INSTALLATION INSTRUCTIONS FS MULTI WALL MOUNTED TYPE

2. SELECTING THE LOCATION FOR THE INDOOR UNIT
●
INSTALLATION INSTRUCTIONS
FS MULTI WALL MOUNTED TYPE
HP
R 410A
0.8
1.0
1.5
1.75
2.0
2.5
3.0
2.2kW
2.8kW
3.6kW
4.5kW
5.6kW
6.3kW
7.1kW
Model name
S-22KA1E5
S-28KA1E5
S-36KA1E5
S-45KA1E5
S-56KA1E5
S-63KA1E5
S-71KA1E5
(Unit: mm)
HP
Cooling
capacity
Model name
0.8
1.0
1.5
1.75
2.2kW
2.8kW
3.6kW
4.5kW
S-22KA1E5S
S-28KA1E5S
S-36KA1E5S
S-45KA1E5S
Carry out installation work with reliability after thorough reading of this “Precaution in terms of safety”.
Precautions shown here are differentiated between
Warnings and
Cautions . Those that have much chances for
leading to significant result such as fatality or serious injury if wrong installation would have been carried out are listed
compiling them especially into the column of
Warnings .
However, even in the case of items which are listed in the column of
Cautions , such items also have a chance for
leading to significant result depending on the situations.
In either case, important descriptions regarding the safety are listed, then observe them without fail.
As to indications with illustration
This mark means “Caution” or “Warning”.
This mark means “Earth”.
After installation work has been completed, do not only make sure that the unit is free from any abnormal condition through
the execution of trial run but also explain how to use and how to perform maintenance of this unit to the customer according
to the instruction manual.
In addition, request the customer to keep this manual for installation work together with the instruction manual.
Warnings
Warnings
The appliance must be installed by technician, who
takes into account the requirements given by ISO5149
or eventual equivalent requirements.
Switch off all supplies before accessing any electrical
part.
Carry out the installation work with reliability according
to this manual for installation work.
Imperfection in installation leads to water leakage,
electric shock, fire, etc.
Carry out the installation work with reliability on the place
that can bears the weight of this unit sufficiently.
Insufficient strength leads to injury due to falling of
the unit.
Carry out predetermined installation work in preparation
for strong wind such as typhoon, earthquake.
Imperfection in installation work may lead to accidents
arisen from overturn, etc.
The unit must be installed in accordance with applicable
national and local regulations.
Any electrical work should only be carried out by qualified
technician and use exclusive circuits without fail.
Presence of insufficient capacity in power circuit or
imperfection in execution leads to electric shock, fire, etc.
Wiring shall be connected using specified cables and fix
them securely so that external force of the cables may
not transfer to the terminal connection section.
Imperfect connection and fixing leads to fire, etc.
If installing inside a small room, measures should be
taken to prevent refrigerant levels from building up to
critical concentrations in the event of a refrigerant leak
occurring. Please discuss with the place of purchase for
advice on what measures may be necessary to prevent
critical concentrations being exceeded. If the refrigerant
leaks and reaches critical concentration levels, there is
the danger that death from suffocation may result.
Securely attach the protective covers for the outdoor
unit connection cables and power cord so that they do
not lift up after installation. If the covers are not properly
attached and installed, the terminal connections may
overheat, and fire or electric shock may result.
Name
Plate
Screw
Installation Instruction
Quantity
Once installation work is completed, check that there are
no refrigerant gas in the room that can come into contact
with sparks or flames from a fan heater, stove or kitchen
range, which will cause toxic gases to be generated.
When performing piping work do not mix air except for
specified refrigerant (R410A) in refrigeration cycle. It
causes capacity down, and risk of explosion and injury
due to high tension inside the refrigerant cycle.
1
50 or more
Carry out Earthing work.
Do not connect the Earth return to the gas
pipe, water line pipe, lightning rod and
telephone lines.
Imperfection in Earth return may lead to
electric shock.
Warning
The installation position must be able to support a load four times the indoor unit weight.
The indoor unit must be away from heat and steam sources, but avoid installing it near an entrance.
The indoor unit must allow easy draining.
The indoor unit must allow easy connection to the outdoor unit.
Before installing in quiet room such as a bedroom, please consult with an authorized distributor.
The indoor unit must be from at least 3m away from any noise-generating equipment. The electrical wiring should
be locally decided.
9. If the power supply is subject to noise generation, add a suppressor.
10. Do not install the indoor unit in a laundry. Electric shocks may result.
●
Drain piping should be made to ensure secure drainage
according to the manual for installation work and carry
out the thermal insulation to prevent the occurrence of
condensation.
Imperfection in piping work leads to water leakage and
may cause the house and property, etc. to become wet.
Position the indoor unit, outdoor unit, power cords and
indoor/outdoor unit connection cables in a way so that
they are at least 1 meter away from televisions and
radios. This is to avoid problems such as interference
with picture and/or sound. (However, note that depending
on the electromagnetic wave conditions, interference
may still occur even if the separation distance is more
than 1 meter.)
Installation plate fixing screw
This manual
Approx. 5 - 7 mm
Bushing for tube assembly
ø70 through hole
CAUTION
Use shock absorber during
pull out the piping to protect
the intake grille from damage
Do not turn over the unit without it’s
shock absorber during pull out the piping.
It may cause intake grille damage.
Piping
Piping
Thoroughly study the following installation locations
1. In such places as restaurants and kitchens, considerable amount of oil steam and flour adhere to the fan, the fin
of the heat exchanger, resulting in heat exchange reduction, spraying, dispersing of water drops, etc.
In these cases, take the following actions:
● Make sure that the ventilation fan for smoke-collecting hood on a cooking table has sufficient capacity so that it
draws oily steam which should not flow into the suction of the air conditioner.
● Make enough distance from the cooking room to install the air conditioner in such place where it may not suck in
oily steam.
Shock absorber
Intake grille
1. FOR THE RIGHT REAR PIPING
Use the ventilation fan for smokecollection hood with sufficient capacity.
Ensure ample
distance
Right Rear piping
Step-1 Pull out the Indoor piping
Step-2 Install the Indoor Unit
Step-3 Secure the Indoor Unit
Tape it with piping
in a position as
mentioned in Fig.
below.
Piping
Cover for the left piping
Cover for the
bottom piping
Cover for the
right piping Cover for the
Drain
hose
bottom piping
Step-4 Insert the connecting cable
Cooking table
Cover for piping
How to keep the cover
2. Avoid installing the air conditioner in such circumstances where cutting oil mist or iron powder exist especially in
factories, etc.
3. Avoid places where inflammable gas is generated, flows-in, contaminated, or leaked.
4. Avoid places where sulphurous acid gas or corrosive gas can be generated.
5. Avoid places near high frequency generators.
2. FOR THE RIGHT AND RIGHT BOTTOM PIPING
Step-1 Pull out the Indoor piping
In case of the cover is cut, keep the cover at the
rear of chassis as shown in the illustration for future
reinstallation.
(Left, right and 2 bottom covers for piping.)
Step-2 Install the Indoor Unit
Right and Right Bottom piping
3. INSTALLATION OF INDOOR UNIT
Step-3 Insert the connecting cable
HOW TO FIX INSTALLATION PLATE
The mounting wall shall be strong and solid enough to prevent it from the vibration.
Wall
Wall
More than 1
More
than 2
screw
Wall
More than 1
Indoor unit
Step-4 Secure the Indoor Unit
Tape it with piping in a
position as mentioned in
Fig. below.
Piping
Cover for the
bottom piping
Cover for
the right
piping
Drain hose
3. FOR THE EMBEDDED PIPING
Cover for the left piping
Step-1 Replace the drain hose
Hooks at
installation
plate
Install the indoor unit
Step-2 Bend the embedded piping
Mounting of the earth leakage circuit breaker is required.
Omission in mounting of the earth leakage circuit breaker
may lead to electric shock.
Purpose
Sleeve
for tube
assembly
INDOOR UNIT INSTALLATION
Do not install the unit at the place where the possibility
of inflammable gas leakage exists. If gas leakage should
arise and the gas builds up around the unit, such situation
may lead to ignition.
Appearance
15 mm
Putty or caulking compound
3.
4.
5.
6.
7.
8.
Note
Outdoor
Indoor
1. Insert the piping sleeve to the hole.
2. Fix the bushing to the sleeve.
3. Cut the sleeve until it extrudes about 15 mm from the
wall.
4. Finish by sealing the sleeve with putty or caulking
compound at the final stage.
Cautions
1
5
100 or more
If refrigerant gas escapes during installation, ventilate the
affected area. If the refrigerant gas comes into contact
with sparks or naked flames, it will cause toxic gases to
be generated.
1. ACCESSORIES PACKED IN THE INDOOR UNIT CONTAINER
Wall
When the wall is hollow, please be sure to use the sleeve
for tube assembly to prevent dangers caused by mice
biting the connecting cable.
Floor
Precautions in terms of safety
As to installation, request the distributor or vendor to
perform it. Imperfection in installation caused by that
having been carried out by the customer himself may
leads to water leakage, electric shock, fire, etc.
TO DRILL A HOLE IN THE WALL AND
INSTALL A SLEEVE OF PIPING
CAUTION
65 or more
REFRIGERANT
Cooling
capacity
Install the indoor unit once the following conditions are satisfied and after receiving the customer approval.
1. The indoor unit must be within a maintenance space.
2. The indoor unit must be free from any obstacles in path of the air inlet and outlet, and must allow spreading of air
throughout the room.
2500-3000
ENGLISH
F614588
• Use a spring bender or equivalent to bend
the piping so that the piping is not crushed.
Measuring
Tape
234.5 mm
Installation
plate
241.5 mm
Step-3 Pull the connecting cable into Indoor Unit
• The inside and outside connecting cable
can be connected without removing the front
grille.
128 mm
128 mm
Step-4 Cut and flare the embedded piping
Model
S-22KA**
S-28KA**
S-36KA**
S-45KA**
S-56KA**
S-63KA**
S-71KA**
1
2
535 mm
82 mm
635 mm
82 mm
Dimension
3
4
165 mm
165 mm
158 mm
158 mm
5
6
43 mm
95 mm
169 mm
219 mm
The center of installation plate should be at more than 1 at right and left of the wall.
The distance from installation plate edge to ceiling should more than 2.
From installation plate left edge to unit’s left side is 3.
From installation plate right edge to unit’s right is 4.
B : For left side piping, piping connection for liquid should be about 5 from this line.
: For left side piping, piping connection for gas should be about 6 from this line.
1. Mount the installation plate on the wall with 5 screws or more (at least 5 screws).
(If mounting the unit on the concrete wall, consider using anchor bolts.)
● Always mount the installation plate horizontally by aligning the marking-off line with the thread and using a level
gauge.
2. Drill the piping plate hole with ø70 mm hole-core drill.
● Line according to the left and right side of the installation plate. The meeting point of the extended line is the
center of the hole. Another method is by putting measuring tape at position as shown in the diagram above. The
hole center is obtained by measuring the distance namely 128 mm for left and right hole respectively.
● Drill the piping hole at either the right or the left and the hole should be slightly slanting to the outdoor side.
• When determining the dimensions of the
piping, slide the unit all the way to the left
on the installation plate.
Hook the indoor unit onto the upper portion
of installation plate. (Engage the indoor
unit with the upper edge of the installation
plate). Ensure the hooks are properly
seated on the installation plate by moving
it in left and right.
Sleeve for
piping hole
Piping
Indoor unit
Drain hose
Secure the Indoor Unit
1. Press the lower left and right side of the
unit against the installation plate until hooks
engages with their slot (sound click).
Step-5 Install the Indoor Unit
• Please refer to “4.REFRIGERANT PIPING”
column.
Step-7 Insulate and finish the piping
• Please carry out insulation at pipe connection
portion as mentioned in Indoor/Outdoor unit
installation diagram.
• If drain hose or connecting piping is in the
room (where dew may form), please increase
the insulation by using POLY-E FOAM with
thickness 6mm or above.
Step-8 Secure the Indoor Unit
Installation
plate
Unit’s
hook
Step-6 Connect the piping
PUSH
PUSH
To take out the unit, push the
marking
at the bottom unit, and pull it slightly
towards you to disengage the hooks from
the unit.
marking
Insert the connecting cable
7
–
Connecting
cable
Ab
8
cm
ou
Gas side piping
t
Liquid side piping
Guide surface Connecting cable
Drain hose
(This can be used for left rear piping and bottom piping also.)
●
Replace the drain hose
Power supply specifications
Power supply cable
Rear view for left piping installation
Model
name
Connecting
cable
Drain hose
Drain cap
Piping
More than 1150 mm
Drain hose
Sleeve for piping hole
Connecting cable
Drain hose
Adjust the piping slightly downwards.
How to pull the piping and drain hose out, in case of the embedded piping.
n
tha
re
Mo 0 mm
115
Apply putty or
caulking material
to seal the wall
opening.
PVC tube for drain
hose (VP-20)
Connecting cable
More than 700 mm
●
●
In case of left piping how to insert the
connecting cable and drain hose.
Cable
°
Piping
Drain hose
Piping
Indoor unit
Cable
72 mm
(For the right piping, follow the same procedure)
Refrigerant is charged to the outdoor unit. For details, see the manual
for installation work of outdoor unit. (Additional charging, etc.)
1. Brazing for piping.
a. Execute brazing before tightening the flare nut.
b. Brazing must be executed while blowing nitrogen gas. (This
prevents generation of oxidized scale in copper pipe.)
2. When there is a lot of brazings for long piping, install a strainer
midway of the piping. (The strainer is locally supplied.)
3. Use clean copper pipe with inner wall surface free from mist and
dust. Blow nitrogen gas or air to blow off dust in the pipe before
connection.
4. Form the piping according to its routing. Avoid bending and bending
back the same piping point more than three times. (This will result
in hardening of the pipe).
5. After deforming the pipe, align centers of the union fitting of
the indoor unit and the piping, and tighten them firmly with
wrenches.
6. Connect pipe to the service valve or ball valve which is located
below the outdoor unit.
7. After completed the piping connection, be sure to check if there is
gas leakage in indoor and outdoor connection.
Indoor unit 220V-240V~
2mm2
100
* 1. This maximum length shows a 2% voltage drop.
* 2. Use an unshielded bus transmission line.
15A
15A
Control cable
0.75mm2
0.5 ~ 2mm2
15A
●
●
Front grille
Cap
Vane
Screw
●
NOTE 1
Screw to connect
the Earth wire
NOTE 2
Control cable
U1 U2
NOTE 4
NOTE 5
N
Remote control wire
A
B
Earth lead wire shall be longer than other lead wires as shown in
the figure for the electrical safety in case of the slipping out of the
cord from anchorage.
Manual address setting cannot be done on wall type indoor units.
* The automatic system settings can take up to 1 minute once power is supplied; do not operate the remote controller
Liquid piping
Gas piping
2.2kW - 6.3kW
ø6.35mm
ø12.7mm
* Once the wires are connected to 1 remote controller group control and power is supplied to the indoor unit, the A/C No. is
ø9.52
42 (430)
ø15.88
65 (660)
7.1kW or more
ø9.52mm
ø15.88mm
automatically set. To stop group control use, follow the directions below and clear the A/C No. that was automatically set
after disconnecting the wires for group control. If it is not cleared then the wired controller will not show any display.
● Instructions on clearing the A/C No. after automatic setup
Turn OFF the indoor unit power supply ➔ Set the SW2 (P.C.B) to ON ➔ Turn ON the power supply of the indoor unit
➔ After approximately 1 minute, turn OFF the power supply to the indoor unit ➔ Set the SW2 (P.C.B) to OFF.
(The next time the power supply is turned ON, the A/C No. will be cleared.)
● Do not set the SW2 to ON except when clearing the A/C No. as mentioned above. If the SW2 is set to ON, the wired
remote controller will no display.
Setting for 1 remote controller group control
● A maximum of 16 indoor units can be connected at the time of group control. (Do not connect the heat pump unit
with the cooling only unit.)
● Only automatic setting is possible when setting the group control address (A/C No.). (Manual setting cannot be
performed.)
● The A/C No. setting cannot be confirmed when using the automatic method.
■ Automatic setting
Refer to the remote controller’s installation instruction manual for remote controller settings.
As to main power source and cable size of outdoor unit,
read the installation manual attached to the outdoor unit.
Warning
The units must be installed in accordance with applicable national and local regulations.
The units installed by a professional installer must be supplied from a dedicated electrical circuit.
All electric work must be carried out by a qualified technician according to proper technical standards for
electrical work and according to installation manual for installation work. If circuits with insufficient capacity are
used, or if electrical work is not carried out properly, electric shocks or fire may result.
Caution
Be sure to install a current leakage breaker or circuit breaker to the main power supply, otherwise electric
shocks may result.
Caution
Be sure to connect the unit to secure earth connection. (with a earth resistance of 100 Ω or less).
If the earthing work is not carried out properly, electric shocks may result.
Warning
Wiring shall be connected securely using specified cables and fix them securely so that external force of the
cables may not transfer to the terminal connection section. Imperfect connection and fixing leads to fire, etc.
1. Select a power source that is capable of supplying the current required by the air conditioner.
2. Feed the power source to the unit via a distribution switch board designed for this purpose, the switch should
disconnected all poles with a contact separation of at least 3 mm.
3. Always ground the air conditioner with a grounding wire and screw to meet the LOCAL REGULATIONS.
4. Be sure to connect the wires correctly to terminal board with connecting the crimp type ring terminal to the wires.
5. Be sure to turn off the main power before installing and connecting the remote controller.
If momentarily turning on the power supply for both the indoor and outdoor units, do not turn the power off
after at least 1 minute has passed. (For the system’s automatic setting.)
Turning off the power supply on the way may cause an abnormal operation.
Use the standard power cord for Europe (such as H05RN-F or H07RN-F which conforms to CENELEC (HAR) rating
specifications) or use the cables based on IEC standard. (245IEC57, 245IEC66)
Power supply
(ex. 1 ~ 230V)
Power supply
(ex. 1 ~ 230V)
Switch
Earth
●
●
Earth leakage breaker
Switch
Receiver
Earth
Wired controller
Switch the power supply to ON for at least 12 hours in advance before the test run.
First, press the ON/OFF (I) button.
Next, select the operational modes.
Then press the TEST RUN button within 1 minute of pressing the ON/OFF (I) button.
Be sure to run the cooling operation test run for at least 20 minutes before starting the heating operation
test run.
Press TEST RUN or ON/OFF (I) button again to cancel the test run mode.
Detaching a connector with electrical current may cause damage to the control board. Ensure to turn OFF
the power supply and wait for at least 5 minutes before performing this operation.
Do not short the remote control wires. (There is no protective circuit operation.) Normal operation will
commence once the short is solved.
During the test run; ensure to operate the units in cooling mode prior to operating the units in heating
mode. Caution: Operating the units in heating mode first may cause compressor failure.
Test run should be performed for a minimum of 20 minutes. (Test run using the remote controller will
change to normal operation after 30 minutes.)
Use the outdoor unit to cancel the outdoor unit test run and the wired controller to cancel the wired controller
test run. For the test run method using the AUTO switch, refer to the “AUTO operation” section in the
installation instruction manual for the infrared receiver.
9. CHECK THE FOLLOWING ITEMS WHEN INSTALLATION IS COMPLETE
6. SETTINGS
Cooling capacity
Infrared remote
controller
NOTE 3
Power supply cable
55 (560)
Earth leakage breaker
●
Cap
●
L
d.c. 5V
Test run is conducted using the wired controller, AUTO switch or by using the outdoor units. For the wired controller test
run see the instructions below.
Terminal board
L N A B U1 U2
Timer
1
The connector must use XH-2 (housing) manufactured by J.S.T. Mfg. Co., Ltd.
Wiring must use vinyl code with the sheath or cable line diameter 0.3mm2.
The length of wiring should be within 150m and separated from power line in order to prevent malfunction.
The input current is DC5V, and 1mA. The relay contact must use the contact for the minute electric current suitable for
this.
●
Union
2
Contact
Close: RUN
Open: STOP
8. PRECAUTIONS IN TEST RUN
Vane
(Move the vane
to upward)
Relay contact
For test run, refer to the “Precautions in test run” in the outdoor unit installation instructions manual.
ø12.7
Note
Printed
circuit
board
●
18 (180)
5. ELECTRICAL WIRING
CN-TIMER
Timer setting
●
ø6.35
Flare nut fastening torque N•m (kgf•cm)
Connect the timer cord to connector (CN-TIMER) on print circuit board.
Connector
CONNECTING THE WIRES TO THE CONTROL BOX
You can see the power supply box on the right side after removing the front grille.
When reinstalling the front grille, first set
the vertical airflow direction louver to the
horizontal position and then carry out above
steps 2 - 3 in the reverse order.
●
TEST RUN
Vacuum drying
After completing the piping connection, execute vacuum drying for the connecting piping and the indoor unit.
The vacuum drying must be carried out by using the service ports of both the liquid and gas side valves.
CAUTION Use two wrenches and tighten with regular torque.
●
* 1
Length
(m)
Please follow the steps below to take out front grille if necessary such as when servicing.
1. Set the vertical airflow direction louvers to the horizontal position.
2. Slide down the 2 caps (3/4 ~ 1.75HP) or 3 caps (2.0 ~ 3.0HP) on the front grille as shown
in the illustration at right, and then remove the 2 (3/4~ 1.75HP) or 4 (2.0 ~ 3.0HP) mounting
screws.
3. Pull the lower section of the front grille towards you to remove the front grille.
45
Piping
4. REFRIGERANT PIPING
Minimum power
supply cables
7. AS FOR TIMER OUTPUT
Remote
controller
cable
* 2
HOW TO TAKE OUT FRONT GRILLE
PVC tube
for drain
hose
than
Drain hose
More m
m
from main unit
470
PVC tube (VP-65) for piping
and connecting cable
PVC tube for drain hose (VP-30)
Power
supply
Circuit breaker
Leakage (Minimum capacity)
current
breaker Switch
Fuse
(A)
(A)
(A)
during this time.
●
●
●
Is circulation of air adequate?
Is draining smooth?
Is heat insulation complete
(refrigerant and drain piping)?
Is there any leakage of refrigerant?
Is remote controller switch operated?
Is there any faulty wiring?
Are the terminal screws loosened?
M3…69-98N•cm {7-10kgf•cm}
M4…157-196N•cm {16-20kgf•cm}
M5…196-245N•cm {20-25kgf•cm}
10. HAND OVER
●
Teach the customer the operation and maintenance procedures, using the operation manual (air filter cleaning,
temperature control, etc.)
As to parts to be sold separately
●
AUTO SWITCH OPERATION
After completing work, be sure to measure and record trial run properties, and store measuring data, etc.
Measuring items are room temperature, outside temperature, suction temperature, blow out temperature, wind velocity,
wind volume, voltage, current, presence of abnormal vibration and noise, operating pressure, piping temperature.
As to the structure and appearance, check the following items.
With regards to installation of the parts sold separately, follow the installation manual which is provided with the parts
sold separately.
As for work specifications of the outdoor unit, read the OUTDOOR UNIT INSTALLATION
MANUAL attached to the outdoor unit.
The below operations will be performed by pressing the “AUTO” switch.
1. AUTO OPERATION MODE
The Auto operation will be activated immediately once the Auto Switch is pressed and release before 5 sec..
2. COOLING TRIAL OPERATION
The Test Run operation will be activated if the Auto Switch is pressed continuously for more than 5 sec. to below
8 sec..
A “pep” sound will occur at the fifth sec., in order to identify the starting of Test Run operation.
3. HEATING TRIAL OPERATION
Press the “AUTO” switch continously for more than 8 sec. to below 11 sec. and release when a “pep
pep” sound is occured at eight sec. (However, a “pep” sound is occured at fifth sec..) then press
Remote controller “A/C Reset” button once. Remote controller signal will activate operation to force
heating mode.
4. REMOTE CONTROLLER RECEIVING SOUND ON/OFF
The ON/OFF of Remote controller receiving sound can be change over by the following steps:
a) Press “AUTO” switch continuously for more than 26 sec. to below 31 sec..
A “pep” “pep” “pep” “pep” “pep” “pep” sound will occur at the twenty-sixth sec..
b) Press the “AC RESET” button once. Remote controller signal will activate the Remote controller sound setting mode.
c) Press the “AUTO” switch once to select Remote controller receiving sound ON/OFF. A “pep” sound indicates
receiving sound ON, and a “peep” sound indicates receiving sound OFF.
Indoor unit-A
To other Indoor unit
Outdoor unit
Branch pipe
Refrigerant pipe
Provide separate power supplies for indoor and outdoor units.
Control cable
F614588
PRINTED IN MALAYSIA
1