Industrial Serial Fiber Converter
Preliminary
IFC-FDC-PRO
PROFIBUS to Daisy Chain Fiber Converter
IFC-Serial-PRO
PROFIBUS to Fiber Converter
EN61000-6-2
EN61000-6-4
PROFIBUS
These products are PROFIBUS to fiber optic converters which secure PROFIBUS data transmission via fiber optical cabling for extending
distance and isolating EMC/noise to reduce mutual interference between PROFIBUS devices.
These products are protocol transparent, can be applied to the PROFIBUS, and also can be applied to other networks using RS485
interfaces (See Figure 1).
Features
▪▪Supports 2 fiber link (IFC-FDC-PRO)
▪▪Supports 1 fiber link (IFC-Serial-PRO)
▪▪Extend serial transmission distance up to 2km, 30km, 60km
▪▪Supports several topology , cable redundancy (Figure 3), ring redundancy (Figure 4), daisy chain (Figure 5), point to point (IFC-FDC-PRO)
▪▪Supports point to point (Figure 6) (IFC-Serial-PRO)
▪▪Redundant dual power inputs (12/24/48VDC)
▪▪Protocol transparent. These products can be applied to the PROFIBUS, but also can be applied to other network using RS485 interface
▪▪Baudrate up to 12Mbps
▪▪Auto baudrate, no need to set baudrate
▪▪2.5KVrms isolation for serial port
▪▪CE, FCC, heavy industrial grade EMS, EMI, EN61000-6-2, EN61000-6-4 certified
▪▪Supports relay output for power or link failure warning
▪▪Hardened housing with IP30 protection
▪▪Fanless and DIN-Rail design for harsh industrial environment
▪▪Adjustable pull high/low resistor and terminator for RS-422/485 transmission
Specifications
FieldBus
Protocol
Problem
isolation
Fiber Port
Interface
Fiber port
Topology
Serial port
Interface
Protocol
PROFIBUS and all operations available
transparent
on RS485
Isolate EMC/noise to reduce mutual interference
between PROFIBUS device.
Isolate the PROFIBUS side of the failure, to avoid the
impact of the other side (See Figure 2 )
Connector
SC, ST
2 fiber ports (IFC-FDC-PRO)
Fiber Port
1 fiber port (IFC-Serial-PRO)
MM 2km, SM 30km, 60km
Fiber Type
Bidi 20KM
MM 1310nm, SM 1310
Wavelength
Bidi: Mode A : TX1310nm/RX1550nm
Mode B : TX1550nm/RX1310nm
Point to Point
Full duplex
Transmission
Ring
Full duplex, self-healing operation
Transmission
Zero recovery time
Cable redundancy(Figure 3) with zero recovery time
Ring redundancy(Figure 4) with zero recovery time
Daisy chain(Figure 5)
Point to point (IFC-FDC-PRO)
Point to point(Figure 6) (IFC-Serial-PRO)
DB9 Female
Serial Port
Connector
RS-485 : 4, 2 wires
RS-485 direction Automatically detection
Serial port
50 to 12Mbps
Baudrate
Auto baudrate, no need to set baudrate
Serial port
2.5KVrms isolation for serial signals
isolation
EMC/noise isolation, to reduce
mutual interference between serial
port device
Serial port
Interface
Pull high resistor
Pull low resistor
120 ohm
terminator
Environmental Operating
Temperature
Selected by 10 position rotary switch
Selected by 10 position rotary switch
Built-in 120 ohm terminator (Selected
by Dip Switch)
-10 ~ 60°C
(IFC-FDC-PRO, IFC-Serial-PRO)
-40 ~ 75°C
(IFC-FDC-PRO-E, IFC-Serial-PRO-E)
Storage
-40 ~ 85°C
Temperature
Humidity
5 ~ 95% RH
LED Indications PWR1, PWR2, Alarm, Master, TD, RD, Fiber Link, Fiber2
Link (IFC-FDC-PRO only), Ring
Alarm Relay
Alarm exists for power, fiber link or ring protection
Relay output with carry capacity 1A @ 24VDC
Power
Redundant Dual Power 12, 24, 48 VDC
Power Input
(9.6 ~ 60VDC)
Power
<6W
Consumption
Power Reversal Yes
Protection
Over Current Protection: Signal Short Together
Protected
Terminal Block for Power and Alarm :
Terminal Block : V1+, V1-, V2+, V2-, Alarm NC, Alarm COM,
Alarm NO
Mechanical
Water & Dust
IP30 Protection, Fanless
Proof
Dimensions
106 x 38.6 x 142.1mm (D x W x H)
Mounting
DIN-Rail, or wall mounting (Optional)
Weight
TBD
www.ctcu.com / [email protected]
Specifications & design are subject to change without prior notice. Please visit CTC Union website for more details.
8-1
8
Industrial Serial Fiber Converter
These converters are capable of selecting interface modes for connection to RS-485 2-wire half duplex or 4-wire full duplex. Additionally,
the terminal block offers an alarm relay contact and two redundant DC power inputs. IFC Series converters are also available in two
operating temperature ranges, a standard -10° to 60°C commercial temperature range and an extended -40° to 75°C range. With all
these specifically designed features, the series is reliable and an ideal solution for keeping your industrial automation applications
running smoothly and continuously even in harsh environments.
Industrial Serial Fiber Converter
Certification
EMC
EMI
Immunity for
Heavy
Industrial
Environment
Emission for
Heavy
Industrial
Environment
EMS
EN61000-4-2 ESD Level 3
EN61000-4-3 RS Level 3
EN61000-4-4 EFT Level 3
EN61000-4-5 Surge Level 3
EN61000-4-6 CS Level 3
IEC 60068-2-32
IEC 60068-2-6
IEC 60068-2-27
RoHS
TBD
(Electromagnetic
Susceptibility)
Protection Level
CE
FCC Part 15 Subpart B Class A, CE
EN61000-6-2
Free Fall
Vibration
Shock
Green
MTBF
EN61000-6-4
Application & Topology (IFC-FDC-PRO)
Figure 1 : Application for PROFIBUS Network
0004
12
0004
12
5F
5F
PLC
Sensor HMI
Digital
power meters
PROFIBUS
PROFIBUS
Digital
power meters
HMI
Sensor
PLC
Fiber
PROFIBUS
0004
12
IFC-FDC-PRO
5F
PLC
Sensor HMI
Digital
power meters
PROFIBUS
IFC-FDC-PRO
Fiber Ring
5F
Digital
power meters
IFC-FDC-PRO
Benefit:
0004
12
1. EMC/noise isolation, to reduce mutual interference between
serial port device
2. Extend distance by fiber
3. Cable redundancy
4. Isolate PROFIBUS failure
5. Achieve a reliable network environment
HMI
Sensor
PLC
IFC-FDC-PRO
IFC-FDC-PRO
PROFIBUS
0004
12
5F
Digital
power meters
HMI
Sensor
PLC
Figure 2 : Isolate PROFIBUS Failure
Failure
5F
PLC
HMI
Fiber Cable
PROFIBUS
0004
12
PROFIBUS
0004
12
5F
Digital
power meters
IFC-FDC-PRO
IFC-FDC-PRO
Digital
power meters
HMI
PLC
Figure 3 : Fiber Cable Redundancy topology & application
Fiber Cable Redundant
RS485
RS485
IFC-FDC-PRO
IFC-FDC-PRO
Figure 4 : Fiber Ring Redundancy topology & application
IFC-FDC-PRO
IFC-FDC-PRO
RS485
RS485
Master
Fiber
Fiber Ring
RS485
IFC-FDC-PRO
IFC-FDC-PRO
IFC-FDC-PRO
RS485
8-2
RS485
www.ctcu.com / [email protected]
Specifications & design are subject to change without prior notice. Please visit CTC Union website for more details.
Industrial Serial Fiber Converter
Figure 5 : Fiber Daisy Chain topology & application
IFC-FDC-PRO
IFC-FDC-PRO
IFC-FDC-PRO
Fiber
Fiber
RS485
IFC-FDC-PRO
RS485
Fiber
RS485
RS485
Application & Topology (IFC-Serial-PRO)
Figure 6 : IFC-Serial-PRO Application for PROFIBUS
8
HMI
PLC
Industrial Serial Fiber Converter
Digital
power meters
0004
12
IFC-Serial-PRO
Digital
power meters
PROFIBUS
0004
12
5F
IFC-Serial-PRO
PROFIBUS
Fiber
5F
IFC-Serial-PRO
Fiber
IFC-Serial-PRO
Digital
power meters
0004
12
PROFIBUS
IFC-Serial-PRO
IFC-Serial-PRO
Fiber
5F
PROFIBUS
0004
12
5F
Digital
power meters
HMI
PLC
Figure 7 : Fiber Point to Point topology & application
Fiber
RS485
IFC-Serial-PRO
RS485
IFC-Serial-PRO
Benefit:
1. Reduce mutual interference between serial port device
2. Extend distance by fiber
3. Achieve a reliable network environment
www.ctcu.com / [email protected]
Specifications & design are subject to change without prior notice. Please visit CTC Union website for more details.
8-3
Industrial Serial Fiber Converter
Ordering Information
Serial (ProfiBus)
Model Name
Fiber
RS422/485
Isolation
2.5KV
SC/ST
IFC-FDC-PRO
1
V
IFC-FDC-PRO-E
1
V
IFC-Serial-PRO
1
IFC-Serial-PRO-E
1
Power Input
Certification
Redundant
EN61000-6-2
EN61000-6-4
CE
FCC
2
12/24/48VDC
V
V
V
2
12/24/48VDC
V
V
V
V
1
12/24/48VDC
V
V
V
V
1
12/24/48VDC
V
V
V
E
SC002
Operating
Temperature
-10~60°C
-40~75°C
-10~60°C
-40~75°C
Model Naming Rule
Industrial
Serial Fiber
Converter
Connector Type
SC, ST
PRO
FDC
IFC
FDC : IFC-FDC
Serial: IFC-Serial
PRO: PROFIBUS
E: -40~75 C
Blank: -10~60 C
Connectivity Distance
002: M/M 2km 030: S/M 30km 060: S/M 60km
020AB: 20KM Bidi (20KM 1x mode A + 1x Mode B) (for IFC-FDC-PRO)
020A: 20KM Bidi mode A (for IFC-Serial-PRO)
020B: 20KM Bidi mode B (for IFC-Serial-PRO)
Mode A: TX 1310nm/RX1550nm Mode B: TX 1550nm/RX1310nm
Temperature
Example:
Package List
• One device of the series
• Quickly installation guide
• Din Rail with screws
• Terminal block
Optional Accessories
Wall Mount kit Accessories
IND-WMK01
8-4
See below for more detail
Wall Mount kit for Industrial product, 184 x 30mm
www.ctcu.com / [email protected]
Specifications & design are subject to change without prior notice. Please visit CTC Union website for more details.
Connector Connectivity
Type
Distance
IFC – FDC –PRO– □ – □□□□□
IFC – FDC –PRO – E– SC002
Industrial Serial Fiber Converter
Preliminary
IFC-Serial-CAN
CAN BUS to Fiber Converter
EN61000-6-2
EN61000-6-4
PROFIBUS
These products are CAN BUS to fiber optic converters which secure CAN BUS data transmission via fiber optic to extend distance and
isolate from EMC/noise thus reducing interference between CAN BUS devices. (See Figure 1)
The converters are available in two operating temperature ranges, a standard -10° to 60°C commercial temperature range and an
extended -40° to 75°C range. With all these specifically designed features, the series is reliable and an ideal solution for keeping your
industrial automation applications running smoothly and continuously even in harsh environments.
Features
8
Specifications
FieldBus
Protocol
Problem
isolation
System
Propagation
delay
Fiber Port
Interface
CAN 2.0A, CAN 2.0B, ISO 11898-2 standard
Isolate EMC/noise to reduce mutual interference
between CAN BUS device.
Isolate the CAN BUS side of the failure, to avoid the
impact of the other side (See Figure 2)
125ns
Connector
Fiber Port
Fiber Type
Wavelength
Baud rate
Fiber port
Topology
CAN BUS port
interface
Power
SC, ST
1 fiber port
MM 2km, SM 30km
Bidi 20KM
MM 1310nm, SM 1310nm
Bidi: Mode A : TX1310nm/RX1550nm
Mode B : TX1550nm/RX1310nm
Upto 1Mbps
Auto baud rate, depend on CAN BUS
copper port
Point to point (Figure 3)
3 pin terminal block
CAN_L, CAN_H, CAN_GND
50 to 1Mbps
Baudrate
Auto baudrate, no need to set baudrate
CAN BUS port
2.5KVrms isolation for CAN BUS
isolation
signals
EMC/noise isolation, to reduce
mutual interference between serial
port device
120 ohm
Built-in 120 ohm terminator (Selected
terminator
by Dip Switch)
Environmental Operating
-10 ~ 60°C (IFC-Serial-CAN)
Temperature
-40 ~ 75°C (IFC-Serial-CAN-E)
Storage
-40
~ 85°C
Temperature
Humidity
5 ~ 95% RH
LED Indications PWR1, PWR2, Alarm, Fiber TX, Fiber RX
Alarm Relay
Alarm exists for power, fiber link
Relay output with carry capacity 1A @ 24VDC
Mechanical
Certification
EMC
EMI
Immunity for
Heavy
Industrial
Environment
Emission for
Heavy
Industrial
Environment
EMS
(Electromagnetic
Susceptibility)
Protection Level
Free Fall
Vibration
Shock
Green
MTBF
Power Input
Redundant Dual Power 12, 24, 48 VDC
(9.6 ~ 60VDC)
Power
<3W
Consumption
Power Reversal Supported for power input
Protection
Over Current Protection : Signal Short Together
Protected
Terminal Block for Power and Alarm :
Terminal Block : V1+, V1-, V2+, V2-, Alarm NC, Alarm COM,
Alarm NO
Water & Dust
IP30 Protection, Fanless
Proof
Dimensions
106 x 38.6 x 142.1mm (D x W x H)
Mounting
DIN-Rail, or wall mounting (Optional)
Weight
TBD
CE
FCC Part 15 Subpart B Class A, CE
EN61000-6-2
EN61000-6-4
EN61000-4-2 ESD Level 3
EN61000-4-3 RS Level 3
EN61000-4-4 EFT Level 3
EN61000-4-5 Surge Level 3
EN61000-4-6 CS Level 3
IEC 60068-2-32
IEC 60068-2-6
IEC 60068-2-27
RoHS
TBD
www.ctcu.com / [email protected]
Specifications & design are subject to change without prior notice. Please visit CTC Union website for more details.
8-5
Industrial Serial Fiber Converter
▪▪Subbports protocol CAN 2.0A , CAN 2.0B, ISO 11898-2 standard
▪▪Extend serial transmission distance up to 2km, 30km
▪▪Redundant dual power inputs (12/24/48VDC)
▪▪Baudrate up to 1Mbps
▪▪Auto baudrate, no need to set baudrate
▪▪2.5KVrms isolation for CAN BUS port
▪▪CE, FCC, heavy industrial grade EMS, EMI, EN61000-6-2, EN61000-6-4 certified
▪▪Supports relay output for power or link failure warning
▪▪Hardened housing with IP30 protection
▪▪Fanless and DIN-Rail design for harsh industrial environment
▪▪120 ohm terminator selectable by DIP SW
Industrial Serial Fiber Converter
Application & Topology
Figure 1 : IFC-Serial-CAN Application for CAN BUS
Dashboard
IFC-Serial-CAN
CAN BUS
Fiber
CAN BUS
Sensor
80
IFC-Serial-CAN
Dashboard
PLC
(CAN Device)
80
IFC-Serial-CAN
Fiber
IFC-Serial-CAN
IFC-Serial-CAN
Dashboard
IFC-Serial-CAN
Fiber
CAN BUS
80
Dashboard
CAN BUS
Benefit:
PLC
(CAN Device)
Sensor
80
1. EMC/noise isolation, to reduce mutual interference between copper port device
2. Extend distance by fiber
3. Isolate CAN BUS failure
4. Achieve a reliable network environment
Figure 2 : Isolate CANBUS Failure
Failure
CAN BUS
Fiber Cable
CAN BUS
80
Sensor
Dashboard
80
PLC
PLC
(CAN Device)
(CAN Device)
IFC-Serial-CAN
Dashboard
Sensor
IFC-Serial-CAN
Figure 3 : Fiber Point to Point topology
Fiber
CAN BUS
IFC-Serial-CAN
Benefit:
1. Reduce mutual interference between serial port device
2. Extend distance by fiber
3. Achieve a reliable network environment
8-6
www.ctcu.com / [email protected]
Specifications & design are subject to change without prior notice. Please visit CTC Union website for more details.
CAN BUS
IFC-Serial-CAN
Industrial Serial Fiber Converter
Ordering Information
Serial
Model Name
Fiber
CAN BUS
Isolation
2.5KV
SC/ST
IFC-Serial-CAN
1
V
IFC-Serial-CAN-E
1
V
Power Input
Certification
Operating
Temperature
Redundant
EN61000-6-2
EN61000-6-4
CE
FCC
1
12/24/48VDC
V
V
V
1
12/24/48VDC
V
V
V
-10~60°C
-40~75°C
Temperature
Connector Connectivity
Type
Distance
Model Naming Rule
IFC
Industrial
Serial Fiber
Converter
Connector Type
SC, ST
Serial
Serial: IFC-Serial
CAN
E
CAN: CAN BUS
E: -40~75°C
Blank: -10~60°C
SC002
See below for more detail
Connectivity Distance
002: M/M 2km 030: S/M 30km
020A: 20KM Bidi mode A
020B: 20KM Bidi mode B
Mode A: TX 1310nm/RX1550nm Mode B: TX 1550nm/RX1310nm
Example:
IFC – Serial –CAN– □ – □□□□□
IFC – Serial – CAN – E– SC002
Package List
8
• Din Rail with screws
• Terminal block
Industrial Serial Fiber Converter
• IFC-Serial-CAN device
• Quickly installation guide
Optional Accessories
Wall Mount kit Accessories
IND-WMK01
Wall Mount kit for Industrial product, 184 x 30mm
www.ctcu.com / [email protected]
Specifications & design are subject to change without prior notice. Please visit CTC Union website for more details.
8-7
Industrial Serial Fiber Converter
IFC-FDC
RS-232/422/485 Daisy Chain Fiber Converter
IFC-Serial
RS-232/422/485 Fiber Converter
UL60950-1
EN61000-6-2
EN61000-6-4
PROFIBUS
These converters are capable of selecting interface modes for connection to RS-232 (3 wire), RS-485 (2 wire, half duplex) or RS-422/485
(4 wire, full duplex) and feature a three-way communication plus a second independent RS-232 communication channel. Additionally,
the terminal block offers an alarm relay contact and two redundant DC power inputs. IFC Series converters are also available in two
operating temperature ranges, a standard -10° to 60°C commercial temperature range and an extended -40° to 75°C range. With all
these specifically designed features, IFC Series are reliable and ideal solutions for keeping your industrial automation applications
running smoothly and continuously even in harsh environments. The product is protocol transparent that can be applied to
RS485/422/232 networks, such as MODBUS to achieve reliable network (See Figure 2).
Features
▪▪Supports 2 fiber link (IFC-FDC)
▪▪Supports 1 fiber link (IFC-Serial)
▪▪Supports dual channel communication, including Triple-Way communication, and Two-Way communication
▪▪Extend serial transmission distance up to 2km, 30km, 60km
▪▪Supports several topology , cable redundancy (Figure 3), ring redundancy (Figure 4), daisy chain (Figure 5), point to point (IFC-FDC)
▪▪Supports point to point (Figure 7) (IFC-Serial)
▪▪Redundant dual power inputs (12/24/48VDC)
▪▪Protocol transparent, suitable for all serial (RS485/422/232) transmission protocol, such as Modbus...
▪▪Baudrate up to 1024kpbs for serial port
▪▪Auto baudrate, no need to set baudrate
▪▪2.5KV isolation for serial port (RS485/422/232)
▪▪UL60950-1, CE, FCC, heavy industrial grade EMS, EMI, EN61000-6-2, EN61000-6-4 certified
▪▪Supports relay output for power or link failure warning
▪▪Hardened housing with IP30 protection
▪▪Fanless and DIN-Rail design for harsh industrial environment
▪▪Adjustable pull high/low resistor and terminator for RS-422/485 transmission
Specifications
FieldBus
Protocol
Data Flow
Optical
Interface
Fiber port
Topology
Electrical
Interface
8-8
Protocol applicable to all operations
available on RS485/422/232, such as
Modbus,…
Dual Channel
Both of Triple-Way and Two-Way
Communication Communication Way (Figure 1 or 6)
Connector
SC, ST
2 fiber ports (IFC-FDC)
Fiber Port
1 fiber port (IFC-Serial)
MM 2km, SM 30km, 60km
Fiber Type
Bidi 20KM
MM 1310nm, SM 1310
Wavelength
Bidi: Mode A : TX1310nm/RX1550nm
Mode B : TX1550nm/RX1310nm
Point to Point
Full duplex
Transmission
Ring
Full duplex, self-healing operation
Transmission
Protocol
transparent
Cable redundancy(Figure 3), ring redundancy(Figure 4),
daisy chain(Figure 5), point to point (IFC-FDC)
Point to point(Figure 7) (IFC-Serial)
RS-232(DB9), RS-422/RS-485(5 pin
Serial Port
terminal block)
Connector
RS-485 : 4, 2 wires, RS-422 : 4 wires
RS-485 direction Automatically detection
Serial port
50 to 1024kpbs
Baudrate
Auto baudrate, no need to set baudrate
Serial port
2.5KV isolation for serial signals
isolation
EMC/noise isolation, to reduce
mutual interference between serial
port device
Pull high resistor Selected by 10 position rotary switch
Pull low resistor Selected by 10 position rotary switch
120 ohm
Built-in 120 ohm terminator (Selected
terminator
by Dip Switch)
Environmental Operating
-10 ~ 60°C (IFC-FDC, IFC-Serial)
Temperature
-40 ~ 75°C (IFC-FDC-E, IFC-Serial-E)
Storage
-40 ~ 85°C
Temperature
Humidity
5 ~ 95% RH
LED Indications PWR1, PWR2, Alarm, Master, TD, RD, Fiber Link, Fiber2
Link (IFC-FDC only), Ring
Alarm Relay
Alarm exists for power, fiber link or ring protection
Relay output with carry capacity 1A @ 24VDC
Power
Redundant Dual Power 12, 24, 48 VDC
Power Input
(9.6 ~ 58VDC)
Power
6W (IFC-FDC)
Consumption
5W (IFC-Serial)
Power Reversal Yes
Protection
Over Current Protection : Signal Short Together Protected
Terminal Block for Power and Alarm :
Terminal Block : V1+, V1-, V2+, V2-, Alarm NC, Alarm COM,
Alarm NO
Mechanical
Water & Dust
IP30 Protection, Fanless
Proof
Dimensions
106 x 38.6 x 142.1mm (D x W x H)
Mounting
DIN-Rail, or wall mounting (Optional)
Weight
0.64kg (IFC-FDC) 0.63kg (IFC-Serial)
Certification
Safety
UL60950-1
EMC
CE
EMI
FCC Part 15 Subpart B Class A, CE
Immunity for
Heavy Industrial EN61000-6-2
Environment
Emission for
Heavy Industrial EN61000-6-4
Environment
www.ctcu.com / [email protected]
Specifications & design are subject to change without prior notice. Please visit CTC Union website for more details.
Industrial Serial Fiber Converter
Certification
Certification
EMS
EN61000-4-2 ESD Level 3
(Electromagnetic EN61000-4-3 RS Level 3
Susceptibility)
EN61000-4-4 EFT Level 3
Protection Level
EN61000-4-5 Surge Level 3
EN61000-4-6 CS Level 3
Free Fall
Vibration
Shock
Green
IEC 60068-2-32
IEC 60068-2-6
IEC 60068-2-27
RoHS
739,886 Hours (IFC-FDC)
847,029 Hours (IFC-Serial)
(MIL-HDBK-217)
MTBF
Application & Topology (IFC-FDC)
Figure 1 : Dual Channel Data Flow
Channel 1 : Triple Way
Channel 2 : Two Way
Isolation
Terminal Block
RS-422/485
TX/RX
CH 1
TX/RX
Fiber1/2
Logic
DB9
CH 2
8
RS-232 1
TX/RX
Industrial Serial Fiber Converter
SG common
RS-232 2
TX/RX
Figure 2 : Application for Modbus Network
0004
12
0004
12
5F
PLC
Sensor
HMI
Modbus
RTU
Digital
power meters
Modbus
RTU
Digital
power meters
HMI
Sensor
PLC
Fiber
Master
IFC-FDC
IFC-FDC
Modbus
RTU
0004
12
5F
Fiber Ring
Modbus
RTU
Message Server
5F
Digital
power meters
IFC-FDC
HMI
Sensor
PLC
IFC-FDC
IFC-FDC
Benefit:
Modbus RTU
1. EMC/noise isolation, to reduce mutual interference
between serial port device
5
2. Extend distance by fiber
Digital
3. Cable redundancy
power meters
4. Achieve a reliable network environment
0004
12
F
HMI
Sensor
PLC
Figure 3 : Fiber Cable Redundancy topology & application
Fiber Cable Redundant
RS485/422/232
RS485/422/232
IFC-FDC
IFC-FDC
www.ctcu.com / [email protected]
Specifications & design are subject to change without prior notice. Please visit CTC Union website for more details.
8-9
Industrial Serial Fiber Converter
Figure 4 : Fiber Ring Redundancy topology & application
IFC-FDC
IFC-FDC
RS-232/422/485
RS-232/422/485
Fiber
Master
Fiber Ring
RS-232/422/485
RS-232/422/485
IFC-FDC
IFC-FDC
IFC-FDC
RS-232/422/485
Figure 5 : Fiber Daisy Chain topology & application
IFC-FDC
IFC-FDC
IFC-FDC
IFC-FDC
RS-232/422/485
Fiber
Fiber
Fiber
OPC Server
RS-232/422/485
RS-232/422/485
RS-232/422/485
RS-232/422/485
Application & Topology (IFC-Serial)
Figure 6 : Dual Channel Data Flow
Isolation
Channel 1 : Triple Way
Channel 2 : Two Way
Terminal Block
RS-422/485
TX/RX
CH 1
TX/RX
Fiber
Logic
CH 2
DB9
RS-232 1
TX/RX
SG common
RS-232 2
TX/RX
Figure 7 : Fiber Point to Point topology & application
Fiber
RS485/422/232
IFC-Serial
Benefit:
1. Reduce mutual interference between serial port device
2. Extend distance by fiber
3. Achieve a reliable network environment
8-10
www.ctcu.com / [email protected]
Specifications & design are subject to change without prior notice. Please visit CTC Union website for more details.
RS485/422/232
IFC-Serial
Industrial Serial Fiber Converter
Dimensions
IFC-FDC
45.72
30.00
38.60
106.00
15.20
29.45
9.00
184.00
50.53
142.10
30.02
30.00
51.30
4.10
12.00
Side View
Front View
Rear View
DIN-Rail Kit View
8
Wall-Mount Kit View
(Optional accessory)
45.72
30.00
38.60
106.00
Industrial Serial Fiber Converter
IFC-Serial
15.20
29.45
9.00
184.00
50.53
142.10
30.02
30.00
25.40
4.10
12.00
Side View
Front View
Rear View
DIN-Rail Kit View
Wall-Mount Kit View
(Optional accessory)
Ordering Information
Model Name
Dual
Channel
Serial (ModBus or others)
RS232
RS422/485
Fiber
Isolation
2.5KV
SC/ST
Power Input
Daisy Chain
Redundant
Certification
Safety
UL60950-1
EN61000-6-2
EN61000-6-4
CE
FCC
IFC-FDC
V
2
1
V
2
V
12/24/48VDC
V
V
V
V
IFC-FDC-E
V
2
1
V
2
V
12/24/48VDC
V
V
V
V
IFC-Serial
IFC-Serial-E
V
2
1
V
1
12/24/48VDC
V
V
V
V
V
2
1
V
1
12/24/48VDC
V
V
V
V
Operating
Temperature
-10~60°C
-40~75°C
-10~60°C
-40~75°C
Model Naming Rule
Industrial
Serial Fiber
Converter
Connector Type
SC, ST
E
FDC
IFC
FDC : IFC-FDC
Serial: IFC-Serial
E: -40~75°C
Blank: -10~60°C
SC002
See below for more detail
Connectivity Distance
002: M/M 2km 030: S/M 30km 050: S/M 50km
020AB: 20KM Bidi (20KM 1x mode A + 1x Mode B) (for IFC-FDC )
020A: 20KM Bidi mode A (for IFC-Serial )
020B: 20KM Bidi mode B (for IFC-Serial )
Mode A: TX 1310nm/RX1550nm Mode B: TX 1550nm/RX1310nm
Example:
IFC – FDC – □ – □□□□□
IFC – FDC – E – SC002
Optional Accessories
Package List
• One device of the series
• Quickly installation guide
Connector Connectivity
Temperature Type
Distance
• Din Rail with screws
• Terminal block
Wall Mount kit Accessories
IND-WMK01
Wall Mount kit for Industrial product, 184 x 30mm
www.ctcu.com / [email protected]
Specifications & design are subject to change without prior notice. Please visit CTC Union website for more details.
8-11
Ethernet Serial Server
STE100A-232
RS232 Serial Server
STE100A-Serial
RS485/232 Serial Server
The IP Device Server provides the serial device server for hosts to control RS-232, 2 or 4 wire asynchronous RS-422/485 serial devices
located virtually anywhere through a TCP/IP or UDP/IP connection. The Device Server has the DB9 port connection on one side, and
a 10/100 Mbps Ethernet connection on the other side. It connects serial devices such as PLC, alarm sensors and PTZ camera control
to IP networks. Applications include industrial/factory automation, public safety and surveillance systems. The IP Device Server
Windows driver is designed to control the IP Serial Server devices. The driver installs a virtual COM on Windows which maps the virtual
COM port to the IP address of the IP Serial Server device across the network, enabling the Windows applications to access remote
serial devices over Ethernet. IP Device Server can function as a UDP or a server or client for TCP connection. The application scenarios
are direct IP mode, virtual COM mode, and paired mode.
Features
▪▪10/100Mbps Ethernet port
▪▪230.4kbps serial interface
▪▪TCP Server, TCP client, Virtual com mode, UDP
▪▪Supports for DHCP, HTTP, ICMP, ARP, IP, UDP, TCP
▪▪Support Virtual COM
▪▪Easy to use with Windows utility
▪▪2 Wire(half duplex) or 4 Wire(full duplex)RS-422/485(STE100A-Serial)
▪▪Configurable IEEE 802.3 DA/SA assignment
▪▪Flexible RS-232/422/485 Interface (STE100A-Serial)
▪▪Configuration by web browser
▪▪Low power consumption with 12VDC input
▪▪Wall mount , or Din Rail optional
Specifications
General
LED
OS supported
Serial Interface
Serial Connector
Baudrate
Data bits
Stop bits
Parity
Flow Control
Data Packing
Delimiter
LAN Interface
Communication
Modes
Ready, TP Link/Act, Data TX/RX
Windows XP / 2000 / 2003 / 2008 /
VISTA / WIN7 / WIN8
STE100A-Seria l : RS-232/422/485
STE100A-232 : RS-232
DB9 Male
110 to 230.4Kbps
5, 6, 7, 8
1, 1,5 for Data bits 5 mode; 1, 2 for data bits 6, 7, 8 mode
None, Even, Odd
None or RTS / CTS for RS-232
Full Duplex(4-Wire) or Half Duplex(2-Wire) for
RS-422/485
1, 2
Protocols
Management
Security
Power
Operating
Temperature
Storage
Temperature
Humidity
DIN rail mount
Panel mount
Dimensions
TCP, UDP, IP, ARP, ICMP, HTTP, DHCP
Web pages, Firmware upgrade
Password Access
12VDC external switching power adapter
0 ~ 60°C
-10 ~ 70°C
0 – 90% non-condensing
DIN-Rail Mounting Kit (Optional)
Yes
85.8 x 84.2 x 22mm (D x W x H)
with DIN-Rail Mounting Kit
CE, FCC
2,501,030 Hours (STE100A-232)
2,385,346 Hours (STE100A-Serial)
(MIL-HDBK-217)
Certifications
MTBF
RJ-45 connector, IEEE802.3 10/100Base-TX
TCP Server, TCP Client, Virtual COM mode, UDP
Application
STE100A-Serial
STE100A-Serial
0004
12
5F
Sensor
PLC
0004
12
RS-232/422/485
Digital
power meters
10/100Base-T Ethernet
UDP, TCP Server
5F
RS-232/422/485
Digital
power meters
UDP, TCP Client
Remote Host
PLC
Sensor
Local Host
IP Network
Ethernet
STE100A-Serial
0004
12
RS-485 2 Wire
5F
Digital
power meters
HMI
PLC
Relay Output
Sensor
8-12
www.ctcu.com / [email protected]
Specifications & design are subject to change without prior notice. Please visit CTC Union website for more details.
Ethernet Serial Server
Appearance
STE100A-232
STE100A-Serial
Power input 12 to 48VDC
Power input 12 to 48VDC
Load Default/Reset Button
Load Default/Reset Button
Ethernet RJ45 10/100Mbps
Ethernet RJ45 10/100Mbps
8
Ethernet Serial Server
RS-232
RS-232/422/485
Dimensions
STE100A-232
STE100A-Serial
Unit: mm (inch)
RS-232
RS-232/422/485
RS-232/422/485
Ordering Information
Model Name
STE100A-232
STE100A-Serial
Description
1-port RS232 device server with AC power adapter
1-port RS232/422/485 device server with AC power adapter
Package List
• One device of the series
• CD (VCOM, Manual)
• 12V DC Switching power adapter
• Rubber Foot
Optional Accessories
Terminal & Wall Mount Kit
STE100A-Serial-WT
STE100A-Serial DB9 wiring terminal
STE100A/DRK01
STE100A/RS232,STE100A/Serial DIN-Rail Mounting Kit
Industrial Power Supply
DC-APT/12V
DB9 Wiring Terminal
-48VDC to 12VDC Adapter - 0.83 Amp, 10 Watts , Output 12 VDC, Input -48VDC
STE100A-Serial-WT
(only for STE100A-Serial)
Din-Rail Mounting Kit
STE100A/DRK01
www.ctcu.com / [email protected]
Specifications & design are subject to change without prior notice. Please visit CTC Union website for more details.
8-13