 Bl Se ries U PS 10 kVA lthree/single phase
“Three Level Inverter
Power Factor Correction
+ NEW TECHNOLOGY
> Three level inverter
> High and stable online efficiency (up to 94%)
> High input PF (20.95)
> Low output voltage THD (<2%)
> Short response time (<2ms)
> High input and output performance
+ RELIABLE & USER FRIENDLY
> Low investment and operation cost
> Short return on investment time
> Reduced weight/volume/footprint
> Wide input voltage tolerances (- 25%, +20%)
> Cold start
> Energy-saving sleep mode
> Short circuit, lightning and surge protection
> Remote emergency power off (EPO)
> Generator compatibility
> 1-5A adjustable charger (optional)
> Extended battery life with intelligent battery management
> Automatic battery test
> LCD interface and LED operation mode indicator
> Remote monitoring panel (optional)
> 128 event log
> Battery capacity and load percentage display
> SNMP (optional) and RS232 communication
° Remote monitoring and management software
° Dry contacts
° Smart fan control
> Internal battery
> Easy installation and maintenance
> 10 years spare part warranty
> 7/24 technical support and customer service
+ STANDARDS
> EN 62040-1 (Safety)
> EN 62040-2 (EMC)
» CE, ISO 9001:2008, ISO 14001, GOST
ELECTRO- LOCAL AREA
MEDICAL DEVICES NETWORKS
TELECOM INDUSTRIAL
APPLICATIONS PROCESSES
E-BUSINESS SMALL COMPUTERS
(SERVERS FARMS, NETWORK
ISP/ASP/POP)
{ale
COMPUTERS
SERVERS
E[EN B1 Series UPS 10 kvA
B1 SERIES UPS TECHNICAL SPECIFICATIONS
Power (kVA) 10
Voltage 380 / 400 / 415 Vac 3ph + N
Voltage Tolerances | - 25%, +20% (without downgrading)
Frequency 50 / 60 Hz
| Frequency Tolerances + 10%
Power Factor > 0.95
Voltage 220 / 230 / 240 Vac 1ph + N
Voltage Tolerances | + 1% (static load), dynamic load in accordance with VFI-SS-11
Frequency | 50 / 60 Hz
sI Frequency Tolerances + 0.1% (self-synchronize), + 1% (mains-synchronize)
Power Factor 0.7
THDw < 2% (linear load), < 5% (non-linear load)
Crest Factor 3:1
‚© 110% 30 min.
WTA] < 125% 60 sec.
CAPACITY < 150% 10 sec.
> 150% 3 sec.
Online up to 94%
Technology Three level inverter, PFC
Control Microprocessor, SPWM
Communication SNMP (optional), RS232
FETE Remote Monitoring | SNMPView , Remote monitoring panel (optional)
Dry Contacts Battery mode, Battery low
Custom Inputs Remote EPO
Cold Start Standard
Maintenance Bypass Standard
Operating Temperature from 0 °C up to +40 °C (from 20 °C to 25 °C for maximum battery life)
Relative Humidity | 0% - 85% (without condensation)
ENVIRONMENT
Maximum Altitude < 2000 m
= Noise Level < 45 dB (A)
Dimensions (W x D x H) (mm) 255 x 660 x 710
ILS Weight (kg) 44
CIEE Degree of Protection | IP20
| Colour RAL7012
Internal Battery Quantity 20 30
51500 Internal Battery Capacity (Ah) 7-9
External Battery Cabinet Socket Standard
fety EN 62040-1
EMC EN 62040-2
ELEN reserve the right of changing information in this without report. 25/01/2013