PGE Product Specifications
PGE
Product Specifications
COMMERCIAL ASHRAE EFFICIENT PACKAGE GAS HEATING/ELECTRIC COOLING
R−22 SINGLE PACKAGE ROOFTOP 6 − 25 TONS (3−Phase)
BUILT TO LAST, EASY TO INSTALL AND SERVICE
• One−piece, high efficiency gas heating, electric cooling with a low profile, prewired, tested, and charged at the factory
• Field convertible supply and return openings are intended for installation on a roof top or ground level for 072−150 models
• Hermetic−type scroll compressor: single compressor on 072 model, dual compressors on 090−300 models
• Refrigeration system: loss−of−charge, freeze protection, and high pressure safety switches
PGE 072
• Units 090 to 300 have 2−stage cooling operation
• Refrigerant circuits contain a filter drier to trap dirt and moisture
• Non−corrosive condensate pan on 072 − 150 models with choice of bottom or side drain connections. All models have self
draining sloping design
• Adjustable belt drive indoor fan standard on all models
• Direct−drive propeller outdoor fan totally enclosed with permanently lubricated bearings
• Prepainted, galvanized steel cabinet, primer inner panels, certified at 500−hr salt spray test and noncorrosive screws
• Easily removable panels provide ready access to unit components for rapid removal or maintenance
• Two inch disposable fiberglass type return air filters in dedicated rack with tool−less filter access door
• Exclusive integrated gas control board with diagnostics and anti−cycle protection
• Tubular, dimpled gas heat exchangers optimize heat transfer for improved efficiency
• Induced−draft fan for gas combustion
• Outdoor temperature cooling operation down to 25°F and up to 125°F
• Fixed orifice metering devices on 072−150 units and TXV’s on 180−300 units to precisely control refrigerant flow
• 24−Volt control circuit with resettable circuit breaker on 072−150 models
• Indoor and outdoor coils constructed of aluminum fins mechanically bonded to seamless copper tubes
• 25% Manual outside air damper on 180−300 models
• Thru−the−bottom power entry capability
PGE090−150
PGE180−240
WARRANTY
PGE300
•10 Year heat exchanger limited warranty
• 5 Year compressor limited warranty
• 1 Year parts limited warranty
180 − 300
UNIT PERFORMANCE DATA
COOLING
UNIT
PGE 3−Phase
PGE072*^A00AA
Nominal
TONS
6
Net
Capacity
(Btuh)
71,000
PGE090*^A00AA
7
88,000
PGE102*^A00AA
8
100,000
PGE120*^A00AA
10
PGE150*^A00AA
PGE180*^A00AA
EER
GAS HEATING RANGE
10.1
Total kW
7.0
Heating
Input Capacity (Btuh)
74,000 − 150,000
AFUE (%)
80
Unit Dimensions
HxWxL
33” x 73” x 45”
Unit
Weight
626
10.1
8.7
125,000 − 224,000
80
41” x 87” x 57”
881
10.1
9.9
125,000 − 224,000
80
41” x 87” x 57”
896
114,000
10.1
11.3
180,000 − 250,000
80
49” x 87” x 57”
1057
12
136,000
9.5
14.3
224,000 − 250,000
80
49” x 87” x 57”
1077
15
176,000
9.5
17.1
45” x 91” x 86”
1800
PGE210*^A00AA
18
202,000
9.7
21.2
45” x 91” x 86”
1850
PGE240*^A00AA
20
236,000
9.5
24.8
47” x 91” x 86”
1900
PGE300*^A00AA
25
278,000
9.7
28.5
52” x 120” x 86”
2270
Belt
275,000 − 360,000
81
* Indicates Unit Voltage 3 Phase: H = 208/230v, L = 460v, S = 575v
^ Indicates Heating Capacity: D = Low Heat, F = High Heat
NOTE: BASE MODEL NUMBERS LISTED. SEE MODEL NOMENCLATURE LISTING FOR ADDITIONAL OPTIONS.
521 21 1001 04
08/19/09
TABLE OF CONTENTS
Model Nomenclature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Features/Benefits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
ARI Capacity Ratings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5−6
Options and Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7−10
PGE072 − 150
Physical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11−14
Base Unit Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15−16
Performance Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17−43
Electrical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44−45
Typical Wiring Schematics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46−47
Typical Piping and Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
Guide Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49−50
PGE180 − 300
Physical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51−52
Base Unit Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53−55
Accessory Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56
Performance Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57−67
Electrical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68
Typical Wiring Schematics and Piping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69−70
Guide Specifications−Constant Volume Application . . . . . . . . . . . . . . . . . . . . . . . . . . . 71−72
Controls . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 73−74
2
Specifications subject to change without notice.
521 21 1001 04
MODEL NOMENCLATURE
MODEL SERIES
P
G
E
090
H
D
A
00
A
A
A
P = Package
G = Gas/Electric
E = ASHRAE Compliant
072 = 72,000
090 = 90,000
102 = 102,000
120 = 120,000
155 = 155,000
180 = 180,000
210 = 210,000
240 = 240,000
300 = 300,000
NOMINAL COOLING BTU/h
H = 208/230−3−60
L = 460−3−60
S = 575−3−60
VOLTAGE
0 = No Heat
D = Low Heat
F = High Heat
HEATING CAPACITY (see spec sheet for actual capacity)
A = Standard Motor
B = High Static Motor
MOTOR OPTION (see spec sheet for details)
00 = No Factory Installed Options
0A = Economizer
0B = Damper
XX = See FIOP Selection Guide for Details
FACTORY INSTALLED OPTIONS (see spec sheet for details)
A = Aluminum/Copper Outdoor Coil
OUTDOOR COIL OPTION
A = Initial Offering
SALES DIGIT
A = Original Design
ENGINEERING DIGIT
521 21 1001 04
Specifications subject to change without notice.
3
FEATURES/BENEFITS
Every compact one−piece unit arrives fully assembled, charged,
tested, and ready to run.
All ignition components are contained in the compact Integrated Gas
Controller (ICG) which is easily accessible for servicing. The IGC
control board provides built−in diagnostic capability. A LED
(light−emitting diode) simplifies troubleshooting by providing visual
fault notification and required system status confirmation.
The IGC also contains an exclusive anti−cycle protection for gas heat
operation. The IGC also contains burner control logic for accurate and
dependable gas ignition. The LED is visible without removing the unit
control box access panel. The IGC also maximizes heating efficiency
by controlling evaporator−fan on and off delays.
Tubular, dimpled gas heat exchangers optimize heat transfer for
improved efficiency. The tubular design permits hot gases to make
multiple passes across the path of the supply air. The dimpled design
creates a turbulent gas flow to maximize heating efficiency.
The efficient in−shot burners and all ignition components are
contained in an easily removable, compact assembly.
The extra thick heat exchanger coating provides corrosion resistance
and ensures long life.
The inducer fan draws hot combustion gas through the heat
exchanger at the optimum rate for the most effective heat transfer. The
heat exchanger operates under negative pressure, preventing flue
gas leakage into the indoor supply air. The 30−second fan delay
prevents cold air from entering the supply duct system when the
conditioned space is calling for heat to maximize efficiency. The
direct−spark ignition system saves operating expense when
compared to pilot ignition systems.
All standard units are designed for natural gas, but an accessory
propane conversion kit is available.
All units have a flame rectification sensor to quickly sense the burner
flame and ignite burners almost immediately. Fast shutdown is a
certainty since the sensor reacts quickly to any flame outage or system
failure.
QUIET,
EFFICIENT
OPERATION
AND
DEPENDABLE
PERFORMANCE − Compressors have vibration isolators for quiet
operation. Efficient fan and motor design permits operation at low
sound levels.
Unit sizes 090−300 offer lower utility costs through part−load
operation using 2 stages of cooling. Quiet and efficient operation is
provided by belt−driven evaporator fans . The belt−driven
evaporator−fan is equipped with variable−pitch pulleys which allow
adjustment within the rpm ranges of the factory−supplied pulleys.
Increased
operating
efficiency
is
achieved
through
computer−designed coils featuring staggered internally enhanced
copper tubes. Fins are ripple−edged for strength, lanced, and double
waved for higher heat transfer.
DURABLE, DEPENDABLE CONSTRUCTION − Designed for
durability in any climate, the weather−resistant cabinets are
constructed of galvanized steel and bonderized, and all exterior
panels are coated with a prepainted baked enamel finish.
The paint finish is non−chalking, and is capable of withstanding ASTM
(American Society for Testing and Materials) B117 500−hour Salt
Spray Test. All internal cabinet panels are primed, permitting longer life
and a more attractive appearance for the entire unit. In addition, all size
072−150 units are designed with a single, continuous top piece to
eliminate any possible leaks at seams or gasketing.
Totally enclosed condenser−fan motors and permanently lubricated
bearings provide additional unit dependability.
EASY INSTALLATION AND CONVERSION All Units are Shipped
in the Vertical Duct Configuration for fit−up to standard roof curbs.
All units feature a base rail design with forklift slots and rigging holes
for easier maneuvering. Durable packaging protects all units during
shipment and storage.
The units can be easily converted from a vertical to a horizontal duct
configuration by relocating the panels supplied with the unit (072−150
only).
To Convert 072−150 Units from vertical to horizontal discharge,
simply relocate 2 panels. The same basic unit can be used for a variety
of applications and can be quickly modified at the jobsite.
To Convert 180−300 Units from vertical to horizontal discharge, use
the optional horizontal supply/return adapter roof curb.
Convenient Duct Openings in the unit basepans permit
side−by−side or concentric duct connections without requiring internal
unit modification.
NOTE: On units using horizontal supply and return, the accessory
barometric relief or power exhaust MUST be installed on the return
ductwork.
4
Thru−The−Bottom Service Connection Capability comes
standard with the rooftop unit to allow power and control wiring and gas
connections to be routed through the unit’s basepan, thereby
minimizing roof penetrations (to prevent water leaks).
(Thru−the−bottom gas connection requires thru−the−bottom
accessory kit.) Power, gas and control connections are made on the
same side of the unit to simplify installation.
The Non−Corrosive Sloped Condensate Drain Pan
(Size 072−150 ) permits either an external horizontal side condensate
drain (outside the roof curb) or an internal vertical bottom drain (inside
the roof curb). Both options require an external, field−supplied P−trap.
Standard 2 in. Throwaway Filters are easily accessed through a
removable panel located above the air intake hood. No tools are
required to change unit filters.
Belt−Driven Evaporator−Fan Motors allow maximum on−site
flexibility without changing motors or drives.
Low Voltage Wiring Connections are easily made thanks to the
large terminal board which is located for quick, convenient access. In
addition, color−coded wires permit easy tracing and diagnostics.
PROVEN COMPRESSOR RELIABILITY − Design techniques
feature computer−programmed balance between compressor,
condenser, and evaporator. Hermetic compressors are equipped with
compressor overcurrent and over temperature protection to ensure
dependability.
All units have piston (072−150 ) or TXV (thermostatic expansion valve)
metering device (180−300) which precisely controls refrigerant flow,
preventing slugging and flood−back, while maintaining optimum unit
performance. Refrigerant filter driers are standard.
INTEGRATED ECONOMIZERS AND OUTDOOR−AIR DAMPERS −
Available as options or accessories, economizers and manual
outdoor−air dampers introduce outdoor air which mixes with the
conditioned air, improving indoor−air quality and often reducing
energy consumption.
During a first stage call for cooling, if the outdoor−air temperature is
below the economizer control changeover set point, the mixed−air
sensor modulates the economizer outdoor−air damper open to take
advantage of free cooling provided by the outside air. When
second−stage cooling is called for, the compressor is energized in
addition to the economizer. If the outdoor−air temperature is above the
changeover set point, the first stage of compression is activated and
the economizer damper stays at minimum position.
Accessory upgrade kits allow for control by differential dry−bulb
temperature (outdoor vs return), outdoor air enthalpy changeover, or
more precise differential enthalpy control. All economizers incorporate
a parallel blade, gear−driven damper system for efficient air mixing
and reliable control. In addition, the standard damper actuator
includes a spring return to provide reliable closure on power loss.
The economizers for sizes 072−150 are equipped with up to 100%
barometric relief capability for high outdoor airflow operations.
Economizers for unit sizes 072−150 are available, factory−installed,
for vertical return only. Economizers for unit sizes 180−300 are
compatible for vertical or horizontal return. An optional field−installed
barometric relief package is available for size 180−300 units.
In addition, single−stage power exhaust is available as a
field−installed accessory to help maintain proper building pressure.
For units without economizer, year−round ventilation is enhanced by
an optional manual outdoor−air damper.
On 072−150 units, a manual damper is available as a field−installed
accessory. Unit sizes 180−300 are equipped with a manual 25%
damper.
INDOOR−AIR QUALITY (IAQ) − Sloped condensate pans minimize
biological growth in rooftop units in accordance with ASHRAE
(American Society of Heating, Refrigeration and Air Conditioning
Engineers) Standard 62.
Two−inch filters with optional dirty filter indicator switch provide for
greater particle reduction in the return air.
The face−split evaporator coils improve the dehumidification
capability of standard units, maximize building humidity control.
Specifications subject to change without notice.
521 21 1001 04
ARI* CAPACITY RATINGS − PGE072−150
UNIT PGE
NOMINAL
TONS
NET COOLING CAPACITY
(Btuh)
TOTAL kW
EER
SOUND
RATING (dB)
072
6
71,000
7.0
10.1
80
**
090
71/2
88,000
8.7
10.1
82
10.5
102
120
81/2
10
100,000
114,000
9.9
11.3
10.1
10.1
82
84
10.4
11.0
150
121/2
136,000
14.3
9.5
86
9.70
IPLV
NOTES:
LEGEND:
SEER − Seasonal Energy Efficiency Ratio
dB − Sound Level (Decibels)
db − Dry Bulb
EER − Energy Efficiency Ratio
IPLV − Integrated Part−Load Value
wb − Wet Bulb
* Air Conditioning and Refrigeration Institute
{ − Applies only to units with capacity of 60,000 Btuh or less
** − The IPLV applies only to two−stage cooling units
1. Rated in accordance with ARI Standards 210/240 (for sizes
072−120) or 360, (for size 150) and 270.
2. ARI ratings are net values, reflecting the effects of circulating fan
heat.
3. Ratings are based on:
Cooling Standard: 80°F db, 67°F wb indoor entering−air
temperature and 95°F db air entering outdoor unit.
IPLV Standard: 80°F db, 67°F wb indoor entering−air temperature
and 80°F db outdoor entering−air temperature.
4. All PGE072, 090, 102, 120, 150 units are in compliance with
ASHRAE 90.1−1999 Energy Standard for minimum SEER and
EER requirements. Refer to state and local codes or visit the
following website: http://bcap−energy.org to determine if
compliance with this standard pertains to a given geographical area
of the United States.
ARI* CAPACITY RATINGS − PGE072−150(cont.)
HEATING CAPACITIES AND EFFICIENCIES
PGE072 − 150
UNIT
PGE
072*D
072*F
090*D
090*F
102*D
102*F
120*D
120*F
150*D
150*E
HEATING INPUT
(Btuh)Stage 2/Stage 1
−/ 74,000
150,000/120,000
−/125,000
224,000/180,000
−/125,000
224,000/180,000
180,000/120,000
250,000/200,000
224,000/180,000
250,000/200,000
OUTPUT CAPACITY
(Btuh)
59,200
120,000
100,000
179,200
100,000
179,200
179,200
200,000
179,200
200,000
TEMPERATURE
RISE (F)
25−55
50−80
20−50
45−75
20−50
45−75
35−65
40−70
35−65
40−70
MINIMUM HEATING
AIRFLOW (CFM)
1220
1390
1860
2180
1860
2180
2060
2650
2510
2650
AFUE
(%)
80.0
80.0
80.0
80.0
80.0
80.0
80.0
80.0
80.0
80.0
STEADY STATE
EFFICIENCY (%)
80.0
80.0
80.0
80.0
80.0
80.0
80.0
80.0
80.0
80.0
LEGEND:
* − Voltage
AFUE − Annual Fuel Efficiency
521 21 1001 04
Specifications subject to change without notice.
5
ARI* CAPACITY RATINGS − PGE180−300
UNIT
PGE
180
210
240
300
UNIT
PGE
180
210
240
300
LEGEND:
NOMINAL TONS
15
18
20
25
NET COOLING
CAPACITY (Btuh)
176,000
202,000
236,000
278,000
TOTAL WATTS
17,064
21,166
24,832
28,535
EER
9.5
9.7
9.5
9.7
SOUND RATING
(dB)
88
88
94
94
IPLV
9.5
10.2
10.1
10.4
NOMINAL TONS
15
18
20
25
NET COOLING
CAPACITY (Btuh)
176,000
202,000
236,000
277,000
TOTAL WATTS
17,179
21,301
24,832
29,067
EER
9.5
9.7
9.5
9.5
SOUND RATING
(dB)
88
88
94
94
IPLV
9.5
10.1
10.0
10.0
SEER − Seasonal Energy Efficiency Ratio
dB − Sound Level (Decibels)
db − Dry Bulb
EER − Energy Efficiency Ratio
IPLV − Integrated Part−Load Value
wb − Wet Bulb
3. Ratings are based on:
Cooling Standard: 80°F db, 67°F wb indoor entering−air
temperature and 95°F db air entering outdoor unit.
IPLV Standard: 80°F db, 67°F wb indoor entering−air temperature
and 80°F db outdoor entering−air temperature.
* Air Conditioning and Refrigeration Institute
NOTES:
1. Rated in accordance with ARI Standards 360 and 270.
2. ARI ratings are net values, reflecting the effects of circulating fan
heat.
4. All PGE180−300 units are in compliance with ASHRAE 90.1−1999
Energy Standard for minimum SEER and EER requirements. Refer
to state and local codes or visit the following website:
http://bcap−energy.org to determine if compliance with this
standard pertains to a given geographical area of the United States.
HEATING CAPACITIES AND EFFICIENCIES
UNIT
PGE
180*D
180*F
210*D
210*F
240*D
240*F
300*D
300*F
HEATING INPUT
(Btuh)Stage 2/Stage 1{
275,000/206,000
360,000/270,000
275,000/206,000
360,000/270,000
275,000/206,000
360,000/270,000
275,000/206,000
360,000/270,000
OUTPUT CAPACITY
(Btuh)
223,000
292,000
223,000
292,000
223,000
292,000
223,000
292,000
TEMPERATURE RISE
(F)
15−45
20−50
15−45
20−50
15−45
20−50
15−45
20−50
STEADY-STATE
EFFICIENCY (%)
81.0
81.0
81.0
81.0
81.0
81.0
81.0
81.0
MINIMUM HEATING
CFM
3750
3830
4580
5400
4580
5400
4580
5400
* − Voltage
{All units are 2−stage heat.
NOTE: Minimum allowable temperature of mixed−air entering the heat exchanger during first−stage heating is 45°F. There is no minimum
mixed−air temperature limitation during second−stage heating. For entering−air temperatures below 45°F both stages of heat must be
energized together to minimize condensation issues and ensure proper unit operation.
AIR QUALITY LIMITS (Cooling)
UNIT PGE
180
210
240
300
MINIMUM CFM
4500
5400
6000
7000
MAXIMUM CFM
7,500
9,000
10,000
11,250
COOLING OPERATION
LOW OUTDOOR TEMPERATURE OPERATING LIMITS (F)
UNIT PGE
All − Standard Unit
180 and 210 with Low Ambient Kit
240 and 300 with Low Ambient Kit
All with Head Pressure Control
6
TEMPERATURE
40
10
25
−20
Specifications subject to change without notice.
521 21 1001 04
OPTIONS AND ACCESSORIES − PGE072−150
ITEM
High Static Motors and Drives
Compressor Cycle Delay
Economizer with Controller
Electronic Programmable Thermostat**
Indoor Air Quality (CO2) Sensor (For Return Air)
Manual Outdoor-Air Damper
Low Ambient Kits
Outdoor Air Enthalpy Sensor
Outdoor Coil Grille
Outdoor Coil Hail Guard Assembly
Outdoor Air/Return Air Temperature Sensor
Power Exhaust with Barometric Relief
Return Air Enthalpy Sensor
Return Air Temperature Sensor
Roof Curbs (Vertical and Horizontal Discharge)
Thermostats and Subbases**
Thru-the-Bottom Utility Connections
Natural to LP Conversion Kit
OPTION*
X
X
X
ACCESSORY{
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
OPTIONS AND ACCESSORIES − PGE 180−300
ITEM
High Static Motors and Drives
Compressor Cycle Delay
Barometric Relief Damper (Not for use with horizontal roof curb)
Economizer with Controller
Electronic Programmable Thermostat**
Horizontal Adapter Curb
Indoor Air Quality (CO2) Sensor
Manual Outdoor-Air Damper
Low Ambient Kit
Outdoor Air Enthalpy Sensor
Power Exhaust without Barometric Relief
Return Air Enthalpy Sensor
Return Air Temperature Sensor
Roof Curbs (Vertical and Horizontal Discharge)
Thermostats and Subbases **
Winter Start Time Delay
Natural to LP Conversion Kit
*Factory−installed.
{Field−installed.
**Available through FAST Parts.
OPTION*
X
X
X
ACCESSORY{
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
NOTES:
1. Refer to unit specifications or contact your local representative for
accessory and option package information.
2. Some options may increase product lead times.
OPTIONS AND ACCESSORIES
Roof Curbs (Horizontal and Vertical) permit installation and Thru−The−Bottom Utility Connectors permit electrical connections
securing of ductwork to curb prior to mounting unit on the curb. 8 inch, to be brought to the unit through the basepan. Connectors are
14 inch, and 24 inch roof curbs are available as field−installed available as field−installed accessories.
accessories.
Power Exhaust accessory will provide system exhaust of up to 100%
Economizer is available as a factory−installed option in vertical
supply/return configuration only for unit sizes 072−150. Vertical or of return air (vertical only). The power exhaust is a field−installed
horizontal configuration is available for unit sizes 180−300. accessory (separate vertical and horizontal design).
(Economizer is available as a field−installed accessory for horizontal
and/or vertical supply return configurations.)
Manual Outdoor−Air Damper accessory can be preset to admit up
to 50% outdoor air for year round ventilation and is available as a
field−installed accessory.
Low Ambient Pressure Control accessory package maintains
condensing temperature between 90°F and 110°F at outdoor ambient
temperatures down to −20°F by condenser−fan speed modulation or
condenser−fan cycling and wind baffles.
Convenience Outlet can be installed and internally mounted with
easily accessible 115v female receptacle. Requires separate field
supplied power source.
Compressor Cycle Delay accessory prevents unit from restarting for
minimum of 5 minutes after shutdown.
521 21 1001 04
Specifications subject to change without notice.
7
ACCESSORIES − PGE072−300
FLAT ROOF CURBS
Model Number
Height
Use With Model Size
AXB035CLA
8” High Roof Curb
072
AXB035CMA
14” High Roof Curb
072
AXB035CHA
24” High Roof Curb
072
AXB045CLA
8” High Roof Curb
090−150
AXB045CMA
14” High Roof Curb
090−150
AXB045CHA
24” High Roof Curb
090−150
AXB060CMA
14” Vertical Roof Curb
180−240
AXB060CHA
24” Vertical Roof Curb
180−240
AXB065CHA
24” Horizontal Roof Curb
180−240
AXB165CHA
24” Horizontal Roof Curb with transition duct
180−240
AXB090CMA
14” Vertical Discharge Roof Curb
300
AXB090CHA
24” Vertical Discharge Roof Curb
300
AXB095CHA
24” Horizontal Roof Curb
300
AXB195CHA
24” Horizontal Roof Curb with transition duct
300
Model Number
Description
Use With Model Size
DNECOMZR020A02
Vertical − with W7212 controller
072
DNECOMZR021A02
Vertical − with W7212 controller
090−150
DNECOMZR024A02
Horizontal − with W7212 controller
072
DNECOMZR025A02
Horizontal − with W7212 controller
090−150
ECONOMIZERS
DNECOMZR008C00
Vertical or Horizontal − with W7212 controller
ALTERNATE ECONOMIZERS
Model Number
Description
AXB035EMA
Fully Modulating Economizer − Downflow
AXB035EPA
Three Position Economizer − Downflow
AXB035HEA
Fully Modulating Economizer − Horizontal
AXB035HPA
Three Position Economizer − Horizontal
AXB145EMA
Fully Modulating Economizer − Downflow
AXB245EMA
Fully Modulating Economizer − Downflow
AXB145EPA
Three Position Economizer − Downflow
AXB245EPA
Three Position Economizer − Downflow
AXB145HEA
Fully Modulating Economizer − Horizontal
AXB245HEA
Fully Modulating Economizer − Horizontal
AXB145HPA
Three Position Economizer − Horizontal
AXB245HPA
Three Position Economizer − Horizontal
AXB060EMA
Fully Modulating Economizer − Horizontal/Downflow
AXB060EPA
Three Position Economizer − Horizontal/Downflow
180−300
P*E Model Size
072
072
072
072
90,102
120,150
90,102
120,150
90,102
120,150
90,102
120,150
180 − 300
180 − 300
DAMPERS
Model Number
Description
Use With Model Size
DNMANDPR001A03
50% Open
072
DNMANDPR002A03
DNBARREL001A00
ALTERNATE DAMPERS
AXB035FAA
AXB035FMA
AXB145FAA
AXB245FAA
AXB145FMA
AXB245FMA
AXB060FMA
50% Open
Barometric Relief Damper
090−150
180−300
Manual Fresh Air Damper
Motorized Fresh Air Damper
Fresh Air Damper − 35% Manual
Fresh Air Damper − 35% Manual
Fresh Air Damper − 35% Motorized
Fresh Air Damper − 35% Motorized
Fresh Air Damper − 35% Motorized
072
072
90,102
120,150
90,102
120,150
180 − 300
8
Specifications subject to change without notice.
521 21 1001 04
ACCESSORIES − PGE072−300
POWER EXHAUST
Model Number
Description
Use With Model Size
DNPWREXH030A01
208/230−3−60, Vertical
072
DNPWREXH021A01
460−3−60, Vertical
072
DNPWREXH022A01
208/230−3−60, Vertical
090−150
DNPWREXH023A01
460−3−60, Vertical
090−150
DNPWREXH028A01
208/230−3−60, Horizontal
072−150
DNPWREXH029A01
460−3−60, Horizontal
DNPWREXH008B00
Power Exhaust 460 volt (field convertiable to 208/230 volt)
DNPWREXH010B00
Power Exhaust 575 volt
ALTERNATE POWER EXHAUST
AXB035PEH
Power Exhaust 208/230 volt
AXB035PEL
Power Exhaust 460 volt
AXB035PES
Power Exhaust 575 volt
AXB145PEH
Power Exhaust 208/230 volt
AXB145PEL
Power Exhaust 460 volt
AXB145PES
Power Exhaust 575 volt
AXB245PEH
Power Exhaust 208/230 volt
AXB245PEL
Power Exhaust 460 volt
AXB245PES
Power Exhaust 575 volt
AXB060PEH
Power Exhaust 208/230 volt
AXB060PEL
Power Exhaust 460 volt
AXB060PES
Power Exhaust 575 volt
072−150
180 − 240
180 − 240
072
072
072
090, 102
090, 102
090, 102
120, 150
120, 150
120, 150
180 − 300
180 − 300
180 − 300
LOW AMBIENT CONTROLS
Model Number
AXB035LAA
AXB045LAA
Description
Low Ambient Kit (0 Deg. F)
Low Ambient / OFM Sequencing Kit (−20 Deg. F) 208/230v
Use With Model Size
072 − 150
090 − 150
AXB160LAA
OFM Sequencing kit (3 fans)
180, 210, 300
AXB260LAA
DNLOWAMB002A01
25_F Low Ambient Kit
Low Ambient Kit (25 Deg. F)
240
240
DNLOWAMB015A00
208/230V Motor Controller (−20_F)
240
DNLOWAMB016A00
460V Motor Controller (−20_F)
240
DNLOWAMB017A00
575V Motor Controller (−20_F)
240
WINTER START KIT
Model Number
Description
Use With Model Size
DNWINSTR001A00
Low pressure switch bypass (time delay)
ALL
PHASE MONITOR CONTROL
Model Number
Description
Use With Model Size
DNPHASE3001A01
Electronic phase monitor breaks “R” control signal if
trouble is detected
ALL
THROUGH−THE−BOTTOM/CURB POWER CONNECTION
Model Number
Description
DNBTMPWR001A01
Thru−the bottom electrical + thru−the curb Gas
072
DNBTMPWR002A01
Thru−the bottom electrical + thru−the curb Gas
090−150
DNBTMPWR003A01
AXB045PKA
Thru−the bottom electrical and Gas
Thru−the−bottom electrical and Gas
072
090 − 150
521 21 1001 04
Specifications subject to change without notice.
Use With Model Size
9
ACCESSORIES − PGE072−300 (cont.)
ECONOMIZER SENSORS
Model Number
Description
Use With Model Size
DNTEMPSN002A00
Single Temp’ (dry bulb) Control
ALL Economizers With W7212 Controller
DNCBDIOX005A00
CO2 Sensor
ALL Economizers With W7212 Controller
DNENTDIF004A00
AXB078ENT
Return Air Enthalpy Sensor
Enthalpy Control
ALL Economizers With W7212 Controller
ALL
Model Number
Description
Use With Model Size
DNTIMEGD001A00
Five minute compressor delay
ALL
Model Number
Description
Use With Model Size
AXB035LPA
Natural to LP
072
AXB345LPA
Natural to LP
090−150
DNLKIT7002A00
Natural to LP
210−300
Model Number
Description
Use With Model Size
AXB036HGA
Hail Guard
072
AXB145CGA
Coil Guard
090, 102
AXB145HGA
Hail Guard
090, 102
AXB245CGA
Coil Guard
120, 150
AXB245HGA
Hail Guard
120, 150
AXB060CGA
Coil Guard
180−240
AXB060HGA
Hail Guard
180−240
AXB090CGA
Coil Guard
300
AXB090HGA
Hail Guard
300
ANTI−CYCLE TIMER
LP GAS CONVERSION KITS
COIL PROTECTION
CONCENTRIC DIFFUSERS AND DUCT KITS
Model Number
Description
AXB035CTA
20” Round Concentric Duct Kit
AXB445CTA
20” Round Concentric Duct Kit
AXB545CTA
Concentric Duct Kit 18” x 28” Rect.
AXB645CTA
Concentric Duct Kit 18” x 32” Rect.
AXB160CTA
Concentric Duct Kit 18” x 36”
AXB260CTA
Concentric Duct Kit 24” x 48”
AXB030CFA
Concentric Diffuser − Flush Mount
AXB030CSA
Concentric Diffuser − Step Down
Concentric Diffuser − Flush Mount
AXB040CFA
Concentric Diffuser − Flush Mount (use with AXB445CTA)
Concentric Diffuser − Step Down
AXB040CSA
Concentric Diffuser − Step Down (use with AXB445CTA)
AXB045CFA
Concentric Diffuser − Flush Mount (use with AXB545CTA)
AXB045CSA
Concentric Diffuser − Step Down (use with AXB545CTA)
AXB050CFA
Concentric Diffuser − Flush Mount (use with AXB645CTA)
AXB050CSA
Concentric Diffuser − Step Down (use with AXB645CTA)
AXB055CFA
Concentric Diffuser − Flush Mount (use with AXB160CTA)
AXB055CSA
Concentric Diffuser − Step Down (use with AXB160CTA)
AXB058CFA
Concentric Diffuser − Flush Mount
AXB058CSA
Concentric Diffuser − Step Down
10
Specifications subject to change without notice.
P*E Model Size
072
090, 102
120
150
180, 210
240, 300
072
072
072
090, 102
072
090, 102
120
120
150
150
180, 210
180, 210
240, 300
240, 300
521 21 1001 04
PHYSICAL DATA − PGE072
UNIT SIZE: PGE
NOMINAL CAPACITY (tons)
OPERATING WEIGHT (lb)
Unit
Al/Cu*
COMPRESSOR
Type
Quantity
No. Cylinders (per Circuit)
Oil (oz)
REFRIGERANT TYPE
Expansion Device
Operating Charge (lb−oz)
Circuit 1 (first stage)
CONDENSER FAN
Nominal Cfm
Quantity...Diameter (in.)
Motor Hp...Rpm
Watts Input (Total)
CONDENSER COIL
Rows...Fins/in.
Total Face Area (sq ft)
EVAPORATOR FAN
Quantity...Size (in.)
Type Drive
Nominal Cfm
Maximum Continuous Bhp
Motor Frame Size
Nominal Rpm High/Low
Fan Rpm Range
Motor Bearing Type
Maximum Allowable Rpm
Motor Pulley Pitch Diameter Min/Max (in.)
Nominal Motor Shaft Diameter (in.)
Fan Pulley Pitch Diameter (in.)
Belt, Quantity...Type...Length (in.)
Pulley Center Line Distance (in.)
Speed Change per Full Turn of
Moveable Pulley Flange (rpm)
Movable Pulley Maximum Full Turns
From Closed Position
Factory Setting
Factory Speed Setting (rpm)
Fan Shaft Diameter at Pulley (in.)
EVAPORATOR COIL
Rows...Fins/in.
Total Face Area (sq ft)
521 21 1001 04
072
6
626
Scroll
1
2
60
R−22
Fixed Orifice Metering Device
11−0
Propeller Type
4100
1...22.0
1/4...1100
320
3/8” OD Enhanced Copper tubes, Aluminum Lanced Fins
2...17
16.5
Centrifugal Type
Std
1...10 x 10
High−Static
1...10 x 10
Std
Belt
High−Static
Belt
2100
Std
2.40
High−Static
2.90
Std
56
High−Static
56
Std
−
High−Static
1725
Std
1070−1460
High−Static
1300−1685
Ball
2100
Std
2.8/3.8
High−Static
3.4/4.4
Std
5/8
High−Static
7/8
Std
4.5
High−Static
4.5
Std
1...A...39
High−Static
1...A...40
Std
14.7−15.5
High−Static
14.7−15.5
Std
80
High−Static
60
Std
5
High−Static
5
Std
3
High−Static
3
Std
1226
High−Static
1416
5/8
3/8” OD Enhanced Copper tubes, Aluminum Double−Wavy Fins, Face Split
4...15
5.5
Specifications subject to change without notice.
11
PHYSICAL DATA − PGE072
UNIT SIZE: PGE
FURNACE SECTION
Rollout Switch Cutout Temp ††
Burner Orifice Diameter (In...drill size)
Natural Gas (Nominal Heating Size)
Liquid Propane (Nominal Heating Size)
072
195
Std
LoNox
LoNox
LoNox
Alt
Thermostat Heat Anticipator Setting (Amps)
208/230v and 575v Stage 1 / Stage 2
460v
Stage 1 / Stage 2
Gas Input (Btuh) Standard Units Stage 1/ Stage 2
(Nominal Heating Size)
Efficiency (Steady State) (%)
Temperature Rise Range
(74,000)
(115,000)
(150,000)
(74,000)
(150,000)
Manifold Pressure (in. wg)
Natural Gas
Std
Liquid Propane
Alt
Gas Valve Quantity
Gas Valve Pressure Range (Min−Max Allowable)
Psig
in. wg.
Field Gas Connection Size (in. FPT)
HIGH−PRESSURE SWITCH (psig)
Standard Compressor
Internal Relief (Differential)
Cutout
Reset (Auto)
LOW−PRESSURE SWITCH (psig)
Cutout
Reset (Auto)
FREEZE PROTECTION THERMOSTAT (F)
Opens
Closes
RETURN AIR FILTERS
Quantity... Size (in.)
LEGEND
(74,000)
(150,000)
(60,000)
(90,000)
(120,000)
(74,000)
(150,000)
.14
.14
74,000 / −
115,000 / −
120,000/150,000
80
15−45
50−80
3.5
3.5
1
0.180−0.470
5.0−13.0
1/2
500 50
428
320
73
22 7
30 5
45 5
Throwaway
2...16 x 25 x 2
Al − Aluminum
Bhp − Brake Horsepower
Cu − Copper
*Evaporator coil fin material/condenser coil fin material.
††Rollout switch lockout is manually reset by interrupting power to
unit or resetting thermostat.
***Three−phase standard high heat models have heating input
values as shown.
12
.113...33
.129...30
−
−
−
.089...43
.104...37
NOTES:
1. An LP kit is available as an accessory. Kit may be used at
elevations as high as 2000 ft. LP kit is not used with Low NOx units.
Specifications subject to change without notice.
521 21 1001 04
PHYSICAL DATA − PGE090−150
UNIT SIZE: PGE
NOMINAL CAPACITY (tons)
OPERATING WEIGHT (lb)
Unit
Al/Cu*
COMPRESSOR
Type
Quantity
No. Cylinders (per Circuit)
Oil (oz)
REFRIGERANT TYPE
Expansion Device
Operating Charge (lb−oz)
Circuit 1 (first stage)
Circuit 2 (second stage)
CONDENSER FAN
Nominal Cfm
Quantity...Diameter (in.)
Motor Hp...Rpm
Watts Input (Total)
CONDENSER COIL
Rows...Fins/in.
Total Face Area (sq ft)
EVAPORATOR FAN
Quantity...Size (in.)
Type Drive
Nominal Cfm
Maximum Continuous Bhp
Motor Frame Size
Fan Rpm Range
Motor Bearing Type
Maximum Allowable Rpm
Motor Pulley Pitch Diameter Min/Max (in.)
Nominal Motor Shaft Diameter (in.)
Fan Pulley Pitch Diameter (in.)
Belt, Quantity...Type...Length (in.)
Pulley Center Line Distance (in.)
Speed Change per Full Turn of
Moveable Pulley Flange (rpm)
Movable Pulley Maximum Full Turns
From Closed Position
Factory Setting
Factory Speed Setting (rpm)
Fan Shaft Diameter at Pulley (in.)
EVAPORATOR COIL
Rows...Fins/in.
Total Face Area (sq ft)
521 21 1001 04
090
7
102
8
120
10
150
12
881
896
1057
1077
Reciprocating
2
2
42
2
2
53
Scroll
2
2
50
2
2
60
R−22
Fixed Orifice Metering Device
7−10
8−2
Std
High−Static
Std
High−Static
Std
High−Static
Std
High−Static
Std
High−Static
Std
High−Static
Std
High−Static
Std
High−Static
Std
High−Static
Std
High−Static
Std
High−Static
Std
High−Static
Std
High−Static
Std
High−Static
7−14
8−10
9−8
8−5
8−8
9−5
Propeller Type
6500
6500
7000
7000
2...22.0
2...22.0
2...22.0
2...22.0
1/4...1100
1/4...1100
1/4...1100
1/4...1100
650
650
650
650
3/8” OD Enhanced Copper tubes, Aluminum Lanced Fins
2...17
2...17
2...17
2...17
20.50
20.50
25.00
25.00
Centrifugal Type
1...15 x 15
1...15 x 15
1...15 x 15
1...15 x 15
1...15 x 15
−
1...15 x 15
1...15 x 15{
Belt
Belt
Belt
Belt
Belt
Belt
Belt
Belt{
2900
3000
3200
5000
2.40
2.40
2.40
3.70
3.70
3.70
5.25
5.25{
56
56
56
56
56
56
56
56{
590−840
685−935
685−935
860−1080
860−1080
860−1080
830−1130
830−1130{
Ball
Ball
Ball
Ball
1500
1500
1500
1500
2.4/3.4
2.8/3.8
2.8/3.8
4.0/5.0
4.0/5.0
4.0/5.0
2.8/3.8
3.1/4.1{
5/8
5/8
5/8
7/8
7/8
7/8
7/8
7/8{
7.0
7.0
7.0
8.0
8.0
8.0
5.8
5.9{
1...A...48
1...A...48
1...A...49
1...A...53
1...A...53
1...A...53
1...BX...48
1...BX...48 {
16.75−19.25
16.75−19.25
15.85−17.50
15.85−17.50
16.75−19.25
16.75−19.25
15.85−17.50
15.85−17.50{
50
50
50
44
60
60
60
50{
5
5
5
5
5
5
6
6{
5
5
5
5
5
5
5
5{
590
685
685
860
860
860
887
887{
1
1
1
1
3/8” OD Enhanced Copper tubes, Aluminum Double−Wavy Fins, Face Split
3...15
8.9
Specifications subject to change without notice.
3...15
8.9
3...15
10.0
4...15
11.1
13
PHYSICAL DATA − PGE090−150
UNIT SIZE: PGE
FURNACE SECTION
Rollout Switch Cutout Temp ††
Burner Orifice Diameter (In...drill size)
Natural Gas (Nominal Htg Size) Std
Liquid Propane (Nominal Htg Size) Alt
Thermostat Heat Anticipator Setting
(Amps)
208/230v and 575v Stage 1 / Stage 2
460v
Stage 1 / Stage 2
Gas Input (Btuh) Stage 1 / Stage 2
(Nominal Htg Size) Stage 1 / Stage 2
Stage 1 / Stage 2
Stage 1 / Stage 2
Efficiency (Steady State) (%)
Temperature Rise Range
(Nominal Htg Size)
Manifold Pressure (in. wg)
Natural Gas
Std
Liquid Propane
Alt
Gas Valve Quantity
Gas Valve Pressure Range
(Min−Max Allowable) Psig/ in. wg.
Field Gas Connection Size (in. FPT)
(Nominal Htg Size)
HIGH−PRESSURE SWITCH (psig)
Standard Compressor
Internal Relief (Differential)
Cutout
Reset (Auto)
LOW−PRESSURE SWITCH (psig)
Cutout
Reset (Auto)
FREEZE PROTECTION THERMOSTAT (F)
Opens
Closes
RETURN AIR FILTERS
Quantity... Size (in.)
LEGENDThrowaway
(125,000)
(180,000)
(224,000)
(250,000)
(125,000)
(180,000)
(224,000)
(250,000)
090
102
120
150
195
195
195
195
.120...31
.120...31
.120...31
−
.096...41
.096...41
.096...41
−
.120...31
.120...31
.120...31
−
.096...41
.096...41
.096...41
−
−
.120...31
.120...31
.120...31
−
.096...41
.096...41
.102...38
−
−
.120...31
.120...31
.120...31
.096...41
.102...38
.102...38
.14 / .20
.14 / .20
(125,000)
(180,000)
(224,000)
(250,000)
(125,000)
(180,000)
(224,000)
(125,000)
(180,000)
(224,000)
(250,000)
125,000/ −
120,000/180,000
180,000/224,000
−
80
20−50
35−65
45−75
125,000/ −
120,000/180,000
180,000/224,000
−
80
20−50
35−65
45−75
−
120,000/180,000
180,000/224,000
250,000/250,000
80
35−65
35−65
40−70
−
−
180,000/224,000
250,000/250,000
80
35−65
40−70
−
3.5
3.5
1
3.5
3.5
1
3.5
3.5
1
3.5
3.5
1
1/2
3/4
3/4
−
0.180−0.470 / 5.0−13.0
1/2
−
3/4
3/4
3/4
3/4
−
3/4
−
−
3/4
3/4
450 50
500 50
428
320
73
22 7
Throwa
way
2...16 x 20 x 2
30 5
45 5
Throwaway
4...20 x 20 x 2
Throwaway
Al − Aluminum
Bhp − Brake Horsepower
Cu − Copper
*Evaporator coil fin material/condenser coil fin material. Contact your
local representative for details about coated fins.
†Alternate drive package for size 150.
††Rollout switch lockout is manually reset by interrupting power to unit
or resetting thermostat.
14
Specifications subject to change without notice.
521 21 1001 04
Economizer
PGE072
Economizer
Economizer
For Economizer
DNRBTMPWR001A01
Threaded
Economizer
BASE UNIT DIMENSIONS − PGE072
521 21 1001 04
Specifications subject to change without notice.
15
BASE UNIT DIMENSIONS − PGE090−150
”
3
/8
All measurements in inches (mm)
”
Alternate
Condensate
Drain opening
(2219)
Corner B
CONDENSER COIL
5
1
/2
(C)
Return Air
TOP
D
E
F
G
H
I
J
K
EVAPORATOR
Center Of
Opening
”
Gravity
36
23
1
/
4
3
/
4
”
(933)
”
28 3 / 4
(591)
1
”
1
”
40 / 4
(1022)
42 / 4
(1073)
4
11
/ 16
”(119)
5
1 / 16
(49)
1-3/8” Dia (35) Field Power Supply Hole
2-1/2“ Dia (64) Power Supply Knockout
1-3/4” Dia (44) Charging Port Hole
7/8” Dia (22) Field Control Wiring Hole
3/4” - 14 NPT Condensate Pan
2” Dia (51) Power Supply Knockout
3/4” - 14 NPT Gas Connection
26-7/16” (090 Model) 34-7/16” (120&150 Models)
(730)
7/
16
5
/
25 16
(643)
(A)
3
(D)
” (138)
13
/ 16
1
/
8
” (79)
”
” (97)
RIGHT SIDE
(E)
(I)
7 5/16
5
(B)
3/
24
(F)
28 / 16
(719)
8”
”
(619)
(G)
7
”
13 / 8
(352)
9
4 / 16
(116)
”
5
3
7 /8
(187)
3
/
4
”
Horizontal
11/ ” (144)
5-16
1/ ” (195)
7-16
Condensate Drain (H)
”
(940)
12
5
/
8
”(321)
4” (102)
(K)
Indoor Blower
Access Panel
Control Box /
Compressor
Access Panel
”
(C)
”(146)
BACK
FRONT
(186)
Supply opening
37
8 7 / 16
PGE090 −−150
”
”
LEFT SIDE
7/8” (22)
1-1/8” (28.4)
1-3/4” (44.4)
14
(356)
3
15
24
Power*
Power*
BASE UNIT WEIGHT AND DIMENSIONS
Corner C
Corner D
”
USE
Connection Sizes
8”
5
/
Ve r t i c a l
4
(1467)
COIL
Supply Air
/
(321) 12
REQUIRED HOLE
SIZES (MAX)
WIRE
* Select either 3/4” or 1−−1/4” for power,
depending on wire size.
” (140)
Vertical Opening
CONDENSER COIL
3
1/2”
3/4”
1-1/4” FPT
In Basepan
Corner A
57
THREADED
CONDUIT SIZE
9/ ”
3−−
16
(90)
Horizontal
Return Air Opening
42 15 / 16
(1091)
87
(J)
3
5
/ 16
Filter Access Panel
”
Blockoff Panel
3
/
8
(10)
16
”
”
36
(914)
Specifications subject to change without notice.
521 21 1001 04
PERFORMANCE DATA − PGE072−150 (cont.)
COOLING CAPACITIES
PGE072 (6 TONS)
Temp (F)
Air Entering
Condenser
(Edb)
TC
75
SHC
kW
TC
85
SHC
kW
TC
95
SHC
kW
TC
SHC
105
kW
TC
SHC
115
kW
1800/0.06
72
81.3
38.2
4.69
78.8
37.7
5.21
77.1
37
5.8
75.4
36.7
6.49
72.1
35.3
7.2
67
77.8
51.3
4.63
75.6
50.4
5.16
73.3
49.9
5.78
70.7
48.7
6.45
67.9
47.5
7.17
62
71.3
61.6
4.52
69
60.5
5.05
66.9
59.7
5.65
62.9
58.2
6.26
59
57.2
6.94
72
82.7
40.2
4.73
81.1
40
5.27
79.2
39.4
5.87
76.6
38.6
6.53
73.6
37.6
7.25
Air Entering Evaporator − Cfm/BF
2100/0.07
2400/0.09
Air Entering Evaporator − Ewb (F)
67
62
72
67
78.7
72.9
84.2
79.7
54.2
65.9
42.3
57.1
4.65
4.56
4.77
4.67
77.1
70.7
83.3
78.6
53.9
64.9
42.2
57.5
5.2
5.09
5.34
5.24
74.8
68.5
81.3
76.2
53.3
64
41.8
56.8
5.81
5.7
5.94
5.85
72.1
64.8
77.9
73.4
52.3
62.2
40.6
55.9
6.48
6.32
6.56
6.51
69
61.1
75.2
70.1
51.2
60.2
39.9
54.8
7.18
7.01
7.29
7.2
3000/0.11
62
74.6
70.2
4.6
72.3
69.2
5.13
70.1
68.3
5.74
66.7
66.3
6.38
63.3
63.3
7.08
72
85.3
43.7
4.8
85
44.3
5.39
82
43.5
5.95
79.7
43
6.61
76.7
42.2
7.35
67
82.5
64
4.75
80.5
63.6
5.29
78
63.4
5.88
74.9
62.4
6.53
71.9
61.5
7.26
62
76.7
76.4
4.63
75
74.9
5.17
73.3
73.2
5.8
70.9
70.9
6.46
68.1
68.1
7.15
PGE090 (71/2 TONS)
Temp (F)
Air Entering
Condenser
(Edb)
TC
SHC
75
kW
TC
SHC
85
kW
TC
SHC
95
kW
TC
SHC
105
kW
TC
SHC
115
kW
2250/0.10
72
105.8
50.9
6.34
101.1
49.4
6.80
96.6
47.8
7.26
91.0
45.9
7.70
85.2
43.9
8.13
PGE102 (81/2 TONS)
Temp (F)
Air Entering
Condenser
(Edb)
75
85
95
105
115
125
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
72
117.7
55.7
6.42
113.8
54.3
7.35
109.6
52.9
8.37
105.6
51.4
9.49
100.4
49.4
10.63
95.8
48.0
11.97
521 21 1001 04
67
97.6
63.6
6.05
92.9
62.0
6.51
87.7
59.9
6.96
82.1
57.9
7.37
76.0
55.4
7.79
62
88.7
75.4
5.77
84.0
73.3
6.21
78.9
70.8
6.64
72.9
67.9
7.08
67.9
65.1
7.47
72
108.9
54.1
6.46
104.8
53.1
6.94
99.9
51.7
7.42
93.7
49.6
7.81
87.7
47.8
8.25
Air Entering Evaporator− Cfm/BF
2800/0.11
3000/0.11
Air Entering Evaporator − Ewb (F)
67
62
72
67
101.1
92.6
109.5
101.9
69.8
84.0
55.2
71.9
6.19
5.93
6.50
6.25
96.4
87.7
105.6
97.2
68.4
81.9
54.4
70.6
6.66
6.37
6.98
6.69
91.0
82.4
100.5
91.6
66.5
79.5
52.9
68.8
7.10
6.78
7.46
7.14
85.2
76.8
94.3
85.9
64.4
76.4
50.9
66.7
7.51
7.22
7.86
7.54
79.1
71.6
88.1
79.7
62.2
71.6
49.2
64.4
7.92
7.67
8.29
7.95
3750/0.14
62
93.5
86.5
5.96
88.5
84.4
6.41
83.6
81.3
6.83
78.2
77.8
7.28
73.1
73.1
7.74
72
112.4
59.9
6.62
107.7
58.5
7.08
102.3
57.2
7.54
96.6
55.8
7.97
90.2
54.4
8.41
67
104.6
79.7
6.37
99.6
78.2
6.82
93.9
76.6
7.24
87.9
74.5
7.67
81.7
72.5
8.08
62
96.4
94.9
6.09
92.2
92.0
6.57
87.7
87.7
7.03
83.0
83.0
7.47
78.2
78.0
7.93
Air Entering Evaporator − Cfm/BF
2550/0.08
3000/0.09
3400/0.11
4250/0.13
Air Entering Evaporator − Ewb
67
104.1
64.7
6.34
100.4
63.3
7.26
96.2
61.9
8.27
92.1
60.4
9.37
87.9
58.6
10.56
83.0
56.8
11.83
62
93.4
76.6
6.26
89.2
75.0
7.17
85.3
73.1
8.16
81.3
71.6
9.27
76.8
69.6
10.46
72.0
67.5
11.61
72
121.3
59.3
6.46
117.9
58.0
7.41
113.3
56.5
8.42
108.8
55.2
9.55
103.1
52.9
10.70
98.5
51.6
12.02
67
107.5
70.6
6.38
103.8
69.4
7.31
99.7
67.9
8.33
95.2
66.4
9.44
90.4
64.7
10.62
85.5
62.9
11.89
62
97.2
85.0
6.30
93.4
83.8
7.24
89.2
81.7
8.24
84.6
80.0
9.34
80.3
78.3
10.55
74.9
74.9
11.73
Specifications subject to change without notice.
72
122.9
61.3
6.47
119.6
60.4
7.43
115.4
59.1
8.46
110.4
57.5
9.57
105.1
55.8
10.74
99.8
54.0
12.05
67
109.0
74.7
6.39
105.3
73.4
7.33
101.1
71.9
8.34
96.4
70.3
9.45
91.7
68.5
10.62
86.6
66.9
11.92
62
98.7
91.4
6.33
94.7
89.1
7.24
90.3
87.3
8.22
86.3
85.3
9.35
82.1
81.9
10.54
77.5
77.5
11.80
72
124.4
66.8
6.50
122.1
65.2
7.46
118.3
64.0
8.51
113.2
62.5
9.61
107.6
60.6
10.80
101.4
58.2
12.09
67
111.1
82.1
6.41
107.5
81.7
7.37
103.2
80.3
8.40
98.4
78.3
9.49
93.5
76.6
10.68
88.2
74.6
11.97
17
62
101.8
99.7
6.35
97.2
97.0
7.28
93.1
8.31
89.1
89.1
9.41
85.0
10.58
80.7
80.7
11.86
PERFORMANCE DATA − PGE072−150 (cont.)
COOLING CAPACITIES
PGE120 (10 TONS)
Temp (F)
Air Entering
Condenser
(Edb)
TC
SHC
75
kW
TC
SHC
85
kW
TC
SHC
95
kW
TC
SHC
105
kW
TC
SHC
115
kW
3000/0.095
72
138.2
68.0
8.37
132.3
65.5
8.92
126.3
63.3
9.54
120.2
61.5
10.23
117.1
60.5
10.51
67
127.0
84.1
8.07
121.7
81.9
8.63
115.7
79.8
9.24
106.5
76.2
9.87
99.8
73.7
10.13
Air Entering Evaporator − Cfm/BF
4000/0.125
Air Entering Evaporator − Ewb (F)
62
72
67
62
72
114.0
145.0
132.9
122.0
149.1
99.1
74.5
95.1
114.7
81.1
7.80
8.57
8.24
7.95
8.72
105.9
138.4
127.2
116.6
142.5
95.5
72.4
93.3
112.2
78.9
8.35
9.15
8.81
8.52
9.29
98.4
131.8
121.0
108.8
135.2
91.6
70.3
91.4
107.8
76.2
8.91
9.75
9.42
9.11
9.87
89.5
124.9
113.8
100.3
128.3
86.7
68.1
89.3
100.3
74.4
9.51
10.40
10.06
9.78
10.52
85.7
122.2
105.7
95.1
124.8
84.9
67.6
86.3
95.1
74.1
9.77
10.70
10.34
10.10
10.80
5000/0.15
67
136.6
106.3
8.36
130.2
103.6
8.92
124.2
101.9
9.55
117.2
100.1
10.19
111.8
98.6
10.46
62
125.9
125.3
8.07
120.9
120.8
8.65
116.1
116.0
9.28
109.9
109.9
9.99
104.6
104.6
10.29
PGE150 (121/2 TONS)
Temp (F)
3750/0.08
Air Entering
Condenser
(Edb)
72
67
TC
164.6
152.0
SHC
81.3
101.9
75
kW
10.24
9.96
TC
159.9
147.1
SHC
79.7
99.9
85
kW
11.38
11.05
TC
154.2
141.5
SHC
77.9
98.0
95
kW
12.59
12.26
TC
147.8
134.2
SHC
75.4
95.2
105
kW
13.84
13.48
TC
139.7
120.4
SHC
72.5
89.8
115
kW
15.03
14.70
TC
130.5
107.0
SHC
69.8
84.4
125
kW
16.32
15.91
LEGEND
Shaded Areas = Standard Ratings
BF −
Bypass Factor
Edb − Entering Dry−Bulb
Ewb − Entering Wet−Bulb
62
139.9
121.7
9.71
133.6
119.1
10.82
124.4
114.8
11.95
114.0
109.5
13.12
102.8
102.6
14.34
92.5
92.4
15.67
72
167.3
84.5
10.31
162.6
83.1
11.45
157.2
81.8
12.68
150.7
79.6
13.92
142.1
76.7
15.12
132.8
73.7
16.43
Air Entering Evaporator − Cfm/BF
4300/0.09
5000/0.11
Air Entering Evaporator − Ewb
67
62
72
67
62
72
155.3
142.6
170.9
158.2
146.2
173.9
108.1
130.0
88.9
115.9
139.8
96.7
10.05
9.78
10.42
10.12
9.84
10.50
150.2
137.4
166.3
153.0
141.3
169.5
106.3
128.0
88.3
114.1
137.7
96.1
11.14
10.87
11.58
11.20
10.97
11.66
144.6
129.3
159.9
147.6
134.5
164.0
104.5
124.1
86.3
112.5
133.8
94.4
12.36
12.04
12.75
12.44
12.15
12.88
137.2
119.1
153.3
140.4
136.4
156.4
101.9
118.2
84.4
110.6
126.5
92.2
13.58
13.24
14.01
13.69
13.37
14.06
124.2
109.1
145.5
127.5
117.1
148.4
97.0
109.1
82.1
105.7
116.6
90.4
14.80
15.24
15.24
14.90
14.65
15.35
109.7
135.5
135.5
112.7
105.0
138.2
91.5
99.2
79.0
99.9
104.9
87.7
16.00
15.79
16.52
16.11
15.97
16.59
kW −
Compressor Motor Power Input
Ldb − Leaving Dry−Bulb
Lwb − Leaving Wet−Bulb
SHC − Sensible Heat Capacity (1000 Btuh) Gross
TC −
Total Capacity (1000 Btuh) Gross
6250/0.13
67
162.0
128.7
10.23
156.8
127.4
11.32
150.9
125.8
12.54
143.7
124.0
13.80
133.2
120.1
15.04
121.1
114.6
16.21
62
151.0
150.8
9.95
147.1
146.9
11.08
142.3
142.2
12.31
136.7
136.6
13.58
128.1
128.0
14.86
118.3
118.3
16.10
NOTES:
1. Direct interpolation is permissible. Do not extrapolate.
2. The following formulas may be used:
tldb =tedb – sensible capacity (Btuh)
1.10 x cfm
tlwb = Wet−bulb temperature corresponding to enthalpy of air leaving indoor coil (hlwb)
hlwb = hewb – total capacity (Btuh)
4.5 x cfm
Where: hewb = Enthalpy of air entering evaporator coil
3. The SHC is based on 80°F edb temperature of air entering indoor coil. Below 80°F edb, subtract (corr factor x cfm) from SHC. Above 80°F edb, add (corr
factor x cfm) to SHC.
ENTERING AIR DRY−BULB TEMP (°F)
BYPASS
FACTOR
(BF)
79
81
78
82
.05
.10
.20
.30
1.04
.98
.87
.76
2.07
1.96
1.74
1.53
18
77
83
76
75
84
85
Correction Factor
3.11
4.14
5.18
2.94
3.92
4.90
2.62
3.49
4.36
2.29
3.05
3.82
under 75
over 85
Use formula
shown at right.
Interpolation is permissible.
Correction Factor = 1.10 x (1−BF) x (edb−80).
Specifications subject to change without notice.
521 21 1001 04
PERFORMANCE DATA − PGE072−150 (cont.)
FAN PERFORMANCE VERTICAL DISCHARGE UNITS
PGE072 (6 TONS) − STANDARD MOTOR (BELT DRIVE)*
Airflow
(Cfm)
External Static Pressure (in. wg)
0.2
0.4
0.6
0.8
1.0
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
1800
967
0.65
579
1077
0.81
718
1172
0.96
856
1257
1.12
993
1334
1.27
Watts
1130
1900
1007
0.75
663
1115
0.91
811
1208
1.08
957
1291
1.24
1101
1368
1.40
1246
2000
1048
0.85
757
1153
1.03
913
1244
1.20
1066
1326
1.37
1219
1401
1.54
1371
2100
1090
0.97
859
1191
1.15
1023
1281
1.33
1185
1361
1.51
1345
1435
1.69
1505
2200
1131
1.09
970
1230
1.29
1143
1318
1.48
1313
1397
1.67
1481
1470
1.86
1649
2300
1173
1.23
1091
1269
1.43
1273
1355
1.63
1451
1433
1.83
1627
1505
2.03
1803
2400
1215
1.38
1223
1309
1.59
1413
1393
1.80
1600
1470
2.01
1784
1540
2.21
1967
2500
1258
1.54
1365
1349
1.76
1564
1431
1.98
1759
1506
2.20
1951
−
−
−
2600
1300
1.71
1518
1389
1.94
1726
1470
2.17
1929
1544
2.40
2130
−
−
−
2700
1343
1.90
1683
1430
2.14
1899
1509
2.38
2111
−
−
−
−
−
−
2800
1386
2.09
1860
1471
2.35
2085
−
−
−
−
−
−
−
−
−
2900
1429
2.31
2050
−
−
−
−
−
−
−
−
−
−
−
−
3000
−
−
−
−
−
−
−
−
−
−
−
−
−
−
−
PGE072 (6 TONS) − STANDARD MOTOR (BELT DRIVE)* (cont)
Airflow
(Cfm)
External Static Pressure (in. wg)
1.2
1.4
1.6
1.8
2.0
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
1800
1406
1.43
1268
1473
1.58
1407
1535
1.74
1548
1595
1.90
1690
1652
2.06
1833
1900
1438
1.57
1391
1504
1.73
1537
1567
1.90
1685
1626
2.06
1833
1682
2.23
1983
2000
1471
1.72
1523
1536
1.89
1677
1598
2.06
1831
1657
2.24
1986
−
−
−
2100
1504
1.87
1665
1569
2.06
1825
1630
2.24
1986
−
−
−
−
−
−
2200
1538
2.04
1816
1602
2.23
1984
−
−
−
−
−
−
−
−
−
2300
1572
2.23
1978
−
−
−
−
−
−
−
−
−
−
−
−
2400
−
−
−
−
−
−
−
−
−
−
−
−
−
−
−
2500
−
−
−
−
−
−
−
−
−
−
−
−
−
−
−
2600
−
−
−
−
−
−
−
−
−
−
−
−
−
−
−
2700
−
−
−
−
−
−
−
−
−
−
−
−
−
−
−
2800
−
−
−
−
−
−
−
−
−
−
−
−
−
−
−
2900
−
−
−
−
−
−
−
−
−
−
−
−
−
−
−
3000
−
−
−
−
−
−
−
−
−
−
−
−
−
−
−
LEGEND
Bhp − Brake Horsepower
Watts − Input Watts to Motor
*Motor drive range: 1070 to 1460 rpm. All other rpms require
field−supplied drive.
521 21 1001 04
NOTES
1. Boldface indicates field−supplied drive required
2. Maximum continuous Bhp is 2.40
3. See General Notes for Fan Performance following this section
Specifications subject to change without notice.
19
PERFORMANCE DATA − PGE072−150 (cont.)
FAN PERFORMANCE VERTICAL DISCHARGE UNITS
PGE072 (6 TONS) − HIGH STATIC MOTOR (BELT DRIVE)*
Airflow
(Cfm)
External Static Pressure (in. wg)
0.2
0.4
0.6
0.8
1.0
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
1800
967
0.65
579
1077
0.81
718
1172
0.96
856
1257
1.12
993
1334
1.27
Watts
1130
1900
1007
0.75
663
1115
0.91
811
1208
1.08
957
1291
1.24
1101
1368
1.40
1246
2000
1048
0.85
757
1153
1.03
913
1244
1.20
1066
1326
1.37
1219
1401
1.54
1371
2100
1090
0.97
859
1191
1.15
1023
1281
1.33
1185
1361
1.51
1345
1435
1.69
1505
2200
1131
1.09
970
1230
1.29
1143
1318
1.48
1313
1397
1.67
1481
1470
1.86
1649
2300
1173
1.23
1091
1269
1.43
1273
1355
1.63
1451
1433
1.83
1627
1505
2.03
1803
2400
1215
1.38
1223
1309
1.59
1413
1393
1.80
1600
1470
2.01
1784
1540
2.21
1967
2500
1258
1.54
1365
1349
1.76
1564
1431
1.98
1759
1506
2.20
1951
1576
2.41
2142
2600
1300
1.71
1518
1389
1.94
1726
1470
2.17
1929
1544
2.40
2130
1613
2.62
2329
2700
1343
1.90
1683
1430
2.14
1899
1509
2.38
2111
1581
2.61
2320
1649
2.85
2527
2800
1386
2.09
1860
1471
2.35
2085
1548
2.60
2305
1619
2.84
2522
−
−
−
2900
1429
2.31
2050
1512
2.57
2283
1588
2.83
2512
−
−
−
−
−
−
3000
1473
2.54
2252
1553
2.81
2494
−
−
−
−
−
−
−
−
−
PGE072 (6 TONS) − HIGH STATIC MOTOR (BELT DRIVE)* (cont)
Airflow
(Cfm)
External Static Pressure (in. wg)
1.2
1.4
1.6
1.8
2.0
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
1800
1406
1.43
1268
1473
1.58
1407
1535
1.74
1548
1595
1.90
1690
1652
2.06
1833
1900
1438
1.57
1391
1504
1.73
1537
1567
1.90
1685
1626
2.06
1833
1682
2.23
1983
2000
1471
1.72
1523
1536
1.89
1677
1598
2.06
1831
1657
2.24
1986
1713
2.41
2142
2100
1504
1.87
1665
1569
2.06
1825
1630
2.24
1986
1688
2.42
2149
1744
2.60
2312
2200
1538
2.04
1816
1602
2.23
1984
1663
2.42
2152
1720
2.61
2321
1775
2.81
2491
2300
1572
2.23
1978
1635
2.42
2153
1695
2.62
2328
1753
2.82
2504
−
−
−
2400
1607
2.42
2150
1669
2.63
2332
1729
2.83
2515
−
−
−
−
−
−
2500
1642
2.63
2333
1704
2.84
2523
−
−
−
−
−
−
−
−
−
2600
1677
2.85
2527
−
−
−
−
−
−
−
−
−
−
−
−
2700
−
−
−
−
−
−
−
−
−
−
−
−
−
−
−
2800
−
−
−
−
−
−
−
−
−
−
−
−
−
−
−
2900
−
−
−
−
−
−
−
−
−
−
−
−
−
−
−
3000
−
−
−
−
−
−
−
−
−
−
−
−
−
−
−
LEGEND
Bhp − Brake Horsepower
Watts − Input Watts to Motor
*Motor drive range: 1300 to 1685 rpm. All other rpms require
field−supplied drive.
20
NOTES
1. Boldface indicates field−supplied drive required
2. Maximum continuous Bhp is 2.90
3. See General Notes for Fan Performance following this section
Specifications subject to change without notice.
521 21 1001 04
PERFORMANCE DATA − PGE072−150 (cont.)
FAN PERFORMANCE VERTICAL DISCHARGE UNITS
PGE090 (71/2 TONS) − STANDARD MOTOR (BELT DRIVE)*
Airflow
(Cfm)
External Static Pressure (in. wg)
0.2
0.4
0.6
0.8
1.0
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
2250
513
0.54
505
595
0.76
713
665
1.01
940
728
1.27
1187
786
1.56
1453
2300
521
0.57
531
601
0.79
741
671
1.04
972
734
1.31
1222
791
1.60
1489
2400
535
0.63
584
615
0.86
802
684
1.11
1038
745
1.39
1293
802
1.68
1566
2500
551
0.69
642
628
0.93
866
696
1.19
1109
757
1.47
1369
813
1.77
1647
2550
558
0.72
673
635
0.97
900
702
1.23
1146
763
1.51
1409
818
1.81
1689
2600
566
0.76
705
642
1.00
935
709
1.27
1183
769
1.55
1450
824
1.86
1732
2700
582
0.83
771
656
1.08
1008
721
1.35
1263
781
1.65
1535
835
1.95
1823
2800
597
0.90
842
670
1.16
1086
734
1.44
1347
793
1.74
1625
847
2.06
1917
2900
613
0.98
918
684
1.25
1169
748
1.54
1436
805
1.84
1720
859
2.16
2019
3000
629
1.07
999
699
1.35
1256
761
1.64
1530
818
1.95
1820
871
2.28
2125
3100
645
1.16
1085
713
1.45
1349
775
1.75
1630
831
2.06
1925
883
2.40
2235
3200
662
1.26
1176
728
1.55
1448
788
1.86
1734
844
2.18
2036
−
−
−
3300
678
1.36
1272
743
1.66
1551
802
1.98
1845
857
2.31
2152
−
−
−
3400
694
1.47
1374
758
1.78
1660
816
2.10
1961
−
−
−
−
−
−
3500
711
1.59
1482
773
1.90
1775
831
2.23
2082
−
−
−
−
−
−
3600
727
1.71
1596
789
2.03
1896
845
2.37
2210
−
−
−
−
−
−
3700
744
1.84
1716
804
2.17
2023
−
−
−
−
−
−
−
−
−
3750
752
1.91
1778
812
2.24
2089
−
−
−
−
−
−
−
−
PGE090 (71/2 TONS) − STANDARD MOTOR (BELT DRIVE)* (cont)
Airflow
(Cfm)
External Static Pressure (in. wg)
1.2
1.4
1.6
1.8
2.0
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
2250
839
1.86
1735
889
2.18
2032
−
−
−
−
−
−
−
−
−
2300
844
1.90
1773
893
2.22
2073
−
−
−
−
−
−
−
−
−
2400
854
1.99
1855
903
2.32
2159
−
−
−
−
−
−
−
−
−
2500
865
2.08
1940
−
−
−
−
−
−
−
−
−
−
−
−
2550
870
2.13
1985
−
−
−
−
−
−
−
−
−
−
−
−
2600
875
2.18
2031
−
−
−
−
−
−
−
−
−
−
−
−
2700
886
2.28
2126
−
−
−
−
−
−
−
−
−
−
−
−
2800
897
2.39
2227
−
−
−
−
−
−
−
−
−
−
−
−
2900
−
−
−
−
−
−
−
−
−
−
−
−
−
−
−
3000
−
−
−
−
−
−
−
−
−
−
−
−
−
−
−
3100
−
−
−
−
−
−
−
−
−
−
−
−
−
−
−
3200
−
−
−
−
−
−
−
−
−
−
−
−
−
−
−
3300
−
−
−
−
−
−
−
−
−
−
−
−
−
−
−
3400
−
−
−
−
−
−
−
−
−
−
−
−
−
−
−
3500
−
−
−
−
−
−
−
−
−
−
−
−
−
−
−
3600
−
−
−
−
−
−
−
−
−
−
−
−
−
−
−
3700
−
−
−
−
−
−
−
−
−
−
−
−
−
−
−
3750
−
−
−
−
−
−
−
−
−
−
−
−
−
−
−
LEGEND
Bhp − Brake Horsepower
Watts − Input Watts to Motor
*Motor drive range: 590 to 840 rpm. All other rpms require
field−supplied drive.
521 21 1001 04
NOTES
1. Boldface indicates field−supplied drive required
2. Maximum continuous Bhp is 2.40
3. See General Notes for Fan Performance following this section
Specifications subject to change without notice.
21
PERFORMANCE DATA − PGE072−150 (cont.)
FAN PERFORMANCE VERTICAL DISCHARGE UNITS
PGE090 (71/2 TONS) − HIGH STATIC MOTOR (BELT DRIVE)*
Airflow
(Cfm)
2250
2300
2400
2500
2550
2600
2700
2800
2900
3000
3100
3200
3300
3400
3500
3600
3700
3750
Rpm
513
521
535
551
558
566
582
597
613
629
645
662
678
694
711
727
744
752
0.2
Bhp
0.54
0.57
0.63
0.69
0.72
0.76
0.83
0.90
0.98
1.07
1.16
1.26
1.36
1.47
1.59
1.71
1.84
1.91
Watts
505
531
584
642
673
705
771
842
918
999
1085
1176
1272
1374
1482
1596
1716
1778
Rpm
595
601
615
628
635
642
656
670
684
699
713
728
743
758
773
789
804
812
0.4
Bhp
0.76
0.79
0.86
0.93
0.97
1.00
1.08
1.16
1.25
1.35
1.45
1.55
1.66
1.78
1.90
2.03
2.17
2.24
External Static Pressure (in. wg)
0.6
Watts
Rpm
Bhp
Watts
Rpm
713
665
1.01
940
728
741
671
1.04
972
734
802
684
1.11
1038
745
866
696
1.19
1109
757
900
702
1.23
1146
763
935
709
1.27
1183
769
1008
721
1.35
1263
781
1086
734
1.44
1347
793
1169
748
1.54
1436
805
1256
761
1.64
1530
818
1349
775
1.75
1630
831
1448
788
1.86
1734
844
1551
802
1.98
1845
857
1660
816
2.10
1961
870
1775
831
2.23
2082
884
1896
845
2.37
2210
897
2023
860
2.51
2343
911
2089
867
2.59
2413
918
0.8
Bhp
1.27
1.31
1.39
1.47
1.51
1.55
1.65
1.74
1.84
1.95
2.06
2.18
2.31
2.44
2.58
2.72
2.87
2.95
Watts
1187
1222
1293
1369
1409
1450
1535
1625
1720
1820
1925
2036
2152
2275
2402
2537
2677
2750
Rpm
786
791
802
813
818
824
835
847
859
871
883
895
908
920
933
946
959
966
1.0
Bhp
1.56
1.60
1.68
1.77
1.81
1.86
1.95
2.06
2.16
2.28
2.40
2.52
2.65
2.79
2.93
3.09
3.24
3.32
Watts
1453
1489
1566
1647
1689
1732
1823
1917
2019
2125
2235
2352
2475
2603
2737
2877
3023
3100
PGE090 (71/2 TONS) − HIGH STATIC MOTOR (BELT DRIVE)* (cont)
Airflow
(Cfm)
External Static Pressure (in. wg)
1.2
1.4
1.6
2.0
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
2250
839
1.86
1735
889
2.18
2032
935
2.52
2345
980
2.87
2673
1022
3.23
3015
2300
844
1.90
1773
893
2.22
2073
940
2.56
2389
984
2.91
2718
1027
3.28
3062
2400
854
1.99
1855
903
2.32
2159
950
2.66
2478
993
3.02
2812
1035
3.39
3159
2500
865
2.08
1940
913
2.41
2249
959
2.76
2573
1003
3.12
2911
1044
3.50
3261
2550
870
2.13
1985
918
2.46
2296
964
2.81
2622
1008
3.18
2962
1049
3.55
3315
2600
875
2.18
2031
923
2.51
2344
969
2.87
2673
1012
3.23
3014
1054
3.61
3370
2700
886
2.28
2126
934
2.62
2445
979
2.98
2777
1022
3.35
3123
−
−
−
2800
897
2.39
2227
944
2.73
2550
989
3.10
2888
1032
3.47
3238
−
−
−
2900
908
2.50
2333
955
2.85
2661
1000
3.22
3003
1042
3.60
3358
−
−
−
3000
920
2.62
2443
966
2.98
2777
1010
3.35
3123
−
−
−
−
−
−
3100
931
2.75
2560
977
3.11
2899
1021
3.49
3250
−
−
−
−
−
−
3200
943
2.88
2682
989
3.25
3026
1032
3.63
3383
−
−
−
−
−
−
3300
955
3.01
2810
1000
3.39
3159
−
−
−
−
−
−
−
−
−
3400
967
3.16
2945
1012
3.54
3299
−
−
−
−
−
−
−
−
−
3500
980
3.31
3084
1024
3.69
3445
−
−
−
−
−
−
−
−
−
3600
992
3.46
3230
−
−
−
−
−
−
−
−
−
−
−
−
3700
1005
3.63
3383
−
−
−
−
−
−
−
−
−
−
−
−
3750
−
−
−
−
−
−
−
−
−
−
−
−
−
−
−
LEGEND
Bhp − Brake Horsepower
Watts − Input Watts to Motor
*Motor drive range: 860 to 1080 rpm. All other rpms require
field−supplied drive.
22
1.8
Rpm
NOTES
1. Boldface indicates field−supplied drive required
2. Maximum continuous Bhp is 3.70
3. See General Notes for Fan Performance following this section
Specifications subject to change without notice.
521 21 1001 04
PERFORMANCE DATA − PGEx072−150 (cont.)
FAN PERFORMANCE VERTICAL DISCHARGE UNITS
PGE102 (81/2 TONS) − STANDARD MOTOR (BELT DRIVE)*
Airflow
(Cfm)
2550
2600
2700
2800
2900
3000
3100
3200
3300
3400
3500
3600
3700
3750
3800
3900
4000
4100
4200
4250
External Static Pressure (in. wg)
0.2
0.4
0.6
0.8
1.0
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
558
566
582
597
613
629
645
662
678
694
711
727
744
752
761
777
794
−
−
−
0.72
0.76
0.83
0.90
0.98
1.07
1.16
1.26
1.36
1.47
1.59
1.71
1.84
1.91
1.98
2.12
2.27
−
−
−
673
705
771
842
918
999
1085
1176
1272
1374
1482
1596
1716
1778
1842
1974
2113
−
−
−
635
642
656
670
684
699
713
728
743
758
773
789
804
812
820
−
−
−
−
−
0.97
1.00
1.08
1.16
1.25
1.35
1.45
1.55
1.66
1.78
1.90
2.03
2.17
2.24
2.31
−
−
−
−
−
900
935
1008
1086
1169
1256
1349
1448
1551
1660
1775
1896
2023
2089
2156
−
−
−
−
−
702
709
721
734
748
761
775
788
802
816
831
845
−
−
−
−
−
−
−
−
1.23
1.27
1.35
1.44
1.54
1.64
1.75
1.86
1.98
2.10
2.23
2.37
−
−
−
−
−
−
−
−
1146
1183
1263
1347
1436
1530
1630
1734
1845
1961
2082
2210
−
−
−
−
−
−
−
−
763
769
781
793
805
818
831
844
857
−
−
−
−
−
−
−
−
−
−
−
1.51
1.55
1.65
1.74
1.84
1.95
2.06
2.18
2.31
−
−
−
−
−
−
−
−
−
−
−
1409
1450
1535
1625
1720
1820
1925
2036
2152
−
−
−
−
−
−
−
−
−
−
−
818
824
835
847
859
871
883
−
−
−
−
−
−
−
−
−
−
−
−
−
1.81
1.86
1.95
2.06
2.16
2.28
2.40
−
−
−
−
−
−
−
−
−
−
−
−
−
1689
1732
1823
1917
2019
2125
2235
−
−
−
−
−
−
−
−
−
−
−
−
−
PGE102 (81/2 TONS) − STANDARD MOTOR (BELT DRIVE)* (cont)
Airflow
(Cfm)
External Static Pressure (in. wg)
1.2
1.4
1.6
1.8
2.0
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
2550
870
2.13
1985
−
−
−
−
−
−
−
−
−
−
−
−
2600
875
2.18
2031
−
−
−
−
−
−
−
−
−
−
−
−
2700
886
2.28
2126
−
−
−
−
−
−
−
−
−
−
−
−
2800
897
2.39
2227
−
−
−
−
−
−
−
−
−
−
−
−
2900
−
−
−
−
−
−
−
−
−
−
−
−
−
−
−
3000
−
−
−
−
−
−
−
−
−
−
−
−
−
−
−
LEGEND
Bhp − Brake Horsepower
Watts − Input Watts to Motor
*Motor drive range: 685 to 935 rpm. All other rpms require
field−supplied drive.
521 21 1001 04
NOTES
1. Boldface indicates field−supplied drive required
2. Maximum continuous Bhp is 2.40
3. See General Notes for Fan Performance following this section
Specifications subject to change without notice.
23
PERFORMANCE DATA − PGE072−150 (cont.)
FAN PERFORMANCE VERTICAL DISCHARGE UNITS
PGE102 (81/2 TONS) − HIGH STATIC MOTOR (BELT DRIVE)*
External Static Pressure (in. wg)
0.2
0.4
0.6
0.8
1.0
Airflow
(Cfm)
2550
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
558
0.72
673
635
0.97
900
702
1.23
1146
763
1.51
1409
818
1.81
1689
2600
566
0.76
705
642
1.00
935
709
1.27
1183
769
1.55
1450
824
1.86
1732
2700
582
0.83
771
656
1.08
1008
721
1.35
1263
781
1.65
1535
835
1.95
1823
2800
597
0.90
842
670
1.16
1086
734
1.44
1347
793
1.74
1625
847
2.06
1917
2900
613
0.98
918
684
1.25
1169
748
1.54
1436
805
1.84
1720
859
2.16
2019
3000
629
1.07
999
699
1.35
1256
761
1.64
1530
818
1.95
1820
871
2.28
2125
3100
645
1.16
1085
713
1.45
1349
775
1.75
1630
831
2.06
1925
883
2.40
2235
3200
662
1.26
1176
728
1.55
1448
788
1.86
1734
844
2.18
2036
895
2.52
2352
3300
678
1.36
1272
743
1.66
1551
802
1.98
1845
857
2.31
2152
908
2.65
2475
3400
694
1.47
1374
758
1.78
1660
816
2.10
1961
870
2.44
2275
920
2.79
2603
3500
711
1.59
1482
773
1.90
1775
831
2.23
2082
884
2.58
2402
933
2.93
2737
3600
727
1.71
1596
789
2.03
1896
845
2.37
2210
897
2.72
2537
946
3.09
2877
3700
744
1.84
1716
804
2.17
2023
860
2.51
2343
911
2.87
2677
959
3.24
3023
3750
752
1.91
1778
812
2.24
2089
867
2.59
2413
918
2.95
2750
966
3.32
3100
3800
761
1.98
1842
820
2.31
2156
874
2.66
2484
925
3.03
2824
973
3.41
3177
3900
777
2.12
1974
835
2.46
2296
889
2.82
2630
939
3.19
2977
986
3.58
3336
4000
794
2.27
2113
851
2.62
2442
904
2.99
2784
953
3.36
3137
−
−
−
4100
811
2.42
2259
867
2.78
2595
919
3.16
2944
968
3.54
3304
−
−
−
4200
828
2.59
2412
883
2.95
2755
934
3.34
3110
−
−
−
−
−
−
4250
837
2.67
2490
891
3.04
2838
942
3.43
3197
−
−
−
−
−
−
PGE102 (81/2 TONS) − HIGH STATIC MOTOR (BELT DRIVE)* (cont)
External Static Pressure (in. wg)
Airflow
(Cfm)
2550
2600
2700
2800
2900
3000
3100
3200
3300
3400
3500
3600
3700
3750
3800
3900
4000
1.2
1.4
1.6
2.0
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
870
875
886
897
908
920
931
943
955
967
980
992
1005
−
−
−
−
2.13
2.18
2.28
2.39
2.50
2.62
2.75
2.88
3.01
3.16
3.31
3.46
3.63
−
−
−
−
1985
2031
2126
2227
2333
2443
2560
2682
2810
2945
3084
3230
3383
−
−
−
−
918
923
934
944
955
966
977
989
1000
1012
1024
−
−
−
−
−
−
2.46
2.51
2.62
2.73
2.85
2.98
3.11
3.25
3.39
3.54
3.69
−
−
−
−
−
−
2296
2344
2445
2550
2661
2777
2899
3026
3159
3299
3445
−
−
−
−
−
−
964
969
979
989
1000
1010
1021
1032
−
−
−
−
−
−
−
−
−
2.81
2.87
2.98
3.10
3.22
3.35
3.49
3.63
−
−
−
−
−
−
−
−
−
2622
2673
2777
2888
3003
3123
3250
3383
−
−
−
−
−
−
−
−
−
1008
1012
1022
1032
1042
−
−
−
−
−
−
−
−
−
−
−
−
3.18
3.23
3.35
3.47
3.60
−
−
−
−
−
−
−
−
−
−
−
−
2962
3014
3123
3238
3358
−
−
−
−
−
−
−
−
−
−
−
−
1049
1054
−
−
−
−
−
−
−
−
−
−
−
−
−
−
−
3.55
3.61
−
−
−
−
−
−
−
−
−
−
−
−
−
−
−
3315
3370
−
−
−
−
−
−
−
−
−
−
−
−
−
−
LEGEND
Bhp − Brake Horsepower
Watts − Input Watts to Motor
*Motor drive range: 860 to 1080 rpm. All other rpms require
field−supplied drive.
24
1.8
Rpm
NOTES
1. Boldface indicates field−supplied drive required
2. Maximum continuous Bhp is 3.70
3. See General Notes for Fan Performance following this section
Specifications subject to change without notice.
521 21 1001 04
PERFORMANCE DATA − PGE072−150 (cont.)
FAN PERFORMANCE VERTICAL DISCHARGE UNITS
PGE120 (10 TONS) − STANDARD MOTOR (BELT DRIVE)*
Airflow
(Cfm)
3000
3100
3200
3300
3400
3500
3600
3700
3800
3900
4000
4100
4200
4300
4400
4500
4600
4700
4800
4900
5000
Rpm
592
607
623
638
653
669
685
700
716
732
748
764
780
796
812
828
−
−
−
−
−
0.2
Bhp
0.77
0.83
0.90
0.98
1.06
1.15
1.23
1.33
1.43
1.53
1.64
1.76
1.88
2.00
2.13
2.27
−
−
−
−
−
Watts
672
731
794
860
931
1005
1084
1167
1254
1345
1441
1542
1648
1758
1874
1994
−
−
−
−
−
Rpm
658
672
686
700
714
728
742
757
771
786
801
816
831
846
861
−
−
−
−
−
−
0.4
Bhp
0.93
1.00
1.08
1.16
1.25
1.34
1.43
1.53
1.64
1.75
1.86
1.98
2.11
2.24
2.38
−
−
−
−
−
−
Watts
817
881
949
1020
1095
1175
1258
1346
1438
1534
1635
1741
1851
1966
2087
−
−
−
−
−
−
External Static Pressure (in. wg)
0.6
Rpm
Bhp
Watts
Rpm
719
1.10
961
775
731
1.17
1030
787
744
1.26
1103
798
757
1.34
1179
810
770
1.44
1260
822
783
1.53
1344
835
796
1.63
1432
847
810
1.74
1524
860
823
1.85
1621
873
837
1.96
1722
886
851
2.08
1828
899
865
2.21
1939
−
879
2.34
2054
−
−
−
−
−
−
−
−
−
−
−
−
−
−
−
−
−
−
−
−
−
−
−
−
−
−
−
−
−
−
−
−
−
0.8
Bhp
1.26
1.34
1.43
1.52
1.62
1.72
1.83
1.94
2.06
2.18
2.30
−
−
−
−
−
−
−
−
−
−
Watts
1105
1179
1257
1338
1423
1512
1606
1703
1805
1911
2022
−
−
−
−
−
−
−
−
−
−
Rpm
828
839
850
861
872
884
895
907
919
932
−
−
−
−
−
−
−
−
−
−
−
1.0
Bhp
1.42
1.51
1.61
1.71
1.81
1.91
2.03
2.14
2.26
2.39
−
−
−
−
−
−
−
−
−
−
−
Watts
1249
1328
1410
1496
1586
1680
1778
1881
1987
2099
−
−
−
−
−
−
−
−
−
−
−
PGE120 (10 TONS) − STANDARD MOTOR (BELT DRIVE)* (cont)
Airflow
(Cfm)
3000
3100
3200
3300
3400
3500
3600
3700
3800
3900
4000
Rpm
878
888
898
909
919
930
941
952
−
−
−
1.2
Bhp
1.59
1.68
1.78
1.88
1.99
2.11
2.22
2.35
−
−
−
Watts
1391
1475
1563
1654
1749
1848
1951
2058
−
−
−
Rpm
925
935
944
954
964
975
−
−
−
−
−
1.4
Bhp
1.75
1.85
1.95
2.06
2.18
2.30
−
−
−
−
−
Watts
1534
1623
1715
1811
1911
2015
−
−
−
−
−
External Static Pressure (in. wg)
1.6
Rpm
Bhp
Watts
Rpm
970
1.91
1676
1014
979
2.02
1769
1022
988
2.13
1867
1031
998
2.24
1968
−
1007
2.36
2073
−
−
−
−
−
−
−
−
−
−
−
−
−
−
−
−
−
−
−
−
−
−
−
−
−
LEGEND
Bhp − Brake Horsepower
Watts − Input Watts to Motor
*Motor drive range: 685 to 935 rpm. All other rpms require
field−supplied drive.
521 21 1001 04
1.8
Bhp
2.07
2.18
2.30
−
−
−
−
−
−
−
−
Watts
1817
1916
2018
−
−
−
−
−
−
−
−
Rpm
1055
1063
−
−
−
−
−
−
−
−
−
2.0
Bhp
2.23
2.35
−
−
−
−
−
−
−
−
−
Watts
1958
2062
−
−
−
−
−
−
−
−
−
NOTES
1. Boldface indicates field−supplied drive required
2. Maximum continuous Bhp is 2.40
3. See General Notes for Fan Performance following this section
Specifications subject to change without notice.
25
PERFORMANCE DATA − PGE072−150 (cont.)
FAN PERFORMANCE VERTICAL DISCHARGE UNITS
PGE120 (10 TONS) − HIGH STATIC MOTOR (BELT DRIVE)*
Airflow
(Cfm)
3000
3100
3200
3300
3400
3500
3600
3700
3800
3900
4000
4100
4200
4300
4400
4500
4600
4700
4800
4900
5000
Rpm
592
607
623
638
653
669
685
700
716
732
748
764
780
796
812
828
845
861
877
894
910
0.2
Bhp
0.77
0.83
0.90
0.98
1.06
1.15
1.23
1.33
1.43
1.53
1.64
1.76
1.88
2.00
2.13
2.27
2.42
2.57
2.72
2.88
3.05
Watts
672
731
794
860
931
1005
1084
1167
1254
1345
1441
1542
1648
1758
1874
1994
2120
2251
2388
2531
2679
Rpm
658
672
686
700
714
728
742
757
771
786
801
816
831
846
861
877
892
907
923
938
954
0.4
Bhp
0.93
1.00
1.08
1.16
1.25
1.34
1.43
1.53
1.64
1.75
1.86
1.98
2.11
2.24
2.38
2.52
2.67
2.82
2.99
3.15
3.33
External Static Pressure (in. wg)
0.6
Watts
Rpm
Bhp
Watts
Rpm
817
719
1.10
961
775
881
731
1.17
1030
787
949
744
1.26
1103
798
1020
757
1.34
1179
810
1095
770
1.44
1260
822
1175
783
1.53
1344
835
1258
796
1.63
1432
847
1346
810
1.74
1524
860
1438
823
1.85
1621
873
1534
837
1.96
1722
886
1635
851
2.08
1828
899
1741
865
2.21
1939
912
1851
879
2.34
2054
925
1966
894
2.48
2175
939
2087
908
2.62
2299
952
2212
922
2.77
2430
966
2343
937
2.92
2566
980
2479
952
3.08
2706
994
2621
966
3.25
2853
1008
2768
981
3.42
3005
1022
2921
996
3.60
3163
1037
0.8
Bhp
1.26
1.34
1.43
1.52
1.62
1.72
1.83
1.94
2.06
2.18
2.30
2.43
2.57
2.71
2.86
3.02
3.18
3.34
3.52
3.69
3.88
Watts
1105
1179
1257
1338
1423
1512
1606
1703
1805
1911
2022
2137
2257
2382
2512
2648
2788
2934
3086
3242
3405
Rpm
828
839
850
861
872
884
895
907
919
932
944
957
969
982
995
1008
1022
1035
1049
1062
1076
1.0
Bhp
1.42
1.51
1.61
1.71
1.81
1.91
2.03
2.14
2.26
2.39
2.52
2.66
2.80
2.95
3.10
3.26
3.43
3.60
3.78
3.96
4.15
Watts
1249
1328
1410
1496
1586
1680
1778
1881
1987
2099
2214
2334
2460
2589
2725
2865
3010
3161
3317
3479
3647
PGE120 (10 TONS) − HIGH STATIC MOTOR (BELT DRIVE)* (cont)
Airflow
(Cfm)
3000
3100
3200
3300
3400
3500
3600
3700
3800
3900
4000
4100
4200
4300
4400
4500
4600
4700
4800
4900
5000
Rpm
878
888
898
909
919
930
941
952
964
976
987
999
1012
1024
1036
1049
1062
1075
1088
1101
1114
1.2
Bhp
1.59
1.68
1.78
1.88
1.99
2.11
2.22
2.35
2.47
2.60
2.74
2.88
3.03
3.19
3.35
3.51
3.68
3.86
4.04
4.23
4.43
Watts
1391
1475
1563
1654
1749
1848
1951
2058
2170
2286
2407
2532
2662
2796
2937
3082
3232
3387
3549
3716
3888
Rpm
925
935
944
954
964
975
985
996
1007
1018
1029
1041
1052
1064
1076
1088
1100
1113
1125
1138
1151
1.4
Bhp
1.75
1.85
1.95
2.06
2.18
2.30
2.42
2.55
2.68
2.82
2.96
3.11
3.26
3.42
3.59
3.76
3.94
4.12
4.31
4.50
4.70
External Static Pressure (in. wg)
1.6
Watts
Rpm
Bhp
Watts
1534
970
1.91
1676
1623
979
2.02
1769
1715
988
2.13
1867
1811
998
2.24
1968
1911
1007
2.36
2073
2015
1017
2.49
2182
2123
1027
2.61
2295
2236
1038
2.75
2412
2352
1048
2.89
2534
2473
1059
3.03
2660
2598
1069
3.18
2790
2729
1080
3.33
2925
2863
1092
3.49
3065
3003
1103
3.66
3210
3148
1114
3.83
3359
3298
1126
4.00
3514
3454
1138
4.19
3675
3614
1150
4.38
3840
3780
1162
4.57
4011
3951
1174
4.77
4188
4129
1187
4.98
4370
LEGEND
Bhp − Brake Horsepower
Watts − Input Watts to Motor
*Motor drive range: 830 to 1130 rpm. All other rpms require
field−supplied drive.
26
Rpm
1014
1022
1031
1040
1049
1058
1068
1078
1088
1098
1108
1119
1130
1141
1152
1163
1174
1186
1198
−
−
1.8
Bhp
2.07
2.18
2.30
2.42
2.55
2.68
2.81
2.95
3.09
3.24
3.40
3.56
3.72
3.89
4.07
4.25
4.44
4.63
4.83
−
−
Watts
1817
1916
2018
2124
2234
2348
2466
2588
2715
2846
2981
3121
3266
3415
3570
3730
3895
4065
4241
−
−
Rpm
1055
1063
1072
1080
1089
1098
1107
1117
1126
1136
1146
1156
1167
1177
1188
1199
1210
1221
−
−
−
2.0
Bhp
2.23
2.35
2.47
2.60
2.73
2.86
3.00
3.15
3.30
3.45
3.61
3.78
3.95
4.13
4.31
4.50
4.69
4.89
−
−
−
Watts
1958
2062
2169
2280
2395
2514
2637
2764
2895
3031
3171
3316
3466
3621
3781
3945
4116
4291
−
−
−
NOTES
1. Boldface indicates field−supplied drive required
2. Maximum continuous Bhp is 5.25
3. See General Notes for Fan Performance following this section
Specifications subject to change without notice.
521 21 1001 04
PERFORMANCE DATA − PGE072−150 (cont.)
FAN PERFORMANCE VERTICAL DISCHARGE UNITS
PGE150 (121/2 TONS) − STANDARD MOTOR (BELT DRIVE)*
Airflow
(Cfm)
External Static Pressure (in. wg)
0.2
0.4
0.6
0.8
1.0
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
3700
728
1.36
1266
789
1.58
1473
848
1.81
1686
904
2.04
1906
957
2.29
2132
3800
744
1.46
1361
804
1.69
1572
861
1.92
1790
916
2.16
2015
969
2.41
2246
3900
760
1.57
1460
819
1.80
1676
875
2.04
1899
929
2.28
2128
981
2.53
2364
4000
777
1.68
1563
834
1.91
1785
889
2.16
2012
942
2.41
2247
993
2.67
2487
4100
793
1.79
1672
850
2.04
1899
904
2.29
2132
956
2.54
2371
1006
2.80
2615
4200
810
1.92
1786
865
2.16
2018
918
2.42
2255
969
2.68
2499
1018
2.95
2748
4300
826
2.04
1906
880
2.30
2142
932
2.56
2385
983
2.82
2633
1031
3.10
2888
4400
843
2.18
2031
896
2.44
2272
947
2.70
2520
996
2.97
2773
1044
3.25
3032
4500
860
2.32
2161
912
2.58
2408
962
2.85
2660
1010
3.13
2918
1057
3.41
3182
4600
876
2.46
2297
927
2.73
2549
977
3.01
2807
1024
3.29
3070
1070
3.58
3338
4700
893
2.62
2439
943
2.89
2696
992
3.17
2958
1038
3.46
3226
−
−
−
4800
910
2.77
2587
959
3.06
2849
1007
3.34
3116
1053
3.63
3390
−
−
−
4900
927
2.94
2741
975
3.23
3008
1022
3.52
3280
−
−
−
−
−
−
5000
944
3.11
2901
991
3.40
3173
1037
3.70
3451
−
−
−
−
−
−
5100
961
3.29
3068
1007
3.59
3345
−
−
−
−
−
−
−
−
−
5200
978
3.48
3241
−
−
−
−
−
−
−
−
−
−
−
−
5300
995
3.67
3420
−
−
−
−
−
−
−
−
−
−
−
−
5400
−
−
−
−
−
−
−
−
−
−
−
−
−
−
−
5500
−
−
−
−
−
−
−
−
−
−
−
−
−
−
−
5600
−
−
−
−
−
−
−
−
−
−
−
−
−
−
−
5700
−
−
−
−
−
−
−
−
−
−
−
−
−
−
−
5800
−
−
−
−
−
−
−
−
−
−
−
−
−
−
−
5900
−
−
−
−
−
−
−
−
−
−
−
−
−
−
−
PGE150 (121/2 TONS) − STANDARD MOTOR (BELT DRIVE)* (cont)
Airflow
(Cfm)
External Static Pressure (in. wg)
1.2
1.4
1.6
1.8
2.0
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
3700
1008
2.54
2364
1058
2.79
2602
1106
3.05
2846
1152
3.32
3094
1198
3.59
3348
3800
1019
2.66
2482
1068
2.92
2725
1116
3.19
2972
1162
3.46
3226
−
−
−
3900
1031
2.79
2605
1079
3.06
2852
1126
3.33
3104
1171
3.61
3362
−
−
−
4000
1042
2.93
2733
1090
3.20
2984
1136
3.48
3241
−
−
−
−
−
−
4100
1054
3.07
2866
1101
3.35
3122
1146
3.63
3383
−
−
−
−
−
−
4200
1066
3.22
3004
1112
3.50
3264
−
−
−
−
−
−
−
−
−
4300
1078
3.38
3148
1123
3.66
3413
−
−
−
−
−
−
−
−
−
4400
1090
3.54
3297
−
−
−
−
−
−
−
−
−
−
−
−
4500
1103
3.70
3451
−
−
−
−
−
−
−
−
−
−
−
−
4600
−
−
−
−
−
−
−
−
−
−
−
−
−
−
−
4700
−
−
−
−
−
−
−
−
−
−
−
−
−
−
−
4800
−
−
−
−
−
−
−
−
−
−
−
−
−
−
−
4900
−
−
−
−
−
−
−
−
−
−
−
−
−
−
−
5000
−
−
−
−
−
−
−
−
−
−
−
−
−
−
−
LEGEND
Bhp − Brake Horsepower
Watts − Input Watts to Motor
*Motor drive range: 860 to 1080 rpm. All other rpms require
field−supplied drive.
521 21 1001 04
NOTES
1. Boldface indicates field−supplied drive required
2. Maximum continuous Bhp is 3.70
3. See General Notes for Fan Performance following this section
Specifications subject to change without notice.
27
PERFORMANCE DATA − PGE072−150 (cont.)
FAN PERFORMANCE VERTICAL DISCHARGE UNITS
PGE150 (121/2 TONS) − ALTERNATE / HIGH STATIC MOTOR (BELT DRIVE)*
Airflow
(Cfm)
3700
3800
3900
4000
4100
4200
4300
4400
4500
4600
4700
4800
4900
5000
5100
5200
5300
5400
5500
5600
5700
5800
5900
6000
Rpm
728
744
760
777
793
810
826
843
860
876
893
910
927
944
961
978
995
1012
1029
1046
1063
1080
1098
1115
0.2
Bhp
1.36
1.46
1.57
1.68
1.79
1.92
2.04
2.18
2.32
2.46
2.62
2.77
2.94
3.11
3.29
3.48
3.67
3.87
4.07
4.29
4.51
4.74
4.98
5.22
Watts
1266
1361
1460
1563
1672
1786
1906
2031
2161
2297
2439
2587
2741
2901
3068
3241
3420
3606
3799
3999
4207
4420
4642
4872
Rpm
789
804
819
834
850
865
880
896
912
927
943
959
975
991
1007
1024
1040
1056
1073
1089
1105
1122
−
−
0.4
Bhp
1.58
1.69
1.80
1.91
2.04
2.16
2.30
2.44
2.58
2.73
2.89
3.06
3.23
3.40
3.59
3.78
3.98
4.18
4.39
4.61
4.84
5.08
−
−
Watts
1473
1572
1676
1785
1899
2018
2142
2272
2408
2549
2696
2849
3008
3173
3345
3523
3707
3899
4097
4302
4515
4734
−
−
External Static Pressure (in. wg)
0.6
Rpm
Bhp
Watts
Rpm
848
1.81
1686
904
861
1.92
1790
916
875
2.04
1899
929
889
2.16
2012
942
904
2.29
2132
956
918
2.42
2255
969
932
2.56
2385
983
947
2.70
2520
996
962
2.85
2660
1010
977
3.01
2807
1024
992
3.17
2958
1038
1007
3.34
3116
1053
1022
3.52
3280
1067
1037
3.70
3451
1082
1053
3.89
3627
1096
1068
4.09
3811
1111
1084
4.29
4000
1126
1099
4.50
4196
1141
1115
4.72
4400
1156
1131
4.94
4610
−
1146
5.18
4827
−
−
−
−
−
−
−
−
−
−
−
−
−
0.8
Bhp
2.04
2.16
2.28
2.41
2.54
2.68
2.82
2.97
3.13
3.29
3.46
3.63
3.82
4.00
4.20
4.40
4.61
4.82
5.05
−
−
−
−
−
Watts
1906
2015
2128
2247
2371
2499
2633
2773
2918
3070
3226
3390
3558
3733
3915
4103
4298
4499
4707
−
−
−
−
−
Rpm
957
969
981
993
1006
1018
1031
1044
1057
1070
1084
1098
1111
1125
1139
1153
1168
1182
−
−
−
−
−
−
1.0
Bhp
2.29
2.41
2.53
2.67
2.80
2.95
3.10
3.25
3.41
3.58
3.75
3.93
4.12
4.31
4.51
4.72
4.93
5.15
−
−
−
−
−
−
Watts
2132
2246
2364
2487
2615
2748
2888
3032
3182
3338
3500
3668
3841
4021
4208
4400
4600
4806
−
−
−
−
−
−
1.8
Bhp
3.32
3.46
3.61
3.76
3.91
4.08
4.24
4.42
4.60
4.79
4.98
5.18
−
−
−
−
−
−
Watts
3094
3226
3362
3503
3649
3801
3958
4121
4289
4464
4644
4830
−
−
−
−
−
−
Rpm
1198
1206
1215
1224
1233
1243
1252
1262
1273
1283
−
−
−
−
−
−
−
−
2.0
Bhp
3.59
3.74
3.89
4.04
4.20
4.37
4.54
4.72
4.91
5.10
−
−
−
−
−
−
−
−
Watts
3348
3484
3624
3770
3921
4077
4238
4405
4578
4757
−
−
−
−
−
−
−
−
PGE150 (121/2 TONS) − ALTERNATE / HIGH STATIC MOTOR (BELT DRIVE)* (cont)
Airflow
(Cfm)
3700
3800
3900
4000
4100
4200
4300
4400
4500
4600
4700
4800
4900
5000
5100
5200
5300
5400
Rpm
1008
1019
1031
1042
1054
1066
1078
1090
1103
1115
1128
1141
1154
1167
1181
1194
−
−
1.2
Bhp
2.54
2.66
2.79
2.93
3.07
3.22
3.38
3.54
3.70
3.87
4.05
4.24
4.43
4.63
4.83
5.04
−
−
Watts
2364
2482
2605
2733
2866
3004
3148
3297
3451
3612
3778
3951
4130
4314
4505
4703
−
−
Rpm
1058
1068
1079
1090
1101
1112
1123
1135
1147
1159
1171
1183
1196
1209
1221
−
−
−
1.4
Bhp
2.79
2.92
3.06
3.20
3.35
3.50
3.66
3.82
4.00
4.17
4.36
4.55
4.74
4.95
5.16
−
−
−
Watts
2602
2725
2852
2984
3122
3264
3413
3566
3726
3891
4062
4239
4422
4611
4808
−
−
−
External Static Pressure (in. wg)
1.6
Rpm
Bhp
Watts
Rpm
1106
3.05
2846
1152
1116
3.19
2972
1162
1126
3.33
3104
1171
1136
3.48
3241
1180
1146
3.63
3383
1190
1157
3.79
3530
1200
1167
3.95
3683
1210
1179
4.12
3841
1221
1190
4.29
4005
1232
1201
4.48
4175
1243
1213
4.67
4350
1254
1225
4.86
4532
1265
1237
5.06
4720
−
−
−
−
−
−
−
−
−
−
−
−
−
−
−
−
−
−
−
−
−
LEGEND
Bhp − Brake Horsepower
Watts − Input Watts to Motor
*Motor drive range: 830 to 1130 rpm. All other rpms require
field−supplied drive.
NOTES
1. Boldface indicates field−supplied drive required
2. Maximum continuous Bhp is 5.25
3. See General Notes for Fan Performance following this section
GENERAL NOTES FOR FAN PERFORMANCE TABLES:
1. Extensive motor and electrical testing on these units ensures that the full range of the motor can be utilized with confidence. Using your fan
motors up to the wattage ratings shown will not result in nuisance tripping or premature motor failure. Unit warranty will not be affected. For
additional information on motor performance, refer to Indoor Fan Motor Performance table.
2. Values include losses for filters, unit casing, and wet coils. Refer to Accessory/FIOP Static Pressure tables for accessory static pressure
information.
3. Use of a field−supplied motor may affect wire sizing.
4. Interpolation is permissible. Do not extrapolate.
28
Specifications subject to change without notice.
521 21 1001 04
PERFORMANCE DATA − PGE072−150 (CONT.)
FAN PERFORMANCE HORIZONTAL DISCHARGE UNITS
PGE072 (6 TONS) − STANDARD MOTOR (BELT DRIVE)*
External Static Pressure (in. wg)
0.2
0.4
0.6
0.8
1.0
Airflow
(Cfm)
1800
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
919
0.63
561
1010
0.75
663
1095
0.87
771
1174
1.00
886
1250
1.14
1008
1900
960
0.73
648
1047
0.85
754
1129
0.98
867
1206
1.11
986
1279
1.25
1111
2000
1001
0.84
744
1085
0.96
855
1163
1.09
972
1238
1.23
1095
1309
1.38
1224
2100
1043
0.96
850
1123
1.09
965
1199
1.22
1086
1271
1.37
1213
1340
1.52
1346
2200
1085
1.09
966
1162
1.22
1086
1235
1.36
1211
1305
1.51
1342
1372
1.67
1479
2300
1127
1.23
1092
1201
1.37
1217
1272
1.52
1347
1340
1.67
1482
1405
1.83
1623
2400
1169
1.38
1229
1241
1.53
1359
1310
1.68
1493
1375
1.84
1633
1439
2.00
1778
2500
1212
1.55
1378
1281
1.70
1513
1348
1.86
1652
1412
2.02
1796
1473
2.19
1945
2600
1255
1.73
1539
1322
1.89
1678
1386
2.05
1822
1448
2.22
1970
1508
2.39
2124
2700
1298
1.93
1713
1363
2.09
1857
1425
2.26
2005
−
−
−
−
−
−
2800
1341
2.14
1899
1404
2.31
2048
−
−
−
−
−
−
−
−
−
2900
1384
2.36
2099
−
−
−
−
−
−
−
−
−
−
−
−
3000
−
−
−
−
−
−
−
−
−
−
−
−
−
−
−
PGE072 (6 TONS) − STANDARD MOTOR (BELT DRIVE)* (cont)
External Static Pressure (in. wg)
1.2
1.4
1.6
1.8
2.0
Airflow
(Cfm)
1800
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
1321
1.28
1137
1390
1.43
1273
1455
1.59
1415
1518
1.76
1563
1579
1.93
1718
1900
1348
1.40
1243
1415
1.56
1381
1479
1.72
1526
1541
1.89
1677
1601
2.06
1834
2000
1377
1.53
1359
1442
1.69
1500
1505
1.86
1648
1565
2.03
1801
1624
2.21
1961
2100
1406
1.67
1485
1470
1.83
1629
1531
2.00
1780
1591
2.18
1936
1648
2.36
2098
2200
1437
1.83
1621
1499
1.99
1769
1559
2.16
1923
1617
2.34
2082
−
−
−
2300
1468
1.99
1769
1529
2.16
1920
1587
2.34
2077
−
−
−
−
−
−
2400
1500
2.17
1928
1559
2.35
2083
−
−
−
−
−
−
−
−
−
2500
1533
2.36
2098
−
−
−
−
−
−
−
−
−
−
−
−
2600
−
−
−
−
−
−
−
−
−
−
−
−
−
−
−
2700
−
−
−
−
−
−
−
−
−
−
−
−
−
−
−
2800
−
−
−
−
−
−
−
−
−
−
−
−
−
−
−
2900
−
−
−
−
−
−
−
−
−
−
−
−
−
−
−
3000
−
−
−
−
−
−
−
−
−
−
−
−
−
−
−
Bhp − Brake Horsepower
Watts − Input Watts to Motor
*Motor drive range: 1070 to 1460 rpm. All other rpms require
field−supplied drive.
521 21 1001 04
NOTES
1. Boldface indicates field−supplied drive required
2. Maximum continuous Bhp is 2.40
3. See General Notes for Fan Performance following this section
Specifications subject to change without notice.
29
PERFORMANCE DATA −PGE072−150(CONT.)
FAN PERFORMANCE HORIZONTAL DISCHARGE UNITS
PGE072 (6 TONS) − HIGH STATIC MOTOR (BELT DRIVE)*
External Static Pressure (in. wg)
Airflow
(Cfm)
1800
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
919
0.63
561
1010
0.75
663
1095
0.87
771
1174
1.00
886
1250
1.14
1008
1900
960
0.73
648
1047
0.85
754
1129
0.98
867
1206
1.11
986
1279
1.25
1111
2000
1001
0.84
744
1085
0.96
855
1163
1.09
972
1238
1.23
1095
1309
1.38
1224
2100
1043
0.96
850
1123
1.09
965
1199
1.22
1086
1271
1.37
1213
1340
1.52
1346
2200
1085
1.09
966
1162
1.22
1086
1235
1.36
1211
1305
1.51
1342
1372
1.67
1479
2300
1127
1.23
1092
1201
1.37
1217
1272
1.52
1347
1340
1.67
1482
1405
1.83
1623
2400
1169
1.38
1229
1241
1.53
1359
1310
1.68
1493
1375
1.84
1633
1439
2.00
1778
2500
1212
1.55
1378
1281
1.70
1513
1348
1.86
1652
1412
2.02
1796
1473
2.19
1945
2600
1255
1.73
1539
1322
1.89
1678
1386
2.05
1822
1448
2.22
1970
1508
2.39
2124
2700
1298
1.93
1713
1363
2.09
1857
1425
2.26
2005
1485
2.43
2158
1544
2.61
2315
2800
1341
2.14
1899
1404
2.31
2048
1464
2.48
2201
1523
2.66
2358
1580
2.84
2520
2900
1384
2.36
2099
1445
2.54
2253
1504
2.71
2410
1561
2.90
2572
−
−
−
3000
1428
2.60
2313
1487
2.78
2471
−
−
−
−
−
−
−
−
−
0.2
0.4
0.6
0.8
1.0
PGE072 (6 TONS) − HIGH STATIC MOTOR (BELT DRIVE)* (cont)
External Static Pressure (in. wg)
1.2
1.4
Airflow
(Cfm)
1800
Rpm
Bhp
Watts
Rpm
1321
1.28
1137
1390
1900
1348
1.40
1243
2000
1377
1.53
2100
1406
2200
1.6
1.8
2.0
Bhp
Watt
s
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
1.43
1273
1455
1.59
1415
1518
1.76
1563
1579
1.93
1718
1415
1.56
1381
1479
1.72
1526
1541
1.89
1677
1601
2.06
1834
1359
1442
1.69
1500
1505
1.86
1648
1565
2.03
1801
1624
2.21
1961
1.67
1485
1470
1.83
1629
1531
2.00
1780
1591
2.18
1936
1648
2.36
2098
1437
1.83
1621
1499
1.99
1769
1559
2.16
1923
1617
2.34
2082
1673
2.53
2246
2300
1468
1.99
1769
1529
2.16
1920
1587
2.34
2077
1644
2.52
2239
1699
2.71
2406
2400
1500
2.17
1928
1559
2.35
2083
1616
2.53
2243
1672
2.71
2408
1726
2.90
2579
2500
1533
2.36
2098
1591
2.54
2257
1647
2.73
2421
−
−
−
−
−
−
2600
1566
2.57
2281
1623
2.75
2444
−
−
−
−
−
−
−
−
−
2700
1600
2.79
2477
−
−
−
−
−
−
−
−
−
−
−
−
2800
−
−
−
−
−
−
−
−
−
−
−
−
−
−
−
2900
−
−
−
−
−
−
−
−
−
−
−
−
−
−
−
3000
−
−
−
−
−
−
−
−
−
−
−
−
−
−
−
Bhp − Brake Horsepower
Watts − Input Watts to Motor
*Motor drive range: 1300 to 1685 rpm. All other rpms require
field−supplied drive.
30
NOTES
1. Boldface indicates field−supplied drive required
2. Maximum continuous Bhp is 2.90
3. See General Notes for Fan Performance following this section
Specifications subject to change without notice.
521 21 1001 04
PERFORMANCE DATA − PGE072−150(CONT.)
FAN PERFORMANCE HORIZONTAL DISCHARGE UNITS
PGE090 (71/2 TONS) − STANDARD MOTOR (BELT DRIVE)*
External Static Pressure (in. wg)
0.2
0.4
0.6
0.8
1.0
Airflow
(Cfm)
2250
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
505
0.52
484
586
0.73
681
657
0.97
901
722
1.22
1142
782
1.50
1403
2300
513
0.55
509
592
0.76
708
663
1.00
931
727
1.26
1174
787
1.54
1437
2400
527
0.60
561
605
0.82
766
674
1.07
993
738
1.33
1241
796
1.62
1508
2500
543
0.66
617
618
0.89
828
686
1.14
1060
748
1.41
1312
806
1.70
1583
2550
550
0.69
647
625
0.92
860
692
1.17
1095
754
1.45
1349
811
1.74
1623
2600
558
0.73
677
632
0.96
894
698
1.21
1131
759
1.49
1388
816
1.78
1664
2700
574
0.80
742
645
1.03
964
710
1.29
1207
770
1.58
1469
826
1.88
1749
2800
589
0.87
811
659
1.11
1039
723
1.38
1287
782
1.67
1554
837
1.97
1839
2900
605
0.95
885
673
1.20
1119
736
1.47
1372
794
1.76
1644
848
2.07
1933
3000
621
1.03
963
688
1.29
1204
749
1.57
1463
806
1.87
1740
859
2.18
2033
3100
637
1.12
1046
702
1.39
1293
762
1.67
1558
818
1.97
1840
871
2.29
2139
3200
654
1.22
1135
717
1.49
1388
776
1.78
1658
831
2.09
1946
−
−
−
3300
670
1.32
1228
732
1.60
1488
789
1.89
1764
843
2.21
2057
−
−
−
3400
686
1.42
1328
747
1.71
1593
803
2.01
1876
856
2.33
2174
−
−
−
3500
703
1.54
1433
762
1.83
1705
817
2.14
1993
−
−
−
−
−
−
3600
720
1.66
1543
777
1.95
1822
832
2.27
2116
−
−
−
−
−
−
3700
736
1.78
1660
793
2.09
1944
−
−
−
−
−
−
−
−
−
3750
745
1.85
1721
801
2.15
2008
−
−
−
−
−
−
−
−
−
PGE090 (71/2 TONS) − STANDARD MOTOR (BELT DRIVE)* (cont)
External Static Pressure (in. wg)
1.2
1.4
1.6
1.8
2.0
Airflow
(Cfm)
2250
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
838
1.81
1683
891
2.12
1981
−
−
−
−
−
−
−
−
−
2300
842
1.84
1719
895
2.17
2019
−
−
−
−
−
−
−
−
−
2400
851
1.92
1793
903
2.25
2097
−
−
−
−
−
−
−
−
−
2500
860
2.01
1873
911
2.34
2180
−
−
−
−
−
−
−
−
−
2550
865
2.05
1914
916
2.38
2223
−
−
−
−
−
−
−
−
−
2600
869
2.10
1957
−
−
−
−
−
−
−
−
−
−
−
−
2700
879
2.19
2046
−
−
−
−
−
−
−
−
−
−
−
−
2800
889
2.29
2140
−
−
−
−
−
−
−
−
−
−
−
−
2900
899
2.40
2239
−
−
−
−
−
−
−
−
−
−
−
−
3000
−
−
−
−
−
−
−
−
−
−
−
−
−
−
−
Bhp − Brake Horsepower
Watts − Input Watts to Motor
*Motor drive range: 590 to 840 rpm. All other rpms require
field−supplied drive.
521 21 1001 04
NOTES
1. Boldface indicates field−supplied drive required
2. Maximum continuous Bhp is 2.40
3. See General Notes for Fan Performance following this section
Specifications subject to change without notice.
31
PERFORMANCE DATA − PGE072−150(CONT.)
FAN PERFORMANCE HORIZONTAL DISCHARGE UNITS
PGE090 (71/2 TONS) −HIGH STATIC MOTOR (BELT DRIVE)*
Airflow
(Cfm)
2250
2300
2400
2500
2550
2600
2700
2800
2900
3000
3100
3200
3300
3400
3500
3600
3700
3750
Rpm
505
513
527
543
550
558
574
589
605
621
637
654
670
686
703
720
736
745
0.2
Bhp
0.52
0.55
0.60
0.66
0.69
0.73
0.80
0.87
0.95
1.03
1.12
1.22
1.32
1.42
1.54
1.66
1.78
1.85
Watts
484
509
561
617
647
677
742
811
885
963
1046
1135
1228
1328
1433
1543
1660
1721
Rpm
586
592
605
618
625
632
645
659
673
688
702
717
732
747
762
777
793
801
0.4
Bhp
0.73
0.76
0.82
0.89
0.92
0.96
1.03
1.11
1.20
1.29
1.39
1.49
1.60
1.71
1.83
1.95
2.09
2.15
External Static Pressure (in. wg)
0.6
Watts
Rpm
Bhp
Watts
Rpm
681
657
0.97
901
722
708
663
1.00
931
727
766
674
1.07
993
738
828
686
1.14
1060
748
860
692
1.17
1095
754
894
698
1.21
1131
759
964
710
1.29
1207
770
1039
723
1.38
1287
782
1119
736
1.47
1372
794
1204
749
1.57
1463
806
1293
762
1.67
1558
818
1388
776
1.78
1658
831
1488
789
1.89
1764
843
1593
803
2.01
1876
856
1705
817
2.14
1993
870
1822
832
2.27
2116
883
1944
846
2.41
2245
896
2008
853
2.48
2312
903
0.8
Bhp
1.22
1.26
1.33
1.41
1.45
1.49
1.58
1.67
1.76
1.87
1.97
2.09
2.21
2.33
2.46
2.60
2.75
2.82
Watts
1142
1174
1241
1312
1349
1388
1469
1554
1644
1740
1840
1946
2057
2174
2297
2425
2560
2630
Rpm
782
787
796
806
811
816
826
837
848
859
871
882
894
907
919
932
944
951
1.0
Bhp
1.50
1.54
1.62
1.70
1.74
1.78
1.88
1.97
2.07
2.18
2.29
2.41
2.54
2.67
2.81
2.95
3.10
3.18
1.8
Bhp
2.82
2.86
2.95
3.05
3.10
3.15
3.25
3.37
3.49
3.61
−
−
−
−
−
−
−
−
Watts
2629
2669
2752
2842
2888
2935
3035
3140
3250
3366
−
−
−
−
−
−
−
−
Rpm
1033
1037
1043
1051
1054
1058
1066
−
−
−
−
−
−
−
−
−
−
−
2.0
Bhp
3.19
3.24
3.33
3.43
3.48
3.53
3.64
−
−
−
−
−
−
−
−
−
−
−
Watts
1403
1437
1508
1583
1623
1664
1749
1839
1933
2033
2139
2249
2365
2488
2616
2750
2889
2962
PGE090 (71/2 TONS) − HIGH STATIC MOTOR (BELT DRIVE)* (cont)
Airflow
(Cfm)
2250
2300
2400
2500
2550
2600
2700
2800
2900
3000
3100
3200
3300
3400
3500
3600
3700
3750
1.2
Rpm
838
842
851
860
865
869
879
889
899
910
921
932
943
954
966
978
990
996
Bhp
1.81
1.84
1.92
2.01
2.05
2.10
2.19
2.29
2.40
2.51
2.63
2.75
2.88
3.02
3.16
3.31
3.47
3.55
Watts
1683
1719
1793
1873
1914
1957
2046
2140
2239
2343
2453
2569
2690
2816
2950
3088
3233
3308
Rpm
891
895
903
911
916
920
929
938
948
958
968
978
989
1000
1011
1022
−
−
1.4
Bhp
2.12
2.17
2.25
2.34
2.38
2.43
2.53
2.64
2.75
2.86
2.98
3.11
3.25
3.39
3.54
3.69
−
−
External Static Pressure (in. wg)
1.6
Watts
Rpm
Bhp
Watts
Rpm
1981
941
2.46
2297
988
2019
944
2.51
2336
992
2097
952
2.59
2416
999
2180
960
2.68
2502
1006
2223
964
2.73
2547
1010
2267
968
2.78
2593
1014
2360
976
2.88
2689
1022
2458
985
2.99
2791
1030
2561
994
3.11
2898
1039
2670
1004
3.23
3011
1048
2783
1013
3.35
3128
−
2903
1023
3.49
3252
−
3029
1033
3.63
3382
−
3159
−
−
−
−
3297
−
−
−
−
3442
−
−
−
−
−
−
−
−
−
−
−
−
−
−
Bhp − Brake Horsepower
Watts − Input Watts to Motor
*Motor drive range: 860 to 1080 rpm. All other rpms require
field−supplied drive.
32
Watts
2976
3018
3104
3196
3243
3292
3395
−
−
−
−
−
−
−
−
−
−
−
NOTES
1. Boldface indicates field−supplied drive required
2. Maximum continuous Bhp is 3.70
3. See General Notes for Fan Performance following this section
Specifications subject to change without notice.
521 21 1001 04
PERFORMANCE DATA − PGE072−150(CONT.)
FAN PERFORMANCE HORIZONTAL DISCHARGE UNITS
PGE102 (81/2 TONS) − STANDARD MOTOR (BELT DRIVE)*
Airflow
(Cfm)
External Static Pressure (in. wg)
0.2
0.4
0.6
Rpm
Bhp
Watts
Rpm
Bhp
Watts
2550
550
0.69
647
625
0.92
2600
558
0.73
677
632
2700
574
0.80
742
2800
589
0.87
2900
605
3000
0.8
1.0
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
860
692
1.17
1095
754
1.45
1349
811
1.74
1623
0.96
894
698
1.21
1131
759
1.49
1388
816
1.78
1664
645
1.03
964
710
1.29
1207
770
1.58
1469
826
1.88
1749
811
659
1.11
1039
723
1.38
1287
782
1.67
1554
837
1.97
1839
0.95
885
673
1.20
1119
736
1.47
1372
794
1.76
1644
848
2.07
1933
621
1.03
963
688
1.29
1204
749
1.57
1463
806
1.87
1740
859
2.18
2033
3100
637
1.12
1046
702
1.39
1293
762
1.67
1558
818
1.97
1840
871
2.29
2139
3200
654
1.22
1135
717
1.49
1388
776
1.78
1658
831
2.09
1946
3300
670
1.32
1228
732
1.60
1488
789
1.89
1764
843
2.21
2057
3400
686
1.42
1328
747
1.71
1593
803
2.01
1876
856
2.33
2174
3500
703
1.54
1433
762
1.83
1705
817
2.14
1993
3600
720
1.66
1543
777
1.95
1822
832
2.27
2116
3700
736
1.78
1660
793
2.09
1944
3750
745
1.85
1721
801
2.15
2008
3800
753
1.91
1783
808
2.22
2074
3900
770
2.05
1912
824
2.37
2209
4000
787
2.20
2047
4100
804
2.35
2189
Rpm
Bhp
4200
4250
PGE102 (81/2 TONS) − STANDARD MOTOR (BELT DRIVE)* (cont)
Airflow
(Cfm)
External Static Pressure (in. wg)
1.2
1.4
1.6
Rpm
Bhp
Watts
Rpm
Bhp
Watts
2550
865
2.05
1914
916
2.38
2223
2600
869
2.10
1957
2700
879
2.19
2046
2800
889
2.29
2140
2900
899
2.40
2239
Rpm
Bhp
1.8
Watts
Rpm
Bhp
2.0
Watts
Watts
3000
Bhp − Brake Horsepower
Watts − Input Watts to Motor
*Motor drive range: 685 to 935 rpm. All other rpms require
field−supplied drive.
521 21 1001 04
NOTES
1. Boldface indicates field−supplied drive required
2. Maximum continuous Bhp is 2.40
3. See General Notes for Fan Performance following this section
Specifications subject to change without notice.
33
PERFORMANCE DATA − PGE072−150 (CONT.)
FAN PERFORMANCE HORIZONTAL DISCHARGE UNITS
PGE102 (81/2 TONS) −− HIGH STATIC MOTOR (BELT DRIVE)*
Airflow
(Cfm)
2550
2600
2700
2800
2900
3000
3100
3200
3300
3400
3500
3600
3700
3750
3800
3900
4000
4100
4200
4250
Rpm
550
558
574
589
605
621
637
654
670
686
703
720
736
745
753
770
787
804
821
829
0.2
Bhp
0.69
0.73
0.80
0.87
0.95
1.03
1.12
1.22
1.32
1.42
1.54
1.66
1.78
1.85
1.91
2.05
2.20
2.35
2.51
2.59
Watts
647
677
742
811
885
963
1046
1135
1228
1328
1433
1543
1660
1721
1783
1912
2047
2189
2338
2415
Rpm
625
632
645
659
673
688
702
717
732
747
762
777
793
801
808
824
840
856
872
880
0.4
Bhp
0.92
0.96
1.03
1.11
1.20
1.29
1.39
1.49
1.60
1.71
1.83
1.95
2.09
2.15
2.22
2.37
2.52
2.68
2.85
2.93
Watts
860
894
964
1039
1119
1204
1293
1388
1488
1593
1705
1822
1944
2008
2074
2209
2351
2499
2655
2735
External Static Pressure (in. wg)
0.6
Rpm
Bhp
Watts
Rpm
692
1.17
1095
754
698
1.21
1131
759
710
1.29
1207
770
723
1.38
1287
782
736
1.47
1372
794
749
1.57
1463
806
762
1.67
1558
818
776
1.78
1658
831
789
1.89
1764
843
803
2.01
1876
856
817
2.14
1993
870
832
2.27
2116
883
846
2.41
2245
896
853
2.48
2312
903
861
2.55
2380
910
875
2.70
2522
924
890
2.86
2669
938
905
3.03
2824
952
920
3.20
2986
967
928
3.29
3069
974
0.8
Bhp
1.45
1.49
1.58
1.67
1.76
1.87
1.97
2.09
2.21
2.33
2.46
2.60
2.75
2.82
2.90
3.05
3.22
3.39
3.57
3.66
Watts
1349
1388
1469
1554
1644
1740
1840
1946
2057
2174
2297
2425
2560
2630
2701
2848
3002
3162
3331
3417
Rpm
811
816
826
837
848
859
871
882
894
907
919
932
944
951
957
970
984
−
−
−
1.0
Bhp
1.74
1.78
1.88
1.97
2.07
2.18
2.29
2.41
2.54
2.67
2.81
2.95
3.10
3.18
3.26
3.42
3.59
−
−
−
Watts
1623
1664
1749
1839
1933
2033
2139
2249
2365
2488
2616
2750
2889
2962
3036
3189
3348
−
−
−
1.8
Bhp
3.10
3.15
3.25
3.37
3.49
3.61
−
−
−
−
−
−
−
−
−
−
−
Watts
2888
2935
3035
3140
3250
3366
−
−
−
−
−
−
−
−
−
−
−
Rpm
1054
1058
1066
−
−
−
−
−
−
−
−
−
−
−
−
−
−
2.0
Bhp
3.48
3.53
3.64
−
−
−
−
−
−
−
−
−
−
−
−
−
−
Watts
3243
3292
3395
−
−
−
−
−
−
−
−
−
−
−
−
−
−
PGE102 (81/2 TONS) − HIGH STATIC MOTOR (BELT DRIVE)* (cont)
Airflow
(Cfm)
2550
2600
2700
2800
2900
3000
3100
3200
3300
3400
3500
3600
3700
3750
3800
3900
4000
Rpm
865
869
879
889
899
910
921
932
943
954
966
978
990
996
1002
−
−
1.2
Bhp
2.05
2.10
2.19
2.29
2.40
2.51
2.63
2.75
2.88
3.02
3.16
3.31
3.47
3.55
3.63
−
−
Watts
1914
1957
2046
2140
2239
2343
2453
2569
2690
2816
2950
3088
3233
3308
3385
−
−
Rpm
916
920
929
938
948
958
968
978
989
1000
1011
1022
−
−
−
−
−
1.4
Bhp
2.38
2.43
2.53
2.64
2.75
2.86
2.98
3.11
3.25
3.39
3.54
3.69
−
−
−
−
−
Watts
2223
2267
2360
2458
2561
2670
2783
2903
3029
3159
3297
3442
−
−
−
−
−
External Static Pressure (in. wg)
1.6
Rpm
Bhp
Watts
Rpm
964
2.73
2547
1010
968
2.78
2593
1014
976
2.88
2689
1022
985
2.99
2791
1030
994
3.11
2898
1039
1004
3.23
3011
1048
1013
3.35
3128
−
1023
3.49
3252
−
1033
3.63
3382
−
−
−
−
−
−
−
−
−
−
−
−
−
−
−
−
−
−
−
−
−
−
−
−
−
−
−
−
−
−
−
−
−
Bhp − Brake Horsepower
Watts − Input Watts to Motor
*Motor drive range: 860 to 1080 rpm. All other rpms require
field−supplied drive.
34
NOTES
1. Boldface indicates field−supplied drive required
2. Maximum continuous Bhp is 3.70
3. See General Notes for Fan Performance following this section
Specifications subject to change without notice.
521 21 1001 04
PERFORMANCE DATA − PGE072−150 (CONT.)
FAN PERFORMANCE HORIZONTAL DISCHARGE UNITS
PGE120 (10 TONS) − STANDARD MOTOR (BELT DRIVE)*
External Static Pressure (in. wg)
Airflow
(Cfm)
3000
3100
3200
3300
3400
3500
3600
3700
3800
3900
4000
4100
4200
4300
4400
4500
4600
4700
4800
4900
5000
0.2
0.4
0.6
0.8
1.0
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
555
568
582
595
609
623
636
650
664
678
693
707
721
735
750
764
779
−
−
−
−
0.72
0.78
0.85
0.92
1.00
1.08
1.16
1.25
1.34
1.44
1.55
1.65
1.77
1.89
2.01
2.14
2.28
−
−
−
−
630
686
745
808
874
945
1019
1097
1179
1266
1356
1451
1551
1656
1764
189
1998
−
−
−
−
629
641
652
664
677
689
702
714
727
740
753
766
779
792
806
819
−
−
−
−
−
0.87
0.94
1.01
1.09
1.17
1.25
1.34
1.44
1.54
1.64
1.75
1.86
1.98
2.10
2.23
2.37
−
−
−
−
−
765
825
888
955
1026
1100
1179
1261
1347
1438
1533
1632
1736
1845
1958
2077
−
−
−
−
−
696
706
717
728
739
750
762
773
785
797
809
821
833
846
−
−
−
−
−
−
−
1.03
1.10
1.18
1.26
1.35
1.43
1.53
1.63
1.73
1.84
1.95
2.07
2.19
2.32
−
−
−
−
−
−
−
904
968
1035
1106
1181
1259
1341
1428
1518
1613
1712
1816
1924
2037
−
−
−
−
−
−
−
757
766
776
786
797
807
817
828
839
850
861
873
−
−
−
−
−
−
−
−
−
1.19
1.27
1.35
1.44
1.53
1.62
1.72
1.82
1.93
2.04
2.16
2.28
−
−
−
−
−
−
−
−
−
1048
1115
1186
1261
1340
1422
1508
1598
1693
1791
1894
2002
−
−
−
−
−
−
−
−
−
814
823
832
841
851
860
870
880
890
901
911
−
−
−
−
−
−
−
−
−
−
1.36
1.45
1.53
1.62
1.71
1.81
1.91
2.02
2.13
2.25
2.37
−
−
−
−
−
−
−
−
−
−
1198
1269
1343
1421
1503
1589
1679
1772
1870
1973
2080
−
−
−
−
−
−
−
−
−
−
PGE120 (10 TONS) − STANDARD MOTOR (BELT DRIVE)* (cont)
External Static Pressure (in. wg)
Airflow
(Cfm)
3000
3100
3200
3300
3400
3500
3600
3700
3800
3900
4000
1.2
1.4
1.6
1.8
2.0
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
867
876
884
893
902
911
920
929
939
−
−
1.54
1.63
1.71
1.81
1.90
2.01
2.11
2.22
2.34
−
−
1353
1427
1504
1586
1671
1760
1854
1951
2053
−
−
918
926
934
942
950
959
967
−
−
−
−
1.72
1.81
1.90
2.00
2.10
2.21
2.32
−
−
−
−
1513
1590
1671
1755
1844
1937
2033
−
−
−
−
966
973
981
988
996
−
−
−
−
−
−
1.91
2.00
2.10
2.20
2.30
−
−
−
−
−
−
1680
1760
1843
1931
2022
−
−
−
−
−
−
1012
1019
1026
1033
−
−
−
−
−
−
−
2.11
2.20
2.30
2.40
−
−
−
−
−
−
−
1852
1934
2020
2111
−
−
−
−
−
−
−
1056
−
−
−
−
−
−
−
−
−
−
2.31
−
−
−
−
−
−
−
−
−
−
2029
−
−
−
−
−
−
−
−
−
−
Bhp − Brake Horsepower
Watts − Input Watts to Motor
*Motor drive range: 685 to 935 rpm. All other rpms require
field−supplied drive.
521 21 1001 04
NOTES
1. Boldface indicates field−supplied drive required
2. Maximum continuous Bhp is 2.40
3. See General Notes for Fan Performance following this section
Specifications subject to change without notice.
35
PERFORMANCE DATA − PGE072−150 (CONT.)
FAN PERFORMANCE HORIZONTAL DISCHARGE UNITS
PGE120 (10 TONS) − HIGH STATIC MOTOR (BELT DRIVE)*
Airflow
(Cfm)
3000
3100
3200
3300
3400
3500
3600
3700
3800
3900
4000
4100
4200
4300
4400
4500
4600
4700
4800
4900
5000
Rpm
555
568
582
595
609
623
636
650
664
678
693
707
721
735
750
764
779
793
808
822
837
0.2
Bhp
0.72
0.78
0.85
0.92
1.00
1.08
1.16
1.25
1.34
1.44
1.55
1.65
1.77
1.89
2.01
2.14
2.28
2.42
2.56
2.72
2.88
Watts
630
686
745
808
874
945
1019
1097
1179
1266
1356
1451
1551
1656
1764
1879
1998
2121
2251
2385
2525
Rpm
629
641
652
664
677
689
702
714
727
740
753
766
779
792
806
819
833
846
860
873
887
0.4
Bhp
0.87
0.94
1.01
1.09
1.17
1.25
1.34
1.44
1.54
1.64
1.75
1.86
1.98
2.10
2.23
2.37
2.51
2.65
2.81
2.96
3.13
External Static Pressure (in. wg)
0.6
Watts
Rpm
Bhp
Watts
Rpm
765
696
1.03
904
757
825
706
1.10
968
766
888
717
1.18
1035
776
955
728
1.26
1106
786
1026
739
1.35
1181
797
1100
750
1.43
1259
807
1179
762
1.53
1341
817
1261
773
1.63
1428
828
1347
785
1.73
1518
839
1438
797
1.84
1613
850
1533
809
1.95
1712
861
1632
821
2.07
1816
873
1736
833
2.19
1924
884
1845
846
2.32
2037
896
1958
858
2.45
2154
908
2077
871
2.59
2276
920
2200
883
2.74
2404
932
2328
896
2.89
2537
944
2462
909
3.05
2674
956
2601
922
3.21
2818
968
2745
935
3.38
2966
981
0.8
Bhp
1.19
1.27
1.35
1.44
1.53
1.62
1.72
1.82
1.93
2.04
2.16
2.28
2.41
2.54
2.68
2.82
2.97
3.13
3.29
3.46
3.63
Watts
1048
1115
1186
1261
1340
1422
1508
1598
1693
1791
1894
2002
2114
2231
2352
2479
2611
2747
2889
3037
3189
Rpm
814
823
832
841
851
860
870
880
890
901
911
922
933
944
955
966
978
989
1001
1013
1024
1.0
Bhp
1.36
1.45
1.53
1.62
1.71
1.81
1.91
2.02
2.13
2.25
2.37
2.50
2.63
2.77
2.91
3.06
3.21
3.37
3.54
3.71
3.89
Watts
1198
1269
1343
1421
1503
1589
1679
1772
1870
1973
2080
2191
2307
2428
2553
2684
2820
2960
3106
3258
3414
PGE120 (10 TONS) −HIGH STATIC MOTOR (BELT DRIVE)* (cont)
Airflow
(Cfm)
3000
3100
3200
3300
3400
3500
3600
3700
3800
3900
4000
4100
4200
4300
4400
4500
4600
4700
4800
4900
5000
Rpm
867
876
884
893
902
911
920
929
939
949
959
969
979
990
1000
1011
1022
1033
1044
1055
1066
1.2
Bhp
1.54
1.63
1.71
1.81
1.90
2.01
2.11
2.22
2.34
2.46
2.59
2.72
2.85
3.00
3.14
3.30
3.45
3.62
3.79
3.97
4.15
Watts
1353
1427
1504
1586
1671
1760
1854
1951
2053
2159
2269
2384
2504
2629
2758
2892
3032
3176
3326
3482
3642
Rpm
918
926
934
942
950
959
967
976
985
995
1004
1014
1024
1034
1044
1054
1064
1075
1085
1096
1107
1.4
Bhp
1.72
1.81
1.90
2.00
2.10
2.21
2.32
2.43
2.55
2.68
2.81
2.94
3.08
3.23
3.38
3.54
3.70
3.87
4.04
4.22
4.41
External Static Pressure (in. wg)
1.6
Watts
Rpm
Bhp
Watts
Rpm
1513
966
1.91
1680
1012
1590
973
2.00
1760
1019
1671
981
2.10
1843
1026
1755
988
2.20
1931
1033
1844
996
2.30
2022
1041
1937
1004
2.41
2118
1048
2033
1013
2.53
2217
1056
2134
1021
2.65
2322
1064
2239
1030
2.77
2430
1073
2349
1039
2.90
2543
1081
2462
1048
3.03
2660
1090
2581
1057
3.17
2782
1098
2705
1066
3.31
2909
1107
2833
1076
3.46
3040
1117
2966
1085
3.62
3177
1126
3104
1095
3.78
3319
1135
3247
1105
3.95
3466
1145
3395
1115
4.12
3618
1155
3549
1126
4.30
3775
1164
3708
1136
4.49
3938
1174
3873
1146
4.68
4106
1184
Bhp − Brake Horsepower
Watts − Input Watts to Motor
*Motor drive range: 830 to 1130 rpm. All other rpms require
field−supplied drive.
36
1.8
Bhp
2.11
2.20
2.30
2.40
2.51
2.62
2.74
2.86
2.99
3.12
3.26
3.40
3.55
3.71
3.87
4.03
4.20
4.38
4.56
4.75
4.95
Watts
1852
1934
2020
2111
2205
2303
2406
2513
2625
2741
2861
2987
3117
3252
3392
3537
3688
3843
4004
4171
4342
Rpm
1056
1062
1069
1076
1083
1091
1098
1106
1114
1122
1130
1139
1147
1156
1165
1174
1183
1193
1202
1212
1221
2.0
Bhp
2.31
2.41
2.51
2.62
2.73
2.84
2.96
3.09
3.22
3.35
3.49
3.64
3.79
3.95
4.11
4.28
4.46
4.64
4.83
5.02
5.22
Watts
2029
2114
2203
2295
2393
2494
2600
2710
2824
2943
3067
3195
3329
3467
3611
3759
3913
4072
4237
4406
4582
NOTES
1. Boldface indicates field−supplied drive required
2. Maximum continuous Bhp is 5.25
3. See General Notes for Fan Performance following this section
Specifications subject to change without notice.
521 21 1001 04
PERFORMANCE DATA − PGE072−150 (CONT.)
FAN PERFORMANCE HORIZONTAL DISCHARGE UNITS
PGE150 (121/2 TONS) − STANDARD MOTOR (BELT DRIVE)*
Airflow
(Cfm)
External Static Pressure (in. wg)
0.2
0.4
0.6
0.8
1.0
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
3700
676
1.19
1106
747
1.42
1328
811
1.66
1552
871
1.91
1779
927
2.15
2008
3800
690
1.27
1185
760
1.52
1414
823
1.76
1644
882
2.01
1876
938
2.26
2111
3900
705
1.36
1269
773
1.61
1503
835
1.86
1739
894
2.12
1977
948
2.38
2217
4000
719
1.45
1357
786
1.71
1597
848
1.97
1838
905
2.23
2082
959
2.50
2328
4100
734
1.55
1449
799
1.82
1695
860
2.08
1942
917
2.35
2192
970
2.62
2443
4200
748
1.66
1545
813
1.93
1797
872
2.20
2050
928
2.47
2305
981
2.75
2562
4300
763
1.76
1646
826
2.04
1903
885
2.32
2162
940
2.60
2423
992
2.88
2686
4400
778
1.88
1751
840
2.16
2014
898
2.44
2279
952
2.73
2546
1004
3.02
2814
4500
792
1.99
1860
853
2.28
2130
910
2.57
2401
964
2.87
2673
1015
3.16
2947
4600
807
2.12
1975
867
2.41
2250
923
2.71
2527
976
3.01
2805
1027
3.31
3085
4700
822
2.25
2094
881
2.55
2375
936
2.85
2658
989
3.15
2942
1038
3.46
3227
4800
837
2.38
2218
895
2.69
2505
949
3.00
2794
1001
3.31
3083
1050
3.62
3375
4900
852
2.52
2347
909
2.83
2640
963
3.15
2935
1014
3.46
3230
−
−
−
5000
867
2.66
2482
923
2.98
2781
976
3.30
3081
1026
3.63
3383
−
−
−
5100
882
2.81
2622
937
3.14
2926
989
3.47
3232
−
−
−
−
−
−
5200
897
2.97
2766
951
3.30
3077
1003
3.63
3389
−
−
−
−
−
−
5300
912
3.13
2917
966
3.47
3233
−
−
−
−
−
−
−
−
−
5400
927
3.30
3073
980
3.64
3395
−
−
−
−
−
−
−
−
−
5500
943
3.47
3234
−
−
−
−
−
−
−
−
−
−
−
−
5600
958
3.65
3402
−
−
−
−
−
−
−
−
−
−
−
−
5700
−
−
−
−
−
−
−
−
−
−
−
−
−
−
−
5800
−
−
−
−
−
−
−
−
−
−
−
−
−
−
−
5900
−
−
−
−
−
−
−
−
−
−
−
−
−
−
−
6000
−
−
−
−
−
−
−
−
−
−
−
−
−
−
−
PGE150 (121/2 TONS) − STANDARD MOTOR (BELT DRIVE)* (cont)
Airflow
(Cfm)
External Static Pressure (in. wg)
1.2
1.4
1.6
1.8
2.0
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
3700
981
2.40
2240
1031
2.65
2473
1079
2.91
2709
1125
3.16
2948
1169
3.42
3189
3800
990
2.52
2348
1040
2.77
2587
1088
3.03
2828
1133
3.30
3073
1177
3.56
3319
3900
1000
2.64
2459
1050
2.90
2705
1097
3.17
2951
1142
3.43
3201
1186
3.70
3452
4000
1011
2.76
2576
1059
3.03
2826
1106
3.30
3079
1151
3.58
3334
−
−
−
4100
1021
2.89
2697
1069
3.17
2953
1116
3.44
3210
−
−
−
−
−
−
4200
1031
3.03
2822
1079
3.31
3083
1125
3.59
3347
−
−
−
−
−
−
4300
1042
3.16
2951
1089
3.45
3218
−
−
−
−
−
−
−
−
−
4400
1053
3.31
3085
1100
3.60
3357
−
−
−
−
−
−
−
−
−
4500
1064
3.46
3224
−
−
−
−
−
−
−
−
−
−
−
−
4600
1075
3.61
3367
−
−
−
−
−
−
−
−
−
−
−
−
4700
−
−
−
−
−
−
−
−
−
−
−
−
−
−
−
4800
−
−
−
−
−
−
−
−
−
−
−
−
−
−
−
Bhp − Brake Horsepower
Watts − Input Watts to Motor
*Motor drive range: 860 to 1080 rpm. All other rpms require
field−supplied drive.
521 21 1001 04
NOTES
1. Boldface indicates field−supplied drive required
2. Maximum continuous Bhp is 3.70
3. See General Notes for Fan Performance following this section
Specifications subject to change without notice.
37
PERFORMANCE DATA − PGE072−150 (CONT.)
FAN PERFORMANCE HORIZONTAL DISCHARGE UNITS
PGE150 (121/2 TONS) − ALTERNATE / HIGH STATIC MOTOR (BELT DRIVE)*
AIRFLOW
(Cfm)
3700
3800
3900
4000
4100
4200
4300
4400
4500
4600
4700
4800
4900
5000
5100
5200
5300
5400
5500
5600
5700
5800
5900
6000
6100
6200
6300
Rpm
676
690
705
719
734
748
763
778
792
807
822
837
852
867
882
897
912
927
943
958
973
988
1004
1019
1034
1050
1065
0.2
Bhp
1.19
1.27
1.36
1.45
1.55
1.66
1.76
1.88
1.99
2.12
2.25
2.38
2.52
2.66
2.81
2.97
3.13
3.30
3.47
3.65
3.83
4.03
4.22
4.43
4.64
4.86
5.09
Watts
1106
1185
1269
1357
1449
1545
1646
1751
1860
1975
2094
2218
2347
2482
2622
2766
2917
3073
3234
3402
3575
3754
3939
4131
4329
4533
4744
Rpm
747
760
773
786
799
813
826
840
853
867
881
895
909
923
937
951
966
980
994
1009
1023
1038
1052
1067
1082
−
−
0.4
Bhp
1.42
1.52
1.61
1.71
1.82
1.93
2.04
2.16
2.28
2.41
2.55
2.69
2.83
2.98
3.14
3.30
3.47
3.64
3.82
4.01
4.20
4.40
4.60
4.81
5.03
−
−
EXTERNAL STATIC PRESSURE (in. wg)
0.6
Watts
Rpm
Bhp
Watts
Rpm
1328
811
1.66
1552
871
1414
823
1.76
1644
882
1503
835
1.86
1739
894
1597
848
1.97
1838
905
1695
860
2.08
1942
917
1797
872
2.20
2050
928
1903
885
2.32
2162
940
2014
898
2.44
2279
952
2130
910
2.57
2401
964
2250
923
2.71
2527
976
2375
936
2.85
2658
989
2505
949
3.00
2794
1001
2640
963
3.15
2935
1014
2781
976
3.30
3081
1026
2926
989
3.47
3232
1039
3077
1003
3.63
3389
1052
3233
1016
3.81
3551
1065
3395
1030
3.99
3719
1078
3563
1044
4.17
3892
1091
3736
1057
4.37
4071
1104
3915
1071
4.56
4256
1117
4100
1085
4.77
4447
1130
4292
1099
4.98
4645
−
4489
1113
5.20
4848
−
4693
−
−
−
−
−
−
−
−
−
−
−
−
−
−
0.8
Bhp
1.91
2.01
2.12
2.23
2.35
2.47
2.60
2.73
2.87
3.01
3.15
3.31
3.46
3.63
3.80
3.97
4.15
4.34
4.53
4.73
4.93
5.14
−
−
−
−
−
Watts
1779
1876
1977
2082
2192
2305
2423
2546
2673
2805
2942
3083
3230
3383
3540
3702
3870
4044
4223
4408
4599
4796
−
−
−
−
−
Rpm
927
938
948
959
970
981
992
1004
1015
1027
1038
1050
1062
1074
1086
1099
1111
1123
1136
1149
−
−
−
−
−
−
−
1.0
Bhp
2.15
2.26
2.38
2.50
2.62
2.75
2.88
3.02
3.16
3.31
3.46
3.62
3.78
3.95
4.13
4.31
4.49
4.69
4.88
5.09
−
−
−
−
−
−
−
Watts
2008
2111
2217
2328
2443
2562
2686
2814
2947
3085
3227
3375
3528
3685
3849
4017
4191
4370
4555
4746
−
−
−
−
−
−
−
1.8
Bhp
3.16
3.30
3.43
3.58
3.72
3.87
4.03
4.19
4.36
4.53
4.71
4.89
5.08
−
−
−
−
−
−
Watts
2948
3073
3201
3334
3471
3612
3758
3909
4064
4224
4389
4559
4734
−
−
−
−
−
−
Rpm
1169
1177
1186
1194
1203
1212
1221
1230
1239
1249
1258
1268
−
−
−
−
−
−
−
2.0
Bhp
3.42
3.56
3.70
3.85
4.00
4.16
4.32
4.49
4.66
4.84
5.02
5.21
−
−
−
−
−
−
−
Watts
3189
3319
3452
3591
3733
3880
4031
4187
4348
4514
4684
4860
−
−
−
−
−
−
−
PGE150 (121/2 TONS) − ALTERNATE / HIGH STATIC MOTOR (BELT DRIVE)* (cont)
AIRFLOW
(Cfm)
3700
3800
3900
4000
4100
4200
4300
4400
4500
4600
4700
4800
4900
5000
5100
5200
5300
5400
5500
Rpm
981
990
1000
1011
1021
1031
1042
1053
1064
1075
1086
1097
1109
1120
1132
1144
1155
1167
1179
1.2
Bhp
2.40
2.52
2.64
2.76
2.89
3.03
3.16
3.31
3.46
3.61
3.77
3.93
4.10
4.28
4.46
4.65
4.84
5.04
5.24
Watts
2240
2348
2459
2576
2697
2822
2951
3085
3224
3367
3515
3668
3826
3990
4159
4333
4512
4697
4889
Rpm
1031
1040
1050
1059
1069
1079
1089
1100
1110
1121
1131
1142
1153
1164
1175
1187
1198
−
−
1.4
Bhp
2.65
2.77
2.90
3.03
3.17
3.31
3.45
3.60
3.76
3.91
4.08
4.25
4.43
4.61
4.79
4.99
5.19
−
−
EXTERNAL STATIC PRESSURE (in. wg)
1.6
Watts
Rpm
Bhp
Watts
Rpm
2473
1079
2.91
2709
1125
2587
1088
3.03
2828
1133
2705
1097
3.17
2951
1142
2826
1106
3.30
3079
1151
2953
1116
3.44
3210
1160
3083
1125
3.59
3347
1169
3218
1135
3.74
3487
1179
3357
1145
3.90
3632
1188
3502
1155
4.06
3782
1198
3650
1165
4.22
3937
1208
3805
1175
4.39
4096
1217
3963
1186
4.57
4260
1228
4128
1196
4.75
4430
1238
4296
1207
4.94
4604
−
4471
1218
5.13
4784
−
4651
−
−
−
−
4836
−
−
−
−
−
−
−
−
−
−
−
−
−
−
Bhp − Brake Horsepower
NOTES
Watts − Input Watts to Motor
1. Boldface indicates field−supplied drive required
*Motor drive range: 830 to 1130 rpm. All other rpms require 2. Maximum continuous Bhp is 5.25
field−supplied drive.
3. See General Notes for Fan Performance following this section
GENERAL NOTES FOR FAN PERFORMANCE TABLES:
1. Extensive motor and electrical testing on these units ensures that the full range of the motor can be utilized with confidence. Using your fan
motors up to the wattage ratings shown will not result in nuisance tripping or premature motor failure. Unit warranty will not be affected. For
additional information on motor performance, refer to Indoor Fan Motor Performance table.
2. Values include losses for filters, unit casing, and wet coils. Refer to Accessory/FIOP Static Pressure tables for accessory static pressure
information.
3. Use of a field−supplied motor may affect wire sizing.
4. Interpolation is permissible. Do not extrapolate.
38
Specifications subject to change without notice.
521 21 1001 04
PERFORMANCE DATA − PGE072−150 (cont.)
OUTDOOR SOUND POWER (Total Unit)
UNIT PGE
072
090, 102
120
150
SOUND
RATING 60
Hz (dB)
80
82
84
86
OCTAVE BANDS
63
59.1
62.2
64.6
63.7
A−WEIGHTED (dB)
80.0
82.0
84.0
86.0
125
68.9
69.3
71.7
69.9
250
68.7
71.5
73.3
72.5
500
71.9
74.7
76.9
78.2
1000
74.0
76.2
77.6
81.1
2000
68.9
72.9
73.7
77.3
4000
65.7
68.7
70.6
73.3
8000
59.0
61.5
63.7
66.8
ACCESSORY/FIOP ECONOMIZER STATIC PRESSURE* (in. wg) − PGE072
CFM
1250
0.045
−
COMPONENT
Vertical Economizer
Horizontal Economizer
1500
0.065
−
1750
0.08
0.1
2000
0.12
0.125
2250
0.145
0.15
2500
0.175
0.18
2750
0.22
0.225
3000
0.255
0.275
NOTE: Performance is for the DN series Economizer
ACCESSORY/FIOP ECONOMIZER STATIC PRESSURE* (in. wg) − PGE090−150
COMPONENT
Vertical Economizer
Horizontal Economizer
2250
0.06
−
2500
0.075
0.1
2750
0.09
0.125
3000
0.115
0.15
3250
0.13
0.18
3500
0.15
0.21
CFM
3750
4000
0.17
0.195
0.25
0.275
4250
0.22
0.3
4500
0.25
0.34
4750
0.285
0.388
5000
0.325
−
5250
0.36
−
6250
−
−
LEGEND
FIOP − Factory Installed Option
*The static pressure must be added to external static pressure. The sum and indoor−entering air cfm should be used in conjunction with the Fan Performance
tables to determine blower rpm and watts.
NOTE: Performance is for the DN series Economizer
FAN RPM AT MOTOR PULLEY SETTINGS* − PGE072
UNIT PGE
072 {{
072**
0
1460
1685
1/2
1421
1647
1
1382
1608
11/2
1343
1570
2
1304
1531
MOTOR PULLEY TURNS OPEN
21/2
3
31/2
1265
1226
1187
1493
1454
1416
4
1148
1377
41/2
1109
1399
5
1070
1300
51/2
−
−
6
−
−
FAN RPM AT MOTOR PULLEY SETTINGS* − PGE090−150
UNIT PGE
090 {{
090**
102 {{
102**
120 {{
120**
150 {{
150 **
0
840
1080
935
1080
935
1130
1080
1130
1/2
815
1025
910
1025
910
1112
1060
1112
1
790
1007
885
1007
885
1087
1035
1087
11/2
765
988
860
988
860
1062
1015
1062
MOTOR PULLEY TURNS OPEN
2
21/2
3
31/2
740
715
690
665
970
952
933
915
835
810
785
760
970
952
933
915
835
810
785
760
1037
1012
987
962
990
970
950
925
1037
1012
987
962
4
635
897
735
897
735
937
905
937
41/2
615
878
710
878
710
912
880
912
5
590
860
685
860
685
887
860
887
51/2
−
−
−
−
−
862
−
862
* Approximate fan rpm shown
** Indicates high−static motor and drive package
{{ Indicates standard motor and drive package
521 21 1001 04
Specifications subject to change without notice.
39
6
−
−
−
−
−
830
−
830
PERFORMANCE DATA − PGE072−150 (cont.)
ALTITUDE COMPENSATION* STANDARD UNITS − PGE072
74,000 AND 115,000 BTUH NOMINAL INPUT
ELEVATION (ft)
0−2,000
2,000
3,000
4,000
5,000
6,000
7,000
8,000
9,000
10,000
11,000
12,000
13,000
14,000
Natural Gas Orifice Size {
33
36
36
37
38
40
41
42
43
44
45
46
47
48
Liquid Propane Orifice Size {
43
44
45
45
46
47
48
49
50
50
51
52
52
53
150,000 BTUH NOMINAL INPUT
Natural Gas Orifice Size {
30
31
31
32
32
34
35
36
37
39
41
42
43
44
Liquid Propane Orifice Size {
37
39
40
41
42
43
43
44
45
46
47
48
49
50
ALTITUDE COMPENSATION* − PGE090−150
125,000,180,000, AND 224,000 BTUH NOMINAL INPUT
250,000 BTUH NOMINAL INPUT
Liquid Propane Orifice
Liquid Propane Orifice
Size
Size
Natural Gas Orifice Size
Natural Gas Orifice Size
ELEVATION (ft)
0−2,000
31
41
30
38
2,000
32
42
30
39
3,000
32
42
31
40
4,000
32
42
32
41
5,000
33
43
33
42
6,000
34
43
34
43
7,000
35
44
35
43
8,000
36
44
36
44
9,000
37
45
37
44
10,000
38
46
38
45
11,000
39
47
39
45
12,000
40
47
40
46
13,000
41
48
41
47
14,000
42
48
42
47
*As the height above sea level increases, there is less oxygen per cubic foot of air, so the input rate should be reduced at higher altitudes.
†Orifices are available through your distributor.
ALTITUDE DERATING FACTOR*
ELEVATION (ft.)
MAXIMUM HEATING VALUE (Btu/ft3)
0−2,000
1,100
2,001−3,000
1,050
3,001−4,000
1,000
4,001−5,000
950
5,001−6,000
900
*Derating of the unit is not required unless the heating value of the gas exceeds the values listed in the table above, or if the elevation exceeds 6000 ft. Derating conditions
must be 4% per thousand ft above 2000 ft. For example at 4000 ft, if the heating value of the gas exceeds 1000 Btu/ft3, the unit requires a 16% derating. For elevations
above 6000 ft, the same formula applies. For example at 7000 ft, the unit requires a 28% derating of the maximum heating value per the National Fuel Gas Code.
IMPORTANT: Local utility companies may be reducing heat content of gas at altitudes above 2000 ft. If this is being done, changing spuds may not be required.
40
Specifications subject to change without notice.
521 21 1001 04
PERFORMANCE DATA − PGE072−150 (cont.)
Vertical Economizer
5000
FLOW (cfm)
4000
3000
6 Ton
2000
7.5−12.5 Ton
1000
0
0
0.1
0.2
0.3
0.4
a48-6308
0.5
STATIC PRESSURE (in. wg)
FLOW IN CUBIC FEET PER MINUTE (cfm)
VERTICAL POWER EXHAUST PERFORMANCE
2500
2000
6 Ton
1500
7 1/2 − 12 1/2 Ton
1000
500
0
0.15
0.05
0.25
a48-6202
STATIC PRESSURE (in. wg)
FLOW IN CUBIC FEET PER MINUTE (cfm)
BAROMETRIC RELIEF FLOW CAPACITY
30
25
20
6 Ton
15
7 1/2 − 12 1/2 Ton
10
5
0
a48-6203
0.13
0. 2 0
0. 22
0. 25
0. 30
0. 35
0 . 40
0.45
0.50
STATIC PRESSURE (in. wg)
OUTDOOR AIR DAMPER LEAKAGE
NOTE: Performance is for the DN series Economizer
POWER EXHAUST OPTIONS
POWER EXHAUST
PART NO.
DNPWREXH030A01
DNPWREXH021A01
DNPWREXH022A01
DNPWREXH023A01
VERTICAL − MOUNTED IN ECONOMIZER HOOD
APPLICATION
POWER EXHAUST DESCRIPTION
USAGE
Power Exhaust System (208/230−1−60)
072
Power Exhaust System (460−3−60)
072
Power Exhaust System (208/230−1−60)
090−150
Power Exhaust System (460−3−60)
090−150
POWER OUTPUT
(Hp per fan)
0.23
0.24
0.47
0.37
NO.
FANS
2
2
2
2
POWER EXHAUST
PART NO.
DNPWREXH028A01
DNPWREXH029A01
HORIZONTAL − MOUNTED IN RETURN DUCTWORK
APPLICATION
POWER EXHAUST DESCRIPTION
USAGE
Horizontal Power Exhaust (208/230−1−60)
All
Horizontal Power Exhaust (460−3−60)
All
POWER OUTPUT
(Hp per fan)
0.48
0.48
NO.
FANS
1
1
521 21 1001 04
Specifications subject to change without notice.
41
PERFORMANCE DATA − PGE072−150 (cont.)
Horizontal Economizer
2500
FLOW (cfm)
2000
1500
1000
500
0
0
0.1
0.2
0.3
0.4
0.5
a48-6309
Fl ow i n cub i c feet per m in ute (cfm )
STATIC PRESSURE (in. wg)
HORIZONTAL POWER EXHAUST PERFORMANCE
2500
2000
1500
6 Ton
7 1/2 − 12 1/2 Ton
1000
500
0
0. 05”
0. 15”
0. 25”
Static Pressure (in. wg)
Fl ow i n cubi c feet p er m i nute (cfm )
BAROMETRIC RELIEF CAPACITY
30
25
20
6 Ton
15
7 1/2 − 12 1/2 Ton
10
5
a48-6225
0
0. 1”
0. 2”
0.3”
0. 4”
0. 5”
Static Pressure (in. wg)
OUTDOOR AIR DAMPER LEAKAGE
NOTE: Performance is for the DN series Economizer
OPTIONAL POWER EXHAUST
UNIT
PGE
072
090−150
AMPS AT 230 V (2
Fans Running)
1.40 Amps at 60 Hz
3.04 Amps at 60 Hz
230 VAC
MOCP
460 VAC
575 VAC
15.0 amps
15.0 amps
15.0 amps
LEGEND
MOCP − Maximum Overcurrent Protection
EVAPORATOR−FAN MOTOR EFFICIENCY
UNIT PGE
072
090−120
150
42
MOTOR EFFICIENCY (%)
84
80
87
NOTE: The EPACT (Energy Policy Act of 1992) regulates energy requirements
for specific types of indoor fan motors. Motors regulated by EPACT include any
general purpose, T−frame (three−digit, 143 and larger), single−speed, foot
mounted, polyphase, squirrel cage induction motors of NEMA (National
Electrical Manufacturers Association) design A and B, manufactured for use in
the United States. Ranging from 1 to 200 Hp, these continuous−duty motors
operate on 230 and 460 volt,60 Hz power. If a motor does not fit into these
specifications, the motor does not have to be replaced by an EPACT−compliant
energy efficient motor. Variable speed motors are exempt from EPACT
compliance requirements. Therefore, the indoor−fan motors for these units are
exempt from these requirements.
Specifications subject to change without notice.
521 21 1001 04
PERFORMANCE DATA − PGE072−150 (cont.)
EVAPORATOR−FAN MOTOR PERFORMANCE
UNIT
PGE
EVAPORATOR FAN
MOTOR
Standard
072
High Static
Standard
090
High Static
Standard
102
High Static
Standard
120
High Static
Standard
150
High Static
UNIT
VOLTAGE
208/230
460
575
208/230
460
575
208/230
460
575
208/230
460
575
208/230
460
575
208/230
460
575
208/230
460
575
208/230
460
575
208/230
460
575
208/230
460
575
MAXIMUM ACCEPTABLE
CONTINUOUS BHP*
MAXIMUM ACCEPTABLE
OPERATING WATTS
2.40
2120
2.90
2562
2.40
2120
3.70
3313
2.40
2120
3.70
3313
2.40
2120
5.25
4400
3.70
3313
5.25
4400
MAXIMUM
AMP DRAW
5.2
3.0
3.0
8.6
3.9
3.9
6.7
3.0
3.0
12.2
5.5
5.5
6.7
3.0
3.0
12.2
5.5
5.5
6.7
3.0
3.0
17.3
8.5
8.5
12.2
5.5
5.5
17.3
8.5
8.5
LEGEND
BHP − Brake Horsepower
*Extensive motor and electrical testing on these units ensures that the full horsepower range of the motors can be utilized with confidence.
Using your fan motors up to the horsepower ratings shown in this table will not result in nuisance tripping or premature motor failure. Unit
warranty will not be affected.
521 21 1001 04
Specifications subject to change without notice.
43
ELECTRICAL DATA − PGE072−150
Unit
Size
PGE
072
Nominal
V- ph-Hz
IFM
Type
208/230
-3-60
STD
High
STD
High
STD
High
STD
High
STD
High
STD
High
460-3-60
575-3-60
208/230
-3-60
090
460-3-60
575-3-60
Unit
Size
PGE
102
Nominal
V- ph-Hz
IFM
Type
208/230
-3-60
STD
High
STD
High
STD
High
STD
High
STD
High
STD
High
STD
460-3-60
208/230
-3-60
460-3-60
575-3-60
208/230
-3-60
150
460-3-60
575-3-60
High
STD
High
STD
High
Compressor
(each)
OFM
(each)
IFM
Min
Max
Qty
RLA
LRA
Qty
FLA
187
254
1
20.6
146
1
1.4
414
508
1
9.5
73
1
0.9
518
632
1
7.6
62
1
0.6
187
254
2
14
91
2
1.4
414
508
2
6.4
42
2
0.7
518
632
2
5.2
39
2
0.6
Voltage
Range
Min
575-3-60
120
Voltage
Range
Max
Compressor
(each)
Qty
OFM
(each)
FLA
5.2
7.5
2.6
3.4
1.9
2.0
5.8
10.6
2.6
4.8
2.0
2.8
IFM
RLA
LRA
Qty
FLA
2
1.4
187
254
2
17.3
120.
0
414
508
2
7.9
70.0
2
0.7
518
632
2
5.5
50.0
2
0.6
187
254
2
15.8
130
2
1.4
414
508
2
7.9
64
2
0.7
518
632
2
6.6
52
2
0.6
187
254
2
19
156
2
1.4
414
508
2
9
75
2
0.7
518
632
2
7.4
54
2
0.6
FLA
5.8
10.6
2.6
4.8
2.0
2.8
5.8
15.0
2.6
7.4
2.0
3.3
10.6
15.0
4.8
7.4
3.3
5.6
Combustion
Fan Motor
FLA
0.6
0.3
0.3
0.6
0.3
0.3
MCA
32.4
34.7
15.4
16.2
15
20
40.1
44.9
18.4
20.6
20
20
Combustion
Fan Motor
FLA
0.6
0.3
0.3
0.6
0.3
0.3
0.6
0.3
0.3
FLA
31
34
15
16
13
14
42
48
19
22
16
18
Min. Unit
Disconnect
Size*
LRA
180
205
90
103
75
84
229
273
108
130
97
114
FLA
46
52
22
24
17
19
46
57
23
28
19
23
59
64
28
31
23
25
Min. Unit
Disconnect
Size*
LRA
272
316
149
171
109
126
307
374
152
185
123
155
359
378
174
213
127
159
Power
Supply
MOCP
40
40
20
20
12.3
13.1
45
50
20
25
14.9
16.7
Power
Supply
MCA
44.3
49.1
21.0
23.2
16.7
18.5
44.6
53.8
22.0
26.8
18.1
21.9
56.2
60.6
26.5
29.1
21.6
23.7
MOCP
50
60
25
30
20
25
50
60
25
30
20
25
70
70
30
35
25
25
See Legend and Notes for Electrical Data following this section.
44
Specifications subject to change without notice.
521 21 1001 04
ELECTRICAL DATA − PGE072−150 (cont.)
LEGEND
Determine maximum deviation from average voltage.
(AB) 457 – 452 = 5 v
(BC) 464 – 457 = 7 v
(AC) 457 – 455 = 2 v
FLA - Full Load Amps
HACR - Heating, Air Conditioning and Refrigeration
IFM - Indoor Fan Motor
LRA - Locked Rotor Amps
MCA - Minimum Circuit Amps
MOCP - Maximum Overcurrent Protection
NEC - National Electrical Code
OFM - Outdoor Fan Motor
RLA - Rated Load Amps
Maximum deviation is 7 v.
Determine percent of voltage imbalance.
% Voltage Imbalance = 100 x
7
457
= 1.53%
This amount of phase imbalance is satisfactory as it is below the maximum
allowable 2%.
IMPORTANT: If the supply voltage phase imbalance is more than 2%, contact
your local electric utility company immediately.
3. For units with power exhaust: If a single power source is to be used, size wire
to include power exhaust MCA and MOCP. Check MCA and MOCP when power
exhaust is powered through the unit (must be in accordance with NEC and/or
local codes). Determine the new MCA including the power exhaust using the
following formula:
*Used to determine minimum disconnect per NEC.
{Fuse or HACR circuit breaker.
NOTES:
1. In compliance with NEC requirements for multimotor and combination load
equipment (refer to NEC Articles 430 and 440), the overcurrent protective
device for the unit shall be fuse or HACR breaker.
2. Unbalanced 3-Phase Supply Voltage Never operate a motor where a phase
imbalance in supply voltage is greater than 2%. Use the following formula to
determine the percent of voltage imbalance.
% Voltage Imbalance
MCA New = MCA unit only + MCA of Power Exhaust
MCA New = 28.9 amps + 1.6 amps = 30.5 amps
If the new MCA does not exceed the published MOCP, then MOCP would not
change. The MOCP in this example is 35 amps, the MCA New is below 35,
therefore the MOCP is acceptable. If MCA New is larger than the published
MOCP, raise the MOCP to the next larger size. For separate power, the MOCP for
the power exhaust will be 15 amps per NEC.
POWER EXHAUST ELECTRICAL DATA
MCA
(460V)
MCA
(575V)
MOCP
(separate
power
source
only)
1.6
N/A
0.64
15
N/A
0.68
N/A
15
3.4
N/A
1.32
15
090-150
N/A
1.4
N/A
15
DNPWREXH028A01
ALL
1.7
N/A
0.68
15
DNPWREXH029A01
ALL
N/A
0.7
N/A
15
= 100 x max voltage deviation from average voltage
average voltage
Example: Supply voltage is 460-3-60.
Power Exhaust
Part No.
Application
Usage
DNPWREXH030A01
072
DNPWREXH021A01
072
DNPWREXH022A01
090-150
DNPWREXH023A01
MCA
(230V)
Unit
AB = 452 v
BC = 464 v
AC = 455 v
Average Voltage = 452 + 464 + 455
3
= 31371
3
= 457
521 21 1001 04
Model
AXB035PEH
Application
Usage
072
Volt/Phase/Hertz
208/230/1/60
LRA
10.2
FLA
4.3
MCA
5.4
Fuse
Size
10
AXB035PEL
072
460/1/60
4.1
1.7
2.2
4
AXB035PES
AXB145PEH
AXB145PEL
AXB145PES
AXB245PEH
AXB245PEL
AXB245PES
072
90-102
90-102
90-102
120-150
120-150
120-150
575/1/60
208-230/1/60
460/1/60
575/1/60
208-230/1/60
460/1/60
575/1/60
4.1
10.2
4.1
4.1
24.9
N/A
N/A
1.7
4.3
1.7
1.7
5.0
2.2
1.5
2.2
5.4
2.2
2.2
6.3
2.8
1.9
4
8
5
5
10
5
4
NOTE: AXB power exhaust is wired single phase, drop third leg when installing.
Specifications subject to change without notice.
45
TYPICAL WIRING SCHEMATICS − PGE072−150
PGE090 − 208/230v SHOWN
120
150
46
Specifications subject to change without notice.
521 21 1001 04
TYPICAL WIRING SCHEMATICS − PGE072−150 (cont.)
ECONOMIZER WIRING − PGE072−150
ECONOMIZER
ECONOMIZER NOTES:
1. 620 ohm, 1 watt 5% resister should be removed only when using differential
enthalpy or dry bulb.
2. If a separate field supplied 24v transformer is used for the IAQ sensor
power supply, it cannot have the secondary of the transformer grounded.
3. For field installed remote minimum position POT, remove black wire jumper
between P and P1 and set control minimum position POT to the minimum
position.
LEGEND
NOTES:
Potentiometer Default Settings:
Power Exhaust Middle
Minimum Pos − Fully Closed
DCV Max. − Middle
DCV Set − Middle
Enthalpy C Setting
NOTE: Wiring is for the DN series Economizer
IAQ − Indoor Air Quality
LA − Low Ambient Lockout Device
POT − Potentiometer
OAT − Outdoor Air Temperature
RAT − Return Air Temperature
TYPICAL WIRING SCHEMATICS − PGE072−150 (cont.)
NON−FUSED DISCONNECT (Optional) − PGE072−150
UNIT
DISCONNECT
FIELD
POWER
SUPPLY
BLK
BLK
YEL
YEL
BLU
BLU
BLK
a48−7463
TB
BLK
YEL
YEL
BLU
BLU
SINGLE POINT CONNECTION BOX
NOTE: Use copper conductors only.
521 21 1001 04
Specifications subject to change without notice.
47
TYPICAL PIPING AND WIRING − PGE072−150 (cont.)
VERTICAL DISCHARGE DUCTING
50−1279
HORIZONTAL DISCHARGE DUCTING
CONVENIENCE
OUTLET
NO.1
NO.2
a48-6307
NEC Ċ National Electrical Code
48
Specifications subject to change without notice.
521 21 1001 04
GUIDE SPECIFICATIONS − PGE072−150
PART 1 − GENERAL
1.01 SYSTEM DESCRIPTION
Outdoor rooftop mounted, electrically controlled heating and cooling
unit utilizing a hermetic compressor(s) for cooling duty and gas
combustion for heating duty. Unit shall discharge supply air vertically
or horizontally as shown on contract drawings.
1.02 QUALITY ASSURANCE
A. Unit well exceeds ASHRAE 90.1−2001 Energy Standards.
B. Unit shall be rated in accordance with ARI Standards 210 or 360.
Designed in accordance with UL Standard 1995.
C. Unit shall be designed to conform to ASHRAE 15, latest revision.
D. Unit shall be UL tested and certified in accordance with ANSI
Z21.47 Standards and UL listed and certified under Canadian
standards as a total package for safety requirements.
E. Roof curb shall be designed to conform to NRCA Standards.
F. Insulation and adhesive shall meet NFPA 90A requirements for
flame spread and smoke generation.
G. Unit casing shall be capable of withstanding 500 hour salt spray
exposure per ASTM B117 (scribed specimen).
H. Unit shall be designed in accordance with ISO 9001:2000, and
shall be manufactured in a facility registered to ISO 9001:2000.
I. Each unit shall be subjected to a completely automated run testing
on the assembly line. A factory supplied printout indicating tested
pressures, amperages, data, and inspectors; providing
certification of the unit status at the time of manufacture, shall be
available upon request.
1.03 DELIVERY, STORAGE, AND HANDLING
Unit shall be stored and handled per manufacturer’s
recommendations.
PART 2 − PRODUCTS
2.01 EQUIPMENT (STANDARD)
A. General: Factory assembled, single piece heating and cooling
unit. Contained within the unit enclosure shall be all factory
wiring, piping, controls, refrigerant charge (R−22), and special
features required prior to field start−up.
B. Unit Cabinet:
1. Unit cabinet shall be constructed of galvanized steel, and shall
be bonderized and coated with a pre−painted baked enamel
finish on all externally exposed surfaces.
2. Evaporator fan compartment interior cabinet surfaces shall be
insulated with a minimum in. thick, 1 lb density, flexible
fiberglass insulation, neoprene coated on the air side.
Aluminum foil−faced fiberglass insulation shall be used in the
gas heat compartment.
3. Cabinet panels shall be easily removable for servicing.
4. Holes shall be provided in the base rails for rigging shackles to
facilitate maneuvering and overhead rigging.
5. Unit shall have a factory installed, sloped condensate drain
pan made of a non corrosive material, providing a minimum in.−14 NPT connection with both vertical and horizontal
drains, and shall comply with ASHRAE Standard 62.
6. Unit shall have a factory installed filter access panel to provide
filter access with toolless removal.
7. Unit shall have standard thru−the−bottom gas and power
connection capability (accessory kit is required).
C. Fans:
1. Evaporator Fan:
a. Fan shall be belt driven as shown on the equipment
drawings. Belt drive shall include an adjustable pitch motor
pulley.
b. Fan wheel shall be double inlet type with forward curved
blades.
c. Bearings shall be sealed, permanently lubricated ball
bearing type for longer life and lower maintenance.
2. Evaporator fan shall be made from steel with a corrosion
resistant finish and shall be dynamically balanced.
3. Rooftop evaporator fan motors smaller than 5 hp are
specifically designed and are rated in maximum continuous
Bhp or maximum continuous watts. The motors do not have a
horsepower rating on the nameplate.
4. Condenser fan shall be of the direct driven (with totally
enclosed motors) propeller type and shall discharge air
vertically.
521 21 1001 04
5. Condenser fan shall have aluminum blades riveted to
corrosion resistant steel spiders and shall be dynamically
balanced.
6. Induced draft blower shall be of the direct driven, single inlet,
forward curved centrifugal type, made from steel with a
corrosion resistant finish and shall be dynamically balanced.
D. Compressor(s):
1. Fully hermetic type, internally protected scroll type.
2. Factory mounted on rubber grommets and internally spring
mounted for vibration isolation.
3. On dual electrically and mechanically independent circuits
(090−150).
E. Coils:
1. Standard evaporator and condenser coils shall have
aluminum lanced plate fins mechanically bonded to seamless
internally grooved 3/8­in. OD copper tubes with all joints
brazed.
2. Dual compressor models (size 090−150) shall have face−split
type evaporator coil (circuit no. 1 on bottom).
3. Testing:
a. Evaporator and condenser coils shall be qualified to UL
1995 burst test at 2,200 psi.
b. Evaporator and condenser coils shall be leak tested to 150
psig and pressure tested to 400 psig.
F. Heating Section:
1. Induced draft combustion type with energy saving direct spark
ignition system and redundant main gas valve.
2. Heat Exchanger:
a. The standard heat exchanger shall be of the tubular section
type constructed of a minimum of 20 gage steel coated with
a nominal 1.2 mil aluminum silicone alloy for corrosion
resistance.
3. Burners shall be of the in shot type constructed of aluminum
coated steel.
4. All gas piping shall enter the unit cabinet at a single location on
side of unit (horizontal plane).
5. The integrated gas controller (IGC) board shall include gas heat
operation fault notification using an LED (light emitting diode).
6. Unit shall be equipped with anti−cycle protection with one short
cycle on unit flame rollout switch or 4 continuous short cycles on
the high temperature limit switch. Fault indication shall be made
using an LED.
7. The IGC board shall contain algorithms that modify evaporator
fan operation to prevent future cycling on high temperature
limit switch.
8. The LED shall be visible without removal of control box access
panel.
G. Refrigerant Components: Refrigerant circuit components shall
include:
1. Fixed orifice metering system.
2. Refrigerant filter drier.
3. Service gage connections on suction, discharge, and liquid
lines.
Specifications subject to change without notice.
49
GUIDE SPECIFICATIONS − PGE072−150 (cont.)
H. Filter Section:
b. Available as a factory−installed option in vertical
supply/return configuration only. (Available as a
1. Standard filter section shall consist of factory installed, low
field−installed accessory for dedicated horizontal and/or
velocity, throwaway 2−in. thick fiberglass filters of
vertical supply return configurations.)
commercially available sizes.
2. Filter face velocity shall not exceed 320 fpm at nominal
c. Includes all hardware and controls to provide cooling with
airflows.
outdoor air.
3. Filter section should use only one size filter.
d. Equipped with low−leakage dampers, not to exceed 2%
4. Filters shall be accessible through an access panel with
leakage at 1 in. wg pressure differential.
no−tool−removal.
e. Capable of introducing up to 100% outdoor air.
I. Controls and Safeties:
1. Unit Controls: Unit shall be complete with self contained low
f. Economizer shall be equipped with a barometric relief
voltage control circuit protected by a fuse on the 24v
damper capable of relieving up to 100% return air.
transformer side (090−150 units have a resettable circuit
g. Designed to close damper(s) during loss−of power situations
breaker).
with spring return built into motor.
2. Safeties:
a. Unit shall incorporate a solid state compressor protector
which provides anti−cycle reset capability at the space
thermostat, should any of the following standard safety
devices trip and shut off compressor.
1) Compressor over temperature, overcurrent.
2) Loss of charge/low pressure switch.
3) Freeze protection thermostat, evaporator coil.
4) High pressure switch.
5) Automatic reset motor thermal overload protector. The
lockout protection shall be easily disconnected at the
control board, if necessary.
b. Heating section shall be provided with the following
minimum protections:
1) High temperature limit switches.
2) Induced draft motor speed sensor.
3) Flame rollout switch.
4) Flame proving controls.
J. Operating Characteristics:
1. Unit shall be capable of starting and running at 125_F ambient
outdoor temperature, meeting maximum load criteria of ARI
Standard 210/240 or 360 at + 10% voltage.
2. Compressor with standard controls shall be capable of operation
down to 25_F ambient outdoor temperature.
K. Electrical Requirements: All unit power wiring shall enter unit
cabinet at a single factory predrilled location.
L. Motors:
1. Compressor motors shall be cooled by refrigerant gas passing
through motor windings and shall have line break thermal and
current overload protection.
2. Evaporator fan motor shall have permanently lubricated
bearings and inherent automatic reset thermal overload
protection. Evaporator motors are specifically designed and
do not have conventional horsepower (HP) ratings listed on
the motor nameplate. Motors are designed and qualified in the
−air over location downstream of the cooling coil and carry a
maximum continuous bhp rating that is the maximum
application bhp rating for the motor; no safety factors above
that rating may be applied.
3. Totally enclosed condenser fan motor shall have permanently
lubricated bearings, and inherent automatic reset thermal
overload protection.
4. Induced draft motor shall have permanently lubricated sealed
bearings and inherent automatic reset thermal overload
protection.
N. Special Features
1. Integrated Economizers
a. Integrated integral modulating type capable of simultaneous
economizer and compressor operation. During economizer
operation, up to two compressors on sizes 090−150 will
operate.
50
h. Dry bulb outdoor−air temperature sensor shall be provided
as standard. Outdoor air sensor set point is adjustable and
shall range from 40° to 100° F. For the economizer, the return
air sensor, indoor enthalpy sensor, and outdoor enthalpy
sensor shall be provided as field installed accessories to
provide enthalpy control, differential enthalpy control, and
differential dry bulb temperature control.
i. Economizer controller shall use a mixed air thermistor
mounted on the evaporator fan housing to control
economizer operation to a supply air temperature of 55° F.
j. The economizer shall have a gear−driven parallel blade
design.
k. Economizer controller shall provide control of internal
building pressure through its accessory power exhaust
function. Factory set at 100%, with a range of 0% to 100%.
l. Economizer Controller Occupied Minimum Damper Position
Setting maintains the minimum airflow into the building
during occupied period providing design ventilation rate for
full occupancy (damper position during heating). A remote
potentiometer may be used to override the set point.
m. Economizer Controller Unoccupied Minimum Damper
Position Setting − The economizer damper shall be
completely closed when the unit is in the occupied mode.
n. Economizer Controller IAQ/DCV Maximum Damper Position
Setting − Setting the maximum position of the damper
prevents the introduction of large amounts of hot or cold air
into the space. This position is intended to satisfy the base
minimum ventilation rate.
o. Economizer controller IAQ/DCV control modulates the
outdoor−air damper to provide ventilation based on the
optional 2 to 10 vdc CO2 sensor input.
p. Compressor lockout sensor (opens at 35° F, closes at 50° F).
q. Actuator shall be direct coupled to economizer gear,
eliminating linkage arms and rods.
r. Control LEDs:
1. When the outdoor−air damper is capable of providing
free cooling, the “Free Cool” LED shall illuminate.
2. The IAQ LED indicates when the module is on the
DCV mode.
3. The EXH LED indicates when the exhaust fan contact
is closed.
s. Remote Minimum Position Control − A field−installed
accessory remote potentiometer shall allow the outdoor−air
damper to be opened or closed beyond the minimum position
in the occupied mode for modified ventilation.
Specifications subject to change without notice.
521 21 1001 04
PHYSICAL DATA − PGE180−300
UNIT PGE
NOMINAL CAPACITY (tons)
OPERATING WEIGHT
Unit
Economizer
COMPRESSOR/MANUFACTURER
Quantity...Model (Ckt 1, Ckt 2)
Rows...Fins/in.
Total Face Area (sq ft)
EVAPORATOR FAN
Quantity...Size (in.)
Type Drive
Nominal Cfm
Motor Hp
Motor Nominal Rpm
Maximum Continuous Bhp
Nominal Fan Shaft Diameter (in.)
Belt, Quantity...Type...Length (in.)
Pulley Center Line Distance (in.)
Speed Change per Full Turn of
Movable Pulley Flange (rpm)
Movable Pulley Maximum Full Turns
From Closed Position
Factory Speed
Factory Speed Setting (rpm)
Fan Shaft Diameter at Pulley (in.)
1800
80
1850
80
240
20
--
1900
80
Scroll, Copeland
1...ZR108KC,
1...ZR125KC,
1...ZR94KC
1...ZR108KC
55, 45
55, 45
2
2
106, 81
106,106
R-22
TXV
300
25
2270
80
1...ZR4140KC,
2...ZR144KC
60, 40
2
136, 106
19-8
13-8
Rows...Fins/in.
Total Face Area (sq ft)
CONDENSER FAN
Nominal Cfm
Quantity...Diameter (in.)
Motor Hp...Rpm
Watts Input (Total)
EVAPORATOR COIL
Motor Bearing Type
Maximum Allowable Rpm
Motor Pulley Pitch Diameter
Min/Max (in.)
Nominal Motor Shaft Diameter (in.)
Fan Pulley Pitch Diameter (in.)
210
18
1...ZR94KC,
1...ZR72KC
60, 40
2
85, 60
Capacity Stages (%)
Number of Refrigerant Circuits
Oil (oz) (Ckt 1, Ckt 2)
REFRIGERANT TYPE
Expansion Device
Operating Charge (lb−oz)
Circuit 1*
Circuit 2
CONDENSER COIL
Motor Frame Size
Nominal Rpm High/Low
Fan Rpm Range
180
15
Low−Medium Static
High Static
Low−Medium Static
High Static
Low−Medium Static
High Static
Low−Medium Static
High Static
Low−Medium Static
High Static
Low−Medium Static
High Static
19-8
19-11
26-13
19-2
13-14
25-10
-Cross-Hatched 3/8-in. Copper Tubes, Aluminum
Lanced,
Aluminum Pre-Coated, or Copper Plate Fins
4...15
4...15
4...15
3...15 (2 coils)
43.4
21.7
21.7
21.7
-Propeller Type
10,500
10,500
14,200
21,000
3...22
3...22
2...30
6...22
1/ ...1050
1/ ...1050
1/ ...1050
1...1075
2
2
2
1100
1100
3400
2200
Cross-Hatched 3/8-in. Copper Tubes, Aluminum Lanced or
Copper Plate Fins, Face Split
4...15
4...15
4...15
4...15
17.5
17.5
17.5
17.5
Centrifugal Type
2...12 x 12
2...12 x 12
2...12 x 12
2...12 x 12
Belt
Belt
Belt
Belt
6000
7200
8000
10,000
5
5
7.5
10
1745
1745
1745
1740
8.7 [208/230v, 575v] 10.2 [208/230v, 575v]
6.13
5.90
9.5 [460 v]
11.8 [460 v]
184T
184T
213T
215T
873-1021
910-1095
1002-1151
1066-1283
1025-1200
1069-1287
1193-1369
1332-1550
Ball
Ball
Ball
Ball
1550
1550
1550
1550
4.9/5.9
4.9/5.9
5.4/6.6
4.9/5.9
4.9/5.9
4.9/5.9
5.4/6.6
4.9/5.9
11/8
11/8
13/8
13/8
9.4
9.4
9.4
8.0
8.0
8.0
7.9
6.4
17/16
17/16
17/16
17/16
1...BX...50
1...BX...50
1...BX...53
2...BX...50
1...BX...48
1...BX...48
1...BX...50
2...BX...47
13.3-14.8
13.3-14.8
14.6-15.4
14.6-15.4
37
37
37
36
44
34
44
45
4
3.5
965
1134
17/16
6
3.5
1002
1178
17/16
6
3.5
1095
1303
17/16
6
3.5
1182
1470
17/16
LEGEND
BHP − Brake Horsepower
TXV − Thermostatic Expansion Valve
*Circuit 1 uses the lower portion of the condenser coil and lower portion of the evaporator coils and Circuit 2 uses the upper portion of both coils.
{ Rollout switch is manual reset.
**The PGE300 unit requires 2−in. industrial grade filters capable of handling face velocities up to 625 ft/min(such as American Air Filter no.
5700 or equivalent).
NOTE: The PGE180−300 units have a low−pressure switch (standard) located on the suction side.
521 21 1001 04
Specifications subject to change without notice.
51
PHYSICAL DATA − PGE180−300 (cont.)
UNIT PGE
FURNACE SECTION
Rollout Switch Cutout Temp (F)†
Burner Orifice Diameter (in. ...drill size)
Natural Gas
Thermostat Heat Anticipator Setting (amps)
208/230v, 575v
Stage 1
Stage 2
460 v
Stage 1
Stage 2
Gas Input
Stage 1
Stage 2
Efficiency (Steady-State) (%)
Temperature Rise Range
Manifold Pressure (in. wg)
Natural Gas
Gas Valve Quantity
Gas Valve Pressure Range
in. wg
psig
Field Gas Connection Size (in.-FPT)
HIGH−PRESSURE SWITCH (psig)
Cutout
Reset (Auto)
LOW-PRESSURE SWITCH (psig)
Cutout
Reset (Auto)
FREEZE PROTECTION THERMOSTAT (F)
Opens
Closes
OUTDOOR-AIR INLET SCREENS
Quantity...Size (in.)
RETURN-AIR FILTERS
Quantity...Size (in.)
POWER EXHAUST*
180
210
240
190
190
190
190
0.1285...30/0.136...29
0.1285...30/0.136...29
-0.1285...30/0.136...29
0.1285...30/0.136...29
0.98
0.44
0.80
0.44
206,000/270,000
275,000/360,000
81
15-45/20-50
0.98
0.44
0.80
0.44
206,000/270,000
275,000/360,000
81
15-45/20-50
0.98
0.44
0.80
-0.44
206,000/270,000
275,000/360,000
81
15-45/20-50 - -
0.98
0.44
0.80
0.44
206,000/270,000
275,000/360,000
81
15-45/20-50
3.3
1
3.3
1
3.3
1
3.3
1
5.5-13.5
0.235-0.487
3/
4
5.5-13.5
0.235-0.487
3/
4
5.5-13.5
0.235-0.487
3/
4
---
--
300
5.5-13.5
0.235-0.487
3/
4
--
426
320
27
44
30 ± 5
45 ± 5
Cleanable
2...20 x 25 x 1
1...20 x 20 x 1
Throwaway**
4...20 x 20 x 2
4...16 x20 x 2
1/ Hp, 208/230-460 v Motor Direct Drive, Propeller-Fan (Factory-Wired for 460 v)
2
* NOTE: DN series Power Exhaust
LEGEND
BHP − Brake Horsepower
TXV − Thermostatic Expansion Valve
*Circuit 1 uses the lower portion of the condenser coil and lower portion of the evaporator coils and Circuit 2 uses the upper portion of both coils.
{ Rollout switch is manual reset.
**The PGE300 unit requires 2−in. industrial grade filters capable of handling face velocities up to 625 ft/min
(such as American Air Filter no. 5700 or equivalent).
NOTE: The PGE180−300 units have a low−pressure switch (standard) located on the suction side.
OPERATING WEIGHTS
UNIT
PGE
180
lb
1800
kg
816
BASE UNIT OPERATING WEIGHTS*
210
240
lb
kg
lb
kg
1850
839
1900
862
300
lb
2270
kg
1030
*Base unit weight does not include copper coils, economizer, power exhaust, barometric relief or crating. See Options and Accessories
table below for more information.
NOTE: For 180 or 210 unit, add 75 lb (34 kg) for domestic crating. For 240 unit, add 135 lb (61 kg). For 300unit, add 175 lb (79 kg) for domestic
crating.
52
Specifications subject to change without notice.
521 21 1001 04
PGE210
PGE180
Base Unit Dimensions − PGE180, 210
521 21 1001 04
Specifications subject to change without notice.
53
PGE240
Base Unit Dimensions − PGE240
54
Specifications subject to change without notice.
521 21 1001 04
8’ 7−1/4”
3.78”
PGE300
BASE UNIT DIMENSIONS − PGE300
521 21 1001 04
Specifications subject to change without notice.
55
ACCESSORY DIMENSIONS
HORIZONTAL SUPPLY/RETURN ADAPTER INSTALLATION − PGE180−240
a48−7458
AXB165CHA
3 1/2”
2” X 1/4
SUPPOR
T TYP.
STITCH
WELDED
FULLY INSULATED
SUPPLY PLENUM
1” INSULATION
1 1/2 # DENSITY,
STICK PINNED & GLUED
14 3/4”
a48−7457
NOTE: AXB165CHA is a horizontal adapter and
includes an insulated transition duct. The pressure drop
through the adapter curb is negligible. Power exhaust
and barometric relief accessory are not available with
horizontal adapter.
For horizontal return applications: The power exhaust
and barometric relief dampers must be installed in the
return air duct.
23”
6”
12” WIDE STANDING
SEAM PANELS
ACCESSORY
PACKAGE NO.
AXB165CHA
CURB
HEIGHT
1′ −11″
(584)
a50−7459
DESCRIPTION
Horizontal
Adapter Roof Curb
POWER EXHAUST
2’−1 5/8”
48−1169
56
2’−2 1/16”
1’−6 5/16”
Specifications subject to change without notice.
521 21 1001 04
PERFORMANCE DATA − PGE180−300
COOLING CAPACITIES
PGE180 (15 TONS)
Air Entering Evaporator − Cfm/BF
Temp (F)
Air Entering
Condenser
(Edb)
75
85
95
105
115
118
120
4,500/0.010
5,250/0.120
6,000/0.140
6,750/0.150
7,500/0.160
Air Entering Evaporator − Ewb (F)
62
67
72
62
67
72
62
67
72
62
67
72
62
67
72
TC
175.7
191.8
210.9
180.5
196.4
214.9
183.3
201.0
218.9
187.1
203.0
222.9
189.2
205.0
224.9
SHC
145.5
123.0
99.9
156.2
131.5
104.9
167.8
139.1
110.6
175.3
146.3
115.0
183.7
155.8
119.4
kW
14.0
14.4
15.0
14.2
14.6
15.1
14.3
14.7
15.2
14.4
14.9
15.4
14.5
14.9
15.4
TC
168.8
185.1
203.0
173.3
189.2
207.0
177.1
192.8
210.9
179.7
196.0
214.9
182.3
198.0
216.9
SHC
141.7
119.8
97.1
151.6
128.6
101.9
162.4
135.9
106.7
171.1
143.1
111.0
179.1
150.2
116.4
kW
15.2
15.6
16.1
15.3
15.8
16.3
15.5
15.9
16.5
15.6
16.1
16.6
15.7
16.1
16.7
TC
161.8
177.5
194.4
166.4
181.5
199.0
169.0
184.7
203.0
171.7
187.7
205.0
174.5
189.4
207.0
SHC
138.7
116.8
93.9
147.5
125.2
99.1
157.6
132.7
103.3
167.2
139.9
108.3
173.9
146.5
112.2
kW
16.4
16.9
17.4
16.6
17.0
17.6
16.7
17.2
17.7
16.8
17.3
17.8
16.9
17.4
17.9
TC
154.6
169.3
185.3
158.6
173.1
189.2
161.2
175.9
192.0
164.0
178.1
194.6
167.4
179.7
196.2
SHC
133.9
113.6
90.7
143.7
121.4
95.7
154.2
129.0
100.3
161.8
136.1
104.7
167.2
142.7
108.7
kW
17.6
18.2
18.7
17.8
18.3
18.8
17.9
18.5
18.9
18.1
18.5
19.1
18.2
18.6
19.1
TC
147.1
160.8
175.5
150.4
164.2
179.1
152.4
166.4
181.9
155.8
168.6
184.3
159.6
169.7
185.7
SHC
130.1
110.2
87.4
139.7
117.8
92.1
149.3
125.4
96.7
155.6
131.9
101.1
159.2
139.1
105.3
kW
19.0
19.5
20.0
19.1
19.7
20.2
19.2
19.8
20.2
19.4
19.9
20.4
19.5
19.9
20.4
TC
144.7
158.0
172.5
147.7
161.2
175.9
150.0
163.4
178.3
153.4
165.4
180.7
157.0
166.8
182.1
SHC
129.0
109.1
86.4
138.5
116.6
91.1
147.7
124.2
95.5
153.4
130.7
99.9
156.8
137.7
104.1
kW
19.4
19.9
20.4
19.5
20.0
20.6
19.6
20.2
20.6
19.8
20.2
20.8
19.9
20.4
20.8
TC
142.9
156.2
170.5
145.9
159.2
−
148.3
161.2
−
151.8
163.2
−
155.4
164.8
−
SHC
128
108
86
138
116
−
146
123
−
152
130
−
155
137
−
kW
19.6
20.2
20.6
19.8
20.2
−
19.9
20.4
−
20.0
20.4
−
20.2
20.6
−
PGE210 (18 TONS)
Air Entering Evaporator − Cfm/BF
Temp (F)
Air Entering
Condenser
(Edb)
62
67
72
62
67
72
62
67
72
62
67
72
62
67
72
TC
227
247
269
232
251
274
237
255
277
241
258
280
248
261
283
75
85
95
105
115
120
5,400/0.095
6,000/0.105
7,000/0.120
8,000/0.140
9,000/0.150
Air Entering Evaporator − Ewb (F)
SHC
200
167
134
215
178
141
231
194
152
241
205
160
248
219
167
kW
15.9
16.5
17.2
16.1
16.7
17.3
16.3
16.8
17.5
16.5
16.9
17.6
16.7
17.0
17.7
273
TC
219
238
259
224
242
265
229
247
269
235
250
272
241
252
SHC
197
164
131
210
175
137
225
188
145
234
200
153
240
214
163
kW
17.2
17.8
18.5
17.4
17.9
18.6
17.6
18.1
18.8
17.8
18.3
19.0
18.0
18.3
19.0
263
TC
210
229
248
214
233
253
219
237
258
225
239
261
231
242
SHC
192
160
126
205
171
133
218
183
141
225
194
148
231
206
156
kW
18.5
19.2
19.9
18.7
19.3
20.0
19.0
19.5
20.2
19.2
19.6
20.3
19.4
19.7
20.4
250
TC
200
218
237
205
222
241
210
225
245
216
228
249
221
230
SHC
186
155
123
199
166
129
210
178
136
216
190
143
221
201
150
kW
19.9
20.5
21.2
20.1
20.7
21.3
20.4
20.8
21.5
20.6
21.0
21.7
20.8
21.0
21.8
236
TC
190
207
225
195
210
228
201
213
232
206
216
235
211
217
SHC
181
151
118
193
161
124
201
173
132
206
185
139
211
196
146
kW
21.3
21.9
22.6
21.5
22.1
22.8
21.8
22.2
22.9
22.0
22.4
23.1
22.2
22.4
23.1
TC
185
200
218
189
205
221
196
207
225
201
209
227
205
210
229
SHC
179
149
117
189
159
122
196
171
130
201
182
137
205
193
144
kW
22.1
22.6
−
22.3
22.8
−
22.5
22.9
−
22.7
−
−
22.9
−
−
LEGEND
BF −
Bypass Factor
Edb − Entering Dry−Bulb
Ewb − Entering Wet−Bulb
kW −
Compressor Motor Power Input
SHC − Sensible Heat Capacity (1000 Btuh) Gross
TC −
Total Capacity (1000 Btuh) Gross
521 21 1001 04
Specifications subject to change without notice.
57
PERFORMANCE DATA − PGE180−300 (cont.)
COOLING CAPACITIES
PGE240 (20 TONS)
Air Entering Evaporator − Cfm/BF
Temp (F)
Air Entering
Condenser
(Edb)
62
67
72
62
67
72
62
67
72
62
67
72
62
67
72
TC
237
258
282
242
264
288
247
268
291
252
271
295
258
274
298
75
85
95
105
115
120
6,000/0.04
7,000/0.05
8,000/0.06
9,000/0.07
10,000/0.08
Air Entering Evaporator − Ewb (F)
SHC
204
171
138
221
184
146
237
199
156
247
210
164
257
221
172
kW
16.7
17.4
18.1
16.9
17.6
18.3
17.1
17.8
18.5
17.3
17.9
18.6
17.5
18.0
18.7
287
TC
229
249
272
234
254
278
239
260
283
245
262
286
250
265
SHC
201
167
135
216
180
142
231
193
150
240
203
157
250
217
167
kW
18.1
18.7
19.5
18.3
18.9
19.7
18.5
19.1
19.9
18.7
19.3
20.1
18.8
19.4
20.1
277
TC
220
239
261
225
245
267
230
249
271
235
251
275
241
255
SHC
195
163
130
211
176
138
224
188
145
233
199
152
241
210
160
kW
19.4
20.2
20.9
19.7
20.4
21.2
19.9
20.6
21.3
20.1
20.6
21.4
20.3
20.8
21.6
263
TC
209
228
249
216
234
254
220
237
259
225
240
262
230
242
SHC
189
159
126
206
171
134
217
183
140
225
195
148
230
205
154
kW
20.9
21.5
22.3
21.2
21.8
22.5
21.4
22.0
22.7
21.6
22.1
22.9
21.8
22.2
23.0
249
TC
200
217
237
205
222
241
211
225
244
216
227
248
221
229
SHC
185
154
122
199
166
129
209
178
136
216
189
143
221
200
150
kW
22.5
23.1
23.8
22.7
23.3
24.0
22.9
23.4
24.2
23.2
23.6
24.4
23.4
23.7
24.4
TC
194
211
230
199
216
234
205
218
237
210
220
240
214
222
241
SHC
183
152
121
195
164
126
204
175
134
210
186
141
214
196
148
kW
23.2
23.8
24.6
23.5
24.0
−
23.7
24.2
−
23.9
24.4
−
24.1
24.4
−
PGE300 (25 TONS) (Continued on Next Page)
Air Entering Evaporator − Cfm/BF
Temp (F)
Air Entering
Condenser
(Edb)
57
62
67
72
57
62
67
72
57
62
67
72
TC
256
271
299
327
267
278
305
336
276
283
309
341
75
85
95
105
115
125
58
7,000/0.05
8,000/0.06
9,000/0.07
Air Entering Evaporator − Ewb (F)
SHC
256
232
196
159
267
249
208
166
276
265
220
173
kW
18.0
18.3
18.9
19.6
18.3
18.5
19.1
19.8
18.5
18.7
19.2
19.9
328
TC
248
262
288
316
259
267
293
322
267
273
298
SHC
248
228
192
154
259
244
204
161
267
259
216
169
kW
20.0
20.4
20.9
21.5
20.3
20.4
21
21.7
20.6
20.6
21.2
21.9
TC
241
252
277
303
251
257
281
309
259
262
286
314
SHC
241
223
187
149
251
239
198
157
259
254
210
164
kW
22.4
22.6
23.1
23.7
22.6
22.7
23.3
23.9
22.8
22.9
23.4
24
TC
233
243
266
289
242
247
270
295
250
252
273
299
SHC
233
218
182
145
242
233
194
152
250
248
206
159
kW
24.9
25.1
25.6
26.2
25.2
25.3
25.8
26.3
25.4
25.4
25.9
26.5
285
TC
225
232
254
277
234
236
258
281
241
242
261
SHC
225
214
178
140
234
228
189
148
241
241
201
155
kW
27.9
27.9
28.5
29
28
28.1
28.6
29.2
28.2
28.2
28.7
29.2
269
TC
216
221
241
263
224
225
245
267
231
231
248
SHC
216
208
173
136
223
221
184
142
230
231
196
149
kW
30.9
31.1
31.6
32
31.2
31.2
31.7
32.2
31.4
31.4
31.7
32.3
Specifications subject to change without notice.
521 21 1001 04
PERFORMANCE DATA − PGE300 (cont.)
COOLING CAPACITIES
PGE300 (25 TONS) (Continued)
Air Entering Evaporator − Cfm/BF
Temp (F)
Air Entering
Condenser
(Edb)
57
62
67
72
57
62
67
72
TC
285
286
313
344
294
294
316
347
75
85
95
105
115
125
LEGEND
BF −
Edb −
Ewb −
kW −
SHC −
TC −
10,000/0.08
11,250/0.09
Air Entering Evaporator − Ewb (F)
SHC
285
281
232
182
294
294
252
198
kW
18.7
18.8
19.4
20.1
19.0
19.0
19.5
20.2
336
TC
276
276
302
331
284
285
305
SHC
276
274
228
175
284
284
244
187
kW
20.8
20.8
21.3
22
21
21
21.5
22.1
321
TC
266
267
290
317
274
275
293
SHC
266
265
222
171
274
275
238
180
kW
23
23
23.5
24.2
23.2
23.2
23.6
24.2
306
TC
256
258
277
303
264
265
280
SHC
256
257
217
166
264
265
232
176
kW
25.6
25.6
26
26.6
25.8
25.8
26.1
26.7
291
TC
247
247
264
288
254
255
267
SHC
247
247
211
162
253
255
227
171
kW
28.4
28.4
28.8
29.3
28.7
28.7
28.9
29.5
276
TC
237
236
251
273
243
242
253
SHC
236
236
206
157
243
242
221
166
kW
31.6
31.6
31.9
32.3
31.7
31.7
31.9
32.5
Bypass Factor
Entering Dry−Bulb
Entering Wet−Bulb
Compressor Motor Power Input
Sensible Heat Capacity (1000 Btuh) Gross
Total Capacity (1000 Btuh) Gross
521 21 1001 04
Specifications subject to change without notice.
59
PERFORMANCE DATA − PGE180−300 (cont.)
FAN PERFORMANCE
PGE180 (15 Ton) Low Heat*
Available External Static Pressure (in. wg)
Airflow
(Cfm)
Rpm
Watts
Bhp
Rpm
Watts
Bhp
Rpm
Watts
Bhp
Rpm
Watts
Bhp
Rpm
Watts
Bhp
4500
753
1307
1.53
761
1330
1.56
840
1572
1.84
912
1822
2.14
980
2080
2.44
4800
747
1384
1.62
790
1515
1.78
866
1765
2.07
936
2023
2.37
1002
2289
2.68
5100
741
1465
1.72
820
1718
2.01
893
1977
2.32
961
2243
2.63
1280
2516
2.95
5700
810
1911
2.24
882
2182
2.56
950
2459
2.88
1014
2741
3.21
1075
3029
3.55
6000
844
2164
2.54
914
2444
2.87
980
2730
3.20
1042
3021
3.54
1100
3317
3.89
6300
879
2439
2.86
947
2729
3.20
1010
3023
3.55
1070
3322
3.90
1127
3626
4.25
6600
915
2737
3.21
980
3035
3.56
1041
3338
3.91
1099
3645
4.28
1155
3957
4.64
6900
950
3057
3.59
1013
3364
3.95
1072
3675
4.31
1129
3991
4.68
1183
4311
5.06
7200
986
3401
3.99
1047
3717
4.36
1104
4037
4.74
1159
4361
5.11
1211
4689
5.50
7500
1022
3770
4.42
1081
4095
4.80
1136
4423
5.19
1189
4755
5.58
1241
5091
5.97
0.2
0.4
0.6
0.8
1.0
PGE180 (15 Ton) Low Heat*
Available External Static Pressure (in. wg)
Airflow
(Cfm)
Rpm
Watts
Bhp
Rpm
Watts
Bhp
Rpm
Watts
Bhp
Rpm
Watts
Bhp
Rpm
Watts
Bhp
4500
1044
2345
2.75
1105
2619
3.07
1163
2899
3.40
1218
3187
3.74
1271
3481
4.08
4800
1065
2561
3.00
1124
2841
3.33
1180
3127
3.67
1235
3420
4.01
1287
3720
4.36
5100
1086
2795
3.28
1144
3082
3.61
1199
3375
3.96
1252
3674
4.31
1304
3979
4.67
5700
1132
3324
3.90
1187
3624
4.25
1240
3929
4.61
1291
4241
4.97
1341
4558
5.35
6000
1157
3619
4.24
1210
3925
4.60
1262
4239
4.97
1312
4557
5.34
1361
4880
5.72
6300
1182
3935
4.62
1234
4249
4.98
1285
4569
5.36
1334
4894
5.74
−
−
−
6600
1208
4274
5.01
1259
4595
5.39
1309
4922
5.77
−
−
−
−
−
−
6900
1235
4636
5.44
1285
4964
5.82
−
−
−
−
−
−
−
−
−
7200
1262
5021
5.89
−
−
−
−
−
−
−
−
−
−
−
−
7500
−
−
−
−
−
−
−
−
−
−
−
−
−
−
−
1.2
1.4
1.6
1.8
2.0
PGE180 (15 Ton) Low Heat*
Available External Static Pressure (in. wg)
Airflow
(Cfm)
Rpm
Watts
Bhp
Rpm
Watts
Bhp
Rpm
Watt
Bhp
Rpm
Watts
Bhp
Rpm
Watts
Bhp
4500
1322
3781
4.43
1372
4088
4.79
1419
4400
5.16
1466
4719
5.53
1511
5042
5.91
4800
1337
4280
4.72
1386
4337
5.09
1433
4655
5.46
1479
4978
5.84
−
−
−
5100
1353
4290
5.03
1401
4607
5.40
1448
4930
5.78
−
−
−
−
−
−
5700
1388
4881
5.72
−
−
−
−
−
−
−
−
−
−
−
−
6000
−
−
−
−
−
−
−
−
−
−
−
−
−
−
−
2.2
2.4
2.6
2.8
3.0
LEGEND
Bhp - Brake Horsepower
Watts - Input Watts to Motor
*Standard low-medium drive range is 873 to 1021 rpm. Alternate high-static drive range is 1025 to 1200. Other rpms may require a field-supplied drive.
NOTES:
1. Maximum continuous Bhp for the standard motor is 6.13 and maximum continuous watts are 5180. Do not adjust motor rpm such that motor maximum
bhp and/or watts is exceeded at the maximum operating cfm.
2. See General Notes for Fan Performance following this section.
60
Specifications subject to change without notice.
521 21 1001 04
PERFORMANCE DATA − PGE180−300 (cont.)
FAN PERFORMANCE
PGE180 (15 Ton) High Heat*
Available External Static Pressure (in. wg)
Airflow
(Cfm)
Rpm
Watts
Bhp
Rpm
Watts
Bhp
Rpm
Watt
Bhp
Rpm
Watts
Bhp
Rpm
Watts
Bhp
4500
753
1307
1.53
786
1404
1.65
861
1644
1.93
932
1893
2.22
997
2150
2.52
4800
747
1384
1.62
818
1603
1.88
890
1852
2.17
958
2108
2.47
1022
2373
2.78
5100
775
1571
1.84
850
1822
2.14
920
2079
2.44
986
2344
2.75
1048
2616
3.07
5700
849
2054
2.41
918
2323
2.73
982
2598
3.05
1044
2879
3.38
1102
3166
3.71
6000
886
2329
2.73
952
2607
3.06
1015
2891
3.39
1074
3180
3.73
1130
3474
4.08
6300
924
2628
3.08
987
2915
3.42
1047
3207
3.76
1105
3504
4.11
1160
3807
4.46
6600
962
2951
3.46
1023
3246
3.81
1081
3547
4.16
1136
3853
4.52
1190
4163
4.88
6900
1000
3298
3.87
1059
3603
4.23
1115
3912
4.59
1168
4225
4.96
1220
4543
5.33
7200
1038
3672
4.31
1095
3986
4.67
1149
4303
5.05
1201
4625
5.42
1251
4950
5.81
7500
1077
4072
4.78
1131
4394
5.15
1184
4720
5.54
1234
5050
5.92
−
−
−
0.2
0.4
0.6
0.8
1.0
PGE180 (15 Ton) High Heat* (cont)
Available External Static Pressure (in. wg)
Airflow
(Cfm)
Rpm
Watts
Bhp
Rpm
Watts
Bhp
Rpm
Watts
Bhp
Rpm
Watts
Bhp
Rpm
Watts
Bhp
4500
1060
2414
2.83
1119
2685
3.15
1175
2964
3.48
1230
3250
3.81
1282
3542
4.15
4800
1082
2644
3.10
1140
2922
3.43
1195
3207
3.76
1248
3498
4.10
1299
3795
4.45
5100
1106
2894
3.39
1163
3178
3.73
1216
3470
4.07
1268
3767
4.42
1319
4071
4.77
5700
1157
3459
4.06
1211
3757
4.41
1262
4061
4.76
1312
4371
5.13
1360
4686
5.50
6000
1184
3774
4.43
1236
4080
4.79
1287
4391
5.15
1335
4707
5.52
1382
5029
5.90
6300
1212
4114
4.83
1263
4427
5.19
1312
4745
5.57
1359
5067
5.94
−
−
−
6600
1241
4478
5.25
1290
4798
5.63
1338
5122
6.01
−
−
−
−
−
−
6900
1270
4866
5.71
−
−
−
−
−
−
−
−
−
−
−
−
7200
−
−
−
−
−
−
−
−
−
−
−
−
−
−
−
7500
−
−
−
−
−
−
−
−
−
−
−
−
−
−
−
1.2
1.4
1.6
1.8
2.0
PGE180 (15 Ton) High Heat* (cont)
Available External Static Pressure (in. wg)
Airflow
(Cfm)
Rpm
Watts
Bhp
4500
1332
3841
4800
1349
4100
5100
1367
5700
6000
2.2
2.4
2.6
Rpm
Watts
Bhp
Rpm
Watts
2.8
3.0
Bhp
Rpm
Watts
Bhp
Rpm
Watts
Bhp
4.50
1381
4145
4.86
1428
4456
5.23
1473
4772
5.60
1518
5095
5.98
4.81
1397
4409
5.17
1443
4725
5.54
1488
5046
5.92
−
−
−
4380
5.14
1414
4695
5.51
1460
5180
5.88
−
−
−
−
−
−
1407
5007
5.87
−
−
−
−
−
−
−
−
−
−
−
−
−
−
−
−
−
−
−
−
−
−
−
−
−
−
−
LEGEND
Bhp - Brake Horsepower
Watts - Input Watts to Motor
*Standard low-medium drive range is 873 to 1021 rpm. Alternate high-static drive range is 1025 to 1200. Other rpms may require a field-supplied drive.
NOTES:
1. Maximum continuous Bhp for the standard motor is 6.13 and maximum continuous watts are 5180. Do not adjust motor rpm such that motor maximum
bhp and/or watts is exceeded at the maximum operating cfm.
2. See General Notes for Fan Performance following this section.
521 21 1001 04
Specifications subject to change without notice.
61
PERFORMANCE DATA − PGE180−300 (cont.)
FAN PERFORMANCE
PGE210 (18 Ton) Low Heat*
Airflow
(Cfm)
5,500
6,000
6,500
7,000
7,500
8,000
8,500
9,000
9,500
10,000
Rpm
755
810
866
923
980
1038
1096
1154
1213
1272
0.2
Bhp
2.27
2.72
3.22
3.78
4.39
5.06
5.78
6.56
7.40
8.30
Watt
1908
2287
2710
3177
3690
4251
4859
5517
6224
6983
Rpm
831
881
932
985
1038
1093
1148
1204
1260
1317
0.4
Bhp
2.58
3.04
3.55
4.11
4.73
5.40
6.13
6.92
7.77
8.67
Watt
2171
2556
2985
3458
3976
4542
5156
5818
6531
7294
Available External Static Pressure (in. wg)
0.6
0.8
Rpm
Bhp
Rpm
Bhp
Watt
Watt
901
2.91
2443
968
3.24
2723
947
3.37
2833
1010
3.71
3116
994
3.88
3266
1054
4.23
3554
1044
4.45
3744
1100
4.80
4036
1094
5.07
4267
1148
5.43
4564
1146
5.75
4838
1197
6.11
5138
1198
6.49
5456
1247
6.85
5761
1251
7.28
6123
1298
7.65
6432
1306
8.13
6840
1350
8.51
7154
1360
9.05
7608
1403
9.43
7926
1.0
Bhp
3.58
4.05
4.57
5.15
5.78
6.47
7.22
8.02
8.88
9.81
Rpm
1031
1070
1111
1155
1200
1246
1294
1343
1394
1445
Rpm
1091
1127
1166
1207
1250
1294
1340
1388
1436
1486
Watt
3009
3406
3847
4333
4864
5443
6070
6745
7471
8247
1.2
Bhp
3.93
4.40
4.93
5.51
6.15
6.84
7.59
8.40
9.26
10.19
Watt
3302
3702
4146
4635
5170
5752
6382
7062
7791
8570
PGE210 (18 Ton) Low Heat* (cont)
Airflow
(Cfm)
5,500
6,000
6,500
7,000
7,500
8,000
8,500
9,000
9,500
10,000
Rpm
1149
1183
1219
1258
1299
1341
1385
1431
1478
−
1.4
Bhp
4.28
4.76
5.29
5.88
6.52
7.21
7.97
8.78
9.65
−
Watts
3602
4003
4450
4942
5480
6065
6699
7382
8114
−
Rpm
1204
1236
1270
1307
1346
1387
1429
1473
1519
−
1.6
Bhp
4.65
5.13
5.66
6.25
6.89
7.59
8.35
9.15
10.04
−
Available External Static Pressure (in. wg)
1.8
Rpm
Bhp
Rpm
Watt
Watt
3907
1258
5.02
4217
1284
4310
1288
5.50
4622
1313
4759
1320
6.03
5073
1344
5253
1355
6.62
5569
1378
5794
1392
7.27
6113
1415
6383
1392
7.97
6704
1453
7019
1472
8.73
7343
1493
7705
1515
9.55
8032
1535
8441
−
−
−
−
−
−
−
−
−
1.9
Bhp
5.20
5.68
6.22
6.81
7.46
8.16
8.93
9.75
−
−
Watt
4375
4780
5232
5729
6273
6866
7506
8196
−
−
Rpm
1309
1337
1368
1402
1437
1475
1514
−
−
−
2.0
Bhp
5.39
5.87
6.41
7.00
7.65
8.36
9.12
−
−
−
Watts
4533
4939
5391
5890
6435
7300
7670
−
−
PGE210 (18 Ton) High Heat*
Airflow
(Cfm)
5,500
6,000
6,500
7,000
7,500
8,000
8,500
9,000
9,500
10,000
Rpm
795
854
914
975
1037
1099
1161
1223
1286
1349
0.2
Bhp
2.43
2.92
3.46
4.06
4.72
5.44
6.22
7.07
7.98
8.95
Watt
2043
2452
2909
3414
3969
4575
5232
5943
6708
7528
Rpm
866
921
977
1034
1092
1150
1210
1270
1331
1392
0.4
Bhp
2.74
3.24
3.79
4.39
5.06
5.79
6.57
7.43
8.34
9.32
Watt
2306
2722
3184
3695
4255
4866
5529
6245
7014
7839
Available External Static Pressure (in. wg)
0.6
0.8
Rpm
Bhp
Rpm
Bhp
Watt
Watt
934
3.07
2578
998
3.40
2856
984
3.57
3998
1044
3.90
3281
1036
4.12
3465
1093
4.46
3752
1090
4.73
3981
1144
5.08
4272
1145
5.41
4546
1196
5.76
4842
1201
6.14
5162
1249
6.50
5462
1258
6.93
5829
1304
7.29
6134
1315
7.79
6550
1360
8.16
6869
1374
8.71
7324
1416
9.08
7638
1433
9.70
8154
1473
10.07
8471
Rpm
1059
1102
1148
1196
1256
1297
1349
1403
1457
−
1.0
Bhp
3.74
4.25
4.81
5.43
6.12
6.86
7.66
8.53
9.46
−
Watt
3142
3570
4045
4569
5142
5766
6443
7171
7954
−
Rpm
1117
1158
1201
1246
1294
1343
1393
1445
1498
−
1.2
Bhp
4.08
4.60
5.16
5.79
6.48
7.22
8.03
8.90
9.84
−
Watt
3434
3865
4343
4870
5447
6075
6755
7487
8274
−
PGE210 (18 Ton) High Heat* (cont)
Airflow
(Cfm)
5,500
6,000
6,500
7,000
7,500
8,000
8,500
9,000
9,500
10,000
Rpm
1173
1211
1252
1295
1340
1388
1436
1486
1538
−
1.4
Bhp
4.44
4.95
5.53
6.16
6.85
7.60
8.41
9.28
10.22
−
Watts
3732
4165
4646
5176
5756
6388
7071
7807
8597
−
Rpm
1227
1263
1302
1343
1386
1431
1478
1527
−
−
1.6
Bhp
4.80
5.32
5.89
6.52
7.22
7.97
8.79
9.67
−
−
Available External Static Pressure (in. wg)
1.8
Watt
Rpm
Bhp
Rpm
Watt
4036
1279
5.17
4345
1304
4471
1313
5.69
4782
1337
4954
1350
6.26
5267
1373
5487
1389
6.90
5802
1412
6070
1431
7.60
6387
1452
6704
1474
8.35
7260
1495
7390
1520
9.17
7713
1540
8130
−
−
−
−
−
−
−
−
−
−
−
−
−
−
1.9
Bhp
5.35
5.87
6.56
7.09
7.79
8.54
9.37
−
−
−
Watts
4502
4939
5425
5961
6547
7186
7876
−
−
−
Rpm
1329
1361
1396
1434
1474
1516
−
−
−
−
2.0
Bhp
5.54
6.06
6.64
7.28
7.98
8.74
−
−
−
−
Watts
4629
5097
5584
6121
6709
7348
−
−
−
−
LEGEND
Bhp - Brake Horsepower
Watts - Input Watts to Motor
*Standard low-medium drive range is 910 to 1095 rpm. Alternate high-static drive range is 1069 to 1287. Other rpms may require a field-supplied drive.
NOTES:
1. Maximum continuous Bhp for the standard motor is 5.90 and maximum continuous watts are 5180. Do not adjust motor rpm such that motor maximum
bhp and/or watts is exceeded at the maximum operating cfm.
2. See General Notes for Fan Performance following this section.
62
Specifications subject to change without notice.
521 21 1001 04
PERFORMANCE DATA − PGE180−300 (cont.)
FAN PERFORMANCE
PGE240 (20 TONS) Low Heat*
0.2
Cfm
6,000
6,500
7,000
7,500
8,000
8,500
9,000
9,500
10,000
Rpm
824
881
939
998
1056
1116
1175
1235
1295
Watts
2607
3030
3488
3982
4512
5077
5678
6315
6988
Bhp
3.09
3.59
4.14
4.72
5.35
6.02
6.74
7.49
8.29
Rpm
894
947
1001
1055
1111
1167
1224
1282
1340
Available External Static Pressure (in. wg)
0.6
Watts
Bhp
Rpm
Bhp
Rpm
3.37
961
3085
3.66
1023
3.88
1009
3507
4.16
1069
1116
4.42
1060
3965
4.70
1165
5.00
1111
4458
5.29
1215
5.63
1164
4988
5.92
1218
1266
6.30
5553
6.59
1272
1319
7.02
6154
7.30
1327
1372
7.77
6791
8.06
1383
1426
8.57
7465
8.86
0.4
Watt
2844
3266
3725
4218
4748
5314
5915
6552
7225
0.8
Watt
3330
3751
4208
4701
5230
5795
6395
7033
7706
Bhp
3.95
4.45
4.99
5.58
6.20
6.87
7.59
8.34
9.14
Rpm
1083
1126
1170
1217
1264
1314
1364
1415
1468
1.0
Watt
3578
3998
4454
4946
5474
6039
6639
7276
7949
Bhp
4.24
4.74
5.28
5.87
6.49
7.16
7.88
8.63
9.43
PGE240 (20 TONS) Low Heat* (cont)
1.2
Cfm
6,000
6,500
7,000
7,500
8,000
8,500
9,000
9,500
10,000
Rpm
1141
1181
1223
1267
1313
1360
1408
1458
1508
Watts
3829
4247
4702
5194
5721
6285
6885
7521
8193
Bhp
4.54
5.04
5.58
6.16
6.79
7.46
8.17
8.92
9.72
Rpm
1196
1234
1274
1316
1359
1405
1451
1499
1549
Available External Static Pressure (in. wg)
1.6
Bhp
Rpm
Watts
Bhp
Rpm
4.84
1249
4337
5.15
1301
5.34
1285
4753
5.64
1334
5.88
1323
5205
6.18
1371
6.46
1363
5694
6.76
1409
7.08
1405
6220
7.38
1449
7.75
1449
6783
8.05
1491
8.46
1494
7381
8.76
1535
9.22
1540
8180
9.51
−
10.01
−
−
−
−
1.4
Watt
4082
4499
4953
5443
5970
6533
7132
7768
8440
1.8
Watt
4596
5009
5460
5947
6472
7034
7631
−
−
Bhp
5.45
5.94
6.48
7.06
7.68
8.34
9.05
−
−
Rpm
1351
1383
1417
1454
1493
1533
−
−
−
2.0
Watt
4856
5267
5716
6202
6726
7286
−
−
−
Bhp
5.76
6.25
6.78
7.36
7.98
8.64
−
−
−
PGE240 (20 TONS) Low Heat* (cont)
2.2
Cfm
6,000
6,500
7,000
7,500
8,000
Rpm
1399
1429
1462
1498
1535
Watts
5118
5527
5974
6459
6981
Bhp
6.07
6.56
7.09
7.66
8.28
Rpm
1446
1475
1507
1540
−
Available External Static Pressure (in. wg)
2.4
2.6
Watts
Bhp
Rpm
Watts
5381
6.38
1492
5647
5789
6.87
1520
6052
6234
7.40
1550
6495
6717
7.97
−
−
−
−
−
−
Bhp
6.70
7.18
7.71
−
−
Rpm
1537
−
−
−
−
2.8
Watts
5914
−
−
−
−
Bhp
7.02
−
−
−
−
LEGEND
Bhp - Brake Horsepower
Watts - Input Watts to Motor
*Standard low-medium drive range is 1002 to 1151 rpm. Alternate high-static drive range is 1193 to 1369. Other rpms may require a field-supplied
drive.
NOTES:
1. Maximum continuous Bhp for the standard motor is 8.70 (208/230v and 575v units) and 9.50 (460v units). Maximum continuous watts are 7915
(208/230v and 575v units) and 8640 (460v units). Do not adjust motor rpm such that motor maximum bhp and/or watts is exceeded at the maximum
operating cfm.
2. See General Notes for Fan Performance following this section.
521 21 1001 04
Specifications subject to change without notice.
63
PERFORMANCE DATA − PGE180−300 (cont.)
FAN PERFORMANCE
PGE240 (20 TONS) High Heat*
Cfm
6,000
6,500
7,000
7,500
8,000
8,500
9,000
9,500
10,000
Rpm
868
929
991
1054
1117
1180
1244
1308
1372
0.2
Watts
2752
3201
3687
4211
4773
5373
6011
6687
7401
Bhp
3.26
3.80
4.37
5.00
5.66
6.37
7.13
7.93
8.78
Rpm
934
991
1049
1109
1168
1229
1290
1352
1414
0.4
Watts
2987
3436
3923
4447
5009
5609
6247
6924
7638
Available External Static Pressure (in. wg)
0.6
Bhp
Rpm
Watt
Bhp
Rpm
3.54
997
3227
3.83
1058
4.08
1051
3675
4.36
1108
4.65
1105
4161
4.94
1159
5.28
1161
4686
5.56
1213
5.94
1218
5247
6.22
1267
6.65
1277
5847
6.94
1323
7.41
1335
6485
7.69
1380
8.21
1395
7162
8.50
1437
9.06
1455
7876
9.34
1496
0.8
Watts
3470
3917
4403
4926
5488
6088
6726
7402
8117
Bhp
4.12
4.65
5.22
5.84
6.51
7.22
7.98
8.78
9.63
Rpm
1115
1162
1211
1262
1314
1368
1423
1479
1535
1.0
Watts
3716
4163
4647
5170
5731
6331
6968
7644
8358
Bhp
4.41
4.94
5.51
6.13
6.80
7.51
8.27
9.07
9.92
PGE240 (20 TONS) High Heat* (cont)
Cfm
6,000
6,500
7,000
7,500
8,000
8,500
9,000
9,500
10,000
Rpm
1171
1215
1262
1310
1360
1412
1465
1519
−
1.2
Watt
3965
4410
4894
5415
5976
6575
7212
7888
−
Bhp
4.70
5.23
5.81
6.42
7.09
7.80
8.56
9.36
−
Rpm
1224
1266
1311
1357
1405
1455
1506
−
−
1.4
Watts
4216
4659
5142
5663
6222
6821
7457
−
−
Available External Static Pressure (in. wg)
1.6
Bhp
Rpm
Watt
Bhp
Rpm
5.00
1276
4469
5.30
1326
5.53
1316
4911
5.83
1364
6.10
1358
5392
6.40
1404
6.72
1403
5912
7.01
1447
7.38
1449
6471
7.68
1492
8.09
1497
7068
8.39
1538
8.85
1547
7705
9.14
−
−
−
−
−
−
−
−
−
−
−
PGE240 (20 TONS) High Heat* (cont)
Available External Static Pressure (in. wg)
2.2
2.4
Cfm
Rpm
Bhp
Rpm
Watts
Bhp
Rpm
Watt
6,000
1422
5243
6.22
1468
5505
6.53
1513
6,500
1456
5679
6.74
1501
5938
7.04
1544
7,000
1493
6155
7.30
1536
6412
7.61
−
7,500
1533
6670
7.91
−
−
−
−
8,000
−
−
−
−
−
−
−
2.6
Watt
5768
6199
−
−
−
1.8
Watts
4726
5165
5645
6164
6721
7318
−
−
−
Bhp
5.61
6.13
6.70
7.31
7.97
8.68
−
−
−
Rpm
1374
1411
1449
1490
1533
−
−
−
−
2.0
Watts
4983
5421
5899
6416
6973
−
−
−
−
Bhp
5.91
6.43
7.00
7.61
8.27
−
−
−
−
Bhp
6.84
7.35
−
−
−
LEGEND
Bhp - Brake Horsepower
Watts - Input Watts to Motor
*Standard low-medium drive range is 1002 to 1151 rpm. Alternate high-static drive range is 1193 to 1369. Other rpms may require a field-supplied
drive.
NOTES:
1. Maximum continuous Bhp for the standard motor is 8.70 (208/230v and 575v units) and 9.50 (460v units). Maximum continuous watts are 7915
(208/230v and 575v units) and 8640 (460v units). Do not adjust motor rpm such that motor maximum bhp and/or watts is exceeded at the maximum
operating cfm.
2. See General Notes for Fan Performance following this section.
64
Specifications subject to change without notice.
521 21 1001 04
PERFORMANCE DATA − PGE180−300 (cont.)
FAN PERFORMANCE
PGE300 (25 TONS) Low Heat*
Airflow
(Cfm)
7,000
7,500
8,000
8,500
9,000
9,500
10,000
10,500
11,000
11,250
Rpm
941
999
1058
1117
1177
1237
1297
1358
1418
1449
0.2
Bhp
3.35
4.05
4.85
5.74
6.75
7.98
9.12
10.49
12.00
12.80
Watts
2,769
3,348
4,007
4,750
5,583
6,511
7,450
8,674
9,919
10,58
Rpm
1002
1057
1113
1169
1226
1284
1342
1400
1459
−
0.4
Bhp
3.80
4.53
5.35
6.28
7.31
8.46
9.74
11.14
12.67
−
Watts
3,140
3,742
4,424
5,190
6,047
6,999
8,051
9,209
10,478
−
Rpm
1061
1112
1165
1219
1274
1329
1385
1442
−
−
Available External Static Pressure (in. wg)
0.6
0.8
Watts
Bhp
Watts
Rpm
Bhp
4.27
3528
1117
4.76
3,934
5.02
4152
1166
5.54
4,579
5.87
4856
1216
6.41
5,304
6.83
5645
1268
7.40
6,114
7.89
6524
1320
8.48
7,015
9.07
7499
1374
9.69
8,012
11.02
10.37
8574
1428
9,110
12.47
10,314
9755
1483
11.8
−
−
−
−
−
−
−
−
−
−
PGE300 (25 TONS) Low Heat* (cont)
Available External Static Pressure (in. wg)
Airflow
1.4
1.6
(Cfm)
Watts
Rpm
Bhp
Rpm
Bhp
Watts
Rpm
7,000
1274
6.35
5248
1323
6.92
5,718
1371
7,500
1316
7.20
6960
1364
7.79
6,437
1410
8,000
1360
8.14
6734
1406
8.76
7,239
1450
8,500
1406
9.20
7605
1449
9.83
8,129
1492
9,000
1453
10.36
8568
1495
11.02
9,111
1536
9,500
1501
11.64
9627
154
12.32
10,19
−
1.8
Bhp
5.54
6.41
7.40
8.48
9.69
−
Rpm
1171
1218
1266
1315
1365
1417
1469
1523
−
−
1.0
Bhp
5.27
6.07
6.97
7.98
9.09
10.33
11.68
13.16
−
−
Watts
4,356
5,210
5,766
6,597
7,520
8,538
9,657
10,883
−
−
Rpm
1224
1268
1314
1361
1410
1459
1510
−
−
−
1.2
Bhp
5.80
6.63
7.55
8.58
9.72
10.98
12.36
−
−
−
Watts
4,794
5,478
6,243
7,094
8,037
9,076
10,217
−
−
−
Watts
6204
6939
7759
8666
9667
−
PGE300 (25 TONS) High Heat*
Airflow
(Cfm)
7,000
7,500
8,000
8,500
9,000
9,500
10,000
10,500
11,000
11,250
Rpm
992
1055
1118
1182
1246
1310
1374
1439
1503
1536
0.2
Bhp
4.05
4.77
5.58
6.46
7.42
8.47
9.61
10.84
12.17
12.86
Watts
3,348
3,947
4,610
5,339
6,136
7,005
7,947
8,964
10,059
10,636
Rpm
1051
1110
1170
1231
1292
1354
1416
1479
1542
−
0.4
Bhp
4.44
5.17
5.99
6.88
7.86
8.92
10.07
11.32
12.65
−
Watts
3,668
4,277
4,950
5,690
6,498
7,377
8,329
9,356
10,460
−
Rpm
1106
1162
1220
1278
1337
1397
1457
1518
−
−
Available External Static Pressure (in. wg)
0.6
0.8
Bhp
Watts
Rpm
Bhp
4.83
3995
1160
5.24
5.58
4615
1214
6.00
6.41
5298
1268
6.84
7.31
6047
1324
7.75
8.30
6865
1381
8.75
9.38
7754
1439
9.84
10.54
8715
1497
11.02
11.79
9752
−
−
−
−
−
−
−
−
−
−
PGE300 (25 TONS) High Heat* (cont)
Available External Static Pressure (in. wg)
Airflow
1.4
1.6
(Cfm)
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
7,000
1311
6.51
5385
1359
6.96
5751
1405
7,500
1358
7.30
6039
1403
7.76
6412
1448
8,000
1406
8.17
6767
1560
8.63
7137
1492
8,500
1456
9.12
7541
1498
9.59
7929
1539
9,000
1507
10.15
8393
1548
10.63
8790
−
1.8
Bhp
6.00
6.84
7.75
8.75
−
Watts
4331
4960
5653
6411
7239
8137
9107
−
−
−
Rpm
1212
1263
1315
1369
1424
1480
1537
−
−
−
1.0
Bhp
5.65
6.43
7.27
8.20
9.21
10.31
11.50
−
−
−
Watts
4675
5312
6014
6782
7618
8525
9504
−
−
−
Rpm
1262
1311
1361
1413
1466
1520
−
−
−
−
1.2
Bhp
6.08
6.86
7.72
8.66
9.68
10.79
−
−
−
−
Watts
5026
5672
6382
7158
8003
8918
−
−
−
−
Watts
6124
6792
7524
8323
−
LEGEND
Bhp - Brake Horsepower
Watts - Input Watts to Motor
*Standard low-medium drive range is 1066 to 1283 rpm. Alternate high-static drive range is 1332 to 1550. Other rpms may require a field-supplied
drive.
NOTES:
1. Maximum continuous Bhp for the standard motor is 10.20 (208/230v and 575v units) and 11.80 (460v units). Maximum continuous watts are 9150
(208/230v and 575v units) and 11,000 (460v units). Do not adjust motor rpm such that motor maximum bhp and/or watts is exceeded at the maximum
operating cfm.
2. See General Notes for Fan Performance following this section.
GENERAL NOTES FOR FAN PERFORMANCE TABLES:
1. Static pressure losses must be added to external static pressure before entering Fan Performance table.
2. Interpolation is permissible. Do not extrapolate.
3. Fan performance is based on wet coils, clean filters, and casing losses. (See Accessory/FIOP Static Pressure table)
4. Extensive motor and drive testing on these units ensures that the full horsepower and watts range of the motor can be utilized with confidence.
Using fan motors up to the watts or bhp rating shown will not result in nuisance tripping or premature motor failure. Unit warranty will not be
affected.
5. Use of a field−supplied motor may affect wire size.
521 21 1001 04
Specifications subject to change without notice.
65
PERFORMANCE DATA − PGE180−300 (cont.)
FAN PERFORMANCE USING ACCESSORY POWER EXHAUST
ALTITUDE DERATING FACTOR*
Elevation
(ft)
0−2,000
2,001−3,000
3,001−4,000
4,001−5,000
5,001−6,000
Maximum Heating Value
(Btu/ft3)
1,100
1,050
1,000
950
900
*Derating of the unit is not required unless the heating value of the gas exceeds
the values listed in the table above, or if the elevation exceeds 6000 ft. Derating
conditions must be 4% per thousand feet above 2000 ft. For example, at 4000
ft, if the heating value of the gas exceeds 1000 Btu/ft3, the unit will require a 16%
derating. For elevations above 6000 ft, the same formula applies. For example,
at 7000 ft, the unit will require a 28% derating of the maximum heating value
per the National Fuel Gas Code.
IMPORTANT: Local utility companies may be reducing heat content of gas at
altitudes above 2000 ft. If this is being done, changing spuds may not be
required.
NOTE: Performance is for the DN series Power Exhaust
ALTITUDE COMPENSATION (LP Gas Units)
ALTITUDE COMPENSATION
ELEVATION
(ft)
0−3,000
3,000−7,000
7,000−9,000
9,000−10,000
above 10,000
NATURAL GAS ORIFICE SIZE
Low Heat
High Heat
30
29
31
30
32
31
33
31
35
32
ELEVATION (ft)
0−2,000
2,000
3,000
4,000
5,000
6,000
7,000
8,000
9,000
10,000
*Includes a 4% input reduction per each 1,000 feet.
{Orifice available through dealer.
Propane Orifice Size
Low Heat and High Heat
36
37
38
38
39
40
41
41
42
43
OUTDOOR SOUND POWER
UNIT PGE
180
210
240
300
SOUND
RATING (60
Hz)
88 dB
88 dB
94 dB
94 dB
OCTAVE BANDS
A−WEIGHTED (dB)
87.6
87.8
94.4
94.1
63
90.8
90.8
99.7
98.7
125
88.7
88.7
93.0
92.3
250
86.4
86.4
93.7
93.8
500
84.3
84.3
91.8
90.9
1000
83.5
83.5
89.7
89.6
2000
78.4
78.4
85.9
85.9
4000
75.6
75.6
80.7
80.3
8000
66.8
66.8
74.4
74.3
LEGEND
Bels - Sound Levels (1 bel = 10 decibels)
66
Specifications subject to change without notice.
521 21 1001 04
PERFORMANCE DATA − PGE180−300 (cont.)
ACCESSORY/FIOP STATIC PRESSURE (in. wg)*
CFM
COMPONENT
Economizer
4500
5000
5400
6000
7200
7500
9000
10,000
11,250
0.040
0.050
0.060
0.070
0.090
0.100
0.110
0.120
0.140
LEGEND
FIOP - Factory Installed Option
*The static pressure must be added to external static pressure. The sum and the evaporator entering−air cfm should then be used in conjunction
with the Fan Performance tables to determine blower rpm and watts.
NOTE: Performance is for the DN series Economizer
FAN RPM AT MOTOR PULLEY SETTINGS*
MOTOR PULLEY TURNS OPEN
UNIT
PGE
0
1/2
1
11/2
2
21/2
3
31/2
4
41/2
5
51/2
6
180 {
180**
{{
{{
{{
{{
1021
1002
984
965
947
928
910
891
873
{{
{{
1156
1134
1112
1091
1069
1047
1025
{{
{{
1077
1178
{{
{{
1095
1200
210 {
210**
1058
1040
1021
1002
984
965
947
928
910
{{
{{
1287
1265
1243
1222
1200
1178
1156
1134
1112
1091
1069
240 {
240**
{{
{{
{{
{{
1151
1132
1114
1095
1077
1058
1040
1021
1002
{{
{{
1347
1325
1303
1281
1259
1237
1215
1193
{{
{{
{{
1269
1369
300 {
300**
{{
1283
1247
1225
1203
1182
1160
1138
1116
1095
1066
{{
{{
{{
{{
1551
1524
1497
1470
1443
1415
1388
1361
1332
LEGEND
*Approximate fan rpm shown.
† Indicates standard drive package.
**Indicates alternate / high static drive package.
†† Due to belt and pulley size, pulley cannot be set to this number of turns open.
EVAPORATOR−FAN MOTOR PERFORMANCE
UNIT
PGE
UNIT
VOLTAGE
208/230
180
460
MAXIMUM
ACCEPTABLE
CONTINUOUS
BkW*
MAXIMUM
ACCEPTABLE
OPERATING
WATTS
6.13
4.57
5,180
300
7.9
6.0
208/230
15.8
5.90
4.40
5,180
7.9
208/230
8.70
6.49
7,915
22.0
460
9.50
7.08
8,640
13.0
575
8.70
6.49
7,915
10.0
208/230
10.20
7.61
9,510
28.0
460
11.80
8.80
11,000
14.6
575
10.20
7.61
9,510
13.0
575
240
MAXIMUM
AMP DRAW
15.8
575
460
210
MAXIMUM
ACCEPTABLE
CONTINUOUS
BHP*
6.0
LEGEND
BHP − Brake Horsepower
BkW − Brake Kilowatts
*Extensive motor and electrical testing on these units ensures that the full horsepower (brake kilowatt) range of the motors can be utilized with
confidence. Using your fan motors up to the horsepower (brake kilowatt) ratings shown in this table will not result in nuisance tripping or
premature motor failure. Unit warranty will not be affected
NOTE: All indoor−fan motors 5 hp and larger meet the minimum efficiency requirements as established by the Energy Policy Act of 1992
(EPACT) effective October 24, 1997.
EVAPORATOR−FAN MOTOR EFFICIENCY
UNIT PGE
MOTOR EFFICIENCY (%)
5 Hp
87.5
7.5 Hp
88.5
10 Hp
89.5
NOTE:
The EPACT (Energy Policy Act of 1992) regulates energy requirements for specific types of indoor fan motors. Motors regulated by EPACT
include any general purpose, T−frame (three−digit, 143 and larger), single−speed, foot mounted, polyphase, squirrel cage induction motors
of NEMA (National Electrical Manufacturers Association) design A and B, manufactured for use in the United States. Ranging from 1 to 200
Hp, these continuous−duty motors operate on 230 and 460 volt, 60 Hz power. If a motor does not fit into these specifications, the motor does
not have to be replaced by an EPACT compliant energy efficient motor. Variable−speed motors are exempt from EPACT compliance
requirements. Therefore, the indoor−fan motors for these units are exempt from these requirements.
521 21 1001 04
Specifications subject to change without notice.
67
ELECTRICAL DATA − PGE180−300
UNIT
PGE
Nominal
Voltage
(3 Ph,
60 Hz)
COMPRESSOR
VOLTAGE
RANGE
Min
Max
No. 1
RLA
No. 1 A
LRA
RLA
OFM
No. 2
LRA
RLA
LRA
Qty
Hp
POWER
EXHAUST *
IFM
FLA
(ea)
Hp
FLA
208/230
187
253
32.1
195
−
−
20.7
156
3
0.5
1.7
5.0
15.8/15.8
460
414
508
16.4
95
−
−
10
70
3
0.5
0.8
5.0
7.9
575
518
633
12
80
−
−
8.2
54
3
0.5
0.75
5.0
6.0
208/230
187
253
30.1
225
−
−
28.8
195
3
0.5
1.7
5.0
15.8/15.8
460
414
508
15.5
114
−
−
14.7
95
3
0.5
0.8
5.0
7.9
575
518
632.5
12.1
80
−
−
10.7
80
3
0.5
0.75
5.0
6.0
208/230
187
253
42
239
−
−
33.6
225
2
1
6.6
7.5
25.0/25.0
460
414
508
19.2
125
−
−
17.3
114
2
1
3.3
7.5
13.0
575
518
633
13.8
80.0
−
−
13.5
80.0
2
1.0
3.4
7.5
10.0
208/230
187.2
253
20.7
156
20.7
156
47.1
245
6
0.5
1.7
10.0
28.0/28.0
460
414
508
10
75
10
75
19.6
125
6
0.5
0.8
10.0
14.6
575
517.5
632.5
8.2
54
8.2
54
15.8
100
6
0.5
0.8
10.0
13.0
180
210
240
300
COMBU
STION
FAN
MOTOR
POWER SUPPLY
FLA
LRA
FLA
MCA
MOCP*
−
4.6
−
2.3
−
2.1
−
4.6
−
2.3
−
2.1
−
4.6
−
2.3
−
2.1
−
4.6
−
2.3
−
2.1
−
18.8
−
6.0
−
4.8
−
18.8
−
6.0
−
4.8
−
18.8
−
6.0
−
4.8
−
18.8
−
6
−
4.8
0.57
0.57
0.30
0.30
82/82
86/86
41
43
31
34
87/87
92/92
44
47
34
36
124/124
129/129
61
63
48
50
138/138
143/143
64
66
54
56
110/110
110/110
50
50
40
40
110/110
110/110
50
60
40
40
150/150
150/150
80
80
60
60
175/175
150/175
80
80
60
70
0.57
0.57
0.57
0.30
0.30
0.57
0.57
0.57
0.30
0.30
0.57
0.57
0.57
0.30
0.30
0.57
* NOTE: Performance is for the DN series Power Exhaust
LEGEND
FLA
HACR
IFM
LRA
MCA
MOCP
NEC
OFM
RLA
− Full Load Amps
− Heating, Air Conditioning and Refrigeration
− Indoor Fan Motor
− Locked Rotor Amps
− Minimum Circuit Amps
− Maximum Overcurrent Protection
− National Electrical Code
− Outdoor Fan Motor
− Rated Load Amps
% Voltage Imbalance
= 100 x max voltage deviation from average voltage
average voltage
Example: Supply voltage is 460-3-60.
AB = 452 v
BC = 464 v
AC = 455 v
Average Voltage = 452 + 464 + 455
3
*Fuse or HACR circuit breaker.
NOTES:
1. In compliance with NEC requirements for multimotor and combination
load equipment (refer to NEC Articles 430 and 440), the overcurrent
protective device for the unit shall be fuse or HACR breaker. Canadian
units may be fuse or circuit breaker.
2. Unbalanced 3-Phase Supply Voltage - Never operate a motor where
a phase imbalance in supply voltage is greater than 2%. Use the
following formula to determine the percent of voltage imbalance.
POWER EXHAUST ELECTRICAL DATA
= 31371
3
= 457
Determine maximum deviation from average voltage.
(AB) 457 – 452 = 5 v
(BC) 464 – 457 = 7 v
(AC) 457 – 455 = 2 v
Maximum deviation is 7 v.
Determine percent of voltage imbalance.
Unit
Model
AXB060PEH
AXB060PEL
AXB060PES
Application
Usage
180-300
180-300
180-300
Volt/Phase/Hertz
208/230/3/60
460/3/60
575/3/60
LRA
24.9
N/A
N/A
FLA
10.0
4.4
3.0
% Voltage Imbalance = 100 x
MCA
12.6
5.6
3.8
NOTE: AXB power exhaust is wired single phase, drop third leg when installing.
68
Fuse
Size
15
8
5
7
457
= 1.53%
This amount of phase imbalance is satisfactory as it is below the
maximum allowable 2%.
IMPORTANT: If the supply voltage phase imbalance is more than
2%, contact your local electric utility company immediately.
Specifications subject to change without notice.
521 21 1001 04
TYPICAL WIRING SCHEMATIC − PGE180, 460v Shown
LEGEND
AHA —
C
—
CAP —
CB
—
CC
—
CH
—
CLO —
COMP —
CR
—
DU
—
EQUIP —
FPT —
FU
GND
HPS
HS
HV
I
IDM
IFC
IFCB
IFM
IGC
—
—
—
—
—
—
—
—
—
—
—
L
LOR
LPS
LS
MGV
OFC
OFM
PL
PRI
QT
R
RS
SEN
SW
TB
TC
TH
TRAN
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
Adjustable Heat Anticipator
Contactor, Compressor
Capacitor
Circuit Breaker
Cooling Compensator
Crankcase Heater
Compressor Lockout
Compressor Motor
Control Relay
Dummy Terminal
Equipment
Freeze Protection
Thermostat
Fuse
Ground
High-Pressure Switch
Hall Effect Sensor
High Voltage
Ignitor
Induced-Draft Motor
Indoor-Fan Contactor
Indoor-Fan Circuit Breaker
Indoor-Fan Motor
Integrated Gas Unit
Controller
Light
Lockout Relay
Low-Pressure Switch
Limit Switch
Main Gas Valve
Outdoor-Fan Contactor
Outdoor-Fan Motor
Plug Assembly
Primary
Quadruple Terminal
Relay
Rollout Switch
Sensor
Switch
Terminal Block
Thermostat, Cooling
Thermostat, Heating
Transformer
Terminal (Marked)
Terminal (Unmarked)
Terminal Block
Splice
Factory Wiring
Field Wiring
Option/Accessory Wiring
To indicate common
potential only, not to
represent wiring.
521 21 1001 04
Specifications subject to change without notice.
69
TYPICAL WIRING SCHEMATIC − PGE180−300
ECONOMIZER WIRING
a48-7877
NOTE: Wiring is for the DN series Economizer
AL
ECB
IA
IAQ
— Ambient Limit
— Economizer Control Board
— Indoor Air
— Indoor Air Quality
LEGEND
OA —
OAS—
RAS—
SAT —
Outdoor Air
Outdoor Air Sensor
Return Air Sensor
Supply Air Temperature
TYPICAL PIPING AND WIRING − PGE180−300
LEGEND
NEC — National Electrical Code
70
b48-1258
Specifications subject to change without notice.
521 21 1001 04
GUIDE SPECIFICATIONS − PGE180−300
CONSTANT VOLUME APPLICATION
PART 1 − GENERAL
1.01 SYSTEM DESCRIPTION
Unit is an outdoor rooftop mounted, electrically controlled heating
and cooling unit utilizing scroll hermetic compressors for cooling
duty and gas combustion for heating duty. Supply air shall be
discharged downward or horizontally (with horizontal
supply/return curb adapter assembly), as shown on contract
drawings. Standard unit shall include a manual outdoor air inlet.
1.02 QUALITY ASSURANCE
A. Unit shall be rated in accordance with ARI Standards 270 and 360
and all units shall be designed in accordance with UL Standard
1995.
NOTE: Size 300 units are beyond the scope of ARI certification
guidelines.
B. Unit shall be designed to conform to ASHRAE 15.
C. Unit shall be ETL and ETL, Canada tested and certified in
accordance with ANSI Z21.47 Standards as a total package.
D. Roof curb shall be designed to conform to NRCA Standards.
E. Insulation and adhesive shall meet NFPA 90A requirements for
flame spread and smoke generation.
F. Unit casing shall be capable of withstanding 500−hour salt spray
exposure per ASTM B117 (scribed specimen).
G. Unit shall be manufactured in a facility registered to ISO
9001:2000.
1.03 DELIVERY, STORAGE, AND HANDLING
Unit shall be stored
recommendations.
and
handled
per
manufacturer’s
PART 2 − PRODUCTS
2.01 EQUIPMENT (STANDARD)
A. General: Each unit shall be a factory assembled, single piece
heating and cooling unit. Contained within the unit enclosure
shall be all factory wiring, piping, controls, refrigerant charge
(R−22), and special features required prior to field start−up.
B. Unit Cabinet:
1.Constructed of galvanized steel (G90 − 1.8 oz. of zinc per square
foot of sheet metal), bonderized and primer coated on both
sides and coated with a baked polyester thermosetting
powdercoating finish on the outer surface.
2. Indoor blower compartment interior surfaces shall be insulated
with a minimum 1/2−in. thick, 1 lb density fiberglass insulation.
Fiberglass insulation shall be bonded with a thermosetting resin
(8 to 12% by weight nominal, phenol formaldehyde typical), and
coated with an acrylic or other material that meets the NFPA 90
flame retardance requirements and has an ”R” Value of 3.70.
Aluminum foil faced fiberglass insulation shall be used in the
gas heat compartment.
3. Cabinet panels shall be easily removable for servicing. Cabinet
panels are minimum 20 gage. Panels shall have 1/2−in. thick,
1.5−lb. density insulation.
4. Filters shall be accessible through an access panel.
5. Holes shall be provided in the base rails (minimum 12 gage) for
rigging shackles to facilitate overhead rigging.
6. Unit shall contain a sloped drain pan, to prevent standing water
from accumulating. Pan shall be fabricated of hot dipped zinc
coated minimum spangle steel. Zinc coating shall be G90
designation according to ASTM Standard A653. Unit shall
contain a factory installed nonferrous main condensate drain
connection.
521 21 1001 04
C. Fans:
1. Indoor blower (evaporator fan):
a. Fan shall be belt driven. Belt drive shall include an adjustable
pulley. The standard fan drive shall have a factory installed
low−medium external static pressure capable fan drive. The
alternate fan drive option shall have a factory installed
external high static pressure capable fan drive.
b. Fan wheel shall be made from steel with a corrosion
resistant finish. It shall be a dynamically balanced, double
inlet type with forward curved blades.
2. Condenser fans shall be of the direct driven propeller type, with
corrosion resistant blades riveted to corrosion resistant steel
supports. They shall be dynamically balanced and discharge air
upwards.
3. Induced draft blower shall be of the direct driven, single inlet,
forward curved, centrifugal type. It shall be made from steel with
a corrosion resistant finish and shall be dynamically balanced.
D. Compressor(s):
1. Fully hermetic, scroll type, internally protected.
2. Factory spring−shock mounted and internally spring mounted
for vibration isolation.
3. On electrically and mechanically independent refrigerant
circuits.
4. All compressors shall have 70 W crankcase heaters.
E. Coils:
1. Standard evaporator and condenser coils shall have aluminum
plate fins mechanically bonded to seamless internally grooved
copper tubes with all joints brazed.
2. Coils shall be leak tested at 150 psig and pressure tested at 450
psig.
F. Heating Section:
1. Induced draft combustion type with energy saving direct spark
ignition system and redundant main gas valve.
2. a. The heat exchanger shall be of the tubular section type
constructed of a minimum of 20−gage steel coated with a
nominal 1.2 mil aluminum silicone alloy for corrosion
resistance.
3. Burners shall be of the in−shot type constructed of aluminum
coated steel.
4. All gas piping shall enter the unit at a single location.
5. Gas piping shall be capable of being routed through the roof curb
directly into unit.
G. Refrigerant Components: Refrigerant circuit components shall
include:
1. Thermostatic expansion valve (TXV).
2. Filter driers.
3. Gage port and connections on suction, discharge, and liquid
lines.
H. Filter Section: Standard filter section shall consist of 2 sizes of
factory installed 2−in. thick throwaway fiberglass filters of
commercially available sizes. Filters shall be approximately 10%
efficient with an air−side pressure drop of approximately 0.07 in.
wg (clean).
I. Controls and Safeties:
1. Unit Controls:
a. Economizer control (optional).
b. Capacity control (2 step).
c. Unit shall be complete with self contained low voltage control
circuit.
J. Safeties:
a. Unit shall incorporate a solid state compressor lockout which
provides reset capability at the space thermostat, should any of
the following safety devices trip and shut off compressor:
1) Compressor lockout protection provided for either internal or
external overload.
2) low pressure switch.
3) Dual freeze−stats (evaporator coil). 4) High pressure switch.
Specifications subject to change without notice.
71
GUIDE SPECIFICATIONS − PGE180−300 (cont.)
b. Supply air thermostat shall be located in the unit.
c. Heating section shall be provided with the following minimum
protections:
1) High temperature limit switch.
2) induced draft motor speed sensor.
3) Flame rollout switch.
4) Flame proving controls.
5) Redundant gas valve.
K. Operating Characteristics:
1. Unit shall be capable of starting and running at 120 F ambient
outdoor temperature per maximum load criteria of ARI Standard
360.
2. Unit with standard controls will operate in cooling down to an
outdoor ambient temperature of 40 F.
3. Unit shall be provided with fan time delay to prevent cold air
delivery.
L. Electrical Requirements:
All unit power wiring shall enter unit cabinet at a single location.
M. Motors:
1. Compressor motors shall be cooled by refrigerant gas passing
through motor windings and shall have line break thermal and
current overload protection.
2. All fan motors shall have permanently lubricated, sealed
bearings and inherent automatic reset thermal overload
protection or manual reset calibrated circuit breakers.
3. All indoor fan motors 5 hp and larger shall meet the minimum
efficiency requirements as established by the Energy Policy Act
of 1992 (EPACT) effective October 24, 1997.
N. Special Features
1. Integrated Economizers
a. Integrated integral modulating type capable of simultaneous
economizer and compressor operation.
b. Available as a factory−installed option in vertical
supply/return configuration only. (Available as a
field−installed accessory for dedicated horizontal and/or
vertical supply return configurations.)
c. Includes all hardware and controls to provide cooling with
outdoor air.
d. Equipped with low−leakage dampers, not to exceed 2%
leakage at 1 in. wg pressure differential.
e. Capable of introducing up to 100% outdoor air.
f. Economizer shall be equipped with a barometric relief
damper.
72
g. Designed to close damper(s) during loss−of power situations
with spring return built into motor.
h. Dry bulb outdoor−air temperature sensor shall be provided
as standard. Outdoor air sensor set point is adjustable and
shall range from 40° to 100° F. For the economizer, the return
air sensor, indoor enthalpy sensor, and outdoor enthalpy
sensor shall be provided as field installed accessories to
provide enthalpy control, differential enthalpy control, and
differential dry bulb temperature control.
i. Economizer controller shall use a mixed air thermistor
mounted on the evaporator fan housing to control
economizer operation to a supply air temperature of 55° F.
j. The economizer shall have a gear−driven parallel blade
design.
k. Economizer controller shall provide control of internal
building pressure through its accessory power exhaust
function. Factory set at 100%, with a range of 0% to 100%.
l. Economizer Controller Occupied Minimum Damper Position
Setting maintains the minimum airflow into the building
during occupied period providing design ventilation rate for
full occupancy (damper position during heating). A remote
potentiometer may be used to override the set point.
m. Economizer Controller Unoccupied Minimum Damper
Position Setting − The economizer damper shall be
completely closed when the unit is in the occupied mode.
n. Economizer Controller IAQ/DCV Maximum Damper Position
Setting − Setting the maximum position of the damper
prevents the introduction of large amounts of hot or cold air
into the space. This position is intended to satisfy the base
minimum ventilation rate.
o. Economizer controller IAQ/DCV control modulates the
outdoor−air damper to provide ventilation based on the
optional 2 to 10 vdc CO2 sensor input.
p. Compressor lockout sensor (opens at 35° F, closes at 50° F).
q. Actuator shall be direct coupled to economizer gear,
eliminating linkage arms and rods.
r. Control LEDs:
1. When the outdoor−air damper is capable of providing
free cooling, the “Free Cool” LED shall illuminate.
2. The IAQ LED indicates when the module is on the
DCV mode.
3. The EXH LED indicates when the exhaust fan contact
is closed.
s. Remote Minimum Position Control − A field−installed
accessory remote potentiometer shall allow the outdoor−air
damper to be opened or closed beyond the minimum position
in the occupied mode for modified ventilation.
Specifications subject to change without notice.
521 21 1001 04
CONTROLS − PGE072−300
OPERATING SEQUENCE, SIZE 072−150 UNITS Cooling, Units
Without Economizer − When thermostat calls for cooling, terminals
G and Y1 are energized. The indoor fan contactor (IFC) and
compressor contactor are energized and indoor fan motor,
compressor, and outdoor fan starts. The outdoor fan motor runs
continuously while unit is cooling. For units with 2 stages of cooling, if
the thermostat calls for a second stage of cooling by energizing Y2,
compressor contactor no. 2 (C2) is energized and compressor no. 2
starts. Heating, Units Without Economizer − When the thermostat
calls for heating, terminal W1 is energized. To prevent thermostat
short cycling, the unit is locked into the Heating mode for at least 1
minute when W1 is energized. The induced draft motor is energized
and the burner ignition sequence begins.
The indoor (evaporator) fan motor (IFM) is energized 45 seconds after
a flame is ignited. On units equipped for two stages of heat, when
additional heat is needed, W2 is energized and the high fire solenoid
on the main gas valve (MGV) is energized. When the thermostat is
satisfied and W1 is deenergized, the IFM stops after a 45 second time
off delay.
Cooling, Units With Economizer − When free cooling is not
available, the compressors will be controlled by the zone thermostat.
When free cooling is available, the outdoor air damper is modulated
by the Economizer control to provide a 50_ to 55_F mixed air
temperature into the zone. As the mixed air temperature fluctuates
above 55 or below 50 F, the dampers will be modulated (open or
close) to bring the mixed air temperature back within control.
If mechanical cooling is utilized with free cooling, the outdoor air
damper will maintain its current position at the time the compressor is
started. If the increase in cooling capacity causes the mixed air
temperature to drop below 45_ F, then the outdoor air damper position
will be decreased to the minimum position. If the mixed air
temperature continues to fall, the outdoor air damper will close.
Control returns to normal once the mixed air temperature rises above
48 F.
If optional power exhaust is installed, as the outdoor air damper opens
and closes, the power exhaust fans will be energized and
deenergized.
If field installed accessory CO2 sensors are connected to the
Economizer control, a demand controlled ventilation strategy will
begin to operate. As the CO2 level in the zone increases above the
CO2 set point, the minimum position of the damper will be increased
proportionally. As the CO2 level decreases because of the increase in
fresh air, the outdoor air damper will be proportionally closed.
For Economizer operation, there must be a thermostat call for the fan
(G). If the unit is occupied and the fan is on, the damper will operate at
minimum position. Otherwise, the damper will be closed when the
thermostat is satisfied.
When the Economizer control is in the occupied mode and a call for
cooling exists (Y1 on the thermostat), the control will first check for
indoor fan operation. If the fan is not on, then cooling will not be
activated. If the fan is on, then the control will open the Economizer
damper to the minimum position.
On the initial power to the Economizer control, it will take the damper
up to 21/2 minutes before it begins to position itself. Any change in
damper position will take up to 30 seconds to initiate. Damper
movement from full closed to full open (or vice versa) will take
between 11/2 and 21/2 minutes.
If free cooling can be used as determined from the appropriate
changeover command (switch, dry bulb, enthalpy curve, differential
dry bulb, or differential enthalpy), then the control will modulate the
dampers open to maintain the mixed air temperature set point at 50 to
55_F.
521 21 1001 04
If there is a further demand for cooling (cooling second stage − Y2
is energized), then the control will bring on compressor stage 1 to
maintain the mixed air temperature set point. The Economizer
damper will be open at maximum position. Economizer operation
is limited to a single compressor.
Heating, Units With Economizer NOTE:
The units have 2 stages of heat. When the thermostat calls for
heating, power is sent to W1 on
the IGC (integrated gas unit controller) board. An LED (light
emitting diode) on the IGC board will be on during normal
operation. A check is made to ensure that the rollout switch and
limit switch are closed and the induced draft motor is running. The
induced draft motor is then energized, and when speed is proven
with the hall effect sensor on the motor, the ignition activation
period begins. The burners will ignite within 5 seconds.
If the burners do not light, there is a 22 second delay before
another 5 second attempt. If the burners still do not light, this
sequence is repeated for 15 minutes. After the 15 minutes have
elapsed, if the burners still have not lit, heating is locked out. To
reset the control, break 24v power to the thermostat.
When ignition occurs the IGC board will continue to monitor the
condition of the rollout and limit switches, the hall effect sensor, as
well as the flame sensor. If the unit is controlled through a room
thermostat set for fan auto., 45 seconds after ignition occurs, the
indoor fan motor will be energized (and the outdoor air dampers
will open to their minimum position). If for some reason the over
temperature limit opens prior to the start of the indoor fan blower,
on the next attempt, the 45 second delay will be shortened to 5
seconds less than the time from initiation of heat to when the limit
tripped. Gas will not be interrupted to the burners and heating will
continue. Once modified, the fan on delay will not change back to
45 seconds unless power is reset to the control.
When additional heat is required, W2 closes and initiates power to
the second stage of the main gas valve. When the thermostat is
satisfied, W1 and W2 open and the gas valve closes, interrupting
the flow of gas to the main burners. If the call for W1 lasted less
than 1 minute, the heating cycle will not terminate until 1 minute
after W1 became active. If the unit is controlled through a room
thermostat set for fan auto., the indoor fan motor will continue to
operate for an additional 45 seconds then stop (and the outdoor
air dampers will close). If the over temperature limit opens after
the indoor motor is stopped within 10 minutes of W1 becoming
inactive, on the next cycle the time will be extended by 15
seconds. The maximum delay is 3 minutes. Once modified, the
fan off delay will not change back to 45 seconds unless power is
reset to the control.
When the thermostat is satisfied and W1 and W2 are
deenergized, the IFM continues to run and the economizer
damper then moves to the minimum position.
OPERATING SEQUENCE, PGE180−300 Cooling, Units
Without Economizer − When thermostat calls for cooling,
terminals G and Y1 are energized. The indoor (evaporator) fan
contactor (IFC) and compressor contactor no. 1 (C1) are
energized, and evaporator fan motor (IFM), compressor no. 1 and
condenser fan(s) start. The condenser fan motor(s) runs
continuously while unit is cooling. When the thermostat calls for a
second stage of cooling by energizing Y2, compressor contactor
no. 2 (C2) is energized and compressor no. 2 starts.
Heating, Units Without Economizer − When the thermostat
calls for heating, power is sent to W on the IGC (integrated gas
unit controller) board. An LED (light emitting diode) on the IGC
board will be on during normal operation. A check is made to
ensure that the rollout switch and limit switch are closed. The
induced draft motor is then energized, and when speed is proven
with the hall effect sensor on the motor, the ignition activation
period begins. The burners will ignite within 5 seconds.
Specifications subject to change without notice.
73
CONTROLS − PGE072−300
If the burners do not light, there is a 22 second delay before
another 5−second attempt. If the burners still do not light, this
sequence is repeated for 15 minutes. After the 15 minutes have
elapsed, if the burners still have not lit, heating is locked out. To
reset the control, break 24v power to the thermostat.
When the Economizer control is in the occupied mode and a call for
cooling exists (Y1 on the thermostat), the control will first check for
indoor fan operation. If the fan is not on, then cooling will not be
activated. If the fan is on, then the control will open the Economizer
damper to the minimum position.
When ignition occurs the IGC board will continue to monitor the
condition of the rollout and limit switches, the hall effect sensor, as
well as the flame sensor. If the unit is controlled through a room
thermostat set for fan auto, 45 seconds after ignition occurs, the
indoor−fan motor will be energized. If for some reason the over
temperature limit opens prior to the start of the indoor fan blower,
on the next attempt, the 45−second delay will be shortened to 5
seconds less than the time from initiation of heat to when the limit
tripped. Gas will not be interrupted to the burners and heating will
continue. Once modified, the fan on delay will not change back to
45 seconds unless power is reset to the control.
On the initial power to the Economizer control, it will take the damper
up to 21/2 minutes before it begins to position itself. Any change in
damper position will take up to 30 seconds to initiate. Damper
movement from full closed to full open (or vice versa) will take
between 11/2 and 21/2 minutes.
When additional heat is required, W2 closes and initiates power to
the second stage of the main gas valve. When the thermostat is
satisfied, W1 and W2 open and the gas valve closes, interrupting
the flow of gas to the main burners. If the call for W1 lasted less
than 1 minute, the heating cycle will not terminate until 1 minute
after W1 became active. If the unit is controlled through a room
thermostat set for fan auto., the indoor fan motor will continue to
operate for an additional 45 seconds then stop. If the over
temperature limit opens after the indoor motor is stopped within
10 minutes of W1 becoming inactive, on the next cycle the time
will be extended by 15 seconds. The maximum delay is 3 minutes.
Once modified, the fan off delay will not change back to 45
seconds unless power is reset to the control.
An LED indicator is provided on the IGC to monitor operation. The
IGC is located by removing the side panel and viewing the IGC
through the view port located in the control box access panel.
During normal operation, the LED is continuously on.
Cooling, Units With Economizer − When free cooling is not
available, the compressors will be controlled by the zone
thermostat. When free cooling is available, the outdoor air
damper is modulated by the Economizer control to provide a 50 to
55_F mixed air temperature into the zone. As the mixed air
temperature fluctuates above 55 or below 50 F, the dampers will
be modulated (open or close) to bring the mixed air temperature
back within control.
If mechanical cooling is utilized with free cooling, the outdoor air
damper will maintain its current position at the time the
compressor is started. If the increase in cooling capacity causes
the mixed air temperature to drop below 45_F, then the outdoor air
damper position will be decreased to the minimum position. If the
mixed air temperature continues to fall, the outdoor air damper
will close. Control returns to normal once the mixed air
temperature rises above 48 F.
If optional power exhaust is installed, as the outdoor air damper
opens and closes, the power exhaust fans will be energized and
deenergized.
If field installed accessory CO2 sensors are connected to the
Economizer control, a demand controlled ventilation strategy will
begin to operate. As the CO2 level in the zone increases above the
CO2 set point, the minimum position of the damper will be
increased proportionally. As the CO2 level decreases because of
the increase in fresh air, the outdoor air damper will be
proportionally closed.
For Economizer operation, there must be a thermostat call for the fan
(G). If the unit is occupied and the fan is on, the damper will operate at
minimum position. Otherwise, the damper will be closed.
If free cooling can be used as determined from the appropriate
changeover command (switch, dry bulb, enthalpy curve, differential
dry bulb, or differential enthalpy), then the control will modulate the
dampers open to maintain the mixed air temperature set point at 50
to 55_F.
If there is a further demand for cooling (cooling second stage − Y2 is
energized), then the control will bring on compressor stage 1 to
maintain the mixed air temperature set point. The Economizer
damper will be open at maximum position. Economizer operation is
limited to a single compressor.
Heating, Units With Economizer
NOTE: The units have 2 stages of heat. When the thermostat
calls for heating, power is sent to W1 on the IGC (integrated gas
unit controller) board. An LED (light emitting diode) on the IGC
board will be on during normal operation. A check is made to
ensure that the rollout switch and limit switch are closed and the
induced draft motor is running. The induced draft motor is then
energized, and when speed is proven with the hall effect sensor
on the motor, the ignition activation period begins. The burners
will ignite within 5 seconds.
If the burners do not light, there is a 22 second delay before another
5 second attempt. If the burners still do not light, this sequence is
repeated for 15 minutes. After the 15 minutes have elapsed, if the
burners still have not lit, heating is locked out. To reset the control,
break 24v power to the thermostat.
When ignition occurs the IGC board will continue to monitor the
condition of the rollout and limit switches, the hall effect sensor, as
well as the flame sensor. If the unit is controlled through a room
thermostat set for fan auto., 45 seconds after ignition occurs, the
indoor fan motor will be energized (and the outdoor air dampers will
open to their minimum position). If for some reason the over
temperature limit opens prior to the start of the indoor fan blower, on
the next attempt, the 45 second delay will be shortened to 5 seconds
less than the time from initiation of heat to when the limit tripped. Gas
will not be interrupted to the burners and heating will continue. Once
modified, the fan on delay will not change back to 45 seconds unless
power is reset to the control.
When additional heat is required, W2 closes and initiates power to
the second stage of the main gas valve. When the thermostat is
satisfied, W1 and W2 open and the gas valve closes, interrupting the
flow of gas to the main burners. If the call for W1 lasted less than 1
minute, the heating cycle will not terminate until 1 minute after W1
became active. If the unit is controlled through a room thermostat set
for fan auto., the indoor fan motor will continue to operate for an
additional 45 seconds then stop (and the outdoor air dampers will
close). If the over temperature limit opens after the indoor motor is
stopped within 10 minutes of W1 becoming inactive, on the next
cycle the time will be extended by 15 seconds. The maximum delay
is 3 minutes. Once modified, the fan off delay will not change back to
45 seconds unless power is reset to the control.
When the thermostat is satisfied and W1 and W2 are deenergized,
the IFM continues to run and the economizer damper then moves to
the minimum position.
International Comfort Products, LLC
Lewisburg, Tennessee 37091 USA
www.GoKeeprite.com
74
Specifications subject to change without notice.
521 21 1001 04
Was this manual useful for you? yes no
Thank you for your participation!

* Your assessment is very important for improving the work of artificial intelligence, which forms the content of this project