Fire Detection - Addressable
Protec
Protec Fire Detection plc
Protec Algo-TecTM 6100
Interactive Digital Addressable Fire Control System
A D D R ESS IN G
S A FE T Y
SYST E M S
W I T H
I NT E L L I G E N CE
Fire Detection - Addressable
Protec
P r ot ecFire
F ire Detection
De tecti on pl cplc
Protec
Protec Algo-TecTM 6100
INTERACTIVE DIGITAL ADDRESSABLE
FIRE CONTROL SYSTEM
• Cost Effective Single Loop Panel
• High Capacity Loop - 192 Addresses
• Algo-TecTM 6000PLUS Protocol
• Surface and Recessed Mounting
• Easy to Install
• Reduced False Alarms
• Enhanced Performance
• On Site Flexibility
• Designed to EN 54-2 & 4
• Open Protocol
System Features
The Protec Algo-TecTM 6100 is an interactive digital
addressable fire detection and alarm system ideally
suited for small and medium sized buildings such as
shops, hotels and offices. The control panel is designed
and manufactured by Protec to comply with EN 54-2 &
4. The control panel is suitable for surface or recessed
mounting with a moulded polycarbonate enclosure
finished in storm grey.
Loop
The 6100 control panel is equipped with a high capacity
Algo-TecTM digital addressable data loop, with up to
192 addresses. In addition to the Algo-TecTM 6000PLUS
sensors, interfaces and manual call points the loop can
also support loop powered SOUNDERS, VISUAL ALARM
DEVICES and OPTICAL BEAM DETECTORS. Additionally
a 6300 Loop Powered Repeat Display can be connected
directly to this loop, resulting in reduced cabling
requirements, simplified installation and associated cost
savings.
Liquid Crystal Display
The 80 character liquid crystal display will under normal quiescent conditions display the current date and time with the option to also display a 40-character user’s
message such as site name.
In an alarm or fault condition the LCD will display the device, address and zone
number and up to 20 characters of user definable location text, programmable on
site using Protec 6100 windows based software.
Device Location Text
Windows based text software is supplied free of charge to our clients to enable
you to enter the location text on to the disk supplied and hand to our commissioning
engineer for loading into the panel during commissioning. This simple process allows you more flexibility enabling you to make any last minute changes and speed
up the entire process.
Alarms
In addition to loop powered sounders and Visual Alarm
Devices (VAD’s), 2 fully monitored alarm outputs are
provided at the panel for alternative wiring arrangements.
Power Supply
The 6100 control panel is supplied with an integral 1A dc switch mode charger and
accommodates two 12V 3.3 Ah sealed lead acid battery.
Auxiliary Contacts
One set of global fire, and one set of fault changeover
contacts.
On Site Programming
The Protec Algo-Tec™ 6100 system is on site programmable. All of the commissioning configuration data can be entered and/or backed up using the Protec 6100
windows based programming software via a PC. This feature enables the system
to be re-configured and checked prior to attending site simplifying commissioning
works on site, enabling text amendments to be carried out whilst on site and providing an invaluable remote backup should the need arise.
Controls and Display
All the functions of the modern styled Control Panel are
accessed by entering the user access code. The controls
are SILENCE, SOUND ALARMS, RESET and ACCEPT
plus navigation push buttons to enable access to the
user menu facilities. The control panel display consists
of a 4x20 character liquid crystal display, twin common
fire LED indicators, 16 separate zonal fire LED’s, power
on, pre-alarm, system fault, common fault, test and
disablement LEDs.
Loop Devices
The Protec Algo-Tec™ 6000PLUS protocol utilises FAST™
addressing (Firmware Addressed Secure Technology).
Every FAST™ device is manufactured with a unique serial number.
FAST™ addressing ELIMINATES troublesome and time
consuming address cards and DIL switching whilst being
far more secure than “soft addressing”.
Plant shutdown
interface 6000/MICCO
The Protec Algo-Tec™ 6000PLUS sensor range has been
developed to incorporate advanced fire sensing technology, electronic sounders, high intensity visual alarm
and speech enhanced talking sounder capability, all integrated within the sensor head and powered from the
loop.
6000PLUS/OP
Plant shutdown
output (Rated
at 240V 5A)
LOOP 1
EOL
Typical Sensor Variants
6000PLUS/OPHT/S = c/w Sounder
6000PLUS/OPHT/VAD = c/w Visual Alarm Device
6000PLUS/OPHT/S VAD = c/w Sounder and Visual Alarm Device
6000PLUS/OPHT/TS = c/w Talking Sounder
6000PLUS/OPHT/TS VAD = c/w Talking Sounder and Visual Alarm Device
6000PLUS/HT Sprinkler delay
interface
6000/MICCO
6300 Loop repeater
Heavy duty plant shutdown
signal (Rated at 240V 5A)
EOL
EOL
EOL
Alarm circuit
Alarm circuit
Zone circuit
Zone circuit
6000/LPZA
Loop powered
zone alarm
interface
FASTTM Interactive Heat Sensor - Interactive
addressable heat sensor with low thermal mass
thermistor, giving fast response to temperature
increases. Other Heat Sensor variants include:
6000PLUS/HT/S, 6000PLUS/HT/SVAD
6000PLUS/HT/TSVAD
6000/LCM
Local Control
Module
FASTTM Interactive Optical Smoke Sensor - Interactive addressable high performance optical
smoke sensor provide efficient reliable detection
using the light scatter sensing principle with rapid
response to a fire signal. Other Optical Sensor
variants include: 6000PLUS/OP/S
Single 2 wire loop cable
6000PLUS/OPHT FAST Interactive Optical Heat Sensor - Interactive addressable high performance optical
smoke and heat multi-sensor. Other Optical Heat
Sensor variants include:
6000PLUS/OPHT/S, 6000PLUS/OPHT/VAD,
6000PLUS/OPHT/SVAD, 6000PLUS/OPHT/TS,
6000PLUS/OPHT/TSVAD
TM
}
6000PLUS/OPHTCOFASTTM Interactive Optical Heat CO Sensor Interactive addressable high performance optical
smoke heat and carbon monoxide multi-sensor.
Other Optical Heat CO Sensor variants include:
6000PLUS/OPHTCO/S, 6000PLUS/OPHTCO/VAD,
6000PLUS/OPHTCO/SVAD, 6000PLUS/OPHTCO/
TSVAD
2 monitored alarm outputs
Monitored fire station output
1 Auxiliary fire c/o contact
1 Auxiliary fault c/o contact
24V Aux. output
Bomb alert/class change input
Remote alarm input
6000PLUS/BASE Low Profile Common Mounting Base - Compatible with the above range of Algo-TecTM 6000PLUS
Sensors.
Mains ac supply
6000PLUS/FFBASE Fast Fixed Base - Fast fixed recessed base is designed to recess the sensor into a false ceiling to
give a lower profile view of the sensor.
6300/LOOP/LCD Repeater - Connected directly to the local data loop
and takes up just one address. The 1 x 40 character LCD Display provides clear text location of fire
and fault events.
6000/MCPFASTTM Addressable Manual Call Point - Key
operated test facility, a loop short circuit isolator
is incorporated.
KEY:
Heat Sensor
Local Control Module
Optical Smoke and Heat Sensor
Monitored Input CC Output Interface
Optical Smoke, Heat and CO Sensor
Electronic Sounder
Duct Probe Unit c/w Smoke Sensor
Electronic Sounder VAD
Manual Call Point
Visual Alarm Device (VAD)
Beam Detector
6300 Loop LCD Display
Loop Powered Zone Alarm Interface
500
550
600
650
Loop Length (Metres)
700
750
800
850
50
100
150
200
250
300
350
400
450
500
550
600
650
700
750
800
850
900
950
1000
Total
Loop
Load
in
Alarm
(mA)
950
1000
6000/FIREBEAMFASTTM Addressable Loop Powered Beam Detector - Combined transmitter/receiver unit and
separate low level controller. With a beam range
of 5-100 metres.
6000/SSRFASTTM Addressable Loop Powered High Output
Electronic Sounder - utilises a Piezo driver unit
to enable high sound output and very low current
consumption.
n/an/a n/an/a n/a n/a n/a n/a
1050
Total
Loop
Load
in
Alarm
(mA)
900
50
100
150
200
250
300
350
400
450
500
550
600
650
700
750
800
850
900
950
1000
n/a
n/a
n/a
n/a
n/a
1100
n/a
n/a
n/a
n/a
n/a
n/a
1150
n/a
n/a
n/a
n/a
n/a
n/a
Loop Length (Metres)
1200 1250 1300
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
1350
1400
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
1450
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
1500
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
The conductor size required as follows:
1.0mm2
1.5mm2
2.5mm2
MAXIMUM LOOP RESISTANCE 16 OHMS PER CONDUCTOR
Table detailing the loop standby and alarm load for typical Algo-tec™ 6000 devices.
Loop
Loop
Standby
Alarm
Load mA Load mA
Description
No of
Addresses
Manual Call Point
1
0.45
6000/FIREBEAM
Loop Beam
1
3.65
7
6000PLUS/HT
Heat Sensor
1
0.2
0.2
Product
6000/MCP
0.85
6000PLUS/HT/S
Heat Sensor c/w Sounder
1
0.4
5.4
6000PLUS/OPHT
Optical Smoke and Heat Sensor
1
0.2
0.2
6000PLUS/OPHT/S
Optical Smoke and Heat Sensor c/w
Sounder
1
0.4
5.4
6000PLUS/OPHT/SVAD
Optical Smoke and Heat Sensor c/w
Sounder and Visual Alarm Device
1
0.55
24
6000PLUS/OPHT/TSVAD
Optical Smoke and Heat Sensor c/w Talking Sounder and Visual Alarm Device
1
0.55
25
6000PLUS/OPHTCO
Optical Smoke, Heat, and CO Sensor
1
0.45
0.45
6000PLUS/OPHTCO/S
Optical Smoke, Heat, and CO Sensor
c/w Sounder
1
0.45
5.45
Loop Visual Alarm Device
1
0.8
19
Loop Sounder
1
0.7
5
6000/VAD/W
6000/SSR
6000/SSR/VAD
6000/LCM
6000/MICCO
6000PLUS/UG4DP Ventilation Duct Smoke Sensor Assembly - Single
pipe air sampling unit for air speeds from 0.5 to
20m per sec. supplied with 6000PLUS/BASE suitable for use with 6000PLUS/OP FASTTM interactive
optical smoke sensor.
Loop Sounder Visual Alarm Device
1
0.7
24
Local Control Module
1
0.7
5
Monitored Input CC Output
1
0.55
5
Note: The following Loop Parameters should be observed
1) The total number of addressable devices should not exceed 192 per loop.
2) Add 20mA to total loop alarm load to allow for fire indicator LED’s on devices
3) The total loop alarm load should not exceed 600mA per loop.
6000/VAD/W/REDFASTTM Addressable Loop Powered High Intensity
VAD - Approved to EN54-23 the wall mounted VAD
has a unique lens that distributes the white light in
a cuboid pattern to achieve 7.5m x 7.5m coverage
@ 2.4m high.
6000/VAD/C/REDFASTTM Addressable Loop Powered High Intensity
VAD - Approved to EN54-23 the ceiling mounted
VAD has a unique lens that distributes the white
light in a cylindrical pattern to achieve 7.5m dia
coverage @ 3m high.
6000/SSR/VADFASTTM Addressable Loop Powered High Output
Electronic Sounder with VAD - Approved to EN543, 17 & 23 the wall mounted combined sounder/
VAD has a sound output of 100dB(A) @ 1m plus
VAD light output of 7m x 7m coverage @ 2.4m high.
6000PLUS/TSR2FASTTM Addressable Loop Powered Talking
Sounder - The 6000PLUS/TSR2 voice enhanced
talking sounder is available with seven voice messages plus ‘bell’ sound in addition to the three fire
alarm tones compatible with the Protec range of
electronic sounders.
6000/FIU
Flush Mounted Short Circuit Isolator Unit - To
isolate a short circuit fault on either the incoming
or outgoing loop cables. Suitable for a 30mm deep
electrical mounting box.
6000/LPZAFASTTM Addressable Flush Mounted Loop Powered Zone Alarm Interface Unit - With a monitored detection circuit suitable for use with
Protec 3000 series detection devices. Line continuity maintained. Monitored alarm output circuit
rated at 24Vdc 50mA max. Suitable for a 45mm
deep electrical mounting box. A loop short
circuit isolator is included.
6000/LCMFASTTM Addressable Flush Mounted Local Control Module - Allows easy integration of Protec
addressable fire detection systems into houses
of multiple occupany and offers novel features to
reduce false alarms. The interface drives a zone
of 3000 series detection devices and provides a
supply to a local alarm circuit.
6000/MICCOFASTTM Addressable Flush Mounted Loop Powered
Monitored Input, Clean Contact Output Interface
Unit - With a monitored input circuit suitable for
use with simple switch devices and the output is a
clean changeover contact 5amp rated at 240V ac.
A link can be cut to provide a 7-second delay to the
input. Suitable for a 45mm deep electrical mounting
box. A loop short circuit isolator is incorporated.
Multi-way Input/Output Interfaces - A range of 16 way input/output
interfaces are available with monitored alarm outputs or clean changeover contacts. All interfaces
are FASTTM addressable.
Fire Detection - Addressable
Guide to loop cable conductor sizing for the Protec 6100 system.
Interactive Decision Making Algorithms - Typical Applications
Office Mode (High Performance)
Clean Mode (Extra High Performance)
DISCRIMINATING
ALGORITHM
Cigarette Smoke
ALARM
Computer Room Fire
ALARM
Computer Fire
ALARM
Printer Paper Fire
ALARM
Bin Fire
Day/Night Mode
CAUTION
Factory Loading Bay
Offices
ALARM
Chemical Fire
Bedroom Mode
DISCRIMINATING
ALGORITHM
Steam From Bathroom
Day Mode:
Office mode (high performance)
Day Mode:
Heat detection only (6000PLUS/OPHT)
Offices
Factory Loading Bay
DISCRIMINATING
ALGORITHM
Aerosols in Bedroom
ALARM
Night Mode:
Clean mode (Extra high performance)
Night Mode:
Smoke & Heat detection
Smoldering Fire
NOTE: The above examples give an indication of system reaction to intermittent contaminants and
typical fire sources in a correctly designed BS5839 system . They by no means detail the full complexity
of the systems decision making algorithms. Examples are for 6000PLUS/OPHT.
The Protec Algo-Tec™ 6100 Interactive Digital
Addressable System unwrapped:
The Protec Algo-TecTM 6000PLUS protocol developed by
Protec’s in-house Research and Development team is
utilised by the Protec Algo-TecTM 6100 interactive digital
addressable fire control systems. Immunity to false
alarms, more responsive fire detection, and ease of use
has all been achieved to develop one of the most reliable
systems available.
Protec Algo-Tec™ 6000PLUS
The name Algo-TecTM is a derivative of Protec algorithms.
Algorithms are logical mathematical procedures for
solving problems. Protec have developed fire detection
algorithms coupled with fuzzy logic specifically designed
to reduce unwanted fire alarms and to enhance the
sensitivity of the system to true fire phenomenon. The
Algo-TecTM algorithms are exclusively utilised by the
Protec Algo-TecTM 6400, 6300 and 6100 Interactive Digital
Addressable Fire Control Systems.
Interactive
Algo-TecTM evaluates the data of each fire sensor
and is able to learn from the information received.
This may simply be to recognise that a sensor is
becoming contaminated or in a dirty environment
and to automatically increase the alarm threshold to
compensate for the background levels (Threshold
Compensation).
More complex Algo-TecTM functions include the ability
to discriminate between certain fire and non-fire
conditions, filtering out certain environmental stimuli, and
increasing the sensitivity of a sensor when an increase in
temperature is detected.
The net effect of the interaction between the sensors
and the Algo-TecTM decision making is enhanced
performance, through immunity to false alarms and more
responsive fire detection.
Digital Addressable
The data communication between the sensors and the
control equipment is Digital.
The Algo-TecTM protocol utilised by the 6000PLUS system
enables high levels of data to be transferred, providing
far more detailed information than was previously
achievable with analogue addressable systems. It should
however be noted that many analogue addressable
systems use digital communication but do not transfer
the high levels of data associated with the Algo-TecTM
protocol. Speed, stability, excellent EMC and security all
serve to enhance the Algo-TecTM Digital signalling. Why
go analogue addressable when you can now choose
Algo-TecTM Digital Addressable.
6300 Loop LCD Display
The 6300/LOOP/LCD can be connected directly to the local Algo-TecTM digital addressable
data loop and takes up just one address. The facia displays power, fire, fault, disablement
and more alarms.
Fire and fault events are displayed on the 2 x 40 character LCD display and automatically
scroll. A backlight ensures that the events can be read in all lighting situations. Fire
events have highest priority and inhibit the display of fault events. A new event initiates
the internal buzzer and a mute button allows the internal buzzer to be muted.
Loop standby/Alarm load 60mA.
Dimensions (mm): 360(W) x 215(H) x 47(D)
Fire Detection - Addressable
Algo-Tec™ 6000PLUS
Fire Detection - Addressable
Technical Specification
6100 Control Panel
Complies with EN54-2 & 4
Model:-
6100 - Single Loop.
Specification:-.
Rated Voltage
Rated Frequency
Rated Current
Working Voltage
Temperature Range
Maximum Humidity
IP Rating
Battery Type
Standby Load (Mains Fail Condition)
Maximum Alarm Load (Mains Fail Condition)
KM575025
Mains 100 to 240V ac rms.
0086-CPD-575026
50 to 60Hz.
BS EN54-2:1997
600mA rms.
BS EN54-4:1998
21.5 - 29V dc.
0 - 40°C.
85% Non-condensing.
IP30.
2 x 12V 3.3Ah sealed lead acid.
22mA.
56mA panel, 600mA loop, 200mA conventional alarms (100mA per alarm output), 150mA auxillary 24V output,
20mA fire-link.
Display
Digital Addressable Loops
Total Loop Load
Zones
Integral Charger
Integral Battery
Alarm Outputs
Global Fire Outputs
Alarm Load
Fault Monitoring
Fault Output
Auxiliary Output Supply
Common Fire Output (fire station)
Communications Interface
Dimensions (mm)
Weight
Applicable Standards
Backlit liquid crystal display 4 lines of 20 characters.
1 loop, with 192 address capacity. Algo-Tec™ 6000PLUS Protocol.
600mA including all loop connected devices.
32 Zones, 16 with LED indication, plus general fire indicator.
1A dc switch mode, temperature compensated.
2 x 12V 3.3Ah sealed lead acid.
2 monitored conventional sounder circuits (100mA per output maximum).
Up to 192 alarm outputs using loop output devices.
1 set of non-monitored changeover contacts (1A @ 24V dc) operating on any fire.
600mA loop, 100mA per conventional alarm output.
Fully fault monitored to EN 54-2 & 4.
Single pole changeover contacts (1A rated @ 24V dc).
24V dc fused at 150mA.
24V dc fully monitored output (requires end of line module SF4165759).
USB 2.0 (Type A male to Type B male connection lead required, 2 metres maximum length).
228(W) x 345(H) x 111(D).
1.5kg (excluding batteries).
EN 54-2 : 1997 + A1 : 2006.
EN 54-4 : 1998 + A1 + A2.
Programmability
32 Input Groups 32 Output Groups Non-Latching Coincidence Detection Sensitivities Sounder Volume Day/Night Time Sounder Pulsing Time Talking Sounder Synchronisation Time Fire Link Delay Time Walk Test Time Windows Software Suite First 31 groups are available for detection zones, group 32 is reserved for Sound Alarms push button.
Each output group can have a delay programmed (5 seconds to 10 minutes).
Each output group can be set as Alarm or Control type.
Loop addresses may be programmed to be non-latching.
To EN 54-2 Type C dependency.
Each detector may have one of two sensitivities programmed.
Each loop sounder may be programmed to be low, medium or high volume.
The panel may be programmed into two time zones to run different sensitivities for each detector.
The sounder on and off times may be programmed from 0.5 sec to 128 sec in 0.5 second increments.
1 sec to 120 sec in 1 second increments.
5 seconds to 10 minutes in 5 second increments.
1 sec to 255 sec in 1 second increments.
Proprietary software suite designed specifically for the 6100.
Allows text editing, matrix configuration, setup of all panel parameters.
Text
Panel Text Device Address Text Zone Text 2 lines of 20 character panel text. Displayed when the system is ‘normal’.
20 characters of device address text.
20 characters of zone text.
Language Support
The 6100 supports multiple languages.
Protec
Protec Fire Detection plc
Protec: Scotland
Tel: 0845 456 5390
Fax: 0845 456 5391
Protec: North East
Tel: 0845 456 5396
Fax: 0845 456 5397
Protec: Yorkshire
Tel: 0845 456 5388
Fax: 0845 456 5389
Protec: Midlands
Tel: 0845 456 5398
Fax: 0845 456 5399
Protec: South East Protec: South West
Tel: 0845 456 5394
Tel: 0845 456 5392
Fax: 0845 456 5395 Fax: 0845 456 5393
Company Policy is one of continuous improvement, we reserve the right to change specification without prior notice
Protec Fire Detection Plc, Protec House, Churchill Way, Nelson, Lancashire, BB9 6RT