Medium Voltage Distribution
U-Series Three-Phase Recloser/
W-Series Single-Phase Recloser
with ADVC Controller
U-Series & W-Series
solid dielectric automatic
circuit recloser
Applications
SMART GRID READY
With the increasing push for advanced monitoring, reduction
of outages and the need to facilitate two-way communications
between supply and the distribution network, the U-Series
solid dielectric recloser is ready to be integrated into your
Smart Grid solution.
LOOP AUTOMATION
Restoring supply to your customers in the shortest possible
time is the focus of Recloser Solutions’ Loop Automation
Scheme.
The Loop Automation Scheme reconfigures protection
settings, sectionalises faults, minimises affected areas, and
restores network supply without the need for communications
or operator intervention, using standard recloser features.
A network affected by an outage is automatically reconfigured
to provide power to the unaffected area when an additional
supply is available. Using a combination of Feeder, Mid-Point
and Tie Reclosers to protect, sectionalise faults and minimise
affected areas, Loop Automation is a Distribution System
Automation Scheme designed to restore supply to customers
in the shortest possible time.
AUTOMATIC CHANGEOVER (ACO)
The Automatic Changeover (ACO) system uses primary &
alternative supplies, master & slave reclosers and fast
communications to ensure that supply is always available for
a critical load in the event of a power failure.
Using a number of different set-ups, including Break-BeforeMake and Make-Before-Break, allows the system to be
configured to the exact specifications required for the critical
load. The system can even be set up for one-way or two-way
switching to ensure power is always available to your critical
systems.
OPERATION AS A SECTIONALISER
Reclosers and sectionalisers work together to further improve
feeder reliability. Using a separate RL-Series LBS/
Sectionaliser, as part of a feeder automation network, detects
fault passage and automatically isolates faulty sections of a
network in conjunction with upstream recloser operation. To
accomplish this it senses the three-phase current and voltage
to count the number of recloser trip operations. When the
pre-programmed number of recloser operations is reached,
the controller opens the sectionaliser during the recloser
dead time to isolate the downstream fault.
2
Introduction & Benefits
The U-Series & W-Series solid dielectric
Automatic Circuit Recloser (ACR)
represents Schneider Electric’s commitment
to improved products and ongoing product
development. Providing the features of a
traditional recloser, plus the benefits of
up-to-date design optimised for automation,
remote control and monitoring, now or in the
future.
REDUCED PURCHASE COST
¢ Fully Intergrated: No requirement for additional RTU, power supplies, batteries
or enclosures. The Remote Terminal Unit (RTU) and a range of communication
ports are included in the standard equipment.
REDUCED INSTALLATION COSTS
¢ Simple Commissioning: Configuration of the unit is from the WSOS Software or
the Operator Interface (O.I.).
¢ All key components required for installation are included
The U-Series & W-Series development was
driven by customer demand for improved
return on capital investment in the
distribution network. After careful evaluation
of customers’ needs, the U-Series was
developed to achieve optimum performance
and reliability, making use of the latest
available technology in solid dielectrics,
vacuum interruption and microelectronics.
The result is a world-class product of which
we are justly proud.
In the past, distribution equipment such as
reclosers have been purchased only to
support load growth. Today, your
customers, the electricity consumers, are
demanding reduced outages and lower
tariffs. At Schneider Electric we are
continually working to provide the advanced
equipment needed for tomorrow’s
competitive electricity distribution system.
By using our technologically advanced
equipment, operating costs will be reduced
and capital works can be deferred through
better management of existing plant. In
addition, outages causing lost revenue will
be reduced.
In addition to automatic circuit reclosers, the
Schneider Electric family of switchgear
includes remotely controlled and monitored
pole-mounted load break switches and
sectionalisers, as well as remote control and
monitoring software.
¢ Pole mounting brackets are provided in the standard package. An optional
Voltage Transformer (VT) for auxiliary supply is available.
¢ Schneider Electric ACRs are ideally suited as low-cost feeder circuit breakers in
outdoor primary substations. In this application, connection into the substation
control system is simple and low cost.
REDUCED OPERATING COSTS
¢ Reduce Equipment Damage: The integral protection relay provides fast isolation
of faults.
¢ The recloser constantly monitors line current and voltage without the need for
additional measurement devices. This data can then be used for forward
planning and optimisation of existing feeders.
¢ Long lifetime, low maintenance equipment reduces lifetime cost.
DSA/SCADA COMPATIBILITY
When used with a compatible Distribution System Automation (DSA) or SCADA
system, Schneider Electric ACRs support remote control and monitoring to provide
the following advantages:
¢ Reduced Travel Time for Line Crews: Information on fault current and recloser
status values transmitted to system control allows fast location of the faulted line
section.
¢ This same information allows informed remote switching, reducing the affected
area and quickly restoring supply.
¢ ACRs can be configured and settings managed from system control, without
technicians having to visit each individual recloser in the field, with a consequent
reduction in travelling time and improved system integrity.
INCREASED CUSTOMER SATISFACTION
¢ Reduced Customer Minutes Lost: Supply can be quickly restored to fault-free
areas.
DEFERRED CAPITAL WORKS
¢ Remotely controlled and monitored reclosers give an improved knowledge of a
system and provide better system control. Feeder and substation load can then
be remotely managed, improving utilisation of existing plant. Purchase of new
plant can then most likely be deferred for a considerable period of time.
The Schneider Electric Switchgear and
Controller product family is a complete
solution for Distribution System Automation.
1
U-Series & W-Series
solid dielectric automatic
circuit recloser
U-Series ACR Overview
The U-Series ACR uses vacuum
interrupters, contained in epoxy bushings,
eliminating the need for insulants like oil and
gas.
The mechanism is enclosed in a 316
stainless steel tank with a stainless steel lid.
The U-Series circuit breaker is controlled and monitored by either the COMPACT or
ULTRA ADVC Controller (ADVC).
Enclosed in a 304 (COMPACT) or 316 (ULTRA) grade stainless steel enclosure the
ADVC provides an electronic controller with Operator Interface (O.I.) that monitors
the circuit breaker and provides protection, measurement, control and
communication functions. Connected via a control cable, the Switchgear and ADVC
can form a remotely controlled and monitored ACR.
1
The switchgear is operated by a magnetic actuator which produces an opening and
closing action. Switching occurs when a controlled pulse is sent through the open/
close actuator from storage capacitors in the ADVC. When closed, the switch is
latched magnetically. Spring loaded pushrods provide contact loading on the
interrupters.
2
A Current Transformer (CT) and a Capacitive Voltage Transformer (CVT) are
moulded into the CT-housing. These are monitored by the ADVC for protection,
remote monitoring and display.
9
10
3
An auxiliary voltage supply of 115/230 volts AC is required to power the control unit.
Where this is inconvenient, an additional voltage transformer can be provided.
The recloser is supplied with copper stems or optional cable clamp connectors.
Mounting brackets for lightning arresters are optionally available.
The switchgear contact position is shown by a large, clearly visible external pointer. A
hookstick can be used to engage the manual trip ring to trip and lockout the recloser
from the ground. The mechanical trip ring has two positions: UP position allows for
normal operation, and in the DOWN position the recloser is tripped and both
mechanically and electronically locked open.
4
5
11
12
6
13
7
14
8
The ADVC interfaces to the switchgear via the control cable and connects to the
Switch Cable Entry Module (SCEM) in the base of the tank via a covered plug/socket
sealing arrangement on both the ADVC and the Switchgear. The SCEM uses
non-volatile memory to store all relevant calibration data, ratings and number of
operations. The SCEM also provides the first stage of electrical isolation and
shorting electronics to short the CTs and CVTs in the event the control cable is
disconnected while current is flowing through the switchgear.
15
Cross section of circuit breaker
Legend
1: X-side terminal 2
8: Manual trip ring
2: Current transformer
9: Vacuum interrupter
3: I-side terminal
10: Epoxy bushing
4: Capacitive voltage
transformer
11: Earthing point
5: Stainless steel lid
13: Magnetic actuator
6: Lightning arrester
brackets
14: SCEM card
7: On/Off indicator
12: Stainless steel tank
15: Control cable
U-Series circuit breaker
2
Solid dielectric bushing
U-Series Recloser Specifications
U-SERIES
15kV
12.5kA
27kV
12.5kA
15.5kV
27kV
RATINGS
Rated Maximum Voltage
Rated Continuous Current
Fault Make Capacity (RMS)
Fault Make Capacity (Peak)
630A
630A
12.5kA
12.5kA
31.5kA
31.5kA
0.1/0.05s
0.1/0.05s
Mechanical Operations
10,000
10,000
Rated full load operations
10,000
10,000
Short time current
12.5kA
12.5kA
Power Operating Time (Close/Open)
BREAKING CAPACITY
Mainly Active (0.7pf)
630A
630A
Fault break capacity
12.5kA
12.5kA
Cable charging
25A
25A
Transformer magnetising
22A
22A
Phase to Earth
110kV
125kV
Across Interrupter
110kV
125kV
LIGHTNING IMPULSE WITHSTAND LEVEL
POWER FREQUENCY WITHSTAND VOLTAGE
Phase to Earth
50kV
60kV
Across Interrupter
50kV
60kV
SERVICE CONDITIONS
Ambient Temperaturea (ºC)
-40 to 50
-40 to 50
Ambient Temperaturea (ºF)
-40 to 122
-40 to 122
Radiation (Max)
1.1kW/m2
1.1kW/m2
Humidity
0 to 100%
0 to 100%
3000
3000
9840
9840
Circuit breaker with pole mount bracket (kg/lbs)
146 / 322
146 / 322
Control cubicle with control cable (kg / lbs)
41 / 90
41 / 90
Gross weight of crate (kg / lbs)
263 / 580
263 / 580
External VT (kg / lbs) (N series Only)
60 / 132
60 / 132
Altitude meters (Max)b
Altitude feet (Max)
b
NET WEIGHTS
CRATE DIMENSIONS
Width (mm / in)
960 / 37.8
960 / 37.8
Depth (mm / in)
1020 / 40.2
1020 / 40.2
Height (mm / in)
1160 / 45.7
1160 / 45.7
a.
b.
Option when cubicle battery heater is fitted (-10ºC to 50ºC {-14ºF to 122ºF} without heater)
For altitudes above 1000m (3280 feet), derate in accordance with ANSI C37.60 for reclosers (ANSI C37.63 for LBS)
3
U-Series & W-Series
solid dielectric automatic
circuit recloser
W-Series ACR Overview
The W-Series ACR uses a vacuum
interrupter, contained in an epoxy bushing,
eliminating the need for insulants like oil and
gas.
The mechanism is enclosed in a 316
stainless steel tank with a stainless steel lid.
1
8
2
9
The W-Series circuit breaker is controlled and monitored by either the COMPACT or
ULTRA ADVC Controller (ADVC).
Enclosed in a 304 (COMPACT) or 316 (ULTRA) grade stainless steel enclosure the
ADVC provides an electronic controller with Operator Interface (O.I.) that monitors
the circuit breaker and provides protection, measurement, control and
communication functions. Connected via a control cable, the Switchgear and ADVC
can form a remotely controlled and monitored ACR.
The switchgear is operated by a magnetic actuator which produces an opening and
closing action. Switching occurs when a controlled pulse is sent through the open/
close actuator from storage capacitors in the ADVC. When closed, the switch is
latched magnetically. A spring-loaded pushrod provides contact loading on the
interrupter.
A Current Transformer (CT) and a Capacitive Voltage Transformer (CVT) are
moulded into the CT-housing. These are monitored by the ADVC for protection,
remote monitoring and display.
An auxiliary voltage supply of 115/230 volts AC is required to power the control unit.
Where this is inconvenient, an additional voltage transformer can be provided.
The recloser is supplied with copper stems or optional cable clamp connectors.
Mounting brackets for lightning arresters are optionally available.
3
4
10
5
11
6
12
7
13
Cross section of W-Series
Legend
1: X-side terminal
7: On/Off indicator
2: Current transformer
8: Vacuum interrupter
3: I-side terminal
9: Epoxy bushing
4: Capacitive voltage
transformer
10: Earthing point
5: Stainless steel lid
12: Magnetic actuator
6: Manual trip ring
13: SCEM card
4
11: Stainless steel tank
The switchgear contact position is shown by a large, clearly visible external pointer. A
hookstick can be used to engage the manual trip ring to trip and lockout the recloser
from the ground. The mechanical trip ring has two positions: UP position allows for
normal operation, and in the DOWN position the recloser is tripped and both
mechanically and electronically locked open.
The ADVC interfaces to the switchgear via the control cable and connects to the
Switch Cable Entry Module (SCEM) in the tank via a covered plug/socket sealing
arrangement on both the ADVC and the Switchgear. The SCEM uses non-volatile
memory to store all relevant calibration data, ratings and number of operations. The
SCEM also provides the first stage of electrical isolation and shorting electronics to
short the CT and CVT in the event the control cable is disconnected while current is
flowing through the switchgear.
W-Series Recloser Specifications
W-SERIES
RATINGS
Rated Maximum Voltage
Rated Nominal Voltage (phase to ground)
Rated Continuous Current
Fault Make Capacity (RMS)
Fault Make Capacity (Peak)
Power Operating Time (Close/Open)
Mechanical Operations
Rated full load operations
Short time current
BREAKING CAPACITY
Mainly Active (0.7pf)
Fault break capacity
Cable charging
Line Charging
Transformer magnetising
LIGHTNING IMPULSE WITHSTAND LEVEL
Phase to Earth
Across Interrupter
POWER FREQUENCY WITHSTAND VOLTAGE
Phase to Earth
Across Interrupter
SERVICE CONDITIONS
Ambient Temperaturea (ºC)
Ambient Temperaturea (ºF)
Radiation (Max)
Humidity
Altitude meters (Max)b
Altitude feet (Max)b
NET WEIGHTS
Circuit breaker with pole mount bracket (kg/lbs)
Control cubicle with control cable (kg / lbs)
Gross weight of crate (kg / lbs)
External VT (kg / lbs) (N series Only)
CRATE DIMENSIONS
Width (mm / in)
Depth (mm / in)
Height (mm / in)
24kV
21kV
400A
6kA
15kA
0.1/0.05s
10,000
10,000
6kA
400A
6kA
25A
5A
22A
125kV
125kV
60kV
60kV
-30 to 50
-22 to 122
1.1kW/m2
0 to 100%
3000
9840
75 / 165
41 / 90
196 / 432
60 / 132
1150 / 45.3
1150 / 45.3
570 / 22.4
c. Option when cubicle battery heater is fitted (-10ºC to 50ºC {-14ºF to 122ºF} without heater)
d. For altitudes above 1000m (3280 feet), derate in accordance with ANSI C37.60 for reclosers (ANSI C37.63 for LBS)
5
U-Series & W-Series
solid dielectric automatic
circuit recloser
ADVC Controller Series
Advanced protection, data logging &
communications capabilities are made
possible by the technology housed in the
ADVC Controller.
With a cubicle designed to minimise temperature rise from solar heating, the 304
(COMPACT) or 316 (ULTRA) grade stainless steel enclosure is used to mount the
Control And Protection Enclosure (CAPE), Power Supply Unit (PSU), customer
accessories and Operator Interface.
It has been designed especially for outdoor
pole mounted operation and is typically
mounted low on the pole for ease of access
by operation personnel.
Batteries are carefully located underneath these modules to help avoid overheating
so that a battery life of up to 5 years1 can be achieved. A vandal resistant lockable
stainless steel door, sealed with a rubber gasket, provides access to the Operator
Interface. Vents are screened against vermin entry and all electronic parts are
enclosed in a sealed die-cast enclosure which protects them from entry of moisture
and condensation ensuring a long lifetime.
The ADVC Controller Series incorporates the functions of a multi-function protection
relay, a circuit breaker controller, a metering unit and a remote terminal unit.
The COMPACT Cubicle is suitable for temperatures from -10°C to 50°C , while the
option of a battery heater in the ULTRA Cubicle extends its operating temperature
range from -40°C to 50°C.
A built-in microprocessor controlled power supply provides uninterrupted operation
of not only the circuit breaker and controller, but also the communications radio or
modem. These accessories are connected to a built-in user progammable radio
power supply. Therefore no other power supplies are required for connection into
your SCADA or Distribution Automation System.
Due to careful design the efficiency of all parts is extremely high, allowing a battery
hold up time of up to 44 hours2. The architecture used has the advantage that the
circuit breaker operation is independent of the high voltage supply, relying on a set of
capacitors charged by the auxiliary supply.
Due to sophisticated power supply management techniques, a circuit breaker
operation is always guaranteed when attempted and alarms are raised over the
telemetry when auxiliary power is lost.
Communications equipment can be mounted within the ADVC Controller cubicle. A
V23 FSK modem, RS232, RS485 and Ethernet TCP/IP are provided as standard to
support all of your communications needs.
The ADVC Controller Series is available in two models:
ADVC ULTRA (with flexVUE)
¢ ULTRA
¢ COMPACT
The table below outlines some of the differences between the two models
ULTRA
COMPACT
Enclosure
316 stainless steel
304 stainless steel
Door Locking
Three-point
Two-point
Customer accessory tray
Side Tray
Upper Tray
Side Tray only
Input/Output modules
8 inputs, 8 outputs
Optional
N/A
Battery heater
Optional
N/A
Battery
7 Ah, or
12 Ah
7 Ah
Temperature Range
-40°C to 50°C
-10°C to 50°C
(with battery heater option)
ADVC COMPACT (with setVUE)
6
Auxiliary power supply
115/230Vac
115/230Vac
Dual AC power supply
Optional
N/A
VT supply via switchgear
Optional
Optional
DC power supply
Optional
N/A
1
Battery replacement interval is influenced by environmental temperature.
2
with optional 12 Ah Battery, panel off and without communications devices operating.
ADVC Block Diagram
Schneider Electric automatic circuit
reclosers provide many outstanding
advantages to the user.
New and innovative features have been
made possible by the intimate way the
pole-mounted circuit breaker and control
cubicle work together. The block diagram on
this page shows how the two items are
interfaced.
Special extended range current
transformers provide a range from 1A to
12,500A for measurement and protection.
Embedded voltage screens accurately
image the primary voltage value and phase
relationship at the analogue front end,
allowing measurement of voltage, current,
power factor and frequency in the electronic
module.
ADVC Controller block diagram
7
U-Series & W-Series
solid dielectric automatic
circuit recloser
ADVC Features
Each recloser is provided with an Operator Interface. From here a user can access
and program the many measurement and protection features available. Two different
Operator Interfaces are available, these are:
¢ setVUE Operator Interface
£
Based on the field-proven operator panels in the previous controllers, this
menu-driven interface with large LCD display offers a familiar look and feel.
setVUE Operator Interface
¢
£
£
£
£
flexVUE Operator Interface
20 Status Lamps provide a quick snapshot of the protection and controller status.
12 Quick Action Keys are available to execute frequently used actions such as
"Remote control" ON/OFF, "Reclose" ON/OFF, etc. Each key has its own
status lamp to indicate the ON/OFF state.
All Status Lamps and Quick Action Keys are customisable.
It is possible to access Event and Measurement data and change settings.
flexVUE Operator Interface
TELEMETRY INTERFACE
The Schneider Electric ACR can be interfaced to your SCADA system either through
its built-in V23 modem and a radio, or its RS232 ports and a modem of your choice.
RS485 and Ethernet TCP/IP are also available. A variable voltage uninterruptable
power supply is included for the radio or modem, which can be mounted inside the
communications cubicle. Many telemetry protocols can be supported such as DNP3
and IEC 60870-5-101.
COMPUTER INTERFACE
WSOS is an advanced personal computer based software package to allow off-line and
on-line programming, monitoring and control of a recloser via a USB port, RS232 port or
Ethernet.
REMOTE CONTROL
The ADVC offers an impressive list of communication ports for use in remote control
applications:
¢ 4 x RS232;
¢ 1 x Ethernet;
¢ 1 x RS485
¢ 1 x V23
8
flexVUE Operator Interface
Customising the operator interface to suit
your unique applications has never been
easier.
The flexVUE Operator Interface uses Light Emitting Diodes (Lamps) and an LCD
display to communicate the system status to a local operator. Operator actions that
are performed on a regular basis can be mapped to 12 dedicated buttons on the
interface.
Each of these buttons also have a lamp to indicate the ON/OFF state of each action.
Together with the 20 status lamps the panel provides no less than 32 three-colour
LEDs that display the state of the controller and overhead system. On the interface,
the action buttons are grouped together and referred to as Quick Action Keys. The
status LEDs are also grouped together and referred to as Status Lamps.
Every controller is programmed with a standard configuration of Status Lamps and
Quick Action Keys: text labels are used to mark the function of each. These labels
are inserted into special pockets within the flexVUE Operator Interface and can be
changed in the field if required.
A graphical panel configuration tool is provided as part of the WSOS 5 software
package that will allow full customisaiton of the flexVUE Operator Interface, if
required. With the the tool you can create your own logic functions driving the Status
Lamps, as well as change the actions linked to each Quick Action Key. New labels
can be printed from the WSOS template using standard office stationery, cut to size
and inserted into the controller.
Example of building the logic function for a Status Lamp
Inserting custom labels into the interface
Example of setting the action keys
9
U-Series & W-Series
solid dielectric automatic
circuit recloser
WSOS is the Schneider Electric Switchgear
Operating System software. It provides
easy access to all switchgear functions from
opening/closing, through configuring
protection and communication parameters
to accessing measurement and analytical
data.
WSOS Version 5 integrates Schneider Electric’s field proven Windows-based
switchgear operating system and its powerful features and tools, developed over
many years, into a modern desktop. The desktop includes the Switchgear Explorer
to organise your switchgear the way you like it and the Launch Pad for handy links to
online help, getting started, updates and much, much more. Controlling, configuring
and accessing valuable switchgear data from a local or remote location is now even
easier than before.
By using a PC, engineers can manage a
large number of reclosers either remotely
via a communications link or locally via a
USB, serial port or Ethernet connection.
¢ Switchgear operation.
LOCAL AND REMOTE CONTROL
¢ Protection group selection.
¢ Protection group copy.
¢ NPS on/off/alarm control.
¢ Auto reclose, earth protection and SEF on/off control.
¢ Work tag, low gas and dead lockout on/off control.
¢ Configurable Input/Output Expander (IOEX).
¢ Configurable quick keys.
¢ Configurable delay for local Open and Close operations (Hit and Run).
¢ Configurable SCADA protocols:
- DNP3.0 is included as standard.
COMMUNICATION OPTIONS
¢ Local USB port (for connection to WSOS only)
¢ Local RS232 port connection.
¢ Radio modem.
¢ GSM / PSTN modem.
¢ DNP3 virtual terminal object.
¢ TCP/IP.
¢ Communications output capture.
Switchgear Explorer window
Example of the WSOS5 desktop
10
WSOS5 cont
MEASUREMENT SCREENS
¢ Three-phase, earth and sequence current.
¢ Phase voltages:
- Phase to phase,
- Phase to earth, and
- Sequence voltages.
¢ Phase live/dead indication.
¢ Apparent, reactive & real power:
- Total, and
- Per phase.
¢ Power factor.
¢ Signed or unsigned power.
¢
Frequency.
¢ Power quality toolkit:
- Waveform capture.
- Harmonics.
INTERFACE CONFIGURATION
¢ Status lamps:
£
£
Logic function to indicate; and
Separate true/false state colour configuration.
¢ Quick Action Keys:
£
£
£
Customise actions assigned to each key;
Custom logic functions for lamp indication; and
Separate true/false colour configuration.
¢ Print labels to insert into operator interface.
Panel Configuration Tool
11
U-Series & W-Series
solid dielectric automatic
circuit recloser
General Protection Features
OPERATING SEQUENCE
Reclose times are individually selectable. The operating sequence is defined by:
O - 1st rt - CO - 2nd rt - CO - 3rd rt - CO
where rt = reclose time.
where O = open.
where C = close.
RECLOSE TIMES
¢ 1st Reclose Time range:
0.3 - 180 sec
¢ 2nd Reclose Time range:
2.0 - 180 sec
¢ 3rd Reclose Time range:
2.0 - 180 sec
¢ Timing resolution:
0.1 sec
SEQUENCE RESET TIME
¢ Sequence Reset Time: 3 - 180 sec
¢ Timing resolution: 1 sec
TRIPS TO LOCKOUT
Overcurrent and fault trips to lockout are selectable between 1 and 4. A separate
setting is available for Sensitive Earth Fault and Negative Phase Sequence.
100
INVERSE TIME CURVES
The ADVC offers a total of 48 user selectable inverse time protection curves. These
are:
¢ Three IEC60255 curves:
10
Time (s)
Standard inverse
Very inverse
Extremely inverse
Inverse,
Very Inverse and
Extremely Inverse.
¢ Three IEEE C37.112 Inverse Time curves: Moderately Inverse,
Very Inverse and
Extremely Inverse.
1
¢ 42 Non Standard Inverse Time Curves:
100
% Setting current
100
Inverse time curves
10
Time (s)
IDMT curve
Threshold
Maximum time
Minimum time
Instantaneous
Modified curve
Refer to the Operating
Manual for a full listing.
INSTANTANEOUS PROTECTION
Instantaneous protection works by tripping the recloser if the line current exceeds
the Instantaneous Multiplier x Setting Current.
¢ Multiplier range:
1 - 30
¢ Resolution of setting:
0.1
¢ Max effective setting:
12.5kA
DEFINITE TIME PROTECTION
1
Definite Time is an alternative to Inverse Time protection. It works by tripping the
recloser at a fixed time after pick-up.
100
% Setting current
Modified curve
¢ Setting current range:
10 - 1260A
¢ Definite time resolution:
0.1 sec
¢ Definite time range:
0.01 - 100 sec
¢ Setting current resolution:
1A
SENSITIVE EARTH FAULT (SEF)
SEF causes the recloser to trip when the earth current rises above a set level for
longer than the set time.
12
¢ SEF trip current range:
4 - 20A
¢ SEF operating time range:
0.1 - 999 sec
¢ SEF trip current setting resolution:
1A
¢ SEF operating time resolution:
0.1 sec
General Protection Features cont
INRUSH RESTRAINT
Inrush restraint raises the phase and earth threshold currents for a short period of
time to allow for short duration inrush currents when closing onto a load.
¢ Multiplier range:
1 - 30
¢ Multiplier resolution:
0.1
¢ Time range:
0.05 - 30 sec
¢ Time resolution:
0.05 sec
COLD LOAD PICK-UP
Cold load pick-up allows for a loss of diversity when a load has been without supply
for a period of time.
¢ Multiplier range:
1-5
¢ Multiplier resolution:
0.1
¢ Time Constant range:
1 - 480 min.
¢ Time constant resolution:
1 min.
MULTIPLE PROTECTION GROUPS
The ADVC supports up to 10 Protection Groups, each of which can be configured
with completely separate protection characteristics with different inverse time curves
and setting currents. The number of protection groups available to the operator can
be configured using WSOS, thereby restricting or enabling access to protection
settings as required.
AUTOMATIC PROTECTION GROUP SELECTION
WSOS offers a quick, easy way to configure the protection groups.
Automatic Protection Group Selection is used to change the protection group
depending on the direction of power flow. This allows the recloser to be correctly
graded with devices downstream regardless of the power flow direction.
LOSS OF PHASE
Loss of phase protection trips the recloser if phase-earth voltage on one or two
phases falls below a set voltage threshold for a set length of time.
¢ Threshold voltage range:
2 - 15kV
¢ Voltage resolution:
1V
¢ Time range:
0.1 - 100 sec
¢ Time resolution:
0.1 sec
LIVE LOAD BLOCKING
Live load blocking prevents a recloser from closing if any of the load side terminals
are live.
¢ Live Load Threshold Voltage range:
2 - 15kV
DEAD LOCKOUT
Dead lockout prevents a reclose unless one or more of the source side or load side
terminals are live. If all terminals are dead then the controller goes to lockout.
13
U-Series & W-Series
solid dielectric automatic
circuit recloser
Advanced Protection Features
DIRECTIONAL BLOCKING
Directional blocking is a protection feature that restricts tripping on faults to a
designated side of the recloser. It prevents nuisance tripping if particular network
conditions are causing “false” earth faults. In radial systems, Directional Blocking
prevents nuisance tripping by blocking faults in the source direction and only
responding to faults in the load direction.
DIRECTIONAL PROTECTION
Distinct protection for faults in the forward and reverse direction. A forward fault may
use a different time-current curve and settings to a reverse fault (i.e. these are
individually selectable). Both the forward protection and reverse protection are
operating at the same time. This is an additional protection feature.
SEQUENCE COMPONENTS
Negative, positive and zero phase sequence currents and voltages can be
monitored and logged.
In addition, the negative phase sequence current protection can be used for
detection of low-level phase-to-phase faults in the presence of high level threephase loads. Inverse Time, Definite Time and Instantaneous operation is available.
¢ Setting current range: 10 - 1260 A
SEQUENCE COORDINATION
Sequence coordination allows a recloser to coordinate its trip sequence with
another recloser downstream.
UNDER / OVER FREQUENCY PROTECTION
This feature trips the recloser when the system frequency exceeds the under and
over frequency trip threshold values. Frequency tripping range: 45 - 65 Hz
¢ Frequency calculation:
Once / cycle over a 2 cycle period
2 - 1000
¢ Accuracy:
±0.05Hz
Frequency
¢ Number of under/over frequency
cycles before tripping:
Trip Delay
Count
Normal Frequency
Close Time
Over Frequency
Trip setting
Over Frequency
Normal restore
Trip at
this time
Close at
this time
Time
Nominal
Frequency
Axis
Under / over frequency protection
14
Advanced Protection Features cont
UNDER / OVER VOLTAGE PROTECTION
When selected, and a nominal Phase to Earth System operating voltage is set, the
UOV Protection works within a defined threshold above and below the specified
voltage.
¢ Under Voltage Lower Threshold Range:
50% - 88%
¢ Over Voltage Upper Threshold Range: 112% - 150%
¢ Trip After X secs Range:
0 - 60 Seconds
¢ Phase Logic
£ AND:
When ALL phases deviate beyond thresholds
£ OR:
When ANY phase voltage deviates beyond the thresholds
£ AVERAGE: When the numerical AVERAGE of all phase Voltages deviates
beyond the threshold.
15
U-Series & W-Series
solid dielectric automatic
circuit recloser
Measurement Features
VOLTAGE & CURRRENT
True RMS voltage is measured on the three I-Side terminals. A user configured
threshold indicates live terminal. RMS current is measured on three phases (reading
2 - 630A).
Optional external Capacitive Voltage Transformers (CVTs) can be fitted to measure
the voltage on the other three (X-Side) terminals. External CVTs can be purchased at
the time of your order or can be added to an existing installation when required. The
external CVTs are mounted onto a cross-arm adjacent to the recloser and the
secondaries are connected to the SCEM card located in the base of the recloser.
REAL POWER (SIGNED OR UNSIGNED)
Real power is determined by multiplying the line voltage and line current in real time
and averaging over 2 seconds (accuracy ±5% of reading, within limits of V and I
above).
POWER & POWER FACTOR
The ADVC Controller measures kW, kVA, kVAr and powerfactor on a per-phase
basis.
The power factor of the line is determined from the line voltage and the line current
phase relationship and the previously calculated real power (accuracy ±5% of
reading, within limits of V and I above).
DEFAULT HISTORICAL MEASUREMENTS
Power flow is integrated over 5, 15, 30, or 60 minute intervals (kWh) and recorded for
two months at the default setting. This can be viewed on the operator control panel,
computer, or compatible SCADA system. Additionally, data can be uploaded into a
portable computer or a compatible SCADA system.
CONFIGURABLE HISTORICAL MEASUREMENTS
Average demand profiles may be configured using WSOS. Customised
configuration enables the user to specify only the parameters that are required,
negating unnecessary information capture. Parameters such as line voltages and
currents, power, kWh, battery voltage and cubicle temperature can be recorded in
intervals selectable between 1 and 1,440 min.
EVENT HISTORY
¢ Maximum number of typical events stored in the event history: 30,000 events
POWER QUALITY TOOLKIT
¢ Supply outage measurement:
£
£
Harmonic analysis
£
The Supply Outage Measurement feature utilises built-in recloser features to
record the number and duration of outages. These statistics are recorded in
the controller and are available to the Utility to help calculate system outage
customer minutes.
The controller records:
- cumulative total number of outages,
- cumulative total outage duration, and
- the time and duration of each outage event in the Event Log.
These records are accessible to the user and can be retrieved using the
operator control panel, WSOS or a SCADA System.
¢ Harmonic analysis:
£
Harmonics 2 to 16 and the Total Harmonic Distortion (THD) are calculated over
a 80 ms period for four currents, six line-line voltages and six line-earth
voltages. These harmonics are available via WSOS.
¢ Waveform capture:
£
£
£
Waveform capture
16
Based on an user defined trigger, the ADVC captures and stores in non-volatile
memory scaled raw data (10 x 3200 samples per second) of the six line-earth
voltages and four currents for a predefined time window either side of a
user-defined trigger.
The user can configure a pre and post trigger time ratio for data to be stored.
This defaults to 50% pre-trigger and 50% post-trigger.
The captured data can be uploaded at anytime in COMTRADE (IEEE Std
C37.111-1999) format via WSOS.
Required details for order
ADVC Controller
Only one of the boxes (ticked
or filled
with the required value) have to be considered between each horizontal line.
lead-time should be requested from yor distributor.
Red Circle
ADVC Controller
Quantity
Model (Features Highlighted are only available on ULTRA)
Operator Interface (O.I.)
flexVUE
setVUE
Ambient Temperature (°C)
Auxilliary Supply Type
ULTRA . .
COMPACT
Standard
-10°C to 50°C
Extended With Battery Heater
-40°C to 50°C
Single AC Supply:
230 Vac
115 Vac
add 27.8 Vac Integrated Supply to above
Dual AC
DC Supply
26 Hours
44 Hours
US English
Spanish
Portugese
MODBUS
IEC
DNP3
FTIM (Ultra FTIM cable only)
Not Applicable
Yes
IOEX
Not Applicable
Yes
General Purpose IEC Socket
Not Applicable
Yes
Maximum Battery Hold Up Time
Language
English
Standard Protocol
Accessories (Additional Costs May Apply)
GPO 10A max.
Only with IEC Socket
None
AUS
Other
UK
EU-A
USA
EU-B
Sth Africa
Special notes (For other available Accessories, contact local suppliers)
17
U-Series & W-Series
solid dielectric automatic
circuit recloser
Required details for order
U-Series Recloser (U15 and U27)
Only one of the boxes (ticked
or filled
with the required value) have to be considered between each
horizontal line. Red Circle
lead-time should be requested from yor distributor.
Certain configurations may attract additional cost. To clarrify these details, please consult your local distributor.
Circuit Breaker Unit
Quantity
Rating (System Voltage / Interrupt / BIL)
15.5 kV / 12.5 kA / 110 kV
27 kV / 12.5 kA / 125 kV
Rated Current (A)
630 A
Frequency
50 Hz Standard
60 Hz Standard
Sensitive Earth Fault Rating
Language
4 - 20 A
English
Spanish
Portugese
Pole Mount:
Centre Mount
End Mount
Substation Frame:
Adjustable
Fixed
230 - 270 mm
270 - 310 mm
310 - 360 mm
4 Metres
7 Metres (Default)
11 Metres
Accessories
Mounting Arrangement
Concrete Pole Clamps
Not Applicable
Control Cable Length
20 Metres
Other
Options
Medium Voltage Terminal Options (Set of 6)
External Capacitive Voltage Transformers
Bare Terminal 630 A
15TP Connector 400 A
30TP Connector 630A
Not Applicable
CVTs
Three external CVTs can be added when voltage measurement is required on all six bushings.
Surge Arrester Brackets
Standard Inclusion
Set of 2 brackets with End Mount option. Only one Centre mount and Substation Options.
Surge Arresters
Not Applicable
Surge Arresters
VT Mounting
Not Applicable
Pole Mounted
Dressing (Australia Only)
Not Applicable
Dressed
Special notes
18
U-Series Recloser
Pole Mounting Details
1175 (46.3”)
840 (33.1”)
295 (11.6”)
380 (15”)
375 (14.8”)
869 (34.2”)
437 (17.2”)
230 (9”)
I-Side
685 (27”)
685 (27”)
X-Side
Lightning
arrester
(optional)
Bracket bolted to pole requires
2 × 20mm bolts for pole mounting
Bracket bolted to pole
requires 2 × 20mm bolts for
pole mounting (not supplied)
(not included)
Side view of Mid-point mounting arrangement
Side view of End mounting arrangement
Notes
(1) Details given in this illustration are subject to change without notice. For full
details see the Installation Manual.
(2) Earthing connections are not shown and are to be in accordance with the
Installation Manual.
(3) Recloser can be mounted closer to pole if lightning arresters are pole mounted.
(4) Optional substation mounting frame available on request.
CABLE CONNECTION OPTIONS
Connections are made to the bare recloser terminals using crimp lugs, parallel
groove clamps or stud connectors. This arrangement is suitable for connection into
an insulated or bare conductor system, as appropriate.
400-15TP stud connector
630-30TP stud connector
HJ connector
Pole mounted U-Series recloser with ADVC Controller
19
U-Series & W-Series
solid dielectric automatic
circuit recloser
Required details for order
W-Series SWER Recloser (W27)
Only one of the boxes (ticked
or filled
by the required value) have to be considered between each horizontal
line. Red Circle
lead-time should be requested from yor distributor.
Certain configurations may attract additional cost. To clarify these details, please consult your local distributor.
Circuit Breaker Unit
Quantity
Rating (System Voltage / Interrupt / BIL)
24 kV / 6 kA / 125 kV
Rated Current (A)
400 A
Frequency
Language
50 Hz Standard
60 Hz Standard
Spanish
Portugese
I/O
On / Off
Not Applicable
Pole Mount
230 - 270 mm
270 - 310 mm
310 - 360 mm
4 Metres
7 Metres (Default)
11 Metres
English
Circuit Breaker Indication
Accessories
Mounting Arrangement
Concrete Pole Clamps
Not Applicable
Control Cable Length
20 Metres
Other
Options
Medium Voltage Terminal Options (Set of 2)
15TP Connector 400 A
Bare Terminal 400A
Not Applicable
Surge Arresters
SWER 12.7 kV
SWER 19.1 kV
VT Mounting
Not Applicable
Pole Mounted
Dressing (Australia Only)
Not Applicable
Dressed
Surge Arresters
Voltage transformers (VTs)
27.8 Vac secondary
Special notes
20
Not Applicable
W-Series Recloser
Pole Mounting Details
360 mm
(14.2")
SURGE ARRESTOR
SUPPLIED AS
OPTIONAL EXTRA
105 mm
(4.1")
620 mm
(24.4")
460 mm
(18.1")
1038 mm
(40.9")
450 mm
(17.7")
260 mm
(10.2")
360 mm
(14.2")
500 mm
(19.7")
NOTE:
2 x M20 BOLTS FOR
POLE MOUNTING
NOT SUPPLIED.
Side view of W-Series mounting arrangement
SURGE ARRESTOR
SUPPLIED AS
OPTIONAL EXTRA
Overhead view of W-Series mounting arrangement
Notes
(1) Details given in this illustration are subject to change without notice. For full
details see the Installation Manual.
(2) Earthing connections are not shown and are to be in accordance with the
Installation Manual.
CABLE CONNECTION OPTIONS
Connections are made to the bare recloser terminals using crimp lugs, parallel
groove clamps or stud connectors. This arrangement is suitable for connection into
an insulated or bare conductor system, as appropriate.
400-15TP stud connector
Pole mounted W-Series recloser with ADVC Controller
21
Locked Bag 10,
Eagle Farm Business Centre,
Qld 4009
Corporate office &
factory