User Manual
Uninterruptible Power System
1700 Series
Single Phase – 1.5/2.0/2.4 kVA
1
TOSHIBA
2
TOSHIBA
IMPORTANT NOTICE
The instructions contained in this manual are not intended to cover all of
the details or variations in equipment, nor to provide for every possible
contingency to be met in connection with installation, operation, or
maintenance. Should further information be desired or should particular
problems arise which are not covered sufficiently for the purchaser's
purposes, the matter should be referred to the local Toshiba sales office.
The contents of this instruction manual shall not become a part of or
modify any prior or existing agreement, commitment, or relationship. The
sales contract contains the entire obligation of Toshiba International
Corporation's UPS Division. The warranty contained in the contract
between the parties is the sole warranty of Toshiba International
Corporation's UPS Division and any statements contained herein do not
create new warranties or modify the existing warranty.
Any electrical or mechanical modifications to this equipment,
without prior written consent of Toshiba International Corporation
will void all warranties and may void UL/CUL listing. Unauthorized
modifications also can result in personal injury, death, or
destruction of the equipment.
UNINTERRUPTIBLE POWER SUPPLY
If additional information or technical assistance is required beyond what
is included in this manual contact Toshiba’s marketing department by
calling toll free (800) 231-1412, by e-mail at toshibaups@tic.toshiba.com,
or write to: Toshiba International Corporation, 13131 W. Little York
Road, Houston, TX 77041-9990.
Please complete the following information for your records and to remain
within this equipment manual:
Model Number:
Serial Number:
Date of Installation:
Inspected By:
January, 2004
Part no. 50124-001
3
TOSHIBA
TABLE OF CONTENTS
SECTION
PAGE
Disclaimer................................................................................................ 3
Table of Contents.................................................................................... 4
General Safety Instructions ................................................................... 5
Important Safety Instructions............................................................. 6-7
Inspection/Installation ............................................................................ 8
Inspection of the New UPS..........................................................................................8
Installation Precautions ...............................................................................................8
Operating Precautions.................................................................................................8
External Layout ....................................................................................... 9
Electronics Module......................................................................................................9
Battery Modules ........................................................................................................10
UPS Connections.................................................................................. 10
Standard Module Connections ..................................................................................10
Operating the UPS ................................................................................ 12
Display Panel Layout.................................................................................................12
Starting the UPS System...........................................................................................12
Starting when AC Power is Available.........................................................................12
Starting on DC Power................................................................................................13
Stopping the UPS......................................................................................................13
UPS Display Status and Operating Condition............................................................14
Battery Backup Time .................................................................................................16
Load Shed Function ..................................................................................................16
Battery Recharge Time .............................................................................................16
Battery Check Function .............................................................................................17
The Function Control Button......................................................................................17
Fixed Frequency Mode..............................................................................................20
Adding Additional Battery Modules............................................................................20
Other Option Modules ...............................................................................................21
Communication Interface..................................................................... 22
Remote Contacts ......................................................................................................22
RS-232C ...................................................................................................................22
Option Card Slot........................................................................................................22
Troubleshooting.................................................................................... 22
Warning/Fault Modes ................................................................................................22
Warnings...........................................................................................................23
Faults ................................................................................................................26
Storage of UPS Equipment .................................................................. 29
Disposal ....................................................................................................................29
Preventative Maintenance/Parts Replacement .................................. 30
Preventative Maintenance .........................................................................................30
Parts Replacement....................................................................................................30
Appendices............................................................................................ 31
A:
B:
C:
D:
E:
F:
G:
Specifications ......................................................................................................31
Fan Speed Control ..............................................................................................32
System Overload Rating......................................................................................33
Parallel Operation ...............................................................................................34
Bypass Undervoltage / Overvoltage ....................................................................35
Unit Configuration Options ..................................................................................36
Weights and Dimensions.....................................................................................37
Warranty Policy..................................................................................... 38
4
TOSHIBA
GENERAL SAFETY INSTRUCTIONS
Warnings in this manual appear in two different ways:
1)
Danger warnings - The danger warning symbol is an exclamation mark
enclosed in a triangle that precedes the large bold letters spelling the
word "DANGER". The Danger warning symbol is used to indicate
situations, locations, and conditions that exist and can cause serious
injury or death:
DANGER
2)
Caution warnings - The caution warning symbol is an exclamation mark
enclosed in a triangle that precedes the large bold letters spelling the
word "CAUTION". The Caution warning symbol is used to indicate
situations and conditions that can cause operator injury and/or
equipment damage:
CAUTION
Other warning symbols may appear along with the Danger and Caution
symbol and are used to specify special hazards. These warnings
describe particular areas where special care and/or procedures are
required in order to prevent serious injury and possible death:
1)
Electrical warnings - The electrical warning symbol is a lightning bolt
mark enclosed in a triangle. The electrical warning
symbol is used to indicate high voltage locations and
conditions that may cause serious injury or death if
the proper precautions are not observed.
2)
Explosion warnings - The explosion warning symbol is an explosion
mark enclosed in a triangle. The explosion warning symbol is
used to indicate locations and conditions where molten,
exploding parts may cause serious injury or death if the
proper precautions are not observed.
5
TOSHIBA
IMPORTANT SAFETY INSTRUCTIONS
SAVE THESE INSTRUCTIONS.
This manual
contains important instructions for the 1.5 and 2.4kVA 1700 Series
Toshiba UPS. These instructions should be followed during the
installation and maintenance of the UPS and its batteries.
¾
¾
¾
The maximum ambient temperature in which this UPS unit should
be operated or stored is 104 °F (40 °C).
The batteries for the Toshiba 1700 Series 1.5 and 2.4kVA UPS are
housed in a self-contained battery module. This module should not
be opened under any circumstances. To replace the batteries, a
new module should be obtained from your local Toshiba
representative, or contact the Toshiba UPS marketing department
toll-free at (800) 231-1412.
When changing battery packs, be sure to use the proper model unit.
CAUTION
Misuse of this equipment could result in human
injury and equipment damage. In no event will
Toshiba Corporation be responsible or liable for
either indirect or consequential damage or injury
that may result from the use of this equipment.
Do not dispose of the battery module
in a fire. The batteries inside may
explode.
DANGER
CAUTION
Do not open or mutilate the battery module.
Released electrolyte is harmful to the eyes and
skin, and could be toxic.
CAUTION
This unit contains sealed lead acid batteries.
Lack of preventative maintenance could result in
batteries exploding and emitting gasses and/or
flame.
CAUTION
Failure to replace the battery pack in
accordance to the maintenance schedule may
cause the batteries inside to crack, possibly
releasing electrolytes from the battery, and
resulting in secondary faults such as odor,
smoke and fire.
6
TOSHIBA
INSTRUCTIONS IMPORTANTES
CONCERNANT LA SÉCURITÉ
CONSERVER CES INSTRUCTIONS. Cette notice
contient des instructions importantes concernant la sécurit.
ATTENTION
Une batterie peut présenter un risque de
choc électrique, de brûlure par transfert
d’énergie.
ATTENTION
Pour le remplacement, utiliser le même
nombre de batteries du modèle suivant.
ATTENTION
L’élimination des batteries est
réglementée. Consulter les codes
locaux à cet effet.
7
TOSHIBA
Inspection/Installation
Inspection of the New UPS Equipment
Upon receipt of the UPS, a careful inspection for shipping damage
should be made.
After Unpacking:
1) Check the unit for loose, broken, bent or otherwise damaged
parts. If damage has occurred during shipment, keep all original
packing materials for return to shipping agent. Warranty will not
apply to units damaged during shipment.
2) Check to see that the rated capacity and the model number
specified on the nameplate conform to the order specifications.
Installation Precautions
CAUTION
1) Install the unit in a well ventilated location; allow at least 10 cm
(4 inches) on all sides for air ventilation and for maintenance.
2) Install the unit in a stable, level, and upright position that is free
of vibration.
3) Install the unit where the ambient temperature is between 32°
and 104°F (0° and 40°C).
4) Do not install the UPS in areas that are subject to high humidity.
5) Do not install the UPS in a location that will cause direct sunlight
to shine on the unit.
6) Do not install the UPS in areas that are subject to contamination
such as high levels of airborne dust, metal particles, or
flammable gas.
7) Avoid installation near sources of electrical noise. Always make
sure that the unit earth ground is intact to prevent electrical
shock and to help reduce electrical noise.
8) Do not install where water or any foreign object may get inside
the UPS.
9) This UPS generates and can radiate radio-frequency energy
during operation. Although RFI noise filters are installed inside
the unit there is no guarantee that the UPS will not influence
some sensitive devices which are operating close by. If such
interference is experienced, the UPS should be installed farther
away from the affected equipment and/or powered from a
different source than that of the affected equipment.
Operating Precautions
CAUTION
1) The UPS should not be powered up until this entire manual has
been reviewed.
8
TOSHIBA
2) The input power source voltage and frequency must be within
the allowable range as specified in appendix A. Voltages and
frequencies outside of the permissible tolerance range may
cause internal protection devices to activate.
3) The UPS should not be used with a load whose rated input is
greater than the rated UPS output.
4) Do not use the UPS to provide power to motors that require high
starting current or that require a long starting time such as
vacuum cleaners and machine tools (unless appropriate sizing is
done by a Toshiba applications engineer, or other qualified
personnel).
5) Do not insert metal objects or combustible materials in the unit's
ventilation slots.
6) Do not place, hang, or paste any objects on the top or on the
exterior surfaces of the UPS.
External Layout
Electronics Module
Figure 1
Electronics
Module
Layout
9
TOSHIBA
Battery Module
Figure 2
Battery Module Layout
UPS Connections
Standard Module Connections
The illustration on the following page shows the proper assembly of
the two modules that make up the standard unit. If additional battery
modules are being installed with the standard unit see page 20. For
all other option modules see page 21.
Note: No more than three modules should be stacked on top of each
other for any configuration.
10
TOSHIBA
Standard Module Connections (cont’d)
If two modules are to be stacked on top of each other, they should
be interlocked to reduce the chances of the top module being
knocked over. Modules do not have to be stacked for the system to
operate. The following steps will guide the user through the process
of assembling and connecting the modules.
Step 1: Place the electronics module on top of
the battery module so that the six round feet on
the bottom of the electronics module fit into the
matching keyhole slots on the top of the battery
module.
Step 2: Slide the
upper unit forward.
This will cause the
two units to lock
together. In order to unlock the units, lift
up on the top module, and slide it back.
This will release the interlock (figure 3).
Step 3: Connect the input power cord
(figure 4) to the AC power source. If no
AC power source is available go to step 5.
Figure 3
Module Interlock
Step 4: Switch the input
breaker to the on position
(figure 1, page 9). Please note
that a battery fault will occur.
Step 5: Plug the battery cord
coming from the battery pack
into the blue battery plug
located on the back of the
electronics module (figure 4).
This will clear the fault from
step 4. Attention: If the
battery cord is not plugged into
the battery plug the UPS will
not be able to provide backup
power in the event of a loss of AC input power.
Figure 4
Power Connections
CAUTION Battery modules present a lifting hazard. The
battery module for this unit weighs approximately 60 lbs.
Two person lift is required to avoid injury.
11
TOSHIBA
Operating the UPS
Display Panel Layout
Function
Control
Button
Startup on
Battery
Button
ON LINE (green lamp)
Lights green when the UPS’s inverter is
supplying power to the load.
AC INPUT (green lamp)
Lights green when normal AC input power
is being supplied to the UPS unit.
WARNING/FAULT (red lamp)
Lights red when the UPS unit is
experiencing an abnormal condition.
BATTERY (red lamp)
Lights red to indicate that a condition exists
that is affecting the batteries.
Starting the UPS System
Once the modules have been connected as shown in the preceding
section (UPS Connections, page 10) the UPS system is ready to be
started. There are two ways to start the system: from AC input
power (if present) or from batteries. If not already done, switch the
input breaker on (figure 1, page 9). If the “AC Input” LED is lit,
proceed on to “Starting when AC power is available”. If the LED is
not lit, there is no AC power available. If the unit is to be started
when AC power is not available proceed to “Starting on DC power.”
Starting When AC Power is Available
If the system is being started with AC input power the system is
started by switching the RUN/STOP switch to the RUN position
(RUN = I, STOP = 0). When the RUN/STOP switch is in the RUN
position both the “AC Input” and the “On Line” LEDs should be lit.
When the unit is started with AC input power it is advisable to allow
time for the batteries to fully charge before any load is connected
(see “Battery Recharge Time”, page 16).
12
TOSHIBA
Starting on DC Power
If no AC power source is available, or if the AC input power is
outside of the allowable range for voltage or frequency, the UPS can
be started from battery power. The length of UPS operation time on
battery power depends on the number of attached battery modules
and the amount of load the UPS is supporting. To start the UPS
from battery power follow these steps:
Step 1: Make sure the RUN/STOP switch is in the STOP position. If
the UPS is being started on DC power because the AC power is out
of range, the input breaker must be in the OFF position (figure 1,
page 9).
Step 2: Press the “Startup on Battery” button. The UPS will beep
indicating that AC power is not available and the Startup on Battery
mode has been activated.
Step 3: Switch the RUN/STOP switch to the RUN position. This
must be done within 5 seconds of the Startup on Battery mode
activation for the unit to startup using batteries.
Once the unit has started, the “On Line” LED will light, indicating that
the inverter is running and power is available at the output
receptacles. If the RUN/STOP switch is not switched to the RUN
position within those 5 seconds, the unit will return to shutdown
mode.
Stopping the UPS
There are two ways of turning the UPS off: switching from on line to
bypass mode, or completely shutting down.
Option 1: The first option is to place the UPS into bypass mode.
Bypass mode means that if there is AC power available, the UPS will
route power directly from the input source to the connected loads
without any conditioning. The UPS inverter is off during this state,
but the attached loads do not lose power during the transition. To
place the UPS into bypass mode, switch the RUN/STOP switch to
the STOP position. This mode is most often used manually during
maintenance and programming operations or automatically upon the
occurrence of an internal UPS fault. (For more information
concerning bypass mode see appendix E.)
Option 2: The other option is to turn the UPS off completely. This
means that in addition to the UPS’s inverter shutting down, all power
will be stopped to any equipment attached to the UPS. To shut
the UPS down completely switch the RUN/STOP switch to the STOP
position. Then switch the input breaker off (figure 1, page 9). Once
the input breaker has been switched off, all the LEDs should turn off.
(If the RUN/STOP switch is in the RUN position when the input
breaker is switched off, the unit will switch to battery backup mode.
The unit will continue to run for as long as the available battery
reserves can support the connected loads.)
13
14
Bypass
Battery
Backup
Normal
Operation Mode
Display State
Alarm is
off.
AC Input............ On
20% to 100%*... On
*see note 1.
*see note 2.
Alarm will
sound for
1 second
at 10
second
intervals.
Alarm is
off.
Alarm State
On Line ............. On
Battery .............. On
Backup.............. On
20% to 100%*... On
*see note 1.
On Line ............. On
AC Input............ On
20% to 100%*... On
LED State
UPS Display Status and Operating Condition
Battery backup is not
available.
The unit will return to
normal operation mode
when AC power is restored.
Notes
TOSHIBA
Display State
*see note 1.
On Line ............. On
AC Input............ On
Battery .............. On
20% to 100%*... On
LED State
Alarm will
sound for
1 second
at 10
second
intervals.
Alarm State
Parallel operation occurs when
input power is present, but
inadequate to fully power the
connected load. The batteries
are used to supplement the
AC input power. The UPS will
return to normal operation
when full input power returns.
Notes
15
Note 2: The level meter described in note 1 above also displays the remaining battery time when the unit is in backup mode. If the batteries are
fully charged when the unit switches to backup mode the 20% through 100% LEDs will light. As the batteries begin to discharge, the LEDs
starting from the top will blink rapidly then slowly and will then turn off as the battery time runs down. For example if the unit has been running on
battery power and there is 90% battery capacity remaining the 20% through 80% LEDs will be lit and the 100% LED will be blinking.
Note 1: The level meter, which consists of the LEDs labeled 20% through 150%, will light according to the current amount of load connected.
As the load exceeds one level, the next level will begin to blink, increasing the blink rate as the load increases until that full percentage is
reached. For example, if the unit is loaded to 40% of maximum output power the 20% and 40% LEDs will be lit. If another small load is added
increasing the load to 45% the 60% LED will begin to blink. If a little bit more load is added so that the total load becomes 50% the 60% LED will
blink faster. This will continue until enough load is added to equal 60% of the maximum output power at which time the 60% LED will stop
blinking and light continuously.
All other display conditions constitute either a warning or a fault condition. These conditions are explained in the section titled “Troubleshooting”
(page 22) in the charts on Warnings and Faults.
Parallel
Operation
Operation Mode
UPS Display Status and Operating Condition
TOSHIBA
TOSHIBA
Battery Backup Time
The exact amount of backup time provided will vary depending on
the UPS model being used, number of batteries, condition of the
batteries and other factors. However, the chart below gives the
times that can be expected from the standard units with batteries in
good condition. For greater backup time, an additional battery
module may be added to the standard unit. Only one additional
battery module may be added to the standard unit. For longer
runtime options contact your Toshiba sales representative or the
Toshiba marketing department at (800) 231-1412 or by e-mail at
toshibaups@tic.toshiba.com.
Table 1
Backup Time*
With 1 Battery Module
Full Load / Half Load
With 2 Battery Modules
Full Load / Half Load
1500 VA
13 min / 35 min
35 min / 90 min
2000 VA
10 min / 25 min
25 min / 60 min
2400 VA
7 min / 20 min
23 min / 50 min
UPS Model
* Times given are approximate and will vary depending on the age of the batteries, the
battery temperature, the number of previous discharges and the type of load.
Load Shed Function
The 1700 Series includes a load shed function. During battery
backup operation, this function allows the load connected to two of
the receptacles (figure 1, page 9) to be turned off in an effort to
conserve power for more critical loads. The battery level at which
these two receptacles will be turned off, or “shed”, can be set by the
user (see “The Function Control Button”, page 17). By default, this
feature is configured so that these two receptacles will remain on for
the full battery backup time available (no “shedding”)
Battery Recharge Time
The following table gives estimates on time required to recharge the
UPS’s batteries. The recharge time may vary depending on the
battery temperature, the age of the batteries, and other factors.
Table 2
Battery Recharge Time*
Unit
With 1 Battery Module
With 2 Battery Modules
1500 VA
3 ½ hours
7 hours
2000 VA
3 ½ hours
7 hours
2400 VA
3 ½ hours
7 hours
* Recharge times are to 90% full capacity.
16
TOSHIBA
Fan Speed
The 1700 Series UPS has variable speed fans. The fan speed will
vary depending on a number of factors. As the load placed on the
UPS increases the fan speed will increase. The temperature of the
environment the UPS is operating in can also cause the fan speed to
increase. (For a more detailed explanation of the variable speed fan
function refer to appendix B)
Battery Check Function
During startup the UPS will perform an automatic 'Battery Check' to
detect whether a problem exists in the battery circuit. If the batteries
pass the test, the unit will start normal operation. If a problem is
detected during the test the “Warning/Fault” LED will activate. Other
LED’s may also activate. If this occurs please refer to the
“Troubleshooting” section on page 22 for a description of the
problem and possible solutions. It is important to note that when
the UPS has detected bad batteries, the battery backup mode is
disabled. The unit will continue to operate and provide clean power;
however, since there is no battery power available, the unit cannot
provide backup power if input power is lost.
The Function Control Button
The function control button is located on the display panel (see
“Display Panel Layout”, page 12). This button is used to perform
several different UPS operations, including initiating self test,
providing programming options, and silencing the alarm. A brief
description of each function follows along with a step by step guide
to accessing each function.
1) Self-Test. In order to perform a self-test the UPS must be
operating in the normal mode (see “UPS Display Status and
Operating Condition”, page 14). To initiate the self-test simply
press and hold the Function Control button until all the LED’s
activate. The self-test also performs the same battery check
described above.
2) Alarm Silence. The alarm silence feature is used to stop the
audible alarm from sounding. Any time the audible alarm is
sounding pressing the Function Control button will silence the
alarm.
3) Programming Mode. There are three programming options:
load shed, output enable/disable after input overvoltage backup,
and reset battery installed date. In order to enter the
programming mode the UPS must first be operating in Bypass
mode without faults (see “Stopping the UPS: Option 1”, page
13). Then press and hold the Function Control button. (“Press
and hold” always means to hold until the unit gives audible
17
TOSHIBA
feedback). The unit will give an audible feedback indicating the
unit is in programming mode. (If at anytime while the UPS is in
the programming mode there is one minute of inactivity the UPS
will automatically exit the programming mode and return to
bypass operation.) What follows is a step by step guide to
navigating in the programming mode, followed by a detailed
description of each option.
A. Load Shed. The backup LED will light indicating the UPS is now
ready to make changes to the load-shed settings (see “The Load
Shed Function”, page 16 for an explanation of load shedding).
To accept this option press and hold the Function control button.
A.1 The UPS comes from the factory set so the load shed
receptacles function for the full battery backup time. The
LEDs on the right side of the display will light to indicate the
current setting for the load-shed level. For example, since
the default factory setting is for no load shed, the first time
the option is accessed no LEDs will be lit. Pressing the
button once will cause the 20% LED to light. This would
indicate that the load shed receptacles should be turned off
18
TOSHIBA
when there is 20% battery power remaining. Pressing the
Function Control button successive times will increase the
load shed level in 20% increments.
A.2 Once the option is set to the desired level, press and hold
the Function Control button. This will save the new load
shed level setting. The UPS will indicate that the value has
been stored by blinking the LEDs. After blinking the LED for
a short time the UPS will exit the programming mode and
return to bypass operation. To return the system to normal
operation switch the RUN/STOP switch back to the RUN
position.
B. Output Enable/Disable After Input Overvoltage Backup. Press
the function control button. The unit is now ready to change the
output enable/disable after input overvoltage backup option.
This is indicated by the 150% LED turning on. This setting
determines whether the UPS will go to bypass in the case of an
input overvoltage fault. To change this setting press and hold the
function control button.
B.1 This setting is set to disable output at the factory. Pressing
the function control button causes the 100% LED to light,
indicating output has been enabled. Pressing it again will
change it back to disabled and the 100% LED will go off.
B.2 Once the option is set as desired, press and hold the
function control button to save the setting. The UPS will
indicate the setting has been saved by blinking the LED(s).
The LED(s) will continue to blink for a short time after which
the UPS will exit programming mode and return to bypass
operation. To return the system to normal operation switch
the RUN/STOP switch back to the RUN position.
C. Reset Battery Installed Date. This should be done whenever a
new battery pack is installed. Press the function control button.
The unit is now ready to reset the battery installed date. This is
indicated by the Battery LED turning on. Once this mode has
been entered press and hold the function control button to reset
the battery install date to the current date. The UPS will indicate
that the date has been reset by blinking the Battery LED for a
short time after which the UPS will return to bypass operation.
To return the system to normal operation switch the RUN/STOP
switch back to the RUN position.
Note: It is not necessary that the unit’s internal clock be set to the
correct date. The UPS will track time relative to the battery installation
date. If it is desired to set the date, this can be done through remote
communication. For instructions on performing this operation refer to
either the "UPSmart" or "Remote Eye II" manual depending on the type
of remote communication being used.
19
TOSHIBA
Fixed Frequency Mode
The 1700 Series UPS has the option of operating in a fixed
frequency mode. Normally the UPS operates in the frequency autodetect mode. If a specific output frequency is required (i.e. 50Hz or
60Hz) the UPS can be set at the factory to supply the desired
frequency regardless of the input frequency (input frequency must be
within allowable limits, see Specifications on page 31). For a unit
already in use the output frequency can be set through software. For
instructions on setting the output frequency through software please
contact Toshiba at (800) 231-1412 or by e-mail at
toshibaups@tic.toshiba.com. It is important to note that when the
UPS is operating with a fixed output frequency, output is
disabled in bypass.
Adding an Additional Battery Module
Note: Only one additional battery module may be added to the
standard unit. For longer runtime options contact your Toshiba sales
representative or the Toshiba marketing department at (800) 2311412 or by e-mail at toshibaups@tic.toshiba.com. Figure 5 shows
the standard unit with one additional battery module added. To
install a second battery module follow these steps:
1) Unplug the standard battery module from the electronics module.
Unlock and remove the
electronics module from the
battery module.
2) Lock the two battery
modules together. Plug the
bottom battery module into the
top battery module.
3) Lock the electronics
module on to the top battery
module. Plug the battery
module into the electronics
module.
It is not necessary to stack the
modules for the system to
operate. Refer to the section
entitled “UPS Connections:
Standard Module Connections”
on page 10 for an explanation
of how to lock and unlock the
modules.
Figure 5
Expansion Battery Module
20
TOSHIBA
Other Option Modules
There are a number of other optional modules that can be ordered
for the 1700 Series UPS system. Table 3 shows some of the
available option modules. For information about options not listed
here contact Toshiba’s UPS Marketing Department at (800) 2311412 or by e-mail at toshibaups@tic.toshiba.com.
Table 3
Option Modules
Part No.
Description
UF1-IO-0XX-6BG
Dual Transformer Module
Single Isolation
Transformer Module
Dual Transformer Module
UF1-IO-0XX-6AA
UF1-IO-0XX-6EE
Input
Voltage
208/240V
Output
Voltage
240/120V
120V
120V
230V
230V
The XX in the part number is replaced by the kVA rating of the system (i.e. 2.4kVA = 024)
Figure 6 shows the standard 1700 series UPS with an optional input
isolation transformer module
(UF1-IO-024-6AA).
Installation of the input
transformer requires
the input power cord
from the electronics
module to be plugged
into the transformer
module. The
transformer power cord
is plugged into the
power source. This is
an example of how the
option modules work.
An instruction sheet is
included with each
module that shows how to
connect each particular
module.
Figure 6
Isolation Transformer Module
21
TOSHIBA
Communication Interface
Dry Contacts
The remote contacts interface is a standard feature. It is provided
through solid state relays with contacts through a DB9 male
connector located on the back of the UPS (refer to the
Communication Option User Manual for a more detailed description
of this option).
RS-232C
RS-232C serial communication interface is a standard feature
provided through a DB9 female connector located on the backside of
the UPS (see “Electronics Module Layout “, page 9). This interface
allows communication between the UPS and a personal computer
(see the Communication Option User Manual for a list of the data
available from the UPS via the RS-232C communication link)
Option Card Slot
The option card slot is a standard feature. An optional network
adapter card slides into the slot which is located on the back of the
electronics module (figure 1, page 9). This optional interface allows
the UPS to be monitored across the network or from any point on the
Internet (refer to the Communication Option User Manual for a more
detailed explanation of this option).
Troubleshooting
Warnings and Faults are those abnormal conditions that can occur
and could cause the unit to stop normal operation. These conditions
are detected by the protective circuitry in the unit. The UPS
“Warning/Fault” lamp will light red when a warning or fault occurs.
"Troubleshooting" involves monitoring the LED’s on the front panel
and then interpreting the readout by using the warning and fault
mode display charts that follow. Only the state of the LED’s listed in
the chart should be considered. Other LED’s might be active;
nevertheless, only those listed under the column “LED state” should
be considered when diagnosing a warning, or fault.
Warning/Fault Modes
All warnings will cause the red “Warning/Fault” LED to flash. All
faults will cause the red “Warning/Fault” LED to light continuously.
Some warnings and most faults will cause the UPS to transfer to
bypass mode. In many cases, after the condition that caused the
fault is corrected the unit will automatically transfer back to normal
mode. For those cases where the unit does not transfer back
automatically contact your Toshiba UPS service representative at 1877-867-8773 (outside the U.S. call 713-466-0277).
22
Alarm will
sound for
1/2second at
1-second
intervals.
Alarm will
sound for
1-second
at 15second
intervals.
Warning/Fault ... Flash
80% .................. Flash
Warning/Fault ... Flash
100% ................ Flash
Ambient
Over Heat
Alarm will
sound for
1-second
at 5second
intervals.
Alarm State
Current
Limit (Over
Current)
LED State
Warning/Fault ... Flash
Backup.............. Flash
Display State
Low Battery
Warning
Warnings
23
The temperature of the UPS
operating environment is too
high. Causes of this condition
include allowing the room
temperature to exceed 104°F
(40°C), a blocked vent or direct
sunlight on the unit. The unit will
transfer to bypass until the
temperature is reduced.
An output current limit warning
is typically a sign of
misapplication. The load may
not be appropriate for UPS
support. For further explanation
contact your Toshiba UPS
service representative at 1-877867-8773 (outside the U.S.
call 713-466-0277).
The batteries have less than
30% power remaining. The
warning will continue until either
the batteries become completely
exhausted or AC input power is
restored.
Description and Resolution
TOSHIBA
24
This warning will occur if the input
voltage exceeds the maximum
allowable voltage. If the unit was
online when the warning occurred it will
transfer to battery backup (see note 2).
If the unit was in bypass the output will
be turned off. The unit will return to
normal operation if input power returns
to within specified limits.
Alarm will
sound for
2, 1/2second
beeps at
10second
intervals.
Warning/Fault ... Flash
40% .................. Flash
Input Over
Voltage
(see note 1)
This warning will occur if the input
voltage drops below the minimum
allowable voltage. If the unit was
online when the warning occurred it will
transfer to battery backup. After the
backup the output will shutdown. If the
unit was in bypass the output will be
turned off. The unit will reinitialize the
startup sequence if input power returns
to within specified limits.
Alarm will
sound for
1/2second at
10second
intervals.
This warning can be caused by
the same conditions listed for
ambient overheat. Another
possible cause would be a
problem with the battery module,
which could prevent the unit
from providing backup power.
Description and Resolution
Warning/Fault ... Flash
20% .................. Flash
Alarm will
sound for
1-second
at 15second
intervals.
Alarm State
Input Under
Voltage
(see note 1)
LED State
Warning/Fault ... Flash
Battery .............. Flash
Display State
Battery
Over Heat
Warning
Warning (cont’d)
TOSHIBA
25
Display State
= LED lit continuously
Warning/Fault ... Flash
150% ................ Flash
Warning/Fault ... Flash
60% .................. Flash
LED State
Alarm will
sound for
1-second
at 15second
intervals.
Alarm will
sound for
3, 1/2second
beeps at
10-second
intervals.
Alarm State
The connected load exceeds
the UPS power rating.
Reduce the load attached to
the UPS. The unit will
automatically return to normal
operation.
The input frequency is outside
specified limits. If the unit was
online when the warning occurred
it will transfer to battery backup.
After the backup the output will
shutdown. If the unit was in
bypass the output will be turned
off. The unit will return to normal
operation if input frequency
returns to within specified limits.
Description and Resolution
Note 1: If any of these faults occur while the UPS is in online mode it will immediately transfer to backup mode. In this case the percentage LED’s
will be used to show the battery power status. To identify the fault that has occurred listen to the number of consecutive beeps. One beep
indicates an input undervoltage, two beeps means input overvoltage, three beeps is a frequency problem.
Note 2: Once the batteries are exhausted the unit will either shutdown the output, or switch to bypass according the selections set by the user (see
the section entitled “Programming Mode” part B on page 19).
= Flashing LED
Output
Overload
(see note 1)
Input
Frequency
Regulation
Warning
Warnings (cont’d)
TOSHIBA
Warning/Fault ... On
Backup.............. On
Warning/Fault ... On
20% .................. On
Battery
Shutdown
DC Bus
Over
Current
LED
Warning/Fault ... On
Battery .............. On
Display State
Replace
Battery
Fault
Faults
26
Alarm will
sound for
1/2second, at
1/2second
intervals.
Continuous
alarm
Alarm will
sound for
1/2second, at
1/2second
intervals.
Alarm State
This fault indicates an internal
problem with the UPS.
Contact your Toshiba UPS
service representative at 1877-867-8773 (outside the
U.S. call 713-466-0277).
The battery power of the unit
has been exhausted. The unit
output will shutdown.
Batteries must charge before
backup power will be
available. For charging times
see page 16.
Battery pack is not connected or
needs replacement as soon as
possible. After replacing the
batteries the battery timer must be
reset (see “The Function Control
Button”, page 17). Failure to
replace the battery pack could
result in danger to the user and
failure of the system to provide
backup power.
Description and Resolution
TOSHIBA
Warning/Fault ... On
60% .................. On
Warning/Fault ... On
80% .................. On
DC Bus
Voltage
Imbalance
Output
Under
Voltage
LED State
Warning/Fault ... On
40% .................. On
Display State
DC Bus
Over
Voltage
Fault
Faults
Alarm will
sound for
1/2second, at
1/2second
intervals.
Alarm State
These faults indicate an
internal problem with the UPS.
Contact your Toshiba UPS
service representative at 1877-867-8773 (outside the
U.S. call 713-466-0277).
Description and Resolution
TOSHIBA
27
28
= Flashing LED
= LED lit continuously
Warning/Fault ... On
150% ................ On
System
Over Heat
LED State
Warning/Fault ... On
100% ................ On
Display State
Output
Over
Voltage
Fault
Faults
Alarm will
sound for
1/2second, at
1/2second
intervals.
Alarm State
These faults indicate an
internal problem with the UPS.
Contact your Toshiba UPS
service representative at 1877-867-8773 (outside the
U.S. call 713-466-0277).
Description and Resolution
TOSHIBA
TOSHIBA
Storage of UPS Equipment.
General Guidelines
If the UPS equipment is to be stored; the following guidelines should be
used.
Avoid:
1) Storage in sites subject to extreme changes in temperature or high
humidity.
2) Storage in sites subject to exposure of high levels of dust or metal
particles
3) Storage on inclined floor surfaces or in sites subject to excessive
vibration.
Before Storing:
1) Allow UPS to be operated for 4 hrs to ensure that the batteries are fully
charged.
2) Stop the unit (see "Stopping the UPS" on page 13).
3) Place the unit's Input Breaker switch in the "off" position (see “Electronics
Module Layout”, page 9).
Storing:
1) Store within a temperature range of -20° to 40° C (-4° to 104° F). If the
UPS is stored at a temperature outside of the allowable operating range,
allow time for the unit to reach equilibrium with the ambient temperature
before starting the UPS.
2) For best results, store the UPS in the original shipping container and
place on a wood or metal pallet.
3) The optimum storage temperature is 21° C (70° F). Higher ambient
temperatures cause UPS batteries to need recharging more frequently.
Recharging requirements during storage:
Recharging the batteries requires that the battery module be connected to
the UPS and the UPS must have AC input power available. The UPS can
be in either the on line or bypass mode. (See “Starting the UPS”, page 12,
and “Battery Recharge Time”, page 16).
1) If stored in an ambient temperature less than 20°C (68°F), recharge the
batteries every 9 months.
2) If stored in an ambient temperature of 20° to 30°C (68° to 86°F),
recharge the batteries every 6 months.
3) If stored in an ambient temperature of 30° to 40° C (86° to 104°F),
recharge the batteries every 3 months.
Disposal
Please contact your local environmental agency for details on disposal of
electrical components and packaging in your particular area. It is illegal to
dump lead-acid batteries in landfills or dispose of improperly. Please
help our Earth by contacting the environmental protection agencies in your
area, the battery manufacturer, or call Toshiba toll-free at (800) 231-1412 for
more information about recycling.
29
TOSHIBA
Preventive and Scheduled Maintenance/Parts
Replacement
Preventive Maintenance
Toshiba's 1700 Series of UPS systems have been designed to
provide years of trouble-free operation requiring a minimum of
preventive maintenance.
The best preventive measure is to keep the area around the unit,
particularly the air inlet vents, clean and free of moisture and dust
accumulations. If the atmosphere of the installation site is very
dusty, use a vacuum cleaner to periodically remove dust
accumulations from the exterior of the unit, especially around
ventilation openings. Schedule authorized Toshiba service centers
to perform internal parts inspections annually, or call a Toshiba UPS
service representative at 1-877-867-8773 (outside the U.S. call 713466-0277).
CAUTION
Proper maintenance of the battery system
of this unit is essential to the safety and
reliability of the UPS system.
Parts Replacement
The following list shows intervals for periodic maintenance and
replacement of certain UPS parts.
1) Battery Module: Replacement should be done once every 3 to 5
years at a minimum.
2) Output Fuses: Replace once every 7 years (always replace
fuses with same fuse type and rating).
3) Cooling fan: Replace once every 3 years. (Fan replacement
must be done by Toshiba authorized service personnel.)
30
TOSHIBA
Appendix A: Specifications
Model Number
UF1A1A015C6(T)
UF1A1A024C6(T)
Capacity
1500VA (1.05KW)
2400VA (1.68KW)
1
Input voltage
Input
Single phase 120VAC, +20% to -50%
Input frequency
30 to 70 Hz
Input capacity
Bypass
Input voltage2
Single phase 120VAC, ±10%
Output voltage
Single phase 120VAC
Overload rating
See appendix C
Output voltage
Single phase 120VAC
Output voltage regulation
Within +/- 3%, steady state
50/60 Hz (+/- 0.5% in free running mode, line sync
range +/-1Hz)
Rated load power factor
0.7
Rated output current (rms)
Inverter overload capacity
12.5A
2.5 at full load
12V, flame retardant,
valve regulated lead acid
Type
Battery backup time (fully
charged, 0.7 power factor, 25°C (77°F)
13 minutes (at full load)
Configuration
7 minutes (at full load)
2 strings in parallel, 4 batteries per string
Operating temperature
Environment
20A
125% for one minute; 150% for 30 seconds
Crest factor
Battery
2400VA
Approximately unity (0.95 to 1.0)
Output frequency
Output
1500VA
Input power factor
0° to 40°C (32° to 104°F)
Altitude
Up to 1000m (3000 ft) above sea level
Efficiency
86%
Operating Humidity
30 to 90%, non-condensing
Note1: Below 77% input voltage unit may begin parallel operation; supplementing input
power with battery power. The point at which parallel operation begins is load
dependant (for a detailed explanation of Parallel Operation see appendix D).
Note2: Input voltage range is limited in bypass for load protection. (For a detailed
explanation of Bypass Undervoltage / Overvoltage see appendix E.)
31
TOSHIBA
Appendix B: Fan Speed Control
The fans in the 1700 Series will operate at any of four different speeds
depending on the environment and system conditions. In the first stage
the fans are off. As the load and or the temperature increase the fans
will subsequently go to low, medium or high speed as required.
The temperature reference given on the graph above refers to the
temperature inside the UPS. There will typically be a 5°C difference
between the internal and external temperature. The 10% hysteresis
shown is to ensure that the unit will not oscillate between fan speeds.
When the output power reaches a level that requires the fan speed to
increase the load will have to be reduced 10% below that level before the
fan speed will return to the lower speed.
32
TOSHIBA
Appendix C: System Overload Rating
The 1700 Series UPS is capable of supporting short duration overloads.
When operating in the On Line mode output overloading of 125% of the
rated output current can be supported for 1 minute, and 150% for 30
seconds. If the overload continues the unit will switch to bypass mode.
When in bypass mode the 1700 Series overload capacity is limited by
the input breaker. The following graph shows the response of the
breaker depending on the applied load. The two lines shown on the
graph represent the upper and lower limits of the breaker response. The
response of a particular breaker could fall anywhere between these two
lines.
If the load capacity of the breaker is exceeded the breaker will trip,
shutting down both the UPS and the attached loads. If the breaker’s
capacity is not exceeded the unit will continue to operate in the bypass
mode until the applied load is reduced. When the load on the UPS is
reduced to within the specified limits the UPS will automatically return to
On Line mode.
33
TOSHIBA
Appendix D: Parallel Operation
The 1700 Series UPS offers a standard feature that allows the unit to
operate with very low input voltage without de-rating the output power. If
the input voltage drops below a certain point the unit will switch to
parallel mode. Parallel mode means that the unit is using the available
input voltage and supplementing with battery power. Because battery
power is being used, the time the unit can operate in parallel mode is
limited. However, the time will be longer than that available when the
unit is operating on battery power alone. The point when the UPS will
enter parallel mode will vary depending on the output load. The following
graph shows the various stages based on full output load and 75%
output load.
As shown by the graph the lower the output load the lower the input
voltage can go before parallel mode is activated. However, the minimum
input voltage will always remain at 50% (60VAC for a 120VAC system).
34
TOSHIBA
Appendix E: Bypass Undervoltage / Overvoltage
When the 1700 Series UPS is in bypass mode the undervoltage and
overvoltage limits are restricted to +/-10% of the rated input voltage. If
the input voltage is outside of this voltage window the UPS output will be
turned off. There is a 5% hysteresis associated with both the upper and
lower limits. This means that once output has been turned off the input
voltage will have to be within ±5% of the rated input voltage before the
startup sequence will reinitialize. (To start the UPS when the input
power is outside of the allowable range see the section entitled “Starting
on DC Power”, page 13.)
When the UPS is started, if the RUN/STOP switch is in the STOP
(bypass) position the unit will start in the on-line mode for 1 second
before switching to bypass mode. If the input voltage is out of range the
UPS will turn off the output after 1 second rather than switching to
bypass.
35
TOSHIBA
Appendix F: Unit Configuration Options
The following chart shows the configuration options for each base model
UPS.
Model Number
Description
Available Option
Modules
Description
UF1-BC-087
UF1-EBC-087
UF1A1A015C6
1500VA
Electronics
Module
UF1-IO-015-6BG
UF1-IO-015-6AA
UF1-IO-015-6EE
UF1-BC-087
UF1A1A015C6T
1500VA
UF1-EBC-087
Electronics
Module with
internal isolation UF1-IO-015-6BG
transformer
UF1-IO-015-6EE
UF1-BC-087
UF1-EBC-087
UF1A1A024C6
2400VA
Electronics
Module
UF1-IO-024-6BG
UF1-IO-024-6AA
UF1-IO-024-6EE
UF1A1A024C6T
UF1-BC-087
2400VA
Electronics
UF1-EBC-087
Module with
1500VA internal
UF1-IO-024-6BG
isolation
transformer 1
UF1-IO-024-6EE
48V battery module
Extended runtime 48V battery
module
208/240V input; 240V/120V
output transformer module
120V input isolation transformer
module
230V input; 230V output
transformer module
48V battery module
Extended runtime 48V battery
module
208/240V input; 240V/120V
output transformer module
230V input; 230V output
transformer module
48V battery module
Extended runtime 48V battery
module
208/240V input; 240V/120V
output transformer module
120V input isolation transformer
module
230V input; 230V output
transformer module
48V battery module
Extended runtime 48V battery
module
208/240V input; 240V/120V
output transformer module
230V input; 230V output
transformer module
Note 1: 1500VA internal isolation transformer only provides isolation on two output
receptacles and 12.5A of output current. For full and total isolation a full isolation
option cabinets is required.
36
TOSHIBA
\Appendix G: Weights and Dimensions
Module
Model No.
Module Weight
Pounds
Kilograms
Shipping Weight
Pounds
Kilograms
UF1A1A015C6
26
12
31
14
UF1A1A015C6T
UF1A1A024C6
UF1A1A024C6T
UF1-BC-087
46
30
50
51
21
14
23
23
51
35
55
56
23
16
25
25
37
TOSHIBA
TOSHIBA INTERNATIONAL CORPORATION LIMITED WARRANTY POLICY
(48 contiguous U.S. States, Canada, Mexico)
(UNINTERRUPTIBLE POWER SUPPLIES-UPS)
TOSHIBA INTERNATIONAL CORPORATION (“TIC”) warrants that the 1700 Series
Uninterruptible Power Supplies (“UPS”) and Uninterruptible Power Supply Battery
(“BATTERY”) (external battery cabinet) sold by TIC to the end user (“User”) shall be free of
defects in material and workmanship.
UPS Unit
Battery
Series Capacity
Toshiba Dispatch
Warranty1 On-Site2
Warranty1 On-Site2
1700
1.5, 2.4 kva 36 months No, Depot 24 months No, Depot M-F, 8AM-5PM CT
Note 1:
Note 2:
The warranty period begins from the shipment date. The shipment date is determined by the
date on the TIC Bill of Lading.
For the 1700 Series the warranty applies if the unit is sent and returned (paid for) by the user
to/from the Toshiba plant or a Toshiba designated Authorized Service Center.
If any UPS, part of UPS, and/or BATTERY fails to conform or is defective then TIC will
repair or replace it at TIC’s option.
LIMITATIONS AND EXCLUSIONS
This limited warranty shall not cover the UPS, UPS part, or BATTERY during their
respective warranty periods, if the following storage, maintenance, installation, operating
conditions are not met throughout the warranty periods (5 conditions below):
VALVE REGUALATED LEAD ACID (VRLA) BATTERIES FOR TOSHIBA UPS
REQUIRED OPERATING CONDITIONS
Annual Average
Temperature per cell < 32°C
1. Temperature
Temperature 25°C (77°F)
(89°F) for more than 30 days
Maximum Number of Cycles
Discharge time
(24 months)
30 minutes
69
2. Maximum number of full
charge/discharge cycles
15 minutes
86
10 minutes
110
5 minutes
130
VALVE REGUALATED LEAD ACID (VRLA) BATTERIES FOT TOSHIBA UPS
INSTALLATION AND MAINTENANCE CONDITIONS
3. Storage
While UPS is in transit or storage it must always be in
suitable temperature (see condition 1).
4. External Batteries
Parallel battery string applications must be approved by TIC
in writing.
5. Idle Batteries
User must recharge the batteries if not in use (charged) for
more than 6 months.
1. This Warranty does not cover damage or defect caused by misuse, improper
application, wrong or inadequate electrical current/voltage/frequency, inadequate
connections, inadequate water or drain services, user negligence, repair by nonToshiba designated personnel, accident during shipment, tampering, alterations, a
change in UPS and/or BATTERY location or application, exposure to the elements, acts
of God, theft, sabotage, installation contrary to TIC's recommendations or specifications
(Published Operation Manuals), also if serial numbers have been altered, defaced, or
removed.
2. Repair or replacement of a defective UPS, UPS part, and/or BATTERY does not extend
the respective original warranty period. All defective UPS, UPS parts, and/or
BATTERIES shall be the property of TIC upon replacement.
3. This warranty shall constitute the sole and exclusive remedy of all purchasers and
users of the UPS, UPS part, and/or BATTERY. TIC’s responsibility for UPS, UPS
Parts, and/or BATTERY shall not exceed one times the net UPS and/or BATTERY
purchase price. TIC HEREBY EXPRESSLY DISCLAIMS ALL OTHER EXPRESS,
STATUTORY AND IMPLIED WARRANTIES, INCLUDING WITHOUT LIMITATION,
THE IMPLIED WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A
PARTICULAR PURPOSE.
38
TOSHIBA
PROCEDURE
User must contact TIC via e-mail upsservice@tic.toshiba.com, or phone 1-877-867-8773
(outside the U.S. call 713-466-0277), no later than 90 days after User’s discovery of
occurrence or defect in UPS, UPS part, and/or BATTERY but in no event after the
expiration of the respective warranty period. Subject to the limitations of this policy and
product type, TIC service or TIC service representative shall repair/replace the UPS/part
warranted hereunder, without charge for material, labor. If TIC determines that the
requested repair is not covered under this limited warranty policy, then TIC shall advise
customer and quote cost of repair. Repair charges shall be based on service parts price
and prevailing service charges at the time of repair.
If the case in process is a BATTERY (stand-alone and/or cabinet) TIC will use its published
Battery Diagnostic Document to evaluate warranty applicability. First, TIC will make sure
that the storage, maintenance, installation, and operating conditions were met; then the
BATTERY capacity will be tested in accordance with the “performance test” guidelines
IEEE Std 450. If the BATTERY fails to deliver 70% of its rated capacity it shall be deemed
defective and be replaced. Either float or cyclic service will be used to determine the
warranty credit (as per published Battery Diagnostic Document). The typical credit applied
will be as in the following table:
Credit for Replacement Battery When Approved Warranty
Time from Shipment
(months)
0-24
25-30
31-36
37-42
43-48
49-54
55-60
UPS Batteries
% Credit
100
55
45
35
25
15
5
Cost to Customer
% List Price
0
45
55
65
75
85
95
MODIFICATIONS
No representative, salesperson, agent, distributor, or employee of TIC is authorized to
modify any of the terms of this warranty, unless modifications are made in writing and
signed by an authorized TIC officer.
THIS WARRANTY REPRESENTS THE ENTIRE AGREEMENT BETWEEN TIC AND
USER WITH RESPECT TO THE SUBJECT MATTER HEREIN AND SUPERSEDES ALL
PRIOR OR CONTEMPORANEOUS ORAL OR WRITTEN COMMUNICATIONS,
REPRESENTATIONS, UNDERSTANDINGS OR AGREEMENTS RELATING TO THIS
SUBJECT
39