw
with
0
200
0
sec
low limit screw
inh
0
50
50
%
limit inverter high
inl
0
50
0
%
lower limit inverter
default
unit
function
3
sec
break or work time in seconds
TIMING
TABLE 4 PARAMETERS
parameter
Minimum
Maximum
code
limit
limit
tco
0
250
1 = 30
irb
minutes
1
trb
option
20 = 10 hours
3
60
15
Tsa
0
60
val *
30min
sec
30
min
if the time set with circ off the temperature
control 0 = not enabled
increases, the block operates
60
5
min
cleaning interval dynamics
0
60
10
sec
Dynamic cleaning duration 0 = no PD
TLO
1
250
6
10 sec
output enable time loader 6 * 10 = 60 =
*
one minute
ral
5
250
30
sec
Alarm activation delay
default
unit
function
0
%
ventola1in power stand-by
Maximum
limit
F1s
0
50
option
F2s
0
50
0
&
ventola2in power stand-by
F1R
0
50
3
%
ventola1 coals in power regeneration
F2R
0
50
3
%
ventola2 coals in power regeneration
inr
0
50
50
%
setting inverter regeneration embers
F1P
0
50
50
%
ventola1 power in PD
F2P
0
50
50
%
ventola2 power in PD
unit
function
TABLE 6 PARAMETERS
parameter
Minimum
Maximum
code
limit
limit
establishes an appropriate time to replenish
the hopper of the boiler through feed screw
secondary
POWERS
TABLE 5 PARAMETERS
limit
OU3 = 2
regeneration time embers
1
Minimum
controls the work if OU3 = 1 break if check it
time control accidental switching
ipd
code
Details
regeneration interval embers
dpd
parameter
Details
Details
For standby means the state of boiler
temperature is reached and then the operator
is stopped, except regeneration cycles embers
AUTOMATIC SWITCH
option
default
Details
Pag. 7
QUICK INSTALLATION
PRG
0
2
0 = Standard 1 = 2 lp = lp with spark
0
plug
PAP
1
60
15
min
automatic switching to pellet
tpr
10
240
120
sec
Time preheating
tac
1
30
5
min
Time ignition
tst
0
30
5
min
Time stabilization
FA1
0
50
20
%
Fan 1 power phase switching
FA2
2
50
20
%
fan power 2-phase power
Further descriptions in note 1
the fan 2 only if enabled
Wiring Diagram
SENSOR COMB. IF
YOU DO NOT USE
THE SENSOR
BRIDGE BETWEEN
0V AND IN4
coelte PELLET SENSOR
1 BROWN +12VOLT
2 BLUE
MASSA
3 BLACK
OUTPUT
SONDA ACQUA
TIME
PROGRAMMER if
you are not using
the bridge to put
FLOW na
If not used, leave
unplugged
THERMOSTAT If
you are not using
the bridge to put
1
2
3
4
5
RELE SU ZOCCOLO
UPPER
CIRCUIT
SEEN FROM
BELOW
ANNOTATION
1 Black 2 White 3 Red 4 Yellow 5 Green -
0Volt potentiometer
setting 0-5 (10) volt
5 (10) volt potentiometer
contact na run
run common contact
INVERTER
RUN
CONTROL
0/10 VOLT
Configurable triac output, (SEE TABLE BENCH
parameters OU5 1) CAN 'BE LEFT OPEN
Configurable output relay (SEE TABLE BENCH
parameters OU4 1) CAN 'BE LEFT OPEN
MAINS 220 VOLT
THERMOSTAT OR OTHER EMERGENCY
SAFETY DEVICE NC
COCLEE OUTPUT 8 AMPERE MAX OR
POWER INVERTER
FAN
SOLENOID
HEATING
PUMP
Pag. 8