EVC302 Series SigTEL Type B Outstation Manual

EVC302 Series
SigTEL Type B Outstation Manual
IMPORTANT
THIS SECTION MUST BE READ PRIOR TO THE INSTALLATION / MAINTENANCE OF THIS PRODUCT
This equipment must only be installed and maintained by a suitably skilled and technically competent person.
No responsibility can be accepted by the manufacturer or distributors of this product for any misinterpretation
of an instruction or guidance note or for the compliance of the system as a whole.
Emergency voice communication system design is beyond the scope of this document. An understanding of
system components and their use is assumed.
Overview
Emergency voice communication system Type B outstations are normally used to allow communication
between disabled refuges and management at a control point.
Building regulations Approved Document B says that some people may not be able to use stairways without
assistance and that for them, evacuation involving the use of refuges on escape routes and either assistance
down (or up) stairways, or the use of suitable lifts, will be necessary.
What are refuges and where are they required?
Refuges are relatively safe waiting areas for short periods. They are not areas where disabled people should
be left alone indefinitely until rescued by the fire and rescue service, or until the fire is extinguished.
In phased evacuation the first people to be evacuated are all those of reduced mobility and those on the
storey most immediately affected by the fire.
Refuges should lead directly to a safe route to a storey exit, evacuation lift or final exit, thus being a temporarily safe space for disabled people to wait for assistance for their evacuation.
A refuge should be provided for each protected stairway allowing exit from each storey, except storeys consisting exclusively of plant rooms.
Refuges should not be confused with “Places of relative safety” - see BS 5588-8 & BS 5839-9:2003 for details.
Location
Type B outstations should normally be mounted 0.9 to 1.2 metres above the floor in an easily accessible, well
illuminated and conspicuous position free from obstruction.
As far as practicable, outstations in buildings should be located where background noise is normally low
[preferably not more than 40 dBA]. Where there is a higher level of background noise, the installation of an
acoustic hood around the outstation might help to reduce the effect of background noise to an acceptable level.
SigTEL
Emergency Voice
Communication System
Approved Doc. No. DAU0302000 Rev 3
1 of 3
Cabling
Use two-core 1.5mm2 enhanced fire resistant cable up to 1000 metres from the exchange. Other cables may
work but will not comply with the recommendations of BS 5839-9.
Installation
EVC302F - Handsfree duplex EVC outstation, stainless steel, flush mounting
EVC302S - Handsfree duplex EVC outstation, stainless steel, surface mounting
EVC302GF - Handsfree duplex EVC outstation, mild steel (green), flush mounting
EVC302GS - Handsfree duplex EVC outstation, mild steel (green), surface mounting
All units are supplied complete with an identical back box that should be fitted to the wall using suitable fasteners. The back box has 20 mm knock-outs at the top and bottom. Gland the cable correctly and connect a
sleeved earth wire to the earth stud.
Connect the line to the LINE IN +Ve and LINE IN –Ve terminals (CONN4)
When installation is complete, secure the lid using the four machine screws supplied. These have a secure
pin-hex design that requires a special Allen key (supplied).
Connections
Connecting to an induction loop system
If an audio induction loop facility is required, the outstation’s AFILS +Ve and AFILS –Ve terminals (CONN3)
should be connected to the line-level input of a suitable induction loop amplifier. The induction loop should
be located adjacent to the outstation so that it covers the immediate area of the outstation adequately.
Interfacing to a disabled person toilet alarm system
NC951 Toilet Alarm
EVC302
(or other controlling
Disabled Refuge
The outstation can be optionally interfaced to an NC951 disabled persons
device with relay)
Outstation
toilet alarm system by connecting its Off-Hook and -Ve terminals (CONN1)
N/C
to the toilet alarm’s volt free relay contacts as shown, right.
COM
Activation of the NC951 (or any other controlling device with volt free
N/O
relay contacts) will have the same effect as pushing the Outstation’s
Volt free
CONN1
“push to call or answer” button. Thus, when the call is answered at the
relay contacts
exchange, a direct speech channel will be established between the
exchange and the outstation. This speech channel will remain open until
the disabled persons toilet alarm is reset as there is a definite requirement in disabled persons toilet alarm
applications for all reset functions to be carried out at source.
SigTEL
Emergency Voice
Communication System
Approved Doc. No. DAU0302000 Rev 3
2 of 3
Connecting to a CCTV camera
When the outstation is active its opto-isolated CONN5 terminals (O/P +Ve and O/P –Ve) close and can be used
to trigger a CCTV camera or recorder. The maximum current they can pass is 3 mA at 24 VDC. If this current is
exceeded, the output will be damaged. If required, an RLPV relay and a 24 VDC power supply can be used to
give two sets of volt-free change-over contacts.
Setting to work
At the exchange end, use the FITT line tester to check the cable is OK and that the outstation is working correctly. See the FITT instructions, document DCP0001518 for details. Then follow the relevant SigTEL installation
manual for SigTEL EVC or SigTEL Compact.
Shorting the “On Hook” and “-Ve” pins (PL1) effectively hangs up a call so that the engineer does not have to
return to the system controller. This is equivalent to hanging up a telephone.
The speaker’s volume can be adjusted to suit the application/background noise levels using the VR1 volume
control.
OPERATION
Calling from the outstation
Press the “Push to Call or Answer” button. The red “Call in Progress” LED will light steadily and a pulsed ringing tone is heard from the loudspeaker. When the call is answered, the ringing tone stops and two-way
speech can commence.
Calling to the outstation
If the outstation is called, the red “Call in Progress” LED pulses and a pulsed ringing tone is heard from the
internal beeper. Press the “Push to Call or Answer” button and the LED lights steadily, the ringing tone stops
and two-way speech can commence.
SPECIFICATIONS
Dimensions:
Weight:
Input voltage (from exchange):
Current consumption @ 24 VDC:
Microphone frequency response:
Loudspeaker frequency response:
Audio output level:
Switch output:
External indicators:
External controls:
Internal controls :
Security fasteners:
Back box:
Surface 240 x 160 x 53 mm; Flush 250 x 175 x 53 mm
Surface 1.3 kg; Flush 1.5 kg
10.7 VDC quiescent; 5 VDC in use
3 mA quiescent; 25 mA in use
250 Hz to 5 kHz ±3 dB
250 Hz to 4 kHz ±3 dB
0 dB (775 mV) balanced line level
Opto-isolated normally open open-collector, max 24 VDC 3 mA
Red call in progress LED
Push to Call or Answer button (Off Hook)
Loudspeaker volume
Engineer’s “On Hook” and “Off Hook” pins
4 x machine screw pin hex button head
Adaptable box AB573K-B (supplied)
Errors and omissions excepted. The manufacturer’s policy is one of continuous improvement and we reserve
the right to alter product specifications at our discretion and without prior notice.
SigTEL
Emergency Voice
Communication System
Approved Doc. No. DAU0302000 Rev 3
3 of 3