SECURITY AND FIRE ALARM - Northwestern University

MASTER SPECIFICATIONS
Division 28 – SECURITY AND FIRE ALARM
Release 1.0
[March] 2017
Released by:
Northwestern University
Facilities Management Operations
2020 Ridge Avenue, Suite 200
Evanston, IL 60208-4301
All information within this Document is considered CONFIDENTIAL and PROPRIETARY. By
receipt and use of this Document, the recipient agrees not to divulge any of the information herein
and attached hereto to persons other than those within the recipients’ organization that have
specific need to know for the purposes of reviewing and referencing this information. Recipient
also agrees not to use this information in any manner detrimental to the interests of Northwestern
University.
Northwestern University
Master Specifications
Copyright © 2017
By Northwestern University
These Specifications, or parts thereof, may not be reproduced in any form without
the permission of the Northwestern University.
NORTHWESTERN UNIVERSITY
PROJECT NAME ____________
JOB # ________
FOR: ___________
ISSUED: 03/29/2017
MASTER SPECIFICATIONS: DIVISION 28 – SECURITY AND FIRE ALARM
SECTION #
TITLE
28 0000
28 0500
28 1000
28 3113
SECURITY DESIGN CRITERIA
COMMON WORK RESULTS FOR SECURITY SYSTEMS
SECURITY ACCESS CONTROL
DIGITAL ADDRESSABLE FIRE DETECTION AND ALARM SYSTEM
** End of List **
NORTHWESTERN UNIVERSITY
PROJECT NAME ____________
JOB # ________
FOR: ___________
ISSUED: 03/29/2017
SECTION 28 0000 – SECURITY DESIGN CRITERIA
PART 1 - GENERAL
1.1
RELATED DOCUMENT
A.
1.2
Drawings and general provisions of the Contract, including General and Supplementary
Conditions and Division 01 Specification Sections, apply to this Section
SUMMARY
A.
This section includes the following:
1.
2.
B.
Related Sections
1.
2.
1.3
Conduits
Boxes
Division 26 – Electrical
Division 27 – Technology and Communications
REFERENCES
A.
NFPA 70 – The National Electrical Code
B.
ANSI/TIA 568-C.0 – Generic Telecommunications Cabling for Customer Premise
C.
ANSI/TIA/EIA 568-C.1 – Commercial Buildings Telecommunications Cabling Standard
D.
ANSI/TIA/EIA 569 – Commercial Building Standard for Telecommunications Pathways and
Spaces
E.
ANSI/TIA/EIA 606-A – Administration Standard for the Telecommunications Infrastructure of
Commercial Building; TR-42.6 - Labeling
F.
ANSI/TIA/EIA 607A – Commercial Building Grounding and Bonding Requirements for
Telecommunications
G.
ANSI/TIA – TSB 95 – Testing Standards
H.
ANSI/TIA-568-B.2-ad10 – Augmented Category 6
I.
ANSI/TIA 942 – Data Center Cabling Standard
J.
BICSI TDMM – Telecommunications Distribution Methods Manual
SECURITY DESIGN CRITERIA
28 0000 - 1
NORTHWESTERN UNIVERSITY
PROJECT NAME ____________
JOB # ________
1.4
FOR: ___________
ISSUED: 03/29/2017
SUBMITTALS
A.
Product Data: For each type of product indicated.
B.
Include data sheets for the following additional items:
1.
2.
C.
Samples
1.
1.5
Grounding and bonding
Lightning Protection
The Engineer reserves the right to request, and have submitted, additional samples, or
samples not explicitly requested within these Documents.
DELIVERY STORAGE AND HANDLING
A.
The Contractor shall responsible for the storage and handling of all Materials required by the
Structured Cabling portion of this Contract.
B.
Storage and Protection
1.
C.
Waste Management and Disposal
1.
2.
1.6
Any Materials that show signs of mishandling or have been stored in a fashion so as to
reduce the value of the Materials shall be replaced with new Materials at no additional
cost to the Owner.
All excess Materials shall be discarded in an appropriate manner.
Any/all hazardous materials shall be handled appropriately and shall be disposed of in a
manner consistent with same, and compliant with all applicable codes and regulations.
DELIVERY STORAGE AND HANDLING
A.
The Contractor shall responsible for the storage and handling of all Materials required by the
Structured Cabling portion of this Contract.
B.
Storage and Protection
1.
C.
Waste Management and Disposal
1.
2.
1.7
Any Materials that show signs of mishandling or have been stored in a fashion so as to
reduce the value of the Materials shall be replaced with new Materials at no additional
cost to the Owner.
All excess Materials shall be discarded in an appropriate manner.
Any/all hazardous materials shall be handled appropriately and shall be disposed of in a
manner consistent with same, and compliant with all applicable codes and regulations.
PROJECT/SITE CONDITIONS
A.
The Contractor shall become and remain familiar with all project/site conditions that may have
impact on the timing, quality and/or quantity of Materials for the project. The Contractor shall
SECURITY DESIGN CRITERIA
28 0000 - 2
NORTHWESTERN UNIVERSITY
PROJECT NAME ____________
JOB # ________
FOR: ___________
ISSUED: 03/29/2017
coordinate their efforts with changes in the Project/Site conditions so as to optimize the
installation for the Owner.
B.
Any additional efforts by the Contractor due to a lack of awareness of project/site conditions
shall not require additional compensation from the Owner.
PART 2 - PRODUCTS
2.1
MATERIALS
A.
Boxes and Conduit
1.
2.
3.
4.
All boxes and conduit shall be new and UL listed.
Security conductors shall be routed in blue metal raceways.
Minimum raceway size is ¾”.
All boxes and conduit shall be as specified under the Division 26 specifications.
PART 3 - EXECUTION
3.1
EXAMINATION
A.
Materials shall be examined for damage on receiving the materials. Reject any materials that
are damaged.
B.
Examine all materials before installation. Reject and materials that are damaged.
C.
Examine elements and surfaces to which materials will be installed.
D.
Proceed with installation only after unsatisfactory conditions have been corrected.
3.2
INSTALLATION
A.
Telecommunications pathways, spaces and metallic raceways, which run parallel with electric
power or lighting cables or conduits, which is less than or equal to 480 Vrms, shall be installed
with a minimum clearance of 50 mm (2 inches).
B.
The Contractor shall provide all devices for routing the cabling as indicated on the Drawings,
and as required by the manufacturer of the Structured Cabling System, so as to maintain the
long term health and operability of the Structured Cabling System.
C.
All horizontal pathways shall be designed, installed and grounded to meet applicable local and
national codes
1.
Boxes
a.
All boxes, unless otherwise specifically indicated, shall be 4-11/16" square by 21/8" deep, with a two gang plaster ring, of appropriate depth for the wall material
utilized in the application.
SECURITY DESIGN CRITERIA
28 0000 - 3
NORTHWESTERN UNIVERSITY
PROJECT NAME ____________
JOB # ________
b.
2.
Where pullboxes are utilized, conduits shall enter and exit the box on opposite
sides of the box. The box shall not be used as the turning point of the cable.
Conduit
a.
b.
All conduit shall be a minimum of 3/4".
Conduit routes shall meet the following criteria:
1)
2)
3)
4)
3.
Security system components shall be bonded to the building grounding systems.
1)
2)
3)
3.3
Every underground and overhead security conductor which enters a facility from
the outdoors shall have a lighting arrestor installed.
Power Outage Protection
a.
6.
Grounding conductor shall be compliant with Class 1 systems.
Conduit shall be properly bonded to cable trays, wireways, and pull boxes,
as appropriate.
Power supplies grounded in compliance with Class 3 requirements.
Lightning Protection
a.
5.
No conduit bend shall exceed 90º.
Conduit bends must be no less than 6-inch radius.
No conduit route shall have more than two bends.
Continuous conduit runs shall not exceed 100 ft. nor contain more than two
(2) 90º bends without utilizing appropriately sized pull boxes
Bonding and Grounding
a.
4.
FOR: ___________
ISSUED: 03/29/2017
Uninterruptable Power Supplies
Door Security Device Power Supplies
FIELD QUALITY CONTROL
A.
Keep areas of work accessible until inspection by authorities having jurisdiction.
B.
Where deficiencies are found, repair products so they comply with the Construction Documents.
C.
Install work in full accordance with the rules, regulations, and safety requirements of Federal,
State, County and City authorities having jurisdiction over premises. Do not construe this as
relieving Contractor from compliance with any requirements of the Specifications which are in
excess of Code requirements and not in conflict therewith.
D.
Correct unacceptable workmanship and, as necessary, provide additional inspection to verify
compliance with this Specification at no additional cost to the Owner or the Owner's appointed
representative.
3.4
ADJUSTING AND CLEANING
A.
Remove equipment, materials, and debris, leaving area in undamaged, clean condition.
SECURITY DESIGN CRITERIA
28 0000 - 4
NORTHWESTERN UNIVERSITY
PROJECT NAME ____________
JOB # ________
B.
FOR: ___________
ISSUED: 03/29/2017
Clean all surfaces adjacent to sealed openings to be free of excess firestopping materials and
soiling as work progresses.
END OF SECTION 28 0000
SECURITY DESIGN CRITERIA
28 0000 - 5
NORTHWESTERN UNIVERSITY
PROJECT NAME ____________
JOB # ________
FOR: ___________
ISSUED: 03/29/2017
THIS PAGE IS INTENTIONALLY BLANK
SECURITY DESIGN CRITERIA
28 0000 - 6
NORTHWESTERN UNIVERSITY
PROJECT NAME ____________
JOB # ________
FOR: ___________
ISSUED: 03/29/2017
SECTION 28 0500 - COMMON WORK RESULTS FOR COMMUNICATIONS
PART 1 - GENERAL
1.1
SUMMARY
A.
It is intended this project pursue a LEED “Gold” rating. LEED criteria will be followed for the
installation of building systems. This Contractor shall be responsible for the following items to
ensure the Facility achieves LEED certification:
1.
2.
3.
4.
5.
6.
7.
B.
Section Includes:
1.
1.2
SS credit 8 – Light Pollution Reduction.
EA prerequisite 2 – Minimum Energy Performance.
EA credit 1 – Optimize Energy Performance.
MR credit 2 – Construction Waste Management.
IEQ credit 4.1 – Low Emitting Materials: Adhesives and Sealants
IEQ credit 4.2 – Low Emitting Materials: Paints and Coatings.
IEQ credit 6.1 – Controllability of Systems: Lighting.
This Section contains the Common communications installation requirements that shall
be required of Contractors bidding and executing any part of these documents.
SUBMITTALS
A.
N/A.
PART 2 - PRODUCTS
2.1
N/A.
PART 3 - EXECUTION
3.1
COMMON REQUIREMENTS FOR COMMUNICATIONS INSTALLATION
A.
Comply with most current edition of the Northwestern University Design Standards.
B.
(Select based on project location) [Comply with City of Chicago Codes and Standards.]
[Comply with City of Evanston Codes and Standards.]
C.
Comply with NECA, NFPA, and OSHA requirements.
D.
All work shall be installed in a neat, workmanlike manner in accordance with ANSI/NECA 1 –
2015.
COMMON WORK RESULTS FOR COMMUNICATIONS
28 0500 - 1
NORTHWESTERN UNIVERSITY
PROJECT NAME ____________
JOB # ________
FOR: ___________
ISSUED: 03/29/2017
E.
All materials and equipment provided under this contract shall be new (except where otherwise
noted) and shall be listed, labeled or certified by Underwriters Laboratories, Inc.
F.
All equipment of the same type and capacity shall be by the same manufacturer.
G.
Where any device or part of equipment is referred to in these specifications in the singular
number (e.g., "the switch"), this reference shall be deemed to apply to as many such devices as
are required to complete the installation as shown on the drawings.
H.
During construction the contractor shall at all times maintain electrical utilities of the building
without interruption. Should it be necessary to interrupt any electrical service or utility, the
contractor shall secure permission in writing from the University for such interruption at least
seven days in advance. Any interruption shall be made with minimum amount of inconvenience
to the University and any shut-down time shall have to be on a premium time basis and such
time to be included in the contractor's bid. Arrange to provide and pay for temporary power
source if required by project conditions.
I.
Measure indicated mounting heights to bottom of unit for suspended items and to center of unit
for wall-mounted items.
J.
Headroom Maintenance: If mounting heights or other location criteria are not indicated, arrange
and install components and equipment to provide maximum possible headroom consistent with
these requirements.
K.
Working clearance around equipment shall not be less than that specified in the N.E.C. for all
voltages specified.
L.
The locations of switches, receptacles, lights, motors, etc. outlets shown are approximate. The
contractor shall use good judgment in placing the preceding items to eliminate all interference
with ducts, piping, etc. The contractor shall check all door swings so that light switches are not
located behind doors. Relocate switches as required, with approval from the Design
Professional. The University may direct relocation of outlets before installation, up to five (5) feet
from the position indicated on the Drawings, without additional cost.
M.
Equipment: Install to facilitate service, maintenance, and repair or replacement of components
of both electrical equipment and other nearby installations. Connect in such a way as to
facilitate future disconnecting with minimum interference with other items in the vicinity. Normal
maintenance shall not require the removal of protective guards from adjacent equipment. Install
equipment as close as practical to the locations shown on the Drawings.
1.
2.
Where the University determines that the Contractor has installed equipment not
conveniently accessible for operations and maintenance, the equipment shall be
removed and reinstalled as directed at no additional cost to the University.
“Conveniently Accessible” is defined as being capable of being reached without use of
ladders, or without climbing or crawling over or under obstacles such as motors, pumps,
belt guards, transformers, racks, piping, ductwork, raceways or similar.
N.
Right of Way: Give to piping systems installed at a required slope.
O.
Firestopping shall be applied to electrical penetrations of fire-rated floor and wall assemblies to
restore original fire-resistance rating of the assembly according to Division 07 and 09 Sections
and the University’s Commissioning Agent.
COMMON WORK RESULTS FOR COMMUNICATIONS
28 0500 - 2
NORTHWESTERN UNIVERSITY
PROJECT NAME ____________
JOB # ________
P.
FOR: ___________
ISSUED: 03/29/2017
Owner furnished equipment: Equipment furnished by the University shall be received, stored,
uncrated, protected, and installed by the Contractor with all appurtenances required to place the
equipment in operation, ready for use. The Contractor shall be responsible for the equipment as
if he had purchased the equipment himself.
END OF SECTION 28 0500
COMMON WORK RESULTS FOR COMMUNICATIONS
28 0500 - 3
NORTHWESTERN UNIVERSITY
PROJECT NAME ____________
JOB # ________
FOR: ___________
ISSUED: 03/29/2017
THIS PAGE IS INTENTIONALLY BLANK
COMMON WORK RESULTS FOR COMMUNICATIONS
28 0500 - 4
NORTHWESTERN UNIVERSITY
PROJECT NAME ____________
JOB # ________
FOR: ___________
ISSUED: 03/29/2017
SECTION 28 1000 – SECURITY ACCESS CONTROL
PART 1 - GENERAL
1.1
RELATED DOCUMENT
A.
1.2
Drawings and general provisions of the Contract, including General and Supplementary
Conditions and Division 01 Specification Sections, apply to this Section
SUMMARY
A.
The Section defines the requirements for the installation of the system. As described elsewhere
in these Documents the system consists of twisted pair cabling and hardware, and related
hardware. In addition to the basic cable plant requirements, the testing and identification
requirements are also defined. Finally, the racks, enclosures, and pathway hardware is also
defined herein.
B.
Section Includes
1.
2.
3.
4.
5.
6.
7.
8.
C.
Related Sections
1.
2.
3.
4.
5.
1.3
Twisted Pair Cable
Patch Panels
Jacks
Faceplates
Patch Cords
Racks
Wire Management
Innerduct
Section 27 05 00 – Communications Common Work Results
Section 27 05 24 – Firestopping
Section 27 05 26 – Technology Grounding System
Section 28 13 00 – Access Control System
Section 28 23 00 – Video Surveillance System
REFERENCES
A.
NFPA 70 – The National Electrical Code
B.
ANSI/TIA 568-C.0 – Generic Telecommunications Cabling for Customer Premise
C.
ANSI/TIA/EIA 568-C.1 – Commercial Buildings Telecommunications Cabling Standard
D.
ANSI/TIA/EIA 569 – Commercial Building Standard for Telecommunications Pathways and
Spaces
SECURITY ACCESS CONTROL
28 1000 - 1
NORTHWESTERN UNIVERSITY
PROJECT NAME ____________
JOB # ________
FOR: ___________
ISSUED: 03/29/2017
E.
ANSI/TIA/EIA 606-A – Administration Standard for the Telecommunications Infrastructure of
Commercial Building; TR-42.6 - Labeling
F.
ANSI/TIA/EIA 607A – Commercial Building Grounding and Bonding Requirements for
Telecommunications
G.
ANSI/TIA – TSB 95 – Testing Standards
H.
ANSI/TIA-568-B.2-ad10 – Augmented Category 6
I.
ANSI/TIA 942 – Data Center Cabling Standard
J.
BICSI TDMM – Telecommunications Distribution Methods Manual
K.
Northwestern University Design Information Technology Building Infrastructure Requirements
for Communications Systems
1.4
SUBMITTALS
A.
Product Data: For each type of product indicated.
B.
Include data sheets for the following additional items:
1.
2.
3.
4.
5.
6.
7.
C.
Shop Drawings
1.
1.5
Twisted Pair Cable
Patch Panels
Jacks
Faceplates
Patch Cords
Racks
Wire Management
Drawings of any through floor fittings with details of their contents.
QUALITY ASSURANCE
A.
Qualifications
1.
2.
3.
4.
5.
The Contractor shall be fully qualified to perform installations as described on the
Contract Drawings and within these Specifications.
The Contractor shall have completed a minimum of three projects of like scope and
complexity within the last three (3) years.
The Contractor shall have been active in bidding, being awarded, and performing work
consistent with that which is indicated on the Contract Documents for a period not less
than five (5) years.
The Contractor shall maintain an installation staff whose sole function is the installation of
Structured Cabling and associated equipment and shall not utilize additional personnel
obtained by means of a temporary placement or staffing agency.
The Contractor shall have a dedicated Project Manager, who shall be the sole point of
contact for the Engineer or Owner. The Project Manager shall be assigned to the project
for the duration of the project.
SECURITY ACCESS CONTROL
28 1000 - 2
NORTHWESTERN UNIVERSITY
PROJECT NAME ____________
JOB # ________
B.
Certifications
1.
2.
C.
The Contractor shall provide equipment assemblies for review at the request of
Northwestern University.
Meetings
1.
1.6
Northwestern University reserves the right to request samples of components required by
these specifications.
Mock Ups
1.
E.
The Contractor shall possess current certifications by BICSI for the installation and
maintenance of all Structured Cabling and associated equipment being provided under
the Structured Cabling Contract.
The Contractor shall possess current certification for the installation of all required fire
stopping to be installed under the scope of the Structured Cable Plant.
Samples
1.
D.
FOR: ___________
ISSUED: 03/29/2017
The Contractor shall be attend all Pre-Construction, Pre-Installation or Progress Meetings
that may be called by Northwestern University.
DELIVERY STORAGE AND HANDLING
A.
The Contractor shall responsible for the storage and handling of all Materials required by the
Structured Cabling portion of this Contract.
B.
Storage and Protection
1.
C.
Waste Management and Disposal
1.
2.
1.7
Any Materials that show signs of mishandling or have been stored in a fashion so as to
reduce the value of the Materials shall be replaced with new Materials at no additional
cost to the Owner.
All excess Materials shall be discarded in an appropriate manner.
Any/all hazardous materials shall be handled appropriately and shall be disposed of in a
manner consistent with same, and compliant with all applicable codes and regulations.
PROJECT/SITE CONDITIONS
A.
The Contractor shall become and remain familiar with all project/site conditions that may have
impact on the timing, quality and/or quantity of Materials for the project. The Contractor shall
coordinate their efforts with changes in the Project/Site conditions so as to optimize the
installation for the Owner.
B.
Any additional efforts by the Contractor due to a lack of awareness of project/site conditions
shall not require additional compensation from the Owner.
SECURITY ACCESS CONTROL
28 1000 - 3
NORTHWESTERN UNIVERSITY
PROJECT NAME ____________
JOB # ________
FOR: ___________
ISSUED: 03/29/2017
PART 2 - PRODUCTS
2.1
GENERAL
A.
Equivalent Products
1.
2.2
Only products listed as approved shall be utilized. Substitutions, under normal
circumstances, shall not be allowed. However, in unusual cases, substitutions may be
unavoidable. ALL requests for product substitutions shall be approved by the Engineer
prior to the bid submission. Loss of certification by the Contractor, or unavailability of
product to the Contractor that is not of a market wide nature, shall not be construed as an
unavoidable circumstance. The request for product substitution and supporting
documentation, must be submitted, in writing, along with any samples requested by the
Engineer. Written approval for product substitution must be submitted with the bid.
COMPONENTS
A.
Connectors
B.
Connectors
1.
Data/Voice (Copper)
a.
b.
c.
C.
Faceplates
1.
2.
3.
4.
5.
6.
All Faceplates shall be available in single, duplex, triplex, quadplex, or sixplex
arrangements in a single gang configuration.
Faceplates shall be available in eightplex arrangements in a two gang configuration.
Surface mount boxes shall be available in single, dual, quad, sixplex and twelveplex
configuration.
All faceplates shall be as manufactured by the manufacturer of the associated
connectors, unless otherwise noted in the Drawings.
Faceplates shall wherever possible match the color of the associated electrical
faceplates. Coordinate the faceplate color with the electrical contractor and drawings
prior to installation.
Acceptable Manufacturers and Series
a.
b.
D.
Panduit Mini-Com Category 5e
Panduit Mini-Com Category 6a
Belden Category 6a
Belden
Panduit – Mini-com faceplates
Patch Panels
1.
Copper
a.
b.
The termination block shall support the appropriate Category 5e or Category 6a
applications, both current and future, designed for the associated connectivity
solution.
All patch panels shall be wired to EIA/TIA 568B.
SECURITY ACCESS CONTROL
28 1000 - 4
NORTHWESTERN UNIVERSITY
PROJECT NAME ____________
JOB # ________
c.
d.
e.
f.
g.
h.
i.
The wiring block shall be able to accommodate both 22 and 24 AWG cable
conductors.
The block shall be Underwriter’s Laboratories (UL) listed, and ETL certified.
All patch panels shall be UL listed for Category 6.
A 110 IDC block shall provide for the termination of horizontal, equipment, or tie
cables.
The signal transmission from the 110 punch down terminals to the RJ45 jack shall
be by means of a printed circuit board.
All patch panels shall be 48 port 2U configurations.
Approved manufacturers and part numbers
1)
2)
E.
FOR: ___________
ISSUED: 03/29/2017
Belden
Panduit Category 6 Patch Panel
Cabling
1.
Copper
a.
Category 5e Unshielded Twisted Pair (UTP), 4 Pair
1)
2)
3)
4)
Category 5e UTP, 4 Pair Horizontal Distribution Cables shall extend
between the station location and the associated HC, shall consist of 4 pair,
24 gauge, UTP, and shall terminate all conductors onto an 8 pin modular
jack provided at each outlet. Cable jacket shall comply with Article 800 of
the NEC for use as a plenum or non-plenum cable as required by these
Specifications and by the local authority having jurisdiction. The 4 pair UTP
cable shall be UL Listed Type CMP (plenum) or CM (non-plenum).
The Category 5e UTP cable shall be a round cable design with fluting to
maintain the appropriate pair spacing relationship. The cable shall support
all current future applications designed to run on Category 5e cabling.
The Category 5e cable shall be specified to a minimum of 100 MHz.
Approved manufacturers and part numbers
a)
b)
b.
Belden
Panduit
Category 6a Unshielded Twisted Pair (UTP), 4 Pair
1)
2)
3)
4)
5)
Category 6 UTP, 4 Pair Horizontal Distribution Cables shall extend between
the station location and the associated HC, shall consist of 4 pair, 24 gauge,
UTP, and shall terminate all conductors onto an 8 pin modular jack provided
at each outlet. Cable jacket shall comply with Article 800 of the NEC for use
as a plenum or non-plenum cable as required by these Specifications and
by the local authority having jurisdiction. The 4 pair UTP cable shall be UL
Listed Type CMP (plenum) or CM (non-plenum).
The Category 6 UTP cable shall be a round cable design with fluting to
maintain the appropriate pair spacing relationship. The cable shall support
all current future applications designed to run on Category 6 cabling.
The Category 6 UTP cable shall be designed to have improved balance of
10dB as compared to current Category 5e cable, which shall result in higher
immunity to EMI.
The Category 6 cable shall be specified to a minimum of 500 MHz.
Approved manufacturers and part numbers
SECURITY ACCESS CONTROL
28 1000 - 5
NORTHWESTERN UNIVERSITY
PROJECT NAME ____________
JOB # ________
a)
b)
F.
FOR: ___________
ISSUED: 03/29/2017
Belden
Panduit
Equipment Racks
1.
2.
Each MC/ER/HC shall be equipped with a 19” Aluminum Rack System to house Owner
provided equipment and Contractor provided termination bays for the multiple cable
types.
19” Aluminum Rack System
a.
b.
The rack shall be able to support and organize electronic equipment, cross
connection and/or termination hardware for fiber optic cabling, horizontal
distribution cabling, riser cabling, or building entrance cabling as may be required
by the design. The rack face shall have a conventional equipment mounting width
of 19”. The rack shall be designed for cable and jumper management and shall
have hardware to organize and support cabling and patch cords in the vertical and
horizontal planes. The rack system shall be equipped for electrical grounding to
meet EIA/TIA 606 Standards, and the designed grounding system. The fastening
system for the equipment shall facilitate installation with roll-formed threads in the
screw holes for greater strength and durability and the mounting screws shall have
pilot points. All rack components shall be charcoal black in color and made of
lightweight 6061-T6 extruded aluminum. The rack shall be shipped with all
necessary hardware to assemble the frame. It shall be packed in cartons with
suitable shipping inserts such that no damage occurs to the rack finish. The finish
shall not be scratched, chipped, or marred.
Self-Supported Rack Framework
1)
2)
3)
4)
5)
6)
The self-supporting equipment rack shall be 7’ tall with 3” wide channels at
each side and with extruded aluminum top angles and base angles
providing support. Standard grade frames shall be capable of supporting
700 lbs., with uniform distribution of weight.
Standard frames shall provide a .19” thick channel flange and .13” web
thickness.
Standard base angles shall be .3125” thick, and top angles shall be .1815”
thick.
Racks shall be able to be mounted side by side and be secured to adjacent
racks in a line-up with vertical wire management between each rack.
The self-supporting rack shall maintain a UL listing for a telecommunications
accessory.
Approved Manufacturers and Products shall be:
a)
b)
c)
c.
Chatsworth – 7’ UL Standard Rack
Equal by Homaco, Ortronics, or Panduit
All accessories and related hardware associated with a rack shall be
provided by the manufacturer of the rack, unless otherwise noted in
these Documents.
Horizontal Wire Management
1)
2)
3)
4)
Units shall fit in a standard 19” rack.
Units shall be 1U or 2U construction.
Units shall be two sided to provide functionality on both the front and back of
the rack.
Units shall have front and back covers that have a dual hinge technology
SECURITY ACCESS CONTROL
28 1000 - 6
NORTHWESTERN UNIVERSITY
PROJECT NAME ____________
JOB # ________
5)
6)
Access into and out of the top and bottom of the Management shall be
finger type construction.
Approved Manufacturers and Models shall be:
a)
b)
d.
Chatsworth Products Universal Cable Manager, utilizing two units, in
a front/back configuration.
Equal by Homoco, Panduit, or Ortronics
Vertical Wire Management
1)
2)
3)
4)
5)
6)
Units shall have a standard bracket that shall allow for ready installation to
any industry standard relay rack.
Units shall have finger guides spaced at 1U.
Units shall be 7’ tall.
Unit shall be double sided to provide wire management for both the front
and back of the rack.
Unless otherwise noted in these Documents, the units shall be 4” wide by 5”
deep in each section, front and back.
Approved Manufacturers and Models
a)
b)
2.3
FOR: ___________
ISSUED: 03/29/2017
Chatsworth Master Cabling Section
Equal by Panduit Standard Vertical Slotted Duct or Ortronics
ACCESSORIES
A.
Patch Cords
1.
Copper
a.
b.
Patch Cords shall be manufactured and supplied by the manufacturer of the
connectivity provide, and shall be rated for the same performance specifications as
the cabling and connectivity being utilized.
Unless otherwise indicated on the Drawings the Contractor shall supply patch
cords based on 100% of the outlets at the work area, and any wall phone
locations. Of the cables provided, the Contractor shall supply 25% of the cables
as 1m, 50% as 3m, and 25% as 5m.
PART 3 - EXECUTION
3.1
EXAMINATION
A.
Materials shall be examined for damage on receiving the materials. Reject any materials that
are damaged.
B.
Examine all materials before installation. Reject and materials that are damaged.
C.
Examine elements and surfaces to which materials will be installed.
D.
Proceed with installation only after unsatisfactory conditions have been corrected.
SECURITY ACCESS CONTROL
28 1000 - 7
NORTHWESTERN UNIVERSITY
PROJECT NAME ____________
JOB # ________
3.2
FOR: ___________
ISSUED: 03/29/2017
INSTALLATION
A.
Cable Routing
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
14.
15.
16.
17.
Provide a 36” service loop at the end of each work area stub, and a 10’ service loop at
the TR servicing that drop. The service loop at the TR shall be stored in the cable
runway of the TR in a fashion so as to prevent the crushing of the service loop by other
cable stacked on the service loop. Should no cable runway or cable tray be available for
such service loops, construct a loop storage system of J-Hooks or add an additional
section(s) of cable runway to accommodate the service loops.
Non-continuous pathways shall keep hallway crossover to a minimum. Furthermore, noncontinuous pathways shall be routed so as to follow logical paths parallel and
perpendicular to the building structure. Diagonal pathways are unacceptable, unless
agreed to by NUIT.
In suspended ceiling and raised floor areas where duct, cable trays or conduit are not
available, the Contractor shall bundle, in bundles of 50 or less, horizontal distribution
wiring with cable ties snug, but not deforming the cable geometry. Where cable bundles
are to be supported by J-hooks, the J-hooks shall be attached to the building structure
and framework per local codes and regulations at a maximum of five (5) foot intervals.
Cables shall be bundled by means of either Velcro or Milli-Ties. Zip-ties are
unacceptable.
All horizontal cables shall not exceed 90m (295 ft) from the Telecommunications Outlets
in the Work Area to the Horizontal Cross Connect.
The combined length of jumpers, or patch cords and equipment cables in the
telecommunications room/closet and the Work Area shall not exceed 10m (33 ft) unless
used in conjunction with a multi-user Telecommunications Outlet.
A minimum of three horizontal cables shall be routed to each Work Area, unless
otherwise noted on the Drawings.
Horizontal pathways shall be installed such that the minimum bending radius of horizontal
cables is kept within manufacturer specifications both during and after installation.
Telecommunications pathways, spaces and metallic raceways, which run parallel with
electric power or lighting cables or conduits, which is less than or equal to 480 Vrms,
shall be installed with a minimum clearance of 50 mm (2 inches).
The installation of telecommunications cabling shall maintain a minimum clearance of 3
m (10 ft) from power cables or conduits in excess of 480 Vrms.
No telecommunications cross connects shall be physically located within 6 m (20 ft) of
electrical distribution panels, or step down transformers, which carry voltages in excess
of 480 Vrms.
Each run of UTP/ScTP cable between the horizontal portion of the cross connect in the
telecommunication closet and the information outlet shall not contain splices.
The Contractor shall provide all devices for routing the cabling as indicated on the
Drawings, and as required by the manufacturer of the Structured Cabling System, so as
to maintain the long term health and operability of the Structured Cabling System.
In a false ceiling environment, a minimum of 75 mm (3 inches) shall be observed
between the cable supports and the false ceiling.
Continuous conduit runs installed by the Electrical Contractor shall not exceed 30.5 m
(100 ft) or contain more than two (2) 90 degree bends without utilizing appropriately sized
pull boxes, unless otherwise indicated in these Specifications or on the Drawings. The
Technology Contractor shall verify the proper installation technique and sizing of the
raceway system with the Electrical Contractor prior to installation of the cabling.
All horizontal pathways shall be designed, installed and grounded to meet applicable
local and national codes.
The number of horizontal cables placed in a cable support or pathway shall be limited to
a number of cables that will not affect the geometric shape of the cables.
SECURITY ACCESS CONTROL
28 1000 - 8
NORTHWESTERN UNIVERSITY
PROJECT NAME ____________
JOB # ________
18.
19.
20.
21.
22.
23.
B.
Maximum conduit pathway capacity shall not exceed a 40% fill with the exception of
perimeter and furniture fill, which is limited to 60% fill for moves, adds and changes,
unless otherwise noted on Drawings.
Horizontal distribution cables shall not be exposed in the Work Area or other locations
with public access.
Cables routed in a suspended ceiling shall not be draped across the ceiling tiles. Cable
supports shall be mounted a minimum of 75 mm (3 inches) above the ceiling grid
supporting the tiles.
Cabling shall not be attached to any mechanical, electrical or technology system other
than those specifically noted in the Contract Documents.
Cabling shall maintain clearance from Line Voltage cabling and devices at all times, and
shall be spaced from these devices so as to comply with the TDMM, the NEC, and any
other local codes or regulations.
Cables shall be bundled by means of either Velcro strap or Milli-Ties. Zip-ties are
unacceptable.
Racks
1.
2.
3.
4.
3.3
FOR: ___________
ISSUED: 03/29/2017
All racks shall be anchored to the floor, structure below or wall as directed by the
manufacturer. And shall comply with any seismic requirements as directed by any local,
state or federal regulations.
All racks shall be assembled as directed by the manufacturer with the addition of any
supplemental grounding requirements listed elsewhere in these Documents.
All racks shall be assembled with a vertical wire management located at each side of
each row of racks, and on vertical wire management between each two adjacent racks,
unless directed otherwise within these Documents.
All racks with active electronics mounted within, or indicated as having active electronics
installed by others, or in the future shall have a vertical power distribution unit mounted
on the rear.
LABELING
A.
General Labeling Requirements
1.
2.
3.
4.
5.
6.
7.
8.
9.
The SCC shall label, all cables, faceplates, cabling enclosures, patch panels, termination
blocks, racks, equipment enclosures and related hardware.
All work shall be in compliance to TIA/EIA 606.
All labels shall be permanently attached, and shall be constructed of materials so as to
assure the lifespan of the identification marker to be equal or greater than that of the
device being identified.
The identification tag or placard shall be self adhering or attached by means of a
permanent adhesive listed for the application, or other permanent mechanical means.
All means of identification shall be visible and clearly identifiable by personnel in charge
of maintaining the cabling infrastructure.
All tape based products shall be manufactured for the purpose of identifying flexible
communications cabling, and shall be used only on flexible materials.
All labels shall be machine generated onto adhesive labels or tags, or engraved on
plastic laminated placards or brass tags. Use of P.Touch tape or other domestic/light duty
type of label is unacceptable.
All laminated placards shall have a black field with white letters, unless otherwise noted.
The SCC shall compile all documentation required under this Section, both hard copy
and electronic, and include the information in the Operating and Maintenance Manuals.
SECURITY ACCESS CONTROL
28 1000 - 9
NORTHWESTERN UNIVERSITY
PROJECT NAME ____________
JOB # ________
10.
B.
2.
3.
4.
5.
3.
4.
3.
4.
All patch panels shall be labeled as to the identity of the patch panel.
The patch panel identification shall be derived based on the rack in which it is mounted
and a sequential letter, e.g. TR01A-PP03, where TR01A is the rack ID, and PP03
indicates that this is the third patch panel in the rack.
The label shall be installed in the space provided by the manufacturer for this purpose. If
no space is provisioned, the Contractor shall provide a laminated placard that shall be
engraved with the identification of the patch panel, and shall be mounted in the upper
right corner of the patch panel, but shall not block the proper installation of the patch
panel.
All ports shall be labeled with the ID of the faceplate terminated at that port, and the
associated jack letter from the faceplate.
Rack Labeling
1.
F.
All faceplates shall be labeled with the Horizontal Cross Connect and Faceplate Number.
The faceplate number shall be derived based on the room in which the faceplate is
located, and a sequential number, e.g. TR01-138-01, where TR01 is the
Telecommunications Room, 138 is the room number of the location of the faceplate and
01 indicates that this is the first faceplate in the room.
The label shall be permanently affixed to the faceplate in a location specifically
engineered by the manufacturer to contain such information, or shall be neatly engraved
directly on the faceplate and painted to facilitate easy recognition of the information.
The individual jack positions shall be identified with sequential letters, either by means of
a pre-manufactured engraving or molding, or by installation of a machine generated label
installed in a location specifically designed to hold such a label.
Patch Panel Labeling
1.
2.
E.
Each Horizontal Cross Connect shall contain a lexan covered copy of the floor plan(s)
associated with the work area outlets serviced by the Cross Connect.
The size of the plans shall be equal to the size of the Contract Drawings, unless Contract
Drawings exceed 30” x 42”, in which case half size prints are to be utilized.
The plans shall be affixed by means of compression between the lexan cover and the
backboard to which it is mounted. The Contractor shall make provisions to assure that
the plans cannot accidentally fall from behind the lexan.
For cross connect locations that are smaller than TIA standard locations, half size plans
shall be permitted.
The Contractor shall utilize the final set of Record Drawings when providing these plans.
Faceplate Labeling
1.
2.
D.
As previously indicated, all electronic documentation shall be recorded onto a readable
CD. All files contained on the CD shall be in the native format of the software in which it
was generated, as well as a plain text format.
Work Area Floor Plans
1.
C.
FOR: ___________
ISSUED: 03/29/2017
All racks shall be labeled as to the identity of the device indicated on the Drawings. The
label shall be made of plastic laminate and attached at the center of the front top rail of
the rack and shall be visible from eye level.
UTP Cable Labeling
SECURITY ACCESS CONTROL
28 1000 - 10
NORTHWESTERN UNIVERSITY
PROJECT NAME ____________
JOB # ________
1.
2.
3.4
FOR: ___________
ISSUED: 03/29/2017
All UTP cables shall be marked at both ends of the cable jacket, at approximately 2” from
the end of the sheath, with a self adhesive label.
The label shall have the exact location of the point of service, i.e. the TR, rack or block
FIELD QUALITY CONTROL
A.
Site Test, Inspection
1.
2.
3.
4.
5.
The Engineer retains the right to be present at any or all cable certification. The
Contractor shall provide written notice 48 hours prior to the beginning of the certification
process.
The Contractor shall provide a copy of the unaltered certification test reports to the
Engineer in both hardcopy and electronic format. The Contractor shall also provide a
copy of the associated Cable Tester’s Database Management Software with unedited
soft copy.
Independent System Certified testing may be required, at the discretion of the Engineer,
provided at the expense of the Contractor, in the event of non-performance of the
specified testing procedures, submittals and/or installation procedures.
The extent and logistics of the independent testing shall be arranged by the Engineer.
Copper Cabling
a.
Upon completion of the cable installation, the Contractor shall perform complete
copper cable certification tests on every cable, included but not limited to:
1)
For Category 3 Cabling and higher:
a)
b)
c)
d)
2)
For Category 6a Cabling, additional tests shall be:
a)
b)
c)
d)
e)
f)
b.
c.
d.
e.
f.
g.
Wire Map
Length
Attenuation
Near End Cross Talk (NEXT)
Equal Level Far End Cross Talk (ELFEXT)
Propagation Delay and Delay Skew
Return Loss
Power Sum Near End Cross Talk (PSNEXT)
Power Sum Equal Level Far End Cross Talk (PSELFEXT)
Insertion Loss
Test shall be performed to published standards, including but not limited to, the
latest revisions of EIA/TIA 568, ISO/IEC 11802 and other applicable standards at
the time of installation.
All tests shall be performed with a certified Level lll UTP test device.
All UTP field tester shall be factory calibrated each calendar year by the field test
equipment manufacturer as stipulated by the manuals provided with the field test
unit. The calibration certificate shall be provided to the Engineer for review prior to
the start of testing.
New test leads and/or calibration of testing instruments shall be provided at the
beginning of each project.
Autotest settings provided in the field tester for testing the installed cabling shall be
set to the default parameters.
Test settings from options provided in the field testers shall be compatible with
SECURITY ACCESS CONTROL
28 1000 - 11
NORTHWESTERN UNIVERSITY
PROJECT NAME ____________
JOB # ________
3.5
FOR: ___________
ISSUED: 03/29/2017
CLEANING
A.
3.6
All equipment and Materials furnish, installed or provided shall be cleaned of all debris
construction or otherwise prior to Owner final Acceptance.
DEMONSTRATION
A.
3.7
Upon completion of all installation, termination and testing, the Contractor shall review the entire
installation with NUIT. At the time of this review, the Contractor shall present the hard copies of
all unadulterated test results.
PROTECTION
A.
The Contractor shall protect all aspects of the cabling system from damage during the time
period from the notice to proceed through the point of Owner Acceptance
END OF SECTION 28 1000
SECURITY ACCESS CONTROL
28 1000 - 12
NORTHWESTERN UNIVERSITY
PROJECT NAME ____________
JOB # ________
FOR: ___________
ISSUED: 03/29/2017
SECTION 28 3113 - DIGITAL ADDRESSABLE FIRE DETECTION AND ALARM SYSTEM
PART 1 - GENERAL
1.1
RELATED DOCUMENTS
A.
Drawings and general provisions of the Contract, including General and Supplementary
Conditions and Division 01 Specification Sections, apply to this Section.
B.
Related Sections include the following:
1.
2.
3.
C.
1.2
Division 21 Sections: Automatic Sprinkler Systems, Clean Agent Systems, and Chemical
Suppression systems.
Division 23 Sections: HVAC systems.
Division 25 section: Integrated Automation.
(Future use).
SUMMARY
A.
Section Includes: (edit for project requirements)
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
14.
15.
16.
17.
18.
B.
Related Requirements:
1.
1.3
Fire-alarm control unit.
Manual fire-alarm boxes.
System smoke detectors.
Heat detectors.
Carbon Monoxide detectors
Notification appliances.
Device guards.
Firefighters' two-way telephone communication service.
Firefighters' smoke-control station.
Magnetic door holders.
Remote annunciator.
Campus Wide Emergency Communication System
Graphical annunciator workstation.
Addressable interface device.
Digital alarm communicator transmitter.
Radio alarm transmitter.
Network communications.
System printer.
(For future use).
DEFINITIONS
A.
EMT: Electrical Metallic Tubing.
DIGITAL ADDRESSABLE FIRE DETECTION AND ALARM SYSTEM
28 3113 - 1
NORTHWESTERN UNIVERSITY
PROJECT NAME ____________
JOB # ________
FOR: ___________
ISSUED: 03/29/2017
B.
FACP: Fire Alarm Control Panel.
C.
NICET: National Institute for Certification in Engineering Technologies.
D.
PC: Personal computer.
1.4
ACTION SUBMITTALS
A.
The fire detection and alarm system shall comply with these specifications and all applicable
Codes and Standards. Acceptance of a submittal does not exempt the Contractor from full
compliance with the contract documents.
B.
Product Data: For each type of product, including furnished options and accessories.
1.
2.
C.
Include construction details, material descriptions, dimensions, profiles, and finishes.
Include rated capacities, operating characteristics, and electrical characteristics.
Shop Drawings: For fire-alarm system.
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
Comply with recommendations and requirements in the "Documentation" section of the
"Fundamentals" chapter in NFPA 72.
Include plans, elevations, sections, details, and attachments to other work.
Include details of equipment assemblies. Indicate dimensions, weights, loads, required
clearances, method of field assembly, components, and locations. Indicate conductor
sizes, indicate termination locations and requirements, and distinguish between factory
and field wiring.
Detail assembly and support requirements.
Include voltage drop calculations for notification-appliance circuits.
Include battery-size calculations.
Include input/output matrix.
Include statement from manufacturer that all equipment and components have been
tested as a system and meet all requirements in this Specification and in NFPA 72.
Include performance parameters and installation details for each detector.
Verify that each duct detector is listed for complete range of air velocity, temperature, and
humidity possible when air-handling system is operating.
Include plans, sections, and elevations of heating, ventilating, and air-conditioning ducts,
drawn to scale; coordinate location of duct smoke detectors and access to them.
a.
b.
c.
d.
e.
12.
13.
D.
Show critical dimensions that relate to placement and support of sampling tubes,
detector housing, and remote status and alarm indicators.
Show field wiring required for HVAC unit shutdown on alarm.
Show field wiring and equipment required for HVAC unit shutdown on alarm and
override by firefighters' control system.
Show field wiring and equipment required for HVAC unit shutdown on alarm and
override by firefighters' smoke-evacuation system.
Locate detectors according to manufacturer's written recommendations.
Include voice/alarm signaling-service equipment rack or console layout, grounding
schematic, amplifier power calculation, and single-line connection diagram.
Include floor plans to indicate final outlet locations showing address of each addressable
device. Show size and route of cable and conduits and point-to-point wiring diagrams.
General Submittal Requirements:
DIGITAL ADDRESSABLE FIRE DETECTION AND ALARM SYSTEM
28 3113 - 2
NORTHWESTERN UNIVERSITY
PROJECT NAME ____________
JOB # ________
1.
2.
Submittals shall be approved by authorities having jurisdiction prior to submitting them to
Architect.
Shop Drawings shall be prepared by persons with the following qualifications:
a.
b.
c.
E.
Trained and certified by manufacturer in fire-alarm system design.
NICET-certified, fire-alarm technician; Level IV minimum.
Licensed or certified by authorities having jurisdiction.
Delegated-Design Submittal: For notification appliances and smoke and heat detectors, in
addition to submittals listed above, indicate compliance with performance requirements and
design criteria, including analysis data signed and sealed by a qualified professional engineer
registered in the State of Illinois and responsible for their preparation.
1.
2.
3.
1.5
FOR: ___________
ISSUED: 03/29/2017
Drawings showing the location of each notification appliance and smoke and heat
detector, ratings of each, and installation details as needed to comply with listing
conditions of the device.
Design Calculations: Calculate requirements for selecting the spacing and sensitivity of
detection, complying with NFPA 72. Calculate spacing and intensities for strobe signals
and sound-pressure levels for audible appliances.
Indicate audible appliances required to produce square wave signal per NFPA 72.
INFORMATIONAL SUBMITTALS
A.
Qualification Data: For Installer.
B.
Field quality-control reports.
1.6
Sample Warranty: For special warranty.
1.7
CLOSEOUT SUBMITTALS
A.
Operation and Maintenance Data: For fire-alarm systems and components to include in
emergency, operation, and maintenance manuals.
1.
In addition to items specified in Division 1 Section "Operation and Maintenance Data,"
include the following and deliver copies to authorities having jurisdiction:
a.
b.
c.
d.
Comply with the "Records" section of the "Inspection, Testing and Maintenance"
chapter in NFPA 72.
Provide "Fire Alarm and Emergency Communications System Record of
Completion Documents" according to the "Completion Documents" Article in the
"Documentation" section of the "Fundamentals" chapter in NFPA 72.
As-built drawings shall be provided before acceptance of the work and final
payment. The As-Built drawings shall be prepared in AutoCAD format. A
reproducible set and four (4) copies are required. Submit a CDROM copy of all
CAD files in addition to the drawings. File format shall be suitable for use with Auto
Cad. Confirm the revision requirements with the Northwestern University Project
Manager.
The As-Built drawings shall locate as a minimum the following: FACP,
annunciators, initiating devices, notification devices, suppression systems, power
supplies.
DIGITAL ADDRESSABLE FIRE DETECTION AND ALARM SYSTEM
28 3113 - 3
NORTHWESTERN UNIVERSITY
PROJECT NAME ____________
JOB # ________
e.
f.
g.
h.
i.
Complete wiring diagrams showing connections between all devices and
equipment. Each conductor shall be numbered at every junction point with
indication of origination and termination points.
Riser diagram.
Device addresses.
Record copy of site-specific software.
Provide "Inspection and Testing Form" according to the "Inspection, Testing and
Maintenance" chapter in NFPA 72, and include the following:
1)
2)
3)
4)
5)
j.
k.
B.
Equipment tested.
Frequency of testing of installed components.
Frequency of inspection of installed components.
Requirements and recommendations related to results of maintenance.
Manufacturer's user training manuals.
Manufacturer's required maintenance related to system warranty requirements.
Abbreviated operating instructions for mounting at fire-alarm control unit and each
annunciator unit.
Software and Firmware Operational Documentation:
1.
2.
3.
4.
1.8
FOR: ___________
ISSUED: 03/29/2017
Software operating and upgrade manuals.
Program Software Backup: On magnetic media or compact disk, complete with data files.
Device address list.
Printout of software application and graphic screens.
MAINTENANCE MATERIAL SUBMITTALS
A.
Furnish extra materials that match products installed and that are packaged with protective
covering for storage and identified with labels describing contents. The spare parts shall be
turned over to Northwestern University’s Supervising Electrician and receipt acknowledging this
shall be required before final payment to contractor.
1.
2.
3.
4.
5.
6.
7.
1.9
Lamps for Remote Indicating Lamp Units: Quantity equal to 10 percent of amount
installed, but no less than one unit.
Lamps for Strobe Units: Quantity equal to 10 percent of amount installed, but no less
than one unit.
Smoke Detectors, Fire Detectors: Quantity equal to 10 percent of amount of each type
installed, but no less than one unit of each type.
Detector Bases: Quantity equal to two percent of amount of each type installed, but no
less than one unit of each type.
Keys and Tools: One extra set for access to locked or tamper-proofed components.
Audible and Visual Notification Appliances: One of each type installed.
Fuses: Two of each type installed in the system. Provide in a box or cabinet with
compartments marked with fuse types and sizes.
QUALITY ASSURANCE
A.
The installation shall be performed by a company specializing in installing the products specified
in this Section with a minimum of five years of experience, and certified by the State of Illinois
as fire alarm installers.
DIGITAL ADDRESSABLE FIRE DETECTION AND ALARM SYSTEM
28 3113 - 4
NORTHWESTERN UNIVERSITY
PROJECT NAME ____________
JOB # ________
FOR: ___________
ISSUED: 03/29/2017
B.
Installer Qualifications: Personnel shall be trained and certified by manufacturer for installation
of units required for this Project.
C.
Installer Qualifications: Installation shall be by personnel certified by NICET as fire-alarm
Level IV technician.
D.
NFPA Certification: Obtain certification according to NFPA 72 by a UL-listed alarm company.
E.
NFPA Certification: Obtain certification according to NFPA 72 by [City of Chicago] [City of
Evanston].
F.
Each and all items of the fire alarm system shall be listed as a product of a single fire alarm
system manufacturer under the appropriate category by Underwriters’ Laboratories, Inc. (UL),
and shall bear the “U.L.” label. Partial listings, or multiple listings for various major sections of
the control, shall not be acceptable.
G.
Comply with FM Global requirements.
H.
Comply with most current edition of the Northwestern University Design Standards.
1.10
PROJECT CONDITIONS (Edit For Project Requirements)
A.
[Perform a full test of the existing fire alarm system prior to starting work. Document any
equipment or components not functioning as designed.]
B.
[Interruption of Existing Fire-Alarm Service: Do not interrupt fire-alarm service to
facilities occupied by the University or others unless permitted under the following
conditions and then only after arranging to provide temporary guard service according
to requirements indicated:
1.
2.
Notify the University no fewer than ten (10) days in advance of proposed
interruption of fire-alarm service.
Do not proceed with interruption of fire-alarm service without the University's
written permission.]
C.
[Prior to performing any work which may impair any portion of an on line fire alarm
system equipment or components the contractor must submit a request for system
shutdown to the University’s project manager. The contractor must inform the
University of the specific location affected and list the circuits which may be inoperable
during the outage and the length of time the system will be impaired.]
D.
[Demolition of existing equipment should begin by the fire alarm contractor
disconnecting the existing circuits at the control panels, terminal cans or junction boxes
as appropriate and rerouting any active circuits around the construction area utilizing
the previously installed temporary wiring.]
E.
[Existing Fire-Alarm Equipment: Maintain existing equipment fully operational until new
equipment has been tested and accepted. As new equipment is installed, label it "NOT IN
SERVICE" until it is accepted. Remove labels from new equipment when put into service,
and label existing fire-alarm equipment "NOT IN SERVICE" until removed from the
building.]
DIGITAL ADDRESSABLE FIRE DETECTION AND ALARM SYSTEM
28 3113 - 5
NORTHWESTERN UNIVERSITY
PROJECT NAME ____________
JOB # ________
FOR: ___________
ISSUED: 03/29/2017
F.
[Equipment Removal: After acceptance of new fire-alarm system, remove existing
disconnected fire-alarm equipment and wiring.]
G.
[Use of Devices during Construction: Protect devices with factory supplied covers
during construction unless devices are placed in service to protect the facility during
construction.]
1.11
WARRANTY
A.
Comply with Division 1 requirements.
B.
Special Warranty: Manufacturer agrees to repair or replace fire-alarm system equipment and
components that fail in materials or workmanship within specified warranty period.
1.
2.
3.
Warranty Extent: All equipment and components not covered in the Maintenance Service
Agreement.
Warranty Period: Five years from date of Substantial Completion.
This warranty shall include a 4 hour response to emergency service calls, parts and
labor, and maintenance per all applicable NFPA codes and the City of [Evanston]
[Chicago] Mandates.
PART 2 - PRODUCTS
2.1
MANUFACTURERS
A.
Basis-of-Design Product: Subject to compliance with requirements, provide products by one of
the following:
1.
2.
Chicago: Siemens – Fire Safety.
Evanston: Simplex (Tyco-Grinnell).
B.
For existing building systems, match existing system.
C.
Being listed as an acceptable Manufacturer in no way relieves obligation of the Contractor to
provide all equipment and features in accordance with these specifications.
2.2
SYSTEM DESCRIPTION
A.
The fire alarm system shall comply with these specifications and all applicable codes.
Acceptance of the fire alarm system submittal does not exempt the contractor from full
compliance with the contract documents.
B.
Source Limitations for Fire-Alarm System and Components: Components shall be compatible
with, and operate as an extension of, existing system. Provide system manufacturer's
certification that all components provided have been tested as, and will operate as, a system.
C.
Non-coded, UL listed, addressable system, with multiplexed signal transmission and [voice]
[horn] [strobe] evacuation. Class I and Class II and equipment must be City of Chicago
approved for use in the alarm system class being installed.
D.
Automatic sensitivity control of certain smoke detectors.
DIGITAL ADDRESSABLE FIRE DETECTION AND ALARM SYSTEM
28 3113 - 6
NORTHWESTERN UNIVERSITY
PROJECT NAME ____________
JOB # ________
FOR: ___________
ISSUED: 03/29/2017
E.
All components provided shall be listed for use with the selected system.
F.
Electrical Components, Devices, and Accessories: Listed and labeled as defined in NFPA 70,
by a qualified testing agency, and marked for intended location and application.
2.3
SYSTEMS OPERATIONAL DESCRIPTION (Edit For Project Requirements)
A.
Fire-alarm signal initiation shall be by one or more of the following devices and systems:
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
B.
Fire-alarm signal shall initiate the following actions:
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
14.
15.
16.
17.
18.
19.
C.
Manual stations.
Heat detectors.
Smoke detectors.
Duct smoke detectors.
Carbon monoxide detectors.
Automatic sprinkler system water flow.
Pre-action system.
Fire-extinguishing system operation.
Fire standpipe system.
Dry system pressure flow switch.
Fire pump running.
<Insert alarm-initiating devices and systems>.
Continuously operate alarm notification appliances, including voice evacuation notices.
Identify alarm and specific initiating device at fire-alarm control unit, connected network
control panels, off-premises network control panels, and remote annunciators.
Transmit an alarm signal to the remote alarm receiving station.
Unlock electric door locks in designated egress paths.
Release fire and smoke doors held open by magnetic door holders.
Activate voice/alarm communication system.
Switch heating, ventilating, and air-conditioning equipment controls to fire-alarm mode.
Activate smoke-control system (smoke management) at firefighters' smoke-control
system panel.
Activate stairwell and elevator-shaft pressurization systems.
Close smoke dampers in air ducts of designated air-conditioning duct systems.
Activate pre-action system.
Recall elevators to primary or alternate recall floors.
Activate elevator power shunt trip.
Activate emergency lighting control.
Activate emergency shutoffs for gas and fuel supplies.
Record events in the system memory.
Record events by the system printer.
Indicate device in alarm on the graphic annunciator.
<Insert signal-initiating actions>.
Supervisory signal initiation shall be by one or more of the following devices and actions:
1.
2.
3.
4.
5.
Valve supervisory switch (for Chicago report to Valve Supervisory Control Panel).
High- or low-air-pressure switch of a dry-pipe or pre-action sprinkler system.
Duct smoke detector.
Elevator shunt-trip supervision.
Fire pump running. (for Chicago report to Valve Supervisory Control Panel)
DIGITAL ADDRESSABLE FIRE DETECTION AND ALARM SYSTEM
28 3113 - 7
NORTHWESTERN UNIVERSITY
PROJECT NAME ____________
JOB # ________
6.
7.
8.
9.
10.
11.
12.
13.
D.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
Open circuits, shorts, and grounds in designated circuits.
Opening, tampering with, or removing alarm-initiating and supervisory signal-initiating
devices. (for Chicago Tamper Switches report to Valve Supervisory Control Panel)
Loss of communication with any addressable sensor, input module, relay, control module,
remote annunciator, printer interface, or Ethernet module.
Loss of primary power at fire-alarm control unit.
Ground or a single break in internal circuits of fire-alarm control unit.
Abnormal AC voltage at fire-alarm control unit.
Break in standby battery circuitry.
Failure of battery charging.
Abnormal position of any switch at fire-alarm control unit or annunciator.
Voice signal amplifier failure.
Hose cabinet door open.
<Insert trouble signal-initiating devices and actions>.
System Supervisory Signal Actions:
1.
2.
3.
4.
5.
6.
2.4
Fire-pump loss of power. (for Chicago report to Valve Supervisory Control Panel)
Fire-pump power phase reversal. (for Chicago report to Valve Supervisory Control
Panel)
Engine-generator running. (for Chicago report to Valve Supervisory Control Panel)
Engine-generator loss of power. (for Chicago report to Valve Supervisory Control
Panel)
Independent fire-detection and -suppression systems.
User disabling of zones or individual devices.
Loss of communication with any panel on the network.
<Insert supervisory signal-initiating devices and actions>.
System trouble signal initiation shall be by one or more of the following devices and actions:
1.
2.
E.
FOR: ___________
ISSUED: 03/29/2017
Initiate notification appliances.
Identify specific device initiating the event at fire-alarm control unit, connected network
control panels, off-premises network control panels, and remote annunciators.
Record the event on system printer.
After a time delay of <Insert time delay>, transmit a trouble or supervisory signal to the
remote alarm receiving station.
Transmit system status to building management system.
Display system status at the graphic annunciator workstation.
(Future use)
A.
.
1.
2.5
.
FIRE-ALARM CONTROL PANEL (Edit For Project Requirements)
A.
General Requirements for Fire-Alarm Control Panel:
1.
Field-programmable, microprocessor-based,
electronic modules, complying with UL 864.
modular,
DIGITAL ADDRESSABLE FIRE DETECTION AND ALARM SYSTEM
power-limited
design
with
28 3113 - 8
NORTHWESTERN UNIVERSITY
PROJECT NAME ____________
JOB # ________
a.
b.
c.
d.
e.
f.
2.
3.
B.
Addressable Initiation Device Circuits: The FACP shall indicate which communication
zones have been silenced and shall provide selective silencing of alarm notification
appliance by building communication zone.
Addressable Control Circuits for Operation of Notification Appliances and Mechanical
Equipment: The FACP shall be listed for releasing service.
Annunciator and Display: LCD type, [80] <Insert number> characters, minimum.
Keypad: Arranged to permit entry and execution of programming, display, and control
commands.
Alphanumeric Display and System Controls: Arranged for interface between human operator at
fire-alarm control unit and addressable system components including annunciation and
supervision. Display alarm, supervisory, and component status messages and the programming
and control menu.
1.
2.
D.
System software and programs shall be held in nonvolatile flash, electrically
erasable, programmable, read-only memory, retaining the information through
failure of primary and secondary power supplies.
Include a real-time clock for time annotation of events on the event recorder and
printer.
Provide communication between the FACP and remote circuit interface panels,
annunciators, and displays.
The FACP shall be listed for connection to a central-station signaling system
service.
Provide nonvolatile memory for system database, logic, and operating system and
event history. The system shall require no manual input to initialize in the event of
a complete power down condition. The FACP shall provide a minimum 500-event
history log.
Spare capacity for 25% additional addressable points.
Alphanumeric Display and System Controls: Arranged for interface between human operator at
fire-alarm control unit and addressable system components including annunciation and
supervision. Display alarm, supervisory, and component status messages and the programming
and control menu.
1.
2.
C.
FOR: ___________
ISSUED: 03/29/2017
Annunciator and Display: LCD type, [two] [three] line(s) of [40] [80] <Insert number>
characters, minimum.
Keypad: Arranged to permit entry and execution of programming, display, and control
commands [and to indicate control commands to be entered into the system for
control of smoke-detector sensitivity and other parameters].
Initiating-Device, Notification-Appliance, and Signaling-Line Circuits:
1.
2.
3.
4.
5.
Pathway Class Designations: NFPA 72, [Class A] [Class B] [Class C] [Class D]
[Class E].
Pathway Survivability: [Level 0] [Level 1].
Install no more than [50] [100] [256] <Insert number> addressable devices on each
signaling-line circuit.
Initiating circuits and notification circuits to be designed with 25 percent spare capacity.
Serial Interfaces:
a.
One dedicated RS 485 port for [central-station] [remote station] operation using
point ID DACT.
DIGITAL ADDRESSABLE FIRE DETECTION AND ALARM SYSTEM
28 3113 - 9
NORTHWESTERN UNIVERSITY
PROJECT NAME ____________
JOB # ________
b.
c.
d.
E.
2.
3.
4.
5.
Initiate audible and visible indication of an "alarm-verification" signal at fire-alarm control
unit.
Activate an approved "alarm-verification" sequence at fire-alarm control unit and detector.
Record events by the system printer.
Sound general alarm if the alarm is verified.
Cancel fire-alarm control unit indication and system reset if the alarm is not verified.
Notification-Appliance Circuit:
1.
2.
3.
H.
Pressurization starts when any alarm is received at fire-alarm control unit.
Alarm signals from smoke detectors at pressurization air supplies have a higher priority
than other alarm signals that start the system.
Smoke-Alarm Verification:
1.
G.
One RS 485 port for remote annunciators, Ethernet module, or multi-interface
module (printer port).
One [USB] [RS 232] port for PC configuration.
One RS 232 port for voice evacuation interface.
Stairwell [and Elevator Shaft] Pressurization: Provide an output signal using an addressable
relay to start the stairwell [and elevator shaft] pressurization system. Signal shall remain on
until alarm conditions are cleared and fire-alarm system is reset. Signal shall not stop in
response to alarm acknowledge or signal silence commands.
1.
2.
F.
FOR: ___________
ISSUED: 03/29/2017
Audible appliances shall sound in a three-pulse temporal pattern, as defined in NFPA 72.
Where notification appliances provide signals to sleeping areas, the alarm signal shall be
a 520-Hz square wave with an intensity 15 dB above the average ambient sound level or
5-dB above the maximum sound level, or at least 75-dBA, whichever is greater,
measured at the pillow.
Visual alarm appliances shall flash in synchronization where multiple appliances are in
the same field of view, as defined in NFPA 72.
Elevator Recall:
1.
Elevator recall shall be initiated only by one of the following alarm-initiating devices:
a.
b.
c.
2.
3.
Elevator lobby detectors except the lobby detector on the designated floor.
Smoke detector in elevator machine room.
Smoke detectors in elevator hoistway.
Elevator controller shall be programmed to move the cars to the alternate recall floor if
lobby detectors located on the designated recall floors are activated.
Water-flow alarm connected to sprinkler in an elevator shaft and elevator machine room
shall shut down elevators associated with the location without time delay.
a.
Water-flow switch associated with the sprinkler in the elevator pit may have a delay
to allow elevators to move to the designated floor.
I.
Door Controls: Door hold-open devices that are controlled by smoke detectors at doors in
smoke-barrier walls shall be connected to fire-alarm system.
J.
Remote Smoke-Detector Sensitivity Adjustment: Controls shall select specific addressable
smoke detectors for adjustment, display their current status and sensitivity settings, and change
DIGITAL ADDRESSABLE FIRE DETECTION AND ALARM SYSTEM
28 3113 - 10
NORTHWESTERN UNIVERSITY
PROJECT NAME ____________
JOB # ________
FOR: ___________
ISSUED: 03/29/2017
those settings. Allow controls to be used to program repetitive, time-scheduled, and automated
changes in sensitivity of specific detector groups. Record sensitivity adjustments and sensitivityadjustment schedule changes in system memory, and print out the final adjusted values on
system printer.
K.
Transmission to Remote Alarm Receiving Station: Automatically transmit alarm, supervisory,
and trouble signals to a remote alarm station.
L.
Voice/Alarm Signaling Service: Central emergency communication system with redundant
microphones, preamplifiers, amplifiers, and tone generators provided [in a separate cabinet
located in the fire command center] [as a special module that is part of fire-alarm control
unit].
1.
Indicate number of alarm channels for automatic, simultaneous transmission of different
announcements to different zones or for manual transmission of announcements by use
of the central-control microphone. Amplifiers shall comply with UL 1711.
a.
b.
c.
d.
2.
3.
Allow the application of, and evacuation signal to, indicated number of zones and,
at the same time, allow voice paging to the other zones selectively or in any
combination.
Programmable tone and message sequence selection.
Standard digitally recorded messages shall be University's standard messages
and must be reviewed and approved by the University before recording. Finished
voice messages shall be installed and tested prior to building occupancy and final
acceptance testing of the system.
Generate tones to be sequenced with audio messages of type recommended by
NFPA 72 and that are compatible with tone patterns of notification-appliance
circuits of fire-alarm control unit.
Status Annunciator: Indicate the status of various voice/alarm speaker zones and the
status of firefighters' two-way telephone communication zones.
Preamplifiers, amplifiers, and tone generators shall automatically transfer to backup units,
on primary equipment failure.
M.
Printout of Events: On receipt of signal, print alarm, supervisory, and trouble events. Identify
zone, device, and function. Include type of signal (alarm, supervisory, or trouble) and date and
time of occurrence. Differentiate alarm signals from all other printed indications. Also print
system reset event, including same information for device, location, date, and time. Commands
initiate the printing of a list of existing alarm, supervisory, and trouble conditions in the system
and a historical log of events.
N.
Power Requirements: The system shall support 100% of addressable devices in alarm or
operated at the same time, under both primary (AC) and secondary (battery) power conditions.
O.
Primary Power: 24-V dc obtained from a dedicated 120-V ac essential power system service
and a power-supply module. Initiating devices, notification appliances, signaling lines, trouble
signals, [supervisory signals] [supervisory and digital alarm communicator transmitters]
[and] [digital alarm radio transmitters] shall be powered by 24-V dc source.
1.
2.
Size the control panel power supplies for 25 percent spare capacity of the calculated
load.
Alarm current draw of entire fire-alarm system shall not exceed 80 percent of the powersupply module rating.
DIGITAL ADDRESSABLE FIRE DETECTION AND ALARM SYSTEM
28 3113 - 11
NORTHWESTERN UNIVERSITY
PROJECT NAME ____________
JOB # ________
P.
Secondary Power: 24-V dc supply system with batteries, automatic battery charger, and
automatic transfer switch.
1.
2.
3.
Q.
Batteries: Rechargeable, low maintenance, sealed lead acid; Lead Calcium grid structure
with immobilized electrolyte in an absorbent separator. UL 924 recognized pressure relief
valves.
Rated for four (4) hours operation in normal supervisory mode and then 15 minutes of
alarm operation.
Provide 25% spare capacity for future growth.
Supplemental Notification and Remote User Access (Fire Panel Internet Interface).
1.
2.
3.
4.
2.6
FOR: ___________
ISSUED: 03/29/2017
Fire Alarm Control Panel (FACP) shall have the capability to provide supplemental
notification and remote user access to the FACP using Ethernet and TCP/IP
communications protocol compatible with IEEE Standard 802.3.
A standard RJ-45 Ethernet connection shall connect to the owners Ethernet network.
Provisions for that connection must be provided at each fire alarm control unit as part of
the contract.
The means of providing supplemental email and SMS text messaging notification shall be
agency listed for specific interfaces and for the purpose described in this section. The use
of non-listed external third party products and interfaces is not acceptable.
The fire panel internet interface shall be capable of sending automated notification of
discrete system events via email and SMS text messaging to up to 50 individual user
accounts and via email to up to 5 distribution list.
PRE-ACTION SYSTEM
A.
2.7
Initiate Pre-signal Alarm: This function shall cause an audible and visual alarm and indication to
be provided at the FACP. Activation of an initiation device connected as part of a pre-action
system shall be annunciated at the FACP only, without activation of the general evacuation
alarm.
MANUAL FIRE-ALARM BOXES
A.
General Requirements for Manual Fire-Alarm Boxes: Comply with UL 38. Boxes shall be
finished in red with molded, raised-letter operating instructions in contrasting color; shall show
visible indication of operation; and shall be mounted on recessed outlet box. If indicated as
surface mounted, provide manufacturer's surface back box.
1.
2.
3.
4.
Double-action mechanism requiring two actions to initiate an alarm - pull up then down
(breaking-glass or plastic-rod not permitted) type; with integral addressable module
arranged to communicate manual-station status (normal, alarm, or trouble) to fire-alarm
control unit.
Station Reset: Key- or wrench-operated switch.
[Indoor Protective Shield: Factory-fabricated, clear plastic enclosure hinged at the
top to permit lifting for access to initiate an alarm. Lifting the cover actuates an
integral battery-powered audible horn intended to discourage false-alarm
operation.]
[Weatherproof Protective Shield: Factory-fabricated, clear plastic enclosure hinged
at the top to permit lifting for access to initiate an alarm.]
DIGITAL ADDRESSABLE FIRE DETECTION AND ALARM SYSTEM
28 3113 - 12
NORTHWESTERN UNIVERSITY
PROJECT NAME ____________
JOB # ________
2.8
FOR: ___________
ISSUED: 03/29/2017
SYSTEM SMOKE DETECTORS
A.
General Requirements for System Smoke Detectors:
1.
2.
3.
4.
5.
6.
7.
Comply with UL 268; operating at 24-V dc, nominal.
Detectors shall be [four] [two]-wire type.
Integral Addressable Module: Arranged to communicate detector status (normal, alarm,
or trouble) to fire-alarm control unit.
Base Mounting: Detector and associated electronic components shall be mounted in a
twist-lock module that connects to a fixed base. Provide terminals in the fixed base for
connection to building wiring.
Self-Restoring: Detectors do not require resetting or readjustment after actuation to
restore them to normal operation.
Integral Visual-Indicating Light: LED type, indicating detector has operated and power-on
status.
Remote Control: Unless otherwise indicated, detectors shall be digital-addressable type,
individually monitored at fire-alarm control unit for calibration, sensitivity, and alarm
condition and individually adjustable for sensitivity by fire-alarm control unit.
a.
b.
c.
d.
B.
Photoelectric Smoke Detectors:
1.
2.
Detector address shall be accessible from fire-alarm control unit and shall be able to
identify the detector's location within the system and its sensitivity setting.
An operator at fire-alarm control unit, having the designated access level, shall be able to
manually access the following for each detector:
a.
b.
c.
d.
e.
C.
Rate-of-rise temperature characteristic of combination smoke- and heat-detection
units shall be selectable at fire-alarm control unit for 15 or 20 deg F (8 or 11 deg C)
per minute.
Fixed-temperature sensing characteristic of combination smoke- and heatdetection units shall be independent of rate-of-rise sensing and shall be settable at
fire-alarm control unit to operate at 135 or 155 deg F (57 or 68 deg C).
Multiple levels of detection sensitivity for each sensor.
Sensitivity levels based on time of day.
Primary status.
Device type.
Present average value.
Present sensitivity selected.
Sensor range (normal, dirty, etc.).
Ionization Smoke Detector:
1.
2.
Detector address shall be accessible from fire-alarm control unit and shall be able to
identify the detector's location within the system and its sensitivity setting.
An operator at fire-alarm control unit, having the designated access level, shall be able to
manually access the following for each detector:
a.
b.
c.
d.
e.
Primary status.
Device type.
Present average value.
Present sensitivity selected.
Sensor range (normal, dirty, etc.).
DIGITAL ADDRESSABLE FIRE DETECTION AND ALARM SYSTEM
28 3113 - 13
NORTHWESTERN UNIVERSITY
PROJECT NAME ____________
JOB # ________
D.
Duct Smoke Detectors: Photoelectric type complying with UL 268A.
1.
2.
Detector address shall be accessible from fire-alarm control unit and shall be able to
identify the detector's location within the system and its sensitivity setting.
An operator at fire-alarm control unit, having the designated access level, shall be able to
manually access the following for each detector:
a.
b.
c.
d.
e.
3.
4.
5.
6.
7.
2.9
FOR: ___________
ISSUED: 03/29/2017
Primary status.
Device type.
Present average value.
Present sensitivity selected.
Sensor range (normal, dirty, etc.).
Weatherproof Duct Housing Enclosure: NEMA 250, Type 4X; NRTL listed for use with the
supplied detector for smoke detection in HVAC system ducts.
Each sensor shall have multiple levels of detection sensitivity.
Sampling Tubes: Design and dimensions as recommended by manufacturer for specific
duct size, air velocity, and installation conditions where applied.
Relay Fan Shutdown: Fully programmable relay rated to interrupt fan motor-control
circuit.
All concealed duct mounted smoke detectors shall be provided with a remote indicator
device and test switch.
PROJECTED BEAM SMOKE DETECTORS
A.
Projected Beam Light Source and Receiver: Designed to accommodate small angular
movements and continue to operate and not cause nuisance alarms.
B.
Detector Address: Accessible from fire-alarm control unit and able to identify the detector's
location within the system and its sensitivity setting.
C.
An operator at fire-alarm control unit, having the designated access level, shall be able to
manually access the following for each detector:
1.
2.
3.
4.
5.
2.10
A.
Primary status.
Device type.
Present average value.
Present sensitivity selected.
Sensor range (normal, dirty, etc.).
CARBON MONOXIDE DETECTORS
General: Carbon monoxide detector listed for connection to fire-alarm system.
1.
2.
3.
4.
5.
6.
7.
8.
Mounting: Adapter plate for outlet box mounting.
Testable by introducing test carbon monoxide into the sensing cell.
Detector shall provide alarm contacts and trouble contacts.
Detector shall send trouble alarm when nearing end-of-life, power supply problems, or
internal faults.
Comply with UL 2075.
Locate, mount, and wire according to manufacturer's written instructions.
Provide means for addressable connection to fire-alarm system.
Test button simulates an alarm condition.
DIGITAL ADDRESSABLE FIRE DETECTION AND ALARM SYSTEM
28 3113 - 14
NORTHWESTERN UNIVERSITY
PROJECT NAME ____________
JOB # ________
2.11
A.
HEAT DETECTORS
General Requirements for Heat Detectors: Comply with UL 521.
1.
B.
2.
2.
A.
Mounting: [Adapter plate for outlet box mounting] [Twist-lock base interchangeable
with smoke-detector bases].
Integral Addressable Module: Arranged to communicate detector status (normal, alarm,
or trouble) to fire-alarm control unit.
Heat Detector, Fixed-Temperature Type: Actuated by temperature that exceeds a fixed
temperature of [190 deg F (88 deg C)/ other].
1.
2.12
Temperature sensors shall test for and communicate the sensitivity range of the device.
Heat Detector, Combination Type: Actuated by either a fixed temperature of [135 deg F (57
deg C)] or a rate of rise that exceeds [15 deg F (8 deg C)] per minute unless otherwise
indicated.
1.
C.
FOR: ___________
ISSUED: 03/29/2017
Mounting: [Adapter plate for outlet box mounting] [Twist-lock base interchangeable
with smoke-detector bases].
Integral Addressable Module: Arranged to communicate detector status (normal, alarm,
or trouble) to fire-alarm control unit.
NOTIFICATION APPLIANCES
General Requirements for Notification Appliances: Individually addressed, connected to a
signaling-line circuit, equipped for mounting as indicated, and with screw terminals for system
connections.
1.
2.
Combination Devices: Factory-integrated audible and visible devices in a single-mounting
assembly, equipped for mounting as indicated, and with screw terminals for system
connections.
Finishes: Chicago: RED, Evanston: RED or WHITE.
B.
Chimes, Low-Level Output: Vibrating type, 75-dBA minimum rated output.
C.
Chimes, High-Level Output: Vibrating type, 81-dBA minimum rated output.
D.
Horns: Electric-vibrating-polarized type, 24-V dc; with provision for housing the operating
mechanism behind a grille. Comply with UL 464. Horns shall produce a sound-pressure level of
90 dBA, measured 10 feet (3 m) from the horn, using the coded signal prescribed in UL 464 test
protocol.
E.
Visible Notification Appliances: Xenon strobe lights complying with UL 1971, with clear
polycarbonate lens mounted on an aluminum faceplate. The word "FIRE" is engraved in
minimum 1-inch- (25-mm-) high letters on the lens.
1.
Rated Light Output: (select a or b)
a.
b.
2.
[15] [30] [75] [110] [177] cd.
15/30/75/110 cd, selectable in the field.
Mounting: [Ceiling] [Wall] mounted as indicated.
DIGITAL ADDRESSABLE FIRE DETECTION AND ALARM SYSTEM
28 3113 - 15
NORTHWESTERN UNIVERSITY
PROJECT NAME ____________
JOB # ________
3.
4.
5.
6.
F.
3.
4.
5.
6.
7.
2.
3.
A.
Shall be rated for wet locations.
Exit Marking Audible Notification Appliance:
1.
2.13
Comply with UL 1480.
Speakers for Voice Notification: Locate speakers for voice notification to provide the
intelligibility requirements of the "Notification Appliances" and "Emergency
Communications Systems" chapters in NFPA 72.
High-Range Units: Rated 2 to 15 W.
Low-Range Units: Rated 1 to 2 W.
Mounting: [Flush] [semi recessed] [ceiling] [wall mounted].
Matching Transformers: Tap range matched to acoustical environment of speaker
location.
Mounting Faceplate: Factory finished red.
Outdoor Notification Devices:
1.
H.
For units with guards to prevent physical damage, light output ratings shall be determined
with guards in place.
Flashing shall be in a temporal pattern, synchronized with other units.
Strobe Leads: Factory connected to screw terminals.
Mounting Faceplate: Factory finished red.
Voice/Tone Notification Appliances:
1.
2.
G.
FOR: ___________
ISSUED: 03/29/2017
Exit marking audible notification appliances shall meet the audibility requirements in
NFPA 72.
Provide exit marking audible notification appliances at the entrance to all building exits.
Provide exit marking audible notification appliances at the entrance to areas of refuge
with audible signals distinct from those used for building exit marking.
FIREFIGHTERS' TWO-WAY TELEPHONE COMMUNICATION SERVICE
Dedicated, two-way, supervised, telephone voice communication links between fire-alarm
control panel, [ the fire command center,] and remote firefighters' telephone stations.
Supervised telephone lines shall be connected to talk circuits by controls in a control module.
Provide the following:
1.
2.
3.
4.
5.
6.
7.
Common-talk type for firefighter use only.
Selective-talk type for use by firefighters and fire wardens.
Controls to disconnect phones from talk circuits if too many phones are in use
simultaneously. An indicator lamp shall flash if a phone is disconnected from the talk
circuits.
Addressable firefighters' phone modules to monitor and control a loop of firefighter
phones. Module shall be capable of differentiating between normal, off-hook, and trouble
conditions.
Audible Pulse and Tone Generator, and High-Intensity Lamp: When a remote telephone
is taken off the hook, it causes an audible signal to sound and a high-intensity lamp to
flash at the [fire-alarm control panel] [fire command center].
Selector panel controls to provide for simultaneous operation of up to six telephones in
selected zones. Indicate ground faults and open or shorted telephone lines on the panel
front by individual LEDs.
Display: digital to indicate location of caller.
DIGITAL ADDRESSABLE FIRE DETECTION AND ALARM SYSTEM
28 3113 - 16
NORTHWESTERN UNIVERSITY
PROJECT NAME ____________
JOB # ________
8.
Remote Telephone Cabinet: Flush- or surface-mounted cabinet as indicated, factorystandard red finish, with handset.
a.
b.
9.
10.
2.14
A.
3.
4.
2.
3.
4.
A.
Provide address-setting means on the module. Store an internal identifying code for
control panel use to identify the module type.
Allow the control panel to switch the relay contacts on command.
Have a minimum of two normally open and two normally closed contacts available for
field wiring.
Listed for controlling HVAC fan motor controllers.
MAGNETIC DOOR HOLDERS
Description: Units are equipped for wall or floor mounting as indicated and are complete with
matching doorplate.
1.
2.
3.
4.
5.
2.16
Comply with sequence of operation as described in Division 23 Section "Sequence of
Operations for HVAC DDC."
Fire-alarm system shall provide all interfaces and control points required to properly
activate smoke-management systems.
First fire-alarm system initiating device to go into alarm condition shall activate the
smoke-control functions.
Subsequent devices going into alarm condition shall have no effect on the smoke-control
mode.
Addressable Relay Modules:
1.
A.
Remote Telephone Jack Stations: Single-gang, stainless-steel-plate mounted plug,
engraved [“Fire Warden Phone" or] "Fire Emergency Phone."
Handsets: <Insert number> [push-to-talk-type] sets [with noise-canceling
microphone] stored in a cabinet [adjacent to fire-alarm control unit] [in the fire
command center].
Initiate Smoke-Management Sequence of Operation:
2.
2.15
Install one-piece handset to cabinet with vandal-resistant armored cord. Silkscreened or engraved label on cabinet door, designating [“Fire Warden Phone"
or] "Fire Emergency Phone."
With "break-glass" type door access lock.
FIREFIGHTERS' SMOKE-CONTROL SYSTEM
1.
B.
FOR: ___________
ISSUED: 03/29/2017
Electromagnets: Require no more than 3 W to develop 25-lbf (111-N) holding force.
Wall-Mounted Units: Flush mounted unless otherwise indicated.
Material and Finish: Match door hardware.
Unit shall operate from a 24Vdc source.
Combination door closer/holder devices are not permitted.
WATER FLOW SWITCHES
Water flow switches shall be UL Listed for intended purpose; furnished mounted and adjusted
under Division 23 and connected under Division 26.
DIGITAL ADDRESSABLE FIRE DETECTION AND ALARM SYSTEM
28 3113 - 17
NORTHWESTERN UNIVERSITY
PROJECT NAME ____________
JOB # ________
2.17
A.
2.18
FOR: ___________
ISSUED: 03/29/2017
SPRINKLER VALVE TAMPER SWITCHES
Valve tamper switches shall be UL Listed for intended-purpose; furnished mounted and
adjusted under Division 23 and connected by Division 26. Valve tamper switches shall be
connected to the fire alarm system (for Chicago report to Valve Supervisory Control Panel)
by way of address reporting interface device.
CAMPUS WIDE EMERGENCY COMMUNICATION SYSTEM (ECS)
A.
The local Fire Alarm System shall interface with audio input from the ECS by means of one of
the following: Line level audio input (1 Volt Peak to Peak), 25v speaker circuit, and 70v speaker
circuit.
B.
Local fire alarm system shall be capable of receiving multiple contact closures or network
communications, at a minimum, for the following:
1.
2.
Initiating multiple digital voice messages as designated per Northwestern University
standards.
Transmitting a “LIVE” voice message or a digital pre-recorded message from the Campus
Wide System as directed by the event.
C.
In the event that the Local Building FA System has a fire event in progress and an ECS event is
received from the Campus Wide System, the ECS will take precedence over the Fire Alarm
event and will respond by either transmitting a “live” voice or a digital pre-recorded message
from the Campus Wide System as directed by the event.
D.
‘Alert’ notification appliances will illuminate during Fire/ECS events. Campus Wide System
Interface to local FACP panel shall be accomplished by FCP/VCP Fire Alarm Network panels
capable of one-way voice communications from the ECS to remote Campus Buildings utilizing
the University LAN/WAN network infrastructure.
E.
Minimum system requirements: FCP/VCP, Fiber modem(s) – Single Mode, Internal relays (8),
Amplifier. (Non-Compliant Fire Alarm panel requirements: Audio input module.)
2.19
GRAPHIC ANNUNCIATOR WORKSTATION (optional)
A.
[Graphic Annunciator Workstation: PC-based, with fire-alarm annunciator software with
historical logging, report generation, and a graphic interface showing all alarm points in
the system. PC with operating system software, two (2) minimum 500 GB hard drives,
minimum 23” digital display monitor, with wireless keyboard and mouse.]
B.
[Power supply: dedicated 120 V ac circuit with UPS for standby power supply. The UPS
system shall be comprised of a static inverter, a battery float charger, and sealed
maintenance free batteries. UPS system shall be sized to operate the central processor,
CRT, printer, and all other directly connected equipment for 10 minutes upon a normal
AC power failure.]
2.20
A.
REMOTE ANNUNCIATOR
Description: Annunciator functions shall match those of fire-alarm control unit for alarm,
supervisory, and trouble indications. Manual switching functions shall match those of fire-alarm
control unit, including acknowledging, silencing, resetting, and testing.
DIGITAL ADDRESSABLE FIRE DETECTION AND ALARM SYSTEM
28 3113 - 18
NORTHWESTERN UNIVERSITY
PROJECT NAME ____________
JOB # ________
1.
B.
2.21
A.
FOR: ___________
ISSUED: 03/29/2017
Mounting: [Flush] [Surface] cabinet, NEMA 250, Type 1.
Display Type and Functional Performance: Alphanumeric display and LED indicating lights shall
match those of fire-alarm control unit. Provide controls to acknowledge, silence, reset, and test
functions for alarm, supervisory, and trouble signals.
ADDRESSABLE INTERFACE DEVICE
General:
1.
2.
3.
Include address-setting means on the module.
Store an internal identifying code for control panel use to identify the module type.
Listed for controlling HVAC fan motor controllers.
B.
Monitor Module: Microelectronic module providing a system address for alarm-initiating devices
for wired applications with normally open contacts.
C.
Integral Relay: Capable of providing a direct signal [to elevator controller to initiate elevator
recall] [to circuit-breaker shunt trip for power shutdown] <Insert functions>.
1.
2.
D.
Control Module:
1.
2.
3.
2.22
Allow the control panel to switch the relay contacts on command.
Have a minimum of two normally open and two normally closed contacts available for
field wiring.
Operate notification devices.
Operate solenoids for use in sprinkler service.
<Insert other functions>.
DIGITAL ALARM COMMUNICATOR TRANSMITTER
A.
Digital alarm communicator transmitter shall be acceptable to the remote central station and
shall comply with UL 632.
B.
Functional Performance: Unit shall receive an alarm, supervisory, or trouble signal from firealarm control unit and automatically capture [one] [two] telephone line(s) and dial a preset
number for a remote central station. When contact is made with central station(s), signals shall
be transmitted. If service on either line is interrupted for longer than 45 seconds, transmitter
shall initiate a local trouble signal and transmit the signal indicating loss of telephone line to the
remote alarm receiving station over the remaining line. Transmitter shall automatically report
telephone service restoration to the central station. If service is lost on both telephone lines,
transmitter shall initiate the local trouble signal.
C.
Local functions and display at the digital alarm communicator transmitter shall include the
following:
1.
2.
3.
4.
5.
6.
Verification that both telephone lines are available.
Programming device.
LED display.
Manual test report function and manual transmission clear indication.
Communications failure with the central station or fire-alarm control unit.
<Insert local function>.
DIGITAL ADDRESSABLE FIRE DETECTION AND ALARM SYSTEM
28 3113 - 19
NORTHWESTERN UNIVERSITY
PROJECT NAME ____________
JOB # ________
D.
FOR: ___________
ISSUED: 03/29/2017
Digital data transmission shall include the following:
1.
2.
3.
4.
5.
6.
7.
8.
9.
Address of the alarm-initiating device.
Address of the supervisory signal.
Address of the trouble-initiating device.
Loss of ac supply.
Loss of power.
Low battery.
Abnormal test signal.
Communication bus failure.
<Insert signal to be transmitted>.
E.
Secondary Power: Integral rechargeable battery and automatic charger.
F.
Self-Test: Conducted automatically every 24 hours with report transmitted to central station.
2.23
[RADIO ALARM TRANSMITTER] (optional)
A.
[Transmitter shall comply with NFPA 1221 and 47 CFR 90.
B.
Description: Manufacturer's standard commercial product; factory assembled, wired, and
tested; ready for installation and operation.
1.
2.
3.
4.
5.
6.
7.
8.
C.
Packaging: A single, modular, NEMA 250, Type 1 metal enclosure with a tamperresistant flush tumbler lock.
Signal Transmission Mode and Frequency: VHF or UHF 2-W power output,
coordinated with operating characteristics of the established remote alarm
receiving station designated by Owner.
Normal Power Input: 120-V ac.
Secondary Power: Integral-sealed, rechargeable, 12-V battery and charger. Comply
with NFPA 72 requirements for battery capacity; submit calculations.
Antenna: Omni-directional, coaxial half-wave, dipole type with driving point
impedance matched to transmitter and antenna cable output impedance. Windload strength of antenna and mounting hardware and supports shall withstand
<Insert value mph> with a gust factor of 1.3 without failure.
Antenna Cable: Coaxial cable with impedance matched to the transmitter output
impedance.
Antenna-Cable Connectors: Weatherproof.
Alarm Interface Devices: Circuit boards, modules, and other auxiliary devices,
integral to the transmitter, matching fire-alarm and other system outputs to
message-generating inputs of the transmitter that produce required message
transmissions.
Functional Performance: Unit shall receive alarm, supervisory, or trouble signal from
fire-alarm control unit or from its own internal sensors or controls and shall
automatically transmit signal along with a unique code that identifies the transmitting
station to the remote alarm receiving station. Transmitted messages shall correspond to
standard designations for fire-reporting system to which the signal is being transmitted
and shall include separately designated messages in response to the following events or
conditions:
1.
Transmitter Low-Battery Condition: Sent when battery voltage is below 85 percent
of rated value.
DIGITAL ADDRESSABLE FIRE DETECTION AND ALARM SYSTEM
28 3113 - 20
NORTHWESTERN UNIVERSITY
PROJECT NAME ____________
JOB # ________
2.
3.
4.
5.
6.
2.24
FOR: ___________
ISSUED: 03/29/2017
System Test Message: Initiated manually by a test switch within the transmitter
cabinet, or automatically at an optionally preselected time, once every 24 hours,
with transmission time controlled by a programmed timing device integral to
transmitter controls.
Transmitter Trouble Message: Actuated by failure, in excess of one-minute
duration, of the transmitter normal power source, derangement of the wiring of the
transmitter, or any alarm input interface circuit or device connected to it.
Local Fire-Alarm-System Trouble Message: Initiated by events or conditions that
cause a trouble signal to be indicated on the building system.
Local Fire-Alarm-System Alarm Message: Actuated when the building system goes
into an alarm state. Identifies device that initiated the alarm.
Local Fire-Alarm-System, Supervisory-Alarm Message: [Actuated when the
building alarm system indicates a supervisory alarm] <Insert condition>.]
NETWORK COMMUNICATIONS
A.
Provide network communications for fire-alarm system according to fire-alarm manufacturer's
written requirements.
B.
Provide network communications per manufacturer's written requirements and requirements in
NFPA 72 and NFPA 70.
C.
Provide integration gateway using [BACnet] [Modbus] for connection to building automation
system.
2.25
CITY CONNECTION (Chicago)
A.
City key disconnect switch: to disconnect the fire alarm panel from reporting any alarm or
trouble condition to the city in order to test and maintain the fire alarm system.
B.
City tie trouble module: to silence and test city tie disconnect troubles.
C.
Fire Alarm trouble module: Fire Alarm Trouble Bell module used to silence and test the fire
alarm trouble bell.
D.
(Future use).
2.26
SYSTEM PRINTER
A.
Printer shall be listed and labeled to UL 864 as an integral part of fire-alarm system.
B.
Serial RS-232, USB, or parallel communications interface.
C.
Transient protection for AC input and RS-232.
2.27
A.
DEVICE GUARDS
Description: Welded wire mesh of size and shape for the manual station, smoke detector, gong,
or other device requiring protection.
1.
2.
Factory fabricated and furnished by device manufacturer.
Finish: Paint of color to match the protected device.
DIGITAL ADDRESSABLE FIRE DETECTION AND ALARM SYSTEM
28 3113 - 21
NORTHWESTERN UNIVERSITY
PROJECT NAME ____________
JOB # ________
FOR: ___________
ISSUED: 03/29/2017
PART 3 - EXECUTION
3.1
EXAMINATION
A.
Examine areas and conditions for compliance with requirements for ventilation, temperature,
humidity, and other conditions affecting performance of the Work.
1.
Verify that manufacturer's written instructions for environmental conditions have been
permanently established in spaces where equipment and wiring are installed, before
installation begins.
B.
Examine roughing-in for electrical connections to verify actual locations of connections before
installation.
C.
Proceed with installation only after unsatisfactory conditions have been corrected.
3.2
EQUIPMENT INSTALLATION
A.
Comply with NFPA 72, NFPA 101, and requirements of authorities having jurisdiction for
installation and testing of fire-alarm equipment. Install all electrical wiring to comply with
requirements in NFPA 70 including, but not limited to, Article 760, "Fire Alarm Systems."
1.
2.
3.
Devices placed in service before all other trades have completed cleanup shall be
replaced.
Devices installed but not yet placed in service shall be protected from construction dust,
debris, dirt, moisture, and damage according to manufacturer's written storage
instructions.
Fire alarm devices shall be installed in a manner that provides accessibility for periodic
maintenance or replacement of the device.
(Edit the Following to Suite Project Requirements)
B.
[Demolition of existing equipment should begin by the fire alarm contractor
disconnecting the existing circuits at the control panels, terminal cans or junction boxes
as appropriate and rerouting any active circuits around the construction area utilizing
the previously installed temporary wiring.]
C.
[Existing devices that are to be reused shall be properly mounted and installed. Mounting
surfaces shall be cut and patched in accordance with Architectural Sections, and be
repainted in accordance with Painting Sections as necessary to match existing.]
D.
[Connecting to Existing Equipment: Verify that existing fire-alarm system is operational
before making changes or connections.
1.
2.
3.
Connect new equipment to existing control panel in existing part of the building.
Connect new equipment to existing monitoring equipment at the supervising
station.
Expand, modify, and supplement existing control and monitoring equipment as
necessary to extend existing control and monitoring functions to the new points.
New components shall be capable of merging with existing configuration without
degrading the performance of either system.
DIGITAL ADDRESSABLE FIRE DETECTION AND ALARM SYSTEM
28 3113 - 22
NORTHWESTERN UNIVERSITY
PROJECT NAME ____________
JOB # ________
4.
E.
FOR: ___________
ISSUED: 03/29/2017
If an existing fire alarm system is to be out of service for more than 4 hours a
University approved fire watch shall be provided. ]
Equipment Mounting: Install fire-alarm control unit on concrete base if required. Comply with
requirements for concrete base specified in Division 3 Sections.
1.
2.
3.
4.
Install dowel rods to connect concrete base to concrete floor. Unless otherwise indicated,
install dowel rods on 18-inch (460-mm) centers around the full perimeter of concrete
base.
For supported equipment, install epoxy-coated anchor bolts that extend through concrete
base and anchor into structural concrete floor.
Place and secure anchorage devices. Use setting drawings, templates, diagrams,
instructions, and directions furnished with items to be embedded.
Install anchor bolts to elevations required for proper attachment to supported equipment.
F.
Install wall-mounted equipment with tops of cabinets not more than 78 inches (1980 mm) above
the finished floor. Mount cabinets plumb and rigid without distortion of box. Do not attach
directly to masonry walls. Attach fire-alarm control unit to the vertical surface behind the
equipment on steel channels such as “Unistrut”.
G.
Mount recessed equipment with fronts uniformly flush with wall finish and mating with back-box.
H.
Manual Fire-Alarm Boxes:
1.
2.
3.
I.
Install manual fire-alarm box in the normal path of egress within 60 inches (1520 mm) of
the exit doorway.
Mount manual fire-alarm box on a background of a contrasting color.
The operable part of manual fire-alarm box shall be between 42 inches (1060 mm) and
48 inches (1220 mm) above floor level. All devices shall be mounted at the same height
unless otherwise indicated.
Smoke or Heat-Detector Spacing:
1.
2.
3.
4.
5.
6.
Comply with the "Smoke-Sensing Fire Detectors" section in the "Initiating Devices"
chapter in NFPA 72, for smoke-detector spacing.
Comply with the "Heat-Sensing Fire Detectors" section in the "Initiating Devices" chapter
in NFPA 72, for heat-detector spacing.
Smooth ceiling spacing shall not exceed [30 feet (9 m)].
Spacing of detectors for irregular areas, for irregular ceiling construction, and for high
ceiling areas shall be determined according to Annex A [or Annex B] in NFPA 72.
HVAC: Locate detectors not closer than [36 inches (910 mm)] [60 inches (1520 mm)]
from air-supply diffuser or return-air opening.
Lighting Fixtures: Locate detectors not closer than 12 inches (300 mm) from any part of a
lighting fixture and not directly above pendant mounted or indirect lighting.
J.
Install a factory supplied cover on each smoke detector that is not placed in service during
construction. Cover shall remain in place except during system testing. Remove cover prior to
system turnover.
K.
Duct Smoke Detectors: Detectors shall be furnished and installed as shown on mechanical
drawings. Comply with NFPA 72 and NFPA 90A. Install sampling tubes so they extend the full
width of duct. Tubes more than 36 inches (9100 mm) long shall be supported at both ends.
DIGITAL ADDRESSABLE FIRE DETECTION AND ALARM SYSTEM
28 3113 - 23
NORTHWESTERN UNIVERSITY
PROJECT NAME ____________
JOB # ________
1.
2.
FOR: ___________
ISSUED: 03/29/2017
Do not install smoke detector in duct smoke-detector housing during construction. Install
detector only during system testing and prior to system turnover.
Provide a remote test station with test switch and indicating LED lights for each duct
detector. Locate key test stations in plain view on walls or ceilings so that they can be
observed and operated from a normal standing position.
L.
Elevator Shafts: Coordinate temperature rating and location with sprinkler rating and location.
Do not install smoke detectors in sprinklered elevator shafts.
M.
Remote Status and Alarm Indicators: Install in a visible location near each smoke detector,
sprinkler water-flow switch, and valve-tamper switch that is not readily visible from normal
viewing position.
N.
Audible Alarm-Indicating Devices: Install at 96” above the finished floor or not less than 6 inches
(150 mm) below the ceiling. Install bells and horns on flush-mounted back boxes with the
device-operating mechanism concealed behind a grille. Install all devices at the same height
unless otherwise indicated.
O.
Visible Alarm-Indicating Devices: Install at 96” above the finished floor or adjacent to each alarm
bell or alarm horn and at least 6 inches (150 mm) below the ceiling. Install all devices at the
same height unless otherwise indicated.
P.
Audible/Visible Alarm-Indicating Devices: Install at 96” above the finished floor or not less than 6
inches (150 mm) below the ceiling. Install devices on flush-mounted back boxes with the
device-operating mechanism concealed behind a grille. Install all devices at the same height
unless otherwise indicated.
Q.
Device Location-Indicating Lights: Locate in public space near the device they monitor.
R.
[Antenna for Radio Alarm Transmitter: Mount to building structure where indicated. Use
mounting arrangement and substrate connection that resists [100-mph (160-km/h)]
<Insert value> wind load with a gust factor of 1.3 without damage.]
S.
Provide wire guards on all devices in areas subject to potential abuse or incidental damage.
T.
Provide a device lock on the circuit breaker(s) serving the fire alarm system to prevent
inadvertent shut-off but does not interfere with the tripping function.
U.
Attach a permanent label to the inside of the fire alarm control panel and equipment cabinets
identifying the location of the panel’s 120 volt electrical source. This label is in addition to any
labeling required under the “Electrical Identification” Section.
V.
The date of installation shall be permanently marked on all batteries installed in the FACP or
power extender panels.
W.
All keying and locks for cabinets shall comply with University Standards.
X.
A parts cabinet with a minimum of 10 percent attic stock is required to be kept on-site in the
FACP room (where one is included) or as directed by the University Electric Shop.
DIGITAL ADDRESSABLE FIRE DETECTION AND ALARM SYSTEM
28 3113 - 24
NORTHWESTERN UNIVERSITY
PROJECT NAME ____________
JOB # ________
3.3
FOR: ___________
ISSUED: 03/29/2017
INSTRUCTIONS
A.
Provide computer printout or typewritten instruction card mounted behind a plastic or glass
cover in a stainless-steel or aluminum frame. Include interpretation and describe appropriate
response for displays and signals. Briefly describe the functional operation of the system under
normal, alarm, and trouble conditions.
B.
Install framed instructions in a location visible from the FACP.
3.4
PATHWAYS
A.
All wiring shall be enclosed by EMT without exception.
B.
EMT, junction boxes, and covers shall be factory-painted red enamel.
C.
Total wiring size including insulation shall be considered when sizing conduit runs and
calculating the 40 percent fill.
D.
Adequate J-boxes shall be installed to allow for wire removal or replacement.
3.5
WIRING
A.
System Wiring: Wire and cable shall be a type listed for its intended use by an approval agency
acceptable to the Authority Having Jurisdiction.
B.
Fire alarm cable shall be designed to survive for two hours in burning infrastructure while being
fully operational in order for safe evacuation of building occupants and support critical systems
such as emergency voice-alarm communication, smoke/fire alarm systems, fireman’s
telephone, area-of-refuge communication systems, and visible notification appliances.
C.
Wiring shall be NEC type FPL, solid copper, fully annealed. Minimum 16 AWG. Color coded
polypropylene insulation. Digital communication loops shall use twisted and shielded (100%
aluminum/polyester foil, 25% overlap), low capacitance cable with stranded copper drain wire.
1.
Manufacturers: Allied Wire & Cable or as approved by fire alarm system vendor.
D.
"T-tapping" of intelligent (addressable) fire alarm initiating circuits is not permitted in the City of
Chicago.
E.
Wiring shall be color coded as to function per University Design Standards.
F.
Wire nuts are not acceptable for joining wires. Wire terminal strips shall be used to join wires.
Wire terminal strips shall be permanently mounted inside junction boxes with wires neatly
bundled and arranged, wires shall be labeled with the system circuit number and area served.
Junction box cover is to be labeled “splice”.
G.
Comply with UL 2196.
H.
Fire alarm riser raceway shall be routed in a 2 hour rated shaft.
DIGITAL ADDRESSABLE FIRE DETECTION AND ALARM SYSTEM
28 3113 - 25
NORTHWESTERN UNIVERSITY
PROJECT NAME ____________
JOB # ________
3.6
FOR: ___________
ISSUED: 03/29/2017
CONNECTIONS
A.
For fire-protection systems related to doors in fire-rated walls and partitions and to doors in
smoke partitions, comply with requirements in "Door Hardware" Section. Connect hardware and
devices to fire-alarm system.
1.
Verify that hardware and devices are listed for use with installed fire-alarm system before
making connections.
B.
The fire alarm control panel shall be connected to the University Campus wide central
supervisory system. Requirements for this connection can be obtained from Facilities
Management Operations (FMO).
C.
Make addressable connections with a supervised interface device to the following devices and
systems. Install the interface device less than 36 inches (910 mm) from the device controlled.
Make an addressable confirmation connection when such feedback is available at the device or
system being controlled. (Edit for project requirements)
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
14.
15.
16.
17.
18.
3.7
Alarm-initiating connection to smoke-control system (smoke management) at firefighters'
smoke-control system panel.
Alarm-initiating connection to stairwell and elevator-shaft pressurization systems.
Smoke dampers in air ducts of designated HVAC duct systems.
Magnetically held-open doors.
Electronically locked doors and access gates.
Alarm-initiating connection to elevator recall system and components.
Alarm-initiating connection to activate emergency lighting control.
Alarm-initiating connection to activate emergency shutoffs for gas and fuel supplies.
Supervisory connections at valve supervisory switches.
Supervisory connections at low-air-pressure switch of each dry-pipe sprinkler system.
Supervisory connections at elevator shunt-trip breaker.
Data communication circuits for connection to building management system.
Data communication circuits for connection to mass notification system.
Supervisory connections at fire-extinguisher locations.
Supervisory connections at fire-pump power failure including a dead-phase or phasereversal condition.
Supervisory connections at fire-pump engine control panel.
Supervisory connections at engine-generator control panel.
<Insert connections>.
IDENTIFICATION
A.
Identify system components, wiring, cabling, and terminals. Comply with requirements for
identification specified in Section 26 0553 "Identification for Electrical Systems."
B.
A barcode is to be placed on the main fire alarm panel that complies with the University’s
standards.
C.
Labeling must be attached to the inside of the fire control panel and equipment cabinet
identifying the location of that panels 120 volt electrical source.
DIGITAL ADDRESSABLE FIRE DETECTION AND ALARM SYSTEM
28 3113 - 26
NORTHWESTERN UNIVERSITY
PROJECT NAME ____________
JOB # ________
3.8
FOR: ___________
ISSUED: 03/29/2017
GROUNDING
A.
Ground fire-alarm control unit and associated circuits; comply with IEEE 1100. Install a ground
wire from main service ground to fire-alarm control unit.
B.
Ground shielded cables at the control panel location only. Insulate shield at device location.
3.9
SURGE PROTECTION
A.
3.10
Provide a UL listed surge protection device on all low voltage communications wiring entering or
leaving the building to or from the FACP and other components.
FIELD QUALITY CONTROL
A.
Field tests shall be witnessed by [Architect] [Engineer] [Authorities Having Jurisdiction]
[Representatives of the University].
B.
Manufacturer's Field Service: Engage a factory-authorized service representative to test and
inspect components, assemblies, and equipment installations, including connections.
C.
Perform tests and inspections.
D.
Perform the following tests and inspections[ with the assistance of a factory-authorized
service representative]:
1.
Visual Inspection: Conduct visual inspection prior to testing.
a.
b.
2.
3.
4.
5.
6.
Inspection shall be based on completed record Drawings and system
documentation that is required by the "Completion Documents, Preparation" table
in the "Documentation" section of the "Fundamentals" chapter in NFPA 72.
Comply with the "Visual Inspection Frequencies" table in the "Inspection" section of
the "Inspection, Testing and Maintenance" chapter in NFPA 72; retain the
"Initial/Reacceptance" column and list only the installed components.
System Testing: Comply with the "Test Methods" table in the "Testing" section of the
"Inspection, Testing and Maintenance" chapter in NFPA 72.
Test audible appliances for the public operating mode according to manufacturer's written
instructions. Perform the test using a portable sound-level meter complying with Type 2
requirements in ANSI S1.4.
Test audible appliances for the private operating mode according to manufacturer's
written instructions.
Test visible appliances for the public operating mode according to manufacturer's written
instructions.
Factory-authorized service representative shall prepare the "Fire Alarm System Record of
Completion" in the "Documentation" section of the "Fundamentals" chapter in NFPA 72
and the "Inspection and Testing Form" in the "Records" section of the "Inspection,
Testing and Maintenance" chapter in NFPA 72.
E.
Reacceptance Testing: Perform reacceptance testing to verify the proper operation of added or
replaced devices and appliances.
F.
Fire-alarm system will be considered defective if it does not pass tests and inspections.
DIGITAL ADDRESSABLE FIRE DETECTION AND ALARM SYSTEM
28 3113 - 27
NORTHWESTERN UNIVERSITY
PROJECT NAME ____________
JOB # ________
FOR: ___________
ISSUED: 03/29/2017
G.
Prepare test and inspection reports.
H.
Maintenance Test and Inspection: Perform tests and inspections listed for weekly, monthly,
quarterly, and semiannual periods. Use forms developed for initial tests and inspections.
I.
Annual Test and Inspection: One year after date of Substantial Completion, test fire-alarm
system complying with visual and testing inspection requirements in NFPA 72. Use forms
developed for initial tests and inspections.
3.11
A.
MAINTENANCE SERVICE
Initial Maintenance Service: Beginning at Substantial Completion, maintenance service shall
include 12 months' full maintenance by skilled employees of manufacturer's designated service
organization. Include preventive maintenance, repair or replacement of worn or defective
components, lubrication, cleaning, and adjusting as required for proper operation. Parts and
supplies shall be manufacturer's authorized replacement parts and supplies.
1.
2.
3.
4.
5.
3.12
Include visual inspections according to the "Visual Inspection Frequencies" table in the
"Testing" paragraph of the "Inspection, Testing and Maintenance" chapter in NFPA 72.
Perform tests in the "Test Methods" table in the "Testing" paragraph of the "Inspection,
Testing and Maintenance" chapter in NFPA 72.
Perform tests per the "Testing Frequencies" table in the "Testing" paragraph of the
"Inspection, Testing and Maintenance" chapter in NFPA 72.
Comply with Evanston Fire Department mandates for test and inspections. (Weekly,
Monthly, Quarterly, Semi-annul, and Annual)
A MS ‘Excel’ report shall be provided and shall include system type, location, deficiency
notes & barcode information.
SOFTWARE SERVICE AGREEMENT
A.
Comply with UL 864.
B.
Technical Support: Beginning at Substantial Completion, service agreement shall include
software support for two years.
C.
Upgrade Service: At Substantial Completion, update software to latest version. Install and
program software upgrades that become available within two years from date of Substantial
Completion. Upgrading software shall include operating system and new or revised licenses for
using software.
1.
3.13
A.
Upgrade Notice: At least 30 days to allow the University to schedule access to system
and to upgrade computer equipment if necessary.
DEMONSTRATION and TRAINING
Engage a factory-authorized service representative to train University's maintenance personnel
to adjust, operate, and maintain fire-alarm system. Provide a minimum of 8 hours training.
DIGITAL ADDRESSABLE FIRE DETECTION AND ALARM SYSTEM
28 3113 - 28
NORTHWESTERN UNIVERSITY
PROJECT NAME ____________
JOB # ________
B.
FOR: ___________
ISSUED: 03/29/2017
[Tuition for two attendees from the University for Manufacturer sponsored and taught
service school shall be included in the contract.]
END OF SECTION 28 3113
DIGITAL ADDRESSABLE FIRE DETECTION AND ALARM SYSTEM
28 3113 - 29
NORTHWESTERN UNIVERSITY
PROJECT NAME ____________
JOB # ________
FOR: ___________
ISSUED: 03/29/2017
THIS PAGE IS INTENTIONALLY BLANK
DIGITAL ADDRESSABLE FIRE DETECTION AND ALARM SYSTEM
28 3113 - 30