TECHNICAL GUIDE R-410A ZF SERIES 7-1/2 THRU

862075-XTG-G-0415
®
TECHNICAL GUIDE
R-410A
ZF SERIES
7-1/2 THRU 12-1/2 TON
50 Hz (Export)
Description
ASHRAE 90.1 COMPLIANT
YORK® Predator® units are convertible single packages
with a common footprint cabinet and common roof curb for
all 7-1/2 through 12-1/2 ton models. All units have two
compressors with independent refrigeration circuits to
provide 2 stages of cooling. The units were designed for
light commercial applications and can be easily installed on
a roof curb, slab, or frame.
All Predator® units are self-contained and assembled on
rigid full perimeter base rails allowing for 3-way forklift
access and overhead rigging. Every unit is completely
charged, wired, piped, and tested at the factory to provide a
quick and easy field installation.
All units are convertible between side and down airflow.
Independent economizer designs are used on side and
down discharge applications, as well as all tonnage sizes.
Predator® units are available in the following configurations:
cooling only, cooling with electric heat, and cooling with gas
heat. Electric heaters are available as factory-installed
options or field-installed accessories.
ZF 7-1/2 AND 10 TON
All units provide constant supply air volume.
ZF 12-1/2 TON
FOR DISTRIBUTION USE ONLY - NOT TO BE USED AT POINT OF RETAIL SALE
862075-XTG-G-0415
Table of Contents
Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Table of Contents . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Component Location . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Nomenclature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Features and Benefits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Guide Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Physical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Capacity Performance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Airflow Performance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Sound Performance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
Electrical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
Typical Wiring Diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
Weights and Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
Economizer Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
Component Location
Cooling With Gas Heat
Simplicity® SE control board
Filter Access
Disconnect location
w/screw connector for T-stat
(2” or 4” filter options) Filter drier
(solid core)
wiring and network connections (optional disconnect switch)
ZF Series utilize Micro-Channel
Aluminum Tube/Aluminum Fin
Condenser
Terminal block for
hi-voltage connection
Second model
nameplate
inside hinged
access panel
Slide-out motor and
blower assembly for
easy adjustment
and service
Dual stage
cooling for
maximum
comfort
Power ventor motor
Compressor #2
access (highefficiency
compressor
w/crankcase
heater)
20-gauge aluminized steel tubular
heat exchanger for
long life (stainless
steel option)
Base rails w/forklift
slots (three sides)
and lifting holes
Two-stage gas
heating to maintain
warm, comfortable
temperature
Roof curbs in eight- and
fourteen-inch heights. Roof
curbs for transitioning from
York Sunline™ footprint to
the ZF Series footprints
are also available (field
installed accessory)
2
Belt-drive
blower motor
Slide-out drain pan
with 3/4” NPT,
female connection
Toolless
door latch
Side entry power
and control wiring
knockouts
Ignition control
board for safe and
efficient operation
Compressor #1 access
(high-efficiency compressor
w/crankcase heater)
Johnson Controls Unitary Products
862075-XTG-G-0415
Nomenclature
7.5-12.5 Ton York® Model Number Nomenclature
Z F 090 N10 A 7 A AA 7 0 1 2 4 A
Product Category
Product Style
Z = A/C, Single Pkg., R410A
A = Style A
Product Identifier
Configuration Options (not required for all units)
These four digits will not be assigned until a quote is requested, or an order placed.
F = 11.2 EER 7.5 & 10 Ton A/C
11.0 EER 12.5 Ton A/C
SS Drain Pan
Honeywell Controller, DFS, APS
Simplicity®Smart Equipment w/Comm Card (BACnet, N2, Mod-Bus)
Nominal Cooling Capacity
2" Pleated Filters, MERV 7
090 = 7.5 Ton
120 = 10.0 Ton
150 = 12.5 Ton
4" Pleated Filters, MERV 13
BAS Ready Unit with Belimo Economizer
Shipping Bag
Any Combination of Additional Options that Don’t Have an Option Code Pre-assigned
Heat Type and Nominal Heat Capacity
C00 = Cooling Only. No heat installed
Product Generation
Gas Heat Options*
N10 = 100 MBH Output Aluminized Steel
N15 = 150 MBH Output Aluminized Steel
N20 = 200 MBH Output Aluminized Steel
S10 = 100 MBH Output Stainless Steel
S15 = 150 MBH Output Stainless Steel
S20 = 200 MBH Output Stainless Steel
* N10/S10 Not Available on ZF120/150
Electric Heat Options*
E18 = 18 KW
E24 = 24 KW
E36 = 36 KW
E54 = 54 KW
* No Electric Heat Options for ZF090
7 = Seventh Generation
Additional Options
AA = None
AB = Phase Monitor
AC = Coil Guard
AD = Dirty Filter Switch
AE = Phase Monitor & Coil Guard
AF = Phase Monitor & Dirty Filter Switch
AG = Coil Guard & Dirty Filter Switch
AH = Phase Monitor, Coil Guard & Dirty Filter Switch
RC = Coil Guard & American Flag
TA = Technicoat Condenser Coil
TJ = Technicoat Evaporator Coil
TS = Technicoat Evaporator & Condenser Coils
EA = ElectroFin Condenser Coil
EJ = ElectroFin Evaporator Coil
ES = ElectroFin Cond & Evap Coils
ZZ = If desired option combination is not listed above, ZZ will be assigned and configuration options will be
located in digits 15-18.
Airflow
A = Std. Motor
D = Std. Motor/Motorized Damper (Downflow Only)
H = Std Motor/Low Leak Econ/Barometric Relief (Downflow
& Horizontal End Return Only)
J = Std Motor/Low Leak Econ/Power Exhaust (Downflow
& Horizontal End Return Only)
N = Hi Static
R = Hi Static/Motorized Damper (Downflow Only)
V = Hi Static Mtr/Low Leak Econ/Barometric Relief
(Downflow & Horizontal End Return Only)
W = Hi Static Mtr/Low Leak Econ/Power Exhaust
(Downflow & Horizontal End Return Only)
** Only Hi Static Is Offered On ZF150
Installation Options
A = No Options Installed
B = Option 1
E = Option 3
F = Option 4
G = Options 1 & 3
H = Options 1 & 4
L = Options 1,3 & 4
R = Options 3 & 4
Options
1 = Disconnect
3 = Smoke Detector S.A.
4 = Smoke Detector R.A.
Voltage
7 = 380/415-3-50
Johnson Controls Unitary Products
3
862075-XTG-G-0415
Features and Benefits
Standard Features
• High Efficiency – High efficiency units reach as high as
11.2 EER. Gas/electric units have electronic spark ignition
and power vented combustion with steady state efficiencies
of 80%. These efficiencies exceed all legislated minimum
levels and provide low operating costs.
• Service Friendly – The Predator® incorporates a number
of enhancements which improve serviceability.
The motor and blower slide out of the unit as a common
assembly. This facilitates greater access to all the indoor
airflow components, thus simplifying maintenance and
adjustment.
Service time is reduced through the use of hinged,
toolless panels. Such panels provide access to frequently
inspected components and areas, including the control
box, compressors, filters, indoor motor & blower, and the
heating section. The panels are screwed in place at the
factory to prevent access by children or other
unauthorized persons. It is recommended that the panels
be secured with screws once service is complete.
Service windows have been placed in both condenser
section walls. Rotation of the cover allows easy access to
the condenser coils for cleaning or inspection.
The Simplicity® SE control board provides alarm
messages to help quickly identify any faults.
All units use the same standard filter size. This
standardization removes any confusion on which filter
sizes are needed for replacement.
The non-corrosive drain pan slides out of the unit to permit
easy cleaning. The drain pan is accessed by removing the
drain pan cover plate on the rear of the unit. Once the plate is
removed, the drain pan slides out through the rear of the unit.
All Predator® units have a second model nameplate
located inside the control access door. This is to prevent
deterioration of the nameplate through weathering.
• Coil Technology – ZF condensers utilize Micro-Channel
“all aluminum” condensers which provide improved heat
transfer capabilities and reduced charge volumes.
• Environmentally Aware – For improved Indoor Air
Quality, a combination of foil faced and elastometric
rubber insulation is used exclusively throughout the units.
• Balanced Heating – The Predator® offers “Ultimate
Heating Comfort” with a balance between 1st and 2nd stage
gas heating. The first stage of a gas heat Predator® unit
provides 60% of the heating capacity. Balanced heating
allows the unit to better maintain desired temperatures.
• Convertible Airflow Design – The side duct openings
are covered when they leave the factory. If a side supply/
return is desired, the installer simply removes the two side
duct covers from the outside of the unit and installs them
over the down shot openings. No panel cutting is required.
Convertible airflow design allows maximum field flexibility
and minimum inventory.
• System Protection - Suction line freezestats are supplied
on all units to protect against loss of charge and coil frosting
when the economizer operates at low outdoor air
4
temperatures while the compressors are running. Every unit
has solid-core liquid line filter-driers and high and lowpressure switches. Internal compressor protection is
standard on all compressors. Crankcase heaters are
standard on reciprocating compressors. Scroll compressors
do not require crankcase heaters. Phase Monitors are
standard on units with scroll compressors. This accessory
monitors the incoming power to the unit and protects the
unit from phase loss and reversed phase rotation.
• Advanced Controls - Simplicity® SE control boards have
standardized a number of features previously available only
as options or by utilizing additional controls.
The Simplicity® SE control board used in this
product will effectively operate the cooling system
down to 0°F when this product is applied in a comfort
cooling application for people. An economizer is
typically included in this type of application. When
applying this product for process cooling applications
(computer rooms, switchgear, etc.), please
reference applications bulletin AE-011-07 or call the
applications department for Unitary Products @ 1877-UPG-SERV for guidance. Additional
accessories may be needed for stable operation at
temperatures below 30°F.
• Units will come with the new state of the art Simplicity
SE (Smart Equipment) control system. The new unit
control incorporates the best of the already proven
Simplicity™ unitary controls and creates a more robust,
intelligent control. The goal of this control is to utilize
cutting edge technology making the equipment easier to
install, operate, and service. All units are Factory
commissioned, configured, and run tested.
• Versatile - The Simplicity SE control can be configured to
use with a standard thermostat (easy to connect screw
terminals), A zone sensor, or can be setup to
Johnson Controls Unitary Products
862075-XTG-G-0415
communicate with multiple BAS communication protocols
to integrate with building automation systems.
• Reduce field installed complexity - Each unit will comes
equipped with factory installed supply air, return air, and
outdoor air temperature sensors providing key
temperature readings thus reduce field installed
complexity.
• On-board USB Port - The new control comes with a long
list of features including data logging, current and
previous system faults and software update capabilities
using the on board USB port and common flash drive.
Energy use monitoring capabilities allow custom tailoring
to allow a system to work more efficiently at all times and
occupancy levels. Self test and start-up reports also
available from the board VIA the USB port.
• Embedded LCD Display - The board has a easy to read,
built-in LCD display and easy to use navigation joystick
and buttons allowing the user to quickly navigate the
menus displaying unit status, options, current function,
supply, return and outdoor temperatures, fault codes and
other information.
• Safety Monitoring - The control monitors the outdoor,
supply, and return air temperatures and the high and low
pressure switch status on the independent refrigerant
circuits. On units with heating the gas valve and high
temperature limit switches are monitored on gas and
electric heating units. The control also monitors the
voltage supplied to the unit and will protect the unit if low
voltage due to a brown out, or other electrical issue
occurs.
• Low Ambient - An integrated low-ambient control allows
units to operate in the cooling mode down to 0°F outdoor
ambient without additional components or intervention.
Optionally, the control board can be programmed to
lockout the compressors when the outdoor air
temperature is low or when free cooling is available.
• Anti-Short Cycle Protection - To aid compressor life, an
anti- short cycle delay is incorporated into the standard
control. Compressor reliability is further ensured by
programmable minimum run times. For testing, the antishort cycle delay can be temporarily overridden with the
push of a button.
• Fan Delays - Fan on and fan off delays are fully
programmable. Furthermore, the heating and cooling fan
delay times are independent of one another. All units are
programmed with default values based upon their
configuration of cooling and/or heating capacity.
• Nuisance Trip Protection and Three Strikes - To
prevent nuisance calls, the control board uses a three
times, you're out philosophy. The high, low-pressure
switch, anti-freeze protection, low voltage or heating high
limit must trip three times within two hours before the unit
control board will lock out the associated compressor.An
alarm message will be displayed on the LCD screen.
• Lead-Lag - An integrated Lead-Lag option allows equal
run time hours on all compressors, thereby extending the
life of all compressors. This option is selectable on the unit
control board.
Johnson Controls Unitary Products
• Low Limit Control (LLC) - To prevent the supply air from
dropping below a specified set point, when there is a
demand for cooling during cold outside conditions.
(Programmable Set point)
• Reliable – From the beginning – All units undergo
computer automated testing before they leave the factory.
Units are tested for refrigerant charge and pressure, unit
amperage, and 100% functionality. For the long term – All
Predator® units are painted with a long lasting, powder
paint that stands up over the life of the unit. The paint
used has been proven by a 1000 hour salt spray test.
• Flexible Placement – All models and configurations
share the same cabinet/footprint and thus the same roof
curb. You have the flexibility to set one curb and choose
the correct tonnage size and heating option after the
internal loads have been determined.
To further simplify planning and installation, Predator® ZF
cabinets are designed to fit your roof. With the optional
roof curb, the unit ductwork is designed to fit around 24”
on-center joists or between 48” on-center joists.
The drain pan can be rotated to drain to either the front or
the rear of the unit. Additionally, the drain pan can be
fitted to drain through the roof curb. As it is sometimes
difficult to have a level installation, the drain pan features
a generous slope to ensure proper drainage.
• Full Perimeter Base Rails – The permanently attached
base rails provide a solid foundation for the entire unit and
protect the unit during shipment. The rails offer forklift
access from 3 sides, and rigging holes are available so that
an overhead crane can be used to place the units on a roof.
• Easy Installation – Gas and electric utility knockouts are
supplied in the unit underside as well as the side of the unit.
A clearly identified location is provided to mount a field
supplied electrical disconnect switch. Utility connections can
be made quickly and with a minimum amount of field labor.
All units are shipped with 2” throw-away filters installed.
• Wide Range of Indoor Airflows – All indoor fan motors
are belt-drive type providing maximum flexibility to handle
most airflow requirements. For high static applications,
factory installed alternate indoor fan motors are available.
With the optional indoor fan motor, all units can supply
nominal airflow at a minimum of 1.5” ESP.
• Warranty - All models include a 1-year limited warranty
on the complete unit. Compressors and electric heater
elements each carry a 5-year warranty. Aluminized steel
and stainless steel tubular heat exchangers carry a 10year warranty.
Factory Installed Options
YORK® offers several equipment options factory installed, for
the Predator®line.
• Optional Factory Installed Economizers - Predator units
offer a variety of optional factory installed economizers
with low leak dampers. The outdoor air enthalpy sensor
enables economizer operation if the outdoor enthalpy is
less than the setpoint of the economizer logic module. See
economizer options section to determine the correct
economizer for your application.
5
862075-XTG-G-0415
• Down flow / End Return Economizers (with barometric
relief and fresh air hood) - All units offer a variety of
optional factory installed down flow economizers that are
shipped, installed and wired with low leak dampers
designed to meet ASHRAE 90.1-2010, AMCA 511 Class
1A damper, and the International Energy Conservation
Code (IECC) certification requirements by achieving
leakage rates of 3 cfm/sq. ft. at 1" of static pressure. Each
economizer goes through a rigorous 60,000 cycle test. Dry
bulb, single enthalpy, and dual enthalpy (with field installed
kit) can be selected. The economizer has spring return,
fully modulating damper actuators and is capable of
introducing up to 100% outdoor air. As the outdoor air
intake dampers open, the return air dampers close. The
changeover from mechanical refrigeration to economizer
operation is regulated by the outdoor air dry bulb
temperature or the outdoor air enthalpy input. The optional
(field installed) single or dual enthalpy kits provide
additional inputs to monitor outdoor air/ or return air
humidity and temperature for true enthalpy control. The
installer needs only to assemble the outdoor air hood,
attach the enthalpy control the hood and mount the hood
to the unit (Hood and control are provided).
• Power Exhaust - This factory option allows down flow or
horizontal end return economizer operation. The power
exhaust must be removed from the unit and mounted
in the horizontal end return duct work when applying
the product in the horizontal, end return
configuration.
• Motorized Outdoor Air Damper - The motorized outdoor
air damper includes a slide-in/plug-in damper assembly
with an outdoor air hood and filters. The outdoor air
dampers open to the preset position when the indoor fan
motor is energized. The damper has a range of 0% to
100% outdoor air entry. Factory installed option or field
installed accessory.
• Alternate Indoor Blower Motor - For applications with
high static restrictions, units are offered with optional
indoor motors that provide higher static output and/or
higher airflow, depending upon the installer’s needs.
• Aluminized Steel Gas Heat Exchanger - For
applications in non-corrosive environments.
• Stainless Steel Gas Heat Exchanger - For applications
in corrosive environments, this option provides a full
stainless steel heat exchanger assembly.
• Stainless Steel Drain Pan - An optional rust-proof
stainless steel drain pan is available to provide years of
trouble-free operation in corrosive environments.
• Electric Heaters (10 & 12.5 Ton Only) - The electric
heaters range from 18KW to 54kW and are available in all
the voltage options of the base units. All heaters are dual
staged. All heaters are intended for single point power
supply.
• Disconnect Switch - For gas heat units and cooling units
with electric heat, a HACR breaker sized to the unit is
provided. For cooling only units, a switch sized to the
largest electric heat available for the particular unit is
provided. Factory installed option only.
6
• Smoke Detectors - The smoke detectors stop operation
of the unit by interrupting power to the control board if
smoke is detected within the air compartment. Available
for both the supply and/or return air configurations.
• Filters – 2” Pleated MERV 7 or 4” Pleated MERV 13 are
available to meet LEED requirements. A 2” Throwaway is
shipped as standard.
Factory-installed smoke detectors may be subjected to
extreme temperatures during "off" times due to outside air
infiltration. These smoke detectors have an operational
range of -4 °F to 158°F. Smoke detectors installed in areas
that could be outside this range will have to be relocated to
prevent false alarms.
• Phase Monitors - Designed to prevent unit damage. The
phase monitor will shut the unit down in an out-of phase
condition. (Standard on units with Scroll Compressors.)
• Coil Guard - Customers can purchase a coil guard kit to
protect the condenser coil from damage. Additionally, this
kit stops animals and foreign objects from entering the
space between the inner condenser coil and the main
cabinet. This is not a hail guard kit.
• Dirty Filter Switch - This kit includes a differential
pressure switch that energizes the fault light on the unit
thermostat, indicating that there is an abnormally high
pressure drop across the filters. Factory installed option or
field installed accessory.
• Technicoat Condenser Coils - The condenser coils are
coated with a phenolic coating for protection against
corrosion due to harsh environments.
• Technicoat Evaporator Coil - The evaporator coils are
coated with a phenolic coating for protection against
corrosion due to harsh environments.
• ElectroFin® E-coat Condenser Coils - The condenser
coils are coated with an epoxy polymer coating to protect
against corrosion.
• ElectroFin® E-coat Evaporator Coils - The evaporator
coils are coated with an epoxy polymer coating to protect
against corrosion.
Control Options
• Simplicity® SE with Communication Option Control The York® Simplicity® SE with Communication Option
Control is factory installed. It includes all the features of
the Simplicity® SE control with an additional gateway to
BACnet MS/TP (programmable to Modbus or N2
protocols).
• Novar® BAS Control - The Novar® building automation
system controller is factory installed. Incudes supply air
sensor, return air sensor, dirty filter indicator switch, and
air proving switch.
• CPC BAS Control - The Computer Process Controls
Model 810-3060 ARTC Advanced Rooftop building
automation system controller is factory installed. Includes
Johnson Controls Unitary Products
862075-XTG-G-0415
supply air sensor, return air sensor, dirty filter indicator
switch and air proving switch.
• Honeywell BAS Control - The Honeywell W7750C
building automation system controller is factory installed.
Includes air supply sensor, return air sensor, dirty filter
indicator switch, and air proving switch.
Field Installed Accessories
YORK® offers several equipment accessories for field
installation, for the Predator® line.
• Down flow and End Return Economizers (with fresh air
hood and barometric relief) - All units offer a variety of
optional factory installed down flow economizers that are
shipped, installed and wired with low leak dampers designed
to meet ASHRAE 90.1-2010, AMCA 511 Class 1A damper,
and the International Energy Conservation Code (IECC)
certification requirements by achieving leakage rates of 3
cfm/sq. ft. at 1" of static pressure. Each economizer goes
through a rigorous 60,000 cycle test. Dry bulb, single
enthalpy, and dual enthalpy (with field installed kit) can be
selected. The economizer has spring return, fully modulating
damper actuators and is capable of introducing up to 100%
outdoor air. As the outdoor air intake dampers open, the
return air dampers close. The changeover from mechanical
refrigeration to economizer operation is regulated by the
outdoor air dry bulb temperature or the outdoor air enthalpy
input. The dual enthalpy kit provides a second input used to
monitor the return air (field installed). The installer needs only
to assemble the outdoor air hood, attach the enthalpy control
the hood and mount the hood to the unit (Hood and control
are provided).
• Single or Dual Enthalpy Control, Accessories - These
kits contain the required components to convert a dry bulb
economizer to a single enthalpy and/or dual enthalpy
economizer.
• Barometric Relief Damper - Zero to 100% capacity
barometric relief dampers for use with horizontal flow, or
field installed slab economizers.
• Power Exhaust - This accessory installs in the unit with a
down flow economizer. Power exhaust plugs into the
connector in the unit bulkhead. You must purchase
1EH0408 barometric relief when applying to a
horizontal flow application.
• Manual Outdoor Air Damper - Like the motorized outdoor
air damper, each manual outdoor air damper includes a
slide-in damper assembly with an outdoor air hood and
filters. Customers have a choice of dampers with ranges of
0% to 100% or 0% to 35% outdoor air entry.
• Motorized Outdoor Air Damper - The motorized outdoor
air damper includes a slide-in/plug-in damper assembly with
an outdoor air hood and filters. The outdoor air dampers
open to the preset position when the indoor fan motor is
energized. The damper has a range of 0% to 100% outdoor
air entry. Factory installed option or field installed accessory.
• Smoke Detectors - The smoke detectors stop operation
of the unit by interrupting power to the control board if
smoke is detected within the air compartment.
Johnson Controls Unitary Products
• CO2 Sensor - Senses CO2 levels and automatically
overrides the economizer when levels rise above the
preset limits.
• Dirty Filter Switch - This kit includes a differential
pressure switch that energizes the fault light on the unit
thermostat, indicating that there is an abnormally high
pressure drop across the filters.
• Coil Guard - Field installed decorative wire coil guard.
• Hail Guard - This kit includes a sloped hood which installs
over the outside condenser coil and prevents damage to
the coil fins from hail strikes. Field installed accessory only.
• Flue Exhaust Extension Kit - In locations with wind or
weather conditions which may interfere with proper
exhausting of furnace combustion products, this kit can be
installed to prevent the flue exhaust from entering nearby
fresh air intakes.
• -60°F Gas Heat Kit - For installations which require gas
heat units to perform in low ambient temperatures, a gas
section heating kit is available. This kit provides electric
heat in the gas heat controls section to ensure the gas
valve and controls will continue to function properly at
extremely low temperatures.
• Gas Heat High Altitude Kit - This kit converts a gas heat
unit to operate at high altitudes, 2,000 to 6,000 feet.
Conversion kits are available for natural gas and propane.
• Gas Heat Propane Conversion Kit - This kit converts a
gas-fired heater from natural gas to propane. It contains the
main burner orifices and gas valve replacement springs.
• Gas Piping Kit - Contains pipe nipples, fittings and gas cock
required for gas supply connection with external shut off.
• Electric Heaters (10 & 12.5 Ton Only) - The electric
heaters range from 18 kW to 54kW.
All heaters are dual staged. Cooling units include an
adapter panel for easy installation of the electric heaters.
Necessary hardware and connectors are included with the
heaters. All heaters are intended for single point power
supply.
• Low Limit / Compressor Lockout Kit
• Compressor Lockout (CLO): To prevent mechanical
(compressorized) operation of the unit during cold
outdoor conditions where there is a risk of returning
liquid refrigerant back to the compressors.
• Low Limit Control (LLC): To prevent the supply air
from dropping below a specified setpoint by utilizing the
units first stage heating means when there is a demand
for cooling during cold outside conditions.
• Metal Frame Filter Kit - Metal frame with polyester filter
medium.
• Permanent Filters - Permanent filters are available.
• Roof Curbs - The roof curbs have insulated decks and are
shipped disassembled The roof curbs are available in 8” and
14” heights. For applications with security concerns, burglar
bars are available for the duct openings of the roof curbs.
• Roof Curb Transition - Single Piece Adapter (10” High) Roof curbs for transitioning from Sunline™ units to
Predator® units. Fits 7.5 to 12.5 Sunline™ roof curbs only.
7
862075-XTG-G-0415
• Burglar Bars - Mount in the supply and return openings
to prevent entry into the duct work.
• Thermostat - The units are designed to operate with 24volt electronic and electro-mechanical thermostats. All
units (with or without an economizer) operate with twostage heat/two-stage cool or two-stage cooling only
thermostats, depending upon unit configuration.
Accessories
Field Installed Accessories - Non-Electrical
MODEL
1BD0408
1CG0419
1CG0420
1CG0427
1CG0428
VOLTAGE
All
All
All
All
All
1HG0411
1HG0415
1FE0411
1FF0414
1FF0415
1FL0402
1FL0423
1GP0405
1HA0442
1HA0443
1NP0442
1RC0470
1RC0471
All
All
All
All
All
All
All
All
All
All
All
All
All
1RC0472
All
1WC0412
All
DESCRIPTION
Burglar Bars, Downflow
Coil Guard
Coil Guard
Coil Guard
Coil Guard
WHERE USED
All Cabinets
(Electric / Electric Models), 50” Tall Standard Cabinets
(Gas / Electric Models), 50" Tall Standard Cabinets
(Electric / Electric Models), 42” Tall Cabinets
(Gas / Electric Models), 42" Tall Cabinets
All Tall (50") Standard Cabinets, (Excludes 12.5T "V"
cabinets)
All Short (42") Standard Cabinets
All Cabinets
All Tall 50" Cabinets
All Tall 42" Cabinets
All Tall 50" Cabinets
All Tall 42" Cabinets
All Cabinets
All 7 1/2 - 12T Cabinets
All 7 1/2 - 12T Cabinets
All 6 - 12T Cabinets
All Cabinets
All Cabinets
Hail Guard Kit
Hail Guard Kit
Flue Exhaust Extension Kit
2" only Metal Filter Frame Kit
2" only Metal Filter Frame Kit
Permanent 2" only Filter Kit Includes (4) Four Filters)
Permanent 2" only Filter Kit (Includes (4) four Filters)
Gas Piping Kit
High Altitude Kit for Natural Gas
High Altitude Kit for Propane
Propane Conversion Kit
Roof Curb, 8" Height
Roof Curb, 14" Height
Roof Curb, Transition (7.5 T thru 12.5T Sunline to
Predator 3- 12T)
All Cabinets
Wooden Crate for extra protection during shipping and Standard Cabinets Only (not applicable to units 119" in
handling
length)
Field Installed Accessories - Electric Heat
MODEL
2TP04521850
VOLTAGE DESCRIPTION
380/415-3-50 18kW Electric Heat
WHERE USED
All 50" Cabinet 10 Ton Models
2TP04522450
380/415-3-50 24kW Electric Heat
All 50" Cabinet 10 and 12.5 Ton Models
2TP04523650
380/415-3-50 36kW Electric Heat
All 50" Cabinet 10 and 12.5 Ton Models
2TP04525450
380/415-3-50 54kW Electric Heat
All 50" Cabinet 10 and 12.5 Ton Models
*Note: No factory or field installed electric heater available for 42” Cabinet ZF090
8
Johnson Controls Unitary Products
862075-XTG-G-0415
Accessories (Continued)
Field Installed Accessories - Fresh Air
MODEL
1FA0413
1FA0414
VOLTAGE
All
All
DESCRIPTION
WHERE USED
Manual Outside Air Damper 0-35%, Downflow
All Cabinets
Manual Outside Air Damper 0-100%, Downflow
All Cabinets
Barometric Relief Kit for Power Exhaust, Horizontal
All Cabinets
1EH0408
All
Application
2EC0401
All
Single Enthalpy Control
All Cabinets
2EC0402
All
Dual Enthalpy Control (Includes 2 Sensors)
All Cabinets
Economizer for Downflow, End Return Horizontal, or
2EE04707624
All
ERV Applications. Includes FA Hood, Exhaust Hood w/ All 50" Cabinets
Baro Relief
Economizer for Downflow, End Return Horizontal, or
2EE04707424
All
ERV Applications. Includes FA Hood, Exhaust Hood w/ All 42" Cabinets
Baro Relief
2EE04706924
All
Horizontal Economizer without Barometric Relief
All Cabinets
2MD04703824
All
Motorized Damper, Downflow without Barometric Relief All Cabinets
Motorized Damper, Horizontal without Barometric
All Cabinets
2MD04703924
All
Relief
2PE04704706*
230
Power Exhaust 230V Downflow or Horizontal
All Cabinets
2PE04704746*
460
Power Exhaust 460V Downflow or Horizontal
All Cabinets
2PE04704758*
575
Power Exhaust 575V Downflow or Horizontal
All Cabinets
* Must be installed in return Duct on Horizontal Applications and a 1EH0408 is required. Approved for operation on 50Hz
Field Installed Accessories - Controls
MODEL
2AP0401
2AQ04700324
2AQ04700424
2DF0402
VOLTAGE
All
All
All
All
2SH0401
All
2SD04700824
2SD04700924
2SD04701024
S1-YKMAP1810-0P
All
All
All
S1-MP-PRTKIT0P
All
All
DESCRIPTION
Air Proving Switch
CO2 Space Accessory
CO2 Unit Accessory
Dirty Air Switch
Wall Mounted humidity sensor-For use with MagnaDry
Reheat or space humidity input to Simplicity SE board.
Smoke Detector for Supply
Smoke Detector for Return
Smoke Detector for Supply and Return
MAP (Mobile Access Portal) Gateway- For use with
Simplicity SE Control.
MAP (Multiple Access Portal) Gateway KitReplacement MAP gateway protective case, lanyard
and communication cable. Use only to replace worn or
damaged components.
WHERE USED
All Units
All Units
All Units
All Units
All Cabinets
All Gen 5 units and greater with 2" & 4" Filters
All Gen 5 units and greater with 2" & 4" Filters
All Gen 5 units and greater with 2" & 4" Filters
All Units
All Units
Field Installed Accessories - Electrical
MODEL
2BC04700106
2BC04700151
2BC04700154
2LA04704632
VOLTAGE
230
460
575
All
DESCRIPTION
Gas heat kit, -60ºF
Gas heat kit, -60ºF
Gas heat kit, -60ºF
Low Ambient Kit
Guide Specifications
GENERAL
Units shall be manufactured by York International Unitary
Products in an ISO 9001 certified facility. YORK® Predator®
units are convertible single packages with a common footprint
cabinet and common roof curb for all 7-1/2 through 12-1/2 ton
models. All units have two compressors with independent R410A refrigeration circuits to provide 2 stages of cooling. The
units were designed for light commercial applications and can
be easily installed on a roof curb, slab, or frame. All Predator®
units are self-contained and assembled on rigid full perimeter
base rails allowing for 3-way forklift access and overhead
rigging. Every unit is completely charged with R-410A, wired,
Johnson Controls Unitary Products
WHERE USED
All Units
All Units
All Units
All 3 - 10T units (excludes 12.5T "V" cabinets)
piped, and tested at the factory to provide a quick and easy
field installation. All units are convertible between side and
down airflow. Independent economizer designs are used on
side and down discharge applications, as well as all tonnage
sizes. Predator® units are available in the following
configurations: cooling only, cooling with electric heat, cooling
with gas heat, heat pump, and heat pump with electric heat.
Electric heaters are available as factory-installed options or
field-installed accessories.
DESCRIPTION
Units shall be factory assembled, single package, (Elec/Elec, Gas/
Elec), designed for outdoor installation. They shall have built in
9
862075-XTG-G-0415
field convertible duct connections for down discharge supply/return
or horizontal discharge supply/return and be available with factory
installed options or field installed accessories. The units shall be
factory wired, piped and charged with R-410A refrigerant and
factory tested prior to shipment. All unit wiring shall be both
numbered and color coded. The cooling performance shall be
rated in accordance with DOE and AHRI test procedures and
MEW-2010.
UNIT CABINET
Unit cabinet shall be constructed of galvanized steel with
exterior surfaces coated with a non-chalking, powder paint
finish, certified at 1000 hour salt spray test per ASTM-B117
standards. Indoor blower sections shall be insulated with up to
1” thick insulation coated on the airside. Either aluminum foil
faced or elastometric rubber insulation shall be used in the
unit’s compartments and be fastened to prevent insulation from
entering the air stream. Cabinet doors shall be hinged with
toolless access for easy servicing and maintenance. Full
perimeter base rails shall be provided to assure reliable transit
of equipment, overhead rigging, fork truck access and proper
sealing on roof curb applications. Disposable 2” filters shall be
furnished as standard and be accessible through hinged access
door. Fan performance measuring ports shall be provided on
the outside of the cabinet to allow accurate air measurements
of evaporator fan performance without removing panels or
creating bypass of the coils. Condensate pan shall be slide out
design, constructed of a non corrosive material, internally
sloped and conforming to ASHRAE 62-B9 standards.
Condensate connection shall be a minimum of ¾” I.D. female
and be rigid mount connection.
INDOOR (EVAPORATOR) FAN ASSEMBLY
Fan shall be a belt drive assembly and include an adjustable
pitch motor pulley. Job site selected brake horsepower shall not
exceed the motors nameplate horsepower rating plus the service factor. Units shall be designed to operate within the service
factor. Fan wheel shall be double inlet type with forward curve
blades, dynamically balanced to operate smoothly throughout
the entire range of operation. Airflow design shall be constant
volume. Bearings shall be sealed and permanently lubricated
for longer life and no maintenance. Entire blower assembly and
motor shall be slide out design.
OUTDOOR (CONDENSER) FAN ASSEMBLY
temperature protection. The hermetic motor shall be
suction gas cooled and have a voltage range of + or –
10% of the unit nameplate voltage.
b. Shall have internal spring isolation and sound muffling to
minimize vibration and noise, and be externally isolated
on a dedicated, independent mounting.
Coils:
a. Evaporator coils shall have aluminum plate fins
mechanically bonded to seamless internally enhanced
copper tubes with all joints brazed. Special Phenolic
coating shall be available as a factory option.
b. Evaporator coils shall be of the direct expansion, drawthru design.
c. Condenser coils shall have Micro-Channel aluminum
tube, aluminum fins.
d. Condenser coils shall be of the draw-thru design.
Refrigerant Circuit and Refrigerant Safety Components shall
include:
a. Independent thermally operated expansion devices.
b. Solid core filter drier/strainer to eliminate any moisture or
foreign matter.
c. Accessible service gage connections on both suction
and discharge lines to charge, evacuate, and measure
refrigerant pressure during any necessary servicing or
troubleshooting, without losing charge.
d. The unit shall have two independent refrigerant circuits,
equally split in 50% capacity increments.
Unit Controls:
a. Unit shall be complete with self-contained low-voltage
control circuit protected by a resettable circuit breaker on
the 24-volt transformer side.
b. Unit shall incorporate a lockout circuit which provides
reset capability at the space thermostat or base unit
should any of the following standard safety devices trip
and shut off compressor:
c. Loss-of-charge/Low-pressure switch.
• High-pressure switch.
• Freeze-protection thermostat, evaporator coil. If any of
the above safety devices trip, an LED (light-emitting
diode) indicator shall flash a diagnostic code that
indicates which safety switch has tripped.
The outdoor fans shall be of the direct drive type, discharge air
vertically, have aluminum blades riveted to corrosion resistant
steel spider brackets and shall be dynamically balanced for
smooth operation. The outdoor fan motors shall have permanently
lubricated bearings internally protected against overload
conditions and staged independently. A cleaning window shall be
provided on two sides of the units for coil cleaning.
d. Unit shall incorporate “AUTO RESET” compressor over
temperature, over current protection.
REFRIGERANT COMPONENTS
f. Unit control board shall have on-board diagnostics and
fault code display.
Compressors:
a. Shall be fully hermetic type, direct drive, internally
protected with internal high-pressure relief and over
10
e. Unit shall operate with conventional thermostat designs
and have a low voltage terminal strip for easy hook-up.
g. Standard controls shall include anti-short cycle and low
voltage protection, and permit cooling operation down to
0 ºF.
Johnson Controls Unitary Products
862075-XTG-G-0415
h. Control board shall monitor each refrigerant safety switch
independently.
FACTORY INSTALLED OPTIONAL OUTDOOR AIR (Shall be
made available by either/or):
i. Control board shall retain last 5 fault codes in nonvolatile memory, which will not be lost in the event of a
power loss.
• DRY BULB AUTOMATIC ECONOMIZER - Outdoor and
return air dampers that are interlocked and positioned by
a fully-modulating, spring-return damper actuator. The
maximum leakage rate for the outdoor air intake dampers
shall be designed to meet ASHRAE 90.1-2010, AMCA
511 Class 1A damper, and the International Energy
Conservation Code (IECC) certification requirements by
achieving leakage rates of 3 cfm/sq. ft. at 1" of static
pressure. Changeover from compressor to economizer
operation shall be provided by an integral electronic
enthalpy control that feeds input into the basic module.
The outdoor intake opening shall be covered with a rain
hood that matches the exterior of the unit. Water
eliminator/filters shall be provided.
GAS HEATING SECTION (IF EQUIPPED)
Heat exchanger and exhaust system shall be constructed of
aluminized steel and shall be designed with induced draft combustion with post purge logic, energy saving direct spark ignition, and redundant main gas valve. The heat exchanger shall
be of the tubular type, constructed of T1-40 aluminized steel for
corrosion resistance and allowing minimum mixed air entering
temperature of 40 ºF. Burners shall be of the in-shot type, constructed of aluminum-coated steel. All gas piping shall enter the
unit cabinet at a single location, through either the side or bottom, without any field modifications. An integrated control board
shall provide timed control of evaporator fan functioning and
burner ignition. Heating section shall be provided with the following minimum protection:
a. Primary and auxiliary high-temperature limit switches.
b. Induced draft pressure sensor.
c. Flame roll out switch (manual reset).
d. Flame proving controls.
e. All two stage units shall have two independent stages of
capacity (60% 1st stage, 100% 2nd stage).
ELECTRIC HEATING SECTION (IF EQUIPPED)
An electric heating section, with nickel chromium elements,
shall be provided in a range of 18 thru 54 KW, offering two
states of capacity all sizes. The heating section shall have a primary limit control(s) (automatic reset) to prevent the heating
element system from operating at an excessive temperature.
The Heating Section assembly shall slide out of the unit for
easy maintenance and service. Units with Electric Heating Sections shall be wired for a single point power supply with branch
circuit fusing (where required).
• MOTORIZED OUTDOOR AIR DAMPERS – Outdoor and
return air dampers that are interlocked and positioned by
a 2-position, spring-return damper actuator. The
maximum leakage rate for the outdoor air intake dampers
shall not exceed 2% when dampers are fully closed and
operating against a pressure differential of 0.5 IWG. A
unit-mounted potentiometer shall be provided to adjust
the outdoor and return air damper assembly to take in the
design CFM of outdoor air to meet the ventilation
requirements of the conditioned space during normal
operation. Whenever the indoor fan motor is energized,
the dampers open up to one of two pre-selected positions
– regardless of the outdoor air enthalpy. Dampers return
to the fully closed position when the indoor fan motor is
de-energized. Dampers shall fully close on power loss.
ADDITIONAL FACTORY INSTALLED OPTIONS
• ALTERNATE INDOOR BLOWER MOTOR – For
applications with high restrictions, units are available with
optional indoor blower motors that provide higher static
output and/or higher airflow.
• ELECTRIC HEAT (10 & 12.5 Ton Only) - Electric Heaters
range from 18 kW to 54 kW and are available in all the
voltage options of the base unit.
UNIT OPERATING CHARACTERISTICS
• PHASE MONITOR - Designed to prevent damage in outof-phase condition.
Unit shall be capable of starting and running at 125 ºF outdoor
temperature, exceeding maximum load criteria of AHRI Standard 340/360. The compressor, with standard controls, shall be
capable of operation down to 0 ºF outdoor temperature. Unit
shall be provided with fan time delay to prevent cold air delivery
before heat exchanger warms up. (Gas heat only)
• COIL GUARD - Designed to prevent condenser coil
damage.
ELECTRICAL REQUIREMENTS - All unit power wiring shall
enter unit cabinet at a single factory provided location and be
capable of side or bottom entry to minimize roof penetrations
and avoid unit field modifications. Separate side and bottom
openings shall be provided for the control wiring.
STANDARD LIMITED WARRANTIES - Compressor – 5 Years,
Heat Exchanger – 10 Years, Elect. Heat Elem. – 5 Years,
Parts – 1 Year
Johnson Controls Unitary Products
• BAS CONTROLS - Include supply air sensor, return air
sensor, dirty filter indicator and air proving switch.
• DIRTY FILTER SWITCH – This kit includes a differential
pressure switch that energizes the fault light on the unit
thermostat, indicating that there is an abnormally highpressure drop across the filters.
• BREAKER – An HACR breaker can be factory installed
on gas heat units or cooling units with electric heat.
• DISCONNECT SWITCH - A disconnect can be factory
installed on a cooling only units sized for the largest
electric heat available.
11
862075-XTG-G-0415
• STAINLESS STEEL HEAT EXCHANGER – For
applications in a corrosive environment, this option
provides a full stainless steel heat exchanger assembly.
• SMOKE DETECTOR – A smoke detector can be factory
mounted and wired in the supply and/or return air
compartments.
OTHER PRE-ENGINEERED ACCESSORIES AVAILABLE
12
hardware. Used to relieve internal air pressure through
the unit during economizer operation.
• PROPANE CONVERSION KIT – Contains new orifices
and gas valve springs to convert from natural to L.P. gas.
• 60ºF GAS HEAT KIT – Provides an electric heat kit for the
gas compartment for use in extreme low ambient
conditions.
• ECONOMIZER (Downflow and Horizontal flow)
• ROOF CURB - 14” and 8” high, full perimeter knockdown
curb, with hinged design for quick assembly.
• POWER EXHAUST – (Unit mount – Downflow, Duct
mount – Horizontal flow)
• BAROMETRIC RELIEF DAMPER – (Unit mounted –
Downflow, Duct Mounted – Horizontal) – Contains a rain
hood, air inlet screen, exhaust damper and mounting
• DUAL ENTHALPY KIT - Provides a second input to
economizer to monitor return air.
Johnson Controls Unitary Products
862075-XTG-G-0415
Physical Data
ZF090-150 Physical Data
Models
Component
ZF090
ZF120
7.5
10
12.5
88200
115300
151500
Nominal Tonnage
Gross Capacity @ AHRI A point (Mbh)
ZF150
EER
11.2
11.2
11.0
Nominal CFM
3000
4000
5000
System power (KW)
7.21
10.05
12.7
R-410A
R-410A
R-410A
System 1
4-12
7-12
8-3
System 2
4-12
7-8
8-10
Refrigerant type
Refrigerant charge (lb-oz)
AHRI HEATING PERFORMANCE
Heating model
10
15
15
20
15
20
Heat input (K Btu)
120
180
180
240
180
240
Heat output (K Btu)
96
144
144
192
144
192
-
-
-
-
-
-
80
80
80
80
80
80
AFUE %
Steady state efficiency (%)
No. burners
4
6
6
8
6
8
No. stages
21
21
21
21
21
21
15-45
30-60
20-50
35-65
10-40
25-55
Gas Limit Setting (ºF)
165
165
195
160
195
160
Gas piping connection (in.)
3/4
3/4
3/4
3/4
3/4
3/4
Temperature Rise Range (ºF)
DIMENSIONS (inches)
Length
89
89
119-1/2
Width
59
59
59
Height
42
50-3/4
50-3/4
OPERATING WT. (lbs.)
880
1060
1253
Scroll
Scroll
Scroll
2
2
2
50 / 100
50 / 100
50 / 100
18.5
29.0
29.0
COMPRESSORS
Type
Quantity
Unit Capacity Steps (%)
CONDENSER COIL DATA
Face area (Sq. Ft.)
Rows
1
1
1
Fins per inch
23
23
23
.71/18
1/25
1/25
Tube diameter (in.)/mm
Circuitry Type
2-pass Microchannel 2-pass Microchannel 2-pass Microchannel
EVAPORATOR COIL DATA
Face area (Sq. Ft.)
10.6
13.2
Rows
3
4
13.2
4
Fins per inch
15
15
15
Tube diameter
0.375
0.375
0.375
Circuitry Type
Intertwined
Intertwined
Intertwined
TXV
TXV
TXV
Refrigerant control
Johnson Controls Unitary Products
13
862075-XTG-G-0415
ZF090-150 Physical Data (Continued)
Models
Component
ZF090
ZF120
ZF150
7.5
10
12.5
Nominal Tonnage
CONDENSER FAN DATA
Quantity of Fans
2
2
4
Fan diameter (Inch)
24
24
24
Type
Prop
Prop
Prop
Drive type
Direct
Direct
Direct
Quantity of motors
2
2
4
Motor HP each @ 50 Hz.
3/4
3/4
3/4
No. speeds
1
1
1
RPM @ 50 Hz.
9402
9402
9402
Nominal total CFM
7600
9500
13900
BELT DRIVE EVAP FAN DATA
Quantity
1
1
1
12 x 12
15 x 15
15 x 15
Centrifugal
Centrifugal
Centrifugal
Fan Size (Inch)
Type
Motor Sheave
1VM50
1VM50
1VM50
1VP56
Blower Sheave
AK59
AK54
AK74
AK66
BK72
A49
A47
A54
A56
BX56
Belt
Motor HP each @ 50 Hz.
RPM @ 50 Hz.
Frame size
1VP56
2
2
2
4
4
14253
14253
14253
14553
14553
56
56
56
184T
184T
FILTERS
Quantity - Size
1.
2.
3.
4.
5.
6.
14
4 - (24 x 16 x 2)4,
4 - (24 x 16 x 4)6
5
4 - (24 x 20 x 2)4,5
4 - (24 x 20 x 2)4, 5
4 - (24 x 20 x 4)6
4 - (24 x 20 x 4)6
1ST Stage 60% of 2nd Stage
1110 RPM 60 Hz.
1725 RPM 60 Hz.
2 In. Throwaway, Standard, MERV (Minimum Efficiency Reporting Value) 3
2 In. Pleated, Optional, MERV 7
4 In. Pleated, Optional, MERV 13
Johnson Controls Unitary Products
862075-XTG-G-0415
ZF078-150 Unit Limitations
Unit Limitations
Size
(Tons/KW)
Model
Unit Voltage
Applied Voltage
Outdoor DB Temp
Min
Max
Max (°F/°C)
090
(7.5/26)
ZF
380/415-3-50
342
457
125/52
120
(10/35)
ZF
380/415-3-50
342
457
125/52
150
(12.5/44)
ZF
380/415-3-50
342
457
125/52
Johnson Controls Unitary Products
15
862075-XTG-G-0415
Capacity Performance
ZF090-150 Cooling Capacities
ZF090 (7.5 Ton) Imperial
Air on
Evaporator Coil
CFM
2250
2625
3000
3325
3650
2250
2625
3000
3325
3650
16
WB
(°F)
Total
Capacity1,2
(MBh)
Total
Input
(kW)3
90
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
105.2
98.1
90.9
82.9
82.6
108.4
101.0
93.6
85.4
85.0
111.5
103.9
96.3
87.9
87.5
112.9
105.2
97.5
88.9
88.6
114.2
106.4
98.7
90.0
89.6
6.36
6.35
6.33
6.33
5.78
6.86
6.85
6.84
6.83
6.25
7.42
7.40
7.39
7.38
6.77
7.43
7.41
7.40
7.39
6.81
7.43
7.42
7.41
7.40
6.85
45.4
58.7
72.1
79.2
78.7
48.1
63.7
79.4
80.5
80.0
50.8
68.7
86.7
81.8
81.3
58.7
74.0
89.2
83.0
82.5
66.7
79.2
91.8
84.1
83.6
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
96.0
88.3
80.6
73.9
73.6
97.4
89.6
81.8
75.0
74.7
98.9
90.9
83.0
76.2
75.8
100.3
92.2
84.2
77.3
76.9
101.7
93.6
85.4
78.4
78.0
7.80
7.79
7.78
7.77
7.77
7.98
7.97
7.96
7.95
7.95
8.21
8.20
8.19
8.18
8.18
8.53
8.52
8.51
8.50
8.50
8.85
8.84
8.83
8.82
8.82
42.6
55.9
69.1
73.9
73.6
50.6
60.7
70.7
75.0
74.7
58.6
65.4
72.3
76.2
75.8
61.9
70.4
78.8
77.3
76.9
65.2
75.3
85.4
78.4
78.0
Temperature of Air on Condenser Coil
Sensible Capacity (MBh)
Total
Total
Return Dry Bulb (°F)
Capacity1,2
Input
(MBh)
(kW)3
85
80
75
70
65
85°F
36.2
33.7
102.4
7.01
49.6
45.4
31.2
94.4
6.99
62.9
57.1
44.5
35.4
86.4
6.98
76.7
71.5
58.3
49.1
39.9
79.2
6.97
78.7
76.4
63.0
53.9
44.7
78.7
6.96
38.7
35.9
104.1
7.19
53.8
48.3
34.0
95.9
7.17
68.9
60.7
48.0
37.5
87.8
7.16
79.2
76.0
62.6
51.8
41.0
80.5
7.15
80.0
81.2
67.4
56.3
45.1
80.0
7.15
41.2
38.0
105.8
7.42
58.1
51.1
36.8
97.5
7.41
74.9
64.3
51.4
39.6
89.3
7.39
81.8
80.4
66.9
54.4
42.0
81.8
7.38
81.3
86.0
71.8
58.7
45.6
81.3
7.38
44.9
40.3
107.3
7.74
62.0
54.3
38.0
98.9
7.73
79.1
68.3
54.0
41.4
90.5
7.71
83.0
85.2
68.8
55.9
43.1
83.0
7.70
82.5
87.8
71.0
57.8
44.6
82.5
7.70
48.5
42.7
108.8
8.06
65.9
57.5
39.2
100.3
8.05
83.3
72.3
56.6
43.3
91.8
8.03
84.1
90.0
70.8
57.4
44.1
84.1
8.02
83.6
89.6
70.3
56.9
43.6
83.6
8.02
105°F
33.4
24.1
89.6
8.60
46.6
37.3
28.1
82.2
8.59
59.8
50.6
41.3
32.0
74.8
8.57
72.8
63.5
54.2
45.0
35.7
68.7
8.58
73.6
67.4
58.2
48.9
39.6
68.4
8.58
38.1
26.4
90.8
8.78
50.7
40.8
30.9
83.3
8.77
63.4
55.3
47.2
39.1
75.8
8.75
74.5
69.5
58.7
47.9
37.1
69.6
8.76
74.7
73.7
62.6
51.4
40.2
69.3
8.76
42.8
28.6
92.0
9.01
54.9
44.3
33.8
84.4
9.00
66.9
60.0
53.1
46.2
76.7
8.98
76.2
75.4
63.1
50.7
38.4
70.5
8.99
75.8
80.1
67.0
53.9
40.8
70.2
8.99
43.8
30.1
93.3
9.33
58.5
46.6
34.8
85.6
9.31
73.2
63.2
53.1
43.1
77.9
9.30
77.3
76.9
64.1
51.4
38.6
71.6
9.30
76.9
79.0
65.9
52.7
39.6
71.3
9.30
44.8
31.6
94.7
9.65
62.1
48.9
35.7
86.9
9.63
79.5
66.3
53.1
39.9
79.0
9.62
78.4
78.4
65.2
52.0
38.8
72.6
9.62
78.0
78.0
64.8
51.6
38.4
72.3
9.62
90
45.6
59.0
72.4
79.2
78.7
57.7
63.9
70.1
80.5
80.0
69.8
68.8
67.8
81.8
81.3
68.1
73.9
79.8
83.0
82.5
66.3
79.1
91.8
84.1
83.6
39.6
52.7
65.8
68.7
68.4
43.5
57.4
71.3
69.6
69.3
47.4
62.1
76.7
70.5
70.2
55.7
66.8
77.9
71.6
71.3
64.1
71.6
79.0
72.6
72.3
Sensible Capacity (MBh)
Return Dry Bulb (°F)
85
80
75
70
95°F
36.3
27.0
49.7
40.4
31.0
63.1
53.7
44.4
35.1
76.8
67.5
58.1
48.8
78.7
72.2
62.9
53.6
43.5
29.3
53.9
43.9
33.9
64.3
58.4
52.6
46.8
79.3
73.4
62.6
51.8
80.0
78.6
67.3
56.0
50.8
31.7
58.1
47.4
36.7
65.5
63.1
60.8
58.5
81.8
79.3
67.0
54.7
81.3
84.9
71.7
58.4
49.6
33.4
62.0
50.0
38.0
74.3
66.6
58.8
51.0
83.0
81.7
68.9
56.2
82.5
84.3
71.0
57.8
48.4
35.1
65.8
52.6
39.3
83.2
70.0
56.7
43.5
84.1
84.1
70.9
57.6
83.6
83.6
70.4
57.1
115°F
30.4
21.3
43.5
34.3
25.1
56.6
47.4
38.2
29.0
68.7
59.5
50.3
41.1
68.4
62.6
53.4
44.2
32.7
23.4
47.6
37.8
28.0
62.5
52.2
41.8
31.5
69.6
65.5
54.8
44.0
69.3
68.9
57.9
46.8
34.9
25.5
51.7
41.2
30.8
68.4
56.9
45.4
34.0
70.5
71.6
59.2
46.8
70.2
75.3
62.3
49.3
38.0
26.8
55.0
43.3
31.5
72.0
59.7
47.4
35.1
71.6
72.1
59.3
46.6
71.3
73.8
60.7
47.7
41.2
28.1
58.4
45.3
32.2
75.7
62.6
49.4
36.3
72.6
72.6
59.5
46.4
72.3
72.3
59.2
46.1
65
39.5
44.2
40.9
44.7
42.4
45.2
43.4
44.6
44.4
43.9
32.0
35.0
33.2
35.7
34.4
36.4
33.8
34.7
33.2
32.9
Johnson Controls Unitary Products
862075-XTG-G-0415
ZF090 (7.5 Ton) Imperial (Continued)
Air on
Evaporator Coil
CFM
2250
2625
3000
3325
3650
WB
(°F)
Total
Capacity1,2
(MBh)
Total
Input
(kW)3
90
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
88.3
80.4
72.5
68.0
67.8
89.2
81.5
73.7
68.9
68.7
90.1
82.5
75.0
69.8
69.6
91.7
83.7
75.8
70.9
70.6
93.3
85.0
76.6
71.9
71.7
8.85
8.84
8.84
8.83
8.83
9.04
9.03
9.02
9.02
9.01
9.28
9.26
9.26
9.25
9.24
9.60
9.59
9.58
9.57
9.56
9.92
9.91
9.90
9.89
9.88
33.5
46.7
59.9
64.0
64.2
36.7
50.8
64.9
66.6
66.8
39.8
54.9
69.9
69.2
69.4
45.7
58.9
72.2
70.5
70.5
51.6
63.0
74.4
71.9
71.7
Temperature of Air on Condenser Coil
Sensible Capacity (MBh)
Total
Total
Return Dry Bulb (°F)
Capacity1,2
Input
(MBh)
(kW)3
85
80
75
70
65
118.4°F
26.8
20.2
85.8
9.48
40.1
33.4
26.8
76.9
9.47
53.3
46.6
40.0
33.3
68.0
9.45
63.4
56.8
50.1
43.5
36.8
66.8
9.45
63.6
59.2
52.5
45.9
39.2
66.6
9.45
29.1
22.5
86.1
9.66
43.8
36.8
29.8
78.0
9.64
58.5
51.0
43.6
36.1
69.8
9.63
65.9
62.5
54.7
46.9
39.0
67.7
9.63
66.1
65.1
57.2
49.2
41.2
67.5
9.63
31.3
24.8
86.4
9.88
47.5
40.1
32.8
79.0
9.87
63.7
55.5
47.2
38.9
71.6
9.86
68.3
68.2
59.2
50.2
41.3
68.5
9.86
68.6
71.1
61.8
52.4
43.1
68.4
9.86
33.5
25.5
88.6
10.20
50.5
42.1
33.7
80.1
10.19
67.6
58.7
49.9
41.0
71.7
10.18
70.1
69.6
60.4
51.2
42.0
69.6
10.17
70.1
71.2
61.8
52.4
43.0
69.4
10.17
35.7
26.2
90.7
10.51
53.6
44.1
34.7
81.3
10.51
71.4
62.0
52.5
43.1
71.9
10.50
71.8
71.0
61.5
52.1
42.6
70.6
10.49
71.7
71.3
61.8
52.4
42.9
70.4
10.49
90
21.5
35.1
48.6
54.8
55.9
23.3
38.0
52.6
60.6
61.8
25.1
40.9
56.7
66.5
67.8
26.2
43.6
61.1
68.5
69.1
27.3
46.4
65.5
70.6
70.4
Sensible Capacity (MBh)
Return Dry Bulb (°F)
85
80
75
70
125°F
19.8
18.1
33.4
31.6
29.9
46.9
45.2
43.5
41.7
53.1
51.4
49.7
47.9
54.2
52.5
50.8
49.1
22.1
20.8
36.4
34.8
33.3
50.8
48.9
47.0
45.1
58.6
56.6
54.5
52.5
59.8
57.8
55.8
53.8
24.3
23.5
39.5
38.0
36.6
54.6
52.6
50.5
48.5
64.1
61.7
59.4
57.0
65.4
63.1
60.8
58.4
24.7
23.1
41.8
39.9
38.0
58.9
56.7
54.5
52.4
67.1
64.8
62.4
60.1
67.9
66.2
63.9
61.6
25.0
22.7
44.1
41.8
39.5
63.2
60.8
58.5
56.2
70.2
67.8
65.5
63.2
70.4
69.3
67.0
64.7
65
46.2
47.4
50.4
51.7
54.6
56.1
57.8
59.3
60.9
62.4
1. These capacities are gross ratings. For net capacity, deduct air blower motor, MBh = 3.415 x kW. Refer to the appropriate Blower
Performance Table for the kW of the supply air blower motor.
2. Capacity rating are based on 80 F (26.6 C) Entering Air Dry Bulb Temperature.
3. These ratings include the condenser fan motors, the compressor motors and supply air blower motor (External Static Pressure 0.25 IWG/
62.3 Pa).
Johnson Controls Unitary Products
17
862075-XTG-G-0415
ZF090 (26 kW) Metric
Air on
Evaporator Coil
3
m /s
1.06
1.24
1.42
1.57
1.72
1.06
1.24
1.42
1.57
1.72
18
WB
(°C)
Total
Capacity1,2
(kW)
Total
Input
(kW)3
32
25
22
19
17
14
25
22
19
17
14
25
22
19
17
14
25
22
19
17
14
25
22
19
17
14
30.8
28.7
26.6
24.3
24.2
31.8
29.6
27.4
25.0
24.9
32.7
30.5
28.2
25.8
25.6
33.1
30.8
28.6
26.1
26.0
33.5
31.2
28.9
26.4
26.3
6.36
6.35
6.33
6.33
5.78
6.86
6.85
6.84
6.83
6.25
7.42
7.40
7.39
7.38
6.77
7.43
7.41
7.40
7.39
6.81
7.43
7.42
7.41
7.40
6.85
13.3
17.2
21.1
23.2
23.1
14.1
18.7
23.3
23.6
23.5
14.9
20.1
25.4
24.0
23.8
17.2
21.7
26.2
24.3
24.2
19.6
23.2
26.9
24.7
24.5
25
22
19
17
14
25
22
19
17
14
25
22
19
17
14
25
22
19
17
14
25
22
19
17
14
28.1
25.9
23.6
21.7
21.6
28.6
26.3
24.0
22.0
21.9
29.0
26.6
24.3
22.3
22.2
29.4
27.0
24.7
22.6
22.5
29.8
27.4
25.0
23.0
22.9
7.78
7.78
7.78
7.77
7.77
7.96
7.96
7.96
7.95
7.95
8.19
8.19
8.19
8.18
8.18
8.51
8.51
8.51
8.50
8.50
8.83
8.83
8.83
8.82
8.82
12.5
16.4
20.2
21.7
21.6
14.8
17.8
20.7
22.0
21.9
17.2
19.2
21.2
22.3
22.2
18.1
20.6
23.1
22.6
22.5
19.1
22.1
25.0
23.0
22.9
Temperature of Air on Condenser Coil
Sensible Capacity (kW)
Total
Total
Return Dry Bulb (°C)
Capacity1,2
Input
(kW)
(kW)3
29
27
24
21
18
29°C
10.6
9.9
30.0
7.01
14.5
13.3
9.1
27.7
6.99
18.4
16.7
13.1
10.4
25.3
6.98
22.5
20.9
17.1
14.4
11.7
23.2
6.97
23.1
22.4
18.5
15.8
13.1
23.1
6.96
11.3
10.5
30.5
7.19
15.8
14.1
10.0
28.1
7.17
20.2
17.8
14.1
11.0
25.7
7.16
23.2
22.3
18.3
15.2
12.0
23.6
7.15
23.5
23.8
19.8
16.5
13.2
23.5
7.14
12.1
11.1
31.0
7.42
17.0
15.0
10.8
28.6
7.40
22.0
18.8
15.1
11.6
26.2
7.39
24.0
23.6
19.6
16.0
12.3
24.0
7.38
23.8
25.2
21.0
17.2
13.4
23.8
7.38
13.1
11.8
31.4
7.74
18.2
15.9
11.1
29.0
7.73
23.2
20.0
15.8
12.1
26.5
7.71
24.3
25.0
20.2
16.4
12.6
24.3
7.70
24.2
25.7
20.8
16.9
13.1
24.2
7.70
14.2
12.5
31.9
8.06
19.3
16.8
11.5
29.4
8.05
24.4
21.2
16.6
12.7
26.9
8.03
24.7
26.4
20.7
16.8
12.9
24.7
8.02
24.5
26.3
20.6
16.7
12.8
24.5
8.02
41°C
9.8
7.1
26.3
8.56
13.7
10.9
8.2
24.1
8.57
17.5
14.8
12.1
9.4
21.9
8.57
21.3
18.6
15.9
13.2
10.5
20.1
8.58
21.6
19.8
17.0
14.3
11.6
20.0
8.58
11.2
7.7
26.6
8.74
14.9
12.0
9.1
24.4
8.75
18.6
16.2
13.8
11.5
22.2
8.75
21.8
20.4
17.2
14.0
10.9
20.4
8.76
21.9
21.6
18.3
15.1
11.8
20.3
8.76
12.6
8.4
27.0
8.97
16.1
13.0
9.9
24.7
8.98
19.6
17.6
15.6
13.5
22.5
8.98
22.3
22.1
18.5
14.9
11.3
20.7
8.99
22.2
23.5
19.6
15.8
12.0
20.6
8.99
12.8
8.8
27.4
9.29
17.1
13.7
10.2
25.1
9.29
21.5
18.5
15.6
12.6
22.8
9.30
22.6
22.5
18.8
15.1
11.3
21.0
9.30
22.5
23.2
19.3
15.5
11.6
20.9
9.30
13.1
9.3
27.8
9.61
18.2
14.3
10.5
25.5
9.61
23.3
19.4
15.6
11.7
23.2
9.62
23.0
23.0
19.1
15.2
11.4
21.3
9.62
22.9
22.9
19.0
15.1
11.3
21.2
9.62
32
13.4
17.3
21.2
23.2
23.1
16.9
18.7
20.5
23.6
23.5
20.5
20.2
19.9
24.0
23.8
20.0
21.7
23.4
24.3
24.2
19.4
23.2
26.9
24.7
24.5
11.6
15.4
19.3
20.1
20.0
12.8
16.8
20.9
20.4
20.3
13.9
18.2
22.5
20.7
20.6
16.3
19.6
22.8
21.0
20.9
18.8
21.0
23.2
21.3
21.2
Sensible Capacity (kW)
Return Dry Bulb (°C)
29
27
24
21
35°C
10.6
7.9
14.6
11.8
9.1
18.5
15.8
13.0
10.3
22.5
19.8
17.0
14.3
23.1
21.2
18.4
15.7
12.8
8.6
15.8
12.9
9.9
18.8
17.1
15.4
13.7
23.2
21.5
18.3
15.2
23.5
23.0
19.7
16.4
14.9
9.3
17.0
13.9
10.8
19.2
18.5
17.8
17.1
24.0
23.2
19.6
16.0
23.8
24.9
21.0
17.1
14.5
9.8
18.2
14.6
11.1
21.8
19.5
17.2
14.9
24.3
23.9
20.2
16.5
24.2
24.7
20.8
16.9
14.2
10.3
19.3
15.4
11.5
24.4
20.5
16.6
12.7
24.7
24.7
20.8
16.9
24.5
24.5
20.6
16.7
46°C
8.9
6.2
12.8
10.1
7.4
16.6
13.9
11.2
8.5
20.1
17.4
14.8
12.1
20.0
18.4
15.7
13.0
9.6
6.9
13.9
11.1
8.2
18.3
15.3
12.3
9.2
20.4
19.2
16.0
12.9
20.3
20.2
17.0
13.7
10.2
7.5
15.1
12.1
9.0
20.1
16.7
13.3
10.0
20.7
21.0
17.3
13.7
20.6
22.1
18.3
14.5
11.2
7.9
16.1
12.7
9.2
21.1
17.5
13.9
10.3
21.0
21.1
17.4
13.6
20.9
21.6
17.8
14.0
12.1
8.2
17.1
13.3
9.4
22.2
18.3
14.5
10.6
21.3
21.3
17.4
13.6
21.2
21.2
17.3
13.5
18
11.6
13.0
12.0
13.1
12.4
13.3
12.7
13.1
13.0
12.9
9.4
10.3
9.7
10.5
10.1
10.7
9.9
10.2
9.7
9.7
Johnson Controls Unitary Products
862075-XTG-G-0415
ZF090 (26 kW) Metric (Continued)
Air on
Evaporator Coil
m3/s
1.06
1.24
1.42
1.57
1.72
WB
(°C)
Total
Capacity1,2
(kW)
Total
Input
(kW)3
32
25
22
19
17
14
25
22
19
17
14
25
22
19
17
14
25
22
19
17
14
25
22
19
17
14
25.9
23.6
21.2
19.9
19.9
26.1
23.9
21.6
20.2
20.1
26.4
24.2
22.0
20.5
20.4
26.9
24.5
22.2
20.8
20.7
27.4
24.9
22.5
21.1
21.0
8.85
8.84
8.84
8.83
8.83
9.04
9.03
9.02
9.02
9.01
9.28
9.26
9.26
9.25
9.24
9.60
9.59
9.58
9.57
9.56
9.92
9.91
9.90
9.89
9.88
9.8
13.7
17.6
18.7
18.8
10.7
14.9
19.0
19.5
19.6
11.7
16.1
20.5
20.3
20.3
13.4
17.3
21.2
20.7
20.7
15.1
18.5
21.8
21.1
21.0
Temperature of Air on Condenser Coil
Sensible Capacity (kW)
Total
Total
Return Dry Bulb (°C)
Capacity1,2
Input
(kW)
(kW)3
29
27
24
21
18
48°C
7.9
5.9
25.2
9.48
11.7
9.8
7.8
22.5
9.47
15.6
13.7
11.7
9.8
19.9
9.45
18.6
16.6
14.7
12.7
10.8
19.6
9.45
18.6
17.3
15.4
13.4
11.5
19.5
9.45
8.5
6.6
25.2
9.66
12.8
10.8
8.7
22.8
9.64
17.1
15.0
12.8
10.6
20.5
9.63
19.3
18.3
16.0
13.7
11.4
19.8
9.63
19.4
19.1
16.8
14.4
12.1
19.8
9.63
9.2
7.3
25.3
9.88
13.9
11.8
9.6
23.1
9.87
18.7
16.3
13.8
11.4
21.0
9.86
20.0
20.0
17.4
14.7
12.1
20.1
9.86
20.1
20.8
18.1
15.4
12.6
20.0
9.86
9.8
7.5
26.0
10.20
14.8
12.3
9.9
23.5
10.19
19.8
17.2
14.6
12.0
21.0
10.18
20.5
20.4
17.7
15.0
12.3
20.4
10.17
20.6
20.9
18.1
15.4
12.6
20.3
10.17
10.5
7.7
26.6
10.51
15.7
12.9
10.2
23.8
10.51
20.9
18.2
15.4
12.6
21.1
10.50
21.0
20.8
18.0
15.3
12.5
20.7
10.49
21.0
20.9
18.1
15.4
12.6
20.6
10.49
32
6.3
10.3
14.2
16.1
16.4
6.8
11.1
15.4
17.8
18.1
7.4
12.0
16.6
19.5
19.9
7.7
12.8
17.9
20.1
20.2
8.0
13.6
19.2
20.7
20.6
Sensible Capacity (kW)
Return Dry Bulb (°C)
29
27
24
21
52°C
5.8
5.3
9.8
9.3
8.8
13.7
13.2
12.7
12.2
15.6
15.1
14.6
14.0
15.9
15.4
14.9
14.4
6.5
6.1
10.7
10.2
9.7
14.9
14.3
13.8
13.2
17.2
16.6
16.0
15.4
17.5
16.9
16.3
15.8
7.1
6.9
11.6
11.1
10.7
16.0
15.4
14.8
14.2
18.8
18.1
17.4
16.7
19.2
18.5
17.8
17.1
7.2
6.8
12.2
11.7
11.1
17.3
16.6
16.0
15.3
19.7
19.0
18.3
17.6
19.9
19.4
18.7
18.0
7.3
6.7
12.9
12.2
11.6
18.5
17.8
17.2
16.5
20.6
19.9
19.2
18.5
20.6
20.3
19.6
19.0
18
13.5
13.9
14.8
15.2
16.0
16.4
16.9
17.4
17.8
18.3
1. These capacities are gross ratings. For net capacity, deduct air blower motor, MBh = 3.415 x kW. Refer to the appropriate Blower
Performance Table for the kW of the supply air blower motor.
2. Capacity rating are based on 80 F (26.6 C) Entering Air Dry Bulb Temperature.
3. These ratings include the condenser fan motors, the compressor motors and supply air blower motor (External Static Pressure 0.25 IWG/
62.3 Pa).
Johnson Controls Unitary Products
19
862075-XTG-G-0415
ZF120 (10 Ton) Imperial
Air on
Evaporator Coil
CFM
3000
3500
4000
4550
5100
3000
3500
4000
4550
5100
20
WB
(°F)
Total
Capacity1,2
(MBh)
Total
Input
(kW)3
90
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
120.6
115.1
109.6
103.7
95.5
128.2
122.4
116.6
110.3
101.6
135.9
129.7
123.5
116.8
107.6
134.8
128.7
122.7
116.1
106.9
133.8
127.8
121.8
115.3
106.2
8.40
8.47
8.54
8.56
8.56
8.64
8.71
8.78
8.80
8.80
8.97
9.04
9.11
9.14
9.14
9.53
9.60
9.67
9.69
9.69
9.98
10.05
10.12
10.15
10.14
68.1
83.7
99.2
103.7
95.5
70.2
90.3
110.4
110.3
101.6
72.2
96.9
121.5
116.8
107.6
92.3
107.0
121.7
116.1
106.9
112.4
117.1
121.8
115.3
106.2
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
120.9
108.8
96.8
89.8
85.2
128.2
115.4
102.6
95.3
90.3
135.5
122.0
108.5
100.7
95.5
136.2
122.6
109.0
101.2
95.9
136.8
123.2
109.5
101.6
96.4
10.83
10.72
10.60
10.55
10.52
11.12
11.01
10.89
10.84
10.81
11.51
11.40
11.28
11.22
11.20
12.08
11.96
11.85
11.79
11.76
12.54
12.43
12.32
12.26
12.23
66.9
78.9
91.0
89.8
85.2
71.0
85.2
99.4
95.3
90.3
75.2
91.5
107.8
100.7
95.5
96.7
102.7
108.7
101.2
95.9
118.3
113.9
109.5
101.6
96.4
Temperature of Air on Condenser Coil
Sensible Capacity (MBh)
Total
Total
Return Dry Bulb (°F)
Capacity1,2
Input
(MBh)
(kW)3
85
80
75
70
65
85°F
55.8
43.5
120.7
9.61
71.4
59.1
46.8
112.0
9.59
86.9
74.7
62.4
50.1
103.2
9.57
89.8
77.5
65.2
52.9
40.7
96.8
9.56
95.5
92.3
80.0
67.7
55.5
90.4
9.54
59.1
46.9
128.2
9.88
77.0
63.7
50.4
118.9
9.86
94.9
80.5
66.2
51.8
109.6
9.83
99.7
83.6
69.2
54.9
40.6
102.8
9.82
101.6 99.6
84.7
69.9
55.1
96.0
9.80
62.4
50.3
135.7
10.24
82.6
68.3
54.1
125.8
10.22
102.8 86.4
69.9
53.5
116.0
10.20
109.6 89.6
73.2
56.9
40.5
108.8
10.18
107.6 106.8 89.5
72.1
54.7
101.6
10.17
68.8
54.6
135.5
10.80
90.6
74.2
57.8
125.7
10.78
112.3 93.8
76.3
58.8
115.8
10.76
112.4 99.3
81.9
64.4
47.0
108.6
10.74
106.9 106.5 88.5
70.6
52.6
101.4
10.73
75.3
58.8
135.3
11.26
98.6
80.0
61.5
125.5
11.24
121.8 101.2 82.7
64.1
115.7
11.22
115.3 109.1 90.5
72.0
53.4
108.5
11.20
106.2 106.2 87.6
69.1
50.5
101.3
11.19
105°F
54.6
42.2
121.0
12.04
66.6
54.3
41.9
105.7
11.84
78.6
66.3
54.0
41.6
90.4
11.64
85.0
72.7
60.3
48.0
35.7
82.9
11.54
85.2
80.4
68.0
55.7
43.4
80.0
11.50
57.9
46.0
128.1
12.36
72.1
59.0
45.9
111.9
12.16
86.3
72.1
57.9
43.7
95.7
11.95
91.6
79.1
64.7
50.3
35.9
87.8
11.85
90.3
87.4
72.7
58.0
43.2
84.7
11.81
61.3
49.7
135.3
12.78
77.7
63.8
49.9
118.1
12.57
94.0
77.9
61.8
45.7
101.0
12.37
98.3
85.5
69.0
52.6
36.2
92.7
12.27
95.5
94.5
77.3
60.2
43.1
89.4
12.23
71.6
55.0
136.8
13.35
86.7
70.6
54.6
119.5
13.15
101.8 86.2
69.1
51.9
102.2
12.94
100.0 92.5
75.2
57.9
40.6
93.7
12.84
95.9
95.4
77.7
60.1
42.4
90.5
12.80
81.8
60.3
138.4
13.82
95.7
77.4
59.2
120.9
13.62
109.5 94.6
76.3
58.1
103.3
13.41
101.6 99.5
81.3
63.1
44.9
94.8
13.31
96.4
96.4
78.2
59.9
41.7
91.5
13.27
90
67.5
81.3
95.1
96.8
90.4
70.6
87.7
104.9
102.8
96.0
73.7
94.2
114.7
108.8
101.6
94.5
104.8
115.2
108.6
101.4
115.3
115.5
115.7
108.5
101.3
66.3
76.6
86.8
82.9
80.0
71.5
82.7
93.9
87.8
84.7
76.7
88.8
101.0
92.7
89.4
98.9
100.6
102.2
93.7
90.5
121.2
112.3
103.3
94.8
91.5
Sensible Capacity (MBh)
Return Dry Bulb (°F)
85
80
75
70
95°F
55.2
42.9
69.0
56.7
44.4
82.8
70.5
58.2
45.9
87.4
75.1
62.8
50.5
90.4
86.3
74.0
61.7
58.5
46.4
74.6
61.4
48.2
90.6
76.3
62.0
47.7
95.7
81.3
67.0
52.6
96.0
93.5
78.7
63.9
61.8
50.0
80.1
66.1
52.0
98.4
82.1
65.9
49.6
103.9 87.5
71.1
54.7
101.6 100.6 83.4
66.2
70.2
54.8
88.6
72.4
56.2
107.0 90.0
72.7
55.4
106.2 95.9
78.5
61.1
101.4 101.0 83.1
65.3
78.5
59.6
97.1
78.7
60.3
115.7 97.9
79.5
61.1
108.5 104.3 85.9
67.5
101.3 101.3 82.9
64.5
115°F
53.9
41.6
64.2
51.8
39.5
74.5
62.1
49.8
37.4
82.6
70.2
57.9
45.5
80.0
74.4
62.0
49.7
57.3
45.5
69.7
56.7
43.7
82.1
67.9
53.8
39.6
87.6
76.8
62.4
48.0
84.7
81.3
66.6
52.0
60.7
49.4
75.2
61.5
47.9
89.7
73.7
57.8
41.8
92.7
83.4
66.9
50.5
89.4
88.3
71.3
54.3
72.9
55.2
84.7
68.8
53.0
96.5
82.5
65.5
48.5
93.7
89.1
71.8
54.6
90.5
89.9
72.4
54.8
85.1
61.1
94.2
76.2
58.1
103.3 91.2
73.2
55.1
94.8
94.8
76.7
58.7
91.5
91.5
73.4
55.4
65
38.2
49.4
38.3
49.2
38.4
48.9
43.8
47.5
49.2
46.1
33.2
37.3
33.6
37.3
34.1
37.3
37.4
37.3
40.6
37.3
Johnson Controls Unitary Products
862075-XTG-G-0415
ZF120 (10 Ton) Imperial (Continued)
Air on
Evaporator Coil
CFM
3000
3500
4000
4550
5100
WB
(°F)
Total
Capacity1,2
(MBh)
Total
Input
(kW)3
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
118.0
102.1
86.2
80.0
77.7
124.8
108.1
91.4
84.7
82.3
131.6
114.1
96.7
89.5
86.9
132.7
115.5
98.2
90.5
87.8
133.9
116.8
99.6
91.5
88.8
12.34
12.21
12.09
11.98
11.96
12.67
12.53
12.39
12.30
12.27
13.11
12.95
12.79
12.71
12.69
13.69
13.52
13.36
13.29
13.26
14.16
14.00
13.83
13.76
13.74
Temperature of Air on Condenser Coil
Sensible Capacity (MBh)
Total
Total
Return Dry Bulb (°F)
Capacity1,2
Input
(MBh)
(kW)3
90
85
80
75
70
65
118.4°F
67.4
53.5
41.1
112.2
12.91
75.7
63.3
50.9
38.6
95.2
12.94
83.9
73.1
60.7
48.4
36.0
78.1
12.96
80.0
79.8
69.0
56.6
44.3
31.9
74.5
12.84
77.7
77.7
71.8
59.5
47.1
34.7
73.2
12.84
73.2
57.3
45.4
118.3
13.28
81.8
68.7
55.7
42.6
100.8
13.26
90.3
80.1
66.0
51.8
37.7
83.2
13.23
84.7
84.6
75.4
60.9
46.4
31.9
78.8
13.16
82.3
82.3
78.5
63.8
49.1
34.4
77.5
13.16
79.0
61.2
49.7
124.5
13.76
87.9
74.2
60.4
46.7
106.4
13.68
96.7
87.1
71.2
55.3
39.4
88.3
13.61
89.5
89.5
81.9
65.2
48.6
31.9
83.2
13.58
86.9
86.9
85.2
68.2
51.1
34.1
81.8
13.58
100.8 74.0
55.0
124.8
14.34
99.5
83.7
67.6
51.6
107.6
14.26
98.2
93.4
80.3
63.1
45.9
90.4
14.17
90.5
90.5
86.7
69.2
51.6
34.1
84.2
14.16
87.8
87.8
87.0
69.3
51.5
33.8
82.8
14.15
122.6 86.8
60.2
125.2
14.82
111.1 93.2
74.8
56.4
108.8
14.73
99.6
99.6
89.4
70.9
52.5
92.5
14.64
91.5
91.5
91.5
73.1
54.6
36.2
85.1
14.64
88.8
88.8
88.8
70.4
52.0
33.5
83.7
14.63
90
69.7
73.9
78.1
74.5
73.2
76.7
80.0
83.2
78.8
77.5
83.7
86.0
88.3
83.2
81.8
104.4
97.4
90.4
84.2
82.8
125.2
108.8
92.5
85.1
83.7
Sensible Capacity (MBh)
Return Dry Bulb (°F)
85
80
75
70
125°F
52.6
40.2
61.5
49.1
36.7
70.4
58.1
45.7
33.3
74.5
66.6
54.2
41.8
73.2
66.9
54.5
42.1
57.4
45.3
66.8
53.7
40.6
76.3
62.2
48.0
33.9
78.8
72.8
58.0
43.3
77.5
73.1
58.3
43.5
62.2
50.4
72.2
58.3
44.5
82.1
66.3
50.4
34.6
83.2
79.0
61.9
44.8
81.8
79.4
62.2
45.0
76.2
54.5
81.8
65.3
48.8
87.3
76.0
58.5
41.0
84.2
82.1
63.9
45.8
82.8
81.5
63.4
45.2
90.2
58.6
91.4
72.2
53.0
92.5
85.7
66.6
47.4
85.1
85.1
66.0
46.8
83.7
83.7
64.5
45.4
65
29.4
29.7
28.5
28.7
27.6
27.8
27.6
27.0
27.6
26.2
1. These capacities are gross ratings. For net capacity, deduct air blower motor, MBh = 3.415 x kW. Refer to the appropriate Blower
Performance Table for the kW of the supply air blower motor.
2. Capacity rating are based on 80 F (26.6 C) Entering Air Dry Bulb Temperature.
3. These ratings include the condenser fan motors, the compressor motors and supply air blower motor (External Static Pressure 0.30 IWG/
74.7 Pa).
Johnson Controls Unitary Products
21
862075-XTG-G-0415
ZF120 (35 kW) Metric
Air on
Evaporator Coil
3
m /s
1.42
1.65
1.89
2.15
2.41
1.42
1.65
1.89
2.15
2.41
22
WB
(°C)
Total
Capacity1,2
(kW)
Total
Input
(kW)3
32
25
22
19
17
14
25
22
19
17
14
25
22
19
17
14
25
22
19
17
14
25
22
19
17
14
35.3
33.7
32.1
30.4
28.0
37.6
35.9
34.2
32.3
29.8
39.8
38.0
36.2
34.2
31.5
39.5
37.7
36.0
34.0
31.3
39.2
37.5
35.7
33.8
31.1
8.40
8.47
8.54
8.56
8.56
8.64
8.71
8.78
8.80
8.80
8.97
9.04
9.11
9.14
9.14
9.53
9.60
9.67
9.69
9.69
9.98
10.05
10.12
10.15
10.14
20.0
24.5
29.1
30.4
28.0
20.6
26.5
32.3
32.3
29.8
21.2
28.4
35.6
34.2
31.5
27.0
31.4
35.7
34.0
31.3
32.9
34.3
35.7
33.8
31.1
25
22
19
17
14
25
22
19
17
14
25
22
19
17
14
25
22
19
17
14
25
22
19
17
14
35.4
31.9
28.4
26.3
25.0
37.6
33.8
30.1
27.9
26.5
39.7
35.8
31.8
29.5
28.0
39.9
35.9
31.9
29.7
28.1
40.1
36.1
32.1
29.8
28.2
10.83
10.72
10.60
10.55
10.52
11.12
11.01
10.89
10.84
10.81
11.51
11.40
11.28
11.22
11.20
12.08
11.96
11.85
11.79
11.76
12.54
12.43
12.32
12.26
12.23
19.6
23.1
26.7
26.3
25.0
20.8
25.0
29.1
27.9
26.5
22.0
26.8
31.6
29.5
28.0
28.3
30.1
31.9
29.7
28.1
34.7
33.4
32.1
29.8
28.2
Temperature of Air on Condenser Coil
Sensible Capacity (kW)
Total
Total
Return Dry Bulb (°C)
Capacity1
Input
(kW)
(kW)2
29
27
24
21
18
29°C
16.4
12.8
35.4
9.61
20.9
17.3
13.7
32.8
9.59
25.5
21.9
18.3
14.7
30.2
9.57
26.3
22.7
19.1
15.5
11.9
28.4
9.56
28.0
27.1
23.5
19.9
16.3
26.5
9.54
17.3
13.8
37.6
9.88
22.6
18.7
14.8
34.8
9.86
27.8
23.6
19.4
15.2
32.1
9.83
29.2
24.5
20.3
16.1
11.9
30.1
9.82
29.8
29.2
24.8
20.5
16.2
28.1
9.80
18.3
14.7
39.8
10.24
24.2
20.0
15.8
36.9
10.22
30.1
25.3
20.5
15.7
34.0
10.20
32.1
26.3
21.5
16.7
11.9
31.9
10.18
31.5
31.3
26.2
21.1
16.0
29.8
10.17
20.2
16.0
39.7
10.80
26.5
21.7
16.9
36.8
10.78
32.9
27.5
22.4
17.2
33.9
10.76
33.0
29.1
24.0
18.9
13.8
31.8
10.74
31.3
31.2
26.0
20.7
15.4
29.7
10.73
22.1
17.2
39.7
11.26
28.9
23.5
18.0
36.8
11.24
35.7
29.7
24.2
18.8
33.9
11.22
33.8
32.0
26.5
21.1
15.7
31.8
11.20
31.1
31.1
25.7
20.2
14.8
29.7
11.19
41°C
16.0
12.4
35.5
12.04
19.5
15.9
12.3
31.0
11.84
23.0
19.4
15.8
12.2
26.5
11.64
24.9
21.3
17.7
14.1
10.5
24.3
11.54
25.0
23.6
19.9
16.3
12.7
23.4
11.50
17.0
13.5
37.6
12.36
21.1
17.3
13.5
32.8
12.16
25.3
21.1
17.0
12.8
28.0
11.95
26.9
23.2
19.0
14.7
10.5
25.7
11.85
26.5
25.6
21.3
17.0
12.7
24.8
11.81
18.0
14.6
39.6
12.78
22.8
18.7
14.6
34.6
12.57
27.6
22.8
18.1
13.4
29.6
12.37
28.8
25.0
20.2
15.4
10.6
27.2
12.27
28.0
27.7
22.7
17.6
12.6
26.2
12.23
21.0
16.1
40.1
13.35
25.4
20.7
16.0
35.0
13.15
29.8
25.3
20.2
15.2
29.9
12.94
29.3
27.1
22.0
17.0
11.9
27.5
12.84
28.1
28.0
22.8
17.6
12.4
26.5
12.80
24.0
17.7
40.6
13.82
28.0
22.7
17.4
35.4
13.62
32.1
27.7
22.4
17.0
30.3
13.41
29.8
29.2
23.8
18.5
13.2
27.8
13.31
28.2
28.2
22.9
17.6
12.2
26.8
13.27
32
19.8
23.8
27.9
28.4
26.5
20.7
25.7
30.7
30.1
28.1
21.6
27.6
33.6
31.9
29.8
27.7
30.7
33.8
31.8
29.7
33.8
33.8
33.9
31.8
29.7
19.4
22.4
25.4
24.3
23.4
21.0
24.2
27.5
25.7
24.8
22.5
26.0
29.6
27.2
26.2
29.0
29.5
29.9
27.5
26.5
35.5
32.9
30.3
27.8
26.8
Sensible Capacity (kW)
Return Dry Bulb (°C)
29
27
24
21
35°C
16.2
12.6
20.2
16.6
13.0
24.3
20.7
17.0
13.4
25.6
22.0
18.4
14.8
26.5
25.3
21.7
18.1
17.2
13.6
21.9
18.0
14.1
26.6
22.4
18.2
14.0
28.0
23.8
19.6
15.4
28.1
27.4
23.1
18.7
18.1
14.7
23.5
19.4
15.2
28.8
24.1
19.3
14.5
30.5
25.7
20.8
16.0
29.8
29.5
24.4
19.4
20.6
16.1
26.0
21.2
16.5
31.4
26.4
21.3
16.2
31.1
28.1
23.0
17.9
29.7
29.6
24.4
19.1
23.0
17.5
28.5
23.1
17.7
33.9
28.7
23.3
17.9
31.8
30.6
25.2
19.8
29.7
29.7
24.3
18.9
46°C
15.8
12.2
18.8
15.2
11.6
21.8
18.2
14.6
11.0
24.2
20.6
17.0
13.3
23.4
21.8
18.2
14.6
16.8
13.3
20.4
16.6
12.8
24.1
19.9
15.8
11.6
25.7
22.5
18.3
14.1
24.8
23.8
19.5
15.2
17.8
14.5
22.0
18.0
14.0
26.3
21.6
16.9
12.3
27.2
24.4
19.6
14.8
26.2
25.9
20.9
15.9
21.4
16.2
24.8
20.2
15.5
28.3
24.2
19.2
14.2
27.5
26.1
21.1
16.0
26.5
26.3
21.2
16.1
24.9
17.9
27.6
22.3
17.0
30.3
26.7
21.4
16.2
27.8
27.8
22.5
17.2
26.8
26.8
21.5
16.2
18
11.2
14.5
11.2
14.4
11.2
14.3
12.8
13.9
14.4
13.5
9.7
10.9
9.9
10.9
10.0
10.9
11.0
10.9
11.9
10.9
Johnson Controls Unitary Products
862075-XTG-G-0415
ZF120 (35 kW) Metric (Continued)
Air on
Evaporator Coil
m3/s
1.42
1.65
1.89
2.15
2.41
WB
(°C)
Total
Capacity1,2
(kW)
Total
Input
(kW)3
32
25
22
19
17
14
25
22
19
17
14
25
22
19
17
14
25
22
19
17
14
25
22
19
17
14
34.6
29.9
25.3
23.5
22.8
36.6
31.7
26.8
24.8
24.1
38.6
33.5
28.3
26.2
25.5
38.9
33.8
28.8
26.5
25.7
39.2
34.2
29.2
26.8
26.0
12.34
12.21
12.09
11.98
11.96
12.67
12.53
12.39
12.30
12.27
13.11
12.95
12.79
12.71
12.69
13.69
13.52
13.36
13.29
13.26
14.16
14.00
13.83
13.76
13.74
19.8
22.2
24.6
23.5
22.8
21.5
24.0
26.5
24.8
24.1
23.2
25.8
28.3
26.2
25.5
29.5
29.2
28.8
26.5
25.7
35.9
32.6
29.2
26.8
26.0
Temperature of Air on Condenser Coil
Sensible Capacity (kW)
Total
Total
Return Dry Bulb (°C)
Capacity1
Input
(kW)
(kW)2
29
27
24
21
18
48°C
15.7
12.1
32.9
12.91
18.5
14.9
11.3
27.9
12.94
21.4
17.8
14.2
10.5
22.9
12.96
23.4
20.2
16.6
13.0
9.3
21.8
12.84
22.8
21.0
17.4
13.8
10.2
21.5
12.84
16.8
13.3
34.7
13.28
20.1
16.3
12.5
29.5
13.26
23.5
19.3
15.2
11.0
24.4
13.23
24.8
22.1
17.9
13.6
9.3
23.1
13.16
24.1
23.0
18.7
14.4
10.1
22.7
13.16
17.9
14.6
36.5
13.76
21.7
17.7
13.7
31.2
13.68
25.5
20.9
16.2
11.5
25.9
13.61
26.2
24.0
19.1
14.2
9.4
24.4
13.58
25.5
25.0
20.0
15.0
10.0
24.0
13.58
21.7
16.1
36.6
14.34
24.5
19.8
15.1
31.5
14.26
27.4
23.5
18.5
13.5
26.5
14.17
26.5
25.4
20.3
15.1
10.0
24.7
14.16
25.7
25.5
20.3
15.1
9.9
24.3
14.15
25.5
17.7
36.7
14.82
27.3
21.9
16.5
31.9
14.73
29.2
26.2
20.8
15.4
27.1
14.64
26.8
26.8
21.4
16.0
10.6
25.0
14.64
26.0
26.0
20.6
15.2
9.8
24.5
14.63
32
20.4
21.7
22.9
21.8
21.5
22.5
23.4
24.4
23.1
22.7
24.5
25.2
25.9
24.4
24.0
30.6
28.5
26.5
24.7
24.3
36.7
31.9
27.1
25.0
24.5
Sensible Capacity (kW)
Return Dry Bulb (°C)
29
27
24
21
52°C
15.4
11.8
18.0
14.4
10.8
20.6
17.0
13.4
9.8
21.8
19.5
15.9
12.3
21.5
19.6
16.0
12.3
16.8
13.3
19.6
15.7
11.9
22.4
18.2
14.1
9.9
23.1
21.3
17.0
12.7
22.7
21.4
17.1
12.8
18.2
14.8
21.1
17.1
13.0
24.1
19.4
14.8
10.1
24.4
23.2
18.1
13.1
24.0
23.3
18.2
13.2
22.3
16.0
24.0
19.1
14.3
25.6
22.3
17.1
12.0
24.7
24.1
18.7
13.4
24.3
23.9
18.6
13.2
26.4
17.2
26.8
21.2
15.5
27.1
25.1
19.5
13.9
25.0
25.0
19.3
13.7
24.5
24.5
18.9
13.3
18
8.6
8.7
8.4
8.4
8.1
8.1
8.1
7.9
8.1
7.7
1. These capacities are gross ratings. For net capacity, deduct air blower motor, MBh = 3.415 x kW. Refer to the appropriate Blower
Performance Table for the kW of the supply air blower motor.
2. Capacity rating are based on 80 F (26.6 C) Entering Air Dry Bulb Temperature.
3. These ratings include the condenser fan motors, the compressor motors and supply air blower motor (External Static Pressure 0.30 IWG/
74.7 Pa).
Johnson Controls Unitary Products
23
862075-XTG-G-0415
ZF150 (12.5 Ton) Imperial
Air on
Evaporator Coil
CFM
3750
4375
5000
5575
6150
3750
4375
5000
5575
6150
24
WB
(°F)
Total
Capacity1,2
(MBh)
Total
Input
(kW)3
90
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
185.6
168.8
151.9
146.1
141.4
190.5
173.2
155.9
149.9
145.1
195.4
177.6
159.9
153.8
148.8
200.8
182.6
164.3
158.0
152.9
206.2
187.5
168.8
162.3
157.0
11.34
11.18
11.02
10.96
10.92
11.63
11.47
11.31
11.25
11.21
11.89
11.73
11.57
11.51
11.47
12.68
12.52
12.36
12.30
12.26
13.46
13.30
13.14
13.08
13.04
82.4
104.3
126.3
145.6
141.4
85.8
112.8
139.8
149.7
145.1
89.2
121.3
153.4
153.8
148.8
93.4
127.2
161.0
158.0
152.9
97.6
133.1
168.6
162.3
157.0
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
155.6
142.6
129.5
122.3
120.6
160.3
146.9
133.4
126.0
124.2
165.0
151.1
137.3
129.7
127.8
167.9
153.8
139.8
132.0
130.1
170.9
156.5
142.2
134.3
132.4
13.79
13.67
13.56
13.49
13.48
14.08
13.96
13.84
13.78
13.76
14.34
14.22
14.10
14.04
14.03
15.11
14.99
14.87
14.81
14.80
15.87
15.75
15.63
15.57
15.56
76.4
96.8
117.3
122.2
120.6
81.9
104.0
126.2
125.9
124.2
87.3
111.2
135.1
129.7
127.8
98.2
118.4
138.6
132.0
130.1
109.2
125.6
142.1
134.3
132.4
Temperature of Air on Condenser Coil
Sensible Capacity (MBh)
Total
Total
Return Dry Bulb (°F)
Capacity1,2
Input
(MBh)
(kW)3
85
80
75
70
65
85°F
66.9
51.4
170.6
12.56
88.8
73.3
57.8
155.7
12.43
110.8 95.2
79.7
64.2
140.7
12.29
122.7 106.4 90.9
75.4
59.8
134.2
12.23
133.8 116.3 100.8 85.3
69.8
131.0
12.20
71.6
55.5
175.4
12.85
96.0
79.2
62.4
160.0
12.71
120.4 102.9 85.4
67.8
144.7
12.57
136.9 115.0 96.9
78.9
60.9
138.0
12.51
141.3 125.7 107.3 88.9
70.4
134.6
12.48
76.3
59.6
180.2
13.12
103.2 85.1
67.0
164.4
12.98
130.1 110.6 91.0
71.5
148.6
12.84
151.0 123.5 103.0 82.5
61.9
141.7
12.78
148.8 135.1 113.8 92.4
71.1
138.3
12.75
80.3
60.9
184.3
13.90
107.0 86.9
66.7
168.2
13.76
133.8 112.9 92.0
71.1
152.0
13.62
156.7 126.7 105.3 83.9
62.5
145.0
13.55
152.9 139.2 117.4 95.6
73.8
141.5
13.53
84.3
62.1
188.5
14.67
110.9 88.6
66.4
172.0
14.53
137.4 115.1 92.9
70.6
155.5
14.39
162.3 129.8 107.5 85.3
63.1
148.3
14.32
157.0 143.3 121.1 98.8
76.6
144.7
14.30
105°F
61.4
46.4
140.6
15.02
81.8
66.8
51.8
129.5
14.92
102.3 87.3
72.3
57.3
118.3
14.83
114.6 100.4 85.4
70.4
55.4
110.5
14.76
118.0 104.9 89.9
74.9
59.9
110.2
14.76
65.0
50.0
145.2
15.30
88.0
72.0
56.0
133.7
15.20
111.1 94.0
77.0
60.0
122.2
15.11
121.7 108.1 90.6
73.2
55.7
114.1
15.04
122.9 113.0 95.2
77.4
59.6
113.8
15.04
68.6
53.5
149.8
15.56
94.2
77.1
60.1
137.9
15.47
119.8 100.8 81.7
62.7
126.0
15.37
128.8 115.8 95.9
76.0
56.1
117.7
15.30
127.8 121.1 100.5 79.9
59.3
117.3
15.30
73.7
55.6
151.5
16.32
99.3
80.1
60.9
139.5
16.23
124.8 104.6 84.5
64.3
127.5
16.13
131.6 119.7 99.1
78.5
57.9
119.0
16.06
130.1 124.5 103.5 82.6
61.6
118.7
16.06
78.9
57.6
153.2
17.07
104.4 83.1
61.8
141.1
16.98
129.8 108.5 87.2
65.9
128.9
16.88
134.3 123.5 102.2 80.9
59.6
120.4
16.81
132.4 127.8 106.5 85.2
63.9
120.0
16.82
90
79.4
100.6
121.8
133.9
131.0
83.8
108.4
133.0
137.8
134.6
88.3
116.3
144.3
141.7
138.3
95.8
122.8
149.8
145.0
141.5
103.4
129.4
155.3
148.3
144.7
73.4
93.1
112.8
110.5
110.2
79.9
99.6
119.4
114.1
113.8
86.4
106.2
126.0
117.7
117.3
100.6
114.1
127.5
119.0
118.7
114.9
121.9
128.9
120.4
120.0
Sensible Capacity (MBh)
Return Dry Bulb (°F)
85
80
75
70
95°F
64.1
48.9
85.3
70.1
54.8
106.5 91.3
76.0
60.7
118.6 103.4 88.1
72.9
125.9 110.6 95.4
80.1
68.3
52.7
92.0
75.6
59.2
115.8 98.5
81.2
63.9
129.3 111.5 93.8
76.0
132.1 119.4 101.3 83.2
72.4
56.6
98.7
81.1
63.5
125.0 105.7 86.4
67.1
139.9 119.7 99.5
79.2
138.3 128.1 107.1 86.2
77.0
58.2
103.2 83.5
63.8
129.3 108.7 88.2
67.7
144.1 123.2 102.2 81.2
141.5 131.8 110.5 89.1
81.6
59.9
107.6 85.8
64.1
133.6 111.8 90.0
68.3
148.3 126.6 104.9 83.1
144.7 135.6 113.8 92.0
115°F
58.6
43.9
78.4
63.6
48.9
98.1
83.3
68.6
53.8
110.5 97.4
82.6
67.9
110.2 99.2
84.5
69.8
61.7
47.2
84.0
68.4
52.8
106.4 89.6
72.8
56.1
114.1 104.7 87.5
70.3
113.8 106.7 89.2
71.7
64.7
50.5
89.7
73.2
56.7
114.7 95.9
77.1
58.3
117.7 112.0 92.4
72.8
117.3 114.2 93.9
73.7
70.5
52.9
95.4
76.7
58.1
120.3 100.5 80.7
60.9
119.0 116.2 96.0
75.8
118.7 117.1 96.6
76.0
76.2
55.4
101.1 80.3
59.5
126.0 105.2 84.4
63.6
120.4 120.4 99.5
78.7
120.0 120.0 99.2
78.4
65
57.6
64.9
58.3
65.0
59.0
65.2
60.2
67.7
61.3
70.3
53.1
55.0
53.2
54.2
53.2
53.5
55.6
55.5
57.9
57.6
Johnson Controls Unitary Products
862075-XTG-G-0415
ZF150 (12.5 Ton) Imperial (Continued)
Air on
Evaporator Coil
CFM
3750
4375
5000
5575
6150
WB
(°F)
Total
Capacity1,2
(MBh)
Total
Input
(kW)3
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
136.5
125.7
115.0
104.8
104.5
140.9
129.8
118.7
108.2
107.9
145.4
133.9
122.4
111.7
111.3
146.6
135.5
124.3
112.9
112.6
147.9
137.0
126.1
114.2
113.9
15.57
15.43
15.28
15.16
15.16
15.85
15.71
15.58
15.45
15.45
16.10
15.97
15.85
15.71
15.71
16.85
16.74
16.62
16.47
16.47
17.59
17.49
17.38
17.22
17.22
Temperature of Air on Condenser Coil
Sensible Capacity (MBh)
Total
Total
Return Dry Bulb (°F)
Capacity1,2
Input
(MBh)
(kW)3
90
85
80
75
70
65
118.4°F
71.2
56.3
41.4
128.4
16.65
91.0
76.1
61.3
46.4
118.5
16.41
110.9 96.0
81.1
66.2
51.3
108.5
16.17
104.8 104.8 96.2
81.3
66.4
51.5
93.9
15.95
104.5 104.5 97.3
82.4
67.5
52.6
93.6
15.95
78.2
59.1
44.5
132.6
16.91
97.4
81.6
65.9
50.1
122.3
16.70
116.7 104.2 87.2
70.2
53.2
112.0
16.48
108.2 108.2 104.1 86.7
69.2
51.8
96.9
16.23
107.9 107.9 105.8 88.1
70.5
52.8
96.6
16.23
85.2
62.0
47.7
136.9
17.15
103.8 87.2
70.5
53.8
126.2
16.96
122.4 112.3 93.3
74.2
55.2
115.5
16.77
111.7 111.7 112.1 92.1
72.0
52.0
100.0
16.50
111.3 111.3 114.3 93.9
73.4
53.0
99.7
16.49
99.5
68.2
50.4
137.2
17.88
111.9 92.9
73.9
54.9
127.6
17.72
124.3 117.6 97.4
77.3
57.1
118.1
17.57
112.9 112.9 113.2 92.5
71.8
51.2
101.1
17.26
112.6 112.6 114.1 93.2
72.4
51.5
100.8
17.26
113.7 74.4
53.1
137.5
18.60
119.9 98.6
77.3
56.0
129.1
18.48
126.1 122.9 101.6 80.3
59.0
120.7
18.35
114.2 114.2 114.2 92.9
71.6
50.3
102.3
18.01
113.9 113.9 113.9 92.6
71.3
50.0
102.0
18.01
90
67.0
87.0
107.1
93.9
93.6
75.0
93.1
111.3
96.9
96.6
83.0
99.2
115.5
100.0
99.7
97.2
107.6
118.1
101.1
100.8
111.4
116.0
120.7
102.3
102.0
Sensible Capacity (MBh)
Return Dry Bulb (°F)
85
80
75
70
125°F
51.9
36.7
71.9
56.7
41.5
91.9
76.7
61.5
46.4
93.9
93.9
78.7
63.5
93.6
93.6
78.4
63.2
54.3
39.4
77.1
61.0
44.9
99.9
82.5
65.1
47.8
96.9 103.1 85.1
67.0
96.6 104.1 86.1
68.1
56.6
42.2
82.2
65.2
48.2
107.8 88.3
68.7
49.2
100.0 112.3 91.4
70.5
99.7 114.6 93.7
72.9
63.7
45.4
88.0
68.4
48.8
112.3 91.4
70.5
49.6
101.1 107.3 85.7
64.2
100.8 108.3 86.7
65.2
70.8
48.6
93.8
71.6
49.3
116.8 94.6
72.3
50.1
102.3 102.3 80.0
57.8
102.0 102.0 79.7
57.5
65
48.3
48.1
49.0
50.0
49.7
52.0
42.6
43.6
35.6
35.2
1. These capacities are gross ratings. For net capacity, deduct air blower motor, MBh = 3.415 x kW. Refer to the appropriate Blower
Performance Table for the kW of the supply air blower motor.
2. Capacity rating are based on 80 F (26.6 C) Entering Air Dry Bulb Temperature.
3. These ratings include the condenser fan motors, the compressor motors and supply air blower motor (External Static Pressure 0.35 IWG/
87.1 Pa).
Johnson Controls Unitary Products
25
862075-XTG-G-0415
ZF150 (44 kW) Metric
Air on
Evaporator Coil
3
m /s
1.77
2.06
2.36
2.63
2.90
1.77
2.06
2.36
2.63
2.90
26
WB
(°C)
Total
Capacity1,2
(kW)
Total
Input
(kW)3
32
25
22
19
17
14
25
22
19
17
14
25
22
19
17
14
25
22
19
17
14
25
22
19
17
14
54.4
49.5
44.5
42.8
41.4
55.8
50.8
45.7
43.9
42.5
57.3
52.1
46.9
45.1
43.6
58.8
53.5
48.2
46.3
44.8
60.4
54.9
49.5
47.6
46.0
11.34
11.18
11.02
10.96
10.92
11.63
11.47
11.31
11.25
11.21
11.89
11.73
11.57
11.51
11.47
12.68
12.52
12.36
12.30
12.26
13.46
13.30
13.14
13.08
13.04
24.1
30.6
37.0
42.7
41.4
25.2
33.1
41.0
43.9
42.5
26.2
35.6
45.0
45.1
43.6
27.4
37.3
47.2
46.3
44.8
28.6
39.0
49.4
47.6
46.0
25
22
19
17
14
25
22
19
17
14
25
22
19
17
14
25
22
19
17
14
25
22
19
17
14
45.6
41.8
38.0
35.9
35.3
47.0
43.0
39.1
36.9
36.4
48.4
44.3
40.2
38.0
37.5
49.2
45.1
41.0
38.7
38.1
50.1
45.9
41.7
39.4
38.8
11.34
11.18
11.02
10.96
10.92
11.63
11.47
11.31
11.25
11.21
11.89
11.73
11.57
11.51
11.47
12.68
12.52
12.36
12.30
12.26
13.46
13.30
13.14
13.08
13.04
22.4
28.4
34.4
35.8
35.3
24.0
30.5
37.0
36.9
36.4
25.6
32.6
39.6
38.0
37.5
28.8
34.7
40.6
38.7
38.1
32.0
36.8
41.7
39.4
38.8
Temperature of Air on Condenser Coil
Sensible Capacity (kW)
Total
Total
Return Dry Bulb (°C)
Capacity1,2
Input
(kW)
(kW)3
29
27
24
21
18
29°C
19.6
15.1
50.0
12.56
26.0
21.5
16.9
45.6
12.43
32.5
27.9
23.4
18.8
41.2
12.29
36.0
31.2
26.6
22.1
17.5
39.3
12.23
39.2
34.1
29.6
25.0
20.5
38.4
12.20
21.0
16.3
51.4
12.85
28.1
23.2
18.3
46.9
12.71
35.3
30.2
25.0
19.9
42.4
12.57
40.1
33.7
28.4
23.1
17.8
40.4
12.51
41.4
36.8
31.4
26.0
20.6
39.5
12.48
22.4
17.5
52.8
13.12
30.2
24.9
19.6
48.2
12.98
38.1
32.4
26.7
20.9
43.6
12.84
44.3
36.2
30.2
24.2
18.1
41.5
12.78
43.6
39.6
33.3
27.1
20.8
40.5
12.75
23.5
17.8
54.0
13.90
31.4
25.5
19.5
49.3
13.76
39.2
33.1
27.0
20.8
44.6
13.62
45.9
37.1
30.9
24.6
18.3
42.5
13.55
44.8
40.8
34.4
28.0
21.6
41.5
13.53
24.7
18.2
55.2
14.67
32.5
26.0
19.5
50.4
14.53
40.3
33.7
27.2
20.7
45.6
14.39
47.6
38.0
31.5
25.0
18.5
43.5
14.32
46.0
42.0
35.5
29.0
22.4
42.4
14.30
41°C
18.0
13.6
41.2
15.02
24.0
19.6
15.2
37.9
14.92
30.0
25.6
21.2
16.8
34.7
14.83
33.6
29.4
25.0
20.6
16.2
32.4
14.76
34.6
30.8
26.4
22.0
17.6
32.3
14.76
19.0
14.6
42.6
15.30
25.8
21.1
16.4
39.2
15.20
32.5
27.6
22.6
17.6
35.8
15.11
35.7
31.7
26.6
21.5
16.3
33.4
15.04
36.0
33.1
27.9
22.7
17.5
33.3
15.04
20.1
15.7
43.9
15.56
27.6
22.6
17.6
40.4
15.47
35.1
29.5
24.0
18.4
36.9
15.37
37.7
34.0
28.1
22.3
16.4
34.5
15.30
37.5
35.5
29.5
23.4
17.4
34.4
15.30
21.6
16.3
44.4
16.32
29.1
23.5
17.9
40.9
16.23
36.6
30.7
24.8
18.8
37.4
16.13
38.6
35.1
29.0
23.0
17.0
34.9
16.06
38.1
36.5
30.3
24.2
18.1
34.8
16.06
23.1
16.9
44.9
17.07
30.6
24.3
18.1
41.3
16.98
38.0
31.8
25.6
19.3
37.8
16.88
39.4
36.2
30.0
23.7
17.5
35.3
16.81
38.8
37.5
31.2
25.0
18.7
35.2
16.82
32
23.3
29.5
35.7
39.2
38.4
24.6
31.8
39.0
40.4
39.5
25.9
34.1
42.3
41.5
40.5
28.1
36.0
43.9
42.5
41.5
30.3
37.9
45.5
43.5
42.4
21.5
27.3
33.1
32.4
32.3
23.4
29.2
35.0
33.4
33.3
25.3
31.1
36.9
34.5
34.4
29.5
33.4
37.4
34.9
34.8
33.7
35.7
37.8
35.3
35.2
Sensible Capacity (kW)
Return Dry Bulb (°C)
29
27
24
21
35°C
18.8
14.3
25.0
20.5
16.1
31.2
26.7
22.3
17.8
34.8
30.3
25.8
21.4
36.9
32.4
28.0
23.5
20.0
15.5
27.0
22.2
17.3
33.9
28.9
23.8
18.7
37.9
32.7
27.5
22.3
38.7
35.0
29.7
24.4
21.2
16.6
28.9
23.8
18.6
36.6
31.0
25.3
19.7
41.0
35.1
29.2
23.2
40.5
37.5
31.4
25.3
22.6
17.1
30.2
24.5
18.7
37.9
31.9
25.9
19.8
42.2
36.1
29.9
23.8
41.5
38.6
32.4
26.1
23.9
17.5
31.5
25.2
18.8
39.2
32.8
26.4
20.0
43.5
37.1
30.7
24.4
42.4
39.7
33.3
27.0
46°C
17.2
12.9
23.0
18.6
14.3
28.7
24.4
20.1
15.8
32.4
28.5
24.2
19.9
32.3
29.1
24.8
20.4
18.1
13.8
24.6
20.0
15.5
31.2
26.3
21.3
16.4
33.4
30.7
25.6
20.6
33.3
31.3
26.1
21.0
19.0
14.8
26.3
21.4
16.6
33.6
28.1
22.6
17.1
34.5
32.8
27.1
21.3
34.4
33.5
27.5
21.6
20.6
15.5
28.0
22.5
17.0
35.3
29.5
23.7
17.9
34.9
34.0
28.1
22.2
34.8
34.3
28.3
22.3
22.3
16.2
29.6
23.5
17.4
36.9
30.8
24.7
18.6
35.3
35.3
29.2
23.1
35.2
35.2
29.1
23.0
18
16.9
19.0
17.1
19.1
17.3
19.1
17.6
19.9
18.0
20.6
15.6
16.1
15.6
15.9
15.6
15.7
16.3
16.3
17.0
16.9
Johnson Controls Unitary Products
862075-XTG-G-0415
ZF150 (44 kW) Metric (Continued)
Air on
Evaporator Coil
m3/s
1.77
2.06
2.36
2.63
2.90
WB
(°C)
Total
Capacity1,2
(kW)
Total
Input
(kW)3
32
25
22
19
17
14
25
22
19
17
14
25
22
19
17
14
25
22
19
17
14
25
22
19
17
14
40.0
36.8
33.7
30.7
30.6
41.3
38.0
34.8
31.7
31.6
42.6
39.2
35.9
32.7
32.6
43.0
39.7
36.4
33.1
33.0
43.3
40.1
37.0
33.5
33.4
15.57
15.43
15.28
15.16
15.16
15.85
15.71
15.58
15.45
15.45
16.10
15.97
15.85
15.71
15.71
16.85
16.74
16.62
16.47
16.47
17.59
17.49
17.38
17.22
17.22
20.9
26.7
32.5
30.7
30.6
22.9
28.6
34.2
31.7
31.6
25.0
30.4
35.9
32.7
32.6
29.2
32.8
36.4
33.1
33.0
33.3
35.1
37.0
33.5
33.4
Temperature of Air on Condenser Coil
Sensible Capacity (kW)
Total
Total
Return Dry Bulb (°C)
Capacity1,2
Input
(kW)
(kW)3
29
27
24
21
18
48°C
16.5
12.1
37.6
16.65
22.3
18.0
13.6
34.7
16.41
28.1
23.8
19.4
15.0
31.8
16.17
30.7
28.2
23.8
19.5
15.1
27.5
15.95
30.6
28.5
24.2
19.8
15.4
27.4
15.95
17.3
13.1
38.9
16.91
23.9
19.3
14.7
35.9
16.70
30.5
25.6
20.6
15.6
32.8
16.48
31.7
30.5
25.4
20.3
15.2
28.4
16.23
31.6
31.0
25.8
20.7
15.5
28.3
16.23
18.2
14.0
40.1
17.15
25.5
20.7
15.8
37.0
16.96
32.9
27.3
21.8
16.2
33.9
16.77
32.7
32.9
27.0
21.1
15.2
29.3
16.50
32.6
33.5
27.5
21.5
15.5
29.2
16.49
20.0
14.8
40.2
17.88
27.2
21.7
16.1
37.4
17.72
34.5
28.6
22.6
16.7
34.6
17.57
33.1
33.2
27.1
21.1
15.0
29.6
17.26
33.0
33.4
27.3
21.2
15.1
29.5
17.26
21.8
15.6
40.3
18.60
28.9
22.7
16.4
37.8
18.48
36.0
29.8
23.5
17.3
35.4
18.35
33.5
33.5
27.2
21.0
14.7
30.0
18.01
33.4
33.4
27.1
20.9
14.7
29.9
18.01
32
19.6
25.5
31.4
27.5
27.4
22.0
27.3
32.6
28.4
28.3
24.3
29.1
33.9
29.3
29.2
28.5
31.5
34.6
29.6
29.5
32.6
34.0
35.4
30.0
29.9
Sensible Capacity (kW)
Return Dry Bulb (°C)
29
27
24
21
52°C
15.2
10.8
21.1
16.6
12.2
26.9
22.5
18.0
13.6
27.5
27.5
23.1
18.6
27.4
27.4
23.0
18.5
15.9
11.6
22.6
17.9
13.2
29.3
24.2
19.1
14.0
28.4
30.2
24.9
19.6
28.3
30.5
25.2
19.9
16.6
12.4
24.1
19.1
14.1
31.6
25.9
20.1
14.4
29.3
32.9
26.8
20.7
29.2
33.6
27.5
21.4
18.7
13.3
25.8
20.0
14.3
32.9
26.8
20.7
14.5
29.6
31.4
25.1
18.8
29.5
31.7
25.4
19.1
20.7
14.2
27.5
21.0
14.5
34.2
27.7
21.2
14.7
30.0
30.0
23.5
16.9
29.9
29.9
23.4
16.8
18
14.2
14.1
14.4
14.7
14.6
15.2
12.5
12.8
10.4
10.3
1. These capacities are gross ratings. For net capacity, deduct air blower motor, MBh = 3.415 x kW. Refer to the appropriate Blower
Performance Table for the kW of the supply air blower motor.
2. Capacity rating are based on 80 F (26.6 C) Entering Air Dry Bulb Temperature.
3. These ratings include the condenser fan motors, the compressor motors and supply air blower motor (External Static Pressure 0.35 IWG/
87.1 Pa).
Johnson Controls Unitary Products
27
862075-XTG-G-0415
Airflow Performance
ZF090-150 Side Duct Application
ZF090 (7.5 Ton) Standard Motor Side Duct Imperial
Turns Open
ESP
(iwg)
0
CFM
Watts
1
BHP
CFM
Watts
2
BHP
CFM
Watts
3
BHP
CFM
Watts
4
BHP
CFM
Watts
5
BHP
CFM
Watts
BHP
0.2
–
–
–
–
–
–
–
–
–
–
–
–
3193
1490
1.60
2981
1310
1.41
0.4
3690
2230
2.39
3468
1950
2.09
3294
1750
1.88
3105
1550
1.66
2922
1370
1.47
2694
1210
1.30
0.6
3478
2110
2.26
3239
1830
1.96
3044
1640
1.76
2850
1440
1.54
2651
1270
1.36
2423
1120
1.20
0.8
3243
1980
2.12
3001
1720
1.85
2790
1520
1.63
2576
1330
1.43
2370
1170
1.26
2105
1020
1.09
1.0
3006
1830
1.96
2758
1580
1.70
2544
1400
1.50
2303
1230
1.32
2017
1050
1.13
1624
880
0.94
1.2
2758
1720
1.85
2533
1510
1.62
2230
1290
1.38
1891
1080
1.16
–
–
–
–
–
–
1.4
2447
1570
1.68
2182
1350
1.45
1769
1110
1.19
–
–
–
–
–
–
–
–
–
1.6
2085
1410
1.51
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
ZF090 (26 kW) Standard Motor Side Duct Metric
Turns Open
ESP
(Pa)
0
1
2
3
4
5
m3/s
In
Out
m3/s
In
Out
m3/s
In
Out
m3/s
In
Out
m3/s
In
Out
m3/s
In
Out
50
–
–
–
–
–
–
–
–
–
–
–
–
1.51
1.49
1.19
1.36
1.31
1.05
100
1.74
2.23
1.78
1.64
1.95
1.55
1.55
1.75
1.40
1.46
1.55
1.24
1.38
1.37
1.10
1.27
1.21
0.97
149
1.64
2.11
1.68
1.53
1.83
1.46
1.44
1.64
1.39
1.34
1.44
1.15
1.25
1.27
1.01
1.14
1.12
0.89
199
1.53
1.98
1.58
1.42
1.72
1.38
1.32
1.52
1.38
1.22
1.33
1.07
1.12
1.17
0.94
0.99
1.02
0.81
249
1.42
1.83
1.46
1.30
1.58
1.27
1.20
1.40
1.28
1.09
1.23
0.98
0.95
1.05
0.84
0.77
0.88
0.70
299
1.30
1.72
1.38
1.20
1.51
1.21
1.05
1.29
1.17
0.89
1.08
0.91
–
–
–
–
–
–
349
1.15
1.57
1.25
1.03
1.35
1.08
0.83
1.11
1.01
–
–
–
–
–
–
–
–
–
399
0.98
1.41
1.26
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
ZF090 (7.5) Ton Optional Motor Side Duct Imperial
Turns Open
ESP
(iwg)
0
1
2
3
4
5
CFM
Watts
BHP
CFM
Watts
BHP
CFM
Watts
BHP
CFM
Watts
BHP
CFM
Watts
BHP
CFM
Watts
BHP
0.25
–
–
–
–
–
–
–
–
–
–
–
–
3650
1800
1.95
3290
1560
1.68
0.5
–
–
–
–
–
–
–
–
–
–
–
–
3250
1650
1.78
2930
1430
1.53
0.8
–
–
–
–
–
–
–
–
–
–
–
–
2783
1500
1.61
2507
1300
1.39
1
3555
2440
2.62
3285
2120
2.27
3047
1860
2.00
2778
1590
1.71
2507
1390
1.49
2209
1180
1.27
1.2
3320
2310
2.48
3034
1990
2.13
2799
1730
1.86
2510
1480
1.59
2213
1260
1.35
1846
1050
1.13
1.4
3101
2160
2.32
2796
1860
2.00
2466
1590
1.71
2188
1330
1.43
1721
1090
1.17
–
–
–
1.6
2864
2040
2.19
2489
1710
1.83
2145
1450
1.56
–
–
–
–
–
–
–
–
–
1.8
2524
1860
2.00
2182
1550
1.66
–
–
–
–
–
–
–
–
–
–
–
–
28
Johnson Controls Unitary Products
862075-XTG-G-0415
ZF090 (7.5) Ton Optional Motor Side Duct Imperial
Turns Open
ESP
(iwg)
2
0
1
2
3
4
5
CFM
Watts
BHP
CFM
Watts
BHP
CFM
Watts
BHP
CFM
Watts
BHP
CFM
Watts
BHP
CFM
Watts
BHP
2189
1680
1.80
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
Johnson Controls Unitary Products
29
862075-XTG-G-0415
ZF090 (26 kW) Optional Motor Side Duct Metric
Turns Open
ESP
(Pa)
0
1
2
3
4
5
m3/s
In
(kW)
Out
(kW)
m3/s
In
(kW)
Out
(kW)
m3/s
In
(kW)
Out
(kW)
m3/s
In
(kW)
Out
(kW)
m3/s
In
(kW)
Out
(kW)
m3/s
In
(kW)
Out
(kW)
62
–
–
–
–
–
–
–
–
–
–
–
–
1.72
1.8
1.46
1.55
1.56
1.25
125
–
–
–
–
–
–
–
–
–
–
–
–
1.53
1.65
1.33
1.38
1.43
1.14
199
–
–
–
–
–
–
–
–
–
–
–
–
1.31
1.5
1.20
1.18
1.3
1.04
249
1.68
2.44
1.95
1.55
2.12
1.70
1.44
1.86
1.49
1.31
1.59
1.27
1.18
1.39
1.11
1.04
1.18
0.94
299
1.52
2.31
1.85
1.43
1.99
1.59
1.32
1.73
1.38
1.18
1.48
1.18
1.04
1.26
1.01
0.87
1.05
0.84
349
1.46
2.16
1.73
1.31
1.86
1.49
1.16
1.59
1.27
1.03
1.33
1.06
0.81
1.09
0.87
–
–
–
399
1.35
2.04
1.63
1.17
1.71
1.36
1.01
1.45
1.16
–
–
–
–
–
–
–
–
–
448
1.19
1.86
1.49
1.03
1.55
1.24
–
–
–
–
–
–
–
–
–
–
–
–
498
1.03
1.68
1.34
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
ZF120 (10 Ton) Standard Motor Side Duct Imperial
Turns Open
ESP
(iwg)
0
1
2
3
4
5
CFM
Watts
BHP
CFM
Watts
BHP
CFM
Watts
BHP
CFM
Watts
BHP
CFM
Watts
BHP
CFM
Watts
BHP
0.35
4820
2675
2.87
4582
2362
2.53
4319
2080
2.23
4086
1842
1.98
3863
1648
1.77
3590
1430
1.53
0.6
4522
2496
2.68
4307
2215
2.38
4025
1941
2.08
3713
1678
1.80
3464
1499
1.61
3149
1291
1.38
0.8
4223
2332
2.50
3973
2062
2.21
3656
1783
1.91
3363
1550
1.66
3026
1350
1.45
-
-
-
1.0
3913
2174
2.33
3679
1923
2.06
3262
1619
1.74
2721
1330
1.43
-
-
-
-
-
-
1.2
3521
1978
2.12
3104
1693
1.82
-
-
-
-
-
-
-
-
-
-
-
-
1.4
2790
1660
1.78
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
ZF120 (35 kW) Standard Motor Side Duct Metric
Turns Open
ESP
(Pa)
0
1
2
3
4
5
m3/s
In
(kW)
Out
(kW)
m3/s
In
(kW)
Out
(kW)
m3/s
In
(kW)
Out
(kW)
m3/s
In
(kW)
Out
(kW)
m3/s
In
(kW)
Out
(kW)
m3/s
In
(kW)
Out
(kW)
87
2.27
2.68
2.14
2.16
2.36
1.89
2.04
2.08
1.66
1.93
1.84
1.47
1.82
1.65
1.32
1.69
1.43
1.14
149
2.13
2.50
2.00
2.03
2.22
1.77
1.90
1.94
1.55
1.75
1.68
1.34
1.63
1.50
1.20
1.49
1.29
1.03
199
1.99
2.33
1.87
1.88
2.06
1.65
1.73
1.78
1.43
1.59
1.55
1.24
1.43
1.35
1.08
-
-
-
249
1.85
2.17
1.74
1.74
1.92
1.54
1.54
1.62
1.30
1.28
1.33
1.06
-
-
-
-
-
-
299
1.66
1.98
1.58
1.46
1.69
1.35
-
-
-
-
-
-
-
-
-
-
-
-
349
1.32
1.66
1.33
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
30
Johnson Controls Unitary Products
862075-XTG-G-0415
ZF120 (10 Ton) Optional Motor Side Duct Imperial
Turns Open
ESP
(iwg)
0
1
2
3
4
5
CFM
Watts
BHP
CFM
Watts
BHP
CFM
Watts
BHP
CFM
Watts
BHP
CFM
Watts
BHP
CFM
Watts
BHP
0.35
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
5100
2495
2.68
0.6
-
-
-
-
-
-
-
-
-
-
-
-
5091
2745
2.94
4646
2314
2.48
0.8
-
-
-
-
-
-
-
-
-
5078
2937
3.15
4839
2584
2.77
4347
2153
2.31
1.0
-
-
-
-
-
-
5075
3117
3.34
4767
2730
2.93
4487
2377
2.55
3946
1942
2.08
1.2
-
-
-
5068
3308
3.55
4742
2881
3.09
4427
2513
2.69
4108
2159
2.32
3501
1723
1.85
1.4
5079
3595
3.86
4787
3105
3.33
4452
2713
2.91
4012
2259
2.42
3665
1926
2.07
-
-
-
1.6
4739
3316
3.56
4482
2892
3.10
4098
2474
2.65
3543
2006
2.15
3057
1642
1.76
-
-
-
1.8
4461
3111
3.34
4070
2621
2.81
3552
2160
2.32
-
-
-
-
-
-
-
-
-
2.0
3997
2782
2.98
3400
2219
2.38
-
-
-
-
-
-
-
-
-
-
-
-
2.2
3496
2480
2.66
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
ZF120 (35 kW) Optional Motor Side Duct Metric
Turns Open
ESP
(Pa)
0
1
2
3
4
5
m3/s
In
(kW)
Out
(kW)
m3/s
In
(kW)
Out
(kW)
m3/s
In
(kW)
Out
(kW)
m3/s
In
(kW)
Out
(kW)
m3/s
In
(kW)
Out
(kW)
m3/s
In
(kW)
Out
(kW)
87
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
2.4
2.50
2.00
149
-
-
-
-
-
-
-
-
-
-
-
-
2.40
2.75
2.20
2.19
2.31
1.85
199
-
-
-
-
-
-
-
-
-
2.40
2.94
2.35
2.28
2.58
2.07
2.05
2.15
1.72
249
-
-
-
-
-
-
2.40
3.12
2.49
2.25
2.73
2.18
2.12
2.38
1.90
1.86
1.94
1.55
299
-
-
-
2.39
3.31
2.65
2.24
2.88
2.30
2.09
2.51
2.01
1.94
2.16
1.73
1.65
1.72
1.38
349
2.40
3.60
2.88
2.26
3.11
2.48
2.10
2.71
2.17
1.89
2.26
1.81
1.73
1.93
1.54
-
-
-
399
2.24
3.32
2.65
2.12
2.89
2.31
1.93
2.47
1.98
1.67
2.01
1.60
1.44
1.64
1.31
-
-
-
448
2.11
3.11
2.49
1.92
2.62
2.10
1.68
2.16
1.73
-
-
-
-
-
-
-
-
-
498
1.89
2.78
2.23
1.60
2.22
1.78
-
-
-
-
-
-
-
-
-
-
-
-
548
1.65
2.48
1.98
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
Johnson Controls Unitary Products
31
862075-XTG-G-0415
ZF150 (12.5 Ton) Side Duct Imperial
Turns Open
ESP
(iwg)
0
1
2
3
4
5
CFM
Watts
BHP
CFM
Watts
BHP
CFM
Watts
BHP
CFM
Watts
BHP
CFM
Watts
BHP
CFM
Watts
BHP
0.35
-
-
-
6150
4171
4.47
5915
3774
4.05
5610
3309
3.55
5396
2948
3.16
4960
2495
2.68
0.6
-
-
-
5850
3932
4.22
5648
3565
3.82
5363
3136
3.36
5091
2745
2.94
4646
2314
2.48
0.8
5870
4273
4.58
5567
3715
3.98
5406
3380
3.62
5078
2937
3.15
4839
2584
2.77
4347
2153
2.31
1.0
5652
4087
4.38
5327
3518
3.77
5075
3117
3.34
4767
2730
2.93
4487
2377
2.55
3946
1942
2.08
1.2
5350
3820
4.10
5068
3308
3.55
4742
2881
3.09
4427
2513
2.69
4108
2159
2.32
-
-
-
1.4
5079
3595
3.86
4787
3105
3.33
4452
2713
2.91
4012
2259
2.42
3665
1926
2.07
-
-
-
1.6
4739
3316
3.56
4482
2892
3.10
4098
2474
2.65
-
-
-
-
-
-
-
-
-
1.8
4461
3111
3.34
4070
2621
2.81
-
-
-
-
-
-
-
-
-
-
-
-
2.0
3997
2782
2.98
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
ZF150 (44 kW) Side Duct Metric
Turns Open
ESP
(Pa)
0
1
2
3
4
5
m3/s
In
(kW)
Out
(kW)
m3/s
In
(kW)
Out
(kW)
m3/s
In
(kW)
Out
(kW)
m3/s
In
(kW)
Out
(kW)
m3/s
In
(kW)
Out
(kW)
m3/s
In
(kW)
Out
(kW)
87
-
-
-
2.90
4.17
3.34
2.79
3.77
3.02
2.65
3.31
2.65
2.55
2.95
2.36
2.34
2.50
2.00
149
-
-
-
2.76
3.93
3.15
2.67
3.57
2.85
2.53
3.14
2.51
2.40
2.75
2.20
2.19
2.31
1.85
199
2.77
4.27
3.42
2.63
3.72
2.97
2.55
3.38
2.70
2.40
2.94
2.35
2.28
2.58
2.07
2.05
2.15
1.72
249
2.67
4.09
3.27
2.51
3.52
2.81
2.40
3.12
2.49
2.25
2.73
2.18
2.12
2.38
1.90
1.86
1.94
1.55
299
2.52
3.82
3.06
2.39
3.31
2.65
2.24
2.88
2.30
2.09
2.51
2.01
1.94
2.16
1.73
-
-
-
349
2.40
3.60
2.88
2.26
3.11
2.48
2.10
2.71
2.17
1.89
2.26
1.81
1.73
1.93
1.54
-
-
-
399
2.24
3.32
2.65
2.12
2.89
2.31
1.93
2.47
1.98
-
-
-
-
-
-
-
-
-
448
2.11
3.11
2.49
1.92
2.62
2.10
-
-
-
-
-
-
-
-
-
-
-
498
1.89
2.78
2.23
-
-
-
-
-
-
-
-
-
-
-
-
-
-
32
-
Johnson Controls Unitary Products
862075-XTG-G-0415
ZF090-150 Bottom Duct Application
ZF090 (7.5 Ton) Standard Motor Bottom Duct Imperial
Turns Open
ESP
(iwg)
0
1
2
3
4
5
CFM
Watts
BHP
CFM
Watts
BHP
CFM
Watts
BHP
CFM
Watts
BHP
CFM
Watts
BHP
CFM
Watts
BHP
0.2
3478
2110
2.26
3239
1830
1.96
3044
1640
1.76
2850
1440
1.54
2651
1270
1.36
2423
1120
1.20
0.4
3243
1980
2.12
3001
1720
1.85
2790
1520
1.63
2576
1330
1.43
2370
1170
1.26
2105
1020
1.09
0.6
3006
1830
1.96
2758
1580
1.70
2544
1400
1.50
2303
1230
1.32
2017
1050
1.13
1624
880
0.94
0.8
2758
1720
1.85
2533
1510
1.62
2230
1290
1.38
1891
1080
1.16
–
–
–
–
–
–
1.0
2447
1570
1.68
2182
1350
1.45
1769
1110
1.19
–
–
–
–
–
–
–
–
–
1.2
2085
1410
1.51
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
ZF090 (26 kW) Standard Motor Bottom Duct Metric
Turns Open
ESP
(Pa)
0
1
2
3
4
5
m3/s
In
(kW)
Out
(kW)
m3/s
In
(kW)
Out
(kW)
m3/s
In
(kW)
Out
(kW)
m3/s
In
(kW)
Out
(kW)
m3/s
In
(kW)
Out
(kW)
m3/s
In
(kW)
Out
(kW)
50
1.64
2.11
1.68
1.53
1.83
1.46
1.44
1.64
1.39
1.34
1.44
1.15
1.25
1.27
1.01
1.14
1.12
0.89
100
1.53
1.98
1.58
1.42
1.72
1.38
1.32
1.52
1.38
1.22
1.33
1.07
1.12
1.17
0.94
0.99
1.02
0.81
149
1.42
1.83
1.46
1.30
1.58
1.27
1.20
1.40
1.28
1.09
1.23
0.98
0.95
1.05
0.84
0.77
0.88
0.70
199
1.30
1.72
1.38
1.20
1.51
1.21
1.05
1.29
1.17
0.89
1.08
0.91
–
–
–
–
–
–
249
1.15
1.57
1.25
1.03
1.35
1.08
0.83
1.11
1.01
–
–
–
–
–
–
–
–
–
299
0.98
1.41
1.26
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
ZF090 (7.5 Ton) Optional Motor Bottom Duct Imperial
Turns Open
ESP
(iwg)
0
1
2
3
4
5
CFM
Watts
BHP
CFM
Watts
BHP
CFM
Watts
BHP
CFM
Watts
BHP
CFM
Watts
BHP
CFM
Watts
BHP
0.4
–
–
–
–
–
–
–
–
–
–
–
–
2783
1500
1.61
2507
1300
1.39
0.6
–
–
–
3285
2120
2.27
3047
1860
2.00
2778
1590
1.71
2507
1390
1.49
2209
1180
1.27
0.8
–
–
–
3034
1990
2.13
2799
1730
1.86
2510
1480
1.59
2213
1260
1.35
1846
1050
1.13
1.0
3101
2160
2.32
2796
1860
2.00
2466
1590
1.71
2188
1330
1.43
1721
1090
1.17
–
–
–
1.2
2864
2040
2.19
2489
1710
1.83
2145
1450
1.56
–
–
–
–
–
–
–
–
–
1.4
2524
1860
2.00
2182
1550
1.66
–
–
–
–
–
–
–
–
–
–
–
–
1.6
2189
1680
1.80
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
Johnson Controls Unitary Products
33
862075-XTG-G-0415
ZF090 (26 kW) Optional Motor Bottom Duct Metric
Turns Open
ESP
(Pa)
0
1
2
3
4
5
m3/s
In
(kW)
Out
(kW)
m3/s
In
(kW)
Out
(kW)
m3/s
In
(kW)
Out
(kW)
m3/s
In
(kW)
Out
(kW)
m3/s
In
(kW)
Out
(kW)
m3/s
In
(kW)
Out
(kW)
100
–
–
–
–
–
–
–
–
–
–
–
–
1.31
1.5
1.20
1.18
1.3
1.04
149
1.67
2.44
1.95
1.55
2.12
1.70
1.44
1.86
1.49
1.31
1.59
1.27
1.18
1.39
1.11
1.04
1.18
0.94
199
1.57
2.31
1.85
1.43
1.99
1.59
1.32
1.73
1.38
1.18
1.48
1.18
1.04
1.26
1.01
0.87
1.05
0.84
249
1.46
2.16
1.73
1.31
1.86
1.49
1.16
1.59
1.27
1.03
1.33
1.06
0.81
1.09
0.87
–
–
–
299
1.35
2.04
1.63
1.17
1.71
1.36
1.01
1.45
1.16
–
–
–
–
–
–
–
–
–
349
1.19
1.86
1.49
1.03
1.55
1.24
–
–
–
–
–
–
–
–
–
–
–
–
399
1.03
1.68
1.34
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
ZF120 (10 Ton) Standard Motor Bottom Duct Imperial
Turns Open
ESP
(iwg)
0
1
2
3
4
5
CFM
Watts
BHP
CFM
Watts
BHP
CFM
Watts
BHP
CFM
Watts
BHP
CFM
Watts
BHP
CFM
Watts
BHP
0.2
4543
2511
2.69
4362
2250
2.41
4139
1996
2.14
3911
1766
1.89
3719
1594
1.71
3518
1407
1.51
0.4
4311
2381
2.55
4115
2127
2.28
3862
1871
2.01
3611
1644
1.76
3386
1471
1.58
3153
1293
1.39
0.6
4032
2232
2.39
3804
1982
2.13
3508
1720
1.84
3246
1506
1.61
2971
1332
1.43
-
-
-
0.8
3706
2068
2.22
3428
1818
1.95
3078
1548
1.66
-
-
-
-
-
-
-
-
-
1.0
3333
1892
2.03
2989
1644
1.76
-
-
-
-
-
-
-
-
-
-
-
-
1.2
2914
1711
1.83
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
ZF120 (35 kW) Standard Motor Bottom Duct Metric
Turns Open
ESP
(Pa)
0
1
2
3
4
5
m3/s
In
(kW)
Out
(kW)
m3/s
In
(kW)
Out
(kW)
m3/s
In
(kW)
Out
(kW)
m3/s
In
(kW)
Out
(kW)
m3/s
In
(kW)
Out
(kW)
m3/s
In
(kW)
Out
(kW)
50
2.14
2.51
2.01
2.06
2.25
1.80
1.95
2.00
1.60
1.85
1.77
1.41
1.75
1.59
1.27
1.66
1.41
1.13
100
2.03
2.38
1.91
1.94
2.13
1.70
1.82
1.87
1.50
1.70
1.64
1.31
1.60
1.47
1.18
1.49
1.29
1.03
149
1.90
2.23
1.79
1.80
1.98
1.59
1.66
1.72
1.38
1.53
1.51
1.20
1.40
1.33
1.07
-
-
-
199
1.75
2.07
1.65
1.62
1.82
1.45
1.45
1.55
1.24
-
-
-
-
-
-
-
-
-
249
1.57
1.89
1.51
1.41
1.64
1.32
-
-
-
-
-
-
-
-
-
-
-
-
299
1.38
1.71
1.37
-
-
-
-
-
-
-
-
-
-
-
-
-
-
34
Johnson Controls Unitary Products
862075-XTG-G-0415
ZF120 (10 Ton) Optional Motor Bottom Duct Imperial
Turns Open
ESP
(iwg)
0
1
2
3
4
5
CFM
Watts
BHP
CFM
Watts
BHP
CFM
Watts
BHP
CFM
Watts
BHP
CFM
Watts
BHP
CFM
Watts
BHP
0.2
-
-
-
-
-
-
-
-
-
-
-
-
4966
2666
2.86
4605
2290
2.46
0.4
-
-
-
-
-
-
-
-
-
4919
2473
2.65
4721
2515
2.70
4344
2145
2.30
0.6
-
-
-
-
-
-
4929
3022
3.24
4665
2324
2.49
4450
2353
2.52
4048
1991
2.13
0.8
-
-
-
4908
3197
3.43
4668
2841
3.05
4391
2171
2.33
4151
2183
2.34
3717
1829
1.96
1.0
4915
3456
3.71
4651
3013
3.23
4388
2656
2.85
4096
2015
2.16
3825
2008
2.15
3352
1664
1.78
1.2
4653
3253
3.49
4377
2823
3.03
4089
2467
2.65
3779
1858
1.99
3471
1830
1.96
2951
1499
1.61
1.4
4372
3046
3.27
4087
2631
2.82
3771
2277
2.44
3442
1703
1.83
3090
1652
1.77
-
-
-
1.6
4070
2837
3.04
3780
2437
2.61
3434
2089
2.24
3084
1552
1.66
-
-
-
-
-
-
1.8
3748
2629
2.82
3455
2243
2.41
3078
1904
2.04
-
-
-
-
-
-
-
-
-
2.0
3406
2425
2.60
3114
2051
2.20
-
-
-
-
-
-
-
-
-
-
-
-
2.2
3044
2228
2.39
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
ZF120 (35 kW) Optional Motor Bottom Duct Metric
Turns Open
ESP
(Pa)
0
1
2
3
4
5
m3/s
In
(kW)
Out
(kW)
m3/s
In
(kW)
Out
(kW)
m3/s
In
(kW)
Out
(kW)
m3/s
In
(kW)
Out
(kW)
m3/s
In
(kW)
Out
(kW)
m3/s
In
(kW)
Out
(kW)
50
-
-
-
-
-
-
-
-
-
-
-
-
2.34
2.67
2.13
2.17
2.29
1.83
100
-
-
-
-
-
-
-
-
-
2.32
2.47
1.98
2.23
2.51
2.01
2.05
2.15
1.72
149
-
-
-
-
-
-
2.33
3.02
2.42
2.20
2.32
1.86
2.10
2.35
1.88
1.91
1.99
1.59
199
-
-
-
2.32
3.20
2.56
2.20
2.84
2.27
2.07
2.17
1.74
1.96
2.18
1.75
1.75
1.83
1.46
249
2.32
3.46
2.76
2.20
3.01
2.41
2.07
2.66
2.12
1.93
2.01
1.61
1.81
2.01
1.61
1.58
1.66
1.33
299
2.20
3.25
2.60
2.07
2.82
2.26
1.93
2.47
1.97
1.78
1.86
1.49
1.64
1.83
1.46
1.39
1.50
1.20
349
2.06
3.05
2.44
1.93
2.63
2.10
1.78
2.28
1.82
1.62
1.70
1.36
1.46
1.65
1.32
-
-
-
399
1.92
2.84
2.27
1.78
2.44
1.95
1.62
2.09
1.67
1.46
1.55
1.24
-
-
-
-
-
-
448
1.77
2.63
2.10
1.63
2.24
1.79
1.45
1.90
1.52
-
-
-
-
-
-
-
-
-
498
1.61
2.43
1.94
1.47
2.05
1.64
-
-
-
-
-
-
-
-
-
-
-
-
548
1.44
2.23
1.78
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
Johnson Controls Unitary Products
35
862075-XTG-G-0415
ZF150 (12.5 Ton) Bottom Duct Imperial
Turns Open
ESP
(iwg)
0
1
2
3
4
5
CFM
Watts
BHP
CFM
Watts
BHP
CFM
Watts
BHP
CFM
Watts
BHP
CFM
Watts
BHP
CFM
Watts
BHP
0.35
5576
4015
4.32
5370
3547
3.80
5171
3197
3.43
5007
2884
3.09
4721
2515
2.70
4344
2145
2.30
0.6
5376
3839
4.12
5147
3376
3.62
4929
3022
3.24
4735
2704
2.90
4450
2353
2.52
4048
1991
2.13
0.8
5155
3652
3.92
4908
3197
3.43
4668
2841
3.05
4411
2501
2.68
4151
2183
2.34
3717
1829
1.96
1.0
4915
3456
3.71
4651
3013
3.23
4388
2656
2.85
4035
2281
2.45
3825
2008
2.15
-
-
-
1.2
4653
3253
3.49
4377
2823
3.03
4089
2467
2.65
3608
2051
2.20
-
-
-
-
-
-
1.4
4372
3046
3.27
4087
3621
2.82
3771
2277
2.44
-
-
-
-
-
-
-
-
-
1.6
4070
2837
3.04
3780
2437
2.61
-
-
-
-
-
-
-
-
-
-
-
-
1.8
3748
2629
2.82
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
ZF150 (44 kW) Bottom Duct Metric
Turns Open
ESP
(Pa)
0
1
2
3
4
5
m3/s
In
(kW)
Out
(kW)
m3/s
In
(kW)
Out
(kW)
m3/s
In
(kW)
Out
(kW)
m3/s
In
(kW)
Out
(kW)
m3/s
In
(kW)
Out
(kW)
m3/s
In
(kW)
Out
(kW)
87
2.63
4.01
3.21
2.53
3.55
2.84
2.44
3.20
2.56
2.36
2.88
2.31
2.23
2.51
2.01
2.05
2.15
1.72
149
2.54
3.84
3.07
2.43
3.38
2.70
2.33
3.02
2.42
2.23
2.70
2.16
2.10
2.35
1.88
1.91
1.99
1.59
199
2.43
3.65
2.92
2.32
3.20
2.56
2.20
2.84
2.27
2.08
2.50
2.00
1.96
2.18
1.75
1.75
1.83
1.46
249
2.32
3.46
2.76
2.20
3.01
2.41
2.07
2.66
2.12
1.90
2.28
1.83
1.81
2.01
1.61
-
-
-
299
2.20
3.25
2.60
2.07
2.82
2.26
1.93
2.47
1.97
1.70
2.05
1.64
-
-
-
-
-
-
349
2.06
3.05
2.44
1.93
2.63
2.10
1.78
2.28
1.82
-
-
-
-
-
-
-
-
-
399
1.92
2.84
2.27
1.78
2.44
1.95
-
-
-
-
-
-
-
-
-
-
-
-
448
1.77
2.63
2.10
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
NOTES FOR TABLES ON PAGES 30 THROUGH 37:
•
•
“Turns Open” refers to the setting of the variable pitch
motor sheave, where “0 Turns Open” is fully closed.
Blower performance includes dry coil and 2” (51mm) throwaway filters.
•
Blower performance for gas heat includes the maximum
number of heat tubes available for each tonnage.
•
ESP (External Static Pressure) given is that available for
the supply and return air duct system. All internal resistances have been deducted from the total static pressure of
the blower.
Rated Airflow Imperial
36
Model
CFM
ESP (iwg)
ZF090
3650
0.2
ZF120
5000
0.3
ZF150
6250
0.3
Johnson Controls Unitary Products
862075-XTG-G-0415
Additional Static Resistance ZF120/150 Cabinet (IMPERIAL)
CFM
Cooling Only1
Economizer2 3
1900
0.06
2100
0.07
2300
0.08
2500
2700
Electric Heat KW2
18
24
36
54
0.02
0.06
0.07
0.08
0.10
0.02
0.07
0.08
0.09
0.11
0.02
0.08
0.09
0.10
0.13
0.09
0.02
0.09
0.10
0.11
0.14
0.11
0.03
0.10
0.12
0.13
0.16
2900
0.12
0.03
0.11
0.13
0.14
0.18
3100
0.14
0.03
0.13
0.15
0.16
0.20
3300
0.16
0.03
0.14
0.17
0.18
0.22
3500
0.18
0.04
0.16
0.19
0.20
0.24
3700
0.20
0.04
0.18
0.21
0.22
0.26
3900
0.23
0.04
0.20
0.23
0.24
0.28
4100
0.25
0.04
0.22
0.25
0.26
0.31
4300
0.28
0.05
0.24
0.28
0.29
0.34
4500
0.30
0.05
0.26
0.30
0.31
0.37
4700
0.33
0.05
0.29
0.33
0.34
0.40
4900
0.36
0.05
0.31
0.35
0.37
0.43
5100
0.39
0.06
0.34
0.38
0.40
0.46
5300
0.42
0.06
0.37
0.41
0.43
0.49
5500
0.45
0.06
0.40
0.44
0.46
0.53
5700
0.48
0.06
0.43
0.47
0.49
0.56
5900
0.52
0.07
0.46
0.50
0.53
0.59
6100
0.56
0.07
0.49
0.53
0.56
0.62
6300
0.60
0.07
0.53
0.56
0.59
0.65
1. Add these resistance values to the available static resistance in the respective Blower Performance Tables.
2. Deduct these resistance values from the available external static pressure shown in the respective Blower Performance Table.
3. The pressure drop through the economizer is greater for 100% outdoor air than for 100% return air. If the resistance of
the return air duct system is less than 0.25 IWG, the unit will deliver less CFM during full economizer operation.
Additional Static Resistance ZF090 Cabinet (Imperial)
CFM
Cooling Only1
Economizer2 3
1900
-0.004
0.07
2100
0.01
0.09
2300
0.01
0.11
2500
0.02
0.13
2700
0.03
0.16
2900
0.04
0.18
3100
0.05
0.20
3300
0.06
0.22
3500
0.07
0.24
3700
0.08
0.27
3900
0.09
0.29
4100
0.09
0.31
4300
0.10
0.33
1. Add these resistance values to the available static resistance in the respective Blower
Performance Tables.
2. Deduct these resistance values from the available external static pressure shown in the
respective Blower Performance Table.
3. The pressure drop through the economizer is greater for 100% outdoor air than for 100%
return air. If the resistance of the return air duct system is less than 0.25 IWG, the unit will
deliver less CFM during full economizer operation.
Johnson Controls Unitary Products
37
862075-XTG-G-0415
Additional Static Resistance ZF120/150 Cabinet (Metric)
M3S
Cooling Only1
Electric Heat kW2
Economizer2 3
18
24
36
54
0.89
14.9
5.0
14.9
17.4
19.9
24.8
0.99
17.4
5.0
17.4
19.9
22.4
27.3
1.08
19.9
5.0
19.9
22.4
24.8
32.3
1.18
22.4
5.0
22.4
24.8
27.3
34.8
1.27
27.3
7.5
24.8
29.8
32.3
39.7
1.36
29.8
7.5
27.3
32.3
34.8
44.7
1.46
34.8
7.5
32.3
37.3
39.7
49.7
1.55
39.7
7.5
34.8
42.2
44.7
54.6
1.65
44.7
9.9
39.7
47.2
49.7
59.6
1.74
49.7
9.9
44.7
52.2
49.7
64.6
1.83
57.1
9.9
49.7
57.1
59.6
69.5
1.93
62.1
9.9
54.6
62.1
64.6
77.0
1.02
69.5
12.4
59.6
69.5
72.0
84.4
2.12
74.5
12.4
64.6
74.5
77.0
91.9
2.21
82.0
12.4
72.0
82.0
84.4
99.3
2.30
89.4
12.4
77.0
86.9
91.9
106.8
2.40
96.9
14.9
84.4
94.4
99.3
114.2
2.49
104.3
14.9
91.9
101.8
106.8
121.7
2.59
111.8
14.9
99.3
109.3
114.2
131.6
2.68
119.2
14.9
106.8
116.7
121.7
139.1
2.77
129.1
17.4
114.2
124.2
131.6
146.5
2.87
139.1
17.4
121.7
131.6
139.1
154.0
2.96
149.0
17.4
131.6
139.1
146.5
161.4
1. Add these resistance values to the available static resistance in the respective Blower Performance Tables.
2. Deduct these resistance values from the available external static pressure shown in the respective Blower Performance Table.
3. The pressure drop through the economizer is greater for 100% outdoor air than for 100% return air. If the resistance of
the return air duct system is less than 62.1 Pa, the unit will deliver less M3S during full economizer operation.
Additional Static Resistance ZF090 Cabinet (Metric)
M3S
Cooling Only1
Economizer2 3
0.9
-0.99
17.40
0.99
2.50
22.40
1.09
2.50
27.40
1.18
4.98
32.40
1.27
7.50
39.90
1.37
10.00
44.83
1.46
12.50
49.81
1.56
14.90
54.80
1.65
17.40
59.80
1.75
19.90
67.20
1.84
22.40
72.20
1.93
22.40
77.20
2.03
24.90
82.20
1. Add these resistance values to the available static resistance in the respective Blower
Performance Tables.
2. Deduct these resistance values from the available external static pressure shown in
the respective Blower Performance Table.
3. The pressure drop through the economizer is greater for 100% outdoor air than for
100% return air. If the resistance of the return air duct system is less than 62.1 Pa, the
unit will deliver less M3S during full economizer operation.
38
Johnson Controls Unitary Products
862075-XTG-G-0415
Gas Heat Minimum Supply Air Imperial
Size
(Ton)
090
(7.5)
ZF
120
(10)
ZF
150
(12.5)
Supply Air (CFM)
Heat
Size
Model
ZF
Cooling
Heating
Min
Max
Min
Max
10
2250
3750
2250
3750
15
2250
3750
2250
3750
15
3000
5000
3000
5000
20
3000
5000
3000
5000
15
3750
6250
3750
6250
20
3750
6250
3750
6250
Gas Heat Minimum Supply Air Metric
Size
(KW)
090
(26)
ZF
120
(35)
ZF
150
(44)
Supply Air (M3S)
Heat
Size
Model
ZF
Cooling
Heating
Min
Max
Min
Max
10
1.06
1.76
1.06
1.76
15
1.06
1.76
1.06
1.76
15
1.42
2.36
1.42
2.36
20
1.42
2.36
1.42
2.36
15
1.76
2.95
1.76
2.95
20
1.76
2.95
1.76
2.95
Electric Heat Minimum Supply Air Imperial
Minimum Supply Air (CFM)
Size
(Tons)
Model
120
(10)
ZF
150
(12.5)
ZF
Voltage
Heater kW
18
24
36
54
380/415-3-50
3000
3000
3000
3500
380/415-3-50
3750
3750
3750
3750
Electric Heat Minimum Supply Air Metric
Minimum Supply Air (C3S)
Size
(KW)
Model
120
(35)
ZF
150
(44)
ZF
Voltage
Heater kW
18
24
36
54
380/415-3-50
1.42
1.42
1.42
1.42
380/415-3-50
1.76
1.76
1.76
1.76
Indoor Blower Specifications
Motor
Size
(Tons)
Model
90
(7.5)
ZF
120
(10)
150
(12.5)
HP
RPM
1
Eff.
SF
Frame
2
2
2
4
1425
1425
1425
1455
0.8
0.8
0.8
0.87
1.15
1.15
1.15
1.15
56
56
56
184T
4
1455
0.87
1.15
184T
ZF
ZF
Motor Sheave
Datum Dia.
Bore (In.)
(In.)
3.4 - 4.4
7/8
3.4 - 4.4
7/8
3.4 - 4.4
7/8
4.0 - 5.0
1-1/8
4.3 - 5.3
1-1/8
Model
1VM50
1VM50
1VM50
1VP56
1VP56
Blower Sheave
Datum Dia.
Bore (In.)
(In.)
5.5
1
5
1
7
1
6.2
1
6.6
1
Model
Belt
AK59
AK54
AK74
AK66
A49
A47
A54
A56
BK72
BX56
1. 1725 RPM at 60 Hz.
Johnson Controls Unitary Products
39
862075-XTG-G-0415
Power Exhaust Specifications
Model
Voltage
2PE04703246
460-1-60
HP
3/4
Motor
RPM1
1075
QTY
1
Motor
FLA
2.2
LRA
3.4
CFM @
0.1 ESP
3800
Fuse Size
MCA
2.8
5
1. Motors are multi-tapped and factory wired for high speed, suitable for 50 HZ power supply
Sound Performance
Indoor Sound Power Levels
Size
(Tons)
090
(7.5)
120
(10)
150
(12.5)
Model
CFM
ESP
(IWG)
Blower
RPM
BHP
Rating1
Sound
dB (A)
63
Sound Power, dB (10-12) Watts
Octave Band Centerline Frequency (Hz)
125
250
500
1000
2000
4000
8000
ZF
3000
0.6
854
1.47
77
74
76
76
74
72
68
68
63
ZF
4000
0.6
959
2.29
83
80
82
82
80
78
74
74
69
ZF
5000
0.6
1132
3.74
87
84
86
86
84
82
78
78
73
1. These values have been accessed using a model of sound propagation from a point source into the hemispheric/free field. The dBA values
provided are to be used for reference only. Calculation of dBA values cover matters of system design and the fan manufacture has no way
of knowing the details of each system. This constitutes an exception to any specification or guarantee requiring a dBA value of sound data
in any other form than sound power level ratings.
40
Johnson Controls Unitary Products
862075-XTG-G-0415
Electrical Data
ZF090-120 Standard Motor
Size
(Tons)
ZF090
Volt
OD Fan Supply Pwr
Compressors (each) Motors Blower Exh
(each) Motor Motor
Electric Heat Option
MCA1
(Amps)
Max Fuse2/
MCA1 w/ Max Fuse2/
Breaker3
3
Pwr Exh
Breaker
Size w/ Pwr
(Amps) Size (Amps)
Exh (Amps)
RLA
LRA
MCC
FLA
FLA
FLA
Model
KW
Stages
Amps
380
6.2
52.0
9.7
1.6
4.3
2.2
None
-
-
-
21.5
23.7
25
25
415
6.2
52.0
9.7
1.6
4.3
2.2
None
-
-
-
21.5
23.7
25
25
380
8.0
67.1
12.5
1.6
4.3
2.2
ZF120
415
8.0
67.1
12.5
1.6
4.3
2.2
None
-
-
-
25.5
27.7
30
35
2TP04521850
11.3
2
17.2
26.8
29.6
30
35
2TP04522450
15.0
2
22.8
33.9
36.6
35
40
2TP04523650
21.3
2
32.4
45.8
48.6
50
50
2TP04525450
33.8
2
51.4
69.6
72.3
70
80
None
-
-
-
25.5
27.7
30
35
2TP04521850
13.5
2
18.8
28.9
31.6
30
35
2TP04522450
17.9
2
24.9
36.5
39.3
40
40
2TP04523650
25.4
2
35.3
49.5
52.3
50
60
2TP04525450
40.4
2
56.2
75.6
78.4
80
80
1. Minimum Circuit Ampacity.
2. Maximum Over current Protection per Standard UL 1995.
3. Fuse or HACR circuit breaker size installed at factory or field installed.
ZF090-150 Hi Static Motor
Size
(Tons)
ZF090
Compressors (each)
Volt
OD Fan Supply
Pwr Exh
Motors Blower
Motor
(each) Motor
Electric Heat Option
MCA1
(Amps)
Max
Max Fuse2/
MCA1 w/ Fuse2/
Breaker3 Size
3
Pwr Exh Breaker
w/ Pwr Exh
Size
(Amps)
(Amps)
(Amps)
RLA
LRA
MCC
FLA
FLA
FLA
Model
KW
Stages
Amps
380
6.2
52.0
9.7
1.6
4.3
2.2
None
-
-
-
21.5
23.7
25
25
415
6.2
52.0
9.7
1.6
4.3
2.2
None
-
-
-
21.5
23.7
25
25
None
-
-
-
27.6
29.8
35
35
2TP04521850
11.3
2
17.2
29.5
32.2
35
35
2TP04522450
15.0
2
22.8
36.5
39.2
40
40
2TP04523650
21.3
2
32.4
48.5
51.2
50
60
2TP04525450
33.8
2
51.4
72.2
74.9
80
80
380
8.0
67.1
12.5
1.6
6.4
2.2
ZF120
415
380
8.0
11.2
67.1
75.0
12.5
17.5
1.6
1.6
6.4
6.4
2.2
2.2
ZF150
415
11.2
75.0
17.5
1.6
6.4
2.2
None
-
-
-
27.6
29.8
35
35
2TP04521850
13.5
2
18.8
31.5
34.2
35
35
2TP04522450
17.9
2
24.9
39.1
41.9
40
45
2TP04523650
25.4
2
35.3
52.2
54.9
60
60
2TP04525450
40.4
2
56.2
78.3
81.0
80
90
None
-
-
-
38.0
40.2
45
50
2TP04521850
11.3
2
17.2
38.0
40.2
45
50
2TP04522450
15.0
2
22.8
38.0
40.2
45
50
2TP04523650
21.3
2
32.4
48.5
51.2
50
60
2TP04525450
33.8
2
51.4
72.2
74.9
80
80
None
-
-
-
38.0
40.2
45
50
2TP04521850
13.5
2
18.8
38.0
40.2
45
50
2TP04522450
17.9
2
24.9
39.1
41.9
45
50
2TP04523650
25.4
2
35.3
52.2
54.9
60
60
2TP04525450
40.4
2
56.2
78.3
81.0
80
90
1. Minimum Circuit Ampacity.
2. Maximum Over current Protection per Standard UL 1995.
3. Fuse or HACR circuit breaker size installed at factory or field installed.
Johnson Controls Unitary Products
41
862075-XTG-G-0415
Typical Wiring Diagrams
ZF090-150 Typical Wiring Diagrams
Typical ZF090-120 Cooling Unit with Gas Heat Volt Wiring Diagram
42
Johnson Controls Unitary Products
862075-XTG-G-0415
Typical ZF090-120 Cooling Unit with/without Electric Heat Wiring Diagram
Johnson Controls Unitary Products
43
862075-XTG-G-0415
Typical ZF150 Cooling Unit with Gas Heat Volt Wiring Diagram
44
Johnson Controls Unitary Products
862075-XTG-G-0415
Typical ZF150 Cooling Unit with Gas Heat 380/415 Volt 50 Hz. Wiring Diagram
Johnson Controls Unitary Products
45
862075-XTG-G-0415
Weights and Dimensions
ZF090-150 Unit Weights
Unit 4 Point Load Weight
Unit 6 Point Load Weight
FRONT
FRONT
LEFT
LEFT
B
C
B
A
A
D
C
E
F
D
Y
X
FRONT
LEFT
Imperial
Size
Model
(Tons)
Weight (lbs.)
Shipping Operating
Center of
Gravity (in.)
X
Y
4 Point Load Location (lbs.)
6 Point Load Location (lbs.)
A
B
C
D
A
B
C
D
E
F
090
(7.5)
ZF
885
860
38
24
205
153
223
299
144
117
97
142
171
210
120
(10)
ZF
1065
1060
38
24
247
184
268
360
173
141
117
171
206
253
150
(12.5)
ZF
1258
1253
47
25
251
280
381
341
164
176
190
259
240
223
Metric
Center of
Gravity (mm)
Shipping Operating
X
Y
Weight (kg.)
Size
(KW)
Model
090
(22)
ZF
401
390
965.2
120
(35)
ZF
483
480
150
(44)
ZF
571
568
46
4 Point Load Location (kg.)
6 Point Load Location (kg.)
A
B
C
D
A
B
C
D
E
F
609.7
93
69.4
101.2
135.6
65.3
53.1
44
64.4
77.6
95.3
965.2
609.7
112
83.5
121.6
163.3
78.5
64
53.1
77.6
93.4
114.8
1193.8
635
113.9
127
172.8
154.7
74.4
79.8
86.2
117.5
108.9
101.2
Johnson Controls Unitary Products
862075-XTG-G-0415
ZF090-150 Unit Accessory Weights Imperial
Unit Accessory
Economizer
Power Exhaust
Electric Heat1
Gas Heat2
ZF090-150 Unit Accessory Weights Metric
Weight (lbs.)
Shipping
Operating
90
85
40
35
49
49
110
110
Weight (kg.)
Shipping
Operating
40.8
38.6
18.1
15.9
22.2
22.2
49.9
49.9
Unit Accessory
Economizer
Power Exhaust
Electric Heat1
Gas Heat2
1. Weight given is for the maximum heater size available
(54KW).
2. Weight given is for the maximum number of tube heat
exchangers available (8 tube).
1. Weight given is for the maximum heater size available
(54KW).
2. Weight given is for the maximum number of tube heat
exchangers available (8 tube).
ZF090-150 Unit Dimensions
ZF090 - 120
(754)
29.69
(387)
15.25
15.38
(391)
59.00
(1499)
15.38
(391)
2X Ø 24.38
(619)
B
NOTE: (XXX) Indicates Millimeters
SEE DETAIL A FOR GAS INLET
A
C
D
E
11.38 (289)
F
(1499)
59.00
(106)
4.19
LEFT
27.31
(694)
SEE DETAIL B
FOR DRAIN LOCATION
(2261)
89.00
(538)
21.19
FRONT
Johnson Controls Unitary Products
47
862075-XTG-G-0415
ZF150
45.64
(1159)
14.92
(379)
4X Ø 24.38
(619)
14.92
(379)
59.00
(1499)
14.92
(379)
29.95
(761)
30.11
(765)
B
SEE DETAIL A FOR GAS INLET
NOTE: (XXX) Indicates Millimeters
A
C
D
E
11.38 (289)
F
(106)
4.19
59.00
(1499)
LEFT
SEE DETAIL B
FOR DRAIN LOCATION
27.31
(694)
89.00
(2261)
21.19
(538)
FRONT
ZF090-150 Unit Physical Dimensions Imperial
Unit Model Number
090
120
150
A
42
50 3/4
50 3/4
B
89
89
119 1/2
Dimension (in.)
C
D
22 1/8
18 3/16
30 3/16
24 3/16
30 3/16
24 3/16
E
15 3/16
17 3/16
17 3/16
F
6 3/16
6 3/16
6 3/16
B
2261
2261
3035
Dimension (mm)
C
D
562
462
767
614
767
614
E
386
437
437
F
157
157
157
ZF090-150 Unit Physical Dimensions Metric
Unit Model Number
090
120
150
48
A
1067
1289
1289
Johnson Controls Unitary Products
862075-XTG-G-0415
Detail A
3.184
(81)
Gas Pipe Inlet
3.184
Gas Pipe Inlet
Ø 2.000
(51)
Ø 2.000
Gas Exhaust Vent
Gas Exhaust Vent
Ø 3.126
(587)
Ø 3.126
17.541
14.594
(371)
7.705
(196)
7.715
4.737
4.727
(120)
42”/1067mm CABINET
50 3/4”/1289mm CABINET
NOTE: (XXX) Indicates Millimeters
Detail B
5-3/8
(137)
NOTE: (XXX) Indicates Millimeters
3/4” FPT
(19.05)
ZF090-150 Unit Clearances Imperial
Direction
Top1
Front
Rear
Distance (in.)
72
36
36
Direction
Right
Left
Bottom2
Distance (in.)
12
36
0
1. Units must be installed outdoors. Over hanging structure or shrubs should not obscure condenser air discharge outlet.
2. Units may be installed on combustible floors made from wood or class A, B or C roof covering materials.
ZF090-150 Unit Clearances Metric
Direction
Top1
Front
Rear
Distance (mm)
1829
914
914
Direction
Right
Left
Bottom2
Distance (mm)
305
914
0
1. Units must be installed outdoors. Over hanging structure or shrubs should not obscure condenser air discharge outlet.
2. Units may be installed on combustible floors made from wood or class A, B or C roof covering materials.
Johnson Controls Unitary Products
49
862075-XTG-G-0415
ZF090-150 Unit Bottom Duct Opening
89
(2261)
32 11/16
(830)
6 13/16
(173)
6 13/16
(173)
SUPPLY
AIR
RETURN
AIR
27 1/2
(690)
LEFT
18
(457)
24
(610)
RIGHT
21
(533)
20 1/8 19 1/8
(511) (486) 17 1/8
(435)
12 5/16
(313)
Bottom condensate drain
14 1/2
(368)
16 3/8
(416)
18 1/16
(459)
25 9/16
(649)
Bottom gas
supply entry
NOTE: (XXX) Indicates Millimeters
FRONT
TOP VIEW
Bottom power, control
and convenience outlet
wiring entry
3X Ø 0.875
(22)
Ø 2.469
(63)
50
Johnson Controls Unitary Products
862075-XTG-G-0415
ZF090-150 Unit Electrical Entry
Disconnect Swith Cover
Power Entry Ø 2-1/2
(64)
Control Entry Ø 7/8
(22)
Power Entry Ø 2-1/2
(64)
Convenience Outlet Cover
Convenience Outlet
Power Entry Ø 7/8
(22)
FRONT
ZF090-120 Unit Side Duct Openings
Dot Plugs
18-1/4
(464)
Return
Air
A
Supply Air
D
B
2-31/32
(75)
5-5/32
(131)
C
NOTE: (XXX) Indicates Millimeters
Johnson Controls Unitary Products
31-11/16
(805)
51
862075-XTG-G-0415
ZF150 Unit Side Duct Openings
NOTE: (XXX) Indicates Millimeters
18-1/4
(464)
Dot Plugs
A
D
B
5-5/32
(131)
31-5/8
(805)
C
ZF Side Duct Dimensions Imperial
Unit Model Number
090
120
150
A
27 3/4
28 1/4
28 1/4
2-7/8
(75)
ZF Side Duct Dimensions Metric
Dimension (in.)
B
C
12 1/16
27 1/2
18 1/16
28 1/4
18 1/16
28 1/4
D
16
18 1/4
18 1/4
Unit Model Number
090
120
150
A
705
718
718
Dimension (mm)
B
C
306
698
459
718
459
718
D
406
464
464
ZF090-150 Unit Left Duct Opening
30-3/8
(772)
4-5/16
(110)
52
Johnson Controls Unitary Products
862075-XTG-G-0415
ZF090-150 Unit Accessory Dimensions
ZF090-150 Roof Curb
R IG H T
8 0 -5 /8
(2 0 5 0 )
IN S U L A T E D D E C K U N D E R
C O N D E N S E R S E C T IO N
2 0
(5 1 0 )
S U P P L Y
6
2 0
(5 1 0 ) (1 5 0 )
2 T Y P .
(5 0 )
R E T U R N
3 0
(7 6 0 )
IN S U L A T E D D E C K U N D E R
C O M P R E S S O R S E C T IO N
5 0 -1 /2
(1 2 8 5 )
8
1 4
O R
(2 0 5 )
(3 5 5 )
F R O N T
N O T E : (X X X ) IN D IC A T E S
D IM E N S IO N S IN
M IL L IM E T E R S
ZF090-150 Transition Roof Curb
2 T Y P
(5 0 )
5 0 -1 /2
(1 2 8 5 )
2 3
(5 8 5 )
3 0 -1 /2
(7 7 5 )
4
(1 0 0 )
2 6
(6 6 0 )
R E T U R N
8 0 -5 /8
(2 0 5 0 )
S U P P L Y
1 0
(2 5 5 )
7 6 -5 /8
(1 9 4 5 )
F R O N T
9 4
(2 3 9 0 )
5 9 -1 /4
(1 5 0 5 )
6 4 -1 /4
(1 6 3 0 )
Johnson Controls Unitary Products
R IG H T
53
862075-XTG-G-0415
Economizer Options
Economizer Usage
Application
Cabinet Height
Description
Model
Side Return
All
Horizontal economizer without barometric relief
2EE047069241
Downflow, End Return
Horizontal or ERV
42"
Economizer, 42” tall cabinet
2EE047074242
50"
Economizer, 50” tall cabinet
2EE047076242
1. Barometric relief must be ordered separately and installed in duct work.
2. Includes fresh air hood, exhaust hood and barometric relief.
Economizer Downflow W/Power Exhaust
Fresh Air Hood
Low Leak Economizer
Power Exhaust
Barometric
Relief Damper
54
Barometric Relief
Hood
Johnson Controls Unitary Products
Economizer End Return W/Power Exhaust
Fresh Air Hood
Field Installed
Duct Work
Low Leak
Economizer
Power Exhaust
Barometric Relief Damper
Barometric Relief Hood
Field Installed Horizontal Economizer W/Power Exhaust
Return Air Damper
Field Installed
Duct Work
Fresh Air Damper
Power Exhaust
Barometric
Relief Damper
Barometric
Relief Hood
Subject to change without notice. Printed in U.S.A.
Copyright © 2015 by Johnson Controls, Inc. All rights reserved.
York International Corporation
5005 York Drive
Norman, OK 73069
Fresh Air Hood
862075-XTG-G-0415
Supersedes: 862075-XTG-F-0513
Download PDF