Intrinsically Safe Call Point Range
IS MCP 3 NO/NC Contact Model
(Red Versions)
> Product Benefits
•
Unique ‘Plug & Play’ installation concept
•
Total ‘Flex-Ability’ in the choice of operating
element
•
Anti-Tamper facility
•
Enhanced aesthetics
•
Fully approved to the latest standards
•
Backward compatibility
166b/43
Product Overview
An Intrinsically Safe version of our MCP3A indoor call point is available for installation in
hazardous areas. These call points are manufactured to protect against other hazards, as
defined in paragraph 1.2.7 of annex II of the ATEX Directive 94/9/EC. They are intended
for use within Intrinsically Safe (I.S.) systems using suitable I.S. barriers. For a list of
suitable barriers see reverse.
Installation efficiency, flexibility and full compliance with the latest standards are at the
heart of the new Indoor Call Point range.
Installation time and ultimately cost, are of paramount importance to any fire or security
installer. The MCP range directly reflects this need by providing a unique ‘plug and play’
concept designed specifically to reduce installation time. All new MCP products utilise
a special terminal block, where all initial installation cabling is terminated. This terminal
block is then simply connected to the back of the MCP. Simple, but effective with no
re-termination required and no time wasted.
Through new standards and legislation, both break glass and resettable operating
elements can now be used within a manual call point. To provide you with the greatest
‘flex-ability’, the new MCP range can be configured as either a break glass or resettable
unit by simply changing from one element to another. No other additional parts or
alternative products need to be ordered.
All MCP Indoor Call Point products also help preserve the integrity of the overall system
as illegal removal of the product lid will result in the call point operating and the system
going in to alarm.
The MCP3A product version is supplied with one normally open and one normally closed
contact. Selecting either the “Normally Open” or “Normally Closed” contact is easily
achieved by simply connecting the terminal block to the required connection in the back of
the MCP3 Product. Single pole changeover switching can be achieved with the use of two
terminal blocks.
IS-MCP3
Rev. No 4
Electrical Specification
Figure .1
Connection Details:
See Figure .1
Cable Termination:
0.5-2.5mm2
Maximum Voltage:
30VDC
Maximum current:
500mA
Maximum Power:
1W
Certification Details: IS-MCP3A-X
1
5
3
7
1
2
3,4,5,6
Suitable IS Barriers:
Pepperl & Fuchs - KFDO-Cs-Ex 1.51P (BAS98ATEX7343), KFDO-Cs-Ex 2.51P (BAS98ATEX7343)
MTL - MTL4061 (BAS01ATEX7176), MTL5061 (BAS01ATEX7160)
A certified shunt zener barrier may be used having the following output parameters;
Uz - 28V, Imax - 93.3mA, Wmax - 0.67W
Environmental Specification
Humidity:
93± 3% non-condensing
Ambient Temperature Range: -100C to + 550C
Ingress Protection (IP) Rating: IP24D
For RoHS, WEEE & REACH information please see www.kac.co.uk
Mechanical Specification
27.5mm 32mm
87mm
60mm
Ordering Information
Model
Electrical Configuration
Mounting
Operating Markings
Element
MCP3A-R000FG-K013-01IS
N\O & N\C contacts 30VDC
Flush
Glass
EN54-11
MCP3A-R000FF-K013-01IS
N\O & N\C contacts 30VDC
Flush
Flexi
EN54-11
MCP3A-R000SG-K013-01IS
N\O & N\C contacts 30VDC
Surface
Glass
EN54-11
MCP3A-R000SF-K013-01IS
N\O & N\C contacts 30VDC
Surface
Flexi
EN54-11
N\O = Normally Open Contact
Accessories
CodeDescription
SC070 Pack Of Ten Test Keys
KG1 x 5 Pack Of Five Glass Elements (Also available in packs of 10, 25 & 50)
PS210 Flexible Operating Element
PS200 Plain Hinged Cover
SC071 Pack Of Twenty Terminal Blocks
> KAC Alarm Company Ltd
KAC House, Thornhill Road,
North Moons Moat, Redditch,
B98 9ND, United Kingdom
Tel: +44 (0) 1527 406655
Fax: +44 (0) 1527 406677
e-mail: marketing@kac.co.uk
We reserve the right to amend the content of this document without prior notice.
87mm
89mm
93mm
Material:PC/ABS
Weight:
130g Flush
180g Surface
Colour: Red, Ral 3001