Delta UPS – Agilon Family
VX Series, Line-interactive
No.
Item
1
LED Indicator
(Only For 600VA Model)
LCD Touch Panel (Only For
1000VA/ 1500VA Model)
600-1500 VA
2
Installation & Operation Quick Guide
3
ENGLISH
1 Package Inspection
No.
ON/ OFF Button
Output Socket
4
AC Input
5
Fuse
6
USB Port
7
Cooling Fan
(Only For 1500VA Model)
yyConnect to Utility Power
Q'ty
1
UPS
1 PC
2
Quick Guide
1 PC
3
USB Cable
1 PC
Connect the AC power cord to the utility power. Then, the UPS will start
to charge its inside battery (batteries). For best result, charge the battery
(batteries) for 6 hours prior to initial use. It is not recommended to connect
the UPS’s AC power cord to any generator.
Remove the UPS from its package and inspect it for damage that may have
occurred during shipping. If any damage is discovered, re-pack the unit and
return it to the place of purchase.
yyPlug in Equipment
Plug your equipment to the Output Socket on the rear panel of the UPS.
WARNING: 1. Make sure that the UPS is powered on to protect all important
devices from data loss during power failure.
2. NEVER connect a laser printer or scanner to the Output
Socket of the UPS. The equipment may draw significant
power to overload the UPS.
2 Front Panel & Rear Panel
600VA
(Front Panel)
(Rear Panel)
2
4 LED Indicator (Only For 600VA Model)
Item
3 Operation
Item
1
No.
yyConnect to USB Port and Install Software
6
5
4
3
Connect one end of the supplied USB cable to your PC and the other to
the USB port located at the rear of the UPS. Download the latest version of
ViewPower software (http://www.deltapowersolutions.com/en/mcis/600va1500va-single-phase-ups-vx-series-software-download.php) to your hard
drive. Follow on-screen instructions to complete the software installation.
yyTurn On/ Off the UPS
1000VA
(Front Panel)
When the UPS is OFF, press the ON/ OFF Button to turn on the UPS and
the LED/ LCD will be on. When the UPS is ON, press the ON/ OFF Button
to turn off the UPS and the LED/ LCD will shut off.
(Rear Panel)
1
6
2
4
Alarm
ON
OFF
ON
Sounds all the time
Flashing
Sounds every
10 seconds
Flashing
Sounds every second
OFF
OFF
(Front Panel)
When the UPS always runs in battery mode, it might be because the fuse
is damaged. If yes, please follow the following procedures to replace the
fuse.
3
Remove the fuse cover from the rear panel.
2
7
UPS Mode
2
Replace the original fuse
1
with the provided backup fuse
3
2
.
(Install)
2
(Take Out)
3
www.deltapowersolutions.com
Low battery.
The UPS is off.
LCD Touch Panel
LCD information will be
displayed in the following
order when the LCD
is touched.
AC Mode
When AVR is functioning,
icon will flash every
second.
Overload
In AC
Mode
Put the fuse cover back to the rear panel.
Description
When the UPS is powered
on, it will enter this mode for
4 seconds.
UPS
Power On
icon will flash.
Battery
Mode
Overload
In Battery
Mode
(Fuse Cover)
1
5
Power failure occurs and the
UPS runs in battery mode.
When battery level is low,
icon will flash.
6
4
UPS fault.
yyOperation Display:
(1500VA)
(Rear Panel)
1
The main AC power is normal
and the UPS runs normally.
5 LCD Display (Only For 1000VA/ 1500VA Model)
(Pull)
1500VA
UPS Status
yyFuse Replacement
1
5
LED
icon will flash.
1. Output voltage
2. Input voltage
3. Load level
4. Battery capacity
When overload occurs,
alarm will beep every 0.5
second.
Alarm will beep every
10 seconds and LCD
information will be displayed
in the following order
when the LCD is touched.
1. Output voltage
2. Input voltage
3. Load level
4. Battery capacity
When overload occurs,
alarm will beep every 0.5
second.
NOTE:
If backlight shuts off, you can activate it by touching the screen.
Continue to the Next Page

yyFault Code Table:
Fault Condition
yyA battery can present a risk of electrical shock and high short circuit curLCD Touch Panel
Solutions
Output Short
Circuited
Disconnect short-circuited
loads and restart the UPS
again.
Overload Fault
Disconnect all output loads
and restart the UPS again.
Over Charge Fault
Call for service immediately.
Battery Too Low
Fault
Please replace the battery
(batteries).
Battery Mode Output
High Fault
Call for service immediately.
Over Temperature
1. Turn off the UPS and wait
for cooling.
2. Or remove excessive
loads and wait for cooling.
If any fault alarm occurs, please call for service immediately.
6 Safety Caution
SAVE THESE INSTRUCTIONS-This quick guide contains important
instructions that should be followed during installation and
maintenance of the UPS and battery (batteries).
yyThe UPS utilizes voltage that may be hazardous. Do not attempt to disassemble the unit. The unit contains no user replaceable parts. Only factory service personnel may perform repairs.
yyThis pluggable type A equipment with battery (batteries) already installed
by the supplier is operator installable and may be operated by laymen.
yyThe mains socket outlet that supplies the UPS shall be installed near the
UPS and shall be easily accessible.
yyDuring the installation of this equipment it should be assured that the
sum of the leakage current of the UPS and the connected loads does
not exceed 3.5mA.
yyConnection to any other type of receptacle other than a two-pole, three-
wire grounded receptacle may result in shock hazard as well as violate
local electrical codes.
yyIn the event of an emergency, press the ON/ OFF Button and disconnect
the power cord from the AC power supply to properly disable the UPS.
yyDo not allow any liquid or any foreign object to enter the UPS. Do not
place beverages or any other liquid-containing vessels on or near the
unit.
yyThe unit is intended for installation in a controlled environment (tempera-
ture controlled, indoor area free of conductive contaminants). Avoid installing the UPS in any location where there is standing or running water,
or excessive humidity.
yyDo not plug the UPS input into its own output.
yyDo not attach a power strip or surge suppressor to the UPS.
yyDo not attach non-computer-related items, such as medical equipment,
life-support equipment, microwave ovens, or vacuum cleaners to the
UPS.
yyDo not dispose of battery (batteries) in a fire as they may explode.
yyDo not open or mutilate the battery or batteries. Release electrolyte is
harmful to the skin and eyes. It may be toxic.
www.deltapowersolutions.com
rent. The following precautions should be observed when working on batteries:
1. Remove watches, rings, or other metal objects from the hands.
2. Use tools with insulated handles.
3. Wear rubber gloves and boots.
4. Do not lay tools or metal parts on top of battery (batteries).
5. Disconnect charging source prior to connecting or disconnecting
the terminals of battery (batteries).
6. Remove battery grounds during installation and maintenance to reduce
likelihood of shock. Remove the connection from ground if any part of
the battery is determined to be grounded.
yyInternal battery voltage is 12Vdc. Battery type is sealed, lead-acid, 6-cell
battery.
yyServicing of batteries should be performed or supervised by personnel
knowledgeable of batteries and the required precautions. Keep unauthorized personnel away from batteries.
8 Technical Specifications
Model
Capacity
yyUnplug the UPS prior to cleaning and do not use liquid or spray detergent.
7 Troubleshooting
Problem
LED doesn’t
illuminate
or nothing
is displayed
on the LCD
panel.
The UPS
always runs
in battery
mode.
The UPS
continuously
beeps.
Backup time
is too short.
Possible Cause
Solutions
The UPS is not on.
Press the ON/ OFF Button again to
turn on the UPS.
Battery voltage is too
low.
Charge the battery (batteries) at
least 6 hours.
Battery fault.
Replace the battery (batteries).
The power cord
becomes loose.
Re-plug the power cord.
Replace the fuse. For how to
The fuse is damaged. replace the fuse, please refer to
3 Operation .
1kVA/600W
1.5kVA/900W
230 Vac
170 ~ 280 Vac
230 Vac ± 10% (Bat. mode)
Transfer Time
Typical 2 ~ 6 ms
Waveform
Battery Type & No.
Simulated Sine Wave
12V/7Ah x 1
Charging Time
Net Weight (kgs)
vents and avoid exposing the unit to direct sunlight or installing the unit
near heat emitting appliances such as heaters or furnaces.
600VA/360W
Output Voltage
yyAttention! Hazardous through electric shock. Even disconnection of this
yyTo reduce the risk of overheating the UPS, do not cover the UPS’s cooling
1500VA
Input Voltage Range
Dimensions
(D x W x H)
unit from the mains, hazardous voltage still may be accessible through
supply from the battery (batteries). The battery supply should be therefore
disconnected in the plus and minus pole at the connectors of the battery
(batteries) when maintenance or service work inside the UPS is necessary.
1000VA
Nominal
Input Voltage
yyWhen replacing battery (batteries), replace with the same number and
type of sealed lead-acid battery (batteries).
600VA
12V/7Ah x 2
12V/7Ah x 2
Typical 6 ~ 8 hours
279 x 101 x
142 mm
Humidity
Noise Level
4.2
320 x 130 x 182 mm
8.2
10.4
0 - 90% RH @ 0 - 40°C (non-condensing)
Less than 40dB
Less than
45dB
* Specifications are subject to change without notice.
9 Warranty
Seller warrants this product, if used in accordance with all applicable
instructions, to be free from original defects in material and workmanship
within the warranty period. If the product has any failure problem within the
warranty period, Seller will repair or replace the product at its sole discretion
according to the failure situation.
This warranty does not apply to normal wear or to damage resulting from
improper installation, operation, usage, maintenance or irresistible force (i.e.
war, fire, natural disaster, etc.), and this warranty also expressly excludes
all incidental and consequential damages. Maintenance service for a fee is
provided for any damage out of the warranty period. If any maintenance is
required, please directly contact the supplier or Seller.
WARNING: The individual user should take care to determine prior to use
whether the environment and the load characteristic are suitable,
adequate or safe for the installation and the usage of this product.
The Quick Guide must be carefully followed. Seller makes no
representation or warranty as to the suitability or fitness of this
product for any specific application.
Please check the
Fault Code Table for
the details.
Please check the Fault Code Table
for the details.
Battery voltage
is too low.
Charge the battery (batteries) at
least 6 hours.
Overload.
Remove some unnecessary loads.
Before reconnecting equipment,
please verify that the load matches
the UPS capability specified in the
specs.
Copyright © 2017 by Delta Electronics Inc. All Rights Reserved.
This Quick Guide is subject to change without prior notice.
Battery defect.
Replace the battery (batteries).
Version Date : 2017_08_16
If any abnormal situations occur that are not listed above, please call for
service immediately.
WARNING: This is a category C2 UPS product. In a residential environment,
this product may cause radio interference, in which case the user many be
required to take additional measures.