Below you will find brief information for Universal Relay TR 800 Web. The Universal Relay TR 800 Web is a web-enabled device that monitors and logs signals from up to 8 inputs. It can be connected to the internet or an intranet and operated via TCP/IP from a normal PC with a suitable browser. You can configure up to 8 limits for each of the 4 output relays, and the device includes an integrated webserver for configuration, readout of measured data, user-management email-alarms, data- and alarm-logging, and ftp-upload.

advertisement

Assistant Bot

Need help? Our chatbot has already read the manual and is ready to assist you. Feel free to ask any questions about the device, but providing details will make the conversation more productive.

Universal Relay TR 800 Web Operating Instructions | Manualzz

MINIPAN

®

digital panel meters, temperature- and mains controlling, special purpose instruments for customer requirements www.ziehl.com

Operating Instructions

- Archive document -

Universal-Relay TR 800 Web

www.ziehl.de

Software version 1.1.9

(Date / Name): 20.04.2011 Fu/Su Drawing no.: 12280-0701-05

Page 1 of 28 Name: TR 800 WEB

ZIEHL industrie-elektronik GmbH + Co KG, Daimlerstr.13, D-74523 Schwäbisch Hall, Tel.: +49 791 504-0, Fax: -56, email: [email protected]

Table of contents

1.

Application and short description ........................................................................... 3

2.

Overview of functions ............................................................................................... 3

3.

Connection Plan ........................................................................................................ 3

4.

Display and controls ................................................................................................. 4

5.

Important Information’s ............................................................................................ 5

6.

Installation ................................................................................................................. 6

7.

Detailed description .................................................................................................. 6

8.

Start-up operation (commissioning) ........................................................................ 7

8.1

General instructions on operating ........................................................................... 7

8.2

Display mode .......................................................................................................... 7

8.3

Menu mode ............................................................................................................. 7

8.4

Info mode ................................................................................................................ 7

8.5

Short operating diagram .......................................................................................... 8

8.6

Overview of commissioning..................................................................................... 9

8.7

Switching on the unit ............................................................................................... 9

8.8

Connection to network and controls ........................................................................ 9

8.9

Find the unit in the network ................................................................................... 10

8.9.1

DHCP server ..................................................................................................... 10

8.9.2

Default IP- Adress 10.10.10.10 ......................................................................... 10

8.9.3

Bonjour ............................................................................................................. 11

8.9.4

UPnP ................................................................................................................ 11

8.9.5

Information about the login window ................................................................... 11

8.10

Make the basic network settings ........................................................................... 12

8.11

Sensor settings ..................................................................................................... 13

8.12

Configuring the alarms .......................................................................................... 14

8.13

Alarm email ........................................................................................................... 15

8.14

System .................................................................................................................. 16

8.15

User management/access control ......................................................................... 17

8.16

Logging and FTP Upload ...................................................................................... 18

8.17

View measurements and alarms, sensor simulation ............................................. 20

8.18

Time-dependent control / Scheduler ..................................................................... 22

9.

Ethernet protocols .................................................................................................. 23

9.1

UDP ...................................................................................................................... 23

9.2

Modbus TCP ......................................................................................................... 23

9.3

SNMP .................................................................................................................... 23

9.4

FTP Upload (Option) ............................................................................................. 23

9.5

AJAX data interface .............................................................................................. 23

10.

RS485 interface ....................................................................................................... 23

10.1

Ziehl Standard Protocol ......................................................................................... 23

10.2

Modbus RTU ......................................................................................................... 23

11.

Maintenance and Repair ......................................................................................... 23

12.

Troubleshooting ...................................................................................................... 24

13.

Technical Data ......................................................................................................... 25

14.

Housing design V8 .................................................................................................. 28

(Date / Name): 20.04.2011 Fu/Su Drawing no.: 12280-0701-05

Page 2 of 28 Name: TR 800 WEB

ZIEHL industrie-elektronik GmbH + Co KG, Daimlerstr.13, D-74523 Schwäbisch Hall, Tel.: +49 791 504-0, Fax: -56, email: [email protected]

1. Application and short description

Web-IO Universal Relay with Ethernet-interface and 8 inputs for temperature-sensors and other analogue signals.

The TR 800 Web can be connected to the internet or an intranet and operated via TCP/IP from a normal PC with a suitable browser (tested with IE 7, IE 8 and Firefox 3). No special software and no special instruction is required.

The Universal Relays TR 800 monitors and logs signals from up to 8 inputs.

Up to 8 limits (one per input) can be programmed for each of the 4 output-relays.

2. Overview of functions

8 measuring inputs: o

Pt 100, Pt 1000 in 2- or 3-wire connection o

KTY 83 or KTY 84 o

Thermocouples type B, E, J, K, L, N, R, S, T o

DC 0-10 V, DC 0/4-20 mA o

Resistance 500 Ohm, resistance 30 kOhm

4 relay-outputs (each potential-free change-over contact)

Ethernet interface (http, https, UDP, Modbus, Bonjour, UpNP, SNMP, AJAX)

RS485 interface (Standard Ziehl- and Modbus RTU- protocol)

Universal power-supply AC/DC 24-240 V

Integrated webserver for configuration, readout of measured data, user-management email-alarms, data- and alarm-logging and ftp-upload

Time-dependent control (day/night)

Real-time clock with synchronisation with timeserver

3. Connection Plan

1) Terminating resistor active: Bridge A to A’ and B to B’

(Date / Name): 20.04.2011 Fu/Su Drawing no.: 12280-0701-05

Page 3 of 28 Name: TR 800 WEB

ZIEHL industrie-elektronik GmbH + Co KG, Daimlerstr.13, D-74523 Schwäbisch Hall, Tel.: +49 791 504-0, Fax: -56, email: [email protected]

4. Display and controls

1, 2 LEDs (yellow) RS485 interface

Rx flashes briefly: Unit is receiving data via the RS485 interface

Tx flashes briefly: Unit is transmitting data via the RS485 interface

Rx and Tx flash/illuminate during firmware update

3 LED (red) Sensor error

Illuminated: Fault in a sensor circuit

4 LEDs (red) alarm

Illuminated:

Flashes briefly (1:4):

Alarm (1-4) has occurred

Response delay is running

Flashes long (4:1): Backshift delay is running

Flashes uniformly (1:1): Ready for reset, reset with key

Press "SET/RESET" ≥ 2s or ext. Reset Y1/Y2

5 LED (yellow) Night

Illuminated: Limits for "Night" (can be set via browser) are active

6 LEDs (yellow) sensors

Illuminated: Displays the sensor value belonging to the LED in the digital display

Flashes: Sensor error in the corresponding sensor circuit

7 LEDs (yellow) relay state

Illuminated: The relay belonging to the LED is picked up

Off: The relay belonging to the LED is released

8 Digital display (4 digits)

Display of sensor value

Display of error codes

Display of menu and configuration mode

9,10 Up button / Down button

Change into the menu mode (see Operating instructions Point 8.3)

11 Set/Reset button

Press briefly:

Press for 10 s:

Displays the next sensor (sensor LED illuminates)

Displays the software version (e.g.

0-00)

12 LED (yellow) Displays Ethernet transmission speed

Off: 10 Mbps On: 100 Mbps

13 LED (green) Displays Ethernet data traffic

Flashes during active data transmission

14 IP address slide switch

Towards Ethernet jack:

Towards reset button:

IP address 10.10.10.10

IP address User (set via web browser)

15 Webserver reset button

Internal webserver restarts when pressed (duration ca. 1 minute)

(Date / Name): 20.04.2011 Fu/Su Drawing no.: 12280-0701-05

Page 4 of 28 Name: TR 800 WEB

ZIEHL industrie-elektronik GmbH + Co KG, Daimlerstr.13, D-74523 Schwäbisch Hall, Tel.: +49 791 504-0, Fax: -56, email: [email protected]

5. Important

Information’s

To use the equipment flawless and safe, transport and store properly, install and start professionally and operate as directed.

Only let persons work with the equipment who are familiar with installation, start and use and who have appropriate qualification corresponding to their function. They must observe the contents of the instructions manual, the information which are written on the equipment and the relevant security instructions for the setting up and the use of electrical units.

The equipments are built according to DIN / EN and checked and leave the plant according to security in perfect condition. To keep this condition, observe the security instructions with the headline „Attention“ written in the instructions manual. Ignoring of the security instructions may lead to death, physical injury or damage of the equipment itself and of other apparatus and equipment.

If, in any case the information in the instructions manual is not sufficient, please contact our company or the responsible representative.

Instead of the industrial norms and regulations written in this instructions manual valid for

Europe, you must observe out of their geographical scope the valid and relevant regulations of the corresponding country.

DANGER!

Hazardous voltage!

Will cause death or serious injury. Turn off and lock out all power supplying this device before working on this device.

Observe the maximum temperature permissible when installing in switching cabinet.

Make sure sufficient space to other equipment or heat sources. If the cooling becomes more difficult e.g. through close proximity of apparatus with elevated surface temperature or hindrance of the cooling air, the tolerable environmental temperature is diminishing.

!

ATTENTION! Connection of sensors

The inputs 1T1, 1T2, 1T3 to 8T3 and RESET Y1, Y2 are not potentially separated from output RS485. Temperature-sensors must have a sufficient insulation.

Only signals according to SELV (Safety Extra Low Voltage) may be connected.

The pluggable terminals of the measuring inputs have a special contact-material and may only be used for the connection of the sensors.

Attention! Universal power supply

The unit is equipped with a universal power supply, which is suitable for DC- and ACvoltages. Before connecting the unit to the current, make sure that the allowed scope of voltage of the control voltage Us, written on the lateral type plate, corresponds to the supply voltage of the unit.

(Date / Name): 20.04.2011 Fu/Su Drawing no.: 12280-0701-05

Page 5 of 28 Name: TR 800 WEB

ZIEHL industrie-elektronik GmbH + Co KG, Daimlerstr.13, D-74523 Schwäbisch Hall, Tel.: +49 791 504-0, Fax: -56, email: [email protected]

!

ATTENTION! When all relays are programmed in operation current mode (= pick up at alarm), a loss of the supply voltage or an instrument failure can remain unidentified.

When the relay is applied as control instrument, the operator must ensure, that this error is recognized by regular examinations.

We recommend to program and accordingly evaluate at least one relay

in the closed-circuit current mode.

6. Installation

The unit can be installed as follows:

Installation in switchgear cabinet on 35 mm mounting rail according to EN 60715

With screws M4 for installation on walls or panel. (additional latch not included in delivery)

Connection according to connection plan or type plate.

!

A circuit-breaker or switch must be situated within easy reach of the unit and fused. Installation excess current protection should be

≤ 10 A.

7. Detailed description

The TR 800 Web measures up to 8 connected sensors, displays the measured values and evaluates them.

Configuration and operation are performed with a computer through a web browser

A setting can be made for each sensor o Assignment limit <-> Alarm (as desired) o Alarm active / inactive o Limit for alarm on o Limit for alarm off

For Relays K1 .. K4 (Alarm 1 .. Alarm 4) can be set individually o Response delay and switch-back delay o Relay on/off during alarm (operating or closed-circuit current) o Alarm during error (message about sensor errors and device errors) o Alarm locked,

(To reset, press "SET" ≥ 2s or ext. reset Y1/Y2

Ethernet interface for o http and https (under http, port can be set and switched off) o UDP protocol to read out data (port adjustable) o Modbus protocol to read data

RS485 interface for o standard Ziehl protocol to read data o Modbus RTU protocol to read data

Via the web browser, the following functions are available o Display measurement, min and max values with date/timestamp o Sensor simulation for simulating individual sensors o Alarm status display o Sensor configuration (name, type, compensation, scale and unit) o Alarm configuration (limits, operating/no-load current, alarm during error, alarm locked, response /switch-back delay and email) o Time-controlled day/night limits switchover o Data logging, alarm logging and parameter logging with date/timestamp

(Date / Name): 20.04.2011 Fu/Su Drawing no.: 12280-0701-05

Page 6 of 28 Name: TR 800 WEB

ZIEHL industrie-elektronik GmbH + Co KG, Daimlerstr.13, D-74523 Schwäbisch Hall, Tel.: +49 791 504-0, Fax: -56, email: [email protected]

o Network configuration o System settings o User management

8. Start-up operation (commissioning)

8.1 General instructions on operating

One can identify the device operating mode with the decimal point behind the last 7-segment display.

8.2 Display mode

Decimal point off (normal state for measurement display)

Displays the current sensor value (related yellow sensor LED illuminated, change to next sensor by pressing Set -> button)

LED yellow

RS485 Rx / Tx

LED yellow

Day / Night

LED yellow

Relay K1 .. K4

Flashes during data communication via RS485 interface

LED red

Alarm 1 .. 4

LED yellow

Sensor 1 .. 8

LED red

Sensor error

ON = Limits for "Night" are active

OFF = Limits for "Day" are active

ON = Relay operating

OFF = Relay is released

Flashes 1:4 = Response delay is active

Flashes 4:1 = switch-back delay is active

Flashes 1:1 = Ready for switch back, reset with press

"SET/RESET" button

≥ 2s or close ext. Reset Y1/Y2

On = Alarm on

OFF = Alarm off

ON = Measurement of selected sensors in the display.

Flashes = Error in sensor circuit

On = Fault in a sensor circuit

(Defective, yellow sensor LED flashes)

Function key

Set/Reset

Press briefly: Displays the next sensor (sensor LED illuminates)

Press for 10 s: displays the software version

Function keys

Up and Down

Press briefly: Change into the menus mode

8.3 Menu mode

Decimal point on

Select the menu items to view the parameters

Function keys

Up and Down

Press briefly: Select menu item; change into the display mode

Function keys

Set/Reset

Press briefly: Change into the configuration mode

8.4 Info mode

Decimal point flashes

Function keys

Up and Down

Not in use

Function keys

Set/Reset

Select next parameter; after the last parameter change into menu mode

(Date / Name): 20.04.2011 Fu/Su Drawing no.: 12280-0701-05

Page 7 of 28 Name: TR 800 WEB

ZIEHL industrie-elektronik GmbH + Co KG, Daimlerstr.13, D-74523 Schwäbisch Hall, Tel.: +49 791 504-0, Fax: -56, email: [email protected]

8.5 Short operating diagram

Display mode

normal operation

= Up

>2s

= Set

= Reset

...

Sensor

1

Sensor

2

Sensor

3

Sensor

4..8

...

Info mode

= Down

Sensor

typ

IP

AL 1

S 1

100

1000

83

84

th..

0-10

0-20

4-20

R500

R30.0

diff

IP-

,192

168

´ 1

_ 95

Dhcp

Off / on / fail

S 2

100

1000

83

84

th..

0-10

0-20

4-20

R500

R30.0

diff

Thermocouples (th..) thb = Typ B thk = Typ K thn = Typ E thj = Typ J thl = Typ L thn = Typ N

S 3 – S 8

Sensors assigned to an alarm are lighting (yellow)

Sensors having caused an alarm are blinking (yellow)

AL 2

AL 3

AL 4

8 typ type of sensor

8 S 1 8

8 S 8 8

sensors 1 to 8

8

8 diff

IP

8

8

difference

IP- address thr = Typ R ths = Typ S tht = Typ T error messages:

Er 1

= sensor shortcircuit

Er 2

= sensor break

Er 4

= thermocouple poled wrong

Er 5

= no contact to web-module

Er 8

= error in unit

Er 9

= error in parameters

8 nc 8

not connected

8 100 8

type Pt 100

8 1000 8

type Pt 1000

8 83 8

KTY 83

8 84 8

KTY 84

8 IP- 8

IP- address

8 ,192 8

1 digit of IP- address

8 π168 8

2 digit of IP- address

8 ´ 1 3 digit of IP- address

8 _ 95 8

4 digit of IP- address

8 th . .

8 thermocouples

8 0-10 8

voltage input 0-10 V

8 0-20 8

current input 0-20 mA

8 4-20 8

current input 4-20 mA

8 r500 8

resistance 500 Ohm

8 r30.0

8

resistance 30 K Ohm

8 dhcp 8 DHCP

8 off 8

DHCP off

8 on 8

DHCP on

8 faIl 8

DHCP missed

8 Al 1 8

...

8 Al 4 8

alarms 1 to 4

8 boot 8

webserver starts

(Date / Name): 20.04.2011 Fu/Su Drawing no.: 12280-0701-05

Page 8 of 28 Name: TR 800 WEB

ZIEHL industrie-elektronik GmbH + Co KG, Daimlerstr.13, D-74523 Schwäbisch Hall, Tel.: +49 791 504-0, Fax: -56, email: [email protected]

8.6 Overview of commissioning

Must Can Overview

X

8.7 Switch on the unit

X

X

X

X

8.8 Connection to network and controls

8.9 Find the unit in the network

8.9.1 DHCP server

8.9.2

8.9.3

8.9.4

Default IP address 10.10.10.10

Bonjour

UPnP

8.10 Make the basic network settings

8.11 Sensor settings

X

X

X

X

8.13 Configure the alarms

8.13 Alarm email

8.14 System

8.15 User management/access control

X

8.16 Logging

X

8.17 View measurements and alarms, sensor simulation

8.7 Switching on the unit

Apply supply voltage to terminals A1 and A2,

Ca. 2s long, all LEDs and the digital display illuminate (

8.8.8.8. )

The TR 800 Web is now ready to operate

In the digital display, boot flashes (alternating with sensor value), the integrated webserver starts (duration ca. 1-2 minutes). After boot extinguishes, the unit can be addressed via its interfaces.

8.8 Connection to network and controls

(Date / Name): 20.04.2011 Fu/Su Drawing no.: 12280-0701-05

Page 9 of 28 Name: TR 800 WEB

ZIEHL industrie-elektronik GmbH + Co KG, Daimlerstr.13, D-74523 Schwäbisch Hall, Tel.: +49 791 504-0, Fax: -56, email: [email protected]

8.9 Find the unit in the network

Prerequisite: Web browser Internet Explorer 7,8 or Firefox 3 (tested).

The TR 800 Web provides four facilities to find itself in the network:

8.9.1 DHCP server

In the network, there is a DHCP server; newly added units automatically are assigned an

IP address

Query of the IP address in the unit

Press the DOWN button 2x, then the SET button

IP address appears in the digital display

Status of DHCP query is displayed ( off

/ on

/

FAIL

)

Start web browser and enter the IP address in the address line [Return]

The TR 800 Web homepage opens in the web browser

Close the login window with the OK button (without user name and without password)

If the network logon fails via DHCP, a network configuration will be performed based on zeroconf (IP = 169.254.x.x).

8.9.2 Default IP- Address 10.10.10.10

! Use this setting for configuration only.

Push slide switch to IP 10.10.10.10 (sketch Point 8.8)

Requires a reboot of webserver (press RESET button), in the digital display boot flashes (start duration ca. 1 min)

User management is deactivated, http-Port = 80 und https-Port = 443

Note: The following actions can only be performed with administrator rights.

Enter this command into your PC in the input prompt (command line): route add 10.10.10.10 xxx.xxx.xxx.xxx (xxx.xxx.xxx.xxx= IP address of PC)

Route for the TR 800 Web ping 10.10.10.10

Connection test

TR 800 Web replies

Reply from 10.10.10.10: Bytes=32 Time=3ms TTL=32

Reply from 10.10.10.10: Bytes=32 Time=1ms TTL=32

Ping statistic for 10.10.10.10:

Package: Sent = 4, Received = 4, Lost = 0 (0% loss),

Connection okay

Start web browser and enter the IP address (10.10.10.10) in the address line [Return]

The TR 800 Web homepage opens in the web browser

Close the login window with the OK button (without user name and without password)

Make the basic network settings

Push the slide switch to IP USER (sketch Point 8.8)

Requires a reboot of webserver (press RESET button), in the digital display boot flashes (start duration ca. 1-2 minutes

Note: The settings made in the web browser under "Network" are only effective after the slide switch is switched to IP User and the unit has been rebooted (press RESET button).

(Date / Name): 20.04.2011 Fu/Su Drawing no.: 12280-0701-05

Page 10 of 28 Name: TR 800 WEB

ZIEHL industrie-elektronik GmbH + Co KG, Daimlerstr.13, D-74523 Schwäbisch Hall, Tel.: +49 791 504-0, Fax: -56, email: [email protected]

8.9.3 Bonjour

Plugin for Internet Explorer (www.apple.com/bonjour)

Plugin for Firefox Browser (www.bonjourfoxy.net)

Optional in the Safari browser (switch on)

Note: not available if the http-service has been disabled.

Windows: Download the plugin for Internet Explorer from the Internet and install it

Mac OS X: Bonjour is integrated in the system (Safari browser)

Linux: Bonjour not available

Start browser and let TR 800 Web search with Bonjour.

Double click on the device found

The TR 800 Web homepage opens in the web browser

Close the login window with the OK button (without user name and without password)

8.9.4 UPnP

Available for Windows starting from Win XP

Note: not available if the http port has been switched off

Start network browser (network environment),

("Symbols for show Network UPnP devices" must be active)

Double click on the device found

The TR 800 Web homepage opens in the web browser

Close the login window with the OK button (without user name and without password)

8.9.5 Information about the login window

Closing the login window (click on OK button) is delayed a couple of seconds as data still needs to be transmitted in the background.

If the user admin/access control is inactive (default) the login window is not visible.

The user management/access control is always deactivated if the slide switch is set to

IP=10.10.10.10 (see Points 8.8 and 8.9.2).

If the user admin/access control is active (see Point 8.15), the Username and Password must be entered.

Entry is case-sensitive.

Guest access (if activated, see Point 8.15) is made by logging in without any user name and password. Guests can only view the "Measurements" and "Sensors" web pages. It is not possible to change the parameters.

(Date / Name): 20.04.2011 Fu/Su Drawing no.: 12280-0701-05

Page 11 of 28 Name: TR 800 WEB

ZIEHL industrie-elektronik GmbH + Co KG, Daimlerstr.13, D-74523 Schwäbisch Hall, Tel.: +49 791 504-0, Fax: -56, email: [email protected]

8.10 Make the basic network settings

Select "Network" in the web browser menu

Network TCP/IP:

You can enter the desired network parameters here.

Ask your network administrator if necessary.

Note: Switch off http with http-Port = 0.

UDP settings:

The device provides a facility to download data via the UDP protocol.

The related UDP port can be changed here.

RS485 interface:

If the device is operated on a RS485 interface, the parameters and the protocol can be selected here

Email settings:

The TR 800 Web provides a facility for sending an email if the alarm state changes.

Enter the access data into the corresponding boxes.

Active services:

Services may be disabled.

(Date / Name): 20.04.2011 Fu/Su Drawing no.: 12280-0701-05

Page 12 of 28 Name: TR 800 WEB

ZIEHL industrie-elektronik GmbH + Co KG, Daimlerstr.13, D-74523 Schwäbisch Hall, Tel.: +49 791 504-0, Fax: -56, email: [email protected]

8.11 Sensor settings

Select "Sensors" in the web browser menu

Make the settings for the connected sensor types here. A name can be assigned for each sensor for clear identification.

Box

Sensor name

Current value

Sensor type

Wire

Compensation

Scaling on

Zero-point

Full-scale

Dec. point

Unit

Description

State a name for sensors 1 - 8

Display the measurement with the unit

Select the sensor type only with Pt100 / Pt1000: Select "3-wire" or choose a total wire resistance for 2-wires.

2-wire technique wire resistance compensation:

To compensate the wire resistance short-circuit the wires nearby the sensor and measure the wire resistance. We recommend to use 2 or better 3 wires for each sensor.

With 2-wire connection and a common wire for all signals, all sensor measuring currents will be added on the common wire. Thus the value of the compensation wire resistance RK must be calculated as follows:

RK = (n+1) x RL/2

(RL = wire resistance of two wires, n = number of sensors)

Scaling for temperature sensors not available.

Zero-point scaling

Full-scale scaling

Decimal point scaling

°C, °F, V, mA, Ω, kΩ, % and a freely-definable unit (box can be edited).

°C and °F are available for temperature sensors.

(Date / Name): 20.04.2011 Fu/Su Drawing no.: 12280-0701-05

Page 13 of 28 Name: TR 800 WEB

ZIEHL industrie-elektronik GmbH + Co KG, Daimlerstr.13, D-74523 Schwäbisch Hall, Tel.: +49 791 504-0, Fax: -56, email: [email protected]

8.12 Configuring the alarms

Box

Day / Night

Alarm name

Delay

Relay on alarm

Alarm on error

Alarm locked

Sensor no.

Description

Switch the display of the alarm values for day / night operation.

Definition of the switchover times in the "Time control" menu

Attention: Only affects the values of "Alarm ON" and "Alarm OFF"

State a name for the respective alarm on: Time (in s) during which an alarm is suppressed: off: Backshift (in s) after an alarm on: The relay picks up during an alarm off: The relay releases during an alarm on: This alarm is non-delayed triggered during: device error sensor error (even if the sensors are not "active") off: This alarm is not triggered during a sensor error / device error.

If a sensor triggers an alarm, and this sensor has an error, then the alarm is non-delayed reset (even if "Alarm locked '= on). on: An alarm occurring one time will not be automatically reset. Only pressing reset (close "SET/RESET" button ≥ 2s or ext. Y1/Y2 reset or break of supply voltage Us) resets the alarm. off: Alarm not locked active: Switches the alarm for this sensor on/off

Alarm on : Value at which the device triggers an alarm

Alarm off: Value at which the device resets an alarm

(Date / Name): 20.04.2011 Fu/Su Drawing no.: 12280-0701-05

Page 14 of 28 Name: TR 800 WEB

ZIEHL industrie-elektronik GmbH + Co KG, Daimlerstr.13, D-74523 Schwäbisch Hall, Tel.: +49 791 504-0, Fax: -56, email: [email protected]

Definition of alarm values:

Value in box

Alarm on >

Value in box

Alarm off

Alarm state

Alarm if: Measurement value >= Alarm on

Alarm off if: Measurement value < Alarm off

Alarm on < Alarm off

Alarm if: Measurement value <= Alarm on

Alarm off if: Measurement value > Alarm off

8.13 Alarm email

In addition to an alarm message on Relay K1-K4, an email can also automatically be sent.

Box

Dropdown list

Email

"Alarm ON"

Email

"Alarm OFF"

Recipient

Subject

Text

Description

Selects for which alarm (1-4) an email will be sent

Email will be sent if an alarm occurs

Email will be sent if an alarm expires

Enter email addresses (separated with a semicolon) or press "Add" button and select the addresses from the list (emails of the addresses entered in the [Users] menu)

Optional subject text

Optional instructions text

(Date / Name): 20.04.2011 Fu/Su Drawing no.: 12280-0701-05

Page 15 of 28 Name: TR 800 WEB

ZIEHL industrie-elektronik GmbH + Co KG, Daimlerstr.13, D-74523 Schwäbisch Hall, Tel.: +49 791 504-0, Fax: -56, email: [email protected]

8.14 System

The device name appears in the uppermost line of the website after saving.

The TR 800 Web has a real-time clock that can be synchronized with a "Timeserver" (NTP protocol, uses UDP Port 123). The server, router, proxy … connected to the network usually provides such a function. Timeservers from the Internet can also be used (e.g. ptbtime1.ptb.de). Ask your network administrator if necessary. Alternatively, the system time can be manually set and transferred with the "Update TR 800 system time".

Function

Save device settings

Save device settings on a PC

Copy device settings from PC to

TR 800 Web

Description

Every change in the device can be taken over with the [Save] button; a new configuration point is automatically added. It is saved with the date, time and the user. A comment can be added to these points.

Activate the desired configuration

Click the link [ Download config. file

The file is downloaded to the PC

]

Press [Search …] button. Choose the desired "Config. file" and press the [upload] button.

The config. file is uploaded and the configuration is taken over

Reactivate saved device settings

Set factory settings

Using the functions

Activate the desired configuration

Press the [Reactivate] button

The saved configuration is taken over

Press the [Set factory settings] button

The device configuration is set to the delivered condition

"Save device settings to a PC"

(Date / Name): 20.04.2011 Fu/Su Drawing no.: 12280-0701-05

Page 16 of 28 Name: TR 800 WEB

ZIEHL industrie-elektronik GmbH + Co KG, Daimlerstr.13, D-74523 Schwäbisch Hall, Tel.: +49 791 504-0, Fax: -56, email: [email protected]

and "Transfer device settings from PC to TR 800 Web" you can very simply copy the device settings to multiple TR 800 Webs.

Firmware updates including the installation instructions can be downloaded from the www.ziehl.com

website as needed.

8.15 User management/access control

The TR 800 Web has user management with access control. Stipulate the administrator, user and guest access here as required. If the user management is switched on (checkbox [active]), a password can be assigned to each user (and administrator). To do that, click on the [Change password] button. In the window that opens, enter the first and second lines for each desired password.

If the settings for the email account ("Network" menu) have been made, a test mail can be sent to each user.

Possibly occurring transmission errors are logged in the "Test mail log file".

(Date / Name): 20.04.2011 Fu/Su Drawing no.: 12280-0701-05

Page 17 of 28 Name: TR 800 WEB

ZIEHL industrie-elektronik GmbH + Co KG, Daimlerstr.13, D-74523 Schwäbisch Hall, Tel.: +49 791 504-0, Fax: -56, email: [email protected]

8.16 Logging and FTP Upload

Logging:

Measurement data and alarms are automatically logged as specified. Data records of 1500 measurements and 500 alarm changes are logged in two ring memories. 100 ring memories are stored internally.

Recording time depending on the setting of the interval: current ring memory recording time

Interval 1500 data records days

00:00:02 0:50:00 0.0

100 ring memory -backups days

17.4 month

0.6 year

0.0

00:00:10

00:00:30

00:01:00

00:03:00

00:05:00

00:30:00

01:00:00

4:10:00 0.2

12:30:00 0.5

25:00:00 1.0

75:00:00 3.1

125:00:00 5.2

750:00:00 31.3

1500:00:00 62.5

17.4

52.1

104.2

312.5

520.8

3125.0

6250.0

0.6

1.7

3.4

10.3

17.1

0.0

0.1

0.3

0.9

1.4

102.7 8.6

205.5 17.1

(Date / Name): 20.04.2011 Fu/Su Drawing no.: 12280-0701-05

Page 18 of 28 Name: TR 800 WEB

ZIEHL industrie-elektronik GmbH + Co KG, Daimlerstr.13, D-74523 Schwäbisch Hall, Tel.: +49 791 504-0, Fax: -56, email: [email protected]

Log description:

Content of the log files

Individual data records

Interval

Checkbox ring memory

Data und Alarms

DecSeparator

[Display measurements] button

[Display alarms] button

[Delete measurements] button

[Delete alarms] button

Download measurement data link Download alarms link

Min/Max values with date/time

Date/time; Measurement values sensors 1-8; Alarm values 1-4 (sum of the sensors that triggered the alarm

S1=1, S2=2…S8=128); Error number (device error)

In this time interval, the data is logged.

Selection of the ring buffer, sorted by date.

. „current“ = the last 1500 / 500 records.

This character is used in the csv files.

The selected memory of data and the alarm states can be viewed in a new window

The current memory and the backups are deleted.

The selected memory is downloaded as a csv file

FTP Upload:

With the FTP upload, depending on selection, the current data values and alarms, the current ring memory for data and alarms, and the internally stored ring memories are uploaded.

There are files with the extension ". upl" uploaded and then renamed to ". csv".

The filename uses the local time format. Inside the files, the selected time format is used (see

System Settings). In the case of transmission problems, see the "Transmission Log" file.

Upload Selection present data and alarms

Current data memory

Data memory backups

Current alarms memory

Alarms memory backups

The file

„current.csv“ will be uploaded.

The file

„values.csv“ will be uploaded. The content consists of

1500 records (current ring memory data). file size about 100-

200 kbyte.

The file(s)

„values.xxx.csv“ will be uploaded. xxx = Date/time in local time format.

The file

„alarms.csv“ “ will be uploaded. The content consists of 500 records (current ring memory alarms). file size about

40-80 kbyte.

The file(s)

„alarms.xxx.csv“ will be uploaded. xxx = Date/time in local time format.

Trigger

Log interval Time between upload of

„ present data and alarms“, current data memory and current alarms memory .If available, also the memory backup files are uploaded.

.

On change of alarm, the upload is performed. additional upload on

„alarm on“ und „alarm off“

Button [manual upload] An upload is performed.

Link Transmission Log

Target Server address

Transmission Log from the last upload. Link colour: black: success; red: error.

Enter the address of the destination FTP server IP or host name. You can optionally add the port number. For example

"192.168.3.3" or "192.168.3.3:2000" or "ftpserver.com"

(Date / Name): 20.04.2011 Fu/Su Drawing no.: 12280-0701-05

Page 19 of 28 Name: TR 800 WEB

ZIEHL industrie-elektronik GmbH + Co KG, Daimlerstr.13, D-74523 Schwäbisch Hall, Tel.: +49 791 504-0, Fax: -56, email: [email protected]

directory

anonymous login username

Password

„delete“ before „rename“

Enter the directory where the files are stored. Example:

"test/test2"

The indication of sub-directories with "/".

There must be no "\" be used.

Can be activated when the FTP server allows anonymous login.

User name for login on the FTP server

Password for the login on the FTP server

This is to activate when the FTP server rename a file into an existing file is not accepted.

This is in some Windows FTP servers / server program needed. See Transmission Log.

8.17 View measurements and alarms, sensor simulation

Here, all measurements can be clearly viewed with min./max. values plus the alarms. Using the sensor simulation, individual sensor values can be simulated. The simulation independently switches off after 15 minutes with no changes in the simulation value.

(Date / Name): 20.04.2011 Fu/Su Drawing no.: 12280-0701-05

Page 20 of 28 Name: TR 800 WEB

ZIEHL industrie-elektronik GmbH + Co KG, Daimlerstr.13, D-74523 Schwäbisch Hall, Tel.: +49 791 504-0, Fax: -56, email: [email protected]

The progression of the measurements is displayed in a chart. Sensors can be flexibly displayed or hidden. The colour and the format of the line and the marker can be set.

Checkbox details: 100 logged points (see Point 8.16) are displayed in the chart.

Using the [<older] / [>newer recent] buttons, one can navigate chronologically in both directions.

Complete checkbox: The entire logged area (1500 points) is shown in the chart

Absolute checkbox: Unit of the y-axis corresponds to the sensor metrics

Relative checkbox: Unit of y-axis: 0-100%

Backups Memory: Selecting the backup ring buffer, which is shown

(Date / Name): 20.04.2011 Fu/Su Drawing no.: 12280-0701-05

Page 21 of 28 Name: TR 800 WEB

ZIEHL industrie-elektronik GmbH + Co KG, Daimlerstr.13, D-74523 Schwäbisch Hall, Tel.: +49 791 504-0, Fax: -56, email: [email protected]

8.18 Time-dependent control / Scheduler

The time control specifies which alarm values (Day or night) are active at which time.

The following settings are available: o active: day (no time control; alarm day-values always apply) o active: night (no time control; alarm night-values always apply) o active: scheduled (the specified switchover times apply)

The times for the night values are entered into the table.

Up to four switch times can be set for each day of the week. To activate these times, the

"active" check box for the corresponding day needs to be set.

Example for switchover times:

Specification in the web browser

Night values are active

Su 00:00 h

Su 22:00 h

Mo 21:30 h

-

-

-

Su. 06:00 h

Mo. 07:30 h

Tu. 00:00 h

(Date / Name): 20.04.2011 Fu/Su Drawing no.: 12280-0701-05

Page 22 of 28 Name: TR 800 WEB

ZIEHL industrie-elektronik GmbH + Co KG, Daimlerstr.13, D-74523 Schwäbisch Hall, Tel.: +49 791 504-0, Fax: -56, email: [email protected]

9. Ethernet protocols

Along with the http and https protocols for the web browser, the TR 800 Web also supports additional Ethernet protocols: UDP, Modbus, SNMP, FTP and AJAX.

9.1 UDP

The interface parameter for the UDP protocol can be viewed and changed in the web user interface [Network / UDP settings].

A detailed description of the protocol can be found in the TR 800 Web online help section or can be downloaded via the Internet (www.ziehl.com).

9.2 Modbus TCP

The Modbus TCP protocol is available through TCP port 502.

A detailed description can be found in the TR 800 Web online help section or can be downloaded via the Internet (www.ziehl.com).

9.3 SNMP

The SNMP protocol makes measurements and configuration values available (read only).

The MIB file is located in the online help of TR 800 Web or can be downloaded via the Internet

(www.ziehl.com).

9.4 FTP Upload (Option)

Recorded measurements and alarm states can be time-controlled saved to an FTP server as a

CSV file. Furthermore, it is possible to continuously transmit the current values or time controlled or event controlled (change in an alarm state).

9.5 AJAX data interface

The AJAX data interface makes data measurement and alarm data in the Ajax-compatible

JSON format. The description can be found in the online help of the TR 800 Web.

10. RS485 interface

The RS485 interface supports two protocols: Ziehl Standard Protocol and Modbus RTU

Protocol. Make the interface settings via the web browser,

[Network / RS485 interface].

10.1 Ziehl Standard Protocol

A description can be found in the TR 800 Web online help section or can be downloaded via the Internet (www.ziehl.com).

10.2 Modbus RTU

A description can be found in the TR 800 Web online help section or can be downloaded via the Internet (www.ziehl.com).

11. Maintenance and Repair

ZIEHL industrie-elektronik GmbH + Co KG

Daimlerstr.13

D-74523 Schwäbisch Hall

Telephone: +49 791 504-0 Fax: +49 791 504-56 e-mail: [email protected] homepage: www.ziehl.com

(Date / Name): 20.04.2011 Fu/Su Drawing no.: 12280-0701-05

Page 23 of 28 Name: TR 800 WEB

ZIEHL industrie-elektronik GmbH + Co KG, Daimlerstr.13, D-74523 Schwäbisch Hall, Tel.: +49 791 504-0, Fax: -56, email: [email protected]

12. Troubleshooting

boot

appears in the digital display

Cause

Remedy

This is not an error.

The internal webserver is starting up.

After switching on the network, the internal webserver needs app. 1 min. until it starts. After that, the digital display extinguishes.

After performing a software update, the webserver automatically reboots.

Er 5 appears in the digital display

Cause The internal webserver is not working correctly

Remedy

Do a reset; press the reset button on the unit (see Point 8.8) or switch off the unit and then back on.

After max. 2 min,

Er 5 and boot should no longer be flashing in the display.

Er 1 or Er 2 appears in the digital display

Cause Sensor short-circuit or sensor interruption on the TR 800 Web

Remedy

Check sensor on the TR 800 Web to see if it is electrically okay and is correctly connected.

Er 4 appears in the digital display

Cause A connected thermocouple is connected the wrong way around

Remedy Check the thermocouple and connect it correctly if applicable

Er 8 appears in the digital display

Cause Internal device error

Remedy

Switch unit off and back on. If the error message continues to appear, the unit must be returned to the factory for repair

LED Rx and Tx constantly flash

Cause

Remedy

The unit is momentarily performing a software update

A software update can take up to 5 min. After that, the LEDs automatically go out.

If the LEDs continue to flash, an error occurred during the software update.

Switch off the unit and back on. The LEDs must go out

Displayed temperature does not match the sensor temperature

Cause o

False measuring-unit was set o

Error in the scaling

Remedy Check the settings in the web user interface in [Sensors

– Sensor Settings]

User name/password not known

Remedy

See 8.9.2 Set default IP address 10.10.10.10

User management is deactivated, http-Port = 80 and https-Port = 443 e-mails are not receive

Remedy e-mails are not receive, if multiple recipients are used. Reason could be that one address from the e-mail server is not accepted, then the e-mail is not sent.

Test: Change to the browser menu "User", enter all the recipients in an "email" field, press "Test Email" button, wait for some time (10-60 s), then check the

"Test Mail Logfile".

(Date / Name): 20.04.2011 Fu/Su Drawing no.: 12280-0701-05

Page 24 of 28 Name: TR 800 WEB

ZIEHL industrie-elektronik GmbH + Co KG, Daimlerstr.13, D-74523 Schwäbisch Hall, Tel.: +49 791 504-0, Fax: -56, email: [email protected]

Login window cannot be closed

Remedy Close the browser window and then reopen it

Data graphics, Logging, it appears a later time stamp

Remedy

Check the date and time in the menu

“System".

Erase all data logs with button "erase log" in menu “Logging”

13. Technical Data

Rated supply voltage Us

Tolerance

Power consumption

Relay output

Switching voltage

Switching current

Switching capacity

AC/DC 24

– 240 V

DC 20,4 - 297 V

< 4 W

AC 20 - 264 V 50-60 Hz

<13 VA

4 x 1 changeover (CO) max. AC 415 V max. 5 A max. 1250 VA (ohmic load) max.120 W at DC 24 V

UL electrical ratings:

E214025

250 V ac, 5 A, resisitive

240 V ac, 1/2 hp

120 V ac, 1/4 hp

B 300

– pilot duty, UL 508

Nominal operational current Ie

AC15

DC13

Recommended fuses for contact

Expected contact life mechanical

Expected contact life electrical

Test conditions

Rated impulse voltage

Overvoltage category

Contamination level

Rated insulation voltage Ui

On-time

Environmental conditions

Ambient temperature range

Storage temperature range

Altitude

Climatic conditions

External wiring temperature range

Vibration resistance EN 60068-2-6

Ie = 3 A Ue = 250 V

Ie = 2 A Ue = 24 V

Ie = 0,2 A Ue = 125 V

Ie = 0,1 A Ue = 250 V

T 3,15 A (gL)

3 x 10

7

operations

1 x 10

5

operations at AC 250 V / 6 A

EN 61010-1

4000 V

III

2

300 V

100%

-20 °C ... +65 °C

-

20 °C … +70 °C

Up to 2000 m

5

– 85 % rel. humidity, no condensation

-

5 °C … +70 °C

2…25 Hz ±1,6 mm

25 ... 150 Hz 5 g

(Date / Name): 20.04.2011 Fu/Su Drawing no.: 12280-0701-05

Page 25 of 28 Name: TR 800 WEB

ZIEHL industrie-elektronik GmbH + Co KG, Daimlerstr.13, D-74523 Schwäbisch Hall, Tel.: +49 791 504-0, Fax: -56, email: [email protected]

EMC-tests

emitted interference

Burst

SURGE

discharge of static electricity

EN 61326-1

EN 61000-6-3

EN 61000-4-4 +/-4 kV

Pulse 5/50 ns, f = 5 kHz, t = 15 ms, T = 300 ms

IEC 61000-4-5 +/-1 kV

Impulse 1,2/50 µs (8/20 µs)

IEC 61000-4-2 +/-4 kV contact,

+/- 8kV air

10/100 MBit Auto-MDIX http/https = 5

Network-connection

Max. number of connections

Real-time clock

Reset input Y1/Y2 time-reserve 7 days app. DC 18 V / 3,5 mA

RS 485 interface:

Baud rate

Parity

Wire length

4800, 9600, 19200 Baud

N, O, E (none, odd, even)

1000 m at 19200 Baud

ZIEHL RS485 protocol

Time end request

– start answer 5…50 ms

Send data without request 3 s 3 s ± 200 ms

Send data without request 170 ms 170 ms ± 50 ms

Sensor connection:

Measuring-cycle / time depending on sensor type

Sensor(1+3+5+7)

Sensor(2+4+6+8)

0.340.. 3 s

0.340.. 3 s

Pt 100, Pt 1000 according to EN 60751:

Measuring range °C

Sensor min max

Pt 100 -199 860

Short-circuit

Ohm

<

15

Break

Ohm

>

400

Sensor resistance

+ line resistance Ohm max

500

Pt 1000 -199 860

KTY 83 -55 175

150

150

4000

4000

4100

4100

KTY 84 -40 150

Tolerance

Sensor current

150 4000 4100

±0,5 % of measured value ±0,5 K (KTY ±5 K)

≤0,6 mA

Temperature drift <0,04°C/K

Measuring time 2-wire connection <= 220 ms

Measuring time 3-wire connection <= 440 ms

(Date / Name): 20.04.2011 Fu/Su Drawing no.: 12280-0701-05

Page 26 of 28 Name: TR 800 WEB

ZIEHL industrie-elektronik GmbH + Co KG, Daimlerstr.13, D-74523 Schwäbisch Hall, Tel.: +49 791 504-0, Fax: -56, email: [email protected]

Thermocouples according to EN 60 584, DIN 43 710:

Measuring range °C Precision

Type min Max

B

E

0

-270

J -210

K -200

1820

1000

1200

1372

±2 °C

T > 300°C

±1 °C

±1 °C

±2 °C

L -200

N -270

R -50

900

1300

1770

±1 °C

±2 °C

±2 °C

S -50

T -270

Reference junction

Measuring time

Voltage- / Current input

1770

400

±2 °C

±1 °C

Temperature drift < 0,01 % / K

Measuring error of the sensor wire +0,25

µV / Ω

±5 °C

<= 440 ms

0

– 10 V

0/4-20 mA

Temperature drift

Measuring time

12 kΩ

18 Ω

Measuring of resistance:

Precision

0,0 … 500,0 Ω

Precision

0…30,00 kΩ

Sensor-current

Measuring time

Housing

Dimensions (W x H x D)

Design V8, switchgear mounting

140 x 90 x 58 mm

Mounting height

Wire connection, one wire

55 mm each 1 x 1,5 mm

Stranded wire with insulated ferrules each 1 x 1,0 mm

2

2

Torque of screw 0,5 Nm (3,6 lb.in)

Protection class housing

Protection class terminal

Fitting position

Installation

Weight

Input resistance

Subject to technical changes

Maximum

Input signal

27 V

100 mA

IP 30

IP 20 any

Precision

(from Full-Scale)

0,1 %

< 0,02 %/K

<= 40 ms

0,5 % a voltage > 20 V will affect other channels

0,2 % of measured value

± 0,5 Ω

0,5 % of measured value

± 2 Ω

≤0,6 mA

<= 220 ms

Snap mounting on mounting rail 35 mm according to

EN 60 715 or with screws M 4

(2 additional bars, not included in delivery) app. 370 g

(Date / Name): 20.04.2011 Fu/Su Drawing no.: 12280-0701-05

Page 27 of 28 Name: TR 800 WEB

ZIEHL industrie-elektronik GmbH + Co KG, Daimlerstr.13, D-74523 Schwäbisch Hall, Tel.: +49 791 504-0, Fax: -56, email: [email protected]

14. Housing design V8

Dimensions in mm

1

58

2

48

16,5

3

4

5

1

2

3

Oberteil / cover

Unterteil / base

Riegel / bar for snap mounting

6

210

Option

280

7

4

5

6

Plombenlasche / latch for sealing

Frontplatteneinsatz / front panel

Kennzeichen für unten / position downward

7 Riegel bei Wandbefestigung mit Schrauben. Riegelbohrung Ø 4,2 mm / for fixing to wall with screws, Ø 4,2 mm.

Sie finden diese und weitere Betriebsanleitungen, soweit verfügbar auch in Englisch, auf unserer Homepage www.ziehl.de.

You find this and other operating-manuals on our homepage www.ziehl.de, as far as available also in English.

(Date / Name): 20.04.2011 Fu/Su Drawing no.: 12280-0701-05

Page 28 of 28 Name: TR 800 WEB

ZIEHL industrie-elektronik GmbH + Co KG, Daimlerstr.13, D-74523 Schwäbisch Hall, Tel.: +49 791 504-0, Fax: -56, email: [email protected]

advertisement

Key Features

  • 8 measuring inputs
  • 4 relay-outputs
  • Ethernet interface
  • RS485 interface
  • Universal power-supply AC/DC
  • Integrated webserver
  • Time-dependent control
  • Real-time clock

Frequently Answers and Questions

What is the TR 800 Web?
The TR 800 Web is a universal relay with an Ethernet interface and 8 inputs for temperature sensors and other analogue signals.
How can I connect the TR 800 Web to the network?
The TR 800 Web can be connected to the internet or an intranet using a DHCP server, a default IP address (10.10.10.10), Bonjour, or UPnP.
What protocols does the TR 800 Web support?
The TR 800 Web supports various protocols, including http, https, UDP, Modbus, SNMP, FTP, and AJAX.