6, 8, and 10 kVA
Tower Model
Series
On-line,
Single-phase
Parallel Redundant
UPS System
■
Power range and runtime scalability
■
Full-time Digital Signal Processor
Control
■
LCD/LED mimic panel
■
Easy-to-set user personalization
■
Up to 98% energy efficiency
■
Continuous power conditioning, even
when not running on battery
■
Smooth, uninterrupted switching from
utility power to battery mode, and back again
■
Wide fluctuations in utility power are handled without
going to battery
■
Parallel up to four units for added capacity or redundancy,
using a simple connection on the rear panel without
additional cabinets
■
Full Three Year
Warranty
Unlike most UPSs in this size range, the UniStar® P has
a very low rate of added and reflected harmonics, which
protects the integrity of your entire electrical system
www.stacoenergy.com
Your tailored power solutions provider
TM
Proven Technology
Parallelable
UPS
Higher reliability and greater immunity
from power anomalies is achieved
through our field-proven Digital
Signal Processor architecture. The front
panel controls are intuitive and user
friendly. The system display clearly
communicates all major system
parameters, system status, and system
diagnostics, and includes access to
system information and unit personalization via the front panel.
Power Range and Runtime
Scalability
The UniStar® P provides an excellent
return on investment. The system is
fully modular, allowing you to increase
the overall power output and battery
runtime as your system grows. It is
important however, that you plan your
electrical installation to fit your needs.
Our worldwide network of sales representatives and distributors can assist
you with a tailored solution that meets
your needs.
Full Time Digital Signal
Processor Control
The full-time DSP controI system
inside the UniStar® P provides a pure
sine wave using our patented inverter
control technology. The UniStar® P
provides N+1 scalability without
additional components.
UniStar® P Series Tower
shown paralleled and
with battery cabinet
Three Year Warranty
Electronics:
Simple Parallel Installation
For increasing power capacity, or making
redundant systems, the UniStar® P
can be installed in parallel. By simply
connecting the parallel control lines
through an RJ-45 connector on the
rear panel and CAN-bus, communication is established to all units. Up to
four units can be paralleled together
without a paralleling cabinet.
www.stacoenergy.com
A full Three Year parts with depot repair or
replacement warranty is standard.
Battery:
A full One Year Warranty, 4-year pro-rated,
on the Battery System ensures that your
batteries are protected from system
failure now and in the future. (Warranty
provided by battery manufacturer.)
Extended warranties, customized
service plans and preventative
maintenance are also available.
Please refer to our warranty statement
for complete details.
On-line, Single-phase
Parallel Redundant UPS System
EPO Function
The Emergency Power Off Function
enables user shutdown of the UPS in
an emergency situation.
Manual Maintenance Bypass
High Input Power Factor
and Low Current THD
The UniStar® P meets today’s industry
standard for energy savings and low
reflected harmonics, and achieves
up to 0.99 Power Factor as well as
<5% THD.
Applications
■
■
■
■
■
■
■
■
Energy Efficient UPS
Broadcast
Computer Networks
Retail
Robotics
Printing
Medical/Pharmaceuticals
Paper Productlon
Food Processing
The AC to AC efficiency of the UPS
may reach up to 91% at 25% load, and
better with larger loads and normal
VFI operation. Using the ECO mode,
up to 98% efficiency can be achieved.
Smart ECO Mode
In ECO operation mode, the UniStar®
P normally supplies power to load
via bypass utility. It will automatically
transfer to inverter supply with
SmartECO Mode if the bypass utility
becomes out of tolerance.
Programmable Frequency
Converter
Using the front panel keypad, you
may reprogram the UniStar® P to
act as a frequency converter for
either 50 Hz or 60 Hz. (Consult factory
for further information)
Your tailored power solutions provider
The internal manual bypass ensures
a continuous supply of power to the
critical load during service or periodic
maintenance of the UPS system. The
bypass switch is electrically interlocked
with the inverter to provide safe
operation.
TM
LCD/LED Mimic Panel
A concise LCD/LED display provides
real-time status and readings such
as operation modes, AC voltage,
frequency, battery voltage, load level,
inner temperature, and more. A fullsize microprocessor-based graphical
LCD display provides advanced
monitoring functions.
Intelligent Self-Diagnostics
The DSP self-diagnostics assists the
service engineer in pinpointing system
fauIts rapidly, making repairs fast and
easy .
Silent Fan Control
The UniStar® P employs forced air
cooling by internally mounted fans
with speed control that is based on
load percentage. This means low
audible noise levels, suitable for most
environments.
User Personalization
Through the LCD front panel, you may
easily change the parameters and
settings built in to the DSP controllers,
such as UPS operation modes, voltage
configurations, synchronization
frequency windows (for use with
generators), bypass voltage tolerances
and audible alarm.
Advanced Battery Management
The UniStar® P automatically manages
the end of discharge voltage according
to load. This function prevents deepdischarge of the built-in battery during
a power failure and saves battery life.
Galvanic Isolation Transformer
The galvanic isolation transformer
provides not only complete isolation
between the input and the output, but
also various secondary voltages, such
as 220/230/240 Vac, 208/120 Vac and
240/120 Vac.
Optional External
Battery Charger
The optional charger can be
installed for fast recharge of
the extended battery pack.
Variety of Customer
Options Slots
This UPS also provides two customer
option communication slots in addition
to the standard RS232 port. All
com-munications cards are designed
for simple installation; electrical
connections are made through a
26-pin edge card connector. The
first RS232 port on the rear panel will
remain active, even though optional
communication cards are installed.
■
Power Output: 1000W
■
Mounting: UPS or wall mount
Matching Extended
Battery Pack
Optional matching battery packs
are available to easily extend the
UPS runtime to several hours.
6, 8 & 10kVA Single Phase UPS Tower
Extended Battery Run Times (minutes)
40 X Cabinet (2 strings)
UPS
Part
Size
Number
6kVA
Internal
SC-BP6000T-2
Communications Capability
The UniStar® P is shipped with standard
monitoring/shutdown software. The
software allows control of the UPS and
graceful shutdown when the utility
power fails, but also allows the user to:
■ Remotely test the major operating
functions of the UPS
■
Communicate via SNMP/WEB card
■
Access UPS functions via the WEB
8kVA
Internal
SC-BP1100T-2
10kVA
Internal
SC-BP1100T-2
60 X Cabinet (3 strings)
UPS
Part
Size
Number
6kVA
Internal
SC-BP6000T-3
8kVA
Internal
SC-BP1100T-3
Cold Start Function
10kVA
Users can turn on the UPS without
utility power available.
Internal
SC-BP1100T-3
Hot-Swappable Battery
The UniStar® P allows users to replace
batteries without electric shock hazard,
while the UPS supplies continuous
power to your application.
www.stacoenergy.com
Qty. of
25%
Cabinets Load
50%
Load
75%
Load
100%
Load
56
226
420
629
847
1073
64
216
402
602
812
1028
40
164
307
461
623
790
22
95
180
273
370
471
21
91
172
261
354
451
15
68
131
198
270
345
12
56
109
166
226
289
12
54
104
158
216
276
8
40
78
120
154
210
8
38
75
116
158
203
7
37
72
110
151
194
5
27
54
83
114
147
Qty. of
25%
Cabinets Load
50%
Load
75%
Load
100%
Load
22
137
273
420
576
737
21
131
261
402
551
706
15
98
198
307
422
541
12
82
106
257
354
454
12
78
158
246
338
435
8
58
120
187
258
332
8
56
116
180
249
321
7
54
110
172
238
307
5
40
83
130
181
234
0
1
2
3
4
5
0
1
2
3
4
5
0
1
2
3
4
5
0
1
2
3
4
5
0
1
2
3
4
5
0
1
2
3
4
5
56
321
629
959
1305
1660
64
307
602
919
1251
1594
40
234
461
706
963
1229
Note: External 1000W Battery Charger (P/N SC-CHG-1000) required
every (2) External Battery Cabinets
Tower Models
Tower Models
SC60021T
SC60022T
SC80021T
SC80022T
SC11021T
SC11022T
INPUT
Connection
Hardwire / Optional 6ft. Line
Cord with L6-30P Plug
Voltage Range
Frequency
Phase/Wire
Power Factor
Current THD
Hardwire
160 -280Vac
45 ~ 65 Hz
Single, Line + Common + Ground
Up to 0.99 at 100% Linear Load
<5% at 100% Linear Load
OUTPUT
Connection
Voltage
Voltage Adjustment
Voltage Regulation
Capacity
Parallel Capability
Rated Power Factor
Wave Form
Frequency Stability
Frequency Regulation
Transfer Time
Crest Factor
Efficiency
(AC to AC Nominal)
Efficiency
(AC to AC ECO Mode)
Leakage Current
Manual Bypass Switch
DC Start
Cooling
Hardwire
208/220/230/
208/120Vac or
208/220/230/
208/120 or
208/220/230/
240Vac
240/120Vac
240Vac
240/120Vac
240Vac
+/- 0%; +/- 1%; +/- 2%; +/- 3% For All Voltages
+/- 2%
6000VA/4200W
8000VA/5600W
10000VA/7000W
Redundancy or Capacity – 4 Units
0.7 Lagging
Sine Wave, THD < 3% (no load to full load)
+/- 0.2% (Free Running)
+/- 1 Hz
0ms/instantaneous
3:1
208/120 or
240/120Vac
91%
Up to 97%
Up to 93%
< 3mA @ Full Load
Make – Before - Break
Yes
Load Dependant Variable Speed Fans
DISPLAY, ALARMS, DIAGNOSTICS, COMMUNICATIONS & EMERGENCY FUNCTION
Self-Diagnostics
Line Mode, Backup Mode, ECO Mode, Bypass Supply, Battery Low, Battery Bad/Disconnected,
Overload, Transferring with interruption & UPS Fault
Input Voltage, Input Frequency, Output Voltage, Output Frequency, Load Percentage,
Battery Voltage & Unit’s Inner Temperature
Upon Power-on, Front Panel Setting & Software Control, 24 Hour self check
Audible Alarms and Visual
Line Failure, Battery Low, Transfer to Bypass, System Fault Conditions
Communications
Emergency Power Off
(EPO) Connection
RS232 Serial Port ( 2 slots available for optional SNMP/WEB, USB or Dry Contact Card)
Status On LED + LCD
Readings On LED + LCD
Emergency Power Off shuts down UPS when activated by customer supplied EPO Circuit
PHYSICAL
Dimensions (H x W x D)
Weight (lbs.)
Safety and Performance
29.5" x 11.4" x 25.4"
34.7" (21T), 29.5" (22T) x 11.4" x 25.4" 34.7" (21T), 29.5" (22T) x 11.4" x 25.4"
320 (21T), 203 (22T)
340 (21T), 223 (22T)
265 (21T), 190 (22T)
UL1778, c-UL; CE – FCC Class A, N 50091-2, EN 61000 (various),
IEC 61000 (various), IEC 62040-2, CISPR 22
INTERNAL BATTERY
Battery Run Time@Full
Load
Type
Hot – Swap Batteries
Recharge Time
*Extended Run Time
Battery Cabinets
8
7
5
Sealed Lead Acid Maintenance
Sealed Lead Acid Maintenance
Free, 20 each 12V/7AH, 240Vdc Free, 20 each 12V/9AH, 240Vdc
Yes
4 hours to 90%
SC-BP6000T-2, SC-BP6000T-3, SC-BP1100T-2,
(Refer To Run Time Chart)
Sealed Lead Acid Maintenance
Free, 20 each 12V/9AH, 240Vdc
5 hours to 80%
SC-BP1100T-3
OPTIONAL COMMUNICATION Cards and Shutdown Software
SC-SNMP1
SC-Contact/EPO
SC-PK
SNMP/WEB Network Card & Shutdown Software
Dry Contact & EPO Card
Parallel Cable kit contains two RJ45 cables and miscellaneous hardware for paralleling
Note: (2) slots available; both cards can be used simultaneously; RS232 Port is disabled when communication cards are installed.
OPTIONAL EXTERNAL EXTENDED BATTERY CABINETS
Model
Type
SC-BP6000T-2 & -3
Sealed Lead Acid Maintenance Free,
-2: 40 each & -3: 60 each 12V/9AH, 240Vdc
Hot – Swap Cabinets
Battery Connection
Dimensions (HxWxD)
Weight (lbs.)
SC-BP1100T-2 & -3
Sealed Lead Acid Maintenance Free,
-2: 40 each & -3: 60 each 12V/9AH, 240Vdc
Yes
Connector
29.5" x 11.4" x 25.4"
326
OPTIONAL EXTENDED BATTERY PACK CHARGER
SC-CHG-1000
1000W External Mount Battery Charger (1) charger per
every (2) External Battery Packs Required
3.4"H x 6.6"W x 11.1"D
7 lbs.
3.7"H x 10.5"W x 9.5"D
3.7"H x 10.5"W x 16.4"D
11 lbs.
20 lbs.
OPTIONAL PARALLEL DISTRIBUTION / BYPASS MODULE (Note 1)
SC-PKIT-2
SC-PKIT-4
Parallel Distribution Bypass 60Amp for (2) UPS Modules
Parallel Distribution Bypass 120Amp for (4) UPS Modules
Notes:
Parallel for capacity configurations can use (1) battery system sized for the ultimate capacity.
Parallel for redundancy configurations require (1) battery system for each UPS.
Service Options
With our ServiStar® program, a wide range of planned maintenance and extended
service options are offered to maximize equipment life and reliability of your FirstLine®
UPS. Through an extensive network of factory trained professionals you receive:
■
Start-Up and Training
■
Annual Service Plan
■
24/7 Emergency Service
■
Preventative Maintenance
■
Programs tailored to meet your needs
About Staco Energy Products Company
Since 1937, customers worldwide have been
relying on Staco Energy Products Company
to deliver voltage control and power quality
solutions tailored to their needs.
In addition to the UniStar® P
we offer a wide array of power
quality products, including:
■ Uninterruptible Power Supplies
■
Power Conditioners
As a leading power quality resource, we offer
our customers world-class support; from our
thorough applications assessment, to our
ability to design and deliver a solution that is
tailored to the specific needs of our customers;
through delivery and commissioning.
■
Voltage Regulators
■
Power Factor Correction and
Harmonic Mitigation
■
■
Active Harmonic Filters
Variable Transformers
■
Custom Engineered Test Sets
Our professional, factory trained service
team is in place to ensure that our
customers’ revenues are protected, and
their investment provides them with
many years of trouble free operation.
Staco develops total power solutions
for OEM and end user applications.
Represented locally by:
Contact Us:
US Toll Free: 866-261-1191
Phone: 937-253-1191
E-mail: sales@stacoenergy.com
Your tailored power solutions provider
TM
www.stacoenergy.com
Staco Energy published documents contain material that can be recycled.
©2011, Staco Energy Products Co.
US-P-twr_bro-0611
Download PDF