Simplex 4100U
Step up to the next generation
in fire protection
4100U Addressable c.i.e.
Based on the established power and flexibility of the 4100 Series products, the new 4100U Series offers
additional operator, installation and service features, including new hardware and software that provides
higher performance and convenient operation, installation and maintenance.
Features
General
• Easy expansion with addressable loop and
collective zone cards
The Simplex 4100U is an analogue addressable fire
• On-site line programmable for a wide variety of
applications with upload/download facility
features to satisfy a wide variety of applications and site
• Supports collective detector inputs and MAPNET
and IDNet analogue addressable loops
On-site programmability allows mapping logic for
alarm system that provides extensive and powerful
requirements.
• 127 devices per MAPNET loop, 250 devices per
IDNet loop
inputs and outputs, custom labelling, and later revisions.
• Up to 30 loops per 4100U, 2,000 points in total
2,000 points.
• Wide range of addressable devices - detectors,
sounder bases, input/output modules and 420mA analogue input module
• Networkable into large systems (4 networks of 99
panels)
Detector and control point expansion is available up to
For quantities exceeding this, multiple panels can be
networked together to form a 4100U network system,
with a 4100U configured as a Network Display Unit to
provide annunciation and control of up to 12,000 points.
• Network Display Unit available for annunciation
and control of up to 12,000 devices for large
network systems
Fire Detection
System Overview
Based on the established power and
flexibility of the 4100 Series products,
the new 4100U Series offers additional
operator, installation and service features,
including new hardware and software
that provides higher performance and
convenient operation, installation and
maintenance.
Point capacity has doubled to 2,000
points. IDNet (addressable loop) cards
support 250 devices, without restrictions
on the quantities of point types.
New panel mounted cards & modules
are smaller, have enhanced capabilities
(including earth fault search) and power
limiting. The card firmware is upgraded
via download – no more changing
EPROMS. Built in diagnostics have been
enhanced.
New addressable modules include loop
powered 4 input/2 output, input/output
with current limited sensing, addressable
line isolator, power isolator and multisensor with selectable (patented)
detection algorithms. Each module
occupies one IDNet address.
New 4100U programming software
has additional features including panel
upload and download, import and export
panel data with Microsoft Excel, Custom
Control wizards, generation of panel label
inserts and a checklist that warns when
not all programming steps are completed.
Configurable
Starting with a minimal 4100U,
consisting of an addressable loop with
250 device capacity, 3 supervised
outputs, an ASE interface, power supply
and 8 zones of AS 4428 compliant
indication and control, the 4100U can be
configured as the project’s needs change.
Increasing the panel’s capacity to 500
addressable devices and 32 zones only
requires an IDNet card and 3 8 Zone
LED/Switch modules that can all be fitted
on site in less than 10 minutes.
Scalable
The 4100U can be configured to be a
zone based collective panel or a 2,000
analogue point addressable panel,
with up to 30 loops (or combination of
conventional zones and addressable
loops). Mimic panels, fire fan controls,
VESDA and graphics are only a few of the
many additions the 4100U can support.
All expansion cards and modules can
be in a central FIP or distributed around
the site in Remote Miniplex Transponder
Units (RTU).
For larger or multi-building projects, the
4100U can be networked with up to 99
panels on a network, with a capacity of
50,000 points per network.
Compatible
Backwards compatibility has always been
a feature of all Simplex panels. Even a 20
year old Simplex 2120 can be interfaced
with the 4100U, using factory tested &
documented procedures. Existing 4100
panels can be upgraded to 4100U point
& processing capabilities & still use the
old 4100 expansion cards in the existing
cabinet. The 4100U is compatible with
existing 4120 networks.
Connectable
The trend towards computer based
building services has exploded and the
4100U can communicate with most
systems, including VESDAnet, BACnet,
Intranet/Internet (with panel generated
emailing of alarms, faults & isolations),
GPS based time & date, Interface to
QE90 EWIS, most makes of BMS, PC
Annunciator (with LAN support). Due to
the worldwide popularity of the 4100U,
applications interfacing information is
widely available, from Simplex, third party
equipment makers & the internet.
Features
• Easy expansion with addressable loop and conventional zone cards
• On-site programmable for a wide variety of applications
• Supports on-site upload & download of panel program
• Supports conventional detector inputs and MAPNET and IDNet
analogue addressable loops
• 127 devices per MAPNET loop, 250 devices per IDNet loop
• Up to 30 loops per 4100U, 2,000 points in total
• Wide range of addressable devices - detectors, sounder bases,
input/output modules and 4-20mA analogue input module
4100U Operator Keypad
• AS 1668 Fan Control module (4 fans) with rotary switches and fan
status LEDs
• 9A System Power Supply (SPS) module includes built-in IDNet analogue loop driver
• Remote MINIPLEX Transponders and serial annunciators
• Networkable into large systems (4 networks of 99 panels)
• Dial-in service modem (option)
• RS232 interfaces for PC annunciators and remote printers (option)
• Panel mount printer (option)
• Four operator access levels
• 1200 event historical log (separate alarm/fault logs)
• Walk test and individual point disconnect/disable
• Programmable alarm verification, output logic control, alarm thresholds, network operation and annunciation
• SafeLinc Internet Interface Card available for remote access via client LAN
• High level links to EWIS, BMS and BACnet
• 19” rack compatible cabinet range - 18U, 21U, 28U & 40U cabinet configuration
4100U Analogue Addressable Controller
4100U / 4120
Up to 4 Loops
IMS
4100
Administration
4100U
Theatre
PULL TO OPEN DOOR
P ULL TO O P E N DO O R
OPERATOR
EMER G EN CY OPER AT IN G
IN ST R U C T ION S
SYSTEM IS NORMAL
12:35:15 am MON 12 JUN 95
. . .. ..
INTE RFA CE
FI RE
PA NEL
A L AR M
ALARM
AL AR M
ACK
AC
K
P R IO R IT Y 2
A LA R M
SY ST EM
. .
S IGN AL S
S Y ST E M
SU PE R V IS OR Y T R OU BL E
AL AR M
AC K
S U PV
AC K
P OW E R
SI L EN C ED
ON
AL AR M
S IL EN C E
S Y ST E M
R ES E T
PULL TO OPEN DOOR
P ULL TO O P E N DO O R
T O A C K N OW L ED GE :
- P R ES S "A C K " LO C AT ED U N D ER F L A SH I N G
I N D I C AT O R .
- R EPE AT OP E R AT I ON U N T IL A LL R EP OR T S A R E
A C KN OW LE D GED .
OPERATOR
T O S IL EN C E A LA R M S I GN A LS :
- P R ES S "A LA R M S ILE N C E".
T BL
AC K
ACKN OWLED GE
4100U
Engineering
AL A R M OR T R OU B L E C ON D I T ION :
- S YST EM I N D I C AT OR F L A SH IN G, T O N E ON .
EMER G EN CY OPER AT IN G
IN ST R U C T ION S
AL A R M OR T R OU B L E C ON D I T ION :
- S YST EM I N D I C AT OR F L A SH IN G, T O N E ON .
SYSTEM IS NORMAL
12:35:15 am MON 12 JUN 95
. . .. ..
INTE RFA CE
T O R E S T O R E SY ST EM T O N O R M A L :
- P R ES S "S YS T EM R ES ET ."
- P R ES S "A C K " T O SI L EN C E T O N E D E VIC E.
P R IO R IT Y 2
FI R E
PA NEL
A L AR M
ALARM
AL AR M
ACK
AC
K
A LA R M
AL AR M
AC K
SY ST EM
S Y ST E M
SU PE R V IS OR Y T R OU BL E
S U PV
AC K
T BL
AC K
. .
S IGN AL S
T O A C K N OW L ED GE :
- P R ES S "A C K " LO C AT ED U N D ER F L A SH I N G
I N D I C AT O R .
- R EPE AT OP E R AT I ON U N T IL A LL R EP OR T S A R E
A C KN OW LE D GED .
P OW E R
SI L EN C ED
ON
AL AR M
S IL EN C E
S Y ST E M
R ES E T
T O S IL EN C E A LA R M S I GN A LS :
- P R ES S "A LA R M S ILE N C E".
T O R E S T O R E SY ST EM T O N O R M A L :
- P R ES S "S YS T EM R ES ET ."
- P R ES S "A C K " T O SI L EN C E T O N E D E VIC E.
ACKN OWLED GE
4100
Education
PULL TO OPEN DOOR
P ULL TO O P E N DO O R
OPERATOR
FI R E
PA NEL
P ULL TO O P E N DO O R
. . .. ..
INTE RFA CE
FI R E
PA NEL
A L AR M
ALARM
AL AR M
ACK
K
AC
P R IO R IT Y 2
A LA R M
AL AR M
AC K
SY ST EM
S Y ST E M
SU PE R V IS OR Y T R OU BL E
S U PV
AC K
T BL
AC K
. .
S IGN AL S
P OW E R
SI L EN C ED
ON
AL AR M
S IL EN C E
S Y ST E M
R ES E T
ALARM
AL AR M
ACK
AC
K
ALL
CLEAR
BRITISH
EVAC
CHIME
ALL
CLEAR
SLOW
WHOOP
GSA
TONE
ALL
SPEAKERS
120 BPM
HORN
MANUAL
AUDIO
OVERRIDE
STUTTER
PHONE
PAGING
HI-L O
LOCAL
SPEAKER
WAIL
AL AR M
AC K
SY ST EM
S Y ST E M
SU PE R V IS OR Y T R OU BL E
S U PV
AC K
T BL
AC K
. .
S IGN AL S
P OW E R
SI L EN C ED
ON
AL AR M
S IL EN C E
S Y ST E M
R ES E T
AL A R M OR T R OU B L E C ON D I T ION :
- S YST EM I N D I C AT OR F L A SH IN G, T O N E ON .
T O A C K N OW L ED GE :
- P R ES S "A C K " LO C AT ED U N D ER F L A SH I N G
I N D I C AT O R .
- R EPE AT OP E R AT I ON U N T IL A LL R EP OR T S A R E
A C KN OW LE D GED .
T O S IL EN C E A LA R M S I GN A LS :
- P R ES S "A LA R M S ILE N C E".
T O R E S T O R E SY ST EM T O N O R M A L :
- P R ES S "S YS T EM R ES ET ."
- P R ES S "A C K " T O SI L EN C E T O N E D E VIC E.
T O R E S T O R E SY ST EM T O N O R M A L :
- P R ES S "S YS T EM R ES ET ."
- P R ES S "A C K " T O SI L EN C E T O N E D E VIC E.
ALL
SPEAKERS
EVAC
FEMALE
VO ICE
EVAC
HO RN
WEATHER
WARNING
A LA R M
T O A C K N OW L ED GE :
- P R ES S "A C K " LO C AT ED U N D ER F L A SH I N G
I N D I C AT O R .
- R EPE AT OP E R AT I ON U N T IL A LL R EP OR T S A R E
A C KN OW LE D GED .
WEATHER
WARNING
ALL
SPEAKERS
EVAC
6TH FL
SPEAKERS
P R IO R IT Y 2
ACKN OWLED GE
AL A R M OR T R OU B L E C ON D I T ION :
- S YST EM I N D I C AT OR F L A SH IN G, T O N E ON .
T O S IL EN C E A LA R M S I GN A LS :
- P R ES S "A LA R M S ILE N C E".
ACKN OWLED GE
4100
A L AR M
EMER G EN CY OPER AT IN G
IN ST R U C T ION S
SYSTEM IS NORMAL
12:35:15 am MON 12 JUN 95
EMER G EN CY OPER AT IN G
IN ST R U C T ION S
SYSTEM IS NORMAL
12:35:15 am MON 12 JUN 95
. . .. ..
INTE RFA CE
PULL TO OPEN DOOR
OPERATOR
PHONE
CIRCUIT
MEDICAL
EMERGENCY
FRENCH /
ENGLISH
EVAC
INDUSTRIAL
FIRE
SPANISH/
ENGLISH
EVAC
CHEMICAL
EMERGENCY
JAPANESE
EVAC
HAZARDO US
MATERIAL
SECURITY
BYPASS
CHLORINE
LEAK
WATCHTOUR
VOICE
CO DE
3- 1-6-4
NIG HT
SENSITIVITY
6TH FL
SPEAKERS
Physical Plant ( IMS)
FEMALE
VO ICE
EVAC
HO RN
BRITISH
EVAC
CHIME
SLOW
WHOOP
GSA
TONE
ALL
SPEAKERS
120 BPM
HORN
MANUAL
AUDIO
OVERRIDE
STUTTER
PHONE
PAGING
HI-L O
LOCAL
SPEAKER
WAIL
4100
PHONE
CIRCUIT
ALL
SPEAKERS
EVAC
FEMALE
VO ICE
EVAC
HO RN
WEATHER
WARNING
PHONE
CIRCUIT
MEDICAL
EMERGENCY
BRITISH
EVAC
CHIME
ALL
CLEAR
SLOW
WHOOP
GSA
TONE
6TH FL
SPEAKERS
FRENCH /
ENGLISH
EVAC
INDUSTRIAL
FIRE
SPANISH/
ENGLISH
EVAC
CHEMICAL
EMERGENCY
JAPANESE
EVAC
HAZARDO US
MATERIAL
SECURITY
BYPASS
CHLORINE
LEAK
ALL
SPEAKERS
120 BPM
HORN
MANUAL
AUDIO
OVERRIDE
STUTTER
PHONE
PAGING
HI-L O
WATCHTOUR
VOICE
CO DE
3- 1-6-4
LOCAL
SPEAKER
WAIL
NIG HT
SENSITIVITY
4100
ALL
SPEAKERS
EVAC
WEATHER
WARNING
INDUSTRIAL
FIRE
CHEMICAL
EMERGENCY
JAPANESE
EVAC
HAZARDO US
MATERIAL
CHLORINE
LEAK
VOICE
CO DE
3- 1-6-4
PHONE
CIRCUIT
BRITISH
EVAC
SLOW
WHOOP
MEDICAL
EMERGENCY
FRENCH /
ENGLISH
EVAC
INDUSTRIAL
FIRE
SPANISH/
ENGLISH
EVAC
CHEMICAL
EMERGENCY
JAPANESE
EVAC
HAZARDO US
MATERIAL
SECURITY
BYPASS
CHLORINE
LEAK
WATCHTOUR
VOICE
CO DE
3- 1-6-4
GSA
TONE
120 BPM
HORN
MANUAL
AUDIO
OVERRIDE
STUTTER
PHONE
PAGING
HI-L O
LOCAL
SPEAKER
WAIL
NIG HT
SENSITIVITY
FIRE ALARM CONTROL
4100
MEDICAL
EMERGENCY
FRENCH /
ENGLISH
EVAC
SPANISH/
ENGLISH
EVAC
SECURITY
BYPASS
WATCHTOUR
FEMALE
VO ICE
EVAC
HO RN
CHIME
ALL
CLEAR
6TH FL
SPEAKERS
ALL
SPEAKERS
FIRE ALARM CONTROL
NIG HT
SENSITIVITY
FIRE ALARM CONTROL
FIRE ALARM CONTROL
PULL TO OPEN DOOR
P ULL TO O P E N DO O R
PULL TO OPEN DOOR
P ULL TO O P E N DO O R
OPERATOR
EMER G EN CY OPER AT IN G
IN ST R U C T ION S
SYSTEM IS NORMAL
12:35:15 am MON 12 JUN 95
. . .. ..
INTE RFA CE
FI RE
PA NEL
A L AR M
ALARM
AL AR M
ACK
AC
K
P R IO R IT Y 2
A LA R M
AL AR M
AC K
SY ST EM
S Y ST E M
SU PE R V IS OR Y T R OU BL E
S U PV
AC K
T BL
AC K
. .
S IGN AL S
P OW E R
SI L EN C ED
ON
AL AR M
S IL EN C E
S Y ST E M
R ES E T
AL A R M OR T R OU B L E C ON D I T ION :
- S YST EM I N D I C AT OR F L A SH IN G, T O N E ON .
T O A C K N OW L ED GE :
- P R ES S "A C K " LO C AT ED U N D ER F L A SH I N G
I N D I C AT O R .
- R EPE AT OP E R AT I ON U N T IL A LL R EP OR T S A R E
A C KN OW LE D GED .
OPERATOR
EMER G EN CY OPER AT IN G
IN ST R U C T ION S
AL A R M OR T R OU B L E C ON D I T ION :
- S YST EM I N D I C AT OR F L A SH IN G, T O N E ON .
SYSTEM IS NORMAL
12:35:15 am MON 12 JUN 95
. . .. ..
INTE RFA CE
FI RE
PA NEL
A L AR M
ALARM
AL AR M
ACK
AC K
T O S IL EN C E A LA R M S I GN A LS :
- P R ES S "A LA R M S ILE N C E".
ACKN OWLED GE
P R IO R IT Y 2
A LA R M
AL AR M
AC K
SY ST EM
S Y ST E M
SU PE R V IS OR Y T R OU BL E
S U PV
AC K
T BL
AC K
. .
S IGN AL S
T O A C K N OW L ED GE :
- P R ES S "A C K " LO C AT ED U N D ER F L A SH I N G
I N D I C AT O R .
- R EPE AT OP E R AT I ON U N T IL A LL R EP OR T S A R E
A C KN OW LE D GED .
P OW E R
SI L EN C ED
ON
AL AR M
S IL EN C E
S Y ST E M
R ES E T
PULL TO OPEN DOOR
T O S IL EN C E A LA R M S I GN A LS :
- P R ES S "A LA R M S ILE N C E".
ACKN OWLED GE
P ULL TO O P E N DO O R
T O R E S T O R E SY ST EM T O N O R M A L :
- P R ES S "S YS T EM R ES ET ."
- P R ES S "A C K " T O SI L EN C E T O N E D E VIC E.
OPERATOR
T O R E S T O R E SY ST EM T O N O R M A L :
- P R ES S "S YS T EM R ES ET ."
- P R ES S "A C K " T O SI L EN C E T O N E D E VIC E.
FI RE
P ULL TO O P E N DO O R
FI R E
A L AR M
ALARM
AL AR M
ACK
K
AC
P R IO R IT Y 2
A LA R M
AL AR M
AC K
SY ST EM
S Y ST E M
SU PE R V IS OR Y T R OU BL E
S U PV
AC K
T BL
AC K
. .
S IGN AL S
ON
AL AR M
S IL EN C E
S Y ST E M
R ES E T
BRITISH
EVAC
T O R E S T O R E SY ST EM T O N O R M A L :
- P R ES S "S YS T EM R ES ET ."
- P R ES S "A C K " T O SI L EN C E T O N E D E VIC E.
INDUSTRIAL
FIRE
CHEMICAL
EMERGENCY
HAZARDO US
MATERIAL
STUTTER
SECURITY
BYPASS
CHLORINE
LEAK
HI-L O
WATCHTOUR
VOICE
CO DE
3- 1-6-4
WAIL
NIG HT
SENSITIVITY
GSA
TONE
120 BPM
HORN
MANUAL
AUDIO
OVERRIDE
PHONE
PAGING
LOCAL
SPEAKER
Loop 1
T O A C K N OW L ED GE :
- P R ES S "A C K " LO C AT ED U N D ER F L A SH I N G
I N D I C AT O R .
- R EPE AT OP E R AT I ON U N T IL A LL R EP OR T S A R E
A C KN OW LE D GED .
PHONE
CIRCUIT
MEDICAL
EMERGENCY
FRENCH /
ENGLISH
EVAC
SPANISH/
ENGLISH
EVAC
JAPANESE
EVAC
SLOW
WHOOP
6TH FL
SPEAKERS
ALL
SPEAKERS
ALL
SPEAKERS
EVAC
WEATHER
WARNING
ALL
CLEAR
6TH FL
SPEAKERS
FEMALE
VO ICE
EVAC
HO RN
BRITISH
EVAC
CHIME
SLOW
WHOOP
GSA
TONE
ALL
SPEAKERS
EVAC
PHONE
CIRCUIT
MEDICAL
EMERGENCY
FRENCH /
ENGLISH
EVAC
INDUSTRIAL
FIRE
SPANISH/
ENGLISH
EVAC
CHEMICAL
EMERGENCY
JAPANESE
EVAC
HAZARDO US
MATERIAL
SECURITY
BYPASS
CHLORINE
LEAK
ALL
SPEAKERS
120 BPM
HORN
MANUAL
AUDIO
OVERRIDE
STUTTER
PHONE
PAGING
HI-L O
WATCHTOUR
VOICE
CO DE
3- 1-6-4
LOCAL
SPEAKER
WAIL
NIG HT
SENSITIVITY
4100
FIRE ALARM CONTROL
WEATHER
WARNING
FEMALE
VO ICE
EVAC
HO RN
BRITISH
EVAC
CHIME
INDUSTRIAL
FIRE
CHEMICAL
EMERGENCY
HAZARDO US
MATERIAL
CHLORINE
LEAK
HI-L O
WATCHTOUR
VOICE
CO DE
3- 1-6-4
LOCAL
SPEAKER
WAIL
NIG HT
SENSITIVITY
ALL
CLEAR
SLOW
WHOOP
GSA
TONE
ALL
SPEAKERS
120 BPM
HORN
MANUAL
AUDIO
OVERRIDE
STUTTER
4100
Loop 2
PHONE
CIRCUIT
MEDICAL
EMERGENCY
FRENCH /
ENGLISH
EVAC
SPANISH/
ENGLISH
EVAC
JAPANESE
EVAC
SECURITY
BYPASS
PHONE
PAGING
6TH FL
SPEAKERS
P R IO R IT Y 2
A LA R M
AL AR M
AC K
SY ST EM
S Y ST E M
SU PE R V IS OR Y T R OU BL E
S U PV
AC K
T BL
AC K
. .
S IGN AL S
ON
AL AR M
S IL EN C E
S Y ST E M
R ES E T
AL A R M OR T R OU B L E C ON D I T ION :
- S YST EM I N D I C AT OR F L A SH IN G, T O N E ON .
T O A C K N OW L ED GE :
- P R ES S "A C K " LO C AT ED U N D ER F L A SH I N G
I N D I C AT O R .
- R EPE AT OP E R AT I ON U N T IL A LL R EP OR T S A R E
A C KN OW LE D GED .
T O S IL EN C E A LA R M S I GN A LS :
- P R ES S "A LA R M S ILE N C E".
FEMALE
VO ICE
EVAC
HO RN
BRITISH
EVAC
CHIME
P OW E R
SI L EN C ED
ACKN OWLED GE
ALL
SPEAKERS
EVAC
WEATHER
WARNING
T O R E S T O R E SY ST EM T O N O R M A L :
- P R ES S "S YS T EM R ES ET ."
- P R ES S "A C K " T O SI L EN C E T O N E D E VIC E.
PHONE
CIRCUIT
MEDICAL
EMERGENCY
FRENCH /
ENGLISH
EVAC
INDUSTRIAL
FIRE
SPANISH/
ENGLISH
EVAC
CHEMICAL
EMERGENCY
JAPANESE
EVAC
HAZARDO US
MATERIAL
STUTTER
SECURITY
BYPASS
CHLORINE
LEAK
PHONE
PAGING
HI-L O
WATCHTOUR
VOICE
CO DE
3- 1-6-4
LOCAL
SPEAKER
WAIL
NIG HT
SENSITIVITY
ALL
CLEAR
6TH FL
SPEAKERS
SLOW
WHOOP
GSA
TONE
ALL
SPEAKERS
120 BPM
HORN
MANUAL
AUDIO
OVERRIDE
FIRE ALARM CONTROL
4100
4100
A L AR M
ALARM
AL AR M
ACK
AC
K
AL A R M OR T R OU B L E C ON D I T ION :
- S YST EM I N D I C AT OR F L A SH IN G, T O N E ON .
T O S IL EN C E A LA R M S I GN A LS :
- P R ES S "A LA R M S ILE N C E".
FEMALE
VO ICE
EVAC
HO RN
CHIME
P OW E R
SI L EN C ED
ACKN OWLED GE
ALL
CLEAR
EMER G EN CY OPER AT IN G
IN ST R U C T ION S
SYSTEM IS NORMAL
12:35:15 am MON 12 JUN 95
. . .. ..
INTE RFA CE
WEATHER
WARNING
EMER G EN CY OPER AT IN G
IN ST R U C T ION S
SYSTEM IS NORMAL
12:35:15 am MON 12 JUN 95
. . .. ..
INTE RFA CE
PA NEL
PULL TO OPEN DOOR
OPERATOR
PA NEL
ALL
SPEAKERS
EVAC
FIRE ALARM CONTROL
FIRE ALARM CONTROL
NDU
Commerce
& Finance
4100
Library
PULL TO OPEN DOOR
P ULL TO O P E N DO O R
OPERATOR
FI R E
P ULL TO O P E N DO O R
FI R E
A L AR M
ALARM
AL AR M
ACK
AC K
P R IO R IT Y 2
A LA R M
AL AR M
AC K
SY ST EM
S Y ST E M
SU PE R V IS OR Y T R OU BL E
S U PV
AC K
T BL
AC K
. .
S IGN AL S
A L AR M
EMER G EN CY OPER AT IN G
IN ST R U C T ION S
SYSTEM IS NORMAL
12:35:15 am MON 12 JUN 95
. . .. ..
INTE RFA CE
P OW E R
SI L EN C ED
ON
AL AR M
S IL EN C E
S Y ST E M
R ES E T
EMER G EN CY OPER AT IN G
IN ST R U CT IONS
SYSTEM IS NORMAL
12:35:15 am MON 12 JUN 95
. . .. ..
INTE RFA CE
PA NEL
PULL TO OPEN DOOR
OPERATOR
PA NEL
ALARM
AL AR M
ACK
AC
K
P R IO R IT Y 2
A LA R M
AL AR M
AC K
SY ST EM
S Y ST E M
SU PE R V IS OR Y T R OU BL E
S U PV
AC K
T BL
AC K
. .
S IGN AL S
P OW E R
SI L EN C ED
ON
AL AR M
S IL EN C E
S Y ST E M
R ES E T
AL A R M OR T R OU B L E C ON D I T ION :
- S YST EM I N D I C AT OR F L A SH IN G, T O N E ON .
T O A C K N OW L ED GE :
- P R ES S "A C K " LO C AT ED U N D ER F L A SH I N G
I N D I C AT O R .
- R EPE AT OP E R AT I ON U N T IL A LL R EP OR T S A R E
A C KN OW LE D GED .
T O S IL EN C E A LA R M S I GN A LS :
- P R ES S "A LA R M S ILE N C E".
ACKN OWLED GE
AL A R M OR T R OU B L E C ON D I T ION :
- S YST EM I N D I C AT OR F L A SH IN G, T O N E ON .
T O R E S T O R E SY ST EM T O N O R M A L :
- P R ES S "S YS T EM R ES ET ."
- P R ES S "A C K " T O SI L EN C E T O N E D E VIC E.
T O A C K N OW L ED GE :
- P R ES S "A C K " LO C AT ED U N D ER F L A SH I N G
I N D I C AT O R .
- R EPE AT OP E R AT I ON U N T IL A LL R EP OR T S A R E
A C KN OW LE D GED .
T O S IL EN C E A LA R M S I GN A LS :
- P R ES S "A LA R M S ILE N C E".
ACKN OWLED GE
T O R E S T O R E SY ST EM T O N O R M A L :
- P R ES S "S YS T EM R ES ET ."
- P R ES S "A C K " T O SI L EN C E T O N E D E VIC E.
NDU
Nursing
4100
Dormitory B
PULL TO OPEN DOOR
P ULL TO O P E N DO O R
OPERATOR
EMER G EN CY OPER AT IN G
IN ST R U CT ION S
SYSTEM IS NORMAL
12:35:15 am MON 12 JUN 95
. . .. ..
INTE RFA CE
FI R E
PA NEL
A L AR M
P R IO R IT Y 2
A LA R M
ALARM
AL AR M
ACK
K
AC
AL AR M
AC K
SY ST EM
S Y ST E M
SU PE R V IS OR Y T R OU BL E
S U PV
AC K
T BL
AC K
. .
S IGN AL S
P OW E R
SI L EN C ED
ON
AL AR M
S IL EN C E
S Y ST E M
R ES E T
AL A R M OR T R OU B L E C ON D I T ION :
- S YST EM I N D I C AT OR F L A SH IN G, T O N E ON .
T O A C K N OW L ED GE :
- P R ES S "A C K " LO C AT ED U N D ER F L A SH I N G
I N D I C AT O R .
- R EPE AT OP E R AT I ON U N T IL A LL R EP OR T S A R E
A C KN OW LE D GED .
T O S IL EN C E A LA R M S I GN A LS :
- P R ES S "A LA R M S ILE N C E".
ACKN OWLED GE
T O R E S T O R E SY ST EM T O N O R M A L :
- P R ES S "S YS T EM R ES ET ."
- P R ES S "A C K " T O SI L EN C E T O N E D E VIC E.
PULL TO OPEN DOOR
P ULL TO O P E N DO O R
OPERATOR
FI RE
PA NEL
A L AR M
ALARM
AL AR M
ACK
K
AC
P R IO R IT Y 2
A LA R M
AL AR M
AC K
SY ST EM
S Y ST E M
SU PE R V IS OR Y T R OU BL E
S U PV
AC K
T BL
AC K
PA NEL
EMER G EN CY OPER AT IN G
IN ST R U C T ION S
. .
S IGN AL S
P OW E R
SI L EN C ED
ON
AL AR M
S IL EN C E
S Y ST E M
R ES E T
ALARM
AL AR M
ACK
K
AC
ALL
SPEAKERS
EVAC
WEATHER
WARNING
ALL
CLEAR
INDUSTRIAL
FIRE
HAZARDO US
MATERIAL
CHLORINE
LEAK
VOICE
CO DE
3- 1-6-4
SLOW
WHOOP
GSA
TONE
120 BPM
HORN
NIG HT
SENSITIVITY
6TH FL
SPEAKERS
BRITISH
EVAC
GSA
TONE
WEATHER
WARNING
PHONE
CIRCUIT
MEDICAL
EMERGENCY
FRENCH /
ENGLISH
EVAC
INDUSTRIAL
FIRE
SPANISH/
ENGLISH
EVAC
CHEMICAL
EMERGENCY
JAPANESE
EVAC
HAZARDO US
MATERIAL
SECURITY
BYPASS
CHLORINE
LEAK
120 BPM
HORN
STUTTER
PHONE
PAGING
HI-L O
WATCHTOUR
VOICE
CO DE
3- 1-6-4
LOCAL
SPEAKER
WAIL
ALL
CLEAR
FEMALE
VO ICE
EVAC
HO RN
BRITISH
EVAC
CHIME
SLOW
WHOOP
GSA
TONE
INDUSTRIAL
FIRE
CHEMICAL
EMERGENCY
HAZARDO US
MATERIAL
SECURITY
BYPASS
CHLORINE
LEAK
VOICE
CO DE
3- 1-6-4
120 BPM
HORN
MANUAL
AUDIO
OVERRIDE
STUTTER
PHONE
PAGING
HI-L O
LOCAL
SPEAKER
WAIL
NIG HT
SENSITIVITY
4100
A LA R M
AL AR M
AC K
SY ST EM
S Y ST E M
SU PE R V IS OR Y T R OU BL E
S U PV
AC K
T BL
AC K
EMER G EN CY OPER AT IN G
IN ST R U C T ION S
. .
S IGN AL S
P OW E R
SI L EN C ED
ON
AL AR M
S IL EN C E
S Y ST E M
R ES E T
PULL TO OPEN DOOR
P ULL TO O P E N DO O R
INDUSTRIAL
FIRE
CHEMICAL
EMERGENCY
JAPANESE
EVAC
HAZARDO US
MATERIAL
SECURITY
BYPASS
CHLORINE
LEAK
HI-L O
WATCHTOUR
VOICE
CO DE
3- 1-6-4
LOCAL
SPEAKER
WAIL
ALL
CLEAR
SLOW
WHOOP
GSA
TONE
T O A C K N OW L ED GE :
- P R ES S "A C K " LO C AT ED U N D ER F L A SH I N G
I N D I C AT O R .
- R EPE AT OP E R AT I ON U N T IL A LL R EP OR T S A R E
A C KN OW LE D GED .
OPERATOR
SYSTEM IS NORMAL
12:35:15 am MON 12 JUN 95
. . .. ..
INTE RFA CE
FI R E
PA NEL
T O R E S T O R E SY ST EM T O N O R M A L :
- P R ES S "S YS T EM R ES ET ."
- P R ES S "A C K " T O SI L EN C E T O N E D E VIC E.
A L AR M
ALARM
AL AR M
ACK
K
AC
P R IO R IT Y 2
A LA R M
AL AR M
AC K
SY ST EM
S Y ST E M
SU PE R V IS OR Y T R OU BL E
S U PV
AC K
T BL
AC K
. .
S IGN AL S
4100
FIRE ALARM CONTROL
FIRE ALARM CONTROL
4100U
Infirmary
FIRE ALARM CONTROL
4100
Dormitory A
FEMALE
VO ICE
EVAC
HO RN
BRITISH
EVAC
CHIME
ON
AL AR M
S IL EN C E
S Y ST E M
R ES E T
AL A R M OR T R OU B L E C ON D I T ION :
- S YST EM I N D I C AT OR F L A SH IN G, T O N E ON .
T O A C K N OW L ED GE :
- P R ES S "A C K " LO C AT ED U N D ER F L A SH I N G
I N D I C AT O R .
- R EPE AT OP E R AT I ON U N T IL A LL R EP OR T S A R E
A C KN OW LE D GED .
T O S IL EN C E A LA R M S I GN A LS :
- P R ES S "A LA R M S ILE N C E".
T O R E S T O R E SY ST EM T O N O R M A L :
- P R ES S "S YS T EM R ES ET ."
- P R ES S "A C K " T O SI L EN C E T O N E D E VIC E.
PHONE
CIRCUIT
INDUSTRIAL
FIRE
CHEMICAL
EMERGENCY
HAZARDO US
MATERIAL
SECURITY
BYPASS
CHLORINE
LEAK
HI-L O
WATCHTOUR
VOICE
CO DE
3- 1-6-4
LOCAL
SPEAKER
WAIL
NIG HT
SENSITIVITY
SLOW
WHOOP
GSA
TONE
ALL
SPEAKERS
120 BPM
HORN
MANUAL
AUDIO
OVERRIDE
4100
ALL
SPEAKERS
EVAC
MEDICAL
EMERGENCY
FRENCH /
ENGLISH
EVAC
SPANISH/
ENGLISH
EVAC
JAPANESE
EVAC
STUTTER
PHONE
PAGING
ALL
CLEAR
4100
Gymnasium
P OW E R
SI L EN C ED
NIG HT
SENSITIVITY
6TH FL
SPEAKERS
4100
EMER G EN CY OPER AT IN G
IN ST R U C T ION S
AL A R M OR T R OU B L E C ON D I T ION :
- S YST EM I N D I C AT OR F L A SH IN G, T O N E ON .
T O S IL EN C E A LA R M S I GN A LS :
- P R ES S "A LA R M S ILE N C E".
PHONE
CIRCUIT
MEDICAL
EMERGENCY
BRITISH
EVAC
FRENCH /
ENGLISH
EVAC
SPANISH/
ENGLISH
EVAC
120 BPM
HORN
STUTTER
PHONE
PAGING
PHONE
CIRCUIT
MEDICAL
EMERGENCY
FRENCH /
ENGLISH
EVAC
SPANISH/
ENGLISH
EVAC
JAPANESE
EVAC
WATCHTOUR
ALL
SPEAKERS
P R IO R IT Y 2
ACKN OWLED GE
FEMALE
VO ICE
EVAC
CHIME
ALL
SPEAKERS
MANUAL
AUDIO
OVERRIDE
6TH FL
SPEAKERS
NIG HT
SENSITIVITY
WEATHER
WARNING
WEATHER
WARNING
4100U
Science
FEMALE
VO ICE
EVAC
HO RN
CHIME
SLOW
WHOOP
ALL
SPEAKERS
MANUAL
AUDIO
OVERRIDE
ALL
SPEAKERS
EVAC
ALL
SPEAKERS
EVAC
6TH FL
SPEAKERS
FIRE ALARM CONTROL
HO RN
ACKN OWLED GE
ALL
SPEAKERS
EVAC
T O R E S T O R E SY ST EM T O N O R M A L :
- P R ES S "S YS T EM R ES ET ."
- P R ES S "A C K " T O SI L EN C E T O N E D E VIC E.
PHONE
CIRCUIT
MEDICAL
EMERGENCY
CHEMICAL
EMERGENCY
SECURITY
BYPASS
WATCHTOUR
WAIL
ALL
CLEAR
A L AR M
AL A R M OR T R OU B L E C ON D I T ION :
- S YST EM I N D I C AT OR F L A SH IN G, T O N E ON .
T O A C K N OW L ED GE :
- P R ES S "A C K " LO C AT ED U N D ER F L A SH I N G
I N D I C AT O R .
- R EPE AT OP E R AT I ON U N T IL A LL R EP OR T S A R E
A C KN OW LE D GED .
T O S IL EN C E A LA R M S I GN A LS :
- P R ES S "A LA R M S ILE N C E".
ACKN OWLED GE
BRITISH
EVAC
FRENCH /
ENGLISH
EVAC
SPANISH/
ENGLISH
EVAC
JAPANESE
EVAC
HI-L O
LOCAL
SPEAKER
SYSTEM IS NORMAL
12:35:15 am MON 12 JUN 95
FI R E
P ULL TO O P E N DO O R
SYSTEM IS NORMAL
12:35:15 am MON 12 JUN 95
. . .. ..
INTE RFA CE
FEMALE
VO ICE
EVAC
HO RN
CHIME
STUTTER
PHONE
PAGING
ALL
SPEAKERS
MANUAL
AUDIO
OVERRIDE
. . .. ..
INTE RFA CE
PULL TO OPEN DOOR
OPERATOR
ALL
SPEAKERS
EVAC
WEATHER
WARNING
6TH FL
SPEAKERS
4100
FIRE ALARM CONTROL
BRITISH
EVAC
CHIME
ALL
CLEAR
4100
Cafeteria
FEMALE
VO ICE
EVAC
HO RN
WEATHER
WARNING
SLOW
WHOOP
GSA
TONE
6TH FL
SPEAKERS
ALL
SPEAKERS
120 BPM
HORN
MANUAL
AUDIO
OVERRIDE
STUTTER
INDUSTRIAL
FIRE
CHEMICAL
EMERGENCY
JAPANESE
EVAC
HAZARDO US
MATERIAL
SECURITY
BYPASS
CHLORINE
LEAK
VOICE
CO DE
3- 1-6-4
HI-L O
LOCAL
SPEAKER
WAIL
NIG HT
SENSITIVITY
4100
PHONE
CIRCUIT
MEDICAL
EMERGENCY
FRENCH /
ENGLISH
EVAC
SPANISH/
ENGLISH
EVAC
WATCHTOUR
PHONE
PAGING
FIRE ALARM CONTROL
4100
Dormitory C
4100/4120 Network Multi-Loop Expansion
Maintenance
Maintenance
Graphic Command Ctr
terminal
terminal
Typical site with multiple buildings
printer
Switchroom
Hardwired
. .
F I RE
SYSE
T
IG M P
S
NO
AL N
S IR N D I C
O
W
E
AT
O
ACA
KCK
R.
PRES" AL AR
M
RSET
E
IS L E N C E
".
Central Station
. .
F I RE
ACK
ACK
Modem communication
OA
P
W L IS
EN
RDI A
IG M N
S
SYSE
T
CO
T R.
O N
E -S E P
R
T RES" AL AR
M
IS L E N C E
".
Warehouse
Fibre Optic
. .
S Y S IG
E
T MP
S
NW
AL E
S
O
I R
NDI A
CO
T R.
O N
ES
R
ACA
KCK
- ET
PRES" AL AR
M
F I RE
IS L E N C E
".
Security
Computer
room
. .
F I RE
Fibre Optic
ACKACK
O L IS
NN
OA
P
W
E
RDI C
IG M N
S
SYSE
T
AT
O
R.
PRES" AL AR
M
RSET
E
IS L E N C ".E
. .
F II R
RE
E
F
AC
CK
K
AC
CK
KA
A
O LL IS
NN
OA
P
W
E
RD
IG M
S
N
A
SY
YS
SE
E
T
MN
IS
N
D II C
AT
C
T
O
O
N
O
P
W
E
R
IG
S
S
T
A
O
R ..
R
PR
RE
ES
S "" A
A LL A
AR
M
R
-P
M
ES
R
SE
ET
T
R
E
I LL E
S
EN
NC
CE
".
IS
".E
Office
Hardwired
Flexible Network Communications
• Communicates information along remote Fire Alarm Control
Panel locations (defined as Network Nodes)
• Initiates Alarm Silence, Acknowledge and Reset
• Displays status of selected circuit points, point lists and
network nodes
• TrueAlarm Sensor Operation:- Read status of TrueAlarm Analogue detection sensors at
multiple locations
- Remote or local sensitivity selection
• Style 7 wired communications:-
• Investigate specific point status details
- Single wire pair between nodes
• Annunciate system alarm from Control Panels Network Nodes
including:-
- Up to 5km between nodes with twisted shielded wire
- 4100 series Fire Alarm Control Panels
- 4120 series Network Processing Units (NDU), Network
Display Units (2500NDU) and MINIPLEX� and Universal
Transponders (UT)
- 4190 series Information Manangement Systems (IMS)
• Retrofit into existing 4100 and 2120 systems
• Optional Fibre Optics communications
• Full Network communication supervision:- Network level diagnostics
- LED Status indications on interface board
• Set host function accesses remote node data
• Remote dial-in modem for off-site data access
4100U Analogue Addressable Controller
Specifications
System Capacity
Panel Capacity
2,000 points of Addressable input / output devices or collective zones.
Networked System Capacity 99 networked panels (2,000 points/ panel)
Mechanical
Cabinet Size(mm)
Cabinet Material
Cabinet Finish
Cabinet Colour
Dependant on system configuration. Wall mounted.
1.6mm mild steel
Powder coated
Cream Wrinkle BFF998CW
Electrical
Mains Input
Power Supply Output
Standby Battery
Battery Charger
PSU Supervision
240V AC @ 2A +6%,-10%,50/60Hz
28.5Vdc @ 9A
24V sealed lead acid up to 80Ah
28.5Vdc (nominal)
Charger high/low,Battery low/fail
Environmental
Temperature
Humidity
0°C to +45°C
10% to 90% RH (non-condensing)
Expansion Modules
Maximum Number
4100 - 5002/5004
4100 - 3003
4100 - 4322
4100 - 0113
4100 - 6011
4100 - 0110
4100 - 3101
4100 - 0304
4100 - 3024
4100 - 0301
4100 - 0154
119 modules
Collective zone module; 8 zone circuits/module; Supports standard 20V
detectors plus normally open contact devices
8 Point Auxiliary Relay Module; 8 CPU controlled auxiliary relays/module SPDT
contacts rated for 3 amps @ 24Vdc or 30VAC
6 Circuit Supervised Signal Module; 6 Style Y (class B) circuits per module
RS-232/2120 Communications Module; Provides two RS-232-C outputs for
remote printers and/or CRT; 5x RS-232-C ports max. per 4100U system; Can be
configured for communication with a host 2120 system; Can be configured as
a Computer Port for communications to a remote system ie BMS or BAS Systems
4120 Network Interface Module; RS485 Communications; Optional Fibre
Optics Media Card
MAPNET� TRUEALARM™ Addressable Loop Module; Up to 127 MAPNET
Addressable devices or TrueAlarm Analogue Sensors; Up to 30 MAPNET/IDNet
Loop Cards per system; Supports MAPNET Short Circuit Line Isolator Modules
IDNet Addressable Loop Module; up to 250 IDNet Addressable devices or
TrueAlarm Analogue sensors; up to 30 IDNet/MAPNET cards per 4100U system
Remote Unit Interface Module; Provides a supervised serial communications
channel to remotely located distributed Miniplex�Transponders and LCD
Annunciators; Up to 32 distributed Miniplex� Transponders and/or LCD
Annunciators per 4100U system
24 Relay Input/Output Relay Motherboard; 24 CPU controlled relays; Each of the
24 relays can be individually configured as either an input or an output, SPST
contacts rated for 0.5A @ 24Vdc or 30VAC
64/64 LED / SWITCH Controller Interfaces up to 64 LEDs and 64 switches to
the master controller for front panel annunciation
The Simplex� 4100U Fire Detection and
Alarm Platform is a high-end, next-generation
distributed network system that combines
superior fire protection and information
management with lower costs of installation,
maintenance and ownership. Designed to
meet the needs of engineers, facility managers,
building owners and electrical contractors,
the 4100U builds upon the field-proven
performance of the industry-leading Simplex
4100 Series fire systems. The 4100U adds
new technology, expanded point capacity,
advanced built-in diagnostics, dual operating
software and other enhancements. Moreover,
it has been specifically designed to allow
existing 4100 and 4120 network systems to
be upgraded rather than replaced.
When combined with an IMS graphic
workstation, the Simplex Fire Alarm Network is
capable of supporting 392 networked panels.
The 4100U platform links multiple 4100/
4100U control panels in a seamless, highly
survivable fire alarm network. Its advanced
peer-to-peer, token ring network provides
a communications platform for master
annunciation, control and information sharing
that does not require centralised processing.
This ensures unparalleled survivability
compared to conventional systems that rely
on central control. The system offers true
interactive, two-way communications between
the 4100U control panels, TrueAlarm�
smoke detectors and TrueAlert™ notification
appliances, with intelligent communications
extending all the way to each individual point
on the system for total addressability.
High Level Interface (HLI) to VESDA� LaserPLUS and LaserSCANNER
Operator Controls and Indications
Zone Status and Control
Individual Zone Alarm and Isolate LED with individual zone isolate/de-isolate
control
2 line by 40 character backlight LCD with adjustable contrast control
Additional Zone Status
LED Status and Control Indicators
Common Alarm, Fault & Isolate External Bell Isolated, Warning System Isolated,
Mains Power ON
Audible Buzzers (2 sounders) Panel sounder for Alarm, Fault, Isolate Conditions, CPU Piezo for keypad feedback
Keypad Controls
Operator Controls
Software Features
Ext. Bell & Warning System Isolate, Ack, System Reset, Isolate, Previous, Next,
Display Keys, Action Keys, Fault/Isolate Keys and Entry Keys, some with
programmable functions and labels for marking the function of each key
• WALK TEST System Test
• 4 Operator Access Levels
• 1200 Event Historical Logging (separate alarm/fault logs)
• Zone selectable Alarm Verification
• Individual Circuit Disconnect / Disable
• Nonvolatile Flash EPROM for field editable program changes
• Dual database configurations for reduced service programming time
• Upload/Download facility for greater service flexibility
• AS 4428 Compliance
Approved
The 4100U is certified to Australian
Standard AS 4428.1-1998:
“Fire detection, warning, control
and intercom systems - Control and
Indicating Equipment, Part 1: Fire”.
CSIRO ActivFire Listing No. afp-1682
tel: 1300 552 559
simplexfire.au@tycoint.com
www.simplexfire.com.au