HYBRID UPS
E11A
Hybrid UPS
E11A
Model: E11A351
商用電源
効率優先
モード
電源事情が
良いとき
Model: E11A751
Model: E11A751****TW
Model: E11A102
電源事情が
悪いとき
1 Energy
給電品質優先
モード
Saving
This UPS delivers a conversion efficiency of 95%.*
● The Hybrid type SANUPS E11A automatically selects
力率が
アクティブ
the most efficient mode of operation
for any given
悪いとき
フィルタモード
power condition.**
●
2
Automatic Battery Test
Battery self-tests can be performed automatically at
regular intervals, ensuring reliable UPS operation in
the event of a power failure.
Battery testing requires no power interruption to
loads.
●
●
* For 1 kVA model at Economy mode
** The modes of operation other than Active Filter mode can be fixed manually.
Note: Battery test interval can be set by the user.
When power conditions are stable
Start battery testing
ECONOMY
mode
Normal operation
Pure sine wave
ACTIVE FILTER
mode
When power
factor is low
Periodic
Check
Return to normal operation
DOUBLE
CONVERSION
mode
When power
conditions are faulty
3
●
Easy Maintenance
Front-access module design allows users to easily
replace battery packs even during inverter operation.
Note: For battery replacement of 0.35 kVA and UL/CE models, please consult us.
SANUPS SOFTWARE STANDALONE included as standard
A power management software is included as standard for power management from a PC.
UPS status can be checked at a glance from a PC or server.
Note: Optional network solutions are available for power management via a network.
RS-232C
SANUPS SOFTWARE
STANDALONE
Power input
Operation screen examples
Battery Cold Start Function
Batteries can start up the UPS even when commercial AC power is not available, delivering inverter output power.
2
Check battery feed
E11A
Installation examples
Mountable in an EIA standard
19-inch rack
Vertical installation
A set of vertical stands is included with 0.75
to 2 kVA models, and a set of floor mounting brackets is included with 0.35 and 3 kVA
models for vertical installation.
Rack-mounting brackets are included
as standard with 1 to 3 kVA models.
Rack support rail is optional.
Lineup:
[No. of phases/wires]
Input/Output voltage
Output capacity
(kVA)
0.35
Battery backup time
(kW) Standard
0.245 6 min
Available
options*
-
Rack
mount
type
✓
0.75
0.525 6 min
20, 30, 40, 60
min
1
100 V
model
100/110/115/120 V
-
20, 30, 40, 60
min
1.5
1.05
3
[Single-phase
2-wire]
200 V
model
200/220/230/240 V
1
2
3
1.4
2.1
0.7
1.4
2.1
-
-
✓
✓
✓
-
-
-
5 min
-
2
✓
5 min
[Single-phase
2-wire]
-
UL/CE
Terminal
certificablock I/O
tion
-
-
0.7
Tower
type
5 min
3.5 min
5 min
5 min
5 min
20, 30, 40, 60
min
15, 30, 45 min
20, 30, 40, 60
min
20, 30, 40, 60
min
20, 30, 40, 60
min
-
✓
✓
✓
✓
✓
✓
✓
✓
-
-
-
-
-
-
-
-
✓
-
-
-
✓
Page
Model no.
Specifi- Dimencations sions
✓
E11A351B001UJ
p. 6
p. 10
✓
E11A351B021UJ
p. 6
p. 10
✓
E11A751B001UJ
p. 6
p. 10
✓
E11A751B011UJ
p. 6
p. 10
✓
E11A751B021UJ
p. 6
p. 10
✓
E11A751B001TWUJ
p. 6
p. 10
✓
E11A751B011TWUJ
p. 6
p. 10
✓
E11A751B021TWUJ
p. 6
p. 10
✓
E11A102B001UJ
p. 7
p. 10
✓
E11A102B011UJ
p. 7
p. 10
✓
E11A102B001TWUJ
p. 7
p. 10
✓
E11A102B011TWUJ
p. 7
p. 10
✓
E11A102B021TWUJ
p. 7
p. 10
-
E11A152B001
p. 7
p. 10
-
E11A152B011
p. 7
p. 10
✓
E11A152B001UJ
p. 7
p. 10
✓
E11A152B011UJ
p. 7
p. 10
-
E11A152B001TW
p. 8
p. 10
-
E11A152B011TW
p. 8
p. 10
-
E11A152B021TW
p. 8
p. 10
✓
E11A152B001TWUJ
p. 8
p. 10
✓
E11A152B011TWUJ
p. 8
p. 10
✓
E11A152B021TWUJ
p. 8
p. 10
-
E11A202B001
p. 8
p. 10
-
E11A202B011
p. 8
p. 10
✓
E11A202B001UJ
p. 8
p. 10
✓
E11A202B011UJ
p. 8
p. 10
-
E11A302B001
p. 8
p. 10
-
E11A302B011
p. 8
p. 10
✓
E11A302B001UJ
p. 8
p. 10
✓
E11A302B011UJ
p. 8
p. 10
✓
E11A102B002UJ
p. 9
p. 10
✓
E11A102B012UJ
p. 9
p. 10
✓
E11A202B002UJ
p. 9
p. 10
✓
E11A202B012UJ
p. 9
p. 10
E11A202B012T
p. 9
p. 10
✓
E11A302B002UJ
p. 9
p. 10
✓
E11A302B012UJ
p. 9
p. 10
E11A302B012T
p. 9
p. 10
-
-
* For 1 to 3 kVA models other than the tower type, the UPS backup time can be extended by combining optional external battery modules.
3
E11A
Hybrid UPS Views and Part Names
0.35 kVA, Front View
0.35 kVA, Back View
Inverter ON/STANDBY Button
Load Level LED
Battery Test Button
Main Power Switch
PC Port
Bypass Breaker
Clear Button
Alarm LED
Operation Mode LED
Output LED
External Signal Port
Input Power LED
0.75 to 3 kVA, Front View
Output Outlet
(only for E11A351B021UJ)
Low Battery Voltage LED
0.75 kVA, Back View
PC Port
Power Input
Cable (1.8 m)
Model: E11A751B011
Bypass Breaker
Auxiliary Port
Optional Card Slot
Output Outlet
Alarm LED
Inverter ON/STANDBY Button
Load Level LED
Battery Test Button
Optional Card Interface Remote Port
1 to 3 kVA, Back View
PC Port
Main Power Switch
Power Input
Cable (1.8 m)
Bypass Breaker
Model: E11A102B011
Optional Card Slot
Auxiliary Port
Power Input
Main Power
Cable (1.8 m)
Switch
Output Outlet
Clear Button
Operation Mode LED
Output LED
External Battery
Connector
Optional Card Interface
Input Power LED
External Battery
Connector
Bypass Breaker
Remote Port
Low Battery Voltage LED
Main Power Switch
Model: E11A202B012T
Tower Type, Front View
Tower Type, Back View
Low Battery Voltage LED
Remote Port
Inverter ON/STANDBY Button
Battery Test Button
Auxiliary Port
I/O Terminal Block
Model: E11A751B011TW
Optional Card
Interface
PC Port
Main Power Switch
Clear Button
Alarm LED
Load Level LED
Operation Mode LED
Output LED
Input Power LED
Output Outlet
Optional Card Slot
Bypass Breaker
Power Input Cable (1.8 m)
Note: Above photos are of typical models. Interface specifications may vary by model.
4
E11A
Common Specifications
Operation mode(1)
Economy mode
Technology
Topology
Hybrid
Cooling method
Forced air cooling
AC input
AC output
Double Conversion mode
Remarks
Within rated voltage ±5%
Within rated voltage -20% to +15%
Number of phases/wires
Single-phase 2-wire
Voltage range
Within rated voltage ±8%
(±5% at auto-detection setting)
Frequency
50/60 Hz
Frequency range
Within rated frequency ±1, 3, or 5% (user settable)
Within rated frequency ±8%
Input power factor
Same as the load power factor
0.95 or greater
When the distortion factor of the input
voltage is less than 1%.
Number of phases/wires
Single-phase 2-wire
Within rated voltage ±2%
Depends on input voltage and load
conditions
At auto-detection setting
0.85 or greater
Rated load power factor
0.7 (lagging)
Voltage regulation
Within rated voltage -10% to +8% (-7% to +5% Within rated voltage -7% to +5%
at auto-detection setting)
Rated frequency
Frequency
regulation
Battery
Active Filter mode
Variation range: 0.7 (lagging) to 1.0
50/60 Hz
Same as the input frequency
At normal operation Within rated frequency ±1, 3, or 5% (user settable)
(utility-synchronous)
Within rated frequency ±1%
At battery power ―
operation
Within rated frequency ±0.5%
Transient voltage Abrupt input
regulation
voltage change
Abrupt load
change
―
―
Within rated voltage ±5%
Loss or return of input power / Abrupt
input voltage change
For 0 ⇔100% load step changes
Overload capability
200% (30 s)
105% (200 ms)
At rated load power factor and rated input
800% (2 cycles)
―
Within rated voltage ±5%
Type
Small-sized valve-regulated lead-acid (VRLA) battery
Expected life
Approx. 5 years
At 25℃ ambient temperature, under initial
battery conditions
Operating environment
Temperature: 0 to 40°C; Humidity: 20 to 90% RH (non-condensing)
Safety standard
UL 1778 5th edition (E226092), CSA C22.2 No. 107.3-14 (3rd edition), CE marking (EN 62040-1:2008/A1:2013)
EMC standard Emission (noise)
0.35 to 1 kVA: EN 62040-2 C2:2006, 2 to 3 kVA: EN 62040-2 C3:2006, EN 55022:2006 Class A (FCC Part 15 Subpart B Class A, CISPR 22
Class A, VCCI Class A)
Immunity
(1)
(2)
200 V models are compliant with VCCI
EN 62040-2:2006, EN 55024:2010
A
momentary power interruption lasting less than 5 ms occurs when switching to battery operation from Economy mode or Active Filter mode. Please fix the operation mode to Double Conversion mode for applications that require uninterrupted transfers.
Maximum capacity in fully charged battery state
Load Level vs Backup Time
Load level (%)
100
80
1 kVA model
(5-minute standard backup)
1.5 kVA model
(5-minute standard backup)
60
40
Load level (%)
100
80
2 kVA model
(5-minute standard backup)
3 kVA, 100 V model
(5-minute standard backup)
0.75 kVA model
(6-minute standard backup)
60
3 kVA, 200 V model
(3.5-minute standard backup)
0.35 kVA model
(6-minute standard backup)
40
20
20
10
10
0
20
40
60
80
100
120
Backup time (min)
0
20
40
60
80
100
120
Backup time (min)
Note: Reference values at 25°C ambient temperature and a load power factor of 0.7, under new, fully charged battery conditions.
Network Options
Item
LAN interface card
Dry contact interface card
SANUPS SOFTWARE
Remote switch
Linked Operation cable
Model
IPv6 model
PRLANIF011B
Environment monitoring, IPv6 model
PRLANIF013B
Terminal block output
D-sub connector
Windows version, IPv6 model
PRCONIF001
PRCONIF003
PMS50□00(2)
Multi-OS version(1), IPv6 model
PMS51□00(2)
RSW011 (cable length: 10 m)
RSW013 (cable length: 2 m)
P10197 (1 m); P10198 (3 m)
Description
This card enables 24/7 monitoring of UPS operations and status, and e-mail notifications to system administrators via network
in the event of a power failure.
Combined with our temperature sensor (PRLANSN001) and humidity sensor (PRLANSN002), this model enables you to monitor
UPS ambient temperature and humidity.
This card outputs no-voltage signals to notify UPS status.
A and B contacts can be selected for each signal.
This is a UPS power management software via network from the installed computer.
-10
For updated OS support information, please refer to our website.
-50
For bulk purchase of software licenses, append appropriate -suffix to model number.
-100
(10 licenses)
(50 licenses)
(100 licenses)
This switch remotely turns on/off outlets of the UPS via wired connection. It is capable of managing the switching of up to 5
UPS units in Linked Operation (An optional Linked Operation cable is needed)
A unit-to-unit cable for performing on/off switching of multiple UPS units.
Supports Windows, Unix, and Linux.
The □’s denote revision characters.
Note: Optional products have different operating temperature ranges from the UPS.
(1)
(2)
5
E11A
Hybrid UPS Specifications
100 V model 0.35 kVA capacity
E11A351B001UJ
Model no.
Rated power capacity (Apparent power / Active power)
0.35 kVA / 0.245 kW (Watts value at a load power factor of 0.7)
AC input
Rated voltage
100/110/115/120 V (User settable. Factory setting: 100 V)
Input plug
NEMA 5-15P
Rated voltage
100/110/115/120 V (User settable. Factory setting: 100 V)
AC output
E11A 102 B 00 1 TW UJ
UJ … UL listed model
TW … Tower type
Breaker protection
Overcurrent protection(1)
Voltage harmonic
distortion(2)
Model Numbering System
E11A351B021UJ
At linear load
3%
At rectifier load
8% (at 100% rectifier load)
T … Terminal block input/
output
Voltage Specification
Output receptacle
NEMA 5-15R (× 4)
Battery
Backup time
6 min (at 25°C ambient temperature and rated output, under initial battery
conditions)
Interface
PC port
RS-232C
Remote port(3)
―
―
―
―
Optional card
Dry contact(5)
―
―(4)
interface
LAN card
―
―
―
―
UL/CE certification
✓
✓
Acoustic noise
40 dB or less (1 m from front of UPS, A-weighted)
Heat dissipation(2)
59 W
Auxiliary port (EPO)
(6)
Output Line Control contact
1 … 100 V model
2 … 200 V model
Interface Specification
00 … Standard
01 … Type C (Enhanced functions)
02 … External signal control capability
(Transistor output)
Revision Character
UPS Output Capacity
351 … 0.35 kVA
Compatible options
Outlet box(7)
―
751 … 0.75 kVA
Rack support rail(8)
―
102 … 1 kVA
Floor mounting brackets(9)
―
152 … 1.5 kVA
Air filter(10)
FL003
202 … 2 kVA
302 … 3 kVA
Replacement battery pack
―
For internal battery
100 V model 0.75 kVA capacity
Model no.
E11A751B001UJ
Rated power capacity (Apparent power / Active power)
0.75 kVA / 0.525 kW (Watts value at a load power factor of 0.7)
AC input
100/110/115/120 V (User settable. Factory setting: 100 V)
AC output
Rated voltage
E11A751B011UJ
Input plug
NEMA 5-15P
Rated voltage
100/110/115/120 V (User settable. Factory setting: 100 V)
Overcurrent protection(1)
Voltage harmonic
distortion(2)
E11A751B021UJ
E11A751B001TWUJ
E11A751B011TWUJ
E11A751B021TWUJ
Breaker protection
At linear load
3%
At rectifier load
8% (at 100% rectifier load)
Output receptacle
NEMA 5-15R (× 4)
Battery
Backup time
6 min (at 25°C ambient temperature and rated output, under initial battery conditions)
Interface
PC port
RS-232C
Remote port(3)
―
✓
―
―
✓
―
Auxiliary port (EPO)
―
✓
―
―
✓
―
Dry contact(5)
―
✓
✓
―
✓
✓
LAN card(6)
✓
✓
✓
✓
✓
✓
―
✓
―
―
✓
―
UL/CE certification
✓
✓
✓
✓
✓
✓
Acoustic noise
40 dB or less (1 m from front of UPS, A-weighted)
Heat dissipation(2)
111 W
―
―
P10037
―
Optional card
interface
Output Line Control contact
Compatible options
Outlet box(7)
―
Rack support rail(8)
RME11A751A00
―
Floor mounting brackets(9)
FMA11F00
FME11AA03
Air filter(10)
FL002
FL004
BPE11A751A00
BPE11A751A01
P10037
Replacement battery pack
For internal battery
t Double Conversion mode, the UPS transfers to bypass operation with no interruption (auto-return). This auto-return setting can be disabled.
A
(2)
Value at Double Conversion mode, rated output, after battery charging completed
(3)
Remote ON/OFF switch (management of the switching of up to 5 UPS units is possible in Linked Operation)
(4)
Transistor output available
(5)
If using as a no-voltage contact output, an optional dry contact interface card is required.
(6)
Optional LAN interface card is required.
(7)
Enables Output Line Control, the coordinated on/off management of UPS outlets. Output 0: constant output; output 1 and 2: controlled output.
(8)
Used for mounting the UPS on a standard 19-inch rack.
(9)
Brackets for mounting the UPS to the floor.
(10)
Front side air intake filter to prevent dust ingress.
(1)
6
E11A
Specifications
100 V model 1 kVA capacity
Model no.
E11A102B001UJ
Rated power capacity (Apparent power / Active power)
1 kVA / 0.7 kW (Watts value at a load power factor of 0.7)
AC input
100/110/115/120 V (User settable. Factory setting: 100 V)
AC output
Rated voltage
E11A102B011UJ
Input plug
NEMA 5-15P
Rated voltage
100/110/115/120 V (User settable. Factory setting: 100 V)
E11A102B011TWUJ
E11A102B021TWUJ
Breaker protection
Overcurrent protection(1)
Voltage harmonic
distortion(2)
E11A102B001TWUJ
At linear load
3%
At rectifier load
7% (at 100% rectifier load)
Output receptacle
NEMA 5-15R (× 6)
Battery
Backup time
5 min (at 25°C ambient temperature and rated output, under initial battery conditions)
NEMA 5-15R (× 4)
Interface
PC port
RS-232C
Remote port(3)
―
✓
―
✓
―
Auxiliary port (EPO)
―
✓
―
✓
―
Optional card
Dry contact(5)
―
✓
―
✓
✓
interface
LAN card(6)
✓
✓
✓
✓
✓
―
✓
―
✓
―
UL/CE certification
✓
✓
✓
✓
✓
Acoustic noise
40 dB or less (1 m from front of UPS, A-weighted)
Heat dissipation(2)
125 W
―
P10037
―
Output Line Control contact
Compatible options
Outlet box(7)
―
Rack support rail(8)
RM030
―
Floor mounting brackets(9)
FMA11F00
FME11AA04
Air filter(10)
FL001
FL004
BPE11A102A00
BPE11A102A02
P10037
Replacement battery pack
For internal battery
Tower type in the next page
100 V model 1.5 kVA capacity
Model no.
E11A152B001
Rated power capacity (Apparent power / Active power)
1.5 kVA / 1.05 kW (Watts value at a load power factor of 0.7)
AC input
Rated voltage
100/110/115/120 V (User settable. Factory setting: 100 V)
Input plug
NEMA 5-15P
Rated voltage
100/110/115/120 V (User settable. Factory setting: 100 V)
AC output
E11A152B001UJ
E11A152B011UJ
NEMA 5-20P
Breaker protection
Overcurrent protection(1)
Voltage harmonic
distortion(2)
E11A152B011
At linear load
3%
At rectifier load
7% (at 100% rectifier load)
Output receptacle
NEMA 5-15R (× 6)
Battery
Backup time
5 min (at 25°C ambient temperature and rated output, under initial battery conditions)
Interface
PC port
RS-232C
Remote port(3)
―
✓
―
✓
Auxiliary port (EPO)
―
✓
―
✓
Dry contact(5)
―
✓
―
✓
LAN card(6)
✓
✓
✓
✓
―
✓
―
✓
UL/CE certification
―
―
✓
✓
Acoustic noise
40 dB or less (1 m from front of UPS, A-weighted)
Heat dissipation(2)
200 W
―
P10037
Optional card
interface
Output Line Control contact
NEMA 5-20R (× 4)
Compatible options
Outlet box(7)
―
Rack support rail(8)
RM030
Floor mounting brackets(9)
FMA11F00
Air filter(10)
FL001
P10037
Replacement battery pack
For internal battery
BPE11A152A00
■ Input plug shape
NEMA 5-15P
NEMA 5-20P
NEMA L5-30P
NEMA L6-20P
NEMA L5-30R
IEC 60320-C13
■ Output receptacle shape
NEMA 5-15R
NEMA 5-20R
IEC 60320-C19
7
E11A
Hybrid UPS Specifications
100 V model 1.5 kVA capacity
Model no.
E11A152B001TW
Rated power capacity (Apparent power / Active power)
1.5 kVA / 1.05 kW (Watts value at a load power factor of 0.7)
AC input
100/110/115/120 V (User settable. Factory setting: 100 V)
AC output
Rated voltage
Input plug
NEMA 5-15P
Rated voltage
100/110/115/120 V (User settable. Factory setting: 100 V)
Overcurrent protection(1)
Voltage harmonic
distortion(2)
Battery
Interface
E11A152B011TW
E11A152B021TW
E11A152B001TWUJ
E11A152B011TWUJ
E11A152B021TWUJ
NEMA 5-20P
Breaker protection
At linear load
3%
At rectifier load
7% (at 100% rectifier load)
Output receptacle
NEMA 5-15R (× 4)
Backup time
5 min (at 25°C ambient temperature and rated output, under initial battery conditions)
NEMA 5-20R (× 4)
PC port
RS-232C
Remote port(3)
―
✓
―
―
✓
―
Auxiliary port (EPO)
―
✓
―
―
✓
―
Optional card
Dry contact(5)
―
✓
✓
―
✓
✓
interface
LAN card(6)
✓
✓
✓
✓
✓
✓
―
✓
―
―
✓
―
UL/CE certification
―
―
―
✓
✓
✓
Acoustic noise
40 dB or less (1 m from front of UPS, A-weighted)
Heat dissipation(2)
200 W
―
―
P10037
―
Output Line Control contact
Compatible options
Outlet box(7)
―
Rack support rail(8)
―
Floor mounting brackets(9)
FME11AA05
Air filter(10)
FL004
P10037
Replacement battery pack
For internal battery
BPE11A152A02
100 V model 2 kVA capacity
100 V model 3 kVA capacity
Model no.
E11A202B001
Rated power capacity (Apparent power / Active power)
2 kVA / 1.4 kW (Watts value at a load power factor of 0.7)
AC input
100/110/115/120 V (User settable. Factory setting: 100 V)
AC output
Rated voltage
NEMA L5-30P
Rated voltage
100/110/115/120 V (User settable. Factory setting: 100 V)
Voltage harmonic
distortion(2)
Interface
E11A202B001UJ
Input plug
Overcurrent protection(1)
Battery
E11A202B011
E11A202B011UJ
E11A302B001
E11A302B011
E11A302B001UJ
E11A302B011UJ
3 kVA / 2.1 kW(11) (Watts value at power factor of 0.7)
Breaker protection
At linear load
3%
At rectifier load
7% (at 100% rectifier load)
Output receptacle
NEMA L5-20R (× 1), NEMA 5-15R (× 3)
Backup time
5 min (at 25°C ambient temperature and rated output, under initial battery conditions) 3.5 min (at 25°C ambient temperature and rated output, under initial battery
conditions)
NEMA L5-30R (× 1)
NEMA L5-30R (× 1)
PC port
RS-232C
Remote port(3)
―
✓
―
✓
―
✓
―
✓
Auxiliary port (EPO)
―
✓
―
✓
―
✓
―
✓
Dry contact(5)
―
✓
―
✓
―
✓
―
✓
LAN card(6)
✓
✓
✓
✓
✓
✓
✓
✓
―
✓
―
✓
―
✓
―
✓
UL/CE certification
―
―
✓
✓
―
―
✓
✓
Acoustic noise
45 dB or less (1 m from front of UPS, A-weighted)
45 dB or less (1 m from front of UPS, A-weighted)
Heat dissipation(2)
250 W
460 W
Optional card
interface
Output Line Control contact
Compatible options
Outlet box(7)
―
Rack support rail(8)
RM030
Floor mounting brackets(9)
FMA11F00
Air filter(10)
FL001
P10040
―
P10040
P10030
Standardly included (FMA11F00)
Replacement battery pack
For internal battery
BPE11A202A00
A
t Double Conversion mode, the UPS transfers to bypass operation with no interruption (auto-return). This auto-return setting can be
disabled.
(2)
Value at rated output, Double Conversion mode, after battery charging completed
(3)
Remote ON/OFF switch (management of the switching of up to 5 UPS units is possible in Linked Operation)
(4)
Transistor output available
(5)
If using as a no-voltage contact output, an optional dry contact interface card is required.
(6)
Optional LAN interface card is required.
(1)
BPE11A302A00-1
E nables Output Line Control, the coordinated on/off management of UPS outlets. Output 0: constant output; output 1 and 2: controlled output.
(8)
Used for mounting the UPS on a standard 19-inch rack.
(9)
Brackets for mounting the UPS to the floor.
(10)
Front side air intake filter to prevent dust ingress.
(11)
Output values for UL/CE models: Output voltage
(7)
setting
100 V
110 V
115 V
120 V
8
Output capacity
2.5 kVA / 1.75 kW
2.75 kVA / 1.925 kW
2.875 kVA / 2.013 kW
3 kVA / 2.1 kW
E11A
Specifications
200 V model 1 kVA capacity
200 V model 2 kVA capacity
Model no.
E11A102B002UJ
Rated power capacity (Apparent power / Active power)
1 kVA / 0.7 kW (Watts value at a load power factor of 0.7) 2 kVA / 1.4 kW (Watts value at a load power factor of 0.7)
AC input
Rated voltage
200/220/230/240 V (Selectable. Factory setting: 200 V)
Input plug
NEMA L6-20P
Rated voltage
200/220/230/240 V (Selectable. Factory setting: 200 V)
AC output
Battery
Interface
E11A202B002UJ
E11A202B012UJ
E11A202B012T
Terminal block
Breaker protection
Overcurrent protection(1)
Voltage harmonic
distortion(2)
E11A102B012UJ
At linear load
3%
At rectifier load
7% (at 100% rectifier load)
Output receptacle
IEC 60320-C13 (× 4)
Backup time
5 min (at 25°C ambient temperature and rated output, under initial battery conditions)
IEC 60320-C19 (× 3)
Terminal block
PC port
RS-232C
Remote port(3)
―
✓
―
✓
✓
Auxiliary port (EPO)
―
✓
―
✓
✓
Optional card
Dry contact(5)
―
✓
―
✓
✓
interface
LAN card(6)
✓
✓
✓
✓
✓
―
✓
―
✓
✓
UL/CE certification
✓
✓
✓
✓
―
Acoustic noise
40 dB or less (1 m from front of UPS, A-weighted)
45 dB or less (1 m from front of UPS, A-weighted)
Heat dissipation(2)
125 W
270 W
Output Line Control contact
Compatible options
Outlet box(7)
―
Rack support rail(8)
RM030
Floor mounting brackets(9)
FMA11F00
Air filter(10)
FL001
Replacement battery pack
For internal battery
BPE11A102A00
BPE11A202A00
200 V model 3 kVA capacity
Model no.
E11A302B002UJ
Rated power capacity (Apparent power / Active power)
3 kVA / 2.1 kW (Watts value at a load power factor of 0.7)
AC input
Rated voltage
200/220/230/240 V (Selectable. Factory setting: 200 V)
Input plug
NEMA L6-20P
Rated voltage
200/220/230/240 V (Selectable. Factory setting: 200 V)
AC output
Battery
Interface
E11A302B012T
Terminal block
Breaker protection
Overcurrent protection(1)
Voltage harmonic
distortion(2)
E11A302B012UJ
At linear load
3%
At rectifier load
7% (at 100% rectifier load)
Output receptacle
IEC 60320-C19 (× 3)
Backup time
5 min (at 25°C ambient temperature and rated output, under initial battery
conditions)
Terminal block
PC port
RS-232C
Remote port(3)
―
✓
✓
Auxiliary port (EPO)
―
✓
✓
Dry contact(5)
―
✓
✓
LAN card(6)
✓
✓
✓
―
✓
✓
UL/CE certification
✓
✓
―
Acoustic noise
45 dB or less (1 m from front of UPS, A-weighted)
Heat dissipation(2)
460 W
Optional card
interface
Output Line Control contact
Compatible options
Outlet box(7)
―
Rack support rail(8)
RM030
Floor mounting brackets(9)
Standardly included (FMA11F00)
Air filter(10)
FL001
Replacement battery pack
For internal battery
BPE11A302A00-2
■ Input plug shape
NEMA 5-15P
NEMA 5-20P
NEMA L5-30P
NEMA L6-20P
NEMA L5-30R
IEC 60320-C13
■ Output receptacle shape
NEMA 5-15R
NEMA 5-20R
IEC 60320-C19
9
E11A
Hybrid UPS UPS Dimensions (Unit: mm)
0.35 kVA capacity models
0.75 kVA capacity models
Mass: 8 kg
Mass: 13.5 kg
350
86
69
408
365
250
1 to 3 kVA capacity models
H
D
W
UPS output capacity
W
D
H
Mass
1 kVA
440
408
86
17 kg
1.5 kVA
500
22 kg
2 kVA
565
29 kg
3 kVA (100 V model)
660
37 kg
3 kVA (200 V model)
750
39 kg
0.75 to 1.5 kVA capacity models, tower type
D
H
W
UPS output capacity
W
D
H
Mass
0.75 kVA
150
350
250
14 kg
1 kVA
395
17 kg
1.5 kVA
450
22 kg
Paint color: Black (Munsell N1.5)
Included Items with UPS
Item
Description
Instruction Manual
User Settings Guide
For models with model nos. ending with 'UJ', both Japanese
and English versions will be included. For other models, only
Manual and Guide in Japanese will be included.
Power Management Software CD-ROM
SANUPS SOFTWARE STANDALONE Communication cable
RS-232C (3 m)
Rack mounting brackets
1 pair (left and right)
Screws for rack mounting bracket
M4 X 6 mm
Vertical stands / Floor mounting brackets
For vertical installation
Screws for stands
M4 X 8 mm
Note: Rack mounting brackets and vertical stands are not supplied with tower type UPSs.
10
E11A
Optional External Battery Module
Compatible UPS capacity
Model no.
Backup time
Battery replacement method
15 min
20 min
―
―
1.5 kVA
―
2 kVA
BCE11A302A03US
3 kVA (100 V model)
BCE11A302A01US
3 kVA (200 V model)
―
BCE11A102A01US
1 kVA
BCE11A102A02US
BCE11A152A01US
BCE11A152A02US
BCE11A202A01US
BCE11A202A02US
30 min
40 min
45 min
60 min
1 unit
―
2 units
―
3 units
―
1 unit
―
―
2 units
The battery module has to be replaced.
1 unit
―
2 units
―
3 units
Battery packs are front replaceable.
―
―
1 unit
―
―
2 units
The battery module has to be replaced.
―
1 unit
―
2 units
―
3 units
Battery packs are front replaceable.
―
―
1 unit
―
―
2 units
The battery module has to be replaced.
1 unit
―
2 units
―
3 units
―
Battery packs are front replaceable.
1 unit
―
2 units
―
3 units
Battery packs are front replaceable.
Battery packs are front replaceable.
External battery module is not available for tower type UPSs.
Note: For battery replacement of UL/CE models, please consult us.
Dimensions (Unit: mm)
Model no.
W
Dimensions
W
D
BCE11A102A01US
440
Mass
D
H
408
86
20 kg
BCE11A102A02US
508
29 kg
BCE11A152A01US
500
26 kg
BCE11A152A02US
600
38 kg
BCE11A202A01US
565
34 kg
BCE11A202A02US
630
47 kg
BCE11A302A03US
660
50 kg
BCE11A302A01US
750
52 kg
H
Paint color: Black (Munsell N1.5)
Dimensions of Options (Unit: mm)
■ Rack support rails Used for mounting the UPS on a standard 19-inch rack. (A pair of left and right rails. Shown below is the left rail.)
RM030 (2U)
RME11A751A00 (2U, for 0.75 kVA models)
Depth adjustment range (485 to 915)
30
440
88.8
88
Front
12.2
48
555 to 913
58
88
Rack mounting depth
Rack mounting brackets are included with the UPS.
Rack mounting brackets are included with the support rails.
■ Floor mounting brackets Used for securing the UPS to the floor.
For tower type
60
W
A±1
140
120
A
8
B
4-φ10
D
H
4-φ10
Model no.
FMA11F00
Compatible UPS
capacity
A
Model no.
Compatible UPS
capacity
W
D
H
A
B
220
306.1
14
200
150
0.75 kVA
320
FME11AA03
0.75 kVA
1 kVA
320
FME11AA04
1 kVA
351.1
200
1.5 kVA
412
FME11AA05
1.5 kVA
406.1
250
2 kVA
477
11
Eco Products
Sanyo Denki’s ECO PRODUCTS are designed with the concept of lessening impact on the environment in the process from product development to waste. The
product units and packaging materials are designed for reduced environmental impact. We have established our own assessment criteria on the environmental
impacts applicable to all processes, ranging from design to manufacture. Those products that satisfy the criteria are accredited as ECO PRODUCTS.
Notes before Purchase
Before installing, assembling, and using the product, please read
Instruction Manual carefully and use it properly.
For use in an environment where vibration is present, such as in a car or
a ship, please consult us in advance.
When using this product in the following applications, consult us in
advance because special considerations are required for operation,
maintenance, and management.
Never attempt to disassemble or alter the product in any way.
(a) Medical equipment that may have direct effects on human life or
human body.
Products listed in this catalog may be regulated by export laws and
regulations in each country. When exporting these products, compliance
with each country's respective export laws and regulations is highly
recommended.
(b) Trains, elevators, and other machinery that can cause injury.
(c) Socially and publicly important computer systems.
(d) Other equipment that is related to safety of human life and that can
have major impact on maintenance of public functions.
For installation and maintenance work of the product, please consult us
or properly licensed personnel.
SANYO DENKI will not be liable for any direct or indirect damages or
loss, including but not limited to equipment downtime, missed power
sales revenue, business interruptions, increased power purchases,
resulting from the use of or inability to use our products or services.
Note: For any inquiry or consultation, please contact our sales department.
https://www.sanyodenki.com
3-33-1 Minami-Otsuka, Toshima-ku, Tokyo 170-8451, Japan
P.A. Paris Nord Ⅱ, 48 Allée des Erables-VILLEPINTE, BP.57286, F-95958 ROISSY CDG Cedex, France
468 Amapola Avenue Torrance, CA 90501, U.S.A.
Room 2106-2110, Bldg A, Far East International Plaza, No.319, Xianxia Road, Shanghai, 200051, China
Beijing Branch
Room1222, Tower B, Beijing COFCO Plaza, No.8 Jianguomennei Dajie, Dong Cheng District, Beijing 100005 China
Room 2305, 23/F, South Tower, Concordia Plaza, 1 Science Museum Road, TST East, Kowloon, Hong Kong
N-711, 7F, Chia Hsin 2nd Bldg., No.96, Sec.2, Zhongshan N. Rd., Taipei 10449, Taiwan
988 Toa Payoh North, #04-08, Singapore 319002
Indonesia Representative Office
Summitmas II 4th Floor, Jl. Jend. Sudirman Kav.61-62, Jakarta 12190, Indonesia
Frankfurter Strasse 80-82, 65760 Eschborn, Germany
15F, KDB Building, 372, Hangang-daero, Yongsan-gu, Seoul, 04323, Korea
Busan Branch
8F, CJ Korea Express Bldg., 119, Daegyo-ro, Jung-gu, Busan, 48943, Korea
2F 02-11, Shenzhen International Chamber of Commerce Tower, No.168 Fuhua 3 Road, Futian District, Shenzhen, 518048 China
Tianjin Branch
Room AB 16th Floor TEDA Building, No. 256 Jie Fang Nan Road, Hexi District, Tianjin 300042 China
Chengdu Branch
Room2105B, Block A, Times Plaza, 2 Zongfu Road, Jinjiang District, Chengdu, 610016 China
388 Exchange Tower, 25th Floor, Unit 2501-1, Sukhumvit Road, Klongtoey, Klongtoey, Bangkok 10110 Thailand
#14 (Old No.6/3), Avenue Road, Nungambakkam, Chennai - 600034, Tamil Nadu, India
TEL: +81 3 5927 1020
TEL: +33 1 48 63 26 61
TEL: +1 310 783 5400
TEL: +86 21 6235 1107
TEL: +86 10 6522 2160
TEL: +852 2312 6250
TEL: +886 2 2511 3938
TEL: +65 6223 1071
TEL: + 62 21 252 3202
TEL: +49 6196 76113 0
TEL: +82 2 773 5623
TEL: +82 51 796 5151
TEL: +86 755 3337 3868
TEL: +86 22 2320 1186
TEL: +86 28 8661 6901
TEL: +66 2261 8670
TEL: +91 44 420 384 72
The names of companies and/or their products specified in this catalog are the trade names, and/or trademarks and/or registered trademarks of such respective companies.
Specifications are subject to change without notice.
CATALOG No. P0978B006 ’18.3