SR10-120
on-line
series
UPS
10 – 20 kVA single/single phase and three/single-phase
10, 12, 15, 20, 30, 40, 60, 80, 100, 120kVA three/three-phase
• LOCAL AREA NETWORKS (LAN)
• Cash Registers
• Industrial PLCS
• SERVERS
• Telecomunication Devices
• Electro-Medical Devices
• DATA CENTERS
• E-Business (Servers Farms, ISP/ASP/POP)
• Emergency Devices (Lights/Alarms)
SR10-120
series
SR10-120 is ideal for the protection of critical information and telecommunications networks which cannot
run the risk of being powered from a poor quality electrical supply.
The SR10-120 series is available in 10-12-15-20 kVA three-phase and single-phase input and single-phase output models, and 10-12-1520-30-40-60-80-100-120 kVA three-phase input and output models, with double conversion on-line technology according to the VFI-SS-111
classification, as defined by the IEC EN 62040-3 standard.
SR10-120 has been designed and manufactured using state-of-the-art technologies in order to deliver maximum protection for critical users, a
zero impact on the mains power supply and a high operating efficiency.
The high level of flexibility at the design stage means that there is full compatibility both with three-phase power and with single-phase sources,
thus eliminating any critical factors in the connection between UPS and system.
ZERO IMPACT SOURCE
The superior technology of a SR10-120
allows it be used where the site mains
power supply is limited in capacity, or
has an on-site generator and/or loads
that generate current harmonic problems.
SR10-120 is designed to have a zeroimpact on its upstream power supply
(mains or generator).
SWMB
Maintenance by-pass
switch
PFC
CONVERTER
INVERTER
Automatic
static by-pass
Line In
Line Out
SWIN
Input
breaker
Input
Relay
Stand-by
switch
SWOUT
Output
breaker
Battery
charger
SWBATT
Battery
Typical for 10 - 100kVA (120kVA with dual input)
Main Features:
• Reliable, filtered, stabilised and regulated sine wave output (double
on-line conversion technology VFI according to EN50091-3
standard) with filters for atmospheric disturbance suppression
• High reliability: IGBT Technology in rectifier and inverter, high
frequency PWM, transformerless, fully digital control with
microprocessor, no break static and manual transferring
• Cleaned source: power factor correction for unitary power
factor and very low input THDI%
• First class in efficiency: high operation efficiency up to 96,5%
in normal mode, up to 99% in eco mode operation
• Low noise levels: the high frequency PWM for rectifier and
inverter allows very low audible noise
• Flexibility: SR10-120 can be set for several configuration as
normal mode, smart mode and stand by off
•Maximum reliability: SR10-120 can work in parallel up to 6
units. The UPS continues to operate in parallel even if one of
the communication cables is disconnected
• Battery care system: SR10-120 is suitable for use with sealed
VRLA, AGM, GEL or open-vented load acid batteries, Ni-Cd
batteries
• Temperature voltage compensation
• Deep discharging controlled by microprocessor with load and
main levels (sharing power mode suitable within -40% Vin)
•High power availability: the output factor 0,9 providing up to
15% more active power than a traditional UPS and more load
expansion
• Low management cost: the transformer less technology allows
the lowest footprint in this category. The SR10-120 design
allows front, top, and sides access
SR10-120
series
% Efficiency
Cost Saving in Efficiency
SR10-120 is the first class in cost saving due to efficiency up
to 96.5% providing a 50% saving in energy usage per annum
compared to traditional UPS products (92% standard). This
exceptional performance can lead to a full initial investment
recovery within three years.
SR10-120 40 kVA
traditional UPS 40 kVA
100
98
96
94
92
90
88
86
84
82
80
78
76
0
Power Loss
8400 kWh
33,5%
DIFFERENCE
20 30 40 60 80 100
120
% load
Power Loss
12600 kWh
Energy Saved
4200 kWh*
* for standard utility contract at 0,15 €/kWh that means 630 € saved per year.
SR10-120 40 kVA
STANDARD UPS 40 kVA
Efficiency at 75% rated load 96%
Efficiency at 75% rated load 88%
UPS Front Panel:
7
Menu
1
4
2
5
3
6
1. LED for mains operation
2. LED for battery operation
3. LED for load on bypass
4. LED for stand-by/alarm
5. LED for replacing batteries
6. LED for ECO mode
7.Graphical Display
F1, F2, F3, F4 = Function Keys.
F1
F2
F3
F4
Messages are available in the following languages:
English, Italian, French, German, Spanish, Polish, Turkish,
Chinese and Russian
power supply
PowerShield³ provides user-friendly UPS management.
The software displays real time information in the form of bar
charts and values for critical data such as mains voltage, UPS
load and battery charge. It allows remote interrogation of UPS
logs and operating parameters to help diagnose alarms and
potential fault conditions.
ETHERNET NETWORK
LINK RS232
RS232 Terminal
shutdown
Server 1
snmp trap
Administrating Workstation
shutdown
web page
When instructed the software performs an automated safe power
down of the protected PCs and file severs.
Windows Workstation
Server 2
ADVANCED COMMUNICATION
• SR10-120 Plus is equipped with a graphic display that
provides information, measures, states and alarms regarding
the UPS in 9 different languages
• Advanced, multi-platform communication for all operating
systems and network environments:
PowerShield3 monitoring and shut-down software included,
with SNMP agent, for Windows NT 4.0, Vista, XP; Mac OS
10.x, Linux, Novell Operating systems. The UPS is equipped
with a cable for direct connection to the PC (Plug and Play)
• Can also provide shut-down software for:
IBM AIX; Free BSD; BSDI Unix; BSD/OS; SCO Unixware;
SCO Openserver; Sun Solaris; Compaq True64; HP Unix;
HP OpenVMS; HP Openview; SGI Irix MIPS; NCR Unix
• RS232 or USB serial port
• 3 slots for the installation of optional communication
accessories such as network adapters and volt-free contacts
• REPO (Remote Emergency Power Off) with which to power
down the UPS through a remote emergency pushbutton
• Input for connection of the auxiliary contact of an external
manual bypass
• Input for synchronisation from an external source
• Graphic mimic panel display for remote connection
The SNMP network
agent allows UPS
management across
a LAN using any of the main
network communication protocols - TCP/IP,
HTTP and network interface via SNMP
UPService, our technical assistance facility uses highly trained engineers to provide a reliable and competent technical support and after-sales
service.
UPService can provide customers with:
• A dedicated CALL CENTRE for connection to the UPService organisation. UPService personnel are always available and ready to provide advice
and assistance regarding UPS installation, maintenance, fault finding and repair.
• FAST & READY A fast repair on site is guaranteed through the use of state-of-the-art UPS technology and the professionalism of the UPService
personnel and Authorised Assistance Centres. UPService guarantees that failed parts are replaced with original ones, tested and updated in
order to maintain the safety, reliability and operating characteristics of the UPS.
• COMMISSIONING AND START-UP UPService can provide assistance during commissioning and startup of the UPS equipment on-site with
additional training during handover to site personnel. UPService engineers can also verify site suitability, analyse and advise on potential
problems, and disconnect and relocate equipment. UPService recommend that all hardwired installations are commissioned by UPService
engineers.
• MAINTENANCE CONTRACTS can be provided by UPService to minimise response times and repair costs. Contracts range from periodic
inspections to comprehensive cover including labour and materials.
• UPService organises regular TECHNICAL TRAINING COURSES for UPS operators and installers.
SR10-120
Three/Single phase Model
series
Technical Specification
SR10M
SR12M
SR15M
SR20M
INPUT
Rated voltage
380-400-415 Vac three-phase with Neutral / 220-230-240 single-phase
Voltage tolerance
240V - 480V (3 Phase) / 140V - 276V (1 Phase)
Rated frequency
50/60 Hz
Frequency tolerance
40 ÷ 72 Hz
Power factor at full load
0.99
Current distortion
THDi ≤ 3%
By Pass
Rated voltage
220-230-240 Vac
Number of phases
1 phase
Voltage tolerance
180 ÷ 264 V (selectable)
Rated frequency
50/60 Hz (selectable)
Frequency tolerance
± 5% (selectable)
OUTPUT
Rated power (kVA)
10
12
15
20
Active power (kW)
8
9.6
12
16
Output power factor
0.8
Number of phases
1 phase
Rated voltage (V)
220-230-240 Vac (selectable)
Static variation
± 1%
Dynamic variation
± 3%, EN62040-3 class performance 1 distorting load
Crest factor (Ipeak/Irms)
3: 1
Voltage distortion (EN62040-3)
≤ 1% with linear load / ≤ 3% with non-linear load
Frequency
50/60 Hz
Frequency stability on battery mode
± 0.01%
Overload at pF 0.8
110% for 10 minutes, 133% for 1 minute, 150% for 5 seconds
BATTERIES
Type
VRLA AGM/GEL; Ni-Cd; WET TYPE
Recharge time
6h
ENVIRONMENTAL
Weight without internal batteries (Kg)
105
110
Dimensions (LxDxH) (mm)
Communication
115
440 x 850 x 1320
DOUBLE RS232/C - SNMP Agent - MODBUS - PROFIBUS
Operating temperature
0°C / +40°C
Relative humidity
90% non condensing
Colour
Dark Grey RAL 7016
Noise ( dBA @ 1m)
Protection rating
Efficiency Smart Mode
Compliance
120
≤ 48
≤ 52
IP20
≥ 98% in Economy mode
European Directives: L V 2006/95/CE Low voltage directive
EMC 2004/108/EC Electromagnetic compatibility directive
Standards: Safety IEC EN 62040-1; EMC IEC EN 62040-2 C2
Classification according to IEC 62040-3 (Voltage Frequency Independent)
VFI - SS - 111
SR10-120
Models
SR10T
series
SR12T
Technical Specification
SR15T
SR20T
SR30T
SR40T
SR60T
SR80T
SR100T
SR120T
INPUT
Rated voltage
380-400-415 Vac three-phase with Neutral
Voltage tolerance
240V - 480V (3 Phase)
Rated frequency
50/60 Hz
Frequency tolerance
40 ÷ 72 Hz
Power factor at full load
0.99
Current distortion at full load
≤ 3%
2.5%
≤ 3%
BY PASS
Rated voltage
380-400-415 Vac three-phase with Neutral
Number of phases
3 phase + N
Voltage tolerance
180 ÷ 264 V (selectable)
Rated frequency
50/60 Hz (selectable)
Frequency tolerance
± 5% (selectable)
Frequency stability
on battery mode
± 0.01%
Overload at pF 0.8
115% infinite; 125% for 10 mins; 150% for 60 secs;
168% for 5sec
103% - ≤ 110% for 10 mins; 110% - ≤ 133% for 60 secs
133% - ≤ 150% for 5 secs; 150% - ≤ 200% for 0.5 secs
OUTPUT
Rated power (kVA)
10
12
15
20
30
40
60
80
100
120
Active power (kW)
9
10.8
13.5
18
27
36
54
72
90
108
Output power factor
0.9
Number of phases
3 phase + N
Rated voltage (V)
380-400-415 Vac (selectable)
Static variation
± 1%
Dynamic variation
± 0.5%
± 3%, EN62040-3 class performance 1 distorting load
Crest factor (Ipeak/Irms)
3: 1
Voltage distortion
≤ 2% with linear load /
≤ 4% with non-linear load
≤ 1% with linear load / ≤ 3% with non-linear load
Frequency
≤ 1% with
linear load /
≤ 3.5% with
non-linear
load
50/60 Hz
Frequency stability on battery mode
0.01%
Overload at pF 0.8
110% for 10 minutes, 133% for 1 minute, 150% for 5 seconds
BATTERIES
Type
VRLA AGM/GEL; Ni-Cd; WET TYPE
Recharge time
6h
ENVIRONMENTAL
Weight without
internal batteries (Kg)
105
110
Dimensions (LxDxH) (mm)
115
120
135
145
200
220
DOUBLE RS232/C - SNMP Agent - MODBUS - PROFIBUS
Operating temperature
0°C / + 40°C
Relative humidity
90% non condensing
Colour
Dark Grey RAL 7016
≤ 48
≤ 52
Protection rating
≤ 48
≤ 56
≤ 58
IP20
Efficiency Smart Mode
up to 99%
European Directives: L V 2006/95/CE Low voltage directive
Compliance
380
750 x 855 x
1900
500 x 850 x 1600
440 x 850 x 1320
Communication
Noise
190
EMC 2004/108/EC Electromagnetic compatibility directive
Standards: Safety IEC EN 62040-1; EMC IEC EN 62040-2 C2
Classification according to IEC 62040-3 (Voltage Frequency Independent) VFI - SS - 111
NOTE: UPS specification and data may be subjected to change for improvement without prior notice
≤ 70
G-Tec Asia Pacific Pte Ltd in Singapore
G-Tec Europe Srl in Vicenza – Italy
GTec Group is also present worldwide with Business Partners in several countries.
G-Tec Asia Pacific Pte Ltd
60 Kaki Bukit Place, #02-05, Eunos Techpark II, Singapore 415979
Tel. +65 6555.5014 - Fax +65 6555.4105
info@gtec.com.sg
G-Tec Europe srl
Strada Marosticana, 81/13 - 36031 Povolaro (VI), Italia
Tel. +39 0444.592463 - Fax +39 0444.365191
info@gtec-power.eu
www.gtec-power.eu
Download PDF