EW Series Water Source Heat Pumps &

"EWV / EWH"
Water Source Heat Pumps and Air Conditioners
Direct Drive Self-contained Packages
Vertical or Horizontal Configuration
Size ¾ - 5 Ton Capacities
Spinnaker EWV / EWH Features and Benefits















24 volt control circuit
Onboard Microprocessor control with diagnostics
5 minute anti short cycle timer
Single point power connection
Available as a Heat Pump or Cooling Only
Acoustically insulated cabinet ensures quiet operation
Quiet efficient rotary or reciprocating compressors
Forward curve DWDI centrifugal blower
Multi speed direct drive blower motor
Schrader fittings on suction and liquid lines
Filter drier
High and low pressure cut outs
1” throwaway filter
1 year parts only warranty from date of shipment
ETL compliance to ANSI/UL1995, CAN/CSA-C22.2
TYPICAL MECHANICAL SPECIFICATIONS
GENERAL
All models are shipped factory pre charged (410A), tested and wired for a single point power connection.
Horizontal (EWH) units are designed for suspended ceiling mounting and are shipped in either right or left
hand configurations refer to dimensional pages for clarification. Vertical (EWV) units are designed for free
standing floor mounting. Water supply, water outlet, and condensate drain connections are via female pipe
thread fittings.
CABINET
All cabinets are constructed of corrosion resistant galvanized steel. Units are complete with integral hanger
holes. The unit is internally insulated with 1/2" thick, 2 lb density neoprene coated insulation. Units are
provided with lift off access panels for ease of servicing while the unit remains in place, and an integral duct
collar is provided on the blower discharge opening. Horizontal units are provide in Left or Right hand return
configurations , ( specify at time of order ) supply discharge may be field converted from end to side . A
flexible duct connection (By others) is recommended.
REFRIGERATION CIRCUITS
All models utilize high efficiency rotary or reciprocating (410A) compressors. Compressors are mounted on
rubber isolators to minimize vibration transmission. Internal overload protection is provided. External high
pressure and low pressure cutout switches are included on each compressor control circuit. Each
refrigeration circuit includes an adjustable bi-flow thermal expansion valve (with external equalizer), bi-flow
liquid line filter drier, and service gauge ports. The reversing valve (on heat pump models) is a pilot operated,
sliding piston type with a replaceable magnetic solenoid coil.
The refrigerant-to-air heat transfer coil is constructed of internally enhanced copper tubes mechanically
bonded to enhanced aluminum plate fins. The evaporator coil is installed in a draw-through configuration for
optimum performance, and the large coil face area minimizes potential water carry over.
The coaxial refrigerant-to-water heat exchanger features a convoluted inner tube design for high heat transfer
efficiency. Standard models feature a copper inner tube surrounded by a steel outer tube, and carry a 400
psig water side working pressure rating.
INDOOR FAN
Forward curved, double inlet and double width, direct-drive centrifugal blowers are used for efficient air
movement. Large diameter wheels have been selected to provide optimum airflow performance at minimum
noise levels. Blower wheels are fabricated of galvanized steel. Fan motors are PSC type, with minimum three
speeds. The PSC motors feature permanently lubricated bearings and internal thermal overload protection.
ELECTRICAL/CONTROLS
All units are completely factory wired with all necessary operating controls. A 24 volt control circuit is provided
for field connection. Units are designed to operate with conventional heat pump thermostat control interface.
The reversing valve solenoid coil shall be energized in the heating mode only.
A manual reset is provided for the compressor control circuit in the event of high/low pressure cutout. A time
delay for anti-short cycle protection is standard in all units. Units include an on board microprocessor control
with diagnostics. Compressor anti short cycle protection is standard.
FILTERS
All models are shipped with 1-inch thick throwaway filters, factory installed. Filters are accessible from
the sides or end of the unit.
STAINLESS STEEL DRAIN PAN
Evaporator drain pan shall be fabricated from 304 stainless steel material. The 3/4 in NPT drain
connection fitting is also from 304 stainless steel
WARRANTY
A parts only warranty is provided with each system for a period of one year from the date of shipment for
vendor verified defective components . Refer to Spinnaker Limited Warranty for all details . An
optional extended compressor warranty is available.
OPTIONAL EXTENDED COMPRESSOR WARRANTY
An optional, four year extended compressor warranty is available at additional cost at the time of original
purchase of the equipment only. This is limited one time replacement only warranty only and obligates
Spinnaker Industries Inc. to replace f.o.b. factory, a defective compressor of equal capacity free of
charge. No responsibility is assumed by Spinnaker Industries Inc. for refrigerant, labor, or freight to and
from the factory.
OPTIONAL ACCESSORIES









Powder coat exterior cabinet finish ( SKY GRAY ) custom color match is available
Condensate pump
Freeze stat
Water regulating valve
Ball Valves
Stainless Steel flexible hose kit
Condensate Overflow sensor
Auto water flow control valve
Programmable Thermostat
OPTIONAL ACCESSORIES (cont )





Locking Thermostat Guard
2” 30% Pleated Filter
2” Fiberglass Throwaway Filter
Discharge Plenum ( vertical Units )
2way 24volt water shut off valve
Spinnaker Industries maintains a continuous improvement policy , therefore this information is subject to change without notice
31082017
Performance tested in accordance with ARI / ISO Standard 13256-1 for Water Loop Applications
Cooling capacities ,entering air conditions of 80.6ºF db / 66.2º F wb, 86ºF entering water temperature
Heating capacities ,entering air conditions of 68ºF db / 59 º F wb, 68ºF entering water temperature
Standard Features
24 volt control circuit
Onboard Microprocessor control with diagnostics
5 minute anti short cycle timer
Single point power connection
Stainless steel drain pan
Available as a Heat Pump or Cooling Only
Acoustically insulated cabinet ensures quiet operation
Quiet efficient rotary or reciprocating compressors
Forward curve DWDI centrifugal blower
Multi speed direct drive blower motor
Schrader fittings on suction and liquid lines
Filter drier
High and low pressure cut outs
1” throwaway filter
5 year compressor and 1 year parts only warranty
Options
Powder coat painted cabinet
Condensate pump
Freeze stat
Water regulating valve
Ball Valves
Stainless Steel flexible hose kit
Condensate Overflow switch
Auto water flow control valve
Programmable Thermostat
Locking Thermostat Guard
2” 30% Pleated Filter
2” Fiberglass Throwaway Filter
Discharge Plenum ( vertical Units )
2way 24volt water shut off valve
Hot Gas By Pass
Note: All capacity data shown is NET—includes motor power heat at design CFM and Hi speed fan operation.
( excludes ) allowance for external pumping power )
For operation of units with entering water temperatures below 60ºF , a mixture of Glycol is recommended.
Units are shipped pre—wired for Medium speed
Air flow ratings are at lowest voltage rating of dual rating ( ie.208 volt )
Airflow ratings include resistance of wet coil and clean air filter
TC = TOTALCOOLING CAPACITY
SC = SENSIBLE COOLING CAPACITY
THR = TOTAL HEAT REJECTION
HC = TOTAL HEATING CAPACITY
WPD = WATER PRESSURE DROP
Note: All capacity data shown is NET—includes motor power heat at design CFM and Hi speed fan operation.
( excludes ) allowance for external pumping power )
For operation of units with entering water temperatures below 60ºF , a mixture of Glycol is recommended.
Units are shipped pre—wired for Medium speed
Air flow ratings are at lowest voltage rating of dual rating ( ie.208 volt )
Airflow ratings include resistance of wet coil and clean air filter
TC = TOTALCOOLING CAPACITY
SC = SENSIBLE COOLING CAPACITY
THR = TOTAL HEAT REJECTION
HC = TOTAL HEATING CAPACITY
WPD = WATER PRESSURE DROP
Note: All capacity data shown is NET—includes motor power heat at design CFM and Hi speed fan operation.
( excludes ) allowance for external pumping power )
For operation of units with entering water temperatures below 60ºF , a mixture of Glycol is recommended.
Units are shipped pre—wired for Medium speed
Air flow ratings are at lowest voltage rating of dual rating ( ie.208 volt )
Airflow ratings include resistance of wet coil and clean air filter
TC = TOTALCOOLING CAPACITY
SC = SENSIBLE COOLING CAPACITY
THR = TOTAL HEAT REJECTION
HC = TOTAL HEATING CAPACITY
WPD = WATER PRESSURE DROP
Note: All capacity data shown is NET—includes motor power heat at design CFM and Hi speed fan operation.
( excludes ) allowance for external pumping power )
For operation of units with entering water temperatures below 60ºF , a mixture of Glycol is recommended.
Units are shipped pre—wired for Medium speed
Air flow ratings are at lowest voltage rating of dual rating ( ie.208 volt )
Airflow ratings include resistance of wet coil and clean air filter
TC = TOTALCOOLING CAPACITY
SC = SENSIBLE COOLING CAPACITY
THR = TOTAL HEAT REJECTION
HC = TOTAL HEATING CAPACITY
WPD = WATER PRESSURE DROP
Note: All capacity data shown is NET—includes motor power heat at design CFM and Hi speed fan operation.
( excludes ) allowance for external pumping power )
For operation of units with entering water temperatures below 60ºF , a mixture of Glycol is recommended.
Units are shipped pre—wired for Medium speed
Air flow ratings are at lowest voltage rating of dual rating ( ie.208 volt )
Airflow ratings include resistance of wet coil and clean air filter
TC = TOTALCOOLING CAPACITY
SC = SENSIBLE COOLING CAPACITY
THR = TOTAL HEAT REJECTION
HC = TOTAL HEATING CAPACITY
WPD = WATER PRESSURE DROP
Note: All capacity data shown is NET—includes motor power heat at design CFM and Hi speed fan operation.
( excludes ) allowance for external pumping power )
For operation of units with entering water temperatures below 60ºF , a mixture of Glycol is recommended.
Units are shipped pre—wired for Medium speed
Air flow ratings are at lowest voltage rating of dual rating ( ie.208 volt )
Airflow ratings include resistance of wet coil and clean air filter
TC = TOTALCOOLING CAPACITY
SC = SENSIBLE COOLING CAPACITY
THR = TOTAL HEAT REJECTION
HC = TOTAL HEATING CAPACITY
WPD = WATER PRESSURE DROP
Note: All capacity data shown is NET—includes motor power heat at design CFM and Hi speed fan operation.
( excludes ) allowance for external pumping power )
For operation of units with entering water temperatures below 60ºF , a mixture of Glycol is recommended.
Units are shipped pre—wired for Medium speed
Air flow ratings are at lowest voltage rating of dual rating ( ie.208 volt )
Airflow ratings include resistance of wet coil and clean air filter
TC = TOTALCOOLING CAPACITY
SC = SENSIBLE COOLING CAPACITY
THR = TOTAL HEAT REJECTION
HC = TOTAL HEATING CAPACITY
WPD = WATER PRESSURE DROP
Note: All capacity data shown is NET—includes motor power heat at design CFM and Hi speed fan operation.
( excludes ) allowance for external pumping power )
For operation of units with entering water temperatures below 60ºF , a mixture of Glycol is recommended.
Units are shipped pre—wired for Medium speed
Air flow ratings are at lowest voltage rating of dual rating ( ie.208 volt )
Airflow ratings include resistance of wet coil and clean air filter
TC = TOTALCOOLING CAPACITY
SC = SENSIBLE COOLING CAPACITY
THR = TOTAL HEAT REJECTION
HC = TOTAL HEATING CAPACITY
WPD = WATER PRESSURE DROP
Note: All capacity data shown is NET—includes motor power heat at design CFM and Hi speed fan operation.
( excludes ) allowance for external pumping power )
For operation of units with entering water temperatures below 60ºF , a mixture of Glycol is recommended.
Units are shipped pre—wired for Medium speed
Air flow ratings are at lowest voltage rating of dual rating ( ie.208 volt )
Airflow ratings include resistance of wet coil and clean air filter
TC = TOTALCOOLING CAPACITY
SC = SENSIBLE COOLING CAPACITY
THR = TOTAL HEAT REJECTION
HC = TOTAL HEATING CAPACITY
WPD = WATER PRESSURE DROP
Note: All capacity data shown is NET—includes motor power heat at design CFM and Hi speed fan operation.
( excludes ) allowance for external pumping power )
For operation of units with entering water temperatures below 60ºF , a mixture of Glycol is recommended.
Units are shipped pre—wired for Medium speed
Air flow ratings are at lowest voltage rating of dual rating ( ie.208 volt )
Airflow ratings include resistance of wet coil and clean air filter
TC = TOTALCOOLING CAPACITY
SC = SENSIBLE COOLING CAPACITY
THR = TOTAL HEAT REJECTION
HC = TOTAL HEATING CAPACITY
WPD = WATER PRESSURE DROP
EWHP / EWHC DIMENSIONAL DATA
LEFT HAND RETURN
EWHP / EWHC DIMENSIONAL DATA
RIGHT HAND RETURN
EWVP / EWVC DIMENSIONAL DATA
Standard right hand connections shown
LIMITED WARRANTY
COVERAGE AND TERMS
EWH / EWV Model Series units, and all related accessories as manufactured by Spinnaker Industries, are warranted to the original buyer to be
free from defects in materials or workmanship provided that these units and accessories have been installed and maintained in accordance with
instructions and operated under normal conditions. Spinnaker Industries sole obligation under this Limited Warranty is to repair or replace, at its
opinion, free of charge to the customer (except as provided below), FOB factory, any part determined by Spinnaker Industries (in its sole
discretion) to be defective. Warranty terms, from original ship date are as follows:
 All components ( excluding filters and fan belts ) ……………. I year from date of shipment
EXCLUSIONS
Spinnaker Industries Limited Warranty does not cover defects, reduced performance, or failure caused, directly or indirectly, by improper
installation, abuse, misuse, misapplication, improper maintenance, lack of maintenance, negligence, accident, or normal deterioration, including
wear and tear. This Limited Warranty shall not apply to items that require replacement due to normal wear i.e. fan drive belts, filters, etc., or to
failures, defects, or reduced performance resulting, directly or indirectly, from use of its products exposed to corrosive gasses or liquids.
Warranty claims that are not supported with a copy of the original start up report will not be considered.
Spinnaker Industries Limited Warranty does not include costs for transportation (including, without limitation, freight and return freight charges,
costs, and insurance), costs for removal or re-installation of parts or equipment, cranes and hoisting, premiums for overtime, labor for performing
repairs or replacement made in the field, roofing contractors or any other sub trades. Spinnaker Industries is not responsible for damages
occurring during transport of any product to or from its facilities.
RETURN PROCEDURE
To return defective parts under these warranty terms, please contact Spinnaker Industries at 1-800-932-6210 to confirm the ship to
address. The serial number located on the rating label of the unit must be provided so that the original ship date of the unit can be verified. All
defective parts must be authorized for return and shipped pre-paid to Spinnaker Industries for inspection. A purchase order must be received
prior to shipment of repaired or replacement parts. Repaired or replacement parts will be invoiced and shipped collect FOB Factory. A credit will
be issued only if the defective parts are deemed the responsibility of Spinnaker Industries. Spinnaker Industries is not responsible for any
damage or loss occurring during shipment to or from Spinnaker Industries.
THE OBLIGATION AND LIABILITY OF Spinnaker Industries UNDER THIS LIMITED WARRANTY DOES NOT
INCLUDE LOSSES, DIRECT OR INDIRECT, FOR INCIDENTAL OR CONSEQUENTIAL DAMAGES. THIS LIMITED
WARRANTY IS PROVIDED EXCLUSIVELY TO THE ORIGINAL BUYER OF PRODUCTS AND MAY NOT BE
ASSIGNED OR OTHERWISE TRANSFERRED.
THIS LIMITED WARRANTY IS IN LIEU OF ALL OTHER WARRANTIES, EXPRESED OR IMPLIED, INCLUDING WARRANTIES
OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE, AND THERE ARE NO WARRANTIES WHICH
EXTEND BEYOND THE DESCRIPTION ON THE FACE HEREOF.
Spinnaker Industries maintains a continuous product improvement policy , therefore specifications are subject to change without notice