ESIM364
GSM ALARM AND MANAGEMENT SYSTEM
Installation Manual v1.0
Valid for ESIM364 v02.03.00 and up
Safety instructions
Please read and follow these safety guidelines in order to maintain safety of operators and people around:
x GSM alarm & management system ESIM364 (also referenced as alarm system, system or device) has radio transceiver operating in GSM
850/900/1800/1900 bands.
x DO NOT use the system where it can be interfere with other devices and cause any potential danger.
x DO NOT use the system with medical devices.
x DO NOT use the system in hazardous environment.
x DO NOT expose the system to high humidity, chemical environment or mechanical impacts.
x DO NOT attempt to personally repair the system.
x System label is on the bottom side of the device.
GSM alarm system ESIM364 is a device mounted in limited access areas. Any system repairs must be done only by qualified,
safety aware personnel.
The system must be powered by main 16-24V 50 Hz ~1.5A max or 18-24V
1,5A max DC power supply which must be
approved by LST EN 60950-1 standard and be easily accessible nearby the device. When connecting the power supply to the
system, switching the pole terminals places does not have any affect.
Any additional devices linked to the system ESIM364 (computer, sensors, relays etc.) must be approved by LST EN 60950-1
standard.
Main power supply can be connected to AC mains only inside installation room
with automatic 2-pole circuit breaker capable of disconnecting circuit in the
event of short circuit or over-current condition. Open circuit breaker must have a
gap between connections of more than 3mm and the disconnection current 5A.
Phase
Null
PE
AC/DC
AC 230V
50 Hz/DC 24V
ESIM364
USB cable
Mains power and backup battery must be disconnected before any installation or tuning work starts. The system installation
or maintenance must not be done during stormy conditions
Backup battery must be connected via the connection which in the case of breaking would result in disconnection of one of
battery pole terminals. Special care must be taken when connecting positive and negative battery terminals. Switching the
pole terminals places is NOT allowed.
In order to avoid fire or explosion hazards the system must be used only with approved backup battery.
The device is fully turned off by disconnecting 2-pole switch off device of the main power supply and disconnecting backup
battery connector.
Fuse F1 type – Slow Blown 3A. Replacement fuses have to be exactly the same as indicated by the manufacturer.
If you use I security class computer for setting the parameters it must be connected to earth.
The WEEE (Waste Electrical and Electronic Equipment) marking on this product (see left) or its documentation indicates that
the product must not be disposed of together with household waste. To prevent possible harm to human health and/or the
environment, the product must be disposed on in an approved and environmentally safe recycling process. For further information on how to dispose of this product correctly, contact the system supplier, or the local authority responsible for waste
disposal in your area.
2
EN
MANUAL ELDES ESIM364 V1.0
Contents
1.
General Information ................................................................................................................................................................6
1.1. Functionality ......................................................................................................................................................................................................6
1.2. Compatible Device Overview ...........................................................................................................................................................................6
1.3. Default Parameters & Ways of Parameter Configuration ...........................................................................................................................6
2.
Technical Specifications .......................................................................................................................................................12
2.1. Electrical & Mechanical Characteristics .........................................................................................................................................................12
2.2. Main Unit, LED & Connector Functionality ....................................................................................................................................................13
2.3. Wiring Diagrams ................................................................................................................................................................................................14
3.
INSTALLATION ...................................................................................................................................................................... 20
4. GENERAL OPERATION ........................................................................................................................................................... 24
5.
CONFIGURATION METHODS ..................................................................................................................................................25
5.1. Remote System Configuration via GPRS Connection ............................................................................................................................... 26
6.
PASSWORDS .......................................................................................................................................................................... 28
7.
MULTI-LANGUAGE SUPPORT ................................................................................................................................................ 29
8. USER PHONE NUMBERS ....................................................................................................................................................... 30
8.1. User Phone Number Names ..........................................................................................................................................................................31
8.2. System Control from any Phone Number ....................................................................................................................................................31
9.
DATE AND TIME ......................................................................................................................................................................33
10. USER PASSWORDS ................................................................................................................................................................ 34
10.1. User Password Names ....................................................................................................................................................................................35
11. iBUTTON KEYS ...................................................................................................................................................................... 36
11.1. Adding and Removing iButton Keys ............................................................................................................................................................ 36
11.2. iButton Key Names..........................................................................................................................................................................................37
12. ARMING AND DISARMING ..................................................................................................................................................... 38
12.1. Free of Charge Phone Call ............................................................................................................................................................................. 38
12.2. SMS Text Message.......................................................................................................................................................................................... 39
12.3. EKB2 Keypad and User Password ................................................................................................................................................................ 40
12.4. EKB3/EKB3W Keypad and User Password ................................................................................................................................................. 40
12.5. iButton Key ...................................................................................................................................................................................................... 41
12.6. EWK1 Wireless Keyfob ................................................................................................................................................................................... 42
12.7. Arm-Disarm by Zone ...................................................................................................................................................................................... 42
12.8. EGR100 Middle-Ware..................................................................................................................................................................................... 43
12.9. Disabling and Enabling Arm/Disarm Notifications.................................................................................................................................... 43
13. EXIT AND ENTRY DELAY ....................................................................................................................................................... 45
14. ZONES.................................................................................................................................................................................... 47
14.1. Zone Numbering............................................................................................................................................................................................. 47
14.2. Zone Expansion .............................................................................................................................................................................................. 47
14.3. 6-Zone Mode ................................................................................................................................................................................................... 47
14.4. ATZ (Advanced Technology Zone) Mode.................................................................................................................................................... 48
14.5. Zone Type Definitions ................................................................................................................................................................................... 49
14.6. Zone Attributes .............................................................................................................................................................................................. 50
14.7. Bypassing and Activating Zones...................................................................................................................................................................52
14.8. Zone Names .....................................................................................................................................................................................................53
14.9. Disabling and Enabling Zones .......................................................................................................................................................................53
15. STAY MODE .............................................................................................................................................................................55
16. TAMPERS ................................................................................................................................................................................56
16.1. Tamper Names ................................................................................................................................................................................................ 56
17. ALARM INDICATIONS AND NOTIFICATIONS ..........................................................................................................................57
17.1. Enabling and Disabling Alarm Notifications............................................................................................................................................... 58
18. PROGRAMMABLE (PGM) OUTPUTS .......................................................................................................................................61
18.1. PGM Output Numbering .................................................................................................................................................................................61
18.2. PGM Output Expansion...................................................................................................................................................................................61
18.3. PGM Output Names ........................................................................................................................................................................................ 62
18.4. Turning PGM Outputs ON and OFF............................................................................................................................................................... 62
18.5. PGM Output Control by Event and Scheduler ............................................................................................................................................ 64
18.6. Wireless PGM Output Type Definitions....................................................................................................................................................... 65
MANUAL ELDES ESIM364 V1.0
EN
3
19. WIRELESS DEVICES ............................................................................................................................................................... 66
19.1. Binding, Removing and Replacing Wireless Devicess .............................................................................................................................. 66
19.2. Wireless Device Information and Signal Status Monitoring .................................................................................................................... 67
19.3. Disabling and Enabling Siren if Wireless Signal is Lost ............................................................................................................................ 69
20. SIREN/BELL ........................................................................................................................................................................... 70
20.1. BELL Output Status Monitoring ....................................................................................................................................................................71
20.2. Bell Squawk ......................................................................................................................................................................................................71
20.3. Indication by EWS2 Indicators .......................................................................................................................................................................72
21. BACKUP BATTERY, MAINS POWER SUPPLY STATUS MONITORING AND MEMORY ..............................................................73
22. GSM CONNECTION AND ANTENNA STATUS MONITORING....................................................................................................76
23. PARTITIONS .......................................................................................................................................................................... 78
23.1. Zone Partition ................................................................................................................................................................................................. 78
23.2. User Phone Number Partition ...................................................................................................................................................................... 78
23.3. Keypad Partition and Keypad Partition Switch.......................................................................................................................................... 79
23.4. User Password Partition ................................................................................................................................................................................ 80
23.5. iButton Key Partition ..................................................................................................................................................................................... 81
23.6. EWK1 Wireless Keyfob Partition .................................................................................................................................................................. 81
24. TEMPERATURE SENSORS ..................................................................................................................................................... 82
24.1. Adding, Removing and Replacing Temperature Sensors ........................................................................................................................ 82
24.2. Primary and Secondary Temperature Sensors.......................................................................................................................................... 83
24.3. Setting Up MIN and MAX Temperature Boundaries. Temperature Info SMS ....................................................................................... 84
24.4. Temperature Sensor Names......................................................................................................................................................................... 85
25. REMOTE LISTENING AND 2-WAY VOICE COMMUNICATION .................................................................................................. 86
26. SYSTEM INFORMATION. INFO SMS ....................................................................................................................................... 87
26.1. Periodic Info SMS ............................................................................................................................................................................................ 87
27. SYSTEM NOTIFICATIONS ...................................................................................................................................................... 89
27.1. SMSC (Short Message Service Center) Phone Number............................................................................................................................ 92
28. EVENT LOG ............................................................................................................................................................................ 93
29. INDICATION OF SYSTEM FAULTS .......................................................................................................................................... 94
30. Monitoring Station ............................................................................................................................................................... 96
30.1. Data Messages – Events ................................................................................................................................................................................ 97
30.2. Communication ............................................................................................................................................................................................. 103
31. DUAL SIM MANAGEMENT ....................................................................................................................................................113
31.1. Disabled Mode............................................................................................................................................................................................... 113
31.2. Automatic Mode ........................................................................................................................................................................................... 113
31.3. Manual Mode ..................................................................................................................................................................................................115
32. ELDES WIRED DEVICES ........................................................................................................................................................117
32.1. RS485 Interface ............................................................................................................................................................................................117
32.2. 1-Wire Interface ............................................................................................................................................................................................ 131
32.3. Modules Interface ........................................................................................................................................................................................ 132
33. ELDES WIRELESS DEVICES.................................................................................................................................................. 136
33.1. EKB3W - Wireless LED Keypad ................................................................................................................................................................... 136
33.2. EW1 - Wireless Zone & PGM Output Expansion Module ........................................................................................................................ 139
33.3. EWP1 – Wireless Motion Detector ............................................................................................................................................................. 141
33.4. EWD1 – Wireless Magnetic Door Contact.................................................................................................................................................. 143
33.5. EWK1 - Wireless Key-Fob ............................................................................................................................................................................ 145
33.6. EWS1 – Wireless Indoor Siren ..................................................................................................................................................................... 147
33.7. EWS2 – Wireless Outdoor Siren.................................................................................................................................................................. 150
33.8. EW1B - Battery-Powered Wireless Zone & PGM Output Expansion Module...................................................................................... 152
34. SMART SECURITY ................................................................................................................................................................156
35. TEHNICAL SUPPORT ............................................................................................................................................................159
35.1. Troubleshooting ........................................................................................................................................................................................... 159
35.2. Restoring Default Parameters ................................................................................................................................................................... 159
35.3. Updating the Firmware via USB Cable Locally ......................................................................................................................................... 159
35.4. Updating Firmware via GPRS Connection Remotely .............................................................................................................................. 160
35.5. Frequently Asked Questions ...................................................................................................................................................................... 161
36. Related Products .................................................................................................................................................................163
4
EN
MANUAL ELDES ESIM364 V1.0
Limited Liability
The buyer must agree that the system will reduce the risk of fire, theft, burglary or other dangers but does not guarantee against such
events.
“ELDES UAB” will not take any responsibility regarding personal or property or revenue loss while using the system.
“ELDES UAB” liability according to local laws does not exceed value of the purchased system. “ELDES UAB” is not affiliated with any of the
cellular providers therefore is not responsible for the quality of cellular service.
Manufacturer Warranty
The system carries a 24-month warranty by the manufacturer “ELDES UAB”. Warranty period starts from the day the system has been
purchased by the end user. The warranty is valid only if the system has been used as intended, following all guidelines listed in the manual
and within specified operating conditions. Receipt must be kept as a proof of purchase date.
The warranty is voided if the system has been exposed to mechanical impact, chemicals, high humidity, fluids, corrosive and hazardous
environments or other force majeure factors.
Package Content
1. ESIM364..................................... ............... qty. 1
2. Microphone................................ ................qty.1
3. SMA antenna............................. ............... qty. 2
4. Back-up battery connection wire ......... qty. 1
5. User manual............................ .................. qty. 1
6. Resistor 5,6kΩ........................... .............qty. 12
7. Resistor 3,3kΩ........................... ...............qty. 6
8. Plastic holders........... ...............................qty. 4
About Installation Manual
This document describes detailed installation and operation process of alarm system ESIM364. It is very important to read the installation
manual before starting to use the system.
Copyright © “ELDES UAB”, 2012. All rights reserved
It is not allowed to copy and distribute information in this document or pass to a third party without advanced written authorization
by “ELDES UAB”. “ELDES UAB” reserves the right to update or modify this document and/or related products without a warning.
Hereby, “ELDES UAB” declares that this GSM alarm and management system ESIM364 is in compliance with the essential requirements and other relevant provisions of Directive 1999/5/EC. The declaration of conformity may be consulted at www.eldes.lt
MANUAL ELDES ESIM364 V1.0
EN
5
1. General Information
1.1. Functionality
ESIM364 – micro-controller based alarm system for houses, cottages, country homes, garages and other buildings, also capable of managing electrical appliances via cellular GSM/GPRS network. It can also be used as Intercom system.
The system can be used in the following applications:
t Property security;
t Alarm switch;
t Thermostat, heating and air-conditioner control, temperature monitoring;
t Lighting, garden watering, water pump and other electrical equipment control via SMS text messages;
t Remote listening to what is happening in the secured area;
t Main 230V power status with SMS text message;
t Two-way intercom device via GSM network.
1.2. Compatible Device Overview
Wired Devices
Description
Device
EKB2
LCD keypad
4*
Max. Connectable Devices
EKB3
LED keypad
4*
EA1
EA2
EPGM1
EPGM8
Audio output module with 3,5mm jack
Audio amplifier module 1W 8Ω
16 zone and 2 PGM output expansion module
8 PGM output expansion module
1**
1**
2
1**
Device
EW1
EW1B
EWP1
EWD1
EWK1
EWS1
EWS2
EKB3W
Wireless Devices
Description
Wireless 2 zone and 2 PGM output expansion module
Battery-powered wireless 2 zone and 2 PGM output expansion module
Wireless PIR movement sensor
Wireless magnetic door contact
Wireless key-fob with 4 buttons
Wireless indoor siren
Wireless outdoor siren
Wireless LED keypad
Max. Connectable Devices
32***
32***
32***
32***
5***
32***
32***
4***
* - A mixed combination of EKB2 and EKB3 keypads is supported. The combination can consist of up to 4 keypads in total.
** - Only 1 of these modules can be connected at a time if the module slots are implemented in ESIM364 unit.
*** - A mixed combination of wireless devices is supported. The combination can consist of up to 32 wireless devices in total.
1.3. Default Parameters & Ways of Parameter Configuration
Main Settings
Parameter
Default Value
Depends on firmware version according to user‘s location
SMS Password
0000
User Password 1
1111
User Password 2... 30
N/A
User Password Name
N/A
Administrator Password
1470
Duress Password
N/A
SGS Password
N/A
User 1... 10 Phone Number
N/A
User 1... 10 Name
N/A
Allow Control from Any Phone Number Disabled
Date & Time
N/A
Exit Delay
Partition 1... 4
Info SMS Scheduler
Frequency (days) – 1; Time - 11
SMS & EKB2 Menu Language
6
EN
Configurable by:
EKB3/
SMS EKB2
EKB3W
Configuration
Tool
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
MANUAL ELDES ESIM364 V1.0
Zones
Parameter
Zone Name
Entry Delay
On-Board Zone Delay
EPGM1 Zone Delay
On-board Z1 Zone Type
On-board Z2... Z12 Zone Type
Keypad Zone Type
EPGM1 Zone Type
Wireless Zone Type
Virtual Zone Type
ATZ Mode
6-Zone Mode: Zone Connection Type
ATZ Mode: Zone Connection Type
On-board Zone Status
Keypad Zone Status
EPGM1 Zone Status
Wireless Zone Status
Virtual Zone Status
Stay attribute for individual zone
Arm-Disarm by Zone
Force atrribute for individual zone
Tamper Name
Chime
Default Value
Z1 - Zone 1; Z2 - Zone 2; Z3 - Zone 3; Z4 - Zone 4; Z5 Zone 5; Z6 - Zone 6
15 seconds
800 milliseconds
800 milliseconds
Delay
Instant
Instant
Instant
Depends on the connected wireless device
Follow
Disabled
Type 1
Type 4
Enabled
Disabled
Enabled
Depends on the connected wireless device
Disabled
Disabled
N/A
Disabled
Tamper 1, Tamper 2, Tamper 3, Tamper 4, Tamper 5,
Tamper 6 etc.
Enabled
Configurable by:
EKB3/
SMS EKB2
EKB3W
Configuration
Tool
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
PGM Outputs
Parameter
PGM Output Name
Default Value
C1 – Controll1, C2 – Controll2, C3 – Controll3, C4 – Controll4 etc.
Disabled
Disabled
Disabled
Enabled
Depends on the connected wireless device
Disabled
PGM Output Status
EPGM8 PGM Output Status
EPGM1 PGM Output Status
Wireless PGM Output Status
Wireless PGM Output Type
PGM Output Control by Event 1... 16
PGM Output Control by Event Management
Scheduler 1... 16
Disabled
Turn ON/OFF PGM Output by Timer
Using Module EPGM8 Mode
Disabled
Configurable by:
EKB3/
SMS EKB2
EKB3W
Configuration
Tool
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
Alarm Duration & Siren
Parameter
Default Value
Alarm Duration
EWS2 LED
Bell Squawk
Activate Siren if Wireless Device is Lost
1 minute
Disabled
Disabled
Disabled
MANUAL ELDES ESIM364 V1.0
Configurable by:
EKB3/
SMS EKB2
EKB3W
9
9
9
9
9
9
9
9
Configuration
Tool
9
9
9
9
EN
7
Parameter
Alarm Notifications & Arm/Disarm Notifications
Configurable by:
Default Value
EKB3/
SMS EKB2
EKB3W
9
9
Disabled
Call in Case of Alarm
Send Alarm SMS to All Users SimultaDisabled
neously
Send Arm/Disarm SMS to User 1... 10 Enabled
Send Arm/Disarm SMS to All Selected
Disabled
Users Simultaneously
9
9
Configuration
Tool
9
9
9
9
9
9
9
9
9
9
Main Power Status
Parameter
Default Value
Main Power Loss Delay
Main Power Restore Delay
30 seconds
120 seconds
Configurable by:
EKB3/
SMS EKB2
EKB3W
9
9
9
9
Configuration
Tool
9
9
Peripheral Devices
Parameter
Default Value
Temperature Sensor 1... 8 Name
Primary Temeprature Sensor
Secondary Temperature Sensor
Temperature Sensor 1... 8 MIN
Temperature Sensor 1... 8 MAX
Allow adding New iButton Keys
iButton 1... 5 Name
N/A
No. 1
No. 2
0 °C
0 °C
Disabled
N/A
Configurable by:
EKB3/
SMS EKB2
EKB3W
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
Configuration
Tool
9
9
9
9
9
9
9
System Notifications
Parameter
Parameter
System Armed
System Disarmed
General Alarm
Mains Power Loss/Restore
Battery Failed
Battery Dead or Missing
Low Battery
Siren Fail/Restore
Date/Time Not Set
GSM Connection Failed
GSM Antenna Fail/Restore
Tamper Alarm
Keypad Failed
Temperature Info
System Started
Periodical Info
Wireless Signal Loss
Enabled
Enabled
Enabled
Enabled
Enabled
Enabled
Enabled
Enabled
Enabled
Disabled
Disabled
Disabled
Enabled
Enabled
Enabled
Enabled
Enabled
8
EN
Configurable by:
EKB3/
SMS EKB2
EKB3W
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
Configuration
Tool
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
MANUAL ELDES ESIM364 V1.0
Partitions
Parameter
Default Value
Partition 1 Name
Partition 2 Name
Partition 3 Name
Partition 4 Name
Keypad 1... 4 Partition
Keypad Partition Switch
User Password 1... 30 Partition
User 1... 10 Phone Number Partition
iButton 1.. 10 Partition
Zone partition
PART1
PART2
PART3
PART4
PART1
Disabled
PART1
PART1
PART1
PART1
Configurable by:
EKB3/
SMS EKB2
EKB3W
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
Configuration
Tool
9
9
9
9
9
9
9
9
9
9
Configurable by:
EKB3/
SMS EKB2
EKB3W
9
9
9
9
9
9
9
Configuration
Tool
9
9
9
Monitoring Station
Parameter
Default Value
MS Mode
Data Messages
Account (Alarm System ID)
Monitoring Station Phone Number 1... 3
(Voice Calls/SMS)
Attempts (Voice Calls/SMS)
Monitoring Station Phone Number 1...
3 (PSTN)
Attempts (PSTN)
Monitoring Station Phone Number 1...
5 (CSD)
Attempts (CSD)
Server IP Address (GPRS)
DNS1 Server IP Address (GPRS)
DNS2 Server IP Address (GPRS)
Protocol (GPRS)
Server Port (GPRS)
Local Port (GPRS)
SIM1 APN (GPRS)
SIM1 User (GPRS)
SIM1 Password (GPRS)
SIM2 APN (GPRS)
SIM2 User (GPRS)
SIM2 Password (GPRS)
Profile (GPRS)
GPRS Attempts
Delay Between Attempts (GPRS)
Unit ID (GPRS)
Test Period (GPRS)
Communication - Primary
Communication - Backup 1... 5
Protocol over GPRS
Disabled
All Enabled
9999
MANUAL ELDES ESIM364 V1.0
N/A
9
9
9
3
9
9
9
N/A
9
9
9
3
9
9
9
N/A
9
9
9
3
0.0.0.0
N/A
N/A
UDP
20000
N/A
N/A
N/A
N/A
N/A
N/A
N/A
Profile1
3
600 seconds
0000
180 seconds
N/A
N/A
EGR100
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
EN
9
Additional Parameters
Parameter
Default Value
Event Log
Microphone Gain
Speaker Level
GSM Signal Loss Indication - Delay
GSM Signal Loss Indication - Activate
Output
Show ARMED Status in Keypad (EKB2)
Enabled
12
85
180 seconds
Configurable by:
EKB3/
SMS EKB2
EKB3W
9
9
9
9
Configuration
Tool
9
9
9
9
N/A
9
Disabled
9
Dual-SIM Management
Configurable by:
EKB3/
SMS EKB2
EKB3W
Parameter
Default Value
SIM Card Switch
Return to Primary SIM
Send SMS / Call via
Try to Find Operator for a Maximum of
Disabled
Enabled
Currently in Use SIM
3 times
Configuration
Tool
9
9
9
9
Smart Security
Parameter
Default Value
Smart Security
Server Address
Port
Disabled
config.eldes.lt
8082
180 seconds
0
Ping Period
Time Zone
10
EN
Configurable by:
EKB3/
SMS EKB2
EKB3W
Configuration
Tool
9
9
9
9
9
MANUAL ELDES ESIM364 V1.0
MANUAL ELDES ESIM364 V1.0
EN
11
2. Technical Specifications
2.1. Electrical & Mechanical Characteristics
Electrical & Mechanical Characteristics
Main Power Supply
Current in Standby without External Sensors and Keypad
Recommended Backup Battery Voltage, Capacity
Recommended Backup Battery Type
Maximum Battery Charge Current
GSM Modem Frequency
Cable Type for GSM Antenna Connection
Number of Zones on Board
Nominal Zone Resistance
Number of PGM Outputs on Board
ESIM364 PGM Output Circuit
16-24V 50 Hz ~1.5A max / 18-24V
Up to 80mA
12V; 1,3-7Ah
Lead-Acid
900mA
850/900/1800/1900MHz
Shielded
6 (ATZ mode: 12)
5,6kΩ (ATZ Mode: 5,6kΩ and 3,3kΩ)
4
Maximum Commuting PGM Output Values
BELL: Siren Output when Activated
BELL: Maximum Siren Output Current
BELL: Maximum Cable Length for Siren Connection
BELL: Cable Type for Siren Connection
AUX: Auxiliary Equipment Power Supply Voltage
AUX: Maximum Accumulative Current of Auxiliary Equipment
AUX: Maximum Cable Length for Auxiliary Equipment Connection
AUX: Cable Type for Auxiliary Equipment Connection
BUZ: Maximum Current of Mini Buzzer
BUZ: Power Supply Voltage of Mini Buzzer
BUZ: Cable Type for Mini Buzzer Connection
Dimensions
Operating Temperature Range
Supported Temperature Sensor Model
Maximum Supported Number of Temperature Sensors
DATA: Maximum Cable Length for 1-Wire® Communication
DATA: Cable Type for 1-Wire® Communication
Supported iButton® Key Model
Maximum Supported Number of Keypads
Y/G: Maximum Cable Length for RS485 Communication
Y/G: Cable Type for RS485 Communication
MIC: Maximum Cable Length for Microphone Connection
MIC: Cable Type for Microphone Connection
Voltage – 30V; Current – 100mA;
Connected to COM
1A
up to 30 meters
Unshielded
13,8V DC
1,1A
up to 100 meters
Unshielded
150mA
5V DC
Unshielded
140x100x18mm
-20...+550C
Maxim®/Dallas® DS18S20, DS18B20
8
up to 30 meters
Unshielded
Maxim®/Dallas® DS1990A
4 x EKB2 / EKB3
up to 100 meters
Unshielded
Up to 2 meters
Unshielded
1R
OUT
1,5A max
Open Collector Output.
Output is pulled to COM
when turned ON.
Wireless Transmitter-Receiver Frequency
868 Mhz
Wireless Communication Range
Maximum Supported Number of Wireless Devices
Event Log Size
Maximum Supported Number of Zones
Up to 30m in premises; up to 150m in open areas
32
500 events
76
Maximum Supported Number of PGM Outputs
Cable Type for Zone and PGM Output Connection
Communications
Supported Protocols
76
Unshielded
SMS, Voice calls, GPRS network, RS485, CSD, PSTN
Ademco Contact ID, 4+2, EGR100, Kronos, Cortex SMS
12
EN
MANUAL ELDES ESIM364 V1.0
2.2. Main Unit, LED & Connector Functionality
SIM CARD2
OPEN
DEF
1
OPEN
S TA T
C4
C3
C2
C1
SIM CARD1
GSM ANT
G SM
MO DE M
3A
FUSE F1
PRG
USB
MODULES
TIP RING
Slots for EA1, EA2 or EPGM8 module
W-LESS ANT
C 4C 3
MODULES*
NE TW
Main Unit Functionality
GSM MODEM
GSM network 850/900/1800/1900MHz
modem
SIM CARD1
Primary SIM card slot / holder
SIM CARD2
Secondary SIM card slot / holder
DEF
Pins for restoring default settings
USB
Mini USB port
FUSE F1
3A fuse
W-LESS ANT
Wireless antenna SMA type connector
GSM ANT
GSM antenna SMA type connector
AK U +
AK U -
AC /DC
AC /DC
AUX+
AUXBELL+
BELL-
CO M
G
Y
C2
C1
BU Z +
BU Z MIC +
M IC +5V
DAT A
CO M
Z6
CO M
Z5
Z4
CO M
Z3
Z2
CO M
Z1
LED Functionality
NETW
GSM network signal strength
C1
PGM output C1 status - on/off
C2
PGM output C2 status - on/off
C3
PGM output C3 status - on/off
C4
PGM output C4 status - on/off
STAT
Micro-controller status
Connector Functionality
TIP*
PSTN (landline) terminal
RING*
PSTN (landline) terminal
DATA
1-Wire® interface for iButton key & temperature sensor connection
+5V
Temperature sensor power supply terminal (+5V)
MICMicrophone negative terminal
MIC+
Microphone positive terminal
BUZBuzzer negative terminal
BUZ+
Buzzer positive terminal
C1 - C4
PGM output terminals
Z1 - Z6
Security zone terminals
Y
RS485 interface for communication (yellow wire)
G
RS485 interface for communication (yellow wire)
COM
Common return terminal
BELLSiren negative terminal
BELL+
Siren positive terminal
AUXNegative power supply terminal for auxiliary equipment
AUX+
Positive power supply terminal for auxiliary equipment
AC/DC
Main power supply terminals
AKUBackup battery negative terminal
AKU+
Backup battery positive terminal
* - Optional, implementable on request in advance
MANUAL ELDES ESIM364 V1.0
EN
13
2.3. Wiring Diagrams
2.3.1.General Wiring
2
AKU+
AKU-
Backup Battery
12V 1.3-7Ah
AC /DC
AC /DC
AUX+
AUXBELL+
BELLCO M
G
Y
C2
C1
BUZ+
BUZMIC +
MIC +5V
DATA
CO M
Z6
CO M
Z5
Z4
CO M
Z3
Z2
CO M
Z1
Metal cabinet
PE terminal
Fuse 500 mA
~16-24V
~230V 50Hz
Z6
Z5
Z4
Z3
Z2
Z1
BUZ
5,6 kΩ
5,6 kΩ
5,6 kΩ
5,6 kΩ
5,6 kΩ
5,6 kΩ
MIC
SIREN/BELL
EPGM1
1A max.
iButton®
key reader
Relay
module
EKB3
Temperature sensor
EKB2
2.3.2. Zone Connection Types
Type 1
COM
Z1
3
Example of magnetic door contact wiring
5,6 kΩ
6-Zone mode: Normally open contact
with 5,6KΩ end-ofline resistor.
COM
NO
Magnet
Type 2
AUX+
5,6 kΩ
6-Zone mode: Normally closed contact
with 5,6KΩ end-ofline resistor
C1
COM
Z1
3
Example of 4-wire smoke detector wiring
COM
GND
NC
+Vin
14
EN
MANUAL ELDES ESIM364 V1.0
Type 3
Example of motion detector wiring
AUX+
AUX-
COM
Z1
5
6-Zone mode: Tamper
and 5,6KΩ end-of-line
resistor and 3,3KΩ
end-of-line resistor
with normally closed
contact.
COM
5,6 kΩ
3,3 kΩ
GND
NC
+Vin
TAMP
Example of magnetic door contact (Z1) and glass break sensor (Z7) wiring
AUX+
AUX-
5,6 kΩ
COM
Z1
6
ATZ mode: 5,6KΩ
end-of-line resistor
and normally closed
contact with 3,3KΩ
end-of-line resistor
and normally closed
contact
3,3 kΩ
Type 4
NC
COM
Magnet
Type 5
COM
GND
NC
+Vin
Example of motion detector (Z1) and magnetic door contact (Z7) wiring
AUX+
AUX-
ATZ mode: Tamper,
5,6KΩ end-of-line
resistor, 5,6KΩ
end-of-line resistor
with normally closed
contact and 3,3KΩ
end-of-line resistor
with normally closed
contact.
COM
Z1
7
5,6 kΩ
5,6 kΩ
3,3 kΩ
NC
COM
Magnet
COM
GND
NC
TAMP
MANUAL ELDES ESIM364 V1.0
+Vin
EN
15
2.3.3. Siren
BELL+
BELL-
8
RED +
COM
BELL+
BELL-
9
BELL
1 Connect negative GND siren wire to COM terminal.
3 Connect positive +12V siren wire to BELL+ terminal.
+12V
BELL+
BELL-
10
Self-contained siren
2 Controlling BELL siren wire must be connected
to BELL- terminal.
GND
SIREN/BELL
1A max.
1 Connect positive siren wire (red) to BELL+ terminal.
2 Connect negative siren wire (black) to BELLterminal.
BLACK SIREN/BELL
1A max.
2-wired siren
No siren
If siren/bell is not in use, connect a resistor of nominal ranging from 7 Ω through 3,3 Ω across BELL+
and BELL- terminals. If the resistor is not connected, the system will indicate system fault.
See also 20. SIREN/BELL.
NOTE: BELL- is the commuted contact intended for siren control.
NOTE: Ensure that the inner resistance of the siren/bell is ranging from 7 Ω through 3,3 Ω, otherwise the system will indicate system fault.
16
EN
MANUAL ELDES ESIM364 V1.0
2.3.4.
iButton Key Reader and Buzzer
Supported iButton key model: Maxim/Dallas
DS1990A
BUZ+
BUZ-
COM
DATA
11
-
The iButton key reader can be installed with buzzer
or separately. The buzzer is intended for audio indication of exit/entry delay countdown providing
short beeps.
+ BUZZER
1 Connect iButton key reader terminal wires to
1-Wire interface: COM and DATA terminals respectively.
2 Connect buzzer‘s negative terminal wire to BUZand positive terminal wire to BUZ+.
3 Additionally, a LED indicator for visual indication
can be installed in parallel to buzzer or instead.
Connect LED anode terminal to BUZ- and cathode to BUZ+.
iButton
key reader
DS1990A
NOTE: The installation of buzzer is not necessary if EKB2/EKB3 keypad is used.
ATENTION: The cable length for connection to 1-Wire interface can be up to 30 meters max.
2.3.5.
Temperature Sensor and iButton Key Reader
Supported iButton key model: Maxim/Dallas DS1990A
Supported temperature sensor model: Maxim/Dallas DS18S20, DS18B20
TEMPERATURE
SENSOR
DS18S20,
DS18B20
2
1
3
DS18S20, DS18B20
TEMPERATURE SENSOR
1 Connect temperature sensor 1, 2, 3 terminals to
1-Wire interface: COM, DATA and +5V terminals
respectively.
2 When connecting iButton key reader in parallel
to temperature sensor, connect iButton key reader terminal wires to COM and DATA terminals
respectively.
+5V
DATA
COM
+5V
DATA
COM
12
1
2
3
BOTTOM VIEW
iButton
key reader
DS1990A
2.3.6. Relay Finder® 40.61.9.12 with Terminal Socket 95.85.3 to PGM Output
AUX+
13
C1
1 Wire up relay A2 terminal to PGM output Cx and
A1 terminal to AUX+.
2 In addition, connect LED anode terminal to relay
A2 terminal and cathode to A1 terminal.
LED
COIL
A2
A1
RELAY
MANUAL ELDES ESIM364 V1.0
EN
17
2.3.7. RS485
Serial Wiring Method
ESIM364
a
EKB2/EKB3
b
EKB2/EKB3
c
EKB2/EKB3
d
EKB2/EKB3
e
EPGM1
Max. cable length: a+b+c+d+e+f= up to 100 meters
f
EPGM1
NOTE: If necessary, the RS485 devices can be powered from anexternal 12-14V DC power supply instead of AUX+ and AUX- terminals
ATTENTION: The cable length must not exceed 100 meters in total.
ATTENTION: When wiring more than 1 keypad and/or EPGM1 module, please ensure that the set address of each keypad and/or EPGM1
module is different.
NOTE: You may connect only 1 EKB2/EKB3 keypad or a mixed combination of EKB2 and EKB3 keypads. The combination can consist of
up to 4 keypads in total.
For more details on RS485 device installation, please refer to 32.1. RS485 Interface
18
EN
MANUAL ELDES ESIM364 V1.0
Parallel Wiring Method
ESIM364
Max. cable length: up to 100 meters
EPGM1
EPGM1
EKB2/EKB3
EKB2/EKB3
EKB2/EKB3
NOTE: If necessary, the RS485 devices can be powered from anexternal 12-14V DC power supply instead of AUX+ and AUX- terminals
ATTENTION: The cable between ESIM364 and each RS485 device must be of the same length and can NOT exceed 100 meters.
ATTENTION: When wiring more than 1 keypad and/or EPGM1 module, please ensure that the set address of each keypad and/or EPGM1
module is different.
NOTE: You may connect only 1 EKB2/EKB3 keypad or a mixed combination of EKB2 and EKB3 keypads. The combination can consist of
up to 4 keypads in total.
For more details on RS485 device installation, please refer to 32.1. RS485 Interface
2.3.8. RING/TIP
ATTENTION: The TIP/RING connectors and PSTN module are NOT
included in a standard ESIM364 alarm system unit. These components
are optional and can be implemented on request in advance.
14
to PSTN
(landline)
RING
TIP
MANUAL ELDES ESIM364 V1.0
ESIM364
EN
19
3. INSTALLATION
x The system can be installed in a metal or non-flammable cabinet only. For a convenient installation, ME1 metal cabinet is highly recommended. When using a different metal cabinet, it is necessary to ground it.
x For the connection of 230V transformer, use 3x0.75 mm2 1 thread double isolated cable. 230V power supply cables must not be
grouped with low voltage cable group.
x For the connection of auxiliary and BELL outputs, use 2x0.75 mm2 1 thread unshielded cable of up to 100 meters length.
x For the connection of zone/PGM output connectors, use 0.50 mm2 1 thread unshielded cable of up to 100 meters length.
System Installation in ME1 Metal Cabinet
1. ME1 metal cabinet components
15
to AC main power line
Null
blue
PE
Phase
brown
Fuse 1A
Transformer
(Primary voltage: 230V AC,
Secondary voltage: 17V
2,35A)
Tamper switch
to AC/DC terminals
of ESIM364 system
2. Insert the plastic holders into the appropriate mounting points and fix the board of ESIM364 on the holders as indicated below.
16
mounting points
20
EN
MANUAL ELDES ESIM364 V1.0
17
7
3. If EPGM1 module is to be installed, please install it in the first and ESIM364 alarm system afterwards. EPGM1 must be mounted on the
shorter plastic holders, while ESIM364 – on the longer ones. The mounting points of EPGM1 module are indicated below.
18
mounting
points
MANUAL ELDES ESIM364 V1.0
EN
21
19
20
7
4. Wire up the system according to the wiring diagrams. Install the buzzer closer to iButton key reader in order to hear the exit delay
countdown. A LED indicator can be used in parallel to the buzzer or instead. For a convenient installation, ED1 is highly recommended
(see 2.3 Wiring Diagrams for more details).
5. Disable the PIN code of the SIM card by inserting it into a mobile phone and following the proper menu steps. Ensure that the addition
al services, such as voice mail, call forwarding, report on missed/busy calls are disabled on the SIM card. For more details on
how to disable these services, please contact your GSM operator.
6.
Once the PIN code is disabled, place the SIM card into the SIM CARD1 slot of the alarm system. If Dual-SIM feature is to be used, insert
another SIM card into the SIM CARD2 slot. For more details, please refer to 31. DUAL-SIM MANAGEMENT.
21
OPEN
22
22
EN
23
Inserting a SIM card into SIM
CARD1 slot is mandatory as it
is the main SIM card slot, while
using a SIM card in SIM CARD2
slot is optional.
MANUAL ELDES ESIM364 V1.0
25
OPEN
24
7.
Connect the GSM and wireless antennas and move them away from the metal cabinet.
8. Power up the system and wait until indicator STAT lights up.
9.
The system starts up in less than a minute. Indicator STAT should be flashing indicating successful micro-controller operation. In
addition, the system sends an SMS text message to a preset User 1 phone number.
10. The illuminated indicator NETW indicates that the system successfully registered to GSM network. To find the strongest GSM signal,
position the GSM antenna and follow the indications provided by NETW indicator. The following table provides the list of available
indications.
NETW indication
OFF
Flashing every 3 sec.
Flashing every 1 sec.
Flashing several times per sec.
Steady ON
GSM signal strength
No GSM signal
Poor
Medium
Good
Excellent
11. Change the default SMS password (see 6. PASSWORDS for more details).
12. Set the phone number for User 1 (see 8. USER PHONE NUMBERS for more details).
13. Set system date and time (see 9. DATE AND TIME for more details).
14. Once the system is fully configured, it is ready for use. However, if you fail to receive an SMS reply from the system, please check the
SMSC (Short Message Service Center) phone number. For more details regarding the SMS centre phone number, please refer to 27.1.
SMSC (Short Message Service Center) Phone Number.
NOTE: The installation of iButton key reader, EKB2/EKB3/EKB3W keypad, EWK1 wireless key-fob is not mandatory. However, it is
recommended to have those devices installed as an emergency switch in case your mobile phone is switched off or missing.
NOTE: For maximum system reliability we recommend you do NOT use a Pay As You Go SIM card. Otherwise, in the event of insufficient
credit balance on the SIM card, the system would fail to make a phone call or send messages.
NOTE: We advise you to choose the same GSM SIM provider for your system as for your mobile phone. This will ensure the fastest,
most reliable SMS text message delivery service and phone call connection.
NOTE: Even though alarm system ESIM364 installation process is not too complicated, we still recommend to perform it by a person
with basic knowledge in electrical engineering and electronics to avoid any system damage.
MANUAL ELDES ESIM364 V1.0
EN
23
4. GENERAL OPERATION
When the system is being armed, it will initiate the exit delay countdown intended for the user to leave the secured area. During the countdown period the buzzer will emit short beeps and/or LED indicator will flash. By default, exit delay duration is 15 seconds. After the countdown is complete, the system will become armed and lock the configuration by keypad possibility. In case the user does not leave the secured area before the countdown is complete, the system will will arm in Stay mode if at least 1 zone has Stay attribute enabled. By default,
if there is at least 1 violated zone or tamper, the user will not be able to arm the system until the violated zone or tamper is restored. In case
it is required to arm the alarm system despite the violated zone presence, the violated zone can be bypassed or Force attribute enabled.
After the system is armed and if a zone (depending on type) or tamper is violated, the system will cause an alarm lasting for 1 minute (by
default), During the alarm, the siren/bell will provide an alarm sound along with the buzzers of the keypads. By default, the system will also
makes a phone call and send an SMS text message containing the violated zone or tamper number to a preset user and indicate the violated
zone or tamper number on the keypad. If another zone or tamper is violated or the same one is restored and violated again during the alarm,
the system will act as mentioned previously, but will not extend the alarm time.
After the user enters the secured area, the system will initiate the entry delay countdown intended for system disarming. During the countdown period, the buzzer will emit a steady beep and/or LED indicator will light ON. By default, entry delay duration is 15 seconds. After the
user successfully performs the disarming process, the system will unlock the keypads. If the user does not disarm the system in time, the
alarm system will cause an instant alarm.
NOTE: The alarm will be caused even if a tamper is violated while the system is disarmed.
For more details, please refer to 12. ARMING AND DISARMING.
24
EN
MANUAL ELDES ESIM364 V1.0
5. CONFIGURATION METHODS
!!! In this installation manual the underscore symbol ”_” represents one space character. Every underscore symbol must
be replaced by a single space character. There must be no spaces or other unnecessary characters at the beginning and at
the end of the SMS text message.
SMS
EKB2
In order to configure and control the system by SMS text message, send the text command to the ESIM364 system phone
number from one of the preset user phone numbers. The structure of SMS text message consists of 4-digit SMS password
(the default SMS password is 0000 – four zeros), the parameter and value. For some parameters the value does not apply e. g.
STATUS. The variables are indicated in lower-case letters, while a valid parameter value range is indicated in brackets.
The system configuration and control by EKB2 keypad is carried out by navigating throughout the menu section list displayed
on LCD screen. To navigate in the menu path, touch Ļ, Ĺ keys to select the desired menu section and touch OK key to open the
selected section. To enter a required value, use 0... 9 keys and touch OK key for confirmation or cancel/go one menu section
back by touching ĸ key. The value can be typed in directly by touching 0... 9 keys while highlighting the desired menu section. EKB2 menu type is “circle”, therefore when the last section in the menu list is selected, you will be brought back to the
beginning of the list after touching the Ļ key. In this installation manual, the menu path is based on the EKB2 menu tree by
starting at home screen view (see 32.1.1.4. EKB2 Menu Tree). The variables are indicated in lower-case letters, while a valid
parameter value range is indicated in brackets.
NOTE: Menu section CONFIGURATION is secured with administrator password. The default administrator password is 1470.
NOTE: The system can be configured using only one keypad at a time. Other connected keypads will be inactive while the menu section
CONFIGURATION is opened. The inactive EKB2 keypads will display
icon and CONFIGURATION MODE message.
NOTE: The keypad will automatically exit the menu section CONFIGURATION and return to home screen view if 1 minute after the last
key-touch expires.
EKB3/
EKB3W
The system configuration and control by EKB3/EKB3W keypad is carried out by activating the Configuration mode using the
administrator password (by default – administrator password is 1470) and entering a valid configuration command using the
number keys [0]... [9] and [#] key for confirmation. When entering a command, the indication of each pressed key is provided
by red indicators. The structure of a standard configuration command is a combination of digits. The commands, which do
not require the Configuration mode being activated, are noted. The variables are indicated in lower-case letters, while a valid
parameter value range is indicated in brackets.
Activate/deactivate
Configuration mode
EKB3/EKB3W:
Enter administrator password:
* aaaa #
Value: aaaa – 4-digit administrator password.
Example: *1470#
The following table provides a list of EKB3/EKB3W indications, which are relevant during Configuration mode.
Indication
Indicator ARMED flashing
Indicator SYSTEM flashing
1 long beep
3 short beeps
Description
Configuration mode activated successfully.
Valid parameter is entered and waiting for valid value to be enetered.
Non-existing command or invalid parameter value entered.
Command entered successfully.
NOTE: The system can be configured using only one keypad at a time. Other connected keypads will be inactive while the Configuration mode is activated
NOTE: Configuration mode will automatically deactivate if 1 minute after the last key-stroke expires
Config
Tool
Software ELDES Configuration Tool is intended for ESIM364 alarm system configuration via USB port locally or via GPRS connection remotely. This software simplifies system configuration process by allowing to use a personal computer in the process.
Before starting to use ELDES Configuration Tool software, please read the user guide provided in the software’s HELP section.
ELDES Configuration Tool is freeware and can be downloaded from at: www.eldes.lt
MANUAL ELDES ESIM364 V1.0
EN
25
5.1. Remote System Configuration via GPRS Connection
ATTENTION: The system will NOT send any data to monitoring station while configuring the system remotely via GPRS network. However,
during the configuration session, the data messages are queued up and transmitted to the monitoring station after the configuration
session is over.
ATTENTION: When the Configuration mode is activated by EKB3/EKB3W keypad or menu section CONFIGURATION is opened by EKB2
keypad, remote system configuration will be disabled.
NOTE: The keypads will be inactive when the system is being configured remotely.
Before configuring ESIM364 remotely via GPRS connection, make sure that:
x SIM card is inserted into SIM CARD1 slot of ESIM364 device (see 2.2. Main Unit, LED & Connector Functionality).
x Mobile internet service is enabled on the SIM card.
x Power supply is connected to ESIM364.
x Default SMS password is changed to a new 4-digit password (see 6. PASSWORDS).
x At least User 1 phone number is set up (see 8. USER PHONE NUMBERS).
x APN, user name and password are set up (see 30.2.1. GPRS Network).
5.1.1. Establishing Remote Connection Between ESIM364 System and Configuration Server
Initiate the
connection
to ELDES server
In order to activate a remote GPRS connection between ESIM364 system and ELDES configuration
server please , send the following SMS text message from user phone number.
Upon the successful SMS text message delivery, the system establishes a connection session for
20 minutes. An SMS reply, containing device IMEI number and confirming a successful connection
establishment, is sent shortly.
SMS
Initiate the
connection to
third-party server
SMS text message content:
ssss_STCONFIG
Value: ssss – 4-digit new SMS password.
Example: 1111_STCONFIG
In case it is necessary to establish a connection between ESIM364 system and a third-party
configuration server, send the following SMS text message.
SMS
SMS text message content:
ssss_STCONFIG:add.add.add.add:Port or ssss_STCONFIG:host-name:pprrt
Value: ssss – 4-digit SMS password; add.add.add.add – public IP address of third-party configuration server; pprrt – port number of third-party configuration server, range – [1... 65535]; host-name – public host-name of third-party configuration server.
Example: 1111_STCONFIG:62.80.115.102:4522
NOTE: Public IP address (host-name) and port number are necessary when connecting to a third-party-server for the first time only.
When connecting to the server next time, XXXX_stconfig is enough as the IP address (host-name) and port number are saved in the
device memory after the first successful connection.
26
EN
MANUAL ELDES ESIM364 V1.0
5.1.2. Connecting to ELDES Configuration Server using ELDES Configuration Tool Software
t
Run ELDES Configuration Tool software.
t
Press Remote Configuration button.
t
In the next window, select Connect to Remote
Server (recommended) and press Next button.
t
Enter the received IMEI number in Device IMEI entry.
t
Press Continue button.
t
Upon the successfully established connection,
the system prompts for an administrator password.
t
By entering a valid administrator password, the
system grants access to full configuration remotely.
t
Remote Configuration Management
window displays all performed configuration actions.
26
5.1.3.Ending the Configuration Process
Shut down the
Connection with the
Server
After the system configuration is complete, use one of the following methods to end the configuration
process:
t Press Disconnect button and close ELDES Configuration Tool software;
t Wait for the system to reply with an SMS text message confirming the end of the session;
t Shut down the connection with the server at any time by sending an SMS text message.
SMS
MANUAL ELDES ESIM364 V1.0
SMS text message content:
ssss_ENDCONFIG
Value: ssss – 4-digit SMS password.
Example: 1111_ENDCONFIG
EN
27
6. PASSWORDS
For security reasons, the system uses the following types of passwords:
t
SMS password – 4-digit password used for system arming/disarming and configuration by SMS text messages. By default, SMS password is 0000, which MUST be changed!
t
Administrator password – 4-digit password used for Configuration mode activation by keypad and logging in to ELDES Configuration
Tool software. By default, Administrator password is 1470, which is highly recommended to change.
Set SMS password
SMS
EKB2
Enter parameter 14 & new SMS password:
14 ssss #
Value: ssss – 4-digit new SMS password; range – [0001... 9999].
Example: 141111#
Config
Tool
This operation may be carried out from the PC using the ELDES Configuration Tool software.
EKB2
Menu path:
OK ĺ CONFIGURATION ĺ OK ĺ 1470 ĺ OK ĺ PRIMARY SETTINGS ĺ OK ĺ PASSWORDS
ĺ OK ĺ ADMIN PASSWORD ĺ OK ĺ aaaa ĺ OK
Value: aaaa – 4-digit new administrator password; range – [0000... 9999].
EKB3/
Enter parameter 16 & new administrator password:
16 aaaa #
EKB3W
Config
Tool
28
EN
Menu path:
OK ĺ CONFIGURATION ĺ OK ĺ aaaa ĺ OK ĺ PRIMARY SETTINGS ĺ OK ĺ PASSWORDS
ĺ OK ĺ SMS PASSWORD ĺ OK ĺ ssss ĺ OK
Value: aaaa – 4-digit administrator password; ssss – 4-digit new SMS password; range –
[0001... 9999].
EKB3W
EKB3/
Set Administrator
password
SMS text message content:
wwww_PSW_ssss
Value: wwww – 4-digit default SMS password; ssss – 4-digit new SMS password; range –
[0001... 9999].
Example: 0000_PSW_1111
Value: aaaa – 4-digit new administrator password; range – [0000... 9999].
Example: 162538#
This operation may be carried out from the PC using the ELDES Configuration Tool software.
MANUAL ELDES ESIM364 V1.0
7. MULTI-LANGUAGE SUPPORT
The system comes equipped with 2 different languages for communication with he user by SMS text messages. The primary SMS language
depends on ESIM364 firmware, which is based on the user’s location, while the secondary SMS language is always English.
Set SMS language
SMS
EKB2
Language
English
Lithuanian
Latvian
Estonian
Finnish
SK
RU
CZ
HU
PT
SP
GR
FR
MY
Slovak
Russian
Czech
Hungarian
Portuguese
Spanish
Greek
French
Malay
MANUAL ELDES ESIM364 V1.0
Menu path:
OK ĺ CONFIGURATION ĺ OK ĺ aaaa ĺ OK ĺ PRIMARY SETTINGS ĺ OK ĺ SMS
LANGUAGE ĺ OK ĺ ENGLISH | second-lang ĺ OK
Value: aaaa – 4-digit administrator password; second-lang – secondary language.
EKB3W
Enter parameter 35 and language number:
35 00 # - English
35 01 # - Secondary language
Example: 3501#
Config
Tool
This operation may be carried out from the PC using the ELDES Configuration Tool software.
EKB3/
ln value
EN
LT
LV
EE
FI
SMS text message content:
ln
Value: ln - language index.
Example: EN
The system supports one EKB2 menu language, which corresponds to the primary SMS language.
ATTENTION: To set SMS language by SMS text message, the user must do so before changing the
SMS password.
NOTE: To obtain a firmware that features a different primary SMS language/EKB2 menu language,
please contact your local dealer.
EN
29
8. USER PHONE NUMBERS
The system supports up to 10 user phone numbers identified as User 1 through 10. When the phone number is set, the user will be able to
arm/disarm the system by SMS text messages and free of charge phone calls (see 12.1. Free of Charge Phone Call and 12.2. SMS Text
Message) as well as to configure the system by SMS text messages. User phone numbers are also used to receive alarm phone calls and
SMS text messages from the system (see 17. ALARM INDICATIONS AND NOTIFICATIONS).
By default, the system ignores any incoming calls and SMS text messages from a non-preset phone number as well as it rejects the SMS text
messages containing wrong SMS password even from a preset user phone number (see 8.2. System Control from any Phone Number).
To set User 1 phone number is mandatory, while the other 9 are optional. The supported phone number formats are the following:
t
International (with plus) – The phone numbers must be entered starting with plus and an international country code in the following format: +[international code][area code][local number], example for UK: +4417091111111. This format can be used when
setting up the phone number by SMS text message and ELDES Configuration Tool software.
t
International (with 00) – The phone numbers must be entered starting with 00 and an international country code in the following
format: 00[international code][area code][local number], example for UK: 004417091111111. This format can be used when setting up the phone number by SMS text message, EKB2/EKB3/EKB3W keypad and ELDES Configuration Tool software.
t
Local – The phone numbers must be entered starting with an area code in the following format: [area code][local number], example
for UK:017091111111. This format can be used when setting up the phone number by SMS text message, EKB2/ EKB3/EKB3W keypad and ELDES Configuration Tool software.
Set user phone
number
SMS
EKB2
EKB3/
EKB3W
Config
Tool
View user phone
number
30
EN
SMS text message content:
ssss_NRup:ttteeellnnuumm
Value: ssss – 4-digit SMS password; up – user phone number slot, range – [1... 10]; ttteeellnnuumm – up to 15 digits user phone number.
Example: 1111_NR1:+4417091111111
Menu path:
OK ĺ CONFIGURATION ĺ OK ĺ aaaa ĺ OK ĺ PRIMARY SETTINGS ĺ OK ĺ CALL/SMS SETTINGS
ĺ OK ĺ USERS ĺ OK ĺ USER 1... 10 ĺ OK ĺ PHONE NUMBER ĺ OK ĺ ttteeellnnuumm ĺ OK
Value: aaaa – 4-digit administrator password; ttteeellnnuumm – up to 15 digits user phone
number.
Enter parameter 17, user phone number slot & phone number:
17 up ttteeellnnuumm #
Value: up – user phone number slot, range – [01... 10]; ttteeellnnuumm – up to 15 digits user
phone number.
Example: 1701004417091111111#
This operation may be carried out from the PC using the ELDES Configuration Tool software.
SMS
SMS text message content:
ssss_HELPNR
Value: ssss – 4-digit SMS password.
Example: 1111_HELPNR
EKB2
Menu path:
OK ĺ CONFIGURATION ĺ OK ĺ aaaa ĺ OK ĺ PRIMARY SETTINGS ĺ OK ĺ CALL/SMS
SETTINGS ĺ OK ĺ USERS ĺ OK ĺ USER 1... 10 ĺ OK ĺ PHONE NUMBER
Value: aaaa – 4-digit administrator password.
Config
Tool
This operation may be carried out from the PC using the ELDES Configuration Tool software.
MANUAL ELDES ESIM364 V1.0
Delete user phone
number
SMS
SMS text message content:
ssss_HELPNR
Value: ssss – 4-digit SMS password.
Example: 1111_HELPNR
EKB2
Menu path:
OK ĺ CONFIGURATION ĺ OK ĺ aaaa ĺ OK ĺ PRIMARY SETTINGS ĺ OK ĺ CALL/SMS
SETTINGS ĺ OK ĺ USERS ĺ OK ĺ USER 2... 10 ĺ OK ĺ PHONE NUMBER ĺ OK ĺ OK
Value: aaaa – 4-digit administrator password.
Config
Tool
This operation may be carried out from the PC using the ELDES Configuration Tool software.
ATTENTION: NEVER add a phone number of the device’s SIM card as a user phone number!
ATTENTION: Once User 1 phone number is set, it will be restricted to modify it only.
NOTE: Multiple user phone numbers can be set by a single SMS text message, Example: 1111_NR1:+4417091111111_
NR2:+4417091111112_NR6:017091111113_NR10:+4417091111114
NOTE: Multiple user phone numbers can be deleted by a single SMS text message, Example: 1111_NR2:DEL_NR3:DEL_NR6:DEL_
NR9:DEL_NR:10:DEL
8.1. User Phone Number Names
When the system is armed or disarmed by free of charge phone call or SMS text message, the system sends a confirmation by SMS text message to user phone number that the system arming/disarming was initiated from. The SMS text message is sent regarding each partition
separately and contains system status and partition name as well as it may contain a user name, set to the user phone number.
Manage user phone
number name
Config
Tool
This operation may be carried out from the PC using the ELDES Configuration Tool software.
8.2. System Control from any Phone Number
By default, the system ignores any incoming calls and SMS text messages from a non-preset phone number as well as it rejects the SMS
text messages containing wrong SMS password even from a preset user phone number. To allow/disallow system arming/disarming by
phone call and SMS text messages that contain a valid SMS password from any phone number, please refer to the following configuration
methods.
Enable system control
from any phone
number
SMS
SMS text message content:
ssss_STR:ON
Value: ssss – 4-digit SMS password.
Example: 1111_STR:ON
EKB2
Menu path:
OK ĺ CONFIGURATION ĺ OK ĺ aaaa ĺ OK ĺ PRIMARY SETTINGS ĺ OK ĺ CALL/SMS
SETTINGS ĺ OK ĺ CTRL FROM ANY NUM ĺ OK ĺ ENABLE ĺ OK
Value: aaaa – 4-digit administrator password.
EKB3/
EKB3W
Config
Tool
MANUAL ELDES ESIM364 V1.0
Enter parameter 12 & parameter status value:
12 1 #
Example: 121#
This operation may be carried out from the PC using the ELDES Configuration Tool software.
EN
31
Disable system
control from any
phone number
SMS
SMS text message content:
ssss_STR:OFF
Value: ssss – 4-digit SMS password.
Example: 1111_STR:OFF
EKB2
Menu path:
OK ĺ CONFIGURATION ĺ OK ĺ aaaa ĺ OK ĺ PRIMARY SETTINGS ĺ OK ĺ CALL/SMS
SETTINGS ĺ OK ĺ CTRL FROM ANY NUM ĺ OK ĺ DISABLE ĺ OK
Value: aaaa – 4-digit administrator password.
EKB3/
EKB3W
Config
Tool
32
EN
Enter parameter 12 & parameter status value:
12 0 #
Example: 120#
This operation may be carried out from the PC using the ELDES Configuration Tool software.
MANUAL ELDES ESIM364 V1.0
9. DATE AND TIME
The system comes equipped with internal real-time clock (RTC) that keeps track of the current date and time. Once the system is up and
running, the user must set the correct date and time, otherwise the system will not operate properly. After shutting down and starting up
the system, the date and time must be set again.
Set date and time
SMS
EKB2
EKB3/
EKB3W
Config
Tool
SMS text message content:
ssss_yyyy.mm.dd_hr:mn
Value: ssss – 4-digit SMS password; yyyy – year; mm – month, range – [01... 12]; dd – day,
range – [01... 31]; hr – hours, range – [00... 23]; mn – minutes, range – [00... 59].
Example: 1111_2013.03.16_14:33
Menu path:
a) OK ĺ DATE/TIME SETTINGS ĺ OK ĺyyyy-mm-dd hr:mn ĺ OK
b) OK ĺ CONFIGURATION ĺ OK ĺ aaaa ĺ OK ĺ PRIMARY SETTINGS ĺ OK ĺ DATE/TIME
SETTINGS ĺ OK ĺ yyyy-mm-dd hr:mn ĺ OK
Value: aaaa – 4-digit administrator password; yyyy – year; mm – month, range – [01... 12];
dd – day, range – [01... 31]; hr – hours, range – [00... 23]; mn – minutes, range – [00... 59].
Enter parameter 66, date & time:
66 yyyy mm dd hr mn#
Value: yyyy – year; mm – month, range – [01... 12]; dd – day, range – [01... 31]; hr – hours,
range – [00... 23]; mn – minutes, range – [00... 59].
Example: 66201305291235#
This operation may be carried out from the PC using the ELDES Configuration Tool software.
NOTE: When the system is connected to the monitoring station, the date and time will be automatically synchronized with the monitoring
station upon the system startup.
MANUAL ELDES ESIM364 V1.0
EN
33
10. USER PASSWORDS
The system supports up to 30 numeric user passwords, identified as User Password 1 through 30, allowing to carry out system arming/disarming by the keypad. By default, User Password 1 is preset as 1111 and assigned to Partition 1. For more details regarding user password
partition, please refer to 23.4. User Password Partition.
Set user password
EKB2
EKB3/
EKB3W
Delete user password
Enter parameter 15, user password slot & user password:
15 us uuuu #
Value: us – user password slot, range – [01... 30]; uuuu – 4-digit user password; range –
[0000... 9999].
Example: 15021111#
Config
Tool
This operation may be carried out from the PC using the ELDES Configuration Tool software.
EKB2
Menu path:
OK ĺ CONFIGURATION ĺ OK ĺ aaaa ĺ OK ĺ PRIMARY SETTINGS ĺ OK ĺ PASSWORDS
ĺ OK ĺ REMOVE PASSWORD ĺ OK ĺ uuuu ĺ OK
Value: aaaa – 4-digit administrator password; uuuu – 4-digit user password.
EKB3W
Enter parameter 65 & user password:
65 uuuu #
Value: uuuu – 4-digit user password.
Example: 651111#
Config
Tool
This operation may be carried out from the PC using the ELDES Configuration Tool software.
EKB3/
Replace user
password
Menu path:
User password 1... 16: OK ĺ CONFIGURATION ĺ OK ĺ aaaa ĺ OK ĺ PRIMARY SETTINGS
ĺ OK ĺ PASSWORDS ĺ OK ĺ USER PSW (1-16) ĺ OK ĺ USER PASSWORD 1... 16 ĺ OK
ĺ PASSWORDS ĺ OK ĺ uuuu ĺ OK
User password 17... 30: OK ĺ CONFIGURATION ĺ OK ĺ aaaa ĺ OK ĺ PRIMARY SETTINGS
ĺ OK ĺ PASSWORDS ĺ OK ĺ USER PSW (17-30) ĺ OK ĺ USER PASSWORD 17... 30 ĺ OK
ĺ PASSWORDS ĺ OK ĺ uuuu ĺ OK
Value: aaaa – 4-digit administrator password; uuuu – 4-digit user password, range – [0000...
9999].
EKB2
EKB3/
EKB3W
Config
Tool
Menu path:
User password 1... 16: OK ĺ CONFIGURATION ĺ OK ĺ aaaa ĺ OK ĺ PRIMARY SETTINGS
ĺ OK ĺ PASSWORDS ĺ OK ĺ USER PSW (1-16)ĺ OK ĺ USER PASSWORD 1... 16 ĺ OK ĺ
PASSWORD ĺ OK ĺ uuuu ĺ OK
User password 17... 30: OK ĺ CONFIGURATION ĺ OK ĺ aaaa ĺ OK ĺ PRIMARY SETTINGS ĺ
OK ĺ PASSWORDS ĺ OK ĺ USER PSW (17-30) ĺ OK ĺ USER PASSWORD 17... 30 ĺ OK ĺ
PASSWORD ĺ OK ĺ uuuu ĺ OK
Value: aaaa – 4-digit administrator password; uuuu – 4-digit user password, range –
[0000... 9999].
Enter parameter 63, existing user password & new user password:
63 vvvv uuuu #
Value: vvvv – 4-digit existing user password; uuuu – 4-digit new user password, range –
[0000... 9999].
Example: 6311113254#
This operation may be carried out from the PC using the ELDES Configuration Tool software.
NOTE: The system does not allow to set a duplicate password
34
EN
MANUAL ELDES ESIM364 V1.0
One of the user passwords ranging from User Password 1 through 10 can be set as SGS (Security Guard Service) password, which is used
for system arming/disarming by a security service employee. When used, the SGS password will be identified by a unique Contact ID code
in the monitoring station.
Set SGS password
EKB2
Menu path:
OK ĺ CONFIGURATION ĺ OK ĺ aaaa ĺ OK ĺ PRIMARY SETTINGS ĺ OK ĺ PASSWORDS
ĺ OK ĺ SGS PASSWORD ĺ OK ĺ N/A / us ĺ OK
Value: aaaa – 4-digit administrator password; N/A – SGS password not in use; us – user password slot, range – [1... 10].
EKB3W
Enter parameter 73 & user password slot:
73 us #
Value: us – user password slot, range – [01... 10].
Example: 7309#
Config
Tool
This operation may be carried out from the PC using the ELDES Configuration Tool software.
EKB3/
The Duress password is used when system disarming is demanded by force. When used, the system will disarm as well as it will silently
transmit an alert to the monitoring station. Only one of the user passwords ranging from User Password 1 through 10 can be set as Duress
password.
Set Duress password
EKB2
Menu path:
OK ĺ CONFIGURATION ĺ OK ĺ aaaa ĺ OK ĺ PRIMARY SETTINGS ĺ OK ĺ PASSWORDS
ĺ OK ĺ DURESS PASSWORD ĺ OK ĺ N/A / us ĺ OK
Value: aaaa – 4-digit administrator password; N/A – Duress password not in use; us – user
password slot, range – [1... 10].
EKB3W
Enter parameter 74 & user password slot:
74 us #
Value: us – user password slot, range – [01... 10].
Example: 7403#
Config
Tool
This operation may be carried out from the PC using the ELDES Configuration Tool software.
EKB3/
10.1. User Password Names
When the system is armed or disarmed by entering a user password using a keypad, the system sends a confirmation by SMS text message
to user phone number, sharing the same partition (-s) as the keypad and user password. The SMS text message is sent regarding each partition separately and contains system status and partition name as well as it may contain a user name, set to the user password.
Manage user
password name
MANUAL ELDES ESIM364 V1.0
Config
Tool
This operation may be carried out from the PC using the ELDES Configuration Tool software.
EN
35
11. iBUTTON KEYS
An iButton key is a chip enclosed in a stainless steel tab usually implemented in a small plastic holder. ESIM364 system supports up to 5
iButton keys each holding a unique identity code (ID), which is used for system arming and disarming.
11.1. Adding and Removing iButton Keys
To add an iButton key to the system, do the following:
a) Enable Allow Adding New iButton Keys mode.
b) T ouch the key to the iButton key reader when the system is disarmed (see Fig. No. 27).
27
c)
The successfully added iButton key will be indicated by short beeps emitted by the system’s buzzer.
d) Add as many iButton keys as necessary – touch one key after another to the reader – until the number of 5 keys is reached.
NOTE: iButton Key 1 can be added without Allow Adding New iButton Keys mode being enabled.
Enable Allow Adding
New iButton Keys
mode
SMS
SMS text message content:
ssss_IBPROG:ON
Value: ssss – 4-digit SMS password.
Example: 1111_IBPROG:ON
EKB2
Menu path:
OK ĺ CONFIGURATION ĺ OK ĺ aaaa ĺ OK ĺ IBUTTON KEYS ĺ OK ĺ NEW IBUTTON ĺ
OK ĺ ENABLE ĺ OK
Value: aaaa – 4-digit administrator password.
EKB3/
EKB3W
Config
Tool
Enter parameter 18 & parameter status value:
18 0 #
Example: 180#
This operation may be carried out from the PC using the ELDES Configuration Tool software.
When adding of iButton keys is complete, please disable Allow Adding New iButton Keys mode.
Disable Allow Adding
New iButton Keys
mode
SMS
SMS text message content:
ssss_IBPROG:OFF
Value: ssss – 4-digit SMS password.
Example: 1111_IBPROG:ON
EKB2
Menu path:
OK ĺ CONFIGURATION ĺ OK ĺ aaaa ĺ OK ĺ IBUTTON KEYS ĺ OK ĺ NEW IBUTTON ĺ
OK ĺ DISABLE ĺ OK
Value: aaaa – 4-digit administrator password.
EKB3/
EKB3W
36
EN
Enter parameter 18 & parameter status value:
18 1 #
Example: 181#
MANUAL ELDES ESIM364 V1.0
Config
Tool
This operation may be carried out from the PC using the ELDES Configuration Tool software.
To view the ID of the added iButton keys, please refer to the following configuration methods.
View iButton key ID
EKB2
Menu path:
OK ĺ CONFIGURATION ĺ OK ĺ aaaa ĺ OK ĺ IBUTTON KEYS ĺ OK ĺ IBUTTON 1... 5 ĺ
OK ĺ ID
Value: aaaa – 4-digit administrator password.
Config
Tool
This operation may be carried out from the PC using the ELDES Configuration Tool software.
If the iButton key is lost or stolen, due to security reasons it is highly recommended to remove it from the system.
Remove individual
iButton key from the
system
Remove all iButton
keys from the system
EKB2
Menu path:
OK ĺ CONFIGURATION ĺ OK ĺ aaaa ĺ OK ĺ IBUTTON KEYS ĺ OK ĺ IBUTTON 1... 5 ĺ
OK ĺ REMOVE ĺ OK
Value: aaaa – 4-digit administrator password..
Config
Tool
This operation may be carried out from the PC using the ELDES Configuration Tool software.
SMS
SMS text message content:
ssss_RESETIB
Value: ssss – 4-digit SMS password.
Example: 1111_RESETIB
11.2. iButton Key Names
When the system is armed or disarmed by iButton key, the system sends a confirmation by SMS text message to preset user phone number,
sharing the same partition (-s) as the key. The SMS text message is sent regarding each partition separately and contains system status and
partition name as well as it may contain a user name, set to the iButton key.
Manage iButton key
name
MANUAL ELDES ESIM364 V1.0
Config
Tool
This operation may be carried out from the PC using the ELDES Configuration Tool software.
EN
37
12. ARMING AND DISARMING
The system features the following methods to carry out arming and disarming process:
t
Free of charge phone call.
t
SMS text message.
t
EKB2/EKB3/EKB3W keypad and user password.
t
iButton key.
t
EWK1 wireless keyfob.
t
Arm-Disarm by Zone.
t
EGR100 middle-ware.
The system arms/disarms the partitions that the preset user phone number, EKB2/EKB3/EKB3W keypad and user password, iButton key,
EWK1 wireless keyfob or zone, set up for Arm-Disarm by Zone method, are assigned to. For example, if User 1 phone number is assigned
to Partition 1, 2 and 4, the user will be able to arm/disarm Partition 1, 2 and 4 by a single phone call to the system (see 23. PARTITIONS).
By default, when the system is successfully armed or disarmed, it replies with confirmation by SMS text message. For more details on SMS
text message regarding system arming/disarming and how to manage it, please refer to 12.9. Disabling and Enabling Arm/Disarm
Notifications.
The system will allow to arm the system if the following system faults are present (see 29. INDICATION OF SYSTEM FAULTS):
t
Main power supply is lost.
t
t
t
t
t
t
t
t
Low battery.
Battery dead or missing.
Battery failed.
Siren failed.
Date/time not set.
GSM connection failed.
GSM antenna failed.
Wireless signal lost.
When attempting to arm the system in case of violated zone/tamper presence, the system will reply with SMS text message containing
violated zone/tamper number. Due to security reasons it is highly recommended to restore the violated zone/tamper before arming the
system. For more details on how to arm the system despite the violated zone presence, please refer to 14.6. Zone Attributes and 14.7.
Bypassing and Activating Zones.
The system ignores any incoming calls and SMS text messages from a non-preset phone number as well as it rejects the SMS text messages
containing wrong SMS password even from a preset user phone number. For more details regarding arming/disarming the system from a
non-preset phone number, please refer to 8.2. System Control from any Phone Number.
12.1. Free of Charge Phone Call
To arm and disarm the system, dial the system‘s phone number from any of 10 available user phone numbers (see 8. USER
PHONE NUMBERS for user phone number management). The phone call is free charge as the system rejects it and carries out
arming/disarming procedure afterwards. When arming – the system rejects the phone call after 2 rings, when disarming – the
system rejects the phone call immediately. If there is more than one preset user dialing to the system at the same time, the
system will accept the incoming call from the user who was the first to dial while other user (-s) will be ignored.
When system’s phone number is dialed for arming, the system will proceed as follows:
t
Non-partitioned system:
t
If ready (no violated zone/tamper), the system will arm.
t
If unready (violated zone/tamper is present), the system will not arm and provide a list of violated zones/tampers by SMS text message
to user phone number.
t
Partitioned system:
t
If all partitions are disarmed ready, the system will arm them.
If one or more partitions are disarmed unready (violated zone/tamper is present), the system will arm the ready partition (-s) and skip the
unready one (-s). The system will then send an SMS text message, containing a list of violated zones/tampers, to user phone number that
the system arming was initiated from.
If a combination of armed and disarmed ready partitions is present, the system will arm the disarmed ready partitions and skip the armed
ones.
38
EN
MANUAL ELDES ESIM364 V1.0
When a user phone number is assigned to multiple partitions, the user will be able arm/disarm the corresponding system partitions by
dialing the system’s phone number. For example, if User 1 is assigned to Partition 1, 2 and 3, the user will be able to arm/disarm Partition 1,
2 and 3 by a single phone call to the system from User 1 phone number. For more details on how to set user phone number partition, please
refer to 23.2. User Phone Number Partition.
28
CALL
User
ESIM364
12.2. SMS Text Message
SMS
To arm the system by SMS text message, send the following text to the system‘s phone number from any of 10 available user
phone numbers (see 8. USER PHONE NUMBERS for user phone number management). When the SMS text message for arming is sent to the system’s phone number, the system will proceed as follows:
t
t
Non-partitioned system:
t
If ready (no violated zone/tamper), the system will arm.
t
If unready, the system will not arm and provide a list of violated zones/tampers by SMS text message to user phone
number.
Partitioned system:
t
If all partitions are disarmed ready (no violated zone/tamper), the system will arm them.
t
If one or more partitions are disarmed unready (violated zone/tamper is present), the system will arm the ready partition (-s) and skip the unready one (-s). The system will then send an SMS text message, containing a list of violated
zones/tampers, to user phone number that the system arming was initiated from.
t
If a combination of armed and disarmed ready partitions is present, the system will arm the disarmed ready partitions
and skip the armed ones.
Arm the system
SMS text message content:
ssss_ARMp or ssss_ARMp,p,p,p
Value: ssss – 4-digit SMS password; p – partition number, range – [1... 4].
Example: 1111_ARM1
29
SMS
User
ESIM364
To disarm the system by SMS text message, send the following text to the system‘s phone number from any of 10 available user phone
numbers:
Disarm the system
SMS text message content:
ssss_DISARMp or ssss_DISARMp,p,p,p
Value: ssss – 4-digit SMS password; p – partition number, range – [1... 4].
Example: 1111_DISARM1,2,4
30
SMS
User
ESIM364
When a user phone number is assigned to multiple partitions, the user will be able arm/disarm the corresponding system partitions by
sending the SMS text message to the system’s phone number. For example, if User 3 is assigned to Partition 2 and 3, the user will be able
MANUAL ELDES ESIM364 V1.0
EN
39
to arm/disarm Partition 2 and/or 3 by sending an SMS text message from User 3 phone number. For more details on how to set user phone
number partition, please refer to 23.2. User Phone Number Partition.
12.3. EKB2 Keypad and User Password
READY message displayed in the home screen view by EKB2 keypad indicates that no system faults and violated zones are
present, therefore the system can be armed. If the message is displayed as NOT READY, the user must restore all violated
zones and tampers before arming the system. To arm the system by EKB2 keypad, enter any out of 30 available 4-digit user
passwords using the number keys on the keypad (see 10. USER PASSWORDS for user password management). By default,
the system arming process is as follows:
EKB2
t
Non-partitioned system – When a valid user password is entered, the system will initiate exit delay, the keypad’s buzzer
will emit short beeps and the keypad will display
icon next to the countdown timer. When the system is successfully
icon for 5 seconds and switch to home screen view.
armed, the keypad will display
t
Partitioned system; arming same partition as the keypad is assigned to – When a valid user password is entered,
the keypad will display the partition selection menu and the system will initiate exit delay. During the exit delay, the keypad’s buzzer will emit short beeps and the keypad will display ARMING part-name message for 3 seconds followed by
icon next to the countdown
partition selection menu. If ĸ key is touched during exit delay, the keypad will display
timer. When successfully armed, the keypad will display
icon for 3 seconds and switch to home screen view.
t
Partitioned system; arming different partition than the keypad is assigned to – When a valid user password is
entered, the keypad will display the partition selection menu. The system will initiate exit delay, but will not indicate it
on EKB2 keypad due to the difference between keypad partition and the one being armed. Then the keypad will display
ARMING part-name message for 3 seconds followed by partition selection menu. When the keypad back-light timeout
expires, the home screen view will follow.
Arm the system
1
2
3
4
5
6
7
8
9
0
Enter user password/menu path:
Non-partitioned system: uuuuĺ OK
Partitioned system: uuuuĺ OKĺ [p] part-nameĺ OK
Value: uuuu – 4-digit user password; p – partition number, range –
[1... 4], part-name – up to 15 characters partition name.
Example: 1111ĺ OKĺ [2] PART2ĺ OK
To cancel the system arming process:
t
Non-partitioned system – Enter the user password again during exit delay countdown.
t
Partitioned system – Select the partition again, that is currently being armed, from the partition selection menu during exit delay
countdown.
To disarm the system by EKB2 keypad, enter any out of 30 available 4-digit user passwords using the number keys on the keypad. By default, the system disarming process is as follows:
t
Non-partitioned system – When a valid user password is entered, the keypad will display
screen view.
t
Partitioned system – When a valid user password is entered, the keypad will display part-name DISARMED message for 3 seconds
and switch to partition selection menu followed by home screen view after the keypad back-light timeout expires.
Disarm the system
1
2
3
4
5
6
7
8
9
0
icon for 5 seconds and switch to home
Enter user password/menu path:
Non-partitioned system: uuuuĺ OK
Partitioned system: uuuuĺ OKĺ [p] part-nameĺ OK
Value: uuuu – 4-digit user password; p – partition number, range –
[1... 4], part-name – up to 15 characters partition name.
Example: 1111ĺ OKĺ [3] GARAGEĺ OK
When a user password is assigned to multiple partitions, the user will be able arm/disarm the corresponding system partitions by EKB2 keypad
using partition selection menu if one of the user password partitions correspond to the keypad partition. For example, if User Password 3 is
assigned to Partition 1, 2 and 4, while EKB2 keypad is assigned to Partition 2, the user will be able to arm/disarm Partition 1, 2 and 4 by entering User Password 3 and selecting the partitions from the partition selection menu. For more details on how to set keypad partition and user
password partition, please refer to 23.3. Keypad Partition and Keypad Partition Switch and 23.4. User Password Partition.
12.4. EKB3/EKB3W Keypad and User Password
EKB3/
EKB3W
40
EN
Illuminated indicator READY on EKB3/EKB3W keypad indicates that no system faults and violated zones are present, therefore
the system can be armed. violated zones are present, therefore the system can be armed. If the indicator is not illuminated,
the user must restore all violated zones and tampers before arming the system. To arm the system by EKB3/EKB3W keypad,
enter any out of 30 available 4-digit user passwords using the number keys on the keypad (see 10. USER PASSWORDS for
user password management). By default, when a valid user password is entered, the system will initiate exit delay, the keypad’s
buzzer will emit short beeps and the indicator ARMED will light ON.
MANUAL ELDES ESIM364 V1.0
Arm the system
1
2
3
4
5
6
7
8
9
Enter user password:
uuuu
Value: uuuu – 4-digit user password.
Example: 1111
0
To cancel the system arming process, enter the user password again during exit delay countdown.
To disarm the system by EKB3/EKB3W keypad, enter any out of 30 available 4-digit user passwords using the number keys on the keypad.
By default, when a valid user password is entered, EKB3/EKB3W keypad indicator ARMED will light OFF.
Disarm the system
1
2
3
4
5
6
7
8
9
Enter user password:
uuuu
Value: uuuu – 4-digit user password.
Example: 1111
0
The system will arm/disarm the partition corresponding to the one that user password (see 23.4. User Password Partition) and the
keypad (see 23.3. Keypad Partition and Keypad Partition Switch) are assigned to. For example, if User Password 4 is assigned to
Partition 2, 3 and 4, while EKB3/EKB3W keypad is assigned to Partition 2, the user will be able to arm/disarm only Partition 2 by entering
User Password 4. To arm/disarm a different partition than the keypad is assigned to, use keypad partition switch feature. For more details
on keypad partition switch, please refer to 23.3. Keypad Partition and Keypad Partition Switch.
NOTE: By default, User Password 1 is preset as 1111 and assigned to Partition 1.
12.5. iButton Key
To arm or disarm the system, touch the iButton key reader by any of 5 available iButton keys (see 11. iBUTTON KEYS for iButton key management). When the iButton is touched to the iButton key reader for arming, the system will proceed as follows:
t
t
Non-partition system:
t
If ready (no violated zone/tamper), the system will arm.
t
If unready, the system will not arm and provide a list of violated zones/tampers by SMS text message to user phone
number.
Partitioned system:
t
If all partitions are disarmed ready (no violated zone/tamper), the system will arm them.
t
If one or more partitions are disarmed unready (violated zone/tamper is present), the system will arm the ready partition (-s) and skip the unready one (-s). The system will then send an SMS text message, containing a list of violated
zones/tampers, to user phone number, sharing the same partition (-s) as the iButton key.
t
If a combination of armed and disarmed ready partitions is present, the system will arm the disarmed ready partitions
and skip the armed ones.
31
When an iButton key is assigned to multiple partitions, the user will be able arm/disarm the corresponding system partitions
by touching the iButton key to the reader. For example, if iButton 5 is assigned to Partition 1 and 4, the user will be able to arm/
disarm Partition 1 and 4 by touching iButton 5 to the reader. For more details on how to set iButton key partition, please refer
to 23.5. iButton Key Partition.
MANUAL ELDES ESIM364 V1.0
EN
41
12.6. EWK1 Wireless Keyfob
EWK1
To arm the system, press 1 of 4 keyfob buttons set to arm the system (by default – button
for arming, the system will proceed as follows:
t
). When EWK1 button is pressed
Non-partition/partitioned system:
t
If ready (no violated zone/tamper), the system will arm.
t
If unready, the system will not arm and provide a list of violated zones/tampers by SMS text message to user phone
number.
32
Arm the
system
To disarm the system, press 1 of 4 keyfob buttons set to disarm the system (by default – button
).
33
Disarm
the
system
The system will arm/disarm the partition corresponding to the one that EWK1 wireless keyfob is assigned to (see 23.6. EWK1
Wireless Keyfob Partition). For example, if EWK1 wireless keyfob is assigned to Partition 3, the user will be able to arm/
disarm only Partition 3. To arm a different partition than the EWK1 wireless keyfob is assigned to, bind another EWK1 keyfob to
the system and assign it to a different partition.
For more details on how to manage EWK1 keyfob buttons, please refer to ELDES Configuration Tool software‘s HELP section.
12.7. Arm-Disarm by Zone
ARM/
DISARM
ZONE
The Arm-Disarm by Zone feature allows to use a zone for arming and disarming the alarm system when the zone is violated and
restored. The process is performed by providing a low-level pulse for more than 3 seconds into the specified zone. It means that
violating and restoring the zone leads to system arming and by repeating this action the system becomes disarmed. The system
will arm/disarm the partition (-s) that the zone is assigned to. This method can be set up for one on-board zone only.
Set zone for ArmDisarm by Zone
method
EKB2
EKB3/
EKB3W
42
EN
Menu path:
OKĺ CONFIGURATIONĺ OKĺ aaaaĺ OKĺ ZONESĺ OKĺ ARM/DISARM BY ZONE
ĺ OKĺ ZONE 1... 12ĺ OK
Value: aaaa – 4-digit administrator password.
Enter parameter 34 & on-board zone number:
34 nn #
Value: nn – on-board zone number, range – [01... 12].
Example: 3403#
MANUAL ELDES ESIM364 V1.0
Disable Arm-Disarm by
Zone method
Config
Tool
This operation may be carried out from the PC using the ELDES Configuration Tool software.
EKB2
Menu path:
OKĺ CONFIGURATIONĺ OKĺ aaaaĺ OKĺ ZONESĺ OKĺ ARM/DISARM BY ZONE
ĺ OKĺ N/Aĺ OK
Value: aaaa – 4-digit administrator password.
EKB3/
EKB3W
Config
Tool
Enter parameter 34 & parameter status value
34 00 #
Example: 3400#
This operation may be carried out from the PC using the ELDES Configuration Tool software.
12.8. EGR100 Middle-Ware
EGR100
12.9. Disabling and Enabling Arm/Disarm Notifications
By default, when the system is successfully armed or disarmed, it replies with confirmation by SMS text message to:
t
user phone number, sharing the same partition as EKB2/EKB3/EKB3W keypad and user password, iButton key, EWK1 wireless keyfob
or zone, set up for Arm/Disarm by Zone method.
t
user phone number that the system arming/disarming by free of charge phone call was initiated from.
t
user phone number that the system arming/disarming by SMS text message was initiated from.
The confirmation SMS text message is sent to the user phone number regarding each partition separately and contains system status and
partition name as well as it may contain a user name assigned to user phone number, user password or iButton key. For more details on
names, please refer to 8.1. User Phone Number Names, 10.1. User Password Names and 11.2. iButton Key Names.
To disable/enable this notification for individual user phone number, please refer to the following configuration methods.
Disable arm/disarm
notification for
individual user phone
number
EKB2
EKB3W
Enter parameter 75, user phone number slot & parameter status value:
75 us 0 #
Value: us – user phone number slot, range – [01... 10].
Example: 75030#
Config
Tool
This operation may be carried out from the PC using the ELDES Configuration Tool software.
EKB3/
Enable arm/disarm
notification for
individual user phone
number
EKB2
EKB3/
EKB3W
MANUAL ELDES ESIM364 V1.0
Menu path:
OK ĺ CONFIGURATION ĺ OK ĺ aaaa ĺ OK ĺ PRIMARY SETTINGS ĺ OK ĺ CALL/SMS
SETTINGS ĺ OK ĺ USERS ĺ OK ĺ USER 1... 10 ĺ OK ĺ SEND ARM/DARM SMS ĺ OK ĺ
DISABLE ĺ OK
Value: aaaa – 4-digit administrator password.
Menu path:
OK ĺ CONFIGURATION ĺ OK ĺ aaaa ĺ OK ĺ PRIMARY SETTINGS ĺ OK ĺ CALL/SMS
SETTINGS ĺ OK ĺ USERS ĺ OK ĺ USER 1... 10 ĺ OK ĺ SEND ARM/DARM SMS ĺ OK ĺ
ENABLE ĺ OK
Value: aaaa – 4-digit administrator password.
Enter parameter 75, user phone number slot & parameter status value:
75 us 1 #
Value: us – user phone number slot, range – [01... 10].
Example: 75091#
EN
43
Config
Tool
This operation may be carried out from the PC using the ELDES Configuration Tool software.
By default, the system sends SMS text message only to the first available user phone number when the system is successfully armed/
disarmed. If the system did not receive the SMS delivery report during 20 seconds, it will attempt to send the SMS text message to the next
preset user phone number. To ignore the SMS delivery report and allow/disallow the system to send the SMS text message to every preset
user phone number, please refer to the following configuration methods.
Enable arm/disarm
notification for all
preset user phone
numbers
EKB2
EKB3/
EKB3W
Config
Tool
Disable arm/disarm
notification for all
preset user phone
numbers
EKB2
EKB3/
EKB3W
Config
Tool
44
EN
Menu path:
OKĺ CONFIGURATIONĺ OKĺ aaaaĺ OKĺ PRIMARY SETTINGSĺ OKĺ CALL/SMS
SETTINGSĺ OKĺ SEND ARM/DARM ALLĺ OKĺ ENABLEĺ OK
Value: aaaa – 4-digit administrator password.
Enter parameter 22 & parameter status value:
22 1 #
Example: 221#
This operation may be carried out from the PC using the ELDES Configuration Tool software.
Menu path:
OKĺ CONFIGURATIONĺ OKĺ aaaaĺ OKĺ PRIMARY SETTINGSĺ OKĺ CALL/SMS
SETTINGSĺ OKĺ SEND ARM/DARM ALLĺ OKĺ DISABLEĺ OK
Value: aaaa – 4-digit administrator password.
Enter parameter 22 & parameter status value:
22 0 #
Example: 220#
This operation may be carried out from the PC using the ELDES Configuration Tool software.
MANUAL ELDES ESIM364 V1.0
13. EXIT AND ENTRY DELAY
When arming, the system initiates the exit delay countdown (by default – 15 seconds) intended for the user to leave the secured area. The
exit delay is indicated by short beeps emitted by EKB2/EKB3/EKB3W keypad buzzer and buzzer, connected to the alarm system. When
arming:
t
a non-partitioned system,
t
a partitioned system, EKB2 keypad will display ARMING part-name message on the screen for 3 seconds and switch to partition
selection menu during exit delay.
icon will be displayed next to the countdown timer on EKB2 keypad screen during exit delay.
Exit delay is provided when arming the system by the following methods:
t
EKB2/EKB3/EKB3W keypad and user password.
t
iButton key.
t
EWK1 wireless keyfob.
t
Arm/Disarm by Zone.
To arm the system without exit delay, use one of the following system arming methods:
t
Free of charge phone call.
t
SMS text message.
t
EGR100 middle-ware.
Set exit delay
SMS
EKB2
EKB3/
EKB3W
Config
Tool
SMS text message content:
ssss_EXITDELAY:p,ext or ssss_EXITDELAY:p,ext;p,ext;p,ext;p,ext
Value: ssss – 4-digit SMS password; p – partition number, range – [1... 4], ext – exit delay
duration, range – [0... 600] seconds.
Example: 1111_EXITDELAY:1,20;3,43
Menu path:
OKĺ CONFIGURATIONĺ OKĺ aaaaĺ OKĺ PRIMARY SETTINGSĺ OKĺ EXIT DELAY
ĺ OKĺ PARTITION 1... 4ĺ OKĺ extĺ OK
Value: aaaa – 4-digit administrator password;, ext – exit delay duration, range – [0... 600]
seconds.
Enter parameter 72, partition number & exit delay duration:
72 pp ext #
Value: pp – partition number, range – [01... 04], ext – exit delay duration, range – [0... 600]
seconds.
Example: 7203259#
This operation may be carried out from the PC using the ELDES Configuration Tool software.
NOTE: Alternatively, you can set exit delay value to 0 in order to arm the system without exit delay by any available method.
Once the exit delay has expired, the system initiates the entry delay countdown (by default – 15 seconds) if a Delay type zone is violated.
The countdown is indicated by short beeps emitted by keypad buzzer and by steady beep emitted by system’s buzzer. The indication is intended to advise the user that the system should be disarmed. Once the user presses/touches any key on the keypad during this delay, the
buzzer of the keypad will be silenced. If the system is disarmed before the entry delay expires, no alarm will be caused.
Set entry delay for
Delay zone
MANUAL ELDES ESIM364 V1.0
SMS
SMS text message content:
ssss_ENTRYDELAY:nn,eeeee or ssss_EXITDELAY:nn,eeeee;nn,eeeee;nn,eeeee;nn,eeeee
Value: ssss – 4-digit SMS password; nn – zone number, range – [1... 76], eeeee – entry delay
duration, range – [0... 65535] seconds.
Example: 1111_ENTRYDELAY:1,25;54,14,12,20
EN
45
EKB2
EKB3/
EKB3W
Config
Tool
Menu path:
On-board zone: OKĺ CONFIGURATIONĺ OKĺ aaaaĺ OKĺ ZONESĺ OKĺ
ONBOARD ZONESĺ OKĺ ZONE 1... 12ĺ OKĺ ENTRY DELAYĺ OKĺ eeeeeĺ OK
Wireless zone: OKĺ CONFIGURATIONĺ OKĺ aaaaĺ OKĺ ZONESĺ OKĺ WIRELESS
ZONES 1... 4ĺ OKĺ WIRELESS ZONE 13... 76ĺ OKĺ ENTRY DELAYĺ OKĺ eeeeeĺ
OK
Keypad zone: OK ĺ CONFIGURATION ĺ OK ĺ aaaa ĺ OK ĺ ZONES ĺ OK ĺ KEYPAD ZONES
ĺ OK ĺ 1ST... 4TH KEYPAD ZONE ĺ OK ĺ ENTRY DELAY ĺ OK ĺ eeeee ĺ OK
EPGM1 zone: OK ĺ CONFIGURATION ĺ OK ĺ aaaa ĺ OK ĺ ZONES ĺ OK ĺ EPGM1
ZONES 1-16... EPGM1 ZONES 17... 32 ĺ OK ĺ EPGM1 ZONE 1... 32 ĺ OK ĺ ENTRY DELAY ĺ
OK ĺ eeeee ĺ OK
Value: aaaa – 4-digit administrator password; eeeee – entry delay duration, range – [0...
65535] seconds.
Enter parameter 54, partition number and entry delay duration:
54 nn eeeee #
Value: nn – zone number, range – [01... 76], eeeee – entry delay duration, range – [0... 65535]
seconds
Example: 5403259#
This operation may be carried out from the PC using the ELDES Configuration Tool software.
NOTE: Due to battery power saving reasons, EKB3W keypad buzzer will not sound during exit and entry delay if the violated Delay type
zone is not of the associated EKB3W keypad.
For more details on zone types, please refer to 14.5. Zone Type Definitions.
46
EN
MANUAL ELDES ESIM364 V1.0
14. ZONES
Detection devices such as motion detectors and door contacts are connected to the alarm system’s zone terminals. Once connected, the
associated zone’s parameters must be configured.
ESIM364 comes equipped with 6 on-board zones allowing to connect up to 6 detection devices. For more details regarding zone expansion,
please refer to 14.2. Zone Expansion.
ESIM364 zones are classified by 5 categories:
Zone category
Description
Max. number of
zones per device
Max. number of
zones in total
On-board Zones
Built-in wired zones of ESIM364 alarm system.
6/12*
6/12*
Keypad zones
Hardwired zones of EKB2/EKB3 keypad.
1
4
EPGM1 zones
Zones of EPGM1 - hardwired zone & PGM output expansion 16
module.
32
Wireless zones
Non-physical zones automatically created by connected 2**
wireless devices.
64***
Virtual zones
Non-physical zones intended for Panic button feature (alarm 64****
activaiton upon pressing the button) on EWK1 wireless keyfob. Virtual zones can be manually created using ELDES Configuration Tool software.
64****
* - 6-Zone mode is enabled by default. ATZ mode doubles the on-board zone number and increases it to 12 in total.
** - Depends on the connected wireless device.
*** - Available only if no zones, EPGM1 zones and virtual zones are present.
**** - Available only if no zones, EPGM1 zones and wireless zones are present.
14.1. Zone Numbering
The zone numbers ranging from Z1 through Z12 are permanently reserved for on-board zones even when ATZ mode is disabled. The
Z13-Z76 zone numbers are automatically assigned in the chronological order to the created virtual zones and the devices connected to the
system: keypads, wireless devices, EPGM1 modules.
14.2. Zone Expansion
For additional detection device connection, the number of zones can be expanded by:
t
enabling the ATZ (Advanced Technology zone) mode (see 14.4. ATZ (Advanced Technology Zone) Mode).
t
connecting EPGM1 hardwired zone and PGM output expansion module (see 32.1.3. EPGM1 – Hardwired Zone & PGM Output Expansion Module).
t
connecting keypads (see 32.1.1. EKB2 – LCD Keypad, 32.1.2. EKB3 – LED Keypad and 33.1. EKB3W – Wireless LED Keypad).
t
binding wireless devices (see 19. WIRELESS DEVICES).
t
creating virtual zones (see ELDES Configuration Tool software’s Help section).
The maximum supported number of zones is 76.
14.3. 6-Zone Mode
By default, ESIM364 alarm system runs in the 6-Zone mode under zone connection Type 1 allowing to connect up to 6 detection devices
of NO (normally-open) type to the on-board zone terminals as indicated in the wiring diagram of Type 1. Once a different zone connection
type is set, the detection device wiring must be done according to the wiring diagram of the associated type. Available zone connection
types for the 6-Zone mode:
t
Type 1 – Parallel wiring of NO (normally-open) detection device with 5,6kΩ EOL (end-of-line) resistor.
t
Type 2 – Serial wiring of NC (normally-closed) detection device with 5,6kΩ EOL resistor.
t
Type 3 – Combination of serial and parallel wiring of tamper with 5,6kΩ EOL resistor and NC (normally-closed) detection device with
3,3kΩ EOL resistor.
For zone wiring diagrams of the 6-Zone mode, please refer to 2.3.2. Zone Connection Types.
Set zone connection
type for 6-Zone mode
MANUAL ELDES ESIM364 V1.0
EKB2
Menu path:
OK ĺ CONFIGURATION ĺ OK ĺ aaaa ĺ OKĺ ZONES ĺ OK ĺ ZONE TYPE:6-ZONE M
ĺ OK ĺ TYPE 1... 3 ĺ OK
Value: aaaa – 4-digit administrator password.
EN
47
EKB3/
EKB3W
Config
Tool
Enter parameter 38 & number of zone connection type:
38 1 # – Type 1
38 2 # – Type 2
38 3 # – Type 3
Example: 382#
This operation may be carried out from the PC using the ELDES Configuration Tool software.
14.4. ATZ (Advanced Technology Zone) Mode
The ATZ mode is a software-based feature that doubles the number of on-board zones and enables two detection devices to be installed
per 1 zone terminal. Once this mode is enabled, the zone connection Type 4 is set automatically. The detection devices must be wired to
the on-board zone terminals as indicated in the wiring diagram of the associated zone connection type. Available zone connection types
for the ATZ mode:
t
Type 4 – Parallel wiring of 2 NC (normally-closed) detection devices with 5,6kΩ and 3,3kΩ EOL (end-of-line) resistors respectively.
5,6kΩ EOL resistor corresponds to zones ranging from Z1 through Z6, while 3,3kΩ EOL resistor corresponds to zones ranging from Z7
through Z12.
t
Type 5 – Combination of serial and parallel wiring of tamper with 5,6kΩ EOL resistor and 2 NC (normally-closed) detection devices with
5,6kΩ and 3,3kΩ EOL resistors respectively. 5,6kΩ EOL resistor corresponds to zones ranging from Z1 through Z6, while 3,3kΩ EOL
resistor corresponds to zones ranging from Z7 through Z12.
For zone wiring diagrams of the ATZ mode, please refer to 2.3.2. Zone Connection Types.
Enable ATZ mode
EKB2
EKB3/
EKB3W
Config
Tool
Disable ATZ mode
EKB2
EKB3/
EKB3W
Config
Tool
Set zone connection
type for ATZ mode
48
EN
EKB2
Menu path:
OK ĺ CONFIGURATION ĺ OK ĺ aaaa ĺ OKĺ ZONES ĺ OK ĺ ATZ MODE ĺ OK ĺ
ENABLE ĺ OK
Value: aaaa – 4-digit administrator password.
Enter parameter 28 & parameter status value:
28 1 #
Example: 281#
This operation may be carried out from the PC using the ELDES Configuration Tool software.
Menu path:
OK ĺ CONFIGURATION ĺ OK ĺ aaaa ĺ OKĺ ZONES ĺ OK ĺ ATZ MODE ĺ OK ĺ
DISABLE ĺ OK
Value: aaaa – 4-digit administrator password.
Enter parameter 28 & parameter status value:
28 0 #
Example: 280#
This operation may be carried out from the PC using the ELDES Configuration Tool software.
Menu path:
OK ĺ CONFIGURATION ĺ OK ĺ aaaa ĺ OKĺ ZONES ĺ OK ĺ ZONE TYPE:ATZ MODE ĺ
OK ĺ TYPE 4... 5 ĺ OK
Value: aaaa – 4-digit administrator password.
MANUAL ELDES ESIM364 V1.0
EKB3W
Enter parameter 39 & number of zone connection type:
39 4 # – Type 4
39 5 # – Type 5
Example: 395#
Config
Tool
This operation may be carried out from the PC using the ELDES Configuration Tool software.
EKB3/
NOTE: The ATZ mode applies to on-board zones only when enabled.
14.5. Zone Type Definitions
t
Follow – The zone can be violated during exit and entry delay without causing an alarm. If the zone is violated before the entry delay
has begun, it will cause an instant alarm. The zone is used where violating a zone during exit/entry delay is unavoidable. Typically, this
zone is used for indoor protection devices, such as motion detectors, installed close to the exit/entry doors.
t
Instant – The alarm is instantly caused if this zone is violated when the system is armed or during entry delay. This zone type is usually
used for doors, windows or other zones, and shock detectors.
t
24H – When the system is either armed or disarmed, the zone will cause instant alarm if violated. Normally, this type of zone is used for
securing the areas that require constant supervisory.
t
Delay – This zone type can be violated during exit and entry delay without causing an alarm. If the zone is violated when the system is
armed, it will initiate entry delay countdown intended for the user to disarm the system. If the zone is left violated after the exit delay
expires, it will cause an instant alarm. If the zone is not violated and restored during exit delay, the system will be armed in Stay mode
(see 15. STAY MODE). Typically, this zone type is used for door contacts installed at designated exit/entry doors.
t
Fire – If this zone type is violated when the system is either armed or disarmed, the alarm will be instantly caused and the siren/bell will
emit pulsating sound. Typically, this zone type is used for flame and smoke detectors.
t
Silent – This zone operates the same as 24H zone type, but the system will not activate the siren/bell and keypad buzzer if violated.
Normally, this zone type used for panic alarm buttons.
Set zone type for
individual zone
EKB2
EKB3/
EKB3W
Config
Tool
Menu path:
On-board zone: OK ĺ CONFIGURATION ĺ OK ĺ aaaa ĺ OK ĺ ZONES ĺ OK ĺ ONBOARD
ZONES ĺ OK ĺ ZONE 1... 12 ĺ OK ĺ TYPE ĺ OK ĺ FOLLOW | INSTANT | 24H | DELAY | FIRE
| SILENT ĺ OK
Wireless zone: OK ĺ CONFIGURATION ĺ OK ĺ aaaa ĺ OK ĺ ZONES ĺ OK ĺ WIRELESS
ZONES 1... 4 ĺ OK ĺ WIRELESS ZONE 13... 76 ĺ OK ĺ TYPE ĺ OK ĺ FOLLOW | INSTANT |
24H | DELAY | FIRE | SILENT ĺ OK
Keypad zone: OK ĺ CONFIGURATION ĺ OK ĺ aaaa ĺ OK ĺ ZONES ĺ OK ĺ KEYPAD
ZONES ĺ OK ĺ 1ST... 4TH KEYPAD ZONE ĺ OK ĺ TYPE ĺ OK ĺ FOLLOW | INSTANT | 24H |
DELAY | FIRE | SILENT ĺ OK
EPGM1 zone: OK ĺ CONFIGURATION ĺ OK ĺ aaaa ĺ OK ĺ ZONES ĺ OK ĺ EPGM1
ZONES 1-16... EPGM1 ZONES 17... 32 ĺ OK ĺ EPGM1 ZONE 1... 32 ĺ OK ĺ TYPE ĺ OK ĺ
FOLLOW | INSTANT | 24H | DELAY | FIRE | SILENT ĺ OK
Value: aaaa – 4-digit administrator password.
Enter parameter 53, zone number & zone type number:
53 nn 1 # – Follow
53 nn 2 # – Instant
53 nn 3 # – 24H
53 nn 4 # – Delay
53 nn 5 # – Fire
53 nn 6 # – Silent
Value: nn – zone number, range – [01... 76]
Example: 53125#
This operation may be carried out from the PC using the ELDES Configuration Tool software.
NOTE: The system will NOT activate siren/bell and keypad buzzer only when Silent zone type is violated.
MANUAL ELDES ESIM364 V1.0
EN
49
14.6. Zone Attributes
t
Stay – If this attribute is enabled, the zone, regardless of type, will not cause an alarm if violated when the system is Stay armed. For
more details on arming the system in the Stay mode, please refer to 15. STAY MODE.
t
Force – This attribute determines whether the system can be armed or not while a zone is violated. If a zone with the Force attribute
enabled is left violated until the exit delay expires, it will be ignored. Once the system is armed and the zone is restored, the violation
will not be ignored and the zone will operate according to the determined type. For more details on zone types, please refer to 14.5.
Zone Type Definitions.
t
Delay, ms – This attribute determines the zone sensitivity level by delay time (By default – 800 milliseconds). If a zone is left triggered
until the delay time expires, the zone is considered violated.
t
Delay becomes Instant in Stay mode – This attribute determines whether or not any Delay type zone will operate as Instant type
zone when the system is armed in the Stay mode. When the system is fully armed, the Delay type zone will operate normally. For more
details on Delay and Instant zone types, please refer to 14.5. Zone Type Definitions.
t
icon on EKB2 keypad screen whenever any
Chime – This feature is used to emit 3 short beeps from the keypad buzzer and display
Delay type zone is violated. Typically, the feature is used for designated exit/entry doors to indicate the opening of the doors.
NOTE: Due to battery power saving reasons, EKB3W wireless keypad buzzer will not sound if the Bell attribute is not enabled and the violated Delay type zone is not of the associated EKB3W wireless keypad. For more details on EKB3W wireless keypad, please refer to 33.2.1.
EKB3W – Wireless LED Keypad.
Enable Stay attribute
for individual zone
EKB2
EKB3W
Enter parameter 56, zone number & parameter status value:
56 nn 1 #
Value: nn – zone number, range – [01... 76].
Example: 56041#
Config
Tool
This operation may be carried out from the PC using the ELDES Configuration Tool software.
EKB3/
Disable Stay attribute
for individual zone
EKB2
EN
Menu path:
On-board zone: OK ĺ CONFIGURATION ĺ OK ĺ aaaa ĺ OK ĺ ZONES ĺ OK ĺ ONBOARD
ZONES ĺ OK ĺ ZONE 1... 12 ĺ OK ĺ STAY ĺ OK ĺ DISABLE ĺ OK
Wireless zone: OK ĺ CONFIGURATION ĺ OK ĺ aaaa ĺ OK ĺ ZONES ĺ OK ĺ WIRELESS
ZONES 1... 4 ĺ OK ĺ WIRELESS ZONE 13... 76 ĺ OK ĺ STAY ĺ OK ĺ DISABLE ĺ OK
Keypad zone: OK ĺ CONFIGURATION ĺ OK ĺ aaaa ĺ OK ĺ ZONES ĺ OK ĺ KEYPAD
ZONES ĺ OK ĺ 1ST... 4TH KEYPAD ZONE ĺ OK ĺ STAY ĺ OK ĺ DISABLE ĺ OK
EPGM1 zone: OK ĺ CONFIGURATION ĺ OK ĺ aaaa ĺ OK ĺ ZONES ĺ OK ĺ EPGM1
ZONES 1-16... EPGM1 ZONES 17... 32 ĺ OK ĺ EPGM1 ZONE 1... 32 ĺ OK ĺ STAY ĺ OK ĺ
DISABLE ĺ OK
Value: aaaa – 4-digit administrator password.
EKB3W
Enter parameter 56, zone number & parameter status value:
56 nn 0 #
Value: nn – zone number, range – [01... 76].
Example: 56190#
Config
Tool
This operation may be carried out from the PC using the ELDES Configuration Tool software.
EKB3/
50
Menu path:
On-board zone: OK ĺ CONFIGURATION ĺ OK ĺ aaaa ĺ OK ĺ ZONES ĺ OK ĺ ONBOARD
ZONES ĺ OK ĺ ZONE 1... 12 ĺ OK ĺ STAY ĺ OK ĺ ENABLE ĺ OK
Wireless zone: OK ĺ CONFIGURATION ĺ OK ĺ aaaa ĺ OK ĺ ZONES ĺ OK ĺ WIRELESS
ZONES 1... 4 ĺ OK ĺ WIRELESS ZONE 13... 76 ĺ OK ĺ STAY ĺ OK ĺ ENABLE ĺ OK
Keypad zone: OK ĺ CONFIGURATION ĺ OK ĺ aaaa ĺ OK ĺ ZONES ĺ OK ĺ KEYPAD
ZONES ĺ OK ĺ 1ST... 4TH KEPAD ZONE ĺ OK ĺ STAY ĺ OK ĺ ENABLE ĺ OK
EPGM1 zone: OK ĺ CONFIGURATION ĺ OK ĺ aaaa ĺ OK ĺ ZONES ĺ OK ĺ EPGM1 ZONES
1-16... EPGM1 ZONES 17... 32 ĺ OK ĺ EPGM1 ZONE 1... 32 ĺ OK ĺ STAY ĺ OK ĺ ENABLE ĺ
OK
Value: aaaa – 4-digit administrator password.
MANUAL ELDES ESIM364 V1.0
Enable Force attribute
for individual zone
EKB2
EKB3W
Enter parameter 82, zone number & parameter status value:
82 nn 1 #
Value: nn – zone number, range – [01... 76].
Example: 82061#
Config
Tool
This operation may be carried out from the PC using the ELDES Configuration Tool software.
EKB3/
Disable Force
attribute for
individual zone
Menu path:
On-board zone: OK ĺ CONFIGURATION ĺ OK ĺ aaaa ĺ OK ĺ ZONES ĺ OK ĺ ONBOARD
ZONES ĺ OK ĺ ZONE 1... 12 ĺ OK ĺ FORCE ĺ OK ĺ ENABLE ĺ OK
Wireless zone: OK ĺ CONFIGURATION ĺ OK ĺ aaaa ĺ OK ĺ ZONES ĺ OK ĺ WIRELESS
ZONES 1... 4 ĺ OK ĺ WIRELESS ZONE 13... 76 ĺ OK ĺ FORCE ĺ OK ĺ ENABLE ĺ OK
Keypad zone: OK ĺ CONFIGURATION ĺ OK ĺ aaaa ĺ OK ĺ ZONES ĺ OK ĺ KEYPAD
ZONES ĺ OK ĺ 1ST... 4TH KEYPAD ZONE ĺ OK ĺ FORCE ĺ OK ĺ ENABLE ĺ OK
EPGM1 zone: OK ĺ CONFIGURATION ĺ OK ĺ aaaa ĺ OK ĺ ZONES ĺ OK ĺ EPGM1
ZONES 1-16... EPGM1 ZONES 17... 32 ĺ OK ĺ EPGM1 ZONE 1... 32 ĺ OK ĺ FORCE ĺ OK ĺ
ENABLE ĺ OK
Value: aaaa – 4-digit administrator password.
EKB2
Menu path:
On-board zone: OK ĺ CONFIGURATION ĺ OK ĺ aaaa ĺ OK ĺ ZONES ĺ OK ĺ ONBOARD
ZONES ĺ OK ĺ ZONE 1... 12 ĺ OK ĺ FORCE ĺ OK ĺ DISABLE ĺ OK
Wireless zone: OK ĺ CONFIGURATION ĺ OK ĺ aaaa ĺ OK ĺ ZONES ĺ OK ĺ WIRELESS
ZONES 1... 4 ĺ OK ĺ WIRELESS ZONE 13... 76 ĺ OK ĺ FORCE ĺ OK ĺ DISABLE ĺ OK
Keypad zone: OK ĺ CONFIGURATION ĺ OK ĺ aaaa ĺ OK ĺ ZONES ĺ OK ĺ KEYPAD
ZONES ĺ OK ĺ 1ST... 4TH KEYPAD ZONE ĺ OK ĺ FORCE ĺ OK ĺ DISABLE ĺ OK
EPGM1 zone: OK ĺ CONFIGURATION ĺ OK ĺ aaaa ĺ OK ĺ ZONES ĺ OK ĺ EPGM1
ZONES 1-16... EPGM1 ZONES 17... 32 ĺ OK ĺ EPGM1 ZONE 1... 32 ĺ OK ĺ STAY ĺ OK ĺ
DISABLE ĺ OK
Value: aaaa – 4-digit administrator password.
EKB3W
Enter parameter 82, zone number & parameter status value:
82 nn 0 #
Value: nn – zone number, range – [01... 76].
Example: 82110#
Config
Tool
This operation may be carried out from the PC using the ELDES Configuration Tool software.
Set Delay, ms atrribute
Config
Tool
This operation may be carried out from the PC using the ELDES Configuration Tool software.
Enable/disable Delay
becomes Instant in
Stay mode attribute
Config
Tool
This operation may be carried out from the PC using the ELDES Configuration Tool software.
Disable Chime
attribute
EKB2
EKB3/
MANUAL ELDES ESIM364 V1.0
Menu path:
OK ĺ CONFIGURATION ĺ OK ĺ aaaa ĺ OK ĺ PRIMARY SETTINGS ĺ OK ĺ CALL/SMS
SETTINGS ĺ OK ĺ CHIME ĺ OK ĺ DISABLE ĺ OK
Value: aaaa – 4-digit administrator password.
EN
51
EKB3/
EKB3W
Config
Tool
Enable Chime attribute
EKB2
EKB3/
EKB3W
Config
Tool
Enter parameter 32 & parameter status value:
32 0 #
Example: 320#
This operation may be carried out from the PC using the ELDES Configuration Tool software.
Menu path:
OK ĺ CONFIGURATION ĺ OK ĺ aaaa ĺ OK ĺ PRIMARY SETTINGS ĺ OK ĺ CALL/SMS
SETTINGS ĺ OK ĺ CHIME ĺ OK ĺ ENABLE ĺ OK
Value: aaaa – 4-digit administrator password.
Enter parameter 32 & parameter status value:
32 1 #
Example: 321#
This operation may be carried out from the PC using the ELDES Configuration Tool software.
14.7. Bypassing and Activating Zones
ATTENTION: Zone bypassing and activation must be carried out without Configuration mode being activated by the EKB3/EKB3W keypad.
Zone bypassing allows the user to deactivate a violated zone and arm the system without restoring the zone. If a bypassed zone is violated
or restored during exit/entry delay, or when then system is armed, it will be ignored. When a zone is bypassed, EKB3/EKB3W keypad indicator BYPS will light ON and EKB2 keypad will display BYP message in the home screen view.
Bypass individual
violated zone
EKB2
EKB3/
EKB3W
Bypass all violated
zones
EKB2
Menu path:
OK ĺ BYPASS ĺ OK ĺ BYPASS LIST 1... 5 ĺ OK ĺ Z1-zone-name... Z76-zone-name ĺ OK ĺ
BYPASS ĺ OK
Value: zone-name - up to 24 characters zone name.
Press the [BYPS] key, enter zone number & user password:
BYPS nn uuuu #
Value: nn – zone number, range – [01... 76]; uuuu – 4-digit user password.
Example: BYPS091111#
Menu path:
OK ĺ BYPASS ĺ OK ĺ BYP VIOLATED ZONES ĺ OK
The zone will stay bypassed until the system is disarmed. Once the system is disarmed, the corresponding zone state will be indicated
on the keypads (see 32.1.1. EKB2 – LCD Keypad, 32.1.2. EKB3 – LED Keypad and 33.1. EKB3W – Wireless LED Keypad) and Info
SMS text message (see 26. SYSTEM INFORMATION. INFO SMS). Alternatively, the user can activate the bypassed zone by the following
configuration methods.
Activate bypassed
zone
EKB2
EKB3/
EKB3W
52
EN
Menu path:
OK ĺ BYPASS ĺ OK ĺ BYPASS LIST 1... 5 ĺ OK ĺ Z1-zone-name... Z76-zone-name ĺ OK ĺ
UNBYPASS ĺ OK
Value: zone-name - up to 24 characters zone name.
Press the [BYPS[ key, enter zone number & user password:
BYPS nn uuuu #
Value: nn – zone number, range – [01... 76]; uuuu – 4-digit user password.
Example: BYPS251111#
MANUAL ELDES ESIM364 V1.0
NOTE: Zones can only be bypassed and activated when the system is not armed.
14.8. Zone Names
Each zone has a name that can be customized by the user. Typically, the name specifies a device type connected to a determined zone
terminal, for Example: Kitchen doors opened. The zone names are used in SMS text messages that are sent to the user during alarm. the
By default, the zone names are: Z1 – Zone1, Z2 – Zone2, Z3 – Zone3, Z4 – Zone4 etc.
Set zone name
SMS
Config
Tool
View zone names
SMS
EKB2
Config
Tool
SMS text message content:
ssss_Znn:zone-name
Value: ssss – 4-digit SMS password; nn – zone number, range – [1... 76]; zone-name – up to
24 characters zone name.
Example: 1111_Z3:Door sensor triggered
This operation may be carried out from the PC using the ELDES Configuration Tool software.
SMS text message content:
ssss_STATUS
Value: ssss – 4-digit SMS password.
Example: 1111_STATUS
EKB2:
Menu path:
On-board zone: OK ĺ CONFIGURATION ĺ OK ĺ aaaa ĺ OK ĺ ZONES ĺ OK ĺ ONBOARD
ZONES ĺ OK ĺ ZONE 1... 12 ĺ OK ĺ NAME
Wireless zone: OK ĺ CONFIGURATION ĺ OK ĺ aaaa ĺ OK ĺ ZONES ĺ OK ĺ WIRELESS
ZONES 1... 4 ĺ OK ĺ WIRELESS ZONE 13... 76 ĺ OK ĺ NAME
Keypad zone: OK ĺ CONFIGURATION ĺ OK ĺ aaaa ĺ OK ĺ ZONES ĺ OK ĺ KEYPAD ZONES
ĺ OK ĺ 1ST... 4TH KEYPAD ZONE ĺ OK ĺ NAME
EPGM1 zone: OK ĺ CONFIGURATION ĺ OK ĺ aaaa ĺ OK ĺ ZONES ĺ OK ĺ EPGM1 ZONES
1-16... EPGM1 ZONES 17... 32 ĺ OK ĺ EPGM1 ZONE 1... 32 ĺ OK ĺ NAME
Value: aaaa – 4-digit administrator password.
This operation may be carried out from the PC using the ELDES Configuration Tool software.
ATTENTION: Colon, semi-colon characters, parameter names and/or values, such as PSW, STATUS, ON, OFF etc. are NOT allowed in zone
names
NOTE: Multiple zone names can be set by a single SMS text message, Example: 1111_Z1:Kitchen doors opened;Z3:Movement in basement;Z4:Bedroom window opened
14.9. Disabling and Enabling Zones
By default, all zones, except keypad and virtual zones, are enabled. To permanently disable/enable an individual zone, please refer to the
following configuration methods.
Disable zone
MANUAL ELDES ESIM364 V1.0
SMS
SMS text message content:
ssss_Znn:OFF
Value: ssss – 4-digit SMS password; nn – zone number, range – [1... 76].
Example: 1111_Z13:OFF
EN
53
EKB2
EKB3W
Enter parameter 52, zone number & parameter status value:
52 nn 0 #
Value: nn – zone number, range – [01... 76].
Example: 52360#
Config
Tool
This operation may be carried out from the PC using the ELDES Configuration Tool software.
EKB3/
Enable zone
SMS
EKB2
EN
SMS text message content:
ssss_Znn:ON
Value: ssss – 4-digit SMS password; nn – zone number, range – [1... 76].
Example: 1111_Z6:ON
Menu path:
On-board zone: OK ĺ CONFIGURATION ĺ OK ĺ aaaa ĺ OK ĺ ZONES ĺ OK ĺ ONBOARD
ZONES ĺ OK ĺ ZONE 1... 12 ĺ OK ĺ STATUS ĺ OK ĺ ENABLE ĺ OK
Wireless zone: OK ĺ CONFIGURATION ĺ OK ĺ aaaa ĺ OK ĺ ZONES ĺ OK ĺ WIRELESS
ZONES 1... 4 ĺ OK ĺ WIRELESS ZONE 13... 76 ĺ OK ĺ STATUS ĺ OK ĺ ENABLE ĺ OK
Keypad zone: OK ĺ CONFIGURATION ĺ OK ĺ aaaa ĺ OK ĺ ZONES ĺ OK ĺ KEYPAD ZONES
ĺ OK ĺ 1ST... 4TH KEYPAD ZONE ĺ OK ĺ STATUS ĺ ENABLE ĺ OK
EPGM1 zone: OK ĺ CONFIGURATION ĺ OK ĺ aaaa ĺ OK ĺ ZONES ĺ OK ĺ EPGM1 ZONES
1-16... EPGM1 ZONES 17... 32 ĺ OK ĺ EPGM1 ZONE 1... 32 ĺ OK ĺ STATUS ĺ ENABLE ĺ OK
Value: aaaa – 4-digit administrator password.
EKB3W
Enter parameter 52, zone number & parameter status value:
52 nn 1 #
Value: nn – zone number, range – [01... 76].
Example: 52151#
Config
Tool
This operation may be carried out from the PC using the ELDES Configuration Tool software.
EKB3/
54
Menu path:
On-board zone: OK ĺ CONFIGURATION ĺ OK ĺ aaaa ĺ OK ĺ ZONES ĺ OK ĺ ONBOARD
ZONES ĺ OK ĺ ZONE 1... 12 ĺ OK ĺ STATUS ĺ OK ĺ DISABLE ĺ OK
Wireless zone: OK ĺ CONFIGURATION ĺ STATUS ĺ aaaa ĺ OK ĺ ZONES ĺ OK ĺ
WIRELESS ZONES 1... 4 ĺ OK ĺ WIRELESS ZONE 13... 76 ĺ OK ĺ STATUS ĺ OK ĺ
DISABLE ĺ OK
Keypad zone: OK ĺ CONFIGURATION ĺ OK ĺ aaaa ĺ OK ĺ ZONES ĺ OK ĺ KEYPAD ZONES
ĺ OK ĺ 1ST... 4TH KEYPAD ZONE ĺ OK ĺ STATUS ĺ DISABLE ĺ OK
EPGM1 zone: OK ĺ CONFIGURATION ĺ OK ĺ aaaa ĺ OK ĺ ZONES ĺ OK ĺ EPGM1 ZONES
1-16... EPGM1 ZONES 17... 32 ĺ OK ĺ EPGM1 ZONE 1... 32 ĺ OK ĺ STATUS ĺ DISABLE ĺ OK
Value: aaaa – 4-digit administrator password.
MANUAL ELDES ESIM364 V1.0
15. STAY MODE
Stay mode allows the user to arm and disarm the alarm system without leaving the secured area. If the zones with Stay attribute enabled
are violated when the system is Stay armed, no alarm will be caused. Typically, this feature is used when arming the system at home before
going to bed.
The system can be Stay armed under the following conditions:
t
If a zone with Stay attribute enabled is violated and restored during exit delay, the system will arm in Stay mode. When arming the
system in Stay mode under this condition, one of the available arming methods must be used that provide exit delay. For more details
on these methods, please refer to 13. EXIT AND ENTRY DELAY.
t
The system will instantly arm in Stay mode when using one of the following methods.
Arm the system in
Stay mode
EKB2
EKB3/
EKB3W
Menu path:
Non-partitioned system: P2 ĺ uuuu ĺ OK
Partitioned system: P2 ĺ uuuu ĺ OK ĺ [p] part-name ĺ OK
Value: uuuu – 4-digit user password; p – partition number, range – [1... 4]; part-name – up to
15 characters partition name.
Press the [STAY] key & enter user password:
STAY uuuu
Value: uuuu – 4-digit user password.
Example: STAY1111
When the system is successfully armed in Stay mode, EKB2 keypad will display STAY message in the home screen view.
ATTENTION: System arming in Stay mode by the keypad must be carried out without Configuration mode being activated.
NOTE: The system can be armed in Stay mode, only if there is at least one zone with Stay attribute enabled.
NOTE: Stay mode is not supported by virtual zones.
For more details on how to enable Stay attribute for zone, please refer to 14.6. Zone Attributes.
MANUAL ELDES ESIM364 V1.0
EN
55
16. TAMPERS
The tamper circuit is a single closed loop such that a break in the loop at any point will cause a tamper alarm regardless of the system
status – armed or disarmed. During the tamper alarm, the system will activate the siren/bell and the keypad buzzer and send the SMS text
message to the preset user phone number. The system will cause tamper alarm under the following conditions:
t
If the enclosure of a detection device, siren/bell, metal cabinet or keypad is opened, the physical tamper switch will be triggered. By
default, indicated as Tamper x in the SMS text message (x = tamper number).
t
If the wireless signal is lost due to low signal level or low battery power on a certain wireless device. This event is identified as Wireless
Signal Loss. By default, indicated as Tamper x * in the SMS text message (x = tamper number; * = wireless signal loss).
By default, tamper alarm notification by SMS text message is enabled. To disable/enable tamper alarm notification, please refer to the
following configuration methods.
Disable tamper alarm
notification
EKB2
EKB3W
Enter parameter 25, event number & parameter status value:
25 13 0 # - Tamper alarm
25 18 0 # - Wireless signal loss
Example: 25180#
Config
Tool
This operation may be carried out from the PC using the ELDES Configuration Tool software.
EKB3/
Enable tamper alarm
notification
Menu path:
Tamper alarm: OK ĺ CONFIGURATION ĺ OK ĺ aaaa ĺ OK ĺ SMS MESSAGES 2 ĺ OK ĺ
TAMPER ALARM ĺOK ĺ DISABLE ĺ OK
Wireless signal loss: OK ĺ CONFIGURATION ĺ OK ĺ aaaa ĺ OK ĺ SMS MESSAGES 2 ĺ OK
ĺ WLESS SIGN LOSS EV ĺ OK ĺ DISABLE ĺ OK
Value: aaaa – 4-digit administrator password.
EKB2
Menu path:
Tamper alarm: OK ĺ CONFIGURATION ĺ OK ĺ aaaa ĺ OK ĺ SMS MESSAGES 2 ĺ OK ĺ
TAMPER ALARM ĺ OK ĺ ENABLE ĺ OK
Wireless signal loss: OK ĺ CONFIGURATION ĺ OK ĺ aaaa ĺ OK ĺ SMS MESSAGES 2 ĺ OK
ĺ WLESS SIGN LOSS EV ĺ OK ĺ ENABLE ĺ OK
Value: aaaa – 4-digit administrator password.
EKB3W
Enter parameter 25, event number & parameter status value:
25 13 1 # - Tamper alarm
25 18 1 # - Wireless signal loss
Example: 25131#
Config
Tool
This operation may be carried out from the PC using the ELDES Configuration Tool software.
EKB3/
For more details on how to view violated tamper, please refer to 17. ALARM INDICATIONS AND NOTIFICATIONS
16.1. Tamper Names
Each tamper has a name that can be customized by the user. The tamper names are used in SMS text messages that are sent to the user
during the tamper alarm. By default, the tamper names are: Tamper 1, Tamper 2, Tamper 3, Tamper 4 etc. To set a different tamper name,
please refer to the following configuration methods.
Manage tamper name
56
EN
Config
Tool
This operation may be carried out from the PC using the ELDES Configuration Tool software.
MANUAL ELDES ESIM364 V1.0
17. ALARM INDICATIONS AND NOTIFICATIONS
When a zone, depending on zone type (see 14.5. Zone Type Definitions), or tamper is violated, the system will cause an alarm. By default, the alarm duration is 1 minute (see 20. SIREN/BELL regarding the alarm duration). During the alarm, the system will follow this
pattern:
1. The system activates the siren/bell and the keypad buzzer.
a) The siren/bell will emit pulsating sound if the violated zone is of Fire type, otherwise the sound will be steady.
b) The keypad buzzer will emit short beeps.
c) Depending on violated zone type, EKB2 keypad will display BURGLARY ALARM message followed by one of the alarm messages in the
home screen view:
t
ALARM.
t
FIRE ALARM.
t
24H ALARM.
d) During the tamper alarm, EKB2 keypad will display TAMPER ALARM message in the home screen view.
e) If one or more zones are violated, EKB3/EKB3W will light ON the corresponding violated zone indicator (-s) ranging from 1 through
12. Indicator SYSTEM will flash if one or more high-numbered zones are violated. If one or tampers are violated, indicator SYSTEM will
light ON. For more details on viewing violated high-numbered zone and tamper numbers by EKB3/EKB3W keypad, please refer to 29.
INDICATION OF SYSTEM FAULTS.
2. The system attempts to send an SMS text message, containing the violated zone/tamper name (see 14.8. Zone Names on how to set
a zone name), to the first preset user phone number, sharing the same partition as the violated zone/tamper. The system will send SMS
text messages regarding each violated zone/tamper separately.
a) If the user phone number is unavailable and the system fails to receive the SMS delivery report during 20 seconds, it will attempt to
send the SMS text message to the next preset user phone number, assigned to the same partition as the previous one. The user phone
number may be unavailable due to the following reasons:
t
mobile phone was switched off.
t
was out of GSM signal coverage.
b) The system will continue sending the SMS text message to the next preset user phone numbers in the priority order until one is available. The system sends the SMS text message only once and will not return to the first user phone number if the last one was unavailable.
3. If enabled, the system attempts to ring the first user phone number, sharing the same partition as the violated zone/tamper. The system
will dial regarding each violated zone/tamper separately.
a) When the call is answered, the system will shut down the siren/bell and the user will be able to listen on the mobile phone for approx.
30 seconds to what is happening in the area, surrounding the alarm system. This feature will be available only if a microphone is connected to the system.
b) The system will dial the next preset user phone number, assigned to the same partition, if the previous user was unavailable due to the
following reasons:
c)
t
mobile phone was switched off.
t
mobile phone was out of GSM signal coverage.
t
provided “busy” signal.
t
user did not answer the call after several rings, predetermined by the GSM operator.
The system will continue dialing the next preset user phone numbers in the priority order until one is available. The system dials only
once and will not return to the first user phone number if the last one was unavailable.
d) The system will not dial the next preset user phone number if the previous one was available, but rejected the phone call.
To silent the siren/bell as well as to cease system phone calls and SMS text message sending to the user phone numbers, please disarm the
system (see 12. ARMING AND DISARMING).
View violated zones
MANUAL ELDES ESIM364 V1.0
SMS
SMS text message content:
ssss_INFO
Value: ssss – 4-digit SMS password.
Example: 1111_INFO
EKB2
Menu path:
OK ĺ VIOLATED ZONES ĺ OK ĺ ZONE 1... 76
EN
57
EKB3W
Please, refer to illuminated zone indicators ranging from 1 through 12 on the keypad. The
flashing indicator SYSTEM stands for violated high-numbered zones (Z13-Z76). For more
details on violated high-numbered zone indication, please refer to 29. INDICATION OF SYSTEM FAULTS.
Config
Tool
This operation may be carried out from the PC using the ELDES Configuration Tool software.
SMS
The systemwill automatically send an SMS text message, containing a violated tamper name,
to user phone number.
EKB2
Menu path:
OK ĺ VIOLATED TAMPERS ĺ OK ĺ TAMPER 1... 76
EKB3/
The illuminated indicator SYSTEM stands for system fault presence including violated tamper. For more details on violated tamper indication, please refer to 29. INDICATION OF SYSTEM FAULTS.
EKB3/
View violated tampers
EKB3W
For more details details on how to disable/enable SMS text messages and phone calls to preset user phone number in case of alarm, please
refer to 17.1. Enabling and Disabling Alarm Notifications
ATTENTION: System phone calls to the user phone number are disabled by force when connected to the monitoring station.
NOTE: If one or more zones/tampers are violated during the alarm, the system will attempt to send as many SMS text message and dial the
user phone number as many times as the zone/tamper was violated.
NOTE: If the system sent the SMS text message and/or dialed the user phone number after disarming the system, it means that the SMS
text message and/or phone call was queued up in the memory before the system was disarmed
17.1. Enabling and Disabling Alarm Notifications
By, default the system will not ring the preset user phone numbers in case of alarm. To enable/disable this feature, please refer to the
following configuration methods.
Enable call in
case of alarm
EKB2
EKB3/
EKB3W
Config
Tool
Disable call in
case of alarm
EKB2
EKB3/
EKB3W
58
EN
Menu path:
OK ĺ CONFIGURATION ĺ OK ĺ aaaa ĺ OK ĺ PRIMARY SETTINGS ĺ OK ĺ CALL/SMS
SETTINGS ĺ OK ĺ CALL IN CASE ALARM ĺ OK ĺ ENABLE ĺ OK
Value: aaaa – 4-digit administrator password.
Enter parameter 30 & parameter status value:
30 0 #
Example: 300#
This operation may be carried out from the PC using the ELDES Configuration Tool software.
Menu path:
OK ĺ CONFIGURATION ĺ OK ĺ aaaa ĺ OK ĺ PRIMARY SETTINGS ĺ OK ĺ CALL/SMS
SETTINGS ĺ OK ĺ CALL IN CASE ALARM ĺ OK ĺ DISABLE ĺ OK
Value: aaaa – 4-digit administrator password.
Enter parameter 30 & parameter status value:
30 0 #
Example: 300#
MANUAL ELDES ESIM364 V1.0
Config
Tool
This operation may be carried out from the PC using the ELDES Configuration Tool software.
By, default the system will send SMS text message to preset user phone numbers in case of alarm. To disable/enable this feature, please
refer to the following configuration methods.
Disable SMS text
message in case of
alarm
EKB2
EKB3/
EKB3W
Enable SMS text
message in case of
alarm
Menu path:
OK ĺ CONFIGURATION ĺ OK ĺ aaaa ĺ OK ĺ SMS MESSAGES 1 ĺ OK ĺ GENERAL
ALARM ĺ OK ĺ DISABLE ĺ OK
Value: aaaa – 4-digit administrator password.
Enter parameter 25, event number & parameter status Value:
25 03 0 #
Example: 25030#
Config
Tool
This operation may be carried out from the PC using the ELDES Configuration Tool software.
EKB2
Menu path:
OK ĺ CONFIGURATION ĺ OK ĺ aaaa ĺ OK ĺ SMS MESSAGES 1 ĺ OK ĺ GENERAL
ALARM ĺ OK ĺ ENABLE ĺ OK
Value: aaaa – 4-digit administrator password.
EKB3/
EKB3W
Config
Tool
Enter parameter 25, event number & parameter status Value:
25 03 1 #
Example: 25031#
This operation may be carried out from the PC using the ELDES Configuration Tool software.
By default, the system sends SMS text message to the first available user in case of alarm. If the system did not receive the SMS delivery
report during 20 seconds, it will attempt to send the SMS text message to the next preset user phone number. To ignore the SMS delivery
report and allow/disallow the system to send the SMS text message to every preset user phone number, please refer to the following
configuration methods.
Enable SMS text
message to all preset
user phone numbers in
case of alarm
SMS
EKB2
EKB3/
EKB3W
Config
Tool
MANUAL ELDES ESIM364 V1.0
SMS text message content:
ssss_SMSALL:ON
Value: ssss – 4-digit SMS password
Example: 1111_SMSALL:ON
Menu path:
OK ĺ CONFIGURATION ĺ OK ĺ aaaa ĺ OK ĺ PRIMARY SETTINGS ĺ OK ĺ CALL/SMS
SETTINGS ĺ OK ĺ SEND ALARM SMS ALL ĺ OK ĺ ENABLE ĺ OK
Value: aaaa – 4-digit administrator password.
Enter parameter 21 & parameter status Value:
21 1 #
Example: 211#
This operation may be carried out from the PC using the ELDES Configuration Tool software.
EN
59
Disable SMS text
message to all preset
user phone numbers in
case of alarm
SMS
EKB2
EKB3/
EKB3W
Config
Tool
SMS text message content:
ssss_SMSALL:OFF
Value: ssss – 4-digit SMS password
Example: 1111_SMSALL:OFF
Menu path:
OK ĺ CONFIGURATION ĺ OK ĺ aaaa ĺ OK ĺ PRIMARY SETTINGS ĺ OK ĺ CALL/SMS
SETTINGS ĺ OK ĺ SEND ALARM SMS ALL ĺ OK ĺ DISABLE ĺ OK
Value: aaaa – 4-digit administrator password.
Enter parameter 21 & parameter status value:
21 0 #
Example: 210#
This operation may be carried out from the PC using the ELDES Configuration Tool software.
By default, tamper alarm notification by SMS text message is enabled. For more details on how to disable/enable tamper alarm notification,
please refer to 16. TAMPERS.
60
EN
MANUAL ELDES ESIM364 V1.0
18. PROGRAMMABLE (PGM) OUTPUTS
A PGM output is a programmable output that toggles to its set up state when a specific event has occurred in the system, the scheduled
weekday and time has come or if the user has initiated the PGM output state change manually. Normally, PGM outputs can be used to open/
close garage doors, activate lights, heating, watering and much more. When a PGM output turns ON, the system triggers any device or relay
connected to it.
ESIM364 comes equipped with four open-collector PGM outputs allowing to connect up to four devices or relays. For more details on PGM
output expanding, please refer to 18.2. PGM Output Expansion.
ESIM364 PGM outputs are classified by 4 categories:
Description
Max. number of PGM
outputs per device
Max. number of PGM
outputs in total
On-board PGM Outputs
Built-in wired PGM outputs of ESIM364 alarm system.
4
4
EPGM8 PGM Outputs
PGM outputs of EPGM8 - hardwired PGM output expan8
sion module.
8
EPGM1 PGM Outputs
PGM outputs of EPGM1 - hardwired zone & PGM output
2
expansion module.
4
Wireless PGM Outputs
Non-physical PGM outputs automatically created by con2*
nected wireless devices.
64**
PGM output category
* - Depends on the connected wireless device.
** - Available only if no EPGM1 PGM outputs are present.
For PGM output wiring diagram, please refer to 2.3.6. Relay Finder® 40.61.9.12 with Terminal Socket 95.85.3.
18.1. PGM Output Numbering
The PGM output numbers ranging from C1 through C12 are permanently reserved for on-board PGM outputs even if EPGM8 module mode is
disabled. The C13-C76 PGM output number are automatically assigned in the chronological order to the devices connected to the system:
EPGM1 modules and wireless devices.
18.2. PGM Output Expansion
For additional electrical appliance connection, the number of PGM outputs can be expanded by:
t
connecting EPGM8 hardwired PGM output expansion module. (see 18.2.1. EPGM8 Mode and 32.3.1. EPGM8 – Hardwired PGM
Output Expansion Module)
t
connecting EPGM1 hardwired zone and PGM output expansion module (see 32.1.3. EPGM1 – Hardwired Zone & PGM Output Expansion Module).
t
binding the wireless devices (see 19. WIRELESS DEVICES).
The maximum supported PGM output number is 76.
18.2.1. EPGM8 Mode
EPGM8 is an expansion module, which expands the system with 8 additional hardwired PGM outputs. For more details on EPGM8 module
installation, please refer to 32.3.1. EPGM8 – Hardwired PGM Output Expansion Module.
Once the EPGM8 module is installed, the EPGM8 mode must be enabled.
Enable EPGM8 mode
EKB2
EKB3/
EKB3W
Config
Tool
MANUAL ELDES ESIM364 V1.0
Menu path:
OKĺ CONFIGURATIONĺ OKĺ aaaaĺ OKĺ PGM OUTPUTSĺ OKĺ USING EPGM8ĺ OK
ĺ ENABLEĺ OK
Value: aaaa – 4-digit administrator password.
Enter parameter 33 & parameter status value:
33 1 #
Example: 331#
This operation may be carried out from the PC using the ELDES Configuration Tool software.
EN
61
Disable EPGM8 mode
EKB2
EKB3/
EKB3W
Config
Tool
Menu path:
OKĺ CONFIGURATIONĺ OKĺ aaaaĺ OKĺ PGM OUTPUTSĺ OKĺ USING EPGM8ĺ OK
ĺ DISABLEĺ OK
Value: aaaa – 4-digit administrator password.
Enter parameter 33 & parameter status value:
33 0 #
Example: 330#
This operation may be carried out from the PC using the ELDES Configuration Tool software.
18.3. PGM Output Names
Each PGM output has a name that can be customized by the user. Typically, the name specifies a device type connected to a determined PGM
output, for Example: Lights. The name can be used instead of PGM output number when controlling the PGM output by SMS text message.
By default, the PGM output names are: C1 – Controll1, C2 – Controll2, C3 – Controll3, C4 – Controll4 etc.
Set PGM output name
SMS
Config
Tool
View PGM output
names
SMS
EKB2
Config
Tool
SMS text message content:
ssss_Coo:out-name
Value: ssss – 4-digit SMS password; oo – PGM output number, range – [1... 76]; out-name –
up to 16 characters PGM output name.
Example: 1111_C2:Lights
This operation may be carried out from the PC using the ELDES Configuration Tool software.
SMS text message content:
ssss_STATUS
Value: ssss – 4-digit SMS password.
Example: 1111_STATUS
Menu path:
On-board PGM output: OKĺ CONFIGURATIONĺ OKĺ aaaaĺ OKĺ PGM OUTPUTSĺ OK
ĺ ONBOARD OUTPUTSĺ OKĺ OUTPUT 1... 12ĺ OKĺ NAME
Wireless PGM output: OKĺ CONFIGURATIONĺ OKĺ aaaaĺ OKĺ PGM OUTPUTSĺ OKĺ
WIRELESS OUTPUTS 1... 4ĺ OKĺ OUTPUT 13... 76ĺ OKĺ NAME
Value: aaaa – 4-digit administrator password.
This operation may be carried out from the PC using the ELDES Configuration Tool software.
ATTENTION: Space, colon, semi-colon characters, parameter names and/or values, such as PSW, STATUS, ON, OFF etc. are NOT allowed in
PGM output names.
18.4. Turning PGM Outputs ON and OFF
By default, all PGM outputs are turned OFF. To instantly turn ON/OFF an individual PGM output and set its state to ON/OFF when the system
starts-up, please refer to the following configuration methods.
Turn ON PGM output/
Set PGM output startup state as ON
62
EN
SMS
SMS text message content:
ssss_Coo:ON or ssss_out-name:ON
Value: ssss – 4-digit SMS password; oo – PGM output number, range – [1... 76]; out-name –
up to 16 characters PGM output name.
Example: 1111_Lights:ON
MANUAL ELDES ESIM364 V1.0
EKB2
EKB3W
Enter parameter 61, PGM output number & parameter status value:
61 oo 1 #
Value: oo – PGM output number, range – [01... 76].
Example: 61031#
Config
Tool
This operation may be carried out from the PC using the ELDES Configuration Tool software.
EKB3/
Turn OFF PGM output/
Set PGM output startup state as OFF
Menu path:
On-board PGM output: OKĺ CONFIGURATIONĺ OKĺ aaaaĺ OKĺ PGM OUTPUTSĺ OK
ĺ ONBOARD OUTPUTSĺ OKĺ OUTPUT 1... 12ĺ OKĺ STATUSĺ OKĺ ENABLEDĺ OK
Wireless PGM output: OKĺ CONFIGURATIONĺ OKĺ aaaaĺ OKĺ PGM OUTPUTSĺ OK
ĺ WIRELESS OUTPUTS 1... 4ĺ OKĺ OUTPUT 13... 76ĺ OKĺ STATUSĺ OKĺ ENABLED
ĺ OK
Value: aaaa – 4-digit administrator password.
SMS
EKB2
SMS text message content:
ssss_Coo:OFF or ssss_out-name:OFF
Value: ssss – 4-digit SMS password; oo – PGM output number, range – [1... 76]; out-name –
up to 16 characters PGM output name.
Example: 1111_C2:OFF
Menu path:
On-board PGM output: OKĺ CONFIGURATIONĺ OKĺ aaaaĺ OKĺ PGM OUTPUTSĺ OK
ĺ ONBOARD OUTPUTSĺ OKĺ OUTPUT 1... 12ĺ OKĺ STATUSĺ OKĺ DISABLEDĺ OK
Wireless PGM output: OKĺ CONFIGURATIONĺ OKĺ aaaaĺ OKĺ PGM OUTPUTSĺ OK
ĺ WIRELESS OUTPUTS 1... 4ĺ OKĺ OUTPUT 13... 76ĺ OKĺ STATUSĺ OKĺ DISABLED
ĺ OK
Value: aaaa – 4-digit administrator password.
EKB3W
Enter parameter 61, PGM output number & parameter status value:
61 oo 0 #
Value: oo – PGM output number, range – [01... 76].
Example: 61020#
Config
Tool
This operation may be carried out from the PC using the ELDES Configuration Tool software.
EKB3/
To instantly turn ON an individual PGM output for a determined time period and automatically turn it OFF when the time period expires,
please refer to the following configuration method.
Turn ON PGM output
for time period
SMS
SMS text message content:
ssss_Coo:ON:hr.mm.sc or ssss_out-name:ON:hr.mn.sc
Value: ssss – 4-digit SMS password; oo – PGM output number, range – [1... 76]; out-name
– up to 16 characters PGM output name; hr – hours, range – [00... 23]; mn – minutes, range
– [00... 59]; sc – seconds, range – [00... 59].
Example: 1111_C4:ON:10.15.35
To instantly turn OFF an individual PGM output for a determined time period and automatically turn it ON when the time period expires,
please refer to the following configuration method.
Turn OFF PGM output
for time period
SMS
SMS text message content:
ssss_Coo:OFF:00.00.sc or ssss_out-name:OFF:hr.mn.sc
Value: ssss – 4-digit SMS password;oo – PGM output number, range – [1... 76]; out-name
– up to 16 characters PGM output name; hr – hours, range – [00... 23]; mn – minutes, range
– [00... 59]; sc – seconds, range – [00... 59].
Example: 1111_Lights:OFF:00.00.23
When the PGM output is turned ON or OFF, the system will send a confirmation by SMS text message to the user phone number that the
SMS text message was sent from.
NOTE: PGM output can be turned ON for a determined time period only when it is in OFF state
MANUAL ELDES ESIM364 V1.0
EN
63
NOTE: PGM output can be turned ON for a determined time period only when it is in ON state
18.5. PGM Output Control by Event and Scheduler
The PGM outputs can automatically operate when a specific event occurs in the system and/or when the scheduled weekday and time
comes.
PGM Output Actions
The automatic action of the determined PGM output can be set as follows:
t
Turn ON – Determines whether the PGM output is to be turned ON.
t
Turn OFF – Determines whether the PGM output is to be turned OFF.
t
Pulse – Determines whether the PGM output is to be turned ON for a set period of time in seconds.
System Events
The aforementioned PGM output action can be automatically carried out under the following events that have occurred in the system:
t
System armed – System is armed in a determined partition ranging from Partition 1 through 4 or any partition.
t
System disarmed – System is disarmed in a determined partition ranging from Partition 1 through 4 or any partition.
t
Alarm begins – Alarm begins in a determined partition ranging from Partition 1 through 4 or any partition.
t
Alarm stops – Alarm stops in a determined partition ranging from Partition 1 through 4 or any partition.
t
Temperature falls – Temperature falls below the set MIN value of a determined temperature sensor 1-8.
t
Temperature rises – Temperature rises above the set MAX value of a determined temperature sensor 1-8.
t
Zone violated – A determined zone ranging from Z1 through Z76 is violated.
t
Zone restored – A determined zone ranging from Z1 through Z76 is restored.
t
Scheduler starts – Determines Start Time of a selected scheduler 1-16.
t
Scheduler ends – Determines End Time of a selected scheduler 1-16.
The user can also set a custom text, which will be sent by SMS text message to user phone number when the automatic PGM output action
is carried out.
Schedulers
The system supports up to 16 schedulers that allow the PGM outputs to operate according to the day of the week and time. When the
scheduler, which includes the set weekday and time, is selected, the PGM output will operate according to it. Each scheduler includes the
following parameters:
t
Always – The scheduler is not in use.
t
At specified time – Determines whether weekday and time settings are enabled:
t
Start Time – Determines the point in time when the PGM output action can begin.
t
End Time – Determines the point in time when the PGM output action can complete.
t
On weekdays – Determines days in week when the PGM output action is valid.
Additional Conditions
Additional condition narrows down the chances for a determined automatic PGM output operation to be carried out. If this feature is enabled, the PGM output will become dependent on one more system event that must be occurred prior or must occur after the aforementioned system event. The PGM output will not operate until the chain of system events meets the set values:
t
System armed – System is armed in a determined partition ranging from 1 to 4 or any partition.
t
System disarmed – System is disarmed in a determined partition ranging from 1 to 4 or any partition.
t
Zone violated – A determined zone ranging from Z1 to 76 is violated.
t
Zone restored – A determined zone ranging from Z1 to Z76 is restored.
Example: PGM output C1 is set to be turned ON when zone Z6 is violated. The additional condition feature is enabled and set to allow this
action to be carried out only if system’s Partition 2 is disarmed. It means that the PGM output C1 will be turned ON when zone Z6 is violated,
but only if system’s Partition 2 is disarmed.
Manage PGM output
control by event &
scheduler
64
EN
Config
Tool
This operation may be carried out from the PC using the ELDES Configuration Tool software.
MANUAL ELDES ESIM364 V1.0
NOTE: When both - a system event is determined and a scheduler is selected, the PGM output will operate only if the determined event has
occurred in the system during the scheduled time period.
ATTENTION: If the date and time are not set, the system will NOT be able to automatically control the PGM outputs. For more details on how
to set date and time, please refer to 9. DATE AND TIME.
18.6. Wireless PGM Output Type Definitions
t
Output – Operates as normal PGM output that can be controlled by the user or automatically by event and scheduler. Normally, this
type is used for any device or relay.
t
Siren – Operates as siren output that automatically activates during alarm. Typically, this type is used for bell/siren connected to EW1
wireless device.
Set output type for
individual wireless
PGM output
MANUAL ELDES ESIM364 V1.0
Config
Tool
This operation may be carried out from the PC using the ELDES Configuration Tool software.
EN
65
19. WIRELESS DEVICES
ESIM364 system has a built-in wireless module for system extension capabilities. The wireless module easily allows the user to bind up to
32 ELDES-made wireless devices to the system. This includes the following:
t
EWP1 – wireless PIR sensor (motion detector).
t
EWD1 – magnetic door contact.
t
EWS1 and EWS2 – internal and external sirens.
t
EWK1 – wireless keyfob.
t
EKB3W – wireless keypad.
t
EW1 – zone and PGM output expansion module.
t
EW1B – battery-powered zone and PGM output expansion module.
The wireless devices can operate at a range of up to 30 meters from the alarm system unit while inside the building and at up to 150
meters range in open areas. The wireless connection is two-way and operates in one of four available channels at 868MHz non-licensed
frequency range. The communication link between the wireless device and the alarm system is constantly supervised by a configurable
self-test period.
For more details on how to install the wireless devices, please refer to 33. ELDES WIRELESS DEVICES.
19.1. Binding, Removing and Replacing Wireless Devicess
When the wireless device is switched ON, it will initiate the data transmission to the system within its wireless connection range. In order to
optimize battery power saving of the wireless device, the data transmission periods vary by itself while the device is switched ON, but still
unbound. The data transmission period of the unbound or removed from the system wireless devices is as follows:
t
EKB3W:
t
t
First 36 attempts after the device startup (reset) - every 5 seconds;
t
Next 5 attempts - every 1 minute;
t
The rest of attempts - every 5 minutes.
EW1, EW1B, EWP1, EWD1, EWS1, EWS2:
t
First 60 attempts after the device startup (reset) - every 10 seconds.
t
Next 60 attempts - every 1 minute.
t
The rest of attempts - every 5 minutes.
By default, the data transmission (supervision signal) period of the bound wireless devices is identified as Test Time and it is as follows:
t
EKB3W: every 60 seconds.
t
EW1, EWP1: every 30 seconds.
t
EW1B: every 20 seconds.
t
EWD1: every 60 seconds.
t
EWS1, EWS2: every 7 seconds.
To set a different Test Time value, please refer to the following configuration method.
Set Test Time
Config
Tool
This operation may be carried out from the PC using the ELDES Configuration Tool software.
NOTE: Test Time affects the wireless device binding process due to the alarm system listening for the incoming data from the wireless
device. The system binds the wireless device only when the first data packet is received.
NOTE FOR EKB3W USERS: Due to battery power saving reasons, Test Time period for EKB3W wireless keypad is 60 seconds (by default)
and affects the alarm indication on the keypad. For example, the communication between the system and EKB3W occured at 09:00:00. A
zone was violated at 09:00:10. In such situation, EKB3W would indicate the violated zone at 09:01:00
An 8-digit wireless device ID code will be required in order to bind the device to the system or to remove it from the system. The wireless
ID code is printed on a label, which can be located on the inner or outer side of the enclosure or on the printed circuit board (PCB) of the
wireless device.
To bind a wireless device, please refer to the following configuration methods.
66
EN
MANUAL ELDES ESIM364 V1.0
Bind wireless device
to the system
SMS
Config
Tool
SMS text message content:
ssss_SET:wless-id
Value: ssss – 4-digit SMS password; wless-id – 8-digit wireless device ID code.
Example: 1111_SET:535185D
This operation may be carried out from the PC using the ELDES Configuration Tool software.
NOTE FOR EWK1 USERS: When binding EWK1 wireless keyfob, it is necessary to press any button on the keyfob several times.
Once a wireless device is bound, it occupies one of 32 available wireless device slots and the system adds one or two wireless zones and
wireless PGM outputs depending on the wireless device model.
To remove a wireless device, please refer to the following configuration methods.
Remove wireless
device from the
system
SMS
Config
Tool
SMS text message content:
ssss_DEL:wless-id
Value: ssss – 4-digit SMS password; wless-id – 8-digit wireless device ID code.
Example: 1111_DEL:535185D
This operation may be carried out from the PC using the ELDES Configuration Tool software.
Once a wireless device is removed from the system, please restore its default parameters and remove the batteries from it.
To replace an existing wireless device with a new same model device, please refer to the following configuration methods
Replace wireless
device
SMS
Config
Tool
SMS text message content:
ssss_REP:wless-id<oldwl-id
Value: ssss – 4-digit SMS password; wless-id – 8-digit wireless device ID code of the old device; oldwl-id - 8-digit wireless device ID code of the new device.
Example: 1111_REP:535185D<41286652
This operation may be carried out from the PC using the ELDES Configuration Tool software.
When a wireless device is successfully replaced with a new one, the configuration of the old wireless device remains.
NOTE: If you are unable to bind a wireless device, please restore the wireless device’s parameters to default and try again. For more details
on how to restore the default parameters, please refer to the user manual provided along with the wireless device or visit www.eldes.lt/en/
download to download the latest user manual
ATTENTION: In order to fully remove the device from the system, the user must restore the parameters of the wireless device to default
and remove it from the system. If only one of these actions is carried out, the wireless device (except EWK1) and the system will attempt to
exchange data to keep the wireless connection alive. This leads to fast battery power drain on the battery-powered wireless device.
19.2. Wireless Device Information and Signal Status Monitoring
Once a wireless device is bound, the user can view the following information of a determined wireless device:
t
Battery level (expressed in percentage).
t
Wireless signal strength (expressed in percentage).
t
Error rate (number of failed data transmission attempts in 10-minute period).
t
Firmware version.
To view the wireless device information, please refer to the following configuration methods.
MANUAL ELDES ESIM364 V1.0
EN
67
View wireless device
information
SMS
EKB2
Config
Tool
SMS text message content:
ssss_RFINFO:wless-id or ssss_RFINFO:Znn
Value: wless-id – 8-digit wireless device ID code; nn – wireless zone number, range – [13...
76].
Example: 1111_RFINFO:535185D
Menu path:
Battery level: OKĺ CONFIGURATIONĺ OKĺ aaaaĺ OKĺ WIRELESS DEVICES 1... 2ĺ OKĺ
wless-dev wless-idĺ OKĺ BATTERY
Wireless signal: OKĺ CONFIGURATIONĺ OKĺ aaaaĺ OKĺ WIRELESS DEVICES 1... 2ĺ OK
ĺ wless-dev wless-idĺ OKĺ SIGNAL
Error rate: OKĺ CONFIGURATIONĺ OKĺ aaaaĺ OKĺ WIRELESS DEVICES 1... 2ĺ OKĺ
wless-dev wless-idĺ OKĺ ERROR RATE
Firmware version: OKĺ CONFIGURATIONĺ OKĺ aaaaĺ OKĺ WIRELESS DEVICES 1... 2ĺ
OKĺ wless-dev wless-idĺ OKĺ FW RELEASE
Value: aaaa – 4-digit administrator password; wless-dev – wireless device model; wless-id
– 8-digit wireless device ID code.
This operation may be carried out from the PC using the ELDES Configuration Tool software.
The system supports up to 32 wireless devices. To view the number of unoccupied wireless device slots in the system, please refer to the
following configuration methods
View unoccupied
wireless device slots
SMS
Config
Tool
SMS text message content:
ssss_STATUS_FREE
Example: 1111_STATUS_FREE
This operation may be carried out from the PC using the ELDES Configuration Tool software.
When the wireless signal between the system and all wireless devices is lost or restored, the system will send notification by SMS text
message to preset user phone number. By default, the notification regarding the wireless signal status is enabled. To disable/enable this
notification, please refer to 16. TAMPERS.
68
EN
MANUAL ELDES ESIM364 V1.0
19.3. Disabling and Enabling Siren if Wireless Signal is Lost
If a wireless device loses its wireless signal, the system will send notification by SMS text message to user phone number and activate
the siren/bell. By default, the siren will not be activated when wireless signal is lost. To enable/disable this feature, please refer to the
following configuration methods.
Enable Siren if
Wireless Signal is Lost
EKB2
EKB3/
EKB3W
Config
Tool
Disable Siren if
Wireless Signal is Lost
EKB2
EKB3/
EKB3W
Config
Tool
MANUAL ELDES ESIM364 V1.0
Menu path:
OKĺ CONFIGURATIONĺ OKĺ aaaaĺ OKĺ PRIMARY SETTINGSĺ OKĺ SIREN SETTINGS
ĺOKĺ SRN IF WLESS LOSSĺ OKĺ ENABLEĺ OK
Value: aaaa – 4-digit administrator password.
Enter parameter 76 & parameter status value:
76 1 #
Example: 761#
This operation may be carried out from the PC using the ELDES Configuration Tool software.
Menu path:
OKĺ CONFIGURATIONĺ OKĺ aaaaĺ OKĺ PRIMARY SETTINGSĺ OKĺ SIREN SETTINGS
ĺOKĺ SRN IF WLESS LOSSĺ OKĺ DISABLEĺ OK
Value: aaaa – 4-digit administrator password.
Enter parameter 76 & parameter status value:
76 0 #
Example: 760#
This operation may be carried out from the PC using the ELDES Configuration Tool software.
EN
69
20. SIREN/BELL
When the system is in alarm state, the siren/bell will sound until the set time (By default – 1 minute) expires or until the system is disarmed.
To set the alarm duration, please refer to the following configuration methods.
Set alarm duration
SMS
SMS text message content:
ssss_SIREN:t
Value: ssss – 4-digit SMS password; t – alarm duration, range – [0... 5] minutes.
Example: 1111_SIREN:4
EKB2
Menu path:
OKĺ CONFIGURATIONĺ OKĺ aaaaĺ OKĺ PRIMARY SETT INGSĺ OKĺ SIREN SETTINGS
ĺ OKĺ ALARM DURATIONĺ OKĺ ttĺ OK
Value: aaaa – 4-digit administrator password; tt – alarm duration, range – [1... 10] minutes.
EKB3W
Enter parameter 10 & alarm duration:
10 tt #
Value: tt – alarm duration, range – [00... 10] minutes.
Example: 1007#
Config
Tool
This operation may be carried out from the PC using the ELDES Configuration Tool software.
EKB3/
View alarm duration
SMS
SMS text message content:
ssss_SIREN
Value: ssss – 4-digit SMS password
Example: 1111_SIREN
EKB2
Menu path:
OKĺ CONFIGURATIONĺ OKĺ aaaaĺ OKĺ PRIMARY SETT INGSĺ OKĺ SIREN SETTINGS
ĺ OKĺ ALARM DURATION
Value: aaaa – 4-digit administrator password.
Config
Tool
This operation may be carried out from the PC using the ELDES Configuration Tool software.
For siren/bell wiring diagram, please refer to 2.3.3. Siren.
NOTE: 0 value disables the siren/bell.
NOTE: Due to battery power saving reasons, the wireless siren will sound for 1 minute regardless of the set alarm duration time, unless it is
set to 0.
70
EN
MANUAL ELDES ESIM364 V1.0
20.1. BELL Output Status Monitoring
The system constantly supervises the BELL output. If the siren/bell is disconnected/cut-off, the system will instantly send the notification
by SMS text message to User 1 and indicate system fault condition on the keypad (see 29. INDICATION OF SYSTEM FAULTS). Once the
bell/siren is connected/fixed, the system will notify User 1 by SMS text message and the keypad will no longer indicate system fault.
By default, the notification by SMS text message regarding the BELL output status is disabled. To enable/disable this notification, please
refer to the following configuration methods.
Enable Siren Fail/
Restore notification
EKB2
EKB3/
EKB3W
Config
Tool
Disable Siren Fail/
Restore notification
EKB2
EKB3/
EKB3W
Config
Tool
Menu path:
OKĺ CONFIGURATIONĺ OKĺ aaaaĺ OKĺ SMS MESSAGES 1ĺ OKĺ SIREN FAIL/REST
EVĺ OKĺ ENABLEĺ OK
Value: aaaa – 4-digit administrator password.
Enter parameter 25, notification number & parameter status value:
25 08 1 #
Example: 25081#
This operation may be carried out from the PC using the ELDES Configuration Tool software.
Menu path:
OKĺ CONFIGURATIONĺ OKĺ aaaaĺ OKĺ SMS MESSAGES 1ĺ OKĺ SIREN FAIL/REST
EVĺ OKĺ DISABLEĺ OK
Value: aaaa – 4-digit administrator password.
Enter parameter 25, notification number & parameter status value:
25 08 0 #
Example: 25080#
This operation may be carried out from the PC using the ELDES Configuration Tool software.
20.2. Bell Squawk
If enabled, the siren/bell indicates the completed system arming and disarming process. After the system is successfully armed, the siren/
bell will emit 2 short beeps and 1 long beep after the system is disarmed. To enable/disable the Bell Squawk feature, please refer to the
following configuration methods.
Enable Bell Squawk
EKB2
EKB3/
EKB3W
Config
Tool
Disable Bell Squawk
MANUAL ELDES ESIM364 V1.0
EKB2
Menu path:
OKĺ CONFIGURATIONĺ OKĺ aaaaĺ OKĺ PRIMARY SETT INGSĺ OKĺ SIREN SETTINGS
ĺ OKĺ BELL SQUAWKĺ OKĺ ENABLEĺ OK
Value: aaaa – 4-digit administrator password.
Enter parameter 29 & parameter status value:
29 1 #
Example: 291#
This operation may be carried out from the PC using the ELDES Configuration Tool software.
Menu path:
OKĺ CONFIGURATIONĺ OKĺ aaaaĺ OKĺ PRIMARY SETT INGSĺ OKĺ SIREN SETTINGS
ĺ OKĺ BELL SQUAWKĺ OKĺ DISABLEĺ OK
Value: aaaa – 4-digit administrator password.
EN
71
EKB3/
EKB3W
Config
Tool
Enter parameter 29 & parameter statusvalue:
29 0 #
Example: 290#
This operation may be carried out from the PC using the ELDES Configuration Tool software.
20.3. Indication by EWS2 Indicators
When enabled, the built-in LED indicators of EWS2 wireless outdoor siren will flash during the alarm. To enable/disable this feature, please
refer to the following configuration methods.
Enable EWS2 LED
indication
EKB2
EKB3/
EKB3W
Config
Tool
Disable EWS2 LED
indication
EKB2
EKB3/
EKB3W
Config
Tool
72
EN
Menu path:
OKĺ CONFIGURATIONĺ OKĺ aaaaĺ OKĺ PRIMARY SETT INGSĺ OKĺ SIREN SETTINGS
ĺ OKĺ EWS2 LEDĺ OKĺ ENABLEĺ OK
Value: aaaa – 4-digit administrator password.
Enter parameter 29 & parameter status value:
88 1 #
Example: 881#
This operation may be carried out from the PC using the ELDES Configuration Tool software.
Menu path:
OKĺ CONFIGURATIONĺ OKĺ aaaaĺ OKĺ PRIMARY SETT INGSĺ OKĺ SIREN SETTINGS
ĺ OKĺ EWS2 LEDĺ OKĺ DISABLEĺ OK
Value: aaaa – 4-digit administrator password.
Enter parameter 29 & parameter status value:
88 0 #
Example: 880#
This operation may be carried out from the PC using the ELDES Configuration Tool software.
MANUAL ELDES ESIM364 V1.0
21. BACKUP BATTERY, MAINS POWER SUPPLY STATUS MONITORING AND MEMORY
The system may come equipped with a backup battery maintaining power supply of the system when the mains power supply is temporally
lost. The implemented feature allows the system to perform a self-test on the backup battery and notify User 1 by SMS text message as
well as to indicate system fault by the keypad (see 29. INDICATION OF SYSTEM FAULTS) if:
t
battery has failed and requires replacement – battery resistance is 2Ω or higher; self-tested every 24 hours.
t
battery is dead or missing – battery is not present or battery voltage is below 5V; self-tested every second.
t
battery power is running low – battery voltage is 10.5V or lower; self-tested every second.
By default, all notifications regarding the backup battery status are enabled. To disable/enable a determined backup battery notification,
please refer to the following configuration methods.
Disable Battery Failed
notification
EKB2
EKB3/
EKB3W
Config
Tool
Enable Battery Failed
notification
EKB2
EKB3/
EKB3W
Config
Tool
Disable Battery Dead
or Missing notification
EKB2
EKB3/
EKB3W
Config
Tool
Enable Battery Dead
or Missing notification
MANUAL ELDES ESIM364 V1.0
EKB2
Menu path:
OK ĺ CONFIGURATION ĺ OK ĺ aaaa ĺ OK ĺ SMS MESSAGES 1 ĺ OK ĺ BATTERY FAILED
ĺ OK ĺ DISABLE ĺ OK
Value: aaaa – 4-digit administrator password.
Enter parameter 25, notification number & parameter statusvalue:
25 05 0 #
Example: 25050#
This operation may be carried out from the PC using the ELDES Configuration Tool software.
Menu path:
OK ĺ CONFIGURATION ĺ OK ĺ aaaa ĺ OK ĺ SMS MESSAGES 1 ĺ OK ĺ BATTERY FAILED ĺ
OK ĺ ENABLE ĺ OK
Value: aaaa – 4-digit administrator password.
Enter parameter 25, notification number & parameter status value:
25 05 1 #
Example: 25051#
This operation may be carried out from the PC using the ELDES Configuration Tool software.
Menu path:
OK ĺ CONFIGURATION ĺ OK ĺ aaaa ĺ OK ĺ SMS MESSAGES 1 ĺ OK ĺ BATTERY DEAD/
MISS ĺ OK ĺ DISABLE ĺ OK
Value: aaaa – 4-digit administrator password.
Enter parameter 25, notification number & parameter status value:
25 06 0 #
Example: 25060#
This operation may be carried out from the PC using the ELDES Configuration Tool software.
OK ĺ CONFIGURATION ĺ OK ĺ aaaa ĺ OK ĺ SMS MESSAGES 1 ĺ OK ĺ BATTERY DEAD/
MISS ĺ OK ĺ ENABLE ĺ OK
Value: aaaa – 4-digit administrator password.
EN
73
EKB3/
EKB3W
Config
Tool
Disable Low Battery
notification
EKB2
EKB3/
EKB3W
Config
Tool
Enable Low Battery
notification
EKB2
EKB3/
EKB3W
Config
Tool
Enter parameter 25, notification number & parameter status value:
25 06 1 #
Example: 25061#
This operation may be carried out from the PC using the ELDES Configuration Tool software.
Menu path:
OKĺ CONFIGURATIONĺ OKĺ aaaaĺ OKĺ SMS MESSAGES 1ĺ OKĺ LOW BATTERY
EVENTĺ OKĺ DISABLEĺ OK
Value: aaaa – 4-digit administrator password.
Enter parameter 25, notification number & parameter status value:
25 07 0 #
Example: 25070#
This operation may be carried out from the PC using the ELDES Configuration Tool software.
Menu path:
OKĺ CONFIGURATIONĺ OKĺ aaaaĺ OKĺ SMS MESSAGES 1ĺ OKĺ LOW BATTERY
EVENTĺ OKĺ ENABLEĺ OK
Value: aaaa – 4-digit administrator password.
Enter parameter 25, notification number & parameter status value:
25 07 1 #
Example: 25071#
This operation may be carried out from the PC using the ELDES Configuration Tool software.
If the household electricity is unstable in the system installation area, the system may temporally lose its power supply and continue operating on the backup battery power. The system supervises the mains power supply and notifiies User 1 by SMS text message as well as
indicates system fault condition on the keypad (see 29. INDICATION OF SYSTEM FAULTS) when the mains power is lost. When the mains
power restores, the system will notify User 1 by SMS text message and the keypad will no longer indicate system fault.
By default, system notification by SMS text message regarding mains power supply status is enabled. To disable/enable this notification,
please refer to the following configuration methods.
Disable mains power
supply loss/restore
notification
EKB2
EKB3/
EKB3W
Config
Tool
74
EN
Menu path:
OKĺ CONFIGURATIONĺ OKĺ aaaaĺ OKĺ SMS MESSAGES 1ĺ OKĺ MAIN POWER L/R
EVĺ OKĺ DISABLEĺ OK
Value: aaaa – 4-digit administrator password.
Enter parameter 25, notification number & parameter status value:
25 04 0 #
Example: 25040#
This operation may be carried out from the PC using the ELDES Configuration Tool software.
MANUAL ELDES ESIM364 V1.0
Enable mains power
supply loss/restore
notification
EKB2
EKB3/
EKB3W
Config
Tool
Menu path:
OKĺ CONFIGURATIONĺ OKĺ aaaaĺ OKĺ SMS MESSAGES 1ĺ OKĺ MAIN POWER L/R
EVĺ OKĺ ENABLEĺ OK
Value: aaaa – 4-digit administrator password.
Enter parameter 25, notification number & parameter status value:
25 04 1 #
Example: 25041#
This operation may be carried out from the PC using the ELDES Configuration Tool software.
By default, mains power supply loss and restore delay are 30 and 120 seconds respectively. To set a different mains power supply loss and
restore delay duration, please refer to the following configuration methods.
Set mains power
supply loss delay
EKB2
EKB3W
Enter parameter 70 & loss delay duration:
70 lllll #
Value: lllll – mains power loss delay duration, range - [0... 65535] seconds.
Example: 7043#
Config
Tool
This operation may be carried out from the PC using the ELDES Configuration Tool software.
EKB3/
Set mains power
supply restore delay
Menu path:
OKĺ CONFIGURATIONĺ OKĺ aaaaĺ OKĺ PRIMARY SETT INGSĺ OKĺ MAIN POWER
STATUSĺ OKĺ LOSS DELAYĺ OKĺ lllllĺ OK
Value: aaaa – 4-digit administrator password; lllll – mains power loss delay duration, range
- [0... 65535] seconds.
EKB2
Menu path:
OKĺ CONFIGURATIONĺ OKĺ aaaaĺ OKĺ PRIMARY SETT INGSĺ OKĺ MAIN POWER
STATUSĺ OKĺ RESTORE DELAYĺ OKĺ rrrrrĺ OK
Value: aaaa – 4-digit administrator password; rrrrr – mains power restore delay duration,
range - [0... 65535] seconds.
EKB3W
Enter parameter 71 & restore delay duration:
71 rrrrr #
Value: rrrrr – mains power restore delay duration, range - [0... 65535] seconds.
Example: 71150#
Config
Tool
This operation may be carried out from the PC using the ELDES Configuration Tool software.
EKB3/
The configuration settings and event log records are stored in a built-in EEPROM memory, therefore even if the system is fully shut down,
the configuration and event log remain. For more details regarding the event log, please refer to 28. EVENT LOG
MANUAL ELDES ESIM364 V1.0
EN
75
22. GSM CONNECTION AND ANTENNA STATUS MONITORING
The system constantly supervises the GSM connection. When the GSM signal is lost, the system indicator NETW will light OFF, the keypad
will indicate system fault condition (see 29. INDICATION OF SYSTEM FAULTS) and the system will turn ON a determined PGM output if
the GSM signal is lost for a longer time period than the set delay value (By default – 180 seconds). Once the GSM signal restores, the system will notify User 1 by SMS text message, the keypad will no longer indicate system fault and the determined PGM output will turn OFF.
By default, the notifications by SMS text message regarding GSM signal loss is disabled. To enable/disable thus notification, please refer to
the following configuration methods.
Enable GSM
Connection Failed
notification
EKB2
EKB3/
EKB3W
Config
Tool
Disable GSM
Connection Failed
notification
EKB2
EKB3/
EKB3W
Config
Tool
Menu path:
OK ĺ CONFIGURATION ĺ OK ĺ aaaa ĺ OK ĺ SMS MESSAGES 2 ĺ OK ĺ GSM CONNECT
FAILED ĺ OK ĺ ENABLE ĺ OK
Value: aaaa – 4-digit administrator password.
Enter parameter 25, notification number & parameter status value:
25 11 1 #
Example: 25111#
This operation may be carried out from the PC using the ELDES Configuration Tool software.
Menu path:
OK ĺ CONFIGURATION ĺ OK ĺ aaaa ĺ OK ĺ SMS MESSAGES 2 ĺ OK ĺ GSM CONNECT
FAILED ĺ OK ĺ DISABLE ĺ OK
Value: aaaa – 4-digit administrator password.
Enter parameter 25, notification number & parameter status value:
25 11 0 #
Example: 25110#
This operation may be carried out from the PC using the ELDES Configuration Tool software.
By default, the PGM output for GSM signal loss indication is not set. To set the PGM output and delay duration for GSM signal loss indication,
please refer to the following configuration method.
Manage GSM signal
loss indication by PGM
output
76
EN
Config
Tool
This operation may be carried out from the PC using the ELDES Configuration Tool software.
MANUAL ELDES ESIM364 V1.0
The system constantly monitors the GSM antenna status. If the GSM antenna is disconnected/cut-off, the system will send notification by
SMS text message to User 1 and the keypad will indicate system fault condition (see 29. INDICATION OF SYSTEM FAULTS) . Once the
antenna is connected/fixed, the system will notify User 1 by SMS text message and the keypad will no longer indicate system fault.
By default, the notification by SMS text message regarding the GSM antenna status is disabled. To enable/disable this notification, please
refer to the following configuration methods.
Enable GSM Antenna
Fail/Restore
notification
EKB2
EKB3/
EKB3W
Config
Tool
Disable GSM
Antenna Fail/Restore
notification
EKB2
EKB3/
EKB3W
Config
Tool
MANUAL ELDES ESIM364 V1.0
Menu path:
OK ĺ CONFIGURATION ĺ OK ĺ aaaa ĺ OK ĺ SMS MESSAGES 2 ĺ OK ĺ GSM ANT FAIL/REST
ĺ OK ĺ ENABLE ĺ OK
Value: aaaa – 4-digit administrator password.
Enter parameter 25, notification number & parameter status value:
25 12 1 #
Example: 25121#
This operation may be carried out from the PC using the ELDES Configuration Tool software.
Menu path:
OK ĺ CONFIGURATION ĺ OK ĺ aaaa ĺ OK ĺ SMS MESSAGES 2 ĺ OK ĺ GSM ANT FAIL/REST
ĺ OK ĺ DISABLE ĺ OK
Value: aaaa – 4-digit administrator password.
Enter parameter 25, notification number & parameter status value:
25 12 0 #
Example: 25120#
This operation may be carried out from the PC using the ELDES Configuration Tool software.
EN
77
23. PARTITIONS
ESIM364 system comes equipped with a partitioning feature that can divide the alarm system into four independently controlled areas
identified as Partition 1 through 4, which are all supervised by one alarm system unit. Partitioning can be used in installations where shared
alarm system is more practical, such as a house and a garage or within a single multi-storey building. When partitioned, each system element, like zone, user phone number, keypad, user password, iButton key and EWK1 wireless keyfob can be assigned to single or multiple
partitions. The user will then be able to arm/disarm the system partition (-s) that the zones and arm/disarm method, except EKB2 keypad,
are assigned to.
The following table reflects the values used for system element assignment to partitions by EKB2/EKB3/EKB3W keypad. A sum of values is
used to assign the element to multiple partitions.
Partition
Partition 1
Partition 2
Partition 3
Partition 4
Value
1
2
4
8
Example1: The user wants to assign a certain iButton key to Partition 4 only. According to the table value 8
reflects Partition 4. He would then have to enter value 8.
Example2: The user wants to assign a certain user password to Partition 2 and 3. According to the table value 2
reflects Partition 2, while value 4 reflects Partition 3, therefore 2 + 4 = 6. He would then have to enter value 6.
Example3: The user wants to assign a certain zone to Partition 1, 3 and 4. According to the table value 1 reflects Partition 1, while values 4 and 8 reflect Partitions 3 and 4 respectively, therefore 1 + 4 + 8 = 13. He
would then have to enter value 13.
23.1. Zone Partition
Zone partition determines which system partition (-s) the zone will operate in.
Set zone partition
EKB2
Menu path:
On-board zone: OK ĺ CONFIGURATION ĺ OK ĺ aaaa ĺ OK ĺ ZONES ĺ OK ĺ ONBOARD
ZONES ĺ OK ĺ ZONE 1... 12 ĺ OK ĺ PARTITION ĺ OK ĺ pv ĺ OK
Wireless zone: OK ĺ CONFIGURATION ĺ OK ĺ aaaa ĺ OK ĺ ZONES ĺ OK ĺ WIRELESS
ZONES 1... 4 ĺ OK ĺ WIRELESS ZONE 13... 76 ĺ OK ĺ PARTITION ĺ OK ĺ pv ĺ OK
Keypad zone: OK ĺ CONFIGURATION ĺ OK ĺ aaaa ĺ OK ĺ ZONES ĺ OK ĺ KEYPAD
ZONES ĺ OK ĺ 1ST... 4TH KEYPAD ZONE ĺ OK ĺ PARTITION ĺ OK ĺ pv ĺ OK
EPGM1 zone: OK ĺ CONFIGURATION ĺ OK ĺ aaaa ĺ OK ĺ ZONES ĺ OK ĺ EPGM1 ZONES
1... 2 ĺ OK ĺ EPGM1 ZONE 1... 32 ĺ OK ĺ PARTITION ĺ OK ĺ pv ĺ OK
Value: aaaa – 4-digit administrator password; pv – partition value (see 23. PARTITIONS).
EKB3W
Enter parameter 57, zone number & partition value:
57 nn pv #
Value: nn – zone number, range – [01... 76]; pv – partition value (see 23. PARTITIONS).
Example: 57032#
Config
Tool
This operation may be carried out from the PC using the ELDES Configuration Tool software.
EKB3/
23.2. User Phone Number Partition
User phone number partition determines which system partition (-s) can be armed/disarmed from a certain user phone number by dialing
system’s phone number or sending an SMS text message.
Set user phone
number partition
EKB2
EKB3/
EKB3W
Config
Tool
78
EN
Menu path:
OK ĺ CONFIGURATION ĺ OK ĺ aaaa ĺ OK ĺ PRIMARY SETTINGS ĺ OK ĺ CALL/SMS
SETTINGS ĺ OK ĺ USERS ĺ OK ĺ USER 1... 5 ĺ OK ĺ PARTITION ĺ pv ĺ OK
Value: aaaa – 4-digit administrator password; pv – partition value (see 23. PARTITIONS).
Enter parameter 59, user phone number slot & partition value:
59 us pv #
Value: us – user phone number slot, range – [01... 10]; pv – partition value (see 23. PARTITIONS).
Example: 591013#
This operation may be carried out from the PC using the ELDES Configuration Tool software.
MANUAL ELDES ESIM364 V1.0
23.3. Keypad Partition and Keypad Partition Switch
Keypad partition determines which system partition the keypad will operate in. To identify which partition the keypad is operating in:
t
EKB2 – Refer to partition name (by default – PART1) indicated in home screen view.
t
EKB3/EKB3W – Refer to the location of the illuminated indicator READY on the keypad. The indicator will be illuminated under section
A or B, which represent Partition 1 and Partition 2 respectively.
The keypad must be assigned to the same partition as the user password (see 23.4. User Password Partition) in order to arm/disarm
the system by the keypad. For more details on system arming/disarming by the keypad, please refer to 12.3. EKB2 Keypad and User
Password and 12.4. EKB3/EKB3W Keypad and User Password.
Set keypad partition
EKB2
EKB3/
EKB3W
Config
Tool
Menu path:
EKB2 partition: OK ĺ CONFIGURATION ĺ OK ĺ aaaa ĺ OK ĺ PRIMARY SETTINGS ĺ OK ĺ
KEYPAD PARTITION ĺ OK ĺ KEYPAD PARTITION ĺ OK ĺ [k] EKB2 ĺ OK ĺ PARTITION 1... 4
ĺ OK
EKB3 partition: OK ĺ CONFIGURATION ĺ OK ĺ aaaa ĺ OK ĺ PRIMARY SETTINGS ĺ OK ĺ
KEYPAD PARTITION ĺ OK ĺ KEYPAD PARTITION ĺ OK ĺ [k] EKB3ĺ OK ĺ PARTITION 1... 2
ĺ OK
EKB3W partition: OK ĺ CONFIGURATION ĺ OK ĺ aaaa ĺ OK ĺ PRIMARY SETTINGS ĺ OK ĺ
KEYPAD PARTITION ĺ OK ĺ EKB3W PARTITION ĺ OK ĺ EKB3W wless-id ĺ OK ĺ PARTITION
1... 2 ĺ OK
Value: aaaa – 4-digit administrator password; k – keypad slot, range – [1... 4]; wless-id –
8-digit wireless device ID code.
Enter parameter 51, keypad slot & partition number:
EKB2 partition: 51 kk p #
EKB3 partition: 51 kk r #
EKB3W partition: 51 kw r #
Value: kk – EKB2/EKB3 keypad slot, range – [01... 04]; kw – EB3W keypad slot, range – [05...
08]; p – EKB2 partition number, range – [1... 4]; r – EKB3/EKB3W partition number, range
– [1... 2].
Example: 51062#
This operation may be carried out from the PC using the ELDES Configuration Tool software.
NOTE: The keypad can only be assigned to one partition.
NOTE: EKB3/EKB3W keypad assignment is restricted to Partition 1 and Partition 2.
NOTE: The slots for EKB3W keypads are automatically assigned to the bound keypad in the chronological order, hence the earliest bound
keypad would acquire slot 5, while the latest bound keypad would acquire slot 8.
Keypad partition switch allows to quickly change the keypad partition. When the keypad partition is changed and when 1 minute after the
last key-stroke/key-touch expires, the system will return to the preset keypad partition. Typically, this feature is used for viewing arm/
disarm status and alarms of a different partition or when arming/disarming a different system partition by EKB3/EKB3W keypad than the
keypad is assigned to.
By default, keypad partition switch is disabled. To enable/disable and use this feature, please refer to the following configuration methods.
Enable keypad
partition switch
EKB2
EKB3/
EKB3W
Config
Tool
MANUAL ELDES ESIM364 V1.0
Menu path:
OK ĺ CONFIGURATION ĺ OK ĺ aaaa ĺ OK ĺ PRIMARY SETTINGS ĺ OK ĺ KEYPAD
PARTITION ĺ OK ĺ PARTITION SWITCH ĺ OK ĺ ENABLE ĺ OK
Value: aaaa – 4-digit administrator password.
Enter parameter 77 & parameter status value:
77 1#
Example: 771#
This operation may be carried out from the PC using the ELDES Configuration Tool software.
EN
79
Use keypad
partition switch
EKB2
EKB3/
EKB3W
Disable keypad
partition switch
EKB2
EKB3/
EKB3W
Config
Tool
Menu path:
P1 ĺ [p] part-name ĺ OK
Value: part-name – up to 15 characters partition name.
Hold the [*] key, release it after 3 short beeps & enter partition number:
*p
Value: p – partition number, range – [1... 2]
Example: *2#
Menu path:
OK ĺ CONFIGURATION ĺ OK ĺ aaaa ĺ OK ĺ PRIMARY SETTINGS ĺ OK ĺ KEYPAD
PARTITION ĺ OK ĺ PARTITION SWITCH ĺ OK ĺ DISABLE ĺ OK
Value: aaaa – 4-digit administrator password.
Enter parameter 77 & parameter status value:
77 0 #
Example: 770#
This operation may be carried out from the PC using the ELDES Configuration Tool software.
NOTE: Keypad partition switch can only be used when the system is partitioned.
23.4. User Password Partition
User password partition determines which system partition (-s) can be armed/disarm using a certain user password. User password must
be assigned to the same partition as the keypad (see 23.3. Keypad Partition and Keypad Partition Switch) in order to arm/disarm the
system by EKB2/EKB3/EKB3W keypad . For more details on system arming/disarming by the keypad, please refer to 12.3. EKB2 Keypad
and User Password and 12.4. EKB3/EKB3W Keypad and User Password.
Set user password
partition
EKB2
EKB3W
Enter parameter 87, user password & partition value:
87 uuuu pv #
Value: uuuu – 4-digit user password; pv – partition value (see 23. PARTITIONS).
Example: 8711118#
Config
Tool
This operation may be carried out from the PC using the ELDES Configuration Tool software.
EKB3/
80
EN
Menu path:
User password 1... 16: OK ĺ CONFIGURATION ĺ OK ĺ aaaa ĺ OK ĺ PRIMARY SETTINGS
ĺ OK ĺ PASSWORDS ĺ OK ĺ USER PSW (1-16) ĺ OK ĺ USER PASSWORD 1... 16 ĺ OK ĺ
PARTITION ĺ OK ĺ pv ĺ OK
User password 17... 30: OK ĺ CONFIGURATION ĺ OK ĺ aaaa ĺ OK ĺ PRIMARY SETTINGS
ĺ OK ĺ PASSWORDS ĺ OK ĺ USER PSW (17-30) ĺ OK ĺ USER PASSWORD 17... 30 ĺ OK ĺ
PARTITION ĺ OK ĺ pv ĺ OK
Value: aaaa – 4-digit administrator password; pv – partition value (see 23. PARTITIONS).
MANUAL ELDES ESIM364 V1.0
23.5. iButton Key Partition
iButton key partition determines which system partition (-s) can be armed/disarmed using a certain key. iButton key must be assigned to
the partition (-s) that the user desires to arm. For more details on system arming/disarming by iButton key, please refer to 12.5. iButton
Key.
Set iButton key
partition
EKB2
Menu path:
OK ĺ CONFIGURATION ĺ OK ĺ aaaa ĺ OK ĺ IBUTTON KEYS ĺ OK ĺ IBUTTON 1... 5 ĺ OK
ĺ PARTITION ĺ OK ĺ pv ĺ OK
Value: aaaa – 4-digit administrator password; pv – partition value (see 23. PARTITIONS).
EKB3W
Enter parameter 60, iButton key slot & partition value:
60 ii pv #
Value: ii – iButton key slot, range – [01... 05]; pv – partition value (see 23. PARTITIONS).
Example: 600511#
Config
Tool
This operation may be carried out from the PC using the ELDES Configuration Tool software.
EKB3/
23.6. EWK1 Wireless Keyfob Partition
EWK1 wireless keyfob partition determines which system partition can be armed/disarmed using a certain EWK1 wireless keyfob. For more
details on system arming/disarming by EWK1 wireless keyfob, please refer to 12.6. EWK1 Wireless Keyfob.
Set EWK1 partition
Config
Tool
This operation may be carried out from the PC using the ELDES Configuration Tool software.
NOTE: EWK1 wireless keyfob can only be assigned to one partition.
MANUAL ELDES ESIM364 V1.0
EN
81
24. TEMPERATURE SENSORS
The system may be equipped with up to 8 temperature sensors intended for temperature measurement in the surrounding areas. This
feature allows to monitor the temperature of up to 8 different areas in real-time and receive a notification by SMS text message to User 1
phone number when the set temperature boundaries are exceeded.
24.1. Adding, Removing and Replacing Temperature Sensors
To add a temperature sensor to the system, do the following:
a) Shutdown the system.
b) Wire up the temperature sensor to the 1-Wire interface terminals (see 2.3.5. Temperature Sensor and iButton Key Reader for
temperature sensor wiring diagram).
c)
If more than one temperature sensor is required, wire another sensor in parallel to the previous one.
d) By default, the first added temperature sensor will be identified as primary and the second one – as secondary temperature sensor
(see 24.2. Primary and Secondary Temperature Sensors).
e) Add as many temperature sensors as necessary – wire up one after another in parallel – until the number of 8 sensors is reached.
f)
Power up the system.
To view the real-time temperature values measured by each temperature sensor, please refer to the following configuration methods.
View real-time
temperature values
of individual
temperature sensor
View real-time
temperature values
of all temperature
sensors
SMS
SMS text message content:
ssss_ITEMP:ts
Value: ssss – 4-digit SMS password; ts – temperature sensor slot, range - [1... 8].
Example: 1111_ITEMP:4
EKB2
Menu path:
OK ĺ TEMP SENSORS INFO ĺ OK ĺ 1. tm.p C (PRIM) | (SEC)... 8. tm.p C
Value: tm.p – real-time temperature value.
Config
Tool
This operation may be carried out from the PC using the ELDES Configuration Tool software.
SMS
SMS text message content:
ssss_ITEMP:?
Value: ssss – 4-digit SMS password.
Example: 1111_ITEMP:?
EKB2
Menu path:
OK ĺ TEMP SENSORS INFO ĺ OK ĺ 1. tm.p C (PRIM) | (SEC)... 8. tm.p C
Value: tm.p – real-time temperature value.
Config
Tool
This operation may be carried out from the PC using the ELDES Configuration Tool software.
If a temperature sensor is faulty, it is recommended to remove it or replace it by a functional sensor.
Remove/replace
individual
temperature sensor
Config
Tool
This operation may be carried out from the PC using the ELDES Configuration Tool software.
NOTE: When multiple temperature sensors are connected, please touch and hold the sensor with your fingers and watch the temperature
value change to identify the number of the temperature sensor slot.
82
EN
MANUAL ELDES ESIM364 V1.0
24.2. Primary and Secondary Temperature Sensors
By default, the first added temperature sensor is automatically set as primary, while the second one is set as secondary temperature sensor. The real-time temperature values of the primary and secondary temperature sensors are included in the Info SMS text message (see
26. SYSTEM INFORMATION. INFO SMS) as well as the temperature measured by the primary temperature sensor is indicated in the
home screen view of EKB2 keypad.
To set a different temperature sensor as primary or secondary, please refer to the following configuration methods.
Set primary
temperature sensor
SMS
SMS text message content:
ssss_TEMPI:PRIM:ts
Value: ssss – 4-digit SMS password; ts – temperature sensor slot, range - [1... 8].
Example: 1111_TEMPI:PRIM:4
EKB2
Menu path:
OK ĺ CONFIGURATION ĺ OK ĺ aaaa ĺ OK ĺ PRIMARY SETTINGS ĺ OK ĺ TEMP SENSORS
ĺ OK ĺPRIMARY TEMP SENS ĺ OK ĺ 1... 8 CONNECTED ĺ OK
Value: aaaa – 4-digit administrator password
EKB3W
Enter parameter 89 & temperature sensor slot:
89 ts #
Value: ts – temperature sensor slot, range - [01... 08].
Example: 8903#
Config
Tool
This operation may be carried out from the PC using the ELDES Configuration Tool software.
EKB3/
Set secondary
temperature sensor
SMS
SMS text message content:
ssss_TEMPI:SEC:ts
Value: ssss – 4-digit SMS password; ts – temperature sensor slot, range - [1... 8].
Example: 1111_TEMPI:SEC:3
EKB2
Menu path:
OK ĺ CONFIGURATION ĺ OK ĺ aaaa ĺ OK ĺ PRIMARY SETTINGS ĺ OK ĺ TEMP SENSORS
ĺ OK ĺ SECOND. TEMP SENS ĺ OK ĺ 1... 8 CONNECTED ĺ OK
Value: aaaa – 4-digit administrator password
EKB3W
Enter parameter 90 & temperature sensor slot:
90 ts #
Value: ts – temperature sensor slot, range - [01... 08].
Example: 9005#
Config
Tool
This operation may be carried out from the PC using the ELDES Configuration Tool software.
EKB3/
To view the slot number of primary and secondary temperature sensors, please refer to the following configuration methods.
View primary and
secondary temperature
sensor slot number
MANUAL ELDES ESIM364 V1.0
SMS
SMS text message content:
ssss_TEMPI:?
Value: ssss – 4-digit SMS password.
Example: 1111_TEMPI:?
EKB2
Menu path:
Primary: OK ĺ TEMP SENSORS INFO ĺ OK ĺ 1... 8 tm.p C (PRIM)
Secondary: OK ĺ TEMP SENSORS INFO ĺ OK ĺ 1... 8 tm.p C (SEC)
Value: tm.p – real-time temperature value.
Config
Tool
This operation may be carried out from the PC using the ELDES Configuration Tool software.
EN
83
View primary and
secondary temperature
sensor real-time
temperature values
SMS
EKB2
Config
Tool
SMS text message content:
ssss_INFO
Value: ssss – 4-digit SMS password.
Example: 1111_INFO
Menu path:
Primary: OK ĺ TEMP SENSORS INFO ĺ OK ĺ 1... 8 tm.p C (PRIM)
Secondary: OK ĺ TEMP SENSORS INFO ĺ OK ĺ 1... 8 tm.p C (SEC)
Value: tm.p – real-time temperature value.
This operation may be carried out from the PC using the ELDES Configuration Tool software.
NOTE: Primary and secondary temperature sensors can be set by a single SMS text message, Example: 1111_TEMPI:PRIM:4,SEC:3
24.3. Setting Up MIN and MAX Temperature Boundaries. Temperature Info SMS
The system supports an SMS text message identified as the Temperature Info SMS, which is automatically delivered to User 1 phone number if the preset minimum (MIN) or maximum (MAX) temperature boundary of any temperature sensor is exceeded.
To set the MIN and MAX temperature boundaries for a certain temperature sensor, please refer to the configuration methods.
Set MIN and MAX
temperature
boundaries
SMS
EKB2
EKB3/
EKB3W
Config
Tool
View MIN and
MAX temperature
boundaries
SMS
EKB2
84
EN
SMS text message content:
ssss_TEMPts:MIN:mnn,MAX:mxx
Value: ssss – 4-digit SMS password; ts - temperature sensor slot, range – [1... 8]; mnn – MIN
boundary, range – [-55... 125] C; mxx - MAX boundary, range – [-55... 125] C.
Example: 1111_TEMP2:MIN:-5,MAX:28
Menu path:
MIN: OK ĺ CONFIGURATION ĺ OK ĺ aaaa ĺ OK ĺ PRIMARY SETTINGS ĺ OK ĺ TEMP
SENSORS ĺ OK ĺ TEMPERATURE SENS 1... 8 ĺ OK ĺ TEMP. MIN ĺ OK ĺ mnn ĺ OK
MAX: OK ĺ CONFIGURATION ĺ OK ĺ aaaa ĺ OK ĺ PRIMARY SETTINGS ĺ OK ĺ TEMP
SENSORS ĺ OK ĺ TEMPERATURE SENS 1... 8 ĺ OK ĺ TEMP. MAX ĺ OK ĺ mxx ĺ OK
Value: aaaa – 4-digit administrator password; mnn – MIN boundary, range – [-55... 125] C;
mxx - MAX boundary, range – [-55... 125] C.
Keys P1 or P2 are used to enter minus character, e.g. -20.
Enter parameter 19 & temperature Value:
19 ts mnn mxx #
Value: ts - temperature sensor slot, range – [1... 8]; mnn – MIN boundary, range – [-55...
125] C; mxx - MAX boundary, range – [-55... 125] C. 00 value stands for minus character, e.
g. 0020 = -20
Example: 1906001530#
This operation may be carried out from the PC using the ELDES Configuration Tool software.
SMS text message content:
ssss_TEMPts
Value: ssss – 4-digit SMS password; ts - temperature sensor slot, range – [1... 8].
Example: 1111_TEMP4
Menu path:
MIN: OK ĺ CONFIGURATION ĺ OK ĺ aaaa ĺ OK ĺ PRIMARY SETTINGS ĺ OK ĺ TEMP
SENSORS ĺ OK ĺ TEMPERATURE SENS 1... 8 ĺ OK ĺ TEMP. MIN
MAX: OK ĺ CONFIGURATION ĺ OK ĺ aaaa ĺ OK ĺ PRIMARY SETTINGS ĺ OK ĺ TEMP
SENSORS ĺ OK ĺ TEMPERATURE SENS 1... 8 ĺ OK ĺ TEMP. MAX
Value: aaaa – 4-digit administrator password.
MANUAL ELDES ESIM364 V1.0
Config
Tool
This operation may be carried out from the PC using the ELDES Configuration Tool software.
NOTE: MIN and MAX boundaries can also be set separately by multiple SMS text messages, Example: 1111_TEMP1:MIN:6 and 1111_
TEMP1:MAX:40
24.4. Temperature Sensor Names
The temperature sensor name is included in the Temperature Info SMS when delivered to the User 1 phone number. This feature allows
easier identification of the temperature sensor and normally it is used when monitoring temperature changes in different areas.
Set temperature
sensor name
SMS
Config
Tool
View temperature
sensor name
SMS text message content:
ssss_TEMPts:NAME:temp-sens-name
Value: ssss – 4-digit SMS password; ts – temperature sensor slot, range – [1... 8]; tempsens-name – 4 to 24 characters temperature sensor name.
Example: 1111_TEMP3:NAME:Warehouse
This operation may be carried out from the PC using the ELDES Configuration Tool software.
SMS
SMS text message content:
ssss_TEMPts
Value: ssss – 4-digit SMS password; ts - temperature sensor slot, range – [1... 8].
Example: 1111_TEMP3
EKB2
Menu path:
OK ĺ CONFIGURATION ĺ OK ĺ aaaa ĺ OK ĺ PRIMARY SETTINGS ĺ OK ĺ TEMP SENSORS
ĺ OK ĺ TEMPERATURE SENS 1... 8 ĺ OK ĺ NAME
Value: aaaa – 4-digit administrator password.
Config
Tool
Delete temperature
sensor name
SMS
Config
Tool
MANUAL ELDES ESIM364 V1.0
This operation may be carried out from the PC using the ELDES Configuration Tool software.
SMS text message content:
ssss_TEMPts:NAME:
Value: ssss – 4-digit SMS password; ts - temperature sensor slot, range – [1... 8].
Example: 1111_TEMP2:NAME:
This operation may be carried out from the PC using the ELDES Configuration Tool software.
EN
85
25. REMOTE LISTENING AND 2-WAY VOICE COMMUNICATION
ESIM364 comes equipped with a microphone that allows the user to listen on his mobile phone to what is happening in the secured area.
By installing one of the audio modules EA1 or EA2, the user will be able to have a 2-way voice communication (see 32.3.2. EA1 – Audio
Output Module and 32.3.3. EA2 – Audio Output Module with Amplifier). Remote listening and 2-way voice communication can
operate under the following conditions:
t
The system makes a phone call to a preset user phone number in case of alarm and the user answers the call.
t
The user initiates remote listening by sending the SMS text message, the system makes a phone call to the user phone number that the
SMS text message was sent from and the user answers the call.
Initiate remote
listening
SMS
SMS text message content:
ssss_MIC
Value: ssss – 4-digit administrator password
Example: 1111_MIC
Set microphone gain
EKB2
Menu path:
OK ĺ CONFIGURATION ĺ OK ĺ aaaa ĺ OK ĺ PRIMARY SETT INGS ĺ OK ĺ GSM AUDIO ĺ OK
ĺ MICROPHONE GAIN ĺ OK ĺ mg ĺ OK
Value: aaaa – 4-digit administrator password; mg – microphone gain, range – [0... 15].
Config
Tool
This operation may be carried out from the PC using the ELDES Configuration Tool software.
EKB2
Menu path:
OK ĺ CONFIGURATION ĺ OK ĺ aaaa ĺ OK ĺ PRIMARY SETT INGS ĺ OK ĺ GSM AUDIO ĺ OK
ĺ SPEAKER LEVEL ĺ OK ĺ sl ĺ OK
Value: aaaa – 4-digit administrator password; sl – speaker level, range – [0... 85].
Config
Tool
This operation may be carried out from the PC using the ELDES Configuration Tool software.
Set speaker level
ATTENTION: Remote listening and 2-way voice communication features are disabled by force when the system is connected to the
monitoring station.
86
EN
MANUAL ELDES ESIM364 V1.0
26. SYSTEM INFORMATION. INFO SMS
The system supports an informational SMS text message identified as the Info SMS, which can be delivered upon request. Once requested,
the system will reply with Info SMS that provides the following:
t
System date & time.
t
System status: partition armed (ON)/disarmed (OFF).
t
GSM signal strength.
t
Mains power supply status.
t
Temperature of the area surrounding primary and secondary temperature sensors (if any).
t
State of zones (OK/alarm).
t
Name and status (ON/OFF) of PGM outputs.
Request for system
information
SMS
Config
Tool
SMS text message content:
ssss_INFO
Value: ssss – 4-digit SMS password.
Example: 1111_INFO
This operation may be carried out from the PC using the ELDES Configuration Tool software.
26.1. Periodic Info SMS
By default, the system sends Info SMS to User 1 phone number periodically once a day at 11:00 (frequency – 1 day; time – 11). The minimum period is every 1 hour (frequency – 0 days; time – 1). Typically, this feature is used to verify the power supply and online status of the
system.
To set a different frequency and time or disable periodic Info SMS, please refer to the following configuration methods.
Set periodic Info SMS
frequency and time
SMS
EKB2
EKB3/
EKB3W
Config
Tool
Disable periodic Info
SMS
SMS
EKB2
MANUAL ELDES ESIM364 V1.0
SMS text message content:
ssss_INFO:fff:it
Value: ssss – 4-digit SMS password; fff – frequency, range – [00... 99] days; it – time, range
– [01... 23].
Example: 1111_INFO:3.15
Menu path:
Frequency: OK ĺ CONFIGURATION ĺ OK ĺ aaaa ĺ PRIMARY SETTINGS ĺ OK ĺ INFO SMS
SCHEDULER ĺ OK ĺ FREQUENCY (DAYS) ĺ fff ĺ OK
Time: OK ĺ CONFIGURATION ĺ OK ĺ aaaa ĺ PRIMARY SETTINGS ĺ OK ĺ INFO SMS
SCHEDULER ĺ OK ĺ TIME ĺ it ĺ OK
Value: aaaa – 4-digit administrator password; fff – frequency, range – [00... 125] days; it –
time, range – [01... 23].
Enter parameter 11, time & frequency:
11it fff #
Value: it – time, range – [01... 23]; fff – frequency, range – [00... 125] days.
Example: 110412#
This operation may be carried out from the PC using the ELDES Configuration Tool software.
SMS text message content:
ssss_INFO:00:00
Example: 1111_INFO:00.00
Menu path:
Frequency: OK ĺ CONFIGURATION ĺ OK ĺ aaaa ĺ PRIMARY SETTINGS ĺ OK ĺ INFO SMS
SCHEDULER ĺ OK ĺ FREQUENCY (DAYS) ĺ 0 ĺ OK
Time: OK ĺ CONFIGURATION ĺ OK ĺ aaaa ĺ PRIMARY SETTINGS ĺ OK ĺ INFO SMS
SCHEDULER ĺ OK ĺ TIME ĺ 0 ĺ OK
Value: aaaa – 4-digit administrator password.
EN
87
EKB3/
EKB3W
Config
Tool
Enter parameter 11, time & frequency:
11 00 00 #
Example: 110000#
This operation may be carried out from the PC using the ELDES Configuration Tool software.
ATTENTION: Unlike Info SMS upon request, periodic Info SMS text message does not included zone states, PGM output names and status.
88
EN
MANUAL ELDES ESIM364 V1.0
27. SYSTEM NOTIFICATIONS
In case of a certain event, the system attempts to send an SMS text message to the first preset user phone number only. If the user phone
number is unavailable and the system fails to receive the SMS delivery report during 20 seconds, it will attempt to send the SMS text message to the next preset user phone number, assigned to the same partition as the previous one. The user phone number may be unavailable
due to the following reasons:
t
mobile phone was switched off.
t
was out of GSM signal coverage.
The system will continue sending the SMS text message to the next preset user phone numbers in the priority order until one is available.
The system sends the SMS text message only once and will not return to the first user phone number if the last one was unavailable.
When using Dual-SIM feature, the Secondary SIM card is involved in the communication process. For more details, please refer to 31. DUAL
SIM MANAGEMENT.
The following table provides the description of system notifications by SMS text message sent to the user phone number.
Seq. No.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
Event
System armed
System disarmed
General alarm
Mains power loss/
restore
Battery failed
Battery dead
or missing
Low battery
Siren fail/restore
Date/time not set
GSM connection failed
GSM antenna
fail/restore
Tamper alarm
Keypad failed
Temperature info
System started
Periodical info
Wireless signal loss
Description
SMS text message sent to the user regarding armed system.
SMS text message sent to the user about disarmed system.
SMS text message sent to the user in case of system alarm occurrence.
SMS text message sent to the user in case the mains power supply is lost or restored
SMS text message sent to the user in case the backup battery resistance is 2Ω or higher
(battery requires replacement).
SMS text message sent to the user in case the backup battery is not present or the battery voltage
runs below 5V.
SMS text message sent to the user in case the backup battery voltage is 10.5V or lower.
SMS text message sent to the user in case the siren is disconnected/broken or connected/fixed.
SMS text message sent to the user in case system date & time is not set.
SMS text message sent to the user in case the GSM connection is lost.
SMS text message sent to the user in case the GSM antenna is disconnected/broken or
connected/broken.
SMS text message sent to the user in case of tamper violation. Indicated as Tamper x.
SMS text message sent to the user in case the keypad is disconnected/broken.
SMS text message sent to the user in case of temperature deviation by the set values.
SMS text message sent to the user on system startup.
Info SMS text message sent to the user periodically by the set values.
SMS text message sent to the user in case the wireless signal is lost. Indicated as Tamper x *.
ATTENTION: The following methods provide the configuration of the master parameters, which override the notification parameters
described in 12.9. Disabling and Enabling Arm/Disarm Notifications.
MANUAL ELDES ESIM364 V1.0
EN
89
To enable/disable a certain system notification, please refer to the following configuration methods.
Disable system
notification
EKB2
EKB3/
EKB3W
Config
Tool
90
EN
Menu path:
System armed: OK ĺ CONFIGURATION ĺ OK ĺ aaaa ĺ OK ĺ SMS MESSAGES 1 ĺ OK ĺ SYS
ARMED EVENT ĺ OK ĺ DISABLE ĺ OKK
System disarmed: OK ĺ CONFIGURATION ĺ OK ĺ aaaa ĺ OK ĺ SMS MESSAGES 1 ĺ OK ĺ
SYS DISARMED EVENT ĺ OK ĺ DISABLE ĺ OK
General alarm: OK ĺ CONFIGURATION ĺ OK ĺ aaaa ĺ OK ĺ SMS MESSAGES 1 ĺ OK ĺ
GENERAL ALARM EV ĺ OK ĺ DISABLE ĺ OK
Mains power loss/restore: OK ĺ CONFIGURATION ĺ OK ĺ aaaa ĺ OK ĺ SMS MESSAGES 1 ĺ
OK ĺ MAIN POWER L/R EV ĺ OK ĺ DISABLE ĺ OK
Battery failed: OK ĺ CONFIGURATION ĺ OK ĺ aaaa ĺ OK ĺ SMS MESSAGES 1 ĺ OK ĺ
BATTERY FAILED ĺ OK ĺ DISABLE ĺ OK
Battery dead or missing: OK ĺ CONFIGURATION ĺ OK ĺ aaaa ĺ OK ĺ SMS MESSAGES 1 ĺ
OK ĺ LOW BATTERY EVENT ĺ OK ĺ DISABLE ĺ OK
Low battery: OK ĺ CONFIGURATION ĺ OK ĺ aaaa ĺ OK ĺ SMS MESSAGES 1 ĺ OK ĺ LOW
BATTERY EVENT ĺ OK ĺ DISABLE ĺ OK
Siren fail/restore: OK ĺ CONFIGURATION ĺ OK ĺ aaaa ĺ OK ĺ SMS MESSAGES 1 ĺ OK ĺ
SIREN FAIL/REST EV ĺ OK ĺ DISABLE ĺ OK
Date/time not set: OK ĺ CONFIGURATION ĺ OK ĺ aaaa ĺ OK ĺ SMS MESSAGES 2 ĺ OK ĺ
DATE/TIME NOT SET ĺ OK ĺ DISABLE ĺ OK
GSM connection failed: OK ĺ CONFIGURATION ĺ OK ĺ aaaa ĺ OK ĺ SMS MESSAGES 2 ĺ OK
ĺ GSM CONNECT FAILED ĺ OK ĺ DISABLE ĺ OK
GSM antenna fail/restore: OK ĺ CONFIGURATION ĺ OK ĺ aaaa ĺ OK ĺ SMS MESSAGES 2 ĺ
OK ĺ GSM ANT FAIL/REST ĺ OK ĺ DISABLE ĺ OK
Tamper alarm: OK ĺ CONFIGURATION ĺ OK ĺ aaaa ĺ OK ĺ SMS MESSAGES 2 ĺ OK ĺ
TAMPER ALARM ĺ OK ĺ DISABLE ĺ OK
Keypad failed: OK ĺ CONFIGURATION ĺ OK ĺ aaaa ĺ OK ĺ SMS MESSAGES 2 ĺ OK ĺ
KEYPAD FAILED ĺ OK ĺ DISABLE ĺ OK
Temperature info: OK ĺ CONFIGURATION ĺ OK ĺ aaaa ĺ OK ĺ SMS MESSAGES 2 ĺ OK ĺ
TEMP INFO EVENT ĺ OK ĺ DISABLE ĺ OK
System started: OK ĺ CONFIGURATION ĺ OK ĺ aaaa ĺ OK ĺ SMS MESSAGES 2 ĺ OK ĺ
SYSTEM STARTED EV ĺ OK ĺ DISABLE ĺ OK
Periodical info: OK ĺ CONFIGURATION ĺ OK ĺ aaaa ĺ OK ĺ SMS MESSAGES 2 ĺ OK ĺ
PERIOD INFO SMS EV ĺ OK ĺ DISABLE ĺ OK
Wireless signal loss: OK ĺ CONFIGURATION ĺ OK ĺ aaaa ĺ OK ĺ SMS MESSAGES 2 ĺ OK ĺ
WLESS SIGN LOSS EV ĺ OK ĺ DISABLE ĺ OK
Value: aaaa – 4-digit administrator password.
Enter parameter 25, event number & parameter status value:
25 01 0 # - System armed event
25 02 0 # - System disarmed event
25 03 0 # - General alarm
25 04 0 # - Main power loss/restore
25 05 0 # - Battery failed
25 06 0 # - Battery dead or missing
25 07 0 # - Low battery
25 08 0 # - Siren fail/restore
25 10 0 # - Date/time not set
25 11 0 # - GSM connection failed
25 12 0 # - GSM antenna fail/restore
25 13 0 # - Tamper alarm
25 14 0 # - Keypad failed
25 15 0 # - Temperature info
25 16 0 # - System started
25 17 0 # - Periodical info
25 18 0 # - Wireless signal loss
Example: 25040#
This operation may be carried out from the PC using the ELDES Configuration Tool software.
MANUAL ELDES ESIM364 V1.0
Enable system
notification
EKB2
EKB3/
EKB3W
Config
Tool
MANUAL ELDES ESIM364 V1.0
Menu path:
System armed: OK ĺ CONFIGURATION ĺ OK ĺ aaaa ĺ OK ĺ SMS MESSAGES 1 ĺ OK ĺ SYS
ARMED EVENT ĺ OK ĺ ENABLE ĺ OK
System disarmed: OK ĺ CONFIGURATION ĺ OK ĺ aaaa ĺ OK ĺ SMS MESSAGES 1 ĺ OK ĺ
SYS DISARMED EVENT ĺ OK ĺ ENABLE ĺ OK
General alarm: OK ĺ CONFIGURATION ĺ OK ĺ aaaa ĺ OK ĺ SMS MESSAGES 1 ĺ OK ĺ
GENERAL ALARM EV ĺ OK ĺ ENABLE ĺ OK
Mains power loss/restore: OK ĺ CONFIGURATION ĺ OK ĺ aaaa ĺ OK ĺ SMS MESSAGES 1 ĺ
OK ĺ MAIN POWER L/R EV ĺ OK ĺ ENABLE ĺ OK
Battery failed: OK ĺ CONFIGURATION ĺ OK ĺ aaaa ĺ OK ĺ SMS MESSAGES 1 ĺ OK ĺ
BATTERY FAILED ĺ OK ĺ ENABLE ĺ OK
Battery dead or missing: OK ĺ CONFIGURATION ĺ OK ĺ aaaa ĺ OK ĺ SMS MESSAGES 1 ĺ
OK ĺ BATTERY DEAD/MISS ĺ OK ĺ ENABLE ĺ OK
Low battery: OK ĺ CONFIGURATION ĺ OK ĺ aaaa ĺ OK ĺ SMS MESSAGES 1 ĺ OK ĺ LOW
BATTERY EVENT ĺ OK ĺ ENABLE ĺ OK
Siren fail/restore: OK ĺ CONFIGURATION ĺ OK ĺ aaaa ĺ OK ĺ SMS MESSAGES 1 ĺ OK ĺ
SIREN FAIL/REST EV ĺ OK ĺ ENABLE ĺ OK
Date/time not set: OK ĺ CONFIGURATION ĺ OK ĺ aaaa ĺ OK ĺ SMS MESSAGES 2 ĺ OK ĺ
DATE/TIME NOT SET ĺ OK ĺ ENABLE ĺ OK
GSM connection failed: OK ĺ CONFIGURATION ĺ OK ĺ aaaa ĺ OK ĺ SMS MESSAGES 2 ĺ OK
ĺ GSM CONNECT FAILED ĺ OK ĺ ENABLE ĺ OK
GSM antenna fail/restore: OK ĺ CONFIGURATION ĺ OK ĺ aaaa ĺ OK ĺ SMS MESSAGES 2 ĺ
OK ĺ GSM ANT FAIL/REST ĺ OK ĺ ENABLE ĺ OK
Tamper alarm: OK ĺ CONFIGURATION ĺ OK ĺ aaaa ĺ OK ĺ SMS MESSAGES 2 ĺ OK ĺ
TAMPER ALARM ĺ OK ĺ ENABLE ĺ OK
Keypad failed: OK ĺ CONFIGURATION ĺ OK ĺ aaaa ĺ OK ĺ SMS MESSAGES 2 ĺ OK ĺ
KEYPAD FAILED ĺ OK ĺ ENABLE ĺ OK
Temperature info: OK ĺ CONFIGURATION ĺ OK ĺ aaaa ĺ OK ĺ SMS MESSAGES 2 ĺ OK ĺ
TEMP INFO EVENT ĺ OK ĺ ENABLE ĺ OK
System started: OK ĺ CONFIGURATION ĺ OK ĺ aaaa ĺ OK ĺ SMS MESSAGES 2 ĺ OK ĺ
SYSTEM STARTED EV ĺ OK ĺ ENABLE ĺ OK
Periodical info: OK ĺ CONFIGURATION ĺ OK ĺ aaaa ĺ OK ĺ SMS MESSAGES 2 ĺ OK ĺ
PERIOD INFO SMS EV ĺ OK ĺ ENABLE ĺ OK
Wireless signal loss: OK ĺ CONFIGURATION ĺ OK ĺ aaaa ĺ OK ĺ SMS MESSAGES 2 ĺ OK ĺ
WLESS SIGN LOSS EV ĺ OK ĺ ENABLE ĺ OK
Value: aaaa – 4-digit administrator password.
Enter parameter 25, event number & parameter status value:
25 01 1 # - System armed event
25 02 1 # - System disarmed event
25 03 1 # - General alarm
25 04 1 # - Main power loss/restore
25 05 1 # - Battery failed
25 06 1 # - Battery dead or missing
25 07 1 # - Low battery
25 08 1 # - Siren fail/restore
25 10 1 # - Date/time not set
25 11 1 # - GSM connection failed
25 12 1 # - GSM antenna fail/restore
25 13 1 # - Tamper alarm
25 14 1 # - Keypad failed
25 15 1 # - Temperature info
25 16 1 # - System started
25 17 1 # - Periodical info
25 18 1 # - Wireless signal loss
Example: 25061#
This operation may be carried out from the PC using the ELDES Configuration Tool software.
EN
91
27.1. SMSC (Short Message Service Center) Phone Number
An SMS center (SMSC) is a GSM network element, which routes SMS text messages to the destination user and stores the SMS text message
if the recipient is unavailable. Typically, the phone number of the SMS center is already stored in the SIM card provided by the GSM operator.
If the user fails to receive replies from the system, the SMS center phone number, provided by the GSM operator, must be set manually.
Set SMSC phone
number
SMS
SMS text message content:
ssss_SMS_+ttteeellnnuumm – up to 15 digits monitoring station phone number.
Value: ssss – 4-digit SMS password; ttteeellnnuumm – up to 15 digits SMSC phone number.
Example: 1111_SMS_+4417031111111
ATTENTION: Before setting the SMSC phone number, please check the credit balance of the system’s SIM card. The system will fail to reply
if the credit balance is insufficient.
92
EN
MANUAL ELDES ESIM364 V1.0
28. EVENT LOG
This feature allows to chronologically register up to 500 timestamped records regarding the following system events:
t
System start.
t
System arming/disarming.
t
Zone violated/restored.
t
Tamper violated/restored.
t
Zone bypassing.
t
Wireless device management.
t
Temperature deviation by MIN and MAX boundaries.
t
System faults.
The event log is of LIFO (last in, first out) type that allows the system to automatically delete the oldest records and add the the latest ones
instead.
To export the event log to .log file or clear it, please refer to the following configuration methods.
Export/clear event log
Config
Tool
This operation may be carried out from the PC using the ELDES Configuration Tool software.
By default, event log is enabled. To disable/enable this feature, please refer to the following configuration methods.
Disable event log
EKB2
EKB3/
EKB3W
Enable event log
Enter parameter 36 and parameter status value:
36 0 #
Example: 360#
Config
Tool
This operation may be carried out from the PC using the ELDES Configuration Tool software.
EKB2
Menu path:
OK ĺ CONFIGURATION ĺ OK ĺ aaaa ĺ OK ĺ PRIMARY SETTINGS ĺ OK ĺ EVENT LOG ĺ OK
ĺ ENABLE ĺ OK
EKB3/
Enter parameter 36 and parameter status value:
36 1 #
EKB3W
Config
Tool
MANUAL ELDES ESIM364 V1.0
Menu path:
OK ĺ CONFIGURATION ĺ OK ĺ aaaa ĺ OK ĺ PRIMARY SETTINGS ĺ OK ĺ EVENT LOG ĺ OK
ĺ DISABLE ĺ OK
Example: 361#
This operation may be carried out from the PC using the ELDES Configuration Tool software.
EN
93
29. INDICATION OF SYSTEM FAULTS
Message FLT displayed in the home screen view indicates presence of system faults. In order to find out more on the particular
system problem, please open menu section FAULTS. The description on each system problem is indicated in the table below.
EKB2
Menu path:
OK ĺ FAULTS
Name
MAIN POWER LOSS
LOW BATTERY
BATTERY DEAD/MISS
BATTERY FAILED
SIREN FAILED
GSM JAMMER DETECT
VIOLATED TAMPER
DATE/TIME NOT SET
GSM CONNECT FAILED
GSM ANTENNA FAILED
WLESS SIGNAL LOST
94
EN
Description
Main power supply is lost
Backup battery voltage is 10.5V or lower
Backup battery is not present or the battery
voltage runs below 5V
Backup battery resistance is 2Ω or higher
Siren is disconnected/broken
GSM jamming is detected
One or more tampers are violated
Date/time not set
GSM connection is lost
GSM antenna is disconnected/broken
Wireless signal is lost
MANUAL ELDES ESIM364 V1.0
Yellow LED SYSTEM indicates system faults. SYSTEM LED indications are mentioned in the table below.
EKB3/
EKB3W
SYSTEM LED
Illuminated continously
Flashing
Description
One ore more zones or tampers are violated; other system faults
One or more high zones are violated
In order to find out more on the particular system fault, please enter command A. After this procedure the system will activate red
zone LEDs for 15 seconds. The description on each LED indication is mentioned in the table below.
Zone LED
Description
1
Main power supply is lost
2
Backup battery voltage is 10.5V or lower
3
Backup battery is not present or the battery voltage runs below 5V
4
Backup battery resistance is 2Ω or higher
5
Siren is disconnected/broken
6
GSM jamming is detected
7
One or more tampers are violated
8
Date/time not set
9
GSM connection is lost
10
One or more high-numbered zones (Z13 - Z76) are violated
11
GSM antenna is disconnected/broken
12
Wireless signal is lost
In order to find out which particular high-numbered zone is violated please , enter command B.
In order to find out which particular tamper is violated please , enter command C.
A. System trouble indication - enter command:
[CODE#]
B. Violated high zone indication – enter command:
[CODE1]
C. Violated tamper indication – enter command:
[CODE2]
The number of violated high-numbered zone or tamper can be calculated using the table below according to the formula: number
from zone LED section B + number from zone LED section A.
Example: LED #3 from section A is flashing and LED #8 from section B is illuminated continuously. According to the table below
LED #8 is equal to number 18, therefore 18 + 3 = 21.
Result: Violated high-numbered zone or tamper number is 21.
Zone LED section - A (flashing)
Zone LED 1 = 1
Zone LED 2 = 2
Zone LED 3 = 3
Zone LED 4 = 4
Zone LED 5 = 5
Zone LED 6 = 6
MANUAL ELDES ESIM364 V1.0
Zone LED section - B (illuminated continously)
Zone LED 7 = 12
Zone LED 8 = 18
Zone LED 9 = 24
Zone LED 10 = 30
Zone LED 11 = 36
Zone LED 12 = 42
EN
95
30. Monitoring Station
The system can be configured to report events to the monitoring station by transmitting data messages to the monitoring station. The
system connects to the monitoring station when the MS (Monitoring Station) mode is enabled.
Enable MS mode
SMS
SMS text message content:
ssss_SCNSET:ON
Value: ssss – 4-digit SMS password.
Example: 1111_SCNSET:ON
EKB2
Menu path:
OK ĺ CONFIGURATION ĺ OK ĺ aaaa ĺ OK ĺ MS SETTINGS ĺ OK ĺ MS MODE ĺ OK ĺ
ENABLE ĺ OK
Value: aaaa – 4-digit administrator password
EKB3/
EKB3W
Config
Tool
Disable MS mode
Enter parameter 23 & parameter status value:
23 1 #
Example: 231#
This operation may be carried out from the PC using the ELDES Configuration Tool software.
SMS
SMS text message content:
ssss_SCNSET:OFF
Value: ssss – 4-digit SMS password.
Example: 1111_SCNSET:OFF
EKB2
Menu path:
OK ĺ CONFIGURATION ĺ OK ĺ aaaa ĺ OK ĺ MS SETTINGS ĺ OK ĺ MS MODE ĺ OK ĺ
DISABLE ĺ OK
Value: aaaa – 4-digit administrator password
EKB3/
EKB3W
Config
Tool
Enter parameter 23 & parameter status value:
23 0 #
Example: 230#
This operation may be carried out from the PC using the ELDES Configuration Tool software.
Account is a 4-digit number (By default – 9999) required to identify the alarm system unit by the monitoring station.
Set account
EKB2
Menu path:
OK ĺ CONFIGURATION ĺ OK ĺ aaaa ĺ OK ĺ MS SETTINGS ĺ OK ĺ ACCOUNT ĺ OK ĺ cccc
ĺ OK
Value: aaaa – 4-digit administrator password; cccc – 4-digit account number.
EKB3/
Enter parameter 27 & account number:
27 cccc #
EKB3W
Config
Tool
Value: cccc – 4-digit account number.
Example: 278853#
This operation may be carried out from the PC using the ELDES Configuration Tool software.
ATTENTION: The system will NOT send any data to the monitoring station while remote configuration or remote firmware update is in progress. However, during the remote configuration session/firmware update process, the data messages will be queued up and transmitted to
the monitoring station after the remote configuration session/firmware update process is complete.
ATTENTION: Phone calls to the preset user phone number in case of alarm, remote listening and 2-way voice communication features are
disabled by force when MS mode is enabled.
96
EN
MANUAL ELDES ESIM364 V1.0
30.1. Data Messages – Events
The configuration of data messages is based on Ademco Contact ID protocol. The data messages can either be transmitted to the monitoring station alone or with duplication by SMS text message to preset user phone number. For more details on system notifications by SMS
text message, please refer to 27. SYSTEM NOTIFICATIONS.
Seq. No.
Contact ID® Code
Event
Description
1
1110
Fire alarm
Transmitted in case a zone of Fire type is violated.
2
3110
Fire restore
Transmitted in case a zone of Fire type is restored.
3
1121
Disarmed by user
(Duress password)
Transmitted in case the system is disarmed by Duress password.
4
1130
Burglary alarm
Transmitted in case a zone of Delay (if not disarmed before entry delay
countdown is completed), Follow or Instant type is violated.
5
3130
Burglary restore
Transmitted in case a zone of Delay (if not disarmed before entry delay
countdown is completed), Follow or Instant type is restored.
6
1133
24H zone alarm
Transmitted in case of zone of 24H type is violated.
7
3133
24H zone restore
Transmitted in case of zone of 24H type is restored.
8
1144
Tamper alarm
Transmitted in case the tamper is violated.
9
3144
Tamper restore
Transmitted in case the tamper is restored.
10
1146
Silent zone alarm
Transmitted in case of zone of Silent type is violated.
11
3146
Silent zone restore
Transmitted in case of zone of Silent type is restored.
12
1158
Temperature risen
Transmitted in case of temperature deviation by the MAX set value.
13
1159
Temperature fallen
Transmitted in case of temperature deviation by the MIN set value.
14
1301
Mains power loss
Transmitted in case the main power supply is lost.
15
3301
Mains power restore
Transmitted in case the main power supply is restored.
16
1302
Low battery
Transmitted in case the backup battery voltage is 10.5V or lower / the
wireless sensor battery level runs below 5%.
17
1308
System shutdown
When the system is running on backup battery power, it transmits the
data message before the backup battery power is fully depleted.
18
1309
Battery failed
Transmitted in case the backup battery resistance is 2Ω or higher.
19
1311
Battery dead or
missing
Transmitted in case the backup battery is not present or the battery
voltage runs below 5V.
20
1321
Siren fail
Transmitted in case the siren is disconnected/broken.
21
3321
Siren restore
Transmitted in case the siren is connected/fixed.
22
1330
Keypad fail
Transmitted in case the keypad is disconnected/broken.
23
3330
Keypad restore
Transmitted in case the keypad is connected/fixed
24
1354
GPRS connection loss
Transmitted in case the GPRS connection is lost.
25
1358
GSM connection
failed
Transmitted in case the GSM connection is lost.
26
1359
GSM antenna fail
Transmitted in case the GSM antenna is disconnected/broken
27
3359
GSM antenna restore
Transmitted in case the GSM antenna is connected/fixed.
28
1381
Wireless signal loss
Transmitted in case the connection with any wireless device is lost.
29
3381
Wireless signal
restore
Transmitted in case the connection with any wireless device is restored.
30
1401
Disarmed by user
Transmitted in case the system is disarmed.
31
3401
Armed by user
Transmitted in case the system is armed.
32
1456
Disarmed in Stay
mode
Transmitted in case the system is disarmed in Stay mode.
33
3456
Armed in Stay mode
Transmitted in case the system is armed in Stay mode.
34
1463
Disarmed by user
(SGS password)
Transmitted in case the system is disarmed by SGS password.
35
3463
Armed by user (SGS
password)
Transmitted in case the system is armed by SGS password.
36
1602
Test event/Kronos
ping
Transmitted for system online status verification purposes.
37
3626
Date/time not set
Transmitted in case system date & time is not set.
38
1900
System started
Transmitted on system startup.
MANUAL ELDES ESIM364 V1.0
EN
97
The following table refers to user codes included in arm/disarm data messages.
Type
User Phone Number 1
User Phone Number 2
User Phone Number 3
User Phone Number 4
User Phone Number 5
User Phone Number 6
User Phone Number 7
User Phone Number 8
User Phone Number 9
User Phone Number 10
iButton 1
iButton 2
iButton 3
iButton 4
iButton 5
Code
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
User Password 1
User Password 2
User Password 3
User Password 4
User Password 5
User Password 6
User Password 7
User Password 8
User Password 9
User Password 10
User Password 11
User Password 12
User Password 13
User Password 14
User Password 15
User Password 16
User Password 17
User Password 18
User Password 19
User Password 20
User Password 21
User Password 22
User Password 23
User Password 24
User Password 25
User Password 26
User Password 27
User Password 28
User Password 29
User Password 30
Remote Code (EGR100)
KeyFob 1
KeyFob 2
KeyFob 3
KeyFob 4
Arm/Disarm by Zone
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
122
123
124
125
198
98
EN
MANUAL ELDES ESIM364 V1.0
Disable data message
MANUAL ELDES ESIM364 V1.0
EKB2
Menu path:
Burglary alarm/restore: OK ĺ CONFIGURATION ĺ OK ĺ aaaa ĺ OK ĺ MS SETTINGS ĺ OK ĺ
DATA MESSAGES 1 ĺ OK ĺ BURGLR ALM/REST EV ĺ OK ĺ DISABLE ĺ OK
Mains power loss/restore: OK ĺ CONFIGURATION ĺ OK ĺ aaaa ĺ OK ĺ MS SETTINGS ĺ OK
ĺ DATA MESSAGES 1 ĺ OK ĺ MAIN POWER L/R EV ĺ OK ĺ DISABLE ĺ OK
Armed/disarmed by user: OK ĺ CONFIGURATION ĺ OK ĺ aaaa ĺ OK ĺ MS SETTINGS ĺ OK
ĺ DATA MESSAGES 1 ĺ OK ĺ ARM/DISARM EVENT ĺ OK ĺ DISABLE ĺ OK
Battery failed: OK ĺ CONFIGURATION ĺ OK ĺ aaaa ĺ OK ĺ MS SETTINGS ĺ OK ĺ DATA
MESSAGES 1 ĺ OK ĺ BATTERY FAILED ĺ OK ĺ DISABLE ĺ OK
Battery dead or missing: OK ĺ CONFIGURATION ĺ OK ĺ aaaa ĺ OK ĺ MS SETTINGS ĺ
OK ĺ DATA MESSAGES 1 ĺ OK ĺ BATTERY DEAD/MISS ĺ OK ĺ DISABLE ĺ OK
Test event: OK ĺ CONFIGURATION ĺ OK ĺ aaaa ĺ OK ĺ MS SETTINGS ĺ OK ĺ DATA
MESSAGES 1 ĺ OK ĺ TEST EVENT ĺ OK ĺ DISABLE ĺ OK
Tamper alarm/restore: OK ĺ CONFIGURATION ĺ OK ĺ aaaa ĺ OK ĺ MS SETTINGS ĺ OK ĺ
DATA MESSAGES 1 ĺ OK ĺ TAMPER ALM/REST EV ĺ OK ĺ DISABLE ĺ OK
Silent zone alarm/restore: OK ĺ CONFIGURATION ĺ OK ĺ aaaa ĺ OK ĺ MS SETTINGS ĺ OK
ĺ DATA MESSAGES 1 ĺ OK ĺ SILENT ALM/REST EV ĺ OK ĺ DISABLE ĺ OK
System started: OK ĺ CONFIGURATION ĺ OK ĺ aaaa ĺ OK ĺ MS SETTINGS ĺ OK ĺ DATA
MESSAGES 1 ĺ OK ĺ SYSTEM STARTED EV ĺ OK ĺ DISABLE ĺ OK
Fire alarm/restore: OK ĺ CONFIGURATION ĺ OK ĺ aaaa ĺ OK ĺ MS SETTINGS ĺ OK ĺ
DATA MESSAGES 1 ĺ OK ĺ FIRE ALM/REST EV ĺ OK ĺ DISABLE ĺ OK
24H zone alarm restore: OK ĺ CONFIGURATION ĺ OK ĺ aaaa ĺ OK ĺ MS SETTINGS ĺ OK ĺ
DATA MESSAGES 1 ĺ OK ĺ 24H ALM/REST EVENTĺ OK ĺ DISABLE ĺ OK
Low battery: OK ĺ CONFIGURATION ĺ OK ĺ aaaa ĺ OK ĺ MS SETTINGS ĺ OK ĺDATA
MESSAGES 1 ĺ OK ĺ LOW BATTE RY EVENT ĺ OK ĺ DISABLE ĺ OK
Temperature risen: OK ĺ CONFIGURATION ĺ OK ĺ aaaa ĺ OK ĺ MS SETTINGS ĺ OK ĺ
DATA MESSAGES 1 ĺ OK ĺ TEMP HIGH EVENT ĺ OK ĺ DISABLE ĺ OK
Temperature fallen: OK ĺ CONFIGURATION ĺ OK ĺ aaaa ĺ OK ĺ MS SETTINGS ĺ OK ĺ
DATA MESSAGES 1 ĺ OK ĺ TEMP LOW EVENT ĺ OK ĺ DISABLE ĺ OK
Wireless signal loss/restore: OK ĺ CONFIGURATION ĺ OK ĺ aaaa ĺ OK ĺ MS SETTINGS ĺ
OK ĺ DATA MESSAGES 1 ĺ OK ĺ WLESS SIGN L/R EV ĺ OK ĺ DISABLE ĺ OK
Disarmed by user (Duress password): OK ĺ CONFIGURATION ĺ OK ĺ aaaa ĺ OK ĺ MS
SETTINGS ĺ OK ĺ DATA MESSAGES 2 ĺ OK ĺ DISARM DURESS EV ĺ OK ĺ DISABLE ĺ OK
Armed/disarmed by user (SGS password): OK ĺ CONFIGURATION ĺ OK ĺ aaaa ĺ OK ĺ MS
SETTINGS ĺ OK ĺ DATA MESSAGES 2 ĺ OK ĺ ARM/DARM SGS EVENT ĺ OK ĺ DISABLE ĺ
OK
Armed/disarmed in Stay mode: OK ĺ CONFIGURATION ĺ OK ĺ aaaa ĺ OK ĺ MS SETTINGS
ĺ OK ĺ DATA MESSAGES 2 ĺ OK ĺ ARM/DARM STAY EV ĺ OK ĺ DISABLE ĺ OK
Siren fail/restore: OK ĺ CONFIGURATION ĺ OK ĺ aaaa ĺ OK ĺ MS SETTINGS ĺ OK ĺ DATA
MESSAGES 2 ĺ OK ĺ SIREN FAIL/REST EV ĺ OK ĺ DISABLE ĺ OK
Date/time not set: OK ĺ CONFIGURATION ĺ OK ĺ aaaa ĺ OK ĺ MS SETTINGS ĺ OK ĺ DATA
MESSAGES 2 ĺ OK ĺ DATE/TIME NOT SET ĺ OK ĺ DISABLE ĺ OK
GSM connection failed: OK ĺ CONFIGURATION ĺ OK ĺ aaaa ĺ OK ĺ MS SETTINGS ĺ OK ĺ
DATA MESSAGES 2 ĺ OK ĺ GSM CONNECT FAILED ĺ OK ĺ DISABLE ĺ OK
GSM antenna fail/restore: OK ĺ CONFIGURATION ĺ OK ĺ aaaa ĺ OK ĺ MS SETTINGS ĺ OK
ĺ DATA MESSAGES 2 ĺ OK ĺ GSM ANT FAIL/REST ĺ OK ĺ DISABLE ĺ OK
System shutdown: OK ĺ CONFIGURATION ĺ OK ĺ aaaa ĺ OK ĺ MS SETTINGS ĺ OK ĺ
DATA MESSAGES 2 ĺ OK ĺ SYSTEM SHUTDOWN EV ĺ OK ĺ DISABLE ĺ OK
Keypad fail/restore: OK ĺ CONFIGURATION ĺ OK ĺ aaaa ĺ OK ĺ MS SETTINGS ĺ OK ĺ
DATA MESSAGES 2 ĺ OK ĺ KEYPAD FAIL/REST ĺ OK ĺ DISABLE ĺ OK
GPRS connection failed: OK ĺ CONFIGURATION ĺ OK ĺ aaaa ĺ OK ĺ MS SETTINGS ĺ OK ĺ
DATA MESSAGES 2 ĺ OK ĺ GPRS CONNECT FAIL ĺ OK ĺ DISABLE ĺ OK
Value: aaaa – 4-digit administrator password.
EN
99
EKB3/
EKB3W
Config
Tool
100
EN
Enter parameter 24, event number & parameter status value:
24 01 0 # – Burglary alarm/restore
24 02 0 # – Mains power loss/restore
24 03 0 # – Armed/disarmed by user
24 04 0 # – Test event
24 05 0 # – Battery failed
24 06 0 # – Battery dead or missing
24 07 0 # – Tamper alarm/restore
24 08 0 # – Silent zone alarm/restore
24 09 0 # – Kronos ping
24 10 0 # – System started
24 13 0 # – 24H zone alarm/restore
24 14 0 # – Fire zone alarm/restore
24 15 0 # – Low battery
24 16 0 # –Temperature risen
24 17 0 # – Temperature fallen
24 18 0 # – Wireless signal loss/restore
24 19 0 # – Disarmed by user (Duress password)
24 20 0 # – Armed/disarmed by user (SGS password)
24 21 0 # – Armed/disarmed in Stay mode
24 22 0 # – Siren fail/restore
24 24 0 # –Date/time not set
24 25 0 # – GSM connection failed
24 26 0 # – GSM antenna fail/restore
24 27 0 # – System shutdown
24 28 0 # – Keypad fail/restore
24 29 0 # – GPRS connection failed
Example: 24080#
This operation may be carried out from the PC using the ELDES Configuration Tool software.
MANUAL ELDES ESIM364 V1.0
Enable data message
MANUAL ELDES ESIM364 V1.0
EKB2
Menu path:
Burglary alarm/restore: OK ĺ CONFIGURATION ĺ OK ĺ aaaa ĺ OK ĺ MS SETTINGS ĺ OK ĺ
DATA MESSAGES 1 ĺ OK ĺ BURGLR ALM/REST EV ĺ OK ĺ ENABLE ĺ OK
Mains power loss/restore: OK ĺ CONFIGURATION ĺ OK ĺ aaaa ĺ OK ĺ MS SETTINGS ĺ OK
ĺ DATA MESSAGES 1 ĺ OK ĺ MAIN POWER L/R EV ĺ OK ĺ ENABLE ĺ OK
Armed/disarmed by user: OK ĺ CONFIGURATION ĺ OK ĺ aaaa ĺ OK ĺ MS SETTINGS ĺ OK
ĺ DATA MESSAGES 1 ĺ OK ĺ ARM/DISARM EVENT ĺ OK ĺ ENABLE ĺ OK
Battery failed: OK ĺ CONFIGURATION ĺ OK ĺ aaaa ĺ OK ĺ MS SETTINGS ĺ OK ĺ DATA
MESSAGES 1 ĺ OK ĺ BATTERY FAILED ĺ OK ĺ ENABLE ĺ OK
Battery dead or missing: OK ĺ CONFIGURATION ĺ OK ĺ aaaa ĺ OK ĺ MS SETTINGS ĺ OK
ĺ DATA MESSAGES 1 ĺ OK ĺ BATTERY DEAD/MISS ĺ OK ĺ ENABLE ĺ OK
Test event: OK ĺ CONFIGURATION ĺ OK ĺ aaaa ĺ OK ĺ MS SETTINGS ĺ OK ĺ DATA
MESSAGES 1 ĺ OK ĺ TEST EVENT ĺ OK ĺ ENABLE ĺ OK
Tamper alarm/restore: OK ĺ CONFIGURATION ĺ OK ĺ aaaa ĺ OK ĺ MS SETTINGS ĺ OK ĺ
DATA MESSAGES 1 ĺ OK ĺ TAMPER ALM/REST EV ĺ OK ĺ ENABLE ĺ OK
Silent zone alarm/restore: OK ĺ CONFIGURATION ĺ OK ĺ aaaa ĺ OK ĺ MS SETTINGS ĺ OK
ĺ DATA MESSAGES 1 ĺ OK ĺ SILENT ALM/REST EV ĺ OK ĺ ENABLE ĺ OK
System started: OK ĺ CONFIGURATION ĺ OK ĺ aaaa ĺ OK ĺ MS SETTINGS ĺ OK ĺ DATA
MESSAGES 1 ĺ OK ĺ SYSTEM STARTED EV ĺ OK ĺ ENABLE ĺ OK
Fire alarm/restore: OK ĺ CONFIGURATION ĺ OK ĺ aaaa ĺ OK ĺ MS SETTINGS ĺ OK ĺ
DATA MESSAGES 1 ĺ OK ĺ FIRE ALM/REST EV ĺ OK ĺ ENABLE ĺ OK
24H zone alarm restore: OK ĺ CONFIGURATION ĺ OK ĺ aaaa ĺ OK ĺ MS SETTINGS ĺ OK ĺ
DATA MESSAGES 1 ĺ OK ĺ 24H ALM/REST EVENTĺ OK ĺ ENABLE ĺ OK
Low battery: OK ĺ CONFIGURATION ĺ OK ĺ aaaa ĺ OK ĺ MS SETTINGS ĺ OK ĺ DATA
MESSAGES 1 ĺ OK ĺ LOW BATTE RY EVENT ĺ OK ĺ ENABLE ĺ OK
Temperature risen: OK ĺ CONFIGURATION ĺ OK ĺ aaaa ĺ OK ĺ MS SETTINGS ĺ OK ĺ
DATA MESSAGES 1 ĺ OK ĺ TEMP HIGH EVENT ĺ OK ĺ ENABLE ĺ OK
Temperature fallen: OK ĺ CONFIGURATION ĺ OK ĺ aaaa ĺ OK ĺ MS SETTINGS ĺ OK ĺ
DATA MESSAGES 1 ĺ OK ĺ TEMP LOW EVENT ĺ OK ĺ ENABLE ĺ OK
Wireless signal loss/restore: OK ĺ CONFIGURATION ĺ OK ĺ aaaa ĺ OK ĺ MS SETTINGS ĺ
OK ĺ DATA MESSAGES 1 ĺ OK ĺ WLESS SIGN L/R EV ĺ OK ĺ ENABLE ĺ OK
Disarmed by user (Duress password): OK ĺ CONFIGURATION ĺ OK ĺ aaaa ĺ OK ĺ MS
SETTINGS ĺ OK ĺ DATA MESSAGES 2 ĺ OK ĺ DISARM DURESS EV ĺ OK ĺ ENABLE ĺ OK
Armed/disarmed by user (SGS password): OK ĺ CONFIGURATION ĺ OK ĺ aaaa ĺ OK ĺ MS
SETTINGS ĺ OK ĺ DATA MESSAGES 2 ĺ OK ĺ ARM/DARM SGS EVENT ĺ OK ĺ ENABLE ĺ OK
Armed/disarmed in Stay mode: OK ĺ CONFIGURATION ĺ OK ĺ aaaa ĺ OK ĺ MS SETTINGS
ĺ OK ĺ DATA MESSAGES 2 ĺ OK ĺ ARM/DARM STAY EV ĺ OK ĺ ENABLE ĺ OK
Siren fail/restore: OK ĺ CONFIGURATION ĺ OK ĺ aaaa ĺ OK ĺ MS SETTINGS ĺ OK ĺ DATA
MESSAGES 2 ĺ OK ĺ SIREN FAIL/REST EV ĺ OK ĺ ENABLE ĺ OK
Date/time not set: OK ĺ CONFIGURATION ĺ OK ĺ aaaa ĺ OK ĺ MS SETTINGS ĺ OK ĺ DATA
MESSAGES 2 ĺ OK ĺ DATE/TIME NOT SET ĺ OK ĺ ENABLE ĺ OK
GSM connection failed: OK ĺ CONFIGURATION ĺ OK ĺ aaaa ĺ OK ĺ MS SETTINGS ĺ OK ĺ
DATA MESSAGES 2 ĺ OK ĺ GSM CONNECT FAILED ĺ OK ĺ ENABLE ĺ OK
GSM antenna fail/restore: OK ĺ CONFIGURATION ĺ OK ĺ aaaa ĺ OK ĺ MS SETTINGS ĺ OK
ĺ DATA MESSAGES 2 ĺ OK ĺ GSM ANT FAIL/REST ĺ OK ĺ ENABLE ĺ OK
System shutdown: OK ĺ CONFIGURATION ĺ OK ĺ aaaa ĺ OK ĺ MS SETTINGS ĺ OK ĺ
DATA MESSAGES 2 ĺ OK ĺ SYSTEM SHUTDOWN EV ĺ OK ĺ ENABLE ĺ OK
Keypad fail/restore: OK ĺ CONFIGURATION ĺ OK ĺ aaaa ĺ OK ĺ MS SETTINGS ĺ OK ĺ
DATA MESSAGES 2 ĺ OK ĺ KEYPAD FAIL/REST ĺ OK ĺ ENABLE ĺ OK
GPRS connection failed: OK ĺ CONFIGURATION ĺ OK ĺ aaaa ĺ OK ĺ MS SETTINGS ĺ OK ĺ
DATA MESSAGES 2 ĺ OK ĺ GPRS CONNECT FAIL ĺ OK ĺ ENABLE ĺ OK
Value: aaaa – 4-digit administrator password.
EN
101
EKB3/
EKB3W
Config
Tool
102
EN
Enter parameter 24, event number & parameter status value:
24 01 1 # – Burglary alarm/restore
24 02 1 # – Mains power loss/restore
24 03 1 # – Armed/disarmed by user
24 04 1 # – Test event
24 05 1 # – Battery failed
24 06 1 # – Battery dead or missing
24 07 1 # – Tamper alarm/restore
24 08 1 # – Silent zone alarm/restore
24 09 1 # – Kronos ping
24 10 1 # – System started
24 13 1 # – 24h zone alarm/restore
24 14 1 # – Fire zone alarm/restore
24 15 1 # – Low battery
24 16 1 # – Temperature risen
24 17 1 # – Temperature fallen
24 18 1 # – Wireless signal loss/restore
24 19 1 # – Disarmed by user (Duress password)
24 20 1 # – Armed/disarmed by user (SGS password)
24 21 1 # – Armed/disarmed in Stay mode
24 22 1 # – Siren fail/restore
24 24 1 # –Date/time not set
24 25 1 # – GSM connection failed
24 26 1 # – GSM antenna fail/restore
24 27 1 # – System shutdown
24 28 1 # – Keypad fail/restore
24 29 1 # – GPRS connection failed
Example: 24031#
This operation may be carried out from the PC using the ELDES Configuration Tool software.
MANUAL ELDES ESIM364 V1.0
30.2. Communication
The system supports the following communication methods and protocols:
t
GPRS network – EGR100, Kronos protocol.
t
Voice calls (GSM audio channel) – Ademco Contact ID, Ademco 4+2 protocol.
t
RS485 data channel.
t
CSD (Cricuit Switched Data; fax line).
t
PSTN (landline) – Ademco Contact ID, Ademco 4+2 protocol.
t
SMS – Cortex SMS format.
Any communication method can be set as primary or backup connection. The user can set up to 5 backup connections in any sequence order.
Initially, the system communicates via primary connection with the monitoring station. By default, if the initial attempt to transmit data is
unsuccessful, the system will make additional attempts until the data is successfully delivered. If all attempts are unsuccessful, the system
will follow this pattern:
a) The system switches to the backup connection that follows in the sequence (presumably - Backup 1).
b) The system then attempts to transmit data by the backup connection.
c)
If the initial attempt is unsuccessful, the system will make additional attempts until the data is successfully delivered.
d)
If the system ends up with all unsuccessful attempts, it will switch to the next backup connection in the sequence (presumably - Backup 2) and will continue to operate as described in the previous steps.
e) If one of the attempts is successful, the system will transmit all queued up data messages by this connection.
f)
The system then returns to the primary connection and attempts to transmit the next data messages by primary connection.
g) If the system ends up with all unsuccessful attempts by all connections, it will wait until the Delay after last communication attempt
time (By default – 600 seconds) expires and will return to the primary connection afterwards.
h) If a new data message, except Test Event (ping), is generated during Delay after last communication attempt time, the system will
immediately attempt to transmit it to the monitoring station, regardless of Delay after last communication attempt being in progress.
MANUAL ELDES ESIM364 V1.0
EN
103
PRIMARY
Makes up to 3 or 5 attempts to transmit data
All attempts failed
Switches to BACKUP 1
Makes up to 3 or 5 attempts to transmit data
All attempts failed
One of the attempts is successful
Switches to BACKUP 2
Transmits all queued up data
Makes up to 3 or 5 attempts to transmit data
Returns to PRIMARY
All attempts failed
One of the attempts is successful
Switches to BACKUP 3
Transmits all queued up data
Makes up to 3 or 5 attempts to transmit data
Returns to PRIMARY
All attempts failed
One of the attempts is successful
Switches to BACKUP 4
Transmits all queued up data
Makes up to 3 or 5 attempts to transmit data
Returns to PRIMARY
All attempts failed
One of the attempts is successful
Switches to BACKUP 5
Transmits all queued up data
Makes up to 3 or 5 attempts to transmit data
Returns to PRIMARY
All attempts failed
One of the attempts is successful
Waits for 600 seconds
Transmits all queued up data
Delay after last communication attempt
Returns to PRIMARY
Returns to PRIMARY
NOTE: The number of attempts, indicated in the diagram, are default and depends on the determined communication method.
NOTE: When using Dual-SIM feature, the Secondary SIM card is involved in the communication process. For more details, please refer
to 31. DUAL SIM MANAGEMENT.
104
EN
MANUAL ELDES ESIM364 V1.0
Set primary connection
EKB2
EKB3/
EKB3W
Config
Tool
Set backup connection
1... 5
EKB2
EKB3/
EKB3W
Menu path:
GPRS network: OK ĺ CONFIGURATION ĺ OK ĺ aaaa ĺ OK ĺ MS SETTINGS ĺ OK ĺ
PRIMARY CONNECTION ĺ OK ĺ GPRS ĺ OK
Voice calls: OK ĺ CONFIGURATION ĺ OK ĺ aaaa ĺ OK ĺ MS SETTINGS ĺ OK ĺ PRIMARY
CONNECTION ĺ OK ĺ VOICE CALLS ĺ OK
RS485: OK ĺ CONFIGURATION ĺ OK ĺ aaaa ĺ OK ĺ MS SETTINGS ĺ OK ĺ PRIMARY
CONNECTION ĺ OK ĺ RS485 ĺ OK
CSD: OK ĺ CONFIGURATION ĺ OK ĺ aaaa ĺ OK ĺ MS SETTINGS ĺ OK ĺ PRIMARY
CONNECTION ĺ OK ĺ CSD ĺ OK
PSTN: OK ĺ CONFIGURATION ĺ OK ĺ aaaa ĺ OK ĺ MS SETTINGS ĺ OK ĺ PRIMARY
CONNECTION ĺ OK ĺ PSTN ĺ OK
SMS: OK ĺ CONFIGURATION ĺ OK ĺ aaaa ĺ OK ĺ MS SETTINGS ĺ OK ĺ PRIMARY
CONNECTION ĺ OK ĺ SMS ĺ OK
connection not in use: OK ĺ CONFIGURATION ĺ OK ĺ aaaa ĺ OK ĺ MS SETTINGS ĺ OK ĺ
PRIMARY CONNECTION ĺ OK ĺ N/A ĺ OK
Value: aaaa – 4-digit administrator password.
Enter parameter 48 & communication method number:
48 0 # – GPRS network
48 1 # – Voice calls
48 2 # – RS485
48 3 # – CSD
48 4 # – PSTN
48 5 # – SMS
48 6 # – connection not in use
Example: 484#
This operation may be carried out from the PC using the ELDES Configuration Tool software.
Menu path:
GPRS network: OK ĺ CONFIGURATION ĺ OK ĺ aaaa ĺ OK ĺ MS SETTINGS ĺ OK ĺ BACKUP
CONNECTION1... 5 ĺ OK ĺ GPRS ĺ OK
Voice calls: OK ĺ CONFIGURATION ĺ OK ĺ aaaa ĺ OK ĺ MS SETTINGS ĺ OK ĺ BACKUP
CONNECTION1... 5 ĺ OK ĺ VOICE CALLS ĺ OK
RS485: OK ĺ CONFIGURATION ĺ OK ĺ aaaa ĺ OK ĺ MS SETTINGS ĺ OK ĺ BACKUP
CONNECTION1... 5 ĺ OK ĺ RS485 ĺ OK
CSD: K ĺ CONFIGURATION ĺ OK ĺ aaaa ĺ OK ĺ MS SETTINGS ĺ OK ĺ
BACKUP CONNECTION1... 5 ĺ OK ĺ CSD ĺ OK
PSTN: OK ĺ CONFIGURATION ĺ OK ĺ aaaa ĺ OK ĺ MS SETTINGS ĺ OK ĺ BACKUP
CONNECTION1... 5 ĺ OK ĺ PSTN ĺ OK
SMS: OK ĺ CONFIGURATION ĺ OK ĺ aaaa ĺ OK ĺ MS SETTINGS ĺ OK ĺ BACKUP
CONNECTION1... 5 ĺ OK ĺ SMS ĺ OK
connection not in use: OK ĺ CONFIGURATION ĺ OK ĺ aaaa ĺ OK ĺ MS SETTINGS ĺ OK ĺ
BACKUP CONNECTION1... 5 ĺ OK ĺ N/A ĺ OK
Value: aaaa – 4-digit administrator password.
Enter parameter 83, backup connection slot number & communication method
number:
83 bb 0 # – GPRS network
83 bb 1 # – Voice calls
83 bb 2 # – RS485
83 bb 3 # – CSD
83 bb 4 # – PSTN
83 bb 5 # – SMS
83 bb 6 # – connection not in use
Value: bb – backup connection slot number, range – [01... 04].
Example: 484#
Config
Tool
MANUAL ELDES ESIM364 V1.0
This operation may be carried out from the PC using the ELDES Configuration Tool software.
EN
105
If all attempts by all set connections are unsuccessful, the system will wait until the delay time (By default – 600 seconds) expires and will
attempt to transmit data to the monitoring station again starting with the primary connection.
Set delay after last
communication
attempt
EKB2
EKB3/
EKB3W
Config
Tool
Menu path:
OK ĺ CONFIGURATION ĺ OK ĺ aaaa ĺ OK ĺ MS SETTINGS ĺ OK ĺ DELAY LAST ATTEMPT
ĺ OK ĺ aaapp ĺ OK
Value: aaaa – 4-digit administrator password; aaapp – duration of delay after last attempt,
range – [0... 65535] seconds.
Enter parameter 69 & duration of delay after last attempt:
69 aaapp #
Value: aaapp – duration of delay after last attempt, range – [0... 65535] seconds.
Example: 69200#
This operation may be carried out from the PC using the ELDES Configuration Tool software.
NOTE: 0 value disables delay after last communication attempt.
NOTE: The system is fully compatible with Kronos NET/Kronos LT monitoring station software for communication via GPRS network. When
using a different monitoring station software, EGR100 middleware is required. EGR100 is freeware and can be downloaded at www.eldes.lt/
en/download
30.2.1. GPRS Network
Set server IP address
SMS
SMS text message content:
ssss_SETGPRS:IP:add.add.add.add
Value: ssss – 4-digit SMS password; add.add.add.add – server IP address.
Example: 1111_SETGPRS:IP:65.82.110.15
EKB2
Menu path:
OK ĺ CONFIGURATION ĺ OK ĺ aaaa ĺ OK ĺ GPRS SETTINGS ĺ OK ĺ SERVER IP ĺ OK ĺ
add.add.add.add ĺ OK
Value: aaaa – 4-digit administartor password; add.add.add.add – server IP address.
EKB3/
Enter parameter 40 & server IP address:
40 add add add add #
EKB3W
Config
Tool
Set server port
SMS
EKB2
EKB3/
EKB3W
Config
Tool
106
EN
Value: add add add add – server IP address.
Example: 40658211015#
This operation may be carried out from the PC using the ELDES Configuration Tool software.
SMS text message content:
ssss_SETGPRS:PORT:pprrt
Value: ssss – 4-digit SMS password; pprrt – server port number, range – [1... 65535].
Example: 1111_SETGPRS:PORT:5521
Menu path:
OK ĺ CONFIGURATION ĺ OK ĺ aaaa ĺ OK ĺ GPRS SETTINGS ĺ OK ĺ SERVER PORT ĺ OK
ĺ pprrt ĺ OK
Value: aaaa – 4-digit administartor password; pprrt – server port number, range – [1...
65535].
Enter parameter 44 & server port number:
44 pprrt #
Value: pprrt – server port number, range – [1... 65535].
Example: 443365#
This operation may be carried out from the PC using the ELDES Configuration Tool software.
MANUAL ELDES ESIM364 V1.0
Set DNS1 server IP
address
SMS
SMS text message content:
ssss_SETGPRS:DNS1:add.add.add.add
Value: ssss – 4-digit SMS password; add.add.add.add – DNS1 server IP address.
Example: 1111_SETGPRS:DNS1:65.82.110.01
EKB2
Menu path:
OK ĺ CONFIGURATION ĺ OK ĺ aaaa ĺ OK ĺ GPRS SETTINGS ĺ OK ĺ DNS1 ĺ OK ĺ add.
add.add.add ĺ OK
Value: aaaa – 4-digit administartor password; add.add.add.add – DNS1 server IP address.
EKB3/
Enter parameter 41 & DNS1 server IP address:
41 add add add add #
EKB3W
Config
Tool
Set DNS2 server IP
address
This operation may be carried out from the PC using the ELDES Configuration Tool software.
SMS
SMS text message content:
ssss_SETGPRS:DNS2:add.add.add.add
Value: ssss – 4-digit SMS password; add.add.add.add – DNS2 server IP address.
Example: 1111_SETGPRS:DNS2:65.82.110.02
EKB2
Menu path:
OK ĺ CONFIGURATION ĺ OK ĺ aaaa ĺ OK ĺ GPRS SETTINGS ĺ OK ĺ DNS2 ĺ OK ĺ add.
add.add.add ĺ OK
Value: aaaa – 4-digit administartor password; add.add.add.add – DNS2 server IP address.
EKB3/
Enter parameter 42 & DNS2 server IP address:
42 add add add add #
EKB3W
Config
Tool
Set protocol
Value: add add add add – DNS1 server IP address.
Example: 41658211001#
Value: add add add add – DNS2 server IP address.
Example: 42658211001#
This operation may be carried out from the PC using the ELDES Configuration Tool software.
SMS
SMS text message content:
ssss_SETGPRS:PROTOCOL:ptc
Value: ssss – 4-digit SMS password; ptc – protocol, range – [TCP... UDP].
Example: 1111_SETGPRS:PROTOCOL:UDP
EKB2
Menu path:
OK ĺ CONFIGURATION ĺ OK ĺ aaaa ĺ OK ĺ GPRS SETTINGS ĺ OK ĺ PROTOCOL ĺ OK ĺ
TCP | UDP ĺ OK
Value: aaaa – 4-digit administartor passw
EKB3W
Enter parameter 43 & protocol number:
43 0 # - TCP
43 1 # - UDP
Example: 431#
Config
Tool
This operation may be carried out from the PC using the ELDES Configuration Tool software.
EKB3/
NOTE: Kronos NET/Kronos LT software communicates via TCP protocol, while EGR100 middle-ware v1.2 and up supports both – TCP and
UDP protocols. However, TCP protocol is NOT recommend to use with EGR100.
MANUAL ELDES ESIM364 V1.0
EN
107
Set APN
SMS
Config
Tool
Set user name
SMS
Config
Tool
Set password
SMS
Config
Tool
SMS text message content:
ssss_SETGPRS:APN:acc-point-name
Value: ssss – 4-digit SMS password; acc-point-name – up to 31 character APN (Access Point
Name) provided by the GSM operator.
Example: 1111_SETGPRS:APN:internet
This operation may be carried out from the PC using the ELDES Configuration Tool software.
SMS text message content:
ssss_SETGPRS:USER:usr-name
Value: ssss – 4-digit SMS password; usr-name – up to 31 character user name provided by
the GSM operator.
Example: 1111_USER:mobileusr
This operation may be carried out from the PC using the ELDES Configuration Tool software.
SMS text message content:
ssss_SETGPRS:PSW:password
Value: ssss – 4-digit SMS password; password – up to 31 character password provided by
the GSM operator.
Example: 1111_SETGPRS:PSW:mobilepsw
This operation may be carried out from the PC using the ELDES Configuration Tool software.
By default, if the initial attempt to transmit data to the monitoring station via GPRS network method is unsuccessful, the system will make
up to 2 additional attempts. If all attempts are unsuccessful, the system will switch to next backup connection that follows in the sequence
and will attempt to transmit data until it is successfully delivered to the monitoring station.
Set attempts
EKB2
Menu path:
OK ĺ CONFIGURATION ĺ OK ĺ aaaa ĺ OK ĺ MS SETTINGS ĺ OK ĺ GPRS SETTINGS ĺ OK
ĺ GPRS ATTEMPTS ĺ OK ĺ att ĺ OK
Value: aaaa – 4-digit administrator password; att – number of attempts, range – [1... 255].
EKB3/
Enter parameter 68 & number of attempts:
68 att #
EKB3W
Config
Tool
Value: att – number of attempts, range – [01... 255].
Example: 6809#
This operation may be carried out from the PC using the ELDES Configuration Tool software.
To report the online status, the system periodically transmits (By default – every 180 seconds) Test Event data message (ping) to the
monitoring station via GPRS network.
Set test period
EKB2
EKB3/
EKB3W
108
EN
Menu path:
OK ĺ CONFIGURATION ĺ OK ĺ aaaa ĺ OK ĺ MS SETTINGS ĺ OK ĺ GPRS SETTINGS ĺ OK
ĺ TEST PERIOD ĺ OK ĺ tteessttpp ĺ OK
Value: aaaa – 4-digit administrator password; tteessttpp – test period, range – [0... 65535]
seconds.
Enter parameter 46 & number of attempts:
46 tteessttpp #
Value: tteessttpp – test period, range – [0... 65535] seconds.
Example: 46120#
MANUAL ELDES ESIM364 V1.0
Config
Tool
This operation may be carried out from the PC using the ELDES Configuration Tool software.
NOTE: 0 value disables test period.
Unit ID is a 4-digit number (By default – 0000) required to identify the alarm system unit by EGR100 middle-ware. It is MANDATORY to
change the default Unit ID before using EGR100.
Set unit ID
EKB2
Menu path:
OK ĺ CONFIGURATION ĺ OK ĺ aaaa ĺ OK ĺ MS SETTINGS ĺ OK ĺ GPRS SETTINGS ĺ OK
ĺ UNIT ID ĺ OK ĺ unid ĺ OK
Value: aaaa – 4-digit administartor password; unid – 4-digit unit ID number.
EKB3/
Enter parameter 47 & unit ID number:
47 unid #
EKB3W
Config
Tool
View GPRS network
settings
SMS
Config
Tool
Value: unid – 4-digit unit ID number.
Example: 472245#
This operation may be carried out from the PC using the ELDES Configuration Tool software.
SMS text message content:
ssss_SETGPRS?
Example: 1111_SETGPRS?
This operation may be carried out from the PC using the ELDES Configuration Tool software.
30.2.2. Voice Calls and SMS
The system supports up to 3 monitoring station phone numbers for communication with the alarm system by Voice Calls or SMS communication method. Tel. Number 1 is mandatory, the other two can be used as backup phone numbers and are not necessary. The supported
phone number formats are the following:
t
International (with plus) – The phone numbers must be entered starting with plus and an international country code in the following format: +[international code][area code][local number], example for UK: +4417091111111. This format can be used when setting
up the phone number by ELDES Configuration Tool software.
t
International (with 00) – The phone numbers must be entered starting with 00 and an international country code in the following
format: 00[international code][area code][local number], example for UK: 004417091111111. This format can be used when setting
up the phone number by EKB2/EKB3/EKB3W keypad.
t
Local – The phone numbers must be entered starting with an area code in the following format: [area code][local number], example
for UK: 017091111111. This format can be used when setting up the phone number by EKB2/EKB3/EKB3W keypad and ELDES Configuration Tool software.
Set monitoring station
phone number
EKB2
EKB3/
EKB3W
Config
Tool
MANUAL ELDES ESIM364 V1.0
Menu path:
OK ĺ CONFIGURATION ĺ OK ĺ aaaa ĺ OK ĺ MS SETTINGS ĺ OK ĺ VOICE CALLS/SMS ST ĺ
OK ĺ TEL. NUMBER 1... 3 ĺ OK ĺ ttteeellnnuumm ĺ OK
Value: aaaa – 4-digit administrator password; ttteeellnnuumm – up to 15 digits monitoring
station phone number.
Enter parameter 26, phone number slot & phone number:
26 ps ttteeellnnuumm #
Value: ps – phone number slot, range – [01... 03]; ttteeellnnuumm – up to 15 digits monitoring station phone number.
Example: 2601004417091111111#
This operation may be carried out from the PC using the ELDES Configuration Tool software.
EN
109
Delete monitoring
station phone number
EKB2
Menu path:
OK ĺ CONFIGURATION ĺ OK ĺ aaaa ĺ OK ĺ MS SETTINGS ĺ OK ĺ VOICE CALLS/SMS ST ĺ
OK ĺ TEL. NUMBER 1... 3 ĺ OK ĺ OK
Value: aaaa – 4-digit administrator password.
Config
Tool
This operation may be carried out from the PC using the ELDES Configuration Tool software.
By default, if the initial attempt to transmit data to the monitoring station’s Tel Number 1 via Voice Calls or SMS method is unsuccessful, the
system will make up to 4 additional attempts. After all unsuccessful attempts, the system will continue to communicate with the monitoring station by switching to the next phone number that follows in the sequence and making up to 4 additional attempts if the initial attempt is unsuccessful. If all attempts to all phone numbers are unsuccessful, the system will switch to next backup connection that follows
in the sequence and will attempt to transmit data until it is successfully delivered to the monitoring station.
Set attempts
EKB2
Menu path:
OK ĺ CONFIGURATION ĺ OK ĺ aaaa ĺ OK ĺ MS SETTINGS ĺ OK ĺ VOICE CALLS/SMS ST ĺ
OK ĺ ATTEMPTS ĺ OK ĺ at ĺ OK
Value: aaaa – 4-digit administrator password; at – number of attempts, range – [1... 10].
EKB3W
Enter parameter 37 & number of attempts:
37 at #
Value: at – number of attempts, range – [01... 10].
Example: 3706#
Config
Tool
This operation may be carried out from the PC using the ELDES Configuration Tool software.
EKB3/
Due to the individual configuration of each monitoring station, the system may fail to deliver the data message via Voice Calls communication method. In such cases it is recommended to adjust the microphone gain until the optimal value, leading to successful data message
delivery, is discovered.
Set microphone gain
EKB2
Menu path:
OK ĺ CONFIGURATION ĺ OK ĺ aaaa ĺ OK ĺ PRIMARY SETT INGS ĺ OK ĺ GSM AUDIO ĺ OK
ĺ MICROPHONE GAIN ĺ OK ĺ mg ĺ OK
Value: aaaa – 4-digit administrator password; mg – microphone gain, range – [0... 15].
Config
Tool
This operation may be carried out from the PC using the ELDES Configuration Tool software.
30.2.3. PSTN
The system supports up to 3 monitoring station phone numbers for communication with the alarm system by PSTN communication method. Tel. Number 1 is mandatory, the other two can be used as backup phone numbers and are not necessary. The supported phone number
formats are the following:
t
International (with 00) – The phone numbers must be entered starting with 00 and an international country code in the following
format: 00[international code][area code][local number], example for UK: 004417091111111. This format can be used when setting
up the phone number by EKB2/EKB3/EKB3W keypad and ELDES Configuration Tool software..
t
Local – The phone numbers must be entered starting with an area code in the following format: [area code][local number], example
for UK: 017091111111. This format can be used when setting up the phone number by EKB2/EKB3/EKB3W keypad and ELDES Configuration Tool software.
Set monitoring station
phone number
110
EN
EKB2
Menu path:
OK ĺ CONFIGURATION ĺ OK ĺ aaaa ĺ OK ĺ MS SETTINGS ĺ OK ĺ PSTN SETTINGS ĺ OK
ĺ TEL. NUMBER 1... 3 ĺ OK ĺ ttteeellnnuumm ĺ OK
Value: aaaa – 4-digit administrator password; ttteeellnnuumm – up to 15 digits monitoring
station phone number.
MANUAL ELDES ESIM364 V1.0
EKB3/
EKB3W
Delete monitoring
station phone number
Enter parameter 58, phone number slot & phone number:
58 ps ttteeellnnuumm #
Value: ps – phone number slot, range – [01... 03]; ttteeellnnuumm – up to 15 digits monitoring station phone number.
Example: 5802004417091111111#
Config
Tool
This operation may be carried out from the PC using the ELDES Configuration Tool software.
EKB2
Menu path:
OK ĺ CONFIGURATION ĺ OK ĺ aaaa ĺ OK ĺ MS SETTINGS ĺ OK ĺ PSTN SETTINGS ĺ OK
ĺ TEL. NUMBER 1... 3 ĺ OK ĺ OK
Value: aaaa – 4-digit administrator password
Config
Tool
This operation may be carried out from the PC using the ELDES Configuration Tool software.
By default, if the initial attempt to transmit data to the monitoring station’s Tel Number 1 via PSTN method is unsuccessful, the system
will make up to 4 additional attempts. After all unsuccessful attempts, the system will switch to the next phone number that follows
in the sequence and will make up to 4 additional attempts if the initial attempt is unsuccessful. If all attempts to all phone numbers are
unsuccessful, the system will switch to next backup connection that follows in the sequence and will attempt to transmit data until it is
successfully delivered to the monitoring station.
Set attempts
EKB2
Menu path:
OK ĺ CONFIGURATION ĺ OK ĺ aaaa ĺ OK ĺ MS SETTINGS ĺ OK ĺ PSTN SETTINGS ĺ OK
ĺ ATTEMPTS ĺ OK ĺ at ĺ OK
Value: aaaa – 4-digit administrator password; at – number of attempts, range – [1... 10].
EKB3/
Enter parameter 91 & number of attempts:
91 at #
EKB3W
Config
Tool
Value: at – number of attempts, range – [01... 10].
Example: 9108#
This operation may be carried out from the PC using the ELDES Configuration Tool software.
30.2.4. CSD
The system supports up to 5 monitoring station phone numbers for communication with the alarm system by CSD communication method.
Tel. Number 1 is mandatory, the other four can be used as backup phone numbers and are not necessary. The supported phone number
formats are the following:
t
International (with plus) – The phone number must be entered starting with plus and an international country code in the following
format: +[international code][area code][local number], example for UK: +4417091111111. This format can be used when setting up
the phone number by ELDES Configuration Tool software.
t
International (with 00) – The phone number must be entered starting with 00 and an international country code in the following ž
format: 00[international code][area code][local number], example for UK: 004417091111111. This format can be used when setting
up the phone number by EKB2/EKB3/EKB3W keypad.
Set monitoring station
phone number
EKB2
EKB3/
EKB3W
MANUAL ELDES ESIM364 V1.0
Menu path:
OK ĺ CONFIGURATION ĺ OK ĺ aaaa ĺ OK ĺ MS SETTINGS ĺ OK ĺ CSD SETTINGS ĺ OK ĺ
TEL. NUMBER 1... 5 ĺ OK ĺ ttteeellnnuumm ĺ OK
Value: aaaa – 4-digit administrator password; ttteeellnnuumm – up to 15 digits monitoring
station phone number.
Enter parameter 85, number of entry & phone number:
85 ps ttteeellnnuumm #
Value: ps – phone number slot, range – [01... 05]; ttteeellnnuumm – up to 15 digits monitoring station phone number.
Example: 8501004417091111111#
EN
111
Delete monitoring
station phone number
Config
Tool
This operation may be carried out from the PC using the ELDES Configuration Tool software.
EKB2
Menu path:
OK ĺ CONFIGURATION ĺ OK ĺ aaaa ĺ OK ĺ MS SETTINGS ĺ OK ĺ CSD SETTINGS ĺ OK ĺ
TEL. NUMBER ĺ OK ĺ OK
Value: aaaa – 4-digit administrator password.
Config
Tool
This operation may be carried out from the PC using the ELDES Configuration Tool software.
By default, if the initial attempt to transmit data to the monitoring station’s phone number via CSD method is unsuccessful, the system will
make up to 4 additional attempts. If all attempts are unsuccessful, the system will switch to next backup connection that follows in the
sequence and will attempt to transmit data until it is successfully delivered to the monitoring station.
Set attempts
EKB2
Menu path:
OK ĺ CONFIGURATION ĺ OK ĺ aaaa ĺ OK ĺ MS SETTINGS ĺ OK ĺ CSD SETTINGS ĺ OK ĺ
ATTEMPTS ĺ OK ĺ at ĺ OK
Value: aaaa – 4-digit administrator password; at – number of attempts, range – [1... 10].
EKB3/
Enter parameter 84 & number of attempts:
84 at #
EKB3W
Config
Tool
112
EN
Value: at – number of attempts, range – [01... 10].
Example: 8403#
This operation may be carried out from the PC using the ELDES Configuration Tool software.
MANUAL ELDES ESIM364 V1.0
31. DUAL SIM MANAGEMENT
The Dual-SIM feature allows the system to operate with one of the two inserted SIM cards identified as Primary SIM and Secondary SIM
respectively. The Primary SIM card works as the main default card, while the Secondary SIM card is intended for backup purposes or addition
to the Primary SIM card - SMS text message sending/calling to the preset user phone number and/or communication with the monitoring
station.
The Dual-SIM feature can operate in one of the following modes:
t
Disabled – The Secondary SIM card will not be functional and the system operates with Primary SIM card only (by default – enabled).
t
Automatic – The system switches between the SIM cards in case of a GSM connection or one of the SIM cards failure.
t
Manual – Provides a fully customizable set up of switching between the SIM cards. FOR ADVANCED USERS ONLY!
Manage Dual -SIM
feature
Config
Tool
This operation may be carried out from the PC using the ELDES Configuration Tool software.
NOTE: Regardless of the selected mode, only one of the two SIM cards can operate at the same time.
31.1. Disabled Mode
Disabled mode is the default system mode that does not involve the Secondary SIM in the communication process. When this mode is in
use, the system will ignore the Secondary SIM card even if inserted in the SIM card slot.
For more details on how the system communicates with the user and the monitoring station in Disabled mode, please refer to 17. ALARM
INDICATIONS AND NOTIFICATIONS and 30.2. Communication respectively.
31.2. Automatic Mode
Automatic mode involves both SIM cards in the communication process. In this mode there is no Primary or Secondary SIM card hierarchy,
since both cards are equal and the SIM card that is currently in use maintains the GSM connection at all time, unless a failure occurs and the
other card would replace the previous one.
When one of the SIM card fails, the system attempts to re-establish a connection with it by starting an initial reconnection for a set number
of attempts (by default - 3 attempts). If all attempts fail, the system will switch to the other SIM card. If the other SIM card is responsive and
a GSM connection is successfully established, the system will remain operating with that SIM card until it fails. However, if the other SIM
card is unresponsive or it is not present in the SIM card slot, the system will return to the previous SIM card and attempt to establish a GSM
connection with it. If the system fails to carry out this action, after a single attempt it will switch to the other SIM card. This cycle continues
until one of the SIM cards responds and a GSM connection is successfully established. When the SIM card fails, the system will once again
attempt to restore the GSM connection for a set number of attempts (by default – 3 attempts). If all attempts fail, the cycle will continue as
described previously.
In Automatic mode the priority is to transmit data to the monitoring station, but if an event, which requires the system to send an SMS text
message occurs , the system will send the SMS text message via the SIM card that is currently in use. This can only be carried out under
the following conditions:
t
among the attempts to transmit data to the monitoring station (depending on communication method).
t
while switching the monitoring station connections.
t
while switching between the SIM cards.
The following example indicates the situation described above.
MANUAL ELDES ESIM364 V1.0
EN
113
Makes up to 3 or 5 attempt to transmit data via PRIMARY connection on Primary SIM
All attempts failed
One of the attempts successful
Switches to BACKUP1 connection on Primary SIM
Continues transmitting data via PRIMARY connection on Primary SIM card
Makes 1 attempt to transmit data via BACKUP1
connection on Primary SIM, but it is unsuccessful
SMS text message queues up for
sending to user phone number
Attempts to send the text message to user phone number
SMS delivery successful
SMS delivery failed
Continues making the rest of the
attempts (2 or 4) to transmit data via
BACKUP1 connection on Primary SIM
Attempts to send SMS text message
to next available user phone number
All users unavailable
One of the attempts successful
All attempts failed
Transmits all queued up data
Switches to BACKUP2 connection on Primary SIM
One of the users available
Sends the SMS text message
Returns to PRIMARY connection on Primary SIM
Makes up to 3 or 5 attempts
to transmit data via BACKUP2
connection on Primary SIM
Primary SIM card ERROR
Makes up to 3 attempts to
re-establish GSM connection on Primary SIM card
One of the attempts to re-establish GSM connection successful
Makes up to 3 or 5 attempts to transmit data
via BACKUP2 connection on Primary SIM
All attempts failed
One of the attempts successful
Waits for 600 seconds
Transmits all queued up data
Delay after last communication attempt
Returns to PRIMARY connection on Primary SIM
Returns to PRIMARY connection on Primary SIM
Continued in next page
114
EN
MANUAL ELDES ESIM364 V1.0
Continued from previous page
All attempts failed
Makes 1 attempt to switch
to Secondary SIM card
All attempts failed
Attempt successful
Makes up to 3 or 5 attempts to transmit data
via BACKUP2 connection on Secondary SIM
Makes 1 attempt to switch
to Primary SIM card
One of the attempts successful
All attempts failed
Attempt successful
All attempts failed
Transmits all queued up data
Waits for 600 seconds
Continues operating on Primary SIM until the card fails
Makes 1 attempt to switch
to Secondary SIM card
Delay after last communication attempt
Returns to PRIMARY connection on Primary SIM
Continues operating on Secondary SIM until the card fails
Returns to PRIMARY connection on Primary SIM
Continues switching between
the SIM cards until one is available
Continues operating on Secondary SIM until the card fails
NOTE: The number of attempts, indicated in the diagram, are default and depends on the determined communication method
31.3. Manual Mode
Manual mode allows to use both - Primary and Secondary SIM cards and fully customize the algorithm of the communication. The system
can be set up to send SMS text messages/call to the preset user phone number and/or communicate with the monitoring station as follows:
t
Primary SIM – Determines that the SMS text messages/calls/data will be transmitted via the Primary SIM card.
t
Secondary SIM – Determines that the SMS text messages/calls/data will be transmitted via the Secondary SIM card.
t
Currently in use SIM – Determines that the SMS text messages/calls/data will be transmitted via the SIM card that the system is
currently switched to - either Primary or the Secondary SIM card.
t
Return to Primary SIM Enabled – Determines that the Primary SIM card will be the main SIM card of the system. If it is set up to use
the Secondary SIM in the communication process, the system will do so, but after completing the task via the Secondary SIM card, the
system will always return to the Primary SIM card
t
Try to find operator for a maximum of x times – Determines the maximum number of attempts the system should attempt to
re-establish a GSM connection on the current SIM card in case of unsuccessful initial attempt (by default – 3 attempts).
In Manual mode the priority is to transmit data to the monitoring station, but if an event, which requires the system to send an SMS text
message via one of the SIM cards, occurs , the system will switch to the requested SIM card and send the SMS text message. This can only
be carried out under the following conditions:
t
t
t
among the attempts to transmit data to the monitoring station (depending on communication method).
while switching the monitoring station connections.
while switching between the SIM cards.
Example: System settings are the following:
Dual SIM Management:
t
Manual Mode selected
t
Return to Primary SIM – Disabled.
t
Send SMS / Call via – Secondary SIM.
MS Settings – Communication:
t
Primary – Voice Calls via Secondary SIM.
t
Backup1 – CSD via Primary SIM.
t
Backup2 – GPRS Network via Primary SIM.
MANUAL ELDES ESIM364 V1.0
EN
115
Let’s say, the system is configured to send an SMS text message to user phone number in case of a Fire Zone Alarm and to transmit data to
the monitoring station when the system is ARMED. The system is currently switched to the Primary SIM card. The system will follow this
pattern:
a) The user arms the system followed by system switching to the Secondary SIM and attempting to transmit data to the monitoring station via the Primary connection, which is Voice Calls communication method, but fails.
b) The system then switches to the Primary SIM and attempts to transmit data via Backup1 connection, which is CSD communication
method, but fails again.
c)
During the event described in step b), a Fire Zone Alarm occurs. The system will switch to the Secondary SIM and attempt to send the
SMS text message to the user regarding this event.
d) The system continues with the data transmission to the monitoring station by switching back to Primary SIM and attempting to transmit data via Backup2 connection, which is GPRS Network communication method, and succeeds.
e) The alarm system switches back to the Primary connection (Voice Calls) and to the Secondary SIM card and waits until the occurrence
of further events.
Attempts to transmit data via PRIMARY connnection (Voice Calls) on Secondary SIM
All attempts failed
Switches to BACKUP1 connection (CSD) on Primary SIM card
Fire Alarm occurs
Stays on Secondary SIM card
Makes up to 5 attempts to transmit data
Attempts to send SMS text message to user phone number
One of the attempts successful
Transmits all queued up data
All attempts failed
SMS delivery successful
Returns to Primary connnection
(Voice Calls) on Secondary SIM
SMS delivery failed
Attempts to send SMS text
message to next available
user phone number
One of the users available
Sends the SMS text message
All users unavailable
Switches to Backup2
(GPRS Network) connection on Primary SIM card
Makes up to 3 attempts
to transmit data
All attempts failed
One of the attempts successful
Waits for 600 seconds
Transmits all queued up data
Delay after last communication attempt
Returns to Primary connnection
(Voice Calls) on Secondary SIM
Returns to PRIMARY connnection
(Voice Calls) on Secondary SIM
NOTE: The number of attempts, indicated in the diagram, are default and depends on the determined communication method
NOTE: If the Return to Primary SIM parameter is enabled, the system would return to the Primary SIM after each data transmission.
116
EN
MANUAL ELDES ESIM364 V1.0
32. ELDES WIRED DEVICES
32.1. RS485 Interface
RS485 interface is used for the system to communicate with the following devices:
t
EKB2 keypads (up to 4 units).
t
EKB3 keypads (up to 4 units).
t
EPGM1 modules (up to 2 units).
The terminals of RS485 interface are Y (yellow wire) and G (green wire), which are clock and data respectively. The devices, connected to
RS485 interface, must be powered from the AUX+ and AUX- terminals.
For more details on RS485 device wiring, please refer to 3.2.7. RS485.
32.1.1. EKB2 - LCD Keypad
EKB2 is an LCD keypad intended for using with ESIM364 alarm system.
Main EKB2 features:
t
Alarm system arming and disarming (see 12.3. EKB2 Keypad and User Password).
t
Arming and disarming in Stay mode (see 15. STAY MODE).
t
System parameter configuration (see 5. CONFIGURATION METHODS).
t
PGM output control (see 18.4. Turning PGM Outputs ON and OFF).
t
System information display on LCD screen (see 32.1.1.4. Visual and Audio Indications).
t
Audio indication by built-in buzzer (see 32.1.1.4. Visual and Audio Indications ).
t
Wireless device information display (see 19.2. Wireless Device Information and Signal Status Monitoring).
t
Keypad partition switch (see 23.3. Keypad Partition and Keypad Partition Switch).
The system configuration is performed by accessing EKB2 menu and entering the required values. ESIM364 system allows to connect up
to 4 EKB2 keypads.
32.1.1.1. Technical Specifications
32.1.1.1.1 Electrical & Mechanical Characteristics
Power Supply
12-14V
Maximum Keypad Connection Cable Length
100 m.
Dimensions
133 x 89 x 19 mm
Range of Operating Temperatures
0...+55ºC
MANUAL ELDES ESIM364 V1.0
150mA max.
EN
117
32.1.1.1.2 Keys funcionality
One menu level back / cancel
Temperature
39
Menu navigation – up
GSM signal
strength
Digital
clock
Menu navigation – down
Confirm (enter) value
...
Value typing
Keypad partition switch / minus
System
status
message
Home screen
view
One or more
violated
zones are
bypassed
One or
more
system
faults are
present
System
armed in Stay
mode
symbol for entering negative
temp. value
Additional menu / minus symbol
for entering negative temp. value
Custom
partition
name
32.1.1.1.3 Connector and Main Unit Functionality
Vin
Positive power supply terminal
COM
Negative power supply terminal
G
RS485 interface for communication (green wire)
Y
RS485 interface for communication (yellow wire)
COM
Common terminal for Z1
Z1
Security zone terminal
A0
Keypad address pin
A1
Keypad address pin
Buzzer
Buzzer for audio indications
Tamper
Tamper-button for EKB2 enclosure status monitoring
40
VIN
COM
Z1
G
Y
COM
A0A1
Buzzer
Tamper
32.1.1.1.4 Keypad Address
A0 and A1 pins located on the back side of the keypad are intended to set keypad address. The keypad address is set by putting the jumper
(-s) on the pins. ESIM364 system allows to connect up to 4 EKB2 keypads - each set under different address. Jumper combinations for different keypad address configuration are indicated in the table below.
118
EN
MANUAL ELDES ESIM364 V1.0
Jumper position
Address
A0 A1
Keypad 1
A0 A1
Keypad 2
A0 A1
Keypad 3
A0 A1
Keypad 4
ENTER USER PSW
The address of each connected keypad is also indicated in ELDES Configuration Tool software.
32.1.1.2. Installation
1.
Remove the screw located on the bottom side of the enclosure (see Fig. No.
41)
2.
Detach keypad holder from EKB2 keypad by gently pulling the holder
towards yourself (see Fig. No. 42).
3.
Fix the keypad holder on the wall using the screws. (see Fig. No. 43)
41
4. Disconnect ESIM364 main power supply and backup battery.
5.
Wire up keypad terminals to ESIM364 alarm system respectively – Vin to
AUX+, COM to AUX-, Y to Y, G to G.
6.
Z1 and COM terminals must be connected with resistor of 5,6kΩ nominal(see Fig. No. 44). As keypad zone Z1 is disabled by default, it can be enabled
by SMS, EKB2 keypad, EKB3 and EKB3W keypad and ELDES Configuration
Tool. Keypad zone Z1 must be enabled and resistor connected even if the
tamper button alone is required.
7.
Set the keypad address by putting the jumper on A0 and A1 pins (see
32.1.1.1.4 Keypad Address).
42
8. Fix the keypad into the holder.
ATTENTION: Before fixing the keypad into the holder please , make
sure that the tamper button is properly pressed (see Fig. No. 40).
9.
Screw up the bottom side of the enclosure. (see Fig. No. 41)
10. Power up ESIM364 alarm system.
11. EKB2 keypad is ready.
For more details on multiple keypad wiring, please refer to 3.2.7. RS485
43
44
ESIM364
Y G
VIN
COM
Z1
AUX- AUX+
EKB2
G
Y
COM
5,6kΩ
MANUAL ELDES ESIM364 V1.0
EN
119
32.1.1.3. Visual and Audio Indications
EKB2 can be used even in dark premises as the LCD screen and keys are illuminated continuously. The illumination level lowers down if 3 minutes after the last key-touch expires while the system is disarmed. In case of alarm, the keypad illumination level is boosted and stays in this
state until the system is disarmed.
The built-in buzzer uses two types of sound signals – three short beeps and one long beep. Three short beeps stand for successfully carried
out configuration, one long beep – for invalid configuration. In addition, the buzzer emits short beeps in case of alarm.
32.1.1.4.
EKB2 Zone and Tamper
Keypad EKB2 has one wired zone Z1 and one tamper button. By default, the keypad zone Z1 is disabled. The keypad zone can be enabled by
SMS, EKB2 keypad, EKB3 keypad, EKB3W keypad and ELDES Configuration Tool software (see 14.9. Disabling and Enabling Zones). When
Z1 is enabled, it operates like any other system zone, therefore a sensor can be connected to it. In addition, Z1 and COM terminals must be
connected with resistor of 5,6kΩ nominal.
The tamper button is intended for monitoring the enclosure status of EKB2, therefore the system causes alarm if the enclosure is illegally
opened. Keypad zone Z1 must be enabled and resistor connected even if the tamper button alone is required.
32.1.1.5. Icons and Messages
Icon / Message
Description
Chime - Delay zone violated when system
is disarmed.
Exit delay countdown initiated.
System is armed and menu is locked.
System is disarmed and menu is unlocked
Icon / Message
24H zone violated.
FIRE ALARM
Fire zone violated.
TAMPER ALARM
READY
NOT READY
ARMED
+ CONFIGURATION
MODE
BURGLARY ALARM
120
EN
Configuration mode activated.
Delay, Instant or Follow zone violated
when system is armed.
Description
24 ALARM
Tamper violated
System is ready to be armed.
System is not ready to be armed – one or
more zones / tampers violated.
System is armed (optional feature).
STAY
Stay mode activated
BYP
System armed in Stay mode
FLT
One or more system faults are present
MANUAL ELDES ESIM364 V1.0
32.1.1.6. Menu Tree
MAIN SCREEN VIEW
P1
P2
[1] part-name...
[4] part-name
OK
uuu
VIOLATED ZONES
BYPASS
VIOLATED TAMPERS
BYP VIOLATED ZONES
Z1-zone-name...
Z12-zone-name
FAULTS
BYPASS LIST 1
UNBYPASS | BYPASS
Z13-zone-name...
Z76-zone-name
TAMPER 1... 76
BATTERY DEAD/MISS | BATTERY FAILED | SIREN FAILED |
GSM CONNECT FAILED | GSM ANTENNA FAILED | VIOLATED
TAMPER | MAIN POWER LOSS | DATE/TIME NOT SET | LOW
BATTERY | WLESS SIGNAL LOST
DATE/TIME SETTINGS
yyyy-mm-dd hr:mn
TEMP SENSORS INFO
1. tm.p C (PRIM) | (SEC)... 8. tm.p C
BYPASS LIST 2
CONFIGURATION
UNBYPASS | BYPASS
Z13-zone-name...
Z76-zone-name
ZONE 1... 76
aaaa
BYPASS LIST 3
PHONE NUMBER
ttteeellnnuumm
ENTER ADMIN PSW
PARTITION
UNBYPASS | BYPASS
15 digits pv
PRIMARY SETTINGS
SEND ARM/DARM SMS
Z13-zone-name...
Z76-zone-name
CALL/SMS SETTINGS
BYPASS LIST 4
UNBYPASS | BYPASS
Z13-zone-name...
Z76-zone-name
USERS
BYPASS LIST 5
WIRELESS DEVICES 1... 2
UNBYPASS | BYPASS
wless-dev wless-id
BATTERY
DISABLE | ENABLE
USER 1... 10
SEND ARM/DARM ALL
DISABLE | ENABLE
SEND ALARM SMS ALL
DISABLE | ENABLE
CALL IN CASE ALARM
DISABLE | ENABLE
CTRL FROM ANY NUM
DISABLE | ENABLE
SIGNAL
PASSWORDS
ERROR RATE
SMS PASSWORD
FW RELEASE
IBUTTON KEYS
NEW IBUTTON
DISABLE | ENABLE
[0001... 9999]
ADMIN PASSWORD
[0001... 9999]
USER PSW (1-16)
PASSWORD
IBUTTON 1... 5
ID
PARTITION
PARTITION
pv
USER PSW (17-30)
PASSWORD
pv
[0001... 9999]
USER PASSWORD 1... 16
[0001... 9999]
USER PASSWORD 17... 30
PARTITION
pv
REMOVE
DURESS PASSWORD
SGS PASSWORD
N/A | 1... 10
N/A | 1... 10
REMOVE PASSWORD
[0001... 9999]
Continued in next page
MANUAL ELDES ESIM364 V1.0
EN
121
NAME
DISABLE |
ENABLE
seconds
ZONE 1... 12
ONBOARD ZONES
STATUS
TYPE
ENTRY DELAY
[1... 65535]
WIRELESS ZONE 13... 76
FOLLOW |
INSTANT | 24H
| DELAY | FIRE |
SILENT
WIRELESS ZONES 1... 4
NAME
ENGLISH | second-lang
DATE/TIME SETTINGS
yyyy-mm-dd hr:mn
INFO SMS SCHEDULER
[0... 99]
FREQUENCY (DAYS)
TIME
EVENT LOG
DISABLE | ENABLE
[0... 23]
DISABLE | ENABLE
TEMPERATURE SENS 1... 8
FOLLOW | INSTANT | 24H | DELAY | FIRE | SILENT
ENTRY DELAY
STAY
SMS LANGUAGE
TEMP SENSORS
STATUS
TYPE
PRIMARY SETTINGS
ZONES
CONFIGURATION
Continued from previous page
[1... 65535]
DISABLE | ENABLE
PRIMARY
TEMP SENS
TEMP. MIN
[-55... +125]
TEMP. MAX
1... 8 PRIM | SEC
| CONNECTED
[-55... +125]
°C
°C
NAME
seconds
PRIMARY TEMP SENS
1... 8 PRIM | SEC | CONNECTED
TAMPER NAME
EXIT DELAY
PARTITION
PARTITION 1... 4
[0... 600]
pv
SIREN SETTINGS
FORCE
DISABLE | ENABLE
ALARM DURATION
1ST... 4TH KEYPAD ZONE
KEYPAD ZONES
NAME
DISABLE | ENABLE
FOLLOW | INSTANT | 24H | DELAY | FIRE | SILENT
ENTRY DELAY
STAY
EWS2 LED
PARTITION
FORCE
DISABLE | ENABLE
LOSS DELAY
seconds
TAMPER NAME
seconds
[0... 65535]
seconds
KEYPAD PARTITION
PARTITION SWITCH
DISABLE | ENABLE
DISABLE | ENABLE
KEYPAD PARTITION
EPGM1 ZONES 1-16
NAME
[1] EKB2 | NOT USED...
[4] EKB2 | NOT USED
PARTITION
1... 4
[1] EKB3 | NOT USED...
[4] EKB3 | NOT USED
PARTITION
1... 2
DISABLE | ENABLE
STATUS
EKB3W PARTITION
FOLLOW | INSTANT | 24H | DELAY | FIRE | SILENT
ENTRY DELAY
STAY
[0... 65535]
RESTORE DELAY
pv
EPGM1 ZONE 1... 16
TYPE
DISABLE | ENABLE
MAIN POWER STATUS
[1... 65535]
DISABLE | ENABLE
minutes
DISABLE | ENABLE
SRN IF WLESS LOSS
STATUS
TYPE
BELL SQUAWK
[1... 10]
EKB3W wless-id | NOT USED
PARTITION 1... 2
GSM AUDIO
[1... 65535]
MICROPHONE GAIN
DISABLE | ENABLE
[0... 15]
seconds
SPEAKER LEVEL
[0... 100]
TAMPER NAME
PARTITION
FORCE
pv
DISABLE | ENABLE
Continued in next page
122
EN
MANUAL ELDES ESIM364 V1.0
EPGM1 ZONES 17-32
NAME
MS SETTINGS
ACCOUNT
DELAY LAST ATTEMPT
DISABLE | ENABLE
STATUS
TYPE
CONFIGURATION
EPGM1 ZONE 17... 32
ZONES
Continued from previous page
MS MODE
[1... 65535]
seconds
DISABLE | ENABLE
FOLLOW | INSTANT | 24H | DELAY | FIRE | SILENT
BURGLR ALM/REST EV
DATA MESSAGES 1
ENTRY DELAY
STAY
[1... 65535]
DISABLE | ENABLE
MAIN POWER L/R EV
seconds
DISABLE | ENABLE
TAMPER NAME
PARTITION
FORCE
pv
DISABLE | ENABLE
ARM/DISARM EVENT
DISABLE | ENABLE
DISABLE | ENABLE
BATTERY FAILED
BATTERY DEAD/MISS
DISABLE | ENABLE
DISABLE | ENABLE
TEST EVENT
DISABLE | ENABLE
ATZ MODE
TAMPER ALM/REST EV
DISABLE | ENABLE
DISABLE | ENABLE
SILENT ALM/REST EV
TYPE 1... 3
ZONE TYPE:6-ZONE M
TYPE 4... 5
ZONE TYPE:ATZ MODE
N/A / ZONE 1... 12
ARM/DISARM BY ZONE
SYSTEM STARTED EV
DISABLE | ENABLE
DISABLE | ENABLE
FIRE ALM/REST EV
24H ALM/REST EVENT
DISABLE | ENABLE
DISABLE | ENABLE
LOW BATTERY EVENT
CHIME
DISABLE | ENABLE
PGM OUTPUTS
USING EPGM8
DISABLE | ENABLE
TEMP HIGH EVENT
DISABLE | ENABLE
DISABLE | ENABLE
TEMP LOW EVENT
WLESS SIGN L/R EV
DISABLE | ENABLE
DISABLE | ENABLE
ONBOARD OUTPUTS
ARM/DARM DURESS EV
DATA MESSAGES 2
OUTPUT 1... 12
STATUS
DISABLE | ENABLE
DISABLE | ENABLE
ARM/DARM SGS EVENT
NAME
WIRELESS OUTPUT 13... 76
WIRELESS OUTPUTS 1... 4
ARM/DARM STAY EV
DISABLE | ENABLE
DISABLE | ENABLE
SIREN FAIL/REST EV
DISABLE
| ENABLE
STATUS
GSM CONNECT FAILED
DISABLE | ENABLE
DISABLE | ENABLE
NAME
DATE/TIME NOT SET
wless-dev wless-id
BATTERY
SIGNAL
WIRELESS DEVICES 1... 2
ERROR RATE
FW RELEASE
SYSTEM SHUTDOWN EV
DISABLE | ENABLE
DISABLE | ENABLE
GSM ANT FAIL/REST
GPRS CONNECT FAIL
DISABLE | ENABLE
GPRS SETTINGS
[0.0.0.0]
SERVER IP
LOCAL PORT
[0.0.0.0]
DNS1
APN
[0.0.0.0]
DNS2
USER
TCP | UDP
[1... 65535]
PROTOCOL
SERVER PORT
KEYPAD FAIL/REST
[1... 65535]
DISABLE | ENABLE
VOICE CALLS/SMS ST
ATTEMPTS
PASSWORD
[1... 10]
TEL. NUMBER1
ttteeellnnuumm
15 digits
TEL. NUMBER2
ttteeellnnuumm
15 digits
TEL. NUMBER3
ttteeellnnuumm
15 digits
PROFILE
Continued in next page
MANUAL ELDES ESIM364 V1.0
EN
123
SYS ARMED EVENT
DISABLE | ENABLE
MS SETTINGS
SMS MESSAGES 1
CONFIGURATION
Continued from previous page
PSTN SETTINGS
ATTEMPTS
[1... 10]
TEL. NUMBER1
ttteeellnnuumm
15 digits
TEL. NUMBER2
ttteeellnnuumm
15 digits
TEL. NUMBER3
ttteeellnnuumm
15 digits
SYS DISARMED EVENT
DISABLE | ENABLE
DISABLE | ENABLE
GENERAL ALARM EV
DISABLE | ENABLE
MAIN POWER L/R EV
CSD SETTINGS
DISABLE | ENABLE
BATTERY FAILED
ATTEMPTS
DISABLE | ENABLE
BATTERY DEAD/MISS
DISABLE | ENABLE
LOW BATTERY EVENT
TEL. NUMBER1
ttteeellnnuumm
15 digits
TEL. NUMBER2
ttteeellnnuumm
15 digits
TEL. NUMBER3
ttteeellnnuumm
15 digits
TEL. NUMBER4
ttteeellnnuumm
15 digits
TEL. NUMBER5
ttteeellnnuumm
15 digits
SIREN FAIL/REST EV
DISABLE | ENABLE
SMS MESSAGES 2
DATE/TIME NOT SET
DISABLE | ENABLE
DISABLE | ENABLE
[1... 10]
GSM CONNECT FAILED
DISABLE | ENABLE
GSM ANT FAIL/REST
DISABLE | ENABLE
TAMPER ALARM
GPRS ATTEMPTS
KEYPAD FAILED
UNIT ID
DISABLE | ENABLE
DISABLE | ENABLE
GPRS SETTINGS
TEMP INFO EVENT
DISABLE | ENABLE
SYSTEM STARTED EV
DISABLE | ENABLE
PERIOD INFO SMS EV
DISABLE | ENABLE
WLESS SIGN LOSS EV
[0... 255]
[0000... 9999]
TEST PERIOD
[0... 65535]
seconds
PRIMARY CONNECTION
GPRS | VOICE CALLS | RS485 | CSD | PSTN | SMS | N/A
BACKUP CONNECTION1
GPRS | VOICE CALLS | RS485 | CSD | PSTN | SMS | N/A
ENTER USER PSW
uuuu
RESET TO DEFAULT
BACKUP CONNECTION2
GPRS | VOICE CALLS | RS485 | CSD | PSTN | SMS | N/A
BACKUP CONNECTION3
GPRS | VOICE CALLS | RS485 | CSD | PSTN | SMS | N/A
BACKUP CONNECTION4
GPRS | VOICE CALLS | RS485 | CSD | PSTN | SMS | N/A
BACKUP CONNECTION5
GPRS | VOICE CALLS | RS485 | CSD | PSTN | SMS | N/A
124
EN
MANUAL ELDES ESIM364 V1.0
32.1.2. EKB3 - LED Keypad
EKB3 is a LED keypad intended for using with ESIM364 alarm system.
Main EKB3 features:
t
Alarm system arming and disarming (see 12.4. EKB3/EKB3W Keypad and User Password).
t
Arming and disarming in Stay mode (see 15. STAY MODE).
t
System parameter configuration (see 5. CONFIGURATION METHODS).
t
PGM output control (see 18.4. Turning PGM Outputs ON and OFF).
t
Visual indication by LED indicators (see 32.1.2.3. Visual and Audio Indications).
t
Audio indication by built-in buzzer (see 32.1.2.3. Visual and Audio Indications).
t
Keypad partition switch (see 23.3. Keypad Partition and Keypad Partition Switch).
The system configuration by EKB3 keypad is performed by activating the Configuration mode (see 5. CONFIGURATION METHODS) and entering the required parameters & values. ESIM364 system allows to connect up to 4 EKB3 keypads.
32.1.2.1. Technical Specifications
32.1.2.1.1 Electrical & Mechanical Characteristics
Power Supply
12-14V
150mA max
Maximum Keypad Connection Cable Length
100 m.
Dimensions
140x100x18mm
Range of Operating Temperatures
-30...+55ºC
32.1.2.1.2 LED Funcionality
ARMED
Alarm system is armed /Configuration mode
READY
System is prepared for arming
SYSTEM
System faults / valid command is being entered
BYPS
Zone bypass mode
1-12
Violated zone
32.1.2.1.3 Keys Functionality
[BYPS]
Zone bypass mode
[CODE]
Additional options - system trouble fault indication / violated high zone indication / violated tamper indication
[*]
Configuration mode (when typed as a 1st character) / cancel command (when typed as a 2nd character) / keypad partition
switch (if enabled)
[#]
Confirm (enter) command
[0] ... [9]
Command typing
[STAY]
Manual system arming in Stay mode
[INST]
(currently inactive)
32.1.2.1.4 Connector Functionality
MANUAL ELDES ESIM364 V1.0
EN
125
AUX+
Positive power supply terminal
AUX-
Negative power supply terminal
G
RS485 interface for communication (green wire)
Y
RS485 interface for communication (yellow wire)
COM
Common terminal for Z1
Z1
Security zone terminal
Z2
N/A
BACK SIDE
FRONT SIDE
45
A
B
ARMED
READY
SYSTEM
1
BYPS
7
8
2
5
10
3
STAY
4
5
6
BYPS
7
8
9
INST
*
0
#
CODE
11
12
6
2
9
3
4
1
TAMPER
ON
OFF
DIP SWITCH
COM Y AUXZ2
Z1
G AUX+
32.1.2.1.5 Keypad Address
DIP switches located on the back side of the keypad are intended to set keypad address. The keypad address is configured by setting the DIP
switch positions. ESIM364 alarm system allows to connect up to 4 EKB3 keypads - each set under different address. DIP switch combinations
for different keypad address configuration are indicated in the table below.
Address Configuration
DIP switch position
Address
ON
OFF
Keypad 1
ON
OFF
Keypad 2
ON
OFF
Keypad 3
ON
OFF
Keypad 4
NOTE: Third switch is not active, therefore its’ position is irrelevant.
The address of each connected keypad is also indicated in ELDES Configuration Tool software.
32.1.2.2. Installation
1.
Detach keypad holder from EKB3 keypad . Keypad holder detach points are marked with arrows (see Fig. No. 46).
126
EN
MANUAL ELDES ESIM364 V1.0
46
DOWN SIDE
BACK SIDE
MANUAL ELDES ESIM364 V1.0
EN
127
2. Disconnect alarm system ESIM364 power supply and backup battery before connecting the wires.
47
ESIM364
Y G
AUX- AUX+
EKB3
COM Y AUXZ2 Z1
G AUX+
5,6kΩ
3.
Wire up keypad terminals to ESIM364 alarm system respectively – AUX+ to AUX+, AUX- to AUX-, Y to Y, G to G. (see Fig. No. 47).
4. Z1 and COM terminals must be connected with resistor of 5,6kΩ nominal (see Fig. No. 20). As keypad zone Z1 is disabled by default, it can
be enabled by SMS, ELDES Configuration Tool, EKB2, EKB3 and EKB3W keypad. Z2 terminal is permanently inactive. Keypad zone Z1 must
be enabled and resistor connected even if the tamper button alone is required.
5.
Set the keypad address by combining DIP switch positions (see 32.1.2.1.5 Keypad Address).
6.
Infix the keypad into the holder (see Fig. No. 46).
7.
Power up ESIM364 alarm system.
ATTENTION: Before fixing the keypad into the holder please , make sure that the tamper is properly pressed (see Fig. No. 45).
8. EKB3 keypad is ready.
For more details on multiple keypad wiring, please refer to 3.2.7. RS485.
32.1.2.3. Visual and Audio Indications
EKB3 keys have a LED back-light, therefore it is possible to use this keypad even in dark premises. The back-light lasts for 3 minutes after the
last key-stroke while the system is disarmed. In case of alarm, the keypad back-light turns ON and lasts until the system is disarmed.
The built-in buzzer uses two types of sound signals – three short beeps and one long beep. Three short beeps stand for successfully carried
out configuration command, one long beep – for invalid configuration command. In addition, the buzzer emits short beeps in case of alarm.
32.1.2.4. EKB3 Zone & Tamper
Keypad EKB3 has one wired zone Z1 and one tamper button. By default, the keypad zone Z1 is disabled. The keypad zone can be enabled by
SMS, EKB2 keypad, EKB3 keypad, EKB3W keypad and ELDES Configuration Tool software (see 14.9. Disabling and Enabling Zones). Zone
Z1 is enabled, it operates like any other system zone, therefore a sensor can be connected to it. In addition, Z1 and COM terminals must be
connected with resistor of 5,6kΩ nominal.
The tamper button is intended for monitoring the enclosure status of EKB3, therefore the system causes alarm if the enclosure is illegally
opened. Keypad zone Z1 must be enabled and resistor connected even if the tamper button alone is required.
32.1.3. EPGM1 - Hardwired Zone & PGM Output Expansion Module
EPGM1 is a hardwired zone & PGM output expansion module intended for using with ELDES alarm systems.
Main EPGM1 features:
t )BSEXJSFE[POFFYQBOTJPO&BDINPEVMFBEETBEEJUJPOBM[POFT
t )BSEXJSFE1(.PVUQVUFYQBOTJPO&BDINPEVMFBEETBEEJUJPOBM1(.PVUQVUTGPSFMFDUSJDBMBQQMJBODFDPOOFDUJPO
t 6QUPIBSEXJSFE[POFBOEVQUPIBSEXJSFE1(.PVUQVUFYQBOTJPO
128
EN
MANUAL ELDES ESIM364 V1.0
32.1.3.1. Technical Specifications
32.1.3.1.1 Electrical & Mechanical Characteristics
Power Supply
Number of Digital Inputs
Nominal Resistance
Number of PGM Outputs
Maximum PGM Output Current
EPGM1 PGM Output Circuit
10-24V
16
5,6kΩ
2
250 mA
100mA max without auxiliary equipment.
Maximum Commuting PGM Output Values
AUX: Auxiliary Equipment Power Supply
Dimensions
Range of Operating Temperatures
Voltage – 30V; current 250mA
13,8V
500 mA max
118 x 47 mm
-20...+55ºC
1R
OUT
Open collector output.
Output is pulled to
COM when turned on.
32.1.3.1.2 LED and Pin Functionality
C2, C1
Z1 - Z16
STATUS
ADR
PGM output C1, C2 status – on/off
Zone Z1 - Z16 state – alarm/restore
EPGM1 micro-controller status
EPGM1 module address pins
32.1.3.1.3 Connector Funcionality
C1, C2
Z1 - Z16
AUXAUX+
Y
G
COM
DC+
PGM output terminals
Security zone terminals
Negative power supply terminal for auxiliary equipment
Positive power supply terminal for auxiliary equipment
RS485 interface for communication (yellow wire)
RS485 interface for communication (green wire)
Negative power supply terminal
Positive power supply terminal
48
C2
C1
Z1 Z2 Z3 Z4 Z5 Z6 Z7 Z8 Z9 Z10 Z11 Z12 Z13 Z14 Z15 Z16
STATUS
ADR
C1 C2 COM Z1 COM Z2 Z3 COM Z4 Z5 COM Z6 Z7 COM Z8 Z9 COM Z10 Z11 COM Z12 Z13COM Z14 Z15COM Z16 -AUX+ COM DC+ Y
MANUAL ELDES ESIM364 V1.0
G
EN
129
49
C2
C1
Z1 Z2 Z3 Z4 Z5 Z6 Z7 Z8 Z9 Z10 Z11 Z12 Z13 Z14 Z15 Z16
STATUS
EPGM1
ADR
C1 C2 COM Z1 COM Z2 Z3 COM Z4 Z5 COM Z6 Z7 COM Z8 Z9 COM Z10 Z11 COM Z12 Z13COM Z14 Z15COM Z16 -AUX+ COM DC+ Y
Z16
Z15
Z14
Z13
Z12
Z11
Z10
Z9
Z8
Z7
Z5
Z6
Z4
Z3
Z1
Z2
5,6 kΩ
5,6 kΩ
5,6 kΩ
5,6 kΩ
5,6 kΩ
5,6 kΩ
5,6 kΩ
5,6 kΩ
5,6 kΩ
5,6 kΩ
5,6 kΩ
5,6 kΩ
5,6 kΩ
5,6 kΩ
5,6 kΩ
5,6 kΩ
RELAY
MODULE
G
AUX+
AUX-
G
Y
ESIM364
32.1.3.1.4 EPGM1 Address
ESIM364 system allows to connect up to 2 EPGM1 modules - each set under different address. The module address can be set by putting or
removing the jumper from the A0 and A1 pins implemented in vertical position (see Fig. No. 48). Jumper combinations for different EPGM1
module address configuration are indicated in the table below.
Address Configuration
Jumper position
130
EN
Address
ADR
Module 1
ADR
Module 2
MANUAL ELDES ESIM364 V1.0
32.1.3.2. Installation
1.
Disconnect ESIM364 alarm system main power supply and backup battery.
2.
Connect EPGM1 DC+ terminal to ESIM364 AUX+ terminal, EPGM1 COM terminal to ESIM364 AUX- terminal, EPGM1 Y and G termianls
must be connected to ESIM364 Y and G terminals respectively (see Fig. No. 49).
3.
Connect the resistors and sensors to EPGM1 module according to zone connection Type 1, Type 2 or Type 3. See 2.3.2 Zone Connection Types.
4. Set the EPGM1 module address by putting or removing the jumper from the ADR pins (see 32.1.3.1.4. EPGM1 Address).
5.
Power up ESIM364 system.
6.
Upon successful startup indicator STATUS should be blinking indicating successful EPGM1 operation.
7.
E PGM1 is ready for use with ESIM364 alarm system.
For more details on multiple EPGM1 module wiring, please refer to 3.2.7. RS485
32.2. 1-Wire Interface
1-Wire interface is used for the system to communicate with an iButton key reader and up to 8 temperature sensors. 1-Wire interface COM
and DATA terminals are ground and data respectively. When connecting single or multiple temperature sensors, the +5V terminal must be
used along.
For more details on 1-Wire device wiring, please refer to 32.2.1 iButton Key Reader and Buzzer
32.2.1. iButton Key Reader and Keys
The iButton key is a chip enclosed in a stainless steel tab usually implemented in a small plastic holder. Each iButton key holds a unique
identity code (ID) which is used for alarm system ESIM364 arming and disarming procedure.
Main iButton features:
t 6QUPJ#VUUPOLFZTQFSBMBSNTZTUFNVOJU&4*.
t $PNNVOJDBUJPOWJB8JSFJOUFSGBDF
32.2.1.1. Technical Specifications
32.2.1.1.1
Electrical & Mechanical Characteristics
Supported iButton Key Model
Communication Interface
Maximum Cable Length for 1-Wire Communication
Maxim/Dallas DS1990A
1-Wire
up to 30 meters
32.2.1.1.2 Installation
1. Disconnect ESIM364 alarm system main power supply and backup battery.
2. Connect iButton key reader contact wires to 1-Wire interface on ESIM364 alarm system: COM and DATA terminals respectively.
DATA
COM
50
iButton
key reader
3. Power up ESIM364 alarm system.
4 iButton® key reader is ready for use with ESIM364 alarm system.
For more details on iButton key management, please refer to 11. iBUTTON KEYS.
MANUAL ELDES ESIM364 V1.0
EN
131
32.3. Modules Interface
32.3.1. EPGM8 - Hardwired PGM Output Expansion Module
EPGM8 is a PGM output expansion module intended for using with alarm system ESIM364. This module allows to connect up to additional
8 electrical appliances.
Main EPGM8 features:
t 1(.PVUQVUFYQBOTJPOBEEJOHBEEJUJPOBM1(.PVUQVUT
t $PNQBUJCMFXJUI&4*.BMBSNTZTUFN
32.3.1.1. Technical Specifications
32.3.1.1.1
Electrical & Mechanical Characteristics
Power Supply
Number of PGM Outputs
EPGM8 PGM Output Circuit
10-24V
8
100mA max
Maximum Commuting PGM Output Values
Dimensions
Range of Operating Temperatures
Voltage – 30V; current 500mA
40 x 55 x 15 mm
-20...+55ºC
1R
OUT
Open collector output.
Output is pulled to COM
when turned on.
32.3.1.1.2 Connector Functionality
PGM output terminals
Positive power supply terminal
Negative power supply terminal
51
12V GND
D1 - D8
12V
GND
D1 D2 D3 D4 D5 D6 D7 D8
132
EN
MANUAL ELDES ESIM364 V1.0
32.3.1.2. Installation
1. Disconnect ESIM364 alarm system main power supply and backup battery.
2. Insert EPGM8 pins into appropriate ESIM364 alarm system slots (see Fig. No. 52)
OPEN
S TA T
C4
C3
C2
C1
NE TW
52
GSM ANT
C 4C 3
OPEN
W-LESS ANT
G SM
M
O DE
DE M
MO
DEF
12V GND
EPGM8
ESIM364
MODULES
TIP RING
D1 D2 D3 D4 D5 D6 D7 D8
AK U +
AK U -
AC /DC
AC /DC
AUX+
AUXBELL+
BELL-
CO M
G
Y
C2
C1
BU Z +
BU Z MIC +
M IC +5V
DAT A
CO M
Z6
CO M
Z5
Z4
CO M
Z3
Z2
CO M
Z1
3.
FUSE F1
3A
PRG
USB
Connect EPGM8 12V positive power supply terminal with ESIM364 alarm system AUX+ terminal and EPGM8 GND terminal with
ESIM364 alarm system AUX- terminal. (see Fig. No. 52).
4. Connect the electrical appliances to D1 – D8 PGM outputs. (see Fig. No. 53).
53
ESIM364
AUX+
12V GND
AUX-
D1 D2 D3 D4 D5 D6 D7 D8
El. Appliance 1
TO AUX+
El. Appliance 2
TO AUX+
El. Appliance 3
TO AUX+
El. Appliance 4
TO AUX+
El. Appliance 5
TO AUX+
El. Appliance 6
TO AUX+
El. Appliance 7
TO AUX+
El. Appliance 8
TO AUX+
5.
Power up ESIM364 alarm system.
6.
Enable EPGM8 mode using EKB2, EKB3, EKB3W keypads or ELDES Configuration Tool software. For more details, please refer to
software’s HELP section or 18.2.1. EPGM8 Mode.
7.
EPGM8 is ready for use with ESIM364 alarm system.
MANUAL ELDES ESIM364 V1.0
EN
133
32.3.2. EA1 – Audio Output Module
EA1 audio output module enables a duplex audio connection for ESIM364 alarm system.
Main EA1 features:
t
5XPXBZWPJDFDPOWFSTBUJPOEVSJOHBQIPOFDBMM
t 1PTTJCJMJUZUPDPOOFDUIFBEQIPOFTPSEFTLUPQTQFBLFST
32.3.2.1. Technical Specifications
t NNGFNBMFKBDL
t %JNFOTJPOTYYNN
32.3.2.2. Installation
1. Disconnect ESIM364 alarm system main power supply and backup battery.
S TA T
C4
C3
C2
C1
NE TW
54
GSM ANT
C 4C 3
OPEN
W-LESS ANT
OPEN
2. Insert EA1 pins into appropriate ESIM364 alarm system slots.
G SM
M O DE
DE M
MO
DEF
USB
ESIM364
FUSE F1
3A
PRG
EA1
MODULES
TIP RING
AK U +
AK U -
AC /DC
AC /DC
AUX+
AUXBELL+
BELL-
CO M
G
Y
C2
C1
BU Z +
BU Z MIC +
M IC +5V
DAT A
CO M
Z6
CO M
Z5
Z4
CO M
Z3
Z2
CO M
Z1
3. Connect headphones or desktop speakers to EA1 3,5 mm female jack.
55
EA1
4. Power up ESIM364 alarm system.
5. EA1 is ready for use with ESIM364 alarm system.
134
EN
MANUAL ELDES ESIM364 V1.0
32.3.3. EA2 – Audio Output Module with Amplifier
EA2 audio output module enables a duplex audio connection for ESIM364 alarm system.
Main EA2 features:
t 5XPXBZWPJDFDPOWFSTBUJPOEVSJOHBQIPOFDBMM
t 1PTTJCJMJUZUPDPOOFDUBTQFBLFS
32.3.3.1. Technical Specifications
t8ƲBVEJPBNQMJmFS
t%JNFOTJPOTYYNN
32.3.3.2. Installation
1. Disconnect ESIM364 alarm system main power supply and backup battery.
S TA T
C4
C3
C2
C1
NE TW
56
GSM ANT
C 4C 3
OPEN
W-LESS ANT
OPEN
2. Insert EA2 pins into appropriate ESIM364 alarm system slots.
G SM
MO DE M
DEF
FUSE F1
3A
PRG
USB
ESIM364
MODULES
TIP RING
EA2
AK U +
AK U -
AC /DC
AC /DC
AUX+
AUXBELL+
BELL-
CO M
G
Y
C2
C1
BU Z +
BU Z MIC +
M IC +5V
DAT A
CO M
Z6
CO M
Z5
Z4
CO M
Z3
Z2
CO M
Z1
3. Connect a speaker to EA2 Speaker terminals.
57
EA2
4. Power up ESIM364 alarm system.
5. EA2 is ready for use with ESIM364 alarm system.
MANUAL ELDES ESIM364 V1.0
EN
135
33. ELDES WIRELESS DEVICES
33.1. EKB3W - Wireless LED Keypad
EKB3W is a wireless LED keypad intended to use with ELDES alarm systems.
Main EKB3W features:
t
Alarm system arming and disarming (see 12.4. EKB3/EKB3W Keypad and User Password).
t
Arming and disarming in Stay mode (see 15. STAY MODE).
t
System parameter configuration (see 5. CONFIGURATION METHODS).
t
PGM output control (see 18.4. Turning PGM Outputs ON and OFF).
t
Visual indication by LED indicators (see 33.1.5. Visual and Audio Indications).
t
Audio indication by built-in buzzer (see 33.1.5. Visual and Audio Indications).
t
Keypad partition switch (see 23.3. Keypad Partition and Keypad Partition Switch).
The system configuration by EKB3W keypad is performed by activating the Configuration mode (see 5. CONFIGURATION METHODS) and
entering the required parameters & values. ESIM364 system allows to connect up to 4 EKB3W keypads.
33.1.1. Technical Specifications
33.1.1.1. Electrical & Mechanical Characteristics
Battery Type
Number of Batteries
Battery Operation Time
Wireless Transmitter-Receiver Frequency
Range of Operating Temperatures
Dimensions
Wireless Communication Range
Compatible with Alarm Systems
1,5V Alkaline AAA type
3
~12 months*
868 Mhz
-30...+55ºC
140 x 100 x 18 mm
Up to 30 meters in premises; up to 150 meters in open areas
ELDES Wireless
* This operating time may vary in different conditions.
33.1.1.2. LED Functionality
ARMED
READY
SYSTEM
BYPS
1-12
Security system is armed /Configuration mode
System is ready – no violated zones and tampers
System troubles / valid command is being entered
Zone bypass mode
Violated zone
33.1.1.3. Keys Functionality
[BYPS]
[CODE]
[*]
[#]
[0] ... [9]
[STAY]
[INST]
136
EN
Zone bypass mode
Additional options - system fault indication / violated high zone indication / violated tamper indication
Configuration mode (when typed as a 1st character) / cancel command (when typed as a 2nd character) / keypad partition
switch (if enabled)
Confirm (enter) command
Command typing
Manual system arming in Stay mode
(currently inactive)
MANUAL ELDES ESIM364 V1.0
33.1.1.4. Main Unit & Connector Functionality
BACK SIDE
FRONT SIDE
58
A
B
ARMED
READY
SYSTEM
1
BYPS
7
8
2
5
6
2
3
STAY
4
5
6
BYPS
7
8
9
INST
*
0
#
CODE
+
BATTERY
-
-
BATTERY
+
+
BATTERY
-
9
3
4
1
10
TAMPER
11
12
5,6 kOhm
Z1 COM
TAMPER
+/-
Tamper-button for EKB3W
enclosure status monitoring
Battery slots
COM
Z1
Common contact
Security zone terminal
33.1.2. Installation
1.
Detach keypad holder from EKB3W front side . Keypad holder detach points are marked with arrows (see Fig. No. 59).
59
DOWN SIDE
BACK SIDE
2.
Fix the keypad holder on the wall using the screws.
3.
Z1 and COM terminals must be connected with resistor of 5,6kΩ nominal (see Fig. No. 29). As keypad zone Z1 is disabled by default, it can
be enabled by SMS, EKB3W keypad and ELDES Configuration Tool software. Keypad zone Z1 must be enabled and resistor connected even
if the tamper button alone is required.
4. Remove the plastic tab inserted between one of the battery terminals and battery slot contacts (see Fig. No. 60).
60
ATTENTION: Before fixing the keypad into the holder please , make sure that the tamper is properly pressed (see Fig. No. 45).
5.
Bind the device to the alarm system by sending a corresponding command via SMS text message or using ELDES Configuration Tool software. Please, refer to the software‘s HELP section or refer to 19.1. Binding, Removing and Replacing Wireless Devices for more
details. The system automatically informs about successful/unsuccessful binding process. If attempt to bind is unsuccessful, try to move
EKB3W closer to alarm system device and bind it again.
7.
Upon the successful binding process, the built-in mini buzzer of EKB3W device provides 3 short beeps and the system automatically informs about successful/unsuccessful binding process. If attempt to bind is unsuccessful, try to move EKB3W closer to alarm system device
and bind anew.
8. EKB3W keypad is ready for use.
NOTE: If you are unable to bind the wireless device please , restore the parameters of the wireless device to default and try again. See
33.1.6. Restoring Default Parameters for more details.
ATTENTION: The minimum wireless connection range between the wireless device and wireless antenna of ESIM364 system can be 0,5
meters.
MANUAL ELDES ESIM364 V1.0
EN
137
33.1.3. EKB3W Zone & Tamper
Upon successful EKB3W wireless LED keypad contact binding process, the system adds 1 wireless Instant zone intended for wired sensor connection. By default, the keypad zone Z1 is disabled. The keypad zone can be enabled by SMS, EKB2 keypad, EKB3 keypad, EKB3W keypad and
ELDES Configuration Tool. software (see 14.9. Disabling and Enabling Zones). When Z1 is enabled, it operates like any other system zone,
therefore a sensor can be connected to it. In addition, Z1 and COM terminals must be connected with resistor of 5,6kΩ nominal.
In case of tamper violation, the alarm is caused regardless of system being armed or disarmed. There are 2 ways to detect tamper violation
on EKB3W:
t By tamper button. EKB3W has a built-in tamper button intended for monitoring the enclosure status. Once the enclosure of EKB3W is
illegally opened, the tamper button becomes unpressed. This action is followed by alarm which is sent by SMS text message and phone
call to the user (-s) by default. The SMS text message contains the violated tamper number.
t
By wireless connection loss. The wireless connection loss between EKB3W and ESIM364 alarm system leads to alarm. The system
identifies this event as a tamper violation and sends alarm by SMS text message and phone call to the user (-s) by default. The SMS text
message contains the violated tamper number and a star * character indicating wireless connection loss as a tamper alarm cause.
ATTENTION: The tamper will not operate if the wireless zone is disabled.
33.1.4. Battery Replacement
1.
Open EKB3W enclosure.
2.
Remove all 3 old batteries from the battery slots.
3.
Postition the 3 new 1,5V alkaline AAA type batteries according to the appropriate battery slot positive/negative terminals indicated on
the PCB (printed-circuit-board) of EKB3W.
4. Insert the batteries into the battery slots.
5.
Batteries replaced.
For more details, please refer to 33.1.2. Installation.
ATTENTION: Only 1,5V Alkaline AAA type batteries can be used. Install only new, high quality and unexpired batteries. Do not
mix the old batteries with the new ones.
ATTENTION: At least 1 battery must be removed if the device is not in use.
ATTENTION: In order to avoid fire or explosion hazards, the system must be used only with approved battery. Special care must
be taken when connecting positive and negative battery terminals. Dispose old batteries only into special collection sites. Do not
charge, disassemble, heat or incinerate old batteries.
NOTE: The system sends an SMS message to a preset User 1 as soon as the battery level runs below 5%.
NOTE: The battery status can be monitored in real-time using ELDES Configuration Tool software.
33.1.5. Visual and Audio Indications
EKB3W keys have a LED back-light, which will be activated once any key is pressed. Due to battery power saving reasons, the back-light and
LED light last for 10 seconds after the last key-stroke.
The built-in buzzer uses two types of sound signals – three short beeps and one long beep. Three short beeps stand for successfully carried
out configuration command, one long beep – for invalid configuration command. In addition, the buzzer emits short beeps in case of alarm.
NOTE: The keypad will not activate any LED indicators, nor the back-light if not bound to the system.
138
EN
MANUAL ELDES ESIM364 V1.0
33.1.6. Restoring Default Parameters
1.
Remove one battery from EKB3W.
2.
Press and hold the [*] key.
3.
Insert the battery back to EKB3W.
4. Hold the [*] key until LED READY starts flashing.
5.
Wait until LED READY turns off and LED ARMED starts flashing.
6.
Release the [*] key.
7.
Parameters reset to default.D
33.2. EW1 - Wireless Zone & PGM Output Expansion Module
Main EW1B features:
t
2 zones for wired sensor connection;
t
2 PGM outputs for electrical appliance connection;
t
Powered by external power supply.
Wireless expansion module EW1 is a wireless device with 2 zones and 2 PGM outputs. This expansion module connects to ELDES wireless
alarm systems and enables wireless access for to 2 wired devices such as movement PIR sensors, magnetic door contacts etc. In addition it
allows to connect and control up to 2 appliances, i.e. lighting, heating etc. After the wiring process to EW1 it is necessary to bind EW1 to the
alarm system by sending a corresponding command via SMS text message or using software ELDES Configuration Tool.
It is possible to connect up to 32 EW1 devices to ESIM364 alarm system at a time. The maximum wireless connection range is 150 meters (in
open areas).
33.2.1. Technical Specifications
33.2.1.1. Electrical & Mechanical Characteristics
Power Supply
Number of Zones
Zone Connection Type
Number of PGM Outputs
Maximum Commuting PGM Output Values
EW1 PGM Output Circuit
7-15V
20mA max
2
Normally closed (NC)
2
Voltage – 30V; current 500mA
Wireless Transmitter-Receiver Frequency
Range of Operating Temperatures
Dimensions
Wireless Communication Range
Compatible with Alarm Systems
868 MHz
-20...+55ºC
38x60x12mm
Up to 30 meters in premises; up to 150 meters in open areas
ELDES Wireless
MANUAL ELDES ESIM364 V1.0
1R
OUT
Open collector
output.
Output is pulled to
COM when turned on.
EN
139
61
COM
Z2
Z1
62
Wireless Expansion
Module EW1
C2
LED
C1
D1
D2
DC+ C1 C2
Z1 Z2 COM
DC+
33.2.1.2. Connector & LED Functionality
COM
Z2, Z1
C2, C1
DC+
D1, D2
LED
Common terminal for power supply, zones
Security zone terminals
PGM output terminals
Positive power supply terminal
Pins for restoring default parameters
EW1 status
+12V
Power supply
33.2.2. Installation
1.
Disconnect ESIM364 alarm system main power supply and backup battery.
2.
Wire up EW1 as indicated in Fig. No. 61
3.
Bind the device to the alarm system by sending a corresponding command via SMS text message or using ELDES Configuration Tool
software. Please, refer to the software‘s HELP section or refer to 19.1. Binding, Removing and Replacing Wireless Devices for
more details.
4. T he system automatically informs about successful/unsuccessful binding process. If attempt to bind is unsuccessful, try to move EW1
closer to ESIM364 alarm system device and bind it again.
5.
EW1 module is ready for use.
NOTE: If you are unable to bind the wireless device please , restore the parameters of the wireless device to default and try again. See
33.2.4 Restoring Default Parameters for more details.
ATTENTION: The minimum wireless connection range between the wireless device and wireless antenna of ESIM364 system can be
0,5 meters.
33.2.3. EW1 Zones, PGM Outputs & Tamper
Upon successful EW1 module binding process, the system adds 2 wireless Instant zones intended for wired sensor connection and 2 wireless
PGM outputs intended for electrical appliance connection and control.
The wireless connection loss between EW1 and ESIM364 alarm system leads to system alarm regardless of system being armed or disarmed.
The system identifies this event as a tamper violation and sends alarm by SMS text message and phone call to the user (-s) by default. The
SMS text message contains the violated tamper number and a star * character indicating wireless connection loss as a tamper alarm cause.
ATTENTION: The tamper will not operate if both wireless zones are disabled.
33.2.4. Restoring Default Parameters
1.
Disconnect EW1 power supply.
2.
Short circuit (connect) pins D1 and D2.
3.
Power up EW1 and wait until LED provides several short flashes.
4. Disconnect power supply.
5.
Remove short-circuit from D1 and D2 pins.
6.
Power up EW1.
7.
Parameters restored to default.
140
EN
MANUAL ELDES ESIM364 V1.0
33.3. EWP1 – Wireless Motion Detector
Main EWP1 features:
t
Violated zone detection by built-in PIR movement sensor.
EWP1 is a wireless device with built-in PIR movement sensor and operates with ELDES wireless alarm systems. The user only needs to switch
on the EWP1 sensor and bind it to ESIM364 alarm system by sending a corresponding command via SMS text message or using software ELDES
Configuration Tool. User can also monitor temperature of the surrounding areas in real-time as EWP1 has a built-in temperature sensor. It is
possible to connect up to 32 EWP1 devices to ESIM364 alarm system at a time. The maximum wireless connection range is 150 meters (in
open areas).
33.3.1. Technical Specifications
33.3.1.1. Electrical & Mechanical Characteristics
Battery Type
Battery Voltage; Capacity
Battery Operation Time
Wireless Transmitter-Receiver Frequency
Range of Operating Temperatures
Dimensions
Detection Coverage Angle
Maximum Detection Distance
Compatible with Alarm Systems
Wireless Communication Range
ER14505 AA Lithium Thionyl Chloride
3,6 V; 2,4 Ah
~18 months*
868 MHz
-10 ... +55°C
104x60x33mm
90°
10 meters
ELDES Wireless
Up to 30 meters in premises; up to 150 meters in open areas
* This operation time might vary in difference conditions.
63
1
2
1
Motion detector
2
LED indicators informing about status of PIR sensor EWP1
3
TAMPER button automatically identifies when the box of sensor
EWP1 is open or closed
4
RESET button for reseting system parameters
5
ER14505 3,6 V Lithium Thionyl Chloride battery
3
4
5
33.3.2. Installation
1.
Choose the place where intrusion into the premises is the most probable and install the device. To avoid false triggers of the system do
not install it in the following places:
t EJSFDUJOHUIFMFOTUPEJSFDUTVOMJHIUGPSFYBNQMFUPUIFXJOEPXPGUIFQSFNJTFT
t XIFSFUIFSFJTBSJTLPGTVEEFOUFNQFSBUVSFBMUFSBUJPOGPSFYBNQMFOFBSBmSFQMBDFPSIFBUJOHTZTUFN
t XIFSFUIFSFJTBOFOMBSHFEQPTTJCJMJUZPGEVTUPSBJSnPX
t CFIJOEUIFDVSUBJOPSTPNFPUIFSDPWFSCMPDLJOHUIFEFUFDUFE[POF
64
2.
Fix EWP1 sensors mounting holder with two screws to the wall and attach the sensor.
MANUAL ELDES ESIM364 V1.0
EN
141
3.
Bind the device to the alarm system by sending a corresponding command via SMS text message or using ELDES Configuration Tool
software. Please, refer to the software‘s HELP section or refer to 19.1. Binding, Removing and Replacing Wireless Devices for
more details.
4. The system automatically informs about successful/unsuccessful binding process. If attempt to bind is unsuccessful, try to move EWP1
closer to alarm system device and bind it again.
5.
EWP1 is ready to use.
NOTE: If you are unable to bind the wireless device please , restore the parameters of the wireless device to default and try again. See
33.3.5. Restoring Default Parameters for more details.
ATTENTION: The minimum wireless connection range between the wireless device and wireless antenna of ESIM364 system can be
0,5 meters.
33.3.3. EWP1 Zone & Tamper
Upon successful EWP1 sensor binding process, the system adds 1 wireless Instant zone intended for movement detection. By, default, the
alarm is caused instantly if any movement is detected in coverage area of the sensor (when system is armed).
In case of tamper violation, the alarm is caused regardless of system being armed or disarmed. There are 2 ways to detect tamper violation
on EWP1 sensor:
t #ZUBNQFSCVUUPOEWP1 has a built-in tamper button intended for monitoring the enclosure status. Once the enclosure of EWP1
is illegally opened, the tamper button becomes unpressed. This action is followed by alarm which is sent by SMS text message and
phone call to the user (-s) by default. The SMS text message contains the violated tamper number.
t
#ZXJSFMFTTDPOOFDUJPOMPTTThe wireless connection loss between EWP1 sensor and ESIM364 system leads to alarm. The system identifies this event as a tamper violation and sends alarm by SMS text message and phone call to the user (-s) by default. The SMS text message
contains the violated tamper number and a star * character indicating wireless connection loss as a tamper alarm cause.
ATTENTION: The tamper will not operate if the wireless zone is disabled.
33.3.4. Battery Replacement
1.
Open EWP1 enclosure.
2.
Remove the old battery from the battery slot.
3.
Postition the new battery according to the appropriate battery slot positive/negative terminals indicated on the PCB (printed-circuitboard) of EWP1.
4. Insert the battery into the battery slot.
5.
Batteries replaced.
For more details, please refer to 33.3.2. Installation.
ATTENTION: Only ER14505 Lithium Thionyl Chlorid AA type batteries can be used. Install only new, high quality and unexpired batteries. Do not mix the old batteries with the new ones.
ATTENTION: At least 1 battery must be removed if the device is not in use.
ATTENTION: In order to avoid fire or explosion hazards, the system must be used only with approved battery. Special care must be taken
when connecting positive and negative battery terminals. Dispose old batteries only into special collection sites. Do not charge, disassemble,
heat or incinerate old batteries.
NOTE: The battery status can be monitored in real-time using ELDES Configuration Tool software.
NOTE: The system sends an SMS message to a preset User 1 as soon as the battery level runs below 5%.
33.3.5. Restoring Default Parameters
1. Remove any battery from EWP1.
2. Press and hold the RESET button.
3. Insert the battery back to EWP1.
4. Hold the RESET button until LED indicator provides several short flashes.
5. Release the RESET button.
6. Parameters restored to default.
142
EN
MANUAL ELDES ESIM364 V1.0
33.4. EWD1 – Wireless Magnetic Door Contact
Main EWD1 features:
t
Violated zone detection by magnetic contact;
t
Panic button.
EWD1 is a wireless device with magnetic contact and panic button which is used to secure doors, windows or any other opening parts and
it operates with ELDES wireless alarm systems. EWD1 is bind to ESIM364 alarm system by sending a corresponding command via SMS text
message or using software ELDES Configuration Tool. When EWD1 is connected to the system, two wireless zones are added. First wireless
zone is used to monitor the magnetic contacts and the second wireless zone is for managing the panic button. By default panic button zone is
configured as Silent zone and in case the panic button is pressed, the system causes silent alarm (no siren is activated).
It is possible to connect up to 32 EWD1 devices to ESIM364 alarm system at a time. The maximum wireless connection range is 150 meters
(in open areas).
33.4.1. Technical Specifications
33.4.1.1. Electrical & Mechanical Characteristics
Battery Type
Number of Batteries
Battery Operation time
Wireless Transmitter-Receiver Frequency
Range of Operating Temperatures
Door Contact Dimensions
Magnet Dimensions
Wireless Communication Range
Compatible with Alarm Systems
CR2032 3V Lithium
1
15 months*
868 Mhz
-20...+55ºC
60x37x18mm
60x17x16mm
Up to 30 meters in premises; up to 150 meters in open areas
ELDES Wireless
* This operating time may vary in different conditions.
MANUAL ELDES ESIM364 V1.0
EN
143
33.4.2. Installation
1.
Open EWD1 enclosure and insert the battery (Fig. No. 65).
65
RESET
LED
3V
CR2032
+
+
2.
EWD1 consists of two parts: a magnet and a sensor. Sensor components are: a mounting part and the sensor. Magnet components are:
a mounting part and the cover.
2.1 Fix the sensor mounting part with two screws on the door or window jamb.
2.2 Fix the magnet mounting part with two screws next to the sensor mounting part on door or window frame. The correct fixing position
is indicated in Fig. No. 66.
66
MAX 20 mm
NOTE: The distance between magnet and sensor can be up to 20 mm only.
2.3 The sensor should be attached to the fixed sensors mounting part. When attaching sensor pay attention to the tamper (micro switch)
- it must be pressed.
2.4 The magnet cover should be attached to the fixed magnet mounting part.
NOTE: It is not recommend to fix EWD1 in other ways than with screws, e.g. with duck tape. See Fig. No. 67 for the incorrect ways of
fixing the magnetic door contact.
67
3.
Bind the device to the alarm system by sending a corresponding command via SMS text message or using ELDES Configuration Tool
software. Please, refer to the software‘s HELP section or refer to 19.1. Binding, Removing and Replacing Wireless Devices for
more details.
4. T he system automatically informs about successful/unsuccessful binding process. If attempt to bind is unsuccessful, try to move
EWD1 closer to alarm system device and bind it again.
5.
EWD1 magnetic door contact is ready to use.
NOTE: If you are unable to bind the wireless device please , restore the parameters of the wireless device to default and try again. See
33.4.5. Restoring Default Parameters for more details.
ATTENTION: The minimum wireless connection range between the wireless device and wireless antenna of ESIM364 system can be
0,5 meters.
33.4.3. EWD1 Zones & Tamper
Upon successful EWD1 magnetic door contact binding process,the system adds 1 wireless Instant zone and 1 wireless Silent zone. The
wireless zones are applied to the following EWD1 components respectively:
t .BHOFUJDDPOUBDUby default, causing alarm if doors/windows is opened when system is armed.
144
EN
MANUAL ELDES ESIM364 V1.0
t 1BOJDCVUUPO - by default, causing silent alarm instantly when pressed.
In case of tamper violation, the alarm is caused regardless of system being armed or disarmed. There are 2 ways to detect tamper violation
on EWD1:
t #ZUBNQFSCVUUPOEWD1 has a built-in tamper button intended for monitoring the enclosure status. Once the enclosure of EWD1 is
illegally opened, the tamper button becomes unpressed. This action is followed by alarm which is sent by SMS text message and phone
call to the user (-s) by default. The SMS text message contains the violated tamper number.
t
#ZXJSFMFTTDPOOFDUJPOMPTT The wireless connection loss between EWD1 and ESIM364 system leads to alarm. The system identifies this event
as a tamper violation and sends alarm by SMS text message and phone call to the user (-s) by default. The SMS text message contains the violated
tamper number and a star * character indicating wireless connection loss as a tamper alarm cause.
ATTENTION: The tamper will not operate if both wireless zones are disabled.
33.4.4. Battery Replacement
1.
Open EWD1 enclosure.
2.
Remove the old battery from the battery slot.
3.
Postition the new battery according to the appropriate battery slot positive terminal indicated.
4. Insert the battery into the battery slot.
5.
Battery replaced.
For more details, please refer to 33.4.2. Installation.
ATTENTION: Only ER14505 Lithium Thionyl Chlorid AA type batteries can be used. Install only new, high quality and unexpired batteries. Do not mix the old batteries with the new ones.
ATTENTION: At least 1 battery must be removed if the device is not in use.
ATTENTION: In order to avoid fire or explosion hazards, the system must be used only with approved battery. Special care must be taken
when connecting positive and negative battery terminals. Dispose old batteries only into special collection sites. Do not charge, disassemble,
heat or incinerate old batteries.
NOTE: The battery status can be monitored in real-time using ELDES Configuration Tool software.
NOTE: The system sends an SMS message to a preset User 1 as soon as the battery level runs below 5%.
33.4.5. Restoring Default Parameters
1.
Remove the battery from EWD1.
2.
Press and hold the RESET button.
3.
Insert the battery back to EWD1.
4. Hold the RESET button until LED indicator provides several short flashes.
5.
Release the RESET button.
6.
Parameters restored to default.
33.5. EWK1 - Wireless Key-Fob
Main EWK1 features:
t
Alarm system arming & disarming;
t
Panic button;
t
PGM output control;
t
Sound indication by built-in mini buzzer.
Key-fob EWK1 – is a wireless device intended to arm and disarm ESIM364 alarm system, to open and close the gates or to control any other device
connected to the alarm system. Wireless key-fob EWK1 is compatible with ELDES wireless alarm systems, therefore user can easily bind it to
the alarm system using ELDES Configuration Tool software or sending a corresponding SMS command. EWK1 key-fob features four configurable
buttons intended to operate according to individual needs. After the button is pressed, EWK1 internal buzzer’s sound signal confirms a transferred command to ESIM364 alarm system via wireless connection. The status of the sent command can be checked by attempting to receive
the feedback signal from the alarm system. This can be performed by pressing down the same button and holding it for 3 seconds. 3 short sound
signals indicate a successfully carried out command while 1 long beep stands for failed command and feedback signal failure. By default one pair
of buttons is already configured to arm and disarm the alarm system.
MANUAL ELDES ESIM364 V1.0
EN
145
The virtual zones of ESIM364 system are intended for EWK1 button configuration. Please, refer to software’s ELDES Configuration Tool HELP section
for more details.
68
Arm the
system
Optional
funcionality
It is possible to connect up to 5 EWK1 devices to ESIM364 alarm system at
a time. The maximum wireless connection range is 150 meters (in open
areas).
Optional
funcionality
Disarm the
system
NOTE: Fig. No. 68 reflects the default EWK1 button configuration. All key-fob buttons are configurable according to individual needs.
33.5.1. Technical Specifications
33.5.1.1. Electrical & Mechanical Characteristics
Battery Type
Battery Voltage; Capacity
Quantity of Batteries
Battery Operation Time
Wireless Transmitter-Receiver Frequency
Range of Operating Temperatures
Wireless Key-fob Dimensions
Wireless Communication Range
Compatible with Alarm Systems
CR2032 Lithium
3V; 240 mAh
1
~18 months*
868 Mhz
-20...+55ºC
54 x 42 x 13 mm
Up to 30 meters in premises; up to 150 meters in open areas
ELDES Wireless
* This operation time depends on different conditions and may vary.
33.5.2. Installation
69
70
1.
Unscrew the EWK1 key-fob housing.
2.
Open EWK1 key-fob housing.
3.
Insert CR2032 battery provided in the EWK1 package.
Before inserting the battery, make sure that the battery’s “+” sign is facing the outer side.
71
+
3V
CR2032
+
4. Close and screw up the key-fob housing.
5.
Bind the device to the alarm system by sending a corresponding command via SMS text message or using ELDES Configuration Tool soft-
146
EN
MANUAL ELDES ESIM364 V1.0
ware. Please, refer to the software‘s HELP section or refer to 19.1. Binding, Removing and Replacing Wireless Devices for more
details.
6.
After binding the device to the alarm system, press any EWK1 button several times.
7.
EWK1 is ready to use.
NOTE: If you are unable to bind the wireless device please , restore the parameters of the wireless device to default and try again. See
33.5.5. Restoring Default Parameters for more details.
33.5.3. EWK1 Zones (Panic Button)
EWK1 key-fob supports a Panic Button feature allowing to cause alarm at any time when the specified button is pressed. This feature can be
configured using ELDES Configuration Tool software by creating a virtual zone of Silent or 24H type and assigning it to Virtual Alarm option.
The Panic Button feature can be set up on any button of EWK1. For more details, please refer to software’s HELP section.
33.5.4. Battery Replacement
1.
Open EWD1 enclosure.
2.
Remove the old battery from the battery slot.
3.
Postition the new battery according to the appropriate battery slot positive terminal indicated.
4. Insert the battery into the battery slot.
5.
Battery replaced.
For more details, please refer to 33.5.2 Installation.
ATTENTION: Only CR2032 3V batteries can be used. Install only new, high quality and unexpired batteries. Do not mix the old batteries
with the new ones.
ATTENTION: At least 1 battery must be removed if the device is not in use.
ATTENTION: In order to avoid fire or explosion hazards, the system must be used only with approved battery. Special care must be
taken when connecting positive and negative battery terminals. Dispose old batteries only into special collection sites. Do not charge,
disassemble, heat or incinerate old batteries.
NOTE: The battery status can be monitored in real-time using ELDES Configuration Tool software.
33.5.5. Restoring Default Parameters
1. Remove the battery from EWK1 key-fob.
2. Press and hold
button.
3. Insert the battery back to EWK1.
4. Hold the button pressed until LED indicator provides several short flashes.
5. Release
button.
6. Parameters restored to default.
33.6. EWS1 – Wireless Indoor Siren
Main EWS1 features:
t
Audio alarm indication by built-in speaker.
EWS1 is a wireless device with built-in siren speaker and operates with ELDES wireless alarm systems. EWS1 has to be bind to the alarm system by sending a corresponding SMS text message or using software ELDES Configuration Tool. Upon successful EWS1 binding, the system
adds one wireless zone and one wireless PGM output. The wireless zone is used to monitor the device (tamper - when the batteries are being
removed) and the wireless PGM output is used to control the speaker. In case of alarm, the siren provides a sound alarm for one minute. The
configuration of this parameter is disabled for EWS1 in order to save the battery power.
It is possible to connect up to 32 EWS1 devices to the alarm system at a time. The maximum wireless connection range is 150 meters (in open
areas).
MANUAL ELDES ESIM364 V1.0
EN
147
33.6.1. Technical Specifications
72
33.6.1.1. Electrical & Mechanical Characteristics
-
+
+
-
BATTERY
LED
RESET
BATTERY
Compatible with Alarm Systems
1,5V Alkaline AA type
3
~18 months*
868 Mhz
-20...+55ºC
123x73x36mm
Up to 30 meters in premises; up to 150 meters in open areas
ELDES Wireless
BATTERY
Battery Type
Number of Batteries
Battery Operation Time
Wireless Transmitter-Receiver Frequency
Range of Operating Temperatures
Dimensions
Wireless Communication Range
33.6.1.2. Main Unit & LED Functionality
RESET
+/LED
+
-
* This operating time may vary in different conditions.
Button for restoring default parameters
Battery slots
EWS1 status indication
33.6.2. Installation
1.
Open EWS1 enclosure.
73
74
Insert a thin flat-shaped screwdriver or any tool alike into the gap located on the back of the enclosure (see Fig. No. 73).
2.
Push the screwdriver down to the right carefully in order to detach
the enclosure parts from each other (see Fig. No. 74)
Once the enclosure is opened, remove the plastic tab inserted between one of the battery terminals and battery slot contact (see Fig. No.
75).
75
148
EN
MANUAL ELDES ESIM364 V1.0
3.
Fix the siren on the wall using the screws (see Fig. No. 76).
76
-
BATTERY
RESET
+
+
LED
-
BATTERY
+
-
BATTERY
4.
Close EWS1 enclosure. No tools are required for this action.
5.
Bind the device to the alarm system by sending a corresponding command via SMS text message or using ELDES Configuration Tool software.
Please, refer to the software‘s HELP section or refer to 19.1. Binding, Removing and Replacing Wireless Devices for more details.
6.
The system automatically informs about successful/unsuccessful binding process. If attempt to bind is unsuccessful, try to move EWS1
closer to alarm system device and bind it again.
7.
EWS1 siren is ready for use.
NOTE: If you are unable to bind the wireless device please , restore the parameters of the wireless device to default and try again. See
33.6.5. Restoring Default Parameters for more details.
ATTENTION: The minimum wireless connection range between the wireless device and wireless antenna of ESIM364 system can be
0,5 meters.
33.6.3. EWS1 Zone, PGM Output & Tamper
Upon successful EWS1 indoor siren binding process,the system adds 1 wireless Instant zone and 1 wireless Siren PGM output. The wireless
zone is intended for EWS1 tamper control and the wireless PGM output is for siren control.
In case of tamper violation, the alarm is caused regardless of system being armed or disarmed. The wireless connection loss between EWS1
and ESIM364 system leads to alarm. The system identifies this event as a tamper violation and sends alarm by SMS text message and phone
call to the user (-s) by default. The SMS text message contains the violated tamper number and a star * character indicating wireless connection loss as a tamper alarm cause.
ATTENTION: The tamper will not operate if the wireless zone is disabled.
33.6.4. Battery Replacement
1.
Open EWS1 enclosure.
2.
Remove all 3 old batteries from the battery slots.
3.
Postition the 3 new 1,5V alkaline AA type batteries according to the appropriate battery slot positive/negative terminals indicated on the
PCB (printed-circuit-board) of EWS1
4. Insert the batteries into the battery slots.
5.
Batteries replaced.
For more details, please refer to 33.6.2 Installation.
ATTENTION: Only CR2032 3V batteries can be used. Install only new, high quality and unexpired batteries. Do not mix the old batteries
with the new ones.
ATTENTION: At least 1 battery must be removed if the device is not in use.
ATTENTION: In order to avoid fire or explosion hazards, the system must be used only with approved battery. Special care must be
taken when connecting positive and negative battery terminals. Dispose old batteries only into special collection sites. Do not charge,
disassemble, heat or incinerate old batteries.
MANUAL ELDES ESIM364 V1.0
EN
149
NOTE: The battery status can be monitored in real-time using ELDES Configuration Tool software.
33.6.5. Restoring Default Parameters
1.
Remove any battery from EWS1.
2.
Press and hold the RESET button.
3.
Insert the battery back to EWS1.
4. Hold the RESET button until LED indicator provides several short flashes.
5.
Release the RESET button.
6.
Parameters restored to default.
33.7. EWS2 – Wireless Outdoor Siren
Main EWS2 features:
t
Audio alarm indication by built-in speaker;
t
Visual alarm indication by built-in LED indicators;
t
Range of operating temperature: -30...+55oC.
EWS2 is a wireless outdoor device with a built-in siren speaker, LED indicators and operates with ELDES wireless alarm systems. EWS2 has to
be bind to the alarm system by sending a corresponding SMS text message or using software ELDES Configuration Tool. Upon successful EWS2
binding process, the system adds one wireless zone and one wireless PGM output. In case of alarm, the siren provides a sound alarm for one
minute. The configuration of this parameter is disabled for EWS2 in order to save the battery power.
It is possible to connect up to 32 EWS2 devices to the alarm system at a time. The maximum wireless connection range is 150 meters (in open
areas).
33.7.1. Technical Specifications
33.7.1.1. Electrical & Mechanical Characteristics
Compatible with Alarm Systems
77
1,5V Alkaline AA type
4
~18 months*
868 Mhz
-30...+55ºC
201 x 140 x 36 mm
Up to 30 meters in premises; up to
150 meters in open areas
ELDES Wireless
TAMPER
Battery Type
Number of Batteries
Battery Operation Time
Wireless Transmitter-Receiver Frequency
Range of Operating Temperatures
Dimensions
Wireless Communication Range
* This operating time may vary in different conditions.
33.7.1.2. Main Unit, LED & Connector Functionality
RESET
+/LED indicators
Tamper
Bell+
Bell-
150
EN
Button for restoring default parameters
Battery slots
Visual alarm indication
Tamper button terminals
Positive siren speaker terminal
Negative siren speaker terminal
TAMPER
+ BELL
+
BATTERY
-
+
BATTERY
-
-
BATTERY
+
-
BATTERY
+
RESET
MANUAL ELDES ESIM364 V1.0
33.7.2. Installation
1.
Open EWS2 enclosure.
78
79
Remove the small blue lid located on the front side of the enclosure
by pulling the lid up. (see Fig. No. 78).
Unscrew the front side of the enclosure (see Fig. No. 79).
2. Once the enclosure is opened, remove the plastic tab inserted between one of the battery terminal and battery slot contact (see Fig. No. 80).
80
3. Fix the siren on the wall using the screws (see Fig. No. 81).
81
+
BATTERY
-
+
BATTERY
-
-
BATTERY
+
-
BATTERY
+
4. Close EWS2 enclosure (see Fig. No. 79, Fig. No. 78)
5. Bind the device to the alarm system by sending a corresponding command via SMS text message or using ELDES Configuration Tool software. Please, refer to the software‘s HELP section or refer to 19.1. Binding, Removing and Replacing Wireless Devices for more
details.
6. The system automatically informs about successful/unsuccessful binding process. If attempt to bind is unsuccessful, try to move EWS2
closer to alarm system device and bind it again.
7. EWS2 siren is ready for use.
NOTE: If you are unable to bind the wireless device please , restore the parameters of the wireless device to default and try again. See
33.7.6. Restoring Default Parameters for more details.
ATTENTION: The minimum wireless connection range between the wireless device and wireless antenna of ESIM364 system can be
0,5 meters.
MANUAL ELDES ESIM364 V1.0
EN
151
33.7.3. EWS2 Zone, PGM Output & Tamper
Upon successful EWS2 outdoor siren binding process,the system adds 1 wireless Instant zone and 1 wireless Siren PGM output. The wireless
zone is intended for EWS2 tamper control and the wireless PGM output is for siren control.
In case of tamper violation, the alarm is caused regardless of system being armed or disarmed. There are 2 ways to detect tamper violation
on EWS2:
t By tamper button. EWS2 has a built-in tamper button intended for monitoring the enclosure status. Once the enclosure of EWS2
is illegally opened, the tamper button becomes unpressed. This action is followed by alarm which is sent by SMS text message and
phone call to the user (-s) by default. The SMS text message contains the violated tamper number.
t By wireless connection loss. The wireless connection loss between EWS2 and ESIM364 alarm system leads to alarm. The system
identifies this event as a tamper violation and sends alarm by SMS text message and phone call to the user (-s) by default. The SMS
text message contains the violated tamper number and a star * character indicating wireless connection loss as a tamper alarm cause.
ATTENTION: The tamper will not operate if the wireless zone is disabled.
33.7.4. Battery Replacement
1. Open EWS2 enclosure.
2. Remove all 4 old batteries from the battery slots.
3. Postition the 4 new 1,5V alkaline AA type batteries according to the appropriate battery slot positive/negative terminals indicated on the
PCB (printed-circuit-board) of EWS2
4. Insert the batteries into the battery slots.
5. Batteries replaced.
For more details, please refer to 33.7.2 Installation.
ATTENTION: Only 1,5V Alkaline AA type batteries can be used. Install only new, high quality and unexpired batteries. Do not mix the old
batteries with the new ones.
ATTENTION: At least 1 battery must be removed if the device is not in use.
ATTENTION: In order to avoid fire or explosion hazards, the system must be used only with approved battery. Special care must be
taken when connecting positive and negative battery terminals. Dispose old batteries only into special collection sites. Do not charge,
disassemble, heat or incinerate old batteries.
NOTE: The system sends an SMS message to a preset User 1 as soon as the battery level runs below 5%.
NOTE: The battery status can be monitored in real-time using ELDES Configuration Tool software.
33.7.5. Restoring Default Parameters
1. Remove any battery from EWS2.
2. Press and hold the RESET button.
3. Insert the battery back to EWS2.
4. Hold the RESET button until LED indicator provides several short flashes.
5. Release the RESET button.
6. Parameters restored to default.
33.8. EW1B - Battery-Powered Wireless Zone & PGM Output Expansion Module
Main EW1B features:
t
2 zones for wired sensor connection;
t
2 PGM outputs for electrical appliance connection.
Wireless expansion module EW1B is a wireless device with 2 zones and 2 PGM outputs. This expansion module connects to ELDES wireless
alarm systems and enables wireless access for to 2 wired devices such as movement PIR sensors, magnetic door contacts etc. In addition it
allows to connect and control up to 2 appliances, i.e. lighting, heating etc. After the wiring process to EW1B it is necessary to bind EW1B to the
alarm system by sending a corresponding command via SMS text message or using software ELDES Configuration Tool. t is possible to connect
up to 32 EW1B devices to ESIM364 alarm system at a time. The maximum wireless connection range is 150 meters (in open areas).
152
EN
MANUAL ELDES ESIM364 V1.0
33.8.1. Technical Specifications
33.8.1.1. Electrical & Mechanical Characteristics
Battery Type
1,5V Alkaline AA type
Number of Batteries
3
Battery Operation Time
~18 months*
Number of Zones
2
Zone Connection Type
Normally closed (NC)
Number of PGM Outputs
2
EW1B PGM Output Circuit
1R
OUT
Open Collector Output.
Output is pulled to COM
when turned ON.
Maximum Commuting PGM Output Voltage – 30V; current 500mA
Values
Wireless Transmitter-Receiver
Frequency
868 MHz
Wireless Communication Range
Up to 30 meters in premises; up to 150 meters in open areas
Compatible with Alarm Systems
ELDES Wireless
Range of Operating Temperatures
-20...+55ºC
EW1B PCB Dimensions
38x60x12mm
EW1B Enclosure Dimensions
90x110x40mm
Enclosure rating
IP65
82
D1
D2
LED
COM
Z2
Z1
C2
C1
* This operating time may vary in different conditions.
33.8.1.2. Connector & LED Functionality
COM
Common terminal for zones
Z2, Z1
Security zone terminals
+ BATTERY –
C2, C1
PGM output terminals
– BATTERY +
D1, D2
Pins for restoring default parameters
LED
EW1B status
+ BATTERY –
33.8.2. Installation
1.
Unscrew EW1B enclosure (see Fig. No. 83)
83
MANUAL ELDES ESIM364 V1.0
2.
Detach the front side of the enclosure by pulling the front side
up (see Fig. No. 84)
84
EN
153
Remove the plastic tab inserted between one of the
battery terminals and battery slot contacts (see Fig. No. 85).
4. Connect the ciruit as indicated in Fig. No. 86.
85
86
EW1B
Z1 Z2 COM
Sensor
C1 C2
Sensor
3.
6.
Close EW1B enclsoure (see Fig. No. 84, Fig. No. 83)
7.
Bind the device to the alarm system by sending a corresponding command via SMS text message or using ELDES Configuration Tool software.
Please, refer to the software‘s HELP section or refer to 19.1. Binding, Removing and Replacing Wireless Devices for more details.
8. The system automatically informs about successful/unsuccessful binding process. If attempt to bind is unsuccessful, try to move EW1B
closer to alarm system device and bind it again.
9.
EW1B is ready for use.
NOTE: If you are unable to bind the wireless device please , restore the parameters of the wireless device to default and try again. See
33.8.5. Restoring Default Parameters for more details.
ATTENTION: The minimum wireless connection range between the wireless device and wireless antenna of ESIM364 system can be 0,5
meters.
33.8.3. EW1B Zones, PGM Outputs & Tamper
Upon successful EW1B module binding process, the system adds 2 wireless Instant zones intended for wired sensor connection and 2 wireless PGM outputs intended for electrical appliance connection and control. The wireless connection loss between EW1B and ESIM364 alarm
system leads to system alarm regardless of system being armed or disarmed. The system identifies this event as a tamper violation and sends
alarm by SMS text message and phone call to the user (-s) by default. The SMS text message contains the violated tamper number and a star *
character indicating wireless connection loss as a tamper alarm cause.
33.8.4. Battery Replacement
1.
Open EW1B enclosure.
2.
Remove all 3 old batteries from the battery slots.
3.
Postition the 3 new 1,5V alkaline AA type batteries according to the appropriate battery slot positive/negative terminals as indicated.
4. Insert the batteries into the battery slots.
5.
Batteries replaced.
For more details, please refer to 33.8.2. Installation.
ATTENTION: Only 1,5V Alkaline AA type batteries can be used. Install only new, high quality and unexpired batteries. Do not mix the old
batteries with the new ones.
ATTENTION: At least 1 battery must be removed if the device is not in use.
ATTENTION: In order to avoid fire or explosion hazards, the system must be used only with approved battery. Special care must be
taken when connecting positive and negative battery terminals. Dispose old batteries only into special collection sites. Do not charge,
disassemble, heat or incinerate old batteries.
154
EN
MANUAL ELDES ESIM364 V1.0
NOTE: The system sends an SMS message to a preset User 1 as soon as the battery level runs below 5%.
NOTE: The battery status can be monitored in real-time using ELDES Configuration Tool software.
33.8.5. Restoring Default Parameters
1.
Remove any battery from EW1B.
2.
Short circuit (connect) pins D1 and D2.
3.
Insert the battery back to EW1B.
4. Wait untill LED provides several short flashes.
5.
Remove short-circuit from D1 and D2 pins.
6.
Parameters restored to default.
MANUAL ELDES ESIM364 V1.0
EN
155
34. SMART SECURITY
The system comes equipped with a Smart Security feature providing a user-friendly graphical interface intended for system status monitoring and control. The graphical interface can be accessed via web browser or a smart-phone application developed for Android and iOSbased (iPhone, iPad) devices. Smart Security feature easily allows to do the following:
t
Arm/disarm the system.
t
Control PGM outputs.
t
View system faults and alarms.
t
Monitor GSM signal strength, back-up battery level and temperature.
1. Before running Smart Security on ESIM364, ensure that::
t
4*.DBSEJTJOTFSUFEJOUPUIF&4*.EFWJDF
t
(134DPOOFDUJPOJTFOBCMFEPOUIF4*.DBSE
t
:PVS&4*.TVQQPSUT4."354&$63*5:
t :PVS&4*.EFWJDFTVQQPSUT4NBSU4FDVSJUZ
t
%FGBVMUEJHJU4.4QBTTXPSEJTDIBOHFEUPBOFXPOF
t
6TFSQIPOFOVNCFSJTTFUVQ
t
"1/6TFSOBNFBOE1BTTXPSETFU
2.
Creating a Smart Security account
t
5ZQFJOUIFGPMMPXJOHBEESFTTJOZPVSXFCCSPXTFSIUUQTFcurity.eldes.lt
t
1SFTTRegister
t
*OUIFOFYUXJOEPXmMMJOVTFSOBNFQBTTXPSEFNBJMBEESFTT
your personal details, verification code and press Register
button.
t
/PXPQFOZPVSFNBJMJOCPYBOEMPPLGPSBOFXFNBJMNFTTBHF
received from ELDES. The email message will contain an account activation link. Please, click on the link to confirm your
account registration.
34
3. Adding the device to Smart Security account
35
t
3FUVSOUPIUUQTFDVSJUZFMEFTMUBOEFOUFSUIFMPHJOEFUBJMT
t
"GUFSTVDDFTTGVMMPHJOQSPDFTTZPVXJMMCFSFRVFTUFEUPmMMJOZPVSEFWJDFEFUBJMTJOCreate Device window. In this window, please, fill in
the following details:
t
156
Name – name of your device displayed in the main screen view of SMART SECURITY.
EN
MANUAL ELDES ESIM364 V1.0
t
Smart Security ID – a unique multi-character security code provided with every ESIM364 unit.
Request Smart
Security ID
SMS
SMS text message content:
ssss_SMART_ID
Value: ssss - 4-digit SMS password.
Example: 1111_SMART_ID
Config
Tool
t
t
This operation may be carried out from the PC using the ELDES Configuration Tool software.
Device Model –select esim364 from the list.
"GUFSmMMJOHJOUIFEFWJDFEFUBJMTQSFTTCreate button.
4. Controlling the System Unit via Smart Security
t
t
"GUFSBEEJOHUIFEFWJDFUPUIFBDDPVOUUJNFZPVXJMMCFCSPVHIUUPUIFOFYUXJOEPXDevices. In addition, a 6-month trial License Key
will be granted for your each device added for the first time to your account. In this window you can view the following information on
your ESIM364 device:
t
Online/Offline – device connection status.
t
vTest Device“ – custom device name provided
by you.
t
ID – internal sequence number of the server.
t
Imei – uniqe hardcoded GSM modem number of
your ESIM364 device.
t
License Key – a special key number provided
after its‘ purchase. This key allows to continue
using SMART SECURITY.
t
Edit button – press to view and edit your device
details
t
Delete button – press to remove your device
from SMART SECURITY account.
36
1SFTTControl button to start controlling your security system and electrical appliances. In the next window you can arm/disarm the
alarm system, view battery, network, temperature status, alarm reports and control electrical appliances.
37
MANUAL ELDES ESIM364 V1.0
EN
157
5. Obtaining a new License Key
t
8IFOUIFQFSJPEPGZPVSNPOUIUSJBM-JDFOTF,FZJTPWFSZPV
will have to purchase a new key via PayPal. Press PayPal Extend License located in the Devices in Use section of Devices
window.
t
*OUIFOFYUXJOEPXGPMMPXUIFJOTUSVDUJPOTPGUIF1BZ1BMTZTtem to complete the purchasing procedure.
t
"GUFS UIF QVSDIBTF JT DPNQMFUF UIF -JDFOTF ,FZ WBMJEJUZ FYtends automatically for a specified device.
158
EN
38
MANUAL ELDES ESIM364 V1.0
35. TEHNICAL SUPPORT
35.1. Troubleshooting
Indication
Possible reason
Indicator STAT is off
· No main power supply
· Wiring done improperly
· Blown fuse
Indicator NETW is off or flashing
·
·
·
·
·
·
·
Missing SIM card
PIN code is enabled
SIM card is inactive
Disconnected antenna
GSM network signal too weak
Problems with GSM provider
Microcontroller is not started due to electrical mains noise or static discharge
System does not send any SMS text messages
and/or does not ring
·
·
·
·
·
SIM card credit balance depleted
Incorrect SMS centre phone number
No GSM network signal
User number is not added (or control from anu phone number is disabled)
SIM card changed before disconnecting main power supply or backup battery
Received SMS text message “Wrong syntax”
· Incorrect SMS text message structure
· Extra space symbol could be left in SMS text message
Missing temperature indication in Info SMS text
message/EKB2 keypad
· Temperature sensor not connected
· Temperature sensor broken
· Connection wires too long
24H and/or Fire zones do not work
· Specified zone must be enabled by SMS, ELDES Configuration Tool, EKB2, EKB3
or EKB3W
No sound during remote listening
· Microphone not connected
· Improper microphone connection
35.2. Restoring Default Parameters
1.
Disconnect the power supply and backup battery.
2.
Short circuit (connect) DEF pins.
3.
Power up the device for 7 seconds.
4. Power down the device.
5.
Remove short circuit from DEF pins.
6.
Parameters restored to default.
35.3. Updating the Firmware via USB Cable Locally
1.
Disconnect the power supply and backup battery.
2.
Short circuit (connect) DEF pins.
3.
Connect the device via USB cable to the PC.
4. Power up the device.
5.
The new window must pop-up where you will find the .bin file. Otherwise open My Computer and look for Boot Disk drive.
6.
Delete the .bin file found in the drive.
7.
Copy the new firmware .bin file to the very same window.
8. Power down the device.
9.
Unplug USB cable.
10. Remove short circuit from DEF pins.
11. Power up the device.
12. Firmware updated.
NOTE: It is strongly recommended to restore default parameters after the firmware update.
MANUAL ELDES ESIM364 V1.0
EN
159
35.4. Updating Firmware via GPRS Connection Remotely
ATTENTION: The system will NOT send any data to monitoring station while updating the firmware remotely via GPRS network. However, during the firmware update process, the data messages are queued up and transmitted to the monitoring station after the firmware
upgrade process is over.
Before updating the firmware remotely via GPRS connection, make sure that:
t4*.DBSEJTJOTFSUFEJOUP4*.$"3%TMPUPG&4*.EFWJDFTFF 2.2. Main Unit, LED & Connector Functionality).
t.PCJMFJOUFSOFUTFSWJDFJTFOBCMFEPOUIF4*.DBSE
t1PXFSTVQQMZJTDPOOFDUFEUP&4*.
t%FGBVMU4.4QBTTXPSEJTDIBOHFEUPBOFXEJHJUQBTTXPSETFF6. PASSWORDS).
t"UMFBTU6TFSQIPOFOVNCFSJTTFUVQTFF 8. USER PHONE NUMBERS).
t"1/VTFSOBNFBOEQBTTXPSEBSFTFUVQTFF30.2.1. GPRS Network).
Initiate FOTA
ESIM364 alarm system supports FOTA (firmware-over-the-air) feature. This allows to upgrade the firmware remotely via GPRS connection. Once the upgrade process is initiated, the system connects to the
specified FTP server address where the firmware file is hosted and begins downloading and re-flashing
the firmware. The firmware file must be located in a folder titled Firmware. In order to initiate the upgrade process please , send the following SMS message.
SMS
SMS text message content:
XXXX_FOTA:ftp-server-ip,port,firmware-file-name.bin,user-name,password
Value: ssss - 4-digit SMS password; ftp-server-io - public IP address of FTP server where
EPIR firmware file is stored; port - port number of FTP server (usually - 21); firmware-filename.bin - name of the firmware file, allowed max. length - up to 31 character; user-name
- user name of FTP server login, allowed max. length - up to 31 character; password password of FTP server login, allowed max. length - up to 31 character.
Example: 1111_FOTA:84.15.143.111,21,ESIM364fw bin,eldesuser,eldespassword
ATTENTION: Comma character is NOT allowed to use in user name and firmware file name.
ATTENTION: “ELDES UAB” does not run a FTP server and does not host the firmware files online. Please, contact your local distributor to
request the latest firmware file: support@eldes.lt
NOTE: It is strongly recommended to restore default parameters after the firmware update.
For product warranty repair service please , contact your local retail store where this product was purchased.
If your problem could not be fixed by the self-guide above please , contact your local distributor. More up to date information about your device
and other products can be found at the manufacturer’s website www.eldes.lt
160
EN
MANUAL ELDES ESIM364 V1.0
35.5. Frequently Asked Questions
Question
Answer
Yes, ESIM364 device can fully operate without any SIM card inserted. In this case
Can ESIM364 operate as standalone device without SIM
you will not be able to configure and control the device by SMS and calls nor to
card inserted?
receive any SMS reports and calls.
Due to security reasons it is recommended to restore the violated zone (-s)
2. I am unable to arm the alarm system when one of the
before arming the alarm system. However, you can enable a Force attribute
zones (some zones) is violated, although I was able
or use the Bypass feature in order to arm the alarm system despite the vioto perform disarming. Is there a way to arm the alarm
lated zone (-s) being present. Please, refer to 14.5. Zone Type Definitions
system while the zone is violated?
and 14.7. Bypassing and Activating Zones.
3. I have activated ATZ mode in ELDES Configuration Tool
It appears that your ELDES Configuration Tool software is outdated. Please,
software, but I am unable to set the connection Type 5.
download the latest ELDES Configuration Tool software version by visiting
Whenever I select Type 5 and press the “Write Settings”
www.eldes.lt/en/download.
button it switches back to Type 4. What’s wrong?
This might have happened due to the jumper left on DEF pins or it is a hard4. When ESIM364 fully powers down my configuration
ware failure. Please, remove the jumper if it is present on DEF pins or contact
becomes lost and I have to re-configure the device
your supplier for warranty service.
again. What’s wrong?
If the smoke detector is connected to one of the ESIM364 PGM outputs
5. I have a smoke detector connected to ESIM364 system. you can reset it by turning the PGM output OFF and then back ON. This
How do I reset the smoke detector when the “Fire” zone can be performed by SMS, EKB2 keypad, EKB3 keypad, EKB3W keypad and
is violated?
ELDES Configuration Tool software. Please, refer to 18.4. Turning PGM
Outputs ON and OFF.
6. What happens if I switch backup battery pole terminals Switching backup battery pole terminals places is forbidden. Otherwise this
places?
will lead to blown fuse and ESIM364 alarm system will have to be repaired.
The SMS reports on tamper violation can be disabled by EKB2, EKB3, EKB3W
keypads or ELDES Configuration Tool software. For mor details, please refer
7. How do I disable SMS reports and calls in case of tamper
violation when alarm system is disarmed?
to 16. TAMPERS or to the software’s HELP section. However, due to security
reasons it is not recommended to disable this feature.
8. Is any additional configuration necessary when conNo additional configuration is required in order to make EPGM1 module
necting EPGM1 module after wiring is done accroding to
operational.
EPGM1 user manual?
No, the number of EPGM1 zones does not duplicate in ATZ mode as
9. Does the number of EPGM1 zones duplicate when ATZ
EPGM1 module does not support ATZ mode. Only ESIM364 zones
mode is activated in the system?
duplicate in ATZ mode.
10. I connect the wired siren to ESIM364 and I hear a silent
sound alarm even when the alarm system is disarmed.
Please, connect the resistor of 3,3 kΩ nominal to the BELL- / BELL+ contacts
In case of alarm system alarm the siren provides a loud
This should solve the problem.
sound alarm as it should. Why?
11. I am using Windows operating system. The windows
Please, update ELDES Configuration Tool software by visiting www.eldes.lt/
of ELDES Configuration Tool are not fully displayed and
en/download and downloading the latest version.
some parts are like cut-off. What’s wrong?
12. The buzzer remains active when I disarm the alarm
The buzzer is intended for iButton indication only and it is not related to
system using the keypad. Why?
disarming process by keypad.
This happens due to wireless connection loss. There might be several reasons:
1. ELDES wireless device is installed too close or too far from ESIM364
13. One of wireless devices connected to ESIM364 system
system.
sends a tamper alarm from time to time, although no
2. Interference of other electronic equipment.
tamper was violated. Why?
3. Physical interference (building walls, floors etc.)
4. Metal material interference.
14. I have connected a wired magnetic door sensor, but
This happens due to incorrect resistor connection. Please, refer to correI receive tamper alarm instead of zone alarm. What’s
sponding connection circuit according to the selected zone connection type
wrong?
(Type 1 – 5). See 2.3.2 Zone Connection Types for more details.
By default, this notification is enabled. The system checks the backup
15. I disconnected the backup battery, but did not receive
battery resistance once a day and sends an SMS report to User 1 on backup
any SMS report on this event. How do I enable SMS
battery replacement if more than 2Ω resistance is detected. For more details,
please refer to 21. BACKUP BATTERY, MAINS POWER SUPPLY STATUS
report on backup battery disconnection?
MONITORING AND MEMORY.
Every time an SMS text message is sent to the user, the system must “know”
that the message was successfully delivered. The only way to partly disable the
16. When I check system SIM card credit balance I see a lot
SMS delivery report (for alarm notifications only) is to enable alarm SMS notificaof SMS delivery confirmation reports. How do I disable
tions to all users. This is useful when having only User1 phone number set up, as
SMS delivery confirmation ESIM364 system?
in case of alarm the system sends the alarm SMS text message to all preset users
simultaneously, but does not require any SMS delivery report.
According to GSM standards 1 SMS text message may consist of up to 160
17. I have set zone names and/or PGM output names
Latin alphabet/English characters maximum. If the message contains at
containing some Cyrillic and/or non-English characters. least one non-latin/non-English character, the length of SMS message beThe zone names and PGM output names do not fully fit comes at least half shorter, since those characters occupy more size of the
in the SMS message. What‘s wrong?
SMS text message than the Latin ones. It is recommended not to use any
non-Latin/ non-English characters in zone names and PGM output names.
1.
MANUAL ELDES ESIM364 V1.0
EN
161
Question
18. The configuration of added wireless key-fob EWK1 to
ESIM364 system is not visible in ELDES Configuration
Tool. What‘s wrong?
ELDES Configuration Tool version is too old. Please, update it.
Answer
19. I am unable to run ELDES Configuration Tool - I receive
error messages in Windows. Why?
Microsoft .NET Framework v3.5 is not installed in Windows system. Please,
download this package from official Microsoft website free of charge and
install it to your Windows system.
20. Info SMS report comes with wrong date and time. How
do I correct it?
Please, set the correct system date and time using either ELDES Configuration Tool, EKB2, EKB3, EKB3W or SMS text message.
It appears that the device is unable to establish a communication with
configuration / FTP server. Please, check the GPRS settings in ESIM364
configuration (APN, user name, password), the location of the firmware
21. I receive an error message when attempting to
..bin file (must be located in the FTP server folder titled Firmware) and
configure the device or update the firmware remotely.
the mobile internet feature presence on the SIM card used with ESIM364.
Whats wrong?
If this does not solve the problem, please contact your GSM operator (and
ISP - for remote configuration problems) in order to request a list of blocked
TCP ports.
1. Send the ssss_endconfig SMS text message.
22. I waited for at least 5 minutes, but did not receive any
2. In ELDES Configuration Tool software press Disconnect button and
SMS message confirming that remote configuration via
repeat the steps from the beginning as described in 5.1. Remote System
GPRS connection has stopped. What‘s wrong?
Configuration via GPRS Connection.
162
EN
MANUAL ELDES ESIM364 V1.0
36. Related Products
EKB2 - LCD keypad
EKB3 - LED keypad
ME1 - metal cabinet
EPGM1 - hardwired zone and PGM output expansion module
EPGM8 - hardwired PGM output expansion module
EA1 - audio output module
MANUAL ELDES ESIM364 V1.0
EN
163
164
EN
EA2 - audio output module with amplifier
DS1990A-F5 - iButton key
DS18S20 - temperature sensor
ED1T - plastic enclosure with iButton key reader
and temperature sensor
EWP1 - wireless PIR sensor (motion detector)
EWD1 - wireless magnetic door contact
EWS2 - wireless external siren
EWS1 - wireless internal siren
MANUAL ELDES ESIM364 V1.0
EWK1 - wireless keyfob
EWF1 – wireless smoke detector
EW1 - wireless zone and PGM output expansion module
EW1B - battery-powered wireless zone and
PGM output expansion module
EKB3W – wireless LED keypad
MANUAL ELDES ESIM364 V1.0
EN
165
Made in the European Union
www.eldes.lt