PA C KA G E D E L E C T R I C / E L E C T R I C
LCH
Energence™ Rooftop Units
60 HZ
P R O D U C T S P E C I F I C AT I O N S
Bulletin No. 210556
September 2011
Supersedes April 2011
L
E
N
N
O
X
L
E
N
N
O
X
L
E
N
N
O
X
L
E
N
N
O
X
L
E
N
N
O
X
L
E
N
N
O
X
L
E
N
N
O
X
ASHRAE 90.1
COMPLIANT
7.5 to 12.5 Tons
Net Cooling Capacity − 90,000 to 138,000 Btuh
Optional Electric Heat - 7.5 to 60 kW
MODEL NUMBER IDENTIFICATION
L C H 120 H 4 B N 1 Y
Brand/Family
L = Energence™
Unit Type
C = Packaged Electric Cooling w/ optional Electric Heat
Major Design Sequence
H = 1st Generation
Nominal Cooling Capacity - Tons
092 = 7.5 Tons
102 = 8.5 Tons
120 = 10 Tons
150 = 12.5 Tons
Cooling Efficiency
H = High Efficiency
S = Standard Efficiency
Voltage
Y = 208/230V-3 phase-60hz
G = 460V-3 phase-60hz
J = 575V-3 phase-60hz
Minor Design Sequence
1 = 1st Revision
2 = 2nd Revision
3 = 3rd Revision
Factory Installed Electric Heat
N = No Heat
C = 7.5 kW Electric Heat
E = 15 kW Electric Heat
G = 22.5 kW Electric Heat
J = 30 kW Electric Heat
K = 45 kW Electric Heat
L = 60 kW Electric Heat
Blower Type
B = Belt Drive
Refrigerant Type
4 = R-410A
FEATURES AND BENEFITS
F
E
C
M
H
L
J
K
D
N
I
B
G
Unit shown with
optional
Economizer with
Outdoor Air Hoods
Lennox’ Energence™ packaged rooftop unit product line was created to save energy with intelligence by
offering some of the highest energy efficiency ratings available with a powerful, easy to use unit controller.
This makes Energence rooftop units perfect for business owners looking for an HVAC product with the lowest
total cost of ownership. Energence rooftop units feature:
•
Hinged Access Panels - Provide quick access to components and protect panels and roof from damage
during servicing.
• Isolated Compressor Compartment - Allows performance check during normal compressor operation
without disrupting airflow.
• Corrosion-Resistant Removable, Reversible Drain Pan - Provides application flexibility, durability and
improved serviceability.
• Thermostatic Expansion Valves - Provide peak cooling performance across the entire application range.
• Scroll Compressors - Standard on all units for reliable, long-term operation.
• Humiditrol® Dehumidification System - Patented system allows for independent control of temperature
and humidity, providing enhanced comfort control.
• Auto-Tensioner for Blower Belt - Factory option ensures blower is delivering the proper airflow for comfort, while maximizing efficiency and belt life.
• MERV 13 Filters - Available as factory or field option, provide an enhanced level of indoor air quality, and
can help the building qualify for additional LEED credits.
• Foil-Faced Insulation - Insulation on all internal surfaces that have contact with airflow helps minimize
airborne fibers and improve IAQ.
Prodigy™ Control System
Standard on every Energence rooftop unit, the new Prodigy™ unit controller is the
heart of the Lennox® controls offering. The intuitive user interface makes setup,
troubleshooting and service easier than ever. Each unit tracks the runtime of every
major component and records the date and time when service or maintenance is
performed.
SmartWire™ System
The SmartWire system simplifies field sensor or thermostat installation through advanced connectors that are
keyed and color-coded to help prevent miswiring. Not only is the wire coloring scheme standardized across all
models, each connection is intuitively labeled to make troubleshooting and servicing quick and easy.
Energence™ Packaged Electric / Electric 7.5 to 12.5 Ton / Page 2
FEATURES AND BENEFITS
Contents
Accessory Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Blower Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Electrical/Electric Heat Data . . . . . . . . . . . . . . . . . . . . . . . . 22
Electric Heat Capacities . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Features And Benefits . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Humiditrol® Dehumidification System Ratings . . . . . . . . . . . . . . . 16
Optional Conventional Temperature Control Systems . . . . . . . . . . . 27
Options / Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Outdoor Sound Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Prodigy™ Control System . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Ratings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .13
Unit Clearances . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Weight Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
COOLING SYSTEM
Designed to maximize sensible
and latent cooling performance at
design conditions.
System can operate from 0°F
to 125°F without any additional
controls.
R-410A Refrigerant
Non-chlorine
based, ozone
friendly, R-410A.
B Scroll Compressors
Scroll compressors on all models
for high performance, reliability and
quiet operation.
Resiliently mounted on rubber
grommets for quiet operation.
Compressor Crankcase Heaters
APPROVALS
AHRI Certified to AHRI Standard
340/360-2007.
WARRANTY
Limited five years on compressors.
ETL listed.
Limited three years on Prodigy™
Unit Controller.
Efficiency ratings are certified by
CSA.
Limited one year all other covered
components.
Components are bonded for
grounding to meet safety standards
for servicing required by UL,
ULC and National and Canadian
Electrical Codes.
All models are ASHRAE 90.1-2010
compliant.
ENERGY STAR® certified units are
designed to use less energy, help
save money on utility bills, and
help protect the environment.
The ENERGY STAR® Partner of
the Year Award signifies that
Lennox has made outstanding
contributions to design energy
efficient units that will lower energy
bills, while meeting industry
standards for comfort and indoor
air quality. Lennox was the first
HVAC manufacturer to win this
award and has been a four-time
recipient since 2003.
ISO 9001 Registered
Manufacturing Quality System.
Protects against refrigerant
migration that can occur during low
ambient operation.
Thermal Expansion Valve
Assures optimal performance
throughout the application range.
Removable element head.
C Filter/Driers
High capacity filter/drier protects
the system from dirt and moisture.
High Pressure Switches
Protects the compressors from
overload conditions such as
dirty condenser coils, blocked
refrigerant flow, or loss of outdoor
fan operation.
Low Pressure Switches
Protects the compressors from low
pressure conditions such as low
refrigerant charge, or low/no airflow.
Freezestats
Protects the evaporator coil from
damaging ice build-up due to
conditions such as low/no airflow,
or low refrigerant charge.
D Coil Construction
Copper tube construction,
enhanced rippled-edge aluminum
fins, flared shoulder tubing
connections, silver soldered
construction for improved heat
transfer. Factory leak tested.
Energence™ Packaged Electric / Electric 7.5 to 12.5 Ton / Page 3
FEATURES AND BENEFITS
COOLING SYSTEM (CONT.)
Evaporator Coil
Cross row circuiting with rifled
copper tubing optimizes both
sensible and latent cooling
capacity.
Condenser Coil
Slab type coil construction.
Condensate Drain Pan
Plastic pan, sloped to meet
drainage requirements of ASHRAE
62.1.
Side or bottom drain connections.
Reversible to allow connection at
back of unit.
E Outdoor Coil Fan Motors
Thermal overload protected, totally
enclosed, permanently lubricated
ball bearings, shaft up, wire basket
mount.
Outdoor Coil Fans
PVC coated fan guard furnished.
REQUIRED SELECTIONS
Cooling Capacity
Specify nominal cooling capacity of
the unit
OPTIONS/ACCESSORIES
Factory Installed
Service Valves
Fully serviceable brass valves
installed in discharge & liquid lines.
Not available for units equipped
with Humiditrol option.
Factory or Field Installed
Condensate Drain Trap
Available in copper or PVC.
Field installed only, may be factory
ordered to ship with unit.
Drain Pan Overflow Switch
Monitors condensate level in
drain pan, shuts down unit if drain
becomes clogged.
CABINET
F Construction
Heavy-gauge steel panels and full
perimeter heavy-gauge galvanized
steel base rail provides structural
integrity for transportation,
handling, and installation.
Base rails have rigging holes.
Three sides of the base rail have
forklift slots.
Raised edges around duct and
power entry openings in the bottom
of the unit provide additional
protection against water entering
the building.
Airflow Choice
Units are shipped in downflow
(vertical) configuration, can be field
converted to horizontal airflow with
optional Horizontal Discharge Kit.
Duct Flanges
Provided for horizontal duct
attachment.
OPTIONS/ACCESSORIES
Factory or Field Installed
Return Air Adaptor Plate
For same size L Series® and
T-Class™ unit replacement.
Installs on return air opening in
unit to match return air opening
on existing roof curbs. Also see
Accessory Air Resistance table.
Factory Installed
Corrosion Protection
A completely flexible immersed
coating with an electrodeposited
dry film process. (AST ElectroFin
E-Coat) Meets Mil Spec
MIL-P-53084, ASTM B117
Standard Method Salt Spray
Testing.
Indoor Corrosion Protection:
- Coated coil
- Coated reheat coil (Humiditrol)
- Painted blower housing
- Painted base
Power Entry
Electrical lines can be brought
through the unit base or through
horizontal access knock-outs
Outdoor Corrosion Protection:
- Coated coil
- Painted base
Exterior Panels
Constructed of heavy-gauge,
galvanized steel with a two-layer
enamel paint finish.
Coil Guards
Painted, galvanized steel wire
guards to protect outdoor coil.
Insulation
All panels adjacent to conditioned
air are fully insulated with nonhygroscopic fiberglass insulation.
Hail Guards
Constructed of heavy gauge steel,
painted to match cabinet, helps
protect outdoor coils from hail
damage.
Unit base is fully insulated. The
insulation also serves as an air
seal to the roof curb, eliminating
the need to add a seal during
installation.
G Hinged Access Panels
Hinged tool-less access panels
are provided for the filter section,
blower/heating section and
compressor/controls section.
All hinged panels have seals and
quarter-turn latching handles to
provide a tight air and water seal.
REQUIRED SELECTIONS
Airflow Configuration
Specify downflow or horizontal.
Energence™ Packaged Electric / Electric 7.5 to 12.5 Ton / Page 4
Field Installed
Not used with Hail Guards.
Not used with Coil Guards.
Horizontal Discharge Kit
Consists of duct covers to block
off downflow supply and return
air openings for horizontal
applications.
Also includes return air duct
flanges for end return air when
economizer is used in horizontal
applications.
NOTE - When configuring unit
for horizontal application with
economizer, a separate Horizontal
Barometric Relief Damper with
Hood must be ordered separately
for installation in the return air duct.
FEATURES AND BENEFITS
H BLOWER
A wide selection of supply air
blower options are available
to meet a variety of airflow
requirements.
Motor
Overload protected, equipped with
ball bearings. Belt drive motors
are offered on all models and are
available in several different sizes
to maximize air performance.
Motor Efficiency
All blower motors 5 hp and above
meet minimum energy efficiency
standards in accordance with the
Energy Independence and Security
Act (EISA).of 2007.
Supply Air Blower
Forward curved blades, double
inlet, blower wheel is statically and
dynamically balanced. Equipped
with ball bearings and adjustable
pulley (allows speed change),.
Blower assembly slides out of unit
for servicing.
REQUIRED SELECTIONS
Order blower motor horsepower
and drive kit number required
when base unit is ordered, see
Drive Kit Specifications Table
Supply Air Blower
Forward curved blades, blower
wheel is statically and dynamically
balanced.
All belt drive motors have
adjustable pulley for speed
change.
Ordering Information
Specify motor horsepower and
drive kit number when base unit is
ordered.
OPTIONS/ACCESSORIES
Factory Installed
Blower Belt Auto-Tensioner
Provides proper tension to belt
drive blower belt without the need
for regular adjustments. Maintains
airflow and proper performance.
ELECTRICAL
REQUIRED SELECTIONS
Voltage Choice
Specify when ordering base unit.
OPTIONS/ACCESSORIES
Factory Installed
Circuit Breakers
HACR type. For overload and
short circuit protection. Factory
wired and mounted in the power
entry panel. Current sensitive and
temperature activated. Manual
reset.
Phase/Voltage Detection
Phase detection monitors power
supply to assure phase is correct
at unit start-up. If phase is
incorrect, the unit will not start
and an alarm code is reported to
the unit controller. Protects unit
from being started with incorrect
phasing which could lead to issues
such as compressors running
backwards.
Voltage detection monitors power
supply voltage to assure proper
voltage. If voltage is not correct
(over/under voltage conditions)
the unit will not start and an
alarm code is reported to the unit
controller.
Factory or Field Installed
Disconnect Switch
Accessible from outside of unit,
spring loaded weatherproof cover
furnished.
I Electric Heat
Helix wound nichrome elements,
individual element limit controls,
wiring harness. Unit fuse block
is furnished as standard. See
Options / Accessories tables for
ordering information.
J GFI Service Outlets (2)
115v ground fault circuit interrupter
(GFCI) type.
INDOOR AIR QUALITY
K Air Filters
Disposable 2 inch filters furnished
as standard.
OPTIONS/ACCESSORIES
Factory or Field Installed
Healthy Climate® High
Efficiency Air Filters
Disposable MERV 8 or MERV 13
(Minimum Efficiency Reporting
Value based on ASHRAE 52.2)
efficiency 2 inch pleated filters.
Healthy Climate® UVC
Germicidal Lamps
Germicidal lamps emit ultra-violet
(UV-C) energy, which has been
proven to be effective in reducing
microbes such as viruses,
bacteria, yeasts, and molds. This
process either destroys the
organism or controls its ability to
reproduce.
UV-C energy greatly reduces the
growth and proliferation of mold
and other bioaerosols (bacteria
and viruses) on illuminated
surfaces (particularly coil and
drain pan).
Lamps are field installed in the
blower/evaporator coil section.
All necessary hardware for
installation is included.
Lamps operate on 208/230V
power supply. Step-down
transformer must be field supplied
when used with 460V and 575V
rooftop units.
Magnetic safety interlock
terminates power when access
panels are removed.
Approved by ETL.
Field Installed
Replacement Filter Media Kit
With Frame
Replaces existing pleated filter
media. Includes washable metal
mesh screen and metal frame with
clip for holding replaceable nonpleated filter.
Indoor Air Quality (CO2)
Sensors
Monitors CO2 levels, reports to the
Prodigy™ Unit Controller which
adjusts economizer dampers as
needed.
Energence™ Packaged Electric / Electric 7.5 to 12.5 Ton / Page 5
FEATURES AND BENEFITS
SERVICEABILITY
Designed to streamline general
maintenance and decrease
troubleshooting time.
Diagnostics
Prodigy Unit Controller diagnostic
scrolling text pinpoints problems,
minimizing troubleshooting time.
SmartWire™ System
Advanced wiring connectors are
keyed and color-coded to prevent
miswiring. Wire coloring scheme
is standardized across all models.
Each connection is intuitively
labeled to make troubleshooting
and servicing quick and easy.
Electrical Plugs
Positive connection electrical plugs
are used to connect common
accessories or maintenance parts
for easy removal or installation.
Thermal Expansion Valves
Thermal expansion valves are
located near the perimeter of the
unit for easier access.
Compressor Compartment
Compressors are located near
the perimeter of the unit for easier
access.
Removable element head allows
change out of element and bulb
without removing the TXV.
Compressors are isolated from the
condenser airflow allowing system
operation checks to be done
without changing the airflow across
the outdoor coils.
Coil Cleaning
Slab condenser coils with hinged
access panels allow easy cleaning.
Standard Components
A large number of common
maintenance parts are standard
throughout the entire range of
sizes (3-30 tons), reducing the
need to carry a lot of different parts
to the job or maintain in inventory.
Toolless, Hinged Access
Panels
Large access panels are hinged
and have quarter-turn, latching
handles for quick and easy access
to maintenance areas (filter,
compressor / controls/ blower /
heat section).
Blower Access
Supply air blower parts are located
near the access door for easy
servicing and adjustment.
Energence™ Packaged Electric / Electric 7.5 to 12.5 Ton / Page 6
Service Valves (optional)
Optional factory installed liquid
and discharge service valves
allow refrigerant to be isolated to
the high side for service work on
the low side of the refrigeration
system.
PRODIGY™ CONTROL SYSTEM
L PRODIGY UNIT CONTROLLER
The Prodigy Unit Controller is a
microprocessor-based control
board that provides flexible control
of all unit functions.
Prodigy Unit Controller features:
Scrolling Display - Scrolls full text
instead of numerical codes.
Push Buttons - Simplified
navigation during setup and
diagnostics.
Guided Setup Procedure Insures proper installation and
setup of the rooftop unit.
Profile setup - Copy key setpoints
between units with the same
configuration greatly reducing
setup time.
USB Port - Easily download and
transfer unit
information via a USB
flash drive and also
interface with Lennox
Unit Controller
Software.
Self Test Mode - Confirm proper
component and system operation.
Time Clock with Run-time
Information
Built-In Functions Include:
Adjustable Blower On/Off Delay
Built-in Control Parameter
Defaults
Compressor Time-Off Delay
DDC Compatible
Dirty Filter Switch Input
Discharge Air Temperature
Control
Display/Sensor Readout
Economizer Control Options See Economizer / Outdoor Air /
Exhaust Options.
Fresh Air Tempering
Extensive Unit Diagnostics Over 100 diagnostic and status
messages in English.
Exhaust Fan Control Modes Fresh air damper position.
Permanent Diagnostic Code Storage
Field Changeable Control
Setpoints - Over 200 different
control setpoints.
Indoor Air Quality Input Demand Control Ventilation ready
Low Ambient Controls - Cooling
operation down to 0°F.
Gas Valve Time Delay Between
First and Second Stage
Minimum Compressor Run Time
Network Capable - Can be daisy
chained to other units or controls.
Night Setback Mode
Return Air Temperature Limit
Control
Safety Switch Input - Allows
Controller to respond to a external
safety switch trip.
Service Relay Output
Smoke Alarm Mode - Four
choices.
Staging - up to 4 heat/4 cool (zone
sensor or network operation). Up
to 2 heat/2 cool (standard Prodigy
unit controller thermostat input).
Up to 3 cool (thermostat input with
additional relay).
“Strike Three” Protection
Gas Reheat Control Simultaneous heating and cooling
operation for controlling humidity
for process air applications such as
supermarkets.
On Demand Dehumidification Monitors and controls condenser
hot gas reheat operation with
Humiditrol® option.
Thermostat Bounce Delay
Warm Up Mode Delay
LED Indicators
PC Interface - For use with PC
with optional Unit Controller
software.
Zone Sensor Operation - Controls
zone temperature.
OPTIONS / ACCESSORIES
Factory or Field Installed
Blower Proving Switch
Monitors blower operation, shuts
down unit if blower fails.
Dirty Filter Switch
Senses static pressure increase
indicating dirty filter condition.
NOTE - Prodigy Control System features
shown vary with the type of rooftop unit
the control is installed in.
NOTE - See separate Prodigy Control
System Product Specifications Bulletin
for additional information.
CONTROLS OPTIONS
Factory or Field Installed
Fresh Air Tempering
Used in applications with high
outside air requirements. The
Controller energizes the first stage
heat as needed to maintain a
minimum supply air temperature
for comfort, regardless of the
thermostat demand. When ordered
as a factory option, the sensor
ships with the unit but must be field
installed.
Smoke Detector
Photoelectric type, installed in
supply air section, return air
section or both sections. Available
with power board and single
sensor (supply or return) or power
board and two sensors (supply and
return). Power board located in unit
control compartment.
Interoperability via BACnet® or
LonTalk® Protocols
Communication compatible with
third-party automation systems that
support the BACnet Application
Specific Controller device
profile, LonMark® Space Comfort
Controller functional profile, or
LonMark Discharge Air Controller
functional profile.
Commercial Control Systems
L Connection® Network Control
System
Complete building automation
control system for single or
multi-zone applications. Options
include local interface, software
for local or remote communication,
and hardware for networking
other control functions. See L
Connection Network Control
System Product Specifications
Bulletin for details.
Aftermarket DDC
Novar® Unit Controller and
options.
Thermostats
Control system and thermostat
options. Aftermarket unit controller
options.
Field Installed
Humidity Sensor Kit
Humidity sensor required with
factory installed Humiditrol®
dehumidification option or
Supermarket reheat field
selectable option.
Energence™ Packaged Electric / Electric 7.5 to 12.5 Ton / Page 7
OPTIONS / ACCESSORIES
M ECONOMIZER/EXHAUST
OPTIONS
Factory or Field Installed
Economizer - Downflow or
Horizontal With Barometric
Relief Dampers and Air Hoods
Parallel gear-driven action return
air and outdoor air dampers,
plug-in connections to unit, nylon
bearings, neoprene seals, 24-volt,
fully-modulating, spring return
motor, adjustable minimum damper
position. Economizer includes
outdoor air hood and barometric
relief dampers with outdoor air
hood.
N Barometric Relief Dampers allow
relief of excess air, aluminum blade
dampers prevent blow back and
outdoor air infiltration during off
cycle, bird screen furnished. For
use in downflow applications only.
Outdoor Air and Barometric
Relief Hoods are included when
economizer is factory installed
and are furnished with economizer
when ordered for field installation.
Choice of economizer control
options:
1. Differential Sensible Control
Factory setting. Uses outdoor
air and return air sensors that
are furnished with the unit.
The Prodigy Unit Controller
compares outdoor air and
return air and using setpoints,
enables the economizer when
the outdoor air temperature is
below the configured setpoint
and cooler than return air.
NOTE - Differential Sensible
Control can be configured in the
field to provide Offset Differential
Sensible Control or Single
Sensible Control.
In Offset Differential Sensible
Control mode, the economizer
is enabled if the temperature
differential (offset) between
outdoor air and return air reaches
the configured setpoint.
In Single Sensible Control mode,
the economizer is enabled when
outdoor air temperature falls below
the configured setpoint.
2. Global Control
The unit controller
communicates with a DDC
system with one global sensor
(enthalpy or sensible) to
determine whether outside air
is suitable for free cooling on all
units connected to the control
system. Sensor must be field
provided.
3. Single Enthalpy Control
Outdoor air enthalpy sensor
enables economizer if the
outdoor enthalpy is less than the
setpoint of the board.
4. Differential Enthalpy Control
Two solid-state enthalpy sensors
allow the economizer control to
select between outdoor air or
return air, whichever has lower
enthalpy.
Factory or Field Installed
Power Exhaust Fan
Installs internal to unit for downflow
applications only with economizer
option. Provides exhaust air
pressure relief. Interlocked to
run when supply air blower is
operating, fan runs when outdoor
air dampers are 50% open
(adjustable), motor is overload
protected. Requires Economizer
with Outdoor Air Hood and
Barometric Relief Dampers. Fan
is 20 in. diameter with 5 blades
(K1PWRE10B) WITH 1/3 hp motor.
Field Installed
Horizontal Barometric Relief
Dampers
For use when unit is configured for
horizontal applications requiring an
economizer.
Allows relief of excess air
Aluminum blade dampers prevent
blow back and outdoor air
infiltration during off cycle.
Field installed in return air duct.
Bird screen and hood furnished.
Requires Horizontal Discharge Kit.
Energence™ Packaged Electric / Electric 7.5 to 12.5 Ton / Page 8
OUTDOOR AIR OPTIONS
Factory or Field Installed
Outdoor Air Damper - Downflow
or Horizontal With Air Hood
Linked mechanical dampers, 0 to
25% (fixed) outdoor air adjustable,
installs in unit. Includes outdoor air
hood.
Automatic model features fully
modulating spring return damper
motor with plug-in connection.
Manual model features a slide
damper.
Maximum mixed air temperature in
cooling mode: 100°F.
ROOF CURBS (DOWNFLOW)
Nailer strip furnished, mates
to unit, US National Roofing
Contractors Approved, shipped
knocked down.
Clip Curbs - Uses interlocking
tabs to fasten corners together. No
tools required.
Standard Curbs - Curb corners
fasten together with furnished
hardware.
Transition Curbs - Curbs are
regionally sourced. Dimensions
will vary based upon the source.
Contact your Lennox sales
representative for a detailed cut
sheet with applicable dimensions.
See Options/Accessories table for
available curbs.
CEILING DIFFUSERS
Ceiling Diffusers
(Flush or Step-Down)
Aluminum grilles, large center
grille, insulated diffuser box with
flanges, hanging rings furnished,
interior transition (even air flow),
internally sealed (prevents
recirculation), adapts to T-bar
ceiling grids or plaster ceilings.
Transitions (Supply and
Return)
Used with diffusers, installs
in roof curb, galvanized steel
construction, flanges furnished for
duct connection to diffusers, fully
insulated.
OPTIONS / ACCESSORIES
HUMIDITROL DEHUMIDIFICATION® SYSTEM
Factory installed option designed
to control humidity.
OPERATION
Provides dehumidification on
demand using ASHRAE 90.1
recommended method for comfort
conditioning humidity control.
No Dehumidification Demand
The unit will operate conventionally
whenever there is a demand
for cooling or heating and no
dehumidification demand.
Unit comes equipped with one row
reheat coil, solenoid valve and
humidity controller.
Free cooling is only permitted
when there is no demand for
dehumidification.
In addition to a thermostat or room
sensor used for conventional
operation, a humidity sensor is
required and must be located
in the occupied space. Remote
Mounted Humidity Sensor Kit is
required for field installation.
Dehumidification Demand Only
The Unit Controller is factory set
at 60% relative humidity setpoint
and can be adjusted at the Unit
Controller or with optional Unit
Controller Software.
The humidity sensor provides
input to the Unit Controller which
is used to control activation of the
dehumidification operation.
Reheat controls are located in the
compressor control section of the
unit for easy access.
Benefits
Improves indoor air quality.
Helps prevents damage due to
high humidity levels.
Improves comfort levels by
reducing space humidity levels.
For L Connection® Network Control
Panel (NCP) applications, the
humidity setpoint can be adjusted
at the NCP.
Reheat operation will initiate on a
dehumidification demand and does
not require a cooling demand.
The unit will operate in the
dehumidification mode until the
relative humidity of the conditioned
space is below the setpoint.
The reheat coil is sized to provide
68°F to 75°F supply air during
reheat operation.
HUMIDITROL REFRIGERANT SCHEMATIC
This reduces sensible cooling
capacity and extends compressor
run time to control humidity when
the cooling load is low.
A solenoid valve diverts hot gas
from the compressor to the reheat
coil.
The cooled and dehumidified air
from the evaporator is reheated as
it passes through the reheat coil.
The de-superheated and partially
condensed refrigerant continues to
the outdoor condenser coil where
condensing is completed. The
unit will continue to operate in this
mode until the dehumidification
demand is satisfied.
See Sequence of Operation for
additional information.
Dehumidification and Cooling
Demand (Thermostat/Room
Sensor Application)
If both a dehumidification and a
full cooling load demand occur, the
system will operate in cooling until
the cooling demand is satisfied.
Then the system will energize the
dehumidification mode.
ACCESSORIES
Humidity Sensor Kit, Remote
Mounted Humidity sensor required
with factory installed Humiditrol®
Option or Supermarket reheat field
selectable option.
EVAPORATOR
COIL
CONDENSER COIL
REHEAT
COIL
REFRIGERANT
CIRCUIT 1
REFRIGERANT
CIRCUIT 2
REHEAT
VALVE
CHECK
VALVE
EXPANSION
VALVES
Energence™ Packaged Electric / Electric 7.5 to 12.5 Ton / Page 9
OPTIONS / ACCESSORIES
Model
Number
Item Description
Catalog
Number
Unit Model No
092 102 120
150
COOLING SYSTEM
Condensate Drain Trap
PVC - C1TRAP20AD2
76W26
OX
OX
OX
OX
Copper - C1TRAP10AD2
76W27
OX
OX
OX
OX
Factory
O
O
O
O
Corrosion Protection
68W88
OX
OX
OX
OX
Refrigerant Type
R-410A
O
O
O
O
Service valves (not for Humiditrol equipped units)
Factory
O
O
O
O
Belt Drive (standard or high efficiency) - 2 hp
Factory
O
O
O
O
Belt Drive (standard or high efficiency) - 3 hp
Factory
O
O
O
O
Belt Drive (standard efficiency) - 5 hp
Factory
O
O
O
O
Kit #1 590-890 rpm
Factory
O
O
O
O
Drain Pan Overflow Switch
E1SNSR71AD1
BLOWER - SUPPLY AIR
Motors
Drive Kits
See Blower Data Tables for selection
Kit #2 800-1105 rpm
Factory
O
O
O
O
Kit #3 795-1195 rpm
Factory
O
O
O
O
Kit #4 730-970 rpm
Factory
O
O
O
O
Kit #5 940-1200 rpm
Factory
O
O
O
O
Kit #6 1015-1300 rpm
Factory
O
O
O
O
Kit #7 730-970 rpm
Factory
O
O
O
O
Kit #8 940-1200 rpm
Factory
O
O
O
O
Kit #9 1015-1300 rpm
Factory
O
O
O
O
Kit #10 900-1135 rpm
Factory
O
O
O
O
Kit #11 1040-1315 rpm
Factory
O
O
O
O
Kit #12 1125-1425 rpm
Factory
O
O
O
O
Blower Belt Auto-Tensioner
Factory
O
O
O
O
E1GARD20B-1
55W06
X
X
X
X
Hail Guards
E1GARD10B1
55W07
X
X
X
X
Horizontal Discharge Kit
K1HECK00B-1
51W25
X
X
X
X
C1CONV10B-1
54W96
OX
OX
OX
OX
CABINET
Coil Guards
Return Air Adaptor Plate (for L Series and T-Class™ replacement)
®
CONTROLS
C1SNSR35FF1
53W65
OX
OX
OX
OX
L Connection® Building Automation System
Prodigy™ Control System - BACnet® Module - C0CTRL60AE1L
Factory
59W51
X
X
X
X
OX
OX
OX
OX
Prodigy™ Control System - LonTalk® Module - C0CTRL65FF1
54W27
OX
OX
OX
OX
Novar® ETM-2051 - E0CTRL30B1
64W73
OX
OX
OX
OX
Novar LSM
Factory
O
O
O
O
Blower Proving Switch
Commercial Controls
®
E1SNSR55B-1
53W67
OX
OX
OX
OX
C1SNSR75AD1
58W63
OX
OX
OX
OX
Smoke Detector - Supply or Return (Power board and one sensor)
C1SNSR44B-1
53W80
OX
OX
OX
OX
Smoke Detector - Supply and Return (Power board and two sensors)
C1SNSR43B-1
53W81
OX
OX
OX
OX
Dirty Filter Switch
Fresh Air Tempering
NOTE - Catalog and model numbers shown are for ordering field installed accessories.
OX - Configure To Order (Factory Installed) or Field Installed
O = Configure To Order (Factory Installed)
X = Field Installed
Energence™ Packaged Electric / Electric 7.5 to 12.5 Ton / Page 10
OPTIONS / ACCESSORIES
Model
Number
Item Description
INDOOR AIR QUALITY
Air Filters
Healthy Climate® High Efficiency Air Filters
20 x 25 x 2 (Order 4 per unit)
Replacement Media Filter With Metal Mesh
Frame (includes non-pleated filter media)
Indoor Air Quality (CO2) Sensors
Sensor - Wall-mount, off-white plastic cover with LCD display
Sensor - Wall-mount, off-white plastic cover, no display
Sensor - Black plastic case with LCD display, rated for plenum
mounting
Sensor - Wall-mount, black plastic case, no display, rated for
plenum mounting
CO2 Sensor Duct Mounting Kit - for downflow applications
Aspiration Box - for duct mounting non-plenum rated CO2 sensors
(87N53 or 77N39)
UVC Germicidal Lamps
1
Healthy Climate® UVC Light Kit (208/230v-1ph)
HUMIDITROL® CONDENSER REHEAT OPTION
Humiditrol
Humidity Sensor Kit, Remote mounted (required)
ELECTRICAL
Voltage 60 hz
HACR Circuit Breakers
Disconnect Switch - See Electrical/Electric Heat tables for selection
GFI Service Outlets
Phase/Voltage Detection
ELECTRIC HEAT
7.5 kW
15 kW
22.5 kW
30 kW
45 kW
60 kW
Catalog
Number
Unit Model No
092 102 120
150
MERV 8 - C1FLTR15B-1
MERV 13 - C1FLTR40B-1
C1FLTR30B-1-
50W61
52W41
Y3063
OX
OX
X
OX
OX
X
OX
OX
X
OX
OX
X
C0SNSR50AE1L
C0SNSR52AE1L
77N39
87N53
X
X
X
X
X
X
X
X
C0SNSR51AE1L
87N52
X
X
X
X
C0MISC19AE1
87N54
X
X
X
X
C0MISC19AE1-
85L43
X
X
X
X
C0MISC16AE1-
90N43
X
X
X
X
C1UVCL10B-1
54W62
OX
OX
OX
OX
COSNSR31AE-1
Factory
17M50
O
X
O
X
O
X
O
X
Factory
Factory
Factory
Factory
54W56
54W57
74M70
Factory
O
O
O
O
OX
OX
OX
O
O
O
O
O
OX
OX
OX
O
O
O
O
O
OX
OX
OX
O
O
O
O
O
OX
OX
OX
O
56W38
56W39
56W40
56W41
56W42
56W43
56W44
56W45
56W46
56W47
56W48
56W49
56W50
56W51
56W52
55W02
55W03
55W04
OX
OX
OX
OX
OX
OX
OX
OX
OX
OX
OX
OX
OX
OX
OX
OX
OX
OX
OX
OX
OX
OX
OX
OX
OX
OX
OX
OX
OX
OX
OX
OX
OX
OX
OX
OX
OX
OX
OX
OX
OX
OX
OX
OX
OX
OX
OX
OX
OX
OX
OX
OX
OX
OX
OX
OX
OX
OX
OX
OX
208/230V - 3 phase
460V - 3 phase
575V - 3 phase
80 amp - C1DISC080B-1
150 amp - C1DISC150B-1
LTAGFIK10/15
208/230V-3ph - C1EHO075B-1Y
460V-3ph - C1EHO075B-1G
575V-3ph - C1EHO075B-1J
208/230V-3ph - C1EHO015B-1Y
460V-3ph - C1EHO150B-1G
575V-3ph - C1EHO150B-1J
208/230V-3ph - C1EHO225B-1Y
460V-3ph - C1EHO225B-1G
575V-3ph - C1EHO225B-1J
208/230V-3ph - C1EHO300B-1Y
460V-3ph - C1EHO300B-1G
575V-3ph - C1EHO300B-1J
208/230V-3ph - C1EHO450B-1Y
460V-3ph - C1EHO450B-1G
575V-3ph - C1EHO450B-1J
208/230V-3ph - C1EHO600B-1Y
460V-3ph - C1EHO600B-1G
575V-3ph - C1EHO600B-1J
Lamps operate on 110-230V single-phase power supply. Step-down transformer may be ordered separately for 460V and 575V units. Alternately, 110V power supply
may be used to directly power the UVC ballast(s)
1
NOTE - Catalog and model numbers shown are for ordering field installed accessories.
OX - Configure To Order (Factory Installed) or Field Installed
O = Configure To Order (Factory Installed)
X = Field Installed
Energence™ Packaged Electric / Electric 7.5 to 12.5 Ton / Page 11
OPTIONS / ACCESSORIES
Model
Number
Item Description
Catalog
Number
Unit Model No
092 102 120
150
ECONOMIZER
Economizer
Economizer - Downflow or Horizontal With Barometric Relief
Dampers (downflow) and Air Hoods
E1ECON15B-1
55W05
OX
OX
OX
OX
Order 2 - C1SNSR64FF1
53W64
OX
OX
OX
OX
Sensor is Furnished
Factory
O
O
O
O
Economizer Controls
Differential Enthalpy
Sensible Control
C1SNSR64FF1
53W64
OX
OX
OX
OX
Sensor Field Provided
Factory
O
O
O
O
LAGEDH03/15
53K04
X
X
X
X
Motorized Dampers with outdoor air hood
E1DAMP20B-1
63W60
OX
OX
OX
OX
Manual Dampers with outdoor air hood
C1DAMP10B-1
53W48
OX
OX
OX
OX
208/230V-3ph - K1PWRE10B-1Y
53W44
OX
OX
OX
OX
460V-3ph - K1PWRE10B-1G
53W45
OX
OX
OX
OX
575V-3ph - K1PWRE10B-1J
53W46
OX
OX
OX
OX
Factory
O
O
O
O
COSNSR31AE-1
17M50
X
X
X
X
8 in. height
C1CURB23B-1
54W46
X
X
X
X
14 in. height
C1CURB20B-1
54W47
X
X
X
X
18 in. height
C1CURB21B-1
54W48
X
X
X
X
24 in. height
C1CURB22B-1
54W49
X
X
X
X
8 in. height
C1CURB12B-1
54W44
X
X
X
X
14 in. height
C1CURB10B-1
54W43
X
X
X
X
24 in. height
C1CURB11B-1
54W45
X
X
X
X
C1CURB55B-1
54W50
X
X
X
X
RTD11-95
29G04
X
RTD11-135
29G05
X
X
RTD11-185
29G06
FD11-95
29G08
FD11-135
29G09
FD11-185
29G10
LASRT08/10
24L14
LASRT10/12
49K55
LASRT15
49K56
Single Enthalpy
Global Control
Horizontal Barometric Relief Dampers With Hood
Horizontal Barometric Relief Dampers - Hood Furnished
OUTDOOR AIR
Outdoor Air Dampers
POWER EXHAUST
Standard Static
HUMIDITROL CONDENSER REHEAT OPTION
®
Humiditrol
Humidity Sensor Kit, Remote mounted (required)
ROOF CURBS - DOWNFLOW
Clip Curb
Standard
Adjustable Pitched Curb
14 in. height
CEILING DIFFUSERS
Step-Down - Order one
Flush - Order one
Transitions (Supply and Return) - Order one
NOTE - Catalog and model numbers shown are for ordering field installed accessories.
OX - Configure To Order (Factory Installed) or Field Installed
O = Configure To Order (Factory Installed)
X = Field Installed
Energence™ Packaged Electric / Electric 7.5 to 12.5 Ton / Page 12
X
X
X
X
X
X
X
X
X
SPECIFICATIONS
General Data
Nominal Tonnage
Model Number
Efficiency Type
Blower Type
Cooling
Performance
Gross Cooling Capacity - Btuh
1
Net Cooling Capacity - Btuh
AHRI Rated Air Flow - cfm
Total Unit Power - kW
1
EER (Btuh/Watt)
2
IEER (Btuh/Watt)
Refrigerant Type
Refrigerant
Circuit 1
Charge
Circuit 2
With
Circuit 1
Humiditrol®
Circuit 2
Electric Heat Available - See page 11
Compressor Type (number)
Outdoor
Net face area (total) - sq. ft.
Coils
Tube diameter - in.
Number of rows
Fins per inch
Outdoor
Motor - (No.) hp
Coil Fans
Motor rpm
Total Motor watts
Diameter - (No.) in.
Number of blades
Total Air volume - cfm
Indoor
Net face area (total) - sq. ft.
Coils
Tube diameter - in.
Number of rows
Fins per inch
Drain connection - Number and size
Expansion device type
3
Indoor
Nominal motor output
Blower and
Maximum usable motor output
Drive
(US Only)
Selection
Motor - Drive kit number
Blower wheel nominal
diameter x width - in.
Filters
Type of filter
Number and size - in.
Electrical characteristics
7.5 Ton
8.5 Ton
10 Ton
12.5 Ton
LCH092H4
LCH102H4
LCH120H4
LCH150S4
High
High
High
Standard
Constant Air
Constant Air
Constant Air
Constant Air
Volume CAV
Volume CAV
Volume CAV
Volume CAV
93,000
103,800
122,000
142,000
90,000
100,000
118,000
136,000
3,000
3,400
3,600
4100
7.5
8.1
9.9
12.4
12.7
12.4
12.2
11
12.9
12.9
13.2
11.2
R-410A
R-410A
R-410A
R-410A
13 lbs. 8 oz.
13 lbs. 8 oz.
14 lbs. 8 oz.
16 lbs. 8 oz.
12 lbs. 8 oz.
12 lbs. 8 oz.
13 lbs. 8 oz.
14 lbs. 8 oz.
17 lbs. 0 oz.
17 lbs. 0 oz.
18 lbs. 0 oz.
18 lbs. 8 oz.
12 lbs. 8 oz.
12 lbs. 8 oz.
13 lbs. 8 oz.
14 lbs. 8 oz.
7.5,15,22.5,30 & 45 KW
15,22.5,30,45 & 60 KW
Scroll (2)
Scroll (2)
Scroll (2)
Scroll (2)
29.33
29.33
29.33
29.33
3/8
3/8
3/8
3/8
3
3
3
3
20
20
20
20
(2) 1/3
(2) 1/3
(2) 1/3
(2) 1/2
1075
1075
1075
1075
725
725
725
920
(2) 24
(2) 24
(2) 24
(2) 24
3
3
3
3
8000
8000
8000
8800
12.78
12.78
13.54
13.54
3/8
3/8
3/8
3/8
4
4
4
4
14
14
14
20
(1) 1 in. NPT coupling
Balance port TXV, removable head
2 hp, 3 hp, 5 hp
2.3 hp, 3.45 hp, 5.75 hp
(1) 15 X 15
2 hp
Kit 1 590-890 rpm (std. and high efficiency)
Kit 2 800-1105 rpm (std. and high efficiency)
Kit 3 795-1195 rpm (std. and high efficiency)
3 hp
Kit 4 730-970 rpm (std. efficiency)
Kit 5 940-1200 rpm (std. efficiency)
Kit 6 1015-1300 rpm (std. efficiency)
Kit 7 730-970 rpm (high efficiency)
Kit 8 940-1200 rpm (high efficiency)
Kit 9 1015-1300 rpm (high efficiency)
5 hp
Kit 10 900-1135 rpm (std. efficiency)
Kit 11 1040-1315 rpm (std. efficiency)
Kit 12 1125-1425 rpm (std. efficiency)
(1) 15 X 15
(1) 15 X 15
(1) 15 X 15
Disposable
(4) 20 x 25 x 2
208/230V, 460V or 575V - 60 hertz - 3 phase
NOTE - Net capacity includes evaporator blower motor heat deduction. Gross capacity does not include evaporator blower motor heat deduction.
1
AHRI Certified to AHRI Standard 340/360; 95°F outdoor air temperature and 80°F db/67°F wb entering evaporator air; minimum external duct static pressure.
2
Integrated Energy Efficiency Ratio certified and tested according to AHRI Standard 340/360.
3
Using total air volume and system static pressure requirements determine from blower performance tables rpm and motor output required. Maximum usable output of
motors furnished are shown. In Canada, nominal motor output is also maximum usable motor output. If motors of comparable output are used, be sure to keep within
the service factor limitations outlined on the motor nameplate.
Energence™ Packaged Electric / Electric 7.5 to 12.5 Ton / Page 13
RATINGS
NOTE − For Temperatures and Capacities not shown in tables, see bulletin − Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.
7.5 TON HIGH EFFICIENCY LCH092H4 (1ST STAGE)
Outdoor Air Temperature Entering Outdoor Coil
Entering
65°F
75°F
85°F
95°F
Total
Wet
Air
Total Comp. Sensible To Total Total Comp. Sensible To Total Total Comp. Sensible To Total Total Comp. Sensible To Total
Bulb
Volume Cool Motor
Ratio (S/T)
Ratio (S/T)
Ratio (S/T)
Ratio (S/T)
Cool Motor
Cool Motor
Cool Motor
TemperCap. Input
Cap. Input
Cap. Input
Cap. Input
Dry Bulb
Dry Bulb
Dry Bulb
Dry Bulb
ature
cfm
kBtuh
kW
75°F 80°F 85°F kBtuh
kW
75°F 80°F 85°F kBtuh
kW
75°F 80°F 85°F kBtuh
kW
75°F 80°F 85°F
2400
42.9
1.98
.62
.76
.93
41.3
2.23
.63
.78
.95
39.6
2.52
.64
.79
.98
37.9
2.84
.65
.82
1.00
63°F
3000
45.0
1.98
.66
.85 1.00 43.4
2.24
.67
.87
1.00 41.6
2.52
.69
.90 1.00 39.7
2.85
.71
.94
1.00
3600
46.7
1.99
.71
.94 1.00 44.9
2.24
.74
.97
1.00 43.1
2.53
.75
.99 1.00 41.2
2.85
.78
1.00 1.00
2400
45.2
1.98
.50
.60
.71
43.7
2.24
.50
.61
.73
42.0
2.52
.51
.62
.75
40.1
2.85
.51
.63
.77
67°F
3000
47.5
1.99
.52
.64
.80
45.8
2.25
.53
.65
.83
43.8
2.53
.54
.66
.85
41.9
2.85
.55
.68
.89
3600
49.3
2.00
.55
.69
.89
47.4
2.25
.56
.70
.93
45.4
2.54
.57
.73
.96
43.1
2.86
.57
.75
.99
2400
47.8
1.99
.38
.48
.58
46.1
2.25
.39
.49
.59
44.3
2.53
.39
.50
.60
42.3
2.85
.38
.50
.61
71°F
3000
50.1
2.00
.39
.51
.62
48.3
2.26
.39
.52
.63
46.2
2.54
.40
.52
.64
44.2
2.86
.40
.54
.66
3600
51.7
2.01
.40
.54
.67
49.8
2.26
.41
.55
.68
47.8
2.54
.41
.56
.70
45.4
2.86
.42
.56
.73
7.5 TON HIGH EFFICIENCY LCH092H4 (2ND STAGE)
Entering
Total
Wet
Air
Bulb
Volume
Temperature
cfm
2400
63°F
3000
3600
2400
67°F
3000
3600
2400
71°F
3000
3600
Total
Cool
Cap.
kBtuh
87.9
92.3
95.6
93.0
97.3
100.6
98.2
102.5
105.9
Outdoor Air Temperature Entering Outdoor Coil
85°F
95°F
105°F
115°F
Comp. Sensible To Total Total Comp. Sensible To Total Total Comp. Sensible To Total Total Comp. Sensible To Total
Ratio (S/T)
Ratio (S/T)
Ratio (S/T)
Ratio (S/T)
Motor
Cool Motor
Cool Motor
Cool Motor
Input
Cap. Input
Cap. Input
Cap. Input
Dry Bulb
Dry Bulb
Dry Bulb
Dry Bulb
kW
75°F 80°F 85°F kBtuh
kW
75°F 80°F 85°F kBtuh
kW
75°F 80°F 85°F kBtuh
kW
75°F 80°F 85°F
5.19
.69
.83
.98
84.0
5.86
.70
.85
1.00 79.8
6.64
.72
.88 1.00 75.2
7.55
.74
.92
1.00
5.20
.74
.92 1.00 88.0
5.87
.76
.95
1.00 83.5
6.64
.78
.98 1.00 78.7
7.54
.81
1.00 1.00
5.21
.79 1.00 1.00 91.4
5.87
.82
1.00 1.00 87.3
6.64
.85 1.00 1.00 82.9
7.55
.88
1.00 1.00
5.20
.55
.66
.79
89.0
5.87
.55
.68
.81
84.5
6.64
.56
.69
.84
79.5
7.54
.58
.71
.87
5.21
.58
.71
.88
93.0
5.88
.59
.73
.91
88.2
6.65
.60
.76
.94
82.8
7.54
.61
.78
.98
5.22
.61
.77
.97
95.7
5.88
.62
.79
.99
90.8
6.65
.63
.82 1.00 85.2
7.54
.64
.86
1.00
5.21
.42
.53
.64
93.8
5.88
.42
.54
.65
89.0
6.65
.42
.54
.67
84.2
7.54
.43
.56
.69
5.23
.43
.56
.69
97.9
5.89
.43
.58
.71
92.9
6.65
.44
.59
.73
87.5
7.54
.44
.60
.76
5.24
.44
.60
.75 100.8 5.89
.45
.61
.77
95.4
6.65
.45
.62
.79
89.9
7.54
.46
.64
.84
8.5 TON HIGH EFFICIENCY LCH102H4 (1ST STAGE)
Outdoor Air Temperature Entering Outdoor Coil
Entering
65°F
75°F
85°F
95°F
Total
Wet
Air
Total Comp. Sensible To Total Total Comp. Sensible To Total Total Comp. Sensible To Total Total Comp. Sensible To Total
Bulb
Volume Cool Motor
Ratio (S/T)
Ratio (S/T)
Ratio (S/T)
Ratio (S/T)
Cool Motor
Cool Motor
Cool Motor
TemperCap. Input
Cap. Input
Cap. Input
Cap. Input
Dry Bulb
Dry Bulb
Dry Bulb
Dry Bulb
ature
cfm
kBtuh
kW
75°F 80°F 85°F kBtuh
kW
75°F 80°F 85°F kBtuh
kW
75°F 80°F 85°F kBtuh
kW
75°F 80°F 85°F
2720
52.3
2.13
.62
.76
.96
50.4
2.41
.63
.78
.98
48.4
2.73
.64
.81 1.00 46.3
3.08
.65
.84
1.00
63°F
3400
54.8
2.14
.66
.87 1.00 52.7
2.42
.67
.90
1.00 50.6
2.73
.69
.93 1.00 48.4
3.09
.71
.97
1.00
4080
56.6
2.15
.72
.97 1.00 54.6
2.43
.74
.99
1.00 52.4
2.74
.77 1.00 1.00 50.3
3.09
.80
1.00 1.00
2720
55.2
2.14
.49
.60
.71
53.2
2.42
.50
.61
.73
51.2
2.73
.50
.62
.76
48.7
3.09
.50
.63
.79
67°F
3400
57.7
2.15
.52
.64
.82
55.6
2.43
.52
.65
.84
53.3
2.74
.54
.67
.88
50.9
3.09
.55
.68
.92
4080
59.7
2.16
.55
.69
.93
57.4
2.44
.56
.71
.96
54.9
2.74
.56
.73
.99
52.4
3.10
.57
.76
1.00
2720
58.0
2.16
.38
.48
.58
56.1
2.43
.38
.49
.59
53.8
2.74
.38
.49
.60
51.3
3.09
.38
.50
.61
71°F
3400
60.7
2.16
.39
.51
.62
58.4
2.44
.39
.51
.63
56.0
2.75
.39
.53
.65
53.6
3.10
.40
.54
.67
4080
62.5
2.17
.40
.53
.67
60.2
2.45
.40
.55
.68
57.8
2.75
.40
.56
.71
55.0
3.10
.41
.56
.73
8.5 TON HIGH EFFICIENCY LCH102H4 (2ND STAGE)
Entering
Total
Wet
Air
Bulb
Volume
Temperature
cfm
2720
63°F
3400
4080
2720
67°F
3400
4080
2720
71°F
3400
4080
Total
Cool
Cap.
kBtuh
98.8
103.3
106.9
104.3
108.8
112.0
109.6
114.3
117.8
Outdoor Air Temperature Entering Outdoor Coil
85°F
95°F
105°F
115°F
Comp. Sensible To Total Total Comp. Sensible To Total Total Comp. Sensible To Total Total Comp. Sensible To Total
Ratio (S/T)
Ratio (S/T)
Ratio (S/T)
Ratio (S/T)
Motor
Cool Motor
Cool Motor
Cool Motor
Input
Cap. Input
Cap. Input
Cap. Input
Dry Bulb
Dry Bulb
Dry Bulb
Dry Bulb
kW
75°F 80°F 85°F kBtuh
kW
75°F 80°F 85°F kBtuh
kW
75°F 80°F 85°F kBtuh
kW
75°F 80°F 85°F
5.54
.70
.85 1.00 94.4
6.27
.72
.88
1.00 89.7
7.10
.73
.91 1.00 84.7
8.09
.76
.95
1.00
5.56
.76
.95 1.00 98.6
6.27
.78
.98
1.00 93.5
7.11
.80 1.00 1.00 88.7
8.08
.83
1.00 1.00
5.56
.82 1.00 1.00 102.6 6.28
.84
1.00 1.00 98.2
7.12
.88 1.00 1.00 93.1
8.08
.91
1.00 1.00
5.56
.55
.68
.81
99.6
6.28
.56
.69
.84
94.7
7.11
.57
.71
.87
89.3
8.08
.59
.73
.91
5.57
.59
.74
.91 103.8 6.29
.60
.76
.94
98.5
7.12
.61
.78
.97
92.7
8.08
.62
.81
1.00
5.58
.62
.80
.99 106.6 6.30
.63
.82
1.00 101.2 7.12
.65
.85 1.00 95.2
8.08
.66
.89
1.00
5.57
.42
.54
.66 104.7 6.29
.43
.55
.67
99.7
7.12
.43
.56
.69
94.1
8.08
.43
.58
.71
5.59
.43
.58
.72 109.2 6.30
.44
.59
.74 103.6 7.12
.45
.60
.76
97.4
8.08
.45
.61
.78
5.60
.45
.61
.77 112.2
6.31
.45
.62
.80 106.4 7.13
.46
.64
.83 100.0 8.08
.47
.66
.86
Energence™ Packaged Electric / Electric 7.5 to 12.5 Ton / Page 14
RATINGS
NOTE − For Temperatures and Capacities not shown in tables, see bulletin − Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.
10 TON HIGH EFFICIENCY LCH120H4 (1ST STAGE)
Outdoor Air Temperature Entering Outdoor Coil
Entering
65°F
75°F
85°F
95°F
Total
Wet
Air
Total Comp. Sensible To Total Total Comp. Sensible To Total Total Comp. Sensible To Total Total Comp. Sensible To Total
Bulb
Volume Cool Motor
Ratio (S/T)
Ratio (S/T)
Ratio (S/T)
Ratio (S/T)
Cool Motor
Cool Motor
Cool Motor
TemperCap. Input
Cap. Input
Cap. Input
Cap. Input
Dry Bulb
Dry Bulb
Dry Bulb
Dry Bulb
ature
cfm
kBtuh
kW
75°F 80°F 85°F kBtuh
kW
75°F 80°F 85°F kBtuh
kW
75°F 80°F 85°F kBtuh
kW
75°F 80°F 85°F
3200
61.5
2.61
.64
.78
.95
59.3
2.96
.65
.80
.97
56.8
3.34
.66
.82 1.00 54.3
3.77
.67
.85
1.00
63°F
4000
64.5
2.64
.68
.86 1.00 62.2
2.99
.70
.89
1.00 59.5
3.37
.71
.93 1.00 56.8
3.80
.74
.96
1.00
4800
66.8
2.67
.73
.95 1.00 64.3
3.02
.76
.98
1.00 61.5
3.40
.78 1.00 1.00 58.8
3.83
.81
1.00 1.00
3200
64.8
2.65
.51
.62
.73
62.5
2.99
.52
.63
.75
60.0
3.38
.52
.64
.78
57.2
3.81
.53
.65
.80
67°F
4000
68.1
2.68
.53
.66
.82
65.5
3.03
.54
.67
.84
62.7
3.41
.55
.69
.88
59.8
3.84
.56
.70
.91
4800
70.3
2.71
.56
.70
.91
67.7
3.06
.58
.73
.94
64.7
3.44
.58
.75
.98
61.6
3.87
.60
.78
1.00
3200
68.5
2.69
.40
.50
.60
66.0
3.04
.39
.50
.61
63.4
3.42
.40
.51
.62
60.5
3.85
.40
.52
.63
71°F
4000
71.5
2.72
.40
.52
.64
68.9
3.07
.40
.53
.65
65.9
3.46
.41
.54
.67
62.7
3.88
.41
.55
.68
4800
73.9
2.75
.41
.55
.68
70.9
3.10
.42
.56
.70
67.9
3.48
.43
.57
.73
64.7
3.91
.43
.58
.75
10 TON HIGH EFFICIENCY LCH120H4 (2ND STAGE)
Entering
Total
Wet
Air
Bulb
Volume
Temperature
cfm
3200
63°F
4000
4800
3200
67°F
4000
4800
3200
71°F
4000
4800
Total
Cool
Cap.
kBtuh
118.3
123.7
127.9
124.8
130.2
134.2
131.6
136.6
140.5
Outdoor Air Temperature Entering Outdoor Coil
85°F
95°F
105°F
115°F
Comp. Sensible To Total Total Comp. Sensible To Total Total Comp. Sensible To Total Total Comp. Sensible To Total
Ratio (S/T)
Ratio (S/T)
Ratio (S/T)
Ratio (S/T)
Motor
Cool Motor
Cool Motor
Cool Motor
Input
Cap. Input
Cap. Input
Cap. Input
Dry Bulb
Dry Bulb
Dry Bulb
Dry Bulb
kW
75°F 80°F 85°F kBtuh
kW
75°F 80°F 85°F kBtuh
kW
75°F 80°F 85°F kBtuh
kW
75°F 80°F 85°F
7.09
.67
.83 1.00 113.1
8.00
.68
.86
1.00 107.4 9.04
.70
.89 1.00 101.4 10.23
.72
.93
1.00
7.16
.72
.94 1.00 118.2
8.07
.75
.97
1.00 112.2
9.11
.78 1.00 1.00 106.1 10.29
.81
1.00 1.00
7.21
.79 1.00 1.00 122.7 8.13
.82
1.00 1.00 116.9
9.17
.85 1.00 1.00 111.3 10.37
.90
1.00 1.00
7.17
.53
.65
.79 119.2
8.08
.54
.66
.81
113.4
9.12
.54
.68
.84 106.8 10.30
.56
.70
.89
7.24
.56
.70
.90 124.4 8.16
.57
.72
.93
118.1
9.19
.58
.75
.97 111.1 10.36
.60
.78
1.00
7.29
.59
.77
.99 127.9 8.21
.61
.80
1.00 121.0 9.23
.62
.82 1.00 114.1 10.40
.64
.87
1.00
7.26
.40
.52
.63 125.7 8.17
.41
.52
.64
119.6
9.21
.41
.53
.66 112.8 10.38
.41
.55
.68
7.33
.42
.55
.68 130.6 8.24
.42
.56
.70 123.7 9.27
.43
.58
.72 116.7 10.45
.43
.59
.75
7.38
.43
.58
.74 134.1 8.29
.44
.60
.77 127.3 9.32
.44
.62
.80 119.5 10.49
.45
.63
.84
12.5 TON STANDARD EFFICIENCY LCH150S4B (1ST STAGE)
Outdoor Air Temperature Entering Outdoor Coil
Entering
65°F
75°F
85°F
95°F
Total
Wet
Air
Total Comp. Sensible To Total Total Comp. Sensible To Total Total Comp. Sensible To Total Total Comp. Sensible To Total
Bulb
Volume Cool Motor
Ratio (S/T)
Ratio (S/T)
Ratio (S/T)
Ratio (S/T)
Cool Motor
Cool Motor
Cool Motor
TemperCap. Input
Cap. Input
Cap. Input
Cap. Input
Dry Bulb
Dry Bulb
Dry Bulb
Dry Bulb
ature
cfm
kBtuh
kW
75°F 80°F 85°F kBtuh
kW
75°F 80°F 85°F kBtuh
kW
75°F 80°F 85°F kBtuh
kW
75°F 80°F 85°F
3800
79.6
3.27 0.64 0.78 0.95 76.6
3.66
0.65
0.8
0.98 73.2
4.1
0.66 0.83
1
69.5
4.59
0.67 0.86
1
63°F
4400
82.3
3.29 0.67 0.84
1
79
3.69
0.68 0.86
1
75.5
4.13 0.69 0.9
1
71.8
4.62
0.71 0.93
1
5000
84.5
3.32 0.69 0.91
1
81.1
3.71
0.72 0.93
1
77.5
4.15 0.73 0.97
1
73.8
4.65
0.77
1
1
3800
84.1
3.31 0.51 0.62 0.74 80.8
3.71
0.51 0.63 0.76 77.4
4.15 0.52 0.64 0.78 73.5
4.64
0.52 0.65 0.81
67°F
4400
86.9
3.35 0.52 0.65 0.8
83.3
3.74
0.53 0.66 0.82 79.6
4.18 0.54 0.67 0.85 75.8
4.68
0.55 0.69 0.88
5000
89.1
3.37 0.54 0.67 0.86 85.5
3.77
0.55 0.69 0.89 81.4
4.21 0.56 0.71 0.92 77.5
4.7
0.57 0.73 0.96
3800
88.8
3.37 0.39 0.49 0.59 85.2
3.77
0.39
0.5
0.61 81.6
4.21
0.4
0.5 0.62 77.7
4.71
0.39 0.51 0.63
71°F
4400
91.3
3.4
0.4 0.51 0.62 87.9
3.8
0.4
0.52 0.63 83.9
4.24
0.4 0.53 0.65 79.7
4.73
0.4
0.53 0.66
5000
93.7
3.43
0.4 0.53 0.65 89.9
3.83
0.41 0.54 0.66 85.8
4.27 0.41 0.55 0.68 81.5
4.76
0.41 0.56
0.7
12.5 TON STANDARD EFFICIENCY LCH150S4B (2ND STAGE)
Entering
Total
Wet
Air
Bulb
Volume
Temperature
cfm
3800
63°F
4400
5000
3800
67°F
4400
5000
3800
71°F
4400
5000
Total
Cool
Cap.
kBtuh
138.7
143.3
147
146.6
151.2
154.5
154.9
159
162.8
Outdoor Air Temperature Entering Outdoor Coil
85°F
95°F
105°F
115°F
Comp. Sensible To Total Total Comp. Sensible To Total Total Comp. Sensible To Total Total Comp. Sensible To Total
Ratio (S/T)
Ratio (S/T)
Ratio (S/T)
Ratio (S/T)
Motor
Cool Motor
Cool Motor
Cool Motor
Input
Cap. Input
Cap. Input
Cap. Input
Dry Bulb
Dry Bulb
Dry Bulb
Dry Bulb
kW
75°F 80°F 85°F kBtuh
kW
75°F 80°F 85°F kBtuh
kW
75°F 80°F 85°F kBtuh
kW
75°F 80°F 85°F
8.68 0.71 0.86
1
131.9 9.72
0.73 0.89
1
124.7 10.91 0.75 0.92
1
116.8 12.25 0.77 0.96
1
8.74 0.75 0.92
1
136
9.79
0.77 0.95
1
128.7 10.97 0.8 0.99
1
120.9 12.32 0.83
1
1
8.8
0.78 0.98
1
139.9 9.84
0.82
1
1
132.6 11.04 0.84
1
1
125.4 12.39 0.87
1
1
8.79 0.56 0.69 0.83 139.3 9.84
0.57
0.7
0.85
132
11.02 0.58 0.72 0.88 123.5 12.36
0.6
0.75 0.92
8.86 0.58 0.72 0.88 143.6
9.9
0.6
0.74 0.91 135.4 11.08 0.61 0.77 0.95
127
12.43 0.63
0.8
0.99
8.91
0.6 0.76 0.94 146.9 9.95
0.62 0.79 0.98 138.5 11.13 0.64 0.82
1
129.6 12.47 0.65 0.86
1
8.91 0.42 0.55 0.67 147.3 9.96
0.43 0.56 0.68 139.3 11.15 0.43 0.56 0.7 130.7 12.48 0.44 0.58 0.72
8.98 0.43 0.57 0.7 150.9 10.02 0.44 0.58 0.72 142.6
11.2 0.44 0.59 0.74 133.6 12.54 0.45 0.61 0.78
9.04 0.44 0.59 0.74 154.6 10.08 0.45 0.61 0.76 145.8 11.26 0.46 0.62 0.79 136.5 12.59 0.46 0.64 0.83
Energence™ Packaged Electric / Electric 7.5 to 12.5 Ton / Page 15
HUMIDITROL® DEHUMIDIFICATION SYSTEM RATINGS
7.5 TON HIGH EFFICIENCY LCH092H4 WITH HUMIDITROL OPERATING (1ST STAGE)
Outdoor Air Temperature Entering Outdoor Coil
Entering
65°F
75°F
85°F
95°F
Total
Wet
Air
Total Comp. Sensible To Total Total Comp. Sensible To Total Total Comp. Sensible To Total Total Comp. Sensible To Total
Bulb
Volume Cool Motor
Ratio (S/T)
Ratio (S/T)
Ratio (S/T)
Ratio (S/T)
Cool Motor
Cool Motor
Cool Motor
TemperCap. Input
Cap. Input
Cap. Input
Cap. Input
Dry Bulb
Dry Bulb
Dry Bulb
Dry Bulb
ature
cfm
kBtuh
kW
75°F 80°F 85°F kBtuh
kW
75°F 80°F 85°F kBtuh
kW
75°F 80°F 85°F kBtuh
kW
75°F 80°F 85°F
2400
26.1
1.9
.45
.63
.81
22.1
2.2
.33
.55
.77
18.0
2.4
.21
.47
.73
14.0
2.6
.09
.39
.69
63°F
3000
30.8
1.9
.49
.69
.89
26.0
2.2
.36
.59
.82
21.2
2.4
.22
.48
.74
16.4
2.6
.09
.37
.66
3600
35.5
1.9
.54
.76
.98
29.9
2.2
.39
.62
.86
24.3
2.4
.24
.49
.74
18.7
2.6
.09
.36
.63
2400
33.8
2.0
.32
.48
.64
29.1
2.2
.20
.39
.58
24.3
2.4
.07
.30
.52
19.5
2.7
-.05
.21
.46
67°F
3000
38.0
2.0
.35
.52
.70
32.8
2.2
.20
.41
.62
27.6
2.4
.06
.30
.54
22.4
2.7
-.08
.19
.47
3600
42.1
2.0
.37
.56
.75
36.5
2.2
.21
.44
.66
30.9
2.4
.05
.31
.56
25.4
2.7
-.10
.18
.47
2400
41.6
2.0
.19
.33
.47
37.0
2.2
.07
.23
.39
30.5
2.5
-.06 .12
.31
25.0
2.7
-.19
.02
.23
71°F
3000
45.1
2.0
.20
.35
.50
39.6
2.2
.05
.24
.42
34.1
2.5
-.10 .12
.35
28.5
2.7
-.24
.01
.27
3600
48.7
2.0
.20
.37
.53
43.1
2.2
.03
.25
.46
41.5
2.5
-.13 .13
.39
32.0
2.7
-.30
.01
.31
7.5 TON HIGH EFFICIENCY LCH092H4 WITH HUMIDITROL OPERATING (2ND STAGE)
Entering
Total
Wet
Air
Bulb
Volume
Temperature
cfm
2400
63°F
3000
3600
2400
67°F
3000
3600
2400
71°F
3000
3600
Outdoor Air Temperature Entering Outdoor Coil
65°F
75°F
85°F
95°F
Total Comp. Sensible To Total Total Comp. Sensible To Total Total Comp. Sensible To Total Total Comp. Sensible To Total
Ratio (S/T)
Ratio (S/T)
Ratio (S/T)
Ratio (S/T)
Cool Motor
Cool Motor
Cool Motor
Cool Motor
Cap. Input
Cap. Input
Cap. Input
Cap. Input
Dry Bulb
Dry Bulb
Dry Bulb
Dry Bulb
kBtuh
kW
75°F 80°F 85°F kBtuh
kW
75°F 80°F 85°F kBtuh
kW
75°F 80°F 85°F kBtuh
kW
75°F 80°F 85°F
75.3
4.0
.63
.76
.89
68.2
4.5
.62
.78
.92
61.2
5.0
.61
.80
.96
54.1
5.5
.60
.82
1.00
78.8
4.0
.68
.81
.94
71.2
4.5
.68
.82
.96
63.5
5.0
.67
.83
.98
55.9
5.5
.67
.83
1.00
82.3
4.0
.73
.90 1.00 74.1
4.5
.73
.90
1.00 65.9
5.0
.73
.89 1.00 57.7
5.5
.74
.88
1.00
84.0
4.0
.48
.61
.73
78.0
4.5
.46
.60
.75
72.0
5.0
.43
.60
.76
66.1
5.5
.41
.60
.77
88.6
4.0
.51
.65
.79
81.7
4.5
.49
.64
.79
74.8
5.1
.47
.63
.80
68.0
5.6
.45
.63
.81
93.3
4.1
.53
.71
.84
85.5
4.6
.52
.69
.84
77.6
5.1
.50
.68
.84
69.8
5.6
.49
.67
.84
92.7
4.1
.33
.45
.58
87.8
4.6
.29
.43
.57
82.9
5.1
.25
.40
.55
78.0
5.6
.22
.38
.54
98.5
4.1
.34
.48
.63
92.3
4.6
.30
.46
.62
86.2
5.1
.26
.44
.62
80.0
5.6
.22
.42
.61
104.2
4.1
.34
.51
.68
96.8
4.6
.30
.49
.68
89.4
5.1
.27
.48
.68
82.0
5.6
.23
.46
.68
8.5 TON HIGH EFFICIENCY LCH102H4 WITH HUMIDITROL OPERATING (1ST STAGE)
Outdoor Air Temperature Entering Outdoor Coil
Entering
65°F
75°F
85°F
95°F
Total
Wet
Air
Total Comp. Sensible To Total Total Comp. Sensible To Total Total Comp. Sensible To Total Total Comp. Sensible To Total
Bulb
Volume Cool Motor
Ratio (S/T)
Ratio (S/T)
Ratio (S/T)
Ratio (S/T)
Cool Motor
Cool Motor
Cool Motor
TemperCap. Input
Cap. Input
Cap. Input
Cap. Input
Dry Bulb
Dry Bulb
Dry Bulb
Dry Bulb
ature
cfm
kBtuh
kW
75°F 80°F 85°F kBtuh
kW
75°F 80°F 85°F kBtuh
kW
75°F 80°F 85°F kBtuh
kW
75°F 80°F 85°F
2720
34.2
2.1
.47
.57
.67
28.5
2.3
.34
.51
.68
22.7
2.6
.22
.45
.68
17.0
2.9
.09
.39
.69
63°F
3400
39.1
2.1
.49
.64
.78
32.4
2.3
.37
.58
.80
25.8
2.6
.24
.53
.82
19.1
2.8
.12
.48
.84
4080
44.0
2.1
.51
.70
.89
36.4
2.3
.39
.66
.93
28.9
2.6
.26
.62
.96
21.3
2.8
.14
.57
1.00
2720
42.5
2.1
.33
.44
.55
37.8
2.4
.19
.36
.52
33.2
2.6
.06
.27
.48
28.5
2.9
-.07
.19
.45
67°F
3400
47.0
2.1
.33
.48
.62
41.5
2.4
.20
.40
.60
31.8
2.6
.06
.32
.57
30.5
2.9
-.07
.24
.55
4080
51.5
2.1
.34
.52
.70
45.1
2.4
.20
.44
.68
38.8
2.6
.06
.36
.66
32.4
2.9
-.08
.29
.65
2720
50.7
2.1
.18
.31
.44
47.2
2.4
.05
.20
.36
43.6
2.7
-.09 .10
.29
40.1
2.9
-.23
-.01
.21
71°F
3400
54.9
2.2
.18
.32
.47
50.5
2.4
.03
.21
.40
46.2
2.7
-.12 .11
.33
41.8
2.9
-.26
.00
.25
4080
59.0
2.2
.17
.34
.50
51.8
2.4
.02
.23
.44
48.7
2.7
-.14 .11
.37
43.5
2.9
-.29
.00
.30
8.5 TON HIGH EFFICIENCY LCH102H4 WITH HUMIDITROL OPERATING (2ND STAGE)
Outdoor Air Temperature Entering Outdoor Coil
Entering
65°F
75°F
85°F
95°F
Total
Wet
Air
Total Comp. Sensible To Total Total Comp. Sensible To Total Total Comp. Sensible To Total Total Comp. Sensible To Total
Bulb
Volume Cool Motor
Ratio (S/T)
Ratio (S/T)
Ratio (S/T)
Ratio (S/T)
Cool Motor
Cool Motor
Cool Motor
TemperCap. Input
Cap. Input
Cap. Input
Cap. Input
Dry Bulb
Dry Bulb
Dry Bulb
Dry Bulb
ature
cfm
kBtuh
kW
75°F 80°F 85°F kBtuh
kW
75°F 80°F 85°F kBtuh
kW
75°F 80°F 85°F kBtuh
kW
75°F 80°F 85°F
2720
85.3
4.3
.64
.81
.97
77.9
4.9
.63
.82
1.00 70.5
5.5
.62
.84 1.00 63.1
6.0
.60
.86
1.00
63°F
3400
89.2
4.3
.69
.84
.98
81.7
4.9
.69
.84
1.00 74.2
5.5
.68
.84 1.00 66.7
6.0
.68
.84
1.00
4080
93.1
4.4
.75
.87
.99
85.5
4.9
.75
.88
1.00 77.8
5.5
.75
.89 1.00 70.2
6.0
.76
.90
1.00
2720
100.8
4.4
.48
.63
.77
93.3
5.0
.45
.62
.77
85.9
5.5
.43
.62
.77
78.5
6.1
.40
.62
.78
67°F
3400
104.5
4.4
.51
.66
.80
97.8
5.0
.49
.65
.80
89.2
5.5
.46
.64
.81
81.5
6.1
.44
.62
.81
4080
108.2
4.4
.54
.69
.83 100.3
5.0
.52
.68
.84
92.4
5.5
.50
.68
.84
84.6
6.1
.48
.67
.84
2720
116.2
4.4
.32
.45
.58 112.6
5.0
.28
.42
.57 101.3
5.6
.24
.40
.56
93.8
6.2
.20
.37
.55
71°F
3400
119.7
4.5
.33
.48
.63 115.2
5.0
.29
.45
.62 104.1
5.6
.24
.43
.62
96.4
6.2
.20
.41
.62
4080
123.2
4.5
.34
.51
.68 118.1
5.1
.29
.49
.68 107.0
5.6
.25
.46
.68
98.9
6.2
.20
.44
.68
Energence™ Packaged Electric / Electric 7.5 to 12.5 Ton / Page 16
HUMIDITROL® DEHUMIDIFICATION SYSTEM RATINGS
10 TON HIGH EFFICIENCY LCH120H4 WITH HUMIDITROL OPERATING (1ST STAGE)
Outdoor Air Temperature Entering Outdoor Coil
Entering
65°F
75°F
85°F
95°F
Total
Wet
Air
Total Comp. Sensible To Total Total Comp. Sensible To Total Total Comp. Sensible To Total Total Comp. Sensible To Total
Bulb
Volume Cool Motor
Ratio (S/T)
Ratio (S/T)
Ratio (S/T)
Ratio (S/T)
Cool Motor
Cool Motor
Cool Motor
TemperCap. Input
Cap. Input
Cap. Input
Cap. Input
Dry Bulb
Dry Bulb
Dry Bulb
Dry Bulb
ature
cfm
kBtuh
kW
75°F 80°F 85°F kBtuh
kW
75°F 80°F 85°F kBtuh
kW
75°F 80°F 85°F kBtuh
kW
75°F 80°F 85°F
3200
49.5
2.6
.48
.70
.92
42.3
2.9
.39
.66
.94
35.1
3.2
.22
.60
.98
27.9
3.5
.01
.46
1.00
63°F
4000
59.0
2.6
.56
.82 1.00 49.1
2.9
.45
.81
1.00 39.1
3.2
.31
.80
.93
29.2
3.5
-.01
.77
.97
4800
68.6
2.6
.62
.92 1.00 55.9
2.9
.56
.96
1.00 43.2
3.2
.41 1.00 1.00 30.5
3.5
-.02
.97
.80
3200
61.2
2.7
.30
.49
.66
52.4
3.0
.20
.41
.64
43.5
3.3
.01
.30
.59
34.7
3.6
-.06
.08
.50
67°F
4000
68.2
2.7
.34
.55
.77
57.7
3.0
.23
.49
.75
47.1
3.3
.05
.38
.75
36.5
3.6
-.12
.15
.72
4800
75.2
2.7
.37
.62
.87
62.9
3.0
.26
.57
.89
50.7
3.3
.06
.50
.92
38.4
3.6
-.18
.28
.98
3200
73.0
2.7
.17
.32
.48
62.5
3.0
.06
.24
.42
52.0
3.3
-.12 .11
.34
41.5
3.6
-.13
.03
.19
71°F
4000
77.4
2.7
.17
.35
.54
66.2
3.0
.05
.28
.50
55.1
3.3
-.14 .15
.42
43.9
3.6
-.23
-.04
.28
4800
81.9
2.8
.19
.39
.61
70.0
3.1
.06
.31
.57
58.1
3.4
-.16 .18
.51
46.3
3.7
-.34
-.09
.40
10 TON HIGH EFFICIENCY LCH120H4 WITH HUMIDITROL OPERATING (2ND STAGE)
Entering
Total
Wet
Air
Bulb
Volume
Temperature
cfm
3200
63°F
4000
4800
3200
67°F
4000
4800
3200
71°F
4000
4800
Total
Cool
Cap.
kBtuh
104.7
114.8
125.0
118.9
128.7
138.4
133.1
142.5
151.9
Outdoor Air Temperature Entering Outdoor Coil
65°F
75°F
85°F
95°F
Comp. Sensible To Total Total Comp. Sensible To Total Total Comp. Sensible To Total Total Comp. Sensible To Total
Ratio (S/T)
Ratio (S/T)
Ratio (S/T)
Ratio (S/T)
Motor
Cool Motor
Cool Motor
Cool Motor
Input
Cap. Input
Cap. Input
Cap. Input
Dry Bulb
Dry Bulb
Dry Bulb
Dry Bulb
kW
75°F 80°F 85°F kBtuh
kW
75°F 80°F 85°F kBtuh
kW
75°F 80°F 85°F kBtuh
kW
75°F 80°F 85°F
5.4
.61
.73
.86
95.0
6.1
.58
.75
.91
85.3
6.8
.56
.76
.95
75.5
7.5
.53
.77
1.00
5.5
.63
.78
.93 103.4
6.2
.62
.78
.95
91.9
6.8
.60
.79
.98
80.5
7.5
.59
.79
1.00
5.5
.65
.82
.99 111.8
6.2
.65
.82
1.00 98.6
6.9
.65
.82 1.00 85.4
7.5
.64
.82
1.00
5.5
.45
.57
.69 108.5
6.2
.42
.57
.71
98.1
6.9
.39
.56
.73
87.7
7.6
.36
.56
.74
5.6
.47
.60
.74 117.3
6.3
.44
.59
.75 105.9
6.9
.42
.59
.75
94.5
7.6
.39
.58
.76
5.6
.48
.64
.79 126.1
6.3
.46
.62
.79
113.8
7.0
.44
.61
.78 101.4
7.6
.42
.60
.78
5.6
.29
.41
.53 122.0
6.3
.26
.39
.51
110.9
7.0
.23
.36
.50
99.8
7.7
.20
.34
.49
5.7
.30
.43
.56 131.2
6.4
.27
.41
.55
119.9
7.1
.23
.38
.53 108.6
7.7
.19
.36
.52
5.8
.31
.45
.59 140.4
6.4
.27
.42
.58 128.9
7.1
.23
.40
.57 117.5
7.7
.19
.37
.56
12.5 TON STANDARD EFFICIENCY LCH150S4 WITH HUMIDITROL OPERATING (1ST STAGE)
Outdoor Air Temperature Entering Outdoor Coil
Entering
65°F
75°F
85°F
95°F
Total
Wet
Air
Total Comp. Sensible To Total Total Comp. Sensible To Total Total Comp. Sensible To Total Total Comp. Sensible To Total
Bulb
Volume Cool Motor
Ratio (S/T)
Ratio (S/T)
Ratio (S/T)
Ratio (S/T)
Cool Motor
Cool Motor
Cool Motor
TemperCap. Input
Cap. Input
Cap. Input
Cap. Input
Dry Bulb
Dry Bulb
Dry Bulb
Dry Bulb
ature
cfm
kBtuh
kW
75°F 80°F 85°F kBtuh
kW
75°F 80°F 85°F kBtuh
kW
75°F 80°F 85°F kBtuh
kW
75°F 80°F 85°F
3800
55.2
3.4
.48
.70
.91
45.8
3.8
.40
.67
.94
36.4
4.1
.25
.61
.97
27.0
4.5
.33
.51
.99
63°F
4400
58.2
3.5
.53
.77 1.00 47.9
3.8
.45
.76
1.00 37.6
4.1
.31
.73 1.00 27.3
4.5
.22
.69
1.00
5000
61.2
3.5
.57
.84 1.00 50.0
3.8
.50
.85
1.00 38.8
4.1
.33
.73
.90
27.6
4.5
.10
.89
1.00
3800
63.7
3.5
.29
.48
.66
53.8
3.9
.20
.41
.63
44.0
4.2
.04
.32
.59
34.1
4.6
.03
.12
.52
67°F
4400
66.6
3.6
.32
.51
.73
56.1
3.9
.21
.46
.72
45.7
4.2
.05
.36
.68
35.3
4.6
-.04
.19
.65
5000
69.4
3.6
.33
.55
.79
58.4
3.9
.24
.51
.79
47.4
4.2
.08
.42
.79
36.4
4.6
-.10
.25
.60
3800
72.2
3.6
.15
.31
.47
61.9
4.0
.05
.23
.42
51.6
4.3
-.10 .12
.35
41.3
4.6
-.28
-.07
.22
71°F
4400
74.9
3.7
.16
.33
.51
64.4
4.0
.05
.25
.45
53.8
4.3
-.11 .14
.39
43.3
4.7
-.29
-.06
.27
5000
77.7
3.7
.16
.35
.55
66.9
4.0
.05
.28
.51
56.1
4.4
-.12 .16
.45
45.3
4.7
-.30
-.04
.33
12.5 TON STANDARD EFFICIENCY LCH150S4 WITH HUMIDITROL OPERATING (2ND STAGE)
Outdoor Air Temperature Entering Outdoor Coil
Entering
65°F
75°F
85°F
95°F
Total
Wet
Air
Total Comp. Sensible To Total Total Comp. Sensible To Total Total Comp. Sensible To Total Total Comp. Sensible To Total
Bulb
Volume Cool Motor
Ratio (S/T)
Ratio (S/T)
Ratio (S/T)
Ratio (S/T)
Cool Motor
Cool Motor
Cool Motor
TemperCap. Input
Cap. Input
Cap. Input
Cap. Input
Dry Bulb
Dry Bulb
Dry Bulb
Dry Bulb
ature
cfm
kBtuh
kW
75°F 80°F 85°F kBtuh
kW
75°F 80°F 85°F kBtuh
kW
75°F 80°F 85°F kBtuh
kW
75°F 80°F 85°F
3800
122.7
7.3
.63
.79
.96 110.6
8.0
.62
.80
.99
98.6
8.8
.61
.81 1.00 86.5
9.6
.60
.82
1.00
63°F
4400
127.4
7.3
.66
.82
.97 114.4
8.1
.65
.83
1.00 101.4
8.8
.65
.84 1.00 88.4
9.6
.64
.85
1.00
5000
132.1
7.3
.69
.84
.99 118.2
8.1
.69
.86
1.00 104.2
8.9
.69
.87 1.00 90.3
9.6
.69
.88
1.00
3800
137.7
7.5
.47
.62
.76 124.7
8.2
.44
.61
.78
111.8
9.0
.42
.60
.79
98.8
9.8
.39
.60
.80
67°F
4400
142.5
7.5
.49
.64
.79 128.7
8.3
.46
.63
.80
115.0
9.0
.44
.63
.81 101.3
9.8
.42
.62
.83
5000
147.2
7.6
.50
.66
.81 132.7
8.3
.48
.65
.82
118.2
9.1
.46
.65
.84 103.7
9.8
.44
.65
.85
3800
152.7
7.7
.31
.44
.57 138.8
8.4
.27
.42
.56 125.0
9.2
.23
.39
.55 111.1
10.0
.19
.37
.55
71°F
4400
157.5
7.7
.31
.46
.60 143.1
8.5
.27
.43
.60 128.6
9.2
.23
.41
.59 114.2
10.0
.19
.39
.59
5000
162.4
7.8
.31
.47
.63 147.3
8.5
.27
.45
.63 132.2
9.3
.23
.43
.63 117.2
10.0
.19
.41
.63
Energence™ Packaged Electric / Electric 7.5 to 12.5 Ton / Page 17
BLOWER DATA
092 AND 102 BELT DRIVE BLOWER − BASE UNIT
BLOWER TABLE INCLUDES RESISTANCE FOR BASE UNIT ONLY (NO HEAT SECTION) WITH DRY INDOOR COIL AND AIR
FILTERS IN PLACE. FOR ALL UNITS ADD:
1 − Wet indoor coil air resistance of selected unit.
2 − Any factory installed options air resistance (heat section, economizer, etc.)
3 − Any field installed accessories air resistance (duct resistance, diffuser, etc.)
Then determine from blower table blower motor output required.
See page 20 for blower motors and drives. See page 20 for wet coil and option/accessory air resistance data.
MINIMUM AIR VOLUME REQUIRED FOR USE WITH OPTIONAL ELECTRIC HEAT (Maximum Static Pressure - 2.0 in. w.g.)
7.5 kW, 15 kW, 22.5 kW, 30 kW and 45 kW - 2800 cfm
Total
Total Static Pressure − in. w.g.
Air
0.2
0.4
0.6
0.8
1.0
1.2
1.4
1.6
1.8
2.0
2.2
2.4
2.6
Volume
cfm RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1750
481 0.21 549 0.4 618 0.57 688 0.7 758 0.82 824 0.93 885 1.08 941 1.23 991 1.39 1038 1.54 1082 1.68 1124 1.82 1166 1.95
2000
493 0.29 561 0.47 629 0.64 700 0.77 768 0.9 832 1.02 892 1.17 946 1.33 995 1.49 1041 1.66 1085 1.81 1126 1.97 1167 2.12
2250
507 0.37 574 0.56 643 0.72 712 0.86 779 0.99 842 1.13 900 1.28 953 1.44 1001 1.61 1045 1.78 1088 1.95 1128 2.12 1168 2.3
2500
521 0.46 588 0.64 657 0.81 727 0.95 792 1.09 853 1.24 909 1.4 960 1.57 1007 1.74 1050 1.93 1091 2.11 1130 2.29 1170 2.48
2750
537 0.56 604 0.74 674 0.91 743 1.06 806 1.21 865 1.36 920 1.53 969 1.71 1014 1.89 1055 2.08 1095 2.27 1133 2.47 1172 2.66
3000
554 0.67 622 0.86 692 1.02 760 1.18 822 1.34 878 1.5 931 1.68 979 1.86 1021 2.06 1061 2.26 1099 2.46 1136 2.65 1174 2.85
3250
572 0.78 641 0.98 712 1.15 778 1.32 838 1.49 892 1.66 943 1.84 989 2.03 1030 2.24 1068 2.45 1105 2.65 1141 2.85 1178 3.06
3500
592 0.9 663 1.12 733 1.3 798 1.47 855 1.65 907 1.83 956 2.02 1000 2.22 1039 2.44 1076 2.65 1111 2.86 1146 3.07 1183 3.27
3750
614 1.04 687 1.28 756 1.47 818 1.65 872 1.83 923 2.02 970 2.22 1011 2.43 1049 2.65 1084 2.87 1118 3.09 1152 3.29 1189 3.51
4000
639 1.22 713 1.48 780 1.66 838 1.83 890 2.02 939 2.22 984 2.44 1023 2.66 1059 2.89 1093 3.11 1126 3.33 1160 3.54 1197 3.77
4250
667 1.43 741 1.69 805 1.86 859 2.02 909 2.22 956 2.45 998 2.68 1036 2.92 1070 3.15 1103 3.37 1135 3.59 1169 3.81 1207 4.05
120 BELT DRIVE BLOWER − BASE UNIT
BLOWER TABLE INCLUDES RESISTANCE FOR BASE UNIT ONLY (NO HEAT SECTION) WITH DRY INDOOR COIL AND AIR
FILTERS IN PLACE. FOR ALL UNITS ADD:
1 − Wet indoor coil air resistance of selected unit.
2 − Any factory installed options air resistance (heat section, economizer, etc.)
3 − Any field installed accessories air resistance (duct resistance, diffuser, etc.)
Then determine from blower table blower motor output required.
See page 20 for blower motors and drives. See page 20 for wet coil and option/accessory air resistance data.
MINIMUM AIR VOLUME REQUIRED FOR USE WITH OPTIONAL ELECTRIC HEAT (Maximum Static Pressure - 2.0 in. w.g.)
15 kW, 22.5 kW, 30 kW and 45 kW - 2800 cfm
60 kW - 4000 cfm
Total
Total Static Pressure − in. w.g.
Air
0.2
0.4
0.6
0.8
1.0
1.2
1.4
1.6
1.8
2.0
2.2
2.4
2.6
Volume
cfm RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2000
497 0.25 558 0.44 624 0.6 694 0.74 764 0.85 830 0.99 889 1.16 943 1.34 994 1.52 1045 1.71 1096 1.89 1146 2.08 1197 2.27
2250
511 0.34 573 0.52 638 0.68 708 0.82 776 0.94 839 1.09 896 1.26 948 1.45 998 1.64 1048 1.83 1098 2.01 1149 2.2 1200 2.4
2500
527 0.44 589 0.62 654 0.78 723 0.91 789 1.05 850 1.21 904 1.39 955 1.58 1003 1.77 1052 1.96 1101 2.14 1152 2.33 1203 2.53
2750
545 0.55 606 0.72 672 0.88 740 1.03 804 1.17 861 1.34 914 1.53 962 1.72 1010 1.92 1057 2.1 1105 2.29 1154 2.47 1206 2.68
3000
564 0.66 626 0.84 692 1.01 759 1.16 819 1.32 874 1.49 924 1.68 971 1.88 1017 2.08 1063 2.26 1110 2.44 1158 2.63 1208 2.83
3250
585 0.79 648 0.98 714 1.14 778 1.31 836 1.48 887 1.66 935 1.86 981 2.06 1026 2.26 1071 2.45 1117 2.63 1163 2.8 1213
3500
607 0.93 672 1.13 737 1.31 798 1.48 852 1.66 901 1.85 948 2.05 993 2.26 1037 2.46 1081 2.65 1125 2.83 1171 3.01 1221 3.21
3750
632 1.1 698 1.31 762 1.5 819 1.67 869 1.86 915 2.05 961 2.25 1005 2.47 1049 2.68 1092 2.88 1136 3.05 1181 3.24 1231 3.45
4000
660 1.3 726 1.52 787 1.7 838 1.87 885 2.06 930 2.26 974 2.48 1018 2.71 1062 2.93 1105 3.12 1149 3.3 1194 3.49 1245 3.72
4250
691 1.53 755 1.75 810 1.91 857 2.07 901 2.27 945 2.5 990 2.74 1034 2.98 1077 3.2 1120 3.39 1163 3.58 1210 3.79 1262 4.03
4500
724 1.78 783 1.98 831 2.12 874 2.28 917 2.5 962 2.75 1006 3.02 1051 3.27 1094 3.49 1137 3.7 1181 3.89 1228 4.11 1281 4.38
4750
757 2.05 809 2.2 851 2.33 891 2.51 935 2.76 980 3.05 1025 3.33 1070 3.59 1113 3.82 1156 4.03 1201 4.24 1249 4.47 1303 4.75
5000
787 2.31 831 2.43 870 2.57 910 2.78 954 3.06 1000 3.38 1046 3.68 1091 3.95 1135 4.19 1178 4.4 1224 4.62 1272 4.86 1325 5.13
Energence™ Packaged Electric / Electric 7.5 to 12.5 Ton / Page 18
3
BLOWER DATA
150 BELT DRIVE BLOWER − BASE UNIT
BLOWER TABLE INCLUDES RESISTANCE FOR BASE UNIT ONLY (NO HEAT SECTION) WITH DRY INDOOR COIL AND AIR
FILTERS IN PLACE. FOR ALL UNITS ADD:
1 − Wet indoor coil air resistance of selected unit.
2 − Any factory installed options air resistance (heat section, economizer, etc.)
3 − Any field installed accessories air resistance (duct resistance, diffuser, etc.)
Then determine from blower table blower motor output required.
See page 20 for blower motors and drives. See page 20 for wet coil and option/accessory air resistance data.
MINIMUM AIR VOLUME REQUIRED FOR USE WITH OPTIONAL ELECTRIC HEAT (Maximum Static Pressure - 2.0 in. w.g.)
15 kW, 22.5 kW, 30 kW and 45 kW - 2800 cfm
60 kW - 4000 cfm
Total
Air
Volume
cfm
Total Static Pressure − in. w.g.
0.2
0.4
0.6
0.8
1.0
1.2
1.4
1.6
1.8
2.0
2.2
2.4
2.6
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2500
537 0.31 596 0.56 663 0.81 736 1.03 805 1.2 867 1.34 924 1.47 976 1.62 1026 1.77 1073 1.95 1118 2.13 1162 2.32 1206 2.51
2750
555 0.43 614 0.69 681 0.94 753 1.16 820 1.34 879 1.48 935 1.61 986 1.76 1034 1.92 1081 2.11 1126 2.31 1171 2.51 1215 2.71
3000
574 0.57 633 0.83 700 1.08 770 1.31 834 1.49 892 1.62 946 1.75 996 1.91 1044 2.09 1090 2.29 1135 2.5 1180 2.71 1225 2.92
3250
595 0.73 654 0.99 721 1.25 789 1.48 850 1.65 905 1.78 957 1.91 1006 2.08 1053 2.27 1099 2.48 1145 2.7 1190 2.92 1235 3.15
3500
617 0.89 677 1.17 743 1.44 807 1.66 865 1.82 919 1.94 970 2.08 1017 2.26 1064 2.47 1110 2.69 1155 2.92 1200 3.15 1246 3.39
3750
640 1.09 701 1.38 765 1.64 826 1.84 882 1.99 933 2.12 982 2.27 1029 2.46 1075 2.68 1120 2.91 1166 3.15 1211 3.39 1258 3.65
4000
665 1.32 725 1.62 787 1.86 846 2.03 899 2.17 949 2.3 996 2.47 1042 2.68 1087 2.92 1132 3.16 1177 3.4 1223 3.66 1270 3.93
4250
691 1.57 750 1.87 810 2.07 866 2.22 917 2.35 964 2.51 1010 2.7 1055 2.93 1099 3.17 1144 3.42 1189 3.67 1235 3.95 1283 4.25
4500
718 1.85 776 2.12 833 2.28 886 2.4 935 2.55 981 2.73 1025 2.95 1069 3.2 1112 3.45 1156 3.7 1201 3.97 1248 4.27 1297 4.59
4750
745 2.14 802 2.36 856 2.48 907 2.6 954 2.77 997 2.99 1040 3.23 1083 3.49 1126 3.75 1170 4.01 1215 4.29 1262 4.61 1311 4.96
5000
773 2.42 828 2.59 880 2.69 928 2.83 972 3.03 1014 3.28 1056 3.55 1097 3.82 1140 4.08 1183 4.35 1229 4.65 1276 4.98 1325 5.33
5250
802 2.69 854 2.82 904 2.93 950 3.09 991 3.33 1032 3.61 1072 3.9 1113 4.17 1155 4.44 1198 4.72 1243 5.02 1291 5.36 1340 5.71
5500
831 2.95 881 3.06 928 3.2 971 3.4 1011 3.68 1050 3.99 1089 4.28 1129 4.56 1170 4.83 1213 5.11 1258 5.42 1306 5.75 1355 6.1
5750
860 3.21 908 3.33 952 3.5 992 3.75 1030 4.07 1068 4.4 1106 4.7 1145 4.98 1186 5.25 1229 5.53 - - - - - - - - - - - - - - - - - -
6000
890 3.48 934 3.63 976 3.86 1013 4.16 1050 4.52 1086 4.85 1123 5.16 1162 5.44 1202 5.7 - - - - - - - - - - - - - - - - - - - - - - - -
6250
919 3.78 961 3.99 999 4.27 1034 4.63 1069 5.01 1104 5.35 1141 5.65 - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -
Energence™ Packaged Electric / Electric 7.5 to 12.5 Ton / Page 19
BLOWER DATA
FACTORY INSTALLED BELT DRIVE KIT SPECIFICATIONS
Motor Efficiency
Nominal
hp
Maximum
hp
Drive Kit Number
RPM Range
Standard & High
2
2.3
1
590 - 890
Standard & High
2
2.3
2
800 - 1105
Standard & High
2
2.3
3
795 - 1195
Standard
3
3.45
4
730 - 970
Standard
3
3.45
5
940 - 1200
Standard
3
3.45
6
1015 - 1300
High
3
3.45
7
730 - 970
High
3
3.45
8
940 - 1200
High
3
3.45
9
1015 - 1300
Standard
5
5.75
10
900 - 1135
Standard
5
5.75
11
1040 - 1315
Standard
5
5.75
12
1125 - 1425
NOTE - Using total air volume and system static pressure requirements determine from blower performance tables rpm and motor output required. Maximum usable
output of motors furnished are shown. In Canada, nominal motor output is also maximum usable motor output. If motors of comparable output are used, be sure to keep
within the service factor limitations outlined on the motor nameplate.
POWER EXHAUST FAN PERFORMANCE
Return Air System Static Pressure
Air Volume Exhausted
in. w.g.
cfm
0
3175
0.05
2955
0.10
2685
0.15
2410
0.20
2165
0.25
1920
0.30
1420
0.35
1200
FACTORY INSTALLED OPTIONS/FIELD INSTALLED ACCESSORY AIR RESISTANCE - in. w.g.
Air
Volume
cfm
1750
2000
2250
2500
2750
3000
3250
3500
3750
4000
4250
4500
4750
5000
5250
5500
5750
6000
Wet Indoor Coil
092, 102,120
150
Electric
Heat
0.09
0.11
0.13
0.15
0.17
0.19
0.23
0.26
0.29
0.31
0.34
0.37
0.40
0.43
0.46
0.50
0.56
0.59
0.12
0.15
0.18
0.22
0.23
0.28
0.33
0.37
0.42
0.45
0.50
0.53
0.59
0.63
0.68
0.73
0.79
0.86
0.03
0.03
0.04
0.04
0.05
0.06
0.06
0.09
0.09
0.09
0.13
0.14
0.17
0.20
0.22
0.25
0.31
0.33
Economizer
0.05
0.06
0.08
0.11
0.12
0.13
0.15
0.15
0.15
0.19
0.19
0.22
0.25
0.29
0.32
0.34
0.45
0.52
Energence™ Packaged Electric / Electric 7.5 to 12.5 Ton / Page 20
Humiditrol
Condenser
Reheat Coil
0.02
0.02
0.02
0.03
0.03
0.03
0.04
0.04
0.05
0.05
0.06
0.07
0.07
0.08
0.08
0.09
0.10
0.10
Filters
MERV 8
MERV 13
0.01
0.01
0.01
0.01
0.02
0.02
0.02
0.03
0.03
0.04
0.04
0.04
0.05
0.06
0.06
0.07
0.07
0.08
0.03
0.03
0.04
0.05
0.05
0.06
0.06
0.07
0.08
0.08
0.09
0.09
0.10
0.10
0.11
0.12
0.12
0.13
Return Air
Adaptor
Plate
0.00
0.00
0.00
0.00
0.00
0.02
0.02
0.04
0.07
0.09
0.11
0.12
0.16
0.18
0.19
0.22
0.25
0.27
BLOWER DATA
CEILING DIFFUSERS AIR RESISTANCE - in. w.g.
RTD11 Step-Down Diffuser
Unit Size
FD11 Flush
Diffuser
Air Volume
cfm
2 Ends Open
1 Side, 2 Ends
Open
All Ends & Sides
Open
2400
0.21
0.18
0.15
0.14
2600
0.24
0.21
0.18
0.17
2800
0.27
0.24
0.21
0.20
3000
0.32
0.29
0.25
0.25
3200
0.41
0.37
0.32
0.31
3400
0.50
0.45
0.39
0.37
3600
0.61
0.54
0.48
0.44
3800
0.73
0.63
0.57
0.51
3600
0.36
0.28
0.23
0.15
3800
0.40
0.32
0.26
0.18
4000
0.44
0.36
0.29
0.21
4200
0.49
0.40
0.33
0.24
4400
0.54
0.44
0.37
0.27
4600
0.60
0.49
0.42
0.31
4800
0.65
0.53
0.46
0.35
5000
0.69
0.58
0.50
0.39
5200
0.75
0.62
0.54
0.43
4200
0.22
0.19
0.16
0.10
4400
0.28
0.24
0.20
0.12
4600
0.34
0.29
0.24
0.15
4800
0.40
0.34
0.29
0.19
5000
0.46
0.39
0.34
0.23
5200
0.52
0.44
0.39
0.27
5400
0.58
0.49
0.43
0.31
5600
0.64
0.54
0.47
0.35
5800
0.70
0.59
0.51
0.39
092 Models
102 & 120 Models
150 Models
CEILING DIFFUSER AIR THROW DATA
Model No.
092 Models
102, 120
Models
150 Models
Air Volume
1
Effective Throw Range
RTD11 Step-Down
FD11 Flush
cfm
ft.
ft.
2600
24 - 29
19 - 24
2800
25 - 30
20 - 28
3000
27 - 33
21 - 29
3200
28 - 35
22 - 29
3400
30 - 37
22 - 30
3600
25 - 33
22 - 29
3800
27 - 35
22 - 30
4000
29- 37
24 - 33
4200
32 - 40
26 - 35
4400
34 - 42
28 - 37
5600
39 - 49
28 - 37
5800
42 - 51
29 - 38
6000
44 - 54
40 - 50
6200
45 - 55
42 - 51
6400
46 - 55
43 - 52
6600
47 - 56
45 - 56
Throw is the horizontal or vertical distance an air stream travels on leaving the outlet or diffuser
before the maximum velocity is reduced to 50 ft. per minute. Four sides open.
1
Energence™ Packaged Electric / Electric 7.5 to 12.5 Ton / Page 21
ELECTRICAL/ELECTRIC HEAT DATA
7.5 TON
7.5 TON HIGH EFFICIENCY (R-410A)
1
LCH092H4
Voltage - 60hz
Compressor 1
208/230V - 3 Ph
460V - 3 Ph
575V - 3 Ph
4.4
Rated Load Amps
13.1
6.1
Locked Rotor Amps
83.1
41
33
Rated Load Amps
13.1
6.1
4.4
Locked Rotor Amps
83.1
41
33
Full Load Amps
2.4
1.3
1
(4.8)
(2.6)
(2)
2.4
1.3
1
Compressor 2
Outdoor Fan
(total)
Motors (2)
Power Exhaust
Full Load Amps
(1) 0.33 HP
Service Outlet 115V GFI (amps)
Indoor Blower
Motor
2
15
Horsepower
15
3
5
2
3
5
2
3
5
Full Load Amps
7.5
10.6
16.7
3.4
4.8
7.6
2.7
3.9
6.1
Unit Only
50
50
60
25
25
30
15
20
20
With (1) 0.33 HP
50
60
70
25
25
30
20
20
25
Maximum
Overcurrent
15
2
Protection
Power Exhaust
Minimum
Unit Only
42
45
52
20
22
25
15
16
19
With (1) 0.33 HP
45
48
55
22
23
26
16
17
20
3
Circuit
Power Exhaust
Ampacity
ELECTRIC HEAT DATA
Electric Heat Voltage
2
Maximum
Overcurrent
Minimum
Circuit
Maximum
Overcurrent
Protection
3
Minimum
Circuit
Ampacity
208V
240V
50
208V
240V
480V
480V
480V
600V
600V
600V
60
Unit+
7.5 kW
50
50
50
60
25
25
30
15
20
20
15 kW
4
50
60
60
60
4
60
70
30
30
35
25
25
30
22.5 kW
4
70
80
80
90
4
80
90
40
40
45
35
35
35
30 kW
4
90
100
100
110
4
100
125
50
60
60
40
45
45
45 kW
150
150
150
150
4
150
175
80
80
80
60
60
70
Unit+
7.5 kW
42
42
45
45
51
51
20
22
24
15
16
18
Electric Heat
15 kW
49
55
53
59
60
66
27
29
33
22
23
26
22.5 kW
69
78
72
81
80
89
39
40
44
31
32
35
30 kW
88
100
92
104
100
112
50
52
55
40
41
44
45 kW
127
145
131
149
139
157
72
74
78
58
60
62
Unit+
7.5 kW
50
50
60
60
70
70
25
25
30
20
20
25
Electric Heat
15 kW
60
60
4
60
70
70
70
30
35
35
25
25
30
80
90
4
80
90
90
100
40
45
45
35
35
40
100
100
110
4
110
125
60
60
60
45
45
45
150
175
4
150
175
80
80
80
60
70
70
Ampacity
2
240V
Electric Heat
Protection
3
208V
and (1) 0.33 22.5 kW
HP
30 kW
Power Exhaust
45 kW
4
4
4
110
4
150
150
4
4
4
Unit+
7.5 kW
45
45
48
48
54
54
22
23
26
16
17
19
Electric Heat
15 kW
52
58
56
62
63
69
29
31
34
23
25
27
and (1) 0.33 22.5 kW
HP
30 kW
Power Exhaust
45 kW
72
81
75
84
83
92
40
42
45
32
34
36
91
103
95
107
103
115
51
53
57
41
43
45
130
148
134
152
142
160
74
76
79
59
61
64
ELECTRICAL ACCESSORIES
Disconnect
7.5 kW 54W56 54W56 54W56 54W56 54W56 54W56 54W56 54W56 54W56 54W56 54W56 54W56
15 kW 54W56 54W56 54W56 54W56 54W56 54W56 54W56 54W56 54W56 54W56 54W56 54W56
22.5 kW 54W56 54W56 54W57 54W57 54W57 54W57 54W56 54W56 54W56 54W56 54W56 54W56
30 kW 54W57 54W57 54W57 54W57 54W57 54W57 54W56 54W56 54W56 54W56 54W56 54W56
45 kW 54W57 54W57 54W57 54W57 54W57 54W57 54W56 54W56 54W56 54W56 54W56 54W56
Extremes of operating range are plus and minus 10% of line voltage.
HACR type breaker or fuse.
Refer to National or Canadian Electrical Code manual to determine wire, fuse and disconnect size requirements.
4
Factory installed circuit breaker not available.
1
2
3
Energence™ Packaged Electric / Electric 7.5 to 12.5 Ton / Page 22
ELECTRICAL/ELECTRIC HEAT DATA
8.5 TON
8.5 TON HIGH EFFICIENCY (R-410A)
1
LCH102H4
Voltage - 60hz
Compressor 1
208/230V - 3 Ph
460V - 3 Ph
575V - 3 Ph
4.8
Rated Load Amps
13.7
6.2
Locked Rotor Amps
83.1
41
33
Rated Load Amps
13.7
6.2
4.8
Locked Rotor Amps
83.1
41
33
Full Load Amps
2.4
1.3
1
(4.8)
(2.6)
(2)
2.4
1.3
1
Compressor 2
Outdoor Fan
(total)
Motors (2)
Power Exhaust
Full Load Amps
(1) 0.33 HP
Service Outlet 115V GFI (amps)
Indoor Blower
Motor
2
15
Horsepower
15
3
5
2
3
5
2
3
5
Full Load Amps
7.5
10.6
16.7
3.4
4.8
7.6
2.7
3.9
6.1
Unit Only
50
50
60
25
25
30
20
20
25
With (1) 0.33 HP
50
60
70
25
25
30
20
20
25
Maximum
Overcurrent
15
2
Protection
Power Exhaust
Minimum
Unit Only
44
47
54
20
22
25
16
17
20
With (1) 0.33 HP
46
49
56
22
23
26
17
18
21
3
Circuit
Power Exhaust
Ampacity
ELECTRIC HEAT DATA
Electric Heat Voltage
2
Maximum
Overcurrent
Minimum
Circuit
Maximum
Overcurrent
Protection
3
Minimum
Circuit
Ampacity
208V
240V
50
208V
240V
480V
480V
480V
600V
600V
600V
60
Unit+
7.5 kW
50
50
50
60
25
25
30
20
20
25
15 kW
4
50
60
60
60
4
60
70
30
30
35
25
25
30
22.5 kW
4
70
80
80
90
4
80
90
40
40
45
35
35
35
30 kW
4
90
100
100
110
4
100
125
50
60
60
40
45
45
45 kW
150
150
150
150
4
150
175
80
80
80
60
60
70
7.5 kW
44
44
47
47
53
53
20
22
25
16
17
19
15 kW
49
55
53
59
60
66
27
29
33
22
23
26
22.5 kW
69
78
72
81
80
89
39
40
44
31
32
35
30 kW
88
100
92
104
100
112
50
52
55
40
41
44
45 kW
127
145
131
149
139
157
72
74
78
58
60
62
7.5 kW
50
50
60
60
70
70
25
25
30
20
20
25
15 kW
and (1) 0.33 22.5 kW
HP
30 kW
Power Exhaust
45 kW
60
Unit+
Electric Heat
Ampacity
2
240V
Electric Heat
Protection
3
208V
Unit+
Electric Heat
4
4
4
60
4
80
90
4
100
110
4
150
150
4
4
60
70
80
90
100
150
70
70
30
35
35
25
25
30
90
100
40
45
45
35
35
40
110
4
110
125
60
60
60
45
45
45
175
4
150
175
80
80
80
60
70
70
4
Unit+
7.5 kW
46
46
49
49
55
55
22
23
26
17
18
20
Electric Heat
15 kW
52
58
56
62
63
69
29
31
34
23
25
27
and (1) 0.33 22.5 kW
HP
30 kW
Power Exhaust
45 kW
72
81
75
84
83
92
40
42
45
32
34
36
91
103
95
107
103
115
51
53
57
41
43
45
130
148
134
152
142
160
74
76
79
59
61
64
ELECTRICAL ACCESSORIES
Disconnect
7.5 kW 54W56 54W56 54W56 54W56 54W56 54W56 54W56 54W56 54W56 54W56 54W56 54W56
15 kW 54W56 54W56 54W56 54W56 54W56 54W56 54W56 54W56 54W56 54W56 54W56 54W56
22.5 kW 54W56 54W56 54W57 54W57 54W57 54W57 54W56 54W56 54W56 54W56 54W56 54W56
30 kW 54W57 54W57 54W57 54W57 54W57 54W57 54W56 54W56 54W56 54W56 54W56 54W56
45 kW 54W57 54W57 54W57 54W57 54W57 54W57 54W56 54W56 54W56 54W56 54W56 54W56
Extremes of operating range are plus and minus 10% of line voltage.
2
HACR type breaker or fuse.
3
Refer to National or Canadian Electrical Code manual to determine wire, fuse and disconnect size requirements.
4
Factory installed circuit breaker not available.
1
Energence™ Packaged Electric / Electric 7.5 to 12.5 Ton / Page 23
ELECTRICAL/ELECTRIC HEAT DATA
10 TON
10 TON HIGH EFFICIENCY (R-410A)
1
LCH120H4
Voltage - 60hz
208/230V - 3 Ph
Compressor 1
460V - 3 Ph
575V - 3 Ph
Rated Load Amps
13.5
8
5
Locked Rotor Amps
109
59
40
Rated Load Amps
13.5
8
5
Locked Rotor Amps
109
59
40
Full Load Amps
2.4
1.3
1
(4.8)
(2.6)
(2)
2.4
1.3
1
Compressor 2
Outdoor Fan
(total)
Motors (2)
Power Exhaust
Full Load Amps
(1) 0.33 HP
Service Outlet 115V GFI (amps)
Indoor Blower
Motor
2
15
Horsepower
15
3
5
2
3
5
2
3
5
Full Load Amps
7.5
10.6
16.7
3.4
4.8
7.6
2.7
3.9
6.1
Unit Only
50
50
60
30
30
35
20
20
25
With (1) 0.33 HP
50
60
70
30
30
35
20
20
25
Maximum
Overcurrent
15
2
Protection
Power Exhaust
Minimum
Unit Only
43
46
53
24
26
29
16
18
20
With (1) 0.33 HP
46
49
56
26
27
30
17
19
21
240V
480V
480V
480V
600V
600V
600V
3
Circuit
Power Exhaust
Ampacity
ELECTRIC HEAT DATA
Electric Heat Voltage
2
Maximum
Overcurrent
Protection
208V
Minimum
Ampacity
2
Maximum
Overcurrent
Protection
3
Minimum
Circuit
Ampacity
240V
50
60
60
70
80
90
100
150
150
15 kW
4
4
Unit+
60 kW
Circuit
208V
Electric Heat 22.5 kW
30 kW
45 kW
3
240V
4
4
150
175
60
4
80
90
4
100
110
4
100
125
50
60
60
40
45
45
150
175
80
80
80
60
60
70
150
175
80
80
90
70
70
70
4
4
150
4
208V
150
4
150
175
4
60
70
30
30
35
25
25
30
80
90
40
40
45
35
35
35
15 kW
49
55
53
59
60
66
27
29
33
22
23
26
Electric Heat 22.5 kW
30 kW
69
78
72
81
80
89
39
40
44
31
32
35
88
100
92
104
100
112
50
52
55
40
41
44
45 kW
127
145
131
149
139
157
72
74
78
58
60
62
60 kW
135
154
139
158
146
166
77
79
82
62
63
66
15 kW
60
60
70
80
90
Unit+
Unit+
Electric Heat 22.5 kW
30 kW
and (1) 0.33
HP
45 kW
4
Power Exhaust
60 kW
4
Unit+
4
60
4
80
90
4
100
110
4
100
110
150
150
150
4
150
150
175
4
70
70
30
35
35
25
25
30
90
100
40
45
45
35
35
40
4
110
125
60
60
60
45
45
45
175
4
150
175
80
80
80
60
70
70
175
4
150
175
80
80
90
70
70
70
4
15 kW
52
58
56
62
63
69
29
31
34
23
25
27
Electric Heat 22.5 kW
30 kW
and (1) 0.33
HP
45 kW
72
81
75
84
83
92
40
42
45
32
34
36
91
103
95
107
103
115
51
53
57
41
43
45
130
148
134
152
142
160
74
76
79
59
61
64
60 kW
138
157
142
161
149
169
79
80
84
63
64
67
Power Exhaust
ELECTRICAL ACCESSORIES
Disconnect
15 kW 54W56 54W56 54W56 54W56 54W56 54W56 54W56 54W56 54W56 54W56 54W56 54W56
22.5 kW 54W56 54W56 54W57 54W57 54W57 54W57 54W56 54W56 54W56 54W56 54W56 54W56
30 kW 54W57 54W57 54W57 54W57 54W57 54W57 54W56 54W56 54W56 54W56 54W56 54W56
45 kW 54W57 54W57 54W57 54W57 54W57 54W57 54W56 54W56 54W56 54W56 54W56 54W56
60 kW
5
N/A
5
N/A
5
N/A
5
N/A
5
N/A
5
N/A 54W56 54W56
Extremes of operating range are plus and minus 10% of line voltage.
2
HACR type breaker or fuse.
3
Refer to National or Canadian Electrical Code manual to determine wire, fuse and disconnect size requirements.
4
Factory installed circuit breaker not available.
5
Disconnect must be field furnished.
1
Energence™ Packaged Electric / Electric 7.5 to 12.5 Ton / Page 24
5
N/A 54W56 54W56 54W56
ELECTRICAL/ELECTRIC HEAT DATA
12.5 TON
12.5 TON STANDARD EFFICIENCY (R-410A)
1
Voltage - 60hz
LCH150S4
208/230V - 3 Ph
Compressor 1
460V - 3 Ph
575V - 3 Ph
Rated Load Amps
19.6
8.2
6.6
Locked Rotor Amps
136
66.1
55.3
Rated Load Amps
19.6
8.2
6.6
Locked Rotor Amps
136
66.1
55.3
3
1.5
1.2
Compressor 2
Outdoor Fan
Full Load Amps
(total)
(6)
(3)
(2.4)
Full Load Amps
2.4
1.3
1
Motors (2)
Power Exhaust
(1) 0.33 HP
Service Outlet 115V GFI (amps)
Indoor Blower
Motor
2
15
Horsepower
15
3
5
2
3
5
2
3
5
Full Load Amps
7.5
10.6
16.7
3.4
4.8
7.6
2.7
3.9
6.1
Unit Only
70
80
80
30
30
35
25
25
25
With (1) 0.33 HP
70
80
80
30
35
35
25
25
30
Maximum
Overcurrent
15
2
Protection
Power Exhaust
Minimum
Unit Only
58
61
67
25
27
30
20
22
24
With (1) 0.33 HP
60
64
70
27
28
31
21
23
25
3
Circuit
Power Exhaust
Ampacity
ELECTRIC HEAT DATA
Electric Heat Voltage
2
Maximum
Overcurrent
Protection
Unit+
60 kW
Minimum
Circuit
Ampacity
2
Maximum
Overcurrent
Protection
3
Minimum
Circuit
Ampacity
240V
70
70
15 kW
Electric Heat 22.5 kW
30 kW
45 kW
3
208V
4
70
80
4
90
100
150
150
4
150
175
208V
240V
80
80
4
4
80
90
100
110
150
4
208V
240V
480V
480V
480V
600V
600V
600V
80
80
30
30
35
25
25
30
80
90
40
40
45
35
35
35
4
100
125
50
60
60
40
45
45
150
175
80
80
80
60
60
70
150
175
80
80
90
70
70
70
4
150
4
150
175
4
15 kW
58
58
61
61
67
67
27
29
33
22
23
26
Electric Heat 22.5 kW
30 kW
69
78
72
81
80
89
39
40
44
31
32
35
88
100
92
104
100
112
50
52
55
40
41
44
45 kW
127
145
131
149
139
157
72
74
78
58
60
62
60 kW
135
154
139
158
146
166
77
79
82
62
63
66
15 kW
70
70
80
80
80
80
30
35
35
25
25
30
Unit+
Unit+
Electric Heat 22.5 kW
30 kW
and (1) 0.33
HP
45 kW
4
Power Exhaust
60 kW
4
Unit+
4
80
90
80
90
90
100
40
45
45
35
35
40
100
110
4
100
110
4
110
125
60
60
60
45
45
45
150
175
4
150
175
80
80
80
60
70
70
150
175
4
150
175
80
80
90
70
70
70
64
70
70
29
31
34
23
25
27
4
150
4
150
175
4
15 kW
60
60
64
Electric Heat 22.5 kW
30 kW
and (1) 0.33
HP
45 kW
72
81
75
84
83
92
40
42
45
32
34
36
91
103
95
107
103
115
51
53
57
41
43
45
130
148
134
152
142
160
74
76
79
59
61
64
60 kW
138
157
142
161
149
169
79
80
84
63
64
67
Power Exhaust
150
4
ELECTRICAL ACCESSORIES
Disconnect
15 kW
22.5 kW
30 kW
45 kW
60 kW
Extremes of operating range are plus and minus 10% of line voltage.
HACR type breaker or fuse.
Refer to National or Canadian Electrical Code manual to determine wire, fuse and disconnect size requirements.
4
Factory installed circuit breaker not available.
5
Disconnect must be field furnished.
1
2
3
Energence™ Packaged Electric / Electric 7.5 to 12.5 Ton / Page 25
ELECTRIC HEAT CAPACITIES
Volts
Input
7.5 kW
15 kW
22.5 kW
30 kW
45 kW
60 kW
kW Btuh No. of kW Btuh No. of kW Btuh No. of kW
Btuh No. of kW
Btuh No. of kW
Btuh No. of
Input Output Stages Input Output Stages Input Output Stages Input Output Stages Input Output Stages Input Output Stages
208
5.6
19,100
1
11.3 38,600
1
16.9 57,700
2
22.5 76,800
2
33.8 115,300
2
45.0 153,600
2
220
6.3
21,500
1
12.6 43,000
1
18.9 64,500
2
25.2 86,000
2
37.8 129,000
2
50.4 172,000
2
230
6.9
23,600
1
13.8 47,100
1
20.7 70,700
2
27.5 93,900
2
41.3 141,000
2
55.1 188,000
2
240
7.5
25,600
1
15.0 51,200
1
22.5 76,800
2
30.0 102,400
2
45.0 153,600
2
60.0 204,800
2
440
6.9
21,500
1
12.6 43,000
1
18.9 64,500
2
25.2 86,000
2
37.8 129,000
2
50.4 172,000
2
460
6.9
23,600
1
13.8 47,100
1
20.7 70,700
2
27.5 93,900
2
41.3 141,000
2
55.1 188,000
2
480
7.5
25,600
1
15.0 51,200
1
22.5 76,800
2
30.0 102,400
2
45.0 153,600
2
60.0 204,800
2
550
6.3
21,500
1
12.6 43,000
1
18.9 64,500
2
25.2 86,000
2
37.8 129,000
2
50.4 172,000
2
575
6.9
23,600
1
13.8 47,100
1
20.7 70,700
2
27.5 93,900
2
41.3 141,000
2
55.1 188,000
2
600
7.5
25,600
1
15.0 51,200
1
22.5 76,800
2
30.0 102,400
2
45.0 153,600
2
60.0 204,800
2
UNIT CLEARANCES - INCHES (MM)
C
OPTIONAL
OUTDOOR
AIR HOOD
D
B
D
A
1
Unit Clearance
A
B
C
D
in.
mm
in.
mm
in.
mm
in.
mm
Service Clearance
60
1524
36
914
36
934
60
1524
Minimum Operation Clearance
36
914
36
914
36
914
36
914
NOTE - Entire perimeter of unit base requires support when elevated above the mounting surface.
1
Service Clearance - Required for removal of serviceable parts.
Minimum Operation Clearance - Required clearance for proper unit operation.
Energence™ Packaged Electric / Electric 7.5 to 12.5 Ton / Page 26
Top
Clearance
Unobstructed
OPTIONAL CONVENTIONAL TEMPERATURE CONTROL SYSTEMS - FIELD INSTALLED
COMMERCIAL TOUCHSCREEN THERMOSTAT
Intuitive Touchscreen Interface - Two Stage Heating / Two Stage Cooling
Conventional or Heat Pump - Seven Day Programmable - Four Time Periods/
Day - Economizer Output - Title 24 Compliant - ENERGY STAR® Qualified Backlit Display - Automatic Changeover
C0STAT02AE1L
(14W81)
Sensors For Touchscreen Thermostat
1
Remote non-adjustable wall mount 20k temperature sensor..........................
C0SNZN01AE2-
1
Remote non-adjustable wall mount 10k averaging temperature sensor.........
C0SNZN73AE1-
1
Remote non-adjustable duct mount temperature sensor................................
C0SNDC00AE1-
Outdoor temperature sensor.............................................................................
C0SNSR03AE1-
(47W36)
(47W37)
(19L22)
(X4148)
Accessories For Touchscreen Thermostat
Locking cover (clear).........................................................................................
C0MISC15AE1(39P21)
1
Remote sensors for C0STAT02AE1L can be applied in the following combinations: (1)
C0SNZN01AE1-, (2) C0SNZN73AE1-, (2) C0SNZN01AE1- and (1) C0SNZN73AE1-, (4)
C0SNZN01AE1-, (3) C0SNZN01AE1- and (2) C0SNZN73AE1.
DIGITAL NON-PROGRAMMABLE THERMOSTATS
Intuitive Interface - Automatic Changeover - Simple Up and Down Temperature Control
Two-stage heating / cooling conventional systems........................................
C0STAT10AE1L
(13K98)
Sensor For Digital Non-Programmable Thermostats Above
Remote wall mounted temperature sensor.......................................................
C0SNZN00AE1(26K57)
Intuitive Interface - Automatic Changeover - Backlit Display - Simple Up and Down Temperature Control
One-stage heating / cooling conventional systems...........................................
C0STAT12AE1L
(51M32)
Sensor For Digital Non-Programmable Thermostats Above
Outdoor temperature sensor.............................................................................
C0SNSR04AE1(X2658)
Accessories For Digital Non-Programmable Thermostats Above
Optional wall mounting plate.............................................................................
C0MISC17AE1(X2659)
OUTDOOR SOUND DATA
Unit
Model Number
Octave Band Sound Power Levels dBA, re 10-12 Watts Center Frequency - HZ
125
250
500
1000
2000
4000
8000
Sound Rating
Number (dB)
092, 102 and 120
76
79
84
83
79
73
66
88
150
77
80
85
84
79
74
66
88
1
Note - The octave sound power data does not include tonal corrections.
1
Sound Rating Number according to AHRI Standard 370-2001.
Energence™ Packaged Electric / Electric 7.5 to 12.5 Ton / Page 27
WEIGHT DATA
Net
Model Number
lbs.
1120
1277
1127
1284
1162
1326
1202
1366
092 Base Unit
092 Max. Unit
102 Base Unit
102 Max. Unit
120 Base Unit
120 Max. Unit
150 Base Unit
150 Max. Unit
Shipping
kg
508
579
511
582
527
601
545
620
lbs.
1205
1362
1212
1369
1247
1411
1287
1451
kg
547
618
550
621
566
640
584
658
OPTIONS / ACCESSORIES
Description
CEILING DIFFUSERS
Step-Down
lbs.
Shipping Weight
kg
RTD11-95
RTD11-135
RTD11-185
88
205
392
40
93
178
FD11-95
FD11-135
FD11-185
75
174
289
34
79
131
LASRT08/10
LASRT10/12
LASRT15
ECONOMIZER / OUTDOOR AIR / EXHAUST
Economizer
Economizer Dampers
Barometric Relief Dampers (downflow)
Barometric Relief Damper Hood (downflow)
Outdoor Air Hood (downflow)
Outdoor Air Dampers
Outdoor Air Damper Section (downflow) - Automatic
Outdoor Air Damper Section (downflow) - Manual
Outdoor Air Damper Hood (downflow)
Power Exhaust
ELECTRIC HEAT
7.5 kW
15 kW
22.5 kW
30 kW
45 kW
60 kW
HUMIDITROL®
Humiditrol
ROOF CURBS - CLIP CURB
Downflow
8 in. height
14 in. height
18 in. height
24 in. height
ROOF CURBS - STANDARD
Downflow
8 in. height
14 in. height
24 in. height
PACKAGING
LTL Packaging (less than truck load)
30
32
36
14
15
16
55
8
25
23
25
4
11
10
9
2
9
31
4
1
4
14
50
50
57
57
59
68
23
23
26
26
27
31
20
9
89
109
126
150
40
49
57
68
91
115
153
41
52
69
105
48
Flush
Transitions
Energence™ Packaged Electric / Electric 7.5 to 12.5 Ton / Page 28
DIMENSIONS - INCHES (mm)
Model
No.
092
102
120
150
CORNER WEIGHTS
AA
Base
lbs.
281
282
294
304
Max.
kg
127
128
133
138
lbs.
327
329
340
350
kg
148
149
154
159
BB
Base
lbs.
252
254
264
273
kg
114
115
120
124
CC
Max.
lbs.
286
287
297
306
kg
130
130
135
139
Base
lbs.
275
276
283
293
kg
125
125
128
133
CENTER OF GRAVITY
EE
DD
Max.
lbs.
306
308
318
327
Base
kg
139
139
144
148
lbs.
312
314
321
332
kg
142
143
146
151
Max.
lbs.
358
360
372
383
Base
kg
162
163
169
174
in.
46.5
46.5
46.5
46.5
mm
1181
1181
1181
1181
FF
Max.
in.
45.5
45.5
45.5
45.5
Base
mm
1156
1156
1156
1156
in.
24.5
24.5
24.5
24.5
mm
622
622
622
622
Max.
in.
25.5
25.5
25.5
25.5
mm
648
648
648
648
Base Unit - The unit with NO INTERNAL OPTIONS.
Max. Unit - The unit with ALL INTERNAL OPTIONS Installed. (Economizer, Standard Static Power Exhaust Fans, Controls, etc.). Does not include accessories external to
unit or high static power exhaust.
6-1/8
(156)
5-5/8
(143)
AA
6-1/8
(156)
24
(610)
BB
28
20 (711)
(508)
10-3/4
(273)
27
(686)
60-1/8 (1527)
BASE
BOTTOM SUPPLY
AIR OPENING
CENTER OF
GRAVITY
BOTTOM RETURN
AIR OPENING
BOTTOM
POWER ENTRY
5-1/2 (140) Dia.
EE
FF
6-5/8
(168)
7 (178)
DD
CC
BOTTOM
CONDENSATE
7 (178)
34-7/8
(886)
101-1/4
(2572)
BASE
TOP VIEW
58-1/8
(1476)
OPTIONAL DISCONNECT
(FACTORY INSTALLED)
46-7/8
(1191)
43-3/8
(1102)
60-1/8
(1527)
3-1/2
(89)
99-1/4
(2521)
46-7/8
(1191)
CONDENSATE
DRAIN (FRONT)
1
(25)
ELECTRIC
INLETS
5-3/8
(137)
FORKLIFT SLOTS
LIFTING HOLES
(BOTH SIDES)
(FOR RIGGING)
101-1/4
(2572)
34-7/8
(886)
END VIEW
SIDE VIEW
15-1/2
(394)
HORIZONTAL
SUPPLY AIR
OPENING
15-1/2
(394)
HORIZONTAL
RETURN AIR
OPENING
1-5/8
(41)
30
(762)
12-1/8
(308)
6-1/8
(156)
CONDENSATE
DRAIN (BACK)
31-1/2
(800)
66-3/8
(1686)
30
(762)
5-3/8
(137)
SIDE VIEW
(Horizontal Openings)
Energence™ Packaged Electric / Electric 7.5 to 12.5 Ton / Page 29
ACCESSORY DIMENSIONS - INCHES (MM)
OUTDOOR AIR HOOD DETAIL
21−3/8
(543)
OUTDOOR AIR HOOD
(Furnished with Economizer or
Outdoor Air Damper)
EXHAUST AIR HOOD
(Furnished, Field Installed)
Energence™ Packaged Electric / Electric 7.5 to 12.5 Ton / Page 30
ACCESSORY DIMENSIONS - INCHES (MM)
HORIZONTAL ECONOMIZER APPLICATION
(with Optional Horizontal Barometric Relief Dampers and Horizontal Discharge Kit)
ECONOMIZER
DAMPERS
HORIZONTAL
BAROMETRIC RELIEF
DAMPERS AND HOOD
SUPPLY AIR DUCT
(Field Provided)
RETURN AIR
DUCT TRANSITION
(Field fabricated and
installed on unit)
SUPPLY
AIR
OUTLET
RETURN
AIR
INLET
RETURN AIR DUCT
(Field Fabricated - Must be sized to
accommodate Horizontal Barometric Relief
Hood and Return Air Requirements)
HORIZONTAL RELIEF HOOD DIMENSIONS
Width - 31-5/8 in. (803 mm)
Height - 14-1/2 in. (368 mm)
TOP VIEW
OUTDOOR AIR HOOD
(Furnished with Economizer)
30
(762)
15-1/2
(394)
21-3/8
(543)
38-3/4
(984)
HORIZONTAL
SUPPLY AIR
OPENING
(On Unit)
This opening
not used in
Horizontal
Applications
with
Economizer
6-1/8
(156)
HORIZONTAL BAROMETRIC
RELIEF DAMPERS
(Optional - Must be Ordered Extra and
Field Installed on Field fabricated
Return Air Duct)
4-1/8
OUTDOOR
(105)
AIR
HORIZONTAL
RETURN AIR
OPENING
27-3/4
(705)
19-3/4
(502)
EXHAUST
AIR
6
(152) OPTIONAL RETURN AIR OPENING
RETURN AIR
RETURN AIR DUCT INLET
DUCT TRANSITION
(Field Fabricated - Must be sized to
WITH ECONOMIZER AND HORIZONTAL
(Field fabricated and
accommodate Horizontal Barometric
DISCHARGE KIT (required)
installed on unit)
Relief Hood and Return Air Requirements)
(Field Installed)
END VIEW
BACK VIEW
NOTE - Return Air Duct and Transition must be supported.
HORIZONTAL BAROMETRIC RELIEF DAMPERS
(Field installed in horizontal return air duct adjacent to unit)
31-5/8 (803)
1 29-1/2
6-1/2
(165)
(749)
14-1/2
(368) 1
13
(300)
FRONT VIEW
1 NOTE
SIDE VIEW
- Opening size required in return air duct.
Energence™ Packaged Electric / Electric 7.5 to 12.5 Ton / Page 31
ACCESSORY DIMENSIONS - INCHES (MM)
CLIP CURBS - DOUBLE DUCT OPENING
1-13/16
(46)
91-3/4
(2330)
21-3/4
(552)
54-1/4
(1378)
50-5/8
(1286)
95-3/8
(2423)
29-3/4
(756)
8-1/2
(216)
8 (203)
14 (356)
18 (457)
24 (610)
SUPPLY
OPENING
26-3/4
(679)
RETURN
OPENING
1-13/16
(46)
29-3/4
(756)
7-1/8
(181)
NOTE - Roof deck may be omitted within confines of curb.
TYPICAL FLASHING DETAIL FOR ROOF CURB
BASE BOTTOM
FIBERGLASS
INSULATION
(Furnished)
DETAIL ROOF CURB
1-13/16
(46)
PACKAGED
UNIT
COUNTER FLASHING
(Field Supplied)
NAILER STRIP
(Furnished)
ROOF CURB
(Extends around entire
perimeter of unit)
CANT STRIP
(Field Supplied)
ROOFING
MATERIAL
8 (203)
14 (356)
18 (457)
24 (610)
FACTORY INSTALLED
PERIMETER WOOD
NAILER STRIP
RIGID INSULATION
(Field Supplied)
2 (51)
Energence™ Packaged Electric / Electric 7.5 to 12.5 Ton / Page 32
ACCESSORY DIMENSIONS - INCHES (MM)
STANDARD ROOF CURBS - DOUBLE DUCT OPENING
1-13/16
(46)
91-3/4
(2330)
21-3/4
(552)
54-1/4
(1378)
50-5/8
(1286)
95-3/8
(2423)
29-3/4
(756)
8-1/2
(216)
8 (203)
14 (356)
24 (610)
SUPPLY
OPENING
26-3/4
(679)
RETURN
OPENING
1-13/16
(46)
29-3/4
(756)
7-1/8
(181)
NOTE - Roof deck may be omitted within confines of curb.
TYPICAL FLASHING DETAIL FOR ROOF CURB
BASE BOTTOM
FIBERGLASS
INSULATION
(Furnished)
DETAIL ROOF CURB
1-13/16
(46)
PACKAGED
UNIT
COUNTER FLASHING
(Field Supplied)
FACTORY INSTALLED
PERIMETER WOOD
NAILER STRIP
NAILER STRIP
(Furnished)
ROOF CURB
(Extends around entire
perimeter of unit)
CANT STRIP
(Field Supplied)
ROOFING
MATERIAL
8 (203)
14 (356)
24 (610)
RIGID INSULATION
(Field Supplied)
2 (51)
Energence™ Packaged Electric / Electric 7.5 to 12.5 Ton / Page 33
ACCESSORY DIMENSIONS - INCHES (MM)
ROOF CURBS WITH SUPPLY & RETURN AIR TRANSITIONS FOR CEILING DIFFUSERS
LASRT08/10 ROUND TRANSITIONS
(for 092 models with FD11−95, RTD11−95 Diffusers)
Typ.
30
(762)
1−1/2
(38)
31
(787)
8
(203)
2 (51)
20 IN. (508 mm)
Diameter
SUPPLY
AIR
OPENING
RETURN
AIR
OPENING
LASRT10/12 & LASRT15 RECTANGULAR TRANSITIONS
(for 102 thru 150 models with FD11−135−185, RTD11−135−185 Diffusers)
30
(762)
Typ.
1−1/2
(38)
31 (787)
LASRT10/12
39 (991)
LASRT15
8 (203)
30-1/2
(775)
4
(102)
30-1/2
(775)
TOP VIEW
2 (51)
27-3/4 (705)
LASRT10/12
35-3/4 (908)
LASRT15
17-3/4
(451)
Energence™ Packaged Electric / Electric 7.5 to 12.5 Ton / Page 34
31-1/2 (800)
LASRT08/10
LASRT10/12
39-1/2 (1003)
LASRT15
ACCESSORY DIMENSIONS - INCHES (MM)
COMBINATION CEILING SUPPLY AND RETURN DIFFUSERS
STEP-DOWN CEILING DIFFUSER
E
FLUSH CEILING DIFFUSER
D
H
G
E
H
F
G
H
G
F
G
C
C
2 (51)
L
2 (51)
A
B
D
H
A
B
J
K
Model Number
A
RTD11-95
in.
mm
B
in.
mm
C
in.
mm
D
in.
mm
E
in.
mm
F
in.
mm
G
in.
mm
H
in.
mm
J
in.
mm
K
in.
mm
L
in.
mm
Duct Size
47-5/8
Model Number
A
1159
29-5/8
C
D
E
1158
22-1/2
G
13-3/4
349
45-1/2
1156
16-5/8
422
27
in.
45
in.
in.
in.
mm
Duct Size
752
686
mm
H
1159
29-5/8
mm
mm
292
47-5/8
in.
mm
F
572
11-1/2
in.
mm
699
45-1/2
in.
mm
365
27-1/2
in.
mm
B
752
14-3/8
FD11-95
1143
22-1/2
572
11-1/4
286
13-1/2
343
in.
20 round
mm
508 round
27-1/2
699
8-1/8
206
in.
20 round
mm
508 round
Energence™ Packaged Electric / Electric 7.5 to 12.5 Ton / Page 35
ACCESSORY DIMENSIONS - INCHES (MM)
COMBINATION CEILING SUPPLY AND RETURN DIFFUSERS
STEP-DOWN CEILING DIFFUSER
F
E
H
G
G
FLUSH CEILING DIFFUSER
F
E
D
J
K
H
G
G
D
J
K
C
C
2 (51)
2 (51)
N
B
B
M
Model Number
A
in.
mm
B
in.
mm
C
in.
mm
D
in.
mm
E
in.
mm
F
in.
mm
G
in.
mm
H
in.
mm
J
in.
mm
K
in.
mm
L
in.
mm
M
in.
mm
N
in.
mm
Duct Size in.
mm
A
A
L
RTD11-135
47-5/8
1210
35-5/8
905
20-5/8
524
33-1/2
851
45-1/2
1156
4-1/2
114
18
457
2-1/2
64
28
711
2-3/4
70
45-1/2
1156
33-1/2
851
9-1/8
232
18 x 28
457 x 711
RTD11-185
47-5/8
1210
47-5/8
1210
24-5/8
625
45-1/2
1156
45-1/2
1156
4-1/2
114
18
457
2-1/2
64
36
914
4-3/4
121
45-1/2
1156
45-1/2
1156
10-1/8
257
18 x 36
457 x 914
Energence™ Packaged Electric / Electric 7.5 to 12.5 Ton / Page 36
Model Number
A
in.
mm
B
in.
mm
C
in.
mm
D
E
F
H
J
47-5/8
1210
1210
35-5/8
47-5/8
905
1210
23-1/4
29-1/4
591
743
33
45
838
1143
in.
45
45
mm
1143
1143
in.
4-1/2
4-1/2
114
114
in.
18
18
mm
457
457
2-1/4
2-1/4
mm
57
57
in.
28
36
in.
in.
mm
Duct Size
47-5/8
mm
mm
K
FD11-185
in.
mm
G
FD11-135
in.
mm
711
914
2-1/2
4-1/2
64
114
18 x 28
18 x 36
457 x 711
457 x 914
REVISIONS
Section
Description
Blower Data
Updated.
Electrical Data
Updated for LCH150S4B.
Rating Tables
Updated rating tables for LCH150S4B.
Specifications
Updated for LCH150S4B.
Visit us at www.lennox.com
For the latest technical information, www.lennoxcommercial.com
Contact us at 1-800-4-LENNOX
NOTE - Due to Lennox’ ongoing commitment to quality, Specifications, Ratings and Dimensions subject to change without notice and without incurring liability.
Improper installation, adjustment, alteration, service or maintenance can cause property damage or personal injury.
Installation and service must be performed by a qualified installer and servicing agency.
©2011 Lennox Industries, Inc.
Download PDF