PCSAU1439A
Warning
Ask a qualified installer or contractor to install this product. Do not try to install the product by yourself.
Improper installation can result in water or refrigerant leakage, electrical shock, fire or explosion.
Use only those parts and accessories supplied or specified by Daikin. Ask a qualified installer or
contractor to install those parts and accessories. Use of unauthorised parts and accessories or
improper installation of parts and accessories can result in water or refrigerant leakage, electrical
shock, fire or explosion.
Read the user's manual carefully before using this product. The user's manual provides important
safety instructions and warnings. Be sure to follow these instructions and warnings.
If you have any enquiries, please contact your local importer, distributor and/or retailer.
Cautions on product corrosion
1. Air conditioners should not be installed in areas where corrosive gases, such as acid gas or alkaline gas, are produced.
2. If the outdoor unit is to be installed close to the sea shore, direct exposure to the sea breeze should be avoided. If you need to install
the outdoor unit close to the sea shore, contact your local distributor.
Air Conditioning System
HEAT PUMP [50Hz]
Inverter series
Specifications, designs and other content appearing in this brochure are current as of October 2015 but subject to change without notice.
c All rights reserved
10/15 SS
PRODUCT RANGE
50
Series
60
71
100
125
140
CEILING MOUNTED
CASSETTE TYPE
Page 7
Round Flow
FCQ50KAVEA
Indoor unit
Outdoor unit
CEILING SUSPENDED TYPE
FCQ60KAVEA
RZQS50AV1
NEW
FCQ71KAVEA
RZQS60AV1
NEW
RZQS71AV1
NEW
FCQ100KAVEA
RZQS100AV1
RZQS100AY1
NEW
FCQ125KAVEA
RZQS125AV1
RZQS125AY1
NEW
FCQ140KAVEA
RZQS140AV1
RZQS140AY1
NEW
Page 11
Indoor unit
Outdoor unit
FHQ50DAVMA
RZQS50AV1
FHQ60DAVMA
RZQS60AV1
FHQ71DAVMA
RZQS71AV1
FHQ100DAVMA
RZQS100AV1
RZQS100AY1
FHQ125DAVMA
RZQS125AV1
RZQS125AY1
FHQ140DAVMA
RZQS140AV1
RZQS140AY1
WALL MOUNTED TYPE
Page 13
FAQ71CVEA
Indoor unit
Outdoor unit
RZQS71AV1
FAQ100CVEA
RZQS100AV1
RZQS100AY1
OUTDOOR UNIT
Page 15
Outdoor unit
Inverter series
Series
RZQS50AV1
RZQS60AV1
RZQS71AV1
50
60
71
RZQS100AV1
RZQS100AY1
RZQS125AV1
100
RZQS125AY1
RZQS140AV1
125
RZQS140AY1
140
CEILING MOUNTED
CASSETTE TYPE
Page 7
Round Flow
Indoor unit
Outdoor unit
FCQ71KAVEA
RZQ71LV1
FCQ100KAVEA
RZQ100LV1
FCQ125KAVEA
RZQ125LV1
FCQ140KAVEA
RZQ140LV1
OUTDOOR UNIT
Page 15
Outdoor unit
1
RZQ71LV1
RZQ100LV1
RZQ125LV1
RZQ140LV1
2
Achieved higher COP
"Nav Ease"
Wired Remote Controller
Inverter series
Complies with MEPS
COP
3.59
4.02
Clear Display
4.46
3.89
3.85
4.05
3.51 3.89
3.18
Dot matrix display
3.65
FCQ50KAVEA
FCQ60KAVEA
FCQ71KAVEA
RZQS50AV1
RZQS60AV1
RZQS71AV1
What is COP
(Coefficient of Performance)
CEILING MOUNTED
CASSETTE TYPE
Heating
Cooling
1
2
2
Heating
Cooling
1
2
Heating
1
Cooling
FCQ100KAVEA FCQ125KAVEA
FCQ140KAVEA
RZQS100AV1/Y1 RZQS125AV1/Y1 RZQS140AV1/Y1
Round Flow
Note :
1
Rated cooling capacities are based on the
following conditions: Indoor temp., 27°CDB,
19.0°CWB; outdoor temp. 35°CDB, 24.0°CWB.
Equiv. refrigeration piping, 7.5 m (horizontal).
2
Rated heating capacities are based on the
following conditions: Indoor temp., 20°CDB,
outdoor temp., 7°CDB, 6°CWB. Equiv.
refrigeration piping, 7.5 m (horizontal)
COP is equal to capacity (kW) divided by power consumption (kW), and the larger the COP value, the higher
the energy efficiency, enabling cooling and heating with less electricity and increasing the energy saving
performance.
High COP models
CEILING MOUNTED CASSETTE TYPE
50
Round Flow
Cooling
CEILING SUSPENDED TYPE
NEW
COP
60
71
Weight
3
98 kg
140
Heating
4.26 4.02 4.46 4.05 3.89 3.65
Cooling
3.48 3.38 3.28 3.23 3.15 3.04
Heating
3.43 3.33 3.23 3.22 3.10 3.24
Cooling
---
---
3.18 3.13
---
---
Heating
---
---
3.43 3.26
---
---
Reduced installation
work thanks to light,
compact outdoor unit.
990 mm
75 kg
125
3.94 3.59 3.85 3.89 3.51 3.18
Compact and lightweight
1,170 mm
100
NEW
NEW
Convenience
Setpoint range set
Weekly schedule
Setpoint auto reset
Multilingual display
Off timer (programmed)
Wired Remote Controller
BRC1E62
Comfortable
Inverter series
Enhanced comfort with Inverter
Soft starter is
unnecessary, making
electrical installation
work much simpler.
Inverter performs variable control of frequency,
which determines air conditioner’s power performance.
Non-inverter
At startup, full power is used to achieve the set temperature quickly.
Then, the capacity is adjusted according to the outdoor temperature
changes and subtle indoor load changes to achieve fine capacity control
resulting in a more stable room temperature.
Non-inverter type air
conditioners must be
switched on and off
repeatedly, causing
large fluctuations of the
room temperature.
Running
current
Cooling operation
Inverter
Temp
990
mm
RQ100LV1A
RZQ100LV1
Inverter series
Reduced by
180 mm
Reduced by
23 kg
Starting
current
Time
Running
current
Set temp
Cools a room
in less time
Small temp.
difference
Time
At startup, inverter raises frequency
smoothly, eliminating the starting
current spike.
Time
Inverter power control
Non-inverter type air conditioner
WALL MOUNTED TYPE
Height
Guide on display
Energy saving
2
Heating
1
Cooling
Heating
Cooling
1
2
2
Heating
1
Cooling
1
Large buttons and arrow keys
Backlight display
3
2
Simple operation
Current
3.94
4
4.26
Current
Energy Efficient
Quiet operation
Night quiet operation function
The Automatic night quiet mode
will initiate 8 hours after the peak
temperature is reached in the
daytime, and normal operation
will resume 10 hours after that.
RZQS50/60AV1
RZQS71AV1
RZQS100AV1/Y1
RZQS125AV1/Y1
Reducing noise will reduce capacity
slightly.
Note :
3
Anechoic chamber conversion value, measured according
to JIS parameters and criteria. During operation these
values are somewhat higher owing to ambient conditions.
4
Value when cooling. Value will differ when heating.
RZQS140AV1/Y1
Inverter series
RZQ71LV1
RZQ100/125LV1
RZQ140LV1
Inverter series
Sound pressure level3 (dB(A))
Rated4
Night Quiet Mode
48
50
53
54
54
44
46
49
50
50
49
51
54
45
47
50
4
Reuse of existing piping
Benefit1
*Only available with RZQS-A series.
Reduces replacement time & cost by simplified installation
Simplified Installation
Enables simplified air conditioner replacement with minimal impact on operations.
When considering air conditioner replacement,
do the following things concern you?
Conventional
installation process
for replacement of
air conditioning
For how long will the business have to close down?
While replacement work is going on, how will sales be affected?
NEW
Won’t the costs be high and work period longer because scaffolding
is necessary for pipe replacement?
Refrigerant recovery and units removal
Quicker
Removal of
existing piping
installation
Reuse of
existing
piping
solved by Daikin!
Enables Increased capacity & Higher EER/COP
Upgrade to air conditioners featuring the latest technology and enjoy greatly
improved energy efficiency.
class
φ9.5
class
φ9.5
φ15.9
φ15.9
3
53%
46%
UP
UP
3.89
3.51
4
2.41
2.55
2
Cooling EER : 2.41
Cooling
FCQ125KAVEA
RZQS125AV1
Heating COP : 2.55
Cooling EER : 3.51
5
Outdoor unit difficult to access.
Multiple units are being upgraded at the same time.
Airtightness test
Quick
installation
thanks to
cleaning-free
pipe reuse
Vacuum drying
Test operation
Heating
Upgrade to
compact
new outdoor
unit
Piping
left as is
Upgrade
to new
indoor
unit
Technology
Advanced technology including use of corrosion resistant EEV, acid neutralisers
and improved compressor reliability enables the re-use of existing piping*
without the need to flush the piping for a simplified replacement process.
An acid neutraliser agent is added to disable
acids (chlorine ions), which cause corrosion.
Heating COP : 3.89
For example, compared with R22 non-inverter units of 15 years ago, in the latest R410A
series some units use smaller diameter piping which means they can achieve greater
cooling capacity by reusing existing piping.
As a result, the greater capacity units ensure better performance to cope with the
increasing amount of heat generated by office equipment.
Carry-in and installation of units
Particularly convenient in these circumstances
Stronger refrigerating
machine oil
1
FHYC71KVE
RY71KV1
Cleaning of piping
Test operation
Pipes are buried and making new pipe installations difficult.
COP
Connection of pipe cleaning machine
Removal of pipe cleaning machine
Test operation
Quicker
installation
Vacuum drying
*Strict conditions must be adhered to, please refer to the installation manual and Engineering Data Book for further details
including pipe sizes (if pipes are to be re-used)
R410A
12.5kW
installation
Vacuum drying
Airtightness test
Normally, when you replace air conditioners, in addition to replacing indoor and
outdoor units, replacement of piping involves high costs and lengthy work periods.
And, the more installed units you have, the greater the cost for connecting them,
especially if they are installed in high places or embedded.
Leave it to Daikin! Since Daikin can carry out upgrades using your existing piping,
you can get the work done faster than ever before.
R22
7.1kW
Quicker
Airtightness test
Carry-in and installation of units
Where feasible, by reusing existing pipes*, we cut your
work cost and reduce work time.
Benefit2
Refrigerant recovery and units removal
Carry-in and installation of units
Installation of new piping
These
problems
are
If existing piping that can
be reused needs cleaning:
with
Refrigerant recovery and units removal
How to minimize inconvenience to tenants, who only leave the
space vacant on weekends?
Installation process
for replacement
Highly corrosion resistant
electronic expansion valve
Highly reliable
compressor
Durability of compressor is improved
by adoption of filter or accumulator
to collect solid foreign substances.
Acid neutraliser
Acid (chlorine ion)
Filter or
Accumulator
Compressor
Refrigerant pipe
*Strict conditions must be adhered to, please refer to the installation manual and Engineering Data Book for further details including pipe sizes
(if pipes are to be re-used)
6
CEILING MOUNTED CASSETTE TYPE
Round Flow
Cassette air conditioner with 360°
uniform airflow sets the standard
Heat pump
FCQ50/60/71/100/125/140KA
Avoids uneven temperature and discomfort caused by drafts
Comfort enhanced by Round Flow!
360° airflow
Air movement is gentle
with Round Flow
With uniform temperature
distribution
Enhanced Comfort
Airflow
distribution
creates uniform
comfort throughout
the space.
Greater comfort
Accessory required for indoor unit
Wired LCD remote controller
"Nav Ease"
BRC1E62
Note: Remote controller cable is not
included and must be procured
locally.
360° airflow can
maintain comfort
even if air
discharge speed is
lower.
Velocity decreases by
25% when set
temperature is raised
1℃ to 1.5℃.
Room remains
comfortable even
when set
temperature is
raised 1℃.
Adapts easily to the installation space
As air flows out from corner outlets, comfort spreads more evenly.
Typical flow patterns
There are a total of 23 flow patterns.
All-round flow
3-way flow
(E.g., installed in
middle of ceiling)
(E.g., installed
near a wall)
L-shaped
2-way flow
Opposite
2-way flow
Option
Wireless LCD remote controller
A signal receiver must be added to the indoor unit.
BRC7F634F
Signal receiver unit
(Installed type)
Wireless remote controller is supplied
in a set with a signal receiver.
4-way flow also possible.
(E.g., installed in
a corner)
(E.g., installed in
a long room)
Note: Whatever the discharge direction, the same type of panel is used. If installing for other than all-round flow, an air discharge outlet sealing material (option) must be used to
close each unused outlet.
Operation sound increases when using 2-way or 3-way flow.
Grime prevention and antibacterial coating: Makes cleaning easier
External panels are treated with a coating that helps to
Treated
Untreated
repel dirt
surface
surface
To prevent dirt sticking to the
external panels, they have
been coated with a surface
treatment
Silver ion anti-bacterial
drain pan
A built-in antibacterial treatment that uses
silver ion in the drain pan prevents
the growth of slime, bacteria, and mould
that cause smells and clogging.
7
Resists
soiling
Non-flocking flaps
Condensation does not easily form on
and dirt does not cling to non-flocking
flaps.
It is easy to clean.
Grimy
surface
• Condition after exposure
to the smoke of 600
cigarettes in 1 m3
enclosed space.
Filter has anti-mould and
antibacterial treatment
Helps prevents mould and
microorganisms growing out of the dust
and moisture that adheres to the filters.
8
CEILING MOUNTED CASSETTE TYPE
Unified square panels
Compact body and quiet operation
Panel size is the same for all models, FCQ50-140KA.
It is easy to maintain a neat appearance when multiple
units are installed in the same room.
950
95
mm
0m
Indoor unit
50KA
60KA
71KA
100KA
125KA
140KA
Same for
all models
m
Optimal comfort and convenience
assured by 2 air discharge modes
Air direction
Standard setting1
Desired
situation
Standard setting to
prevent draft.
Auto-swing
Setting to prevent soiling
of ceiling2 (field setting)
Recommended for shops with
light coloured ceilings that
must be kept spotless.
Auto-swing between
15° and 60°
Auto-swing between
25° and 60°
Settable to 5 different
levels between 15° and 60°
Settable to 5 different
levels between 25° and 60°
Draft prevention
(In heating mode)
At heating startup and thermo OFF, air discharge
is automatically set to a near horizontal 25˚ or 30˚
to prevent direct exposure to cool air drafts.
Auto air
direction control
The air direction is set automatically to the
memorised position of the previous air direction.
Note:
1
Air direction is set to the standard position when the unit is shipped from the factory.
The position can be changed from the remote controller.
2
Closing of the corner discharge outlets is recommended.
Suitable for high ceilings
Even in spaces with
high ceilings, a
comfortable airflow
is carried down to
the floor level.
Standard
Setting
3.6
m
3.2
m
Setting
4.2
m
When all round flow is selected, ceilings up to 4.2 m in height can be
accommodated. (100-140KA)
Criteria for ceiling height and number of air discharge outlets
(Ceiling height is reference value)
Number of air discharge outlets used
50–71KA
Standard
Ceiling
High ceiling
height
High ceiling
100–140KA
All round 4-way 3-way 2-way All round 4-way 3-way 2-way
flow
flow
flow
flow
flow
flow
flow
flow
2.7 m 3.1 m 3.0 m 3.5 m 3.2 m 3.4 m 3.6 m 4.2 m
3.0 m 3.4 m 3.3 m 3.8 m 3.6 m 3.9 m 4.0 m 4.2 m
3.5 m 4.0 m 3.5 m 4.2 m 4.5 m 4.2 m -
Note: Factory settings are for standard ceiling height and all-round flow.
High ceiling settings (1) and (2) are set with the remote controller by field setting.
Two selectable temperature-sensors
Sound pressure level
High
Middle
35
35
35
43
44
44
Low
31.5
31.5
31.5
37.5
39
40
28
28
28
32
34
36
Quick and easy to install
Just 256 mm high. Installable in tight
ceiling spaces (50–71KA)
The condition of the drain pan and
drain water can be checked by
removing the drain plug and
suction grille
*1 298 mm high with 100–140KA
*2 308 mm high with 100–140KA
e
en th e!
p
o
t
l
Jus on gril
i
suct
Drain plug
Options required for specific operating environments
High-efficiency filter unit
Available in two types: 65% and 90% colorimetry.
Filter chamber
266 mm *2
256 mm *1
High-efficiency filter
Fresh air intake kit
Please use if you think the temperature and humidity
inside the ceiling exceeds 30°C and RH 80%,
respectively.
Top panel insulation(1)
Insulation for decoration panel
Side panel insulation
Suspension bracket insulation
Note:
If the wireless remote
controller is installed, a signal
receiver unit is housed in one
of the adjuster pockets.
Outside
The units can be installed in the following different ways.
Chamber type (without T-duct joint)
Note 3.4
KDDP55B160
Flexible duct
(procured locally)
T-duct joint
(procured locally)
Suction
chamber
Intake duct
(procured locally)
(duct length: 4 m max.)
Connection
chamber
Top panel insulation(2)
Top panel insulation(3)
Note 1.2
Using this kit, a duct can be
connected to take outdoor air
in.There are two chamber types
that have intake in two places: with
T-duct joint and without T-duct joint.
Insulation kit for high humidity
Each corner of the
unit has an Adjuster
Pocket that lets you
easily adjust the
unit's suspended
height.
Chamber type (with T-duct joint)
Note 3.4
KDDP55B160K
Flexible duct
Panel spacer
All models can be installed without
using lifter because of the light weight
Installed in any direction
T-duct joint
Use when only minimal space is available between
drop ceilings and ceiling slabs.
Intake duct
(procured locally)
(duct length: 4 m max.)
Connection
chamber
KDDP55X160
40mm
Note: Some ceiling constructions may hinder installation.
Contact your Daikin Dealer before installing your unit.
Sealing material of air discharge
outlet
Sealing material block air discharge openings not
used in 2-way or 3-way blow.
Branch duct
(direct-connection round duct)
A round duct can be attached without the need
for a chamber.
850 mm
Suction
chamber
Direct installation type
Panel spacer
Since the orientation of
the suction grille can
be adjusted after
installing, the direction
of the suction grille
lines can be unified
when multiple units
are installed.
Drain pump is
equipped as
standard
accessory with
850 mm lift
Easier to maintain
Duct flange
(with insulation material)
Intake duct
(procured locally)
Note: 1 Use of options will increase operating sound.
2 Connecting ducts, fan, insect nets, fire dampers, air filters, and other parts
should, as required, be procured locally.
3 When a local-procured fan is used, an interlock with air conditioner is
necessary.Optional PCB(KRP1C63)is required for interlocking.
4 It is recommended that the volume of outdoor air introduced through the kit is
limited to 10% of the maximum airflow rate of the indoor unit. Introducing higher
quantities will increase the operating sound and may also influence temperature
sending.
A flanged port for direct connection of a round
duct is provided. An existing branch duct chamber
can also be fitted (square slit hole).
175 mm
Transparent drain socket
See page 21
See page 21
Switchable fan speed: High/Middle/Low
Control of airflow rate has been improved from 2-step to 3-step.
9
dB(A)
Easy height adjustment
5-levels
air direction
setting
Hot start
Round Flow
DIII-NET communication standard
Connection to a centralised control system
is available, no need for option card.
Low gas pressure detection
See page 22
10
CEILING SUSPENDED TYPE
Comfortable airflow travels
throughout the room
The latest stylish
model
Installation flexibility for
freedom of design
Sophisticated
design
Flexible installation
The unit fits more snugly
into tight spaces.
Flap neatly closes
when not in use.
Heat pump
NEW FHQ50/60/71/100/125/140DA
White colour
The technology of the DC fan motor, wide
sirocco fan, and large heat exchanger
combine for greater airflow and quiet
operation
Wired Remote Controller
"Nav Ease"
BRC1E62
Note: Remote controller cable is not
included and must be procured
locally.
Auto swing (up and down) and louvers
(left and right by hand) bring comfort to
the room
Louver manually adjusts for straight or
wide angle airflow
Wireless LCD remote controller
A signal receiver must be added to the indoor unit.
BRC7GA53
Signal receiver unit (Installed type)
Wireless remote controller is supplied in a
set with a signal receiver.
Drain pipe connection can be done
inside the unit. Refrigerant and drain
pipe outlets are at the same opening.
600
mm
Drain pump kit
(built inside
the unit)
DIII-NET communication standard
Connection to a centralised control system is available, no need
for option card.
All wiring and internal servicing can be done
from under the unit
Easier piping work for
rear side by removable
frame
Easy maintenance
Non-flocking flap
Suitable for high ceilings
Easy-clean, flat surfaces
It is easy to wipe dirt off the flat side and lower surfaces of the unit.
50-71DA
Standard
High ceiling
Condensation does not easily form on and
dirt does not cling to non-flocking flap.
Non-flocking flap
It is easy to clean.
4.3
m
3.5
m
100-140DA
50-71DA
2.7m or less
2.7m~3.5m
100DA
3.8m or less
3.8m~4.3m
125/140DA
4.3m or less
-
Note: Factory settings is “standard”.
“High ceiling” are set with remote controller by field setting.
Two selectable temperature-sensors
See page 21
Switchable fan speed: High/Middle/Low
Programme "Dry"
11
or more
Drain pump kit (option) includes a silver ion
antibacterial agent that assists in preventing
the growth of slime, bacteria, and mould that
cause smells and clogging
Option
140CA
30 mm
or more
*Water used in the test-run can be drained from the air
discharge opening rather than from the side as was
formerly the case.
Drain pump kit (option) can
be easily incorporated
Comfortable
Accessory required for indoor unit
30 mm
See page 21
Quiet operation
Indoor unit
50/60DA
71DA
100DA
125DA
140DA
dB(A)
Sound pressure level
High
37
38
42
44
46
Middle
35
36
38
41
42
Low
32
34
34
37
38
Oil resistant grille
Oil-resistant plastic is used for the air suction grille. This satisfies
durability in restaurants and other similar environments.
Note: Intended for use in salons, dining rooms, and ordinary sales floors, this specification
is not suitable for kitchens or other harsh environments.
12
WALL MOUNTED TYPE
Compact design and
easy installation
Design and
installation flexibility
Compact &
Sophisticated design
FAQ100
FAQ 71/100C
9kg lighter
340
mm
FAQ71C
1,200mm
370mm shorter
FAQ100BV FAQ100C
Height
360mm
340mm
Width
1,570mm
1,200mm
Depth
200mm
240mm
Weight
26kg
17kg
Wired LCD remote controller
"Nav Ease"
BRC1E62
Note: Remote controller cable is not
included and must be procured
locally.
Option
Wireless LCD remote controller
A signal receiver must be added to the indoor unit.
BRC7EB518
Signal receiver unit (Installed type)
Wireless remote controller is supplied in a
set with a signal receiver.
An air discharge
modes ensure
comfortable air
distribution across
the entire room
Back-right pipe
Bottom-right pipe
Drain pump kit is available as option
Installs onto side of unit.
Height of drain up
Comfortable
Accessory required for indoor unit
Back-left pipe
Bottom-left pipe
All maintenance tasks can be carried out via front
access. During servicing, attachment and detachment
of parts is easier.
Fresh white colour
Auto swing (up and
down) and
wide-angle louvers
(left and right by
hand) facilitate
even room
temperature
Right pipe
Left pipe
Maintenance possible from the front
of the unit
Flaps neatly close when not
in use
FAQ100C
6-direction
refrigerant piping
offers greater
installation
flexibility
1,000 mm
Wide-angle
louvers
(by hand)
Drain pump kit
Indoor unit
Drain pump kit can be installed
on either left and right side of
the indoor unit.
Soft material
louver bends
airflow over a
wider area
Auto-swing
Refrigerant
piping
5-level air direction setting
Gettable to 5
different levels
Comfort even on the far side of the room
To carry air to the far side of long
rooms, extra-high airflow adds 10%
more fan speed the "high" setting.
Air discharge setting is selected
from the remote controller by field
setting.
Interlock control
As an energy saving feature, the room air conditioning
unit can be interlocked with the key card system.
Through 3rd party
building
management
system, it is
possible to
interlock air
conditioning and
lighting.
Interlock
DIII-NET communication standard
Connection to a centralised control system is available,
no need for option card.
Easy cleaning
Removable and washable grille
Switchable fan speed: High/Middle/Low
Auto airflow rate (When BRC1E62 is used)
Programme "Dry"
Dehumidification is microprocessor controlled to prevent abrupt and
uncomfortable changes in air temperature.
13
Flat panel, easy to wipe dust off
Non-flocking flaps
Condensation does not easily form on and dirt does not
cling to non-flocking flaps.
It is easy to clean.
14
OUTDOOR UNIT
Technology for energy efficiency
Inverter series
The high efficiency compressor to
achieve a high COP
1
RZQS71AV1
RZQS100AV1/Y1
RZQS125AV1/Y1
RZQS140AV1/Y1
RZQ71LV1
RZQ100LV1
Easy installation and maintenance
Pre charged for up to 30 metres
If the refrigerant piping length does not
exceed 30 m, there is no need for on-site
gas charging.
75 m piping length
(Applicable to RZQS100–140A and RZQ100–140L
outdoor units)
RZQS50-71A
RZQ71L
Pre
charged1
Max.
length
RZQS100-140A
RZQ100-140L
50 m
Max. level
difference
Cooling is efficient even in winter
when indoor temperatures are higher
than those outside, such as in
underground public spaces or offices
with many computers.
The outer panel for the piping connection part
of the front, right side and backside can be
removed and is easier for post-installation
piping work.
(Equivalent
length 90m)
40
30
20
Low gas pressure detection function
Note : 1Additional refrigerant charging is required if the
refrigerant pipe is longer than the length.
Effective gas monitoring reduces the labor required
for operation, maintenance, and repairs.
10
0
Height
Weight
1,170 mm
98 kg
990
mm
990 mm
75 kg
-20
48
50
53
54
54
49
51
54
Night Quiet Mode
44
46
49
50
50
45
47
50
Note : 1Anechoic chamber conversion value, measured according to JIS
parameters and criteria. During operation these values are
somewhat higher owing to ambient conditions.
2
Value when cooling. Value will differ when heating.
15
Capacity (%)
RZQS71AV1
RZQS100AV1/Y1
RZQS125AV1/Y1
RZQS140AV1/Y1
RZQ71LV1
RZQ100/125LV1
RZQ140LV1
Rated2
50
WB
Heating
-15˚C
DB
Note: Data are based on studies conducted under
controlled conditions at a Daikin laboratory.
WB
Outdoor temp(˚CDB)
Outdoor temp(˚CWB)
Non-treated fin
Aluminium
Anti corrosion
treated fin
Hydrophilic treatment
Aluminium
Corrosion resistant
resin
The maximum capacity is maintained
within a set level of power
consumption, which makes it possible
to keep a comfortable and effective
demand control.
10 hours
Limitation
0
50
Rated
46 Quiet mode
8:00
12:00 16:00 20:00
Note : 3In case of RZQS71AV1
Quiet mode
0:00
4:00
*1. A neodymium magnet is approximately 10
times stronger than a standard ferrite
magnet.
*2. The torque created by the change in power
between the iron and magnet parts.
RZQS50-71A, RZQ71/100L
RZQS100-140A, RZQ125/140L
>> Swing compressor
Energy savings is
realised, eliminating
the friction and the
leakage of
refrigerant gas.
2
Swing bushing
Refrigerant gas
Piston by incorporated
blade and roller.
>> Scroll compressor
Suction
Sucked gas is compressed in
the scrolling part before the
heated motor, so that the
Discharge
machine compress the
non-expanded gas, resulting in
high efficiency compression.
Aero Spiral Fan
With the bent
blade edge
The Aero Spiral Fan features fan blades with
the bent blade edges, further reducing
turbulence.
Demand Control
Function
100
8 hours
15.5˚C
-5˚C
Large load
High capacity
Scroll section
Motor section
Without the bent
blade edge
Escaping eddies are sucked in by
the bent blade edges, reducing
overall turbulence.
3
DC fan motor
Efficiency improved in all areas compared to AC
motors, especially at low speeds.
DC fan motor structure
Power
consumption
Inverter
series
RZQS50/60AV1
Cooling
Construction
Peak in outdoor temperature
Load (%)
Operation
Sound (dB(A))
Sound pressure level1 (dB(A))
Small load
Low capacity
Heat exchange fins are provided with
anti-corrosion treatment
Reduced by
23 kg
The Automatic night quiet mode will initiate 8 hours after the peak temperature is reached in
the daytime, and normal operation will resume 10 hours after that.
Reducing noise will reduce capacity slightly.
DC motor
Rotational speed
DB
As the bottom frame is subject to
corrosion, a corrosion-proof galvarium
steel plate is adopted to enhance the
durability.
Reduced by
180 mm
Night time quiet operation function
1
Reluctance
DC motor
AC motor
Durability
RZQ100LV1
RQ100LV1A
2
More than 20%
46˚C
-10
Compact and light weight
Reduced installation work
thanks to light, compact
outdoor unit.
3
50
Separation
available
*Pump-down function is available for pre-charged refrigerant
amount.
30 m
Reluctance DC Motor
Wide operation range
(Refrigerant recovery function)
A pump-down switch is provided to make it
easier to collect refrigerant if the unit is to be
moved or layout modified.
75 m
(Equivalent
length 70m)
Suited for year-round
cooling applications
4-direction piping offers greater
layout freedom
Facilitates pump down
30 m
RZQ140LV1
Operation range
Removable part of
bottom frame makes
the piping work easier
Allowed refrigerant piping length and
level difference
RZQ125LV1
Motor efficiency
RZQS50AV1
RZQS60AV1
Compressor equiped with Reluctance DC motor
Daikin DC Inverter models are equipped with the Reluctance DC
motor for compressor.
The Reluctance DC motor uses 2 different types of torque,
neodymium magnet*1 and reluctance torque*2.
This motor can save energy because it generates more power
with a smaller electric power than an AC or previous DC motor.
8:00
8:00
12:00
16:00
20:00 Time
* Required for KRP58M51 (Option)
16
REMOTE CONTROLLER
Optional accessory
Easy-to-read LCD remote controller allows various system
Remote controller options are shown on the page introducing each indoor unit model.
Wired Remote Controller
NEW
"Nav Ease"
control configurations and control of multiple indoor units.
Convenience
Weekly schedule
This simple, contemporary remote controller with
fresh white colour matches your interior design.
The clear, backlight display with large
easy-to-read text makes navigation easy and
provides one-touch control over your in-home
comfort.
NEW
- 5 actions per day can be scheduled for each day of the week.
- The holiday function will disable schedule timer for the days that have been set as
holiday.
- 3 independent schedules can be set. (e.g. summer, winter, mid-season)
College classroom sample (a summer Monday case)
1) 8:30
ON
2) 10:00
The first period starts and the
air conditioner starts the cooling
operation.
ON
OFF
3) 13:00
In the second period, the classroom
is unoccupied and the air conditioner
stops.
ON
4) 15:00
When the third period starts,
operation starts again.
OFF
ON
OFF
After the third period, the classroom
becomes vacant again and the
air conditioner stops.
OFF
BRC1E62
Clear Display
Dot matrix display
Backlight
display
A combination of fine dots
enables various icons.
Large text display is easy to
see.
Multilingual display
Display is available in 11 languages.
LCD wireless remote controller
Energy saving
Auto operation mode
NEW
Until now only the temperature for one point could be
set, but now the new remote controller (BRC1E62)
allows the setting of both Cooling and Heating, and with
the fan operation, mid-range temperatures are
comfortable andoperation is more energy efficient.
Setpoint auto reset
NEW
The wireless remote controller is supplied in a set with a signal receiver.
- Even if the set temperature is changed, it returns to
the preset temperature after a preset period of time.
- Period selectable from
30min/60min/90min/120min.
Signal receiver unit is contained inside decoration panel or indoor unit.
Shape of signal receiver unit differs according to the indoor unit.
Note: The signal receiver unit shown in the photograph is for mounting inside the decoration panel of the
ceiling mounted cassette type.
Restaurant sample
Restaurant opened
27 °C
Wireless remote controller for each indoor unit type
Temperature is set to 27ºC
2 setpoints
Signal receiver unit
(For ceiling mounted
cassette type)
Cooling / Heating
Full tables at lunchtime
20ºC
Heating
operation
NEW
26ºC
Fan operation
Setpoint range set
Cooling
Then is lowered to 24ºC
for crowded room
24 °C
BRC7F634F
Heat pump
BRC7F634F
CEILING MOUNTED CASSETTE TYPE
CEILING SUSPENDED TYPE
BRC7GA53
WALL MOUNTED TYPE
BRC7EB518
Wireless remote controller
operation
- Saves energy by limiting the min. and max. set
temperature.
- Avoids excessive heating or
cooling.
- This function is convenient when
the remote controller is installed
at a place where any number of
people may operate it.
17
(English, German, French, Spanish, Italian, Portuguese, Greek, Dutch, Russian, Turkish, and Polish).
After 30 minutes*
Returns to
Automatically returns to
preset temperature (27ºC)
automatically
27°C
*Setting possible for after 30, 60, 90,
and 120 minutes.
Off timer (programmed)
- Sets and saves setting for an increment of time that
automatically turns off air conditioner after a preset period of
time for each time operation starts.
- Period can be preset from 30 to 180 minutes in10-minute increments.
SkyAir shares common control with the Heat
Reclaim Ventilator and other Daikin
air-conditioning units, thus simplifying interlocking
operations.
LCD remote controller
for SkyAir indoor unit
SkyAir
Indoor unit
Interlocking
Heat Reclaim
Ventilator
18
REMOTE CONTROLLER
FUNCTIONS
Optional accessory
System variation to control multiple indoor units
Control pattern
Control by 1
remote controller
(Basic system)
Control by 2
remote controllers
For control from 2
locations such as in
room and control room,
exits, etc.
Wired remote controller
Wireless remote controller
CEILING MOUNTED
CASSETTE TYPE
CEILING SUSPENDED TYPE
WALL MOUNTED TYPE
Indoor unit
FCQ50-140KAVEA
FHQ50-140DAVMA
FAQ71/100CVEA
Outdoor unit
RZQS50-140AV1
RZQS100-140AY1
RZQ71-140LV1
RZQS50-140AV1
RZQS100-140AY1
RZQS71/100AV1
RZQS100AY1
Functions
overview
Round Flow
Cooling only
Non-polar, double-core
(max. wiring length 500 m)
Signal receiver unit installed
on indoor unit
Auto swing
Swing pattern selection
Draft prevention function (heating)
Not possible
(See note 2, 3)
Connects 2 wired remote
controllers (See note 1)
DC fan mortor (Indoor unit)
Switchable fan speed
Group control
For simultaneous
control of up to 16
indoor units.
Automatic address setting function
Automatic address setting function
Comfort
Signal receiver unit installed
on 1 indoor unit
Control by
external command
Operation and monitoring
is carried out using the
contact signal from the
operation control box in
the monitoring room.
3step
3step
*3
High fan speed mode
Programme “Dry”
High ceiling application
*4
Two selectable temperature-sensors *1
Hot start
(Command from outside)
(Command from outside)
Optional wiring adaptor for
electrical appendices is necessary
Year-round cooling applicable
Night quiet operation *2
Optional wiring adaptor for
electrical appendices is necessary
Central remote controller (option)
Central remote controller (option)
Centralised remote
control
3step
Auto airflow rate
Centralised control of
up to 64 indoor groups
from remote location
up to 1 km away.
Setpoint auto reset *3
Remote
Controller
Setpoint range set *3
Weekly schedule timer *3
Off timer (programmed) *3
Anti-bacterial air filter
Cleanliness
Link by remote
controller group control.
Interlock control
with Heat Reclaim
Ventilator
Heat Reclaim
Ventilator
Heat Reclaim
Ventilator
Can be operated simultaneously
or independently by remote controller
(set by ventilation mode)
Can be operated simultaneously
by remote controller
(set by ventilation mode)
Central remote controller (option)
Central remote controller (option)
Mould-proof air filter
Silver ion anti-bacterial drain pan
Drain pump mechanism
*5
*5
*5
*5
Pre-charged for up to 30 m *2
Work &
servicing
Filter sign
Ceiling soiling prevention
Low gas pressure detection *2
Emergency operation
Zone link control by
centralised control.
Heat Reclaim
Ventilator
Heat Reclaim
Ventilator
Heat Reclaim Ventilator for indoor units within a zone are operated by
interlocking. Can also be operated independently by remote controller.
Self-diagnosis function
Heat Reclaim Ventilator for indoor units within
a zone are operated by interlocking
Auto-restart
Auto-cooling/heating change-over
Note:1BRC1E62 can connect to BRC1E62 only. 2It is not possible to use two wireless remote controllers. 3BRC1E62 cannot connect to wireless remote controller.
Control by 2 remote controllers
Easily adaptable to large-scale, high-function, centralised remote control system.
Central remote controller
DCS302CA61 (Option)
Unified on/off controller
DCS301BA61 (Option)
Control
features
19
Centralised control of on/off by
group or all at once for up to 256
indoor units.
Unified control of weekly schedule
for up to 1,024 indoor units.
Schedule timer sets on/off time in 1 minute units
to be executed twice a day for a week at a time.
With its high functionality, the full
colour “all-in-one” graphic controller
facilitates management of SkyAir
System in a variety of ways.
*5
Interlock control with Heat Reclaim Ventilator
DCS601C51 (Option)
DIII-NET communication standard
Options
Centralised control, with a setting as
simple as it is with a standard
remote controller, of up to 64 groups
(1,024 indoor units) is possible.
External command control
Central remote control
Schedule timer
DST301BA61 (Option)
Group control by 1 remote controller
Others
High-efficiency filter
Fresh air intake kit
Anti corrosion treated heat exchangers *2
Note: *1 : Applicable when wired remote controller is used
*2 : For outdoor units
*3 : Applicable when BRC1E62 is used
*4 : Installable on max. 3.5 m(50-71) and 4.3 m (100-140) high ceiling
*5 : Option
20
FUNCTIONS
Abundance of features that provide comfortable
air-conditioning in stores and offices.
Note: Some features only available on selected models. See overview pages for full list of features applicable to each unit.
Comfort
High-ceiling application
Auto-swing
Delivers comfortable
air-conditioning to all areas, near
to and far from the air-conditioner.
The air flow direction can be
fixed at your desired angle by
the remote controller.
Swing pattern selection
(standard, ceiling soiling prevention)
You can freely set air discharge settings by remote controller.
(1) standard setting
(2) Draft prevention setting
Draft prevention function (heating)
To prevent cold air drafts, automatically adjusts airflow to near
horizontal position when heating initially starts or when the
thermo off.
DC fan motor (indoor unit)
DC fan motor improves efficiency.
Switchable fan speed
High setting provides maximum reach while low setting
minimises drafts.
Auto airflow rate
Airflow rate is automatically controlled in accordance with the
difference between room temperature and set temperature.
High fan speed mode
Applicable for wall mounted type.
You can increase fan speed approximately 10% higher than the
"high" setting.
Programme "Dry"
Dehumidification is a microprocessor controlled to prevent abrupt
and uncomfortable changes in air temperature. Useful for
reducing uncomfortable humidity without uncomfortable cooling
of the room.
Applicable for ceiling mounted cassette type and ceiling suspended type.
Delivers
air-conditioning
comfort all the way
down to the floor in
air-conditioning zones
with high ceilings.
Note:When units are installed on high ceilings, depending on the model, various
restrictions concerning maximum height, air discharge direction, and choice
of options may apply.
Two selectable temperature-sensors
Temperature-sensors are included in the indoor unit and optional
wired remote controller. Temperature sensing closer to the
target area is possible to further
increase the comfort level.
Use the temperature-sensor in the
indoor unit when controlling air
conditioning from another room.
Note: Wireless remote controllers have no
temperature-sensor.
Hot start
Cold air flow is avoided when heating operation starts or when
switching to heat after defrosting.
Year-round cooling applicable
Efficient cooling even in winter when the indoor temperatures are
higher than those outside, such as in underground public spaces
or offices with many computers.
Night quiet operation
The Automatic night quiet mode will initiate 8 hours after the
peak temperature is reached in the daytime, and normal
operation will resume 10 hours after that.
Remote Controller
Setpoint auto reset
Even if the set temperature is changed, it returns to the preset
temperature after a preset period of time.
Setpoint range set
Saves energy by limiting the minimum and maximum set
temperatures. Avoids excessive heating and cooling.
Weekly schedule timer
Up to five operation ON/OFF settings can be programmed per
day for each day of the week. Not only can the time be set for the
operation ON setting, but also the temperature.
Off timer (programmed)
Sets and saves setting for an increment of time that
automatically turns off air conditioner after a preset period of time
for each time operation starts.
Work and Servicing
Drain pump mechanism
Applicable for ceiling mounted cassette type and ceiling suspended type.
Steeper gradient realises more
efficient condensate drainage.
High-lift is especially useful for long
lengths of drain piping.
Pre charged for up to 30 m
If the refrigerant piping length does not exceed 30 m, there is no
need for on-site gas charging.
Filter sign
The filter sign warns you when it is time to clean the filter.
*When using a wired remote controller the sign is displayed in the LCD. When
using a wireless remote controller the filter sign lamp illuminates on the signal
receiver unit.
Ceiling soiling prevention
Applicable for ceiling mounted cassette type.
The air filter has an anti-bacterial treatment to help prevent the
growth of bacteria and mould on it.
Mould-proof air filter
Sanitary filter has mould-resistant treatment.
21
Silver ion anti-bacterial drain pan
A built-in antibacterial treatment that uses silver ion in the drain
pan prevents the growth of slime, bacteria, and mould that cause
smells and clogging.
Insufficient gas charging is normally hard to detect. During test
run after installation and regular inspection, the refrigerant level
is monitored by a microprocessor to maintain proper gas
pressure. Reliability is assured and maintenance and inspection
can be carried out more quickly.
Emergency operation
Even if there is a malfunction elsewhere in the system, the fan or
compressor can still be operated. (depending on the malfunction)
Self diagnosis function
The operating parameters of indoor and outdoor units, and
sensor data at critical locations throughout the system, are
constantly monitored using a microcomputer. To facilitate a quick
response in the event of a malfunction, a message appears on
the LCD of the remote controller and an LED on the unit
illuminates.
Daikin's innovative air discharge mechanism keeps airflow away
from the ceiling. Ceiling cleaning is less frequently required.
Control features
Auto-restart
If there is a power outage while the equipment is operating,
operations will restart in the same mode as before the power cut
when electricity is restored.
Auto cooling / heating change-over
Detects difference in preset temperature and actual room
temperature and automatically switches to cooling or heating
accordingly.
Control by 2 remote controllers
Using 2 remote controllers you can operate the equipment locally
or from a remote location.
Note: When a wireless remote controller is used, remote control by two remote controllers is
not possible.
Group control by 1 remote controller
You can turn up to 16 indoor units on/off with a single remote
controller. (When using connected indoor units, the settings
must all be the same and on/off will be simultaneous.)
External command control
Operation and monitoring is carried out using the contact signal
from the operation control box in the building monitoring room.
*An option is required.
Central remote control
An optional central remote controller enables centralised control
of up to 1024 indoor units (64 groups) from up to 1 km away.
Interlock control with Heat Reclaim Ventilator
Enables interlocking control with external equipment such as
Heat Reclaim Ventilator.
DIII-NET communication standard
Standardly equipped interface enables connection to centralised
control system without need of an adaptor.
Options
High-efficiency filter
Applicable for ceiling mounted cassette type.
Two types are available: 65% and 90% colorimetry.
Cleanliness
Anti-bacterial air filter
Low gas pressure detection
Fresh-air intake kit
Applicable for ceiling mounted cassette type.
You can provide air-conditioning with fresh air from outside.
Convenient for places where a ventilation fan cannot be installed.
Others
Anti corrosion treated heat exchangers
To achieve increased durability by improved resistance to salt corrosion and atmospheric pollution, Anti corrosion treated fin for heat
exchangers (with special coating) are used for the heat exchanger of the outdoor unit.
In high corrosive areas, regular maintenance needs to be carried out.
22
SPECIFICATIONS
CEILING MOUNTED CASSETTE TYPE
Model
Name
Power supply
Cooling capacity1,3
Rated (Min. - Max.)
Heating capacity2,3
Rated (Min. - Max.)
Power consumption
Power supply
Cooling capacity
rated (Min. - Max.)1,3
kW
kW
Cooling1
Heating2
Cooling
Heating
Unit
Colour
Decoration panel
Airflow rate (H/M/L)
Sound pressure level (H/M/L)4
Sound power level (H/L)
Certified Indoor
Operation Range
Outdoor
unit
Colour
Compressor
kW
kW
kW/kW
kW
/s
m /min
dB(A)
dB(A)
mm
mm
kg
kg
°CWB
°CDB
3
kW
kg
dB(A)
dB(A)
dB(A)
mm
kg
°CDB
°CWB
mm
mm
mm
mm
m
m
140
100
125
140
Unit
Decoration panel
Unit
Decoration panel
Cooling
Heating
Type
Motor output
Refrigerant charge (R-410A)
Sound pressure Cooling/Heating
level4
Night quiet mode
Sound power level
Dimensions (HXWXD)
Machine weight
Certified Outdoor Cooling
Operation Range Heating
Liquid (Flare)
Gas (Flare)
Drain
Indoor unit
Outdoor unit
Max. interunit piping length
Piping
connections
Max. installation level difference
Heat insulation
5.0
(3.2-5.6)
6.0
(3.5-7.0)
1.27
1.41
3.94
4.26
6.0
(3.2-6.0)
7.0
(3.5-8.0)
1.67
1.74
3.59
4.02
1 Phase, 220-240 V, 50 Hz
10.0
7.1
(5.0-11.2)
(3.2-8.0)
11.2
8.0
(5.1-12.8)
(3.5-9.0)
1.84
2.57
1.79
2.77
3.85
3.89
4.46
4.05
3 Phase, 380-415 V, 50 Hz
10.0
12.5
14.0
(5.0-11.2)
(5.7-14.0)
(6.2-15.5)
11.2
14.0
16.0
(5.1-12.8)
(6.0-16.2)
(6.2-18.0)
2.57
3.56
4.40
2.77
3.60
4.38
3.89
3.51
3.18
4.05
3.89
3.65
12.5
14.0
(5.7-14.0)
(6.2-15.5)
14.0
16.0
(6.0-16.2)
(6.2-18.0)
3.56
4.40
3.60
4.38
3.51
3.18
3.89
3.65
---------Fresh white
350/292/225
533/433/333
550/467/375
533/433/333
21/17.5/13.5
32/26/20
32/26/20
33/28/22.5
43/37.5/32
44/39/34
44/40/36
35/31.5/28
43/37.5/32
53/46
60/50
61/52
61/54
60/50
298X840X840
256X840X840
50X950X950
24
21
5.5
14 to 25
15 to 27
Ivory white
Hermetically sealed swing type
Hermetically sealed scroll type
1.3
1.6
1.55
3.15
2.9
4.0
2.0
4.0
4.2
(Charged for 30 m)
(Charged for 30 m) (Charged for 30 m)
(Charged for 30 m)
(Charged for 30 m)
48/50
50/52
53/55
53/55
54/56
44
46
49
50
49
66
69
---------69
770X900X320
990X940X320
1,430X940X320
64
75
108
-5 to 46
-15 to 15.5
o/ 9.5
o/ 15.9
VP25 (I.Do/ 25XO.D o/ 32)
o/ 26.0 (Hole)
50 (Equivalent length 70)
75 (Equivalent length 90)
30
Both liquid and gas piping
550/467/375
33/28/22.5
44/39/34
44/40/36
61/52
61/54
4.2
(Charged for 30 m)
54/56
50
----------
140
FCQ140KAVEA
RZQ140LV1
kW
7.1
(3.2–8.0)
10.0
(5.0–11.2)
12.5
(5.7–14.0)
13.6
(6.2–15.5)
kW
8.0
(3.5–9.0)
11.2
(5.1–12.8)
14.0
(6.0–16.2)
16.0
(6.2–18.0)
kW
kW
kW/kW
kW
1.99
2.10
3.57
3.81
2.64
2.84
3.79
3.95
4.02
3.83
3.11
3.66
4.53
4.80
3.00
3.33
/s
m3/min
dB(A)
dB(A)
mm
mm
kg
kg
O
CWB
O
CDB
350/292/225
21/17.5/13.5
35/31.5/28
53/46
256X840X840
533/433/333
32/26/20
43/37.5/32
60/50
kW
kg
dB(A)
dB(A)
dB(A)
mm
kg
O
CDB
O
CWB
mm
mm
mm
mm
m
m
50X950X950
21
Hermetically sealed swing type
1.7
2.08
2.0
2.9
(Charged for 30 m)
(Charged for 30 m)
49/51
45
66
770X900X320
64
50 (Equivalent length 70)
69
990X940X320
75
5.5
14 to 25
15 to 27
Ivory white
44/39/34
61/52
298X840X840
550/467/375
33/28/22.5
44/40/36
61/54
Hermetically sealed scroll type
2.4
3.15
3.15
4.2
(Charged for 30 m)
(Charged for 30 m)
1,170X900X320
98
-5 to 46
-15 to 15.5
o/ 9.5
o/ 15.9
VP25 (I.Do/ 25XO.Do/ 32)
o/ 26.0 (Hole)
75 (Equivalent length 90)
30
Both liquid and gas piping
----------
EER
COP
Indoor
unit
FHQ50DAVMA FHQ60DAVMA FHQ71DAVMA FHQ100DAVMA FHQ125DAVMA FHQ140DAVMA FHQ100DAVMA FHQ125DAVMA FHQ140DAVMA
50
60
Outdoor unit
RZQS50AV1
RZQS60AV1
5.0
(3.2-5.6)
6.0
(3.5-7.0)
1.44
1.75
3.48
3.43
6.0
(3.2-6.0)
6.8
(3.5-8.0)
1.78
2.04
3.38
3.33
kW
kW
kW
kW
kW/kW
kW
Cooling1
Heating2
Cooling
Heating
Colour
Airflow rate (H/M/L)
(H/M/L)4
Sound pressure level
Sound power level (H/M/L)
Dimensions (HXWXD)
Machine weight
Cooling
Certified
Operation range Heating
Colour
Type
Compressor
Motor output
Refrigerant charge (R-410A)
Sound pressure Cooling/Heating
level4
Night quiet mode
Sound power level Cooling/Heating
Dimensions (HXWXD)
Machine weight
Cooling
Certified
Operation range Heating
Piping
Liquid (Flare)
connections
Gas (Flare)
Drain
Indoor unit
Outdoor unit
Max. interunit piping length
/s
m3/min
dB(A)
dB(A)
mm
kg
°CWB
°CDB
kW
kg
dB(A)
dB(A)
dB(A)
mm
kg
°CDB
°CWB
mm
mm
mm
mm
m
m
WALL MOUNTED TYPE
Model
Name
Power supply
Cooling capacity1,3
Rated (Min. - Max.)
Heating capacity2,3
Rated (Min. - Max.)
Power consumption
EER
COP
24
51/53
47
Power supply
Cooling capacity1,3
Rated (Min. - Max.)
Heating capacity2,3
Rated (Min. - Max.)
Power consumption
Indoor unit
250/200/167
15/12/10
37/35/32
54/52/49
235X960X690
25
71
100
125
140
100
125
140
RZQS71AV1 RZQS100AV1 RZQS125AV1 RZQS140AV1 RZQS100AY1 RZQS125AY1 RZQS140AY1
1 Phase, 220-240 V, 50 Hz
10.0
7.1
(5.0-11.2)
(3.2-8.0)
11.2
8.0
(5.1-12.8)
(3.5-9.0)
2.16
3.10
2.48
3.48
3.28
3.23
3.23
3.22
342/283/233 467/400/333
20.5/17/14
28/24/20
38/36/34
42/38/34
60/56/52
55/53/51
235X1,270X690
32
Hermetically sealed swing type
1.6
1.3
1.55
4.0
2.0
2.9
(Charged for 30 m) (Charged for 30 m)
(Charged for 30 m)
48/50
50/52
53/55
44
49
46
66
69
990X940X320
770X900X320
64
75
50
(equivalent length 70)
12.5
(5.7-14.0)
14.0
(6.0-16.2)
3.97
4.52
3.15
3.10
White
517/450/383
31/27/23
44/41/37
62/59/55
13.2
(6.2-15.5)
16.0
(6.2-18.0)
4.34
4.94
3.04
3.24
3 Phase, 380-415 V, 50 Hz
10.0
12.5
13.2
(5.0-11.2)
(5.7-14.0)
(6.2-15.5)
16.0
11.2
14.0
(6.2-18.0)
(5.1-12.8)
(6.0-16.2)
3.10
3.97
4.34
3.48
4.52
4.94
3.23
3.15
3.04
3.22
3.10
3.24
567/483/400 467/400/333
34/29/24
28/24/20
42/38/34
46/42/38
64/60/56
60/56/52
235X1,590X690
38
14 to 25
15 to 27
Ivory white
517/450/383
31/27/23
44/41/37
62/59/55
Hermetically sealed scroll type
3.15
4.2
4.0
(Charged for 30 m)
(Charged for 30 m)
53/55
54/56
49
50
---------69
1,430X940X320
108
-5 to 46
-15 to 15.5
o/ 9.5
o/ 15.9
VP20 (I.D o/ 20XO.D o/ 26)
o/ 26.0 (Hole)
75
(equivalent length 90)
30
Both liquid and gas piping
567/483/400
34/29/24
46/42/38
64/60/56
4.2
(Charged for 30 m)
54/56
50
----------
Inverter series
125
FCQ125KAVEA
RZQ125LV1
---------Fresh white
Model
Name
Max. installation level difference
Heat insulation
100
FCQ100KAVEA
RZQ100LV1
1 Phase, 220-240 V, 50 Hz
CEILING SUSPENDED TYPE
Outdoor
unit
71
FCQ71KAVEA
RZQ71LV1
Indoor unit
Outdoor unit
Power consumption
Dimensions
(HXWXD)
Machine
weight
125
RZQS50AV1 RZQS60AV1 RZQS71AV1 RZQS100AV1 RZQS125AV1 RZQS140AV1 RZQS100AY1 RZQS125AY1 RZQS140AY1
Heating capacity
rated (Min. - Max.)2,3
EER
COP
Indoor
unit
100
Outdoor unit
Sound pressure Cooling/Heating
level4
Night quiet mode
Sound power level
Dimensions (HXWXD)
Machine weight
Cooling
Certified
Operation range Heating
Piping
Liquid (Flare)
connections
Gas (Flare)
Drain
Indoor unit
Outdoor unit
Max. interunit piping length
Max. installation level difference
Heat insulation
Model
Name
71
FCQ50KAVEA FCQ60KAVEA FCQ71KAVEA FCQ100KAVEA FCQ125KAVEA FCQ140KAVEA FCQ100KAVEA FCQ125KAVEA FCQ140KAVEA
Sound pressure level (H/M/L)4
Sound power level (H/L)
Dimensions Unit
(HXWXD)
Decoration panel
Machine
Unit
weight
Decoration panel
Cooling
Certified
Operation range Heating
Colour
Type
Compressor
Motor output
Refrigerant charge (R-410A)
Outdoor
unit
60
Indoor unit
Cooling1
Heating2
Cooling
Heating
Unit
Colour
Decoration panel
Airflow rate (H/M/L)
EER
COP
Indoor
unit
50
54/56
50
1,430X940X320
108
Indoor
unit
71
Indoor unit
FAQ71CVEA
Outdoor unit
RZQS71AV1
kW
kW
kW
kW
kW/kW
kW
Cooling1
Heating2
Cooling
Heating
Colour
Airflow rate (H/M/L)
(H/M/L)4
Sound pressure level
Sound power level (H/M/L)
Dimensions (HXWXD)
Machine weight
Cooling
Certified
Operation range Heating
Colour
Outdoor
Type
Compressor
unit
Motor output
Refrigerant charge (R-410A)
Sound pressure Cooling/Heating
level4
Night quiet mode
Sound power level Cooling/Heating
Dimensions (HXWXD)
Machine weight
Cooling
Certified
Operation range Heating
Piping
Liquid (Flare)
connections
Gas (Flare)
Drain
Indoor unit
Outdoor unit
Max. interunit piping length
Max. installation level difference
Heat insulation
/s
m3/min
dB(A)
dB(A)
mm
kg
°CWB
°CDB
kW
kg
dB(A)
dB(A)
dB(A)
mm
kg
°CDB
°CWB
mm
mm
mm
mm
m
m
7.1
(3.2-8.0)
8.0
(3.5-9.0)
2.23
2.33
3.18
3.43
100
100
FAQ100CVEA
1 Phase, 220-240 V, 50 Hz
300/267/233
18/16/14
45/42/40
61/58/56
290X1,050X238
13
Hermetically sealed swing type
1.55
2.9 (Charged for 30 m)
50/52
46
990X940X320
75
50 (Equivalent length 70 m)
FAQ100CVEA
RZQS100AV1
Fresh white
14 to 25
15 to 27
Ivory white
69
RZQS100AY1
10.0
(5.0-11.2)
11.2
(5.1-12.8)
3.19
3.44
3.13
3.26
3 Phase, 380-415 V, 50 Hz
433/383/317
26/23/19
49/45/41
65/62/58
340X1,200X240
17
Hermetically sealed scroll type
3.15
4.0 (Charged for 30 m)
53/55
49
1,430X940X320
108
-5 to 46
-15 to 15.5
o/ 9.5
o/ 15.9
VP13 (I.D o/ 13XO.D o/ 18)
o/ 26.0 (Hole)
75 (Equivalent length 90 m)
30
Both liquid and gas piping
Note :
1
Rated cooling capacities are based on the following conditions: Indoor temp., 27°CDB, 19.0°CWB; outdoor temp. 35°CDB, 24°CWB. Equiv. refrigeration piping, 7.5 m (horizontal).
2
Rated heating capacities are based on the following conditions: Indoor temp., 20°CDB, 15°CWB; outdoor temp., 7°CDB, 6°CWB. Equiv. refrigeration piping, 7.5 m (horizontal)
3
Capacities are net, including a deduction for cooling for indoor fan motor heat.
4
The operation sound is measured in anechoic chamber. If it is measured under the actual installation conditions, it is normally over the set value due to environmental noise and sound reflection.
Note :
1
Rated cooling capacities are based on the following conditions: Indoor temp., 27°CDB, 19.0°CWB; outdoor temp. 35°CDB, 24°CWB. Equiv. refrigeration piping, 7.5 m (horizontal).
2
Rated heating capacities are based on the following conditions: Indoor temp., 20°CDB, 15°CWB; outdoor temp., 7°CDB, 6°CWB. Equiv. refrigeration piping, 7.5 m (horizontal)
3
Capacities are net, including a deduction for cooling for indoor fan motor heat.
4
The operation sound is measured in anechoic chamber. If it is measured under the actual installation conditions, it is normally over the set value due to environmental noise and sound reflection.
23
24
OPTIONS
Indoor unit
Indoor unit
CEILING MOUNTED CASSETTE TYPE
Name of option
Remark
Decoration panel
Sealing material of air discharge outlet
Panel spacer
Fresh air
Chamber
type
intake kit1
Without T-duct joint
With T-duct joint
Direct installation type
(Colorimetric method 65%)
High-efficiency filter unit
(including filter chamber)
(Colorimetric method 90%)
Replacement
(Colorimetric method 65%)
high-efficiency filter
(Colorimetric method 90%)
Filter chamber
Branch duct chamber
Chamber connection kit2
Insulation kit for high humidity
Wireless type
Heat pump
Remote controller
Navigation Remote Controller
Wired type3 "Nav Ease"
Central remote controller4
Unified ON/OFF controller4
Schedule timer4
intelligent Touch Controller4
Adaptor for wiring5
Wiring adaptor for electrical appendices(2)5
Installation box for adaptor PCB
Remote sensor (for indoor temperature)
Kit name
FCQ50KAVEA FCQ60KAVEA FCQ71KAVEA FCQ100KAVEA FCQ125KAVEA FCQ140KAVEA
BYCP125K-W1
KDBH55K160F
KDBP55H160FA
KDDP55B160
KDDP55B160K
KDDP55X160
KAFP556B160
KAFP556B80
KAFP557B160
KAFP557B80
KAFP552B160
KAFP552B80
KAFP553B160
KAFP553B80
KDDFP55B160
KDJP55B80
KDJP55B160
KKSJ55KA160
KDTP55K80
KDTP55K160
BRC7F634F
BRC1E62
DCS302CA61
DCS301BA61
DST301BA61
DCS601C51
KRP1C63
KRP4AA53
KRP1H98
KRCS01-4B
Note: 1Refer to page 10 for the details.
2
Required for installing high-efficiency filter unit.
3
Wiring for wired remote controller to be procured locally.
4
The indoor unit is equipped standardly with the interface adaptor for SkyAir series. An option is unnecessary.
5
Installation box for adaptor PCB (KRP1H98) is necessary.
For each flow pattern – all round, 4-way, 3-way, 2-way, branch duct connection – the compatibility of each independently installed option
(shown in the column on the left) to accessory options (listed across the top of each table) is shown in the cells where the relevant row and column intersect.
A circle (o) indicates compatibility, and a cross (x) indicates incompatibility. Any options not shown below are not suitable for independent or accessory installation.
Optional accessory parts
Independently installable optional parts
Panel/grille related
Panel spacer1
Operation control related
Wireless remote controller
Auxillary function related
Fresh air intake kit (Chamber type)1,2
Fresh air intake kit (direct mount)
High-humidity operation kit
Filter related
High-efficiency filter2
Panel spacer1
o
o
o
x
o
3-way flow 2-way flow
Optional accessory parts
Independently installable optional parts
Panel/grille related
Panel spacer1
Operation control related
Wireless remote controller
Auxillary function related
Fresh air intake kit (Chamber type)1,2
Fresh air intake kit (direct mount)
High-humidity operation kit
Panel spacer1
o3
o3
o3
x
Branch duct connection
Optional accessory parts
Independently installable optional parts
1
Branch duct
1-way branch / unit 3-way flow
(Chamber type)
2-way branch / unit 2-way flow
(Round duct type)
1-way branch / unit 2-way flow
1
Panel spacer1
o
x
x
Wireless
Fresh air intake kit Fresh air intake kit
remote controller (Chamber type)1,2
(direct mount)
o
o
o
o
o
o
o
o
o
x
x
x
o
o
o
o
o
o
o
o
o
3
x
x
o
o
x
3
o
Wireless
Fresh air intake kit Fresh air intake kit
remote controller (Chamber type)1,2
(direct mount)
o
o
o
o
o
o
High-humidity
operation kit
x
o
x
o
x
Wireless
Fresh air intake kit Fresh air intake kit
remote controller (Chamber type)1,2
(direct mount)
3
o4
o4
o4
High-humidity
operation kit
x
o
x
o
High-humidity
operation kit
x
x
x
High-efficiency
filter2
o
o
o
o
x
High-efficiency
filter2
x
x
x
x
x
High-efficiency
filter2
x
x
x
In some cases, depending on how the unit is embedded in the ceiling, use of branch ducts and fresh air intake kits may not be possible. Before starting installation work make sure to check
whether or not joint installation is possible. In particular, ensure that the lower fixing position caused by the addition of panel spacers is acceptable.
Use a chamber connection kit if two different types of optional chamber are used together. In this case, the fresh air intake kit must be installed in the upper position.
3
It is not possible to use panel spacers in a 2-way flow installation.
4
It is not possible to install a branch duct on the same side to which a fresh air intake kit (direct mount) is installed.
2
25
Name of option
Remark
Fresh air intake kit
Drain pump kit
L-type piping kit (for upward direction)
Remote controller
Wireless type
Heat pump
Wired type1 "Nav Ease"
Navigation Remote Controller
Central remote controller2
Unified ON/OFF controller2
Schedule timer2
intelligent Touch Controller2
Wiring adaptor for electrical appendices
Wiring adaptor for electrical appendices3
Installation box for adaptor PCB
Adaptor box mounting plate
Remote sensor (for indoor temperature)
Electrical box with earth terminal (3 blocks)
Electrical box with earth terminal (2 blocks)
FHQ50DAVMA
FHQ60DAVMA
KKSAP50A56
Note: 1Wiring for wired remote controller to be procured locally.
2
The indoor unit is equipped standardly with the interface adaptor for SkyAir series. An option is unnecessary.
3
Installation box for adaptor PCB is necessary.
WALL MOUNTED TYPE
Name of option
Round flow type: List of optional parts required to achieve different flow patterns
All-round flow 4-way flow
CEILING SUSPENDED TYPE
Remark
FAQ71CVEA
Drain-up kit
Heat pump
Wireless type
Remote controller
Navigation Remote Controller
Wired type1 "Nav Ease"
Remote sensor (for Indoor temperature)
Central remote controller2
Unified ON/OFF controller2
Schedule timer2
intelligent Touch Controller2
Wiring adaptor for electrical appendices3
Installation box for adaptor PCB
Electrical box with earth terminal (3 blocks)
Electrical box with earth terminal (2 blocks)
Noise filter ( For electromagnetic interface use only)
Note: 1Wiring for wired remote controller to be procured locally.
2
The indoor unit is equipped standardly with the interface adaptor for SkyAir series. An option is unnecessary.
3
Installation box for adaptor PCB (KRP4AA93) is necessary.
Outdoor unit
Name of option
Central drain plug
Fixture for preventing overturning
Wire fixture for preventing overturning
Demand adaptor
Name of option
Central drain plug
Fixture for preventing overturning
Wire fixture for preventing overturning
Demand adaptor
RZQS50AV1
RZQS60AV1
KKPJ5F180
KPT-60B160
RZQ71LV1
KKPJ5F180
KPT-60B160
Kit name
FHQ71DAVMA FHQ100DAVMA FHQ125DAVMA FHQ140DAVMA
KDDQ50A140
KDU50P140VE
KHFP5N160
BRC7GA53
BRC1E62
DCS302CA61
DCS301BA61
DST301BA61
DCS601C51
KRP1BA54
KRP4AA52
KRP1D93A
KRCS01-4B
KJB311AA
KJB212AA
Kit name
K-KDU572EVE
BRC7EB518
BRC1E62
KRCS01-4B
DCS302CA61
DCS301BA61
DST301BA61
DCS601C51
KRP4AA51
KRP4AA93
KJB311AA
KJB212AA
KEK26-1A
FAQ100CVEA
Kit name
Heat pump
RZQS100AV1 RZQS125AV1 RZQS140AV1
RZQS71AV1
RZQS100AY1 RZQS125AY1 RZQS140AY1
KKPJ5G280
KKTP5B112
K-KYZP15C
KRP58M51
Kit name
RZQ100LV1
RZQ125LV1
KKPJ5G280
KKPJ5F180
KKTP5B112
KPT-60B160
K-KYZP15C
KRP58M51
RZQ140LV1
KKPJ5G280
KKTP5B112
26
DIMENSIONS (Unit: mm)
CEILING SUSPENDED TYPE
83
105
156
5
17 20 16
210
156
105
102
131 57
Liquid pipe connection
Gas pipe connection
Drain pipe connection
Transmission wiring connection
Remote controller wiring
connection
Air-outlet
Suction grille
Corner decoration cover
Drain hose (accessory)
116
690
Hanging bolt
4-M8~M10
60
157 63
115
12
19 15
4
1
5
6
30 or more
(Service space)
30 or more
(Service space)
1270
The Front
Obstacle
Brand name plate
(Note.2)
Floor side
268
214
221
268
6
76
3
2
7
63
134 59
Position slit hole for taking out in pipe back
(View from the front)
11
235
13
9
1230
(Hanging bolt pitch)
300 or more
(Required space)
For height installation
From the floor side 2500 or more
51
10
8
57
Connection position of fresh air intake kit
φ100(Knock out hole)
120
90
5
83
105
156
4
Notes:
1
Location of unit's Name Plate: Bottom of fan housing inside the suction grille.
2
In case of using wireless remote controller, this position will be a signal receiver.
Refer to the drawing of wireless remote controller in detail.
3
Please do not place the thing been damp and troubled under an indoor unit.
When the case where humidity is 80% or more, and the drain outlet are choked up and the air filter are dirty, dew may fall.
φ45
57
220
103
5
(Required space)
18
Drain piping connection VP20
(For left pipe)
27
90
CEILING SUSPENDED TYPE
[FHQ71DAVMA]
6
7
8
9
175
92
Notes:
Location of unit's Name Plate: Bottom of fan housing inside the suction grille.
In case of using wireless remote controller, this position will be a signal receiver.
Refer to the drawing of wireless remote controller in detail.
3
Please do not place the thing been damp and troubled under an indoor unit.
When the case where humidity is 80% or more, and the drain outlet are choked up
and the air filter are dirty, dew may fall.
175
1500mm
or more
200mm
or more
1500mm or more
The necessary space is 500mm or more when the
air-outlet is blocked with the accessory.
Moreover when the corner areas are blocked
(both right and left of the blocked air outlet),
the necessary space is 200mm or more.
1
2
3
4
5
4
2
197
Notes:
1
Sticking location for manufacture's label
manufacture's label for indoor unit:
Suction grille inner side's electric components box's lid surface
manufacture's label for decoration panel :
Decoration panel's corner decoration cover inner surface
2
In case of using wireless remote controller, this position will be a signal receiver. Refer to the drawing of wireless remote controller
in detail.
3
When the temperature and humidity in the ceiling exceed 30˚C and RH 80% or the fresh air is inducted into the ceiling or the unit
continues 24 hour operation, an additional insulation (thickness 10mm or more of glasswool or polyethylene form) is required.
4
Though the installation is acceptable up to maximum of 910mm square ceiling opening, keep the clearance of 35mm or less
between the indoor unit and the ceiling opening so that
the panel overlap allowance can be ensured.
5
Please do not place the thing been damp and troubled under an indoor unit.
When the case where humidity is 80% or more, and the drain outlet are choked up and the air filter are dirty, dew may fall.
7
157 63
35 or less
(Note 4)
Connection position
of branch duct
(square-shaped type)
2
1
1500mm or more
1500mm
or more
3
115
A
6
90
157
350
Required space
200mm or more
1 Air discharge grille
2 Air suction grille
3 Air filter
4 Gas pipe connection
5 Liquid pipe connection
6 Drain pipe connection
7 Earth terminal (inside the control box) (M4)
8 Hanger
9 Rear pipe penetration cover
10 Top panel penetration cover
11 Right side pipe connection
12 Left back drain pipe connection
13 Left side drain pipe connection
14 Right side drain pipe connection
15 Hole of wall for taking out in pipe back
16 Upward drain pipe connection
17 Upward gas pipe connection
18 Upward liquid pipe connection
19 Power supply wiring and a unit wiring back connection
20 Power supply wiring and a unit wiring upper connection
91
131
197
5
Brand name plate
(Note.2)
Drain piping connection VP20
(For left pipe)
14
φ 45
175
92
256
91
131
197
The Front
Floor side
Position : Hole of wall for taking out in pipe back
(View from the front)
40
60
42
105
35 or less
(Note 4)
Connection position
of branch duct
(round shape type)
27-M4 Prepared hole
30 or more
(Service space)
960
76
55
40
235
300 or more
(Required space)
Obstacle
90
196
C arrow view
57
6
30 or more
(Service space)
220
103
11
5
30
87
100
163
189
195
35
2
85
4
1
210
1
840
2 100=200
160
Position slit hole for taking out in pipe back
(View from the front)
197
For height installation
From the floor side 2500 or more
157
350
ø1
(kn 00
holock
e)
13
57
63
134 59
12
175
5
(Required space)
Hanging bolt
4-M8~M10
260
4
64
50
81
60
5
(Required space)
260
29
95
90
Connection position
of branch duct
(round shape type)
Connection position
of fresh air intake kit
(direct installation type)
30
87
100
163
189
195
210
(Hanging
bolt pitch)
167
160
67
2 100=200 80
213
25
160
2x100=200 80
25
124
67
95
29
C/L
213
80
90
160
160
9
90
19 15
(Hanging
bolt pitch)
280
330
167
93
Connection position of fresh air intake kit
φ100(Knock out hole)
920
(Hanging bolt pitch)
690
5
(Required space)
157
3 55
150
160
298
125
165
20 C/L
350
A
35 or less
(Note 4)
Connection position
of branch duct
(square-shaped type)
1500 or more
(required space)
From the floor side 2500 or more
For height installation
Hanging bolt
4-M8~M10
Connection position
of branch duct
(round shape type)
157
350
ø1
Connection position
(kn 00
of branch duct
ock
hole
(round shape type)
)
90
Connection position
183
of fresh air intake kit
C
arrow
view
(direct installation type)
67
160
16-M4 Prepared hole
55 Connection position
of branch duct
(square-shaped type)
95
167
840
340
80 2 100=200 80
160
256
Connection position
of branch duct
(square-shaped type)
20-M4
Prepared hole
51
10
8
[FCQ100-140KAVEA]
175
29
50
40
160
288
10
850
Adjustable(0~675)
[FCQ100-140KAVEA]
55
95
110
124
130
60
42
35 or less
(Note 4)
Connection position
of branch duct
(round shape type)
C/L
[FCQ100-140KAVEA]
120
214
221
268
2
840
81 2x100=200 85
124
95
167
93
29
280
330
1
64
50
Connection position
of branch duct
(square-shaped type)
B arrow view
116
268
4
55
27-M4 Prepared hole
55
5
1500 or more
(required space)
From the floor side 2500 or more
For height installation
157
150
124
256
125
165
350
3
105
95
110
850
Adjustable(0~675)
80
175
29
20 C/L
50
40
160
246
10
340
80 2 100=200
124
160
124
109
95
Connection position
of branch duct
(square-shaped type)
20-M4
Prepared hole
16-M4 Hole
157
350
[FCQ50-71KAVEA]
7
[FCQ50-71KAVEA]
16-M4 Prepared hole
55 Connection position
of branch duct
(square-shaped type)
B arrow view
Connection position
of branch duct
(square-shaped type)
210
156
105
102
131 57
17 20 16
18
Connection position
85 of branch duct
(round shape type)
2 100=200
160
C/L
80
Drain Connection
Side
81
157
350
6
85 Connection position
of branch duct
(round shape type)
16-M4 Hole
157
350
[FHQ50-60DAVMA]
[FCQ100-140KAVEA]
93
124
950
C
[FCQ50-71KAVEA]
Hanging bolt
4-M8~M10
Connection position
of branch duct
(round shape type)
Note 2
A arrow view
840
2x100=200
124
C/L
160
8
420
55
81
950
Piping Connection
Side
780(Hanging bolt pitch)
860~910(Ceiling opening space) (Note 4)
9
B
860~910(Ceiling opening space) (Note 4)
710(Hanging bolt pitch)
420
[FCQ50-71KAVEA]
130
300
or less
[FCQ50-140KAVEA]
95
110
[FCQ50-140KAVEA]
35
CEILING MOUNTED CASSETTE TYPE
14
Position : Hole of wall for taking out in pipe back
(View from the front)
1 Air discharge grille
2 Air suction grille
3 Air filter
4 Gas pipe connection
5 Liquid pipe connection
6 Drain pipe connection
7 Earth terminal (inside the control box) (M4)
8 Hanger
9 Rear pipe penetration cover
10 Top panel penetration cover
11 Right side pipe connection
12 Left back drain pipe connection
13 Left side drain pipe connection
14 Right side drain pipe connection
15 Hole of wall for taking out in pipe back
16 Upward drain pipe connection
17 Upward gas pipe connection
18 Upward liquid pipe connection
19 Power supply wiring and a unit wiring back connection
20 Power supply wiring and a unit wiring upper connection
28
DIMENSIONS (Unit: mm)
CEILING SUSPENDED TYPE
WALL MOUNTED TYPE
5
11
235
30 or more
(Service
space)
1590
The Front
Obstacle
Brand name plate
(Note.2)
Floor side
Drain piping connection VP20
(For left pipe)
214
221
268
268
6
76
3
2
7
5
83
105
156
4
Notes:
1
Location of unit's Name Plate: Bottom of fan housing inside the suction grille.
2
In case of using wireless remote controller, this position will be a signal receiver.
Refer to the drawing of wireless remote controller in detail.
3
Please do not place the thing been damp and troubled under an indoor unit.
When the case where humidity is 80% or more, and the drain outlet are choked up and the air filter are dirty, dew may fall.
14
Position : Hole of wall for taking out in pipe back
(View from the front)
9
2
1 Air discharge grille
2 Air suction grille
3 Air filter
4 Gas pipe connection
5 Liquid pipe connection
6 Drain pipe connection
7 Earth terminal (inside the control box) (M4)
8 Hanger
9 Rear pipe penetration cover
10 Top panel penetration cover
11 Right side pipe connection
12 Left back drain pipe connection
13 Left side drain pipe connection
14 Right side drain pipe connection
15 Hole of wall for taking out in pipe back
16 Upward drain pipe connection
17 Upward gas pipe connection
18 Upward liquid pipe connection
19 Power supply wiring and a unit wiring back connection
20 Power supply wiring and a unit wiring upper connection
Name plate Note)2
50 or more
(Requred space)
φ45
50 or more
(Required space)
8
3
Piping direction
1
Piping direction
1050
14.5
30 or more
(Service
space)
6
Dimensions
for full open
front panel
104
50 or more
(Requred space)
894
2500 or more
For installation
in high spaces
120 or less
52
φ80 hole
Piping and
Wiring intake
Outside line
φ80 hole
44
300 or more
(Required space)
57
13
57
30 or more
(Required space)
4
1
220
103
105
19 15
1550
(Hanging bolt pitch)
7
60
Mounting location
6
5
4
Approx.345
98
Approx.390
44
Position slit hole for taking out in pipe back
(View from the front)
240
238
290
12
91
131
197
Hanging bolt
4-M8~M10
Approx.400
63
134 59
175
5
(Required space)
690
Piping direction
157 63
90
60
115
35
51
8
197
For height installation
From the floor side 2500 or more
10
9
5
(Required space)
260
116
Connection position of fresh air intake kit
φ100(Knock out hole)
120
90
40
(Hanging
bolt pitch)
210
30
87
100
163
189
195
18 17 20 16
[FAQ71CVEA]
210
156
105
102
131 57
175
92
[FHQ100-140DAVMA]
1
2
3
4
5
6
7
8
9
Approx.475
Notes:
1
Location of unit's of Name Plate:Right side surface of casing
2
In case of using wireless remote controller, this position will be a signal receiver. Refer to the drawing of wireless remote contorller in detail.
3
Please do not place the thing been damp and troubled under an indoor unit. when the case where humidity is 80% or more,
and the drain outlet are choked up and the air filter are dirty, dew may fall.
Front panel
Front grill
Air outlet
Gas piping
Liquid piping
Drain hose
Earth terminal
Right side pipe connection hole
Left side pipe connection hole
WALL MOUNTED TYPE
[FAQ100CVEA]
242
50 or more
(Required space)
Piping direction
Approx.440
240
Dimensions for
full open
front panel
1
50 or more
(Requred space)
Piping direction
1200
79.5
3
Name plate Note)2
Piping direction
1085
120 or less
35.5
φ80 hole
Outside line
Piping and
Wiring intake
45
45
φ80 hole
6
65
Mounting location
5
4
Approx.400
Approx.460
89
Approx.465
Notes:
1
Location of unit's of Name Plate:Right side surface of casing
2
In case of using wireless remote controller, this position will be a signal receiver. Refer to the drawing of wireless remote contorller in detail.
3
Please do not place the thing been damp and troubled under an indoor unit. when the case where humidity is 80% or more,
and the drain outlet are choked up and the air filter are dirty, dew may fall.
29
2500 or more
For installation
in high spaces
50 or more
(Requred space)
8
114
2
14.5
9
30 or more
(Required space)
340
7
1
2
3
4
5
6
7
8
9
Front panel
Front grill
Air outlet
Gas piping
Liquid piping
Drain hose
Earth terminal
Right side pipe connection hole
Left side pipe connection hole
30
DIMENSIONS (Unit: mm)
OUTDOOR UNIT // RZQ125LV1
43
61
350
(345~355)
94
140
43
61
3
94
4
3
4
2
1
7
6
5
2
1
7
7
6
5
422
423
Gas pipe connection
Liquid pipe connection
Service port
Earth terminal M5 (in switch box)
Refrigerant piping intake
Power supply wiring intake
Transmission wiring intake
Drain pipe connection
95
54
19
45
376
16
7 Control wiring intake
8 Drain outlet
30
620
940
3
160
4
2
1
5
145
5
423
95
54
52
13
8
67
71
89
19
9
58
Gas pipe connection
Liquid pipe connection
Service port
Grounding terminal (in switch box)(M5 )
Refrigerant piping intake
Power supply wiring intake
Control wiring intake
Drain pipe connection
295
1
2
3
4
5
6
7
8
5
20
36
201
25
154
179
19
80
145
16
16
142
53
84
95
54
60
223
95
89
80
422
55
19
53
84
95
53
55
340
95
6
5
6 19 99 161
142
19
71
16
5
95
6
7
6
55
5
339
6
53
89
58
6
19
179
7
16
89
60
990
99
5
1
5
7
1430
7
2
153
350
(345∼355)
30
38
320
30
620
30
55
37
30
320
55
37
345
(340∼350)
91
160
3
36
3 Service port
4 Grounding terminal
5 Refrigerant piping intake
6 Power supply wiring intake
4
31
1 Gas pipe connection
2 Liquid pipe connection
191
940
25
203
67
16
91
35
52
13
5
160
38
6
8
80
145
Hole for anchor bolt 4-M12
Hole for anchor
bolt 4-M12
7
19
OUTDOOR UNIT // RZQS100/125/140AV1, RZQS100/125/140AY1, RZQ140LV1
OUTDOOR UNIT // RZQS71AV1, RZQ100LV1
30
5
58
70 102 117
58 16
1
2
3
4
5
6
7
8
191
160
6
6
84
95
89
71
8
16
70 102 117
376
89
13 67
5
45
60
52
142
71
8
80
145
54
223
142
53 95
84 55
54 95
341
339
54 95
60
89
28
19
19
7
55
5
55
770
5
89
7
6
223
95
900
53
140
55
620
30
140
1170
140
620
900
30
30
41
30
41
320
350
(345~355)
30
Hole for anchor
bolt 4-M12
30
Hole for anchor
bolt 4-M12
320
OUTDOOR UNIT // RZQS50/60AV1, RZQ71LV1
13
67
1 Gas pipe connection
2 Liquid pipe connection
3 Service port
4 Earth terminal
5 Refrigerant piping intake
6 Power supply wiring intake
7 Wiring between unit intake
8 Drain outlet
9 Drain port
32
DIMENSIONS (Unit: mm)
Installation service space for outdoor unit (Unit: mm)
For RZQS50-140AV1, RZQS100-140AY1, RZQ71-140LV1,
•
Transmitting part
Receiver detail
157
62
r
10
Decoration panel
17.5
re
mo
When there are obstructions
on both sides
WALL MOUNTED TYPE
• Receiver installation procedure
100
Receiver
The Front
1. For single unit installation
0o
Drain piping
side
CEILING SUSPENDED TYPE
• Receiver installation procedure
1) When the overhead space is open
When there is an
obstruction only
on the inlet side
Liquid crystal
remote controller
(wireless)
Remote
controller
holder
1) When the overhead space is open
1. For single unit installation
Receiver
Refrigerant
piping side
2 When there is an obstruction on the outlet side
or m
ore
Receiver
100
r
0o
or m
10
ore
When there are
obstructions on
both sides
• Receiver detail
• Receiver detail
10
00
or
2) When there is an obstruction
in the overhead space
Lower case
A Exposed cord
Top left
outlet
42
Operation
lamp
(Green)
B Embedded cord
Staple
19
Condit
C Embedded cord
(use switch box)
19
mo
re
rm
0
30
ore
84
When there is an
obstruction on the
inlet side
19
5X7 oblong hole
28
23
48.5
46
ss
r le
0o
50
An obstruction
in the overhead
space
48.5
Left outlet
19
Lower case portion
Note)2
28
Through hole
Switch box for one switch
( 8- 10)
ex.) KJB111A
(optional accessory)
Lower case
Note)
1. Remote controller cord and staple are not attached. They are field
supplied parts.
Specifications of cord
Type
Vinyl cord with sheath or cable (insulated thickness: 1mm or more)
Size
0.75~1.25 mm2
Total length
500 m
46
0~5
Switch box for two switch (Between remote
ex.) KJB211A
controller and
(optional accessory)
control box)
Switch box
portion
[field supplied part]
2.If the hole size is too large or the location
is not proper, the hole may come out from
the remote controller.
When there are obstructions
on the inlet side and
both lateral sides
An obstruction
in the overhead
space
s
s
r le
0o
50
100 or more
e
or
3 When there are obstructions on both
the inlet and outlet sides
(When the obstruction on the outlet side is higher than the
unit itself)
1) When the overhead space is open
150
or m
ore
150
0o
or m
ore
15
re
o
rm
(There is no limit to the height of the obstruction on the
outlet side.)
1. For single unit installation
ss
r le
0o
50
L
100 or more
mo
H
2. For series installation
(more than two units)
re
0
50 ore
m
or
20
0o
rm
ore
0
30 ore
m
or
L
H
0
10 ore
m
or
100 or more
100 or more
L
or
L
An obstruction
in the overhead
space
1000 or more
When there are obstructions
on the inlet side and
both lateral sides 100 or more
00
ore
rm
0o
2. For series installation (more than two units)
10
ss
r le
0o
50
100 or more
0
10
rm
0o
10
Code outlet hole
5X15 oblong hole
ore
rm
0o
50
2. For series installation
(more than two units)
1000 or more
120
ore
m
or
An obstruction
in the overhead space
40
84
40
84
120
Top center
outlet
ss
r le
0o
50
1. For single unit installation
1000 or more
Upper case
re
mo
An obstruction
in the overhead space
1. For single unit installation
• Installation method
or
0
00
1
2) When there is an obstruction
in the overhead space
BRC1E62
100 or more
100 or more
0o
Remote controller dimensions
100 or more
re
100 or more
20
Wired type
2. For series installation
(more than two units)
mo
2. For series installation
(more than two units)
ore
rm
0o
50
1000 or more
Remote controller holder
installation procedure
< installation to wall
surface >
Remote controller dimensions
1 When there is an obstruction on the inlet side
1000 or more
CEILING MOUNTED CASSETTE TYPE < Round Flow >
Receiver installation procedure
H
Wireless type
H
REMOTE CONTROLLER
00
10 ore
m
or
0
30 ore
m
or
Note : As for other patterns of installation, please refer to Installation manual or Engineering Data Book.
33
34
PCSAU1439A
Warning
Ask a qualified installer or contractor to install this product. Do not try to install the product by yourself.
Improper installation can result in water or refrigerant leakage, electrical shock, fire or explosion.
Use only those parts and accessories supplied or specified by Daikin. Ask a qualified installer or
contractor to install those parts and accessories. Use of unauthorised parts and accessories or
improper installation of parts and accessories can result in water or refrigerant leakage, electrical
shock, fire or explosion.
Read the user's manual carefully before using this product. The user's manual provides important
safety instructions and warnings. Be sure to follow these instructions and warnings.
If you have any enquiries, please contact your local importer, distributor and/or retailer.
Cautions on product corrosion
1. Air conditioners should not be installed in areas where corrosive gases, such as acid gas or alkaline gas, are produced.
2. If the outdoor unit is to be installed close to the sea shore, direct exposure to the sea breeze should be avoided. If you need to install
the outdoor unit close to the sea shore, contact your local distributor.