EasyAir Office sensor advanced grouping SNS200

Sensors
EasyAir
office sensor advanced
grouping SNS200
Datasheet
EasyAir
Office sensor advanced
grouping SNS200
The Philips EasyAir office sensor is the ideal solution for per-luminaire control of new
light luminaires. It combines occupancy sensing, daylight harvesting and task tuning in
a single, compact package for easy OEM luminaire assembly. EasyAir operates with the
established Xitanium SR driver standard to make a simple two-wire connection
between sensor and driver, thus eliminating the need for multiple components and
auxiliary devices. The result is a cost effective and easy-to-design-in solution ideal for
energy-savings. An intuitive app makes configuration and commissioning during and
after installation fast and easy using Philips Field Apps.
Features
Benefits
Applications
• Occupancy sensing, daylight harvesting
and task tuning in one device
• Compact size, 2-wire connection
• Operates with Philips Xitanium SR
drivers and qualified wireless switches
• Preset with most common sensor
parameters
• Configuration of sensor parameters– if
desired – using NFC or IR via intuitive
Android-based Philips Field Apps
• Simple grouping of luminaires to a
wireless switch with Philips Field Apps
• Combines functionality to reduce need
for multiple components
• Fits into existing and new-design
luminaires
• Quick task tuning in the field to
optimize light and power levels
• Enables auto-off/manual-on
application
• Cost-effective solution for energysavings
• 5-year limited system warranty with
Philips Xitanium LED drivers
• Configuration and commissioning from
the floor
•
•
•
•
•
•
•
•
January 2018
Conference rooms
Individual offices
Open offices
Classrooms
Storage and break areas
Restrooms
Lobbies
Stairways
Ordering Information
Commercial product name
Colour
Description
EOC
12NC
Carton Quantity
EasyAir SNS200/w
White
Office Sensor Advanced Grouping
8718696 698945 00
929 000 766 803
50 pcs
EasyAir SNS200/g
Grey
Office Sensor Advanced Grouping
8718696 712412 00
929 000 560 703
50 pcs
Product Data
All specifications are typical and at 25 °C Tcase unless otherwise specified.
Physical Information
Overall Dimensions
50 mm x 19.0 mm x 31.5 mm
Housing (Luminaire Hole)
44 mm x 17 mm (l x w)
Net Weight per Piece
17 gr
Volume required Inside Luminaire (LxWxH)
50 mm x 19 mm x 24 mm
Color
White and Grey
Connectors
(2) Lite-Trap connectors
Input wire cross-section (solid conductor wire)
0.25 - 0.75 mm2
18 - 24 AWG
Input wire cross-section (stranded wire)
0.3 - 0.5 mm2
20 - 22 AWG
Electrical Information
Input Voltage
Powered by SR driver low-voltage interface
Current Consumption
13 mA
Nominal Power Consumption
200 mW
Standby Power
< 1 W on luminaire level, including driver standby power
Occupancy Sensing
Type
Passive infrared (PIR)
Occupancy Based Control
Default enabled
Occupancy Mode
Auto-on/off, Manual-on/off, Manual-on/auto-off; Red LED indicates “on”
Group Occupancy Sharing
Enabled/disabled
Group light behaviour
Background light level, Field task level
Hold Time
0.5 - 60 minutes
Viewing Angle
X = 72°, Y = 86° ( See detection pattern)
Background Light Level
0-100%
Prolong Time
0 minutes - infinity
Grace Fading
0-25 sec
Response Time/Fading to Switch On/Off
0.7 sec
Daylight Sensing
Daylight based control
Default enabled
Auto-calibration
Upon power-up
Daylight dependent switching
Default disabled
Daylight dependent override
Default disabled
Viewing Angle
40° (half value sensitivity); 2% cut-off point at 75°
Task Tuning
Field Task Level
0-100%
Environment & Approbation
Operating Ambient Temperature Range
0 °C to 55 °C
Operating Humidity
0 – 95% non condensing
Storage Temperature
-25 °C to 85 °C
Storage Humidity
0-95% non condensing
Max Case Temperature (Tcase)
55 °C
Agency Approbations
Warranty
CE, ENEC, RTTE, EMC
Digital Interface
Xitanium SR
5 years warranty for released Philips system combination (sensor and compatible driver).
3 years warranty for sensor only.
Other
Status Indicators
Red, Yellow. Yellow LED on: Vacancy & Sensor is functional; Red LED on: Motion is detected
Energy reporting
Calculated from last “power on”: % On, Energy Consumed (Whr), System on time (hrs), Avg power consumed
No. Drivers per Sensor
4 max
Max Distance Switch-to-First-Luminaire
10 m line-of-sight
Max Distance Luminaire-to-Luminaire
12 m line-of-sight
No. Switches per Group
10 max
Field Configuration
via NFC or IR, parameters set via Philips Field Apps
2-8
Datasheet - EasyAir office sensor advanced grouping SNS200
January 2018
EasyAir office sensor
43.8 MAX
16.8 MAX
2.3
Sensor Dimensions (mm)
24.3 MAX
7.5 MAX
50.0 MAX
Mounting Dimensions (mm)
Mounting in U-shaped slot in sheet metal (max thickness 1 mm), tolerance +0.2 mm/-0.0 mm
43.5
43.5
16.0
16.0
Mounting in cut-out in sheet matal (thickness 0.7 mm to 1.2 mm), tolerance +/-0.2 mm
Mounting hole dimension (+/- 0.2mm)
2.3
3-8
17.0
44.0
Datasheet - EasyAir office sensor advanced grouping SNS200
January 2018
Mounting in a bracket (SMB-50)
Accessories
65 Max.
Colour
12NC
EasyAir SMB-50/w
White
929001540206
EasyAir SMB-50/g
Grey
929001540306
The EasyAir office sensor SNS200 can be mounted in a
bracket (SMB 50). Refer the figures for details on mounting
and design-in into luminaire. All dimensions are in mm.
26 Max.
64 Max.
60 ± 0.2
24 Max.
22 ± 0.2
8 Max.
Press springs inwards on both sides before the bracket can
slide-in the luminaire hole.
4-8
Datasheet - EasyAir office sensor advanced grouping SNS200
January 2018
Installing EasyAir office sensor with ceiling mount bracket (SNS200CMP)
The ceiling mount SNS200CMP bracket is premounted with an EasyAir office sensor SNS200 along with the cable. For
cut-out in the ceiling and mounting, refer the figures below. All dimensions are in mm.
Colour
12NC
EasyAir SNS200CMP
White
9290 007 90206
74
Product
Radius min 5 mm
46
86
63
Ø 4
7
Ø
5-8
Datasheet - EasyAir office sensor advanced grouping SNS200
January 2018
EasyAir office sensor
Wiring Diagram
Connectors
XITANIUM SR
LED DRIVER
NC
GROUND
Use 0.75 mm2 solid copper wire,
rated >= 600 V / 90 °C.
NEUTRAL
Strip wire to 8 mm.
LINE
Connectors
(non-polarized)
LED+
LED+
LEDLEDLEDset
GNDset
SRSR+
SR
SR
EASYAIR
NC
NFC ANTENNA
EasyAir office sensor
Occupancy Sensing
The detection area for the movement sensor can be roughly divided into two parts:
• Minor movement (person moving ≤ 0.9 m/s).
• Major movement (person moving ≥ 0.9 m/s)..
H
Height
Minor Movement
Major Movement
h
Y1
X1
Y2
X2
2.4 m
2.9 m
2.7 m
4.5 m
2.9 m
3m
3.6 m
3.4 m
5.4 m
3.6 m
Y2
Y1
X1
X2
Note: L
onger dimension of detection area (Y1, Y2) is parallel
to longer dimension of EasyAir.
Switch On level (fixed)
Fade to
switch o
n
(fixed)
T1
Prolong time
(configurable)
T2
Switch On sequence
6-8
Datasheet - EasyAir office sensor advanced grouping SNS200
T3
T4
T5
ff
itch o
to sw
Fade (fixed)
LIGHT LEVEL
Background level
(configurable)
ing
ad ble)
ef
ac ura
Gr nfig
(co
Hold time
(configurable)
T6 T7
Switch Off sequence
January 2018
EasyAir office sensor
Daylight Sensor
The light sensor measures the total amount of light in a circular field of ≈ 80% of the PIR detection area. The following
aspects should be observed during installation:
• Minimum distance from the window ≥ 0.6 m.
• Prevent light reflections from outside entering the sensor (for example sunlight reflection on a car bonnet) as this will lead
to incorrect light regulation.
As a guideline the formula 0.72 x H can be used to calculate the minimum distance between the window and sensor
whereby H is the height from the bottom of the window to the ceiling.
Photosensor Spatial Response
Light Fixture
Window
40˚
Field of View
Typical Daylit Zone, about 3.6 m
Output current (Normalized)
Photosensor Spectral Response
1.0
Light Sensor
Human Eye
0.9
0.8
0.7
0.6
0.5
0.4
0.3
0.2
0.1
0
200
300
400
500
600
700
800
900
1000
Wavelength (nm)
7-8
Datasheet - EasyAir office sensor advanced grouping SNS200
January 2018
EasyAir office sensor
EasyAir Configuration App
EasyAir parameters can be configured via
Philips Field Apps. Two versions are
available:
1. EasyAir NFC – This app allows configuring
EasyAir parameters only, when you can
physically access the sensor with a
smartphone.
2. EasyAir IR – This app allows grouping of
luminaires and adding switches along with
easy configuration of EasyAir parameters.
This can be done via the IR feature of the
app using applicable phones from floor
level.
You must first register for the app to receive a
username and password, then download
Philips Field Apps from the Google Play
Store. For more information, please visit our
website:
http://www.lighting.philips.co.uk/oememea/products/easy-to-integrate-wirelesssensors.html for details including
recommended Android phones and user
manuals.
Default Factory Settings
Occupancy based control
Auto-on, Enabled
Daylight Based Control
Auto-on, Enabled
Daylight dependent switching
Default disabled
Daylight dependent override
Default disabled
LED Indicator
Enabled
Occupancy Mode
Auto-on/off
Group Occupancy Sharing
Enabled
Group Light Behaviour
Background level
Field Task Tuning
100%
Background Light Level
20%
Hold Time
15 minutes
Prolong Time
15 minutes
Grace Fading
10 seconds
Fade to Switch On
0.7 seconds
Fade to Switch Off
0.7 seconds
8-8
Datasheet - EasyAir office sensor advanced grouping SNS200
January 2018
EasyAir office sensor
Disclaimer
The information in this guide is accurate at the time of
writing. This guide is provided “as is” without expressed or
implied warranty of any kind. Neither Philips nor its agents
assume any liability for inaccuracies in this guide or losses
incurred by use or misuse of the information in this guide.
Philips will not be liable for any indirect, special, incidental
or consequential damages (including damages for loss of
business, loss of profits or the like), whether based on
breach of contract, tort (including negligence), product
liability or otherwise, even if Philips or its representatives
have been advised of the possibility of such damages.
9-8
Datasheet - EasyAir office sensor advanced grouping SNS200
January 2018
© Philips Lighting Holding B.V. 2018. All rights reserved. Philips reserves the right to make
changes in specifications and/or to discontinue any product at any time without notice or
obligation and will not be liable for any consequences resulting from the use of this publication.
01/2018
Data subject to change
www.lighting.philips.co.uk/oem-emea/
products/connected-lighting