L series 3/3 online UPS (10KVA~400KVA)
User’s Manual
PDF 文件使用 "pdfFactory Pro" 试用版本创建 www.fineprint.cn
Table of contents
1. Importance indication ------------------------------------------------------------------------------------------------------------4
1.1 Applied condition--------------------------------------------------------------------------------------------------------------4
1.2. Working environment--------------------------------------------------------------------------------------------------------4
1.3. Safety notice-------------------------------------------------------------------------------------------------------------------4
2. Product information ---------------------------------------------------------------------------------------------------------------5
2.1. How to name the UPS ----------------------------------------------------------------------------------------------------5
2.2. Main features ----------------------------------------------------------------------------------------------------------------6
2.3. Technology parameters ---------------------------------------------------------------------------------------------------7
3. UPS appearance introduction ------------------------------------------------------------------------------------------------10
3.1. L10~30K3/3---------------------------------------------------------------------------------------------------------------10
3.2.
L40~60K3/3-------------------------------------------------------------------------------------------------------------10
3.3.
L80~120K3/3-------------------------------------------------------------------------------------------------------------11
3.4.
L80~120K3/3 ------------------------------------------------------------------------------------------------------------12
3.5.
L80~120K3/3 ------------------------------------------------------------------------------------------------------------13
4. Parts of UPS --------------------------------------------------------------------------------------------------------------------14
4.1. Rectifier----------------------------------------------------------------------------------------------------------------------14
4.2. Inverter-----------------------------------------------------------------------------------------------------------------------15
4.3. Battery-----------------------------------------------------------------------------------------------------------------------15
4.4. Switch -----------------------------------------------------------------------------------------------------------------------15
4.5. Displaying and touching screen operation--------------------------------------------------------------------------16
4.6. RS232 intelligent communication ------------------------------------------------------------------------------------28
4.7. RS485 intelligent communication ------------------------------------------------------------------------------------28
4.8. Communication of SNMP and distant web -------------------------------------------------------------------------29
4.9. Dry connect state communication ------------------------------------------------------------------------------------29
5. UPS working principle --------------------------------------------------------------------------------------------------------30
5.1. Working principle of complete machine -----------------------------------------------------------------------------30
5.2. Mains operational mode ------------------------------------------------------------------------------------------------32
5.3. Battery inverter operational mode ------------------------------------------------------------------------------------32
5.4. Bypass operational mode ----------------------------------------------------------------------------------------------32
5.5. Manual maintenance bypass mode ----------------------------------------------------------------------------------33
6. UPS installation ----------------------------------------------------------------------------------------------------------------33
6.1. Disassemble and inspect -----------------------------------------------------------------------------------------------33
6.2. UPS positioning -----------------------------------------------------------------------------------------------------------33
6.3. UPS wires connection ---------------------------------------------------------------------------------------------------34
6.4. Connection inspection---------------------------------------------------------------------------------------------------38
7. Operation and management ------------------------------------------------------------------------------------------------38
7.1. Preparations before turning on the machine -----------------------------------------------------------------------38
7.2. The first time turn on the UPS -----------------------------------------------------------------------------------------38
7.3. Test in AC mode operation ---------------------------------------------------------------------------------------------38
7.4. Test in battery mode operation-----------------------------------------------------------------------------------------38
7.5. Daily operation management ------------------------------------------------------------------------------------------39
8. Daily maintaining ---------------------------------------------------------------------------------------------------------------39
8.1. Preventing maintaining --------------------------------------------------------------------------------------------------39
8.2. Battery maintaining ------------------------------------------------------------------------------------------------------39
8.3. The explanation of alarm-------------- ---------------------------------------------------------------------------------40
9. Dispose of abnormal-----------------------------------------------------------------------------------------------------------42
1
PDF 文件使用 "pdfFactory Pro" 试用版本创建 www.fineprint.cn
10. Transport requirements -----------------------------------------------------------------------------------------------------46
10.1. Transport marks ---------------------------------------------------------------------------------------------------------46
10.2. Handling and shipping -------------------------------------------------------------------------------------------------47
11. Packing list ---------------------------------------------------------------------------------------------------------------------47
2
PDF 文件使用 "pdfFactory Pro" 试用版本创建 www.fineprint.cn
1. Importance indication
This manual contains the guidance of UPS and accumulator when installation and application, also
includes the guidance of problem setting and maintenance.
Ø
Please read this user manual carefully before using or installing the machine.
Ø
This manual must be read to and conserved by a professional person.
Ø
This manual does not introduce the specified technologies.
Ø
This manual only applies to the L series 3/3 online UPS.
This manual provides the reference when using and guidance when alarming and working.
1.1. Applied condition
This UPS provides AC power supply, which is the basic power of your equipment. Please carefully check
whether the input and output pressure and frequency can meet the using requirements.
UPS input AC capacitor must be as requested. Otherwise the UPS will work improperly or even occur
security accident (when the UPS input is generator, generator capacity should be 3 multiple more than
UPS).
1.2. Working environment
The working environment and maintain methods also influent the using age and failure rate of the UPS.
Therefore, please avoid the following working environment in long term.
Places over demand of specifications (temperature 0℃~40℃, relative humidity 30%~95%).
Places with bare sunshine.
Places near by the heat sources. Over heat will speed up the external battery self-discharge.
Places liable to shaking and shoving.
Places have powder, corrosive substances and combustible gas.
1.3. Safety notice
Forbiddance
1.3.1. Because it is with high-voltage power in the UPS, only our company’s or our non-authorized technical
staff can open the UPS cover. Otherwise there will be the danger of electric shock and loss the warranty
qualification.
1.3.2. Discussion with distributor is a must before applying to the following load equipments. The application,
setting, management and maintenance and so on must be considerate and design specially.
Life supporting systems
Medical devise directly linked to with the patient's life
Equipment which might endanger person’s safety such as elevator
Similar equipments
3
PDF 文件使用 "pdfFactory Pro" 试用版本创建 www.fineprint.cn
1.3.3. The battery is prohibited to be close to fire, so as to avoid the explosion.
Safety notice
1.3.4. Generally the UPS is in connection with batteries. So that there might still be voltage in the output end
even without AC input.
1.3.5. When UPS need to be moved or re-wiring, you must ensure that all UPS stop working, electricity input
and batteries input is off. Otherwise, there may still be risk of electric shock in the output end.
1.3.6. To ensure the person’s safety, this series UPS must be of good grounding protection and of reliable
grounding before the using.
1.3.7. Please keep the air intake and exhaust open. Poor ventilation will increase the internal temperature of
the UPS and therefore short the lifetime of UPS spare parts.
1.3.8. Liquid and other objects should not be leaked into the inside UPS inside box.
1.3.9. In case of fire broken out around, please use dry powder fire extinguisher. Liquid fire extinguisher will
be danger of electric shock.
1.3.10. The life time of product will decrease by the increasing of temperature. Regular replacement could
guarantee UPS work normally and maintain sufficient time. Replacement the battery must be operated by
authorized technologists.
1.3.11. If no use it long time, UPS must be stored in dry environment, the host (without batteries) the storage
temperature range: -40 ℃~+70 ℃.
1.3.12. In term of no use the UPS for long time, it is advised to charge it by AV for more than 12 hours every
3 months. To avoid any battery damage for long time no using.
1.3.13. Please do not open the battery cabinet in case that the electrolyte injury the skin and eye. If incaution
the body contact the electrolyte, please wash it with plenty of water and then go to the hospital.
1.3.14. Please do not open the cabinet by yourself because there are many high voltage accumulator spare
parts. Otherwise any accident arisen should at your peril.
1.3.15. Please do not disassembly any connection cable by yourself without permission.
1.3.16. Because this UPS is very big and heavy, please do not move and shake it violently. Also good
ventilation is necessary.
1.3.17. Do not exhaust the dust when it is electrophorus. Do not use wet washrag to clean the dirt.
1.3.18. The battery must be replaced by professional technologist. Replaced battery should be send to
special Recycling agencies. Battery belongs to toxic waste.
4
PDF 文件使用 "pdfFactory Pro" 试用版本创建 www.fineprint.cn
2. Products information
L series 3/3 UPSs are with a power range from 10KVA up to 400KVA. This series UPSs use high-speed
MCU and CPLD and programmed and controlled by software. L series 3/3 UPSs bring in the sixth
generation low-exhaust and big-power IGBT and static switch as power components. L series 3/3 UPSs
product combine world’s newest control spare parts and the most advanced software, and apply broadly to
industrials such as building lighting, road traffic lighting, electricity, industry and other industrial and mining
enterprises fields.
2.1. How to name the UPS
L
XXX — 3/3
3 phase in and single out
Rating capacity (KVA)
Low frequency
UNINTERRUPTIBLE POWER SUPPLY
Name: UPS
Type:
L**K3/ 3
Input voltage:
380VAC±20%, 50Hz
Output voltage: 380VAC±2%, 50Hz
Battery voltage: 384VDC
Production date:
Production number: BKUPSTT400K060508001
PC1215400K9H060508
Name——UPS;
Type——it means the UPS’s rating capacity; please refer to the product naming regulation.
Input pressure——rating input pressure and frequency
Output pressure——rating output pressure and frequency
Battery pressure——rating battery pressure
Production date——leave factory date
Production number——production serial number
Code number——CODE-39 standard
2.2. Main features
l
Online working pattern and prompt static switch
5
PDF 文件使用 "pdfFactory Pro" 试用版本创建 www.fineprint.cn
l
Intelligent digital control technology
It adopts 3 high-speed microprocessor controlling systems and operation parameters which make its
operation & management more perfect and its self-diagnosis and self-detect function stronger. You can also
fully trust the sine wave which was converted by figure voltage to operate perfectly and meet your demand.
l
Efficient IGBT inverter AB technology
l
High-speed switch feature of IGBT; High voltage and large current; adopt voltage drives, only needs
little control power. With lower saturation voltage of the fifth IGBT, the inverter AB works more efficiency
and reliable.
l
Superior load
It is completely capable to load from 0-100% while no need to change to bypass, which make sure the
output reliable.
l
Intuitive view of the LED working state and work flow
l
Humanized big touch screen LCD in both Chinese and English
It provides intuitive view of intelligent icon status of the flow chat, tabular data, events records and menu
operation in both Chinese and English.
l
Perfect protection
It has output over/low load protection, input surge protection, phase sequence protection; battery over
charge/discharge protection; short circuit protection; over-temperature protection and so on, as well as
alarming function.
l
High dynamic performance
Adopting kinds of feedback control such as instantaneous control method and valid date, it achieves high
dynamic adjustment and reduces the output THD.
l
Adopt 6 pulse rectifier (option 12 pulse and input harmonic filter)
Effectively restrain the input THD; raise UPS input power factor, reduce the input THD current.
l
Intelligent battery management
L series 3/3 online UPSs can automatically adjust battery charge parameters according the user’s battery
configuration, and can achieve battery float and boost conversion, temperature compensation and battery
charge& discharge management according to the power supply environment. It prolongs the battery’s
lifetime and reduces the operator’s burden.
l
Optional battery detecting module
It is able to test the single parameter, and display on the LCD. If battery failure it will alarm to runner.
l
Intelligent detection function
The system microprocessor will continuously detect on line all power’s supply working status, breaker
status, and all circuits working status. Any failure occurs, the detecting system will immediately alarm to the
runner.
l
Intelligent communication
RS232 and RS485 interface realizes multi-communication and long distance monitor.
The choice SNMP card 100% carries out long distance supervision and network management; the
optional dry contact connection, adopting no have no the source, efficiently carries out the supervision and
control of the UPS status.
l
Characteristic setting
As per different power supply, the UPS can adjust the input parameters.
2.3. Technology parameters
(1)
Rectifier parameters
6
PDF 文件使用 "pdfFactory Pro" 试用版本创建 www.fineprint.cn
Type
(KVA)
L10
L15
L20
L30
L40
L50
L60
L80
L10
L12
L16
L20
L25
L30
L35
L40
K3/
K3/
K3/
K3/
K3/
K3/
K3/
K3/
0K
0K
0K
0K
0K
0K
0K
0K
3
3
3
3
3
3
3
3
3/3
3/3
3/3
3/3
3/3
3/3
3/3
3/3
10
15
20
30
40
50
60
80
100
120
160
200
250
300
350
400
20
30
40
60
80
101
121
161
202
242
323
404
505
606
707
808
Input
capacity(A
)
Working
6 pulse(2 pulse option)rectifier
Phase
Three phase +N+G
Voltage
380VAC±25%
Frequency
50Hz±5%, 60Hz±5%
THDi
<5%
Soft start
0~100% 5s
Output
432VDC
voltage
Set
the DC
voltage by
432VDC(set them by our engineer)
soft
(2) Battery and charge parameters
L10
L15
L20
L30
L40
L50
L60
L80
L10
L12
L16
L20
L25
L30
L35
L40
K3/
K3/
K3/
K3/
K3/
K3/
K3/
K3/
0K
0K
0K
0K
0K
0K
0K
0K
3
3
3
3
3
3
3
3
3/3
3/3
3/3
3/3
3/3
3/3
3/3
3/3
current
27.
42.
discharge(
6
5
108
135
162
216
270
324
428
535
668
803
935
Type
Max
55
82
106
9
A)
Battery
Maintenance-free lead acid battery
type
Battery
32pcs
numbers
DC voltage
384VDC
Float
432VDC(once of three months charge, charge voltage 464VDC)
voltage
Charge
Rated powerX20%(automatically change follow the batteries)
power
(3) Inverter parameters
Type
L10
L15
L20
L30
L40
L50
L60
L80
L10
L12
L16
L20
L25
L30
L35
L40
K3/
K3/
K3/
K3/
K3/
K3/
K3/
K3/
0K
0K
0K
0K
0K
0K
0K
0K
3
3
3
3
3
3
3
3
3/3
3/3
3/3
3/3
3/3
3/3
3/3
3/3
Rated
power
Capacity×0.8(KW)
Cosφ=0.8
7
PDF 文件使用 "pdfFactory Pro" 试用版本创建 www.fineprint.cn
Phase
Three phase+ N+G
Voltage
220/380VAC±1%(state load, 220/380VAC±5%(fluctuate load))
Frequency
50Hz±0.5%, 60Hz±0.5%(with battery)
Output
<±0.5%(no in phase)
frequency
stability
Input
50Hz±5%
frequency
Crest
3:1
factor
Wave
Pure sine wave
Output
waveform
Pure sine wave, linear load<3%; non-linear load<5%
distortion
Dynamic
<±5%( 0←→100%load)
characteris
tics
Recover
<10ms
time
Overload
125% 1 minute, 150% 1s
Inverter
≥95%(with100% load)
efficiency
(4)Bypass parameters
Type
L10
L15
L20
L30
L40
L50
L60
L80
L10
L12
L16
L20
L25
L30
L35
L40
K3/
K3/
K3/
K3/
K3/
K3/
K3/
K3/
0K
0K
0K
0K
0K
0K
0K
0K
3
3
3
3
3
3
3
3
3/3
3/3
3/3
3/3
3/3
3/3
3/3
3/3
Phase
Single phase + N
Voltage
220/380VAC±25%
Frequency
50Hz±5%, 60Hz±5%
Transfer
<1ms(inverter←→bypass)
time
(5)System parameters
Type
L1
L1
L2
L3
L4
L5
L6
L8
L1
L1
L1
L2
L2
L3
L3
L4
0K
5K
0K
0K
0K
0K
0K
0K
00
20
60
00
50
00
50
00
3/3
3/3
3/3
3/3
3/3
3/3
3/3
3/3
K3/
K3/
K3/
K3/
K3/
K3/
K3/
K3/
3
3
3
3
3
3
3
3
Efficiency
>80%(load 100%)
Communication
RS232/RS485, (SNMP card option)
Temperature
0~40℃
Relative
humidity(no
30%~90%
coagulation)
8
PDF 文件使用 "pdfFactory Pro" 试用版本创建 www.fineprint.cn
<1000M(a 1% decrease against 100 meters’ rise; altitude 4000M Max)
Height(Max)
Cooling–down
Compulsive ventilation(with temperature control)
method
Noise dB
40~50
45~55
55~60
60~65
65~70
980×800×180
1380×950×180
1600×1150×18
0
0
00
Cabinet colors
Grey(option other colors)
Input place
Under/back
Easy to maintain
Top/left or right side open
Cabinet size
W×D×H(mm3)
Weight(Kg)
430×750×1050
200
300
350
430×765×1050
40
0
480
530
580
85
92
12
13
15
17
18
19
19
0
0
00
00
20
20
30
30
80
Input mode
With the line connection
Output mode
With the line connection
All the above parameters are reference only, any difference please refer to the actual UPS.
3. UPS appearance introduction
3.1. L10~30K3/3
Logo
Dry port
Working LED display
Parallel port
Touch screen + LCD
Switch
Fan
Switch
Connection
Trolley
3.2. L40~60K3/3
9
PDF 文件使用 "pdfFactory Pro" 试用版本创建 www.fineprint.cn
3.3. L80~120K3/3
10
PDF 文件使用 "pdfFactory Pro" 试用版本创建 www.fineprint.cn
3.4. L160~250K 3/3
11
PDF 文件使用 "pdfFactory Pro" 试用版本创建 www.fineprint.cn
3.5. L300~400 3/3
12
PDF 文件使用 "pdfFactory Pro" 试用版本创建 www.fineprint.cn
A.
Working status lamp ---- indicate each part of the circuit working status when it works.
Ø
Bypass input---- lightens when bypass input power’s voltage and frequency are within normal
range.
Ø
Bypass operation----lightens when static switch is bypass working status.
Ø
Main power input---- lightens when main input power’s voltage and frequency are within normal
range.
B.
Ø
Rectifier normal -- lightens when rectifier works normally.
Ø
Inverter normal -- lightens when inverter works normally.
Ø
Input indication -- lightens when UPS inputs.
Ø
Wrong phase order -- lighten when input AC’s phase order has error.
Ø
Working status -- lightens when controlling circuit of the whole machine works normally.
Ø
Battery normal -- lightens when battery’s voltage works normally.
Ø
Low voltage -- lightens when the voltage of the battery is low.
Ø
Overloaded input -- lightens when the input is overloaded.
Touch screen plus LCD
Ø
Touch screen -- you can touch directly on the screen board and enter into the corresponding
menu.
Ø
C.
LCD -- show the status and figures.
Details please refer to the part of display and communication.
13
PDF 文件使用 "pdfFactory Pro" 试用版本创建 www.fineprint.cn
Ø
Rectifier switch -- the breaker controls the rectifier’s input. Meanwhile it protects the rectifier: the
breaker cuts when the rectifier is over current.
Ø
Bypass switch -- the breaker controls the bypass’s input and protect the bypass meanwhile. The
breaker cuts when bypass circuit is over current.
Ø
Battery’s switch -- the breaker controls the battery’s input and protects the battery group
meanwhile. The breaker cuts when battery group is over current.
Ø
Input switch -- the breaker controls the UPS’s AC output and protects the output meanwhile. The
breaker cuts when input over current or short circuit.
Ø
Maintain switch -- it is used for maintain ups with uninterruptible power, It will turn off when working
normally. Please refer to correct flow when using this swift, otherwise it will cause the failure of
UPS or output cut.
——Flow of turning on the manual bypass: Manually turn off the inverter (please press the F1 and F2
synchronously on the panel) and start the UPS bypass status. Turn off the manual bypass and then cut
off the output swift. Then cut off the other swift according to the detail.
——Flow of turning off the manual bypass: turn on the bypass swift and manually turn off the inverter.
Then turn off the output swift and the manual bypass. Then close the rectifier swift and battery swift.
D.
Connection end -- cables connect the input, output and battery.
E.
Dry connection point connections
F.
RSS232 communication meet end -- connect the RS232 meet end in the computer. It will monitor the
UPS in background through monitor software.
G.
RS485 communication meet end -- connect the RS485 meet end in the computer. It will monitor the
UPS in background through monitor software.
H.
SNMP card -- connect the inter website and operate the web long-distance monitor.
I.
Boarding -- open it and screw and connect lines
J.
Idler wheel -- To move the UPS when installing. Should be fixed after installation.
4. Parts of UPS
4.1. Rectifier
Convert the 3 phase input AC electricity into stable DC through the rectifier and charge the battery
meanwhile. Its consisted parts are as following:
Rectifier circuit
MCU
DC bus filter
BUS FILTER
Harmonic filter
3phase mains
Rectifier switch
Inverter
6 or 12 pulse rectifier
Batteries
Input voltage and frequency
Battery voltage and charging circuit
inspection
inspection
Input voltage frequency default
Charging voltage and circuit controlling,
phase Rectifier controlling
BUS protection
14
PDF 文件使用 "pdfFactory Pro" 试用版本创建 www.fineprint.cn
As the above chart, controlled by input through rectifier switch, the main power was rectified to DC firstly
by harmonic filter and secondly the 6 or 12 pulse rectifier. At last it was rectified to stable DC bus by
harmonic again. Though measuring the input voltage and frequency and DC bus and controlling the rectifier,
the commutating control circuit input stable DC to inverter and battery group. Meanwhile it starts protection
when I/P wrong phase, be lack phase and over limited.
4.2. Inverter
Filter
¸Transformer
IGBT
Output filter
DC input
Load
Sampling
Sampling
Reactive circuit
Sampling
CPU
Reactive circuit
Be consist of sampling circuit, single-chip controlling circuit, IGB driving circuit, IGBT module, inverter
isolating transformer, filter inductance and protecting circuit. Microprocessor firstly produce the SPWM signal
through computing the sampling signals, and meanwhile drive the IGBT module bas AC and change it into
high frequency SPWM waves. Secondly it output pure sine AC through inverter isolating transformer,
inverter filter. At the same time it adjust the output voltage and waves’ shape via the feedback of sampling
signals such as voltage, current and temperature.
4.3. Battery
Battery is consisted of the power slot (plastic crust), the cathode plate, the negative electrode, separator,
electrolyte, inter-unit bridge, terminations, safety valves and other components. It is a power and chemical
energy conversion devices. The working principle is, when AC is normal the charger will charge and the
battery will convert the power to chemical energy which will be stored in the battery; when the AC works
abnormally the battery will convert the chemical energy to power to UPS.
4.4. Switch
15
PDF 文件使用 "pdfFactory Pro" 试用版本创建 www.fineprint.cn
Static bypass switch
Bypass switch
Output switch
Inverter
Static inverter switch
The UPS pattern is dual-mode transformation. When the inverter does not start it is bypass mode; after
turning on the inverter it will high-speedily switch from static bypass switch to static inverter output switch. As
static switch is electronic switch so there is no mechanical switching time.
4.5. Displaying and touching screen operation
4.5.1. Touching screen information
Touch-screen LCD monitors is our company’s latest invention of the UPS modules, using today's most
popular and intuitive graphical operation interface. Comparing with the traditional button-LCD display
modules, the touch-screen display module shows a more rich content which avoids frequent page turning. At
the same time because the user can get corresponding information by directly press the button on the
display screen. It is easy to use easy to get. Meanwhile touch-screen display module comes with real-time
clock and memory and can be recorded 256 incidents and other information, which is more humanize.
4.5.2. Operation interface statement
4.5.2.1 Standby screen
Standby screen is shown in figure 1. UPS will start up in the show this standby screen. When the
touch-screen interval of about four minutes not to touch, shows CPU will automatically cut off power ----touch screen backlight can be extended so the backlight life, and return to the standby interface (if UPS is in
the police state, the touch screen will be priority information shows that the police box, police information to
repeal or abolish manual alarm will not be cut off before the show CPU touch screen backlight back to
standby power supply interface).
Chart 1
16
PDF 文件使用 "pdfFactory Pro" 试用版本创建 www.fineprint.cn
4.5.2.2 Flow chart
As shown in chart 2. Flow chart of the display screen is as shown in figure 2. In standby screen, click any
on display screen with their hands to enter the flow chart of the display screen. In this screen can be seen in
the UPS work and running the graphics display. Screen in all parts of significance as follows:
(1) Working status: UPS is on working.
(2) Alarming: work abnormally.
(3) Phase lock: when the touch screen displays this mark, it means the UPS and bypass at same frequency,
same phase; if in parallel system, and this UPS in accessorial l status, it shows the accessory UPS and the
main UPS at same frequency, same phase.
(4) Communicating: UPS has been in connection with long distant monitor.
(5) Timing: there is timing assignment.
(6) Time countdown turning on/off: when the screen appears in the “S” logo, the system is to enter the
countdown shutdown turning off; when the screen appears “R” logo, the system is to enter into the
countdown turning on state.
(7) Count down clock: balance time display.
, it means
(8) Maintaining bypass switch: display the maintaining bypass state, when it turns out mark
the maintaining bypass is turned on, when it turns out mark of
turned off.
, it means the maintaining bypass is
(9) Bypass button: you can check the bypass input state and data display by pressing it.
(10) When it turns out mark
bypass is turned off.
, it means the bypass is turned on, when it turns out mark
, it means the
(11) AC button: you can check the AC input state and data display by pressing it
(12) Input switch: display the input switch state, when it turns out mark
, it means the input switch is
turned on, when it turns out mark
, it means the input switch is turned off.
(13) Rectifier button: you can check the rectifier’s working status and data display.
(14) System management module: you can control the UPS and inquiry the system record by pressing it.
, in the screen it means the AC fuse works
(15) AC safety: display the AC safety state, when it is
normally, when it is
, in the screen it means the AC fuse works abnormally.
(16) Inverter button: you can check the inverter’s working status and data display by pressing it.
(17) Output switch: display the state of output switch, when it turns out mark
, it means the output switch
is turned on; when it turns out mark
it means the output switch is turned off.
(18) Output button: you can check the UPS output status and data display by pressing it.
(19) Battery switch: display the switch’s statement, when it is
when it is
it means the batter’s switch is turned on;
, it means the batter’s switch is turned off.
(20) System parameters setting module: to set the system time and language and so on.
(21) Battery button: you can check the battery’s working status and data display by pressing it.
(22) System time: display the real time on the system.
(23) UPS series number: show the UPS production series number.
(24) Broken line: it means the connected modules with broken line are off working.
(25) Real line, it means the connected modules with real line are on working.
(26) Present working pattern: if it shows the mark
pattern; if it shows the mark
, it means the system is working under the ECO
, it means the system is working under the UPS pattern; if no mark, it
17
PDF 文件使用 "pdfFactory Pro" 试用版本创建 www.fineprint.cn
means the system is working under UPS pattern.
1
2
3
6
5
4
27
7
8
25
26
9
16
10
17
11
18
12
19
13
20
14
21
15
22
23
24
Chart 2
4.5.2.3 Data measured display interface
You can enter into the corresponding measuring data display interface by press the buttons. The detail is:
⑴ Table title
⑵ Table content: kinds of states and data display
⑶ System time: system real time
⑷ Back
⑸ Escape: back to the standby interface
UPS AC output instant inspection
1
AC output voltage(V)
220
220
220
AC output frequency(Hz)
50.0
50.0
50.0
AC output current(A)
00.0
00.0
00.0
Load capacity (%)
000
000
000
Bypass static switch working
Turn on
state
Inverter static switch working
Turn off
5
state
3
4
2007-01-01 00:00:00
Chart 3
18
PDF 文件使用 "pdfFactory Pro" 试用版本创建 www.fineprint.cn
4.5.2.4 Management display interface
As shown in chart 4, when you are in flow chart interface you can enter into the management display
interface by clicking on the management display interface button. In this interface you can press
corresponding button to operate the UPS.
⑴ Turn on/off UPS operation button: the button will display “start the system” when the UPS is turned off.
Press this button it will start the UPS. Correspondently, the button will display “shut down the system” when
the UPS is turned on.
⑵ Battery test operation button: when the UPS is turned on, you can press this button to enter into battery
test pattern (password is required in order to avoid mis-operation).
⑶ About the button: you can enquiry touching screen edition information by pressing it.
⑷ Alarming elimination: to eliminate the buzzer alarming by pressing it.
⑸ Current status button: to check the UPS current working status by pressing it.
⑹ Esc: back to standby interface.
⑺ Back
⑻ Help: you can look into help information about the touching screen by pressing it.
⑼ System information: you can look into UPS rating information by pressing it.
⑽ System record: you can look into record about the touching screen by pressing it.
2
3
4
1
5
10
6
9
7
8
Chart 4
4.5.2.5 Password input interface
Some operation will change the UPS current state, such as turning on/off the machine and so on. So here
you will be requested to input the password and otherwise the operation will be refused. Original password
when the machine leaves the factory is 1234. Password input interface is shown as chart five and the detail
meanings are:
19
PDF 文件使用 "pdfFactory Pro" 试用版本创建 www.fineprint.cn
⑴ Input password: to display the input password digit. In order to protect it, the password will be covered by
**
⑵ Number key: to input corresponding figures.
⑶ Enter key: to press this key after you finished the password input.
⑷ Cancel: escape the password input dialog.
System will run correspondingly after input the correct password.
1
2
4
3
Chart 5
4.5.2.6 Incident record enquiry interface
You can enter into incident enquiry interface after pressing “system record key” in the management
display interface. This interface display the all the system records and incidents, as shown in the chart six.
Each part in the chart is means:
⑴ Events in memory are of the order, the latest incident is in the first order, the smallest number.
⑵ Incident code
⑶ Incident time: incidents occur time.
⑷ Time description: describe the detail incident type.
⑸ Page up: enquiry other 9 incidents record.
⑹ Page down: enquiry other 9 incidents record.
⑺ Escape key: escape from the catalogue and back to standby interface.
⑻ Back key.
20
PDF 文件使用 "pdfFactory Pro" 试用版本创建 www.fineprint.cn
Incident record
1
Number
000
2
Code
044
001
002
002
062
Time
2007-01-01
001
004
000
4
Eliminate alarming
00:00:03
Batter low voltage
2007-01-01
00:00:00
2007-01-01
6
Rectifier shut down
00:00:00
3
003
Incident
2007-01-01
Input abnormally
00:00:00
2000-00-00
Blank
00:00:00
8
5
7
2007-01-01 00:00:00
Chart 6
4.5.2.7 Currently UPS working state interface
You can enter into current UPS working state interface after pressing this button in the management
display interface. This interface display the system current working state, as shown in the chart seven. Each
part in the chart is means:
⑴ Show UPS’s currently working status.
⑵ Escape: escape all menu and back to standby interface.
⑶ Back up
UPS current working state
UPS has been turned off; battery low voltage, input
1
abnormally; bypass
Output
2
3
2007-01-01
00:00:00
Chart 7
4.5.2.8 System setting interface
21
PDF 文件使用 "pdfFactory Pro" 试用版本创建 www.fineprint.cn
As shown in the chart eight. Press the system parameter setting module button in the flow chart interface
you will enter into the system setting display interface. Press any key you can modify the UPS’s system
parameter. Each part of the interface means:
⑴ Time setting: to modify the system clock (password is required by the system in case of wrong operation).
⑵ Language choosing: to choose system language. Chinese and English is available from the system.
⑶ Help: enquiry touch screen information by pressing it.
⑷ Back
⑸ Escape: escape all menu and back to standby interface.
⑹ Clean system record: to clean all incident record in the system (password is required by the system in
case of wrong operation).
⑺ Password modifying: to modify the system operation password. Last password is required by the system
in case of wrong operation. New password will be required to input twice. If two passwords are the same the
password modifying succeeds.
7
1
6
2
5
3
4
Chart 8
4.5.2.9 Password input interface
Some operation will change the UPS’s current parameters, such as system time modifying. Here system
will request operator to input password. Otherwise operation will be refused.
4.5.2.10 Clock setting interface
You can enter into clock setting interface by pressing the clock setting button in the setting interface and
input the correct password. Each part of the interface means:
(1) Dialog. Input "?" before input new number; when the user input new number then it will display the
number.
⑵ Month: enter the new month. Input "?" before input new number; when the user input new number then it
will display the number.
⑶ Day: enter the new day. Input "?" before input new number; when the user input new number then it will
display the number.
⑷ Enter: finish the input by pressing it.
⑸ Cancel: escape new clock setting dialog box.
22
PDF 文件使用 "pdfFactory Pro" 试用版本创建 www.fineprint.cn
⑹ Number key: input corresponding figures.
⑺ Minute: enter the new minute. Input "?" before input new number; when the user input new number then it
will display the number.
⑻ Seconds: enter the new seconds. Input "?" before input new number; when the user input new number
then it will display the number.
⑼ Hour: enter the new hour. Input "?" before input new number; when the user input new number then it will
display the number.
1
3
9
7
8
6
2
5
4
Chart 9
Notice: when setting the clock, the order is from left to right, that is set chronological order: year → month
→ day → hour → minute → seconds. Every figure the user input, the number of the cursor automatically
move right one digit, and correspondingly, the “?” be replaced by the number user inputted.
4.5.2.11. Record clean interface
In the setting interface, press the record clean button and input the correct password can enter into record
clean interface. All the incidents records will be deleted and irretrievable. As shown in the chart ten. Each
part of the interface means:
⑴ Message dialog
⑵ Schedule bar: delete assignment schedule
23
PDF 文件使用 "pdfFactory Pro" 试用版本创建 www.fineprint.cn
1
2
Chart 10
4.5.2.12. Language choosing interface
Press language button in the setting interface you will enter into the language choosing interface. Here
you can choose the system language:
⑴ Message dialog
⑵ Chinese language choosing dialog: press this button the system will display all message with Chinese.
⑶ English language choosing dialog: press this button the system will display all message with English.
1
2
3
Chart 11
4.5.2.13. Alarming interface
When the UPS is on alarming status, the displaying module will prior display alarming interface. If UPS
alarming interface does not canceled, displaying module will keep on displaying the alarming interface till be
canceled. As shown in chart 12. Each part of the interface means:
⑴ Alarming message dialog: alarming message will display here.
⑵ Alarming message display
⑶ Enter key: press this will cancel the alarming and escape the alarming interface meanwhile.
24
PDF 文件使用 "pdfFactory Pro" 试用版本创建 www.fineprint.cn
1
2
3
Chart 12
4.5.2.14 battery password setting interface
When UPS are in setting interface, the screen will skip automatically to this interface to require user to input
the operation password, as shown in chart 13. Each part of the interface means:
⑴ Password input: display password digit. For safety purpose the inputted number will be replaced by *.
⑵ Number key: input corresponding numbers.
⑶ Enter key: press it to finish the password inputting. If the password is correct, the screen will switch to
4.5.2.15 display interface. Otherwise there will be no switch and require another password inputting.
⑷ Cancel: to cancel the inputted password and try again.
Notice: This password is not the touch screen operation password mentioned above, but is the password
which is set when leaving factory. Acquiescent password: 6666.
1
2
3
4
Chart 13
4.5.2.15. Battery capacity setting interface
25
PDF 文件使用 "pdfFactory Pro" 试用版本创建 www.fineprint.cn
When UPS is on setting status and you have inputted the correct password, the screen will automatically
skip to this interface and you are required to input UPS corresponding battery capacity. As shown in chart 14.
Each part of the chart means:
⑴ Inputted battery capacity: to display inputted numbers. Please set from left to right. That is the order of:
hundred place → ten place → one place. Each number the user inputs, the cursor automatically move right
one digit, correspondingly the “?“ will replace with the inputted number.
⑵ Number key: input corresponding number.
⑶ Enter key: press it to finish the password inputting. If the password is correct, the screen will switch to
4.5.2.15 display interface.
⑷ Cancel: to cancel the inputted password and try again.
1
2
3
4
Chart 14
4.5.2.16. Working pattern setting interface
As shown in chart 15. Each part of the chart means:
⑴ Working pattern choosing dialog
⑵ UPS working pattern. Press this button to enter into the UPS working pattern.
⑶ ECO working pattern: press this button to enter into the ECO working pattern.
⑷ UPS working pattern: press this button to enter into the UPS working pattern.
1
2
3
4
26
PDF 文件使用 "pdfFactory Pro" 试用版本创建 www.fineprint.cn
Chart 15
After setting the working pattern the setting parameters will be permanently saved in the machine. Escape
the setting status and restart the machine.
4.5.2.17. Incident code
System will automatically record some important incident and the date for future enquiry and management.
The maximum capacity is 256 incidents. Every kind of incident will be code differently. Users can press the
system record key in the system management operation interface to enquiry the incident record. In the table,
beside of displaying ever y record’s code and time, the screen will also present brief incident description. In
the below chart 13 we will give all the incident code and detail incident descriptions.
Code
Detail incident description
000
Blank, no record
001
Mains error
002
Battery voltage low
003
UPS overloaded
004
Temperature error means temp high
005
Phase order error,
Phase order error: wrong input phase order
006
Inverter error
007
System error
008
Bypass output incident, means the UPS switch to bypass output.
009
Inverter output incident, means the UPS switch to inverter output.
010
Rectifier error
011
Maintaining bypass switch is turning on
012
DC fuse is off
013
Rectifier switch is cut down
014
Bypass switch is turning on
015
Output switch is turning off
016
Battery switch is cut down
020
Batter switch is turning on
021
AC returns to normal
022
Battery voltage returns to normal
023
Load returns to normal
024
UPS temperature recover normal
025
UPS phase order returns to normal
026
Maintaining bypass switch is turning off
027
AC insurance returns to normal
028
Rectifier switch turning on
029
Battery switch turning on
030
Output switch turning on
031
Transmission error
032
Transmission returns to normal
041
042
Turning off automatically, means the machine is automatically shut down
because of low UPS voltage or other error, and switch to bypass output
UPS restart
27
PDF 文件使用 "pdfFactory Pro" 试用版本创建 www.fineprint.cn
043
UPS enter battery testing status
044
Cancel buzzer alarming manually
045
Turn off UPS manually
051
052
User sends distant count down UPS turning off command from the
monitor end
User sends distant count down UPS turning on command from the
monitor end
053
Count down time till turning off the UPS
054
Count down time till turning on the UPS
055
User sends distant count down UPS turning on canceling command from
the monitor end
056
Send battery testing command from the display panel
057
Send alarming canceling command from the display panel
058
Send turning on command from the display panel
059
Send turning off command from the display panel
061
Rectifier re-works
062
Rectifier stops working
Other
Unknown error or wrong error record
4.6. RS232 intelligent communication
End definition adopts DB9 standard port
NC--------------------------------1
RXD------------------------------2
TXD------------------------------3
NC--------------------------------4
Signal GND---------------------5
NC--------------------------------6
NC--------------------------------7
NC--------------------------------8
NC--------------------------------9
2 pin: receiving end, receive computer RS-232 communication data in the UPS.
3 pin: sending end, send computer RS-232 communication data in the UPS.
5 pin: communication “GND”;
Other pin: no connect.
RS-232 communication provides the following functions
Monitor UPS current power supplying status.
Monitor UPS current alarming status.
Monitor UPS current running parameters.
To control the UPS time turning on/ff and setting the system.
RS-232 communication data format
Baud rate ---------------------- 2400bps
28
PDF 文件使用 "pdfFactory Pro" 试用版本创建 www.fineprint.cn
Byte------------------------------ 8bit
Over No ------------------------ 1bit
Parity check ------------------- NO
Connection of computer RS-232 and UPS RS232
Computer ----------------------------------------------------------
UPS
RXD (2 pin) --------------------------------------------------------
TX (3 pin)
TXD (3 pin) ----------------------------------------------- ----------
RX (2 pin)
GND (5 pin) --------------------------------------------------------
GND (5 pin)
4.7. RS485 intelligent communication
Port definition (from left to right)
1 pin: RS-485 communication port A(DATA+) port;
2 pin: RS-485 communication port B(DATA-) port;
3 pin: RS-485 Communication GND
4 pin: RS-485 communication port A(DATA+) port
5 pin: RS-485 communication port B(DATA-) port
6 pin: communication GND;
RS-485 communication method provides the same function with RS-232
RS-485 communication data format provides the same function with RS-232
How to connect UPS with RS-485
How to connect -------------------------------------------------- UPS
DATA+ port ------------------------------------------------------- A port (1 pin)
DATA- port -------------------------------------------------------- B port (2 pin)
GND por t --------------------------------------------------------- Communication source (3 pin)
How to connect UPS with UPS RS-485
UPS1
----------------------------------------------------- UPS2
A port (4 pin) ---------------------------------------------------- A port (1 pin)
B port (5 pin) ---------------------------------------------------- B port (2 pin)
Communication GND (6 pin)-------------------------------- Communication GND (3 pin)
4.8. Communication of SNMP and distant web
Port definition
T568A standard and T568B standard
Ø
T568A standard description order from left to right is: 1-white & green, 2-green, 3-white&orange,
4-blue, 5-white&blue, 6-orange, 7-white&brown, 8-brown
Ø
T568B standard description order from left to right is: 1-white and brown, 2-orange, 3-white&green,
29
PDF 文件使用 "pdfFactory Pro" 试用版本创建 www.fineprint.cn
4-blue, 5-white&blue, 6-green, 7-white&brown, 8-brown
SNMP card has the following function
Ø
Provide SNMP MIB to monitor the UPS status.
Ø
Automatically detect and transform the 10/100M fast ETHERNET SPEED
Ø
Set the functions through internet, web browser or NMS
Ø
Support TCP/IP, UDP, SNMP, TELNET, SNTP, PPP, HTTP, SMTP agreements.
Ø
Provide facility installation and updating tools which applied to MS-windows. No need the
time-costing RS232 traditional way to set.
Ø
Send SNMP TRAP, EMAIL and pager to inform the operator when battery errors.
Ø
Can be set of sending daily history record via email.
Ø
Able to match shutdown software to protect computer system to save documents safely and turning
off the machine.
Ø
Net Agent-3 ports generation: able to link out NETFEELER LITE environment detecting system and
external modems. Also able to use the dial-up methods
4.9. Dry connect state communication
Port definition
1 pin: Rectifier signal is the COM port of relay
2 pin: Rectifier signal is the NC port of relay
3 pin: Bypass signal is the COM port of relay
4 pin: Rectifier signal is the NC port of relay
5 pin: Inverter signal is the COM port of relay
6 pin: Inverter signal is the NC port of relay
7 pin: DC input signal is the COM port of relay
8 pin: DC input signal is the NC port of relay
9 pin: BAT low signal is the COM port of relay
10 pin: BAT low signal is the NC port of relay
11 pin: System fault signal is the COM port of relay
12 pin: System fault signal is the NC port of relay
13 pin: Rectifier switch signal is the COM port of relay
14 pin: Rectifier switch signal is the NC port of relay
15 pin: Bypass switch signal is the COM port of relay
16 pin: Rectifier switch signal is the NC port of relay
17 pin: Inverter switch signal is the COM port of relay
18 pin: Inverter switch signal is the NC port of relay
19 pin: DC input switch signal is the COM port of relay
20 pin: DC input switch signal is the NC port of relay
21 pin: Maintain switch signal is the COM port of relay
22 pin: Maintain switch signal is the NC port of relay
23 pin: Fuse signal is the COM port of relay
24 pin: Fuse signal is the NC port of relay
Dry connect state communication function
Rectifier status—signal relay turns on at the rectifier working normally
30
PDF 文件使用 "pdfFactory Pro" 试用版本创建 www.fineprint.cn
Bypass status—signal relay turns on at the bypass working normally
Inverter status—signal relay turns on at the inverter working normally
DC input status—signal relay turns on at the DC inverter working normally
BAT voltage low status—signal relay turns on at the BAT voltage low
System fault status—signal relay turns on at the system fault
Rectifier switch status—signal relay turns on when the rectifier switch is turned on
Bypass switch status—signal relay turns on when the bypass switch is turned on
Output switch status—signal relay turns on when the output switch is turned on
DC input switch status—signal relay turns on when the DC input switch is turned on
Maintain switch status—signal relay turns on when the maintain switch is turned on
Fuse status—signal relay turns on when the fuse is broken
5. UPS working principle
5.1. Working principle of complete machine
l
Diagram of complete machine working principle
Manual maintenance bypass
Bypass input
Auto bypass
Load
Battery input
Static switch
Main power input
Communication unit
l
Rectifier
Inverter
Display unit
MCU control center
Working principle of complete machine
UPS is multi-lay protected alternating current supply equipment. When the main power is normal, firstly, to
rectify the main current and transfer it into pure direct current and filter the disturbance in main power; then
charge up the accumulator and output the main power. When the main power is abnormal, to invert the
direct current stocked in accumulator into alternating current and output it to ensure the high quality power
supply of user load. The manual maintenance bypass ensures the maintenance, examination and repair of
UPS on the condition of no power cut.
l
MCU control center
MCU high-speed operates such data as input, output, battery and environment; then control the running
and protection of rectifier, inverter and static switch to respond the external operation instruction.
l
Rectify and charge unit
Main power input examines the circuit and send the voltage, frequency and phase of main power input to
MCU for operation. When the voltage, frequency and phase of main power input are within the normal range,
MCU delivers the rectified control signal; rectified voltage slowly raised to rated voltage from 0V so as to
minus the strike on the input surge current.
31
PDF 文件使用 "pdfFactory Pro" 试用版本创建 www.fineprint.cn
As battery pack and DC(direct current) bus is operating in parallel, rectifier is charging the battery at the
same time, therefore, when battery’s voltage is lower than floating battery’s voltage, rectifier will operate in
constant current mode. At this time, MCU will calculate and control the feedback of charge current from
battery and the information of battery capacity set by user; when battery is charged into floating voltage, then
rectifier will change into constant voltage charging mode. Meanwhile, basing on the temperature of battery,
MCU will charge battery in a temperature compensation style, maintain and manage battery in a regular time
on the basis of its using situation (when battery hasn’t been charged or discharged for a very long time, MCU
will automatically transfer into an equalized charging mode in order to activate the activity of battery), thus it
will extend battery’s lifetime and reduce user’s burden of management.
l
IGBT inverter unit
When DC bus is normal, if MCU issues inverter control signal, inverter circuit will drive IGBT Inverter
Bridge by SPWM driving signal, through inverter’s isolation, voltage transformation and wave filtration,
produce out pure sine AC (altering current). Through adjusting driving signal’s pulse width, Inverter can raise
output voltage from 0V to rated degree, and control stability of output through its feedback. Meanwhile,
check voltage and current of output in order to protect inverter.
l
Automatic and manual bypass unit
Bypass circuit can directly convert input electricity into output electricity through switch circuit. If inverter is
closed or fell, MCU-controlled high-speed static switch will automatically switch into bypass electricity,
without interrupt loaded power supply.
Bypass and main power can be a same group of power supply; it also can be a different AC (altering
current).
l
Display communication unit:
Display unit is to show operational status and data of entire machine through LCD and LED, and through
RS232, RS485, dry contact signal, SNMP card, etc., realize long-distance monitor with background
software.
L series 3/3 adopt large-screen LCD (320×240) and touch-screen design, graphical manipulative interface,
tabular data display. With 256 long record of incident, L series 3/3 can provide great help to your power
supply status’s analysis and management.
POCASA-styled UPS highly integrates digital technology, improves MTBF and reliability, its independent
main control board controls the whole system’s work. Meanwhile, it is controlled by a high-speed
microprocessor, which ensures the stability of equipment and the reliability of operation.
32
PDF 文件使用 "pdfFactory Pro" 试用版本创建 www.fineprint.cn
Power& sampling board
Input sampling
Output sampling
Rectifier sampling
Temperature
Charger Inverter
Static
LED display
switch
LCD display
CPU
Display
Battery sampling
Rectifier
Touch screen
Communication board
Switch sampling
Fuse sampling
Fuse sampling
Dry contact
Protec Alarm Battery
signal
tion
SPWM
signal
RS
232
RS
485
SNMP
card
Besides the above chart, other components of UPS include: inverter transformer, input inductance, IGBT,
SCR, switches, etc.
5.2. Mains operational mode
Manual maintenance bypass
Bypass input
Auto bypass
Battery input
Static
switch
Main power input
Rectifier
Communication unit
Load
Inverter
Display unit
MCU control center
The input AC will be transformed into DC through rectification and filtering, and then through SPWM
Inverter, DC outputs AC supply, through static inverter switch, AC reaches user. At the same time, DC can
charge the battery pack.
5.3. Battery inverter operational mode
Bypass input
Auto bypass
Static
Main power input
switch
Battery input
Communication unit
Rectifier
Load
Inverter
Display unit
MCU control center
When mains become abnormal, battery will supply AC through SPWM Inverter; put it out through static
inverter switch.
5.4. Bypass operational mode
33
PDF 文件使用 "pdfFactory Pro" 试用版本创建 www.fineprint.cn
Manual maintenance bypass
Bypass input
Auto bypass
Static
Main power input
Load
switch
Inverter
Battery input
Rectifier
Communication unit
Display unit
MCU control center
When inverter is not open or abnormal, then system will convert into bypass operational mode, AC inputs
through bypass circuit, and outputs through static switch.
5.5. Manual maintenance bypass mode
Manual maintenance bypass
Bypass input
Auto bypass
Static
Main power input
switch
Battery input
Rectifier
Communication unit
Display unit
Load
Inverter
MCU control center
When asked on-wire maintenance without cutting power, the switch on maintenance bypass needs to be
turned on, cut off the output switch and auto bypass switch, this will completely separate UPS's circuit from
input and output, without interrupting users’ output.
Note: when using maintenance bypass switch, must accord with operational procedures of maintenance
switch!
6. UPS installation
6.1. Disassemble and inspect
Ø
When open up packages, and take out UPS, check if it has any damage during transportation
Ø
At the same time, make sure all the switches are cut off, UPS inside should include: warranty card,
instruction, installation manual, RS232 CD-ROM, RS232 cable.
6.2. UPS positioning
6.2.1. Environmental requirements of installation
Ø
Temperature: 0℃~+40℃
Ø
Relative humidity: 30%~90%
Ø
Height: less than 1000M, if height exceeds 1,000M, reduce 10% usage per 1000M
Ø
The size of installation environment should be larger at least 800 mm than the front and back, left and
right size of equipment in order to convenient thermal dispersion and routine maintenance; floor force
requirement: 1500KG/M2.
Ensure installation has following indoor environment.
34
PDF 文件使用 "pdfFactory Pro" 试用版本创建 www.fineprint.cn
Ø
No dust
Ø
A proper indoor temperature: UPS can operate under 0~40℃ indoor environment, but to open it, it
needs temperature to be higher than 0℃, the ideal temperature is 25℃.
Ø
Have a good cooling system, there are some feasible methods as followings:
A. Natural ventilation system: only apply to low heat and broad space.
B. Artificial ventilation system: when temperature of machine shell (TA) higher than exterior
temperature (TE), then it is necessary to install an air condition. When these two temperatures are
close, the capacity of ventilation system needs to be increased relatively.
UPS is forbidden to locate at any of following conditions
Avoid direct sunlight
Avoid raining and humidity
Level off
Far from fire and high temperature
Do not place on unsmooth ground
Avoid rot-gas
Do not place on oblique ground
6.2.2. Installation location
Ø
Distance of machine back from wall or any object should be at least 800mm
Ø
At the top of UPS should not be placed any object
Ø
The front, right and left sides of equipment should be prepared enough space for maintenance
operation
Ø
Equipment battery should be installed in the right-hand side of machine, and reserve sufficient space for
battery overhauling
6.3. UPS wires connection
6.3.1. 3 phase in and 3 phase out UPS systems 10-400KVA recommended cable specifications: (unit: mm2)
Capacity
L10K3/3
Input, bypass, output
Battery
A
B
C
N
E
+
-
6
6
6
10
6
10
10
35
PDF 文件使用 "pdfFactory Pro" 试用版本创建 www.fineprint.cn
L15K3/3
8
8
8
10
6
16
16
L20K3/3
10
10
10
16
6
16
16
L30K3/3
16
16
16
25
8
25
25
L40K3/3
20
20
20
25
10
35
35
L60K3/3
25
25
25
35
16
50
50
L80K3/3
35
35
35
50
16
70
70
L100K3/3
50
50
50
70
25
90
90
L120K3/3
60
60
60
70
25
110
110
L160K3/3
80
80
80
90
35
150
150
L200K3/3
100
100
100
150
35
180
180
L250K3/3
120
120
120
150
35
230
L300K3/3
150
150
150
180
35
275
L350K3/3
180
35
325
L400K3/3
200
35
370
6.3.2. Main circuit cable connection
G
A
B
C
N
N
Main power input
A
B
C
N
Bypass input
A
B
AC output
C
N
+
Battery
-
G
N
Before installing UPS, turn off all switches. According to left part of the above plan, A, B, C, N connect
three-phase, separately to the fire wire and middle wire of main power input; A, B, C, N on bypass connect
three-phase, separately to the fire wire and middle wire of bypass input(when one power inputs, link the
main power input and bypass input together); According to right part of the above plan, A, B, C, N connect to
three-phase, separately to the fire wire and middle wire of AC output.; E is connected to the safe protecting
ground wire; +, - are connected to the anode and cathode of battery.
6.3.3. Battery connection
1.
Before connecting battery, please check manufacturers of each battery, specifications and models,
and terminal voltage to make sure whether they are in consistent (because different manufacturers’
battery internal resistances are different. When battery pack run in series, because of uneven
voltage, the whole battery pack can be damaged; meanwhile, the old and new batteries from same
manufacturers cannot be mixed as well).
2.
The input battery voltage of UPS is voltage of battery pack in series, the labeled voltage is a
standard value, and it is the summation of all batteries’ standard values in the battery pack running
in series. For example, the standard value of a single 100AH/12VDC is 12VDC rather than
measured value. The input voltage of L10K3/3 battery is 384VDC, namely, 12VDC×32=384VDC.
3.
Series and parallel connection of battery:
When the capacity of a single battery pack meet required backup time, then all the batteries should
be connected in series; or couples of series connected batteries should be connected in parallel,
the bus voltage of battery must be the same when connecting in parallel, capacity is equivalent to
36
PDF 文件使用 "pdfFactory Pro" 试用版本创建 www.fineprint.cn
the summation of parallel battery pack.
Input
Input
UPS
Connection
Connection
UPS
Anode
Cathode
When connecting in series, the first battery’s anode is connected to the second battery’s cathode, the
second battery’s anode is connected to the second battery’s cathode, and so is the other battery’s
connection.
When connecting in parallel, the battery pack’s anodes are connected together; the battery pack’s
cathodes are connected together.
Ø
Open the chassis of battery box connect according the above methods.
Ø
Install battery on the appropriate position; connect battery wire rightly according to the above
connecting methods.
Ø
Connect the cable of battery to UPS’s battery terminal board.
6.3.4. RS232 cable connections
Connect one end of DB9 signal cable which is distributed from UPS to the serial port of computer’s DB9,
connect the other end to the interface of UPS’s RS232. If the distance is too far to connect, then you can
increase the standard length of communication wire of D89, however, it should not exceeded 30 meters, or it
can not communicate normally.
6.3.5. RS485 cable connection
According to UPS’s A, B and G, use communication wires to connect the interfaces of computer's RS485
and UPS’s RS485. The longest linking distance should be less than 4,000M, or it can not communicate
normally.
6.3.6. Connection method of SNMP card
The international standard of producing twisted-pair: EIA/TIA568A and EIA/TIA568B. Both ends of plug
should follow 568 A or 568 B standard.
Network cable production:
(1) Cut: use knife-edge scissor of press line pliers to cut network cables with appropriate length.
(2) Peel: use knife-edge of press line pliers to shear cables orderly, then put wire heads on peeling blade,
make wire heads touch baffle, then slightly clench pliers and slowly rotate it, let knife rip off the protecting
rubber skin of twisted pair, peel off the skin(note: strip as long as thumb’s length).
37
PDF 文件使用 "pdfFactory Pro" 试用版本创建 www.fineprint.cn
【Tip】: The length between baffle and peeling blade of press line pliers usually is just same length as plug’s,
which can effectively avoiding peeling too long or too short. If peel too long, the network cable will look ugly,
meanwhile, it can not be stuck by plug, the connection point can easily get to loose; if peel too short,
because of the existing of protecting skin, cables become too thick to plug into the bottom of plug, which
results in plug can not contact perfectly with cable cores. Production can not be success as well.
(3) Sort: after removing outer protecting skin, you can see four pairs of twisted-pair’s eight cores, and each
pair’s color is different. Each pair of two allied core wires consists by one core wire stained with a
corresponding color and one core wire stained with white and little corresponding color. The colors of four
panchromatic core wires are: brown, orange, green and blue. Each pair is entangled with each other. When
produce network cable, these four pairs of eight thin cores should be disassembled, tidied up, straightened
and sorted in sequence according to the following wire order regulation.
Put the side with plastic spring of plug down, up the side with pin, make the end with pin towards to the
opposite direction of yourself, the end with square hole towards to yourself, simultaneously, the far left is the
first wire, the far right is the eighth wire, followed by the remaining order.
(Standard)
T568A
T568B
Alignment
1
White
green
White
orange
2
3
4
Green
White orange
Blue
Orange
White green
Blue
Same alignment
Same alignment
with 6
5
White
blue
White
blue
6
Orange
Green
7
White
brown
White
brown
8
Brown
Brown
Same
Same alignment
alignment with
Same alignment
3
T568A standard and T568B standard wire order table
(4) Cut: straighten wires as right as possible (do not wrap), press to flat (do not overlap), tighten and tidy
up (lean against each other in one direction), and then use press line pliers to cut flush. In this way, after
inserting twisted pair into plug, each wire can well contact plug’s pin, which avoids bad connection. If the
former skin is peeled too long, then it can be cut shorter at this stage. Except outer insulation skin, the
remained part is about 14mm, which length can rightly insert each thin wire into corresponding trucking. If
this part is too long, for one hand it can increase mutual crosstalk, because allied wires ate no longer twist
together, for the other hand, owing to the plug can not pin the sheathes, cables derail from plug, which can
cause bad connection or even Interruption.
(5) Insert: use one hand’s thumb and middle finger to nip plug, the plastic shrapnel of plug faces downside,
its pin towards the opposite direction of yourself, using your forefinger to hold it. Other hand nips the rubber
skin which is outside of twisted pair, slowly inserts eight wires along RJ-45’s eight truckings with proper force
until reaching the top of trucking.
(6) Press: when all wires are in place, and all wires’ sequence is correct after thoroughly checking over
through connectors, then you can use press line pliers to make RJ-45 plug. Push one head of RJ-45, from
the side without teeth, into the trough of press line pliers, then clench pliers at full tilt(if your strength is not
enough, you can use both hands to press), press pins which are prominent outside into plug.
Network cable connection:
38
PDF 文件使用 "pdfFactory Pro" 试用版本创建 www.fineprint.cn
One end of a well pressed network cable connects to UPS’s SNMP card, the other one connects to the
switch or hub of LAN (local area network).
6.4. Connection inspection
After connecting all the wires and cables, check the following items:
Whether all of battery cables are connected correctly and in a good contacting status, whether all of input,
output, grounding wires have been properly connected to corresponding connection field on equipment,
whether UPS's input voltage, frequency, and phase sequence are consistent with UPS’s bypass voltage,
frequency, and phase sequence.
7. Operation and management
7.1. Preparations before turning on the machine
Test tool
Millimeter
Ammeter
Computer for communication test
Load (actual load)
7.2. The first time turn on the UPS
Wiring inspections
Check the input line to make sure all of them meet the requirements.
Input supply test
Use millimeter to test input voltage and frequency, to make sure whether they are in the input range.
Load test
Check the output load by millimeter to make sure if there is short circuit. And calculate the loads.
Battery polarity test
Check whether the polar is right or not by millimeter and the voltage of battery belongs to the input range
of UPS.
7.3. Testing in AC mode operation
Procedures of turning on the machine
Turn off the bypass switch and output switch and check whether the machine bypass is in the normal
condition.
Turn off the rectification switch; the rectification will be done automatically. After that low-voltage battery
indicator light will extinguish and inverter indicator will lighten, automation will become inverter running.
Turn off the battery switch, and battery will be tested by UPS. After that battery will be rectified again,
when it becomes normal, use the concurrent ammeter to test charging current.
7.4. Testing in battery mode operation
Turn off the rectifier switch to simulate the inversion of battery and check whether the supply is normal.
39
PDF 文件使用 "pdfFactory Pro" 试用版本创建 www.fineprint.cn
Close the rectifier switch to change the inverter of city electricity and charge the battery.
7.5. Daily operation management
7.5.1. The opening procedures of UPS
Although the battery switch is equipped in UPS, it still must follow the following steps to open UPS:
If the commutate switch does not be turned on with 10 seconds after UPS got the power, it will alarm for
wrong phase order. Please press F1 to cancel the alarm and meanwhile operate the UPS starting program
as above.
7.5.2. No AC input, the battery is in inverter mode
Turn on the battery switch and press the BAT button on the panel. The panel lamp will lights and UPS will
be in inverter running mode. Turn on the output switch after normal inverter then it can be add load.
7.5.3. Urgency turning off program
This program only suggested to be started when fire, electricity attaching and electricity is arcing.
Cut down all the switches.
8. Daily maintaining
8.1. Preventing maintaining
——the preventing maintaining will protect the UPS liability and long term performance.
l
Regularly check whether any of the UPS cables insulation parts is aging or broken. If yes it should be
maintained immediately to avoid any safety accident.
l
UPS; Check whether the intakes are jam. There should be enough heat sink room, otherwise the
UPS lifetime will be shorten even the UPS will be damaged.
l
Use the dry dishcloth (do not use wet dishcloth or liquid cleaner) to clean the UPS external dust.
Should be processed without wires nearby to avoid electrical shock.
l
Check whether all the lamps work normally. The lamps status should be accordant with LCD
displaying status.
l
Check whether LCD displays normally, enquiry UPS incidents records and analysis the power supply
status.
l
AC work status testing.
l
Battery inverter running testing.
l
Battery charging testing.
l
Check whether all the fasteners are fixed and whether the wires are over hot with the power cut off.
8.2. Battery maintaining
——good maintaining towards the battery could prevent any loss when electricity is cut down
accidentally or battery is low.
l
Open the battery cabinet to check whether the battery liquid is leaked and whether the port
40
PDF 文件使用 "pdfFactory Pro" 试用版本创建 www.fineprint.cn
connection is loose.
l
Use the millimeter to test whether each battery voltage is accordant with each other. If any battery
voltage is abnormal, it should be replaced immediately in order to avoid the damage of whole battery
group.
8.3. The explanation of alarm
l
Alarm 1: switch status abnormal
If buzzer alarms and the LCD displays switch are abnormal, please check the following:
1. Rectifier switch is turned off: the LCD displays
and if changed to
please check whether
the rectifier’s switch is off automatically. If switch off please check whether there is output overloaded or
short circuit. Switch the LCD screen to output menu to examine the output circuit, if displayed data are within
prescribed range please re-start rectifier switch. The alarm will be cleaned automatically. The LCD
displays
and if change to
, the UPS gets right.
2. Bypass switch is turned off: the LCD displays
and if changed to
please check whether
the bypass is switched off automatically. If switch off please check whether there is output overloaded or
short circuit. Switch the LCD screen to output menu to examine the output circuit, if displayed data are within
prescribed range please re-start bypass switch. The alarm will be cleaned automatically. The LCD displays
bypass status change from
to
, the UPS gets right.
3. Battery switch is turned off: the LCD displays
and if changed to
please check whether the
battery’s switch is off automatically. If switch off please check whether there is output overloaded or short
circuit. Switch the LCD screen to output menu to examine the output circuit, if displayed data are within
prescribed range please re-start battery switch. The alarm will be cleaned automatically. The LCD
displays
and if change to
, the UPS gets right. Check the LCD battery displaying column for the
battery voltage and charging circuit. They should be accord with battery capacity’s setting.
4. Output switch is turned off: the LCD displays
and if changed to
please check whether the
output’s switch is off automatically. If switch off please check whether there is output overloaded or short
circuit. Carefully check the load and after confirm it is normal please re-turn off the output switch. Switch the
LCD screen to output menu to examine the output circuit, if displayed data are within prescribed range
please re-start rectifier switch. The alarm will be cleaned automatically. The LCD displays
change to
and if
, the UPS gets right.
5. Breaker switch is turned off: the LCD displays
and if changed to
please check whether
the commutate switch is normal. If it is normal please press F1. After cleaning the alarm please switch to
inverter column and press the F2 on the panel to check whether inverter works normal. If it is also normal it
is the problem of the breaker. Please replace the breaker.
l
Alarm 2: input error
When the buzzer alarms 1 second with 3 seconds intermission, please check:
1. Input phase voltage is not within 165-275VAC range
2. Input frequency is not within 47.5-52.5Hz range
3. Commutate switch is not turned on.
41
PDF 文件使用 "pdfFactory Pro" 试用版本创建 www.fineprint.cn
4. Bypass switch is not turned on
l
Alarm 3: wrong phase order
If buzzer alarms please check the following:
1. Main input power error or commutate input switch is cut down
2. Input main phase order errors
3. Bypass input phase order errors
4. Main power input some of the phase fault
l
Alarm 4: low battery voltage
If buzzer alarms 1 second with 1 second’s intermission please check:
1. Low battery voltage
2. The battery running time is less than set schedule time
l
Alarm 5: inverter running errors
If buzzer alarms please check:
1. The loose connection of the inverter part leads to its abnormal work
2. Breaker is cut off and there is no AC input in the inverter
3. Inverter output is short circuit or output overload
4. Inverter output voltage beyond the prescribed range
5. Transmission errors
A. Connection cable between display panel and main panel leads to abnormal communication.
B. Main panel works abnormal and the display panel can not receive the data back from it. Please check
whether the connection wires of the main panel is loose or the MCU of mail panel connect bad.
l
Alarm 6: UPS overload
Buzzer alarms 3 seconds with 1 second’s intermission, and the overload lamp on the panel is lighted. It
means the load power is bigger than rating output power, that is, the percentage value is bigger than 100%.
When overload peak value is too big the UPS alarms. When UPS alarms it need to lessen the load capacity.
Otherwise the UPS will automatically switch to bypass power supplying, time span is calculated accord to
overload value’s inverse ratio.
l
Alarm 7: temperature error
When buzzer alarms please check the following:
1. Cabinet airway is jam and can not
2. The installation environment’s temperature is too high and beyond the machines. It protects itself.
3. Heat sink fan does not work, which leads to too hot power part.
l
Alarm 8: system error
42
PDF 文件使用 "pdfFactory Pro" 试用版本创建 www.fineprint.cn
When buzzer alarms please check the following:
1. Loose main board connection cable leads to abnormal working
2. Main board setting error leads to wrong MCU receiving data.
3. Low battery voltage.
4. Power board abnormality leads to controlling circuit abnormal.
l
Alarm 9: commutate error
Bypass voltage error or bypass fuse SCR error, alarming when:
1. Bypass input voltage error
2. Bypass switch input switch break up
3. Bypass SCR fuse break up or be burned because of short circuit.
9. Dispose of abnormal
* On-off status abnormal
On-off status abnormal
1、Checking whether the rectifier switch damage & the
connection reliable
2、Checking the O/P current, overload and short circuit
Cut off
Rectifier
3、Checking charge voltage and current
switch
4、Testing whether contact single normal
Turn on
1. Checking whether the bypass switch damage & the
connect reliable
Rectifier
2. Testing output current, overload and short circuit
switch
Cut off
3. Testing whether the contact normal
Turn on
1. Checking whether the output switch damage & the
connect reliable
Rectifier
switch
2. Testing output current, overload and short circuit
Cut off
3. Testing whether the contact normal
1. Checking whether the battery switch damage & the
connect reliable
2. Checking the output current, overload and short
Rectifier
switch
circuit
Cut off
3. Checking whether the battery normal
4. Checking whether the contact normal
Turn on
43
PDF 文件使用 "pdfFactory Pro" 试用版本创建 www.fineprint.cn
1. Checking whether the inverter damage & the
Rectifier
switch
connect reliable
2. Checking the output current, overload and short
Cut off
circuit
3. Checking whether the battery normal
4. Checking whether the contact normal
Turn on the switch,
restart the UPS
*Input abnormal
Input abnormal
1. Checking whether the input wires reliable and
Input phase
reasonable
Abnormal
2. Checking whether the input phase and the phase
sequence
sequence correct
Turn on
Abnormal
1. Input frequency within the rated range
Input
2. Change or replace the input power
frequency
Turn on
Input voltage
Abnormal
1. Input voltage within the rated range
2. Change or replace the input power
Turn on
Input current
date
Abnormal
1. Checking whether the sampling single connection
reliable. Also checking the insulation
2. Checking the adjusting whether the varistor
excursion
Normal
3.
Checking
whether
the
connector
components on the circuit reliable
Restart function recover
* Phase sequence not correct
44
PDF 文件使用 "pdfFactory Pro" 试用版本创建 www.fineprint.cn
of
insert
Wrong phase
sequence
Cut off
Rectifier
1. Checking the O/P current, over load and short circuit
2. Turn on the rectifier witch
switch
Turn on
1. Input phase sequence not correct
Input phase
2. Input lack phase
Abnormal
3. Replace phase sequence
sequence
Normal
1. Checking whether the sampling single connection
Abnormal
reliable. Also checking the insulation
Input display
2. Checking the adjusting whether the varistor
date
excursion
Normal
3.
Checking
whether
the
connector
of
insert
components on the circuit reliable
Restart function recover
*Battery low voltage
Battery low voltage
The wires connection in
1. Cut off battery, fasten all fasteners
Cut off
2. Turn on the battery switch
good condition
Turn on
Abnormal
1. Battery damage or leakage
Battery
2. Battery failure or low capacity
3. Replacement battery
Normal
Abnormal
1. Frequently AC failure, battery not completely charge
Charger
2. Battery capacity not setting right, charge current not
right
3. Charger failure, battery not charge
Normal
45
PDF 文件使用 "pdfFactory Pro" 试用版本创建 www.fineprint.cn
Restart function recover
*Inverter failure
Inverter failure
Cut off
1. Checking the output current, overload and short
Output load
circuit
2. Turn on the rectifier
Turn on
Abnormal
1. Cut whether all the power connection reliable; also
Connection
checking the insulation
wires
2. Fasten all fasteners
Normal
3. Connection the power
Abnormal
1. Checking whether the sampling single connection
Inverter display
reliable. Also checking the insulation
date
2. Checking the adjusting whether the varistor
excursion
Normal
3.
Checking
whether
the
connector
of
insert
components on the circuit reliable
Restart function recover
*Output overload
Output overload
Output load
Abnormal
1. Checking output current or short circuit
2. Reduce the output load
Normal
Abnormal
1. Cut whether all the power connection reliable; also
Output
checking the insulation
display date
2. Fasten all fasteners
3. Connection the power
Normal
Restart function recover
46
PDF 文件使用 "pdfFactory Pro" 试用版本创建 www.fineprint.cn
*Temperature
Temperature failure
Environment
Abnormal
1. Checking the hot fountain, far away hot fountain
temperature
2. Reduce the circumstance temperature,change
the working temperature
Normal
Inverter
Abnormal
1. Checking the heat sink intake, make sure good
ventilation conditions
connector
2.
Reduce
the
load,
reduce
the
contactor
temperature
Normal
3. Change the environment temperature
Restart function recover
*Transportation failure
Transportation failure
Communicati
Abnormal
1. Checking the connection wires between display
on wires
board and he main board connection
2. Replacement the connection port
Normal
Abnormal
1. Checking whether the connection of the MCU in
Control circuit
good condition
2. Checking whether the connection of the main
board in good condition
Normal
3. Replacement the connection port
Restart function recover
10. Transport requirements
10.1. Transport marks
47
PDF 文件使用 "pdfFactory Pro" 试用版本创建 www.fineprint.cn
UP
Frangible
No hook
No rain
10.2. Handling and shipping
10.2.1. Forklift handling
Forklift
10.2.2. Crane load and unload
Hook
UPS
10.2.3. Transport
Put the packed machine into the carriage stably and fix it with cord in case of any vibration of the vehicle.
Although there is anti-vibration of the box designed, please surely make some anti-vibration and drive slowly
when in the bumpy road.
48
PDF 文件使用 "pdfFactory Pro" 试用版本创建 www.fineprint.cn
11. Packing list
S/N
Name
Qty/piece
1
UPS
1 pc
2
Manual
1 pc
3
Qualification
1 pc
4
Installation guider
1 pc
Notice
5
6
If can not understand the manual or any more detail please contacted the distributor or our company. We
will zealously provide our service.
Notice: Any changing of the manual will not be informed specially.
49