DSC Impassa (SCW9055,SCW9057)
Wiring the MN01-4G Cellular Communicator
and Programming the Panel
CAUTION: It is advised that an experienced alarm installer programs the panel as further programming may be
required to ensure proper performance and use of the full functionality.
Do not route any wiring over circuit board.
Full panel testing and signal confirmation must be completed by the installer.
Wiring the MN01-4G to the Alarm Panel
NEW FEATURE: For MiNi01-4G-V2, the status of the panel can be retrieved not only from the status PGM but now
also from the Open/Close reports from the dialer. Therefore, wiring the white wire and programming of the status
PGM of the panel is optional.
Wiring the white wire is necessary only if the Open/Close reporting is disabled.
IMPORTANT NOTE: The Open/Close reporting needs to be enabled during the initial pairing procedure.
1 of 2
Programming the DSC Impassa Alarm Panel via the Keypad
Enable Contact ID reporting:
Keypad Display
Enter Section:
Enter Section:
Toggle Option:
Enter Section:
DFFFFF
Enter Section:
Enter data:
Enter Section:
Enter Data:
Enter Section:
Toggle Option:
Enter Section :
Toggle Option:
Enter Section:
Toggle Option:
Enter Section:
Toggle Option:
Keypad
entry
*85555
015
7#
301
123456#
310
1111
350
03030303
351
1#
367
1#
380
1#
381
7#
#
Action description
To enter in Programming mode
To enter menu “Third System options”.
Option 7 must be off (TLM disabled).
To enter menu” First phone number”.
Enter actual or non-existing number (any number will do, 123456 is an example).
To enter menu “System account code”.
Enter 4-digit account number (1111 is an example) to receive the events from
To enter “Communicator Alarm Format” options.
03 is for Contact ID (03030303 is to set all 4 phone lines).
To program phone 1 communicator call direction.
Toggle 1 to ON for alarms (it has to appear on screen).
Open/Close Communicator Cell directions.
Toggle 1 to ON to enable Open/Close reports (it has to appear on screen).
Enter First Communication Options.
Toggle 1 to ON, 3 to off to enable communications.
Enter Second Communication Options.
Toggle 7 to OFF, to enable automatic reporting.
To manually program the reporting codes in the menu 381, enable option 7 to
ON and then set the desired reporting codes in menus 320 to 348.
Exit Programming mode.
Program Keyswitch zone and output:
Keypad Display
Enter Section:
Enter Section
Toggle Option
Enter Section
Enter Data :XX
Enter Section
Toggle Option
Enter Section
Toggle Option
Toggle Option
Enter Section:
Enter Data: XX
Enter Data: XX
Keypad
entry
*85555
206
1
003
22#
013
1#
133
9
7#
009
00
05
#
Action description
To enter in Programming mode
Enter Zone Assignment
Toggle option 1 to ON to enable the Keyswitch zone.
Zone 33 Keyswitch (on zone 33 because the first 32 are wireless)
22 is for the Zone Type Keyswitch.
Enter First System Options (to select I/O as Input or PGM)
When panel is defaulted press the toggle buttons until 1 is ON and 2 is OFF.
Enter I/O Programming for zone 33 (First 32 are wireless zones)
Press 9 to move to option 9‐16.
Make sure that option 15 is selected (shows as 7 on the second screen).
This standard mode of operations REQUIRES a resistor across the STC.
Enter I/O Programming
Enter 00 to program zone Type, I/O 1
Enter 05 to program Armed Status on I/O 2, XX is default value
Exit Programming mode.