Product Data Sheet
A45E-2
Addressable interface module
Miniature input interface unit
The A45E-2 addressable interface is designed for
installation within the enclosures of equipment
associated with fire detection systems. The unit is
installed directly onto the ZP loop wiring, carries a
system address and enables signals from associated
equipment to be interfaced into the fire alarm
system. Input signals are fully displayed at the
control panel and can be programmed to activate
any system output.
By routing loop wiring and installing interfaces
adjacent to input equipment, system integrity is
increased and the need for long spur wiring between
equipment terminals and the fire alarm interface is
eliminated.
Low profile mouldings
Complying with EN54 Part 18 the A45E-2 can be
installed singly, or used in groups to provide
multiway inputs from equipment such as volt free,
zonal outputs from conventional fire alarm systems
or flow valves from sprinkler installations.
Housed in a low profile, single width moulding the
interface is designed to clip directly onto a standard
DIN rail fixing or be installed in a SMB-DIN100 box
(two unit capacity), or a SMB-DIN200 box (four unit
capacity).
LED indication
A red LED indicator positioned on the front moulding
flashes when the interface has operated, providing
clear identification of the input signal source.
Installed as part of an analogue addressable system,
up to 127 line devices (sensors, callpoints or
interface units) can be connected to each of the
control panel loops. All loop devices incorporate
switch settings enabling them to be assigned a
unique address, which is polled by the panel every
two seconds.
Standard Features
E
E
E
E
E
E
Addressable input interface unit
Complies with EN54 Part18
Low profile
DIN rail mounted
Accepts normally open input circuits
Monitors input circuit wiring for open or short circuit faults
A45E-2
Addressable interface module
Specifications
A45E-2
EN54 Part 18
Addressable interface unit
All ZP analogue addressable systems
Equipment cabinet DIN rail, or SMB-DIN 100, SMB-DIN200 surface boxes
2 core loop (screened)
Input cable for open or short circuit fault by 3K9 ohm EOL resistor
Normally open - with 1K8 series resistor
Fire or non fire (set by software in panel)
LED (red) flashing on operation
Pulsed ZP loop (19.5 – 20.5V) with max 4 Volt line loss.
650uA quiescent, 700uA alarm
10m (from switching terminals) Cable must be screened and the screen
terminated in the loop screen terminal
Indoor installation
IP20
-10ºC to +75ºC
20% to 95% RH (non condensing)
CE marked (EEC89/336)
Moulded ABS
45mm (W) x 78mm (H) x 28mm (D)
White
40g
PS1762
Model No
Specification
Description
Compatibility
Mounting
Wiring
Monitoring
Input signal
Interface type
Indication
Operating voltage
Current
Max cable distance
Application
EN60529 rating
Temperature range
Humidity range
EMC
Material
Dimensions
Colour
Weight
Publication No
Ordering Information
Part No.
Description
A45E-2
Addressable interface module
As a company of innovation, UTC Fire & Security reserves the right to change product specifications without notice. For the latest product specifications, visit UTC Fire & Security
online or contact your sales representative.
IPS-A45E-2-2011-06-16 09:51:57 Released : 16-JUL-07