XPSECPE3930C
Product data sheet
Characteristics
module XPSEC - increasing the number of safety
contacts - 115..230 V ACDC-spring
Range of product
Preventa Safety automation
Product or component type
Preventa safety module
Safety module name
XPSECPE
Safety module application
Increasing the number of safety contacts
Function of module
Increasing the number of safety contacts
Safety level
Can reach PL e/category 4 conforming to EN/ISO 13849-1 can reach the maximum safety level of
module base
Can reach SILCL 3 conforming to EN/IEC 62061 can reach the maximum safety level of module
base
Safety reliability data
DC = 0...99 % conforming to EN/ISO 13849-1
MTTFd > 100 years conforming to EN/ISO 13849-1
PFHd = 2.47E-8 1/h conforming to EN/IEC 62061
Output type
Relay 8 NO, volt-free
[Us] rated supply voltage
115...230 V AC (- 15...10 %)
Number of additional circuits
2 NC + 1 solid state output
Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications
Main
Complementary
Supply frequency
50/60 Hz
Power consumption in VA
<= 6 VA
Input protection type
Internal, electronic
Breaking capacity
B300 : holding 360 VA AC-15 for relay output
B300 : inrush 3600 VA AC-15 for relay output
Breaking capacity
20 mA / 24 V for solid state output circuit
3 A / 24 V - L/R = 50 ms, DC-13 for relay output
Output thermal current
6 A per relay for relay output
[Ith] conventional free air thermal
current
< 24 A for relay output
Associated fuse rating
6 A gG for relay output conforming to EN/IEC 60947-5-1, DIN VDE 0660 part 200
Minimum output current
10 mA for relay output
Minimum output voltage
5 V for relay output
Response time on input open
<= 10 ms
[Ui] rated insulation voltage
300 V, degree of pollution 2 conforming to EN/IEC 60947-5-1, DIN VDE 0110 parts 1 & 2
[Uimp] rated impulse withstand voltage
4 kV overvoltage category III, conforming to EN/IEC 60947-5-1, DIN VDE 0110 parts 1 & 2
Local signalling
3 LEDs
Mar 31, 2018
1
Connections - terminals
Spring terminals, removable terminal block, clamping capacity: 1 x 0.2...1 x 2.5 mm² solid cable
without cable end
Spring terminals, removable terminal block, clamping capacity: 1 x 0.2...1 x 2.5 mm² flexible cable
without cable end
Spring terminals, removable terminal block, clamping capacity: 1 x 0.25...1 x 2.5 mm² flexible cable
with cable end, without bezel
Spring terminals, removable terminal block, clamping capacity: 1 x 0.25...1 x 1.5 mm² flexible cable
with cable end, with bezel
Spring terminals, removable terminal block, clamping capacity: 2 x 0.2...2 x 1 mm² solid cable without
cable end
Spring terminals, removable terminal block, clamping capacity: 2 x 0.2...2 x 1 mm² flexible cable
without cable end
Spring terminals, removable terminal block, clamping capacity: 2 x 0.25...2 x 1 mm² flexible cable
with cable end, without bezel
Spring terminals, removable terminal block, clamping capacity: 2 x 0.5...2 x 1.5 mm² flexible cable
with cable end, with double bezel
Mounting support
35 mm symmetrical DIN rail
Product weight
0.65 kg
Environment
Standards
EN/IEC 60204-1
EN/IEC 60947-5-1
Product certifications
CCC
CSA
UL
IP degree of protection
IP20 (terminals) conforming to EN/IEC 60529
IP40 (enclosure) conforming to EN/IEC 60529
Ambient air temperature for operation
-25...55 °C
Ambient air temperature for storage
-25...70 °C
2
Product data sheet
Dimensions Drawings
XPSECPE3930C
Dimensions
3
Product data sheet
Connections and Schema
XPSECPE3930C
Wiring Diagrams
Refer to the Instruction Sheet
To download the instruction sheet, follow below procedure:
1
2
Click on Download & Documents.
Click on Instruction sheet.
4