emfis DC
Operation and instruction manual for emfis DC
emfis DC
CH 3:(ENB) + 00L
0.0 kWh
MULTIFUNCTION DC ENERGY METER
HPL Electric & Power Pvt. Ltd.
1/21, Atma Ram Mansion, Asaf Ali Road, New Delhi-110002
Phone : 23234411, 23234811, 23236811; Fax : 23232639
E-Mail : hpl@hplindia.com, Website : www.hplindia.com
This document is not contractual, HPL Electric & Power Pvt. Ltd. reserves the
right to modify features without prior notice in view of continued improvements.
GCPK4DCMETER-H
SHIFT
HPL Electric & Power Pvt. Ltd.
emfis DC
HPL ELECTRIC & POWER PVT. LTD.
TEST CERTIFICATE
ITEM
: DC Multifunction Meter
METER SL. No.
:
RATING
:
CURRENT SENSOR TYPE :
20-60V DC
Shunt External (10-120mV)
CHANNEL
:
4 Channel
COMMUNICATION
:
RS485 MODBUS
MODEL
:
SL. NO.
01
6 Channel
Yes
No
EMFDC4CHA1SHXXX
EMFDC4CHA0SHXXX
EMFDC6CHA1SHXXX
EMFDC6CHA0SHXXX
TEST
RESULT
Voltage
OK
02
Current
OK
03
Communication
OK / N.A.
04
Meter Accuracy Test
OK
CERTIFIED BY:
Signature:
Dated:
Operation and Instruction Manual
21
emfis DC
emfis DC
6. Communication
emfis DC has RS485 communication (As per applicable in the model). MODBUS
(RTU) is used as communication protocol. Default Baud Rate is 9600bps and default
Device ID is 247. User can change Baud Rate as 4800, 9600, 19200, 28800,
38400bps and Device ID from 1 to 247. MODBUS (RTU) Address mapping given in
separate manual.
Technical Specifications
Enclosure:
l
Bezel Size
96mm x 96mm
l
Cutout Size
92mm x 92mm
l
Termination
Rear Side
l
Operating Temperature
-10 to 70 C
l
Weight
0
<350 grams
Contents
1.
Preliminary Operations ...................................... 02
2.
General Information ........................................... 02
3.
Installation.......................................................... 03
4.
Operations ......................................................... 05
5.
Programming Parameters.................................. 10
6.
Communication .................................................. 20
7.
Technical Specifications..................................... 20
8.
Test Certificate ................................................... 21
Front Panel:
l
Display
16x2 line Dot Matrix Backlit LCD Display
l
Character Size
5.0mm x 3.65mm
l
Protection Index
IP 54 (on front Panel)
This instruction manual is applicable for the following models:
S.No. Description
Model Number
1
4 channel with communication
l
Current Channels
4 channels / 6 channels (As applicable)
2
4 channel without communication
EMFDC4CHA0SHXXX
l
Current Sensor
External Shunt (configurable shunt rating
from 10 to 120 mV in multiples of 1 mV)
3
6 channel with communication
EMFDC6CHA1SHXXX
l
Current Range
Configurable (1 to 1000 Amps in multiples of 1A)
4
6 channel without communication
EMFDC6CHA0SHXXX
Inputs Current:
EMFDC4CHA1SHXXX
Inputs Voltage:
l
Input Voltage
20V DC to 60V DC
Note:
Auxiliary Supply:
Operation and Instruction Manual
1. Please check the correct reference number to your order.
2. MODBUS (RTU) Address mapping given in separate manual.
Self Powered
20
Operation and Instruction Manual
1
emfis DC
emfis DC
Caution
Keys
!
This equipment must be mounted only by professional. The manufacturer shall not
Instruction
Press once
Display
Comment
C h a n g eC a l i b
P WD ?
Ye s
Facilitate to change
Calibration password
be held responsible for failure to comply with the instructions in this manual.
Press “Enter” to change the calibration password of the meter. If default password is
4000, It can be set to any four digit number. Typical example showing how to change
calibration password from 4000 to 5432 is shown below.
1. Preliminary Operations
For personal & product safety please read the contents of these operation instructions
C h a n g eC a l i b
P WD ?
0 0 00
Press five
Times
C h a n g eC a l i b
P WD ?
5 0 00
Press once
C h a n g eC a l i b
P WD ?
5 0 00
Press four
times
C h a n g eC a l i b
P WD ?
5 4 00
Press once
C h a n g eC a l i b
P WD ?
5 4 00
carefully before connecting.
Check the following as you receive the emfis DC package:
a.
The Packing is in good condition.
b.
The product is not been damaged during transit.
c.
The Product reference number confirms to your order.
d.
Operating and Instruction manual.
2. General Information
The emfis DC is an instrument for measuring electrical values for a DC Electrical
Facilitate to change
Calibration password
Digit increments
by 5
Moves cursor
Right
Digit increments
by 4
System. By using 4 push buttons on the front panel and LCD display, you can configure
and display the parameters.
Moves cursor
Right
Measuring Parameters
●
●
●
●
●
●
●
Press three
C h a n g eC a l i b
times
Real Date / Time.
System Voltage.
P WD ?
5 4 30
Digit decrements
by 3
Current (Channel Wise).
Power (Channel Wise).
Press once
C h a n g eC a l i b
P WD ?
5 4 30
C h a n g eC a l i b
P WD ?
5 4 32
R e - E n t e r
PWD
0 0 0 0
Energy (Channel Wise).
Moves cursor
Right
Total Energy (Cumulative for all channels).
Press twice
Channel Status (Enable/Disable).
Press once
T h e
Digit decrements
by 2
Re Enter the
same Password
Re-Enter the same password as filled above and press Enter to confirm the setting
and to Exit from the programming mode.
Operation and Instruction Manual
2
Operation and Instruction Manual
19
emfis DC
Keys
Instruction
Display
Press once
Press once
S h u n t
0 1
Am p s
0 0 7 5
S h u n t
0 1
Am p s
0 0 8 5
emfis DC
Comment
3. Installation
Moves cursor
Right
The emfis DC is fitted on a Panel by means of four clips in a 96x96 flush mounted case.
Digit increments
To 8
emfis DC
CH 3:(ENB) + 00L
0.0 kWh
Press Enter to confirm the setting and to move on next parameter. Shunt input
current changes successfully, if it moves to next parameter otherwise it will show
Invalid value! on the display.
MULTIFUNCTION DC ENERGY METER
6.3 Change status of channel 1:
En t e r
CH 1
S t a tu s
E n b
To change status of
channel 1
SHIFT
To change status of the channel 1, press scroll up to change it to Dis, then press
enter to change and to move on next parameter.
Press once
En t e r
CH 1
S t a tu s
D i s
To change status of
channel 1
3.1. Mechanical Environment : To install the device properly the cutout
Press Enter to confirm the setting and to move on next parameter.
diagram given below should be followed closely.
Proceed for programming of channel 2-6 as followed for channel 1.
6.4 Energy Reset of channel 1:
R e s e t
k w h
CH
1 ?
N o
92mm
To reset energy of
channel 1
92mm +0.8mm
-0.0mm
To reset energy of the channel 1, press scroll up to change it to yes, then press enter
to reset and to move on next parameter.
86mm
Press once
R e s e t
k w h
CH
1 ?
Y e s
To reset the
Energy
+0.8mm
-0.0mm
emfis DC
Press Enter to confirm the setting and to move on next parameter.
36mm
Proceed for programming of channel 2-6 as followed for channel 1.
SHIFT
7. Change Calibration password:
C h a n g eC a l i b
Operation and Instruction Manual
P WD ?
N o
96mm
To change calibration
password
18
Operation and Instruction Manual
3
emfis DC
emfis DC
3.2 Climatic Environment : For optimum operation, it is recommended to use
o
this equipment between -10 to 70 C with relative humidity between 20 to 95%.
Keys
Instruction
6.1. Shunt Output Voltage:
Display
S h u n t
3.3 Connection Diagram:
0 1
Comment
( mV )
0 7 5
Default shunt
Output voltage
The shunt output voltage can be programmed from 010-120 mV in multiples of 1mV.
Typical example shows how to change shunt output voltage from 075 to 120 mV as
given below.
Press once
V. AUX
(48 VDC)
S h u n t
0 1
( mV )
1 7 5
Press once
S h u n t
0 1
( mV )
1 7 5
Press five
times
S h u n t
0 1
( mV )
1 2 5
Press once
S h u n t
0 1
( mV )
1 2 5
Press five
times
S h u n t
0 1
( mV )
1 2 0
RS 485
A +
A
B -
B
RS-485
Converter
GND
Current Channels : 0 to 75 mV
Ch-1
Ch-2
Ch-3
Ch-4
Ch-5
Digit increments
by 1
Moves cursor
Right
Digit increments
by 5
Ch-6
Moves cursor
Right
LOAD-1
Shunt-1
Shunt-2
LOAD-2
LOAD-3
Shunt-3
Shunt-4
LOAD-4
Shunt-5
LOAD-5
Shunt-6
LOAD-6
Digit decrements
by 5
Press Enter to confirm the setting and to move on next parameter. Shunt output
voltage changes successfully, if it moves to next parameter otherwise it will show
Invalid value! on the display.
6.2. Shunt Input Current:
S h u n t
DC
Am p s
0 0 7 5
Default shunt
Input current
The shunt input current can be programmed from 0001-1000 A. Typical example
shows how to change shunt input current from 0075 to 0085 A.
2
1. Use 0.25 to 0.5 mm cable for voltage terminal.
2. Use low impedance shielded twisted pair cable of max. length of 3 meter for shunt
output current.
3. A shielded twisted pair cable for RS 485 communication is recommended.
Operation and Instruction Manual
0 1
Press once
4
Operation and Instruction Manual
S h u n t
0 1
Am p s
0 0 7 5
Moves cursor
Right
17
emfis DC
emfis DC
Keys
Instruction
Display
Press once
Press once
4. Operations
4.1. Front Panel View:
E n t e r
D a t e
2 2 / 0 9 / 1 0
Digit increments
to 9
E n t e r
D a t e
2 2 / 0 9 / 1 0
Moves cursor
Right
E n t e r
Press once
Comment
D a t e
2 2 / 0 9 / 1 0
emfis DC
CH 1 :
1 . 0 1
Moves cursor
Right
Press Enter to confirm the setting and to move on next parameter. Date changes
successfully, if it moves to next parameter otherwise it will show Invalid Date! on the
display.
KW
2 0 . 1
5 0 . 5 6
V
A
SHIFT
6. Calibration Modification:
C a l i b
Mo d i f y ?
N o
Calibration modification enables user to change either shunt output voltage, shunt
input current or to reset energy of all channel. If user wants to change these
parameters please proceed as given below.
Press once
Press once
C a l i b
En t e r
Mo d i f y ?
Ye S
C a l i b PWD
0 0 0 0
Channel Number
C a l i b
Mo d i f y ?
Ye S
SHIFT
+
To go on programming mode (press both for 10sec.).
Enter.
Enter default
calibration
password
To move on next parameter or to increase digit during the programming.
Digit increment
by 1
Press Enter to confirm the setting and to move on next parameter. Calibration
password entered successfully, if it moves to next parameter otherwise it will show
Invalid value! on the display.
Operation and Instruction Manual
Current
Voltage
To modify
Calibration
Enter the calibration password to change shunt output voltage, shunt input current
and to reset the energy of any channel, if default calibration password is 1000.User
should change the password for security concern. Typical example shows how to
enter default calibration password is given below.
Press once
Power
16
To back on parameter and to move cursor right during the programming.
SHIFT
+
To decrease the digit during the programming mode.
SHIFT
+
To move cursor left during the programming mode.
Operation and Instruction Manual
5
emfis DC
emfis DC
Keys
4.2. Display Parameter:
(The following screen shots will follow in chronological order automatically)
Instruction
Display
Press once
E n t e r
T i me
2 1 : 2 0
Press three
times
E n t e r
T i me
2 1 : 5 0
Press once
E n t e r
T i me
2 1 : 5 0
Comment
Moves cursor
Right
This is a typical example of 6 channel model. For other models display
parameter will vary with respect to shunt configured.
1. Version Number:
Digit increments
to 5
Moves cursor
Right
Press Enter to confirm the setting and to move on next parameter. Time changes
successfully, if it moves to next parameter otherwise it will show Invalid Time! on the
display.
2. Serial Number, ID and Baud Rate:
5. Enter Date:
S r .
E n t e r
D a t e
1 1 / 0 8 / 1 0
Shows Default date
(DD/MM/YY)
To change the current date of the meter from 11/08/10 to 22/09/ 10 follow the
procedure as given below.
3. Real Date and Time:
Press once
E n t e r
D a t e
2 1 / 0 8 / 1 0
Digit increments
to 2
E n t e r
D a t e
2 1 / 0 8 / 1 0
Moves cursor
Right
E n t e r
D a t e
2 2 / 0 8 / 1 0
Digit increments
to 2
Press once
E n t e r
D a t e
2 2 / 0 8 / 1 0
Moves cursor
Right
Press once
E n t e r
D a t e
2 2 / 0 8 / 1 0
Moves cursor
Right
Press once
4. Total Energy (Cumulative for all Channels):
Press once
T o t a l
Operation and Instruction Manual
Σ ( 6
CH ) :
1 1 47
kWh
6
Operation and Instruction Manual
15
emfis DC
Keys
Instruction
Display
Press four
times
En t e r
Comment
Ba u d r a te
3 8 4 0 0
emfis DC
5. Energy, Channel Status and Overflow Count of Channel 1:
Baud rate changes
Successfully
CH
Press Enter to confirm the setting and to move on next parameter. Baud rate
changes successfully, if it moves to next parameter otherwise it will show Invalid
value! on the display.
3. Backlit Control:
Backlit control of the meter display can be programmed as 0 or 1. At zero (0)
backlight will ON only for one minute and by pressing shift or enter button it will again
light up for one minute. At 1 it will remain continuously ON. Typical example shows
how to change it from 0 to 1.
B a c k l i t
Press once
B a c k l i t
C o n t r o l
0
Co n t ro l
1
E n t e r
T i me
2 0 : 2 0
When energy reached 1000000, then there is an Energy overflow. Overflow count
shows 10 and energy is 00, this means
Proceed for channel 2-6 as followed for channel 1.
Digit increments
By 1
6. Instantaneous Value of Channel 1 (Voltage, Power, and Current):
Shows current time
(HH:MM)
CH 1 :
2 . 5 3
KW
5 0 . 1
5 0 . 5 1
V
A
7. Energy, Channel Status and Overflow Count of Channel 2:
To change the current time of the meter from 10:20 to 21:50 follow the procedure as
given below.
Press once
This shows Energy in Lacs
and Overflow count
This shows Energy.
Note: Here overflow (OF) is displayed like this 10, 20, 30…….etc,representing
additional energy in Lacs.
4. Enter Time:
T i me
1 0 : 2 0
This shows Channel Status
ENB: Enable
DIS : Disable
0 0 L
kWh
Total Energy = (Overflow count * 100000) + Energy.
To change backlit
Control
Press Enter to confirm the setting and to move on next parameter. Backlight of the
meter changes successfully, if it moves to next parameter otherwise it will show
Invalid value! on the display
E n t e r
1 : ( ENB )
+
1 5 . 1
Digit increments
to 2
CH
2 : ( D I S )
+
1 9 . 2
0 0 L
kWh
8. Instantaneous Value of Channel 2 (Voltage, Power, and Current):
Press once
Press once
Operation and Instruction Manual
E n t e r
E n t e r
T i me
2 0 : 2 0
T i me
2 1 : 2 0
Moves cursor
Right
CH 2 :
2 . 5 2
Digit increments
By 1
14
Operation and Instruction Manual
KW
4 8 . 6
5 1 . 7 1
V
A
7
emfis DC
9.
Energy, Channel Status and Overflow Count of Channel 3:
CH
3 : ( ENB )
+
2 2 . 3
emfis DC
1. Device ID:
To change the device ID of the meter press “Enter" button once. The default device
ID is 247. The device ID can be programmed 001 to 247. Typical example showing
how to change device ID from 005 to 152 is shown below:
Keys
Instruction
Display
Comment
0 0 L
kWh
E n t e r
D e v i c e ID
0 0 5
Default device ID
Press once
E n t e r
D e v i c e ID
1 0 5
Digit increments
by 1
Press once
E n t e r
De v i c e ID
1 0 5
Moves cursor
Right
Press five
Times
E n t e r
D e v i c e ID
1 5 5
Digit increments
by 5
Press once
En t e r
D e v i c e ID
1 5 5
Moves cursor
Right
Press three
times
En t e r
D e v i c e ID
1 5 2
Digit decrements
by 3
10. Instantaneous Value of Channel 3 (Voltage, Power, and Current):
CH 3 :
2 . 6 2
KW
5 0 . 5
5 1 . 9 1
V
A
11. Energy, Channel Status and Overflow Count of Channel 4:
CH
4 : ( ENB )
+
1 6 . 2
0 0 L
kWh
12. Instantaneous Value of Channel 4 (Voltage, Power, and Current):
CH 4 :
2 . 6 5
KW
4 9 . 9
5 3 . 2 1
V
A
SHIFT
Press Enter to confirm the setting and to move on next parameter. Device ID
changes successfully, if it moves to next parameter otherwise it will show Invalid
value! on the display.
13. Energy, Channel Status and Overflow Count of Channel 5:
CH
5 : ( ENB )
+
2 0 . 3
+
2. Baud Rate:
To change the MODBUS (RTU) communication baud rate of the meter. The default
baud rate is 9600 bps. The baud rate can be set as 4800, 9600, 19200, 28800, and
38400 bps. Typical example showing how to change baud rate from 4800 to
38400bps is shown below:
0 0 L
kWh
E n t e r
Operation and Instruction Manual
8
Operation and Instruction Manual
B a u d r a te
4 8 0 0
Default Meter
Baud rate
13
emfis DC
emfis DC
Keys
Instruction
Press once
Press once
Press once
Display
E n t e r
E n t e r
C a l i b
14. Instantaneous Value of Channel 5 (Voltage, Power, and Current):
Comment
T i me
2 0 : 2 0
D a t e
2 1 / 0 8 / 1 0
To change current
Time
CH 5 :
2 . 6 1
To change current
Date
KW
4 8 . 9
5 3 . 5 2
V
A
15. Energy, Channel Status and Overflow Count of Channel 6:
CH
Mo d i f y ?
No
6 : ( ENB )
+
2 4 . 1
0 0 L
kWh
Press Enter to Exit from programming mode. To see next parameters shunt output
voltage, shunt input current, and reset energy then proceed as given below.
16. Instantaneous Value of Channel 6 (Voltage, Power, and Current):
Press once
Press once
C a l i b
Mo d i f y ?
Ye s
To view next
Parameters
En t e r
C a l i b PWD
0 0 0 0
Enter calibration
Password
CH 6 :
2 . 1 9
Enter the calibration password (Default password is 1000, Factory programmed) to
view next programming parameter and proceed as given below.
Press once
S h u n t
0 1
( mV )
0 7 5
To change output
Shunt voltage
Press once
Sh u n t
0 1
Am p s
0 0 7 5
To change input
shunt current
S t a tu s
En b
To change
channel Status
CH
To reset energy of
specified channel
Press once
E n t e r
CH 1
Press once
R e s e t
k w h
1 ?
N o
KW
4 8 . 1
4 5 . 7 2
V
A
NOTE : In case shunt is not connected (open) to any of the channel then
meter will display as “Shunt Open” for respective channel.
CH 5 :
* * * Sh u n t
4 9 . 1
V
Op e n * * *
Proceed for programming of channel 2-6 as followed for channel 1.
Operation and Instruction Manual
12
Operation and Instruction Manual
9
emfis DC
5. Programming Parameters:
emfis DC
Keys
emfis DC can be programmed by 4 push buttons in the front plate. The programming
Instruction
Display
Comment
Press Twice
En t e r
N ew
PWD
1 2 0 0
Digit increments
by 2
Press once
E n t e r
N e w
P WD
1 2 0 0
Moves cursor
Right
Press Three
Times
En t e r
N ew
PWD
1 2 3 0
Digit increments
by 3
parameters for different models of DC meters are given below:
How to enter into the programming mode.
Keys
SHIFT
+
Instruction
Display
Comment
Press once
(For 10 sec.)
Enter default
Password
Enter the password (Default password is 1000, Factory programmed) to access the
programming parameters. A typical example shows how to enter the default
password.
Press once
E n t e r
Press once
C h a n g e
P a s s w o r d
1 0 0 0
Digit increments
to 1
Press once
E n t e r
N e w
P WD
1 2 3 0
Moves cursor
Right
P a s sw o rd ?
No
To retain same
Password
Press Four
Times
En t e r
N ew
PWD
1 2 3 4
Digit increments
by 4
Press Enter to retain same password and to directly go on programming parameters.
To change default password proceed as given below. A Typical example shows how
to change password from 1000 to 1234.
Press once
C h a n g e
Press once
P a s s w o rd ?
Y e s
To change default
Password
E n t e r
N ew
P WD
0 0 0 0
Enter new
Password
Press once
E n t e r
N ew
PWD
1 0 0 0
Digit increments
by 1
Press once
E n t e r
N e w
P WD
1 0 0 0
Operation and Instruction Manual
Press once
Re Enter the
same Password
R e -
Re-Enter the same password as filled earlier to validate the password and press
“Enter” to go on next programming parameter.
Press once
E
Press once
En t e r
Press once
B a c k l i t
Moves cursor
Right
10
Operation and Instruction Manual
To change
device ID
B a u d r a te
9 6 0 0
Co n t ro l
1
To change
Baud rate
To change backlit
Control
11