ZETTLER Product Catalogue
ZETTLER
Product
Catalogue
fire_content_page:Layout 1 16/12/2016 13:07 Page 1
CONTENTS
CONTENTS
Chapter 1 - Introduction
Chapter 2 - MZX Technology
• PROFILE Panels
• PROFILE Repeaters
• Minerva MZX Detection Control Panels
• Minerva MZX Addressable Control Panels
• Minerva MX2 Range
• Minerva MX4000
• Battery & Expansion Boxes
• Minerva MX Repeaters
• MZX4000 Black Box
• Minerva T2000 & T2000 CV Marine
Detection Panels
• Minerva T2000R & T2000R CV Marine
Repeaters
• MX Panel Components
• DDA Compliant Pager
• Generation 6 Fire Detectors
• Beam and Linear Heat Detectors
• Detector Bases & Accessories
• Detector Ancillaries
• Duct Probe Air Sampling
• MX Addressable Input/Output Modules
• MZX Compatible 4 Amp 24VDC
Addressable Door Holder PSU
• MX Ancillary Housings
• Callpoints
• Sounders & Beacons
• Software Tools & Accessories
• MZX Interactive Training CD
• Programming and Service Tools
• Service & Spares
Chapter 3 - Conventional Systems
• Control Panels and Repeater Panels
• Extinguishing Panels, Repeaters
& Accessories
• DDA Compliant Pager
• Point Detectors
• Beam Detectors
• Linear Heat Detectors
• Detector Bases and Accessories
• Duct Probes
• Callpoints
• Sounders & Beacons
• Service & Spares
Chapter 4 - Networks & Graphics
• Tyco Expert Graphics (TXG)
• TLI800EN Network Interface Module
& FOM800 Fibre Optic Module
• MX Minerva - Bridge
12/16
1.1
2.3
2.4
2.5
2.2
2.4
2.5
2.6
2.7
2.8
2.9
2.10
2.13
2.25
2.28
2.31
2.34
2.38
2.39
2.41
2.48
2.48
2.50
2.56
2.73
2.74
2.76
2.79
3.1
3.1
3.7
3.9
3.11
3.16
3.18
3.19
3.23
3.25
3.32
3.48
Chapter 5 - Detector Test Equipment
• Essential Test Equipment
• Additional and Alternative Products and
Accessories
• Product Selector
• Flame Detector Test Equipment
5.1
5.1
5.2
Chapter 6 - System Accessories
• Batteries, PSU and Chargers
• Door Release Equipment
• Auxiliary Interface Relays
• Fire Resistant Cable
6.1
6.1
6.3
6.4
6.5
Chapter 7 - VESDA
• LaserFOCUS Aspirating Smoke Detection
• LaserCOMPACT and MX Laser COMPACT
• LaserPLUS Standard Modular Range
• LaserPLUS Scanners
• Remote Displays and Modules
• ICAM IAS800 Air Sampling Smoke
Detection Systems
• VESDA Pipe, Fittings and Test Equipment
• VESDA-E VEU
• VESDA VLQ
• OSID Smoke Detection
7.1
7.1
7.2
7.3
7.4
7.5
7.7
5.3
5.4
7.8
7.11
7.13
7.11
Chapter 8 - Fire Phones & Disable Refuge 8.1
Chapter 9 - Special Hazards
• Special Hazard Flame Detectors
• System 800 Fire Detection for Hazardous
Areas
• System 620 Fire Detection for Hazardous
Areas
• MZX SensorLaser Plus Fibre Optic
Linear Heat Detection System
9.1
9.3
9.7
9.15
9.25
Chapter 10 - Gas Detection
Meridian Gas Detectors
10.1
10.1
Chapter 11 - Useful Information
• MKII Sounder Base Application Table
• Sounder Tone Tables
• Consultants Guide
11.1
11.1
11.3
11.5
Chapter 12 - Index
12.1
4.1
4.1
4.4
4.7
Fire Catalogue
fire_content_page:Layout 1 16/12/2016 13:07 Page 2
This page is left intentionally blank
Fire Catalogue
12/16
FIRE_Ch1_Introduction:Layout 1 04/12/2012 10:35 Page 1
Chapter 1 - Introduction
Fire Detection
Welcome to the latest issue of the Tyco Fire Protection Products Fire Detection Catalogue which details products available
from our Letchworth U.K. distribution centre. This catalogue is intended to assist all sellers and system designers involved
in fire detection from entry level conventional systems to extensive networked addressable systems and special hazard
protection.
In line with our ISO 9000 accreditation, only those products that meet the highest quality criteria have been included.
Our goal is to despatch product on the same day as we receive your order. Our warranty and service returns policy is
second to none. We recognise that your business is highly dependant on excellence in customer service and to help
achieve this we offer extended warranty from many of our suppliers. Full credit is also available on a "No Question - No
Fuss" basis for any new in-warranty product returned to the distribution centre.
New Catalogue Layout
With an emphasis on ease of use, the contents of this Issue has been arranged to meet the specific needs of individual
users. Each section covers a different aspect of fire detection and contains all product associated with that subject. If a
particular product is used for example with both conventional systems and addressable systems, it will appear in both
sections. Each section can therefore be used independently and each section can also be downloaded separately from the
Tyco Fire Protection Products website. The 12 sections covered are:
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
Introduction
Addressable Systems
Conventional Systems
Networks & Graphics
Detector Test Equipment
System Accessories
Aspirating Systems
Fire Phones and Disabled Refuge
Water Leak Detection
Special Hazards
Useful Information
Index
Website
The Tyco Fire Protection Products website is full of up-to-date information
including a section dedicated to fire detection products where you will find lots of useful information including;
Approval Certificates
AutoCAD Downloads
Catalogues
Datasheets
Forums
Marketing Bulletins
Presentations
Technical Information including;
User manuals
Application & Design Manuals
Installation Manuals
Commissioning Manuals
Service Manuals
Sales Information
Software Downloads
Contact Us
For further details on this catalogue, contact our customer telephone Help Line
at Letchworth Customer Services on + 44 (0) 1462 66 77 00.
TFS Technical Support Call Centre:Direct: +31 475 352 722
Fax: +31 475 352 725
Hours: 9:00 to 19:00 CET, 8:00 to 18:00 GMT, 7:00 to 17:00 EET
UK only: 08701-238 787
Toll Free: 0800 CALL TYCO or (0800 22 55 89 26)
E-Mail: [email protected]
Our web site can be found at: www.tycoemea.com
11/12
Fire Catalogue
Chapter 1 Page 1
FIRE_Ch1_Introduction:Layout 1 04/12/2012 10:35 Page 2
Chapter 1 - Introduction
This page is left intentionally blank.
Chapter 1 Page 2
Fire Catalogue
11/12
Chapter 2 - MZX Technology
ZETTLER PROFILE Detection Control Panels and
Repeaters
Features
•8.4” TFT colour touch screen multilingual user interface Architecturally attractive and fully programmable
•Ergonomic Icon Display - Simple to operate user interface
eliminates operator errors
•Touch sensitive status LED’s provide event summary
information
•Context sensitive help and on screen operator instructions
- Reduces the need for user training
•User configurable on screed site maps - No need for
additional site plans
•Programmable graphic quiescent display - Opportunity for
customer branding
•Comprehensive point management and disable functions
- Gives the user full control and reduces service and
maintenance effort
•Selectively view or print from the extensive 10,000 event
log using dynamic filters - Effective event diagnostics to
quickly resolve site investigations
•Multilingual support
•Keyless log-on using RFID tags - Identifies and logs user
actions
ZETTLER PROFILE is a powerful fire detection and alarm
system that uses MZX Technology at its heart. Due to
the fact that MZX Technology was originally designed for
operation in the most hostile of environments, the system is
highly resilient to external factors such as electrical noise or
sources of false alarm. The new touchscreen user interface
with context sensitive help has been ergonomically
engineered so that every operation is made easy.
Features such as the touch sensitive LEDs that provide
detailed status information ensure a fast response to all
system events. The system combines ease of use with
high performance, and through innovation brings lifetime
cost benefits to end users. The optional, sleek and discreet
stand alone touchscreen user interface makes the system
suitable for the most critical and sensitive environments.
The screen of the ZETTLER PROFILE panel display is wellstructured and has an easy-to-read appearance. In addition
the home screen can be customised to adopt the end
user’s corporate identity.
The ZETTLER PROFILE panel provides an extensive 10,000
event log which can be selectively viewed or downloaded
and then printed or analysed using dynamic filters. These
effective event diagnostics help to quickly resolve site
investigations.
The Info-Button provides context sensitive help and
on-screen operator instructions. This guarantees fast and
reliable assistance even for infrequent users.
Screen site maps allow easy access to any information
such as floors or detectors. These can be site configured
so will always carry the most up-to-date information. Having
all this information saves time in the event of a fire and
helps to speed up responses during fire fighting.
All necessary information can be viewed in a clear and
structured way. In the case of a system event, it helps to
make the right decision quickly and efficiently.
Log in options include, password, key or RFID. An RFID
card will give instant user control of the menus and also log
the operator access. A new scroll button allows all active
alarm events to be viewed without the need for passwords
or keys.
02/17
Fire Catalogue
Chapter 2 Page 1
Chapter 2 - MZX Technology
Technical Specifications
PROFILE Panel
P115S
P115D
P485D
P405D
P885D
P805D
1
1
2 to 4
2 to 4
2 to 8
2 to 8
Addresses per
loop
250
250
250
250
250
250
Total number of
addresses
250
250
1000
1000
2000
2000
No of zonal LEDs
16
16
80
0
80
0
No of Zones supported
240
240
240
240
240
240
480 x 410 x
140
480 x 410 x
205
480 x 410 x
205
480 x 410 x
205
580 x 458 x
209
580 x 458 x 209
9.7 Kg
10.6 Kg
10.6 Kg
10.6 Kg
15.2 Kg
15.1 Kg
General
Number of loops
Mechanical
Dimensions
HxWxD mm
Weight
Environmental
Operating
Temperature
-8°C to +55°C
Storage
Temperature
-20°C to +70°C
Relative Humidity
Relative Humidity: 90% RH continuous (non-condensing)
EMC/RFI:
EN50130-4, EN50081-1
Electrical
Supply
Voltage(panel):
Input Current
(panel):
Max battery
capacity
230 VAC 50/60 Hz
1.6A
1.6A
1.6A
1.6A
1.6A
1.6A
17 A/H
38 A/H
38 A/H
38 A/H
38 A/H
38 A/H
PROFILE Repeater
General
PR8AS
PR1DS
PZ4DS
PZ8DS
AC Repeater
Compact DC Repeater
Zonal Display
Zonal Display
No of zonal LEDs
80
16
40
80
No of Zones supported
240
240
120 (3 x PZ4DS)
240 (3 x PZ8DS)
195 x 248 x 33
195 x 248 x 33
0.7 Kg
0.7 Kg
Mechanical
Dimensions HxWxD mm
Weight
480 x 410 x 205
9.3 Kg
195 x 248 x 33
0.8 Kg
Environmental
Operating Temperature
-8°C to +55°C
Storage Temperature
-20°C to +70°C
Relative Humidity
Relative Humidity: 90% RH continuous (non-condensing)
EMC/RFI:
EN50130-4, EN50081-1
Electrical
Supply Voltage(panel):
Input Current
Max battery capacity
Chapter 2 Page 2
230 VAC 50/60 Hz
24 Vdc
N/A
N/A
0.9A
0.2A
N/A
N/A
17 A/H
N/A
N/A
N/A
Fire Catalogue
02/17
Chapter 2 - MZX Technology
Panels
P115S
Product Code
557.200.551
P115S
PROFILE one loop panel with TFT
touchscreen display 16 zonal LEDs
250 addresses 5A PSU shallow
housing for 17 AH batteries
Product Code
557.200.552
P115D
PROFILE one loop panel with TFT
touchscreen display 16 zonal LEDs
250 addresses 5A PSU deep housing
for 38 AH batteries
Product Code
557.200.553
P485D
PROFILE 2-4 loop panel with TFT
touchscreen display 80 zonal LEDs
1000 addresses 5A PSU deep
housing for 38 AH batteries
Product Code
557.200.554
P405D
PROFILE 2-4 loop panel with TFT
touchscreen display 240 zone 1000
addresses 5A PSU deep housing for
38 AH batteries
Product Code
557.200.555
P885D
PROFILE 2-8 loop panel with TFT
touchscreen display 80 zonal LEDs
2000 addresses 5A PSU deep
housing for 38 AH batteries
Product Code
557.200.556
P805D
PROFILE 2-8 loop panel with TFT
touchscreen display 240 zones 2000
addresses 5A PSU deep housing for
38 AH batteries
Product Code
557.200.560
PR8AS
PROFILE repeater panel with 80 zonal
leds and AC power supply shallow
housing
P115D
P485D
P405D
P885D
P805D
Repeaters
PR8AS
02/17
Fire Catalogue
Chapter 2 Page 3
Chapter 2 - MZX Technology
PR1DS
Product Code
557.200.801
PR1DS
PROFILE repeater compact TFT
display 16 zone DC powered with
shallow backbox
Product Codes
557.202.812
RDS800
PROFILE repeater distribution switch
RDS800
557.202.901
IMC-V111ET-TB
557.202.902
IMC-111FB-MM-SC
Accessories
557.202.903
IMC-111FB-SS-SC
Industrial VDSL extended media converter
with 1x100Base-TX to 1xEthernet extender,
Terminal block socket
Mini Type 1x 10/100TX (RJ-45) to 1x 100FX
(MM SC) with Link Fault Passthrough Media
Converter
Mini Type 1x 10/100TX (RJ-45) to 1x 100FX
(SM SC) with Link Fault Passthrough Media
Converter
PZ4DS
Product Code
557.200.806
PZ4DS
PROFILE 40 way zonal display
shallow
Product Code
557.200.811
PZ8DS
PROFILE 80 way zonal display
shallow
Product Code
557.202.804
P-RCK
PROFILE repeater 19 inch rack mount
Product Code
557.202.801
P-WSH
PROFILE repeater backbox shallow
spare
Product Code
557.202.818 Replacement bezel for PROFILE user
interface
PZ8DS
P-WDP
P-WSH
Replacement bezel
Chapter 2 Page 4
Fire Catalogue
02/17
Chapter 2 - MX Technology
Ancillaries
557.202.804 557.202.813 557.202.814 557.200.530.P 557.200.531.P 557.202.817 557.202.818 557.202.819 557.202.820 P-RCK PROFILE repeater 19 inch
rack mount
Ancillary Housing matches P115S
Ancillary Housing matches P115D
17AH Addressable expansion PSU
- matches P115S housing
38AH Addressable expansion PSU
- matches P115D housing
Ancillary Housing Matches P805D
Replacement bezel for PROFILE
user interface
PROFILE zonal display inserts. Set
contains zonal inserts 1-80, 81-160,
161-20, 1-40, 41-80, 81-120 and 3 x
blank inserts.
PROFILE RFID Card Pack of 5
557.202.880
PROFILE language inserts Polish
(Pack of ten)
PROFILE language inserts Czech
(Pack of ten)
PROFILE language inserts Italian
(Pack of ten)
PROFILE language inserts Spanish
(Pack of ten)
PROFILE language inserts Russian
(Pack of ten)
PROFILE language inserts Swedish
(Pack of ten)
PROFILE language inserts Danish
(Pack of ten)
PROFILE language inserts French
(Pack of ten)
PROFILE language inserts Austrian
(Pack of ten)
PROFILE language inserts Turkish
(Pack of ten)
PROFILE language inserts Swiss
(Pack of four pieces, two per
language French-CH and Italian-CH)
557.202.881
557.202.882
557.202.883
557.202.884
557.202.885
557.202.886
557.202.887
557.202.888
557.202.889
557.202.890
Profile Demo Case
The PROFILE demo case consist of a PR1DS slim-line
PROFILE repeater panel complete with a mains 24 Vdc
power supply, RJ45 connection lead, Ethernet adapter
and USB memory stick. The display has a custom
protective leather cover that folds to create a desktop stand.
Accessories are secured within a zip-up soft holdall and
the complete demonstration kit is housed within a stylish
carbon fibre effect case with the Zettler logo printed on
the front. For live demonstrations the user interface can be
driven from a personal computer running MZX Checker to
simulate any system configuration. The demo kit allows
sellers to effectively demonstrate PROFILE’s capabilities
and provides potential customers a convenient way of
experiencing the PROFILE touchscreen user interface.
02/17
Product Code
557.202.839
Fire Catalogue
PROFILE Demo Case
Chapter 2 Page 5
Chapter 2 - MX Technology
MZX Detection Panels
Tyco MX detection panels use all the features of Tyco MX Technology to provide the latest fire detection technology meeting
the latest worldwide standards in cost-effective, expandable packages.
Tyco MX detection panels support Tyco MX Technology:
• MX VIRTUAL Multi-sensor detectors
• MX DIGITAL high speed reliable digital protocol
• MX FASTLOGIC fuzzy logic smoke detection algorithms
• MX CCO universal carbon monoxide fire detection
algorithms
Tyco MX detection panels provide modular cost effective
solutions:
•
•
•
•
•
•
Networked panels from 1 to 792 detection loops
Powerful central loop processing functions
Powerful and modular user interface
MX REMOTE diagnostics and service functions
TXG graphical user interfaces
MZX, MX2 and designer housing options
Tyco MX detection panels provide long term fire detection
solutions including upgrade paths from earlier panel
models and a long term develop-ment strategy providing
future upgrade paths.
Tyco MX detection panels include:
• MZX for compact single loop solutions
• MINERVA MX for EN54 LPCB approved systems
• MINERVA T2000 for Marine approved systems
Tyco MX detection panels include a powerful user
interface:
• 640 Character display
• Displays first alarm and most recent alarm
• Permanently displays systems status including number of alarms, number of faults, number of isolated points
• Scroll function allows details of all events and status to be easily viewed
• Displays temperature, CO level and smoke level at point in alarm
• Displays 95 character custom messages for emergency procedures
Chapter 2 Page 6
Tyco MX panels include advanced manager and
engineer functions including:
•
•
•
•
•
•
•
•
•
•
Menu driven
Multi-level password protected
Viewing 3000 event log
Detailed fault reporting
Isolate by point, zone or sector
Viewing and printing status
Viewing and printing isolated points
Manual and automatic walk test and reporting functions
Viewing and printing maintenance reports
Extensive diagnostic functions including simulation and force outputs
• Text and configuration changes/Automatic battery test
• Detector service functions
Tyco MX detection panels include very powerful event/
action programming including:
• Seamless network wide event/action
• 240 x 240 Output map and output sequencing algorithms
• Over 3000 event/action groups for the most complex applications
• Templates for fast programming of standard applications including:
- EN54/BS5839
- EN54 Marine
• User defined templates
• Time, date and special day programming
• Wide range of co-incidence, double knock and delay
functions
Fire Catalogue
02/17
Chapter 2 - MX Technology
Features
•Supports one, two or 4 loops with 125, 250, 500 or 1000
addresses (panel dependant)
• 2km loop length
• High level User Interface with “Front Panel Controls” to
reduce lifetime cost of ownership
• Wide range of detectors including the 3oTec triple sensing
detector providing early detection without false alarms.
• Wide range of ancillaries including door control to BS7273
category A
• DDA compliance using AVBase and loop powered
sounder beacons.
• Approved to EN54 the system is designed to be installed
to BS5839 Part 2
Minerva® MZX Addressable Control Panels
This range of digital addressable fire control panels uses
the well established MXDigital® Loop protocol, detectors, i/o
modules, user interface and software from the MX range of
panels. They provide a single box solution ideally suited for
small and medium sized installations up to 240 zones.
The following models are available :MZX125 Single Loop, 125 Addresses, 16 Zones
MZX250 Single Loop, 250 Addresses, 32 Zones
MZX251 Single Loop, 250 Addresses, 32 Zones
MZX252 Two Loop, 500 Addresses, 32 Zones
MZX253 2 to 4 Loop, up to 1000 addresses, 64 Zones
MZX254 2 to 4 Loop, up to 1000 addresses, 240 Zones
The MZX125 housing has space for 2 x 12Ah batteries
The MZX250 housing has space for 2 x 17Ah batteries
The MZX251, 252, 253 and 254 housings have space for
2 x 38Ah batteries
Product Codes
557.200.532 557.200.533
557.200.534
557.200.536
557.200.538
Running the robust MXDigital® loop protocol the panels can
operate using most cable types. This makes them ideal for
upgrades as the existing cables can be utilised reducing
installation time and cost.
All panels are complete with an integral PSU which will
support a full compliment of loop powered sounders and
beacons.
The MZX250, 251, 252, 253 and 254 control panels can
be fitted with the TLI800EN network interface module,
This enables up to 99 control panels to be seamlessly
networked, or to be added to an existing network of MX Fire
controllers.
Repeaters
Four dedicated repeaters are available.
These repeaters offer the user full panel functionality. Up
to 7 repeaters can be attached to the control panel’s 2 wire
remote bus. Two repeaters are mains driven with internal
mains psu & batteries and two require an external 24 VDC
supply.
MZX16R 16 Zones with space for 7 Ah or 12Ah batteries
MZX32R 32 Zones with space for 17 Ah batteries
MZX64DR 64 Zones (requires 24 VDC supply)
MZXDR 240 Zones (No Zonal Led’s) (Requires 24 VDC
supply)
02/17
MZX125 1 loop 16 Zone Fire Controller
MZX250 1 loop 32 Zone Fire Controller
MZX251 1 loop 32 Zone Fire Controller
MZX252 2 loop 32 Zone Fire Controller
MZX253 2 to 4 loop 64 Zone Fire
Controller (CPU801)
557.200.539
MZX254 2 to 4 loop 240 Zone Fire
Controller (No Zonal LED’S)
557.202.073 2 Loop expansion kit for MZX253 (includes
XLM loop card)
557.200.520 MZX16R 16 Zone Repeater (mains
powered)
557.200.521 MZX32R 32 Zone Repeater (mains
powered)
557.200.526 MZX64DR 64 Zone Repeater (24VDC
powered)
557.200.523
MZXDR 240 Zone Repeater No Zonal
Led’s (24VDC powered)
557.201.502 Semi-Flush Bezel for MZX125/MZX16R
557.201.501 Semi-Flush Bezel for
MZX250/251/252/253/254/MZX32R
557.201.503 Accessory mounting plate for std
modules, IOB800, LIM800 and TUD800
(MZX250/251/252/253/254 only)
557.201.519
Comms Interface mounting plate
(MZX250/251/252/253/254 only)
557.201.510 Rack mount kit for MZX 125
557.201.511 Rack mount kit for MZX 250
557.201.512 Rack Mount Kit for MZX 251/252/253/254
557.201.307
MZX250 17Ah Battery Clamp
557.201.505
MZX251/ 252 38Ah Battery Clamp
557.201.520 MZX251/252/253/254 24Ah Battery Clamp
Fire Catalogue
Chapter 2 Page 7
Chapter 2 - MZX Technology
MZX Addressable Control Panels
Technical Specifications
MZX125
MZX250
Dimensions
H x W x D mm
370x325x126
Weight
7 kg
MZX251/
252/253/254
MZX16R
MZX32R
MZX64DR/
MZXDR
480x410x140 480x410x205
370x325x126
480x410x140
370x254x84
9.7 kg
6.6 kg
9.3 kg
4 kg
10.6 kg
o
o
Operating Temp
-5 C +40 C
Storage Temp
-20oC +70oC
Humidity
90% relative Humidity Non Condensing
Housing Colour
RAL7035
Facia Colour
Pantone Grey 431C
EMC/RFI
EN50130-4 & EN61000-6-3
Supply Voltage
230VAC 50/60 Hz
Input Current
0.9 A
1.6 A
1.6 A
24 VDC
0.9 A
0.9 A
250 mA
Charger Size Note 1
2.5 A
5.0 A
5.0 A
2.5 A
2.5 A
none
Max Battery Size
2x12V 12 Ah
2x12V 17 Ah
2x12V 38Ah
2x12V 12Ah
2x12 V 17Ah
none
Note 1 – Max PSE output current with the charger interrupted (I max b, EN54-4)
MZX Ancillary housings & PSUs
This range of housing & PSU’s is designed to complement the MZX range of fire controllers, the housings are available in
different sizes to match the MZX fire controller. Two ranges of ancillary housing are available; one is designed to
accommodate various modules on the removable chassis plate and also has the option to mount a document holder on
the rear of the door. The other ancillary housings, (aperture housings) are designed to accommodate one or two standard sized MX control, display, printer or annunciator modules ie ANN880, COM820, PRN800 or similar, a chassis plate for
mounting modules is also fitted.
The housings with two apertures are supplied with one blanking plate
Product Codes
557.202.625
557.202.626
557.202.627
557.202.622
557.202.623
557.202.624
557.201.513
557.201.518
ANC125-A
ANC250-A
ANC251-A
ANC125
ANC250
ANC251
Ancillary Housing, One Aperture (Small - matches MZX125)
Ancillary Housing, Two Aperture (Large – matches MZX250)
Ancillary Housing, Two Aperture (Deep – matches MZX251/252/253/254)
Ancillary Housing (Small - matches MZX125)
Ancillary Housing (Large – matches MZX250)
Ancillary Housing (Deep – matches MZX251/252/253/254)
Document Holder attachment (used with ANC125/250/251)
M520 Anc Fitting Kit – req’d for older M520 modules, fittings for 4 modules
Power Supply Units
The power supplies utilise switch mode PSU’s as used in the MZX range of panels, if monitoring of these PSU’s is required
a monitoring kit is available which includes a MIM800, mounting bracket and cables
557.200.530
557.200.531
557.201.516
PSU A17
PSU A38
Chapter 2 Page 8
17Ahr 5A Addressable expansion PSU - matches MZX250
38Ahr 5A Addressable expansion PSU - matches MZX251/252/253/254
PSU monitor kit (includes MIM800)
Fire Catalogue
02/17
Chapter 2 - MZX Technology
Minerva MX2 Range - IEC 61508 Approved (SIL2)
The Minerva MX2 range of panels are intelligent LPCB
EN54 compliant panels, which can be networked to provide
up to 396 detection loops and installed to BS5839:Pt1
2002.
The MX2 design philosophy is to have a single panel
housing that incorporates all the necessary components
required to satisfy the most comprehensive of
specifications. Additional matching ancillary housings can
accommodate a range of standard modules, adjacent to or
remote from the main controller.
The panel has a removable steel front door, which
incorporates the MX user interface and optional zonal
LED’s. The user interface has a 16 x 40-character
backlit LCD display, simple alphanumeric keypad and 5
softkeys. All mandatory operator controls are provided with
LED functions including Day/Night switching. One control
key and 2 status indication LEDs are provided for sitespecific functions.
• MX2 panels support two MX DIGITAL detection loops with
up to 250 addressable devices per loop.
• MX2 panels can be expanded to eight loops supporting
up to 1000 addressable devices.
• MX2 consists of a strong steel enclosure incorporating a
removable chassis plate. The chassis plate holds:
• PSU830 5A 24Vdc battery back power supply and loop
booster to EN54:pt.4.
• FIM800 field interface PCB incorporating two MX DIGITAL
loops.
• CPU800 32 bit processor and memory card
• Optional network card and additional loop card(s)
• Optional IOB800 input/output expansion card
Product Codes
557.200.203
MX2-210 Two loop c/w LEDs shallow housing
557.200.205
MX2-211 Two loop c/w LEDs deep housing
557.200.207
MX2-XB0 Expansion Box Shallow
557.200.208
MX2-XB1 Expansion Box Deep
557.200.209
MX2-FB Panel/repeater flush mounting bezel
557.200.210
MX2-FBX Expansion box flush mounting bezel
557.202.007
XLM800 Loop expansion module
557.202.080
TLI800EN Network Card and Cable 557.202.021
ANN840 LED Annunciator 40 way
bi-colour
557.202.022
ANN880 LED Annunciator 80 way
557.202.020
COM820 Status command module 20 way
557.202.024
PRN800 In-built thermal printer (expansion box)
557.201.211
Ancillary/expansion board mounting kit
02/17
557.202.206
MX battery expansion aperture installation kit.
557.202.204
MX2 Battery housing
557.202.205
MX2 Battery and Expansion Housing
(65AH)
557.202.209
MX2 LCD Assembly (Spare)
557.202.208
MX2 8 Loop Expansion Kit
557.202.200
DCM800 (Display + Control Module)
Fire Catalogue
Chapter 2 Page 9
Chapter 2 - MZX Technology
Features
•Compact
•MX Technology Digital Loop
•LPCB Approved
Minerva MX4000 - IEC 61508 Approved (SIL2)
The MINERVA MX panels are intelligent LPCB EN54
approved panels, which can be networked to provide up to
792 detection loops and installed to BS5839:Pt.1.
• The MX4000 supports two MX DIGITAL detection loops
and can be expanded to eight loops supporting up to
1000 addressable devices.
• The MX4000 provides up to 240 zones of detection
Both panels consist of a strong steel enclosure
incorporating a removable chassis plate. The chassis plate
holds:
• PSB800M 5A 24Vdc battery backed power supply and
loop booster to EN54:pt.4
• FIM800 field interface PCB incorporating one or two MX
DIGITAL loops
• CPU800 32 bit processor and memory card
• Optional network card and additional loop card(s)
• Optional IOB800 input/output expansion card
The panel has a strong cast aluminium front door, which
incorporates a modular user interface that fully complies
with EN54:pt.2. The user interface incorporates the
ODM800 operator display module with a 16 x 40-character
backlit LCD display, simple alphanumeric keypad, 5
softkeys. The OCM800 operator control module provides
all mandatory operator control keys and LED functions
including Day/Night switching. Two control keys and 2
indication LEDs are provided for site-specific functions.
Control keys and LEDs are labelled in English according to
the default LPCB functionality. The slide in decals can be
reversed and alternative text added.
A maximum of 1200 digital INPUT/OUTPUT points can be
provided via expansion boards connected to the remote
bus.
Product Codes
Standard Panels
557.200.003 MX4000 Two to Four Loop
Panel – Shallow Back Box
557.200.543 MX4000 Two to Eight Loop Panel – Deep
Back Box
557.200.009
MX4000 Two to Four Loop Panel - Flush
Back Box
Options
557.202.006
IOB800 (8in/8out) expansion board (Max. 24 I/O on main panel 8in/16out)
557.202.007
XLM-MX two loop MX DIGITAL expansion card
557.202.080
TLI800EN Network Card and Cable
Chapter 2 Page 10
Fire Catalogue
02/17
Chapter 2 - MZX Technology
Features
•Compact
•Low Cost Option
•Rack Mounting Kit
Battery & Expansion Boxes
The batteries and any additional zone LED’s or operator
controls and fireman’s interface are mounted in a separate
housing which can be mounted below the main panel or
behind the panel. The matching battery and expansion box
is available with shallow (17Ah) or deep backbox (38Ah)
according to the batteries used.
The chassis plate in the battery box also has space for up
to 2 x IOB800 input/output expansion modules (maximum
24 I/O) or 1 x MX FILNET or 1 x PSM/PSB800M.
Product Codes
557.200.005
557.200.019
557.200.006
557.200.016
572.065
02/17
Fire Catalogue
MX-BBX 17Ah shallow expansion and battery box
MX-BBX-F 17Ah shallow flush expansion and battery box
MX-DPBX 38Ah deep expansion and battery box.
MX-BATT Deep Battery Box
(322H x 442W x 217D mm)
MX Rack Mounting Kit for standard 19”
racks
Chapter 2 Page 11
Chapter 2 - MZX Technology
Features
•Fully Functional
•Flush or Surface Mounting
•Fully Monitored
Minerva MX Repeaters
The MINERVA MX full function repeater is an EN54 LPCB
approved repeater with optional addressable EN54:Pt.4
power supply. The repeater consists of a steel backbox and
cast aluminium front door which incorporates the ODM800
operator display module with a 16 x 40-character backlit
LCD display, simple alphanumeric keypad and 5 softkeys.
The OCM800 operator control module provides all
mandatory operator control keys and LED functions
including Day/Night switching. One control key and 2
indication LEDs are provided for site-specific functions.
The back box has a removable chassis plate with either the
RSM800 or the PSM800 power supply. APM800
addressable PSU monitor and provides space for 2 x 7 Ah
batteries to provide 72 h backup.
Control keys and LEDs are labelled in English according to
the default LPCB functionality. The slide in decals can be
reversed and alternative text added.
The operator control module (OCM800) can support up
to 80 inputs and outputs in the form of LED annunciators,
IOB800 input/output modules, or com 820 command
modules.
The MINERVA MX repeater is connected to the Panel via
the remote bus (RS485, 1200 m distance). A maximum
of 7 repeaters (including one MX REMOTE repeater) can
be linked to each MINERVA MX panel and can provide full
repeater functions for all panels on the system.
Two power supply options are available for repeaters. The
MXR incorporates an RSM800 repeater supply module for
connection to a 24 Vdc supply. Or the MXR-PSU which
incorporates a PSM800 power supply module for
connection to a 120-240Vac mains supply and an APM800
addressable power monitor for connection to an MX
addressable loop, providing power supply monitoring in
accordance with EN54-pt.4.
Product Codes
Standard Repeaters
557.200.012
MXR Repeater with shallow backbox (24 Vdc)
557.200.017
MXR-F Repeater with flush backbox (24 Vdc)
557.200.013
MXR-PSU Repeater and addressable PSU (120-240 Vac)
Options
557.202.006
IOB-800 (8in/8out) expansion board
557.180.005 Mimic driver module
557.180.016 XIOM universal I/O module
557.202.028 RSM800 PSU Module (24 Vdc)
Chapter 2 Page 12
Fire Catalogue
02/17
Chapter 2 - MZX Technology
Features
•2 MZX detection loops as standard
•Expandable to 8 loops using XLM800
•Same loop power capability of standard MZX4000 panel/
Reduces the cost of network systems
•Uses MXNet networks (network card supplied separately)
•Create a system of distributed loops to reduce installation
costs
•Alarm, fault, power and system fault status display
•Single deep surface mount enclosure
•Integral power supply and space for 38 AH batteries
•Distributed power supplies reduce cabling costs
•On board dual sounder circuits/Printer support at each
black box
•Fully featured and supported remote bus at each black
box-drive repeaters and mimic displays
•Download MX Consys configurations from any panel or
black box on the network
MZX4000 Black Box - IEC 61508 Approved (SIL2)
For situations where a networked MX TechnologyTM panel
is not required to have a user interface an MZX4000 black
box panel can be used. Black box panels consist of steel
back boxes which house the FIM, processor board, power
supply and optional network card and expansion loop card.
The front cover is of steel construction and has a simple
status display panel giving LED indication of alarm, fault,
power and system fault.
MZX4000 black box panels are fully featured MZX
TechnologyTM panels designed to be used on networked
systems in situations where a local user interface is not
required.
Technical Specification
Product Code
Dimensions (mm):
640H X 440W X 230D
Aprox weight: 16 Kg
Colour, housing & front cover: Dawn Grey (BS 4800 10A)
Operating Temp:
Range -8°C to +55°C
Storage Temp: -20°C to +70°C
Relative Humidity:
95% non condensing
Supply voltage: 120 to 240 Vac
Input current:
0.8 to 2.2A
557.200.098
02/17
Fire Catalogue
MZX4000 Black Box Chapter 2 Page 13
Chapter 2 - MZX Technology
Features
•PSU830 5 A 24 V DC battery backed power supply and
loop booster to EN54pt4
• FIM800 field interface PCB incorporating one or two MX
DIGITAL loops
• CPU801 32 bit processor and memory card
• Optional network card and additional loop card(s) (T2000
only)
• VDR (Voyage Data Recorder) Interface as standard
Minerva T2000 and T2000 CV Marine Detection Panels
IEC 61508 Approved (SIL2)
The T2000 is a fully Marine approved EN54 compliant 1 to 8
loop networkable detection panel. The T2000 supports two
Tyco MX DIGITAL detection loops and can be expanded
to eight loops supporting up to 1000 addressable devices.
The T2000 consists of a strong stainless steel or mild
steel Marine approved enclosure incorporating the above
features.
The OCM800 operator control module provides all
mandatory operator control keys and LED functions
including Day/Night switching. One control key and 2
indication LEDs are provided for vessel specific functions.
Control keys and LEDs are labelled in English according to
the default Marine functionality. The slide in decals can be
reversed and alternative text added.
The T2000CV is a 3 loop marine approved panel housed
in a mild steel enclosure designed for use in commercial
vessels.
The batteries and any additional zonal LED’s or operator
controls are mounted in a separate housing which can be
mounted below the main panel or behind the panel. The
battery box incorporates a heavy duty backbox and battery
clamp.
All panels have a strong cast aluminium front door, which
incorporates a modular user interface that fully complies
with EN54 pt2. The user interface incorporates the ODM800
operator display module with a 16 x 40-character backlit
LCD display, simple alphanumeric keypad and 5 softkeys.
The chassis plate in the battery box also has space for up
to 2 x IOB800 input/output expansion modules (maximum
24 I/O) or 1 x PSU830.
Product Codes
557.200.600 T2000 Two To Eight Loop Marine Panel
(Stainless steel enclosure)
557.200.602 T2000B Battery Box (Stainless steel
enclosure)
557.200.605 T2000 BM Battery Box (Mild steel
enclosure)
557.200.606
T2000 RMRS Door Stay Kit
557.200.610 T2000 Standard Two to Eight Loop
Marine Panel (Mild steel enclosure)
557.201.216 T2000 XLM 8-Loop Mounting Kit 557.200.620 T2000CV 3 loop marine panel (mild steel
back box)
557.202.127 VDR Cable For a Standalone panel, Com
port 3
557.202.128 VDR Cable for a networked system, Com
port 1
557.180.454 Marine Bulkhead Mount
557.180.452 Marine 19” rack mount kit for use with
surface mounting housings
557.180.022 Terminal chamber PCB assembly
557.201.233 PSU 830 T2000/T2000R Conversion Kit
557.201.234
PSU 830 T2000 120VAC Kit
508.023.126
AC2SW 230VAC Changeover Unit
508.023.127
AC1SW 115VAC Changeover Unit
Chapter 2 Page 14
Fire Catalogue
02/17
Chapter 2 - MZX Technology
Features
• Fully Functional
• Optional Approved Mild Steel Enclosure
• Fully Monitored R-Bus
Minerva T2000R and T2000R CV Marine Repeaters
- IEC 61508 Approved (SIL2)
The T2000R full function repeater is an EN54 Marine
approved repeater with optional addressable EN54:Pt.4
power supply. The repeater consists of a steel backbox
and cast aluminium front door which incorporates the
ODM800 operator display module with a 16 x 40-character
backlit LCD display, simple alphanumeric keypad and 5
softkeys. The OCM800 operator control module provides all
mandatory operator control keys and LED functions
including Day/Night switching. One control key and 2
indication LEDs are provided for vessel-specific functions.
Control keys and LEDs are labelled in English according to
the default Marine functionality. The slide in decals can be
reversed and alternative text added. The back box has a
removable chassis plate with the PSU830 power supply and
space for 2 x 7 Ah batteries to provide 72h backup.
The T2000R CV indicating repeater is an EN54 Marine
approved repeater (24Vdc Supply). The repeater consists of
a mild steel backbox and cast aluminium front door which
incorporates the ODM800 operator display module with a
16 x 40-character backlit LCD display, simple alphanumeric
keypad and 5 softkeys.Operator controls comprise a panel
buzzer silence button , status LED’s are provided for
fire, fault and power on indication.
Both repeaters are connected to the Panel via the remote
bus (RS485, 1200 m distance). A maximum of 7 repeaters
(including one MX REMOTE repeater) can be linked to each
control panel and can provide repeater functions for all
panels on the system.
The repeater can support up to 80 inputs and outputs in the
form of LED annunciators, IOB800 input/output modules,
XIOM universal I/O modules or the 80 LED mimic module.
Product Codes
557.200.601 557.200.604 557.200.606
557.200.611 557.200.612 557.200.621 557.201.233 557.201.234
508.023.126
508.023.127
02/17
Fire Catalogue
T2000R Marine Repeater with Power
Supply Unit 240 Vac (Stainless steel
enclosure)
T2000R Marine Repeater without Power
Supply Unit 24 Vdc (Stainless steel
enclosure)
T2000 RMRS Door Stay Kit
T2000R Standard Marine Repeater with
Power Supply Unit 240 Vac (Mild steel
enclosure)
T2000R Standard Marine Repeater
without Power Supply Unit 24 Vdc (Mild
steel enclosure)
T2000R CV Marine Indicating Repeater
without Power supply unit 24 Vdc (Mild
Steel enclosure)
PSU 830 T2000/T2000R Conversion Kit
PSU 830 T2000 120 VAC Kit
AC2SW 230 VAC Changeover Unit
AC1SW 115 VAC Changeover Unit
Chapter 2 Page 15
Chapter 2 - MZX Technology
MX Detection Panels - Technical Specifications & System Schematics
MX Detection Panels - Designer Housing Technical Specification
Shallow Housing
Flush Shallow Housing
Deep Housing
Marine
Dimensions (mm)
320Hx440Wx120D
380Hx500Wx120D
320Hx440Wx215D
320Hx440Wx135D
Approx Weight
7 Kg
7.2 Kg
8 Kg
14 Kg
Temperature (Storage)-20oC to +70oC-20oC to +70oC-20oC to +70oC-20oC to +70oC
Temperature (Operating)
-8oC to +55oC
-8oC to +55oC
-8oC to +55oC
-8oC to +55oC
Humidity
up to 95% RH, Non-Condensing
Colour (Housing)
Dawn Grey (BS 4800 10A - 03)
Colour (Modules)
Pantone 431C
EMC/RFI
EN 50130-4
Shock
EN 54-2
Vibration
EN 54-2
MX2 Detection Panels Technical Specification
Panel Shallow Housing
Panel Deep Housing
Expansion Housing Expansion Housing
Shallow
Deep
Dimensions (MM)
580H x 458W x 129D
580H x 458W x 209D
357Hx 458W x 129D
357H x 458W x 209D
Approx Weight
12.7 kg
15.2 kg
6.2 kg
7.5 kg
Temperate (storage)
-20 °C to + 70°C
Temperate (operating) -5°C to +55 °C
Humidity
Up to 90 % RH Non Condensing
Colour (Housing)
Dawn Grey (BS4800 10A-03)
Colour (Modules)
Pantone 431C
EMC/RFI
EN50130-4 EN61000-6-3
IP Rating
IP30
Chapter 2 Page 16
Fire Catalogue
02/17
Chapter 2 - MZX Technology
DESIGNER HOUSING SCHEMATIC
24Vdc
Non-Resettable
24Vdc
Resettable
Field I/O
Network
PC/Modem
Printer
CPU
ODM
TLI
PSU830
RBus
FIM
FRONT
DOOR
Loop C
XLM
Loop A
Loop D
110-240Va.c.
OCM
Loop B
XBus
MAIN PANEL HOUSING
TUD/
IOB
IOB
ANN880
ANN840
or COM820
PSU
MX NET
17 or 38Ah
17 or 38Ah
FRONT
DOOR
MPM
BATTERY & EXPANSION HOUSING
ANN880
ANN840
or COM820
Remote bus up to 15 addresses a combination of
up to 7 x OCM and 15 x MPM Maximum
MX2 Schematic
NETWORK
FIELD
I/O
110-240 Vac
LOOP B
LOOP C
LOOP D
XLM
DCM
CPU
LOOP A
TLI
RBUS
PSB
FIM
PRINTER
NETWORK
PC MODEM
17AH OR 38AH
24Vdc
ANN881
17AH OR 38AH
FRONT DOOR
MAIN PANEL HOUSING
02/17
Fire Catalogue
Chapter 2 Page 17
Chapter 2 - MZX Technology
Features
•MX Digital Loop Protocol
•Extensive Loop Protection
•Interfaced to FIM 800 module
MX Loop Expansion Module
The XLM800 Loop Expansion Module fits “piggyback” style
onto the FIM or an existing XLM 800 and is used to:
• Expand the capability of the MX4000 C.I.E. two loop system to eight loops.
• Replace the FIM loops in case of a failure on either a two or four loop system.
The XLM800 Loop Expansion Module controls the
communications between the detectors (and other
ancillaries) connected on the 2-wire loop circuits and the
controller. In addition, the addressable interface contains
line isolation circuits which protect the loop driver circuit
from short-circuit conditions.
Technical Specification
Product Code
Dimensions: 17.5H x 104W x 196D mm
Battery Requirements: Standby 104.3 mA+loop current Alarm105.3 mA + loop current
Loop Current 495 mA maximum
557.202.007
Chapter 2 Page 18
Fire Catalogue
XLM-MX Two Loop MX Digital
Expansion Card
02/17
Chapter 2 - MZX Technology
Features
•Interfaces to CPU & XLM modules
•3 Download/Network & Printer ports •U­p to 2 MX Loops
FIM800 Field Interface Module
The Field Interface Module FIM is the main interface for field
wiring on MX detection panels and contains plug-in field
wiring terminals, inter board connectors, EMC protectors
and filters and general I/O electronics.
The FIM incorporates a local I/O bus which allows the local
I/O connections to be increased by 24. A variety of I/O
expansion boards are available including:
•
IOB800 (8 in/8 out) expansion board
The FIM801 and FIM801CV provides 1 x MX DIGITAL loop
and the FIM802 provides 2 x MX DIGITAL loops. Each MX
DIGITAL loop can support several kilometres of loop wiring
using a mixed topology using multiple loops and spurs.
The FIM includes two connections to the RBUS one for the
local user interface and one for connecting up to 15 remote
addresses in the form of up to 2 x operator control modules
(OCM800) or up to 15 multi-purpose modules (MPM800).
The FIM provides up to 495 mA of loop power to each
loop to drive loop powered sounders and other loop power
devices. An optional plug-in additional loop cards (XLM800MX) provide up to 8 x MX Digital loops.
The FIM provides 3 configurable external serial ports :
• Port 1 Local printer
• Port 2 Configuration PC or remote diagnostics and
upload/download modem
• Port 3 FSI open protocol or Network card/gateway
TLI800EN (not provided on FIM 801CV)
The FIM incorporates the following local I/O connections:
•
2 x reverse polarity monitored sounder outputs
•
2 x volt free outputs (Default alarm and fault)
•
1 monitored input (eg. Day/Night changeover)
•
1 emergency alarm input
•
1 unmonitored input (eg. Class Change or Tamper)
•
Full monitoring of power supply
•
Ground fault monitoring
Technical Specification
Product Codes
Dimensions:
25H x 105W x 196D mm
Weight:156g
Power Consumption: 119mA (Quiescent - excluding loops and operator interface)
169mA (Alarm)
Relay Outputs:
30Vdc @ 2A
Monitored inputs:
10k Ohm EOL, 3KHz in parallel
RBUS:
RS-485 , default 19.6kB, up to 1200m
Serial Ports:
RS232C, 19.6kB, up to 10m
Local I/O Expansion: Up to 2 modules, up to 24 I/O, max. 300mm
557.202.000
02/17
557.202.001
557.202.008
Fire Catalogue
FIM801 field interface module with one
MX loop driver
FIM802 field interface module with two MX
loop drivers
FIM801CV for Marine T2000 CV
Chapter 2 Page 19
Chapter 2 - MZX Technology
Features
•Universal Input Voltage
•Temperature Compensated
•Full Fault Monitoring
•Can drive 4 fully loaded MX digital loops
•When used with second PSU830 and MX2 8 loop
expansion kit can power 8 fully loaded MX digital loops
•Same footprint and fixings as the PSB821
•Replaces PSB820 and PSM820
•Meets the requirements of EN54 part 4 amendment 2
PSU830 Power Supply
The MX PSU830 power supply module is a state-of-the-art
integrated switch mode system power supply and battery
charger, which can provide up to 5 A external and auxiliary
loop power during alarm conditions.
Fault signals (Loss of AC, Battery charger fault, Battery fault
and earth fault) are provided. Battery voltage readings are
also provided to the FIM and a volt free fault o/p is also
provided.
The charging voltage is temperature compensated. The
power supply recharges the batteries within 24hr for the
following timings:
Screw terminals provide 2 x 27V outputs (one with reset
control) and one 5 V output. The power supply is fitted in a
steel cage with mounting points to allow any of the following
boards to be mounted:
•90hr stand by time and 15 minute alarm condition.
•72hr stand by time and 30 minute alarm condition.
•APM800 addressable power supply monitor module.
•FB800 fuse board with 15 x 24 Vdc fused spurs.
•IOB800 input/output expansion board.
•PTM800 power terminal module.
The power supply provides full condition and fault
monitoring to the system via the FIM. The PSU830
incorporates a booster module to provide the correct
voltage levels to maximise the performance of the MX
DIGITAL protocol.
The MX2 PSU830 Dual PSU Kit is required to power the
XLM800 pcb on 6 to 8 loop systems which require the
extended loop power capability. It consists of the necessary
cables & connectors to enable an additional PSU830 to be
fitted to an MX2 controller.
Technical Specification
Product Codes
Dimensions (HWD): 62 x 132 x 242 mm
Electrical Characteristics:
Input Voltage:
120-240 Vac -15% /+10% 50/60Hz
(auto ranging)
Input Current Rated Load:
0.8-2.2 ARMS
Output Voltages
27.3 Vdc @ +25°C
Non-reset:
27.3 Vdc @ 2 A
5 Vdc @ 2.2 A
40 Vdc @ 2.2 A
Reset:
27.3 Vdc @ 2 A
Rated Output
Maximum Alarm current 5 A for 30 minutes
Maximum continuous load
current (excluding
charging): 2.5 A
Battery Requirements
17 Ah or 38 Ah single PSU
65 Ah dual PSU
Standby Current Consumption:
90 mA @ 24 Vdc
Battery Fault High Resistance:
Single PSU:
0.6 Ohms
Dual PSU:
0.3 Ohms
557.202.210
557.201.232
557.201.231
557.202.044
557.202.030
557.202.031
Chapter 2 Page 20
Fire Catalogue
PSU830 Power Supply Module
PTM800 Power Terminal Module
MX2 PSU830 Dual PSU Kit
PSU 830K Power Expansion Kit
PSU 830 Panel Fixing Conversion Kit
PSU 830 Small Chassis Plate Conversion
Kit
02/17
Chapter 2 - MZX Technology
Features
•Changeable Legends
•Fully programmable
•Optional I/O via R-Bus OCM800 Operator Control Module
The OCM800 is utilised by all MX detection panels and full
function repeaters to provide mandatory operator control
and LED indication functions to comply with EN54:pt.2. The
OCM800 is fully programmable but operates in default
configurations according to the software template used.
In addition the OCM800 can drive up to 80 inputs/outputs
using one of the following modules.
Most software templates allow several of the LED’s
and control buttons to be programmed for site-specific
functions. The LED’s and control buttons both have slide
in legends to suit the default configurations and language.
Standard panels include the appropriate legends for their
relevant markets.
• Up to 5 x IOB800 (8 in/8 out LPCB/VdS approved expansion board)
•Up to 5 x XIOM (16 way universal I/O board)
•One Mimic Panel (80 way LED mimic driver PCB)
•One 80 way ANN880 LED mimic
•One 40 way ANN840 LED mimic using red & yellow LED’s
•One 20 way COM820 LED status/command modules
The OCM800 incorporates the functionality of an MPM800,
which allows it to drive an operator display module to
provide a complete panel user interface.
The following I/O and LED annunciator modules can be
slaved from an MPM800:
Up to 2 x OCM800 units can be connected to an MX panel
via the internal or external RBus communication port.
Technical Specification
Product Code
Dimensions:
Weight:
Power Consumption:
Control Buttons:
Indication LED’s:
Communications:
557.202.013
50H x 232W x 133D mm
0.272 Kg
35 mA (Quiescent)
36 mA (Lamp test)
81 mA (Alarm)
7
18
RS-485: RBus –Default 9.2 Kb
Expansion Bus:
MX X-Bus
Legends for LPCB modules: UK/English, Marine
02/17
OCM800 with Minerva MX Inserts
Fire Catalogue
Chapter 2 Page 21
Chapter 2 - MZX Technology
Features
•0-9 alpha-numeric phone style keypad
•Up and down scroll keys
•Five function keys
ODM800 Operator Display Module
The ODM800 operator display module provides a powerful
and flexible 40 x 16 character backlit LCD display used by
all MX detection panels and full function repeaters. The
ODM800 is used with the OCM800 to provide a fully
compliant and approved user interface EN54 fire detection
panel.
The ODM800 is powered and controlled by the OCM800
operator control module and provides various functions
according to the panel software.
Standard EN54 panels use the LCD display as five windows
on the system.
Window 1-Details of first detector in alarm
Window 2-Details of the most recent detector in alarm
Window 3-System Status including Alarm/Fault and Isolate
counters
Window 4-Full alarm/event details and lists including 95
character procedure plus full password controlled system
manager, service and engineering menu structure
Window 5-Function key legends (eg. Back, Enter, >>,<<)
Technical Specification
Product Code
Dimensions:
Weight:
Power Consumption:
557.202.019
25H x 232W x 133D mm
0.361 Kg
50 mA (Quiescent)
900 mA (Alarm Backlit)
50 mA (Alarm during mains failure)
ODM800 operator display module
OCM800 to IOB800 Connection Details
OCM800 TO IOB800 CONNECTION DETAILS
Chapter 2 Page 22
Fire Catalogue
02/17
Chapter 2 - MZX Technology
ANN840 LED Annunciator
The ANN840 is a standard LED
annunciator user interface module
which can be driven from an
OCM800 or an MPM800. The
MPM800 can be mounted remotely
or “piggy-backed” on the ANN840.
The ANN840 has removable legends
for 40 zone status indicators. Each
zone can indicate RED (eg. Alarm)
and YELLOW (eg. Fault & Isolate).
The functionality is programmed in
the MX detection panel.
The ANN840 operates as 80 outputs
(RED & YELLOW).
Technical Specification
Dimensions:
25H x 232W x 133D mm
Weight: 177 g
Power Consumption:
1 mA + MPM800 (Quiescent)
85 mA + MPM800 (25% zones in
alarm (Alarm))
340 mA +MPM800 (Lamp test)
Product Code
557.202.021
ANN840 LED annunciator
­
ANN880 LED Annunciator
The ANN880 is a standard LED
annunciator user interface module,
which can be driven from an
OCM800 or an MPM800. The
MPM800 can be mounted remotely
or “piggy-backed” on the ANN880.
The ANN880 has 80 red LEDs
numbered 1 to 80. The functionality
is programmed in the MX detection
panel but is defaulted to zone alarm
LED’s.
Technical Specification
Dimensions:
25H x 232W x 133D mm
Weight: 177 g
Power Consumption:
1mA + MPM800 (Quiescent)
85 mA +MPM800 (25% zones in alarm (Alarm))
340 mA + MPM800 (Lamp test)
­
Product Code
557.202.022
ANN880 LED annunciator
The COM820 is a standard user
interface module, which can be
driven from an OCM800 or an
MPM800. The MPM800 can be
mounted remotely or “piggybacked” on the COM820. The
COM820 has removable legends
for 20 status command functions.
Each function includes a command
button and a yellow status LED.
The functionality is programmed
in the MX detection panel. Typical
applications include:
.Manual/OFF/Auto/Isolate
functions for evacuation or plant
control
. Selective isolate and evacuate
functions for fireman’s control
. Selective plant shutdown and
override functions
. Selective system delay and timer
functions
Technical Specification
Dimensions:
25H x 232W x 133D mm
Weight: 204 g
Power Consumption:
0.267 mA (Quiescent - No LED’s) 5 mA (Alarm - 25% LED’s) 21 mA (Lamp test)
­ roduct Code
P
557.202.020
COM820 Status/Command Module
The 80-Way Mimic allows custommade display and presentation
panels to be incorporated in the
MINERVA MX addressable system.
It is supplied as a single PCB, which
may be mounted in an expansion
box or on the rear of a free-standing
panel, as required. It may be used to
drive up to 80 zonal LED indicators,
arranged in any configuration,
together with two FIRE LEDs, one
FAULT LED and one ISOLATE LED.
These indicators can operate in the
same manner as the corresponding
indicators on the panel. A remote
Mimic can be connected to the
MPM800’s configured as remote
Mimic drivers via the remote bus.
Up to 15 MPM800’s may be
connected on to the remote bus,
each with a unique address [set
on-board]. The Mimic includes
audible and visible warning facilities.
Technical Specification
Dimensions:235H x 190Wmm
Operating Temp:
-10°C to +55°C
Storage Temp:
-20°C to +65°C
Relative Humidity:
Up to 95% RH Non- Condensing
Power Consumption:
11mA (Quiescent)
200 mA (25% Alarm)
800 mA (Lamp Test)
COM820 Status Command Module - 20 Way
Remote Mimics
02/17
Fire Catalogue
Product Code
557.180.005
MINERVA 80 way mimic driver
module
Chapter 2 Page 23
Chapter 2 - MZX Technology
Features
•Drives up to 80 I/O points
•Direct Interface to Zonal Displays and other
Modules
•Interfaces to FIM Board
MPM800 Multi Purpose Interface Module
The MPM800 is used to provide various expansion
capabilities via the remote bus (RBUS). The MPM800 is
provided as a standalone module but is also incorporated
into the circuitry of the OCM800 operator control module
to drive the LCD display, LEDs, keyswitch and keys on the
OCM800 and the operator display module. The OCM800
and MPM800 have an XBUS which can be used to drive up
to 80 I/O. The MPM800 also has a printer interface for
connecting to a serial or parallel printer.
An additional printer driver kit is required to allow the
MPM800 to drive a printer - a serial isolation module
should be used to eliminate earth fault indications caused
by some mains connected printers.
Up to 15 x MPM modules can be connected to each panel
of which 8 can be in the form of OCM800 (including the
main OCM800 user interface). One OCM800 can also be
in the form of an emulated user interface on a remote PC
connected via the network or dial up modem.
The following I/O and LED annunciator modules can be
slaved from an MPM800:
• Up to 5 x IOB800 (8 in/8 out expansion board)
• Up to 5 x XIOM800 (16 way universal I/O board)
• One Mimic Panel (80 way LED mimic driver PCB)
• One 80 way ANN880 LED mimic**
• One 40 way ANN840 LED mimic using red
& yellow LEDs**
• One 20 way COM820 LED status/command modules**
The MPM800 is mounted by plugging directly onto the
back of those items marked **
Technical Specification
Product Codes
Dimensions:
Weight:
Power Supply:
Communications:
Printer Connection:
557.202.012
557.202.117
557.180.052
Chapter 2 Page 24
25.4H x 92W x 167.64D mm
98 g
24 Vdc (from PSU830)
RS-485, up to 19.6kB
Serial or Parallel
557.180.053
Fire Catalogue
MPM800 multi-purpose interface modules
Serial printer cable for MPM800 or FIM800
Serial Printer Driver Kit only required for
earlier MPM800 Modules
Isolated RS485 IC (for U16)
02/17
Chapter 2 - MZX Technology
XIOM Input/Output Expansion Board
The I/O on the XIOM can be set in
banks of 8 to operate as follows:
Features
• 16 I/P’s or 16 O/P’s or 8 I/P + 8
O/P
• 5 per MPM800 (80 I/O points)
• Fully configurable in MX consys
• LED driver outputs (10mA source)
• Relay Driver Outputs (100mA sink)
Technical Specification
Dimensions:144H x 85W x 15D mm
The XIOM is a 16 universal input/
output expansion board.
Product Code
557.180.016
XIOM MINERVA Input/Output
Expansion Module (16 Way)
• Voltage Monitor Input (8 - 30Vdc
Normal)
• Volt Free Contact inputs
FB800 Fuse Board
The FB800 fuse board provides
terminations for 15 fused 24Vdc
output spurs from a single 24V d.c.
input. The FB800 is designed to be
normally mounted on the PSU830
power supply. The fuses are rated
at 500mA.
Technical Specification
Dimensions:
93H x165W x 80D mm
Weight: 149 g
Input:
24 Vdc
Output: 15 x 24V d.c / 500mA
Terminations:
2.5 mm
Product Code
557.202.100
FB800 fuse board (15 way)
IOB Input/Output Expansion Board
The IOB800 is an LPCB approved
board that provides 8 opto-isolated
digital inputs and 8 x 24V d.c. relay
outputs for providing I/O expansion
capabilities to MX detection panels
for interfacing to other subsystems
and signalling devices. The IOB800
also incorporates a connector, which
provides decoded signals for the 8
inputs and 8 outputs for specialist
interfacing.
The IOB800 can be used to provide
expansion I/O to the following MX
panel components:
. FIM801/802 field interface
modules (maximum 24 I/O
8IN/16OUT)
. OCM800 operator control
modules (maximum 80 I/O)
. MPM800 multi-purpose interface
(maximum 80 I/O)
02/17
The IOB800 can be mounted in the
top of a battery box or repeater.
The IOB800 has two expansion bus
connectors which allow them to be
daisy chained together.
Product Code
557.202.006
IOB800 Expansion Board and cables
Technical Specification
Dimensions:
15H X 164W X 80D mm
weight: 153 g
Terminations:
1.5 mm
Fire Catalogue
Chapter 2 Page 25
Chapter 2 - MZX Technology
Features
•High level interface to building automation systems
•Meet interfacing requirements for large integrated
projects
Displayed on BACnet Client side:
•Zone alarms, point alarms from fire inputs
•MZX Technology panel faults, faults from zones and
points
•Mains fault, System faults
•Pre-alarms and alarm warnings
•Isolation of zones, loops & points
•Day/Night Mode status
•Analogue values of automatic detectors
Supported commands issued from the BACnet Client side:
•Silence, Resound
•Sounders On and Off
•Evacuate
•Fire Reset
•Isolation of zones and points
MZX BACnet Interface
BACnet can be provided from a stand-alone MZX
Technology panel or from a network via the UC-8112-LX
BACnet converter.
The BACnet converter is a mini RISC-based
embedded computer which converts fire data to the
BACnet communications protocol. The converter needs
special firmware that is simply uploaded from a PC.
Technical Specification
Product Code
Mechanical
Weight: 224 g
Dimensions: 128 x 101 x 27 mm
Mounting: DIN-Rail, wall
Operating Temperature: -10 to 60°C
Operating Humidity: 5 to 95% RH
Storage Temperature: -40 to 80°C
Electrical
Input Voltage: 12 to 24 VDC
96160183
Chapter 2 Page 26
Fire Catalogue
UC-8112-LX BACnet Interface
02/17
Chapter 2 - MZX Technology
Features
•A cost effective digital communication platform to enable
a range of remote services
•Robust dual path transmission over the clients IT
network and the GPRS network, ensures continuity of
communication in the event of a failure
•Regular polling of the IP path and the GPRS path
confirms successful end to end communication - a failure
will be reported within 3 minutes
•Secure communication is ensured by AES encryption
with a 128 bit key and 256 bit hash code
•BRE approved to EN 54-21 for fire alarm transmission
and fault warning routing equipment and LPCB Red Book
listed
•Supplied with an activated 02 SIM card
•All access is securely controlled and logged
RS800-IP/GPRS - IP Communication Module
The RS800-IP/GPRS module connects to an individual or a
network of MZX, MX, MX2 and T2000 fire control panels
to provide a cost effective, secure and robust IP (Internet
Protocol) based communication platform for alarm
signalling, fault reporting and a range of remote services.
Communication is dual path. The primary path is the clients
IP network, eliminating the additional cost of a traditional
PSTN telephone line. Efficient, digital communication puts
negligible demand on the network and ensures future
compatibility as the traditional analogue systems are
progressively phased out.
The RS800-IP/GPRS module connects to the
communication ports and relays of a fire control panel and
converts the RS232 and digital data into IP data that can be
transmitted over the internet.
The GPRS mobile communication network is the secondary
path and maintains communication in the event of a failure
of the primary path.
Technical Specfication
Product Codes
RS800-IP/GPRS
Type:
557.202.090
Dual Path Ethernet / GPRS EN
54-21 Alarm Transmission and
Fault Routing Equipment
Fire Alarms and Fault Warning
Type 1 - Dual Path LPS 1277 Fire
Type 1
Transmission protocol: UDP/IP
Encryption:
AES standard with a 128-bit key
and 256 bit hash code
Data bandwidth:
160 bytes (round trip including
alarm and acknowledgement)
Approvals:
BRE 0832-CPD-1565: EN 54-21: 2006
LPCB Red Book to LPS1277
Power Supply:
From the connected panel’s EN
54-4 power supply
Power Consumption: 100 mA / 24 VDC
Dimensions:
160 x 95 x 40 mm
Weight:
0.2 kg
Housing:
To be mounted in an IP30 / Access
Level 2 metal enclosure, close
coupled to MZX panel.
557.202.091
557.202.093
22-5054
22-5049-10M
22-5049-15M
RS800 WebWay IP/ GPRS
For alarm signalling, fault reporting and remote IP services.
Includes cables, SIM and first year’s service
RS800 WebWay IP
For remote IP services only. No GPRS SIM included. Includes cables and first year’s service
Enclosure for RS-800
WebWay Smart Disc Eng Pack
High performance antenna with
roaming SIM
WebWay High Gain Eng Pack
High gain extension antenna with roaming SIM and 10m cable
WebWay High Gain Eng Pack
High gain extension antenna with roaming SIM and 15m cable
Enclosure for RS-800
Dimensions:
237 x 161 x 58 mm
Weight:
1 Kg
Material:
1.2 mm Mild Steel
Finish:
RAL 7035 Semi Textured
Ingress Protection:
IP30
Access Level:
2
02/17
Fire Catalogue
Chapter 2 Page 27
Chapter 2 - MZX Technology
Desktop Printer
The printer is designed as a
low cost business printer ideally
suited for mounting adjacent to
the fire control panel.The LQ-350
combines high performance with
paper handling flexibility and quiet
operation.
Features
• 300 cps draft/ 90cps LQ.
• Quiet operation
• Lightweight and compact design
• 9 LQ fonts
• 2 paper feed paths
• Convertible push/pull tractor
• Paper guide
• Auto loading
• Paper park
• Cable feed recess
• Epson LQ standard terminal
emulation available
• Parallel and serial interface
Technical Specification
Dimensions:
159H x 366W x 275D mm
Weight:
4.4kg
Operating Voltage:
180V to 264Va.c.
­ roduct Codes
P
557.180.244
MINERVA printer LQ-350
557.180.220
LQ 300+ Printer Ribbon (spare)
557.202.117
MX FIM/MPM to serial printer lead
In-Built Printer
The PRN800 Printer Kit is designed
for use with the designer range of
MX Controllers (MX4000 and T2000). It is fitted to the front cover of the
MX battery housing and is powered
from the PSU830 power supply
via an FB800 fuseboard in the MX
Controller housing.
Features
• A thermal printer mechanism
which ensures high reliability.
• Quiet Operation
• Lightweight and Compact Design
• High Speed Printing: 40 mm per
second.
• High quality printing: 384 dots.
• 40 Columns
• Friction paper feed
Technical Specification
Dimensions:
230H x 137W x 85D mm
Weight:
0.38 Kg
Operating Temp: +5°C to +45°C
Storage Temp:
-20°C to +70°C
Relative Humidity: Up to 80% non-
condensing
EMC: 61000-6-3 for emissions
BS EN 50082-1 for immunity
Product Codes
557.202.024
PRN 800 Printer c/w front cover
module
557.301.014
Spare Paper Roll (pk of 5)
Remote LCD Display
The Remote LCD Repeater
Module is designed to provide an
independent scrolling log of system
status at numerous points within
a building or site. The module
interfaces directly to a serial printer
port of the MX addressable fire
panel. If a local printer is already
connected to the Panel’s MPM800
serial port, a second MPM800 must
be used.
Features
• Uses a backlit 4x20 character
alphanumeric display.
• Provides an internal log of up to
330 events.
• Provides internal audible warning
of an event.
• Allows the event log to be
scrolled.
• Local internal buzzer silence.
• Connects to host panels RS232
port (maximum cable length
between panels and first repeater
of 15 m).
• Provides an external sounder to
mimic the internal buzzer.
• Can be connected to an
unlimited number of other LCD
Repeaters by using the RS232/
RS422 converter (Up to 1200 m
between repeaters).
Chapter 2 Page 28
The LCD repeater must not be used
in the primary fire path. It must not
be used as the sole warning that a
fire exists.
Technical Specification
Dimensions:
150H x 200W x 75D mm
Material: Bayblend polycarbonate/
ABS alloy
Operating Temp:
-10 C to +55 C
Relative Humidity:
Up to 95% RH NonCondensing
Power Supply:
200 mA @24 Vdc
Ext. Sounder Relay: 500 [email protected] Vdc
EMC:
Product Family Standard
EN50130-4 in respect
of Conducted
Disturbances, Radiated
Immunity, Electrostatic
Discharge, Fast
Transients and Slow
High Energy. EN61000-6
3 -1 for Emissions.
Fire Catalogue
­ roduct Codes
P
557.200.030
Remote LCD Repeater MKII
557.202.128
MX FIM com1 to RS422 Lead
557.180.151
RS232/422 converter for LCD
Repeaters.
02/17
Chapter 2 - MZX Technology
DDA Compliant Pager
Features
•UHF radio link for maximum licensable protection
•Unique coding avoids neighbouring system clashes
•Self monitoring of system health
•Rugged steel enclosure to IP65
•Backlit 2 line text display continuously reports system
status
•Additional audible & visible status indicators
•Prioritised Fire Alarm Inputs
•Automated test calls alert pagers to loss of radio signal
•Fault Notification to the lost fire panel via a monitored link
•Key operated “System Test” facility for routine confidence
checking
•Over 90 hour’s backup operation with internal battery
•Achieves Disability Discrimination Act (DDA) compliance Fire Tek Pro Paging System
The FireTek Pro paging system is designed for use with
professional Fire Systems installed in commercial, industrial
and educational premises. The system is primarily designed
to alert the “hearing impaired” in the event of a fire or other
emergency where an audible sounder is the normal means
of indication.
The FireTek Pro has been designed to comply with the
recommendations detailed in BS5839-1: 2002 for alerting
the “hearing impaired” to the activation of a fire alarm
system.
High Integrity Pagers
To complete the system the alphanumeric pagers have
added features specifically incorporated for the “hard of
hearing” when used with the FireTek Pro. These features
include distinct vibrate alerts for emergency messages, a
vibrating out of range indicator which displays “No Service”
on the pager when the radio link is lost, and a vibrating low
battery indicator.
Antenna Options
Mini Dipole Antenna - remote internally mounted antenna for
large sites or areas of difficult signal propagation.
The system can also be used in conjunction with a security
panel to alert guards who might be located remotely from
the main premises.
Folded Dipole Antenna - remote externally mounted antenna
for maximum signal coverage e.g. campuses and multibuilding sites.
The interface to the fire panel comprises of three Prioritised
Fire Inputs and two Fault Inputs. For ease of installation, a
monitored cable assembly is provided with each system
which includes a “common fault” relay output back to the
host fire panel. This output will activate if the FireTek Pro
suffers a mains failure, transmitter fault, antenna mismatch,
interface link failure, or low battery state.
Upon activation of any one of the Fire Inputs, the FireTek Pro
will enter the fire alert condition, prioritising and transmitting
the Fire message to all enrolled pagers. The transmissions
will be repeated until the fire condition is reset. The FireTek
Pro Pagers ensure that users are alerted by distinct vibration
patterns and clear text messages.
UHF Radio Operation
Any alerting system is only as good as its weakest link. The
FireTek Pro utilises UHF radio frequencies, the main benefits
being superior in-building radio signal propagation and the
option of a manual frequency co-ordinate license issued by
OFCOM. Licensing the FireTek Pro provides a higher degree
of protection from interference. This fact is acknowledged in
Section 18.1 of BS 5839-1:2002.
02/17
Fire Catalogue
Chapter 2 Page 29
Chapter 2 - MZX Technology
Technical Specification
Supply Voltage:
Operational Current:
Inputs:
Outputs:
Fault Notification:
Visual Display:
Enclosure:
Dimensions:
Chapter 2 Page 30
230 V AC 50-60 Hz
12 v 7Ah standby battery
250 mA
3 Prioritised Volt Free (Fire)
Input 1 - Fire Alarm - Evacuate
Building
Input 2 - There is an Incident Leave Building
Input 3 - Prepare to Evacuate Await Instructions
2 Volt Free (Fault)
1 off volt free relay output
Mains Failure
Transmitter Fault
Antenna Mismatch
Panel Link Failure
Low/Missing Battery
2 Line Backlit LCD
Steel Enclosure rated to IP65
380 x 320 x 110 mm (H x W x D)
(No antenna fitted)
Product Codes
557.200.071
Paging Transmitter
557.200.074 40 Character Alpha Numeric Pager
557.200.076
1/2 wave dipole antenna
557.200.077
Wall mounting folded dipole antenna
557.200.078
Pole mounting folded dipole antenna
557.200.079
5 metre antenna feeder cable
557.200.080
10 metre antenna feeder cable
Fire Catalogue
02/17
Chapter 2 - MZX Technology
Features
The pagers:• Display messages sent out by the MX as displayed
on the MX LCD
•Internal log of up to 40 events
• Audible and/or vibrate warning of event
• Allows the event log to be displayed
The transmitter:• Connects using a 9 way D type MX interface lead to MX
printer port
Pager Interface
The Type A alarm pager displays alarm and critical fault
messages, (ie power supply failure or mains failure).
The Type A maintenance pager displays all messages sent
by the fire controller.
The MX pager system is designed to provide a facility to
signal all text messages or alarm/fault messages from a
local transmitter to the pagers.
The transmitter connects to the serial printer port on the
FIM800 or if already in use to a MPM800. The pager system
requires a +12 V d.c. connection from a remote psu. If the
transmitter needs to be located further than 2 m from the MX
Panel, then a non-standard serial printer cable may be used,
up to a maximum distance of 14 m.
CAUTION: Before any installation is carried out, an on site
radio paging license must be obtained by the customer.
Care should be taken when designing pager systems.
Normal practice indicates that a site survey should be done.
Contact Product Management for additional advice on site
surveys.
Technical Specification
Product Codes
Dimensions: System operating
voltage:
Effective radiated power: Frequency range: Channel spacing: TX baud rate:
Type approval 557.200.029
577.002.002
577.002.003
577.002.007
328H x 190W x 75D mm
12 to 13.8 Vdc
500 mW Max
450-470 MHZ
25 KHz
512 or 1200
ETS 300 224,EC type approved to
ETS 300 682
577.002.008 G13801N-A
Pager Transmitter
Type A alarm pager
Type A maintenance pager
Pager aerial 60 db gain up to 1km (c/w
mounting bracket)
Optional feeder cable (10m long)
Elmdene 12 V 1 A PSU in Housing
Manual - Vol17A-2-Pager
02/17
Fire Catalogue
Chapter 2 Page 31
Chapter 2 - MZX Technology
Generation 6 Fire Detectors
Features
•Advanced multi-sensor designs
•Choice of heat, optical, optical and heat multi-sensor or
3oTec triple multi-sensor
•FASTLOGIC expert algorithms
•Up to 250 detectors per loop
•Built-in line isolator on 850 series
•Advanced commissioning features using the 850EMT
Engineering Management Tool
•Two way infra-red communication to the 850EMT
Engineering Management Tool
•Protective optical chamber screen
•Robust coated electronics
•Extended service life
•Fire, isolate and fault LED indications
•Green Passport Certified
850 and 830 Series Fire Detectors - Generation 6
- IEC 61508 Approved (SIL2)
The 850 and 830 series of fire detectors are designed to be
both adaptable and flexible which means they can be used
in most premises to protect against a wide range of
potential fire risks. They use sophisticated digital signalling
to communicate with the MZX Technology fire control
panel, sending fire data from each sensing element for
analysis. Because all of the sensed data is sent to the
controller, powerful algorithms can be used to determine
whether a fire condition is real or not. The sensitivity, mode
and degree of verification can be altered by the user in
response to environmental or activity changes.
Both 850 series and 830 series detectors are
environmentally friendly. They do not use any radioactive
parts and can be returned for recycling at the end of their
life.
The detectors are constructed from hardwearing flame
retardant FR3010 ‘BAYBLEND’ plastic. They are supplied
with dust covers as part of the packaging which essentially
prevents contamination entering the detection chambers
during installation, after which they are removed.
A built-in line isolator incorporated into the 850 series
devices means that when a single short circuit fault occurs
on a loop, all the detectors will continue to operate. An
on-board amber LED will give a local indication that the
line isolator has operated. The 830 series detectors can be
used with an isolator base to provide protection against
short circuit faults.
Two way infrared communications allows the detector to
work with the 850EMT Engineering Management Tool to
speed up commissioning and service routines and to
provide status / reports data without the need to physically
access the device. Extended drift compensation reduces
the lifetime cost of ownership by typically doubling the
service life of the detector whilst a new insect screen and
surface coating of electronics results in a robust industrial
design.
Chapter 2 Page 32
Fire Catalogue
02/17
Chapter 2 - MZX Technology
850PH, 851PH and 830PH Photo Heat Multi-Sensor Detectors
With its ability to detect a wide range
of fires from flaming to smouldering
types, the combined optical and heat
multi-sensor detector is the
preferred choice for a range of
applications including light industrial,
retail and office environments.
It operates in a number of approved
modes and sensitivities that can be
dynamically selected to suit different
environmental conditions.
Technical Specification
Detector material: Flame Retardant FR3010 ‘BAYBLEND’
Dimensions:
Height 43mm Dia.109mm
Colour: White
Weight: (Excluding Base)76g.
Voltage: 20 – 40 VDC
Quiescent Current:
380uA
Alarm Current: 3.3mA
Operating Temp: -25 °C to +70 °C
Storage Temp: -40 °C to +80 °C
Relative Humidity:95% (non-
condensing)
Approvals: EN54-5 and EN54-
7,CPD, VdS
Type Approval: CEA4021
851PH MED Approved
Product Codes
516.850.051
850PH Photo Heat Detector
with built in line isolator
516.830.051
830PH Photo Heat Detector
516.850.055
851PH Photo-Heat Detector with built
in line isolator Marine
Technical Specification
Detector material: Flame Retardant FR3010 ‘BAY
BLEND’
Dimensions: Height 43 mm Dia.
109 mm
Colour: White
Weight:
(Excluding Base)76 g.
Voltage: 20 – 40 VDC
Quiescent Current:
380uA
Alarm Current: 3.3 mA
Operating Temp: -25 °C to +70 °C
Storage Temp: -40 °C to +80 °C
Relative Humidity: 95% (non-con
densing)
Approvals: EN54-7, CPD, VdS Type Approval
CEA4021
Product Codes
516.850.052
850P Photo Detector with built in line
isolator
516.830.052
830P Photo Detector
850P and 830P Photo Detectors
More benign environments where any
potential fire will be slow burning can
be protected using the optical
detector. A choice of sensitivities and
modes gives this detector a broad
range of applications.
02/17
Fire Catalogue
Chapter 2 Page 33
Chapter 2 - MZX Technology
850H and 830H Heat Detectors
Complimenting the range is the heat
sensor which can operate in fixed
temperature and rate-of-rise modes
with a number of approved
sensitivities. It is most often used in
areas where high levels of dust are
present or where the environment
precludes the use of smoke
detectors.
Technical Specification
Detector material:
Flame Retardant FR3010 ‘BAYBLEND’
Dimensions:
Height 43mm Dia. 109mm
Colour:White
Weight: (Excluding Base) 81g
Voltage: 20 – 40 VDC
Quiescent Current:
335uA
Alarm Current:
3.3mA
Operating Temp:
-25 °C to +70 °C, Short-term:
to +90 °C
Storage Temp:
-40 °C to +80 °C
Relative Humidity:
95% (non-con
densing)
Approvals: EN54-5, CPD, VdS Type Approval MED Approved
Product Codes
516.850.053
850H Heat Detector with built in line
isolator
516.830.053
830H Heat Detector 850PC and 830PC 3oTec Triple Sensor Detectors
3oTec Triple Sensor Detector
For life protection and when the
environmental conditions are
challenging, the 850PC/830PC
3oTec detector provides the ultimate
in detector performance and false
alarm rejection. It is a multi sensor
that uses optical, heat and carbon
monoxide sensors in concert to
accurately determine the presence
of fire.
Applications include industrial, retail,
transport hubs, and healthcare. Its
false alarm rejection properties make
it the ideal choice for hotel
bedrooms where steam from
bathrooms is a common source of
false alarms.
Technical Specification
Detector material:Flame Retardant FR3010 ‘BAYBLEND’
Dimensions:
Height 43 mm Dia.
109 mm
Colour: White
Weight: (Excluding Base) 94g
Voltage: 20 – 40 VDC
Quiescent Current:
420uA
Alarm Current:
3.3 mA
Operating Temp:
-10 °C to +55 °C
Storage Temp:
-20 °C to +55 °C
Relative Humidity:
95% (non-condensing)
Approvals: 850PC: EN54-5 and EN54-7, CPD, VdS Type Approval: VdS2806, CEA4021
MED Approved
Product Codes
516.850.054
850PC 3oTec Triple Sensor Detector
with built in line isolator
516.830.054
830PC 3oTec Triple Sensor Detector
850 and 830 Series Coloured Detector Covers & Bases
The existing white cover on the 850 and 830 Series Fire Detectors can be removed and replaced with any of the below coloured covers.
Product Codes
517.050.501
517.050.502
517.050.503
517.050.504
517.050.505
517.050.506
517.050.507
517.050.508
517.050.509
517.050.510
517.050.511
Sample set of coloured detector covers and bases - set of 10
Detector Cover & Base in Orange Semi Gloss-pack of 10
Detector Cover & Base in Yellow Gloss-pack of 10
Detector Cover & Base in Matt Green-pack of 10
Detector Cover & Base in Matt Red-pack of 10
Detector Cover & Base in Matt Brown-pack of 10
Detector Cover & Base in Blue Gloss-pack of 10
Detector Cover & Base in Pink Gloss-pack of 10
Detector Cover & Base in Metallic Silver-pack of 10
Detector Cover & Base in Metallic Gold-pack of 10
Detector Cover & Base in Matt Black-pack of 10
Chapter 2 Page 34
Fire Catalogue
02/17
Chapter 2 - MZX Technology
800F Flame Detectors
The 800F is a digital addressable,
low cost infrared flame detector with
some high end features such as
‘Solar Blind’ operation for false alarm
free reliability and an automatic
health check feature. They will detect
a 0.1m2 flaming fire at a range of
20m. Uses the standard MX detector
bases and MX base accessories. An
Intrinsically safe version is available
as part of the System 800 I.S. range.
Technical Specification
Dimensions (mm): 108Dia x 21.2H
Weight: 74 g
Operation Temp:
-20°C to+70°C
Storage Temperature: -40°C to+80°C
Relative Humidity:
90% RH continuous (non-condensing)
Range: 0.1m2 n-heptane at 50 m
Field of View:100°
Standards EN54 pt10 Certification
Product Codes
516.800.006
801F
LPCB
516.800.007
811F
Marine
compensation for detector condition
monitoring. The 801I is LPCB
approved.
Product Codes
801I
516.800.515.A
ADT
516.800.515.T THORN
516.800.515.YTYCO
800I Ionisation Smoke Detector
The 800I ionisation detectors
are offered for old specifications
which still call for ionisation
smoke detectors. The 800CH and
800PH detectors offer improved
performance, significantly lower
false alarms and environmental
compatibility for smoke detection
applications. The 800I nevertheless
offers state-of-the-art ionisation
smoke detection with self verification,
smoke level indication and threshold
Technical Specification
Dimensions: 109dia x 43Hmm
Operating Temp: -20 to +70°C
Storage Temp: -40 to +80°C
Relative Humidity: <95% (non condensing)
Standards:
EN54 pt 7
801PS High Sensitivity Smoke Detector
The 801 PS high sensitivity smoke
detector is designed for applications
which require a detector with a
greater sensitivity than specified
within EN54-7.
Having a response to smoke of
0.6%/m makes this device suitable
for use in locations where early
smoke detection is required, ie
cabinet protection and areas where
aspirating systems would have
previously been considered.
Technical Specification
Dimensions:
109 Dia x 43H mm
Operation temp:
- 25oC to + 70o C
Storage temp:
- 40oC to +80oC
Relative Humidity 95%
non-condensing
Product Code 516.800.518
801PS High sensitivity smoke
detector
Line Shorting Adaptor
Low profile line shorting adaptor
commissioning tool (shorts terminals
together enabling cable resistance
checks to be carried out) - ADT
Branded
02/17
Product Code
517.050.002.A
Line Shorting Adapter
Fire Catalogue
Chapter 2 Page 35
Chapter 2 - MZX Technology
Beam and Linear Heat Detectors
Beam type smoke detection is ideal for large open span buildings where point type detection is unsuitable i.e.
warehousing & sports halls. The range of Linear Heat Detection is of particular use in tunnels and cable ducts and other
similar areas.
Features
•Motorised Auto-Aligning
•Up to two Detectors per System Controller
•Controller provides fire and fault relays for each detector
head
• Each Detector configurable from 8m to 100m
• Integral LASER
• Auto-Align Fast Automatic BeamAlignment
• Auto-Optimise Building Movement and Contamination
Compensation
• Low Level System Controller
• 20mm Cable Gland Knockouts on System Controller
• 2-wire interface from System Controller to Detector
•Worldwide Approvals including EN54:12 and UL268
•Individual fire and fault relays for each detector
FIRERAY 5000 Multi Head Auto Aligning Infrared Optical Beam Smoke Detector
The FIRERAY® 5000 motorised, auto aligning infrared optical
beam smoke detector can support two detector heads per
system, thus saving on installation time and costs. This
innovative system has been designed from the ground up
to include pioneering technology that fully addresses the
needs of the installer and user, both now and in the future.
With its indu­stry leading optics, the FIRERAY 5000 is ideally
suited for the protection of large areas where the use of
traditional detection technologies would prove to be too
difficult and/or costly to install. The FIRERAY 5000 combines
an infrared transmitter and receiver in the same discrete
unit and operates by projecting a well-defined beam to a
reflective prism, which returns the beam to the receiver for
analysis. Smoke in the beam path causes a drop in power,
which, if below a pre-determined level, results in an alarm
signal.
Getting the system operational is simplified by a number of
groundbreaking features that combine to make the FIRERAY
5000 the quickest and easiest detector of its type to install.
Once the detector heads are connected, using the Easifit
First Fix system, an integral LASER, which is aligned
along the optical path of the beam, can be activated. This
allows the reflective prism to be sighted quickly and with
confidence.
Technical Specification
Controller: Detector: Operating Current ­
Operating Voltage: (low power mode):
IP Rating: Operating Temp: Humidity: Chapter 2 Page 36
202w x 230h x 81d mm 0.9 Kg
134w x 135h x 134d mm - 0.5 Kg
14 to 36 VDC
8 mA @ 24 VDC
IP54
-20 to +55oC
93% RH (non condensing) max
Once the LASER has been used to coarsely align the beam,
the AutOptimise beam alignment system takes over and
automatically steers the beam into the optimum position.
The system can be fully customised, according to local
conditions; both alarm thresholds (sensitivity) and time
to Alarm/Fault can be set from the ground level System
Controller.
Each detector head is independently configurable from 8m
through to 100m and has its own individual fire threshold
and dedicated fire / fault relay outputs. The System
Controller retains one set of Fire and Fault relays that is
common to all detectors that are installed.
The FR5000 MultiHead is supplied with one detector head
and reflector for single beam operation from 8 to 50 meters.
An additional detector head can be added to the
controller to enable larger or more complex areas to be
protected (Subject to local codes and standards).
The Fireray 5000 when used in its low power mode can be
interfaced to the MZX Fire Controller using the BDM800
module.
Product Codes
516.015.020
516.015.021
516.015.007 Fire Catalogue
FireRay 5000 System (50 m)
FR 5000 Detector Head (50 m)
FireRay Reflector 100 x 100 mm
4 reflectors are required for distances from
50 to 100 m
02/17
Chapter 2 - MZX Technology
Features
•Separate Transmitter and Receiver Heads
•Range 5 to 120 metres, configurable per set of Detectors
•Integral Laser Alignment in Receiver
•2-wire Interface between Controller and Receiver
•Single and Twin Detector options
•Separate Fire and Fault Relays per Detector
•Low Level Controller with LCD display
•Programmable Sensitivity and Fire Threshold
•Automatic Gain Control (AGC) for drift compensation
•First Fix concept for Transmitter, Receiver and Controller
•Multiple cable gland knockouts for ease of wiring
•Optional Transmitter powering from Controller
Fireray® 3000 Optical Beam Smoke Detector
The FIRERAY® 3000 is ideal for applications where line
of sight for the IR (infra-red) detection path is narrow and
where the building structure uses reflective surfaces. It has
also been designed to be aesthetically pleasing and thus
can equally suit modern architectural buildings as well as
heritage sites, particularly where ornate ceilings exist.
The FIRERAY® 3000 has been designed so that it can be
installed by one operator, with its laser assisted alignment
method combined with easy to use alignment LED’s offering
visual feedback. The integrated laser alignment aid can be
activated at the controller or at the receiver head.
An additional detector head set (one transmitter & one
receiver) can be added to the controller, separate relay
contacts are provided for each of the 2 beam sets.
Technical Specification
Dimensions & Weight
Control Unit: 203 x 124 x 71.5 mm (W x H x D)
606 gms
Transmitter & Receiver: 78 x 77 x 161 mm (W x H x D)
207 gms
Operating Range: 5 to 120 m
Operating Voltage Range:
12 to 36 V DC ±10%
Operating Controller Current (with 1 or 2 Receivers):
14mA (constant)
Operating Transmitter Current:
8 mA (per transmitter)
Power Down Reset Time: >10 seconds
Fire and Fault Relay Contacts: VFCO 2 A @ 30 Volts DC
resistive
Operating Temp. (non-condensing):
UL - -20°C to +55°C
EN54 - -10°C to +55°C
IP Rating: IP54
Relative Humidity (non-condensing): 93%
Product Codes
516.015.030
516.015.031
Fireray3000 Optical beam detector
FireRay3000 Extra beam set
FireRay Optical Beam Smoke Detector Mounting Accessories
There are a range of mounting accessories available for use with FireRay® Optical Beam Smoke Detectors. These
accessories will help reduce installation times and provide a professional mounting solution when faced with challenging
building internals.
The large prism plate will securely
The Universal Mounting bracket can be used
mount 4 prisms and is designed
with the Fireray 5000 detector head and the 1
to be used in conjunction with the
or 4 way prism plates to enable the detector
Universal Mounting Bracket (not
head or prism plates to be easily mounted
included)
and adjusted when fixing to angled walls or
cladding
The small prism plate will securely
mount a single prism and is
designed to be used in
conjunction with the Universal
Mounting Bracket (not included)
The Flat Mounting plate is a metal plate
which will support a single prism or 4 prisms,
the side mounting holes are compatible with
Unistrut® racking systems.
Adjustable bracket for use with the
Fireray 3000 heads or Fireray 5000
head.
02/17
Product Codes
5000-005
5000-006
5000-007
5000-008
3000-201
Fire Catalogue
Universal Mounting Bracket
Flat Mounting Plate for 1 to 4 Prisms
Prism Mounting Plate for 4 Prisms
Prism Mounting Plate for 1 Prism
FireRay3000 adjustable bracket
Chapter 2 Page 37
Chapter 2 - MZX Technology
Linear Heat Detectors
Features
•Alarm & Pre-Alarm temperature ranges from 54oC to
100oC
•Programmable on-site adjustment of sensitivity.
•Up to 500 m continuous length
•Alarm hot-spot length equal to 3% of zone length
•Separate Alarm and Pre-alarm volt-free outputs
•No nomograms or other scales to interpret
•Simple, 3-Step Installation:
•Ambient temperature compensation maintains alarm
temperature accuracy
•Self-Restorable after fire event up to 125oC
•Flexible cable for easy mechanical installation
•Reliable signalling of open and short circuit conditions
•Extrusion and Braiding options to satisfy both mechanical
and environmental conditions
Linear Heat Detection
ProReact Analogue Heat Detector is a control module and
detection cable designed to interface to a conventional
fire alarm panel or addressable detector monitor module
DIM800 or DDM800. The control module monitors the
resistance of specially doped polymers within the sensor
cable which change as a function of temperature. An
abnormal change in resistance along the detection cable
triggers either a Pre- Alarm or Alarm on the interface
module.
The system is intended to simplify system design
and be uncomplicated and straightforward to install.
Commissioning of the controller can be done using a laptop
computer or through an optional built-in self-programming
module. The sensor cable has been designed to be
physically and electronically rugged to suite a range of
environments with options for PVC, Polypropylene or Nylon
coatings or a strong stainless steel braid.
Technical Specification
Product Codes
Environmental Specifications
Min/Max Operating ambient temperature
Controller 0°C – +50°C
Sensor Cable (recoverable)
-40°C – +125°C
Continuous operating temperature range
Sensor Cable -40°C – +90°C
Humidity
Controller 0% - 95% RH
(Max. 75% RH for <75 m cable
and 54°C alarm setpoint)
Sensor cable 0% - 99% RH
Electrical Specifications
Operating Voltage Range
20 Vdc – 28 Vdc
Current Consumption
normal & fault conditions <70 mA (Base PCB only < 50
mA)
pre-alarm OR alarm conditions
<80 mA
pre-alarm & alarm conditions
<100 mA
Relay outputs
Alarm & Pre-alarm FORM C
2 A @ 30 Vdc load rating resistive
0.25 A @ 250 Vac (62.5 VA) load
rating - resistive
516.016.019
Chapter 2 Page 38
516.016.020
516.016.021
516.016.022
516.016.023
516.016.024
516.016.025
516.016.026
Control units
516.016.016
516.016.017
516.016.018
Fire Catalogue
ProReact Analogue Cable PVC order in
multiples of 200
ProReact Analogue Cable PVC order in
multiples of 500
ProReact Analogue Cable with additional
Polypropylene coating order in multiples
of 200
ProReact Analogue Cable Polypropylene
coating order in multiples of 500
ProReact Analogue Cable Nylon coating
order in multiples of 200
ProReact Analogue Cable Nylon coating
order in multiples of 500
ProReact Analogue Cable Stainless Steel
Braid order in multiples of 200
ProReact Analogue Cable Stainless Steel
Braid order in multiples of 500
ProReact ProReact Analogue Controller
with display including EOL unit
ProReact ProReact Analogue Controller
including EOL unit
Sensor
02/17
Chapter 2 - MX Technology
Linear Heat Detectors
Linear Heat Detection
Installation standards such as BS5839 part 1 specify noncombustible cable supports and this requirement extends
to linear heat sensor cable. To satisfy this requirement the
ProReact Analogue Heat Detector range includes a range
of fixings in either Zintec or Stainless Steel and compatible
cable ties.
Product Codes
516.016.220
516.016.221
516.016.222
516.016.223
516.016.224
516.016.225
516.016.230
516.016.231
516.016.232
516.016.234
516.016.235
516.016.236
516.016.237
516.016.238
11/16
Fire Catalogue
Dual Height L cable clip 100 mm Zintec
Standard L Clip 50 mm Zintec
Channel bracket for attaching LHD cable
to flat surface Zintec
V-clip for cable trays Spring Stainless
Steel
L clip with edge clip Zintec
clip extension for use with other clips
where required Zintec
Dual Height L cable clip 100 mm
Stainless Steel
Standard L Clip 50 mm Stainless Steel
Channel bracket for attaching LHD cable
to flat surface Stainless Steel
L clip with edge clip Stainless Steel
clip extension for use with other clips
where required Stainless Steel
110 deg C indoor/outdoor cable tie UV & Heat Stabilised Pack of 100
170 deg C indoor tie wrap Not UV stabilised Pack of 100
170 deg C indoor/outdoor tie wrap Stainless Steel Pack of 100
Chapter 2 Page 39
Chapter 2 - MZX Technology
Standard Detector Bases
To complement the new 850 range and 830 range of detectors, a number of bases and detector accessories are
available. They are designed to further enhance the installability and serviceability of the range with an emphasis on
reducing engineering costs. The detector bases are designed to snap-fit to the ceiling tile adaptor or can be screw fixed
to a ceiling or electrical box in the traditional manner. A park position allows the detector to be mechanically attached to
the base without making electrical connection to facilitate the testing of electronic free bases.
4B-C 4” Continuity Base
The new 4B-C 4” continuity base is
designed to snap-fit to the ceiling tile
adaptor or it can screw fix to a
ceiling in the traditional manner. The
4B-C 4” continuity base is designed
specifically for use with the 850 series
detector and provides a switching
mechanism that ensures continuity
when the detector (and built-in short
circuit isolator) is removed. When
used with the time saver ceiling tile
adaptor, the 4B-C 4” continuity base
uses a snap-fit mechanism that saves
installation time.
Features
• For use with the 850 series
detectors
• Compact rigid design that
improves the appearance and is
easy to install
• Built-in continuity switch that
closes on detector removal
• Electronics free, permits in circuit
testing
• Snap fit to the time saver ceiling
tile adaptor
• Detector locking pin included
• Detector park position for service
and commissioning, holds the
detector mechanically in place
whilst disconnected from the loop
and continuity switch is closed
• Choice of 8 mini-trunking
break-outs
Product Code
517.050.042 4B-C 4” Continuity Base
4B 4” Detector Base
The new 4B 4” detector base is
designed to snap-fit to the ceiling tile
adaptor or it can be screw fixed to a
ceiling in the traditional manner.
Features
• Compatible with 830 series
detectors
• Drives a remote indicator
• Detector locking pin provided
with every base
• Snap fits to the Time Saver
Ceiling Tile Adaptor
• Fits directly to a British or
European electrical back box
• Temporary park position
• Break-outs for surface mount
Product Code
517.050.041
4B 4” Detector Base
Features
• For use with the 830 series
detectors
• Compact rigid design that
improves the appearance and is
easy to install
• Up to 250 x 4B-I 4” isolators can
be connected on each loop
• Snap fit to the time saver ceiling
tile adaptor
• Detector locking pin included
• Detector park position for service
and commissioning, holds the
detector mechanically in place
whilst disconnected from the loop
• Choice of 8 mini-trunking breakouts
Product Code
517.050.043 4B-I 4” Isolator Base
4B-I 4” Isolator Base
The new 4B-I 4” Isolator base is
designed to snap-fit to the ceiling tile
adaptor or it can screw fix to a
ceiling in the traditional manner. The
4B-I 4” base is designed specifically
for use with the 830 series detectors
and provides protection against
short circuit faults on the MZX digital
addressable loop.
02/17
Fire Catalogue
Chapter 2 Page 40
Chapter 2 - MZX Technology
Ceiling Tile Adapter
The Time Saver Ceiling Tile Adaptor
is used with the 4” snap fit base and
consists of three parts, a bezel and
clamp that are fitted to the ceiling
tile and a back-box that carries the
detector and base assembly. It
is available as a complete unit or
alternatively, the back-box can be
ordered separately, as can the bezel
and clamp assembly. Ordering the
parts separately may be preferred if
there is an extended period before
the false ceiling is installed e.g.
“shell and core” projects. Requires
a 127mm diameter hole. The CTA
adaptor plate allows the Time Saver
Ceiling Tile Adaptor to be used with
other devices such as the AV Base,
802SB or Mini Firecryer.
Features
• Cuts installation time by 30%
• Commission the system before
the suspended ceiling is installed
• Suitable for ceiling tiles from 1mm
to 30mm thick
• Made from flame retardant
material
• No additional back-box is
required
• Time saver is designed for use
with a new snap-fit 4” detector
base
• Adaptor available for use with the
AV base & other devices
Product Codes
517.050.060
Ceiling Tile Adaptor Kit consists of
1 x 517.050.056 and 1 x 517.050.057
517.050.056
CTA-BB CTA Back Box
517.050.057
CTA-BC CTA Bezel and Clamp
517.050.058
CTA-AP CTA Adaptor Plate
Features
• Adapts 6” electrical boxes to fit
the 4B-C 4” continuity base
• Architectural trim for neat
appearance
• Concealed fixings
• Use to conceal marks left by old
detectors when replaced by MZX
Technology
Product Code
517.050.054 4B-6A 4” to 6” Base Adaptor
4B-6A 4” to 6” Adaptor
The 4B-6A 4” to 6” Adaptor is
designed for use with U.S. style 6”
electrical back boxes and provides
a flush architectural trim between
the electrical box and the 4B-C 4”
continuity base. It can also be fixed
directly to a ceiling and used to
conceal marks left when older, large
diameter detectors are replaced with
MZX Technology.
Chapter 2 Page 41
Fire Catalogue
02/17
Chapter 2 - MZX Technology
Functional Detector Bases
The range of standard bases is supplemented by this selection of sounder bases, relay bases and accessories, including
loop powered sounder bases for use on MX technology controllers. In addition, changes to the building during it’s life can
be easily adapted to, by retrofitting sounders and relay outputs to existing detection points.
When functional bases are fitted to universal bases, they automatically lock into position. Removal is then achieved using
the detector removal tool. This feature ensures that the detector and functional bases are removed separately.
Tyco MKII Sounder Base
A new low current range of sounder
bases for use with Conventional
and Addressable Fire Alarm Control
Panels.
Product Codes
516.800.911
901SB Universal Sounder Base
516.800.910
802SB MX Loop Powered Sounder
Base
516.800.913
812SB MX Loop Powered UL
Sounder Base
517.050.022
Volume Pot Spare Cover (1 sheet of
144)
517.050.005
4” Detector Base Locking Pin Kit
(PK100)
Features
• Manufactured to EN54 part 3
• Integral sounder and detector
base
• Volume and tone adjustable after
installation
• Low Power Synchronisation
• Do not require use of a standard
base (maybe installed directly
onto a standard besa box)
SAB 801 Sounder Addressable Beacon
The SAB 801 Sounder Addressable
Beacon is an MX Addressable
Beacon that fits into the Standard
Minerva Universal Base. Alternatively
the SAB may be fitted to the 802SB,
812SB, 901SB and 912SB Sounder
Bases to enable the MX Control
Panel to communicate with and
control these sounder bases and
also provide a Flashing Beacon
effectively turning the 802SB, 812SB,
901SB and 912SB into a combined
addressable loop powered sounder
and beacon.
The SAB is suitable for wall or
ceiling mounting. Sound selection
and tones will be as per the 802SB,
812SB, 901SB and 912SB.
Product Code
516.800.956
SAB 801 Low Power Sounder
Addressable Beacon (Compatible
with Consys Version 8.1 and above)
Features
• Dual pole 24V DC relay contact (60VA)
• Very low power consumption
(<20µA except startup)
Product Code
516.800.905
801RB Relay base
Sounder volume can be easily varied
between the maximum 90dBA and
minimum 68dBA-volume settings,
using this simple, functional tool.
Product Code
517.050.015
Volume Adjustment Tool
801RB - Functional Relay Base
The 801RB provides dual relay
contacts for signalling external
devices on MX addressable systems.
A very low operating current even
when the relay is energised enables
the relay base to be used without
any additional power. The dual
contacts are under the control of a
programmable output, through the
powerful cause and effect software.
Volume Adjustment Tool
A simple Volume Adjustment Tool,
specific to the task of sounder
volume selection on the “variablevolume” range of Tyco MKII Sounder
Bases.
Note: Sounder Bases are supplied
with the volume pre-set to maximum
volume.
02/17
Fire Catalogue
Chapter 2 Page 42
Chapter 2 - MZX Technology
Detector Base ­­­Ancillaries
801RIL - Remote Indication LED
All detector bases have the ability to
drive a remote LED in the event that
the installed position of the detector
is not easily visible. The 801RIL
is primarily designed for LPCB
influenced markets but is compatible
with all 800 Series detectors.
Features
• UK Single gang mounting
• High intensity red LED
Product Code
516.800.908
801RIL remote indication LED
801HL - Indication Lamp
The 801HL remote indicator lamp
provides a larger indicator for use
in place of the RIL when longer
distances are involved or in VdS
influenced markets. Typically used
to indicate the source of an alarm
in buildings with long corridors eg.
Hotels, hospitals, apartments.
Product Code
516.800.909
801HL indication lamp
4B-EM 4” Euro Mount
The euro-mounting base provides a
matching back box, which allows the
4” bases to be ceiling mounted with
conduit entries for standard 18 and
21mm conduit.
Features
• 2 x 18 mm conduit entries
• 2 x 21 mm conduit entries
• Fits all 4” Bases
• Accepts up to 8 accessory
terminals
Product Codes
517.050.052
4B-EM 4” Euro Mount
517.050.612
Base Accessory terminal kit
(pack of 10)
Features
• 4 x 20 mm gland entries
• Fits ALL 4” bases
• IP55 with supplied gasket
Product Codes
517.050.051
4B-DHM Deckhead Mount
517.050.612
Base accessory terminal kit
(pack of 10)
4B-DHM Deck Head Mounting
Where the detectors are mounted in
humid and environmentally
challenging situations such as
marine or offshore installations, the
4B-DHM deck head mount provides
a sealed waterproof mounting which
protects the electrical connections in
the base. Can be screwed, bolted /
welded to the deckhead. Supplied
with 1 terminal. If more are required,
use the optional base accessory
terminal kit.
Protective Detector Cage
Robust steel protective cage for
Series 800 detector ranges using
the 5” bases. Ideal for schools and
sporthalls or whenever detectors
need protection.
Product Code
517.050.614
CW-5B Detector Cage
Strong coated steel construction with
4 point fitting.
Protective Detector Sounder Base Cage
White powder coated steel protective
cage for Series 800 Detectors
fitted with a sounder base. Internal
dimensions: 120mm dia x 80mm
deep.
Chapter 2 Page 43
Product Code
517.050.011
Steel Protective Detector Cage
Fire Catalogue
02/17
Chapter 2 - MZX Technology
Detector Ancillaries
Features
•Provides clear identification of address
•Colour coded
•Flag remains on base
800 Series MX Address Flag
The 800 Series detectors incorporate a feature, which
automatically transfers the address flag to the detector base,
when the detector is plugged into the base. On removal of
the detector the address flag remains on the ceiling, thus
ensuring that detectors are not accidentally returned to the
wrong detector base following service routines.
Most MX detection panels incorporate additional fail
safe software features to ensure that incorrect detector
positioning does not compromise the system. Address
flags are supplied in packs of 100. Labels are provided on
sheets of 250 in eight colours to enable quick identification
between different loops.
Product Codes
516.800.915
516.800.931
516.800.932
516.800.933
516.800.934
MX Address flags (pack of 100)
Address flag labels Loop A - White
Address flag labels Loop B - Yellow
Address flag labels Loop C - Purple
Address flag labels Loop D - Green
516.800.935
516.800.936
516.800.937
516.800.938
Address
Address
Address
Address
flag
flag
flag
flag
labels
labels
labels
labels
Loop
Loop
Loop
Loop
E - Grey
F - Blue
G - Orange
H - Red
Features
•Colour coded for Easy Loop Identification
•Space for Zonal Label
•Strong Adhesive Backing
Callpoint & Ancillary Address Labels
Detectors have a special address flag for carrying the
address labels - detailed in the detector section. For other
devices or on detectors where zone information is also
required a series of address labels are available.
Numbered 1 to 250, the address labels are available in 8
different colours to distinguish between different loops.
In addition small zone labels can be fixed to the address
labels.
Product Codes
Zone Labels
599.047.011
599.047.012
599.047.013
599.047.014
599.047.015
599.047.016
599.047.018
599.047.019
599.047.020
599.047.021
599.047.022
599.047.023
599.047.024
02/17
Zone labels - Zones 1 - 16
Zone labels - Zones 17 - 32
Zone labels - Zones 33 - 48
Zone labels - Zones 49 - 64
Zone labels - Zones 65 - 80
Zone labels - Zones 81 - 100
Zone labels - Zones 101 - 120
Zone labels - Zones 121 - 140
Zone labels - Zones 141 - 160
Zone labels - Zones 161 - 180
Zone labels - Zones 181 - 200
Zone labels - Zones 201 - 220
Zone labels - Zones 221 - 240
Address Labels
599.047.030
599.047.031
599.047.032
599.047.033
599.047.034 599.047.035 599.047.036 599.047.037 Fire Catalogue
Address
Address
Address
Address
Address
Address
Address
Address
Labels
Labels
Labels
Labels
Labels
Labels
Labels
Labels
1
1
1
1
1
1
1
1
- 250 Loop A - White
- 250 Loop B - Yellow
- 250 Loop C - Purple
- 250 Loop D - Green
– 250 Loop E Light Blue
– 250 Loop F Orange
– 250 Loop G Red
– 250 Loop H Dark Blue
Chapter 2 Page 44
Chapter 2 - MZX Technology
Duct Probe Air Sampling
Where smoke within duct work needs to be detected these duct probe units provide an economical solution, for
use with 800 series detectors. SMP Duct Probe Units
The SMP Duct Probe Units are designed to be installed in air conditioning
supply and exhaust ducts for the purpose of monitoring the airflow for
smoke and combustion products.
The SMP69 probe units are designed to accept and operate with the
800 series detectors. For general applications it is recommended that
photoelectric smoke detectors rather than ionisation smoke detectors are
used.
Warning
Duct probe units sited in the common duct work
to several extract grills may fail to respond to
smoke from any one extract due to the effect of
dilution. The SMP units will not respond to airflow
of less than 1.5 m/sec.
SMP69
Height 90 mm
Width
150 mm
Length
225 mm
Weight
1.2 Kg
The SMP stainless steel probe unit is designed to withstand the more
demanding environments of the offshore oil and gas industries.
The units are designed to operate in airspeeds of 1.5 to 25 metres per
second. A range of sampling tubes from 525mm to 1575mm are available.
Technical Specification
Operating temperature: -20°C to + 70°C
Storage temperature: -25°C to + 80°C
Relative Humidity: 0 to 95%
SMP69 Stainless steel 316 housing
with transparent polycarbonate cover
SMP69 Duct Probe Air Sampling - Stainless Steel
Product Codes
517.025.035
SMP69 Stainless Steel Duct Probe
unit and universal detector base for
Series 600/800 Detectors.
517.025.028
DPS450 Probe tube stainless steel
450mm and exhaust
517.025.029
DPS600 Probe tube stainless steel
600mm and exhaust
517.025.030
DPS750 Probe tube stainless steel
750mm and exhaust
Chapter 2 Page 45
517.025.031
DPS900 Probe tube stainless steel
900mm and exhaust
577.025.032
DPS1200 Probe tube Stainless Steel
1200mm and exhaust
517.025.033
DPS1500 Probe tube stainless steel
1500mm and exhaust
Fire Catalogue
Datasheet - Product Code PSF92
“SMP69 Duct Probe Unit”
Manual - Vol 01B-06-D1 “Detectors
Fire Manual
02/17
Chapter 2 - MZX Technology
Features
•DPK6 for use with Generation6 multi-sensor
detectors 850PH and 830PH with built-in 4B-C
4” Continuity Base
•Designed to comply with prEN 54-27
•One-pipe air sampling system
•Patented venturi pipe and duct housing
•Test hole on cover
•Simple installation
•Simple service and maintenance
DPK6 Duct Probe
The DPK6 duct probe units have been developed to detect
smoke in ventilation ducts. They offer significant benefits
in terms of performance and installation. The system
comprises a single duct probe tube and housing specially
designed for optimum airflow through the smoke detector
and suitable for use in incoming, outgoing and circulation
air ducts of ventilation and conditioning systems. The duct
probes can operate across a wide range of airflow speeds
and are designed to comply with prEN 54-27and VdS.
Unlike more traditional duct probe units that employ an inlet
and exhaust tube with sampling holes, the DPK6
unit uses a highly efficient single sampling tube that is
slotted along its length. This allows the sampling tubes to
be cut to the desired length whilst maintaining maximum
efficiency.
In order to reduce the time required to test the duct probe
detector during routine maintenance, an aperture is
provided that allows aerosol test gas to be directed at the
detector without having to dismantle the unit.
Accessories
Tyco Fire Protection Products offers 3 lengths of the duct
probe tubes. The tube is made of aluminium and can easily
be shortened to suit the span of the air duct. Where the
unit is mounted on insulated or circular air ducts, the DPK6MB mounting bracket is required.
Product Codes
517.025.056 517.025.058 517.025.059 517.025.060 517.025.061 517.025.055 02/17
Fire Catalogue
DPK6 Duct Probe with 4B-C 4” Continuity
Base
DPK6-60 - Duct Probe Tube 60 cm
DPK6-150 - Duct Probe Tube 150 cm
DPK6-280 - Duct Probe Tube 280 cm
DPK6-MB - Duct Pobe Mounting bracket
DPKF - Filter
Chapter 2 Page 46
Chapter 2 - MZX Technology
MX Addressable Input/Output Modules
APM800 Addressable Power Supply Monitor
The APM800 is an MX addressable
power supply monitoring module
which is usually used with the
PSM800/820/821 power supply
module to make an addressable
power supply. The APM800 is
designed to fix to studs on the top
of the PSM800/820/821 The APM800
monitors the PSM800/820/821 for
mains failure, earth fault, battery
charger fault and battery fault. It can
reset the PSM800/820/821 resettable
24Vdc output and initiate a battery
test which then reports battery
voltage and current to the controller.
Technical Specification
EMC/RFI: Equal or exceeds EN50081- 1 & EN50130-4
Operating Temp.:
-25oC to +70oC
Relative Humidity:
up to 95% RH non-condensing
Dimensions:
24H x 127W x 57D mm
Weight: 0.794Kg
­ roduct Code
P
557.202.027
APM800 addressable power supply
monitor
Technical Specification
EMC/RFI: Equal or exceeds EN50081- 1 & EN50130-4
Operating Temp.:
-25oC to +70oC
Relative Humidity:
up to 95% RH non-
condensing
Dimensions:
13H x 48W x 57D mm
Weight:100g
EOL Resistor:
200 Ohm
Monitor Resistor:
100 Ohm
­ roduct Code
P
555.800.001
MIM800 mini-input module
MIM800 Mini-Input Module
The MIM800 is a small MX
addressable module designed for
monitoring a single input circuit.
The MIM800 can monitor normally
open or normally closed inputs and
provides open and short circuit
monitoring of the line. The MIM800 is
designed for fitting in small devices
such as flow switches, special
detection devices and explosion
proof callpoints. A variant of the
MIM800 is used in all callpoints and
pullstations.
CIM800 Contact Input Module
The CIM800 is a flexible addressable
input-monitoring device that fits in
the standard ancillary housings.
The CIM800 provides two inputs to
current MX panels though this can
be implemented as two separately
wired spurs (Style B) or as a loop
(Style A). Both spur and loop input
wiring can be configured to monitor
normally open or normally closed
inputs. In addition both can be
configured to initiate an alarm or
short circuit fault message in the
event of a short circuit on normally
open monitoring circuits.
Technical Specification
EMC/RFI: Equal or exceeds EN50081-1 & EN50130-4
Operating Temp.:
-25oC to +70oC
Relative Humidity:
up to 95% RH non-condensing
Dimensions:
14H x 148W x 87D mm
Weight:100g
EOL & monitor resistor: 10k Ohms
­
Product Codes
555.800.002
CIM800 contact input monitor
555.800.032
CIM800 Module c/w Front Cover
Technical Specification
EMC/RFI: Equal or exceeds EN50081- 1 & EN50130-4
Operating Temp:
-25oC to +70oC
Relative Humidity:
up to 95% RH non-condensing
Dimensions:
14H x 148W x 87D mm
Weight:100g
Product Codes
555.800.012
DIM800 detector input monitor
555.800.042
DIM800 Module c/w front cover
DIM800 Detector Input Module
The DIM800 is designed to power
and monitor a circuit of low
voltage conventional detectors and
callpoints. The detection circuit
is powered from an external 24V
d.c. supply and is reset by the MX
addressable panel. The DIM800
monitors the external 24V d.c. and
provides a fault signal if it is lost. The
input detection circuit can be wired
as one or two spur circuits (Class B),
one loop configured circuit (Class
A) or one 4 wire detection circuit.
The DIM800 is designed to be
compatible with most conventional
detection products. Compatibility
has been tested to date on the
following products: Compatible
Thorn detectors: M300 Series,
M601 Series, S100 Series, H Series,
S231F, S231F+ & CP200.
Chapter 2 Page 47
Fire Catalogue
02/17
Chapter 2 - MZX Technology
LIM800 Line Isolator Module
The LIM800 Ancillary Line Isolator
Module is designed to be used
on all MX addressable loops. It
monitors the line condition and
upon detection of a short circuit it
isolates the affected section whilst
allowing the rest of the addressable
loop to function normally. The
LIM800 Ancillary Line Isolator
Module ensures that on a looped
addressable system a short circuit
fault cannot disable more detection
devices than would be lost on a
conventional non-addressable
system in accordance with BS5839
Part 1.
Technical Specification
EMC/RFI: Equal or exceeds EN61000-6-3 & EN50130-4
Operating Temperature: - 25°C to +70°C
Relative Humidity:
Up to 95% RH non-condensing
Dimensions: 14H x 148W x 87D mm
Weight:100g
Product Codes
545.800.004
LIM800 Ancillary Line Isolator
Module
545.800.033
LIM800 Ancillary Line Isolator
Module c/w front cover
outputs are active, and illuminates
a yellow LED when the timer is
counting down. To provide a warning
that the delay is nearly over, the
red LED and the buzzer will pulse 5
minutes before the end of the delay .
The TM520 requires a separate 24V
DC supply to operate. The module
is not addressable and will therefore
not take an address on the loop.
Technical Specification
Powered: 24Vdc
Temperature Range: -20°C to +70°C
Operating Humidity: <95% RH
Dimensions:
87H x148W x 14D mm
TM520 Timer Module
The TM520 provides 2 x outputs that
can be activated based on a delay
time. If either the key-switch on the
module is activated, or a predefined
event within the control panel occurs
then a timed delay (set between 10
minutes and 2 hours 10 minutes) is
started. When the delay reaches zero
the TM520 outputs are activated.
The unit sounds an internal buzzer
and illuminates a red LED when the
Product Code
557.180.423
TM520 timer module - non
addressable
SIO800 Single Input/Output Module
The SIO800 Single Input/Output
Module is designed to provide a
monitored input and a volt free relay
changeover output. It consists of an
input for monitoring the status of a
normally open contact and a single
changeover relay contact. The relay
is controlled by a command sent
from the Minerva MX Fire Controller
via the addressable loop. The state of the relay
(activated,deactivated or
stuck) is reported to the Minerva
MX Fire Controller. The LED may be
turned ON or OFF by the controller
during a relay activated condition.
Technical Specification
EMC/RFI:
Product Family standard EN501304 in respect of Conducted
Disturbances, Radiated Immunity,
Electrostatic Discharge, Fast
Transients and Slow High Energy.
61000-6-3 for Emissions.
Operating Temperature: -25°C to + 70°C
Relative Humidity: Up to 95% RH non-condensing
Dimensions: 14H x 148W x 87D mm
Weight:
105g
Product Codes
555.800.063
SIO800 Single Input/Output Module
555.800.064
SIO800 Single Input/Output Module
c/w Front Cover
Technical Specification
EMC/RFI Equal or exceeds
EN61000-6-3 & EN50130-4
Operating Temperature:
-25oC to +70oC
Operating Humidity:
Up to 95% RH non- condensing
Product Codes
577.800.006
DDM800 Universal Fire and Gas
Module
577.800.036
DDM800 Universal Fire and Gas
Module c/w front cover
577.800.056
DDM800 Universal Fire and Gas
Module housed in IP55 D800
Enclosure
557.800.057
DDM800 Detector Removal End of
Line Resistor (pack of 10)
DDM800 Universal Fire and Gas Module
The DDM800 provides the ability to
connect and interface 2 zones of
conventional 2 wire fire detectors or
two 4-20mA sensors to the MX Fire
alarm controllers.
When used to interface conventional
detection devices, Open &
Short circuit and device removal
monitoring is provided. Intrinsically
safe (IS) detection is supported
when used with a galvanic isolator
An integral line isolator is
incorporated in the module.
Loop powered or 24vdc operation.
The 4-20mA interface can be used
to monitor devices such as gas
detectors, temperature alarms or any
4-20mA interfaced device.
Compatible with MXConsys version
15 or later.
02/17
Fire Catalogue
Chapter 2 Page 48
Chapter 2 - MZX Technology
RIM800 Relay Interface Module
The RIM800 provides a single
programmable relay output from the
MX DIGITAL addressable loop which
can be programmed for a variety of
applications including signalling fire
conditions to plant, machinery, fire
doors, dampers & security systems.
The RIM800 relay coil is monitored.
The RIM800 relay contact is rated
for 2A @ 24V d.c. but can be used
to switch mains voltage when used
with the HVR800. This unit has two
opto-isolated terminals specifically
for driving the HVR800.
Technical Specification
EMC/RFI:
Equal or exceeds
EN61000.6.3 &
EN50130-4
Operating Temp.:
-25oC to +70oC
Relative
Humidity:
up to 95% RH
non -condensing
Dimensions:
14H x 148W x 87D
mm
Weight:
100 g
Quiescent Current:
200µA
Relay contacts: 2A @ 24 V d.c.
Product Codes
568.800.003
RIM800 relay interface module
568.800.033
RIM800 Module C/W Front Cover
Technical Specification
EMC/RFI:
Equal or exceeds
EN61000.6.3 &
EN50130-4
Operating Temp.:-25oC to +70oC
Relative Humidity:up to 95% RH
non-condensing
Dimensions:
26.5H x 42W x
74D mm
Relay Contacts: Up to 10A @
250Va.c.
Product Codes
568.800.004
HVR800 high voltage relay 568.800.034
HVR800 in isolated D800 housing Technical Specification
EMC/RFI:
Equal or exceeds
EN61000.6.3 &
EN50130-4
Operating Temp.:-25oC to +70oC
Relative Humidity:up to 95% RH
non-condensing
Dimensions:
14H x 148W x
87D mm
Weight:
100 g
Output rating:
2 A @ 24 V d.c.
EOL resistor:
27 k 1/2 W
Product Codes
577.800.005
SNM800 sounder notification module
577.800.035
SNM800 Module c/w Front cover
Relative Humidity:
Dimensions:
Weight:
Output rating:
Product Codes
577.800.011
LPS800 Loop Powered Sounder
module
577.800.041
LPS800 Module c/w front cover
HVR800 High Voltage Relay Module
The HVR800 module is a
non-addressable device which
allows a low current mains
rated relay to switch up to 10A.
Alternatively a low voltage drive signal such as that provided by
the RIM800 or 80 way mimic can
be used to switch the integral mains
relay via the opto-isolated input.
SNM800 Sounder Notification Module
The SNM800 is a remote
addressable sounder circuit output
device capable of switching sounder
and speaker circuits up to 2A @
24V d.c. or provide a monitored
output facility for other applications.
These can be used in addition to the
two circuits provided as standard
on most MX detection panels.The
SNM800 can support sounder
circuits wired as a spur (Class B –
Style Y) or in a loop configuration
(Class A – Style Z). The SNM800 can
be configured with a RIM800 to provide a secure monitored
extinguishing release solenoid
control.
LPS800 Loop Powered Sounder Module
The LPS800 provides a single
monitored sounder output circuit
with up to 75 mA of power sourced
from the MX panel.
Technical Specification
EMC/RFI:
Equal or exceeds
EN61000.6.31
& EN50130-4
o
o
Operating Temp: -25 C to +70 C
up to 95% RH
non- condensing
14H x 148W x
87D mm
100 g
75 mA @
24 V d.c. max
NOTE: Each MX Digital Loop can
provide up to 495mA for loop
powered sounders and modules
SB520 Sounder Booster Module
The SB520 sounder booster module
enables the SNM800 to drive circuits
with higher currents whilst
maintaining the reverse polarity
integrity line monitoring.
Technical Specification
EMC/RFI:
Equal or exceeds
EN61000.6.31 &
EN50130-4
Operating Temp: -25oC to +70oC
Chapter 2 Page 49
Relative Humidity: up to 95% RH
non--condensing
Dimensions:
14H x 148W x
87D mm
Weight:
100 g
Output rating:
15 A @ 24V
d.c./10A Max.
per terminal
Non addressable
Fire Catalogue
Product Codes
577.001.023
SB520 Sounder Booster Module
577.001.033
SB520 Module c/w Front Cover
02/17
Chapter 2 - MZX Technology
BDM800 Beam Detector Module - Loop Powered
The BDM800 Beam Detector
Module is designed to interface the
FIRERAY 50R or the 100R reflective
beam detector to the MX Digital
Addressable Loop. The BDM800
provides power from the loop,
monitors the Fire and Fault outputs
of the detector and also monitors
inter-connections for open and
short circuit faults. The BDM800
can also be used with the FIRERAY
2000 active infrared beam detector.
Supplied fitted in a standard double
gang ancillary housing, the BDM800
greatly simplifies the wiring normally
associated with beam detection.
The considerable cost of providing
local power supplies that satisfy the
stringent requirements of BS5839
part 1 is eliminated.
Features
• Power Beam detectors directly from the MX Digital loop
• Reduced wiring and installation costs
• Monitors beam detector for fire and fault
• Inter-connection monitored for open and short circuit faults
• LPCB and VdS approved
(pending)
• Can be installed to BS5839 part 1
2002
•On board LED indicates polling and
active
•Use with reflective beams
FIRERAY 50R or 100R for greater
savings on installation
•Compatible with FIRERAY 2000
+ FIRERAY 5000 beam detectors
•Optional BTM800 beam terminal
tion module to further simplify installation
­ roduct Code
P
555.800.066
BDM800 Beam Detector Module c/w Cover
BTM Beam Termination Module
In many cases it will be necessary
to site the BDM800 Beam Detector
Module some distance from the
beam detector itself. To minimise
and simplify wiring in such cases
an optional unit, the BTM800 beam
termination module is available. The
BTM800 is also housed in a standard
double gang ancillary cover and has
all the connections and components
required to minimise installation time.
Features
•Simplifies the wiring between
Beam detector and BDM800
•Allows BDM800 to be sited up to
40m from the beam detector
­ roduct Code
P
555.800.067
BTM800 Beam Terminal Module c/w
Cover
MIO800 Multi-Input Output Module
The MIO800 is a general purpose
interface module for use with MX
technologyTM fire detection systems.
It allows multiple input and output
connections to be made between
external equipment and the MX
Digital loop. Three input and four
outputs are provided. Each input
and output can be programmed
independently using the MX Consys
configuration tool to provide
customised functionality.
An IP55 rated D800 style housing is
used as the standard enclosure with
the option of a DIN-rail mounting kit
for in-cabinet installations.
Features
• Normally open or normally closed
inputs
• Inputs monitored for open or
short circuit faults.
• STYLE B (short circuit gives an
alarm) or STYLE C (short circuit
gives a fault) selectable for inputs
• Provides four digital outputs
• All four outputs can drive a
self-powered high voltage relay
HVR800
• Two outputs have both volt free
change over contacts and HVR
Drivers.
Technical Specification
Operating Temperature:
-25°C to + 70°C
Storage Temperature:
-40°C to +80°C
Operating Humidity:
Up to 95% non
condensing
Dimensions (HWD):
Module 72 x 110 x 18mm
Boxed 124.5 x 166.5 x 84.5mm
Weight: Module 70g
Boxed 271g
Relay Contact Rating:
DC - 2A @ 24V dc
­ roduct Codes
P
555.800.065
Multi I/O Module 557.201.401
D800 Ancillary Housing
557.201.303
Din Rail Mounting Kit
TSM800 Door Control Module
The TSM800 is used to control fire
doors in accordance with BS7273
Part 4. When activated, either by a
fire signal or by a fault or isolation
within the fire door zone, the TSM800
will interrupt the supply to the door
holders and the doors under control
of the module will close. The module
has the provision to monitor a contact to report to the fire controller if
the door fails to close. The module
also includes a built-in line isolator.
This module requires MX Consys 10
or later to function.
Technical Specification
EMC/RFI: Equal or exceeds
EN61000.6.3 & EN50130-4
Operating Temp:
-25oC to +70oC
Relative Humidity: up to 95% RH
non-condensing
Dimensions:
14H x 148W x 87D mm
Weight: 100 g
Relay contacts:
2 A @30VDC
Product Code
555.800.069
TSM800 PCB
VIO800 MX Vesda Interface
The VIO800 MX Vesda Interface
will enable all versions of the
popular LaserPLUS Detectors
and 7 relay versions of the Laser
SCANNER Detectors to be interfaced
directly to the MXDigital detection
loops. 3 configurable inputs and 1
output signal are available from the
interface enabling it to integrate fully
with the Vesda detector.
02/17
This module is designed to fit in bay
one of the Vesda Detectors.
Fire Catalogue
Product Code
516.018.014
VIO800 MX VESDA Interface
Chapter 2 Page 50
Chapter 2 - MZX Technology
Quad Input/Output Module (QIO850)
The Quad Input/Output Module
connects directly to the MZX Digital
loop and provides four change over
relay outputs, four High Voltage
Relay (HVR) outputs and four
monitored inputs. It is loop powered
and therefore does not need a power
supply, however it can monitor the
presence of a local 24Vdc or 48Vdc
power supply.
Features
• Four change over relay outputs and four monitored inputs each individually programmable for a wide range of applications
• Four HVR drivers. No need for a local power supply to switch 240Vac mains
• Inputs can monitor normally open or normally closed contacts
• The relay contacts are monitored and users are alerted to “output stuck” conditions
• Uses 2 addresses when
configured for 2 inputs with 2 associated outputs
• Uses 4 addresses when
configured for 4 inputs with 4 associated outputs
• Uses 8 addresses when
configured for 4 inputs and 4 independent outputs
• Compact DIN rail mount design saves space
• Lower installation costs than
individual modules
• Built-in line isolators improve fault tolerance
• Status LED’s provide rapid
diagnostics
• Two way IR communication to the 850EMT programming tool speeds up commissioning
• Monitors input power supply for improved system integrity
• VdS and CPD approved to EN54-
17, EN54-18 and EN54-13
Product Code
555.800.071
Quad Input/Output Module
(QIO850)
• Uses 4 addresses when
configured for 4 outputs
• Compact DIN rail mount design saves space
• Lower installation costs than
individual modules
• Built-in line isolators improve fault tolerance
• Status LED’s provide rapid
diagnostics
• Two way IR communication to the 850EMT programming tool speeds up commissioning
• Monitors input power supply for improved system integrity
• VdS and CPD approved to EN54-
17, EN54-18 and EN54-13
­ roduct Code
P
555.800.070
Quad Monitored Output Module
(QMO850)
Quad Monitored Output Module (QMO850)
The Quad Monitored Output Module
connects directly to the MZX Digital
loop and requires a 24Vdc or 48Vdc
power supply. It provides four
monitored outputs for connection to
conventional sounder circuits or
auxiliary relays.
Features
• Four polarity reversal monitored
outputs
• Class A or Class B wiring for
versatility
• Uses 2 addresses when
configured for 2 outputs
Quad Relay Output Module (QRM850)
The Quad Relay Output Module
connects directly to the MZX Digital
loop and provides four change over
relay outputs or four High Voltage
Relay (HVR) outputs. It is loop
powered and therefore does not
need a power supply, however it
can monitor the presence of a local
24Vdc or 48Vdc power supply.
Features
• Four change over relay outputs each individually programmable for a wide range of applications
• Four HVR drivers. No need for a local power supply to switch 240Vac mains
• The relay contacts are monitored and users are alerted to “output stuck” conditions
• Uses 2 addresses when
configured for 2 outputs
• Uses 4 addresses when
configured for 4 outputs
• Compact DIN rail mount design saves space
• Lower installation costs than
individual modules
• Built-in line isolators improve fault tolerance
• Status LED’s provide rapid
diagnostics
• Two way IR communication to the 850EMT programming tool speeds up commissioning
• Monitors input power supply for improved system integrity
• VdS and CPD approved to EN54-
17, EN54-18 and EN54-13
Product Code
555.800.073
Quad Relay Output Module
(QRM850)
IP66 Housing for Quad I/O Modules
A polystyrene/polycarbonate IP66
rated housing prefitted with a din
rail for mounting either 1 x Quad
Input/Output Module (QIO850), or
1 x Quad Monitored Output Module
(QMO850) or 1 x Quad Relay Output
Module (QRM850) complete with a
transparent front cover.
Features
• Ingress Protection rating of IP66
• Polystyrene/polycarbonate
construction hence will not
corrode
Chapter 2 Page 51
• Supplied prefitted with a din rail to
enable the Quad Modules to snap
fit into the housing
• Transparent front cover allows the
status LEDS of the Quad Module
to be viewed without removing the
cover and also allows two way IR
communication with the 850EMT
programming tool
• Supplied with M20/M25/M32/M40
cable entry knockouts
Fire Catalogue
Product Code
557.201.410
IP66 Housing for Quad I/O Modules
02/17
Chapter 2 - MZX Technology
Technical Specification
QIO850
System
Compatability
QMO850
QRM850
HOUSING FOR QUAD
I/O MODULES
Any MZX Fire Alarm Controller configured with MZX Consys Version 20.0
or later
Mechanical
Dimensions (H x W
x D)
103 x 134 x 49 mm
170 x 254 x 90 mm
Material
Grey Polystrene
similar to RAL
7035 (Base).
Transparent
Polycarbonate
(Cover).
Cable Entry
Knockouts
24 x M20, 4 x M25/32,
4 x M32/40
Electrical
Voltage
Current
40VDC
1.1 mA (standby),
5.9 mA (alarm)
2.1 mA (standby),
6.7 mA (alarm)
Wire Size
Output Circuit
(Relay Contacts)
Auxiliary Voltage
Input
1.1 mA (standby),
5.9 mA (alarm)
0.5mm² to 2.5mm²
Nominal switching capacity 2A at 30VDC (resistive load),
Maximum switching power 60W, 125VA (resistive load)
Auxiliary voltage
24VDC to 55VDC
(threshold voltage for
auxiliary voltage fault
indication: 18VDC +/1VDC). Auxiliary voltage 48VDC to 55VDC
(threshold voltage
for auxiliary voltage
indication 36VDC +/2VDC).
Auxiliary voltage
24VDC to 55VDC
(threshold voltage for
auxiliary voltage fault
indication: 18VDC
+/- 1.5VDC). Auxiliary
voltage 48VDC to
55VDC (threshold
voltage for auxiliary
voltage indication:
36VDC +/- 2.5VDC).
Wiring monitoring
(threshold resistance
for auxiliary voltage
fault indication 50
ohms +/- 5 ohms).
Auxiliary voltage
24VDC to 55VDC
(threshold voltage for
auxiliary voltage fault
indication: 18VDC +/1VDC). Auxiliary voltage 48VDC to 55VDC
(threshold voltage for
auxiliary voltage indication 36VDC +/- 2VDC).
Environmental
Operating
Temperature
-25oC to +7oC
Storage
Temperature
40oC to +80oC
Operating Humidity
Up to 95% Non
condensing
Ingress Protection
Electromagnetic
Compatability
Approvals
02/17
-25oC to +40oC
100% at 25oC
(SHORT TERM)
IP66
EN50130-4 for immunity
EN61000-6-3 for emissions
EN54-17, EN54-18 and EN54-13
Fire Catalogue
Chapter 2 Page 52
Chapter 2 - MZX Technology
Features
•Connects directly to the MX Digital Loop.
•Reduced installation time and cost since no external
module is required.
•Easier Programming and Commissioning – predefined in
MXconsys.
•EN60950:2000 Compliant PSU.
•EN50130-4:1996 & EN50081-1:1992 Compliant PSU.
•Mains and Fault LED Indicator on front cover.
•Output fuse protected.
•24VDC Voltage Door Release Relay.
•Specifically designed for the safe actuation of release
mechanisms for doors.
•Satisfies the requirements of BS7273 Part 4 for category
A actuation of Fire Doors.
•Built in line isolator.
•Self monitoring operation.
•Approved to EN54-18 (Input/Output Devices) and EN5417 (Line Isolators).
MZX Compatible 4 Amp 24VDC Addressable Door Holder PSU
The MZX compatible ELM24TSM 4 Amp 24VDC
Addressable Door Control & Power Supply Unit, is designed
to provide monitoring and activation in compliance with the
most stringent local door control standards.
This Door Holder PSU is interfaced to the MZX Panels via
an integral TSM800 Door Control Module which is field
mounted inside the Door Holder PSU and connects to the
MZX Detector Loop.
Technical Specification
Product Code
Input Voltage:
Output Voltage:
Output Current:
Temperature:
Relative Humidity:
IP Rating:
Material:
Dimensions:
558.004.011
Chapter 2 Page 53
230 VAC 50Hz
22 - 30 Vdc
4 Amps Continuous
-10C to + 40C
95% RH
IP41 (excluding rear face)
1.2 mm white powder coated steel
230 mm (W) x 200 mm (H) x 80 mm (D)
Fire Catalogue
ELM24TSM 4 Amp 24VDC Addressable
Door Holder PSU
02/17
Chapter 2 - MZX Technology
Housings
MX Ancillary Housings
A variety of ancillary housings are available to fit the 800 Series MX ancillaries. The standard sized modules are
mechanically compatible with all options. LPCB approvals are with the M520 double gang cover plate or ancillary housings. The M520 double gang cover provides external access for the MX SERVICE TOOL to plug into the ancillary module
which is mounted in the cover. All options allow the ancillary to be programmed and tested when the cover is removed.
M520
M520 Ancillary cover for use with
800 series modules. Will fit onto a
MK style double gang back box.
Product Code
517.035.007
M520 Ancillary Cover
D800
D800 IP55 ancillary housing
140W x 120H x 70 mmD incorporates
window to view module LED
Product Code
557.201.401
D800 IP55 Ancillary Housing
ANC-3 Ancillary Housing
ANC-3 MINERVA ancillary
housing - for use with M800 ancillary
modules (can accommodate up to 3
M800 modules).
340W x 290H x 90 mm D
Product Code
557.180.097.A
ADT Branded
ANC-8 Ancillary Housing
ANC-8 MINERVA ancillary
housing - for use with M800 ancillary
modules, houses 8 modules,
expandable to 16 using the STK8
stacking kit.
440W x 320H x 140 mm D
Product Codes
557.180.096.A
ADT Branded
557.180.095
STK8 stacking kit
DIN Rail Mounting Bracket
DIN Rail mounting bracket enables
any module which can be mounted
to a M520 ancillary cover to be DIN
rail mounted using this bracket.
Clip-on PCB mounting pillars are
included. Will fit standard 35 mm
DIN Rail bracket.
02/17
Product Code
547.004.002
DIN rail mounting bracket
Fire Catalogue
Chapter 2 Page 54
Chapter 2 - MZX Technology
QFB/2
QFB/2 Dry lining flush mount (for
plasterboard etc) MK backbox for
use with 800 Series addressable
ancillaries using 517.035.007 cover.
Product Code
517.035.015
QFB/2 Dry Lining Flush Mount MK
backbox
­
K2214 ALM
K2214 ALM Metal surface mount
MK backbox for use with 800 Series
addressable ancillaries using
517.035.007 cover. Product Code
517.035.011
K2214 ALM Metal Surface Mount MK
backbox
­
K2142
K2142 White plastic surface mount
MK backbox for use with 800
Series addressable ancillaries using
517.035.007 cover.
Product Code
517.035.010
K2142 White Plastic Surface Mount
MK backbox
8621C
8621C Steel flush mount MK
backbox for use with 800 Series
addressable ancillaries using
517.035.007 cover.
­Product Code
517.035.014
8621C Steel Flush Mount MK
backbox
Technical Specification
Product Code
517.035.011
517.035.010
517.035.014
517.035.015
MK Ref
K2214
K2142
8621C
QFB/2
Chapter 2 Page 55
Mounting
Surface
Surface
Flush
Flush/
Dry Lining
Dimensions
146x86x40mm
146x86x34mm
132x72x26mm
146x85x38mm
Knockouts
1x20mm rear/7x20mm sides
One rear (25x35mm)
4x20mm rear/12x20mm sides
2 top & bottom
Earth Screw Material
Yes
Steel
N/A
Plastic
Yes
Steel
N/A
Plastic
Fire Catalogue
02/17
Chapter 2 - MZX Technology
Callpoints
Features
•Integral LED indicator for easy identification of operation
•Surface or flush mounting
•Extensive range of digital addressable callpoints
•Test key facility, speeds maintenance visits
•Hazardous areas models available (See Special Hazards
Section)
•IP67 Waterproof models for external applications
CP Series Callpoints
A comprehensive range of callpoints for use with
addressable systems. All the callpoints are designed to
enable an alarm signal to be given by breaking a glass
element.
This operates a switch and is indicated by an LED indicator.
If required, an optional transparent hinged cover may be
installed to guard against accidental operation.
Technical Specification
(Indoor & Outdoor)
Housing: PC/ABS Operating Temp.: Outdoor-25oC TO +70oC
Indoor-10oC TO +55oC
Relative Humidity: up to 95% RH (non-condensing)
02/17
Fire Catalogue
Chapter 2 Page 56
Chapter 2 - MZX Technology
Callpoints CP820/MCP820M/CP830/MCP830M
73mm
45.5mm
76.53
93
97.5mm
04.5 fixing
holes
(3) places
Earth
continuity
terminal
(internal)
83.8
MCP820 Indoor Addressable Break Glass Callpoint
1 –Short Circuit Isolator Activation (Yellow) and Alarm
Indicator LED (Red) MCP versions only
2 –Test/Release Key Access
MCP830 Weatherproof Break Glass Callpoint - Overall and Fixing Dimensions
1 –Short Circuit Isolator Activation (Yellow) and Alarm Indicator LED (Red)
MCP versions only
2 –Test/Release Key Access
CP820/MCP820M Indoor Callpoint
The CP820 is an indoor addressable
manual callpoint for Fire Panels with
MZX technology. It is designed for
LPCB approvals and is equipped
with a programmable status LED.
The MCP820 offers the same features
plus an integrated line isolator. In
case of a short circuit on the loop,
the line isolator isolates the affected
part of the loop and ensures, that
the parts of the loop, that are not
affected from the failure continue to
work. The MCP820M is an indoor
callpoint for Marine applications. All
manual callpoints provide high speed
communication to the MZX panel of a
manual fire alarm.
Technical Specification
Meets BS5839 Pt.2 and pr EN54
Pt:11
EMC/RFI: EN50130-4/
EN61000-6-3
Operating Temp.: -10°to +55°C
Relative Humidity: up to 95% RH
non-condensing
Dimensions:
93H x 89W x 59.5D
(27.5 mm flush mount)
Weight: 110 g
IP Rating: 24D
Product Codes
514.800.603.T
CP820 Indoor Callpoint
(Thorn Branded)
514.800.603.A
CP820 Indoor Callpoint
(ADT Branded)
514.800.603.Y
CP820 Indoor Callpoint
(TYCO Branded)
514.800.611
MCP820 Indoor Callpoint c/w
Isolator
514.800.609
MCP820M Indoor Callpoint c/w
Isolator
Technical Specification
Meets BS5839 Pt.2 and pr EN54
Pt:11
EMC/RFI: EN50130-4/
ENG61000-6-3
Operating Temp.: -25° to +70°C
Relative Humidity: up to 95% RH
non-condensing
Dimensions:
93H x 97.5W x 73Dmm
Weight: 240g
IP Rating: 67
Product Codes
514.800.604.T
CP830 Outdoor Callpoint
(Thorn Branded)
514.800.604.A
CP830 Outdoor Callpoint
(ADT Branded)
514.800.604.Y
CP830 Outdoor Callpoint
(TYCO Branded)
514.800.612
MCP830 Outdoor Callpoint c/w
Isolator
514.800.610
MCP830M Outdoor Callpoint c/w
Isolator
CP830/MCP830M Outdoor Callpoint
The CP830 is an outdoor addressable
manual callpoint for Fire Panels with
MZX technology. It is designed for
LPCB approvals and is equipped
with a programmable status LED.
The MCP830 offers the same features
plus an integrated line isolator. In
case of a short circuit on the loop,
the line isolator isolates the affected
part of the loop and ensures, that
the parts of the loop, that are not
affected from the failure continue to
work. The MCP830M is an outdoor
callpoint for Marine applications. All
manual callpoints provide high speed
communication to the MZX panel of a
manual fire alarm.
Chapter 2 Page 57
Fire Catalogue
02/17
Chapter 2 - MZX Technology
Callpoint Ancillaries
Product Codes
90-107
Red M141 spacer for red CP200/800
KAC callpoints
515.001.045
Test key for all MCP and CP style callpoints
515.001.128
Callpoint hinged cover for use with
MCP callpoints models
(Colour -Clear)
515.001.026
Black callpoint bezel for CP200/800
models.
Ancillaries - Back Boxes
Product Codes
515.001.021
Standard Red surface mounting back
box for MCP & CP indoor callpoints
Unless stated the indoor callpoints are supplied
as flush mount units. The range is approved for
use with the standard backbox. However, SR2-T
backboxes are also available.
10-115
SR2-T Optional Back Box (2 terminals)
Callpoint Spare Glasses - Current
Product Codes
515.001.119
EN54 Part 11 Spare Glass for MCP
and CP series Callpoints (Pack of 5)
515.001.127
Deformable operating unit “glass” for
use in place of glasses, for kitchens
or other areas where glass is not
acceptable. For MCP callpoints only.
515.001.025
CP200/500/900 Glasses, clear English
text on white background. No logo
(Pack of 5).
02/17
Fire Catalogue
Chapter 2 Page 58
Chapter 2 - MZX Technology
Features
•Prevents accidental operation of callpoints
•Strong polycarbonate construction
•Break Seal provided. (Use is optional)
UNIVERSAL STOPPER
The UNIVERSAL STOPPER provides protection from malicious
or accidental activation of manual callpoints. Available for flush
or surface mounted callpoints the UNIVERSAL STOPPER
is also available with optional high pitch sounder which is
activated when the lid is lifted.
WARNING:- Break Seals should only to be fitted by agreement
with relevant fire authorities.
The UNIVERSAL STOPPER is suitable for all callpoints up to
100 mm square.
A Break Seal is supplied with all models, to provide extra
protection if required.
Flush Surface
STI-13110FR
UNIVERSAL STOPPER
With Sounder Weatherproof
P
P
P
STI-13020FR
UNIVERSAL STOPPER
P
P
P
P
37 mm
96 dB
STI-1100
STOPPER II
515.001.034
P
515.001.035
P
P
P
P
50 mm
96 dB
P
STI-1230
STOPPER II
P
50 mm
P
P
P
P
50 mm
Flush Kit
Surface Kit
UNIVERSAL STOPPER
STI-13010FR
STI-13110FR
UNIVERSAL STOPPER with Sounder
STI-13020FR
STI-13120FR
UNIVERSAL STOPPER
Max. Call point size
Max. Call point depth
IPO36 Break Seal Kit
STI/BS - available in
packs of 10.
STOPPER II Surface Red
Weather Stopper II
Surf- Red
96 dB
STI-1130
STOPPER II
STI-3150
WEATHER STOPPER II
P
96 dB
STI-13120FR
UNIVERSAL STOPPER
STI-1250
WEATHER STOPPER II
515.001.033
37 mm
STI-13010FR
UNIVERSAL STOPPER
STI-1200
STOPPER II
Product Codes
STOPPER ll
100 x 100 mm
160 x 160 mm
57.5
120
(add 37 mm surface)
Chapter 2 Page 59
Fire Catalogue
03/17
Chapter 2 - MZX Technology
Features
•Strong polycarbonate construction
•Tamper resistant
STOPPER II
The STOPPER II is constructed from tough UV stabilised
polycarbonate. Physically larger than the UNIVERSAL
STOPPER the STOPPER II extends the number of products
to which these tough multi-purpose covers can protect.
STOPPER II can also be fitted with an integral battery
powered sounder which activates if the cover is lifted.
The STOPPER II is suitable for callpoints up to 160 mm
square.
It consists of a strong tamper-proof clear polycarbonate
cover and frame that fits easily over such products as break
glass callpoints.
Product Code
515.001.034
STOPPER II Surface - Red
Features
•Strong polycarbonate construction
•Provides environmental protection
•Ideal for indoor/outdoor applications
UNIVERSAL STOPPER & WEATHER STOPPER II
The UNIVERSAL STOPPER and WEATHER STOPPER II
extends the life of weather exposed devices, such as
break glass callpoints, by offering protection against harsh
conditions and environments. Experience has shown that
this protective cover can extend the life of products installed
in saline atmospheres, such as oil rigs and ship decks.
While offering environmental protection the UNIVERSAL
STOPPER and WEATHER STOPPER II are constructed from
tough UV stabilised polycarbonate which will also guard
against tampering, vandalism or accidental operation of
devices such as emergency switches.
Product Codes
STI-13110FR
515.001.035
03/17
Fire Catalogue
UNIVERSAL STOPPER Surface Red
WEATHER STOPPER II Red
Chapter 2 Page 60
Chapter 2 - MZX Technology
STOPPER II Dimensions
76 mm
81 mm
70 mm
102 mm
50 mm
127 mm
41 mm
140 mm
19 mm
STI-3100 spacer adds 50 mm
depth for surface mounted
division
140 mm
Depth Chart
Cover
Cover
140 mm
165 mm
Spacer
166 mm
81 mm
81 mm
190 mm
Cover
76 mm
81 mm
127 mm
216 mm
51 mm
Spacer
216 mm
51 mm Spacer
51 mm
140 mm
Side View without sounder
Side View with sounder
End View
Devices to be protected
Removable plastic insert
50 mm conduit spacer for
surface mounting
Optional sounder
Cover
Rawl plug 4
provided
Screws 4
provided
Optional backplate for
irregular surfaces
Mounting frame
UNIVERSAL STOPPER Dimensions
64 mm
Without
label hood
162 mm
138 mm
138 mm
64 mm
Without
label hood
162 mm
138 mm
116 mm
Locking Tab
35 mm
Flush side view
Chapter 2 Page 61
Fire Catalogue
Surface side view
02/17
Chapter 2 - MZX Technology
Smoke Beam/CCTV Guard
The Smoke Beam/CCTV Guard is
manufactured from tough coated
steel rod and is designed to protect
projected beam detectors or
CCTV cameras from vandalism or
accidental damage.
Technical Specification
Dimensions:
260H x 200W x 321D mm
Product Code
516.015.009
STI9625 Smoke beam/CCTV guard
Suitable for use with System Sensor,
Hochiki and Fireray 2000 detectors.
Keybox
This tough polycarbonate breakglass
keybox is available to protect
emergency keys.
Product Code
515.001.043
STI6720 Keybox with printed glass
Sounders & Beacons
Features
•Wide range of both bells and electronic sounders
•High sound output characteristics
•Low current consumption
•Clean lines, modern styling
•Easy to install, low installation costs
•Weatherproof units for outdoor use
•Distinct sounds are available
•Motorised and Solenoid bells available
•Wide range of voltages available
• Visual alarm approved to EN54-23
• Audible alarm approved to EN54-3
Sounders
A range of sounders to meet a wide variety of alarm
applications where loud, penetrating and distinctive
warnings must be given to alert people of fire situations.
In addition, multi-tone electronic sounders can give a variety
of sounds to signal other conditions e.g.“extinguishing gas
release imminent,” etc.
Note: For I.S. & Flameproof sounders, please see the special hazards section in Chapter 10.
02/17
Fire Catalogue
Chapter 2 Page 62
Chapter 2 - MZX Technology
Loop Powered Sounders & Beacons
Features
•High output programmable sounder base and sounder
beacon base
•One point of installation for detector, isolator, sounder &
beacon
•Loop powered from the MX Technology® Digital Loop
•High brightness Multi-LED Beacon
•Software programmable
•15 Tones and 2 Flash Rates
•Integral line isolator
•RSM (Reflective Sound Monitoring)
•Can be used as a standalone device using the sounder
blanking cap
•Optional surface mount plastic conduit adaptor
• Visual alarm approved to EN54-23 open category
• Audible alarm approved to EN54-3
Sounder/Beacon and Sounder Bases
One Point of Installation – Unique Solution with Huge
Savings
Combining a detector base, sounder, beacon and line
isolator in one low cost unit will result in a dramatic
reduction in the final installation cost. Typically 40% to
55% of the installation costs per point can be saved. This
presents an exciting opportunity for sellers. This is achieved
without the need for specialist high cost detector heads as
standard 830 series MZX detectors are used.
Unique
When used with the 3oTec triple multi-sensor the AV base
can provide a completely unique solution combining fire
detector, toxic gas detector, isolator, sounder and beacon
into a single very cost effective single point of installation.
Reflective Sound Monitoring (RSM) – Patented* Solution
significantly reduces Risk
Reflective Sound Monitoring is employed to monitor the
audio output of the LPSB3000 and LPBS300 by listening to
the output and reporting any sounders that are not working.
RSM is a Tyco patented* technology and was successfully
introduced with the Loop powered Symphoni sounders.
It is particularly beneficial during regular weekly sounder
tests where users can be satisfied that all their sounders are
working, even if the building is not fully occupied at the time
of the test. Failure of the beacon would also generate a fault
at the control panel.
EN54 Compliant
The addressable loop powered sounder base meets the
requirements of EN54 part 3 whilst the loop powered
addressable sounder with beacon base is also approved to
EN54 part 23 as an open category device.
Chapter 2 Page 63
Loop Power Capacity
The advanced 3000 series sounders and beacons are
independently addressed and are therefore separately
controllable from the MZX Digital loop. The maximum
number that can be driven from a single loop is dependant
on the number of addresses available, the volume selected
and the flash rate of the beacon. MXDesigner version
5.0 should be used to accurately determine loop loading
and battery size. Typically, at full volume of 90dBA, 50 x
LPBS3000 sounders or 30 x LPAV3000 sounder beacons at
0.5Hz flash rate can be driven by a single 1Km loop. That
gives a typical maximum of 240 sounder beacons at full
volume from a single 8 loop panel.
Built-in Isolation
As the line lsolator is now integral to the device the need for
separate line isolation devices is reduced.
Tones
15 Tones are available from the sounder, which include
tones compatible with the LP Symphoni range, 802SB
sounder base and the LPBB520 (loop powered Besson
Banshee). 4 sound levels 60dB to 90dB (±3dB) and 2 flash
rates 1/2Hz & 1Hz are available.
MXConsys
The AV base range of devices are fully supported by Consys
Version 14 and later, the point input dialog box provides an
easy method for setting the Tones, Volume and Flash rate
of the device. The only operation required at the device is to
set the address using the 850EMT device programmer.
Fire Catalogue
02/17
Chapter 2 - MZX Technology
Technical Specification
System Environment
Temp- Operating
Temp - Storage
Dimensions Weight:
Materials EMC
02/17
For use with MX/ZX fire alarm
controllers
Up to 95% RH (non condensing)
IP Rating 21 C EN60529
-20°C to +70°C
-25°C to +70°C
102 mm dia x 42 mm high
LPSB3000 0.160 kg
LPBS3000 Loop Powered BeaconSounder Base 0.170 Kg
Housing ABS FR & Polycarbonate
The range complies with the
following:
Product family standard EN50130-4
in respect of conducted
disturbances, radiated immunity,
electrostatic discharge, fast
transients and slow high energy
EN61000-6-3 for emissions
Product Codes
516.800.957
516.800.969
516.800.959
557.001.040 LPSB3000 Sounder only L/P addressable
base
LPBS3000 Loop Powered BeaconSounder Base
DAB3-4 Mounting flange – type B for
conduit (supplied in packs of 10)
Mk 2 Sounder Cap pack of 5
Note: Detectors supplied separately
Fire Catalogue
Chapter 2 Page 64
Chapter 2 - MX Technology
Features
•Loop Powered – Reduced installation costs
•High Output/Low consumption – Lower lifetime costs
•Indoor and Outdoor models – Same sounder tones in all
areas
•Sounder/LED Beacon Version
•16 Tones and 2 Flash rates – Suits individual
requirements
•Reflective Sound Monitoring RSM - Reassurance that ALL
sounders are working
•Integral Line Isolator – Saves cost and installation time
• Visual alarm approved to EN54-23 open category
• Audible alarm approved to EN54-3
Loop Powered Symphoni Sounders and Sounder Beacons
Built-in Isolation
As the line lsolator is now integral to the device the need for
separate line isolation devices is reduced.
Models Available
The Sounder only models are available with a red or white
housing suitable for indoor use and an IP65 rated red
housing for outdoor applications.
The Audio / Visual models, which incorporate a highly
efficient white LED beacon, are also available with a red or
white housing for indoor use and an IP65 rated red housing
for outdoor applications.
Reflective Sound Monitoring
The LP Symphoni utilising Reflective Sound Monitoring
(RSM) employs a transducer to actively monitor the units’
sound output during the weekly sounder test and will report
back to the control panel if it fails to detect the sounder
operating when it has been commanded to, this ensures
that the LP Symphoni range of sounders will in the unlikely
event of a fault, display it immediately on the fire controller
and is therefore not dependant upon the staff within a
building reporting a sounder failure.
Technical Specification
Operating temp:
Indoor devices -10°C to +55°C
Outdoor devices -20°C to +70°C
IP rating:
Indoor devices IP21C
Outdoor devices IP65
EMC:
Product family standard EN50130-4 in respect of
Conducted Disturbances, Radiated Immunity,
Electrostatic Discharge, Fast Transients and Slow High
Energy
EN61000-6-3 for Emissions
Chapter 2 Page 65
Tones
16 Tones are available from the sounder, which include
tones compatible with the 802SB sounder base and the
LPBB520 (loop powered Besson Banshee). Dutch slow
whoop and the DIN 1Hz sweep are included.Two sound
levels 103dB & 90dB (±3dB).
EN54 Compliant
The addressable loop powered sounder meets the
requirements of EN54 part 3 whilst the loop powered
addressable sounder with beacon is also approved to EN54
part 23 as an open category device.
Product Codes
516.800.960 516.800.961 516.800.962 516.800.966 516.800.967 516.800.968 Fire Catalogue
LPSY800-R L/P Symphoni addressable sounder red body indoor use
LPSY800-R L/P Symphoni addressable sounder whitebody indoor use
LPSY865 Symphoni IP65 addressable sounder IP65 red body outdoor use
LPBS800-R Open class Symphoni addressable beacon sounder red body white flash indoor use
LPBS800-W Open class Symphoni addressable beacon sounder white body white flash indoor use
LPBS865 Open class Symphoni addressable beacon sounder IP65 red body white flash outdoor use
11/16
Chapter 2 - MX Technology
Bells
Features
•CE marked
•Low current 6” bell (ONLY 11 mA)
•Low cost
•Extra high 95dBA/m
•Slim profile (53 mm)
•Fully suppressed and polarised
•Quick and easy to install
•LPCB approved to EN54 Pt 3
6” & 8” Motorised Bells
Product Codes
Model
MBF-6EV
MBF-8EV
MBA 8EV
Rated Voltage 24 V d.c. 24 V d.c. 24V d.c.
Rated Current 11 mA 17 mA 18 mA
Sound output 90-95dBA
90-97dBA
91-97dBA
Operating Temp -12 to +50°C -10 to +50°C
Colour Red
Weight 410 g 640 g 1100 g with back box
576.501.039.A
576.501.039.T 576.501.040.A
576.501.044.A
576.501.044.T
576.501.045
11/16
MBF-6EV ADT Branded
MBF-6EV Thorn Branded
MBF-8EV ADT Branded
MBA-8EV ADT Branded
MBA-8EV Thorn Branded
BBX4 (2) W/P Backbox for MBA-8 Bell
Fire Catalogue
Chapter 2 Page 66
Chapter 2 - MZX Technology
Features
•Weatherproof Option
•Flexible Mounting Option
•Attractive Design
Electronic Solenoid Bell
Unique patented alarm bell with miniature solenoid and
integrated electronic control. No backbox required for
surface wiring.
Technical Specification
Product Codes
Dimensions:
Voltage:
Typical Current: Typ. Sound Output:
20-100
20-101
20-111
6” diameter
18-30 Vdc
30 mA @ 94dB (A) @ 1 m
6” 24 Vdc Electronic bell, weatherproof IP33C - Wormald Branded
6” 24 Vdc Electronic bell - red IP21C - Wormald Branded
6” 24 Vdc Electronic bell - white IP21C
Marine Approved Products
576.501.407 576.501.408
MED 6” 24 Vdc Electronic bell,
weatherproof - red IP33C
MED 6” 24 Vdc Electronic bell - red IP21C
Features
•Low Current Consumption
•Suppressed and Polarised
•Sturdy Construction
CF Motorised Bell
The CF Motorised Bell is low current, fully suppressed and
polarised.
Technical Specification
Product Code
Dimensions:
6” Diameter Colour:Red
Output Voltage: 20-28 Vdc
Typical Current: 25 mA @ 24Vdc
Typical Sound Output:
95dB (A) @ 1m
Marine Approved Product
Chapter 2 Page 67
576.501.405 Fire Catalogue
MED 6” Red 24Vdc Motorised bell, “Fire”
text with Thorn Branding
02/17
Chapter 2 - MZX Technology
Electronic Sounders
Features
•Modern aesthetic design
•32 Selectable tones
•3 Volume settings
•Push and twist mount
•Shallow and deep bases
•Available in red or white
•Low current consumption
•2 Stage alarm available
•Independently switched sounder or beacon
•Xenon beacon with the Excel Lite
Banshee Excel Sounders
Banshee Excel Lite Sounder Beacon
The Banshee Excel sounder replaces the Banshee Multi
Tone range of Sounders. It uses the same technically
superior rocking arm transducer to reproduce the familiar
32 tones of the previous Banshee and Bedlam ranges.
The new Banshee Excel adds the Banshee Excel Lite
Sounder Beacon to its range using a high output xenon
with the familiar sounder. The Banshee Excel Lite can be
used as a multi stage device by switching the beacon and
the sounder independently using a third wire.
Technical Specification
Product Codes
Approvals:
VdS approved to EN54-3
Tones available:
32
Operating voltage:
9-30 Vdc
Tone current consumption: See Tone Table in Chapter 11
Flash current consumption:40 mA
Operating temperature range (Deg C): -40 to +70
Volume control via DIL switch: Maximum, Medium (-10dBA),
Low (-20dBA)
Flash rate per second: 1
Ingress Protection: IP45 or IP66 Termination:
Screw terminals for 028mm2 to 2.5 mm2 wire conductor
576.501.060
576.501.061
576.501.062
576.501.063 Banshee Excel sounder, red, IP45
(replaces 576.501.005.A & 576.501.005.T)
Banshee Excel sounder, white, IP45
(replaces 576.501.009 & 576.501.025.A)
Banshee Excel sounder, red, IP66
(replaces 576.501.016.A & 576.501.016.T)
Banshee Excel Lite, red sounder, red
xenon beacon, IP45
Accessories
The combined mounting bracket
for the Besson Multi-tone Banshee
and Xenon Beacon allows quick
and neat installation of combined
sounders and beacons. The bracket
allows the following electronic
sounders to be mounted with the
range of 1W Xenon Beacons:
• Besson Banshee
• MINERVA FIRECRYER voice
enhanced sounder
02/17
The bracket can be used with any of
the 24Vd.c 1W Xenon beacons in
red, clear, amber or blue (Part no.’s
LPB24-C-T/LPB24-B-T/LPB24-A-T
& LPB24-R-T)
Fire Catalogue
Product Code
576.501.047
Banshee/Xenon bracket
Chapter 2 Page 68
Chapter 2 - MZX Technology
Yodalarms
This versatile range of sounders
are ideally suited for fire, safety and
security hazard warning.
Approvals
EN54-3:2001+A1:2002 + A2 :2006
Vds 2504 (12/96), Vds 2203 (03/01),
Vds 2344 (12/05), Cert No. G28702
Marine Equipment Directive
MED Module B BSI/MED/A.
1/3.53/590299, Module D BSI/MED/
PC/590302
Technical Specification
Dimensions:
YO3:
89H x 89W x 85D mm
YO5:
134H x 134W x 128D mm
YO8:
216H x 216W x 153D mm
Product Codes
YA30/D/RF/WR
Sounder YA30 100 dB 24 VDC IP65
YA50/D/RF/WR
Sounder YA50 110dB 24 VDC IP65
YA80/D/RF/WR
Sounder YA80 115dB 24 VDC IP65
24Vdc Symphoni Sounder
The 24Vdc Symphoni Sounder is a
general purpose internal sounder,
available either as a very high
output sounder for noisy areas, or
a high output low current sounder
for applications where power is
limited. Both versions share the
same horn and backbox which has
double cable entries for ease of
installation.
The low power version has 3
selectable tones which may be
employed for one, two or three stage
alarm applications. The high output
version has 32 selectable tones and
retains full tone compatibility with the
Roshni, Squashni and Askari product
ranges.
Product Codes
576.501.200
SY/R Low Power Red Symphoni
Sounder (3 tone)
576.501.201
SY/W Low Power White Symphoni
Sounder (3 tone)
576.501.202
SYHO/R High Output Red Symphoni
Sounder (32 tone)
576.501.203
SYHO/W High Output White
Symphoni Sounder (32 tone)
Technical Specification
Model
Operation
Operating Voltage Range
Sound Output @ 1m
Volume Control
Current Consumption
Tones
Synchronisation
Frequency Stability
Operating Temperature
Line Monitoring Method
Construction
Ingress Protection
Weight
Symphoni High Output
2 Hours Continuous
9-28 Vdc
Up to 120dB(A)
240 mA +/- 20mA on Tone 3
1 to 32 Synchronised Start
+/- 0.15%
-25 °C to +55°C
Polarised Input
ABS Plastic Case
IP21C
0.58 Kg
Symphoni (Low Power)
Continuous
12-30 Vdc
100dB(A) +/- 2dB(A) @24Vd. c.
Down to 80dB approx.
5mA +/- 1 mA at all volumes
Alternating 990Hz/[email protected]
Continuous 990Hz
Intermittent 990Hz, On/[email protected]
Synchronised Start
+/- 0.5%
-25°C to +70°C
Polarised Input
ABS Plastic Case
IP21C
0.212 Kg
Roshni
A flexible alarm sounder for Fire and
Security applications complete with
volume control and dil switch to
provide 32 tones.
Low profile Roshni with Deep base
offers IP65 protection. All Roshni
sounders have synchronised start
for self synchronisation without third
wire.
Chapter 2 Page 69
Technical Specification
Dimensions:
93 Dia x
105D mm
(Deep base)
Colour:
Red or white
Output Voltage:
9-28 Vdc
Typical Current:
16 mA @ 24 Vdc Typ. Sound Output: 102dB @ 1m Fire Catalogue
Product Codes
ROSHRDSR
ROSHNI Sounder c/w deep base red
576.501.220
ROSHNI Sounder c/w shallow base
- red
576.501.221
ROSHNI Sounder c/w shallow base
- white
576.501.222
ROSHNI/Flashni Deep Base - Red
576.501.223
ROSHNI/Flashni Deep Base - White
02/17
Chapter 2 - MZX Technology
Features
•Single Message or Multiple Message using the same
sounder
•Multi Message facilitates multi evacuation strategies
•Clear and unambiguous alarm messages
•Voice Alarm Messages provoke an immediate response
•Sound Output – Up to 100db(A) (Fire-Cryer® Plus),
90db(A) (Mini Fire-Cryer® Plus), 110db(A) (Midi FireCryer® Plus)
•Optional integral Red Strobe
•Low current consumption – average 20 mA
•No special wiring easily retro fitted
•Fully synchronised over multi zones
•Deep base version available to IP66
•Ultra slim base sounder to fit industry standard detectors
•Suitable for ceiling or wall mounting (Mini Fire-Cryer®
Plus)
•Optional front plate for stand alone use (Mini Fire-Cryer®
Plus)
•Voice Message Controller makes manual message
switching easy
Fire-Cryer Plus® - Voice Enhanced Sounders
The Fire-Cryer® Plus range of voice sounders are electronic
sounders which are pre-programmed with 9 messages.
Each of the Fire-Cryer® voice sounders can be used as a
single message voice sounder by simply installing them
on to a conventional 24Vdc sounder circuit or by using a
sounder controller on a loop. The choice of message(s)
broadcast can be selected using a DIL switch on the rear of
the sounder. See Table A
A special Extinguishing PCB (576.501.173) used with the
576.501.135 will enable 1st, 2nd Stage, ‘Hold’ and ‘Gas
Released’ messages to be automatically broadcast dependent on the state of the alarm. See Table A1
The Fire-Cryer® Plus offers an excellent service upgrade
opportunity for systems as well as a highly flexible and cost
effective solution to providing a voice evacuation system to
many buildings. The choice of Fire-Cryer® voice sounders
can be selected using Table B
Messages 1 to 7 in Table A can be used in a multi
message installation with the addition of a Multi Message
Switching PCB (576.501.171) or a Voice Message
Controller (576.501.181 or 576.501.182) interfaced between
the fire alarm control panel and the sounder circuits. The
Voice Message Controllers can be supplied with a 2.5A
or 5.25A power supply built in. A Zone Extension PCB
(576.501.172) is available to extend the system to 4 zones
or 8 sounder circuits. See Table C
Chapter 2 Page 70
Fire Catalogue
02/17
Chapter 2 - MZX Technology
Fire-Cryer® Plus Multi Message PCB
Product Code
576.501.171 Fire-Cryer® Plus Multi Message PCB
Fire-Cryer® Plus Zone Extension PCB
Product Code
576.501.172 Fire-Cryer® Plus Zone Extension PCB
Fire-Cryer® Plus Extinguishing PCB
Product Code
576.501.173 Fire-Cryer® Plus Extinguishing PCB
Din Rail Mounting Kit for Fire-Cryer® Plus Extinguishing PCB
Product Code
557.201.303 Din Rail Mounting Kit
IP66 Housing for Fire-Cryer® Plus Extinguishing PCB
Product Code
557.201.410 IP66 Housing
VMC / Multi Message PCB and 2.5A PSU
Product Code
576.501.181
VMC / Multi Message PCB and 2.5A PSU
VMC / Multi Message / Zone Extension PCB and 5.25A PSU
Product Code
576.501.182 02/17
VMC / Multi Message / Zone Extension PCB and 5.25A PSU
Fire Catalogue
Chapter 2 Page 71
Chapter 2 - MZX Technology
Technical Specification
Fire-Cryer® Plus Model
Fire-Cryer® Plus Mini Midi
VDC Operating Voltage 20-28 20-28 20-28
Current mA @ 24VDC Peak/Avg - Sounder only
27/20 27/20
180/100
Current mA @ 24VDC Typical: Sounder with low current strobe
33/26
n/a
n/a
Current mA @ 24VDC Typical: Sounder with high current strobe
52/60
n/a
n/a
Current mA @ 24VDC Low current strobe only
13
n/a
n/a
Current mA @ 24VDC High current strobe only
32
n/a
n/a
Strobe Output Cd (LOW) 2
n/a n/a
Strobe Output Cd (HIGH) 6
n/a n/a
Volume Adjustment from Max. dBA Output to max output -18dBA
82 to 100
72 to 90
101 to 110
Weatherproofing (IP66 requires Deep Base)
IP45 or IP66
n/a
IP44
Housing Material
ABS
ABS Aluminium/ Plastic Base
Temperature Range °C -25 to +70 -10 to +55 -25 to +70
Colour Red or White White Red
Connections Screw TB 1.5mm² Screw TB 1.5mm² Clamp 2.5mm2
Chapter 2 Page 72
Fire Catalogue
02/17
Chapter 2 - MZX Technology
Standard Message Set which consists of 9
pre-programmed messages with tones (See Table A)
When used as a Multi Message sounder DIL Switches 4,
5, 6, 7 and 8 are OFF. When used as a single messa
sounder use the DIL Switch settings in the table below 1
= ON, 0 = OFF
When used as a Multi Message Sounder the Multi Message Switching
PCB (576.501.171) will assign the messages to the following triggers:
Beacon Flashes Y/N
2
2
0
1
CG
CH
LU
CJ
Beacon Flashes Y/N
Two Letter Message Code
1st Stage
2nd Stage
Hold
Gas Released
SW6
SW7
SW8
Fire emergency. Please remain calm and evacuate the building immediately S1A/S1B
This is a fire alert. This is a fire alert. Await further instructions.
Await further instructions.
MA
Standby alert. Close all blinds and move to the middle of the room.
MB
All clear. All clear. No further action required.
MC This is an ADT fire test. No action required.
MD
This is a class change announcement.
ME
Fire detected. Keep calm. Leave the building by the nearest exit.
MF
Ladies and gentlemen – due to unforeseen circumstances we
must ask you to leave the building immediately by the nearest exit
or as directed by members of staff. We have an emergency situation. Please leave the building by the
nearest exit. Members of staff will assist you.
1 0
0
0
0
0
1
0
1
0
1
1
1
0
0
1
1
0
0
1
1
1
1
0
0 0
0 0
0 0
0 0
0 0
0 0
0
1 0
1 0
0
1
0
GAS EXTINGUISHANT MESSAGES (Used with 576.501.135)
Starting Tone (See Table (A2) below)
Table A1
SW5
Message 1 1 AK Y
Message 2 2 AB Y
Message 3 2 MA Y
Message 4 0 AD N
Message 5 0 SP N
Message 6 3 CC N
Message 7 1 AF Y
Message 8 2 AZ Y
Message 9 2 AX Y
Speech Message
SW4
Two Letter Message Code
Starting Tone (See Table (A2) below)
Table A
Y
Y
N
Y
Speech Message
First stage extinguishant release warning.
Second stage extinguishant release warning.
Extinguishant gas release on hold.
Extinguishant released.
Table A2
Tone
0
No tone
1
Banshee LF Fast Sweep. 800Hz to 950Hz swept @ 9hz
2
Banshee LF Fast Sweep. 800Hz to 950Hz swept @ 9hz Pulsed at 1 second ON, 1 second OFF
3
Bell tone, pulsed
02/17
Fire Catalogue
Chapter 2 Page 73
Chapter 2 - MZX Technology
Ordering Fire-Cryer Plus® Voice Sounders
Step 1 - Choose your Fire-Cryer® Sounder
Table B
Type
Body Colour
Beacon
Base
Part Ref.
Wall Mount
Red
Red
Shallow
576.501.131
Deep
576.501.132
None
Shallow
576.501.133
Deep
576.501.134
Red
Shallow
576.501.141
Wall Mount
White
None
Shallow
576.501.142
Wall Mount
Red
Red
Shallow
576.501.135
Wall Mount
Red
None
Deep
576.501.151
Base Mount
White
None
N/A
576.501.161
Step 2 - Choose your Interfaces for Multi Message Systems
Table C
Standard Multi Message Switching PCB
576.501.171
Zone Extension PCB (adds 3 Zones of 2 Sounder Circuits i.e. 6 sounder circuits.
Must be used with 576.501.171)
576.501.172
Extinguishant Interface PCB
576.501.173
Voice Message Controllers & PSUs (All VMC enclosures include a 576.501.171)
576.501.171
576.501.172
PSU
Box Size
Part Ref
Yes
No
2.5A
M2
576.501.181
Yes
Yes
5.25A
M3
576.501.182
Box Sizes
M2 Enclosure 385W x 310H x 90D mm
M3 Enclosure 385W x 520H x 90D mm
Product Codes
576.501.131 576.501.132 576.501.133 576.501.134 576.501.135 576.501.141 576.501.142 576.501.151 576.501.161 576.501.052
576.501.171 576.501.172 576.501.173 557.201.303
557.201.410
576.501.181 576.501.182 576.501.191 Standard Fire-Cryer® Plus, red wall mounted, shallow base, red beacon
Standard Fire-Cryer® Plus, red wall mounted, deep base, red beacon
Standard Fire-Cryer® Plus, red, wall mounted, shallow base
Standard Fire-Cryer® Plus, red, wall mounted, deep base
Standard Fire-Cryer® Plus (for use with 576.501.173 in Gas Extinguishant systems)
Standard Fire-Cryer® Plus, white wall mounted, shallow base, red beacon
Standard Fire-Cryer® Plus, white, wall mounted, shallow base
Midi Fire-Cryer® Plus, c/w back box, red
Mini Fire-Cryer® Plus, base mounted, white, c/w cover
Mini Fire-Cryer® Plus, voice enhanced base sounder cable spacing ring
Fire-Cryer® Plus Multi Message PCB
Fire-Cryer® Plus Zone Extension PCB
Fire-Cryer® Plus Extinguishing PCB
Din Rail Mounting Kit for Fire-Cryer® Plus Extinguishing PCB
IP66 Housing for Fire-Cryer® Plus Extinguishing PCB
Voice Message Controller c/w Multi Message PCB and 2.5 A PSU
Voice Message Controller c/w Multi Message PCB, Zone Extension PCB and 5.25 A PSU
Fire-Cryer® Plus Demo Unit
Please Note:
The beacon in this product should be used for supplementary indication purposes only. In this case the device is not
required to be used as a Visual Alarm Device (VAD) and EN54-23 is not relevant to its classification.
Chapter 2 Page 74
Fire Catalogue
02/17
Chapter 2 - MZX Technology
Beacons
Single Gang Lamp/Buzzer Units
Lamp Buzzer units may be used for
local alarms when high level audible
warnings may not be appropriate.
Available in flush and surface mount
versions to fit standard single gang
backboxes.
Technical Specification
Dimensions:
90H x 90W
x 40D mm
Current Rating:
15 mA at
24 Vdc
nominally
Features
• Low Current
• Flush or Surface Mount
• Hi-Brightness LED
Product Codes
540.011.012
Single gang flush mount LED
(red)/Buzzer Unit labelled ‘Fire
Alarm’
540.011.013
Single gang surface mount LED
(red)/Buzzer Unit labelled ‘Fire
Alarm’ c/w surface backbox.
Solista LED Beacon
Ultra low power requirement 3mA or
6mA at 24Vdc. Long life low profile
design. Protected to IP54, supplied
complete with base.
Product Code
576.501.230
Solista LED Beacon (Red)
Please Note:
The beacon in this product
should be used for
supplementary indication
purposes only. In this case the
device is not required to be
used as a Visual Alarm Device
(VAD) and EN54-23 is not
relevant to its classification.
Easy AVTM Retrofit LED Beacon
This low power LED beacon is
designed to be retrofitted to existing
Banshee electronic sounders. Easy
and fast installation typically 3 min. Low power 6 mA max at 24 Vdc.
High Output LEDs.
02/17
Product Code
576.501.012
Easy AV strobe for Banshee
Sounders
Please Note:
The beacon in this product
should be used for
supplementary indication
purposes only. In this case the
device is not required to be
used as a Visual Alarm Device
(VAD) and EN54-23 is not
relevant to its classification.
Fire Catalogue
Chapter 2 Page 75
Chapter 2 - MZX Technology
Features
• Uses efficient LED technology
•Low profile design (44 mm)
•Twin thread mount
•Low current operation
•Maximum light intensity and dispersion
•Compatible with a wide range of systems
•IP66 rated
•Fresnel Lens
•Polycarbonate and ABS construction
•Choice of coloured lenses: Amber, Blue, Clear or Red
•Suitable for fire alarm VID applications
24 V LED Beacons
A range of cost effective, low profile, high efficiency LED
beacons with a variety of lens colour options. They are
designed for use as visual indicator devices (VID).
Technical Specification
Voltage Power OutputAlarm Current
Flash Rate
Rating Temp. Range
Dimensions (mm)
VdcWatt(s)mAHeight
Diameter
24
1
42
60/min
IP65
-30 to +70°C
51
75
24
2
84
60/min
IP65
-30 to +70°C
51
75
24
3
126
60/min
IP65
-30 to +70°C
51
75
Rated Voltage 12 V dc / 24 V dc
Current Consumption: 80 mA - 12 V dc
30 mA - 24 V dc
Operating Temperature: -10 to 50°C
Product Dimensions
73 mm Diameter x 44 mm Height
Material
Base: ABS
Lens: Acrylic / Polycarbonate
Colour
Base: Black
Lens: Amber, Blue, Clear and Red
Chapter 2 Page 76
Product Codes
LPB24-C-T
LPB24-B-T
LPB24-A-T
LPB24-R-T
24 V DC LED Strobe Clear lens
24 V DC LED Strobe Blue lens
24 V DC LED Strobe Amber lens
24V DC LED Strobe Red lens
Please Note:
The beacon in this product should be used for
supplementary indication purposes only. In this case the
device is not required to be used as a Visual Alarm Device
(VAD) and EN54-23 is not relevant to its classification.
Fire Catalogue
02/17
Chapter 2 - MZX Technology
Features
•Combined strobe & sounder
•Matches Roshni sounders
•Weather Resistant to IP65
Flashni
A combined sounder and beacon which combines the
features of the Roshni electronic sounder with a fully
integrated Xenon beacon.
These sounders are fully compatible with all Roshni tones.
Technical Specification
Product Codes
Dimensions:
Input Voltage:
Typical Current:
Typ. Sound Output:
20-118
93 Dia x 92D mm
(Shallow base)
93 Dia x 121D mm
(Deep base)
18-30Vdc
68 [email protected] Vdc
101dB (A)@1 m
576.501.224
576.501.227
Combined Roshni sounder/strobe
complete with deep base (IP65).
Combined Roshni Sounder/Strobe, Red
Body/Red Lens complete with shallow
base & tone switch.
Combined Roshni Sounder/Strobe, Red
Body/Red Lens, deep base, tone switch &
separate sounder/strobe operation.
Please Note:
The beacon in this product should be used for
supplementary indication purposes only. In this case the
device is not required to be used as a Visual Alarm Device
(VAD) and EN54-23 is not relevant to its classification.
02/17
Fire Catalogue
Chapter 2 Page 77
Chapter 2 - MZX Technology
Software Tools & Accessories
MX Technology Fire controllers are supported by a
comprehensive suite of software programmes which provide
key features to enable fast and accurate configuration and
commissioning of the MX systems.
MXConsys
MXChecker
MXChecker - MXChecker replaces, in software, all
configured MX loop devices on a single panel. It offers a
user the following major functionality:
Connection to a panel directly, or indirectly via the
MXNetwork (in the same way Consys does to perform a
download/upload).
MXConsys, the highly flexible and extremely powerful
programming tool that has been used successfully with
MX systems since day one. Specially designed for MX
it is constantly being extended and refined to meet ever
changing demands. Available for free download from the
Tyco Fire and Security Website but requires a dongle and
license to operate.
Incorporated into MXConsys is MXConsys-Express – An
alternative approach to system configuration that simplifies
the programming effort by automating many of the
processes. Its heart lies in a number of pre-defined
templates that have been expertly designed to match a
selection of building types. The demands on users in terms
of experience and training are considerably reduced.
MXDesigner
MXDesigner is a sophisticated engineering design tool that
not only ensures system parameters and design rules are
obeyed but are key to the ordering and documentation
processes. Battery calculations, loop loading calculations,
remote bus parameters, system schematics and parts lists
are all included. The extensive use of graphics and ‘drag
and drop’ techniques makes the system easy and quick to
use. In addition, a design module for the intrinsically safe
MXDigital detectors and associated system 800 components
is included. Available for free download from the Tyco Fire
and Security Website.
MXFlow
MXFlow - If you have ever been involved in the configuration
process for a complex ‘cause and effect’ programme, you
will appreciate the benefits of an automated method of
documenting your work. MXFlow does just that; it takes your
MXConsys ‘event action’ and transcribes it into a graphical
format that is comprehensive and easy to follow. It can be
a valuable commissioning tool that saves time and effort
as well as an easily understood form of documentation for
future service use.
Available for free download from the Tyco Fire and Security
Website to authorised personnel.
Provides the input status of each and every device
configured on the Loops, e.g. make a Sounder go ’No
Response’, a detector appear active, etc.
The ability to display the General Status of each and every
Point configured on the Loops, e.g. indicate a Sounder is
Isolated, a Callpoint is Disarmed, a Detector is Resetting,
etc. The ability to display the Output Status of each and
every Point configured on the Loops, e.g. indicate a
Sounder is being driven to P1, a Relay Module is not being
driven, etc.
MXLogger
MXLogger – MXLogger enables the engineer to selectively
monitor any device or devices on the addressable loops.
The returned values are displayed on a PC screen and
can be saved to a file for later analysis. Available for free
download from the Tyco Fire and Security Website.
MXRemote
MXRemote - Remote communications software provides a
fast and efficient means of diagnosis without anyone having
to leave the office. In situations where access to a site may
be difficult or where an attending technician requires high
level assistance then MXRemote is the tool for the job. Using
modems, MXRemote can link to the MXDigital fire system
via PSTN or IP and once connected, becomes an integral
part of the fire system, acting as a fully functional repeater.
All system functions are then available to the MXRemote
operator. Available for free download from the Tyco Fire
and Security Website but requires a dongle and license to
operate.
MXService Tool
The TYCO MXService tool is a powerful and flexible tool for
assistance in the installation, commissioning, diagnostics
and service of Tyco MX detection systems. The MXService
tool allows all MX addressable devices to be interrogated,
tested and programmed. Suitable for desktop or single
handed operation the MXService tool is battery operated
using standard rechargeable batteries.
MXLoop Tester
The MXLoop Tester can test, commission and fault-find
a loop of up to 250 MX analogue addressable detectors/
devices, without a fire panel. A laptop is generally used for
operation & display, but a “One Person Installation Mode” is
automatically enabled on power up.
Identifies all devices on the loop, determining addresses
and types. Over-addressed (>250), unknown device types,
and, generally, duplicate addressed devices are recognised.
Monitors analogue values of all detectors/modules on the
loop to determine device status: normal/alarm/fault/dirty etc.
Chapter 2 Page 78
Fire Catalogue
02/17
Chapter 2 - MZX Technology
Features
•MZX Product Line Overview.
•Key Terms & Conditions.
•Key Functions & Features.
•System Display and Controls.
•Set Time and Date.
•Enter Pass Codes.
•Customer Operator Access Levels.
•Accept Fire Alarm Events.
•Accept Incoming Events.
•Walk Test.
•Isolate Detectors.
•Isolate Field Devices.
•View Status of a Loop Device.
•View Event Log.
•Interpret System Faults.
•Carry out Routine Testing.
MZX Interactive Training CD
An Operator Training CD which contains an interactive
training programme that provides information on the MZX
Fire Detection System.
Product Code
TCD-1
02/17
Fire Catalogue
MZX Interactive Training CD
Chapter 2 Page 79
Chapter 2 - MZX Technology
Features
•Programs the system across multiple sub-panels
•Downloads to the system from one point
•Provides Firmware download as well as configuration
download
•Dongle protected
•Provides full project configuration printouts. Includes MX
consys express
MXConsys
MXConsys is a powerful Windows programming tool which
provides full system programming functions and project
configuration and issue control. MXConsys is used on
MINERVA MX, MX2,T2000 & MZX panels.
It also supports automatic data transfer to MXGraph &
TXG graphical mimic and alarm management systems.
MXConsys is available under document control from
authorised personnel in the Tyco businesses.
Product Codes
557.203.033
557.202.118
MXConsys Dongle and license (USB)
MXConsys Download lead
Features
•Facilitates remote diagnostics
•Display identical to panel view
•Remote Assistance
MXRemote
MXRemote is a Windows based software tool for remote
service and support of MX detection panels. MXRemote
provides a full function fire panel repeater running on a
PC either locally or over dial up telephone lines or via the
internet. Providing the operator has the correct passwords
MXRemote allows all operator, manager, service and
engineer functions available at the panel to be provided at
the PC.
This allows the customer or the Tyco service organisation to
provide remote assistance, service and limited configuration
assistance to the installation.
MXRemote is available as a stand-alone software
application for Tyco service operations. Alternatively Tyco
Fire Protection Products are able to provide consultancy
and assistance in implementing MXRemote as an integrated
part of a central station and service centre system.
Product Codes
557.203.004
557.202.128
UDS1100
Chapter 2 Page 80
Fire Catalogue
MXRemote Dongle and license (USB)
MX-FIM Modem Lead
Lantronics Device Server LAN
02/17
Chapter 2 - MZX Technology
Programming and Service Tools
Features
•Simplifies installation and commissioning
•Reduces the possibility of engineer error
•Improves health and safety by removing the need to work
at height
•Provides peace of mind through evidence based digital
reporting
850EMT Engineering Management Tool
The engineering management tool communicates with the 850 series and 830
series devices using a 2 way infrared wireless link. Commissioning data is held
within the 850 EMT and the technician will be prompted to select and confirm
configuration details resulting in an evidence based commissioning document
that can be downloaded from the programmer.
Technical Specification
2 way wireless infrared communication with detectors
TFT colour touch screen display
Save time with One Visit Commissioning (OVC)
Facilitates evidence based commissioning
Read/write the detector/ancillary address
Display and confirm zone and point strings
Display temperature/ CO levels / smoke obscuration
Programme the device LED
Initiate detector self verification test
Display detector dirtiness level
Control ancillary outputs
Read ancillary statuses
Compatible with all 800 series devices
Product Codes
516.850.900 516.800.922
516.800.924
516.800.923
02/17
850EMT engineering management tool
Spare ancillary programming lead
Pack of 10 spare pins for ancillary lead
Accessory kit (Carry case, shoulder strap & car
12v adaptor)
Fire Catalogue
Chapter 2 Page 81
Chapter 2 - MZX Technology
Features
•Compact
•Organises Tools •Sturdy Construction Protects Tools
MXService Accessory Kit
Product Code
A carry case which contains the following items:Car Lighter Adapter
Shoulder Strap
516.800.923
850EMT Engineer Management Tool
accessory kit
This provides space for the following:850EMT Engineer Management Tool
Ancillary Programming Lead
Mains Charger
Features
•Pre-Programmed with latest AVR firmware
•Powered from XLM Loop card or FIM, No external power
required
•Simple to operate
•Compact handheld device
•Complete with ribbon cable and connector
•High Speed USB port • Increased RAM increases speed of operation
MZX AVR Programmer
This unit will allows the MZX Technology® Fire Controller
Loop Drivers to be updated to the latest software version.
When required upgrades can be performed easily and
quickly in the field with minimal system downtime. The MZX
AVR Programmer is designed for use with MX,MZX,ZX and
T2000 addressable fire controllers, please check document
17-05-AVR for compatibility details.
Technical Specification
Product Code
2 Button Keypad
3 Status LEDs
Operating Temperature 0°C to 50°C
Size 189 x 80 x 31
516.800.942
Chapter 2 Page 82
Fire Catalogue
AVR PROGRAMMER EPSILON5-MK4
02/17
Chapter 2 - MZX Technology
Features
•Ability to commission loops without a panel
•Verify installed loops before connection to panel
•Fault find loops whilst disconnected from panel
MXLoop Tester
The MX Loop Tester can test, commission and fault-find
a loop of up to 250 MX digital addressable detectors/
devices, without a fire panel. A laptop is generally used for
operation & display, but a “One Person Installation Mode” is
automatically enabled on power up.
Identifies all devices on the loop, determining addresses
and types. Over-addressed (>250), unknown device types,
and, generally, duplicate addressed devices are recognised.
Monitors analogue values of all detectors/modules on the
loop to determine device status: normal/alarm/fault/dirty etc.
Provides alarm test for detectors that support it.
Allows Walk Test. Any device going into alarm is shown on
the laptop with address and time. Walk Test Status (devices
not tested yet) can be requested. Walk test mode overrides
detection algorithm delays for fast testing.
Technical Specification
Powered from 110V/230 V mains supply via 24 V, 3 A plug
pack, or from 24 V batteries (batteries not included).
Dimensions
Unit:
200 mm x122 mm x 46 mm
Carry Bag:
250 mm x 250 mm x 70 mm
Weight:
2 kg (without battery)
02/17
Monitors loop current and status, identifying open / short
and over-current conditions. Details devices present on each
side of break (so that position of break or tripped isolator
can be determined).
Includes commands to operate device LED and control
output modules (relays and sounders).
Turns on LED of faulty detectors (when there is no alarm) to
aid visual identification.
Automatic addressing mode allows un-programmed devices
to be added in sequence and be automatically addressed.
Detailed diagnostics and commissioning modes via laptop.
Product Codes
557.203.021 MXLoop tester with EUROPEAN/UK MAINS to IEC CABLE
557.203.022 SPARE ECM prog DB6 (FEM) - DB9 (FEM) null modem
557.203.023 Spare carry bag with 2 pockets and strap
557.203.024 Spare PSU 90-264 VAC IN/24 VDC 3 A out
557.203.026 Spare MX loop tester battery lead set Fire Catalogue
Chapter 2 Page 83
Chapter 2 - MZX Technology
Service & Spares
Keys & Keyswitches
557.203.005 Set of spare keys for MX Panel (AL102)
557.180.209 Keyswitch assembly for use with MX2
controllers (spare)
557.180.208 MX2 Spare Keys
557.201.508
MZX Spare Key Set
1500080 MZX Keyswitch cylinder
1700421 MZX Keyswitch lead
Housings & Metalwork
557.201.300 BFP801Blank Half Module - Grey Overlay
557.201.306 Standard MX Expansion backbox and
chassis plate
557.201.310 Deep MX Expansion backbox and chassis
plate
557.202.206 MX2 expansion aperture installation kit
CPU FIMs & Loop Cards
557.202.000 FIM801 1-Loop Field I/F Module
557.202.001 FIM802 2-Loop Field I/F Module
557.202.008 FIM801CV – T2000CV only
557.202.007 XLM800 2-Loop Expansion Card
557.202.810 CPU801 Central Processor Unit
Power Supplies
557.202.003 PSM800 Power Supply Unit
557.202.004 LBM800 Loop Booster Module PCB
557.202.210
PSU830 Power Supply with Loop Booster
557.202.208 MX2 8 Loop Expansion kit
557.201.210 Dual power supply mounting kit
557.202.050 PSM800 Temp Sensor Accessory Kit
557.202.113 PSB to FIM Cable
557.202.608
PMM800 Power monitor module
557.202.609
BAQ60T24 2.5A MZX PSU
557.202.610
BAQ140T24 5A MZX PSU
557.202.611
PMM805Power Monitor Module - 5 V
Repeater
557.202.612
PMM840Power Monitor Module - 40 V
Loop Power
Chapter 2 Page 84
Indication & Expansion
557.202.013 OCM800 Operator Control Module
557.202.019 ODM800 Operator Display Module
557.202.021 ANN840 40-Way Alarm/Fault LED Module
557.202.022 ANN880 80-Way Alarm LED Module
557.202.020 COM820 20-Way Status/Command
Module
557.202.200 DCM800 MX2 Display Control Module
(without LCD assy)
557.202.601 DCM816 16 zone display PCB for
MZX125/MZX16R
557.202.602 DCM832 32 zone display PCB for
MZX250/251/252
557.202.209 MX2 LCD assembly
557.202.028 RSM800 Power Supply
557.180.053 Isolated RS485 IC (for U16)
557.180.052 Serial Printer Driver Kit
557.202.613
DCM864R Spare Display / Control PCB for
MZX 253 (64 red zonal LEDs)
557.202.614
DCM8240 240 zone display PCB for
MZX254 and MZXDR
Callpoint Key & Glasses
515.001.045 MCP test key
515.001.119 MCP EN54 Spare Glasses pk of 5
MX Service Tool
516.800.922 MX Service tool, Spare programming lead
516.800.924 MX Service tool, Spare pins for
programming lead pk of 10
MX Loop Tester
557.203.022 MX
557.203.023 MX
557.203.024 MX
557.203.026 MX
Fire Catalogue
Loop
Loop
Loop
Loop
Tester ECM Prog Null Modem
Tester Carry Bag
tester PSU
Tester Battery lead set
02/17
FIRE_Ch3_Conventional_Systems:Layout 1 02/05/2017 10:44 Page 1
Chapter 3 - Conventional Systems
Control Panels and Repeater Panels
Features
• 2, 4 and 8 zone versions available.
• Supports the complete range of EN54 approved series
600 detectors including photo multi-sensor and CO
multi-sensor.
• Supports Tyco twin wire sounders on all eight detection
zones.
• Drives up to 3 repeater panels (4 and 8 zone panels).
• Access to controls via key switch.
• Space for 2 x 3.4 A/H batteries providing up to 72 hour
standby.
• Remote control inputs for class change, alert, evacuate,
silence alarms and reset.
• Zone 1 configurable for latching or non latching.
• Selectable zonal or general alarm sounder operation.
• Alert sounder option.
• Configurable zone co-incidence for automatic detectors.
• Fully monitored fire signalling output.
• Single pole volt free change over fire relay output.
• Single pole volt free change over fail safe fault relay
output.
• Short circuit fire option.
• Auxiliary 24 VDC 250 mA power supply output.
• Open collector output for buzzer active, disablement
active and evacuate active.
• Earth fault monitoring.
• Zone/Output disablement for each zone, fire signal
output and all sounders.
• Buzzer disable feature.
• One man zone test.
• One man sounder test.
• Automatic fire detector and manual alarm call point fire
event discrimination.
• Alarm counter.
• Compatible with diode bases for detector removal.
Minerva® MZX-c
The Minerva MZX-c range of conventional twin wire
firealarm control panels will satisfy a wide range of
applications from 2 to 8 zones and have many features
that are normally associated with more expensive
addressable systems.
The range consists of 2, 4 and 8 zone panels together
with an 8 zone repeater which is compatible with the 4
and 8 zone variants. The matching repeater panel has an
inbuilt 240 Vac power supply.
The Minerva MZX-c range of conventional fire detection
control panels are designed to be both installer and user
friendly. A high degree of flexibility and programmability
allows the systems to be customised without the need for
any configuration software.
03/17
Fire Catalogue
Chapter 3 Page 1
FIRE_Ch3_Conventional_Systems:Layout 1 02/05/2017 10:44 Page 2
Chapter 3 - Conventional Systems
Technical Specifications
Panels
2 Zone
Electrical
Mains Supply
Power Consumption (max)
PSU/Charger Output
Sounder Circuits 24VDC Nominal
Aux DC Output 24VDC Nominal
Maximum Battery Space
Environmental
Operating Temperature
Operating Humidity
Mechanical
Dimensions (W x H x D mm)
Weight Excl Batteries Kg
Enclosure Colour
2 x 0.5A
4 Zone
8 Zone
230 VAC +10% - 15%
138 W
1.5A
4 x 0.5A
4 x 0.5A
0.25A
2 x 3.4 A/H (PS-1230)
Repeater
8 Zone
N/A
N/A
-5°C to +40°C
95% Non Condensing
365 x 273 x 110
2.2
Light Grey RAL7035
Product Codes
508.031.004.EG
508.031.005.EG
508.031.006.EG
508.031.016.EG
Chapter 3 Page 2
Fire Catalogue
MZX-c
MZX-c
MZX-c
MZX-c
2
4
8
8
ZONE
ZONE
ZONE
ZONE
PANEL TYCO 2 WIRE
PANEL TYCO 2 WIRE
PANEL TYCO 2 WIRE
REPEATER PANEL
03/17
FIRE_Ch3_Conventional_Systems:Layout 1 02/05/2017 10:44 Page 3
Chapter 3 - Conventional Systems
Features
• 4, 8, 16 and 32 zone versions available
• Semi-Flush mounting using optional bezel
• Supports the complete range of EN54 Approved Series
600 Detectors including photo multi-sensor and CO
multi-sensor
• Compatible with System 620 ATEX and IECEx approved
intrinsically safe system
• Extensive custom options programmable via switches
and front panel controls
• Two stage alarms and investigate delay options
• Day/Night modes and alarm counter (with optional timer
module)
• Full EN54 zone operation with options for non-latching,
short circuit alarm or indication only circuits
Minerva® MZX-c+ (Does not suppport Tyco twin wire sounders)
The MZX-c+ range of Conventional Control Panels are
designed to be both installer and user friendly.
Additional Benefits
They are designed and manufactured to a high standard
and are approved by LPCB to EN54 parts 2 & 4.
These Panels are available in 4,8,16 & 32 zone versions
along with suitable Repeaters for all models.
The 8 to 32 Zone Panels are capable of driving any
combination of 8 channel output expansion boards (relays,
alarm circuits & open collector 0v outputs) up to a
maximum of 12 boards which can be set to zonal activated
or common output modes.
Each Panel has extensive configuration options but remains
easy to install, program and operate and are supported by
detailed documentation on commissioning, operation and
maintenance.
• Inputs for remote Silence, Evacuate, Reset and Class
change
• Configurable monitored or volt free outputs for Fire, Fault
and Protection
• Outputs for zones 1 to 4 (open collector) with 8, 16 or 32
zonal outputs provided by optional expansion boards
• Outputs for Disablement active, Evacuate active and
buzzer active (open collector)
• Volt free reset relay. Active for 10 seconds following a
panel reset
• 8 to 32 zone systems can drive up to 12 expansion input
/ output modules per panel
• Drive up to 5 repeater panels
The Panels are designed to work with a wide range of
manufacturers detectors (in addition to Tyco detectors) and
are suitable for use in many types of installation including
upgrades and new installations
Ancillaries and Expansion
C1631 Repeater Interface Board provides a port for
driving up to 5 repeater panels. One C1631 Repeater
interface board is required for the panel and one for each
repeater. Repeaters are supplied with a C1631 fitted.
C1630 Output Expansion Interface Board provides a port
for driving up to 12 output expansion boards.
EXP 4 and EXP 4 PSU Expansion Housings are designed
to house any combination of up to four output expansion
boards. The PSU version is equipped with a 5 A 24 Vdc
power supply with space for 2 x 12V 12 Ah batteries.
Housing dimensions 325W x 370H x 126D mm
EXP 5 and EXP 5 PSU Expansion Housings are similar
to the EXP 4 and EXP 4 PSU but accommodate five
output expansion boards. Housing dimensions 400W x
441H x 131D mm
03/17
Fire Catalogue
Chapter 3 Page 3
FIRE_Ch3_Conventional_Systems:Layout 1 02/05/2017 10:44 Page 4
Chapter 3 - Conventional Systems
Technical Specifications
Panels
Repeaters
Electrical
Mains Supply
Power Consumption
PSU / Charger Output
Sounder Circuits 24Vdc nominal
Aux. DC Output 24Vdc nominal
Maximum Battery Space
Environmental
Operating Temperature
Operating Humidity
Mechanical
Dimensions (W x H x D mm)
Space for 8 way expansion
Weight Excl. Batteries Kg
Enclosure Colour
4 Zone
8 Zone
85W
1.5A
4 @ 500mA
500mA
2 x 3Ah
165W
3.0A
4 @ 1A
1A
2 x 7Ah
16 Zone
32 Zone
230Vac +10% - 15%
165W
240W
3.0A
5.0A
4 @ 1A
4 @ 1A
1A
1A
2 x 12Ah 2 x 17Ah
8 Zone
16 Zone
32 Zone
85W
1.5A
N/A
N/A
2 x 3Ah
85W
1.5A
N/A
N/A
2 x 3Ah
85W
1.5A
N/A
N/A
2 x 3Ah
-5 to +40 oC
5% to 95% non-condensing
N/A
6.2
325x370x126
400x441x131
2 Boards
2 Boards
Use Exp Hsg
7.1
7.1
10.25
RAL7035 Light Grey
325x370x126
N/A
6.2
6.2
400x441x131
7.6
Product Codes
508.032.002.EA
508.032.003.EA
508.032.004.EA
508.032.005.EA
508.032.006.EA
MZXC+ 4 Zone Panel English/Arabic
MZXC+ 8 Zone Panel English/Arabic
MZXC+ 16 Zone Panel English/Arabic
MZXC+ 32 Zone Panel English/Arabic
MZXC+ 8 Zone Repeater 240Vac
English/Arabic
508.032.007.EA MZXC+16 Zone Repeater 240Vac
English/Arabic
508.032.008.EA MZXC+ 32 Zone Repeater 240Vac
English/Arabic
508.032.012
MZXC+ 4 Way Expansion Housing
508.032.013
MZXC+ 4 Way Expansion Housing with
PSU
508.032.014
MZXC+ 5 Way Expansion Housing
508.032.015
MZXC+ 5 Way Expansion Housing with
PSU
557.201.502
Flush Mount Bezel for MZXC+ 4/8/16
Zone Panel and Repeater
2605060
C1630 O/P Expansion Interface Board
2605061
C1631 Repeater Interface Board
2605062
C1632 16 Zone Interface Board
2605063
C1633 LED Driver Board
2605064
C1634 Relay Output Board
2605065
C1635 Monitored Output Board
2605070
C1651 MZX-c+ Timer Board
Chapter 3 Page 4
Fire Catalogue
03/17
FIRE_Ch3_Conventional_Systems:Layout 1 02/05/2017 10:45 Page 5
Chapter 3 - Conventional Systems
Features
• Developed for use in vessels which require between 4
and 32 zones of fire detection.
• Console or bulkhead mountable
• Range includes a separate Water Mist Panel
• Integrated Voyage Data Recorder output on 16 and 32
Zone Panel
• Increased configuration options to meet a wide range of
Class Society requirements
• Discrimination between Automatic Fire Detectors and
Manual Alarm
• Optional Marine Approved Muster Alarm.
• Separate battery box
• Multiple power supply options
• Lloyds approved water-mist functionality
T1200 Conventional Marine Controller
Developed and Manufactured in the United Kingdom the
T1200 range of Conventional Panels are a powerful yet user
friendly series of Control Panels. The range is fully
approved by all major Marine Authorities and takes advantage of the very latest technological advancements both in
terms of design and manufacturing to the latest Marine
standards.
Configurable Detection Zones allowing zones to be configured for any or all of the following :- Latching or Non
Latching Fire Indication Normal or Intrinsically Safe Zone
Monitoring of Machinery space zones. Crew Alert Mode :Manages Alarm Annunciation.
Detection Options
Optical Detector - An excellent all round detector suited to
all applications.
High Performance Optical (HPO) Detector - A direct
replacement for the Ion Chamber Smoke Detector.
Flame Detector- Used where there is a risk of large flaming
fires e.g. Machinery Spaces.
Enhanced Compensated Carbon Monoxide (CCO) Detector
– The best detector for early warning without false alarms
used in life threatening applications e.g. Cabins, Public
Spaces etc.
Pre-configured for Immediate use.
Heat Detector - Used where smoke detectors cannot be
used e.g. Galleys, Laundries, Drying Rooms etc.
Extensive configuration options using simple on board DIL
switches and links
03/17
Fire Catalogue
Chapter 3 Page 5
FIRE_Ch3_Conventional_Systems:Layout 1 02/05/2017 10:45 Page 6
Chapter 3 - Conventional Systems
Product Codes
508.023.001
508.023.002
508.023.003
508.023.104
508.023.105
508.023.106
508.023.111
508.023.114
508.023.122
508.023.123
508.023.126
508.023.127
508.023.025
2605061
2605063
2605064
2605065
508.023.035
508.023.036
508.023.051
508.023.052
508.023.053
T1204 DC 4 ZONE PANEL C/W 1.5 A
24 VDC PSU (requires T1200B battery
box)
T1204A1 4 ZONE PANEL C/W 1.5 A
110 VAC PSU (requires T1200B battery
box)
T1204A2 4 ZONE PANEL C/W 1.5 A
230 VAC PSU (requires T1200B battery
box)
T1216-C CONSOLE MOUNT 16 ZONE
PANEL C/W 5.0 AMP 115/230 VAC PSU
T1216W-C CONSOLE MOUNT 16 ZONE
WATER MIST FIRE DETECTION PANEL
C/W 5.0 AMP 115/230 VAC PSU
T1232-C CONSOLE MOUNT 32 ZONE
PANEL C/W 5.0 AMP 115/230VAC PSU
T1216R-C CONSOLE MOUNT 16 ZONE
REPEATER WITHOUT PSU
T1232R-C CONSOLE MOUNT 32 ZONE
REPEATER WITHOUT PSU
T1200E-C CONSOLE MOUNT
EXPANSION BOX WITHOUT PSU
T1200B-C BATTERY BOX SUITABLE FOR
2 X 17 A/H SLA BATTERIES
AC2SW 230 VAC MAINS CHANGEOVER
UNIT
AC1SW 115 VAC MAINS CHANGEOVER
UNIT
T1200 RMRS DOOR STAY KIT
C1631 REPEATER INTERFACE BOARD
C1633 LED DRIVER BOARD
C1634 RELAY OUTPUT BOARD
C1635 MONITORED OUTPUT BOARD
C1665 MUSTER INTERFACE BOARD
A1466 RELAY OUTPUT BOARD
T1216 CHINESE/JAPANESE INSERT SET
T1232 CHINESE/JAPANESE INSERT SET
T1216R CHINESE/JAPANESE INSERTSET
Chapter 3 Page 6
Spares
509.023.001
509.023.002
509.023.008
509.023.009
509.023.010
509.023.011
509.023.012
509.023.021
509.023.022
509.023.023
509.023.031
509.023.032
2605060
509.023.042
509.023.051
509.023.052
509.023.061
509.023.071
Fire Catalogue
C1626 4 ZONE PANEL MOTHERBOARD
C/W AC PSU
C1626 4 ZONE PANEL MOTHERBOARD
WITHOUT AC PSU
T1216-C MOTHERBOARD
T1232-C MOTHERBOARD
T1216W-C MOTHERBOARD
C1626 REPEATER MOTHERBOARD C/W
AC PSU
C1626 REPEATER MOTHERBOARD
WITHOUT AC PSU
C1628 4 ZONE PANEL DISPLAY
C1628 16 ZONE PANEL DISPLAY
C1629 32 ZONE PANEL DISPLAY
C1628 16 ZONE REPEATER DISPLAY
C1629 32 ZONE REPEATER DISPLAY
C1630 OUTPUT EXPANSION INTERFACE
BOARD
C1632 16 ZONE PANEL EXPANSION
BOARD
PS136 5.0A 110/230VAC PSU
PS40 1.5A 24VDC PSU
T1200 & T1200-C SPARE KEY SET
C1714 T1200-C SERIAL VDR PCB
03/17
FIRE_Ch3_Conventional_Systems:Layout 1 02/05/2017 10:45 Page 7
Chapter 3 - Conventional Systems
Extinguishing Panels, Repeaters & Accessories
Features
•
•
•
•
Approval to BS EN 12094-1:2003 additional options
Approval to BS EN 54-2 and 4
Designed to BS7273-1:2000
Comprehensive facilities for gaseous extinguishing
systems
• Monitored inputs for gas discharged, gas low, isolation
valve closed/abnormal, gas trapped in manifold
• Control inputs for auto/manual, gas hold, gas abort
• 1 minute actuator cut off option
• Monitored actuator/solenoid release
• Extensive disablement options
• Common fire, fault, relay / monitored output facilities
• 1st, 2nd, 3rd stage and gas discharged relay / monitored
output facilities
• Reset relay facilities
MZX-e Extinguishing Control Panel
The MZX-e gaseous extinguishant control panel is powerful
yet user-friendly and is designed and manufactured to a
high standard. The panel features approval to BS EN
12094- 1:2003, BS EN 54-2 and 4 and is designed to BS
7273 part 1. The panel has extensive configuration options
but is easy to install, programme and operate. The
removable chassis enables the engineer to “first fix” an
empty cabinet and then fit the chassis at the commissioning
stage.
Normally-open inputs provide for remote evacuate, silence
alarms, system reset, lock-off input, low pressure and gas
discharged pressure switch input.
This is supported by comprehensive documentation on
commissioning, operating, maintenance and fault finding. In
addition there is a comprehensive range of compatible
accessories available to meet most customer requirements.
Configuration
The use of DIL switches on the internal motherboard
enables the engineer to easily configure the extensive
options available and view the panel’s configuration upon
any return visit.
Operation
Three fully-monitored detection zones are provided. Zones
1 and 2 normally provide first stage and second stage fire
conditions to allow extinguishant discharge (coincidence
detection zones). Zone 3 is an auxiliary zone for detection
only purposes. Zone 4 is used as a manual release zone.
Facilities
Three fully-monitored alarm circuits are provided, each
rated at 0.5A with various configuration options via the
engineers DIL switch settings. Two circuits are designed to
provide audible warning of any fire condition and one circuit
to provide an individually distinct audible warning of the
pre-discharge, discharged and emergency hold condition.
Two fully-monitored actuator/solenoid circuits, each rated at
1A, operate simultaneously upon “extinguishant release”.
An RS485 multi-drop circuit link supports up to 7 Status
Controller/Indicators of any type mixed on the
communication path. Additional terminals and
configuration options allows the engineer to configure the
manual release, abort and hold switches to either data
comms or hard wired inputs as required.
03/17
Outputs are provided for first stage signalling, second stage
signalling, system discharged, common fire and common
fault . These outputs may be configured as either Volt-Free
C/O contacts or monitored 24V (50mA) outputs. A system
reset Volt-Free relay is also provided.
Additional Benefits
• Intrinsically safe barrier settings
• Metron or solenoid compatible
• Single or double knock operation
• Pre-discharge delay adjustable from 0 to 60 seconds
• Discharged indication with or without pressure switch
• Inhibit silence alarms until gas discharged
• Latching or non latching fault indication option
• Option for rapid buzzer pulse when gas discharge is
imminent
• One man zone and sounder test
• Easily removable chassis
Product Codes
508.033.050.EA MZX-e Extinguishing Control Panel
English / Arabic
508.033.002.EA MZX-e SLU1 Status Lamp Unit, Indication
only English / Arabic
508.033.003.EA MZX-e SLU2 Status Lamp Unit, Indication,
Auto/Manual Select and Manual Release
English / Arabic
508.033.004.EA MZX-e SLU3 Full Function Status Lamp
Unit, Indication, Auto/Manual Select,
Manual Release, Hold, Abort & Time
Counter English / Arabic
508.033.005.EA MZX-e SLU4 Weatherproof Status Lamp
Unit, Indication and Auto/Manual Select
English / Arabic
Fire Catalogue
Chapter 3 Page 7
FIRE_Ch3_Conventional_Systems:Layout 1 02/05/2017 10:45 Page 8
Chapter 3 - Conventional Systems
Extinguishing Door Interlock Ancillaries & T500 Series Spares
A microswitch lock keep can be used
with a deadlock to provide a signal to
the panel to ensure that the
extinguishing system is only put into
Automatic mode when the door is
locked shut.
Product Codes
527.001.028
Micro-switch Lock Keep & Back-plate
For Deadlock
599.001.012
Lamp 28V 60mA Used On T525
T561 Electrical Manual Release Unit
A stand alone manual extinguishant
release unit with selectable activation
and end of line resistors making the
T561 compatible with MZXE,
Prescient 3, System 1700 and NTR
Extinguishing Panels.
Product Code
509.030.117
T561 Extinguishing Release Manual
Callpoint.
Weatherproof Extinguishing Indicator Units
E1 Single Red lamp unit
Single 24 V d.c. red lamp labelled
'Extinguishing System Operated'
Technical Specification Dimensions:
H(mm)
W(mm)
D(mm)
E1
110
110
122
E3
220
91
115
E3 Red/Amber/Green lamp unit
Heavy Duty IP67 Cast Aluminium
Surface Mount Lamp Unit Three
24Vdc lamps:
Red labelled 'Extinguishing System
Operated'
Chapter 3 Page 8
Amber labelled 'Extinguishing
System Automatic Control'
Green labelled 'Extinguishing
System Manual Control'
Fire Catalogue
Product Codes
540.007.001
E1 Single Red lamp unit
Heavy Duty IP67 Cast Aluminium
Surface Mount Lamp Unit
599.001.029
Spare bulb for E1/E3 24V-5W
Product Codes
540.007.002
E3 Red/Amber/Green lamp unit
599.001.029
Spare Bulb for E1/E3 24V-5W
03/17
FIRE_Ch3_Conventional_Systems:Layout 1 02/05/2017 10:45 Page 9
Chapter 3 - Conventional Systems
DDA Compliant Pager
Features
•
•
•
•
•
•
•
•
•
•
•
•
UHF radio link for maximum licensable protection
Unique coding avoids neighbouring system clashes
Self monitoring of system health
Rugged steel enclosure to IP65
Backlit 2 line text display continuously reports system
status
Additional audible & visible status indicators
Prioritised Fire Alarm Inputs
Automated test calls alert pagers to loss of radio signal
Fault Notification to the lost fire panel via a monitored link
Key operated "System Test" facility for routine confidence
checking
Over 90 hour's backup operation with internal battery
Achieves Disability Discrimination Act (DDA) compliance
Fire Tek Pro Paging System
The FireTek Pro paging system is designed for use with
professional Fire Systems installed in commercial, industrial
and educational premises. The system is primarily
designed to alert the "hearing impaired" in the event of a fire
or other emergency where an audible sounder is the
normal means of indication.
The FireTek Pro has been designed to comply with the
recommendations detailed in BS5839-1: 2002 for alerting
the "hearing impaired" to the activation of a fire alarm
system.
High Integrity Pagers
To complete the system the alphanumeric pagers have
added features specifically incorporated for the "hard of
hearing" when used with the FireTek Pro. These features
include distinct vibrate alerts for emergency messages, a
vibrating out of range indicator which displays "No Service"
on the pager when the radio link is lost, and a vibrating low
battery indicator.
Antenna Options
Mini Dipole Antenna - remote internally mounted antenna
for large sites or areas of difficult signal propagation.
The system can also be used in conjunction with a security
panel to alert guards who might be located remotely from
the main premises.
Folded Dipole Antenna - remote externally mounted
antenna for maximum signal coverage e.g. campuses and
multi-building sites.
The interface to the fire panel comprises of three Prioritised
Fire Inputs and two Fault Inputs. For ease of installation, a
monitored cable assembly is provided with each system
which includes a "common fault" relay output back to the
host fire panel. This output will activate if the FireTek Pro
suffers a mains failure, transmitter fault, antenna mismatch,
interface link failure, or low battery state.
Upon activation of any one of the Fire Inputs, the FireTek
Pro will enter the fire alert condition, prioritisng and
transmitting the Fire message to all enrolled pagers. The
transmissions will be repeated until the fire condition is
reset. The FireTek Pro Pagers ensure that users are alerted
by distinct vibration patterns and clear text messages.
UHF Radio Operation
Any alerting system is only as good as its weakest link. The
FireTek Pro utilises UHF radio frequencies, the main
benefits being superior in-building radio signal propagation
and the option of a manual frequency co-ordinate license
issued by OFCOM. Licensing the FireTek Pro provides a
higher degree of protection from interference. This fact is
acknowledged in Section 18.1 of BS 5839-1:2002.
03/17
Fire Catalogue
Chapter 3 Page 9
FIRE_Ch3_Conventional_Systems:Layout 1 02/05/2017 10:45 Page 10
Chapter 3 - Conventional Systems
Technical Specifications
Product Codes
Supply Voltage:
557.200.071
557.200.074
557.200.076
557.200.077
557.200.078
557.200.079
557.200.080
Operational Current:
Inputs:
Outputs:
Fault Notification:
Visual Display:
Enclosure:
Dimensions:
Chapter 3 Page 10
230 V AC 50-60 Hz
12 v 7Ah standby battery
250mA
3 Prioritised Volt Free (Fire)
Input 1 - Fire Alarm - Evacuate
Building
Input 2 - There is an Incident Leave Building
Input 3 - Prepare to Evacuate Await Instructions
2 Volt Free (Fault)
1 off volt free relay output
Mains Failure
Transmitter Fault
Antenna Mismatch
Panel Link Failure
Low/Missing Battery
2 Line Backlit LCD
Steel Enclosure rated to IP65
380 x 320 x 110 mm (H x W x D)
(No antenna fitted)
Fire Catalogue
Paging Transmitter
40 Character Alpha Numeric Pager
1/2 wave dipole antenna
Wall mounting folded dipole antenna
Pole mounting folded dipole antenna
5 metre antenna feeder cable
10 metre antenna feeder cable
03/17
FIRE_Ch3_Conventional_Systems:Layout 1 02/05/2017 10:45 Page 11
Chapter 3 - Conventional Systems
Point Detectors
Features
•
•
•
•
•
•
•
Through innovative design the Series 600 detectors have
reduced the installation and servicing time to a minimum,
needing only one visit to complete the installation and
having a park position for the detector to ease the servicing.
Unique early detection enhanced CO fire detector
Intelligent Universal HPO Smoke Detector
Low profile, discreet and unobtrusive
Superior performance and reliability
Designed for fast, easy installation
Integral and remote alarm LED
Series of Product Approvals
The HPO can be seen as a truly universal smoke detector,
suitable for most applications.
Approvals:-
The Series 600 detectors include the unique enhanced
Carbon Monoxide CO fire detector, which provides a
general purpose fire detector with unprecedented early
detection capability and excellent false alarm immunity. The
CO fire detectors are the first choice for sleeping risks.
Also included within the range is the intelligent high
performance optical smoke (HPO) detector. The use of the
patented optical sensing chamber, together with refined
signal processing, has enabled the introduction of a smoke
detector suitable for fast, reliable smoke detection of both
slow and fast developing fires.
03/17
Fire Catalogue
Chapter 3 Page 11
FIRE_Ch3_Conventional_Systems:Layout 1 02/05/2017 10:45 Page 12
Chapter 3 - Conventional Systems
High Performance Optical Smoke
These detectors react to the whole
range of fire products from slow
smouldering fires, producing visible
particles to open flaming fires
producing large numbers of very hot
smaller sized aerosols. It combines
optical and heat detector technology
to detect clear burning fire products
which hitherto could only be easily
detected by ion-chamber detectors.
For normal ambient conditions, the
high performance optical detector
behaves as a normal optical detector.
Only when a rapid rise in temperature
is detected does the sensitivity of the
detector increase and the presence
of smoke will confirm a fire condition.
The HPO will not operate on a rate of
rise of temperature alone.
Datasheet - Product Code PSF123
Manual - Vol 01C-02-D2 “Detectors
Fire Manual”
Product Codes
516.600.002
Approval
Model
LPCB
601PH
516.600.202
Approval
Branded
Marine
Tyco
Model
601PH-M
Enhanced Carbon Monoxide Fire
The CO fire detector is a unique
general purpose fire detector which
provides very early warning of slow
smouldering fires. Ideal for sleeping
risks the CO fire detector is also well
suited to many applications where
heat detection is insufficient but
smoke detection causes false alarms.
As CO travels more freely than smoke
the position of CO fire detectors is
more flexible.
This feature is particularly useful in
large complex structures such as atria
and warehouses, where position of
smoke detectors is difficult.
Datasheet - Product Code PSF123
Manual - Vol 01C-02-D3 “Detectors
Fire Manual”
Product Codes
516.600.004
Approval
Model
LPCB
601CH
These detectors are capable of
detecting the visible smoke produced
by materials which smoulder or burn
slowly, i.e. soft furnishings, plastic
foam etc;. or 'smoke' produced by
overheated but unburnt PVC. These
detectors are particularly suitable for
general applications and areas where
cable overheating may occur e.g.
electrical services areas. The novel
design of the asymmetrical sampling
chamber and signal processing
techniques stop unwanted alarms
caused by very small insects. i.e.
thrips. Smoke entering the sampling
chamber scatters the infra-red light
pulses onto a photo-diode. These
pulses are converted to an electrical
signal which is compared against a
preset alarm level.
Product Codes
516.600.001
Approval
Model
LPCB
601P
516.600.201
Approval
Branded
Marine
Tyco
Model
601P-M
These detectors use two networked
thermistors in a bridge configuration
to provide a fast response, that
depends both on absolute
temperature and notes the change of
temperature. The rate of rise/fixed
temperature heat detectors can be
used in areas where smoke sensors
are unsuitable due to environmental
conditions (smoke, dust etc,). Such
areas include kitchens, locker rooms,
canteens, garages, loading bays etc.
Rate of Rise
Product Codes
516.600.003
Approval
Model
LPCB
601H-R
516.600.203
Approval
Branded
Model
Marine
Tyco
601H-R-M
Fixed Temperature 60°C
Product Code
516.600.214
Approval
LPCB/Marine
Model
611H-F
Fixed Temperature 90°C
Product Code
516.600.033
Approval
LPCB/Marine
Model
631H-F
Optical Smoke
Datasheet - Product Code PSF123
Manual - Vol 01C-02-D6 “Detectors
Fire Manual”
Heat
Datasheet - Product Code PSF123
Manual - Vol 01C-02-D5 “Detectors
Fire Manual”
Chapter 3 Page 12
Fire Catalogue
03/17
FIRE_Ch3_Conventional_Systems:Layout 1 02/05/2017 10:45 Page 13
Chapter 3 - Conventional Systems
Solar Blind Infra Red Flame Detector
Flame detectors, unlike smoke and
heat detectors, do not rely on
convection to transport the fire
product to the detector, nor do they
rely on a ceiling to trap the products.
They can therefore, be used to
protect large open areas without
sacrificing speed of response to
flaming fires. In order to ensure full
coverage, however, flame detectors
do require direct line of sight to all
parts of the protected area.
Infra-red flame detectors such as the
601F are designed to respond
03/17
rapidly to fires which involve cleanburning fuels such as alcohol or
methane, ie fires which would not be
detected by smoke detectors. The
601F Flame detector, by virtue of it’s
operating wavelength and flicker
discrimination, is insensitive to
normal environmental influences. For
outdoor use, a solar-blind detector
(e.g. the S200Plus) should be used.
The 601F flame detector should,
normally, only be used inside
buildings to supplement heat and
smoke detectors.
Fire Catalogue
Product Codes
516.600.006
601F
516.600.007
601F-M Marine
Datasheet - Product Code PSF132
Manual - Vol 01C-02-D9 “Detectors
Fire Manual”
Chapter 3 Page 13
FIRE_Ch3_Conventional_Systems:Layout 1 02/05/2017 10:45 Page 14
Chapter 3 - Conventional Systems
Series 600 Detector Specifications
Dimensions of Smoke/Heat/Co Detector
43
109
Dimensions of Flame Detector
21.2
108
Technical Specification - Series 600
601I
601PH/P/601PH-M/601P-M
Weight
100g
93g
Material
Operating Temp.
-20 to +70°C
-20 to +70°C
Storage Temp.
-40 to +80°C
-25 to +80°C
Relative Humidity
Quiescent Current(typ)
62μA
65μA
Alarm Current(typ)
54mA
45mA
Operating Voltage
10.5 - 33 Vdc
10.5 - 33 Vdc
*Short Term (<3min) -40 to +120°C
601H-R/611H-F/601H-R-M/631H-F
80g
FR 110 Bayblend
-20 to +70°C*
-25 to +80°C
95/98% Non-Condensing
61/65μA
53mA
10.5 - 33 Vdc
Chapter 3 Page 14
Fire Catalogue
601CH/601CH-M
90g
601F/601F-M
74g
-10 to +55°C
-20 to +55°C
-20 to +70°C
-40 to + 80°C
87μA
53mA
10.5 - 33 Vdc
300μA
42mA
18-28Vdc
03/17
FIRE_Ch3_Conventional_Systems:Layout 1 02/05/2017 10:45 Page 15
Chapter 3 - Conventional Systems
Features
• Sealed Stainless Steel Construction
• Suitable for use in hazardous areas
T54B - Point Type Heat Detector
Constructed from stainless steel, the T54B is an extremely
rugged heat detector that can be used to detect fires in the
harshest of environments. The T54B can be used in
environments with ambient temperatures up to 200°C and,
being hermetically sealed is impervious to most
contaminants.
For reliable operation, it is recommended that T54B
detectors have set points 20°C or 20% (whichever is higher)
above the maximum temperature they will be exposed to in
normal operation.
Preferred factory preset temperatures are:
60, 90, 100, 145°C; normally with open contacts.
Classified as a simple device, the T54B can be used in
Zone 0 areas when connected to a suitable intrinsically safe
barrier.
Technical Specification
Product Codes
Operating voltage
@ 0.5A:
Switching Current:
Contact Resistance:
Actuating Temp:
(factory set)
Fixed Temp. only:
Accuracy:
Ambient Temp.:
Relative Humidity:
Protection Category:
Thread Size:
516.033.011
03/17
240Va.c. to 24Vdc
5 to 500mA
<1 ohm
516.033.012
516.033.013
60 to 240°C
Type E
+ or - 5%
-40 to +270°C
100% RH
IP67
M20 x 1.5mm
516.033.014
T4E60X T54B Point Type heat
detector - 60°C
T4E90X T54B Point Type heat
detector - 90°C
T4E100X T54B Point Type heat
detector - 100°C
T4E145X T54B Point Type heat
detector - 145°C
Other temperatures and normally closed contacts are
available by request.
Fire Catalogue
Chapter 3 Page 15
FIRE_Ch3_Conventional_Systems:Layout 1 02/05/2017 10:45 Page 16
Chapter 3 - Conventional Systems
Beam Detectors
Features
• Motorised Auto-Aligning
• Up to two Detectors per System Controller
• Controller provides fire and fault relays for each detector
head
• Each Detector configurable from 8m to 100m
• Integral LASER
• Auto-Align Fast Automatic BeamAlignment
• Auto-Optimise Building Movement and Contamination
Compensation
• Low Level System Controller
• 20mm Cable Gland Knockouts on System Controller
• 2-wire interface from System Controller to Detector
• Worldwide Approvals including EN54:12 and UL268
• Individual fire and fault relays for each detector
FIRERAY 5000 Multi Head Auto Aligning Infrared Optical Beam Smoke
Detector
The FIRERAY® 5000 motorised, auto aligning infrared
optical beam smoke detector can support two detector
heads per system, thus saving on installation time and
costs. This innovative system has been designed from the
ground up to include pioneering technology that fully
addresses the needs of the installer and user, both now and
in the future.
Once the LASER has been used to coarsely align the beam,
the AutOptimise beam alignment system takes over and
automatically steers the beam into the optimum position.
The system can be fully customised, according to local
conditions; both alarm thresholds (sensitivity) and time
to Alarm/Fault can be set from the ground level System
Controller.
With its industry leading optics, the FIRERAY 5000 is ideally
suited for the protection of large areas where the use of
traditional detection technologies would prove to be too
difficult and/or costly to install. The FIRERAY 5000 combines
an infrared transmitter and receiver in the same discrete unit
and operates by projecting a well-defined beam to a
reflective prism, which returns the beam to the receiver for
analysis. Smoke in the beam path causes a drop in power,
which, if below a pre-determined level, results in an alarm
signal.
Each detector head is independently configurable from 8m
through to 100m and has its own individual fire threshold
and dedicated fire / fault relay outputs. The System
Controller retains one set of Fire and Fault relays that is
common to all detectors that are installed.
Getting the system operational is simplified by a number of
groundbreaking features that combine to make the FIRERAY
5000 the quickest and easiest detector of its type to install.
Once the detector heads are connected, using the Easifit
First Fix system, an integral LASER, which is aligned along
the optical path of the beam, can be activated. This allows
the reflective prism to be sighted quickly and with
confidence.
The FR5000 MultiHead is supplied with one detector head
and reflector for single beam operation from 8 to 50 meters.
An additional detector head can be added to the
controller to enable larger or more complex areas to be
protected (Subject to local codes and standards).
The Fireray 5000 when used in its low power mode can be
interfaced to the MZX Fire Controller using the BDM800
module.
Technical Specification
Product Codes
Controller:
202w x 230h x 81d mm 0.9 Kg
Detector:
134w x 135h x 134d mm - 0.5 Kg
Operating Current Operating
Voltage:
14 to 36 VDC
(low power mode):
8 mA @ 24 VDC
IP Rating:
IP54
Operating Temp:
-20 to +55oC
Humidity:
93% RH (non condensing) max
516.015.020
516.015.021
516.015.007
Chapter 3 Page 16
Fire Catalogue
FireRay 5000 System (50 m)
FR 5000 Detector Head (50 m)
FireRay Reflector 100 X 100 mm
4 reflectors are required for distances from
50 to 100 m
03/17
FIRE_Ch3_Conventional_Systems:Layout 1 02/05/2017 10:45 Page 17
Chapter 3 - Conventional Systems
Features
•
•
•
•
•
•
•
•
•
•
•
•
Separate Transmitter and Receiver Heads
Range 5 to 120 metres, configurable per set of Detectors
Integral Laser Alignment in Receiver
2-wire Interface between Controller and Receiver
Single and Twin Detector options
Separate Fire and Fault Relays per Detector
Low Level Controller with LCD display
Programmable Sensitivity and Fire Threshold
Automatic Gain Control (AGC) for drift compensation
First Fix concept for Transmitter, Receiver and Controller
Multiple cable gland knockouts for ease of wiring
Optional Transmitter powering from Controller
Fireray® 3000 Optical Beam Smoke Detector
The FIRERAY® 3000 is ideal for applications where line of
sight for the IR (infra-red) detection path is narrow and
where the building structure uses reflective surfaces. It has
also been designed to be aesthetically pleasing and thus
can equally suit modern architectural buildings as well as
heritage sites, particularly where ornate ceilings exist.
The FIRERAY® 3000 has been designed so that it can be
installed by one operator, with its laser assisted alignment
method combined with easy to use alignment LED’s offering
visual feedback. The integrated lser alignment aid can be
activated at the controller or at the receiver head.
An additional detector head set (one transmitter & one
receiver) can be added to the controller, separate relay
contacts are provided for each of the 2 beam sets.
Technical Specification
Dimensions & Weight
Control Unit:
203 x 124 x 71.5mm (W x H x D)
606gms
Transmitter & Receiver: 78 x 77 x 161mm (W x H x D)
207gms
Operating Range:
5 to 120 m
Operating Voltage Range:
12 to 36V DC ±10%
Operating Controller Current (with 1 or 2 Receivers):
14mA (constant)
Operating Transmitter Current:
8mA (per transmitter)
Power Down Reset Time: >10 seconds
Fire and Fault Relay Contacts: VFCO 2A @ 30Volts DC
resistive
Operating Temp.
(non-condensing):
UL - -20°C to +55°C
EN54 - -10°C to +55°C
IP Rating:
IP54
Relative Humidity (non-condensing):
93%
Product Codes
516.015.030
516.015.031
Fireray3000 Optical beam detector
FireRay3000 Extra beam set
FireRay Optical Beam Smoke Detector Mounting Accessories
There are a range of mounting accessories available for use with FireRay® Optical Beam Smoke Detectors. These
accessories will help reduce installation times and provide a professional mounting solution when faced with challenging
building internals.
The large prism plate will securely
The Universal Mounting bracket can be used
mount 4 prisms and is designed
with the Fireray 5000 detector head and the 1
to be used in conjunction with the
or 4 way prism plates to enable the detector
Universal Mounting Bracket (not
head or prism plates to be easily mounted
included)
and adjusted when fixing to angled walls or
cladding
The small prism plate will securely
mount a single prism and is
designed to be used in
conjunction with the Universal
Mounting Bracket (not included)
The Flat Mounting plate is a metal plate
which will support a single prism or 4 prisms,
the side mounting holes are compatible with
Unistrut® racking systems.
Adjustable bracket for use with the
Fireray 3000 heads or Fireray 5000
head.
03/17
Product Codes
5000-005
5000-006
5000-007
5000-008
3000-201
Fire Catalogue
Universal Mounting Bracket
Flat Mounting Plate for 1 to 4 Prisms
Prism Mounting Plate for 4 Prisms
Prism Mounting Plate for 1 Prism
FireRay3000 adjustable bracket
Chapter 3 Page 17
FIRE_Ch3_Conventional_Systems:Layout 1 02/05/2017 10:45 Page 18
Chapter 3 - Conventional Systems
Linear Heat Detectors
Features
• Alarm & Pre-Alarm temperature ranges from 54oC to
100oC
• Programmable on-site adjustment of sensitivity.
• Up to 500 m continuous length
• Alarm hot-spot length equal to 3% of zone length
• Separate Alarm and Pre-alarm volt-free outputs
• No nomograms or other scales to interpret
• Simple, 3-Step Installation:
• Ambient temperature compensation maintains alarm
temperature accuracy
• Self-Restorable after fire event up to 125oC
• Flexible cable for easy mechanical installation
• Reliable signalling of open and short circuit conditions
• Extrusion and Braiding options to satisfy both
mechanical and environmental conditions
Linear Heat Detection
ProReact Analogue Heat Detector is a control module and
detection cable designed to interface to a conventional fire
alarm panel or addressable detector monitor module
DIM800 or DDM800. The control module monitors the
resistance of specially doped polymers within the sensor
cable which change as a function of temperature. An
abnormal change in resistance along the detection cable
triggers either a Pre- Alarm or Alarm on the interface
module.
The system is intended to simplify system design and be
uncomplicated and straightforward to install.
Technical Specification
Product Codes
Environmental Specifications
Min/Max Operating ambient temperature
Controller
0°C – +50°C
Sensor Cable (recoverable)
-40°C – +125°C
Continuous operating temperature range
Sensor Cable
-40°C – +90°C
Humidity
Controller
0% - 95% RH
(Max. 75% RH for <75m cable
and 54°C alarm setpoint)
Sensor cable
0% - 99% RH
Electrical Specifications
Operating Voltage Range
20 Vdc – 28 Vdc
Current Consumption
normal & fault conditions
<70 mA (Base PCB only < 50
mA)
pre-alarm OR alarm conditions
<80 mA
pre-alarm & alarm conditions
<100 mA
Relay outputs
Alarm & Pre-alarm FORM C
2 A @ 30 Vdc load rating resistive
0.25 A @ 250 Vac (62.5 VA) load
rating - resistive
Sensor Cables
516.016.019
Chapter 3 Page 18
Commissioning of the controller can be done using a laptop computer or through an optional built-in self-programming module. The sensor cable has been designed to be
physically and electronically rugged to suite a range of
environments with options for PVC, Polypropylene or Nylon
coatings or a strong stainless steel braid.
516.016.020
516.016.021
516.016.022
516.016.023
516.016.024
516.016.025
516.016.026
Control Units
516.016.016
516.016.017
516.016.018
Fire Catalogue
ProReact Analogue Cable PVC order in
multiples of 200
ProReact Analogue Cable PVC order in
multiples of 500
ProReact Analogue Cable with additional
Polypropylene coating order in multiples
of 200
ProReact Analogue Cable Polypropylene
coating order in multiples of 500
ProReact Analogue Cable Nylon coating
order in multiples of 200
ProReact Analogue Cable Nylon coating
order in multiples of 500
ProReact Analogue Cable Stainless Steel
Braid order in multiples of 200
ProReact Analogue Cable Stainless Steel
Braid order in multiples of 500
ProReact ProReact Analogue Controller
with display including EOL unit
ProReact ProReact Analogue Controller
including EOL unit
End of line unit
03/17
FIRE_Ch3_Conventional_Systems:Layout 1 02/05/2017 10:45 Page 19
Chapter 3 - Conventional Systems
Linear Heat Detectors
Installation standards such as BS5839 part 1 specify noncombustible cable supports and this requirement extends
to linear heat sensor cable. To satisfy this requirement the
ProReact Analogue Heat Detector range includes a range
of fixings in either Zintec or Stainless Steel and compatible
cable ties
Product Codes
Fixings
516.016.220
516.016.221
516.016.222
516.016.223
516.016.224
516.016.225
516.016.230
Standard L 50 mm
Dual height L clip
Channel bracket
516.016.231
516.016.232
516.016.234
516.016.235
516.016.236
516.016.237
L with edge clip
516.016.238
Clip extension
Dual Height L cable clip 100mm Zintec
Standard L Clip 50mm Zintec
Channel bracket for attaching LHD cable
to flat surface Zintec
V-clip for cable trays Spring Stainless
Steel
L clip with edge clip Zintec
clip extension for use with other clips
where required Zintec
Dual Height L cable clip 100mm Stainless
Steel
Standard L Clip 50mm Stainless Steel
Channel bracket for attaching LHD cable
to flat surface Stainless Steel
L clip with edge clip Stainless Steel
clip extension for use with other clips
where required Stainless Steel
110 deg C indoor/outdoor cable tie UV &
Heat Stabilised Pack of 100
170 deg C indoor tie wrap Not UV
stabilised Pack of 100
170 deg C indoor/outdoor tie wrap
Stainless Steel Pack of 100
V Clip
Detector Bases and Accessories
Features
•
•
•
•
Optional relay bases
Remote indication LEDs
Optional conduit entry backboxes
Protective wire cages
Detector Bases and Ancillaries
The 600 Series range of low profile detectors provide a
comprehensive range of highly effective and aesthetically
pleasing smoke and heat detectors with worldwide
approvals.
The unique design and leading edge technology of the
detectors go beyond the detection technology itself.
The range of detector bases is designed to make low profile
detector installations cost effective, aesthetically pleasing
and easy to install and maintain – thus minimising
disruption.
03/17
The detector bases include standard universal bases,
which have no integral electronics, thus making them low
cost and low maintenance. Alternatively, a range of
functional bases incorporate sounders and relays to
provide a cost effective method of adding functions and
flexibility to the fire detection installation.
Fire Catalogue
Chapter 3 Page 19
FIRE_Ch3_Conventional_Systems:Layout 1 02/05/2017 10:45 Page 20
Chapter 3 - Conventional Systems
Standard Detector Bases
The standard universal detector bases are compatible with the Series 600 low profile detectors. The standard bases have
no electronics and even when the detectors are connected to the bases, they can be electrically disconnected and left in
a ‘park’ position. This enables wiring integrity tests to take place without any damage to electronics. An optional, tool
removable locking pin allows the detector to be fixed in place to prevent tampering.
4B 4” Detector Base
The new 4B 4” detector base is
designed to snap-fit to the ceiling tile
adaptor or it can be screw fixed to a
ceiling in the traditional manner.
Features
• Drives a remote indicator
• Detector locking pin provided
with every base
• Snap fits to the Time Saver
Ceiling Tile Adaptor
• Fits directly to a British or
European electrical back box
• Temporary park position
• Break-outs for surface mount
Product Code
517.050.041
4B 4” Detector Base
4B-D 4” Diode Continuity Base
The 4B-D Continuity Base is a
standard 4 inch base fitted with a
continuity diode, for use with all
Series 600 detectors. The base is
designed to ensure that conventional
systems meet the requirements of
BS5839 Pt:1 for callpoints placed
after detectors.
Features
• Compatible with Series 600 Low
Profile Detector Range
• Designed for two wire operation
• Facility to drive a remote indicator
• A breakout locking key is
provided as an integral part of
each base, which can be fitted to
lock the detector into position.
• A temporary park position is
provided so that the field wiring
can be tested with the detector in
situ.
• Maybe fitted directly to a British or
European conduit box or directly
onto the ceiling
Product Code
517.050.045
4B-D 4” Diode Continuity Base
Features
• Cuts installation time by 30%
• Commission the system before
the suspended ceiling is installed
• Suitable for ceiling tiles from 1mm
to 30mm thick
• Made from flame retardant
material
• No additional back-box is
required
• Time saver is designed for use
with a new snap-fit 4” detector
base
• Adaptor available for use with the
601 and 602 sounder bases.
Product Codes
517.050.060
Ceiling Tile Adaptor Kit consists of 1
x 517.050.056 and 1 x 517.050.057
517.050.056
CTA-BB CTA Back Box
517.050.057
CTA-BC CTA Bezel and Clamp
517.050.058
CTA-AP CTA Adaptor Plate
Features
• Adapts 6” electrical boxes to fit
the 4B-C 4” continuity base
• Architectural trim for neat
appearance
• Concealed fixings
• Use to conceal marks left by old
detectors when replaced by MZX
Technology
Product Code
517.050.054
4B-6A 4" to 6" Base Adaptor
Ceiling Tile Adapter
The Time Saver Ceiling Tile Adaptor
is used with the 4” snap fit base and
consists of three parts, a bezel and
clamp that are fitted to the ceiling tile
and a back-box that carries the
detector and base assembly. It is
available as a complete unit or
alternatively, the back-box can be
ordered separately, as can the bezel
and clamp assembly. Ordering the
parts separately may be preferred if
there is an extended period before
the false ceiling is installed e.g. “shell
and core” projects. Requires a
127mm diameter hole. The CTA
adaptor plate allows the Time Saver
Ceiling Tile Adaptor to be used with
other devices such as the 601 and
602 sounder bases.
4B-6A 4” to 6” Adaptor
The 4B-6A 4” to 6” Adaptor is
designed for use with U.S. style 6”
electrical back boxes and provides a
flush architectural trim between the
electrical box and the 4B-C 4”
continuity base. It can also be fixed
directly to a ceiling and used to
conceal marks left when older, large
diameter detectors are replaced with
MZX Technology.
Chapter 3 Page 20
Fire Catalogue
03/17
FIRE_Ch3_Conventional_Systems:Layout 1 02/05/2017 10:45 Page 21
Chapter 3 - Conventional Systems
Functional Detector Bases
Functional detector bases use a common moulding which
incorporates a double sided circuit board which enables
electrical connections to be made on the top and bottom of
the functional base. This allows the functional bases to be
retrofitted into new and existing universal bases or
alternatively the depth and cost of the installed detector can
be reduced by using the functional base instead of the
universal base.
This feature enables additional sounders to be easily added
during commissioning. In addition, changes to the building
during it’s life can be easily adapted to, by retrofitting
sounders and relay outputs to existing detection points.
When functional bases are fitted to universal bases, they
automatically lock into position. Removal is then achieved
using the detector removal tool. This feature ensures that
the detector and functional bases are removed separately.
Manual - Vol 01B-09-D1/01B-07-D1 “Detectors Fire Manual”
Tyco MKII Sounder Base
A new low current range of sounder
bases for use with Conventional Fire
Alarm Control Panels.
Features
• Manufactured to EN54 part 3
• Integral sounder and detector
base
• Volume and tone adjustable after
installation
• Low Power Synchronisation
• Do not require use of a standard
base (maybe installed directly
onto a standard besa box)
Product Codes
577.001.035
601SB Conventional Sounder Base
577.001.037
601SBD Conventional Diode Sounder
Base
577.001.036
602SB 2 Wire Line Powered Sounder
Base
577.001.038
602SBD 2 Wire Line Powered Diode
Sounder Base
517.050.022
Volume Pot Spare Cover (1 sheet of
144)
517.050.005
4” Detector Base Locking Pin Kit
(PK100)
Tyco MKII Sounder Cap
A plastic cap which fits onto the
601SB/601SBD/602SB/602SBD
Sounder Base to enable these
bases to operate as a sounder
without fitting a detector.
Product Code
557.001.040
Mk 2 Sounder Cap pack of 5
MC600 Functional Relay Base
The 600 Series relay base provides
dual relay contacts for signalling
external devices on conventional
detection systems. Very low
operating current even when the
relay is energised, enable the relay
base to be used without additional
power. The relay contacts operate
when the detector enters the alarm
condition.
Features
• Dual pole 24Vdc relay contact
(60VA)
• Status indicator LED
• Low power consumption (<20μA
except start up)
• Latching operation
• Can be used instead of a standard base
• Requires diode fitting if used in
place of a diode base.
Technical Specification
Operating Temp:
-25°C to +70°C
Humidity:
Up to 95% RH
(noncondensing)
Vibration:
Exceeds
requirements of
EN54-3, Marine
& UL268
Product Code
568.001.018
MC600 Relay base (BS5839)
Volume Adjustment Tool
A simple Volume Adjustment Tool,
specific to the task of sounder
volume selection on the “variablevolume” range of Tyco MKII Sounder
Bases.
Sounder volume can be easily varied
between the maximum 90dBA and
minimum 68dBA volume settings,
using this simple, functional tool.
Product Code
517.050.015
Volume Adjustment Tool
Note: Sounder Bases are supplied
with the volume pre-set to maximum
volume.
03/17
Fire Catalogue
Chapter 3 Page 21
FIRE_Ch3_Conventional_Systems:Layout 1 02/05/2017 10:45 Page 22
Chapter 3 - Conventional Systems
Detector Base Ancillaries
Remote Indication LED
All detector bases have the ability to
drive a remote LED in the event that
the installed position of the detector
is not easily visible.
Features
• UK Single gang mounting
• High intensity red LED
Product Code
540.003.006
Remote LED
Features
• 2 x 18mm conduit entries
• 2 x 21mm conduit entries
• Fits all 4” Bases
• Accepts up to 8 accessory
terminals
Product Codes
517.050.052
4B-EM 4" Euro Mount
use the optional base accessory
terminal kit.
Product Codes
517.050.051
4B-DHM Deckhead Mount
4B-EM 4" Euro Mount
The euro-mounting base provides a
matching back box, which allows the
4” bases to be ceiling mounted with
conduit entries for standard 18 and
21mm conduit.
517.050.612
Base Accessory terminal kit
(pack of 10)
4B-DHM Deck Head Mounting
Where the detectors are mounted in
humid and environmentally
challenging situations such as
marine or offshore installations, the
4B-DHM deck head mount provides
a sealed waterproof mounting which
protects the electrical connections in
the base. Can be screwed, bolted /
welded to the deckhead. Supplied
with 1 terminal. If more are required,
Features
• 4 x 20mm gland entries
• Fits ALL 4” bases
• IP55 with supplied gasket
517.050.612
Base accessory terminal kit
(pack of 10)
Protective Detector Cage
Robust steel protective cage for
Series 600 detectors using the 5”
base. Ideal for schools and sporthalls
or whenever detectors need
protection.
Strong coated steel construction with
4 point fitting.
Product Code
517.050.614
CW-5B Detector Cage
Protective Detector/Sounder Base Cage
White powder coated steel protective
cage for Series 600 Detectors fitted
with a sounder base. Internal
dimensions: 120mm dia x 80mm
deep.
Chapter 3 Page 22
Product Code
517.050.011
Steel Protective Detector Cage
Fire Catalogue
03/17
FIRE_Ch3_Conventional_Systems:Layout 1 02/05/2017 10:45 Page 23
Chapter 3 - Conventional Systems
Duct Probes
SMP Duct Probe Units
Where smoke within duct work needs to be detected these
duct probe units provide an economical solution, for use
with series 600 detectors. .
The SMP Duct Probe Units are designed to be installed in
air conditioning supply and exhaust ducts for the purpose
of monitoring the airflow for smoke and combustion
products.
The SMP69 probe units are designed to accept and operate
with series 600 detectors. For general applications it is
recommended that photoelectric smoke detectors rather
than ionisation smoke detectors are used.
The SMP stainless steel probe unit is designed to withstand
the more demanding environments of the offshore oil and
gas industries.
Warning
Duct probe units sited in the common duct work to several extract grills
may fail to respond to smoke from any one extract due to the effect of
dilution. The SMP units will not respond to airflow of less than
1.5m/sec.
Technical Specification
Operating temperature:
-20°C to +70°C
Storage temperature:
-25°C to +80°C
Relative Humidity:
0 to 95%
SMP69
Stainless steel 316 housing
with transparent
polycarbonate cover
The units are designed to operate in airspeeds of 1.5 to 25
metres per second. A range of sampling tubes from 525mm
to 1575mm are available.
Height
Width
Length
Weight
SMP69
90mm
150mm
225mm
1.2Kg
SMP69 Duct Probe Air Sampling - Stainless Steel
Product Codes
517.025.035
SMP69 Stainless Steel Duct Probe
unit and universal detector base for
Series 600/800 Detectors.
517.025.028
DPS450 Probe tube stainless steel
450mm and exhaust
517.025.029
DPS600 Probe tube stainless steel
600mm and exhaust
517.025.030
DPS750 Probe tube stainless steel
750mm and exhaust
03/17
517.025.031
DPS900 Probe tube stainless steel
900mm and exhaust
517.025.032
DPS1200 Probe tube stainless steel
1200mm and exhaust
517.025.033
DPS1500 Probe tube stainless steel
1500mm and exhaust
Datasheet - Product Code PSF092
“SMP69 Duct Probe Unit”
Manual - Vol 01B-06-D1 “Detectors
Fire Manual
Fire Catalogue
Chapter 3 Page 23
FIRE_Ch3_Conventional_Systems:Layout 1 02/05/2017 10:45 Page 24
Chapter 3 - Conventional Systems
Features
• DPK6 for use with Generation6 multi-sensor
detectors 850PH and 830PH with built-in 4B-C
4” Continuity Base
• Designed to comply with prEN 54-27
• One-pipe air sampling system
• Patented venturi pipe and duct housing
• Test hole on cover
• Simple installation
• Simple service and maintenance
DPK6 Duct Probe
The DPK6 duct probe units have been developed to detect
smoke in ventilation ducts. They offer significant benefits in
terms of performance and installation. The system
comprises a single duct probe tube and housing specially
designed for optimum airflow through the smoke detector
and suitable for use in incoming, outgoing and circulation
air ducts of ventilation and conditioning systems. The duct
probes can operate across a wide range of airflow speeds
and are designed to comply with prEN 54-27 and VdS.
Unlike more traditional duct probe units that employ an inlet
and exhaust tube with sampling holes, the DPK6
unit uses a highly efficient single sampling tube that is
slotted along its length. This allows the sampling tubes to
be cut to the desired length whilst maintaining maximum
efficiency.
In order to reduce the time required to test the duct probe
detector during routine maintenance, an aperture is
provided that allows aerosol test gas to be directed at the
detector without having to dismantle the unit.
Accessories
Tyco Fire Protection Products offers 3 lengths of the duct
probe tubes. The tube is made of aluminium and can easily
be shortened to suit the span of the air duct. Where the
unit is mounted on insulated or circular air ducts, the DPK6MB mounting bracket is required.
Product Codes
517.025.056
517.025.058
517.025.059
517.025.060
517.025.061
517.025.055
Chapter 3 Page 24
Fire Catalogue
DPK6 Duct Probe with 4B-C 4” Continuity
Base
DPK6-60 - Duct Probe Tube 60 cm
DPK6-150 - Duct Probe Tube 150 cm
DPK6-280 - Duct Probe Tube 280 cm
DPK6-MB - Duct Pobe Mounting bracket
DPKF - Filter
03/17
FIRE_Ch3_Conventional_Systems:Layout 1 02/05/2017 10:45 Page 25
Chapter 3 - Conventional Systems
Callpoints
Features
•
•
•
•
•
•
Integral LED indicator for easy identification of operation
Surface or flush mounting
Extensive range of conventional callpoints
Test key facility, speeds maintenance visits
Optional transparent hinged cover
Hazardous areas models available (See Special Hazards
Section)
• IP67 Waterproof models for external applications
MCP Series Callpoints
A comprehensive range of callpoints for use with
conventional systems. All the callpoints are designed to
enable an alarm signal to be given by breaking a glass
element.
This operates a switch and is indicated by an LED indicator.
If required, an optional transparent hinged cover may be
installed to guard against accidental operation.
Technical Specification
(Indoor & Outdoor)
Housing:
Operating Temp:
Outdoor
Indoor
Relative Humidity:
PC/ABS
-30oC TO +70oC
-10oC TO +55oC
up to 95% RH (non-condensing)
Commonly Used Callpoints
Model
MCP200
MCP210
MCP230
MCP270
Keyswitch
Colour
Red
Red
Red
Yellow
White
Type
Conventional
Conventional
Conventional
Conventional
Conventional
IP Rating
24D
24D
67
24D
24D
Alert
Evacuate
Alert
Evacuate
R4/R1 Ohms
120/470
47/39
120/470
47/39
Not Applicable
Indoor & Outdoor MCP Callpoint
Indoor Callpoint
Weight: 110g
89mm
Outdoor Callpoint
Weight: 240g
27.5 mm
03/17
71 mm
84 mm
72 mm
93mm
93mm
97.5mm
Fire Catalogue
Chapter 3 Page 25
FIRE_Ch3_Conventional_Systems:Layout 1 02/05/2017 10:45 Page 26
Chapter 3 - Conventional Systems
Conventional MCP200 Callpoint
The MCP200 is a red indoor callpoint
with ‘alert’ resistors and LED
indicator. The MCP200 is LPCB
approved.
Product Codes
514.001.142.A
MCP200 without backbox-ADT
branded
514.001.142.T
MCP200 without backbox - Thorn
branded
514.001.142.Y
MCP200 without backbox - Tyco
branded
514.001.143.Y
MCP210 Tyco branded
514.001.160.Y
MCP211 Without backbox - Tyco
branded
514.001.160.A
MCP211 Without backbox - ADT
branded
514.001.160.T
MCP211 Without backbox - Thorn
branded
Conventional MCP210/MCP211 Callpoint
The MCP210 is a red indoor callpoint
with LED indicator and evacuate
resistors. The MCP210 is LPCB
approved and is supplied without a
backbox.
Product Codes
514.001.143.A
MCP210 ADT branded
514.001.143.T
MCP210 Thorn branded
The MCP211 is a red indoor callpoint
with evacuate resistors and LED
indicator. (For use with the
MZX-c Panels only).
Conventional MCP230 Callpoint
The MCP230 is a IP67 red outdoor
callpoint with“alert” resistors and
LED indicator and is LPCB approved.
Product Codes
514.001.110.A
MCP230 ADT branded
514.001.110.T
MCP230 Thorn branded
514.001.110.Y
MCP230 Tyco branded
Operation is by break glass. This call
point is semi flush mounted or can
be surface mounted using back box
515.001.021, and comes complete
with a test key.
Product Codes
2501012
Conventional Manual Call Point with
Glass Element (No Back Box).
515.001.021
BACK BOX FOR CALLPOINTS
This call point is surface mounted
and comes complete with back box
& test key.
Product Codes
509.030.117
T561 Extinguishant Release Manual
Callpoint
Operation is by break glass. This call
point is surface mounted and comes
complete with back box & test key.
Product Codes
509.030.119
Extinguishant Abort Manual Callpoint
button. This call point is surface
mounted and comes complete with
back box & test key.
Product Codes
509.030.121
Extinguishant Hold Manual Callpoint
Operation is by break glass. This call
point is surface mounted and comes
complete with back box & test key.
Product Codes
2501176
Conventional Weather Proof Manual
Call Point with Glass Element
Indoor Alarm Call Point
A manual alarm call point with
integral alarm LED and activation
resistor making it compatible
with the Prescient III Suppression
Panel.
Indoor Manual Release Call Point
A manual suppression release call
point with activation and end of line
resistors making it compatible with
the Prescient III Suppression Panel.
Operation is by break glass.
Indoor Abort Call Point
A manual abort call point with
activation and end of line resistors
making it compatible with the
Prescient III Suppression Panel.
Indoor Hold Call Point
A manual hold call point with
activation and end of line resistors
making it compatible with the
Prescient III Suppression Panel.
Operation is via a non-latching push
Outdoor Alarm Call Point
A weatherproof manual alarm call
point with integral alarm LED and
activation resistor making it
compatible with the Prescient III
Suppression Panel.
Chapter 3 Page 26
Fire Catalogue
03/17
FIRE_Ch3_Conventional_Systems:Layout 1 02/05/2017 10:45 Page 27
Chapter 3 - Conventional Systems
Outdoor Manual Release Call Point
A weatherproof manual suppression
release call point with activation and
end of line resistors making
it compatible with the Prescient III
Suppression Panel.
Operation is by break glass. This call
point is surface mounted and comes
complete with back box & test key.
Product Code
509.030.118
Extinguishant Release Weather Proof
Manual Call Point
This call point is surface mounted
and comes complete with back box
& test key..
Product Codes
509.030.120
Extinguishant Abort Weather Proof
Manual Call Point
Outdoor Abort Call Point
A weatherproof manual abort call
point with activation and end of line
resistors making it compatible
with the Prescient III Suppression
Panel. Operation is by break glass.
Other Conventional Callpoints & Keyswitches
Product Code
514.002.002.A
White keyswitch in callpoint housing.
English ‘Bomb Alert’ marking with
ADT branded
Special Marine Callpoints
Product Codes
514.001.112
MCP260M Marine callpoint complete
with LED indicator - IP67
514.001.113
MCP250M Marine callpoint complete
with LED indicator without back box
Callpoint Ancillaries
Product Codes
90-107
Red M141 spacer for red MCP KAC
callpoints
515.001.045
Test key for all MCP and CP style callpoints
515.001.128
Callpoint hinged cover for use with
MCP & CP style callpoint models
(Colour - Clear)
515.001.026
Black callpoint bezel for MCP KAC
callpoints
Ancillaries - Back Boxes
Product Codes
515.001.021
Standard Red surface mounting back
box for MCP & CP indoor callpoints
Unless stated the indoor callpoints are supplied
as flush mount units. The range is approved for
use with the standard backbox. However, the
SR2-T backbox is also available.
10-115
SR2-T Optional Back Box (2
terminals) for MCP & CP indoor
callpoints
03/17
Fire Catalogue
Chapter 3 Page 27
FIRE_Ch3_Conventional_Systems:Layout 1 02/05/2017 10:45 Page 28
Chapter 3 - Conventional Systems
Callpoint Spare Glasses - Current
Product Codes
515.001.119
EN54 Part 11 Spare Glass for MCP
and CP series Callpoints (Pack of 5)
515.001.025
CP200 Glasses, clear English text
on white background. No logo
(Pack of 5).
515.001.127
Deformable operating unit “glass”
for use in place of glasses, for
kitchens or other areas where glass
is not acceptable. For MCP
callpoints only.
515.001.024
CP200 spare glasses, black
Arabic/English text with Thorn
Security logo on white background
(Pack of 5)
515.001.014
CP200 Spare glasses, black Arabic
text on a white background
(Pack of 5)
515.001.023
CP200 Spare glasses for CP200
white dutch text on clear
background (Pack of 5)
Callpoint Spare Glasses - Old
Product Codes
515.001.010
Walsall callpoint glasses (Pack of 10)
for service spares. The Walsall
callpoint is an old square callpoint
with round glass
515.001.003
ZF121 Callpoint glass (Pack 10) for
service spares. The ZF121 is a
square metal fronted AFA MINERVA
callpoint typically used on Firefinder,
System 1100, ZF/System 1200, CP
and CT systems
515.001.009
CP100A glass unscored (Pack 10)
for service spares. The CP100A has
a large square glass to the edge of
the callpoint. Used on the same AFA
systems as the ZF121.
Chapter 3 Page 28
Fire Catalogue
03/17
FIRE_Ch3_Conventional_Systems:Layout 1 02/05/2017 10:45 Page 29
Chapter 3 - Conventional Systems
Features
• Prevents accidental operation of callpoints
• Strong polycarbonate construction
• Break Seal provided. (Use is optional)
UNIVERSAL STOPPER
The UNIVERSAL STOPPER provides protection from malicious
or accidental activation of manual callpoints. Available for flush
or surface mounted callpoints the UNIVERSAL STOPPER
is also available with optional high pitch sounder which is
activated when the lid is lifted.
WARNING:- Break Seals should only to be fitted by agreement
with relevant fire authorities.
The UNIVERSAL STOPPER is suitable for all callpoints up to
100 mm square.
A Break Seal is supplied with all models, to provide extra
protection if required.
Product Codes
515.001.033
515.001.034
515.001.035
Flush
STI-13110FR UNIVERSAL STOPPER
STI-13010FR UNIVERSAL STOPPER P
STI-13020FR UNIVERSAL STOPPER P
STI-13120FR UNIVERSAL STOPPER
STI-1100 STOPPER II
STI-1130 STOPPER II
STI-1200 STOPPER II
STI-1230 STOPPER II
STI-1250 WEATHER STOPPER II
P
STI-3150 WEATHER STOPPER II
UNIVERSALSTOPPER
UNIVERSAL STOPPER with Sounder
Max. Call point size
Max. Call point depth
03/17
Surface
P 37 mm
P
37 mm
P
50 mm
P
50 mm
P
50 mm
Flush kit
STI-13010FR
STI-13020FR
With sounder
P
P
P
P
96 dB
96 dB
96 dB
96 dB
IPO36 Break Seal Kit STI/BS - available in
packs of 10.
STOPPER II Surface - Red
Weather Stopper II Surf- Red
Weatherproof
P
P
P
P
P
P
Surface kit
STI-13110FR
STI-13120FR
UNIVERSAL STOPPER
StOPPER II
100 x 100 mm
160 x 160 mm
57.5
120
(add 37 mm surface)
Fire Catalogue
Chapter 3 Page 29
FIRE_Ch3_Conventional_Systems:Layout 1 02/05/2017 10:46 Page 30
Chapter 3 - Conventional Systems
Features
• Strong polycarbonate construction
• Tamper resistant
STOPPER II
The STOPPER II is constructed from tough UV stabilised
polycarbonate. Physically larger than the UNIVERSAL
STOPPER the STOPPER II extends the number of products
to which these tough multi-purpose covers can protect.
STOPPER II can also be fitted with an integral battery
powered sounder which activates if the cover is lifted.
The STOPPER II is suitable for callpoints up to 160 mm
square.
It consists of a strong tamper-proof clear polycarbonate
cover and frame that fits easily over such products as break
glass callpoints.
Product Code
515.001.034
STOPPER II Surface - Red
Features
• Strong polycarbonate construction
• Provides environmental protection
• Ideal for indoor/outdoor applications
UNIVERSAL STOPPER & WEATHER STOPPER II
The UNIVERSAL STOPPER and WEATHER STOPPER II
extends the life of weather exposed devices, such as
break glass callpoints, by offering protection against harsh
conditions and environments. Experience has shown that
this protective cover can extend the life of products
installed in saline atmospheres, such as oil rigs and ship
decks.
While offering environmental protection the UNIVERSAL
STOPPER and WEATHER STOPPER II are constructed
from tough UV stabilised polycarbonate which will also
guard against tampering, vandalism or accidental operation
of devices such as emergency switches.
Product Codes
STI-13110FR
515.001.035
Chapter 3 Page 30
Fire Catalogue
UNIVERSAL STOPPER Surface Red
WEATHER STOPPER II Red
03/17
FIRE_Ch3_Conventional_Systems:Layout 1 02/05/2017 10:46 Page 31
Chapter 3 - Conventional Systems
STOPPER II Dimensions
76 mm
81 mm
70 mm
102 mm
50 mm
127 mm
41 mm
140 mm
19 mm
STI-3100 spacer adds
50 mm depth for surface
mounted division
140 mm
Depth Chart
Cover
Cover
140 mm
166 mm
81 mm
81 mm
190 mm
165 mm
Cover
76 mm
127 mm
Spacer
216 mm
51 mm
Side View with sounder
Spacer
216 mm
51 mm
Spacer
140 mm
81 mm
51 mm
Side View without sounder
Devices to be protected
Removable plastic insert
50 mm conduit spacer for
surface mounting
Optional sounder
Cover
Rawl plug 4 provided
Screws 4 provided
Optional backplate for
irregular surfaces
Mounting frame
UNIVERSAL STOPPER Dimensions
64 mm
Without label
hood 162 mm
138 mm
64 mm
Without label
138 mm
hood 162 mm
138 mm
116 mm
35 mm
Locking Tab
Flush side view
Smoke Beam/CCTV Guard
The Smoke Beam/CCTV Guard is
manufactured from tough coated
steel rod and is designed to protect
projected beam detectors or CCTV
cameras from vandalism or
accidental damage.
Suitable for use with System Sensor,
Hochiki and Fireray 2000 detectors.
Product Code
516.015.009
STI9625 Smoke beam/CCTV guard
Technical Specification
Dimensions:
260H x 200W x
321D mm
Keybox
This tough polycarbonate breakglass
keybox is available to protect
emergency keys.
03/17
Product Code
515.001.043
STI6720 Keybox with printed glass
Fire Catalogue
Chapter 3 Page 31
FIRE_Ch3_Conventional_Systems:Layout 1 02/05/2017 10:46 Page 32
Chapter 3 - Conventional Systems
Sounders and Beacons
Features
•
•
•
•
•
•
•
•
•
Wide range of both bells and electronic sounders
High sound output characteristics
Low current consumption
Clean lines, modern styling
Easy to install, low installation costs
Weatherproof units for outdoor use
Distinct sounds are available
Motorised and Solenoid bells available
Wide range of voltages available
Sounders
A range of sounders to meet a wide variety of alarm
applications where loud, penetrating and distinctive
warnings must be given to alert people of fire situations.
In addition, multitone electronic sounders can give a variety
of sounds to signal other conditions e.g.“extinguishing gas
release imminent,” etc.
Note: For I.S. & Flameproof sounders, please see the special hazards section.
Bells
Features
•
•
•
•
•
•
•
•
CE marked
Low current 6” bell (ONLY 11mA)
Low cost
Extra high 95dBA/m
Slim profile (53mm)
Fully suppressed and polarised
Quick and easy to install
LPCB approved to EN54 Pt 3
6” & 8” Motorised Bells
Product Codes
Model
MBF-6EV
MBF-8EV
MBA 8EV
Rated Voltage 24V d.c.
24V d.c.
24V d.c.
Rated Current
11mA
17mA
18mA
Sound output 90-95dBA
90-97dBA
91-97dBA
Operating Temp
-12 to +50°C
-10 to +50°C
Colour
Red
Weight
410g
640g
1100g with back box
576.501.039.A
576.501.039.T
576.501.040.A
576.501.044.A
576.501.044.T
576.501.045
Chapter 3 Page 32
Fire Catalogue
MBF-6EV ADT Branded
MBF-6EV Thorn Branded
MBF-8EV ADT Branded
MBA-8EV ADT Branded
MBA-8EV Thorn Branded
BBX4 (2) W/P Backbox for MBA-8 Bell
03/17
FIRE_Ch3_Conventional_Systems:Layout 1 02/05/2017 10:46 Page 33
Chapter 3 - Conventional Systems
Features
• Weatherproof Option
• Flexible Mounting Option
• Attractive Design
Electronic Solenoid Bell
Unique patented alarm bell with miniature solenoid and
integrated electronic control. No backbox required for
surface wiring.
Technical Specification
Product Codes
Dimensions:
Voltage:
Typical Current:
Typ. Sound Output:
20-100 6” 24Vdc Electronic bell, weatherproof IP33C Wormald Branded
20-101 6” 24Vdc Electronic bell - red IP21C - Wormald
Branded
20-111 6” 24Vdc Electronic bell - white IP21C
6” diameter
18-30Vdc
30mA @ 24Vdc
94dB (A) @ 1m
Marine Approved Products
576.501.407
MED 6” 24Vdc Electronic bell,
weatherproof - red IP33C
576.501.408
MED 6” 24Vdc Electronic bell-red IP21C
Features
• Low Current Consumption
• Suppressed and Polarised
• Sturdy Construction
CF Motorised Bell
The CF Motorised Bell is low current, fully suppressed and
polarised.
Technical Specification
Product Code
Dimensions:
Colour:
Output Voltage:
Typical Current:
Typical Sound Output:
Marine Approved Product
03/17
6” Diameter
Red
20-28Vdc
25mA @ 24Vdc
95dB (A) @ 1m
576.501.405
Fire Catalogue
MED 6” Red 24Vdc Motorised bell, “Fire”
text with Thorn Branding
Chapter 3 Page 33
FIRE_Ch3_Conventional_Systems:Layout 1 02/05/2017 10:46 Page 34
Chapter 3 - Conventional Systems
Electronic Sounders
Features
•
•
•
•
•
•
•
•
•
•
Modern aesthetic design
32 Selectable tones
3 Volume settings
Push and twist mount
Shallow and deep bases
Available in red or white
Low current consumption
2 Stage alarm available
Independently switched sounder or beacon
Xenon beacon with the Excel Lite
Banshee Excel Sounders
Banshee Excel Lite Sounder Beacon
The Banshee Excel sounder replaces the Banshee Multi
Tone range of Sounders. It uses the same technically
superior rocking arm transducer to reproduce the familiar
32 tones of the previous Banshee and Bedlam ranges.
The new Banshee Excel adds the Banshee Excel Lite
Sounder Beacon to its range using a high output xenon
with the familiar sounder. The Banshee Excel Lite can be
used as a multi stage device by switching the beacon and
the sounder independently using a third wire.
Technical Specification
Product Codes
Approvals:
VdS approved to EN54-3
Tones available:
32
Operating voltage:
9-30Vdc
Tone current consumption: See Tone Table in Chapter 11
Flash current consumption: 40mA
Operating temperature range (Deg C): -40 to +70
Volume control via DIL switch: Maximum, Medium (-10dBA),
Low (-20dBA)
Flash rate per second:
1
Ingress Protection:
IP45 or IP66
Termination:
Screw terminals for 0.8mm2 to
2.5mm2 wire conductor
576.501.060
Chapter 3 Page 34
576.501.061
576.501.062
576.501.063
Fire Catalogue
Banshee Excel sounder, red, IP45
(replaces 576.501.005.A & 576.501.005.T)
Banshee Excel sounder, white, IP45
(replaces 576.501.009 & 576.501.025.A)
Banshee Excel sounder, red, IP66
(replaces 576.501.016.A & 576.501.016.T)
Banshee Excel Lite, red sounder, red
xenon beacon, IP45
03/17
FIRE_Ch3_Conventional_Systems:Layout 1 02/05/2017 10:46 Page 35
Chapter 3 - Conventional Systems
Accessories
The combined mounting bracket for
the Besson Multi-tone Banshee and
Xenon Beacon allows quick and
neat installation of combined
sounders and beacons. The
bracket allows the following
electronic sounders to be mounted
with the range of 1W Xenon
Beacons:
• Besson Banshee
• MINERVA FIRECRYER voice
enhanced sounder
The bracket can be used with any of
the 24Vd.c 1W Xenon beacons in
red, clear, amber or blue (Part no.'s
LPB24-C-T/LPB24-B-T/LPB24-A-T &
LPB24-R-T)
Product Code
576.501.047
Banshee/Xenon bracket
This versatile range of sounders are
ideally suited for fire, safety and
security hazard warning.
Approvals
EN54-3:2001+A1:2002 + A2 :2006
Vds 2504 (12/96), Vds 2203 (03/01),
Vds 2344 (12/05), Cert No. G28702
Marine Equipment Directive MED
Module B BSI/MED/A.
1/3.53/590299, Module D
BSI/MED/PC/590302
Technical Specification
Dimensions:
YO3:
89H x 89W x 85D mm
YO5:
134H x 134W x 128D mm
YO8:
216H x 216W x 153D mm
Product Codes
YA30/D/RF/WR
Sounder YA30 100 dB 24 VDC IP65
YA50/D/RF/WR
Sounder YA50 110dB 24 VDC IP65
YA80/D/RF/WR
Sounder YA80 115dB 24 VDC IP65
Yodalarms
03/17
Fire Catalogue
Chapter 3 Page 35
FIRE_Ch3_Conventional_Systems:Layout 1 02/05/2017 10:46 Page 36
Chapter 3 - Conventional Systems
24Vdc Symphoni Sounder
The 24Vdc Symphoni Sounder is a
general purpose internal sounder,
available either as a very high output
sounder for noisy areas, or a high
output low current sounder for
applications where power is limited.
Both versions share the same horn
and backbox which has double
cable entries for ease of installation.
The low power version has 3
selectable tones which may be
employed for one, two or three stage
alarm applications. The high output
version has 32 selectable tones and
retains full tone compatibility with the
Roshni, Squashni and Askari product
ranges.
Product Codes
576.501.200
SY/R Low Power Red Symphoni
Sounder (3 tone)
576.501.201
SY/W Low Power White Symphoni
Sounder (3 tone)
576.501.202
SYHO/R High Output Red Symphoni
Sounder (32 tone)
576.501.203
SYHO/W High Output White
Symphoni Sounder (32 tone)
Technical Specification
Model
Operation
Operating Voltage Range
Sound Output @ 1m
Volume Control
Current Consumption
Tones
Symphoni High Output
2 Hours Continuous
9-28Vdc
Up to 120dB(A)
Synchronisation
Frequency Stability
Operating Temperature
Line Monitoring Method
Construction
Ingress Protection
Weight
Synchronised Start
+/- 0.15%
-25 °C to + 55°C
Polarised Input
ABS Plastic Case
IP21C
0.58Kg
240mA +/- 20mA on Tone 3
1 to 32
Symphoni (Low Power)
Continuous
12-30Vdc
100dB(A) +/- 2dB(A) @ 24Vd. c.
Down to 80dB approx.
5mA +/- 1mA at all volumes
Alternating 990Hz/[email protected] 2Hz
Continuous 990Hz
Intermittent 990Hz, On/Off @ 1Hz
Synchronised Start
+/- 0.5%
-25°C to +70°C
Polarised Input
ABS Plastic Case
IP21C
0.212Kg
Roshni
A flexible alarm sounder for Fire and
Security applications complete with
volume control and dil switch to
provide 32 tones.
Low profile Roshni with Deep base
offers IP65 protection. All Roshni
sounders have synchronised start for
self synchronisation without third
wire.
Chapter 3 Page 36
Technical Specification
Dimensions:
93 Dia x
105D mm
(Deep base)
Colour:
Red or white
Output Voltage:
9-28Vdc
Typical Current:
16mA @ 24Vdc
Typ. Sound Output: 102dB @ 1m
Fire Catalogue
Product Codes
ROSHRDSR
ROSHNI Sounder c/w deep base red
576.501.220
ROSHNI Sounder c/w shallow base
- red
576.501.221
ROSHNI Sounder c/w shallow base
- white
576.501.222
ROSHNI/Flashni Deep Base - Red
576.501.223
ROSHNI/Flashni Deep Base - White
03/17
FIRE_Ch3_Conventional_Systems:Layout 1 02/05/2017 10:46 Page 37
Chapter 3 - Conventional Systems
Squashni
The Squashni electronic sounder is
the original ceiling sounder for use
as a universal fire detector platform
or as a stand alone sounder
complete with blank cover. It comes
preset to tone 3 with a volume
control and is fully compatible with
Roshni tones, and has a
synchronised start.
Technical Specification
Dimensions:
112 Dia x 27D mm
Colour:
Matched to
leading fire
detector
manufacturers
Approvals:
None
Output Voltage: 9-28Vdc
Typical Current: [email protected]
Typ. Sound Output: @1m 93dB (A)
Product Codes
576.501.030
Squashni white 24Vdc
576.501.031
Blank cover plate white for Squashni
Technical Specification
Dimensions:
87.5H x 87.5W
x 36D mm
Colour:
Red or white
Product Codes
576.501.242
Multi Tone Askari Compact
Sounder - white
576.501.243
Multi Tone Askari Compact
Sounder - red
Multi-Tone Askari Compact
The Multi-Tone Askari Compact is a
compact bedroom sounder for
unobtrusive installation. It comes
with a volume control and is fully
compatible with Roshni tones and
has a synchronised start. A surface
mount backbox is available from the
supplier to special order.
03/17
Approvals:
Input Voltage:
Typ. Current:
Typ. Sound Output:
Fire Catalogue
BS 5839 pt 1
9-28Vdc
18mA @ 24Vdc
97dB (A) @1m
Chapter 3 Page 37
FIRE_Ch3_Conventional_Systems:Layout 1 02/05/2017 10:46 Page 38
Chapter 3 - Conventional Systems
Features
• Single Message or Multiple Message using the same
sounder
• Multi Message facilitates multi evacuation strategies
• Clear and unambiguous alarm messages
• Voice Alarm Messages provoke an immediate response
• Sound Output – Up to 100db(A) (Fire-Cryer® Plus),
90db(A) (Mini Fire-Cryer® Plus), 110db(A) (Midi FireCryer® Plus)
• Optional integral Red Strobe
• Low current consumption – average 20mA
• No special wiring easily retro fitted
• Fully synchronised over multi zones
• Deep base version available to IP66
• Ultra slim base sounder to fit industry standard detectors
• Suitable for ceiling or wall mounting (Mini Fire-Cryer®
Plus)
• Optional front plate for stand alone use (Mini Fire-Cryer®
Plus)
• Voice Message Controller makes manual message
switching easy
Fire-Cryer Plus® - Voice Enhanced Sounders
The Fire-Cryer® Plus range of voice sounders are electronic
sounders which are pre-programmed with 9 messages.
Each of the Fire-Cryer® voice sounders can be used as a
single message voice sounder by simply installing them on
to a conventional 24Vdc sounder circuit or by using a
sounder controller on a loop. The choice of message(s)
broadcast can be selected using a DIL switch on the rear of
the sounder. See Table A
A special Extinguishing PCB (576.501.173) used with the
576.501.135 will enable 1st, 2nd Stage, ‘Hold’ and ‘Gas
Released’ messages to be automatically broadcast
dependent on the state of the alarm. See Table A1
The Fire-Cryer® Plus offers an excellent service upgrade
opportunity for systems as well as a highly flexible and cost
effective solution to providing a voice evacuation system to
many buildings. The choice of Fire-Cryer® voice sounders
can be selected using Table B
Messages 1 to 7 in Table A can be used in a multi
message installation with the addition of a Multi Message
Switching PCB (576.501.171) or a Voice Message
Controller (576.501.181 or 576.501.182) interfaced between
the fire alarm control panel and the sounder circuits. The
Voice Message Controllers can be supplied with a 2.5A or
5.25A power supply built in. A Zone Extension PCB
(576.501.172) is available to extend the system to 4 zones
or 8 sounder circuits. See Table C
Chapter 3 Page 38
Fire Catalogue
03/17
FIRE_Ch3_Conventional_Systems:Layout 1 02/05/2017 10:46 Page 39
Chapter 3 - Conventional Systems
Fire-Cryer® Plus Multi Message PCB
Product Code
576.501.171
Fire-Cryer® Plus Multi Message PCB
Fire-Cryer® Plus Zone Extension PCB
Product Code
576.501.172
Fire-Cryer® Plus Zone Extension PCB
Fire-Cryer® Plus Extinguishing PCB
Product Code
576.501.173
Fire-Cryer® Plus Extinguishing PCB
Din Rail Mounting Kit for Fire-Cryer® Plus Extinguishing PCB
Product Code
557.201.303
Din Rail Mounting Kit
IP66 Housing for Fire-Cryer® Plus Extinguishing PCB
Product Code
557.201.410
IP66 Housing
VMC / Multi Message PCB and 2.5A PSU
Product Code
576.501.181
VMC / Multi Message PCB and 2.5A PSU
VMC / Multi Message / Zone Extension PCB and 5.25A PSU
Product Code
576.501.182
03/17
VMC / Multi Message / Zone Extension PCB and 5.25A PSU
Fire Catalogue
Chapter 3 Page 39
FIRE_Ch3_Conventional_Systems:Layout 1 02/05/2017 10:46 Page 40
Chapter 3 - Conventional Systems
Technical Specification
Fire-Cryer® Plus Model
Fire-Cryer® Plus
VDC Operating Voltage
20-28
Current mA @ 24VDC Peak/Avg - Sounder only
27/20
Current mA @ 24VDC Typical: Sounder with low current strobe
33/26
Current mA @ 24VDC Typical: Sounder with high current strobe
52/60
Current mA @ 24VDC Low current strobe only
13
Current mA @ 24VDC High current strobe only
32
Strobe Output Cd (LOW)
2
Strobe Output Cd (HIGH)
6
Volume Adjustment from Max. dBA Output to max output -18dBA
82 to 100
Weatherproofing (IP66 requires Deep Base)
IP45 or IP66
Housing Material
ABS
Temperature Range °C
Colour
Connections
Chapter 3 Page 40
Midi
20-28
180/100
n/a
n/a
n/a
n/a
n/a
n/a
101 to 110
IP44
Aluminium/
Plastic Base
-25 to +70
-10 to +55
-25 to +70
Red or White
White
Red
Screw TB 1.5mm² Screw TB 1.5mm² Clamp 2.5mm2
Fire Catalogue
Mini
20-28
27/20
n/a
n/a
n/a
n/a
n/a
n/a
72 to 90
n/a
ABS
03/17
FIRE_Ch3_Conventional_Systems:Layout 1 02/05/2017 10:46 Page 41
Chapter 3 - Conventional Systems
Standard Message Set which consists of 9
pre-programmed messages with tones (See Table A)
When used as a Multi Message sounder DIL Switches 4,
5, 6, 7 and 8 are OFF. When used as a single messa
sounder use the DIL Switch settings in the table below 1
= ON, 0 = OFF
When used as a Multi Message Sounder the Multi Message Switching
PCB (576.501.171) will assign the messages to the following triggers:
Beacon Flashes Y/N
SW5
SW6
SW7
SW8
Speech Message
SW4
Two Letter Message Code
Starting Tone (See Table (A2) below)
Table A
Message 1 1 AK Y Fire emergency. Please remain calm and evacuate the building immediately S1A/S1B 1
Message 2 2 AB Y This is a fire alert. This is a fire alert. Await further instructions.
Await further instructions.
MA
0
Message 3 2 MA Y Standby alert. Close all blinds and move to the middle of the room.
MB
1
Message 4 0 AD N All clear. All clear. No further action required.
MC
0
Message 5 0 SP N This is an ADT fire test. No action required.
MD
1
Message 6 3 CC N This is a class change announcement.
ME
0
Message 7 1 AF Y Fire detected. Keep calm. Leave the building by the nearest exit.
MF
1
Message 8 2 AZ Y Ladies and gentlemen – due to unforeseen circumstances we
must ask you to leave the building immediately by the nearest exit
or as directed by members of staff.
0
Message 9 2 AX Y We have an emergency situation. Please leave the building by the
nearest exit. Members of staff will assist you.
1
0
0
0
0
1
1
0
0
1
1
0
0
1
1
1
1
0
0
0
0
0
0
0
0
0
0
0
0
0
0
1
0
0
0
1
0
Table A1
Table A2
Tone
0
1
2
3
03/17
Two Letter Message Code
Beacon Flashes Y/N
1st Stage
2nd Stage
Hold
Gas Released
Starting Tone (See Table (A2) below)
GAS EXTINGUISHANT MESSAGES (Used with 576.501.135)
2
2
0
1
CG
CH
LU
CJ
Y
Y
N
Y
Speech Message
First stage extinguishant release warning.
Second stage extinguishant release warning.
Extinguishant gas release on hold.
Extinguishant released.
No tone
Banshee LF Fast Sweep. 800Hz to 950Hz swept @ 9hz
Banshee LF Fast Sweep. 800Hz to 950Hz swept @ 9hz Pulsed at 1 second ON, 1 second OFF
Bell tone, pulsed
Fire Catalogue
Chapter 3 Page 41
FIRE_Ch3_Conventional_Systems:Layout 1 02/05/2017 10:46 Page 42
Chapter 3 - Conventional Systems
Ordering Fire-Cryer Plus® Voice Sounders
Step 1 - Choose your Fire-Cryer® Sounder
Table B
Type
Wall Mount
Body Colour Beacon
Red
Red
None
Red
None
Red
Base
Shallow
Deep
Shallow
Deep
Shallow
Shallow
Shallow
Part Ref.
576.501.131
576.501.132
576.501.133
576.501.134
576.501.141
576.501.142
576.501.135
Wall Mount
White
Wall Mount
Red
Wall Mount
Red
None
Deep
576.501.151
Base Mount
White
None
n/a
576.501.161
Step 2 - Choose your Interfaces for Multi Message Systems
Table C
Standard Multi Message Switching PCB
Zone Extension PCB (adds 3 Zones of 2 Sounder Circuits i.e. 6 sounder circuits.
Must be used with 576.501.171)
Extinguishant Interface PCB
576.501.171
576.501.172
576.501.173
Voice Message Controllers & PSUs (All VMC enclosures include a 576.501.171)
576.501.171
576.501.172
PSU
Box Size
Part Ref
Yes
No
2.5A
M2
576.501.181
Yes
Yes
5.25A
M3
576.501.182
Box Sizes
M2 Enclosure 385W x 310H x 90D mm
M3 Enclosure 385W x 520H x 90D mm
Product Codes
576.501.131
576.501.132
576.501.133
576.501.134
576.501.135
576.501.141
576.501.142
576.501.151
576.501.161
576.501.052
576.501.171
576.501.172
576.501.173
557.201.303
557.201.410
576.501.181
576.501.182
576.501.191
Standard Fire-Cryer® Plus, red wall mounted, shallow base, red beacon
Standard Fire-Cryer® Plus, red wall mounted, deep base, red beacon
Standard Fire-Cryer® Plus, red, wall mounted, shallow base
Standard Fire-Cryer® Plus, red, wall mounted, deep base
Standard Fire-Cryer® Plus (for use with 576.501.173 in Gas Extinguishant systems)
Standard Fire-Cryer® Plus, white wall mounted, shallow base, red beacon
Standard Fire-Cryer® Plus, white, wall mounted, shallow base
Midi Fire-Cryer® Plus, c/w back box, red
Mini Fire-Cryer® Plus, base mounted, white, c/w cover
Mini Fire-Cryer® Plus, voice enhanced base sounder cable spacing ring
Fire-Cryer® Plus Multi Message PCB
Fire-Cryer® Plus Zone Extension PCB
Fire-Cryer® Plus Extinguishing PCB
Din Rail Mounting Kit for Fire-Cryer® Plus Extinguishing PCB
IP66 Housing for Fire-Cryer® Plus Extinguishing PCB
Voice Message Controller c/w Multi Message PCB and 2.5A PSU
Voice Message Controller c/w Multi Message PCB, Zone Extension PCB and 5.25A PSU
Fire-Cryer® Plus Demo Unit
Please Note:
The beacon in this product should be used for supplementary indication purposes only. In this case the
device is not required to be used as a Visual Alarm Device(VAD) and EN54-23 is not relevant to its classification.
Chapter 3 Page 42
Fire Catalogue
03/17
FIRE_Ch3_Conventional_Systems:Layout 1 02/05/2017 10:46 Page 43
Chapter 3 - Conventional Systems
Beacons
Single Gang Lamp/Buzzer Units
Lamp Buzzer units may be used for
local alarms when high level audible
warnings may not be appropriate.
Available in flush and surface mount
versions to fit standard single gang
backboxes.
Technical Specification
90H x 90W
Dimensions:
x 40D mm
15mA at 24Vdc
Current Rating:
nominally
Features
• Low Current
• Flush or Surface Mount
• Hi-Brightness LED
Product Codes
540.011.012
Single gang flush mount LED
(red)/Buzzer Unit labelled ‘Fire
Alarm’
540.011.013
Single gang surface mount LED
(red)/Buzzer Unit labelled ‘Fire
Alarm’ c/w surface backbox.
Solista LED Beacon
Ultra low power requirement 3mA
or 6mA at 24Vdc. Long life low
profile design. Protected to IP54,
supplied complete with base.
Product Code
576.501.230
Solista LED Beacon (Red)
Please Note:
The beacon in this product
should be used for
supplementary indication
purposes only. In this case the
device is not required to be
used as a Visual Alarm
Device(VAD) and EN54-23 is
not relevant to its classification.
Easy AVTM Retrofit LED Beacon
Product Code
576.501.012
Easy AV strobe for Banshee
Sounders
This low power LED beacon is
designed to be retrofitted to existing
Banshee electronic sounders. Easy
and fast installation typically 3 min.
Low power 6mA max at 24Vdc.High
Output LEDs.
NOTE: For I.S. Flameproof Beacons, please see the special hazards section.
03/17
Fire Catalogue
Please Note:
The beacon in this product
should be used for
supplementary indication
purposes only. In this case the
device is not required to be
used as a Visual Alarm
Device(VAD) and EN54-23 is
not relevant to its classification.
Chapter 3 Page 43
FIRE_Ch3_Conventional_Systems:Layout 1 02/05/2017 10:46 Page 44
Chapter 3 - Conventional Systems
Features
•
•
•
•
•
•
•
•
•
•
•
Uses efficient LED technology
Low profile design (44 mm)
Twin thread mount
Low current operation
Maximum light intensity and dispersion
Compatible with a wide range of systems
IP66 rated
Fresnel Lens
Polycarbonate and ABS construction
Choice of coloured lenses: Amber, Blue, Clear or Red
Suitable for fire alarm VID applications
24 V LED Beacons
A range of cost effective, low profile, high efficiency LED
beacons with a variety of lens colour options. They are
designed for use as visual indicator devices (VID).
Technical Specification
Product Codes
Rated Voltage
Current Consumption:
LPB24-C-T
LPB24-B-T
LPB24-A-T
LPB24-R-T
12 V dc / 24 V dc
80 mA - 12 V dc
30 mA - 24 V dc
Operating Temperature: -10 to 50°C
Product Dimensions
73 mm Diameter x 44 mm Height
Material
Base:
ABS
Lens:
Acrylic / Polycarbonate
Colour
Base:
Black
Lens:
Amber, Blue, Clear and Red
24 V DC LED Strobe Clear lens
24 V DC LED Strobe Blue lens
24V DC LED Strobe Amber lens
24 V DC LED Strobe Red lens
Please Note:
The beacon in this product should be used for supplementary
indication purposes only. In this case the device is not
required to be used as a Visual Alarm Device(VAD) and EN54
23 is not relevant to its classification.
Features
•
•
•
•
•
•
•
High Power – 10 Candela
Current Surge Suppression
High Efficiency – 88mA at 24VDC
1 Hz Flash Rate
Protected to IP54
Wide Operating Voltage – 10 to 60 VDC
Operating Temperature -25oC to + 70oC
Solex 10 cd Xenon Beacon
Product Code
A Solex 10 Candela Xenon Beacon with a red lens and a
white shallow base which can be used wherever a high
power xenon beacon is required.
576.501.232
Due to the high power output and current consumption it is
recommended that this device is not used with the MZX-c,
MZX-c+ or similar small panels (an SB520 sounder booster
module and PSU may be required in some cases).
Chapter 3 Page 44
Solex 10 cd Beacon with red lens and
white base
Please Note:
The beacon in this product should be used for supplementary
indication purposes only. In this case the device is not
required to be used as a Visual Alarm Device(VAD) and EN54
23 is not relevant to its classification.
Fire Catalogue
03/17
FIRE_Ch3_Conventional_Systems:Layout 1 02/05/2017 10:46 Page 45
Chapter 3 - Conventional Systems
Features
• Combined strobe & sounder
• Matches Roshni sounders
• Weather Resistant to IP65
Flashni - Sounder/Strobe
A combined sounder and beacon which combines the
features of the Roshni electronic sounder with a fully
integrated Xenon beacon.
These sounders are fully compatible with all Roshni tones.
Technical Specification
Product Codes
Dimensions:
20-118
Input Voltage:
Typical Current:
Typ. Sound Output:
93 Dia x 92D mm
(Shallow base)
93 Dia x 121D mm
(Deep base)
18-30Vdc
[email protected]
101dB (A)@1m
576.501.224
576.501.227
Combined Roshni sounder/strobe
complete with deep base (IP65).
Combined Roshni Sounder/Strobe, Red
Body/Red Lens complete with shallow
base & tone switch.
Combined Roshni Sounder/Strobe, Red
Body/Red Lens, deep base, tone switch
& separate sounder/strobe operation.
Please Note:
The beacon in this product should be used for
supplementary indication purposes only. In this case the
device is not required to be used as a Visual Alarm
Device(VAD) and EN5423 is not relevant to its classification.
03/17
Fire Catalogue
Chapter 3 Page 45
FIRE_Ch3_Conventional_Systems:Layout 1 02/05/2017 10:46 Page 46
Chapter 3 - Conventional Systems
Service & Spares
T1200 CONVENTIONAL MARINE PANEL
MZX-e EXTINGUISHING PANEL
C1626 4 ZONE PANEL MOTHERBOARD WITH AC PSU
(509.023.001)
C1626 4 ZONE PANEL MOTHERBOARD WITHOUT AC
PSU
(509.023.002)
C1627 16 ZONE PANEL MOTHERBOARD WITHOUT AC
PSU (509.023.003)
C1627 16 ZONE PANEL MOTHERBOARD WITHOUT AC
PSU FOR T1232 (509.023.004)
C1626 REPEATER MOTHERBOARD WITH AC PSU
(509.023.011)
C1626 REPEATER MOTHERBOARD WITHOUT AC PSU
(509.023.012)
C1628 4 ZONE PANEL DISPLAY PCB (509.023.021)
C1628 16 ZONE PANEL DISPLAY PCB (509.023.022)
C1629 32 ZONE PANEL DISPLAY PCB (509.023.023)
C1628 16 ZONE REPEATER DISPLAY PCB (509.023.031)
C1629 32 ZONE REPEATER DISPLAY PCB (509.023.032)
C1630 OUTPUT EXPANSION INTERFACE PCB (2605060)
C1632 16 ZONE PANEL EXPANSION PCB (509.023.042)
PS136 5.0 AMP 110/230VAC PSU (509.023.051)
PS40 1.5 AMP 24VDC PSU (509.023.052)
T1200 & T1200-C SPARE KEY SET (509.023.061)
MZX-e SPARE KEY SET (557.201.508)
EXTINGUISHING ANCILLARIES
LAMP 28V 60mA (MCC) FOR T525 (599.001.012)
24V5WSBC SP BULB FOR E1/E3 (599.001.029)
MANUAL ALARM CALLPOINTS
ZF121 CALLPOINT GLASS (PK10) (515.001.003)
CP100A CALLPOINT GLASS UNSCORED (PK10)
(515.001.009)
WALSALL CALLPOINT GLASS (PK10) (515.001.010)
CP200 CALLPOINT GLASS-ARABIC (PK5) (515.001.014)
CP200N CALLPOINT GLASS (PK5) (515.001.023)
CP200 CALLPOINT ARABIC/ENGLISH GLASS (PK5)
(515.001.024)
CP200 CALLPOINT ENGLISH GLASS NO LOGO (PK5)
(515.001.025)
STOPPER BREAK SEAL KIT-RED (PK1) (515.001.033)
MCP/CP CALLPOINT TEST KEY (PK1) (515.001.045)
MCP/CP CALLPOINT EN54 PT11 SPARE GLASS (PK5)
(515.001.119)
DEFORMABLE MCP ELEMENT (PK1) (515.001.127)
MZX-c CONVENTIONAL PANEL
2 ZONE 2 WIRE MZX-c MOTHERBOARD (2605508)
4 ZONE 2 WIRE MZX-c MOTHERBOARD (2605509)
8 ZONE 2 WIRE MZX-c MOTHERBOARD (2605510)
MZX-c MOTHERBOARD 8 ZONE REPEATER (2605505)
MZX-c POWER SUPPLY (BAQ35T-24)
MZX-c SPARE ENABLE KEY (2501061)
MZX-c ZONE EOL UNIT - PK5 (2605538)
MZX-c+ CONVENTIONAL PANEL
MZX-c+
MZX-c+
MZX-c+
MZX-c+
MZX-c+
SPARE KEY SET (557.201.508)
5.0 AMP PSU - C1652 (2605071)
TRANSFORMER 1.5 AMP (2000636)
TRANSFORMER 3.0 AMP (2000637)
TRANSFORMER 5.0 AMP (2000638)
Chapter 3 Page 46
Fire Catalogue
03/17
FIRE_Ch4_Networks_and_Graphics:Layout 1 01/04/2015 14:15 Page 1
Chapter 4 - Networks and Graphics
Tyco Expert Graphics (TXG)
Features
• Provides annunciation, status display, and control in
both normal and emergency situations
• Developed by Tyco specifically to provide monitoring
and control of fire protection life safety systems
• Supports a range of fire detection systems:Minerva® MX and MZX Minerva® Simplex 4100 range
4100, 4120,4020,4100U with upgrade paths to 2120
Zettler Zetfas, Wormald PBS16, Tyco Fast 2000
• Multiple workstations can be configured for specific
functions or redundant operation
• Single monitor or two monitor (text and graphics)support
at each workstation
Emergency Management System & Fire Detection Graphical User Interface
Tyco Expert Graphics is a new client/server emergency
management system and fire detection graphical user
interface.
TXG is based on a Tyco graphical alarm monitoring system
that has been installed on hundreds of large fire detection
and alarm monitoring systems around the world and offers
the ability to integrate all Fire Panels with MZX technology,
such as Minerva MX, MZX500 series and Zettler ZX, with
improved functionalites
Tyco Expert Graphics provides annunciation, status display,
and control for various fire detection and alarm systems
including MX networks incorporating the latest MZX
Technology™ fire detection systems. It also supports the
predecessor Minerva® fire detection systems thus ensuring
that future updates from Minerva® to MX technology™ can
be accommodated. Additional support is provided for
Simplex 4100 range, Zetfas and Fast2000\PBS (Token ring
format).
TXG is a Microsoft Windows® based graphical interface with
a high resolution colour display. Responsive touch-screen
(optional) buttons with realistic icons and keyboard provide
control switches specific to the operation being performed.
Utilising a combination of symbols, floor plans, pictures,
text, voice messages and video input, TXG displays the
precise location and gives instructions on what emergency
action should be taken.
Additional Features
• Link up with I.P. CCTV camera systems, no additional
wiring, reduced installation cost for a fully integrated
fire\CCTV system
• Compatible with Flamevision® FV300 array based IR
flame detectors with built in CCTV
• MX Hotspot, chromatic analogue display. Programmable
tracking of analogue values. Changes display colour in
response to changes in analogue value from a selected
number of MX devices.
• Trending diagrams of analogue values helps reduce
maintenance time and cost
• Export analogue values to Excel for in depth analysis
• Audio descriptions of screens can be played when they
are displayed or played when an event occurs
01/15
The display can be configured to track detector inputs by
changing the colour of areas in response to changes in
analogue value. A detailed map of the area affected can be
printed automatically for use by personnel responding to an
emergency. Prompt response to a fire emergency, with the
correct action, provides the opportunity to reduce financial
loss and greatly improves safety.
Much of the work involved in configuring TXG has been
simplified through the automatic import of panel
configurations, AutoCAD® graphics, including data points,
and the ability to use a wide range of input data file types
including GIF, JPG, bitmap, Vector and WAV files.
System maintenance can be carried out via the high level
user interface with the ability to edit the position and
attributes of point icons as well as make changes to drawing
layouts. As well as simplifying maintenance, being a true
client server application means that any number of on-site or
off-site workstations can interrogate the database with
pre-defined security levels to facilitate any required
combination of access and control.
• High level user interface allows end user to make
changes to point attributes and layout further reducing
lifetime cost of ownership.
• Centralised security administration means that operator
accounts are administered through the TXG client’s
common database
• Mouse, keyboard or touch-screen control with full
multimedia compatibility
• Dual language switching
• The ability to display live video when specific predefined
alarm conditions occur
• Easy to configure and set-up. No special networking or
PC training required
• Facilities and maintenance management report and
analysis tools are available
Fire Catalogue
Chapter 4 Page 1
FIRE_Ch4_Networks_and_Graphics:Layout 1 01/04/2015 14:15 Page 2
Chapter 4 - Networks and Graphics
The IP Video feature allows real-time images of the area at
risk to be displayed in the event of an alarm or fault. Video
capture of the affected area appears on the screen
automatically, allowing the severity of the situation to be
assessed quickly and the appropriate executive action to be
taken.
AVAILABILITY AND ORDER PROCESS
For less serious incidents, expensive and unnecessary plant
shut downs can be avoided. In more critical situations,
accurate information can be quickly and efficiently
communicated to the response team.
MX HOTSPOT Icons representing the devices being
monitored will change colour dependant on status, alarm,
normal, fault, isolate etc.
Customers can fax or e-Mail an order form which details the
software options required, to customer service at
Letchworth. Original order forms can be obtained from
http://www.tycoemea.com/. This form will allow customer
service to prepare and allocate a license code that will
activate the required features. Customers will also be
required to place an order on JDE for each part number on
the form.
In addition to this, selected areas can be highlighted using
the chromatic analogue display feature, MX HOTSPOT. As
the analogue value of a monitored point changes the
chromatic analogue display will change the highlight colour
through a pre-defined range.
A media pack containing CD with license number, dongle,
multi language manuals on CD and original order form will
be dispatched to the customer.
For example a heat detector assigned MX HOTSPOT could
transit the highlight from blue to red. The number of
chromatic steps is dependent on the resolution of the
graphics card used, 16, 24 or 32 bits
TXG can be downloaded from the tycoemea.com website
and can be used with a time restriction for demonstration or
training purposes. TXG can also be ordered from our
Letchworth and Echt distribution centres.
On receipt, the software can be loaded and the license
number entered to make available the requested software
features.
Product Codes
NOTIFICATION BY EMAIL
Events, whether they are real or false alarms are handled
most efficiently when information can be quickly and
accurately communicated. TXG allows users to set up email
groups and notification texts linked to predetermined
events.
508.040.100
508.040.001
508.040.002
508.040.003
These are automatically transmitted ensuring that the
appropriate resource is deployed.
508.040.004
ADDITIONAL FUNCTIONS AND FEATURES
508.040.005
• Response buttons with configurable icons or text provide
control switches specific to any operation being
performed
• Uses a combination of symbols, floor plans, pictures, text
and video to communicate events
• Standard MX and Minerva® symbol libraries supplied
• Gives instructions on what emergency action should be
taken
• Prints maps and instructions to assist response teams
• History logging recallable or printable by event, dates,
device, or a host of other available filters
• The advanced filter allows the history report to be
specifically limited to a particular range or date period.
• Commands to control outputs from the Graphical User
Interface
• Events can be accepted individually or can be
“auto-accept”
• Supports all standard PC image file types (i.e. GIF, JPG,
BMP), AutoCAD® & Vector file types
Chapter 4 Page 2
508.040.011
508.040.021
508.040.025
508.040.027
508.040.033
508.020.050
Fire Catalogue
TXG USB Server Dongle/License/Software
TXG001-Single Client with 1 panel
(Requires TXG USB)
TXG004-Single Client with 2 to 4 panels
(Requires TXG USB and TXG001)
TXG010-Single Client with 5 to 10 panels
(Requires TXG USB, TXG001 and
TXG004)
TXG020-Single Client with 11 to 20 panels
(RequiresTXG USB, TXG001, TXG004 and
TXG010)
TXG999-Single Client with 21 or above
panels (Requires TXG USB, TXG001,
TXG004 TXG010 and TXG020)
TXG-C Additional Client license
TXG-MIN80 Minerva driver license
TXG-OPC - OPC Alarm / Event & Data
Access Server Licence
TXG-CPP - SIMPLEX CPP driver
TXG-PBS/FAST2000 DRIVER
19” LCD Touchscreen Monitor
01/15
FIRE_Ch4_Networks_and_Graphics:Layout 1 01/04/2015 14:15 Page 3
Chapter 4 - Networks and Graphics
TXG IS TOTALLY SCALABLE
……FROM A SINGLE FIRE ALARM
PANEL
CONNECTED TO A TXG SERVER……
The modest additional cost of a single
TXG client/server is easily justified when
the benefits that a Graphical User
Interface bring are considered.
RS232
TXG with direct connection to a single Minerva® MX
……TO A COMPLEX
INSTALLATION WITH MULTIPLE
DIVERSE NETWORKS AND
DISTRIBUTED CLIENTS
Large multi-building facilities may have
a number of fire detection networks,
possibly installed over an extended
period of time. TXG can be used as a
hub to integrate these systems with a
number clients providing annunciation
and control where it is needed.
Zetfas
Simplex 4100 Range
Wormald PBS 16
Tyco Fast 2000
Minerva® network via TLK800 Interface
TXG Client
TLI 800EN-G
Interface
TXG Server
TXG Client
CCTV Surveillance System
Minerva® MX Network
TXG Client
TCP\IP
TXG with multiple fire detection networks and CCTV integration
01/15
Fire Catalogue
Chapter 4 Page 3
FIRE_Ch4_Networks_and_Graphics:Layout 1 01/04/2015 14:15 Page 4
Chapter 4 - Networks and Graphics
Features
• Allows MZX Technology Fire Controllers to be
“seamlessly” networked together
• Dual ARM 7 RISC processors
• Support for Emergency Mode Indication
• True peer-to-peer communications; no host or master
controller required
• Highly resilient, node failure open and short circuit does
not affect remaining network
• Approved to EN54-13 and EN54-2
• Up to 99 controllers may be used on the network
• Wide range of cable topography supported
• Network can use a variety of cable types with up to
2500m between nodes (cable dependant), 1200m using
standard 1.5mm MICC cable
• FOM800 Plug on fibre optic module provides up to
5000m between nodes using 62.5/125 multimode fibres
• Easy to install and programme
• Simple to operate
TLI800EN Network Interface Module and FOM800 Fibre Optic Module
Inter-controller Network
The use of the MZX Technology Network allows the
fragmentation of a number of fire controllers to be drawn
into a network system. Because every installation is
different, the MZX Technology Network has been designed
to be highly flexible, allowing for a wide range of different
systems applications. With a large network system the
amount of data and information passing between fire
controllers can become high during an emergency
condition. The MZX Technology Network communication
protocol has been specifically designed with this in mind
and ensures that each event message passed around the
network is acknowledged by the receiving controller in the
fastest possible time.
Operation
The network is totally flexible and enables from 2 to 99 fire
controllers to be seamlessly linked together, providing a
system capability of up to 23,760 fire zones with 99,000
detection addresses, and over 100,000 digital I/O points.
System Overview
The MX Net communications network comprises a
collection of network interface modules and peripheral
equipment that together form a fault resistant, and flexible
peer-to-peer network for the MX Digital addressable fire
systems controllers.
With the MZX Technology Network, each MZX Fire
Controller on the network permits an operator to interrogate
and control any other MZX Fire Controller on the network
for extended interrogation and control, the MZX Technology
Network allows for up to a maximum of five nodes on the
network to be configured either as Master operating
stations or TXG graphical user interfaces (refer to datasheet
PSF206).
Cable Parameters
Maximum wire to wire capacitance
Resistance
Baud rate Capacitance
Maximum resistance = 40
Ohm for EN54-13
38400
0.3 uF
compliant installation.
19200
0.6 uF
Maximum resistance = 65
9600
1.2 uF
Ohm for proper function
without compliance.(all
2400
1.2 uF
baud rates)
1200
1.2 uF
Chapter 4 Page 4
Master operating stations use the standard MZX Fire
Controller hardware. In this application, the controller
changes its personality; and enables additional information
from each controller on the network to be displayed.
Mode of Operation
The MZX Technology Network employs a token passing
communications protocol that treats each node on the
network equally. Loss of one or more nodes does not affect
the operation of the remainder of the network.
Data is regenerated at each node in the network enabling
maximum distance between nodes. In the event of a short/
open circuit on the network between any two nodes,
isolation will automatically occur and the network will
re-configure communications and continue to allow
communication between all nodes physically connected.
The MZX Technology Network offers a high level of system
integrity, allowing safety critical actions to be passed across
the network from one MZX Fire Controller to another. This
very high level of system integrity enables the MZX
Technology Network to meet the requirements of EN54-13
and EN54-2.
In the event of loss of communication with the host
controller, the TLI800EN will use its secondary processor to
monitor the controllers fire outputs and if necessary can
activate the controllers emergency fire input. In addition it
can support a LED annunicator for network panel fire
indication, this is wired to a MPM800 via the TLI800EN’s
integral RBus RS485 port.
Fibre Optics
Fibre optics can also be supported on the MZX Technology
Network system by fitting one or two FOM800 modules to
the TLI800EN network card, this uses either type 62.5/125
or 50/125 multi-mode fibres between nodes on the network.
Use of fibre permits a maximum distance between nodes of
up to 5000 metres in either bus or ring topology.
Product Codes
557.202.080
557.202.081
557.200.039
TLI800EN Network Card and cable
FOM800 Fibre Optic Module
TLI800EN Network Interface in
Housing c/w PSU
557.180.219
PC to TLI800 EN Network Card
connection Cable
Fire Catalogue
01/15
FIRE_Ch4_Networks_and_Graphics:Layout 1 01/04/2015 14:15 Page 5
Chapter 4 - Networks and Graphics
Technical Specification
Technical Specification
TLI800EN Network Card
FOM800 Fibre Optic Network Interface
Mechanical
Dimensions:
Weight:
Housing:
Electrical
Power Consumption:
Network Connections:
Network diagnostic:
Cable Type:
Network Connections:
74mA @ 24VDC & 20mA @
5VDC
2 x RS 485
9 x on board LED’s / RS232 port
for system analysis and fault
finding
2 Core MICC, Shielded or
Twisted pair
Screw terminals, will accept
2.5 mm2 cable
Network Parameters:
Number of nodes:
99 (max)
Distance between nodes: 1000 to 5000 metres
(dependent upon cable type)
Communications type:
RS485
Baud Rates:
9.6K to 115.2K
Transport Type:
Token passing, non-collision
protocol
Environmental
Operating Temp:
-10°C to + 55°C
Storage Temp:
-10°C to + 70°C
Relative Humidity:
95% (100% intermittent)
01/15
Mechanical
Dimension:
Weight:
Housing:
116 x 90 x 20 mm
0.10 Kg
The TLI800 Network P.C.B. is
mounted directly onto the MZX
CPU800 within the panel
enclosure
Electrical
Supply Voltage:
Network Connections:
Cable Type:
Environmental
Operating Temp:
Storage Temp:
Relative Humidity:
50 x 58 x 12 mm
0.015 Kg
The FOM800 is mounted directly
onto the TLI800EN Network card
Powered from TLI800EN
2 x ST Fibre optic connections
62.5/125 or 50/125 multi-mode
fibre optic cables
-10°C to + 55°C
-10°C to + 70°C
95% (100% intermittent)
Technical Specification
TLI800EN-G Housed Network Card with PSU
Mechanical
Dimension:
Weight:
300 x 200 x 85 mm
3.85 Kg
Environmental
Operating Temperature: 0°C to +55°C
Relative Humidity:
95% max
Electrical
Supply Voltage:
Power consumption:
Fire Catalogue
220 to 250 VAC
160mA
Chapter 4 Page 5
FIRE_Ch4_Networks_and_Graphics:Layout 1 01/04/2015 14:15 Page 6
Chapter 4 - Networks and Graphics
TLD-530 ThornNet/MXNet direct line driver PCB
The Telephone Line Driver Module (TLD-530) is
used to interface two (2) dedicated telephone line
circuits to the TLI-800 module. The TLD-530 line
driver module converts the RS-485 signals
received from the TLI-800 network interface
module to signals capable of being transmitted
over the telephone line circuits. One TLI-800
supports two channels so only one module is
required per controller for both single path and
redundant path star connections. The interface
allows for field configured baud rates and
supports distances of up 3,000 metres. Up to two
units can be fitted into a TLO/TLD Housing.
Technical Specification
Dimensions
170H x 120W x
20D mm
140g
Weight
Product Codes
557.180.699
TLD 530 ThornNet/MXNet
direct line driver PCB
557.180.148.A TLO/TLD Housing - ADT
branded
CCU3
The CCU3/C-MXMB provides a MODBUS interface
to a number of MX panels on an MXNet. CCU/IO
boards may also be connected to provide general
I/O devices accessed through the MODBUS
interface.
The CCU3/C-MXMB connects to MX panels on the
MXNet via a TLI-800 (TPI) interface card using
RS232 (PL2 socket). It connects to MODBUS via
either an RS232, RS485 (default) or RS422
connection. Another port allows up to 8 CCU/IO
boards to be connected. Each CCU/IO has 8
relay outputs that can be used as inputs to the
MX. These contacts are controlled via WRITE
commands to the MODBUS map. Each CCU/IO
also has 8 supervised inputs whose status can be
read from the MODBUS map.
The CCU3/C-MX Bridge enables the direct
connection of an MX Technology® fire controller
and Minerva® 16E or 80 fire controllers via the
H-Bus Communications Driver Module (CDM). No
network cards are required in this configuration.
The CDM attaches on to the Minerva® H-Bus and
provides a serial port for the CCU3/C-MX bridge.
Chapter 4 Page 6
Technical Specification
Input Voltage:
18-30Vdc
Current:
150mA at
24Vdc
Dimensions:
140 x 105 x
15mm
Product Code
557.202.046
MX CCU3/C-MXMB
MX to MOD Bus Interface
Product Codes
557.202.123
MX Bridge CCU3/C-MX Bridge
557.180.025
Minerva Comms Driver Module
Fire Catalogue
01/15
FIRE_Ch4_Networks_and_Graphics:Layout 1 01/04/2015 14:15 Page 7
Chapter 4 - Networks and Graphics
Features
• Facilitates Integration of MX & Minerva Systems
• Easy Upgrade Path for MINERVA systems
MX Minerva - Bridge
The MX Minerva bridge enables a mix of Minerva and MX
Panels anywhere on a shared network to operate as an
integrated system.
The bridge comprises of 2 network cards and a translating
host (CCU).
Housed in either a MXAPSU17 or MXAPSU38 housing, the
MX-Minerva bridge is a translating host converting packets
between the Minerva format and the MX format in both
directions. Flexibility is provided for packet conversion in
the bridge configuration programme.
The MX Minerva bridge can be added to one mixed
network using both Minerva and MX Nodes or it can be
connected to span between two physically separated
network rings, one with Minerva nodes and one with MX
nodes.
Technical Specification
Product Codes
Size:
557.202.120
557.202.121
Input voltage:
Operating Temp:
EMC/RFI:
01/15
320x440x120mm (17A/H)
320x440x215mm (38A/H)
120-250VAC - 50/60Hz
8°C to +55°C
EN50130-4
Fire Catalogue
MX-Minerva Bridge Kit (17A/H)
MX-Minerva Bridge Kit (38A/H)
Chapter 4 Page 7
FIRE_Ch4_Networks_and_Graphics:Layout 1 01/04/2015 14:15 Page 8
Chapter 4 - Networks and Graphics
This page is left intentionally blank
Chapter 4 Page 8
Fire Catalogue
01/15
Chapter 5 Detector Test Equipment
Testifire
Testifire is the world’s first 3 in 1 detector tester. Suitable for single and multisensor detectors, it enables functional testing of Smoke, Heat and CO and
offers a wide rangeof benefits over existing test tools.
Features
•Smoke, Heat & CO in one unit*
• Independent, simultaneous or sequential testing
• Clearing mode
• Capsule generated stimuli
• ‘Hi Heat’ setting for sensors up to 100°C
Benefits
•Increases productivity on site
• Compatible with widest range of detectors
• Controlled stimuli release prevents damage to the
detector
• Non-pressurised capsules eliminate environmental
concerns
• Designed for use with Solo Access poles
*CO available on Testifire 2001
Smoke, Heat & CO Detector Test Kit
Smoke, Heat & CO Detector Test Kit
Product Code
517.001.236
1 x Testifire Smoke, Heat & CO Detector Tester
1 x Testifire Smoke Capsule
1 x Testifire CO Capsule
2 x Solo 770 Battery Batons 517.001.273
1 x Solo 727 Battery Charger 517.001.274
Smoke & Heat Detector Test Kit
Product Code
517.001.237
Testifire TS3
6 x Replacement smoke capsules for use with Testifire
CO Capsules
Smoke Capsules
09/16
Product Code
517.001.237
Testifire TS3
Product Code
517.001.238
Testifire TC3
6 x Replacement smoke capsules
for use with Testifire
6 x Replacement CO capsules (for use
with Testifire 2001)
Fire Catalogue
Chapter 2 Page 1
Chapter 5 Detector Test Equipment
Scorpion
Scorpion is an innovative solution for functionally testing any hard-toaccess
smoke detector.
A Scorpion head unit is a smoke generator which is installed next to the
point detector or at the furthest sampling hole of an ASD pipe and
when required, generates smoke for a functional test of the device.
A test that would have taken hours in planning, risk assessments and execution, is now completed in a matter of minutes and is as easy as testing a detector within reach.
Perfect for:
•Lift Shafts
• Ceiling and Floor Voids
• Secure Areas (e.g. Plant / Storage / Server room)
•Hazardous Areas
Scorpion - for ASD and hard-to-access smoke detectors
Product Code
517.001.270
Scorpion Point Installation Kit
Product Code
517.001.272
Scorpion Engineer’s Controller
Includes: 1 x Scorpion Point
Head Unit, 1 x Scorpion
Access Point.
• Controls Scorpion Head Unit via connection to Scorpion Access Point.
Product Code
517.001.271
Scorpion ASD Installation Kit
Includes: 1 x Scorpion ASD
head Unit, 1 x Scorpion
Access Point.
Chapter 2 Page 2
Fire Catalogue
09/16
Chapter 5 Detector Test Equipment
Solo
Smoke, Heat & CO Detector Test Kit
Aerosol Dispenser for Solo Smoke and Test Aerosols
Product Code
517.001.236
1 x Testifire Smoke, Heat & CO Detector Tester
1 x Testifire Smoke Capsule
1 x Testifire CO Capsule
2 x Solo 770 Battery Batons 517.001.273
1 x Solo 727 Battery Charger 517.001.274
Smoke, Heat & CO Detector Test Kit
Smoke Detector Test Aerosol
Product Code
517.001.256
Solo A3
•
•
•
•
Designed for use with Solo Dispenser
Non-flammable
Fast activation
Fast clearing
CO Detector Test Aerosol
Product Code
517.001.262
Solo C3
• Designed for use with Solo Dispenser
• Genuine, non-flammable CO stimulus
• Controlled delivery
Cordless Heat Detector Test Kit
Product Code
517.001.254
Solo 461
• Designed for use with Solo Access Poles Includes:
• Battery powered
• Suits fixed temperature, rate of rise and combination detectors up to 90°C
• Lightweight and simple to use
• Universal design suits wide range of
detectors
1 x Solo Heat Detector Tester
1 x Solo 727 Battery Charger
517.001.274
2 x Solo 770 Battery Batons
517.001.273
Battery Baton and Chargers
09/16
Product Code
517.001.273
Solo 770
Product Code
517.001.274
Solo 727
Product Code
517.001.239
Solo 760
Product Code
517.001.243
Solo 760
3.0Ah NiMH
Battery Baton for
use with Testifire,
Solo 461 and
Scorpion.
Charger for use
with 3.0Ah Solo
770 Battery
Batons
2.2Ah NiMH
Battery Baton
for use with
Testifire,
Solo 461 and
Scorpion.
Charger for use
with 2.2Ah Solo
760 Battery
Batons.
Fire Catalogue
Chapter 2 Page 3
Chapter 5 Detector Test Equipment
Detector Removal Tool
800RT Detector Removal Tool
Product Code
517.001.240
Solo 200
• Universal design suits wide range of detectors
• Designed for use with Solo Access Poles
Storage Bag
Product Code
516.800.917
Product Code
517.001.264
• Compatible with 800 and 600 series detectors
• Enables detector dust
covers to be removed
A protective storage
bag for the Solo and
Testifire product
ranges
Telescopic Access Pole
Extension Pole
Product Code
517.001.230
Solo 100
Product Code
517.001.275
Solo 108
Product Code
517.001.226
Solo 101
3 section Telescopic
Pole extends from 1.26
to 4.5 metres
2 section Telescopic
Pole extends from 1.2 to
2.2 metres
1.13 metre Extension
Pole which can be
used on its own or
fitted to a Solo
Telescopic Pole
Adaptor Tube B
Product Code
517.001.224 Adaptor for Solo Access Poles to allow fitting of:
800RT Detector Removal Tool T110 Flame Detector Tester T210+ Flame Detector Tester M900 Address Key Extractor Tool
516.800.917
592.001.012
592.001.016
517.001.235
M900 Address Key Extractor Tool
Product Code
517.001.235 The address key extractor tool can be used to remove the address
key from
either a 4” or 5” detector base from ground level
Chapter 2 Page 4
Fire Catalogue
09/16
Chapter 5 Detector Test Equipment
517.001.236
Testifire Smoke,
Heat & CO
Detector Tester
517.001.267
Testifire Smoke
& Heat Detector
Tester
517.001.255
Solo Smoke
& CO Aerosol
Dispenser
517.001.254
Solo Heat
Detector
Tester
517.001.240
Solo Universal
Removal Tool
592.001.012
516.800.917
592.001.016
Detector
Flame Detector Removal Tool
Testers
517.001.235
Address Key
Extractor Tool
Product Code
517.001.226
Solo ExtensionPole
Product Code
517.001.226
Solo ExtensionPole
Product Code
517.001.226
Solo ExtensionPole
Scorpion - for ASD and
hard-to-access Point Detectors
Product Code
517.001.273
Scorpion Point Installation Kit
Product Code
517.001.271
Scorpion ASD Installation Kit
Product Code
517.001.272
Scorpion Engineer’s Controller
Product Code
517.001.230
Solo Telescopic Access Pole
Product Code
517.001.275
Solo Telescopic Access Pole
09/16
Fire Catalogue
Part No.
Access Height
(approx. max.)
517.001.275
4m
517.001.230
6m
517.001.230 +
517.001.226 (x 1)
7m
517.001.230 +
517.001.226 (x 2)
8m
517.001.230 +
517.001.226 (x 3)
9m
Chapter 2 Page 5
Chapter 5 Detector Test Equipment
Features
•Approved for use in zone 1 & 2 areas (GPIIC gases)
• Adaptor plate to ensure perfect alignment
• IECEX Approved
Technical Specifications
Product Codes
Material: Glass filled polyester
Weight: 0.8 kg
Supply Voltage: 9 Vdc
Operating Temp: -10°C to + 50°C
Humidity: 95% (Non Condensing)
Enclosure: IP54
Classification: Atex EExe ib IICT4. Suitable for use in
zones 1 & 2 where group IIC gases or
lesser hazards are sometimes present in
explosive concentrations.
592.001.016
592.001.014
592.001.010
T210+ Test source for use with Solo 704
Adaptor Tube B (517.001.224) and Solo
100/101 Poles (517.001.230/226)
T210+Adaptor required for the T210+ to
be used with S200 and S200 Plus Flame
Detectors
T110 PP3 Battery and Charger Kit
Manual - Vol 01B-01-G5 “Detectors Fire Manual”
Flame Detector Test Equipment
Product Code
592.001.012 T110 Test Source for use with Solo 704 adaptor tube B (517.001.224)
and Solo 100/101 poles (517.001.230/226)
Product Code
592.001.018
T110 Adaptor for series 600 and 800 flame detectors
Product Code
592.001.010
T110 PP3 Battery and Charger Kit
07/16
Fire Catalogue
Chapter 2 Page 6
FIRE_Ch6_System_Accesories:Layout 1 30/03/2017 11:44 Page 1
Chapter 6 - System Accessories
Batteries, PSU and Chargers
Product Codes
PS-1221
PS-1230
PS-1270
PS-1212
PS-12650
PS-12380
PS- 6100
PS-12170
PS-12260
PS-1242
PS-12120
Voltage (V)
12
12
12
12
12
12
6
12
12
12
12
Ah at
20h rate
2.1
3.0
7.0
1.2
65.0
38.0
10.0
17.0
26.0
4.5
12.0
Length
178
134
151
97
348
197
151
181
166
90
151
Dimensions (mm)
Width
35
67
65
42
167
165
51
76
176
70
98
Height
60
60
94
51
178
170
94
167
112
101
94
Height including
Terminals
66
66
98
54
178
170
98
167
125
105
100
Product Codes
PS-1221
PS-1230
PS-1270
PS-1212
PS-12650
PS-12380
PS-6100
PS-12170
PS-12260
PS-1242
PS-12120
03/17
Fire Catalogue
12 Volt 2.1 Ampere hour rechargeable
sealed lead acid battery
12 Volt 3.0 Ampere hour rechargeable
sealed lead acid battery
12 Volt 7.0 Ampere hour rechargeable
sealed lead acid battery
12 Volt 1.2 Ampere hour rechargeable
sealed lead acid battery
12 Volt 65.0 Ampere hour rechargeable
sealed lead acid battery
12 Volt 38.0 Ampere hour rechargeable
sealed lead acid battery
6 Volt 10.0 Ampere hour rechargeable
sealed lead acid battery
12 Volt 17.0 Ampere hour rechargeable
sealed lead acid battery
12 Volt 26.0 Ampere hour rechargeable
sealed lead acid battery
12 Volt 4.5 Ampere hour rechargeable
sealed lead acid battery
12 Volt 12.0 Ampere hour rechargeable
sealed lead acid battery
Chapter 6 Page 1
FIRE_Ch6_System_Accesories:Layout 1 30/03/2017 11:44 Page 2
Chapter 6 - System Accessories
Power Supply Unit
Features
•
•
•
•
•
•
•
•
•
•
Robust metal housing
Twin fused outputs
Temperature compensated charging
Deep discharge protection of batteries
Fault relay output
Size 383mm wide x 408mm high x 97mm deep
Weight 4.3 Kg (excluding batteries)
Operating temperature -5°C to +40°C
Supply voltage 230VAC 50/60Hz
Comprehensive LED status indication
This PSU is approved by IMQ to EN 54-4:1997 + A1:2002
and EN60950-1:2001. The steel housing contains a 5 amp
switch mode power supply and monitoring board and has
space to accommodate 2 x 12V 17Ah sealed lead acid
batteries. The 10 front panel LED's comprehensively
indicate the status of the unit.
Product Code
558.004.020
The new STX range of switch mode power supplies has
been specifically designed for EN54 compliant fire systems.
Available in 2A versions they are certified to EN544:1997, A1:2002 & A2:2006. The units include intelligent
battery charging using Elmdene’s efficient EcoCharge
technology, possess mains & battery monitoring with
independent voltfree outputs and also feature battery deep
discharge protection in the event of a prolonged mains
failure.
24V 5 Amp Power Supply Unit with
housing for 17A/H Batteries
Product Codes
558.004.021
558.004.022
Compact Power Supply EN54 2 A 7 AH
24 V d.c (27.6 V) 2 Amp to load +0.3 A
battery charging. Fit upto 2 x 7 Ah
batteries. 275h x 330w x 80d - Hinged lid
Compact Power Supply En54 2 A 17Ah
24 V d c PSU (27.6 V) 2 Amp to load +
0.3 A battery charging. Fit up to 2 x 7 Ah
batteries. 420h x 400w x 80 x 80d Hinged lid
The inclusion of LED indicators provides quick diagnostics
of the status of the power supply, while a variety of
enclosures offer the installer a choice of standby battery
backup options
Chapter 6 Page 2
Fire Catalogue
03/17
FIRE_Ch6_System_Accesories:Layout 1 30/03/2017 11:44 Page 3
Chapter 6 - System Accessories
Door Release Equipment
Door Release Magnets
The door magnet range encompasses 2 metal and
2 ABS housed wall mounted and 1 floor mounted
release magnet sets
Features
•
•
•
•
Integral release button
Attractive design
Slimline ABS housed units
Robust floor mounted unit
Door release magnet set, Wall
Mount, Metal Housing, 24VDC
Product Code
3-59-0404-S001
Door release magnet set, Wall
Mount, Metal Housing, 230VAC
Product Code
3-59-0404-S002
Door release magnet set, Wall
Mount, ABS Housing, 24VDC
Product Code
3-87-0351
Door release magnet set, Wall
Mount, ABS Housing, 230VAC
Product Code
3-87-0352
Door release magnet set, floor
mount, ABS housing 24VDC
Product Code
3-84-0301
Floor mounting bracket for
adapting wall mounted door
magnets to floor mount
Product Code
2-34-035G-S001
Technical Specifications
3-59-0404-S001 - 89 x 89 x 70mm, 0.5Kg, 180N Holding Force, 1.15W Coil @ 24VDC
3-59-0404-S002 - 89 x 89 x 70mm, 0.5Kg, 180N Holding Force, 1.15W Coil @ 230VAC
3-87-0351 - 95 x 87 x 46mm, 0.36Kg, 200N Holding Force, 1.15W Coil @ 24VDC
3-87-0352 - 95 x 87 x 46mm, 0.36Kg, 200N Holding Force, 1.15W Coil @ 230VAC
3-84-0301 - 110 x 96 x 96mm, 0.7Kg, 200N Holding Force, 45mA Coil @ 24VDC
Door Release Power Supply
The Transformer Rectifier is a dual
purpose, smoothed power supply
providing either an energised or
de-energised output upon activation.
The output may be activated by
utilising a set of volt free contacts from
a fire or security panel, or by providing
a 12/24Vdc trigger voltage from other
apparatus.
The transformer rectifier units are
normally used to control the operation
of other 24Vdc equipment such as
magnetic door retainers. The units are
ideal for applications where the supply
is to be energised from a remote
source.
Technical Specification
Input Voltage:
230VAC 50Hz
Output Voltage:
22 - 30Vdc
Output Current:
4 Amps
Continuous
Temperature:
-10C to + 40C
Relative Humidity: 95% RH
IP Rating:
IP41 (excluding
rear face)
Material:
1.2mm white
powder coated
steel
Dimensions:
230mm (W) x
200mm (H) x
80mm (D)
Product Code
558.004.010
ELM 24V 4A Door Holder PSU
Door Release Button
Door Release Button (white) supplied
with surface mount backbox (black)
for manual release of door magnets
or door release units.
03/17
Product Code
519.001.008
Door Release Button
Fire Catalogue
Chapter 6 Page 3
FIRE_Ch6_System_Accesories:Layout 1 30/03/2017 11:44 Page 4
Chapter 6 - System Accessories
Auxiliary Interface Relays
Boxed Relays
Metal boxed heavy duty alarm relay
with 25A mains rated DPCO contacts.
Available with either a 240VAC 12mA
or 24 VDC 50 mA rated coil.
Suitable for heavy duty switching
applications.
Product Codes
567.007.008
Alarm Relay 240Vac MK4
567.007.009
Alarm Relay 24Vdc MK4
RU1-24, this is a metal boxed
auxiliary relay with 5 A Mains rated
double pole contacts with a
24 VDC 25 mA coil. This compact
relay is suitable for interfacing a fire
alarm controller to low current mains
powered devices or contactors
Product Code
RU1-24
Relay Boxed 24Vdc Coil 5A contacts
Relay Output Board
Technical Specifications
Gold clad contacts 2A @ 24 VDC
DPCO
Coil resistance 2900 ohms
Operating current 8mA @ 24 VDC
Operating Voltage 17.5 - 30 VDC
Terminals suitable for 2.5 mm2 cable
26 mm x 60 mm x 18 mm
Polarised and suppressed
Product Code
508.023.036
A1466 Relay Output Board
Fire Notice Frames
These snap fit frames are used mainly
for fire alarm zone charts and are
available to fit A4 to A1 size drawings.
Product Codes
A4FRAME
Fire Notice Snap Frame
A4 346 x 260 x 25 mm
A3FRAME
Fire Notice Snap Frame
A3 475 x 350 x 25 mm
A2FRAME
Fire Notice Snap Frame
A2 650 x 475 x 25 mm
A1FRAME
Fire Notice Snap Frame
A1 890 x 645 x 25 mm
A4 Document Box
An A4 sized box ideal for the safe
keeping of important fire system
documents and log books. Formed
from red powder coated steel with a
cam lock. The box is branded Zettler
with a white FIRE logo. 2 Keys are
provided and all units are keyed alike.
Dimensions 300 x 235 x 50 mm HWD
Chapter 6 Page 4
Product Codes
557.202.629
Fire Document Box Zettler
Fire Catalogue
03/17
FIRE_Ch6_System_Accesories:Layout 1 30/03/2017 11:44 Page 5
Chapter 6 - System Accessories
Fire Resistant Cable
DÄTWYLER Lifeline cable is suitable for fire alarms and
emergency lighting where BS6387 and BS7629 standards
are acceptable and meets the installation and performance
requirements of:
• BS5839 Pt.1 for use in fire alarms
• BS5266 for use with emergency lighting
• IEC331 fire resistance
Lifeline is LPCB approved to BS6387 CAT CWZ and
BASEC approved to BS7629.
Lifeline is low smoke, zero halogen, has an integral
aluminium backed mylar tape screen with tinned drain wire
and requires no special terminations, tools or ferrules for
installation.
Full details of Lifeline cable can be found in the DÄTWYLER
Lifeline datasheets on the Tyco Fire Protection Products
website (www.tycoemea.com).
DÄTWYLER offer a wide range of cable and safety cabling
systems including complete safety cable systems to
DIN4102 part 12.
The following DÄTWYLER Lifeline cables are held in stock
at Tyco Fire Protection Products Letchworth warehouse,
together with suitable P clips and glands. Cables are priced
per metre but must be ordered in units of 100 metre. P
clips and glands are priced each but must be ordered in
packs.
Technical Specification
Product Codes
Construction
Conductor:
Product Codes
Bare copper, solid or
stranded to BS 6360
Insulation:
Special double layer
insulation according to
BS 7655, E15
Inner Covering: High temperature resistant
glass fibre tape
Screening:
Al-Laminated tape with
tinned copper drain wire,
solid to BS 6360
Outer Sheath:
Flame retardant polyolefin
compound according to
BS 7655, LTS3
Technical Properties
Rated Voltage: 300/500V
Test Voltage:
2000V, 50Hz core/core
2000V, 50Hz core/screen
Operating Temp: -15oC to +90oC
Core Colours:
2 cores + earth: red, black
4 cores + earth: red,yellow,blue,black
Sheath Colour: Red or white
General Properties
Zero Halogen, no corrosive gases IEC 60754-2, BS 6425 part 1
Reduced fire propagation - IEC 603323, BS 4066 part 3
Minimum smoke emission - IEC 61034,
BS 7622
Insulation integrity - IEC 60331
(FE180), BS 6387 (cat. CWZ)
Approvals
BASEC
No. of Cores x Cross Section (n x mm2) Copper Content (Kg/Km)
2 x 1.0
19
2 x 1.5
29
2 x 2.5
48
4 x 1.0
39
4 x 2.5
96
03/17
No. Cores
2 + earth
2 + earth
2 + earth
2 + earth
4 + earth
4 + earth
4 + earth
4 + earth
599.048.020
599.048.022
599.048.023
599.048.024
599.048.032
599.048.034
599.048.035
599.048.036
DÄTWYLER Lifeline cable
Core Size
Colour
1 mm
Red
1.5 mm
Red
1.5 mm
White
2.5 mm
Red
1 mm
Red
1.5 mm
Red
1.5 mm
White
2.5 mm
Red
Clips
P34 R
P34 R
P34 W
P37 R
P37 R
P40 R
P40 W
P43 R
Product Codes
559.048.000
599.048.001
599.048.002
599.048.003
599.048.005
599.048.009
599.048.010
DÄTWYLER Lifeline Fire Resistant P
Clips & Glands
Qty. per pack Reference
Colour
50
P32
Red
50
P34
Red
50
P34
White
50
P37
Red
50
P40
Red
10
NG1
Red
10
NG1
White
Total Weight (Kg/Km) Outer Diameter (approx. mm) Calorific Potential (KWh/m)
75
7.4
0.16
97
8.2
0.18
141
9.6
0.24
114
8.6
0.23
223
11.3
0.37
Fire Catalogue
Chapter 6 Page 5
FIRE_Ch6_System_Accesories:Layout 1 30/03/2017 11:44 Page 6
Chapter 6 - System Accessories
This page is left intentionally blank.
Chapter 6 Page 6
Fire Catalogue
03/17
FIRE_Ch7_VESDA:Layout 1 09/05/2017 09:44 Page 1
Chapter 7 - VESDA
Aspirating Smoke Detection
Vesda aspirating smoke detection provides a high sensitivity method for detection of fires at a very early stage - it is
ideal for computer rooms and other high risk and high value areas. The range of products range from the Laserfocus
for small risks up to the LaserPlus range of networkable 4 pipe panels.
Features
• Laser Based Absolute Smoke Detection
• Very Early Warning of a Potential Fire Incident
• Wide Sensitivity Range (0.025%-20% obs/m)
(0.008 - 6.4% obs/ft)
• Detection Capabilities for smaller critical areas up to 500m
• Dual Stage Dust Filtration
• Programmable Alarm Thresholds
• Reliable Air Flow Monitoring
• Easy User Interaction
• AutoLearn Smoke & Flow
• Pre-engineered Pipe Designs
LaserFOCUS Aspirating Smoke Detection
Incorporating detection methodology derived from its
VESDA predecessors - the VESDA LaserFOCUS multiple
point air sampling technology works by utilising a highly
effective aspirator that continually draws air into its laser
detection chamber via a pipe network.
Accurate assessment of the air sample using calibrated
detection and long detector life expectancy, are assured
with a patented dual stage filtration process that both
eliminates background ‘noise’ and preserves the optical
integrity of the laser technology with its clean air bleed. The
result of which is an unchallenged detection process able to
provide reliable and consistent very early warning smoke
detection performance across a diverse range of
applications.
Technical Specification
Product Codes
Supply Voltage:
Current Consumption:
516.018.020
Dimensions:
Weight:
IP Rating:
Operating Temp:
Sampled Air:
Humidity:
05/17
18 to 30 Vdc
220 mA quiescent
295 mA alarm
255H x 185W x 90D mm
2 kg
IP30
0°C to + 40°C
0°C to + 40°C
5% to 95% (non condensing)
516.018.022
516.018.023
Fire Catalogue
VLF-250 Vesda Laserfocus
(with English overlay)
VIC-010 LaserFocus VesdaNetwork Card
VLF-500 Vesda Laserfocus
(with English overlay)
Chapter 7 Page 1
FIRE_Ch7_VESDA:Layout 1 09/05/2017 09:44 Page 2
Chapter 7 - VESDA
Features
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
Reduced size
Absolute smoke detection
Wide sensitivity range
Single pipe inlet
Simple display
Referencing
VESDAnet communication (VN)
Dual stage dust filter
Three alarm levels
Configurable relays
Air flow monitoring
Optional remote display and relay capability
Simple mounting design
AutoLearnTM
Marine Approved Version
LaserCOMPACTTM and MX LaserCOMPACTTM
The LaserCOMPACT and VLC800 MX Laser compact
detector has been specifically designed to provide all the
benefits of aspirating smoke detection, including very early
warning, in single small areas and where space is a
premium.
This has been achieved through the combination of
approved LaserPLUS detection technology, dual stage
filtration technology and a modified aspirator design
incorporated in a smaller enclosure with simplified display.
The LaserCOMPACT is available in two versions, one that
interfaces via relays only (RO) or across either the relays or
VESDAnetTM (VN).
The VLC 800MX Laser Compact is available with an in-built
MX interface to enable it to communicate directly with the
MX loop.
Technical Specification
Product Codes
Supply Voltage:
Current Consumption:
516.018.011
516.018.010
516.018.012
Dimensions:
Weight:
Operating Temp:
Sampled Air:
18 to 30Vdc
225mA quiescent,
245mA in alarm
225H x 225W x 85Dmm
1.9Kg
-10°C to+ 39°C
-20°C to +60°C
516.018.030
516.018.031
516.018.032
Chapter 7 Page 2
Fire Catalogue
VLC-505-VN VESDA net Version (VN)
VLC-500-RO Relays Only Version (RO)
VLC800 MX Addressable Vesda Laser
compact (Compatible with MX Consys
versions 2.1 and above)
VLC-500-RO Relays Only Version (RO)
Marine
VLC-500-VN Vesdanet Version (VN)
Marine
VRT-J00 Remote Display c/w 7 relays
Marine
05/17
FIRE_Ch7_VESDA:Layout 1 09/05/2017 09:44 Page 3
Chapter 7 - VESDA
Features
•
•
•
•
•
•
•
•
•
•
•
•
•
Wide sensitivity range
Laser-based light source
4 Configurable alarm levels
Purpose built Aspirator
4 In-line Inlet pipes
Flow sensor for each inlet pipe
Wide range DC power
Low-cost maintenance
Dual stage filter
Easy access to filter cartridge
7 Software configurable relays
Recessed mounting
Multiple exhausts
LaserPLUS Standard Modular Range
The detector assembly contains the laser detection
chamber, high efficiency aspirator, monitored filter
cartridge, control electronics and relay interface. The
detector assembly can be used as a “distributed” system,
with the display, programmer and VESDAnet socket
modules mounted in a remote location.
516.018.001
VLP-012 LaserPLUS Detector, programmer and
display
Alternatively, the detector assembly can be configured as a
“self-contained” system by replacing the detector’s blank
panels with the display and/or programming modules.
516.018.002
VLP-002 LaserPLUS Detector and display
516.018.013
VLP-400 LaserPLUS Detector with fire OK LED
Technical Specification
Product Codes
Supply Voltage:
Current Consumption:
516.018.001
Dimensions:
Weight:
Operating Temp:
Humidity:
05/17
18 to 30 Vdc
(No display or programmer)
240 mA quiescent plus 50 mA
alarm (24Vdc at 3000 rpm)
225H x 350W x 125D mm
4.0 Kg (including display and
programmer modules)
0°C to + 39°C
0-95% RH, non condensing
516.018.002
516.018.013
Fire Catalogue
VLP-012 LaserPLUS Detector,
programmer and display
VLP-002 LaserPLUS Detector and display
VLP-400 LaserPLUS Detector with fire OK
LED
Chapter 7 Page 3
FIRE_Ch7_VESDA:Layout 1 09/05/2017 09:44 Page 4
Chapter 7 - VESDA
Features
•
•
•
•
•
•
•
•
•
•
•
•
Individual pipe annunciation
Adaptive scan threshold
Wide sensitivity range (0.005 to 20% obs/m)
Laser based light source
Configurable alarm levels
Purpose built Aspirator
4 In-Line inlet pipes
Flow sensor for each pipe inlet
Low-cost maintenance
Dual stage filter
Easy access to filter cartridge
Recessed mounting
LaserPLUS Scanners
VESDA LaserPLUS is also available in a Scanner
configuration, which allows the system to distinguish and
identify the pipe carrying smoke, while sampling multiple
sectors.
The VESDA LaserPLUS will continue to sample from all
sectors to monitor the fire growth and maintain full
protection.
VLS-214/314 FD7/FD12 Scanner
Product Codes
516.018.004
VLS-214 FD7 Scanner, programmer
and display with 7 relays.
516.018.007
VLS-314 FD12 Scanner, programmer
and display with 12 relays
VLS-600/700 FD7/FD12 Scanner
Product Codes
516.018.016
VLS-600 FD7 Scanner with Fire OK LED
516.018.019
VLS-700 FD12 Scanner with Fire OK LED
VLS-204/304 FD7/FD12 Scanner
Product Codes
516.018.005
VLS-204 FD7 Scanner and display
with 7 relays.
516.018.008
VLS-304 FD12 Scanner and display
with 12 relays
Technical Specification
Product Codes
Supply Voltage:
Current consumption:
516.018.004
Dimensions:
Weight:
Operating Temp:
Humidity:
Relay Outputs:
18 to 30Vdc
(No display or programmer)
240mA quiescent plus 70mA
alarm (24Vdc at 3000 rpm)
225H x 350W x 125D mm
4.0Kg including display and
programmer modules
0°C to + 39°C
10-95% RH, non condensing
7 or 12
516.018.007
516.018.005
516.018.008
516.018.016
516.018.019
VLS-214 FD7 Scanner, programmer and
display with 7 relays.
VLS-314 FD12 Scanner, programmer and
display with 12 relays
VLS-204 FD7 Scanner and display with 7
relays.
VLS-304 FD12 Scanner and display with
12 relays
VLS-600 FD7 Scanner with Fire OK LED
VLS-700 FD12 Scanner with Fire OK LED
Datasheet - Product Code PSF105U “VESDA LaserPLUS”
Chapter 7 Page 4
Fire Catalogue
05/17
FIRE_Ch7_VESDA:Layout 1 09/05/2017 09:44 Page 5
Chapter 7 - VESDA
Features
• Four alarm levels (Alert/Action, Fire 1 & Fire 2)
• 20 segment vertical bar graph
• Alarm threshold indicators
(Alert, Action & Fire 1)
• Audio and visual indication
• Alarm indicators
• Informative fault indicators
• Multi-mode numeric display(defaults to smoke
obscuration)
• Acknowledged push-button presses
• Multiple language supported
• Addressable to any detector
Remote Displays and Modules
A display module monitors the VESDA LaserPLUS
detector. It reports a visual representation of smoke levels,
and all alarm and fault conditions. The internal sounder
warns personnel in the local area that an alarm threshold
has been reached, or a fault has occurred.
It has a 20 segment vertical bar graph, a 2-digit numerical
display, an audible sounder and clear alarm and fault
indicators. It also has 4 push buttons to control the
detector and the mode of the display.
Displays can be located at a convenient location - either
within the detector module, or remotely on the VESDAnet.
For monitoring convenience, multiple displays can be
associated with a single detector.
VRT-400,700 & 800
Product Codes
516.018.104
VRT-400 Remote scanner display
including 7 relays
516.018.107
VRT-700 Remote scanner display no relays
516.018.108
VRT-800 Remote scanner display
with 12 relays
VRT-200,600,J00 and K00 displays
Product Codes
516.018.102
VRT-200 Remote display
including 7 relays
516.018.106
VRT-600 Remote detector displayno relays
516.018.119
VRT-J00 Compact Display c/w 7
relays
516.018.120
VRT-K00 Compact Display no relays
VRT-300 Remote VESDAnet socket
Product Code
516.018.103
VRT-300 Remote VESDAnet socket
VRT-100 Remote programmer
Product Code
516.018.101
VRT-100 Remote programmer
Technical Specification
Supply Voltage:
Current Consumption:
Dimensions:
Operating Temp:
Humidity:
05/17
18-30Vdc (when used in
detector unit, Remote unit or
19” rack)
60mA quiescent plus 20mA
alarm @24Vdc - (module
only)/90mA quiescent plus
20mA alarm @24Vdc (in remote
mounitng box)
150H x 140W x 90D mm
0°C to +39°C
10-95% RH, non condensing
Fire Catalogue
Chapter 7 Page 5
FIRE_Ch7_VESDA:Layout 1 09/05/2017 09:44 Page 6
Chapter 7 - VESDA
LaserPLUS Standard 19 Inch Sub-Rack Remote Display Assemblies
The 19” sub-rack is available as a
mounting option, with 4 mounting
slots for display or programming
modules.
Technical Specification
Dimensions: 128H x 482W x
120D mm
Product Codes
516.018.201
VSR-2000 19” Sub-rack with 1
detector display and 3 blanks
516.018.203
VSR-2210 19” Sub-rack, 2 detector
displays, programmer and 1 blank
516.018.204
VSR-2221 19” Sub-rack with 3
detector displays and programmer
516.018.206
VSR-2222 19” Sub-rack with 4
detector displays
LaserPLUS Components for Ordering Custom Built Remote Display Sub-racks
Sub-rack configurations other than
those available as standard can be
supplied as custom built units. The
sub-rack and cost of assembly are
included in the VSR-CUSTOM.
The configuration of the custom built
unit must be specified at time of
ordering (e.g. 2 x VSU-0 and 2 x
VSU-2 configured as VSR-0022)
Note: The order of the numbers (e.g.
0022) indicates the order in which
the sub-units will be mounted in the
sub-rack housing when looking from
the front of the unit - from left to
right.
Product Codes
516.018.260
VSU-0 Blank Sub-unit
516.018.261
VSU-1 Programmer sub-unit
516.018.262
VSU-2 Detector display sub-unit
plus 7 relays
516.018.264
VSU-4 Scanner display sub-unit plus
7 relays
516.018.265
VSU-5 Blank sub-unit with 7 relays
516.018.214
VSU-E Blank scanner sub-unit with 7
relays
516.018.268
VSU-8 Scanner display sub-unit with
12 relays
516.018.269
VSU-9 Blank display sub-unit with 12
relays
516.018.219
VSU-J Compact display sub-unit
plus 7 relays
516.018.210
VSR-CUSTOM Custom sub-rack
housing includes cost of custom
building 4 VSU sub-rack units.
LaserPLUS Standard 19 Inch Rack Remote Display Assemblies
Standard rack enclosure to fit 2
sub-rack assemblies.
Technical Specification
Dimensions:
020-050 300H x 400W x 140D mm
Product Code
516.018.303
020-050 IP66 Enclosure
LaserPLUS Ancillaries & Power Supply Unit
Product Codes
516.018.402
VHX-0200 PC link HLI plus leads
(MK2)
516.018.407
VESDA VPS-220 2A 24VDC PSU
516.018.410
VESDA VPS-250-E 2A 24VDC PSU
516.018.401
VHH-100 Hand held programmer
plus leads
A variety of other ancillaries are
available. Configuration software is
available from the Xtralis website
www.vision-fs.com.
LaserPLUS Spares
The following common VESDA
LaserPLUS spares are kept in stock
by Tyco Fire Protection Products.
Other spares can be supplied if
required.
Product Codes
516.018.502
VSP-004 Scanner display (spare)
516.018.505
VSP-019 Filter cover door (spare)
Chapter 7 Page 6
516.018.506
VSP-006 Spare detector chassis and
manifold
516.018.508
VSP-008 Spare remote termination
card 7 relays
516.018.509
VSP-009 Spare scanner chassis and
manifold
Fire Catalogue
516.018.514
VSP-014 Spare header termination
card 7 relays
516.018.515
VSP-015 Spare aspirator fan
516.018.504
VSP-005 Filter cartridge (spare)
05/17
FIRE_Ch7_VESDA:Layout 1 09/05/2017 09:44 Page 7
Chapter 7 - VESDA
Features
• Powerful fan
• Upto two x 50m pipe runs
• Pipes can be individually monitored for air flow with LED
bar graph
• MX Loop and 24 VDC connections
• Fault monitored via the MX Loop
• IP65 enclosure
• Field serviceable air filters
• Uses standard 25mm Vesda pipe & fittings
ICAM IAS800 Air Sampling Smoke Detection Systems
The ICAM IAS800 Air Sampling Smoke Detection System
provides a flexible solution to meet the unique needs of
numerous applications including industrial spaces such as
cable tunnels, tamper proof and unobtrusive requirements
for special accommodation, or can simply be used to
replace spot (point) detectors in office environments.
The system utilises a high performance aspirator and
software configurable flow monitoring circuitry. The air flow
level is displayed on a ten element bar graph that can be
adjusted for high and low flow thresholds, and flow failure is
reported as a device fault via upto two MX Technology
MIM800 addressable modules.
The IAS800 system actively draws air from the protected
area through sampling holes in a pipe network. Sampled air
is then filtered before being analyzed by upto two MX
Technology detectors.
Applications:
Ideal for areas where access is restricted, harsh
environments and areas where a point detector would be
damaged. Such as:Lift Shafts
Floor / Ceiling Voids
Cabinet Protection
Conveyor Tunnels
Hose Down Areas
Stables
Prison Cells
Areas with Low Ceilings
The IAS800 system is available in three configurations:IAS800 twin inlet pipe configuration which can be fitted with
two detectors for monitoring one or two pipe runs.
IAS801 single inlet pipe configuration which can be fitted
with one detector.
IAS802 twin inlet pipe configuration which can be fitted with
two detectors for monitoring one or two separate pipe runs
with independant fault outputs.
Technical Specification
Product Codes
Supply Voltage
Current Consumption
Dimensions
Weight
Operating Temp
Humidity
Sampling Pipes
516.016.301
18 to 30Vdc
300mA
259w x 184h x 166dmm
2.77 Kg
-10 to +55°C (with detectors)
10 to 90% RH NonCondensing
25mm dia, 50m per inlet
516.016.303
516.016.304
516.016.305
516.016.306
ICAM IAS800 Aspirated Smoke
Dual Detector common fault monitor
ICAM Course Filter (PK10)
ICAM IAS801 Aspirated Smoke
Single Detector common fault monitor
ICAM IAS802 Aspirated Smoke
Dual Detector dual fault monitor
ICAM In-Line Filter Housing
Note: Detectors to be ordered separately.
05/17
Fire Catalogue
Chapter 7 Page 7
FIRE_Ch7_VESDA:Layout 1 09/05/2017 09:44 Page 8
Chapter 7 - VESDA
Vesda Pipe, Fittings and Test Equipment
VESDA Aspirating Pipe & Fittings are a metric standard of 25mm external diameter with suitable adaptors available for
imperial to metric conversions. (British Standard approved pipes BS5391 Part 1 1976 and BS5391 Part 1 1976 for
fittings). The British manufactured pipe is produced in red ABS under stringent quality control approved to BS EN
ISO9001, which covers all aspects of product design, manufacture and inspection.
Features
•
•
•
•
•
•
•
Toughness and durability
Chemical resistance
Easy to joint
Low Friction
Wide temperature range
Lightweight
Red colour for easy identification
Aspirating Pipe & Fittings
Pipe 25mm diameter
VESDA aspirating pipe, printed along
its length on opposite side at 450mm
intervals. 3 m length pipe.
Order in multiples of 10.
Product Code
516.018.901
Pipe 25mm diameter
Socket 25mm
Straight socket for 25mm pipe.
Order in multiples of 10.
Product Code
516.018.902
Socket 25mm
Socket union 25mm
Socket union to facilitate servicing of
pipework. Order in multiples of 1.
Product Code
516.018.903
Socket union 25mm
Socket Adaptor 25mm to 3/4"
Socket adaptor, imperial to metric, to
extend existing systems.
Order in multiples of 5.
Product Code
516.018.909
Socket Adaptor 25mm to 3/4"
90 degree Long Radius bend.
Order in multiples of 5.
Product Code
516.018.904
Long Radius bend 90°
45 deg elbow.
Order in multiples of 5.
Product Code
516.018.905
Elbow 25mm
Bend 25mm
Elbow 25mm
Chapter 7 Page 8
Fire Catalogue
05/17
FIRE_Ch7_VESDA:Layout 1 09/05/2017 09:45 Page 9
Chapter 7 - VESDA
End Cap 25mm
End cap 25mm.
Order in multiples of 5.
Product Code
516.018.906
End cap 25mm
Equal Tee 25mm.
Order in multiples of 5.
Product Code
516.018.907
Equal Tee 25mm
In-Line Filter, suitable for all Vesda
Aspirating Smoke Detectors.
Product Code
516.018.925
In-Line Filter (red) for use with Vesda
ASD systems
Dual density replaceable filter
elements for use with In-Line Filter.
Product Code
516.018.926
Replacement Filter Elements
(pack of 4)
Water Condenser for use with Vesda
ASD Systems
Product Code
516.018.927
Water Condenser
Pipe Clip 25mm.
Order in multiples of 10.
Product Code
516.018.908
Pipe Clip 25mm
Equal Tee 25mm
In-Line Filter
Filter Elements
Water Condenser
Pipe Clip 25mm
Solvent Cement (0.25 Litre Tin)
Solvent cement.
Product Code
516.018.910
Solvent cement
Capillary Tube Conical Sample Point Assembly
Capillary Tube Conical Sample Point
Assembly. 25mm socket adaptor +
2m capillary tube (tube colour - red).
Product Code
516.018.911
Capillary Tube Conical Sample Point
Assembly
Capillary Tube Flush Sample Point Assembly
Capillary Tube Flush Sample Point
Assembly. 25mm socket adaptor +
2m capillary tube (tube colour - red).
Product Code
516.018.912
Capillary Tube Flush Sample Point
Assembly
Capillary Tube 10 mm
Capillary Tube 10 mm.
10mm o/d x 30m length
(tube colour - red).
05/17
Product Code
516.018.915
Capillary Tube 10 mm
Fire Catalogue
Chapter 7 Page 9
FIRE_Ch7_VESDA:Layout 1 09/05/2017 09:45 Page 10
Chapter 7 - VESDA
Pipe Cutters
Pipe Cutter.
Product Code
516.018.918
Pipe Cutter
Pipe Ties (Red).
Order in multiples of 100.
Product Code
516.018.920
Pipe Ties (Red)
Pipe Ties
Sampling Point Label (1 reel)
Sampling point label. Order in
multiples of 100.
Product Code
517.017.005
Sampling point label
Pipe Label (1reel)
Pipe Label. Order in multiples of 100.
Product Code
517.017.006
Pipe Label
Pipework designs for Vesda Systems must be verified by the use of the “Aspire” pipework Design Software Tool. Available
for download from the Xtralis Website at www.vision-fs.com.
Test Equipment
Wire Burn Test Box
Wire burn test box designed to heat
up a measured length of special wire
to produce smoke, used to test the
transport time and performance of
Vesda aspirating smoke detectors.
•
•
•
•
•
•
Built in timer
Insulated terminals
Selectable input voltage
Illuminated power on indicator
Robust enclosure
Supplied with UK power lead
Technical Specification
Input Voltage:
110-120 or 220240VAC
Output Voltage: 6.3VAC @ 20A
IP rating:
IP30
Timer:
1 to 3 mins
Dimensions:
170w x 120d x
135h (mm)
Weight:
2.75Kg
Product Code
516.018.921
Wire Burn Test Box
Smoke Test Wire
Smoke test wire for use with the wire
burn test box.
Chapter 7 Page 10
Technical Specification
Size - 10/0.1mm, 0.078 mm2 CSA
Length – 100m
Weight – 0.25Kg
Fire Catalogue
Product Code
516.018.923
Smoke Test Wire
05/17
FIRE_Ch7_VESDA:Layout 1 09/05/2017 09:45 Page 11
Chapter 7 - VESDA
Features
VESDA-E VEU
The VEU series of aspirating smoke detectors are the
premium detector of the VESDA-E range.
An Ultra-wide sensitivity range; 15 times greater than
VESDA VLP, and provision for more sampling holes provide
an increased coverage in high airflow applications by up to
40%. Considerably longer linear pipe runs and extended
branched pipe network configurations cater perfectly to
applications with higher ceilings providing an increased
coverage by up to 80% whilst allowing convenient
detector mounting for ease of service and maintenance. A
range of revolutionary new features provide unsurpassed
detection performance, flexibility, field programmability,
connectivity and reduced total cost of ownership.
Installation, Commissioning and Operation
VEU features a robust IP40-rated enclosure and is equipped
with a powerful aspirator that provides a total pipe length of
800 m. It is fully supported by the ASPIRE-E and Xtralis VSC
software applications which facilitate ease of pipe network
design, system commissioning and maintenance
together with compatibility with existing VESDA installations.
• Short wavelength laser based detection
• Inherent absolute calibration
• Advanced detection technology equivalent to hundreds of
thousands of sensors
• Clean air barrier for optics protection
• Most robust contamination resistance
• Ultra-wide sensitivity range
• Flow fault thresholds configurable per port
• Long-life, easy-to-replace filter
• Quiet operation
• LEDs for alarm and fault signalling
• 3.5” colour touch screen for status review
• Advanced remote diagnostics
• Area coverage up to 2,000 m²
• Up to four inlet pipes
• Total pipe length of 800 m
• Referencing
• AutoLearnTM Smoke and Flow
• Seven programmable relays
• Two GPIs, monitored and unmonitored
• Ultrasonic flow sensing
• Xtralis VSC, VSM4 and ASPIRE-E PC software support
• IP 40 enclosure (not UL tested)
• Easy mounting with optional steel support bracket
• Field replaceable aspirator, sampling module, filter and
detection chamber
• VESDAnet networking
• Ethernet 100 base T
• WiFi, IEEE488.11/b/g/n
• Local host-mode USB port
• Easy cable termination access
• Event Log (20,000 events)
Colour touch screen display
The VEU-A10 detector features a 3.5” colour touch screen
display which provides a range of status information
including smoke level as well as trouble conditions. A
simple navigation system allows the user to view all the
status information.
05/17
Fire Catalogue
Chapter 7 Page 11
FIRE_Ch7_VESDA:Layout 1 09/05/2017 09:45 Page 12
Chapter 7 - VESDA
VESDAnet™
VESDA devices communicate on VESDAnet which provides
a robust bi-directional communication network allowing
continued redundant operation even during single point
wiring failures. VESDAnet enables primary reporting,
centralized configuration, control, maintenance and
monitoring.
Ethernet and WiFi connectivity
VESDA-E detectors offer Ethernet and WiFi connectivity as
standard features. The detector can be added to a
corporate network, allowing WiFi enabled tablet devices
and laptops installed with Xtralis configuration software to
connect wirelessly to the detector via the network.
Backward Compatibility
VESDA-E detectors occupy the same mounting footprint,
pipe, conduit and electrical connector positioning as
VESDA VLP and VLS detectors hence providing complete
backwards compatibility.
How it works
Air is continually drawn from the protected area through the
air sampling pipe network and into the detector by a
high efficiency aspirator. The air sampling pipe network can
contain up to four pipes. The air from each sampling pipe
passes through an airflow sensor and then a sample of the
air is drawn into the smoke detection chamber via the
sampling module, after first passing through the filter.
An additional filter provides clean air to protect the optical
surfaces inside the detection chamber from contamination.
The FlairTM detection chamber uses the equivalent of
330,000 sensors and sophisticated algorithms for detection
and particle classification.
If the detected smoke is higher than the set alarm
thresholds it is reported as an Alert, Action, Fire1 or Fire2
alarm condition.
Air is exhausted from the detector and may be vented back
into the protected area.
Alarms can be signalled via Relays and VESDAnet. Ethernet
and WiFi can be used for configuration and secondary
monitoring, and a USB interface is provided for initial setup.
A series of LEDs display Alarm, Trouble, Disable and
detector power on status. A button allows the user to Reset
or Disable the detector. In addition, an optional 3.5” LCD
displays detector status including smoke level and a
smoke level bar graph, alarm thresholds, trouble status, %
airflow level, normalization status and filter life used.
Technical Specification
Product Codes
Dimensions (WHD):
Weight:
VEU-A00
VEU-A10
VSP-960
VSP-962
VSP-962-20
VSP-963
VSP-964
VSP-965
350 mm x 225 mm x 135 mm
VEU-A00 - 4.800 kg VEU-A10 4.835 kg
Operating conditions: Ambient: 0°C to 39°C
Sampled Air:
-20°C to 60°C
Tested to:
-20°C to 55°C
Humidity:
10% to 95% RH, non-condensing
Sampling network:
Maximum area of Coverage:
2,000 m²
Minimum airflow per pipe: 15 l/m
Maximum pipe lengths: Total Pipe Length (with branches):
800 m
Maximum length per pipe, when
using four straight pipes: 100 m
Computer design tool: ASPIRE-ETM
Pipe: Inlet:
External diameter 25 mm or 1.05
in (3/4 in IPS)
Exhaust:
External diameter 25mm or 1.05
in (3/4 in IPS) via adaptor
Relays:
7 programmable relays (latch or
non-latch states)
Contacts rated 2 A @ 30 VDC (Resistive)
IP rating:
IP40
Cable access:
4 x 26 mm cable entries
Cable termination:
Screw Terminal blocks
0.2–2.5 sq mm (30–12 AWG)
Dynamic Range:
0.0002%/m to 20% obs/m
Sensitivity Range:
0.001% - 20.0% obs/m
Threshold setting range:
Alert: 0.001%-2.0% obs/m
Action:
0.001%-2.0% obs/m
Fire1:
0.001%-2.0% obs/m
Fire2:
0.001%-20.0% obs/m
Chapter 7 Page 12
Fire Catalogue
VESDA-E VEU with LED’s
VESDA-E VEU with 3.5” Display
Mounting bracket (optional) Spare Parts
VESDA-E Filter
VESDA-E Filter - 20 pieces
VESDA-E Aspirator
VESDA-E Smoke Detection Chamber
VESDA-E Sampling Module
05/17
FIRE_Ch7_VESDA:Layout 1 09/05/2017 09:45 Page 13
Chapter 7 - VESDA
Features
•
•
•
•
VESDA® VLQ
The VESDA VLQ detector is a costeffective Aspirated
Smoke Detection (ASD) solution that meets the unique
needs of numerous small area applications of up to 100 m².
Examples of these include telco landline remote
offices, base station controllers, remote base stations, small
server rooms, data centre containers, critical equipment,
packaged HVAC units, anechoic chambers, pump houses,
generator enclosures, signalling huts and modular
laboratories, just to name a few.
•
•
•
•
•
•
•
•
•
•
•
•
•
•
Laser-based absolute smoke detection
Clean air barrier for optics protection
Up to 100 m² coverage
Up to 2 x 6 m linear or up to 2 x 9 m branched pipe
lengths
2 or 4 Class A / VEWFD sampling holes
Metric/Imperial pipe inlets
Pre-alarm, Alarm and Fault Relays
5 LEDs, Pre-alarm, Fire, Fault, Filter, Power
Monitored on-board filter
AutoLearn™ Smoke
General Purpose Input (GPI)
IP30 enclosure
Xtralis QSC support
USB port for PC connection
Event log
Low power consumption
Configuration via DIP switches
Various mounting optionsess
VLQ detectors are suitable for both high and normal
sensitivity applications and offer many installation
advantages in terms of out-of-box operation, standalone
functionality and simplified pipe network.
How it Works
The VLQ detector actively draws air from the protected area
through a pipe network where two or four holes are
used. The VLQ has two pipe inlets and there are always one
or two holes on each pipe. Sampled air is then filtered
before being analyzed by the detection chamber.
The detection chamber utilizes a laser light source and
photoelectric receiver circuitry to detect scattered light
caused by the presence of smoke. Alarm (Pre-Alarm & Fire)
and Fault conditions are reported by activating the
corresponding LEDs on the simple display and dry contact
relays. The system allows configuration of both smoke
alarm and flow fault thresholds to suit the application needs.
Configuration Options
Convenient and expedient configuration of the VLQ detector
is available via DIP switches for true out-of-box operation. A
USB communication interface is also available for the Xtralis
QSC Configuration and Fire System Management Software
application.
Inputs and Outputs
The VLQ detector provides a programmable General
Purpose Input (GPI) for remote Reset, Reset + Disable,
Stand-by and External Device (PSU) monitoring functions.
Three dry contact relay outputs are available for Alarm
and Fault annunciation.
05/17
Fire Catalogue
Chapter 7 Page 13
FIRE_Ch7_VESDA:Layout 1 09/05/2017 09:45 Page 14
Chapter 7 - VESDA
Technical Specification
Product Codes
Supply voltage:
VLQ-100
VESDA VLQ Aspirated Smoke Detector
Mount Kits
VSP-890
VSP-891
Surface Mount Kit
Flush Mount Kit
Current consumption:
24 VDC nominal (18 to 30 VDC),
externally supplied
170 mA (quiescent), 190 mA
(max)
260 mm x 228 mm x 110 mm
1.2 Kg
Dimensions (WHD):
Weight:
Operating conditions:
Tested to:
-10°C to 55°C *
Recommended Detector Ambient:
0°C to 39°C
Humidity:
0% to 95% RH, non-condensing
Inlet Pipe Size
Accepts both metric and imperial standard pipe sizes
Metric: 2
5 mm external diameter
Imperial:
1.05 in (3/4” pipe) external
diameter
Sampling network:
Pipe Length:
Up to 2 x 6 m linea, rup to 2 x 9 m
branched
Sampling Holes:
2 or 4 (1 or 2 per pipe)
Sensitivity Range:
0.005% - 3.0% obs/m
Threshold Setting Range:
Fire Alarm:
0.15%/m - 3%/m
Pre-Alarm:
0.1%/m - 1.5%/m
Alarm and Flow Delays: 0 - 60 seconds
AutoLearn:
Smoke
Indication:
5 LEDs for Pre-alarm, Fire, Fault,
Filter and
Power
IP rating:
IP30
Filtration:
Field replaceable and monitored
Flow Monitoring and Reporting:
High and Low adjustable
Spare parts
VSP-892
VSP-892-20
VSP-893
VSP-893-US
VKT-100
Replacement Filter
Replacement Filter (20 pieces)
Pipe Kit (Metric)
Pipe Kit (Imperial)
VESDA VLQ-100 demo kit (consisting of
VLQ-100, pre-drilled pipes and power
supply fitted in a carry case)
Fan control:
2 x fans at fixed speed,
supervised
Relays:
3 Relays rated 2 A @ 30 VDC
(Pre-alarm, Fire, Fault)
PC Connection:
USB
General Purpose Input (GPI):
Reset, Reset + Disable, Stand-by
and External Device (PSU)
monitoring
Event Log:
1,000 events
Cable termination:
Screw terminal blocks
(0.2-2.5 sq mm, 30-12 AWG)
Warranty period:
2 years
* Product UL listed between 0°C to 39°C
Listings / Approvals:
• UL
• ULC
• VNIPPO
• LPCB
• CE
• EN 54-20
- Class A, B & C with 4 holes
• Other approvals pending
Regional approvals listings and regulatory compliance
vary between product models.
Chapter 7 Page 14
Fire Catalogue
05/17
FIRE_Ch7_VESDA:Layout 1 09/05/2017 09:45 Page 15
Chapter 7 - VESDA
Features
•
•
•
•
•
•
•
•
•
•
•
•
Maximum detection range of 150 metres for the OSI-10
Status LEDs for Fire, Fault and Power
High false alarm immunity
Dust and intrusive solid object rejection
Easy alignment with large adjustment and viewing angles
No need for precise alignment
Tolerant of alignment drift
Automatic commisioning in under ten minutes
Simple DIP switch configuration
Dual wavelength LED-based smoke detection
Simple and easy maintenance requirements
Conventional alarm interface for straightforward fire
system integration
• Three selectable alarm thresholds
OSID Smoke Detection
Open-area Smoke Imaging Detection (OSID) by Xtralis is a
new innovation in projected beam smoke detection
technology. By using advanced dual wavelength projected
beams and optical imaging technology, OSID provides a
low-cost, reliable and easy to install solution that overcomes
typical beam detection issues such as false alarm incidents
and alignment difficulties.
Simple Installation and Maintenance
The OSID system consists of up to seven Emitters, for the
90° Imager unit, located along the perimeter of the
protected area, and an Imager mounted opposite. Each
component can be mounted directly to the surface or can
be secured with the supplied mounting brackets. Battery
powered Emitters with up to five years battery life are also
available to reduce installation time and cost.
Unique Detection Technology
The OSID system measures the level of smoke entering
beams of light projected over an area of protection. A single
OSID Imager can detect up to seven Emitters to provide
a wide coverage area.
Technical Specification
Supply Voltage
20 to 30 VDC (24 VDC nominal)
Imager Current Consumption
Nominal (at 24 VDC):
4 mA (1 Emitter)
7 mA (7 Emitters)
Peak (at 24 VDC) during training
mode: 27 mA
Emitter Current Consumption
Wired Version (at 24 VDC): 350 μA
Battery Version
Built-in 5 Year Battery
Adjustment Angle
±60° (horizontal)
±15° (vertical)
Maximum Misalignment Angle
± 2°
Dimensions (WHD)
Emitter / Imager
198 mm x 130 mm x 96 mm
Operating Conditions*
Temperature
-10 °C to 55 °C *
Humidity
10 to 95% RH (non-condensing)
IP Rating
IP 44 for Electronics
IP 66 for Optics Enclosure
Status LEDs
Fire Alarm (Red)
Trouble / Power (Bi-color Yellow / Green)
Product Codes
OSI-10
OSI-90
OSE-SP-01
OSE-SPW
OSE-HPW
OSID-INST
VKT-301
05/17
Imager 7o coverage
Imager 80o coverage
Emitter Standard Power
Emitter Standard Power, Wired
Emitter High Power, Wired
OSID Installation Kit
OSID Demo Kit (2 x OSE-SPW + 1 x
OSI-90 + 1 x OSID-INST + Stand and
Carry Case)
OSID-WG
OSID-EHI
OSID-EHE
OSP-001
Fire Catalogue
Wire Guard for OSID Imager & Emitter
OSID Imager Environmental Housing
OSID Emitter Environmental Housing
OSID USB to FTDI Serial PC Interface
Cable
Chapter 7 Page 15
FIRE_Ch7_VESDA:Layout 1 09/05/2017 09:45 Page 16
Chapter 7 - VESDA
This page is left intentionally blank.
Chapter 7 Page 16
Fire Catalogue
05/17
Chapter 8 - Emergency Voice Communication (EVC)
Fire Telephones, Disabled Refuge & Toilet Alarm
There are two types of Emergency Voice Communication
(EVC) system on offer:
Omnicare - LOOP Wired
Features
• Loop wired system.
• Choice of panels from 4-way through to 127-way.
• Fully networkable.
• Multiple panels can be fitted on a network system.
• Optional connection to a fire alarm panel.
• Optional connection to a remote indicator for unattended
panels.
• Toilet alarm connection ability.
• Choice of finish for panels and outstations, including toilet
alarm.
• Any combination of outstation can be connected on a
loop.
• Button control with LED indicators.
• Lockable glazed door on control panels.
Care2 - RADIAL Wired
Features
• Radial wired system.
• 4-way panels, easily expanded to 8, 12 or 16-way by the
addition of line cards.
• System networking via expansion panels.
• Optional connection to a remote indicator for unattended
panels (add module).
• Toilet alarm connection ability.
• Choice of finish for panels and outstations, including toilet
alarm.
• Any combination of outstation can be connected to a
single panel.
• LCD display and rotary encoder for easy control.
• Robust red handset with T-coil in control panel.
• Lockable door covering handset.
06/16
Fire Catalogue
Chapter 8 Page 1
Chapter 8 - Emergency Voice Communication (EVC)
Which System?
The table below highlights the main differences between the
two systems.
General
OMNICARE
System type
Loop wired
Cabling
CARE2
Radial wired
4 core fire resisting
2 core fire resisting
Networking
Yes (maximum 127 outstations)
Yes (maximum 256 outstations)
Control panels
4, 8, 16, 32, 48, 64, 80, 96, 112 or 127 way 4 way (expandable to 8, 12 or 16 way)
Options
Finish
Operation
Grey or stainless steel
Black or stainless steel
Tactile membrane switches
LCD screen & rotary encoder
Mounting
Lockable door
Surface or flush mount with bezel
Full cover - glazed
Covers handset only
Disabled refuge
Standard outstation finish
Advance outstation finish
Induction loop
Call reset
Green or stainless steel
Green or stainless steel with Braille &
raised luminescent text
n/a
In the front panel of Advance outstation
Not available on the standard outstation
Output to feed external amplifier
At the control panel or outstation
At the control panel
Fire telephone
Fire telephone finish
Red or stainless steel
Door type
Push or slot lock
Operation
Opening door initiates call. Lift handset for speech communication
Conference call facility
External beacon/sounder
Via control panel
Via control panel (including roaming
telephones)
Available as an option
n/a
Steward telephone
Finish and operation
Green finish. Operation is the same as for the fire telephone
Roaming telephone
Roaming handset
n/a
Red
Monitored handset enclosure
n/a
holds up to 6 handsets
Black or stainless steel finish
Jack sockets
n/a
UK or American. Stainless steel finish
Via repeater unit
Direct to control panel
Disabled toilet alarm
Connection to system
Chapter 8 Page 2
Fire Catalogue
06/16
Chapter 8 - Emergency Voice Communication (EVC)
Fire Telephones, Disabled Refuge & Toilet Alarm - Loop Wired System
Features
• One master and multiple slave panels can be linked on
one system.
• Control panel options from 4-way through to 127-way.
• Remote units are connected to the control panel in a loop
configuration.
• Fully compliant to BS5839-9:2011.
• Assists companies with compliance to BS9999:2008.
• Addressable system via the remote units.
• Link to the fire detection system prevents hoax disabled
refuge calls (toilet alarms, fire and steward telephones
remain active). Can be completely or partly overridden.
• Speech steered (disabled refuge remotes) and full duplex
speech (fire telephones and steward telephones).
• Full system monitoring.
• Battery backed for use in the event of mains power failure
(24 hours in standby plus three hours use, as standard).
• Any combination of the following outstations can be
installed on a single system:
• Disabled refuge remotes (Type B outstations).
• Firefighter telephones (Type A outstations).
• Emergency (steward) telephones (Type A outstations).
• Combined disabled refuge and fire telephone.
• Disabled toilet alarms.
The OmniCare system was the first of its kind when
introduced as a combined EVC system. Since then it has
been installed worldwide and has become the system
of choice for many. The system includes a three-part
toilet alarm kit option which, like all of the remote units, is
powered from the line.
System Benefits
General Information
• There are two main components - the master control panel(s) and the remote units (outstations).
• Remote units are wired in a ring circuit configuration and
are ‘self-learning’, with an auto-commissioning feature.
• The ring circuit technology enables continued operation,
even in the event of a cable break.
• Any combination of remote units can be linked to the
control panel on a single wiring loop.
• The master control panel is typically wall mounted in a
central control room.
• Remote units are wall mounted in locations such as
refuge areas, stairwells, fallback positions, corridors and
other ‘gathering’ points, at a height easily reached by
users (as detailed in BS5839-9).
• More than one master panel can be placed on the ring
circuit, thus allowing control of local areas.
06/16
• Loop wiring provides time and cost savings on new
installations.
• Combinations of outstation can be fitted on a single loop.
• Combined outstation available featuring a disabled refuge
and fire telephone in one housing.
• Full networking and multi-panel facilities.
• All outstations powered from the line, including toilet
alarms.
• Standard and Advance disabled refuge outstations
available.
• Backup batteries supplied with every control panel.
• Robust, reliable and well established system.
• Operates even of there is a break in the loop.
Fire Catalogue
Chapter 8 Page 3
Chapter 8 - Emergency Voice Communication (EVC)
Control Panel
Features
• Available in a variety of options to suit systems of 4-127
way.
• One master and multiple slave panels can be linked on
one system (configured on installation).
• Output for unanswered call indicator; with adjustable
delay - useful when the control panel is not always
manned. (Can be used with Remote Lamp/Buzzer.)
• Volt free contact - operated when in fault, set during
installation.
• Lockable glazed door.
• Indicators for: in use/occupied, call, fault, power, charger
and speech volume.
• Handset volume control and ‘Listening’ facility.
• Fire panel interface.
• Available in grey or stainless steel finish.
Disabled Refuge (Type B)
Features
• Provides two-way communication between building
management and person(s) occupying a ‘Refuge Area’
during an emergency evacuation - typically a fire.
• User simply presses the button to initiate call (occupy
area). Further communication is hands free at the refuge
point or by the user at the control panel.
• Calls are reset either at the control panel or via the
remote, when the refuge area occupant has been
evacuated to safety.
• The refuge outstations have a volt free contact, active
when occupied, to silence loudspeakers, operate overdoor lamps, etc.
• Available in either Standard or Advanced options, with
either a green or stainless steel finish.
• Advanced unit additional features: Integral induction loop,
tactile luminescent text, Braille and a large call button with
integral high intensity LED ring.
Fire Telephone (Type A)
Features
• Telephone handset in a metal enclosure. Used by fire
officers/building control during an emergency, such as a
fire.
• Assists with the efficient evacuation of a building.
• Robust red handset with hearing aid compatible earpiece
(T-coil).
• Provides clear, full duplex, two-way communication with
the control panel.
• Conference facility via control panel.
• Speaker for local broadcast from the control panel.
• Calls are initiated by simply opening the door.
• Available in either a red or stainless steel finish.
Chapter 8 Page 4
Fire Catalogue
06/16
Chapter 8 - Emergency Voice Communication (EVC)
Steward Telephone
Features
• Designed for sports venues and stadia, the steward
telephone has the same facilities as the fire telephone.
• The distance between outstations in sports venues should
be no greater than 60 m (BS5839-9:2011 “no-one should
have to travel more that 30 m to reach an outstation”).
• Green finish.
Disabled Toilet Alarm
Features
• Fits to the system via a repeater unit (order separately).
• Powered via the line (no local power required).
• Fully compliant to BS8300:2009.
• Connect up to two toilet alarm kits per repeater (shown as
one point on the panel).
• Caller reassurance facility.
• Each kit comprises: ceiling mounted pull switch, reset
button with LED and over-door triangular light/sounder.
• Available in either a white or stainless steel finish.
Combined Unit
Features
• Disabled refuge and fire telephone in a single enclosure.
• Shows as a single presence on the control panel.
• Designed to enable correct mounting positions for each
section of the unit (as set out in BS5839-9).
Control panels & outstations are supplied as surface
mounting units. To flush mount simply add the appropriate
bezel. (This does not apply to toilet alarms.)
06/16
Fire Catalogue
Chapter 8 Page 5
Chapter 8 - Emergency Voice Communication (EVC)
Remote lamp/buzzer option
provides notification of an
unanswered call.
Enhanced 1.5 mm 4 -core fire rated cable
(standard fire resisting cable may be used for
some systems refer to BS5839-9
1.0 mm 2-core screened cable
2-core security cable
Any combination od outstation
can be placed on a single loop
(typically 20-30 units)
Up to 2 toilet alarms can be fitted
to a repeater
Systems can
be networked
Up to 200 m between units (use a repeater for
longer runs)
Enhanced 1.5 mm
4-core fire rated cable
More than one panel can be
placed on the loop to enable
control of local areas
The master panel must be
large enough to see all the outstations on the systems
System Requirements
• Fire rated enhanced four core, colour coded, cable with a
screen must be used for fire fighting systems.
• Standard fire resisting cables could be considered suitable
for:
• EVC systems for use in disabled refuges but not for fire
fighting in (a) sprinklered buildings; (b) unsprinklered
buildings less than 30m in height, provided that
evacuation takes place in three or fewer phases.
• Underground sections of cabling at sports and similar
venues.
• A repeater unit must be used if the distance between
remotes exceeds 200m.
• Disabled refuge, advance disabled refuge, fire telephone,
emergency/steward telephone, combined DRS/fire
telephone and toilet alarm units can be placed on the
same loop.
• Typically 20-30 remotes per loop.
Chapter 8 Page 6
• Repeater units are used to connect the toilet alarms to
the system. Up to two (3-part) toilet alarm kits can be
connected to a repeater unit. (Alternatively one toilet
alarm kit with an additional pull cord can be installed.
Useful for rooms with two points of call, e.g. a toilet
cubicle or shower area.)
• No local power required for any outstation, including
disabled toilet alarms.
• The capacitance of MICC cable varies between
manufacturers, if the specification is for MICC cable and
if the runs are greater than 100 metres, you may wish to
contact our technical team to ensure it is within tolerance:
• MICC lightweight 4-core with screen: 100 m
• MICC heavyweight 4-core with screen: 200 m
• Enhanced colour coded 4-core with screen: 200 m
(recommended by the manufacturer).
Fire Catalogue
06/16
Chapter 8 - Emergency Voice Communication (EVC)
Omnicare System Specification
Control Panel
Power supply
230 V AC
Power consumption
(VA)
10 VA + 1 VA per
remote fitted
Disabled Refuge
Fire
Telephone
Emergency
/ Steward
Telephone
Combined DRS &
Fire Telephone
12-40 V DC powered from ring circuit
30 mA @35 V typical
Humidity range
95% non-condensing
Temperature range
-10°C to +30°C
-10°C to +40°C
Indicators
In use, call, fault,
power, charger &
speech volume
System healthy,
status + (Advance)
system active
System healthy
System healthy,
call status
Dimensions mm
WxHxD
Mini: 461 x 340 (25)
Standard: 461 x 506
(25)
Large: 461 x 827 (25)
Standard: 154 x
154 (10)
Advance: 230 x
490
170 x 390 (20)
170 x 520
Bezel cut out mm
Mini: 420 x 300
Standard: 420 x 465
Large: 420 x 787
Standard: 136 x
136
Advance: 190 x
450
138 x 358
138 x 488
Knockouts/cable
entry points
20 mm top & rear
Finish
Grey or stainless steel
20 mm & 25 mm
Std: green or
stainless steel
Adv: green or
stainless steel with
Braille & tactile
luminescent text
Red or
stainless steel
20 mm & 25 mm*
Green
Red or stainless
steel
* 2 x 20 mm top (site wiring), and 2 x 20 mm bottom (relay contacts from disabled refuge section).
Disabled Toilet Alarm Specification
Overdoor Light / Sounder
Reset Point
Alarm type
Dimensions mm
WxHxD
Cable requirements
Ceiling Pull
90 dB @ 30 cm
White: 85 x 85 x 58
Stainless steel: 85 x 85 x 60
White: 85 x 85 x 13
Stainless steel: 85 x 85 x 14
White: 30 x 80 (diameter)
Stainless steel: 85 x 85 x 14
2-core security cable
Back box
25 mm deep single gang flush back box or ‘round cornered’ plas- White: supplied in a surface
requirements (not suptic surface box
mount enclosure Stainless
plied)
steel: 25 mm deep single
gang flush back box or ‘round
cornered’ surface box
Please Note: Stainless steel products are not intended for installation in humid areas.
BS8300:2009 requires that all new disabled toilets are fitted with an emergency toilet alarm.
06/16
Fire Catalogue
Chapter 8 Page 7
Chapter 8 - Emergency Voice Communication (EVC)
Omnicare Product Codes
Control Panels
Product code
Mini - Grey
Dimensions (mm):
410 W x 290 H x
200 D
4-way
131.4640
BVOC4M
8-way
131.4650
BVOC8M
16-way
131.4660
BVOC16M
32-way
131.4670
BVOC32M
4-way
131.4645
BVOC4MS
8-way
131.4740
BVOC8MS
16-way
131.4750
BVOC16MS
32-way
131.4760
BVOC32MS
Standard - Grey
Dimensions (mm):
410 W x 455 H x
200 D
48-way
131.4680
BVOC48
64-way
131.4690
BVOC64
Standard Stainless Steel
Dimensions (mm):
410 W x 455 H x
200 D
48-way
131.4770
BVOC48S
64-way
131.4780
BVOC64S
Large - Grey
Dimensions (mm):
410 W x 777 H x
200 D
80-way
131.4700
BVOC80
96-way
131.4710
BVOC96
112-way
131.4720
BVOC112
128-way
131.4730
BVOC128
Mini - Stainless
Steel
Dimensions (mm):
410 W x 290 H x
200 D
Bezel
Rack Mount
Kit
131.4610
BVCRFB2
131.4790
BVCRM3
131.4620
BVCRFB2S
n/a
131.4600
BVCRFB1
131.4800
BVCRM1
131.4605
Remote
Lamp /
Buzzer
Spare
Key
BVOCCA
131.4630
KEYBVE
IP66
Enclosure
Spare
Key
131.3430
BVCRIPBG
131.4360
KEYBVR
n/a
DISABLED REFUGE (DRS)
Product code
Bezel
Plasterboard
Backbox
Standard GREEN
131.3410
BVOCECPG
131.3420
BVCRMGRN
131.3960
BVCRFBG
Standard
STAINLESS STEEL
131.4820
BVOCECPS
131.4540
BVCRMSS
131.4510
BVCRFBS
Advance GREEN
131.4831
BVOCA2G
131.4833
BVOCA2GBZ
Advance
STAINLESS STEEL
131.4841
BVOCA2S
131.4843
BOCA2SBZ
Chapter 8 Page 8
n/a
Fire Catalogue
06/16
Chapter 8 - Emergency Voice Communication (EVC)
Omnicare Product Codes
Fire Telephones (FT) & Steward Telephones
Push Door
Push Door
+ Beacon
Lock Door
Lock Door
+ Beacon
Bezel
Fire telephone RED
131.4805
BVOCF
131.4815
BVOCFB
n/a
131.4825
BVOCFLB
131.4560
BVFHBEZ
Fire telephone
STAINLESS STEEL
131.4835
BVOCFS
n/a
131.4845
BVOCFSL
Steward telephone
GREEN
131.3510
BVOCET
131.3520
BVOCETB
131.3540
BVOCETL
131.4570
BVFHBEZSS
131.3550
BVOCETLB
131.3530
BVOCETBZ
Combined Units
Push Door
Push Door +
Beacon
Bezel
DRS & FT in one housing RED
131.4850
BVOCC
131.4855
BVOCCB
1131.4580
BVOCFBR
DRS & FT in one housing
STAINLESS STEEL
131.4860
BVOCCSP
n/a
131.4590
BVOCFBS
Repeater Unit - ZINTEC finish
131.3400
BVOCRIF
Disabled Toilet Alarms
White
Stainless Steel
Full Kit (3 parts + disabled WC sign)
131.3860
DTAKIT
131.3900
DTASKIT
Pull cord
131.3850
DTACP
131.3890
DTASCP
Local reset switch
131.3880
DTARP
131.3920
DTASRP
Overdoor light/sounder
131.3870
DTAODL
131.3910
DTASODL
Disabled Refuge Signs
06/16
‘Refuge Point’
Dimensions
(mm):348W x 248 H
131.3440
BVOCLAB1
‘Keep Clear,
Refuge Point’
Dimensions
(mm):348W x
248 H
131.3460
BVOCLAB3
‘These premises
have a disabled
persons evacuation
point’
Dimensions
(mm):348W x 248 H
131.3450
BVOCLAB2
‘Refuge Point’
Dimensions
(mm):120W x
120 H
131.3470
BVOCLAB4
Fire Catalogue
Chapter 8 Page 9
Chapter 8 - Emergency Voice Communication (EVC)
Fire Telephones, Disabled Refuge & Toilet Alarm - Radial Wired
Features
CARE2 is a radial wired emergency voice communication
system built to the high standard you expect from Baldwin
Boxall. It is stylish, versatile and easy to use and offers an
alternative to the well-established loop-wired Omnicare
range.
System Benefits
•Stylish, versatile and simple to navigate and control.
•Suitable for small or large systems - fully networkable.
•Monitored roaming telephone handsets - enables use
with confidence.
•System configuration via SD card, front panel or PC
connection.
•Facilitates clear communication during an emergency
event.
•Ideal for retro-fitting old star-wired systems.
•Quality built, robust system.
•Activity/fault log.
•Outstations, including toilet alarms, powered directly from
the line - no local power needed..
•Any combination of outstation on one system.
•CARE2 is an all-in-one Emergency Voice Communication
(EVC) system.
•Fully monitored and battery-backed (24 hours quiescent
and three hours functional).
•Fully compliant to BS5839-9:2011. Assists companies with
compliance to BS9999:2008.
•Remote units are wired in a radial (star) configuration
using two core (fire resisting enhanced/non-enhanced)
cable.
•Fully networkable. Networked panels are wired in a loop
configuration using 2 x two core (fire resisting enhanced)
cable.
•In the event of a break in the network loop, the system will
continue to function.
•All outstations are powered from the line, including the
roaming telephone enclosure and disabled toilet alarms.
•Optional link to fire detection system prevents hoax
disabled refuge calls (C2CFPE required). Firefighter,
roaming telephones and toilet alarms remain active.
•Speech steered; disabled refuge outstations.
•Full duplex speech; firefighter and emergency/steward
telephones.
•Any combination of the following outstations can be
installed on a single system:
•Disabled refuge (Type B outstations).
•Firefighter telephones (Type A outstations).
•Steward (emergency) telephones (Type A outstations).
•Roaming telephones.
•Disabled toilet alarms.
General Information
•There are three main components - control panel,
network expansion panels (NEP) and the remote units.
•Remote units are wired in a radial (star-wired)
configuration. Control/NEP panels are loop wired.
•Two control panels can be installed on a networked
system (the second one will serve as a ‘slave’ unit unless
activated as the ‘master’ during an emergency).
•Any combination of remote units can be connected to a
control/NEP panel.
•Any number of jack sockets (for the roaming telephone)
can be daisy chained (up to 500m; EOL resistor required
in end unit). One handset will be operational per line at
any one time.
Chapter 8 Page 10
•Outstations and control/NEP panels can be surface
mounted or flush mounted with optional bezel. Back
boxes are required for the roaming telephone jack
sockets, toilet alarm reset and overdoor light.
•The control console is typically wall mounted in a central
control room.
•Remote units are wall mounted in locations such as
refuge areas, stairwells, fallback positions, corridors and
other ‘gathering’ points, at a height easily reached by
users.
•All outstations are powered from the line, including the
disabled toilet alarms and roaming telephone handset
enclosure.
•System configuration is stored on an SD card and can be
modified either with a PC (via Ethernet or directly onto the
SD card) or without (via the encoder and display).
•Up to two disabled toilet alarms can be connected to one
line. (Or one toilet alarm with two ceiling pulls.)
Fire Catalogue
06/16
Chapter 8 - Emergency Voice Communication (EVC)
Control / Slave Panel
Features
•Unique design and easy to operate using the rotary
encoder and clear LCD screen.
•The rugged red handset (with hearing aid compatible
earpiece) is mounted in a lockable compartment.
•System configuration is stored on an SD card and can be
modified either with a PC (via Ethernet or directly onto the
SD card) or without (via the encoder and display).
•Includes a fault relay for indicator at the fire panel.
•The system can be connected to a local fire panel using
the interface module.
•Two of these panels can be installed on a networked
system (network cards required). One panel will act as
a ‘slave’ unit. The ‘slave’ unit can be activated as the
‘master’ if required (typically during an emergency).
Network expansion panel (NEP):
Features
•Facilitates expansion of the CARE2 system.
•Fit up to 15 NEPs on a network (or fourteen if installing
two ‘control’ panels), enabling systems of 256 outstations.
(If you have a requirement for a larger system, please
contact our sales department to discuss.)
•The NEP is supplied as a 4-way unit as standard. Simply
increase to 8, 12 or 16-way by fitting line cards. (Each
NEP is fitted with a network card).
•For initial system set-up and local testing (prior to
connection to the network) a ‘roaming telephone’ can be
temporarily connected to an internal socket.
•The status of local outstations can be viewed by using the
rotary encoder and LCD screen.
Each control / NEP panel is supplied as 4-way unit as standard. Simply add C2CEK4 line cards to increase to 8, 12 or 16-way.
Integral batteries (supplied) enable continuation of system use during mains power failure (24 hours in standby and three
hours operational).
Remote Lamp / Buzzer
Features
•Provides a visible and audible signal of a call on the
CARE2 system. (The control panel sounder must be
enabled, not silenced.)
•Uses the output on either a network or fire panel interface
card.
•Has an adjustable delay of 3-200 seconds.
06/16
Fire Catalogue
Chapter 8 Page 11
Chapter 8 - Emergency Voice Communication (EVC)
Expansion Cards & Modules
4-way Line Card
Features
•Each module enables the addition of four outstations.
•Add these modules to the control panel(s) and/or NEPs as required.
•Up to three modules can be added per panel/NEP.
Fire Panel Interface Card
Features
•Includes Ethernet connection ability.
•Optional module which fits in the control panel (not required if a
network card has been fitted).
•Use to keep disabled refuge outstations in ‘standby’ mode until
activated by the fire panel.
•Add for connection to remote lamp/buzzer.
Network Card
Features
•Includes fire panel interface & Ethernet connection ability.
•Add one to each control panel for including on a networked system.
Disabled Refuge (Type B)
Disabled Toilet Alarm
Features
•Provides two-way communication between building management
and person(s) occupying a ‘Refuge Area’ during an emergency
evacuation - typically a fire.
•User simply presses the button to initiate call (occupy area). Further
communication is hands free at the refuge point or by the user at
the control panel.
•Calls are reset at the control panel when the refuge area occupant
has been evacuated to safety.
•The unit has an output to feed an external induction loop amplifier.
•Disabled refuge outstations on the system are permanently ‘active’.
As an option (by fitting a fire panel interface or network card to the
control panel) they can be set to ‘standby’ mode until activated by
the fire panel.
•Available in green or stainless steel finish
Features
•The 3-part toilet alarm is connected directly to the CARE2 control panel
(or NEP).
•Powered from the line (does not require local power).
•Fully compliant to BS8300:2009.
•Up to two toilet alarm kits can be connected to one line (will show as
one point on the panel).
•Caller reassurance facility.
•Each kit comprises: ceiling mounted pull switch, reset button with LED
and over-door triangular light/sounder.
•Available in either a white or stainless steel finish.
Chapter 8 Page 12
Fire Catalogue
06/16
Chapter 8 - Emergency Voice Communication (EVC)
Fire Telephone (Type A)
Features
•Telephone handset in a metal enclosure. Used by fire officers/
building control during an emergency, such as a fire.
•Assists with the efficient evacuation of a building.
•Robust red handset with hearing aid compatible earpiece (T-coil).
•Provides clear, full duplex, two-way communication with the control
panel.
•Push door or slot lock versions available.
•Conference facility for fire and roaming telephones via control panel
(recommended maximum of five including the control panel).
•Calls are initiated by simply opening the door.
•Available in red or stainless steel finish.
Steward Telephone
Features
•Designed for sports venues and stadia, the steward telephone has
the same facilities as the fire telephone.
•The distance between outstations in sports venues should be no
greater than 60 m (BS5839-9:2011 “no-one should have to travel
more that 30 m to reach an outstation”).
•Green finish.
Roaming Telephone
Features
•Robust red handset with hearing aid compatible earpiece.
•Any number of jack sockets can be daisy chained (up to 500 m.
EOL resistor required in end unit). (One handset operational per
line at any one time.)
•The enclosure features a lockable glass door and stores up to six
handsets (order separately).
•Handsets in the enclosure are monitored at all times (green
reassurance LEDs).
•Jack sockets are flush mounting (back box required).
•UK & American options available.
Control panels & outstations are supplied as surface mounting units. To flush mount simply add the appropriate bezel. (This does not apply
to toilet alarms & jack sockets.)
06/16
Fire Catalogue
Chapter 8 Page 13
Chapter 8 - Emergency Voice Communication (EVC)
Any combination of outstation type
can be connected to a panel
All panels are supplied 4 way as
standard (Can be expanded to 8, 12
or 16 way.)
Optional fire
panel interface
(C2CFPE) (This
facility is also
included on the
C2CN network
card
Enhanced 2-core fire rated cable
(standard fire resisting cable may
be used for some systems refer to
BS5839-9)
Control panel
Up to 500 m
Systems can be
networked
2-core cable (max
resistance of 40
Ohms)
2-core security cable
Upto 2 toilet alarms
per panel call point/
line
2 x 2 core enhanced fire-rated cable
Maximum overall length of the network is 15 km (i.e
network ring length + cable length to furthest
outstation = <5 Km)
NEP panel
Up to 16 panels can be placed on the network (2 of these can be control panels, one of which will act as a slave unless
activated as the master during an emergency).
Add C2CN card to a control
panel when using on a
networked system already
include in NEP panels)
One 4-way (C2CEK4) line
card is supplied with each
panel
Add up to three further line
cards to each panel
Chapter 8 Page 14
Fire Catalogue
If a second control panel
does not require outstations to be fitted, the line card
can be removed and used in
another panel
06/16
Chapter 8 - Emergency Voice Communication (EVC)
Care2 System Specification
Control panel (&
network expansion
panel)
Power supply
200-230 V AC
50-60 Hz
Power consumption
75 VA max
Disabled
Refuge
Fire
Telephone
Steward
Telephone
Roaming
Roaming
Telephone Telephone
Jack Socket Enclosure
20-30 V DC self powered from line
Humidity range
95% non-condensing
Temperature range
-10°C to +40°C
Indicators include
4 x green LEDs: Power,
call, RR active, healthy.
3 x yellow LEDs:
Processor restart,
common fault,
processor fault.
1 x red LED:
‘status’
1 x green
LED: ‘system
ok’
1 x red LED:
1 x green
status indicator LED: status
indicator
Dimensions mm
WxHxD
430 x 310 x 130
134 x 134 x
44
130 x 330 x 75
130 x 330
x 75
Bezel dimensions
mm W x H
470 x 350
154 x 154
170 x 370
170 x 370
Bezel cut out mm
440 x 320
136 x 136
136 x 336
136 x 336
Back box
requirements
WxHxD
-
1 x green
LED: status
indicator
UK: 85 x 85
A: 41/2“ x
23/4“
430 x 310 x
130
UK (mm): 85
x8 5 x 35
A: 4“x
21/8“x 27/8“
Knockouts/cable
entry points mm
top: 23 x 20
top: 4 x 20
bottom: 4 x 25
top: 1 x 20
top: 1 x 20
Finish
Black or stainless steel
Green or
stainless steel
Red or
stainless steel
Green
top: 23 x 20
Stainless
steel
Black or
stainless
steel
Disabled Toilet Alarm Specification
Overdoor Light / Sounder
Reset Point
Dimensions mm WxHxD
Cable requirements
Back box requirements
(not supplied)
Ceiling Pull
90 dB @ 30 cm
Alarm type
White: 85 x 85 x 58
Stainless steel: 85 x 85 x
60
White: 85 x 85 x 13
Stainless steel: 85 x 85 x 14
White: 30 x 80 (diameter)
Stainless steel: 85 x 85 x 14
2-core security cable
25 mm deep single gang flush back box or ‘round cornered’
plastic surface box
White: supplied in a surface
mount enclosure
Stainless steel: 25 mm deep
single gang flush back box or
‘round cornered’ surface box
Please Note: Stainless steel products are not intended for installation in humid areas.
BS8300:2009 requires that all new disabled toilets are fitted with an emergency toilet alarm.
06/16
Fire Catalogue
Chapter 8 Page 15
FIRE_Ch9_Special_Hazards:Layout 1 28/04/2017 10:23 Page 1
Chapter 9 - Special Hazards
Special Hazards
Introduction
Tyco Fire Protection Products manufacturers and provides a
wide range of equipment suitable for use in hazardous
areas both onshore and offshore where normal equipment
cannot be safely used.
The range includes Instrinsically Safe point detectors for
use on conventional and Digital Addressable systems and
extends to Flameproof and I.S. flame detectors with
multiple interface options for use in the most demanding of
environments.
A complete range of Barriers, Housings, Callpoints and
Sounders are available to fully support the product range.
04/17
Fire Catalogue
Chapter 9 Page 1
FIRE_Ch9_Special_Hazards:Layout 1 28/04/2017 10:23 Page 2
Chapter 9 - Special Hazards
Special Hazard Flame Detectors
Features
• Reliability Choice of IR array or enhanced Triple IR solar blind
technologies allow users to tailor their systems to provide
reliable and fast fire detection.
• Fast Acting FLAMEVision reacts to minimise the effect of fire
and improve life safety through detection with less disruption
and downtime.
• Accuracy Event location information will pin point fire using
the IR array to allow targeted shutdown and suppression.
• Operator verification The optional built-in video camera
assists operator verification and ensures optimum actions are
taken. Additional benefit of post event analysis and to aid and
verify alignment.
• Optimum protection in all weather conditions FLAMEVision
maintains sensitivity using the enhanced IR sensors through
heavy rain, snow, fog and morning dew.
• Use in Hazardous explosive atmospheres FLAMEVision
is approved for protection regardless of area classifications
for all applications throughout the facility.
• Reduced spares inventory and simpler maintenance
Intrinsically safe, low cost and easy to use test equipment
simplifies maintenance and reduces service costs. Universal
mechanical mounting and cabling arrangements makes
FLAMEVision installation friendly.
• Easy integration FLAMEVision interconnects to site control
and safety systems via a range of standard industrial
interfaces.
• Dynamic masking FLAMEVision maintains detection
coverage even when a flame is part of the process being
protected.
• Complete piece of mind FLAMEVision detectors continually
monitor all electronics and perform regular optical window
tests.
FLAMEVision Flame Detectors
The FLAMEVision flame detectors use patented IR array and
triple IR solar blind technologies to provide reliable and cost
effective fire detection solutions. FLAMEVision can be
trusted in high dependency situations where fast acting and
accurate flame detection is essential. FLAMEVision
detectors offer superior performance in all weather
conditions and all lighting situations with the added benefit
of fire event location information provided by the IR array.
FLAMEVision can protect all hydrocarbon risks in classified
hazardous explosive and non hazardous atmospheres.
There is a wide range of system design options available
with flexible monitoring and control interfaces and integrated
video camera for verification purposes. Installation and
maintenance procedures are easy and efficient, minimising
the lifetime cost of ownership and reducing the need for
complex test equipment and high level operator training.
Chapter 9 Page 2
Fire Catalogue
04/17
FIRE_Ch9_Special_Hazards:Layout 1 28/04/2017 10:23 Page 3
Chapter 9 - Special Hazards
FLAMEVision FV300
FLAMEVision FV400
FLAMEVision FV300 uses Infra-Red Array based sensing
technology to provide the ultimate programmable flame
detector. An array of 256 infra-red sensors plus two optical
channels view the protected area. Powerful algorithms
running on a Digital Signal Processor (DSP) are tuned to the
characteristics of a fire and analyse the signals from these
FLAMEVision FV400 uses Triple IR Solar Blind technology
for flame detection. This provides a reliable and cost
effective solution in standard flame detection applications
especially where there is a single hazard in the field of view.
The FV400 FLAMEVision detectors use Triple IR Solar Blind
sensing technology and flame detection algorithms to
provide high performance sensing capabilities for
hydrocarbon fires. This includes the ability to reliably sense
flames through high densities of solvent vapours and black
smoke, increasing the probability of early detection with
consistent high sensitivity to flame throughout the whole
field of view. They also ensure consistent detection of many
different types of hydrocarbon fuels from alcohol to aviation
fuel. Multiple interfaces are provided with the option of an
integral CCTV camera to provide a visual means of operator
verification.
channels to quickly and reliably identify fires. A key
advantage of using an array is that the detector can
accurately identify the location of the flame within the field of
view. The location information is used to overlay a marker on
the live video output to highlight the fire location. The user
can quickly see the location of one fire or multiple fires and
decide on the appropriate action. The location information is
also available on the field network interface. User defined
areas within the field of view can be masked and un-masked
dynamically to improve reliability and maintain maximum
coverage at all times. The detector can be supplied with an
optional integral colour video camera to display a live image
of the field of view, this is in addition to the alarm location
and status information which is available as standard on the
video output.
Features
• Advanced array based detector
• Powerful signal processing on DSP with algorithms to give
reliable flame detection
• Detection range: Over 50m for 0.1m2 n-heptane pan fire
• Field of view: 90° horizontal, 85° vertical with full range
maintained
• High immunity to false alarms
• Solar blind
• Masking of areas in field of view
• Automatic optical path monitoring
• Advanced self test and service features
• Built-in video camera (option): View protected area with
alarm location and status overlay
• IEC 61508 Approved (SIL2)
04/17
Features
• Triple IR solar blind sensing technology
• Multiple Field Interfaces
• Detection range: Up to 65m for 0.1m2 n-heptane pan fire
• Automatic optical path monitoring,
• Integral flame simulation and remote walk test help
reduce the on going life time cost of the flame detecti
installation
• Video verification via the integrated optional flameproo
camera
EX II 2 GD
FV411F:
EX d IIC T4 Gb Ta -40°C to +80°C
EX d IIC T5 Gb Ta -40°C to +75°C
EX td IIIC T135°C Db Ta -40°C to +80°C
EX td IIIC T100°C Db Ta -40°C to +75°C
FV412F and FV413F:
EX d IIC T4 Gb Ta -40°C to +80°C
EX d IIC T5 Gb Ta -40°C to +70°C
EX td IIIC T135°C Db Ta -40°C to +80°C
EX td IIIC T100°C Db Ta -40°C to +70°C
Fire Catalogue
Chapter 9 Page 3
FIRE_Ch9_Special_Hazards:Layout 1 28/04/2017 10:23 Page 4
Chapter 9 - Special Hazards
Technical Specifications
Mechanical - Detector
Dimension:
155.5 mm (6.1”) H x 153 mm (6”)
W x 92 mm (3.6”) D
Weight :
4 kg 8.8 Lb
Gland entry:
2 x M20
Material:
Stainless steel 316L, ANC4BFCLC
to BS3146: Part 2
Guard/label plate:Stainless steel 316S16 to BS
1449: Part 2
Screws external: Stainless steel 316 A4
Detection window:Sapphire
Camera window: Toughened glass
FV400
Modbus
4-20mA Sink or source
Conventional detector I/F
Tyco MZX Digital
Fire & fault relay contacts NO or NC
Composite Video o/p (Camera option only)
Hart interface *
Electrical
FV300
Supply voltage: 20 to 30 Vdc
Current consumption (max):
196mA quiescent, 205 mA Alarm
(24 Vdc)
Heater:
90 [email protected] vdc
Connections:
2.5mm2 (14AWG) Terminals
Mechanical - Bracket
Dimension:
181 mm (7.2”) H x 125 mm (5”) W
x 95 mm (3.75”) D
Material:
Stainless steel 316S16 to BS
1449: Part 2
Weight:
1.54 kg 3.2 Lb
Environmental
Operating temp: -40°C to +80°C
Storage temp:
-40°C to + 80°C
Operating temp of camera:
-10°C to +50°C
Storage temp with camera:
-20°C to + 70°C
(operating temperature is reduced for T5
risks)
Relative humidity :99% (non condensing)
Enclosure:
IP 66
516.300.006
516.300.008
516.300.007
EN54 Approval
CPD EN54-10:2002 + A1:2005
FV400 is classified as Class 1 on the Extended and Normal
range settings.
FV400 is certified as Class 3 on the Half range setting.
FV300 is classified as Class 1
(1V p-p) into 75 Ohm via twisted
pair balum
Horizontal resolution:
Standard 450 TVL
Light sensitivity (-30 IRE): 0.3 Lux
Detector performance
Range (0.1m² n heptane):
FV400 65m, FV300 50m
Field of view:
90° horizontal, 85° vertical
* - Feature implemented by future field software update
Product Codes
Flameproof certification:
FV300
Ex II 2GD EX d II C Ext D A21 IP66/67 T4 T135oC
(T amp = -40oC to 80oC) or T5, T100 (T amp = -40oC
to +70oC)
Camera Specification
Composite video:
FV400
Supply voltage: 15 to 30 Vdc
Current consumption:
12 mA quiescent 22mA Alarm
(24 Vdc - interface dependant)
Camera:
185 mA @24vdc
Heater:
[email protected]
External supply required only for camera, heater or MODBUS options
Connections:
2.5mm2 (14AWG) Terminals
516.300.411
516.300.412
516.300.413
FV311S
FV311SC
Infrared array flame detector
Infrared array flame detector PAL camera
FV311SC-N Infrared array flame detector NTSC camera
FV411f
Triple infrared flame detector
FV412f
Triple infrared flame detector
with PAL camera
FV413f
Triple infrared flame detector
with NTSC camera
Ancillary equipment
517.300.001
MB300
517.300.002
517.300.021
517.300.022
WH300
WT300
CTI300
517.300.024
CTI400
517.300.006
MK300
FLAMEVision mounting
bracket
FLAMEVision weather hood
FLAMEVision walk test tool
FLAMEVision off-line
configuration tool
FLAMEVision off-line
configuration tool
FLAMEVision field spares kit
Interfaces
FV300
Modbus
4-20mA Sink or source
Fire & fault relay contacts NO or NC
Composite video o/p
Chapter 9 Page 4
Fire Catalogue
04/17
FIRE_Ch9_Special_Hazards:Layout 1 28/04/2017 10:23 Page 5
Chapter 9 - Special Hazards
Features
• Triple waveband infrared solar blind flame detection for
optimum false alarm immunity
• Unrivalled black body rejection over a wide range of
source temperatures
• Range adjustable to 50 metres for a 0.1m2 petrol pan fire
• Discrimination of optical faults (dirty windows) from other
faults by the built-in self test feature
• Housing designed for easy installation of cabling
• Models also available with relay or 4-20mA outputs
• Patented dual filter for complete solar blindness
• 100° field of view on IS versions
• 90° field of view on Flameproof versions
• ATEX, IECEX & FM Approval
S200 Plus Triple IR Solar Blind Flame Detector-IEC 61580 Approved (SIL2)
Unlike other flame detectors on the market the MINERVA
S200 PLUS is available in both Intrinsically Safe (EEx ia) and
Flameproof (EEx d) models.
The flameproof models are suffixed by the letter " f " and are
ATEX Certified EEx d IIC T6. The detectors are suitable for
zones 1 and 2 where group IIC gases or lesser hazards can
be intermittently present in explosive concentrations.
The intrinsically safe models are suffixed by the letter " i "
and are ATEX Certified EEx ia IIC T5. As part of an
intrinsically safe circuit, it is suitable for zones 0,1 and 2
where group IIC gases or lesser hazards can be
continuously present in explosive concentrations.
Technical Specification
Product Codes
Detector Material:
Dimensions:
Weight:
Gland Entry:
Range:
517.001.266
517.001.263
517.001.184
Operating Temp:
Intrinsically Safe=
Flame Proof=
Response Time:
Sensitivity:
Relative Humidity:
Enclosure:
Stainless Steel 316L/316
167H x 167W x 89D MM
4.5Kg
2 x 20mm
0.1m2 petrol at 50m
0.4m2 petrol at 60m
S200+ Spares Kit & Sealant
S200+ Weather Protection Assembly
S200+ Detector Mounting Bracket
Datasheet - Product Code PSF102U “Minerva S200 Plus Series”
- 40o c to +80o c (IECEX & ATEX)
- 20o c to +60o c/+80o c
(IECEX/ATEX)
Field Selectable 3, 6 and 12s
3 range settings
95% (100% intermittent)
IP 66 and IP 67
Approvals
Various models are certified by a number of approval
bodies including those listed below.
ATEX Approved models have a suffix ‘1’ as the third digit.
FM Approved models have a suffix ‘2’ as the third digit.
04/17
Fire Catalogue
Chapter 9 Page 5
FIRE_Ch9_Special_Hazards:Layout 1 28/04/2017 10:23 Page 6
Chapter 9 - Special Hazards
S200 Plus Triple IR Solar Blind Flame Detector
Additional Features
• Flexible mounting and angular adjustment
• 2 x 20 mm field cable entries
• IP66/67 housing designed for external use
• Rugged 316 stainless steel housing and mounting bracket
• Variable response times and sensitivity settings
• Remote self test and range setting
• True window test in detection area (i.e. not in the edge of the
window)
• Terminals provided for Remote LED connection where relevant
• BASEEFA (CENELEC) certified
• Approved to EN54 Pt 10 (Except FV282F)
• IEC 61508 Approved (SIL2)
• FM, DNV and LRS certified
• Very low power consumption (0.35mA)
• Models available with Conventional or Analogue Addressable
interface (requires 2 core cable only)
Interface
Conventional 4-20mA MZX Addressable
S231i+
4
S231f+
4
S232f+
4
S241i+
4
S241f+
4
S261f+
4
S271i+
4
S271f+
4
FV282F+
4
4
Relay
4
4
4
Ex ‘ia’
4
Approvals
ATEX
Ex ‘d’
4
4
4
4
4
FM
Ex ‘d’
Product Codes
516.037.004
516.037.003
516.037.015
516.038.004
516.038.003
516.040.002
516.041.004
516.041.003
516.040.014
Types S231i+, S241i+, S251I+ and S271i+
IECEx BAS 05.0051
Ex ia IIC T5 (-20°C < Ta < +40°C )
or T4(-40°C < Ta < +80°C )
II 1 G EEx ia IIC T5 or T4 (-40°C < Ta < +80°C )
Types S231f+, S241f+, S251f+ and S261i+ and S271f+
IECEx BAS 05.0056
Ex d IIC T6 or T5 (-20°C < Ta < +60°C )
or T4(-40°C < Ta < +80°C )
Ex II 2 G EEx d IIC T6 or T5 (T amp =-20°C < Ta < +80°C )
Chapter 9 Page 6
Fire Catalogue
04/17
FIRE_Ch9_Special_Hazards:Layout 1 28/04/2017 10:24 Page 7
Chapter 9 - Special Hazards
System 800 Fire Detection for Hazardous Areas
Features
•
•
•
•
•
Addressable I.S. MX Technology
Compatible with S271i+ flame detector
Compatible I.S. callpoint.
ATEX certified intrinsically safe Ex II 1 GD System
Suitable for use in Zone 0, 1, 2, 20, 21 & 22
System 800 Fire Detection for Hazardous Areas
A complete range of ATEX and ICEX certified detectors suitable
for use in Zone 0, 1, 2, 20, 21 & 22 Areas. MX digital
addressable for use on Minerva MX Fire Controllers.
There is a risk of fire or explosion in all areas containing
flammable substances in the form of liquids, gasses, dust or
materials. Where these combustible materials are mixed with air
in sufficient concentration they form a flammable atmosphere
and the areas containing them are designated Hazardous
Areas. When a source of ignition, such as a spark, is applied in
a hazardous area, an explosion could take place. Electrical
equipment supplied for use in Hazardous Areas must comply
with requirements to ensure that its introduction into the area
does not increase the existing risk. System 800 is an MX
TechnologyTM Intrinsically Safe (I.S) system for use in Hazardous
Areas which can be connected to the MX Fire Detection
Systems installed in the Safe Areas.
The System designer must be familiar with ATEX certification
and have successfully completed an appropriate recognised
course in Intrinsic Safety. Design of the system requires that
the designer has all the information concerning the
installation correctly documented. The nature of the hazard
must be defined by the customer and a survey carried out to
determine the proximity of the safe area to establish cable
runs.
In order that an Installation will comply with the ATEX
certification designated for each system, it is essential that
the certified devices are connected with cables of the
specified limits. These limits have been certified for specific
classifications of hazard in order that energy storage is
limited.
The number of devices connected to the barrier and located
in the Hazardous Area must always be limited to not more
than the listed maximum.
The use of the MX designer Software tool will ensure correct
loop loading and it’s use is essential to the design process.
System 800 is for use in MX Technology Addressable Fire
detection circuits.
Datasheet PSF129U
Manual 17A-02-DETEx
The probability of a flammable mixture being present is
defined by a zone number. Flammable gasses are classified
in Groups and their minimum spontaneous ignition
temperature is categorised by Class. Tyco Fire Protection
Products supplied equipment marked EEx ia IIC T5 would
be suitable for use in worst case conditions. E.G. Zone 0
(ia), Hydrogen (IIc), T5 (100 deg C). The Fire Alarm
Equipment and Safety Barriers should be placed as near as
possible to the containment wall of the Hazardous Area.
This minimises the cable lengths between the barrier and
the Hazardous Area and thus the capacity to store energy.
04/17
Fire Catalogue
Chapter 9 Page 7
FIRE_Ch9_Special_Hazards:Layout 1 28/04/2017 10:24 Page 8
Chapter 9 - Special Hazards
801PHEx Smoke and Heat Detector
The 801PHEx Optical Smoke & Heat
Detectors form part of the 800Ex
Series of MX Addressable Fire
Detectors. The detector plugs into the
5BEX base.
The mode of detector may be:
• Optical smoke only detector
(sensitivity - High, Normal or Low)
• HPO smoke detector (sensitivity High, Normal or Low)
• Heat only rate-of-rise (A1R)
detector (no sensitivity selection)
• Heat fixed temperature 60°C (A2S
no sensitivity selection)
• Optical (sensitivity - High, Normal
or Low) combined with heat fixed
temperature 60°C (A2S)
• HPO (sensitivity - High, Normal or
Low) combined with heat fixed
temperature 60°C (A2S)
Technical Specification
ATEX Code:
BASA01ATEX1394X
II 1GD
CE 1180
EX la IIC T5
EX laD 20 T100OC
IECEx BAS 07.00-63X
UI=28V II=93mA PI=0.65W CI=0=
LI=0
Weight:
0.2Kg detector and base (approx)
Operating Temp. Range:
-25°C to +70°C
Storage Temp:
-40°C to +70°C
Relative Humidity:
95% non- condensing
Product Code
516.800.530
801PHEx Optical Smoke + Heat
Detector
Manual Vol 17A-02-PHEx
801CHEx CO & Heat Detector
The 801CHEx Carbon Monoxide plus
Heat Detector form part of the 800Ex
Series of MX Addressable Fire
Detectors. The detector plugs into
the 5BEX base.
The mode of detector may be:
• Heat only detector (A1R or A2S)
(sensitivity: - High, Normal or Low)
• Compensated Carbon Monoxide
detector (sensitivity: - High, Normal
or Low)
• Compensated Carbon Monoxide
detector (sensitivity: - High or
Normal) combined with heat (A1R)
Technical Specification
ATEX Code:
BASA01ATEX1394X
II 1GD
CE 1180
EX la IIC T5
EX laD 20 T100OC
IECEx BAS 07.00-63X
UI=28V II=93mA PI=0.65W CI=0=
LI=0
Weight:
0.2Kg detector and base (approx)
Operating Temp. Range:
0°C to +55°C/-20°C to +40°C
Storage Temp:
-20°C to +55°C
Relative Humidity:
95% non condensing
Product Code
516.800.531
801CHEx Carbon Monoxide + Heat
Detector
Manual Vol 17A-02-CHEx
801HEx Heat Detector
The 801HEx Heat Detectors form
part of the 800Ex Series of MX
Addressable Fire Detectors. The
detector plugs into the 5BEX base.
The mode of detector may be:
• EN54-5 A1R, rate-of- rise normal
ambient
• EN54-5 A2S, fixed 60°C
• EN54-5 CR, rate-of-rise high
ambient
Technical Specification
ATEX Code:
BASA01ATEX1394X
II 1GD
CE 1180
EX la IIC T5
EX laD 20 T100OC
IECEx BAS 07.00-63X
UI=28V II=93mA PI=0.65W CI=0=
LI=0
Weight:
0.2Kg detector and base (approx)
Operating Temp. Range:
-25°C to +70°C
Storage Temp:
-40°C to +70°C/-40°C to +80°C
Relative Humidity:
95% non-condensing
Technical Specification
ATEX Code:
BASA01ATEX1394X
II 1GD
CE 1180
EX la IIC T5
EX laD 20 T100OC
IECEx BAS 07.00-63X
UI=28V II=93mA PI=0.65W CI=0=
LI=0
Weight:
0.2Kg detector and base (approx)
Operating Temp.Range:
-20°C to +70°C
Storage Temp:
-40°C to +80°C
Relative Humidity:
90% non-condensing
Product Codes
516.800.066
801FEx I.R. Flame Detector
516.800.067
811FEx Marine I.R. Flame Detector
Product Code
516.800.532
801HEx Heat Detector
Manual Vol 17A-02-HEx
801FEx Flame Detector
The 801FEx point type flame
detector forms part of the MX
Technology®range of digital
addressable fire detectors. The
detector plugs into the 5BEX base.
The 801FEx is a full featured solar
blind flame detector and can detect
a 0.1 m2 fire at a range of 20 m.
Chapter 9 Page 8
Fire Catalogue
Manual Vol 17A-02-FEX
04/17
FIRE_Ch9_Special_Hazards:Layout 1 28/04/2017 10:24 Page 9
Chapter 9 - Special Hazards
CP840Ex Break Glass Call Point
The CP840Ex Weatherproof Break
Glass Call Point is designed to
monitor and signal the condition of a
switch contact associated with the
break glass.
Technical Specification
ATEX Code:
BASA01ATEX1394X
II 1GD
CE 1180
EX la IIC T5
EX laD 20 T100OC
IECEx BAS 07.00-63X
UI=28V II=93mA PI=0.65W CI=0=
LI=0
Operating Temp Range:
-25°C to +70°C
Storage Temp: -30°C to +70°C
Relative Humidity: Up to 95% RH
non condensing
Product Code
Technical Specification
ATEX Code:
BASA01ATEX1394X
II 1GD
CE 1180
EX la IIC T5
EX laD 20 T100OC
IECEx BAS 07.00-63X
UI=28V II=93mA PI=0.65W CI=0=
LI=0
Product Code
514.001.062
IF800Ex MX Digital Addressable
Interface Module Assembly
514.800.513
CP840Ex MX Digital Addressable
Break Glass Call Point
Manual Vol 17A-02-CPEx
IF800Ex Interface Module
The Intrinsically Safe IF800EX
Interface Module is designed to
monitor fire contacts such as
sprinkler flow switches. The IF800Ex
is contained within a grey
compression moulded glass filled
polyester box with 2 x 20 mm cable
gland holes.
Manual Vol 17A-02-IFEX
The electronic components are
mounted on a double sided printed
circuit board built into a potted
module formed from a plastic
moulding. Connectivity is via two
terminal blocks fitted to the PCB.
04/17
Fire Catalogue
Chapter 9 Page 9
FIRE_Ch9_Special_Hazards:Layout 1 28/04/2017 10:24 Page 10
Chapter 9 - Special Hazards
EXI800 Interface Module & Galvanic Isolators
The EXI800 Interface Module when
used with a galvanic isolator, provides
a path for an MX panel to
transparently communicate to slave
devices (800Ex Detectors, IF800Ex
Interface Module or CP840Ex
Addressable Break Glass Call Point)
connected to the Intrinsically Safe
Loop. The EXI800 interface reduces
the standard MX loop supply voltage
and signalling currents to levels that
are acceptable for hazardous areas.
The EXI800 can detect a short circuit
on the left-loop, the right-loop, or the
IS spur and will isolate the offending
circuit from the other loop
connections.
The IS loop output of the EXI800
interfaces with the Pepperl & Fuchs
KFDO-CS-Ex1.54 Galvanic Isolator
supplying loop voltage and signalling
currents to the Intrinsically Safe Loop.
Both single channel and dual channel
Galvanic Isolators are available.
The EXI800 is supplied complete with
a service tool EX dongle that is
required to activate the address
programming when using the
standard MX service tool. The
MTL5525 Isolating Sounder Driver
enables an intrinsically safe sounder
located in the hazardous area, to be
controlled from the safe area. The
MTL5525 has one channel and is
suitable for connecting certified loads
in Zone 0, IIC, T4-T6 hazardous
areas.
Product Codes
514.001.063
EXI800 Interface Module
517.001.306
Single channel KFDO-CS-EX1.54
GALVANIC ISOLATOR
517.001.305
Two channel KFDO-CS-EX2.54
GALVANIC ISOLATOR
517.001.304
MTL5525 I.S. Sounder Driver
Manual Vol 17A-02-EXI
IS Barrier Enclosure
The MTL ’DX’ Series enclosures will
house the EXI800 (20mm pitch),
Pepperl & Fuchs KFDO-CS-Ex1.54
Galvanic Isolator (20mm pitch) and
the MTL5525 I.S. Sounder Driver
(16.2mm pitch). The units are DIN
rail mounted with 70mm of rail
supplied with the DX070 and 170mm
of rail with the DX170. The
enclosures are usually selected on
the number of units they will
accommodate. The following table
shows the capacity of each of the
enclosure types.
Enclosure
MTL5500 isolators 16.2mm Pitch
Product Codes
517.001.248
DX070 Enclosure
517.001.247
DX170 Enclosure
MTL7700 barriers 7.5mm Pitch
DX070
4 (2*)
9 (5*)
DX170
10 (8*)
22 (18*)
* Use these figures when two IMB57 mounting brackets for tagging/earth rail accessories are included.
Chapter 9 Page 10
Fire Catalogue
04/17
FIRE_Ch9_Special_Hazards:Layout 1 28/04/2017 10:24 Page 11
Chapter 9 - Special Hazards
Features
• Glass Reinforced Polyester Enclosure – light, strong and
not subject to corrosion.
• Resettable Element.
• Explosion protected EExe (ATEX Approved).
• In line and end of line resistors.
• Red Epoxy Finish.
• 7 x terminals.
• Lift flap for extra protection against inadvertent operation.
• 1 x changeover switch.
• Captive cover screws.
• Key operated test facility – simple but secure.
• 1 x M20 bottom cable entry.
BG MIM800 Callpoint EX II 2 GD
An Ex II 2 GD Dust Approved & Increased Safety (EExemd)
Resettable Manual Alarm Call Point for use with the EExd
Flameproof MIM800 input module in EExd housing on an
Addressable Detection & Releasing System in gas and dust
explosive risks.
Please note that the above part is only compatible with
Consys Version 17.0 and above when used with
577.800.067.
Technical Specification
Product Code
Protection:
514.001.107
Explosion Protected
EExed(Increased Safety)
Certification:
ATEX approved Ex II 2 GD
BAS02ATEX2105X
EExemdIICT4
CENELEC EN50014
EN50019
EN50018
EN50028
Suitable for use in Zones 1 & 2
Voltage:
Up to 250V
Certified Temperature: -20oC to +50oC
Ingress Protection:
IP66 & 67
Terminals:
7 x 2.5mm²
Switch Ratings(1 x Changeover):
DC 0-30V 5A (Resistive) or 3A
(Inductive)
DC 30-50V 1A Resistive or Inductive
AC 0-254V 5A Resistive or Inductive
Cable Entries:
1 x M20 Bottom
Weight:
1.2Kg
Material:
Anti Static U.V. Resistant Glass
Reinforced Polyester
Finish:
Red Epoxy Paint
Resistors:
Alarm: 100 Ohm
EOL: 250 Ohm
Labelling:
Burning House Symbol
Dimensions (W X H X D):
120mm x 126mm x 75mm
04/17
Fire Catalogue
EX II 2 GD Dust Approved & Increased
Safety (EExemd) Resettable Manual
Alarm Callpoint
Chapter 9 Page 11
FIRE_Ch9_Special_Hazards:Layout 1 28/04/2017 10:24 Page 12
Chapter 9 - Special Hazards
Features
•
•
•
•
•
Copper Free Metal Alloy Aluminium Housing
Explosion Protected to EExd (ATEX Approved)
9 x Terminals
3 x M20 Cable Entries
Fast Interrupt Mode for Call Points
MIM800 Input Module in EExd Housing
An EExd Flameproof MIM800 Addressable Module for
extending the monitoring of Call Points and other Alarm
Inputs on an MX, ZX and MZX Addressable System in gas
and dust explosive risks.
Please note that the above part is only compatible with
Consys Version 17.0 and above when used with
514.001.107.
Technical Specification
Protection:
Certification:
Voltage:
Certified Temperature:
Ingress Protection:
Terminals:
Cable Entries:
Weight:
Material:
Dimensions
(W X H X D):
Chapter 9 Page 12
Product Code
Explosion Protected EExd
(Flameproof)
Ex II 2 GD LOM02ATEX2037
EExdIICT6
CENELEC EN50014
EN50018
EN50019
EN50281-1-1
EN60439-1
Suitable for use in Zones 1 and 2
to IEC 60079-10
Suitable for use in Zones 21 and 22
to EN50281-3
40Vdc
-20oC to +55oC
IP67
9 x 2.5 mm²
3 x M20 (No Blanking Plugs)
0.8 Kg
Metal Alloy Aluminium - Copper
Free
577.800.067
MIM800 Input Module in EExd Housing
108 mm x 98 mm x 90 mm
Fire Catalogue
04/17
FIRE_Ch9_Special_Hazards:Layout 1 28/04/2017 10:24 Page 13
Chapter 9 - Special Hazards
System 620 Fire Detection for Hazardous Areas
Features
•
•
•
•
•
•
Conventional I.S. system
Suitable for worst case (EEx ia IIC T5)
High Performance Optical (HPO) smoke detector
Compatible with S231i+ flame detector
Compatible I.S. callpoint
Suitable for use in Zone 0,1,2,20,21& 22
System 620 Fire Detection
A complete range of ATEX and ICEX certified detectors
suitable for use in Zones 0,1,2,20,21 & 22 areas for use on
conventional panels. There is a risk of fire or explosion in all
areas containing flammable substances in the form of
liquids, gasses, dust or materials. Where these combustible
materials are mixed with air in sufficient concentration they
form a flammable atmosphere and the areas containing
them are designated Hazardous Areas. When a source of
ignition, such as a spark, is applied in a hazardous area, an
explosion could take place. Electrical equipment supplied
for use in Hazardous Areas must comply with requirements
to ensure that its introduction into the area does not
increase the existing risk. System 620 is an Intrinsically Safe
(I.S.) system for use in Hazardous Areas which can be
connected to a conventional fire Alarm Controller installed in
the Safe Area.
The System Designer must be familiar with ATEX
certification and have successfully completed an
appropriate recognised course in Intrinsic Safety. Design
of the system requires that the designer has all the
information concerning the installation correctly
documented. The nature of the hazard must be defined by
the customer and a survey carried out to determine the
proximity of the safe area to establish cable runs.
The number of devices connected to the barrier and located
in the Hazardous Area must always be limited to not more
than the listed maximum.
When a mixture of devices is connected to any one zone the
numbers must be reduced in proportion to the ratio of the
load presented to the barrier. When a System includes the
use of an S231i+, it must be remembered that the load it
presents to the circuit is twice that of a detector. A mixture of
large and small load devices connected to a zone will
require a calculation for the number of allowed detectors.
System 620
System 620 is for use in conventional fire detection circuits.
Two Sounder Systems, (one earthed and one isolated), are
available and either can be used with System 620.
Datasheet - PSF122U
The probability of a flammable mixture being present is
defined by a Zone Number. Flammable gases are classified
in Groups and their minimum spontaneous ignition
temperature is categorised by Class. Tyco Fire Protection
Products supplied equipment marked EEx ia IIC T5 would
be suitable for use in worst case conditions. Eg. Zone 0 (ia),
Hydrogen (IIc), T5 (100 deg C). The Fire Alarm Equipment
and Safety Barriers should be placed as near as possible to
the containment wall of the Hazardous Area. This minimises
the cable lengths between the barrier and the Hazardous
Area and thus the capacity to store energy.
In order that an Installation will comply with the ATEX
certification designated for each system it is essential that
the certified devices are connected with cables of the
specified limits. These limits have been certified for specific
classifications of hazard in order that energy storage is
limited.
04/17
Fire Catalogue
Chapter 9 Page 13
FIRE_Ch9_Special_Hazards:Layout 1 28/04/2017 10:24 Page 14
Chapter 9 - Special Hazards
High Performance Optical Smoke
The MR601TEX has been developed
to overcome the slower response of
the optical detectors to hot burning
fires, by increasing the sensitivity of
the optical detector when it is
associated with a rapid change in
temperature. In this way it is intended
to become a detector which can
cover some of the risks currently
covered by ion chamber detectors.
Smoke detectors will not detect
burning alcohol or other clean
burning liquids which do not
generate smoke particles.
If environmental conditions rule out
the use of smoke detectors, then a
heat detector of the type
MD601Ex/MD611Ex may provide an
acceptable, though less sensitive,
alternative. For general use, and particularly where the ambient temperature may be low, a 'Rate-of-Rise' heat
sensor is to be preferred. This type of
sensor reacts to abnormally high
rates of change of temperature and
provides the fastest response over a
wide range of ambient temperatures.
A fixed temperature limit is also incorporated in these detectors. In many
environments, e.g. kitchens and boil-
er rooms, sudden, large changes in
temperature are considered 'normal'.
Rate-of-rise detectors are generally
not suitable in these cases and fixed
temperature [static] types should be
used.
ATEX Code:
Cenelec Code:
Ex II 1GD
Ex ia IIC T5/
Ex iaD 20
T100°C
Operating Temp Range:
-20°C to +70°C
Storage Temp:
-25°C to +80°C
Relative Humidity:
95% noncondensing
Product Code
516.054.011.Y (Vol 01B-04-D12)
MR601TEX Conventional High
Performance Optical Smoke Detector
Heat Detectors
ATEX Code :
Cenelec Code:
Ex II 1GD
Ex ia IIC T5/
Ex iaD 20
T100°C
Operating Temp Range:
-20°C to +70°C
Storage Temp:
-25°C to +80°C
Relative Humidity:
95% noncondensing
Product Codes
516.052.051.Y (Vol 01B-04-D11)
MD601EX Conventional Rate of Rise
Heat Detector
516.052.041.Y (Vol 01B-04-D11)
MD611EX Conventional Fixed
Temperature Heat Detector
Flame Detectors
Flame detectors, unlike smoke and
heat detectors, do not rely on
convection to transport the fire
products to the detector nor do they
rely on a ceiling to trap the products.
They can therefore be used to
protect large open areas without
sacrificing speed of response to
flaming fires. In order to ensure full
coverage however, flame detectors
do require direct line of sight to all
parts of the protected area.
Infra-red flame detectors such as the
601FEx are designed to respond
rapidly to fires which involve
clean-burning fuels such as alcohol
or methane, i.e. fires which would not
be detected by smoke detectors. The
601FEx Flame Sensor, by virtue of its
operating wavelength and flicker
discrimination is insensitive to normal
environmental influences. For
outdoor use a solar-blind detector
[e.g. the S200 Plus] should be used.
The 601FEx Flame detector should,
normally, only be used inside
buildings to supplement heat and
smoke detectors.
ATEX Code:
Cenelec Code:
Ex II 1GD
Ex ia IIC T4/
Ex iaD 20
T135°C
Operating Temp Range:
-20°C to +70°C
Storage Temp:
-40°C to +80°C
Relative Humidity:
90% noncondensing
Product Codes
516.600.066 (Vol 01C-02-D10)
601FEx Infra-Red Flame Detector
516.600.067 (Vol 01C-02-D10)
601FEx-M Infra-Red Flame Detector
(Marine)
Enhanced Carbon Monoxide Fire & Heat Detector
The MDU601EX detector is a
combined CO and Rate of Rise Heat
Detector where the sensitivity of the
CO detector is enhanced in response
to a fast rate of change of
temperature.
ATEX Code:
Ex II 1GD
Cenelec Code:
Ex ia IIC T5/
Ex iaD 20
T100°C
Operating Temp Range:
-10°C to +55°C
Storage Temp:
-20°C to +55°C
Relative Humidity:
90% noncondensing
Product Code
516.061.001.Y (Vol 01B-04-D14)
MDU 601EX Enhanced Carbon
Monoxide Fire & Heat Detector
5BEX Detector Base and Ancillaries
ATEX Code:
Cenelec Code:
Ex II 1GD
Ex ia IIC T5/
Ex iaD 20
T100°C
Operating Temp Range:
-25°C to +70°C
Storage Temp:
-40°C to +80°C
Relative Humidity:
95% noncondensing
Chapter 9 Page 14
Product Codes
517.050.023
5BEX 5” Universal Ex Base
517.050.603
DHM-5B deckhead mounting
517.001.120
System 601 EOL Unit (Pk 10)
Fire Catalogue
04/17
FIRE_Ch9_Special_Hazards:Layout 1 28/04/2017 10:24 Page 15
Chapter 9 - Special Hazards
Features
• Intrinsically Safe
• Weatherproof to IP67
• Compatible with System 620
Intrinsically Safe Callpoint - ATEX Approved
The MCP220Ex is a conventional callpoint for use on the
ATEX Certified System.
Technical Specification
Product Code
Dimensions:
Weight:
Material:
Colour:
ATEX Code:
Cenelec Code:
514.001.109
ATEX Cert:
IP Rating:
93H x 98W x 66Dmm
270g
PC/ABS
Red
Ex II 1GD
EX ia IIC T4 Ga
/EX iaD T135°c Da
SIRA 06ATEX2131X
IP67
MCP220Ex Red Callpoint intrinsically safe
for use with ATEX certified conventional
system 620.
Features
• Intrinsically safe
• Weatherproof to IP66/IP67
• Robust GRP Housing
BG3 Intrinsically Safe Conventional Callpoint -Atex Approved
This manual fire alarm call point is designed in accordance
with the latest European Callpoint Standard (EN54-11).
Units are supplied in self coloured GRP with a ‘Burning
House’ duty label as standard.
Weatherproof to IP66/IP67 and available certified
intrinsically safe, simple apparatus manufactured from
glass reinforced polyester (GRP) which provides a robust,
corrosion free construction and ensures effective and
reliable operation in harsh industrial and offshore
environments.
Technical Specification
Model:
Protection:
BG3I
Explosion Protected EExia
(Intrinsically Safe)
Certification:
CENELEC EN50014, 020
BASEEFA EExia IIC T4
Cert No. BAS00ATEX1067X
Suitable for use in Zones 0,1 & 2
Voltage:
Up to 28V (IS)
Certified Temp: -55°C to +55°C
Ingress Protection: IP66 & IP67
04/17
European Standard
for Callpoints:
EN54-11
Terminals:
6 X 4.0mm2
Cable Entries:
2 X M20 Bottom
Weight:
0.5Kg
Material:
UV resistant glass reinforced polyester
Finish:
Natural Red GRP
Product Code
514.001.059
Fire Catalogue
Intrinsically Safe Callpoint (BG3I4NBN)
Chapter 9 Page 15
FIRE_Ch9_Special_Hazards:Layout 1 28/04/2017 10:24 Page 16
Chapter 9 - Special Hazards
Features
• Polyester Enclosure – light, strong and not subject to
corrosion.
• Break Glass.
• Explosion protected EExe (ATEX Approved).
• In line and end of line resistors.
• Red.
• 9 x terminals.
• Lift flap for extra protection against inadvertent operation.
• 1 x changeover switch.
• Captive cover screws.
• No hammer required – the glass is covered by a
membrane thus protecting the operator from glass
fragments.
• Key operated test facility – simple but secure.
• 2 x M20 bottom cable entries.
BG Conventional Callpoint EX II 2 GD
This EX II 2 GD Dust Approved & Increased Safety
(EExemd) Conventional Break Glass Manual Alarm Call
Point is fitted with a 470 ohm Alarm Level Resistor and a
4K7 ohm EOL Resistor for use with Tyco Conventional
Detection Circuits including the DIM800 and DDM800 MX
Modules.
It is also fitted with a removable link which allows it to be
connected on its own or with other Conventional Devices to
a Tyco Conventional Detection Circuit.
Technical Specification
Product Code
Protection:
514.001.108
Explosion Protected EExed
(Increased Safety)
Certification:
ATEX approved Ex II 2 GD
BAS02ATEX2105X
EExedmIICT4
CENELEC EN50014
EN50019
EN50018
EN50028
Suitable for use in Zones 1 & 2
Voltage:
Up to 250V
Certified Temperature: -20oC to +50oC
Ingress Protection:
IP66 & 67
Terminals:
9 x 2.5mm – up to 60V
Switch Ratings(1 x Changeover):
DC 0-30V 5A (Resistive) or 3A
(Inductive)
30-50 1A Resistive or Inductive
AC 0-254V 5A Resistive or
Inductive
Cable Entries:
2 x M20 Bottom
Weight:
1.2Kg
Material:
Anti Static U.V. Resistant Glass
Reinforced Polyester
Finish:
Red Epoxy Paint
Resistors:
Alarm: 470 Ohm
EOL: 4K7 Ohm
Labelling:
Burning House Symbol
Chapter 9 Page 16
Fire Catalogue
EX II 2 GD Dust Approved & Increased
Safety (EExemd) Conventional Break
Glass Manual Alarm Callpoint
04/17
FIRE_Ch9_Special_Hazards:Layout 1 28/04/2017 10:24 Page 17
Chapter 9 - Special Hazards
Features
• Robust GRP Body
• Suitable for offshore and petrochem
• Certificated Intrinsically Safe
XB8 Intrinsically Safe Beacon
This ruggedised, intrinsically safe and weatherproof
beacon is intended for use in potentially explosive
atmospheres, and has been designed with high ingress
protection to cope with the harsh environmental conditions
found offshore and onshore in the oil, gas and
petrochemical industries.
Please refer to MEDC for guidance on cable capacitance
and barriers.
Technical Specification
Product Code
Certification:
540.001.038
CENELEC EN50014, 20 & 39
BAS02ATEX1258X
EExia IIB T4
Zones 0,1 & 2
Material:
UV stable glass reinforced
polyester body. Clear
polycarbonate cover/lens.
Retained stainless steel cover
screws.
Finish:
Painted Red
Tube Type:
Xenon discharge
Lens Colour:
Clear
Terminals:
8 x 2.5mm2
Flash Rate:
1 flash per second
Cable Entries:
Up to 3 x M20 via knockouts
Tube Energy:
0.5 Joules
Weight:
1.4kg
Certified Temperature: -55°C to + 60°C
Ingress Protection:
IP66 & IP67
Tube Life:
>1 x 106 Flashes
Voltage:
24V via suitable barrier
Current Consumption: 71mA max nominal
04/17
Fire Catalogue
Intrinsically Safe Xenon Beacon
(XB8BB024CNR)
Chapter 9 Page 17
FIRE_Ch9_Special_Hazards:Layout 1 28/04/2017 10:24 Page 18
Chapter 9 - Special Hazards
Features
• For use in hazardous areas
• Robust GRP construction
• Powerful Output, up to 122dBA
DB3B Flameproof Horn Sounder
This lightweight all GRP flameproof sounder is intended for
use in potentially explosive gas and dust atmospheres and
has been designed with high ingress protection to cope
with the harsh environmental conditions found offshore and
onshore in the oil, gas and petrochemical industries.
The flamepaths, flare and body, are manufactured
completely from a UV stable glass reinforced polyester.
Stainless steel screws and sinter are incorporated thus
ensuring a corrosion free product. A tapered flamepath is
used to overcome the problems of assembly of parallel
spigot flamepaths.
Technical Specification
Product Code
Terminals:
Mounting:
Cable Entries:
Tone Selection:
Certification:
Material:
Weight:
Ingress Protection:
Voltage:
Certified Temperature:
Chapter 9 Page 18
2
6 x 2.5 mm
Stainless steel bracket with ratchet
facility
2 x 20 mm EExd.
27 user selectable tones.
ATEX Ex d Gas & Dust Cert. no.
Baseefa13ATEX0231X. Certified to:
EN60079-0,1,31Ex II 2GD, Ex d IIC
T4/T5/T6 Gb, Ex tb IIIC
T135°C/T100°C/T85°C Db, IP66
Body & horn in anti-static, UV
stable, glass reinforced polyester.
Swivel bracket & captive cover
screws in stainless steel.
6.0 kg approx
IP66 & IP67/NEMA 4X & 6
12 VDC to 48 VDC
-55°C to +70°C
DB3BDGD048N2BNR
Fire Catalogue
DB3B Flameproof Horn Sounder
04/17
FIRE_Ch9_Special_Hazards:Layout 1 28/04/2017 10:24 Page 19
Chapter 9 - Special Hazards
Features
• Robust Corrosion Resistant GRP body
• High Power (5 Joule)
• Certificated Flameproof
XB11 Flameproof Xenon Beacon
These certified beacons have been designed for use in
potentially explosive gas and dust atmospheres and harsh
environmental conditions. The glass reinforced polyester
enclosures are suitable for use offshore or onshore, where
light weight combined with corrosion resistance is required.
The beacon housing is manufactured completely from a
U.V. stable, glass reinforced polyester. Stainless steel
screws and mounting bracket are incorporated ensuring a
totally corrosion free product.
Technical Specification
Product Code
Voltage:
Tube Energy:
Peak Current
Consumption (mA):
Effective Intensity (Cd):
Peak Intensity (Cd):
Power Consumption
(Watts):
Note:
540.001.039
Weight:
Certified Temperature:
Ingress Protection:
Terminals:
Entries:
Certification:
24Vdc
5 Joules
Flameproof Xenon Beacon
(XB11B02406RNBNNNR)
320
29
22213
8
The Cd figures are for a clear
lens @ 1Hz flash rate. For red
lens multiple by 0.15
2.5Kg
EExd -55°C to + 70°C (T4)
-55°C to + 55°C (T5)
-55°C to + 40°C (T6)
IP66 & IP67
6 x 2.5mm2
2 x 20mm ISO EExd.
BASEEFA EExd IIB
135°C (-55 to AMB +70°C)T4
100°C (-55 to AMB + 55°C)T5
85°C (-55 to AMB + 40°C)T6
Cert. No. 99 ATEX 2195X.
CENELEC EN50014 and
EN50018
Material
Body: Glass reinforced polyester
Lens: Glass
Cover Screws + Backstrap:
Stainless steel 316
Finish: Red
04/17
Fire Catalogue
Chapter 9 Page 19
FIRE_Ch9_Special_Hazards:Layout 1 28/04/2017 10:24 Page 20
Chapter 9 - Special Hazards
Intrinsically Safe Barriers - Atex Approved
The following section relates to a range of intrinsically safe barrier and isolator equipment for use with Tyco Fire
Protection Products manufactured fire detection systems. It essentially encompasses the relevant MTL5500 and
MTL7700 series barriers plus the associated housing options as an alternative to existing MTL700 series equipment.
On all issues of intrinsically safe system design, please refer to Manual 26A for guidance.
Galvanic Isolators - MTL5500
The MTL5561 is a two channel
interface for use with conventional
detectors located in hazardous areas.
This galvanic isolator is CE marked,
and replaces the MTL3043 barrier
option. It is suitable for connecting
loads in Zone 0, IIC, T4-T6 hazardous
areas if suitably certified.
The MTL5525 Isolating Sounder
Driver enables an intrinsically safe
sounder located in the hazardous
area, to be controlled from the safe
area. The MTL5525 barrier is
designed as a CE marked
replacement for the existing
MTL3021 barrier. It has one channel
and is suitable for connecting loads
in Zone 0, IIC, T4-T6 hazardous
areas if suitably certified.
When designing new systems or
upgrading existing MTL3000 series
systems to MTL5500 series, please
use the appropriate MTL “DX” series
enclosure equipment (16.2mm
pitch).
Product Codes
517.001.302
MTL5561 2 Channel Galvanic Isolator
517.001.304
MTL5525 I.S. Sounder Driver
Zener Barriers - MTL7700
The MTL7700 Series intrinsically safe
shunt-diode safety barriers are
innovative devices designed to
provide exceptionally high packing
densities, straightforward installation
and simplified connection,
commissioning and maintenance
facilities. The MTL7700 Series
include secondary replaceable
fuses. These are useful where there
is the possibility of faults occurring
during commissioning, which would
otherwise blow the barriers’ internal
safety fuses.
Chapter 9 Page 20
One secondary replaceable fuse for
each barrier channel is provided and
is lower in value than the safety
related fuse. Fuses are packaged in
small mouldings which can be
latched in a disconnect position to
break the safe and hazardous areas
during commissioning, maintenance
and fault finding, thus avoiding the
need for additional disconnect
terminals.
Product Code
517.001.301
MTL7728 + Zener Safety Barrier for
conventional detection circuits
designed in accordance with System
601
546.004.005
Intrinsically safe sounder circuit
interface module
Please note that this barrier is a
direct alternative for the MTL728+
barrier.
Fire Catalogue
04/17
FIRE_Ch9_Special_Hazards:Layout 1 28/04/2017 10:24 Page 21
Chapter 9 - Special Hazards
Safety Enclosures
UC Series Enclosures
The UC series of enclosures
provides a simple but effective
means of mounting and protecting
the MTL3000 series units, in safe
areas. A standard lightweight
enclosure with transparent lid, which
can accommodate 4 units. The
polycarbonate enclosure is impact
resistant, flame retardant and
dustproof to IP65.
Product Code
517.001.196
UC2 4 Way Barrier Housing
MT Series Enclosures
The MT series of enclosures
provides a simple, effective means
of mounting and protecting MTL700
Series barriers in safe areas or
low-risk hazardous areas. Three
lightweight polycarbonate enclosures
with see through lids accommodate
up to 2, 5 and 12 barriers in the safe
area. All the enclosures are supplied
ready fitted with a nickel plated brass
busbar mount, so barriers can be
installed and wired up immediately
without special tools.
Product Codes
517.001.198
MT2 2 Way Zener Barrier Housing
517.001.199
MT5 5 Way Zener Barrier Housing
517.001.200
MT12 12 Way Zener Barrier Housing
The ERL7 earth rail is a nickel plated
3 x 10mm rail (1 metre long),
suitable for a do-it-your self
mounting arrangement. It will
accommodate up to 2.5 ETM7 earth
terminals per barrier location for
terminating earth returns and cable
screens from the hazardous area.
Product Codes
517.001.205
ERL7 Earth rail for I.S. systems
517.001.206
ETM7 Earth termination connection
system
517.001.207
IMB7 Insulating mounting block
Ancillaries
The IMB7 mounts on a flat surface or
top hat rail (35mm) or G-profile rail
and acts as a convenient method for
mounting the earth busbar.
04/17
Fire Catalogue
Chapter 9 Page 21
FIRE_Ch9_Special_Hazards:Layout 1 28/04/2017 10:24 Page 22
Chapter 9 - Special Hazards
Features
• Continuous detection despite extremely large monitoring
area.
• Easy and rapid installation of the maintenance free sensor
cable.
• Very high resistance to extreme ambient influences
(immune against heat, cold, humidity, corrosion, strong
winds and draft).
• Undiminished operation under electromagnetic
interference.
• Unprecedented security against false alarms.
• Very high sensor cable service life of up to 30 years.
• Temperature profile over the complete measurement
range delivers exact information of location, size and
spread of fire.
• Very low maintenance costs as maintenance and trouble
shooting can be done from the control unit.
• VdS certified to EN 54 part 5
• One controller unit will drive up two 8 km spurs or one 8
km loop.
• Easy integration into existing installations.
• Each sensor cable divided into up to 256 zones.
• Individual configuration of 5 alarm criteria per zone.
• Network connection through Modbus, TCP/IP, FTP and
SCPI interfaces.
MZX SensorLaser™ Plus Fibre Optic Linear Heat Detection System
The MZX SensorLaser™ Plus guarantees fast and
continuous fire detection even in difficult and varying
ambient conditions. This linear heat detection system
enables long and heavily fragmented facilities such as traffic
and supply tunnels, cable routes and conveyor belts as well
as large scale buildings such as production halls, cold
stores and multi storey car parks to be monitored at all
times. The MZX SensorLaser™ Plus is ideal for use in areas
that are hard or impossible to access after installation, e.g.
false floors, since maintenance and troubleshooting can be
carried out from the control unit.
The fibre optic sensor cable itself is maintenance free and,
thanks to its particularly robust characteristics, offers a high
level of security against false alarms. The sensor cable is
insensitive to dust, dirt, moisture, high temperatures (up to
approx. 90 °C), pressure and the action of vibration and
wind as well as corrosive atmospheres. Because of its
purely passive, optical analysis process, the MZX
SensorLaser™ Plus is even immune from electromagnetic
interference caused by generators, energy routes, cables or
electric motors.
The MZX SensorLaser™ Plus delivers precise information
about the location, size and spread of a fire even under
ambient conditions that would cause other fire detection
systems to fail.
The MZX SensorLaser™ Plus enables a measuring range of
up to 8 km per sensor cable. Up to 2 spurs each with an 8
km measurement range, or 1 loop with an 8 km range can
be connected. Since the ambient conditions in a monitoring
area of this size can vary enormously, each sensor cable
can be divided into up to 256 zones. Several alarm criteria
can be freely defined in each zone. This level of precision
adjustment allows the MZX SensorLaser™ Plus to provide a
high level of resistance to false alarms and precise fire
detection despite contrary and variable ambient conditions.
The accessible laser radiation emitted by the Class 1M laser
is not hazardous to the eyes (provided there are no other
optical instruments in the path of the beam), while operation
is absolutely fail-safe even in the event of a break in the
cable. In addition, the sensor cable can be used in
explosive atmospheres (ATEX zones) up to zone 0 without
any additional measures being required. In contrast to
conventional fibre optic systems, the low laser output of <
20mW ensures that the measuring system has a long
service life.
Zone Configuration
Ambient conditions (temperatures) can fluctuate sharply
over a measuring range of many hundreds of metres. This
makes it essential to divide the measuring range into zones
that can be adapted optimally to the ambient conditions on
the basis of differing alarm criteria. This ensures high
detection reliability and also security against false alarms.
The MZX SensorLaser™ Plus allows the measuring range to
be very finely divided into zones. Up to 256 zones can be
defined for each sensor cable, with up to 5 alarm criteria
configurable in each zone. Another 2 alarm criteria respond
when there is a temperature drop, enabling them to be used
e.g. in tunnels to warn of black ice.
Chapter 9 Page 22
Fire Catalogue
04/17
FIRE_Ch9_Special_Hazards:Layout 1 28/04/2017 10:24 Page 23
Chapter 9 - Special Hazards
MZX SensorLaser™ Plus Fibre Optic Linear Heat Detection System Con’t.
Control Unit
With ten product variants, permitting measuring ranges of 1
to 8 km, the MZX SensorLaser™ Plus can be configured to
suit the particular project.
Sensor Cable
The sensor cables offered are optimised for a rapid
response time. The sheathing is flame retardant, halogen
free and resistant to dust, dirt, moisture, corrosive
atmospheres and most organic solvents. Both types of
sensor cable offer adequate protection against rodents and
are designed for a service life of 30 years.
There are two different types of sensor cable for differing
project requirements. The MZX SensorLaser™ Plus Safety
cable can be used under normal ambient conditions. It is
particularly flexible and extremely versatile.
Where the sensor cable is expected to be exposed to high
mechanical stresses, we recommend that the MZX
SensorLaser™ Plus Steel Wire Armoured cable be used.
This sensor cable, which was specifically developed for
heavy duty applications, is particularly suitable where high
tensile forces and high lateral pressures can occur.
The cable length will be individually cut to the customer
specified length and 2 connectors are fitted for easy
handling. The cable should be commissioned in multiples
of one metre and therefore the order for the cable has to be
placed per metre.
Every order for sensor cable must include the
corresponding connectors, which will be assembled by the
supplier. The cable with pre assembled connectors offers
fast commissioning of the system without any additional
splicing.
Plastic Clamps
The plastic of these clamps is UV resistant, halogen free
and particularly robust in ambient conditions.
Steel Clamps
The clamps in these sets are made of stainless steel or zinc
plated steel and are rubber protected. The rubber
protection guarantees that the sensor cable is not damaged
if friction occurs. For every clamp 2 x nuts are included for
fixing to the anchor.
Connection Cable
Connection to the MZX Fire Alarm Panel is by means of the
MZX SensorLaser™ Plus Connection Set. This set consists
of 3 x cables. For connection of the Fire Alarm Panel to one
end of the sensor cable a D-Sub connector is included. The
other end of the sensor cable is desoldered which provides
a quick connection into the MZX System without any
soldering effort.
Enhanced Communication
The MZX SensorLaser™ Plus iBox allows the 20 relay
outputs supplied as standard to be expanded up to 2 x 256
outputs so that each zone can be assigned its own relay
output. This could, for instance, be used to control fire
extinguishing systems. The iBox also enables connection to
SCADA or process control systems via Modbus TCP or
Modbus RTU.
The number of relays can be extended using the MZX
SensorLaser™ Plus Relay Controller Set. This set consists
of a pre-programmed field bus controller, one Digital Output
Module and an End module. It also comes with 8 x relays
and accessories for easy wiring.
Mounting Materials
For professional mounting of the sensor cables four
different types of mounting sets are available. These sets
are designed for different applications. They can be used
for the mounting of the sensor cable to the wall and the
ceiling. Every set contains 100 x clamps, 100 x anchors and
1 x SDS drill bit.
LAN (10/100M)
Modbus / TCP/IP
SCPI/FTP
Modbus/TCP/IP/SCPI/FPT SCPI
SCADA
System
Controller Unit
Supervisory Control
and Data Acquisition
Interface Box
PC Work Station
20 Relay Outputs
1 Fault
19 Alarms
MZX Panel
Relay Controller
Set
Relay Extension
Set
By means of the Relay Controller Set and the Relay Extension Set an
additional 256 relays per sensor cable can be connected.
04/17
Fire Catalogue
Chapter 9 Page 23
FIRE_Ch9_Special_Hazards:Layout 1 28/04/2017 10:24 Page 24
Chapter 9 - Special Hazards
MZX SensorLaser™ Plus Fibre Optic Linear Heat Detection System Con’t.
Complies with the essential requirements of the following
applicable European Directives and carries the CE marking
accordingly:
• The Low Voltage Directive 73/23/EEC amended by
93/68/EEC
• The EMC Directive 2004/108/EC
Conforms with the following product standards:
EMC
IEC61326:1997+A1:1998+A2:2000
EN61326:1997+A1:1998+A2:2001
CISPR11:1997+A1:1999 / EN55011:1998+A1:1999
IEC61000-4-2:2001/EN61000-4-2:1995+A1:1998+A2:2001
IEC61000-4-3:2002/EN61000-4-3:2002
IEC61000-4-4:2001/EN61000-4-4:1995+A1:2001+A2:2001
IEC61000-4-5:2001/EN61000-4-5:1995+A1:2001
IEC61000-4-6:1995+A1:2000 /EN61000-4-6:1996+A1:2001
IEC61000-4-8:2001/EN61000-4-8:1993+A1:2001
IEC61000-4-11:1994+A1:2000
EN61000-4-11:1994+A1:2001
Canada: ICES-001:1998
SAFETY
IEC61010-1:2001/EN61010-1:2001
IEC60825-1:2001/EN60825-1:1994+A11:1996+A2:2001
Canada:CAN/CSA-C22.2No.61010-1:2004
USA:UL61010-1:2004;FDA21CFR1040.10+Laser Notice
No.50
Product Codes
516.016.310
Technical Specification
Operating temperature range:
-10°C to +60°C (2 channel
options: from -5°C)
Storage temperature range:
-40°C to +80°C
Operating humidity range:
0% to 95% RH (2 channel options:
15% to 85% RH) non condensing
Dimensions (H x W x D):
88 x 448 x 364 mm (19” rack)
Weight:
9 kg
Fibre types:
MM 50/125 μm graded index MM
62.5/125 μm graded index
Dynamic range:
30 dB (2-way loss)
Sensing temperature range:
-273°C to +700°C depending on
sensor coating
Optical connector:
E2000; 8° angled
Number of channels:
1, 2 depending on channel option
Computer interface:
USB, LAN
Relay board:
4 inputs / 20 outputs
Power supply:
10 V to 30 Vdc
Power consumption:
15 W typically, at 20°C ambient
temperature < 40 W (entire
operating conditions)
Measurement times:
from 10s to 30s
Available spatial resolution settings:
1 m; 1.5 m; 3 m; 5 m; 8 m
Available measurement modes:
Single ended/Dual ended;
including fibre break recovery
Internal data storage capability:
150 traces total
Power Supply (option) operating conditions:
0°C to +50°C; non condensing;
indoor use only
Laser class (IEC 60825-1: 2001):1M
516.016.311
516.016.312
516.016.313
516.016.333
516.016.334
516.016.314
516.016.315
516.016.316
516.016.317
516.016.318
516.016.319
516.016.320
516.016.321
516.016.322
516.016.322.C
516.016.323
516.016.323.C
516.016.324
516.016.325
516.016.326
516.016.327
516.016.328
516.016.329
516.016.330
516.016.331
Chapter 9 Page 24
Fire Catalogue
MZX SensorLaser™ Plus 1/1 – 1 km
range, 1 sensor cable.
MZX SensorLaser™ Plus 1/2 – 1 km
range, 2 sensor cables.
MZX SensorLaser™ Plus 2/1 – 2 km
range, 1 sensor cable.
MZX SensorLaser™ Plus 2/2 – 2 km
range, 2 sensor cables.
MZX SensorLaser™ Plus 3/1 – 3 km
range, 1 sensor cable.
MZX SensorLaser™ Plus 3/2 – 3 km
range, 2 sensor cables.
MZX SensorLaser™ Plus 4/1 – 4 km
range, 1 sensor cable.
MZX SensorLaser™ Plus 4/2 – 4 km
range, 2 sensor cables.
MZX SensorLaser™ Plus 8/1 – 8 km
range, 1 sensor cable.
MZX SensorLaser™ Plus 8/2 – 8 km
range, 2 sensor cables.
MZX SensorLaser™ Plus Connection Set.
MZX SensorLaser™ Plus iBox
MZX SensorLaser™ Plus Relay Controller
Set.
MZX SensorLaser™ Plus Power Supply.
MZX SensorLaser™ Plus Safety Cable
(per metre).
MZX SensorLaser™ Plus Safety
Connector.
MZX Steel Wire Armoured SensorLaser™
Plus Cable (per metre).
MZX SensorLaser™ Plus Steel Connector.
MZX SensorLaser™ Plus Setting Tool.
MZX SensorLaser™ Plus Relay Extension
Set.
MZX SensorLaser™ Plus Zinc Plastic
Clamp Set. (PK 100)
MZX SensorLaser™ Plus Steel Plastic
Clamp Set. (PK 100)
MZX SensorLaser™ Plus Steel Zinc Clamp
Set. (PK 100)
MZX SensorLaser™ Plus Stainless Steel
Clamp Set. (PK 100)
MZX SensorLaser™ Plus Spare Unit.
MZX SensorLaser™ Plus Demo Unit.
04/17
FIRE_Ch11_Gas Detection:Layout 1 16/12/2016 13:25 Page 1
Chapter 10 - Gas Detection
Scott Meridian Fixed Gas Detector
This section introduces the Meridian Universal Fixed Gas Detector from Scott Safety, a Tyco International
company and a world leader in the design and manufacture of industrial gas detectors. The Meridian Universal Fixed
Gas Detector can interface directly with MZX and ZETTLER PROFILE fire detection and alarm systems using the
DDM800 Fire and Gas Module, to provide an economical combined fire and gas solution Industrial facilities protected
by MZX and ZETTLER PROFILE fire detection and alarm systems often have a requirement for gas detection.
Employing the fire detection system’s high-quality cabling infrastructure to also communicate toxic or flammable gas
hazards provides a practical and economical means of achieving total environmental protection.
Meridian Applications
Commercial Gas Detection Applications
Brewers, Distillers
and Wineries
Local Authority
Beverage brewing, fermenting and
distilling. Beverage storage and
dispensing
Schools, Colleges and Universities
CO2 and O2 monitoring.
Flammable gas and CO2 (refrigerant) in
laboratories
O2 detection in MRI suites.
O2 detection in oxygen bottle stores.
N2O detection in operating theatres and
bottle stores
CL2 and O3 detection in swimming pool
purification chemical stores.
CH4 detection.
CO and petrol vapour detection.
LPG and CNG detection for compressors
and storage tanks.
CO and NOx detection from diesel engine
emissions
LPG detection in commercial kitchens
Hospitals
Swimming pools
Automotive
Boiler rooms
Car Parks
Fuel Filling Stations
Bus stations
Hospitality
Hotels and restaurants
Industrial Gas Detection Applications
Chemical
Construction
Mining
Defence
Nuclear
Process or pipeline monitoring
Brownfield development
Building construction
Tunnelling
General mining
Gold extraction
Fuel monitoring.
Fuel process monitoring.
Solvent detection, plus O2 depletion and toxics
CH4 and H2S detection and landfill build.
CH4 detection in apartment blocks (meter cup
boards).
CH4 and H2S detection
CH4 and H2S and oxygen detection
Hydrogen cyanide used for extracting gold from ore
Hydrazine (missiles) and jet fuel (aircraft) detection
H2 & HF and O2 monitoring.
Commercial Gas Detection Applications
Power Generation
Gas-fired power stations
Gas turbines
Coal mill monitoring.
NOx reduction equipment
12/16
CH4 detection.
CH4 detection. Very high temperature:
Also requires heat detectors and flame
detectors.
CO monitoring (for fire detection).
NH3 and propane detection. Open path
IR detector for monitoring valve racks and
across stacks
Fire Catalogue
Chapter 10 Page 1
FIRE_Ch11_Gas Detection:Layout 1 16/12/2016 13:25 Page 2
Chapter 10 - Gas Detection
Industrial Gas Detection Applications
Manufacturing
Steel production.Coke ovens, BOS
plants, Blast Furnaces, Concast.
Vehicle production plants.
Aerosol manufacturing
Semiconductor manufacturing
Gas suppliers.
Telecoms
Switch room monitoring
Water
Clean water sites
Waste water sites.
Pharmaceutical
Wet wells
Manufacturing process.
Laboratories.
HVAC
Duct monitoring.
Refrigerant monitoring
Food
Food and beverage production.
Landfill
Sterilisation
Borehole monitoring.
Biogas monitoring.
Pulp and Paper
Process monitoring.
Chapter 10 Page 2
CO, SO2, CH4, O2, NH3 detection.
Robust products required. ‘ppm’ level
Benzene detection using PID.NH3
detection in carbonising process
Engine test cells (CO NOx, petrol vapour),
paint plants (Vapours, CH4 for drying
bays), pits (O2 monitoring).
Butane or propane leak detection form
aerosol canisters and storage tanks. Fast
detection needed on aerosol conveyers
Highly toxic gases: arsine, phosphine,
diborane, silane, germane plus many
other ‘standard’ gases.
Toxic, flammable and oxygen gas
leakage from production and bottle filling
processes.
CH4 H2S and O2 monitoring from cable
ducts. H2 monitoring in battery rooms
CL2, SO2, NH3, O3 storage tank leak detection
CH4, H2S, O2 detection. Aggressive
atmosphere.CH4, CO2 and O2 monitoring
in digester gas for engine supply gas
Flammable vapour and H2S detection.
Solvent detection, plus O2 depletion and toxics.
Low level VOC detection is required (PID). ETO is
sometimes used for sterilisation. O2 detection is
needed in filling rooms where N2 is used.
Flammable gas, O2 and CO2 (refrigerant)
detectors
Gas detection in ducts
NH3 and CO2 detectors which can work at very low
temperatures.
NH3 and CO2 and O2 detection
(refrigeration). CO2 and O2 monitoring
(drink dispensing).
SO2 detection.
CH4 & CO2 concentration monitoring
CH4 & CO2 concentration monitoring in
engine supply pipes
Chlorine and SO2 detection (bleaching agents).
Fire Catalogue
12/16
FIRE_Ch11_Gas Detection:Layout 1 16/12/2016 13:25 Page 3
Chapter 10 - Gas Detection
Features
Advancements in Sensor Technology
• Electrochemical, Infrared, Catalytic Bead and Solid
State Sensors
• Scott Rock Solid™ Sensor Technology
• All sensors can be replaced under power in
hazardous locations
• Electrochemical sensors offer support for multiple
ranges with one sensor
• Calibration of electrochemical sensors is range
invariant
Multiple Communication Protocols
• 4-20 mA, Modbus
• Wired HART
• Wireless HART, ISA100.11A
Certifications
• IECEx, CSA, ATEX, CE
• INMETRO, China Ex, CCCF, A&C Tick, MRD, ABS
Scott Meridian Fixed Gas Detector
Scott’s Meridian Universal Gas Detector is an innovative
next generation gas detection solution. Meridian’s single
detector head supports combustible and toxic sensors.
Designed for ease of use, Meridian significantly reduces
upfront investment and on-going maintenance costs.
With global approvals and SIL2 certification from TUVRheinland, Meridian ensures best in class performance and
safety.
The Meridian Universal Fixed Gas Detector can interface
directly with MZX and ZETTLER PROFILE fire detection and
alarm systems using the DDM800 Fire and Gas Module, to
provide an economical combined fire and gas solution.
Industrial facilities protected by MZX and ZETTLER
PROFILE fire detection and alarm systems often have a
requirement for gas detection. Employing the fire detection
system’s high-quality cabling infrastructure to also
communicate toxic or flammable gas hazards provides a
practical and economical means of achieving total
environmental protection.
12/16
The Meridian Universal Gas Detector utilizes a single
detector head to easily accept all sensor types for toxic and
flammable risks. There is no requirement for distinct
personality boards in the gas detector or different detector
heads to make the instrument behave as a combustible or
toxic gas detector. The Meridian gas detector accepts all
sensor types in one detector. Simply attach the specific
toxic or combustible sensor to the universal detector head
and the Meridian Universal Gas Detector will automatically
determine the type of gas to be detected. Installation of the
sensor is a simple plugand-play action.
Multi-headed sensor options are available simultaneously
across a single transmitter base,providing comprehensive
coverage with reduced cabling requirements
Full-Range Detection
The Meridian Universal Gas Detection System detects a full
range of combustible and toxic gases.
Fire Catalogue
Chapter 10 Page 3
FIRE_Ch11_Gas Detection:Layout 1 16/12/2016 13:25 Page 4
Chapter 10 - Gas Detection
Meridian Transmitter Assy.
Item No
1
Quantity
1
2
1
3
4
4
1
5
6
1
1
8
4
Part No.
096-3401
096-3407
096-3404
Description
3-4 Wire Power Supply PCB
2-Wire Power Supply PCB
Terminal/Relay MODBUS RS-485 PCB
(Standard with 3-4 Transmitter)
M4 X 85 Standoff
3-4 Wire I.S Barrier Assy
2-Wire I.S Barrier Assy
Terminal Block Cover
LCD Display Assembly
LCD Display Assembly with Heater
Blind Display Assembly
Housing O-Ring
6-32 x 3/4 Philips Pan Head
007-0011
096-3448
096-3449
074-0528-01
096-3447-01
096-3447-02
096-3447-03
009-0056
076-0221
Combustable Gases
Acetaldehyde
Acetone
Acetylene
Ammonia
Benzene
Butadiene
Butane
Butanol
Butyl Acetate
Chlorobenzene
Cyclohexane
Chapter 10 Page 4
Decane
Diethyl
Ethane
Ethanol
Ethyl Acetate
Ethylbenzene
Ethylene
Ethylene Oxide
Heptane
Hexane
Hydrogen
Isobutane
Ether Isobutylene
Isopentane
Isopropanol
Methane
Methanol
Methyl Chloride
Methylene Chloride
Methy Ethyl Ketone (MEK)
Pentane
Propane
Propylene
Propylene Oxide
Styrene
Tetrahydrofuran
Toluene
Vinyl Chloride
Xylene
Octane
Fire Catalogue
12/16
FIRE_Ch11_Gas Detection:Layout 1 16/12/2016 13:25 Page 5
Chapter 10 - Gas Detection
Meridian Gas Detector - 2 Wire Configurations
The following Single Head configurations offer wired
HART communications:
Product Codes
Product Codes
Aluminum Enclosure, 4-20 mA, Modbus,
HART Communications, Standard
Display, Plastic End Cap, CSA, ATEX,
IECEX, CE, SIL2
096-3534-02
Aluminum Enclosure, 4-20 mA, Modbus,
096-3533-02
HART Communications, Standard
Display, Stainless Steel End Cap, CSA,
ATEX, IECEX, CE, SIL2
096-3533-03
096-3534-03
Stainless Steel Enclosure, 4-20 mA,
Modbus, HART Communications, Standard
Display, Plastic End Cap, CSA, ATEX,
IECEX, CE, SIL2
096-3533-04
096-3534-04
Stainless Steel Enclosure, 4-20 mA,
Modbus, HART Communications, Standard
Display, Stainless Steel End Cap, CSA,
ATEX, IECEX, CE, SIL2
096-3533-05
096-3534-05
Aluminum Enclosure, 4-20 mA, Modbus,
HART Communications, Blind Display,
Plastic End Cap, CSA, ATEX, IECEX, CE,
096-3533-06
SIL2
096-3534-06
Aluminum Enclosure, 4-20 mA, Modbus,
HART Communications, Blind Display,
096-3533-07
Stainless Steel End Cap, CSA, ATEX,
IECEX, CE, SIL2
096-3534-07
Stainless Steel Enclosure, 4-20 mA,
Modbus, HART Communications, Blind
096-3533-08
Display, Plastic End Cap, CSA, ATEX,
IECEX, CE, SIL2
096-3534-08
Stainless Steel Enclosure, 4-20 mA,
Modbus, HART Communications, Blind
Single Head Configurations offer one detector head with
Display, Stainless Steel End Cap, CSA,
the transmitter for use with one Meridian sensor
ATEX, IECEX, CE, SIL2
096-3480-01
Aluminum Enclosure, 4-20 mA, Modbus
Single Head Configurations offer one detector head with
Communications, Standard Display, Plastic the transmitter for use with one Meridian sensor
End Cap, CSA, ATEX, IECEX, CE, SIL2
096-3534-09
Aluminum Enclosure, 4-20 mA, Modbus,
096-3480-02
Stainless Steel Enclosure, 4-20 mA,
HART Communications, Heated Display,
Modbus Communications, Standard
Plastic End Cap, CSA, ATEX, IECEX, CE,
Display, Plastic End Cap, CSA, ATEX,
SIL2
IECEX, CE, SIL2
096-3534-10
Aluminum Enclosure, 4-20 mA, Modbus,
096-3480-03
Aluminum Enclosure, 4-20 mA, Modbus
HART Communications, Heated Display,
Communications, Heated Display, Plastic
Stainless Steel End Cap, CSA, ATEX,
End Cap, CSA, ATEX, IECEX, CE, SIL2
IECEX, CE, SIL2
096-3480-04
Stainless Steel Enclosure, 4-20 mA,
096-3534-011
Stainless Steel Enclosure, 4-20 mA,
Modbus Communications, Heated
Modbus, HART Communications, Heated
Display, Plastic End Cap, CSA, ATEX,
Display, Plastic End Cap, CSA, ATEX,
IECEX, CE, SIL2 Aluminum Enclosure
IECEX, CE, SIL2
096-3480-05
4-20 mA, Modbus Communications,
096-3534-012
Stainless Steel Enclosure, 4-20 mA,
Standard Display, Stainless Steel End
Modbus, HART Communications, Heated
Cap, CSA, ATEX, IECEX, CE, SIL2
Display, Stainless Steel End Cap, CSA,
096-3480-06
Stainless Steel Enclosure, 4-20 mA,
ATEX, IECEX, CE, SIL2
Modbus Communications, Standard
096-3534-013
Aluminum Enclosure, 4-20 mA, Modbus,
Display, Stainless Steel End
HART Communications, Blind Display,
Cap, CSA, ATEX, IECEX, CE, SIL2
Plastic End Cap, CSA, ATEX, IECEX, CE,
096-3480-07
Aluminum Enclosure, 4-20 mA, Modbus
SIL2
Communications, Heated Display,
096-3534-014
Aluminum Enclosure, 4-20 mA, Modbus,
Stainless Steel End Cap, CSA, ATEX,
HART Communications, Blind Display,
IECEX, CE, SIL2
Stainless Steel End Cap, CSA, ATEX,
096-3480-08
Stainless Steel Enclosure, 4-20 mA,
IECEX, CE, SIL2
Modbus Communications, Heated
096-3534-015
Stainless Steel Enclosure, 4-20 mA,
Display, Stainless Steel End Cap, CSA,
Modbus, HART Communications, Blind
ATEX, IECEX, CE, SIL2
Display, Plastic End Cap, CSA, ATEX,
IECEX, CE, SIL2
096-3534-016
Stainless Steel Enclosure, 4-20 mA,
Modbus, HART Communications, Blind
Display, Stainless Steel End Cap, CSA,
ATEX, IECEX, CE, SIL2
096-3533-01
12/16
Aluminum Enclosure, 4-20 mA
Communications, Standard Display,
Plastic End Cap, CSA, ATEX,
IECEX, CE, SIL2
Stainless Steel Enclosure, 4-20 mA
Communications, Standard Display, Plastic
End Cap, CSA, ATEX, IECEX, CE, SIL2
Aluminum Enclosure, 4-20 mA
Communications, Standard Display,
Stainless Steel End Cap, CSA, ATEX,
IECEX, CE, SIL2
Stainless Steel Enclosure, 4-20 mA
Communications, Standard Display,
Stainless Steel End Cap, CSA, ATEX,
IECEX, CE, SIL2
Aluminum Enclosure,4-20 mA
Communications, Standard Display, Plastic
End Cap, CSA, ATEX, IECEX, CE, SIL2
Stainless Steel Enclosure, 4-20 mA
Communications, Standard Display, Plastic
End Cap, CSA, ATEX, IECEX, CE, SIL2
Aluminum Enclosure, 4-20 mA
Communications, Standard Display,
Stainless Steel End Cap, CSA, ATEX,
IECEX, CE, SIL2
Stainless Steel Enclosure, 4-20 mA
Communications, Standard Display,
Stainless Steel End Cap, CSA, ATEX,
IECEX, CE, SIL2
096-3534-01
Fire Catalogue
Chapter 10 Page 5
FIRE_Ch11_Gas Detection:Layout 1 16/12/2016 13:25 Page 6
Chapter 10 - Gas Detection
Dual Head Configurations offer two detector heads with
the transmitter for use with two Meridian sensors
Triple Head Configurations offer three detector heads
with the transmitter for use with three Meridian sensors
Product Codes
Product Codes
096-3493-01
096-3493-09
096-3493-02
096-3493-03
096-3493-04
096-3493-05
096-3493-06
096-3493-07
096-3493-08
Aluminum Enclosure, 4-20 mA, Modbus
Communications, Standard Display, Plastic
End Cap, CSA, ATEX, IECEX, CE, SIL2
Stainless Steel Enclosure, 4-20 mA,
Modbus Communications, Standard
Display, Plastic End Cap, CSA, ATEX,
IECEX, CE, SIL2
Aluminum Enclosure, 4-20 mA, Modbus
Communications, Heated Display, Plastic
End Cap, CSA, ATEX, IECEX, CE, SIL2
Stainless Steel Enclosure, 4-20 mA,
Modbus Communications, Heated Display,
Plastic End Cap, CSA, ATEX, IECEX, CE,
SIL2
Aluminum Enclosure, 4-20 mA, Modbus
Communications, Standard Display,
Stainless Steel End Cap, CSA, ATEX,
IECEX, CE, SIL2
Stainless Steel Enclosure, 4-20 mA,
Modbus Communications, Standard
Display, Stainless Steel End Cap, CSA,
ATEX, IECEX, CE, SIL2
Aluminum Enclosure, 4-20 mA, Modbus
Communications, Heated Display,
Stainless Steel End Cap, CSA, ATEX,
IECEX, CE, SIL2
Stainless Steel Enclosure, 4-20 mA,
Modbus Communications, Heated
Display, Stainless Steel End Cap, CSA,
ATEX, IECEX, CE, SIL2
096-3493-10
096-3493-11
096-3493-12
096-3493-13
096-3493-14
096-3493-15
096-3493-16
Aluminum Enclosure, 4-20 mA, Modbus
Communications, Standard Display, Plastic
End Cap, CSA, ATEX, IECEX, CE, SIL2
Stainless Steel Enclosure, 4-20 mA,
Modbus Communications, Standard
Display, Plastic End Cap, CSA, ATEX,
IECEX, CE, SIL2
Aluminum Enclosure, 4-20 mA, Modbus
Communications, Heated Display, Plastic
End Cap, CSA, ATEX, IECEX, CE, SIL2
Stainless Steel Enclosure, 4-20 mA,
Modbus Communications, Heated
Display, Plastic End Cap, CSA, ATEX,
IECEX, CE, SIL2
Aluminum Enclosure, 4-20 mA, Modbus
Communications, Standard Display,
Stainless Steel End Cap, CSA, ATEX,
IECEX, CE, SIL2
Stainless Steel Enclosure, 4-20 mA,
Modbus Communications, Standard
Display, Stainless Steel End Cap, CSA,
ATEX, IECEX, CE, SIL2
Aluminum Enclosure, 4-20 mA, Modbus
Communications, Heated Display,
Stainless Steel End Cap, CSA, ATEX,
IECEX, CE, SIL2
Stainless Steel Enclosure, 4-20 mA,
Modbus Communications, Heated Display,
Stainless Steel End Cap, CSA, ATEX,
IECEX, CE, SIL2
The following Dual Head configurations offer wired
HART communications:
The following Triple Head configurations offer wired
HART communications:
096-3535-01
096-3535-09
096-3535-02
096-3535-03
096-3535-04
096-3535-05
096-3535-06
096-3535-07
096-3535-08
Aluminum Enclosure, 4-20 mA, Modbus,
HART Communications, Standard Display,
Plastic End Cap, CSA, ATEX, IECEX, CE,
SIL2
Stainless Steel Enclosure, 4-20 mA,
Modbus, HART Communications, Standard
Display, Plastic End Cap, CSA, ATEX,
IECEX, CE, SIL2
Aluminum Enclosure, 4-20 mA, Modbus,
HART Communications, Heated Display,
Plastic End Cap, CSA, ATEX, IECEX, CE,
SIL2
Stainless Steel Enclosure, 4-20 mA,
Modbus, HART Communications, Heated
Display, Plastic End Cap, CSA, ATEX,
IECEX, CE, SIL2
Aluminum Enclosure, 4-20 mA, Modbus,
HART Communications, Standard
Display, Stainless Steel End Cap, CSA,
ATEX, IECEX, CE, SIL2
Stainless Steel Enclosure, 4-20 mA,
Modbus, HART Communications, Standard
Display, Stainless Steel End Cap, CSA,
ATEX, IECEX, CE, SIL2
Aluminum Enclosure, 4-20 mA, Modbus,
HART Communications, Heated Display,
Stainless Steel End Cap, CSA, ATEX,
IECEX, CE, SIL2
Stainless Steel Enclosure, 4-20 mA,
Modbus, HART Communications, Heated
Display, Stainless Steel End Cap, CSA,
ATEX, IECEX, CE, SIL2
Chapter 10 Page 6
096-3535-10
096-3535-11
096-3535-12
096-3535-13
096-3535-14
096-3535-15
096-3535-16
Fire Catalogue
Aluminum Enclosure, 4-20 mA, Modbus,
HART Communications, Standard Display,
Plastic End Cap, CSA, ATEX, IECEX, CE,
SIL2
Stainless Steel Enclosure, 4-20 mA,
Modbus, HART Communications, Standard
Display, Plastic End Cap, CSA, ATEX,
IECEX, CE, SIL2
Aluminum Enclosure, 4-20 mA, Modbus,
HART Communications, Heated Display,
Plastic End Cap, CSA, ATEX, IECEX, CE,
SIL2
Stainless Steel Enclosure, 4-20 mA,
Modbus, HART Communications, Heated
Display, Plastic End Cap, CSA, ATEX,
IECEX, CE, SIL2
Aluminum Enclosure, 4-20 mA, Modbus,
HART Communications, Standard Display,
Stainless Steel End Cap, CSA, ATEX,
IECEX, CE, SIL2
Stainless Steel Enclosure, 4-20 mA,
Modbus, HART Communications, Standard
Display, Stainless Steel End Cap, CSA,
ATEX, IECEX, CE, SIL2
Aluminum Enclosure, 4-20 mA, Modbus,
HART Communications, Heated Display,
Stainless Steel End Cap, CSA, ATEX,
IECEX, CE, SIL2
Stainless Steel Enclosure, 4-20 mA,
Modbus, HART Communications, Heated
Display, Stainless Steel End Cap, CSA,
ATEX, IECEX, CE, SIL2
12/16
FIRE_Ch11_Gas Detection:Layout 1 16/12/2016 13:25 Page 7
Chapter 10 - Gas Detection
Meridian Gas Detector Sensors
Meridian Spares and Accessories
Product Codes
Product Codes
096-3473-01
096-3473-02
096-3473-03
096-3473-05
048-0089
048-0091
069-0097-10
069-0097-100
069-0097-25
069-0097-50
069-0097-75
073-0367
073-0373
073-0374
074-0528-01
076-0376
076-0377
077-1385
077-1386
087-0049
093-0572-1
093-0572-2
093-0603
093-0604
093-0609
096-3395
096-3401
096-3404
096-3407
096-3408
096-3434
096-3436-1
096-3436-2
096-3437-1
096-3437-2
096-3438
096-3439
096-3440
096-3441
096-3447-01
096-3447-02
096-3447-03
096-3448
096-3449
096-3456
096-3475
096-3475-01
096-3482
096-3483
096-3484-01
096-3484-02
096-3484-03
096-3484-04
096-3484-05
096-3484-06
096-3488
096-3495
096-3496
096-3497
096-3498
096-3520
096-3520-01
096-3523-01
096-3523-02
096-3537
096-3541-00
096-3473-09
096-3473-11
096-3473-19
096-3473-20
096-3473-21
096-3473-22
096-3473-23
096-3473-24
096-3473-25
096-3473-26
096-3473-27
096-3473-28
096-3473-31
096-3473-32
096-3473-37
096-3473-38
096-3473-39
096-3473-54
096-3473-55
096-3473-56
096-3473-58
Meridian Sensor- CO
Meridian Sensor- H2S (Low Methanol)
Meridian Sensor- NH3
Meridian Sensor- SO2 High Relative
Humidity *
Meridian Sensor- SiH4
Meridian Sensor- HCN *
Meridian Sensor- O2
Meridian Sensor- Cl2 Rock Solid, High
Relative Humidity
Meridian Sensor- Cl2 Rock Solid, Low
Relative Humidity
Meridian Sensor- F2 Rock Solid, High
Relative Humidity
Meridian Sensor- F2 Rock Solid, Low
Relative Humidity
Meridian Sensor- Br2 Rock Solid, High
Relative Humidity
Meridian Sensor- HCl Rock Solid, High
Relative Humidity *
Meridian Sensor- HCl Rock Solid, Low
Relative Humidity *
Meridian Sensor- HF Rock Solid, High
Relative Humidity *
Meridian Sensor- HF Rock Solid, Low
Relative Humidity *
Meridian Sensor- SO2 Rock Solid, High
Relative Humidity *
Meridian Sensor- SO2 Rock Solid, Low
Relative Humidity *
Meridian Sensor- ClO2 Rock Solid, High
Relative Humidity
Meridian Sensor- ClO2 Rock Solid, Low
Relative Humidity
Meridian Sensor- O3 Rock Solid, High
Relative Humidity
Meridian Sensor- NO2
Meridian Sensor-Combustible Catalytic
Bead
Meridian Sensor-Combustible IR
Meridian Sensor- CO2 IR
* Require an export licence
12/16
Fire Catalogue
096-390 DEG. M-F ELBOW 3/4 NPT
3/4 NPT Cable Gland Fitting
Cable, HAZLOC, 7 Conductor
Cable, HAZLOC, 7 Conductor
Cable, HAZLOC, 7 Conductor
Cable, HAZLOC, 7 Conductor
Cable, HAZLOC, 7 Conductor
Junction Box Next GEN
Sun Shield, Transmitter
Adapter Mounting Plate
IS Terminal Cover
Pipe MTG.BKT.JBOX Meridian
Pipe MTG.BKT.ENCL. Meridian
Fitting,10-32QD,RT ANG,1/8 Tube
Fitting,10-32QD,RT ANG,1/4 Tube
Meridian User Guide
Enclosure, Next GEN, Aluminum
Enclosure, Next-GEN, Stainless
Cover, Alum Encl, Meridian
Cover, Stainless Encl, Meridia
A Frame Extension
Sensor Simulator
NEXT GEN Power Supply PCBA
Terminal / Relay PCBA
2 Wire Power Supply BoardAssy
HART Expansion Board Assembly
Transmitter Junction Box PCBA
Assembly,Detector Body, NEX-GEN
Assembly,Detector Body, NEX-GEN
Assembly, Cap, Detector Head
Assembly, Cap, Detector Head
Assembly, Adapter, Calibration, NEX-G
Assembly, Adapter, Flow Cell, NEX-GEN
Assembly, Kit, Duct Mount Adapter
Assembly, Deluge Guard
Display Assembly NEXT GEN
Display Assembly NEXT GEN
Blind Display Assy Meridian
IS Barrier Puck
2 Wire Is Barrier Assembly
Display Cable Assembly
Junction Box Assembly NEXT GEN
JCT Box Assy Meridian Inmetro
Assembly, Chain
NPT To NPT Wire Gland Assembly
DET Head End Cap Assy 3/4 Wire
DET Head End Cap Assy 2 Wire
DET Head Plas End Cap 2 Wire
DET Head SS End Cap 2 Wire
DET Head Plas End Cap 3/4 Wire
DET Head SS End Cap 3/4 Wire
Meridian E-CHEM Sensor BIAS AS
Meridian Connector/Jumper Kit
Meridian Screw Replacement Kit
Meridian Standoff Replace Kit
Meridian O-Ring Replace Kit
SS Junction Box Assembly
SS Junction Box Assembly INM
Sales Display Kit (ATEX)
Sales Display Kit (CSA)
ASSY, Dust FLTR, MER Detector
A-Frame Sales Display Only
Chapter 10 Page 7
FIRE_Ch11_Gas Detection:Layout 1 16/12/2016 13:25 Page 8
Chapter 10 - Gas Detection
Meridian Spares and Accessories
Product Codes
Product Codes
096-3541-01
096-3541-02
096-3550
096-3553-02
096-3554-01
096-3554-02
096-3566-04
096-3568-01
096-3568-02
096-3569-01
096-3569-02
096-3579-01
096-3554-03
096-3554-04
096-3554-05
096-3554-06
096-3554-07
096-3554-08
096-3557-01
096-3557-02
096-3557-03
096-3557-04
096-3557-05
096-3557-06
096-3557-07
096-3557-08
096-3558-01
096-3558-02
096-3558-03
096-3558-04
096-3558-05
096-3558-06
096-3558-07
096-3558-08
096-3558-09
096-3558-10
096-3558-11
096-3558-12
096-3558-13
096-3558-14
096-3558-15
096-3558-16
096-3559-01
096-3559-02
096-3563-01
096-3563-02
096-3564-01
096-3564-02
096-3564-03
096-3564-04
096-3565-01
096-3565-02
096-3566-01
096-3566-02
096-3566-03
A-Frame Sales Display Assy USA
A-Frame Sales Display Assy CAN
IS Terminal Block Kit
Factory Kit, Flat Duct, ATEX
Sensor Propane Infrared - C3H8
Sensor Octamethyl Trisiloxane
C8H24O2Si3
Sensor Methanol Infrared - CH3OH
Sensor Butane Infrared - C4H10
Sensor Isopropanol Infrared - C3H7OH
Sensor Toluene Infrared - C7H8
Sensor Pentane Infrared - C5H12
Sensor Hexane Infrared - C6H14
2W AL, Std Dsp, Pl Cap, Remote
2W SS, Std Dsp, Pl Cap, Remote
2W AL, Std Dsp, SS Cap, Remote
2W SS, Std Dsp, SS Cap, Remote
2W AL, Std Dsp, Pl Cap, Remote, CSA
2W SS, Std Dsp, Pl Cap, Remote, CSA
2W AL, Std Dsp, SS Cap, Remote, CSA
2W SS, Std Dsp, SS Cap, Remote, CSA
3W AL, Std Dsp, Pl Cap, Remote
3W SS, Std Dsp, Pl Cap, Remote
3W AL, Heat Dsp, Pl Cap, Remote, CSA
3W SS, Heat Dsp, Pl Cap, Remote, CSA
3W AL, Std Dsp, SS Cap, Remote
3W SS, Std Dsp, SS Cap, Remote
3W AL, Heat Dsp, SS Cap, Remote, CSA
3W SS, Heat Dsp, SS Cap, Remote, CSA
3W AL, Std Dsp, HART, Pl Cap, Remote
3W SS, Std Dsp, HART, Pl Cap, Remote
3W AL, Heat Dsp, HART, Pl Cap, Rmt, CSA
3W SS, Heat Dsp, HART, Pl Cap, Rmt, CSA
3W AL, Std Dsp, HART, SS Cap, Remote
3W SS, Std Dsp, HART, SS Cap, Remote
3W AL, Heat Dsp, HART, SS Cap, Remote
3W SS, Heat Dsp, HART, SS Cap, Remote
Remote Junction Box Assy AL
Remote Junction Box Assy SS
2W AL, Std Dsp, Pl Cap, INMETRO
2W SS, Std Dsp, Pl Cap, INMETRO
3W AL, Std Dsp, Pl Cap, INMETRO
3W SS, Std Dsp, Pl Cap, INMETRO
3W AL, Blind Dsp, Pl Cap, INMETRO
3W SS, Blind Dsp, Pl Cap, INMETRO
2W AL, Std Dsp, Pl Cap, Remote,
INMETRO
2W SS, Std Dsp, Pl Cap, Remote,
INMETRO
3W AL, Std Dsp, Pl Cap, Remote,
INMETRO
3W SS, Std Dsp, Pl Cap, Remote,
INMETRO
3W AL, Blind Dsp, Pl Cap, Rmt, INMETRO
Chapter 10 Page 8
Fire Catalogue
3W SS, Blind Dsp, Pl Cap, Rmt, INMETRO
3W AL, Std Dsp, Pl Cap, INMETRO
3W SS, Std Dsp, Pl Cap, INMETRO
3W AL, Std Dsp, Pl Cap, INMETRO
3W SS, Std Dsp, Pl Cap, INMETRO
Meridian Hart CEC KIT
12/16
12/16
602SB 2 WIRE LINE POWERED SOUNDER BASE
602SBD 2 WIRE LINE POWERED DIODE SOUNDER BASE
802SB MX LOW POWERED SOUNDER BASE
812SB LOOP POWERED UL SOUNDER BASE
516.800.911
577.001.036
577.001.038
516.800.910
516.800.913
601SB CONVENTIONAL SOUNDER BASE
601SBD CONVENTIONAL DIODE SOUNDER BASE
901SB UNIVERSAL SOUNDER BASE
602SB 2 WIRE LINE POWERED SOUNDER BASE
602SBD 2 WIRE LINE POWERED DIODE SOUNDER BASE
802SB MX LOW POWERED SOUNDER BASE
812SB LOOP POWERED UL SOUNDER BASE
577.001.035
577.001.037
516.800.911
577.001.036
577.001.038
516.800.910
516.800.913
PART NO. DESCRIPTION
901SB UNIVERSAL SOUNDER BASE
577.001.037
Fire Catalogue
21mA
1.2mA
1.2mA
1.2mA
1.2mA
1.2mA
1.2mA
CURRENT CONSUMPTION AT
68 dBA (MINIMUM VOLUME)
MX ONLY
MX ONLY
MZX-c ONLY
MZX-c ONLY
MINERVA ADDRESSABLE/MX
CONVENTIONAL ONLY
CONVENTIONAL ONLY
601SB CONVENTIONAL SOUNDER BASE
601SBD CONVENTIONAL DIODE SOUNDER BASE
577.001.035
CONTROL PANEL COMPATIBILITY
PART NO. DESCRIPTION
YES
YES
NO
NO
YES
NO
NO
6.8mA
6.8mA
6.8mA
6.8mA
6.8mA
6.8mA
WHITE
WHITE
YELLOW
YELLOW
BLUE
GREEN
GREEN
PARK CLIP
COLOUR
CURRENT CONSUMPTION AT
100dBA (FIXED VOLUME)
DETECTOR REQUIRED
TO OPERATE
CURRENT CONSUMPTION AT
90 dBA (MAXIMUM VOLUME)
LOOP
LOOP
DETECTION CIRCUIT
DETECTION CIRCUIT
24Vdc
24Vdc
24Vdc
POWERED FROM
.
FIRE_Ch11_Useful_Information:Layout 1 16/12/2016 13:49 Page 1
Chapter 11 - Useful Information
MKII Sounder Base Application Table
Chapter 11 Page 1
YES
601SB CONVENTIONAL SOUNDER BASE
601SBD CONVENTIONAL DIODE SOUNDER BASE
901SB UNIVERSAL SOUNDER BASE
602SB 2 WIRE LINE POWERED SOUNDER BASE
602SBD 2 WIRE LINE POWERED DIODE SOUNDER BASE
802SB MX LOW POWERED SOUNDER BASE
812SB LOOP POWERED UL SOUNDER BASE
577.001.035
577.001.037
516.800.911
577.001.036
Chapter 11 Page 2
577.001.038
516.800.910
516.800.913
YES
Fire Catalogue
901SB UNIVERSAL SOUNDER BASE
602SB 2 WIRE LINE POWERED SOUNDER BASE
602SBD 2 WIRE LINE POWERED DIODE SOUNDER BASE
802SB MX LOW POWERED SOUNDER BASE
812SB LOOP POWERED UL SOUNDER BASE
577.001.037
516.800.911
577.001.036
577.001.038
516.800.910
516.800.913
(2) (3) (7) (9) (11) (14) (25) (26) = ROSHNI TONE NUMBER
601SB CONVENTIONAL SOUNDER BASE
601SBD CONVENTIONAL DIODE SOUNDER BASE
577.001.035
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
DUTCH SLOW TEMPORAL 4 SLOW SWEEP (3) MARCH TIME BEEP(25)
SWEEP (7)
YES
YES
YES
YES
YES
YES
YES
YES
YES
CONTINUOUS
MARCH TIME BEEP(26)
YES
YES
YES
YES
YES
YES
TEMPORAL 3 ALTERNATING 2(11) ALTERNATING 2 (9) CONTINUOUS(14)
PART NO. DESCRIPTION
YES
YES
YES
YES
YES
YES
FAST
SWEEP (2)
PART NO. DESCRIPTION
FIRE_Ch11_Useful_Information:Layout 1 16/12/2016 13:49 Page 2
Chapter 11 - Useful Information
MKII Sounder Base Application Table
12/16
12/16
Fire Catalogue
DIL SW
12345
00000
10000
01000
11000
00100
10100
01100
11100
00010
10010
01010
11010
00110
10110
01110
11110
00001
10001
01001
11001
00101
10101
01101
11101
00011
10011
01011
11011
00111
10111
01111
11111
Banshee Buzz LF
Banshee Fast Sweep LF*
Banshee Slow Sweep LF
Banshee Continious LF
Banshee Fast Sweep LF (New)
Medium Sweep LF*
Continious LF
Back up Alarm LF
Alternate LF
Medium Sweep LF
Alternate LF
Banshee Buzz HF
Banshee Fast Sweep HF
Banshee Slow Sweep HF
Banshee Continious HF
Banshee Fast Sweep HF (New)
Back up Alarm HF
Alternate HF
Slow Whoop*
Din Tone (DK)*
French Fire Sound*
Austrailian Alert Signal
Austrialian Evacuation Signal
US Temporal Tone LF
US Temporal Tone HF
Swedish Tone (Fire)
Swedish Tone (All Clear)
ISO8201 LF
ISO8201 HF
BT Banshee (FP1063.1)
BT Banshee (FP1063.1)
Bell Tone
Description
800Hz to 950Hz swept at 120Hz
800Hz to 950Hz swept at 9Hz
800Hz to 950Hz swept at 3Hz
Continious at 900Hz
830Hz to 970Hz swept at 9Hz
800Hz to 950Hz swept at 1Hz
Continious at 950Hz
Intermittent at 950Hz 1 sec on, 1 sec off
Alternating 800Hz/1000Hz at 1Hz
800Hz to 1000Hz swept at 0.5 secs
Alternating Tones 800/950 at 3Hz
2400Hz to 2900Hz at 120Hz
2400Hz to 2900Hz at 9Hz
2400Hz to 2900Hz at 3Hz
Continious 2900Hz*
2450Hz to 3100Hz swept at 9Hz
Intermittent at 2900Hz 1 sec on, 1 sec off
Alternating Tones 2400/2900 at 3Hz
500Hz rising to 1200Hz over 3.5 sec, silence 0.5 sec
1200Hz falling to 500Hz over 1 sec, silence 10mS, repeat
554Hz for 100mS and 440Hz for 400mS
420Hz repeating 0.625 sec on, 0.625 sec off
500Hz to 1200Hz sweeping, 3.75 secs on, 0.25 secs off
950Hz for 0.5 sec on. 0.5 sec off for 3 phases, silence for 1.5secs and repeat
2900Hz for 0.5 sec on. 0.5 sec off for 3 phases, silence for 1.5secs and repeat
Intermittent 660Hz 150mS on, 150mS off
Continuous 660Hz
Intermittent 970Hz 500mS on, 500mS off
Intermittent 2900Hz 500mS on, 500mS off*
Yodel 800Hz/1000Hz, 0.25sec each frequency
Continuous 1000Hz
Bell Tone
Frequency and Timing
2nd
Tone
4
4
4
4
4
7
7
4
4
4
4
15
15
15
15
15
15
15
4
4
4
4
4
4
15
26
27
28
29
31
31
32
94
94
94
94
95
96
96
96
94
95
96
102
103
103
103
103
104
104
95
93
90
89
95
95
104
90
91
93
103
93
90
96
6
6
6
6
6
6
6
8
6
6
6
16
17
17
19
18
18
16
6
5
4
3
6
5
13
3
5
5
13
6
6
12
101
101
101
101
101
101
102
102
100
101
101
110
110
110
110
110
110
110
101
100
96
95
103
101
110
96
97
99
110
100
96
101
12
12
12
12
12
12
13
14
13
12
12
35
35
35
39
36
36
36
12
10
7
6
12
10
26
6
9
10
27
12
14
25
Banshee Excel TM
(12V)
(24V)
dBA mA dBA mA
Notes:*Tones highlighted in bold are approved under the Construction Product Directive. Sound output (dBA) and current (mA) values are typical.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
No
Tone Information
Banshee Excel Tone Table
94
94
94
94
93
94
94
93
94
94
94
102
103
103
103
103
103
104
95
93
90
89
95
93
103
90
91
90
103
94
88
94
6
6
6
6
6
6
6
6
6
6
6
16
17
17
19
18
18
17
6
5
4
3
6
5
13
3
5
5
13
6
6
12
100
100
100
100
100
100
100
99
100
100
101
109
110
110
109
109
109
110
101
100
96
94
101
99
109
96
97
96
109
100
94
99
12
12
12
12
12
12
12
14
13
12
12
35
35
35
39
36
37
36
12
12
7
6
12
10
27
6
9
10
27
12
14
25
Banshee Excel Lite TM
(12V)
(24V)
dBA mA dBA mA
FIRE_Ch11_Useful_Information:Layout 1 16/12/2016 13:49 Page 3
Chapter 11 - Useful Information
Chapter 11 Page 3
FIRE_Ch11_Useful_Information:Layout 1 16/12/2016 13:49 Page 4
Chapter 11 - Useful Information
Fulleon Sounder Tone Compatibility Table
Fulleon Tone
Tone Number
CONTINUOUS TONE (970HZ)
14
2 Wire Symphoni
24V Symphoni
Sounder Base
601SB/601SBD
602SB/602SBD
SWITCH A B
SWITCH 1 2 3 4 5
SWITCH 1 2 3 4
10
10010
111X
(880Hz)
PULSED/INTERMITTENT TONE ([email protected] 1HZ)
25
11
00111
011X
([email protected])EURO ONLY
ALTERNATING TONE (970HZ/[email protected])
1
01
11111
N/A
(CLOSEST MATCH)
(990HZ/[email protected])
(500Hz-1200Hz-3s on/0.5s off)
7
N/A
11001
000X
SLOW SWEEP (800Hz/[email protected])
3
N/A
11101
010X
FAST SWEEP (800Hz/[email protected])
2
N/A
11110
100X
TWO TONE/ALTERNATING (800HZ/[email protected])
11
N/A
10101
110X
DUTCH SLOW WHOOP
(660Hz/[email protected])EURO ONLY
Fulleon Sounder Tone Table
No.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
TONE
ALT TONES 800/970 at 1/4 Hz
SWEEPING 800/970Hz at 7Hz
SWEEPING 800/970Hz at 1Hz
CONTINUOUS at 2850Hz
SWEEPING 2400-2850Hz at 7Hz
SWEEPING 2400-2850Hz at 1Hz
SLOW WHOOP
SWEEP 1200-500 at 1Hz
ALT TONES 2400/2850 2Hz
INT TONE OF 970Hz at 1Hz
ALT TONES 800/970 Hz at 1Hz
INT TONE at 2850 Hz at 1Hz
970Hz at 1/4 SEC. ON 1 SEC. OFF
CONTINUOUS AT 970Hz
554 FOR 100ms and 440Hz FOR 400ms
INT 660Hz 150ms ON/150ms OFF
INT 660Hz 1.8s ON/1.8s OFF
INT 660Hz 6.5s ON/13s OFF
CONTINUOUS 660Hz
ALT 554/440Hz at 1Hz
INT 660Hz 1Hz
INT 2850Hz 150ms ON 100ms OFF
SWEEP 800-970Hz at 50Hz
SWEEP 2400-2850Z at 50 Hz
INTERMITTENT 970Hz 500ms ON 500ms OFF
INTERMITTENT 2850HZ 500ms ON 500ms OFF
CONTINUOUS AT 4kHz
ALTERNATING TONES 800/970 AT 2Hz
ALTERNATING TONES 988/645 AT 2Hz
ALTERNATING 510/610 at 1Hz
SWEEPING 300-1200 at 1Hz
CONTINUOUS AT 4kHz
Chapter 11 Page 4
Fire Catalogue
12/16
FIRE_Ch11_Useful_Information:Layout 1 16/12/2016 13:49 Page 5
Chapter 11 - Useful Information
Features
• Selecting the category of protection and coverage.
• How to configure detector zones and alarm zones within
premises.
• Which type of fire detection system?
• Detector suitability.
• Detector coverage.
• Manual break glass call points.
• Limitation of false alarms.
• Means of giving warning to occupants.
• Control and indicating equipment.
• Power supplies.
• Cabling considerations.
• Communication with the fire service.
• System installation.
• Documentation.
• Standards and Specifications.
• Associated Ancillary Equipment.
• Networking and Graphics.
• Installation.
• Commissioning.
• Training.
• Maintenance.
Consultants Guide
A Fire Detection System Consultants Guide for consultants
designing systems to BS5839-1:2002.
Product Code
CGUK-01
12/16
Fire Catalogue
Consultants Guide
Chapter 11 Page 5
FIRE_Ch11_Useful_Information:Layout 1 16/12/2016 13:49 Page 6
Chapter 11 - Useful Information
This page is left intentionally blank.
Chapter 11 Page 6
Fire Catalogue
12/16
Chapter 12 - Index
Index
Product Code Description Chapter Page
096-3533-01
Aluminium Enclosure, 4-20 mA105
096-3480-02
Stainless Steel Enclosure, 4-20 mA105
096-3533-03
Stainless Steel Enclosure, 4-20 mA105
096-3533-04
Stainless Steel Enclosure, 4-20 mA105
096-3533-05
Aluminium Enclosure, 4-20 mA105
096-3533-06
Stainless Steel Enclosure, 4-20 mA105
096-3533-07
4-20 mA, Modbus Communications105
096-3533-08
Stainless Steel Enclosure105
096-3480-07
Aluminium Enclosure, 4-20 mA105
096-3480-08
Stainless Steel Enclosure105
096-3480-01
Aluminium Enclosure 105
096-3480-02
Stainless Steel Enclosure105
096-3480-03
Aluminium Enclosure105
096-3480-04
Stainless Steel Enclosure105
096-3480-05
4-20 mA, Modbus Communications105
096-3480-06
Stainless Steel Enclosure105
096-3480-07
Aluminium Enclosure105
096-3480-08
Stainless Steel Enclosure105
096-3534-01
Aluminium Enclosure105
096-3534-02
Aluminium Enclosure105
096-3534-03
Stainless Steel Enclosure105
096-3534-04
Stainless Steel Enclosure105
096-3534-05
Aluminium Enclosure105
096-3534-06
Aluminium Enclosure105
096-3534-07
Stainless Steel Enclosure105
096-3534-08
Stainless Steel Enclosure105
096-3534-09
Aluminium Enclosure105
096-3534-10
Aluminium Enclosure105
096-3534-011
Stainless Steel Enclosure105
096-3534-012
Stainless Steel Enclosure105
096-3534-013
Aluminium Enclosure105
096-3534-014 Aluminium Enclosure105
096-3534-015
Stainless Steel Enclosure105
096-3534-016
Stainless Steel Enclosure105
096-3493-01
Aluminium Enclosure10 6
096-3493-02
Stainless Steel Enclosure106
096-3493-03
Aluminium Enclosure106
096-3493-04
Stainless Steel Enclosure106
096-3493-05
Aluminium Enclosure106
096-3493-06
Stainless Steel Enclosure106
096-3493-07
Aluminium Enclosure106
096-3493-08
Stainless Steel Enclosure106
096-3535-01
Aluminium Enclosure106
096-3535-02
Stainless Steel Enclosure106
096-3535-03
Aluminium Enclosure106
096-3535-04
Stainless Steel Enclosure106
096-3535-05
Aluminium Enclosure106
096-3535-06
Stainless Steel Enclosure106
096-3535-07
Aluminium Enclosure106
096-3535-08
Stainless Steel Enclosure106
096-3493-09
Aluminium Enclosure106
096-3493-10
Stainless Steel Enclosure10 6
096-3493-11
Aluminium Enclosure106
096-3493-12
Stainless Steel Enclosure106
04/17
Fire Catalogue
Chapter 12 Page 1
Chapter 2 - MX Technology
Product Code Description Chapter Page
096-3493-13
Aluminium Enclosure106
096-3493-14
Stainless Steel Enclosure106
096-3493-15
Aluminium Enclosure 10 6
096-3493-16
Stainless Steel Enclosure 106
096-3535-09
Aluminium Enclosure106
096-3535-10
Stainless Steel Enclosure106
096-3535-11
Aluminium Enclosure106
096-3535-12
Stainless Steel Enclosure106
096-3535-13
Aluminium Enclosure106
096-3535-14
Stainless Steel Enclosure106
096-3535-15
Aluminium Enclosure106
096-3535-16
Stainless Steel Enclosure106
096-3473-01
Meridian Sensor- CO107
096-3473-02
Meridian Sensor- H2S (Low Methanol)
10 7
096-3473-03
Meridian Sensor- NH310 7
096-3473-05
Meridian Sensor- SO2 High Relative Humidity *
10 7
096-3473-09
Meridian Sensor- SiH4107
096-3473-11
Meridian Sensor- HCN * 107
096-3473-19
Meridian Sensor- O2107
096-3473-20
Meridian Sensor- Cl2 Rock Solid, High
Relative Humidity107
096-3473-21
Meridian Sensor- Cl2 Rock Solid, Low
Relative Humidity107
096-3473-22
Meridian Sensor- F2 Rock Solid, High
Relative Humidity107
096-3473-23
Meridian Sensor- F2 Rock Solid, Low
Relative Humidity107
096-3473-24
Meridian Sensor- Br2 Rock Solid, High
Relative Humidity107
096-3473-25
Meridian Sensor- HCl Rock Solid, High
Relative Humidity *107
096-3473-26
Meridian Sensor- HCl Rock Solid, Low
Relative Humidity *107
096-3473-27
Meridian Sensor- HF Rock Solid, High
Relative Humidity *107
096-3473-28
Meridian Sensor- HF Rock Solid, Low
Relative Humidity *107
096-3473-31
Meridian Sensor- SO2 Rock Solid, High
Relative Humidity *107
096-3473-32
Meridian Sensor- SO2 Rock Solid, Low
Relative Humidity *107
096-3473-37
Meridian Sensor- ClO2 Rock Solid, High
Relative Humidity107
096-3473-38
Meridian Sensor- ClO2 Rock Solid, Low
Relative Humidity107
096-3473-39
Meridian Sensor- O3 Rock Solid, High
Relative Humidity107
096-3473-54
Meridian Sensor- NO2107
096-3473-55
Meridian Sensor-Combustible Catalytic
Bead107
096-3473-56
Meridian Sensor-Combustible IR107
096-3473-58
Meridian Sensor- CO2 IR107
048-0089
096-390 DEG. M-F ELBOW 3/4 NPT
10
7
048-0091
3/4 NPT Cable Gland Fitting
10 7
069-0097-10
Cable, HAZLOC, 7 Conductor107
69-0097-100
Cable, HAZLOC, 7 Conductor
10 7
069-0097-25 Cable, HAZLOC, 7 Conductor 10 7
* Require an export licence
Chapter 13 Page 2
Fire Catalogue
03/17
Chapter 12 - Index
Product Code Description Chapter Page
069-0097-50
Cable, HAZLOC, 7 Conductor
10 7
069-0097-75
Cable, HAZLOC, 7 Conductor
10 7
073-0367Junction Box Next GEN10 7
073-0373Sun Shield, Transmitter10 7
073-0374Adapter Mounting Plate10 7
074-0528-01
IS Terminal Cover10 7
076-0376Pipe MTG.BKT.JBOX Meridian10 7
076-0377Pipe MTG.BKT.ENCL. Meridian10 7
077-1385Fitting,10-32QD,RT ANG,1/8 Tube10 7
077-1386Fitting,10-32QD,RT ANG,1/4 Tube10 7
087-0049Meridian User Guide10 7
093-0572-1
Enclosure, Next GEN,Aluminium10 7
093-0572-2
Enclosure, Next-GEN, Stainless10 7
093-0603
Cover, Alum Encl, Meridian
10 7
093-0604
Cover, Stainless Encl, Meridia
10 7
093-0609A Frame Extension10 7
096-3395Sensor Simulator10 7
096-3401
NEXT GEN Power Supply PCBA
10 7
096-3404Terminal / Relay PCBA10 7
096-3407
2 Wire Power Supply BoardAssy
10 7
096-3408
HART Expansion Board Assembly
10 7
096-3434
Transmitter Junction Box PCBA
10 7
096-3436-1 Assembly,Detector Body, NEX-GEN
10 7
096-3436-2 Assembly,Detector Body, NEX-GEN
10 7
096-3437-1 Assembly, Cap, Detector Head
10 7
096-3437-2 Assembly, Cap, Detector Head
10 7
096-3438 Assembly, Adapter, Calibration, NEX-G
10 7
096-3439 Assembly, Adapter, Flow Cell, NEX-GEN
10 7
096-3440 Assembly, Kit, Duct Mount Adapter
10 7
096-3441 Assembly, Deluge Guard10 7
096-3447-01 Display Assembly NEXT GEN
10 7
096-3447-02 Display Assembly NEXT GEN
10 7
096-3447-03 Blind Display Assy Meridian
10 7
096-3448 IS Barrier Puck10 7
096-3449 2 Wire Is Barrier Assembly
10 7
096-3456 Display Cable Assembly10 7
096-3475 Junction Box Assembly NEXT GEN
10 7
096-3475-01 JCT Box Assy Meridian Inmetro
10 7
096-3482 Assembly, Chain10 7
096-3483 NPT To NPT Wire Gland Assembly
10 7
096-3484-01 DET Head End Cap Assy 3/4 Wire
10 7
096-3484-02 DET Head End Cap Assy 2 Wire
10 7
096-3484-03 DET Head Plas End Cap 2 Wire
10 7
096-3484-04 DET Head SS End Cap 2 Wire
10 7
096-3484-05 DET Head Plas End Cap 3/4 Wire
10 7
096-3484-06 DET Head SS End Cap 3/4 Wire
10 7
096-3488 Meridian E-CHEM Sensor BIAS AS
10 7
096-3495 Meridian Connector/Jumper Kit
10 7
096-3496 Meridian Screw Replacement Kit
10 7
096-3497 Meridian Standoff Replace Kit
10 7
096-3498 Meridian O-Ring Replace Kit
10 7
096-3520 SS Junction Box Assembly
10 7
096-3520-01 SS Junction Box Assembly INM
10 7
096-3523-01 Sales Display Kit (ATEX)
10 7
096-3523-02 Sales Display Kit (CSA)
10 7
096-3537 ASSY, Dust FLTR, MER Detector
10 7
096-3541-00 A-Frame Sales Display Only
10 7
096-3541-01 A-Frame Sales Display Assy USA
10
8
096-3541-02 A-Frame Sales Display Assy CAN
10
8
096-3550 IS Terminal Block Kit108
04/17
Fire Catalogue
Chapter 12 Page 3
Chapter 2 - MX Technology
Product Code Description Chapter Page
096-3553-02 Factory Kit, Flat Duct, ATEX
10
8
096-3554-01 Sensor Propane Infrared - C3H8
10
8
096-3554-02 Sensor Octamethyl Trisiloxane108
C8H24O2Si3
096-3554-03 Sensor Methanol Infrared - CH3OH
10
8
096-3554-04 Sensor Butane Infrared - C4H10
10
8
096-3554-05 Sensor Isopropanol Infrared - C3H7OH
10
8
096-3554-06 Sensor Toluene Infrared - C7H8
10
8
096-3554-07 Sensor Pentane Infrared - C5H12
10
8
096-3554-08 Sensor Hexane Infrared - C6H14
10
8
096-3557-01 2W AL, Std Dsp, Pl Cap, Remote
10
8
096-3557-02 2W SS, Std Dsp, Pl Cap, Remote
10
8
096-3557-03 2W AL, Std Dsp, SS Cap, Remote
10
8
096-3557-04 2W SS, Std Dsp, SS Cap, Remote
10
8
096-3557-05 2W AL, Std Dsp, Pl Cap, Remote, CSA
10
8
096-3557-06 2W SS, Std Dsp, Pl Cap, Remote, CSA
10
8
096-3557-07 2W AL, Std Dsp, SS Cap, Remote, CSA
10
8
096-3557-08 2W SS, Std Dsp, SS Cap, Remote, CSA
10
8
096-3558-01 3W AL, Std Dsp, Pl Cap, Remote
10
8
096-3558-02
3W SS, Std Dsp, Pl Cap, Remote
10
8
096-3558-03 3W AL, Heat Dsp, Pl Cap, Remote, CSA
10
8
096-3558-04 3W SS, Heat Dsp, Pl Cap, Remote, CSA
10
8
096-3558-05 3W AL, Std Dsp, SS Cap, Remote
10
8
096-3558-06 3W SS, Std Dsp, SS Cap, Remote
10
8
096-3558-07
3W AL, Heat Dsp, SS Cap, Remote, CSA
10
8
096-3558-08 3W SS, Heat Dsp, SS Cap, Remote, CSA
10
8
096-3558-09 3W AL, Std Dsp, HART, Pl Cap, Remote
10
8
096-3558-10 3W SS, Std Dsp, HART, Pl Cap, Remote
10
8
096-3558-11 3W AL, Heat Dsp, HART, Pl Cap, Rmt, CSA
10
8
096-3558-12 3W SS, Heat Dsp, HART, Pl Cap, Rmt, CSA
10
8
096-3558-13 3W AL, Std Dsp, HART, SS Cap, Remote
10
8
096-3558-14 3W SS, Std Dsp, HART, SS Cap, Remote
10
8
096-3558-15 3W AL, Heat Dsp, HART, SS Cap, Remote
10
8
096-3558-16 3W SS, Heat Dsp, HART, SS Cap, Remote
10
8
096-3559-01 Remote Junction Box Assy AL
10
8
096-3559-02 Remote Junction Box Assy SS
10
8
096-3563-01 2W AL, Std Dsp, Pl Cap, INMETRO
10
8
096-3563-02 2W SS, Std Dsp, Pl Cap, INMETRO
10
8
096-3564-01 3W AL, Std Dsp, Pl Cap, INMETRO
10
8
096-3564-02 3W SS, Std Dsp, Pl Cap, INMETRO
10
8
096-3564-03 3W AL, Blind Dsp, Pl Cap, INMETRO
10
8
096-3564-04 3W SS, Blind Dsp, Pl Cap, INMETRO
10
8
096-3565-01 2W AL, Std Dsp, Pl Cap, Remote,
INMETRO108
096-3565-02 2W SS, Std Dsp, Pl Cap, Remote,
INMETRO108
096-3566-01 3W AL, Std Dsp, Pl Cap, Remote,
INMETRO
096-3566-02 3W SS, Std Dsp, Pl Cap, Remote,
INMETRO108
096-3566-03 3W AL, Blind Dsp, Pl Cap, Rmt, INMETRO
10
8
096-3566-04 3W SS, Blind Dsp, Pl Cap, Rmt, INMETRO
10
8
096-3568-01 3W AL, Std Dsp, Pl Cap, INMETRO
10
8
096-3568-02 3W SS, Std Dsp, Pl Cap, INMETRO
10
8
096-3569-01 3W AL, Std Dsp, Pl Cap, INMETRO
10
8
096-3569-02 3W SS, Std Dsp, Pl Cap, INMETRO
10
8
096-3579-01 Meridian Hart CEC KIT108
572.065 MX Rack Mounting Kit for standard 19” racks 2 6
2000636 MZX-c+ CONVENTIONAL PANEL TRANSFORMER 1.5 AMP 3 48
2000637 MZX-c+ CONVENTIONAL PANEL TRANSFORMER 3.0 AMP 3 48
Chapter 13 Page 4
Fire Catalogue
03/17
Chapter 2 - MX Technology
Product Code Description Chapter Page
2000638 MZX-c+ CONVENTIONAL PANEL TRANSFORMER 5.0 AMP 2501061 MZX-c CONVENTIONAL PANEL SPARE ENABLE KEY 2572200 CelTEL 4 Way Master EVC Panel with Handset and Display 2572201 CelTEL 8 Way Master EVC Panel with Handset and Display 2572202 CelTEL Master Controller without Handset 2572203 CelTEL Slave EVC Panel with 8 Additional Lines 2572204 CelTEL EVC Network Communication Card 2572206 Anti Tamper Enclosure for the CelTEL Master EVC Panel 2572210 Type B Stainless Steel Flush Mounting Disabled Refuge Outstation 2572211 Type B Stainless Steel Surface Mnt Disabled Refuge Outstation 2572212 IP65 Enclosure for Type B Surface Mnt Disabled Refuge Outstation 2572213 Type A Fire Telephone Outstation with Push Door 2572214 Type A Fire Telephone Outstation with Lift up Lock 2572215 Type B Green Flush Mounting Disabled Refuge Outstation 2572216 Type B Green Surface Mounting Disabled Refuge Outstation 2572217 Semi Flush Bezel for Type A Outstation 2572219 Disabled Persons Toilet Alarm 2605060 C1630 O/P Expansion Interface Board 2605060 C1630 O/P Expansion Interface Board 2605060 C1630 O/P Expansion Interface Board 2605061 C1631 Repeater Interface Board 2605061 C1631 Repeater Interface Board 2605061 C1631 Repeater Interface Board 2605062 C1632 16 Zone Interface Board 2605063 C1633 LED Driver Board 2605063 C1633 LED Driver Board 2605064 C1634 Relay Output Board 2605064 C1634 Relay Output Board 2605065 C1635 Monitored Output Board 2605065 C1635 Monitored Output Board 2605070 C1651 MZX-c+ Timer Board 2605071 MZX-c+ CONVENTIONAL PANEL 5.0 AMP PSU - C1652 2605505 MZX-c MOTHERBOARD 8 ZONE REPEATER 2605508 MZX-c 2 ZONE 2 WIRE MZX-c MOTHERBOARD 2605509 MZX-c 4 ZONE 2 WIRE MZX-c MOTHERBOARD 2605510 MZX-c 8 ZONE 2 WIRE MZX-c MOTHERBOARD 2605538 MZX-c CONVENTIONAL PANEL ZONE EOL UNIT - PK5 10-115 SR2-T Optional Back Box (2 terminals) 10-115 SR2-T Optional Back Box (2 terminals) 20-100 6” 24Vdc Electronic bell, weatherproof IP33C - Wormald Branded 20-100 6” 24Vdc Electronic bell, weatherproof IP33C - Wormald Branded 20-101 6” 24Vdc Electronic bell - red IP21C - Wormald Branded 20-101 6” 24Vdc Electronic bell - red IP21C - Wormald Branded 20-111 6” 24Vdc Electronic bell - white IP21C 20-111 6” 24Vdc Electronic bell - white IP21C 20-118 Flashni complete with deep base (IP65) 20-118 Flashni complete with deep base (IP65)
22-5049-10M WebWay High Gain Eng Pack with 10 metres of Cable 22-5049-15M WebWay High Gain Eng Pack with 15 metres of Cable 22-5054 WebWay Smart Disc Eng Pack 2-34-035G-S001 Door release magnet set, floor mount, ABS housing 24VDC 3000-201 FireRay 3000 Swivel Bracket 3000-201 FireRay 3000 Swivel Bracket 3000-201 FireRay 3000 Swivel Bracket 3-59-0404-S001 Door release magnet set, Wall Mount, Metal Housing, 230VAC 3-59-0404-S002 Door release magnet set, Wall Mount, Metal Housing, 24VDC 3-84-0301 Floor mounting bracket for wall mounted door magnets 3-87-0351 Door release magnet set, Wall Mount, ABS Housing, 24VDC 03/17
Fire Catalogue
3
3
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
2
3
2
3
2
3
2
3
2
3
2
2
2
6
2
3
3
6
6
6
6
48
48
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
6
48
4
4
6
4
4
6
4
6
4
6
4
48
48
48
48
48
48
53
27
61
33
61
33
61
33
72
45
23
23
23
3
33
17
17
3
3
3
3
Chapter 13 Page 5
Chapter 12 - Index
Product Code Description Chapter Page
3-87-0352 Door magnet Wall Mnt ABS 230V 6 3
5000-005 Universal Mounting Bracket 2 33
5000-005 Universal Mounting Bracket 3 17
5000-006 Flat Mounting Plate for 1 to 4 Prisms 2 33
5000-006 Flat Mounting Plate for 1 to 4 Prisms 3 17
5000-007 Prism Mounting Plate for 4 Prisms 2 33
5000-007 Prism Mounting Plate for 4 Prisms 3 17
5000-008 Prism Mounting Plate for 1 Prism 2 33
5000-008 Prism Mounting Plate for 1 Prism 3 17
508.020.026 TXG Emergency Management PC (no monitor) 4 2
508.020.050 19” LCD Touchscreen Monitor 4 2
508.023.001
T1204DC 4 ZONE PANEL C/W 1.5A 24VDC PSU 3 6
508.023.002 T1204A1 4 ZONE PANEL C/W 1.5A 110VAC PSU 3 6
508.023.003 T1204A2 4 ZONE PANEL C/W 1.5A 230VAC PSU 3 6
508.023.011 T1216RDC 16 ZONE REPEATER WITHOUT PSU 3 6
508.023.021 T1200EA EXPANSION BOX C/W 5.0A 110/230VAC PSU 3 6
508.023.022 T1200EDC EXPANSION BOX (NO PSU) 3
6
508.023.023 T1200B BATTERY BOX FOR T1204 4 ZONE PANEL 3 6
508.023.025 T1200 RMRS DOOR STAY KIT 3 6
508.023.035 C1665 MUSTER INTERFACE BOARD 3 6
508.023.036 A1466 RELAY OUTPUT BOARD 3 6
508.023.051 T1216 CHINESE/JAPANESE INSERT SET 3 6
508.023.052 T1232 CHINESE/JAPANESE INSERT SET 3 6
508.023.053 T1216R CHINESE/JAPANESE INSERT SET 3 6
508.023.054 T1232R CHINESE/JAPANESE INSERT SET 3 6
508.023.126 AC2SW 230VAC Changeover Unit 2 9
508.023.126 AC2SW 230VAC Changeover Unit 2 10
508.023.127 AC1SW 115VAC Changeover Unit 2 9
508.023.127 AC1SW 115VAC Changeover Unit 2 10
508.031.004.EG MZX-c 2 ZONE PANEL TYCO 2 WIRE 3 2
508.031.005.EG MZX-c 4 ZONE PANEL TYCO 2 WIRE 3 2
508.031.006.EG MZX-c 8 ZONE PANEL TYCO 2 WIRE 3 2
508.031.016.EG MZX-c 8 ZONE REPEATER PANEL 3 2
508.032.002.EA MZXC+ 4 Zone Panel English/Arabic 3 4
508.032.003.EA MZXC+ 8 Zone Panel English/Arabic 3 4
508.032.004.EA MZXC+ 16 Zone Panel English/Arabic 3 4
508.032.005.EA MZXC+ 32 Zone Panel English/Arabic 3 4
508.032.006.EA MZXC+ 8 Zone Repeater 240Vac English/Arabic 3 4
508.032.007.EA MZXC+16 Zone Repeater 240Vac English/Arabic 3 4
508.032.008.EA MZXC+ 32 Zone Repeater 240Vac English/Arabic 3 4
508.032.012 MZXC+ 4 Way Expansion Housing 3 4
508.032.013 MZXC+ 4 Way Expansion Housing with PSU 3 4
508.032.014 MZXC+ 5 Way Expansion Housing 3 4
508.032.015 MZXC+ 5 Way Expansion Housing with PSU 3 4
508.033.002.EA MZX-e SLU1 Status Lamp Unit, Indication only English / Arabic 3 7
508.033.003.EA MZX-e SLU2 Status Lamp Unit, Indication, English / Arabic 3 7
508.033.004.EA MZX-e SLU3 Full Function Status Lamp Unit, English / Arabic 3 7
508.033.005.EA MZX-e SLU4 Weatherproof Status Lamp Unit, English / Arabic 3 7
508.033.050.EA MZX-e Extinguishing Control Panel English / Arabic 3 7
508.040.001 TXG001-Single Client with 1 panel 4 2
508.040.002 TXG004-Single Client with 2 to 4 panels 4 2
508.040.003 TXG010-Single Client with 5 to 10 panels 4 2
508.040.005 TXG999-Single Client with 21 or above panels 4 2
508.040.011 TXG-C Additional Client license 4 2
508.040.021 TXG-MIN80 Minerva driver license 4 2
508.040.025 TXG-OPC - OPC Alarm / Event & Data Access Server Licence 4 2
508.040.027 TXG-CPP - SIMPLEX CPP driver 4 2
508.040.033 TXG-PBS/FAST2000 DRIVER 4 2
508.040.100 TXG USB Server Dongle/License/Software 4 2
508.200.004 Chapter 12 Page 6
Fire Catalogue
04/17
Chapter 12 - Index
Product Code Description Chapter Page
509.023.001 T1200 C1626 4 ZONE PANEL MOTHERBOARD WITH AC PSU 3 6
509.023.001 T1200 C1626 4 ZONE PANEL MOTHERBOARD WITH AC PSU 3 48
509.023.002 T1200 C1626 4 ZONE PANEL MOTHERBOARD WITHOUT AC PSU 3 6
509.023.002 T1200 C1626 4 ZONE PANEL MOTHERBOARD WITHOUT AC PSU 3 48
509.023.003 T1200 C1627 16 ZONE PANEL MOTHERBOARD WITHOUT AC PSU 3 6
509.023.003 T1200 C1627 16 ZONE PANEL MOTHERBOARD WITHOUT AC PSU 3 48
509.023.004 T1200 C1627 16 ZONE PANEL M/BOARD WITHOUT AC PSU FOR T1232 3
6
509.023.004 T1200 C1627 16 ZONE PANEL M/BOARD WITHOUT AC PSU FOR T1232 3
48
509.023.011 T1200 C1626 REPEATER MOTHERBOARD C/W AC PSU 3 6
509.023.011 T1200 C1626 REPEATER MOTHERBOARD C/W AC PSU 3 48
509.023.012 T1200 C1626 REPEATER MOTHERBOARD WITHOUT AC PSU 3 6
509.023.012 T1200 C1626 REPEATER MOTHERBOARD WITHOUT AC PSU 3 48
509.023.021 T1200 C1628 4 ZONE PANEL DISPLAY PCB 3 6
509.023.021 T1200 C1628 4 ZONE PANEL DISPLAY PCB 3 48
509.023.022 T1200 C1628 16 ZONE PANEL DISPLAY PCB 3 6
509.023.022 T1200 C1628 16 ZONE PANEL DISPLAY PCB 3 48
509.023.023 T1200 C1629 32 ZONE PANEL DISPLAY PCB 3 6
509.023.023 T1200 C1629 32 ZONE PANEL DISPLAY PCB 3 48
509.023.031 T1200 C1628 16 ZONE REPEATER DISPLAY PCB 3 6
509.023.031 T1200 C1628 16 ZONE REPEATER DISPLAY PCB 3 48
509.023.032 T1200 C1629 32 ZONE REPEATER DISPLAY PCB 3 6
509.023.032 T1200 C1629 32 ZONE REPEATER DISPLAY PCB 3 48
509.023.042 T1200 C1632 16 ZONE PANEL EXPANSION PCB 3
6
509.023.042 T1200 C1632 16 ZONE PANEL EXPANSION PCB 3 48
509.023.051 T1200 PS136 5.0 AMP 110/230VAC PSU 3 6
509.023.051 T1200 PS136 5.0 AMP 110/230VAC PSU 3 48
509.023.052 T1200 PS40 1.5 AMP 24VDC PSU 3 6
509.023.052 T1200 PS40 1.5 AMP 24VDC PSU 3 48
509.023.061 T1200 & T1200-C SPARE KEY SET 3 6
509.023.061 T1200 & T1200-C SPARE KEY SET 3 48
509.030.117 T561 Extinguishing Release Manual Callpoint. 3 8
514.001.059
Intrinsically Safe Callpoint (BG3I4NBN) 9 17
514.001.062 IF800Ex MX Digital Addressable Interface Module Assembly 9
9
514.001.063 EXI800 Interface Module 9 10
514.001.107 EX II 2 GD Addressable (EExemd) Manual Alarm Callpoint 9 11
514.001.108 EX II 2 GD Conventional (EExemd) Manual Alarm Callpoint 9 18
514.001.109 MCP220Ex Red ATEX Approved Conventional I.S. Callpoint 9 17
514.001.110.A MCP230 Weatherproof IP67 red callpoint - ADT Branded 3 26
514.001.110.T MCP230 Weatherproof IP67 red callpoint - Thorn Branded 3 26
514.001.110.Y MCP230 Weatherproof IP67 red callpoint - Tyco Branded 3 26
514.001.112 MCP260M Marine callpoint complete with LED indicator - IP67 3 26
514.001.113 MCP250M Marine callpoint complete with LED indicator 3 26
514.001.114 MCP270 Yellow callpoint ‘Evacuate’ complete with LED indicator 3 26
514.001.142.A MCP2 00 Conventional Callpoint without backbox - ADT Branded 3 26
514.001.142.T MCP200 Conventional Callpoint without backbox - Thorn Branded 3 26
514.001.142.Y MCP200 Conventional Callpoint without backbox - Tyco Branded 3 26
514.001.143.A MCP210 red indoor callpoint with LED indicator - ADT Branded 3 26
514.001.143.T MCP210 red indoor callpoint with LED indicator - Thorn Branded 3 26
514.001.143.Y MCP210 red indoor callpoint with LED indicator - Tyco Branded 3 26
514.001.160.A MCP211 red indoor callpoint with evacuate resistors and LED indicator 3 26
514.001.160.T MCP211 red indoor callpoint with evacuate resistors and LED indicator 3 26
514.001.160.Y MCP211 red indoor callpoint with evacuate resistors and LED indicator 3 26
514.002.002.A White keyswitch callpoint ‘Bomb Alert’ - ADT Branded 3 26
514.800.513 CP840Ex MX Digital Addressable Break Glass Call Point 9 9
514.800.603.A CP820 Indoor Callpoint ADT Branded 2 52
514.001.160.Y MCP211 red indoor callpoint with evacuate resistors and LED indicator 3 26
514.002.002.A White keyswitch callpoint ‘Bomb Alert’ - ADT Branded 3 26
514.800.513 CP840Ex MX Digital Addressable Break Glass Call Point 9
9
514.800.603.A CP820 Indoor Callpoint ADT Branded 2 52
04/17
Fire Catalogue
Chapter 12 Page 7
Chapter 12 - Index
Product Code Description Chapter Page
514.800.603.T CP820 Indoor Callpoint Thorn Branded 2 52
514.800.603.Y CP820 Indoor Callpoint TYCO Branded 2 52
514.800.604.A CP830 Outdoor Callpoint ADT Branded 2 52
514.800.604.T CP830 Outdoor Callpoint Thorn Branded 2 52
514.800.604.Y CP830 Outdoor Callpoint TYCO Branded 2 52
514.800.609 MCP820M Marine Isolator Callpoint Indoor 2 52
514.800.610 MCP830M Marine Isolator Callpoint Outdoor 2 52
515.001.003 ZF121 Callpoint glasses (Pack of 10) for service spares 3 28
515.001.003 ZF121 Callpoint glasses (Pack of 10) for service spares 3 48
515.001.009 CP100A glass unscored (Pack of 10) for service spares 3 28
515.001.009 CP100A glass unscored (Pack of 10) for service spares 3 48
515.001.010 Walsall Callpoint glasses (Pack of 10) for service spares 3 28
515.001.010 Walsall Callpoint glasses (Pack of 10) for service spares 3 48
515.001.014 CP200 Spare glasses, black Arabic text on a white background 3 28
515.001.014 CP200 Spare glasses, black Arabic text on a white background 3 48
515.001.021 Standard Red surface mounting back box for MCP & CP callpoints 2 53
515.001.021 Standard Red surface mounting back box for MCP & CP callpoints 3 27
515.001.023 CP200 Spare glasses white Dutch text on clear background 3 28
515.001.023 CP200 Spare glasses white Dutch text on clear background 3 48
515.001.024 CP200 Spare glasses, black Arabic/English text 3 28
515.001.024 CP200 Spare glasses, black Arabic/English text 3 48
515.001.025 CP200/500/900 Glasses, clear English text on white background 2 53
515.001.025 CP200/500/900 Glasses, clear English text on white background 3 28
515.001.025 CP200/500/900 Glasses, clear English text on white background 3 48
515.001.026 Black callpoint bezel for CP200/800 models. 2 53
515.001.026 Black callpoint bezel for CP200/800 models. 3 27
STI-13010FR callpoint STOPPER Flush 2 54
STI-13010FR callpoint STOPPER Flush 3 29
STI-13110FR
callpoint STOPPER Surface 2 54
STI-13110FR callpoint STOPPER Surface 3 29
STI-13020FR callpoint STOPPER Flush With Sounder 2 54
STI-13020FR callpoint STOPPER Flush With Sounder 3 29
STI-13120FR callpoint STOPPER Surface With Sounder 2 54
STI-13120FR callpoint STOPPER Surface With Sounder 3 29
515.001.033 IPO36 Break Seal Kit for STOPPER 2 54
515.001.033 IPO36 Break Seal Kit for STOPPER 3 29
515.001.033 IPO36 Break Seal Kit for STOPPER 3 48
515.001.034 STI1230 Surface fit STOPPER II 2 54
515.001.034 STI1230 Surface fit STOPPER II 2 55
515.001.034 STI1230 Surface fit STOPPER II 3 29
515.001.034 STI1230 Surface fit STOPPER II 3 30
515.001.035 STI3150 callpoint STOPPER II Weatherproof 2
54
515.001.035 STI3150 callpoint STOPPER II Weatherproof 2 55
515.001.035 STI3150 callpoint STOPPER II Weatherproof 3 29
515.001.035 STI3150 callpoint STOPPER II Weatherproof 3 30
STI-13110FR
callpoint STOPPER Surface Weatherproof 2 54
STI-13110FR callpoint STOPPER Surface Weatherproof 2 55
STI-13110FR callpoint STOPPER Surface Weatherproof 3 29
STI-13110FR callpoint STOPPER Surface Weatherproof 3 30
515.001.043 STI6720 Keybox with printed glass 2 56
515.001.043 STI6720 Keybox with printed glass 3 31
515.001.045 Test key for all MCP and CP style callpoints 2 53
515.001.045 Test key for all MCP and CP style callpoints 2 79
515.001.045 Test key for all MCP and CP style callpoints 3 27
515.001.045 Test key for all MCP and CP style callpoints 3 48
515.001.119 EN54 Part 11 Spare Glass for MCP and CP Callpoints 2 53
515.001.119 EN54 Part 11 Spare Glass for MCP and CP Callpoints 2 79
515.001.119 EN54 Part 11 Spare Glass for MCP and CP Callpoints 3 28
515.001.119 EN54 Part 11 Spare Glass for MCP and CP Callpoints 3 48
515.001.127 Deformable operating unit “glass” for use in place of glasses 3 28
515.001.127 Deformable operating unit “glass” for use in place of glasses 3 48
515.001.127 Deformable operating unit “glass” for use in place of glasses 2 53
515.001.127 Deformable operating unit “glass” for use in place of glasses 3 28
Chapter 12 Page 8
Fire Catalogue
04/17
Chapter 12 - Index
Product Code Description Chapter Page
515.001.127 Deformable operating unit “glass” for use in place of glasses 3 48
515.001.128 Callpoint hinged cover for use with MCP callpoints 2 53
515.001.128 Callpoint hinged cover for use with MCP callpoints 3 27
516.015.007 FireRay Reflector 100 x 100 mm 2 32
516.015.007 FireRay Reflector 100 x 100 mm 3 16
516.015.009 STI9625 Smoke beam/CCTV guard 2 56
516.015.009 STI9625 Smoke beam/CCTV guard 3 31
516.015.020 FireRay 5000 System (50 m) 2 32
516.015.020 FireRay 5000 System (50 m) 3 16
516.015.021 FR 5000 Detector Head (50m) 2 32
516.015.021 FR 5000 Detector Head (50m) 3 16
516.015.030 FireRay 3000 Beam Detector 2 33
516.015.030 FireRay 3000 Beam Detector 3 17
516.015.031 FR3000 Additional Head Set
2 33
516.015.031 FR3000 Additional Head Set 3 17
516.016.005 LD40 High resistance sensor cable blue - 200 M reel 2 34
516.016.005 LD40 High resistance sensor cable blue - 200 M reel 3 18
516.016.006 LD40 High resistance sensor cable black - 200 M reel 2 34
516.016.006 LD40 High resistance sensor cable black - 200 M reel 3 18
516.016.010 LD40 EOL Termination kit (PK10) 2 34
516.016.010 LD40 EOL Termination kit (PK10) 3 18
516.016.011 LD40 In-line Jointing kit (PK10) 2 34
516.016.011 LD40 In-line Jointing kit (PK10) 3 18
516.016.012 LD40 Analyser module with conventional detection zone interface 2 34
516.016.012 LD40 Analyser module with conventional detection zone interface 3 18
516.016.201 B6782-003 EDGE CLIP 2-3 mm WEB 2 34
516.016.201 B6782-003 EDGE CLIP 2-3 mm WEB 3 18
516.016.202 B6782-024 EDGE CLIP 3-8 mm WEB 2 34
516.016.202 B6782-024 EDGE CLIP 3-8 mm WEB 3 18
516.016.203 B6782-025 EDGE CLIP 8-13 mm WEB 2 34
516.016.203 B6782-025 EDGE CLIP 8-13 mm WEB 3 18
516.016.204 B6782-026 EDGE CLIP 14-20 mm WEB 2 34
516.016.204 B6782-026 EDGE CLIP 14-20 mm WEB 3 18
516.016.205 B6782-004 ‘T’ CLIP 2 34
516.016.205 B6782-004 ‘T’ CLIP 3 18
516.016.206 B6782-005 PIPE CLIP 2 34
516.016.206 B6782-005 PIPE CLIP 3 18
516.016.207 B6782-023 ‘V’ CLIP 2 34
516.016.207 B6782-023 ‘V’ CLIP 3 18
516.016.208 B6782-008 NEOPRENE SLEEVE 2 34
516.016.208 B6782-008 NEOPRENE SLEEVE 3 18
516.016.301 ICAM IAS800 Aspirated Smoke Dual Detector 7 7
516.016.303 ICAM Course Filter (PK10) 7 7
516.016.304 ICAM IAS801 Aspirated Smoke Single Detector 7 7
516.016.305 ICAM IAS802 Aspirated Smoke Dual Detector 7 7
516.016.306 ICAM In-Line Filter Housing 7 7
516.016.310 MZX SensorLaser™ Plus 1/1 – 1 km range, 1 sensor cable 9 27
516.016.311 MZX SensorLaser™ Plus 1/2 – 1 km range, 2 sensor cables 9 27
516.016.312 MZX SensorLaser™ Plus 2/1 – 2 km range, 1 sensor cable 9 27
516.016.313 MZX SensorLaser™ Plus 2/2 – 2 km range, 2 sensor cables 9 27
516.016.314 MZX SensorLaser™ Plus 4/1 – 4 km range, 1 sensor cable 9 27
516.016.315 MZX SensorLaser™ Plus 4/2 – 4 km range, 2 sensor cables 9 27
516.016.316 MZX SensorLaser™ Plus 8/1 – 8 km range, 1 sensor cable 9 27
516.016.317 MZX SensorLaser™ Plus 8/2 – 8 km range, 2 sensor cables 9 27
516.016.318 MZX SensorLaser™ Plus Connection Set 9 27
516.016.319 MZX SensorLaser™ Plus iBox 9 27
516.016.320 MZX SensorLaser™ Plus Relay Controller Set 9 27
516.016.321 MZX SensorLaser™ Plus Power Supply 9 27
516.016.322 MZX SensorLaser™ Plus Safety Cable (per metre) 9 27
516.016.322.C MZX SensorLaser™ Plus Safety Connector 9 27
516.016.323 MZX Steel Wire Armoured SensorLaser Plus Cable (per metre) 9 27
516.016.323.C MZX SensorLaser™ Plus Steel Connector 9 27
516.016.324 MZX SensorLaser™ Plus Setting Tool 9
27
04/17
Fire Catalogue
Chapter 12 Page 9
Chapter 12 - Index
Product Code Description Chapter Page
516.016.325 MZX SensorLaser™ Plus Relay Extension Set 9
27
516.016.326 MZX SensorLaser™ Plus Zinc Plastic Clamp Set (PK 100) 9 27
516.016.327 MZX SensorLaser™ Plus Steel Plastic Clamp Set (PK 100) 9 27
516.016.328 MZX SensorLaser™ Plus Steel Zinc Clamp Set (PK 100) 9 27
516.016.329 MZX SensorLaser™ Plus Stainless Steel Clamp Set (PK 100) 9 27
516.016.330 MZX SensorLaser™ Plus Spare Unit 9 27
516.016.331 MZX SensorLaser™ Plus Demo Unit 9
27
516.016.332 MZX SensorLaser™ Plus Demo Box 9 27
516.016.333 MZX SensorLaser™ Plus 3/1 – 3 km range, 1 sensor cable 9 27
516.016.334 MZX SensorLaser™ Plus 3/2 – 3 km range, 2 sensor cables 9 27
516.018.001 VLP-012 LaserPLUS Detector, programmer and display 7 3
516.018.002 VLP-002 LaserPLUS Detector and display 7 3
516.018.004 VLS-214 FD7 Scanner, programmer and display with 7 relays 7 4
516.018.005
VLS-204 FD7 Scanner and display with 7 relays 7 4
516.018.007 VLS-314 FD12 Scanner, programmer and display with 12 relays 7 4
516.018.008 VLS-304 FD12 Scanner and display with 12 relays 7 4
516.018.010 VLC-500-RO Relays Only Version (RO) 7 2
516.018.011 VLC-505-VN VESDA net Version (VN) 7 2
516.018.012 VLC-800 MX Addressable Vesda Laser Compact 7 2
516.018.013 VLP-400 LaserPLUS Detector with fire OK LED 7 3
516.018.014 VIO800 MX VESDA Interface 2 45
516.018.016 VLS-600 FD7 Scanner with Fire OK LED 7 4
516.018.019 VLS-700 FD12 Scanner with Fire OK LED 7 4
516.018.020 VLF-250 Vesda Laserfocus (with English overlay) 7 1
516.018.022 VIC-010 LaserFocus VesdaNetwork Card 7 1
516.018.023 VLF-500 Vesda Laserfocus (with English overlay) 7 1
516.018.030 VLC-500-RO Relays Only Version (RO) Marine 7 2
516.018.031 VLC-500-VN Vesdanet Version (VN) Marine 7 2
516.018.032 VRT-J00 Remote Display c/w 7 relays Marine 7 2
516.018.101 VRT-100 Remote programmer 7 5
516.018.102 VRT-200 Remote display including 7 relays 7 5
516.018.103 VRT-300 Remote VESDAnet socket 7 5
516.018.104 VRT-400 Remote scanner display including 7 relays 7 5
516.018.106 VRT-600 Remote detector display no relays 7 5
516.018.107 VRT-700 Remote scanner display no relays 7 5
516.018.108 VRT-800 Remote scanner display with 12 relays 7 5
516.018.119 VRT-J00 Compact Display c/w 7 relays 7 5
516.018.120 VRT-K00 Compact Display no relays 7 5
516.018.201 VSR-2000 19” Sub-rack with 1 detector display and 3 blank 7 6
516.018.203 VSR-2210 19” Sub-rack, 2 detector displays, programmer & 1 blank 7 6
516.018.204 VSR-2221 19” Sub-rack with 3 detector displays and programmer 7 6
516.018.206 VSR-2222 19” Sub-rack with 4 detector displays 7 6
516.018.210 VSR-CUSTOM Custom sub-rack housing 7 6
516.018.214 VSU-E Blank scanner sub-unit with 7 relays 7 6
516.018.219 VSU-J Compact display sub-unit plus 7 relays 7 6
516.018.260 VSU-0 Blank Sub-unit 7 6
516.018.261 VSU-1 Programmer sub-unit 7 6
516.018.262 VSU-2 Detector display sub-unit plus 7 relays 7 6
516.018.264 VSU-4 Scanner display sub-unit plus 7 relays 7 6
516.018.265 VSU-5 Blank sub-unit with 7 relays 7 6
516.018.268 VSU-8 Scanner display sub-unit with 12 relays 7 6
516.018.269 VSU-9 Blank display sub-unit with 12 relays 7 6
516.018.303 LaserPLUS 020-050 IP66 Enclosure 7 6
516.018.401 VHH-100 Hand held programmer plus leads 7 6
516.018.402 VHX-0200 PC link HLI plus leads (MK2) 7 6
516.018.407 VESDA VPS-220 2A 24VDC PSU 7 6
516.018.410 VESDA VPS-250-E 5A 24VDC PSU 7 6
516.018.502 VSP-004 Scanner display (spare) 7 6
516.018.504 VSP-005 Spare filter cartridge 7 6
516.018.505 VSP-019 Filter cover door (spare) 7 6
516.018.506 VSP-006 Spare detector chassis and manifold 7 6
516.018.508 VSP-008 Spare remote termination card 7 relays 7 6
516.018.509 VSP-009 Spare scanner chassis and manifold 7 6
516.018.514 VSP-014 Spare header termination card 7 relays 7 6
516.018.515 VSP-015 Spare aspirator fan 7 6
Chapter 12 Page 10
Fire Catalogue
04/17
Chapter 12 - Index
Product Code Description Chapter Page
516.018.901 Aspirating Pipe & Fittings Pipe 25 mm diameter 7 8
516.018.902 Aspirating Pipe & Fittings Socket 25 mm 7 8
516.018.903 Aspirating Pipe & Fittings Socket Union 25 mm 7 8
516.018.904 Aspirating Pipe & Fittings Long Radius bend 90° 7 8
516.018.905 Aspirating Pipe & Fittings Elbow 25 mm 7 9
516.018.906 Aspirating Pipe & Fittings End Cap 25 mm 7 9
516.018.907 Aspirating Pipe & Fittings Equal Tee 25 mm 7 9
516.018.908 Aspirating Pipe & Fittings Pipe Clip 25 mm 7 9
516.018.909 Aspirating Pipe & Fittings Socket Adaptor 25 mm to 3/4” 7 8
516.018.910 Aspirating Pipe & Fittings Solvent Cement 7 9
516.018.911 Aspirating Pipe & Fittings Capillary Tube Conical Sample Point 7 9
516.018.912 Aspirating Pipe & Fittings Capillary Tube Flush Sample Point 7 9
516.018.915 Aspirating Pipe & Fittings Capillary Tube 10 mm Dia 7 9
516.018.918 Aspirating Pipe & Fittings Pipe Cutter 7 10
516.018.920 Aspirating Pipe & Fittings Pipe Ties (Red) 7 10
516.018.921 Wire Burn Test Box 7 10
516.018.923 Smoke Test Wire 7 10
516.018.925 Aspirating Pipe & Fittings In-Line Filter (red) 7 9
516.018.926 Aspirating Pipe & Fittings Replacement Filter Elements (pack of 4) 7 9
516.018.927 Water Condenser for use with VESDA ASD Systems 7 9
516.033.011 T54B Point Type heat detector - 60°C 3 15
516.033.012 T54B Point Type heat detector - 90°C 3 15
516.033.013 T54B Point Type heat detector - 100°C 3 15
516.033.014 T54B Point Type heat detector - 145°C 3 15
516.037.003 S231f+ Triple IR Solar Blind Flame Detector 9
6
516.037.004 S231i+ Triple IR Solar Blind Flame Detector 9 6
516.037.015 S232f+ Triple IR Solar Blind Flame Detector 9
6
516.038.003 S241f+ Triple IR Solar Blind Flame Detector 9 6
516.038.004 S241i+ Triple IR Solar Blind Flame Detector 9
6
516.040.002 S261f+ Triple IR Solar Blind Flame Detector 9 6
516.040.014 FV282f+ Triple IR Solar Blind Flame Detector 9
6
516.041.003 S271f+ Triple IR Solar Blind Flame Detector 9 6
516.041.004 S271i+ Triple IR Solar Blind Flame Detector 9 6
516.052.041.Y MD611Ex Conventional Fixed Temperature Heat Detector 9 16
516.052.051.Y MD601Ex Conventional Rate of Rise Heat Detector 9 16
516.054.011.Y MR601TEx Conventional High Performance Optical Smoke Detector 9
16
516.061.001.Y MDU601Ex Enhanced Carbon Monoxide Fire & Heat Detector 9 16
516.100.013 Test Gas Kit - 12 L can of 2.5% methane, adaptor and tube 2
31
516.100.014 Test Gas - 12 L can of 2.5% methane 2 31
516.100.050 GD210 Flammable Gas Detector 4 - 20mA interface 2 31
516.300.006 FV311S Flameproof Detector - cable gland entries - no camera 9 4
516.300.007 FV311SC-N Fproof Detector - cable gland entries - NTSC camera 9 4
516.300.008
FV311SC Flameproof Detector - cable gland entries - PAL camera 9 4
516.600.001 601P Optical Smoke Detector 3 12
516.600.002 601PH High Performance Optical Smoke Detector 3 12
516.600.003 601H-R Rate of Rise Heat Detector 3 12
516.600.004 601CH Enhanced Carbon Monoxide Fire Detector 3 12
516.600.006 601F Solar Blind Infra Red Flame Detector 3 13
516.600.007 601F-M Solar Blind Infra Red Flame Detector Marine 3 13
516.600.033 631H-F Fixed Temperature 90°C Heat Detector LPCB /Marine 3 12
516.600.066 601FEx Infra-Red Flame Detector 9
16
516.600.067 601FEx-M Infra-Red Flame Detector (Marine) 9 16
516.600.201 601P-M Optical Smoke Detector Marine Tyco branded 3 12
516.600.202 601PH-M High Performance Optical Smoke Detector Marine 3 12
516.600.203 601H-R-M Rate of Rise Heat Detector Marine Tyco branded 3 12
04/17
Fire Catalogue
Chapter 12 Page 11
Chapter 12 - Index
Product Code Description Chapter Page
516.600.214 611H-F Fixed Temperature 60°C Heat Detector LPCB /Marine 3 12
516.800.006 801F LPCB Approved 2 31
516.800.007 811F Marine Approved 2 31
516.800.066 801FEx I.R. Flame Detector 9
8
516.800.067 811FEx Marine I.R. Flame Detector 9 8
516.800.515.A 801I Ionisation detector ADT branded 2 31
516.800.515.T 801I Ionisation detector Thorn branded 2 31
516.800.515.Y 801I Ionisation detector Tyco branded 2 31
516.800.518 801PS High sensitivity smoke detector 2 31
516.800.530 801PHEx Optical Smoke + Heat Detector 9 8
516.800.531 801CHEx Carbon Monoxide + Heat Detector 9
8
516.800.532 801HEx Heat Detector 9 8
516.800.905 801RB Relay base2 37
516.800.908 801RIL remote indication LED 2 38
516.800.909 801HL indication lamp 2 38
516.800.910 802SB MX Loop Powered Sounder Base 2 37
516.800.911 901SB Universal Sounder Base 2 37
516.800.913 812SB MX Loop Powered UL Sounder Base 2 37
516.800.915 MX Address flags (pack of 100) 2 39
516.800.917 800RT Detector Removal Tool 5 1
516.800.922 MX Service tool, Spare programming lead 2 76
516.800.922 MX Service tool, Spare programming lead 2 79
516.800.923 MX SERVICE UK - ACCESSORY KIT 2
77
516.800.924 MX Service tool, Spare pins for programming lead pk of 10 2 76
516.800.924 MX Service tool, Spare pins for programming lead pk of 10 2 79
516.800.931 Address flag labels Loop A - White 2 39
516.800.932 Address flag labels Loop B - Yellow 2 39
516.800.933 Address flag labels Loop C - Purple 2 39
516.800.934 Address flag labels Loop D - Green 2 39
516.800.935 Address flag labels Loop E - Grey 2 39
516.800.936 Address flag labels Loop F - Blue 2 39
516.800.937 Address flag labels Loop G - Orange 2 39
516.800.938 Address flag labels Loop H - Red 2 39
516.800.956 SAB 801 Low Power Sounder Addressable Beacon 2 37
516.800.957 LPSB3000 Sounder L/P addressable base 2 58
516.800.958 LPAV3000 Sounder beacon L/P addressable base 2 58
516.800.959 DAB3-4 Mounting Flange – type B for conduit (pk of 10) 2 58
516.800.960 LPSY800-R L/P Symphoni Sounder (indoor use) red 2 59
516.800.961 LPSY800-W LP Symphoni Sounder (indoor use) white 2 59
516.800.962 LPSY865 L/P Symphoni Sounder IP65 (out door use) 2 59
516.800.963 LPAV800-R L/P Symphoni Sounder/Beacon (indoor use) red 2 59
516.800.964 LPAV800-W L/P Symphoni Sounder/Beacon (indoor use) white 2 59
516.800.965 LPAV865 L/P Symphoni Sounder/ Beacon IP65 (outdoor use) 2 59
516.830.051 830PH Photo Heat Detector 2 29
516.830.052 830P Photo Detector 2 29
516.830.053 830H Heat Detector 2 30
516.830.054 830PC 3oTec Triple Sensor Detector 2 30
516.850.051 850PH Photo Heat Detector with built in line isolator 2 29
516.850.052 850P Photo Detector 2 29
516.850.053 850H Heat Detector with built in line isolator 2 30
516.850.054 850PC 3oTec Triple Sensor Detector with built in line isolator 2 30
516.850.055 851PH Photo Heat Detector Marine Only 2 29
516.850.900 850EMT Engineering Management Tool 2 76
517.001.120 System 601 EOL Unit (Pk 10) 9 16
517.001.120 System 601 EOL Unit (PK10) 9 24
517.001.184 S200+ Detector Mounting Bracket 9
5
517.001.196 UC2 4 Way Barrier Housing 9 24
517.001.198 MT2 2 Way Zener Barrier Housing 9
24
517.001.199 MT5 5 Way Zener Barrier Housing 9
24
517.001.200 MT12 12 Way Zener Barrier Housing 9 24
Chapter 12 Page 12
Fire Catalogue
04/17
Chapter 12 - Index
Product Code Description Chapter Page
517.001.205 ERL7 Earth rail for I.S. systems 9 24
517.001.206 ETM7 Earth termination connection system 9 24
517.001.207 IMB7 Insulating mounting block 9 24
517.001.224 Adaptor for Solo Access Poles 5 2
517.001.226 1.13 metre Solo Extension Pole 5 1
517.001.230 Solo Telescopic Pole extends from 1.26 to 4.5 metres 5 1
517.001.236 Testifier Smoke, Heat & CO Detector Test Kit 5 1
517.001.237 6 x Replacement smoke capsules for use with Testifire 5 1
517.001.238 6 x Replacement CO capsules for use with Testifire 5
1
517.001.239 Battery Baton for use with Testifire and Heat Detector Tester 5 2
517.001.240 Detector Removal Tool Universal 5 1
517.001.243 Fast Charger for use with Solo Battery Batons 5 2
517.001.247 DX170 Enclosure 910
517.001.248 DX070 Enclosure 9 10
517.001.254 Cordless Heat Detector Test Kit 5 2
517.001.255 Dispenser for Solo Smoke and CO Canister 5 2
517.001.256 Solo Smoke Detector Tester aerosol canister 5 2
517.001.262 Solo CO Detector Tester gas canister 5 2
517.001.263 S200+ Weather Protection Assembly 9 5
517.001.264 Protective carry and storage bag for the Solo / Testifire 5 1
517.001.266 S200+ Spares Kit & Sealant 9 5
517.001.267 Testifier Smoke & Heat Detector Test Kit 5 2
517.001.301 MTL7728+ Zener Safety Barrier for conventional detection circuits 9 23
517.001.302 MTL5561 2 CHANNEL GALVANIC ISOLATOR 9
23
517.001.304 MTL5525 I.S. SOUNDER DRIVER 9 10
517.001.304 MTL5525 I.S. SOUNDER DRIVER 9 23
517.001.306 Pepperl+Fuchs KFD0-CS-EX1.54 Galvanic Isolator 9 10
517.017.005 Aspirating Pipe & Fittings Sampling Point Label 7 10
517.017.006 Aspirating Pipe & Fittings Pipe Label 7 10
517.025.028 DPS450 Probe tube stainless steel 450 mm and exhaust 2 40
517.025.028 DPS450 Probe tube stainless steel 450 mm and exhaust 3 23
517.025.029 DPS600 Probe tube stainless steel 600 mm and exhaust 2 40
517.025.029 DPS600 Probe tube stainless steel 600 mm and exhaust 3 23
517.025.030 DPS750 Probe tube stainless steel 750 mm and exhaust 2 40
517.025.030 DPS750 Probe tube stainless steel 750 mm and exhaust 3 23
517.025.031 DPS900 Probe tube stainless steel 900 mm and exhaust 2 40
517.025.031 DPS900 Probe tube stainless steel 900 mm and exhaust 3 23
517.025.033 DPS1500 Probe tube stainless steel 1500 mm and exhaust 2 40
517.025.033 DPS1500 Probe tube stainless steel 1500 mm and exhaust 3 23
517.025.035 SMP69 Stainless Steel Duct Probe Unit 2 40
517.025.035 SMP69 Stainless Steel Duct Probe Unit 3 23
517.025.055
DPKF - Filter245
517.025.055
DPKF - Filter324
517.025.056 DPK6 Duct Probe with 4B-C 4” Continuity Base
3
24
517.025.056 DPK6 Duct Probe with 4B-C 4” Continuity Base
2
45
517.025.058 DPK6-60 - Duct Probe Tube 60 cm
3
24
517.025.058 DPK6-60 - Duct Probe Tube 60 cm
2
45
517.025.059 DPK6-150 - Duct Probe Tube 150 cm
3
24
517.025.059 DPK6-150 - Duct Probe Tube 150 cm
2
45
517.025.060 DPK6-280 - Duct Probe Tube 280 cm
3
24
517.025.060 DPK6-280 - Duct Probe Tube 280 cm
2
45
517.025.061 DPK6-MB - Duct Pobe Mounting bracket
2
45
517.025.061 DPK6-MB - Duct Pobe Mounting bracket
3
24
517.035.007 M520 Ancillary Cover 2 49
517.035.010 K2142 White plastic surface mount backbox 2 50
517.035.011 K2214 ALM Metal Surface Mount backbox 2 50
517.035.014 8621C Steel Flush Mount MK backbox 2 50
517.035.015 QFB/2 Dry lining flush mount backbox 2 50
517.050.002.A Line Shorting Adapter 231
517.050.005 4” Detector Base Locking Pin Kit (PK100) 2 37
517.050.005 4” Detector Base Locking Pin Kit (PK100) 3 21
517.050.011 Steel Protective Detector Cage 2 38
517.050.011 Steel Protective Detector Cage 3 22
517.050.015 Volume Adjustment Tool 2 37
04/17
Fire Catalogue
Chapter 12 Page 13
Chapter 12 - Index
Product Code Description Chapter Page
517.050.015 Volume Adjustment Tool 3 21
517.050.022 Volume Pot Spare Cover (1 sheet of 144) 2 37
517.050.022 Volume Pot Spare Cover (1 sheet of 144) 3 21
517.050.023 5BEX 5” Universal Ex Base 9
16
517.050.041 4B 4” Detector Base 2 35
517.050.041 4B 4” Detector Base 2 72
517.050.041 4B 4” Detector Base 3 20
517.050.041
4B 4” Detector Base 3 46
517.050.041 4B 4” Detector Base 3 47
517.050.042 4B-C 4” Continuity Base 2 35
517.050.043 4B-I 4” Isolator Base 2 35
517.050.045 4B-D 4” Diode Continuity Base
3 20
517.050.045 4B-D 4” Diode Continuity Base 3 46
517.050.045 4B-D 4” Diode Continuity Base 3 47
517.050.051 4B-DHM Deckhead Mount 2 38
517.050.051 4B-DHM Deckhead Mount 3 22
517.050.052 4B-EM 4” Euro Mount 2 38
517.050.052 4B-EM 4” Euro Mount 3 22
517.050.054 4B-6A 4” to 6” Base Adaptor 2 36
517.050.054 4B-6A 4” to 6” Base Adaptor 3 20
517.050.056 CTA-BB CTA Back Box 2 36
517.050.056 CTA-BB CTA Back Box 3 20
517.050.057 CTA-BC CTA Bezel and Clamp 2 36
517.050.057 CTA-BC CTA Bezel and Clamp 3 20
517.050.058 CTA-AP CTA Adaptor Plate 2 36
517.050.058 CTA-AP CTA Adaptor Plate 3 20
517.050.060 Ceiling Tile Adaptor Kit 2 36
517.050.060 Ceiling Tile Adaptor Kit 3 20
517.050.501 Sample set of coloured detector covers and bases - set of 10 2 30
517.050.502 Detector Cover & Base in Orange Semi Gloss-pack of 10 2 30
517.050.503 Detector Cover & Base in Yellow Gloss-pack of 10 2 30
517.050.504 Detector Cover & Base in Matt Green-pack of 10 2 30
517.050.505 Detector Cover & Base in Matt Red-pack of 10 2 30
517.050.506 Detector Cover & Base in Matt Brown-pack of 10 2 30
517.050.507 Detector Cover & Base in Blue Gloss-pack of 10 2 30
517.050.508 Detector Cover & Base in Pink Gloss-pack of 10 2 30
517.050.509 Detector Cover & Base in Metallic Silver-pack of 10 2 30
517.050.510 Detector Cover & Base in Metallic Gold-pack of 10 2 30
517.050.511 Detector Cover & Base in Matt Black-pack of 10 2 30
517.050.603 DHM-5B deckhead mounting 916
517.050.612 Base Accessory terminal kit (pack of 10) 2 38
517.050.612 Base Accessory terminal kit (pack of 10) 3 22
517.050.614 CW-5B Detector Cage 2 38
517.050.614 CW-5B Detector Cage 3 22
517.300.001 MB300 Mounting Bracket 9 4
517.300.002 WH300 Stainless Steel Weather Hood 9 4
517.300.006 MK300 Field Spares Kit 9 4
517.300.021 WT300 Walk-test Controller 9 4
517.300.022 CTI300 Off-line Configuration Tool Kit 9 4
519.001.008 Door Release Button 6 3
A4FRAME Fire Notice Snap Frame A4 346 x 260 x 25 mm
6 4
A3FRAME
Fire Notice Snap Frame A3 475 x 350 x 25 mm 6 4
A2FRAME
Fire Notice Snap Frame A2 650 x 475 x 25 mm
6 4
A1FRAME
Fire Notice Snap Frame A1 890 x 645 x 25 mm
6 4
527.001.028 Micro-switch Lock Keep & Back-plate For Deadlock 3 8
LPB24-C-T 24 V DC LED Strobe Clear lens
2 71
LPB24-C-T 24 V DC LED Strobe Clear lens
3 44
LPB24-B-T 24V DC LED Strobe Blue lens 2 71
LPB24-B-T 24V DC LED Strobe Blue lens
3 44
LPB24-A-T 24V DC LED Strobe Amber lens
3 44
LPB24-R-T 24V DC LED Strobe Red lens 2 71
LPB24-R-T 24V DC LED Strobe Red lens
3 44
540.001.038 XB8 Intrinsically Safe Xenon Beacon 9 20
540.001.039 XB11 Flameproof Xenon Beacon 9 22
540.003.006 Remote Indication LED 3 22
Chapter 12 Page 14
Fire Catalogue
04/17
Chapter 12 - Index
Product Code Description Chapter Page
540.007.001 E1 Single Red lamp unit Heavy Duty IP67 CastAluminium 3 8
540.007.002 E3 Red/Amber/Green lamp unit 3 8
540.011.012 Single gang flush mount LED (red)/Buzzer Unit 2 70
540.011.012 Single gang flush mount LED (red)/Buzzer Unit 3 43
540.011.013 Single gang surface mount LED (red)/Buzzer Unit 2 70
540.011.013 Single gang surface mount LED (red)/Buzzer Unit 3 43
545.800.004 LIM800 Ancillary Line Isolator Module 2 43
545.800.033 LIM800 Ancillary Line Isolator Module c/w front cover 2 43
546.004.005 Intrinsically safe sounder circuit interface module 9 23
547.004.002 DIN rail mounting bracket for MZX ancillary module 2 49
555.800.001 MIM800 mini-input module 2 42
555.800.002 CIM800 contact input monitor 2 42
555.800.012 DIM800 detector input monitor 2 42
555.800.032 CIM800 Module c/w Front Cover 2 42
555.800.042 DIM800 Module c/w front cover 2 42
555.800.063 SIO800 Single Input/Output Module 2 43
555.800.064 SIO800 Single Input/Output Module c/w Front Cover 2 43
555.800.065 MIO800 Multi I/O Module 2 45
555.800.066 BDM800 Beam Detector Module c/w Cover 2 45
555.800.067 BTM800 Beam Terminal Module c/w Cover 2 45
555.800.069 TSM800 Door Control Module 2 45
555.800.070 QMO850 Quad Monitored Output Module 2 46
555.800.071 QIO850 Quad Input/Output Module 2 46
555.800.072 SIO800 Single Input/Output Module in EExd Housing 9 14
555.800.073 QRM850 Quad Relay Output Module 2 46
557.001.040 Mk 2 Sounder Cap pack of 5
2 64
557.001.040 Mk 2 Sounder Cap pack of 5
3 21
557.180.005 80 way Mimic driver module 2 7
557.180.005 80 way Mimic driver module 2 19
557.180.016 XIOM Input/Output Expansion Module (16 Way) 2 7
557.180.016 XIOM Input/Output Expansion Module (16 Way) 2 21
557.180.022 Terminal chamber PCB assembly 2 9
557.180.025 Minerva Comms Driver Module 4 6
557.180.052 Serial Printer Driver Kit 2 20
557.180.052 Serial Printer Driver Kit 2 79
557.180.053 Isolated RS485 IC (for U16) 2 20
557.180.053 Isolated RS485 IC (for U16) 2 79
557.180.095 STK8 stacking kit 2 49
557.180.096.A ANC-8 MINERVA ancillary housing 2 49
557.180.097.A ANC-3 MINERVA ancillary housing 2 49
557.180.148.A TLO/TLD Housing - ADT branded 4 6
557.180.151 RS232/422 converter for LCD Repeater 2 24
557.180.208 MX2 Spare Keys 2 79
557.180.209 Keyswitch assembly for use with MX2 controllers (spare) 2 79
557.180.219 PC to TLI800EN Networtk Card Connection Cable 4 4
557.180.220 LQ 300+ Printer Ribbon (spare) 2 24
557.180.239 DOT Matrix printer 80 columns LQ 300+ 2 24
557.180.423 TM520 timer module (non addressable) 2 43
557.180.452 Marine 19” rack mount kit for use with surface mounting housings 2 9
557.180.454 Marine Bulkhead Mount 2 9
557.180.699 TLD 530 ThornNet/MXNet direct line driver PCB 4 6
557.200.003 MX4000 Two to Four Loop Panel – Shallow Back Box 2 5
557.200.004 MX4000 Two to Eight Loop Panel – Deep Back Box 2 5
557.200.005 MX-BBX 17Ah shallow expansion and battery box 2 6
557.200.006 MX-DPBX 38Ah deep expansion and battery box 2 6
557.200.009 MX4000 Two to Four Loop Panel - Flush Back Box 2 5
557.200.012 MXR Repeater with shallow backbox (24Vdc) 2 7
557.200.013 MXR-PSU Repeater and addressable PSU (120-240 Vac) 2 7
557.200.014 MXAPSU17 Boxed Addressable PSU (17A/H) 2 16
557.200.015 MXAPSU38 Boxed Addressable PSU (38A/H) 2 16
557.200.016 MX-BATT Deep Battery Box (322H x 442W x 217D mm) 2 6
04/17
Fire Catalogue
Chapter 12 Page 15
Chapter 12 - Index
Product Code Description Chapter Page
557.200.017 557.200.019 557.200.029 557.200.030 557.200.039 557.200.071 557.200.071 557.200.074 557.200.074 557.200.076 557.200.076 557.200.077 557.200.077 557.200.078 557.200.078 557.200.079 557.200.079 557.200.080 557.200.080 557.200.203 557.200.205 557.200.207 557.200.208 557.200.209 557.200.210 557.200.520 557.200.521 557.200.523 557.200.526 557.200.530 557.200.531 557.200.538 557.200.600 557.200.601 557.200.602 557.200.604 557.200.605 557.200.606 557.200.606 557.200.610 557.200.611 557.200.612 557.200.620 557.200.621 557.201.210 557.201.211 557.201.216 557.201.231 557.201.232 557.201.233 557.201.233 557.201.234 557.201.234 557.201.300 557.201.303 557.201.303 557.201.303 557.201.303 557.201.303 557.201.306 557.201.307 557.201.310 557.201.401 557.201.401 MXR-F Repeater with flush backbox (24Vdc) MX-BBX-F 17Ah shallow flush expansion and battery box MX Paging System Pager Transmitter Remote LCD Repeater MKII TLI800EN Network Interface in Housing c/w PSU Fire Tek Pro Paging System Paging Transmitter Fire Tek Pro Paging System Paging Transmitter Fire Tek Pro Paging System 40 Character Alpha Numeric Pager Fire Tek Pro Paging System 40 Character Alpha Numeric Pager Fire Tek Pro Paging System 1/2 wave dipole antenna Fire Tek Pro Paging System 1/2 wave dipole antenna Fire Tek Pro Paging System Wall mounting folded dipole antenna Fire Tek Pro Paging System Wall mounting folded dipole antenna Fire Tek Pro Paging System Pole mounting folded dipole antenna Fire Tek Pro Paging System Pole mounting folded dipole antenna Fire Tek Pro Paging System 5 metre antenna feeder cable Fire Tek Pro Paging System 5 metre antenna feeder cable Fire Tek Pro Paging System 10 metre antenna feeder cable Fire Tek Pro Paging System 10 metre antenna feeder cable MX2-210 Two loop c/w LEDs shallow housing MX2-211 Two loop c/w LEDs deep housing MX2-XB0 Expansion Box Shallow MX2-XB1 Expansion Box Deep MX2-FB Panel/repeater flush mounting bezel MX2-FBX Expansion box flush mounting bezel MZX16R 16 Zone Repeater (mains powered) MZX32R 32 Zone Repeater (mains powered) MZXDR 240 Zone Repeater No Zonal Led’s (24VDC powered) MZX64DR 64 Zone Repeater (24 VDC powered) PSU A17 17Ahr 5A Addressable expansion PSU PSU A38 38Ahr 5A Addressable expansion PSU MZX253 2 to 4 loop 64 Zone Fire Controller (CPU801) T2000 Two To Eight Loop Marine Panel (Stainless steel enclosure) T2000R Marine Repeater with 240 Vac PSU (Stainless steel) T2000B Battery Box (Stainless steel enclosure) T2000R Marine Repeater 24 Vdc (Stainless steel) T2000 BM Battery Box (Mild steel enclosure) T2000 RMRS Door Stay Kit T2000 RMRS Door Stay Kit T2000 Standard Two to Eight Loop Marine Panel (Mild steel) T2000R Marine Repeater with 240Vac PSU (Mild steel) T2000R Marine Repeater 24Vdc (Mild steel) T2000CV 3 loop marine panel (mild steel back box) T2000R CV Marine Indicating Repeater 24Vdc (Mild steel) Dual power supply mounting kit Ancillary/expansion board mounting kit T2000 XLM 8-Loop Mounting Kit MX2 PSU830 Dual PSU Kit PTM800 Power Terminal Module PSU 830 T2000/T2000R Conversion Kit PSU 830 T2000/T2000R Conversion Kit PSU 830 T2000 120VAC Kit PSU 830 T2000 120VAC Kit BFP801Blank Half Module - Grey Overlay DIN Rail Mounting Kit DIN Rail Mounting Kit DIN Rail Mounting Kit DIN Rail Mounting Kit DIN Rail Mounting Kit Standard MX Expansion backbox and chassis plate MZX250 17Ah Battery Clamp Deep MX Expansion backbox and chassis plate D800 IP55 Ancillary Housing D800 IP55 Ancillary Housing Chapter 12 Page 16
Fire Catalogue
2
2
2
2
4
2
3
2
3
2
3
2
3
2
3
2
3
2
3
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
3
3
2
2
2
2
2
7
6
27
24
4
26
10
26
10
26
10
26
10
26
10
26
10
26
10
4
4
4
4
4
4
2
2
2
2
3
3
2
9
10
9
10
9
9
10
9
10
10
9
10
79
4
9
16
16
9
10
9
10
79
45
66
69
39
42
79
2
79
45
49
04/17
Chapter 12 - Index
Product Code Description Chapter Page
557.201.410 557.201.410 557.201.410 557.201.410 557.201.410 557.201.501 557.201.502 557.201.502 557.201.503 557.201.505 557.201.508 557.201.508 557.201.508 557.201.510 557.201.511 557.201.512 557.201.513 557.201.516 557.201.518 557.201.519 557.201.520 557.202.000 557.202.000 557.202.001 557.202.001 557.202.003 557.202.004 557.202.006 557.202.006 557.202.006 557.202.007 557.202.007 557.202.007 557.202.007 557.202.008 557.202.008 557.202.012 557.202.013 557.202.013 557.202.019 557.202.019 557.202.020 557.202.020 557.202.020 557.202.021 557.202.021 557.202.021 557.202.022 557.202.022 557.202.022 557.202.024 557.202.024 557.202.027 557.202.028 557.202.028 557.202.030 557.202.031 557.202.044 557.202.046 557.202.050 557.202.073 557.202.080 04/17
IP66 Housing for Quad I/O Modules 2 IP66 Housing for Fire-Cryer® Plus Extinguishing PCB 2 IP66 Housing for Fire-Cryer® Plus Extinguishing PCB 2 IP66 Housing for Fire-Cryer® Plus Extinguishing PCB 3 IP66 Housing for Fire-Cryer® Plus Extinguishing PCB 3 Semi-Flush Bezel for MZX250/251/252/253/254/MZX32R 2 Flush Bezel for MZX125/MZX16R/MZXC+ 4/8/16 Zone Panel & Repeater 2 Flush Bezel for MZX125/MZX16R/MZXC+ 4/8/16 Zone Panel & Repeater 3 Accessory mounting plate for std modules, IOB800 & LIM800 2 MZX251/ 252 38Ah Battery Clamp 2 MZX/MZXC/MZXE Spare Key Set 2 MZX/MZXC/MZXE Spare Key Set 3 MZX/MZXC/MZXE Spare Key Set 3 Rack mount kit for MZX 125 2 Rack mount kit for MZX 250 2 Rack Mount Kit for MZX 251/252/253/254 2 Document Holder attachment (used with ANC125/250/251) 2 PSU monitor kit (includes MIM800) 2 M520 Anc Fitting Kit – req’d for older M520 modules 2 Comms Interface mounting plate (MZX250/251/252/253/254 only) 2 MZX251/252/253/254 24 Ah Battery Clamp 2 FIM801 field interface module with one MX loop driver 2 FIM801 field interface module with one MX loop driver 2 FIM802 field interface module with two MX loop drivers 2 FIM802 field interface module with two MX loop drivers 2 PSM800 Power Supply Unit 2 LBM800 Loop Booster Module PCB 2 IOB800 (8in/8out) expansion board 2 IOB800 (8in/8out) expansion board 2 IOB800 (8in/8out) expansion board 2 XLM800 2-Loop Expansion Card 2 XLM800 2-Loop Expansion Card 2 XLM800 2-Loop Expansion Card 2 XLM800 2-Loop Expansion Card 2 FIM801CV for Marine T2000CV 2 FIM801CV for Marine T2000CV 2 MPM800 multi-purpose interface module 2 OCM800 with Inserts - English 2 OCM800 with Inserts - English 2 ODM800 Operator Display Module 2 ODM800 Operator Display Module 2 COM820 20-Way Status/Command Module 2 COM820 20-Way Status/Command Module 2 COM820 20-Way Status/Command Module 2 ANN840 40-Way Alarm/Fault LED Module 2 ANN840 40-Way Alarm/Fault LED Module 2 ANN840 40-Way Alarm/Fault LED Module 2 ANN880 80-Way Alarm LED Module 2 ANN880 80-Way Alarm LED Module 2 ANN880 80-Way Alarm LED Module 2 PRN800 Printer c/w front cover module 2 PRN800 Printer c/w front cover module 2 APM800 addressable power supply monitor 2 RSM800 PSU Module (24 Vdc) 2 RSM800 PSU Module (24 Vdc) 2 PSU 830 Panel Fixing Conversion Kit 2 PSU 830 Small Chassis Plate Conversion Kit 2 PSU 830K Power Expansion Kit 2 MX CCU3/C-MXMB MX to MOD Bus Interface 4 PSM800 Temp Sensor Accessory Kit 2 2 Loop expansion kit for MZX253 (includes XLM loop card) 2 TLI800EN MXNet network card & cable
2 Fire Catalogue
46
66
69
39
42
2
2
4
2
2
79
48
48
2
2
2
3
3
3
2
2
15
79
15
79
79
79
5
7
21
4
5
14
79
15
79
20
17
79
18
79
4
19
79
4
19
79
4
19
79
4
24
42
7
79
16
16
16
6
79
2
4
Chapter 12 Page 17
Chapter 12 - Index
Product Code Description Chapter Page
557.202.080 TLI800EN MXNet network card & cable 2 5
557.202.080 TLI800EN MXNet network card & cable 4 4
557.202.081 FOM800 Fibre Optic Module 4 4
557.202.090 RS800 WebWay IP/ GPRS 2 23
557.202.091 RS800 WebWay IP for remote IP services only 2 23
557.202.093 Enclosure for RS-800 2 23
557.202.100 FB800 fuse board (15 way) 2 21
557.202.113 PSB to FIM Cable 2 79
557.202.117 Serial printer cable for MPM800 or FIM800 2 20
557.202.117 Serial printer cable for MPM800 or FIM800 2 24
557.202.118 MXConsys Download lead 2 75
557.202.120 MX-Minerva Bridge Kit (17AH) 4 7
557.202.121 MX Minerva Bridge Kit (38AH) 47
557.202.123 MX Bridge CCU3/C-MX Bridge 4 6
557.202.127 VDR Cable For a Standalone panel, Com port 3 2 9
557.202.128 VDR Cable for a networked system, Com port 1 2 9
557.202.128 VDR Cable for a networked system, Com port 1 2
24
96160183
UC-8112-LX BACnet interface 2
26
557.202.200 DCM800 MX2 Display Control Module (without LCD assy) 2
4
557.202.200 DCM800 MX2 Display Control Module (without LCD assy) 2
79
557.202.204 MX2 Battery housing 2
4
557.202.205 MX2 Battery and Expansion Housing (65 AH) 2
4
557.202.206 MX2 expansion aperture installation kit 2
4
557.202.206 MX2 expansion aperture installation kit 2
79
557.202.208 MX2 8 Loop Expansion Kit 2
4
557.202.208 MX2 8 Loop Expansion kit 2
79
557.202.209 MX2 LCD Assembly (Spare) 2
4
557.202.209 MX2 LCD Assembly (Spare) 2
79
557.202.210 PSU830 Power Supply Module 2
16
557.202.210 PSU830 Power Supply Module 2
79
557.202.298 MX Service Case 2
78
557.202.601 DCM816 16 zone display PCB for MZX125 2
79
557.202.602 DCM832 32 zone display PCB for MZX250/251/252 2
79
557.202.608 PMM800 Power monitor module 2
79
557.202.609 BAQ60T24 2.5A MZX PSU 2
79
557.202.610 BAQ140T24 5A MZX PSU 2
79
557.202.611 PMM805 Power Monitor Module - 5 V Repeater 2
79
557.202.612 PMM840 Power Monitor Module - 40 V Loop Power 2
79
557.202.613 DCM864R Spare Display / Control PCB for MZX253 2
79
557.202.614 DCM8240 240 zone display PCB for MZX254 and MZXDR 2
79
557.202.622 ANC125 Ancillary Housing (Small - matches MZX125) 2
3
557.202.623 ANC250 Ancillary Housing (Large – matches MZX250) 2
3
557.202.624 ANC251 Ancillary Housing (Deep – matches MZX251/252/253/254) 2 3
557.202.625 ANC125-A Ancillary Housing, One Aperture (Small) 2
3
557.202.626 ANC250-A Ancillary Housing, Two Aperture (Large) 2
3
557.202.627 ANC251-A Ancillary Housing, Two Aperture (Deep) 2
3
557.202.810
CPU801 Central Processor Unit
557.203.004 MXRemote Dongle and license (USB) 2
75
557.203.005 Set of spare keys for MX Panel (AL102) 2
79
557.203.021 MXLoop tester with EUROPEAN/UK MAINS to IEC CABLE 2
78
557.203.022 MX Loop Tester ECM Prog Null Modem 2
78
557.203.022 MX Loop Tester ECM Prog Null Modem 2
79
557.203.023 MX Loop Tester Carry Bag 2
78
557.203.023 MX Loop Tester Carry Bag 2
79
557.203.024 MX Loop Tester PSU 2
78
557.203.024 MX Loop Tester PSU 2
79
557.203.026 MX Loop Tester Battery Lead Set 2
78
557.203.026 MX Loop Tester Battery Lead Set 2
79
557.203.033
MXConsys Dongle and license (USB) 2
75
557.301.014 Spare Paper Roll (pk of 5) 2
24
557.800.057 DDM800 Detector Removal End of Line Resistor (pack of 10) 2
43
558.004.010 ELM 24 V 4A Door Holder PSU 6
3
558.004.011 ELM24TSM 4 Amp 24 VDC Addressable Door Holder PSU 2
48
558.004.020 24V 5 Amp Power Supply Unit with housing for 17A/H Batteries 6
2
Chapter 12 Page 18
Fire Catalogue
04/17
Chapter 12 - Index
Product Code Description 567.005.004 567.007.008 567.007.009 568.001.002 568.001.018 568.800.003 568.800.004 568.800.033 568.800.034 569.001.007 576.501.001 576.501.001 576.501.002 576.501.002 576.501.003 576.501.003 576.501.012 576.501.012 576.501.030 576.501.031 576.501.039.A 576.501.039.A 576.501.039.T 576.501.039.T 576.501.040.A 576.501.040.A 576.501.044.A 576.501.044.A 576.501.044.T 576.501.044.T 576.501.045 576.501.045 576.501.047 576.501.047 576.501.052 576.501.052 576.501.060 576.501.060 576.501.061 576.501.061 576.501.062 576.501.062 576.501.063 576.501.063 576.501.131 576.501.131 576.501.132 576.501.132 576.501.133 576.501.133 576.501.134 576.501.134 576.501.135 576.501.135 576.501.141 576.501.141 Relay 5010 Alarm Relay 240 Vac MK4 Alarm Relay 24 Vdc MK4 Relay 5010 PCB MC600 Relay base RIM800 relay interface module HVR800 high voltage relay RIM800 Module c/w Front Cover HVR800 in isolated D800 housing Cradle relay and retaining clip 2 C/O 26 V 700 ohm coil 5 amp YO3 Yodalarm sounder 3” 24 Vdc 100dB @ 1 Mtr YO3 Yodalarm sounder 3” 24 Vdc 100dB @ 1 Mtr YO5 Yodalarm sounder 5” 24 Vdc 106dB @ 1 Mtr YO5 Yodalarm sounder 5” 24 Vdc 106dB @ 1 Mtr YO8 Yodalarm sounder 8” 24 Vdc 112dB @ 1 Mtr YO8 Yodalarm sounder 8” 24 Vdc 112dB @ 1 Mtr Easy AV strobe for Banshee Sounders Easy AV strobe for Banshee Sounders Squashni Squashni electronic sounder white 24Vdc Blank cover plate white for Squashni electronic sounder MBF-6EV ADT Branded Motorised Bell MBF-6EV ADT Branded Motorised Bell MBF-6EV Thorn Branded Motorised Bell MBF-6EV Thorn Branded Motorised Bell MBF-8EV ADT Branded Motorised Bell MBF-8EV ADT Branded Motorised Bell MBA-8EV ADT Branded Motorised Bell MBA-8EV ADT Branded Motorised Bell MBA-8EV Thorn Branded Motorised Bell MBA-8EV Thorn Branded Motorised Bell BBX4 (2) W/P Backbox for MBA-8 Bell BBX4 (2) W/P Backbox for MBA-8 Bell Banshee/Xenon bracket Banshee/Xenon bracket Mini Fire-Cryer® Plus, voice enhanced base sndr cable spacing
Mini Fire-Cryer® Plus, voice enhanced base sndr cable spacing
Banshee Excel Sounder, red, IP45 Banshee Excel Sounder, red, IP45 Banshee Excel Sounder, white, IP45 Banshee Excel Sounder, white, IP45 Banshee Excel Sounder, red, IP66 Banshee Excel Sounder, red, IP66 Banshee Excel Lite, red sounder, red xenon beacon, IP45 Banshee Excel Lite, red sounder, red xenon beacon, IP45 Fire-Cryer® Plus, red wall mounted, shallow base, red beacon Fire-Cryer® Plus, red wall mounted, shallow base, red beacon Fire-Cryer® Plus, red wall mounted, deep base, red beacon Fire-Cryer® Plus, red wall mounted, deep base, red beacon Fire-Cryer® Plus, red, wall mounted, shallow base Fire-Cryer® Plus, red, wall mounted, shallow base Fire-Cryer® Plus, red, wall mounted, deep base Fire-Cryer® Plus, red, wall mounted, deep base Fire-Cryer® Plus (for use with Gas Extinguishant Systems) Fire-Cryer® Plus (for use with Gas Extinguishant Systems) Fire-Cryer® Plus, white wall mounted, shallow base, red beacon
Fire-Cryer® Plus, white wall mounted, shallow base, red beacon
04/17
Chapter Fire Catalogue
6
6
6
6
3
2
2
2
2
6
2
3
2
3
2
3
2
3
3
3
2
3
2
3
2
3
2
3
2
3
2
3
2
3
ring 2
ring 3
2
3
2
3
2
3
2
3
2
3
2
3
2
3
2
3
2
3
2
3
Page
4
4
4
4
21
44
44
44
44
4
63
35
63
35
63
35
70
43
37
37
60
32
60
32
60
32
60
32
60
32
60
32
63
35
69
42
62
34
62
34
62
34
62
34
69
42
69
42
69
42
69
42
69
42
69
42
Chapter 12 Page 19
Chapter 12 - Index
Product Code Description 576.501.142 576.501.142 576.501.151 576.501.151 576.501.161 576.501.161 576.501.171 576.501.171 576.501.171 576.501.171 576.501.172 576.501.172 576.501.172 576.501.172 576.501.173 576.501.173 576.501.173 576.501.173 576.501.181 576.501.181 576.501.181 576.501.181 576.501.182 576.501.182 576.501.182 576.501.182 576.501.191 576.501.191
576.501.200 576.501.200 576.501.201 576.501.201 576.501.202 576.501.202 576.501.203 576.501.203 576.501.204 576.501.205 576.501.220 576.501.220 576.501.221 576.501.221 576.501.222 576.501.222 576.501.223 576.501.223 576.501.224 576.501.224 576.501.227 576.501.227 576.501.230 576.501.230 576.501.232 576.501.242 576.501.243 576.501.250 576.501.250 576.501.251 576.501.255 576.501.255 576.501.255 Fire-Cryer® Plus, white, wall mounted, shallow base 2
Fire-Cryer® Plus, white, wall mounted, shallow base 3
Midi Fire-Cryer® Plus, c/w back box, red 2
Midi Fire-Cryer® Plus, c/w back box, red 3
Mini Fire-Cryer® Plus, base mounted, white, c/w cover 2
Mini Fire-Cryer® Plus, base mounted, white, c/w cover 3
Fire-Cryer® Plus Multi Message PCB 2
Fire-Cryer® Plus Multi Message PCB 2
Fire-Cryer® Plus Multi Message PCB 3
Fire-Cryer® Plus Multi Message PCB 3
Fire-Cryer® Plus Zone Extension PCB 2
Fire-Cryer® Plus Zone Extension PCB 2
Fire-Cryer® Plus Zone Extension PCB 3
Fire-Cryer® Plus Zone Extension PCB 3
Fire-Cryer® Plus Extinguishing PCB 2
Fire-Cryer® Plus Extinguishing PCB 2
Fire-Cryer® Plus Extinguishing PCB 3
Fire-Cryer® Plus Extinguishing PCB 3
Voice Message Controller c/w Multi Message PCB and 2.5A PSU 2
Voice Message Controller c/w Multi Message PCB and 2.5A PSU 2
Voice Message Controller c/w Multi Message PCB and 2.5A PSU 3
Voice Message Controller c/w Multi Message PCB and 2.5A PSU 3
Voice Message Controller c/w Multi Message PCB and 5.25A PSU 2
Voice Message Controller c/w Multi Message PCB and 5.25A PSU 2
Voice Message Controller c/w Multi Message PCB and 5.25A PSU 3
Voice Message Controller c/w Multi Message PCB and 5.25A PSU 3
Fire-Cryer® Plus Demo Unit 2
Fire-Cryer® Plus Demo Unit 3
SY/R Low Power Red Symphoni Sounder (3 tone) 2
SY/R Low Power Red Symphoni Sounder (3 tone) 3
SY/W Low Power White Symphoni Sounder (3 tone) 2
SY/W Low Power White Symphoni Sounder (3 tone) 3
SYHO/R High Output Red Symphoni Sounder (32 tone) 2
SYHO/R High Output Red Symphoni Sounder (32 tone) 3
SYHO/W High Output White Symphoni Sounder (32 tone) 2
SYHO/W High Output White Symphoni Sounder (32 tone) 3
Symphoni 2 Wire Sounder (Red) 3
Symphoni 2 Wire Sounder (White) 3
ROSHNI Sounder c/w shallow base - RED 2
ROSHNI Sounder c/w shallow base - RED 3
ROSHNI Sounder c/w shallow base - WHITE 2
ROSHNI Sounder c/w shallow base - WHITE 3
ROSHNI/Flashni Deep Base - Red 2
ROSHNI/Flashni Deep Base - Red 3
ROSHNI/Flashni Deep Base - White 2
ROSHNI/Flashni Deep Base - White 3
Flashni complete with shallow base & tone switch 2
Flashni complete with shallow base & tone switch 3
Flashni c/w deep base, tone switch & separate sndr/strobe operation 2 Flashni c/w deep base, tone switch & separate sndr/strobe operation 3 Solista LED Beacon (Red) 2
Solista LED Beacon (Red) 3
Solex 10 cd Beacon with red lens and white base 3
Multi Tone Askari Compact bedroom sounder - white 3
Multi Tone Askari Compact bedroom sounder - red 3
Squashni G3/AV Sounder Beacon 2
Squashni G3/AV Sounder Beacon 3
Squashni G3/AV 2 Wire Sounder Beacon 3
Squashni G3/AV Blanking Cap – Pack of 5 2
Squashni G3/AV Blanking Cap – Pack of 5 3
Squashni G3/AV Blanking Cap – Pack of 5 3
Chapter 12 Page 20
Chapter Fire Catalogue
Page
69
42
69
42
69
42
66
69
39
42
66
69
39
42
66
69
39
42
66
69
39
42
66
69
39
42
69
42
64
36
64
36
64
36
64
36
36
36
64
36
64
36
64
36
64
36
72
45
72
45
70
43
44
37
37
72
46
47
72
46
47
04/17
Chapter 12 - Index
Product Code Description Chapter Page
576.501.405 576.501.405 576.501.407 576.501.407 576.501.408 576.501.408 577.001.023 577.001.033 577.001.035 577.001.036 577.001.037 577.001.038 577.002.002 577.002.003 577.002.007 577.002.008 577.025.032 577.025.032 577.800.005 577.800.006 577.800.011 577.800.035 577.800.036 577.800.041 577.800.056 577.800.066 577.800.067 592.001.010 592.001.012 592.001.014 592.001.016 592.001.018 599.001.012 599.001.012 599.001.029 599.001.029 599.047.005 599.047.006 599.047.007 599.047.008 599.047.011 599.047.012 599.047.013 599.047.014 599.047.015 599.047.016 599.047.018 599.047.019 599.047.020 599.047.021 599.047.022 599.047.023 599.047.024 599.047.030 599.047.031 599.047.032 599.047.033 599.048.001 599.048.002 599.048.003 MED 6” Red 24Vdc Motorised bell, “Fire” text with Thorn Branding MED 6” Red 24Vdc Motorised bell, “Fire” text with Thorn Branding MED 6” 24Vdc Electronic bell, weatherproof IP33C MED 6” 24Vdc Electronic bell, weatherproof IP33C MED 6” 24Vdc Electronic bell - red IP21C MED 6” 24Vdc Electronic bell - red IP21C SB520 Sounder Booster Module SB520 Sounder Booster Module c/w Front Cover 601SB Conventional Sounder Base 602SB 2 Wire Line Powered Sounder Base 601SBD Conventional Diode Sounder Base 602SBD 2 Wire Line Powered Diode Sounder Base MX Paging System Type A alarm pager MX Paging System Type A maintenance pager MX Paging System Pager aerial 60 db gain MX Paging System Optional feeder cable (10m long) DPS1200 Probe tube stainless steel 1200mm and exhaust DPS1200 Probe tube Stainless Steel 1200mm and exhaust SNM800 sounder notification module DDM800 Universal Fire and Gas Module LPS800 Loop Powered Sounder module SNM800 sounder notification module c/w Front cover DDM800 Universal Fire and Gas Module c/w front cover LPS800 Module c/w front cover DDM800 Universal Fire and Gas Module housed in IP55 Enclosure DDM800 Fire & Gas Detector Module in EExd Housing MIM800 Input Module in EExd Housing T110 PP3 Battery and Charger Kit T110 Test Source T210+ Adaptor required for the T210+ T210+ Test Source T110 Adaptor for series 600 and 800 flame detectors Lamp 28 V 60 mA used on T525 Lamp 28 V 60 mA used on T525 Spare bulb for E1/E3 24 V-5W Spare bulb for E1/E3 24 V-5W Address Labels 1 - 127 Loop E - Grey Address Labels 1 - 127 Loop F - Blue Address Labels 1 - 127 Loop G - Orange Address Labels 1 - 127 Loop H - Red Zone labels - Zones 1 - 16 Zone labels - Zones 17 - 32 Zone labels - Zones 33 - 48 Zone labels - Zones 49 - 64 Zone labels - Zones 65 - 80 Zone labels - Zones 81 - 100 Zone labels - Zones 101 - 120 Zone labels - Zones 121 - 140 Zone labels - Zones 141 - 160 Zone labels - Zones 161 - 180 Zone labels - Zones 181 - 200 Zone labels - Zones 201 - 220 Zone labels - Zones 221 - 240 Address Labels 1 - 250 Loop A - White Address Labels 1 - 250 Loop B - Yellow Address Labels 1 - 250 Loop C - Purple Address Labels 1 - 250 Loop D - Green DÄTWYLER Lifeline Fire Resistant P Clips 50 P34 Red DÄTWYLER Lifeline Fire Resistant P Clips 50 P34 White DÄTWYLER Lifeline Fire Resistant P Clips 50 P37 Red 2
3
2
3
2
3
2
2
3
3
3
3
2
2
2
2
2
3
2
2
2
2
2
2
2
9
9
5
5
5
5
5
3
3
3
3
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
6
6
6
61
33
61
33
61
33
44
44
21
21
21
21
27
27
27
27
40
23
44
43
44
44
43
44
43
13
12
4
4
4
4
4
8
48
8
48
39
39
39
39
39
39
39
39
39
39
39
39
39
39
39
39
39
39
39
39
39
5
5
5
04/17
Fire Catalogue
Chapter 12 Page 21
Chapter 12 - Index
Product Code Description 599.048.005 DÄTWYLER Lifeline Fire Resistant P Clips 50 P40 Red 599.048.009 DÄTWYLER Lifeline Fire Resistant Glands 10 NG1 Red 599.048.010 DÄTWYLER Lifeline Fire Resistant Glands 10 NG1 White 599.048.020 DÄTWYLER Lifeline cable 2 + earth 1 mm Red 599.048.022 DÄTWYLER Lifeline cable 2 + earth 1.5 mm Red 599.048.023 DÄTWYLER Lifeline cable 2 + earth 1.5 mm White 599.048.024 DÄTWYLER Lifeline cable 2 + earth 2.5 mm Red 599.048.032 DÄTWYLER Lifeline cable 4 + earth 1 mm Red 599.048.034 DÄTWYLER Lifeline cable 4 + earth 1.5 mm Red 599.048.035 DÄTWYLER Lifeline cable 4 + earth 1.5 mm White 599.048.036 DÄTWYLER Lifeline cable 4 + earth 2.5 mm Red 609.001.015 24VDC double pole C/O relay 2K ohm coil, 2 Amps @ 30VDC 90-107 Red M141 spacer for red CP200/800 KAC callpoints Red M141 spacer for red CP200/800 KAC callpoints BAQ35T-24 MZX-c CONVENTIONAL PANEL POWER SUPPLY CGUK-01 Consultants Guide DB3BDGD048N2BNR
DB3B Flameproof Horn Sounder
G13801N-A Elmdene 12 V 1 A PSU in Housing OSE-HPW OSID Emitter High Power, Wired OSE-SP OSID Emitter Standard Power OSE-SPW OSID Emitter Standard Power, Wired OSI-10 OSID Imager 7o coverage OSI-45 OSID Imager 38o coverage OSI-90 OSID Imager 80o coverage OSID-WG Wire Guard for OSID Imager 8x Emitter OSID-EHI OSID Imager Environmental Housing OSID-EHE OSID Emitter Environmental Housing OSP-001 OSID USB to FTDI Serial P.C. Interface Cable
OSID-INST OSID Installation Kit PS-1212 12 Volt 1.2 Ampere hour rechargeable sealed lead acid battery PS-12120 12 Volt 12.0 Ampere hour rechargeable sealed lead acid battery PS-12170 12 Volt 17.0 Ampere hour rechargeable sealed lead acid battery PS-1221 12 Volt 2.1 Ampere hour rechargeable sealed lead acid battery PS-12260 12 Volt 26.0 Ampere hour rechargeable sealed lead acid battery PS-1230 12 Volt 3.0 Ampere hour rechargeable sealed lead acid battery PS-12380 12 Volt 38.0 Ampere hour rechargeable sealed lead acid battery PS-1242 12 Volt 4.5 Ampere hour rechargeable sealed lead acid battery PS-12650 12 Volt 65.0 Ampere hour rechargeable sealed lead acid battery PS-1270 12 Volt 7.0 Ampere hour rechargeable sealed lead acid battery PS-6100 6 Volt 10.0 Ampere hour rechargeable sealed lead acid battery ROSHRDSR ROSHNI Sounder c/w deep base - RED ROSHRDSR ROSHNI Sounder c/w deep base - RED RU1-24 Relay Boxed 24 Vdc Coil 5A contacts TCD-1 MZX Interactive Training CD UDS1100 Lantronics Device Server LAN VEU-A00 VESDA-E VEU with LED’s
VEU-A10 VESDA-E VEU with 3.5” Display
VSP-960 Mounting bracket (optional) Spare Parts
VSP-962 VESDA-E Filter
VSP-962-20 VESDA-E Filter - 20 pieces
VSP-963 VESDA-E Aspirator
VSP-964 VESDA-E Smoke Detection Chamber
VSP-965
VESDA-E Sampling Module
VLQ-100 VESDA VLQ Aspirated Smoke Detector
VSP-890 Surface Mount Kit
VSP-891 Flush Mount Kit
VSP-892 Replacement Filter
VSP-892-20 Replacement Filter (20 pieces)
VSP-893 Pipe Kit (Metric)
VSP-893-US Pipe Kit (Imperial)
VKT-100 VESDA VLQ-100 demo kit (consisting of
VLQ-100, pre-drilled pipes and power
supply fitted in a carry case)
VKT-301 OSID Demo Kit Chapter 12 Page 22
Fire Catalogue
Chapter Page
6
6
6
6
6
6
6
6
6
6
6
6
2
3
3
10 5
5
5
5
5
5
5
5
5
5
5
4
53
27
48
5
9
18
2
7
7
13
7
13
7
13
7
13
7
13
7
13
7
13
7
13
7
13
7
13
7
13
6
1
6
1
6
1
6
1
6
1
6
1
6
1
6
1
6
1
6
1
6
1
2
64
3
36
6
4
2
74
2
75
7
11
7
11
7
11
7
11
7
11
7
11
7
11
711
7
11
7
11
7
11
7
11
7
11
7
11
7
11
7
7
11
13
04/17
European Distribution Centre - Echt Holland
(Warehousing/Distribution/Purchasing
Customer Service/Call Centre Helpdesk)
Voltaweg 20
6101 XK
Echt
Holland
Phone: +31 475 371 666
Fax:
+31 475 371 660
E-mail: [email protected]
European TSP Technical Call Centre
Toll Free: 0800 CALL TYCO or
0800 22558986
9:00 AM to 5:00 PM EET, CET & GMT
UK Only: 08701 238787
UK Distribution Centre
(Warehousing/Distribution/Purchasing)
Dunhams Lane
Letchworth
Hertfordshire
SG6 1BE
Phone: +44 (0) 1462 667 700
Fax:
+44 (0) 1462 667 777
E-mail: [email protected]
www.zettlerfire.com
© 2017 Tyco Integrated Fire & Security PMC001 Issue 10.5 - 05/17
The right is reserved to modify or withdraw any product or service without notice
Was this manual useful for you? yes no
Thank you for your participation!

* Your assessment is very important for improving the work of artificial intelligence, which forms the content of this project

Download PDF

advertisement