User manual
ONLINE YUNTO series
Models 500 – 1500
Germany
Italy
Switzerland
ONLINE USV-Systeme AG
Luise-Ullrich-Str. 8
D-82031 Grünwald
ONLINE UPS-Systems S.r.l.
Via Ferruccio Gilera 110
I-20862 Arcore (MB)
ONLINE USV-Systeme AG
c/o POTESTA AG
Hertistrasse 29
8304 Wallisellen (Zürich)
Phone +49 (89) 2423990-10
Fax
+49 (89) 2423990-20
Phone +39 (039) 2051444
Fax
+39 (039) 2051435
Phone
Fax
www.online-usv.de
www.online-ups.it
www.online-usv.ch
1 / 22
Y500-1500_usermanual_engl_20180312
+49 (89) 242399010
+49 (89) 242399020
Content
User manual ...................................................................................... 1
1. Introduction ................................................................................. 4
2. Safety warnings .......................................................................... 6
3. Installation .................................................................................. 7
3.1
Checking the delivery .......................................................... 7
3.2
Unpacking the UPS system ................................................ 7
3.3
Checking the accessories ................................................... 8
3.4
Installation and setup .......................................................... 8
4. Functions and controls ............................................................. 10
5. Communication and interfaces ................................................. 11
5.1
USB interface .................................................................... 11
5.2
Surge voltage protection for data and telephone
lines (DSL / telephone / fax / network) .............................. 11
5.3
DataWatch software .......................................................... 11
6. Maintenance ............................................................................. 13
6.1
Care and maintenance ...................................................... 13
6.2
Storage .............................................................................. 13
6.3
Replacing the batteries ..................................................... 13
6.4
Disposing of the old batteries or UPS system ................... 15
7. Troubleshooting ........................................................................ 16
8. Support ..................................................................................... 17
9. Technical data .......................................................................... 18
9.1
Specification ...................................................................... 18
9.2
Rear view .......................................................................... 20
9.3
CE confirmation ................................................................. 21
10. Warranty ................................................................................... 22
List of Illustrations
Figure1: YUNTO 500 - 800 ................................................................. 5
Figure 2: YUNTO 1200 - 1500 ............................................................ 5
Figure 3: Control panel and display .................................................. 10
Figure 4: Rear view of YUNTO 500 - 800......................................... 20
Figure 5: Rear view of YUNTO 1200 - 1500..................................... 20
2 / 22
Y500-1500_usermanual_engl_20180312
List of tables
Table 1: Package contents ................................................................. 8
Table 2: Descriptions of display ........................................................ 10
Table 3: Troubleshooting .................................................................. 16
Table 4: Specification ....................................................................... 19
3 / 22
Y500-1500_usermanual_engl_20180312
INTRODUCTION
1. Introduction
ONLINE USV-Systeme AG (ONLINE) is one of the leading manufacturers of uninterruptible power supplies (UPS). Since 1988, the German company has focussed on the development, production, sale and
support of UPS systems. Based on unit numbers sold, ONLINE products are the German number one in the UPS market and internationally recognised because of their top quality and excellent support.
The power supply often fails when you least expect it. There can also
be significant fluctuation in the quality of the power supply. Network
problems can lead to the destruction of critical data, data which is not
backed up can be lost and hardware damaged. This means expensive
repairs and downtime.
With models from the YUNTO series from ONLINE, you are perfectly
prepared for such eventualities. YUNTO protects sensitive applications from data loss and operating downtime, whether they are pricesensitive entry servers or high-end PCs, telephone systems, network
peripherals or NAS boxes.
YUNTO offers the following advantages:
•
•
•
•
•
•
•
•
•
•
Compact design
Silent operation
Cold start function, starts the UPS system without network voltage
Intelligent battery management, self test and fast charge function
Surge protection for data and telephone wires
Alarm function
USB interface
Built-in wall mount
Inc. shutdown, management and monitoring software, DataWatch to download for all operating systems
2 years warranty incl. battery and 24h advance replacement
4 / 22
Y500-1500_usermanual_engl_20180312
INTRODUCTION
Figure1: YUNTO 500 - 800
Figure 2: YUNTO 1200 - 1500
5 / 22
Y500-1500_usermanual_engl_20180312
SAFETY WARNINGS
2. Safety warnings
This manual contains important instructions that you must follow during the installation and maintenance of the UPS system and the batteries. Please read all the instructions in the manual before working
with the device. Keep the manual in a safe place.
CAUTION
•
The UPS system carries life-threatening voltages. All repair
and maintenance work must be carried out by customer service personnel.
•
The UPS system has its own energy source (batteries). The
output of the UPS system can be live even when the UPS system is not connected to a wall outlet.
•
In order to reduce the risk of fire or electric shock, the UPS
system may only be installed in buildings with controlled temperature and air humidity in which there are no conductive
contaminants. The ambient temperature must not exceed
40°C. The UPS system must not be operated near water or in
extremely high air humidity (>90%).
•
Before transporting the UPS system, make sure that it is disconnected from the power supply and switched off.
•
Batteries can pose a risk of electric shock or catch fire as a
result of high short circuit current. Please take the necessary
precautionary measures. Maintenance must be carried out by
qualified personnel who are trained in handling batteries and
have good knowledge of the necessary precautionary
measures, see Chapter 6 Maintenance. Keep unauthorised
personnel away from batteries
•
Batteries must be disposed of properly. Local regulations must
be taken into consideration.
•
Batteries must not be burnt. There is risk of explosion.
6 / 22
Y500-1500_usermanual_engl_20180312
INSTALLATION
3. Installation
3.1 Checking the delivery
Keep the transport box and the packaging material for the carrier or
sales point. If parts of the system have been damaged in transit, submit a transport damage complaint to your supplier within 24 hours. If
you only discover damage after accepting the device, please submit a
complain for concealed damage.
3.2 Unpacking the UPS system
CAUTION
Unpacking the UPS system at a low ambient temperature can
lead to the formation of condensation inside and outside the
casing. Only install the UPS system if the inside and outside
are completely dry (risk of electric shock).
PLEASE NOTE
Move and open the packaged UPS system carefully. Leave
the components in their packaging until they are installed.
To unpack the UPS system and accessories:
1. Open the external box and take the accessories packed with
the UPS system out.
2. Carefully lift the UPS system out of the external box.
3. Place the UPS system in a protected, adequately ventilated position which is free of humidity, flammable gasses and corrosion.
4. In order to avoid interference with other devices, make sure to
maintain a clearance of at least 20 cm.
7 / 22
Y500-1500_usermanual_engl_20180312
INSTALLATION
YUNTO 1200
YUNTO 1500
USB interface cable
10A power extension cable
Quick start guide
DataWatch software*
Manual*
*Download from www.online-ups.com
YUNTO 800
Description
YUNTO 500
3.3 Checking the accessories
1
2
1
1
2
1
1
2
1
1
2
1
Table 1: Package contents
3.4 Installation and setup
The UPS system is delivered fully assembled.
CAUTION
Make sure that the overall rated performance of the load
connected does not exceed the capacity of the UPS system.
The power consumption of inductive loads or laser printers
can be very high, please take this into consideration when
specifying your UPS system.
1. Connect the load with the UPS system without switching them
on.
2. Connect the mains connection cable for the UPS system into a
socket.
3. Press the
button on the UPS system until a short beep
sounds and the status LED
lights up.
4. The UPS system is now operating in normal mode and supplying the load with reliable power.
5. Switch the loads on one by one.
8 / 22
Y500-1500_usermanual_engl_20180312
INSTALLATION
PLEASE NOTE
The internal batteries charge up to 90% of their full capacity in
less than eight hours. ONLINE recommends charging the batteries for 48 hours after installation or extended periods of
non-use.
The battery charging starts as soon as the UPS system is connected to the supply network and switched on.
Starting in battery mode
1. Press the
button on the UPS system until a short beep
sounds and the status LED
lights up.
2. The UPS system is starting, the display then shows the battery
statues (see Chapter 4 Battery statuses) and supplies the loads
connected with reliable power.
3. If the
display is lit, fix all warnings (see Chapter 7 Troubleshooting) and restart the UPS system.
Switching off
1. Press the
off switch on the UPS system. The UPS system
switches off.
2. Disconnect the mains connection cable of the UPS system from
the socket.
9 / 22
Y500-1500_usermanual_engl_20180312
FUNCTIONS AND CONTROLS
4. Functions and controls
Together with the beeps, the LEDs on the front of the device indicate
the operating status of the UPS.
Figure 3: Control panel and display
Switch / LED
Function
Alarm
Switch on/off
Normal operating mode:
Green LED permanently lit
Battery mode:
Green LED flashes every 10 seconds
Battery voltage low:
Green LED flashes every second,
red LED permanently lit
Error:
Red LED permanently lit
Temperature too high:
Red LED flashes every 0.5 seconds
Table 2: Descriptions of display
10 / 22
Y500-1500_usermanual_engl_20180312
Every 10 seconds
Every second
Continuous tone
COMMUNICATION AND INTERFACES
5. Communication and interfaces
5.1 USB interface
In order to establish communication between the UPS system and a
computer, connect the computer using a suitable data cable (cable
provided) to the USB interface on the UPS system (see Chapter 9.2
Rear view).
The UPS system can then exchange data via the DataWatch software
(see Chapter DataWatch software).
5.2 Surge voltage protection for data and telephone
lines (DSL / telephone / fax / network)
The surge protection filters surge voltage from the data and telephone
cables. This involves connecting the incoming cable to the IN connection on the reverse of the UPS system. Connect the OUT connection
to the end device. The data connection protection cable protects networks with a transfer rate of 10 to 1000 Mbit/s.
5.3 DataWatch software
The YUNTO series is supplied as standard with DataWatch, the comprehensive software solution for shutdown and management of the PC
or server system and for monitoring the YUNTO and the power supply
network. To ensure you are always working with the latest version of
DataWatch, please download it from the download area of
www.online-usv.de.
DataWatch works in the background and is in constant communication
with the YUNTO via the USB protocol. The most famous of all functions: Automatic data backup including the shutdown of running applications and the proper shutdown of the whole system by means of a
freely configurable shutdown routine. At the same time, DataWatch
has a comprehensive messaging system, time-controlled test routines
and event logging.
DataWatch supports all current operating systems.
11 / 22
Y500-1500_usermanual_engl_20180312
COMMUNICATION AND INTERFACES
As a client/server application, DataWatch works in networks and on
local workstations. Based on optional RCCMD agent (Remote Console Command), multiple servers connected to a UPS system can be
addressed and controlled across the network without additional hardware.
12 / 22
Y500-1500_usermanual_engl_20180312
MAINTENANCE
6. Maintenance
6.1 Care and maintenance
To ensure a long service life of the system, the area around the UPS
system should be kept clean and free of dust. If the area around the
system is very dusty, clean the external surfaces of the system with a
vacuum cleaner.
To ensure a long service life for the batteries, the ambient temperature
should not exceed 25°C.
PLEASE NOTE
•
Before transporting the UPS system, make sure that it is disconnected from the supply network and switched off.
•
The service life of a battery varies as a function of how often it
is used, intensity of use and ambient temperature. Batteries
which are used beyond their expected service life often have
reduced autonomy times. Replace the batteries in good time
to ensure the system always runs at optimum performance.
6.2 Storage
If you intend to store the UPS system for an extended period, charge
the battery every three months by connecting the UPS system to the
supply network for five hours. The system should be stored in a cool,
dry place.
6.3 Replacing the batteries
PLEASE NOTE
Do not replace the batteries while the UPS system is in battery
mode.
To replace the batteries, the UPS system bust be switched off, disconnected from the power supply and opened. Batteries cannot be hotswapped.
13 / 22
Y500-1500_usermanual_engl_20180312
MAINTENANCE
CAUTION
•
Maintenance work must be carried out by a qualified technician who is familiar with batteries and the necessary safety
measures. Do not allow unauthorised personnel to handle the
batteries.
•
Batteries pose the risk of an electric shock or injury due to high
short circuit current. Take the following safety measures:
o remove watches, jewellery and other metal items
o only use tools with insulated handles
o do not place tools or metal components on the batteries
•
The batteries must only be replaced with the same number of
batteries of the same type.
•
Batteries must be properly disposed of. When disposing of
batteries, comply with the statutory regulations applicable in
your location.
•
Batteries must not be burnt. There is risk of explosion.
•
Do not open or damage the battery or batteries. Battery acid
can damage the eyes and skin and cause poisoning.
14 / 22
Y500-1500_usermanual_engl_20180312
MAINTENANCE
CAUTION
•
DANGER OF ELECTRIC SHOCK. Never make changes to
the battery cabling or connections. Attempting to change the
battery cabling yourself could lead to serious injury.
•
The batteries of the UPS system are very heavy. Be careful
when handling heavy batteries.
6.4 Disposing of the old batteries or UPS system
Find out from a local recycling centre how the old batteries or the UPS
system should properly be disposed of. Old batteries can also be returned to ONLINE for disposal free of charge. Please contact Support
(see Chapter 8 Support).
CAUTION
•
Batteries must not be burnt. There is risk of explosion.
•
Batteries must be disposed of properly. Find out about the local disposal regulations.
•
Do not open or damage the battery or batteries. Battery acid
can damage the eyes and skin and cause poisoning.
15 / 22
Y500-1500_usermanual_engl_20180312
TROUBLESHOOTING
7. Troubleshooting
The YUNTO is designed for autonomous operation and automatically
reports any problems in the display.
Operating status
No LED display on the
front panel.
Permanent alarm beep
and red
LED while
mains voltage is available.
Possible cause
The battery capacity is
too low.
The battery is worn
through age or faulty.
The UPS system is not
switched on.
The UPS system is overloaded.
Error
Alarm sounds every 2
seconds while network
voltage available.
The battery is worn
through age or faulty.
Charger faulty.
Autonomy time is shorter
than expected.
The UPS system is overloaded.
LED flashing with normal
network voltage.
The battery capacity is
too low.
The battery is worn
through age or faulty.
Mains cable not connected properly.
Table 3: Troubleshooting
16 / 22
Y500-1500_usermanual_engl_20180312
Measure
Charge the battery for at
least 8 hours.
Replace the battery (see
Chap. 6.3).
Press the ON button.
Check whether the total
load exceeds the capacity of the UPS system.
Reduce the load as required.
Contact ONLINE support
(see Chapter 8).
Replace the battery (see
Chap. 6.3).
Contact ONLINE support
(see Chapter 8).
Check whether the total
load exceeds the capacity of the UPS system.
Reduce the load as required.
Charge the battery for at
least 8 hours.
Replace the battery (see
Chap. 6.3).
Check the mains cable
and connect it properly.
SUPPORT
8. Support
ONLINE USV-Systeme AG (ONLINE) is one of the leading manufacturers of uninterruptible power supplies (UPS). Since 1988, the German company has focussed on the development, production, sale and
support of UPS systems. Based on unit numbers sold, ONLINE products are the German number one in the UPS market and internationally recognised because of their top quality and excellent support.
As a German provider, ONLINE guarantees direct approachability,
simple processing and short response times. Comprehensive support
is a matter of course - before and after purchase.
ONLINE sets great store by reliable support and service.
•
•
•
•
•
•
Free direct advice and support on:
Software hotline: +49 (89) 242 39 90 - 13
Hardware hotline: +49 (89) 242 39 90 - 18
Free 24 h advance exchange
Interactive UPS configurator online or as app
2 years full warranty, optional renewal
Unbureaucratic 14 day money-back guarantee
Excellent product availability and wide network of distributors.
Further information: www.online-usv.de
17 / 22
Y500-1500_usermanual_engl_20180312
TECHNICAL DATA
9. Technical data
9.1 Specification
Model
Order no.
Electrical characteristics
Rated power (VA / W)
Input voltage and tolerance in normal mode
Frequency
Max. input current
Cold-start function
Output voltage
Output frequency
Battery operation
Wave form
Efficiency,
Normal operation
Battery mode
Power loss, max.
Connections
Input
Outputs, 10A
Batteries
Typ. Autonomy times at
50 and 100% load and
pf=0.6
Battery type
Design
Charge current
Charging time
Communication
USB
Modem / Network
Over-voltage protection
YUNTO
500
YUNTO
800
YUNTO
1200
YUNTO
1500
Y500
Y800
Y1200
Y1500
500 / 300
800 / 480
1200 / 720
1500 / 900
230V (180 – 270V)
50 / 60Hz (automatic detection) +/-5Hz
3.3A
5.2A
7.8A
9.7A
Yes
230V +/-10%
50 / 60Hz +/-1Hz
Simulated sine
>95%
70%
15W
3x IEC320
C13 (10A)
24W
36W
1x IEC320 C14 (10A)
3x IEC320
5x IEC320
C13 (10A)
C13 (10A)
6/3
6 / 2.5
6/3
45W
5x IEC320
C13 (10A)
6 / 2.5
1x 12V /
1x 12V /
2x 12V /
2x 12V /
7Ah
9h
7Ah
9Ah
Sealed, maintenance-free, valve-controlled,
lead/acid, life expectancy 3 to 5 years in accordance
with EUROBAT
0.5A
< 8 hours to 90%
Yes
Yes
18 / 22
Y500-1500_usermanual_engl_20180312
TECHNICAL DATA
Operating conditions, standards and approvals
Operating temperature
0 - 40°C
Storage temperature
-15 - 50°C
Rel. air humidity
0 – 90%
Noise level
silent
Safety
EN62040-1: 2008 +A1: 2013
EMC, Performance
EN62040-2: 2006
Approval
CE
Protection class
IP20
Dimensions / Weight
Dimensions (W x H x D)
80.1 x 177.5 x 232
90.9 x 238.7 x 282
Weight
3kg
3.5kg
5.4kg
6.3kg
Table 4: Specification
19 / 22
Y500-1500_usermanual_engl_20180312
TECHNICAL DATA
9.2 Rear view
Figure 4: Rear view of YUNTO 500 - 800
Figure 5: Rear view of YUNTO 1200 - 1500
20 / 22
Y500-1500_usermanual_engl_20180312
TECHNICAL DATA
9.3 CE confirmation
21 / 22
Y500-1500_usermanual_engl_20180312
WARRANTY
10. Warranty
ONLINE USV-Syteme AG (ONLINE) guarantees that this product will
be free of material and production faults for a period of two years from
the purchase date. ONLINE’s obligation in accordance with this guarantee is restricted to the repair or replacement (at ONLINE’s discretion) of any faulty products. Before warranty claims can be asserted,
a Returned Material Authorization (RMA) number must be obtained
from customer services. Products must be returned with the postage
paid by the sender, a brief description of the problem and evidence of
the place and date of purchase. This warranty does not apply to devices damaged by accidents, negligence or misuse or those which
have otherwise been altered or modified.
Apart from the above exceptions, ONLINE accepts no explicit or tacit
warranty, including a guarantee of conventional quality or suitability for
a specific purpose. In some jurisdictions, the restriction or exclusion of
tacit guarantees is prohibited, which means that the restrictions or exclusions above may not apply to the purchaser.
Irrespective of the above exclusions, ONLINE shall under no circumstances for direct, indirect, specific, auxiliary or subsequent damage
caused as a result of the use of this product, even if ONLINE was
informed about the possibility of such damage. In particular, ONLINE
shall not be liable for costs of whatsoever nature, such as lost profit or
revenue, loss of equipment, loss of the use of device, loss of software
or data, replacement costs, third-party claims or other costs.
The content is copyright © 2017 by ONLINE USV-Systeme AG. All
rights reserved. Unauthorised reproduction in part or in whole is not
permitted without consent.