60 HZ MODEL
T4D-3500
LIQUID COOLED DIESEL ENGINE GENERATOR SET
Model
T4D-3500-60 HERTZ
HZ
60
STANDBY
PRIME
130ºC RISE
350
105ºC RISE
350
All generator sets are USA prototype built and thoroughly tested.
Production models are USA factory built and 100% load tested.
UL1446, UL508, UL142, UL498
NFPA 110, 99, 70, 37
All generator sets meet NFPA-110 Level 1, when equipped with the
necessary accessories and installed per NFPA standards.
NEC 700, 701, 702, 708
NEMA ICS10, MG1, ICS6, AB1
“OPEN” GEN-SET
There is no enclosure, so gen-set must be
placed within a weather protected area, uninhabited by humans or animals, with proper
ventilation. Silencer not supplied, as
installation requirements are not known.
However, this item is available as optional
equipment.
ANSI C62.41, 27, 59, 32, 480, 40Q, 81U, 360-05
ASCE 7-05 & 7-10
All generator sets meet 180 MPH rating.
EPA 40CFR Part 60, 89, 1039, 1048, 1054, 1065, 1068
“LEVEL 2” HOUSED GEN-SET
Full aluminum weather protection and superior
sound attenuation for specific low noise
applications. Critical grade muffler is standard.
GENERATOR RATINGS
VOLTAGE
GENERATOR
MODEL
L-N
L-L
T4D-3500-3-2
120
208
3
T4D-3500-3-3
120
240
T4D-3500-3-4
277
480
T4D-3500-3-5
T4D-3500-3-16
127
346
220
600
PH
HZ
130°°C RISE STANDBY RATING
105°°C RISE PRIME RATING
KW/KVA
AMP
KW/KVA
AMP
60
350/438
1216
350/438
1216
3
60
350/438
1054
350/438
1054
3
60
350/438
527
350/438
527
3
3
60
60
350/438
350/438
1150
421
350/438
350/438
1150
421
RATINGS: All three phase gen-sets are 12 lead windings, rated at .8 power factor. 130° C “STANDBY RATINGS” are strictly for gen-sets that are used for back-up
emergency power to a failed normal utility power source. This standby rating allows varying loads, with no overload capability, for the entire duration of utility power
outage. 105° C “PRIME RATINGS” are strictly for gen-sets that provide the prime source of electric power, where normal utility power is unavailable or unreliable. A 10%
overload is allowed for a total of 1 hour, within every 12 hours of operation, on every PRIME RATED systems. All gen-set power ratings are based on temperature rise
measured by resistance method as defined by MIL-STD 705C and IEEE STD 115, METHOD 6.4.4. All generators have class H (180°C) insulation system on both rotor and
stator windings. All factory tests and KW/KVA charts shown above are based 130°C (standby), and 105°C (prime) R/R winding temperature, within a maximum 40°C
ambient condition. Generators operated at standby power ratings must not exceed the temperature rise limitation for class H insulation system, as specified in NEMA MG122.40. Specifications & ratings are subject to change without prior notice.
Gillette Generators, Inc. • 2921 Thorne Dr. •Elkhart, IN • 46514 • Ph: 574-264-9639 • Fax: 574-262-1840 • Web: www.gillettegenerators.com • spc4-170414
1
APPLICATION & ENGINEERING DATA FOR MODEL T4D-3500-60 HZ
GENERATOR SPECIFICATIONS
GENERATOR FEATURES
Manufacturer ................................................ Stamford Generators
Model & Type ........ HCI534C-311, 4 Pole, 12 Lead, Three Phase
..................... HCI434F-311, 4 Pole, 12 Lead, 480V, Three Phase
....................... HCI434F-17, 4 Pole, 12 Lead, 600V, Three Phase
Exciter ..................................................... Brushless, shunt excited
Voltage Regulator ....................................... Solid State, HZ/Volts
Voltage Regulation ................................ ½%, No load to full load
Frequency ................................ Field convertible, 60 HZ to 50 HZ
Frequency Regulation ........± ½% (1/2 cycle, no load to full load)
Unbalanced Load Capability ..................... 100% of standby amps
One Step Load Acceptance .................. 100% of nameplate rating
Total Stator and Load Insulation ...........................Class H, 180°C
Temperature Rise .............105°C R/R, prime rating @ 40°C amb.
3 Ø Motor Starting @ 30% Voltage Dip (208-240V) ...1500 kVA
3 Ø Motor Starting @ 30% Voltage Dip (480V-600V) 2300 kVA
Bearing ..................................................... 1, Pre-lubed and sealed
Coupling ......................................................... Direct flexible disc.
Total Harmonic Distortion ............... Max 3½% (MIL-STD705B)
Telephone Interference Factor ............ Max 50 (NEMA MG1-22)
Deviation Factor................................. Max 5% (MIL-STD 405B)
Alternator ...................................... Self ventilating and drip-proof
Ltd. Warranty Period.................. 24 Months from start-up date or
....................................................... 1000 hours use, first to occur.
• World Renown Stamford Electric Generator having UL-1446
certification.
• Full generator protection with Deep Sea 7420 controller,
having UL-508 certification.
• Automatic voltage regulator with over-excitation, underfrequency compensation, under-speed protection, and EMI
filtering. Entire solid-state board is encapsulated for
moisture protection.
• Generator power ratings are based on temperature rise,
measured by resistance method, as defined in MIL-STD
705C and IEEE STD 115, Method 6.4.4.
• Power ratings will not exceed temperature rise limitation for
class H insulation as per NEMA MG1-22.40.
• Insulation resistance to ground, exceeds 1.5 meg-ohm.
• Stator receives 2000 V. hi-potential test on main windings,
and rotor windings receive a 1500 V. hi-potential test, as per
MIL-STD 705B.
• Full amortisseur windings with UL-1446 certification.
• Complete engine-generator torsional acceptance, confirmed
during initial prototype testing.
• Full load testing on all engine-generator sets, before shipping.
ENGINE SPECIFICATIONS AND APPLICATIONS DATA
ENGINE ___________________________________
Manufacturer ..................................................... VOLVO-PENTA
Model and Type ................. TWD1670VE, 4 cycle, liquid Cooled
Aspiration ................................... Turbo After Cooler, H2O to Air
Charged Air Cooled System........................................ H2O to Air
Cylinder Arrangement................................... 6 Cylinders, In-Line
Displacement Cu. In. (Liters) ........................................ 984 (16.1)
Bore & Stroke in (Cm) ........................... 5.67 x 6.50 (14.4 x 16.5)
Compression Ratio .............................................................. 17.0:1
Main Bearings .......................... Tin Overlay with Babbit Backing
Cylinder Head .................................Cast Iron with overhead Cam
Pistons............................Aluminum Alloy with Graphite Coating
Crankshaft ................... Induction Hardened, Heat Treated Forged
Valves ....................... Heat Treated and Hardened Exhaust Valve
Governor ....................................................... Electronic, EMS 2.2
Frequency Regulation ........................................................ ± 1/4%
Air Cleaner ......................................... Dry, Replaceable Cartridge
Engine Speed ................................................................. 1800 rpm
Max Power, bhp (kwm) Standby .................. ................ 551 (405)
BMEP: psi (MPa) Standby ............................ ................. 298 (1.9)
Ltd. Warranty Period................. 2 Year or 1000 hrs, first to occur
FUEL SYSTEM ____________________________
Type ......................................... Diesel Fuel Oil (ASTM No. 2-D)
Combustion System ............................................. Direct Injection
Fuel Injection Pump .................................... Electronic, Delphi E3
24 VDC Coolant heaters ............................... Optional Equipment
Fuel Filter ...................... ……………..Yes with Water Separator
2
FUEL CONSUMPTION
GAL/HR (LITER/HR)
STANDBY
PRIME
100% LOAD
75% LOAD
50% LOAD
25.5 (96.5)
19.3 (73.1)
13.2 (50.0)
23.1 (87.4)
17.7 (67.0)
12.3 (46.6)
OIL SYSTEM
Type ......................................................................... Full Pressure
Oil Pan Capacity qt. (L) ..................................................50.7 (48)
Oil Pan Cap. W/ filter qt. (L) ..........................................44.3 (42)
Oil Filter ......................................... 3, Replaceable Cartridge type
ELECTRICAL SYSTEM _____________________
Ignition System ............................................................. Electronic
Eng. Alternator/Starter: 24 VDC, negative ground, 110 amp/hr.
Recommended battery to -18°C (0° F): ....(2) 12 VDC, BCI# 31,
Max. Dimensions: 14”lg x 6 3/4” wi x 10” hi, with standard
round posts. Min output 1000 CCA. Battery tray (max. dim. at
15”lg x 7”wi). This model has (2) battery trays, (2) hold down
straps, (2) sets of battery cables, and (1) battery charger.
Installation of (2) 12VDC starting batteries connected in series
for 24VDC output is required, with possible higher AMP/HR
rating, as described above, if the normal environment
temperature averages -13° F (-25°C) or cooler.
CERTIFICATIONS
All engines are EPA emissions certified. All non-emergency
stationary diesel engines are Tier IV Final compliant.
Gillette Generators, Inc. • 2921 Thorne Dr. •Elkhart, IN • 46514 • Ph: 574-264-9639 • Fax: 574-262-1840 • Web: www.gillettegenerators.com • spc4-170414
APPLICATION & ENGINEERING DATA FOR MODEL T4D-3500-60 HZ
COOLING SYSTEM
Type of System ............................ Air to Air, Charged Air Cooler
Coolant Pump .....................................Pre-lubricated, self-sealing
Cooling Fan Type ...............................................................Pusher
Fan Diameter inches (cm) ............................................... 35.1 (89)
Fan drive ratio ..................................................................... 1.04:1
Ambient Capacity of Radiator °F (°C) ............................. 131 (55)
Engine Jacket Coolant Capacity gal. (L)......................... 8.70 (33)
Radiator Coolant Capacity gal. (L) ................................. 16.0 (60)
Water Pump Capacity gpm (L/min) .............. ................ 122 (462)
Heat Reject Coolant: Btu/min ....................... ................….12,682
Air to Air Heat Reject, BTU/min. ................ . ...............….11,715
Heat Radiated to Ambient, BTU/min ........... ................. ….4,253
Low Radiator Coolant Level Shutdown………………..Standard
Note: Coolant temp. shut-down switch setting at 228°F (109°C) with
50/50 (water/antifreeze) mix.
COOLING AIR REQUIREMENTS
Combustion Air cfm (m3/min) ...................... ............ 1,646 (46.6)
Max Air Intake Restrictions:
Clean Air Cleaner, KPA (psi) ................ ................... 5 (1.5)
Radiator Cooling Air, SCFM (m3/min)………….....29,894 (846)
EXHAUST SYSTEM
Exhaust Outlet Size .................................................................... 8"
Max. Back Pressure in KPA (in. H2O) .............................. 10 (40)
Exhaust Flow, at rated KW, CFM (m3/min)............... 4,347 (123)
Exhaust Temp, (Stack) °F (ºC) ..................... ................ 932 (500)
SOUND LEVELS MEASURED IN dB(A)
Open
Set
Level 2
Encl.
Level 2, Critical Silencer .........................98............ ........... 83
Level 3, Hospital Silencer ........................93............ ........... 78
Note: Open sets (no enclosure) have optional silencer system choices
due to unknown job-site applications. Level 2 enclosure has installed
critical silencer with upgrade to Level 3 hospital silencer. Sound tests
are averaged from several test points and taken at 23 ft. (7 m) from
source of noise at normal operation.
DERATE GENERATOR FOR ALTITUDE
3% per 1000 ft. (305m) above 3000 ft. (914m) from sea level
DERATE GENERATOR FOR TEMPERATURE
2% per 10°F (5.6°C) above 104°F (40°C)
DIMENSIONS AND WEIGHTS
Open
Set
Level 2
Enclosure
Length in (cm)......................... 152 (368) ..... ................ 204 (518)
Width in (cm) ........................... 72 (183) ...... ................. 72 (183)
Height in (cm) .......................... 80 (203) ...... ................. 94 (239)
3 Ø Net Weight lbs (kg) ........ 9625 (4366) ... .......... 12125 (5500)
3 Ø Ship Weight lbs (kg) ..... 10025 (4547) .. .......... 12525 (5681)
DEEP SEA 7420 DIGITAL MICROPROCESSOR CONTROLLER
Deep Sea 7420
The “7420” controller is an
auto start mains (utility)
failure module for single
gen-set applications. This
controller includes a backlit
LCD
display
which
continuously displays the
status of the engine and
generator at all times.
The “7420” controller will also monitor speed, frequency,
voltage, current, oil pressure, coolant temp., and fuel levels.
These modules have been designed to display warning and shut
down status. It also includes: (11) configurable inputs • (8)
configurable outputs • voltage monitoring • mains (utility)
failure detection • (250) event logs • configurable timers •
automatic shutdown or warning during fault detection • remote
start (on load) • engine preheat • advanced metering capability •
hour meter • text LCD displays • protected solid state outputs •
test buttons for: stop/reset • manual mode • auto mode • lamp
test • start button • power monitoring (kWh, kVAr, kVAh,
kVArh)
This controller includes expansion features including RS232,
RS484 (using MODBUS-RTU/TCP), direct USB connection
with PC, expansion optioned using DSENet for remote
annunciation and remote relay interfacing for a distance of up to
3300FT. The controller software is freely downloadable from
the internet and allows monitoring with direct USB cable, LAN,
or by internet via the built in web interface.
Further expansion is
available by
adding the optional “WebNet“ gateway
interface module. This device will allow
comprehensive monitoring of the generator
via the cloud including identification,
location, and status. Some advantages of this
module include: reduced site visits and
maintenance costs • remote fuel management
• fault analysis • asset tracking • automatic
system alerts • maximized system up-time.
Gillette Generators, Inc. • 2921 Thorne Dr. •Elkhart, IN • 46514 • Ph: 574-264-9639 • Fax: 574-262-1840 • Web: www.gillettegenerators.com • spc4-170414
3
STANDARD FEATURES FOR MODEL T4D-3500-60 HZ
STANDARD FEATURES
CONTROL PANEL:
Deep Sea 7420 digital microprocessor with
logic allows programming in the field. Controller has:
• STOP-MANUAL-AUTO modes and automatic engine
shutdowns, signaled by full text LCD indicators:
• Low oil pressure
Engine fail to start
• High engine temp
Engine over speed
Low Radiator Level
Engine under speed
Three auxiliary alarms
Over & under voltage
Battery fail alarm
Also included is tamper-proof engine hour meter
ENGINE:
Fuel filter • Full flow Oil filter • Air filter • Fuel pump •
Oil pump • Solenoid type starter motor • Hi-temp radiator •
Jacket water pump • Thermostat • Pusher fan and guard •
Exhaust manifold • Electronic Governor • 24 VDC battery
charging alternator • Flexible fuel and exhaust connectors •
Vibration isolators • Open coolant recovery system with
50/50 water to anti-freeze mixture • flexible oil & radiator
hose • Shut-down sensors for low oil pressure, high coolant
temp., low coolant level, high ambient temp.
AC GENERATOR SYSTEM:
AC generator • Shunt excited • Brushless design • Circuit
Breaker installed and wired to gen-set • Direct connection
to engine with flex disc • Class H, 180°C insulation • Self
ventilated • Drip proof construction • UL Certified
VOLTAGE REGULATOR:
1% Voltage regulation • EMI filter • Under-speed
protection • Over-excitation protection • total encapsulation
DC ELECTRICAL SYSTEM:
Battery trays • Battery cables • Battery hold down straps
3-stage battery charger with float, absorption, & bulk
automatic charge stages
WEATHER / SOUNDPROOF ALUMINUM HOUSING:
Corrosion Resistant Protection consisting of:
• (9) Heated and Agitated Wash Stages
• Zinc Phosphate Etching-Coating Stage
• Final Baked on Enamel Powder Coat
• 18/8 Stainless Steel Hardware
Design & specifications subject to
change
without
prior
notice.
Dimensions shown are approximate.
Contact Gillette for certified drawings.
DO NOT USE DIMENSIONS FOR
INSTALLATION PURPOSES.