product data - Nilan Belgium

PRODUCT DATA
COMFORT 1200 BY NILAN
Ventilation & passive heat recovery
Commercial
Passive
heat recovery
Ventilation
< 1400 m3/h
COMFORT 1200
The Comfort 1200 is a ventilation unit suitable for central ventilation of residential buildings, schools, offices and business facilities with a ventilation requirement of up to 1400 m3/h.
Every component has been carefully selected with a view to unsurpassed quality and each component is tested throughout the
entire production process, as are the finished units before leaving the factory. This quality control reflects our high standards,
which not only exceed market requirements but also take them
several steps further.
Modulating bypass
An automatic bypass valve directs the fresh air past
the heat exchanger when waste heat recovery is not
necessary, thus conserving energy.
Automatic control
The Comfort 1200 is supplied with an integrated CTS 602
control, which is operated by the enclosed control panel.
The modern CTS 602 control communicates Modbus
RTU RS485. A CTS system using this type of
communication can easily be connected to the device.
Filters
The Comfort 1200 is supplied with bag filters. An M5
filter in the air exhaust and an F7 filter for fresh air are
supplied as standard.
The CTS 602 control has a built-in timer controlled
alarm for change of filter. It is possible to install a pressure controlled filter monitor (accessorie).
Doors
The large doors allow easy access for the changing
the filters, as well as for servicing of the unit.
Frost protection
An electric heater can be purchased for frost protection.
This prevents the formation of ice in the counterflow
heat exchanger in the event of long periods of frost.
2
COMFORT 1200 BY NILAN
Counterflow heat exchanger
Heat recovery is achieved by two counter flow heat
exchangers made of highly corrosion resistant marine aluminium. The counterflow heat exchangers have an energy
efficiency of more than 80% and prevent odours being
transferred from the extracted air to the supply air.
The CTS 602 control allows for cooling recovery.
Plug fans
The two fan sections consist of energy-efficient EC motors
with built-in motor controllers operated by a 0-10V signal.
The efficient fan wheels haverear facing impellers and are
extremely quiet.
Construction
The Comfort 1200 is housed in a strong frame structure
of Aluzinc with 50 mm insulation.
Base
The Comfort 1200 is delivered with a robust, built-in base.
Heating elements
External water or electric heating elements, regulated
by the CTS 602 control, can be purchased.
Pressure control
The extraction and/or supply fan can be operated
with the aid of a pressure transmitter.
The water-heating surface can be built into the unit.
3
COMFORT 1200
Technical specifications
Dimensions (W x D x H)
1815 x 825 x 970 mm
Weight
230 kg
Min. Airvolume
400 m3/h
Max. Airvolume
1400 m3/h
Power consumption
500W
Power supply
230 V (±10 %), 50/60 HZ
Max. phase
13 A
Standby power
4W
Plate type casing
Aluzinc steel plate
Heat exchanger type
Aluminium counterflow heat exchanger
Filter class
Standard bagfilters M5 Extract air and F7 Fresh air
Duct connections
Ø 315 mm
Condensate drain
PVC, Ø 20×1.5 mm
External leakage underpressure (*1)
< 1.45 %
External leakage overpressure (*2)
< 2.14 %
Internal leakage (*3)
< 2.90 %
Tightness class
IP31
*1 At ± 250 Pa and 1200 m3/h according EN 308/EN 13141-7.
*2 At ± 100 Pa and 1200 m3/h according EN 308/EN 13141-7.
*3 At ± 100 Pa and 1200 m3/h according EN 308/EN 13141-7.
Motor and motor control
Motor type
EC-Engine
Motor class in accordance with IEC 60034-30
IE3 (Premium efficiency)
Voltage input
1 x 230 V
Current overload protection
Built-in
Control signal with third party control system
0 - 10 V DC
Fluid temperature (air)
-20 / +40 °C
Ambient temperature (operating)
-20 / +40 °C
4
COMFORT 1200 BY NILAN
Functional diagram
TC
T3
3
T2/T7
6
2
T9
T8
1
T10
T7
T4
4
5
Connections
Automation
T2/T7: Supply air sensor
T9/TC: Heating element frost protection
T3: Extract air sensor
T4: Discharge air and defrost sensor
T8: Fresh air sensor
T10: Room sensor
1: Fresh air
2: Supply air
3: Extract air
4: Discharge air
5: Condensate drain
6: Electric and water heating
5
PLANNING DATA
Nilan units are tested in accordance with the valid standards of accredited independent test institutes.
Capacity
Capacity of standard unit as a function of qv and Pt, ext.
SFP values according to EN 13141-7 are for standard units with M5-filter in extract air, F7-filter in fresh air and no heating element.
SFP values comprise the unit´s total power comsumption incl. control.
Conversion factor:
J/m3
3600
= W/m3/h
Pt ext [Pa]
600
500
400
300
2100 J/m3
1800 J/m3
200
1500 J/m3
1000 J/m3
100
qv [m3/h]
0
200
400
600
800
1000
1200
1400
1600
1800
2000
qv [l/s]
100
150
200
250
300
350
6
400
450
500
COMFORT 1200 BY NILAN
Temperature efficiency
Temperature efficiency for unit with counterflow heat exchanger according to EN308 (dry).
Temperature efficiency EN308: ɳ t = (tsupply air-tfresh air)/(textract air-tfresh air)
ηt (%)
100
95
90
85
80
75
70
65
qv [m3/h]
60
200
400
600
800
1000
1200
1400
1600
1800
2000
qv [l/s]
60
100
150
200
250
300
350
400
450
500
Sound data
Sound data for qV = 1200 m3/h and Pt, ext = 250 Pa according to EN 9614-2 for surfaces and EN 5136 for ducts.
Sound output level LWA drops with falling air volume and falling back pressure.
Sound output level LpA at a given distance will depend on acoustic conditions in the place of installation.
Sound output level (LWA)
Oktavband
Hz
Surface
dB(A)
Supply air
dB(A)
Extract air
dB(A)
Fresh air
dB(A)
Discharge air
dB(A)
63
48
66
58
59
65
125
46
63
57
58
63
250
44
69
64
66
68
500
33
69
60
61
67
1.000
26
71
54
54
71
2.000
27
71
50
51
72
4.000
28
66
47
47
69
Total ±2 dB(A)
51
77
67
69
77
7
PLANNING DATA
Heating elements (accessory)
Water heating element (for internal fitting)
Entreprenøren skal sørge for frostsikring af rørinstallationen
Mixer
proposal
Forslagcircuit
til blandekreds
70°C
40°C
CTS Brugerpanel
CTS2
ESC
P
°C
ENTER
P=20kPa
Safety
switch
Sikkerhedsafbryder
max. 3m
T10 (accessory) can be mounted in a
extraction valve or duct
B2
CN16
CN1
1
2
3
4
5
6
7
8
9
10
CN2
IF
CN6
2
1
RS1
RS2
1
2
3
4
5
6
7
8
9
10
2
1
4
3
2
1
R5
R6
R7
R8
6
5
4
3
2
1
CN17
R9
R10
R11
R12
1
2
3
4
CN20
CN7
4
3
2
1
R4
R3
1
2
3
4
5
6
7
8
CN3
CN5
CTS1
T3
5
4
3
2
1
4
3
2
1
5
4
3
2
1
2
1
T2/T7
Supply air
CN8
CN9
CN10
CN11
CN12
B3
T9
CN13
CN14
T8
Fresh air
Switch
for
user choise
Kontakt for
brugervalg
(Tilbehør)
(accessory)
°C
B1
Extract air
T10
T15
Strømforsyning
Power
supply
1N 230V 50Hz max. 1x13A
M5
°C
ON
The operating panel must be placed
in a dry, frost-free location.
°C
Y4
OFF
T4
Discharge air
UF
T2/T7: Supply air sensor
T9: Heating element frost protection
T3: Extract air sensor
T4: Discharge air and defrost sensor
T8: Fresh air sensor
T10: Room sensor
Electrical heating element (duct mounted)
The operating panel must be placed
in a dry, frost-free location.
CTS Brugerpanel
CTS2
ESC
Strømforsyning
Power
supply
1N
230V 50Hz
max. 1x13A
T10 (accessory) can be mounted in a
extraction valve or duct
Sikkerhedsafbryder
Safety
switch
B2
CN16
CN1
1
2
3
4
5
6
7
8
9
10
CN2
CN6
RS1
RS2
1
2
3
4
5
6
7
8
9
10
2
1
6
5
4
3
2
1
R9
R10
R11
R12
CN20
T8
4
3
2
1
R5
R6
R7
R8
CN17
1
2
3
4
CN7
2
1
4
3
2
1
R4
R3
1
2
3
4
5
6
7
8
CN3
IF
2
1
CTS1
T3
CN5
Fresh air
OFF
ON
T15
Power
supply
Strømforsyning
Kontakt forfor
brugervalg
Switch
user (Tilbehør)
choise
(accessory)
B1
Extract air
T10
ENTER
5
4
3
2
1
4
3
2
1
5
4
3
2
1
T2/T7
T7
CN8
CN9
CN10
CN11
CN12
0,63 m
CN13
CN14
T4
UF
8
Supply air
1m
Discharge air
COMFORT 1200 BY NILAN
Capacity - Heating element (accessory)
Electrical heating surface
The electrical heating surface is fitted in the air inlet duct at a distance of min. 2 x duct
diameter from the system´s fresh air inlet connection pipe (normally min 400 mm.)
and connected to the CTS 602 control panel and 3 x 400 V supply.
The electrical heating surface can supply up to 6 kW of heat.
Water heating element for internal fitting
The water heating element is designed to be built into the system and must be
connected to the primary heating supply and the CTS 602 control. The water heating
element includes copper pipes and aluminium fins.
Capacities can be seen in the table below.
Capacity water heating element
Water side
Temperature
input/output
[°C]
40/30
60/40
70/40
Air side
Flow
Pressure drop
Output
Flow
[m3/h]
Temperature
before WHE*
[°C]
Temperature
after WHE*
[°C]
Pressure drop
over WHE*
[Pa]
[l/h]
[kPa]
[kW]
156
2.2
1.8
400
16
29.2
4.2
206
249
3.6
2.4
600
16
27.7
8.1
5.1
2.9
800
16
26.6
13.0
286
6.6
3.3
1000
16
25.7
18.7
319
8.0
3.7
1200
16
25.0
25.2
350
9.5
4.1
1400
16
24.5
32.4
142
1.8
3.3
400
16
40.0
4.2
188
2.9
4.3
600
16
37.1
8.1
226
4.1
5.2
800
16
35.1
13.0
260
5.2
6.0
1000
16
33.5
18.7
290
6.4
6.7
1200
16
32.3
25.2
318
7.5
7.3
1400
16
31.3
32.4
107
1.0
3.7
400
16
42.9
4.2
140
1.7
4.8
600
16
39.5
8.1
168
2.3
5.8
800
16
37.2
13.0
192
3.0
6.6
1000
16
35.4
18.7
214
3.6
7.4
1200
16
34.0
25.2
234
4.2
8.1
1400
16
32.9
32.4
* Water heating element.
9
AUTOMATION
CTS602 Control
The Comfort 1200 is controlled using its CTS 602 operating
panel, featuring a wide range of functions, e.g., menu-controlled operation, weekly programme settings, filter monitor
with timer, fan speed adjustment, summer bypass (free cooling), post-heating element control, error messages etc.
The CTS 602 comes with factory settings, including a default
setting which can be customised to operational requirements
to achieve optimum operation and utilisation of the system.
The operating panel must be placed in a dry, frost-free location, at least 1.5 m above floor level and at least 0.5 m from
any corner. Avoid placing the panel on an external wall or in
areas in direct sunlight.
Operating instructions for the CTS 602 can be found in a separate user manual supplied with the unit.
External communication
The CTS 602 control unit communicates by default with
Modbus RTU RS485 communication. A CTS system using this
form of communication can easily be connected to the unit.
Nilan units have an open Modbus communication, i.e. not only
can the unit be monitored, but its operation can also be set in
the same way as it can via the operating panel.
CTS / Computer
Konverter
Modbus
The protocol is set up by default for a Modbus RTU 30
address, but can be set to a value between 1 and 247.
A Modbus converter allows you to connect one or more units
to a computer to monitor and control the unit.
10
COMFORT 1200 BY NILAN
Functional overview
+ Standard
- Accessories
3 levels
The control function is divided into 3 levels: User/Service/Factory with various options at each level
+
Weekly plan
There is an option for you to set your own weekly programme.
+
User option 1
This allows you to override the operating mode in the main menu via an external potential-free contact
or PIR sensor.
+
Alarms
Alarm log featuring the last 16 alarms.
+
Filter monitor
Filter monitor with timer (factory setting of 90 days). Adjustable to 30/90/180/360 days.
+
Pressure controlled
filter monitor
It is possible to purchase Comfort 1200 with a pressure controlled filter monitor
-
Bypass
Bypassing the outdoor air reduces heat recovery, enabling the desired supply air temperature to be
maintained spring, summer and autumn.
+
Air quality
Allows you to choose whether to switch humidity sensors and/or CO2 sensors on and off.
-
Humidity control
Allows you to set a higher or lower ventilation step in the case of high/low air humidity.
-
CO2 control
Allows you to set a higher or lower ventilation step in the case of a high/low CO2 level.
-
Air exchange
Allows you to select a low ventilation step in the case of low outside temperatures and air humidity.
+
Defrost function
Temperature-based automatic function for defrosting the heat exchanger.
+
Frostprotection
In case of failing heating system, the unit is turned off to avoid further cooling with a risk of the water
heating coil frost bursting.
+
Temperature control
Allows you to select the temperature sensor which will control the unit.
• T15 ROOM (panel sensor)
• T10 EXT (fitted in a representative extraction valve)
• T3 EXTRACT (extract air)
Room low
Stops the unit at a low room temperature. Hereby is cooling of the home avoided in case of a failing
central heating system. Standard set to OFF. Can be set from 1 to 20 degrees and is controlled by:
• T15 ROOM (panel sensor)
• T10 EXT (fitted in a representative extraction valve)
• T3 EXHAUST (extract air)
+
Room control
Allows you to set the regulator to control the room temperature.
+
Air volume
Allows you to set four ventilation steps. Supply air and extract air are set individually.
Step 1 < 25% - Step 2 < 45% - Step 3 < 70% - Step 4 < 100%
+
Fire alarm
This allows you to connect fire-detecting thermostats, smoke detectors and other fire alarm contacts.
In case of an alarm, smoke dampers are closed and the unit stops.
+
Joint alarm
Outlet for joint alarm
+
Constant pressure control
Allows control from both the extract air and supply air side.
-
Cooling
Via bypass.
This allows you to choose whether to run the system at a higher or the highest ventilation step during
cooling.
The weekly programme has an option for setting cooling at night.
+
Intake air control
Allows you to set the regulator to control the intake air temperature/supply air
(only available if the control unit has been configured for a supply-heating element).
+
External heating element
• Temperature sensor T7 is an supply air sensor
• Integrated frost protection for external water heating element
• Motorised valve and circulation pump control unit
-
External electric heating
element
• Temperature sensor T7 is an supply air sensor
• Overheating protection
-
Delayed start-up
There is a possibility for a delayed start-up by the fans, when a closing damper is installed.
+
Expansion PCB
Allows you to make additional connections, e.g.
• User option 2 overrides User option 1 (e.g. connecting an EM box)
• Up to 500 W direct
• Can give the signal for external heating if the defrost function is used
• Switching the central heating system on/off
-
Reset
Allows you to restore the factory settings.
+
Manual test
Allows you to test the unit’s functions manually.
+
Language
Option for setting the relevant language (Danish/Finnish/Norwegian/Swedish/German/English/
French).
+
11
+/-
OPERATION
Frost protection
All ventilation units with a counterflow heat exchanger will ice
up if the outdoor temperature is below freezing for a
prolonged period.
ɳt[%]
Consideration must be given to whether the unit’s operation
can be protected during a lengthy period of frost or whether it
is acceptable to decrease its operation.
Temperature efficiency
The extracted air condenses when it is cooled down during heat
recovery. The high temperature efficiency will slowly turn the
condensate to ice, which will block up the counterflow heat
exchanger unless action is taken to remedy this.
With pre-heater
tAußen > -3°C
tAußen < -3°C
Defrost function
Operation Ice building
In homes which are occupied at night, it would be advisable to
protect the unit against frost when the outdoor temperature
is coldest by using a pre-heating element. On the other hand, if
the ventilation is for an office, it may be acceptable to decrease
the operating level at night.
Defrost
Ice building
Defrost
The energy used for the preheating is not wasted, as it ensures
a constant high temperature efficiency
Frost protection
No
Normal operation
After 30 min.
Outdoor temperature
< -3 °C
Yes
Yes
No
Pre-heater
installed
Defrost function
starts when:
Outdoor temp < 1 °C (T8)
Discharge air < 3 °C in 5 min.
Normal operation secured
until outdoor temp. < -12 °C
When outdoor temp. < -12 °C
reduced air volume
Eftervarmeflade
monteret
Ja
Nej
1. The heating element goes up in
operation
2. The bypass damper is opened and
leads the outdoor air past the
heat exchanger
3. Warm exhaust air is blown
through the heat exchanger
4. The ice melts
1. Bypass damper opens
2. The intake motor switches off
3. Warm extracted air will flow
through the heat exchanger
4. The ice is melting
Defrosting stops when:
Discharge air > 7°C (T4)
12
DIMENSIONAL DRAWING
COMFORT 1200 BY NILAN
Right model
Fresh air
Discharge air
100
100
1015
414
297
970
297
825
414
414
Ø 315
100
1015
412,5
960
825
1817
Condensation drain
13
100
412,5
412,5
960
100
297
970
1817
297
414
Supply air
970
Extract air
ACCESSORIES
Top cover
If Comfort 1200 is going to be installed outside, it is possible to order a top cover which
protects the unit against rain and snow.
Pressure transmitter
The extraction and/or supply fan can be operated with the aid of one or two pressure
transmitters.
Water heating element incl. regulation
The supply temperature can always be raised to the required level using a water
heating element. The water heating element is designed to be built into the unit and
must be connected to the primary heating supply. Supplied with two-way adjustment
valve, temperature sensor and frost thermostat.
Electrical heating surface incl. regulation
When you fit an electrical heating surface, you can raise the fresh air temperature
to the desired level at any time. The electrical heating surface is supplied ready to
fit into the fresh air duct and, for easy fitting, the device is pre-fitted with all the
required sensors.
Electrical pre-heating element (Frost protection)
An electrical pre-heating element heats up the outdoor air before it enters the unit.
This avoids having to defrost the unit, resulting in a loss of power.
There are temperature sensors supplied to be fitted in the ducts.
Expansion PCB
The expansion PCB provides additional functions for the CTS 602 control unit, e.g.,
controlling the EM-box (see list of functions on page 7).
Installationset
Vibration absorbers and a water trap for the condensation outlet.
Heating cable
To protect the condensation outlet against frost, a 3 metre-long self-regulating
heating cable can be ordered.
14
DELIVERY
AND HANDLING
COMFORT 1200 BY NILAN
Ø 315
414
Transport and storage
Comfort 1200 comes in factory packaging that protects it during transport and storage. Comfort 1200 must be stored in a dry
place in its original packaging until installation.
297
The packaging should only be removed immediately prior to installation.
100
1015
412,5
1817
Installation conditions
825
During installation, future service and maintenance should be
taken into account. We recommend a minimum gap in front of
and behind the unit of 96 cm.
Service clearance
(unit shown from above)
Installation of electric
heating element
Electric heating elements (accessories) are fitted in the duct. The
fitter should ensure that there is a safe distance of at least 15
cm between the electric heating element and any inflammable
material. The heating element must be insulated using
fire-resistant insulation material.
The electric heating element must be connected by an authorised electrician.
Min. 15 cm
Electric pre-heating element with
Electric heating element
temperature sensor
Min. 63 cm
Min. 63 cm
15
960
The unit must be installed level for the sake of the
condensate drain. The condensate drain requires clearance
of min. 12,5 cm under the drain nozzle.
INFORMATION FROM A TO Z
414
297
297
970
414
Ø 315
1015
100
100
412,5
412,5
960
825
1817
Brochure
Product data
General information
about the solution
and its benefits.
Technical information
to ensure correct
choice of solution.
Nilan A/S
Nilanvej 2
8722 Hedensted
Danmark
Tlf. +45 76 75 25 00
Fax +45 76 75 25 25
nilan@nilan.dk
www.nilan.dk
User manual
Detailed guide for
Detailed guide for instal- regulation of the
lation and initial adjust- solution to ensure
ment of the
optimum day-to-day
solution.
operation.
Drawings
Tender documents
and 3D drawings are
available to download for planning
purposes.
Visit us at www.nilan.dk to find out
more about our company and solutions,
download further information and find
your nearest dealer.
Ver. 2.05 - 2017.09
WWW.NILAN.DK
Installation
instructions
Nilan A/S assumes no responsibility for any errors or omissions in the printed information material or for loss or damage that may follow from the use of such published materials - whether such loss of damage is caused by errors or
inexpediencies in the material or otherwise. Nilan A/S reserves the right without prior notice to change products and information material. All trademarks are the property of Nilan A/S. All rights reserved.
Nilan develops and manufactures premium-quality, energy-saving ventilation and heat pump solutions
that provide a healthy indoor climate and low-level energy consumption with the greatest consideration for
the environment. In order to facilitate each step in the construction process – from choosing the solution
through to planning, installation and maintenance – we have created a series of information material which
is available for download at www.nilan.dk.
Download PDF