Instruction manual for HMW11

SURFACE MOUNT HIGH BAY MOTION SENSOR HMW11
Installation and Instruction Manual
1. Technical Specifications
2. Installation
Product type
High bay microwave motion sensor (Tri-level control)
Operating voltage
120~277VAC 50/60Hz
Rated load
Resistive:700W@120V; 1600W@220-277V;
Warnings:
1. Installation must be carried out by a qualified engineer in accordance with local regulations.
2. Disconnect supply before installing.
3. Install to a solid surface - vibrations may cause mis-triggering.
4. Ensure environmental conditions are suitable for electronic equipment
Capacitive:400VA@120V; 800VA@220-277V;
Power consumption
< 1W
Detection angle
360
Detection area (DxH)
12 x 12m (Maximum)
Mounting height
15M(Maximum)
Detection range
10% / 50% / 75% / 100%
Hold time
2s / 30s / 1min / 5min / 10min / 15min / 20min / 30min
Stand-by time
0s / 10s / 1min / 5min / 10min / 30min / 1h / +
Stand-by dimming level
10% / 20% / 30% / 50%
C - Surface box
B - Facia Cover
Infrared receiver
HF Sensor module
8
Daylight threshold
2 ~ 500Lux, Disable
Warmming up time
20s
Operating temperature
-20 C ~ +50 C
IP rating
IP42
o
32.5
53.7
o
Photocell
LED indicator
o
Rotary switch preset
A - Control Board
3. Rotary Switch Settings
Direct junction “J” box mounting
0
1
2
3
4
5
6
7
8
9
A
B
C
D
E
F
Detection
range
Hold
time
Stand-by
time
100%
100%
100%
100%
100%
100%
100%
100%
100%
100%
100%
75%
50%
100%
100%
100%
5s
1min
5min
5min
5min
5min
5min
10min
10min
10min
10min
10min
10min
30min
30min
5s
10s
5min
10min
30min
0s
+∞
+∞
10min
30min
+∞
+∞
+∞
+∞
+∞
+∞
10s
Stand-by
dimming level
10%
10%
10%
10%
Disable
10%
30%
10%
10%
10%
30%
10%
10%
10%
30%
10%
Daylight
threshold
Disable
2Lux
10Lux
30Lux
10Lux
30Lux
Disable
2Lux
10Lux
30Lux
Disable
30Lux
10Lux
50Lux
Disable
2Lux
Note: settings can also be changed by remote control HRC-11. The last action controls.
4. Functions
a. Separate control board (A) from facia (B)
& Surface box (C). C is not required.
b. Make electrical connections to control board
(A). See detailed wiring diagram on next page.
c. Secure control board (A) to junction box.
d. Set-up sensor modes as per sections 3 & 4
of this manual.
e. Clip facial plate (B) to control board (A).
Surface mount assembly
a. Separate control board (A) from facia (B) &
Surface box (C).
b. Securely mount surface box (C) to a flat and
solid surface.
c. Make electrical connections to control board
(A). See detailed wiring diagram on next page.
d. Set-up sensor modes as per sections 3 & 4 of
this manual.
e. Secure control board (A) to surface box (C).
f. Clip facial plate (B) to control board (A).
50.2
Channel
Rotary switch preset (Please
see the location in 2. Installation)
29
A rotary switch is built inside the sensor for
scene selection / fast programming. Total
16 channels available:
4.3 Manual Override
With the help of push-switch, this sensor maybe over-ridden by the end-users to switch on/off
the lights manually, or adjust the light brightness during motion hold-time. This makes the
product more user-friendly and offers more options to fit for extra-ordinary demands.
* Short push (<1s): on/off function;
ON → OFF: the light turns off immediately and cannot be lighten for a certain time (equals
to hold time preset) even there is movement is detected. After this period, the sensor goes
back to auto sensor mode.
OFF → ON: the light turns on 100% and goes to auto sensor mode, even when ambient
Lux level exceeds the daylight threshold.
* Long push (>1s): adjust the maximum brightness (between 10% and 100%) during
hold-time. Both the settings on remote control and push switch can
overwrite each other, the last adjustment remains in memory.
4.1 Tri-level Control (Corridor Function)
Hytronik builds this function inside the motion sensor to achieve tri-level control, for some areas require a
light change notice before switch-off.
It offers 3 levels of light: 100%-->dimmed light-->off; and 2 periods of selectable waiting time: motion
hold-time and stand-by period; Selectable daylight threshold and freedom of detection area.
4.2 Lux Off Function
4.4 Semi-auto Function (Absence Detection)
The motion sensor is employed, but only activated on the manual press of the push switch,
The light remains on during presence and dims down in absence, eventually switching off
automatically after the stand-by time has expired.
Note: in this mode, the push terminal used for the ‘manual on’ switch input.
End-user can choose either function 4.3 or 4.4 for application. Default function is 4.3.
The built-in daylight sensor can measure ambient natural light and switch off the fixture automatically
whenever artificial light is not required (natural light lux level exceeds daylight threshold).
Note: if the stand-by time is preset at "+∞", the fixture never switches off even when natural light
is sufficient.
HMW11-20170309-A1
5. Wiring Diagram
6. Detection Pattern
0
L
N
L
N
P L’ N N L
LED Driver
+
1-10V
-
HMW11
1-10V
Ceiling mounted height(m)
6
-+
10%
30%
50%
75%
12
Note: if neither function 4.3 nor 4.4 is desired, simply leave the “push” terminal disconnected.
7. Description of the
Button Functions
(remote control HRC-11)
Permanent ON/OFF [ button 1 ]
Detection range [ zone 8 ]
Press button 1 to select permanent ON or permanent OFF mode.
* Press button 2 / 4 to resume automatic operation.
Press buttons in zone
50% / 10%.
Daylight threshold [ zone 9 ]
Press buttons in zone 9 to set the daylight sensor at 2Lux / 10Lux /
50Lux / 100Lux / 300Lux / 500Lux or Disable.
Note: To set daylight sensor at 100Lux / 300 Lux / 500Lux, press
button 3 Shift at first.
2
, all settings go back to the rotary switch settings.
Auto Mode [ button 4 ]
Press button 4 to initiate automatic mode. The sensor starts working
and all settings remain as before the light was switched ON/OFF.
Semi-auto Mode [ button 3 & 4 ]
Hold time [ zone 11 ]
6
1. Press button 3 Shift (the red LED is on for indication),
2. press button 4 to initiate semi-auto mode. The fixture is manually on
by push-switch and automatically off in semi-auto mode.
8
Press button 5 , the light output shifts between 80% and 100%.
Note: the function of “Sensor off” and “Twilight” are disabled.
Press buttons in zone 11 to set the hold time at 2s / 30s / 1min /
5min / 10min / 15min / 20min / 30min.
Note: 1.To set hold-time at 30s / 5min / 15min / 30min, press button
3 Shift at first.
2. 2s is for test purpose only, stand-by period and daylight
sensor settings are disabled in this mode.
*To exit from Test mode, press button 2 or any button in zone 11 .
7
Power output [ button 5 ]
10
Brightness +/- [ button 6 ]
Press button
6
to adjust the light brightness between 10%~100% .
Scene prog. [ zone 7 ] (One-key-commissioning)
11
12
13
14
HRC-11
Ambient daylight threshold [ button 10 ]
1. Press button 3 Shift, the red LED is on for indication.
2. Press button 10 , the ambient lux level is sampled and set as the
new daylight threshold.
2
5
3
9
to set detection range at 100% / 75% /
RESET [ button 2 ]
Shift [ button 3 ]
4
8
Press button
Press button 3 , the LED on the top left corner is on for indication.
All values / settings in RED are in valid for 20 seconds.
1
Ceiling mounted detection pattern (m)
1. Press button “Start” to program.
2. Select the buttons in 8 “Detection range”, 9 / 10 “Daylight threshold”,
11 “Hold time”, 12 “Stand-by time”, 13 “Stand-by dimming level” to
set all parameters.
3. Press button “Memory” to save all the settings programmed in the
remote control.
4. Press button “Apply” to set the settings to each sensor unit(s).
For example, to pre-set detection range 100%, daylight threshold
Disable, hold time 5min, stand-by time +∞, stand-by dimming level
30%, steps should be:
Press button 7 Start, button 8 100%, 10 Disable, 3 Shift, 11 5min,
3 Shift, 12 +∞ , 13 30%, 7 Memory. By pointing to the sensor unit(s)
and pressing 7 Apply, all settings are passed on the sensor(s).
Stand-by time [ zone 12 ]
Press buttons in zone 12 to set the stand-by period at 0s / 10s /
1min / 5min / 10min / 30min / 1h / +∞.
Note: “0s” means on/off control; “+∞” means bi-level control, 100%
on when motion detected, and remains at the stand-by dimming
level when no presence after hold-time.
Stand-by dimming level [ zone 13 ]
Press buttons in zone 13 to set the stand-by dimming level at 10% /
20% / 30% / 50%.
Dual tech & RF mode [ zone 14 ]
All buttons in zone
14
are disabled.
8. Trouble Shooting
MALFUNCTION CAUSE REMEDY
The fixture does not light up
CAUSE
REMEDY
Incorrect daylight threshold setting
Adjust daylight threshold setting
Faulty fixture
Replace fixture
No power supply
Check power to sensor
Detection zone not targeted
Check detection area setting
The fixture is always on
Continued movement in the detection zone
Check detection area setting
The fixture is on when it should not
Sudden change in temperature due to weather (wind, rain, snow) or air
expelled from fans, open windows
Adjust zone, change installation site