BPS 307i
EN 2018/01 - 50127000
We reserve the right to
make technical changes
Bar Code Positioning System
Original operating instructions
© 2018
Leuze electronic GmbH + Co. KG
In der Braike 1
D-73277 Owen / Germany
Phone: +49 7021 573-0
Fax: +49 7021 573-199
http://www.leuze.com
info@leuze.de
Leuze electronic
BPS 307i
2
1
About this document . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
1.1
2
3
Used symbols and signal words . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Safety . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
2.1
Intended use . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
2.2
Foreseeable misuse . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
2.3
Competent persons . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
2.4
Exemption of liability . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
2.5
Laser warning notices . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Device description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
3.1
3.1.1
3.1.2
3.1.3
3.1.4
Device overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
General information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Performance characteristics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Device model with heating. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
12
12
13
13
13
3.2
3.2.1
3.2.2
3.2.3
Connection technology . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
MS 307 connection hood with M12 connectors. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
MK 307 connection hood with spring-cage terminals . . . . . . . . . . . . . . . . . . . . . . . . . . . .
KB 307 connection hood with cable . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
14
14
14
15
3.3 Display elements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
3.3.1 LED indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
3.3.2 Display indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
3.4
3.4.1
3.4.2
3.4.3
3.4.4
4
6
Leuze electronic
19
19
21
24
25
Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
4.1
5
Bar code tape . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
General information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Control bar codes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Marker labels . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Twin tapes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Position measurement. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
4.2
Speed measurement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
4.3
Timing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
4.4
Leuze webConfig tool . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
4.5
Evaluation of the reading quality . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
4.6
Distance measurement to the bar code tape. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Applications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
5.1
High-bay storage device . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
5.2
Telpher line . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
5.3
Gantry cranes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
Mounting and installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
6.1
6.1.1
6.1.2
6.1.3
Mounting bar code tape. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Installation and application remarks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Cutting bar code tapes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Mounting the BCB . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
33
33
34
35
6.2
6.2.1
6.2.2
6.2.3
6.2.4
6.2.5
6.2.6
Bar code positioning system . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Mounting instructions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Orientation of the BPS to the bar code tape . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Mounting with the BTU 0300M-W mounting device . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Mounting with the BT 300 W mounting bracket. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Mounting with BT 56 mounting device. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Mounting with BT 300-1 mounting device . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
38
39
40
40
41
41
42
BPS 307i
3
6.2.7 Mounting with M4 fastening screws. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
7
8
Electrical connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
7.1
External parameter memory in the connection hood. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
7.2
7.3
MS 307 connection hood with connectors. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
MK 307 connection hood with spring-cage terminals . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
7.4
KB 307 connection hood with cable . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
7.5
7.5.1
7.5.2
7.5.3
7.5.4
Pin assignment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
PWR / SW IN/OUT (Power and switching input/output) . . . . . . . . . . . . . . . . . . . . . . . . . .
SSI (HOST / BUS IN) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
SSI connection cable KB 307 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Service USB . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
7.6
Cable lengths and shielding . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
46
46
47
48
49
Basic configuration. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
8.1 Configuring the SSI interface. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
8.1.1 Principal functionality of the SSI interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
8.1.2 Setting the configuration of the SSI interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
9
8.2
Configuring the switching inputs/outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
8.3
Configuring the resolution for the position value . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
8.4
Configuring speed monitoring with switching output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
8.5
Setting tape selection via the webConfig tool . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
8.6
Configuration via the switches of the connection hood . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
8.7
Setting configuration parameters to factory settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56
8.8
Key factory settings of the BPS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
Leuze electronic webConfig tool – Extended configuration . . . . . . . . . . . . . . . . 58
9.1 Installing software . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
9.1.1 System requirements. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
9.1.2 Install USB driver. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
10
9.2
Start webConfig tool . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59
9.3
9.3.1
9.3.2
9.3.3
9.3.4
9.3.5
9.3.6
Short description of the webConfig tool. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
CONFIGURATION function. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
ALIGNMENT function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
PROCESS function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
DIAGNOSTICS function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
MAINTENANCE function. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
60
60
61
67
68
69
70
Diagnostics and troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71
10.1 What to do in case of failure? . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71
10.1.1Diagnostics with webConfig tool . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71
10.2 Operating indicators of the LEDs. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71
10.3 Error messages on the display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72
10.4 Checklist for causes of errors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72
11
Care, maintenance and disposal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 74
11.1 Cleaning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 74
11.2 Servicing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 74
11.2.1Firmware update . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 74
11.2.2BCB repair with repair kit. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 74
11.3 Disposing. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75
Leuze electronic
BPS 307i
4
12
Service and support . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 76
12.1 What to do should servicing be required? . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 76
13
Technical data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
13.1 General specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
13.1.1BPS without heating . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79
13.1.2BPS with heating . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79
13.2 Bar code tape . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 80
13.3 Dimensioned drawings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 82
13.4 Dimensioned drawings: Accessories. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 84
13.5 Dimensioned drawing bar code tape . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 88
14
Order guide and accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 89
14.1 BPS 307i type overview. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 89
14.2 Connection hoods . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 89
14.3 Cables accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 89
14.4 Other accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 89
14.5 Bar code tapes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 90
15
EC Declaration of Conformity. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 93
16
Appendix . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 94
16.1 BCB bar code tape with 40 mm grid . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 94
16.2 Bar code tape BCB8 with 30 mm grid . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 95
Leuze electronic
BPS 307i
5
About this document
1
About this document
1.1
Used symbols and signal words
Table 1.1:
Warning symbols and signal words
Symbol indicating dangers to persons
Symbol indicating dangers from harmful laser radiation
NOTE
Signal word for property damage
Indicates dangers that may result in property damage if the measures for
danger avoidance are not followed.
Table 1.2:
Other symbols
Symbol for tips
Text passages with this symbol provide you with further information.

Table 1.3:
Symbol for action steps
Text passages with this symbol instruct you to perform actions.
Terms and abbreviations
BCB
Bar code tape (general or specific BCB type with 40 mm grid)
BCB8
Bar code tape (BCB type with 30 mm grid)
BPS
Bar code Positioning System
CFR
Code of Federal Regulations
DAP
Device Access Point
DCP
Discovery and Configuration Protocol
EMC
Electromagnetic compatibility
EN
European standard
FE
Functional earth
GSD
General Station Description
GSDML
Generic Station Description Markup Language
GUI
Graphical User Interface
IO or I/O
Input/Output
I&M
Information & Maintenance
IP
Internet Protocol
LED
Light Emitting Diode
MAC
Media Access Control
MVS
Type of control bar code
MV0
Type of control bar code
Leuze electronic
BPS 307i
6
About this document
NEC
National Electric Code
OSI
Open Systems Interconnection model
PELV
Protective Extra-Low Voltage
RT
Real Time
SNMP
Simple Network Management Protocol
PLC
Programmable Logic Control
Programmable Logic Control
SSI
Synchronous Serial Interface
(Digital Synchronous Serial Interface)
TCP
Transmission Control Protocol
UDP
User Datagram Protocol
USB
Universal Serial Bus
UL
Underwriters Laboratories
UV
Ultraviolet
XML
Extensible Markup Language
Leuze electronic
BPS 307i
7
Safety
2
Safety
This sensor was developed, manufactured and tested in line with the applicable safety standards. It corresponds to the state of the art.
2.1
Intended use
The device is an optical measuring system which uses visible red laser light to determine its position relative to a permanently mounted bar code tape.
All accuracy details for the BPS 300 measurement system refer to the position relative to the permanently
mounted bar code tape.
Areas of application
The BPS is designed for positioning in the following areas of application:
• Telpher line
• Travel and lifting axes of high-bay storage devices
• Repositioning units
• Gantry crane bridges and their trolleys
• Elevators
CAUTION
Observe intended use!
 Only operate the device in accordance with its intended use.
The protection of personnel and the device cannot be guaranteed if the device is operated in a manner
not complying with its intended use.
Leuze electronic GmbH + Co. KG is not liable for damages caused by improper use.
 Read the operating instructions before commissioning the device.
Knowledge of the operating instructions is an element of proper use.
NOTICE
Comply with conditions and regulations!
 Observe the locally applicable legal regulations and the rules of the employer's liability insurance association.
2.2
Foreseeable misuse
Any use other than that defined under “Intended use” or which goes beyond that use is considered
improper use.
In particular, use of the device is not permitted in the following cases:
• in rooms with explosive atmospheres
• for medical purposes
• as own safety component in accordance with the machinery directive
Use as safety-related component within the safety function is possible, if the component combination is designed correspondingly by the machine manufacturer.
NOTICE
Do not modify or otherwise interfere with the device!
 Do not carry out modifications or otherwise interfere with the device.
The device must not be tampered with and must not be changed in any way.
The device must not be opened. There are no user-serviceable parts inside.
Repairs must only be performed by Leuze electronic GmbH + Co. KG.
Leuze electronic
BPS 307i
8
Safety
2.3
Competent persons
Connection, mounting, commissioning and adjustment of the device must only be carried out by competent
persons.
Prerequisites for competent persons:
• They have a suitable technical education.
• They are familiar with the rules and regulations for occupational safety and safety at work.
• They are familiar with the original operating instructions of the device.
• They have been instructed by the responsible person on the mounting and operation of the device.
Certified electricians
Electrical work must be carried out by a certified electrician.
Due to their technical training, knowledge and experience as well as their familiarity with relevant standards and regulations, certified electricians are able to perform work on electrical systems and independently detect possible dangers.
In Germany, certified electricians must fulfill the requirements of accident-prevention regulations DGUV
(German Social Accident Insurance) provision 3 (e.g. electrician foreman). In other countries, there are
respective regulations that must be observed.
2.4
Exemption of liability
Leuze electronic GmbH + Co. KG is not liable in the following cases:
• The device is not being used properly.
• Reasonably foreseeable misuse is not taken into account.
• Mounting and electrical connection are not properly performed.
• Changes (e.g., constructional) are made to the device.
2.5
Laser warning notices
ATTENTION, LASER RADIATION – LASERCLASS2
Never look directly into the beam!
The device satisfies the requirements of IEC 60825-1:2007 (EN 60825-1:2007) safety regulations for a
product of laser class 2 as well as the U.S. 21 CFR 1040.10 regulations with deviations corresponding
to “Laser Notice No. 50” from June 24, 2007.
 Never look directly into the laser beam or in the direction of reflected laser beams!
If you look into the beam path over a longer time period, there is a risk of injury to the retina.
 Do not point the laser beam of the device at persons!
 Interrupt the laser beam using a non-transparent, non-reflective object if the laser beam is accidentally
directed towards a person.
 When mounting and aligning the device, avoid reflections of the laser beam off reflective surfaces!
 CAUTION! The use of operating or adjusting devices other than those specified here or carrying out
of differing procedures may lead to dangerous exposure to radiation.
 Observe the applicable statutory and local laser protection regulations.
 The device must not be tampered with and must not be changed in any way.
There are no user-serviceable parts inside the device.
Repairs must only be performed by Leuze electronic GmbH + Co. KG.
Leuze electronic
BPS 307i
9
Safety
NOTICE
Affix laser information and warning signs!
Laser information and warning signs attached to the device (see figure 2.1). Also included with the device
are self-adhesive laser warning and laser information signs (stick-on labels) in multiple languages (see
figure 2.2).
 Affix the laser information sheet to the device in the language appropriate for the place of use.
When using the device in the U.S.A., use the stick-on label with the “Complies with 21 CFR 1040.10”
notice.
 Affix the laser information and warning signs near the device if no signs are attached to the device (e.g.
because the device is too small) or if the attached laser information and warning signs are concealed
due to the installation position.
Affix the laser information and warning signs so that they are legible without exposing the reader to the
laser radiation of the device or other optical radiation.
1
2
3
1
2
3
Figure 2.1:
Leuze electronic
Laser aperture
Laser warning sign
Laser information sign with laser parameters
Laser aperture, laser warning and information signs
BPS 307i
10
Safety
50120562-02
Figure 2.2:
Leuze electronic
LASERSTRAHLUNG
NICHT IN DEN STRAHL BLICKEN
Max. Leistung (peak):
1,8 mW
Impulsdauer:
<150 µs
Wellenlänge:
655 nm
LASER KLASSE 2
DIN EN 60825-1:2008-05
RADIAZIONE LASER
NON FISSARE IL FASCIO
Potenza max. (peak):
1,8 mW
Durata dell'impulso:
<150 µs
Lunghezza d'onda:
655 nm
APARRECCHIO LASER DI CLASSE 2
EN 60825-1:2007
LASER RADIATION
DO NOT STARE INTO BEAM
Maximum Output (peak):
1.8 mW
Pulse duration:
<150 µs
Wavelength:
655 nm
CLASS 2 LASER PRODUCT
EN 60825-1:2007
RAYONNEMENT LASER
NE PAS REGARDER DANS LE FAISCEAU
1,8 mW
Puissance max. (crête):
Durée d`impulsion:
<150 µs
655 nm
Longueur d`onde:
APPAREIL À LASER DE CLASSE 2
EN 60825-1:2007
AVOID EXPOSURE – LASER RADIATION
IS EMITTED FROM THIS APERTURE
EXPOSITION DANGEREUSE – UN RAYONNEMENT
LASER EST ÉMIS PAR CETTE OUVERTURE
RADIACIÓN LÁSER
NO MIRAR FIJAMENTE AL HAZ
1,8 mW
Potencia máx. (peak):
<150 µs
Duración del impulso:
655 nm
Longitud de onda:
PRODUCTO LÁSER DE CLASE 2
EN 60825-1:2007
RADIAÇÃO LASER
NÃO OLHAR FIXAMENTE O FEIXE
1,8 mW
Potência máx. (peak):
<150 µs
Período de pulso:
655 nm
Comprimento de onda:
EQUIPAMENTO LASER CLASSE 2
EN 60825-1:2007
LASER RADIATION
DO NOT STARE INTO BEAM
<1 mW
Maximum Output (avg):
<150 µs
Pulse duration:
655 nm
Wavelength:
CLASS 2 LASER PRODUCT
IEC 60825-1:2007
Complies with 21 CFR 1040.10
䉏⏘戟⺓
▎䦃展⏘㧮
㦏⮶戢⒉᧤⽿⋋᧥
厘⑁㖐兼㢅梃
㽱栎
伊䉏⏘ℶ❐
GB7247.1-2012
1.8 mW
<150 µs
655 nm
Laser warning and information signs – supplied stick-on labels
BPS 307i
11
Device description
3
Device description
3.1
Device overview
3.1.1
General information
The BPS bar code positioning system uses visible red laser light to determine its position and its speed
value relative to a bar code tape that is affixed along the travel path. This takes place in the following steps:
• Read a code on the bar code tape (see figure 3.1)
• Determine the position of the read code in the scanning beam
• Calculate the position to within less than a millimeter using the code information and the code position relative to the device's center.
The position and speed values are then output to the controller via the host interface.
The BPS consists of device housing and interface connection hood for the connection to the control. The
BPS can optionally be delivered with display and optics heating.
The following connection hoods are available for the connection of the SSI interface:
• MS 307 connection hood with M12 connectors
• MK 307 connection hood with spring-cage terminals
• KB 307 connection hood with cable
4
000040
000044
4
000048
8
000052
000
000
0000
0 52
000056
56
56
000060
00
000
000064
000068
1
2
1
2
3
4
Figure 3.1:
Leuze electronic
3
Bar code tape
Connection hood
Device housing
Middle of the scanning beam (device middle, output position value)
Device construction, device arrangement and beam exit
BPS 307i
12
Device description
3.1.2
Performance characteristics
The most important performance characteristics of the bar code positioning system:
• Positioning with submillimeter accuracy from 0 to 10,000 m
• For the control at high traverse rates of up to 10 m/s
• Simultaneous position and speed measurement
• Working range: 50 to 170 mm; enables flexible mounting positions
• Interfaces: PROFINET fieldbus, PROFIBUS fieldbus, SSI, RS 232/RS 422, RS 485
• Binary inputs and outputs for control and process monitoring
• Configuration via webConfig tool or fieldbus
• Diagnostics via webConfig tool or optional display
• Optional model with display
• Optional model with heating for use to -35 °C
3.1.3
Accessories
Special accessories are available for the bar code positioning system. The accessories are optimally
matched to the BPS:
• Highly flexible, scratch-, smudge- and UV-resistant bar code tape
• Mounting devices for precise mounting with one screw (easy-mount)
• Modular connection technology via connection hoods with M12 connectors, spring-cage terminals or
with cable.
3.1.4
Device model with heating
The bar code positioning system is optionally available as a model with integrated heating. In this case,
heating is permanently installed ex works.
NOTICE
No self-installation of the heating!
 Self-installation of the heating on-site by the user is not possible.
The heating consists of two parts:
• Front cover heater
• Housing heater
Features of the integrated heating:
• Extends the application range of the BPS to -35 °C
• Supply voltage 18 … 30 VDC
• BPS release through an internal temperature switch (start-up delay of about 30 min for 24 V DC and
minimum ambient temperature of -35 °C)
• Required conductor cross-section for the power supply: At least 0.75 mm2
NOTICE
Do not use ready-made cables!
 It is not possible to use ready-made cables.
The current consumption of the BPS is too high for the ready-made cables.
Function
When the supply voltage is applied to the BPS, a temperature switch initially only supplies the heating with
current (front cover heater and housing heater). During the heating phase (around 30 min), when the
inside temperature rises above 15 °C, the temperature switch connects the BPS to the supply voltage. This
is followed by the self test and the changeover to read operation. The PWR LED lights up, showing overall
readiness for operation.
Leuze electronic
BPS 307i
13
Device description
When the inside temperature reaches approx. 18 °C, another temperature switch turns the housing heater
off and, if necessary, back on again (if the inside temperature drops below 15 °C). This does not interrupt
the read operation.
The front cover heater remains activated until an inside temperature of 25 °C is reached. At temperatures
above this, the front cover heater switches off and, with a switching hysteresis of 3 °C, back on again at
an inside temperature below 22 °C.
3.2
Connection technology
For the electrical connection of the BPS, the following connection variants are available:
• MS 307 connection hood with M12 connectors
• MK 307 connection hood with spring-cage terminals
• KB 307 connection hood with cable
The voltage supply (18 … 30 VDC) is connected acc. to the connection type selected.
Two freely programmable switching inputs/switching outputs for individual adaptation to the respective
application are also available here.
3.2.1
MS 307 connection hood with M12 connectors
The MS 307 connection hood features two M12 connector plugs and a Mini-B type USB socket as a
service interface for configuration and diagnostics of the BPS.
The configuration switches and the integrated parameter memory for the simple replacement of
the BPS are located in the MS 307.
1
2
3
1
2
3
4
Figure 3.2:
4
PWR / SW IN/OUT: M12 plug (A-coded)
SERVICE: Mini-B USB socket (behind protective cap)
HOST / BUS IN: M12 plug (B-coded), SSI
BUS OUT: not equipped
MS 307 connection hood, connections
NOTICE
Shielding connection
 The shielding connection is done via the M12 connector housing.
3.2.2
MK 307 connection hood with spring-cage terminals
The MK 307 connection hood makes it possible to connect the BPS directly and without additional connectors. The MK 307 features cable bushings in which the shielding connection for the interface cable is also
located. A Mini-B type USB socket is used for service purposes and for configuration and diagnostic of the
BPS.
Leuze electronic
BPS 307i
14
Device description
The configuration switches and the integrated parameter memory for simple replacement of the
BPS are located in the MK 307.
2
1
1
1
2
Figure 3.3:
1
3x cable bushing, M16 x 1.5
SERVICE: Mini-B USB socket (behind protective cap)
Connection hood MK 307, connections
Cable fabrication and shielding connection
 Remove approx. 78 mm of the connection cable sheathing.
15 mm of sheath of the shielded line must be freely accessible.
 Lead the individual wires into the terminals according to the diagram.
NOTICE
Do not use wire-end sleeves!
 When fabricating cables, we recommend against using wire-end sleeves.
The shield is automatically contacted when the cable is lead into the metal screw fitting and fastened when the cord grip is closed.
1
2
≈ 15 mm
1
2
Figure 3.4:
3.2.3
≈ 55 mm
≈ 8 mm
Diameter of contact area, cable: 6 … 9.5 mm
Diameter of contact area, shield: 5 … 9.5 mm
Cable fabrication for connection hoods with spring-cage terminals
KB 307 connection hood with cable
With connection hood KB 307 , it is possible to directly connect the BPS. A Mini-B type USB socket is used
for service purposes and for configuration and diagnostic of the BPS.
The length of the connection cable is 3 m.
Leuze electronic
BPS 307i
15
Device description
To connect, the system plugs (JST) at the end of the cable must be removed.
No parameter memory is integrated in connection hood KB 307.
1
2
1
2
Figure 3.5:
3.3
SERVICE: Mini-B USB socket (behind protective cap)
Connection cable
Connection hood KB 307-3000
Display elements
The BPS is available optionally with display, two control buttons and LEDs or with only two LEDs as indicators on the device housing.
3.3.1
LED indicators
The device housing features the following multicolor LED indicators as primary display element:
• PWR
• BUS
1
3
1
2
3
4
Figure 3.6:
Leuze electronic
2
4
PWR LED
LED BUS
Display
Control buttons
Indicators on the device housing
BPS 307i
16
Device description
Table 3.1:
Meaning of the LED indicators on the device housing
LED
Color, state
Description
LED 1
PWR
Off
Device is switched off
• No supply voltage
Green, flashing
Device is being initialized
• Supply voltage connected
• Initialization running
• No measurement value output
Green, continuous light Device in operation
• Initialization finished
• Measurement value output
LED 2
BUS
Red, flashing
Warning set
• No measurement (e.g. no bar code tape)
Orange, continuous
light
Service active
• No data on the host interface
• Configuration via USB service interface
Off
No supply voltage
Green, flashing
Initialization of the host interface
• No communication
Green, continuous light Host interface active
• Communication possible
Red, flashing
3.3.2
Communication error detected
Display indicators
The optional display of the BPS is only used as a display element. The display has the following features:
• Monochromatic with white background lighting
• Double line, 128 x 32 pixels
• Display language: English
Two control buttons can be used to control which values appear in the display.
The background lighting is activated by pressing any control button and is automatically deactivated after
ten minutes have passed.
The display shows the content on two lines:
• The upper display line shows the selected function as an English term.
• The lower display line shows the data of the selected function.
1
1
2
Figure 3.7:
Leuze electronic
2
Display
Control buttons
Display on the device housing
BPS 307i
17
Device description
Display functions
The following functions can be displayed and activated in the display:
• Position value
• Position Value
• Position value in mm
Display with “.” as decimal separator character (e.g., + 34598.7 mm)
• Reading quality
• Quality
• 0 … 100%
• Device status
• BPS Info
• System OK / Warning / Error
• I/O status
Status of the inputs/outputs
• I/O status
• IO1 In:0 / IO2 Out:0
In/Out depending on configuration, 0/1 for state of the I/O
• Version information
Software and hardware version of the device
• Version
• SW: V1.3.0 HW:1
NOTICE
Laser activation by selecting Quality!
 If measurement is stopped, the laser is activated by selecting Quality.
The display is controlled via the control buttons:
•
– Enter: activate or deactivate the display shift function
•
– Down: scroll through functions (downwards)
Example: Representation of the I/O status on the display
1.
Press button
: Display flashes
2.
Press button
: Display changes from position value (Position Value) to reading quality (Quality)
3.
Press button
: Display changes from reading quality (Quality) to device status (BPS Info)
4.
Press button
: Display changes from device status (BPS Info) to I/O status
5.
Press button
: I/O status displayed, display stops flashing
Display during device start-up
During device start-up, a start-up display first appears which is briefly followed by the display with the
version information.
The standard display after starting up the BPS is Position Value.
Leuze electronic
BPS 307i
18
Device description
3.4
Bar code tape
3.4.1
General information
The bar code tape is available in different variants:
• BCB bar code tape with 40 mm grid
Code128 with character set C, increasing in increments of 4 (e.g., 000004, 000008, … )
• Bar code tape BCB8 with 30 mm grid
Code128 with character set C, increasing in increments of 3 (e.g. 000003, 000006, … )
A bar code tape consists of a sequence of individual position labels in one of the two grids. Defined cut
marks are provided for cutting the BCB.
The bar code tape is delivered on a roll. A roll contains up to 200 m of BCB, with the wrapping direction
from the outside to the inside (smallest number on the outside). If more than 200 m of BCB is ordered, the
total length is divided into rolls of 200 m.
Bar code tapes with special requirements with respect to height, length and value range can be ordered
from Leuze electronic (see chapter 14.5 "Bar code tapes").
NOTICE
Value range for BCB with special requirements!
 When ordering bar code tapes with special requirements, make certain that the value range contains
only values that are divisible by three (BCB8 with 30 mm grid) or four (BCB with 40 mm grid).
It may otherwise not be possible to purchase and use repair tapes.
NOTICE
Only one BCB type per system!
 In a given system, use either only BCB8 with 30 mm grid or only BCB with 40 mm grid.
If different BCB types are used in one system, the BPS cannot ensure an exact position determination.
NOTICE
Configure the BPS for the used BCB type!
 The used BCB type must be set in the webConfig tool with the Tape selection parameter; see
chapter 9.3.2 "CONFIGURATION function".
 On delivery, the BPS is set for BCB with a 40 mm grid.
If the BCB8 with a 30 mm grid is used, the Tape selection must be adjusted in the BPS configuration.
 If the used BCB type does not correspond to the Tape selection configured in the BPS, exact position
determination cannot be performed by the BPS.
Leuze electronic
BPS 307i
19
Device description
BCB bar code tape with 40 mm grid
40
000040
000044
000048
1
1
2
Figure 3.8:
000052
2
Position label with position value
Cut mark
Bar code tape with 40 mm grid
The standard height of 47 mm can be adapted. Other BCB height (25 mm) and special heights on request.
With a standard bar code tape and a repair tape with 40 mm grid, the printed numerical values
are divisible by four without a remainder.
Bar code tape BCB8 with 30 mm grid
30
BCB8
000018
BCB8
000021
1
1
2
Figure 3.9:
BCB8
000024
BCB8
000027
BCB8
000030
2
Position label with position value
Cut mark
Bar code tape with 30 mm grid
The standard height of 47 mm can be adapted. Other BCB heights (25 mm and 30 mm) and special
heights on request.
With a standard bar code tape and repair tape with 30 mm grid, the printed numerical values are
divisible by three without a remainder.
For bar code tapes with 30 mm grid, the designation BCB8 is printed in plain text in addition to
the position value.
Leuze electronic
BPS 307i
20
Device description
3.4.2
Control bar codes
With the help of control bar codes that are affixed on top of the bar code tape at appropriate positions, functions in the BPS can be activated or deactivated, e.g., for changing various position values at switches.
Code type Code128 with character set B is used for the control bar code.
The MVS label is a control bar code for the direction-independent switching of the position values from one
bar code tape to another in the middle of the control bar code label.
• If, upon reaching the changeover position in the middle of the MVS label, the BPS does not detect
the new BCB section in the scanning beam, the position value of the first BCB section is still output
after the middle of the MVS label for half of the label width.
The MV0 label is a control bar code for the deactivation of the position output.
• If the BPS detects the middle of the MV0 label, no position values are output after the middle of the
MV0 label.
Arrangement of the control bar codes
The control bar code is attached in such a way that it replaces one position bar code or seamlessly
connects two bar code tapes with different value ranges to one another (see figure 3.10).
1
2
000040
1
2
000044
000048
0150000
015004
Control bar code
The control bar code is decoded in the marked scans
Figure 3.10: Arrangement of the MVS control bar code
Leuze electronic
BPS 307i
21
Device description
1
000040
1
2
2
0
000044
Control bar code
End of position determination from the middle of the control bar code
Figure 3.11: Arrangement of the MV0 control bar code
NOTICE
Distance between two control bar codes!
 Make certain that there is only one control bar code (or marker label) in the scanning beam at a time.
The minimum distance between two control bar codes is determined by the distance between the BPS
and bar code tape and the resulting length of the scanning beam.
The control bar codes are simply affixed over the existing bar code tape.
A control bar code should cover an entire position bar code and must have the correct grid dimension (see
figure 3.12):
• 30 mm with BCB8 bar code tapes
• 40 mm with BCB bar code tapes
Keep the gap between the BCBs that are switched between as small as possible.
Leuze electronic
BPS 307i
22
Device description
1
000040
000044
000048
000040
000044
000048
015000
015004
2
1
2
015004
Control bar code perfectly affixed on the bar code tape
Control bar code at small gap between two bar code tapes
Figure 3.12: Correct positioning of the control bar code
NOTICE
Gaps in bar code tape
 Avoid polished and high-gloss surfaces.
 Keep the gaps between the two bar code tapes and the control bar code as small as possible.
Measurement value switching between two bar code tapes with different value ranges
The MVS or MV0 control bar code is used to switch between two bar code tapes.
NOTICE
1 m minimum distance of the bar code values for measurement value switching!
 For different BCB value ranges, make certain that the minimum distance of 1 m between the preceding
position bar code (before the control bar code) and the subsequent position bar code (after the control
bar code) is maintained.
Example (BCB with 40 mm grid): If the last position bar code on the BCB before the control bar code
is 75120, the following position bar code on the BCB after the control bar code must be at least 75220.
If the minimum distance between the bar code values is not maintained, position determination may
be faulty.
• The end of the preceding bar code tape and the start of the subsequent bar code tape can end and
begin, respectively, with completely different position bar codes.
• BCB changeover by means of a control bar code always occurs at the same position, i.e., it serves to
change from the preceding tape to the subsequent tape and vice versa.
• If the center of the BPS reaches the transition point of the control bar code, the device switches to
the second BCB, provided the next position label is in the BPS's scanning beam (see figure 3.13).
The output position value is thereby always uniquely assigned to one BCB.
Leuze electronic
BPS 307i
23
Device description
If the BPS does not detect the new BCB section upon reaching the changeover position, the position-value output is dependent on the used control bar code.
MVS control bar code: The position value of the first BCB is output beyond the middle of the MVS
label for half of the label width.
MV0 control bar code: No position values are output after the middle of the MV0 label.
• When the control label is passed, the new BCB value is output relative to the middle of the device or
label.
2
1
000040
000044
000048
0150000
015004
4
3
1
2
3
4
Scanning beam
Middle of the control bar code
Middle of the BPS
Direction of movement
Figure 3.13: Changeover position with MVS control bar code for BCB changeover
3.4.3
Marker labels
Marker labels, which are affixed at the appropriate locations on top of the bar code tape, can be used to
trigger various functions in the superior control. The BPS detects the defined marker labels in the scanning
beam, decodes them, and makes them available to the control.
NOTICE
Distance between two marker labels!
 Make certain that there is only one marker label (or control bar code) in the scanning beam at a time.
The minimum distance between two marker labels is determined by the distance between the BPS and
bar code tape and the resulting length of the scanning beam.
Definition of the marker label
The following combinations of letters and numbers may be used as marker labels:
First character: A … Z, a … z
Second character: Digit from 0 … 9
Third character: Digit from 0 … 9
Structure of the marker labels
Code type Code128 with character set B is used for the marker labels.
Arrangement when using the marker label with positioning
The marker label must be attached to the bar code tape aligned with the grid of the actual coding. A position code should be visible before and after the marker label.
Leuze electronic
BPS 307i
24
Device description
1
000040
1
000044
000048
0000052
000056
Marker label
Figure 3.14: System arrangement of marker labels
Arrangement when using the marker label without positioning
The marker label must be positioned within the BPS's detection range.
3.4.4
Twin tapes
Twin tapes are jointly manufactured bar code tapes with the same value range.
NOTICE
A twin tape always consists of two bar code tapes!
 When ordering a twin tape, two bar code tapes are always included with an order.
Twin tapes are used if positioning with two bar code tapes is necessary, e.g., with crane systems or elevators.
Because they are manufactured jointly, both tapes have the same length tolerance. As a result, differences
in length and code position are minimal. By having the same code position on both tapes, improved
synchronization can be achieved during positioning compared to bar code tapes that are manufactured
separately.
1
2
1
2
Twin bar code tape 1
Twin bar code tape 2
Figure 3.15: Twin tape with double numbering
Twin tapes are always delivered in pairs on two rolls.
If twin tapes are replaced, both tapes are to be replaced.
Twin tapes can be ordered from Leuze electronic (see chapter 14.5 "Bar code tapes").
Leuze electronic
BPS 307i
25
Functions
4
Functions
This chapter describes the functions of the BPS and the parameters for adaptation to the respective application conditions and requirements.
The parameters are set via the webConfig tool; see chapter 9 "Leuze electronic webConfig tool –
Extended configuration".
Main functions:
• Position measurement
• Speed measurement
The following parameters are relevant for the timing of the position and speed measurement:
• Measurement value preparation
Configurable response time
• Measurement error tolerance
Configurable time-based error suppression
4.1
Position measurement
The output value of the position measurement is calculated from the measurement and the settings for
resolution, preset, offset, etc.
The most important individual parameters for the position measurement are:
4.2
Parameter
Description
Range/Values
Position resolution
The parameter specifies the resolution of the position value.
It acts only on the host interface.
The resolution has no effect on the set parameter values
such as offset or preset.
0.001 mm
0.01 mm
0.1 mm
1 mm
10 mm
or
Free resolution
Unit
The parameter specifies the measurement unit of the measured position and speed.
The selection of the measurement unit affects all parameters with measurement units.
Metric (mm)
or
inch (1/100 in)
Offset
The offset is used to correct the position value by a fixed
amount.
If the offset is activated, the offset is added to the position
value. This yields a new output value:
Output value = position value + offset
1 mm
or
inch/100
Preset
Like the offset, the preset is used to correct the position
value.
With preset, a preset value is specified. The value is
accepted during a corresponding event (switching input or
fieldbus).
If the preset is activated, this has priority over the offset.
1 mm
or
inch/100
Speed measurement
The current speed is ascertained and output on the basis of the respective position values.
The most important individual parameters for the speed measurement are:
Leuze electronic
BPS 307i
26
Functions
4.3
Parameter
Description
Range/Values
Speed resolution
The parameter defines the resolution of the speed value. It
affects only the fieldbus output.
1 mm/s
10 mm/s
100 mm/s
1000 mm/s
or
Free resolution
Averaging
The parameter specifies the averaging time of the calculated speed values in steps.
Steps:
2 ms, 4 ms,
8 ms,
16 ms, 32 ms,
64 ms, 128 ms
Timing
The BPS of the 300i series operate with a scanning rate of 1000 scans per second. A measurement value
is ascertained every 1 ms.
The following parameters are relevant for the timing of the position and speed measurement:
4.4
Parameter
Description
Range/Values
Integration depth
The integration depth affects the measurement of position Factory setting:
and speed. The integration depth parameter specifies the 8
number of sequential measurements that the BPS uses for
position determination.
The integration results in smoothing of the output measurement value.
An integration depth of 8 (position determination with 8
measurement values) results in a response time of 8 ms.
Update rate
The update rate (50 µs to 2 ms) of the measurement values Factory setting:
at the SSI interface can be configured via the webConfig
2 ms
tool; see chapter 9.3.2 "CONFIGURATION function".
Error delay time
Factory setting:
Errors that occur are suppressed for the configured time.
If no valid position or speed value can be ascertained in the 50 ms
configured error delay time, the last valid value is always
output.
If the error persists after the error delay time elapses, the
value of the Position/Speed value in case of error parameter is then output (standard).
Leuze webConfig tool
The webConfig configuration tool offers a graphical user interface for the display of process data, configuration and diagnostics of the BPS via a PC; see chapter 9 "Leuze electronic webConfig tool – Extended
configuration".
4.5
Evaluation of the reading quality
The BPS can signal the reading quality of the BPS. The reading quality is displayed in % values.
The parameters for the evaluation of the reading quality are set via the webConfig tool:
CONFIGURATION > DATA PROCESSING > Reading quality; see chapter 9.3.2 "CONFIGURATION
function".
The values of the reading quality are displayed via the optional display (Quality), the serial communication protocol and via the webConfig tool; see chapter 9.3.3 "ALIGNMENT function".
Leuze electronic
BPS 307i
27
Functions
The evaluation of the reading quality provides the following information, e.g.:
• The reading quality is constantly bad: Soiling of the BPS optics
• The reading quality is always bad at certain position values: Soiling of the BCB
4.6
Distance measurement to the bar code tape
Within the reading field, the BPS can output the current distance from the read head to the BCB. The
distance from the position label closest to the reference point is output.
The distance measurement value is output via:
• The ALIGNMENT function (Quality menu) in the webConfig tool (see chapter 9.3.3); this function is
only available in the Service operating mode.
Leuze electronic
BPS 307i
28
Applications
5
Applications
Wherever systems are moved automatically, it is necessary to uniquely determine their respective positions. In addition to mechanical measuring sensors, optical methods are particularly well suited for position
determination as they can be used to determine position without mechanical wear and slippage.
Compared to common optical measurement techniques, the Leuze electronic Bar code Positioning
System (BPS) is able to measure a position with absolute sub-millimeter accuracy, i.e. independent of
reference points. As a result, it is able to provide a unique position value at any time. With the highly flexible
and hard-wearing Bar Code Tape (BCB), the system can even be used without problem in systems with
curves or guide tolerances. And this at lengths of up to 10,000 meters.
The product family of Leuze electronic bar code positioning systems convinces with a variety of advantages:
• The laser simultaneously scans three bar codes and, as a result, is able to determine the position
with sub-millimeter accuracy. The wide reading field makes accurate position determination possible
even in the event of minor damage to the tape.
• With the systems' flexible depth of field, it is also possible to bridge over mechanical deviations.
• Due to the large reading distance combined with the great depth of field, a large opening angle and a
very compact construction, the device is ideally suited for the conveyor and storage technology market.
• The BPS devices are capable of simultaneously measuring position and speed and are thus also
suitable for control tasks in your automation applications.
• Using a mounting device, the BPS can be mounted with millimeter accuracy with just one screw. If
mounted using a mounting device, a new device is automatically aligned correctly should it be necessary to exchange a device (easy-mount).
• The unique labeling of the bar code tape allows the system to be put back into operation without
problem even after a brief voltage drop without, e.g., needing to utilize a reference point.
• The Leuze electronic bar code tape is very robust, highly flexible and, thanks to the self-adhesive
back, can be easily integrated into your overall mechanical system. It can be fit optimally to both vertical as well as horizontal curved paths and thereby reliably facilitates trouble-free and reproducible
measurement at any point in your system with sub-millimeter accuracy.
Typical applications for the BPS include:
• High-bay storage device (see chapter 5.1)
• Telpher line (see chapter 5.2)
• Gantry cranes (see chapter 5.3)
Leuze electronic
BPS 307i
29
Applications
5.1
High-bay storage device
Figure 5.1:
High-bay storage device
 Simultaneous position and speed measurement for regulation tasks
 Precise positioning with a reproducibility of  0.15 mm
 Control at high traverse rates of up to 10 m/s
Leuze electronic
BPS 307i
30
Applications
5.2
Telpher line
Figure 5.2:
Telpher line
 The working range from 50 - 170 mm allows for flexible mounting positions and reliable position detection at varying distances
 Control codes for changing to different position values at switches
Leuze electronic
BPS 307i
31
Applications
5.3
Gantry cranes
Figure 5.3:
Gantry cranes
 Positioning from 0 to 10,000 meters
 Scratch- and smudge-proof, UV-resistant bar code tapes
 Synchronous positioning with twin tapes on both rails
 Mounting device for fast, precise mounting with one screw
Leuze electronic
BPS 307i
32
Mounting and installation
6
Mounting and installation
6.1
Mounting bar code tape
6.1.1
Installation and application remarks
NOTICE
BCB mounting
 When processing BCBs, observe the specified processing temperatures.
When processing BCBs in cold storage facilities, the BCB must be affixed before cooling the storage
facility.
However, if it should be necessary to affix the BCB at temperatures outside of the specified processing
temperature, assure that the bonding surface as well as the BCB are at the processing temperature.
 Avoid dirt deposits on the BCB.
If possible, affix the BCB vertically.
If possible, affix the BCB below an overhead covering.
The BCB must never be continuously cleaned by on-board cleaning devices such as brushes or
sponges. Permanent on-board cleaning devices polish the BCB and give it a glossy finish. The reading
quality deteriorates as a result.
 After affixing the BCBs, make certain that there are no polished, high-gloss surfaces in the scanning
beam (e.g., glossy metal at gaps between the individual BCBs), as the measurement quality of the
BPS may be impaired.
Affix the BCBs to a diffusely reflective support, e.g., a painted surface.
 Avoid sources of extraneous light and reflections on the BCB.
Ensure that neither strong sources of extraneous light nor reflections of the support on which the BCB
is affixed occur in the vicinity of the BPS scanning beam.
 Affix the BCB over expansion joints up to a width of several millimeters.
The BCB must not be interrupted at this location.
 Cover protruding screw heads with the BCB.
 Ensure that the BCB is affixed without tension.
The BCB is a plastic tape that can be stretched by strong mechanical tension. Excessive mechanical
stretching results in lengthening of the tape and distortion of the position values.
NOTICE
BCB application
 Make certain that the BCB is located in the scanning beam of the BPS over the entire traversing path.
The BPS can determine the position on BCBs with arbitrary orientation.
 Bar code tapes with different value ranges may not directly follow one another.
In the case of different value ranges, a gap of at least 1 m must be maintained between the last position
bar code of the preceding BCB and the first position bar code of the subsequent BCB (see
chapter 3.4.2).
 For MVS/MV0 control bar codes (see chapter 3.4.2), the minimum distance of 1 m between the last
position bar code before the control bar code and the first position bar code after the control bar code
must be maintained.
 For bar code tapes with different value ranges, both BCBs must correspond to the BCB type configured in the BPS (see chapter 3.4.1).
 Avoid position bar code labels with the value 00000.
Measurements to the left of the center of a 00000 label produce negative position values that may not
be displayed correctly.
Leuze electronic
BPS 307i
33
Mounting and installation
6.1.2
Cutting bar code tapes
NOTICE
Avoid cutting BCB!
 If possible, avoid cutting bar code tapes.
Optimum position value determination by the BPS is achieved with continuously affixed BCB.
 If there are mechanical gaps, first affix the BCB continuously. Then cut the BCB.
The BCB is cut at the indicated cut marks; see figure 6.1.
1
000040
1
Figure 6.1:
000044
000048
000052
000056
Cut mark
Cut mark on the bar code tape
If another BCB is to be affixed directly after the preceding BCB, the subsequent bar code value must differ
from the preceding BCB by at least 1 m; see figure 6.2.
2
000040
1
1
2
3
Figure 6.2:
000044
000148
000152
000156
3
Preceding bar code tape
Cut mark
Subsequent bar code tape, value range + 1 m
Cut bar code tape
If there is a gap without tape after the preceding BCB, it must be at least 300 mm wide before the subsequent BCB is affixed; see figure 6.3. The first bar code value of the subsequent BCB must differ by at least
20 (200 mm) from the last bar code value of the preceding BCB.
Leuze electronic
BPS 307i
34
Mounting and installation
2
2
3
000040
000044
000064
1
000068
4
1
2
3
4
Figure 6.3:
Preceding bar code tape
Cut mark
Gap, at least 300 mm
Subsequent bar code tape
Gap in cut bar code tape to avoid double positions
NOTICE
No glossy gaps in the cut bar code tape!
 Ensure that there are matt, bright surfaces behind the gaps in the BCB.
Polished, reflective, and high-gloss surfaces in the scanning beam may impair the measurement quality of the BPS.
6.1.3
Mounting the BCB
Mount the BCB as follows:
 Check the surface.
It must be flat, free of grease and dust, and be dry.
 Define a reference edge (e.g., metal edge of the busbar).
 Remove the backing and affix the BCB along the reference edge tension free.
 Secure the bar code tape to the mounting surface by pressing down with the palm of your hand.
When affixing, make certain that the BCB is free of folds and creases and that no air pockets form.
NOTICE
When mounting, do not pull on the BCB!
 The BCB is a plastic tape that can be stretched by strong mechanical tension. The stretching results
in lengthening of the tape and distortion of the position values on the BCB.
While the BPS can still perform the position calculation in the event of distortions, the absolute measurement accuracy is no longer ensured in this case. If the values are taught using a teach-in process,
stretching of the BCB is irrelevant.
If a bar code tape was damaged, e.g., by falling parts, you can download a repair kit for the BCB
from the Internet (see chapter 11.2.2 "BCB repair with repair kit").
Use the bar code tape created with the repair kit only temporarily as an emergency solution.
Leuze electronic
BPS 307i
35
Mounting and installation
BCB mounting in horizontal curves
NOTICE
Limited absolute measurement accuracy and reproducibility!
 BCB mounting in curves decreases the absolute measurement accuracy of the BPS, since the distance between two bar codes is no longer exactly 40 mm or 30 mm.
 For horizontal curves, maintain a minimum bending radius of 300 mm (see figure 6.4).
3
2
1
1
2
3
Figure 6.4:
BPS
Reading distance
Radius of the bar code tape, Rmin = 300 mm
Mounting the bar code tape for use in horizontal curves
BCB mounting in vertical curves
NOTICE
Limited absolute measurement accuracy and reproducibility!
 BCB mounting in curves decreases the absolute measurement accuracy of the BPS, since the distance between two bar codes is no longer exactly 40 mm or 30 mm.
 In areas where the BCB is fanned out around curves, limitations of the reproducibility must be
expected.
Leuze electronic
BPS 307i
36
Mounting and installation
 Only partially cut the BCB at the cut mark.
 Affix the BCB along the curve like a fan (see figure 6.5).
 Ensure that the BCB is affixed without mechanical tension.
NOTICE
No glossy gaps in the bar code tape!
 Ensure that there are matt, bright surfaces behind the fanning in the BCB curves.
Polished, reflective, and high-gloss surfaces in the scanning beam may impair the measurement quality of the BPS.
000040
000044
000
048
00
00
52
00
Figure 6.5:
00
56
Preparing the bar code tape for use in vertical curves
Mounting twin tapes
If two bar code tapes with the same value range are used for positioning, e.g., for crane systems or elevators, the use of twin tapes is recommended (see chapter 3.4.4 "Twin tapes").
“Upside down” in order to have the same values at the same position (see figure 6.6).
1
2
1
2
Figure 6.6:
Leuze electronic
Twin bar code tape 1
Twin bar code tape 2
Mounting twin tapes
BPS 307i
37
Mounting and installation
NOTICE
A twin tape always consists of two bar code tapes.
 When ordering twin tapes, two bar code tapes are always included with an order.
 Ensure that the BCB is affixed without tension.
The BCB is a plastic tape that can be stretched by strong mechanical tension. Excessive mechanical
stretching results in lengthening of the tape and distortion of the position values.
Mounting two bar code tapes with the same value range
For crane systems or elevators, two bar code tapes with the same value range are used for positioning.
If two bar code tapes with the same value range are needed, the use of twin tapes is recommended (see chapter 3.4.4 "Twin tapes").
If a twin tape is not used: To have the same values at the same position, one bar code tape must be affixed
with numbers upside down while the other is affixed normally (see figure 6.7).
1
2
1
2
Figure 6.7:
6.2
BCB affixed upside down
BCB affixed normally
Affixing two bar code tapes with the same value range
Bar code positioning system
The BPS can be mounted in the following ways:
• Mounting using a mounting device on the fastening grooves
• BTU 0300M-W: Wall mounting
• BT 56: Mounting on a rod
• Mounting using a mounting device on the M4 mounting threads on the rear of the device
• BT 300 W: Mounting on a mounting bracket
• BT 300-1: Mounting on a rod
• Mounting using four M4 mounting threads on the rear of the device
If the BTU 0300M-W mounting device is used to mount the device, the new device is automatically aligned correctly should it be necessary to exchange a device.
Leuze electronic
BPS 307i
38
Mounting and installation
6.2.1
Mounting instructions
NOTICE
Select the mounting location.
 Make certain that the required environmental conditions (humidity, temperature) are maintained.
 Make certain that the distance between BPS and bar code tape is sufficiently large.
The scanning beam of the BPS should cover three or more bar codes.
The distance between BPS and bar code tape must be in the working range of the reading field curve.
 Make certain that the exit window does not become soiled, e.g., by leaking liquids, abrasion from cardboard packaging or residues from packaging material.
 Mounting the BPS outdoors or with BPS with integrated heating:
Mount the BPS in a way which provides maximum thermal isolation, e.g., using rubber-bonded metal.
Mount the BPS so that it is protected from airflow, e.g., in a protective housing.
 Mounting the BPS in a protective housing:
When installing the BPS in a protective housing, ensure that the scanning beam can exit the protective
housing without obstruction.
 Make certain that the scanning range determined from the scanning curve is adhered to at all locations
where a position determination is to be made.
 Ensure that the scanning beam is always incident on the BCB when the system is moving.
For the position calculation, the scanning beam of the BPS must be incident on the BCB without interruption.
For the best functionality, the BPS must be guided parallel to the BCB. It is not permitted to move outside of the approved working range of the BPS (50 … 170 mm) while the system is in motion.
 Make certain that there is only one control bar code (or marker label) in the scanning beam at a time.
The minimum distance between two control bar codes is determined by the distance between the BPS
and bar code tape and the resulting length of the scanning beam.
NOTICE
For parallel mounting, maintain the minimum distance!
 Maintain the minimum distance of 300 mm if you mount two BPS next to or above one another.
300 mm
Figure 6.8:
Minimum distance for parallel mounting
NOTICE
Install the connection hood before mounting the BPS!
 Screw connection hood MS 307, MK 307 or KB 307 to the device housing with two M4 screws.
 Tighten the screws on the connection hood with a tightening torque of 1.4 Nm.
Leuze electronic
BPS 307i
39
Mounting and installation
6.2.2
Orientation of the BPS to the bar code tape
The beam of the BPS must be oriented at an incline of 7° to the bar code tape (see figure 6.9). When positioning, make certain that the angle of radiation to the rear side of the housing is 90 ° and the reading
distance to the bar code tape is maintained.
50
2
000040
000044
000048
000052
000056
000060
000064
000068
2
1
3
1
2
3
Figure 6.9:
6.2.3
Reading distance
Reference point for the bar code position
Scanning beam
Beam exit
Mounting with the BTU 0300M-W mounting device
Mounting the BPS with a BTU 0300M-W mounting device is intended for wall mounting. For ordering information see chapter 14; for dimensioned drawing see figure 13.9.
Leuze electronic
BPS 307i
40
Mounting and installation
1
2
3
1
2
3
Clamp profile
Clamping jaws
Screw terminal
Figure 6.10: Mounting the BPS with the BTU 0300M-W mounting device
 Mount the BTU 0300M-W on the system side with M6 fastening screws (not included in delivery contents).
 Mount the BPS with the dovetail fastening grooves on the clamping jaws of the BTU 0300M-W with limit
stop at end.
 Secure the BPS with the M6 screw terminal.
Maximum tightening torque for the M6 screw terminal: 8 Nm
6.2.4
Mounting with the BT 300 W mounting bracket
Mounting of the BPS with a BT 300 W mounting bracket is intended for wall mounting. For ordering information see chapter 14; for dimensioned drawing see figure 13.10.
 Mount the BT 0300 W mounting bracket on the system side with M6 fastening screws (included in delivery contents).
 Mount the BPS on the mounting bracket with M4 fastening screws (included in delivery contents).
Maximum tightening torque of the M4 fastening screws: 2 Nm
6.2.5
Mounting with BT 56 mounting device
Mounting of the BPS with a BT 56 mounting device is intended for rod mounting. For ordering information
see chapter 14; for dimensioned drawing see figure 13.11.
 Mount the BT 56 on the rod with the clamp profile (system-side).
 Mount the BPS with its fastening grooves on the clamping jaws of the BT 56 with limit stop at end.
 Secure the BPS with the M6 screw terminal.
Maximum tightening torque for the M6 screw terminal: 8 Nm
Leuze electronic
BPS 307i
41
Mounting and installation
6.2.6
Mounting with BT 300-1 mounting device
Mounting of the BPS with a BT 300-1 mounting device is intended for rod mounting. For ordering information see chapter 14; for dimensioned drawing see figure 13.12.
 Mount the BT 300-1 mounting device with the clamp profile on the rod (system-side).
 Mount the BPS on the mounting bracket of the BT 300-1 with M4 fastening screws (included in delivery
contents).
Maximum tightening torque of the M4 fastening screws: 2 Nm
6.2.7
Mounting with M4 fastening screws
all dimensions in mm
Figure 6.11: Dimensioned drawing of rear of BPS
 Mount the BPS on the system with M4 fastening screws (not included in delivery contents).
Maximum tightening torque of the fastening screws: 2 Nm
Leuze electronic
BPS 307i
42
Electrical connection
7
Electrical connection
CAUTION
Safety notices!
 Before connecting the device, be sure that the supply voltage agrees with the value printed on the
name plate.
 Only allow competent persons to perform the electrical connection.
 Ensure that the functional earth (FE) is connected correctly.
Fault-free operation is only guaranteed if the functional earth is connected properly.
 If faults cannot be rectified, take the device out of operation. Protect the device from accidentally being
started.
CAUTION
UL applications!
 For UL applications, use is only permitted in Class 2 circuits in accordance with the NEC (National
Electric Code).
NOTICE
Protective Extra Low Voltage (PELV)
 The BPS is designed in accordance with protection class III for supply with PELV (protective extra-low
voltage).
NOTICE
Connection hood and degree of protection IP 65
 Before connecting, mount the connection hood on the BPS device housing.
 To ensure degree of protection IP 65 is fulfilled, the screws of the connection hood are tightened with
a tightening torque of 1.4 Nm for connecting to the BPS.
 Degree of protection IP 65 is not fulfilled until connectors or cable bushings are screwed on and caps
are installed.
For all connections (connection cable, interconnection cable, etc.), use only the cables listed in
the accessories (see chapter 14).
7.1
External parameter memory in the connection hood
To enable simple exchange of the BPS, the integrated parameter memory of the MS 307 and MK 307
connection hoods store a copy of the current parameter set.
Also located in the MS 307 and MK 307 are switches S1 and S2.
• Slide switch S1 is used to toggle the encoding of the output measurement value between Gray and
binary.
• Rotary switch S2 is used to set the resolution of the position value (in mm) or a speed monitoring
function.
NOTICE
No parameter memory and no configuration switches in connection hood KB 307!
 No parameter memory is integrated in connection hood KB 307.
 Connection hood KB 307 does not include any switches for configuring the BPS.
Leuze electronic
BPS 307i
43
Electrical connection
7.2
MS 307 connection hood with connectors
The MS 307 connection hood features two M12 connector plugs and a Mini-B type USB socket as a
service interface.
The integrated parameter memory for the simple replacement of the BPS is located in the MS 307.
1
2
3
1
2
3
4
Figure 7.1:
4
PWR / SW IN/OUT: M12 plug (A-coded)
SERVICE: Mini-B USB socket (behind protective cap)
HOST / BUS IN: M12 plug (B-coded), SSI
BUS OUT: not equipped
MS 307 connection hood, connections
NOTICE
Shielding connection and functional earth connection!
 The shielding connection is done via the M12 connector housing.
 Ensure that the functional earth (FE) is connected correctly. Unimpaired operation is only guaranteed
when the functional earth is connected properly. All electrical disturbances (EMC couplings) are discharged via the functional earth connection.
 Connect connection PWR / SW IN/OUT to the supply voltage or the switching inputs/outputs.
 Connect connection SSI (HOST / BUS IN) to your SSI interface.
7.3
MK 307 connection hood with spring-cage terminals
With the MK 307 connection hood, the BPS is connected directly and with no additional plug.
• The MK 307 features cable bushings in which the shielding connection for the interface cable is also
located.
• The integrated parameter memory for the simple replacement of the BPS is located in the MK 307.
• A Mini-B type USB socket is used for service purposes.
Leuze electronic
BPS 307i
44
Electrical connection
2
1
1
1
2
Figure 7.2:
1
3x cable bushing, M16 x 1.5
SERVICE: Mini-B USB socket (behind protective cap)
Connection hood MK 307, connections
NOTICE
Cable fabrication!
 We recommend against using wire-end sleeves.
NOTICE
Functional earth connection!
 Ensure that the functional earth (FE) is connected correctly. Unimpaired operation is only guaranteed
when the functional earth is connected properly. All electrical disturbances (EMC couplings) are discharged via the functional earth connection.
 Connect connection PWR / SW IN/OUT to the supply voltage or the switching inputs/outputs.
 Connect connection SSI (HOST / BUS IN) to your SSI interface.
7.4
KB 307 connection hood with cable
Connection hood KB 307 features an SSI connection cable and a Mini-B type USB socket as service interface.
1
2
1
2
Figure 7.3:
Leuze electronic
SERVICE: Mini-B USB socket (behind protective cap)
Connection cable
Connection hood KB 307-3000
BPS 307i
45
Electrical connection
NOTICE
No integrated parameter memory!
 No parameter memory is integrated in connection hood KB 307.
 Remove the system plug (JST) at the end of the cable.
 Connect the connection cable to your SSI interface.
7.5
Pin assignment
7.5.1
PWR / SW IN/OUT (Power and switching input/output)
5-pin, M12 plug (A-coded) or terminal block for connecting to PWR / SW IN/OUT.
2
5
1
FE
3
4
Figure 7.4:
Table 7.1:
4
2
1
3
5
PWR / SW IN/OUT connection
PWR / SW IN/OUT pin assignment
Pin/terminal
Designation
Assignment
1
VIN
+18 … +30 VDC supply voltage
2
SWIO1
Sw. input/output 1 (configurable)
3
GNDIN
Negative supply voltage (0 VDC)
4
SWIO2
Sw. input/output 2 (configurable)
5
FE
Functional earth
Thread (M12 plug)
Cable gland
Functional earth
Connection cable shield.
The shield of the connection cable is on the thread of
the M12 plug or on the screw fitting of the cable bushing.
The thread or the screw fitting is part of the metallic
housing. The housing is at the potential of the functional earth via pin 5.
Connection cables: see table 14.3
CAUTION
UL applications!
 For UL applications, use is only permitted in Class 2 circuits in accordance with the NEC (National
Electric Code).
Leuze electronic
BPS 307i
46
Electrical connection
Switching input/output
The BPS is equipped with two, freely programmable, optically decoupled switching inputs/outputs, SWIO1
and SWIO2.
• The switching inputs can be used to activate various internal functions of the BPS (e.g., Measurement Stop/Start, Teach Preset, Reset Preset).
• The switching outputs can be used to signal the state of the BPS and to implement external functions
independent of the superior control (e.g. position value/speed value invalid, position and speed limit
value exceeded, device error).
• The control can use switching inputs/outputs as digital I/Os.
If no internal BPS function is connected to the switching inputs/outputs, the ports can be addressed
as two inputs, two outputs or as one input and one output of a digital I/O component.
The function as input or output is set via the webConfig configuration tool (CONFIGURATION >
DEVICE > Switching inputs/outputs, see chapter 9.3.2).
NOTICE
Maximum input current
 The input current of the respective switching input is maximum 8 mA.
NOTICE
Maximum loading of the switching outputs
 Do not load the respective switching output of the BPS with more than 60 mA at + 18 … 30 VDC in
normal operation.
 Each configured switching output is short-circuit proof.
The two switching inputs/outputs, SWIO1 and SWIO2, are configured as follows by default:
Switching output SWIO1: Position value invalid
Switching input SWIO2: Teach Preset
NOTICE
SWIO1 and SWIO2 as switching output
 At the outputs of the BPS (SWIO1 and SWIO2), no switching outputs may be connected from external
sensors/devices.
The switching output of the BPS may otherwise malfunction.
7.5.2
SSI (HOST / BUS IN)
5-pin, M12 plug (B-coded) or terminal block for connecting to an SSI interface.
2
5
1
3
4
Figure 7.5:
Leuze electronic
1
2
nc
4
3
SSI connection
BPS 307i
47
Electrical connection
Table 7.2:
SSI (HOST / BUS IN) pin assignment
Pin/terminal
Designation
Assignment
1
DATA+
+ Data line SSI
(Output electrically isolated)
2
DATA-
- Data line SSI
(Output electrically isolated)
3
CLK+
+ Clock line SSI
(Input electrically isolated)
4
CLK-
- Clock line SSI
(Input electrically isolated)
5
FE
Functional earth
Thread (M12 plug)
Cable gland
Functional earth
(housing)
Connection cable shield.
The shield of the connection cable is on the
thread of the M12 plug or on the screw fitting of
the cable bushing.
The thread or the screw fitting is part of the
metallic housing. The housing is at the potential
of the functional earth via pin 5.
NOTICE
Use ready-made connection cables!
 If possible, use the ready-made cables from Leuze electronic; see table 14.4.
NOTICE
Data cables for the SSI interface!
 Use only shielded and twisted-pair cables as data line for the SSI interface.
Twisting: pin 1 with 2, pin 3 with 4
The shield must be connected at both ends.
7.5.3
SSI connection cable KB 307
Table 7.3:
SSI connection cable KB 307
KB 307-3000
KB 307-5000 FLEX
KB 307-10000 FLEX
Designation
Assignment
WH
GY
FE
Functional earth
WH-BK
WH
GNDIN
Negative supply voltage (0 VDC)
BK
BN
VIN
+18 … +30 VDC supply voltage
GY
VT
SWIO1
Sw. input/output 1 (configurable)
WH-GN
BK
SWIO2
Sw. input/output 2 (configurable)
WH-YE
BU
CLK-
- Clock line SSI
(Input electrically isolated)
WH-RD
GN
DATA-
- Data line SSI
(Output electrically isolated)
YE
RD
CLK+
+ Clock line SSI
(Input electrically isolated)
Leuze electronic
BPS 307i
48
Electrical connection
7.5.4
KB 307-3000
KB 307-5000 FLEX
KB 307-10000 FLEX
Designation
Assignment
RD
YE
DATA+
+ Data line SSI
(Output electrically isolated)
---
PK
---
Not connected
VT
---
---
Reserved
WH-BN
---
---
Reserved
BN
---
---
Reserved
WH-OG
---
---
Reserved
OG
---
---
Reserved
GN
---
---
Reserved
BU
---
---
Reserved
Service USB
NOTICE
Connection to PC with standard USB cable!
 The service USB interface of the BPS is connected to the USB interface on the PC with a standard
USB cable (plug combination - Mini-B type / Type A).
5-pin, Mini-B plug for connecting to the service USB.
1
2
3
Figure 7.6:
Table 7.4:
4
5
Service USB connection
Service USB pin assignment
Pin
Designation
Assignment
1
VB
Sense input
2
D-
Data -
3
D+
Data +
4
ID
Not connected
5
GND
Ground
NOTICE
Use ready-made connection cables!
 If possible, use the ready-made cables from Leuze electronic; see table 14.6.
NOTICE
Self-configured cables!
 Ensure adequate shielding.
The maximum cable length of 3 m must not be exceeded.
Leuze electronic
BPS 307i
49
Electrical connection
7.6
Cable lengths and shielding
Observe the maximum cable lengths and the shielding types:
Connection
Interface
Max. cable length
Shielding
BPS service
USB
3m
Shielding absolutely
necessary acc. to USB
specifications
30 m
Not necessary
BPS power supply unit
Cable length according to the data rate
NOTICE
Data cables for the SSI interface!
 Use only shielded and twisted-pair cables as data line for the SSI interface.
Twisting: pin 1 with 2, pin 3 with 4
The shield must be connected at both ends.
 Do not lay the data line parallel to power cables.
The maximum possible cable length of the SSI connection is dependent on the used cable and the data
rate.
Table 7.5:
SSI cable lengths according to the data rate
Data rate [kbit/s]
80
100
200
300
400
500
600
800
Maximum cable length [m]
500
400
200
100
50
25
18
15
Leuze electronic
BPS 307i
50
Basic configuration
8
Basic configuration
The parameters of the SSI interface as well as the switching inputs/outputs can be configured via the
webConfig tool (see chapter 9) or via connection hood MS 307 or MK 307.
Devices with connection hood KB 307 can only be configured via the webConfig tool.
8.1
Configuring the SSI interface
8.1.1
Principal functionality of the SSI interface
Data communication of the SSI interface is based on differential transmission as is used for RS 422 interfaces. The position value is transmitted in sync with a cycle (CLOCK) specified by the control, starting with
the most significant bit (MSB); see figure 8.1.
• In the idle state, both the clock line as well as the data line are at HIGH level.
On the first HIGH-LOW edge (1), the data of the internal register are stored.
This ensures that the data are not changed during serial transfer of the value.
• With the subsequent change of the clock signal from LOW to HIGH level (2), transfer of the position
value begins with the most significant bit (MSB).
• With each subsequent change of the clock signal from LOW to HIGH level, the next least-significant bit is transmitted on the data line.
• After the least significant bit (LSB) has been output, the clock signal switches from LOW to HIGH
for one last time and the data line switches to LOW level (end of transmission).
• A monoflop retriggered by the clock signal determines how long before the SSI interface can be
called for the next transmission. This yields the minimum pause time between two successive clock
cycles (tm)
If time tm has elapsed, the data line is reset to bias level (HIGH) (3). This signals the fully completed
data exchange and renewed transmission-ready state.
• tm = 20 µs with master clock frequency 80 kHz - 800 kHz
• tm = 30 µs with master clock frequency 50 kHz - 79 kHz
• The update rate (50 µs to 2 ms) of the measurement values at the SSI interface can be configured
via the webConfig tool. Factory setting: 2 ms.
The update rate describes how quickly the data are replaced on the SSI interface by current data.
The measurement value is updated independent of the clock frequency.
Leuze electronic
BPS 307i
51
Basic configuration
3
4
1
7
5
2
6
9
10
9
8
1
2
3
4
5
6
7
8
9
10
Figure 8.1:
CLOCK
DATA
Clock sequence
First HIGH-LOW edge
Change LOW level to HIGH level
Bias level (HIGH)
TSSI (1/fSSI)
Tm = 20 µs or 30 µs
MSB
LSB (0)
SSI data transmission sequence diagram
If the off-cycle of data transmission is interrupted for longer than tm = 20 µs or tm = 30 µs , a completely new transmission cycle starts on the next cycle.
If a new transmission cycle is started before time tm elapses, the previous value is output again.
NOTICE
Factory setting: only positive position and speed values with SSI!
 In the factory setting, the SSI interface can only represent positive position and speed values.
If negative output values are ascertained due to the orientation of the BPS to the BCB or the counting
direction, the value 0 is output at the SSI interface!
In the event of a number overflow, all data bits are set to 1.
Factory settings of the SSI interface parameters
• Data encoding of the measurement values: Gray
• Sign: binary representation
• Transmission mode: 24 measurement bits + 1 error bit
• Resolution position value: 1 mm
• Error bit: measurement error, LSB, 1 = active
• Value of the error bit:
The error bit is not included in the Gray encoding of the measurement value.
The error bit is 1 = active
• Update rate: 2 ms
• SSI master clock frequency: 80 kHz - 800 kHz
Leuze electronic
BPS 307i
52
Basic configuration
8.1.2
Setting the configuration of the SSI interface
 Set the parameters of the SSI interface via the webConfig tool or via connection hood MS 307 or
MK 307.
• Setting via the webConfig tool:
CONFIGURATION > OUTPUT; see chapter 9.3.2 "CONFIGURATION function"
• Setting via connection hood MS 307/MK 307:
see chapter 8.6 "Configuration via the switches of the connection hood"
Devices with connection hood KB 307 can only be configured via the webConfig tool.
8.2
Configuring the switching inputs/outputs
 Set the configuration of the switching inputs/outputs via the webConfig tool or via connection hood
MS 307 or MK 307.
• Setting via the webConfig tool:
CONFIGURATION > DEVICE; see chapter 9.3.2 "CONFIGURATION function"
• Setting via connection hood MS 307/MK 307:
see chapter 8.6 "Configuration via the switches of the connection hood"
Devices with connection hood KB 307 can only be configured via the webConfig tool.
8.3
Configuring the resolution for the position value
 Set the parameters for the resolution during position measurement via the webConfig tool or via connection hood MS 307 or MK 307.
• Setting via the webConfig tool:
CONFIGURATION > OUTPUT; see chapter 9.3.2 "CONFIGURATION function"
• Setting via connection hood MS 307/MK 307:
see chapter 8.6 "Configuration via the switches of the connection hood"
Devices with connection hood KB 307 can only be configured via the webConfig tool.
8.4
Configuring speed monitoring with switching output
 Set the parameters for speed monitoring via the webConfig tool or via connection hood MS 307 or
MK 307.
• Setting via the webConfig tool:
• Switching output function: CONFIGURATION > DEVICE > Switching inputs/outputs; see
chapter 9.3.2 "CONFIGURATION function"
• Speed limit values: CONFIGURATION > DATA PROCESSING > Speed > Monitoring; see
chapter 9.3.2 "CONFIGURATION function"
• Setting via connection hood MS 307/MK 307:
see chapter 8.6 "Configuration via the switches of the connection hood"
Devices with connection hood KB 307 can only be configured via the webConfig tool.
Leuze electronic
BPS 307i
53
Basic configuration
8.5
Setting tape selection via the webConfig tool
 In the webConfig tool (CONFIGURATION > MEASUREMENT DATA > Bar code tape), set the Tape
selection parameter according to the used bar code tape grid; see chapter 9.3.2 "CONFIGURATION
function".
• 30 mm grid
• 40 mm grid
8.6
Configuration via the switches of the connection hood
The following settings can be configured via the operational controls of connection hoods MS 307 and
MK 307:
• Resolution of the position value
• Data encoding of the measurement values: Gray or binary
• Speed monitoring via switching output (SWIO1)
The settings made via the operational controls of the connection hood can alternatively be configured via the webConfig tool; see chapter 9.3.2. To do this, rotary switch S2 must be set to
switch position 0.
If rotary switch S2 is set to switch position 0, slide switch S1 is not evaluated.
1
1
2
Figure 8.2:
Leuze electronic
2
Slide switch S1
Factory setting: Gray encoding
Hexadecimal rotary switch S2
Factory setting: 0, i.e., configuration via the webConfig tool
Operational controls of connection hood MS 307
BPS 307i
54
Basic configuration
1
1
Slide switch S1
Factory setting: Gray encoding
Hexadecimal rotary switch S2
Factory setting: switch position 0, i.e., configuration via webConfig tool
2
Figure 8.3:
2
Operational controls of connection hood MK 307
Slide switch S1
Change the measurement value encoding
• S1 up: Gray encoding
• S1 down: binary encoding
Rotary switch S2
NOTICE
Hexadecimal rotary switch S2 for setting the resolution and speed monitoring!
 Set the resolution of the position measurement and speed monitoring via rotary switch S2.
Table 8.1:
Configuration via rotary switch S2
Switch position
Position resolution
[mm]
0
Configuration via webConfig tool
1
0.01
webConfig
webConfig
webConfig
2
0.1
webConfig
webConfig
webConfig
3
1
webConfig
webConfig
webConfig
4
10
webConfig
webConfig
webConfig
5
webConfig
webConfig
webConfig
webConfig
6
webConfig
webConfig
webConfig
webConfig
Leuze electronic
Maximum speed
[m/s]
BPS 307i
Level of the switch- Speed monitoring
ing output
55
Basic configuration
Switch position
Position resolution
[mm]
Maximum speed
[m/s]
Level of the switch- Speed monitoring
ing output
7
webConfig
0.7
8
webConfig
2
9
webConfig
3
A
webConfig
4
F
Factory setting of the configuration parameters
Notice: Switch S1 must be set to switch position Gray encoding.
• HIGH
Current speed
Below maximum speed
• LOW
Current speed
Above maximum speed
Activated
Activated
Activated
Activated
webConfig: The parameter value set via the webConfig tool is used.
All parameters that are not influenced by the position of the switch are configured via the webConfig tool; see chapter 9.
In rotary switch positions 7, 8, 9 or A, the webConfig tool can be used, e.g., to change the resolution of the position measurement or invert the mode of the switching inputs/outputs.
NOTICE
Rotary switch S2 on 0 if configuring with the webConfig tool!
 To configure the BPS with the webConfig tool, rotary switch S2 on connection hood MK 307 or MS 307
must be set to switch position 0.
8.7
Setting configuration parameters to factory settings
Proceed as follows:
 Set slide switch S1 to switch position Gray encoding.
 Set rotary switch S2 to switch position F.
 Restart the BPS.
The current parameter set of the BPS is overwritten with the parameter set containing the factory settings.
Leuze electronic
BPS 307i
56
Basic configuration
8.8
Key factory settings of the BPS
Table 8.2:
Factory settings on delivery of the BPS
Parameter
Factory setting
Explanation
Measurement value
encoding
Gray
Data encoding of the measurement
values
Tape selection
BCB with 40 mm grid
Changeover between BCB with 30 mm
grid and BCB with 40 mm grid
Position measurement
Integration depth: 8
Number of successive measurements
that the BPS uses for position determination.
Resolution: 1 mm
Resolution of the position value in mm
Master clock frequency
80 kHz - 800 kHz
Request frequency of the control
(master)
Update rate
2 ms
Update rate of the measurement values on the SSI interface
SSI interface
Transmission mode
24 measurement bits + 1 error bit
Position resolution
1 mm
Resolution of the position value in mm
Error bit
Measurement error
LSB
1 = active
Value of the error bit:
• The error bit is not included in the
Gray encoding of the measurement value.
• The error bit is 1 = active
IO1
HIGH
Function: Position value invalid
Switching output - level controlled
If a valid position value cannot be
ascertained, the output is set
IO2
HIGH
Function: Preset teach
Switching input - edge-triggered
Transition 0 → 1: Read in preset value
Sw. inputs/outputs
Leuze electronic
BPS 307i
57
Leuze electronic webConfig tool – Extended configuration
9
Leuze electronic webConfig tool – Extended configuration
With the Leuze electronic webConfig tool, an operating-system independent, web-technology based,
graphical user interface is available for configuring the BPS.
The webConfig tool can be run on any Internet-ready PC. The webConfig tool uses HTTP as communication protocol and the client-side restriction to standard technologies (HTML, JavaScript and AJAX) that are
supported by modern browsers.
The webConfig tool is offered in the following languages:
German, English, French, Italian, Spanish
9.1
Installing software
In order for the BPS to be automatically detected by the connected PC, the USB driver must be installed
once on your PC. Administrator rights are required for driver installation.
If a USB driver for the webConfig tool is already installed on your computer, the USB driver does
not need to be installed again.
9.1.1
System requirements
Regularly update the operating system and the Internet browser.
Install the current Windows Service Packs.
Table 9.1:
9.1.2
webConfig system requirements
Operating system
Windows XP (Home Edition, Professional)
Windows Vista
Windows 7
Windows 8
Computer
PC with USB interface version 1.1 or higher
Graphics card
Min. 1024 x 768 pixels or higher resolution
Required disk space
for USB driver
10 MB
Internet browser
Internet Explorer version 8.0 or higher
Firefox version 4.0 or higher
Install USB driver
 Start your PC with administrator privileges and log on.
 Download the setup program from the Internet:
www.leuze.com > Products > Measuring Sensors > Sensors for Positioning > BPS 300i > (Name of the
BPS) > Tab Downloads > Software/driver.
 Start the setup program and follow the instructions.
Alternatively, you can manually install the LEO_RNDIS.inf USB driver.
Contact your network administrator if the installation fails.
Leuze electronic
BPS 307i
58
Leuze electronic webConfig tool – Extended configuration
9.2
Start webConfig tool
Prerequisite: The Leuze electronic USB driver for the webConfig tool is installed on the PC.
 Connect the operating voltage to the BPS.
 Connect the SERVICE USB interface of the BPS to the PC.
The connection to the SERVICE USB interface of the BPS is established via the PC-side USB interface.
Use a standard USB cable with one Type A plug and one Mini-B type plug.
 Start the webConfig tool using your PC's Internet browser with IP address 192.168.61.100
This is the default Leuze electronic service address for communication with bar code positioning systems of the BPS 300i series.
The webConfig start page appears on your PC.
1
1
Figure 9.1:
Changing the operating mode (Process - Service) (upper left)
The start page of the webConfig tool
The user interface of the webConfig tool is largely self-explanatory.
The webConfig tool is completely contained in the firmware of the BPS.
The pages and functions of the webConfig tool may appear and be displayed differently depending on the firmware version.
Clear browser history
The cache of the Internet browser must be deleted if different device types or devices with different firmware have been connected to the webConfig tool.
 Delete cookies and temporary Internet and website data from browser history before starting the
webConfig tool.
Example for Internet Explorer 10:
Settings > Security > Browser History > [Delete]
Note limit of Firefox sessions for version 17.0 and higher
If the limited number of Firefox sessions is exceeded, it may no longer be possible to address the BPS via
the webConfig tool.
 Do not use the refresh functions of the Internet browser:
[Shift] [F5] or [Shift] + mouse click
Leuze electronic
BPS 307i
59
Leuze electronic webConfig tool – Extended configuration
9.3
Short description of the webConfig tool
9.3.1
Overview
Operating modes
For configurations with the webConfig tool, you can switch between the following operating modes:
• Process
The BPS is connected to the control.
•
•
•
•
•
The process communication to the control is activated.
The switching inputs/outputs are activated.
The configuration cannot be changed.
PROCESS function available.
ALIGNMENT function not available.
• Service
•
•
•
•
•
The process communication to the control is interrupted.
The switching inputs/outputs are deactivated.
The configuration can be changed.
PROCESS function not available.
ALIGNMENT function available.
Functions
In the Process operating mode, the webConfig tool has the following main menus and functions:
• HOME
Information on the connected BPS as well as on installation.
This information corresponds to the information in the current technical description.
• CONFIGURATION (see chapter 9.3.2)
Information on the current BPS configuration – no change to the configuration:
• Display of the interface parameters
• Display of the output modules (value formatting)
• Selection of the used bar code tape (30 mm grid or 40 mm grid)
• Display of the tape value correction (deviation of the BCB from scaling)
• Display of the device components (switching inputs/outputs, display)
• Data processing (position/speed detection or monitoring, data preparation)
• Display of the warning threshold and the error threshold for the reading quality
• PROCESS
Check and save the current read data in process mode (see chapter 9.3.4).
• Tabular display of the following values:
Scan number, position, speed, reading quality, distance from BCB, info on the control label
In the Service operating mode, the webConfig tool also has the following main menus and functions:
• CONFIGURATION (see chapter 9.3.2)
•
•
•
•
•
•
Configuration of the interface parameters
Configuration of the output modules (value formatting)
Configuration of device components (switching inputs/outputs, display)
Selection of the used bar code tape
Configuration of the data processing (position/speed detection or monitoring, data preparation)
Configuration of the warning threshold and the error threshold for the reading quality
• ALIGNMENT (see chapter 9.3.3)
• Display of the following values:
Scan number, position, speed, quality, distance, number of labels in the scanning beam
• Graphical displays of the following values:
Position, speed, quality
• DIAGNOSTICS (see chapter 9.3.5)
• Event logging of warnings and errors.
• MAINTENANCE (see chapter 9.3.6)
Leuze electronic
BPS 307i
60
Leuze electronic webConfig tool – Extended configuration
• Firmware update
• User management
• Backup/Restore
9.3.2
CONFIGURATION function
NOTICE
Rotary switch S2 of MS 307 or MK 307 to 0 if configuring with the webConfig tool!
 To configure with the webConfig tool, set rotary switch S2 on connection hood MS 307 or MK 307 to
switch position 0; see chapter 8.1.
NOTICE
Configuration changes only in the Service operating mode!
 Changes made using the CONFIGURATION function can only be performed in the Service operating
mode.
Overview of the webConfig configuration functions
Figure 9.2:
CONFIGURATION webConfig function
Configuration of the SSI interface (OUTPUT tab)
The SSI parameters and the formatting of the SSI host interface are configured via the OUTPUT > HOST
formatting function.
Leuze electronic
BPS 307i
61
Leuze electronic webConfig tool – Extended configuration
Figure 9.3:
webConfig function OUTPUT > HOST formatting
SSI parameters
• Data encoding
Toggling the measurement value encoding: Gray or binary
For devices with connection hood MK 307 or MS 307, the measurement value encoding set here is
overwritten on device startup with the measurement value encoding set via slide switch S1; see
chapter 8.6.
• Position value
Number of data bits - position value
• Speed value
Number of data bits - speed value
• Sign
If changed to sign with magnitude, the BPS can also transmit negative position and speed values.
Formatting data output on the SSI interface
To format the data output, the symbols of the configured output modules are arranged in the desired order
in the SSI formatting area.
 Select the required output module in the Output modules area.
Click the symbol for the output module with the left mouse button and keep the mouse button pressed
down.
 Drag the symbol for the output module into the white field in the SSI formatting area and release the
mouse button (“drag and drop”).
 Use “drag and drop” to drag the symbols for all required output modules into the SSI formatting area.
 Arrange the symbols for the output modules in the SSI formatting area with the left mouse button in the
sequence required for the data output.
 Save the SSI formatting in the device.
Click the
Leuze electronic
symbol.
BPS 307i
62
Leuze electronic webConfig tool – Extended configuration
NOTICE
Set data bits in the SSI master!
 Set the configured number of data bits in the SSI master.
Figure 9.4:
Data output on the SSI interface
The webConfig tool can be used to output the following data modules via the SSI interface:
• Position value
Current position of the BPS.
• Status: Position value invalid
Signals that no valid position value can be ascertained.
• Status: Upper/lower position limit value 1/2
Signals a value above/below the position limit.
• Speed
Current speed of the BPS
• Status: Speed invalid
Signals that no valid speed can be ascertained.
• Status: speed limit value 1-4
Signals that speed limit value 1-4 has been exceeded or has not been met.
• Direction of movement
Signals the direction of movement of the BPS.
• Tape direction
Signals the orientation of the BPS to the BCB (0° or 180°).
• Status IO1, IO2
The status of the switching input/output is output.
Configuration of the switching inputs/outputs (DEVICE tab)
• I/O mode: switching input or switching output
• Output function
• Input function
• Timing functions
•
•
•
•
•
Signal delay
Pulse duration
Switch-on/switch-off delay
Debounce time
Inversion yes/no
Configuring switching outputs
 Select the function symbol for activation of the switching output in the Functions area.
 Use the left mouse button to drag the function symbol into the Activation window.
Leuze electronic
BPS 307i
63
Leuze electronic webConfig tool – Extended configuration
 Configure the timing; see chapter "Timing functions of the switching inputs/outputs".
 Save the configuration of the switching outputs in the device.
Click the
Figure 9.5:
symbol.
Configuration of the switching outputs
Possible signals via the switching outputs:
• Position limit 1/2
Signals a value above/below the position limit.
• Invalid position
Signals that no valid position can be ascertained.
• Speed limit
Signals a value above/below the speed limit.
• Speed limit value 1-4
Signals that speed limit value 1-4 has been exceeded or has not been met.
• Invalid speed
Signals that no valid speed can be ascertained.
• Quality warning threshold
Signals that the reading quality is less than the warning threshold.
• Quality error threshold
Signals that the reading quality is less than the error threshold.
• Device error
Signals a device error.
Configuring switching inputs
 Select the function of the switching input from the Function list:
• No function
• Start/stop measurement
• Teach preset
• Reset preset
Leuze electronic
BPS 307i
64
Leuze electronic webConfig tool – Extended configuration
 Configure the timing; see chapter "Timing functions of the switching inputs/outputs".
 Save the configuration of the switching inputs in the device.
Click the
Figure 9.6:
symbol.
Configuration of the switching inputs
Timing functions of the switching inputs/outputs
The timing functions (e.g., start-up delay) can only be configured with the webConfig tool.
• Start-up delay
With this setting, the output pulse is delayed by the specified time (in ms).
• Switch-on time
Defines the switch-on time period for the switching input. Any activated switch-off function then no
longer has any function.
If the output is deactivated via the switch-off signal before the start-up delay lapses, only a brief pulse
appears at the output following the start-up delay.
• Debounce time
Parameter for setting the software debounce time for the switching input. The definition of a
debounce time extends the signal transition time accordingly.
If this parameter has the value 0, no debouncing takes place. Otherwise, the set value corresponds
to the time (in ms) that the input signal must be present and stable.
• Switch-off delay
This parameter specifies the duration of the switch-off delay (in ms).
Leuze electronic
BPS 307i
65
Leuze electronic webConfig tool – Extended configuration
Configuration of the resolution for position and speed measurement on the SSI interface (OUTPUT tab,
Preparation > SSI)
Figure 9.7:
webConfig function OUTPUT > Preparation > SSI
• Position resolution
Resolution for the position value
• Speed resolution
Resolution for the speed value
Configuration of the bar code tape selection and tape value correction (MEASUREMENT DATA tab, Bar
code tape)
• Bar code tape with 30 mm grid or 40 mm grid
• Tape value correction
With this parameter, the deviation of the BCB from the correct millimeter scaling that arises from the
production process can be corrected.
Configuration of position detection (DATA PROCESSING tab, Position >Detection)
• Integration depth
Number of successive measurements that the BPS uses for position determination.
• Scaling free resolution
Free scaling of the output of the position values.
• Preset
A preset position value (preset value) is activated at an appropriate position.
• Offset
Output value=measurement value+offset
If a preset is active, this has priority over the offset.
• Error handling procedures
Parameters for the position value in case of failure.
Leuze electronic
BPS 307i
66
Leuze electronic webConfig tool – Extended configuration
Configuration of position monitoring (DATA PROCESSINGtab, Position >Monitoring)
• Position limit value 1/2
Signals that the position value is outside of the configured limit value range.
Configuration of speed detection (DATA PROCESSING tab, Speed > Detection)
• Speed measurement averaging
Measurement value preparation averages all speed values calculated during the selected period
(averaging) to yield a speed output value.
• Scaling free resolution
Free scaling of the output of the speed values.
• Error handling procedures
Parameters for the speed value in case of failure.
Configuration of speed monitoring (DATA PROCESSING tab, Measurement data > Speed > Monitoring)
• Speed limit value 1-4
Signals that the speed is outside of the configured limit value range.
Configuration of the measurement value display (DATA PROCESSING tab, General preparation)
Unit of measurement: metric or inch
• Counting direction
Count direction for position calculation or sign for speed calculation.
• Output mode sign
Output mode of the sign. Affects position value and speed output.
Configuration of monitoring of the reading quality (DATA PROCESSING tab, Reading quality)
• Warning threshold for reading quality in %
• Error threshold for reading quality in %
Configuration of the communication data (COMMUNICATION tab)
• Configuration of the SERVICE USB interface
• Selection of the master clock frequency according to the request frequency of the control (master):
• 80 kHz - 800 kHz
• 50 kHz - 79 kHz
• Update rate of the measurement values on the SSI interface. The measurement value is updated
independent of the clock frequency.
•
•
•
•
9.3.3
2 ms
1 ms
200 µs
50 µs
ALIGNMENT function
NOTICE
ALIGNMENT function only in the Service operating mode!
 The BPS can only be aligned using the ALIGNMENT function in the Service operating mode.
The ALIGNMENT function serves to simplify mounting and alignment of the BPS. The laser is to be activated via the Start icon so that the function can monitor and directly display the measurement values for
position and speed and determine the optimum installation location.
In addition, reading quality (in %), working distance and the number of labels in the scanning beam can be
displayed. Using this information, it is possible to assess how well the BPS is aligned with the BCB.
Leuze electronic
BPS 307i
67
Leuze electronic webConfig tool – Extended configuration
During output of the read results, the BPS is controlled by the webConfig tool.
Figure 9.8:
9.3.4
ALIGNMENT webConfig function
PROCESS function
The PROCESS function serves to control the current measurement data in the Process operating mode.
The measurement results are output in tabular form – strictly as monitor output.
The Pause/Start icon can be used to interrupt and resume monitor recording.
Leuze electronic
BPS 307i
68
Leuze electronic webConfig tool – Extended configuration
Figure 9.9:
9.3.5
PROCESS webConfig function
DIAGNOSTICS function
The DIAGNOSTICS function is available in the Process and Service operating modes.
The device event log is displayed with the DIAGNOSTICS function.
Figure 9.10: DIAGNOSTICS webConfig function
Leuze electronic
BPS 307i
69
Leuze electronic webConfig tool – Extended configuration
9.3.6
MAINTENANCE function
The MAINTENANCE function is only available in the Service operating mode.
Functionalities:
• User management
• Devices Backup/Restore
• Firmware update
• System clock
• Settings of the user interface
Figure 9.11: MAINTENANCE webConfig function
Leuze electronic
BPS 307i
70
Diagnostics and troubleshooting
10
Diagnostics and troubleshooting
10.1
What to do in case of failure?
After switching on the BPS, display elements (see chapter 3.3) assist in checking the proper function and
troubleshooting.
In case of error, you can determine the error from the LED displays. With the error message you can determine the cause of the error and initiate measures to rectify it.
 Switch off the system and leave it switched off.
 Analyze the cause of the error using the operation indicators, the error messages and the diagnostic
tools (also with the help of the webConfig tool, DIAGNOSTICS tab) and rectify the error.
NOTICE
Contact Leuze electronic subsidiary/customer service.
 If you are unable to rectify a fault, contact the Leuze electronic branch responsible for you or call the
Leuze electronic customer service (see chapter 12 "Service and support").
10.1.1 Diagnostics with webConfig tool
System events are displayed in the webConfig tool via the DIAGNOSTICS tab. Noteworthy system events
are recorded in the event log. Depending on their importance, the events are classified as info, warning,
error and critical error. The statistics counters detect the number of all recorded as well as non-acknowledged messages. With the message filters, the events can be filtered according to their status and their
class.
Figure 10.1: DIAGNOSTICS webConfig function
10.2
Operating indicators of the LEDs
You can ascertain general causes of errors via the PWR and BUS status LEDs (see table 10.4).
Leuze electronic
BPS 307i
71
Diagnostics and troubleshooting
Table 10.1:
PWR LED displays – causes and measures
Error
10.3
Possible cause
Measures
Off
• No supply voltage connected
to the device
• Hardware error
• Check supply voltage
• Contact Leuze electronic customer service (see chapter 12 "Service and support")
Red, flashing
• No bar code in the scanning
beam
• No valid measurement value
• Query BCB diagnostic data and carry out
the resulting measures (see table 10.5)
Orange, continuous
light
• Device in Service mode
• Reset the device to Process mode using
the webConfig tool
Error messages on the display
Via the optional display of the BPS, the device outputs the following possible error status information while
it has the BPS Info device status:
• System OK
BPS operating error-free.
• Warning
Warning message. Query the device status in the webConfig tool.
• Error
Device function is not ensured.
BPS Info
System OK
Figure 10.2: Example: Device status/error status information on the display
10.4
Checklist for causes of errors
Table 10.2:
Service interface errors – causes and measures
Error
webConfig does not
start
Leuze electronic
Possible cause
Measures
• Incorrectly connected interconnection cable
• Connected BPS is not recognized
• No communication via USB service interface
• Old webConfig configuration in
the browser cache
BPS 307i
• Check interconnection cable
• Install USB driver
• Clear browser history
72
Diagnostics and troubleshooting
Table 10.3:
Process interface errors – causes and measures
Error
Possible cause
Sporadic interface
error
Table 10.4:
• Check wiring for proper contacting
Check wiring:
• Check wire shielding
• Check wires used
• EMC coupling
• Observe contact quality of screwed or
soldered contacts in the wiring
• Avoid EMC coupling caused by power
cables laid parallel to device lines
• Separate laying of power and data communications cables
• Maximum cable length
exceeded
• Check cable lengths according to the
data rate
LED indicators - interface errors – causes and measures
Error
Possible cause
BUS LED “Off”
BUS LED “red
flashing”
Table 10.5:
Measures
Measures
• No supply voltage connected
to the device
• Check supply voltage
• Hardware error
• Send device to customer service
• Incorrect wiring
• Check wiring
• Communication error
• Check SSI parameters
• Carry out a reset on the control
• Different protocol settings
• Check protocol settings
Position measurement errors – causes and measures
Error
Possible cause
Measures
Measurement value
or reading quality is
continuously instable
• Soiling of the BPS optics
• Clean the optics of the BPS
Measurement value
or reading quality is
poor
• at certain position values
• always at the
same position
values
• Soiling of the bar code tape
• Clean the bar code tape
• Replace the bar code tape
No measurement
value can be determined
• No code in scanning beam
• Code not in the working range
of the BPS
• Align the scanning beam with the
bar code tape
• Align the BPS with the bar code tape
(working range 50 mm … 170 mm)
Faulty measurement value
• Wrong bar code tape
BCB grid different from BPS
configuration
• Change BPS configuration to the
bar code tape that is being used
Leuze electronic
BPS 307i
73
Care, maintenance and disposal
11
Care, maintenance and disposal
11.1
Cleaning
If there is dust on the BPS device:
 Clean the BPS device with a soft cloth; use a cleaning agent (commercially available glass cleaner) if
necessary.
NOTICE
Do not use aggressive cleaning agents!
 Do not use aggressive cleaning agents such as thinner or acetone for cleaning the BPS device.
Use of improper cleaning agents can damage the lens cover.
11.2
Servicing
The BPS does not normally require any maintenance by the operator.
Repairs to the device must only be carried out by the manufacturer.
 For repairs, contact your responsible Leuze electronic subsidiary or Leuze electronic customer service
(see chapter 12 "Service and support").
11.2.1 Firmware update
A firmware update can only be performed by Leuze electronic Service on-site or at the company headquarters.
 For firmware updates, contact your responsible Leuze electronic subsidiary or Leuze electronic customer service (see chapter 12).
11.2.2 BCB repair with repair kit
NOTICE
Do not use the BCB repair kit on a permanent basis!
 Use the bar code tape created with the repair kit only temporarily as an emergency solution.
The optical and mechanical properties of the self-printed bar code tape do not correspond to those of
the original bar code tape.
Self-printed bar code tape should not remain in the system on a permanent basis.
 Repair bar code tapes in lengths of 1 m can be ordered from Leuze electronic on request.
If a bar code tape was damaged, e.g., by falling parts, you can download a repair kit for the BCB from the
Internet.
www.leuze.com > Products > Measuring Sensors > Sensors for Positioning > BPS 300i > (Name of the
BPS) > Tab Downloads > Repair kit.
In the repair kit files, you will find all position values with 30 mm grid and 40 mm grid.
Layout:
• BCB8: 0.9 m of bar code tape is provided on each A4 sheet.
Five lines of 18 cm with six code-information segments of 30 mm each
Tape lengths: 0 … 500 m, 500 … 1000 m, 1000 … 1500 m … 2500 … 3000 m
• BCB: 1 m of bar code tape is provided on each A4 sheet.
Five lines of 20 cm with five code-information sections of 40 mm each
Tape lengths: 0 … 500 m, 500 … 1000 m, 1000 … 1500 m and 1500 … 2000 m
Replacing a section of defective bar code tape
 Determine the coding of the defective area.
 Print out the coding for the given area.
Leuze electronic
BPS 307i
74
Care, maintenance and disposal
 Affix the printed code over the defective section of bar code tape.
NOTICE
Printing coding
 Select only those pages that are actually required.
 Change the printer settings so that the bar code is not distorted.
 Check the print results and measure the distance between two bar codes (see figure 11.1 and see
figure 11.2):
BCB: 40 mm
BCB8: 30 mm
 Cut the code strips and arrange them next to one another. The code content must always increase or
decrease in increments of 30 mm or 40 mm.
Check that the printed values increase by 3 or 4.
40
000040
000044
000048
000052
Figure 11.1: Checking the print results of the BCB repair kit (40 mm grid)
30
BCB8
000018
BCB8
000021
BCB8
000024
BCB8
000027
BCB8
000030
Figure 11.2: Checking the print results of the BCB8 repair kit (30 mm grid)
11.3
Disposing
 For disposal observe the applicable national regulations regarding electronic components.
Leuze electronic
BPS 307i
75
Service and support
12
Service and support
24-hour on-call service at:
+49 (0) 7021 573 - 0
Service hotline:
+49 (0) 7021 573 - 123
Monday to Friday 8.00 a.m. to 5.00 p.m. (UTC+1)
E-mail:
service.identify@leuze.de
Repair service and returns:
Procedure and Internet form can be found at
www.leuze.com/repair
Return address for repairs:
Service center
Leuze electronic GmbH + Co. KG
In der Braike 1
D-73277 Owen / Germany
12.1
What to do should servicing be required?
NOTICE
Please use this chapter as a master copy if service is required!
 Enter the contact information and fax the form together with your service order to the fax number given
below.
Customer data (please complete)
Device type:
Serial number:
Firmware:
Display messages:
Status of LEDs:
Error description:
Company:
Contact person/department:
Phone (direct dial):
Fax:
Street/No:
ZIP code/City:
Country:
Leuze Service fax number:
+49 7021 573 - 199
Leuze electronic
BPS 307i
76
Technical data
13
Technical data
13.1
General specifications
Table 13.1:
Optics
Light source
Laser diode
Wavelength
655 nm
Life expectancy laser diode
100,000 h (typ. at +25 °C)
Beam deflection
Via rotating polygon wheel
Exit window
Glass
Laser class
2 acc. to IEC 60825-1:2007 (EN 60825-1:2008-05);
II acc. to CDRH (U.S. 21 CFR 1040.10 with deviations corresponding to "Laser Notice No. 50" from June 24, 2007)
Working range
50 mm … 170 mm
At a reading distance of 50 mm, the reading field width is
120 mm.
At a reading distance beyond 100 mm, the reading field
width is 160 mm (see figure 13.1, BPS reading field
curve).
100
75
50
25
1
-25
-50
-75
-100
0
25
50
75
100
125
150
175
200
225
250
275
30
2
1
2
Figure 13.1:
Leuze electronic
Reading field width [mm]
Reading distance [mm]
BPS reading field curve
BPS 307i
77
Technical data
Table 13.2:
Measurement data
Reproducibility (3 sigma)
0.15 mm
Response time
8 ms
Output time
2 ms
Basis for contouring error calculation
4 ms
Measurement range
0 … 10,000,000 mm
Max. traverse rate
10 m/s
Table 13.3:
Operating and display elements
Display
Monochromatic graphical display, 128 x 32 pixels,
With background lighting
Keyboard
Two buttons
LEDs
Two LEDs for power (PWR) and bus state (BUS),
two-colored (red/green)
Table 13.4:
Mechanical data
Housing
Diecast aluminum
Connection technology
• BPS with MS 307: M12 connectors
• BPS with MK 307: Terminal blocks with spring-cage
terminals (5-pin)
• BPS with KB 307: cable connection
Degree of protection
IP 65
Weight
Approx. 580 g (without connection hood)
Dimensions (without connection hood)
(H x W x D) 108.7 mm x 100.0 mm x 48.3 mm
Dimensions (with MS 307 connection hood) (H x W x D) 108.7 mm x 100.0 mm x 48.3 mm
Dimensions (with MK 307 connection hood) (H x W x D) 147.4 mm x 100.0 mm x 48.3 mm
Dimensions (with KB 307 connection hood) (H x W x D) 108.7 mm x 100.0 mm x 48.3 mm
Dimensions of MS 307 connection hood
(H x W x D) 64.0 mm x 43.5 mm x 33.5 mm
Dimensions of MK 307 connection hood
(H x W x D) 64.0 mm x 43.5 mm x 83.5 mm
Dimensions of KB 307 connection hood
(H x W x D) 64.0 mm x 43.5 mm x 18.1 mm
Table 13.5:
Environmental data
Air humidity
Max. 90% rel. humidity, non-condensing
Vibration
IEC 60068-2-6, test Fc
Shock
Continuous shock
IEC 60068-2-27, test Ea
Electromagnetic compatibility
IEC 61000-6-3
IEC 61000-6-2 (contains IEC 61000-4-2, -3, -4, -5, -6)
Leuze electronic
BPS 307i
78
Technical data
Table 13.6:
Certifications, conformity
Conformity
CE, CDRH
Certifications
UL 60950-1, CSA C 22.2 No. 60950-1
CAUTION
UL applications!
 For UL applications, use is only permitted in Class 2 circuits in accordance with the NEC (National
Electric Code).
13.1.1 BPS without heating
CAUTION
UL applications!
 For UL applications, use is only permitted in Class 2 circuits in accordance with the NEC (National
Electric Code).
Table 13.7:
Electrical equipment
Interface type
SSI
SSI clock rate (CLOCK): 50 kHz … 800 kHz
Service USB interface
Mini-B type USB 2.0 socket
Switching input / switching output
Two switching inputs/outputs
Switching input: 18 … 30 VDC depending on supply voltage, I max. = 8 mA
Switching output: 18 … 30 VDC, depending on supply
voltage, I max. = 60 mA (short-circuit proof)
Switching inputs/outputs protected against polarity reversal!
PWR LED green
Device ready (power on)
Operating voltage UB
18 … 30 VDC (Class 2, protection class III)
Power consumption
Max. 3.7 W
Table 13.8:
Ambient temperature
Ambient temperature (operation)
-5 °C … +50 °C
Ambient temperature (storage)
-35 °C … +70 °C
13.1.2 BPS with heating
CAUTION
UL applications!
 For UL applications, use is only permitted in Class 2 circuits in accordance with the NEC (National
Electric Code).
Leuze electronic
BPS 307i
79
Technical data
Table 13.9:
Operating voltage UB
18 … 30 VDC
Power consumption
Max. 17.7 W
Structure of the heating
Housing heating and separate heating of the optics glass
Warmup time
Minimum 30 min at +24 VDC and an ambient temperature
of -35 °C
Minimum conductor cross section
Conductor cross section of at least 0.75 mm² for the supply voltage supply line.
Note:
Wiring through of the voltage supply to multiple heating
devices is not permissible.
Standard, M12 ready-made cable not usable (insufficient
conductor cross section).
Table 13.10:
13.2
Electrical equipment
Ambient temperature
Ambient temperature (operation)
-35 °C … +50 °C
Ambient temperature (storage)
-35 °C … +70 °C
Bar code tape
Table 13.11:
BCB dimensions
BCB
BCB8
Grid
40 mm
30 mm
Standard height
47 mm
47 mm
Preferred heights
25 mm,
Special heights for lengths
greater than 150 m
25 mm, 30 mm, special
heights for lengths greater
than 150 m
Length
0 … 5 m, 0 … 10 m,
0 … 20 m, …, 0 … 150 m,
0 … 200 m;
Special lengths and special
codings for lengths greater
than 150 m (see chapter 14)
0 … 5 m, 0 … 10 m,
0 … 20 m, …, 0 … 150 m;
Special lengths and special
codings for lengths greater
than 150 m (see chapter 14)
Tape tolerance
1 mm per meter
1 mm per meter
NOTICE
Twin tapes on request
 Twin tapes can be ordered on request (see chapter 14).
Table 13.12:
BCB structure
Manufacturing process
Filmsetting
Surface protection
Polyester, matt
Base material
Polyester film, affixed without silicone
Leuze electronic
BPS 307i
80
Technical data
Adhesive
Acrylate adhesive
Strength of adhesive
0.1 mm
Adhesive strength (average values)
On aluminum: 25 N/25 mm
On steel: 25 N/25 mm
On polycarbonate: 22 N/25 mm
On polypropylene: 20 N/25 mm
Table 13.13:
BCB environmental data
Recommended processing temperature
0 °C … +45 °C
Ambient temperature
-40 °C … +120 °C
Dimensional stability
No shrinkage, tested according to DIN 30646
Curing
Final curing after 72 h;
the BPS can detect the position immediately after the BCB
is affixed.
Tear resistance
150 N
Elongation at tear
Min. 80%, tested in accordance with DIN 50014,
DIN 51220
Weathering resistance
UV-light, humidity, salt spray (150 h/5 %)
Chemical resistance
(checked at 23 °C over 24 h)
Transformer oil, diesel oil, white spirit, heptane, ethylene
glycol (1:1)
Behavior in fire
Self-extinguishing after 15 s, does not drip
Surface
Grease-free, dry, clean, smooth
Mechanical properties
Scratch and wipe resistant, UV resistant, moisture resistant, partly chemical resistant
Leuze electronic
BPS 307i
81
Technical data
13.3
Dimensioned drawings
2
2
1
1
2
Figure 13.2:
Leuze electronic
all dimensions in mm
Reference point for the bar code position
Optical axis
Dimensioned drawing BPS without connection hood
BPS 307i
82
Technical data
Dimensioned drawing BPS with MS 348 connection hood
all dimensions in mm
Figure 13.3:
Dimensioned drawing BPS with MS 307 connection hood
all dimensions in mm
Figure 13.4:
Leuze electronic
Dimensioned drawing BPS with MK 307 connection hood
BPS 307i
83
Technical data
all dimensions in mm
Figure 13.5:
13.4
Dimensioned drawing BPS with KB 307 connection hood
Dimensioned drawings: Accessories
all dimensions in mm
Figure 13.6:
Leuze electronic
Dimensioned drawing MS 307 connection hood
BPS 307i
84
Technical data
all dimensions in mm
Figure 13.7:
Dimensioned drawing MK 307 connection hood
all dimensions in mm
Figure 13.8:
Leuze electronic
Dimensioned drawing KB 307 connection hood
BPS 307i
85
Technical data
all dimensions in mm
Figure 13.9:
Dimensioned drawing BTU 0300M-W mounting device
all dimensions in mm
Figure 13.10: Dimensioned drawing BT 300-W mounting bracket
Leuze electronic
BPS 307i
86
Technical data
1
2
3
1
2
3
all dimensions in mm
Clamping jaws for mounting on the BPS
Clamp profile for fastening to round or oval pipes ( 16 … 20 mm)
Rod holder, turnable 360 °
Figure 13.11: Dimensioned drawing BT 56 mounting device
all dimensions in mm
Figure 13.12: Dimensioned drawing BT 300-1 mounting device
Leuze electronic
BPS 307i
87
Technical data
13.5
Dimensioned drawing bar code tape
1,28
47 ±0,2
38,72
000040
000044
000048
all dimensions in mm
Figure 13.13: Dimensioned drawing bar code tape BCB with 40 mm grid
1,28
47 ±0,2
28,72
BCB8
000018
BCB8
000021
BCB8
000024
all dimensions in mm
Figure 13.14: Dimensioned drawing bar code tape BCB8 with 30 mm grid
Leuze electronic
BPS 307i
88
Order guide and accessories
14
Order guide and accessories
14.1
BPS 307i type overview
Table 14.1:
14.2
14.3
BPS 307i type overview
Part no.
Part designation
Description
50125677
BPS 307i SM 100 D H
BPS with SSI interface, display and heating
50125678
BPS 307i SM 100 D
BPS with SSI interface and display
50125679
BPS 307i SM 100
BPS with SSI interface
50136334
BPS 307i SM 100 H
BPS with SSI interface and heating
Connection hoods
Table 14.2:
BPS connection hoods
Part no.
Part designation
Description
50126130
MS 307
Connection hood with M12 connectors
50126131
MK 307
Connection hood with spring-cage terminals
50126132
KB 307-3000
Connection hood with 3 m cable
50128803
KB 307-5000 FLEX
FLEX connection hood with FLEX cable, 5 m
50128804
KB 307-10000 FLEX
FLEX connection hood with FLEX cable, 10 m
Cables accessories
Table 14.3:
Accessories – PWR connection cable (voltage supply)
Part no.
Part designation
Description
50104557
K-D M12A-5P-5m-PVC
PWR connection cable, M12 socket for PWR, axial
plug outlet, open cable end, cable length 5 m, not
shielded
50104559
K-D M12A-5P-10m-PVC
PWR connection cable, M12 socket for PWR, axial
plug outlet, open cable end, cable length 10 m, not
shielded
Table 14.4:
Part no.
Accessories – SSI/Interbus connection cable (only for RS 232)
Part designation
Description
M12 plug for SSI/Interbus, axial connector, open line end
14.4
50104172
KB SSI/IBS-2000-BA
SSI/Interbus connection cable, length 2 m
50104171
KB SSI/IBS-5000-BA
SSI/Interbus connection cable, length 5 m
50104170
KB SSI/IBS-10000-BA
SSI/Interbus connection cable, length 10 m
50104169
KB SSI/IBS-15000-BA
SSI/Interbus connection cable, length 15 m
50108446
KB SSI/IBS-30000-BA
SSI/Interbus connection cable, length 30 m
Other accessories
Leuze electronic
BPS 307i
89
Order guide and accessories
Table 14.5:
Part no.
Part designation
Description
50020501
KD 095-5A
M12 axial socket for voltage supply, shielded
50038538
KD 02-5-BA
M12 axial socket, B-coded, for SSI, shielded
Table 14.6:
Accessory USB cable
Part no.
Part designation
Description
50117011
KB USBA-USBminiB
USB service cable, 1 Type A and Mini-B type connector, length 1 m
Table 14.7:
14.5
Accessories – BPS connectors
Mounting device accessories
Part no.
Part designation
Description
50124941
BTU 0300M-W
Mounting device for wall mounting – precise alignment of the BPS without adjustment (easy-mount).
50121433
BT 300 W
Mounting bracket for wall mounting
50027375
BT 56
Mounting device for rod
50121434
BT 300-1
Mounting device for rod
Bar code tapes
Table 14.8:
Accessories – BCB
Part no.
Part designation
Description
50038895
BCB 005
Bar code tape, 5 m length, 47 mm high
50040041
BCB 010
Bar code tape, 10 m length, 47 mm high
50037489
BCB 020
Bar code tape, 20 m length, 47 mm high
50037491
BCB 030
Bar code tape, 30 m length, 47 mm high
50037492
BCB 040
Bar code tape, 40 m length, 47 mm high
50038894
BCB 050
Bar code tape, 50 m length, 47 mm high
50038893
BCB 060
Bar code tape, 60 m length, 47 mm high
50038892
BCB 070
Bar code tape, 70 m length, 47 mm high
50038891
BCB 080
Bar code tape, 80 m length, 47 mm high
50038890
BCB 090
Bar code tape, 90 m length, 47 mm high
50037493
BCB 100
Bar code tape, 100 m length, 47 mm high
50040042
BCB 110
Bar code tape, 110 m length, 47 mm high
50040043
BCB 120
Bar code tape, 120 m length, 47 mm high
50040044
BCB 130
Bar code tape, 130 m length, 47 mm high
50040045
BCB 140
Bar code tape, 140 m length, 47 mm high
50040046
BCB 150
Bar code tape, 150 m length, 47 mm high
Leuze electronic
BPS 307i
90
Order guide and accessories
Part no.
Part designation
Description
50037494
BCB 200
Bar code tape, 200 m length, 47 mm high
50037495
BCB special length 47 mm height Bar code tape with special length, 47 mm high
50102600
BCB special length 25 mm height Bar code tape with special length, 25 mm high
50106979
BCB special length / height
Bar code tape with special length and height
50111786
BCB special length / height /
winding
Bar code tape with special length, height and
wrapping direction
50106478
MVS label 40 mm 10 pieces
MVS label, 40 mm grid; packaging unit: 10 pieces
50126134
MV0 label 40 mm 10 pieces
MV0 label, 40 mm grid; packaging unit: 10 pieces
50106473
Repair kit 40 mm
Repair kit, 40 mm grid
Table 14.9:
Accessories – BCB8
Part no.
Part designation
Description
50104792
BCB8 010
Bar code tape, 10 m length, 47 mm high
50104793
BCB8 020
Bar code tape, 20 m length, 47 mm high
50104794
BCB8 030
Bar code tape, 30 m length, 47 mm high
50104795
BCB8 040
Bar code tape, 40 m length, 47 mm high
50104796
BCB8 050
Bar code tape, 50 m length, 47 mm high
50104797
BCB8 060
Bar code tape, 60 m length, 47 mm high
50104798
BCB8 070
Bar code tape, 70 m length, 47 mm high
50104799
BCB8 080
Bar code tape, 80 m length, 47 mm high
50104800
BCB8 090
Bar code tape, 90 m length, 47 mm high
50104801
BCB8 100
Bar code tape, 100 m length, 47 mm high
50104802
BCB8 110
Bar code tape, 110 m length, 47 mm high
50104803
BCB8 120
Bar code tape, 120 m length, 47 mm high
50104804
BCB8 130
Bar code tape, 130 m length, 47 mm high
50104805
BCB8 140
Bar code tape, 140 m length, 47 mm high
50104806
BCB8 150
Bar code tape, 150 m length, 47 mm high
50104807
BCB8 special length 47 mm
height
Bar code tape with special length, 47 mm high
50104808
BCB8 special length 30 mm
height
Bar code tape with special length, 30 mm high
50104809
BCB8 special length 25 mm
height
Bar code tape with special length, 25 mm high
50106980
BCB8 special length / height
Bar code tape with special length and height
Leuze electronic
BPS 307i
91
Order guide and accessories
Part no.
Part designation
Description
50106476
MVS label 30 mm 10 pieces
MVS label, 30 mm grid; packaging unit: 10 pieces
50126135
MV0 label 30 mm 10 pieces
MV0 label, 30 mm grid; packaging unit: 10 pieces
50106472
Repair kit 30 mm
Repair kit, 30 mm grid
Table 14.10:
Accessories – twin tapes
Part no.
Part designation
Description
50120378
BCB twin tape special length /
height
BCB twin tape, 40 mm grid, with special length
and high; delivery contents: 2 bar code tapes with
the same value range
50120379
BCB8 twin tape special length /
height
BCB8 twin tape, 30 mm grid, with special length
and high; delivery contents: 2 bar code tapes with
the same value range
50120380
BCB twin tape special length
BCB twin tape, 40 mm grid, 47 mm high; delivery
contents: 2 bar code tapes with the same value
range
50120381
BCB8 twin tape special length
BCB8 twin tape, 30 mm grid, 47 mm high; delivery
contents: 2 bar code tapes with the same value
range
Leuze electronic
BPS 307i
92
EC Declaration of Conformity
15
EC Declaration of Conformity
The bar code positioning systems of the BPS 300 series have been developed and manufactured in accordance with the applicable European standards and directives.
The manufacturer of the product, Leuze electronic GmbH + Co. KG in D-73277 Owen, possesses a certified quality assurance system in accordance with ISO 9001.
Leuze electronic
BPS 307i
93
Appendix
16
Appendix
16.1
BCB bar code tape with 40 mm grid
000000
000004
000008
000012
Figure 16.1: Continuous, 40 mm grid
Figure 16.2: Single label MVS, 40 mm grid
Figure 16.3: Single label MV0, 40 mm grid
Figure 16.4: Single marker label, 40 mm grid
Leuze electronic
BPS 307i
94
Appendix
16.2
Bar code tape BCB8 with 30 mm grid
BCB8
000000
BCB8
000003
BCB8
000006
BCB8
000009
BCB8
000012
Figure 16.5: Continuous, 30 mm grid
Figure 16.6: Single label MVS, 30 mm grid
Figure 16.7: Single label MV0, 30 mm grid
Figure 16.8: Single marker label, 30 mm grid
Leuze electronic
BPS 307i
95