FDL2-i SLIM 102÷502 - Central Heating NZ

INSTALLATION - USER - MAINTENANCE MANUAL
EN
Fan coil with casing or for built-in
installation, with tangential fan and
inverter controlled brushless motor
FDL2-i SLIM 102÷502
U I A
CONTENTS
U I A
General warnings
3
I A
Water connections
9
U I A
Fundamental safety rules
3
I A
Condensate drain
9
U I A
Product range
4
I A
Filling the system
10
I A
Rated technical specifications
4
I A
Venting air when filling the system
10
I
Overall dimensions
4
I A
Electrical connections
11
I A
Packaging
5
I A
Maintenance
11
I A
Storage on site
5
I A
Cleaning the outside of the unit
11
I A
Installation - Positioning the unit
6
I A
Cleaning the air intake filter
11
I A
Installation procedure
6
I A
Tips on saving energy
13
I A
Minimum installation clearance
6
U
A
Troubleshooting
13
I A
Dismantling/assembling the casing
7
U
A
Troubleshooting table
13
I A
Vertical installation
7
I A
Horizontal installation
8
I A
Front grill safety support assembly
8
The following symbols are used in this publication and inside the unit:
U
I
A
2
User
Important
Installer
Prohibition
Assistance
Danger voltage
FDL2-i SLIM EN 05/2013
Danger high temperatures
GENERAL WARNINGS
After having removed the packing, check that the contents are intact and complete.
In the event of discrepancies, contact the service centre
that sold the appliance.
The appliances must be installed by authorised personnel,
who at the end of the work shall issue a declaration of
conformity in compliance with the legislation in force and
with the instructions provided in the booklet supplied with
the appliance.
These appliances have been designed for cooling and
heating rooms and must be used in applications compatible with their performance characteristics.
Incorrect installation, adjustment and maintenance or
improper use absolve the manufacturer from all liability,
whether contractual or otherwise, for damage to people,
animals or things.
In the event of water leaks, move the main system switch
to the “off” position and close the water taps.
Contact the technical service or a qualified professional
as soon as possible. Do not attempt to repair the appliance yourself.
Built-in fan coils are supplied without grills and casing.
Protective covers and air outlet/intake grills must be provided, to prevent accidental contact with the appliance.
U I A
If the appliance is not used for a long period, proceed as
follows:
- Move the main system switch to the “off” position
- Close the water taps
- If there is the risk of freezing, empty the system or
make sure it antifreeze is added.
Excessively low or high temperatures are harmful to the
health and a useless waste of energy.
Avoid extended direct contact with the air flow.
Do not leave the rooms closed for too long.
Periodically open windows to ensure correct air change.
This instruction booklet is an integral part of the appliance
and must therefore be kept carefully and must ALWAYS
accompany the appliance if sold to another owner or user,
or transferred to another system.
If this booklet is lost or damaged, contact your local Technical Service for a replacement.
All repair or maintenance work must be carried out by
the company's Technical Service or qualified personnel,
following the instructions in this booklet. Do not modify or
tamper with the appliance as this may create situations
of danger; in such cases the manufacturer of the appliance is not liable for any damage caused.
Pay careful attention to avoiding contact: danger of burns.
FUNDAMENTAL SAFETY RULES
U I A
When operating equipment involving the use of electricity and water, a number of fundamental safety rules must be observed,
namely:
The appliance is not intended for use by persons (including children) with reduced physical, sensory or mental
capabilities, or lack of experience and knowledge, unless
they have been given supervision or instruction concerning use of the appliance by a person responsible for their
safety.
Children must be supervised to ensure they do not play
with the appliance.
Installation must only be performed by qualified personnel.
Do not pull, detach or twist the electrical cables coming
from the unit, even when disconnected from the mains
electricity supply.
Do not touch the unit with bare feet or with wet or damp
parts of the body.
Do not dispose of, abandon or leave within reach of children packaging materials, as they may represent a hazard.
Do not introduce objects or substances through the air
outlet and intake grills.
Do not open doors or panels providing access to the
internal parts of the appliance, without first having
moved the main switch to “off”.
Never perform any cleaning operations before having
disconnected the unit from the mains power supply,
moving the main switch to the “off” position.
Do not sit or stand on the appliance and/or rest any type
of object on top of it.
Do not modify safety or control devices without authorisation and instructions from the manufacturer.
The outside components of the appliance may reach
temperatures exceeding 70°
EN 05/2013 FDL2-i SLIM
3
U I A
PRODUCT RANGE
The FDL2-i SLIM range of fan coils comprises 4 versions,
DLIU, DLMV, DLMO and DLRV, each of which available in
five sizes, with different performance and overall dimensions.
FDL2-i SLIM DLMV
fan coil with painted metal casing (suitable for vertical installation)
FDL2-i SLIM DLIU
built-in fan coil without panelling (suitable for built-in horizontal or vertical installations)
FDL2-i SLIM DLRV
fan coil with painted metal casing with radiant effect (suitable for vertical installation only)
FDL2-i SLIM DLMO
fan coil with painted metal casing (suitable for horizontal
installation)
I A
RATED TECHNICAL SPECIFICATIONS
TECHNICAL SPECIFICATIONS
FDL2-i SLIM
102
202
302
402
502
l
0,47
0,8
1,13
1,46
1,8
Maximum operating pressure
bar
10
10
10
10
10
Maximum water inlet temperature
°C
80
80
80
80
80
Minimum water inlet temperature
Coil water content
°C
4
4
4
4
4
Water connections *
“
Eurokonus 3/4
Eurokonus 3/4
Eurokonus 3/4
Eurokonus 3/4
Eurokonus 3/4
Power supply voltage
V/ph/Hz
230/1/50
230/1/50
230/1/50
230/1/50
230/1/50
Maximum current draw, DLIU, DLMV and DLMO
A
0,15
0,24
0,28
0,29
0,30
Maximum power consumption, DLIU, DLMV and DLMO
W
18
27
35
35
37
Weight, DLIU
kg
9
12
15
18
21
Weight, DLMV and DLMO
kg
17
20
23
26
29
Weight, DLRV
kg
17,3
20,4
23,4
26,4
29,4
* kit supplied as standard containing a pair of adapters for flat gaskets, for 3/4” fittings
I
OVERALL DIMENSIONS
FDL2-i SLIM DLMV, DLMO, DLRV fan coils with casing
Dimensions
A
mm
102
202
302
402
502
737
937
1137
1337
1537
579
131
659
A
4
FDL2-i SLIM EN 05/2013
131
I
OVERALL DIMENSIONS
FDL2-i SLIM DLIU built-in fan coil
Dimensions
A
mm
80
102
202
302
402
502
525
725
925
1125
1325
A
63,5
126
590
47
I A
PACKAGING
The units are delivered in standard packaging comprising a
cardboard box on pallets; the accessories are supplied separately, unassembled, or already fitted on the unit (upon
request).
Inside the unit is an envelope containing the user, installation and maintenance manual. An identification label is
affixed to each individual unit, describing:
• Manufacturer’s details
• Model of the unit and part/serial number
• Wiring diagrams
DATI COSTRUTTORE (società costruttrice):
COSTRUTTORE S.R.L. – VIA XY – INDIRIZZO XY – CITTA’ XY
XYZ-XYZ
00123/01/2001
Modello della macchina
Codice di identificazione
MODELLO
Potenza frigorifera
kW
Potenza termica
KW
Portata aria
mc
Assorbimento elettrico W
Corrente assorbita
A
STORAGE ON SITE
10
12
23
330
18
1
20
15
33
550
20
2
30
17
43
670
45
2
40
34
53
750
90
3
50
56
63
770
120
3
Data di produzione
15 / 10 / 2001
Lotto di produzione
1937 / 2001
60
77
65
850
150
4
70
84
90
910
150
4
I A
The units must be stored indoors!
EN 05/2013 FDL2-i SLIM
5
INSTALLATION - POSITIONING THE UNIT
Avoid installing the unit:
- in places exposed to direct sunlight;
- near sources of heat;
- in damp environments and areas where there may be
contact with water;
- in environments with oil vapour;
- in environments with high frequency interference.
Make sure:
- the wall where the unit is installed features a suitable
structure and capacity;
- there are no pipes or wiring in the part of the wall affected;
INSTALLATION PROCEDURE
The following descriptions of the various assembly operations and the corresponding drawings refer to versions of
the unit with the fittings on the left.
The descriptions of assembly operations for units with the
fittings on the right are identical.
Only the drawings will need to be inverted horizontally.
MINIMUM INSTALLATION CLEARANCE
The figure illustrates the minimum clearance to be left from
walls and furniture in the room when assembling the fan coil.
6
FDL2-i SLIM EN 05/2013
I A
- the wall where the unit is installed is perfectly flat;
- there is sufficient clearance around the unit to allow
proper air circulation at the intake and outlet;
- the wall where the unit is installed should be an outside
perimeter wall, so as to be able to drain the condensate outside;
- in the event of ceiling installation (DLMO or DLIU version), the air flow must not be aimed directly towards
people in the room.
I A
For best installation results and optimum operating performance, carefully observe the instructions provided in this
booklet.
Failure to heed the instructions may cause the equipment to
malfunction. In such cases, the warranty will be void and the
company declines all liability for any damage caused to people, animals or things.
I A
I A
DISMANTLING / ASSEMBLING THE CASING
- Remove the front grill.
- Remove the filter, pulling it outwards horizontally
- Unscrew the fastening screws.
- Lift the casing in one piece, as shown in the figure.
I A
VERTICAL INSTALLATION
For floor-standing assembly using the mouldings, see the
individual instruction sheets and the corresponding manual
for details on assembling the mouldings.
Use the paper template, and trace the position of the two
fastening brackets on the wall.
Drill the holes with a suitable drill bit and insert the anchors
(2 for each bracket); fasten the two brackets.
Do not fully tighten the screws, so as to be able to adjust the
brackets against a spirit level.
A
B
Then secure the two brackets in place by completely tightening the four screws.
Check stability by moving the brackets manually to the right
and left, up and down.
Fit the unit, making sure it is correctly attached to the brackets and is stable.
anchors
brackets
A
B
A
B
EN 05/2013 FDL2-i SLIM
7
I A
HORIZONTAL INSTALLATION
Use the paper template, and trace the position of the two fastening brackets and the two rear screws on the ceiling.
Drill the holes with a suitable drill bit and insert the anchors (2
for each bracket); fasten the two brackets.
Do not fully tighten the screws.
Insert the unit on the two brackets, holding it in position, then
tighten the two screws in the rear anchors, one on each side.
Leave the unit sloping down towards the drain pipe so as to
assist drainage.
Then completely tighten all 6 fastening screws.
A
B
C
D
anchors
brackets
screws
drain pipe
A
B
A
For installation of DLMO versions, the horizontal condensate
collection pan kits are available as accessories.
DLRV versions must not be installed horizontally.
Carefully check the slope of the drain pipe.
If the drain line is not sloping downwards, water may
leak from the line.
B
D
C
I A
FRONT GRILL SAFETY SUPPORT ASSEMBLY (DLMO)
If the fan coil is installed in the horizontal position, to ensure
safety when cleaning/replacing the filters, the installer must
fit the two safety clamps provided in the bag supplied
together with the instruction booklet and the accessories.
A
B
C
These supports are designed to stop the grill from falling.
- Separate the two clamps;
- open the front grill and completely unscrew the spring
fastening screws;
- fasten the two clamps by tightening the screws again;
- fasten the other part of the clamps to the grill, using the
screws supplied;
- close the grill.
clamps
spring fastening screws
grill
A
B
A
C
8
FDL2-i SLIM EN 05/2013
I A
WATER CONNECTIONS
Dimensions
Pipe diameter
mm
102
202
302
402
502
12
14
16
18
20
The choice and sizing of the water lines is the responsibility
of the designer, who must apply best working practice and
comply with the legislation in force, also considering that
undersized lines will lead to poor performance.
The water lines and the joints must be thermally insulated.
Make sure the pipes are completely insulated.
Avoid over-tightening so as to not damage the insulation.
To make the connections:
- position the water lines
- tighten the connections using two spanners in opposite
directions
- check for any leaks
- cover the connections with insulating material
To ensure water tightness of threaded connections, use
plumber’s hemp and green paste; Teflon tape is recommended when antifreeze is added to the water circuit.
I A
CONDENSATE DRAIN
The condensate drain line must be suitably sized (pipe with
a minimum inside diameter of 16 mm) and the pipe laid out
as to ensure a minimum slope of 1% along the entire line.
For vertical installation, the drain line is connected directly to
the drain pan, located at the bottom of the side frame,
underneath the water connections.
For horizontal installation, the drain line is connected to the
drain pipe already fitted on the unit.
For horizontal installation of DLMO versions, the horizontal
condensate collection pan kits are available as accessories.
- If possible, discharge the condensate directly into a gutter
or a storm water drain.
- If draining into the sewers, a drain trap should be fitted to
prevent bad odours from drifting back into the rooms.
The bend in the drain trap must be lower than the condensate collection pan.
- If discharging the condensate into a container, this must
be open and the drain pipe must not be immersed in the
Assembling the condensate drain pipe on vertical versions
Connect a drain pipe to the condensate collection pan drain
fitting and secure it in place.
A
B
C
water, so as to avoid surface tension and backpressure
that would prevent correct drainage.
- If needing to overcome a raised section that wold prevent
condensate drainage, a pump must be installed:
- for vertical installation, fit the pump underneath the side
drain pan;
- for horizontal installation, the position of the pump should
be determined according to specific needs.
These pumps are widely available on the market.
In any case, following installation check correct condensate
drainage by pouring very slowly (around 1/2 l of water in
around 5-10 minutes) into the collection pan.
Make sure that the drip guard is installed correctly.
drain fitting
drain pipe
drip guard
C
A (Ø14mm)
B
EN 05/2013 FDL2-i SLIM
9
I A
CONDENSATE DRAIN
Assembling the condensate drain pipe on horizontal
versions
To assemble the horizontal drain pan on DLMO versions,
see the instructions supplied with the horizontal pan kit.
- make sure that the “L” pipe and the rubber hose are correctly connected to the pan.
- insert the side of the unit, keeping the pipe held against
the front grill.
- close the side, making sure the pipe remains secured in
the groove provided on the side.
A
B
Connection pipes
Groove
N.B. warnings for horizontal installation:
- make sure that the unit is perfectly level, or with a slight
slope towards the condensate drain;
- carefully insulate the outlet and return pipes all the way to
the unit, so as to prevent condensate from dripping outside of the collection pan;
- insulate the entire condensate pan drain pipe.
B
A
Ø14mm
I A
FILLING THE SYSTEM
When starting the system the first time, check that the lockshield valve is open.
If there is a power failure and the temperature actuated
valve has previously been powered, use the cap provided to
press the valve member and open the valve.
I A
VENTING AIR WHEN FILLING THE SYSTEM
- Open all the shut-off devices in the system (manual or
automatic);
- Start filling by slowly opening the system water fill tap;
- For models with vertical installation, use a screwdriver to
open the vent at the top of the coil; for units with horizontal
installation, open the vent at the top; for 4-pipe versions,
open the vents at the top of both coils.
- When water starts coming out of the vent valves on the
unit, close the vents and continue filling until reaching the
rated system pressure.
A
This operation should be repeated after the appliance has
been operating a number of hours, and system pressure
should be checked periodically.
Coil vent
A
10
Check water tightness of the gaskets.
FDL2-i SLIM EN 05/2013
A
I A
ELECTRICAL CONNECTIONS
Make the electrical connections following the instructions
shown under General warnings and Fundamental safety
rules, with reference to the diagrams provided in the accessory installation manuals.
Before performing any work, make sure that power is disconnected.
The appliance must be connected to the power supply via a
disconnect switch with minimum contact opening of 3 mm,
i.e. a device that ensures complete disconnection of the
appliance
I A
MAINTENANCE
Periodical maintenance is essential to ensure efficient, safe
and reliable operation of the fan coil over time.
Some maintenance operations are required every six
months, others once a year, carried out by authorised and
trained personnel from the Technical Service and using original spare parts when required.
I A
CLEANING THE OUTSIDE OF THE UNIT
Before any cleaning and maintenance work, disconnect
the unit from the mains power supply, switching off the
mains switch.
Wait until the components have cooled down, to avoid
the danger of burns.
Do not use abrasive sponges or abrasive or corrosive
detergents, to avoid damaging the painted surfaces.
When required, clean the outside surfaces of the fan coil
using a soft cloth dipped in water.
I A
CLEANING THE AIR INTAKE FILTER
After a period of continuous operation, based on the concentration of impurities in the air, or alternatively when
restarting the system after a long period of inactivity, proceed as follows.
Remove the filter cells
- remove the front grill by lifting it slightly and turning it until
it is completely released;
- remove the filter, pulling it outwards horizontally.
A
B
Front grill
Grill housing
A
C
D
Filter
Filter removal
B
C
D
EN 05/2013 FDL2-i SLIM
11
I A
CLEANING THE AIR INTAKE FILTER
Cleaning the filtering media
- use a vacuum cleaner to remove the dust from the filter
with
- wash the filter under running water, without using detergents or solvents, and leave it to dry.
- Reposition the filter on the fan coil, making sure the bottom edge is correctly fitted in place.
A
B
C
Never use the appliance without the mesh filter.
The appliance is fitted with a safety switch that prevents
the fan from operating if the panel is not fitted or is positioned incorrectly.
After cleaning the filter, making sure the panel has been
positioned correctly.
Filter
Bottom edge
Filter housing
B
B
A
After cleaning
- For versions with louver grills, insert the two tabs into the
corresponding slots, turn the grill and press it gently
closed at the top.
A
B
Tabs
Slots
A
B
12
FDL2-i SLIM EN 05/2013
C
I A
TIPS ON SAVING ENERGY
- Keep the filters clean at all times;
- where possible, keep the doors and windows in the airconditioned room closed;
- where possible, in cooling operation limit exposure of the
air-conditioned room to direct sunlight (use curtains, shutters, etc.).
U A
TROUBLESHOOTING
In the event of water leaks o malfunctions, move the
main system switch to the “off” position and close the
water taps.
If one of the following faults occurs, contact the technical
service or a qualified professional as soon as possible.
Do not attempt to repair the appliance yourself.
- The fan does not start active even when there is hot or
cold water in the circuit.
- Water leaks from the appliance in heating mode.
- Water leaks from the appliance in cooling mode only.
- The appliance is very noisy.
- Dew forms on the front panel.
U A
TROUBLESHOOTING TABLE
The following operations must be performed by a qualified installer or a specialist service centre.
Fault
The fan starts after a delay from changing the
temperature settings or function.
The fan does not start.
Possible cause
Solution
The circuit valve takes some time to open and Wait 2 or 3 minutes for the circuit valve to
let hot or cold water circulate in the appliance. open.
Make sure that the boiler or water chiller are
No hot or cold water in the system.
operating.
Remove the valve body and check if water
starts circulating.
The water valve remains closed
The fan does not start active even when there
is hot or cold water in the circuit.
The fan motor is blocked or burnt out.
The microswitch that stops the fan when
opening the filter grill does not close correctly.
Incorrect electrical connections.
Water leaks from the appliance in heating
mode.
Leaks from the system water connections.
Dew forms on the front panel.
Heat insulation detached.
There are droplets of water on the air outlet
louvers.
When relative humidity inside the room is
quite high (>60%), condensate may form,
especially at low fan speed.
Leaks from the valves.
The condensate pan is blocked.
Water leaks from the appliance in cooling
mode only.
The appliance is very noisy.
The condensate drain is not sloped downwards enough for correct draining.
Check valve operation by powering it separately at 230 V.
If the valve is activated, the problem may lie in
the electronic controller.
Check the motor windings and make sure the
fan can spin freely.
Make sure that when closing the grill, the
microswitch contact is activated.
Check the electrical connections.
Check the leaks and fully tighten the connections.
Check the gaskets.
Make sure that the heat insulation/soundproofing is positioned correctly, especially at
the front above the finned coil.
When the relative humidity falls, the phenomenon will disappear.
In any case, the formation of some droplets of
water inside the appliance does not indicate a
malfunction.
Slowly pour a bottle of water into the bottom
of the coil to check drainage; if necessary,
clean the pan and/or increase the slope of the
drain pipe.
The connection pipes and valves are not
properly insulated.
Check the insulation on the pipes.
The fan is touching the structure.
Check the filters and clean them if necessary.
The fan is unbalanced.
An unbalanced fan will cause excessive vibrations on the unit: replace the fan.
Check the filters and clean them if necessary
Clean the filters
EN 05/2013 FDL2-i SLIM
13
COD. xxxxxxxxxx_00
Sede Legale: Via L.Seitz, 47 - 31100 Treviso
Sede Amm.va: Via Sarson, 57/S - 36061 Bassano del Grappa (VI) - Italia