Please read this installation manual completely before installing the product.
Installation work must be performed in accordance with the national wiring standards by authorized personnel only.
Please retain this installation manual for future reference after reading it thoroughly..
中文
Model type: NEW STANDARD REMOTE CONTROLLER
Model name: PREMTB100, PREMTBB10
ČEŠTINA
P/NO : MFL69312302
Rev.04_052217
www.lg.com
TIPS FOR SAVING ENERGY
2
IMPORTANT SAFETY INSTRUCTIONS
IMPORTANT SAFETY INSTRUCTIONS
Here are some tips that will help you minimize the power consumption when you use the air
conditioner. You can use your air conditioner more efficiently by referring to the instructions
below:
READ ALL INSTRUCTIONS BEFORE USING THE APPLIANCE.
•
•
•
•
•
•
Do not cool excessively indoors. This may consume more electricity.
Block sunlight with blinds or curtains while you are operating the air conditioner.
Keep doors or windows closed tightly while you are operating the air conditioner.
Adjust the direction of the air flow vertically or horizontally to circulate indoor air.
Speed up the fan to cool or warm indoor air quickly, in a short period of time.
Clean the air filter once every 2 weeks. Dust and impurities collected in the air filter may block the
air flow or reduce the cooling / dehumidifying functions.
Always comply with the following precautions to avoid dangerous situations and ensure peak
performance of your product
! WARNING
This symbol indicates potentially hazardous situation which, if not avoided could result in death or
serious injury.
! CAUTION
This symbol indicates a potentially hazardous situation which, if not avoided, may result in minor
or moderate injury.
! WARNING
Installation
• For electrical work, contact the dealer, seller, a qualified electrician, or an authorized service Center.
- Do not disassemble or repair the product. There is risk of fire, electric shock, explosion, equipment
malfunction, or injury.
• Request to the service center or installation specialty store when reinstalling the installed product.
- There is risk of fire, electric shock, explosion, equipment malfunction, or injury.
• Do not disassemble, fix, and modify products randomly.
- There is risk of fire, electric shock, explosion, equipment malfunction, or injury.
• The product shall be installed according to the national standards and local code.
• Apply totally enclosed noncombustible conduit in case of local building code requiring plenum.
• Use appropriate unit mounting procedures.
• Avoid direct sunlight.
• Avoid moist areas.
In-Use
• Do not place flammable objects close to the product.
- There is risk of fire, electric shock, explosion, equipment malfunction or injury.
For your records
Staple your receipt to this page in case you need it to prove the date of purchase or for warranty
purposes. Write the model number and the serial number here:
Model number :
Serial number :
You can find them on a label on the side of each unit.
• Do not allow product to get wet.
- There is risk of fire, electric shock, explosion, equipment malfunction or injury.
• Avoid dropping the product.
- There is risk of fire, electric shock, explosion, equipment malfunction or injury.
• If product gets wet, contact your dealer or authorized service center.
- There is risk of fire, electric shock, explosion, equipment malfunction, or injury. If the instructions
are not followed, it may cause death or severe injury of the user.
• Do not use sharp or pointed objects on product.
- There is risk of fire, electric shock, explosion, equipment malfunction or injury.
Dealer’s name :
Date of purchase :
• Do not touch or pull the lead wire with wet hands.
- There is risk of product breakdown or electric shock.
ENGLISH
TIPS FOR SAVING ENERGY
3
4
IMPORTANT SAFETY INSTRUCTIONS
• Do not clean using powerful detergents like solvent but use soft cloths.
There is risk of fire, electric shock, explosion, equipment malfunction or deformation.
• Do not press the screen using powerful pressure.
There is risk of product break-down or malfunction.
5
ENGLISH
! CAUTION
In-use
TABLE OF CONTENTS
TABLE OF CONTENTS
2
3
8
9
9
TIPS FOR SAVING ENERGY
IMPORTANT SAFETY INSTRUCTIONS
DESCRIPTION
READ BEFORE OPERATING
THE CONTROLLER
Menu Structure
14 DESCRIPTION OF THE OPERATION
14
14
15
15
16
17
17
Main screen
Menu screen
Setting screen
Popup screen
Monitoring / Sub function screen
Interface screen
Returning to the screen
18 OPERATION SETTING
18
18
19
20
21
22
23
24
25
On / Off
Operation mode
Cooling Operation
Heating Operation
Dry Operation
Fan Only Operation
AI / Auto operation
Dual setpoint auto operation
Power Cool Operation
26 OPERATION SETTING VENTILATOR
26
Operation mode
30 HOME LEAVE SETTING
30
31
Controlling Desired Temperature
Check Room Temperature
Hold
32 ADDITIONAL OPERATION –
VENTILATION
32
Additional operation
33 EXTERNAL EQUIPMENT
CONTROL SETTING
33
External equipment control
34 PLASMA PURIFICATION
SETTING
34
Plasma Purification
35 OVERRIDE CONTROL SETTING
35
Override control
36 MONITORING SCREEN
36
37
How to enter fine dust status screen
Fine dusts status
38 SUB FUNCTION SETTING
38
39
40
41
42
43
44
45
46
27 TEMPERATURE SETTING
27
28
Home leave (Unoccupied Mode)
31 HOLD SETTING
Sub function entrance and setting method
Energy Saving Setting
Plasma Purification Setting
Fan Auto Setting
Humidification setting
Electric Heater Setting
Robot Cleaning Setting
Ventilation kit Setting
Comfort Cooling Setting (air conditioner /
DX ventilator)
47 ZONE CONTROL SETTING
47
Zone Control
29 WIND SETTING
48 LOCK SETTING
29
29
29
48
48
Fan speed control
Fan speed control - ventilation
Air flow control
How to enter lock setting
Lock setting – all, on/off, mode, temperature range lock
6
TABLE OF CONTENTS
49
50
51
52
53
Timer entrance and setting method
Simple timer
Sleep timer
Turn-off Reservation
Turn-on Reservation
54 SCHEDULE SETTING
54
55
56
57
58
How to enter schedule
Daily Schedule
Schedules & Edit
Schedules & Edit – Add schedule
Exception day
59 ENERGY (air conditioner /
DX ventilator)
59
60
61
63
64
65
66
67
68
69
70
How to enter energy
Instantaneous power check
Energy consumption
Energy saving - Temperature Setback Timer
Energy saving - Time Limit Control
Energy setting - outdoor unit capacity setting
Energy setting - target instantaneous power
setting
Energy setting - target power consumption
Energy setting - target operation time
Energy setting - Alarm Popup Setting
Energy setting – Usage data initialization
71 FUNCTION SETTING
71
72
73
74
75
75
76
77
78
79
80
81
82
How to enter function setting
Function Setting
Vane angle control setting
Elevation grill setting
Robot cleaning setting
Auto dry setting
Filter sign check and initialization (air conditioner / DX ventilator)
Change temperature setting
Dead Band
Wi-Fi pairing setting
Zone Name setting
Override Set Time Setting
Home Leave Set Temperature Setting
83
83
84
85
86
87
88
89
90
Comfort cooling setting (air conditioner /
DX ventilator)
ODU Refrigerant Noise Reduction setting
(air conditioner / DX ventilator)
Defrost mode setting (air conditioner / DX
ventilator)
Smart load control(SLC) setting (air conditioner / DX ventilator)
Low noise mode time setting (air conditioner / DX ventilator)
Advanced fan speed “Auto” setting
Delay time (exclusive for ventilation)
Midnight air cooling (ventilation interface)
Human detection mode setting
92 USER SETTING
92
92
93
94
95
96
97
98
98
99
100
101
102
103
104
105
106
107
108
How to enter user setting
User Setting
Language setting
Setpoint Type Setting
Temperature unit setting
Screen saver timer setting
LCD brightness in idle setting
External device setting
External device use
External device types
On condition / Off condition
Date setting
Time setting
Summer time setting
Password setting
Schedule initialization
Theme setting
Humidity display
System restart
109 SERVICE SETTING
109
109
110
111
112
113
114
How to enter service setting
Service setting
Service contact
Model information (air conditioner / DX ventilator)
RMC Version Information
Error history
Open source license
115 INSTALLATION
115
117
Installation of Remote Controller
Group control
119 INSTALLATION METHOD
119
TO USE EXTERNAL DEVICE
146
Cable connection method to use external
device
147
120 AIR CONDITIONER AND
VENTILATION INTERFACE
121 INSTALLER SETTING
121
122
124
125
126
127
128
129
130
131
132
133
134
135
135
136
137
138
139
140
141
142
143
144
145
How to enter installer setting
Installer setting – air conditioner
Installer setting - ventilator
Test run setting (air conditioner / DX ventilator)
Central control address setting (air conditioner / DX ventilator)
ESP setting (air conditioner / general, DX
ventilator)
Temperature sensor(2TH) setting (air conditioner / DX ventilator)
Ceiling height setting (air conditioner)
Static pressure setting(air conditioner)
Remote controller master / slave setting (air
conditioner / General, DX ventilator)
Override Master/Slave setting (air conditioner / General, DX ventilator)
Dry contact mode setting (air conditioner /
DX ventilator)
Fixed air volume (air conditioner / DX ventilator)
Zone Type Setting(air conditioner)
Zone Number Setting(air conditioner)
Emergency heater setting (air conditioner)
Function control during group Control setting (air conditioner)
External devices of indoor unit setting (air
conditioner)
Expand of Temperature Range (air conditioner)
Indoor unit address verification (air conditioner / DX ventilator)
Static pressure step setting (air conditioner)
Guard timer(air conditioner)
148
149
150
151
152
153
154
155
157
158
159
160
161
162
163
164
Fan speed in Cooling thermal off (air conditioner)
Primary heater setting(air conditioner)
Air conditioner Fan operation interlocked
with ventilation setting (air conditioner)
Indoor unit Auto-Start setting (air conditioner / DX ventilator)
Occupancy duration time setting(air conditioner)
CN_CC setting (air conditioner)
CN_EXT setting (air conditioner / DX ventilator)
Outdoor unit function master setting (air
conditioner / DX ventilator)
Fan continuous operation setting (air conditioner)
Low Noise Mode Priority setting (air conditioner / DX ventilator)
Human detection sensor
Humidity sensing position (air conditioner)
ODU cycle priority (airconditioner)
Outdoor temp. for heating stages (air conditioner)
Estimated energy display (airconditioner)
Password initialization (air conditioner / general, DX ventilator)
Product direction (general ventilator)
Express ventilation priority (general , DX
ventilator)
Humidification of stand-alone ventilation
mode (general , DX ventilator)
Humidification of ventilation with heating
operation (DX ventilator)
Ventilation Fan Speed Alignment(DX ventilator)
165 GUIDE TO DIFFERENT
MODE OPERATION/OPEN
SOURCE SOFTWARE
165
165
7
Different mode operation
Open Source License Notice Information
ENGLISH
49 TIMER SETTING
TABLE OF CONTENTS
8
DESCRIPTION
READ BEFORE OPERATING THE CONTROLLER
READ BEFORE OPERATING THE CONTROLLER
Menu Structure
NEW STANDARD REMOTE CONTROLLER
Menu
Override
......................................................................................................................35
Fine Dust
......................................................................................................................36
Sub function
Energy Saving
Operation display
window
Back button
..............................................................................39
Plasma Purification ..............................................................................40
OK
Up/Down/Left/Right
Button
Fan Auto
..............................................................................41
Humidification
..............................................................................42
On/Off Button
Electric Heater
..............................................................................43
OK Button
Robot Cleaning
..............................................................................44
Ventilation Kit
..............................................................................45
Comfort Saving
..............................................................................46
Zone Control
Operation display window
Operation and Settings status display
Back button
When you move to the previous stage from the menu’s setting stage
Up/down/left/right button
When you change the menu’s setting value
OK button
When you save the menu’s setting value
On/Off button
When you turn ON/OFF the air conditioner
......................................................................................................................47
Lock
All Lock
..............................................................................48
On/Off Lock
..............................................................................48
Mode Lock
..............................................................................48
Set temp range lock ..............................................................................48
Timer
Accessories
Simple Timer
..............................................................................50
Sleep Timer
..............................................................................51
Turn-off reservation ..............................................................................52
Turn-on reservation ..............................................................................53
Schedule
Connecting cable
(1 EA)
Remote controller
fixing screws (4 EA)
User/Installation Manual
Daily Schedule
..............................................................................55
Schedules & Edit ..............................................................................56
Exception Day
..............................................................................58
ENGLISH
DESCRIPTION
9
10 READ BEFORE OPERATING THE CONTROLLER
READ BEFORE OPERATING THE CONTROLLER
...............................80
...............................81
Home Leave Set Temp ...............................82
Energy Consumption
Comfort Cooling
...............................83
Year-on-year Usage
..........................61
Weekly Usage
..........................61
Monthly Usage
..........................61
Defrost Mode
...............................84
Yearly Usage
..........................61
Smart Load Control
...............................85
ODU Refrigerant Noise ...............................83
Reduction
Low Noise Mode Time ...............................86
Energy Saving
Temp Setback Timer ..........................63
Time Limit control
Advanced fan speed
“Auto”
..........................64
...............................87
Delay Time(Ventilator) ...............................88
Energy Setting
Midnight Air Cooling
(Ventilator)
Outdoor Unit Capacity ..........................65
Human detection mode ...............................90
Target Instantaneous Power ................66
Target Power Consumption ................67
Target Operation Time ..........................68
Alarm Popup
..........................69
Usage Data Initialization ..........................70
Setting
...............................89
User
Language
...............................93
Setpoint type
...............................94
Temperature Unit
...............................95
Screen Saver Timer
...............................96
LCD Brightness In Idle ...............................97
Function
Vane Angle Control
..........................73
External Device
...............................98
Elevation Grill
..........................74
Date
.............................101
Robot Cleaning
..........................75
Time
.............................102
Auto Dry
..........................75
Summer Time
.............................103
Filter Sign
..........................76
Password
.............................104
Schedule Initialization
.............................105
Dead Band
..........................78
Theme
.............................106
Wi-Fi Paring
..........................79
Humidity display
.............................107
System Reboot
.............................108
Change Temperature ..........................77
ENGLISH
Zone Naming
Override Set Time
Energy
Instantaneous Power .........................................................................60
11
12 READ BEFORE OPERATING THE CONTROLLER
READ BEFORE OPERATING THE CONTROLLER 13
Service Contact
..........................110
Model Information
..........................111
RMC Version Information
..........................112
Error History
..........................113
Open Source License
..........................114
IDU Auto-Start
.............................146
Occupancy Duration Time
.............................147
CN_CC
.............................148
CN_EXT
.............................149
Installer
Test Run
.............................144
AC Fan Operation Interlocked .............................145
With Ventilation
ODU Function Master
.............................150
Fan Continuous Operation
.............................151
Low Noise Mode Priority
.............................152
..........................125
Central Control Address
..........................126
ESP
..........................127
Temperature Sensor(2TH)
..........................128
Ceiling Height Selection
..........................129
Static Pressure
..........................130
RMC Master/Slave
Human detection sensor
.............................153
Humidity sensing position
.............................154
ODU cycle priority
.............................155
..........................131
Outdoor temp. for heating
stages
.............................157
Override Master/Slave
..........................132
Estimated energy display
.............................158
Dry Contact Mode
..........................133
Password Initialization
.............................159
Fixed Air Volume
..........................134
Zone Type
..........................135
Zone Number
..........................135
Emergency Heater
..........................136
Humidification of stand-alone .............................162
ventilation mode(Ventilator)
Function Control During Group ..........................137
Control
Humidification of ventilation with .............................163
heating operation(Ventilator)
External devices of indoor unit ..........................138
Ventilation Fan Speed Align- .............................164
ment(Ventilator)
Product direction(ventilator) .............................160
Express ventilation
priority(Ventilator)
Expand of Temperature Range ..........................139
IDU Address Verification
..........................140
Static Pressure Step
..........................141
Guard Timer
..........................142
Fan Speed In Cooling Thermal ..........................143
off
Notice
• Some functions may not work in some indoor unit products.
.............................161
ENGLISH
Primary Heater
Service
14 DESCRIPTION OF THE OPERATION
DESCRIPTION OF THE OPERATION 15
Setting screen
Select the category to set using [∧,∨(up/down)] button.
Main screen
In each detail screen of the menu, as in the box in the left figure,
when “<,>” icons are displayed at the same time, you can immediately apply the setting value by pressing [<, >(left/right)]
button.
※ For the values that can be set in each category, refer to the
detail manual for each function.
In the main screen, press [<, >(left/right)] button to select the category to set, and you can control by pressing [∧,∨ (up/down)] button.
< Air conditioner main screen>
<Genernal Ventilation main
screen>
In each detail screen of the menu, as in the box in the left figure,
if only “>” icon is displayed, you can move to the detail setting
screen by pressing [>(right) or OK] button.
※ For the values that can be set in each category, refer to the
detail manual for each function.
<Dx Ventilation main screen>
Menu screen
In the main screen, press [<, >(left/right)] button to select the menu and press [OK] button to
move to menu screen.
Popup screen
The toast message is the message displayed at the bottom of the screen when an operation is
turned On/Off or if a function is set / cancelled.
The popup message is mainly displayed when an error occurred in the product.
In the menu screen, press [<, >(left/right)] button to select the category to set, and press [OK]
button to move to the detail screen.
< Toast message >
< Popup message >
ENGLISH
DESCRIPTION OF THE OPERATION
16 DESCRIPTION OF THE OPERATION
DESCRIPTION OF THE OPERATION
Interface screen
In the main screen, you can enter the monitoring / sub function screen by pressing [Back] button
and then pressing [<, >(left/right)] button.
- In the monitoring screen, you can check the indoor temperature and outdoor unit monitoring information.
- In the sub function screen, you can turn on or off the sub function supported by the product.
Select the product (air conditioner or ventilation) to set using [<, >(left/right)] button.
When you control the air conditioner and the ventilation product
with one remote controller, the screen is displayed as in the side
figure. You can set the air conditioner by pressing [<(left)] button and pressing [OK] button to move to the air conditioner
screen.
When you control the air conditioner and the ventilation product
with one remote controller, the screen is displayed as in the side
figure. You can set the ventilation by pressing [>(right)] button
and pressing [OK] button to move to the ventilation screen.
Returning to the screen
In the main screen, after moving to the category by pressing [<, >(left/right)] button, if there is no
remote controller operation, after 10 seconds, it returns to the main screen basic position. (basic
position: indoor temperature display part)
In the screens except the main screen, if there is no remote controller operation for 1 minute, it
moves to the main screen.
ENGLISH
Monitoring / Sub function screen
17
18 OPERATION SETTING
OPERATION SETTING 19
Cooling Operation
On / Off
Cooling operation’s minimum setting temperature is 18°C (16°C).
For some types of the indoor units, the desired temperature can be controlled in the units of 1°C
or 0.5°C.
Air conditioner and ventilator will be turned on or off.
Press the remote controller’s
(On/Off) button.
- If the product is in operation, On/Off button will be illuminated.
If the product is in off, On/Off button backlight will be off.
- Set the desired temperature lower than the indoor temperature.
- Indoor temperature is displayed on the default screen of the remote controller.
- If the setpoint is set higher than the room temperature, then the unit will remain in the cool
mode but will not begin to cool unit the room temperature exceeds the setpoint.
- If you unit is operating in cooling mode and you press the [On/Off] button the cooling operation
will shut off.
Operation mode
You can easily control the desired operation mode.
In the main screen, press [<,>(left/right)] button to select the operation mode or home leave or
hold category, and press [∧,∨(up/down)] button to set the operation mode.
※Some products may not support some operation modes.
Mode
Description
Cool
Cool the room to the desired temperature.
Dry
It removes the moisture with cooling.
Heat
Heats the room to the desired room temperature.
AI / Auto
Fan
Power Cool
The product automatically provides the appropriate fan speed based on
the temperature of the room.
Fan only operation, no cooling or heating.
It provides strong cooling in short time.
What is 3 minute delay function?
After the cooling stops, when the product is started right away, the reason that the cold
wind does not come out is that it is the function to protect the compressor.
The compressor starts after 3 minutes and the cold wind comes out.
!
NOTE
The compressor starts after 3 minutes and the cold wind comes out.
In the cooling operation, you can select the desired temperature in the range of 18°C ~ 30°C
(16°C ~ 30°C).
The favorable temperature difference between the indoor temperature and the outdoor
temperature is 5°C.
For some types of the indoor units, you can select the desired temperature in the range of
16°C ~ 30°C.
ENGLISH
OPERATION SETTING
20 OPERATION SETTING
OPERATION SETTING 21
Dry Operation
The heating operation’s minimum setting temperature is 16°C.
For some types of the indoor units, the desired temperature can be controlled in the units of 1°C
or 0.5°C.
Dry operation’s initial fan speed is “Low”.
Dry operation does not have a separate desired temperature.
- Set the desired temperature higher than the indoor temperature.
- Indoor temperature is displayed on the default screen of the remote controller.
- When the desired temperature is set lower than the indoor temperature, warm air doesn't
come out, but for some products, the fan will recirculate room air, or stop altogether.
- If you unit is operating in heating mode and you press the [On/Off] button the heatling operation
will shut off.
- If you unit is operating in dehumidification mode and you press the [On/Off] button the dehumidification operation will shut off.
!
NOTE
If you use it in the rainy season, or when the humidity is high, you can have both the
effective dehumidification and cooling operation at the same time.
!
NOTE
In the heating operation, you can select the desired temperature in the range of 16°C ~ 30°C.
Heating operation is operated only in cooling/heating model. The heating is not operated in
cooling exclusive model.
ENGLISH
Heating Operation
22 OPERATION SETTING
OPERATION SETTING 23
AI / Auto operation
Fan only operation’s initial wind strength is “High”.
Fan only operation does not have a separate desired temperature.
Auto operation’s initial desired temperature is 25°C.
The cooling exclusive model’s initial desired temperature is “It’s Fine”.
Cooling/heating model’s desired temperature can be controlled in the units of 1°C or 0.5°C.
For cooling exclusive model, the value can be controlled from “hot” stage to “cold” stage.
- Hot
- A little hot
- It’s fine
- A little cold
- Cold
- If you unit is operating in fan only mode and you press the [On/Off] button the the unit will stop.
- If you unit is operating in ai/auto mode and you press the [On/Off] button the ai/auto operation
will shut off.
!
NOTE
It provides the Fan only operation without temperature control, with recirculation of indoor
air.
!
NOTE
If the product is a cooling/heating model, in the auto operation, the desired temperature can
be selected in the range of 18°C ~ 30°C.
If it does not operate as you wish, select another operation mode.
ENGLISH
Fan Only Operation
24 OPERATION SETTING
OPERATION SETTING 25
Power Cool Operation
The indoor unit automatically manages room temperature with extended heating and cooling setting temperature ranges.
Dual setpoint auto mode can be set in the USER SETTING. This is recommended in North America region.
Power cooling quickly lowers the indoor temperature.
Desired temperature: 18°C
Fan speed : Power fan speed
fan direction: Current fan direction
- During the power cooling, if fan speed or desired temperature is changed, the power cooling is
cleared, and it operates in the cooling operation mode.
- During the power cooling, if you press [On/Off] button, the power cooling operation stops, and
when you press [On/Off] button again, it operates in the cooling operation mode.
!
NOTE
• Auto heating function only operates on cooling and heating models.
• Auto heating function doesn’t operate on cooling only models.
• When remote controller has a connection with indoor unit that does not support 'dual
setpoint', thermal operation function of indoor unit is replaced with ON/Off control from the
wired remote, when the user sets target temperatures in the below ranges.
- cooling target temp. range : 87~99 °F (30.5~37.5 °C)
- heating target temp. range : 40~59 °F (4~15.5 °C).
ENGLISH
Dual setpoint auto operation
26 OPERATION SETTING - VENTILATOR
TEMPERATURE SETTING 27
ENGLISH
OPERATION SETTING - VENTILATOR
TEMPERATURE SETTING
Operation mode
Controlling Desired Temperature
Ventilation (general and direct cooling type ventilation) operation mode supports the following operation modes.
※Some products may not support some operation modes.
You can easily control to the desired temperature.
• In the main screen, press [<,>(left/right)] button to select the desired temperature category,
and press [∧,∨(up/down)] button to set the desired temperature.
- In the cooling, heating, and AI/auto mode, the desired temperature control is possible.
Mode
Auto
Classification
Description
It measures the ventilation system’s indoor temperature and the outdoor temperature for the automatic operation in the optimal ventilation mode state.
It is the mode of ventilation with both supply/discharge
Ventilation operation
through the heat exchanger. It is adequate to use in
Heat Exchange mode – commonly
summer/winter where the indoor/outdoor temperature
supported by ventiladifference is big.
tion products
It is the ventilation where the exhausted air is ventilated
without going through the exchanger. It is adequate to
Bypass
use in spring/fall or when the indoor contamination is
severe.
Cool
Heat
Auto
Stop
Cools down the room to desired temperature.
Air conditioner opera- It provides warm air to the room.
tion mode – supports
The product automatically provides the appropriate fan
direct cooling type
speed based on the temperature of the room.
ventilation
Mode
Cool
Heat
If the desired temperature is lower than the indoor temperature, the heating is not performed.
Set the desired temperature higher than the indoor temperature.
You can select in the range of 16°C ~ 30°C.
It stops the product’s air conditioner operation.
In the main screen, press [<,>(left/right)] button to select the operation mode category, and press
[∧,∨(up/down)] button to set the operation mode.
AI / Auto
!
Description
If the desired temperature is higher than the indoor temperature, the
cooling is not performed.
Set the desired temperature lower than the indoor temperature.
You can select in the range of 18°C ~ 30°C (16°C ~ 30°C).
For cooling/heating product, you can select in the range of 18°C ~ 30°C.
For cooling exclusive product, you can select Hot, A little hot, Adequate,
A little Cold, and Cold.
NOTE
The favorable temperature difference between the indoor temperature and the outdoor
temperature is 5°C.
※The direct cooling type ventilation’s air conditioner operation mode is composed separately
from the ventilation operation mode.
28 TEMPERATURE SETTING
WIND SETTING 29
WIND SETTING
You can check the current indoor temperature.
• In the remote controller’s the main screen, you can check the indoor temperature.
Fan speed control
From the main screen, press [<,>(left/right)] button to select the fan speed category, and press
[∧,∨(up/down)] button to set the fan speed control the desired fan speed.
- It circulates in the order of Slow ↔ Low ↔ Medium ↔ High ↔ Power ↔ Auto.
※For some product some fan speed may not be available.
Fan speed control - ventilation
!
NOTE
The temperature distribution in the remote controller installation space is not uniform, so
there can be a little difference between the temperature you actually feel and the remote
controller’s room temperature display
According to Control type setting value
• Single setpoint
Fahrenheit: 52~99 °F
- below 52 °F: display ‘LO’
- over 99 °F: display ‘HI’
Celsius: 10.5~39.5 °C
- below 10.5 °C: display ‘LO’
- over 39.5 °C: display ‘HI’
• Dual setpoints
Fahrenheit: 34~99 °F
- below 34 °F: display ‘LO’
- over 99 °F: display ‘HI’
Celsius: 0.5~39.5 °C
- below 0.5 °C: display ‘LO’
- over 39.5 °C: display ‘HI’
- For indoor temperature below 50 °F (10 °C), the value perceived by the Thermostat(with
cable) is displayed.
You can easily control the desired fan speed.
• In the main screen, press [<,>(left/right)] button to select the fan speed category, and press
[∧,∨(up/down)] button to set the fan speed.
- It circulates in the order of low ↔ high ↔ power ↔ auto.
※The auto Fan can be used only when the air contamination (CO2) sensor is installed.
Air flow control
You can easily control the desired air flow
• In the main screen, press [<,>(left/right)] button to select the air flow category, and press
[∧,∨(up/down)] button to set the air flow.
- It circulates in the order of Off ↔ Up/Down swing ↔ Left/Right swing ↔ Up/Down/Left/Right
swing ↔ Swirl ↔ Indirect wind ↔ Direct wind↔Human detection direct wind↔Human detection indirect wind.
• Because of location of Temperature sensing, the real room temperature and the this
displayed value can be different.
※For some product some air flow settings may not be available.
ENGLISH
Check Room Temperature
30 HOME LEAVE SETTING
HOLD SETTING 31
HOLD SETTING
Home leave (Unoccupied Mode)
Hold
The "Home Leave" function enables proper operation of indoor unit when a space is left for a period of time.
This feature can only be used when Control type setting is set to the Dual Set Point Control
mode
User can use this function when they want to manage indoor unit as home leave control mode
only.
!
NOTE
User can not change indoor unit status with wired remote controller while set 'home leave
mode' except for 'home leave mode' release control.
• Home leave mode will be released if indoor unit operation was changed by commands of
other controllers(central controller, drycontact and wireless remote controller).
• When occupied schedule event occurs while operate a home leave mode, home leave
mode will be released and indoor unit status follow the occupied schedule event.
• Indoor unit operation change as below when the home leave mode is released.
- The setpoints and operation mode values are reflected in the control events of the
scheduled events that are currently applied.
- If there are no schedule events, the setpoint shall be applied as last setpoints before the
home leave operation.
- If there are no setpoints before the 'home leave' operation(dehumidification or fan mode),
default values will be applied to the setpoints.
- Default values : dual setpoint auto , heat 60 °F(16 °C), cool 86 °F(30 °C)
!
NOTE
Can not change indoor unit status with wired remote controller while set ‘hold mode' except
for ‘hold mode' release control.
• Hold mode will be released if indoor unit operation was changed by commands of other
controllers(central controller, drycontact and wireless remote controller).
• A scheduled event is not applied to the indoor unit during a hold mode, even if a scheduled
event is set.
ENGLISH
HOME LEAVE SETTING
32 ADDITIONAL OPERATION –VENTILATION
EXTERNAL EQUIPMENT CONTROL SETTING 33
EXTERNAL EQUIPMENT CONTROL SETTING
Additional operation
External equipment control
You can change the additional operation of the ventilation product.
• In the main screen, press [<,>(left/right)] button to select the additional operation category, and
press [∧,∨(up/down)] button to set the additional operation.
It is the function to set the contact point output of the external equipment control mode.
• In the main screen, press [<,>(left/right)] button to select the external equipment control category, and press [∧,∨(up/down)] button to set the contact point output.
Additional Operation
Description
Mode
On
When it is set to “On”, it always performs the contact point output.
Fast
It ventilates in short period of time.
It is the function to operate the ventilation function more efficiently
through the express setting which is an additional operation of the ventilation product.
Off
When you set it to “Off”, it does not perform the contact point output in
any case.
Auto
When it is set to “auto”, the contact point output is decided according to
the user setting’s external equipment logic setting value.
Energy saving
!
It performs the energy saving function while ventilating efficiently.
NOTE
The general ventilation and the direct cooling type ventilation’s additional operation are the
same.
The ventilation product’s additional functions (air cleaning / heater / humidification / fan auto)
setting methods are the same as the air conditioner.
!
Description
NOTE
Please use the corresponding function when the external equipment is actually connected.
When the external equipment is not set, please maintain “Off” status.
For the detail external equipment control condition setting, refer to the user setting - external
equipment logic setting.
ENGLISH
ADDITIONAL OPERATION –VENTILATION
34 PLASMA PURIFICATION SETTING
OVERRIDE CONTROL SETTING 35
OVERRIDE CONTROL SETTING
Plasma Purification
Override control
It cleans and makes pleasant indoor air.
1. Plasma Purification - single operation
If plasma purification is turned on in operation Off state, plasma purification single operation is
performed.
In dual setpoint setting, wired remote controller can manages indoor unit status based on programmed control events which have occupancy option.
Override control function switches between ‘occupied’ and ‘unoccupied’, and vice-versa.
User can set timer option which can return to original schedule event in override function menu.
OK
In case of plasma purification single operation, it operates in fan mode / automatic wind state,
and the wind direction operated before the plasma purification single operation is turned off.
There are 3 ways to end the plasma purification single operation.
1) Input of On/Off button during plasma purification single operation
2) Select plasma purification OFF
3) Change operation mode during plasma purification single operation
2. Plasma purification - additional operation
!
NOTE
• If mode is changed during plasma purification single operation, it is switched to the air
cleaning additional operation.
• Air cleaning operation may not be displayed or performed in some products.
!
NOTE
• If there are no 'occupied' schedule event when operate 'override' control, wired remote
controller change indoor unit operation as below default setting value.
- operation mode : Auto
- target temperature : 86 °F(30 °C)(cool), 60 °F(16 °C)(heat)
• If there are no ‘unoccupied' schedule event when operate 'override' control, wired remote
controller change indoor unit operation as 'home leave' mode default value.
- operation mode : Auto
- target temperature: 'home leave' target temperature.
• If wired remote controller received command from other controller, ‘Override’ operation will
be released.
• When schedule event occurs while operating an override mode, override mode will be released and indoor unit status follow the schedule event.
ENGLISH
PLASMA PURIFICATION SETTING
36 MONITORING SCREEN
How to enter fine dust status screen
• In the main screen, press [Back] button to move to monitoring/additional functions screen, and
press [<, > (left/right)] button to move to fine dust status screen. (Method 1)
Fine dusts status
It is the function to monitor dust value measured by the dust sensor mounted inside the air conditioner.
• In the fine dust status screen, you can check fine dust, ultra fine dust, and super ultra fine dust
concentration values.
• The overall index displays the worst dust status value among the three dust status values.
• In the menu screen, press [<, > (left/right)] button to select the fine dust screen category, and
press [OK] button to move to the fine dust status screen. (Method 2)
!
NOTE
• The fine dust status may not be displayed in some products.
• Fine dust status can be checked only when the product is in operation.
ENGLISH
MONITORING SCREEN
MONITORING SCREEN 37
38 ADDITIONAL FUNCTION SETTING
ADDITIONAL FUNCTION SETTING 39
Energy Saving Setting
Sub function entrance and setting method
The energy saving cooling function is the function to control the desired temperature during the
cooling operation to improve the comfort of the user and to improve the power saving performance.
In the menu screen, press [<,>(left/right)] button to select the sub function category, and press
[OK] button to move to the sub function setting list screen.
In the sub function setting list screen, if you press [<, >(left/right)] button, you can turn on/off the
corresponding sub function. (method 1)
In the main screen, press [Back] button to move to the monitoring/sub function screen, and press
[<,>(left/right)] button to move to the sub function screen. In the sub function screen, select the
sub function category to set, and if you press [OK] button, you can turn on/off the corresponding
function. (method 2)
!
NOTE
The energy saving function is an additional function, and it may not be displayed/operated in
some products.
The energy saving function is possible only when the product is in the cooling operation.
ENGLISH
SUB FUNCTION SETTING
40 ADDITIONAL FUNCTION SETTING
ADDITIONAL FUNCTION SETTING 41
Fan Auto Setting
It makes the indoor air clean and pleasant.
Select fan operation after performing thermal control of indoor units.
If set to 'ON', fan operation keeps on after thermal operation of indoor units.
!
NOTE
The air cleaning function is an additional function, and it may not be displayed/operated in
some products.
The air cleaning function is possible only when the product is in operation.
If you want air cleaning single operation, set air cleaning in the wind only operation.
!
NOTE
The fan auto function is an additional function, and it may not be displayed/operated in some
products.
ENGLISH
Plasma Purification Setting
42 ADDITIONAL FUNCTION SETTING
ADDITIONAL FUNCTION SETTING 43
Electric Heater Setting
It is the function to activate the humidifier installed in the product when the indoor air is dry.
It is the function to reinforce the heating capability by turning on the electric heater during the
heating operation.
!
NOTE
The humidification function is an additional function, and it may not be displayed/operated in
some products.
!
NOTE
It can be set only in the heating operation.
The heater function is an additional function, and it may not be displayed/operated in some
products.
ENGLISH
Humidification setting
44 ADDITIONAL FUNCTION SETTING
ADDITIONAL FUNCTION SETTING 45
Ventilation kit Setting
Robot cleaning function is the function to automatically perform the filter cleaning with the
cleaner in the product when the air conditioner is used for certain period of time.
Function enables operation of an optional ventilation kit with indoor units
!
NOTE
It can be set 30 seconds after the operation stopped.
The robot cleaning function is an additional function, and it may not be displayed/operated in
some products.
!
NOTE
The ventilation kit function is an additional function, and it may not be displayed/operated in
some products.
ENGLISH
Robot Cleaning Setting
46 ADDITIONAL FUNCTION SETTING
ZONE CONTROL SETTING 47
ZONE CONTROL SETTING
The comfort cooling is the function to automatically control the cooling strength to maintain the
pleasant feeling without turning off the product after the indoor temperature reached the desired
temperature.
Zone Control
A function to control zone with duct type indoor units.
Wired Remote controller can control maximum 8 zones.
OK
!
NOTE
The comfort cooling function is an additional function, and it may not be displayed/operated in
some products.
The comfort cooling function is only possible when the product is in the cooling operation.
!
NOTE
According to installation setting value
• If no function is supported this entry can not function.
• Old type
- Zone control is currently only available to monitor.
• New type(4zone or 8Zone)
- Any number of zones is installed is displayed on the screen can be controlled.
ENGLISH
Comfort Cooling Setting (air conditioner / DX ventilator)
48 LOCK SETTING
TIMER SETTING 49
ENGLISH
LOCK SETTING
TIMER SETTING
How to enter lock setting
Timer entrance and setting method
• In the menu screen, press [<,>(left/right)] button to select “lock setting” category, and press
[OK] button to move to the lock setting list screen.
• In the lock setting list, if you press [∧ ,∨(up/down)] button, you can turn on/off the corresponding lock function.
• In the menu screen, press [<,>(left/right)] button to select the timer category, and press [OK]
button to move to the timer setting list screen.
• In the timer setting list screen, press [∧,∨(up/down)] button to select the timer to set, and
press [OK] button to move to the detail screen.
• After setting the value, when you press [OK] button, the timer is activated.
• After setting the value, if you press [Back] button, the changed value will not be applied.
OK
OK
Lock setting – all, on/off, mode, temperature range lock
• It is the function to lock the button operation of the remote controller so that children or other
persons cannot use it without permission.
• It is the function to limit the desired temperature range that can be set in the wired remote controller.
Lock
All lock
On/Off lock
It locks the On/Off button operation of the remote controller.
Mode lock
It locks the operation mode button operation of the remote controller.
Temperature range
lock
!
Description
It locks all button operation of the remote controller.
It is the function that can limit the range of the desired temperature that
can be set in the wired remote controller.
- Single: Lower limit : 16~30 °C (60~86 °F)
Upper limit : 16/18~30 °C (60/64~86 °F)
- Dual : Cooling : 50~99 °F (10~37.5 °C)
Heating : 40~90 °F (4~32 °C)
NOTE
In the central controller, when the central control temperature range lock is set, the wired
remote controller’s temperature lock setting is cleared.
The temperature change by external equipment is reflected regardless of the remote
controller temperature range lock.
50 TIMER SETTING
TIMER SETTING 51
Sleep timer
You can easily set the timer in the range of 1~7 hours in the units of 1 hour.
Sleep timer is the function to operate the air conditioner in sleep mode before going to sleep for
certain hours and stop the operation.
OK
!
NOTE
If the product operation is On, the easy timer turns off the operation after the corresponding
time.
If the product operation is Off, the easy timer turns on the operation after the corresponding
time.
If the easy timer operation is turned On/Off before the timer operation, the set timer will be
cleared.
OK
!
NOTE
You can set the sleep timer while the product is in operation.
If the sleep timer operation is turned On before the timer operation, the set timer will be
cleared.
ENGLISH
Simple timer
52 TIMER SETTING
LOCK SETTING 53
Turn-on Reservation
The product is automatically turned Off at the set timer time.
The product is automatically turned On at the set timer time.
OK
!
NOTE
Even if the Turn-off Reservation operation is turned On/Off after the setting and before the
timer operation, the set timer is not cleared.
OK
!
NOTE
Even if the Turn-on Reseravation operation is turned On/Off after the setting and before the
timer operation, the set timer is not cleared.
ENGLISH
Turn-off Reservation
54 SCHEDULE SETTING
SCHEDULE SETTING 55
Daily Schedule
How to enter schedule
It is the function that can check the status of the timer (schedule) saved in the remote controller.
• In the schedule list, select the daily schedule status category, and press [OK] button to move to
the detail daily schedule status screen.
• In the menu screen, press [<,>(left/right)] button so select the schedule category, and press
[OK] button to move to the schedule setting list screen.
• In the schedule setting list screen, press [∧,∨(up/down)] button to select the menu to set, and
press [OK] button to move to the detail screen.
• You can use the remote controller’s [<,>(left/right)] button to check the timer information of
other dates.
• You can use the remote controller’s [∧,∨(up/down)] button to check the corresponding date’s
other timer information.
OK
• Select the timer information, and press [OK] button to move to the corresponding timer’s edit
screen.
!
NOTE
In the daily schedule status screen, even if the timer (schedule) is set, if the corresponding
date is designated as an exception date, the schedule will not be performed.
Less than 5 schedules per day is recommended.
ENGLISH
SCHEDULE SETTING
56 SCHEDULE SETTING
SCHEDULE SETTING 57
Schedules & Edit – Add schedule
It is the function that can check the status of the timer (schedule) saved in the remote controller.
Description of each stage in Add schedule
ENGLISH
Schedules & Edit
• In the schedule list, select the daily schedule status category, and press [OK] button to move to
the daily schedule status detail screen.
• You can use the remote controller’s [<,>(left/right)] button to check other date’s timer information.
You can check the set
timer’s operation information (operation
On/Off, operation
mode, desired temperature), timer time, period,
and day of week.
Stage 1. Period setting
Stage 2. Day of week setting
• You can edit the saved schedule’s timer information.
- Select the schedule to edit using [∧,∨(up/down)] button, and press [OK] button to move to
the edit screen.
Stage 3. Time setting
Stage 4. Operation setting
• Select the timer information, and press [OK] button to move to the corresponding timer’s edit
screen.
Add schedule is completed
< If schedule is changed >
< If schedule is deleted >
In ‘Stage 1’, it sets the period to perform the timer.
In ‘Stage 2’, it sets the day of week to perform the timer.
- You can select ‘Everyday / Weekend / Weekdays / Individual selection’.
In ‘Stage 3’, it sets the start time for the timer.
In ‘Stage 4’, it sets the timer operation information.
- If ‘Stop’ is selected, you cannot set the mode / temperature / fan speed.
When stages 1~4 are completed, along with the message of ‘schedule is added’, it moves to
View and edit schedule screen.
58 SCHEDULE SETTING
It is the function to automatically stop the operation on the set timer day.
• In the schedule list, select the exception day category, and press [OK] button to move to the
Exception day designation detail screen.
• In the exception day, you can check, and add/change/delete the exception day information
saved in the remote controller.
- To add an exception day, in the Exception day registration detail screen, designate
year/month/day, and press [OK] button to save the Exception day.
- Select the Exception day to edit using [∧,∨(up/down)] button, and press [OK] button to move
to the edit screen.
ENERGY (air conditioner / DX ventilator)
How to enter energy
• In the menu screen, press [<,>(left/right)] button to select the energy category, and press [OK]
button to move to the energy list.
OK
- In the exception day edit screen, you can check, delete/change the corresponding exception
day’s setting contents.
- When you change the exception day information, you need to save it after the change.
ENGLISH
Exception day
ENERGY 59
60 ENERGY
ENERGY 61
Energy consumption
It is the function that can check the product’s instantaneous power.
※There may be some error with the actual instantaneous power, so use it only for reference.
• In the energy list, select the “Instantaneous power” category, and press [OK] button to move
to the detail screen.
You can check the energy consumption (operation time, power consumption).
※There may be some error with the actual consumption, so use it only for reference.
• In the energy list, select the “energy consumption” category, and press [OK] button to move to
the detail screen.
OK
OK
• In the detail screen, press [<,>(left/right)] button to move to the power consumption and operation time screen.
• The target and the value of all can be set in the energy setting.
• The usage ratio compared to the target is the value expressed in current/target * 100.
※For how to set the energy, refer to the energy setting.
!
NOTE
Instantaneous power: It is the power currently used in the product.
<, >
ENGLISH
Instantaneous power check
62 ENERGY
ENERGY 63
List
Description
Power consumption
Operation time
You can see the power consumption compared to the same month
of the previous year.
You can see the operation time
compared to the same month of
the previous year.
Weekly usage
It displays the daily power consumption of the current month.
It displays the daily operation time
of the current month.
Monthly usage
It displays the weekly power consumption of the current month.
It displays the weekly operation
time of the current month.
Year On Year Usage
Yearly usage
Energy saving - Temperature Setback Timer
It is the function to return to the desired temperature after the set time after the product operation for energy saving.
• In the energy list, select “Energy saving” category, and press [OK] button to move to the energy saving screen.
• In the energy saving list, select “Temperature Setback Timer” category, and press [OK] button
to move to the Temperature Setback Timer setting screen.
It displays the monthly power con- It displays the monthly operation
sumption of the current year.
time of the current year.
OK
OK
• When it is set to On, you can set the time (10 minutes ~ 120 minutes, 10 minutes unit) and the
temperature (18°C ~ 30°C), and after the setting, when you press [OK] button, the set value is
saved.
• When the desired temperature setback timer setting is set to “On”, after the set time, the desired temperature is recovered to the set temperature.
!
NOTE
When it is set at the same time with the remote controller desired temperature range lock or
the central control temperature range lock, it may not return to the desired temperature.
ENGLISH
• Operation time unit is time (hr.), and power consumption unit is kWh.
• The power consumption display can be checked when it is connected to the indoor unit that
supports the power consumption information display function.
64 ENERGY
ENERGY 65
Energy setting - outdoor unit capacity setting
It is the function to stop the product operation after the set time after starting the product operation for the energy saving.
• In the energy saving list, select “time limit control” category, and press [OK] button to move to
the time limit control setting screen.
It is the function that can set the outdoor unit capacity.
• In the energy list, select “energy setting” category, and press [OK] button to move to the energy setting screen.
• In the energy setting list, select “outdoor unit capacity setting” category, and press [OK] button
to move to the outdoor unit capacity setting screen.
OK
OK
OK
OK
• In the detail screen, you can select “On/Off” to turn on and off the time limit control function.
When it is set to On, you can set the time (30 minutes ~ 540 minutes, 30 minutes unit), and
after the setting, if you press [OK] button, the set value is saved.
If you do not press [OK] button but press [Back] button, it moves to the list screen without saving the set value.
• If the time limit control is set to “On”, the operation stops after the set time.
!
NOTE
If it is set at the same time with the remote controller operation lock, the time limit control
will not be performed.
• In the detail screen, you can select “On/Off” to set the outdoor unit capacity. If it is set to On,
you can set the outdoor unit capacity (minimum 1kW), and after the setting, if you press [OK]
button, the set value is saved. If you do not press [OK] button but press “Back’ button, it
moves to the list screen without saving the set value.
• If the capacity setting is set to “On”, in the Instantaneous power screen, it is displayed as “all”
capacity.
• For the outdoor unit capacity, refer to the label of the outdoor unit product.
- For Single product and Multi product, the first 3 digits of the model name is the outdoor unit
capacity.
ex) For ABC1019…, it is 10.1kW
- For Multi-V product, the first 2 digits of the model name < 0.75 is the outdoor unit capacity.
ex) For ABCD101.…, it is 10 * 0.75 = 7.5kW
• For TMS users, refer to the all capacity displayed on TMS.
!
NOTE
According to the user input, there may be difference to the actual product capacity.
ENGLISH
Energy saving - Time Limit Control
66 ENERGY
ENERGY 67
Energy setting - target power consumption
It is the function that can set the Instantaneous power’s target value.
You can set the target value to find the power consumption status.
• In the energy setting list, select “target Instantaneous power” category, and press [OK] button
to move to the target Instantaneous power setting screen.
It is the function to set the target power consumption per hour.
• In the energy setting list, select “target power consumption” setting category, and press [OK]
button to move to the target power consumption setting screen.
OK
OK
OK
OK
• In the detail screen, you can select “On/Off” to set the target Instantaneous power.
If it is set to On, you can set the target Instantaneous power (minimum 1kW), and after the
setting, if you press [OK] button, the set value is saved.
- If the outdoor unit capacity is set, the maximum value is the outdoor unit capacity
- If the outdoor unit capacity is not set, the maximum value is 9999kW
If you do not press [OK] button but press “Back’ button, it moves to the list screen without
saving the set value.
• When the target Instantaneous power setting is set to “On”, in the Instantaneous power
screen, it is displayed as “all” capacity.
• In the detail screen, you can select “On/Off” to set the target power consumption.
When it is set to On, you can set the target power consumption (minimum 1kWh, maximum
100kWh), and after the setting, if you press [OK] button, the set value is saved.
If you do not press [OK] button but press “Back’ button, it moves to the list screen without
saving the set value.
• If the target power consumption setting is set to “On”, it is displayed as the energy
consumption’s power consumption target value.
- Daily target consumption: Weekly usage’s daily target
- Weekly target consumption: Monthly usage’s weekly target (daily target * 7)
- Monthly target consumption: Yearly usage’s monthly target (daily target * 31)
ENGLISH
Energy setting - target instantaneous power setting
68 ENERGY
ENERGY 69
Energy setting - Alarm Popup Setting
It is the function that can set the Instantaneous power’s target value.
You can find the power consumption status by setting the target value.
• In the energy setting list, select “target operation time” category, and press [OK] button to
move to the target operation time setting screen.
It is the function to set whether to use the target power consumption and the target operation
time notice popup window.
• In the energy setting list, select “target operation time” category, and press [OK] button to
move to the target operation time setting screen.
• In the notice popup list, select “target power consumption notice or target operation time notice” category, and press [OK] button to move to the detail setting screen.
OK
OK
OK
OK
OK
• In the detail screen, you can select “On/Off” to set the target operation time.
When it is set to On, you can set the target operation time (minimum 1hr. and maximum 24hr.),
and after the setting, if you press [OK] button, the set value is saved.
If you do not press [OK] button but press “Back’ button, it moves to the list screen without
saving the set value.
• If the target operation time setting is set to “On”, it is displayed as the energy consumption’s
operation time target value.
- Daily target : Weekly usage’s daily target
- Weekly target : Monthly usage’s weekly target (daily target * 7)
• You can set the notice popup as “daily”, “weekly”, “monthly”.
After the setting, if you press [OK] button, the setting is saved and moves to the previous
screen.
• When the target power consumption notice is set to “On, daily”
If the daily target power consumption’s 80%, 90%, 95%, and 100% power is used a day, the
popup screen appears.
• When the target operation time notice is set to “On, daily”
When the product is operated at the daily target operation time’s 80%, 90%, 95%, and 100%,
the popup screen appears.
- Monthly target : Yearly usage’s monthly target (daily target * 31)
!
NOTE
The popup message appears once every hour.
ENGLISH
Energy setting - target operation time
70 ENERGY
FUNCTION SETTING
FUNCTION SETTING
It is the function to initialize all of the power consumption and operation time information.
• In the energy setting list, select “consumption data initialization” category, and press [OK] button to move to the consumption data initialization setting screen.
How to enter function setting
OK
ENGLISH
Energy setting – Usage data initialization
To enter the menu displayed at the bottom, you need to enter the function setting menu as follows.
• In the menu screen, press [<,>(left/right)] button to select the setting category, and press [OK]
button to move to the setting list.
• In the setting list, select the function setting category, and press [OK] button to move to the
function setting list.
OK
OK
OK
• In the initialization popup screen, if you press “check” button, all previously saved power consumption and operation time are deleted.
71
72 FUNCTION SETTING
FUNCTION SETTING 73
Menu
Vane angle control setting
Description
Vane up/down control setting You can control the Air Direction angle.
Elevation grill setting It is the function to operate the Elevation grill for the indoor unit filter cleaning.
Robot cleaning setting
Robot cleaning function is the function to automatically perform the filter cleaning with the cleaner of the product when the air conditioner is
used for certain time period. It sets the manual or automatic operation
of the robot cleaning. You can set it 30 seconds after the stopping of
the operation.
Auto dry setting
Auto dry function is the function to remove mold and moisture by drying the inside of the indoor unit after the cooling operation and when
the product is turned off.
You can control the wind blowing angle.
- In the function setting list screen, press [∧,∨(up/down)] button to select the vane angle control
category, and press [OK] button to move to the up/down vane angle detail screen.
Filter status check and When it becomes the time for the indoor unit filter cleaning, the filter
initialization
cleaning display appears, and it is the function to remove the display.
Change Temperature
setting
Change Temperature is the function to set the temperature for the automatic conversion between cooling and heating according to the
temperature in AI operation mode.
Dead Band
When heating and cooling desired temperatures have been changed,
the set value will maintain a difference between the heating and cooling desired temperature.
Wi-Fi pairing
OK
It is the function to perform the pairing function of the Wi-Fi module
connected to the indoor.
Zone Name setting
Zone name settings allow you to select zone name.
Override set time setting When timed override is used, the set time will be a default value.
Home leave set temper- When customer operate as home leave mode, this setting temperaature setting
ture value will be applied.
Comfort saving setting
It is the function to set the outdoor unit Comfort saving operation
stage value.
ODU Refrigerant Noise It is the function to set the outdoor unit’s refrigerant noise reduction
Reduction setting
function.
Defrost Mode setting
It is the function to set the outdoor unit’s defrost mode operation.
It is the function to set the outdoor unit’s smart load control stage
Smart load control set- value. (Smart load control is the function to calculate the necessary
ting
performance with the indoor and outdoor air temperature and humidity and operate.)
Low noise mode time
setting
• In the detail screen, press [∧,∨(up/down)] button to select “individual control, overall control,
standard”.
• Use [<,>(left/right)] button to select the vane.
- The selected vane is moving. Check the moving vane.
• Press [∧,∨ (up/down)] button to select the desired wind angle, and press [OK] button to save
the setting.
- The wind angle’s setting range can be changed to 5 stages or 6 stages according to the product.
※If you do not press [OK] button, the selected wind angle will not be reflected.
Control
It is the function to set the start and end time of the outdoor unit’s
low noise mode operation.
Each
Advanced fan speed “Auto” It is the function to set the indoor unit’s fan auto by temperature.
All
Delay time setting (ex- It is the function to set the ventilation operation to start after the delay
clusive for ventilation) time.
Midnight air cooling
(ventilation interface)
It is the function to discharge indoor air and supply cool outdoor air
into the indoor during summer
nights to save energy.
Human detection mode It is the function to set the operation of human detection mode.
Standard
!
Description
It sets the vane angle individually.
It sets the vane angle of all the vanes of the product at once.
It sets the vane angle to the factory initialization state.
NOTE
For some product types, there are products with only 1 or 2 vanes.
ENGLISH
Function Setting
74 FUNCTION SETTING
FUNCTION SETTING 75
Robot cleaning setting
It is the function to operate the Elevation grill for the indoor unit filter cleaning.
- While the product operation is stopped, if you use [<,>(left/right)] button to select the setting
value, the grill operation status changes.
Robot cleaning function is the function to perform the automatic filter cleaning with the cleaner
of the product when the conditioner is used for certain period of time. It sets the manual or automatic operation of the robot cleaning.
- It can be set 30 seconds after the operation stop.
• You can use [<,>(left/right)] button to set the following setting values as follows.
Value
Up
!
Description
Stops the movement of the Elevation grill
Down
Lowers the Elevation grill toward the floor
NOTE
The Elevation grill setting function may not work in some products.
Description
Auto
It automatically performs the robot cleaning when the accumulated indoor unit operation time passes 30 hours
Manual
Raises the Elevation grill toward the product
Stop
Value
!
It manually performs the robot cleaning.
NOTE
The robot cleaning setting function may not work in some products.
Auto dry setting
Auto dry function is the function to remove mold and moisture by drying inside the indoor unit
after the cooling operation and when the product is turned off.
• You can use [<,>(left/right)] button to set the following setting values as follows.
Value
Use
Not Use
!
Description
Use auto dry function
Not use auto dry function
NOTE
Auto dry setting function may not work in some products.
ENGLISH
Elevation grill setting
76 FUNCTION SETTING
FUNCTION SETTING 77
Change temperature setting
Change Temperature is the function to set the automatic Change Temperature between cooling
and heating operation according to the temperature in AI operation mode.
• In the function setting list, select the Change Temperature category, and press [OK] button to
move to the detail screen.
OK
OK
Value
1~7°C(Default : 2°C)
It is the function that can be used only in cooling/heating product.
Filter sign
Good
Description
Usage time is 70% or less
Normal
Usage time is 71~80%
Caution
Usage time is 81~99%
Bad
Usage time is 100%
- When it becomes time to the filter clean, “Filter cleaning or replacement is required.” message
is displayed. Enter the Filter sign check and initialization detail screen.
- If the product has the function to display the time remaining until the filter cleaning, even if the
filter cleaning message is not displayed, you can enter the Filter sign check and initialization.
- If there is a remaining time display function, when you enter the Filter sign detail screen, you
can see the consumption and the remaining time.
!
NOTE
• Some products have a Filter Time Remaining function that can be accessed with Filter Sign
check.
• Dirty filters will increase the cost to cool or heat the conditioned space.
• The filter check message is cleared after certain time without a separate clearing.
Example of using Change Temperature
Condition
1) Mode: AI mode
2) temperature: 22°C
3) Change Temperature: 3°C → Change Temperature 3°C difference
※In case of the above conditions, it operates as in the graph.
Temp(ഒ)
‫ڸ‬
‫ڸ‬
25ഒ
‫ ڸ‬: Cooling operation start
‫ ڹ‬: Heating operation start
22ഒ
19ഒ
‫ڹ‬
!
NOTE
The Change Temperature setting function may not work in some products.
ENGLISH
Filter sign check and initialization (air conditioner / DX ventilator)
When it becomes the time for the indoor unit filter cleaning, the filter cleaning message appears,
and it is the function to remove the message.
• In the function setting list, select the Filter sign check and initialization category, and press [OK]
button to display the detail screen.
78 FUNCTION SETTING
FUNCTION SETTING 79
Wi-Fi pairing setting
Dead Band function is used with a dual setpoint mode.
When heating and cooling desired temperatures have been changed, the set value will maintain a
difference between the heating and cooling desired temperature.
• In the function setting list, select the dead band category, and press [OK] button to move to the
detail screen.
It is the function to perform the pairing function of the Wi-Fi module connected to the indoor unit.
• In the function setting list, select the Wi-Fi pairing category, and press [OK] button to move to
the detail screen.
- After selecting “Apply”, if you press [OK] button, the Wi-Fi pairing popup window is created,
select “check” and press [OK] button to request the Wi-Fi pairing.
OK
OK
!
NOTE
Dead Band function only can use in dual setpoint mode.
• When changing the desired cooling temperature, in case of that the difference with the
heating temperature becomes lesser than its minimal value of difference, it lowers the
desired heating temperature automatically.
• When changing the desired heating temperature, in case of that the difference with the
heating temperature becomes lesser than its minimal value of difference, it raises the
desired cooling temperature automatically.
!
NOTE
The Wi-Fi setting function may not work in some products.
ENGLISH
Dead Band
80 FUNCTION SETTING
FUNCTION SETTING 81
Override Set Time Setting
Zone name settings allow you to select zone name.
Override Set Time function can only be used in Dual Setpoint Control mode.
When timed override is used, the set time will be a default value.
OK
OK
OK
!
NOTE
Override Set Time function can only be used in a dual setpoint control mode.
!
NOTE
Zone name setting function may not work in some indoor unit products.
ENGLISH
Zone Name setting
82 FUNCTION SETTING
FUNCTION SETTING 83
Comfort cooling setting (air conditioner / DX ventilator)
Home Leave Set Temperature function is used in Dual Setpoint Control mode.
When customer operate as home leave mode, this setting temperature value will be applied.
It is the function to set the outdoor unit Comfort saving operation value.
• You can set the following values using [<,>(left/right)] button.
Value
Step 1
OK
Step 2
Step 3
!
NOTE
The Comfort cooling function does not work in the group control.
Comfort cooling setting function is only available in some products.
ODU Refrigerant Noise Reduction setting (air conditioner / DX ventilator)
It is the function to set the outdoor unit’s refrigerant noise reduction function.
• You can use [<,>(left/right)] button to set the following setting values as follows.
!
NOTE
Home Leave Set Temperature function can only be used in a dual setpoint control mode.
Value
!
Description
Step 0
Not use
Step 1
Outdoor unit noise mode 1
Step 2
Outdoor unit noise mode 2
NOTE
The ODU Refrigerant Noise Reduction function can be set only when the installer setting’s
outdoor unit function M/S setting is set to “Master”.
ODU Refrigerant Noise Reduction function is only available in some products.
ENGLISH
Home Leave Set Temperature Setting
84 FUNCTION SETTING
FUNCTION SETTING 85
Smart load control(SLC) setting (air conditioner / DX ventilator)
Change the outdoor unit’s defrost mode operation.
• Select value using [<,>(left/right)] button.
Change the outdoor unit’s Smart Load Control stage value.
(Smart load control is the function to calculate the indoor air temperature, outdoor air temperature, and humidity to operate effectivly.)
• In the function setting list, select the Smart load control category, and press [OK] button to
move to the detail screen.
Value
!
Step 0
Not use
Step 1
Forced snow removal
Step 2
Quick defrost
Step 3
Forced snow removal + quick defrost
OK
NOTE
The Defrost mode setting function can be set only when the installer setting’s outdoor unit
function M/S setting is set to “Master”.
Defrost mode setting function is only available in some products.
Off
Value
Step 0
Step 1
On
Step 2
Step 3
- When SLC is Operating, on the expanded screen’s monitoring information, ‘In Smart load control’ is displayed.
!
NOTE
Smart load control function can be set only when the installer setting’s outdoor unit function
M/S setting is set to “Master”.
Smart load control function is only available in some products.
ENGLISH
Defrost mode setting (air conditioner / DX ventilator)
86 FUNCTION SETTING
FUNCTION SETTING 87
Advanced fan speed “Auto” setting
It is the function to set the start and end time of the outdoor unit’s low noise mode operation.
• In the function setting list, select the Low Noise Mode Time category, and press [OK] button to
move to the detail screen.
- After setting the start time and the end time, press [OK] button to move to the upper level
list.
- If the start time and the current time are the same, it enters the outdoor unit low noise operation mode, and in the monitoring screen, ‘in outdoor unit low noise operation mode’ message
is displayed.
- If the end time and the current time are the same, the outdoor unit low noise operation mode
is cleared.
It is the function to set the indoor unit’s temperature based auto fan usage.
It is the function to automatically change the fan speed according to the difference between the
indoor temperature and the desired temperature.
• You can set the following setting values using [<,>(left/right)] button.
Value
Set
Clear
Description
Do not change the fan speed automatically
Change the fan speed automatically
OK
!
NOTE
Advanced fan speed “Auto” setting function is only available in some products.
!
NOTE
Low noise mode time setting function can be set only when the installer setting’s outdoor
unit function M/S setting is set to “Master”.
Low noise mode time setting function is only available in some products.
! CAUTION
If the function is not used, please set it to Off.
When you enter the low noise operation, the cooling capacity may be degraded.
ENGLISH
Low noise mode time setting (air conditioner / DX ventilator)
88 FUNCTION SETTING
FUNCTION SETTING 89
Midnight air cooling (ventilation interface)
It is the function to set the ventilation operation to start after the delay time.
• In the function setting list, select the delay time category, and press [OK] button to move to the
detail screen.
- After setting the minute, press [OK] button to move to the upper level list.
It is the function to discharge indoor air and supply cool outdoor air into the indoor during summer nights to save energy.
• In the function setting list, if you select midnight outdoor air cooling category and press [OK]
button, it moves to the detail screen.
- When you set the start and end time and press [OK] button, it saves and moves to the upper
level list.
OK
Value
0 ~ 60 Minutes
OK
!
NOTE
Whether to run the midnight air cooling is decided only when both air conditioner and
ventilation are stopped.
• Even if it is the set midnight air cooling time, it enters the midnight air cooling only when
the outdoor temperature conditions is met.
• During the midnight air cooling operation, “in midnight outdoor air cooling” message is
displayed on the monitoring screen.
• Midnight air cooling function may not work in some products.
! CAUTION
. If you do not use the function, please set it as off.
ENGLISH
Delay time (exclusive for ventilation)
90 FUNCTION SETTING
FUNCTION SETTING 91
ENGLISH
Human detection mode setting
It is the function that enables energy saving through the human detection power saving operation and wind direction setting.
In the function setting list, select human detection operation mode category and press [OK] button to move to the lower level setting list.
After selecting human detection wind direction category, you can set the following setting values
using [<,> (left/right)] button.
Value
OFF
Direct
OK
Indirect
!
Description
Do not use human detection wind direction control
Human detection direct wind operation
Human detection indirect wind operation
NOTE
Human detection operation setting function may not work in some products.
After selecting human detection power saving mode category, if you press [OK] button, it moves
to the detail screen.
You can select OFF ← → On/Off Power saving ← → Temperature power saving for mode value.
You can set the time value when you select On/Off power saving or Temperature power saving.
92 USER SETTING
USER SETTING 93
How to enter user setting
To enter the menu displayed at the bottom, you need to enter the user setting menu as follows.
• Select the setting category, and press [OK] button to move to the setting list.
• Select the user setting category, and press [OK] button to move to the user setting list.
Set the language to be displayed on the remote controller.
• In the user setting list, select the language category, and press [OK] button to move to the detail screen.
• After the setting, if you press [OK] button, the setting is saved and moves to the previous
screen.
OK
OK
User Setting
• You can set the product user functions.
• Some functions may not be available in some product types.
Menu
Language setting
Setpoint Type Setting
Temperature unit setting
Screen saver timer setting
LCD brightness in idle setting
External device setting
Date setting
Time setting
Summer time setting
Password setting
Schedule initialization
Theme setting
Description
Set the language to be displayed on the remote controller.
It is the function to set GUI type on the remote controller.
Set the temperature unit displayed on the remote controller.
Adjust the screen Off time of the remote controller.
Adjust the remote controller’s screen brightness.
Set the name of external equipment and equipment logic setting
Set the date displayed on the remote controller.
Set the time displayed on the remote controller.
Set the summer time in the remote controller.
Set the password to prevent unauthorized change to remote controller settings.
Initialize all timer settings in the remote controller.
Set the theme of the remote controller screen.
Humidity display
It is the function to decide whether to display humidity on the main
screen and additional information screen.
System reboot
Restart the remote controller.
Language
한국어
English
Deutsche
Italiano
Français
Español
Русский
Polskie
Português
中文
Čeština
ENGLISH
Language setting
USER SETTING
94 USER SETTING
USER SETTING 95
Temperature unit setting
It is the function to set GUI type on the remote controller.
* Dual setpoint type is a function that makes it possible to set the cooling and heating target temperature simultaneously. It is recommended for customers accustomed to using North American thermostats.
We recommend that you use it only in the region (North America).
If select dual setpoint option, target temperature ranges will be expanded and activated override, home leave, hold mode and occupancy information based schedule.
Set the temperature unit displayed on the remote controller.
• In the user setting list, select the temperature unit setting category, and press [OK] button to
move to the detail screen.
OK
<Dual setpoint>
<Single setpoint>
Value
1°C
Celsius
0.5°C
Fahrenheit
! CAUTION
The temperature unit function may not work or work differently in some products.
You cannot set the temperature unit in the slave wired remote controller.
ENGLISH
Setpoint Type Setting
96 USER SETTING
USER SETTING 97
LCD brightness in idle setting
Adjust the screen Off time of the remote controller.
• Select the following setting values using [<,>(left/right)] button.
Adjust the remote controller’s screen brightness.
• Select the following setting values using [<,>(left/right)] button.
Value
15sec
30sec (default)
! CAUTION
Selecting longer stand by screen will decrease LCD lifespan.
ENGLISH
Screen saver timer setting
Value
1min
0%
10%
(default)
20%
! CAUTION
Selecting brighter stand by screen will decrease LCD lifespan.
30%
98 USER SETTING
USER SETTING 99
External device types
Set the name of external equipment and equipment logic setting
• In the user setting list, select the external device setting category, and press [OK] button to
move to the detail screen.
It is the function to set the name of the External device attached to the remote controller.
• You can set the following setting values using [<,>(left/right)] button.
OK
Value
Motor Lighting
External device use
• In the external device setting list, select “External device use” category, and press [OK] button
to move to the external device use setting screen.
- If external device use setting value is use, you can see the control unit of external device in
main screen.
Value
Not use
Use
Fan
Heater
Pump
Others
ENGLISH
External device setting
100 USER SETTING
USER SETTING 101
Date setting
It is the function to set to use the information managed by the wired remote controller as the
contact point control condition to widen the usage of the contact point (Digital Output) installed in
the remote controller.
Set the date displayed on the remote controller.
• In the user setting list, select the date category, and press [OK] button to move to the detail
screen.
• After the setting, if you press [OK] button, the setting is saved and moves to the previous
screen.
• In the external device setting list, select the On/Off condition setting category, and press [OK]
button to move to the detail screen.
OK
OK
Condition 1
Condition 2
Condition 3
Condition 4
None
Deactivate
-
Deactivate
On
-
Aircon
Cool mode
-
Heat mode
-
Fan mode
-
Dry mode
-
Auto mode
-
External device name On
External device name Off
Over
Current Temp.
1°C~ 39.5°C
Occupied
-
-
Unoccupied
-
-
Under
• The External device operates as the operation set in the conditions 1~3.
• If the External device is set to auto while both ON condition and OFF condition are not set, contact point OFF is output.
• If the ON condition and OFF condition are the same, it is finally processed as OFF condition.
ENGLISH
On condition / Off condition
102 USER SETTING
USER SETTING 103
Summer time setting
Set the time displayed on the remote controller.
• In the user setting list, select the time category, and press [OK] button to move to the detail
screen.
• After the setting, if you press [OK] button, the setting is saved and moves to the previous
screen.
Set the daylight savings time dates in the remote controller.
• In the user setting list, select the summer time setting category, and press [OK] button to
move to the detail screen.
- Summer time: The system to advance the time by 1 hour from the spring when the day is
longer and return back in the fall when the day gets shorter.
- When it becomes AM 02:00 on the DST start date, the current time changes to AM 03:00,
and when it becomes AM 02:00 of the DST end date, the current time changes to AM 01:00.
OK
OK
ENGLISH
Time setting
104 USER SETTING
USER SETTING 105
Schedule initialization
Set the password to prevent unauthorized change to remote controller settings.
• Select the user password setting category, and press [OK] button to move to the detail screen.
- If the password is set, when you enter “menu – setting”, you need to input password to
enter the setting list.
- When you forgot the password, you can initialize the password using the installer setting’s
“password initialization”.
The initialized password is “0000”.
Initialize all timer settings in the remote controller.
• In the user setting list, select the schedule initialization setting category, and press [OK] button
to move to the detail screen.
- Press the check button to initialize the sleep/simple timer, on/off timer, schedule and exception date in the remote controller.
OK
OK
ENGLISH
Password setting
106 USER SETTING
USER SETTING 107
Humidity display
Set the theme of the remote controller screen.
• Select either white or black using [<,>(left/right)] button.
It is the function to decide whether to display humidity on the main screen and additional information screen.
You can use [<, > (left/right)] button to set the setting values (On or Off).
ON
Display humidity.
OFF
Do not display humidity.
Setting value
!
NOTE
If humidity display is `ON`, the displayed humidity is different according to the humidity
detection location setting (installer setting).
• Remote controller: remote controller humidity display.
• Indoor unit: If it receives indoor unit humidity, it displays the indoor unit humidity, and if it
does not receive indoor unit humidity, it does not display humidity.
ENGLISH
Theme setting
108 USER SETTING
SERVICE SETTING 109
ENGLISH
System restart
SERVICE SETTING
Restart the remote controller.
• In the user setting list, select the system restart setting category, and press [OK] button to
move to the detail screen.
- In the detail screen, when you press [OK] button, a popup message is displayed, press the
check button, to restart the system.
- For forced reset, press down [On/Off + Back] button for 5 seconds to restart the system.
How to enter service setting
To enter the menu displayed at the bottom, you need to enter the service setting menu as follows.
• In the menu screen, press [<,>(left/right)] button to select the setting category, and press [OK]
button to move to the setting list.
• In the setting list, select the service setting category, and press [OK] button to move to the
service setting list.
OK
OK
Service setting
• You can set the product service functions.
• Some functions may not be displayed/operated in some product types.
Menu
Description
Service contact
Check and input the service center phone number that you can call
when there is service issue.
Model Information
Check the indoor/outdoor product group and capacity information to
which the remote controller is connected.
RMC Version Information
Error History
Open Source License
Check the remote controller model name and software version.
View the connected indoor unit’s error history.
View the remote controller’s open source license.
110 SERVICE SETTING
SERVICE SETTING 111
Model information (air conditioner / DX ventilator)
Check and input the service center phone number that you can call when there is service issue.
• In the service setting list, select the service contact point and press [OK] button to move to the
detail screen.
• While “edit” button is selected, press [OK] button to move to the edit screen, change it, and
press [OK] button to change the service contact point.
Check the indoor/outdoor product group and capacity information to which the remote controller
is connected.
• In the service setting list, select the indoor/outdoor model information category, and press [OK]
button to move to the detail screen.
• Indoor unit capacity
- 1kWh = 1kBtu * 0.29307
kWh is the result calculated based on Btu, There may be a small difference between calculated and actual capacity.
Ex) If the indoor unit capacity is 18kBtu, it is displayed as 5kWh.
OK
OK
OK
ENGLISH
Service contact
112 SERVICE SETTING
SERVICE SETTING 113
Error history
Check the indoor/outdoor product group and capacity information to which the remote controller
is connected.
• In the service setting list, select the remote controller version information check category, and
press [OK] button to move to the detail screen.
View the connected indoor unit’s error history.
• In the service setting list, select ‘check error history’ category, and press [OK] button to move
to the detail screen.
- You can view up to 20 error instances sorted by date occurred.
OK
OK
ENGLISH
RMC Version Information
114 SERVICE SETTING
INSTALLATION 115
ENGLISH
Open source license
INSTALLATION
View the remote controller’s open source license.
• In the service setting list, select the open source license category, and press [OK] button to
move to the detail screen.
Installation of Remote Controller
• After fixing the remote controller installation plate on the desired location, fix it firmly with the
provided screws.
- If the installation plate is not flat on the surface, it may result in the controller being twisted
and cause a defect.
- If there is a mounting box, install the remote controller installation plate using the fixings holes
which suit, as in the below diagrams.
- Do not leave a gap with the wall or product loose after the installation.
OK
• The wired remote controller cable can be installed in 3 directions. Install to the suitable
direction according to the installation environment.
- Installation direction: Rear entry, top side, right side
- When you install the remote controller cable at the top side and right side, remove the remote
controller cable guide hole before the installation.
※ Use a long nose pliers to remove the guide hole.
• After removing the hole, trim the cut surface neatly.
‫ ڹ‬Top side guide groove
‫ ڹ‬Top side guide groove
‫ں‬Right side guide
groove
‫ں‬Right side guide
groove
‫ڸ‬Rear cable entry
• After fixing the remote controller top side on the installation plate attached to the wall as in the
following figure, press the bottom side to combine with the installation plate.
- Do not leave a gap in the top, bottom, left, and right side of the remote controller and the installation plate after combining them.
- Before combining with the installation plate, arrange the cables to avoid interference with the
circuit parts.
<Order of Combining>
Wall
Wall
116 INSTALLATION
INSTALLATION 117
ENGLISH
• When you remove the remote controller from the installation plate, insert a small flat head
screwdriver into the bottom side separation hole and turn clockwise to separate the remote
controller.
- There are 2 separation holes at the bottom part. Slowly separate one by one.
- Be careful not to damage the internal parts during the removal.
Group control
• It connects and controls 2 or more air conditioner indoor units to one wired remote controller.
※Connect using the group control cable.
Indoor unit Main PCB
Indoor unit 2
Slave
Indoor unit 1
Master
<Order of Separation>
Wall Side
RED(12V)
YELLOW(SIG)
BLACK(GND)
YELLOW(SIG)
BLACK(GND)
Indoor unit 3
Slave
YELLOW(SIG)
BLACK(GND)
OK
① Group control cable (PZCWRCG3): Connect to indoor unit’s wired remote controller connector
② Extension cable (PZCWRC1): Connect to No. ① cable and slave indoor unit’s wired remote
controller connector
• Use the connection cables to connect the indoor unit with the remote controller.
While No. ① cable is connected, connect No. ② cable.
DC 12 V
Red
Signal
Yellow
GND
Black
Please check if connector is normally connected.
1
Indoor
Unit side
OK
Connecting cable
• For the following cases, separately purchase and use the cables suitable for the situation.
- Do not install the cable over 50 m. (It may cause communication issues.)
- If the distance between the wired remote controller and the indoor unit is 10 m or more : 10
m extension cable (model name: PCW-QE10A)
- If you control several indoor unit products with one wired remote controller : Group control
cable (model name: PCW-QG00A)
!
NOTE
During the wired remote controller installation, do not bury it in the wall. (It may cause
temperature sensor failure.)
Do not install the cable over 50 m. (It may cause communication defect.)
When you install the extension cable, carefully check the direction of the connectors on the
remote controller side and the product side before the installation.
Extension cable specification: Use 2547 1007 22# 2core 3shield, 5 Ø or equivalent or higher
level
!
2
NOTE
• Connect only GND and signal cable to the indoor unit set as slave. (If power cable is also
connected, it may cause loss of communication)
• Inquiries related to the purchase of the cable shall be directed to the specialized company
and the service center.
• After checking the existence of the event communication in the product manual, change
master/slave of the remote controller.
※For details, refer to ‘remote controller master/slave’ contents.
• Change master/slave of the indoor unit.
- For ceiling cassette and duct product group, change the setting with the indoor unit PCB
switch.
Master
GND
Signal cable
12V
Slave
Slave
No. 3 switch OFF: master (factory ship-out based)
Black
Yellow
Red
GND Signal cable
OK
No. 3 switch ON: slave
118 INSTALLATION
- After completing the master/slave setting in the indoor unit product, turn Off the power of the
indoor unit product, and turn On the power after 1 minute.
!
NOTE
• During the group control, set only 1 indoor unit as master.
• During the group control, some functions other than the basic operation setting, fan speed
Low/Med/High, remote controller lock setting, and time setting may be limited.
• During the individual control, if the master indoor unit Dip switch is set to slave, malfunction
may occur.
INSTALLATION METHOD TO USE EXTERNAL
DEVICE
Cable connection method to use external device
1) Wired remote controller-cable connection method.
- In the wired remote controller, connect the part marked in the following figure (J02C, DOPort) to the cable.
- According to the installation environment, there are 3 directions (Rear entry, top side, and
right side) for the installation.
2) Cable extension connection method
- Among the cables connected to the wired remote controller, cut the remaining connectors
on the other side, and then extend and connect the cables
- Extension cable specification: 24~26AWG.
! CAUTION
For the External device connection, use the cable insulated with sheath for the extension connection.
Before combining with the installation plate, arrange the cables to avoid interference with the internal parts.
RMC
DO-Port
30cm
2
(GND_Black)
3
(DC 12 V_Red)
Remote
controller
product
composition
• Output specification
- Voltage : DC 11~12V
- Current : 5mA
Field connection
ENGLISH
- For the details on the wireless remote controller master/slave setting changes, refer to the
wireless remote controller manual.
INSTALLATION METHOD TO USE EXTERNAL DEVICE 119
120 AIR CONDITIONER AND VENTILATION INTERFACE
INSTALLER SETTING 121
• It controls using the wired remote controller at a place where the air conditioner indoor unit and
the ventilation product are connected and installed at the same time.
- When the power is applied, the remote controller recognizes the product and operates normally.
Independent operation
Interfaced operation
[general ventilation
independent operation]
[General ventilation interfaced operation]
General
ventilation
General
ventilation
OK
Wired
remote
controller
[Direct ventilation
independent operation]
Air conditioner
indoor unit
OK
Wired
remote
controller
INSTALLER SETTING
How to enter installer setting
! CAUTION
The installer setting mode is the mode to set the remote controller’s detail function. If the installer setting mode is incorrectly set, it may cause product failure, user’s injury, or property damage. It must be set by the installation specialist with the installation license, and if it is installed or
changed without installation license, all problems caused will be the responsibility of the installer,
and may void the LG warrenty.
• In the menu screen, press [<,>(left/right)] button to select the setting category, and press
[∧(up)] button for 3 seconds to enter the password input screen for the installer setting.
• Input the password and press [OK] button to move to the installer setting list.
Wired
remote
controller
OK
[Direct ventilation interfaced operation]
General
ventilation
Direct
ventilation
General
ventilation
ENGLISH
AIR CONDITIONER AND VENTILATION INTERFACE
Air conditioner
indoor unit
OK
General
ventilation
Wired
remote
controller
※The wiring method is the same as the air conditioner user manual. (Refer to the remote controller manual group control page contents)
※Ventilation product means general ventilation product and direct cooling type ventilation product.
OK
OK
※Installer setting password
Main screen → menu → setting → service → RMC version information → SW Version
Example) SW version : 1.00.1 a
In the above case, the password is 1001.
!
NOTE
Some categories of the installer setting menu may not be available depending on the
product function or the menu name may be different.
122 INSTALLER SETTING
INSTALLER SETTING 123
• You can set the product user functions.
• Some functions may not be displayed/operated in some product types.
Menu
Description
Test run setting
It is the function to set the trial operation at the initial product installation.
Central control address
Setting
It is the function to set the central control address of the indoor unit
during the central controller connection.
ESP setting
It is the function to set the wind amount value corresponding to each
wind amount for easy installation.
Temperature sensor setting
It is the function to select the temperature sensor that will decide the
indoor temperature.
Ceiling height setting
It is the function to control the wind amount stage according to the
ceiling height for the ceiling type products.
Static pressure setting
The fixed pressure setting can be set only in the duct products.
It cannot be set in other products.
RMC master/slave setting
Override master/slave setting
Menu
Description
Guard timer
It is a function that sets the minimum running time of outdoor unit
cycle mode when switching from cooling mode to heating mode and
vice versa during Auto Operation mode.
Fan speed in Cooling thermal It is a function that sets the indoor unit fan movement, in cooling
off
mode, when thermal is off.
Primary heater setting
It is the function to set the heater usage to have higher priority over
the outdoor unit cycle during the indoor unit heating operation.
Air conditioner Fan operation It is the function to set whether to operate the air conditioner fan durinterlocked with ventilation ing the interface operation of the air conditioner and the ventilation
setting
product.
Indoor unit Auto-Start
setting
It is a function that sets whether to restore the indoor unit operation
by resuming the previous power-on state or as power-off state in the
power failure compensation.
Occupancy duration time
setting
It is the function to set the occupied decision maintaining time among
the occupied sensor values.
It is the function to set group control or 2-remote controller control.
CN_CC setting
The operation master / slave selection function is to avoid other mode
operations, and it is the function to prevent the selection of the opposite mode of the indoor unit set as master by the indoor units set as
slaves.
It is the function to set whether to install (use) Dry Contact.
(It is not a function for Dry Contact installation, but it is a function to
set the usage of the indoor unit’s CN_CC port.)
CN_EXT setting
It is the function to set the indoor unit’s Dry Contact Port to control external input and output according to DI/DO set by the customer. (It is
the function to decide the usage of the contact point port (CN_EXT)
mounted in the indoor unit PCB.)
Dry contact mode setting
Dry contact function is the function that can be used only when the
dry contact devices is separately purchased and installed.
Fixed air volume
It is the function to apply different fan speeds automatically for each
thermal control status.
Zone Type Setting
It is possible to setup zone new type or old one of the product which
is available to install the damper controller.
Zone Number Setting
Zone Number is to set the number of installed zones. It's possible to
control only in zone new type.
ODU function master setting It is the function to set the outdoor unit’s function Master / Slave.
Fan continuous operation
setting
It is the function to set the indoor unit’s continued Fan function usage.
It is the function to maximize the cooling/heating efficiency by the outdoor unit operating the indoor unit fan operation longer than the previous operation method.
Low noise mode priority
setting
It is the function to set the main agent of the low noise mode control.
(It is the function to set only one of the outdoor unit / remote controller can control the low noise operation.)
Emergency Heater setting
It is the function to set whether to use emergency heater control function and the usage environment.
Func. control during grp.
Control setting
It is the function to set common functions or some functions to be
controlled by the master indoor unit standard during the group control.
Option Kit – Plasma / Heater /
Humidification / Elevation grill
/ Ventilation / Refrigerant leakage detection sensor
It is the function to set whether to mount option unit (Plasma / Humidification / Heater / Ventilation / Elevation grill / Aux Heater / Refrigerant
leakage detection sensor) when it is additionally installed or removed
after the mass production.
Humidity sensing position
ODU cycle priority
It is the function to set the location to detect humidity.
This function can select standby mode or priority cooling.
Outdoor temp. for heating
stages
This function can select outdoor temperature values for use reference
point of heater and heating mode operation.
Expand of Temperature Range
This function is used for select setting temperature range option.
Estimated energy display
This function can set to display energy data which ODU estimated.
Indoor unit address verification
This function allows you to check the address of the indoor unit designated by the outdoor unit.
Static pressure step setting
This is the function that static pressure of the product is divided in 11
steps for setting.
Human detection sensor set- It is the function to set whether to install human detection sensor and
ting
operation standard value.
Password initialization
It is the function to initialize (0000) the password when you forgot the
password set in the remote controller.
ENGLISH
Installer setting – air conditioner
124 INSTALLER SETTING
INSTALLER SETTING 125
Test run setting (air conditioner / DX ventilator)
• You can set the product user functions.
• Some functions may not be displayed/operated in some product types.
After product installation, the Test run must be performed. For Test run related details, refer to
the product manual.
• In the installer setting list, select the Test run setting category, and press [OK] button to move
to the detail screen.
- You can select ‘cooling Test run / heating Test run’
- During the Test run, if you start the following functions, the Test run stops.
☞ Operation mode, desired temperature, fan speed, wind direction, start/stop
Menu
Test run setting
Central control address Setting
Applied products
Description
DX(Direct Exchanger) Type It is the function to set the trial operation at the initial product installation.
General
Air supply ESP
General/DX Type
Air discharge ESP
It is the function to set the central control address of the indoor unit during
the central controller connection.
It is the function to set the fan speed value corresponding to the air supply
side fan speed.
It is the function to set the fan speed value corresponding to the air discharge side fan speed.
Temperature sensor setting
DX Type
It is the function to select the temperature sensor that will decide the indoor
temperature.
Product direction
General
It is the function to set the ventilation indoor unit’s installation direction.
Express ventilation priority
General/DX Type
RMC master/slave setting
It is the function to set the priority of the air supply and discharge during the
express ventilation operation.
It is the function to set group control or 2-remote controller control.
DX Type
The operation master / slave selection function is to avoid other mode operations, and it is the function to prevent the selection of the opposite mode
of the indoor unit set as master by the indoor units set as slaves.
Dry contact mode setting
DX Type
Dry contact function is the function that can be used only when the dry contact devices is separately purchased and installed.
Fixed fan speed setting
DX Type
It is the function to set the indoor unit’s fan speed option to variable or fixed.
Hum. Of Stand-alone Vent.
Mode
General/DX Type
It is the function to set whether to use the humidification function in the direct cooling type ventilation’s ventilation single operation.
Hum. Of Vent. With Heating
Oper.
DX Type
It is the function to set the direct cooling type ventilation’s heating humidification function as auto or manual.
Vent. Fan Speed Alignment
General
It is the function to increase/decrease ventilation’s standard fan speed from
the current status according to the field environment.
Indoor unit address verification
DX Type
This function allows you to check the address of the indoor unit designated
by the outdoor unit.
Indoor unit Auto-Start setting
DX Type
It is a function that sets whether to restore the indoor unit operation by resuming the previous power-on state or as power-off state in the power failure compensation.
CN_EXT setting
DX Type
It is the function to set the indoor unit’s Dry Contact Port to control external
input and output according to DI/DO set by the customer. (It is the function
to decide the usage of the contact point port (CN_EXT) mounted in the indoor unit PCB.)
ODU function master setting
DX Type
It is the function to set the outdoor unit’s function Master / Slave.
Low noise mode priority setting
DX Type
It is the function to set the main agent of the low noise mode control. (It is
the function to set only one of the outdoor unit / remote controller can control the low noise operation.)
Override master/slave setting
OK
ENGLISH
Installer setting - ventilator
126 INSTALLER SETTING
INSTALLER SETTING 127
ESP setting (air conditioner / general, DX ventilator)
It is the function to set the central control address of the indoor unit to allow communication with
a central controller,
• In the installer setting list, select the central control address setting category, and press [OK]
button to move to the detail screen.
- Select a hex value between 00 and FF.
Value 1: group address setting / value 2: indoor unit address setting
It is the function to set the fan speed value corresponding to each fan speed for easy installation.
OK
!
NOTE
If ESP is incorrectly set, the air conditioner may malfunction.
This function must be set by the installation specialist that holds an installation license.
For ventilation products, separate ESP values are used for the supply and exhaust fans.
OK
• In the installer setting list, select the ESP setting category, and press [OK] button to move to
the detail screen.
Product
ESP fan speed
value
Slow
Low
Air conditioner
Med
High
Power
0 ~ 255
Low
Ventilation
High
Power
!
NOTE
Be especially careful not to switch ESP values corresponding to each fan speed.
Engineering manuals have ESP setting tables that reference air flow and corresponding
value setting to achieve the flow.
The ESP values that can be set may be different for each product and capacity.
ENGLISH
Central control address setting (air conditioner / DX ventilator)
128 INSTALLER SETTING
INSTALLER SETTING 129
Ceiling height setting (air conditioner)
It is the function to control the fan speed stage according to the ceiling height in the ceiling type
product.
• You can set the following setting values using [<,>(left/right)] button.
Temperature sensor location
Description
Remote controller
Operate the system with wired remote controller’s temperature
sensor
Indoor Unit
Ceiling height
Low
Operate the system with indoor unit’s temperature sensor
Cool
2TH
Heat
Standard
Compare the temperatures of the indoor unit and the wired remote controller and operate with the higher temperature
(There are system operated with lower temperature)
Compare the temperatures of the indoor unit and the wired remote controller and operate with the lower temperature
• 2TH function’s operation characteristics may be different for each product.
!
Description
Fan speed operates one step slower than the default value.
Operates at the default fan speed
High
Fan speed operates one step faster than the default value.
Very high
Fan speed operates two steps faster than the default value.
NOTE
When group control is enabled some functions are limited depending on product type.
ENGLISH
Temperature sensor(2TH) setting (air conditioner / DX ventilator)
It is the function to select the temperature sensor to decide the indoor temperature.
• You can set the following setting values using [<,>(left/right)] button.
130 INSTALLER SETTING
INSTALLER SETTING 131
Static pressure setting can be set only in the duct products. (It cannot be set in other products.)
• You can set the following setting values using [<,>(left/right)] button.
Remote controller master / slave setting
(air conditioner / General, DX ventilator)
This function sets configuration for the master/slave setting through the remote controller.
• Change setting values using [<,>(left/right)] button.
Description
Static pressure
Variable / Fixed
ESP default value
Variable high static pressure
V-H
Variable
High static pressure(High)
Fixed high static pressure
F-H
Fixed
High static pressure(High)
Variable low static pressure
V-L
Variable
Low static pressure(Low)
Fixed low static pressure
F-L
Fixed
Low static pressure(Low)
• 2TH function’s operation characteristics may be different for each product.
M/S
Description
Master (default)
Using group control, the indoor units are operated based on the remote controller.
Slave
Using group control, all remote controllers except 1 master remote
controller are set as slaves.
• 2TH function’s operation characteristics may be different for each product.
ENGLISH
Static pressure setting(air conditioner)
132 INSTALLER SETTING
INSTALLER SETTING 133
The operation master / slave selection function is to avoid other mode operations, and it is the
function to prevent the selection of opposite mode of the indoor unit master by the indoor units
set as slaves.
• Change setting values using [<,>(left/right)] button.
Dry contact mode setting (air conditioner / DX ventilator)
Dry contact function is the function that can be used only when the dry contact devices is separately purchased and installed.
• Change setting values using [<,>(left/right)] button.
Value
Auto
M/S
Master
Slave
!
Description
manual
Using group control, this master sets the mode of slave IDU’s.
For the indoor unit set as slave, it can only select the some operation
mode of the master indoor unit cycle.
Ex) Master is in cooling cycle, Slave can select cooling, dehumidification, auto, and wind only
Master is in heating cycle, Slave can select auto, heating, and wind
only
NOTE
Override M/S setting function is only available in some products.
!
NOTE
For dry contact mode related detail functions, refer to the individual dry contact manual.
What is dry contact?
It means the contact point signal input when the hotel card key, human body detection
sensor, etc. are interfacing with the air conditioner.
Added system functionality by using external inputs (dry contacts and wet contacts).
ENGLISH
Override Master/Slave setting (air conditioner / General, DX
ventilator)
134 INSTALLER SETTING
INSTALLER SETTING 135
Zone Type Setting(air conditioner)
It is the function to apply different fan speeds automatically for each thermal control status.
• You can set the following setting values using [<,>(left/right)] button.
This function is only available on some products.
This function select a type of zone control type which indoor unit support as 'new type' or 'old
type'.
Value
Comp on
Comp off
Variable
Set fan speed
Low
Fixed
Set fan speed
Set fan speed
Value
Old
New(4 Zone)
New(8 Zone)
Zone Number Setting(air conditioner)
This function is only available on some products.
Zone Number is to set the number of installed zones. It's possible to control only in zone new
type.
Value
New(4 zone) : 2~4
New(8 zone) : 2~8
ENGLISH
Fixed air volume (air conditioner / DX ventilator)
136 INSTALLER SETTING
INSTALLER SETTING 137
Function control during group Control setting (air conditioner)
Enable the emergency heater control function and the usage environment.
• In the installer setting list, select the emergency heater setting category, and press [OK] button
to move to the detail screen.
- In case of an error, it sets whether the emergency heater can be used / outdoor temperature
standard heater operation usage setting and temperature step value setting / and during the
emergency heater operation, whether to use the indoor unit fan operation.
This function enables the control of the common functions or some functions based on the master indoor unit during the group control.
• Change setting values using [<,>(left/right)] button.
OK
!
Value
Description
Not use
Common function,
Use
Use expanded function which
is based on master indoor unit
NOTE
Common functions and some indoor unit master standard setting shall be set only during
the group control with the same type indoor units.
During the group control with different indoor unit types, set it as ‘000’ to use the existing
group control method.
Value
Outdoor temperature standard heater
operation
Fan operation in emergency
control
-
-
Not use
Use
!
Emergency heater
Step 0 ~ 3
Extended emergency heater
Step 0 ~ 15
On/Off
NOTE
This function setting must be carried out by a certified-technician.
ENGLISH
Emergency heater setting (air conditioner)
138 INSTALLER SETTING
INSTALLER SETTING 139
Expand of Temperature Range (air conditioner)
At the Code field, select when air cleaner/heater/humidifier/elevation grill/ventilation KIT/Aux
Heater/refrigerant leakage detection sensor are newly installed to the indoor unit or when an installed KIT is removed.
• You can set the following setting values using [<,>(left/right)] button.
This function using in dual setpoint control mode.
This function is used for select setting temperature range option.
Value
Function
Clear : 60~86 °F / 16~30 °C (default)
Value
Set : 40~99 °F / 4~37.5 °C
Plasma purification
Heater
!
Humidifier
Elevation grill
Ventilation Kit
Aux Heater
Refrigerant leakage detection sensor
Not install / Install
NOTE
When the set values are changed, the items below will be initialized.
- Target temperature (default: Cooling: 86 °F(30 °C)/ Heating: 60 °F(16 °C))
'home leave' temperature (default: Cooling: 86 °F(30 °C)/ Heating: 60 °F(16 °C))
In case of the setting expanded temperature range (set), please note that the setting of the
wired remote controller can be altered under below circumstances.
- In case of cooling at 30~37.5 °C(64~99 °F), it is changed to cooling at 86 °F(30 °C).
- In case of heating at 4~15.5 °C(40~86 °F), it is changed to heating at 60 °F(16 °C).
- If set on dual setpoint, it is changed to the current operation mode(cooling or heating) of
the indoor unit.
Situation where changes in the setting occur
a. Operates the Auto address work and pipe search in situations such as product installment
and service.
b. Occurrence of errors and deactivation.
c. Command generated by the central control, outdoor unit, Dry contact, Remote controller,
indoor unit switch.
ENGLISH
External devices of indoor unit setting (air conditioner)
140 INSTALLER SETTING
141
Static pressure step setting (air conditioner)
This function allows you to check the address of the indoor unit designated by the outdoor unit.
• In the installer setting list, select the indoor unit address check category, and press [OK] button
to move to the detail screen.
It is the function to subdivide and set the product’s Static pressure to 11 stages.
• Change setting values using [<,>(left/right)] button.
OK
Value
Step 0 ~ Step 11
!
NOTE
If Static pressure step setting is used, the Static pressure setting is not used.
For the Static pressure step value for each stage, refer to the indoor unit product manual
ENGLISH
Indoor unit address verification (air conditioner / DX ventilator)
142 INSTALLER SETTING
INSTALLER SETTING 143
Fan speed in Cooling thermal off (air conditioner)
It is a function that sets the minimum running time of outdoor unit cycle mode when switching
from cooling mode to heating mode and vice versa during Auto Operation mode.
Under the condition of cooling/heating switching, it switches between cooling and heating mode
after operation during the time scheduled in the Guard timer.
Indoor unit fan, in cooling mode, during thermal off condition.
• Select value using [<,>(left/right)] button.
Value
Step
Value
Low
0
0 minute
Off
Fan speed low
Fan off
1
15 minutes
Setting
fan speed setting value
2
30 minutes
3
45 minutes
4
60 minutes
ENGLISH
Guard timer(air conditioner)
144 INSTALLER SETTING
INSTALLER SETTING 145
It is the function to set the air conditioner fan operation if the ventilation is operated while the air
conditioner operation is stopped when the air conditioner and the ventilation are installed to interface with each other.
• You can set the following setting values using [<,>(left/right)] button.
Value
Not use
Use
Air conditioner Fan operation interlocked with ventilation setting
(air conditioner)
It is the function to set the air conditioner fan operation if the ventilation is operated while the air
conditioner operation is stopped when the air conditioner and the ventilation are installed to interface with each other.
• You can set the following setting values using [<,>(left/right)] button.
Description
During the heating, heater is set to be used as secondary
During the heating, heater is set to be used as main
Value
Description
Off
The air conditioner indoor unit Fan is Off during the ventilation interface
On
The air conditioner indoor unit operates in very weak wind during the ventilation interface
- When the air conditioner operation is Off, if the ventilation product is in operation, the air conditioner fan shall be operated, and when the fan is in operation, dust may fall, so it is the function
to set the air conditioner fan operation status in case of ventilation interface through the setting.
ENGLISH
Primary heater setting(air conditioner)
146 INSTALLER SETTING
INSTALLER SETTING 147
Occupancy duration time setting(air conditioner)
It is a function that sets whether to restore the indoor unit operation by resuming the previous
power-on state or as power-off state in the power failure compensation.
• You can set the following setting values using [<,>(left/right)] button.
It is a function that sets the light-on/occupancy duration after motion is detected when installing
an occupancy sensor.
• You can set the following setting values using [<,>(left/right)] button.
Value
Use
Not use
Description
Use indoor unit auto restart
Not use indoor unit auto restart
Value
0 Minute
10 Minutes
30 Minutes
60 Minutes
ENGLISH
Indoor unit Auto-Start setting (air conditioner / DX ventilator)
148 INSTALLER SETTING
INSTALLER SETTING 149
CN_EXT setting (air conditioner / DX ventilator)
It is the function to set the usage of the indoor unit’s CN_CC port.
• Select CN_CC setting category, and press [OK] button to move to the detail screen.
It is the function to set to control the external input and output according to DI/DO set by the customer using the indoor unit’s Dry Contact Port. (It is the function to decide the usage of the contact point port (CN_EXT) mounted in the indoor unit PCB.)
• In the installer setting list, select CN_EXT setting category, and press [OK] button to move to
the detail screen.
OK
OK
Value
Description
DC auto install
(default)
When power is applied to the product, indoor unit when the contact
point is on in Dry Contact installed state recognizes Dry Contact installation
DC manual not install
DC manual install
Do not use (install) Dry Contact
Use (install) Dry Contact
Programmable DI/DO Use as Programmable DI/DO (Simple On/Off)
!
NOTE
CN_CC is the device connected to the indoor unit to recognize and control the external
contact point.
Value
Description
Not use
(default)
Use installer code No. 41 setting value (simple Dry Contact setting
value)
Simple operation
control
Simple operation On/Off
Single emergency stop
Indoor unit single emergency stop
Occupied / Unoccupied
Occupied / Unoccupied
All emergency stop
Indoor unit all emergency stop
※It can be set only when there is indoor unit emergency stop
function.
ENGLISH
CN_CC setting (air conditioner)
150 INSTALLER SETTING
INSTALLER SETTING 151
It is the function to set the outdoor unit’s function Master / Slave.
• You can set the following setting values using [<,>(left/right)] button.
Value
Slave
Master
Description
Cannot enter the Smart load control function setting
Cannot enter the low noise operation time setting
Cannot enter the refrigerant noise reduction setting
Cannot enter the defrost mode setting
Smart load control function setting is possible
Low noise operation time setting is possible
Refrigerant noise reduction setting is possible
Low noise operation control main agent setting is possible
Defrost mode setting is possible
! CAUTION
※When you change the outdoor unit function master setting from master to slave, check the operation status of the outdoor unit function (outdoor unit low noise operation, smart load control)
and make sure to stop the outdoor unit function before the change.
Fan continuous operation setting (air conditioner)
It is the function to set the indoor unit’s continued fan function usage. (It is the function to maximize the cooling/heating efficiency by the outdoor unit operating the indoor unit fan operation
longer than the previous operation method.)
• You can set the following setting values using [<,>(left/right)] button.
Value
Clear
Set
Description
Do not use continued fan usage
Use continued fan usage
ENGLISH
Outdoor unit function master setting (air conditioner / DX ventilator)
152 INSTALLER SETTING
INSTALLER SETTING 153
Human detection sensor
It is the function to set the low noise mode control main agent. (It is the function to set that only
one of the outdoor unit / remote controller can control the low noise operation.)
• You can set the following setting values using [<,>(left/right)] button.
It is the function to set whether to install human detection sensor and operation standard value.
• In the installer setting list, after selecting human detection sensor setting category, if you press
[OK] button, it moves to the detail screen.
Value
Description
RMC
Ignore the outdoor unit PCB’s low noise operation Switch Setting value
- Function setting – remote controller low noise operation time menu deactivation
ODU(default)
It is controlled in the outdoor unit itself according to the outdoor unit
PCB’s low noise operation Switch Setting value
- Function setting – remote controller low noise operation time menu deactivation
• You can set the following setting values for each category using [<,> (left/right)] button.
Value
Description
Installation status
Not installed, basic installation, 90º rotation installation
Detection result sending cycle
5 s, 30 s, 1 min., 3 min.
Sensitivity setting
Standard, low sensitivity, high sensitivity
ENGLISH
Low Noise Mode Priority setting (air conditioner / DX ventilator)
154 INSTALLER SETTING
INSTALLER SETTING 155
ODU cycle priority (airconditioner)
It is the function to set the location to detect humidity.
You can use [<, > (left/right)] button to set the following setting values.
This function can set cycle priority of outdoor unit.
Multi V Heat Pump system does not support mixed mode therefore wired remote controller can
not show opposite operation mode for select option while ODU operate cooling or heating cycle.
Set this function user can select opposite operation mode with wired remote controller and indoor units enter to ‘standby’ status or outdoor unit can support cooling first and operate heating
with heater.
Value
Description
Remote controller (default value)
Humidity sensor of the remote controller itself
Indoor unit
Humidity received from indoor unit
OK
ENGLISH
Humidity sensing position (air conditioner)
156 INSTALLER SETTING
INSTALLER SETTING 157
Description
Not use
Does not support opposite cycle operation using wired remote controller
- When ODU operate as cooling cycle selectable operation modes with
wired remote controller are cool, auto, dehumidification and fan.
- When ODU operate as heating cycle selectable operation modes with
wired remote controller are heat, auto and fan
Standby
When user set opposite operation mode using wired remote controller indoor unit stop thermal operation and fan.
Cool
Cooling cycle has a priority.
When user change operation mode of specific indoor unit to cooling on
heating cycle, outdoor unit change cycle to cooling and Indoor unit keep
heating operation using heater.
h Please set emergency heater and aux heater function before using this
option
Outdoor temp. for heating stages (air conditioner)
It is a function that sets outdoor temperature values for two stage heating.
if user set outdoor temperature T1 and T2, Indoor unit will select heating stage between Indoor
unit operation and heater operation.
h When user select cooling option, additional setting menu will be activated.
The additional timer setting menu is for setting minimum cooling operation period.
Once outdoor unit change over to cooling by cooling priority, outdoor unit can change over to
heating after set time.
Setting value
Step 0
Step 1
Step 2
Step 3
Step 4
OK
Cooling operation time
45 min.(default)
30 min.
60 min.
90 min.
120 min.
T1 Value
T2 Value
-23 ~ 16 °C (-10 ~ 60 °F)
-23 ~ 51 °C (-10 ~ 130 °F)
ENGLISH
Option
158 INSTALLER SETTING
INSTALLER SETTING 159
Password initialization (air conditioner / general, DX ventilator)
This function can set to display energy data which outdoor unit estimated power consumption
data without wattmeter.
It is the function to initialize (0000) when you forgot the password set in the remote controller.
• In the installer setting list, select the password initialization setting category, and press [OK]
button to move to the detail screen.
• When you press “initialization” button, a popup screen appears, and when you press “check”
button, password initialization starts, and the user password is changed to 0000.
Setting value
Use
Not Use
Description
Display energy consumption data which outdoor unit estimated
Not display energy consumption data which outdoor unit estimated
OK
ENGLISH
Estimated energy display (airconditioner)
160 INSTALLER SETTING
INSTALLER SETTING 161
Express ventilation priority (general , DX ventilator)
It is the function to set the direction of the ventilation product.
• Select value using [<,>(left/right)] button.
It is the function to set the priority of the air supply and air discharge during the express ventilation operation.
• Select value using [<,>(left/right)] button.
Value
Normal
Value
Reverse
Priority in air supply
Priority in air discharge
ENGLISH
Product direction (general ventilator)
162 INSTALLER SETTING
INSTALLER SETTING 163
Humidification of ventilation with heating operation
(DX ventilator)
It is the function to set whether to use the humidification function during the ventilation product
single operation.
• Select value using [<,>(left/right)] button.
It is the function to set the heating humidification function of the direct ventilation to be automatic or manual.
• Select value using [<,>(left/right)] button.
Value
Not use
Value
Use
Not use
Use
ENGLISH
Humidification of stand-alone ventilation mode (general , DX
ventilator)
164 INSTALLER SETTING
GUIDE TO DIFFERENT MODE OPERATION/OPEN SOURCE SOFTWARE 165
It is the function to change the standard fan speed of the ventilation product.
• Select value using [<,>(left/right)] button.
GUIDE TO DIFFERENT MODE
OPERATION/OPEN SOURCE SOFTWARE
Different mode operation
Different mode operation is the case when the indoor units’ operation modes are different when
multiple indoor units are installed to one outdoor unit. (Different mode operation doesn’t happen
in the cooling exclusive model.)
• Example of different mode operation
- When one indoor unit is operated in heat while several indoor units one outdoor unit are operated in cooling, the heating operation is not performed.
- With one outdoor unit, while several indoor units are in heat mode, if one indoor unit requests
in cooling or dehumidification, the operation is not performed.
Open Source License Notice Information
Value
Default value
10% increase
10% decrease
20% decrease
To obtain the source code under GPL, LGPL, MPL, and other open source licenses, that is contained in this product, please visit http://opensource.lge.com. In addition to the source code, all
referred license terms, warranty disclaimers and copyright notices are available for download.
LG Electronics will also provide open source code to you on CD-ROM for a charge covering the
cost of performing such distribution (such as the cost of media, shipping, and handling) upon
email request to opensource@lge.com. This offer is valid for three (3) years from the date on
which you purchased the product.
ENGLISH
Ventilation Fan Speed Alignment(DX ventilator)