PLFY-P VBM-E
INDOOR UNIT – 4-WAY CASSETTE
The VBM 4-way cassette model offers 72
different selectable air flow configurations and
is the ideal solution for applications with high
ceilings up to 4.2 m.
1
2
3
4
5
Offset -4°
Wide air flow
Individually settable vanes
The ability to set the optimum position
for each air distribution vane ensures
superlative comfort throughout the
whole room.
Air flow distributed over a wide
area
The wide-angle outlet vents distribute
air effectively into every corner of the
room.
As well as offering different air flow delivery
modes (2, 3 or 4-way), this function also
makes it possible to select the vertical air flow
independently for each vane, to maintain a
comfortable and uniformly distributed ambient
temperature.
The outlet vents are larger than on previous
models, while the shape of the vents has
been optimised to improve ventilation over a
broader area.
V
* An air shutter (not supplied by
Mitsubishi Electric) must be installed
to permit 2 and 3-way operation.
New 4-way ceiling-mounted cassette unit
Horizontal
Fixed
Downwards
72 settable air flows
128
Individually
settable
vanes
Wide Airflow
Previous
model
Selectable 2, 3 or 4-way
operating modes
The direction of the air
flow from each individual
vane is controllable from a
wired remote control.
Illustration of multi-directional air-conditioning
Adjustable
The ability to set each single air vane to
achieve the ideal air flow for the layout
of the individual room, combined with
the wide angle outlet air flow function,
ensures uniform temperature distribution
in every room. The result is homogeneous,
comfortable air conditioning.
Automatic fan speed adjustment
Draught-free air distribution
The innovative new horizontal stream mode distributes air
horizontally without directing cooled/heated air directly onto the
persons in the air conditioned space, avoiding the perceived sense
of discomfort caused by overexposure to the air flow.
The automatic fan speed adjustment mode ensures fast,
comfortable heating as soon as heating mode is activated.
Automatic fan speed control is included in the four standard
modes “Low”, “Medium1”, “Medium2” and “High”, and ensures
faster, comfortable air conditioning by increasing the air flow speed
on activation and then reducing speed once stable comfort levels
are attained.
DRAUGHT-FREE AIR DISTRIBUTION MADE POSSIBLE WITH A
HORIZONTAL AIR STREAM
Low
Medium2
Medium1
High
Automatic
INDOOR UNITS
Condensate drain pump
The VBM series features a built-in condensate drain pump.
TECHNICAL SPECIFICATIONS
PLFYPLFYPLFYPLFYPLFYPLFYPLFYPLFYPLFYP20VBM-E P25VBM-E P32VBM-E P40VBM-E P50VBM-E P63VBM-E P80VBM-E P100VBM-E P125VBM-E
MODEL
Power
Capacity in cooling
mode *1
A single phase, 220-240V 50Hz / a single phase, 200V 60Hz
Capacity in heating
mode*1
Power consumption
Current
External finish
(Munsel No.)
Dimensions (HxLxW)
Net weight
Heat exchanger
Fan
Motor
Air filter
Refrigerant pipe
diameter
Cooling
Heating
Cooling
Heating
Unit
Grille
Unit
Grille
Unit
Grille
kW
Btu/h
kW
Btu/h
kW
kW
A
A
2,2
2,8
3.6
4.5
5.6
7.1
9.0
11.2
14.0
7500
9600
12,300
15,400
19,100
24,200
30,700
38,200
47,800
2,5
3,2
4.0
5.0
6.3
8.0
10.0
12.5
16.0
8500
10900
13,600
17,100
21,500
27,300
34,100
42,700
54,600
0,03
0,03
0.03
0.04
0.04
0.05
0.07
0.15
0.16
0,02
0,02
0.02
0.03
0.03
0.04
0.06
0.14
0.15
0,26
0,26
0.22
0.29
0.29
0.36
0.51
1.00
1.07
0,19
0,19
0.14
0.22
0.22
0.29
0.43
0.94
1.00
Galvanised steel sheet
White (6.4Y 8.9/0.4)
mm
mm
kg
kg
258x840x840
298x840x840
35x950x950
22
23
27
6
Cross fins (sheet aluminium fins and copper piping)
Type x Quantity
Air flow*2
Static ext.l pressure
Type
Power output
Turbo fan x 1
m3/min
l/s
cfm
Pa
12.5-12-11.5-11
11-12-13-14
12-13-14-16
208-200-192-183
183-200-217-233
200-217-233-267
441-424-406-388
388-424-459-494
424-459-494-565
14-15-16-18
16-18-20-22
21-24-27-29
22-25-28-30
233-250-267-300 267-300-333-367 350-400-450-483 367-417-467-500
494-530-565-636 565-636-706-777 742-848-953-1024 777-883-989-1059
0
DC motor
kW
0.050
0.120
Polypropylene honeycomb
Gas (swaged)
mm
ø12.7
ø12.7 / ø15.88
(Compatible)
Liquid (swaged)
mm
ø6.35
ø6.35/ ø9.52
(Compatible)
Local drain pipe diameter
Sound pressure*2*3
ø15.88
ø15.88 / ø19.05
(Compatible)
ø9.52 (ø3/8)
O.D 32(1-1/4)<VP-25>
dB(A)
30-29-28-27
27-28-29-31
27-28-30-31
28-29-30-32
30-32-35-37
34-37-39-41
35-38-41-43
*1 For heating/cooling capacity, the maximum value with the unit operating in the following conditions is given.
Cooling: indoor 27°C (81°F) DB/19°C (66°F) WB, outdoor 35°C (95°F) DB. Heating: indoor 20°C (68°F) DB, outdoor 7°C (45°F) DB/6°C (43°F) WB.