- Home
- Domestic appliances
- Climate control
- Thermostats
- Danfoss
- ECL Comfort 210
- Installation Guide
- 209 Pages
Danfoss ECL Comfort 210, 310 Heating and Cooling Controller, ECA 30, ECA 31 Remote Control Unit, ECA 32 Internal Extension Module Installation Guide
Below you will find brief information for ECL Comfort 210, ECL Comfort 310. This document provides a comprehensive guide on installing, configuring and using ECL Comfort 210 and 310 controllers for heating, cooling or combination of these, in ventilation systems. It covers a wide variety of applications including room temperature, duct temperature and air pressure control. You will also find instructions for connecting and utilizing ECA 30, 31 and 32 modules depending on your system configuration.
advertisement
Assistant Bot
Need help? Our chatbot has already read the manual and is ready to assist you. Feel free to ask any questions about the device, but providing details will make the conversation more productive.
Installation Guide
ECL Comfort 210 / 310, application A214 / A314
1.0 Table of Contents
1.0 Table of Contents ............................................... 1
Important safety and product information. . . . . . . . . . . . . . . . . . . . . 2
2.0 Installation ........................................................ 5
Placing the temperature sensors. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60
Inserting the ECL Application Key . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79
Navigation, ECL Application Key A214 / A314 . . . . . . . . . . . . . . . . 86
3.0 Daily use ....................................................... 104
Understanding the controller display . . . . . . . . . . . . . . . . . . . . . . . . 105
6.0 Common controller settings............................ 171
Introduction to ‘Common controller settings’ . . . . . . . . . . . . . . 171
7.0 Miscellaneous ................................................ 186
ECA 30 / 31 setup procedures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 186
Several controllers in the same system . . . . . . . . . . . . . . . . . . . . . . 194
4.0 Settings overview .......................................... 113
5.0 Settings......................................................... 116
Flow temperature / Inlet temperature . . . . . . . . . . . . . . . . . . . . . . . 117
Fan / acc. control (fan / accessory control) . . . . . . . . . . . . . . . . . . 141
Danfoss District Energy VI.GU.A2.02
DEN-SMT/DK 1
Installation Guide ECL Comfort 210 / 310, application A214 / A314
1.1 Important safety and product information
1.1.1 Important safety and product information
This Installation Guide is associated with ECL Application Key A214
(order code no. 087H3811).
The ECL Application Key A214 contains the subtypes:
A214.1 … A214.6 (applicable in ECL Comfort 210 and 310)
A314.1 … A314.7 (applicable in ECL Comfort 310)
A314.9 (applicable in ECL Comfort 310)
A214.1 is cooling related application
A214.2, A214.3 and A214.6 are heating related applications
A214.4 and A214.5 are basic heating / cooling applications
A314.1 and A314.2 are basic heating / cooling applications
A314.3 is a special heating application
A314.4 and A314.5 are advanced heating applications
A314.6 and A314.7 are advanced heating / cooling applications
A314.9 is an advanced heating application
The described functions are realized in ECL Comfort 210 for basic solutions and in ECL Comfort 310 for advanced solutions, e.g.
M-bus, Modbus and Ethernet (Internet) communication.
The application Key A214 complies with ECL Comfort 210 and
ECL Comfort 310 controllers as of software version 1.11 (visible at start-up of the controller and in ‘Common controller settings’ in ‘System’).
A Remote Control Unit, ECA 30 or ECA 31, can be connected and the built-in room temperature sensor can be utilized.
The applications A314.1 … A314.7 and A314.9 work with the
Internal I/O module ECA 32 (order code no. 087H3202).
ECA 32 is placed in the base part for ECL Comfort 310.
ECL Comfort 210 is available as:
• ECL Comfort 210, 230 volt a.c. (087H3020)
• ECL Comfort 210B, 230 volt a.c. (087H3030)
ECL Comfort 310 is available as:
• ECL Comfort 310, 230 volt a.c(087H3040)
• ECL Comfort 310B, 230 volt a.c. (087H3050)
• ECL Comfort 310, 24 volt a.c. (087H3044)
The B-types have no display and dial. The B-types are operated by means of the remote control unit ECA 30 / 31:
• ECA 30 (087H3200)
• ECA 31 (087H3201)
Base parts for ECL Comfort:
• for ECL Comfort 210, 230 volt (087H3220)
• for ECL Comfort 310, 230 volt and 24 volt (087H3230)
Additional documentation for ECL Comfort 210 and 310, modules and accessories is available on http://den.danfoss.com/.
2 DEN-SMT/DK VI.GU.A2.02
Danfoss District Energy
Installation Guide ECL Comfort 210 / 310, application A214 / A314
Automatic update of controller software:
The software of the controller is updated automatically when the key is inserted (as of controller version 1.11). The following animation will be shown when the software is being updated:
Progress bar
During update:
• Do not remove the KEY
If the key is removed before the hour-glass is shown, you have to start afresh.
• Do not disconnect the power
If the power is interrupted when the hour-glass is shown, the controller will not work.
Safety Note
To avoid injury of persons and damages to the device, it is absolutely necessary to read and observe these instructions carefully.
Necessary assembly, start-up, and maintenance work must be performed by qualified and authorized personnel only.
Local legislations must be respected. This comprises also cable dimensions and type of isolation (double isolated at 230 V).
A fuse for the ECL Comfort installation is max. 10 A typically.
The ambient temperature range for the ECL Comfort in operation is
0 - 55 °C. Exceeding this temperature range can result in malfunctions.
Installation must be avoided if there is a risk for condensation (dew).
The warning sign is used to emphasize special conditions that should be taken into consideration.
This symbol indicates that this particular piece of information should be read with special attention.
As this Installation Guide covers several system types, special system settings will be marked with a system type. All system types are shown in the chapter: 'Identifying your system type'.
Danfoss District Energy VI.GU.A2.02
DEN-SMT/DK 3
Installation Guide ECL Comfort 210 / 310, application A214 / A314
°C (degrees Celsius) is a measured temperature value whereas K
(Kelvin) often is used for temperature differences.
The ID no. is unique for the selected parameter.
Example
11174
12174
First digit
1
-
1
-
Second digit
1
Circuit 1
2
Circuit 2
Last three digits
174
Parameter no.
174
Parameter no.
If an ID description is mentioned more than once, it means that there are special settings for one or more system types. It will be marked with the system type in question (e.g. 12174 - A266.9).
Parameters indicated with an ID no. like "1x607" mean a universal parameter.
x stands for circuit / parameter group.
Disposal Note
This product should be dismantled and its components sorted, if possible, in various groups before recycling or disposal.
Always follow the local disposal regulations.
4 DEN-SMT/DK VI.GU.A2.02
Danfoss District Energy
Installation Guide ECL Comfort 210 / 310, application A214 / A314
2.0 Installation
2.1 Before you start
The Application Key A214 contains several applications, mainly related to ventilation systems with heating or cooling or a combination of these. The applications in the A214 key offer a wide range of possibilities (see the examples).
The application A214.1 is very flexible. These are the basic principles:
Cooling with room temperature control:
Typically, the air duct temperature is adjusted according to your requirements. The air duct temperature sensor S3 is the most important sensor. The desired temperature at S3 is set in the ECL
Comfort controller as the 'Desired balance temperature'.
The motorized control valve M2 (controlling the cooling transfer) is opened gradually when the duct temperature is higher than the desired duct temperature and vice versa.
Typical A214.1 application:
S 1
ECL 210 / 310
P 2
X3
S 5
A1
M2
F1 S 3
S 8
S 4
Room temperature:
If the measured room temperature (S4 or ECA 30) does not equal the desired room temperature, the desired temperature at S3 can be adjusted.
By means of a week schedule (up to 3 ‘Comfort’ periods / day), the cooling circuit can be in ‘Comfort’ or ‘Saving’ mode (two different temperature values for desired room temperature).
The desired room temperature determines a correction of the desired temperature at S3.
If the room temperature is not measured, the desired room temperature equals (will be) the desired temperature at S3. In this case, the setting of the 'Balance temperature' is not considered (or: has no influence).
The fan (F1) is ON / OFF controlled according to the schedule and cooling demand. The damper (P2) is ON / OFF controlled according to schedule. The circulation pump (X3) is ON / OFF controlled according to cooling demand.
Return temperature (optional):
If the measured return temperature (S5) does not equal the limitation value (typically, the return temperature becomes lower than the limitation value), the desired temperature at S3 can be adjusted (typically to a higher value). This results in a gradual closing of the motorized control valve.
The shown diagram is a fundamental and simplified example and does not contain all components that are necessary in a system.
All named components are connected to the ECL Comfort controller.
List of components:
ECL 210 / 310
Electronic controller ECL Comfort 210 or 310
S1
S2
S3
S4
S5
S8
F1
Outdoor temperature sensor
(Optional) Compensation temperature sensor (not illustrated)
Duct temperature sensor
(Optional) Room temperature sensor*
(Optional) Return temperature sensor
(Optional) Fire thermostat
Fan (ON / OFF)
P2
X3
Damper (ON / OFF)
M2
A1
Circulation pump (ON / OFF)
Motorized control valve, cooling (3-point controlled)
Alarm
* Alternative: ECA 30
A simple frost protection (via S5) can be established. Furthermore, it is expected that the cooling exchanger (fan coil) circuit contains brine.
For a description of alarms and compensation temperature, please read the section ‘A214 and A314 in general’.
Danfoss District Energy VI.GU.A2.02
DEN-SMT/DK 5
Installation Guide ECL Comfort 210 / 310, application A214 / A314
The applications A214.2 and A214.3 are very flexible and almost identical. These are the basic principles:
A214.2: Heating with duct temperature control
A214.3: Heating with room temperature control
Typically, the heating temperature is adjusted according to your requirements. The temperature sensor S3 is the most important sensor. The desired temperature at S3 is set in the ECL Comfort controller as the 'Desired balance temperature'.
The motorized control valve M1 (controlling the heating supply temperature) is opened gradually when the S3 temperature is lower than the desired S3 temperature and vice versa.
S4 temperature:
If the measured S4 temperature does not equal the desired S4 temperature, the desired temperature at S3 can be adjusted.
By means of a week schedule (up to 3 ‘Comfort’ periods / day), the heating circuit can be in ‘Comfort’ or ‘Saving’ mode (two different temperature values for desired S4 temperature). The desired S4 temperature determines a correction of the desired temperature at S3.
The fan (F1) is ON / OFF controlled according to the schedule and heating demand. The damper (P2) is ON / OFF controlled according to schedule. The circulation pump (X3) is ON / OFF controlled according to heating demand.
For a description of alarms, compensation temperature, return temperature limitation (S5) and frost protection (S6 and S7), please read the section ‘A214 and A314 in general’.
Typical A214.2 application:
S 1
ECL 210 / 310
A1
P 2
S 3
X3
S 5
S 6 F1 S 4
S 7
M1
S 8
The shown diagram is a fundamental and simplified example and does not contain all components that are necessary in a system.
All named components are connected to the ECL Comfort controller.
P2
X3
M1
A1
S7
S8
F1
List of components:
ECL 210 / 310 Electronic controller ECL Comfort 210 or 310
S1
S2
Outdoor temperature sensor
S3
S4
(Optional) Compensation temperature sensor (not illustrated)
Flow temperature sensor
Duct temperature sensor
S5
S6
(Optional) Return temperature sensor
(Optional) Frost temperature sensor
(Optional) Frost thermostat
(Optional) Fire thermostat
Fan (ON / OFF)
Damper (ON / OFF)
Circulation pump (ON / OFF)
Motorized control valve, heating (3-point controlled)
Alarm
6 DEN-SMT/DK VI.GU.A2.02
Danfoss District Energy
Installation Guide ECL Comfort 210 / 310, application A214 / A314
Typical A214.3 application:
S 1
ECL 210 / 310
A1
P 2
X3
M1
S 5
S 6
F1 S 3
S 7
S 8
S 4
The shown diagram is a fundamental and simplified example and does not contain all components that are necessary in a system.
All named components are connected to the ECL Comfort controller.
F1
P2
X3
S4
S5
S6
List of components:
ECL 210 / 310 Electronic controller ECL Comfort 210 or 310
S1 Outdoor temperature sensor
S2
S3
(Optional) Compensation temperature sensor (not illustrated)
Duct temperature sensor
S7
S8
Room temperature sensor*
(Optional) Return temperature sensor
(Optional) Frost temperature sensor
(Optional) Frost thermostat
(Optional) Fire thermostat
Fan (ON / OFF)
Damper (ON / OFF)
M1
A1
Circulation pump (ON / OFF)
Motorized control valve, heating (3-point controlled)
Alarm
* Alternative: ECA 30
Danfoss District Energy VI.GU.A2.02
DEN-SMT/DK 7
Installation Guide ECL Comfort 210 / 310, application A214 / A314
The application A214.4 is very flexible. These are the basic principles:
Heating / cooling with air duct temperature control
Typically, the heating / cooling temperature is adjusted according to your requirements.
The flow temperature sensor S3 in the heating circuit is the most important sensor. The desired temperature at S3 is set in the ECL
Comfort controller as the 'Desired balance temperature'.
The motorized control valve M1 (controlling the heating temperature) is opened gradually when the flow temperature is lower than the desired balance temperature and vice versa.
At cooling, the motorized control valve M2 controls the cooling temperature at S4.
Air duct temperature:
A too low air duct temperature S4 will activate the heating circuit
M1, whereas a too high air duct temperature will activate the cooling circuit M2.
At heating demand, the air duct temperature S4 can adjust the desired temperature at S3. At cooling demand, the air duct temperature S4 is controlled according to the desired air duct temperature. A "Dead zone" (= number of degrees) can be set in order to avoid unstable shifts between heating and cooling operation.
By means of a week schedule (up to 3 ‘Comfort’ periods / day), the heating / cooling circuit can be in ‘Comfort’ or ‘Saving’ mode (two different temperature values for desired air duct temperature).
In 'Saving' mode the desired air duct temperature determines a correction of the desired temperature at S3 in heating mode. In cooling mode the cooling is OFF during 'Saving'.
The fan F1 is ON / OFF controlled according to the schedule and heating / cooling demand. The damper P2 is ON / OFF controlled according to schedule. The circulation pump X3 is ON / OFF controlled according to heating demand.
For a description of alarms, compensation temperature, return temperature limitation (S5) and frost protection (S6 and S7), please read the section ‘A214 and A314 in general’.
Typical A214.4 application:
S 1
ECL 210 / 310
P 2
S 3
X3
S 6
S 7
M1
S 5
A1
M2
F1
S 4
S 8
The shown diagram is a fundamental and simplified example and does not contain all components that are necessary in a system.
All named components are connected to the ECL Comfort controller.
P2
X3
M1
List of components:
ECL 210 / 310
Electronic controller ECL Comfort 210 or 310
S1
Outdoor temperature sensor
S2
S3
S4
(Optional) Compensation temperature sensor (not illustrated)
Heating temperature sensor
Air duct temperature sensor
S5
S6
S7
(Optional) Return temperature sensor
(Optional) Frost temperature sensor
S8
F1
(Optional) Frost thermostat
(Optional) Fire thermostat
Fan (ON / OFF)
M2
A1
Damper (ON / OFF)
Circulation pump, heating (ON / OFF)
Motorized control valve, heating (3-point controlled)
Motorized control valve, cooling (3-point controlled)
Alarm
8 DEN-SMT/DK VI.GU.A2.02
Danfoss District Energy
Installation Guide ECL Comfort 210 / 310, application A214 / A314
The application A214.5 is very flexible. These are the basic principles:
Heating / cooling with room temperature control
Typically, the heating / cooling temperature is adjusted according to your requirements.
The temperature sensor S3 in the air duct is the most important sensor. The desired temperature at S3 is set in the ECL Comfort controller as the 'Desired balance temperature'.
The motorized control valve M1 (controlling the heating temperature) is opened gradually when the air duct temperature is lower than the desired balance temperature and vice versa.
At cooling, the motorized control valve M2 controls the cooling temperature.
Room temperature:
A too low room temperature S4 will activate the heating circuit M1, whereas a too high room temperature will activate the cooling circuit M2. A "Dead zone" (= number of degrees) can be set in order to avoid unstable shifts between heating and cooling operation.
At heating / cooling demand, the room temperature S4 can adjust the desired temperature at S3.
By means of a week schedule (up to 3 ‘Comfort’ periods / day), the heating / cooling circuit can be in ‘Comfort’ or ‘Saving’ mode (two different temperature values for desired room temperature).
In 'Saving' mode the desired room temperature determines a correction of the desired temperature at S3 in heating mode. In cooling mode the cooling is OFF during 'Saving'.
The fan F1 is ON / OFF controlled according to the schedule and heating / cooling demand. The damper P2 is ON / OFF controlled according to schedule. The circulation pump X3 is ON / OFF controlled according to heating demand.
For a description of alarms, compensation temperature, return temperature limitation (S5) and frost protection (S6 and S7), please read the section ‘A214 and A314 in general’.
Typical A214.5 application:
S 1
ECL 210 / 310
P 2
X3
S 6
S 7
M1
S 5
A1
M2
F1
S 3
S 8
S 4
The shown diagram is a fundamental and simplified example and does not contain all components that are necessary in a system.
All named components are connected to the ECL Comfort controller.
P2
X3
M1
M2
A1
List of components:
ECL 210 / 310
Electronic controller ECL Comfort 210 or 310
S1
Outdoor temperature sensor
S2
S3
S4
(Optional) Compensation temperature sensor (not illustrated)
Duct temperature sensor
Room temperature sensor*
S5
S6
S7
(Optional) Return temperature sensor
(Optional) Frost temperature sensor
S8
F1
(Optional) Frost thermostat
(Optional) Fire thermostat
Fan (ON / OFF)
Damper (ON / OFF)
Circulation pump, heating (ON / OFF)
Motorized control valve, heating (3-point controlled)
Motorized control valve, cooling (3-point controlled)
Alarm
* Alternative: ECA 30
Danfoss District Energy VI.GU.A2.02
DEN-SMT/DK 9
Installation Guide ECL Comfort 210 / 310, application A214 / A314
The application A214.6 is very flexible. These are the basic principles:
Heating with room temperature control:
Typically, the flow temperature is adjusted according to your requirements. The flow temperature sensor S3 is the most important sensor. The desired temperature at S3 is set in the ECL
Comfort controller as the 'Desired balance temperature'.
The motorized control valve M1 is opened gradually when the flow temperature is lower than the desired flow temperature and vice versa.
Room temperature:
If the measured room temperature (S4 or ECA 30) does not equal the desired room temperature, the desired temperature at S3 can be adjusted.
By means of a week schedule (up to 3 ‘Comfort’ periods / day), the heating circuit can be in ‘Comfort’ or ‘Saving’ mode (two different temperature values for desired room temperature). The desired room temperature determines a correction of the desired temperature at S3.
The circulation pump (F1) is ON / OFF controlled according to the
Schedule 1. The accessory (P2) is ON / OFF controlled according to Schedule 1 or 2.
For a description of alarms, compensation temperature, return temperature limitation (S5), frost protection (S6 and S7) and fire alarm please read the section ‘A214 and A314 in general’.
Typical A214.6 application:
The shown diagram is a fundamental and simplified example and does not contain all components that are necessary in a system.
All named components are connected to the ECL Comfort controller.
S7
S8
F1
List of components:
ECL 210 / 310 Electronic controller ECL Comfort 210 or 310
S1
S2
S3
Outdoor temperature sensor
(Optional) Compensation temperature sensor
Flow temperature sensor
S4
S5
S6
Room temperature sensor*
(Optional) Return temperature sensor
(Optional) Frost temperature sensor (not illustrated)
(Optional) Frost thermostat (not illustrated)
P2
X3
M1
A1
(Optional) Fire thermostat (not illustrated)
Circulation pump (ON / OFF)
Accessory output (ON / OFF)
Optional output (ON / OFF)
Motorized control valve, heating (3-point controlled)
Alarm
* Alternative: ECA 30
10 DEN-SMT/DK VI.GU.A2.02
Danfoss District Energy
Installation Guide ECL Comfort 210 / 310, application A214 / A314
The application A314.1 is very flexible. These are the basic principles:
Heating and (passive) cooling with air duct temperature control
Typically, the heating / cooling temperature is adjusted according to your requirements. The flow temperature sensor S3 is the most important sensor. The desired temperature at S3 is set in the ECL
Comfort controller as the 'Desired balance temperature'.
The motorized control valve M1 (controlling the heating temperature) is opened gradually when the flow temperature is lower than the desired temperature and vice versa. At cooling, the motorized damper M2 controls the cooling temperature. The cooling section can be passive (re-circulation) or active.
Air duct temperature:
A too low temperature at S4 will activate the heating circuit (M1), whereas a too high duct temperature will activate the cooling circuit (M2).
At heating demand, the temperature at S4 can adjust the desired temperature at S3. At cooling demand, the S4 temperature is controlled according to the desired S4 temperature. A "Dead zone"
(= number of degrees) can be set in order to avoid unstable shifts between heating and cooling operation.
M1 is 3-point controlled, whereas M2 is 0-10 V controlled.
By means of a week schedule (up to 3 ‘Comfort’ periods / day), the heating / cooling circuit can be in ‘Comfort’ or ‘Saving’ mode (two different temperature values for desired air duct temperature).
In 'Saving' mode the desired air duct temperature determines a correction of the desired temperature at S3 in heating mode. In cooling mode the cooling is OFF during 'Saving'.
The fan F1 is ON / OFF controlled according to the schedule and heating / cooling demand. The damper P2 is ON / OFF controlled according to schedule. The circulation pump X3 is ON / OFF controlled according to heating demand.
For a description of alarms, compensation temperature, return temperature limitation (S5) and frost protection (S6 and S7), please read the section ‘A214 and A314 in general’.
Typical A314.1 application:
S 1
ECL 310
+ ECA 32
A1
P 2 M2
A
S 3
X3
S 5
S 6
F1
S 4
S 7
M1
S 8
S 2
The shown diagram is a fundamental and simplified example and does not contain all components that are necessary in a system.
All named components are connected to the ECL Comfort controller.
S7
S8
F1
List of components:
ECL 310 Electronic controller ECL Comfort 310
ECA 32 Built-in extension module
S1
Outdoor temperature sensor
S2
S3
S4
S5
(Optional) Compensation temperature sensor
Flow temperature sensor
Duct temperature sensor
(Optional) Return temperature sensor
S6
(Optional) Frost temperature sensor
(Optional) Frost thermostat
P2
X3
M1
M2
A1
(Optional) Fire thermostat
Fan (ON / OFF)
Damper (ON / OFF)
Circulation pump, heating (ON / OFF)
Motorized control valve, heating (3-point controlled)
Motorized damper (0 - 10 volt controlled)
Alarm
Danfoss District Energy VI.GU.A2.02
DEN-SMT/DK 11
Installation Guide ECL Comfort 210 / 310, application A214 / A314
The application A314.2 is very flexible. These are the basic principles:
Heating and (passive) cooling with room temperature control
Typically, the heating / cooling temperature is adjusted according to your requirements. The air duct temperature sensor S3 is the most important sensor. The desired temperature at S3 is set in the
ECL Comfort controller as the 'Desired balance temperature'.
The motorized control valve M1 (controlling the heating temperature) is opened gradually when the air duct temperature is lower than the desired temperature and vice versa. At cooling, the motorized damper M2 controls the cooling temperature. The cooling section can be passive (re-circulation) or active.
Room temperature:
A too low temperature at S4 will activate the heating circuit (M1), whereas a too high duct temperature will activate the cooling circuit (M2). A "Dead zone" (= number of degrees) can be set in order to avoid unstable shifts between heating and cooling operation.
At heating / cooling demand, the temperature at S4 can adjust the desired temperature at S3.
M1 is 3-point controlled, whereas M2 is 0-10 V controlled.
By means of a week schedule (up to 3 ‘Comfort’ periods / day), the heating / cooling circuit can be in ‘Comfort’ or ‘Saving’ mode (two different temperature values for desired room temperature).
In 'Saving' mode the desired room temperature determines a correction of the desired temperature at S3 in heating mode. In cooling mode the cooling is OFF during 'Saving'.
The fan F1 is ON / OFF controlled according to the schedule and heating / cooling demand. The damper P2 is ON / OFF controlled according to schedule. The circulation pump X3 is ON / OFF controlled according to heating demand.
For a description of alarms, compensation temperature, return temperature limitation (S5) and frost protection (S6 and S7), please read the section ‘A214 and A314 in general’.
Typical A314.2 application:
S 1
P 2 M2
A
ECL 310
+ ECA 32
A1
X3
S 5
S 6
F1
S 7
M1
S 2
S 3
S 8
The shown diagram is a fundamental and simplified example and does not contain all components that are necessary in a system.
All named components are connected to the ECL Comfort controller.
S8
F1
P2
X3
M1
M2
A1
S3
S4
S5
S6
S7
List of components:
ECL 310 Electronic controller ECL Comfort 310
ECA 32 Built-in extension module
S1
S2
Outdoor temperature sensor
(Optional) Compensation temperature sensor
Duct temperature sensor
Room temperature sensor*
(Optional) Return temperature sensor
(Optional) Frost temperature sensor
(Optional) Frost thermostat
(Optional) Fire thermostat
Fan (ON / OFF)
Damper (ON / OFF)
Circulation pump, heating (ON / OFF)
Motorized control valve, heating (3-point controlled)
Motorized damper (0 - 10 volt controlled)
Alarm
* Alternative: ECA 30
S 4
12 DEN-SMT/DK VI.GU.A2.02
Danfoss District Energy
Installation Guide ECL Comfort 210 / 310, application A214 / A314
The application A314.3 is very flexible. These are the basic principles:
Heating with room temperature control
Typically, the air duct temperature is adjusted according to your requirements. The air duct temperature sensor S3 is the most important sensor. The desired temperature at S3 is set in the ECL
Comfort controller as the 'Desired balance temperature'.
The motorized control valve M1 (controlling the heating temperature) is opened gradually when the air duct emperature is lower than the desired air duct temperature and vice versa.
Typical A314.3 application:
S 1
ECL 310
+ ECA 32
A1
S10
P 2
X3
S 5
M1
S 2
S 6
F1 / V1 S 3
S 4
Room temperature:
If the room temperature (S4 or ECA 30) does not equal the desired room temperature, the desired temperature at S3 can be adjusted.
By means of a week schedule (up to 3 ‘Comfort’ periods / day), the heating circuit can be in ‘Comfort’ or ‘Saving’ mode (two different temperature values for desired room temperature).
In 'Saving' mode the desired room temperature determines a correction of the desired temperature at S3.
The fan F1 is ON / OFF controlled according to the schedule and heating demand. The damper P2 is ON / OFF controlled according to schedule. The circulation pump X3 is ON / OFF controlled according to heating demand.
S 7
S 8
The shown diagram is a fundamental and simplified example and does not contain all components that are necessary in a system.
All named components are connected to the ECL Comfort controller.
Variable fan speed (optional):
The fan V1 can be speed controlled in relation to the measured wind speed S10. The fan speed control signal is a 0–10 volt signal, generated by the internal input / output module ECA 32. A menu in the ECL Comfort 310 contains settings for relationship between actual wind speed and desired fan speed.
For a description of alarms, compensation temperature, return temperature limitation (S5) and frost protection (S6 and S7), please read the section ‘A214 and A314 in general’.
List of components:
ECL 310 Electronic controller ECL Comfort 310
ECA 32 Built-in extension module
S1 Outdoor temperature sensor
S2 (Optional) Compensation temperature sensor
S3 Duct temperature sensor
S4 Room temperature sensor*
S5 (Optional) Return temperature sensor
S6 (Optional) Frost temperature sensor
S7 (Optional) Frost thermostat
S8 (Optional) Fire thermostat
S10 Wind speed signal (0 - 10 volt)
F1 Fan (ON / OFF)
P2 Damper (ON / OFF)
X3 Circulation pump, heating (ON / OFF)
M1 Motorized control valve, heating (3-point controlled)
M2 Motorized damper (0 - 10 volt controlled)
V1 Fan speed (0 - 10 volt controlled)
A1 Alarm
* Alternative: ECA 30
Danfoss District Energy VI.GU.A2.02
DEN-SMT/DK 13
Installation Guide ECL Comfort 210 / 310, application A214 / A314
The advanced heating application A314.4 is very flexible. These are the basic principles:
Heating with room temperature and air pressure control
Typically, the heating temperature is adjusted according to your requirements. The air duct temperature sensor S3 is the most important sensor. The desired temperature at S3 is set in the ECL
Comfort controller as the 'Desired inlet temperature'.
The recovery circuit, controlled by M2, is considered as the main circuit, whereas the heating circuit, controlled by M1, is the supplementary circuit.
The motorized control valve M1 (controlling the heating temperature) is opened gradually when the S3 temperature is lower than the desired S3 temperature and vice versa.
Typical A314.4 application:
•
Room temperature:
If the room temperature (S4 or ECA 30) does not equal the desired room temperature, the desired temperature at S3 can be adjusted.
By means of a week schedule (up to 3 ‘Comfort’ periods / day), the heating circuit can be in ‘Comfort’ or ‘Saving’ mode (two different temperature values for desired inlet temperature and two different temperature values for desired room temperature).
The fan F1 is ON / OFF controlled according to the schedule and heating demand. A damper P2 can be ON / OFF controlled according to schedule. The circulation pump X3 is ON / OFF controlled according to heating demand.
Air pressure control:
The fans V2 and V3 are speed controlled individually in relation to desired pressures (Pascal) at S11 and S12. The signals at S11 and
S12 are measured as 0 - 10 volt and converted into Pascal in the ECL
Comfort 310. Furthermore, the speed of the fans can be lowered at lower outdoor temperatures in order to reduce cold air inlet.
Heat recovery:
In order to utilize heat from the exit air duct, a rotating heat-exchanger, a cross heat-exchanger or a fluid battery can be controlled by M2. Based on the outdoor temperature S1, the entry duct temperature S13 and the exit duct temperature S14 the recovery efficiency (in %) can be indicated.
Night cooling:
During Saving mode a passive cooling (setting the fans ON) can be arranged, mainly under the following conditions:
• room temperature is higher than desired saving room temperature outdoor temperature is lower than the room temperature
The shown diagram is a fundamental and simplified example and does not contain all components that are necessary in a system.
All named components are connected to the ECL Comfort controller.
List of components:
ECL 310 Electronic controller ECL Comfort 310
ECA 32 Built-in extension module
S1 Outdoor temperature sensor
S2 (Optional) Compensation temperature sensor
S3 Duct temperature sensor
S4 Room temperature sensor*
S5 (Optional) Return temperature sensor
S6 (Optional) Frost temperature sensor
S7 (Optional) Frost thermostat
S8 (Optional) Fire thermostat
S9 Fan monitor
S10 Filter monitor
S11 Inlet pressure sensor
S12 Outlet pressure sensor
S13 Entry duct temperature sensor
S14 Exit duct temperature sensor
F1 Fan (ON / OFF)
P2 Damper (ON / OFF)
X3 Circulation pump, heating (ON / OFF)
X4 Schedule 3
P7 Recovery circuit pump, ON / OFF, (not illustrated)
P8 Night damper, ON / OFF, (not illustrated)
M1 Motorized control valve, heating (3-point controlled)
M2 Rotating heat-exchanger (0 - 10 volt controlled)
V2 Fan speed (0 - 10 volt controlled)
V3 Fan speed (0 - 10 volt controlled)
A1 Alarm
* Alternative: ECA 30
14 DEN-SMT/DK VI.GU.A2.02
Danfoss District Energy
Installation Guide ECL Comfort 210 / 310, application A214 / A314
Heating with room temperature and air pressure control
(continued)
Ventilation during saving period:
A desired reduced pressure can be set.
• Room temperature signal must be present
• The night damper P8 will open
• The fan V2 will operate at reduced speed
• The fan V3 is OFF
• P2 is OFF
• M2 is OFF
Summer cut-out:
When outdoor temperature exceeds a selectable value, the heating system closes totally.
M1 is 3-point controlled, whereas M2 is 0-10 V controlled.
For a description of alarms, compensation temperature, return temperature limitation (S5) and frost protection (S6 and S7), please read the section ‘A214 and A314 in general’.
Danfoss District Energy VI.GU.A2.02
DEN-SMT/DK 15
Installation Guide ECL Comfort 210 / 310, application A214 / A314
The advanced heating application A314.5 is very flexible. These are the basic principles:
Heating with room temperature and air quality control
Typically, the heating temperature is adjusted according to your requirements. The air duct temperature sensor S3 is the most important sensor. The desired temperature at S3 is set in the ECL
Comfort controller as the 'Desired inlet temperature'.
The recovery circuit, controlled by M2, is considered as the main circuit, whereas the heating circuit, controlled by M1, is the supplementary circuit.
The motorized control valve M1 (controlling the heating temperature) is opened gradually when the S3 temperature is lower than the desired S3 temperature and vice versa.
Typical A314.5 application:
•
Room temperature:
If the room temperature (S4 or ECA 30) does not equal the desired room temperature, the desired temperature at S3 can be adjusted.
By means of a week schedule (up to 3 ‘Comfort’ periods / day), the heating circuit can be in ‘Comfort’ or ‘Saving’ mode (two different temperature values for desired inlet temperature and two different temperature values for desired room temperature).
The fan F1 is ON / OFF controlled according to the schedule and heating demand. A damper P2 can be ON / OFF controlled according to schedule. The circulation pump X3 is ON / OFF controlled according to heating demand.
Air quality control (CO
2 measured in "ppm"):
The fans V2 and V3 are increased in speed when the ppm value (0 -
10 volt signal measured by S11) exceeds a selectable limit. Speed relation between V2 and V3 can be set. As an alternative, the S11 signal can express an RH signal (Relative Humidity).
Heat recovery:
In order to utilize heat from the exit air duct, a rotating heat-exchanger, a cross heat-exchanger or a fluid battery can be controlled by M2. Based on the outdoor temperature S1, the entry duct temperature S13 and the exit duct temperature S14 the recovery efficiency (in %) can be indicated.
Night cooling:
During Saving mode a passive cooling can be arranged, mainly under the following conditions:
• room temperature is higher than desired saving room temperature outdoor temperature is lower than the room temperature
The shown diagram is a fundamental and simplified example and does not contain all components that are necessary in a system.
All named components are connected to the ECL Comfort controller.
List of components:
ECL 310 Electronic controller ECL Comfort 310
ECA 32 Built-in extension module
S1 Outdoor temperature sensor
S2 (Optional) Compensation temperature sensor
S3 Duct temperature sensor
S4 Room temperature sensor*
S5 (Optional) Return temperature sensor
S6 (Optional) Frost temperature sensor
S7 (Optional) Frost thermostat
S8 (Optional) Fire thermostat
S9 Fan monitor
S10 Filter monitor
S11 Air quality (CO
2
) signal (ppm). Alternative: Relative
Humidity signal.
S13 Entry duct temperature sensor
S14 Exit duct temperature sensor
F1 Fan (ON / OFF)
P2 Damper (ON / OFF)
X3 Circulation pump, heating (ON / OFF)
X4 Schedule 3
P7 Recovery circuit pump, ON / OFF, (not illustrated)
P8 Night damper, ON / OFF, (not illustrated)
M1 Motorized control valve, heating (3-point controlled)
M2 Rotating heat-exchanger (0 - 10 volt controlled)
V2 Fan speed (0 - 10 volt controlled)
V3 Fan speed (0 - 10 volt controlled)
A1 Alarm
* Alternative: ECA 30
16 DEN-SMT/DK VI.GU.A2.02
Danfoss District Energy
Installation Guide ECL Comfort 210 / 310, application A214 / A314
Heating with room temperature and air quality control
(continued)
Ventilation during saving period:
A desired fan speed can be set.
• Room temperature signal must be present
• The night damper P8 will open
• The fan V2 will operate at reduced speed
• The fan V3 is OFF
• P2 is OFF
• M2 is OFF
Summer cut-out:
When outdoor temperature exceeds a selectable value, the heating system closes totally.
M1 is 3-point controlled, whereas M2 is 0-10 V controlled.
For a description of alarms, compensation temperature, return temperature limitation (S5) and frost protection (S6 and S7), please read the section ‘A214 and A314 in general’.
Danfoss District Energy VI.GU.A2.02
DEN-SMT/DK 17
Installation Guide ECL Comfort 210 / 310, application A214 / A314
The advanced heating application A314.6 is very flexible. These are the basic principles:
Heating / cooling with room temperature and air pressure control
Typically, the heating temperature is adjusted according to your requirements. The air duct temperature sensor S3 is the most important sensor. The desired temperature at S3 is set in the ECL
Comfort controller as the 'Desired inlet temperature'.
The recovery circuit, controlled by M2, is considered as the main circuit, whereas the heating circuit (controlled by M1) and the cooling circuit (controlled by M3) are the supplementary circuits.
The motorized control valve M1 (controlling the heating temperature) is opened gradually when the air duct temperature is lower than the desired inlet temperature and vice versa.
At cooling, the motorized control valve M3 controls the cooling temperature.
Typical A314.6 application:
S 1
P 2
S 10
M 2
A
S 14
X 3
S 13
S 10
ECL 310
+ ECA 32
A 1 X 4
S 2
S 5
S 6
S 7
M 1
X 5
M 3
S 9
S 11
S 3
F1 / V2
F1 / V3
S 12
S 8
S 8
S 4
S 9
•
Room temperature:
If the room temperature (S4 or ECA 30) does not equal the desired room temperature, the desired temperature at S3 can be adjusted.
A too low temperature at S4 will activate the heating circuit (M1), whereas a too high air duct temperature will activate the cooling circuit (M3). A "Dead zone" (= number of degrees) can be set in order to avoid unstable shifts between heating and cooling operation.
By means of a week schedule (up to 3 ‘Comfort’ periods / day), the heating / cooling circuit can be in ‘Comfort’ or ‘Saving’ mode (two different temperature values for desired inlet temperature and two different temperature values for desired room temperature).
The fan F1 is ON / OFF controlled according to the schedule and heating demand. A damper P2 can be ON / OFF controlled according to schedule. The circulation pump X3 is ON / OFF controlled according to heating demand.
Air pressure control:
The fans V2 and V3 are speed controlled individually in relation to desired pressures (Pascal) at S11 and S12. The signals at S11 and
S12 are measured as 0 - 10 volt and converted into Pascal in the
ECL Comfort 310.
Heat recovery:
In order to utilize heat from the exit air duct, a rotating heat-exchanger, a cross heat-exchanger or a fluid battery can be controlled by M2. Based on the outdoor temperature S1, the entry duct temperature S13 and the exit duct temperature S14 the recovery efficiency (in %) can be indicated.
Night cooling:
During Saving mode a passive cooling can be arranged, mainly under the following conditions:
• room temperature is higher than desired saving room temperature
• outdoor temperature is lower than the room temperature schedule 3 is in Comfort mode
The shown diagram is a fundamental and simplified example and does not contain all components that are necessary in a system.
All named components are connected to the ECL Comfort controller.
List of components:
ECL 310 Electronic controller ECL Comfort 310
ECA 32 Built-in extension module
S1 Outdoor temperature sensor
S2 (Optional) Compensation temperature sensor
S3 Duct temperature sensor
S4 Room temperature sensor*
S5 (Optional) Return temperature sensor
S6 (Optional) Frost temperature sensor
S7 (Optional) Frost thermostat
S8 (Optional) Fire thermostat
S9 Fan monitor
S10 Filter monitor
S11 Inlet pressure sensor
S12 Outlet pressure sensor
S13 Entry duct temperature sensor
S14 Exit duct temperature sensor
F1 Fan (ON / OFF)
P2 Damper (ON / OFF)
X3 Circulation pump, heating (ON / OFF)
X4 Schedule 3
X5 Circulation pump, cooling (ON / OFF)
P7 Recovery circuit pump, ON / OFF, (not illustrated)
M1 Motorized control valve, heating (3-point controlled)
M2 Rotating heat-exchanger (0 - 10 volt controlled)
M3 Motorized control valve, cooling (3-point controlled)
V2 Fan speed (0 - 10 volt controlled)
V3 Fan speed (0 - 10 volt controlled)
A1 Alarm
* Alternative: ECA 30
18 DEN-SMT/DK VI.GU.A2.02
Danfoss District Energy
Installation Guide ECL Comfort 210 / 310, application A214 / A314
Heating / cooling with room temperature and air pressure control (continued)
M1 and M3 are 3-point controlled, whereas M2 is 0-10 V controlled.
For a description of alarms, compensation temperature, return temperature limitation (S5) and frost protection (S6 and S7), please read the section ‘A214 and A314 in general’.
Danfoss District Energy VI.GU.A2.02
DEN-SMT/DK 19
Installation Guide ECL Comfort 210 / 310, application A214 / A314
The advanced heating application A314.7 is very flexible. These are the basic principles:
Heating / cooling with room temperature and air quality control
Typically, the heating temperature is adjusted according to your requirements. The air duct temperature sensor S3 is the most important sensor. The desired temperature at S3 is set in the ECL
Comfort controller as the 'Desired inlet temperature'.
The recovery circuit, controlled by M2, is considered as the main circuit, whereas the heating circuit (controlled by M1) and the cooling circuit (controlled by M3) are the supplementary circuits.
The motorized control valve M1 (controlling the heating temperature) is opened gradually when the S3 temperature is lower than the desired S3 temperature and vice versa.
At cooling, the motorized control valve M3 controls the cooling temperature.
Typical A314.7 application:
S 1
P 2
S 10
M 2
A
S 14
X 3
S 13
S 10
ECL 310
+ ECA 32
A 1 X 4
S 2
S 5
S 6
S 7
M 1
X 5
M 3
S 9
F1 / V2
F1 / V3
S 11
S 9
S 3
S 8
S 8
S 4
•
Room temperature:
If the room temperature (S4 or ECA 30) does not equal the desired room temperature, the desired temperature at S3 can be adjusted.
A too low temperature at S4 will activate the heating circuit (M1), whereas a too high air duct temperature will activate the cooling circuit (M3). A "Dead zone" (= number of degrees) can be set in order to avoid unstable shifts between heating and cooling operation.
By means of a week schedule (up to 3 ‘Comfort’ periods / day), the heating circuit can be in ‘Comfort’ or ‘Saving’ mode (two different temperature values for desired inlet temperature and two different temperature values for desired room temperature).
The fan F1 is ON / OFF controlled according to the schedule and heating demand. A damper P2 can be ON / OFF controlled according to schedule. The circulation pump X3 is ON / OFF controlled according to heating demand.
Air quality control (CO
2 measured in "ppm"):
The fans V2 and V3 are increased in speed when the ppm value (0 -
10 volt signal measured by S11) exceeds a selectable limit. Speed relation between V2 and V3 can be set. As an alternative, the S11 signal can express an RH signal (Relative Humidity).
Heat recovery:
In order to utilize heat from the exit air duct, a rotating heat-exchanger, a cross heat-exchanger or a fluid battery can be controlled by M2. Based on the outdoor temperature S1, the entry duct temperature S13 and the exit duct temperature S14 the recovery efficiency (in %) can be indicated.
Night cooling:
During Saving mode a passive cooling can be arranged, mainly under the following conditions:
• room temperature is higher than desired saving room temperature
• outdoor temperature is lower than the room temperature schedule 3 is in Comfort mode
The shown diagram is a fundamental and simplified example and does not contain all components that are necessary in a system.
All named components are connected to the ECL Comfort controller.
List of components:
ECL 310 Electronic controller ECL Comfort 310
ECA 32 Built-in extension module
S1 Outdoor temperature sensor
S2 (Optional) Compensation temperature sensor
S3 Duct temperature sensor
S4 Room temperature sensor*
S5 (Optional) Return temperature sensor
S6 (Optional) Frost temperature sensor
S7 (Optional) Frost thermostat
S8 (Optional) Fire thermostat
S9 Fan monitor
S10 Filter monitor
S11 Air quality (CO
2
) signal (ppm). Alternative: Relative
Humidity signal
S13 Entry duct temperature sensor
S14 Exit duct temperature sensor
F1 Fan (ON / OFF)
P2 Damper (ON / OFF)
X3 Circulation pump, heating (ON / OFF)
X4 Schedule 3
X5 Circulation pump, cooling (ON / OFF)
P7 Recovery circuit pump ON / OFF, (not illustrated)
M1 Motorized control valve, heating (3-point controlled)
M2 Rotating heat-exchanger (0 - 10 volt controlled)
M3 Motorized control valve, cooling (3-point controlled)
V2 Fan speed (0 - 10 volt controlled)
V3 Fan speed (0 - 10 volt controlled)
A1 Alarm
* Alternative: ECA 30
20 DEN-SMT/DK VI.GU.A2.02
Danfoss District Energy
Installation Guide ECL Comfort 210 / 310, application A214 / A314
Heating / cooling with room temperature and air quality control (continued)
M1 and M3 are 3-point controlled, whereas M2 is 0-10 V controlled.
For a description of alarms, compensation temperature, return temperature limitation (S5) and frost protection (S6 and S7), please read the section ‘A214 and A314 in general’.
Danfoss District Energy VI.GU.A2.02
DEN-SMT/DK 21
Installation Guide ECL Comfort 210 / 310, application A214 / A314
The advanced heating application A314.9 is very flexible. These are the basic principles:
Heating with room temperature and air quality control
Typically, the heating temperature is adjusted according to your requirements. The air duct temperature sensor S3 is the most important sensor. The desired temperature at S3 is set in the ECL
Comfort controller as the 'Desired inlet temperature'.
The air mixing circuit, controlled by M2, is considered as the main circuit, whereas the heating circuit, controlled by M1, is the supplementary circuit.
The motorized control valve M1 (controlling the heating temperature) is opened gradually when the S3 temperature is lower than the desired S3 temperature and vice versa.
Room temperature:
If the room temperature (S4 or ECA 30) does not equal the desired room temperature, the desired temperature at S3 can be adjusted.
By means of a week schedule (up to 3 ‘Comfort’ periods / day), the heating circuit can be in ‘Comfort’ or ‘Saving’ mode (two different temperature values for desired inlet temperature and two different temperature values for desired room temperature).
The fan F1 is ON / OFF controlled according to the schedule and heating demand. A damper P2 can be ON / OFF controlled according to schedule. The circulation pump X3 is ON / OFF controlled according to heating demand.
Air quality control (CO
2 measured in "ppm"):
When the ppm value (0 - 10 volt signal measured by S11) exceeds a selectable limit, the damper M2 gradually opens in order to supply more fresh air.
When M2 is fully open, the fans V2 and V3 are gradually increased in speed until the ppm value is acceptable. Speed relation between
V2 and V3 can be set.
As an alternative, the S11 signal can express an RH signal (Relative
Humidity).
Ventilation during saving period:
A desired fan speed can be set.
• Room temperature signal must be present
• The night damper P8 will open
• The fan V2 will operate at reduced speed
• The fan V3 is OFF
• P2 is OFF
• M2 is OFF
M1 is 3-point controlled, whereas M2 is 0-10 V controlled.
For a description of alarms, compensation temperature, return temperature limitation (S5) and frost protection (S6 and S7), please read the section ‘A214 and A314 in general’.
Typical A314.9 application:
S 1
S 10
M 2
A
X 3
S 10
ECL 310
+ ECA 32
A 1 P 2 X 4
S 2
S 5
S 6
S 7
M 1
S 9
F1 / V2
F1 / V3
S 11
S 9
S 3
S 8
S 8
S 4
The shown diagram is a fundamental and simplified example and does not contain all components that are necessary in a system.
All named components are connected to the ECL Comfort controller.
List of components:
ECL 310 Electronic controller ECL Comfort 310
ECA 32 Built-in extension module
S1 Outdoor temperature sensor
S2 (Optional) Compensation temperature sensor
S3 Duct temperature sensor
S4 Room temperature sensor*
S5 (Optional) Return temperature sensor
S6 (Optional) Frost temperature sensor
S7 (Optional) Frost thermostat
S8 (Optional) Fire thermostat
S9 Fan monitor
S10 Filter monitor
S11 Air quality (CO
2
) signal (ppm). Alternative: Relative
Humidity signal
F1 Fan (ON / OFF)
P2 Damper (ON / OFF), not illustrated
X3 Circulation pump, heating (ON / OFF)
X4 Schedule 3
P8 Night damper, not illustrated
M1 Motorized control valve, heating (3-point controlled)
M2 Motorized damper (0 - 10 volt controlled)
V2 Fan speed (0 - 10 volt controlled)
V3 Fan speed (0 - 10 volt controlled)
A1 Alarm
* Alternative: ECA 30
22 DEN-SMT/DK VI.GU.A2.02
Danfoss District Energy
Installation Guide ECL Comfort 210 / 310, application A214 / A314
A214 and A314 in general:
Compensation temperature (optional):
If the measured compensation temperature (S1 or S2) is higher or lower than the limitation value, the desired temperature at S3 can be adjusted. The compensation temperature can be measured by the outdoor temperature sensor or for example an additional room temperature sensor.
Override possibilities:
Unused input can, by means of an override switch, be used to override the schedule to a fixed 'Comfort' or 'Saving' mode.
Alarm functions:
The alarm (relay 4 in ECL 210, relay 6 in ECL 310) is activated:
1. If an unaccepted deviation between the desired and actual S3 temperature occurs.
2. If a frost thermostat (S7) is activated.
3. If a frost temperature is detected at S5 or S6.
4. If the fire alarm (S8) is activated.
5. If a temperature sensor or its connection disconnects / short circuits.
A214.2, A214.3, A214.4, A214.5, A314.1, A314.2 and A314.3:
Return temperature (optional):
If the measured return temperature (S5) does not equal the limitation value (typically, the return temperature becomes higher than the limitation value), the desired temperature at S3 can be adjusted (typically to a lower value). This results in a gradual closing of the motorized control valve.
Frost protection (optional):
Temperature sensor S6 and / or frost thermostat S7 can protect the heat exchanger against frost.
Furthermore, if the S5 temperature becomes too low, it also can enable the frost protection.
An activated frost protection will start the alarm, stop the fan F1, close the damper P2 and fully open the motorized control valve M1.
Fire alarm (optional):
An activated fire alarm input will start the alarm, stop the fan F1, close the damper P2 and close the motorized control valves.
Danfoss District Energy VI.GU.A2.02
DEN-SMT/DK 23
Installation Guide ECL Comfort 210 / 310, application A214 / A314
A314.4, A314.5, A314.6 and A314.7:
Efficiency calculation:
( Entry duct - Outdoor ) x 100
( Exit duct - Outdoor )
= %
Example:
Outdoor (S1)
=
7 °C
Entry duct (S13) = 16 °C
Exit duct (S14)
= 24 °C
( 16 - 7 ) x
100
= 53 %
( 24 - 7 )
A314.4, A314.5, A314.6 and A314.7:
Circuit 1's overview display shows output status for M1.
An approximate %-value for M1's position is also indicated in order to follow the control procedure.
The controller is pre-programmed with factory settings that are shown in the ‘Parameter ID overview’ appendix.
24 DEN-SMT/DK VI.GU.A2.02
Danfoss District Energy
Installation Guide ECL Comfort 210 / 310, application A214 / A314
2.2 Identifying the system type
Sketch your application
The ECL Comfort controller series is designed for a wide range of heating, domestic hot-water (DHW) and cooling systems with different configurations and capacities. If your system differs from the diagrams shown here, you may want to make a sketch of the system about to be installed. This makes it easier to use the Installation Guide, which will guide you step-by-step from installation to final adjustments before the end-user takes over.
The ECL Comfort controller is a universal controller that can be used for various systems. Based on the shown standard systems, it is possible to configure additional systems. In this chapter you find the most frequently used systems. If your system is not quite as shown below, find the diagram which has the best resemblance with your system and make your own combinations.
The circulation pump(s) in heating circuit(s) can be placed in the flow as well as the return. Place the pump according to the manufacturer’s specification.
A214.1 example a
Ventilation system with cooling and constant room temperature control
S 1
ECL 210 / 310
A1
P 2
X3
M2
S 5
F1 S 3
S 4
S 8
Setting advice:
Set desired room temperature, for example 20 °C.
Set desired balance temperature, for example 12 °C.
If a room temperature sensor is not connected, the desired duct temperature at S3 will correspond to the desired room temperature.
Danfoss District Energy VI.GU.A2.02
DEN-SMT/DK 25
Installation Guide ECL Comfort 210 / 310, application A214 / A314
A214.1 example b
Ventilation system with cooling and constant room temperature control. Chiller has constant flow.
S 1 ECL 210 / 310
A1
F1 S 3
S 8
S 4
S 5
X3
M2
Setting advice:
Set desired room temperature, for example 20 °C.
Set desired balance temperature, for example 12 °C.
If a room temperature sensor is not connected, the desired duct temperature at S3 will correspond to the desired room temperature.
A214.1 example c
Ventilation system (fan coils) with cooling and constant room temperature control
S 1 ECL 210 / 310
A1
F1 F1
S 4
M2
S 3
S 5
X3
Setting advice:
Set desired room temperature, for example 5 °C.
Set desired balance temperature, for example 1 °C.
If a room temperature sensor is not connected, the desired flow temperature at S3 will correspond to the desired room temperature.
26 DEN-SMT/DK VI.GU.A2.02
Danfoss District Energy
Installation Guide ECL Comfort 210 / 310, application A214 / A314
A214.1 example d
Cooling system with constant flow temperature control
S 1 ECL 210 / 310
A1
M2
S 3
F1
Setting advice:
Set desired room temperature, for example 1 °C.
If a room temperature sensor is not connected, the desired flow temperature at S3 will correspond to the desired room temperature.
Set ‘Fan cut-in delay’ (ID no. 11086 — ‘Settings’, ‘Fan / acc. control’) to 0 seconds.
A214.1 example e
Cooling system in ceiling and constant room temperature control in for example a wine cellar
S 1 ECL 210 / 310
A1
M2
S 3
S 4
F1
Setting advice:
Set desired room temperature, for example 14 °C.
Set desired balance temperature, for example 10 °C.
If a room temperature sensor is not connected, the desired flow temperature at S3 will correspond to the desired room temperature.
Set ‘Fan cut-in delay’ (ID no. 11086 — ‘Settings’, ‘Fan / acc. control’) to 0 seconds.
Danfoss District Energy VI.GU.A2.02
DEN-SMT/DK 27
Installation Guide ECL Comfort 210 / 310, application A214 / A314
A214.2 example a
Ventilation system with heating and constant duct temperature control
S 1
ECL 210 / 310
A1
M1
S 3
X3
S 5
P 2
S 6
F1 S 4
S 7
S 8
Sensor advice:
Sensor S3 and S4 must be connected. If not, the fan (F1) stops, the damper (P2) and motorized control valve (M1) close.
Navigation:
Special settings for sensors / thermostats used as frost protection:
S6* frost temperature sensor — MENU \ Alarm \ Frost T \ Alarm value
S5 return temperature sensor — MENU \ Alarm \ Limit T frost \ Alarm value
Closing contact of the S7* frost thermostat — MENU \ Alarm \ Frost thermostat \ Alarm value
Opening contact of the S7* frost thermostat — MENU \ Alarm \ Frost thermostat \ Alarm value
* both frost protection methods, by means of S6 and / or S7, can be used
Special settings for thermostats used as fire alarm:
Closing contact of the S8 fire thermostat — MENU \ Alarm \ Fire safety \ Alarm value
Opening contact of the S8 fire thermostat — MENU \ Alarm \ Fire safety \ Alarm value
ID no.: Recommended setting:
11676
11656
11616
11616
5 °C
5 °C
0
1
11636
11636
0
1
28 DEN-SMT/DK VI.GU.A2.02
Danfoss District Energy
Installation Guide ECL Comfort 210 / 310, application A214 / A314
A214.2 example b
Heating of a swimming pool, constant water temperature control
S 1 ECL 210 / 310
A1
S 3
M1
S 5
F1
S 4
Sensor advice:
Sensor S3 and S4 must be connected. If not, the pump (F1) stops and motorized control valve (M1) closes.
Navigation:
Special settings for sensors / thermostats used as frost protection:
S6* frost temperature sensor — MENU \ Alarm \ Frost T \ Alarm value
S5 return temperature sensor — MENU \ Alarm \ Limit T frost \ Alarm value
Closing contact of the S7* frost thermostat — MENU \ Alarm \ Frost thermostat \ Alarm value
Opening contact of the S7* frost thermostat — MENU \ Alarm \ Frost thermostat \ Alarm value
* both frost protection methods, by means of S6 and / or S7, can be used
Special settings for thermostats used as fire alarm:
Closing contact of the S8 fire thermostat — MENU \ Alarm \ Fire safety \ Alarm value
Opening contact of the S8 fire thermostat — MENU \ Alarm \ Fire safety \ Alarm value
Other settings:
Fan cut-in delay — MENU \ Settings \ Fan / acc. control
ID no.:
Recommended setting:
11676
11656
11616
11616
5 °C
5 °C
0
1
11636
11636
11086
0
1
0
Danfoss District Energy VI.GU.A2.02
DEN-SMT/DK 29
Installation Guide ECL Comfort 210 / 310, application A214 / A314
A214.3 example a
Ventilation system with heating and constant room temperature control
S 1
ECL 210 / 310
A1
P 2
X3
M1
S 5
S 6
F1 S 3
S 7
S 8
S 4
Setting advice:
Set desired room temperature, for example 20 °C.
Set desired balance temperature, for example 20 °C.
If a room temperature sensor is not connected, the desired duct temperature at S3 will correspond to the desired room temperature.
Navigation:
Special settings for sensors / thermostats used as frost protection:
S6* frost temperature sensor — MENU \ Alarm \ Frost T \ Alarm value
S5 return temperature sensor — MENU \ Alarm \ Limit T frost \ Alarm value
Closing contact of the S7* frost thermostat — MENU \ Alarm \ Frost thermostat \ Alarm value
Opening contact of the S7* frost thermostat — MENU \ Alarm \ Frost thermostat \ Alarm value
* both frost protection methods, by means of S6 and / or S7, can be used
Special settings for thermostats used as fire alarm:
Closing contact of the S8 fire thermostat — MENU \ Alarm \ Fire safety \ Alarm value
Opening contact of the S8 fire thermostat — MENU \ Alarm \ Fire safety \ Alarm value
ID no.: Recommended setting:
11676
11656
11616
11616
5 °C
5 °C
0
1
11636
11636
0
1
30 DEN-SMT/DK VI.GU.A2.02
Danfoss District Energy
Installation Guide ECL Comfort 210 / 310, application A214 / A314
A214.3 example b
Ventilation system (fan coils) with heating and constant room temperature control
S 1 ECL 210 / 310
A1
F1 F1
S 4
S 3
X3
S 5
M1
Setting advice:
Set desired room temperature, for example 20 °C.
Set desired balance temperature, for example 35 °C.
If a room temperature sensor is not connected, the desired flow temperature at S3 will correspond to the desired room temperature.
Navigation:
Special settings for sensors / thermostats used as frost protection:
S6* frost temperature sensor — MENU \ Alarm \ Frost T \ Alarm value
S5 return temperature sensor — MENU \ Alarm \ Limit T frost \ Alarm value
Closing contact of the S7* frost thermostat — MENU \ Alarm \ Frost thermostat \ Alarm value
Opening contact of the S7* frost thermostat — MENU \ Alarm \ Frost thermostat \ Alarm value
* both frost protection methods, by means of S6 and / or S7, can be used
Special settings for thermostats used as fire alarm:
Closing contact of the S8 fire thermostat — MENU \ Alarm \ Fire safety \ Alarm value
Opening contact of the S8 fire thermostat — MENU \ Alarm \ Fire safety \ Alarm value
ID no.: Recommended setting:
11676
11656
11616
11616
5 °C
5 °C
0
1
11636
11636
0
1
Danfoss District Energy VI.GU.A2.02
DEN-SMT/DK 31
Installation Guide ECL Comfort 210 / 310, application A214 / A314
A214.4 example a
Ventilation system with heating, cooling and constant duct temperature control
S 1
ECL 210 / 310
A1
M1 M2
S 3
X3
S 5
P 2
S 6 F1
S 4
S 7
S 8
Sensor advice:
Sensor S3 and S4 must be connected. If not, the fan (F1) stops, the damper (P2) and motorized control valves (M1 / M2) close.
Navigation:
Special settings for sensors / thermostats used as frost protection:
S6* frost temperature sensor — MENU \ Alarm \ Frost T \ Alarm value
S5 return temperature sensor — MENU \ Alarm \ Limit T frost \ Alarm value
Closing contact of the S7* frost thermostat — MENU \ Alarm \ Frost thermostat \ Alarm value
Opening contact of the S7* frost thermostat — MENU \ Alarm \ Frost thermostat \ Alarm value
* both frost protection methods, by means of S6 and / or S7, can be used
Special settings for thermostats used as fire alarm:
Closing contact of the S8 fire thermostat — MENU \ Alarm \ Fire safety \ Alarm value
Opening contact of the S8 fire thermostat — MENU \ Alarm \ Fire safety \ Alarm value
ID no.: Recommended setting:
11676
11656
11616
11616
5 °C
5 °C
0
1
11636
11636
0
1
32 DEN-SMT/DK VI.GU.A2.02
Danfoss District Energy
Installation Guide ECL Comfort 210 / 310, application A214 / A314
A214.4 example b
Ventilation system with heating, passive cooling (outside air) and constant duct temperature control
ECL 210 / 310
S 1
A1
M1
S 3
X3
S 5
P 2 M2
S 6
F1 S 4
S 7
S 8
Sensor advice:
Sensor S3 and S4 must be connected. If not, the fan (F1) stops, the damper (P2) and motorized control valves (M1 / M2) close.
Navigation:
Special settings for sensors / thermostats used as frost protection:
S6* frost temperature sensor — MENU \ Alarm \ Frost T \ Alarm value
S5 return temperature sensor — MENU \ Alarm \ Limit T frost \ Alarm value
Closing contact of the S7* frost thermostat — MENU \ Alarm \ Frost thermostat \ Alarm value
Opening contact of the S7* frost thermostat — MENU \ Alarm \ Frost thermostat \ Alarm value
* both frost protection methods, by means of S6 and / or S7, can be used
Special settings for thermostats used as fire alarm:
Closing contact of the S8 fire thermostat — MENU \ Alarm \ Fire safety \ Alarm value
Opening contact of the S8 fire thermostat — MENU \ Alarm \ Fire safety \ Alarm value
ID no.: Recommended setting:
11676
11656
11616
11616
5 °C
5 °C
0
1
11636
11636
0
1
Danfoss District Energy VI.GU.A2.02
DEN-SMT/DK 33
Installation Guide ECL Comfort 210 / 310, application A214 / A314
A214.5 example a
Ventilation system with heating, cooling and constant room temperature control
S 1
ECL 210 / 310
A1
M1 M2
P 2
X3
S 5
S 6
S 7
F1
S 3
S 8
S 4
Setting advice:
Set desired room temperature, for example 20 °C.
Set desired balance temperature, for example 20 °C.
If a room temperature sensor is not connected, the desired duct temperature at S3 will correspond to the desired room temperature.
Navigation:
Special settings for sensors / thermostats used as frost protection:
S6* frost temperature sensor — MENU \ Alarm \ Frost T \ Alarm value
S5 return temperature sensor — MENU \ Alarm \ Limit T frost \ Alarm value
Closing contact of the S7* frost thermostat — MENU \ Alarm \ Frost thermostat \ Alarm value
Opening contact of the S7* frost thermostat — MENU \ Alarm \ Frost thermostat \ Alarm value
* both frost protection methods, by means of S6 and / or S7, can be used
Special settings for thermostats used as fire alarm:
Closing contact of the S8 fire thermostat — MENU \ Alarm \ Fire safety \ Alarm value
Opening contact of the S8 fire thermostat — MENU \ Alarm \ Fire safety \ Alarm value
ID no.: Recommended setting:
11676
11656
11616
11616
5 °C
5 °C
0
1
11636
11636
0
1
34 DEN-SMT/DK VI.GU.A2.02
Danfoss District Energy
Installation Guide ECL Comfort 210 / 310, application A214 / A314
A214.5 example b
Ventilation system with heating, passive cooling (outside air) and constant room temperature control
ECL 210 / 310
S 1
A1
M1
P 2 M2
X3
S 5
S 6
F1 S 3
S 7
S 8
S 4
Setting advice:
Set desired room temperature, for example 20 °C.
Set desired balance temperature, for example 20 °C.
If a room temperature sensor is not connected, the desired duct temperature at S3 will correspond to the desired room temperature.
Navigation:
Special settings for sensors / thermostats used as frost protection:
S6* frost temperature sensor — MENU \ Alarm \ Frost T \ Alarm value
S5 return temperature sensor — MENU \ Alarm \ Limit T frost \ Alarm value
Closing contact of the S7* frost thermostat — MENU \ Alarm \ Frost thermostat \ Alarm value
Opening contact of the S7* frost thermostat — MENU \ Alarm \ Frost thermostat \ Alarm value
* both frost protection methods, by means of S6 and / or S7, can be used
Special settings for thermostats used as fire alarm:
Closing contact of the S8 fire thermostat — MENU \ Alarm \ Fire safety \ Alarm value
Opening contact of the S8 fire thermostat — MENU \ Alarm \ Fire safety \ Alarm value
ID no.: Recommended setting:
11676
11656
11616
11616
5 °C
5 °C
0
1
11636
11636
0
1
Danfoss District Energy VI.GU.A2.02
DEN-SMT/DK 35
Installation Guide ECL Comfort 210 / 310, application A214 / A314
A214.5 example c
Ventilation system with heating, cross-flow heat exchanger control and constant room temperature control
S 1 ECL 210 / 310
A1
M1
P 2
M2
X3
S 5
S 6
F1 S 3
S 7
S 8
S 4
Setting advice:
Set desired room temperature, for example 20 °C.
Set desired balance temperature, for example 20 °C.
If a room temperature sensor is not connected, the desired duct temperature at S3 will correspond to the desired room temperature.
Navigation:
Special settings for sensors / thermostats used as frost protection:
S6* frost temperature sensor — MENU \ Alarm \ Frost T \ Alarm value
S5 return temperature sensor — MENU \ Alarm \ Limit T frost \ Alarm value
Closing contact of the S7* frost thermostat — MENU \ Alarm \ Frost thermostat \ Alarm value
Opening contact of the S7* frost thermostat — MENU \ Alarm \ Frost thermostat \ Alarm value
* both frost protection methods, by means of S6 and / or S7, can be used
Special settings for thermostats used as fire alarm:
Closing contact of the S8 fire thermostat — MENU \ Alarm \ Fire safety \ Alarm value
Opening contact of the S8 fire thermostat — MENU \ Alarm \ Fire safety \ Alarm value
ID no.: Recommended setting:
11676
11656
11616
11616
5 °C
5 °C
0
1
11636
11636
0
1
36 DEN-SMT/DK VI.GU.A2.02
Danfoss District Energy
Installation Guide ECL Comfort 210 / 310, application A214 / A314
A214.6 example a
Heating system with 3–port mixing valve
A214.6 example b
Heating system with heat exchanger
Setting advice:
Sensor S3 must be connected. If not, the pump (F1) stops and motorized control valve (M1) closes.
Danfoss District Energy VI.GU.A2.02
DEN-SMT/DK 37
Installation Guide ECL Comfort 210 / 310, application A214 / A314
A314.1 example a
Ventilation system with heating, passive cooling (outside air) and constant duct temperature control. Analog controlled passive cooling (M2).
S 1
ECL 310
+ ECA 32
A1
S 2
M1
S 3
X3
P 2 M2
A
S 5
S 6
F1
S 4
S 7
S 8
Sensor advice:
Sensor S3 and S4 must be connected. If not, the fan (F1) stops, the damper (P2) and motorized control valves (M1 / M2) close.
Navigation:
Special settings for sensors / thermostats used as frost protection:
S6* frost temperature sensor — MENU \ Alarm \ Frost T \ Alarm value
S5 return temperature sensor — MENU \ Alarm \ Limit T frost \ Alarm value
Closing contact of the S7* frost thermostat — MENU \ Alarm \ Frost thermostat \ Alarm value
Opening contact of the S7* frost thermostat — MENU \ Alarm \ Frost thermostat \ Alarm value
* both frost protection methods, by means of S6 and / or S7, can be used
Special settings for thermostats used as fire alarm:
Closing contact of the S8 fire thermostat — MENU \ Alarm \ Fire safety \ Alarm value
Opening contact of the S8 fire thermostat — MENU \ Alarm \ Fire safety \ Alarm value
ID no.: Recommended setting:
11676
11656
11616
11616
5 °C
5 °C
0
1
11636
11636
0
1
38 DEN-SMT/DK VI.GU.A2.02
Danfoss District Energy
Installation Guide ECL Comfort 210 / 310, application A214 / A314
A314.1 example b
Ventilation system with heating, cooling and constant duct temperature control. Analog controlled cooling (M2).
S 1
ECL 310
+ ECA 32
A1
S 2
M1 M2
A
S 3
X3
S 5
P 2
S 6
F1
S 4
S 7
S 8
Sensor advice:
Sensor S3 and S4 must be connected. If not, the fan (F1) stops, the damper (P2) and motorized control valves (M1 / M2) close.
Navigation:
Special settings for sensors / thermostats used as frost protection:
S6* frost temperature sensor — MENU \ Alarm \ Frost T \ Alarm value
S5 return temperature sensor — MENU \ Alarm \ Limit T frost \ Alarm value
Closing contact of the S7* frost thermostat — MENU \ Alarm \ Frost thermostat \ Alarm value
Opening contact of the S7* frost thermostat — MENU \ Alarm \ Frost thermostat \ Alarm value
* both frost protection methods, by means of S6 and / or S7, can be used
Special settings for thermostats used as fire alarm:
Closing contact of the S8 fire thermostat — MENU \ Alarm \ Fire safety \ Alarm value
Opening contact of the S8 fire thermostat — MENU \ Alarm \ Fire safety \ Alarm value
ID no.: Recommended setting:
11676
11656
11616
11616
5 °C
5 °C
0
1
11636
11636
0
1
Danfoss District Energy VI.GU.A2.02
DEN-SMT/DK 39
Installation Guide ECL Comfort 210 / 310, application A214 / A314
A314.2 example a
Ventilation system with heating, passive cooling (outside air) and constant room temperature control. Analog controlled passive cooling (M2).
S 1
ECL 310
+ ECA 32
A1
S 2
M1
P 2 M2
A
X3
S 5
S 6
F1
S 3
S 7
S 8
S 4
Setting advice:
Set desired room temperature, for example 20 °C.
Set desired balance temperature, for example 20 °C.
If a room temperature sensor is not connected, the desired duct temperature at S3 will correspond to the desired room temperature.
Navigation:
Special settings for sensors / thermostats used as frost protection:
S6* frost temperature sensor — MENU \ Alarm \ Frost T \ Alarm value
S5 return temperature sensor — MENU \ Alarm \ Limit T frost \ Alarm value
Closing contact of the S7* frost thermostat — MENU \ Alarm \ Frost thermostat \ Alarm value
Opening contact of the S7* frost thermostat — MENU \ Alarm \ Frost thermostat \ Alarm value
* both frost protection methods, by means of S6 and / or S7, can be used
Special settings for thermostats used as fire alarm:
Closing contact of the S8 fire thermostat — MENU \ Alarm \ Fire safety \ Alarm value
Opening contact of the S8 fire thermostat — MENU \ Alarm \ Fire safety \ Alarm value
ID no.: Recommended setting:
11676
11656
11616
11616
5 °C
5 °C
0
1
11636
11636
0
1
40 DEN-SMT/DK VI.GU.A2.02
Danfoss District Energy
Installation Guide ECL Comfort 210 / 310, application A214 / A314
A314.2 example b
Ventilation system with heating, cooling and constant room temperature control. Analog controlled cooling (M2).
S 1
ECL 310
+ ECA 32
A1
S 2
M1 M2
A
S 5
X3
P 2
S 6
F1
S 3
S 4
S 7
S 8
Setting advice:
Set desired room temperature, for example 20 °C.
Set desired balance temperature, for example 20 °C.
If a room temperature sensor is not connected, the desired duct temperature at S3 will correspond to the desired room temperature.
Navigation:
Special settings for sensors / thermostats used as frost protection:
S6* frost temperature sensor — MENU \ Alarm \ Frost T \ Alarm value
S5 return temperature sensor — MENU \ Alarm \ Limit T frost \ Alarm value
Closing contact of the S7* frost thermostat — MENU \ Alarm \ Frost thermostat \ Alarm value
Opening contact of the S7* frost thermostat — MENU \ Alarm \ Frost thermostat \ Alarm value
* both frost protection methods, by means of S6 and / or S7, can be used
Special settings for thermostats used as fire alarm:
Closing contact of the S8 fire thermostat — MENU \ Alarm \ Fire safety \ Alarm value
Opening contact of the S8 fire thermostat — MENU \ Alarm \ Fire safety \ Alarm value
ID no.: Recommended setting:
11676
11656
11616
11616
5 °C
5 °C
0
1
11636
11636
0
1
Danfoss District Energy VI.GU.A2.02
DEN-SMT/DK 41
Installation Guide ECL Comfort 210 / 310, application A214 / A314
A314.3 example a
Ventilation system with heating and constant room temperature control. Analog controlled fan speed (V1) based on outdoor wind speed.
S 1
ECL 310
+ ECA 32
A1
S 2
M1
S10
S 5
X3
P 2
S 6
F1 / V1
S 3
S 7
S 8
S 4
Setting advice:
Set desired room temperature, for example 20 °C.
Set desired balance temperature, for example 35 °C.
If a room temperature sensor is not connected, the desired duct temperature at S3 will correspond to the desired room temperature.
Navigation:
Special settings for sensors / thermostats used as frost protection:
S6* frost temperature sensor — MENU \ Alarm \ Frost T \ Alarm value
S5 return temperature sensor — MENU \ Alarm \ Limit T frost \ Alarm value
Closing contact of the S7* frost thermostat — MENU \ Alarm \ Frost thermostat \ Alarm value
Opening contact of the S7* frost thermostat — MENU \ Alarm \ Frost thermostat \ Alarm value
* both frost protection methods, by means of S6 and / or S7, can be used
Special settings for thermostats used as fire alarm:
Closing contact of the S8 fire thermostat — MENU \ Alarm \ Fire safety \ Alarm value
Opening contact of the S8 fire thermostat — MENU \ Alarm \ Fire safety \ Alarm value
ID no.: Recommended setting:
11676
11656
11616
11616
5 °C
5 °C
0
1
11636
11636
0
1
42 DEN-SMT/DK VI.GU.A2.02
Danfoss District Energy
Installation Guide ECL Comfort 210 / 310, application A214 / A314
A314.3 example b
Ventilation system with heating and constant room temperature control. Analog controlled air curtain (V1) speed based on outdoor wind speed.
S 1
ECL 310
+ ECA 32
A1
S 2
V1
A
M1
S10
S 5
X3
P 2
S 6
F1
S 3
S 4
S 7
S 8
Setting advice:
Set desired room temperature, for example 20 °C.
Set desired balance temperature, for example 35 °C.
If a room temperature sensor is not connected, the desired duct temperature at S3 will correspond to the desired room temperature.
Navigation:
Special settings for sensors / thermostats used as frost protection:
S6* frost temperature sensor — MENU \ Alarm \ Frost T \ Alarm value
S5 return temperature sensor — MENU \ Alarm \ Limit T frost \ Alarm value
Closing contact of the S7* frost thermostat — MENU \ Alarm \ Frost thermostat \ Alarm value
Opening contact of the S7* frost thermostat — MENU \ Alarm \ Frost thermostat \ Alarm value
* both frost protection methods, by means of S6 and / or S7, can be used
Special settings for thermostats used as fire alarm:
Closing contact of the S8 fire thermostat — MENU \ Alarm \ Fire safety \ Alarm value
Opening contact of the S8 fire thermostat — MENU \ Alarm \ Fire safety \ Alarm value
ID no.: Recommended setting:
11676
11656
11616
11616
5 °C
5 °C
0
1
11636
11636
0
1
Danfoss District Energy VI.GU.A2.02
DEN-SMT/DK 43
Installation Guide ECL Comfort 210 / 310, application A214 / A314
A314.4 example a
Ventilation system with heating, passive cooling (outside air) and room temperature control. Analog controlled speed of fans in relation to pressures. Analog controlled speed of rotary heat exchanger (M2) for heat recovery.
A314.4 example b
Ventilation system with heating, passive cooling (outside air) and room temperature control. Analog controlled speed of fans in relation to pressures. Analog controlled damper (M2) for heat recovery by means of a cross heat exchanger.
44 DEN-SMT/DK VI.GU.A2.02
Danfoss District Energy
Installation Guide ECL Comfort 210 / 310, application A214 / A314
A314.4 example c
Ventilation system with heating, passive cooling (outside air) and room temperature control. Analog controlled speed of fans in relation to pressures. Analog controlled speed of rotary heat exchanger (M2) for heat recovery. Control of Night damper P8 for reduced ventilation during saving periods.
A314.4 example d
Ventilation system with heating, passive cooling (outside air) and room temperature control. Analog controlled speed of fans in relation to pressures. Analog controlled damper (M2) for heat recovery by means of a cross heat exchanger. Control of Night damper P8 for reduced ventilation during saving periods.
Danfoss District Energy VI.GU.A2.02
DEN-SMT/DK 45
Installation Guide ECL Comfort 210 / 310, application A214 / A314
A314.4 example e
Ventilation system with heating, passive cooling (outside air) and room temperature control. Analog controlled speed of fans in relation to pressures. Analog controlled valve (M2) for heat recovery by means of a Fluid battery. Control of Night damper P8 for reduced ventilation during saving periods.
Sensor advice:
Sensor S3 must be connected. If not, the fan F1 stops and motorized control valve M1 closes.
S1, S13 and S14 must be connected in order to calculate the recovery efficiency.
Navigation:
Special settings for sensors / thermostats used as frost protection:
S6* frost temperature sensor — MENU \ Alarm \ Frost T \ Alarm value
S5 return temperature sensor — MENU \ Alarm \ Limit T frost \ Alarm value
Closing contact of the S7* frost thermostat — MENU \ Alarm \ Frost thermostat \ Alarm value
Opening contact of the S7* frost thermostat — MENU \ Alarm \ Frost thermostat \ Alarm value
* both frost protection methods, by means of S6 and / or S7, can be used
Special settings for thermostats used as fire alarm:
Closing contact of the S8 fire thermostat — MENU \ Alarm \ Fire safety \ Alarm value
Opening contact of the S8 fire thermostat — MENU \ Alarm \ Fire safety \ Alarm value
ID no.: Recommended setting:
11676
11656
11616
11616
5 °C
5 °C
0
1
11636
11636
0
1
46 DEN-SMT/DK VI.GU.A2.02
Danfoss District Energy
Installation Guide ECL Comfort 210 / 310, application A214 / A314
A314.5 example a
Ventilation system with heating, passive cooling (outside air) and room temperature control. Analog controlled speed of fans in relation to air quality (CO
2
). Analog controlled speed of rotary heat exchanger (M2) for heat recovery.
A314.5 example b
Ventilation system with heating, passive cooling (outside air) and room temperature control. Analog controlled speed of fans in relation to air quality (CO
2
). Analog controlled damper (M2) for heat recovery by means of a cross heat exchanger.
Danfoss District Energy VI.GU.A2.02
DEN-SMT/DK 47
Installation Guide ECL Comfort 210 / 310, application A214 / A314
A314.5 example c
Ventilation system with heating, passive cooling (outside air) and room temperature control. Analog controlled speed of fans in relation to air quality (CO
2
). Analog controlled speed of rotary heat exchanger (M2) for heat recovery. Control of Night damper P8 for reduced ventilation during saving periods.
A314.5 example d
Ventilation system with heating, passive cooling (outside air) and room temperature control. Analog controlled speed of fans in relation to air quality (CO
2
). Analog controlled damper (M2) for heat recovery by means of a cross heat exchanger. Control of Night damper
P8 for reduced ventilation during saving periods.
48 DEN-SMT/DK VI.GU.A2.02
Danfoss District Energy
Installation Guide ECL Comfort 210 / 310, application A214 / A314
A314.5 example e
Ventilation system with heating, passive cooling (outside air) and room temperature control. Analog controlled speed of fans in relation to air quality (CO
2
). Analog controlled valve (M2) for heat recovery by means of a Fluid battery. Control of Night damper P8 for reduced ventilation during saving periods.
Sensor advice:
Sensor S3 must be connected. If not, the fan F1 stops and motorized control valve M1 closes.
S1, S13 and S14 must be connected in order to calculate the recovery efficiency.
Navigation:
Special settings for sensors / thermostats used as frost protection:
S6* frost temperature sensor — MENU \ Alarm \ Frost T \ Alarm value
S5 return temperature sensor — MENU \ Alarm \ Limit T frost \ Alarm value
Closing contact of the S7* frost thermostat — MENU \ Alarm \ Frost thermostat \ Alarm value
Opening contact of the S7* frost thermostat — MENU \ Alarm \ Frost thermostat \ Alarm value
* both frost protection methods, by means of S6 and / or S7, can be used
Special settings for thermostats used as fire alarm:
Closing contact of the S8 fire thermostat — MENU \ Alarm \ Fire safety \ Alarm value
Opening contact of the S8 fire thermostat — MENU \ Alarm \ Fire safety \ Alarm value
ID no.: Recommended setting:
11676
11656
11616
11616
5 °C
5 °C
0
1
11636
11636
0
1
Danfoss District Energy VI.GU.A2.02
DEN-SMT/DK 49
Installation Guide ECL Comfort 210 / 310, application A214 / A314
A314.6 example a
Ventilation system with heating, cooling and room temperature control. Analog controlled speed of fans in relation to pressures. Analog controlled speed of rotary heat exchanger (M2) for heat recovery.
S 1
ECL 310
+ ECA 32
A 1 X 4
S 2
P 2
S 10
M 2
A
S 14
X 3
S 13
S 10
S 5
S 6
S 7
M 1
X 5
M 3
S 9
S 11
S 3
F1 / V2
F1 / V3
S 12
S 8
S 8
S 4
S 9
A314.6 example b
Ventilation system with heating, cooling and room temperature control. Analog controlled speed of fans in relation to pressures. Analog controlled damper (M2) for heat recovery by means of a cross heat exchanger.
S 1
ECL 310
+ ECA 32
A 1 X 4
S 2
P 2
S 10
A
M 2
X 3
S 13
S 5
S 6
S 7
M 1
X 5
M 3
S 9
S 11
S 3
F1 / V2
S 8
S 4
F1 / V3
S 12
S 8
S 14
S 10 S 9
50 DEN-SMT/DK VI.GU.A2.02
Danfoss District Energy
Installation Guide ECL Comfort 210 / 310, application A214 / A314
A314.6 example c
Ventilation system with heating, cooling and room temperature control. Analog controlled speed of fans in relation to pressures. Analog controlled valve (M2) for heat recovery by means of a Fluid battery.
S 1
ECL 310
+ ECA 32
A 1 X 4
S 2
P 2
S 10
M 2
A
P 7
X 3
S 13
S 5
S 6
S 7
M 1
X 5
M 3
S 9
S 11
S 3
F1 / V2
S 8
S 4
F1 / V3
S 12
S 8
S 14
S 10 S 9
Sensor advice:
Sensor S3 must be connected. If not, the fan F1 stops and motorized control valve M1 closes.
S1, S13 and S14 must be connected in order to calculate the recovery efficiency.
Navigation:
Special settings for sensors / thermostats used as frost protection:
S6* frost temperature sensor — MENU \ Alarm \ Frost T \ Alarm value
S5 return temperature sensor — MENU \ Alarm \ Limit T frost \ Alarm value
Closing contact of the S7* frost thermostat — MENU \ Alarm \ Frost thermostat \ Alarm value
Opening contact of the S7* frost thermostat — MENU \ Alarm \ Frost thermostat \ Alarm value
* both frost protection methods, by means of S6 and / or S7, can be used
Special settings for thermostats used as fire alarm:
Closing contact of the S8 fire thermostat — MENU \ Alarm \ Fire safety \ Alarm value
Opening contact of the S8 fire thermostat — MENU \ Alarm \ Fire safety \ Alarm value
ID no.: Recommended setting:
11676
11656
11616
11616
5 °C
5 °C
0
1
11636
11636
0
1
Danfoss District Energy VI.GU.A2.02
DEN-SMT/DK 51
Installation Guide ECL Comfort 210 / 310, application A214 / A314
A314.7 example a
Ventilation system with heating, cooling and room temperature control. Analog controlled speed of fans in relation to air quality (CO
2
).
Analog controlled speed of rotary heat exchanger (M2) for heat recovery.
S 1
ECL 310
+ ECA 32
A 1 X 4
S 2
P 2
S 10
M 2
A
S 14
X 3
S 13
S 5
S 6
S 7
M 1
X 5
M 3
S 9
F1 / V2
F1 / V3
S 11
S 3
S 8
S 8
S 4
S 10 S 9
A314.7 example b
Ventilation system with heating, cooling and room temperature control. Analog controlled speed of fans in relation to air quality (CO
2
).
Analog controlled damper (M2) for heat recovery by means of a cross heat exchanger.
S 1
ECL 310
+ ECA 32
A 1 X 4
S 2
P 2
S 10
A
M 2
X 3
S 13
S 5
S 6
S 7
M 1
X 5
M 3
S 9
F1 / V2
S 3
S 8
S 4
F1 / V3
S 11
S 8
S 14
S 10 S 9
52 DEN-SMT/DK VI.GU.A2.02
Danfoss District Energy
Installation Guide ECL Comfort 210 / 310, application A214 / A314
A314.7 example c
Ventilation system with heating, cooling and room temperature control. Analog controlled speed of fans in relation to air quality (CO
2
).
Analog controlled valve (M2) for heat recovery by means of a Fluid battery.
S 1
ECL 310
+ ECA 32
A 1 X 4
S 2
P 2
S 10
M 2
A
P 7
X 3
S 13
S 5
S 6
S 7
M 1
X 5
M 3
S 9
F1 / V2
F1 / V3
S 11
S 3
S 8
S 4
S 8
S 14
S 10 S 9
Sensor advice:
Sensor S3 must be connected. If not, the fan F1 stops and motorized control valve M1 closes.
S1, S13 and S14 must be connected in order to calculate the recovery efficiency.
Navigation:
Special settings for sensors / thermostats used as frost protection:
S6* frost temperature sensor — MENU \ Alarm \ Frost T \ Alarm value
S5 return temperature sensor — MENU \ Alarm \ Limit T frost \ Alarm value
Closing contact of the S7* frost thermostat — MENU \ Alarm \ Frost thermostat \ Alarm value
Opening contact of the S7* frost thermostat — MENU \ Alarm \ Frost thermostat \ Alarm value
* both frost protection methods, by means of S6 and / or S7, can be used
Special settings for thermostats used as fire alarm:
Closing contact of the S8 fire thermostat — MENU \ Alarm \ Fire safety \ Alarm value
Opening contact of the S8 fire thermostat — MENU \ Alarm \ Fire safety \ Alarm value
ID no.: Recommended setting:
11676
11656
11616
11616
5 °C
5 °C
0
1
11636
11636
0
1
Danfoss District Energy VI.GU.A2.02
DEN-SMT/DK 53
Installation Guide ECL Comfort 210 / 310, application A214 / A314
A314.9 example a
Ventilation system with heating and room temperature control. Analog controlled speed of fans in relation to air quality (CO
2
).
S 1
ECL 310
+ ECA 32
A 1 P 2 X 4
S 2
S 10
M 2
A
X 3
M 1
S 5
S 9
S 6
S 7
F1 / V2
F1 / V3
S 11
S 3
S 8
S 8
S 4
S 10 S 9
54 DEN-SMT/DK VI.GU.A2.02
Danfoss District Energy
Installation Guide ECL Comfort 210 / 310, application A214 / A314
A314.9 example b
Ventilation system with heating and room temperature control. Analog controlled speed of fans in relation to air quality (CO
2
). ON-OFF control of damper P2.
S 1
ECL 310
+ ECA 32
A 1 X 4
S 2
P 2
S 10
M 2
A
X 3
M 1
S 5
S 9
S 6
S 7
F1 / V2
F1 / V3
S 11
S 3
S 8
S 8
S 4
S 10 S 9
Sensor advice:
Sensor S3 must be connected. If not, the fan F1 stops and motorized control valve M1 closes.
S1, S13 and S14 must be connected in order to calculate the recovery efficiency.
Navigation:
Special settings for sensors / thermostats used as frost protection:
S6* frost temperature sensor — MENU \ Alarm \ Frost T \ Alarm value
S5 return temperature sensor — MENU \ Alarm \ Limit T frost \ Alarm value
Closing contact of the S7* frost thermostat — MENU \ Alarm \ Frost thermostat \ Alarm value
Opening contact of the S7* frost thermostat — MENU \ Alarm \ Frost thermostat \ Alarm value
* both frost protection methods, by means of S6 and / or S7, can be used
Special settings for thermostats used as fire alarm:
Closing contact of the S8 fire thermostat — MENU \ Alarm \ Fire safety \ Alarm value
Opening contact of the S8 fire thermostat — MENU \ Alarm \ Fire safety \ Alarm value
ID no.: Recommended setting:
11676
11656
11616
11616
5 °C
5 °C
0
1
11636
11636
0
1
Danfoss District Energy VI.GU.A2.02
DEN-SMT/DK 55
Installation Guide ECL Comfort 210 / 310, application A214 / A314
2.3 Mounting
2.3.1 Mounting the ECL Comfort controller
For easy access, you should mount the ECL Comfort controller near the system. Select one of the following methods using the same base part (code no. 087H3230):
• Mounting on a wall
• Mounting on a DIN rail (35 mm)
The ECL Comfort 310 can only be mounted in the ECL Comfort
310 base part.
Screws, PG cable glands and rawlplugs are not supplied.
Locking the ECL Comfort controller
In order to fasten the ECL Comfort controller to its base part, secure the controller with the locking pin.
56 DEN-SMT/DK
To prevent injuries to persons or the controller, the controller has to be securely locked into the base. For this purpose, press the locking pin into the base until a click is heard and the controller no longer can be removed from the base.
If the controller is not securely locked into the base part, there is a risk that the controller during operation can unlock from the base and the base with terminals (and also the 230 V a.c. connections) are exposed.
To prevent injuries to persons, always make sure that the controller is securely locked into its base. If this is not the case, the controller should not be operated!
The easy way to lock the controller to its base or unlock it is to use a screw driver as lever.
VI.GU.A2.02
Danfoss District Energy
Installation Guide ECL Comfort 210 / 310, application A214 / A314
Mounting on a wall
Mount the base part on a wall with a smooth surface. Establish the electrical connections and position the controller in the base part.
Secure the controller with the locking pin.
Mounting on a DIN rail (35 mm)
Mount the base part on a DIN rail. Establish the electrical connections and position the controller in the base part. Secure the controller with the locking pin.
Dismounting the ECL Comfort controller
In order to remove the controller from the base part, pull out the locking pin by means of a screwdriver. The controller can now be removed from the base part.
Danfoss District Energy
The easy way to lock the controller to its base or unlock it is to use a screw driver as lever.
Before removing the ECL Comfort controller from the base part, ensure that the supply voltage is disconnected.
VI.GU.A2.02
DEN-SMT/DK 57
Installation Guide ECL Comfort 210 / 310, application A214 / A314
2.3.2 Mounting the Remote Control Units ECA 30 / 31
Select one of the following methods:
• Mounting on a wall, ECA 30 / 31
• Mounting in a panel, ECA 30
Screws and rawlplugs are not supplied.
Mounting on a wall
Mount the base part of the ECA 30 / 31 on a wall with a smooth surface. Establish the electrical connections. Place the ECA 30 /
31 in the base part.
Mounting in a panel
Mount the ECA 30 in a panel using the ECA 30 frame kit (order code no. 087H3236). Establish the electrical connections. Secure the frame with the clamp. Place the ECA 30 in the base part. The ECA
30 can be connected to an external room temperature sensor.
The ECA 31 must not be mounted in a panel if the humidity function is to be used.
58 DEN-SMT/DK VI.GU.A2.02
Danfoss District Energy
Installation Guide ECL Comfort 210 / 310, application A214 / A314
2.3.3 Mounting the internal I/O module ECA 32
Mounting of the internal I/O module ECA 32
The ECA 32 module (order code no. 087H3202) can be inserted into the ECL Comfort 310 / 310B basepart for additional input and output signals in relevant applications.
Danfoss District Energy VI.GU.A2.02
DEN-SMT/DK 59
Installation Guide ECL Comfort 210 / 310, application A214 / A314
2.4 Placing the temperature sensors
It is important that the sensors are mounted in the correct position in your system.
The temperature sensor mentioned below are sensors used for the ECL Comfort 210 and 310 series which not all will be needed for your application!
Outdoor temperature sensor (ESMT)
The outdoor sensor should be mounted on that side of the building where it is less likely to be exposed to direct sunshine. It should not be placed close to doors, windows or air outlets.
Flow temperature sensor (ESMU, ESM-11 or ESMC)
Place the sensor max. 15 cm from the mixing point. In systems with heat exchanger, Danfoss recommends that the ESMU-type to be inserted into the exchanger flow outlet.
Make sure that the surface of the pipe is clean and even where the sensor is mounted.
Return temperature sensor (ESMU, ESM-11 or ESMC)
The return temperature sensor should always be placed so that it measures a representative return temperature.
Room temperature sensor
(ESM-10, ECA 30 / 31 Remote Control Unit)
Place the room sensor in the room where the temperature is to be controlled. Do not place it on outside walls or close to radiators, windows or doors.
Boiler temperature sensor (ESMU, ESM-11 or ESMC)
Place the sensor according to the boiler manufacturer’s specification.
Air duct temperature sensor (ESMB-12 or ESMU types)
Place the sensor so that it measures a representative temperature.
DHW temperature sensor (ESMU or ESMB-12)
Place the DHW temperature sensor according to the manufacturer’s specification.
Slab temperature sensor (ESMB-12)
Place the sensor in a protection tube in the slab.
ESM-11: Do not move the sensor after it has been fastened in order to avoid damage to the sensor element.
ESM-11, ESMC and ESMB-12: Use heat conducting paste for quick measurement of the temperature.
ESMU and ESMB-12: Using a sensor pocket to protect the sensor will, however, result in a slower temperature measurement.
60 DEN-SMT/DK VI.GU.A2.02
Danfoss District Energy
Installation Guide ECL Comfort 210 / 310, application A214 / A314
Pt 1000 temperature sensor (IEC 751B, 1000 Ω / 0 °C) Relationship between temperature and ohmic value:
°C Ω
1271
1309
1347
1385
1423
1461
1498
1535
1573
1000
1039
1078
1117
1155
1194
1232
803
843
882
922
961
100
110
120
70
80
90
130
140
150
0
10
20
30
40
50
60
-50
-40
-30
-20
-10
1600
Ω
1500
1400
1300
1200
1100
1000
900
800
-50 -25 0 25 50 75 100 125 150
° C
Danfoss District Energy VI.GU.A2.02
DEN-SMT/DK 61
Installation Guide ECL Comfort 210 / 310, application A214 / A314
2.5 Electrical connections
2.5.1 Electrical connections 230 V a.c. in general
Safety Note
Necessary assembly, start-up, and maintenance work must be performed by qualified and authorized personnel only.
Local legislations must be respected. This comprises also cable size and isolation (reinforced type).
A fuse for the ECL Comfort installation is max. 10 A typically.
The ambient temperature range for the ECL Comfort in operation is
0 - 55 °C. Exceeding this temperature range can result in malfunctions.
Installation must be avoided if there is a risk for condensation (dew).
The common ground terminal is used for connection of relevant components (pumps, motorized control valves).
62 DEN-SMT/DK
Factory established jumpers in the base part:
5 to 8, 9 to 14, L to 5 and L to 9, N to 10
See also the A214 Mounting Guide (delivered with the application key) for application specific connections.
Electrical connections, 230 V a.c., power supply, pumps, dampers, motorized control valves etc.
Connections, in general:
See also the A214 Mounting Guide (delivered with the application key) for application specific connections.
VI.GU.A2.02
Danfoss District Energy
Installation Guide ECL Comfort 210 / 310, application A214 / A314
2.5.2 Electrical connections, 230 V a.c., power supply, pumps, dampers, motorized control valves etc.
Connections, in general.
See also the Mounting Guide (delivered with the application key) for application specific connections.
Terminals
ECL 210
16
15
14
13
ECL 310
19
18
17
16
15
14
13
12
12
11 11
6
5
4
8
7
10
9
4
3
6
5
8
7
10
9
230 V a.c., Neutral (N)
230 V a.c., Live (L)
3
2
1
* 4 A for ohmic load, 2 A for inductive load
Max. load
4 (2) A / 230 V a.c. *
4 (2) A / 230 V a.c. *
4 (2) A / 230 V a.c. *
4 (2) A / 230 V a.c. *
4 (2) A / 230 V a.c. *
4 (2) A / 230 V a.c. *
0,2 A / 230 V a.c.
0,2 A / 230 V a.c.
0,2 A / 230 V a.c.
0,2 A / 230 V a.c.
0,2 A / 230 V a.c.
0,2 A / 230 V a.c.
Factory established jumpers in the base part:
5 to 8, 9 to 14, L to 5 and L to 9, N to 10
Danfoss District Energy VI.GU.A2.02
DEN-SMT/DK 63
Installation Guide ECL Comfort 210 / 310, application A214 / A314
Electrical connections, ECA 32
Connections, in general.
See also the A214 Mounting Guide (delivered with the application key) for application specific connections.
E CA 32
43
42
41
40
39
48
47
4 6
45
44
P 7
P 8
L
230 V a .c.
N
Terminals
ECA 32
48
47
46
45
44
43
42
41
40
39
* 4 A for ohmic load, 2 A for inductive load
Max. load
4 (2) A / 230 V a.c. *
4 (2) A / 230 V a.c. *
4 (2) A / 230 V a.c. *
4 (2) A / 230 V a.c. *
4 (2) A / 230 V a.c. *
4 (2) A / 230 V a.c. *
Wire cross section: 0.5 - 1.5 mm²
Incorrect connection can damage the electronic outputs.
Max. 2 x 1.5 mm² wires can be inserted into each screw terminal.
64 DEN-SMT/DK VI.GU.A2.02
Danfoss District Energy
Installation Guide ECL Comfort 210 / 310, application A214 / A314
2.5.3 Electrical connections, 24 V a.c., power supply, pumps, dampers, motorized control valves etc.
Connections, in general.
See also the A214 Mounting Guide (delivered with the application key) for application specific connections.
Do not use a common transformer for ECL Comfort 310 and motorized valve / damper control. Use separate transformers.
Terminals
ECA 310
19
18
17
16
15
14
13
12
9
8
7
11
10
24 V a.c., (SN)
24 V a.c., (SP)
4
3
6
5
2
1
* 4 A for ohmic load, 2 A for inductive load
E CL Comfort 310
R 1
N
L
11
10
9
8
230 V / 24 V
S P
S N
0 - 10 V 0 - 10 V
S N S P Y
M
S N S P Y
M
E CL Comfort 310
R 1
N
L
11
10
9
8
2 30 V / 24 V
S P
S N
2 30 V / 24 V
S P
S N
0 - 10 V 0 - 10 V
S N S P Y
M
S N S P Y
M
Max. load
4 (2) A / 24 V a.c. *
4 (2) A / 24 V a.c. *
4 (2) A / 24 V a.c. *
4 (2) A / 24 V a.c. *
4 (2) A / 24 V a.c. *
4 (2) A / 24 V a.c. *
Factory established jumpers in the base part:
5 to 8, 9 to 14, L (SP) to 5 and L (SP) to 9, N (SN) to 10
Danfoss District Energy VI.GU.A2.02
1 A / 24 V a.c.
1 A / 24 V a.c.
1 A / 24 V a.c.
1 A / 24 V a.c.
1 A / 24 V a.c.
1 A / 24 V a.c.
DEN-SMT/DK 65
Installation Guide ECL Comfort 210 / 310, application A214 / A314
Do not connect 230 V a.c. powered components to a 24 V a.c. power supplied controller directly. Use auxilliary relays (K) to separate 230
V a.c. from 24 V a.c.
Wire cross section: 0.5 - 1.5 mm²
Incorrect connection can damage the electronic outputs.
Max. 2 x 1.5 mm² wires can be inserted into each screw terminal.
66 DEN-SMT/DK VI.GU.A2.02
Danfoss District Energy
Installation Guide ECL Comfort 210 / 310, application A214 / A314
Electrical connections, ECA 32
Connections, in general.
See also the A214 Mounting Guide (delivered with the application key) for application specific connections.
E CA 32
43
42
41
40
39
48
47
4 6
45
44
P 7
P 8
L
230 V a .c.
N
Terminals
ECA 32
48
47
46
45
44
43
42
41
40
39
* 4 A for ohmic load, 2 A for inductive load
Max. load
4 (2) A / 230 V a.c. *
4 (2) A / 230 V a.c. *
4 (2) A / 230 V a.c. *
4 (2) A / 230 V a.c. *
4 (2) A / 230 V a.c. *
4 (2) A / 230 V a.c. *
Danfoss District Energy VI.GU.A2.02
DEN-SMT/DK 67
Installation Guide ECL Comfort 210 / 310, application A214 / A314
Electrical connections, ECA 32
Connections, in general.
See also the A214 Mounting Guide (delivered with the application key) for application specific connections.
The transformers for supplying the actuators must be double-isolated versions.
Terminals
ECA 32
56
57
58
59
60
61
62
* The value must be 47 kΩ as a minimum.
Max. load
47 kΩ *
47 kΩ *
47 kΩ *
68 DEN-SMT/DK VI.GU.A2.02
Danfoss District Energy
Installation Guide ECL Comfort 210 / 310, application A214 / A314
Example showing separate transformers for ECL 310 supply and output connections:
ECL 310 24 V a .c.
11
10
9
8
29
30
3 1
230 V / 24 V
S P
S N
E CA 32
4 9
56
59
62
0 - 10 V
AMD
Y (BK)
S P
S N
(BN)
(BU)
230 V / 24 V
S P
S N
AMD = Danfoss damper actuator
Example showing supply for ECL 310 and output connections:
ECL 310 24 V a .c.
11
10
9
8
29
30
3 1
230 V / 24 V
S P
S N
ECA 32
4 9
56
59
62
0 - 10 V
V S D
V
Hz
F1 / V1
L
230 V a .c.
N
VSD = Variable Speed Drive
Example showing supply for ECL 310, 24 V a.c.
Separate transformer for supply of transmitter (for input) and output connections:
ECL 310 24 V a .c.
11
10
9
8
29
30
3 1
230 V / 24 V
S P
S N
ECA 3 2
4 9
5 0
56
59
62
0 - 10 V
0 - 10 V
AMD
Y (BK)
S P
S N
(BN)
(BU)
1 2 3
AMD = Danfoss damper actuator
230 V / 24 V
S P
S N
Danfoss District Energy VI.GU.A2.02
DEN-SMT/DK 69
Installation Guide ECL Comfort 210 / 310, application A214 / A314
2.5.4 Electrical connections, Pt 1000 temperature sensors
A214/ A314:
Terminal
29 and 30 S1 Outdoor temp. sensor *
28 and 30 S2 Compensation temp.
sensor **
27 and 30 S3 Air duct / flow temp. sensor
***
26 and 30
Sensor / description
S4 A214.1, A214.3, A214.5,
A214.6, A314.2 - A314.9:
Type
(recomm.)
ESMT
ESM-11 / ESMB
/
ESMC / ESMU /
ESMT
ESM-11 / ESMB
/
ESMC / ESMU
ESM-10
Room temp. sensor.
A214.2, A214.4, A314.1:
Flow temp. sensor.
25 and 30 S5 Return temp. sensor
ESM-11 / ESMB
/
ESMC / ESMU
ESM-11 / ESMB
/
ESMC / ESMU
ESMB
24 and 30
S6 Frost temp. sensor ****
(not used in A214.1)
23 and 30
S7
Frost thermostat *****
22 and 30 S8 Fire thermostat *****
21 and 30
S9
ECL 310 only.
A314.4 - A314.9:
Fan monitor
20 and 30 S10 ECL 310 only.
A314.3: Wind speed signal
(0 - 10 V).
A314.4 - A314.9:
Filter monitor
* If the outdoor temperature sensor is not connected or the cable is short-circuited, the controller assumes that the outdoor temperature is 0 (zero) °C.
** Could for example be an extra room temperature sensor.
***
If the sensor is not connected or the cable is short-circuited, the motorized control valve closes (safety function).
**** Both frost protection methods can be used.
***** Can be set up to react on a closing or an opening contact.
Factory established jumper:
30 to common terminal.
70 DEN-SMT/DK VI.GU.A2.02
Danfoss District Energy
Installation Guide ECL Comfort 210 / 310, application A214 / A314
Override contact
230 V a.c.
L
N
P E
S 2 S 1
E CL Comfort 210 / 310
28
29
3 0
31
3 2
+12 V
B
S 2
S 1
230 V a .c.
L
N
P E
S 2 S 1
E CL Comfort 210 / 310
28
29
3 0
31
3 2
+12 V
B
S 2
S 1
Example of override contact, connected to S8:
Danfoss District Energy VI.GU.A2.02
DEN-SMT/DK 71
Installation Guide ECL Comfort 210 / 310, application A214 / A314
Connection of frost thermostats, S7
When frost (too low temperature) is detected, contacts 1-2 close.
When frost (too low temperature) is detected, contacts 1-4 open.
Connections of Fan and Filter monitor (S9 and S10):
S10 S10 2 x S9
29
30
31
32
26
27
28
33
34
35
3 6
37
3 8
2 0
2 1
2 2
23
24
25
ECL 310
S 10
S 9
S 8
S 7
S 6
S 5
S 4
S 3
S 2
S 1
+12 V
B
A
B
A
S .Gnd
Wire cross section: 0.5 - 1.5 mm²
Incorrect connection can damage the electronic outputs.
Max. 2 x 1.5 mm² wires can be inserted into each screw terminal.
72 DEN-SMT/DK VI.GU.A2.02
Danfoss District Energy
Installation Guide ECL Comfort 210 / 310, application A214 / A314
Do not use common transformer when pressure transmitters are supplied by 24 V a.c.:
S11
S12
S13
ECA 3 2
49
50
51
5 2
1
2 3
0 - 10 V
ECL 310
2 8
29
3 0
3 1
0 - 10 V 0 - 10 V
230 V / 24 V
S P
S N
S N S P Y
M
S N S P Y
M
S 11
S 12
S 13
E CA 32
49
50
51
5 2
2 30 V / 24 V
S P
S N
2 30 V / 24 V
S P
S N
1
2 3
0 - 10 V
0 - 10 V
E CL 310
2 8
29
3 0
3 1
0 - 10 V
S N S P Y
M
S N S P Y
M
Danfoss District Energy VI.GU.A2.02
DEN-SMT/DK 73
Installation Guide ECL Comfort 210 / 310, application A214 / A314
Connections of inputs S11, S12, S13 and S14
(S11 and S12 transmitters generate 0 - 10 V)
(S11 and S12 transmitters generate 4 - 20 mA)
Example showing supply for ECL 310, 24 V a.c.
Separate transformer for supply of transmitter (for input) and output connections.
ECL 310 24 V a .c.
11
10
9
8
29
30
3 1
230 V / 24 V
S P
S N
ECA 3 2
4 9
5 0
56
59
62
0 - 10 V
0 - 10 V
AMD
Y (BK)
S P
S N
(BN)
(BU)
1 2 3
230 V / 24 V
S P
S N
AMD = Danfoss damper actuator
74 DEN-SMT/DK VI.GU.A2.02
Danfoss District Energy
Installation Guide ECL Comfort 210 / 310, application A214 / A314
2.5.5 Electrical connections, ECA 30 / 31
Terminal
ECL
30
31
32
33
Terminal
ECA 30 / 31
4
1
4
5
2
3
Description
Twisted pair
Twisted pair
Ext. room temperature sensor*
Type
(recomm.)
Cable 2 x twisted pair
ESM-10
* After an external room temperature sensor has been connected,
ECA 30 / 31 must be repowered.
The communication to the ECA 30 / 31 must be set up in the ECL
Comfort controller in 'ECA addr.'
The ECA 30 / 31 must be set up accordingly.
After application setup the ECA 30 / 31 is ready after 2–5 min. A progress bar in the ECA 30 / 31 is displayed.
ECA 30 / 31
ESM-10
ECL 210 / 310
B
A
B
A
Danfoss District Energy
Max. 2 ECA 30 / 31 can be connected to an ECL Comfort 310 controller or to ECL Comfort 310 controllers in a master-slave system.
Setup procedures for ECA 30 / 31: See section ‘Miscellaneous’.
VI.GU.A2.02
DEN-SMT/DK 75
Installation Guide ECL Comfort 210 / 310, application A214 / A314
ECA information message:
‘Application req. newer ECA’:
The software of your ECA does not comply with the software of your
ECL Comfort controller. Please contact your Danfoss sales office.
Some applications do not contain functions related to actual room temperature. The connected ECA 30 / 31 will only function as remote control.
Total cable length: Max. 200 m (all sensors incl. internal ECL 485 communication bus).
Cable lengths of more than 200 m may cause noise sensibility (EMC).
76 DEN-SMT/DK VI.GU.A2.02
Danfoss District Energy
Installation Guide ECL Comfort 210 / 310, application A214 / A314
2.5.6 Electrical connections, master / slave systems
The controller can be used as master or slave in master / slave systems via the internal ECL 485 communication bus (2 x twisted pair cable).
The ECL 485 communication bus is not compatible with the ECL bus in ECL Comfort 110, 200, 300 and 301!
Terminal Description Type
(recomm.)
30
31*
32
Common terminal
+12 V*, ECL 485 communication bus
33
B, ECL 485 communication bus
A, ECL 485 communication bus
Cable 2 x twisted pair
* Only for ECA 30 / 31 and master / slave communication
B
A
B
A
B
A
B
A
Total cable length: Max. 200 m (all sensors incl. internal ECL 485 communication bus).
Cable lengths of more than 200 m may cause noise sensibility (EMC).
Danfoss District Energy VI.GU.A2.02
DEN-SMT/DK 77
Installation Guide ECL Comfort 210 / 310, application A214 / A314
2.5.7 Electrical connections, communication
Electrical connections, Modbus
ECL Comfort 210: Non-galvanic isolated Modbus connections
ECL Comfort 310: Galvanic isolated Modbus connections
ECL 210 / 310
B
A
B
A
Electrical connections, M-bus
(ECL Comfort 310 and 310 B only)
ECL 310
B
A
B
A
Example, M-bus connections
(ECL Comfort 310 and 310 B only)
78 DEN-SMT/DK VI.GU.A2.02
Danfoss District Energy
Installation Guide ECL Comfort 210 / 310, application A214 / A314
2.6 Inserting the ECL Application Key
2.6.1 Inserting the ECL Application Key
The ECL Application Key contains
• the application and its subtypes,
• currently available languages,
• factory settings: e.g. schedules, desired temperatures, limitation values etc. It is always possible to recover the factory settings,
• memory for user settings: special user / system settings.
After having powered-up the controller, different situations might be existing:
1. The controller is new from the factory, the ECL Application Key is not inserted.
2. The controller already runs an application. The ECL Application
Key is inserted, but the application needs to be changed.
3. A copy of the controllers settings is needed for configuring another controller.
User settings are, among others, desired room temperature, desired
DHW temperature, schedules, heat curve, limitation values etc.
System settings are, among others, communication set-up, display brightness etc.
Danfoss District Energy VI.GU.A2.02
DEN-SMT/DK 79
Installation Guide ECL Comfort 210 / 310, application A214 / A314
Automatic update of controller software:
The software of the controller is updated automatically when the key is inserted (as of controller version 1.11). The following animation will be shown when the software is being updated:
Progress bar
During update:
• Do not remove the KEY
If the key is removed before the hour-glass is shown, you have to start afresh.
• Do not disconnect the power
If the power is interrupted when the hour-glass is shown, the controller will not work.
The “Key overview” does not inform — through ECA 30 / 31 — about the subtypes of the application key.
Key inserted / not inserted, description:
ECL Comfort 210 / 310, controller versions lower than 1.36:
-
-
Take out the application key; for 20 minutes settings can be changed.
Power up the controller without the application key inserted; for 20 minutes settings can be changed.
ECL Comfort 210 / 310, controller versions 1.36 and up:
-
-
Take out the application key; for 20 minutes settings can be changed.
Power up the controller without the application key inserted; settings cannot be changed.
80 DEN-SMT/DK VI.GU.A2.02
Danfoss District Energy
Installation Guide ECL Comfort 210 / 310, application A214 / A314
Application Key: Situation 1
The controller is new from the factory, the ECL Application Key is not inserted.
An animation for the ECL Application Key insertion is displayed.
Insert the Application Key .
Application Key name and Version is indicated (example: A266
Ver. 1.03).
If the ECL Application Key is not suitable for the controller, a "cross" is displayed over the ECL Application Key-symbol.
Action: Purpose:
Select language
Confirm
Select application
Confirm with ‘Yes’
Set 'Time & Date'
Turn and push the dial to select and change 'Hours', 'Minutes', 'Date',
'Month' and 'Year'.
Choose ''Next'
Confirm with ‘Yes’
Go to ‘Aut. daylight’
Choose whether ‘Aut. daylight´ * should be active or not
Examples:
YES or NO
* ‘Aut. daylight’ is the automatic changeover between summer and winter time.
Depending on the contents of the ECL Application Key, procedure
A or B is taking place:
A
The ECL Application key contains factory settings:
The controller reads / transfers data from the ECL Application Key to ECL controller.
The application is installed, and the controller resets and starts up.
B
The ECL Application key contains changed system settings:
Push the dial repeatedly.
’NO’: Only factory settings from the ECL Application Key will be copied to the controller.
’YES*: Special system settings (differing from the factory settings) will be copied to the controller.
If the key contains user settings:
Push the dial repeatedly.
‘NO: Only factory settings from the ECL Application Key will be copied to the controller.
‘YES*: Special user settings (differing from the factory settings) will be copied to the controller.
* If ‘YES’ cannot be chosen, the ECL Application Key does not contain any special settings.
Choose ‘Start copying’ and confirm with 'Yes'.
Danfoss District Energy VI.GU.A2.02
DEN-SMT/DK 81
Installation Guide ECL Comfort 210 / 310, application A214 / A314
Application Key: Situation 2
The controller already runs an application. The ECL Application
Key is inserted, but the application needs to be changed.
To change to another application on the ECL Application Key, the current application in the controller must be erased (deleted).
Be aware that the Application Key must be inserted.
Action: Purpose:
Choose ‘MENU’ in any circuit
Confirm
Choose the circuit selector at the top right corner in the display
Confirm
Choose ‘Common controller settings’
Confirm
Choose ‘Key functions’
Confirm
Choose ‘Erase application’
Examples:
Confirm with ‘Yes’
The controller resets and is ready to be configured.
Follow the procedure described in situation 1.
82 DEN-SMT/DK VI.GU.A2.02
Danfoss District Energy
Installation Guide ECL Comfort 210 / 310, application A214 / A314
Application Key: Situation 3
A copy of the controllers settings is needed for configuring another controller.
This function is used
• for saving (backup) of special user and system settings
• when another ECL Comfort controller of the same type (210 or
310) must be configured with the same application but user / system settings differ from the factory settings.
How to copy to another ECL Comfort controller:
*
‘ECL’:
‘KEY’:
Action: Purpose:
Choose ‘MENU’
Confirm
Choose the circuit selector at the top right corner in the display
Confirm
Choose 'Common controller settings'
Confirm
Go to ‘Key functions’
Examples:
Confirm
Choose ‘Copy’
Confirm
Choose ‘To’.
‘ECL’ or ‘KEY’ will be indicated. Choose
’ECL’ or KEY’
Push the dial repeatedly to choose copy direction
Choose ‘System settings’ or ‘User settings’
Push the dial repeatedly to choose
‘Yes’ or ‘No’ in ‘Copy’. Push to confirm.
*
’ECL’ or ‘KEY’.
**
‘NO’ or ‘YES’
Choose ‘Start copying’
The Application Key or the controller is updated with special system or user settings.
Data will be copied from the Application Key to the
ECL Controller.
Data will be copied from the ECL Controller to the
Application Key.
**
‘NO’:
‘YES’:
The settings from the ECL controller will not be copied to the Application Key or to the ECL Comfort controller.
Special settings (differing from the factory settings) will be copied to the Application Key or to the ECL Comfort controller. If YES can not be chosen, there are no special settings to be copied.
Danfoss District Energy VI.GU.A2.02
DEN-SMT/DK 83
Installation Guide ECL Comfort 210 / 310, application A214 / A314
2.6.2 ECL Application Key, copying data
General principles
When the controller is connected and operating, you can check and adjust all or some of the basic settings. The new settings can be stored on the Key.
How to update the ECL Application Key after settings have been changed?
All new settings can be stored on the ECL Application Key.
How to store factory setting in the controller from the
Application Key?
Please read the paragraph concerning Application Key, Situation
1: The controller is new from the factory, the ECL Application Key is not inserted.
How to store personal settings from the controller to the Key?
Please read the paragraph concerning Application Key, Situation 3:
A copy of the controllers settings is needed for configuring another controller
As a main rule, the ECL Application Key should always remain in the controller. If the Key is removed, it is not possible to change settings.
Factory settings can always be restored.
Make a note of new settings in the 'Settings overview' table.
Do not remove the ECL Application Key while copying. The data on the ECL Application Key can be damaged!
It is possible to copy settings from one ECL Comfort controller to another controller provided that the two controllers are from the same series (210 or 310).
The “Key overview” does not inform — through ECA 30 / 31 — about the subtypes of the application key.
Key inserted / not inserted, description:
ECL Comfort 210 / 310, controller versions lower than 1.36:
-
-
Take out the application key; for 20 minutes settings can be changed.
Power up the controller without the application key inserted; for 20 minutes settings can be changed.
ECL Comfort 210 / 310, controller versions 1.36 and up:
-
-
Take out the application key; for 20 minutes settings can be changed.
Power up the controller without the application key inserted; settings cannot be changed.
84 DEN-SMT/DK VI.GU.A2.02
Danfoss District Energy
Installation Guide ECL Comfort 210 / 310, application A214 / A314
2.7 Check list
Is the ECL Comfort controller ready for use?
Make sure that the correct power supply is connected to terminals 9 and 10 (230 V or 24 V).
Make sure the correct phase conditions are connected:
230 V: Live = terminal 9 and Neutral = terminal 10
24 V: SP = terminal 9 and SN = terminal 10
Check that the required controlled components (actuator, pump etc.) are connected to the correct terminals.
Check that all sensors / signals are connected to the correct terminals (see 'Electrical connections').
Mount the controller and switch on the power.
Is the ECL Application Key inserted (see 'Inserting the Application Key').
Does the ECL Comfort controller contain an existing application (see 'Inserting the Application Key').
Is the correct language chosen (see 'Language' in 'Common controller settings').
Is the time & date set correctly (see 'Time & Date' in 'Common controller settings').
Is the right application chosen (see 'Identifying the system type').
Check that all settings in the controller (see 'Settings overview') are set or that the factory settings comply with your requirements.
Choose manual operation (see 'Manual control'). Check that valves open and close, and that required controlled components (pump etc.) start and stop when operated manually.
Check that the temperatures / signals shown in the display match the actual connected components.
Having completed the manual operation check, choose controller mode (scheduled, comfort, saving or frost protection).
Danfoss District Energy VI.GU.A2.02
DEN-SMT/DK 85
Installation Guide ECL Comfort 210 / 310, application A214 / A314
2.8 Navigation, ECL Application Key A214 / A314
Navigation, A214, applications A214.1, A214.2, A214.3, A214.4, A214.5 and A214.6
Home
MENU
Schedule
Settings
Flow temperature
Room limit
Duct T limit
Return limit
Limit T safety
Compensation 1
Compensation 2
Control par. (1)
ID no.
Function
Selectable
11008 Desired balance T
11178 Temp. max.
11177 Temp. min.
11009 Dead zone
11182 Infl. - max.
11183
Infl. - min.
11015 Adapt. time
11182 Infl. - max.
11183 Infl. - min.
11015
Adapt. time
11030 Limit
11035
Infl. - max.
11036
Infl. - min.
11037 Adapt. time
11108
Limit T frost
11105 Infl. - min.
11107
Adapt. time
11139 Actual comp. T
11060
Limit
11062
Infl. - max.
11063
Infl. - min.
11061 Adapt. time
11139
Actual comp. T
11064 Limit
11066
Infl. - max.
11067
Infl. - min.
11065
Adapt. time
11174
Motor pr.
11184 Xp
11185 Tn
11186 M run
11187 Nz
11189 Min. act. time
Applications A214
A214.1
A214.2
A214.3
A214.4
A214.5
A214.6
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
86 DEN-SMT/DK VI.GU.A2.02
Danfoss District Energy
Installation Guide ECL Comfort 210 / 310, application A214 / A314
Navigation, A214, applications A214.1, A214.2, A214.3, A214.4, A214.5 and A214.6 continued
Home
MENU
Settings
Control par. 2
Fan / acc. control
Application
ID no.
Function
12174 Motor pr.
12184
Xp
12185
Tn
12186
M run
12187 Nz
12189
Min. act. time
11088
Fan output func.
11086
Fan cut-in delay
11137
Fan function
11089
Acc. output func.
11087 Acc. cut-in delay
11091
Acc. time control
11090
Optional function
11077
P frost T
11027
Room T diff.
11194 Stop difference
11010
ECA addr.
11500 Send desired T
11021
Total stop
11140 Comp. T select
11093 Frost pr. T
10304
S4 filter
11082
Accum. filter
11141
Ext. input
11142 Ext. mode
Applications, A214
A214.1
A214.2
A214.3
A214.4
A214.5
A214.6
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
( ( (
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
Danfoss District Energy VI.GU.A2.02
DEN-SMT/DK 87
Installation Guide ECL Comfort 210 / 310, application A214 / A314
Navigation, A214, applications A214.1, A214.2, A214.3, A214.4, A214.5 and A214.6 continued
Home
MENU
Holiday
Alarm
Frost T
Limit T frost
Frost thermostat
Influence overview
Fire safety
Temp. monitor.
Alarm overview
Des. flow T
ID no.
Function
Selectable
11676
Alarm value
11656
Alarm value
11616 Alarm value
11617
Alarm time-out
11636 Alarm value
11637
Alarm time-out
11147 Upper difference
11148
Lower difference
11149
Delay
11150
Lowest temp.
Frost T
Limit T frost
Frost thermostat
Fire safety
Temp. monitor.
Flow T sensor
Return lim.
Room lim.
Duct T limit
Compensation 1
Compensation 2
Limit T safety
Holiday
Ext. override
ECA override
SCADA offset
(
(
(
(
(
(
Applications A214
A214.1
A214.2
A214.3
A214.4
A214.5
A214.6
( ( ( ( ( (
( (
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
88 DEN-SMT/DK VI.GU.A2.02
Danfoss District Energy
Installation Guide ECL Comfort 210 / 310, application A214 / A314
Navigation, A214, applications A214.1, A214.2, A214.3, A214.4, A214.5 and A214.6, Common controller settings
Home
MENU
Time & Date
Schedule
Input overview
Log (sensors)
Output override
Log today
Log yesterday
Log 2 days
Log 4 days
ID no. Function
Applications A214, Common controller settings
A214.1
A214.2
A214.3
A214.4
A214.5
A214.6
Selectable
Selectable
Outdoor T
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
Compensation T
Flow T
(
(
(
(
(
(
(
(
(
(
(
(
Room T
( ( ( (
Duct T
( (
Return T
Frost T
Accumulated T
Frost thermostat
Fire safety
Outdoor T
Flow T & desired
Duct T & desired
Room T & desired
Return T & limit
Compensation T
Frost T
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
M1
F1
M2
P2
X3
A1
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
Danfoss District Energy VI.GU.A2.02
DEN-SMT/DK 89
Installation Guide ECL Comfort 210 / 310, application A214 / A314
Navigation, A214, applications A214.1, A214.2, A214.3, A214.4, A214.5 and A214.6, Common controller settings, continued
Home
MENU
Key functions
System
New application
Application
Factory setting
Copy
Key overview
ECL version
Extension
Ethernet
Portal config
M-bus config
Energy Meters
Raw input overview
Alarm
Display
Communication
Language
Applications A214, Common controller settings
ID no. Function A214.1
A214.2
A214.3
A214.4
A214.5
A214.6
Erase application
System settings
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
User settings
Go to factory
(
(
(
(
(
(
(
(
(
(
(
(
To
System settings
(
(
(
(
(
(
(
(
(
(
(
(
User settings
Start copying
Code no.
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
Hardware
Software
Build no.
(
(
(
(
(
Serial no.
Production date
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
T sensor defect
60058 Backlight
60059 Contrast
2048 ECL 485 addr.
38 Modbus addr.
39 Baud
2150 Service pin
2151 Ext. reset
2050 Language
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
90 DEN-SMT/DK VI.GU.A2.02
Danfoss District Energy
Installation Guide ECL Comfort 210 / 310, application A214 / A314
Navigation, A314, applications A314.1, 314.2 and A314.3
Home
MENU
Schedule
Settings
Flow temperature
Room limit
Duct T limit
Return limit
Limit T safety
Compensation 1
Compensation 2
Control par. (1)
ID no.
Function
Selectable
11008 Desired balance T
11178 Temp. max.
11177 Temp. min.
11009
Dead zone
11182 Infl. - max.
11183
Infl. - min.
11015 Adapt. time
Application A314
A314.1
A314.2
A314.3
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
11182 Infl. - max.
11183
Infl. - min.
11015
Adapt. time
11030 Limit
11035
Infl. - max.
11036
Infl. - min.
11037 Adapt. time
11108
Limit T frost
11105
Infl. - min.
11107
Adapt. time
11139
Actual comp. T
11060 Limit
11062 Infl. - max.
11063
Infl. - min.
11061 Adapt. time
11139
Actual comp. T
11064 Limit
11066
Infl. - max.
11067 Infl. - min.
11065
Adapt. time
11174 Motor pr.
11184 Xp
11185 Tn
11186 M run
11187 Nz
11189 Min. act. time
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
Danfoss District Energy VI.GU.A2.02
DEN-SMT/DK 91
Installation Guide ECL Comfort 210 / 310, application A214 / A314
Navigation, A314, applications A314.1, A314.2 and A314.3 continued
Home
MENU
Settings
Control par. 2
Fan / acc. control
Application
ID no.
Function
12174 Motor pr.
12184
Xp
12185
Tn
12187
Nz
12165 V out max.
12167
V out min.
12171
Reverse out
11098
Wind actual
11081
Filter constant
11104
Control voltage
Applications A314
A314.1
A314.2
A314.3
(
(
(
(
(
(
(
(
(
(
(
(
(
(
11088
11086
11137
11089
Fan output func.
Fan cut-in delay
Fan function
Acc. output func.
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
11087
Acc. cut-in delay
11091 Acc. time control
11090
Optional function
11077
P frost T
(
(
(
(
(
(
(
(
11027
11010
Room T diff.
ECA addr.
11500 Send desired T
11021
Total stop
11140 Comp. T select
11093 Frost pr. T
10304
S4 filter
11082
Accum. filter
11141
Ext. input
11142
Ext. mode
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
92 DEN-SMT/DK VI.GU.A2.02
Danfoss District Energy
Installation Guide ECL Comfort 210 / 310, application A214 / A314
Navigation, A314, applications A314.1, A314.2 and A314.3 continued
Home
MENU
Holiday
Alarm
Influence overview
Frost T
Limit T frost
Frost thermostat
Fire safety
Temp. monitor.
Alarm overview
Des. flow T
ID no.
11676
11656
11616
11617
Alarm time-out
11636 Alarm value
11637
Alarm time-out
11147 Upper difference
11148
Function
Selectable
Alarm value
Alarm value
Alarm value
Lower difference
11149
Delay
11150
Lowest temp.
Frost T
Limit T frost
Frost thermostat
Fire safety
Temp. monitor.
Flow T sensor
Return lim.
Applications A314
A314.1
A314.2
A314.3
( ( (
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
Room lim.
Duct T limit
Compensation 1
Compensation 2
Limit T safety
Holiday
Ext. override
ECA override
SCADA offset
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
Danfoss District Energy VI.GU.A2.02
DEN-SMT/DK 93
Installation Guide ECL Comfort 210 / 310, application A214 / A314
Navigation, A314, applications A314.1, A314.2 and A314.3, Common controller settings
Home
MENU
Time & Date
Schedule
Input overview
Log (sensors)
Output override
Log today
Log yesterday
Log 2 days
Log 4 days
ID no.
Applications A314, Common controller settings
Function
Selectable
Selectable
Outdoor T
Compensation T
Flow T
Room T
Duct T
Return T
Frost T
Accumulated T
Frost thermostat
Fire safety
Outdoor T
Flow T & desired
Duct T & desired
Room T & desired
Return T & limit
Compensation T
Frost T
Wind speed
M1
F1
V1
M2
P2
X3
A1
A314.1
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
A314.2
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
A314.3
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
94 DEN-SMT/DK VI.GU.A2.02
Danfoss District Energy
Installation Guide ECL Comfort 210 / 310, application A214 / A314
Navigation, A314, applications A314.1, A314.2 and A314.3, Common controller settings, continued
Home
MENU
Key functions
System
New application
Application
Factory setting
Copy
Key overview
ECL version
Extension
Ethernet
Portal config
M-bus config
Energy Meters
Raw input overview
Alarm
Display
Communication
Language
ID no.
Applications A314, Common controller settings
Function A314.1
A314.2
A314.3
Erase application
System settings
User settings
(
(
(
(
(
(
(
(
(
Go to factory
To
System settings
(
(
(
(
(
(
(
(
(
(
(
(
User settings
Start copying
Code no.
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
Hardware
Software
Build no.
Serial no.
Production date
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
T sensor defect
60058 Backlight
60059 Contrast
2048 ECL 485 addr.
38 Modbuss addr.
39 Baud
2150 Service pin
2151 Ext. reset
2050 Language
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
Danfoss District Energy VI.GU.A2.02
DEN-SMT/DK 95
Installation Guide ECL Comfort 210 / 310, application A214 / A314
Navigation, A314, applications A314.4, A314.5, A314.6, A314.7 and A314.9, circuit 1
Home
MENU
Schedule
Settings
Inlet temperature
Room limit
Return limit
Limit T safety
Compensation 1
Compensation 2
Control par. (1)
ID no.
Function
Selectable
11018 Des. T comfort
11019 Des. T saving
11178 Temp. max.
11177 Temp. min.
11009
Dead zone
11182 Infl. - max.
11183
Infl. - min.
11015
Adapt. time
11030
Limit
11035
Infl. - max.
11036 Infl. - min.
11037
Adapt. time
11108
Limit T frost
11105
Infl. - min.
11107
Adapt. time
11139
Actual comp. T
11060 Limit
11062
Infl. - max.
11063 Infl. - min.
11061
Adapt. time
11139 Actual comp. T
11064
Limit
11066
Infl. - max.
11067
Infl. - min.
11065 Adapt. time
11174 Motor pr.
11184 Xp
11185 Tn
11186 M run
11187
Nz
11189
Min. act. time
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
Applications 314
A314.4
A314.5
A314.6
A314.7
A314.9
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
96 DEN-SMT/DK VI.GU.A2.02
Danfoss District Energy
Installation Guide ECL Comfort 210 / 310, application A214 / A314
Navigation, A314, applications A314.4, A314.5, A314.6 , A314.7 and A314.9, circuit 1, continued
Home
MENU
Settings
Control par. 2
Fan / acc. control
Application
ID no.
Function
12368
1. step level
12369
2. step level
12184 Xp
12185 Tn
12187 Nz
12165 V out max.
12167 V out min.
11088
Fan output func.
11086
Fan cut-in delay
11137
Fan function
11089 Acc. output func.
11087
Acc. cut-in delay
11091 Acc. time control
11010
ECA addr.
11021 Total stop
11093 Frost pr. T
11140
Comp. T select
11368 1. step level
11369
2. step level
11179 Summer, cut-out
11082
Accum. filter
11141
Ext. input
11142 Ext. mode
(
(
(
(
(
(
Applications, A314
A314.4
A314.5
A314.6
A314.7
A314.9
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
Danfoss District Energy VI.GU.A2.02
DEN-SMT/DK 97
Installation Guide ECL Comfort 210 / 310, application A214 / A314
Navigation, A314, applications A314.4, A314.5, A314.6 , A314.7 and A314.9, circuit 1, continued
Home
MENU
Holiday
Alarm
Frost T
Limit T frost
Frost thermostat
Fire safety
Digital S9
Digital S10
Inlet pressure
Outlet pressure
Air quality
Temp. monitor.
Heat recovery
ID no.
Function
Selectable
11676
Alarm value
11656
Alarm value
11616 Alarm value
11617
Alarm time-out
11636 Alarm value
11637
Alarm time-out
10656 Alarm value
10657
Alarm time-out
12390 Clear alarm
10696
Alarm value
10697 Alarm time-out
13614
Alarm high
13615 Alarm low
13617
Alarm time-out
13390 Clear alarm
14614
Alarm high
14615 Alarm low
14617
Alarm time-out
14390 Clear alarm
13614
Alarm high
13615 Alarm low
13617
Alarm time-out
11147
Upper difference
11148
Lower difference
11149
Delay
11150 Lowest temp.
12615
Alarm low
12617 Alarm time-out
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
Applications A314
A314.4
A314.5
A314.6
A314.7
A314.9
( ( ( ( (
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
98 DEN-SMT/DK VI.GU.A2.02
Danfoss District Energy
Installation Guide ECL Comfort 210 / 310, application A214 / A314
Navigation, A314, applications A314.4, A314.5, A314.6 , A314.7 and A314.9, circuit 1, continued
Home
MENU
Influence overview
Alarm overview
Desired inlet T
ID no.
Function
Frost T
Limit T frost
Frost thermostat
Fire safety
Temp. monitor.
Inlet T sensor
Digital S9
Digital S10
Air quality
Inlet pressure
Outlet pressure
Heat recovery
T sensor defect
Return lim.
Room lim.
Compensation 1
Compensation 2
Limit T safety
Holiday
Ext. override
SCADA offset
Applications A314
A314.4
A314.5
A314.6
A314.7
A314.9
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
Danfoss District Energy VI.GU.A2.02
DEN-SMT/DK 99
Installation Guide ECL Comfort 210 / 310, application A214 / A314
Navigation, A314, applications A314.4, A314.5, A314.6 , A314.7 and A314.9, circuit 2
Home
MENU
Settings
Control par., inlet
Control par., outlet
ID no.
13600
Function
Pressure
13113
Filter constant
13406 X1
13407 X2
12321
Pressure, des.
11168
Max. Pressure
11169
Min. Pressure
13184 Xp
13185
Tn
13187
Nz
13165
V out max.
13167
V out min.
13357
Fan speed, red.
13600 Pressure
14113
Filter constant
14406 X1
14407 X2
12321
Pressure, des.
12168
Max. Pressure
12169
Min. Pressure
14184 Xp
14185
Tn
14187
Nz
14165
V out max.
12167
V out min.
(
(
(
(
(
(
(
(
(
(
(
(
Applications, A314
A314.4
A314.5
A314.6
A314.7
A314.9
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
100 DEN-SMT/DK VI.GU.A2.02
Danfoss District Energy
Installation Guide ECL Comfort 210 / 310, application A214 / A314
Navigation, A314, applications A314.4, A314.5, A314.6 , A314.7 and A314.9, circuit 2, continued
Home
MENU
Settings
Control par., fan
Control par., cool.
Application
ID no.
Function
13339
Air quality
13113 Filter constant
13406 X1
13407 X2
13111 Limit
13184 Xp
13185 Tn
13187
13165
13167
15184
15185
15186
15187
15189
11038
11194
11077
Nz
V out max.
V out min.
13357
Fan speed, red.
13356
Outlet fan, offset
Xp
Tn
M run
Nz
Min. act. time
Stop at T out
Stop difference
P frost T
Applications, A314
A314.4
A314.5
A314.6
A314.7
A314.9
( ( (
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
Danfoss District Energy VI.GU.A2.02
DEN-SMT/DK 101
Installation Guide ECL Comfort 210 / 310, application A214 / A314
Navigation, A314, applications A314.4, A314.5, A314.6, A314.7 and A314.9, Common controller settings
Home
MENU
Time & Date
Schedule
Input overview
Log (sensors)
Output override
Log today
Log yesterday
Log 2 days
Log 4 days
ID no.
P2
X3
A1
Function
Selectable
Selectable
Outdoor T
Applications A314, Common controller settings
A314.4
A314.5
A314.6
A314.7
A314.9
Outdoor acc. T
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
Accumulated T
Compensation T
Inlet T
(
(
(
(
(
(
(
(
(
Room T
Return T
Frost T
Entry duct T
Exit duct T
Frost thermostat
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
Fire safety
Digtial S9
Digtial S10
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
Inlet pressure
Outlet pressure
(
(
(
(
(
(
Air quality
Outdoor T
Inlet T & desired
Room T & desired
Return T & limit
Compensation T
Frost T
Press. inlet & des.
Press. outlet & des.
Air quality & limit
M1
F1
M2
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
V2
V3
X4
P7
P8
M3
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
102 DEN-SMT/DK VI.GU.A2.02
Danfoss District Energy
Installation Guide ECL Comfort 210 / 310, application A214 / A314
Navigation, A314, applications A314.4, A314.5, A314.6 , A314.7 and A314.9, Common controller settings, continued
Home
MENU
Key functions
System
New application
Application
Factory setting
Copy
Key overview
ECL version
Extension
Ethernet
Portal config
M-bus config
Energy Meters
Raw input overview
Alarm
Display
Communication
Language
ID no.
Function
Applications A314, Common controller settings
A314.4
A314.5
A314.6
A314.7
A314.9
Erase application
System settings
User settings
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
Go to factory
To
System settings
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
User settings
Start copying
Code no.
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
Hardware
Software
Build no.
Serial no.
Production date
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
T sensor defect
60058 Backlight
60059 Contrast
2048 ECL 485 addr.
38 Modbus addr.
39 Baud
2150 Service pin
2151 Ext. reset
2050 Language
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
Danfoss District Energy VI.GU.A2.02
DEN-SMT/DK 103
Installation Guide ECL Comfort 210 / 310, application A214 / A314
3.0 Daily use
3.1 How to navigate
You navigate in the controller by turning the dial left or right to the desired position ( ).
The dial has a built-in accellerator. The faster you turn the dial, the faster it reaches the limits of any wide setting range.
The position indicator in the display ( ) will always show you where you are.
Push the dial to confirm your choices ( ).
The display examples are from a two-circuit application: One heating circuit ( ) and one domestic hot-water (DHW) circuit ( ).
The examples might differ from your application.
Heating circuit ( ): DHW circuit ( );
Some general settings which apply to the entire controller are located in a specific part of the controller.
To enter ‘Common controller settings’:
Action: Purpose:
Choose ‘MENU’ in any circuit
Examples:
Confirm
Choose the circuit selector at the top right corner in the display
Confirm
Choose ‘Common controller settings’
Confirm
Circuit selector
104 DEN-SMT/DK VI.GU.A2.02
Danfoss District Energy
Installation Guide ECL Comfort 210 / 310, application A214 / A314
3.2 Understanding the controller display
This section describes the function in general for the ECL Comfort
210 / 310 series. The shown displays are typical and not application related. They might differ from the displays in your application.
Choosing a favorite display
Your favorite display is the display you have chosen as the default display. The favorite display will give you a quick overview of the temperatures or units that you want to monitor in general.
If the dial has not been activated for 20 min., the controller will revert to the overview display you have chosen as favorite.
To shift between displays: Turn the dial until you reach the display selector ( ) at the bottom right side of the display. Push the dial and turn to choose your favorite overview display. Push the dial again.
Heating circuit
Overview display 1 informs about: actual outdoor temperature, controller mode, actual room temperature, desired room temperature.
Overview display 2 informs about: actual outdoor temperature, trend in outdoor temperature, controller mode, max. and min. outdoor temperatures since midnight as well as desired room temperature.
Overview display 1: Overview display 2:
Overview display 3 informs about: date, actual outdoor temperature, controller mode, time, desired room temperature as well as shows the comfort schedule of the current day.
Overview display 4 informs about: state of the controlled components, actual flow temperature,
(desired flow temperature), controller mode, return temperature
(limitation value), influence on desired flow temperature.
Dependent on the chosen display, the overview displays for the heating circuit inform you about:
• actual outdoor temperature (-0.5)
• controller mode ( )
• actual room temperature (24.5)
• desired room temperature (20.7 °C)
• trend in outdoor temperature ( )
• min. and max. outdoor temperatures since midnight ( )
• date (23.02.2010)
• time (7:43)
• comfort schedule of the current day (0 - 12 - 24)
• state of the controlled components (M2, P2)
• actual flow temperature (49 °C), (desired flow temperature (31))
• return temperature (24 °C) (limitation temperature (50))
Overview display 3:
Example of overview display with
Influence indication:
Overview display 4:
The setting of the desired room temperature is important even if a room temperature sensor / Remote Control Unit is not connected.
Danfoss District Energy VI.GU.A2.02
DEN-SMT/DK 105
Installation Guide ECL Comfort 210 / 310, application A214 / A314
If the temperature value is displayed as
"- -" the sensor in question is not connected.
"- - -" the sensor connection is short-circuited.
Setting the desired temperature
Depending on the chosen circuit and mode, it is possible to enter all daily settings directly from the overview displays (see also the next page concerning symbols).
Setting the desired room temperature
The desired room temperature can easily be adjusted in the overview displays for the heating circuit.
Action: Purpose:
Desired room temperature
Confirm
Adjust the desired room temperature
Confirm
Examples:
20.5
21.0
This overview display informs about outdoor temperature, actual room temperature as well as desired room temperature.
The display example is for comfort mode. If you want to change the desired room temperature for saving mode, choose the mode selector and select saving.
The setting of the desired room temperature is important even if a room temperature sensor / Remote Control Unit is not connected.
Setting the desired room temperature, ECA 30 / ECA 31
The desired room temperature can be set exactly as in the controller. However, other symbols can be present in the display
(please see 'What do the symbols mean?').
With the ECA 30 / ECA 31 you can override the desired room temperature set in the controller temporarily by means of the override functions:
106 DEN-SMT/DK VI.GU.A2.02
Danfoss District Energy
Installation Guide ECL Comfort 210 / 310, application A214 / A314
3.3 A general overview: What do the symbols mean?
Symbol Description
Outdoor temp.
Relative humidity indoor
Temperature
Room temp.
DHW temp.
Position indicator
Scheduled mode
Comfort mode
Saving mode
Frost protection mode
Manual mode
Standby
Mode
Cooling mode
42
!
Active output override
Optimized start or stop time
Heating
Cooling
DHW
Common controller settings
Circuit
Pump ON
Pump OFF
Actuator opens
Actuator closes
Actuator, analogue control signal
Controlled component
Symbol
7-23
Description
Alarm
Monitoring temperature sensor connection
Display selector
Max. and min. value
Trend in outdoor temperature
Wind speed sensor
Sensor not connected or not used
Sensor connection short-circuited
Fixed comfort day (holiday)
Active influence
Heating active
Cooling active
Additional symbols, ECA 30 / 31:
Symbol
15
Description
ECA Remote Control Unit
Connection address (master: 15, slaves: 1 - 9)
Day off
Holiday
Relaxing (extended comfort period)
Going out (extended saving period)
In ECA 30 / 31 only the symbols that are relevant to the application in the controller are displayed.
Danfoss District Energy VI.GU.A2.02
DEN-SMT/DK 107
Installation Guide ECL Comfort 210 / 310, application A214 / A314
3.4 Monitoring temperatures and system components
This section describes the function in general for the ECL Comfort
210 / 310 series. The shown displays are typical and not application related. They might differ from the displays in your application.
Heating circuit
The overview display in the heating circuit ensures a quick overview of the actual and (desired) temperatures as well as the actual state of the system components.
Display example:
49 °C Flow temperature
(31) Desired flow temperature
24 °C Return temperature
(50)
Return temperature limitation
Input overview
Another option to get a quick overview of measured temperatures is the 'Input overview' which is visible in the common controller settings (how to enter the common controller settings, see
‘Introduction to common controller settings’.)
As this overview (see display example) only states the measured actual temperatures, it is read-only.
108 DEN-SMT/DK VI.GU.A2.02
Danfoss District Energy
Installation Guide ECL Comfort 210 / 310, application A214 / A314
3.5 Influence overview
This section describes the function in general for the ECL Comfort
210 / 310 series. The shown displays are typical and not application related. They might differ from the displays in your application.
The menu gives an overview of the influences on the desired flow temperature. It differs from application to application which parameters are listed. It can be helpful in a service situation to explain unexpected conditions or temperatures among others.
If the desired flow temperature is influenced (corrected) by one or more parameters, it is indicated by a small line with arrow-down, arrow-up or double-arrow:
Arrow-down:
The parameter in question reduces the desired flow temperature.
Arrow-up:
The parameter in question increases the desired flow temperature.
Double-arrow:
The parameter in question creates an override (e.g. Holiday).
Straight line:
No active influence.
In the example, the arrow in the symbol points downwards for
'Room lim.'. This means that the actual room temperature is higher than the desired room temperature which again results in a decrease of the desired flow temperature.
Example of overview display with Influence indication:
Danfoss District Energy VI.GU.A2.02
DEN-SMT/DK 109
Installation Guide ECL Comfort 210 / 310, application A214 / A314
3.6 Manual control
This section describes the function in general for the ECL Comfort
210 / 310 series. The shown displays are typical and not application related. They might differ from the displays in your application.
It is possible to manually control the installed components.
Manual control can only be selected in favorite displays in which the symbols for the controlled components (valve, pump etc.) are visible.
Action: Purpose:
Choose mode selector
Examples:
Confirm
Choose manual mode
Confirm
Choose pump
Confirm
Switch ON the pump
Switch OFF the pump.
Confirm pump mode
Choose motorized control valve
Confirm
Open the valve
Stop opening the valve
Close the valve
Stop closing the valve
Confirm valve mode
To leave manual control, use the mode selector to select the desired mode. Push the dial.
Manual control is typically used when commisioning the installation. The controlled components, valve, pump etc., can be controlled for correct function.
Controlled components
During manual operation:
• All control functions are deactivated
• Output override is not possible
• Frost protection is not active
Circuit selector
When manual control is selected for one circuit, it is automatically selected for all circuits!
Manual control of 0 – 10 volt controlled actuator:
The actuator symbol has a value (in %) which can be changed. The % value is corresponding to a voltage in the range 0 – 10 volt.
110 DEN-SMT/DK VI.GU.A2.02
Danfoss District Energy
Installation Guide ECL Comfort 210 / 310, application A214 / A314
Manual control of 0 – 10 volt controlled fan speed:
The V1 and V2 symbols have a value (in %) which can be changed. The
% value is corresponding to a voltage in the range 0 – 10 volt.
Danfoss District Energy VI.GU.A2.02
DEN-SMT/DK 111
Installation Guide ECL Comfort 210 / 310, application A214 / A314
3.7 Schedule
3.7.1 Set your schedule
This section describes the schedule in general for the ECL Comfort
210 / 310 series. The shown displays are typical and not application related. They might differ from the displays in your application.
In some applications, however, there might be more than one schedule. Additional schedules can be found in ‘Common controller settings’.
The schedule consists of a 7-day week:
M = Monday
T
= Tuesday
W = Wednesday
T
= Thursday
F
= Friday
S
= Saturday
S
= Sunday
The schedule will day-by-day show you the start and stop times of your comfort periods (heating / DHW circuits).
Changing your schedule:
Examples:
Action:
Purpose:
Choose 'MENU' in any of the overview displays
Confirm
Confirm the choice 'Schedule'
Choose the day to change
Confirm*
Go to Start1
Confirm
Adjust the time
Confirm
Go to Stop1, Start2 etc. etc.
Return to 'MENU'
Confirm
Choose 'Yes' or 'No' in 'Save'
Confirm
T
* Several days can be marked
The chosen start and stop times will be valid for all the chosen days
(in this example Thursday and Saturday).
You can set max. 3 comfort periods a day. You can delete a comfort period by setting start and stop times to the same value.
Each circuit has its own schedule. To change to another circuit, go to
'Home', turn the dial and choose the desired circuit.
The start and stop times can be set in half-hourly (30 min. ) intervals.
112 DEN-SMT/DK VI.GU.A2.02
Danfoss District Energy
Installation Guide ECL Comfort 210 / 310, application A214 / A314
4.0 Settings overview
Desired balance T
Dead zone
Des. T Comfort
Des. T Saving
Temp. min. (duct / flow / inlet temp. limit, min.)
Temp. max. (duct / flow / inlet temp. limit, max.)
Adapt. time (adaption time)
Infl. - max. (room / duct temp. limitation, max.)
Infl. - min. (room / duct temp. limitation, min.)
Limit (return temp. limitation)
Infl. - max. (return temp. limitation - max. influence)
Infl. - min. (return temp. limitation - min. influence)
Adapt. time (adaptation time)
Infl. - min. (min. influence)
Adapt. time (adaptation time)
Limit T frost (sliding frost protection)
Limit (compensation temp., 1. point)
Adapt. time (adaptation time)
Infl. - max. (compensation temp., 1. point)
Infl. - min. (compensation temp., 1. point)
Limit (compensation temp., 2. point)
Adapt. time (adaptation time)
Infl. - max. (compensation temp., 2. point)
Infl. - min. (compensation temp., 2. point)
Limit (limitation value)
Filter constant
V out max.
V out min.
Max. pressure
Min. pressure
Reverse out
Motor pr. (motor protection)
Xp (proportional band)
Tn (integration time constant)
M run (running time of the motorized control valve)
Nz (neutral zone)
Min. act. time (min. activation time gear motor)
Pressure, des. (desired pressure)
Air quality
Outlet fan, offset
Fan speed, red. (reduced fan speed)
It is recommendable to make a note of any changed settings in the empty columns.
Setting ID
Page
*
*
*
*
*
*
*
*
*
*
*
*
*
*
*
*
*
*
*
*
*
*
*
*
*
*
*
*
*
*
*
*
*
*
1
*
*
*
*
*
*
*
1x060
1x061
1x062
1x063
1x064
1x065
1x066
1x067
1x111
1x113
1x165
1x167
1x168
1x169
1x171
1x174
1x184
1x008
1x009
1x018
1x019
1x177
1x178
1x015
1x182
1x183
1x030
1x035
1x036
1x037
1x105
1x107
1x108
1x185
1x186
1x187
1x189
1x339
1x356
1x357
2
Factory settings in circuit(s)
3
Danfoss District Energy VI.GU.A2.02
DEN-SMT/DK 113
Installation Guide ECL Comfort 210 / 310, application A214 / A314
Setting
1. step level
2. step level
X1
X2
Pressure
Room T diff.
P frost T (circulation pump, frost protection temp.)
Fan cut-in delay (relay 1, F1)
Acc. cut-in delay (Accessory cut-in delay, relay 2, P2)
Fan output func. (Fan output function, relay 1, F1)
Acc. output func. (Accessory output function, relay 2, P2)
Optional function (relay 3, X3)
Acc. time control (Accessory time control, relay 2, P2)
Fan function
Stop difference
Wind actual
Filter constant
Control voltage
ECA addr. (ECA address, choice of Remote Control Unit)
Total stop
Stop at T out
P frost T (circulation pump, frost protection temp.)
Accum. filter (Accummulation filter)
Frost pr. T (frost protection temp.)
Comp. T select (Compensation temperature selection)
Ext. input (external override)
Ext. mode (external override mode)
Summer, cut-out (limit for heating cut-out)
Stop difference
S4 filter
1. step level
2. step level
Send desired T
Upper difference
Lower difference
Delay
Lowest temp.
Clear alarm
Alarm high
Alarm low
Alarm value
Alarm time-out
Alarm value
Alarm time-out
ID
Page
1x368
1x369
1x406
1x407
1x027
1x077
1x086
1x087
1x088
1x089
1x090
1x091
1x137
1x194
1x081
1x104
1x010
1x021
1x038
1x077
1x082
1x093
1x140
1x141
1x142
1x179
1x194
1x304
1x368
1x369
1x500
1x147
1x148
1x149
1x150
1x390
1x614
1x615
1x616
1x617
1x636
1x637
*
*
*
*
*
*
*
*
*
*
*
*
*
*
*
*
*
*
*
*
*
COM-
FORT
*
*
*
*
*
*
*
*
*
1
*
*
*
*
*
*
*
*
*
*
*
*
114 DEN-SMT/DK VI.GU.A2.02
2
Factory settings in circuit(s)
3
Danfoss District Energy
Setting
Alarm value
Alarm time-out
Alarm value
Alarm value
Alarm time-out
Alarm overview, in general
State
Baud (bits per second)
Command
M-bus address
Type
Scan time
ID
Energy meter 1 (2, 3, 4, 5)
Backlight (display brightness)
Contrast (display contrast)
Modbus addr.
ECL 485 addr. (master / slave address)
Service Pin
Ext. reset
Language
Room T Offset
RH offset (ECA 31 only)
Backlight (display brightness)
Contrast (display contrast)
Use as remote
Slave addr. (Slave address)
Connection addr. (Connection address)
Override addr. (Override address)
Override circuit
Installation Guide ECL Comfort 210 / 310, application A214 / A314
ID
Page
1x656
1x657
1x676
1x696
1x697
Readout
5997
5998
6000
6001
6002
Readout
Readout
60058
60059
38
2048
2150
2151
2050
1
*
*
*
*
*
2
Factory settings in circuit(s)
3
-
300
NONE
255
0
60 sec
-
0
0.0 K
0.0 %
5
3
*)
A
15
OFF
OFF
1
15
5
3
0
0
English
Danfoss District Energy VI.GU.A2.02
DEN-SMT/DK 115
Installation Guide ECL Comfort 210 / 310, application A214 / A314
5.0 Settings
5.1 Introduction to Settings
Descriptions of settings (parameter's functions) are divided into groups as used in the ECL Comfort 210 / 310 controller's menu structure. Examples: "Flow temperature", "Room limit" and so on.
Each group starts with a general explanation.
The descriptions of each parameter are in numeric order, related to the parameter's ID numbers. You might come across differences between the order in this Installation Guide and the ECL Comfort
210 / 310 controllers.
You might also come across navigation hints which are not present in your application.
The note "See Appendix …" refers to the Appendix at the end of this Installation Guide, where parameter's setting ranges and factory settings are listed.
The navigation hints (for example MENU > Settings > Return limit
… ) cover multiple subtypes.
116 DEN-SMT/DK VI.GU.A2.02
Danfoss District Energy
Installation Guide ECL Comfort 210 / 310, application A214 / A314
5.2 Flow temperature / Inlet temperature
The temperature, measured by S3, can be a flow or an air duct temperature.
The desired temperature at S3 in the subtypes A214.1 - A214.6 and
A314.1 - A314.3 is indicated as 'Desired balance T'.
The desired temperature at S3 in the subtypes A314.4 - A314.7 and
A314.9 is indicated as 'Desired T comfort' / 'Desired T saving'.
Parameters indicated with an ID no. like "1x607" mean a universal parameter.
x stands for circuit / parameter group.
MENU > Settings > Flow temperature
Desired balance T
Circuit
All
Setting range
*
* See Appendix “Parameter ID overview”
Set the desired temperature at S3.
1x008
Factory setting
*
In all applications, the S3 temperature sensor is the most important sensor and must always be connected.
MENU > Settings > Flow temperature
MENU > Settings > Inlet temperature
Dead zone
Circuit Setting range
1x009
Factory setting
All *
When the application runs in combined heating / cooling mode or as
2-stage heating, the desired duct or room temperature is increased with the dead zone value when in cooling mode.
This setting prevents unexpected changes (instability) between heating and cooling operation.
*
* See Appendix “Parameter ID overview”
OFF:
Value:
No dead zone between heating and cooling operation or 2-stage heating.
The number of degrees between the desired duct or room temperature in heating mode and the desired duct or room temperature in cooling mode.
Duct / room temp.
° C
Actual
Dampened
Dead zone
Desired temp., cooling
Desired temp., heating
Heating
Cooling
Example
Desired duct / room temperature: 20 °C
Dead zone: 5 K
When the duct / room temperature rises above 20 °C, heating stops.
When the duct / room temperature rises above 25 °C, cooling starts.
When the duct / room tempeture falls below 25 °C, cooling stops.
When the duct / room tempeture falls below 20 °C, heating starts.
Danfoss District Energy VI.GU.A2.02
DEN-SMT/DK 117
Installation Guide ECL Comfort 210 / 310, application A214 / A314
MENU > Settings > Flow temperature
MENU > Settings > Inlet temperature
Des. T Comfort
Circuit Setting range
1x018
Factory setting
All *
Setting of desired flow temperature when the ECL controller is in comfort mode.
*
* See Appendix “Parameter ID overview”
This setting has no influence if the controller receives an external value for the desired flow temperature.
MENU > Settings > Flow temperature
MENU > Settings > Inlet temperature
Des. T Saving
Circuit
All
Setting range
*
1x019
Factory setting
Setting of desired flow temperature when the ECL controller is in saving mode.
*
* See Appendix “Parameter ID overview”
This setting has no influence if the controller receives an external value for the desired flow temperature.
MENU > Settings > Flow temperature
MENU > Settings > Inlet temperature
Temp. min. (duct / flow / inlet temp. limit, min.)
Circuit Setting range
All *
1x177
Factory setting
*
* See Appendix “Parameter ID overview”
Set the min. duct / flow / inlet temperature for the system. The desired duct / flow / inlet temperature will not be lower than this setting. Adjust the factory setting, if required.
‘Temp. min.’ is overruled if 'Total stop' is active in Saving mode or
'Cut-out' is active.
‘Temp. min.’ can be overruled by the influence from the return temperature limitation (see 'Priority').
The setting for ‘Temp. max.’ has higher priority than ‘Temp. min.’.
MENU > Settings > Flow temperature
MENU > Settings > Inlet temperature
Temp. max. (duct / flow / inlet temp. limit, max.)
Circuit Setting range
All *
1x178
Factory setting
*
* See Appendix “Parameter ID overview”
Set the max. flow / duct / inlet temperature for the system. The desired temperature will not be higher than this setting. Adjust the factory setting, if required.
The setting of ‘heat curve’ is possible for heating circuits only.
The setting for ‘Temp. max.’ has higher priority than ‘Temp. min.’.
118 DEN-SMT/DK VI.GU.A2.02
Danfoss District Energy
Installation Guide ECL Comfort 210 / 310, application A214 / A314
5.3 Duct T limit / Room limit
This section is only relevant if you have installed a duct / room temperature sensor S4 or a Remote Control Unit for utilizing the room temperature signal.
In the following description is referred to "flow temperature" in general. This can be air duct or inlet temperature too.
The controller adjusts the desired flow temperature to compensate for the difference between the desired and the actual duct / room temperature.
If the duct / room temperature is higher than the desired value, the desired flow temperature can be reduced.
The 'Infl. -max.' (Influence, max. duct / room temp.) determines how much the desired flow temperature should be reduced.
Use this influence type to avoid a too high duct / room temperature.
The controller will allow for free heat gains, i.e. solar radiation or heat from a fire place etc.
If the duct / room temperature is lower than the desired value, the desired flow temperature can be increased.
The 'Infl. -min.' (Influence, min. duct / room temperature) determines how much the desired flow temperature should be increased.
Use this influence type to avoid a too low duct / room temperature.
This could e.g. be caused by windy surroundings.
A typical setting will be -4.0 for 'Infl. -max.' and 4.0 for 'Infl. -min.'
Parameters indicated with an ID no. like "1x607" mean a universal parameter.
x stands for circuit / parameter group.
MENU > Settings > Duct T limit
MENU > Settings > Room limit
Adapt. time (adaption time)
Circuit
All
Setting range
*
1x015
Factory setting
Controls how fast the actual room / duct temperature adapts to the desired room / duct temperature (I control).
*
* See Appendix “Parameter ID overview”
OFF:
The control function is not influenced by the 'Adapt.
time'.
The desired room / duct temperature is adapted quickly.
Minor value:
Major value:
The desired room / duct temperature is adapted slowly.
If your application key has a heat curve setting:
The adaptation function can correct the desired room temperature with max. 8 K x heat curve slope value.
If your application key does not have a heat curve setting:
The adaptation function can correct the desired flow temperature with max. 8 K.
Danfoss District Energy VI.GU.A2.02
DEN-SMT/DK 119
Installation Guide ECL Comfort 210 / 310, application A214 / A314
MENU > Settings > Duct T limit
MENU > Settings > Room limit
Infl. - max. (room / duct temp. limitation, max.)
Circuit Setting range
1x182
Factory setting
All * *
Determines how much the desired flow / duct temperature will be influenced
(decreased) if the actual room / duct temperature is higher than the desired room / duct temperature (P control).
* See Appendix “Parameter ID overview”
0.0:
-2.0:
-5.0:
-9.9:
No influence
Minor influence
Medium influence
Maximum influence
Influence
‘Infl. - min.’ (min. limitation)
Desired room / duct temperature
Actual room / duct temperature
‘Infl. - max.’ (max. limitation)
The ‘Infl. - max.’ and 'Infl. - min.' determine how much the room / duct temperature should influence the desired flow / duct temperature.
If the ‘Infl.’ factor is too high and / or the ‘Adapt. time’ too low, there is a risk of unstable control.
Example 1 (application with heat curve value):
The actual room temperature is 2 degrees too high.
The ‘Infl. - max.’ is set to -4.0.
The heat curve slope is 1.8 (see 'Heat curve' in 'Flow temperature').
Result:
The desired flow temperature is changed by (2 x -4.0 x 1.8)
–14.4 degrees.
Example 2 (application, no heat curve value):
The actual room temperature is 3 degrees too high.
The ‘Infl. - max.’ is set to -4.0.
Result:
The desired flow temperature is changed by (3 x -4.0)
-12 degrees.
MENU > Settings > Duct T limit
MENU > Settings > Room limit
Infl. - min. (room / duct temp. limitation, min.)
Circuit
All
Setting range
*
1x183
Factory setting
*
Determines how much the desired flow / duct temperature will be influenced
(increased) if the actual room / duct temperature is lower than the desired room / duct temperature (P control).
* See Appendix “Parameter ID overview”
9.9:
5.0:
2.0:
0.0:
Maximum influence
Medium influence
Minor influence
No influence
Example 1 (application with heat curve value):
The actual room temperature is 2 degrees too low.
The ‘Infl. - min.’ is set to 4.0.
The heat curve slope is 1.8 (see 'Heat curve' in 'Flow temperature').
Result:
The desired flow temperature is changed by (2 x 4.0 x 1.8)
14.4 degrees.
Example 2 (application, no heat curve value):
The actual room temperature is 3 degrees too low.
The ‘Infl. - min.’ is set to 4.0.
Result:
The desired flow temperature is changed by (3 x 4.0)
12 degrees.
120 DEN-SMT/DK VI.GU.A2.02
Danfoss District Energy
Installation Guide ECL Comfort 210 / 310, application A214 / A314
5.4 Return limit
Parameters indicated with an ID no. like "1x607" mean a universal parameter.
x stands for circuit / parameter group.
The return temperature limitation is based on a selectable temperature value. The controller automatically changes the desired flow / duct temperature to obtain an acceptable return temperature when the return temperature falls below or gets higher than the set limit.
This limitation is based on a PI regulation where P ('Infl.' factor) responds quickly to deviations and I ('Adapt. time') responds slower and over time removes the small offsets between the desired and actual values. This is done by changing the desired flow / duct temperature.
Typical for heating systems is that the return temperature must be as low as possible.
Typical for cooling systems is that the return temperature must be as high as possible.
Desired flow / duct temperature
° C
Influence
Limit
° C
Return temp.
‘Infl. - min.’ > 0
‘Limit’
‘Infl. - max.’ > 0
Return temperature
‘Infl. - max.’ < 0
‘Infl. - min.’ < 0
If the ‘Infl.’ factor is too high and / or the ‘Adapt. time’ too low, there is a risk of unstable control.
MENU > Settings > Return limit
Limit (return temp. limitation)
Circuit Setting range
All
Set the return temperature you accept for the system.
*
1x030
Factory setting
*
* See Appendix “Parameter ID overview”
When the return temperature falls below or gets higher than the set value, the controller automatically changes the desired flow / duct temperature to obtain an acceptable return temperature. The influence is set in 'Infl. - max.' and 'Infl. - min.'.
Danfoss District Energy VI.GU.A2.02
DEN-SMT/DK 121
Installation Guide ECL Comfort 210 / 310, application A214 / A314
MENU > Settings > Return limit
Infl. - max. (return temp. limitation - max. influence)
Circuit
All
Setting range
*
1x035
Factory setting
*
Determines how much the desired flow / duct temperature will be influenced if the return temperature is higher than the set limit.
* See Appendix “Parameter ID overview”
Influence higher than 0:
The desired flow / duct temperature is increased, when the return temperature gets higher than the set limit.
Influence lower than 0:
The desired flow / duct temperature is decreased, when the return temperature gets higher than the set limit.
Example
The return limit is active above 20 °C.
The influence is set to 0.5.
The actual return temperature is 2 degrees too high.
Result:
The desired flow / duct temperature is changed by 0.5 x 2 = 1.0 degree.
MENU > Settings > Return limit
Infl. - min. (return temp. limitation - min. influence)
Circuit
All
Setting range
*
1x036
Factory setting
*
Determines how much the desired flow / duct temperature will be influenced if the return temperature is lower than the calculated limit.
* See Appendix “Parameter ID overview”
Influence higher than 0:
The desired flow / duct temperature is increased, when the return temperature gets below the calculated limit.
Influence lower than 0:
The desired flow / duct temperature is decreased, when the return temperature gets below the calculated limit.
Example
The return limit is active below 50 °C.
The influence is set to -3.0.
The actual return temperature is 2 degrees too low.
Result:
The desired flow / duct temperature is changed by -3.0 x 2 = -6.0
degrees.
Normally, this setting is 0 in district heating systems because a lower return temperature is acceptable.
Typically, this setting is higher than 0 in boiler systems to avoid a too low return temperature (see also 'Infl. - max.').
MENU > Settings > Return limit
Adapt. time (adaptation time)
Circuit
All
Setting range
*
1x037
Factory setting
Controls how fast the return temperature adapts to the desired return temperature limit (Integration control).
*
* See Appendix “Parameter ID overview”
OFF:
The control function is not influenced by the ‘Adapt.
time’.
The desired temperature is adapted quickly.
Minor value:
Major value:
The desired temperature is adapted slowly.
The adaptation function can correct the desired flow / duct temperature with max. 8 K.
122 DEN-SMT/DK VI.GU.A2.02
Danfoss District Energy
Installation Guide ECL Comfort 210 / 310, application A214 / A314
5.5 Limit T safety
The temperature sensor S5 can, besides operating as return temperature limitation sensor, act as frost protection sensor.
When the S5 temperature becomes lower than the set limitation value, the desired flow / duct temperature will be increased (the motorized control valve opens gradually). The influence can be set.
Parameters indicated with an ID no. like "1x607" mean a universal parameter.
x stands for circuit / parameter group.
MENU > Settings > Limit T safety
Infl. - min. (min. influence)
Circuit
All
Setting range
*
1x105
Factory setting
Determines how much the desired flow / duct temperature will be increased if the S5 temperature is lower than the set value for 'Limit T frost'.
*
* See Appendix “Parameter ID overview”
0.0:
Value:
The desired flow / duct temperature will not be increased if the S5 temperature is lower than 'Limit T frost'
The desired flow / duct temperature will be increased if the S5 temperature is lower than 'Limit T frost'.
Example
The sliding frost protection is active below 10 °C.
The influence is set to 3.0.
The actual S5 temperature is 2 degrees too low.
Result:
The desired flow / duct temperature is increased with 3.0 x 2 = 6.0
degrees.
MENU > Settings > Limit T safety
Adapt. time (adaptation time)
Circuit
All
Setting range
*
1x107
Factory setting
Controls how fast the S5 temperature adapts to the desired 'Limit T frost' (I control).
*
* See Appendix “Parameter ID overview”
OFF:
The control function is not influenced by the ‘Adapt.
time’.
The desired temperature is adapted quickly.
Minor value:
Major value:
The desired temperature is adapted slowly.
The adaptation function can correct the desired flow / duct temperature with max. 8 K.
Danfoss District Energy VI.GU.A2.02
DEN-SMT/DK 123
Installation Guide ECL Comfort 210 / 310, application A214 / A314
MENU > Settings > Limit T safety
Limit T frost (sliding frost protection)
Circuit Setting range
All *
1x108
Factory setting
*
* See Appendix “Parameter ID overview”
OFF:
Sliding frost protection, based on the temperature at sensor S5, is inactive.
Value:
Temperature at which the sliding frost protection is active.
124 DEN-SMT/DK VI.GU.A2.02
Danfoss District Energy
Installation Guide ECL Comfort 210 / 310, application A214 / A314
5.6 Compensation 1
A limit value for the compensation temperature makes it possible to change the desired flow / duct temperature.
The influence from the compensation temperature can result in an increase or a decrease desired flow / duct temperature. The compensation temperature is often the outdoor temperature but could for example be a room temperature.
This application contains 2 compensation temperature limits:
Compensation 1 (Comp. 1) and Compensation 2 (Comp. 2).
In the parameter descriptions "Sx"is used for the compensation temperature.
A214.1 - A214.6 and A314.1 - A314.3:
The desired flow / duct temperature can be influenced by a compensation temperature, measured by S1 or S2. The choice between S1 and S2 is made by the parameter "Comp. T select".
A314.4 - A314.7 and A314.9:
The desired flow / duct temperature can be influenced by a compensation temperature, measured by one of the temperature sensors S1 . . . S16.
The choice of compensation sensor is made by the parameter
"Comp. T select".
Parameters indicated with an ID no. like "1x607" mean a universal parameter.
x stands for circuit / parameter group.
MENU > Settings > Compensation 1
MENU > Settings > Surface limit
Limit (compensation temp., 1. point)
Circuit Setting range
All *
Set the compensation temperature limit point 1.
1x060
Factory setting
*
* See Appendix “Parameter ID overview”
When the compensation temperature measured by Sx falls below or gets higher than the set value, the controller automatically changes the desired flow / duct temperature. The influence is set in 'Infl. - max.' and 'Infl. - min.'.
-
Influence
+
Compensation 1
° C
Temp. Sx
Danfoss District Energy VI.GU.A2.02
DEN-SMT/DK 125
Installation Guide ECL Comfort 210 / 310, application A214 / A314
MENU > Settings > Compensation 1
MENU > Settings > Surface limit
Adapt. time (adaptation time)
Circuit
All
Setting range
*
1x061
Factory setting
Controls how fast the compensation temperature influences the desired flow / duct temperature.
*
* See Appendix “Parameter ID overview”
OFF:
The control function is not influenced by the ‘Adapt.
time’.
Minor value:
The desired flow / duct temperature is adapted quickly.
Major value:
The desired flow / duct temperature is adapted slowly.
The adaptation function can correct the desired flow / duct temperature with max. 8 K.
MENU > Settings > Compensation 1
MENU > Settings > Surface limit
Infl. - max. (compensation temp., 1. point)
Circuit Setting range
1x062
Factory setting
All * *
Determines how much the desired flow / duct temperature will be influenced if the compensation temperature is higher than the set limit.
* See Appendix “Parameter ID overview”
Influence higher than 0:
The desired flow / duct temperature is increased, when the compensation temperature gets above the set limit.
Influence lower than 0:
The desired flow / duct temperature is decreased, when the compensation temperature gets above the set limit.
Example
The limit value is set to 5 °C.
‘Infl. max.’ is set to -1.5.
The actual compensation temperature is 7°C (2 degrees above the limit value).
Result:
The desired flow / duct temperature is changed by -1.5 x 2 = -3.0
degrees.
MENU > Settings > Compensation 1
MENU > Settings > Surface limit
Infl. - min. (compensation temp., 1. point)
Circuit
All
Setting range
*
1x063
Factory setting
*
Determines how much the desired flow / duct temperature will be influenced if the compensation temperature is lower than the set limit.
* See Appendix “Parameter ID overview”
Influence higher than 0:
The desired flow / duct temperature is increased, when the compensation temperature gets below the set limit.
Influence lower than 0:
The desired flow / duct temperature is decreased, when the compensation temperature gets below the set limit.
Example
The limit value is set to 5 °C.
‘Infl. min.’ is set to 2.5.
The actual compensation temperature is 2°C (3 degrees below the limit value).
Result:
The desired flow / duct temperature is changed by 2.5 x 3 = 7.5
degrees.
126 DEN-SMT/DK VI.GU.A2.02
Danfoss District Energy
Installation Guide ECL Comfort 210 / 310, application A214 / A314
5.7 Compensation 2
This extra compensation temperature limit setting makes it possible to change the desired flow / duct temperature in relation to a second temperature limitation point. The measured compensation temperature is the same as in section "Compensation 1".
In the parameter descriptions "Sx"is used for the compensation temperature.
Parameters indicated with an ID no. like "1x607" mean a universal parameter.
x stands for circuit / parameter group.
MENU > Settings > Compensation 2
Limit (compensation temp., 2. point)
Circuit Setting range
All
Set the compensation temperature limit point 2.
*
1x064
Factory setting
*
* See Appendix “Parameter ID overview”
When the compensation temperature measured by Sx falls below or gets higher than the set value, the controller automatically changes the desired flow / duct temperature. The influence is set in 'Infl. - max.' and 'Infl. - min.'.
-
Influence
+
Compensation 2
° C
Temp. Sx
MENU > Settings > Compensation 2
Adapt. time (adaptation time)
Circuit Setting range
1x065
Factory setting
* All *
Controls how fast the compensation temperature influences the desired flow / duct temperature.
* See Appendix “Parameter ID overview”
OFF:
The control function is not influenced by the ‘Adapt.
time’.
Minor value:
The desired flow / duct temperature is adapted quickly.
Major value:
The desired flow / duct temperature is adapted slowly.
The adaptation function can correct the desired flow / duct temperature with max. 8 K.
Danfoss District Energy VI.GU.A2.02
DEN-SMT/DK 127
Installation Guide ECL Comfort 210 / 310, application A214 / A314
MENU > Settings > Compensation 2
Infl. - max. (compensation temp., 2. point)
Circuit Setting range
1x066
Factory setting
All * *
Determines how much the desired flow / duct temperature will be influenced if the compensation temperature is higher than the set limit.
* See Appendix “Parameter ID overview”
Influence higher than 0:
The desired flow / duct temperature is increased, when the compensation temperature gets above the set limit.
Influence lower than 0:
The desired flow / duct temperature is decreased, when the compensation temperature gets above the set limit.
Example
The limit value is set to 25 °C.
‘Infl. max.' is set to 2.5.
The actual compensation temperature is 28 °C (3 degrees above limit value).
The desired flow / duct temperature is changed by 2.5 x 3 = 7.5
degrees.
MENU > Settings > Compensation 2
Infl. - min. (compensation temp., 2. point)
Circuit
All
Setting range
*
1x067
Factory setting
*
Determines how much the desired flow / duct temperature will be influenced if the compensation temperature is lower than the set limit.
* See Appendix “Parameter ID overview”
Influence higher than 0:
The desired flow / duct temperature is increased, when the compensation temperature gets below the set limit.
Influence lower than 0:
The desired flow / duct temperature is decreased, when the compensation temperature gets below the set limit.
Example
The limit value is set to 25 °C.
‘Infl. min.’ is set to 0.5.
The actual compensation temperature is 23 °C (2 degrees below the limit value).
Result:
The desired flow / duct temperature is changed by 0.5 x 2= 1.0 degree.
128 DEN-SMT/DK VI.GU.A2.02
Danfoss District Energy
Installation Guide ECL Comfort 210 / 310, application A214 / A314
Combination of two compensation temperature limit points:
Compensation 1 and 2 can be combined to give a compensation at
2 different compensation temperatures. This can for instance be used to avoid a too big difference between the indoor and outdoor temperatures.
The example below shows that below Comp. 1 and above Comp.
2, the desired flow / duct temperature will be increased, but with different values.
Example :
Comp. 1 value is set to 21 °C and Comp. 2 value is set to 25 °C.
'Infl. min.' for Comp. 1 is set to 2.5 and 'Infl. max.' for Comp. 1 is set to 0.0.
'Infl. min.' for Comp. 2 is set to 0.0 and 'Infl. max.' for Comp. 2 is set to 1.5.
The desired flow / duct temperature is kept on a constant level as long as the compensation temperature is between 21 and 25
°C, but the desired flow / duct temperature will rise if the the compensation temperature gets above 25 °C or below 21 °C.
Example 1:
Influence
+
-
Comp. 1 Comp. 2
°C
Temp. Sx
Danfoss District Energy VI.GU.A2.02
DEN-SMT/DK 129
Installation Guide ECL Comfort 210 / 310, application A214 / A314
5.8 Control parameters
Control of valves / dampers / cross- / rotating heat-exchangers
/ fluid batteries
The motorized control valves / dampers are controlled by means of either 3-point control or a 0 - 10 volt control signal or a mix of these.
Valve control:
The motorized control valve is opened gradually when the flow temperature is lower than the desired flow temperature and vice versa.
The water flow through the control valve is managed by means of an electric actuator. The combination "actuator" and "control valve" is also called motorized control valve. The actuator can in this way gradually increase or decrease the flow in order to change the supplied energy. Different types of actuators are available.
Damper control (typical M2):
The motorized controlled damper(s) is(are) opened gradually when the air duct temperature is lower than the desired duct temperature and vice versa.
The air flow through the damper(s) is managed by means of an electric actuator.
Rotating heat-exchanger, cross heat-exchanger or fluid battery
(typical M2):
In order to utilize the heat of the exit air different devices can be controlled.
3-point controlled actuator:
The electric actuator contains a reversible gear-motor. Electric
"open" and "close" signals come from the electronic outputs of the
ECL Comfort controller in order to manage the control valve. The signals are in the ECL Comfort controller expressed as "Arrow-up"
(open) and "Arrow-down" (close) and displayed at the valve symbol.
When the flow temperature (for example at S3) is lower than the desired flow temperature, short open-signals come from the ECL
Comfort controller in order to gradually increase the flow. By this, the flow temperature will align with the desired temperature.
Oppositely, when the flow temperature is higher than the desired flow temperature, short close-signals come from the ECL Comfort controller in order to gradually reduce the flow. Again, the flow temperature aligns with the desired temperature.
Neither open-signals nor close-signals will come as long as the flow temperature corresponds to the desired temperature.
130 DEN-SMT/DK VI.GU.A2.02
Danfoss District Energy
Installation Guide ECL Comfort 210 / 310, application A214 / A314
0 - 10 volt controlled actuator or damper (ECL Comfort 310):
This actuator type is indicated in the application diagrams with an "A". This electric actuator contains a reversible gear-motor. A control voltage between 0 and 10 volt comes from the extension module ECA 32 in order to manage the control valve. The voltage in the ECL Comfort controller is expressed as a % value and displayed at the valve symbol. Example: 45 % corresponds to 4.5 volt.
When the flow temperature (for example at S3) is lower than the desired flow temperature, the control voltage is gradually increased in order to gradually increase the flow. By this, the flow temperature will align with the desired temperature.
The control voltage remains on a constant value as long as the flow temperature corresponds to the desired temperature.
Oppositely, when the flow temperature is higher than the desired flow temperature, the control voltage is gradually reduced in order to reduce the flow. Again, the flow temperature aligns with the desired temperature.
A314.1 and A314.2: The 0 - 10 volt output signal can be reversed.
Control of fan speed
The fans V2 and V3 can be individually speed controlled by means of 0 - 10 volt signals. Each speed control signal comes from the analog outputs of the ECA 32 module.
The control voltage is expressed as a % value and displayed at the
V1 and V2 symbols.
Danfoss District Energy VI.GU.A2.02
DEN-SMT/DK 131
Installation Guide ECL Comfort 210 / 310, application A214 / A314
Control of fan speed
A314.3:
The fan speed is controlled in relation to measured wind speed
(S10). When the wind speed gets higher, the control voltage is gradually increased in order to increase the speed of the fan V1.
A314.4 and A314.6:
The desired pressures (Pascal) at S11 and S12 can be set individually in relation to the outdoor temperature (S1).
When the pressure gets lower than the desired pressure, the control voltage is gradually increased in order to increase the speed of the fan more than the moment before. By this, the pressure difference aligns with the desired pressure. A too high pressure results in opposite procedure.
The control voltage remains on a fixed value as long as the pressure corresponds to the desired pressure.
The desired pressure can be limited to a maximum and a minimum pressure value.
The control voltage can be limited to a maximum and a minimum
% value.
When the ECL controller is in Saving mode:.
• the fan velocity of V2 is controlled in relation to a desired pressure at S11
• V3 is OFF
The pressures at S11 and S12 are measured in Pascal and represented as a 0 - 10 volt signal. Conversion of the 0 - 10 volt signal into pressure is done in a conversion (scale) menu. Two different voltages (X1 and X2) and the related pressure values can be set.
A314.5, A314.7 and A314.9:
The limitation value for air quality (ppm) at S11 can be set.
When the air quality (ppm) gets higher than the set limit, the control voltage is gradually increased in order to increase the speed of the fan(s). Fan V3 is speed controlled by means of an off-set in relation to fan V2.
The control voltage can be limited to a maximum and a minimum
% value.
When the ECL controller is in Saving mode:
• the fan velocity of V2 can be controlled in relation to a desired pressure at S11
• V3 is OFF
The air quality at S11 is measured in ppm and represented as a 0 - 10 volt signal. The higher ppm value, the less air quality.
Conversion of the 0 - 10 volt signal into ppm is done in a conversion
(scale) menu. Two different voltages (X1 and X2) and the related ppm values can be set.
132 DEN-SMT/DK VI.GU.A2.02
Danfoss District Energy
Installation Guide ECL Comfort 210 / 310, application A214 / A314
MENU > Settings > Control par., fan
MENU > Settings > Flow / power limit
Limit (limitation value)
Circuit Setting range
1x111
Factory setting
All * *
This value is in some applications a calculated limitation value, based on the actual outdoor temperature.
In other applications the value is a selectable limitation value.
* See Appendix “Parameter ID overview”
MENU > Settings > Control par., fan
MENU > Settings > Control par., inlet
MENU > Settings > Control par., outlet
MENU > Settings > Flow / power limit
Filter constant
Circuit
All
Setting range
*
1x113
Factory setting
The value of the filter constant determines the dampening of the measured value.
The higher the value, the more dampening.
By this, a too quick change of the measured value can be avoided.
*
* See Appendix “Parameter ID overview”
Minor value:
Major value:
Lower dampening
Higher dampening
MENU > Settings > Control par., fan
MENU > Settings > Control par., inlet
MENU > Settings > Control par., outlet
MENU > Settings > Control par. 2
V out max.
Circuit
All
Setting range
*
The output voltage can be limited to a maximum value.
1x165
Factory setting
*
* See Appendix “Parameter ID overview”
The value in % expresses the maximum voltage for the output in question.
Example
A setting of 60% means that the output voltage will be 6 volt as a maximum.
Danfoss District Energy VI.GU.A2.02
DEN-SMT/DK 133
Installation Guide ECL Comfort 210 / 310, application A214 / A314
MENU > Settings > Control par., fan
MENU > Settings > Control par., inlet
MENU > Settings > Control par., outlet
MENU > Settings > Control par. 2
V out min.
Circuit
All
Setting range
*
The output voltage can be limited to a minimum value.
1x167
Factory setting
*
* See Appendix “Parameter ID overview”
The value in % expresses the minimum voltage for the output in question.
Example:
A setting of 20% means that the output voltage will be 2 volt as a minimum.
The setting 'Reverse out' has no influence on the 'V out max’ or ‘V out min' settings.
The 'V out min' setting has higher priority than 'V out max'.
MENU > Settings > Control par., fan
MENU > Settings > Control par., inlet
MENU > Settings > Control par., outlet
Max. pressure
Circuit
All
Setting range
*
1x168
Factory setting
The desired pressure at the inlet can be in relation to the outdoor temperature. In order to limit the desired pressure, the max. limit is set here.
*
* See Appendix “Parameter ID overview”
MENU > Settings > Control par., fan
MENU > Settings > Control par., inlet
MENU > Settings > Control par., outlet
Min. pressure
Circuit
All
Setting range
*
1x169
Factory setting
The desired pressure at the inlet can be in relation to the outdoor temperature. In order to limit the desired pressure, the min. limit is set here.
*
* See Appendix “Parameter ID overview”
MENU > Settings > Control par. 2
Reverse out
Circuit
All
Setting range
*
1x171
Factory setting
The analog output (0-10 volt) can be a rising or a falling voltage for rising cooling demand.
*
* See Appendix “Parameter ID overview”
OFF:
ON:
The analog output voltage will fall at a rising cooling demand.
The analog output voltage will rise at a rising cooling demand.
134 DEN-SMT/DK VI.GU.A2.02
Danfoss District Energy
Installation Guide ECL Comfort 210 / 310, application A214 / A314
MENU > Settings > Control par.
MENU > Settings > Control par. 1
MENU > Settings > Control par. 2
Motor pr. (motor protection)
Circuit
All
Setting range
*
1x174
Factory setting
*
Prevents the controller from unstable temperature control (and resulting actuator oscillations). This can occur at very low load. The motor protection increases the lifetime of all involved components.
* See Appendix “Parameter ID overview”
OFF:
Value:
Motor protection is not activated.
Motor protection is activated after the set activation delay in minutes.
Recommended for duct systems with variable load.
MENU > Settings > Control par.
MENU > Settings > Control par., cool.
MENU > Settings > Control par., fan
MENU > Settings > Control par., inlet
MENU > Settings > Control par., outlet
MENU > Settings > Control par. 1
MENU > Settings > Control par. 2
Xp (proportional band)
Circuit
All
Setting range
*
1x184
Factory setting
*
* See Appendix “Parameter ID overview”
Set the proportional band. A higher value will result in a stable but slow control of the flow / duct temperature.
MENU > Settings > Control par.
MENU > Settings > Control par., cool.
MENU > Settings > Control par., fan
MENU > Settings > Control par., inlet
MENU > Settings > Control par., outlet
MENU > Settings > Control par. 1
MENU > Settings > Control par. 2
Tn (integration time constant)
Circuit
All
Setting range
*
1x185
Factory setting
*
* See Appendix “Parameter ID overview”
Set a high integration time constant (in seconds) to obtain a slow but stable reaction to deviations.
A low integration time constant will make the controller react fast but with less stability.
Danfoss District Energy VI.GU.A2.02
DEN-SMT/DK 135
Installation Guide ECL Comfort 210 / 310, application A214 / A314
MENU > Settings > Control par.
MENU > Settings > Control par., cool.
MENU > Settings > Control par. 1
MENU > Settings > Control par. 2
M run (running time of the motorized control valve)
Circuit
All
Setting range
*
1x186
Factory setting
*
‘M run’ is the time in seconds it takes the controlled component to move from fully closed to fully open position.
* See Appendix “Parameter ID overview”
Set the ‘M run’ according to the examples or measure the running time by means of a stop watch.
How to calculate the running time of a motorized control valve
The running time of the motorized control valve is calculated using the following methods:
Seated valves
Running time = Valve stroke (mm) x actuator speed (sec. / mm)
Example: 5.0 mm x 15 sec. / mm = 75 sec.
Rotating valves
Running time = Turning degrees x actuator speed (sec. / degr.)
Example: 90 degr. x 2 sec. / degr. = 180 sec.
MENU > Settings > Control par.
MENU > Settings > Control par., cool.
MENU > Settings > Control par., fan
MENU > Settings > Control par., inlet
MENU > Settings > Control par., outlet
MENU > Settings > Control par., P circ.
MENU > Settings > Control par., P refill
MENU > Settings > Control par. 1
MENU > Settings > Control par. 2
Nz (neutral zone)
Circuit
All
Setting range
*
1x187
Factory setting
When the actual flow / duct temperature is within the neutral zone, the controller does not activate the motorized control valve.
*
* See Appendix “Parameter ID overview”
Set the acceptable flow /duct temperature deviation.
Set the neutral zone to a high value if you can accept a high variation in flow temperature.
The neutral zone is symmetrical around the desired flow / duct temperature value, i.e. half the value is above and half the value is below this temperature.
MENU > Settings > Control par.
MENU > Settings > Control par., cool.
MENU > Settings > Control par. 1
MENU > Settings > Control par. 2
Min. act. time (min. activation time gear motor)
Circuit
All
Setting range
*
1x189
Factory setting
*
The min. pulse period of 20 ms (milliseconds ) for activation of the gear motor.
* See Appendix “Parameter ID overview”
Setting example
2
10
50
Value x 20 ms
40 ms
200 ms
1000 ms
The setting should be kept as high as acceptable to increase the lifetime of the actuator (gear motor).
136 DEN-SMT/DK VI.GU.A2.02
Danfoss District Energy
Installation Guide ECL Comfort 210 / 310, application A214 / A314
MENU > Settings > Control par., inlet
MENU > Settings > Control par., outlet
Pressure, des. (desired pressure)
Circuit
All
Setting range
*
Read out of the calculated desired pressure at the inlet / outlet.
Access to conversion (scale) settings: Push dial.
Factory setting
*
* See Appendix “Parameter ID overview”
Set the relationship between outdoor temperature and desired pressure.
Y
-10 5 0 5 1 0 1 5
X
Y
=
=
Outdoor temperature
Desired pressure (Pascal)
X
MENU > Settings > Control par., fan
Air quality
Circuit
All
Setting range
*
Setting the limitation value for air quality (ppm).
* See Appendix “Parameter ID overview”
1x339
Factory setting
*
MENU > Settings > Control par., fan
Outlet fan, offset
Circuit
All
Setting range
*
1x356
Factory setting
Setting an offset value for the relationship between two fan speeds.
*
* See Appendix “Parameter ID overview”
MENU > Settings > Control par., fan
MENU > Settings > Control par., inlet
Fan speed, red. (reduced fan speed)
Circuit
All
Setting range
*
1x357
Factory setting
*
When the ECL Comfort 310 controller is in active saving mode, the fan speed can be reduced.
* See Appendix “Parameter ID overview”
OFF:
Fan is OFF during Saving mode
Value:
Fan is ON during Saving mode, but at set, reduced speed
Danfoss District Energy VI.GU.A2.02
DEN-SMT/DK 137
Installation Guide ECL Comfort 210 / 310, application A214 / A314
MENU > Settings > Application
MENU > Settings > Control par. 2
1. step level
Circuit
All
Setting range
*
The total control range is covered by M2 within the set % value.
1x368
Factory setting
*
* See Appendix “Parameter ID overview”
MENU > Settings > Application
MENU > Settings > Control par. 2
2. step level
Circuit
All
Setting range
*
1x369
Factory setting
From the set % value and up to 100 %, the control is covered by M1.
*
* See Appendix “Parameter ID overview”
MENU > Settings > Control par., fan
MENU > Settings > Control par., inlet
MENU > Settings > Control par., outlet
X1
Circuit
All
Setting range
*
1x406
Factory setting
*
Definition of which voltage value corresponds to which pressure value.
The voltage (as a 0 - 10 volt signal) comes from a pressure transmitter and is applied to the relevant input.
This input voltage is converted to display a pressure value (in Pascal).
See also "Pressure" and "X2".
* See Appendix “Parameter ID overview”
X
=
Volt
Y
=
Pressure
# 1 #
=
'X1'
138 DEN-SMT/DK VI.GU.A2.02
Danfoss District Energy
Installation Guide ECL Comfort 210 / 310, application A214 / A314
MENU > Settings > Control par., fan
MENU > Settings > Control par., inlet
MENU > Settings > Control par., outlet
X2
1x407
Circuit
All
Setting range
*
Factory setting
*
Definition of which voltage value corresponds to which pressure value.
The voltage (as a 0 - 10 volt signal) comes from a pressure transmitter and is applied to the relevant input.
This input voltage is converted to display a pressure value (in Pascal).
See also "Pressure" and "X1".
* See Appendix “Parameter ID overview”
X
Y
# 1 #
=
=
=
Volt
Pressure
'X2'
MENU > Settings > Control par., inlet
MENU > Settings > Control par., outlet
Pressure
Circuit
All
Setting range
*
Factory setting
*
The actual pressure, measured in Pascal.
A 0 - 10 volt signal comes from a pressure transmitter and is applied to related input.
This input voltage is converted to the displayed pressure value.
Access to conversion (scale) settings: Push dial.
* See Appendix “Parameter ID overview”
The pressure is measured by means of a 0 - 10 volt signal.
The measured voltage must be converted to a pressure value by the controller.
The following procedure sets up the conversion:
Push the dial to see the graph and enter the value sets for the 2 input voltages and related pressure values.
Pressure value range: 0 … 1999 pascal
The factory set voltage values can be changed in the two separate menus "X1" and "X2".
Typically, the higher the voltage, the higher the displayed pressure.
Danfoss District Energy VI.GU.A2.02
DEN-SMT/DK 139
Installation Guide ECL Comfort 210 / 310, application A214 / A314
If you want to tune the PI regulation precisely, you can use the following method:
• Set the ‘Tn’ (integration time constant) to its max. value (999 sec.).
• Decrease the value for the ‘Xp’ (proportional band) until the system starts hunting (i.e. gets unstable) with a constant amplitude (it might be necessary to force the system by setting an extreme low value).
• Find the critical time period on the temperature recorder or use a stop watch.
Temp.
Critical time period
Time
This critical time period will be characteristic for the system, and you can evaluate the settings from this critical period.
‘Tn’ = 0.85 x critical time period
‘Xp’ = 2.2 x proportional band value in the critical time period
If the regulation seems to be too slow, you can decrease the proportional band value by 10%. Make sure there is a consumption when you set the parameters.
140 DEN-SMT/DK VI.GU.A2.02
Danfoss District Energy
Installation Guide ECL Comfort 210 / 310, application A214 / A314
5.9 Fan / acc. control (fan / accessory control)
This section describes the function possibilities for relay 1 (F1), relay 2 (P2), relay 3 (X3), relay 4 (X4), relay 5 (X5), relay 7 (P7) and relay 8 (P8).
Schedule 1 is set in circuit 1, whereas Schedule 2 (and 3) are set in circuit 2 or "Common controller".
When the ECL Comfort controller is in Saving mode, the system can be totally stopped or work in Saving conditions.
The output X3 ('Optional function', ID 1x090) is flexible and has different options, depending on application. See the table at the parameter description.
A214.6 and A314.3:
The parameter "Fan function" (ID 11137) has no functionality. The parameter is prepared for future use.
A314.4 … A314.7 and A314.9:
The output X4 is controlled from Schedule 3.
Comfort = relay closed; Saving = relay open.
The output X5 is used in A314.6 and A314.7. X5 is ON at cooling demand.
The output P7 (in ECA 32) is used in A314.4 . . . A314.7 for control of the circulation pump in the Fluid battery.
The output P8 (in ECA 32) is used in A314.4, A314.5 and A314.9 for control of the "Night damper".
The parameter 'Stop difference' (ID 1x194) is used differently, depending on application:
• A214.6: When X3 is set to act as room thermostat.
• A314.4 … A314.7:
When utilizing the "Night cooling" function. The room temperature must be "Stop difference" higher than the outdoor temperature for enabling "Night cooling".
Parameters indicated with an ID no. like "1x607" mean a universal parameter.
x stands for circuit / parameter group.
Danfoss District Energy VI.GU.A2.02
DEN-SMT/DK 141
Installation Guide ECL Comfort 210 / 310, application A214 / A314
MENU > Settings > Fan / acc. control
MENU > Settings > Room limit
Room T diff.
Circuit Setting range
1x027
Factory setting
All *
The relay 3 (X3) can be activated when the room temperature gets lower than the desired room temperature.
Relay X3 is activated when the difference between the actual room temperature and the desired room temperature is bigger than the set value.
Relay X3 is deactivated when the actual room temperature becomes higher than the desired room temperature.
*
* See Appendix “Parameter ID overview”
OFF:
Value:
Function disabled
Set the desired temperature difference
In order to activate the relay X3 in relation to room temperature difference, the code setting in 'Optional function' must be "3".
Room temp.
° C
Room T diff.
ON
OFF
Desired room temp.
Actual room temp.
Relay X3
Time
MENU > Settings > Application
MENU > Settings > Fan / acc. control
P frost T (circulation pump, frost protection temp.)
Circuit
All
Setting range
*
1x077
Factory setting
*
Frost protection, based on the outdoor temperature.
When the outdoor temperature gets below the set temperature value in ‘P frost T’, the controller automatically switches ON the circulation pump (for example P1 or X3) to protect the system.
* See Appendix “Parameter ID overview”
OFF:
Value:
No frost protection.
Circulation pump is ON when the outdoor temperature is below the set value.
Under normal conditions, your system is not frost protected if your setting is below 0 °C or OFF.
For water-based systems, a setting of 2 °C is recommended.
If the outdoor temperature sensor is not connected and the factory setting has not been changed to 'OFF', the circulation pump is always
ON.
MENU > Settings > Fan / acc. control
Fan cut-in delay (relay 1, F1)
Circuit
All
Delay for activating the fan.
Setting range
*
* See Appendix “Parameter ID overview”
Value:
Set the delay (in seconds).
1x086
Factory setting
*
A delay in fan cut-in can prevent frost damages in the heat exchanger.
142 DEN-SMT/DK VI.GU.A2.02
Danfoss District Energy
Installation Guide ECL Comfort 210 / 310, application A214 / A314
MENU > Settings > Fan / acc. control
Acc. cut-in delay (Accessory cut-in delay, relay 2, P2)
Circuit Setting range
All
Set the delay for activating the damper (relay 2, P2).
*
1x087
Factory setting
*
* See Appendix “Parameter ID overview”
0 ... 900: Set the delay (in seconds).
A delay in opening the damper can prevent frost damages in the heat exchanger.
MENU > Settings > Fan / acc. control
Fan output func. (Fan output function, relay 1, F1)
Circuit Setting range
All *
1x088
Factory setting
Desired function for relay 1 (F1). F1 is typically the fan. The codes have different meanings.
*
* See Appendix “Parameter ID overview”
Code:
0
1
2
3
Description (relay 1 (F1)):
Comfort mode Saving mode
The connected unit is switched OFF
The connected unit is switched ON
Frost alarm
Example, code = 1:
The fan is ON during Comfort mode. In case of frost alarm, the fan is switched OFF.
Depending on application, the control of fan F1 can furthermore be related to:
- Saving mode with or without 'Total stop'
- Setting of 'Fan function'
Danfoss District Energy VI.GU.A2.02
DEN-SMT/DK 143
Installation Guide ECL Comfort 210 / 310, application A214 / A314
MENU > Settings > Fan / acc. control
MENU > Settings > Optional function
Acc. output func. (Accessory output function, relay 2, P2)
Circuit Setting range
1x089
Factory setting
All *
Desired function for relay 2 (P2). P2 is typically the damper. The codes have different meanings.
*
* See Appendix “Parameter ID overview”
Code: Description (relay 2 (P2)):
Comfort mode Saving mode Frost alarm
2
3
0
1
The connected unit is switched OFF
The connected unit is switched ON
Example, code = 1:
The damper is open (switched ON) during Comfort mode. In case of frost alarm, the damper is closed (switched OFF).
144 DEN-SMT/DK VI.GU.A2.02
Danfoss District Energy
Installation Guide ECL Comfort 210 / 310, application A214 / A314
MENU > Settings > Fan / acc. control
Optional function (relay 3, X3)
Circuit
All
Setting range
*
Desired function for relay 3 (X3). The codes have different meanings.
1x090
Factory setting
*
* See Appendix “Parameter ID overview”
Code: 0 1 2 3
A214.1
Pu-cool Sch-1 Sch-2 Cool dem.
A214.2
Pu-heat Sch-1 Sch-2
A214.3
Pu-heat Sch-1 Sch-2 Room stat.
A214.4
Pu-heat Sch-1 Sch-2 Cool dem.
A214.5
Pu-heat Sch-1 Sch-2 Cool dem.
A214.6
Pu-heat Sch-1 Sch-2
Room stat.
4
Pu-cool
Pu-cool
A314.1
Pu-heat Sch-1 Sch-2 Cool dem.
A314.2
Pu-heat Sch-1 Sch-2 Cool dem.
A314.3
Pu-heat Sch-1 Sch-2
Room stat.
Pu-cool:
Pu-heat:
Sch-1:
Sch-2:
Cool-dem.:
Room stat.:
Pu-cool
Pu-cool
Control of circulation pump in cooling circuit
Control of circulation pump in heating circuit
Follows Schedule 1
Follows Schedule 2
ON at cooling demand
Room thermostat function
MENU > Settings > Fan / acc. control
Acc. time control (Accessory time control, relay 2, P2)
Circuit Setting range
1x091
Factory setting
All * *
The connected unit can follow schedule 1 or schedule 2.
* See Appendix “Parameter ID overview”
1:
2:
Relay 2 follows schedule 1.
Relay 2 follows schedule 2.
Danfoss District Energy VI.GU.A2.02
DEN-SMT/DK 145
Installation Guide ECL Comfort 210 / 310, application A214 / A314
MENU > Settings > Fan / acc. control
Fan function
Circuit
All
Setting range
*
The fan can remain switched ON even if saving mode is active.
1x137
Factory setting
*
* See Appendix “Parameter ID overview”
OFF:
ON:
The fan is switched OFF during saving mode.
The fan is switched ON also during saving mode.
146 DEN-SMT/DK VI.GU.A2.02
Danfoss District Energy
Installation Guide ECL Comfort 210 / 310, application A214 / A314
MENU > Settings > Application
MENU > Settings > Fan / acc. control
Stop difference
Circuit Setting range
1x194
Factory setting
All *
When the difference between outdoor temperature and room temperature gets higher than the set value, the related function is enabled.
*
Application A214.6:
Y
* See Appendix “Parameter ID overview”
# 4 #
# 5 #
X
=
Time
Y
=
Temperature
# 1 #
=
Desired room temperature
# 2 #
=
'Room T diff.' (ID 1x027)
# 3 #
=
'Stop diff.' (ID 1x194)
# 4 #
=
Room temperature
# 5 #
=
X3 status
Application A314.4 . . . A314.7:
Y
# 2 #
# 1 #
# 3 #
X
# 1 #
# 2 #
# 3 #
# 4 #
X
=
Time
Y
=
Temperature
# 1 #
=
'Stop diff.' (ID 1x194)
# 2 #
=
Room temperature
# 3 #
=
Outdoor temperature
# 4 #
=
Night cooling possible / not possible
X
Danfoss District Energy VI.GU.A2.02
DEN-SMT/DK 147
Installation Guide ECL Comfort 210 / 310, application A214 / A314
A314.3:
Wind influence on fan speed
A wind speed sensor can be connected to the ECL controller in order to control the fan speed. Typically, the more windy, the higher the fan speed.
The signal from the wind speed sensor is a 0-10 volt signal which is applied directly to input S10. The voltage rises at higher wind speed.
The measured voltage on input S10 must be converted to a wind speed value by the controller.
The following procedure sets up the scaling.
MENU > Settings > Fan / acc. control
MENU > Settings > Wind influence
Wind actual
Circuit
All
Setting range Factory setting
The actual wind speed is indicated by the unit ‘m/s’ (meter per second).
Push the dial to see the graph and enter the value sets for the input voltage (2 and 10 volt) and displayed wind speed.
Wind speed:
Fixed voltage settings:
Factory settings:
0.0 ... 75.0 m/s
2 V and 10 V
(2 , 5.0) and (10 , 25.0)
This means that the ‘Wind actual’ is 5.0 m/s at 2.0 volt and 25.0
m/s at 10 volt.
Typically, the higher the voltage, the higher the displayed wind speed.
Example: Relationship between input voltage and displayed wind speed
Wind speed (m/s)
25. 0
5.0
Volt
2 10
This example shows that 2 volt correspond to 5.0 m/s and 10 volt correspond to 25.0 m/s.
148 DEN-SMT/DK VI.GU.A2.02
Danfoss District Energy
Installation Guide ECL Comfort 210 / 310, application A214 / A314
MENU > Settings > Fan / acc. control
MENU > Settings > Flow / power limit
MENU > Settings > Wind influence
Filter constant
Circuit
All
Setting range
*
1x081
Factory setting
The filter constant dampens the measured input data by the set factor.
*
* See Appendix “Parameter ID overview”
Minor value:
Major value:
Minor dampening (low filter constant)
Major dampening (high filter constant)
MENU > Settings > Fan / acc. control
MENU > Settings > Flow temperature
Control voltage
Circuit Setting range
All
Output voltage in relation to measured wind speed.
*
1x104
Factory setting
* See Appendix “Parameter ID overview”
The measured and converted wind speed signal controls the output signal 'Control voltage'. Typically, the higher the wind speed, the higher the 'control voltage' for the fan speed.
Push the dial to see the graph and enter the value sets for the wind speed values (0 and 10 m/s) and control voltage.
Control voltage: 0.0 ... 10.0 V
Fixed wind speed settings: 0 (zero) m/s and 10 m/s.
Factory settings: (0 , 2.0) and (10 , 10.0).
This means that the ‘Control voltage’ is 2.0 volt at 0 m/s and 10.0
volt at 10 m/s.
Typically, the higher the wind speed, the higher the 'Control voltage'.
Example: Relationship between displayed wind speed and control voltage
Control voltage
10. 0
2.0
Wind speed
(m/s)
0 10
This example shows that 0 (zero) m/s corresponds to 2.0 volt and 10 m/s corresponds to 10.0 volt.
The 'Control voltage' is only available from the internal module ECA 32.
Danfoss District Energy VI.GU.A2.02
DEN-SMT/DK 149
Installation Guide ECL Comfort 210 / 310, application A214 / A314
5.10 Application
The section "Application" describes specific application related issues.
"Total stop" (ID 1x021) works differently, depending on actual subtype. In relation to the parameter "Fan function" (ID 11137), selected subtype and controller mode, different functionalities are present. See the related tables.
"Stop at T out" (ID 1x038) is used for the "Night cooling" function.
Outdoor temperature must be higher than set value in order to activate "Night cooling".
"Comp. T select" (ID 1x140) is a universal parameter:
A214.1 - A214.6 and A314.1 - A314.3:
The desired flow / duct temperature can be influenced by a compensation temperature, measured by S1 or S2. The choice between S1 and S2 is made by the parameter "Comp. T select".
A314.4 - A314.7 and A314.9:
The desired flow / duct temperature can be influenced by a compensation temperature, measured by one of the temperature sensors S1 . . . S16.
The choice of compensation sensor is made by the parameter
"Comp. T select".
"Summer, cut-out" (ID 1x179) is present in A314.4 and A314.5.
When outdoor temperature gets higher than cut-out value + 0.5 K, the heating is stopped.
Falling outdoor temperature: When actual - and "accumulated outdoor temperature" come below cut-out value - 0.5 K, the heating will start. The time constant for "accumulated outdoor temperature" is a fixed value and corresponds to an average building's time constant.
The parameter 'Stop difference' (ID 1x194) is used differently, depending on application:
A214.6: When X3 is set to act as room thermostat.
A314.4 … A314.7: When utilizing the "Night cooling" function.
The room temperature must be "Stop difference" higher than the outdoor temperature for enabling "Night cooling".
"S4 filter" is present in the subtypes A214.2, A214.4 and A314.1.
"1. step level" and "2. step level" are used for smooth transition between recovery stage and heating / cooling stage.
"Send desired T" (ID 1x500) is present in some of the subtypes.
Parameters indicated with an ID no. like "1x607" mean a universal parameter.
x stands for circuit / parameter group.
150 DEN-SMT/DK VI.GU.A2.02
Danfoss District Energy
Installation Guide ECL Comfort 210 / 310, application A214 / A314
MENU > Settings > Application
ECA addr. (ECA address, choice of Remote Control Unit)
Circuit Setting range
1x010
Factory setting
All * *
Decides the room temperature signal transfer and communication with the
Remote Control Unit.
* See Appendix “Parameter ID overview”
OFF:
No Remote Control Unit. Only room temperature sensor, if any.
A:
Remote Control Unit ECA 30 / 31 with address A.
B:
Remote Control Unit ECA 30 / 31 with address B.
The Remote Control Unit must be set accordingly (A or B).
MENU > Settings > Application
MENU > Settings > Optimization
Total stop
Circuit
All
Setting range
*
1x021
Factory setting
*
Setting the 'Total stop' to OFF or ON gives different results, depending on the actual application (subtype). The conditions, among others, are:
- Room temperature controlled applications
- Controllers mode
- Desired "Fan function" (ID 11137)
* See Appendix “Parameter ID overview”
OFF:
ON:
No total stop
Heating applications in general:
Saving mode: The desired flow / duct temperature is reduced according to desired duct / room temperature.
Cooling applications in general:
Saving mode: The cooling is stopped.
Total stop
Heating applications in general:
Saving mode:
The desired flow / duct temperature is reduced to the Frost protection value.
Cooling applications in general:
Saving mode: The cooling is stopped.
The examples below are related to heating applications:
Desired flow temp. °C
Total stop = ON
Desired flow temp. °C
‘Frost pr.’
Time
Total stop = OFF
‘Frost pr.’
Time
The min. flow temperature limitation ('Temp. min.') is overruled when
'Total stop' is ON.
Danfoss District Energy VI.GU.A2.02
DEN-SMT/DK 151
Installation Guide ECL Comfort 210 / 310, application A214 / A314
Fan control related to actual application (subtype), Total stop,
Fan function and mode:
A214.1, A214.6 and A314.3
(with and without room temperature signal):
Total stop
(ID 11021)
Fan
(F1)
Mode:
Comfort
Saving
OFF
ON
OFF
ON
= Fan OFF
= Fan ON
A214.2, A214.3, A314.4, A314.5 and A314.9
(with room temperature signal):
Total stop
(ID 11021)
Fan function
(ID 11137)
Mode:
Comfort
Saving
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
OFF
ON
ON
OFF
OFF
ON
ON
*
= Fan OFF
= Fan ON
See the function diagram
"Fan stop", heating applications.
Fan
(F1)
*
*
*
152 DEN-SMT/DK VI.GU.A2.02
Danfoss District Energy
Installation Guide ECL Comfort 210 / 310, application A214 / A314
Function diagram "Fan function", heating applications:
T
1 K
# 1 #
# 2 #
X
X
=
Time
T
=
Room temperature
# 1 #
=
Desired room temperature
# 2 #
=
Output status
Danfoss District Energy VI.GU.A2.02
DEN-SMT/DK 153
Installation Guide ECL Comfort 210 / 310, application A214 / A314
A214.2, A214.3, A314.4, A314.5 and A314.9
(without room temperature signal):
Total stop
(ID 11021)
Fan function
(ID 11137)
Mode:
Comfort
Saving
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
OFF
ON
ON
OFF
OFF
ON
ON
= Fan OFF
= Fan ON
Fan
(F1)
A214.4, A214.5, A314.1, A314.2, A314.6 and A314.7
(with and without room temperature signal):
Total stop
(ID 11021)
Fan function
(ID 11137)
Mode:
Comfort
Saving
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
OFF
ON
ON
OFF
OFF
ON
ON
Fan
(F1)
*
*
*
*
*
= Fan OFF
= Fan ON
See the function diagram
"Fan function", heating / cooling applications
154 DEN-SMT/DK VI.GU.A2.02
Danfoss District Energy
Installation Guide ECL Comfort 210 / 310, application A214 / A314
Function diagram "Fan function", heating / cooling applications:
# 1 #
# 2 #
# 4 #
# 5 #
# 3 #
X
X
=
Time
# 1 #
=
Cooling mode
# 2 #
=
Heating mode
# 3 #
=
Dead zone Dz ( ID 11009)
# 4 #
=
Fan function (ID 11137) = ON
# 5 #
=
Fan function (ID 11137) = OFF
MENU > Settings > Application
Stop at T out
Circuit
All
Setting range
*
When the outdoor temperature gets higher than set limit, the related function is enabled.
1x038
Factory setting
*
* See Appendix “Parameter ID overview”
Value:
OFF:
Limit for outdoor temperature dependent functionality.
The 'Stop at T out' function is not active.
MENU > Settings > Application
MENU > Settings > Fan / acc. control
P frost T (circulation pump, frost protection temp.)
Circuit Setting range
1x077
Factory setting
All *
Frost protection, based on the outdoor temperature.
When the outdoor temperature gets below the set temperature value in ‘P frost T’, the controller automatically switches ON the circulation pump (for example P1 or X3) to protect the system.
*
* See Appendix “Parameter ID overview”
OFF:
Value:
No frost protection.
Circulation pump is ON when the outdoor temperature is below the set value.
Under normal conditions, your system is not frost protected if your setting is below 0 °C or OFF.
For water-based systems, a setting of 2 °C is recommended.
If the outdoor temperature sensor is not connected and the factory setting has not been changed to 'OFF', the circulation pump is always
ON.
Danfoss District Energy VI.GU.A2.02
DEN-SMT/DK 155
Installation Guide ECL Comfort 210 / 310, application A214 / A314
MENU > Settings > Application
Accum. filter (Accummulation filter)
Circuit
All
Setting range
*
1x082
Factory setting
The value determines the filtering of the desired flow / duct temperature in order to change correctly from heating to cooling mode or vice versa.
The set value is an indirect time constant. The resulting time constant is listed in the examples below.
*
* See Appendix “Parameter ID overview”
Duct / room temp.
° C
Dead zone (ID no.
11009)
Actual
Dampened
Heating
Cooling
Low value:
Minor dampening.
High value:
Major dampening.
The setting values (examples) give the following approximate time constants:
Set value (examples):
10:
20:
50:
100:
200:
250:
1:
2:
5:
Resulting time constant:
80 sec
160 sec
~ 7 min
~ 14 min
~ 25 min
~ 1 hour
~ 2 hours
~ 4 hours
~ 5.5 hours
The setting of 'Accum. filter' prevents unexpected changes between heating and cooling or changes between heating and passive cooling.
MENU > Settings > Application
Frost pr. T (frost protection temp.)
Circuit
All
Setting range
*
1x093
Factory setting
Set the desired flow temperature at temperature sensor S3 to protect the system against frost (at heating cut-out, total stop etc.).
When the temperature at S3 gets lower than the setting, the motorized control valve opens gradually.
*
* See Appendix “Parameter ID overview”
The frost protection temperature can also be set in your favorite display when the mode selector is in frost protection mode.
156 DEN-SMT/DK VI.GU.A2.02
Danfoss District Energy
Installation Guide ECL Comfort 210 / 310, application A214 / A314
MENU > Settings > Application
Comp. T select (Compensation temperature selection)
Circuit Setting range
1x140
Factory setting
All
Selection of compensation temperature.
* *
* See Appendix “Parameter ID overview”
OFF:
The compensation temperature is measured by S1 or the S1 value is received from the ECL 485 bus.
ON:
The compensation temperature is measured by S2.
Sxvalue:
The compensation temperature.
Override mode functions:
The following settings describe the function in general for the ECL
Comfort 210 / 310 series. The explained modes are typical and not application related. They might differ from the override modes in your application.
MENU > Settings > Application
Ext. input (external override)
Circuit
All
Setting range
*
1x141
Factory setting
Choose the input for 'Ext. input' (external override). By means of a switch the controller can be overridden to ‘Comfort’, 'Saving', 'Frost protection' or
'Constant temperature' mode.
*
Example: Connection of an override switch
* See Appendix “Parameter ID overview”
Example: Connection of an override relay
OFF:
No inputs have been selected for external override.
S1 ... S16: Input selected for external override.
If S1... S6 is chosen as override input, the override switch must have gold-plated contacts.
If S7 ... S16 is chosen as override input, the override switch can be a standard contact.
See the drawings for connection examples of override switch and override relay to input S8.
Choose only an unused input for override. If an already used input is applied for override, the functionality of this input is also neglected.
See also ‘Ext. mode’.
Danfoss District Energy VI.GU.A2.02
DEN-SMT/DK 157
Installation Guide ECL Comfort 210 / 310, application A214 / A314
MENU > Settings > Application
Ext. mode (external override mode)
Circuit Setting range
1x142
Factory setting
COMFORT / SAVING /
FROST PR. / CONST. T
COMFORT
The mode override can be activated for Saving, Comfort, Frost pr. or
Constant T mode.
For override, the controller mode must be in scheduled mode.
See also ‘Ext. input’.
Example: Override to Comfort mode
Choose an override mode:
SAVING:
The circuit in question is in saving mode when the override switch is closed.
COMFORT:
The circuit in question is in comfort mode when the override switch is closed.
FROST PR.:
The heating or DHW circuit closes, but is still frost protected.
CONSTANT T: The circuit in question controls a constant temperature *)
*)
See also 'Desired T' (1x004), setting of desired flow temperature (MENU > Settings > Flow temperature)
See also ' Con. T, ret. T lim.' (1x028), setting of return temperature limitation (MENU > Settings > Return limit)
# 1 # = Override switch (not activated / activated)
# 2 # = Function mode (Schedule / Comfort)
# 3 # = Time
Example: Override to Saving mode
The process diagrams show the functionality.
# 1 # = Override switch (not activated / activated)
# 2 # = Function mode (Schedule / Saving)
# 3 # = Time
The result of override to 'Saving' mode depends on the setting in
'Total stop'.
Total stop = OFF: Heating reduced
Total stop = ON: Heating stopped
158 DEN-SMT/DK VI.GU.A2.02
Danfoss District Energy
Installation Guide ECL Comfort 210 / 310, application A214 / A314
Example: Override to Frost protection mode
# 1 # = Override switch (not activated / activated)
# 2 # = Function mode (Schedule / Frost pr.)
# 3 # = Time
Example: Override to Constant temperature mode
# 1 # = Override switch (not activated / activated)
# 2 # = Function mode (Schedule / Const. T)
# 3 # = Time
The "Const. T" value can be influenced by:
• temp. max.
• temp. min.
• room temp. limit
• return temp. limit
• flow / power limit
Danfoss District Energy VI.GU.A2.02
DEN-SMT/DK 159
Installation Guide ECL Comfort 210 / 310, application A214 / A314
MENU > Settings > Application
MENU > Settings > Heat cut-out
MENU > Settings > Optimization
Summer, cut-out (limit for heating cut-out)
Circuit Setting range
All
*
1x179
Factory setting
*
* See Appendix “Parameter ID overview”
The heating can be switched OFF when the outdoor temperature is higher than the set value. The valve closes and after the post-run time, the heating circulation pump stops. ‘Temp. min.’ will be overruled.
The heating system switches ON again when the outdoor temperature and the accumulated (filtered) outdoor temperature become lower than the set limit.
This function can save energy.
Set the value for outdoor temperature at which you want the heating system to switch OFF.
Temp.
1 8 °C
Actual outdoor temp.
Accumulated outdoor temp.
Heating ON Heating OFF Heating ON
Time
The heating cut-out is only active when the controller mode is in scheduled operation. When the cut-out value is set to OFF, there is no heating cut-out.
160 DEN-SMT/DK VI.GU.A2.02
Danfoss District Energy
Installation Guide ECL Comfort 210 / 310, application A214 / A314
MENU > Settings > Application
MENU > Settings > Fan / acc. control
Stop difference
Circuit Setting range
1x194
Factory setting
All *
When the difference between outdoor temperature and room temperature gets higher than the set value, the related function is enabled.
*
Application A214.6:
Y
* See Appendix “Parameter ID overview”
# 4 #
# 5 #
X
=
Time
Y
=
Temperature
# 1 #
=
Desired room temperature
# 2 #
=
'Room T diff.' (ID 1x027)
# 3 #
=
'Stop diff.' (ID 1x194)
# 4 #
=
Room temperature
# 5 #
=
X3 status
Application A314.4 . . . A314.7:
Y
# 2 #
# 1 #
# 3 #
X
# 1 #
# 2 #
# 3 #
# 4 #
X
=
Time
Y
=
Temperature
# 1 #
=
'Stop diff.' (ID 1x194)
# 2 #
=
Room temperature
# 3 #
=
Outdoor temperature
# 4 #
=
Night cooling possible / not possible
X
Danfoss District Energy VI.GU.A2.02
DEN-SMT/DK 161
Installation Guide ECL Comfort 210 / 310, application A214 / A314
MENU > Settings > Application
S4 filter
Circuit
All
Setting range
*
1x304
Factory setting
The filtering of the measured temperature at S4 prevents instability in the control of the duct temperature.
The set value is an indirect time constant. The resulting time constant is listed in the examples below.
*
* See Appendix “Parameter ID overview”
Low value:
Low filtering (minor dampening)
High value:
High filtering (major dampening)
The setting values (examples) give the following approximate time constants:
Set value (examples):
10
20
50
100
1
2
5
Resulting time constant:
1 sec
1.5 sec
4 sec
7 sec
14 sec
35 sec
70 sec
MENU > Settings > Application
MENU > Settings > Control par. 2
1. step level
Circuit
All
Setting range
*
1x368
Factory setting
*
The total control range is covered by M2 within the set % value.
* See Appendix “Parameter ID overview”
MENU > Settings > Application
MENU > Settings > Control par. 2
2. step level
Circuit
All
Setting range
*
1x369
Factory setting
*
From the set % value and up to 100 %, the control is covered by M1.
* See Appendix “Parameter ID overview”
162 DEN-SMT/DK VI.GU.A2.02
Danfoss District Energy
Installation Guide ECL Comfort 210 / 310, application A214 / A314
MENU > Settings > Application
Send desired T
Circuit Setting range
1x500
Factory setting
All *
When the controller acts as a slave controller in a master / slave system, information about the desired flow temperature can be sent to the master controller via the ECL 485 bus.
*
* See Appendix “Parameter ID overview”
OFF:
Information about the desired flow temperature is not sent to the master controller.
ON:
Information about the desired flow temperature is sent to the master controller.
In the master controller, 'Demand offset' must be set to a value in order to react on a desired flow temperature from a slave controller.
When the controller acts as a slave, its address must be 1, 2, 3 ... 9 in order to send the desired temperature to the master (see the section
‘Miscellaneous’, ‘Several controllers in the same system’).
Danfoss District Energy VI.GU.A2.02
DEN-SMT/DK 163
Installation Guide ECL Comfort 210 / 310, application A214 / A314
5.11 Alarm
Many applications in the ECL Comfort 210 and 310 series have an alarm function. The alarm function activates relay 4
(A214 applications in ECL Comfort 210 or 310) or relay 6 (A314 applications in ECL Comfort 310).
The alarm relay can activate a lamp, a horn, an input to an alarm transmitting device etc.
Typical alarms, type 1:
• S3 defective
• Actual S3 temperature differs from the desired S3 temperature
• Fire alarm (S8)
• Filter monitor S10 (Digital 10)
• Heat recovery
• Activation of a frost thermostat (S7)
• Detection of frost temperature at S5 or S6
Type 1 alarms are present as long as the alarm reason is present.
Typical alarms, type 2:
• Fan monitor S9 (Digital 9)
• Inlet pressure
• Outlet pressure
• Disconnection or short-circuiting of a temperature sensor or its connection.
Type 2 alarms are present even if the alarm reason no longer is present. To remove the alarm indications, the alarms must be cleared.
When an alarm is activated, the appears in the favorite displays.
To find the reason for alarm:
• select MENU
• select ‘Alarm’
• select ‘Alarm overview’. A will be shown at the alarm in question.
Some alarms are generated if a measured value gets higher or lower than set values.
Parameters indicated with an ID no. like "1x607" mean a universal parameter.
x stands for circuit / parameter group.
164 DEN-SMT/DK VI.GU.A2.02
Danfoss District Energy
Installation Guide ECL Comfort 210 / 310, application A214 / A314
MENU > Alarm > Temp. monitor
Upper difference
Circuit
All
Setting range
*
1x147
Factory setting
*
The alarm is activated if the actual flow / duct temperature increases more than the set difference (acceptable temperature difference above the desired flow / duct temperature). See also 'Delay'.
* See Appendix “Parameter ID overview”
OFF:
Value:
The related alarm function is not active.
The alarm function is active if the actual temperature gets above the acceptable difference.
Flow / duct temp. °C
Upper difference (set value)
Desired flow / duct temp.
Time
MENU > Alarm > Temp. monitor
Lower difference
Circuit
All
Setting range
*
1x148
Factory setting
*
The alarm is activated if the actual flow / duct temperature decreases more than the set difference (acceptable temperature difference below the desired flow / duct temperature). See also 'Delay'.
* See Appendix “Parameter ID overview”
OFF:
Value:
The related alarm function is not active.
The alarm function is active if the actual temperature gets below the acceptable difference.
MENU > Alarm > Temp. monitor
Delay
1x149
Circuit
All
Setting range
*
Factory setting
If an alarm condition from either 'Upper difference' or 'Lower difference' is present for a longer time than the set delay (in minutes), the alarm function is activated.
*
* See Appendix “Parameter ID overview”
Value:
The alarm function will be activated if the alarm condition remains after the set delay.
Flow / duct temp. °C
Temp.
Lower difference (set value)
Desired flow / duct temp.
Time
Flow temp.
Alarm limit
Time
Delay
MENU > Alarm > Temp. monitor
Lowest temp.
Circuit
All
Setting range
*
1x150
Factory setting
The alarm function will not be activated if the desired flow / duct temperature is lower than the set value.
*
* See Appendix “Parameter ID overview”
If the cause of the alarm disappears, the alarm indication and output also disappear.
Danfoss District Energy VI.GU.A2.02
DEN-SMT/DK 165
Installation Guide ECL Comfort 210 / 310, application A214 / A314
MENU > Alarm > Digital S9
MENU > Alarm > Inlet pressure
MENU > Alarm > Outlet pressure
Clear alarm
Circuit
All
Setting range
*
Alarm types 2 (requiring manual reset) can be reset here.
1x390
Factory setting
*
* See Appendix “Parameter ID overview”
OFF:
ON:
No alarm present
Resetting the alarm
An alarm can be cleared (to "OFF").
If the alarm reason still exists, the "OFF" changes to "ON" after 10 seconds (alarm types without delay) or the alarm's delay time (alarm types with delay).
MENU > Alarm > Air quality
MENU > Alarm > Inlet pressure
MENU > Alarm > Outlet pressure
Alarm high
Circuit
All
Setting range
*
1x614
Factory setting
When the measured value gets higher than the set value, the alarm will be activated.
*
* See Appendix “Parameter ID overview”
Value:
Set the alarm value
MENU > Alarm > Air quality
MENU > Alarm > Heat recovery
MENU > Alarm > Inlet pressure
MENU > Alarm > Outlet pressure
Alarm low
Circuit Setting range
1x615
Factory setting
All *
When the measured value gets lower than the set value, the alarm will be activated.
*
* See Appendix “Parameter ID overview”
Value:
Set the alarm value
166 DEN-SMT/DK VI.GU.A2.02
Danfoss District Energy
Installation Guide ECL Comfort 210 / 310, application A214 / A314
0:
1:
MENU > Alarm > Frost thermostat
Alarm value
Circuit Setting range
1x616
Factory setting
All * *
A frost thermostat can be connected to the frost thermostat sensor input.
When the temperature, measured by the frost thermostat, gets below the set value, the S7 input will be activated.
The frost alarm can be activated when the contacts in the frost thermostat open or close.
* See Appendix “Parameter ID overview”
The frost alarm is activated when the contacts in the frost thermostat close.
The frost alarm is activated when the contacts in the frost thermostat open.
An activated frost alarm opens the control valve fully, closes the damper, starts the circulation pump and stops the fan.
'Alarm value' = 0:
An active frost alarm is indicated by a in the display and as OFF in favorite display no. 3.
‘Alarm value' = 1:
An active frost alarm is indicated by a in the display and as ON in favorite display no. 3.
See also 'Alarm time-out', parameter 1x617.
MENU > Alarm > Air quality
MENU > Alarm > Frost thermostat
MENU > Alarm > Heat recovery
MENU > Alarm > Inlet pressure
MENU > Alarm > Outlet pressure
Alarm time-out
Circuit
All
Setting range
*
1x617
Factory setting
The alarm is activated when the alarm reason has been present for a longer time (in seconds) than the set value.
*
* See Appendix “Parameter ID overview”
Value:
Set the alarm time-out
0:
1:
MENU > Alarm > Fire safety
Alarm value
Circuit
All
Setting range
*
1x636
Factory setting
A fire thermostat can be connected to the S8 input. When the temperature, measured by the fire thermostat, gets above the set value, the S8 input will be activated.
The fire alarm can be activated when the contacts in the fire thermostat open or close.
*
* See Appendix “Parameter ID overview”
The fire alarm is activated when the contacts in the fire thermostat close.
The fire alarm is activated when the contacts in the fire thermostat open.
An active fire alarm is indicated by a in the display.
S8 input status:
MENU > Common controller > System > Raw input overview > S8:
0 = Input activated. 1 = input not activated
See also 'Alarm time-out', parameter 1x637.
Danfoss District Energy VI.GU.A2.02
DEN-SMT/DK 167
Installation Guide ECL Comfort 210 / 310, application A214 / A314
MENU > Alarm > Fire safety
Alarm time-out
Circuit
All
Setting range
*
1x637
Factory setting
The alarm is activated when the alarm reason has been present for a longer time (in seconds) than the set value.
*
* See Appendix “Parameter ID overview”
Value:
Set the alarm time-out
MENU > Alarm > Digital S9
MENU > Alarm > Limit T frost
Alarm value
Circuit
All
Setting range
*
1x656
Factory setting
ID 10656 (Digital S9):
A differential pressure switch can be connected to the S9 input. When the differential pressure, measured by the differential pressure switch, gets below the set value, the S9 input will be activated.
The alarm can be activated when the contacts in the differential pressure switch open or close.
ID 11656 (Limit T frost):
When the actual temperature, measured by the return temperature sensor, gets below the set value, the frost alarm will be activated.
*
* See Appendix “Parameter ID overview”
ID 10656 (Digital 9):
0:
1:
The alarm is activated when the contacts in the differential pressure switch close.
The alarm is activated when the contacts in the differential pressure switch open.
ID 11656 (Limit T frost):
When the actual temperature, measured by the return temperature sensor, gets below the set value, the frost alarm will be activated.
ID 10656 (Digital 9):
An active fan alarm is indicated by a in the display.
S9 input status:
MENU > Common controller > System > Raw input overview > S9:
0 = Input activated. 1 = input not activated
ID 11656 (Limit T frost):
An active frost alarm is indicated by a in the display.
See also 'Alarm time-out', parameter 1x657.
An activated frost alarm opens the control valve fully, closes the damper, starts the circulation pump and stops the fan.
MENU > Alarm > Digital S9
Alarm time-out
Circuit
All
Setting range
*
1x657
Factory setting
The alarm is activated when the alarm reason has been present for a longer time (in seconds) than the set value.
*
* See Appendix “Parameter ID overview”
Value:
Set the alarm time-out
168 DEN-SMT/DK VI.GU.A2.02
Danfoss District Energy
Installation Guide ECL Comfort 210 / 310, application A214 / A314
MENU > Alarm > Frost T
Alarm value
Circuit Setting range
1x676
Factory setting
All *
When the actual temperature, measured by S6, gets below the set value, the frost alarm will be activated.
*
* See Appendix “Parameter ID overview”
Value:
Set the alarm value
An activated frost alarm opens the control valve fully, closes the damper, starts the circulation pump and stops the fan.
0:
1:
MENU > Alarm > Digital S10
Alarm value
Circuit
All
Setting range
*
1x696
Factory setting
A differential pressure switch can be connected to the S10 input. When the differential pressure, measured by the differential pressure switch, gets above the set value, the S10 input will be activated.
The alarm can be activated when the contacts in the differential pressure switch open or close.
*
* See Appendix “Parameter ID overview”
The alarm is activated when the contacts in the differential pressure switch close.
The alarm is activated when the contacts in the differential pressure switch open.
MENU > Alarm > Digital S10
Alarm time-out
Circuit Setting range
1x697
Factory setting
All *
The alarm is activated when the alarm reason has been present for a longer time (in seconds) than the set value.
*
* See Appendix “Parameter ID overview”
Value:
Set the alarm time-out
Danfoss District Energy VI.GU.A2.02
DEN-SMT/DK 169
Installation Guide ECL Comfort 210 / 310, application A214 / A314
MENU > Alarm > Alarm overview
Alarm overview, in general
Circuit
All
Setting range
Factory setting
Access to overview showing the alarm number / alarm type. The alarm number is entered into the alarm register and can be obtained from a
SCADA system.
Example: "5: Temp. monitor": If an alarm is activated because of conditions in 'Temp. monitor' the alarm number 5 is placed in the alarm register.
Alarm overview
1: Frost T
2: Limit frost T
3: Frost thermostat
4: Fire safety
5: Temp. monitor
6: Flow T sensor
170 DEN-SMT/DK VI.GU.A2.02
Danfoss District Energy
Installation Guide ECL Comfort 210 / 310, application A214 / A314
6.0 Common controller settings
6.1 Introduction to ‘Common controller settings’
Some general settings which apply to the entire controller are located in a specific part of the controller.
To enter ‘Common controller settings’:
Action: Purpose:
Choose ‘MENU’ in any circuit
Confirm
Choose the circuit selector at the top right corner in the display
Confirm
Choose ‘Common controller settings’
Confirm
Examples:
Circuit selector
Danfoss District Energy VI.GU.A2.02
DEN-SMT/DK 171
Installation Guide ECL Comfort 210 / 310, application A214 / A314
6.2 Time & Date
It is only necessary to set the correct date and time in connection with the first use of the ECL Comfort controller or after a power break of more than 72 hours.
The controller has a 24 hour clock.
Aut. daylight (Daylight saving time changeover)
YES:
The controller’s built-in clock automatically changes + /
- one hour on the standardized days for daylight saving time changeover for Central Europe.
NO:
You change manually between summer and winter time by setting the clock backward or forward.
When controllers are connected as slaves in a master / slave system
(via ECL 485 communication bus), they will receive ‘Time & Date’ from the master.
172 DEN-SMT/DK VI.GU.A2.02
Danfoss District Energy
Installation Guide ECL Comfort 210 / 310, application A214 / A314
6.3 Holiday
This section describes the holiday program in general for the ECL
Comfort 210 / 310 series. The shown displays are typical and not application related. They might differ from the displays in your application. In A214 / A314 applications, however, the holiday program can only be found in circuit 1 but the general description is still valid.
There is a holiday program for each circuit and a holiday program for the common controller.
Each holiday program contains one or more schedules. Each schedule can be set to a start date and an end date. The set period starts on the start date at 00.00 and stops on the end date at 00.00.
Selectable modes are Comfort, Saving, Frost protection or Comfort
7-23 (before 7 and after 23, the mode is scheduled).
How to set your holiday schedule:
Action: Purpose:
Choose ‘MENU’
Confirm
Choose the circuit selector at the top right corner in the display
Confirm
Choose a circuit or 'Common controller settings'
Heating
DHW
Common controller settings
Confirm
Go to ‘Holiday’
Confirm
Choose a schedule
Confirm
Examples:
Confirm choice of mode selector
Choose mode
. Comfort
∙ Comfort 7–23
. Saving
∙ Frost protection
Confirm
Enter the start time first and then the end time
Confirm
Go to ‘Menu’
Confirm
Choose ‘Yes’ or ‘No’ in ‘Save’. Choose the next schedule, if required
7-23
Danfoss District Energy
The holiday program in the ‘Common controller settings’ is valid for all circuits. The holiday program can also be set individually in the heating or DHW circuits.
The end date must be at least be one day later than the start date.
VI.GU.A2.02
DEN-SMT/DK 173
Installation Guide ECL Comfort 210 / 310, application A214 / A314
Holiday, specific circuit / Common Controller
When setting one holiday program in specific circuit and another holiday program in Common Controller, a priority will be taken into account:
1. Comfort
2. Comfort 7 - 23
3. Saving
4. Frost protection
Example 1:
Circuit 1:
Holiday set to "Saving"
Common Controller:
Holiday set to "Comfort"
Result:
As long as "Comfort" is active in Common Controller, circuit 1 will be in
"Comfort".
Example 2:
Circuit 1:
Holiday set to "Comfort"
Common Controller:
Holiday set to "Saving"
Result:
As long as "Comfort" is active in circuit 1, it will be in "Comfort".
Example 3:
Circuit 1:
Holiday set to "Frost protection"
Common Controller:
Holiday set to "Saving"
Result:
As long as "Saving" is active in Common Controller, circuit 1 will be in "Saving".
The ECA 30 / 31 cannot override the holiday schedule of the controller temporarily.
However, it is possible to make use of the following options from the ECA 30 / 31 when the controller is in scheduled mode:
Day off
Holiday
Relaxing (extended comfort period)
Going out (extended saving period)
Energy-saving trick:
Use 'Going out' (the extended saving period) for airing purposes (e.g.
for ventilating the rooms by means of fresh air from open windows).
Connections and setup procedures for ECA 30 / 31:
See section 'Miscellaneous'.
Quick guide "ECA 30 / 31 to override mode":
1. Go to ECA MENU
2. Move cursor to "Clock" symbol
3. Select the "Clock" symbol
4. Choose and select one of 4 override functions
5. Below the override symbol: Set hours or date
174 DEN-SMT/DK VI.GU.A2.02
Danfoss District Energy
Installation Guide ECL Comfort 210 / 310, application A214 / A314
6.4 Input overview
This section describes the function in general for the ECL Comfort
210 / 310 series. The shown displays are typical and not application related. They might differ from the displays in your application.
The input overview is located in the common controller settings.
This overview will always show you the actual temperatures in the system (read-only).
"Outdoor acc. T" means "Accummulated outdoor temperature" and is a calculated value in the ECL Comfort controller.
Danfoss District Energy VI.GU.A2.02
DEN-SMT/DK 175
Installation Guide ECL Comfort 210 / 310, application A214 / A314
6.5 Log
This section describes the function in general for the ECL Comfort
210 / 310 series. The shown displays are typical and not application related. They might differ from the displays in your application.
The log function (temperature history) allows you to monitor the logs of today, yesterday, the past 2 days as well as the past 4 days for the connected sensors.
There is a log display for the relevant sensor, showing the measured temperature.
The log function is only available in the 'Common controller settings'.
Example 1:
1 day log for yesterday showing the development in outdoor temperature during the past 24 hours.
Example 2:
Today’s log for the actual heating flow temperature as well as the desired temperature.
Example 3:
Yesterday’s log for the DHW flow temperature as well as the desired temperature.
176 DEN-SMT/DK VI.GU.A2.02
Danfoss District Energy
Installation Guide ECL Comfort 210 / 310, application A214 / A314
6.6 Output override
This section describes the function in general for the ECL Comfort
210 / 310 series. The shown displays are typical and not application related. They might differ from the displays in your application.
The output override is used to disable one or more of the controlled components. This could among others be useful in a service situation.
Action: Purpose:
Choose 'MENU' in any of the overview displays
Confirm
Choose the circuit selector at the top right corner in the display
Confirm
Examples:
Choose common controller settings
Confirm
Choose 'Output override'
Confirm
Choose a controlled component
Confirm
Adjust the status of the controlled component:
Motorized control valve: AUTO, STOP,
CLOSE, OPEN
Pump: AUTO, OFF, ON
Confirm status change
M1, P1 etc.
Remember to change the status back again as soon as an override is not required any longer.
Controlled components Circuit selector
"Manual control" has higher priority than "Output override".
When the selected controlled component (output) is not ‘AUTO’, the
ECL Comfort controller does not control the component in question
(pump or motorized control valve e.g.). Frost protection is not active.
When output override of a controlled component is active the symbol
‘ ! ’ is shown to the right of the mode indicator in the enduser displays.
Valves (M), dampers (M) and Fans (V) are in some applications controlled by a 0–10 volt (0–100 %) signal. The control can be set to
AUTO or ON.
AUTO: Normal control (0–100%).
ON: The 0–10 volt signal is set to the %-value, set below the indication
'ON'.
Danfoss District Energy VI.GU.A2.02
DEN-SMT/DK 177
Installation Guide ECL Comfort 210 / 310, application A214 / A314
6.7 Key functions
New application
Application
Factory setting
Copy
Key overview
Erase application:
Removes the existing application. As soon as the ECL key is inserted, another application can be chosen.
Gives an overview over the actual application in the ECL controller. Push the dial again to exit the overview.
System settings:
System settings are, among others, communication set-up, display brightness etc.
User settings:
User settings are, among others, desired room temperature, desired DHW temperature, schedules, heat curve, limitation values etc.
Go to factory:
Restores the factory settings.
To:
Copy direction
System settings
User settings
Start copying
Gives an overview over the inserted ECL key. (Example: A266 Ver. 2.30).
Turn the dial to see the subtypes. Push the dial again to exit the overview.
A more detailed description of how to use the individual ‘Key functions’ can also be seen in ‘Inserting the ECL application key’.
The “Key overview” does not inform — through ECA 30 / 31 — about the subtypes of the application key.
Key inserted / not inserted, description:
ECL Comfort 210 / 310, controller versions lower than 1.36:
-
-
Take out the application key; for 20 minutes settings can be changed.
Power up the controller without the application key inserted; for 20 minutes settings can be changed.
ECL Comfort 210 / 310, controller versions 1.36 and up:
-
-
Take out the application key; for 20 minutes settings can be changed.
Power up the controller without the application key inserted; settings cannot be changed.
178 DEN-SMT/DK VI.GU.A2.02
Danfoss District Energy
Installation Guide ECL Comfort 210 / 310, application A214 / A314
6.8 System
6.8.1 ECL version
In ‘ECL version’ you will always be able to find an overview of the data related to your electronic controller.
Please have this information available if you need to contact your
Danfoss sales organization concerning the controller.
Information about your ECL Application Key can be found in ‘Key functions’ and ‘ Key overview’.
Code no.:
Hardware:
Software:
Serial no.:
Production week:
The Danfoss sales and order no.
for the controller
Hardware version of the controller
Software version of the controller
Unique number for the individual controller
Week no. and year (WW.YYYY)
Example, ECL version
6.8.2 Extension
ECL Comfort 310 only:
‘Extension’ will offer you information about additional modules, if any. An example could be the ECA 32 module.
6.8.3 Ethernet
The ECL Comfort 310 (only) has a Modbus/TCP communication interface that allows the ECL controller to be connected to an
Ethernet network. This allows remote access to the ECL 310 controller based on standard communication infrastructures.
In ‘Ethernet’ it is possible to set up the required IP addresses.
6.8.4 Portal config
The ECL Comfort 310 (only) has a Modbus/TCP communication interface that allows the ECL controller to be monitored and controlled via the ECL Portal.
ECL Portal related parameters are set here.
Danfoss District Energy VI.GU.A2.02
DEN-SMT/DK 179
Installation Guide ECL Comfort 210 / 310, application A214 / A314
6.8.5 Energy meter (heat-meter) and M-bus, general information
ECL 310 only
When using the Application Key in the ECL Comfort 310 / 310B, up to 5 energy meters (heat-meters) can be connected to the M-bus connections.
Connection of energy meter can:
• limit the flow
• limit the power
• transfer energy meter data to the ECL Portal, via Ethernet, and / or a SCADA system, via Modbus.
Energy meter data acquisition from ECL Portal is possible without setting up the M-bus configuration.
Many applications with control of heating, DHW or cooling circuit have the possibility to react on energy meter data.
To verify if actual application key can be set to react on energy meter data:
See Circuit > MENU > Settings > Flow / power.
The ECL Comfort 310 can always be used for monitoring purpose of up to 5 energy meters.
The ECL Comfort 310 acts as an M-bus master and must be set to communicate with connected energy meter(s).
See MENU > Common controller > System > M-bus config.
Technical info:
• The M-bus data are based on standard EN-1434.
• Danfoss recommends AC supplied energy meters in order to avoid battery draining.
MENU > Common controller > System > M-bus config.
State
Circuit
-
Setting range
Information about the current M-bus activity.
-
Read-out
Factory setting
-
IDLE:
INIT:
Normal state
The command for initialization has been activated
SCAN:
The command for scanning has been activated
GATEW: The command Gateway has been activated
The ECL Comfort 310 will return to IDLE when commands have been completed.
Gateway is used for read-out of energy meter via ECL Portal.
MENU > Common controller > System > M-bus config.
Baud (bits per second)
Circuit
-
Setting range
300 / 600 / 1200 / 2400
5997
Factory setting
The communication speed between ECL Comfort 310 and the connected energy meter(s).
300
Typically, 300 or 2400 baud is used.
If ECL Comfort 310 is connected to the ECL Portal, a baud rate of 2400 is recommendable, provided the energy meter allows this.
180 DEN-SMT/DK VI.GU.A2.02
Danfoss District Energy
Installation Guide ECL Comfort 210 / 310, application A214 / A314
MENU > Common controller > System > M-bus config.
Command
Circuit
-
Setting range
NONE / INIT / SCAN / GATEW
5998
Factory setting
NONE
The ECL Comfort 310 is M-bus master. In order to verify connected energy meters, different commands can be activated.
NONE:
No command activated
INIT:
Initialization is activated
SCAN:
Scanning is activated in order to search for connected energy meters. The ECL Comfort 310 detects the
M-bus addresses of up to 5 connected energy meters and place these automatically in the "Energy meters" section. The verified address is placed after "Energy meter 1 (2, 3, 4, 5)"
GATEW: The ECL Comfort 310 acts as a gateway between energy meters and ECL Portal. Used only for service.
Scan time can take up to 12 minutes.
When all energy meters are found, the command can be changed to INIT or NONE.
MENU > Common controller > System > M-bus config.
M-bus address
Energy meter 1 (2, 3, 4, 5)
Circuit
-
Setting range
0 - 255
The set or verified address of energy meter 1 (2, 3, 4, 5).
6000
Factory setting
255
0:
1 - 250:
Normally not used
Valid M-bus addresses
251 - 254: Special functions. Use only M-bus address 254 when one energy meter is connected.
255:
Not used
0:
1:
2:
3:
4:
MENU > Common controller > System > M-bus config.
Type
Energy meter 1 (2, 3, 4, 5)
Circuit
-
Setting range
0 - 4
Selecting data range from the M-bus telegram.
6001
Factory setting
0
Small data set, small units
Small data set, large units
Large data set, small units
Large data set, large units
Volume and energy data only
(example: HydroPort Pulse)
Data examples:
0:
Flow temp., return temp., flow, power, acc. volume, acc. energy.
3:
Flow temp., return temp., flow, power, acc. volume, acc. energy, tariff 1, tariff 2.
See also the "Instructions, ECL Comfort 210 / 310, communication description" for further details.
See also Appendix for detailed description of "Type".
Danfoss District Energy VI.GU.A2.02
DEN-SMT/DK 181
Installation Guide ECL Comfort 210 / 310, application A214 / A314
MENU > Common controller > System > M-bus config.
Scan time
Energy meter 1 (2, 3, 4, 5)
Circuit
-
Setting range
1 - 3600 sec
6002
Factory setting
60 sec
Setting the scanning time for acquiring data of connected energy meter(s).
If the energy meter is battery powered, the scan time should be set to a high value to prevent a too fast battery draining.
Oppositely, if the flow / power limitation function is used in the ECL
Comfort 310, the scan time should be set to a low value in order to have quick limitation.
MENU > Common controller > System > M-bus config.
ID
Energy meter 1 (2, 3, 4, 5)
Circuit
-
Setting range
-
Information about the energy meter's serial no.
Read-out
Factory setting
-
MENU > Common controller > System > Energy meters
Energy meter 1 (2, 3, 4, 5)
Circuit
-
Setting range
0 - 4
Read-out
Factory setting
Information from actual energy meter about, for example, ID, temperatures, flow / volume, power / energy.
The shown information depends on the settings made in the “M-bus config.” menu.
0
6.8.6 Raw input overview
Measured temperatures, input status and voltages are displayed.
In addition, a detection of malfunctions can be chosen for activated temperature inputs.
Monitoring the sensors:
Choose the sensor which measures a temperature, for example the
S5. When the dial is pressed, a magnifying glass appears in the selected line. The S5 temperature is now being monitored.
Alarm indication:
Should the connection to the temperature sensor be disconnected, short-circuited or the sensor itself be defective, the alarm function is activated.
In the "Raw input overview" an alarm symbol is shown at the defective temperature sensor in question.
Resetting the alarm:
Choose the sensor (S number) for which you want to clear the alarm. Press the dial. The magnifying glass and alarm symbols disappear.
When the dial is pressed again, the monitoring function is reactivated.
The temperature sensor inputs have a measuring range from -60 ...
150 ° C.
If a temperature sensor or its connection breaks, the value indication is " - - ".
If a temperature sensor or its connection is short-circuited, the value indication is " - - - ".
182 DEN-SMT/DK VI.GU.A2.02
Danfoss District Energy
Installation Guide ECL Comfort 210 / 310, application A214 / A314
6.8.7 Display
Backlight (display brightness)
Circuit
Adjust the brightness of the display.
0:
10:
Weak backlight.
Strong backlight.
Setting range
0 ... 10
60058
Factory setting
5
Contrast (display contrast)
Circuit
Adjust the contrast of the display.
0:
10:
Low contrast.
High contrast.
Setting range
0 ... 10
60059
Factory setting
3
6.8.8 Communication
Modbus addr.
Circuit Setting range
1 ... 247
Set the Modbus address if the controller is part of a Modbus network.
38
Factory setting
1
1 ... 247: Assign the Modbus address within the stated setting range.
The Application Key A214 (subtypes A214.1 . . . A214.6 and A314.1
. . . A314.3) is also able to communicate via Modbus to Danfoss
ADAP-KOOL® Service Manager.
Danfoss District Energy VI.GU.A2.02
DEN-SMT/DK 183
Installation Guide ECL Comfort 210 / 310, application A214 / A314
ECL 485 addr. (master / slave address)
Circuit Setting range
0 ... 15
2048
Factory setting
15
This settting is relevant if more controllers are working in the same ECL
Comfort system (connected via the ECL 485 communication bus) and / or
Remote Control Units (ECA 30 / 31) are connected.
0:
The controller works as slave.
The slave receives information about the outdoor temperature (S1), system time, and signal for DHW demand in the master.
1 ... 9:
The controller works as slave.
The slave receives information about the outdoor temperature (S1), system time, and signal for DHW demand in the master. The slave sends information about the desired flow temperature to the master.
10 ... 14: Reserved.
15:
The ECL 485 communication bus is active.
The controller is master. The master sends information about the outdoor temperature (S1) and system time.
Connected Remote Control Units (ECA 30 / 31) are powered.
The ECL Comfort controllers can be connected via the ECL 485 communication bus to perform a larger system (the ECL 485 communication bus can connect to max. 16 devices).
Each slave must be configured with its own address (1 ... 9).
However, more slaves can have the address 0 if they only have to receive information about outdoor temperature and system time
(listeners).
The total cable length of max. 200 m (all devices incl. the internal ECL
485 communication bus) should not be exceeded.
Cable lengths of more than 200 m may cause noise sensibility (EMC).
In a system with MASTER / SLAVE controllers, only one MASTER controller with address 15 is allowed.
If by mistake more MASTER controllers are present in an ECL 485 communication bus system, decide which controller is to be MASTER.
Change the address in the remaining controllers. However, the system will operate but not be stable with more than one MASTER controller.
In the MASTER controller, the address in ‘ECL 485 addr. (master / slave address)’, ID no. 2048, must always be 15.
Service Pin
Circuit Setting range
0 / 1
This setting is only used in connection with set-up of Modbus communication.
Not applicable for the time being and reserved for future use!
2150
Factory setting
0
0:
1:
Ext. reset
Circuit Setting range
0 / 1
This setting is only used in connection with set-up of Modbus communication.
2151
Factory setting
0
Reset not activated.
Reset.
184 DEN-SMT/DK VI.GU.A2.02
Danfoss District Energy
Installation Guide ECL Comfort 210 / 310, application A214 / A314
6.8.9 Language
Language
Circuit
Choose your language.
Setting range
English / ‘Local’
2050
Factory setting
English
Local language is selected during installation. If you want to change to another local language, the application must be reinstalled. However, it is always possible to change between the local language and English.
Danfoss District Energy VI.GU.A2.02
DEN-SMT/DK 185
Installation Guide ECL Comfort 210 / 310, application A214 / A314
7.0 Miscellaneous
7.1 ECA 30 / 31 setup procedures
ECA 30 (code no. 087H3200) is a remote control unit with built-in room temperature sensor.
ECA 31 (code no. 087H3201) is a remote control unit with built-in room temperature sensor and humidity sensor (relative humidity).
An external room temperature sensor can be connected to both types to substitute the built-in sensor.
An external room temperature sensor will be recognized at ECA
30 / 31 power-up.
Connections: See the section 'Electrical connections'.
Max. two ECA 30 / 31 can be connected to one ECL controller or a system (master-slave) consisting of several ECL controllers connected on the same ECL 485 bus. In the master-slave system only one of the ECL controllers is master. The ECA 30 / 31 can, among others, be set to:
• monitor and set the ECL controller remotely
• measure the room temperature and (ECA 31) humidity
• extend comfort / saving period temporarily
After application upload in the ECL Comfort controller, the remote control unit ECA 30 / 31 will after approx. one minute ask to 'Copy application'.
Confirm this in order to upload the application to the ECA 30 / 31.
Menu structure
The menu structure of ECA 30 / 31 is an "ECA MENU" and the ECL menu, copied from the ECL Comfort controller.
The ECA MENU contains:
Part of the ECA 30 / 31 display in ECL mode:
• ECA settings
• ECA system
• ECA factory
ECA settings: Offset adjustment of the measured room temperature.
Offset adjustment of relative humidity (ECA 31 only).
ECA system: Display, communication, override settings and version info.
ECA factory: Erase of all applications in the ECA 30 / 31, restore to factory settings, reset of ECL address and firmware update.
Part of the ECA 30 / 31 display in ECA mode:
If only the "ECA MENU" is shown, it can indicate that the ECA 30 / 31 is not having correct communication address.
See ECA MENU > ECA system > ECA communication: ECL address.
In most cases the ECL address setting must be "15".
Regarding ECA settings:
When ECA 30 / 31 is not used as remote unit, the offset adjustments menu(s) are not present.
186 DEN-SMT/DK VI.GU.A2.02
Danfoss District Energy
Installation Guide ECL Comfort 210 / 310, application A214 / A314
The ECL menus are as described for the ECL controller.
Most of the settings done directly in the ECL controller can be done via the ECA 30 / 31 too.
All settings can be seen even if the application key is not inserted in the ECL controller.
For changing settings, the application key must be inserted.
The Key overview (MENU > 'Common controller settings' > 'Key functions') does not show the applications of the key.
The ECA 30 / 31 will display this information (an X on the ECA 30 / 31 symbol) if the application in the ECL controller does not comply with the ECA 30 / 31:
Danfoss District Energy
In the example 1.10 is current version and 1.42 is desired version.
Display part of ECA 30 / 31:
This display indicates that an application has not been uploaded or the communication to the ECL controller (master) is not working properly.
An X on the ECL controller symbol indicates wrong setup of communication addresses.
Display part of ECA 30 / 31:
Newer versions of ECA 30 / 31 indicate the address number of the connected ECL Comfort controller.
Address number can be changed in the ECA MENU.
A stand-alone ECL Controller has the address 15.
VI.GU.A2.02
DEN-SMT/DK 187
Installation Guide ECL Comfort 210 / 310, application A214 / A314
When ECA 30 / 31 is in ECA MENU mode, the date and measured room temperature is displayed.
ECA MENU > ECA settings > ECA sensor
Room T Offset
Setting range
–10.0 ... 10.0 K
Factory setting
0.0 K
The measured room temperature can be corrected with a number of Kelvin. The corrected value is used by the heating circuit in the ECL controller.
Minus value:
The indicated room temperature is lower.
0.0 K:
No correction of the measured room temperature.
Plus value:
The indicated room temperature is higher.
Example:
Room T offset:
Displayed room temperature:
Room T offset:
Displayed room temperature:
0.0 K
21.9 °C
1.5 K
23.4 °C
ECA MENU > ECA settings > ECA sensor
RH offset (ECA 31 only)
Setting range
–10.0 ... 10.0 %
Factory setting
0.0 %
The measured relative humidity can be corrected with a number of %-values. The corrected value is used by the application in the ECL controller.
Minus value:
The indicated relative humidity is lower.
0.0 %:
No correction of the measured relative humidity.
Plus value:
The indicated relative humidity is higher.
ECA MENU > ECA system > ECA display
Backlight (display brightness)
Setting range
0 ... 10
Adjust the brightness of the display.
0:
10:
Weak backlight.
Strong backlight.
Factory setting
5
Example:
RH offset:
Displayed relative humidity:
RH offset:
Displayed relative humidity:
0.0 %
43.4 %
3.5 %
46.9 %
188 DEN-SMT/DK VI.GU.A2.02
Danfoss District Energy
Installation Guide ECL Comfort 210 / 310, application A214 / A314
ECA MENU > ECA system > ECA display
0:
10:
Contrast (display contrast)
Setting range
0 ... 10
Adjust the contrast of the display.
Low contrast.
High contrast.
Factory setting
3
ECA MENU > ECA system > ECA display
Use as remote
Setting range
OFF / ON
Factory setting
ECA 30 / 31 can act as a simple or normal remote control for the ECL controller.
*)
OFF:
Simple remote control, no room temperature signal.
ON:
Remote control, room temperature signal is available.
*):
Differently, depending on chosen application.
When set to OFF: The ECA menu shows date and time.
When set to ON: The ECA menu shows date and room temperature
(and for ECA 31 relative humidity).
ECA MENU > ECA system > ECA communication
A:
B:
Slave addr. (Slave address)
Setting range Factory setting
A / B
The setting of 'Slave addr.' is related to the setting 'ECA address' in the ECL controller.
In the ECL controller it is selected from which ECA 30 / 31 unit the room temperature signal is received.
A
The ECA 30 / 31 has the address A.
The ECA 30 / 31 has the address B.
For installation of an application in an ECL Comfort 210 / 310 controller the 'Slave addr.' must be A.
If two ECA 30 / 31 are connected in the same ECL 485 bus system, the
'Slave addr.' must be "A" in the one ECA 30 / 31 unit and "B" in the other.
Danfoss District Energy VI.GU.A2.02
DEN-SMT/DK 189
Installation Guide ECL Comfort 210 / 310, application A214 / A314
ECA MENU > ECA system > ECA communication
Connection addr. (Connection address)
Setting range
1 … 9 / 15
Factory setting
15
Setting of the address to which ECL controller the communication must run.
1 .. 9:
Slave controllers.
15:
Master controller.
An ECA 30 / 31 can in an ECL 485 bus system (master – slave) be set to communicate, one by one, with all addressed ECL controllers.
Example:
Connection addr. = 15: The ECA 30 / 31 communicates with the
ECL master controller.
Connection addr. = 2: The ECA 30 / 31 communicates with the
ECL controller with address 2.
There must be a master controller present in order to broadcast time and date information.
An ECL Comfort controller 210 / 310, type B (without display and dial) cannot be assigned to the address 0 (zero).
ECA MENU > ECA system > ECA override
Override addr. (Override address)
Setting range
OFF / 1 … 9 / 15
Factory setting
OFF
The feature 'Override' (to extended comfort or saving period or holiday) must be addressed to the ECL controller in question.
OFF:
Override not possible.
1 .. 9:
Address of slave controller for override.
15:
Address of master controller for override.
Extended saving mode:
Extended comfort mode:
Override functions:
Holiday away from home:
Holiday at home:
Override by means of settings in ECA 30 / 31 are cancelled if the ECL
Comfort controller goes into holiday mode or is changed to another mode than scheduled mode.
The circuit in question for override in the ECL controller must be in scheduled mode.
See also the parameter 'Override circuit'.
190 DEN-SMT/DK VI.GU.A2.02
Danfoss District Energy
Installation Guide ECL Comfort 210 / 310, application A214 / A314
ECA MENU > ECA system > ECA override
Override circuit
Setting range
OFF / 1 … 4
Factory setting
OFF
The feature 'Override' (to extended comfort or saving period or holiday) must be addressed to the heating circuit in question.
OFF:
No heating circuit is selected for override.
1 … 4:
The heating circuit number in question.
The circuit in question for override in the ECL controller must be in scheduled mode.
See also the parameter 'Override addr.'.
Example 1:
(One ECL controller and one ECA 30 / 31)
Override of heating circuit 2:
Set 'Connection addr.' to
15
Set 'Override circuit' to 2
Example 2:
(Several ECL controllers and one ECA 30 / 31)
Override of heating circuit 1 in ECL controller with the address 6:
Set 'Connection addr.' to 6 Set 'Override circuit' to 1
Quick guide "ECA 30 / 31 to override mode":
1. Go to ECA MENU
2. Move cursor to "Clock" symbol
3. Select the "Clock" symbol
4. Choose and select one of 4 override functions
5. Below the override symbol: Set hours or date
6. Below hours / date: Set desired room temperature for the override period
ECA MENU > ECA system > ECA version
ECA version (read-out only), examples
Code no.
087H3200
Hardware
Software
Build no.
A
1.42
5927
Serial no.
13579
Production week
23.2012
The ECA version information is useful in service situations.
Danfoss District Energy VI.GU.A2.02
DEN-SMT/DK 191
Installation Guide ECL Comfort 210 / 310, application A214 / A314
ECA MENU > ECA factory > ECA clear apps.
Erase all apps. (Erase all applications)
Erase all applications which are in the ECA 30 / 31.
After erasing, the application can be uploaded again.
NO:
The erase procedure is not done.
YES:
The erase procedure is done (await 5 sec.).
After the erase procedure, a pop-up in the display indicates "Copy application". Choose "Yes".
Hereafter the application is uploaded from the ECL controller. An upload bar is shown.
ECA MENU > ECA factory > ECA default
Restore factory
The ECA 30 / 31 is set back to factory settings.
Affected settings by the restore procedure:
• Room T offset
• RH offset (ECA 31)
• Backlight
• Contrast
• Use as remote
• Slave addr.
• Connection addr.
• Override addr.
• Override circuit
• Override mode
• Override mode end time
NO:
YES:
The restore procedure is not done.
The restore procedure is done.
192 DEN-SMT/DK VI.GU.A2.02
Danfoss District Energy
Installation Guide ECL Comfort 210 / 310, application A214 / A314
ECA MENU > ECA factory > Reset ECL addr.
Reset ECL addr. (Reset ECL address)
If none of the connected ECL Comfort controllers has the address
15, the ECA 30 / 31 can set all connected ECL controllers on the
ECL 485 bus back to address 15.
NO:
The reset procedure is not done.
YES:
The reset procedure is done (await 10 sec.).
The ECL 485 bus related address of the ECL controller is found:
MENU > 'Common controller settings' > 'System' > 'Communication' >
'ECL 485 addr.'
The "Reset ECL addr." cannot be activated if one or more of the connected ECL Comfort controllers has the address 15.
In a system with MASTER / SLAVE controllers, only one MASTER controller with address 15 is allowed.
If by mistake more MASTER controllers are present in an ECL 485 communication bus system, decide which controller is to be MASTER.
Change the address in the remaining controllers. However, the system will operate but not be stable with more than one MASTER controller.
ECA MENU > ECA factory > Update firmware
Update firmware
The ECA 30 / 31 can be updated with new firmware (software).
The firmware comes with the ECL application key, when the key version is at least 2.xx.
If no new firmware is available, a symbol of the application key is displayed with an X.
NO:
The updating procedure is not done.
YES:
The updating procedure is done.
The ECA 30 / 31 automatically verifies if a new firmware is present on the application key in the ECL Comfort controller.
The ECA 30 / 31 is automatically updated at new application upload in the ECL Comfort controller.
The ECA 30 / 31 is not automatically updated when connected to an
ECL Comfort controller with uploaded application. A manual update is always possible.
Quick guide "ECA 30 / 31 to override mode":
1. Go to ECA MENU
2. Move cursor to "Clock" symbol
3. Select the "Clock" symbol
4. Choose and select one of 4 override functions
5. Below the override symbol: Set hours or date
6. Below hours / date: Set desired room temperature for the override period
Danfoss District Energy VI.GU.A2.02
DEN-SMT/DK 193
Installation Guide ECL Comfort 210 / 310, application A214 / A314
7.2 Several controllers in the same system
When ECL Comfort controllers are interconnected by means of the ECL 485 communication bus (cable type: 2 x twisted pair), the master controller will broadcast the following signals to the slave controllers:
• Outdoor temperature (measured by S1)
• Time and date
• DHW tank heating / charging activity
Furthermore, the master controller can receive information about:
• the desired flow temperature (demand) from slave controllers
• and (as from ECL controller version 1.48) DHW tank heating / charging activity in slave controllers
Situation 1:
SLAVE controllers: How to make use of the outdoor temperature signal sent from the MASTER controller
The slave controllers only receive information about outdoor temperature and date / time.
SLAVE controllers:
Change the factory set address from 15 to address 0.
• In , go to System > Communication > ECL 485 addr:
In a system with MASTER / SLAVE controllers, only one MASTER controller with address 15 is allowed.
If by mistake more MASTER controllers are present in an ECL 485 communication bus system, decide which controller is to be MASTER.
Change the address in the remaining controllers. However, the system will operate but not be stable with more than one MASTER controller.
In the MASTER controller, the address in ‘ECL 485 addr. (master / slave address)’, ID no. 2048, must always be 15.
ECL 485 addr. (master / slave address)
Circuit Setting range
0 ... 15
2048
Choose
0
194 DEN-SMT/DK VI.GU.A2.02
Danfoss District Energy
Installation Guide ECL Comfort 210 / 310, application A214 / A314
Situation 2:
SLAVE controller: How to react on a DHW tank heating / charging activity sent from the MASTER controller
The slave receives information about a DHW tank heating / charging activity in the master controller and can be set to close the selected heating circuit.
ECL controller versions 1.48 (as from August 2013):
The master receives information about DHW tank heating / charging activity in the master controller itself and also slaves in the system.
This status is broadcasted to all ECL controllers in the system and each heating circuit can be set to close the heating.
SLAVE controller:
Set the desired function:
• In circuit 1 / circuit 2, go to ‘Settings’ > ‘Application’ >’DHW priority’:
DHW priority (closed valve / normal operation)
Circuit Setting range
1 / 2 OFF / ON
11052
/ 12052
Choose
OFF / ON
OFF:
The flow temperature control remains unchanged during active DHW heating / charging in the master / slave system.
ON:
The valve in the heating circuit is closed during active
DHW heating / charging in the master / slave system.
Danfoss District Energy VI.GU.A2.02
DEN-SMT/DK 195
Installation Guide ECL Comfort 210 / 310, application A214 / A314
Situation 3:
SLAVE controller: How to make use of the outdoor temperature signal and send information about the desired flow temperature back to the MASTER controller
The slave controller receives information about outdoor temperature and date / time. The master controller receives information about the desired flow temperature from slave controllers with an address from 1 ... 9:
SLAVE controller:
• In , go to System > Communication > ECL 485 addr.
• Change the factory set address from 15 to an address (1 ... 9).
Each slave must be configured with its own address.
In the MASTER controller, the address in ‘ECL 485 addr. (master / slave address)’, ID no. 2048, must always be 15.
ECL 485 addr. (master / slave address)
Circuit Setting range
0 ... 15
2048
Choose
1 ... 9
Furthermore, each slave can send information about the desired flow temperature (demand) in each circuit back to the master controller.
SLAVE controller:
• In the circuit in question, go to Settings > Application > Send desired T
• Choose ON or OFF.
Send desired T
Circuit
1 / 2
Setting range
OFF / ON
11500
/ 12500
Choose
ON or OFF
OFF:
Information about the desired flow temperature is not sent to the master controller.
ON:
Information about the desired flow temperature is sent to the master controller.
196 DEN-SMT/DK VI.GU.A2.02
Danfoss District Energy
Installation Guide ECL Comfort 210 / 310, application A214 / A314
7.3 Frequently asked questions
The definitions apply to the Comfort 210 as well as ECL Comfort
310 series. Consequently, you might come across expressions that are not mentioned in your guide.
The time shown in the display is one hour off?
See ‘Time and Date’.
The time shown in the display is not correct?
The internal clock may have been reset, if there has been a power break for more than 72 hours.
Go to the 'Common controller settings' and 'Time & Date' to set the correct time.
The ECL Application Key is lost?
Switch the power off and on again to see the system type and the software generation of the controller or go to 'Common controller settings' >'Key functions' > 'Application'. The system type (e.g.
TYPE A266.1) and the system diagram is displayed.
Order a replacement from your Danfoss representative (e.g. ECL
Application Key A266).
Insert the new ECL Application Key and copy your personal settings from the controller to the new ECL Application Key, if required.
The room temperature is too low?
Make sure that the radiator thermostat does not limit the room temperature.
If you still cannot obtain the desired room temperature by adjusting the radiator thermostats, the flow temperature is too low. Increase the desired room temperature (display with desired room temperature). If this does not help, adjust the ‘Heat curve’
(‘Flow temp.’).
The room temperature is too high during saving periods?
Make sure that the min. flow temperature limitation ('Temp. min.') is not too high.
The temperature is unstable?
Check that the flow temperature sensor is correctly connected and in the right place. Adjust the control parameters ('Control par.').
If the controller has a room temperature signal, see 'Room limit'.
The controller does not operate and the control valve is closed?
Check that the flow temperature sensor is measuring the correct value, see 'Daily use' or 'Input overview'.
Check the influence from other measured temperatures.
How to make an extra comfort period in the schedule?
You can set an additional comfort period by adding new ‘Start’ and ‘Stop’ times in ‘Schedule’.
How to remove a comfort period in the schedule?
You can remove a comfort period by setting start and stop times to the same value.
How to restore your personal settings?
Please read the chapter concerning ‘Inserting the ECL Application
Key’.
How to restore the factory settings?
Please read the chapter concerning ‘Inserting the ECL Application
Key’.
Why can’t the settings be changed?
The ECL Application Key has been removed.
Danfoss District Energy VI.GU.A2.02
DEN-SMT/DK 197
Installation Guide ECL Comfort 210 / 310, application A214 / A314
Why can’t an application be selected when inserting the ECL application key into the controller?
The actual application in the ECL Comfort controller must be deleted before a new application (subtype) can be selected.
How to react on alarms?
An alarm indicates that the system is not operating satisfactorily.
Please contact your installer.
What does P and PI control mean?
P control: Proportional control.
By using a P control, the controller will change the flow temperature proportional to the difference between a desired and an actual temperature, e.g. a room temperature.
A P control will always have an offset which not will disappear over time.
PI control: Proportional and Integrating control.
A PI control does the same as a P control, but the offset will disappear over time.
A long ‘Tn’ will give a slow but stable control, and a short ‘Tn’ will result in a fast control but with a higher risk of unstability.
198 DEN-SMT/DK VI.GU.A2.02
Danfoss District Energy
Installation Guide ECL Comfort 210 / 310, application A214 / A314
7.4 Definitions
The definitions apply to the Comfort 210 as well as ECL Comfort
310 series. Consequently, you might come across expressions that are not mentioned in your guide.
Air duct temperature
Temperature measured in the air duct where the temperature is to be controlled.
Alarm function
Based on the alarm settings, the controller can activate an output.
Anti-bacteria function
For a defined period, the DHW temperature is increased in order to neutralize dangerous bacteria, e.g. Legionella.
Balance temperature
This setpoint is the basis for the flow / air duct temperature. The balance temperature can be adjusted by the room temperature, the compensation temperature and the return temperature. The balance temperature is only active if a room temperature sensor is connected.
BMS
Building Management System. A supervisory system for remote control and monitoring.
Comfort operation
Normal temperature in the system controlled by the schedule.
During heating the flow temperature in the system is higher to maintain the desired room temperature. During cooling the flow temperature in the system is lower to maintain the desired room temperature.
Comfort temperature
Temperature maintained in the circuits during comfort periods.
Normally during daytime.
Compensation temperature
A measured temperature influencing the flow temperature reference / balance temperature.
Desired flow temperature
Temperature calculated by the controller on basis of the outdoor temperature and influences from the room and / or return temperatures. This temperature is used as a reference for the control.
Desired room temperature
Temperature which is set as the desired room temperature. The temperature can only be controlled by the ECL Comfort controller if a room temperature sensor is installed.
If a sensor is not installed, the set desired room temperature however still influences the flow temperature.
In both cases the room temperature in each room is typically controlled by radiator thermostats / valves.
Desired temperature
Temperature based on a setting or a controller calculation.
Dew point temperature
Temperature at which the humidity in the air condensates.
DHW circuit
The circuit for heating the domestic hot water (DHW).
Duct temperature
Temperature measured in the air duct where the temperature is to be controlled.
Danfoss District Energy VI.GU.A2.02
DEN-SMT/DK 199
Installation Guide ECL Comfort 210 / 310, application A214 / A314
ECL Portal
A supervisory system for remote control and monitoring, locally and via Internet.
EMS
Energy Management System. A supervisory system for remote control and monitoring.
Factory settings
Settings stored on the ECL Application Key to simplify the set up of your controller the first time.
Flow temperature
Temperature measured in the water flow where the temperature is to be controlled.
Flow temperature reference
Temperature calculated by the controller on basis of the outdoor temperature and influences from the room and / or return temperatures. This temperature is used as a reference for the control.
Heat curve
A curve showing the relationship between actual outdoor temperature and desired flow temperature.
Heating circuit
The circuit for heating the room / building.
Holiday schedule
Selected days can be programmed to be in comfort, saving or frost protection mode. Besides this, a day schedule with comfort period from 07.00 to 23.00 can be selected.
Humidity, relative
This value (stated in %) refers to the indoor moisture content compared to the max. moisture content. The relative humidity is measured by the ECA 31 and is used for the calculation of the dew point temperature.
Inlet temperature
Temperature measured in the inlet air flow where the temperature is to be controlled.
Limitation temperature
Temperature that influences the desired flow / balance temperature.
Log function
The temperature history is displayed.
Master / slave
Two or more controllers are interconnected on the same bus, the master sends out e.g. time, date and outdoor temperature.
The slave receives data from master and sends e.g. desired flow temperature value.
Modulating control (0 - 10 V control)
Positioning (by means of a 0 - 10 V control signal) of the actuator for the motorized control valve in order to control the flow.
Optimization
The controller optimizes the start time of the scheduled temperature periods. Based on the outdoor temperature, the controller automatically calculates when to start in order to reach the comfort temperature at the set time. The lower the outdoor temperature, the earlier the start time.
Outdoor temperature trend
The arrow indicates the tendency, i.e. whether the temperature rises or falls.
Override mode
When ECL Comfort is in Scheduled mode, a switch or contact signal can be applied to an input in order to override to Comfort,
Saving, Frost protection or Constant temperature. As long as the switch or contact signal is applied, the override is active.
200 DEN-SMT/DK VI.GU.A2.02
Danfoss District Energy
Installation Guide ECL Comfort 210 / 310, application A214 / A314
Pt 1000 sensor
All sensors used with the ECL Comfort controller are based on the
Pt 1000 type (IEC 751B). The resistance is 1000 ohm at 0 °C and it changes with 3.9 ohm / degree.
Pump control
One circulation pump is working and the other is the spare circulation pump. After a set time, the roles are exchanged.
Refill water function
If the measured pressure in the heating system is too low (e.g.
due to a leakage), water can be supplemented.
Return temperature
The temperature measured in the return influences the desired flow temperature.
Room temperature
Temperature measured by the room temperature sensor or the Remote Control Unit. The room temperature can only be controlled directly if a sensor is installed. The room temperature influences the desired flow temperature.
Room temperature sensor
Temperature sensor placed in the room (reference room, typically the living room) where the temperature is to be controlled.
Saving temperature
Temperature maintained in the heating / DHW circuit during saving temperature periods. Typically, the Saving temperature is lower than the Comfort temperature in order to save energy.
SCADA
Supervisory Control And Data Acquisition. A supervisory system for remote control and monitoring.
Schedule
Schedule for periods with comfort and saving temperatures. The schedule can be made individually for each week day and may consist of up to 3 comfort periods per day.
Weather compensation
Flow temperature control based on the outdoor temperature.
The control is related to a user-defined heat curve.
2-point control
ON / OFF control, e.g. circulation pump, ON / OFF valve, change-over valve or damper control.
3-point control
Opening, closing or no action of the actuator for the motorized control valve. No action means that the actuator remains in its current position.
Danfoss District Energy VI.GU.A2.02
DEN-SMT/DK 201
Installation Guide ECL Comfort 210 / 310, application A214 / A314
7.5 Type (ID 6001), overview
Address
Type
Scan time
ID / Serial
Reserved
Flow temp. [0.01 °C]
Return temp. [0.01 °C]
Flow [0.1 l/h]
Power [0.1 kW]
Acc. Volume
Acc. Energy
Tariff1 Acc. Energy
Tariff2 Acc. Energy
Up time [days]
Current time [M-bus defined structure]
Error status [heat meter defined bitmask]
Acc. Volume
Acc. Energy
Acc. Volume2
Acc. Energy2
Acc. Volume3
Acc. Energy3
Acc. Volume4
Acc. Energy4
Type 0
✔
✔
✔
✔
✔
✔
✔
✔
✔
[0.1 m3]
[0.1 kWh]
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
Type 1
✔
✔
✔
✔
✔
✔
✔
✔
✔
[0.1 m3]
[0.1 MWh]
-
-
-
-
✔
-
-
-
-
-
-
-
-
Type 3
✔
✔
✔
✔
✔
✔
✔
✔
✔
[0.1 m3]
[0.1 MWh]
[0.1 MWh]
[0.1 MWh]
✔
✔
✔
-
-
-
-
-
-
-
-
Type 2
✔
✔
✔
✔
✔
✔
✔
✔
✔
[0.1 m3]
[0.1 kWh]
[0.1 kWh]
[0.1 kWh]
✔
✔
-
-
-
✔
Type 4
-
-
-
-
-
✔
✔
✔
✔
✔
-
-
[0.1 m3]
[0.1 kWh]
[0.1 m3]
[0.1 kWh]
[0.1 m3]
[0.1 kWh]
[0.1 m3]
[0.1 kWh]
202 DEN-SMT/DK VI.GU.A2.02
Danfoss District Energy
Installation Guide ECL Comfort 210 / 310, application A214 / A314
ID Parameter Name
10304 S4 filter
10643
Digital S9
10656 Alarm value
10657
Alarm time-out
10683 Digital S10
10696
Alarm value
10697 Alarm time-out
11008
Desired balance T
-||-
11009 Dead zone
11010
ECA addr.
11015 Adapt. time
11018
Des. T comfort
11019 Des. T saving
11021
Total stop
-||-
11027 Room T diff.
-||-
11030
Limit
-||-
-||-
11035 Infl. - max.
-||-
11036
Infl. - min.
11037
Adapt. time
-||-
11038
Stop at T out
11060 Limit
11061 Adapt. time
11062
Infl. - max.
11063
Infl. - min.
11064 Limit
11065 Adapt. time
11066
Infl. - max.
11067
Infl. - min.
11077 P frost T
-||-
7.6 Parameter ID overview
A214.x or A314.x — x refers to the subtypes listed in the column.
A214.x
2, 4
1
2, 3, 4, 5, 6
A314.x
1
4, 5, 6, 7, 9
4, 5, 6, 7, 9
4, 5, 6, 7, 9
4, 5, 6, 7, 9
4, 5, 6, 7, 9
4, 5, 6, 7, 9
1, 2, 3
Setting range
1 ... 100
OFF ; ON
0 ... 1
0 ... 250
OFF ; ON
0 ... 1
0 ... 250
-20 ... 110
5 ... 110
4, 5
1, 3, 5, 6
1, 2, 6, 7
2, 3, 4, 5, 6, 7, 9
OFF, 0.5 ... 25.0
OFF ; A ; B
1, 2, 3, 4, 5, 6 1, 2, 3, 4, 5, 6, 7, 9 OFF, 1 ... 50
4, 5, 6, 7, 9 5 ... 110
4, 5, 6, 7, 9
1, 2, 3, 4, 5, 6 1, 2, 4, 5, 6, 7, 9
5 ... 110
OFF ; ON
3
3 3
6
1
2, 3, 4, 5, 6 1, 2, 3
OFF ; ON
-9.0 ... -0.5
-9.0 ... -0.5, OFF
-10 ... 110
10 ... 110
4, 5, 6, 7, 9
1, 2, 3, 4, 5, 6 1, 2, 3
4, 5, 6, 7, 9
10 ... 110
-9.9 ... 9.9
-9.9 ... 9.9
1, 2, 3, 4, 5, 6 1, 2, 3, 4, 5, 6, 7, 9 -9.9 ... 9.9
1, 2, 3, 4, 5, 6 1, 2, 3
4, 5, 6, 7, 9
OFF, 1 ... 50
OFF, 1 ... 50
4, 5, 6, 7, 9
OFF, 5 ... 40
1, 2, 3, 4, 5, 6 1, 2, 3, 4, 5, 6, 7, 9 -20 ... 80
1, 2, 3, 4, 5, 6 1, 2, 3, 4, 5, 6, 7, 9 OFF, 1 ... 50
1, 2, 3, 4, 5, 6 1, 2, 3, 4, 5, 6, 7, 9 -9.9 ... 9.9
1, 2, 3, 4, 5, 6 1, 2, 3, 4, 5, 6, 7, 9 -9.9 ... 9.9
1, 2, 3, 4, 5, 6 1, 2, 3, 4, 5, 6, 7, 9 -20 ... 80
1, 2, 3, 4, 5, 6 1, 2, 3, 4, 5, 6, 7, 9 OFF, 1 ... 50
1, 2, 3, 4, 5, 6 1, 2, 3, 4, 5, 6, 7, 9 -9.9 ... 9.9
1, 2, 3, 4, 5, 6 1, 2, 3, 4, 5, 6, 7, 9 -9.9 ... 9.9
2, 3, 4, 5, 6 1, 2, 3
4, 5, 6, 7, 9
OFF, -10 ... 20
OFF, -10 ... 20
0.0
2
6
OFF
0.0
0.0
25
OFF
0.0
35
0.0
-3.0
0.0
25
OFF
OFF
5
OFF
0
0
20
20
5.0
Factory
8
OFF
0
0
ON
-2.0
OFF
10
25
OFF
OFF
20
16
OFF
Unit
Sec
Sec
°C
°C
K
K
K
°C
°C
°C
Sec
°C
°C
Sec
Sec
°C
°C
Sec
°C
Sec
°C
°C
Own settings
Danfoss District Energy VI.GU.A2.02
DEN-SMT/DK 203
Installation Guide ECL Comfort 210 / 310, application A214 / A314
ID Parameter Name
11081
Filter constant
11082 Accum. filter
11086
Fan cut-in delay
-||-
-||-
-||-
-||-
-||-
11087
Acc. cut-in delay
11088
Fan output func.
-||-
11089
Acc. output func.
11090 Optional function
-||-
-||-
-||-
11091
Acc. time control
-||-
11093 Frost pr. T
-||-
11105
Infl. - min.
-||-
11107 Adapt. time
11108
Limit T frost
-||-
11137
Fan function
-||-
11140 Comp. T select
11141 Ext. input
-||-
11142
-||-
Ext. mode
11147
Upper difference
11148
Lower difference
11149 Delay
11150 Lowest temp.
A214.x
4, 5
1
2, 3, 4, 5
6
A314.x
3
1, 2, 6, 7
1, 2
3
4, 5, 6, 7
Setting range
1 ... 80
1 ... 250
0 ... 900
0 ... 900
0 ... 900
0 ... 900
0 ... 900
9 0 ... 900
1, 2, 3, 4, 5, 6 1, 2, 3, 4, 5, 6, 7, 9 0 ... 900
1, 2, 3, 4, 5 1, 2, 3, 4, 5, 6, 7, 9 0 ... 3
6 0 ... 3
1, 2, 3, 4, 5, 6 1, 2, 3, 4, 5, 6, 7, 9 0 ... 3
1, 3
2
3 0 ... 3
0 ... 2
4, 5
6
1, 2
1, 2, 3, 4, 5, 6 1, 2, 3
4, 5, 6, 7, 9
2, 4 1
4, 5, 6, 7, 9
0 ... 4
0 ... 3
1 ... 2
1 ... 3
0 ... 40
5 ... 40
2, 3, 4, 5
6
2, 3, 4, 5, 6
2, 3, 4, 5, 6
1, 2, 3, 4, 5, 6, 7, 9 0.0 ... 9.9
0.0 ... 9.9
1, 2, 3, 4, 5, 6, 7, 9 OFF, 1 ... 50
1, 2, 3 0 ... 50
2, 3, 4, 5, 6
4, 5, 6, 7, 9
1, 2
0 ... 50
OFF ; ON
3, 4, 5, 6, 7, 9 OFF ; ON
1, 2, 3, 4, 5, 6 1, 2, 3
1, 2, 3, 4, 5, 6 3
OFF ; ON
OFF ; S1 ; S2 ; S3 ;
S4 ; S5 ; S6 ; S7 ; S8
1, 2
OFF ; S1 ; S2 ; S3 ;
S4 ; S5 ; S6 ; S7 ; S8
; S9 ; S10
4, 5, 6, 7, 9 OFF ; S1 ; S2 ; S3
; S4 ; S5 ; S6 ; S7 ;
S8 ; S9 ; S10 ; S11
; S12 ; S13 ; S14 ;
S15 ; S16
1, 2, 3, 4, 5, 6 1, 2, 3, 4, 5, 6, 7, 9
COMFORT ;
SAVING
2, 3, 4, 5, 6 1, 2, 3, 4, 5, 6, 7, 9
OFF, 1 ... 30
2, 3, 4, 5, 6 1, 2, 3, 4, 5, 6, 7, 9 OFF, 1 ... 30
2, 3, 4, 5, 6
2, 3, 4, 5, 6
1, 2, 3, 4, 5, 6, 7, 9 1 ... 99
1, 2, 3, 4, 5, 6, 7, 9 10 ... 50
OFF
OFF
COMFORT
OFF
OFF
10
30
1
1
0
3
6
10
3
1
0
0
30
0
10
60
20
0
1
Factory
50
25
5
12
OFF
ON
ON
OFF
2.0
0.0
OFF
10
Unit
°C
°C
Sec
°C
°C
K
K
Min
°C
Sec
Sec
Sec
Sec
Sec
Sec
Sec
Sec
Own settings
204 DEN-SMT/DK VI.GU.A2.02
Danfoss District Energy
Installation Guide ECL Comfort 210 / 310, application A214 / A314
ID Parameter Name
11168 Max. Pressure
11169 Min. Pressure
11174 Motor pr.
11177
Temp. min.
-||-
-||-
11178 Temp. max.
-||-
-||-
11179 Summer, cut-out
11182
Infl. - max.
-||-
11183
Infl. - min.
-||-
11184
Xp
11185
Tn
-||-
11186 M run
-||-
11187 Nz
-||-
-||-
11189 Min. act. time
11194
Stop difference
-||-
11301 High T max Y2
11303 Low T max Y1
11368
1. step level
11369
2. step level
11500
Send desired T
11609 Low Y
11610 High Y
11616
Alarm value
-||-
11617
Alarm time-out
-||-
11623
Digital
11636
Alarm value
-||-
11637
Alarm time-out
-||-
A214.x
2, 3, 4, 5, 6
A314.x
4, 6
Setting range
0 ... 1999
4, 6 0 ... 1999
1, 2, 3, 4, 5, 6 1, 2, 3, 4, 5, 6, 7, 9 OFF, 10 ... 59
1 -20 ... 110
1, 2, 3
4, 5, 6, 7, 9
5 ... 150
5 ... 150
1
2, 3, 4, 5, 6 1, 2, 3
4, 5, 6, 7, 9
-20 ... 110
5 ... 150
5 ... 150
4, 5
1, 2, 3, 4, 5, 6 1, 2, 3, 4, 5, 6, 7
9
OFF, 1 ... 50
-30.0 ... 0.0
-30.0 ... 0.0
1, 2, 3, 4, 5, 6 1, 2, 3, 4, 5, 6, 7
9
0.0 ... 30.0
0.0 ... 30.0
1, 2, 3, 4, 5, 6 1, 2, 3, 4, 5, 6, 7, 9 5 ... 250
1, 2, 3, 4, 5, 6 1, 2, 3, 5, 6, 7, 9 1 ... 999
4
1 ... 999
1, 2, 3, 4, 5, 6 1, 2, 3, 5, 6, 7, 9
4
1, 2, 3, 4, 5, 6 1, 2, 3
4
5, 6, 7, 9
5 ... 250
5 ... 250
1 ... 9
0 ... 9
0 ... 9
1, 2, 3, 4, 5, 6 1, 2, 3, 4, 5, 6, 7, 9 2 ... 50
6 0.5 ... 9.0
4, 5, 6, 7
1 ... 15
3
3
4, 5, 6, 7
4, 5, 6, 7
1, 2, 3, 4, 5, 6 1, 2, 3
0.0 ... 75.0
0.0 ... 75.0
5 ... 95
5 ... 95
2, 3, 4, 5, 6
3
3
1, 2, 3
OFF ; ON
0.0 ... 10.0
0.0 ... 10.0
0 ... 1
2, 3, 4, 5, 6
4, 5, 6, 7, 9
1, 2, 3
4, 5, 6, 7, 9
1, 2, 3, 4, 5, 6 1, 2
0 ... 1
0 ... 240
0 ... 240
1, 2, 3, 4, 5, 6
1, 2, 3, 4, 5, 6
1, 2, 3
4, 5, 6, 7, 9
1, 2, 3
4, 5, 6, 7, 9
OFF ; ON
0 ... 1
0 ... 1
0 ... 240
0 ... 240
3
1.0
3
25.0
5.0
80
85
1
0
10
ON
2.0
10.0
0
3
1
30
35
2
2.0
0.0
80
30
100
40
40
35
OFF
-2.0
0.0
OFF
0
1
0
10
Factory
400
50
OFF
5
10
15
V
V
K
K m/s m/s
%
%
K
Sec
Sec
K
K
Sec
Sec
K
Sec
Sec
Sec
Sec
°C
°C
°C
°C
°C
°C
°C
Unit
pascal pascal
Min
Own settings
Danfoss District Energy VI.GU.A2.02
DEN-SMT/DK 205
Installation Guide ECL Comfort 210 / 310, application A214 / A314
12165 V out max.
12167 V out min.
-||-
12168 Max. Pressure
12169 Min. Pressure
12171 Reverse out
12174 Motor pr.
12184 Xp
-||-
-||-
12185 Tn
-||-
-||-
12186
M run
12187 Nz
-||-
-||-
12189 Min. act. time
12368 1. step level
12369
2. step level
12390 Clear alarm
12615
Alarm low
12617 Alarm time-out
13111 Limit
-||-
13113
Filter constant
-||-
13165 V out max.
13167 V out min.
-||-
13184 Xp
-||-
13185 Tn
ID Parameter Name
11656
Alarm value
-||-
11676 Alarm value
-||-
12140
Comp. T select
6
1
A214.x
2, 3, 4, 5
2, 3, 4, 5, 6
4, 5
4, 5
4, 5
4, 5
4, 5
4, 5
9
9
4, 5, 6, 7, 9
4, 5, 6, 7
4, 5, 6, 7
5, 7
9
4
5, 6, 7, 9
4, 5, 6, 7, 9
4, 5, 6, 7
9
4, 5, 6, 7
9
4, 5, 6, 7, 9
4, 6
4, 6
1, 2
1, 2
1, 2, 5, 6, 7
4
9
1, 2, 5, 6, 7
4
9
A314.x
Setting range
1, 2, 3, 4, 5, 6, 7, 9 -20 ... 20
-20 ... 20
-20 ... 20
1, 2, 3, 4, 5, 6, 7, 9 -20 ... 20
4, 5, 6, 7, 9
1, 2, 4, 5, 6, 7, 9
1, 2, 4, 5, 6, 7
9
S1 ; S2 ; S3 ; S4 ;
S5 ; S6 ; S7 ; S8 ;
S9 ; S10 ; S11 ; S12
; S13 ; S14 ; S15 ;
S16
0 ... 100
0 ... 100
0 ... 100
0 ... 1999
0 ... 1999
OFF ; ON
OFF, 10 ... 59
5 ... 250
5 ... 250
5 ... 250
1 ... 999
1 ... 999
1 ... 999
5 ... 250
1, 2
4, 5, 6, 7
9
0 ... 99
0 ... 1999
0 ... 1999
1 ... 250
1 ... 250
0 ... 100
0 ... 100
0 ... 90
5 ... 250
5 ... 250
1 ... 999
1 ... 9
1 ... 9
1 ... 9
2 ... 50
5 ... 95
5 ... 95
OFF ; ON
0 ... 100
Factory
6
-20
2
-20
S1
60
30
90
ON
OFF
80
100
100
0
20
400
50
3
1
20
30
80
60
30
30
900
500
40
20
100
0
30
2
3
80
85
OFF
40
Unit
°C
°C
°C
°C
%
%
%
%
%
Sec
Sec
Sec
K
K
K
Min
K
K
K
Sec
%
%
% pascal pascal
%
Min ppm ppm
Sec
Own settings
206 DEN-SMT/DK VI.GU.A2.02
Danfoss District Energy
ID Parameter Name
13187 Nz
-||-
-||-
-||-
13356 Outlet fan, offset
-||-
13357
Fan speed, red.
-||-
13390
Clear alarm
13406
X1
-||-
13407 X2
13609 Low Y
13610 High Y
-||-
13614
Alarm high
13615 Alarm low
13617
Alarm time-out
14113 Filter constant
14165 V out max.
14167
V out min.
14184 Xp
14185 Tn
14187 Nz
14390
Clear alarm
14406 X1
-||-
14407
X2
14609
Low Y
14610
High Y
-||-
14614
Alarm high
14615
Alarm low
14617
Alarm time-out
15184 Xp
15185 Tn
15186 M run
15187 Nz
15189
Min. act. time
A214.x
Installation Guide ECL Comfort 210 / 310, application A214 / A314
A314.x
4
5, 7
6
9
5, 7
9
4
5, 9
4, 6
4, 5, 7, 9
6
4, 5, 6, 7, 9
4, 5, 6, 7, 9
4, 5, 7, 9
6
4, 5, 6, 7, 9
4, 5, 6, 7, 9
4, 5, 6, 7, 9
4, 6
4, 6
4, 6
4, 6
4, 6
4
6
4, 6
4, 6
4, 6
4
6
4, 6
4, 6
4, 6
4, 6
6, 7
6, 7
6, 7
6, 7
6, 7
1.0
OFF
0.0
2.0
10.0
0
1000
200
2000
0
3
20
100
0
80
30
0
3
80
30
30
3
10
OFF
OFF
OFF
0.0
2.0
10.0
0
1000
200
2000
Factory
2.0
20.0
1.0
10.0
0
10
Setting range
0.2 ... 20.0
1.0 ... 50.0
0.2 ... 20.0
1.0 ... 50.0
-50 ... 50
-50 ... 50
0 ... 2000
0 ... 30
1 ... 250
0 ... 100
0 ... 100
5 ... 250
1 ... 999
0.2 ... 20.0
OFF ; ON
0.0 ... 10.0
0.0 ... 10.0
0.0 ... 10.0
0 ... 1999
0 ... 1999
0 ... 1999
0 ... 2000
0 ... 2000
0 ... 30
5 ... 250
1 ... 999
5 ... 250
1 ... 9
2 ... 50
OFF, 1 ... 1999
OFF, 1 ... 100
OFF ; ON
0.0 ... 10.0
0.0 ... 10.0
0.0 ... 10.0
0 ... 1999
0 ... 1999
0 ... 1999
0 ... 2000
%
%
V
V
V pascal pascal pascal pascal pascal
Min
Sec pascal
V
V
V pascal pascal pascal pascal pascal
Min
K
Sec
Sec
K
Unit
pascal ppm pascal ppm
%
% pascal
%
Own settings
Danfoss District Energy VI.GU.A2.02
DEN-SMT/DK 207
Installation Guide ECL Comfort 210 / 310, application A214 / A314
Installer:
By:
Date:
208 DEN-SMT/DK VI.GU.A2.02
Danfoss District Energy
Installation Guide ECL Comfort 210 / 310, application A214 / A314
*087H9058*
*VIGUA202*
Produced by Danfoss A/S © 01/2015
advertisement
Key Features
- Installation and Setup
- Heating and Cooling Control
- Room Temperature Control
- Duct Temperature Control
- Air Pressure Control
- Modular Design
- Remote Control Options
- Extensive Documentation