m alco theatres: ow ensboro 12 2700 calum et trace ow ensboro, ky

m alco theatres: ow ensboro 12 2700 calum et trace ow ensboro, ky
2
3
4
5
6
N
O
T
FO
R
C
O
N
ST
R
U
C
TI
O
N
1
E
COMPRESSED BATT INSULATION TO
CLOSE DECK FLUTES @ HEAD TYP. EACH
SIDE OF DEMISING WALLS TO SEAL ALL
INTERFACES & AT ANY STRUCTURAL
PENETRATIONS
STRUCTURE WHERE OCCURS
METAL STUD FRAMING @ 16"
O.C.
ROOF INSULATION ON METAL DECKING
1/2" GAP
TYP
CAULK EACH LAYER OF ENTIRE PERIMETER
WALL WITH NON-HARDENING ACOUSTIC CAULK
STEEL RUNNER TRACK WITH BUILT-IN
SHADOWLINE - EQUAL TO "FIRE TRACK
CAVITY SHADOWLINE" BY FIRE TRACK
CORPORATION OR APPROVED EQUAL - TYP.
EACH SIDE
ROOF INSULATION
ROOF DECK
VARIES W/
DEFLECTION
COMPRESSED ACOUSTIC BATT INSULATION TO CLOSE DECK
FLUTES @ HEAD TYP. SEAL ALL INTERFACES & AT ANY
STRUCTURAL PENETRATIONS
FIRE SEALANT
FILL ALL VOID SPACES WITH BATT
INSULATION
8 3/8"
GYP TOP CUT TO PROFILE OF DECK
STRUCTURAL MEMBER WITHIN STUD WIDTH
USE FURRING STUDS OR CHANNELS FROM
MEMBER TO SUPPORT GYP
NEVER ATTACHED OUTER
LAYERS OF GYP. TO INNER WALL
LAYERS
CUT INSULATION AT EACH BRACE (DO
NOT COMPRESS INSULATION)
DRAWINGS & SPECIFICATIONS REMAIN THE
PROPERTY OF THE DESIGN PROFESSIONAL.
COPIES OF THE DRAWINGS & SPECIFICATIONS
RETAINED BY THE CLIENT MAY BE UTILIZED ONLY
FOR THEIR USE & FOR OCCUPYING THE PROJECT
FOR WHICH THEY WERE PREPARED & NOT FOR
CONSTRUCTION OF ANY OTHER PROJECT
LATERAL BRACING PER
MANUFACTURER (6'-0" O.C. MAX.)
POSI CLIPS FROM FIRE TRAK TO VERT STUD
(FIRE TRAK CORP)
IF REQUIRED TO CATCH SLIP
TRACK GC TO WELD PLATE TO
BEAM FLANGE
GYP OVERLAP TO
NO STRUCTURE AT WALL HEAD
BRIDGING INSTALLED AT STUD
HEAD PER MANUFACTURER'S
WRITTEN RECOMMENDATIONS
(12" MAX FROM TOP)
LAY-IN ACOUSTICAL CEILING SYSTEM,
REFERENCE RCP
INSTALLER TO CONFIRM SPACING & GAGE REQUIRED
FOR STUD WITH ARCHITECT PRIOR TO INSTALL.
FIRE TRAK FIXED TO STRUCTURE (FIRE TRAK CORP)
INSTALL PER MANUFACTURERS WRITTEN INSTRUCTIONS
INCLUDING SLIP CONNECTION (POSI CLIP) TO VERTICAL
WALL STUDS. SIZE TRAKS TO MEET DEFLECTION CRITERIA
AS WELL AS LAYERS OF GYP TO CLOSE AT TOP SYSTEM
HW-D-1020 OR EQUAL
`Z` CLIP TO ALLOW CONNECTION OF TRAK TO DECK
ROOF INSULATION
ROOF DECK
COMPRESSED ACOUSTIC BATT INSULATION TO CLOSE DECK
FLUTES @ HEAD TYP. SEAL ALL INTERFACES & AT ANY
STRUCTURAL PENETRATIONS
(3) LAYERS OF 5/8" GYP.
BOARD ON 6" METAL
STUD FRAMING
C
DRAPERY PER ELEVATIONS
DEFLECTION NOTES:
1. USE "FIRE TRAK CAVITY SHADOWLINE" OR EQUAL. (ANGLES MAY BE USED)
2. TRACKS OR ANGLES TO SUPPORT STUDS AT ROOF - 12GA. MIN.
3. VERTICAL LEGS SHALL BE 2" LONGER THAN THE DEFLECTION, TYP.
FACE LAYER TO 1/2" MAX. OF ALL
EDGES OF ROOF DECK
CORRUGATIONS (4" MIN. HT. PIECE)
E.S.
(3) LAYERS OF 5/8" GYP.
BOARD ON 6" METAL
STUD FRAMING
POSI CLIPS FROM FIRE TRAK
TO VERT STUD
(FIRE TRAK CORP)
AIR GAP PER WALL TYPE
BRIDGING INSTALLED AT STUD
HEAD PER MANUFACTURER'S
WRITTEN RECOMMENDATIONS
(12" MAX FROM TOP)
GAP PER STRUCTURAL
DRAWING & DEFLECTION
REQUIREMENTS FOR
STRUCTURE
ACOUSTICAL BATT
INSULATION (ONE SIDE
ONLY)
BASE LAYER TO
UNDERSIDE OF ROOF
DECK FLUTES
ROOF DECK
FIRE TRAK FIXED TO STRUCTURE (FIRE TRAK CORP)
INSTALL PER MANUFACTURERS WRITTEN INSTRUCTIONS
INCLUDING SLIP CONNECTION (POSI CLIP) TO VERTICAL
WALL STUDS. SISE TRAKS TO MEET DEFLECTION CRITERIA
AS WELL AS LAYERS OF GYP TO CLOSE AT TOP SYSTEM
HW-D-1020 OR EQUAL
FIRE SEALANT
RE: RCP
INSTALLER TO CONFIRM SPACING & GAGE REQUIRED
FOR STUD WITH ARCHITECT PRIOR TO INSTALL.
NO STRUCTURE AT WALL HEAD
ACOUSTICAL CAULK
E.S. (FIRE CAULK
RATED WALLS)
BID SET
1' - 0"
BATT INSULATION FIRE SAFING AT
RATED WALLS (6" WIDE MIN.)
FIRE TRAK SHADOWLINE
OR EQUAL
PER STRUCT
2700 CALUMET TRACE
OWENSBORO, KY
RE: RCP
MALCO THEATRES: OWENSBORO 12
1" x 0.15" GA. METAL STRAPPING
ATTACHED BETWEEN LATERAL
BRACING TO SUPPORT INSULATION
(EA. SIDE) AS REQUIRED
EXCEED DESIGNED DEFLECTION TRAVEL TYP
D
1100 Main Street
Suite 2200
Kansas City, Missouri
64105
Phone : 816-842-7552
Fax :
816-842-1302
POUR STOP -1" OFF FINISH GYP FACE
1"
6" ACOUSTIC BATT INSULATION
THIS DETAIL APPLIES TO ALL WALLS AROUND THEATRES
AT WALLS PERPENDICULAR TO DECK CORRUGATIONS.
FACE LAYER TO 1/2" MAX. OF
ALL EDGES OF ROOM DECK
CORRUGATIONS (4" MIN. HT.
PIECE) E.S.
FIRE SAFING INSULATION TO FILL
VOIDS AT F.R. PARTITIONS,
FIBERGLASS INSULATION OTHERWISE
ACOUSTICAL
CAULKING
ACOUSTICAL CAULK E.S.
(FIRE CAULK RATED WALLS)
Revision Schedule
PROJECTION
MINERAL FIBER COMPRESSIBLE
FILLER OR ACOUSTICAL SEALANT TO
PREVENT VIBRATION OF GYP & SLAB
PROJ.
FLOOR
#
Date
Description
AUDITORIUM
VERTICAL STUDS FIXED TO TRACK AT TOP
USING REDI KLIP (TOTAL STEEL
SOLUTIONS) TO ALLOW DEFLECTION TYP
1' - 0"
B
10.10.2017
WALL BASE, MITER VERTICAL
TRANSITIONS GLUE & STAPLE, REMOVE
STAPLES WHEN MASTIC DRIES TYP.
5/8" GYP. BD.
CONTINUE R-19
BATTS TO TOP OF
TRACK
5/8" GYP. BD.
WALL FINISH PER
SCHEDULES TYP.
CONTINUE STUD
BELOW STRUCTURE
5/8" GYP. BD.
THIS DETAIL APPLIED TO ALL WALLS AROUND THEATRES
AT WALLS PARALLEL TO DECK CORRUGATIONS.
FACE LAYER TO 1/2" MAX. OF
ALL EDGES OF ROOM DECK
CORRUGATIONS (4" MIN. HT.
PIECE) E.S.
SEALANT AT INTERSECTION OF
GYPSUM WALL BOARD &
PLATFORM TO PROVIDE
CONTINUOUS SEAL TYP
VCT
4' - 0" A.F.F.
ACOUSTICAL CAULK E.S. (FIRE
CAULK RATED WALLS)
INSULATION (6" WIDE
MINIMUM) (FIRE SAFING @
FIRE RATED PARTITIONS)
WALL CARPET PER ELEVATIONS
BASE LAYER TO UNDERSIDE
OF ROOF DECK FLUTES
JOIST GIRDER OR BEAM
PER STRUCT.
TOP STADIUM SEATING PLATFORM
VERTICAL STUDS FIXED TO
TRACK
AT TOP USING REDI KLIP (TOTAL
STEEL SOLUTIONS) TO ALLOW
DEFLECTION TYP
ACOUSTICAL MATTING
(FULL WIDTH OF WALL)
3" FIBERGLASS BATTS E.S.
OF GIRDER
STADIUM SEATING SUPPORT REF
STRUCTURAL
1' - 0"
1" CLOSED CELL STYROFOAM
EMBEDDED INTO GRAVEL 2" MIN.
NUMBER OF GYP. BD. LAYERS
PER WALL TYPE
STUD WITH
ACOUSTICAL
INSULATION PER WALL KEY
4"
2' - 0"
4"
1ST FLOOR
PROMENADE/CORRIDOR WALL
THIS DETAIL APPLIED TO ALL WALLS AROUND AUDITORIUMS AT
WALLS PERPENDICULAR TO DECK CORRUGATIONS AT A JOIST
GIRDER OR BEAM.
3
2
INTERIOR WALL
SECTIONS
CEILING PER RCP
A
1
PROJECT # 17025
3
DETAILS AT THEATRE ROOF
1 1/2" = 1'-0"
2
4
TYPICAL DEMISING WALL
1" = 1'-0"
5
1
6
PROJECTION WALL FLOOR JUNCTIONS
1 1/2" = 1'-0"
SHEET NUMBER
A1.64