Remote control of two RR7 power relays from LynTec Modular Sequencer system
NOTE: 0Ω (single black band) jumpers
must be installed in all JRR7 positions
to drive RR7 relays.
Circuit breaker cabinet or electrical box
provided by others.
RR-7
Latching relay
100Ω sequencer relay-control resistors.
Lift one end to disable sequencer control.
20 Amp receptacle A
STEP RATE
ON (red)
CR-1
+35v (blue)
CR-2
OFF (black)
CR-3
CR-4
1on
2on
1off
2off
ON 1 (red)
ON 2 (red)
OFF 1 (blk)
OFF 2 (blk)
+35v (blue)
Com
Aux LED–
Aux LED+
Auxiliary
Breakers
or
Remote
RR7s
None =
sec.
DELAY TIME
First
Second
2 sec.
4 sec.
8 sec.
16 sec.
30 sec.
2 min.
4 min.
8 min.
RR-7
Latching relay
FIRST
Sequencer
20 Amp receptacle B
1B ______________
Connect to breaker #
1A ______________
Connect to breaker #
ON (red)
+35v (blue)
B
CR Option
Completion
Relay
OFF (black)
All 1N4004s
CR-5
CR-6
NC
LED+
LED–
NO
C
DO NOT connect this LED –
line to common.
You'll let the smoke out !
Terminal layout is rear view
Also see 139-0243-01 for
RR7 control wire
sizing
BOOTH
ON
155 ft. run - 22 ga.
Green LED
246 ft. run - 20 ga.
Optional BONS-1
BOOTH ON control switch
See http://www.lyntec.com/139-0309.pdf for
custom switch legends.
CR N.O.
CR ARM
CR N.C.
CR Select
STEP 1
STEP 2
STEP 3
STEP 4
STEP 5
STEP 6
3B ______________
3A ______________
Connect to breaker #
Connect to breaker #
4B ______________
4A ______________
Relay contacts
shown at rest
BEFORE
completion.
Connect CR Select
to desired step.
Relay changes
state when that
step turns on.
Connect to breaker #
Connect to breaker #
5B ______________
5A ______________
Connect to breaker #
Connect to breaker #
Connect to breaker #
6A ______________
Connect to breaker #
NO
C
Green LED
Flashes during sequencing
Mounts on the side of any breaker
panel.
Both = 1/8 sec.
1/4 sec.
1/2 sec.
1on
2on
1off
2off
ON 1 (red)
ON 2 (red)
OFF 1 (blk)
OFF 2 (blk)
+35v (blue)
Com
Aux LED–
Aux LED+
NC
Auxiliary
Breakers
or
Remote
RR7s
None =
sec.
DELAY TIME
First
1A ______________
DELAY POSITION
Borrow
Pilot
ON
Hold
Kill
N/C
24v AC
Com
ON
STEP RATE
J-RR7
jumper holes
5 -> 6
4 -> 5
3 -> 4
2 -> 3
1 -> 2
Before 1
The RRC-6 Remote Relay Controller
is a sidecar with storage capacitors
and RR-7 relay drivers capable of
driving up to 6 RR7s.
MAIN
Second
2 sec.
4 sec.
8 sec.
16 sec.
30 sec.
2 min.
4 min.
8 min.
LAST
Sequencer
1B ______________
Connect to breaker #
Connect to breaker #
NO
RR7s mount in knockout in the host
breaker panel.
see
http://www/lyntec.com/139-0291.pdf
C
Terminal layout is rear view
MAIN
OFF
Red lens
How it works
The momentary BOOTH switch pulses on both RR7
latching relay circuits A & B at the same time through
steering diodes CR-5 & CR-6
Pressing the MAIN ON switch turns on all sequenced
circuits without affecting the already-on RR7s.
CR Option
Completion
Relay
2A ______________
2B ______________
Connect to breaker #
Connect to breaker #
Shown
unpowered
CR N.O.
CR ARM
CR N.C.
CR Select
STEP 1
STEP 2
STEP 3
STEP 4
STEP 5
STEP 6
Relay contacts
shown at rest
BEFORE
completion.
Connect CR Select
to desired step.
Relay changes
state when that
step turns on.
3A ______________
3B ______________
Connect to breaker #
Connect to breaker #
4A ______________
4B ______________
Connect to breaker #
Connect to breaker #
5A ______________
5B ______________
Connect to breaker #
Connect to breaker #
6B ______________
Steering diodes CR-1 thru CR-4 pulse RR7s ON and
OFF in parallel with breakers 1a-1b and 2a-2b during the
main sequence.
Connect to breaker #
Connect to breaker #
Kill
Busy
Carry
Com
Com
Pilot
Borrow
Hold
OFF
V–
V+
ON
+5v Pilot Logic
6A ______________
Com
Pilot
Power & Kill
Connector
Cascade
Connector
Off
V–
Carry
Busy
Kill
N/C
24v AC
Com
The steering diodes prevent the BOOTH switch from
toggling the breakers connected to steps 1 and 2.
Cascade
Connector
100Ω sequencer relay-control resistors.
Lift one end to disable sequencer control.
LED–
Terminal layout is rear view
Alternative Uses Cat 5 Wire
Power & Kill
Connector
Off
V–
Carry
Busy
Kill
N/C
24v AC
Com
NC
LED+
Kill
OFF
V–
V+
RR7 Kit includes: 2 – G-E RR7 relays, mounting brackets and screws.,
6 – 1N4004 diodes, 4 – zero ohm jumpers (single black band) to install
in JRR7 positions in the MS-12 board that will drive the relays.
(RR7s to be mounted in box supplied by others)
ON
1574 ft. run - 12 ga.
Com
Pilot
Low voltage control of two remotely located 20 Amp, 120v circuits.
Turned on & off by steps #1 & #2.
Busy
Carry
Com
Com
Pilot
Borrow
Hold
-RR7 Option + BONS-1 BOOTH ON switch
990 ft. run - 14 ga.
+5v Pilot Logic
Specifying & ordering information
623 ft. run - 16 ga.
All other control and LED
wiring may be 22 ga.,
5,000 ft max.
Connect to breaker #
Connect to breaker #
6B ______________
392 ft. run - 18 ga.
2503 ft. run - 10 ga.
2B ______________
2A ______________
Shown
unpowered
MS-12 Modular Sequencer Board
20 Amp
circuit breaker
source
B
MS-12 Modular Sequencer Board
A
DELAY POSITION
Borrow
Pilot
ON
Hold
Kill
N/C
24v AC
Com
Both = 1/8 sec.
1/4 sec.
1/2 sec.
All 1N4004s
5 -> 6
4 -> 5
3 -> 4
2 -> 3
1 -> 2
Before 1
20 Amp
circuit breaker
source
A
Pressing the OFF switch forces an off cycle and turns off
all motorized breakers and RR7 relays.
139-0271-06 RR7s for MS12 7/3/03
See http://www.lyntec.com/139-0271.pdf for latest revision.
Optional emergency shutdown switch.
Close to kill all systems. Open to re-sequence.